Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2024-07-03 12:21:28
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 12096.35 | 1066.20 | 1066.20 |
Net Site Energy | 12096.35 | 1066.20 | 1066.20 |
Total Source Energy | 27219.91 | 2399.23 | 2399.23 |
Net Source Energy | 27219.91 | 2399.23 | 2399.23 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 828.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1162.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 322.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1661.82 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 841.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1210.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2706.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6772.67 | 5323.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 28.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 800.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1162.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 322.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 15.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 11.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1210.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 4.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 2706.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 20.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 828.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1162.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 322.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1661.82 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 841.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1210.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 4.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 2706.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 162.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 209.49 | 311.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.55 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 596.96 | 469.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 162.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 209.49 | 311.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.55 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 596.96 | 469.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6772.667 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6772.667 | 100.00 |
Total On-Site and Utility Electric Sources | 6772.667 | 100.00 |
Total Electricity End Uses | 6772.667 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 65.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7994.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 PTAC COOLING COIL | ROOM_2_FLR_3 PTAC COOLING COIL | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | ROOM_5_FLR_3 PTAC COOLING COIL | ROOM_6_FLR_3 PTAC COOLING COIL | ROOM_1_FLR_6 PTAC COOLING COIL | ROOM_2_FLR_6 PTAC COOLING COIL | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | PTAC_3 PTAC COOLING COIL | PTAC_6 PTAC COOLING COIL | VAV_FLR_1 COOLING COIL | VAV_FLR_6 COOLING COIL | VAV_FLR_0 COOLING COIL | PSZ_LAUNDRY COOLING COIL | PSZ_CAFE COOLING COIL | PSZ_KITCHEN COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_FLR_1 HEATING COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | VAV_FLR_6 HEATING COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 HEATING COIL | ROOM_2_FLR_3 HEATING COIL | ROOM_3_MULT19_FLR_3 HEATING COIL | ROOM_4_MULT19_FLR_3 HEATING COIL | ROOM_5_FLR_3 HEATING COIL | ROOM_6_FLR_3 HEATING COIL | ROOM_1_FLR_6 HEATING COIL | ROOM_2_FLR_6 HEATING COIL | ROOM_3_MULT9_FLR_6 HEATING COIL | VAV_FLR_0 HEATING COIL | PTAC_3 HEATING COIL | PTAC_6 HEATING COIL | PSZ_LAUNDRY HEATING COIL | PSZ_CAFE HEATING COIL | PSZ_KITCHEN HEATING COIL | ROOM_1_FLR_3 PTAC COOLING COIL | ROOM_2_FLR_3 PTAC COOLING COIL | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | ROOM_5_FLR_3 PTAC COOLING COIL | ROOM_6_FLR_3 PTAC COOLING COIL | ROOM_1_FLR_6 PTAC COOLING COIL | ROOM_2_FLR_6 PTAC COOLING COIL | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | PTAC_3 PTAC COOLING COIL | PTAC_6 PTAC COOLING COIL | VAV_FLR_1 COOLING COIL | VAV_FLR_6 COOLING COIL | VAV_FLR_0 COOLING COIL | PSZ_LAUNDRY COOLING COIL | PSZ_CAFE COOLING COIL | PSZ_KITCHEN COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| VAV_FLR_1 FAN | VAV_FLR_6 FAN | VAV_FLR_0 SZVAV FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | LAUNDRY_FLR_1 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3_PTAC_SUPPLY FAN | ROOM_2_FLR_3_PTAC_SUPPLY FAN | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | ROOM_5_FLR_3_PTAC_SUPPLY FAN | ROOM_6_FLR_3_PTAC_SUPPLY FAN | ROOM_1_FLR_6_PTAC_SUPPLY FAN | ROOM_2_FLR_6_PTAC_SUPPLY FAN | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | PTAC_3_PTAC_SUPPLY FAN | PTAC_6_PTAC_SUPPLY FAN | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |AirLoopSystemComponentLoadsMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |AirLoopSystemComponentEnergyUseMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1368.30 | 497.27 | 98.60 | 673.82 | 98.60 |
Gross Window-Wall Ratio [%] | 30.01 | 26.54 | 24.26 | 35.97 | 24.26 |
Above Ground Window-Wall Ratio [%] | 33.99 | 29.91 | 28.11 | 40.54 | 28.11 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1368.30 | 497.27 | 98.60 | 673.82 | 98.60 |
Gross Window-Wall Ratio [%] | 30.01 | 26.54 | 24.26 | 35.97 | 24.26 |
Above Ground Window-Wall Ratio [%] | 33.99 | 29.91 | 28.11 | 40.54 | 28.11 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 11.0679 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 16.1458 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 16.1458 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 15.0695 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 13.9931 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 4.22 | 4.22 | 12.2708 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 4.23 | 4.23 | 12.2708 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 18.31 | 18.31 | 5.3819 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 7.75 | 7.75 | 12.2709 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 36.97 | 36.97 | 15.0695 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 36.97 | 36.97 | 15.0695 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 30.28 | 30.28 | 12.9167 | 4.65 | 2935.6055 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 32.40 | 32.40 | 5.3819 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1368.30 | 1368.30 | 11.3147 | 7.07 | 41.0811 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1368.30 | 1368.30 | 11.3147 | 7.07 | 41.0811 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.0679 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 16.1458 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 16.1458 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 16.1458 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 8.6111 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 15.0695 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 13.9931 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 12.2708 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 12.2708 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 5.3819 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 12.2708 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 12.2708 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 12.2709 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 15.0695 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 15.0695 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 12.9167 | 4.65 | 2935.6055 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 5.3819 | 18.58 | 0.0000 | |
Total | 11345.29 | 11.3147 | 3.54 | 41.0811 | |||||||
Conditioned Total | 11345.29 | 11.3147 | 3.54 | 41.0811 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 6.0626 | 8.82 | 37.2091 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-JUL-18:10 | 18-JAN-19:00 | - | - | - | - | - | - | - | - | - | - | 08-MAR-21:10 |
Heating | 0.00 | 162910.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 193003.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 107831.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77688.87 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 29010.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58383.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 244604.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1320.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 467287.20 | 495135.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 10897.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 152013.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 193003.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 107831.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 365.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1069.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 58383.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 47.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 244604.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 427.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 664.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 898.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3681.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4833.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1020.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5262.99 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2666.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3832.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 13.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2933.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 138.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 21449.04 | 5770.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 79.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 324.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 89.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.89 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 337.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 258.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1890.57 | 508.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 79.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 324.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 89.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.89 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 337.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 258.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1890.57 | 508.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 3.75 | 0.402101 | 0.300000 | 1.12 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.583438 | 0.087599 | 0.300000 | 0.175032 | 0.300000 | 0.500000 | 0.004349 | 0.000061 | 0.357161 | 12.89 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.408368 | 0.144927 | 0.355000 | 0.144971 | 0.386473 | 0.500000 | 0.002629 | 0.000021 | 0.144971 | 12.89 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.461569 | 0.271148 | 0.300000 | 0.138471 | 0.723061 | 0.500000 | 0.001405 | 0.000030 | 0.174430 | 12.89 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.235556 | 0.306537 | 0.388000 | 0.091396 | 0.817432 | 0.500000 | 0.001243 | 0.000030 | 0.174255 | 12.89 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 7.50 | 0.132840 | 0.399000 | 2.99 | 0.399000 | 0.500000 | 0.002868 | 0.000409 | 2.99 | 12.89 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 3.45 | 0.073294 | 0.468000 | 1.61 | 0.468000 | 0.500000 | 0.005198 | 0.000203 | 1.61 | 12.89 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 3.60 | 0.070108 | 0.447000 | 1.61 | 0.447000 | 0.500000 | 0.005434 | 0.000204 | 1.61 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 6932.49 | 0.000061 | 161.69 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2375.12 | 0.000021 | 53.13 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3385.26 | 0.000030 | 78.96 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 3382.25 | 0.000030 | 78.89 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 46742.96 | 0.000409 | 1034.89 |
ROOM_1_FLR_3 HEATING COIL | 18448.39 | 0.000161 | 460.36 |
ROOM_2_FLR_3 HEATING COIL | 18287.30 | 0.000160 | 456.29 |
ROOM_3_MULT19_FLR_3 HEATING COIL | 116085.39 | 0.001016 | 2846.13 |
ROOM_4_MULT19_FLR_3 HEATING COIL | 112696.24 | 0.000986 | 2759.94 |
ROOM_5_FLR_3 HEATING COIL | 16300.77 | 0.000143 | 406.03 |
ROOM_6_FLR_3 HEATING COIL | 16159.32 | 0.000141 | 402.45 |
PTAC_3 HEATING COIL | 37292.41 | 0.000326 | 882.18 |
ROOM_1_FLR_6 HEATING COIL | 5043.59 | 0.000044 | 126.00 |
ROOM_2_FLR_6 HEATING COIL | 4989.96 | 0.000044 | 124.65 |
ROOM_3_MULT9_FLR_6 HEATING COIL | 22119.40 | 0.000194 | 549.31 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 23213.63 | 0.000203 | 505.72 |
DINING_FLR_6 VAV BOX REHEAT COIL | 23366.54 | 0.000204 | 509.82 |
PTAC_6 HEATING COIL | 18601.13 | 0.000163 | 455.91 |
VAV_FLR_1 HEATING COIL | 56787.38 | 0.000497 | 912.26 |
VAV_FLR_6 HEATING COIL | 43775.93 | 0.000383 | 703.24 |
VAV_FLR_0 HEATING COIL | 37014.77 | 0.000324 | 2244.94 |
Design Size Maximum Air Flow Rate [m3/s] | |
LAUNDRY_FLR_1 DIRECT AIR | 4.68 |
CAFE_FLR_1 DIRECT AIR | 2.33 |
KITCHEN_FLR_6 DIRECT AIR | 3.23 |
Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | |
ROOM_1_FLR_3 | 1.48 | 1.48 | 1.48 | 0.061735 | 0.061735 | 0.061735 |
ROOM_2_FLR_3 | 1.47 | 1.47 | 1.47 | 0.061728 | 0.061728 | 0.061728 |
ROOM_3_MULT19_FLR_3 | 8.16 | 8.16 | 8.16 | 0.837072 | 0.837072 | 0.837072 |
ROOM_4_MULT19_FLR_3 | 7.86 | 7.86 | 7.86 | 0.837300 | 0.837300 | 0.837300 |
ROOM_5_FLR_3 | 1.29 | 1.29 | 1.29 | 0.061735 | 0.061735 | 0.061735 |
ROOM_6_FLR_3 | 1.28 | 1.28 | 1.28 | 0.061728 | 0.061728 | 0.061728 |
PTAC_3 | 2.09 | 2.09 | 2.09 | 0.474762 | 0.474762 | 0.474762 |
ROOM_1_FLR_6 | 0.409173 | 0.409173 | 0.409173 | 0.015434 | 0.015434 | 0.015434 |
ROOM_2_FLR_6 | 0.404398 | 0.404398 | 0.404398 | 0.015432 | 0.015432 | 0.015432 |
ROOM_3_MULT9_FLR_6 | 1.71 | 1.71 | 1.71 | 0.099154 | 0.099154 | 0.099154 |
PTAC_6 | 1.33 | 1.33 | 1.33 | 0.125616 | 0.125616 | 0.125616 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
ROOM_1_FLR_3 PTAC COOLING COIL | 1.48 | 24546.83 | 0.800655 |
ROOM_2_FLR_3 PTAC COOLING COIL | 1.47 | 24309.50 | 0.800655 |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 8.16 | 135074.73 | 0.800655 |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 7.86 | 130064.98 | 0.800655 |
ROOM_5_FLR_3 PTAC COOLING COIL | 1.29 | 21378.67 | 0.800655 |
ROOM_6_FLR_3 PTAC COOLING COIL | 1.28 | 21170.30 | 0.800655 |
PTAC_3 PTAC COOLING COIL | 2.09 | 34571.06 | 0.800655 |
ROOM_1_FLR_6 PTAC COOLING COIL | 0.409173 | 6773.27 | 0.800655 |
ROOM_2_FLR_6 PTAC COOLING COIL | 0.404398 | 6694.22 | 0.800655 |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 1.71 | 28345.45 | 0.800655 |
PTAC_6 PTAC COOLING COIL | 1.33 | 22031.05 | 0.800655 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3_PTAC_SUPPLY FAN | 1.48 |
ROOM_2_FLR_3_PTAC_SUPPLY FAN | 1.47 |
ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | 8.16 |
ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | 7.86 |
ROOM_5_FLR_3_PTAC_SUPPLY FAN | 1.29 |
ROOM_6_FLR_3_PTAC_SUPPLY FAN | 1.28 |
PTAC_3_PTAC_SUPPLY FAN | 2.09 |
ROOM_1_FLR_6_PTAC_SUPPLY FAN | 0.409173 |
ROOM_2_FLR_6_PTAC_SUPPLY FAN | 0.404398 |
ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | 1.71 |
PTAC_6_PTAC_SUPPLY FAN | 1.33 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_FLR_1 | 4.60 | 3.54 | 9.19 | 3.54 | 9.15 | 9.15 | 0.300000 | 0.387357 | 9.15 |
VAV_FLR_6 | 3.53 | 3.23 | 7.05 | 3.23 | 7.05 | 7.05 | 0.300000 | 0.457267 | 7.05 |
VAV_FLR_0 | 1.12 | 1.12 | 3.75 | 1.12 | 3.75 | 3.75 | 1.00 | 0.300000 | 3.75 |
PSZ_LAUNDRY | 4.68 | 4.68 | 4.68 | 4.68 | 4.68 | 4.68 | 1.00 | 1.000000 | 4.68 |
PSZ_CAFE | 2.33 | 2.33 | 2.33 | 2.33 | 2.33 | 2.33 | 1.00 | 1.00 | 2.33 |
PSZ_KITCHEN | 3.23 | 3.23 | 3.23 | 3.23 | 3.23 | 3.23 | 1.00 | 1.00 | 3.23 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_FLR_1_OA_CONTROLLER | 9.15 | |
VAV_FLR_6_OA_CONTROLLER | 7.05 | |
VAV_FLR_0_OA_CONTROLLER | 3.75 | |
PSZ_LAUNDRY_OA_CONTROLLER | 4.68 | 0.000000 |
PSZ_CAFE_OA_CONTROLLER | 2.33 | 0.676389 |
PSZ_KITCHEN_OA_CONTROLLER | 3.23 | 0.367350 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
VAV_FLR_1 COOLING COIL | 9.15 | 157663.30 | 0.800168 | 3.05 | 52549.18 | 0.800168 |
VAV_FLR_6 COOLING COIL | 7.05 | 132122.34 | 0.800877 | 2.35 | 44036.38 | 0.800877 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_FLR_1 FAN | 9.15 |
VAV_FLR_6 FAN | 7.05 |
VAV_FLR_0 SZVAV FAN | 3.75 |
Maximum Actuated Flow [m3/s] | |
VAV_FLR_1_HEATC_CONTROLLER | 0.000497 |
VAV_FLR_6_HEATC_CONTROLLER | 0.000383 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | Design Size Maximum Supply Air Temperature [C] | |
VAV_FLR_0_UNITARY_PACKAGE_DX | 3.75 | 3.75 | 3.75 | 1.12 | 62075.33 | 66038.92 | 1.00 | 12.89 | 32.11 | |
PSZ_LAUNDRY_UNITARY_PACKAGE_DX | 4.68 | 4.68 | 4.68 | 4.68 | 77473.27 | 51751.67 | 1.00 | 32.11 | ||
PSZ_CAFE_UNITARY_PACKAGE_DX | 2.33 | 2.33 | 2.33 | 2.33 | 42726.05 | 45263.07 | 1.00 | 32.11 | ||
PSZ_KITCHEN_UNITARY_PACKAGE_DX | 3.23 | 3.23 | 3.23 | 3.23 | 59155.83 | 46874.52 | 1.00 | 32.11 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
VAV_FLR_0 COOLING COIL | 3.75 | 1.87 | 2.50 | 62075.33 | 31037.67 | 0.800660 | 0.800660 |
PSZ_LAUNDRY COOLING COIL | 4.68 | 2.34 | 3.12 | 77473.27 | 38736.64 | 0.800660 | 0.800660 |
PSZ_CAFE COOLING COIL | 2.33 | 1.17 | 1.56 | 42726.05 | 21363.03 | 0.800470 | 0.800470 |
PSZ_KITCHEN COOLING COIL | 3.23 | 1.62 | 2.15 | 59155.83 | 29577.92 | 0.800560 | 0.800560 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | 4.68 | 7534.29 |
PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | 2.33 | 3786.20 |
PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | 3.23 | 5243.44 |
Design Size Nominal Capacity [W] | |
PSZ_LAUNDRY HEATING COIL | 51751.67 |
PSZ_CAFE HEATING COIL | 45263.07 |
PSZ_KITCHEN HEATING COIL | 46874.52 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.005538 | 0.664531 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.005538 | 1667.73 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 633000.24 | 633000.24 | 0.005538 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 6.92 | 4.22 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 6.92 | 4.23 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 30.00 | 18.31 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 12.69 | 7.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 60.57 | 36.97 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 60.57 | 36.97 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 57.04 | 30.28 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 53.08 | 32.40 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 11.068 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.448 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 16.146 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.906 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 16.146 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.906 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 16.146 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 21.526 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 8.611 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 11.301 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 15.069 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 20.449 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 13.993 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 22.063 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 15.069 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 82.889 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 15.069 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 82.889 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 12.917 | 516.346 | 2419.260 | 0.000 | 0.000 | 0.000 | 2948.522 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 21901.435 | 11.068 | 205.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21901.435 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1082.924 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1082.924 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1254.030 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1254.030 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 2651.846 | 16.146 | 999.942 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2651.846 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 815.983 | 8.611 | 399.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 815.983 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2846.047 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2846.047 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 18305.540 | 13.993 | 43.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18305.540 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 300.928 | 12.271 | 200.619 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 300.928 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 301.011 | 12.271 | 200.674 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 301.011 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2095.757 | 5.382 | 100.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2095.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 301.011 | 12.271 | 200.674 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 301.011 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4997.899 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4997.899 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4997.899 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4997.899 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1334.351 | 12.917 | 60.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1334.351 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2218.035 | 5.382 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2218.035 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 493.000 | 4.772 | 22.169 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 493.000 | 493.000 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 365.000 | 3.533 | 16.413 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 365.000 | 365.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 200.0 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | NONRES_EXT_WALL_MID | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_TOP | 23 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | RES_EXT_WALL_MID | 25 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | RES_EXT_WALL_TOP | 26 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5000E-02 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
13 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
14 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
15 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
19 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
20 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
21 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
23 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
24 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
25 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
26 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
27 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
28 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
31 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
36 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
37 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
38 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
39 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
40 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
42 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
44 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
46 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 200.00000 | 200.00000 | 200.00000 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
21 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
22 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
23 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
24 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
25 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
26 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
27 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
28 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
29 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
30 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
31 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
32 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
33 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
34 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
35 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
36 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
37 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
38 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
39 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
40 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
41 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
42 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
43 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
44 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
45 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
46 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
47 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
48 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
49 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
50 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
51 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
52 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
53 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
54 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
55 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
56 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
57 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
58 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
59 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
60 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
61 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
62 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
63 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
64 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
65 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
66 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
67 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
68 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
69 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
70 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
71 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
72 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
73 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
74 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
75 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
76 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
77 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
78 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
79 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
80 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
81 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
82 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
83 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
84 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
85 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
86 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
87 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
88 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
89 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
90 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
91 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
108 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
109 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
110 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
111 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
112 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
113 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
114 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
115 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
116 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
117 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
118 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
119 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
120 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
121 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
122 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
123 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | RESWINDOW_U_0.57_SHGC_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 8000.0 | 0.975 | 0.8950 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone RETAIL_1_FLR_1 | 1.2500 |
4 | Zone RETAIL_2_FLR_1 | 1.2500 |
5 | Zone MECH_FLR_1 | 1.2500 |
6 | Zone STORAGE_FLR_1 | 1.2500 |
7 | Zone LAUNDRY_FLR_1 | 1.2500 |
8 | Zone CAFE_FLR_1 | 1.2500 |
9 | Zone LOBBY_FLR_1 | 1.2500 |
10 | Zone ROOM_1_FLR_3 | 1.2500 |
11 | Zone ROOM_2_FLR_3 | 1.2500 |
12 | Zone ROOM_3_MULT19_FLR_3 | 1.2500 |
13 | Zone ROOM_4_MULT19_FLR_3 | 1.2500 |
14 | Zone ROOM_5_FLR_3 | 1.2500 |
15 | Zone ROOM_6_FLR_3 | 1.2500 |
16 | Zone CORRIDOR_FLR_3 | 1.2500 |
17 | Zone ROOM_1_FLR_6 | 1.2500 |
18 | Zone ROOM_2_FLR_6 | 1.2500 |
19 | Zone ROOM_3_MULT9_FLR_6 | 1.2500 |
20 | Zone BANQUET_FLR_6 | 1.2500 |
21 | Zone DINING_FLR_6 | 1.2500 |
22 | Zone KITCHEN_FLR_6 | 1.2500 |
23 | Zone CORRIDOR_FLR_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone RETAIL_1_FLR_1 | 1.1500 |
4 | Zone RETAIL_2_FLR_1 | 1.1500 |
5 | Zone MECH_FLR_1 | 1.1500 |
6 | Zone STORAGE_FLR_1 | 1.1500 |
7 | Zone LAUNDRY_FLR_1 | 1.1500 |
8 | Zone CAFE_FLR_1 | 1.1500 |
9 | Zone LOBBY_FLR_1 | 1.1500 |
10 | Zone ROOM_1_FLR_3 | 1.1500 |
11 | Zone ROOM_2_FLR_3 | 1.1500 |
12 | Zone ROOM_3_MULT19_FLR_3 | 1.1500 |
13 | Zone ROOM_4_MULT19_FLR_3 | 1.1500 |
14 | Zone ROOM_5_FLR_3 | 1.1500 |
15 | Zone ROOM_6_FLR_3 | 1.1500 |
16 | Zone CORRIDOR_FLR_3 | 1.1500 |
17 | Zone ROOM_1_FLR_6 | 1.1500 |
18 | Zone ROOM_2_FLR_6 | 1.1500 |
19 | Zone ROOM_3_MULT9_FLR_6 | 1.1500 |
20 | Zone BANQUET_FLR_6 | 1.1500 |
21 | Zone DINING_FLR_6 | 1.1500 |
22 | Zone KITCHEN_FLR_6 | 1.1500 |
23 | Zone CORRIDOR_FLR_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 36619.43341 | 42112.34842 | 3.26084 | 3.74997 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 27.74250 | 5.68807E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5697.06831 | 6551.62856 | 0.50734 | 0.58344 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3206.49181 | 4008.11476 | 0.28573 | 0.35716 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3987.40142 | 4585.51163 | 0.35510 | 0.40837 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.76000 | 5.69575E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 950.55387 | 1188.19234 | 8.47066E-002 | 0.10588 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 4507.92079 | 5184.10890 | 0.40136 | 0.46157 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 34.11000 | 5.69784E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1565.93187 | 1957.41484 | 0.13954 | 0.17443 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 2300.53993 | 2645.62092 | 0.20483 | 0.23556 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 32.31000 | 5.69506E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1564.35620 | 1955.44525 | 0.13940 | 0.17425 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45704.92471 | 52560.66341 | 4.06970 | 4.68016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 32.67000 | 5.69561E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2127.06750 | 2658.83437 | 0.18954 | 0.23693 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 22771.32977 | 26187.02923 | 2.02965 | 2.33410 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 8389.38449 | 10486.73062 | 0.74758 | 0.93448 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 73248.81757 | 84236.14020 | 6.52524 | 7.50403 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10000 | 5.69938E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17782.09132 | 22227.61414 | 1.58461 | 1.98077 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 14483.83102 | 16656.40568 | 1.28946 | 1.48287 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5873.51912 | 7341.89891 | 0.52342 | 0.65428 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 14343.79525 | 16495.36454 | 1.27699 | 1.46854 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5873.32122 | 7341.65152 | 0.52341 | 0.65426 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 79703.11711 | 91658.58467 | 7.09553 | 8.15986 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 33767.91402 | 42209.89252 | 3.00939 | 3.76173 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 76740.82374 | 88251.94730 | 6.83237 | 7.85723 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 33778.64081 | 42223.30101 | 3.01034 | 3.76293 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 12614.46655 | 14506.63653 | 1.12303 | 1.29149 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 29.58750 | 5.69088E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5873.51912 | 7341.89891 | 0.52342 | 0.65428 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 12491.52283 | 14365.25126 | 1.11209 | 1.27890 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 29.20500 | 5.69029E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5873.32122 | 7341.65152 | 0.52341 | 0.65426 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20394.78636 | 23454.00432 | 1.81603 | 2.08844 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 10201.64014 | 12752.05017 | 0.90911 | 1.13639 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3996.56013 | 4596.04415 | 0.35580 | 0.40917 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 33.57000 | 5.69700E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1974.38648 | 2467.98310 | 0.17595 | 0.21994 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3949.91669 | 4542.40420 | 0.35165 | 0.40440 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1976.39560 | 2470.49449 | 0.17613 | 0.22016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 16724.65328 | 19233.35127 | 1.48900 | 1.71235 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9650.70130 | 12063.37662 | 0.86005 | 1.07506 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 33628.28278 | 38672.52519 | 2.99830 | 3.44805 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7998.50947 | 9998.13684 | 0.71277 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 35157.34799 | 40430.95019 | 3.13459 | 3.60478 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 8136.21454 | 10170.26818 | 0.72504 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31479.90409 | 36201.88970 | 2.81083 | 3.23245 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2957.26526 | 3696.58158 | 0.26350 | 0.36735 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 12997.15698 | 14946.73052 | 1.15730 | 1.33090 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 35.10000 | 5.69938E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8710.43019 | 10888.03774 | 0.77622 | 0.97027 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -7.90000 | 2.34317E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_FLR_1 | Cooling | Sensible | 132403.75 | 9.14912 | 9.14912 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_FLR_1 | Heating | Sensible | 57775.45 | 2.79249 | 2.79249 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | VAV_FLR_6 | Cooling | Sensible | 112920.83 | 7.05283 | 7.05283 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_FLR_6 | Heating | Sensible | 49149.96 | 2.37559 | 2.37559 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | VAV_FLR_0 | Cooling | Sensible | 44645.05 | 3.74997 | 3.74997 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | VAV_FLR_0 | Heating | Sensible | 34023.52 | 0.85446 | 0.85446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ_LAUNDRY | Cooling | Sensible | 51747.90 | 4.68016 | 4.68016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
8 | PSZ_LAUNDRY | Heating | Sensible | 2619.85 | 0.23693 | 0.23693 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
9 | PSZ_CAFE | Cooling | Sensible | 33110.89 | 2.33410 | 2.33410 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ_CAFE | Heating | Sensible | 29786.81 | 0.93448 | 0.93448 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
11 | PSZ_KITCHEN | Cooling | Sensible | 39207.20 | 3.23245 | 3.23245 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ_KITCHEN | Heating | Sensible | 14627.45 | 0.36735 | 0.36735 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 3.74997 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.40210 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 1.12499 |
5 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58344 |
6 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.75986E-002 |
7 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17503 |
9 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
10 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.34939E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.06485E-005 |
13 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35716 |
14 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6932.49242 |
17 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.06485E-005 |
18 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 161.69455 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.40837 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14493 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35500 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14497 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38647 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.62890E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07786E-005 |
27 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14497 |
28 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2375.12475 |
31 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07786E-005 |
32 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 53.13188 |
33 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.46157 |
34 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27115 |
35 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13847 |
37 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72306 |
38 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40514E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.96157E-005 |
41 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17443 |
42 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3385.25559 |
45 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.96157E-005 |
46 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 78.95544 |
47 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23556 |
48 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30654 |
49 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.38800 |
50 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 9.13956E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81743 |
52 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24292E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.95894E-005 |
55 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17425 |
56 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3382.24721 |
59 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.95894E-005 |
60 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 78.88781 |
61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LAUNDRY_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.68016 |
62 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CAFE_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.33410 |
63 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.50403 |
64 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13284 |
65 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39900 |
66 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.99411 |
67 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39900 |
68 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
69 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86810E-003 |
70 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.08928E-004 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.99411 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
74 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 46742.95906 |
75 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.08928E-004 |
76 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1034.89492 |
77 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.48287 |
78 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.48287 |
79 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.48287 |
80 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17350E-002 |
81 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17350E-002 |
82 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17350E-002 |
83 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 18448.38901 |
84 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61395E-004 |
85 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 460.36316 |
86 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.48287 |
87 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 24546.82835 |
88 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
89 | Fan:OnOff | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.48287 |
90 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46854 |
91 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46854 |
92 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.46854 |
93 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17278E-002 |
94 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17278E-002 |
95 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17278E-002 |
96 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 18287.29809 |
97 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59985E-004 |
98 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 456.28885 |
99 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.46854 |
100 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 24309.49952 |
101 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
102 | Fan:OnOff | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.46854 |
103 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.15986 |
104 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 8.15986 |
105 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 8.15986 |
106 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.83707 |
107 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.83707 |
108 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.83707 |
109 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 116085.39086 |
110 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01557E-003 |
111 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2846.13359 |
112 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 8.15986 |
113 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 135074.72953 |
114 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
115 | Fan:OnOff | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 8.15986 |
116 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.85723 |
117 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 7.85723 |
118 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 7.85723 |
119 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.83730 |
120 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.83730 |
121 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.83730 |
122 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 112696.24400 |
123 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.85916E-004 |
124 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2759.94468 |
125 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 7.85723 |
126 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 130064.97879 |
127 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
128 | Fan:OnOff | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 7.85723 |
129 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29149 |
130 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29149 |
131 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.29149 |
132 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17350E-002 |
133 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17350E-002 |
134 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17350E-002 |
135 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 16300.77378 |
136 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42606E-004 |
137 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 406.02833 |
138 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.29149 |
139 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 21378.66525 |
140 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
141 | Fan:OnOff | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.29149 |
142 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27890 |
143 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27890 |
144 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.27890 |
145 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17278E-002 |
146 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17278E-002 |
147 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17278E-002 |
148 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 16159.31826 |
149 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41369E-004 |
150 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 402.44960 |
151 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.27890 |
152 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 21170.30257 |
153 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
154 | Fan:OnOff | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.27890 |
155 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.08844 |
156 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 2.08844 |
157 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 2.08844 |
158 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.47476 |
159 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.47476 |
160 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47476 |
161 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size Rated Capacity [W] | 37292.41282 |
162 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.26250E-004 |
163 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 882.17505 |
164 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 2.08844 |
165 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 34571.05775 |
166 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
167 | Fan:OnOff | PTAC_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 2.08844 |
168 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40917 |
169 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40917 |
170 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40917 |
171 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.54338E-002 |
172 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.54338E-002 |
173 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.54338E-002 |
174 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 5043.59455 |
175 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.41236E-005 |
176 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 126.00258 |
177 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40917 |
178 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6773.26685 |
179 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
180 | Fan:OnOff | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40917 |
181 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40440 |
182 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40440 |
183 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40440 |
184 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.54319E-002 |
185 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.54319E-002 |
186 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.54319E-002 |
187 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 4989.95576 |
188 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.36543E-005 |
189 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 124.64615 |
190 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40440 |
191 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6694.21687 |
192 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
193 | Fan:OnOff | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40440 |
194 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.71235 |
195 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.71235 |
196 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.71235 |
197 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 9.91540E-002 |
198 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 9.91540E-002 |
199 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 9.91540E-002 |
200 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 22119.40496 |
201 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.93510E-004 |
202 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 549.31395 |
203 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.71235 |
204 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 28345.44800 |
205 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
206 | Fan:OnOff | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.71235 |
207 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.44805 |
208 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.32945E-002 |
209 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
210 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61369 |
211 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46800 |
212 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.19821E-003 |
214 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.03083E-004 |
215 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61369 |
216 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
217 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
218 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23213.63100 |
219 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03083E-004 |
220 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 505.72072 |
221 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.60478 |
222 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.01078E-002 |
223 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44700 |
224 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61133 |
225 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44700 |
226 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
227 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.43449E-003 |
228 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.04421E-004 |
229 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61133 |
230 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
231 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
232 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23366.54017 |
233 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.04421E-004 |
234 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 509.82229 |
235 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.23245 |
236 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.33090 |
237 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.33090 |
238 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.33090 |
239 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.12562 |
240 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.12562 |
241 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.12562 |
242 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size Rated Capacity [W] | 18601.13276 |
243 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62731E-004 |
244 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 455.91184 |
245 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.33090 |
246 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 22031.04805 |
247 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
248 | Fan:OnOff | PTAC_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.33090 |
249 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.59648 |
250 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.54397 |
251 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.19296 |
252 | AirLoopHVAC | VAV_FLR_1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.54397 |
253 | AirLoopHVAC | VAV_FLR_1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.14912 |
254 | AirLoopHVAC | VAV_FLR_1 | Adjusted Main Design Air Flow Rate [m3/s] | 9.14912 |
255 | AirLoopHVAC | VAV_FLR_1 | User Heating Air Flow Ratio [] | 0.30000 |
256 | AirLoopHVAC | VAV_FLR_1 | Calculated Heating Air Flow Ratio [] | 0.38736 |
257 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.52641 |
258 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.22502 |
259 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.05283 |
260 | AirLoopHVAC | VAV_FLR_6 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.22502 |
261 | AirLoopHVAC | VAV_FLR_6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.05283 |
262 | AirLoopHVAC | VAV_FLR_6 | Adjusted Main Design Air Flow Rate [m3/s] | 7.05283 |
263 | AirLoopHVAC | VAV_FLR_6 | User Heating Air Flow Ratio [] | 0.30000 |
264 | AirLoopHVAC | VAV_FLR_6 | Calculated Heating Air Flow Ratio [] | 0.45727 |
265 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12499 |
266 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12499 |
267 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.74997 |
268 | AirLoopHVAC | VAV_FLR_0 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12499 |
269 | AirLoopHVAC | VAV_FLR_0 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.74997 |
270 | AirLoopHVAC | VAV_FLR_0 | Adjusted Main Design Air Flow Rate [m3/s] | 3.74997 |
271 | AirLoopHVAC | VAV_FLR_0 | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | VAV_FLR_0 | Calculated Heating Air Flow Ratio [] | 0.30000 |
273 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.68016 |
274 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.68016 |
275 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.68016 |
276 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Heating Design Air Flow Rate [m3/s] | 4.68016 |
277 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.68016 |
278 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Main Design Air Flow Rate [m3/s] | 4.68016 |
279 | AirLoopHVAC | PSZ_LAUNDRY | User Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | PSZ_LAUNDRY | Calculated Heating Air Flow Ratio [] | 1.00000 |
281 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.33410 |
282 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.33410 |
283 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.33410 |
284 | AirLoopHVAC | PSZ_CAFE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.33410 |
285 | AirLoopHVAC | PSZ_CAFE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.33410 |
286 | AirLoopHVAC | PSZ_CAFE | Adjusted Main Design Air Flow Rate [m3/s] | 2.33410 |
287 | AirLoopHVAC | PSZ_CAFE | User Heating Air Flow Ratio [] | 1.00000 |
288 | AirLoopHVAC | PSZ_CAFE | Calculated Heating Air Flow Ratio [] | 1.00000 |
289 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.23245 |
290 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.23245 |
291 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.23245 |
292 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Heating Design Air Flow Rate [m3/s] | 3.23245 |
293 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.23245 |
294 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Main Design Air Flow Rate [m3/s] | 3.23245 |
295 | AirLoopHVAC | PSZ_KITCHEN | User Heating Air Flow Ratio [] | 1.00000 |
296 | AirLoopHVAC | PSZ_KITCHEN | Calculated Heating Air Flow Ratio [] | 1.00000 |
297 | AirLoopHVAC | VAV_FLR_1 | Design Supply Air Flow Rate [m3/s] | 9.14912 |
298 | AirLoopHVAC | VAV_FLR_6 | Design Supply Air Flow Rate [m3/s] | 7.05283 |
299 | AirLoopHVAC | VAV_FLR_0 | Design Supply Air Flow Rate [m3/s] | 3.74997 |
300 | AirLoopHVAC | PSZ_LAUNDRY | Design Supply Air Flow Rate [m3/s] | 4.68016 |
301 | AirLoopHVAC | PSZ_CAFE | Design Supply Air Flow Rate [m3/s] | 2.33410 |
302 | AirLoopHVAC | PSZ_KITCHEN | Design Supply Air Flow Rate [m3/s] | 3.23245 |
303 | Controller:OutdoorAir | VAV_FLR_1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.14912 |
304 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 9.14912 |
305 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 157663.30331 |
306 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80017 |
307 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 3.04940 |
308 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 52549.17899 |
309 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80017 |
310 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size Rated Capacity [W] | 56787.37560 |
311 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.96801E-004 |
312 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 912.26091 |
313 | Fan:VariableVolume | VAV_FLR_1 FAN | Design Size Maximum Flow Rate [m3/s] | 9.14912 |
314 | Controller:WaterCoil | VAV_FLR_1_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.96801E-004 |
315 | Controller:OutdoorAir | VAV_FLR_6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.05283 |
316 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 7.05283 |
317 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 132122.33731 |
318 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80088 |
319 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.35071 |
320 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 44036.37503 |
321 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80088 |
322 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 43775.92954 |
323 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.82971E-004 |
324 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 703.23850 |
325 | Fan:VariableVolume | VAV_FLR_6 FAN | Design Size Maximum Flow Rate [m3/s] | 7.05283 |
326 | Controller:WaterCoil | VAV_FLR_6_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.82971E-004 |
327 | Controller:OutdoorAir | VAV_FLR_0_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.74997 |
328 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.74997 |
329 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.74997 |
330 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.74997 |
331 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12499 |
332 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.74997 |
333 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.87499 |
334 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.49998 |
335 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 62075.33000 |
336 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31037.66500 |
337 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
338 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
339 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 62075.33000 |
340 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size Rated Capacity [W] | 37014.76713 |
341 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.23821E-004 |
342 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2244.94310 |
343 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 66038.91510 |
344 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
345 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
346 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
347 | Fan:VariableVolume | VAV_FLR_0 SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 3.74997 |
348 | Controller:OutdoorAir | PSZ_LAUNDRY_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.68016 |
349 | Controller:OutdoorAir | PSZ_LAUNDRY_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.00000 |
350 | Fan:SystemModel | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.68016 |
351 | Fan:SystemModel | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 7534.28701 |
352 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.68016 |
353 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.68016 |
354 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.68016 |
355 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.68016 |
356 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.68016 |
357 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.34008 |
358 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.12011 |
359 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 77473.27000 |
360 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 38736.63500 |
361 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
362 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
363 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 77473.27000 |
364 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51751.66579 |
365 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
366 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Coil:Heating:Fuel | PSZ_LAUNDRY HEATING COIL | Design Size Nominal Capacity [W] | 51751.66579 |
368 | Controller:OutdoorAir | PSZ_CAFE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.33410 |
369 | Controller:OutdoorAir | PSZ_CAFE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.67639 |
370 | Fan:SystemModel | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.33410 |
371 | Fan:SystemModel | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3786.19573 |
372 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.33410 |
373 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.33410 |
374 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.33410 |
375 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.33410 |
376 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.33410 |
377 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.16705 |
378 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.55607 |
379 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42726.05000 |
380 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21363.02500 |
381 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80047 |
382 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80047 |
383 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42726.05000 |
384 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 45263.06925 |
385 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
386 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Coil:Heating:Fuel | PSZ_CAFE HEATING COIL | Design Size Nominal Capacity [W] | 45263.06925 |
388 | Controller:OutdoorAir | PSZ_KITCHEN_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.23245 |
389 | Controller:OutdoorAir | PSZ_KITCHEN_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.36735 |
390 | Fan:SystemModel | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.23245 |
391 | Fan:SystemModel | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 5243.43551 |
392 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.23245 |
393 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.23245 |
394 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.23245 |
395 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.23245 |
396 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.23245 |
397 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.61623 |
398 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.15497 |
399 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 59155.83000 |
400 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 29577.91500 |
401 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80056 |
402 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80056 |
403 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 59155.83000 |
404 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46874.52342 |
405 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
406 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
407 | Coil:Heating:Fuel | PSZ_KITCHEN HEATING COIL | Design Size Nominal Capacity [W] | 46874.52342 |
408 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.53776E-003 |
409 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.66453 |
410 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.53776E-003 |
411 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1667.73079 |
412 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
413 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 633000.23735 |
414 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 633000.24000 |
415 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.53776E-003 |
416 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
417 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
418 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
419 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
420 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 6579.24 |
2 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2254.51 |
3 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3212.76 |
4 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 3209.90 |
5 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 44370.46 |
6 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | 19497.06 |
7 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | 19323.18 |
8 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | 119283.02 |
9 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | 115591.33 |
10 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | 17177.77 |
11 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | 17025.01 |
12 | Coil:Heating:Water | PTAC_3 HEATING COIL | 36218.19 |
13 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | 5340.00 |
14 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | 5282.12 |
15 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | 23199.78 |
16 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 22036.46 |
17 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 22181.51 |
18 | Coil:Heating:Water | PTAC_6 HEATING COIL | 19154.19 |
19 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | 41489.44 |
20 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | 31983.15 |
21 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | 64425.50 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | 23396.2 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
2 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | 23170.0 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
3 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 128743.0 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
4 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 123968.1 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
5 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | 20376.5 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
6 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | 20177.9 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
7 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | 32950.5 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
8 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | 6455.8 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
9 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | 6380.4 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
10 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 27016.7 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
11 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | 20998.3 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
12 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | 59136.4 | 10.16 | 10.16 | |||
13 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | 73805.4 | 10.40 | 10.40 | |||
14 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | 40894.2 | 10.35 | 10.35 | |||
15 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | 56619.0 | 10.35 | 10.35 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | N/A | N/A | 150855.29 | 514739.60 | 10.82 | 2.91 | 3.17 | 3.15 | 3.29 | 9.94 | 10.80 | 10.75 | 11.22 | 8.7035 | 6.8809 | 4.6135 | 1.9207 |
2 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | N/A | N/A | 126892.14 | 432973.94 | 10.99 | 2.96 | 3.21 | 3.20 | 3.34 | 10.09 | 10.96 | 10.90 | 11.41 | 6.7093 | 5.3458 | 3.5878 | 1.4381 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 200.000 | 200.000 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 6.92 | 11.15 | 6.92 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 4.22 | 4.22 | 4.22 | 180.00 | 90.00 | 3.02 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 6.92 | 11.15 | 6.92 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 4.23 | 4.23 | 4.23 | 0.00 | 90.00 | 3.02 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 90.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 90.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 4.04 | 6.50 | 4.04 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.47 | 2.47 | 2.47 | 0.00 | 90.00 | 1.76 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 4.04 | 6.50 | 4.04 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.46 | 2.46 | 2.46 | 180.00 | 90.00 | 1.76 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 12.69 | 20.44 | 12.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.75 | 7.75 | 7.75 | 180.00 | 90.00 | 5.53 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.57 | 97.55 | 60.57 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 36.97 | 36.97 | 36.97 | 0.00 | 90.00 | 26.40 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.57 | 97.55 | 60.57 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 36.97 | 36.97 | 36.97 | 0.00 | 90.00 | 26.40 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 16.08 | 21.37 | 16.08 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 32.31 | 52.03 | 32.31 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 19.72 | 19.72 | 19.72 | 90.00 | 90.00 | 14.08 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 9.81 | 15.79 | 9.81 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.99 | 5.99 | 5.99 | 0.00 | 90.00 | 4.27 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 32.31 | 52.03 | 32.31 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 19.72 | 19.72 | 19.72 | 180.00 | 90.00 | 14.08 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.5144400740E-002 | 2.5219860171E-002 | Pass | Pass | 2.4864509713E-002 | 2.2706322167E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.4415997396E-002 | 8.8593200562E-002 | Pass | Pass | 0.1312458548 | 0.5139407739 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.0824067469E-002 | 2.5882451583E-002 | Pass | Pass | 5.3142679460E-003 | 5.3772910566E-003 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3348785903E-002 | 2.0758846094E-002 | Pass | Pass | 3.9281194652E-003 | 4.2582841779E-003 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1612158421E-002 | 1.4767231759E-002 | Pass | Pass | 0.1018763558 | 0.2711032392 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9119733570E-005 | 3.7493931061E-005 | Pass | Pass | 2.1216050191E-002 | 5.9331968707E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7837007710E-002 | 0.1049210714 | Pass | Pass | 2.6557358332E-002 | 2.8247157548E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7836495853E-002 | 3.8511546033E-002 | Pass | Pass | 1.0951605197E-002 | 1.8508732163E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.7469944897E-002 | 0.2934736870 | Pass | Pass | 0.1771952184 | 0.4343646435 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.9029073807E-002 | 0.2119111713 | Pass | Pass | 0.1523106540 | 0.3285912947 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.6868311785E-002 | 3.8011957137E-002 | Pass | Pass | 0.1740665795 | 1.2996521197 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2753277906E-002 | 0.1804527812 | Pass | Pass | 0.2716369254 | 0.8211633137 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.3096436971E-002 | 0.3308679781 | Pass | Pass | 0.2986743509 | 1.7107834605 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.1864179429E-002 | 0.2569453869 | Pass | Pass | 0.1496454953 | 0.3724391753 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.0924332154E-003 | 7.9808122727E-003 | Pass | Pass | 0.1089137631 | 0.3976932567 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.6606815917E-002 | 0.2424512590 | Pass | Pass | 0.1590943196 | 0.4499319222 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.5492244393E-002 | 0.2792738748 | Pass | Pass | 0.1389960234 | 0.3747449011 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2625885209E-002 | 0.3622052804 | Pass | Pass | 0.7205903897 | 5.2198698367 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.7849995101E-002 | 8.9319187748E-002 | Pass | Pass | 8.5968011254E-003 | 1.7801210043E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.2414259528E-002 | 7.6152850686E-002 | Pass | Pass | 8.7164461074E-003 | 2.2577486757E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.5823459881E-003 | 2.8586703960E-003 | Pass | Pass | 2.5084080869E-002 | 4.6275530674E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.6008475220E-002 | 4.5215958308E-002 | Pass | Pass | 3.7815619996E-002 | 0.1481486196 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4661.66 | 106.09 | 1252.04 | 3893.39 | 5696.85 | 15610.04 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 55.74 | 34.61 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 104.06 | 64.62 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 55.74 | 34.61 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 104.05 | 64.61 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 847.14 | 526.04 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 847.37 | 526.16 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 104.06 | 64.62 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 55.74 | 34.61 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 55.74 | 34.61 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 104.05 | 64.61 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 70.60 | 43.85 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 26.01 | 16.14 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 26.02 | 16.16 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 70.60 | 43.85 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 13.94 | 8.65 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 26.01 | 16.15 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 13.94 | 8.65 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 26.01 | 16.15 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 183.96 | 114.24 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 97.55 | 60.57 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 97.55 | 60.57 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 21.37 | 16.08 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 52.03 | 32.31 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 13.94 | 8.65 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 17.65 | 10.96 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 15.79 | 9.81 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 52.03 | 32.31 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 3.241 | 0.391 | 0.431 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 3.241 | 0.391 | 0.431 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 3.241 | 0.391 | 0.431 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.391 | 0.431 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.391 | 0.431 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.391 | 0.431 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.391 | 0.431 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 4.22 | 0.00 | 0.00 | 4.22 | 321.10 | 3.241 | 0.391 | 0.431 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 4.23 | 0.00 | 0.00 | 4.23 | 321.20 | 3.241 | 0.391 | 0.431 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.391 | 0.431 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.391 | 0.431 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.391 | 0.431 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.391 | 0.431 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 6.69 | 0.00 | 0.00 | 6.69 | 26.76 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.47 | 0.00 | 0.00 | 2.47 | 9.86 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.46 | 0.00 | 0.00 | 2.46 | 9.86 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 6.69 | 0.00 | 0.00 | 6.69 | 26.76 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.391 | 0.431 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 9.86 | 3.241 | 0.391 | 0.431 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.391 | 0.431 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 9.86 | 3.241 | 0.391 | 0.431 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 7.75 | 0.00 | 0.00 | 7.75 | 69.72 | 3.241 | 0.391 | 0.431 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 36.97 | 0.00 | 0.00 | 36.97 | 36.97 | 3.241 | 0.391 | 0.431 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 36.97 | 0.00 | 0.00 | 36.97 | 36.97 | 3.241 | 0.391 | 0.431 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.391 | 0.431 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 19.72 | 0.00 | 0.00 | 19.72 | 19.72 | 3.241 | 0.391 | 0.431 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.391 | 0.431 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.99 | 0.00 | 0.00 | 5.99 | 5.99 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 19.72 | 0.00 | 0.00 | 19.72 | 19.72 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1368.30 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 497.27 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 871.02 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 6.464 | 200.000 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.0679 | 1978.83 | 21901.44 | LightsWired | LTG_SCH_BASEMENT | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 241.03 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 16.1458 | 67.07 | 1082.92 | LightsWired | LTG_SCH_RETAIL | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 11.92 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 16.1458 | 77.67 | 1254.03 | LightsWired | LTG_SCH_RETAIL | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.80 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 16.1458 | 164.24 | 2651.85 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.18 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 8.6111 | 94.76 | 815.98 | LightsWired | LTG_SCH_STORAGE | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.98 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 15.0695 | 188.86 | 2846.05 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 31.32 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 13.9931 | 1308.19 | 18305.54 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 201.46 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 12.2708 | 156.09 | 1915.33 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 12.2708 | 156.07 | 1915.11 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 12.2708 | 1863.81 | 22870.56 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 297.14 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 12.2708 | 1864.32 | 22876.81 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 297.22 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 12.2708 | 156.09 | 1915.33 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 12.2708 | 156.07 | 1915.11 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 5.3819 | 1557.62 | 8383.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 92.26 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 12.2708 | 39.02 | 478.83 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.22 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 12.2708 | 39.02 | 478.78 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.22 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 12.2709 | 220.77 | 2709.10 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 35.20 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 15.0695 | 331.66 | 4997.90 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 55.00 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 15.0695 | 331.66 | 4997.90 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 55.00 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 12.9167 | 103.30 | 1334.35 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.68 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 5.3819 | 412.12 | 2218.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 24.41 |
Interior Lighting Total | 11.3147 | 11345.29 | 128367.98 | 764.46 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 20502.98 | AstronomicalClock | - | 83.71 | 83.71 | 322.16 | |
Exterior Lighting Total | 20502.98 | 322.16 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 633000.24 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 24546.83 | 19653.55 | 4893.28 | 0.80 | 3.20 | |||
ROOM_2_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 24309.50 | 19463.53 | 4845.97 | 0.80 | 3.20 | |||
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 135074.73 | 108148.29 | 26926.44 | 0.80 | 3.20 | |||
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 130064.98 | 104137.21 | 25927.77 | 0.80 | 3.20 | |||
ROOM_5_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 21378.67 | 17116.94 | 4261.72 | 0.80 | 3.20 | |||
ROOM_6_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 21170.30 | 16950.11 | 4220.19 | 0.80 | 3.20 | |||
PTAC_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 34571.06 | 27679.50 | 6891.56 | 0.80 | 3.20 | |||
ROOM_1_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6773.27 | 5423.05 | 1350.22 | 0.80 | 3.20 | |||
ROOM_2_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6694.22 | 5359.76 | 1334.46 | 0.80 | 3.20 | |||
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 28345.45 | 22694.93 | 5650.52 | 0.80 | 3.20 | |||
PTAC_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 22031.05 | 17639.27 | 4391.77 | 0.80 | 3.20 | |||
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 157663.30 | 126157.07 | 31506.23 | 0.80 | 3.50 | |||
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 132122.34 | 105813.73 | 26308.61 | 0.80 | 3.50 | |||
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 62075.33 | 49701.23 | 12374.10 | 0.80 | 3.40 | |||
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | 77473.27 | 62029.75 | 15443.52 | 0.80 | 3.50 | |||
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42726.05 | 34200.92 | 8525.13 | 0.80 | 3.40 | |||
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | 59155.83 | 47357.79 | 11798.04 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
ROOM_1_FLR_3 PTAC COOLING COIL | 23396.2 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_2_FLR_3 PTAC COOLING COIL | 23170.0 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 128743.0 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 123968.1 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_5_FLR_3 PTAC COOLING COIL | 20376.5 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_6_FLR_3 PTAC COOLING COIL | 20177.9 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
PTAC_3 PTAC COOLING COIL | 32950.5 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_1_FLR_6 PTAC COOLING COIL | 6455.8 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_2_FLR_6 PTAC COOLING COIL | 6380.4 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 27016.7 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
PTAC_6 PTAC COOLING COIL | 20998.3 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
VAV_FLR_1 COOLING COIL | 150855.3 | 2.91 | 9.94 | N/A | N/A | 10.82 | |
VAV_FLR_6 COOLING COIL | 126892.1 | 2.96 | 10.09 | N/A | N/A | 10.99 | |
VAV_FLR_0 COOLING COIL | 59136.4 | 10.16 | 10.16 | ||||
PSZ_LAUNDRY COOLING COIL | 73805.4 | 10.40 | 10.40 | ||||
PSZ_CAFE COOLING COIL | 40894.2 | 10.35 | 10.35 | ||||
PSZ_KITCHEN COOLING COIL | 56619.0 | 10.35 | 10.35 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
ROOM_1_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_2_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_5_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_6_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PTAC_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_1_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_2_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PTAC_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6932.49 | 6579.24 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2375.12 | 2254.51 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3385.26 | 3212.76 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3382.25 | 3209.90 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 46742.96 | 44370.46 | - |
ROOM_1_FLR_3 HEATING COIL | Coil:Heating:Water | 18448.39 | 19497.06 | - |
ROOM_2_FLR_3 HEATING COIL | Coil:Heating:Water | 18287.30 | 19323.18 | - |
ROOM_3_MULT19_FLR_3 HEATING COIL | Coil:Heating:Water | 116085.39 | 119283.02 | - |
ROOM_4_MULT19_FLR_3 HEATING COIL | Coil:Heating:Water | 112696.24 | 115591.33 | - |
ROOM_5_FLR_3 HEATING COIL | Coil:Heating:Water | 16300.77 | 17177.77 | - |
ROOM_6_FLR_3 HEATING COIL | Coil:Heating:Water | 16159.32 | 17025.01 | - |
PTAC_3 HEATING COIL | Coil:Heating:Water | 37292.41 | 36218.19 | - |
ROOM_1_FLR_6 HEATING COIL | Coil:Heating:Water | 5043.59 | 5340.00 | - |
ROOM_2_FLR_6 HEATING COIL | Coil:Heating:Water | 4989.96 | 5282.12 | - |
ROOM_3_MULT9_FLR_6 HEATING COIL | Coil:Heating:Water | 22119.40 | 23199.78 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 23213.63 | 22036.46 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 23366.54 | 22181.51 | - |
PTAC_6 HEATING COIL | Coil:Heating:Water | 18601.13 | 19154.19 | - |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | 56787.38 | 41489.44 | - |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | 43775.93 | 31983.15 | - |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | 66038.92 | 64425.50 | - |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | 51751.67 | 0.80 | |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | 45263.07 | 0.80 | |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | 46874.52 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.48 | 944.39 | 636.87 | 1.00 | 1.41 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.47 | 935.26 | 636.87 | 1.00 | 1.41 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 8.16 | 5196.74 | 636.87 | 1.00 | 1.20 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 7.86 | 5003.99 | 636.87 | 1.00 | 1.20 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.29 | 822.50 | 636.87 | 1.00 | 1.44 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.28 | 814.49 | 636.87 | 1.00 | 1.45 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 |
PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 2.09 | 1330.05 | 636.87 | 1.00 | 1.34 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.41 | 260.59 | 636.87 | 1.00 | 1.91 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.40 | 257.55 | 636.87 | 1.00 | 1.92 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.71 | 1090.54 | 636.87 | 1.00 | 1.38 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 1.89 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.33 | 847.60 | 636.87 | 1.00 | 1.44 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
VAV_FLR_1 FAN | Fan:VariableVolume | 0.61 | 1337.13 | 9.15 | 20107.77 | 2197.78 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
VAV_FLR_6 FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.05 | 15500.57 | 2197.78 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 0.60 | 1337.13 | 3.75 | 8348.65 | 2226.32 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 |
PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 4.68 | 7534.29 | 1609.84 | 1.00 | 1.18 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 |
PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 2.33 | 3786.20 | 1622.12 | 1.00 | 1.23 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 3.23 | 5243.44 | 1622.12 | 1.00 | 1.20 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.005538 | 1667.73 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 0.80 | 0.98 | 0.90 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 150855.29 | 2.91 | 9.94 | 10.82 | 8.7035 | 3.17 | 10.80 | 6.8809 | 3.15 | 10.75 | 4.6135 | 3.29 | 11.22 | 1.9207 |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 126892.14 | 2.96 | 10.09 | 10.99 | 6.7093 | 3.21 | 10.96 | 5.3458 | 3.20 | 10.90 | 3.5878 | 3.34 | 11.41 | 1.4381 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 36619.43 | 42112.35 | 21.28 | 3.261 | 3.750 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 24.00 | 24.00 | 0.00915 | 27.74 | 0.00569 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5697.07 | 6551.63 | 97.68 | 0.507 | 0.583 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00887 | 34.99 | 0.00570 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3987.40 | 4585.51 | 59.04 | 0.355 | 0.408 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00917 | 32.76 | 0.00570 | 0.092 | 0.00 |
MECH_FLR_1 | 4507.92 | 5184.11 | 31.56 | 0.401 | 0.462 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 24.00 | 24.00 | 0.00857 | 34.11 | 0.00570 | 0.000 | 0.00 |
STORAGE_FLR_1 | 2300.54 | 2645.62 | 27.92 | 0.205 | 0.236 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00863 | 32.31 | 0.00570 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45704.92 | 52560.66 | 673.51 | 4.070 | 4.680 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 24.00 | 24.00 | 0.00853 | 32.67 | 0.00570 | 0.000 | 0.00 |
CAFE_FLR_1 | 22771.33 | 26187.03 | 138.66 | 2.030 | 2.334 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00986 | 34.88 | 0.00570 | 0.676 | 0.00 |
LOBBY_FLR_1 | 73248.82 | 84236.14 | 64.39 | 6.525 | 7.504 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.00976 | 35.10 | 0.00570 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 14483.83 | 16656.41 | 426.85 | 1.289 | 1.483 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 33.39 | 0.00570 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 14343.80 | 16495.36 | 422.77 | 1.277 | 1.469 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 33.21 | 0.00570 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 79703.12 | 91658.58 | 3737.53 | 7.096 | 8.160 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00846 | 34.88 | 0.00570 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 76740.82 | 88251.95 | 3597.63 | 6.832 | 7.857 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00870 | 35.10 | 0.00570 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 12614.47 | 14506.64 | 371.76 | 1.123 | 1.291 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00852 | 29.59 | 0.00569 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 12491.52 | 14365.25 | 368.18 | 1.112 | 1.279 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 21.11 | 21.11 | 0.00853 | 29.21 | 0.00569 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20394.79 | 23454.00 | 60.23 | 1.816 | 2.088 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00938 | 35.10 | 0.00570 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3996.56 | 4596.04 | 117.78 | 0.356 | 0.409 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00852 | 33.57 | 0.00570 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3949.92 | 4542.40 | 116.42 | 0.352 | 0.404 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 33.39 | 0.00570 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 16724.65 | 19233.35 | 784.06 | 1.489 | 1.712 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00859 | 34.99 | 0.00570 | 0.099 | 0.00 |
BANQUET_FLR_6 | 33628.28 | 38672.53 | 116.60 | 2.998 | 3.448 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01015 | 35.10 | 0.00570 | 1.188 | 0.00 |
DINING_FLR_6 | 35157.35 | 40430.95 | 121.91 | 3.135 | 3.605 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01007 | 35.10 | 0.00570 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31479.90 | 36201.89 | 350.44 | 2.811 | 3.232 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01001 | 33.89 | 0.00570 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 12997.16 | 14946.73 | 36.27 | 1.157 | 1.331 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00885 | 35.10 | 0.00570 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.03 | 0.00234 | -7.90 | 0.00234 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3206.49 | 4008.11 | 59.76 | 0.286 | 0.357 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00779 | -7.90 | 0.00234 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 950.55 | 1188.19 | 15.30 | 0.085 | 0.106 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -7.90 | 0.00234 | 0.092 | 0.00 |
MECH_FLR_1 | 1565.93 | 1957.41 | 11.92 | 0.140 | 0.174 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00763 | -7.90 | 0.00234 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1564.36 | 1955.45 | 20.64 | 0.139 | 0.174 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00778 | -7.90 | 0.00234 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2127.07 | 2658.83 | 34.07 | 0.190 | 0.237 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00763 | -7.90 | 0.00234 | 0.000 | 0.00 |
CAFE_FLR_1 | 8389.38 | 10486.73 | 55.53 | 0.748 | 0.934 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00783 | -7.90 | 0.00234 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17782.09 | 22227.61 | 16.99 | 1.585 | 1.981 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -7.90 | 0.00234 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5873.52 | 7341.90 | 188.15 | 0.523 | 0.654 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00774 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5873.32 | 7341.65 | 188.16 | 0.523 | 0.654 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00774 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 33767.91 | 42209.89 | 1721.18 | 3.009 | 3.762 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00776 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 33778.64 | 42223.30 | 1721.25 | 3.010 | 3.763 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00776 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5873.52 | 7341.90 | 188.15 | 0.523 | 0.654 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00774 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5873.32 | 7341.65 | 188.16 | 0.523 | 0.654 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00774 | -7.90 | 0.00234 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 10201.64 | 12752.05 | 32.75 | 0.909 | 1.136 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00782 | -7.90 | 0.00234 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1974.39 | 2467.98 | 63.25 | 0.176 | 0.220 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00781 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1976.40 | 2470.49 | 63.32 | 0.176 | 0.220 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00781 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9650.70 | 12063.38 | 491.77 | 0.860 | 1.075 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00782 | -7.90 | 0.00234 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7998.51 | 9998.14 | 30.15 | 0.713 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00788 | -7.90 | 0.00234 | 1.188 | 0.00 |
DINING_FLR_6 | 8136.21 | 10170.27 | 30.66 | 0.725 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00788 | -7.90 | 0.00234 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2957.27 | 3696.58 | 35.78 | 0.264 | 0.367 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00756 | -7.90 | 0.00234 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8710.43 | 10888.04 | 26.42 | 0.776 | 0.970 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00790 | -7.90 | 0.00234 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_FLR_1 | 9.15 | 9.15 | 2.79 | 2.79 | 9.1491 | 3.5440 | 9.1491 | 0.3874 | 0.3000 |
VAV_FLR_6 | 7.05 | 7.05 | 2.38 | 2.38 | 7.0528 | 3.2250 | 7.0528 | 0.4573 | 0.3000 |
VAV_FLR_0 | 3.75 | 3.75 | 0.85 | 0.85 | 3.7500 | 1.1250 | 3.7500 | 0.3000 | 1.0000 |
PSZ_LAUNDRY | 4.68 | 4.68 | 0.24 | 0.24 | 4.6802 | 4.6802 | 4.6802 | 1.0000 | 1.0000 |
PSZ_CAFE | 2.33 | 2.33 | 0.93 | 0.93 | 2.3341 | 2.3341 | 2.3341 | 1.0000 | 1.0000 |
PSZ_KITCHEN | 3.23 | 3.23 | 0.37 | 0.37 | 3.2325 | 3.2325 | 3.2325 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 6932.492 | 6932.492 | 0.357161 | 0.00006065 | 161.695 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6932.49 | 6932.49 | 0.357161 | 12.89 | 9.89 | 0.00800000 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00779413 | 41.4575 | 4008.11 | 0.00 | 6583.07 | 6583.07 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2375.125 | 2375.125 | 0.144971 | 0.00002078 | 53.132 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2375.12 | 2375.12 | 0.144971 | 12.89 | 9.89 | 0.00800000 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00773483 | 41.1448 | 1188.19 | 0.00 | 2255.72 | 2255.72 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3385.256 | 3385.256 | 0.174430 | 0.00002962 | 78.955 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3385.26 | 3385.26 | 0.174430 | 12.89 | 9.89 | 0.00800000 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00762713 | 40.5790 | 1957.41 | 0.00 | 3214.63 | 3214.63 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 3382.247 | 3382.247 | 0.174255 | 0.00002959 | 78.888 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3382.25 | 3382.25 | 0.174255 | 12.89 | 9.89 | 0.00800000 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00777852 | 41.3745 | 1955.45 | 0.00 | 3211.77 | 3211.77 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 46742.959 | 46742.959 | 2.994107 | 0.00040893 | 1034.895 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 46742.96 | 46742.96 | 2.994107 | 12.89 | 9.89 | 0.00800000 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00776669 | 41.3123 | 22227.61 | 0.00 | 44393.73 | 44393.73 |
ROOM_1_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | 18448.389 | 18448.389 | 1.482874 | 0.00016139 | 460.363 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 18448.39 | 18448.39 | 1.482874 | 19.90 | 12.11 | 0.00751684 | 32.22 | 16.63 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 4.1632 | 21.11 | 0.00774159 | 40.9017 | 7341.90 | 0.00 | 19504.62 | 19504.62 |
ROOM_1_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | 24546.828 | 19653.547 | 1.482874 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 20341.68 | 20341.68 | 1.482874 | 21.62 | 13.50 | 0.00840499 | 9.37 | 8.87 | 0.00840499 | 33.39 | 0.00569673 | 15.22 | 4.1632 | 21.11 | 0.00852264 | 44.9708 | 16656.41 | 0.00 | 24558.84 | 17835.83 |
ROOM_2_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | 18287.298 | 18287.298 | 1.468537 | 0.00015999 | 456.289 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 18287.30 | 18287.30 | 1.468537 | 19.89 | 12.11 | 0.00751469 | 32.22 | 16.63 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 4.2034 | 21.11 | 0.00774160 | 40.9018 | 7341.65 | 0.00 | 19330.67 | 19330.67 |
ROOM_2_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | 24309.500 | 19463.529 | 1.468537 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 20191.20 | 20191.20 | 1.468537 | 21.62 | 13.49 | 0.00840402 | 9.37 | 8.87 | 0.00840402 | 33.21 | 0.00569645 | 15.16 | 4.2034 | 21.11 | 0.00852282 | 44.9718 | 16495.36 | 0.00 | 24321.40 | 17663.38 |
ROOM_3_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | 116085.391 | 116085.391 | 8.159864 | 0.00101557 | 2846.134 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 116085.39 | 116085.39 | 8.159864 | 18.13 | 11.17 | 0.00720511 | 32.22 | 16.63 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 10.2584 | 21.11 | 0.00776088 | 41.0013 | 42209.89 | 0.00 | 119321.57 | 119321.57 |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | 135074.730 | 108148.293 | 8.159864 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 110202.19 | 110202.19 | 8.159864 | 22.52 | 13.61 | 0.00817299 | 9.37 | 8.64 | 0.00817299 | 34.88 | 0.00569904 | 15.70 | 10.2584 | 21.11 | 0.00845579 | 44.6219 | 91658.58 | 0.00 | 135140.85 | 98145.87 |
ROOM_4_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | 112696.244 | 112696.244 | 7.857225 | 0.00098592 | 2759.945 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 112696.24 | 112696.24 | 7.857225 | 18.02 | 11.11 | 0.00718355 | 32.22 | 16.63 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 10.6564 | 21.11 | 0.00776089 | 41.0014 | 42223.30 | 0.00 | 115628.09 | 115628.09 |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | 130064.979 | 104137.209 | 7.857225 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 106529.29 | 106529.29 | 7.857225 | 22.60 | 13.81 | 0.00838083 | 9.37 | 8.84 | 0.00838083 | 35.10 | 0.00569938 | 15.77 | 10.6564 | 21.11 | 0.00870066 | 45.8988 | 88251.95 | 0.00 | 130128.65 | 94505.76 |
ROOM_5_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | 16300.774 | 16300.774 | 1.291485 | 0.00014261 | 406.028 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 16300.77 | 16300.77 | 1.291485 | 19.72 | 12.02 | 0.00748354 | 32.22 | 16.63 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 4.7802 | 21.11 | 0.00774159 | 40.9017 | 7341.90 | 0.00 | 17184.32 | 17184.32 |
ROOM_5_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | 21378.665 | 17116.941 | 1.291485 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 18568.18 | 18568.18 | 1.291485 | 21.52 | 13.45 | 0.00838948 | 9.37 | 8.85 | 0.00838948 | 29.59 | 0.00569088 | 13.95 | 4.7802 | 21.11 | 0.00852495 | 44.9828 | 14506.64 | 0.00 | 21389.13 | 15533.83 |
ROOM_6_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | 16159.318 | 16159.318 | 1.278898 | 0.00014137 | 402.450 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 16159.32 | 16159.32 | 1.278898 | 19.71 | 12.01 | 0.00748104 | 32.22 | 16.63 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 4.8266 | 21.11 | 0.00774160 | 40.9018 | 7341.65 | 0.00 | 17031.50 | 17031.50 |
ROOM_6_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | 21170.303 | 16950.114 | 1.278898 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | 7/21 09:40:00 | 18471.65 | 18471.65 | 1.278898 | 21.50 | 13.44 | 0.00838830 | 9.37 | 8.85 | 0.00838830 | 29.21 | 0.00569029 | 13.82 | 4.8266 | 21.11 | 0.00852513 | 44.9838 | 14365.25 | 0.00 | 21180.67 | 15382.43 |
PTAC_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | 37292.413 | 37292.413 | 2.088438 | 0.00032625 | 882.175 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 37292.41 | 37292.41 | 2.088438 | 14.43 | 9.11 | 0.00657306 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 22.7329 | 21.00 | 0.00781754 | 41.5790 | 12752.05 | 0.00 | 36223.23 | 36223.23 |
PTAC_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | 34571.058 | 27679.499 | 2.088438 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | unknown | 7/21 14:40:00 | 29760.10 | 29593.58 | 2.088438 | 26.52 | 15.25 | 0.00854018 | 12.26 | 10.12 | 0.00850000 | 35.10 | 0.00569938 | 15.77 | 22.7329 | 24.00 | 0.00937598 | 41.4577 | 23454.00 | 0.00 | 34587.98 | 25119.48 |
ROOM_1_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | 5043.595 | 5043.595 | 0.409173 | 0.00004412 | 126.003 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 5043.59 | 5043.59 | 0.409173 | 20.02 | 12.23 | 0.00759946 | 32.22 | 16.63 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 3.7719 | 21.11 | 0.00780550 | 41.2351 | 2467.98 | 0.00 | 5342.16 | 5342.16 |
ROOM_1_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | 6773.267 | 5423.052 | 0.409173 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 5598.49 | 5598.49 | 0.409173 | 21.58 | 13.49 | 0.00841406 | 9.37 | 8.88 | 0.00841406 | 33.57 | 0.00569700 | 15.28 | 3.7719 | 21.11 | 0.00852057 | 44.9600 | 4596.04 | 0.00 | 6776.58 | 4921.48 |
ROOM_2_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | 4989.956 | 4989.956 | 0.404398 | 0.00004365 | 124.646 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 4989.96 | 4989.96 | 0.404398 | 20.00 | 12.22 | 0.00759725 | 32.22 | 16.63 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 3.8160 | 21.11 | 0.00780570 | 41.2362 | 2470.49 | 0.00 | 5284.25 | 5284.25 |
ROOM_2_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | 6694.217 | 5359.760 | 0.404398 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 5545.94 | 5545.94 | 0.404398 | 21.58 | 13.49 | 0.00841302 | 9.37 | 8.88 | 0.00841302 | 33.39 | 0.00569673 | 15.22 | 3.8160 | 21.11 | 0.00852078 | 44.9612 | 4542.40 | 0.00 | 6697.49 | 4864.05 |
ROOM_3_MULT9_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | 22119.405 | 22119.405 | 1.712349 | 0.00019351 | 549.314 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 22119.40 | 22119.40 | 1.712349 | 19.43 | 11.92 | 0.00749948 | 32.22 | 16.63 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 5.7905 | 21.11 | 0.00781641 | 41.2916 | 12063.38 | 0.00 | 23208.75 | 23208.75 |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | 28345.448 | 22694.932 | 1.712349 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 23089.85 | 23089.85 | 1.712349 | 21.91 | 13.61 | 0.00842087 | 9.37 | 8.88 | 0.00842087 | 34.99 | 0.00569921 | 15.74 | 5.7905 | 21.11 | 0.00858815 | 45.3128 | 19233.35 | 0.00 | 28359.32 | 20595.92 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 23213.631 | 23213.631 | 1.613688 | 0.00020308 | 505.721 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 23213.63 | 23213.63 | 1.613688 | 12.89 | 9.89 | 0.00800000 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00788114 | 41.9133 | 9998.14 | 0.00 | 22047.60 | 22047.60 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 23366.540 | 23366.540 | 1.611334 | 0.00020442 | 509.822 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 23366.54 | 23366.54 | 1.611334 | 12.89 | 9.89 | 0.00800000 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00788311 | 41.9237 | 10170.27 | 0.00 | 22192.76 | 22192.76 |
PTAC_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | 18601.133 | 18601.133 | 1.330896 | 0.00016273 | 455.912 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 18601.13 | 18601.13 | 1.330896 | 18.27 | 11.38 | 0.00737912 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 9.4384 | 21.00 | 0.00790397 | 42.0330 | 10888.04 | 0.00 | 19161.17 | 19161.17 |
PTAC_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | 22031.048 | 17639.275 | 1.330896 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 18656.22 | 18501.63 | 1.330896 | 25.05 | 14.78 | 0.00855479 | 12.26 | 10.12 | 0.00850000 | 35.10 | 0.00569938 | 15.77 | 9.4384 | 24.00 | 0.00885239 | 39.1746 | 14946.73 | 0.00 | 22041.83 | 16007.85 |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_FLR_1 | 157663.303 | 126157.070 | 9.149125 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 149497.16 | 149497.16 | 9.149125 | 27.43 | 15.43 | 0.00838835 | 10.71 | 9.40 | 0.00838835 | 35.10 | 0.00569938 | 15.77 | 30.9352 | 23.99 | 0.00959278 | 42.4121 | 89313.33 | 0.00 | 158119.30 | 114663.58 |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_1 | 56787.376 | 56787.376 | 2.744737 | 0.00049680 | 912.261 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 56787.38 | 56787.38 | 2.744737 | -7.90 | -7.90 | 0.00234317 | 12.89 | 9.89 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 103.1173 | 21.00 | 0.00776101 | 41.2826 | 25069.43 | 0.00 | 50162.17 | 50162.17 |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_FLR_6 | 132122.337 | 105813.728 | 7.052825 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 125279.09 | 125279.09 | 7.052825 | 28.98 | 15.72 | 0.00812883 | 10.71 | 9.14 | 0.00812883 | 35.10 | 0.00569938 | 15.77 | 44.9111 | 23.98 | 0.01010943 | 44.6875 | 68785.63 | 0.00 | 132504.46 | 96166.88 |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_6 | 43775.930 | 43775.930 | 2.115848 | 0.00038297 | 703.239 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 43775.93 | 43775.93 | 2.115848 | -7.90 | -7.90 | 0.00234317 | 12.89 | 9.89 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 149.7036 | 21.00 | 0.00788206 | 41.9183 | 16132.76 | 0.00 | 38668.73 | 38668.73 |
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | VAV_FLR_0 | 62075.330 | 49701.234 | 3.749970 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 31037.67 | 31037.67 | 2.499980 | 24.85 | 14.56 | 0.00836400 | 10.69 | 9.36 | 0.00836400 | 27.74 | 0.00568807 | 13.32 | 34.1786 | 24.00 | 0.00915423 | 40.4923 | 36589.10 | 0.00 | -999.00 | -999.00 |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_0 | 66038.915 | 66038.915 | 3.749971 | 0.00032382 | 2244.943 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 66038.92 | 66038.92 | 3.749971 | 14.41 | 9.24 | 0.00671105 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 22.7857 | 22.15 | 0.00234317 | 11.7159 | 0.00 | 0.00 | 64439.31 | 64439.31 |
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_LAUNDRY | 77473.270 | 62029.748 | 4.680160 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 38736.64 | 38528.30 | 3.120107 | 24.00 | 14.41 | 0.00853322 | 11.30 | 9.74 | 0.00850000 | 32.67 | 0.00569561 | 14.99 | 0.0000 | 24.00 | 0.00853322 | 37.7815 | 45704.92 | 0.00 | -999.00 | -999.00 |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_LAUNDRY | 51751.666 | 51751.666 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 51751.67 | 51751.67 | 4.680161 | 21.00 | 12.61 | 0.00762537 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00762537 | 40.5710 | 2127.07 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_CAFE | 42726.050 | 34200.921 | 2.334100 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21363.03 | 20927.24 | 1.556067 | 27.14 | 15.54 | 0.00865381 | 11.28 | 9.74 | 0.00850000 | 34.88 | 0.00569904 | 15.70 | 43.4679 | 23.99 | 0.00986564 | 43.6175 | 22707.36 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_CAFE | 45263.069 | 45263.069 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 45263.07 | 45263.07 | 2.334098 | 12.62 | 8.02 | 0.00623649 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 28.9786 | 21.00 | 0.00782507 | 41.6197 | 8389.38 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_KITCHEN | 59155.830 | 47357.791 | 3.232450 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 29577.92 | 25600.60 | 2.154967 | 25.08 | 15.55 | 0.00952065 | 11.29 | 9.74 | 0.00850000 | 33.89 | 0.00569749 | 15.38 | 17.0467 | 23.97 | 0.01001084 | 44.2997 | 31479.90 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_KITCHEN | 46874.523 | 46874.523 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 46874.52 | 46874.52 | 3.232451 | 17.54 | 10.72 | 0.00696671 | 32.11 | 16.60 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 11.3645 | 21.00 | 0.00753217 | 40.0817 | 1978.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6932.492 | 6932.492 | 0.357161 | 0.00006065 | 161.695 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 1.0736 | 1.095180 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6932.49 | 6932.49 | 1.0000 | 0.35373528 | 0.357161 | 12.89 | 9.89 | 0.00800000 | 33150.5 | 32.11 | 16.60 | 0.00800000 | 52751.6 | 0.06064228 | 60.00 | 32.22 | 27.78 | 0.000 | 6932.49 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00779413 | 21.00 | 0.00779413 | 41.4575 | 4008.11 | 0.00 | 6583.07 | 6583.07 | 0.35373528 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55544.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2375.125 | 2375.125 | 0.144971 | 0.00002078 | 53.132 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 0.3678 | 0.375217 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2375.12 | 2375.12 | 1.0000 | 0.14358019 | 0.144971 | 12.89 | 9.89 | 0.00800000 | 33150.5 | 32.11 | 16.60 | 0.00800000 | 52751.6 | 0.02077651 | 60.00 | 32.22 | 27.78 | 0.000 | 2375.12 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00773483 | 21.00 | 0.00773483 | 41.1448 | 1188.19 | 0.00 | 2255.72 | 2255.72 | 0.14358019 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.01 | 18.70 | 0.00800000 | 52645.2 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3385.256 | 3385.256 | 0.174430 | 0.00002962 | 78.955 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 0.5242 | 0.534795 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3385.26 | 3385.26 | 1.0000 | 0.17275723 | 0.174430 | 12.89 | 9.89 | 0.00800000 | 33150.5 | 32.11 | 16.60 | 0.00800000 | 52751.6 | 0.02961267 | 60.00 | 32.22 | 27.78 | 0.000 | 3385.26 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00762713 | 21.00 | 0.00762713 | 40.5790 | 1957.41 | 0.00 | 3214.63 | 3214.63 | 0.17275723 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55542.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3382.247 | 3382.247 | 0.174255 | 0.00002959 | 78.888 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 0.5238 | 0.534320 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3382.25 | 3382.25 | 1.0000 | 0.17258356 | 0.174255 | 12.89 | 9.89 | 0.00800000 | 33150.5 | 32.11 | 16.60 | 0.00800000 | 52751.6 | 0.02958636 | 60.00 | 32.22 | 27.78 | 0.000 | 3382.25 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00777852 | 21.00 | 0.00777852 | 41.3745 | 1955.45 | 0.00 | 3211.77 | 3211.77 | 0.17258356 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55544.7 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 46742.959 | 46742.959 | 2.994107 | 0.00040893 | 1034.895 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 7.2387 | 7.384351 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 46742.96 | 46742.96 | 1.0000 | 2.96538980 | 2.994107 | 12.89 | 9.89 | 0.00800000 | 33150.5 | 32.11 | 16.60 | 0.00800000 | 52751.6 | 0.40888608 | 60.00 | 32.22 | 27.78 | 0.000 | 46742.96 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00776669 | 21.00 | 0.00776669 | 41.3123 | 22227.61 | 0.00 | 44393.73 | 44393.73 | 2.96538980 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.28 | 18.46 | 0.00800000 | 51905.4 | |
ROOM_1_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18448.389 | 18448.389 | 1.482874 | 0.00016139 | 460.363 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.482874 | 1.46865150 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 2.8569 | 2.914436 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 18448.39 | 18448.39 | 1.0000 | 1.46865150 | 1.482874 | 19.90 | 12.11 | 0.00751684 | 39076.1 | 32.22 | 16.63 | 0.00800000 | 52863.7 | 0.16137809 | 60.00 | 32.22 | 27.78 | 0.000 | 18448.39 | -7.90 | 0.00234317 | -7.90 | 0.06173502 | 4.1632 | 21.11 | 0.00774159 | 21.11 | 0.00774159 | 40.9017 | 7341.90 | 0.00 | 19504.62 | 19504.62 | 1.46865150 | 16.60 | 12.68 | 0.00751684 | 35711.5 | 29.64 | 17.52 | 0.00751684 | 48992.1 | |
ROOM_1_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 24546.828 | 19653.547 | 1.482874 | -999.0 | -999.000 | -999.0000 | 1.12774 | 1.00000 | 1020.4645 | 1004.8586 | 0.9904 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.482874 | 1.46865150 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 20341.68 | 20341.68 | 0.8287 | 1.46865150 | 1.482874 | 21.62 | 13.50 | 0.00840499 | 43084.9 | 9.37 | 8.87 | 0.00840499 | 30580.9 | -999.0 | -999.00 | -999.00 | -999.00 | 944.391 | 19397.29 | 33.39 | 0.00569673 | 15.22 | 0.06173502 | 4.1632 | 21.11 | 0.00852264 | 21.11 | 0.00852264 | 44.9708 | 16656.41 | 0.00 | 24558.84 | 17835.83 | 1.41065087 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
ROOM_2_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18287.298 | 18287.298 | 1.468537 | 0.00015999 | 456.289 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.468537 | 1.45445197 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 2.8320 | 2.888988 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 18287.30 | 18287.30 | 1.0000 | 1.45445197 | 1.468537 | 19.89 | 12.11 | 0.00751469 | 39058.7 | 32.22 | 16.63 | 0.00800000 | 52863.7 | 0.15996894 | 60.00 | 32.22 | 27.78 | 0.000 | 18287.30 | -7.90 | 0.00234317 | -7.90 | 0.06172779 | 4.2034 | 21.11 | 0.00774160 | 21.11 | 0.00774160 | 40.9018 | 7341.65 | 0.00 | 19330.67 | 19330.67 | 1.45445197 | 16.60 | 12.68 | 0.00751469 | 35706.0 | 29.65 | 17.52 | 0.00751469 | 48996.7 | |
ROOM_2_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 24309.500 | 19463.529 | 1.468537 | -999.0 | -999.000 | -999.0000 | 1.13056 | 1.00000 | 1020.4627 | 1004.8586 | 0.9904 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.468537 | 1.45445197 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 20191.20 | 20191.20 | 0.8306 | 1.45445197 | 1.468537 | 21.62 | 13.49 | 0.00840402 | 43079.7 | 9.37 | 8.87 | 0.00840402 | 30578.4 | -999.0 | -999.00 | -999.00 | -999.00 | 935.260 | 19255.94 | 33.21 | 0.00569645 | 15.16 | 0.06172779 | 4.2034 | 21.11 | 0.00852282 | 21.11 | 0.00852282 | 44.9718 | 16495.36 | 0.00 | 24321.40 | 17663.38 | 1.39701211 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
ROOM_3_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 116085.391 | 116085.391 | 8.159864 | 0.00101557 | 2846.134 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 8.159864 | 8.08160229 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 17.9771 | 18.338917 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 116085.39 | 116085.39 | 1.0000 | 8.08160229 | 8.159864 | 18.13 | 11.17 | 0.00720511 | 36484.8 | 32.22 | 16.63 | 0.00800000 | 52863.7 | 1.01546204 | 60.00 | 32.22 | 27.78 | 0.000 | 116085.39 | -7.90 | 0.00234317 | -7.90 | 0.83707151 | 10.2584 | 21.11 | 0.00776088 | 21.11 | 0.00776088 | 41.0013 | 42209.89 | 0.00 | 119321.57 | 119321.57 | 8.08160229 | 16.60 | 12.37 | 0.00720511 | 34922.2 | 31.10 | 17.76 | 0.00720511 | 49686.8 | |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 135074.730 | 108148.293 | 8.159864 | -999.0 | -999.000 | -999.0000 | 1.03736 | 1.00000 | 1020.0332 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 8.159864 | 8.08160229 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 110202.19 | 110202.19 | 0.8159 | 8.08160229 | 8.159864 | 22.52 | 13.61 | 0.00817299 | 43414.5 | 9.37 | 8.64 | 0.00817299 | 29996.3 | -999.0 | -999.00 | -999.00 | -999.00 | 5196.735 | 105005.46 | 34.88 | 0.00569904 | 15.70 | 0.83707151 | 10.2584 | 21.11 | 0.00845579 | 21.11 | 0.00845579 | 44.6219 | 91658.58 | 0.00 | 135140.85 | 98145.87 | 7.76244009 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
ROOM_4_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 112696.244 | 112696.244 | 7.857225 | 0.00098592 | 2759.945 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 7.857225 | 7.78186589 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 17.4523 | 17.803507 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 112696.24 | 112696.24 | 1.0000 | 7.78186589 | 7.857225 | 18.02 | 11.11 | 0.00718355 | 36312.6 | 32.22 | 16.63 | 0.00800000 | 52863.7 | 0.98581533 | 60.00 | 32.22 | 27.78 | 0.000 | 112696.24 | -7.90 | 0.00234317 | -7.90 | 0.83730041 | 10.6564 | 21.11 | 0.00776089 | 21.11 | 0.00776089 | 41.0014 | 42223.30 | 0.00 | 115628.09 | 115628.09 | 7.78186589 | 16.60 | 12.35 | 0.00718355 | 34867.7 | 31.19 | 17.77 | 0.00718355 | 49726.3 | |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 130064.979 | 104137.209 | 7.857225 | -999.0 | -999.000 | -999.0000 | 1.03549 | 1.00000 | 1020.4196 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 7.857225 | 7.78186589 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | Sensible | 106529.29 | 106529.29 | 0.8190 | 7.78186589 | 7.857225 | 22.60 | 13.81 | 0.00838083 | 44022.5 | 9.37 | 8.84 | 0.00838083 | 30520.0 | -999.0 | -999.00 | -999.00 | -999.00 | 5003.995 | 101525.29 | 35.10 | 0.00569938 | 15.77 | 0.83730041 | 10.6564 | 21.11 | 0.00870066 | 21.11 | 0.00870066 | 45.8988 | 88251.95 | 0.00 | 130128.65 | 94505.76 | 7.47454101 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
ROOM_5_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16300.774 | 16300.774 | 1.291485 | 0.00014261 | 406.028 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.291485 | 1.27909840 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 2.5244 | 2.575161 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 16300.77 | 16300.77 | 1.0000 | 1.27909840 | 1.291485 | 19.72 | 12.02 | 0.00748354 | 38809.2 | 32.22 | 16.63 | 0.00800000 | 52863.7 | 0.14259173 | 60.00 | 32.22 | 27.78 | 0.000 | 16300.77 | -7.90 | 0.00234317 | -7.90 | 0.06173502 | 4.7802 | 21.11 | 0.00774159 | 21.11 | 0.00774159 | 40.9017 | 7341.90 | 0.00 | 17184.32 | 17184.32 | 1.27909840 | 16.60 | 12.65 | 0.00748354 | 35627.2 | 29.79 | 17.54 | 0.00748354 | 49061.9 | |
ROOM_5_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 21378.665 | 17116.941 | 1.291485 | -999.0 | -999.000 | -999.0000 | 1.19188 | 1.00000 | 1020.4356 | 1004.8586 | 0.9904 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.291485 | 1.27909840 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 18568.18 | 18568.18 | 0.8685 | 1.27909840 | 1.291485 | 21.52 | 13.45 | 0.00838948 | 42937.3 | 9.37 | 8.85 | 0.00838948 | 30541.8 | -999.0 | -999.00 | -999.00 | -999.00 | 822.502 | 17745.68 | 29.59 | 0.00569088 | 13.95 | 0.06173502 | 4.7802 | 21.11 | 0.00852495 | 21.11 | 0.00852495 | 44.9828 | 14506.64 | 0.00 | 21389.13 | 15533.83 | 1.22858368 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
ROOM_6_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16159.318 | 16159.318 | 1.278898 | 0.00014137 | 402.450 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.278898 | 1.26663193 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 2.5025 | 2.552814 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 16159.32 | 16159.32 | 1.0000 | 1.26663193 | 1.278898 | 19.71 | 12.01 | 0.00748104 | 38789.1 | 32.22 | 16.63 | 0.00800000 | 52863.7 | 0.14135434 | 60.00 | 32.22 | 27.78 | 0.000 | 16159.32 | -7.90 | 0.00234317 | -7.90 | 0.06172779 | 4.8266 | 21.11 | 0.00774160 | 21.11 | 0.00774160 | 40.9018 | 7341.65 | 0.00 | 17031.50 | 17031.50 | 1.26663193 | 16.60 | 12.64 | 0.00748104 | 35620.8 | 29.80 | 17.54 | 0.00748104 | 49067.1 | |
ROOM_6_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 21170.303 | 16950.114 | 1.278898 | -999.0 | -999.000 | -999.0000 | 1.19873 | 1.00000 | 1020.4334 | 1004.8586 | 0.9904 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.278898 | 1.26663193 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | unknown | unknown | unknown | 7/21 09:40:00 | Sensible | 18471.65 | 18471.65 | 0.8725 | 1.26663193 | 1.278898 | 21.50 | 13.44 | 0.00838830 | 42919.5 | 9.37 | 8.85 | 0.00838830 | 30538.8 | -999.0 | -999.00 | -999.00 | -999.00 | 814.486 | 17657.17 | 29.21 | 0.00569029 | 13.82 | 0.06172779 | 4.8266 | 21.11 | 0.00852513 | 21.11 | 0.00852513 | 44.9838 | 14365.25 | 0.00 | 21180.67 | 15382.43 | 1.21660955 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
PTAC_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37292.413 | 37292.413 | 2.088438 | 0.00032625 | 882.175 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 2.088438 | 2.06840717 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 5.7751 | 5.891374 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 37292.41 | 37292.41 | 1.0000 | 2.06840717 | 2.088438 | 14.43 | 9.11 | 0.00657306 | 31115.1 | 32.11 | 16.60 | 0.00800000 | 52751.6 | 0.32621701 | 60.00 | 32.22 | 27.78 | 0.000 | 37292.41 | -7.90 | 0.00234317 | -7.90 | 0.47476218 | 22.7329 | 21.00 | 0.00781754 | 21.00 | 0.00781754 | 41.5790 | 12752.05 | 0.00 | 36223.23 | 36223.23 | 2.06840717 | 16.60 | 11.73 | 0.00657306 | 33322.0 | 33.82 | 18.15 | 0.00657306 | 50834.6 | |
PTAC_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 34571.058 | 27679.499 | 2.088438 | -999.0 | -999.000 | -999.0000 | 1.01539 | 1.00000 | 1020.7158 | 1004.8586 | 0.9904 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 2.088438 | 2.06840717 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | unknown | unknown | unknown | 7/21 14:40:00 | Sensible | 29760.10 | 29593.58 | 0.8608 | 2.06840717 | 2.088438 | 26.52 | 15.25 | 0.00854018 | 48430.3 | 12.26 | 10.12 | 0.00850000 | 33769.9 | -999.0 | -999.00 | -999.00 | -999.00 | 1330.054 | 28430.05 | 35.10 | 0.00569938 | 15.77 | 0.47476218 | 22.7329 | 24.00 | 0.00937598 | 24.00 | 0.00937598 | 41.4577 | 23454.00 | 0.00 | 34587.98 | 25119.48 | 1.98672072 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
ROOM_1_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5043.595 | 5043.595 | 0.409173 | 0.00004412 | 126.003 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.409173 | 0.40524863 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 0.7811 | 0.796776 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 5043.59 | 5043.59 | 1.0000 | 0.40524863 | 0.409173 | 20.02 | 12.23 | 0.00759946 | 39401.4 | 32.22 | 16.63 | 0.00800000 | 52863.7 | 0.04411906 | 60.00 | 32.22 | 27.78 | 0.000 | 5043.59 | -7.90 | 0.00234317 | -7.90 | 0.01543376 | 3.7719 | 21.11 | 0.00780550 | 21.11 | 0.00780550 | 41.2351 | 2467.98 | 0.00 | 5342.16 | 5342.16 | 0.40524863 | 16.60 | 12.76 | 0.00759946 | 35920.7 | 29.54 | 17.55 | 0.00759946 | 49103.1 | |
ROOM_1_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 6773.267 | 5423.052 | 0.409173 | -999.0 | -999.000 | -999.0000 | 1.12849 | 1.00000 | 1020.4813 | 1004.8586 | 0.9904 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.409173 | 0.40524863 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 5598.49 | 5598.49 | 0.8266 | 0.40524863 | 0.409173 | 21.58 | 13.49 | 0.00841406 | 43065.9 | 9.37 | 8.88 | 0.00841406 | 30603.7 | -999.0 | -999.00 | -999.00 | -999.00 | 260.588 | 5337.90 | 33.57 | 0.00569700 | 15.28 | 0.01543376 | 3.7719 | 21.11 | 0.00852057 | 21.11 | 0.00852057 | 44.9600 | 4596.04 | 0.00 | 6776.58 | 4921.48 | 0.38924437 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
ROOM_2_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4989.956 | 4989.956 | 0.404398 | 0.00004365 | 124.646 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.404398 | 0.40051902 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 0.7728 | 0.788302 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 4989.96 | 4989.96 | 1.0000 | 0.40051902 | 0.404398 | 20.00 | 12.22 | 0.00759725 | 39382.8 | 32.22 | 16.63 | 0.00800000 | 52863.7 | 0.04364986 | 60.00 | 32.22 | 27.78 | 0.000 | 4989.96 | -7.90 | 0.00234317 | -7.90 | 0.01543195 | 3.8160 | 21.11 | 0.00780570 | 21.11 | 0.00780570 | 41.2362 | 2470.49 | 0.00 | 5284.25 | 5284.25 | 0.40051902 | 16.60 | 12.76 | 0.00759725 | 35915.1 | 29.55 | 17.56 | 0.00759725 | 49108.6 | |
ROOM_2_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 6694.217 | 5359.760 | 0.404398 | -999.0 | -999.000 | -999.0000 | 1.13122 | 1.00000 | 1020.4794 | 1004.8586 | 0.9904 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.404398 | 0.40051902 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 5545.94 | 5545.94 | 0.8285 | 0.40051902 | 0.404398 | 21.58 | 13.49 | 0.00841302 | 43061.8 | 9.37 | 8.88 | 0.00841302 | 30601.1 | -999.0 | -999.00 | -999.00 | -999.00 | 257.547 | 5288.39 | 33.39 | 0.00569673 | 15.22 | 0.01543195 | 3.8160 | 21.11 | 0.00852078 | 21.11 | 0.00852078 | 44.9612 | 4542.40 | 0.00 | 6697.49 | 4864.05 | 0.38470155 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
ROOM_3_MULT9_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22119.405 | 22119.405 | 1.712349 | 0.00019351 | 549.314 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.712349 | 1.69592520 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 3.4254 | 3.494375 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 22119.40 | 22119.40 | 1.0000 | 1.69592520 | 1.712349 | 19.43 | 11.92 | 0.00749948 | 38551.2 | 32.22 | 16.63 | 0.00800000 | 52863.7 | 0.19349046 | 60.00 | 32.22 | 27.78 | 0.000 | 22119.40 | -7.90 | 0.00234317 | -7.90 | 0.09915400 | 5.7905 | 21.11 | 0.00781641 | 21.11 | 0.00781641 | 41.2916 | 12063.38 | 0.00 | 23208.75 | 23208.75 | 1.69592520 | 16.60 | 12.66 | 0.00749948 | 35667.5 | 30.03 | 17.64 | 0.00749948 | 49352.5 | |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 28345.448 | 22694.932 | 1.712349 | -999.0 | -999.000 | -999.0000 | 1.08379 | 1.00000 | 1020.4940 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.712349 | 1.69592520 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 23089.85 | 23089.85 | 0.8146 | 1.69592520 | 1.712349 | 21.91 | 13.61 | 0.00842087 | 43423.2 | 9.37 | 8.88 | 0.00842087 | 30620.9 | -999.0 | -999.00 | -999.00 | -999.00 | 1090.535 | 21999.32 | 34.99 | 0.00569921 | 15.74 | 0.09915400 | 5.7905 | 21.11 | 0.00858815 | 21.11 | 0.00858815 | 45.3128 | 19233.35 | 0.00 | 28359.32 | 20595.92 | 1.62894897 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23213.631 | 23213.631 | 1.613688 | 0.00020308 | 505.721 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 3.5949 | 3.667239 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 23213.63 | 23213.63 | 1.0000 | 1.59821046 | 1.613688 | 12.89 | 9.89 | 0.00800000 | 33150.5 | 32.11 | 16.60 | 0.00800000 | 52751.6 | 0.20306225 | 60.00 | 32.22 | 27.78 | 0.000 | 23213.63 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00788114 | 21.00 | 0.00788114 | 41.9133 | 9998.14 | 0.00 | 22047.60 | 22047.60 | 1.59821046 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.13 | 18.08 | 0.00800000 | 50729.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23366.540 | 23366.540 | 1.611334 | 0.00020442 | 509.822 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 3.6186 | 3.691395 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 23366.54 | 23366.54 | 1.0000 | 1.59588001 | 1.611334 | 12.89 | 9.89 | 0.00800000 | 33150.5 | 32.11 | 16.60 | 0.00800000 | 52751.6 | 0.20439983 | 60.00 | 32.22 | 27.78 | 0.000 | 23366.54 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00788311 | 21.00 | 0.00788311 | 41.9237 | 10170.27 | 0.00 | 22192.76 | 22192.76 | 1.59588001 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.24 | 18.12 | 0.00800000 | 50841.0 | |
PTAC_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18601.133 | 18601.133 | 1.330896 | 0.00016273 | 455.912 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.330896 | 1.31813085 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 2.8806 | 2.938566 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 18601.13 | 18601.13 | 1.0000 | 1.31813085 | 1.330896 | 18.27 | 11.38 | 0.00737912 | 37066.0 | 32.11 | 16.60 | 0.00800000 | 52751.6 | 0.16271422 | 60.00 | 32.22 | 27.78 | 0.000 | 18601.13 | -7.90 | 0.00234317 | -7.90 | 0.12561561 | 9.4384 | 21.00 | 0.00790397 | 21.00 | 0.00790397 | 42.0330 | 10888.04 | 0.00 | 19161.17 | 19161.17 | 1.31813085 | 16.60 | 12.54 | 0.00737912 | 35362.8 | 30.87 | 17.82 | 0.00737912 | 49899.4 | |
PTAC_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 22031.048 | 17639.275 | 1.330896 | -999.0 | -999.000 | -999.0000 | 1.10473 | 1.00000 | 1020.7429 | 1004.8586 | 0.9904 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.330896 | 1.31813085 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 18656.22 | 18501.63 | 0.8468 | 1.31813085 | 1.330896 | 25.05 | 14.78 | 0.00855479 | 46961.3 | 12.26 | 10.12 | 0.00850000 | 33770.0 | -999.0 | -999.00 | -999.00 | -999.00 | 847.601 | 17808.62 | 35.10 | 0.00569938 | 15.77 | 0.12561561 | 9.4384 | 24.00 | 0.00885239 | 24.00 | 0.00885239 | 39.1746 | 14946.73 | 0.00 | 22041.83 | 16007.85 | 1.26607465 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.50 | 0.00931606 | 37912.8 | |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_FLR_1 | RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LOBBY_FLR_1; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 157663.303 | 126157.070 | 9.149125 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4335 | 1004.8586 | 0.9904 | VAV_FLR_1 FAN | Fan:VariableVolume | 9.149125 | 9.06137459 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | Sensible | 149497.16 | 149497.16 | 0.9482 | 9.06137459 | 9.149125 | 27.43 | 15.43 | 0.00838835 | 48969.4 | 10.71 | 9.40 | 0.00838835 | 31912.0 | -999.0 | -999.00 | -999.00 | -999.00 | 20107.773 | 129389.39 | 35.10 | 0.00569938 | 15.77 | 2.83030000 | 30.9352 | 23.99 | 0.00959278 | 23.99 | 0.00959278 | 42.4121 | 89313.33 | 0.00 | 158119.30 | 114663.58 | 8.70351880 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.78 | 13.21 | 0.00922706 | 37155.1 | |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_1 | RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LOBBY_FLR_1; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 56787.376 | 56787.376 | 2.744737 | 0.00049680 | 912.261 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_FLR_1 FAN | Fan:VariableVolume | 9.149125 | 9.06137459 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 8.7942 | 8.971146 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 56787.38 | 56787.38 | 1.0000 | 2.71841238 | 2.744737 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 12.89 | 9.89 | 0.00800000 | 33150.5 | 0.49675006 | 60.00 | 32.22 | 27.78 | 0.000 | 56787.38 | -7.90 | 0.00234317 | -7.90 | 2.83030000 | 103.1173 | 21.00 | 0.00776101 | 21.00 | 0.00776101 | 41.2826 | 25069.43 | 0.00 | 50162.17 | 50162.17 | 2.71841238 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 21.08 | 9.15 | 0.00234317 | 27138.6 | |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_FLR_6 | BANQUET_FLR_6; DINING_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 132122.337 | 105813.728 | 7.052825 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9511 | 1004.8586 | 0.9904 | VAV_FLR_6 FAN | Fan:VariableVolume | 7.052825 | 6.98518098 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 125279.09 | 125279.09 | 0.9482 | 6.98518098 | 7.052825 | 28.98 | 15.72 | 0.00812883 | 49884.3 | 10.71 | 9.14 | 0.00812883 | 31256.7 | -999.0 | -999.00 | -999.00 | -999.00 | 15500.566 | 109778.52 | 35.10 | 0.00569938 | 15.77 | 3.16750000 | 44.9111 | 23.98 | 0.01010943 | 23.98 | 0.01010943 | 44.6875 | 68785.63 | 0.00 | 132504.46 | 96166.88 | 6.70931913 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.64 | 12.59 | 0.00906117 | 35573.1 | |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_6 | BANQUET_FLR_6; DINING_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 43775.930 | 43775.930 | 2.115848 | 0.00038297 | 703.239 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_FLR_6 FAN | Fan:VariableVolume | 7.052825 | 6.98518098 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 6.7792 | 6.915626 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 43775.93 | 43775.93 | 1.0000 | 2.09555429 | 2.115848 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 12.89 | 9.89 | 0.00800000 | 33150.5 | 0.38293186 | 60.00 | 32.22 | 27.78 | 0.000 | 43775.93 | -7.90 | 0.00234317 | -7.90 | 3.16750000 | 149.7036 | 21.00 | 0.00788205 | 21.00 | 0.00788206 | 41.9183 | 16132.76 | 0.00 | 38668.73 | 38668.73 | 2.09555429 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 21.08 | 9.15 | 0.00234317 | 27138.6 | |
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | VAV_FLR_0 | BASEMENT | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 62075.330 | 49701.234 | 3.749970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3883 | 1004.8586 | 0.9904 | VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 3.749971 | 3.71400455 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | Sensible | 31037.67 | 31037.67 | 1.0000 | 2.47600243 | 2.499980 | 24.85 | 14.56 | 0.00836400 | 46276.1 | 10.69 | 9.36 | 0.00836400 | 31821.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31037.67 | 27.74 | 0.00568807 | 13.32 | 0.85445887 | 34.1786 | 24.00 | 0.00915366 | 24.00 | 0.00915423 | 40.4923 | 36589.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_0 | BASEMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 66038.915 | 66038.915 | 3.749971 | 0.00032382 | 2244.943 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 3.749971 | 3.71400455 | 4197.9300 | 999.8980 | 5.53719731 | 54.44 | 82.22 | 27.78 | 645739.62 | 10.2269 | 5.847512 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 66038.92 | 66038.92 | 1.0000 | 3.71400455 | 3.749971 | 14.41 | 9.24 | 0.00671105 | 31448.5 | 32.11 | 16.60 | 0.00800000 | 52750.5 | 0.32378830 | 60.00 | 32.22 | 27.78 | 0.000 | 66038.92 | -7.90 | 0.00234317 | -7.90 | 0.85445887 | 22.7857 | 21.00 | 0.00800000 | 22.15 | 0.00234317 | 11.7159 | 0.00 | 0.00 | 64439.31 | 64439.31 | 3.71400455 | 16.60 | 11.87 | 0.00671105 | 33671.4 | 33.66 | 18.21 | 0.00671105 | 51021.7 | |
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 77473.270 | 62029.748 | 4.680160 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7028 | 1004.8586 | 0.9904 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 4.680161 | 4.63527262 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | Sensible | 38736.64 | 38528.30 | 1.0000 | 3.09018139 | 3.120107 | 24.00 | 14.41 | 0.00853322 | 45836.8 | 11.30 | 9.74 | 0.00850000 | 32787.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38736.64 | 32.67 | 0.00569561 | 14.99 | 0.00000000 | 0.0000 | 24.00 | 0.00853322 | 24.00 | 0.00853322 | 37.7815 | 45704.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51751.666 | 51751.666 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 4.680161 | 4.63527262 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 51751.67 | 51751.67 | 1.0000 | 4.63527262 | 4.680161 | 21.00 | 12.61 | 0.00762537 | 40469.1 | 32.11 | 16.60 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51751.67 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00762537 | 21.00 | 0.00762537 | 40.5710 | 2127.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42726.050 | 34200.921 | 2.334100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9270 | 1004.8586 | 0.9904 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.334098 | 2.31171104 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 21363.03 | 20927.24 | 1.0000 | 1.54114227 | 1.556067 | 27.14 | 15.54 | 0.00865381 | 49353.4 | 11.28 | 9.74 | 0.00850000 | 32775.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21363.03 | 34.88 | 0.00569904 | 15.70 | 0.67638938 | 43.4679 | 23.99 | 0.00985944 | 23.99 | 0.00986564 | 43.6175 | 22707.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45263.069 | 45263.069 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.334098 | 2.31171104 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 45263.07 | 45263.07 | 1.0000 | 2.31171104 | 2.334098 | 12.62 | 8.02 | 0.00623649 | 28429.3 | 32.11 | 16.60 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45263.07 | -7.90 | 0.00234317 | -7.90 | 0.67638938 | 28.9786 | 21.00 | 0.00782507 | 21.00 | 0.00782507 | 41.6197 | 8389.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 59155.830 | 47357.791 | 3.232450 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.5384 | 1004.8586 | 0.9904 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.232451 | 3.20144774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 29577.92 | 25600.60 | 1.0000 | 2.13429815 | 2.154967 | 25.08 | 15.55 | 0.00952065 | 49452.2 | 11.29 | 9.74 | 0.00850000 | 32778.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29577.92 | 33.89 | 0.00569749 | 15.38 | 0.36735036 | 17.0467 | 23.95 | 0.01001084 | 23.97 | 0.01001084 | 44.2997 | 31479.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46874.523 | 46874.523 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.232451 | 3.20144774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 46874.52 | 46874.52 | 1.0000 | 3.20144774 | 3.232451 | 17.54 | 10.72 | 0.00696671 | 35274.5 | 32.11 | 16.60 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46874.52 | -7.90 | 0.00234317 | -7.90 | 0.36735036 | 11.3645 | 20.80 | 0.00755952 | 21.00 | 0.00753217 | 40.0817 | 1978.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_FLR_1_OA_CONTROLLER | FixedDryBulb | 0.00 | 9.15 | - | |||
VAV_FLR_6_OA_CONTROLLER | FixedDryBulb | 0.00 | 7.05 | - | |||
VAV_FLR_0_OA_CONTROLLER | FixedDryBulb | 0.00 | 3.75 | - | |||
PSZ_LAUNDRY_OA_CONTROLLER | FixedDryBulb | 0.00 | 4.68 | - | |||
PSZ_CAFE_OA_CONTROLLER | FixedDryBulb | 0.68 | 2.33 | - | |||
PSZ_KITCHEN_OA_CONTROLLER | FixedDryBulb | 0.37 | 3.23 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_FLR_6_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_FLR_6_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1041.00 | 5378.00 | 116.00 |
RETAIL_1_FLR_1 | 3596.33 | 5101.17 | 1103.17 |
RETAIL_2_FLR_1 | 2228.83 | 5215.00 | 183.50 |
MECH_FLR_1 | 1526.50 | 5715.83 | 29.50 |
STORAGE_FLR_1 | 1546.00 | 6823.50 | 642.00 |
LAUNDRY_FLR_1 | 8729.67 | 3776.67 | 3776.67 |
CAFE_FLR_1 | 4349.50 | 3700.33 | 580.17 |
LOBBY_FLR_1 | 2970.50 | 3919.00 | 354.17 |
ROOM_1_FLR_3 | 1184.50 | 7510.50 | 774.17 |
ROOM_2_FLR_3 | 2296.50 | 7190.33 | 1404.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 841.83 | 8296.50 | 613.33 |
ROOM_5_FLR_3 | 1299.67 | 7469.83 | 784.50 |
ROOM_6_FLR_3 | 2205.83 | 7188.00 | 1366.50 |
CORRIDOR_FLR_3 | 5607.83 | 3058.50 | 3058.50 |
ROOM_1_FLR_6 | 2549.83 | 7355.83 | 1888.33 |
ROOM_2_FLR_6 | 3664.00 | 7100.83 | 2623.17 |
ROOM_3_MULT9_FLR_6 | 1818.17 | 7227.67 | 1129.17 |
BANQUET_FLR_6 | 3642.50 | 4072.83 | 665.67 |
DINING_FLR_6 | 3918.33 | 3266.17 | 627.00 |
KITCHEN_FLR_6 | 8515.17 | 6069.83 | 6069.83 |
CORRIDOR_FLR_6 | 5954.83 | 3861.17 | 3008.17 |
Facility | 8760.00 | 8760.00 | 7994.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 0.00 | 18.17 | 0.00 | 18.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 52.83 | 0.00 | 52.83 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 43.50 | 0.00 | 43.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.17 | 0.00 | 0.17 |
ROOM_2_FLR_6 | 0.00 | 12.67 | 0.00 | 12.67 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 65.33 | 0.00 | 65.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.899 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.306 | 0.137 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.428 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.653 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.677 | 0.051 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.171 | 0.147 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 5.534 | 0.108 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.779 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.357 | 0.177 | 0.000 | 0.058 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.353 | 0.178 | 0.000 | 0.035 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.394 | 0.079 | 0.000 | 0.099 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.361 | 0.177 | 0.000 | 0.058 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.178 | 0.000 | 0.044 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.068 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.358 | 0.177 | 0.000 | 0.070 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.354 | 0.178 | 0.000 | 0.040 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.417 | 0.144 | 0.000 | 0.111 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 5.266 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 5.485 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 19.975 | 0.148 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.053 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 0.629 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.255 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.928 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.411 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.432 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 0.000 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 3.202 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 1.245 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.108 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 4.268 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 4.195 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.000 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV_FLR_0 | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.8545 | 0.854 |
RETAIL_1_FLR_1 | VAV_FLR_1 | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV_FLR_1 | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV_FLR_1 | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV_FLR_1 | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | PSZ_CAFE | 82.56 | 142.30 | 748.35 | 188.86 | 0.6764 | 0.676 |
LOBBY_FLR_1 | VAV_FLR_1 | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 39.02 | 0.062 | ||
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 39.02 | 0.062 | ||
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | 24.52 | 0.837 | |||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 24.53 | 0.837 | ||
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 39.02 | 0.062 | ||
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 39.02 | 0.062 | ||
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 389.40 | 0.475 | ||
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 39.02 | 0.015 | ||
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 39.02 | 0.015 | ||
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 24.53 | 0.099 | ||
BANQUET_FLR_6 | VAV_FLR_6 | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV_FLR_6 | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | PSZ_KITCHEN | 12.90 | 22.24 | 314.87 | 103.30 | 0.3674 | 0.367 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 412.12 | 0.126 | ||
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 1.8982 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 37480381.61 | 0.00 | 37480381.61 | 0.00 | 37480381.61 | 26946214.98 | 0.00 | 4871.65 | 3888.35 | 0.00 |
RETAIL_1_FLR_1 | 5304046.67 | 0.00 | 5304046.67 | 315975.89 | 5620022.56 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 3793190.98 | 0.00 | 3793190.98 | 121967.09 | 3915158.07 | 2892943.94 | 2417.32 | 1365.23 | 4977.44 | 0.00 |
MECH_FLR_1 | 3675789.54 | 0.00 | 3675789.54 | 288257.75 | 3964047.29 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2206010.95 | 0.00 | 2206010.95 | 166308.84 | 2372319.79 | 1821682.01 | 2672.38 | 1634.23 | 4453.39 | 0.00 |
LAUNDRY_FLR_1 | 64515173.60 | 0.00 | 64515173.60 | 393601.23 | 64908774.84 | 0.00 | 0.00 | 0.00 | 7244.50 | 0.00 |
CAFE_FLR_1 | 35734787.76 | 0.00 | 35734787.76 | 698482.59 | 36433270.35 | 21330615.53 | 0.00 | 4711.60 | 4048.40 | 0.00 |
LOBBY_FLR_1 | 79474948.41 | 0.00 | 79474948.41 | 1995724.30 | 81470672.71 | 59728886.00 | 2202.58 | 1534.74 | 5022.69 | 0.00 |
ROOM_1_FLR_3 | 1478000.28 | 60154.55 | 1538154.83 | 183401.85 | 1721556.68 | 1946875.62 | 2430.29 | 5719.65 | 610.06 | 0.00 |
ROOM_2_FLR_3 | 1456935.27 | 35874.52 | 1492809.79 | 183387.86 | 1676197.65 | 1946647.51 | 2432.65 | 6023.97 | 303.38 | 0.00 |
ROOM_3_MULT19_FLR_3 | 4869255.82 | 0.00 | 4869255.82 | 51171.17 | 4920426.99 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 6974.55 |
ROOM_4_MULT19_FLR_3 | 19463972.09 | 63524.73 | 19527496.82 | 51185.17 | 19578681.99 | 26405105.73 | 2432.95 | 5738.53 | 588.52 | 0.00 |
ROOM_5_FLR_3 | 1492616.23 | 60313.46 | 1552929.70 | 183401.85 | 1736331.54 | 1946875.62 | 2430.91 | 5719.44 | 609.64 | 0.00 |
ROOM_6_FLR_3 | 1465155.14 | 45084.28 | 1510239.42 | 183387.86 | 1693627.28 | 1946647.51 | 2432.37 | 5907.50 | 420.13 | 0.00 |
CORRIDOR_FLR_3 | 2747650.25 | 0.00 | 2747650.25 | 221769.73 | 2969419.98 | 14972100.18 | 8760.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 369933.54 | 72010.15 | 441943.68 | 183439.96 | 625383.65 | 486718.90 | 2252.15 | 5721.04 | 786.81 | 0.00 |
ROOM_2_FLR_6 | 365894.09 | 40931.10 | 406825.19 | 183425.97 | 590251.16 | 486661.88 | 2301.91 | 6028.69 | 429.40 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2437364.76 | 72032.93 | 2509397.69 | 93854.31 | 2603251.99 | 3126920.42 | 2433.33 | 5718.67 | 608.00 | 0.00 |
BANQUET_FLR_6 | 45887451.70 | 0.00 | 45887451.70 | 447914.29 | 46335365.99 | 37458366.31 | 593.95 | 2323.02 | 5843.03 | 0.00 |
DINING_FLR_6 | 47779202.04 | 0.00 | 47779202.04 | 447914.29 | 48227116.32 | 37458366.31 | 0.00 | 791.91 | 7968.09 | 0.00 |
KITCHEN_FLR_6 | 54179311.19 | 0.00 | 54179311.19 | 400987.13 | 54580298.33 | 11584760.86 | 0.00 | 1519.83 | 7240.17 | 0.00 |
CORRIDOR_FLR_6 | 573020.67 | 0.00 | 573020.67 | 392463.83 | 965484.50 | 3961413.96 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.23E+10 | 6394824.22 | 0.23E+10 | 18481630.20 | 0.23E+10 | 0.43E+10 | 8760.00 | 7918.83 | 8760.00 | 6974.55 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.1885 | 0.0000 | 1.1885 | 0.0000 | 1.1885 | 0.8545 | 0.00 | 4871.65 | 3888.35 |
RETAIL_1_FLR_1 | 0.1682 | 0.0000 | 0.1682 | 0.0100 | 0.1782 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1203 | 0.0000 | 0.1203 | 0.0039 | 0.1241 | 0.0917 | 2417.32 | 1365.23 | 4977.44 |
MECH_FLR_1 | 0.1166 | 0.0000 | 0.1166 | 0.0091 | 0.1257 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0700 | 0.0000 | 0.0700 | 0.0053 | 0.0752 | 0.0578 | 2672.38 | 1634.23 | 4453.39 |
LAUNDRY_FLR_1 | 2.0458 | 0.0000 | 2.0458 | 0.0125 | 2.0582 | 0.0000 | 0.00 | 0.00 | 7244.50 |
CAFE_FLR_1 | 1.1331 | 0.0000 | 1.1331 | 0.0221 | 1.1553 | 0.6764 | 0.00 | 4711.60 | 4048.40 |
LOBBY_FLR_1 | 2.5201 | 0.0000 | 2.5201 | 0.0633 | 2.5834 | 1.8940 | 2202.58 | 1534.74 | 5022.69 |
ROOM_1_FLR_3 | 0.0469 | 0.0019 | 0.0488 | 0.0058 | 0.0546 | 0.0617 | 2430.29 | 5719.65 | 610.06 |
ROOM_2_FLR_3 | 0.0462 | 0.0011 | 0.0473 | 0.0058 | 0.0532 | 0.0617 | 2432.65 | 6023.97 | 303.38 |
ROOM_4_MULT19_FLR_3 | 0.6172 | 0.0020 | 0.6192 | 0.0016 | 0.6208 | 0.8373 | 2432.95 | 5738.53 | 588.52 |
ROOM_5_FLR_3 | 0.0473 | 0.0019 | 0.0492 | 0.0058 | 0.0551 | 0.0617 | 2430.91 | 5719.44 | 609.64 |
ROOM_6_FLR_3 | 0.0465 | 0.0014 | 0.0479 | 0.0058 | 0.0537 | 0.0617 | 2432.37 | 5907.50 | 420.13 |
CORRIDOR_FLR_3 | 0.0871 | 0.0000 | 0.0871 | 0.0070 | 0.0942 | 0.4748 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.0117 | 0.0023 | 0.0140 | 0.0058 | 0.0198 | 0.0154 | 2252.15 | 5721.04 | 786.81 |
ROOM_2_FLR_6 | 0.0116 | 0.0013 | 0.0129 | 0.0058 | 0.0187 | 0.0154 | 2301.91 | 6028.69 | 429.40 |
ROOM_3_MULT9_FLR_6 | 0.0773 | 0.0023 | 0.0796 | 0.0030 | 0.0825 | 0.0992 | 2433.33 | 5718.67 | 608.00 |
BANQUET_FLR_6 | 1.4551 | 0.0000 | 1.4551 | 0.0142 | 1.4693 | 1.1878 | 593.95 | 2323.02 | 5843.03 |
DINING_FLR_6 | 1.5151 | 0.0000 | 1.5151 | 0.0142 | 1.5293 | 1.1878 | 0.00 | 791.91 | 7968.09 |
KITCHEN_FLR_6 | 1.7180 | 0.0000 | 1.7180 | 0.0127 | 1.7307 | 0.3674 | 0.00 | 1519.83 | 7240.17 |
CORRIDOR_FLR_6 | 0.0182 | 0.0000 | 0.0182 | 0.0124 | 0.0306 | 0.1256 | 8760.00 | 0.00 | 0.00 |
Total Facility | 60.7908 | 0.2028 | 60.9936 | 0.4627 | 61.4563 | 73.9670 | 8760.00 | 7918.83 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_FLR_1 | 92650838.90 | 0.00 | 92650838.90 | 66941728.23 | 0.00 | 2.33 | 8757.67 | 0.00 |
VAV_FLR_6 | 91878536.45 | 0.00 | 91878536.45 | 74916732.61 | 583.13 | 3484.89 | 4691.98 | 0.00 |
VAV_FLR_0 | 36764899.63 | 0.00 | 36764899.63 | 26946214.98 | 4870.65 | 37.67 | 3851.68 | 0.00 |
PSZ_LAUNDRY | 63283564.57 | 0.00 | 63283564.57 | 0.00 | 0.00 | 0.00 | 7244.50 | 0.00 |
PSZ_CAFE | 35052602.70 | 0.00 | 35052602.70 | 21330615.53 | 4709.28 | 45.08 | 4005.64 | 0.00 |
PSZ_KITCHEN | 53145016.07 | 0.00 | 53145016.07 | 11584760.86 | 1519.50 | 2.17 | 7238.33 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_FLR_1 | 2.9379 | 0.0000 | 2.9379 | 2.1227 | 0.00 | 2.33 | 8757.67 |
VAV_FLR_6 | 2.9134 | 0.0000 | 2.9134 | 2.3756 | 583.13 | 3484.89 | 4691.98 |
VAV_FLR_0 | 1.1658 | 0.0000 | 1.1658 | 0.8545 | 4870.65 | 37.67 | 3851.68 |
PSZ_LAUNDRY | 2.0067 | 0.0000 | 2.0067 | 0.0000 | 0.00 | 0.00 | 7244.50 |
PSZ_CAFE | 1.1115 | 0.0000 | 1.1115 | 0.6764 | 4709.28 | 45.08 | 4005.64 |
PSZ_KITCHEN | 1.6852 | 0.0000 | 1.6852 | 0.3674 | 1519.50 | 2.17 | 7238.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_FLR_1 | 0.00 | 45.17 | 7199.33 | 0.00 | 0.00 | 0.00 | 1515.50 | 0.00 | 0.00 | 0.00 |
VAV_FLR_6 | 0.00 | 45.33 | 5809.31 | 0.00 | 0.00 | 0.00 | 2905.36 | 0.00 | 0.00 | 0.00 |
VAV_FLR_0 | 0.00 | 0.00 | 3900.71 | 0.00 | 0.00 | 0.00 | 4859.29 | 0.00 | 0.00 | 0.00 |
PSZ_LAUNDRY | 0.00 | 0.00 | 7244.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_CAFE | 0.00 | 4694.42 | 4065.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_KITCHEN | 0.00 | 1519.33 | 7240.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_FLR_1 | 0.0000 | 3.4240 | 3.0636 | 0.0000 | 0.0000 | 0.0000 | 2.3282 | 0.0000 | 0.0000 | 0.0000 |
VAV_FLR_6 | 0.0000 | 3.1211 | 3.1803 | 0.0000 | 0.0000 | 0.0000 | 2.3775 | 0.0000 | 0.0000 | 0.0000 |
VAV_FLR_0 | 0.0000 | 0.0000 | 1.5743 | 0.0000 | 0.0000 | 0.0000 | 0.8382 | 0.0000 | 0.0000 | 0.0000 |
PSZ_LAUNDRY | 0.0000 | 0.0000 | 2.4267 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ_CAFE | 0.0000 | 0.6635 | 1.6291 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ_KITCHEN | 0.0000 | 0.3604 | 1.9634 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 6 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1309 |
Defaulted Fields | 1279 |
Fields with Defaults | 4096 |
Autosized Fields | 364 |
Autosizable Fields | 530 |
Autocalculated Fields | 279 |
Autocalculatable Fields | 538 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6772.67 | 99713.45 | 10-JUN-05:00 | 467287.20 | 21-JUL-18:10 |
Electricity:Building | 3195.05 | 37866.17 | 02-JAN-02:10 | 208035.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 384.14 | 4218.04 | 02-JAN-02:10 | 29343.82 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 3187.96 | 37725.02 | 02-JAN-02:10 | 207793.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 241.03 | 2190.14 | 02-JAN-02:10 | 19711.29 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 241.03 | 2190.14 | 02-JAN-02:10 | 19711.29 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 22.10 | 252.63 | 02-JAN-02:10 | 1660.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.92 | 108.29 | 02-JAN-02:10 | 974.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.92 | 108.29 | 02-JAN-02:10 | 974.63 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 25.60 | 292.55 | 02-JAN-02:10 | 1922.56 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.80 | 125.40 | 02-JAN-02:10 | 1128.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.80 | 125.40 | 02-JAN-02:10 | 1128.63 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 41.66 | 441.91 | 02-JAN-02:10 | 3226.11 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 29.18 | 265.18 | 02-JAN-02:10 | 2386.66 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 29.18 | 265.18 | 02-JAN-02:10 | 2386.66 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 12.58 | 132.58 | 02-JAN-02:10 | 976.54 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 8.98 | 81.60 | 02-JAN-02:10 | 734.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 8.98 | 81.60 | 02-JAN-02:10 | 734.39 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 45.66 | 487.82 | 02-JAN-02:10 | 3526.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 31.32 | 284.60 | 02-JAN-02:10 | 2561.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 31.32 | 284.60 | 02-JAN-02:10 | 2561.44 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 350.46 | 3941.97 | 02-JAN-02:10 | 26504.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 201.46 | 1830.55 | 02-JAN-02:10 | 16474.99 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 201.46 | 1830.55 | 02-JAN-02:10 | 16474.99 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 35.36 | 389.80 | 01-JAN-02:10 | 2642.31 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 35.36 | 389.75 | 01-JAN-02:10 | 2642.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 492.14 | 5849.00 | 01-JAN-02:10 | 36399.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 297.14 | 2515.76 | 01-JAN-02:10 | 22870.56 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 297.14 | 2515.76 | 01-JAN-02:10 | 22870.56 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 492.27 | 5850.60 | 01-JAN-02:10 | 36409.55 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 297.22 | 2516.45 | 01-JAN-02:10 | 22876.81 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 297.22 | 2516.45 | 01-JAN-02:10 | 22876.81 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 35.36 | 389.80 | 01-JAN-02:10 | 2642.31 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 35.36 | 389.75 | 01-JAN-02:10 | 2642.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.84 | 97.45 | 01-JAN-02:10 | 660.58 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.83 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.83 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.84 | 97.44 | 01-JAN-02:10 | 660.50 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.78 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.78 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 58.30 | 692.83 | 01-JAN-02:10 | 4311.66 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.20 | 298.00 | 01-JAN-02:10 | 2709.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.20 | 298.00 | 01-JAN-02:10 | 2709.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 230.86 | 2749.09 | 02-JAN-02:10 | 11246.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 230.86 | 2749.09 | 02-JAN-02:10 | 11246.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 459.16 | 6380.86 | 02-JAN-02:10 | 19096.59 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.69 | 133.44 | 02-JAN-02:10 | 1200.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.69 | 133.44 | 02-JAN-02:10 | 1200.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1661.82 | 24317.47 | 02-JAN-02:10 | 89286.95 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1661.82 | 24317.47 | 02-JAN-02:10 | 89286.95 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 437.38 | 6106.28 | 01-JAN-00:10 | 16602.84 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.79 | 732.74 | 10-APR-22:30 | 2783.12 | 02-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 40.88 | 685.56 | 10-APR-22:20 | 2733.29 | 15-DEC-05:00 |
LowTempRefrigeration:Refrigeration:Electricity | 15.81 | 0.00 | 01-JAN-11:10 | 1306.77 | 15-AUG-05:20 |
MedTempRefrigeration:Refrigeration:Electricity | 20.90 | 634.57 | 15-DEC-04:10 | 713.53 | 01-JUL-14:00 |
Fans:Electricity | 1210.16 | 26985.92 | 04-JAN-08:00 | 58755.53 | 21-JUL-18:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2394.84 | 27543.32 | 18-JAN-15:00 | 252457.83 | 21-JUL-18:10 |
ExteriorEquipment:Electricity | 841.97 | 10954.76 | 02-JAN-02:20 | 50420.89 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.24 | 382.76 | 02-JAN-02:20 | 1343.17 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 6772.67 | 99713.45 | 10-JUN-05:00 | 467287.20 | 21-JUL-18:10 |
ElectricityPurchased:Plant | 6772.67 | 99713.45 | 10-JUN-05:00 | 467287.20 | 21-JUL-18:10 |
Cogeneration:ElectricityPurchased | 6772.67 | 99713.45 | 10-JUN-05:00 | 467287.20 | 21-JUL-18:10 |
General:Cogeneration:ElectricityPurchased | 6772.67 | 99713.45 | 10-JUN-05:00 | 467287.20 | 21-JUL-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6772.67 | 99713.45 | 10-JUN-05:00 | 467287.20 | 21-JUL-18:10 |
ElectricityNet:Plant | 6772.67 | 99713.45 | 10-JUN-05:00 | 467287.20 | 21-JUL-18:10 |
Cogeneration:ElectricityNet | 6772.67 | 99713.45 | 10-JUN-05:00 | 467287.20 | 21-JUL-18:10 |
General:Cogeneration:ElectricityNet | 6772.67 | 99713.45 | 10-JUN-05:00 | 467287.20 | 21-JUL-18:10 |
General:Fans:Electricity | 1210.16 | 26985.92 | 04-JAN-08:00 | 58755.53 | 21-JUL-18:20 |
Cooling:Electricity | 1162.44 | 0.00 | 01-JAN-02:40 | 193003.97 | 21-JUL-18:10 |
General:Cooling:Electricity | 1162.44 | 0.00 | 01-JAN-02:40 | 193003.97 | 21-JUL-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorLights:Electricity | 322.16 | 0.00 | 01-JAN-07:20 | 20502.98 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 322.16 | 0.00 | 01-JAN-07:20 | 20502.98 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 4.18 | 47.91 | 17-APR-17:10 | 791.25 | 15-DEC-05:00 |
General:Pumps:Electricity | 4.18 | 47.91 | 17-APR-17:10 | 791.25 | 15-DEC-05:00 |
WIRED_LTG_ELECTRICITY | 53.72 | 0.00 | 01-JAN-00:10 | 4267.60 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5323.69 | 25128.20 | 07-AUG-01:10 | 495135.16 | 18-JAN-20:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:HVAC | 28.54 | 0.00 | 01-JAN-00:10 | 18508.56 | 15-DEC-07:10 |
Heating:NaturalGas | 828.67 | 0.00 | 01-JAN-12:20 | 231956.11 | 15-DEC-05:00 |
General:Heating:NaturalGas | 28.54 | 0.00 | 01-JAN-00:10 | 18508.56 | 15-DEC-07:10 |
NaturalGas:Plant | 3506.31 | 11766.30 | 07-AUG-01:10 | 403366.36 | 18-JAN-22:00 |
WaterSystems:NaturalGas | 2706.18 | 11766.30 | 07-AUG-01:10 | 257083.15 | 02-FEB-21:30 |
Water Heater:WaterSystems:NaturalGas | 2706.18 | 11766.30 | 07-AUG-01:10 | 257083.15 | 02-FEB-21:30 |
Boiler:Heating:NaturalGas | 800.13 | 0.00 | 01-JAN-12:20 | 217373.53 | 15-DEC-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAR-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAR-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAR-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAR-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAR-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 08-MAR-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 17-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 11864.65 | 115019.51 | 10-NOV-15:00 | 1056445.32 | 20-JUL-18:20 |
EnergyTransfer:Building | 5899.58 | 85928.08 | 19-JAN-11:10 | 432592.95 | 20-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 710.70 | 8172.83 | 15-DEC-04:00 | 37636.76 | 22-JUL-10:40 |
Refrigeration:EnergyTransfer | 180.69 | 4015.60 | 10-APR-22:20 | 10342.09 | 05-SEP-06:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.34 | 2007.80 | 10-APR-22:20 | 5171.04 | 05-SEP-06:40 |
General:Refrigeration:EnergyTransfer | 90.34 | 2007.80 | 10-APR-22:20 | 5171.04 | 05-SEP-06:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.34 | 2007.80 | 10-APR-22:20 | 5171.04 | 05-SEP-06:40 |
EnergyTransfer:Plant | 1344.69 | 10972.67 | 16-AUG-01:10 | 196889.22 | 15-DEC-07:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.53 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.81 | 1986.32 | 15-DEC-04:10 | 2537.46 | 01-JUL-14:00 |
EnergyTransfer:Zone:BASEMENT | 429.52 | 5.14 | 07-MAR-17:10 | 28053.24 | 06-OCT-20:00 |
Heating:EnergyTransfer | 60.16 | 0.00 | 01-JAN-08:00 | 44949.46 | 21-DEC-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.04 | 0.00 | 01-JAN-00:10 | 1836.07 | 08-MAR-14:00 |
General:Heating:EnergyTransfer | 60.16 | 0.00 | 01-JAN-08:00 | 44949.46 | 21-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.04 | 0.00 | 01-JAN-00:10 | 1836.07 | 08-MAR-14:00 |
Cooling:EnergyTransfer | 5749.08 | 75880.00 | 06-FEB-04:00 | 429025.04 | 20-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 429.48 | 0.00 | 13-FEB-14:40 | 28053.24 | 06-OCT-20:00 |
General:Cooling:EnergyTransfer | 5749.08 | 75880.00 | 06-FEB-04:00 | 429025.04 | 20-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 429.48 | 0.00 | 13-FEB-14:40 | 28053.24 | 06-OCT-20:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 51.11 | 0.05 | 11-NOV-00:50 | 5415.76 | 05-OCT-13:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.95 | 0.00 | 01-JAN-00:10 | 1310.33 | 21-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.95 | 0.00 | 01-JAN-00:10 | 1310.33 | 21-JAN-07:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 50.15 | 0.00 | 01-JAN-04:30 | 5415.76 | 05-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 50.15 | 0.00 | 01-JAN-04:30 | 5415.76 | 05-OCT-13:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.60 | 605.63 | 19-JAN-11:20 | 2974.40 | 21-JUL-19:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.60 | 605.63 | 19-JAN-11:20 | 2974.40 | 21-JUL-19:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.60 | 605.63 | 19-JAN-11:20 | 2974.40 | 21-JUL-19:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 38.24 | 141.27 | 20-JAN-05:00 | 3380.48 | 21-JUL-19:50 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 38.24 | 141.27 | 20-JAN-05:00 | 3380.48 | 21-JUL-19:50 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 38.24 | 141.27 | 20-JAN-05:00 | 3380.48 | 21-JUL-19:50 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 18.57 | 0.00 | 31-JAN-24:00 | 1794.76 | 20-JUL-18:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.42 | 0.00 | 01-JAN-00:10 | 591.57 | 06-FEB-05:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.42 | 0.00 | 01-JAN-00:10 | 591.57 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 18.15 | 0.00 | 01-JAN-05:00 | 1794.76 | 20-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 18.15 | 0.00 | 01-JAN-05:00 | 1794.76 | 20-JUL-18:30 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.33 | 7676.83 | 06-FEB-05:00 | 39474.01 | 21-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.33 | 7676.83 | 06-FEB-05:00 | 39474.01 | 21-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.33 | 7676.83 | 06-FEB-05:00 | 39474.01 | 21-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 265.55 | 283.39 | 08-DEC-09:20 | 18298.18 | 01-OCT-12:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 265.55 | 283.39 | 08-DEC-09:20 | 18298.18 | 01-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 265.55 | 283.39 | 08-DEC-09:20 | 18298.18 | 01-OCT-12:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 869.83 | 14965.89 | 19-JAN-11:20 | 49605.91 | 21-JUL-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 869.83 | 14965.89 | 19-JAN-11:20 | 49605.91 | 21-JUL-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 869.83 | 14965.89 | 19-JAN-11:20 | 49605.91 | 21-JUL-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 93.67 | 0.00 | 01-JAN-08:00 | 16486.39 | 20-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 5.38 | 0.00 | 01-JAN-08:00 | 4544.20 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 5.38 | 0.00 | 01-JAN-08:00 | 4544.20 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 88.29 | 0.00 | 01-JAN-00:10 | 16486.39 | 20-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 88.29 | 0.00 | 01-JAN-00:10 | 16486.39 | 20-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 72.30 | 0.00 | 01-JAN-08:00 | 17118.36 | 26-MAY-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 8.83 | 0.00 | 01-JAN-08:00 | 5270.16 | 15-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 8.83 | 0.00 | 01-JAN-08:00 | 5270.16 | 15-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 63.47 | 0.00 | 01-JAN-00:10 | 17118.36 | 26-MAY-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 63.47 | 0.00 | 01-JAN-00:10 | 17118.36 | 26-MAY-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 617.83 | 0.00 | 01-JAN-00:40 | 76956.44 | 14-FEB-13:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 617.83 | 0.00 | 01-JAN-00:40 | 76956.44 | 14-FEB-13:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 617.83 | 0.00 | 01-JAN-00:40 | 76956.44 | 14-FEB-13:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 528.51 | 0.00 | 01-JAN-08:00 | 99984.95 | 11-SEP-20:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 9.67 | 0.00 | 01-JAN-00:10 | 20455.90 | 21-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 9.67 | 0.00 | 01-JAN-00:10 | 20455.90 | 21-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 518.83 | 0.00 | 01-JAN-04:10 | 99984.95 | 11-SEP-20:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 518.83 | 0.00 | 01-JAN-04:10 | 99984.95 | 11-SEP-20:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 98.39 | 0.00 | 01-JAN-08:00 | 14283.06 | 20-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 5.50 | 0.00 | 01-JAN-07:40 | 4229.14 | 20-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 5.50 | 0.00 | 01-JAN-07:40 | 4229.14 | 20-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 92.89 | 0.00 | 01-JAN-00:10 | 14283.06 | 20-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 92.89 | 0.00 | 01-JAN-00:10 | 14283.06 | 20-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 75.54 | 0.00 | 01-JAN-08:00 | 17154.15 | 18-JUN-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 8.48 | 0.00 | 01-JAN-07:50 | 4273.57 | 20-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 8.48 | 0.00 | 01-JAN-07:50 | 4273.57 | 20-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 67.05 | 0.00 | 01-JAN-00:10 | 17154.15 | 18-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 67.05 | 0.00 | 01-JAN-00:10 | 17154.15 | 18-JUN-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 159.87 | 0.00 | 01-JAN-02:40 | 15104.57 | 20-JUL-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 159.87 | 0.00 | 01-JAN-02:40 | 15104.57 | 20-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 159.87 | 0.00 | 01-JAN-02:40 | 15104.57 | 20-JUL-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 25.46 | 0.00 | 01-JAN-08:00 | 4700.71 | 20-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.05 | 0.00 | 01-JAN-08:00 | 1435.41 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.05 | 0.00 | 01-JAN-08:00 | 1435.41 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 21.41 | 0.00 | 01-JAN-00:10 | 4700.71 | 20-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 21.41 | 0.00 | 01-JAN-00:10 | 4700.71 | 20-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.50 | 0.00 | 01-JAN-08:00 | 4915.93 | 26-MAY-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.57 | 0.00 | 01-JAN-08:00 | 1660.41 | 15-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.57 | 0.00 | 01-JAN-08:00 | 1660.41 | 15-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.93 | 0.00 | 01-JAN-00:10 | 4915.93 | 26-MAY-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.93 | 0.00 | 01-JAN-00:10 | 4915.93 | 26-MAY-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 146.12 | 0.00 | 01-JAN-08:00 | 21485.46 | 18-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 9.62 | 0.00 | 01-JAN-00:10 | 5929.23 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 9.62 | 0.00 | 01-JAN-00:10 | 5929.23 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 136.50 | 0.00 | 01-JAN-00:50 | 21485.46 | 18-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 136.50 | 0.00 | 01-JAN-00:50 | 21485.46 | 18-OCT-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 467.24 | 8662.20 | 15-DEC-09:20 | 25007.89 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 467.24 | 8662.20 | 15-DEC-09:20 | 25007.89 | 21-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 467.24 | 8662.20 | 15-DEC-09:20 | 25007.89 | 21-JUL-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 495.58 | 9518.45 | 15-DEC-09:20 | 26209.94 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 495.58 | 9518.45 | 15-DEC-09:20 | 26209.94 | 21-JUL-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 495.58 | 9518.45 | 15-DEC-09:20 | 26209.94 | 21-JUL-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 620.35 | 5937.59 | 15-DEC-04:00 | 32602.78 | 22-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 620.35 | 5937.59 | 15-DEC-04:00 | 32602.78 | 22-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 76.14 | 0.00 | 01-JAN-00:10 | 10756.65 | 20-AUG-13:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.63 | 0.00 | 01-JAN-00:10 | 3643.95 | 21-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.63 | 0.00 | 01-JAN-00:10 | 3643.95 | 21-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 74.52 | 0.00 | 01-JAN-00:10 | 10756.65 | 20-AUG-13:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 74.52 | 0.00 | 01-JAN-00:10 | 10756.65 | 20-AUG-13:20 |
PlantLoopHeatingDemand:Facility | 1258.75 | 8667.52 | 08-AUG-00:20 | 192993.51 | 15-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 740.12 | 8667.52 | 08-AUG-00:20 | 55958.08 | 06-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 740.12 | 8667.52 | 08-AUG-00:20 | 55958.08 | 06-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 740.12 | 8667.52 | 08-AUG-00:20 | 55958.08 | 06-FEB-07:10 |
EnergyTransfer:HVAC | 4620.38 | 328.50 | 10-NOV-13:10 | 604250.41 | 31-JUL-20:20 |
HeatingCoils:EnergyTransfer | 541.47 | 0.00 | 01-JAN-12:20 | 169918.31 | 15-DEC-05:00 |
PlantLoopHeatingDemand:HVAC | 518.64 | 0.00 | 01-JAN-12:20 | 158252.25 | 15-DEC-05:00 |
HeatingCoils:PlantLoopHeatingDemand | 518.64 | 0.00 | 01-JAN-12:20 | 158252.25 | 15-DEC-05:00 |
CoolingCoils:EnergyTransfer | 4078.92 | 0.00 | 01-JAN-02:40 | 604245.15 | 31-JUL-20:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 740.12 | 8667.52 | 08-AUG-00:20 | 55958.08 | 06-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 740.12 | 8667.52 | 08-AUG-00:20 | 55958.08 | 06-FEB-07:10 |
Boilers:EnergyTransfer | 514.23 | 0.00 | 01-JAN-12:20 | 157078.59 | 15-DEC-05:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.038 | -429.481 | 0.000 | 0.000 | 137.731 | 241.034 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -92.427 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.954 | -50.155 | 0.000 | 0.000 | 14.890 | 11.918 | 10.186 | 35.342 | 0.000 | 0.225 | 0.001 | 0.000 | -13.891 | 0.000 | -3.202 | -6.266 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -40.601 | 0.000 | 0.000 | 16.336 | 13.801 | 11.795 | 0.000 | 0.000 | 0.087 | 0.000 | 0.000 | 0.000 | 0.000 | -1.314 | -0.104 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -38.243 | 0.000 | 0.000 | 3.525 | 29.185 | 12.471 | 0.000 | 0.000 | 0.205 | 0.000 | 0.000 | 0.000 | 0.000 | -3.017 | -4.126 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.420 | -18.152 | 0.000 | 0.000 | 2.836 | 8.980 | 3.598 | 0.000 | 0.000 | 0.122 | 3.817 | 0.000 | 0.000 | 0.000 | -1.620 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -597.329 | 0.000 | 0.000 | 10.551 | 5.547 | 658.131 | 0.000 | 0.000 | 0.278 | 0.000 | 0.000 | 0.000 | 0.000 | -4.494 | -72.684 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -265.550 | 0.000 | 0.000 | 189.028 | 31.322 | 14.341 | 98.298 | 0.000 | 0.493 | 0.003 | 0.000 | -40.878 | 0.000 | -7.394 | -19.660 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -869.837 | 0.000 | 0.000 | 541.241 | 201.459 | 148.998 | 131.049 | 0.000 | 1.418 | 0.000 | 0.000 | -56.500 | 0.000 | -22.046 | -75.783 |
ROOM_1_FLR_3 | 5.380 | -88.284 | 0.000 | 0.000 | 0.000 | 0.000 | 9.632 | 24.885 | 10.478 | 78.348 | 0.000 | 0.837 | 1.777 | 0.000 | -35.529 | 0.000 | -7.522 | -0.000 |
ROOM_2_FLR_3 | 8.833 | -63.463 | 0.000 | 0.000 | 0.000 | 0.000 | 9.375 | 24.882 | 10.477 | 54.176 | 0.000 | 0.742 | 0.979 | 0.000 | -38.150 | 0.000 | -7.849 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -617.819 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 297.141 | 194.997 | 454.210 | 0.000 | 1.393 | 0.004 | 0.000 | -264.062 | 0.000 | -52.925 | -12.935 |
ROOM_4_MULT19_FLR_3 | 9.673 | -518.810 | 0.000 | 0.000 | 0.000 | 0.000 | 180.033 | 297.222 | 195.050 | 124.176 | 0.000 | 4.116 | 0.005 | 0.000 | -208.306 | 0.000 | -58.370 | -24.784 |
ROOM_5_FLR_3 | 5.505 | -92.887 | 0.000 | 0.000 | 0.000 | 0.000 | 9.620 | 24.885 | 10.478 | 82.063 | 0.000 | 0.836 | 1.377 | 0.000 | -34.314 | 0.000 | -7.563 | -0.001 |
ROOM_6_FLR_3 | 8.484 | -67.050 | 0.000 | 0.000 | 0.000 | 0.000 | 9.389 | 24.882 | 10.477 | 56.814 | 0.000 | 0.741 | 0.355 | 0.000 | -35.936 | 0.000 | -8.155 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | -159.868 | 0.000 | 0.000 | 0.000 | 0.000 | 105.583 | 92.258 | 0.000 | 66.097 | 0.000 | 0.621 | 0.000 | 0.000 | -50.793 | 0.000 | -10.123 | -43.775 |
ROOM_1_FLR_6 | 4.054 | -21.405 | 0.000 | 0.000 | 0.000 | 0.000 | 2.414 | 6.221 | 2.620 | 19.429 | 0.000 | 0.210 | 0.000 | 0.000 | -8.654 | 0.000 | -1.898 | -2.992 |
ROOM_2_FLR_6 | 5.570 | -15.924 | 0.000 | 0.000 | 0.000 | 0.000 | 2.349 | 6.220 | 2.619 | 13.423 | 0.000 | 0.184 | 0.000 | 0.000 | -9.294 | 0.000 | -1.966 | -3.182 |
ROOM_3_MULT9_FLR_6 | 9.623 | -136.494 | 0.000 | 0.000 | 0.000 | 0.000 | 21.661 | 35.197 | 23.098 | 106.689 | 0.000 | 1.063 | 0.001 | 0.000 | -40.209 | 0.000 | -9.536 | -11.091 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -467.242 | 0.000 | 0.000 | 320.462 | 55.004 | 175.857 | 12.138 | 0.000 | 0.310 | 0.000 | 0.000 | -28.342 | 0.000 | -4.951 | -63.236 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -495.582 | 0.000 | 0.000 | 317.894 | 55.004 | 175.857 | 11.867 | 0.000 | 0.309 | 0.000 | 0.000 | -29.165 | 0.000 | -5.023 | -31.161 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -620.342 | 0.000 | 0.000 | 27.944 | 14.685 | 554.015 | 33.603 | 0.000 | 0.277 | 16.446 | 0.000 | -22.017 | 0.000 | -4.610 | -0.000 |
CORRIDOR_FLR_6 | 1.628 | -74.512 | 0.000 | 0.000 | 0.000 | 0.000 | 29.018 | 24.410 | 0.000 | 33.067 | 0.000 | 0.271 | 11.929 | 0.000 | -21.530 | 0.000 | -4.282 | -0.000 |
Total Facility | 58.749 | -1856.518 | 1.411 | -3892.513 | 0.000 | 0.000 | 1961.511 | 1526.141 | 2368.647 | 1410.790 | 0.000 | 14.736 | 36.693 | 0.000 | -937.569 | 0.000 | -227.861 | -464.208 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-OCT-20:00 | 0.00 | 0.00 | 0.00 | -28057.72 | 0.00 | 0.00 | 5183.68 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6469.77 |
RETAIL_1_FLR_1 | 05-OCT-13:10 | 0.00 | 0.00 | 0.00 | -5414.80 | 0.00 | 0.00 | 150.60 | 270.73 | 252.59 | 6017.69 | 0.00 | 17.13 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1293.94 |
RETAIL_2_FLR_1 | 21-JUL-19:10 | 0.00 | 0.00 | 0.00 | -2974.87 | 0.00 | 0.00 | 610.39 | 1128.63 | 793.93 | 0.00 | 0.00 | 35.35 | 406.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 21-JUL-19:50 | 0.00 | 0.00 | 0.00 | -3380.64 | 0.00 | 0.00 | 129.08 | 2386.66 | 839.45 | 0.00 | 0.00 | 62.38 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -36.93 |
STORAGE_FLR_1 | 20-JUL-18:30 | 0.00 | 0.00 | 0.00 | -1794.90 | 0.00 | 0.00 | 99.29 | 652.79 | 229.41 | 0.00 | 0.00 | 54.20 | 759.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 21-JUL-20:00 | 0.00 | 0.00 | 0.00 | -39471.21 | 0.00 | 0.00 | 408.84 | 453.60 | 44299.38 | 0.00 | 0.00 | 77.86 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5768.47 |
CAFE_FLR_1 | 01-OCT-12:00 | 0.00 | 0.00 | 0.00 | -18299.81 | 0.00 | 0.00 | 2968.38 | 853.81 | 406.43 | 17596.22 | 0.00 | 34.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3559.24 |
LOBBY_FLR_1 | 21-JUL-20:10 | 0.00 | 0.00 | 0.00 | -49612.88 | 0.00 | 0.00 | 23501.58 | 14644.43 | 9501.36 | 437.54 | 0.00 | 389.20 | 1138.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 04-FEB-16:12 | 0.00 | -20594.39 | 0.00 | 0.00 | 0.00 | 0.00 | 130.72 | 632.06 | 221.25 | 11589.23 | 0.00 | 0.00 | 8390.42 | 0.00 | -0.00 | 0.00 | -369.29 | 0.00 |
ROOM_2_FLR_3 | 09-JUN-18:51 | 0.00 | -21357.98 | 0.00 | 0.00 | 0.00 | 0.00 | 275.88 | 1704.45 | 484.60 | 4189.20 | 0.00 | 0.00 | 14806.46 | 0.00 | -0.00 | 0.00 | -102.60 | 0.00 |
ROOM_3_MULT19_FLR_3 | 14-FEB-13:00 | 0.00 | -76951.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6403.76 | 2352.88 | 101253.76 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -882.06 | -32176.58 |
ROOM_4_MULT19_FLR_3 | 04-MAR-09:02 | 0.00 | -123076.71 | 0.00 | 0.00 | 0.00 | 0.00 | 2627.63 | 12811.01 | 12159.85 | 0.00 | 0.00 | 0.00 | 106738.42 | 0.00 | -8786.05 | 0.00 | -2474.16 | 0.00 |
ROOM_5_FLR_3 | 28-NOV-09:02 | 0.00 | -18496.52 | 0.00 | 0.00 | 0.00 | 0.00 | 87.14 | 842.75 | 453.05 | 11650.74 | 0.00 | 0.00 | 6010.30 | 0.00 | -0.00 | 0.00 | -547.45 | 0.00 |
ROOM_6_FLR_3 | 10-JUN-08:51 | 0.00 | -18916.83 | 0.00 | 0.00 | 0.00 | 0.00 | 107.48 | 1072.46 | 653.15 | 10352.61 | 0.00 | 0.00 | 6876.39 | 0.00 | -0.00 | 0.00 | -145.27 | 0.00 |
CORRIDOR_FLR_3 | 20-JUL-18:30 | 0.00 | -15104.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4080.35 | 6706.42 | 0.00 | 4082.37 | 0.00 | 288.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -52.68 |
ROOM_1_FLR_6 | 26-MAY-18:01 | 0.00 | -5628.66 | 0.00 | 0.00 | 0.00 | 0.00 | 83.88 | 426.16 | 121.16 | 2164.62 | 0.00 | 0.00 | 2835.87 | 0.00 | -0.00 | 0.00 | -3.03 | 0.00 |
ROOM_2_FLR_6 | 09-JUN-18:51 | 0.00 | -5874.65 | 0.00 | 0.00 | 0.00 | 0.00 | 68.97 | 426.11 | 121.15 | 1008.15 | 0.00 | 0.00 | 4276.35 | 0.00 | -0.00 | 0.00 | -26.08 | 0.00 |
ROOM_3_MULT9_FLR_6 | 04-FEB-16:12 | 0.00 | -24811.59 | 0.00 | 0.00 | 0.00 | 0.00 | 294.12 | 894.00 | 487.74 | 7830.60 | 0.00 | 0.00 | 15740.92 | 0.00 | -0.00 | 0.00 | -435.79 | 0.00 |
BANQUET_FLR_6 | 21-JUL-21:10 | 0.00 | 0.00 | 0.00 | -25027.18 | 0.00 | 0.00 | 15641.59 | 2998.74 | 6747.90 | 227.92 | 0.00 | 75.78 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -664.76 |
DINING_FLR_6 | 21-JUL-21:10 | 0.00 | 0.00 | 0.00 | -26230.12 | 0.00 | 0.00 | 15641.48 | 2998.74 | 6747.90 | 207.75 | 0.00 | 75.78 | 558.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 22-JUL-10:40 | 0.00 | 0.00 | 0.00 | -32589.03 | 0.00 | 0.00 | 463.82 | 333.59 | 24375.41 | 4248.40 | 0.00 | 110.34 | 3057.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 20-AUG-13:20 | 0.00 | -10756.52 | 0.00 | 0.00 | 0.00 | 0.00 | 308.46 | 443.61 | 0.00 | 4051.70 | 0.00 | 108.23 | 5844.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-OCT-18:02 | 0.00 | -266744.82 | 0.00 | -188425.44 | 0.00 | 0.00 | 73663.84 | 107831.13 | 120597.93 | 0.00 | 0.00 | 1276.03 | 168047.60 | 0.00 | -15811.70 | 0.00 | -434.57 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-MAR-14:00 | 0.00 | 0.00 | 1835.95 | 0.00 | 0.00 | 0.00 | 1533.08 | 5475.36 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12393.22 |
RETAIL_1_FLR_1 | 21-JAN-07:05 | 0.00 | 0.00 | 1310.24 | 0.00 | 0.00 | 0.00 | 447.48 | 324.88 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1588.08 | 0.00 | -314.07 | -469.13 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 06-FEB-05:00 | 0.00 | 0.00 | 591.57 | 0.00 | 0.00 | 0.00 | 151.76 | 81.60 | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -141.95 | -733.95 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 17-JAN-09:02 | 14224.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.63 | 842.75 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1863.89 | 0.00 | -584.29 | -13179.41 |
ROOM_2_FLR_3 | 15-DEC-09:02 | 15618.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.88 | 842.65 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2763.66 | 0.00 | -684.12 | -13574.79 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 14-DEC-16:12 | 79388.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5244.85 | 6405.51 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16343.35 | 0.00 | -2509.28 | -75912.30 |
ROOM_5_FLR_3 | 20-JAN-09:02 | 13178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.29 | 842.75 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1440.39 | 0.00 | -596.40 | -12545.17 |
ROOM_6_FLR_3 | 20-JAN-09:02 | 13141.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.59 | 842.65 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1522.64 | 0.00 | -588.84 | -12434.33 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 20-JAN-09:02 | 4068.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 210.69 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -414.01 | 0.00 | -149.04 | -3856.75 |
ROOM_2_FLR_6 | 15-DEC-09:02 | 4304.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 210.66 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -677.15 | 0.00 | -171.30 | -3807.38 |
ROOM_3_MULT9_FLR_6 | 20-JAN-09:02 | 17728.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.86 | 1192.00 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1723.55 | 0.00 | -684.33 | -17753.00 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 21-JAN-07:10 | 3643.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916.66 | 665.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2302.34 | 0.00 | -391.45 | -2532.01 |
Total Facility | 21-DEC-16:12 | 47312.51 | 96073.69 | 411.51 | -96073.69 | 0.00 | 0.00 | 59366.23 | 33804.24 | 74028.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74320.10 | 0.00 | -14403.99 | -126198.50 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_FLR_1 | 9.1930 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.1491 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_6 | 7.0528 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 7.0528 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_0 | 3.7500 | 0.0000 | 106.4990 | 1.0000 | Calculated from schedules | 0.8545 | 3.7500 | 0.2279 | 1.0000 | Not calculated | 0.8545 | 0.2279 | ||
PSZ_LAUNDRY | 4.6802 | 0.0000 | 8.4000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6802 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PSZ_CAFE | 2.3341 | 0.0000 | 142.3000 | 1.0000 | Calculated from schedules | 0.6764 | 2.3341 | 0.2898 | 1.0000 | Not calculated | 0.6764 | 0.2898 | ||
PSZ_KITCHEN | 3.2325 | 0.0000 | 22.2380 | 1.0000 | Calculated from schedules | 0.3674 | 3.2325 | 0.1136 | 1.0000 | Not calculated | 0.3674 | 0.1136 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_FLR_1 | 4.5965 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.5440 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_6 | 3.5264 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2250 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_0 | 1.1250 | 0.0000 | 106.4990 | 1.0000 | Calculated from schedules | 0.8545 | 1.1250 | 1.0000 | 1.0000 | Not calculated | 0.8545 | 0.7595 | ||
PSZ_LAUNDRY | 4.6802 | 0.0000 | 8.4000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6802 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PSZ_CAFE | 2.3341 | 0.0000 | 142.3000 | 1.0000 | Calculated from schedules | 0.6764 | 2.3341 | 1.0000 | 1.0000 | Not calculated | 0.6764 | 0.2898 | ||
PSZ_KITCHEN | 3.2325 | 0.0000 | 22.2380 | 1.0000 | Calculated from schedules | 0.3674 | 3.2325 | 1.0000 | 1.0000 | Not calculated | 0.3674 | 0.1136 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV_FLR_0 | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.8545 | 1.0000 | 0.8545 | 1.000 | 0.8545 |
RETAIL_1_FLR_1 | VAV_FLR_1 | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV_FLR_1 | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | PSZ_CAFE | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.6764 | 1.0000 | 0.6764 | 1.000 | 0.6764 |
LOBBY_FLR_1 | VAV_FLR_1 | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV_FLR_6 | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.3674 | 1.0000 | 0.3674 | 1.000 | 0.3674 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_FLR_1 | 0.00 | 0.001240 | 1711.9288 | 0.0000 | 0.0000 | 0.0000 | |
VAV_FLR_6 | 0.00 | 0.003581 | 663.3149 | 0.0000 | 0.0000 | 0.0000 | |
VAV_FLR_0 | 0.000000 | 106.50 | 0.000432 | 1978.8302 | 0.8545 | 0.8545 | 0.8545 |
PSZ_LAUNDRY | 0.000000 | 8.40 | 0.000000 | 78.0395 | 0.0000 | 0.0000 | 0.0000 |
PSZ_CAFE | 0.000000 | 142.30 | 0.003581 | 188.8619 | 0.6764 | 0.6764 | 0.6764 |
PSZ_KITCHEN | 0.000000 | 22.24 | 0.003556 | 103.3045 | 0.3674 | 0.3674 | 0.3674 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV_FLR_0 | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 3.7500 | 3.7500 | 1.1250 | No | 0.8545 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5834 | 0.5834 | 0.1750 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4084 | 0.4084 | 0.1450 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4616 | 0.4616 | 0.1385 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2356 | 0.2356 | 0.0914 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6802 | 4.6802 | 4.6802 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | PSZ_CAFE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3341 | 2.3341 | 2.3341 | No | 0.6764 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5040 | 7.5040 | 2.9941 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4481 | 3.4481 | 1.6137 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.6048 | 3.6048 | 1.6113 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.2325 | 3.2325 | 3.2325 | No | 0.3674 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_FLR_1 | 9.1930 | 9.1491 | 9.1930 | 3.5440 | 0.0000 | 1.0000 |
VAV_FLR_6 | 7.0528 | 7.0528 | 7.0528 | 3.2250 | 0.0000 | 1.0000 |
VAV_FLR_0 | 3.7500 | 3.7500 | 3.7500 | 1.1250 | 0.8545 | 1.0000 |
PSZ_LAUNDRY | 4.6802 | 4.6802 | 4.6802 | 4.6802 | 0.0000 | 1.0000 |
PSZ_CAFE | 2.3341 | 2.3341 | 2.3341 | 2.3341 | 0.6764 | 1.0000 |
PSZ_KITCHEN | 3.2325 | 3.2325 | 3.2325 | 3.2325 | 0.3674 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV_FLR_0 | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 1.1250 | 1.1250 | 1.1250 | No | 0.8545 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2917 | 0.2917 | 0.1750 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2042 | 0.2042 | 0.1450 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2308 | 0.2308 | 0.1385 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1178 | 0.1178 | 0.0914 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6802 | 4.6802 | 4.6802 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | PSZ_CAFE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3341 | 2.3341 | 2.3341 | No | 0.6764 | 0.7238 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7520 | 3.7520 | 2.9941 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7240 | 1.7240 | 1.6137 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8024 | 1.8024 | 1.6113 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.2325 | 3.2325 | 3.2325 | No | 0.3674 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_FLR_1 | 4.5965 | 3.5440 | 3.5440 | 3.5440 | 0.0000 | 1.0000 |
VAV_FLR_6 | 3.5264 | 3.2250 | 3.2250 | 3.2250 | 0.0000 | 1.0000 |
VAV_FLR_0 | 1.1250 | 1.1250 | 1.1250 | 1.1250 | 0.8545 | 1.0000 |
PSZ_LAUNDRY | 4.6802 | 4.6802 | 4.6802 | 4.6802 | 0.0000 | 1.0000 |
PSZ_CAFE | 2.3341 | 2.3341 | 2.3341 | 2.3341 | 0.6764 | 1.0000 |
PSZ_KITCHEN | 3.2325 | 3.2325 | 3.2325 | 3.2325 | 0.3674 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 65.33 |
Number of hours not met | 65.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 28.54 | 18508.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 800.13 | 217373.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1162.44 | 193003.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1526.14 | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 322.16 | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 15.55 | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 11.51 | 365.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.24 | 1343.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1210.16 | 58755.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 4.18 | 791.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 2706.18 | 257083.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.81 | 1306.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 20.90 | 713.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1705.61 | 6772.67 |
Natural Gas | 1788.84 | 5323.69 |
Additional | 0.00 | 0.00 |
Total | 3494.45 | 12096.35 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 134.52 |
Space Heating | 0.00 |
Space Cooling | 102.46 |
Fans (All) | 106.67 |
Service Water Heating | 0.00 |
Receptacle Equipment | 146.48 |
Miscellaneous (All) | 596.96 |
Subtotal | 596.96 |
Natural Gas [MJ/m2] | |
Space Heating | 73.04 |
Service Water Heating | 238.53 |
Miscellaneous (All) | 469.24 |
Subtotal | 469.24 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.62 |
Space Heating | 6.85 |
Space Cooling | 9.61 |
Fans (All) | 10.00 |
Service Water Heating | 22.37 |
Receptacle Equipment | 28.53 |
Miscellaneous | 10.02 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 3061. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 3061. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 3061. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | RETAIL_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | RETAIL_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8640.17 | 119.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8609.33 | 150.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8607.33 | 152.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8607.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 152.67 | 0.00 | 0.00 | 0.00 |
Average | 8740.77 | 19.23 | 0.00 | 0.00 | 0.00 |
Sum | 192296.83 | 423.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4125.17 | 28.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4152.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4106.17 | 47.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 47.83 | 0.00 | 0.00 | 0.00 |
Average | 288883.47 | 3.58 | 0.00 | 0.00 | 0.00 |
Sum | 6355436.33 | 78.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8715.33 | 44.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8683.67 | 76.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8725.50 | 34.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8594.50 | 165.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 7020.50 | 1739.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8668.33 | 91.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 7854.83 | 905.17 | 0.00 | 0.00 | 0.00 |
Min | 7020.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1739.50 | 0.00 | 0.00 | 0.00 |
Average | 8620.35 | 139.65 | 0.00 | 0.00 | 0.00 |
Sum | 189647.67 | 3072.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529053.00 | 278.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37183.33 | 19.67 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 705748.00 | 4669.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2114985.67 | 443.33 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4123.67 | 30.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4136.83 | 17.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4129.50 | 24.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 81357.33 | 19000.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4118.17 | 35.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245379.00 | 336.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245491.00 | 224.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108169.00 | 100.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 96308.33 | 9637.67 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2114985.67 | 19000.67 | 0.00 | 0.00 | 0.00 |
Average | 287304.49 | 1582.55 | 0.00 | 0.00 | 0.00 |
Sum | 6320698.83 | 34816.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:28
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389525E+11 | 22594.15 | 26-JAN-04:00 | -7.8 | -10.0 | 0.719072E+10 | 4836.74 | 09-JAN-22:30 | -7.8 | -10.0 |
February | 0.300486E+11 | 21611.86 | 01-FEB-04:00 | -6.7 | -7.9 | 0.620234E+10 | 4836.80 | 14-FEB-22:30 | 10.60 | 3.54 |
March | 0.256120E+11 | 18223.58 | 30-MAR-06:00 | -2.2 | -3.1 | 0.735855E+10 | 4836.97 | 13-MAR-21:10 | -2.2 | -3.1 |
April | 0.224643E+11 | 17487.94 | 28-APR-21:00 | 20.00 | 7.20 | 0.774298E+10 | 4837.23 | 14-APR-21:00 | 20.00 | 7.20 |
May | 0.248510E+11 | 18363.80 | 19-MAY-20:54 | 23.30 | 8.29 | 0.820888E+10 | 4837.40 | 23-MAY-21:10 | 16.02 | 11.93 |
June | 0.292134E+11 | 20604.00 | 29-JUN-21:00 | 25.60 | 13.69 | 0.799812E+10 | 4837.47 | 05-JUN-21:10 | 25.60 | 13.69 |
July | 0.359734E+11 | 22856.13 | 21-JUL-21:00 | 30.00 | 14.72 | 0.823284E+10 | 4837.41 | 27-JUL-23:10 | 20.92 | 14.96 |
August | 0.405452E+11 | 24566.05 | 18-AUG-20:00 | 27.20 | 13.67 | 0.826770E+10 | 4837.44 | 10-AUG-23:10 | 27.20 | 13.67 |
September | 0.447474E+11 | 26974.81 | 29-SEP-20:00 | 22.20 | 12.39 | 0.797745E+10 | 4837.47 | 05-SEP-23:10 | 22.20 | 12.39 |
October | 0.485389E+11 | 28053.24 | 06-OCT-20:00 | 19.40 | 11.28 | 0.823055E+10 | 4837.45 | 03-OCT-00:49 | 19.40 | 11.28 |
November | 0.449052E+11 | 27420.68 | 01-NOV-20:00 | 7.80 | 4.71 | 0.794065E+10 | 4837.39 | 09-NOV-22:10 | 8.43 | 6.92 |
December | 0.436260E+11 | 25573.40 | 01-DEC-21:00 | 9.40 | 2.54 | 0.777949E+10 | 4837.15 | 01-DEC-23:10 | 6.78 | 1.32 |
Annual Sum or Average | 0.429478E+12 | 0.931303E+11 | ||||||||
Minimum of Months | 0.224643E+11 | 17487.94 | -7.8 | -10.0 | 0.620234E+10 | 4836.74 | -7.8 | -10.0 | ||
Maximum of Months | 0.485389E+11 | 28053.24 | 30.00 | 14.72 | 0.826770E+10 | 4837.47 | 27.20 | 14.96 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278933E+10 | 4823.05 | 01-JAN-13:40 | 14.83 | 5.43 | 0.661082E+09 | 426.69 | 09-JAN-22:10 | 6.60 | 0.62 |
February | 0.277979E+10 | 5267.39 | 14-FEB-13:30 | 20.00 | 6.81 | 0.607545E+09 | 464.75 | 14-FEB-22:10 | 10.60 | 3.54 |
March | 0.323423E+10 | 4707.55 | 08-MAR-13:30 | 21.40 | 9.29 | 0.687348E+09 | 470.79 | 13-MAR-21:10 | 11.88 | 3.50 |
April | 0.369858E+10 | 3893.31 | 13-APR-13:30 | 24.15 | 9.14 | 0.701308E+09 | 491.82 | 14-APR-21:19 | 18.53 | 9.74 |
May | 0.400149E+10 | 3216.35 | 13-MAY-13:10 | 28.40 | 11.85 | 0.741920E+09 | 491.86 | 17-MAY-21:40 | 19.63 | 9.46 |
June | 0.477382E+10 | 3860.39 | 29-JUN-14:30 | 37.25 | 15.80 | 0.755705E+09 | 491.86 | 23-JUN-21:10 | 37.25 | 15.80 |
July | 0.566369E+10 | 3980.32 | 22-JUL-13:40 | 37.23 | 17.83 | 0.804392E+09 | 491.86 | 21-JUL-21:10 | 37.23 | 17.83 |
August | 0.595441E+10 | 4683.45 | 22-AUG-13:30 | 31.40 | 16.68 | 0.805183E+09 | 491.85 | 21-AUG-00:10 | 31.40 | 16.68 |
September | 0.564710E+10 | 5402.47 | 28-SEP-13:30 | 29.45 | 15.27 | 0.755559E+09 | 491.87 | 22-SEP-21:00 | 29.45 | 15.27 |
October | 0.504335E+10 | 5415.76 | 05-OCT-13:10 | 25.78 | 13.28 | 0.737375E+09 | 491.84 | 04-OCT-22:10 | 25.78 | 13.28 |
November | 0.366931E+10 | 4972.96 | 20-NOV-13:30 | 13.85 | 4.44 | 0.664360E+09 | 474.32 | 02-NOV-21:10 | 13.85 | 4.44 |
December | 0.289958E+10 | 4838.02 | 31-DEC-13:00 | 8.30 | 1.00 | 0.663102E+09 | 412.77 | 29-DEC-22:10 | 8.30 | 1.00 |
Annual Sum or Average | 0.501547E+11 | 0.858488E+10 | ||||||||
Minimum of Months | 0.277979E+10 | 3216.35 | 8.30 | 1.00 | 0.607545E+09 | 412.77 | 6.60 | 0.62 | ||
Maximum of Months | 0.595441E+10 | 5415.76 | 37.25 | 17.83 | 0.805183E+09 | 491.87 | 37.25 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272927E+10 | 1515.49 | 03-JAN-21:10 | 3.25 | -0.5 | 0.854958E+09 | 569.52 | 05-JAN-22:30 | 3.35 | -1.3 |
February | 0.255213E+10 | 1808.44 | 14-FEB-20:20 | 10.73 | 3.32 | 0.784814E+09 | 569.52 | 13-FEB-22:19 | 10.73 | 3.32 |
March | 0.301790E+10 | 1943.26 | 15-MAR-19:10 | 13.22 | 5.85 | 0.900062E+09 | 569.54 | 30-MAR-21:10 | 10.40 | 4.53 |
April | 0.328110E+10 | 2367.37 | 13-APR-18:15 | 23.90 | 9.25 | 0.899417E+09 | 569.55 | 17-APR-22:10 | 13.62 | 3.75 |
May | 0.359114E+10 | 2537.95 | 19-MAY-18:30 | 28.30 | 10.89 | 0.943734E+09 | 569.58 | 17-MAY-21:00 | 28.30 | 10.89 |
June | 0.390608E+10 | 2836.94 | 23-JUN-19:10 | 31.13 | 13.20 | 0.931382E+09 | 569.62 | 01-JUN-01:10 | 31.13 | 13.20 |
July | 0.424401E+10 | 2974.40 | 21-JUL-19:10 | 33.77 | 14.01 | 0.967197E+09 | 569.59 | 01-JUL-00:49 | 33.77 | 14.01 |
August | 0.423559E+10 | 2825.06 | 15-AUG-18:30 | 30.00 | 14.03 | 0.970389E+09 | 569.56 | 04-AUG-21:10 | 30.00 | 14.03 |
September | 0.383815E+10 | 2529.62 | 20-SEP-18:15 | 26.67 | 11.96 | 0.929403E+09 | 569.59 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.352104E+10 | 2411.72 | 04-OCT-18:12 | 22.80 | 11.64 | 0.934082E+09 | 569.57 | 20-OCT-21:10 | 14.22 | 8.62 |
November | 0.293971E+10 | 1943.31 | 02-NOV-19:20 | 14.27 | 4.87 | 0.872905E+09 | 569.59 | 02-NOV-21:00 | 10.00 | 7.26 |
December | 0.274453E+10 | 1418.65 | 29-DEC-21:10 | 1.78 | -1.9 | 0.858659E+09 | 569.52 | 29-DEC-22:19 | 2.03 | -1.4 |
Annual Sum or Average | 0.406007E+11 | 0.108470E+11 | ||||||||
Minimum of Months | 0.255213E+10 | 1418.65 | 1.78 | -1.9 | 0.784814E+09 | 569.52 | 2.03 | -1.4 | ||
Maximum of Months | 0.424401E+10 | 2974.40 | 33.77 | 14.03 | 0.970389E+09 | 569.62 | 33.77 | 14.15 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226022E+10 | 1093.26 | 05-JAN-21:00 | 5.00 | -0.9 | 0.166556E+09 | 114.46 | 05-JAN-22:10 | 3.72 | -1.3 |
February | 0.212449E+10 | 1163.36 | 15-FEB-21:00 | 7.80 | 3.08 | 0.153019E+09 | 119.93 | 15-FEB-22:10 | 6.60 | 2.40 |
March | 0.259740E+10 | 1363.56 | 16-MAR-20:00 | 13.90 | 3.72 | 0.180970E+09 | 120.46 | 15-MAR-21:10 | 13.90 | 3.72 |
April | 0.293353E+10 | 2435.68 | 28-APR-20:00 | 22.20 | 8.52 | 0.186351E+09 | 120.46 | 18-APR-21:10 | 22.20 | 8.52 |
May | 0.347208E+10 | 2877.34 | 19-MAY-19:50 | 25.87 | 9.49 | 0.199059E+09 | 120.46 | 17-MAY-21:00 | 25.87 | 9.49 |
June | 0.414200E+10 | 3276.10 | 23-JUN-19:40 | 29.43 | 14.77 | 0.197201E+09 | 120.46 | 23-JUN-21:10 | 26.60 | 15.77 |
July | 0.460723E+10 | 3380.48 | 21-JUL-19:50 | 31.23 | 12.86 | 0.204445E+09 | 120.46 | 01-JUL-00:00 | 31.23 | 12.86 |
August | 0.440863E+10 | 3110.77 | 18-AUG-19:50 | 27.77 | 14.00 | 0.205013E+09 | 120.46 | 21-AUG-00:10 | 26.32 | 16.42 |
September | 0.371575E+10 | 2768.54 | 01-SEP-20:00 | 22.80 | 14.95 | 0.196090E+09 | 120.46 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.313501E+10 | 2513.52 | 02-OCT-20:00 | 18.90 | 14.94 | 0.193460E+09 | 120.46 | 20-OCT-21:10 | 14.22 | 8.62 |
November | 0.253778E+10 | 1559.23 | 02-NOV-20:00 | 12.80 | 4.41 | 0.174894E+09 | 120.46 | 02-NOV-22:10 | 10.00 | 7.26 |
December | 0.230831E+10 | 1118.77 | 01-DEC-22:00 | 9.40 | 2.31 | 0.166651E+09 | 116.73 | 01-DEC-22:10 | 8.95 | 2.17 |
Annual Sum or Average | 0.382424E+11 | 0.222371E+10 | ||||||||
Minimum of Months | 0.212449E+10 | 1093.26 | 5.00 | -0.9 | 0.153019E+09 | 114.46 | 3.72 | -1.3 | ||
Maximum of Months | 0.460723E+10 | 3380.48 | 31.23 | 14.95 | 0.205013E+09 | 120.46 | 31.23 | 16.42 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.582797E+09 | 549.46 | 03-JAN-21:00 | 3.90 | 0.12 | 0.117217E+09 | 72.58 | 05-JAN-22:10 | 3.72 | -1.3 |
February | 0.675510E+09 | 617.54 | 14-FEB-13:40 | 20.20 | 6.86 | 0.106876E+09 | 77.97 | 14-FEB-22:10 | 10.60 | 3.54 |
March | 0.124815E+10 | 635.86 | 08-MAR-21:00 | 13.90 | 5.15 | 0.122394E+09 | 80.54 | 16-MAR-21:10 | 14.17 | 4.07 |
April | 0.156639E+10 | 758.41 | 28-APR-19:50 | 22.48 | 8.72 | 0.129039E+09 | 90.94 | 28-APR-21:10 | 19.90 | 7.11 |
May | 0.182198E+10 | 1206.82 | 19-MAY-18:30 | 28.30 | 10.89 | 0.142785E+09 | 92.66 | 22-MAY-21:10 | 21.83 | 11.87 |
June | 0.222581E+10 | 1660.43 | 26-JUN-18:17 | 33.17 | 14.73 | 0.146852E+09 | 92.66 | 23-JUN-21:10 | 33.17 | 14.73 |
July | 0.247365E+10 | 1794.76 | 20-JUL-18:30 | 35.00 | 14.62 | 0.154631E+09 | 92.66 | 21-JUL-21:10 | 29.72 | 14.71 |
August | 0.230485E+10 | 1434.49 | 18-AUG-18:20 | 31.67 | 15.79 | 0.154122E+09 | 92.66 | 09-AUG-21:10 | 31.67 | 15.79 |
September | 0.188942E+10 | 1032.16 | 02-SEP-18:03 | 29.45 | 14.81 | 0.143857E+09 | 92.66 | 11-SEP-21:10 | 21.52 | 12.92 |
October | 0.161539E+10 | 794.71 | 01-OCT-13:30 | 27.75 | 13.90 | 0.134548E+09 | 92.23 | 02-OCT-21:10 | 18.30 | 14.29 |
November | 0.119081E+10 | 647.72 | 02-NOV-21:00 | 12.80 | 4.93 | 0.117205E+09 | 81.55 | 02-NOV-21:10 | 12.33 | 5.44 |
December | 0.556802E+09 | 571.69 | 01-DEC-22:00 | 9.40 | 2.31 | 0.117079E+09 | 74.98 | 01-DEC-22:10 | 8.95 | 2.17 |
Annual Sum or Average | 0.181516E+11 | 0.158660E+10 | ||||||||
Minimum of Months | 0.556802E+09 | 549.46 | 3.90 | 0.12 | 0.106876E+09 | 72.58 | 3.72 | -1.3 | ||
Maximum of Months | 0.247365E+10 | 1794.76 | 35.00 | 15.79 | 0.154631E+09 | 92.66 | 33.17 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478087E+11 | 37179.08 | 30-JAN-21:00 | 6.70 | 0.22 | 0.649330E+09 | 381.52 | 31-JAN-05:00 | -2.8 | -5.0 |
February | 0.436227E+11 | 37659.05 | 14-FEB-21:00 | 10.00 | 3.10 | 0.587068E+09 | 381.52 | 02-FEB-01:39 | 10.00 | 3.10 |
March | 0.495994E+11 | 37980.47 | 13-MAR-19:55 | 15.60 | 5.33 | 0.652382E+09 | 381.52 | 10-MAR-04:49 | 15.60 | 5.33 |
April | 0.493273E+11 | 38609.58 | 28-APR-20:00 | 22.20 | 8.52 | 0.629497E+09 | 381.55 | 14-APR-21:00 | 22.20 | 8.52 |
May | 0.518449E+11 | 38940.13 | 19-MAY-20:00 | 25.60 | 9.31 | 0.650721E+09 | 381.70 | 23-MAY-21:10 | 16.02 | 11.93 |
June | 0.514578E+11 | 39412.84 | 27-JUN-20:00 | 31.10 | 14.88 | 0.630898E+09 | 381.74 | 05-JUN-21:10 | 31.10 | 14.88 |
July | 0.534659E+11 | 39474.01 | 21-JUL-20:00 | 30.60 | 12.57 | 0.649429E+09 | 381.78 | 25-JUL-23:19 | 20.77 | 17.09 |
August | 0.534297E+11 | 39224.44 | 17-AUG-20:00 | 28.30 | 14.86 | 0.652166E+09 | 381.76 | 25-AUG-21:10 | 16.10 | 15.28 |
September | 0.506521E+11 | 38835.29 | 13-SEP-20:00 | 23.90 | 12.88 | 0.629241E+09 | 381.77 | 05-SEP-21:10 | 23.90 | 12.88 |
October | 0.507789E+11 | 38468.94 | 04-OCT-20:00 | 20.00 | 11.76 | 0.649649E+09 | 381.74 | 02-OCT-21:40 | 20.00 | 11.76 |
November | 0.476385E+11 | 37779.24 | 02-NOV-20:00 | 12.80 | 4.41 | 0.628117E+09 | 381.52 | 10-NOV-01:10 | 5.82 | 2.79 |
December | 0.477021E+11 | 37333.42 | 01-DEC-21:00 | 9.40 | 2.54 | 0.649331E+09 | 381.52 | 14-DEC-05:19 | -3.0 | -7.3 |
Annual Sum or Average | 0.597328E+12 | 0.765783E+10 | ||||||||
Minimum of Months | 0.436227E+11 | 37179.08 | 6.70 | 0.22 | 0.587068E+09 | 381.52 | -3.0 | -7.3 | ||
Maximum of Months | 0.534659E+11 | 39474.01 | 31.10 | 14.88 | 0.652382E+09 | 381.78 | 31.10 | 17.09 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204711E+11 | 16908.99 | 01-JAN-13:00 | 13.30 | 4.92 | 0.866200E+10 | 6215.51 | 09-JAN-22:30 | 6.40 | 0.54 |
February | 0.189523E+11 | 17544.13 | 14-FEB-13:20 | 19.80 | 6.75 | 0.809932E+10 | 6461.08 | 15-FEB-02:30 | 8.85 | 3.11 |
March | 0.200559E+11 | 16019.36 | 08-MAR-13:30 | 21.40 | 9.29 | 0.974583E+10 | 6462.34 | 16-MAR-23:00 | 8.90 | 2.05 |
April | 0.198368E+11 | 14201.67 | 01-APR-13:30 | 21.65 | 7.61 | 0.101849E+11 | 6463.19 | 14-APR-21:19 | 18.53 | 9.74 |
May | 0.201187E+11 | 12349.27 | 13-MAY-13:00 | 28.30 | 11.84 | 0.109073E+11 | 6464.01 | 21-MAY-23:19 | 21.87 | 14.15 |
June | 0.222790E+11 | 13656.74 | 29-JUN-15:10 | 37.43 | 15.90 | 0.106792E+11 | 6464.29 | 24-JUN-03:39 | 37.43 | 15.90 |
July | 0.255263E+11 | 13557.33 | 22-JUL-13:30 | 36.95 | 17.78 | 0.110006E+11 | 6464.64 | 25-JUL-22:49 | 21.05 | 17.14 |
August | 0.264151E+11 | 15678.82 | 20-AUG-12:00 | 32.80 | 17.08 | 0.110468E+11 | 6464.66 | 14-AUG-23:49 | 32.80 | 17.08 |
September | 0.250471E+11 | 17450.49 | 28-SEP-13:10 | 29.08 | 15.59 | 0.106568E+11 | 6464.39 | 01-SEP-01:19 | 29.08 | 15.59 |
October | 0.243428E+11 | 18298.18 | 01-OCT-12:00 | 25.60 | 14.51 | 0.104888E+11 | 6464.24 | 10-OCT-21:19 | 20.00 | 14.26 |
November | 0.214713E+11 | 16756.52 | 20-NOV-13:10 | 13.48 | 4.25 | 0.929205E+10 | 6461.16 | 08-NOV-02:49 | 13.48 | 4.25 |
December | 0.210327E+11 | 17017.76 | 31-DEC-13:00 | 8.30 | 1.00 | 0.867683E+10 | 6461.22 | 01-DEC-22:10 | 8.30 | 1.00 |
Annual Sum or Average | 0.265549E+12 | 0.119440E+12 | ||||||||
Minimum of Months | 0.189523E+11 | 12349.27 | 8.30 | 1.00 | 0.809932E+10 | 6215.51 | 6.40 | 0.54 | ||
Maximum of Months | 0.264151E+11 | 18298.18 | 37.43 | 17.78 | 0.110468E+11 | 6464.66 | 37.43 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.612227E+11 | 33825.45 | 03-JAN-19:05 | 5.92 | 1.15 | 0.302452E+11 | 19183.32 | 30-JAN-23:19 | 3.87 | -0.5 |
February | 0.567456E+11 | 37000.93 | 14-FEB-21:10 | 10.10 | 3.17 | 0.276589E+11 | 19183.62 | 13-FEB-22:10 | 10.10 | 3.17 |
March | 0.658717E+11 | 38020.95 | 08-MAR-21:02 | 13.62 | 5.13 | 0.314689E+11 | 19184.79 | 13-MAR-21:10 | 11.88 | 3.50 |
April | 0.693776E+11 | 42688.87 | 13-APR-20:10 | 19.68 | 7.16 | 0.310404E+11 | 19186.21 | 17-APR-22:10 | 13.62 | 3.75 |
May | 0.751057E+11 | 45228.80 | 19-MAY-20:10 | 25.22 | 9.14 | 0.323542E+11 | 19188.44 | 01-MAY-01:10 | 25.22 | 9.14 |
June | 0.801009E+11 | 48965.62 | 27-JUN-20:10 | 30.82 | 14.79 | 0.316135E+11 | 19187.90 | 01-JUN-00:00 | 30.82 | 14.79 |
July | 0.873531E+11 | 49605.91 | 21-JUL-20:10 | 30.50 | 12.95 | 0.326336E+11 | 19186.67 | 01-JUL-00:40 | 30.50 | 12.95 |
August | 0.880273E+11 | 48087.28 | 17-AUG-20:10 | 28.03 | 14.80 | 0.327587E+11 | 19186.23 | 31-AUG-22:10 | 23.18 | 14.15 |
September | 0.819112E+11 | 45884.91 | 13-SEP-20:04 | 23.53 | 12.84 | 0.315632E+11 | 19186.42 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.768972E+11 | 44056.76 | 04-OCT-20:10 | 20.18 | 11.71 | 0.321792E+11 | 19186.20 | 04-OCT-22:10 | 17.70 | 10.79 |
November | 0.655870E+11 | 38496.08 | 02-NOV-20:10 | 12.80 | 4.49 | 0.305515E+11 | 19186.49 | 01-NOV-01:10 | 12.80 | 4.49 |
December | 0.616283E+11 | 32292.87 | 29-DEC-19:07 | 6.78 | 1.58 | 0.304178E+11 | 19183.33 | 29-DEC-22:10 | 2.12 | -1.4 |
Annual Sum or Average | 0.869828E+12 | 0.374485E+12 | ||||||||
Minimum of Months | 0.567456E+11 | 32292.87 | 5.92 | 1.15 | 0.276589E+11 | 19183.32 | 2.12 | -1.4 | ||
Maximum of Months | 0.880273E+11 | 49605.91 | 30.82 | 14.80 | 0.327587E+11 | 19188.44 | 30.82 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.680192E+09 | 5113.08 | 26-JAN-16:12 | 10.40 | 1.47 | 97639787.26 | 56.70 | 18-JAN-23:49 | 10.40 | 1.47 |
February | 0.851655E+09 | 5148.70 | 04-FEB-16:12 | 6.50 | -0.6 | 88699516.67 | 56.70 | 06-FEB-02:49 | -5.0 | -7.3 |
March | 0.120864E+10 | 5116.00 | 04-MAR-16:12 | 12.20 | 2.54 | 98772607.11 | 57.00 | 20-MAR-04:30 | 8.85 | 4.64 |
April | 0.184954E+10 | 5082.68 | 08-APR-15:12 | 14.07 | 4.79 | 95954978.41 | 56.69 | 24-APR-03:00 | 6.10 | 2.66 |
May | 0.215007E+10 | 5124.72 | 26-MAY-18:01 | 22.43 | 11.72 | 99377739.38 | 56.69 | 05-MAY-04:00 | 22.43 | 11.72 |
June | 0.277453E+10 | 5081.71 | 10-JUN-18:01 | 23.53 | 11.40 | 96358571.96 | 56.69 | 01-JUN-01:30 | 23.53 | 11.40 |
July | 0.313258E+10 | 4547.46 | 29-JUL-18:02 | 28.95 | 16.22 | 99568465.28 | 56.69 | 01-JUL-01:10 | 28.95 | 16.22 |
August | 0.312012E+10 | 4752.26 | 23-AUG-18:01 | 23.62 | 15.24 | 99638701.21 | 56.69 | 22-AUG-03:09 | 23.62 | 15.24 |
September | 0.264050E+10 | 4881.09 | 18-SEP-15:12 | 25.20 | 14.17 | 96239359.91 | 56.69 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.199274E+10 | 5096.12 | 27-OCT-15:12 | 13.70 | 4.43 | 99006873.51 | 56.69 | 26-OCT-04:10 | 13.70 | 4.43 |
November | 0.102509E+10 | 5085.78 | 03-NOV-15:12 | 12.60 | 2.67 | 95459953.22 | 56.69 | 27-NOV-05:00 | -4.4 | -6.9 |
December | 0.646074E+09 | 5101.06 | 20-DEC-16:12 | 5.30 | -1.2 | 97506810.82 | 56.70 | 23-DEC-05:30 | -5.3 | -7.8 |
Annual Sum or Average | 0.220717E+11 | 0.116422E+10 | ||||||||
Minimum of Months | 0.646074E+09 | 4547.46 | 5.30 | -1.2 | 88699516.67 | 56.69 | -5.3 | -7.8 | ||
Maximum of Months | 0.313258E+10 | 5148.70 | 28.95 | 16.22 | 99638701.21 | 57.00 | 28.95 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208098E+09 | 5017.04 | 05-JAN-17:01 | 12.85 | 5.27 | 96109010.22 | 56.70 | 18-JAN-00:49 | -2.0 | -3.6 |
February | 0.356340E+09 | 4988.88 | 15-FEB-18:01 | 12.23 | 3.61 | 88227966.87 | 64.30 | 14-FEB-19:10 | 12.23 | 3.61 |
March | 0.613295E+09 | 5217.51 | 30-MAR-18:11 | 13.50 | 4.61 | 0.102668E+09 | 88.80 | 24-MAR-18:10 | 13.50 | 4.61 |
April | 0.123373E+10 | 5200.25 | 14-APR-21:51 | 17.80 | 9.61 | 0.107938E+09 | 100.85 | 25-APR-21:10 | 18.72 | 6.67 |
May | 0.179047E+10 | 5310.43 | 26-MAY-18:01 | 22.43 | 11.72 | 0.109724E+09 | 103.51 | 02-MAY-21:10 | 22.43 | 11.72 |
June | 0.259462E+10 | 5339.56 | 09-JUN-18:51 | 20.60 | 9.85 | 0.102796E+09 | 107.48 | 09-JUN-18:19 | 20.60 | 9.85 |
July | 0.287454E+10 | 4930.82 | 29-JUL-21:51 | 23.30 | 14.84 | 0.105978E+09 | 94.87 | 31-JUL-21:30 | 21.60 | 17.59 |
August | 0.266909E+10 | 5082.15 | 30-AUG-21:51 | 22.80 | 13.38 | 0.107558E+09 | 98.05 | 28-AUG-21:10 | 22.80 | 13.38 |
September | 0.190574E+10 | 5199.38 | 30-SEP-21:51 | 18.00 | 8.68 | 0.108120E+09 | 96.98 | 12-SEP-21:10 | 18.00 | 8.68 |
October | 0.104643E+10 | 5235.78 | 19-OCT-21:41 | 15.60 | 9.18 | 0.109186E+09 | 96.49 | 04-OCT-21:10 | 15.60 | 9.18 |
November | 0.419600E+09 | 5053.85 | 02-NOV-18:11 | 15.00 | 7.63 | 94629151.40 | 68.87 | 02-NOV-18:19 | 15.00 | 7.63 |
December | 0.154682E+09 | 4946.44 | 20-DEC-16:12 | 5.30 | -1.2 | 95677157.38 | 56.70 | 22-DEC-00:00 | -2.8 | -5.1 |
Annual Sum or Average | 0.158666E+11 | 0.122861E+10 | ||||||||
Minimum of Months | 0.154682E+09 | 4930.82 | 5.30 | -1.2 | 88227966.87 | 56.70 | -2.8 | -5.1 | ||
Maximum of Months | 0.287454E+10 | 5339.56 | 23.30 | 14.84 | 0.109724E+09 | 107.48 | 22.80 | 17.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.537371E+09 | 999.52 | 01-JAN-13:40 | 14.83 | 5.43 | 0.00 | 0.00 | 01-JAN-00:10 | 14.83 | 5.43 |
February | 0.519828E+09 | 1012.58 | 14-FEB-13:00 | 19.40 | 6.65 | 0.00 | 0.00 | 01-FEB-00:10 | 19.40 | 6.65 |
March | 0.519765E+09 | 870.39 | 08-MAR-13:30 | 21.40 | 9.29 | 0.00 | 0.00 | 01-MAR-00:10 | 21.40 | 9.29 |
April | 0.548454E+09 | 680.72 | 01-APR-13:30 | 21.65 | 7.61 | 0.00 | 0.00 | 01-APR-00:10 | 21.65 | 7.61 |
May | 0.537007E+09 | 496.28 | 13-MAY-13:10 | 28.40 | 11.85 | 0.00 | 0.00 | 01-MAY-00:10 | 28.40 | 11.85 |
June | 0.654004E+09 | 511.84 | 29-JUN-14:30 | 37.25 | 15.80 | 0.00 | 0.00 | 01-JUN-00:10 | 37.25 | 15.80 |
July | 0.826471E+09 | 569.16 | 23-JUL-13:30 | 36.15 | 17.47 | 0.00 | 0.00 | 01-JUL-00:10 | 36.15 | 17.47 |
August | 0.901089E+09 | 714.18 | 20-AUG-12:50 | 32.80 | 17.07 | 0.00 | 0.00 | 01-AUG-00:10 | 32.80 | 17.07 |
September | 0.918176E+09 | 907.45 | 28-SEP-13:20 | 29.27 | 15.43 | 0.00 | 0.00 | 01-SEP-00:10 | 29.27 | 15.43 |
October | 0.885328E+09 | 1000.59 | 31-OCT-13:00 | 20.00 | 8.32 | 0.00 | 0.00 | 01-OCT-00:10 | 20.00 | 8.32 |
November | 0.694151E+09 | 1000.69 | 20-NOV-12:20 | 12.97 | 3.92 | 0.00 | 0.00 | 01-NOV-00:10 | 12.97 | 3.92 |
December | 0.587676E+09 | 1010.07 | 31-DEC-13:40 | 9.43 | 1.41 | 0.00 | 0.00 | 01-DEC-00:10 | 9.43 | 1.41 |
Annual Sum or Average | 0.812932E+10 | 0.00 | ||||||||
Minimum of Months | 0.519765E+09 | 496.28 | 9.43 | 1.41 | 0.00 | 0.00 | 9.43 | 1.41 | ||
Maximum of Months | 0.918176E+09 | 1012.58 | 37.25 | 17.47 | 0.00 | 0.00 | 37.25 | 17.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143547E+09 | 1613.69 | 01-JAN-09:02 | 2.67 | -1.3 | 96448232.82 | 56.69 | 20-JAN-02:20 | -7.9 | -7.9 |
February | 0.191830E+09 | 1619.17 | 18-FEB-09:02 | 2.15 | -1.0 | 87836915.79 | 56.82 | 14-FEB-19:10 | 2.15 | -1.0 |
March | 0.371902E+09 | 1619.49 | 04-MAR-09:02 | 2.15 | -2.2 | 99865995.32 | 71.33 | 13-MAR-20:40 | 13.00 | 4.07 |
April | 0.551652E+09 | 1600.32 | 08-APR-08:62 | 4.60 | 0.65 | 0.101944E+09 | 87.54 | 25-APR-21:40 | 18.17 | 6.50 |
May | 0.763970E+09 | 1578.77 | 26-MAY-19:31 | 19.47 | 11.36 | 0.106095E+09 | 88.86 | 22-MAY-21:00 | 19.47 | 11.36 |
June | 0.100600E+10 | 1598.84 | 09-JUN-21:51 | 13.90 | 9.18 | 0.101156E+09 | 88.62 | 02-JUN-21:00 | 13.90 | 9.18 |
July | 0.111321E+10 | 1420.33 | 22-JUL-07:31 | 26.27 | 14.64 | 0.104926E+09 | 91.44 | 31-JUL-21:10 | 21.67 | 17.79 |
August | 0.101859E+10 | 1458.81 | 30-AUG-21:51 | 22.80 | 13.38 | 0.105795E+09 | 90.43 | 03-AUG-21:10 | 22.80 | 13.38 |
September | 0.759870E+09 | 1553.37 | 30-SEP-21:51 | 18.00 | 8.68 | 0.104890E+09 | 89.05 | 12-SEP-21:10 | 18.00 | 8.68 |
October | 0.503272E+09 | 1585.42 | 29-OCT-08:62 | 5.87 | 1.27 | 0.104175E+09 | 88.36 | 02-OCT-21:00 | 5.87 | 1.27 |
November | 0.280554E+09 | 1617.14 | 25-NOV-09:02 | 2.48 | -0.9 | 94353641.21 | 56.72 | 02-NOV-18:19 | 2.48 | -0.9 |
December | 0.122372E+09 | 1582.14 | 31-DEC-19:02 | 5.92 | -1.0 | 95897591.15 | 56.69 | 15-DEC-04:40 | 5.92 | -1.0 |
Annual Sum or Average | 0.682677E+10 | 0.120338E+10 | ||||||||
Minimum of Months | 0.122372E+09 | 1420.33 | 2.15 | -2.2 | 87836915.79 | 56.69 | -7.9 | -7.9 | ||
Maximum of Months | 0.111321E+10 | 1619.49 | 26.27 | 14.64 | 0.106095E+09 | 91.44 | 22.80 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.665143E+09 | 4592.76 | 26-JAN-09:02 | -0.6 | -5.0 | 97961122.34 | 56.70 | 17-JAN-00:49 | -0.6 | -5.0 |
February | 0.792589E+09 | 4615.87 | 04-FEB-09:02 | -3.5 | -6.1 | 88967492.09 | 56.70 | 04-FEB-02:49 | -3.5 | -6.1 |
March | 0.127768E+10 | 4606.26 | 04-MAR-09:02 | 2.15 | -2.2 | 99237222.98 | 56.70 | 04-MAR-05:30 | 2.15 | -2.2 |
April | 0.203328E+10 | 4570.50 | 06-APR-08:62 | 4.08 | -1.7 | 96356086.85 | 56.69 | 24-APR-04:00 | 6.10 | 2.66 |
May | 0.234992E+10 | 4532.27 | 06-MAY-08:62 | 8.48 | 1.34 | 99612865.40 | 56.69 | 06-MAY-04:10 | 8.48 | 1.34 |
June | 0.300455E+10 | 4467.23 | 19-JUN-08:62 | 18.07 | 7.29 | 96444609.44 | 56.69 | 01-JUN-01:30 | 18.07 | 7.29 |
July | 0.341414E+10 | 4190.94 | 06-JUL-08:61 | 25.87 | 16.03 | 99586013.97 | 56.69 | 01-JUL-01:10 | 25.87 | 16.03 |
August | 0.333098E+10 | 4209.91 | 20-AUG-08:62 | 24.68 | 14.76 | 99693241.99 | 56.69 | 22-AUG-03:09 | 21.20 | 15.85 |
September | 0.270793E+10 | 4421.13 | 21-SEP-08:62 | 18.77 | 10.46 | 96374804.74 | 56.69 | 22-SEP-21:00 | 19.40 | 14.15 |
October | 0.199021E+10 | 4541.11 | 27-OCT-08:62 | 2.98 | -0.4 | 99314567.98 | 56.69 | 26-OCT-03:30 | 2.98 | -0.4 |
November | 0.103408E+10 | 4624.26 | 28-NOV-09:02 | -0.1 | -3.2 | 95685669.83 | 56.70 | 27-NOV-04:30 | -0.1 | -3.2 |
December | 0.621686E+09 | 4612.97 | 31-DEC-09:02 | -0.3 | -4.0 | 97950515.49 | 56.70 | 04-DEC-04:19 | -0.3 | -4.0 |
Annual Sum or Average | 0.232222E+11 | 0.116718E+10 | ||||||||
Minimum of Months | 0.621686E+09 | 4190.94 | -3.5 | -6.1 | 88967492.09 | 56.69 | -3.5 | -6.1 | ||
Maximum of Months | 0.341414E+10 | 4624.26 | 25.87 | 16.03 | 99693241.99 | 56.70 | 25.87 | 16.03 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162273E+09 | 4468.35 | 26-JAN-09:02 | -0.6 | -5.0 | 96446345.55 | 56.70 | 20-JAN-02:09 | -0.6 | -5.0 |
February | 0.280501E+09 | 4506.18 | 04-FEB-09:02 | -3.5 | -6.1 | 88263037.09 | 56.80 | 14-FEB-19:10 | 12.93 | 4.07 |
March | 0.728089E+09 | 4518.59 | 04-MAR-09:02 | 2.15 | -2.2 | 0.101202E+09 | 72.81 | 13-MAR-20:30 | 13.65 | 4.40 |
April | 0.151487E+10 | 4605.36 | 27-APR-08:51 | 17.20 | 8.10 | 0.104575E+09 | 93.92 | 27-APR-21:10 | 17.80 | 7.33 |
May | 0.199589E+10 | 4638.19 | 19-MAY-08:32 | 21.67 | 11.47 | 0.108543E+09 | 94.26 | 16-MAY-21:10 | 21.67 | 11.47 |
June | 0.272336E+10 | 4729.20 | 10-JUN-08:51 | 18.90 | 10.49 | 0.104285E+09 | 90.49 | 19-JUN-21:19 | 21.87 | 9.02 |
July | 0.303304E+10 | 4563.51 | 22-JUL-07:12 | 25.33 | 14.24 | 0.108106E+09 | 94.11 | 26-JUL-21:19 | 22.93 | 16.67 |
August | 0.276300E+10 | 4495.54 | 02-AUG-08:62 | 24.78 | 14.77 | 0.109195E+09 | 95.20 | 24-AUG-21:10 | 18.90 | 15.21 |
September | 0.191649E+10 | 4696.38 | 20-SEP-08:51 | 20.00 | 11.61 | 0.107702E+09 | 94.34 | 01-SEP-21:10 | 20.00 | 11.61 |
October | 0.111856E+10 | 4514.36 | 06-OCT-21:51 | 19.40 | 11.12 | 0.105976E+09 | 93.35 | 02-OCT-21:10 | 19.40 | 11.12 |
November | 0.397289E+09 | 4494.34 | 28-NOV-09:02 | -0.1 | -3.2 | 94962002.23 | 56.78 | 02-NOV-18:19 | -0.1 | -3.2 |
December | 0.130051E+09 | 4485.25 | 31-DEC-09:02 | -0.3 | -4.0 | 95697717.82 | 56.70 | 04-DEC-02:09 | -0.3 | -4.0 |
Annual Sum or Average | 0.167634E+11 | 0.122495E+10 | ||||||||
Minimum of Months | 0.130051E+09 | 4468.35 | -3.5 | -6.1 | 88263037.09 | 56.70 | -0.6 | -5.0 | ||
Maximum of Months | 0.303304E+10 | 4729.20 | 25.33 | 14.77 | 0.109195E+09 | 95.20 | 22.93 | 16.67 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106004E+10 | 2137.58 | 03-JAN-16:10 | 14.53 | 5.76 | 0.159061E+10 | 951.85 | 03-JAN-04:19 | 14.53 | 5.76 |
February | 0.133081E+10 | 2717.54 | 14-FEB-16:10 | 22.02 | 7.76 | 0.145236E+10 | 951.85 | 28-FEB-02:20 | -0.8 | -2.0 |
March | 0.224219E+10 | 2426.24 | 08-MAR-14:10 | 22.70 | 9.58 | 0.162583E+10 | 951.85 | 10-MAR-05:49 | -1.1 | -4.2 |
April | 0.333736E+10 | 2783.72 | 11-APR-18:15 | 23.33 | 8.78 | 0.157040E+10 | 951.85 | 08-APR-04:00 | 23.33 | 8.78 |
May | 0.392579E+10 | 3156.71 | 19-MAY-18:15 | 28.67 | 11.04 | 0.162336E+10 | 951.84 | 17-MAY-22:10 | 28.67 | 11.04 |
June | 0.495528E+10 | 3616.05 | 16-JUN-18:30 | 29.70 | 12.88 | 0.157387E+10 | 951.85 | 23-JUN-21:10 | 26.60 | 15.77 |
July | 0.567707E+10 | 3776.14 | 20-JUL-18:30 | 35.00 | 14.62 | 0.161993E+10 | 951.84 | 27-JUL-22:10 | 22.02 | 15.26 |
August | 0.567897E+10 | 3484.90 | 18-AUG-18:15 | 31.67 | 15.79 | 0.162678E+10 | 951.84 | 31-AUG-22:10 | 23.18 | 14.15 |
September | 0.493243E+10 | 3242.74 | 13-SEP-15:10 | 28.30 | 14.80 | 0.156967E+10 | 951.84 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.378650E+10 | 3197.63 | 05-OCT-15:10 | 26.70 | 12.29 | 0.161917E+10 | 951.85 | 25-OCT-01:39 | -0.9 | -2.0 |
November | 0.207128E+10 | 2447.75 | 02-NOV-15:10 | 17.12 | 9.39 | 0.156453E+10 | 951.85 | 27-NOV-01:19 | -2.1 | -5.2 |
December | 0.970313E+09 | 2049.16 | 30-DEC-14:10 | 10.68 | 2.42 | 0.159700E+10 | 951.85 | 19-DEC-04:10 | 10.68 | 2.42 |
Annual Sum or Average | 0.399680E+11 | 0.190335E+11 | ||||||||
Minimum of Months | 0.970313E+09 | 2049.16 | 10.68 | 2.42 | 0.145236E+10 | 951.84 | -2.1 | -5.2 | ||
Maximum of Months | 0.567897E+10 | 3776.14 | 35.00 | 15.79 | 0.162678E+10 | 951.85 | 28.67 | 15.77 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493138E+09 | 5554.28 | 26-JAN-16:12 | 10.40 | 1.47 | 96511788.46 | 56.70 | 19-JAN-02:09 | 10.40 | 1.47 |
February | 0.677372E+09 | 5585.07 | 04-FEB-16:12 | 6.50 | -0.6 | 87934210.34 | 56.70 | 23-FEB-02:49 | -0.9 | -2.3 |
March | 0.101156E+10 | 5560.33 | 04-MAR-16:12 | 12.20 | 2.54 | 98152426.01 | 56.70 | 10-MAR-05:40 | -1.1 | -4.2 |
April | 0.173654E+10 | 5552.81 | 08-APR-15:12 | 14.07 | 4.79 | 95649692.35 | 57.30 | 03-APR-00:30 | 14.07 | 4.79 |
May | 0.211563E+10 | 5628.64 | 26-MAY-18:01 | 22.43 | 11.72 | 99154131.30 | 57.47 | 24-MAY-02:00 | 22.43 | 11.72 |
June | 0.294502E+10 | 5579.20 | 10-JUN-18:01 | 23.53 | 11.40 | 96279784.46 | 56.69 | 09-JUN-02:00 | 23.53 | 11.40 |
July | 0.340919E+10 | 5006.69 | 29-JUL-18:02 | 28.95 | 16.22 | 99544456.17 | 56.69 | 01-JUL-01:10 | 28.95 | 16.22 |
August | 0.334745E+10 | 5203.41 | 23-AUG-18:01 | 23.62 | 15.24 | 99579855.59 | 56.69 | 30-AUG-01:10 | 16.52 | 16.19 |
September | 0.265132E+10 | 5378.54 | 18-SEP-15:12 | 25.20 | 14.17 | 96079928.61 | 57.44 | 24-SEP-03:30 | 12.50 | 11.66 |
October | 0.183424E+10 | 5588.80 | 18-OCT-15:11 | 22.97 | 9.55 | 98556372.78 | 57.23 | 20-OCT-04:49 | 10.10 | 7.05 |
November | 0.757996E+09 | 5532.40 | 06-NOV-16:12 | 14.40 | 4.29 | 94648244.12 | 56.70 | 26-NOV-05:19 | 0.93 | -2.6 |
December | 0.426162E+09 | 5540.51 | 31-DEC-16:12 | 9.63 | 1.35 | 96336254.36 | 56.70 | 09-DEC-05:10 | 9.63 | 1.35 |
Annual Sum or Average | 0.214056E+11 | 0.115843E+10 | ||||||||
Minimum of Months | 0.426162E+09 | 5006.69 | 6.50 | -0.6 | 87934210.34 | 56.69 | -1.1 | -4.2 | ||
Maximum of Months | 0.340919E+10 | 5628.64 | 28.95 | 16.22 | 99579855.59 | 57.47 | 28.95 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128294E+09 | 5451.84 | 05-JAN-17:01 | 12.85 | 5.27 | 94767683.62 | 56.70 | 20-JAN-02:20 | -7.9 | -7.9 |
February | 0.247189E+09 | 5445.70 | 15-FEB-18:01 | 12.23 | 3.61 | 87264497.68 | 64.72 | 14-FEB-19:10 | 12.23 | 3.61 |
March | 0.449193E+09 | 5719.51 | 30-MAR-18:11 | 13.50 | 4.61 | 0.102099E+09 | 94.08 | 24-MAR-18:10 | 13.50 | 4.61 |
April | 0.114134E+10 | 5665.93 | 20-APR-20:41 | 14.18 | 5.76 | 0.108484E+09 | 106.69 | 24-APR-18:19 | 20.20 | 7.95 |
May | 0.180170E+10 | 5858.49 | 26-MAY-18:01 | 22.43 | 11.72 | 0.109876E+09 | 109.15 | 02-MAY-18:19 | 22.43 | 11.72 |
June | 0.280952E+10 | 5874.73 | 09-JUN-18:51 | 20.60 | 9.85 | 0.102673E+09 | 111.25 | 09-JUN-18:19 | 20.60 | 9.85 |
July | 0.320021E+10 | 5395.73 | 29-JUL-21:51 | 23.30 | 14.84 | 0.105673E+09 | 96.74 | 31-JUL-21:30 | 21.60 | 17.59 |
August | 0.294476E+10 | 5712.72 | 23-AUG-16:51 | 24.40 | 17.29 | 0.107399E+09 | 100.68 | 28-AUG-21:10 | 18.22 | 14.01 |
September | 0.196554E+10 | 5680.57 | 19-SEP-21:51 | 18.90 | 10.44 | 0.107985E+09 | 97.81 | 01-SEP-21:10 | 18.90 | 10.44 |
October | 0.918772E+09 | 5711.89 | 19-OCT-21:41 | 15.60 | 9.18 | 0.109196E+09 | 97.14 | 03-OCT-21:10 | 15.60 | 9.18 |
November | 0.242763E+09 | 5538.86 | 02-NOV-18:11 | 15.00 | 7.63 | 93502680.81 | 69.63 | 02-NOV-18:19 | 15.00 | 7.63 |
December | 75928185.75 | 5237.38 | 31-DEC-16:12 | 9.63 | 1.35 | 94238092.79 | 56.70 | 15-DEC-05:10 | 9.63 | 1.35 |
Annual Sum or Average | 0.159252E+11 | 0.122316E+10 | ||||||||
Minimum of Months | 75928185.75 | 5237.38 | 9.63 | 1.35 | 87264497.68 | 56.70 | -7.9 | -7.9 | ||
Maximum of Months | 0.320021E+10 | 5874.73 | 24.40 | 17.29 | 0.109876E+09 | 111.25 | 22.43 | 17.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.881052E+09 | 2735.80 | 21-JAN-16:12 | 9.03 | 1.68 | 98204077.06 | 56.70 | 19-JAN-02:09 | 9.03 | 1.68 |
February | 0.872983E+09 | 2756.90 | 04-FEB-16:12 | 6.50 | -0.6 | 88964896.55 | 56.70 | 04-FEB-05:00 | 6.50 | -0.6 |
March | 0.876077E+09 | 2685.96 | 04-MAR-09:02 | 2.15 | -2.2 | 98786331.08 | 56.69 | 22-MAR-02:49 | 2.30 | -0.4 |
April | 0.100947E+10 | 2659.26 | 08-APR-15:12 | 14.07 | 4.79 | 95848813.72 | 56.69 | 08-APR-04:00 | 14.07 | 4.79 |
May | 0.107353E+10 | 2611.00 | 01-MAY-15:12 | 13.50 | 5.23 | 99203691.70 | 56.69 | 06-MAY-04:00 | 6.10 | -0.8 |
June | 0.141151E+10 | 2564.83 | 10-JUN-18:01 | 23.53 | 11.40 | 96282861.17 | 56.69 | 01-JUN-01:10 | 23.53 | 11.40 |
July | 0.179084E+10 | 2304.06 | 27-JUL-15:12 | 29.47 | 16.04 | 99548207.81 | 56.69 | 01-JUL-01:10 | 29.47 | 16.04 |
August | 0.188216E+10 | 2410.15 | 28-AUG-15:12 | 24.47 | 14.97 | 99583102.28 | 56.69 | 30-AUG-01:10 | 16.52 | 16.19 |
September | 0.175800E+10 | 2540.80 | 26-SEP-18:02 | 23.25 | 10.40 | 96171934.96 | 56.69 | 22-SEP-21:00 | 23.25 | 10.40 |
October | 0.155241E+10 | 2742.17 | 15-OCT-15:21 | 20.85 | 7.97 | 99069397.81 | 56.69 | 26-OCT-04:10 | -2.8 | -4.1 |
November | 0.110466E+10 | 2756.58 | 28-NOV-09:02 | -0.1 | -3.2 | 95774089.29 | 56.69 | 05-NOV-03:20 | -0.1 | -3.2 |
December | 0.953832E+09 | 2755.15 | 14-DEC-16:12 | 1.67 | -5.1 | 98073600.15 | 56.70 | 09-DEC-05:10 | 1.67 | -5.1 |
Annual Sum or Average | 0.151665E+11 | 0.116551E+10 | ||||||||
Minimum of Months | 0.872983E+09 | 2304.06 | -0.1 | -5.1 | 88964896.55 | 56.69 | -2.8 | -5.1 | ||
Maximum of Months | 0.188216E+10 | 2756.90 | 29.47 | 16.04 | 99583102.28 | 56.70 | 29.47 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316763E+11 | 16314.62 | 05-JAN-22:10 | 3.72 | -1.3 | 0.177485E+11 | 11344.12 | 05-JAN-22:19 | 3.53 | -1.3 |
February | 0.298582E+11 | 18569.74 | 14-FEB-22:10 | 10.60 | 3.54 | 0.163520E+11 | 11344.82 | 13-FEB-22:10 | 10.60 | 3.54 |
March | 0.360149E+11 | 19473.81 | 16-MAR-21:10 | 14.17 | 4.07 | 0.188165E+11 | 11346.81 | 13-MAR-21:10 | 14.17 | 4.07 |
April | 0.387198E+11 | 22050.70 | 28-APR-21:10 | 19.90 | 7.11 | 0.185214E+11 | 11349.05 | 11-APR-22:10 | 19.90 | 7.11 |
May | 0.429179E+11 | 23048.17 | 19-MAY-21:02 | 23.12 | 8.19 | 0.192680E+11 | 11349.17 | 17-MAY-22:10 | 23.12 | 8.19 |
June | 0.457336E+11 | 24882.10 | 27-JUN-21:10 | 28.85 | 14.13 | 0.187435E+11 | 11349.06 | 07-JUN-22:10 | 28.85 | 14.13 |
July | 0.488183E+11 | 25007.89 | 21-JUL-21:10 | 29.72 | 14.71 | 0.193094E+11 | 11349.08 | 13-JUL-22:10 | 29.72 | 14.71 |
August | 0.477159E+11 | 24049.20 | 17-AUG-21:10 | 26.78 | 14.47 | 0.193852E+11 | 11349.12 | 29-AUG-21:10 | 19.90 | 15.15 |
September | 0.425794E+11 | 22632.72 | 13-SEP-21:10 | 21.60 | 12.51 | 0.186687E+11 | 11349.17 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.387875E+11 | 21836.61 | 02-OCT-21:10 | 18.30 | 14.29 | 0.189748E+11 | 11349.06 | 04-OCT-22:10 | 17.70 | 10.79 |
November | 0.331911E+11 | 19133.92 | 02-NOV-21:10 | 12.33 | 5.44 | 0.178163E+11 | 11346.97 | 02-NOV-21:40 | 10.93 | 6.67 |
December | 0.312249E+11 | 17356.50 | 01-DEC-22:10 | 8.95 | 2.17 | 0.176414E+11 | 11344.05 | 01-DEC-22:49 | 7.15 | 1.50 |
Annual Sum or Average | 0.467238E+12 | 0.221246E+12 | ||||||||
Minimum of Months | 0.298582E+11 | 16314.62 | 3.72 | -1.3 | 0.163520E+11 | 11344.05 | 3.53 | -1.3 | ||
Maximum of Months | 0.488183E+11 | 25007.89 | 29.72 | 14.71 | 0.193852E+11 | 11349.17 | 29.72 | 15.15 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.337728E+11 | 17853.89 | 05-JAN-22:10 | 3.72 | -1.3 | 0.183089E+11 | 11344.48 | 05-JAN-22:19 | 3.53 | -1.3 |
February | 0.317819E+11 | 19945.56 | 14-FEB-22:10 | 10.60 | 3.54 | 0.167792E+11 | 11345.00 | 13-FEB-22:10 | 10.60 | 3.54 |
March | 0.382649E+11 | 20823.35 | 16-MAR-21:10 | 14.17 | 4.07 | 0.190938E+11 | 11346.88 | 13-MAR-21:10 | 14.17 | 4.07 |
April | 0.411436E+11 | 23256.49 | 28-APR-21:10 | 19.90 | 7.11 | 0.186337E+11 | 11349.05 | 11-APR-22:10 | 19.90 | 7.11 |
May | 0.455517E+11 | 24247.10 | 19-MAY-21:02 | 23.12 | 8.19 | 0.193182E+11 | 11349.17 | 17-MAY-22:10 | 23.12 | 8.19 |
June | 0.484193E+11 | 26083.76 | 27-JUN-21:10 | 28.85 | 14.13 | 0.187563E+11 | 11349.10 | 01-JUN-00:49 | 28.85 | 14.13 |
July | 0.516057E+11 | 26209.94 | 21-JUL-21:10 | 29.72 | 14.71 | 0.193106E+11 | 11349.08 | 13-JUL-22:10 | 29.72 | 14.71 |
August | 0.504515E+11 | 25234.24 | 17-AUG-21:10 | 26.78 | 14.47 | 0.193913E+11 | 11349.12 | 29-AUG-21:10 | 19.90 | 15.15 |
September | 0.450867E+11 | 23822.41 | 13-SEP-21:10 | 21.60 | 12.51 | 0.186999E+11 | 11349.17 | 22-SEP-22:10 | 19.03 | 14.04 |
October | 0.410783E+11 | 23022.04 | 02-OCT-21:10 | 18.30 | 14.29 | 0.191370E+11 | 11349.06 | 04-OCT-22:10 | 17.70 | 10.79 |
November | 0.351214E+11 | 20501.66 | 08-NOV-22:10 | 13.62 | 7.41 | 0.181690E+11 | 11347.19 | 02-NOV-21:40 | 13.62 | 7.41 |
December | 0.332995E+11 | 18910.43 | 01-DEC-22:10 | 8.95 | 2.17 | 0.182157E+11 | 11344.34 | 29-DEC-22:19 | 2.03 | -1.4 |
Annual Sum or Average | 0.495577E+12 | 0.223814E+12 | ||||||||
Minimum of Months | 0.317819E+11 | 17853.89 | 3.72 | -1.3 | 0.167792E+11 | 11344.34 | 2.03 | -1.4 | ||
Maximum of Months | 0.516057E+11 | 26209.94 | 29.72 | 14.71 | 0.193913E+11 | 11349.17 | 29.72 | 15.15 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465458E+11 | 27632.62 | 01-JAN-11:40 | 9.83 | 3.02 | 0.188674E+11 | 11319.15 | 21-JAN-18:10 | 2.33 | -2.0 |
February | 0.431736E+11 | 28618.26 | 14-FEB-11:40 | 16.47 | 5.70 | 0.170431E+11 | 11319.29 | 18-FEB-18:10 | 9.82 | 3.45 |
March | 0.501878E+11 | 29675.32 | 26-MAR-10:40 | 14.80 | 5.60 | 0.188757E+11 | 11319.94 | 25-MAR-17:19 | 14.80 | 5.60 |
April | 0.517263E+11 | 31006.58 | 28-APR-10:40 | 21.13 | 8.61 | 0.182625E+11 | 11320.07 | 29-APR-17:49 | 24.08 | 9.12 |
May | 0.550185E+11 | 31072.69 | 20-MAY-10:40 | 22.40 | 8.51 | 0.188723E+11 | 11320.11 | 27-MAY-17:49 | 24.40 | 12.44 |
June | 0.560067E+11 | 32125.64 | 29-JUN-10:40 | 32.60 | 16.86 | 0.182670E+11 | 11320.10 | 03-JUN-17:00 | 32.60 | 16.86 |
July | 0.589323E+11 | 32602.78 | 22-JUL-10:40 | 33.33 | 17.03 | 0.188696E+11 | 11320.19 | 01-JUL-17:00 | 33.33 | 17.03 |
August | 0.584101E+11 | 32440.23 | 20-AUG-10:40 | 30.17 | 17.03 | 0.188767E+11 | 11320.13 | 12-AUG-17:40 | 30.17 | 17.03 |
September | 0.543076E+11 | 32187.80 | 03-SEP-10:40 | 28.53 | 16.32 | 0.182625E+11 | 11320.12 | 23-SEP-17:00 | 18.90 | 13.00 |
October | 0.525138E+11 | 30954.51 | 01-OCT-10:40 | 22.97 | 13.29 | 0.188690E+11 | 11320.15 | 07-OCT-17:49 | 15.62 | 12.50 |
November | 0.472485E+11 | 28408.80 | 01-NOV-10:40 | 13.13 | 7.69 | 0.182581E+11 | 11319.16 | 18-NOV-18:10 | 10.40 | 1.78 |
December | 0.462812E+11 | 27510.99 | 30-DEC-11:50 | 8.03 | 1.40 | 0.188674E+11 | 11319.16 | 02-DEC-18:10 | 8.03 | 1.40 |
Annual Sum or Average | 0.620352E+12 | 0.222191E+12 | ||||||||
Minimum of Months | 0.431736E+11 | 27510.99 | 8.03 | 1.40 | 0.170431E+11 | 11319.15 | 2.33 | -2.0 | ||
Maximum of Months | 0.589323E+11 | 32602.78 | 33.33 | 17.03 | 0.188767E+11 | 11320.19 | 33.33 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.410927E+09 | 3393.76 | 01-JAN-14:00 | 15.60 | 5.65 | 0.141110E+10 | 935.03 | 05-JAN-22:10 | 3.72 | -1.3 |
February | 0.904652E+09 | 6009.72 | 14-FEB-13:40 | 20.20 | 6.86 | 0.133545E+10 | 1007.40 | 15-FEB-00:20 | 9.80 | 3.40 |
March | 0.225267E+10 | 6436.20 | 08-MAR-13:50 | 22.33 | 9.56 | 0.162026E+10 | 1007.40 | 08-MAR-23:49 | 7.20 | 2.22 |
April | 0.557272E+10 | 8117.84 | 13-APR-12:50 | 23.62 | 8.92 | 0.163440E+10 | 1007.40 | 09-APR-23:40 | 23.62 | 8.92 |
May | 0.796992E+10 | 8775.32 | 30-MAY-14:30 | 27.20 | 12.25 | 0.171101E+10 | 1007.40 | 12-MAY-03:20 | 27.20 | 12.25 |
June | 0.116472E+11 | 10530.22 | 28-JUN-14:10 | 37.88 | 14.15 | 0.166539E+10 | 1007.40 | 23-JUN-21:10 | 37.88 | 14.15 |
July | 0.141639E+11 | 10474.70 | 20-JUL-14:10 | 37.02 | 15.31 | 0.171447E+10 | 1007.39 | 27-JUL-22:10 | 22.02 | 15.26 |
August | 0.136159E+11 | 10756.65 | 20-AUG-13:20 | 33.33 | 17.04 | 0.172172E+10 | 1007.39 | 28-AUG-22:10 | 17.70 | 13.87 |
September | 0.103282E+11 | 10606.52 | 03-SEP-13:30 | 31.95 | 16.76 | 0.166121E+10 | 1007.40 | 09-SEP-04:00 | 12.20 | 10.82 |
October | 0.602405E+10 | 9717.47 | 01-OCT-13:30 | 27.75 | 13.90 | 0.166951E+10 | 1007.40 | 12-OCT-21:30 | 6.65 | 0.07 |
November | 0.144130E+10 | 5811.78 | 02-NOV-14:10 | 15.87 | 8.99 | 0.152388E+10 | 1007.40 | 01-NOV-01:39 | 15.87 | 8.99 |
December | 0.183682E+09 | 3345.55 | 02-DEC-13:40 | 10.40 | 3.08 | 0.139392E+10 | 974.21 | 01-DEC-22:10 | 10.40 | 3.08 |
Annual Sum or Average | 0.745152E+11 | 0.190623E+11 | ||||||||
Minimum of Months | 0.183682E+09 | 3345.55 | 10.40 | 3.08 | 0.133545E+10 | 935.03 | 3.72 | -1.3 | ||
Maximum of Months | 0.141639E+11 | 10756.65 | 37.88 | 17.04 | 0.172172E+10 | 1007.40 | 37.88 | 15.26 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 3808303.41 | 769.84 | 13-FEB-16:00 | 21.70 |
March | 29304844.75 | 1836.07 | 08-MAR-14:00 | 22.80 |
April | 4524968.19 | 799.07 | 01-APR-13:50 | 22.02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 37638116.35 | |||
Minimum of Months | 0.00 | 0.00 | 2.30 | |
Maximum of Months | 29304844.75 | 1836.07 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333805E+09 | 1310.39 | 21-JAN-07:10 | -7.8 |
February | 0.200761E+09 | 1137.10 | 04-FEB-07:05 | -6.6 |
March | 47468187.73 | 781.26 | 04-MAR-06:10 | -1.7 |
April | 630208.90 | 165.82 | 08-APR-06:10 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 29604357.86 | 825.47 | 26-OCT-06:15 | -1.7 |
November | 35707616.44 | 584.10 | 27-NOV-06:10 | -4.4 |
December | 0.305771E+09 | 1226.53 | 09-DEC-07:20 | -2.9 |
Annual Sum or Average | 0.953748E+09 | |||
Minimum of Months | 0.00 | 0.00 | -7.8 | |
Maximum of Months | 0.333805E+09 | 1310.39 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166809E+09 | 523.54 | 20-JAN-02:20 | -7.9 |
February | 0.105743E+09 | 591.57 | 06-FEB-05:00 | -4.4 |
March | 9284650.26 | 263.36 | 04-MAR-06:00 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 812307.39 | 136.01 | 26-OCT-04:00 | -2.8 |
November | 5148443.80 | 222.94 | 27-NOV-05:00 | -3.9 |
December | 0.132152E+09 | 469.02 | 15-DEC-05:00 | -9.4 |
Annual Sum or Average | 0.419950E+09 | |||
Minimum of Months | 0.00 | 0.00 | -9.4 | |
Maximum of Months | 0.166809E+09 | 591.57 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.392154E+09 | 3556.19 | 17-JAN-09:02 | -2.5 |
February | 0.257837E+09 | 2347.21 | 16-FEB-16:12 | 1.70 |
March | 0.110120E+09 | 1608.32 | 22-MAR-18:03 | 9.72 |
April | 17891205.90 | 1693.37 | 28-APR-08:03 | 16.97 |
May | 7032399.64 | 1636.20 | 17-MAY-08:03 | 15.97 |
June | 2336005.76 | 1368.10 | 20-JUN-08:03 | 21.05 |
July | 42525.54 | 440.52 | 06-JUL-08:03 | 25.87 |
August | 333233.89 | 744.67 | 28-AUG-08:04 | 19.08 |
September | 2266490.95 | 1464.90 | 27-SEP-08:03 | 16.05 |
October | 45561683.70 | 2183.79 | 25-OCT-08:62 | 0.22 |
November | 0.128756E+09 | 1589.66 | 23-NOV-19:03 | 11.60 |
December | 0.380583E+09 | 3077.16 | 21-DEC-16:12 | -1.1 |
Annual Sum or Average | 0.134491E+10 | |||
Minimum of Months | 42525.54 | 440.52 | -2.5 | |
Maximum of Months | 0.392154E+09 | 3556.19 | 25.87 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.554997E+09 | 3687.34 | 20-JAN-09:02 | -3.2 |
February | 0.365058E+09 | 3806.89 | 04-FEB-09:02 | -3.5 |
March | 0.138217E+09 | 1586.72 | 28-MAR-15:13 | 11.87 |
April | 54462413.07 | 2332.73 | 02-APR-21:53 | 13.90 |
May | 47044714.24 | 1633.72 | 07-MAY-08:03 | 12.48 |
June | 32129860.01 | 1431.55 | 02-JUN-08:53 | 18.30 |
July | 40091901.24 | 1166.03 | 27-JUL-21:54 | 22.20 |
August | 43971610.37 | 1316.03 | 23-AUG-21:54 | 19.40 |
September | 59046862.49 | 2055.99 | 19-SEP-08:53 | 18.30 |
October | 91349765.92 | 2718.65 | 26-OCT-08:62 | 1.97 |
November | 0.201441E+09 | 2726.95 | 28-NOV-09:02 | -0.1 |
December | 0.580405E+09 | 3904.63 | 15-DEC-09:02 | -6.5 |
Annual Sum or Average | 0.220822E+10 | |||
Minimum of Months | 32129860.01 | 1166.03 | -6.5 | |
Maximum of Months | 0.580405E+09 | 3904.63 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24186037.85 | 676.29 | 01-JAN-09:03 | 2.67 |
February | 16830483.65 | 677.25 | 18-FEB-09:03 | 2.15 |
March | 4374531.70 | 641.60 | 10-MAR-09:03 | 4.78 |
April | 5706257.39 | 566.64 | 06-APR-08:03 | 4.08 |
May | 5747798.52 | 458.72 | 25-MAY-08:05 | 13.68 |
June | 5240443.00 | 349.29 | 09-JUN-08:05 | 12.88 |
July | 7932788.91 | 76.21 | 07-JUL-08:15 | 26.33 |
August | 7137046.38 | 76.99 | 18-AUG-08:32 | 26.50 |
September | 6115617.60 | 345.57 | 08-SEP-08:05 | 15.10 |
October | 5880183.82 | 647.51 | 13-OCT-08:03 | 5.78 |
November | 4555847.07 | 658.69 | 14-NOV-09:03 | 6.97 |
December | 33566754.51 | 1044.60 | 14-DEC-16:12 | 1.67 |
Annual Sum or Average | 0.127274E+09 | |||
Minimum of Months | 4374531.70 | 76.21 | 1.67 | |
Maximum of Months | 33566754.51 | 1044.60 | 26.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405754E+09 | 3294.84 | 20-JAN-09:02 | -3.2 |
February | 0.268427E+09 | 2658.45 | 16-FEB-16:12 | 1.70 |
March | 0.110126E+09 | 1677.34 | 19-MAR-18:03 | 12.43 |
April | 18052159.42 | 1429.95 | 15-APR-18:03 | 7.38 |
May | 3580655.93 | 1452.33 | 11-MAY-08:03 | 12.70 |
June | 350461.60 | 774.47 | 08-JUN-08:04 | 17.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 160199.61 | 1343.21 | 08-SEP-08:03 | 15.10 |
October | 45660270.26 | 2179.87 | 25-OCT-08:62 | 0.22 |
November | 0.131970E+09 | 1592.43 | 04-NOV-08:62 | 1.70 |
December | 0.392156E+09 | 2937.13 | 08-DEC-09:02 | -0.5 |
Annual Sum or Average | 0.137624E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.405754E+09 | 3294.84 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.552320E+09 | 3285.51 | 20-JAN-09:02 | -3.2 |
February | 0.367249E+09 | 2972.49 | 16-FEB-16:12 | 1.70 |
March | 0.144145E+09 | 2357.84 | 24-MAR-19:03 | 12.93 |
April | 54410699.90 | 2274.14 | 01-APR-21:53 | 12.20 |
May | 37215447.93 | 1856.44 | 03-MAY-19:03 | 13.72 |
June | 17687113.69 | 1487.08 | 10-JUN-19:54 | 20.00 |
July | 20897590.53 | 724.24 | 13-JUL-21:54 | 23.30 |
August | 23420068.95 | 500.76 | 29-AUG-20:55 | 20.00 |
September | 41867431.81 | 1149.88 | 15-SEP-21:54 | 15.60 |
October | 91837037.12 | 2439.23 | 14-OCT-19:13 | 12.77 |
November | 0.199124E+09 | 1953.04 | 04-NOV-08:62 | 1.70 |
December | 0.570756E+09 | 3161.51 | 21-DEC-16:12 | -1.1 |
Annual Sum or Average | 0.212093E+10 | |||
Minimum of Months | 17687113.69 | 500.76 | -3.2 | |
Maximum of Months | 0.570756E+09 | 3285.51 | 23.30 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102306E+10 | 4068.72 | 20-JAN-09:02 | -3.2 |
February | 0.721173E+09 | 4064.25 | 05-FEB-09:02 | -5.0 |
March | 0.428509E+09 | 2983.15 | 30-MAR-08:62 | 4.87 |
April | 0.123679E+09 | 1486.32 | 15-APR-08:03 | 14.27 |
May | 42289937.82 | 1544.02 | 04-MAY-15:13 | 12.20 |
June | 7867796.46 | 1487.74 | 01-JUN-18:03 | 12.30 |
July | 430018.96 | 564.48 | 28-JUL-08:03 | 22.57 |
August | 1405745.85 | 1271.66 | 31-AUG-08:03 | 20.87 |
September | 4866093.65 | 1382.59 | 15-SEP-08:03 | 21.47 |
October | 0.196789E+09 | 3845.68 | 25-OCT-08:62 | 0.22 |
November | 0.484168E+09 | 3750.96 | 04-NOV-08:62 | 1.70 |
December | 0.102001E+10 | 4004.33 | 22-DEC-09:02 | -5.2 |
Annual Sum or Average | 0.405424E+10 | |||
Minimum of Months | 430018.96 | 564.48 | -5.2 | |
Maximum of Months | 0.102306E+10 | 4068.72 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135172E+10 | 4047.00 | 20-JAN-09:02 | -3.2 |
February | 0.930412E+09 | 4200.67 | 04-FEB-09:02 | -3.5 |
March | 0.484507E+09 | 3787.75 | 04-MAR-09:02 | 2.15 |
April | 0.149031E+09 | 2386.91 | 01-APR-21:53 | 12.20 |
May | 81663698.42 | 2086.73 | 16-MAY-08:53 | 19.40 |
June | 41004545.04 | 2175.18 | 19-JUN-08:53 | 19.40 |
July | 46951876.94 | 943.37 | 16-JUL-21:54 | 22.80 |
August | 51378462.08 | 1349.26 | 12-AUG-21:54 | 21.10 |
September | 70031894.47 | 1934.78 | 17-SEP-08:53 | 17.80 |
October | 0.259631E+09 | 3830.43 | 27-OCT-08:62 | 2.98 |
November | 0.677271E+09 | 3977.05 | 28-NOV-09:02 | -0.1 |
December | 0.142625E+10 | 4304.80 | 15-DEC-09:02 | -6.5 |
Annual Sum or Average | 0.556985E+10 | |||
Minimum of Months | 41004545.04 | 943.37 | -6.5 | |
Maximum of Months | 0.142625E+10 | 4304.80 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284504E+09 | 1969.90 | 20-JAN-09:02 | -3.2 |
February | 0.199144E+09 | 1823.91 | 16-FEB-16:12 | 1.70 |
March | 0.112156E+09 | 956.52 | 21-MAR-18:03 | 9.53 |
April | 34436005.39 | 906.13 | 15-APR-18:03 | 7.38 |
May | 11706204.62 | 889.96 | 04-MAY-18:03 | 10.92 |
June | 1206088.96 | 620.03 | 16-JUN-08:03 | 26.28 |
July | 18560.36 | 197.23 | 06-JUL-08:03 | 25.87 |
August | 94873.43 | 456.38 | 28-AUG-08:04 | 19.08 |
September | 174766.37 | 716.34 | 08-SEP-08:03 | 15.10 |
October | 43089584.56 | 1833.98 | 25-OCT-08:62 | 0.22 |
November | 0.103406E+09 | 950.63 | 04-NOV-08:62 | 1.70 |
December | 0.279349E+09 | 1897.13 | 08-DEC-09:02 | -0.5 |
Annual Sum or Average | 0.106928E+10 | |||
Minimum of Months | 18560.36 | 197.23 | -3.2 | |
Maximum of Months | 0.284504E+09 | 1969.90 | 26.28 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.661491E+09 | 3644.15 | 21-JAN-07:10 | -7.8 |
February | 0.261110E+09 | 2808.08 | 06-FEB-07:10 | -5.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 6813054.99 | 957.34 | 26-OCT-06:20 | -1.7 |
November | 3552898.31 | 622.98 | 27-NOV-07:10 | -4.2 |
December | 0.695192E+09 | 3288.01 | 15-DEC-07:05 | -8.1 |
Annual Sum or Average | 0.162816E+10 | |||
Minimum of Months | 0.00 | 0.00 | -8.1 | |
Maximum of Months | 0.695192E+09 | 3644.15 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.204643E+11 | 19711.29 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.184774E+11 | 19711.29 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.205273E+11 | 19711.29 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.197704E+11 | 19711.29 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.204997E+11 | 19711.29 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.198611E+11 | 19711.29 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.204091E+11 | 19711.29 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.205352E+11 | 19711.29 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.197783E+11 | 19711.29 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.204564E+11 | 19711.29 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.198453E+11 | 19711.29 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.204091E+11 | 19711.29 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.241034E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.184774E+11 | 19711.29 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.205352E+11 | 19711.29 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101186E+10 | 974.63 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.913620E+09 | 974.63 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.101498E+10 | 974.63 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.977556E+09 | 974.63 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.101362E+10 | 974.63 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.982039E+09 | 974.63 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.100913E+10 | 974.63 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.101537E+10 | 974.63 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.977945E+09 | 974.63 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.101147E+10 | 974.63 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.981259E+09 | 974.63 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.100913E+10 | 974.63 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.119180E+11 | 0.101856E+11 | ||||
Minimum of Months | 0.913620E+09 | 974.63 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.101537E+10 | 974.63 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117174E+10 | 1128.63 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.105798E+10 | 1128.63 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.117535E+10 | 1128.63 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.113201E+10 | 1128.63 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.117377E+10 | 1128.63 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.113720E+10 | 1128.63 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.116858E+10 | 1128.63 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.117580E+10 | 1128.63 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.113246E+10 | 1128.63 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.117129E+10 | 1128.63 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.113630E+10 | 1128.63 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.116858E+10 | 1128.63 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.138011E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.105798E+10 | 1128.63 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.117580E+10 | 1128.63 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.247783E+10 | 2386.66 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.223726E+10 | 2386.66 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.248547E+10 | 2386.66 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.239382E+10 | 2386.66 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.248213E+10 | 2386.66 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.240480E+10 | 2386.66 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.247115E+10 | 2386.66 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.248642E+10 | 2386.66 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.239478E+10 | 2386.66 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.247688E+10 | 2386.66 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.240289E+10 | 2386.66 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.247115E+10 | 2386.66 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.291846E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.223726E+10 | 2386.66 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.248642E+10 | 2386.66 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.762439E+09 | 734.39 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.688413E+09 | 734.39 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.764789E+09 | 734.39 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.736588E+09 | 734.39 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.763761E+09 | 734.39 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.739966E+09 | 734.39 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.760382E+09 | 734.39 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.765082E+09 | 734.39 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.736882E+09 | 734.39 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.762145E+09 | 734.39 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.739379E+09 | 734.39 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.760382E+09 | 734.39 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.898021E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.688413E+09 | 734.39 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.765082E+09 | 734.39 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.265929E+10 | 2561.44 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.240110E+10 | 2561.44 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.266749E+10 | 2561.44 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.256913E+10 | 2561.44 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.266390E+10 | 2561.44 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.258091E+10 | 2561.44 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.265212E+10 | 2561.44 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.266851E+10 | 2561.44 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.257015E+10 | 2561.44 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.265826E+10 | 2561.44 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.257886E+10 | 2561.44 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.265212E+10 | 2561.44 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.313218E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.240110E+10 | 2561.44 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.266851E+10 | 2561.44 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.171043E+11 | 16474.99 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.154437E+11 | 16474.99 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.171571E+11 | 16474.99 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.165244E+11 | 16474.99 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.171340E+11 | 16474.99 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.166002E+11 | 16474.99 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.170582E+11 | 16474.99 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.171636E+11 | 16474.99 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.165310E+11 | 16474.99 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.170977E+11 | 16474.99 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.165870E+11 | 16474.99 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.170582E+11 | 16474.99 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.201459E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.154437E+11 | 16474.99 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.171636E+11 | 16474.99 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332597E+09 | 300.93 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.300367E+09 | 300.93 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.329954E+09 | 300.93 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.322251E+09 | 300.93 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.331275E+09 | 300.93 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.319694E+09 | 300.93 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.333875E+09 | 300.93 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.329954E+09 | 300.93 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.322338E+09 | 300.93 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.332554E+09 | 300.93 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.320973E+09 | 300.93 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.333919E+09 | 300.93 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.390975E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.300367E+09 | 300.93 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.333919E+09 | 300.93 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332688E+09 | 301.01 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.300450E+09 | 301.01 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.330044E+09 | 301.01 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.322339E+09 | 301.01 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.331366E+09 | 301.01 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.319782E+09 | 301.01 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.333967E+09 | 301.01 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.330044E+09 | 301.01 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.322426E+09 | 301.01 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.332644E+09 | 301.01 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.321060E+09 | 301.01 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.334010E+09 | 301.01 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.391082E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.300450E+09 | 301.01 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.334010E+09 | 301.01 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.195823E+10 | 1886.18 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.176811E+10 | 1886.18 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.196427E+10 | 1886.18 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.189184E+10 | 1886.18 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.196163E+10 | 1886.18 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.190052E+10 | 1886.18 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.195295E+10 | 1886.18 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.196502E+10 | 1886.18 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.189259E+10 | 1886.18 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.195748E+10 | 1886.18 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.189901E+10 | 1886.18 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.195295E+10 | 1886.18 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.230646E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.176811E+10 | 1886.18 | 0.00 | 0.00 | |
Maximum of Months | 0.196502E+10 | 1886.18 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332688E+09 | 301.01 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.300450E+09 | 301.01 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.330044E+09 | 301.01 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.322339E+09 | 301.01 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.331366E+09 | 301.01 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.319782E+09 | 301.01 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.333967E+09 | 301.01 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.330044E+09 | 301.01 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.322426E+09 | 301.01 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.332644E+09 | 301.01 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.321060E+09 | 301.01 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.334010E+09 | 301.01 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.391082E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.300450E+09 | 301.01 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.334010E+09 | 301.01 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466994E+10 | 4498.11 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.421653E+10 | 4498.11 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.468433E+10 | 4498.11 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.451160E+10 | 4498.11 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.467803E+10 | 4498.11 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.453229E+10 | 4498.11 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.465734E+10 | 4498.11 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.468613E+10 | 4498.11 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.451340E+10 | 4498.11 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.466814E+10 | 4498.11 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.452870E+10 | 4498.11 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.465734E+10 | 4498.11 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.550038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.421653E+10 | 4498.11 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.468613E+10 | 4498.11 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466994E+10 | 4498.11 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.421653E+10 | 4498.11 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.468433E+10 | 4498.11 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.451160E+10 | 4498.11 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.467803E+10 | 4498.11 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.453229E+10 | 4498.11 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.465734E+10 | 4498.11 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.468613E+10 | 4498.11 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.451340E+10 | 4498.11 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.466814E+10 | 4498.11 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.452870E+10 | 4498.11 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.465734E+10 | 4498.11 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.550038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.421653E+10 | 4498.11 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.468613E+10 | 4498.11 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124679E+10 | 1200.92 | 02-JAN-20:10 | 0.371477E+11 | 16602.84 | 01-JAN-07:10 |
February | 0.112574E+10 | 1200.92 | 01-FEB-20:10 | 0.335528E+11 | 16602.84 | 01-FEB-07:10 |
March | 0.125063E+10 | 1200.92 | 01-MAR-20:10 | 0.371477E+11 | 16602.84 | 01-MAR-07:10 |
April | 0.120452E+10 | 1200.92 | 03-APR-19:10 | 0.359494E+11 | 16602.84 | 01-APR-06:10 |
May | 0.124895E+10 | 1200.92 | 01-MAY-19:10 | 0.371477E+11 | 16602.84 | 01-MAY-06:10 |
June | 0.121004E+10 | 1200.92 | 01-JUN-19:10 | 0.359494E+11 | 16602.84 | 01-JUN-06:10 |
July | 0.124343E+10 | 1200.92 | 03-JUL-19:10 | 0.371477E+11 | 16602.84 | 01-JUL-06:10 |
August | 0.125111E+10 | 1200.92 | 01-AUG-19:10 | 0.371477E+11 | 16602.84 | 01-AUG-06:10 |
September | 0.120500E+10 | 1200.92 | 01-SEP-19:10 | 0.359494E+11 | 16602.84 | 01-SEP-06:10 |
October | 0.124631E+10 | 1200.92 | 02-OCT-19:10 | 0.371477E+11 | 16602.84 | 01-OCT-06:10 |
November | 0.120908E+10 | 1200.92 | 01-NOV-19:10 | 0.359494E+11 | 16602.84 | 01-NOV-06:10 |
December | 0.124343E+10 | 1200.92 | 01-DEC-20:10 | 0.371477E+11 | 16602.84 | 01-DEC-07:10 |
Annual Sum or Average | 0.146850E+11 | 0.437384E+12 | ||||
Minimum of Months | 0.112574E+10 | 1200.92 | 0.335528E+11 | 16602.84 | ||
Maximum of Months | 0.125111E+10 | 1200.92 | 0.371477E+11 | 16602.84 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.207249E+10 | 1996.23 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.187127E+10 | 1996.23 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.207888E+10 | 1996.23 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.200222E+10 | 1996.23 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.207608E+10 | 1996.23 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.201140E+10 | 1996.23 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.206690E+10 | 1996.23 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.207967E+10 | 1996.23 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.200302E+10 | 1996.23 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.207169E+10 | 1996.23 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.200981E+10 | 1996.23 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.206690E+10 | 1996.23 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.244103E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.187127E+10 | 1996.23 | 0.00 | 0.00 | |
Maximum of Months | 0.207967E+10 | 1996.23 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.204643E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.184774E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.205273E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.197704E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.204997E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.198611E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.204091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.205352E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.197783E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.204564E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.198453E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.204091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.241034E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.184774E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.205352E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.101186E+10 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544841E+09 |
February | 0.179968E+10 | 0.913620E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450239E+09 |
March | 0.199990E+10 | 0.101498E+10 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369386E+09 |
April | 0.192973E+10 | 0.977556E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1007051.27 | 0.231130E+09 |
May | 0.199475E+10 | 0.101362E+10 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10611834.08 | 0.146284E+09 |
June | 0.193394E+10 | 0.982039E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59794783.56 | 66454212.21 |
July | 0.199054E+10 | 0.100913E+10 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77080930.26 | 28301829.95 |
August | 0.199896E+10 | 0.101537E+10 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53561278.34 | 43716073.76 |
September | 0.192879E+10 | 0.977945E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19250074.14 | 94777106.00 |
October | 0.199148E+10 | 0.101147E+10 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3238019.97 | 0.253356E+09 |
November | 0.192552E+10 | 0.981259E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412729E+09 |
December | 0.199054E+10 | 0.100913E+10 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560967E+09 |
Annual Sum or Average | 0.234744E+11 | 0.119180E+11 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224544E+09 | 0.320218E+10 |
Minimum of Months | 0.179968E+10 | 0.913620E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28301829.95 |
Maximum of Months | 0.199990E+10 | 0.101537E+10 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77080930.26 | 0.560967E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.117174E+10 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217484E+09 |
February | 0.208403E+10 | 0.105798E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180094E+09 |
March | 0.231589E+10 | 0.117535E+10 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151742E+09 |
April | 0.223463E+10 | 0.113201E+10 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 420594.78 | 96987530.62 |
May | 0.230993E+10 | 0.117377E+10 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4254592.40 | 64488906.50 |
June | 0.223950E+10 | 0.113720E+10 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23123930.80 | 30844820.13 |
July | 0.230505E+10 | 0.116858E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29743092.13 | 14127677.06 |
August | 0.231480E+10 | 0.117580E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20755095.27 | 20371444.58 |
September | 0.223354E+10 | 0.113246E+10 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7531588.51 | 41594773.73 |
October | 0.230614E+10 | 0.117129E+10 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1279187.29 | 0.104872E+09 |
November | 0.222975E+10 | 0.113630E+10 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168067E+09 |
December | 0.230505E+10 | 0.116858E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223441E+09 |
Annual Sum or Average | 0.271834E+11 | 0.138011E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87108081.19 | 0.131412E+10 |
Minimum of Months | 0.208403E+10 | 0.105798E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14127677.06 |
Maximum of Months | 0.231589E+10 | 0.117580E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29743092.13 | 0.223441E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.247783E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494516E+09 |
February | 0.440737E+09 | 0.223726E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408056E+09 |
March | 0.489771E+09 | 0.248547E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.84 | 0.347026E+09 |
April | 0.472586E+09 | 0.239382E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1268669.55 | 0.225516E+09 |
May | 0.488511E+09 | 0.248213E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9751400.85 | 0.153151E+09 |
June | 0.473617E+09 | 0.240480E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54117545.44 | 73751665.80 |
July | 0.487480E+09 | 0.247115E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69969661.63 | 33315256.51 |
August | 0.489542E+09 | 0.248642E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48753029.79 | 48254991.72 |
September | 0.472357E+09 | 0.239478E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17663328.47 | 98569042.63 |
October | 0.487709E+09 | 0.247688E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3026760.48 | 0.243163E+09 |
November | 0.471555E+09 | 0.240289E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384189E+09 |
December | 0.487480E+09 | 0.247115E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507373E+09 |
Annual Sum or Average | 0.574883E+10 | 0.291846E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204551E+09 | 0.301688E+10 |
Minimum of Months | 0.440737E+09 | 0.223726E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33315256.51 |
Maximum of Months | 0.489771E+09 | 0.248642E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69969661.63 | 0.507373E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.762439E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273829E+09 |
February | 0.339028E+09 | 0.688413E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 654.94 | 0.224165E+09 |
March | 0.376747E+09 | 0.764789E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19223.07 | 0.183234E+09 |
April | 0.363528E+09 | 0.736588E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1263014.85 | 0.116583E+09 |
May | 0.375778E+09 | 0.763761E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6523764.67 | 79208753.68 |
June | 0.364321E+09 | 0.739966E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31569230.19 | 38619303.99 |
July | 0.374985E+09 | 0.760382E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40462352.51 | 17306326.34 |
August | 0.376571E+09 | 0.765082E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28398619.46 | 24993233.02 |
September | 0.363352E+09 | 0.736882E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11102118.78 | 51063531.68 |
October | 0.375161E+09 | 0.762145E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2234704.65 | 0.126534E+09 |
November | 0.362735E+09 | 0.739379E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203578E+09 |
December | 0.374985E+09 | 0.760382E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280954E+09 |
Annual Sum or Average | 0.442217E+10 | 0.898021E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121574E+09 | 0.162007E+10 |
Minimum of Months | 0.339028E+09 | 0.688413E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17306326.34 |
Maximum of Months | 0.376747E+09 | 0.765082E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40462352.51 | 0.280954E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751375E+09 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620595E+09 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522323E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 1254064.24 | 0.331312E+09 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 12891218.82 | 0.220175E+09 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 73817241.11 | 0.103608E+09 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 95534776.55 | 46202723.72 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 66558050.65 | 66996809.10 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 23973490.21 | 0.138441E+09 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 4032518.41 | 0.354332E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570147E+09 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768756E+09 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.278061E+09 | 0.449426E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46202723.72 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 95534776.55 | 0.768756E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.265929E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119972E+10 |
February | 0.236489E+11 | 0.240110E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998835E+09 |
March | 0.262800E+11 | 0.266749E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853474E+09 |
April | 0.253579E+11 | 0.256913E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2225455.45 | 0.559633E+09 |
May | 0.262123E+11 | 0.266390E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22876879.86 | 0.383678E+09 |
June | 0.254132E+11 | 0.258091E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130996E+09 | 0.183387E+09 |
July | 0.261570E+11 | 0.265212E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169534E+09 | 81940808.29 |
August | 0.262677E+11 | 0.266851E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118116E+09 | 0.118833E+09 |
September | 0.253456E+11 | 0.257015E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42546621.61 | 0.245522E+09 |
October | 0.261693E+11 | 0.265826E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7157365.85 | 0.598441E+09 |
November | 0.253025E+11 | 0.257886E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938261E+09 |
December | 0.261570E+11 | 0.265212E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123215E+10 |
Annual Sum or Average | 0.308468E+12 | 0.313218E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493453E+09 | 0.739387E+10 |
Minimum of Months | 0.236489E+11 | 0.240110E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81940808.29 |
Maximum of Months | 0.262800E+11 | 0.266851E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169534E+09 | 0.123215E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.171043E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364899E+10 |
February | 0.702046E+11 | 0.154437E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302278E+10 |
March | 0.780153E+11 | 0.171571E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255023E+10 |
April | 0.752779E+11 | 0.165244E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6435950.01 | 0.162951E+10 |
May | 0.778146E+11 | 0.171340E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67808284.20 | 0.108371E+10 |
June | 0.754422E+11 | 0.166002E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376695E+09 | 0.515444E+09 |
July | 0.776503E+11 | 0.170582E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486130E+09 | 0.233315E+09 |
August | 0.779788E+11 | 0.171636E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338464E+09 | 0.336402E+09 |
September | 0.752414E+11 | 0.165310E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121649E+09 | 0.694224E+09 |
October | 0.776868E+11 | 0.170977E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20574244.45 | 0.175936E+10 |
November | 0.751137E+11 | 0.165870E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282125E+10 |
December | 0.776503E+11 | 0.170582E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375113E+10 |
Annual Sum or Average | 0.915726E+12 | 0.201459E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141776E+10 | 0.220464E+11 |
Minimum of Months | 0.702046E+11 | 0.154437E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233315E+09 |
Maximum of Months | 0.780153E+11 | 0.171636E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486130E+09 | 0.375113E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310296E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5356.01 | 0.254791E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23924.87 | 0.207098E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2408149.48 | 0.122812E+09 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11418576.08 | 74237146.51 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47564621.83 | 29572531.59 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62354083.75 | 6887382.44 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45785704.93 | 13268820.45 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17844018.36 | 38898062.72 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3610423.00 | 0.131770E+09 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230099E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318353E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191015E+09 | 0.173808E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6887382.44 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62354083.75 | 0.318353E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305516E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252300E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211613E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1885272.56 | 0.135551E+09 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10500302.71 | 85080027.07 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46037126.25 | 36938257.03 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60052491.67 | 14136064.39 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44006815.80 | 22425293.56 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16890944.21 | 51536820.04 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3129988.49 | 0.142884E+09 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227371E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312481E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182503E+09 | 0.179783E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14136064.39 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60052491.67 | 0.312481E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.332597E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107333E+09 |
February | 0.00 | 0.300367E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90083785.38 |
March | 0.00 | 0.329954E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78864327.79 |
April | 0.00 | 0.322251E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53912862.28 |
May | 0.00 | 0.331275E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 326777.18 | 38725396.80 |
June | 0.00 | 0.319694E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5528700.50 | 20452954.67 |
July | 0.00 | 0.333875E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7103243.67 | 12057434.46 |
August | 0.00 | 0.329954E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4364216.05 | 15853832.80 |
September | 0.00 | 0.322338E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 953794.76 | 27034491.05 |
October | 0.00 | 0.332554E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48649.23 | 56977171.58 |
November | 0.00 | 0.320973E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84997695.87 |
December | 0.00 | 0.333919E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110082E+09 |
Annual Sum or Average | 0.00 | 0.390975E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18325381.40 | 0.696376E+09 |
Minimum of Months | 0.00 | 0.300367E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12057434.46 |
Maximum of Months | 0.00 | 0.333919E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7103243.67 | 0.110082E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.332688E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85402130.75 |
February | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70179005.15 |
March | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57980211.88 |
April | 0.293479E+09 | 0.322339E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 533959.33 | 35961731.67 |
May | 0.303504E+09 | 0.331366E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2943826.99 | 22669615.93 |
June | 0.293842E+09 | 0.319782E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12849277.18 | 9777514.07 |
July | 0.303141E+09 | 0.333967E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16737429.69 | 3564528.06 |
August | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12282370.01 | 5672147.83 |
September | 0.293479E+09 | 0.322426E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4741228.71 | 13466374.34 |
October | 0.303322E+09 | 0.332644E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 879886.85 | 38213830.81 |
November | 0.293661E+09 | 0.321060E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63152389.43 |
December | 0.303141E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87221937.77 |
Annual Sum or Average | 0.357224E+10 | 0.391082E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50967978.76 | 0.493261E+09 |
Minimum of Months | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3564528.06 |
Maximum of Months | 0.303685E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16737429.69 | 87221937.77 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311134E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5411.87 | 0.255560E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24085.78 | 0.208227E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2419602.70 | 0.123745E+09 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11423701.51 | 74854365.42 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47520172.14 | 29821973.26 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62291668.29 | 6974872.79 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45757276.81 | 13451119.41 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17849670.27 | 39224302.77 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3619191.04 | 0.132461E+09 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230702E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319528E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190911E+09 | 0.174568E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6974872.79 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62291668.29 | 0.319528E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306733E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253236E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210912E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1900061.85 | 0.132617E+09 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10505042.28 | 84981432.54 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45926388.96 | 40062122.33 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59817037.60 | 17597658.68 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43842640.23 | 25904251.88 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16863372.38 | 52567362.45 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3141712.08 | 0.140094E+09 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228607E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312730E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181996E+09 | 0.180604E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17597658.68 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59817037.60 | 0.312730E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.195823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420232E+09 |
February | 0.348285E+10 | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348832E+09 |
March | 0.387034E+10 | 0.196427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294864E+09 |
April | 0.373454E+10 | 0.189184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668008.54 | 0.187394E+09 |
May | 0.386038E+10 | 0.196163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7125013.19 | 0.124694E+09 |
June | 0.374269E+10 | 0.190052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41273398.82 | 58796221.84 |
July | 0.385223E+10 | 0.195295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53421287.51 | 26366919.76 |
August | 0.386853E+10 | 0.196502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37161270.51 | 38153525.58 |
September | 0.373273E+10 | 0.189259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13315504.50 | 78546839.70 |
October | 0.385404E+10 | 0.195748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2224803.13 | 0.200136E+09 |
November | 0.372639E+10 | 0.189901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321707E+09 |
December | 0.385223E+10 | 0.195295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431007E+09 |
Annual Sum or Average | 0.454292E+11 | 0.230646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155189E+09 | 0.253073E+10 |
Minimum of Months | 0.348285E+10 | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26366919.76 |
Maximum of Months | 0.387034E+10 | 0.196502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53421287.51 | 0.431007E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308413E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4428.87 | 0.253781E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22449.41 | 0.206528E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2328012.97 | 0.122987E+09 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11183381.79 | 74471799.51 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47094150.77 | 29832875.10 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61707258.96 | 7096608.71 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45228543.08 | 13503811.14 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17533983.83 | 39163769.18 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3522651.91 | 0.131553E+09 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229262E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316444E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188625E+09 | 0.173304E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7096608.71 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61707258.96 | 0.316444E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302623E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250394E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210775E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1832660.47 | 0.136563E+09 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10305635.32 | 85620210.62 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45615791.35 | 37048369.81 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59483713.36 | 13975938.64 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43511280.74 | 22421739.94 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16619571.63 | 51705011.80 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3061871.12 | 0.142989E+09 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225384E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309238E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180431E+09 | 0.178874E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13975938.64 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59483713.36 | 0.309238E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.332688E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159994E+09 |
February | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2186.71 | 0.131176E+09 |
March | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11402.49 | 0.106491E+09 |
April | 0.293479E+09 | 0.322339E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1194051.13 | 63179268.61 |
May | 0.303504E+09 | 0.331366E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5728354.33 | 38186456.07 |
June | 0.293842E+09 | 0.319782E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24106432.32 | 15266948.40 |
July | 0.303141E+09 | 0.333967E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31577369.29 | 3637751.96 |
August | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23138960.44 | 6916523.54 |
September | 0.293479E+09 | 0.322426E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8964115.87 | 20143540.61 |
October | 0.303322E+09 | 0.332644E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1799460.79 | 67958110.96 |
November | 0.293661E+09 | 0.321060E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118559E+09 |
December | 0.303141E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164098E+09 |
Annual Sum or Average | 0.357224E+10 | 0.391082E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96522333.37 | 0.895607E+09 |
Minimum of Months | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3637751.96 |
Maximum of Months | 0.303685E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31577369.29 | 0.164098E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.466994E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813131E+09 |
February | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676967E+09 |
March | 0.461508E+11 | 0.468433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578614E+09 |
April | 0.445315E+11 | 0.451160E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1250145.32 | 0.373305E+09 |
May | 0.460320E+11 | 0.467803E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14136706.08 | 0.250237E+09 |
June | 0.446286E+11 | 0.453229E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82478761.14 | 0.119083E+09 |
July | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106772E+09 | 54177402.25 |
August | 0.461292E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74129726.66 | 77864978.31 |
September | 0.445099E+11 | 0.451340E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26404539.26 | 0.158421E+09 |
October | 0.459565E+11 | 0.466814E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4445157.69 | 0.394684E+09 |
November | 0.444343E+11 | 0.452870E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625107E+09 |
December | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829608E+09 |
Annual Sum or Average | 0.541708E+12 | 0.550038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309617E+09 | 0.495120E+10 |
Minimum of Months | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54177402.25 |
Maximum of Months | 0.461508E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106772E+09 | 0.829608E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.466994E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827723E+09 |
February | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688336E+09 |
March | 0.461508E+11 | 0.468433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586891E+09 |
April | 0.445315E+11 | 0.451160E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1245807.89 | 0.377175E+09 |
May | 0.460320E+11 | 0.467803E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14050083.09 | 0.252140E+09 |
June | 0.446286E+11 | 0.453229E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82477726.01 | 0.119644E+09 |
July | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106765E+09 | 54213274.60 |
August | 0.461292E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74109289.87 | 78162133.91 |
September | 0.445099E+11 | 0.451340E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26356126.44 | 0.159653E+09 |
October | 0.459565E+11 | 0.466814E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4368167.20 | 0.399832E+09 |
November | 0.444343E+11 | 0.452870E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634929E+09 |
December | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844454E+09 |
Annual Sum or Average | 0.541708E+12 | 0.550038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309373E+09 | 0.502315E+10 |
Minimum of Months | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54213274.60 |
Maximum of Months | 0.461508E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106765E+09 | 0.844454E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.124679E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768652E+09 |
February | 0.369574E+10 | 0.112574E+10 | 0.304050E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635102E+09 |
March | 0.410691E+10 | 0.125063E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535295E+09 |
April | 0.396281E+10 | 0.120452E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1110833.28 | 0.340497E+09 |
May | 0.409635E+10 | 0.124895E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 12521186.10 | 0.227000E+09 |
June | 0.397146E+10 | 0.121004E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 73781825.88 | 0.107380E+09 |
July | 0.408770E+10 | 0.124343E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 95500129.23 | 48627506.89 |
August | 0.410499E+10 | 0.125111E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 66278779.20 | 70113025.66 |
September | 0.396089E+10 | 0.120500E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 23562292.74 | 0.143444E+09 |
October | 0.408962E+10 | 0.124631E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3896840.87 | 0.364028E+09 |
November | 0.395417E+10 | 0.120908E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583867E+09 |
December | 0.408770E+10 | 0.124343E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786360E+09 |
Annual Sum or Average | 0.482060E+11 | 0.146850E+11 | 0.396352E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.276652E+09 | 0.461037E+10 |
Minimum of Months | 0.369574E+10 | 0.112574E+10 | 0.304050E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48627506.89 |
Maximum of Months | 0.410691E+10 | 0.125111E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 95500129.23 | 0.786360E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.207249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689456E+09 |
February | 0.368610E+10 | 0.187127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578820E+09 |
March | 0.409620E+10 | 0.207888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504613E+09 |
April | 0.395248E+10 | 0.200222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1089225.89 | 0.328430E+09 |
May | 0.408566E+10 | 0.207608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12265261.49 | 0.221040E+09 |
June | 0.396110E+10 | 0.201140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72243506.31 | 0.105069E+09 |
July | 0.407704E+10 | 0.206690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93517625.55 | 47553832.88 |
August | 0.409429E+10 | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64909590.77 | 68590559.70 |
September | 0.395056E+10 | 0.200302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23082089.91 | 0.140391E+09 |
October | 0.407896E+10 | 0.207169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3818392.94 | 0.347374E+09 |
November | 0.394385E+10 | 0.200981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546576E+09 |
December | 0.407704E+10 | 0.206690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703915E+09 |
Annual Sum or Average | 0.480803E+11 | 0.244103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270926E+09 | 0.428183E+10 |
Minimum of Months | 0.368610E+10 | 0.187127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47553832.88 |
Maximum of Months | 0.409620E+10 | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93517625.55 | 0.703915E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 19711.29 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 19711.29 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 19711.29 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 19711.29 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 19711.29 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 19711.29 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 19711.29 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 19711.29 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 19711.29 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 19711.29 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 19711.29 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 19711.29 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 974.63 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 320.67 | 21-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 974.63 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 299.56 | 04-FEB-06:10 |
March | 1169.53 | 01-MAR-00:10 | 974.63 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 268.38 | 05-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 974.63 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 13-APR-16:51 | 203.84 | 08-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 974.63 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.37 | 22-MAY-13:00 | 172.13 | 07-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 974.63 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.70 | 28-JUN-16:00 | 135.85 | 09-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 974.63 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.05 | 22-JUL-15:00 | 61.67 | 08-JUL-03:00 |
August | 1169.53 | 01-AUG-00:10 | 974.63 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.15 | 20-AUG-15:00 | 93.21 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 974.63 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.74 | 03-SEP-14:00 | 113.31 | 20-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 974.63 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.80 | 01-OCT-16:00 | 254.61 | 26-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 974.63 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 272.98 | 27-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 974.63 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 334.74 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 974.63 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 | |||||
Maximum of Months | 1169.53 | 974.63 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 137.70 | 334.74 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 1128.63 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 125.68 | 21-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 1128.63 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 119.23 | 05-FEB-08:00 |
March | 1354.32 | 01-MAR-00:10 | 1128.63 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 107.85 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 1128.63 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 | 13-APR-16:51 | 84.96 | 08-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 1128.63 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 22-MAY-13:00 | 73.45 | 07-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 1128.63 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 28-JUN-16:00 | 60.86 | 09-JUN-04:40 |
July | 1354.32 | 01-JUL-00:10 | 1128.63 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.97 | 22-JUL-15:00 | 29.56 | 08-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 1128.63 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.81 | 20-AUG-15:00 | 43.07 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 1128.63 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.94 | 03-SEP-14:00 | 51.62 | 20-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 1128.63 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 01-OCT-16:00 | 103.85 | 27-OCT-06:53 |
November | 1354.32 | 01-NOV-00:10 | 1128.63 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 110.73 | 27-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 1128.63 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 133.18 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.56 | |||||
Maximum of Months | 1354.32 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | 133.18 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 2386.66 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 292.51 | 21-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 2386.66 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 273.42 | 05-FEB-08:00 |
March | 286.42 | 01-MAR-00:10 | 2386.66 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 08-MAR-14:00 | 248.55 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 2386.66 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 | 13-APR-16:51 | 196.82 | 06-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 2386.66 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.38 | 22-MAY-13:00 | 171.88 | 07-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 2386.66 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.61 | 28-JUN-16:00 | 143.43 | 09-JUN-04:40 |
July | 286.42 | 01-JUL-00:10 | 2386.66 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.46 | 22-JUL-15:00 | 69.03 | 08-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 2386.66 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.09 | 20-AUG-15:00 | 101.67 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 2386.66 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.49 | 03-SEP-14:00 | 121.19 | 20-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 2386.66 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.69 | 01-OCT-16:00 | 242.88 | 27-OCT-06:53 |
November | 286.42 | 01-NOV-00:10 | 2386.66 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 255.42 | 27-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 2386.66 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 305.38 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.03 | |||||
Maximum of Months | 286.42 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 125.61 | 305.38 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 734.39 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 168.77 | 21-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 734.39 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 14-FEB-16:00 | 157.65 | 04-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 734.39 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 08-MAR-14:00 | 141.25 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 734.39 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.95 | 13-APR-17:00 | 107.28 | 08-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 734.39 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.01 | 22-MAY-13:00 | 91.66 | 07-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 734.39 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.47 | 28-JUN-16:00 | 77.09 | 09-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 734.39 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.50 | 22-JUL-15:00 | 36.89 | 08-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 734.39 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.29 | 20-AUG-15:00 | 53.97 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 734.39 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 | 03-SEP-14:00 | 64.02 | 20-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 734.39 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 | 01-OCT-16:00 | 134.00 | 26-OCT-06:56 |
November | 220.32 | 01-NOV-00:10 | 734.39 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 143.66 | 27-NOV-06:50 |
December | 220.32 | 01-DEC-00:10 | 734.39 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 176.19 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.89 | |||||
Maximum of Months | 220.32 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 72.47 | 176.19 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 440.30 | 21-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 413.48 | 04-FEB-06:00 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 374.56 | 05-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 25.03 | 13-APR-16:51 | 293.34 | 08-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 71.49 | 22-MAY-13:00 | 253.16 | 07-MAY-05:00 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 171.52 | 28-JUN-16:00 | 207.64 | 09-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 164.48 | 22-JUL-15:00 | 98.28 | 08-JUL-03:00 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 128.47 | 20-AUG-15:00 | 140.82 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 103.08 | 03-SEP-14:00 | 170.79 | 09-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 58.29 | 01-OCT-16:00 | 357.11 | 26-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 380.13 | 27-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 458.11 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 98.28 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 171.52 | 458.11 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2561.44 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 708.79 | 21-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 2561.44 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 662.07 | 04-FEB-06:50 |
March | 15368.40 | 01-MAR-00:10 | 2561.44 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 593.23 | 05-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 2561.44 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.42 | 13-APR-16:51 | 450.55 | 08-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 2561.44 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.87 | 22-MAY-13:00 | 389.38 | 07-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 2561.44 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.38 | 28-JUN-16:00 | 350.04 | 09-JUN-04:00 |
July | 15368.40 | 01-JUL-00:10 | 2561.44 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.88 | 22-JUL-15:00 | 174.32 | 08-JUL-04:00 |
August | 15368.40 | 01-AUG-00:10 | 2561.44 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.99 | 20-AUG-15:00 | 249.85 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 2561.44 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.92 | 03-SEP-14:00 | 301.53 | 25-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 2561.44 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.44 | 01-OCT-16:00 | 562.79 | 26-OCT-06:52 |
November | 15368.40 | 01-NOV-00:10 | 2561.44 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 603.34 | 27-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 2561.44 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 739.96 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2561.44 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.32 | |||||
Maximum of Months | 15368.40 | 2561.44 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 304.38 | 739.96 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 16474.99 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2106.39 | 20-JAN-02:00 |
February | 45622.98 | 01-FEB-00:10 | 16474.99 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1998.77 | 04-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 16474.99 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1802.14 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 16474.99 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.94 | 13-APR-16:51 | 1422.96 | 08-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 16474.99 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.11 | 22-MAY-13:00 | 1229.63 | 07-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 16474.99 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 869.74 | 28-JUN-16:00 | 1041.30 | 09-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 16474.99 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 834.05 | 22-JUL-15:00 | 498.18 | 08-JUL-03:00 |
August | 45622.98 | 01-AUG-00:10 | 16474.99 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 651.50 | 20-AUG-15:00 | 713.92 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 16474.99 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 522.69 | 03-SEP-14:00 | 861.63 | 25-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 16474.99 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.60 | 01-OCT-16:00 | 1732.12 | 26-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 16474.99 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1861.72 | 27-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 16474.99 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2233.93 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 16474.99 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.18 | |||||
Maximum of Months | 45622.98 | 16474.99 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 869.74 | 2233.93 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.09 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 14-FEB-16:20 | 174.81 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 08-MAR-16:20 | 156.73 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 | 13-APR-16:50 | 119.24 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:20 | 100.84 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.76 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.19 | 22-JUL-15:20 | 32.18 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 20-AUG-15:20 | 48.95 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.58 | 02-SEP-15:20 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 148.56 | 26-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.38 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.28 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.28 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.07 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 174.80 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 156.72 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 | 13-APR-16:50 | 119.23 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:20 | 100.83 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.18 | 22-JUL-15:20 | 46.21 | 15-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 20-AUG-15:20 | 54.74 | 25-AUG-21:50 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.57 | 02-SEP-15:20 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 148.55 | 26-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.37 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.26 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.21 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.26 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 300.93 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 57.57 | 26-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 300.93 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 55.85 | 05-FEB-08:10 |
March | 0.00 | 01-MAR-00:10 | 300.93 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 50.69 | 05-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 300.93 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 41.02 | 06-APR-06:10 |
May | 0.00 | 01-MAY-00:10 | 300.93 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 | 22-MAY-13:00 | 35.91 | 07-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 300.93 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 28-JUN-16:00 | 30.26 | 09-JUN-05:20 |
July | 0.00 | 01-JUL-00:10 | 300.93 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 22-JUL-15:00 | 17.16 | 08-JUL-04:00 |
August | 0.00 | 01-AUG-00:10 | 300.93 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 | 20-AUG-15:00 | 22.74 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 300.93 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 | 03-SEP-14:00 | 26.69 | 09-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 300.93 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 | 01-OCT-16:00 | 50.92 | 27-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 300.93 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 52.61 | 27-NOV-07:40 |
December | 0.00 | 01-DEC-00:10 | 300.93 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 60.72 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 300.93 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 | |||||
Maximum of Months | 0.00 | 300.93 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 60.72 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 301.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 52.21 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 301.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 48.79 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 301.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 43.74 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 301.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 13-APR-16:50 | 33.70 | 08-APR-07:10 |
May | 180.00 | 01-MAY-00:10 | 301.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 19-MAY-15:50 | 28.14 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 301.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 28-JUN-16:00 | 22.26 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 301.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.89 | 22-JUL-15:20 | 12.34 | 07-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 301.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 20-AUG-15:20 | 14.44 | 25-AUG-21:50 |
September | 180.00 | 01-SEP-00:10 | 301.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 | 02-SEP-15:20 | 17.49 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 301.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 01-OCT-16:00 | 42.38 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 301.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 44.48 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 301.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 54.50 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 | |||||
Maximum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 54.50 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.09 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 14-FEB-16:20 | 178.58 | 04-FEB-08:20 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 08-MAR-16:20 | 156.73 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 | 13-APR-16:50 | 127.35 | 08-APR-07:10 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:20 | 100.84 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.76 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.19 | 22-JUL-15:20 | 32.18 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 20-AUG-15:20 | 48.94 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.58 | 02-SEP-15:20 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 154.81 | 27-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 163.28 | 28-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.28 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.28 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.08 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 174.80 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 156.72 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 | 13-APR-16:50 | 127.34 | 08-APR-07:10 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:20 | 100.83 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.18 | 22-JUL-15:20 | 53.43 | 08-JUL-07:40 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 20-AUG-15:20 | 60.41 | 11-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.57 | 02-SEP-15:20 | 63.27 | 19-SEP-08:10 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 152.41 | 27-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 160.27 | 28-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.27 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.43 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.27 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1886.18 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 239.47 | 26-JAN-04:00 |
February | 2263.36 | 01-FEB-00:10 | 1886.18 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 229.08 | 04-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1886.18 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 208.87 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1886.18 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 | 13-APR-16:51 | 165.18 | 08-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1886.18 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 | 22-MAY-13:00 | 142.95 | 07-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1886.18 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 28-JUN-16:00 | 117.30 | 09-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1886.18 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.40 | 22-JUL-15:00 | 55.67 | 08-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1886.18 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 | 20-AUG-15:00 | 79.64 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1886.18 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.80 | 03-SEP-14:00 | 96.53 | 09-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1886.18 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.56 | 01-OCT-16:00 | 198.83 | 27-OCT-07:00 |
November | 2263.36 | 01-NOV-00:10 | 1886.18 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 212.33 | 27-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1886.18 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 254.58 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1886.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 | ||||
Maximum of Months | 2263.36 | 1886.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 254.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.51 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 14-FEB-16:20 | 175.22 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.74 | 08-MAR-16:20 | 157.14 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 | 13-APR-16:50 | 119.64 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 | 19-MAY-15:20 | 101.22 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.89 | 28-JUN-16:00 | 80.13 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.88 | 22-JUL-15:20 | 32.53 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.02 | 20-AUG-15:20 | 49.30 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.26 | 02-SEP-15:20 | 63.05 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 | 01-OCT-16:00 | 148.96 | 26-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.79 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.71 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.53 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 94.89 | 195.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.50 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 175.21 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 157.13 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 | 13-APR-16:50 | 119.63 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 | 19-MAY-15:20 | 101.21 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 28-JUN-16:00 | 80.12 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.88 | 22-JUL-15:20 | 46.88 | 15-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.02 | 20-AUG-15:20 | 54.78 | 25-AUG-21:50 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.26 | 02-SEP-15:20 | 63.04 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 | 01-OCT-16:00 | 148.95 | 26-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.78 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 195.70 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.88 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 195.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 301.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 95.94 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 301.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 14-FEB-16:20 | 89.65 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 301.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 | 08-MAR-16:20 | 80.40 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 301.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 | 13-APR-16:50 | 61.21 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 301.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 | 19-MAY-15:20 | 51.79 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 301.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 28-JUN-16:00 | 41.00 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 301.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.48 | 22-JUL-15:20 | 16.65 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 301.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 20-AUG-15:20 | 25.23 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 301.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.79 | 02-SEP-15:20 | 32.26 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 301.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.81 | 01-OCT-16:00 | 76.21 | 26-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 301.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 81.75 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 301.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 100.13 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.65 | |||||
Maximum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 100.13 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 4498.11 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 480.28 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 4498.11 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 454.29 | 05-FEB-08:00 |
March | 26988.77 | 01-MAR-00:10 | 4498.11 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 411.54 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 4498.11 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 | 13-APR-16:51 | 329.10 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 4498.11 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.47 | 22-MAY-13:00 | 277.51 | 07-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 4498.11 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.88 | 28-JUN-16:00 | 237.69 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 4498.11 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.87 | 22-JUL-15:00 | 113.20 | 08-JUL-03:00 |
August | 26988.77 | 01-AUG-00:10 | 4498.11 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.88 | 20-AUG-15:00 | 161.65 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 4498.11 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.96 | 03-SEP-14:00 | 195.77 | 09-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 4498.11 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.97 | 01-OCT-16:00 | 394.91 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 4498.11 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 418.79 | 27-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 4498.11 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 499.76 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.20 | |||||
Maximum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 193.88 | 499.76 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 4498.11 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 486.99 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 4498.11 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 460.49 | 05-FEB-08:00 |
March | 26988.77 | 01-MAR-00:10 | 4498.11 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 416.91 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 4498.11 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.11 | 13-APR-16:51 | 333.09 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 4498.11 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.15 | 22-MAY-13:00 | 280.82 | 07-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 4498.11 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.88 | 28-JUN-16:00 | 237.69 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 4498.11 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.87 | 22-JUL-15:00 | 113.20 | 08-JUL-03:00 |
August | 26988.77 | 01-AUG-00:10 | 4498.11 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.88 | 20-AUG-15:00 | 161.65 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 4498.11 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.96 | 03-SEP-14:00 | 195.77 | 09-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 4498.11 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.97 | 01-OCT-16:00 | 399.78 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 4498.11 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 423.41 | 27-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 4498.11 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 505.04 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.20 | |||||
Maximum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 193.88 | 505.04 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1200.92 | 02-JAN-20:10 | 15028.36 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 449.87 | 21-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1200.92 | 01-FEB-20:10 | 15028.36 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 422.60 | 04-FEB-06:00 |
March | 2401.70 | 01-MAR-00:10 | 1200.92 | 01-MAR-20:10 | 15028.36 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 382.86 | 05-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1200.92 | 03-APR-19:10 | 15028.36 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 24.25 | 13-APR-16:59 | 300.09 | 08-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1200.92 | 01-MAY-19:10 | 15028.36 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 71.57 | 22-MAY-13:00 | 259.20 | 07-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 1200.92 | 01-JUN-19:10 | 15028.36 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 173.52 | 28-JUN-16:00 | 212.80 | 09-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1200.92 | 03-JUL-19:10 | 15028.36 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 166.34 | 22-JUL-15:00 | 101.38 | 08-JUL-03:00 |
August | 2401.70 | 01-AUG-00:10 | 1200.92 | 01-AUG-19:10 | 15028.36 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 129.65 | 20-AUG-15:00 | 144.64 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1200.92 | 01-SEP-19:10 | 15028.36 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 103.77 | 03-SEP-14:00 | 175.20 | 09-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1200.92 | 02-OCT-19:10 | 15028.36 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 58.12 | 01-OCT-16:00 | 365.13 | 26-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1200.92 | 01-NOV-19:10 | 15028.36 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 388.61 | 27-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 1200.92 | 01-DEC-20:10 | 15028.36 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 468.00 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1200.92 | 15028.36 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 101.38 | ||||||
Maximum of Months | 2401.70 | 1200.92 | 15028.36 | 22492.83 | 0.00 | 0.00 | 0.00 | 173.52 | 468.00 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1996.23 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 399.66 | 21-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1996.23 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 373.39 | 04-FEB-06:10 |
March | 2395.44 | 01-MAR-00:10 | 1996.23 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 335.44 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1996.23 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 13-APR-16:51 | 273.61 | 08-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1996.23 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.08 | 22-MAY-13:00 | 241.05 | 07-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1996.23 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.86 | 28-JUN-16:00 | 203.71 | 09-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1996.23 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.83 | 22-JUL-15:00 | 99.25 | 08-JUL-04:00 |
August | 2395.44 | 01-AUG-00:10 | 1996.23 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.92 | 20-AUG-15:00 | 141.69 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1996.23 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.59 | 03-SEP-14:00 | 170.76 | 25-SEP-05:00 |
October | 2395.44 | 01-OCT-23:10 | 1996.23 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 | 01-OCT-16:00 | 322.19 | 27-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 1996.23 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 340.38 | 27-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1996.23 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 417.18 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.25 | ||||
Maximum of Months | 2395.44 | 1996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.86 | 417.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22594.15 | 26-JAN-04:00 | 11501.89 | 2190.14 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21611.86 | 01-FEB-04:00 | 11501.89 | 2190.14 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18223.58 | 30-MAR-06:00 | 8945.92 | 8760.57 | 5069.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17487.94 | 28-APR-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18363.80 | 19-MAY-20:54 | 51119.52 | 87605.74 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20604.00 | 29-JUN-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22856.13 | 21-JUL-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24566.05 | 18-AUG-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26974.81 | 29-SEP-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28053.24 | 06-OCT-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27420.68 | 01-NOV-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25573.40 | 01-DEC-21:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17487.94 | 8945.92 | 2190.14 | 2027.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28053.24 | 51119.52 | 87605.74 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4823.05 | 01-JAN-13:40 | 259.90 | 216.58 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.33 |
February | 5267.39 | 14-FEB-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.11 |
March | 4707.55 | 08-MAR-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.26 |
April | 3893.31 | 13-APR-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 0.00 |
May | 3216.35 | 13-MAY-13:10 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 41.98 | 0.00 |
June | 3860.39 | 29-JUN-14:30 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 | 0.00 |
July | 3980.32 | 22-JUL-13:40 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 122.86 | 0.00 |
August | 4683.45 | 22-AUG-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 70.20 | 0.00 |
September | 5402.47 | 28-SEP-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 52.08 | 0.00 |
October | 5415.76 | 05-OCT-13:10 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 17.13 | 0.00 |
November | 4972.96 | 20-NOV-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.32 |
December | 4838.02 | 31-DEC-13:00 | 389.84 | 324.88 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3216.35 | 259.90 | 216.58 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5415.76 | 389.84 | 324.88 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 | 160.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1515.49 | 03-JAN-21:10 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.92 |
February | 1808.44 | 14-FEB-20:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.64 |
March | 1943.26 | 15-MAR-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.80 |
April | 2367.37 | 13-APR-18:15 | 2106.72 | 2006.45 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
May | 2537.95 | 19-MAY-18:30 | 1053.36 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 | 0.00 |
June | 2836.94 | 23-JUN-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 26.01 | 0.00 |
July | 2974.40 | 21-JUL-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 35.35 | 0.00 |
August | 2825.06 | 15-AUG-18:30 | 1053.36 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 | 0.00 |
September | 2529.62 | 20-SEP-18:15 | 2106.72 | 2006.45 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 0.00 |
October | 2411.72 | 04-OCT-18:12 | 5266.80 | 5016.12 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 |
November | 1943.31 | 02-NOV-19:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 |
December | 1418.65 | 29-DEC-21:10 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1418.65 | 1053.36 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2974.40 | 5266.80 | 5016.12 | 3760.73 | 0.00 | 0.00 | 0.00 | 0.00 | 35.35 | 89.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1093.26 | 05-JAN-21:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.43 |
February | 1163.36 | 15-FEB-21:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.93 |
March | 1363.56 | 16-MAR-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.61 |
April | 2435.68 | 28-APR-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 |
May | 2877.34 | 19-MAY-19:50 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 0.00 |
June | 3276.10 | 23-JUN-19:40 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 47.13 | 0.00 |
July | 3380.48 | 21-JUL-19:50 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 62.38 | 0.00 |
August | 3110.77 | 18-AUG-19:50 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 33.06 | 0.00 |
September | 2768.54 | 01-SEP-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 |
October | 2513.52 | 02-OCT-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 |
November | 1559.23 | 02-NOV-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.86 |
December | 1118.77 | 01-DEC-22:00 | 254.59 | 2121.48 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1093.26 | 222.77 | 2121.48 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3380.48 | 254.59 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 62.38 | 174.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 549.46 | 03-JAN-21:00 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 |
February | 617.54 | 14-FEB-13:40 | 48.96 | 204.00 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 |
March | 635.86 | 08-MAR-21:00 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.27 |
April | 758.41 | 28-APR-19:50 | 342.72 | 1468.77 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 |
May | 1206.82 | 19-MAY-18:30 | 171.36 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 21.55 | 0.00 |
June | 1660.43 | 26-JUN-18:17 | 514.08 | 1958.36 | 688.24 | 0.00 | 0.00 | 0.00 | 0.00 | 45.55 | 0.00 |
July | 1794.76 | 20-JUL-18:30 | 171.36 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 54.20 | 0.00 |
August | 1434.49 | 18-AUG-18:20 | 342.72 | 1305.57 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 38.30 | 0.00 |
September | 1032.16 | 02-SEP-18:03 | 881.28 | 3427.13 | 1223.53 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 0.00 |
October | 794.71 | 01-OCT-13:30 | 48.96 | 163.20 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 | 0.00 |
November | 647.72 | 02-NOV-21:00 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 |
December | 571.69 | 01-DEC-22:00 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 549.46 | 48.96 | 163.20 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1794.76 | 881.28 | 3427.13 | 1223.53 | 0.00 | 0.00 | 0.00 | 0.00 | 54.20 | 97.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37179.08 | 30-JAN-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 219.76 |
February | 37659.05 | 14-FEB-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 176.44 |
March | 37980.47 | 13-MAR-19:55 | 1411.20 | 907.21 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 104.69 |
April | 38609.58 | 28-APR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.84 |
May | 38940.13 | 19-MAY-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.11 | 0.00 |
June | 39412.84 | 27-JUN-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 83.98 | 0.00 |
July | 39474.01 | 21-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 77.86 | 0.00 |
August | 39224.44 | 17-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 51.33 | 0.00 |
September | 38835.29 | 13-SEP-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
October | 38468.94 | 04-OCT-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 49.02 |
November | 37779.24 | 02-NOV-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 140.44 |
December | 37333.42 | 01-DEC-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 184.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37179.08 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39474.01 | 1411.20 | 907.21 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 83.98 | 219.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16908.99 | 01-JAN-13:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.65 |
February | 17544.13 | 14-FEB-13:20 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.86 |
March | 16019.36 | 08-MAR-13:30 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.84 |
April | 14201.67 | 01-APR-13:30 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 |
May | 12349.27 | 13-MAY-13:00 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 90.70 | 0.00 |
June | 13656.74 | 29-JUN-15:10 | 8538.00 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 275.94 | 0.00 |
July | 13557.33 | 22-JUL-13:30 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 266.07 | 0.00 |
August | 15678.82 | 20-AUG-12:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 184.24 | 0.00 |
September | 17450.49 | 28-SEP-13:10 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 107.55 | 0.00 |
October | 18298.18 | 01-OCT-12:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 34.21 | 0.00 |
November | 16756.52 | 20-NOV-13:10 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.00 |
December | 17017.76 | 31-DEC-13:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12349.27 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18298.18 | 8538.00 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 275.94 | 355.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33825.45 | 03-JAN-19:05 | 212907.24 | 87866.59 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1185.13 |
February | 37000.93 | 14-FEB-21:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.88 |
March | 38020.95 | 08-MAR-21:02 | 405537.60 | 146444.32 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.69 |
April | 42688.87 | 13-APR-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.38 |
May | 45228.80 | 19-MAY-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 73.88 | 0.00 |
June | 48965.62 | 27-JUN-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 409.36 | 0.00 |
July | 49605.91 | 21-JUL-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 389.20 | 0.00 |
August | 48087.28 | 17-AUG-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 244.51 | 0.00 |
September | 45884.91 | 13-SEP-20:04 | 202768.80 | 73222.16 | 47506.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.80 |
October | 44056.76 | 04-OCT-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.84 |
November | 38496.08 | 02-NOV-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.08 |
December | 32292.87 | 29-DEC-19:07 | 212907.24 | 87866.59 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 32292.87 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49605.91 | 405537.60 | 146444.32 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 409.36 | 1185.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5113.08 | 26-JAN-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.10 |
February | 5148.70 | 04-FEB-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.32 |
March | 5116.00 | 04-MAR-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 |
April | 5082.68 | 08-APR-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.42 |
May | 5124.72 | 26-MAY-18:01 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
June | 5081.71 | 10-JUN-18:01 | 936.00 | 3830.67 | 969.31 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
July | 4547.46 | 29-JUL-18:02 | 702.00 | 2873.00 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 36.53 | 0.00 |
August | 4752.26 | 23-AUG-18:01 | 1108.80 | 3409.29 | 969.31 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 | 0.00 |
September | 4881.09 | 18-SEP-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 0.00 |
October | 5096.12 | 27-OCT-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.06 |
November | 5085.78 | 03-NOV-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.42 |
December | 5101.06 | 20-DEC-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4547.46 | 324.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5148.70 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 36.53 | 98.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5017.04 | 05-JAN-17:01 | 874.80 | 1206.52 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.07 |
February | 4988.88 | 15-FEB-18:01 | 777.60 | 2566.25 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.43 |
March | 5217.51 | 30-MAR-18:11 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.70 |
April | 5200.25 | 14-APR-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 |
May | 5310.43 | 26-MAY-18:01 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 |
June | 5339.56 | 09-JUN-18:51 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.65 |
July | 4930.82 | 29-JUL-21:51 | 1386.00 | 4069.61 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 |
August | 5082.15 | 30-AUG-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
September | 5199.38 | 30-SEP-21:51 | 1386.00 | 4069.61 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.23 |
October | 5235.78 | 19-OCT-21:41 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.42 |
November | 5053.85 | 02-NOV-18:11 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.28 |
December | 4946.44 | 20-DEC-16:12 | 583.20 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4930.82 | 583.20 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | |
Maximum of Months | 5339.56 | 1800.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 999.52 | 01-JAN-13:40 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 |
February | 1012.58 | 14-FEB-13:00 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 |
March | 870.39 | 08-MAR-13:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 |
April | 680.72 | 01-APR-13:30 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 |
May | 496.28 | 13-MAY-13:10 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 | 0.00 |
June | 511.84 | 29-JUN-14:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 0.00 |
July | 569.16 | 23-JUL-13:30 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 0.00 |
August | 714.18 | 20-AUG-12:50 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 0.00 |
September | 907.45 | 28-SEP-13:20 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 | 0.00 |
October | 1000.59 | 31-OCT-13:00 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.65 |
November | 1000.69 | 20-NOV-12:20 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 |
December | 1010.07 | 31-DEC-13:40 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 496.28 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1012.58 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 28.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1613.69 | 01-JAN-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.68 |
February | 1619.17 | 18-FEB-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 |
March | 1619.49 | 04-MAR-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 |
April | 1600.32 | 08-APR-08:62 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.26 |
May | 1578.77 | 26-MAY-19:31 | 1386.00 | 3010.11 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 |
June | 1598.84 | 09-JUN-21:51 | 1800.00 | 2016.77 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 |
July | 1420.33 | 22-JUL-07:31 | 763.20 | 1348.53 | 1858.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 0.00 |
August | 1458.81 | 30-AUG-21:51 | 1800.00 | 2016.77 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 |
September | 1553.37 | 30-SEP-21:51 | 1386.00 | 2558.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 |
October | 1585.42 | 29-OCT-08:62 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 |
November | 1617.14 | 25-NOV-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.07 |
December | 1582.14 | 31-DEC-19:02 | 702.00 | 1806.06 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1420.33 | 324.00 | 1011.40 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1619.49 | 1800.00 | 3010.11 | 1858.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 32.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4592.76 | 26-JAN-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.20 |
February | 4615.87 | 04-FEB-09:02 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.32 |
March | 4606.26 | 04-MAR-09:02 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.99 |
April | 4570.50 | 06-APR-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.34 |
May | 4532.27 | 06-MAY-08:62 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.95 |
June | 4467.23 | 19-JUN-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.80 |
July | 4190.94 | 06-JUL-08:61 | 360.00 | 2106.87 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 | 0.00 |
August | 4209.91 | 20-AUG-08:62 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 | 0.00 |
September | 4421.13 | 21-SEP-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.61 |
October | 4541.11 | 27-OCT-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.78 |
November | 4624.26 | 28-NOV-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.86 |
December | 4612.97 | 31-DEC-09:02 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4190.94 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4624.26 | 360.00 | 2106.87 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 | 157.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4468.35 | 26-JAN-09:02 | 216.00 | 1263.97 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.60 |
February | 4506.18 | 04-FEB-09:02 | 324.00 | 1608.69 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.98 |
March | 4518.59 | 04-MAR-09:02 | 324.00 | 1608.69 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.11 |
April | 4605.36 | 27-APR-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.69 |
May | 4638.19 | 19-MAY-08:32 | 180.00 | 1053.31 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 |
June | 4729.20 | 10-JUN-08:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.32 |
July | 4563.51 | 22-JUL-07:12 | 572.40 | 1608.69 | 1422.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 |
August | 4495.54 | 02-AUG-08:62 | 216.00 | 1263.97 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
September | 4696.38 | 20-SEP-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.41 |
October | 4514.36 | 06-OCT-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.85 |
November | 4494.34 | 28-NOV-09:02 | 216.00 | 1263.97 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.15 |
December | 4485.25 | 31-DEC-09:02 | 324.00 | 1608.69 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4468.35 | 180.00 | 1053.31 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | |
Maximum of Months | 4729.20 | 1800.00 | 3207.81 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2137.58 | 03-JAN-16:10 | 2514.84 | 1047.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 |
February | 2717.54 | 14-FEB-16:10 | 2514.84 | 1047.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.80 |
March | 2426.24 | 08-MAR-14:10 | 502.97 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 |
April | 2783.72 | 11-APR-18:15 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 |
May | 3156.71 | 19-MAY-18:15 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 | 0.00 |
June | 3616.05 | 16-JUN-18:30 | 1760.39 | 1676.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.51 | 0.00 |
July | 3776.14 | 20-JUL-18:30 | 1760.39 | 1676.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.00 | 0.00 |
August | 3484.90 | 18-AUG-18:15 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.80 | 0.00 |
September | 3242.74 | 13-SEP-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | 0.00 |
October | 3197.63 | 05-OCT-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 0.00 |
November | 2447.75 | 02-NOV-15:10 | 2514.84 | 1047.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.30 |
December | 2049.16 | 30-DEC-14:10 | 754.45 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2049.16 | 502.97 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3776.14 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.00 | 95.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5554.28 | 26-JAN-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 |
February | 5585.07 | 04-FEB-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.67 |
March | 5560.33 | 04-MAR-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.54 |
April | 5552.81 | 08-APR-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.18 |
May | 5628.64 | 26-MAY-18:01 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
June | 5579.20 | 10-JUN-18:01 | 936.00 | 3830.67 | 969.31 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 0.00 |
July | 5006.69 | 29-JUL-18:02 | 702.00 | 2873.00 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 | 0.00 |
August | 5203.41 | 23-AUG-18:01 | 1108.80 | 3409.29 | 969.31 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 | 0.00 |
September | 5378.54 | 18-SEP-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 | 0.00 |
October | 5588.80 | 18-OCT-15:11 | 680.40 | 938.51 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 |
November | 5532.40 | 06-NOV-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.88 |
December | 5540.51 | 31-DEC-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5006.69 | 324.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5628.64 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 | 91.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5451.84 | 05-JAN-17:01 | 874.80 | 1206.52 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.30 |
February | 5445.70 | 15-FEB-18:01 | 777.60 | 2566.25 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 |
March | 5719.51 | 30-MAR-18:11 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 |
April | 5665.93 | 20-APR-20:41 | 1602.00 | 4261.12 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.30 |
May | 5858.49 | 26-MAY-18:01 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 |
June | 5874.73 | 09-JUN-18:51 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.08 |
July | 5395.73 | 29-JUL-21:51 | 1386.00 | 4069.61 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 |
August | 5712.72 | 23-AUG-16:51 | 680.40 | 938.40 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.49 |
September | 5680.57 | 19-SEP-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.87 |
October | 5711.89 | 19-OCT-21:41 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.46 |
November | 5538.86 | 02-NOV-18:11 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.77 |
December | 5237.38 | 31-DEC-16:12 | 324.00 | 947.98 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5237.38 | 324.00 | 938.40 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | |
Maximum of Months | 5874.73 | 1800.00 | 4261.12 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2735.80 | 21-JAN-16:12 | 324.00 | 596.00 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.72 |
February | 2756.90 | 04-FEB-16:12 | 324.00 | 596.00 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 |
March | 2685.96 | 04-MAR-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.73 |
April | 2659.26 | 08-APR-15:12 | 324.00 | 596.00 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 |
May | 2611.00 | 01-MAY-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.19 |
June | 2564.83 | 10-JUN-18:01 | 936.00 | 2408.09 | 949.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 | 0.00 |
July | 2304.06 | 27-JUL-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 | 0.00 |
August | 2410.15 | 28-AUG-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 0.00 |
September | 2540.80 | 26-SEP-18:02 | 831.60 | 1607.40 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 0.00 |
October | 2742.17 | 15-OCT-15:21 | 378.00 | 695.33 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
November | 2756.58 | 28-NOV-09:02 | 216.00 | 794.67 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.00 |
December | 2755.15 | 14-DEC-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2304.06 | 216.00 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2756.90 | 936.00 | 2408.09 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 | 70.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16314.62 | 05-JAN-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.73 |
February | 18569.74 | 14-FEB-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.17 |
March | 19473.81 | 16-MAR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.00 |
April | 22050.70 | 28-APR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.32 |
May | 23048.17 | 19-MAY-21:02 | 161932.61 | 17992.44 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.55 |
June | 24882.10 | 27-JUN-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 64.52 | 0.00 |
July | 25007.89 | 21-JUL-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.78 | 0.00 |
August | 24049.20 | 17-AUG-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 | 0.00 |
September | 22632.72 | 13-SEP-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.68 |
October | 21836.61 | 02-OCT-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.22 |
November | 19133.92 | 02-NOV-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.18 |
December | 17356.50 | 01-DEC-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16314.62 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25007.89 | 161932.61 | 17992.44 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 75.78 | 300.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17853.89 | 05-JAN-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.73 |
February | 19945.56 | 14-FEB-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.18 |
March | 20823.35 | 16-MAR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.01 |
April | 23256.49 | 28-APR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.32 |
May | 24247.10 | 19-MAY-21:02 | 161932.61 | 17992.44 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.55 |
June | 26083.76 | 27-JUN-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 64.52 | 0.00 |
July | 26209.94 | 21-JUL-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.78 | 0.00 |
August | 25234.24 | 17-AUG-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 | 0.00 |
September | 23822.41 | 13-SEP-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.68 |
October | 23022.04 | 02-OCT-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.22 |
November | 20501.66 | 08-NOV-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.65 |
December | 18910.43 | 01-DEC-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17853.89 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26209.94 | 161932.61 | 17992.44 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 75.78 | 300.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27632.62 | 01-JAN-11:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 185.69 |
February | 28618.26 | 14-FEB-11:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 96.13 |
March | 29675.32 | 26-MAR-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 117.76 |
April | 31006.58 | 28-APR-10:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 36.89 |
May | 31072.69 | 20-MAY-10:40 | 800.57 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 |
June | 32125.64 | 29-JUN-10:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 102.22 | 0.00 |
July | 32602.78 | 22-JUL-10:40 | 800.57 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 110.34 | 0.00 |
August | 32440.23 | 20-AUG-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 73.59 | 0.00 |
September | 32187.80 | 03-SEP-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 53.72 | 0.00 |
October | 30954.51 | 01-OCT-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
November | 28408.80 | 01-NOV-10:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 140.19 |
December | 27510.99 | 30-DEC-11:50 | 800.57 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 209.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27510.99 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32602.78 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 110.34 | 209.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3393.76 | 01-JAN-14:00 | 532.32 | 443.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.02 |
February | 6009.72 | 14-FEB-13:40 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.31 |
March | 6436.20 | 08-MAR-13:50 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 |
April | 8117.84 | 13-APR-12:50 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 |
May | 8775.32 | 30-MAY-14:30 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.12 | 0.00 |
June | 10530.22 | 28-JUN-14:10 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.07 | 0.00 |
July | 10474.70 | 20-JUL-14:10 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.39 | 0.00 |
August | 10756.65 | 20-AUG-13:20 | 532.32 | 443.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.23 | 0.00 |
September | 10606.52 | 03-SEP-13:30 | 532.32 | 443.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.92 | 0.00 |
October | 9717.47 | 01-OCT-13:30 | 532.32 | 443.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 | 0.00 |
November | 5811.78 | 02-NOV-14:10 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.07 |
December | 3345.55 | 02-DEC-13:40 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3345.55 | 532.32 | 443.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10756.65 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.07 | 171.98 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.492135E+12 | 296285.70 | 30-JAN-19:10 | 0.620222E+12 | 495135.16 | 18-JAN-19:00 |
February | 0.448366E+12 | 315009.02 | 14-FEB-19:10 | 0.523884E+12 | 445755.79 | 05-FEB-19:10 |
March | 0.503785E+12 | 321534.99 | 15-MAR-19:19 | 0.477909E+12 | 401033.37 | 04-MAR-22:00 |
April | 0.522542E+12 | 381544.62 | 28-APR-18:49 | 0.400512E+12 | 347225.10 | 03-APR-17:19 |
May | 0.577478E+12 | 411432.41 | 19-MAY-19:10 | 0.383186E+12 | 337870.23 | 03-MAY-17:30 |
June | 0.640720E+12 | 449485.55 | 27-JUN-18:10 | 0.355736E+12 | 325496.63 | 02-JUN-17:49 |
July | 0.723540E+12 | 467287.20 | 21-JUL-18:10 | 0.359506E+12 | 316364.46 | 05-JUL-17:49 |
August | 0.703247E+12 | 441122.83 | 17-AUG-19:10 | 0.358155E+12 | 313041.46 | 29-AUG-17:30 |
September | 0.619194E+12 | 415186.29 | 13-SEP-18:19 | 0.351136E+12 | 319861.05 | 29-SEP-17:00 |
October | 0.560190E+12 | 389854.39 | 05-OCT-18:10 | 0.405791E+12 | 395251.89 | 24-OCT-17:00 |
November | 0.488695E+12 | 326088.39 | 02-NOV-18:19 | 0.468035E+12 | 404010.84 | 27-NOV-18:49 |
December | 0.492775E+12 | 297620.41 | 01-DEC-20:19 | 0.619614E+12 | 463833.00 | 21-DEC-19:00 |
Annual Sum or Average | 0.677267E+13 | 0.532369E+13 | ||||
Minimum of Months | 0.448366E+12 | 296285.70 | 0.351136E+12 | 313041.46 | ||
Maximum of Months | 0.723540E+12 | 467287.20 | 0.620222E+12 | 495135.16 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.129696E+12 | 0.321077E+11 | 0.141138E+12 | 0.715096E+11 | 0.953314E+11 | 0.830038E+09 | 0.00 | 0.178185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117116E+12 | 0.273469E+11 | 0.127470E+12 | 0.645894E+11 | 0.866821E+11 | 0.620949E+09 | 0.00 | 0.211952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129400E+12 | 0.278882E+11 | 0.141191E+12 | 0.715122E+11 | 0.971751E+11 | 0.370604E+09 | 0.00 | 0.325461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125475E+12 | 0.245421E+11 | 0.136545E+12 | 0.692026E+11 | 0.976584E+11 | 0.192449E+09 | 0.00 | 0.653530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129561E+12 | 0.232750E+11 | 0.141170E+12 | 0.715109E+11 | 0.103562E+12 | 0.141761E+09 | 0.00 | 0.104538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125286E+12 | 0.214174E+11 | 0.136635E+12 | 0.692051E+11 | 0.106461E+12 | 0.124914E+09 | 0.00 | 0.177968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129759E+12 | 0.227091E+11 | 0.141079E+12 | 0.715085E+11 | 0.113240E+12 | 0.128342E+09 | 0.00 | 0.241372E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129426E+12 | 0.244190E+11 | 0.141202E+12 | 0.715122E+11 | 0.112721E+12 | 0.128352E+09 | 0.00 | 0.220080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125517E+12 | 0.259568E+11 | 0.136555E+12 | 0.692027E+11 | 0.105033E+12 | 0.124372E+09 | 0.00 | 0.153178E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129662E+12 | 0.293029E+11 | 0.141127E+12 | 0.715095E+11 | 0.102759E+12 | 0.232127E+09 | 0.00 | 0.818823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125477E+12 | 0.304961E+11 | 0.136629E+12 | 0.692036E+11 | 0.941951E+11 | 0.426952E+09 | 0.00 | 0.286889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129767E+12 | 0.326982E+11 | 0.141079E+12 | 0.715085E+11 | 0.953429E+11 | 0.855975E+09 | 0.00 | 0.178219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152614E+13 | 0.322159E+12 | 0.166182E+13 | 0.841975E+12 | 0.121016E+13 | 0.417683E+10 | 0.00 | 0.116244E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117116E+12 | 0.214174E+11 | 0.127470E+12 | 0.645894E+11 | 0.866821E+11 | 0.124372E+09 | 0.00 | 0.178185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129767E+12 | 0.326982E+11 | 0.141202E+12 | 0.715122E+11 | 0.113240E+12 | 0.855975E+09 | 0.00 | 0.241372E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.216056E+12 | 0.00 | 0.252248E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.157484E+12 | 0.00 | 0.229196E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.767898E+11 | 0.00 | 0.249096E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.220903E+11 | 0.00 | 0.231466E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.437449E+10 | 0.00 | 0.226833E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.235572E+09 | 0.00 | 0.208386E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 8510612.44 | 0.00 | 0.207677E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 11049708.60 | 0.00 | 0.206106E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 57433040.38 | 0.00 | 0.204108E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.330871E+11 | 0.00 | 0.220801E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.953264E+11 | 0.00 | 0.225618E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.223150E+12 | 0.00 | 0.244644E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.828670E+12 | 0.00 | 0.270618E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 8510612.44 | 0.00 | 0.204108E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.223150E+12 | 0.00 | 0.252248E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 121238.68 | 02-JAN-20:10 | 20502.98 | 01-JAN-00:10 | 89286.95 | 02-JAN-07:10 | 50420.89 | 02-JAN-07:19 | 42475.78 | 01-JAN-13:30 | 765.92 | 21-JAN-06:00 | 0.00 | 01-JAN-00:10 |
February | 121238.68 | 01-FEB-20:10 | 20502.98 | 01-FEB-00:10 | 89286.95 | 01-FEB-07:10 | 50420.89 | 01-FEB-07:19 | 44599.03 | 14-FEB-22:10 | 704.33 | 04-FEB-05:00 | 0.00 | 01-FEB-00:10 |
March | 121238.68 | 01-MAR-20:10 | 20502.98 | 01-MAR-00:10 | 89286.95 | 01-MAR-07:10 | 50420.89 | 01-MAR-07:19 | 45485.00 | 13-MAR-20:10 | 538.02 | 05-MAR-06:30 | 0.00 | 01-MAR-00:10 |
April | 121238.68 | 03-APR-19:10 | 20502.98 | 01-APR-00:10 | 89286.95 | 03-APR-06:10 | 50420.89 | 03-APR-06:19 | 49963.98 | 28-APR-20:10 | 339.08 | 08-APR-05:49 | 0.00 | 01-APR-00:10 |
May | 121238.68 | 01-MAY-19:10 | 20502.98 | 01-MAY-00:10 | 89286.95 | 01-MAY-06:10 | 50420.89 | 01-MAY-06:19 | 52422.73 | 19-MAY-20:10 | 231.90 | 07-MAY-04:00 | 0.00 | 01-MAY-00:10 |
June | 121238.68 | 01-JUN-19:10 | 20502.98 | 01-JUN-00:10 | 89286.95 | 01-JUN-06:10 | 50420.89 | 01-JUN-06:19 | 56535.23 | 23-JUN-18:19 | 113.16 | 09-JUN-03:00 | 0.00 | 01-JUN-00:10 |
July | 121238.68 | 03-JUL-19:10 | 20502.98 | 01-JUL-00:10 | 89286.95 | 03-JUL-06:10 | 50420.89 | 03-JUL-06:19 | 58755.53 | 21-JUL-18:19 | 50.14 | 27-JUL-21:00 | 0.00 | 01-JUL-00:10 |
August | 121238.68 | 01-AUG-19:10 | 20502.98 | 01-AUG-00:10 | 89286.95 | 01-AUG-06:10 | 50420.89 | 01-AUG-06:19 | 55293.76 | 17-AUG-20:10 | 53.62 | 28-AUG-08:09 | 0.00 | 01-AUG-00:10 |
September | 121238.68 | 01-SEP-19:10 | 20502.98 | 01-SEP-00:10 | 89286.95 | 01-SEP-06:10 | 50420.89 | 01-SEP-06:19 | 52202.03 | 01-SEP-20:10 | 98.06 | 08-SEP-08:09 | 0.00 | 01-SEP-00:10 |
October | 121238.68 | 02-OCT-19:10 | 20502.98 | 01-OCT-00:10 | 89286.95 | 02-OCT-06:10 | 50420.89 | 02-OCT-06:19 | 50492.56 | 02-OCT-20:10 | 543.52 | 26-OCT-03:00 | 0.00 | 01-OCT-00:10 |
November | 121238.68 | 01-NOV-19:10 | 20502.98 | 01-NOV-00:10 | 89286.95 | 01-NOV-06:10 | 50420.89 | 01-NOV-06:19 | 45554.77 | 02-NOV-20:10 | 583.74 | 27-NOV-05:00 | 0.00 | 01-NOV-00:10 |
December | 121238.68 | 01-DEC-20:10 | 20502.98 | 01-DEC-00:10 | 89286.95 | 01-DEC-07:10 | 50420.89 | 01-DEC-07:19 | 42613.32 | 30-DEC-13:30 | 791.25 | 15-DEC-04:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 121238.68 | 20502.98 | 89286.95 | 50420.89 | 42475.78 | 50.14 | 0.00 | |||||||
Maximum of Months | 121238.68 | 20502.98 | 89286.95 | 50420.89 | 58755.53 | 791.25 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 41306.62 | 03-JAN-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65743.34 | 14-FEB-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68038.84 | 08-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 108947.36 | 13-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 136754.73 | 19-MAY-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 192814.50 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 193003.97 | 21-JUL-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 173589.50 | 20-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 148288.90 | 02-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 132889.22 | 06-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 47317.11 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34986.85 | 30-DEC-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 34986.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 193003.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 296285.70 | 30-JAN-19:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 38344.40 | 106.38 | 0.00 | 21144.01 | 0.00 |
February | 315009.02 | 14-FEB-19:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 42889.96 | 54.65 | 0.00 | 35737.61 | 0.00 |
March | 321534.99 | 15-MAR-19:19 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 43916.51 | 54.89 | 0.00 | 35741.27 | 0.00 |
April | 381544.62 | 28-APR-18:49 | 107831.13 | 77688.87 | 20502.98 | 29030.08 | 48110.01 | 47.91 | 0.00 | 97016.55 | 0.00 |
May | 411432.41 | 19-MAY-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 51581.20 | 47.91 | 0.00 | 118314.02 | 0.00 |
June | 449485.55 | 27-JUN-18:10 | 107831.13 | 77688.87 | 0.00 | 29010.56 | 56222.27 | 47.91 | 0.00 | 177364.27 | 0.00 |
July | 467287.20 | 21-JUL-18:10 | 107831.13 | 77688.87 | 0.00 | 29010.56 | 58383.90 | 47.91 | 0.00 | 193003.97 | 0.00 |
August | 441122.83 | 17-AUG-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 54679.19 | 47.91 | 0.00 | 144563.32 | 0.00 |
September | 415186.29 | 13-SEP-18:19 | 107831.13 | 77688.87 | 20502.98 | 29030.08 | 51348.23 | 47.91 | 0.00 | 127055.81 | 0.00 |
October | 389854.39 | 05-OCT-18:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 48918.83 | 47.91 | 0.00 | 104172.38 | 0.00 |
November | 326088.39 | 02-NOV-18:19 | 107831.13 | 77688.87 | 20502.98 | 29030.08 | 43710.72 | 51.57 | 0.00 | 45607.19 | 0.00 |
December | 297620.41 | 01-DEC-20:19 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 40074.49 | 47.91 | 0.00 | 16019.03 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 296285.70 | 107831.13 | 77688.87 | 0.00 | 11860.16 | 38344.40 | 47.91 | 0.00 | 16019.03 | 0.00 | |
Maximum of Months | 467287.20 | 121238.68 | 86555.31 | 20502.98 | 29030.08 | 58383.90 | 106.38 | 0.00 | 193003.97 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 229126.35 | 21-JAN-06:00 | 0.00 | 256050.06 | 31-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 213478.57 | 04-FEB-05:00 | 0.00 | 257083.15 | 02-FEB-21:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 157261.26 | 05-MAR-06:30 | 0.00 | 254771.39 | 03-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 92221.01 | 08-APR-05:49 | 0.00 | 245807.57 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 61298.30 | 07-MAY-04:00 | 0.00 | 235419.71 | 01-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 21315.00 | 09-JUN-03:00 | 0.00 | 222949.13 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 666.44 | 27-JUL-21:00 | 0.00 | 212818.42 | 03-JUL-20:30 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 1664.34 | 28-AUG-08:09 | 0.00 | 210941.35 | 31-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 15050.11 | 08-SEP-08:09 | 0.00 | 218131.21 | 28-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 157215.87 | 26-OCT-03:00 | 0.00 | 229183.45 | 30-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 166954.87 | 27-NOV-05:00 | 0.00 | 241773.01 | 29-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 231956.11 | 15-DEC-04:00 | 0.00 | 251281.18 | 28-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 666.44 | 0.00 | 210941.35 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 231956.11 | 0.00 | 257083.15 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.01 | 0.17 | 22.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.87 | 0.33 | 21.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.73 | 2.00 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.79 | 6.33 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.76 | 6.83 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.69 | 2.00 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 18.17 | 21.76 | 18.17 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 22.01 | 6.83 | 22.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.96 | 3.50 | 21.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 22.01 | 6.67 | 22.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 22.07 | 8.83 | 22.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 22.31 | 12.50 | 22.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 22.35 | 10.17 | 22.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 22.14 | 7.33 | 22.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.94 | 3.50 | 21.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 52.83 | 22.16 | 52.83 | 22.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 22.35 | 12.50 | 22.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.80 | 1.00 | 21.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.90 | 4.33 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 22.16 | 7.50 | 22.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 22.34 | 11.00 | 22.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 22.19 | 11.83 | 22.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.95 | 6.83 | 21.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.92 | 1.00 | 21.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 43.50 | 22.14 | 43.50 | 22.14 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 22.34 | 11.83 | 22.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.00 | 0.17 | 22.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.88 | 0.33 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.73 | 1.33 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.74 | 5.67 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.72 | 4.83 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.67 | 21.74 | 12.67 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.00 | 5.67 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
February | 672.00 | 22.09 | 10.67 | 22.08 | 10.67 | 22.06 |
March | 743.83 | 22.74 | 0.00 | 22.74 | 0.00 | 22.74 |
April | 715.33 | 23.66 | 0.00 | 23.66 | 0.00 | 23.66 |
May | 558.50 | 23.93 | 28.17 | 23.93 | 0.00 | 23.93 |
June | 273.67 | 24.00 | 45.83 | 24.00 | 6.17 | 24.00 |
July | 73.67 | 24.00 | 354.50 | 24.00 | 60.17 | 24.00 |
August | 34.67 | 24.00 | 344.83 | 24.00 | 34.67 | 24.00 |
September | 4.33 | 24.00 | 207.00 | 24.00 | 4.33 | 24.00 |
October | 307.50 | 23.98 | 50.00 | 23.98 | 0.00 | 23.98 |
November | 510.67 | 23.96 | 0.00 | 23.96 | 0.00 | 23.96 |
December | 739.83 | 23.35 | 0.00 | 23.35 | 0.00 | 23.35 |
Annual Sum or Average | 5378.00 | 23.24 | 1041.00 | 23.36 | 116.00 | 23.37 |
Minimum of Months | 4.33 | 22.09 | 0.00 | 22.08 | 0.00 | 22.06 |
Maximum of Months | 744.00 | 24.00 | 354.50 | 24.00 | 60.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 595.00 | 21.43 | 358.17 | 21.54 | 269.83 | 21.42 |
February | 511.33 | 21.52 | 253.83 | 21.69 | 166.83 | 21.57 |
March | 582.00 | 21.69 | 166.67 | 21.85 | 88.83 | 21.76 |
April | 487.17 | 22.05 | 79.67 | 22.15 | 32.67 | 22.09 |
May | 460.17 | 22.18 | 108.67 | 22.49 | 8.17 | 22.47 |
June | 289.50 | 22.45 | 313.17 | 23.25 | 0.50 | 23.24 |
July | 199.33 | 23.04 | 568.17 | 23.64 | 82.17 | 23.60 |
August | 185.17 | 22.83 | 531.17 | 23.61 | 40.17 | 23.57 |
September | 270.17 | 22.45 | 383.83 | 23.32 | 12.33 | 23.30 |
October | 415.83 | 22.00 | 258.67 | 22.61 | 35.50 | 22.53 |
November | 528.83 | 21.73 | 201.33 | 22.02 | 82.50 | 21.91 |
December | 576.67 | 21.43 | 373.00 | 21.54 | 283.67 | 21.42 |
Annual Sum or Average | 5101.17 | 21.90 | 3596.33 | 22.41 | 1103.17 | 22.28 |
Minimum of Months | 185.17 | 21.43 | 79.67 | 21.54 | 0.50 | 21.42 |
Maximum of Months | 595.00 | 23.04 | 568.17 | 23.64 | 283.67 | 23.60 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.50 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
February | 652.33 | 22.71 | 0.00 | 22.71 | 0.00 | 22.71 |
March | 689.50 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
April | 593.33 | 23.32 | 0.00 | 23.32 | 0.00 | 23.32 |
May | 400.00 | 23.38 | 48.00 | 23.45 | 0.00 | 23.45 |
June | 121.50 | 23.49 | 247.83 | 23.81 | 6.33 | 23.81 |
July | 102.83 | 23.93 | 711.50 | 23.96 | 102.83 | 23.96 |
August | 54.17 | 23.91 | 710.50 | 23.95 | 54.17 | 23.95 |
September | 60.33 | 23.59 | 409.50 | 23.89 | 20.17 | 23.89 |
October | 404.83 | 23.21 | 101.50 | 23.36 | 0.00 | 23.36 |
November | 654.67 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
December | 744.00 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
Annual Sum or Average | 5215.00 | 22.99 | 2228.83 | 23.28 | 183.50 | 23.29 |
Minimum of Months | 54.17 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
Maximum of Months | 744.00 | 23.93 | 711.50 | 23.96 | 102.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
February | 672.00 | 21.98 | 3.67 | 21.97 | 3.67 | 21.97 |
March | 744.00 | 22.58 | 0.00 | 22.58 | 0.00 | 22.58 |
April | 707.50 | 23.26 | 0.00 | 23.26 | 0.00 | 23.26 |
May | 510.67 | 23.54 | 17.67 | 23.55 | 0.00 | 23.55 |
June | 176.17 | 23.75 | 126.83 | 23.85 | 0.00 | 23.85 |
July | 12.50 | 23.94 | 621.17 | 23.98 | 12.50 | 23.98 |
August | 13.00 | 23.77 | 551.17 | 23.98 | 12.83 | 23.97 |
September | 115.83 | 23.64 | 179.83 | 23.83 | 0.00 | 23.83 |
October | 560.33 | 23.15 | 25.67 | 23.19 | 0.00 | 23.19 |
November | 715.83 | 22.63 | 0.00 | 22.63 | 0.00 | 22.63 |
December | 744.00 | 21.83 | 0.50 | 21.83 | 0.50 | 21.83 |
Annual Sum or Average | 5715.83 | 22.61 | 1526.50 | 22.90 | 29.50 | 22.90 |
Minimum of Months | 12.50 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
Maximum of Months | 744.00 | 23.94 | 621.17 | 23.98 | 12.83 | 23.98 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.04 | 197.33 | 21.03 | 197.33 | 21.03 |
February | 672.00 | 21.12 | 104.50 | 21.11 | 104.50 | 21.09 |
March | 744.00 | 21.40 | 12.33 | 21.39 | 12.33 | 21.38 |
April | 720.00 | 22.24 | 0.00 | 22.24 | 0.00 | 22.24 |
May | 715.50 | 22.90 | 0.00 | 22.90 | 0.00 | 22.90 |
June | 390.17 | 23.29 | 65.50 | 23.39 | 0.00 | 23.39 |
July | 67.83 | 23.43 | 479.17 | 23.88 | 18.67 | 23.87 |
August | 139.33 | 23.27 | 345.33 | 23.73 | 14.50 | 23.71 |
September | 457.17 | 23.14 | 43.17 | 23.20 | 0.00 | 23.20 |
October | 709.50 | 22.27 | 4.00 | 22.28 | 0.00 | 22.28 |
November | 720.00 | 21.35 | 13.83 | 21.35 | 13.83 | 21.34 |
December | 744.00 | 21.03 | 280.83 | 21.02 | 280.83 | 21.02 |
Annual Sum or Average | 6823.50 | 21.91 | 1546.00 | 22.07 | 642.00 | 22.00 |
Minimum of Months | 67.83 | 21.03 | 0.00 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 23.43 | 479.17 | 23.88 | 280.83 | 23.87 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 141.00 | 24.00 | 736.50 | 24.00 | 141.00 | 24.00 |
February | 134.50 | 24.00 | 666.17 | 24.00 | 134.50 | 24.00 |
March | 168.50 | 24.00 | 743.67 | 24.00 | 168.50 | 24.00 |
April | 192.17 | 24.00 | 720.00 | 24.00 | 192.17 | 24.00 |
May | 307.67 | 24.00 | 744.00 | 24.00 | 307.67 | 24.00 |
June | 481.17 | 24.00 | 720.00 | 24.00 | 481.17 | 24.00 |
July | 630.67 | 24.00 | 744.00 | 24.00 | 630.67 | 24.00 |
August | 613.50 | 24.00 | 744.00 | 24.00 | 613.50 | 24.00 |
September | 527.00 | 24.00 | 720.00 | 24.00 | 527.00 | 24.00 |
October | 282.83 | 24.00 | 744.00 | 24.00 | 282.83 | 24.00 |
November | 160.67 | 24.00 | 718.50 | 24.00 | 160.67 | 24.00 |
December | 137.00 | 24.00 | 728.83 | 24.00 | 137.00 | 24.00 |
Annual Sum or Average | 3776.67 | 24.00 | 8729.67 | 24.00 | 3776.67 | 24.00 |
Minimum of Months | 134.50 | 24.00 | 666.17 | 24.00 | 134.50 | 24.00 |
Maximum of Months | 630.67 | 24.00 | 744.00 | 24.00 | 630.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 589.83 | 21.33 | 187.67 | 21.67 | 76.50 | 21.61 |
February | 478.67 | 21.47 | 151.33 | 21.92 | 32.17 | 21.88 |
March | 476.83 | 22.15 | 122.33 | 22.50 | 4.83 | 22.49 |
April | 340.00 | 22.99 | 164.50 | 23.32 | 0.00 | 23.32 |
May | 187.83 | 23.55 | 350.83 | 23.84 | 8.33 | 23.85 |
June | 40.33 | 23.88 | 548.50 | 23.99 | 17.50 | 23.99 |
July | 150.33 | 24.00 | 742.17 | 24.00 | 150.33 | 24.00 |
August | 123.17 | 24.00 | 740.67 | 24.00 | 123.17 | 24.00 |
September | 71.50 | 24.00 | 637.50 | 24.00 | 71.33 | 24.00 |
October | 218.33 | 22.35 | 346.83 | 23.34 | 6.50 | 23.33 |
November | 438.83 | 22.01 | 154.67 | 22.51 | 2.83 | 22.51 |
December | 584.67 | 21.34 | 202.50 | 21.69 | 86.67 | 21.62 |
Annual Sum or Average | 3700.33 | 22.14 | 4349.50 | 23.07 | 580.17 | 23.06 |
Minimum of Months | 40.33 | 21.33 | 122.33 | 21.67 | 0.00 | 21.61 |
Maximum of Months | 589.83 | 24.00 | 742.17 | 24.00 | 150.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 652.17 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
February | 535.67 | 23.04 | 0.00 | 23.04 | 0.00 | 23.04 |
March | 509.67 | 23.19 | 2.83 | 23.20 | 0.00 | 23.20 |
April | 390.00 | 23.46 | 3.17 | 23.47 | 0.00 | 23.47 |
May | 200.50 | 23.48 | 175.17 | 23.70 | 4.17 | 23.70 |
June | 31.83 | 23.68 | 444.33 | 23.95 | 15.83 | 23.95 |
July | 169.00 | 23.99 | 739.00 | 23.99 | 169.00 | 23.99 |
August | 112.00 | 23.99 | 744.00 | 23.98 | 112.00 | 23.98 |
September | 55.33 | 23.91 | 616.50 | 23.96 | 53.17 | 23.96 |
October | 178.33 | 23.25 | 220.33 | 23.65 | 0.00 | 23.65 |
November | 412.50 | 23.32 | 25.17 | 23.36 | 0.00 | 23.36 |
December | 672.00 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
Annual Sum or Average | 3919.00 | 23.25 | 2970.50 | 23.56 | 354.17 | 23.58 |
Minimum of Months | 31.83 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
Maximum of Months | 672.00 | 23.99 | 744.00 | 23.99 | 169.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 698.67 | 21.41 | 246.50 | 21.30 | 246.50 | 21.23 |
February | 620.33 | 21.47 | 129.50 | 21.42 | 121.17 | 21.36 |
March | 685.83 | 21.54 | 50.83 | 21.53 | 43.67 | 21.51 |
April | 647.33 | 21.57 | 15.17 | 21.58 | 10.83 | 21.57 |
May | 654.17 | 21.56 | 18.67 | 21.60 | 2.33 | 21.60 |
June | 577.33 | 21.44 | 54.00 | 21.60 | 0.00 | 21.60 |
July | 549.67 | 21.32 | 96.33 | 21.62 | 1.00 | 21.62 |
August | 546.67 | 21.30 | 103.17 | 21.62 | 0.50 | 21.62 |
September | 544.33 | 21.32 | 78.67 | 21.57 | 0.00 | 21.57 |
October | 630.33 | 21.45 | 64.00 | 21.54 | 23.83 | 21.52 |
November | 654.33 | 21.51 | 64.00 | 21.48 | 60.67 | 21.45 |
December | 701.50 | 21.41 | 263.67 | 21.30 | 263.67 | 21.23 |
Annual Sum or Average | 7510.50 | 21.44 | 1184.50 | 21.50 | 774.17 | 21.46 |
Minimum of Months | 544.33 | 21.30 | 15.17 | 21.30 | 0.00 | 21.23 |
Maximum of Months | 701.50 | 21.57 | 263.67 | 21.62 | 263.67 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.17 | 21.22 | 367.17 | 21.12 | 367.17 | 21.06 |
February | 651.33 | 21.34 | 211.83 | 21.29 | 204.33 | 21.22 |
March | 693.50 | 21.75 | 97.17 | 22.00 | 74.33 | 22.08 |
April | 603.33 | 22.11 | 110.33 | 22.87 | 39.67 | 23.14 |
May | 578.33 | 21.94 | 104.33 | 22.56 | 18.33 | 22.71 |
June | 490.83 | 21.65 | 126.50 | 22.32 | 9.67 | 22.41 |
July | 462.33 | 21.64 | 193.83 | 22.46 | 36.50 | 22.62 |
August | 452.67 | 21.59 | 193.17 | 22.49 | 22.67 | 22.60 |
September | 458.17 | 21.67 | 172.17 | 22.63 | 5.50 | 22.66 |
October | 600.17 | 21.85 | 152.67 | 22.54 | 61.00 | 22.65 |
November | 712.50 | 21.47 | 134.83 | 21.42 | 132.83 | 21.38 |
December | 744.00 | 21.16 | 432.50 | 21.05 | 432.50 | 21.00 |
Annual Sum or Average | 7190.33 | 21.59 | 2296.50 | 21.94 | 1404.50 | 21.91 |
Minimum of Months | 452.67 | 21.16 | 97.17 | 21.05 | 5.50 | 21.00 |
Maximum of Months | 744.00 | 22.11 | 432.50 | 22.87 | 432.50 | 23.14 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.25 | 144.00 | 21.22 | 144.00 | 21.20 |
February | 672.00 | 21.38 | 75.50 | 21.35 | 75.50 | 21.32 |
March | 744.00 | 21.72 | 6.83 | 21.72 | 6.83 | 21.71 |
April | 684.83 | 22.04 | 0.50 | 22.04 | 0.00 | 22.04 |
May | 686.17 | 22.05 | 14.83 | 22.12 | 0.00 | 22.12 |
June | 650.00 | 21.97 | 37.00 | 22.15 | 0.00 | 22.15 |
July | 670.50 | 22.11 | 86.17 | 22.43 | 43.00 | 22.56 |
August | 661.67 | 22.08 | 80.00 | 22.39 | 25.33 | 22.47 |
September | 612.67 | 22.06 | 64.50 | 22.34 | 1.83 | 22.35 |
October | 706.67 | 21.94 | 16.33 | 22.02 | 0.67 | 22.02 |
November | 720.00 | 21.42 | 24.17 | 21.41 | 24.17 | 21.40 |
December | 744.00 | 21.15 | 292.00 | 21.12 | 292.00 | 21.10 |
Annual Sum or Average | 8296.50 | 21.75 | 841.83 | 21.82 | 613.33 | 21.80 |
Minimum of Months | 612.67 | 21.15 | 0.50 | 21.12 | 0.00 | 21.10 |
Maximum of Months | 744.00 | 22.11 | 292.00 | 22.43 | 292.00 | 22.56 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.57 | 238.67 | 21.44 | 238.67 | 21.35 |
February | 646.17 | 21.59 | 128.17 | 21.50 | 128.17 | 21.44 |
March | 680.67 | 21.60 | 51.83 | 21.57 | 51.67 | 21.54 |
April | 620.00 | 21.56 | 15.67 | 21.55 | 15.00 | 21.54 |
May | 627.00 | 21.53 | 8.33 | 21.54 | 2.67 | 21.54 |
June | 531.67 | 21.29 | 54.17 | 21.48 | 0.00 | 21.48 |
July | 513.67 | 21.16 | 169.67 | 21.70 | 0.50 | 21.70 |
August | 518.50 | 21.17 | 157.50 | 21.68 | 0.00 | 21.68 |
September | 538.33 | 21.30 | 99.67 | 21.62 | 0.00 | 21.62 |
October | 610.83 | 21.42 | 52.83 | 21.49 | 24.67 | 21.47 |
November | 695.17 | 21.65 | 66.00 | 21.60 | 66.00 | 21.56 |
December | 743.83 | 21.59 | 257.17 | 21.44 | 257.17 | 21.36 |
Annual Sum or Average | 7469.83 | 21.47 | 1299.67 | 21.54 | 784.50 | 21.50 |
Minimum of Months | 513.67 | 21.16 | 8.33 | 21.44 | 0.00 | 21.35 |
Maximum of Months | 744.00 | 21.65 | 257.17 | 21.70 | 257.17 | 21.70 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.30 | 330.33 | 21.19 | 330.33 | 21.13 |
February | 672.00 | 21.50 | 187.33 | 21.40 | 187.33 | 21.33 |
March | 731.33 | 21.88 | 63.83 | 21.82 | 63.83 | 21.76 |
April | 587.67 | 21.88 | 80.83 | 22.25 | 19.17 | 22.22 |
May | 541.50 | 21.85 | 96.67 | 22.42 | 16.50 | 22.53 |
June | 472.00 | 21.99 | 157.17 | 22.88 | 44.33 | 23.26 |
July | 481.00 | 22.16 | 278.83 | 23.09 | 71.33 | 23.47 |
August | 456.17 | 22.05 | 256.67 | 23.09 | 56.50 | 23.43 |
September | 413.17 | 21.69 | 161.83 | 22.77 | 21.00 | 22.93 |
October | 625.67 | 21.89 | 77.00 | 22.07 | 40.83 | 22.05 |
November | 719.50 | 21.58 | 116.50 | 21.51 | 116.50 | 21.46 |
December | 744.00 | 21.17 | 398.83 | 21.10 | 398.83 | 21.07 |
Annual Sum or Average | 7188.00 | 21.71 | 2205.83 | 22.01 | 1366.50 | 22.02 |
Minimum of Months | 413.17 | 21.17 | 63.83 | 21.10 | 16.50 | 21.07 |
Maximum of Months | 744.00 | 22.16 | 398.83 | 23.09 | 398.83 | 23.47 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 579.33 | 23.75 | 625.00 | 23.76 | 579.33 | 23.75 |
February | 503.50 | 23.88 | 538.00 | 23.89 | 503.50 | 23.88 |
March | 385.00 | 23.98 | 492.00 | 23.98 | 385.00 | 23.98 |
April | 129.50 | 24.00 | 252.17 | 24.00 | 129.50 | 24.00 |
May | 90.17 | 24.00 | 273.67 | 24.00 | 90.17 | 24.00 |
June | 43.50 | 24.00 | 301.17 | 24.00 | 43.50 | 24.00 |
July | 70.17 | 24.00 | 678.67 | 24.00 | 70.17 | 24.00 |
August | 58.83 | 24.00 | 607.17 | 24.00 | 58.83 | 24.00 |
September | 68.83 | 24.00 | 385.00 | 24.00 | 68.83 | 24.00 |
October | 176.67 | 23.95 | 359.17 | 23.96 | 176.67 | 23.96 |
November | 343.00 | 23.96 | 431.00 | 23.97 | 343.00 | 23.97 |
December | 610.00 | 23.82 | 664.83 | 23.83 | 610.00 | 23.82 |
Annual Sum or Average | 3058.50 | 23.89 | 5607.83 | 23.92 | 3058.50 | 23.91 |
Minimum of Months | 43.50 | 23.75 | 252.17 | 23.76 | 43.50 | 23.75 |
Maximum of Months | 610.00 | 24.00 | 678.67 | 24.00 | 610.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 703.33 | 21.23 | 426.50 | 21.10 | 426.50 | 21.03 |
February | 622.67 | 21.33 | 321.50 | 21.23 | 308.67 | 21.15 |
March | 682.33 | 21.42 | 247.67 | 21.34 | 233.67 | 21.27 |
April | 628.83 | 21.47 | 124.83 | 21.45 | 109.33 | 21.40 |
May | 626.17 | 21.45 | 65.50 | 21.55 | 23.17 | 21.54 |
June | 536.33 | 21.35 | 97.50 | 21.65 | 0.00 | 21.65 |
July | 517.17 | 21.28 | 153.33 | 21.74 | 2.17 | 21.74 |
August | 521.00 | 21.27 | 155.83 | 21.73 | 1.67 | 21.73 |
September | 527.50 | 21.28 | 115.33 | 21.64 | 0.33 | 21.64 |
October | 620.50 | 21.35 | 151.67 | 21.43 | 98.00 | 21.37 |
November | 659.67 | 21.39 | 246.33 | 21.30 | 241.00 | 21.24 |
December | 710.33 | 21.24 | 443.83 | 21.09 | 443.83 | 21.03 |
Annual Sum or Average | 7355.83 | 21.34 | 2549.83 | 21.39 | 1888.33 | 21.32 |
Minimum of Months | 517.17 | 21.23 | 65.50 | 21.09 | 0.00 | 21.03 |
Maximum of Months | 710.33 | 21.47 | 443.83 | 21.74 | 443.83 | 21.74 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.17 | 20.98 | 587.50 | 20.89 | 587.50 | 20.85 |
February | 654.50 | 21.15 | 410.17 | 21.07 | 403.33 | 21.00 |
March | 697.33 | 21.66 | 286.83 | 21.74 | 266.50 | 21.71 |
April | 599.83 | 22.18 | 188.83 | 22.81 | 123.33 | 22.97 |
May | 556.67 | 21.90 | 136.83 | 22.56 | 36.67 | 22.70 |
June | 459.83 | 21.63 | 163.67 | 22.38 | 11.50 | 22.50 |
July | 447.33 | 21.70 | 250.67 | 22.55 | 39.17 | 22.71 |
August | 445.33 | 21.70 | 236.00 | 22.60 | 31.33 | 22.75 |
September | 438.17 | 21.60 | 192.83 | 22.64 | 7.67 | 22.68 |
October | 600.33 | 21.83 | 234.17 | 22.41 | 141.67 | 22.44 |
November | 714.33 | 21.28 | 352.67 | 21.17 | 350.67 | 21.11 |
December | 744.00 | 20.89 | 623.83 | 20.81 | 623.83 | 20.77 |
Annual Sum or Average | 7100.83 | 21.50 | 3664.00 | 21.77 | 2623.17 | 21.69 |
Minimum of Months | 438.17 | 20.89 | 136.83 | 20.81 | 7.67 | 20.77 |
Maximum of Months | 744.00 | 22.18 | 623.83 | 22.81 | 623.83 | 22.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 639.00 | 21.33 | 328.17 | 21.34 | 276.67 | 21.27 |
February | 561.67 | 21.33 | 227.17 | 21.36 | 185.00 | 21.30 |
March | 652.17 | 21.45 | 142.50 | 21.45 | 117.17 | 21.41 |
April | 619.00 | 21.47 | 64.83 | 21.44 | 64.83 | 21.41 |
May | 650.67 | 21.52 | 17.17 | 21.52 | 15.67 | 21.51 |
June | 592.67 | 21.45 | 26.17 | 21.53 | 0.00 | 21.53 |
July | 565.00 | 21.32 | 115.33 | 21.66 | 3.33 | 21.67 |
August | 558.50 | 21.30 | 128.50 | 21.68 | 2.33 | 21.68 |
September | 559.00 | 21.35 | 121.50 | 21.70 | 0.17 | 21.70 |
October | 603.83 | 21.37 | 153.17 | 21.61 | 52.83 | 21.57 |
November | 604.83 | 21.41 | 169.83 | 21.49 | 117.67 | 21.43 |
December | 621.33 | 21.26 | 323.83 | 21.25 | 293.50 | 21.20 |
Annual Sum or Average | 7227.67 | 21.38 | 1818.17 | 21.49 | 1129.17 | 21.44 |
Minimum of Months | 558.50 | 21.26 | 17.17 | 21.25 | 0.00 | 21.20 |
Maximum of Months | 652.17 | 21.52 | 328.17 | 21.70 | 293.50 | 21.70 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 715.67 | 22.80 | 0.00 | 22.80 | 0.00 | 22.80 |
February | 570.33 | 22.92 | 0.00 | 22.92 | 0.00 | 22.92 |
March | 414.67 | 23.15 | 20.33 | 23.18 | 0.00 | 23.18 |
April | 165.17 | 23.38 | 82.00 | 23.58 | 0.00 | 23.58 |
May | 55.50 | 23.40 | 403.83 | 23.89 | 9.50 | 23.90 |
June | 31.67 | 23.99 | 667.17 | 23.98 | 31.67 | 23.98 |
July | 326.33 | 23.99 | 744.00 | 24.00 | 326.33 | 24.00 |
August | 218.83 | 23.99 | 744.00 | 23.99 | 218.83 | 23.99 |
September | 72.83 | 23.96 | 686.50 | 23.96 | 72.83 | 23.96 |
October | 217.33 | 23.16 | 263.33 | 23.59 | 6.50 | 23.60 |
November | 547.33 | 23.06 | 31.33 | 23.11 | 0.00 | 23.11 |
December | 737.17 | 22.75 | 0.00 | 22.75 | 0.00 | 22.75 |
Annual Sum or Average | 4072.83 | 23.12 | 3642.50 | 23.52 | 665.67 | 23.56 |
Minimum of Months | 31.67 | 22.75 | 0.00 | 22.75 | 0.00 | 22.75 |
Maximum of Months | 737.17 | 23.99 | 744.00 | 24.00 | 326.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 641.50 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
February | 441.83 | 23.13 | 4.50 | 23.14 | 0.00 | 23.14 |
March | 258.50 | 23.30 | 45.50 | 23.40 | 0.00 | 23.40 |
April | 69.67 | 23.49 | 152.33 | 23.84 | 0.00 | 23.84 |
May | 24.67 | 23.52 | 460.50 | 23.96 | 6.17 | 23.96 |
June | 26.83 | 23.99 | 685.17 | 23.99 | 26.83 | 23.99 |
July | 311.33 | 24.00 | 744.00 | 24.00 | 311.33 | 24.00 |
August | 209.33 | 24.00 | 744.00 | 24.00 | 209.33 | 24.00 |
September | 68.33 | 23.98 | 714.00 | 23.98 | 68.33 | 23.98 |
October | 129.50 | 23.28 | 313.33 | 23.77 | 5.00 | 23.77 |
November | 421.17 | 23.26 | 55.00 | 23.34 | 0.00 | 23.34 |
December | 663.50 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
Annual Sum or Average | 3266.17 | 23.31 | 3918.33 | 23.68 | 627.00 | 23.71 |
Minimum of Months | 24.67 | 23.03 | 0.00 | 23.03 | 0.00 | 23.03 |
Maximum of Months | 663.50 | 24.00 | 744.00 | 24.00 | 311.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 449.00 | 23.98 | 671.83 | 23.98 | 449.00 | 23.98 |
February | 421.67 | 23.98 | 638.00 | 23.99 | 421.67 | 23.98 |
March | 480.83 | 23.99 | 730.67 | 23.99 | 480.83 | 23.99 |
April | 484.83 | 23.99 | 711.00 | 23.99 | 484.83 | 23.99 |
May | 523.50 | 24.00 | 742.50 | 24.00 | 523.50 | 24.00 |
June | 537.00 | 24.00 | 720.00 | 24.00 | 537.00 | 24.00 |
July | 621.17 | 24.00 | 744.00 | 24.00 | 621.17 | 24.00 |
August | 598.67 | 24.00 | 744.00 | 24.00 | 598.67 | 24.00 |
September | 538.17 | 24.00 | 720.00 | 24.00 | 538.17 | 24.00 |
October | 505.50 | 23.99 | 741.17 | 23.99 | 505.50 | 23.99 |
November | 465.17 | 23.98 | 697.33 | 23.98 | 465.17 | 23.98 |
December | 444.33 | 23.98 | 654.67 | 23.98 | 444.33 | 23.98 |
Annual Sum or Average | 6069.83 | 23.99 | 8515.17 | 23.99 | 6069.83 | 23.99 |
Minimum of Months | 421.67 | 23.98 | 638.00 | 23.98 | 421.67 | 23.98 |
Maximum of Months | 621.17 | 24.00 | 744.00 | 24.00 | 621.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 684.50 | 22.05 | 486.33 | 22.10 | 462.17 | 22.09 |
February | 587.67 | 22.44 | 464.00 | 22.46 | 432.83 | 22.44 |
March | 521.17 | 23.19 | 539.50 | 23.23 | 472.33 | 23.20 |
April | 233.67 | 23.54 | 352.33 | 23.64 | 218.83 | 23.61 |
May | 134.00 | 23.80 | 369.50 | 23.89 | 132.00 | 23.87 |
June | 44.50 | 23.97 | 470.17 | 23.99 | 44.50 | 23.99 |
July | 3.17 | 24.00 | 714.83 | 24.00 | 3.17 | 24.00 |
August | 14.17 | 24.00 | 680.17 | 24.00 | 14.17 | 24.00 |
September | 72.17 | 23.99 | 463.33 | 24.00 | 72.17 | 24.00 |
October | 284.67 | 23.32 | 452.83 | 23.48 | 264.17 | 23.43 |
November | 581.17 | 23.07 | 532.67 | 23.07 | 474.50 | 23.04 |
December | 700.33 | 22.00 | 429.17 | 22.00 | 417.33 | 21.99 |
Annual Sum or Average | 3861.17 | 22.72 | 5954.83 | 23.12 | 3008.17 | 23.04 |
Minimum of Months | 3.17 | 22.00 | 352.33 | 22.00 | 3.17 | 21.99 |
Maximum of Months | 700.33 | 24.00 | 714.83 | 24.00 | 474.50 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.56247 | 19.24555 | -0.1396 | 6.05879 |
February | 672.00000 | 22.09277 | 21.36835 | -0.2542 | 7.02386 |
March | 744.00000 | 22.74409 | 21.45788 | -0.1224 | 5.77530 |
April | 720.00000 | 23.65922 | 18.22946 | 0.06735 | 5.32556 |
May | 744.00000 | 23.94518 | 25.40839 | -0.7395 | 16.72261 |
June | 720.00000 | 23.99953 | 32.86043 | -0.6475 | 13.89137 |
July | 744.00000 | 24.00009 | 43.69418 | -0.5483 | 11.33904 |
August | 744.00000 | 24.00012 | 42.41817 | -0.5378 | 11.08571 |
September | 720.00000 | 24.00011 | 36.98673 | -0.5512 | 11.42350 |
October | 744.00000 | 23.99204 | 24.79328 | 0.26813 | 6.57547 |
November | 720.00000 | 23.97103 | 19.30227 | 0.21930 | 6.04305 |
December | 744.00000 | 23.35386 | 16.79748 | 0.04732 | 5.29634 |
Annual Sum or Average | 8760.00000 | 23.53432 | 26.92587 | -0.2450 | 8.89212 |
Minimum of Months | 672.00000 | 22.09277 | 16.79748 | -0.7395 | 5.29634 |
Maximum of Months | 744.00000 | 24.00012 | 43.69418 | 0.26813 | 16.72261 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.93955 | 19.92260 | -0.2733 | 10.29629 |
February | 672.00000 | 22.11012 | 21.61163 | -0.2031 | 9.57624 |
March | 744.00000 | 22.19076 | 21.77761 | -0.1679 | 8.54756 |
April | 720.00000 | 22.67616 | 18.37487 | -0.0432 | 7.63678 |
May | 744.00000 | 22.85613 | 26.29691 | -0.9231 | 26.45692 |
June | 720.00000 | 23.33323 | 34.45290 | -0.6526 | 16.73655 |
July | 744.00000 | 23.65372 | 46.76491 | -0.4157 | 10.14347 |
August | 744.00000 | 23.61698 | 45.74445 | -0.4201 | 10.66617 |
September | 720.00000 | 23.37093 | 39.96588 | -0.5547 | 15.00750 |
October | 744.00000 | 22.86626 | 27.37695 | 0.10533 | 8.71820 |
November | 720.00000 | 22.32799 | 21.94416 | -0.1122 | 8.68190 |
December | 744.00000 | 22.00774 | 17.98682 | -0.2628 | 10.30681 |
Annual Sum or Average | 8760.00000 | 22.74904 | 28.57325 | -0.3278 | 11.91566 |
Minimum of Months | 672.00000 | 21.93955 | 17.98682 | -0.9231 | 7.63678 |
Maximum of Months | 744.00000 | 23.65372 | 46.76491 | 0.10533 | 26.45692 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.58783 | 20.74593 | -0.1096 | 5.84093 |
February | 672.00000 | 22.74618 | 22.31381 | -0.0580 | 5.65683 |
March | 744.00000 | 23.04432 | 22.12459 | 0.01884 | 5.45592 |
April | 720.00000 | 23.43522 | 18.81330 | 0.10425 | 5.56648 |
May | 744.00000 | 23.61264 | 26.27698 | -0.7220 | 16.56925 |
June | 720.00000 | 23.84799 | 34.52901 | -0.5625 | 11.92640 |
July | 744.00000 | 23.96860 | 46.91741 | -0.4234 | 8.80556 |
August | 744.00000 | 23.95003 | 45.90981 | -0.4368 | 9.07173 |
September | 720.00000 | 23.85958 | 39.97327 | -0.5216 | 10.90237 |
October | 744.00000 | 23.53127 | 27.70326 | 0.19455 | 6.36480 |
November | 720.00000 | 23.16940 | 22.37441 | 0.05269 | 5.43578 |
December | 744.00000 | 22.63939 | 18.91072 | -0.1080 | 5.74223 |
Annual Sum or Average | 8760.00000 | 23.36881 | 28.93626 | -0.2154 | 8.12790 |
Minimum of Months | 672.00000 | 22.58783 | 18.81330 | -0.7220 | 5.43578 |
Maximum of Months | 744.00000 | 23.96860 | 46.91741 | 0.19455 | 16.56925 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99970 | 12.48514 | 0.73938 | 17.27799 |
February | 672.00000 | 23.99970 | 14.18411 | 0.76229 | 18.03106 |
March | 744.00000 | 23.99970 | 14.58624 | 0.79243 | 19.03109 |
April | 720.00000 | 23.99978 | 12.95795 | 0.81285 | 19.72228 |
May | 744.00000 | 23.99997 | 21.68615 | 0.26588 | 8.21443 |
June | 720.00000 | 24.00023 | 31.50997 | 0.37344 | 9.65678 |
July | 744.00000 | 24.00109 | 41.00365 | 0.45159 | 10.72188 |
August | 744.00000 | 24.00109 | 40.61857 | 0.44495 | 10.67030 |
September | 720.00000 | 24.00070 | 36.28074 | 0.38528 | 9.64036 |
October | 744.00000 | 23.99994 | 22.12951 | 0.87241 | 21.89678 |
November | 720.00000 | 23.99968 | 14.68493 | 0.78610 | 18.80229 |
December | 744.00000 | 23.99971 | 10.74293 | 0.72641 | 16.87754 |
Annual Sum or Average | 8760.00000 | 24.00011 | 22.79721 | 0.61687 | 15.02715 |
Minimum of Months | 672.00000 | 23.99968 | 10.74293 | 0.26588 | 8.21443 |
Maximum of Months | 744.00000 | 24.00109 | 41.00365 | 0.87241 | 21.89678 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.86499 | 22.92705 | -0.1953 | 9.33775 |
February | 672.00000 | 22.17749 | 24.55183 | -0.0975 | 8.79598 |
March | 744.00000 | 22.80517 | 24.29042 | 0.04494 | 7.66809 |
April | 720.00000 | 23.51906 | 20.51163 | 0.20801 | 7.34497 |
May | 744.00000 | 23.88308 | 27.67987 | -0.5305 | 12.08837 |
June | 720.00000 | 23.99208 | 35.40468 | -0.3720 | 8.46566 |
July | 744.00000 | 24.00026 | 47.66114 | -0.2256 | 6.50071 |
August | 744.00000 | 24.00002 | 46.59253 | -0.2175 | 6.63527 |
September | 720.00000 | 23.99796 | 41.14339 | -0.2750 | 7.73783 |
October | 744.00000 | 23.50583 | 29.27667 | 0.31821 | 9.60394 |
November | 720.00000 | 22.77149 | 24.61863 | 0.06850 | 8.13958 |
December | 744.00000 | 21.88272 | 21.03232 | -0.1943 | 9.29244 |
Annual Sum or Average | 8760.00000 | 23.20436 | 30.52346 | -0.1229 | 8.47083 |
Minimum of Months | 672.00000 | 21.86499 | 20.51163 | -0.5305 | 6.50071 |
Maximum of Months | 744.00000 | 24.00026 | 47.66114 | 0.31821 | 12.08837 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.09805 | 22.92944 | 0.04477 | 5.61133 |
February | 672.00000 | 23.22351 | 24.46571 | 0.09040 | 5.62062 |
March | 744.00000 | 23.43313 | 24.30809 | 0.14876 | 5.78368 |
April | 720.00000 | 23.69532 | 21.06116 | 0.20717 | 6.09309 |
May | 744.00000 | 23.79166 | 28.37903 | -0.6069 | 13.13699 |
June | 720.00000 | 23.92408 | 36.49791 | -0.4752 | 9.90453 |
July | 744.00000 | 23.98479 | 48.79395 | -0.3494 | 7.59601 |
August | 744.00000 | 23.97532 | 47.75187 | -0.3572 | 7.72515 |
September | 720.00000 | 23.95283 | 41.79576 | -0.4182 | 8.79642 |
October | 744.00000 | 23.78506 | 29.64698 | 0.30462 | 7.34290 |
November | 720.00000 | 23.58917 | 24.49288 | 0.19481 | 6.06855 |
December | 744.00000 | 23.17460 | 21.14812 | 0.05317 | 5.50858 |
Annual Sum or Average | 8760.00000 | 23.63732 | 30.99220 | -0.0982 | 7.44411 |
Minimum of Months | 672.00000 | 23.09805 | 21.06116 | -0.6069 | 5.50858 |
Maximum of Months | 744.00000 | 23.98479 | 48.79395 | 0.30462 | 13.13699 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.52379 | 25.63084 | -0.3768 | 9.70710 |
February | 672.00000 | 21.60985 | 27.17022 | -0.3184 | 8.96388 |
March | 744.00000 | 21.67723 | 26.91934 | -0.2721 | 8.17594 |
April | 720.00000 | 21.74660 | 24.19998 | -0.2157 | 7.62737 |
May | 744.00000 | 21.76862 | 30.66003 | -1.2341 | 38.88579 |
June | 720.00000 | 21.79430 | 36.71824 | -1.1231 | 33.89375 |
July | 744.00000 | 21.80861 | 42.68417 | -1.0552 | 30.92068 |
August | 744.00000 | 21.80390 | 42.14899 | -1.0590 | 31.19035 |
September | 720.00000 | 21.78920 | 39.70942 | -1.1135 | 33.77541 |
October | 744.00000 | 21.72209 | 31.69000 | -0.1730 | 7.47024 |
November | 720.00000 | 21.67242 | 27.52510 | -0.2807 | 8.29379 |
December | 744.00000 | 21.51612 | 23.63205 | -0.3913 | 9.92386 |
Annual Sum or Average | 8760.00000 | 21.70297 | 31.58815 | -0.6365 | 19.13203 |
Minimum of Months | 672.00000 | 21.51612 | 23.63205 | -1.2341 | 7.47024 |
Maximum of Months | 744.00000 | 21.80861 | 42.68417 | -0.1730 | 38.88579 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.22765 | 26.26665 | -0.5020 | 11.21456 |
February | 672.00000 | 21.44225 | 27.78667 | -0.4129 | 10.10932 |
March | 744.00000 | 21.97660 | 27.45630 | -0.2495 | 9.34621 |
April | 720.00000 | 22.64576 | 24.78364 | -0.0545 | 9.81985 |
May | 744.00000 | 22.53868 | 30.43601 | -1.0262 | 32.87450 |
June | 720.00000 | 22.39583 | 36.12422 | -0.9537 | 28.71169 |
July | 744.00000 | 22.43443 | 42.66624 | -0.8839 | 25.45603 |
August | 744.00000 | 22.51885 | 42.08358 | -0.8762 | 25.58808 |
September | 720.00000 | 22.70445 | 39.31906 | -0.9026 | 27.04196 |
October | 744.00000 | 22.48139 | 31.92314 | -0.0701 | 9.49543 |
November | 720.00000 | 21.49897 | 28.17880 | -0.3787 | 9.15948 |
December | 744.00000 | 21.15507 | 24.31645 | -0.5377 | 11.94837 |
Annual Sum or Average | 8760.00000 | 22.08780 | 31.80766 | -0.5719 | 17.61279 |
Minimum of Months | 672.00000 | 21.15507 | 24.31645 | -1.0262 | 9.15948 |
Maximum of Months | 744.00000 | 22.70445 | 42.66624 | -0.0545 | 32.87450 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.25089 | 23.21497 | -0.4996 | 10.32995 |
February | 672.00000 | 21.37707 | 25.05363 | -0.4483 | 9.49217 |
March | 744.00000 | 21.72171 | 24.64692 | -0.3449 | 8.06447 |
April | 720.00000 | 22.18919 | 21.88840 | -0.2261 | 7.41116 |
May | 744.00000 | 22.28262 | 28.69777 | -1.2066 | 37.50888 |
June | 720.00000 | 22.26680 | 35.72723 | -1.1258 | 33.90563 |
July | 744.00000 | 22.35057 | 43.86849 | -1.0382 | 30.45872 |
August | 744.00000 | 22.38129 | 43.43979 | -1.0432 | 30.60188 |
September | 720.00000 | 22.47628 | 39.61954 | -1.0705 | 31.67941 |
October | 744.00000 | 22.08893 | 30.03931 | -0.2092 | 7.31155 |
November | 720.00000 | 21.42443 | 25.55796 | -0.4214 | 8.97348 |
December | 744.00000 | 21.15286 | 21.22409 | -0.5397 | 11.20874 |
Annual Sum or Average | 8760.00000 | 21.91604 | 30.28594 | -0.6827 | 18.97228 |
Minimum of Months | 672.00000 | 21.15286 | 21.22409 | -1.2066 | 7.31155 |
Maximum of Months | 744.00000 | 22.47628 | 43.86849 | -0.2092 | 37.50888 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57430 | 25.41190 | -0.3684 | 9.49322 |
February | 672.00000 | 21.66171 | 26.93094 | -0.3122 | 8.76710 |
March | 744.00000 | 21.74730 | 26.51178 | -0.2503 | 7.95249 |
April | 720.00000 | 21.80658 | 23.70080 | -0.1872 | 7.47680 |
May | 744.00000 | 21.80777 | 29.97761 | -1.2000 | 37.35302 |
June | 720.00000 | 21.81396 | 36.08829 | -1.0926 | 32.58320 |
July | 744.00000 | 21.81844 | 41.90138 | -1.0269 | 29.81653 |
August | 744.00000 | 21.81759 | 41.43912 | -1.0355 | 30.25259 |
September | 720.00000 | 21.81049 | 39.35288 | -1.0985 | 33.06136 |
October | 744.00000 | 21.76461 | 31.27904 | -0.1630 | 7.37524 |
November | 720.00000 | 21.71054 | 27.24411 | -0.2729 | 8.13743 |
December | 744.00000 | 21.58727 | 23.44754 | -0.3785 | 9.62192 |
Annual Sum or Average | 8760.00000 | 21.74359 | 31.13608 | -0.6175 | 18.55084 |
Minimum of Months | 672.00000 | 21.57430 | 23.44754 | -1.2000 | 7.37524 |
Maximum of Months | 744.00000 | 21.81844 | 41.90138 | -0.1630 | 37.35302 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30118 | 26.09526 | -0.4884 | 10.75171 |
February | 672.00000 | 21.50386 | 27.52350 | -0.4056 | 9.50288 |
March | 744.00000 | 21.92557 | 26.62383 | -0.2542 | 7.92860 |
April | 720.00000 | 22.44314 | 23.79536 | -0.0841 | 7.73215 |
May | 744.00000 | 22.53015 | 29.60013 | -1.0070 | 31.30926 |
June | 720.00000 | 22.61452 | 35.40006 | -0.8627 | 28.74416 |
July | 744.00000 | 22.67724 | 41.62197 | -0.7833 | 26.18324 |
August | 744.00000 | 22.75680 | 41.14143 | -0.7836 | 25.96473 |
September | 720.00000 | 22.77516 | 38.87720 | -0.8701 | 26.58276 |
October | 744.00000 | 22.29542 | 31.11125 | -0.1093 | 7.67301 |
November | 720.00000 | 21.57678 | 27.96642 | -0.3620 | 8.66454 |
December | 744.00000 | 21.16749 | 24.16765 | -0.5363 | 11.49394 |
Annual Sum or Average | 8760.00000 | 22.13333 | 31.18640 | -0.5467 | 16.92665 |
Minimum of Months | 672.00000 | 21.16749 | 23.79536 | -1.0070 | 7.67301 |
Maximum of Months | 744.00000 | 22.77516 | 41.62197 | -0.0841 | 31.30926 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.34463 | 26.21715 | -0.4938 | 12.34654 |
February | 672.00000 | 21.47777 | 27.75799 | -0.4149 | 11.04204 |
March | 744.00000 | 21.57954 | 27.43602 | -0.3457 | 9.66018 |
April | 720.00000 | 21.70309 | 24.31630 | -0.2512 | 8.51341 |
May | 744.00000 | 21.73929 | 31.00498 | -1.2583 | 40.59424 |
June | 720.00000 | 21.78516 | 36.99751 | -1.1123 | 34.14433 |
July | 744.00000 | 21.80685 | 42.79222 | -1.0291 | 30.53526 |
August | 744.00000 | 21.79739 | 42.36869 | -1.0401 | 31.11097 |
September | 720.00000 | 21.76861 | 40.33949 | -1.1231 | 34.89861 |
October | 744.00000 | 21.65401 | 32.26236 | -0.2196 | 8.51339 |
November | 720.00000 | 21.55609 | 28.21281 | -0.3693 | 9.95628 |
December | 744.00000 | 21.33521 | 24.16292 | -0.5125 | 12.75808 |
Annual Sum or Average | 8760.00000 | 21.62940 | 32.01858 | -0.6827 | 20.39900 |
Minimum of Months | 672.00000 | 21.33521 | 24.16292 | -1.2583 | 8.51339 |
Maximum of Months | 744.00000 | 21.80685 | 42.79222 | -0.2196 | 40.59424 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.98384 | 26.76359 | -0.6385 | 14.71170 |
February | 672.00000 | 21.24739 | 28.40811 | -0.5273 | 12.85526 |
March | 744.00000 | 21.86184 | 28.06728 | -0.3264 | 11.12386 |
April | 720.00000 | 22.65691 | 25.02365 | -0.0720 | 11.11206 |
May | 744.00000 | 22.52666 | 30.77055 | -1.0376 | 34.54071 |
June | 720.00000 | 22.37318 | 36.31245 | -0.9423 | 29.08229 |
July | 744.00000 | 22.40334 | 42.58258 | -0.8634 | 25.18706 |
August | 744.00000 | 22.49279 | 42.01877 | -0.8592 | 25.60293 |
September | 720.00000 | 22.67465 | 39.66538 | -0.9093 | 27.96931 |
October | 744.00000 | 22.43313 | 32.48319 | -0.1096 | 10.91696 |
November | 720.00000 | 21.30786 | 28.96443 | -0.4896 | 11.46876 |
December | 744.00000 | 20.89024 | 24.70206 | -0.6836 | 15.86802 |
Annual Sum or Average | 8760.00000 | 21.99083 | 32.17379 | -0.6225 | 19.24769 |
Minimum of Months | 672.00000 | 20.89024 | 24.70206 | -1.0376 | 10.91696 |
Maximum of Months | 744.00000 | 22.67465 | 42.58258 | -0.0720 | 34.54071 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.60862 | 26.61675 | -0.3334 | 10.02544 |
February | 672.00000 | 21.65599 | 28.01590 | -0.2950 | 9.44624 |
March | 744.00000 | 21.68053 | 27.78879 | -0.2866 | 8.81679 |
April | 720.00000 | 21.73516 | 25.07502 | -0.2588 | 8.33577 |
May | 744.00000 | 21.74884 | 32.06810 | -1.3102 | 42.61557 |
June | 720.00000 | 21.78400 | 38.16518 | -1.2000 | 37.34238 |
July | 744.00000 | 21.80694 | 43.97951 | -1.1052 | 33.13429 |
August | 744.00000 | 21.79853 | 43.36916 | -1.0985 | 33.14619 |
September | 720.00000 | 21.78329 | 40.69602 | -1.1328 | 35.22113 |
October | 744.00000 | 21.73419 | 32.18669 | -0.1671 | 8.04380 |
November | 720.00000 | 21.71403 | 28.32084 | -0.2494 | 8.72493 |
December | 744.00000 | 21.59831 | 24.68001 | -0.3387 | 10.15536 |
Annual Sum or Average | 8760.00000 | 21.72087 | 32.61237 | -0.6502 | 20.48570 |
Minimum of Months | 672.00000 | 21.59831 | 24.68001 | -1.3102 | 8.04380 |
Maximum of Months | 744.00000 | 21.80694 | 43.97951 | -0.1671 | 42.61557 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.84115 | 23.10574 | -0.0349 | 5.53093 |
February | 672.00000 | 23.07636 | 24.65419 | 0.05198 | 5.63321 |
March | 744.00000 | 23.49061 | 24.45129 | 0.19024 | 6.09081 |
April | 720.00000 | 23.80357 | 21.26241 | 0.29212 | 6.99932 |
May | 744.00000 | 23.90456 | 28.67802 | -0.4526 | 9.71070 |
June | 720.00000 | 23.97408 | 37.04185 | -0.3060 | 7.18861 |
July | 744.00000 | 23.99554 | 50.60513 | -0.1793 | 5.79258 |
August | 744.00000 | 23.98679 | 49.33993 | -0.2082 | 6.03585 |
September | 720.00000 | 23.94766 | 42.97982 | -0.3205 | 7.36417 |
October | 744.00000 | 23.68215 | 30.45107 | 0.31172 | 7.61971 |
November | 720.00000 | 23.27262 | 24.97497 | 0.11900 | 5.75017 |
December | 744.00000 | 22.76010 | 21.27243 | -0.0729 | 5.67382 |
Annual Sum or Average | 8760.00000 | 23.56319 | 31.62493 | -0.0516 | 6.62160 |
Minimum of Months | 672.00000 | 22.76010 | 21.26241 | -0.4526 | 5.53093 |
Maximum of Months | 744.00000 | 23.99554 | 50.60513 | 0.31172 | 9.71070 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.20842 | 22.72731 | 0.08031 | 5.51871 |
February | 672.00000 | 23.39570 | 24.24395 | 0.15446 | 5.91587 |
March | 744.00000 | 23.70439 | 24.02424 | 0.26542 | 6.68342 |
April | 720.00000 | 23.90799 | 20.87079 | 0.34142 | 7.58681 |
May | 744.00000 | 23.95707 | 28.29190 | -0.3992 | 8.67046 |
June | 720.00000 | 23.98950 | 36.70459 | -0.2644 | 6.68519 |
July | 744.00000 | 23.99669 | 50.31215 | -0.1428 | 5.56138 |
August | 744.00000 | 23.99527 | 49.02140 | -0.1696 | 5.73798 |
September | 720.00000 | 23.98272 | 42.59109 | -0.2740 | 6.76236 |
October | 744.00000 | 23.81782 | 30.02509 | 0.36715 | 8.25315 |
November | 720.00000 | 23.53153 | 24.58575 | 0.20404 | 6.19029 |
December | 744.00000 | 23.13338 | 20.93993 | 0.04407 | 5.49740 |
Annual Sum or Average | 8760.00000 | 23.71955 | 31.25205 | 0.01627 | 6.59173 |
Minimum of Months | 672.00000 | 23.13338 | 20.87079 | -0.3992 | 5.49740 |
Maximum of Months | 744.00000 | 23.99669 | 50.31215 | 0.36715 | 8.67046 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.98656 | 25.34283 | 0.90324 | 24.25316 |
February | 672.00000 | 23.98716 | 25.76673 | 0.93369 | 25.45279 |
March | 744.00000 | 23.98908 | 23.39597 | 0.97058 | 26.87966 |
April | 720.00000 | 23.99305 | 21.00480 | 1.02550 | 29.43394 |
May | 744.00000 | 23.99633 | 30.25292 | 0.57113 | 17.07395 |
June | 720.00000 | 23.99955 | 40.73949 | 0.72581 | 21.47998 |
July | 744.00000 | 24.00196 | 49.41974 | 0.81768 | 23.66014 |
August | 744.00000 | 24.00147 | 48.23603 | 0.79285 | 22.90133 |
September | 720.00000 | 23.99950 | 42.94361 | 0.68891 | 19.90129 |
October | 744.00000 | 23.99337 | 29.49405 | 1.06285 | 30.85661 |
November | 720.00000 | 23.98649 | 24.56754 | 0.94984 | 25.93929 |
December | 744.00000 | 23.98657 | 24.09081 | 0.88944 | 23.73128 |
Annual Sum or Average | 8760.00000 | 23.99346 | 32.15434 | 0.86051 | 24.28864 |
Minimum of Months | 672.00000 | 23.98649 | 21.00480 | 0.57113 | 17.07395 |
Maximum of Months | 744.00000 | 24.00196 | 49.41974 | 1.06285 | 30.85661 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04336 | 19.09479 | -0.5319 | 10.96545 |
February | 672.00000 | 21.12384 | 20.96075 | -0.4946 | 10.23347 |
March | 744.00000 | 21.39706 | 20.84360 | -0.4092 | 8.67416 |
April | 720.00000 | 22.24329 | 17.01830 | -0.2226 | 6.59239 |
May | 744.00000 | 22.94109 | 24.34814 | -1.0094 | 27.55202 |
June | 720.00000 | 23.59273 | 32.36271 | -0.7172 | 16.40165 |
July | 744.00000 | 23.83483 | 44.77473 | -0.5423 | 11.32607 |
August | 744.00000 | 23.74348 | 43.98873 | -0.5865 | 12.44970 |
September | 720.00000 | 23.38156 | 38.47820 | -0.7621 | 17.73684 |
October | 744.00000 | 22.34200 | 26.44789 | -0.1370 | 6.49338 |
November | 720.00000 | 21.35242 | 21.23060 | -0.4163 | 8.84488 |
December | 744.00000 | 21.02945 | 17.14621 | -0.5449 | 11.25859 |
Annual Sum or Average | 8760.00000 | 22.34202 | 27.27551 | -0.5315 | 12.39482 |
Minimum of Months | 672.00000 | 21.02945 | 17.01830 | -1.0094 | 6.49338 |
Maximum of Months | 744.00000 | 23.83483 | 44.77473 | -0.1370 | 27.55202 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.80214 | 70.63460 | 0.43811 | 9.14304 |
February | 672.00000 | 23.91153 | 66.11027 | 0.44170 | 9.23525 |
March | 744.00000 | 23.98706 | 54.51795 | 0.39038 | 8.26184 |
April | 720.00000 | 23.99888 | 45.60754 | 0.34526 | 7.54187 |
May | 744.00000 | 23.99919 | 45.28475 | -0.5745 | 11.93452 |
June | 720.00000 | 23.99923 | 44.33282 | -0.5626 | 11.64456 |
July | 744.00000 | 23.99925 | 47.31372 | -0.5332 | 10.95523 |
August | 744.00000 | 23.99923 | 46.94002 | -0.5357 | 11.01061 |
September | 720.00000 | 23.99919 | 46.04436 | -0.5496 | 11.35529 |
October | 744.00000 | 23.98645 | 48.55900 | 0.36697 | 7.87200 |
November | 720.00000 | 23.98214 | 55.00609 | 0.39141 | 8.31464 |
December | 744.00000 | 23.85029 | 71.40414 | 0.45549 | 9.47734 |
Annual Sum or Average | 8760.00000 | 23.95956 | 53.43861 | 0.00366 | 9.73307 |
Minimum of Months | 672.00000 | 23.80214 | 44.33282 | -0.5745 | 7.54187 |
Maximum of Months | 744.00000 | 23.99925 | 71.40414 | 0.45549 | 11.93452 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.20167 | 64.13621 | -0.0257 | 6.47061 |
February | 672.00000 | 22.63527 | 65.66797 | 0.10298 | 6.48204 |
March | 744.00000 | 23.43199 | 62.03369 | 0.29778 | 7.26504 |
April | 720.00000 | 23.84742 | 46.78630 | 0.33595 | 7.50078 |
May | 744.00000 | 23.96261 | 44.05537 | -0.5431 | 11.31081 |
June | 720.00000 | 23.99772 | 40.96219 | -0.4974 | 10.28752 |
July | 744.00000 | 23.99924 | 42.05300 | -0.4603 | 9.53248 |
August | 744.00000 | 23.99924 | 42.14337 | -0.4674 | 9.67932 |
September | 720.00000 | 23.99872 | 43.37974 | -0.4988 | 10.34239 |
October | 744.00000 | 23.73595 | 50.38958 | 0.33335 | 7.58118 |
November | 720.00000 | 23.24809 | 63.41119 | 0.25226 | 6.87131 |
December | 744.00000 | 22.11325 | 62.66655 | -0.0605 | 6.38479 |
Annual Sum or Average | 8760.00000 | 23.43372 | 52.23752 | -0.1043 | 8.31920 |
Minimum of Months | 672.00000 | 22.11325 | 40.96219 | -0.5431 | 6.38479 |
Maximum of Months | 744.00000 | 23.99924 | 65.66797 | 0.33595 | 11.31081 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.82410 | 18.12665 | -0.3265 | 7.55805 |
February | 672.00000 | 21.97865 | 19.78438 | -0.2783 | 7.06213 |
March | 744.00000 | 22.57896 | 19.32439 | -0.1355 | 5.72033 |
April | 720.00000 | 23.26810 | 15.86170 | 0.01286 | 5.34329 |
May | 744.00000 | 23.65647 | 23.13812 | -0.7715 | 18.11859 |
June | 720.00000 | 23.90802 | 31.55007 | -0.6054 | 12.87824 |
July | 744.00000 | 23.97935 | 44.18891 | -0.4838 | 9.94912 |
August | 744.00000 | 23.96732 | 43.16666 | -0.5008 | 10.30460 |
September | 720.00000 | 23.87705 | 37.06851 | -0.5897 | 12.46737 |
October | 744.00000 | 23.34148 | 24.88618 | 0.09503 | 5.85975 |
November | 720.00000 | 22.63657 | 19.57106 | -0.1186 | 5.64461 |
December | 744.00000 | 21.82990 | 16.24028 | -0.3351 | 7.63425 |
Annual Sum or Average | 8760.00000 | 23.07562 | 26.12797 | -0.3371 | 9.06090 |
Minimum of Months | 672.00000 | 21.82410 | 15.86170 | -0.7715 | 5.34329 |
Maximum of Months | 744.00000 | 23.97935 | 44.18891 | 0.09503 | 18.11859 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.136562E+12 | 0.00 | 690.45 | 200342.26 | 20-JAN-09:02 | 0.00 | 33.07 | 70.55 | 0.30 | 0.00 | 0.08 | 0.32 | 20-JAN-09:02 |
February | 0.986204E+11 | 0.00 | 567.37 | 159886.84 | 16-FEB-16:12 | 0.00 | 31.49 | 66.03 | 0.24 | 0.00 | 0.06 | 0.25 | 16-FEB-16:12 |
March | 0.462157E+11 | 0.00 | 461.12 | 103494.57 | 05-MAR-06:00 | 0.00 | 28.62 | 54.12 | 0.10 | 0.00 | 0.03 | 0.16 | 05-MAR-06:00 |
April | 0.126038E+11 | 0.00 | 215.93 | 87524.73 | 06-APR-08:03 | 0.00 | 26.54 | 38.89 | 0.03 | 0.00 | 0.01 | 0.14 | 06-APR-08:03 |
May | 0.246561E+10 | 0.00 | 66.87 | 41721.47 | 25-MAY-08:05 | 0.00 | 27.26 | 30.94 | 0.01 | 0.00 | 0.00 | 0.07 | 25-MAY-08:05 |
June | 0.132678E+09 | 0.00 | 22.19 | 31349.71 | 09-JUN-08:05 | 0.00 | 25.57 | 26.81 | 0.00 | 0.00 | 0.00 | 0.05 | 09-JUN-08:05 |
July | 4794171.70 | 0.00 | 153.75 | 3745.53 | 27-JUL-21:54 | 0.00 | 25.89 | 34.08 | 0.00 | 0.00 | 0.00 | 0.01 | 27-JUL-21:54 |
August | 6223951.83 | 0.00 | 89.36 | 4725.13 | 23-AUG-21:54 | 0.00 | 26.98 | 31.62 | 0.00 | 0.00 | 0.00 | 0.01 | 23-AUG-21:54 |
September | 32346849.16 | 0.00 | 11.61 | 26434.47 | 08-SEP-08:05 | 0.00 | 27.73 | 28.34 | 0.00 | 0.00 | 0.00 | 0.04 | 08-SEP-08:05 |
October | 0.195462E+11 | 0.00 | 245.63 | 135705.72 | 25-OCT-08:62 | 0.00 | 27.55 | 41.10 | 0.04 | 0.00 | 0.01 | 0.21 | 25-OCT-08:62 |
November | 0.574503E+11 | 0.00 | 574.77 | 111844.37 | 27-NOV-06:00 | 0.00 | 28.80 | 61.59 | 0.13 | 0.00 | 0.04 | 0.18 | 27-NOV-06:00 |
December | 0.140591E+12 | 0.00 | 731.84 | 257806.21 | 21-DEC-16:12 | 0.00 | 33.14 | 72.90 | 0.31 | 0.00 | 0.08 | 0.41 | 21-DEC-16:12 |
Annual Sum or Average | 0.514230E+12 | 0.00 | 3830.90 | 0.00 | 28.55 | 46.34 | 0.10 | 0.00 | 0.03 | ||||
Minimum of Months | 4794171.70 | 0.00 | 11.61 | 3745.53 | 0.00 | 25.57 | 26.81 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.140591E+12 | 0.00 | 731.84 | 257806.21 | 0.00 | 33.14 | 72.90 | 0.31 | 0.00 | 0.08 | 0.41 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.272001E+10 | 0.797678E+09 | 279.15 | 0.271826E+10 | 1749393.18 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 22580.75 | 30-JAN-16:12 | 22580.75 | 06-JAN-16:12 | 138.11 | 29-JAN-09:02 | 5846.54 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.348967E+10 | 0.101748E+10 | 319.16 | 0.348290E+10 | 6778985.92 | 0.00 | 1.00 | 02-FEB-16:12 | 0.00 | 01-FEB-00:05 | 22580.75 | 10-FEB-16:12 | 22580.75 | 08-FEB-16:12 | 472.92 | 21-FEB-19:02 | 5846.54 | 02-FEB-16:12 | 0.00 | 01-FEB-00:05 |
March | 0.522988E+10 | 0.152263E+10 | 483.99 | 0.521206E+10 | 17822397.89 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 22580.75 | 04-MAR-16:12 | 22580.75 | 04-MAR-16:12 | 1207.07 | 28-MAR-18:02 | 5846.54 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 |
April | 0.833714E+10 | 0.242533E+10 | 612.49 | 0.831849E+10 | 18653838.46 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-04:30 | 23457.99 | 15-APR-08:62 | 22580.75 | 02-APR-18:02 | 2936.97 | 15-APR-08:62 | 6080.72 | 15-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.103712E+11 | 0.305781E+10 | 679.47 | 0.100188E+11 | 0.352369E+09 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-06:52 | 24949.07 | 24-MAY-18:02 | 22580.75 | 10-MAY-18:02 | 6978.32 | 24-MAY-18:02 | 6446.93 | 24-MAY-18:02 | 0.00 | 01-MAY-00:10 |
June | 0.138608E+11 | 0.432966E+10 | 687.70 | 0.131550E+11 | 0.705861E+09 | 0.00 | 1.00 | 01-JUN-15:12 | 0.00 | 01-JUN-06:52 | 24808.96 | 08-JUN-15:12 | 22643.53 | 09-JUN-15:12 | 6706.03 | 08-JUN-15:12 | 6888.04 | 29-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.169316E+11 | 0.530904E+10 | 724.33 | 0.150094E+11 | 0.192227E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:53 | 25952.59 | 01-JUL-08:62 | 21022.43 | 29-JUL-18:02 | 9662.24 | 01-JUL-08:62 | 6992.41 | 22-JUL-15:12 | 0.00 | 01-JUL-00:10 |
August | 0.166188E+11 | 0.508698E+10 | 719.75 | 0.147714E+11 | 0.184736E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 25842.34 | 26-AUG-08:62 | 21468.33 | 28-AUG-15:12 | 9265.01 | 26-AUG-08:62 | 6748.67 | 01-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.134927E+11 | 0.400290E+10 | 684.14 | 0.122974E+11 | 0.119524E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:52 | 25401.66 | 06-SEP-08:62 | 22580.75 | 26-SEP-18:02 | 8888.63 | 06-SEP-08:62 | 6550.58 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.931147E+10 | 0.271342E+10 | 618.06 | 0.893922E+10 | 0.372241E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 25194.54 | 11-OCT-08:62 | 22631.02 | 09-OCT-15:12 | 7894.02 | 11-OCT-08:62 | 6503.57 | 11-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.433296E+10 | 0.127109E+10 | 436.60 | 0.429212E+10 | 40843552.81 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:52 | 23296.55 | 09-NOV-09:02 | 22580.75 | 07-NOV-16:12 | 2412.12 | 09-NOV-09:02 | 6038.71 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.251558E+10 | 0.741771E+09 | 292.82 | 0.251435E+10 | 1233057.54 | 0.00 | 1.00 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 | 22580.75 | 04-DEC-16:12 | 22580.75 | 02-DEC-16:12 | 317.97 | 25-DEC-16:12 | 5846.54 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.107212E+12 | 0.322758E+11 | 6537.65 | 0.100729E+12 | 0.648243E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.251558E+10 | 0.741771E+09 | 279.15 | 0.251435E+10 | 1233057.54 | 0.00 | 1.00 | 0.00 | 22580.75 | 21022.43 | 138.11 | 5846.54 | 0.00 | |||||||
Maximum of Months | 0.169316E+11 | 0.530904E+10 | 724.33 | 0.150094E+11 | 0.192227E+10 | 0.00 | 1.00 | 0.00 | 25952.59 | 22643.53 | 9662.24 | 6992.41 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.847145E+09 | 0.249615E+09 | 126.17 | 0.846452E+09 | 693508.38 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 22472.74 | 05-JAN-17:01 | 22472.74 | 05-JAN-17:01 | 132.39 | 13-JAN-09:04 | 5820.45 | 05-JAN-17:01 | 0.00 | 01-JAN-00:05 |
February | 0.149312E+10 | 0.439132E+09 | 191.37 | 0.148893E+10 | 4185013.39 | 0.00 | 1.00 | 02-FEB-16:12 | 0.00 | 01-FEB-00:05 | 22487.17 | 15-FEB-18:01 | 22487.17 | 15-FEB-18:01 | 433.38 | 17-FEB-16:17 | 5824.37 | 15-FEB-18:01 | 0.00 | 01-FEB-00:05 |
March | 0.269526E+10 | 0.793856E+09 | 376.72 | 0.267743E+10 | 17828097.50 | 0.00 | 1.00 | 04-MAR-16:12 | 0.00 | 01-MAR-00:10 | 22975.24 | 07-MAR-19:31 | 22975.24 | 07-MAR-19:31 | 1247.70 | 28-MAR-18:02 | 5955.15 | 07-MAR-19:31 | 0.00 | 01-MAR-00:10 |
April | 0.555834E+10 | 0.162678E+10 | 494.35 | 0.553411E+10 | 24235509.40 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-04:20 | 23285.54 | 14-APR-21:51 | 23285.54 | 14-APR-21:51 | 2773.41 | 15-APR-08:62 | 6035.95 | 14-APR-21:51 | 0.00 | 01-APR-00:10 |
May | 0.853712E+10 | 0.252033E+10 | 565.40 | 0.823310E+10 | 0.304019E+09 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-06:52 | 25353.61 | 24-MAY-19:41 | 24112.33 | 26-MAY-17:42 | 6858.02 | 24-MAY-19:42 | 6531.43 | 24-MAY-19:41 | 0.00 | 01-MAY-00:10 |
June | 0.128111E+11 | 0.401461E+10 | 590.10 | 0.121641E+11 | 0.646967E+09 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-06:42 | 25667.24 | 24-JUN-08:51 | 23445.67 | 15-JUN-21:51 | 7562.15 | 05-JUN-21:53 | 6823.50 | 29-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.153179E+11 | 0.481935E+10 | 607.96 | 0.136343E+11 | 0.168361E+10 | 0.00 | 1.00 | 01-JUL-08:51 | 0.00 | 01-JUL-05:13 | 27354.33 | 01-JUL-08:51 | 22438.80 | 29-JUL-21:51 | 11158.10 | 01-JUL-08:53 | 6943.27 | 01-JUL-08:51 | 0.00 | 01-JUL-00:10 |
August | 0.141455E+11 | 0.434599E+10 | 591.37 | 0.125776E+11 | 0.156786E+10 | 0.00 | 1.00 | 01-AUG-08:31 | 0.00 | 01-AUG-05:12 | 27365.99 | 13-AUG-08:51 | 23119.32 | 23-AUG-16:51 | 10957.64 | 26-AUG-08:53 | 6945.48 | 13-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.987309E+10 | 0.294041E+10 | 528.40 | 0.888138E+10 | 0.991703E+09 | 0.00 | 1.00 | 01-SEP-08:51 | 0.00 | 01-SEP-05:13 | 26258.07 | 05-SEP-21:51 | 23288.85 | 19-SEP-21:51 | 9000.44 | 05-SEP-21:52 | 6725.57 | 05-SEP-21:51 | 0.00 | 01-SEP-00:10 |
October | 0.512008E+10 | 0.151056E+10 | 454.12 | 0.480489E+10 | 0.315191E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 26052.43 | 02-OCT-21:51 | 23318.76 | 19-OCT-21:41 | 8173.47 | 02-OCT-21:53 | 6682.60 | 02-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.187133E+10 | 0.553501E+09 | 301.28 | 0.183963E+10 | 31704970.93 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:52 | 23792.57 | 02-NOV-18:11 | 22466.50 | 02-NOV-18:11 | 2281.92 | 09-NOV-09:02 | 6164.33 | 02-NOV-18:11 | 0.00 | 01-NOV-00:10 |
December | 0.605148E+09 | 0.178700E+09 | 118.13 | 0.604796E+09 | 352239.52 | 0.00 | 1.00 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 | 22362.43 | 18-DEC-16:12 | 22362.43 | 02-DEC-16:12 | 171.17 | 26-DEC-09:03 | 5790.01 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.788751E+11 | 0.239928E+11 | 4945.37 | 0.732868E+11 | 0.558835E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.605148E+09 | 0.178700E+09 | 118.13 | 0.604796E+09 | 352239.52 | 0.00 | 1.00 | 0.00 | 22362.43 | 22362.43 | 132.39 | 5790.01 | 0.00 | |||||||
Maximum of Months | 0.153179E+11 | 0.481935E+10 | 607.96 | 0.136343E+11 | 0.168361E+10 | 0.00 | 1.00 | 0.00 | 27365.99 | 24112.33 | 11158.10 | 6945.48 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.373631E+11 | 0.107384E+11 | 396.43 | 0.373631E+11 | -0.0 | 0.00 | 0.63 | 01-JAN-14:00 | 0.00 | 01-JAN-00:40 | 73501.00 | 01-JAN-14:00 | 73501.00 | 01-JAN-14:00 | 0.00 | 04-JAN-16:00 | 20272.77 | 01-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.365359E+11 | 0.105479E+11 | 407.43 | 0.365359E+11 | -0.0 | 0.00 | 0.65 | 14-FEB-13:00 | 0.00 | 01-FEB-00:05 | 76594.58 | 14-FEB-13:00 | 76594.58 | 14-FEB-13:00 | 0.00 | 22-FEB-15:10 | 21042.32 | 14-FEB-13:00 | 0.00 | 01-FEB-00:05 |
March | 0.376866E+11 | 0.109688E+11 | 493.97 | 0.376866E+11 | -0.0 | 0.00 | 0.57 | 08-MAR-13:30 | 0.00 | 01-MAR-00:10 | 66761.51 | 08-MAR-13:30 | 66761.51 | 08-MAR-13:30 | 0.00 | 14-MAR-15:00 | 18607.00 | 08-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 0.411196E+11 | 0.120888E+11 | 578.99 | 0.411196E+11 | -0.0 | 0.00 | 0.46 | 01-APR-14:10 | 0.00 | 01-APR-00:10 | 52753.88 | 01-APR-14:10 | 52753.88 | 01-APR-14:10 | 0.00 | 15-APR-14:30 | 14949.23 | 01-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.417160E+11 | 0.125184E+11 | 652.78 | 0.414544E+11 | 0.261668E+09 | 0.00 | 0.40 | 13-MAY-14:10 | 0.00 | 01-MAY-02:20 | 43269.15 | 13-MAY-14:10 | 43269.15 | 13-MAY-14:10 | 1944.94 | 28-MAY-08:00 | 13727.45 | 13-MAY-14:10 | 0.00 | 01-MAY-00:10 |
June | 0.532971E+11 | 0.170620E+11 | 693.00 | 0.528542E+11 | 0.442861E+09 | 0.00 | 0.50 | 29-JUN-15:00 | 0.00 | 02-JUN-01:40 | 52968.95 | 29-JUN-14:30 | 52968.95 | 29-JUN-14:30 | 2165.43 | 24-JUN-07:55 | 19917.74 | 29-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.704126E+11 | 0.224707E+11 | 744.00 | 0.672272E+11 | 0.318542E+10 | 0.00 | 0.53 | 22-JUL-14:10 | 0.02 | 08-JUL-05:00 | 56371.87 | 23-JUL-14:10 | 56371.87 | 23-JUL-14:10 | 5330.55 | 01-JUL-16:10 | 21169.56 | 22-JUL-14:10 | 0.00 | 01-JUL-00:10 |
August | 0.751852E+11 | 0.233305E+11 | 744.00 | 0.721954E+11 | 0.298978E+10 | 0.00 | 0.57 | 20-AUG-14:10 | 0.02 | 29-AUG-04:00 | 64380.36 | 20-AUG-14:10 | 64380.36 | 20-AUG-14:10 | 5771.61 | 26-AUG-10:50 | 22234.86 | 20-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.734132E+11 | 0.218399E+11 | 713.00 | 0.717574E+11 | 0.165586E+10 | 0.00 | 0.63 | 27-SEP-14:10 | 0.00 | 09-SEP-01:30 | 73607.85 | 28-SEP-13:30 | 73607.85 | 28-SEP-13:30 | 5677.85 | 05-SEP-12:40 | 22777.25 | 03-SEP-13:30 | 0.00 | 01-SEP-00:10 |
October | 0.666733E+11 | 0.192575E+11 | 626.10 | 0.663531E+11 | 0.320265E+09 | 0.00 | 0.65 | 31-OCT-13:00 | 0.00 | 08-OCT-01:50 | 75995.81 | 31-OCT-13:00 | 75995.81 | 31-OCT-13:00 | 3109.72 | 11-OCT-11:00 | 22314.45 | 01-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.488923E+11 | 0.140646E+11 | 498.01 | 0.488923E+11 | 0.00 | 0.00 | 0.63 | 20-NOV-13:30 | 0.00 | 01-NOV-04:00 | 72916.88 | 20-NOV-13:30 | 72916.88 | 20-NOV-13:30 | 0.00 | 30-NOV-15:15 | 20126.78 | 20-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.399613E+11 | 0.115046E+11 | 408.44 | 0.399613E+11 | -0.0 | 0.00 | 0.62 | 31-DEC-13:50 | 0.00 | 01-DEC-00:10 | 71695.65 | 31-DEC-13:50 | 71695.65 | 31-DEC-13:50 | 0.00 | 27-DEC-16:00 | 19820.84 | 31-DEC-13:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.622256E+12 | 0.186392E+12 | 6956.14 | 0.613401E+12 | 0.885586E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.365359E+11 | 0.105479E+11 | 396.43 | 0.365359E+11 | -0.0 | 0.00 | 0.40 | 0.00 | 43269.15 | 43269.15 | 0.00 | 13727.45 | 0.00 | |||||||
Maximum of Months | 0.751852E+11 | 0.233305E+11 | 744.00 | 0.721954E+11 | 0.318542E+10 | 0.00 | 0.65 | 0.02 | 76594.58 | 76594.58 | 5771.61 | 22777.25 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.331729E+10 | 0.976753E+09 | 118.47 | 0.331564E+10 | 1648107.09 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 119647.42 | 01-JAN-16:12 | 119647.42 | 04-JAN-16:12 | 574.05 | 20-JAN-19:02 | 30978.73 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.684126E+10 | 0.200952E+10 | 162.05 | 0.682118E+10 | 20078973.92 | 0.00 | 1.00 | 08-FEB-19:02 | 0.00 | 01-FEB-00:05 | 119647.42 | 17-FEB-16:12 | 119647.42 | 15-FEB-19:02 | 4989.79 | 17-FEB-09:02 | 30978.73 | 08-FEB-19:02 | 0.00 | 01-FEB-00:05 |
March | 0.186289E+11 | 0.544116E+10 | 344.30 | 0.184706E+11 | 0.158319E+09 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 119647.42 | 02-MAR-19:02 | 119647.42 | 02-MAR-16:12 | 8076.30 | 29-MAR-08:62 | 30978.73 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 |
April | 0.375111E+11 | 0.108461E+11 | 471.77 | 0.373441E+11 | 0.167014E+09 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-04:40 | 121546.02 | 14-APR-21:51 | 121546.02 | 14-APR-21:51 | 9594.34 | 15-APR-08:03 | 31495.42 | 14-APR-21:51 | 0.00 | 01-APR-00:10 |
May | 0.621358E+11 | 0.179324E+11 | 548.98 | 0.592363E+11 | 0.289946E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-06:52 | 132377.98 | 24-MAY-19:41 | 124399.43 | 26-MAY-19:31 | 36893.54 | 24-MAY-19:46 | 34202.22 | 24-MAY-19:41 | 0.00 | 01-MAY-00:10 |
June | 0.921486E+11 | 0.277474E+11 | 575.74 | 0.863878E+11 | 0.576079E+10 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-06:42 | 135764.83 | 05-JUN-21:51 | 124148.37 | 23-JUN-08:51 | 42065.09 | 05-JUN-21:57 | 36864.27 | 29-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.115161E+12 | 0.345224E+11 | 588.80 | 0.990162E+11 | 0.161447E+11 | 0.00 | 1.00 | 01-JUL-08:51 | 0.00 | 01-JUL-05:13 | 147095.95 | 31-JUL-20:11 | 119196.58 | 21-JUL-07:11 | 60909.80 | 01-JUL-08:54 | 37464.71 | 22-JUL-15:12 | 0.00 | 01-JUL-00:10 |
August | 0.103769E+12 | 0.305718E+11 | 570.13 | 0.890691E+11 | 0.146996E+11 | 0.00 | 1.00 | 01-AUG-08:31 | 0.00 | 01-AUG-05:12 | 143986.29 | 13-AUG-08:51 | 119075.05 | 30-AUG-21:51 | 57129.22 | 26-AUG-08:54 | 36690.81 | 13-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.714767E+11 | 0.206181E+11 | 510.12 | 0.624071E+11 | 0.906965E+10 | 0.00 | 1.00 | 01-SEP-08:51 | 0.00 | 01-SEP-05:13 | 139614.30 | 05-SEP-21:51 | 124687.34 | 11-SEP-20:11 | 51173.89 | 05-SEP-21:57 | 35801.51 | 05-SEP-21:51 | 0.00 | 01-SEP-00:10 |
October | 0.368307E+11 | 0.106444E+11 | 429.28 | 0.340901E+11 | 0.274065E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 137610.57 | 02-OCT-21:51 | 122186.10 | 06-OCT-21:51 | 43351.10 | 02-OCT-21:57 | 35374.74 | 02-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.121943E+11 | 0.358640E+10 | 272.70 | 0.119316E+11 | 0.262683E+09 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-06:52 | 119862.56 | 02-NOV-18:11 | 119647.42 | 03-NOV-15:12 | 8606.94 | 02-NOV-08:62 | 31037.88 | 02-NOV-18:11 | 0.00 | 01-NOV-00:10 |
December | 0.223757E+10 | 0.660533E+09 | 92.18 | 0.223501E+10 | 2559161.01 | 0.00 | 1.00 | 01-DEC-16:12 | 0.00 | 01-DEC-00:20 | 119647.42 | 01-DEC-16:12 | 119647.42 | 01-DEC-16:12 | 2123.23 | 25-DEC-19:02 | 30978.73 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.562252E+12 | 0.165557E+12 | 4684.52 | 0.510325E+12 | 0.519272E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.223757E+10 | 0.660533E+09 | 92.18 | 0.223501E+10 | 1648107.09 | 0.00 | 1.00 | 0.00 | 119647.42 | 119075.05 | 574.05 | 30978.73 | 0.00 | |||||||
Maximum of Months | 0.115161E+12 | 0.345224E+11 | 588.80 | 0.990162E+11 | 0.161447E+11 | 0.00 | 1.00 | 0.00 | 147095.95 | 124687.34 | 60909.80 | 37464.71 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.256169E+10 | 0.750728E+09 | 279.87 | 0.255874E+10 | 2949432.21 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 19666.34 | 03-JAN-09:02 | 19666.34 | 08-JAN-16:12 | 289.60 | 29-JAN-09:15 | 5091.95 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.313950E+10 | 0.918388E+09 | 328.61 | 0.312993E+10 | 9572149.88 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-00:05 | 19666.34 | 09-FEB-16:12 | 19666.34 | 07-FEB-09:02 | 634.29 | 17-FEB-09:02 | 5091.95 | 01-FEB-16:12 | 0.00 | 01-FEB-00:05 |
March | 0.533109E+10 | 0.155354E+10 | 500.55 | 0.530457E+10 | 26527502.72 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 19985.60 | 29-MAR-08:62 | 19666.34 | 02-MAR-09:02 | 1615.99 | 29-MAR-08:62 | 5178.72 | 29-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.886034E+10 | 0.257313E+10 | 644.77 | 0.883664E+10 | 23703537.92 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-04:10 | 20088.06 | 15-APR-08:62 | 19666.34 | 03-APR-15:12 | 1607.19 | 15-APR-08:62 | 5206.09 | 15-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.109775E+11 | 0.321094E+10 | 710.67 | 0.105858E+11 | 0.391658E+09 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-06:52 | 21692.07 | 24-MAY-18:02 | 19677.96 | 26-MAY-18:01 | 6018.40 | 24-MAY-18:02 | 5606.24 | 24-MAY-18:02 | 0.00 | 01-MAY-00:10 |
June | 0.146159E+11 | 0.447572E+10 | 706.82 | 0.138620E+11 | 0.753943E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:52 | 21495.72 | 08-JUN-08:62 | 19736.60 | 10-JUN-18:01 | 5770.12 | 08-JUN-08:62 | 5997.72 | 29-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.179358E+11 | 0.550209E+10 | 736.56 | 0.159232E+11 | 0.201259E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:53 | 22463.25 | 01-JUL-08:62 | 18710.10 | 05-JUL-08:62 | 8076.16 | 01-JUL-08:62 | 6100.55 | 22-JUL-15:12 | 0.00 | 01-JUL-00:10 |
August | 0.173184E+11 | 0.520623E+10 | 735.88 | 0.153910E+11 | 0.192735E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 21901.15 | 23-AUG-08:62 | 18696.16 | 20-AUG-08:62 | 6457.39 | 23-AUG-08:62 | 5892.14 | 01-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.135524E+11 | 0.397818E+10 | 704.27 | 0.123321E+11 | 0.122031E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:52 | 21803.34 | 06-SEP-08:62 | 19668.80 | 26-SEP-18:02 | 6349.21 | 06-SEP-08:62 | 5655.81 | 02-SEP-15:12 | 0.00 | 01-SEP-00:10 |
October | 0.908824E+10 | 0.264176E+10 | 630.42 | 0.870413E+10 | 0.384105E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 21577.97 | 11-OCT-08:62 | 19703.09 | 11-OCT-18:02 | 5605.53 | 11-OCT-08:62 | 5579.47 | 11-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.420273E+10 | 0.122999E+10 | 446.26 | 0.416078E+10 | 41951355.91 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-06:52 | 19984.40 | 09-NOV-09:02 | 19666.34 | 07-NOV-16:12 | 1251.50 | 09-NOV-09:02 | 5178.40 | 09-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.233055E+10 | 0.684870E+09 | 301.40 | 0.232884E+10 | 1707686.20 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 19666.34 | 01-DEC-09:02 | 19666.34 | 15-DEC-16:12 | 249.16 | 26-DEC-19:03 | 5091.95 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.109914E+12 | 0.327256E+11 | 6726.07 | 0.103118E+12 | 0.679637E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.233055E+10 | 0.684870E+09 | 279.87 | 0.232884E+10 | 1707686.20 | 0.00 | 1.00 | 0.00 | 19666.34 | 18696.16 | 249.16 | 5091.95 | 0.00 | |||||||
Maximum of Months | 0.179358E+11 | 0.550209E+10 | 736.56 | 0.159232E+11 | 0.201259E+10 | 0.00 | 1.00 | 0.00 | 22463.25 | 19736.60 | 8076.16 | 6100.55 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.611462E+09 | 0.179917E+09 | 101.09 | 0.609592E+09 | 1870755.11 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 19474.67 | 01-JAN-09:02 | 19474.67 | 01-JAN-09:02 | 243.93 | 29-JAN-09:15 | 5042.32 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.110175E+10 | 0.324324E+09 | 187.65 | 0.109457E+10 | 7181644.77 | 0.00 | 1.00 | 02-FEB-09:02 | 0.00 | 01-FEB-00:05 | 19474.67 | 13-FEB-09:02 | 19474.67 | 02-FEB-09:02 | 462.87 | 19-FEB-09:15 | 5042.32 | 02-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.301845E+10 | 0.885620E+09 | 419.01 | 0.299387E+10 | 24572382.05 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 19803.66 | 29-MAR-08:62 | 19474.67 | 01-MAR-16:12 | 1646.69 | 29-MAR-08:62 | 5131.69 | 29-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.652003E+10 | 0.189564E+10 | 531.65 | 0.649263E+10 | 27397102.14 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:20 | 20208.14 | 14-APR-21:51 | 20208.14 | 14-APR-21:51 | 1518.80 | 15-APR-08:62 | 5238.31 | 14-APR-21:51 | 0.00 | 01-APR-00:10 |
May | 0.921965E+10 | 0.269301E+10 | 590.77 | 0.887824E+10 | 0.341413E+09 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-06:52 | 21940.39 | 24-MAY-19:41 | 21206.61 | 19-MAY-08:32 | 6068.43 | 24-MAY-19:42 | 5656.91 | 24-MAY-19:41 | 0.00 | 01-MAY-00:10 |
June | 0.132039E+11 | 0.406456E+10 | 604.42 | 0.125098E+11 | 0.694106E+09 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-06:42 | 22968.51 | 24-JUN-08:32 | 21480.46 | 17-JUN-08:62 | 6704.38 | 05-JUN-21:53 | 5941.08 | 29-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.158888E+11 | 0.489939E+10 | 619.42 | 0.141214E+11 | 0.176744E+10 | 0.00 | 1.00 | 01-JUL-08:51 | 0.00 | 01-JUL-05:13 | 24594.95 | 09-JUL-08:22 | 20958.17 | 22-JUL-07:12 | 9571.26 | 15-JUL-21:54 | 6188.08 | 09-JUL-08:22 | 0.00 | 01-JUL-00:10 |
August | 0.144462E+11 | 0.436127E+10 | 602.52 | 0.127996E+11 | 0.164657E+10 | 0.00 | 1.00 | 01-AUG-08:31 | 0.00 | 01-AUG-05:12 | 24366.41 | 26-AUG-08:32 | 20746.44 | 02-AUG-08:62 | 8308.52 | 26-AUG-08:54 | 6147.38 | 26-AUG-08:32 | 0.00 | 01-AUG-00:10 |
September | 0.977782E+10 | 0.287954E+10 | 544.81 | 0.876455E+10 | 0.101326E+10 | 0.00 | 1.00 | 01-SEP-08:32 | 0.00 | 01-SEP-05:13 | 22851.17 | 05-SEP-21:51 | 20864.45 | 13-SEP-08:32 | 8324.66 | 05-SEP-21:53 | 5853.73 | 05-SEP-21:51 | 0.00 | 01-SEP-00:10 |
October | 0.524632E+10 | 0.153609E+10 | 486.63 | 0.492747E+10 | 0.318843E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 22926.73 | 02-OCT-21:51 | 20039.65 | 06-OCT-21:51 | 7661.30 | 02-OCT-21:53 | 5869.37 | 02-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.164580E+10 | 0.485060E+09 | 289.60 | 0.161350E+10 | 32301790.75 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-06:52 | 20070.05 | 02-NOV-18:11 | 19474.67 | 07-NOV-16:12 | 1724.77 | 02-NOV-18:11 | 5202.31 | 02-NOV-18:11 | 0.00 | 01-NOV-00:10 |
December | 0.439803E+09 | 0.129989E+09 | 84.14 | 0.439057E+09 | 746022.11 | 0.00 | 1.00 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 | 19474.67 | 10-DEC-09:02 | 19474.67 | 12-DEC-09:02 | 189.57 | 25-DEC-19:04 | 5042.32 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.811200E+11 | 0.243344E+11 | 5061.70 | 0.752443E+11 | 0.587570E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.439803E+09 | 0.129989E+09 | 84.14 | 0.439057E+09 | 746022.11 | 0.00 | 1.00 | 0.00 | 19474.67 | 19474.67 | 189.57 | 5042.32 | 0.00 | |||||||
Maximum of Months | 0.158888E+11 | 0.489939E+10 | 619.42 | 0.141214E+11 | 0.176744E+10 | 0.00 | 1.00 | 0.00 | 24594.95 | 21480.46 | 9571.26 | 6188.08 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.518559E+09 | 0.151892E+09 | 183.45 | 0.518336E+09 | 223629.32 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 6230.76 | 21-JAN-16:12 | 6230.76 | 02-JAN-16:12 | 57.79 | 13-JAN-09:04 | 1613.25 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.722897E+09 | 0.210405E+09 | 233.50 | 0.721786E+09 | 1110832.38 | 0.00 | 1.00 | 02-FEB-16:12 | 0.00 | 01-FEB-00:05 | 6230.76 | 15-FEB-16:12 | 6230.76 | 15-FEB-16:12 | 117.09 | 17-FEB-16:17 | 1613.25 | 02-FEB-16:12 | 0.00 | 01-FEB-00:05 |
March | 0.112494E+10 | 0.326867E+09 | 362.30 | 0.112256E+10 | 2372928.75 | 0.00 | 1.00 | 04-MAR-16:12 | 0.00 | 01-MAR-00:10 | 6230.76 | 23-MAR-15:12 | 6230.76 | 12-MAR-18:02 | 185.21 | 20-MAR-18:02 | 1613.25 | 04-MAR-16:12 | 0.00 | 01-MAR-00:10 |
April | 0.200155E+10 | 0.581919E+09 | 542.63 | 0.199747E+10 | 4075506.76 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-00:10 | 6230.76 | 12-APR-18:02 | 6230.76 | 04-APR-18:02 | 902.35 | 15-APR-08:62 | 1636.57 | 29-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.259491E+10 | 0.766042E+09 | 641.25 | 0.251261E+10 | 82300987.03 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-06:52 | 6896.00 | 29-MAY-08:62 | 6230.76 | 06-MAY-18:02 | 2028.63 | 29-MAY-08:62 | 1781.65 | 29-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.368588E+10 | 0.115901E+10 | 680.23 | 0.351385E+10 | 0.172030E+09 | 0.00 | 1.00 | 01-JUN-15:12 | 0.00 | 01-JUN-06:52 | 6873.88 | 08-JUN-15:12 | 6251.78 | 09-JUN-15:12 | 1965.53 | 08-JUN-15:12 | 1897.80 | 29-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.457615E+10 | 0.144373E+10 | 723.05 | 0.408951E+10 | 0.486636E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:53 | 7292.72 | 01-JUL-08:62 | 5813.31 | 27-JUL-18:02 | 3010.35 | 01-JUL-08:62 | 1926.82 | 22-JUL-15:12 | 0.00 | 01-JUL-00:10 |
August | 0.444442E+10 | 0.136658E+10 | 716.53 | 0.397859E+10 | 0.465823E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 7247.26 | 26-AUG-08:62 | 5956.30 | 28-AUG-15:12 | 2864.02 | 26-AUG-08:62 | 1859.49 | 26-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.342785E+10 | 0.101989E+10 | 677.53 | 0.313609E+10 | 0.291760E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:52 | 6919.09 | 10-SEP-08:62 | 6230.76 | 26-SEP-18:02 | 2295.49 | 10-SEP-08:62 | 1787.51 | 10-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.219310E+10 | 0.639338E+09 | 535.36 | 0.210534E+10 | 87763016.69 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 6743.21 | 02-OCT-08:62 | 6240.27 | 04-OCT-18:02 | 1891.01 | 11-OCT-08:62 | 1745.47 | 02-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.830928E+09 | 0.243782E+09 | 322.03 | 0.823685E+09 | 7242633.64 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-03:10 | 6277.46 | 02-NOV-18:02 | 6230.76 | 19-NOV-16:12 | 733.93 | 09-NOV-09:02 | 1626.27 | 02-NOV-18:02 | 0.00 | 01-NOV-00:10 |
December | 0.437873E+09 | 0.128980E+09 | 183.26 | 0.437774E+09 | 99103.14 | 0.00 | 1.00 | 02-DEC-16:12 | 0.00 | 01-DEC-00:10 | 6230.76 | 05-DEC-16:12 | 6230.76 | 13-DEC-16:12 | 54.95 | 26-DEC-09:03 | 1613.25 | 02-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.265591E+11 | 0.803843E+10 | 5801.12 | 0.249576E+11 | 0.160144E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.437873E+09 | 0.128980E+09 | 183.26 | 0.437774E+09 | 99103.14 | 0.00 | 1.00 | 0.00 | 6230.76 | 5813.31 | 54.95 | 1613.25 | 0.00 | |||||||
Maximum of Months | 0.457615E+10 | 0.144373E+10 | 723.05 | 0.408951E+10 | 0.486636E+09 | 0.00 | 1.00 | 0.00 | 7292.72 | 6251.78 | 3010.35 | 1926.82 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.139003E+09 | 40899122.13 | 69.64 | 0.138938E+09 | 64784.39 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 6186.83 | 05-JAN-17:01 | 6186.83 | 05-JAN-17:01 | 42.56 | 20-JAN-19:04 | 1602.36 | 05-JAN-17:01 | 0.00 | 01-JAN-00:05 |
February | 0.272927E+09 | 80183894.04 | 121.74 | 0.272248E+09 | 678470.77 | 0.00 | 1.00 | 08-FEB-16:12 | 0.00 | 01-FEB-00:05 | 6210.54 | 15-FEB-18:01 | 6210.54 | 15-FEB-18:01 | 131.26 | 17-FEB-16:15 | 1608.82 | 15-FEB-18:01 | 0.00 | 01-FEB-00:05 |
March | 0.515283E+09 | 0.151466E+09 | 246.70 | 0.512682E+09 | 2600728.08 | 0.00 | 1.00 | 04-MAR-16:12 | 0.00 | 01-MAR-00:10 | 6345.82 | 07-MAR-19:31 | 6345.82 | 07-MAR-19:31 | 165.73 | 29-MAR-08:03 | 1644.89 | 07-MAR-19:31 | 0.00 | 01-MAR-00:10 |
April | 0.132615E+10 | 0.387833E+09 | 435.51 | 0.132049E+10 | 5657844.75 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-00:10 | 6404.11 | 14-APR-21:51 | 6404.11 | 14-APR-21:51 | 869.73 | 15-APR-08:62 | 1660.05 | 14-APR-21:51 | 0.00 | 01-APR-00:10 |
May | 0.217824E+10 | 0.643658E+09 | 536.20 | 0.210627E+10 | 71969977.58 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-06:52 | 6963.91 | 24-MAY-19:41 | 6646.99 | 26-MAY-17:42 | 1929.89 | 24-MAY-19:42 | 1794.62 | 24-MAY-19:41 | 0.00 | 01-MAY-00:10 |
June | 0.346405E+10 | 0.109169E+10 | 587.83 | 0.330450E+10 | 0.159553E+09 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-06:42 | 7051.24 | 24-JUN-08:51 | 6456.59 | 15-JUN-21:51 | 2048.74 | 08-JUN-08:51 | 1876.06 | 29-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.421508E+10 | 0.133289E+10 | 608.13 | 0.378724E+10 | 0.427846E+09 | 0.00 | 1.00 | 01-JUL-08:51 | 0.00 | 01-JUL-05:13 | 7584.25 | 01-JUL-08:51 | 6196.62 | 29-JUL-21:51 | 3208.32 | 01-JUL-08:53 | 1921.72 | 01-JUL-08:51 | 0.00 | 01-JUL-00:10 |
August | 0.386788E+10 | 0.119315E+10 | 593.26 | 0.347038E+10 | 0.397501E+09 | 0.00 | 1.00 | 01-AUG-08:31 | 0.00 | 01-AUG-05:12 | 7557.55 | 26-AUG-08:51 | 6656.02 | 23-AUG-16:51 | 3123.41 | 26-AUG-08:53 | 1916.70 | 26-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.256321E+10 | 0.766047E+09 | 528.84 | 0.231977E+10 | 0.243441E+09 | 0.00 | 1.00 | 01-SEP-08:51 | 0.00 | 01-SEP-05:13 | 7225.02 | 05-SEP-21:51 | 6444.45 | 19-SEP-21:51 | 2644.17 | 06-SEP-08:52 | 1850.85 | 05-SEP-21:51 | 0.00 | 01-SEP-00:10 |
October | 0.116618E+10 | 0.344569E+09 | 385.40 | 0.109182E+10 | 74363806.00 | 0.00 | 1.00 | 01-OCT-15:12 | 0.00 | 01-OCT-06:52 | 7166.01 | 02-OCT-21:51 | 6433.08 | 19-OCT-21:41 | 2245.73 | 02-OCT-21:53 | 1838.49 | 02-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.286944E+09 | 84656235.63 | 168.75 | 0.282021E+09 | 4923497.58 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-04:00 | 6566.62 | 02-NOV-18:11 | 6225.09 | 02-NOV-18:11 | 561.53 | 02-NOV-18:12 | 1701.16 | 02-NOV-18:11 | 0.00 | 01-NOV-00:10 |
December | 80366453.47 | 23620302.68 | 55.37 | 80297610.52 | 68842.95 | 0.00 | 0.99 | 31-DEC-16:12 | 0.00 | 01-DEC-00:10 | 6057.50 | 31-DEC-16:12 | 6057.50 | 31-DEC-16:12 | 40.92 | 25-DEC-09:04 | 1572.24 | 31-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.200753E+11 | 0.614067E+10 | 4337.38 | 0.186867E+11 | 0.138867E+10 | 0.00 | ||||||||||||||
Minimum of Months | 80366453.47 | 23620302.68 | 55.37 | 80297610.52 | 64784.39 | 0.00 | 0.99 | 0.00 | 6057.50 | 6057.50 | 40.92 | 1572.24 | 0.00 | |||||||
Maximum of Months | 0.421508E+10 | 0.133289E+10 | 608.13 | 0.378724E+10 | 0.427846E+09 | 0.00 | 1.00 | 0.00 | 7584.25 | 6656.02 | 3208.32 | 1921.72 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.756269E+10 | 0.215334E+10 | 314.89 | 0.755119E+10 | 11503045.13 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 26075.12 | 25-JAN-16:12 | 26075.12 | 01-JAN-09:02 | 553.00 | 20-JAN-16:17 | 6751.29 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.759892E+10 | 0.217242E+10 | 333.80 | 0.757759E+10 | 21336137.17 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-00:05 | 26215.09 | 21-FEB-16:12 | 26075.12 | 09-FEB-19:02 | 1067.39 | 21-FEB-16:12 | 6789.66 | 21-FEB-16:12 | 0.00 | 01-FEB-00:05 |
March | 0.800648E+10 | 0.230505E+10 | 432.23 | 0.797422E+10 | 32262741.72 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 26075.12 | 05-MAR-16:12 | 26075.12 | 08-MAR-16:12 | 2017.40 | 28-MAR-18:02 | 6751.29 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 |
April | 0.988888E+10 | 0.287380E+10 | 559.54 | 0.985878E+10 | 30099388.27 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-00:10 | 27120.28 | 15-APR-08:62 | 26075.12 | 04-APR-15:12 | 3708.66 | 15-APR-08:62 | 7030.03 | 15-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.115842E+11 | 0.342048E+10 | 645.99 | 0.110953E+11 | 0.488900E+09 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-06:52 | 28680.19 | 24-MAY-15:12 | 26075.12 | 10-MAY-08:62 | 8376.93 | 24-MAY-15:12 | 7414.26 | 24-MAY-15:12 | 0.00 | 01-MAY-00:10 |
June | 0.161483E+11 | 0.504873E+10 | 681.11 | 0.151298E+11 | 0.101855E+10 | 0.00 | 1.00 | 01-JUN-15:12 | 0.00 | 01-JUN-06:52 | 28816.06 | 08-JUN-15:12 | 26111.75 | 21-JUN-08:62 | 8407.48 | 08-JUN-15:12 | 7989.11 | 29-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.221051E+11 | 0.687458E+10 | 721.79 | 0.192209E+11 | 0.288417E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:53 | 30498.45 | 01-JUL-08:62 | 24073.68 | 27-JUL-18:02 | 12704.14 | 01-JUL-08:62 | 8111.15 | 22-JUL-15:12 | 0.00 | 01-JUL-00:10 |
August | 0.225669E+11 | 0.684418E+10 | 716.06 | 0.197734E+11 | 0.279353E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 30215.07 | 26-AUG-08:62 | 24599.33 | 15-AUG-18:02 | 11795.87 | 26-AUG-08:62 | 7835.69 | 01-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.196393E+11 | 0.574774E+10 | 681.24 | 0.178294E+11 | 0.180993E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:52 | 29380.83 | 06-SEP-08:62 | 26075.12 | 26-SEP-18:02 | 11271.21 | 06-SEP-08:62 | 7575.15 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.154139E+11 | 0.440394E+10 | 592.38 | 0.148358E+11 | 0.578171E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 28897.36 | 11-OCT-08:62 | 26144.36 | 09-OCT-15:12 | 9264.37 | 11-OCT-08:62 | 7464.88 | 11-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.978888E+10 | 0.279495E+10 | 436.77 | 0.971559E+10 | 73286889.39 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-06:52 | 26741.80 | 01-NOV-08:62 | 26075.12 | 15-NOV-09:02 | 3039.73 | 01-NOV-08:62 | 6931.15 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.804112E+10 | 0.229821E+10 | 323.29 | 0.803449E+10 | 6621524.05 | 0.00 | 1.00 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 | 26075.12 | 06-DEC-16:12 | 26075.12 | 06-DEC-16:12 | 686.13 | 26-DEC-19:03 | 6751.29 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.158345E+12 | 0.469374E+11 | 6439.09 | 0.148596E+12 | 0.974836E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.756269E+10 | 0.215334E+10 | 314.89 | 0.755119E+10 | 6621524.05 | 0.00 | 1.00 | 0.00 | 26075.12 | 24073.68 | 553.00 | 6751.29 | 0.00 | |||||||
Maximum of Months | 0.225669E+11 | 0.687458E+10 | 721.79 | 0.197734E+11 | 0.288417E+10 | 0.00 | 1.00 | 0.00 | 30498.45 | 26144.36 | 12704.14 | 8111.15 | 0.00 |
Report: DXReportMonthly
For: PTAC_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.500286E+10 | 0.148026E+10 | 401.80 | 0.337114E+10 | 0.163171E+10 | 0.00 | 0.31 | 01-JAN-13:00 | 0.00 | 01-JAN-02:40 | 9331.80 | 01-JAN-13:00 | 7723.01 | 03-JAN-16:10 | 4432.27 | 29-JAN-10:53 | 2711.67 | 01-JAN-13:00 | 0.00 | 01-JAN-00:05 |
February | 0.617970E+10 | 0.182567E+10 | 445.43 | 0.434650E+10 | 0.183320E+10 | 0.00 | 0.38 | 14-FEB-16:10 | 0.00 | 01-FEB-00:05 | 11030.23 | 14-FEB-16:10 | 11030.23 | 14-FEB-16:10 | 4058.69 | 17-FEB-13:30 | 3166.11 | 14-FEB-16:10 | 0.00 | 01-FEB-00:05 |
March | 0.983403E+10 | 0.290644E+10 | 660.79 | 0.774993E+10 | 0.208409E+10 | 0.00 | 0.36 | 08-MAR-14:00 | 0.00 | 01-MAR-03:50 | 10630.57 | 08-MAR-14:00 | 9970.10 | 08-MAR-14:00 | 3619.79 | 04-MAR-12:10 | 3066.51 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.140113E+11 | 0.412702E+10 | 715.43 | 0.124403E+11 | 0.157099E+10 | 0.00 | 0.40 | 11-APR-18:15 | 0.00 | 01-APR-06:10 | 11527.45 | 11-APR-18:15 | 11527.45 | 11-APR-18:15 | 2253.90 | 08-APR-11:40 | 3321.23 | 13-APR-18:03 | 0.00 | 01-APR-00:10 |
May | 0.177409E+11 | 0.526018E+10 | 744.00 | 0.153828E+11 | 0.235809E+10 | 0.00 | 0.50 | 19-MAY-18:15 | 0.01 | 05-MAY-06:05 | 14286.76 | 19-MAY-18:15 | 14286.76 | 19-MAY-18:15 | 2917.85 | 29-MAY-06:52 | 4454.30 | 19-MAY-18:03 | 0.00 | 01-MAY-00:10 |
June | 0.243216E+11 | 0.752145E+10 | 720.00 | 0.213534E+11 | 0.296818E+10 | 0.00 | 0.65 | 23-JUN-18:03 | 0.08 | 09-JUN-04:00 | 17947.58 | 23-JUN-18:03 | 17947.58 | 23-JUN-18:03 | 3188.77 | 24-JUN-07:55 | 6489.10 | 28-JUN-15:35 | 0.00 | 01-JUN-00:10 |
July | 0.309495E+11 | 0.952623E+10 | 744.00 | 0.252195E+11 | 0.573005E+10 | 0.00 | 0.70 | 21-JUL-18:13 | 0.19 | 02-JUL-05:00 | 19590.66 | 21-JUL-18:13 | 19590.66 | 21-JUL-18:13 | 4781.72 | 31-JUL-20:10 | 6851.44 | 21-JUL-18:13 | 0.00 | 01-JUL-00:10 |
August | 0.301031E+11 | 0.909081E+10 | 744.00 | 0.244976E+11 | 0.560543E+10 | 0.00 | 0.60 | 20-AUG-18:03 | 0.14 | 31-AUG-06:10 | 17567.51 | 18-AUG-18:15 | 16885.49 | 20-AUG-18:03 | 4371.55 | 26-AUG-09:53 | 5741.48 | 20-AUG-18:03 | 0.00 | 01-AUG-00:10 |
September | 0.243736E+11 | 0.720010E+10 | 720.00 | 0.200397E+11 | 0.433394E+10 | 0.00 | 0.55 | 03-SEP-13:30 | 0.08 | 09-SEP-06:10 | 16089.89 | 03-SEP-13:30 | 15351.81 | 03-SEP-13:40 | 3759.32 | 10-SEP-09:53 | 5280.57 | 03-SEP-13:30 | 0.00 | 01-SEP-00:10 |
October | 0.169016E+11 | 0.495502E+10 | 703.60 | 0.142372E+11 | 0.266445E+10 | 0.00 | 0.49 | 06-OCT-15:10 | 0.00 | 13-OCT-06:05 | 14551.50 | 02-OCT-15:10 | 14236.41 | 06-OCT-15:10 | 3627.73 | 26-OCT-12:30 | 4349.29 | 06-OCT-15:10 | 0.00 | 01-OCT-00:10 |
November | 0.893838E+10 | 0.264509E+10 | 621.86 | 0.678516E+10 | 0.215322E+10 | 0.00 | 0.36 | 02-NOV-15:10 | 0.00 | 04-NOV-06:05 | 10756.82 | 02-NOV-15:10 | 9172.15 | 02-NOV-15:10 | 4580.36 | 05-NOV-09:53 | 3101.95 | 02-NOV-15:10 | 0.00 | 01-NOV-00:10 |
December | 0.461534E+10 | 0.136999E+10 | 402.33 | 0.292208E+10 | 0.169326E+10 | 0.00 | 0.30 | 30-DEC-13:40 | 0.00 | 01-DEC-06:10 | 8663.45 | 30-DEC-12:40 | 6914.92 | 30-DEC-14:30 | 4051.85 | 11-DEC-12:40 | 2526.40 | 30-DEC-12:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.192972E+12 | 0.579083E+11 | 7623.24 | 0.158345E+12 | 0.346266E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.461534E+10 | 0.136999E+10 | 401.80 | 0.292208E+10 | 0.157099E+10 | 0.00 | 0.30 | 0.00 | 8663.45 | 6914.92 | 2253.90 | 2526.40 | 0.00 | |||||||
Maximum of Months | 0.309495E+11 | 0.952623E+10 | 744.00 | 0.252195E+11 | 0.573005E+10 | 0.00 | 0.70 | 0.19 | 19590.66 | 19590.66 | 4781.72 | 6851.44 | 0.00 |
Report: DXReportMonthly
For: PTAC_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.543378E+09 | 0.162052E+09 | 86.89 | 0.398808E+09 | 0.144570E+09 | 0.00 | 0.22 | 02-JAN-14:05 | 0.00 | 01-JAN-00:05 | 4258.37 | 01-JAN-13:00 | 3365.37 | 01-JAN-14:00 | 1390.69 | 03-JAN-12:50 | 1252.56 | 01-JAN-13:00 | 0.00 | 01-JAN-00:05 |
February | 0.114310E+10 | 0.336965E+09 | 121.96 | 0.891324E+09 | 0.251774E+09 | 0.00 | 0.36 | 14-FEB-13:20 | 0.00 | 01-FEB-00:05 | 6754.45 | 14-FEB-13:10 | 6145.90 | 14-FEB-13:40 | 2015.11 | 18-FEB-12:40 | 1950.38 | 14-FEB-13:10 | 0.00 | 01-FEB-00:05 |
March | 0.274274E+10 | 0.808160E+09 | 299.40 | 0.224168E+10 | 0.501056E+09 | 0.00 | 0.38 | 08-MAR-13:30 | 0.00 | 01-MAR-00:10 | 7238.28 | 08-MAR-13:30 | 6692.29 | 08-MAR-14:00 | 2088.01 | 15-MAR-11:30 | 2081.56 | 08-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 0.623206E+10 | 0.183123E+10 | 531.22 | 0.565543E+10 | 0.576628E+09 | 0.00 | 0.46 | 13-APR-14:10 | 0.00 | 01-APR-00:10 | 8482.89 | 13-APR-13:00 | 8482.89 | 13-APR-13:00 | 2250.14 | 01-APR-10:25 | 2418.67 | 13-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.909477E+10 | 0.269966E+10 | 674.92 | 0.824679E+10 | 0.847975E+09 | 0.00 | 0.51 | 30-MAY-14:30 | 0.00 | 01-MAY-24:00 | 9512.58 | 28-MAY-13:30 | 9395.75 | 30-MAY-14:30 | 1970.68 | 25-MAY-09:30 | 2828.42 | 30-MAY-14:30 | 0.00 | 01-MAY-00:10 |
June | 0.135862E+11 | 0.427220E+10 | 715.00 | 0.125178E+11 | 0.106842E+10 | 0.00 | 0.73 | 28-JUN-15:10 | 0.00 | 09-JUN-01:40 | 12356.92 | 28-JUN-14:10 | 12356.92 | 28-JUN-14:10 | 1768.06 | 03-JUN-08:32 | 4594.53 | 28-JUN-15:10 | 0.00 | 01-JUN-00:10 |
July | 0.172900E+11 | 0.542852E+10 | 744.00 | 0.153451E+11 | 0.194493E+10 | 0.00 | 0.70 | 20-JUL-14:10 | 0.08 | 02-JUL-05:00 | 12154.01 | 20-JUL-14:10 | 12154.01 | 20-JUL-14:10 | 1831.38 | 08-JUL-09:25 | 4451.74 | 21-JUL-14:10 | 0.00 | 01-JUL-00:10 |
August | 0.164607E+11 | 0.504729E+10 | 744.00 | 0.145710E+11 | 0.188968E+10 | 0.00 | 0.68 | 20-AUG-14:00 | 0.04 | 31-AUG-06:10 | 12262.57 | 21-AUG-14:10 | 12099.16 | 20-AUG-14:00 | 2066.87 | 26-AUG-10:03 | 4145.95 | 20-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 0.122809E+11 | 0.365696E+10 | 713.82 | 0.108141E+11 | 0.146681E+10 | 0.00 | 0.65 | 03-SEP-13:30 | 0.00 | 09-SEP-05:00 | 11983.37 | 03-SEP-13:30 | 11780.25 | 03-SEP-13:30 | 2226.51 | 09-SEP-10:25 | 3900.29 | 03-SEP-13:40 | 0.00 | 01-SEP-00:10 |
October | 0.699877E+10 | 0.205580E+10 | 524.31 | 0.614460E+10 | 0.854178E+09 | 0.00 | 0.56 | 01-OCT-13:30 | 0.00 | 05-OCT-06:10 | 10498.83 | 01-OCT-13:10 | 10440.88 | 01-OCT-13:30 | 2646.33 | 23-OCT-10:30 | 3168.32 | 01-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 0.187599E+10 | 0.554146E+09 | 228.57 | 0.139140E+10 | 0.484582E+09 | 0.00 | 0.36 | 02-NOV-13:10 | 0.00 | 01-NOV-01:40 | 7068.81 | 02-NOV-13:00 | 5774.68 | 02-NOV-14:10 | 2578.84 | 22-NOV-11:40 | 2036.48 | 02-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.256456E+09 | 76312713.80 | 57.06 | 0.173399E+09 | 83056765.39 | 0.00 | 0.24 | 02-DEC-13:00 | 0.00 | 01-DEC-00:10 | 5032.56 | 02-DEC-12:50 | 3174.35 | 02-DEC-13:40 | 2422.74 | 02-DEC-12:10 | 1462.94 | 02-DEC-12:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.885051E+11 | 0.269293E+11 | 5441.15 | 0.783914E+11 | 0.101137E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.256456E+09 | 76312713.80 | 57.06 | 0.173399E+09 | 83056765.39 | 0.00 | 0.22 | 0.00 | 4258.37 | 3174.35 | 1390.69 | 1252.56 | 0.00 | |||||||
Maximum of Months | 0.172900E+11 | 0.542852E+10 | 744.00 | 0.153451E+11 | 0.194493E+10 | 0.00 | 0.73 | 0.08 | 12356.92 | 12356.92 | 2646.33 | 4594.53 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_1 COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.214940E+09 | 70882107.50 | 15.50 | 0.214940E+09 | 0.00 | 0.00 | 0.17 | 05-JAN-15:20 | 0.00 | 01-JAN-00:05 | 6974.95 | 05-JAN-15:20 | 6974.95 | 05-JAN-15:20 | 0.00 | 03-JAN-16:05 | 2272.72 | 05-JAN-15:20 | 0.00 |
February | 0.160687E+10 | 0.484612E+09 | 32.50 | 0.160687E+10 | 957.09 | 0.00 | 0.79 | 14-FEB-16:10 | 0.00 | 01-FEB-00:05 | 38276.68 | 14-FEB-16:10 | 38276.68 | 14-FEB-16:10 | 1.60 | 19-FEB-16:50 | 10630.60 | 14-FEB-16:10 | 0.00 |
March | 0.560001E+10 | 0.173365E+10 | 133.67 | 0.559835E+10 | 1660018.11 | 0.00 | 0.76 | 08-MAR-16:10 | 0.00 | 01-MAR-00:10 | 36829.24 | 08-MAR-16:10 | 36829.24 | 08-MAR-16:10 | 251.98 | 16-MAR-11:40 | 10298.92 | 08-MAR-16:10 | 0.00 |
April | 0.245166E+11 | 0.710474E+10 | 318.50 | 0.245027E+11 | 13902725.75 | 0.00 | 1.00 | 11-APR-18:02 | 0.00 | 01-APR-00:10 | 58692.08 | 13-APR-18:03 | 58692.08 | 13-APR-18:03 | 1077.83 | 15-APR-01:10 | 15332.38 | 13-APR-18:03 | 0.00 |
May | 0.500120E+11 | 0.140822E+11 | 502.00 | 0.486998E+11 | 0.131229E+10 | 0.00 | 1.00 | 08-MAY-17:03 | 0.00 | 01-MAY-00:10 | 73255.71 | 19-MAY-18:03 | 73255.71 | 19-MAY-18:03 | 9360.52 | 24-MAY-13:00 | 19136.69 | 19-MAY-18:03 | 0.00 |
June | 0.964554E+11 | 0.268712E+11 | 648.50 | 0.937919E+11 | 0.266353E+10 | 0.00 | 1.00 | 03-JUN-17:03 | 0.00 | 01-JUN-04:00 | 92520.77 | 27-JUN-18:03 | 92520.77 | 27-JUN-18:03 | 10295.89 | 23-JUN-24:00 | 28072.80 | 28-JUN-16:00 | 0.00 |
July | 0.141715E+12 | 0.385970E+11 | 744.00 | 0.123687E+12 | 0.180277E+11 | 0.00 | 1.00 | 01-JUL-00:40 | 0.33 | 08-JUL-04:00 | 97679.99 | 21-JUL-18:17 | 97679.99 | 21-JUL-18:17 | 46305.72 | 01-JUL-01:00 | 29215.89 | 21-JUL-18:03 | 0.00 |
August | 0.126806E+12 | 0.344808E+11 | 742.17 | 0.112034E+12 | 0.147724E+11 | 0.00 | 1.00 | 01-AUG-11:20 | 0.00 | 31-AUG-04:40 | 85988.55 | 18-AUG-18:03 | 85988.55 | 18-AUG-18:03 | 28743.14 | 26-AUG-09:53 | 24047.09 | 20-AUG-18:03 | 0.00 |
September | 0.798687E+11 | 0.220287E+11 | 655.17 | 0.729789E+11 | 0.688984E+10 | 0.00 | 1.00 | 01-SEP-12:40 | 0.00 | 08-SEP-05:40 | 75679.14 | 20-SEP-15:10 | 75679.14 | 20-SEP-15:10 | 21971.43 | 05-SEP-12:50 | 20296.67 | 20-SEP-15:10 | 0.00 |
October | 0.314821E+11 | 0.891651E+10 | 348.75 | 0.298753E+11 | 0.160683E+10 | 0.00 | 1.00 | 01-OCT-11:20 | 0.00 | 03-OCT-03:40 | 68074.97 | 06-OCT-15:10 | 68074.97 | 06-OCT-15:10 | 14562.16 | 02-OCT-17:05 | 17776.82 | 06-OCT-15:10 | 0.00 |
November | 0.733623E+09 | 0.237558E+09 | 39.17 | 0.706240E+09 | 27382759.41 | 0.00 | 0.40 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 17455.45 | 09-NOV-14:00 | 17455.45 | 09-NOV-14:00 | 1052.37 | 02-NOV-16:50 | 5375.88 | 09-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.559012E+12 | 0.154608E+12 | 4179.92 | 0.513696E+12 | 0.453155E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.141715E+12 | 0.385970E+11 | 744.00 | 0.123687E+12 | 0.180277E+11 | 0.00 | 1.00 | 0.33 | 97679.99 | 97679.99 | 46305.72 | 29215.89 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_6 COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.185591E+09 | 61205653.57 | 15.83 | 0.185591E+09 | -0.0 | 0.00 | 0.16 | 05-JAN-14:20 | 0.00 | 01-JAN-00:05 | 5610.89 | 05-JAN-14:10 | 5610.89 | 05-JAN-14:10 | 0.00 | 01-JAN-15:00 | 1831.08 | 05-JAN-14:20 | 0.00 |
February | 0.124337E+10 | 0.380461E+09 | 33.17 | 0.124337E+10 | -0.0 | 0.00 | 0.71 | 14-FEB-16:10 | 0.00 | 01-FEB-00:05 | 28102.73 | 14-FEB-16:10 | 28102.73 | 14-FEB-16:10 | 0.00 | 13-FEB-16:45 | 7983.53 | 14-FEB-16:10 | 0.00 |
March | 0.514900E+10 | 0.158707E+10 | 137.11 | 0.514899E+10 | 5402.42 | 0.00 | 0.79 | 08-MAR-16:13 | 0.00 | 01-MAR-00:10 | 32252.56 | 08-MAR-16:13 | 32252.56 | 08-MAR-16:13 | 8.81 | 16-MAR-11:20 | 8948.63 | 08-MAR-16:13 | 0.00 |
April | 0.242403E+11 | 0.688587E+10 | 325.42 | 0.242382E+11 | 2148777.25 | 0.00 | 1.00 | 01-APR-17:03 | 0.00 | 01-APR-00:10 | 51967.14 | 28-APR-18:03 | 51967.14 | 28-APR-18:03 | 331.71 | 15-APR-08:40 | 13573.79 | 28-APR-18:03 | 0.00 |
May | 0.504216E+11 | 0.138914E+11 | 511.17 | 0.497226E+11 | 0.698948E+09 | 0.00 | 1.00 | 07-MAY-18:02 | 0.00 | 01-MAY-00:30 | 67931.39 | 19-MAY-18:03 | 67931.39 | 19-MAY-18:03 | 7931.76 | 24-MAY-15:00 | 17740.25 | 19-MAY-18:03 | 0.00 |
June | 0.963152E+11 | 0.265459E+11 | 652.83 | 0.952230E+11 | 0.109223E+10 | 0.00 | 1.00 | 02-JUN-15:10 | 0.00 | 01-JUN-04:20 | 91150.04 | 28-JUN-16:00 | 91150.04 | 28-JUN-16:00 | 7383.02 | 08-JUN-09:20 | 29409.06 | 28-JUN-16:00 | 0.00 |
July | 0.133194E+12 | 0.360980E+11 | 744.00 | 0.122926E+12 | 0.102684E+11 | 0.00 | 1.00 | 01-JUL-00:40 | 0.42 | 08-JUL-04:00 | 91258.82 | 21-JUL-18:03 | 91258.82 | 21-JUL-18:03 | 43741.92 | 01-JUL-01:00 | 27474.06 | 21-JUL-15:10 | 0.00 |
August | 0.115544E+12 | 0.312702E+11 | 742.33 | 0.107364E+12 | 0.818045E+10 | 0.00 | 1.00 | 01-AUG-09:30 | 0.00 | 31-AUG-04:50 | 79319.59 | 01-AUG-15:40 | 79319.59 | 01-AUG-15:40 | 26379.59 | 26-AUG-09:53 | 23337.76 | 01-AUG-15:40 | 0.00 |
September | 0.690027E+11 | 0.190254E+11 | 661.83 | 0.651070E+11 | 0.389577E+10 | 0.00 | 1.00 | 01-SEP-12:20 | 0.00 | 08-SEP-05:50 | 67826.90 | 02-SEP-17:07 | 67826.90 | 02-SEP-17:07 | 13418.78 | 05-SEP-12:00 | 18331.04 | 02-SEP-17:07 | 0.00 |
October | 0.255052E+11 | 0.728593E+10 | 354.67 | 0.246714E+11 | 0.833842E+09 | 0.00 | 1.00 | 01-OCT-13:00 | 0.00 | 03-OCT-03:50 | 53202.98 | 06-OCT-15:10 | 53202.98 | 06-OCT-15:10 | 9232.19 | 02-OCT-16:51 | 13895.76 | 06-OCT-15:10 | 0.00 |
November | 0.646450E+09 | 0.208942E+09 | 40.31 | 0.638888E+09 | 7562509.85 | 0.00 | 0.44 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 16310.11 | 09-NOV-14:00 | 16310.11 | 09-NOV-14:00 | 424.10 | 02-NOV-16:51 | 4970.95 | 09-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.521447E+12 | 0.143240E+12 | 4218.67 | 0.496468E+12 | 0.249793E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.133194E+12 | 0.360980E+11 | 744.00 | 0.122926E+12 | 0.102684E+11 | 0.00 | 1.00 | 0.42 | 91258.82 | 91258.82 | 43741.92 | 29409.06 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_0 COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 1084031.41 | 356393.38 | 0.83 | 1084031.41 | 0.00 | 0.00 | 0.03 | 14-FEB-16:10 | 0.00 | 01-FEB-00:05 | 722.45 | 14-FEB-16:10 | 722.45 | 14-FEB-16:10 | 0.00 | 14-FEB-15:00 | 237.68 | 14-FEB-16:10 | 0.00 | 01-FEB-00:05 |
March | 206.03 | 67.28 | 0.11 | 206.03 | 0.00 | 0.00 | 0.00 | 15-MAR-18:53 | 0.00 | 01-MAR-00:10 | 0.79 | 15-MAR-18:53 | 0.79 | 15-MAR-18:53 | 0.00 | 15-MAR-18:57 | 0.26 | 15-MAR-18:53 | 0.00 | 01-MAR-00:10 |
April | 0.389870E+10 | 0.118421E+10 | 168.44 | 0.388599E+10 | 12715407.68 | 0.00 | 0.73 | 28-APR-19:10 | 0.00 | 01-APR-00:10 | 18350.34 | 28-APR-19:10 | 18350.34 | 28-APR-19:10 | 1055.10 | 14-APR-20:00 | 5153.59 | 28-APR-18:15 | 0.00 | 01-APR-00:10 |
May | 0.117679E+11 | 0.356214E+10 | 364.17 | 0.113781E+11 | 0.389788E+09 | 0.00 | 0.88 | 19-MAY-18:15 | 0.00 | 01-MAY-00:10 | 22526.62 | 19-MAY-19:20 | 22526.62 | 19-MAY-19:20 | 4500.16 | 27-MAY-20:20 | 6643.20 | 19-MAY-18:03 | 0.00 | 01-MAY-00:10 |
June | 0.295978E+11 | 0.909639E+10 | 579.72 | 0.279181E+11 | 0.167966E+10 | 0.00 | 1.00 | 13-JUN-18:02 | 0.00 | 01-JUN-02:70 | 29708.34 | 27-JUN-18:20 | 29708.34 | 27-JUN-18:20 | 7268.04 | 05-JUN-20:40 | 9652.24 | 27-JUN-18:03 | 0.00 | 01-JUN-00:10 |
July | 0.535509E+11 | 0.155604E+11 | 741.67 | 0.426256E+11 | 0.109253E+11 | 0.00 | 1.00 | 02-JUL-19:10 | 0.00 | 08-JUL-02:40 | 43459.53 | 31-JUL-19:55 | 34236.84 | 21-JUL-19:10 | 21240.84 | 31-JUL-19:55 | 11377.52 | 21-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 0.527526E+11 | 0.149638E+11 | 741.50 | 0.418843E+11 | 0.108684E+11 | 0.00 | 1.00 | 01-AUG-18:02 | 0.00 | 25-AUG-05:00 | 38175.54 | 08-AUG-19:40 | 32384.34 | 17-AUG-19:10 | 17505.11 | 25-AUG-21:00 | 9739.59 | 17-AUG-18:15 | 0.00 | 01-AUG-00:10 |
September | 0.395294E+11 | 0.110150E+11 | 674.33 | 0.322826E+11 | 0.724680E+10 | 0.00 | 1.00 | 01-SEP-18:02 | 0.00 | 08-SEP-23:50 | 34732.42 | 04-SEP-19:35 | 30345.28 | 13-SEP-19:20 | 15632.82 | 05-SEP-20:00 | 8702.15 | 04-SEP-19:12 | 0.00 | 01-SEP-00:10 |
October | 0.181832E+11 | 0.510915E+10 | 442.48 | 0.158200E+11 | 0.236319E+10 | 0.00 | 1.00 | 02-OCT-18:02 | 0.00 | 03-OCT-04:00 | 35000.74 | 02-OCT-19:20 | 26760.70 | 05-OCT-18:10 | 14742.83 | 02-OCT-20:00 | 8526.55 | 02-OCT-19:20 | 0.00 | 01-OCT-00:10 |
November | 0.214290E+10 | 0.655396E+09 | 150.69 | 0.189688E+10 | 0.246018E+09 | 0.00 | 0.53 | 08-NOV-22:00 | 0.00 | 01-NOV-00:10 | 12649.19 | 08-NOV-22:00 | 11094.63 | 02-NOV-19:10 | 3460.41 | 09-NOV-21:00 | 3584.82 | 08-NOV-22:00 | 0.00 | 01-NOV-00:10 |
December | 76836722.47 | 24208319.43 | 12.00 | 73540581.24 | 3296141.22 | 0.00 | 0.22 | 01-DEC-21:00 | 0.00 | 01-DEC-00:10 | 4938.63 | 01-DEC-21:00 | 4692.90 | 01-DEC-21:00 | 245.73 | 01-DEC-21:00 | 1522.21 | 01-DEC-21:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.211501E+12 | 0.611710E+11 | 3875.95 | 0.177766E+12 | 0.337352E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.535509E+11 | 0.155604E+11 | 741.67 | 0.426256E+11 | 0.109253E+11 | 0.00 | 1.00 | 0.00 | 43459.53 | 34236.84 | 21240.84 | 11377.52 | 0.00 |
Report: DXReportMonthly
For: PSZ_LAUNDRY COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 90600.99 | 26266.59 | 65.20 | 90600.99 | 0.00 | 0.00 | 0.00 | 28-JAN-18:05 | 0.00 | 01-JAN-00:05 | 6.04 | 28-JAN-18:05 | 6.04 | 28-JAN-18:05 | 0.00 | 05-JAN-08:35 | 1.75 | 28-JAN-18:05 | 0.00 | 01-JAN-00:05 |
February | 0.261973E+09 | 70427983.12 | 84.42 | 0.261973E+09 | 52.86 | 0.00 | 0.44 | 14-FEB-16:00 | 0.00 | 01-FEB-00:05 | 14635.20 | 14-FEB-16:00 | 14635.20 | 14-FEB-16:00 | 0.30 | 21-FEB-19:02 | 3851.89 | 14-FEB-16:00 | 0.00 | 01-FEB-00:05 |
March | 0.977839E+09 | 0.264871E+09 | 146.88 | 0.977838E+09 | 774.82 | 0.00 | 0.52 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 17713.01 | 08-MAR-14:00 | 17713.01 | 08-MAR-14:00 | 1.17 | 14-MAR-17:03 | 4606.27 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.125110E+11 | 0.314324E+10 | 273.98 | 0.125063E+11 | 4722552.56 | 0.00 | 1.00 | 11-APR-18:02 | 0.00 | 01-APR-02:20 | 43791.44 | 28-APR-19:00 | 43791.44 | 28-APR-19:00 | 555.25 | 14-APR-20:00 | 10160.17 | 28-APR-19:00 | 0.00 | 01-APR-00:10 |
May | 0.262918E+11 | 0.665029E+10 | 401.44 | 0.258729E+11 | 0.418942E+09 | 0.00 | 1.00 | 08-MAY-18:02 | 0.00 | 01-MAY-00:10 | 46474.42 | 19-MAY-20:00 | 46474.42 | 19-MAY-20:00 | 7765.14 | 27-MAY-20:20 | 11388.16 | 19-MAY-19:20 | 0.00 | 01-MAY-00:10 |
June | 0.455896E+11 | 0.121902E+11 | 540.77 | 0.445723E+11 | 0.101732E+10 | 0.00 | 1.00 | 03-JUN-18:15 | 0.00 | 01-JUN-00:10 | 49441.63 | 06-JUN-20:02 | 46944.37 | 27-JUN-20:00 | 10246.30 | 05-JUN-19:45 | 13028.53 | 27-JUN-19:20 | 0.00 | 01-JUN-00:10 |
July | 0.643259E+11 | 0.169506E+11 | 691.17 | 0.572222E+11 | 0.710368E+10 | 0.00 | 1.00 | 01-JUL-17:05 | 0.00 | 01-JUL-04:10 | 72543.79 | 31-JUL-20:00 | 47004.03 | 21-JUL-20:00 | 34920.70 | 31-JUL-20:00 | 16704.95 | 31-JUL-20:00 | 0.00 | 01-JUL-00:10 |
August | 0.576843E+11 | 0.149282E+11 | 651.97 | 0.515232E+11 | 0.616107E+10 | 0.00 | 1.00 | 01-AUG-18:02 | 0.00 | 01-AUG-03:00 | 61260.54 | 08-AUG-19:40 | 46754.93 | 17-AUG-20:00 | 24525.39 | 29-AUG-18:08 | 14427.63 | 08-AUG-19:40 | 0.00 | 01-AUG-00:10 |
September | 0.359791E+11 | 0.914453E+10 | 473.53 | 0.330527E+11 | 0.292640E+10 | 0.00 | 1.00 | 01-SEP-18:02 | 0.00 | 02-SEP-00:40 | 51753.25 | 04-SEP-19:02 | 46366.59 | 13-SEP-20:00 | 15545.03 | 04-SEP-20:00 | 12017.76 | 04-SEP-19:02 | 0.00 | 01-SEP-00:10 |
October | 0.123942E+11 | 0.314759E+10 | 296.24 | 0.116463E+11 | 0.747897E+09 | 0.00 | 1.00 | 02-OCT-19:10 | 0.00 | 01-OCT-00:10 | 42784.59 | 10-OCT-18:02 | 40495.00 | 05-OCT-18:08 | 15124.71 | 02-OCT-19:50 | 9802.51 | 10-OCT-18:02 | 0.00 | 01-OCT-00:10 |
November | 2144362.28 | 618281.13 | 85.36 | 2142476.27 | 1886.01 | 0.00 | 0.03 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 914.79 | 09-NOV-14:00 | 914.79 | 09-NOV-14:00 | 0.32 | 08-NOV-19:02 | 263.20 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 70250.99 | 20366.79 | 54.65 | 70249.84 | 1.16 | 0.00 | 0.00 | 25-DEC-08:63 | 0.00 | 01-DEC-00:10 | 8.83 | 25-DEC-08:63 | 8.83 | 25-DEC-08:63 | 0.01 | 08-DEC-19:02 | 2.56 | 25-DEC-08:63 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.256018E+12 | 0.664905E+11 | 3765.60 | 0.237638E+12 | 0.183800E+11 | 0.00 | ||||||||||||||
Minimum of Months | 70250.99 | 20366.79 | 54.65 | 70249.84 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 6.04 | 0.00 | 1.75 | 0.00 | |||||||
Maximum of Months | 0.643259E+11 | 0.169506E+11 | 691.17 | 0.572222E+11 | 0.710368E+10 | 0.00 | 1.00 | 0.00 | 72543.79 | 47004.03 | 34920.70 | 16704.95 | 0.00 |
Report: DXReportMonthly
For: PSZ_CAFE COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 845595.07 | 251514.58 | 1.50 | 845595.07 | 0.00 | 0.00 | 0.02 | 01-JAN-14:10 | 0.00 | 01-JAN-00:05 | 276.05 | 01-JAN-14:10 | 276.05 | 01-JAN-14:10 | 0.00 | 05-JAN-14:00 | 82.04 | 01-JAN-14:10 | 0.00 | 01-JAN-00:05 |
February | 0.464430E+09 | 0.120452E+09 | 19.12 | 0.464430E+09 | 23.57 | 0.00 | 0.74 | 14-FEB-15:10 | 0.00 | 01-FEB-00:05 | 14895.45 | 14-FEB-15:10 | 14895.45 | 14-FEB-15:10 | 0.04 | 19-FEB-22:40 | 3666.45 | 14-FEB-15:10 | 0.00 | 01-FEB-00:05 |
March | 0.905433E+09 | 0.243973E+09 | 52.33 | 0.905433E+09 | 199.58 | 0.00 | 0.81 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 16452.78 | 08-MAR-14:00 | 16452.78 | 08-MAR-14:00 | 0.33 | 20-MAR-02:20 | 4044.25 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.533413E+10 | 0.140852E+10 | 177.04 | 0.533405E+10 | 76505.03 | 0.00 | 0.88 | 13-APR-15:10 | 0.00 | 01-APR-00:10 | 18262.36 | 13-APR-15:10 | 18262.36 | 13-APR-15:10 | 22.80 | 14-APR-20:00 | 4582.57 | 13-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 0.114475E+11 | 0.307224E+10 | 308.04 | 0.113777E+11 | 69811906.53 | 0.00 | 0.94 | 19-MAY-15:10 | 0.00 | 01-MAY-00:10 | 19366.09 | 19-MAY-15:10 | 19366.09 | 19-MAY-15:10 | 1610.37 | 21-MAY-23:10 | 5319.32 | 19-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 0.250145E+11 | 0.696698E+10 | 492.33 | 0.243274E+11 | 0.687120E+09 | 0.00 | 1.00 | 13-JUN-15:10 | 0.00 | 01-JUN-00:10 | 26744.07 | 28-JUN-15:12 | 26744.07 | 28-JUN-15:12 | 4659.85 | 24-JUN-00:10 | 9274.95 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.378530E+11 | 0.102287E+11 | 680.09 | 0.329096E+11 | 0.494337E+10 | 0.00 | 1.00 | 03-JUL-14:10 | 0.00 | 01-JUL-03:30 | 26584.77 | 22-JUL-14:00 | 26584.77 | 22-JUL-14:00 | 9156.40 | 01-JUL-01:00 | 8895.74 | 21-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 0.333915E+11 | 0.885300E+10 | 623.34 | 0.294553E+11 | 0.393616E+10 | 0.00 | 1.00 | 01-AUG-12:40 | 0.00 | 02-AUG-05:10 | 26339.55 | 21-AUG-14:10 | 25465.03 | 20-AUG-12:00 | 9531.75 | 26-AUG-11:20 | 7768.69 | 20-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 0.200640E+11 | 0.520641E+10 | 414.33 | 0.187168E+11 | 0.134719E+10 | 0.00 | 1.00 | 01-SEP-13:20 | 0.00 | 01-SEP-05:10 | 26860.17 | 05-SEP-12:50 | 26090.75 | 03-SEP-13:30 | 10116.39 | 05-SEP-12:50 | 7396.74 | 03-SEP-13:30 | 0.00 | 01-SEP-00:10 |
October | 0.787464E+10 | 0.202263E+10 | 206.67 | 0.759158E+10 | 0.283065E+09 | 0.00 | 1.00 | 01-OCT-11:30 | 0.00 | 01-OCT-00:10 | 23872.45 | 01-OCT-12:00 | 23439.10 | 01-OCT-13:30 | 3786.23 | 11-OCT-10:50 | 6051.64 | 01-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 9654886.05 | 2799847.86 | 2.02 | 8829977.62 | 824908.43 | 0.00 | 0.17 | 02-NOV-15:05 | 0.00 | 01-NOV-00:10 | 2967.53 | 02-NOV-15:05 | 2745.35 | 02-NOV-15:05 | 222.18 | 02-NOV-15:05 | 847.43 | 02-NOV-15:05 | 0.00 | 01-NOV-00:10 |
December | 25968.41 | 7748.59 | 0.92 | 25968.41 | -0.0 | 0.00 | 0.00 | 01-DEC-20:50 | 0.00 | 01-DEC-00:10 | 20.17 | 01-DEC-20:50 | 20.17 | 01-DEC-20:50 | 0.00 | 01-DEC-00:10 | 6.02 | 01-DEC-20:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.142360E+12 | 0.381260E+11 | 2977.73 | 0.131092E+12 | 0.112676E+11 | 0.00 | ||||||||||||||
Minimum of Months | 25968.41 | 7748.59 | 0.92 | 25968.41 | -0.0 | 0.00 | 0.00 | 0.00 | 20.17 | 20.17 | 0.00 | 6.02 | 0.00 | |||||||
Maximum of Months | 0.378530E+11 | 0.102287E+11 | 680.09 | 0.329096E+11 | 0.494337E+10 | 0.00 | 1.00 | 0.00 | 26860.17 | 26744.07 | 10116.39 | 9274.95 | 0.00 |
Report: DXReportMonthly
For: PSZ_KITCHEN COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 15304085.08 | 4512114.14 | 6.17 | 15304085.08 | 0.00 | 0.00 | 0.10 | 05-JAN-14:00 | 0.00 | 01-JAN-00:05 | 2275.50 | 05-JAN-14:00 | 2275.50 | 05-JAN-14:00 | 0.00 | 05-JAN-16:05 | 662.56 | 05-JAN-14:00 | 0.00 | 01-JAN-00:05 |
February | 0.991441E+09 | 0.256504E+09 | 29.17 | 0.991441E+09 | 0.00 | 0.00 | 0.81 | 14-FEB-16:12 | 0.00 | 01-FEB-00:05 | 23211.41 | 14-FEB-16:12 | 23211.41 | 14-FEB-16:12 | 0.00 | 14-FEB-15:50 | 5598.56 | 14-FEB-16:05 | 0.00 | 01-FEB-00:05 |
March | 0.401693E+10 | 0.105292E+10 | 123.50 | 0.401628E+10 | 654357.55 | 0.00 | 0.89 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 | 25792.55 | 08-MAR-14:00 | 25792.55 | 08-MAR-14:00 | 213.94 | 16-MAR-11:50 | 6175.65 | 08-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.176546E+11 | 0.436884E+10 | 282.17 | 0.171155E+11 | 0.539078E+09 | 0.00 | 1.00 | 01-APR-14:50 | 0.00 | 01-APR-00:10 | 42070.89 | 11-APR-17:20 | 33803.54 | 13-APR-17:20 | 9041.52 | 11-APR-17:20 | 10152.04 | 11-APR-17:20 | 0.00 | 01-APR-00:10 |
May | 0.343969E+11 | 0.855643E+10 | 419.67 | 0.314285E+11 | 0.296837E+10 | 0.00 | 1.00 | 07-MAY-15:10 | 0.00 | 01-MAY-00:10 | 45092.48 | 23-MAY-10:40 | 36486.08 | 19-MAY-10:40 | 11026.83 | 29-MAY-17:20 | 11912.32 | 19-MAY-17:20 | 0.00 | 01-MAY-00:10 |
June | 0.585737E+11 | 0.155100E+11 | 559.08 | 0.510301E+11 | 0.754366E+10 | 0.00 | 1.00 | 02-JUN-15:00 | 0.00 | 01-JUN-00:10 | 50499.60 | 25-JUN-10:40 | 40409.82 | 29-JUN-10:50 | 13967.21 | 24-JUN-09:10 | 14933.64 | 27-JUN-17:20 | 0.00 | 01-JUN-00:10 |
July | 0.828596E+11 | 0.218080E+11 | 710.33 | 0.638915E+11 | 0.189681E+11 | 0.00 | 1.00 | 01-JUL-09:15 | 0.00 | 01-JUL-03:30 | 57295.48 | 01-JUL-10:50 | 41202.15 | 22-JUL-10:50 | 25729.92 | 01-JUL-10:50 | 15124.91 | 21-JUL-17:20 | 0.00 | 01-JUL-00:10 |
August | 0.743055E+11 | 0.191390E+11 | 675.33 | 0.578681E+11 | 0.164375E+11 | 0.00 | 1.00 | 01-AUG-07:15 | 0.00 | 03-AUG-02:50 | 56768.63 | 26-AUG-10:40 | 39923.77 | 20-AUG-10:50 | 27881.59 | 26-AUG-09:51 | 14071.47 | 21-AUG-17:20 | 0.00 | 01-AUG-00:10 |
September | 0.485413E+11 | 0.121078E+11 | 511.50 | 0.397535E+11 | 0.878780E+10 | 0.00 | 1.00 | 01-SEP-08:50 | 0.00 | 02-SEP-01:00 | 49710.85 | 03-SEP-10:40 | 38963.43 | 03-SEP-10:40 | 18932.45 | 05-SEP-12:00 | 13182.00 | 03-SEP-10:40 | 0.00 | 01-SEP-00:10 |
October | 0.188848E+11 | 0.469806E+10 | 283.00 | 0.168353E+11 | 0.204951E+10 | 0.00 | 1.00 | 01-OCT-10:40 | 0.00 | 01-OCT-00:10 | 44080.41 | 10-OCT-17:15 | 34273.19 | 02-OCT-10:50 | 13193.41 | 02-OCT-17:20 | 10887.68 | 01-OCT-15:40 | 0.00 | 01-OCT-00:10 |
November | 0.252113E+09 | 70345995.97 | 19.67 | 0.236778E+09 | 15334918.02 | 0.00 | 0.46 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 | 11862.70 | 09-NOV-14:00 | 11862.70 | 09-NOV-14:00 | 969.46 | 02-NOV-16:20 | 3132.48 | 09-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 43854.75 | 13084.01 | 0.50 | 43854.75 | -0.0 | 0.00 | 0.00 | 20-DEC-03:50 | 0.00 | 01-DEC-00:10 | 35.74 | 20-DEC-03:50 | 35.74 | 20-DEC-03:50 | 0.00 | 01-DEC-00:10 | 10.66 | 20-DEC-03:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.340492E+12 | 0.875724E+11 | 3620.08 | 0.283182E+12 | 0.573100E+11 | 0.00 | ||||||||||||||
Minimum of Months | 43854.75 | 13084.01 | 0.50 | 43854.75 | -0.0 | 0.00 | 0.00 | 0.00 | 35.74 | 35.74 | 0.00 | 10.66 | 0.00 | |||||||
Maximum of Months | 0.828596E+11 | 0.218080E+11 | 710.33 | 0.638915E+11 | 0.189681E+11 | 0.00 | 1.00 | 0.00 | 57295.48 | 41202.15 | 27881.59 | 15124.91 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1320.63 | 1027.01 | 293.62 | 1419.20 | 782.75 | 0.00 | 0.00 | 0.00 |
February | 1301.76 | 952.71 | 349.05 | 1426.59 | 724.03 | 0.00 | 0.00 | 0.00 |
March | 967.98 | 590.67 | 377.31 | 1082.28 | 578.22 | 0.00 | 0.00 | 0.00 |
April | 743.41 | 304.66 | 438.75 | 859.69 | 403.01 | 0.00 | 0.00 | 0.00 |
May | 500.32 | 113.19 | 387.14 | 589.60 | 287.05 | 0.00 | 0.00 | 0.00 |
June | 418.26 | 50.22 | 368.03 | 608.74 | 182.78 | 0.00 | 0.00 | 0.00 |
July | 462.98 | 72.65 | 390.34 | 745.71 | 111.51 | 0.00 | 0.00 | 0.00 |
August | 629.81 | 198.64 | 431.17 | 953.29 | 135.82 | 0.00 | 0.00 | 0.00 |
September | 894.10 | 503.30 | 390.80 | 1241.79 | 245.22 | 0.00 | 0.00 | 0.00 |
October | 1204.57 | 886.06 | 318.51 | 1476.75 | 430.69 | 0.00 | 0.00 | 0.00 |
November | 1358.79 | 1045.75 | 313.04 | 1509.72 | 621.90 | 0.00 | 0.00 | 0.00 |
December | 1440.16 | 1188.84 | 251.33 | 1556.12 | 800.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 934.81 | 575.84 | 358.97 | 1120.70 | 440.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 418.26 | 50.22 | 251.33 | 589.60 | 111.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1440.16 | 1188.84 | 438.75 | 1556.12 | 800.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3718.81 | 2891.99 | 826.82 | 3977.41 | 2220.77 | 0.00 | 0.00 | 0.00 |
February | 3665.68 | 2682.78 | 982.90 | 3993.65 | 2068.71 | 0.00 | 0.00 | 0.00 |
March | 2725.78 | 1663.29 | 1062.49 | 3002.69 | 1708.14 | 0.00 | 0.00 | 0.00 |
April | 2093.40 | 857.90 | 1235.50 | 2365.27 | 1224.51 | 0.00 | 0.00 | 0.00 |
May | 1408.87 | 318.72 | 1090.15 | 1593.05 | 904.72 | 0.00 | 0.00 | 0.00 |
June | 1177.78 | 141.43 | 1036.35 | 1664.82 | 574.79 | 0.00 | 0.00 | 0.00 |
July | 1303.73 | 204.56 | 1099.16 | 2064.81 | 347.28 | 0.00 | 0.00 | 0.00 |
August | 1773.51 | 559.36 | 1214.15 | 2647.34 | 420.85 | 0.00 | 0.00 | 0.00 |
September | 2517.72 | 1417.26 | 1100.46 | 3451.20 | 753.29 | 0.00 | 0.00 | 0.00 |
October | 3392.00 | 2495.09 | 896.91 | 4114.98 | 1289.33 | 0.00 | 0.00 | 0.00 |
November | 3826.27 | 2944.77 | 881.50 | 4219.47 | 1821.70 | 0.00 | 0.00 | 0.00 |
December | 4055.40 | 3347.68 | 707.72 | 4369.45 | 2269.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2632.37 | 1621.53 | 1010.84 | 3117.00 | 1296.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1177.78 | 141.43 | 707.72 | 1593.05 | 347.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4055.40 | 3347.68 | 1235.50 | 4369.45 | 2269.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4830.94 | 3756.86 | 1074.09 | 5243.02 | 3152.01 | 0.00 | 0.00 | 0.00 |
February | 4761.93 | 3485.08 | 1276.85 | 5284.14 | 2920.83 | 0.00 | 0.00 | 0.00 |
March | 3540.94 | 2160.71 | 1380.23 | 3992.10 | 2376.74 | 0.00 | 0.00 | 0.00 |
April | 2719.44 | 1114.47 | 1604.98 | 3181.02 | 1666.45 | 0.00 | 0.00 | 0.00 |
May | 1830.21 | 414.04 | 1416.17 | 2172.81 | 1208.75 | 0.00 | 0.00 | 0.00 |
June | 1530.00 | 183.72 | 1346.28 | 2271.61 | 760.25 | 0.00 | 0.00 | 0.00 |
July | 1693.61 | 265.74 | 1427.87 | 2801.54 | 450.87 | 0.00 | 0.00 | 0.00 |
August | 2303.89 | 726.64 | 1577.25 | 3571.04 | 543.90 | 0.00 | 0.00 | 0.00 |
September | 3270.66 | 1841.10 | 1429.57 | 4621.14 | 982.89 | 0.00 | 0.00 | 0.00 |
October | 4406.40 | 3241.27 | 1165.13 | 5470.87 | 1744.00 | 0.00 | 0.00 | 0.00 |
November | 4970.54 | 3825.42 | 1145.12 | 5576.18 | 2538.16 | 0.00 | 0.00 | 0.00 |
December | 5268.20 | 4348.83 | 919.36 | 5758.97 | 3224.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3419.60 | 2106.47 | 1313.13 | 4155.55 | 1791.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1530.00 | 183.72 | 919.36 | 2172.81 | 450.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5268.20 | 4348.83 | 1604.98 | 5758.97 | 3224.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 299.92 | 233.23 | 66.68 | 323.69 | 183.55 | 0.00 | 0.00 | 0.00 |
February | 295.63 | 216.36 | 79.27 | 324.62 | 169.47 | 0.00 | 0.00 | 0.00 |
March | 219.83 | 134.14 | 85.69 | 244.69 | 134.41 | 0.00 | 0.00 | 0.00 |
April | 168.83 | 69.19 | 99.64 | 195.80 | 89.19 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 25.70 | 87.92 | 136.50 | 59.88 | 0.00 | 0.00 | 0.00 |
June | 94.99 | 11.41 | 83.58 | 148.08 | 33.42 | 0.00 | 0.00 | 0.00 |
July | 105.14 | 16.50 | 88.65 | 182.56 | 15.06 | 0.00 | 0.00 | 0.00 |
August | 143.03 | 45.11 | 97.92 | 227.27 | 19.84 | 0.00 | 0.00 | 0.00 |
September | 203.05 | 114.30 | 88.75 | 288.76 | 45.20 | 0.00 | 0.00 | 0.00 |
October | 273.56 | 201.22 | 72.33 | 340.64 | 92.54 | 0.00 | 0.00 | 0.00 |
November | 308.58 | 237.49 | 71.09 | 346.08 | 141.84 | 0.00 | 0.00 | 0.00 |
December | 327.06 | 269.99 | 57.08 | 356.62 | 186.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.30 | 130.77 | 81.52 | 259.24 | 97.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.99 | 11.41 | 57.08 | 136.50 | 15.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 327.06 | 269.99 | 99.64 | 356.62 | 186.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.96 | 123.73 | 93.23 | 176.24 | 385.82 | 0.00 | 0.00 | 0.00 |
February | 278.73 | 160.83 | 117.90 | 248.33 | 347.48 | 0.00 | 0.00 | 0.00 |
March | 311.01 | 165.21 | 145.80 | 302.99 | 261.71 | 0.00 | 0.00 | 0.00 |
April | 397.90 | 211.77 | 186.13 | 436.75 | 162.48 | 0.00 | 0.00 | 0.00 |
May | 378.38 | 195.50 | 182.87 | 456.93 | 108.98 | 0.00 | 0.00 | 0.00 |
June | 403.18 | 224.54 | 178.64 | 578.53 | 62.52 | 0.00 | 0.00 | 0.00 |
July | 364.02 | 177.88 | 186.14 | 558.31 | 28.37 | 0.00 | 0.00 | 0.00 |
August | 372.36 | 171.98 | 200.38 | 541.21 | 37.21 | 0.00 | 0.00 | 0.00 |
September | 337.85 | 178.38 | 159.47 | 449.35 | 85.39 | 0.00 | 0.00 | 0.00 |
October | 309.18 | 192.58 | 116.60 | 349.38 | 188.87 | 0.00 | 0.00 | 0.00 |
November | 241.60 | 142.12 | 99.47 | 213.62 | 296.19 | 0.00 | 0.00 | 0.00 |
December | 207.46 | 129.55 | 77.91 | 165.39 | 398.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 318.25 | 172.76 | 145.49 | 373.60 | 196.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 207.46 | 123.73 | 77.91 | 165.39 | 28.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.18 | 224.54 | 200.38 | 578.53 | 398.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.64 | 0.00 | 40.64 | 2.53 | 212.71 | 0.00 | 0.00 | 0.00 |
February | 50.79 | 0.00 | 50.79 | 8.76 | 191.73 | 0.00 | 0.00 | 0.00 |
March | 64.08 | 0.00 | 64.08 | 27.52 | 146.65 | 0.00 | 0.00 | 0.00 |
April | 81.73 | 1.09 | 80.64 | 53.27 | 94.07 | 0.00 | 0.00 | 0.00 |
May | 88.47 | 5.75 | 82.72 | 83.26 | 60.84 | 0.00 | 0.00 | 0.00 |
June | 100.72 | 16.75 | 83.97 | 146.21 | 32.91 | 0.00 | 0.00 | 0.00 |
July | 92.36 | 7.87 | 84.49 | 151.72 | 16.39 | 0.00 | 0.00 | 0.00 |
August | 85.71 | 2.10 | 83.62 | 124.42 | 21.81 | 0.00 | 0.00 | 0.00 |
September | 68.43 | 0.05 | 68.38 | 79.99 | 51.95 | 0.00 | 0.00 | 0.00 |
October | 51.01 | 0.00 | 51.01 | 30.89 | 109.52 | 0.00 | 0.00 | 0.00 |
November | 43.32 | 0.00 | 43.32 | 5.96 | 163.80 | 0.00 | 0.00 | 0.00 |
December | 34.59 | 0.00 | 34.59 | 0.35 | 222.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.88 | 2.81 | 64.07 | 59.86 | 110.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.59 | 0.00 | 34.59 | 0.35 | 16.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.72 | 16.75 | 84.49 | 151.72 | 222.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.96 | 123.73 | 93.23 | 184.85 | 376.67 | 0.00 | 0.00 | 0.00 |
February | 278.73 | 160.83 | 117.90 | 256.67 | 340.55 | 0.00 | 0.00 | 0.00 |
March | 311.01 | 165.21 | 145.80 | 305.73 | 262.50 | 0.00 | 0.00 | 0.00 |
April | 397.90 | 211.77 | 186.13 | 434.25 | 173.25 | 0.00 | 0.00 | 0.00 |
May | 378.38 | 195.50 | 182.87 | 453.12 | 118.68 | 0.00 | 0.00 | 0.00 |
June | 403.18 | 224.54 | 178.64 | 572.34 | 67.20 | 0.00 | 0.00 | 0.00 |
July | 364.02 | 177.88 | 186.14 | 552.67 | 32.25 | 0.00 | 0.00 | 0.00 |
August | 372.36 | 171.98 | 200.38 | 537.34 | 43.14 | 0.00 | 0.00 | 0.00 |
September | 337.85 | 178.38 | 159.47 | 450.82 | 96.91 | 0.00 | 0.00 | 0.00 |
October | 309.18 | 192.58 | 116.60 | 352.25 | 196.64 | 0.00 | 0.00 | 0.00 |
November | 241.60 | 142.12 | 99.47 | 221.68 | 289.36 | 0.00 | 0.00 | 0.00 |
December | 207.46 | 129.55 | 77.91 | 173.90 | 386.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 318.25 | 172.76 | 145.49 | 375.11 | 197.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 207.46 | 123.73 | 77.91 | 173.90 | 32.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.18 | 224.54 | 200.38 | 572.34 | 386.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 239.88 | 186.55 | 53.33 | 241.63 | 185.59 | 0.00 | 0.00 | 0.00 |
February | 236.46 | 173.05 | 63.40 | 242.64 | 174.00 | 0.00 | 0.00 | 0.00 |
March | 175.83 | 107.29 | 68.54 | 178.94 | 144.25 | 0.00 | 0.00 | 0.00 |
April | 135.04 | 55.34 | 79.70 | 140.23 | 103.74 | 0.00 | 0.00 | 0.00 |
May | 90.88 | 20.56 | 70.32 | 92.59 | 78.24 | 0.00 | 0.00 | 0.00 |
June | 75.97 | 9.12 | 66.85 | 99.16 | 51.46 | 0.00 | 0.00 | 0.00 |
July | 84.10 | 13.20 | 70.90 | 124.92 | 34.17 | 0.00 | 0.00 | 0.00 |
August | 114.40 | 36.08 | 78.32 | 162.16 | 40.34 | 0.00 | 0.00 | 0.00 |
September | 162.41 | 91.42 | 70.99 | 213.61 | 65.51 | 0.00 | 0.00 | 0.00 |
October | 218.80 | 160.95 | 57.86 | 254.77 | 107.70 | 0.00 | 0.00 | 0.00 |
November | 246.82 | 189.95 | 56.86 | 259.00 | 151.56 | 0.00 | 0.00 | 0.00 |
December | 261.60 | 215.95 | 45.65 | 268.14 | 189.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 169.80 | 104.60 | 65.20 | 189.51 | 110.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.97 | 9.12 | 45.65 | 92.59 | 34.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 261.60 | 215.95 | 79.70 | 268.14 | 189.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.52 | 0.00 | 32.52 | 2.21 | 173.02 | 0.00 | 0.00 | 0.00 |
February | 40.64 | 0.00 | 40.64 | 8.03 | 153.98 | 0.00 | 0.00 | 0.00 |
March | 51.27 | 0.00 | 51.27 | 24.77 | 115.35 | 0.00 | 0.00 | 0.00 |
April | 65.39 | 0.88 | 64.52 | 48.12 | 71.20 | 0.00 | 0.00 | 0.00 |
May | 70.78 | 4.60 | 66.18 | 72.60 | 46.37 | 0.00 | 0.00 | 0.00 |
June | 80.59 | 13.40 | 67.19 | 124.45 | 24.80 | 0.00 | 0.00 | 0.00 |
July | 73.90 | 6.30 | 67.60 | 128.84 | 11.71 | 0.00 | 0.00 | 0.00 |
August | 68.58 | 1.68 | 66.90 | 106.90 | 15.65 | 0.00 | 0.00 | 0.00 |
September | 54.75 | 0.04 | 54.71 | 69.34 | 38.77 | 0.00 | 0.00 | 0.00 |
October | 40.81 | 0.00 | 40.81 | 27.79 | 83.80 | 0.00 | 0.00 | 0.00 |
November | 34.66 | 0.00 | 34.66 | 5.46 | 131.27 | 0.00 | 0.00 | 0.00 |
December | 27.68 | 0.00 | 27.68 | 0.29 | 180.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53.51 | 2.25 | 51.26 | 51.81 | 86.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 27.68 | 0.00 | 27.68 | 0.29 | 11.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.59 | 13.40 | 67.60 | 128.84 | 180.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 210.38 | 117.75 | 92.63 | 146.16 | 366.46 | 0.00 | 0.00 | 0.00 |
February | 254.76 | 136.95 | 117.82 | 199.96 | 328.24 | 0.00 | 0.00 | 0.00 |
March | 338.56 | 192.88 | 145.68 | 322.01 | 242.86 | 0.00 | 0.00 | 0.00 |
April | 459.27 | 261.35 | 197.92 | 513.24 | 150.21 | 0.00 | 0.00 | 0.00 |
May | 438.76 | 249.92 | 188.85 | 534.65 | 103.05 | 0.00 | 0.00 | 0.00 |
June | 473.18 | 291.46 | 181.72 | 667.51 | 56.45 | 0.00 | 0.00 | 0.00 |
July | 437.62 | 250.17 | 187.45 | 659.02 | 26.89 | 0.00 | 0.00 | 0.00 |
August | 433.13 | 238.74 | 194.39 | 620.02 | 34.56 | 0.00 | 0.00 | 0.00 |
September | 361.18 | 202.10 | 159.08 | 474.06 | 79.48 | 0.00 | 0.00 | 0.00 |
October | 314.67 | 199.82 | 114.85 | 340.85 | 172.94 | 0.00 | 0.00 | 0.00 |
November | 244.74 | 143.57 | 101.16 | 203.42 | 282.75 | 0.00 | 0.00 | 0.00 |
December | 199.35 | 121.60 | 77.75 | 145.60 | 388.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 347.48 | 200.78 | 146.70 | 403.19 | 185.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.35 | 117.75 | 77.75 | 145.60 | 26.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 473.18 | 291.46 | 197.92 | 667.51 | 388.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 299.92 | 233.23 | 66.68 | 322.36 | 182.63 | 0.00 | 0.00 | 0.00 |
February | 295.63 | 216.36 | 79.27 | 323.28 | 168.24 | 0.00 | 0.00 | 0.00 |
March | 219.83 | 134.14 | 85.69 | 242.30 | 133.75 | 0.00 | 0.00 | 0.00 |
April | 168.83 | 69.19 | 99.64 | 193.15 | 88.95 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 25.70 | 87.92 | 133.94 | 59.77 | 0.00 | 0.00 | 0.00 |
June | 94.99 | 11.41 | 83.58 | 145.71 | 33.11 | 0.00 | 0.00 | 0.00 |
July | 105.14 | 16.50 | 88.65 | 180.32 | 14.92 | 0.00 | 0.00 | 0.00 |
August | 143.03 | 45.11 | 97.92 | 225.32 | 19.65 | 0.00 | 0.00 | 0.00 |
September | 203.05 | 114.30 | 88.75 | 287.30 | 44.62 | 0.00 | 0.00 | 0.00 |
October | 273.56 | 201.22 | 72.33 | 338.96 | 91.59 | 0.00 | 0.00 | 0.00 |
November | 308.58 | 237.49 | 71.09 | 344.61 | 140.92 | 0.00 | 0.00 | 0.00 |
December | 327.06 | 269.99 | 57.08 | 355.19 | 185.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.30 | 130.77 | 81.52 | 257.33 | 96.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.99 | 11.41 | 57.08 | 133.94 | 14.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 327.06 | 269.99 | 99.64 | 355.19 | 185.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.64 | 0.00 | 40.64 | 1.88 | 212.85 | 0.00 | 0.00 | 0.00 |
February | 50.79 | 0.00 | 50.79 | 7.86 | 191.10 | 0.00 | 0.00 | 0.00 |
March | 64.08 | 0.00 | 64.08 | 26.01 | 145.55 | 0.00 | 0.00 | 0.00 |
April | 81.73 | 1.09 | 80.64 | 51.53 | 91.84 | 0.00 | 0.00 | 0.00 |
May | 88.47 | 5.75 | 82.72 | 80.19 | 59.65 | 0.00 | 0.00 | 0.00 |
June | 100.72 | 16.75 | 83.97 | 141.04 | 32.30 | 0.00 | 0.00 | 0.00 |
July | 92.36 | 7.87 | 84.49 | 146.83 | 16.42 | 0.00 | 0.00 | 0.00 |
August | 85.71 | 2.10 | 83.62 | 119.69 | 21.48 | 0.00 | 0.00 | 0.00 |
September | 68.43 | 0.05 | 68.38 | 77.48 | 51.10 | 0.00 | 0.00 | 0.00 |
October | 51.01 | 0.00 | 51.01 | 29.69 | 106.59 | 0.00 | 0.00 | 0.00 |
November | 43.32 | 0.00 | 43.32 | 5.01 | 163.85 | 0.00 | 0.00 | 0.00 |
December | 34.59 | 0.00 | 34.59 | 0.26 | 222.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.88 | 2.81 | 64.07 | 57.57 | 109.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.59 | 0.00 | 34.59 | 0.26 | 16.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.72 | 16.75 | 84.49 | 146.83 | 222.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 210.38 | 117.75 | 92.63 | 151.43 | 354.39 | 0.00 | 0.00 | 0.00 |
February | 254.76 | 136.95 | 117.82 | 206.79 | 319.75 | 0.00 | 0.00 | 0.00 |
March | 338.56 | 192.88 | 145.68 | 326.68 | 242.73 | 0.00 | 0.00 | 0.00 |
April | 459.27 | 261.35 | 197.92 | 514.26 | 158.29 | 0.00 | 0.00 | 0.00 |
May | 438.76 | 249.92 | 188.85 | 530.60 | 111.55 | 0.00 | 0.00 | 0.00 |
June | 473.18 | 291.46 | 181.72 | 655.51 | 60.79 | 0.00 | 0.00 | 0.00 |
July | 437.62 | 250.17 | 187.45 | 646.71 | 30.68 | 0.00 | 0.00 | 0.00 |
August | 433.13 | 238.74 | 194.39 | 609.36 | 39.85 | 0.00 | 0.00 | 0.00 |
September | 361.18 | 202.10 | 159.08 | 471.97 | 89.38 | 0.00 | 0.00 | 0.00 |
October | 314.67 | 199.82 | 114.85 | 345.76 | 177.62 | 0.00 | 0.00 | 0.00 |
November | 244.74 | 143.57 | 101.16 | 209.24 | 274.35 | 0.00 | 0.00 | 0.00 |
December | 199.35 | 121.60 | 77.75 | 150.08 | 372.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 347.48 | 200.78 | 146.70 | 402.46 | 185.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.35 | 117.75 | 77.75 | 150.08 | 30.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 473.18 | 291.46 | 197.92 | 655.51 | 372.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.47 | 0.00 | 51.47 | 1.00 | 319.04 | 479.00 | 0.00 | 0.00 |
February | 64.32 | 0.00 | 64.32 | 7.16 | 285.46 | 373.83 | 0.00 | 0.00 |
March | 81.15 | 0.00 | 81.15 | 30.27 | 214.33 | 146.67 | 0.00 | 0.00 |
April | 103.51 | 1.39 | 102.12 | 65.96 | 132.73 | 13.33 | 0.00 | 0.00 |
May | 112.04 | 7.28 | 104.76 | 103.92 | 88.58 | 1.00 | 0.00 | 0.00 |
June | 127.56 | 21.21 | 106.34 | 184.75 | 51.57 | 0.00 | 0.00 | 0.00 |
July | 116.97 | 9.97 | 107.00 | 191.98 | 29.85 | 0.00 | 0.00 | 0.00 |
August | 108.55 | 2.66 | 105.89 | 157.57 | 36.68 | 0.00 | 0.00 | 0.00 |
September | 86.66 | 0.06 | 86.59 | 100.36 | 75.98 | 0.00 | 0.00 | 0.00 |
October | 64.60 | 0.00 | 64.60 | 36.00 | 158.15 | 58.50 | 0.00 | 0.00 |
November | 54.86 | 0.00 | 54.86 | 4.09 | 249.69 | 195.83 | 0.00 | 0.00 |
December | 43.81 | 0.00 | 43.81 | 0.16 | 336.66 | 505.50 | 0.00 | 0.00 |
Annual Sum or Average | 84.70 | 3.55 | 81.14 | 73.98 | 164.31 | 1773.67 | 0.00 | 0.00 |
Minimum of Months | 43.81 | 0.00 | 43.81 | 0.16 | 29.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.56 | 21.21 | 107.00 | 191.98 | 336.66 | 505.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.97 | 0.00 | 18.97 | 0.37 | 117.61 | 479.00 | 0.00 | 0.00 |
February | 23.71 | 0.00 | 23.71 | 2.64 | 105.23 | 373.83 | 0.00 | 0.00 |
March | 29.92 | 0.00 | 29.92 | 11.16 | 79.01 | 146.67 | 0.00 | 0.00 |
April | 38.16 | 0.51 | 37.65 | 24.32 | 48.93 | 13.33 | 0.00 | 0.00 |
May | 41.30 | 2.68 | 38.62 | 38.31 | 32.65 | 1.00 | 0.00 | 0.00 |
June | 47.02 | 7.82 | 39.20 | 68.11 | 19.01 | 0.00 | 0.00 | 0.00 |
July | 43.12 | 3.68 | 39.44 | 70.77 | 11.00 | 0.00 | 0.00 | 0.00 |
August | 40.02 | 0.98 | 39.04 | 58.09 | 13.52 | 0.00 | 0.00 | 0.00 |
September | 31.95 | 0.02 | 31.92 | 37.00 | 28.01 | 0.00 | 0.00 | 0.00 |
October | 23.81 | 0.00 | 23.81 | 13.27 | 58.30 | 58.50 | 0.00 | 0.00 |
November | 20.22 | 0.00 | 20.22 | 1.51 | 92.05 | 195.83 | 0.00 | 0.00 |
December | 16.15 | 0.00 | 16.15 | 0.06 | 124.11 | 505.50 | 0.00 | 0.00 |
Annual Sum or Average | 31.22 | 1.31 | 29.91 | 27.27 | 60.57 | 1773.67 | 0.00 | 0.00 |
Minimum of Months | 16.15 | 0.00 | 16.15 | 0.06 | 11.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.02 | 7.82 | 39.44 | 70.77 | 124.11 | 505.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.94 | 108.83 | 31.11 | 149.08 | 97.21 | 378.33 | 0.00 | 0.00 |
February | 137.94 | 100.95 | 36.99 | 149.98 | 90.23 | 288.00 | 0.00 | 0.00 |
March | 102.57 | 62.59 | 39.98 | 112.57 | 72.83 | 121.17 | 0.00 | 0.00 |
April | 78.77 | 32.28 | 46.49 | 90.42 | 49.65 | 13.17 | 0.00 | 0.00 |
May | 53.02 | 11.99 | 41.02 | 62.57 | 35.18 | 1.67 | 0.00 | 0.00 |
June | 44.32 | 5.32 | 39.00 | 67.85 | 21.11 | 0.00 | 0.00 | 0.00 |
July | 49.06 | 7.70 | 41.36 | 83.75 | 11.56 | 0.00 | 0.00 | 0.00 |
August | 66.74 | 21.05 | 45.69 | 105.12 | 14.32 | 0.00 | 0.00 | 0.00 |
September | 94.74 | 53.33 | 41.41 | 134.31 | 27.61 | 0.00 | 0.00 | 0.00 |
October | 127.64 | 93.89 | 33.75 | 157.97 | 51.52 | 46.83 | 0.00 | 0.00 |
November | 143.98 | 110.81 | 33.17 | 159.89 | 76.66 | 141.00 | 0.00 | 0.00 |
December | 152.61 | 125.97 | 26.63 | 164.64 | 98.99 | 380.50 | 0.00 | 0.00 |
Annual Sum or Average | 99.06 | 61.02 | 38.04 | 119.67 | 53.72 | 1370.67 | 0.00 | 0.00 |
Minimum of Months | 44.32 | 5.32 | 26.63 | 62.57 | 11.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.61 | 125.97 | 46.49 | 164.64 | 98.99 | 380.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 379.82 | 295.38 | 84.45 | 404.64 | 263.86 | 378.33 | 0.00 | 0.00 |
February | 374.40 | 274.01 | 100.39 | 407.08 | 244.91 | 288.00 | 0.00 | 0.00 |
March | 278.40 | 169.88 | 108.52 | 305.55 | 197.68 | 121.17 | 0.00 | 0.00 |
April | 213.81 | 87.62 | 126.19 | 245.42 | 134.76 | 13.17 | 0.00 | 0.00 |
May | 143.90 | 32.55 | 111.34 | 169.82 | 95.47 | 1.67 | 0.00 | 0.00 |
June | 120.29 | 14.44 | 105.85 | 184.15 | 57.30 | 0.00 | 0.00 | 0.00 |
July | 133.16 | 20.89 | 112.26 | 227.32 | 31.38 | 0.00 | 0.00 | 0.00 |
August | 181.14 | 57.13 | 124.01 | 285.31 | 38.85 | 0.00 | 0.00 | 0.00 |
September | 257.15 | 144.75 | 112.40 | 364.53 | 74.93 | 0.00 | 0.00 | 0.00 |
October | 346.45 | 254.84 | 91.61 | 428.77 | 139.84 | 46.83 | 0.00 | 0.00 |
November | 390.80 | 300.77 | 90.03 | 433.97 | 208.07 | 141.00 | 0.00 | 0.00 |
December | 414.20 | 341.92 | 72.28 | 446.86 | 268.68 | 380.50 | 0.00 | 0.00 |
Annual Sum or Average | 268.86 | 165.62 | 103.24 | 324.81 | 145.80 | 1370.67 | 0.00 | 0.00 |
Minimum of Months | 120.29 | 14.44 | 72.28 | 169.82 | 31.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 414.20 | 341.92 | 126.19 | 446.86 | 268.68 | 380.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 299.92 | 233.23 | 66.68 | 323.54 | 179.57 | 0.00 | 0.00 | 0.00 |
February | 295.63 | 216.36 | 79.27 | 323.62 | 166.10 | 0.00 | 0.00 | 0.00 |
March | 219.83 | 134.14 | 85.69 | 243.29 | 131.66 | 0.00 | 0.00 | 0.00 |
April | 168.83 | 69.19 | 99.64 | 193.36 | 87.23 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 25.70 | 87.92 | 134.31 | 58.20 | 0.00 | 0.00 | 0.00 |
June | 94.99 | 11.41 | 83.58 | 145.96 | 32.20 | 0.00 | 0.00 | 0.00 |
July | 105.14 | 16.50 | 88.65 | 179.89 | 14.21 | 0.00 | 0.00 | 0.00 |
August | 143.03 | 45.11 | 97.92 | 224.12 | 18.96 | 0.00 | 0.00 | 0.00 |
September | 203.05 | 114.30 | 88.75 | 285.68 | 43.82 | 0.00 | 0.00 | 0.00 |
October | 273.56 | 201.22 | 72.33 | 338.94 | 90.22 | 0.00 | 0.00 | 0.00 |
November | 308.58 | 237.49 | 71.09 | 345.45 | 138.07 | 0.00 | 0.00 | 0.00 |
December | 327.06 | 269.99 | 57.08 | 356.75 | 181.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.30 | 130.77 | 81.52 | 257.54 | 94.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.99 | 11.41 | 57.08 | 134.31 | 14.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 327.06 | 269.99 | 99.64 | 356.75 | 181.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.96 | 123.73 | 93.23 | 175.37 | 375.65 | 0.00 | 0.00 | 0.00 |
February | 278.73 | 160.83 | 117.90 | 245.85 | 339.64 | 0.00 | 0.00 | 0.00 |
March | 311.01 | 165.21 | 145.80 | 299.90 | 255.52 | 0.00 | 0.00 | 0.00 |
April | 397.90 | 211.77 | 186.13 | 430.96 | 158.25 | 0.00 | 0.00 | 0.00 |
May | 378.38 | 195.50 | 182.87 | 451.15 | 105.76 | 0.00 | 0.00 | 0.00 |
June | 403.18 | 224.54 | 178.64 | 572.46 | 60.28 | 0.00 | 0.00 | 0.00 |
July | 364.02 | 177.88 | 186.14 | 551.84 | 26.79 | 0.00 | 0.00 | 0.00 |
August | 372.36 | 171.98 | 200.38 | 534.90 | 35.56 | 0.00 | 0.00 | 0.00 |
September | 337.85 | 178.38 | 159.47 | 444.29 | 82.57 | 0.00 | 0.00 | 0.00 |
October | 309.18 | 192.58 | 116.60 | 346.05 | 183.17 | 0.00 | 0.00 | 0.00 |
November | 241.60 | 142.12 | 99.47 | 211.95 | 286.89 | 0.00 | 0.00 | 0.00 |
December | 207.46 | 129.55 | 77.91 | 164.37 | 386.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 318.25 | 172.76 | 145.49 | 369.60 | 190.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 207.46 | 123.73 | 77.91 | 164.37 | 26.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.18 | 224.54 | 200.38 | 572.46 | 386.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.64 | 0.00 | 40.64 | 3.28 | 206.44 | 0.00 | 0.00 | 0.00 |
February | 50.79 | 0.00 | 50.79 | 9.39 | 187.18 | 0.00 | 0.00 | 0.00 |
March | 64.08 | 0.00 | 64.08 | 27.88 | 143.77 | 0.00 | 0.00 | 0.00 |
April | 81.73 | 1.09 | 80.64 | 52.05 | 93.37 | 0.00 | 0.00 | 0.00 |
May | 88.47 | 5.75 | 82.72 | 81.59 | 60.12 | 0.00 | 0.00 | 0.00 |
June | 100.72 | 16.75 | 83.97 | 144.14 | 32.26 | 0.00 | 0.00 | 0.00 |
July | 92.36 | 7.87 | 84.49 | 149.49 | 15.76 | 0.00 | 0.00 | 0.00 |
August | 85.71 | 2.10 | 83.62 | 122.28 | 21.37 | 0.00 | 0.00 | 0.00 |
September | 68.43 | 0.05 | 68.38 | 78.59 | 51.13 | 0.00 | 0.00 | 0.00 |
October | 51.01 | 0.00 | 51.01 | 30.60 | 107.54 | 0.00 | 0.00 | 0.00 |
November | 43.32 | 0.00 | 43.32 | 6.68 | 158.27 | 0.00 | 0.00 | 0.00 |
December | 34.59 | 0.00 | 34.59 | 0.55 | 214.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.88 | 2.81 | 64.07 | 59.16 | 107.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.59 | 0.00 | 34.59 | 0.55 | 15.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.72 | 16.75 | 84.49 | 149.49 | 214.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.96 | 123.73 | 93.23 | 186.11 | 365.96 | 0.00 | 0.00 | 0.00 |
February | 278.73 | 160.83 | 117.90 | 256.24 | 332.18 | 0.00 | 0.00 | 0.00 |
March | 311.01 | 165.21 | 145.80 | 303.40 | 256.62 | 0.00 | 0.00 | 0.00 |
April | 397.90 | 211.77 | 186.13 | 427.86 | 171.13 | 0.00 | 0.00 | 0.00 |
May | 378.38 | 195.50 | 182.87 | 446.85 | 116.80 | 0.00 | 0.00 | 0.00 |
June | 403.18 | 224.54 | 178.64 | 566.08 | 65.46 | 0.00 | 0.00 | 0.00 |
July | 364.02 | 177.88 | 186.14 | 546.10 | 30.85 | 0.00 | 0.00 | 0.00 |
August | 372.36 | 171.98 | 200.38 | 530.91 | 42.00 | 0.00 | 0.00 | 0.00 |
September | 337.85 | 178.38 | 159.47 | 445.84 | 95.25 | 0.00 | 0.00 | 0.00 |
October | 309.18 | 192.58 | 116.60 | 349.35 | 192.48 | 0.00 | 0.00 | 0.00 |
November | 241.60 | 142.12 | 99.47 | 222.10 | 278.94 | 0.00 | 0.00 | 0.00 |
December | 207.46 | 129.55 | 77.91 | 175.54 | 374.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 318.25 | 172.76 | 145.49 | 371.83 | 192.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 207.46 | 123.73 | 77.91 | 175.54 | 30.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.18 | 224.54 | 200.38 | 566.08 | 374.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 439.86 | 342.06 | 97.79 | 463.40 | 273.12 | 0.00 | 0.00 | 0.00 |
February | 433.57 | 317.32 | 116.26 | 465.76 | 250.97 | 0.00 | 0.00 | 0.00 |
March | 322.40 | 196.73 | 125.67 | 352.29 | 196.47 | 0.00 | 0.00 | 0.00 |
April | 247.60 | 101.47 | 146.13 | 284.47 | 126.50 | 0.00 | 0.00 | 0.00 |
May | 166.64 | 37.70 | 128.94 | 201.29 | 83.38 | 0.00 | 0.00 | 0.00 |
June | 139.31 | 16.73 | 122.58 | 222.42 | 45.55 | 0.00 | 0.00 | 0.00 |
July | 154.20 | 24.20 | 130.01 | 271.77 | 19.63 | 0.00 | 0.00 | 0.00 |
August | 209.77 | 66.16 | 143.61 | 334.61 | 26.51 | 0.00 | 0.00 | 0.00 |
September | 297.79 | 167.63 | 130.16 | 419.93 | 63.45 | 0.00 | 0.00 | 0.00 |
October | 401.20 | 295.12 | 106.08 | 492.56 | 134.60 | 0.00 | 0.00 | 0.00 |
November | 452.57 | 348.30 | 104.26 | 497.34 | 209.50 | 0.00 | 0.00 | 0.00 |
December | 479.67 | 395.96 | 83.71 | 511.07 | 277.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 311.35 | 191.79 | 119.56 | 375.90 | 141.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 139.31 | 16.73 | 83.71 | 201.29 | 19.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 479.67 | 395.96 | 146.13 | 511.07 | 277.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.46 | 0.00 | 284.46 | 8.99 | 1688.63 | 0.00 | 0.00 | 0.00 |
February | 355.53 | 0.00 | 355.53 | 43.16 | 1529.70 | 0.00 | 0.00 | 0.00 |
March | 448.54 | 0.02 | 448.53 | 163.65 | 1182.28 | 0.00 | 0.00 | 0.00 |
April | 572.10 | 7.66 | 564.43 | 335.64 | 748.93 | 0.00 | 0.00 | 0.00 |
May | 619.24 | 40.23 | 579.00 | 529.28 | 513.41 | 0.00 | 0.00 | 0.00 |
June | 705.02 | 117.25 | 587.77 | 962.21 | 309.59 | 0.00 | 0.00 | 0.00 |
July | 646.49 | 55.10 | 591.39 | 1000.87 | 192.58 | 0.00 | 0.00 | 0.00 |
August | 599.98 | 14.68 | 585.29 | 817.50 | 232.01 | 0.00 | 0.00 | 0.00 |
September | 478.96 | 0.34 | 478.62 | 519.65 | 444.91 | 0.00 | 0.00 | 0.00 |
October | 357.05 | 0.00 | 357.05 | 188.34 | 877.07 | 0.00 | 0.00 | 0.00 |
November | 303.22 | 0.00 | 303.22 | 25.10 | 1339.70 | 0.00 | 0.00 | 0.00 |
December | 242.12 | 0.00 | 242.12 | 1.13 | 1762.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 468.13 | 19.64 | 448.49 | 384.90 | 898.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 242.12 | 0.00 | 242.12 | 1.13 | 192.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 705.02 | 117.25 | 591.39 | 1000.87 | 1762.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.46 | 0.00 | 284.46 | 6.45 | 1744.65 | 0.00 | 0.00 | 0.00 |
February | 355.53 | 0.00 | 355.53 | 37.04 | 1576.91 | 0.00 | 0.00 | 0.00 |
March | 448.54 | 0.02 | 448.53 | 151.46 | 1211.14 | 0.00 | 0.00 | 0.00 |
April | 572.10 | 7.66 | 564.43 | 322.42 | 765.00 | 0.00 | 0.00 | 0.00 |
May | 619.24 | 40.23 | 579.00 | 516.59 | 524.78 | 0.00 | 0.00 | 0.00 |
June | 705.02 | 117.25 | 587.77 | 950.26 | 317.37 | 0.00 | 0.00 | 0.00 |
July | 646.49 | 55.10 | 591.39 | 990.00 | 199.70 | 0.00 | 0.00 | 0.00 |
August | 599.98 | 14.68 | 585.29 | 806.81 | 240.01 | 0.00 | 0.00 | 0.00 |
September | 478.96 | 0.34 | 478.62 | 509.77 | 456.06 | 0.00 | 0.00 | 0.00 |
October | 357.05 | 0.00 | 357.05 | 179.46 | 899.16 | 0.00 | 0.00 | 0.00 |
November | 303.22 | 0.00 | 303.22 | 21.14 | 1379.69 | 0.00 | 0.00 | 0.00 |
December | 242.12 | 0.00 | 242.12 | 0.89 | 1821.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 468.13 | 19.64 | 448.49 | 376.29 | 924.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 242.12 | 0.00 | 242.12 | 0.89 | 199.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 705.02 | 117.25 | 591.39 | 990.00 | 1821.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.64 | 0.00 | 40.64 | 0.57 | 257.54 | 0.00 | 0.00 | 0.00 |
February | 50.79 | 0.00 | 50.79 | 4.42 | 233.66 | 0.00 | 0.00 | 0.00 |
March | 64.08 | 0.00 | 64.08 | 19.81 | 179.44 | 0.00 | 0.00 | 0.00 |
April | 81.73 | 1.09 | 80.64 | 46.33 | 115.00 | 0.00 | 0.00 | 0.00 |
May | 88.47 | 5.75 | 82.72 | 76.00 | 80.78 | 0.00 | 0.00 | 0.00 |
June | 100.72 | 16.75 | 83.97 | 141.33 | 50.72 | 0.00 | 0.00 | 0.00 |
July | 92.36 | 7.87 | 84.49 | 147.80 | 33.93 | 0.00 | 0.00 | 0.00 |
August | 85.71 | 2.10 | 83.62 | 121.42 | 39.89 | 0.00 | 0.00 | 0.00 |
September | 68.43 | 0.05 | 68.38 | 77.17 | 69.44 | 0.00 | 0.00 | 0.00 |
October | 51.01 | 0.00 | 51.01 | 26.60 | 133.30 | 0.00 | 0.00 | 0.00 |
November | 43.32 | 0.00 | 43.32 | 2.64 | 203.59 | 0.00 | 0.00 | 0.00 |
December | 34.59 | 0.00 | 34.59 | 0.09 | 269.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.88 | 2.81 | 64.07 | 55.64 | 138.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.59 | 0.00 | 34.59 | 0.09 | 33.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 100.72 | 16.75 | 84.49 | 147.80 | 269.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 420.72 | 235.48 | 185.24 | 281.08 | 858.36 | 0.00 | 0.00 | 0.00 |
February | 509.49 | 273.88 | 235.61 | 385.13 | 777.61 | 0.00 | 0.00 | 0.00 |
March | 677.07 | 385.72 | 291.34 | 620.11 | 598.91 | 0.00 | 0.00 | 0.00 |
April | 918.47 | 522.66 | 395.81 | 1004.95 | 396.37 | 0.00 | 0.00 | 0.00 |
May | 877.46 | 499.80 | 377.66 | 1045.23 | 299.55 | 0.00 | 0.00 | 0.00 |
June | 946.29 | 582.88 | 363.41 | 1310.48 | 191.04 | 0.00 | 0.00 | 0.00 |
July | 875.17 | 500.30 | 374.87 | 1297.55 | 127.77 | 0.00 | 0.00 | 0.00 |
August | 866.20 | 477.44 | 388.76 | 1224.77 | 149.06 | 0.00 | 0.00 | 0.00 |
September | 722.31 | 404.17 | 318.14 | 941.52 | 247.34 | 0.00 | 0.00 | 0.00 |
October | 629.30 | 399.62 | 229.68 | 673.47 | 444.90 | 0.00 | 0.00 | 0.00 |
November | 489.44 | 287.12 | 202.31 | 394.94 | 679.12 | 0.00 | 0.00 | 0.00 |
December | 398.67 | 243.18 | 155.49 | 282.53 | 898.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 694.91 | 401.54 | 293.38 | 790.43 | 470.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 398.67 | 235.48 | 155.49 | 281.08 | 127.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 946.29 | 582.88 | 395.81 | 1310.48 | 898.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 299.92 | 233.23 | 66.68 | 318.06 | 212.16 | 0.00 | 0.00 | 0.00 |
February | 295.63 | 216.36 | 79.27 | 319.15 | 198.03 | 0.00 | 0.00 | 0.00 |
March | 219.83 | 134.14 | 85.69 | 236.47 | 163.68 | 0.00 | 0.00 | 0.00 |
April | 168.83 | 69.19 | 99.64 | 187.71 | 116.05 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 25.70 | 87.92 | 128.43 | 86.22 | 0.00 | 0.00 | 0.00 |
June | 94.99 | 11.41 | 83.58 | 140.62 | 55.67 | 0.00 | 0.00 | 0.00 |
July | 105.14 | 16.50 | 88.65 | 175.35 | 35.21 | 0.00 | 0.00 | 0.00 |
August | 143.03 | 45.11 | 97.92 | 222.34 | 41.85 | 0.00 | 0.00 | 0.00 |
September | 203.05 | 114.30 | 88.75 | 286.00 | 68.74 | 0.00 | 0.00 | 0.00 |
October | 273.56 | 201.22 | 72.33 | 337.49 | 117.69 | 0.00 | 0.00 | 0.00 |
November | 308.58 | 237.49 | 71.09 | 342.04 | 168.74 | 0.00 | 0.00 | 0.00 |
December | 327.06 | 269.99 | 57.08 | 352.68 | 214.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 212.30 | 130.77 | 81.52 | 253.49 | 122.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.99 | 11.41 | 57.08 | 128.43 | 35.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 327.06 | 269.99 | 99.64 | 352.68 | 214.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.47 | 0.00 | 51.47 | 1.30 | 294.79 | 397.83 | 0.00 | 0.00 |
February | 64.32 | 0.00 | 64.32 | 6.91 | 267.41 | 375.17 | 0.00 | 0.00 |
March | 81.15 | 0.00 | 81.15 | 28.53 | 207.85 | 297.50 | 0.00 | 0.00 |
April | 103.51 | 1.39 | 102.12 | 61.38 | 131.64 | 61.50 | 0.00 | 0.00 |
May | 112.04 | 7.28 | 104.76 | 98.17 | 89.50 | 24.17 | 0.00 | 0.00 |
June | 127.56 | 21.21 | 106.34 | 177.61 | 53.19 | 2.00 | 0.00 | 0.00 |
July | 116.97 | 9.97 | 107.00 | 184.31 | 31.88 | 0.00 | 0.00 | 0.00 |
August | 108.55 | 2.66 | 105.89 | 150.23 | 38.90 | 0.00 | 0.00 | 0.00 |
September | 86.66 | 0.06 | 86.59 | 94.52 | 77.80 | 0.00 | 0.00 | 0.00 |
October | 64.60 | 0.00 | 64.60 | 32.65 | 155.99 | 107.00 | 0.00 | 0.00 |
November | 54.86 | 0.00 | 54.86 | 3.67 | 240.34 | 326.50 | 0.00 | 0.00 |
December | 43.81 | 0.00 | 43.81 | 0.16 | 309.29 | 409.83 | 0.00 | 0.00 |
Annual Sum or Average | 84.70 | 3.55 | 81.14 | 70.31 | 157.67 | 2001.50 | 0.00 | 0.00 |
Minimum of Months | 43.81 | 0.00 | 43.81 | 0.16 | 31.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.56 | 21.21 | 107.00 | 184.31 | 309.29 | 409.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 46.05 | 0.00 | 46.05 | 1.16 | 263.71 | 397.83 | 0.00 | 0.00 |
February | 57.55 | 0.00 | 57.55 | 6.18 | 239.26 | 375.17 | 0.00 | 0.00 |
March | 72.61 | 0.00 | 72.61 | 25.53 | 185.97 | 297.50 | 0.00 | 0.00 |
April | 92.61 | 1.24 | 91.37 | 54.92 | 117.78 | 61.50 | 0.00 | 0.00 |
May | 100.24 | 6.51 | 93.73 | 87.83 | 80.07 | 24.17 | 0.00 | 0.00 |
June | 114.13 | 18.98 | 95.15 | 158.91 | 47.59 | 2.00 | 0.00 | 0.00 |
July | 104.65 | 8.92 | 95.73 | 164.90 | 28.53 | 0.00 | 0.00 | 0.00 |
August | 97.12 | 2.38 | 94.74 | 134.41 | 34.80 | 0.00 | 0.00 | 0.00 |
September | 77.53 | 0.06 | 77.48 | 84.57 | 69.61 | 0.00 | 0.00 | 0.00 |
October | 57.80 | 0.00 | 57.80 | 29.21 | 139.57 | 107.00 | 0.00 | 0.00 |
November | 49.08 | 0.00 | 49.08 | 3.29 | 215.02 | 326.50 | 0.00 | 0.00 |
December | 39.19 | 0.00 | 39.19 | 0.15 | 276.70 | 409.83 | 0.00 | 0.00 |
Annual Sum or Average | 75.78 | 3.18 | 72.60 | 62.91 | 141.07 | 2001.50 | 0.00 | 0.00 |
Minimum of Months | 39.19 | 0.00 | 39.19 | 0.15 | 28.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.13 | 18.98 | 95.73 | 164.90 | 276.70 | 409.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1119.67 | 870.73 | 248.94 | 1199.83 | 720.59 | 334.67 | 0.00 | 0.00 |
February | 1103.68 | 807.74 | 295.94 | 1201.13 | 677.41 | 308.33 | 0.00 | 0.00 |
March | 820.69 | 500.79 | 319.90 | 891.34 | 566.37 | 253.50 | 0.00 | 0.00 |
April | 630.29 | 258.30 | 371.99 | 705.16 | 395.15 | 57.00 | 0.00 | 0.00 |
May | 424.19 | 95.96 | 328.23 | 481.70 | 284.78 | 23.67 | 0.00 | 0.00 |
June | 354.61 | 42.58 | 312.03 | 522.31 | 174.28 | 4.00 | 0.00 | 0.00 |
July | 392.53 | 61.59 | 330.94 | 646.34 | 99.19 | 0.00 | 0.00 | 0.00 |
August | 533.98 | 168.41 | 365.56 | 816.44 | 121.76 | 0.00 | 0.00 | 0.00 |
September | 758.05 | 426.71 | 331.33 | 1051.55 | 226.79 | 0.00 | 0.00 | 0.00 |
October | 1021.28 | 751.23 | 270.04 | 1248.73 | 406.82 | 83.83 | 0.00 | 0.00 |
November | 1152.03 | 886.62 | 265.41 | 1274.39 | 588.07 | 249.67 | 0.00 | 0.00 |
December | 1221.02 | 1007.93 | 213.08 | 1326.26 | 726.93 | 352.00 | 0.00 | 0.00 |
Annual Sum or Average | 792.56 | 488.22 | 304.35 | 945.66 | 414.29 | 1666.67 | 0.00 | 0.00 |
Minimum of Months | 354.61 | 42.58 | 213.08 | 481.70 | 99.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1221.02 | 1007.93 | 371.99 | 1326.26 | 726.93 | 352.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.353718E+10 | 0.275074E+10 | 0.786437E+09 | 0.380118E+10 | 0.209651E+10 |
February | 0.314923E+10 | 0.230481E+10 | 0.844424E+09 | 0.345121E+10 | 0.175157E+10 |
March | 0.259265E+10 | 0.158205E+10 | 0.101060E+10 | 0.289879E+10 | 0.154871E+10 |
April | 0.192692E+10 | 0.789680E+09 | 0.113724E+10 | 0.222831E+10 | 0.104459E+10 |
May | 0.134006E+10 | 0.303158E+09 | 0.103690E+10 | 0.157919E+10 | 0.768823E+09 |
June | 0.108412E+10 | 0.130179E+09 | 0.953939E+09 | 0.157785E+10 | 0.473768E+09 |
July | 0.124005E+10 | 0.194572E+09 | 0.104548E+10 | 0.199732E+10 | 0.298667E+09 |
August | 0.168689E+10 | 0.532039E+09 | 0.115485E+10 | 0.255329E+10 | 0.363773E+09 |
September | 0.231750E+10 | 0.130455E+10 | 0.101295E+10 | 0.321873E+10 | 0.635619E+09 |
October | 0.322633E+10 | 0.237323E+10 | 0.853100E+09 | 0.395532E+10 | 0.115355E+10 |
November | 0.352199E+10 | 0.271059E+10 | 0.811403E+09 | 0.391320E+10 | 0.161195E+10 |
December | 0.385733E+10 | 0.318418E+10 | 0.673150E+09 | 0.416792E+10 | 0.214300E+10 |
Annual Sum or Average | 0.294802E+11 | 0.181598E+11 | 0.113205E+11 | 0.353423E+11 | 0.138905E+11 |
Minimum of Months | 0.108412E+10 | 0.130179E+09 | 0.673150E+09 | 0.157785E+10 | 0.298667E+09 |
Maximum of Months | 0.385733E+10 | 0.318418E+10 | 0.115485E+10 | 0.416792E+10 | 0.214300E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.996046E+10 | 0.774590E+10 | 0.221455E+10 | 0.106531E+11 | 0.594811E+10 |
February | 0.886802E+10 | 0.649018E+10 | 0.237784E+10 | 0.966143E+10 | 0.500462E+10 |
March | 0.730072E+10 | 0.445495E+10 | 0.284577E+10 | 0.804241E+10 | 0.457508E+10 |
April | 0.542609E+10 | 0.222369E+10 | 0.320240E+10 | 0.613079E+10 | 0.317392E+10 |
May | 0.377353E+10 | 0.853672E+09 | 0.291986E+10 | 0.426682E+10 | 0.242321E+10 |
June | 0.305280E+10 | 0.366575E+09 | 0.268623E+10 | 0.431521E+10 | 0.148986E+10 |
July | 0.349190E+10 | 0.547903E+09 | 0.294399E+10 | 0.553038E+10 | 0.930152E+09 |
August | 0.475017E+10 | 0.149819E+10 | 0.325198E+10 | 0.709063E+10 | 0.112720E+10 |
September | 0.652593E+10 | 0.367353E+10 | 0.285240E+10 | 0.894550E+10 | 0.195253E+10 |
October | 0.908513E+10 | 0.668285E+10 | 0.240227E+10 | 0.110216E+11 | 0.345335E+10 |
November | 0.991770E+10 | 0.763284E+10 | 0.228486E+10 | 0.109369E+11 | 0.472184E+10 |
December | 0.108620E+11 | 0.896644E+10 | 0.189554E+10 | 0.117031E+11 | 0.607778E+10 |
Annual Sum or Average | 0.830144E+11 | 0.511367E+11 | 0.318777E+11 | 0.982978E+11 | 0.408776E+11 |
Minimum of Months | 0.305280E+10 | 0.366575E+09 | 0.189554E+10 | 0.426682E+10 | 0.930152E+09 |
Maximum of Months | 0.108620E+11 | 0.896644E+10 | 0.325198E+10 | 0.117031E+11 | 0.607778E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129392E+11 | 0.100624E+11 | 0.287683E+10 | 0.140429E+11 | 0.844234E+10 |
February | 0.115201E+11 | 0.843111E+10 | 0.308895E+10 | 0.127834E+11 | 0.706607E+10 |
March | 0.948405E+10 | 0.578723E+10 | 0.369682E+10 | 0.106925E+11 | 0.636587E+10 |
April | 0.704880E+10 | 0.288869E+10 | 0.416010E+10 | 0.824521E+10 | 0.431944E+10 |
May | 0.490203E+10 | 0.110897E+10 | 0.379306E+10 | 0.581965E+10 | 0.323750E+10 |
June | 0.396576E+10 | 0.476202E+09 | 0.348956E+10 | 0.588802E+10 | 0.197056E+10 |
July | 0.453617E+10 | 0.711757E+09 | 0.382442E+10 | 0.750364E+10 | 0.120761E+10 |
August | 0.617074E+10 | 0.194623E+10 | 0.422451E+10 | 0.956468E+10 | 0.145679E+10 |
September | 0.847756E+10 | 0.477212E+10 | 0.370543E+10 | 0.119780E+11 | 0.254764E+10 |
October | 0.118021E+11 | 0.868141E+10 | 0.312069E+10 | 0.146532E+11 | 0.467113E+10 |
November | 0.128837E+11 | 0.991549E+10 | 0.296816E+10 | 0.144535E+11 | 0.657890E+10 |
December | 0.141103E+11 | 0.116479E+11 | 0.246242E+10 | 0.154248E+11 | 0.863606E+10 |
Annual Sum or Average | 0.107840E+12 | 0.664295E+11 | 0.414110E+11 | 0.131049E+12 | 0.564999E+11 |
Minimum of Months | 0.396576E+10 | 0.476202E+09 | 0.246242E+10 | 0.581965E+10 | 0.120761E+10 |
Maximum of Months | 0.141103E+11 | 0.116479E+11 | 0.422451E+10 | 0.154248E+11 | 0.863606E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.803294E+09 | 0.624694E+09 | 0.178600E+09 | 0.866966E+09 | 0.491612E+09 |
February | 0.715191E+09 | 0.523422E+09 | 0.191769E+09 | 0.785331E+09 | 0.409984E+09 |
March | 0.588791E+09 | 0.359284E+09 | 0.229507E+09 | 0.655366E+09 | 0.360011E+09 |
April | 0.437605E+09 | 0.179336E+09 | 0.258268E+09 | 0.507521E+09 | 0.231182E+09 |
May | 0.304329E+09 | 68847219.79 | 0.235481E+09 | 0.365609E+09 | 0.160387E+09 |
June | 0.246203E+09 | 29563633.99 | 0.216640E+09 | 0.383814E+09 | 86628376.39 |
July | 0.281616E+09 | 44187454.95 | 0.237428E+09 | 0.488961E+09 | 40333646.70 |
August | 0.383093E+09 | 0.120826E+09 | 0.262267E+09 | 0.608717E+09 | 53131863.47 |
September | 0.526305E+09 | 0.296264E+09 | 0.230042E+09 | 0.748458E+09 | 0.117146E+09 |
October | 0.732700E+09 | 0.538961E+09 | 0.193739E+09 | 0.912370E+09 | 0.247853E+09 |
November | 0.799845E+09 | 0.615575E+09 | 0.184270E+09 | 0.897051E+09 | 0.367657E+09 |
December | 0.876000E+09 | 0.723128E+09 | 0.152872E+09 | 0.955167E+09 | 0.499130E+09 |
Annual Sum or Average | 0.669497E+10 | 0.412409E+10 | 0.257088E+10 | 0.817533E+10 | 0.306505E+10 |
Minimum of Months | 0.246203E+09 | 29563633.99 | 0.152872E+09 | 0.365609E+09 | 40333646.70 |
Maximum of Months | 0.876000E+09 | 0.723128E+09 | 0.262267E+09 | 0.955167E+09 | 0.499130E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581104E+09 | 0.331407E+09 | 0.249697E+09 | 0.472040E+09 | 0.103339E+10 |
February | 0.674302E+09 | 0.389082E+09 | 0.285221E+09 | 0.600759E+09 | 0.840616E+09 |
March | 0.833010E+09 | 0.442493E+09 | 0.390517E+09 | 0.811520E+09 | 0.700959E+09 |
April | 0.103135E+10 | 0.548902E+09 | 0.482452E+09 | 0.113205E+10 | 0.421140E+09 |
May | 0.101345E+10 | 0.523637E+09 | 0.489810E+09 | 0.122385E+10 | 0.291889E+09 |
June | 0.104505E+10 | 0.582014E+09 | 0.463034E+09 | 0.149954E+10 | 0.162043E+09 |
July | 0.974991E+09 | 0.476425E+09 | 0.498566E+09 | 0.149537E+10 | 75975151.95 |
August | 0.997320E+09 | 0.460622E+09 | 0.536698E+09 | 0.144958E+10 | 99670935.35 |
September | 0.875696E+09 | 0.462348E+09 | 0.413348E+09 | 0.116472E+10 | 0.221319E+09 |
October | 0.828111E+09 | 0.515813E+09 | 0.312297E+09 | 0.935781E+09 | 0.505871E+09 |
November | 0.626217E+09 | 0.368379E+09 | 0.257838E+09 | 0.553702E+09 | 0.767733E+09 |
December | 0.555650E+09 | 0.346979E+09 | 0.208671E+09 | 0.442970E+09 | 0.106674E+10 |
Annual Sum or Average | 0.100363E+11 | 0.544810E+10 | 0.458815E+10 | 0.117819E+11 | 0.618735E+10 |
Minimum of Months | 0.555650E+09 | 0.331407E+09 | 0.208671E+09 | 0.442970E+09 | 75975151.95 |
Maximum of Months | 0.104505E+10 | 0.582014E+09 | 0.536698E+09 | 0.149954E+10 | 0.106674E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108847E+09 | 0.00 | 0.108847E+09 | 6785599.97 | 0.569713E+09 |
February | 0.122875E+09 | 0.00 | 0.122875E+09 | 21186764.20 | 0.463841E+09 |
March | 0.171632E+09 | 5966.21 | 0.171626E+09 | 73711852.61 | 0.392778E+09 |
April | 0.211848E+09 | 2837829.67 | 0.209010E+09 | 0.138084E+09 | 0.243833E+09 |
May | 0.236946E+09 | 15395335.14 | 0.221551E+09 | 0.223008E+09 | 0.162966E+09 |
June | 0.261069E+09 | 43416898.60 | 0.217652E+09 | 0.378978E+09 | 85295175.36 |
July | 0.247377E+09 | 21085524.22 | 0.226291E+09 | 0.406364E+09 | 43891144.54 |
August | 0.229577E+09 | 5618487.49 | 0.223958E+09 | 0.333259E+09 | 58409916.89 |
September | 0.177358E+09 | 126386.42 | 0.177232E+09 | 0.207324E+09 | 0.134664E+09 |
October | 0.136621E+09 | 0.00 | 0.136621E+09 | 82743794.87 | 0.293347E+09 |
November | 0.112281E+09 | 0.00 | 0.112281E+09 | 15446057.50 | 0.424562E+09 |
December | 92645119.08 | 0.00 | 92645119.08 | 928807.15 | 0.595820E+09 |
Annual Sum or Average | 0.210908E+10 | 88486427.75 | 0.202059E+10 | 0.188782E+10 | 0.346912E+10 |
Minimum of Months | 92645119.08 | 0.00 | 92645119.08 | 928807.15 | 43891144.54 |
Maximum of Months | 0.261069E+09 | 43416898.60 | 0.226291E+09 | 0.406364E+09 | 0.595820E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581104E+09 | 0.331407E+09 | 0.249697E+09 | 0.495113E+09 | 0.100886E+10 |
February | 0.674302E+09 | 0.389082E+09 | 0.285221E+09 | 0.620936E+09 | 0.823847E+09 |
March | 0.833010E+09 | 0.442493E+09 | 0.390517E+09 | 0.818873E+09 | 0.703092E+09 |
April | 0.103135E+10 | 0.548902E+09 | 0.482452E+09 | 0.112557E+10 | 0.449067E+09 |
May | 0.101345E+10 | 0.523637E+09 | 0.489810E+09 | 0.121363E+10 | 0.317867E+09 |
June | 0.104505E+10 | 0.582014E+09 | 0.463034E+09 | 0.148351E+10 | 0.174179E+09 |
July | 0.974991E+09 | 0.476425E+09 | 0.498566E+09 | 0.148026E+10 | 86389312.23 |
August | 0.997320E+09 | 0.460622E+09 | 0.536698E+09 | 0.143921E+10 | 0.115538E+09 |
September | 0.875696E+09 | 0.462348E+09 | 0.413348E+09 | 0.116854E+10 | 0.251192E+09 |
October | 0.828111E+09 | 0.515813E+09 | 0.312297E+09 | 0.943479E+09 | 0.526672E+09 |
November | 0.626217E+09 | 0.368379E+09 | 0.257838E+09 | 0.574599E+09 | 0.750025E+09 |
December | 0.555650E+09 | 0.346979E+09 | 0.208671E+09 | 0.465780E+09 | 0.103501E+10 |
Annual Sum or Average | 0.100363E+11 | 0.544810E+10 | 0.458815E+10 | 0.118295E+11 | 0.624174E+10 |
Minimum of Months | 0.555650E+09 | 0.331407E+09 | 0.208671E+09 | 0.465780E+09 | 86389312.23 |
Maximum of Months | 0.104505E+10 | 0.582014E+09 | 0.536698E+09 | 0.148351E+10 | 0.103501E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.642507E+09 | 0.499656E+09 | 0.142852E+09 | 0.647181E+09 | 0.497091E+09 |
February | 0.572039E+09 | 0.418654E+09 | 0.153385E+09 | 0.587006E+09 | 0.420932E+09 |
March | 0.470939E+09 | 0.287370E+09 | 0.183569E+09 | 0.479286E+09 | 0.386372E+09 |
April | 0.350014E+09 | 0.143441E+09 | 0.206574E+09 | 0.363466E+09 | 0.268883E+09 |
May | 0.243414E+09 | 55066824.53 | 0.188348E+09 | 0.247989E+09 | 0.209562E+09 |
June | 0.196924E+09 | 23646204.60 | 0.173277E+09 | 0.257034E+09 | 0.133372E+09 |
July | 0.225248E+09 | 35342935.20 | 0.189905E+09 | 0.334586E+09 | 91523959.43 |
August | 0.306414E+09 | 96641690.18 | 0.209772E+09 | 0.434339E+09 | 0.108045E+09 |
September | 0.420961E+09 | 0.236964E+09 | 0.183997E+09 | 0.553675E+09 | 0.169807E+09 |
October | 0.586044E+09 | 0.431083E+09 | 0.154961E+09 | 0.682371E+09 | 0.288452E+09 |
November | 0.639749E+09 | 0.492362E+09 | 0.147387E+09 | 0.671332E+09 | 0.392850E+09 |
December | 0.700661E+09 | 0.578387E+09 | 0.122274E+09 | 0.718187E+09 | 0.507606E+09 |
Annual Sum or Average | 0.535491E+10 | 0.329862E+10 | 0.205630E+10 | 0.597645E+10 | 0.347450E+10 |
Minimum of Months | 0.196924E+09 | 23646204.60 | 0.122274E+09 | 0.247989E+09 | 91523959.43 |
Maximum of Months | 0.700661E+09 | 0.578387E+09 | 0.209772E+09 | 0.718187E+09 | 0.507606E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 87089113.54 | 0.00 | 87089113.54 | 5918905.92 | 0.463422E+09 |
February | 98313144.90 | 0.00 | 98313144.90 | 19422036.54 | 0.372517E+09 |
March | 0.137324E+09 | 4773.60 | 0.137319E+09 | 66342891.65 | 0.308947E+09 |
April | 0.169500E+09 | 2270564.67 | 0.167230E+09 | 0.124727E+09 | 0.184556E+09 |
May | 0.189582E+09 | 12317900.70 | 0.177264E+09 | 0.194462E+09 | 0.124204E+09 |
June | 0.208883E+09 | 34738123.00 | 0.174145E+09 | 0.322580E+09 | 64291750.78 |
July | 0.197927E+09 | 16870655.38 | 0.181057E+09 | 0.345079E+09 | 31352850.53 |
August | 0.183686E+09 | 4495385.80 | 0.179190E+09 | 0.286310E+09 | 41907316.04 |
September | 0.141905E+09 | 101122.54 | 0.141804E+09 | 0.179723E+09 | 0.100499E+09 |
October | 0.109312E+09 | 0.00 | 0.109312E+09 | 74422719.77 | 0.224459E+09 |
November | 89836958.00 | 0.00 | 89836958.00 | 14142923.87 | 0.340262E+09 |
December | 74125919.77 | 0.00 | 74125919.77 | 767444.41 | 0.484455E+09 |
Annual Sum or Average | 0.168748E+10 | 70798525.71 | 0.161669E+10 | 0.163390E+10 | 0.274087E+10 |
Minimum of Months | 74125919.77 | 0.00 | 74125919.77 | 767444.41 | 31352850.53 |
Maximum of Months | 0.208883E+09 | 34738123.00 | 0.181057E+09 | 0.345079E+09 | 0.484455E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.563470E+09 | 0.315381E+09 | 0.248090E+09 | 0.391480E+09 | 0.981528E+09 |
February | 0.616324E+09 | 0.331304E+09 | 0.285020E+09 | 0.483750E+09 | 0.794084E+09 |
March | 0.906790E+09 | 0.516599E+09 | 0.390191E+09 | 0.862465E+09 | 0.650474E+09 |
April | 0.119042E+10 | 0.677420E+09 | 0.513002E+09 | 0.133032E+10 | 0.389346E+09 |
May | 0.117518E+10 | 0.669373E+09 | 0.505803E+09 | 0.143201E+10 | 0.276012E+09 |
June | 0.122648E+10 | 0.755467E+09 | 0.471011E+09 | 0.173020E+10 | 0.146314E+09 |
July | 0.117212E+10 | 0.670052E+09 | 0.502064E+09 | 0.176513E+10 | 72022978.62 |
August | 0.116010E+10 | 0.639431E+09 | 0.520667E+09 | 0.166066E+10 | 92560490.35 |
September | 0.936174E+09 | 0.523838E+09 | 0.412337E+09 | 0.122877E+10 | 0.206021E+09 |
October | 0.842823E+09 | 0.535210E+09 | 0.307613E+09 | 0.912944E+09 | 0.463197E+09 |
November | 0.634355E+09 | 0.372138E+09 | 0.262217E+09 | 0.527261E+09 | 0.732895E+09 |
December | 0.533938E+09 | 0.325687E+09 | 0.208251E+09 | 0.389972E+09 | 0.104179E+10 |
Annual Sum or Average | 0.109582E+11 | 0.633190E+10 | 0.462627E+10 | 0.127150E+11 | 0.584624E+10 |
Minimum of Months | 0.533938E+09 | 0.315381E+09 | 0.208251E+09 | 0.389972E+09 | 72022978.62 |
Maximum of Months | 0.122648E+10 | 0.755467E+09 | 0.520667E+09 | 0.176513E+10 | 0.104179E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.803294E+09 | 0.624694E+09 | 0.178600E+09 | 0.863411E+09 | 0.489149E+09 |
February | 0.715191E+09 | 0.523422E+09 | 0.191769E+09 | 0.782087E+09 | 0.407007E+09 |
March | 0.588791E+09 | 0.359284E+09 | 0.229507E+09 | 0.648973E+09 | 0.358235E+09 |
April | 0.437605E+09 | 0.179336E+09 | 0.258268E+09 | 0.500654E+09 | 0.230564E+09 |
May | 0.304329E+09 | 68847219.79 | 0.235481E+09 | 0.358740E+09 | 0.160077E+09 |
June | 0.246203E+09 | 29563633.99 | 0.216640E+09 | 0.377668E+09 | 85827990.71 |
July | 0.281616E+09 | 44187454.95 | 0.237428E+09 | 0.482975E+09 | 39959526.19 |
August | 0.383093E+09 | 0.120826E+09 | 0.262267E+09 | 0.603484E+09 | 52637036.51 |
September | 0.526305E+09 | 0.296264E+09 | 0.230042E+09 | 0.744676E+09 | 0.115650E+09 |
October | 0.732700E+09 | 0.538961E+09 | 0.193739E+09 | 0.907876E+09 | 0.245317E+09 |
November | 0.799845E+09 | 0.615575E+09 | 0.184270E+09 | 0.893241E+09 | 0.365259E+09 |
December | 0.876000E+09 | 0.723128E+09 | 0.152872E+09 | 0.951336E+09 | 0.496975E+09 |
Annual Sum or Average | 0.669497E+10 | 0.412409E+10 | 0.257088E+10 | 0.811512E+10 | 0.304666E+10 |
Minimum of Months | 0.246203E+09 | 29563633.99 | 0.152872E+09 | 0.358740E+09 | 39959526.19 |
Maximum of Months | 0.876000E+09 | 0.723128E+09 | 0.262267E+09 | 0.951336E+09 | 0.496975E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108847E+09 | 0.00 | 0.108847E+09 | 5033292.64 | 0.570093E+09 |
February | 0.122875E+09 | 0.00 | 0.122875E+09 | 19013293.78 | 0.462308E+09 |
March | 0.171632E+09 | 5966.21 | 0.171626E+09 | 69666869.73 | 0.389832E+09 |
April | 0.211848E+09 | 2837829.67 | 0.209010E+09 | 0.133569E+09 | 0.238048E+09 |
May | 0.236946E+09 | 15395335.14 | 0.221551E+09 | 0.214790E+09 | 0.159758E+09 |
June | 0.261069E+09 | 43416898.60 | 0.217652E+09 | 0.365579E+09 | 83726058.18 |
July | 0.247377E+09 | 21085524.22 | 0.226291E+09 | 0.393257E+09 | 43990546.52 |
August | 0.229577E+09 | 5618487.49 | 0.223958E+09 | 0.320567E+09 | 57531245.65 |
September | 0.177358E+09 | 126386.42 | 0.177232E+09 | 0.200829E+09 | 0.132448E+09 |
October | 0.136621E+09 | 0.00 | 0.136621E+09 | 79523354.30 | 0.285480E+09 |
November | 0.112281E+09 | 0.00 | 0.112281E+09 | 12976872.68 | 0.424708E+09 |
December | 92645119.08 | 0.00 | 92645119.08 | 686070.87 | 0.596626E+09 |
Annual Sum or Average | 0.210908E+10 | 88486427.75 | 0.202059E+10 | 0.181549E+10 | 0.344455E+10 |
Minimum of Months | 92645119.08 | 0.00 | 92645119.08 | 686070.87 | 43990546.52 |
Maximum of Months | 0.261069E+09 | 43416898.60 | 0.226291E+09 | 0.393257E+09 | 0.596626E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.563470E+09 | 0.315381E+09 | 0.248090E+09 | 0.405580E+09 | 0.949203E+09 |
February | 0.616324E+09 | 0.331304E+09 | 0.285020E+09 | 0.500259E+09 | 0.773536E+09 |
March | 0.906790E+09 | 0.516599E+09 | 0.390191E+09 | 0.874972E+09 | 0.650117E+09 |
April | 0.119042E+10 | 0.677420E+09 | 0.513002E+09 | 0.133297E+10 | 0.410293E+09 |
May | 0.117518E+10 | 0.669373E+09 | 0.505803E+09 | 0.142117E+10 | 0.298784E+09 |
June | 0.122648E+10 | 0.755467E+09 | 0.471011E+09 | 0.169909E+10 | 0.157555E+09 |
July | 0.117212E+10 | 0.670052E+09 | 0.502064E+09 | 0.173215E+10 | 82166404.36 |
August | 0.116010E+10 | 0.639431E+09 | 0.520667E+09 | 0.163210E+10 | 0.106723E+09 |
September | 0.936174E+09 | 0.523838E+09 | 0.412337E+09 | 0.122335E+10 | 0.231663E+09 |
October | 0.842823E+09 | 0.535210E+09 | 0.307613E+09 | 0.926091E+09 | 0.475748E+09 |
November | 0.634355E+09 | 0.372138E+09 | 0.262217E+09 | 0.542343E+09 | 0.711104E+09 |
December | 0.533938E+09 | 0.325687E+09 | 0.208251E+09 | 0.401972E+09 | 0.996617E+09 |
Annual Sum or Average | 0.109582E+11 | 0.633190E+10 | 0.462627E+10 | 0.126921E+11 | 0.584351E+10 |
Minimum of Months | 0.533938E+09 | 0.315381E+09 | 0.208251E+09 | 0.401972E+09 | 82166404.36 |
Maximum of Months | 0.122648E+10 | 0.755467E+09 | 0.520667E+09 | 0.173215E+10 | 0.996617E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137848E+09 | 0.00 | 0.137848E+09 | 2667447.98 | 0.854528E+09 |
February | 0.155614E+09 | 0.00 | 0.155614E+09 | 17312194.55 | 0.690592E+09 |
March | 0.217361E+09 | 7555.83 | 0.217354E+09 | 81073838.76 | 0.574057E+09 |
April | 0.268292E+09 | 3593932.22 | 0.264698E+09 | 0.170967E+09 | 0.344046E+09 |
May | 0.300077E+09 | 19497220.56 | 0.280580E+09 | 0.278340E+09 | 0.237243E+09 |
June | 0.330628E+09 | 54984762.62 | 0.275643E+09 | 0.478885E+09 | 0.133674E+09 |
July | 0.313287E+09 | 26703486.00 | 0.286583E+09 | 0.514202E+09 | 79952833.69 |
August | 0.290744E+09 | 7115459.90 | 0.283629E+09 | 0.422046E+09 | 98249570.14 |
September | 0.224613E+09 | 160060.43 | 0.224453E+09 | 0.260135E+09 | 0.196932E+09 |
October | 0.173022E+09 | 0.00 | 0.173022E+09 | 96417533.01 | 0.423593E+09 |
November | 0.142197E+09 | 0.00 | 0.142197E+09 | 10593855.89 | 0.647209E+09 |
December | 0.117329E+09 | 0.00 | 0.117329E+09 | 416890.09 | 0.901713E+09 |
Annual Sum or Average | 0.267101E+10 | 0.112062E+09 | 0.255895E+10 | 0.233306E+10 | 0.518179E+10 |
Minimum of Months | 0.117329E+09 | 0.00 | 0.117329E+09 | 416890.09 | 79952833.69 |
Maximum of Months | 0.330628E+09 | 54984762.62 | 0.286583E+09 | 0.514202E+09 | 0.901713E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50816411.18 | 0.00 | 50816411.18 | 983331.78 | 0.315014E+09 |
February | 57365622.32 | 0.00 | 57365622.32 | 6381991.75 | 0.254580E+09 |
March | 80128364.71 | 2785.39 | 80125579.31 | 29887173.97 | 0.211621E+09 |
April | 98903363.85 | 1324872.23 | 97578491.62 | 63025633.63 | 0.126830E+09 |
May | 0.110621E+09 | 7187482.82 | 0.103433E+09 | 0.102608E+09 | 87457660.04 |
June | 0.121883E+09 | 20269660.24 | 0.101613E+09 | 0.176537E+09 | 49277906.90 |
July | 0.115490E+09 | 9844010.64 | 0.105646E+09 | 0.189556E+09 | 29473925.08 |
August | 0.107180E+09 | 2623053.15 | 0.104557E+09 | 0.155584E+09 | 36218859.75 |
September | 82801643.63 | 59004.90 | 82742638.73 | 95896538.62 | 72597219.62 |
October | 63783196.41 | 0.00 | 63783196.41 | 35543495.00 | 0.156154E+09 |
November | 52419775.69 | 0.00 | 52419775.69 | 3905333.94 | 0.238588E+09 |
December | 43252400.50 | 0.00 | 43252400.50 | 153682.95 | 0.332409E+09 |
Annual Sum or Average | 0.984646E+09 | 41310869.37 | 0.943335E+09 | 0.860062E+09 | 0.191022E+10 |
Minimum of Months | 43252400.50 | 0.00 | 43252400.50 | 153682.95 | 29473925.08 |
Maximum of Months | 0.121883E+09 | 20269660.24 | 0.105646E+09 | 0.189556E+09 | 0.332409E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.374814E+09 | 0.291480E+09 | 83334033.15 | 0.399299E+09 | 0.260379E+09 |
February | 0.333705E+09 | 0.244227E+09 | 89478636.15 | 0.362836E+09 | 0.218294E+09 |
March | 0.274727E+09 | 0.167641E+09 | 0.107087E+09 | 0.301515E+09 | 0.195070E+09 |
April | 0.204185E+09 | 83677678.65 | 0.120507E+09 | 0.234366E+09 | 0.128689E+09 |
May | 0.141998E+09 | 32123835.32 | 0.109875E+09 | 0.167579E+09 | 94213036.72 |
June | 0.114877E+09 | 13794272.49 | 0.101083E+09 | 0.175860E+09 | 54722259.26 |
July | 0.131401E+09 | 20617688.42 | 0.110783E+09 | 0.224317E+09 | 30970893.77 |
August | 0.178750E+09 | 56376988.64 | 0.122373E+09 | 0.281549E+09 | 38341628.45 |
September | 0.245572E+09 | 0.138236E+09 | 0.107336E+09 | 0.348119E+09 | 71556691.83 |
October | 0.341875E+09 | 0.251477E+09 | 90397980.71 | 0.423119E+09 | 0.137997E+09 |
November | 0.373205E+09 | 0.287225E+09 | 85979612.01 | 0.414429E+09 | 0.198704E+09 |
December | 0.408738E+09 | 0.337409E+09 | 71329678.86 | 0.440966E+09 | 0.265132E+09 |
Annual Sum or Average | 0.312385E+10 | 0.192428E+10 | 0.119956E+10 | 0.377395E+10 | 0.169407E+10 |
Minimum of Months | 0.114877E+09 | 13794272.49 | 71329678.86 | 0.167579E+09 | 30970893.77 |
Maximum of Months | 0.408738E+09 | 0.337409E+09 | 0.122373E+09 | 0.440966E+09 | 0.265132E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101732E+10 | 0.791136E+09 | 0.226186E+09 | 0.108378E+10 | 0.706723E+09 |
February | 0.905744E+09 | 0.662881E+09 | 0.242863E+09 | 0.984811E+09 | 0.592493E+09 |
March | 0.745666E+09 | 0.455011E+09 | 0.290656E+09 | 0.818373E+09 | 0.529459E+09 |
April | 0.554199E+09 | 0.227118E+09 | 0.327081E+09 | 0.636117E+09 | 0.349288E+09 |
May | 0.385413E+09 | 87190659.85 | 0.298222E+09 | 0.454843E+09 | 0.255713E+09 |
June | 0.311801E+09 | 37440477.09 | 0.274361E+09 | 0.477319E+09 | 0.148527E+09 |
July | 0.356648E+09 | 55960623.62 | 0.300688E+09 | 0.608841E+09 | 84061340.63 |
August | 0.485163E+09 | 0.153019E+09 | 0.332145E+09 | 0.764182E+09 | 0.104067E+09 |
September | 0.666533E+09 | 0.375200E+09 | 0.291333E+09 | 0.944865E+09 | 0.194219E+09 |
October | 0.927918E+09 | 0.682560E+09 | 0.245359E+09 | 0.114843E+10 | 0.374553E+09 |
November | 0.101295E+10 | 0.779587E+09 | 0.233366E+09 | 0.112485E+10 | 0.539325E+09 |
December | 0.110940E+10 | 0.915796E+09 | 0.193603E+09 | 0.119687E+10 | 0.719622E+09 |
Annual Sum or Average | 0.847876E+10 | 0.522290E+10 | 0.325586E+10 | 0.102433E+11 | 0.459805E+10 |
Minimum of Months | 0.311801E+09 | 37440477.09 | 0.193603E+09 | 0.454843E+09 | 84061340.63 |
Maximum of Months | 0.110940E+10 | 0.915796E+09 | 0.332145E+09 | 0.119687E+10 | 0.719622E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.803294E+09 | 0.624694E+09 | 0.178600E+09 | 0.866564E+09 | 0.480950E+09 |
February | 0.715191E+09 | 0.523422E+09 | 0.191769E+09 | 0.782890E+09 | 0.401840E+09 |
March | 0.588791E+09 | 0.359284E+09 | 0.229507E+09 | 0.651623E+09 | 0.352634E+09 |
April | 0.437605E+09 | 0.179336E+09 | 0.258268E+09 | 0.501177E+09 | 0.226095E+09 |
May | 0.304329E+09 | 68847219.79 | 0.235481E+09 | 0.359742E+09 | 0.155883E+09 |
June | 0.246203E+09 | 29563633.99 | 0.216640E+09 | 0.378334E+09 | 83469579.73 |
July | 0.281616E+09 | 44187454.95 | 0.237428E+09 | 0.481824E+09 | 38066595.55 |
August | 0.383093E+09 | 0.120826E+09 | 0.262267E+09 | 0.600296E+09 | 50787999.72 |
September | 0.526305E+09 | 0.296264E+09 | 0.230042E+09 | 0.740487E+09 | 0.113592E+09 |
October | 0.732700E+09 | 0.538961E+09 | 0.193739E+09 | 0.907805E+09 | 0.241650E+09 |
November | 0.799845E+09 | 0.615575E+09 | 0.184270E+09 | 0.895413E+09 | 0.357877E+09 |
December | 0.876000E+09 | 0.723128E+09 | 0.152872E+09 | 0.955509E+09 | 0.486710E+09 |
Annual Sum or Average | 0.669497E+10 | 0.412409E+10 | 0.257088E+10 | 0.812166E+10 | 0.298955E+10 |
Minimum of Months | 0.246203E+09 | 29563633.99 | 0.152872E+09 | 0.359742E+09 | 38066595.55 |
Maximum of Months | 0.876000E+09 | 0.723128E+09 | 0.262267E+09 | 0.955509E+09 | 0.486710E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581104E+09 | 0.331407E+09 | 0.249697E+09 | 0.469717E+09 | 0.100613E+10 |
February | 0.674302E+09 | 0.389082E+09 | 0.285221E+09 | 0.594771E+09 | 0.821664E+09 |
March | 0.833010E+09 | 0.442493E+09 | 0.390517E+09 | 0.803248E+09 | 0.684381E+09 |
April | 0.103135E+10 | 0.548902E+09 | 0.482452E+09 | 0.111706E+10 | 0.410177E+09 |
May | 0.101345E+10 | 0.523637E+09 | 0.489810E+09 | 0.120835E+10 | 0.283275E+09 |
June | 0.104505E+10 | 0.582014E+09 | 0.463034E+09 | 0.148381E+10 | 0.156238E+09 |
July | 0.974991E+09 | 0.476425E+09 | 0.498566E+09 | 0.147804E+10 | 71745289.70 |
August | 0.997320E+09 | 0.460622E+09 | 0.536698E+09 | 0.143269E+10 | 95247560.69 |
September | 0.875696E+09 | 0.462348E+09 | 0.413348E+09 | 0.115161E+10 | 0.214030E+09 |
October | 0.828111E+09 | 0.515813E+09 | 0.312297E+09 | 0.926865E+09 | 0.490589E+09 |
November | 0.626217E+09 | 0.368379E+09 | 0.257838E+09 | 0.549374E+09 | 0.743615E+09 |
December | 0.555650E+09 | 0.346979E+09 | 0.208671E+09 | 0.440247E+09 | 0.103505E+10 |
Annual Sum or Average | 0.100363E+11 | 0.544810E+10 | 0.458815E+10 | 0.116558E+11 | 0.601214E+10 |
Minimum of Months | 0.555650E+09 | 0.331407E+09 | 0.208671E+09 | 0.440247E+09 | 71745289.70 |
Maximum of Months | 0.104505E+10 | 0.582014E+09 | 0.536698E+09 | 0.148381E+10 | 0.103505E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108847E+09 | 0.00 | 0.108847E+09 | 8796541.30 | 0.552940E+09 |
February | 0.122875E+09 | 0.00 | 0.122875E+09 | 22724977.56 | 0.452834E+09 |
March | 0.171632E+09 | 5966.21 | 0.171626E+09 | 74661779.72 | 0.385068E+09 |
April | 0.211848E+09 | 2837829.67 | 0.209010E+09 | 0.134923E+09 | 0.242003E+09 |
May | 0.236946E+09 | 15395335.14 | 0.221551E+09 | 0.218525E+09 | 0.161037E+09 |
June | 0.261069E+09 | 43416898.60 | 0.217652E+09 | 0.373599E+09 | 83617089.01 |
July | 0.247377E+09 | 21085524.22 | 0.226291E+09 | 0.400405E+09 | 42214600.01 |
August | 0.229577E+09 | 5618487.49 | 0.223958E+09 | 0.327504E+09 | 57225074.07 |
September | 0.177358E+09 | 126386.42 | 0.177232E+09 | 0.203704E+09 | 0.132531E+09 |
October | 0.136621E+09 | 0.00 | 0.136621E+09 | 81960523.45 | 0.288048E+09 |
November | 0.112281E+09 | 0.00 | 0.112281E+09 | 17315512.34 | 0.410247E+09 |
December | 92645119.08 | 0.00 | 92645119.08 | 1468679.48 | 0.575197E+09 |
Annual Sum or Average | 0.210908E+10 | 88486427.75 | 0.202059E+10 | 0.186559E+10 | 0.338296E+10 |
Minimum of Months | 92645119.08 | 0.00 | 92645119.08 | 1468679.48 | 42214600.01 |
Maximum of Months | 0.261069E+09 | 43416898.60 | 0.226291E+09 | 0.400405E+09 | 0.575197E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581104E+09 | 0.331407E+09 | 0.249697E+09 | 0.498476E+09 | 0.980178E+09 |
February | 0.674302E+09 | 0.389082E+09 | 0.285221E+09 | 0.619888E+09 | 0.803601E+09 |
March | 0.833010E+09 | 0.442493E+09 | 0.390517E+09 | 0.812628E+09 | 0.687326E+09 |
April | 0.103135E+10 | 0.548902E+09 | 0.482452E+09 | 0.110901E+10 | 0.443577E+09 |
May | 0.101345E+10 | 0.523637E+09 | 0.489810E+09 | 0.119684E+10 | 0.312832E+09 |
June | 0.104505E+10 | 0.582014E+09 | 0.463034E+09 | 0.146728E+10 | 0.169668E+09 |
July | 0.974991E+09 | 0.476425E+09 | 0.498566E+09 | 0.146268E+10 | 82616881.07 |
August | 0.997320E+09 | 0.460622E+09 | 0.536698E+09 | 0.142198E+10 | 0.112503E+09 |
September | 0.875696E+09 | 0.462348E+09 | 0.413348E+09 | 0.115562E+10 | 0.246894E+09 |
October | 0.828111E+09 | 0.515813E+09 | 0.312297E+09 | 0.935706E+09 | 0.515549E+09 |
November | 0.626217E+09 | 0.368379E+09 | 0.257838E+09 | 0.575677E+09 | 0.723010E+09 |
December | 0.555650E+09 | 0.346979E+09 | 0.208671E+09 | 0.470170E+09 | 0.100179E+10 |
Annual Sum or Average | 0.100363E+11 | 0.544810E+10 | 0.458815E+10 | 0.117260E+11 | 0.607955E+10 |
Minimum of Months | 0.555650E+09 | 0.331407E+09 | 0.208671E+09 | 0.470170E+09 | 82616881.07 |
Maximum of Months | 0.104505E+10 | 0.582014E+09 | 0.536698E+09 | 0.146728E+10 | 0.100179E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117811E+10 | 0.916174E+09 | 0.261934E+09 | 0.124117E+10 | 0.731514E+09 |
February | 0.104890E+10 | 0.767649E+09 | 0.281248E+09 | 0.112676E+10 | 0.607140E+09 |
March | 0.863518E+09 | 0.526925E+09 | 0.336594E+09 | 0.943582E+09 | 0.526216E+09 |
April | 0.641790E+09 | 0.263014E+09 | 0.378775E+09 | 0.737347E+09 | 0.327879E+09 |
May | 0.446327E+09 | 0.100971E+09 | 0.345356E+09 | 0.539141E+09 | 0.223318E+09 |
June | 0.361081E+09 | 43357906.48 | 0.317723E+09 | 0.576519E+09 | 0.118053E+09 |
July | 0.413016E+09 | 64805143.36 | 0.348211E+09 | 0.727900E+09 | 52573804.09 |
August | 0.561843E+09 | 0.177203E+09 | 0.384640E+09 | 0.896218E+09 | 71010002.44 |
September | 0.771877E+09 | 0.434500E+09 | 0.337378E+09 | 0.108845E+10 | 0.164461E+09 |
October | 0.107458E+10 | 0.790438E+09 | 0.284137E+09 | 0.131927E+10 | 0.360522E+09 |
November | 0.117305E+10 | 0.902800E+09 | 0.270250E+09 | 0.128911E+10 | 0.543019E+09 |
December | 0.128474E+10 | 0.106054E+10 | 0.224202E+09 | 0.136886E+10 | 0.742012E+09 |
Annual Sum or Average | 0.981882E+10 | 0.604837E+10 | 0.377045E+10 | 0.118543E+11 | 0.446772E+10 |
Minimum of Months | 0.361081E+09 | 43357906.48 | 0.224202E+09 | 0.539141E+09 | 52573804.09 |
Maximum of Months | 0.128474E+10 | 0.106054E+10 | 0.384640E+09 | 0.136886E+10 | 0.742012E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761900E+09 | 0.00 | 0.761900E+09 | 24066935.05 | 0.452283E+10 |
February | 0.860093E+09 | 0.00 | 0.860093E+09 | 0.104420E+09 | 0.370065E+10 |
March | 0.120138E+10 | 41761.91 | 0.120134E+10 | 0.438313E+09 | 0.316661E+10 |
April | 0.148288E+10 | 19864055.37 | 0.146301E+10 | 0.869986E+09 | 0.194124E+10 |
May | 0.165856E+10 | 0.107763E+09 | 0.155080E+10 | 0.141764E+10 | 0.137511E+10 |
June | 0.182741E+10 | 0.303907E+09 | 0.152351E+10 | 0.249405E+10 | 0.802449E+09 |
July | 0.173157E+10 | 0.147593E+09 | 0.158398E+10 | 0.268073E+10 | 0.515801E+09 |
August | 0.160698E+10 | 39327922.90 | 0.156765E+10 | 0.218958E+10 | 0.621408E+09 |
September | 0.124146E+10 | 884671.44 | 0.124058E+10 | 0.134694E+10 | 0.115320E+10 |
October | 0.956313E+09 | 0.00 | 0.956313E+09 | 0.504458E+09 | 0.234915E+10 |
November | 0.785939E+09 | 0.00 | 0.785939E+09 | 65057788.85 | 0.347251E+10 |
December | 0.648491E+09 | 0.00 | 0.648491E+09 | 3025693.89 | 0.472107E+10 |
Annual Sum or Average | 0.147630E+11 | 0.619382E+09 | 0.141436E+11 | 0.121383E+11 | 0.283420E+11 |
Minimum of Months | 0.648491E+09 | 0.00 | 0.648491E+09 | 3025693.89 | 0.515801E+09 |
Maximum of Months | 0.182741E+10 | 0.303907E+09 | 0.158398E+10 | 0.268073E+10 | 0.472107E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761900E+09 | 0.00 | 0.761900E+09 | 17281109.28 | 0.467287E+10 |
February | 0.860093E+09 | 0.00 | 0.860093E+09 | 89616383.85 | 0.381487E+10 |
March | 0.120138E+10 | 41761.91 | 0.120134E+10 | 0.405662E+09 | 0.324392E+10 |
April | 0.148288E+10 | 19864055.37 | 0.146301E+10 | 0.835725E+09 | 0.198288E+10 |
May | 0.165856E+10 | 0.107763E+09 | 0.155080E+10 | 0.138362E+10 | 0.140558E+10 |
June | 0.182741E+10 | 0.303907E+09 | 0.152351E+10 | 0.246307E+10 | 0.822617E+09 |
July | 0.173157E+10 | 0.147593E+09 | 0.158398E+10 | 0.265161E+10 | 0.534865E+09 |
August | 0.160698E+10 | 39327922.90 | 0.156765E+10 | 0.216096E+10 | 0.642832E+09 |
September | 0.124146E+10 | 884671.44 | 0.124058E+10 | 0.132131E+10 | 0.118212E+10 |
October | 0.956313E+09 | 0.00 | 0.956313E+09 | 0.480659E+09 | 0.240831E+10 |
November | 0.785939E+09 | 0.00 | 0.785939E+09 | 54784226.22 | 0.357615E+10 |
December | 0.648491E+09 | 0.00 | 0.648491E+09 | 2392250.18 | 0.487847E+10 |
Annual Sum or Average | 0.147630E+11 | 0.619382E+09 | 0.141436E+11 | 0.118667E+11 | 0.291655E+11 |
Minimum of Months | 0.648491E+09 | 0.00 | 0.648491E+09 | 2392250.18 | 0.534865E+09 |
Maximum of Months | 0.182741E+10 | 0.303907E+09 | 0.158398E+10 | 0.265161E+10 | 0.487847E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108847E+09 | 0.00 | 0.108847E+09 | 1516211.65 | 0.689807E+09 |
February | 0.122875E+09 | 0.00 | 0.122875E+09 | 10681292.93 | 0.565274E+09 |
March | 0.171632E+09 | 5966.21 | 0.171626E+09 | 53055731.16 | 0.480608E+09 |
April | 0.211848E+09 | 2837829.67 | 0.209010E+09 | 0.120075E+09 | 0.298083E+09 |
May | 0.236946E+09 | 15395335.14 | 0.221551E+09 | 0.203555E+09 | 0.216373E+09 |
June | 0.261069E+09 | 43416898.60 | 0.217652E+09 | 0.366327E+09 | 0.131471E+09 |
July | 0.247377E+09 | 21085524.22 | 0.226291E+09 | 0.395865E+09 | 90890013.49 |
August | 0.229577E+09 | 5618487.49 | 0.223958E+09 | 0.325205E+09 | 0.106830E+09 |
September | 0.177358E+09 | 126386.42 | 0.177232E+09 | 0.200021E+09 | 0.179996E+09 |
October | 0.136621E+09 | 0.00 | 0.136621E+09 | 71239330.84 | 0.357021E+09 |
November | 0.112281E+09 | 0.00 | 0.112281E+09 | 6850341.35 | 0.527697E+09 |
December | 92645119.08 | 0.00 | 92645119.08 | 229611.91 | 0.720886E+09 |
Annual Sum or Average | 0.210908E+10 | 88486427.75 | 0.202059E+10 | 0.175462E+10 | 0.436494E+10 |
Minimum of Months | 92645119.08 | 0.00 | 92645119.08 | 229611.91 | 90890013.49 |
Maximum of Months | 0.261069E+09 | 43416898.60 | 0.226291E+09 | 0.395865E+09 | 0.720886E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112686E+10 | 0.630716E+09 | 0.496144E+09 | 0.752839E+09 | 0.229904E+10 |
February | 0.123256E+10 | 0.662561E+09 | 0.569999E+09 | 0.931708E+09 | 0.188118E+10 |
March | 0.181345E+10 | 0.103312E+10 | 0.780327E+09 | 0.166091E+10 | 0.160411E+10 |
April | 0.238068E+10 | 0.135474E+10 | 0.102593E+10 | 0.260483E+10 | 0.102738E+10 |
May | 0.235019E+10 | 0.133865E+10 | 0.101153E+10 | 0.279955E+10 | 0.802325E+09 |
June | 0.245278E+10 | 0.151083E+10 | 0.941955E+09 | 0.339677E+10 | 0.495176E+09 |
July | 0.234406E+10 | 0.134001E+10 | 0.100406E+10 | 0.347535E+10 | 0.342211E+09 |
August | 0.232003E+10 | 0.127877E+10 | 0.104126E+10 | 0.328042E+10 | 0.399244E+09 |
September | 0.187222E+10 | 0.104760E+10 | 0.824615E+09 | 0.244042E+10 | 0.641112E+09 |
October | 0.168553E+10 | 0.107034E+10 | 0.615182E+09 | 0.180383E+10 | 0.119162E+10 |
November | 0.126862E+10 | 0.744224E+09 | 0.524397E+09 | 0.102367E+10 | 0.176029E+10 |
December | 0.106780E+10 | 0.651329E+09 | 0.416472E+09 | 0.756732E+09 | 0.240761E+10 |
Annual Sum or Average | 0.219148E+11 | 0.126629E+11 | 0.925187E+10 | 0.249270E+11 | 0.148513E+11 |
Minimum of Months | 0.106780E+10 | 0.630716E+09 | 0.416472E+09 | 0.752839E+09 | 0.342211E+09 |
Maximum of Months | 0.245278E+10 | 0.151083E+10 | 0.104126E+10 | 0.347535E+10 | 0.240761E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.803294E+09 | 0.624694E+09 | 0.178600E+09 | 0.851894E+09 | 0.568247E+09 |
February | 0.715191E+09 | 0.523422E+09 | 0.191769E+09 | 0.772081E+09 | 0.479063E+09 |
March | 0.588791E+09 | 0.359284E+09 | 0.229507E+09 | 0.633361E+09 | 0.438392E+09 |
April | 0.437605E+09 | 0.179336E+09 | 0.258268E+09 | 0.486544E+09 | 0.300808E+09 |
May | 0.304329E+09 | 68847219.79 | 0.235481E+09 | 0.343992E+09 | 0.230932E+09 |
June | 0.246203E+09 | 29563633.99 | 0.216640E+09 | 0.364499E+09 | 0.144284E+09 |
July | 0.281616E+09 | 44187454.95 | 0.237428E+09 | 0.469668E+09 | 94307484.57 |
August | 0.383093E+09 | 0.120826E+09 | 0.262267E+09 | 0.595513E+09 | 0.112095E+09 |
September | 0.526305E+09 | 0.296264E+09 | 0.230042E+09 | 0.741321E+09 | 0.178167E+09 |
October | 0.732700E+09 | 0.538961E+09 | 0.193739E+09 | 0.903936E+09 | 0.315231E+09 |
November | 0.799845E+09 | 0.615575E+09 | 0.184270E+09 | 0.886566E+09 | 0.437383E+09 |
December | 0.876000E+09 | 0.723128E+09 | 0.152872E+09 | 0.944612E+09 | 0.574801E+09 |
Annual Sum or Average | 0.669497E+10 | 0.412409E+10 | 0.257088E+10 | 0.799399E+10 | 0.387371E+10 |
Minimum of Months | 0.246203E+09 | 29563633.99 | 0.152872E+09 | 0.343992E+09 | 94307484.57 |
Maximum of Months | 0.876000E+09 | 0.723128E+09 | 0.262267E+09 | 0.944612E+09 | 0.574801E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137848E+09 | 0.00 | 0.137848E+09 | 3473999.40 | 0.789564E+09 |
February | 0.155614E+09 | 0.00 | 0.155614E+09 | 16720245.79 | 0.646922E+09 |
March | 0.217361E+09 | 7555.83 | 0.217354E+09 | 76415125.79 | 0.556712E+09 |
April | 0.268292E+09 | 3593932.22 | 0.264698E+09 | 0.159099E+09 | 0.341219E+09 |
May | 0.300077E+09 | 19497220.56 | 0.280580E+09 | 0.262936E+09 | 0.239710E+09 |
June | 0.330628E+09 | 54984762.62 | 0.275643E+09 | 0.460362E+09 | 0.137869E+09 |
July | 0.313287E+09 | 26703486.00 | 0.286583E+09 | 0.493645E+09 | 85394399.21 |
August | 0.290744E+09 | 7115459.90 | 0.283629E+09 | 0.402379E+09 | 0.104190E+09 |
September | 0.224613E+09 | 160060.43 | 0.224453E+09 | 0.245002E+09 | 0.201657E+09 |
October | 0.173022E+09 | 0.00 | 0.173022E+09 | 87452392.31 | 0.417812E+09 |
November | 0.142197E+09 | 0.00 | 0.142197E+09 | 9520478.49 | 0.622957E+09 |
December | 0.117329E+09 | 0.00 | 0.117329E+09 | 441912.91 | 0.828402E+09 |
Annual Sum or Average | 0.267101E+10 | 0.112062E+09 | 0.255895E+10 | 0.221745E+10 | 0.497241E+10 |
Minimum of Months | 0.117329E+09 | 0.00 | 0.117329E+09 | 441912.91 | 85394399.21 |
Maximum of Months | 0.330628E+09 | 54984762.62 | 0.286583E+09 | 0.493645E+09 | 0.828402E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123333E+09 | 0.00 | 0.123333E+09 | 3108200.42 | 0.706327E+09 |
February | 0.139228E+09 | 0.00 | 0.139228E+09 | 14959667.26 | 0.578807E+09 |
March | 0.194474E+09 | 6760.23 | 0.194467E+09 | 68368902.58 | 0.498092E+09 |
April | 0.240041E+09 | 3215504.78 | 0.236826E+09 | 0.142347E+09 | 0.305290E+09 |
May | 0.268480E+09 | 17444237.11 | 0.251036E+09 | 0.235250E+09 | 0.214470E+09 |
June | 0.295814E+09 | 49195075.45 | 0.246619E+09 | 0.411887E+09 | 0.123352E+09 |
July | 0.280299E+09 | 23891710.10 | 0.256407E+09 | 0.441666E+09 | 76402692.54 |
August | 0.260130E+09 | 6366228.93 | 0.253764E+09 | 0.360010E+09 | 93218925.84 |
September | 0.200962E+09 | 143206.67 | 0.200819E+09 | 0.219205E+09 | 0.180423E+09 |
October | 0.154804E+09 | 0.00 | 0.154804E+09 | 78243986.76 | 0.373820E+09 |
November | 0.127224E+09 | 0.00 | 0.127224E+09 | 8518008.18 | 0.557335E+09 |
December | 0.104975E+09 | 0.00 | 0.104975E+09 | 395381.15 | 0.741126E+09 |
Annual Sum or Average | 0.238976E+10 | 0.100263E+09 | 0.228950E+10 | 0.198396E+10 | 0.444866E+10 |
Minimum of Months | 0.104975E+09 | 0.00 | 0.104975E+09 | 395381.15 | 76402692.54 |
Maximum of Months | 0.295814E+09 | 49195075.45 | 0.256407E+09 | 0.441666E+09 | 0.741126E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299894E+10 | 0.233217E+10 | 0.666767E+09 | 0.321362E+10 | 0.193002E+10 |
February | 0.267002E+10 | 0.195409E+10 | 0.715931E+09 | 0.290578E+10 | 0.163879E+10 |
March | 0.219813E+10 | 0.134131E+10 | 0.856817E+09 | 0.238738E+10 | 0.151696E+10 |
April | 0.163371E+10 | 0.669517E+09 | 0.964193E+09 | 0.182779E+10 | 0.102422E+10 |
May | 0.113615E+10 | 0.257027E+09 | 0.879122E+09 | 0.129019E+10 | 0.762768E+09 |
June | 0.919150E+09 | 0.110370E+09 | 0.808781E+09 | 0.135383E+10 | 0.451738E+09 |
July | 0.105135E+10 | 0.164965E+09 | 0.886390E+09 | 0.173116E+10 | 0.265677E+09 |
August | 0.143020E+10 | 0.451080E+09 | 0.979121E+09 | 0.218676E+10 | 0.326135E+09 |
September | 0.196486E+10 | 0.110604E+10 | 0.858814E+09 | 0.272561E+10 | 0.587829E+09 |
October | 0.273539E+10 | 0.201210E+10 | 0.723287E+09 | 0.334460E+10 | 0.108964E+10 |
November | 0.298606E+10 | 0.229813E+10 | 0.687935E+09 | 0.330323E+10 | 0.152428E+10 |
December | 0.327037E+10 | 0.269965E+10 | 0.570718E+09 | 0.355226E+10 | 0.194702E+10 |
Annual Sum or Average | 0.249943E+11 | 0.153965E+11 | 0.959787E+10 | 0.298222E+11 | 0.130651E+11 |
Minimum of Months | 0.919150E+09 | 0.110370E+09 | 0.570718E+09 | 0.129019E+10 | 0.265677E+09 |
Maximum of Months | 0.327037E+10 | 0.269965E+10 | 0.979121E+09 | 0.355226E+10 | 0.194702E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1419.20 | 782.75 | 1320.63 | 1027.01 | 293.62 | 0.00 | 0.00 |
February | 1426.59 | 724.03 | 1301.76 | 952.71 | 349.05 | 0.00 | 0.00 |
March | 1082.28 | 578.22 | 967.98 | 590.67 | 377.31 | 0.00 | 0.00 |
April | 859.69 | 403.01 | 743.41 | 304.66 | 438.75 | 0.00 | 0.00 |
May | 589.60 | 287.05 | 500.32 | 113.19 | 387.14 | 0.00 | 0.00 |
June | 608.74 | 182.78 | 418.26 | 50.22 | 368.03 | 0.00 | 0.00 |
July | 745.71 | 111.51 | 462.98 | 72.65 | 390.34 | 0.00 | 0.00 |
August | 953.29 | 135.82 | 629.81 | 198.64 | 431.17 | 0.00 | 0.00 |
September | 1241.79 | 245.22 | 894.10 | 503.30 | 390.80 | 0.00 | 0.00 |
October | 1476.75 | 430.69 | 1204.57 | 886.06 | 318.51 | 0.00 | 0.00 |
November | 1509.72 | 621.90 | 1358.79 | 1045.75 | 313.04 | 0.00 | 0.00 |
December | 1556.12 | 800.10 | 1440.16 | 1188.84 | 251.33 | 0.00 | 0.00 |
Annual Sum or Average | 1120.70 | 440.47 | 934.81 | 575.84 | 358.97 | 0.00 | 0.00 |
Minimum of Months | 589.60 | 111.51 | 418.26 | 50.22 | 251.33 | 0.00 | 0.00 |
Maximum of Months | 1556.12 | 800.10 | 1440.16 | 1188.84 | 438.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3977.41 | 2220.77 | 3718.81 | 2891.99 | 826.82 | 0.00 | 0.00 |
February | 3993.65 | 2068.71 | 3665.68 | 2682.78 | 982.90 | 0.00 | 0.00 |
March | 3002.69 | 1708.14 | 2725.78 | 1663.29 | 1062.49 | 0.00 | 0.00 |
April | 2365.27 | 1224.51 | 2093.40 | 857.90 | 1235.50 | 0.00 | 0.00 |
May | 1593.05 | 904.72 | 1408.87 | 318.72 | 1090.15 | 0.00 | 0.00 |
June | 1664.82 | 574.79 | 1177.78 | 141.43 | 1036.35 | 0.00 | 0.00 |
July | 2064.81 | 347.28 | 1303.73 | 204.56 | 1099.16 | 0.00 | 0.00 |
August | 2647.34 | 420.85 | 1773.51 | 559.36 | 1214.15 | 0.00 | 0.00 |
September | 3451.20 | 753.29 | 2517.72 | 1417.26 | 1100.46 | 0.00 | 0.00 |
October | 4114.98 | 1289.33 | 3392.00 | 2495.09 | 896.91 | 0.00 | 0.00 |
November | 4219.47 | 1821.70 | 3826.27 | 2944.77 | 881.50 | 0.00 | 0.00 |
December | 4369.45 | 2269.18 | 4055.40 | 3347.68 | 707.72 | 0.00 | 0.00 |
Annual Sum or Average | 3117.00 | 1296.22 | 2632.37 | 1621.53 | 1010.84 | 0.00 | 0.00 |
Minimum of Months | 1593.05 | 347.28 | 1177.78 | 141.43 | 707.72 | 0.00 | 0.00 |
Maximum of Months | 4369.45 | 2269.18 | 4055.40 | 3347.68 | 1235.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5243.02 | 3152.01 | 4830.94 | 3756.86 | 1074.09 | 0.00 | 0.00 |
February | 5284.14 | 2920.83 | 4761.93 | 3485.08 | 1276.85 | 0.00 | 0.00 |
March | 3992.10 | 2376.74 | 3540.94 | 2160.71 | 1380.23 | 0.00 | 0.00 |
April | 3181.02 | 1666.45 | 2719.44 | 1114.47 | 1604.98 | 0.00 | 0.00 |
May | 2172.81 | 1208.75 | 1830.21 | 414.04 | 1416.17 | 0.00 | 0.00 |
June | 2271.61 | 760.25 | 1530.00 | 183.72 | 1346.28 | 0.00 | 0.00 |
July | 2801.54 | 450.87 | 1693.61 | 265.74 | 1427.87 | 0.00 | 0.00 |
August | 3571.04 | 543.90 | 2303.89 | 726.64 | 1577.25 | 0.00 | 0.00 |
September | 4621.14 | 982.89 | 3270.66 | 1841.10 | 1429.57 | 0.00 | 0.00 |
October | 5470.87 | 1744.00 | 4406.40 | 3241.27 | 1165.13 | 0.00 | 0.00 |
November | 5576.18 | 2538.16 | 4970.54 | 3825.42 | 1145.12 | 0.00 | 0.00 |
December | 5758.97 | 3224.34 | 5268.20 | 4348.83 | 919.36 | 0.00 | 0.00 |
Annual Sum or Average | 4155.55 | 1791.60 | 3419.60 | 2106.47 | 1313.13 | 0.00 | 0.00 |
Minimum of Months | 2172.81 | 450.87 | 1530.00 | 183.72 | 919.36 | 0.00 | 0.00 |
Maximum of Months | 5758.97 | 3224.34 | 5268.20 | 4348.83 | 1604.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 470.74 | 540.18 | 516.87 | 356.97 | 159.91 | 0.00 | 0.00 |
February | 551.87 | 495.87 | 574.36 | 377.19 | 197.17 | 0.00 | 0.00 |
March | 538.13 | 386.58 | 530.84 | 299.35 | 231.49 | 0.00 | 0.00 |
April | 628.90 | 248.02 | 566.73 | 280.96 | 285.77 | 0.00 | 0.00 |
May | 591.62 | 167.04 | 492.00 | 221.21 | 270.79 | 0.00 | 0.00 |
June | 726.49 | 95.83 | 498.17 | 235.95 | 262.22 | 0.00 | 0.00 |
July | 740.86 | 43.42 | 469.16 | 194.37 | 274.79 | 0.00 | 0.00 |
August | 768.44 | 57.01 | 515.39 | 217.09 | 298.30 | 0.00 | 0.00 |
September | 737.44 | 129.92 | 540.90 | 292.67 | 248.22 | 0.00 | 0.00 |
October | 680.02 | 271.41 | 582.74 | 393.81 | 188.93 | 0.00 | 0.00 |
November | 535.37 | 413.71 | 550.18 | 379.61 | 170.57 | 0.00 | 0.00 |
December | 481.25 | 543.87 | 534.52 | 399.53 | 134.98 | 0.00 | 0.00 |
Annual Sum or Average | 621.10 | 281.65 | 530.54 | 303.53 | 227.01 | 0.00 | 0.00 |
Minimum of Months | 470.74 | 43.42 | 469.16 | 194.37 | 134.98 | 0.00 | 0.00 |
Maximum of Months | 768.44 | 543.87 | 582.74 | 399.53 | 298.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 177.49 | 579.48 | 257.60 | 123.73 | 133.86 | 0.00 | 0.00 |
February | 256.24 | 523.09 | 329.52 | 160.83 | 168.69 | 0.00 | 0.00 |
March | 327.37 | 403.26 | 375.09 | 165.21 | 209.88 | 0.00 | 0.00 |
April | 483.71 | 263.51 | 479.63 | 212.86 | 266.77 | 0.00 | 0.00 |
May | 534.19 | 177.33 | 466.84 | 201.25 | 265.59 | 0.00 | 0.00 |
June | 714.48 | 96.04 | 503.90 | 241.29 | 262.61 | 0.00 | 0.00 |
July | 703.34 | 47.59 | 456.38 | 185.75 | 270.63 | 0.00 | 0.00 |
August | 660.66 | 63.84 | 458.07 | 174.07 | 284.00 | 0.00 | 0.00 |
September | 530.53 | 148.58 | 406.27 | 178.42 | 227.85 | 0.00 | 0.00 |
October | 378.72 | 301.73 | 360.19 | 192.58 | 167.61 | 0.00 | 0.00 |
November | 218.79 | 444.31 | 284.91 | 142.12 | 142.79 | 0.00 | 0.00 |
December | 158.81 | 593.45 | 242.05 | 129.55 | 112.50 | 0.00 | 0.00 |
Annual Sum or Average | 429.47 | 302.43 | 385.13 | 175.56 | 209.56 | 0.00 | 0.00 |
Minimum of Months | 158.81 | 47.59 | 242.05 | 123.73 | 112.50 | 0.00 | 0.00 |
Maximum of Months | 714.48 | 593.45 | 503.90 | 241.29 | 284.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 241.63 | 185.59 | 239.88 | 186.55 | 53.33 | 0.00 | 0.00 |
February | 242.64 | 174.00 | 236.46 | 173.05 | 63.40 | 0.00 | 0.00 |
March | 178.94 | 144.25 | 175.83 | 107.29 | 68.54 | 0.00 | 0.00 |
April | 140.23 | 103.74 | 135.04 | 55.34 | 79.70 | 0.00 | 0.00 |
May | 92.59 | 78.24 | 90.88 | 20.56 | 70.32 | 0.00 | 0.00 |
June | 99.16 | 51.46 | 75.97 | 9.12 | 66.85 | 0.00 | 0.00 |
July | 124.92 | 34.17 | 84.10 | 13.20 | 70.90 | 0.00 | 0.00 |
August | 162.16 | 40.34 | 114.40 | 36.08 | 78.32 | 0.00 | 0.00 |
September | 213.61 | 65.51 | 162.41 | 91.42 | 70.99 | 0.00 | 0.00 |
October | 254.77 | 107.70 | 218.80 | 160.95 | 57.86 | 0.00 | 0.00 |
November | 259.00 | 151.56 | 246.82 | 189.95 | 56.86 | 0.00 | 0.00 |
December | 268.14 | 189.52 | 261.60 | 215.95 | 45.65 | 0.00 | 0.00 |
Annual Sum or Average | 189.51 | 110.18 | 169.80 | 104.60 | 65.20 | 0.00 | 0.00 |
Minimum of Months | 92.59 | 34.17 | 75.97 | 9.12 | 45.65 | 0.00 | 0.00 |
Maximum of Months | 268.14 | 189.52 | 261.60 | 215.95 | 79.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.21 | 173.02 | 32.52 | 0.00 | 32.52 | 0.00 | 0.00 |
February | 8.03 | 153.98 | 40.64 | 0.00 | 40.64 | 0.00 | 0.00 |
March | 24.77 | 115.35 | 51.27 | 0.00 | 51.27 | 0.00 | 0.00 |
April | 48.12 | 71.20 | 65.39 | 0.88 | 64.52 | 0.00 | 0.00 |
May | 72.60 | 46.37 | 70.78 | 4.60 | 66.18 | 0.00 | 0.00 |
June | 124.45 | 24.80 | 80.59 | 13.40 | 67.19 | 0.00 | 0.00 |
July | 128.84 | 11.71 | 73.90 | 6.30 | 67.60 | 0.00 | 0.00 |
August | 106.90 | 15.65 | 68.58 | 1.68 | 66.90 | 0.00 | 0.00 |
September | 69.34 | 38.77 | 54.75 | 0.04 | 54.71 | 0.00 | 0.00 |
October | 27.79 | 83.80 | 40.81 | 0.00 | 40.81 | 0.00 | 0.00 |
November | 5.46 | 131.27 | 34.66 | 0.00 | 34.66 | 0.00 | 0.00 |
December | 0.29 | 180.87 | 27.68 | 0.00 | 27.68 | 0.00 | 0.00 |
Annual Sum or Average | 51.81 | 86.91 | 53.51 | 2.25 | 51.26 | 0.00 | 0.00 |
Minimum of Months | 0.29 | 11.71 | 27.68 | 0.00 | 27.68 | 0.00 | 0.00 |
Maximum of Months | 128.84 | 180.87 | 80.59 | 13.40 | 67.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 447.53 | 528.10 | 510.29 | 350.98 | 159.31 | 0.00 | 0.00 |
February | 508.82 | 482.05 | 550.39 | 353.31 | 197.09 | 0.00 | 0.00 |
March | 556.99 | 369.30 | 558.39 | 327.02 | 231.37 | 0.00 | 0.00 |
April | 697.63 | 230.40 | 628.10 | 330.54 | 297.56 | 0.00 | 0.00 |
May | 664.01 | 158.24 | 552.38 | 275.62 | 276.76 | 0.00 | 0.00 |
June | 810.21 | 86.55 | 568.16 | 302.87 | 265.30 | 0.00 | 0.00 |
July | 838.83 | 41.30 | 542.76 | 266.67 | 276.09 | 0.00 | 0.00 |
August | 844.11 | 52.99 | 576.16 | 283.85 | 292.31 | 0.00 | 0.00 |
September | 759.15 | 121.89 | 564.23 | 316.40 | 247.83 | 0.00 | 0.00 |
October | 675.40 | 260.11 | 588.23 | 401.05 | 187.18 | 0.00 | 0.00 |
November | 531.49 | 407.12 | 553.32 | 381.06 | 172.26 | 0.00 | 0.00 |
December | 465.05 | 538.77 | 526.41 | 391.58 | 134.83 | 0.00 | 0.00 |
Annual Sum or Average | 650.55 | 272.02 | 559.78 | 331.56 | 228.22 | 0.00 | 0.00 |
Minimum of Months | 447.53 | 41.30 | 510.29 | 266.67 | 134.83 | 0.00 | 0.00 |
Maximum of Months | 844.11 | 538.77 | 628.10 | 401.05 | 297.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 133.32 | 547.25 | 251.01 | 117.75 | 133.26 | 0.00 | 0.00 |
February | 197.16 | 493.36 | 305.56 | 136.95 | 168.61 | 0.00 | 0.00 |
March | 337.96 | 373.54 | 402.64 | 192.88 | 209.76 | 0.00 | 0.00 |
April | 557.75 | 242.08 | 541.00 | 262.45 | 278.55 | 0.00 | 0.00 |
May | 608.59 | 168.99 | 527.23 | 255.66 | 271.56 | 0.00 | 0.00 |
June | 796.25 | 92.79 | 573.90 | 308.21 | 265.69 | 0.00 | 0.00 |
July | 793.47 | 47.04 | 529.98 | 258.04 | 271.94 | 0.00 | 0.00 |
August | 728.70 | 60.98 | 518.85 | 240.83 | 278.01 | 0.00 | 0.00 |
September | 546.04 | 137.06 | 429.60 | 202.15 | 227.46 | 0.00 | 0.00 |
October | 364.11 | 272.87 | 365.68 | 199.82 | 165.86 | 0.00 | 0.00 |
November | 197.91 | 421.87 | 288.05 | 143.57 | 144.48 | 0.00 | 0.00 |
December | 128.44 | 572.95 | 233.94 | 121.60 | 112.34 | 0.00 | 0.00 |
Annual Sum or Average | 450.39 | 284.88 | 414.36 | 203.59 | 210.77 | 0.00 | 0.00 |
Minimum of Months | 128.44 | 47.04 | 233.94 | 117.75 | 112.34 | 0.00 | 0.00 |
Maximum of Months | 796.25 | 572.95 | 573.90 | 308.21 | 278.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 499.82 | 742.47 | 590.20 | 404.20 | 186.00 | 0.00 | 0.00 |
February | 528.83 | 687.82 | 600.38 | 374.96 | 225.41 | 0.00 | 0.00 |
March | 447.05 | 551.35 | 492.04 | 232.48 | 259.57 | 0.00 | 0.00 |
April | 424.54 | 364.50 | 434.25 | 121.80 | 312.45 | 0.00 | 0.00 |
May | 371.33 | 248.60 | 350.25 | 54.51 | 295.74 | 0.00 | 0.00 |
June | 498.85 | 142.99 | 339.19 | 48.80 | 290.39 | 0.00 | 0.00 |
July | 572.21 | 82.20 | 342.30 | 42.24 | 300.07 | 0.00 | 0.00 |
August | 604.75 | 102.03 | 396.44 | 81.82 | 314.63 | 0.00 | 0.00 |
September | 635.51 | 205.84 | 470.49 | 198.17 | 272.32 | 0.00 | 0.00 |
October | 620.02 | 391.82 | 562.50 | 348.73 | 213.77 | 0.00 | 0.00 |
November | 553.41 | 580.43 | 609.87 | 411.58 | 198.29 | 0.00 | 0.00 |
December | 532.46 | 749.18 | 626.76 | 467.89 | 158.87 | 0.00 | 0.00 |
Annual Sum or Average | 523.98 | 402.66 | 483.84 | 231.50 | 252.34 | 0.00 | 0.00 |
Minimum of Months | 371.33 | 82.20 | 339.19 | 42.24 | 158.87 | 0.00 | 0.00 |
Maximum of Months | 635.51 | 749.18 | 626.76 | 467.89 | 314.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 471.57 | 527.87 | 516.87 | 356.97 | 159.91 | 0.00 | 0.00 |
February | 549.61 | 485.88 | 574.36 | 377.19 | 197.17 | 0.00 | 0.00 |
March | 534.13 | 378.12 | 530.84 | 299.35 | 231.49 | 0.00 | 0.00 |
April | 620.66 | 241.82 | 566.73 | 280.96 | 285.77 | 0.00 | 0.00 |
May | 583.60 | 162.11 | 492.00 | 221.21 | 270.79 | 0.00 | 0.00 |
June | 718.30 | 92.36 | 498.17 | 235.95 | 262.22 | 0.00 | 0.00 |
July | 731.72 | 40.99 | 469.16 | 194.37 | 274.79 | 0.00 | 0.00 |
August | 758.99 | 54.48 | 515.39 | 217.09 | 298.30 | 0.00 | 0.00 |
September | 729.35 | 125.78 | 540.90 | 292.67 | 248.22 | 0.00 | 0.00 |
October | 675.80 | 264.20 | 582.74 | 393.81 | 188.93 | 0.00 | 0.00 |
November | 534.74 | 402.29 | 550.18 | 379.61 | 170.57 | 0.00 | 0.00 |
December | 482.83 | 529.88 | 534.52 | 399.53 | 134.98 | 0.00 | 0.00 |
Annual Sum or Average | 616.10 | 274.41 | 530.54 | 303.53 | 227.01 | 0.00 | 0.00 |
Minimum of Months | 471.57 | 40.99 | 469.16 | 194.37 | 134.98 | 0.00 | 0.00 |
Maximum of Months | 758.99 | 529.88 | 582.74 | 399.53 | 298.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 180.10 | 563.11 | 257.60 | 123.73 | 133.86 | 0.00 | 0.00 |
February | 256.68 | 510.41 | 329.52 | 160.83 | 168.69 | 0.00 | 0.00 |
March | 325.18 | 394.29 | 375.09 | 165.21 | 209.88 | 0.00 | 0.00 |
April | 475.75 | 260.34 | 479.63 | 212.86 | 266.77 | 0.00 | 0.00 |
May | 526.20 | 174.68 | 466.84 | 201.25 | 265.59 | 0.00 | 0.00 |
June | 706.44 | 93.94 | 503.90 | 241.29 | 262.61 | 0.00 | 0.00 |
July | 694.73 | 45.74 | 456.38 | 185.75 | 270.63 | 0.00 | 0.00 |
August | 652.18 | 62.37 | 458.07 | 174.07 | 284.00 | 0.00 | 0.00 |
September | 524.12 | 146.07 | 406.27 | 178.42 | 227.85 | 0.00 | 0.00 |
October | 375.32 | 295.39 | 360.19 | 192.58 | 167.61 | 0.00 | 0.00 |
November | 220.16 | 428.59 | 284.91 | 142.12 | 142.79 | 0.00 | 0.00 |
December | 161.83 | 574.52 | 242.05 | 129.55 | 112.50 | 0.00 | 0.00 |
Annual Sum or Average | 425.65 | 294.72 | 385.13 | 175.56 | 209.56 | 0.00 | 0.00 |
Minimum of Months | 161.83 | 45.74 | 242.05 | 123.73 | 112.50 | 0.00 | 0.00 |
Maximum of Months | 706.44 | 574.52 | 503.90 | 241.29 | 284.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 463.40 | 273.12 | 439.86 | 342.06 | 97.79 | 0.00 | 0.00 |
February | 465.76 | 250.97 | 433.57 | 317.32 | 116.26 | 0.00 | 0.00 |
March | 352.29 | 196.47 | 322.40 | 196.73 | 125.67 | 0.00 | 0.00 |
April | 284.47 | 126.50 | 247.60 | 101.47 | 146.13 | 0.00 | 0.00 |
May | 201.29 | 83.38 | 166.64 | 37.70 | 128.94 | 0.00 | 0.00 |
June | 222.42 | 45.55 | 139.31 | 16.73 | 122.58 | 0.00 | 0.00 |
July | 271.77 | 19.63 | 154.20 | 24.20 | 130.01 | 0.00 | 0.00 |
August | 334.61 | 26.51 | 209.77 | 66.16 | 143.61 | 0.00 | 0.00 |
September | 419.93 | 63.45 | 297.79 | 167.63 | 130.16 | 0.00 | 0.00 |
October | 492.56 | 134.60 | 401.20 | 295.12 | 106.08 | 0.00 | 0.00 |
November | 497.34 | 209.50 | 452.57 | 348.30 | 104.26 | 0.00 | 0.00 |
December | 511.07 | 277.04 | 479.67 | 395.96 | 83.71 | 0.00 | 0.00 |
Annual Sum or Average | 375.90 | 141.67 | 311.35 | 191.79 | 119.56 | 0.00 | 0.00 |
Minimum of Months | 201.29 | 19.63 | 139.31 | 16.73 | 83.71 | 0.00 | 0.00 |
Maximum of Months | 511.07 | 277.04 | 479.67 | 395.96 | 146.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.99 | 1688.63 | 284.46 | 0.00 | 284.46 | 0.00 | 0.00 |
February | 43.16 | 1529.70 | 355.53 | 0.00 | 355.53 | 0.00 | 0.00 |
March | 163.65 | 1182.28 | 448.54 | 0.02 | 448.53 | 0.00 | 0.00 |
April | 335.64 | 748.93 | 572.10 | 7.66 | 564.43 | 0.00 | 0.00 |
May | 529.28 | 513.41 | 619.24 | 40.23 | 579.00 | 0.00 | 0.00 |
June | 962.21 | 309.59 | 705.02 | 117.25 | 587.77 | 0.00 | 0.00 |
July | 1000.87 | 192.58 | 646.49 | 55.10 | 591.39 | 0.00 | 0.00 |
August | 817.50 | 232.01 | 599.98 | 14.68 | 585.29 | 0.00 | 0.00 |
September | 519.65 | 444.91 | 478.96 | 0.34 | 478.62 | 0.00 | 0.00 |
October | 188.34 | 877.07 | 357.05 | 0.00 | 357.05 | 0.00 | 0.00 |
November | 25.10 | 1339.70 | 303.22 | 0.00 | 303.22 | 0.00 | 0.00 |
December | 1.13 | 1762.65 | 242.12 | 0.00 | 242.12 | 0.00 | 0.00 |
Annual Sum or Average | 384.90 | 898.72 | 468.13 | 19.64 | 448.49 | 0.00 | 0.00 |
Minimum of Months | 1.13 | 192.58 | 242.12 | 0.00 | 242.12 | 0.00 | 0.00 |
Maximum of Months | 1000.87 | 1762.65 | 705.02 | 117.25 | 591.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.45 | 1744.65 | 284.46 | 0.00 | 284.46 | 0.00 | 0.00 |
February | 37.04 | 1576.91 | 355.53 | 0.00 | 355.53 | 0.00 | 0.00 |
March | 151.46 | 1211.14 | 448.54 | 0.02 | 448.53 | 0.00 | 0.00 |
April | 322.42 | 765.00 | 572.10 | 7.66 | 564.43 | 0.00 | 0.00 |
May | 516.59 | 524.78 | 619.24 | 40.23 | 579.00 | 0.00 | 0.00 |
June | 950.26 | 317.37 | 705.02 | 117.25 | 587.77 | 0.00 | 0.00 |
July | 990.00 | 199.70 | 646.49 | 55.10 | 591.39 | 0.00 | 0.00 |
August | 806.81 | 240.01 | 599.98 | 14.68 | 585.29 | 0.00 | 0.00 |
September | 509.77 | 456.06 | 478.96 | 0.34 | 478.62 | 0.00 | 0.00 |
October | 179.46 | 899.16 | 357.05 | 0.00 | 357.05 | 0.00 | 0.00 |
November | 21.14 | 1379.69 | 303.22 | 0.00 | 303.22 | 0.00 | 0.00 |
December | 0.89 | 1821.41 | 242.12 | 0.00 | 242.12 | 0.00 | 0.00 |
Annual Sum or Average | 376.29 | 924.83 | 468.13 | 19.64 | 448.49 | 0.00 | 0.00 |
Minimum of Months | 0.89 | 199.70 | 242.12 | 0.00 | 242.12 | 0.00 | 0.00 |
Maximum of Months | 990.00 | 1821.41 | 705.02 | 117.25 | 591.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 522.10 | 1250.46 | 761.28 | 468.72 | 292.56 | 0.00 | 0.00 |
February | 651.53 | 1152.13 | 855.91 | 490.24 | 365.68 | 0.00 | 0.00 |
March | 847.80 | 913.43 | 960.97 | 519.87 | 441.11 | 0.00 | 0.00 |
April | 1218.72 | 607.15 | 1169.03 | 592.95 | 576.08 | 0.00 | 0.00 |
May | 1239.91 | 456.80 | 1079.55 | 531.25 | 548.30 | 0.00 | 0.00 |
June | 1586.82 | 291.80 | 1142.00 | 611.04 | 530.96 | 0.00 | 0.00 |
July | 1619.33 | 195.54 | 1072.68 | 524.67 | 548.00 | 0.00 | 0.00 |
August | 1565.51 | 227.78 | 1094.95 | 524.65 | 570.30 | 0.00 | 0.00 |
September | 1297.78 | 378.61 | 993.78 | 518.52 | 475.27 | 0.00 | 0.00 |
October | 1015.20 | 673.53 | 953.87 | 600.85 | 353.03 | 0.00 | 0.00 |
November | 676.99 | 988.83 | 841.34 | 524.61 | 316.72 | 0.00 | 0.00 |
December | 521.47 | 1268.83 | 760.32 | 513.16 | 247.16 | 0.00 | 0.00 |
Annual Sum or Average | 1065.54 | 698.16 | 974.09 | 535.12 | 438.97 | 0.00 | 0.00 |
Minimum of Months | 521.47 | 195.54 | 760.32 | 468.72 | 247.16 | 0.00 | 0.00 |
Maximum of Months | 1619.33 | 1268.83 | 1169.03 | 611.04 | 576.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1127.91 | 1204.71 | 1217.19 | 870.73 | 346.46 | 0.00 | 0.00 |
February | 1162.86 | 1132.71 | 1225.55 | 807.74 | 417.81 | 0.00 | 0.00 |
March | 927.43 | 942.22 | 974.45 | 500.79 | 473.66 | 0.00 | 0.00 |
April | 819.02 | 642.13 | 826.41 | 260.93 | 565.48 | 0.00 | 0.00 |
May | 661.79 | 448.44 | 636.46 | 109.76 | 526.71 | 0.00 | 0.00 |
June | 847.41 | 263.64 | 596.29 | 82.77 | 513.52 | 0.00 | 0.00 |
July | 992.26 | 156.31 | 614.15 | 80.48 | 533.67 | 0.00 | 0.00 |
August | 1098.63 | 193.02 | 739.65 | 173.45 | 566.20 | 0.00 | 0.00 |
September | 1229.56 | 373.12 | 922.23 | 426.83 | 495.40 | 0.00 | 0.00 |
October | 1287.08 | 678.87 | 1143.67 | 751.23 | 392.44 | 0.00 | 0.00 |
November | 1215.91 | 977.99 | 1255.97 | 886.62 | 369.35 | 0.00 | 0.00 |
December | 1221.12 | 1207.47 | 1304.02 | 1007.93 | 296.08 | 0.00 | 0.00 |
Annual Sum or Average | 1048.55 | 682.70 | 953.04 | 494.95 | 458.09 | 0.00 | 0.00 |
Minimum of Months | 661.79 | 156.31 | 596.29 | 80.48 | 296.08 | 0.00 | 0.00 |
Maximum of Months | 1287.08 | 1207.47 | 1304.02 | 1007.93 | 566.20 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.380118E+10 | 0.209651E+10 | 0.353718E+10 | 0.275074E+10 | 0.786437E+09 | 0.00 | 0.00 |
February | 0.345121E+10 | 0.175157E+10 | 0.314923E+10 | 0.230481E+10 | 0.844424E+09 | 0.00 | 0.00 |
March | 0.289879E+10 | 0.154871E+10 | 0.259265E+10 | 0.158205E+10 | 0.101060E+10 | 0.00 | 0.00 |
April | 0.222831E+10 | 0.104459E+10 | 0.192692E+10 | 0.789680E+09 | 0.113724E+10 | 0.00 | 0.00 |
May | 0.157919E+10 | 0.768823E+09 | 0.134006E+10 | 0.303158E+09 | 0.103690E+10 | 0.00 | 0.00 |
June | 0.157785E+10 | 0.473768E+09 | 0.108412E+10 | 0.130179E+09 | 0.953939E+09 | 0.00 | 0.00 |
July | 0.199732E+10 | 0.298667E+09 | 0.124005E+10 | 0.194572E+09 | 0.104548E+10 | 0.00 | 0.00 |
August | 0.255329E+10 | 0.363773E+09 | 0.168689E+10 | 0.532039E+09 | 0.115485E+10 | 0.00 | 0.00 |
September | 0.321873E+10 | 0.635619E+09 | 0.231750E+10 | 0.130455E+10 | 0.101295E+10 | 0.00 | 0.00 |
October | 0.395532E+10 | 0.115355E+10 | 0.322633E+10 | 0.237323E+10 | 0.853100E+09 | 0.00 | 0.00 |
November | 0.391320E+10 | 0.161195E+10 | 0.352199E+10 | 0.271059E+10 | 0.811403E+09 | 0.00 | 0.00 |
December | 0.416792E+10 | 0.214300E+10 | 0.385733E+10 | 0.318418E+10 | 0.673150E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.353423E+11 | 0.138905E+11 | 0.294802E+11 | 0.181598E+11 | 0.113205E+11 | 0.00 | 0.00 |
Minimum of Months | 0.157785E+10 | 0.298667E+09 | 0.108412E+10 | 0.130179E+09 | 0.673150E+09 | 0.00 | 0.00 |
Maximum of Months | 0.416792E+10 | 0.214300E+10 | 0.385733E+10 | 0.318418E+10 | 0.115485E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106531E+11 | 0.594811E+10 | 0.996046E+10 | 0.774590E+10 | 0.221455E+10 | 0.00 | 0.00 |
February | 0.966143E+10 | 0.500462E+10 | 0.886802E+10 | 0.649018E+10 | 0.237784E+10 | 0.00 | 0.00 |
March | 0.804241E+10 | 0.457508E+10 | 0.730072E+10 | 0.445495E+10 | 0.284577E+10 | 0.00 | 0.00 |
April | 0.613079E+10 | 0.317392E+10 | 0.542609E+10 | 0.222369E+10 | 0.320240E+10 | 0.00 | 0.00 |
May | 0.426682E+10 | 0.242321E+10 | 0.377353E+10 | 0.853672E+09 | 0.291986E+10 | 0.00 | 0.00 |
June | 0.431521E+10 | 0.148986E+10 | 0.305280E+10 | 0.366575E+09 | 0.268623E+10 | 0.00 | 0.00 |
July | 0.553038E+10 | 0.930152E+09 | 0.349190E+10 | 0.547903E+09 | 0.294399E+10 | 0.00 | 0.00 |
August | 0.709063E+10 | 0.112720E+10 | 0.475017E+10 | 0.149819E+10 | 0.325198E+10 | 0.00 | 0.00 |
September | 0.894550E+10 | 0.195253E+10 | 0.652593E+10 | 0.367353E+10 | 0.285240E+10 | 0.00 | 0.00 |
October | 0.110216E+11 | 0.345335E+10 | 0.908513E+10 | 0.668285E+10 | 0.240227E+10 | 0.00 | 0.00 |
November | 0.109369E+11 | 0.472184E+10 | 0.991770E+10 | 0.763284E+10 | 0.228486E+10 | 0.00 | 0.00 |
December | 0.117031E+11 | 0.607778E+10 | 0.108620E+11 | 0.896644E+10 | 0.189554E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.982978E+11 | 0.408776E+11 | 0.830144E+11 | 0.511367E+11 | 0.318777E+11 | 0.00 | 0.00 |
Minimum of Months | 0.426682E+10 | 0.930152E+09 | 0.305280E+10 | 0.366575E+09 | 0.189554E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117031E+11 | 0.607778E+10 | 0.108620E+11 | 0.896644E+10 | 0.325198E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140429E+11 | 0.844234E+10 | 0.129392E+11 | 0.100624E+11 | 0.287683E+10 | 0.00 | 0.00 |
February | 0.127834E+11 | 0.706607E+10 | 0.115201E+11 | 0.843111E+10 | 0.308895E+10 | 0.00 | 0.00 |
March | 0.106925E+11 | 0.636587E+10 | 0.948405E+10 | 0.578723E+10 | 0.369682E+10 | 0.00 | 0.00 |
April | 0.824521E+10 | 0.431944E+10 | 0.704880E+10 | 0.288869E+10 | 0.416010E+10 | 0.00 | 0.00 |
May | 0.581965E+10 | 0.323750E+10 | 0.490203E+10 | 0.110897E+10 | 0.379306E+10 | 0.00 | 0.00 |
June | 0.588802E+10 | 0.197056E+10 | 0.396576E+10 | 0.476202E+09 | 0.348956E+10 | 0.00 | 0.00 |
July | 0.750364E+10 | 0.120761E+10 | 0.453617E+10 | 0.711757E+09 | 0.382442E+10 | 0.00 | 0.00 |
August | 0.956468E+10 | 0.145679E+10 | 0.617074E+10 | 0.194623E+10 | 0.422451E+10 | 0.00 | 0.00 |
September | 0.119780E+11 | 0.254764E+10 | 0.847756E+10 | 0.477212E+10 | 0.370543E+10 | 0.00 | 0.00 |
October | 0.146532E+11 | 0.467113E+10 | 0.118021E+11 | 0.868141E+10 | 0.312069E+10 | 0.00 | 0.00 |
November | 0.144535E+11 | 0.657890E+10 | 0.128837E+11 | 0.991549E+10 | 0.296816E+10 | 0.00 | 0.00 |
December | 0.154248E+11 | 0.863606E+10 | 0.141103E+11 | 0.116479E+11 | 0.246242E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.131049E+12 | 0.564999E+11 | 0.107840E+12 | 0.664295E+11 | 0.414110E+11 | 0.00 | 0.00 |
Minimum of Months | 0.581965E+10 | 0.120761E+10 | 0.396576E+10 | 0.476202E+09 | 0.246242E+10 | 0.00 | 0.00 |
Maximum of Months | 0.154248E+11 | 0.863606E+10 | 0.141103E+11 | 0.116479E+11 | 0.422451E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126082E+10 | 0.144682E+10 | 0.138440E+10 | 0.956101E+09 | 0.428297E+09 | 0.00 | 0.00 |
February | 0.133509E+10 | 0.119960E+10 | 0.138949E+10 | 0.912504E+09 | 0.476990E+09 | 0.00 | 0.00 |
March | 0.144133E+10 | 0.103542E+10 | 0.142180E+10 | 0.801777E+09 | 0.620024E+09 | 0.00 | 0.00 |
April | 0.163011E+10 | 0.642867E+09 | 0.146896E+10 | 0.728239E+09 | 0.740720E+09 | 0.00 | 0.00 |
May | 0.158459E+10 | 0.447404E+09 | 0.131778E+10 | 0.592485E+09 | 0.725292E+09 | 0.00 | 0.00 |
June | 0.188306E+10 | 0.248380E+09 | 0.129125E+10 | 0.611578E+09 | 0.679674E+09 | 0.00 | 0.00 |
July | 0.198431E+10 | 0.116294E+09 | 0.125661E+10 | 0.520612E+09 | 0.735995E+09 | 0.00 | 0.00 |
August | 0.205820E+10 | 0.152704E+09 | 0.138041E+10 | 0.581448E+09 | 0.798965E+09 | 0.00 | 0.00 |
September | 0.191145E+10 | 0.336740E+09 | 0.140200E+10 | 0.758612E+09 | 0.643389E+09 | 0.00 | 0.00 |
October | 0.182137E+10 | 0.726943E+09 | 0.156081E+10 | 0.105477E+10 | 0.506037E+09 | 0.00 | 0.00 |
November | 0.138769E+10 | 0.107233E+10 | 0.142606E+10 | 0.983954E+09 | 0.442108E+09 | 0.00 | 0.00 |
December | 0.128898E+10 | 0.145671E+10 | 0.143165E+10 | 0.107011E+10 | 0.361543E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.195870E+11 | 0.888220E+10 | 0.167312E+11 | 0.957219E+10 | 0.715903E+10 | 0.00 | 0.00 |
Minimum of Months | 0.126082E+10 | 0.116294E+09 | 0.125661E+10 | 0.520612E+09 | 0.361543E+09 | 0.00 | 0.00 |
Maximum of Months | 0.205820E+10 | 0.145671E+10 | 0.156081E+10 | 0.107011E+10 | 0.798965E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.475400E+09 | 0.155208E+10 | 0.689951E+09 | 0.331407E+09 | 0.358544E+09 | 0.00 | 0.00 |
February | 0.619885E+09 | 0.126545E+10 | 0.797177E+09 | 0.389082E+09 | 0.408096E+09 | 0.00 | 0.00 |
March | 0.876819E+09 | 0.108010E+10 | 0.100464E+10 | 0.442499E+09 | 0.562144E+09 | 0.00 | 0.00 |
April | 0.125377E+10 | 0.683013E+09 | 0.124320E+10 | 0.551740E+09 | 0.691462E+09 | 0.00 | 0.00 |
May | 0.143077E+10 | 0.474959E+09 | 0.125039E+10 | 0.539033E+09 | 0.711361E+09 | 0.00 | 0.00 |
June | 0.185194E+10 | 0.248926E+09 | 0.130612E+10 | 0.625431E+09 | 0.680687E+09 | 0.00 | 0.00 |
July | 0.188382E+10 | 0.127474E+09 | 0.122237E+10 | 0.497510E+09 | 0.724857E+09 | 0.00 | 0.00 |
August | 0.176952E+10 | 0.170998E+09 | 0.122690E+10 | 0.466241E+09 | 0.760656E+09 | 0.00 | 0.00 |
September | 0.137513E+10 | 0.385120E+09 | 0.105305E+10 | 0.462475E+09 | 0.590580E+09 | 0.00 | 0.00 |
October | 0.101436E+10 | 0.808157E+09 | 0.964732E+09 | 0.515813E+09 | 0.448919E+09 | 0.00 | 0.00 |
November | 0.567110E+09 | 0.115165E+10 | 0.738498E+09 | 0.368379E+09 | 0.370120E+09 | 0.00 | 0.00 |
December | 0.425362E+09 | 0.158949E+10 | 0.648295E+09 | 0.346979E+09 | 0.301316E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135439E+11 | 0.953741E+10 | 0.121453E+11 | 0.553659E+10 | 0.660874E+10 | 0.00 | 0.00 |
Minimum of Months | 0.425362E+09 | 0.127474E+09 | 0.648295E+09 | 0.331407E+09 | 0.301316E+09 | 0.00 | 0.00 |
Maximum of Months | 0.188382E+10 | 0.158949E+10 | 0.130612E+10 | 0.625431E+09 | 0.760656E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.647181E+09 | 0.497091E+09 | 0.642507E+09 | 0.499656E+09 | 0.142852E+09 | 0.00 | 0.00 |
February | 0.587006E+09 | 0.420932E+09 | 0.572039E+09 | 0.418654E+09 | 0.153385E+09 | 0.00 | 0.00 |
March | 0.479286E+09 | 0.386372E+09 | 0.470939E+09 | 0.287370E+09 | 0.183569E+09 | 0.00 | 0.00 |
April | 0.363466E+09 | 0.268883E+09 | 0.350014E+09 | 0.143441E+09 | 0.206574E+09 | 0.00 | 0.00 |
May | 0.247989E+09 | 0.209562E+09 | 0.243414E+09 | 55066824.53 | 0.188348E+09 | 0.00 | 0.00 |
June | 0.257034E+09 | 0.133372E+09 | 0.196924E+09 | 23646204.60 | 0.173277E+09 | 0.00 | 0.00 |
July | 0.334586E+09 | 91523959.43 | 0.225248E+09 | 35342935.20 | 0.189905E+09 | 0.00 | 0.00 |
August | 0.434339E+09 | 0.108045E+09 | 0.306414E+09 | 96641690.18 | 0.209772E+09 | 0.00 | 0.00 |
September | 0.553675E+09 | 0.169807E+09 | 0.420961E+09 | 0.236964E+09 | 0.183997E+09 | 0.00 | 0.00 |
October | 0.682371E+09 | 0.288452E+09 | 0.586044E+09 | 0.431083E+09 | 0.154961E+09 | 0.00 | 0.00 |
November | 0.671332E+09 | 0.392850E+09 | 0.639749E+09 | 0.492362E+09 | 0.147387E+09 | 0.00 | 0.00 |
December | 0.718187E+09 | 0.507606E+09 | 0.700661E+09 | 0.578387E+09 | 0.122274E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.597645E+10 | 0.347450E+10 | 0.535491E+10 | 0.329862E+10 | 0.205630E+10 | 0.00 | 0.00 |
Minimum of Months | 0.247989E+09 | 91523959.43 | 0.196924E+09 | 23646204.60 | 0.122274E+09 | 0.00 | 0.00 |
Maximum of Months | 0.718187E+09 | 0.507606E+09 | 0.700661E+09 | 0.578387E+09 | 0.209772E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5918905.92 | 0.463422E+09 | 87089113.54 | 0.00 | 87089113.54 | 0.00 | 0.00 |
February | 19422036.54 | 0.372517E+09 | 98313144.90 | 0.00 | 98313144.90 | 0.00 | 0.00 |
March | 66342891.65 | 0.308947E+09 | 0.137324E+09 | 4773.60 | 0.137319E+09 | 0.00 | 0.00 |
April | 0.124727E+09 | 0.184556E+09 | 0.169500E+09 | 2270564.67 | 0.167230E+09 | 0.00 | 0.00 |
May | 0.194462E+09 | 0.124204E+09 | 0.189582E+09 | 12317900.70 | 0.177264E+09 | 0.00 | 0.00 |
June | 0.322580E+09 | 64291750.78 | 0.208883E+09 | 34738123.00 | 0.174145E+09 | 0.00 | 0.00 |
July | 0.345079E+09 | 31352850.53 | 0.197927E+09 | 16870655.38 | 0.181057E+09 | 0.00 | 0.00 |
August | 0.286310E+09 | 41907316.04 | 0.183686E+09 | 4495385.80 | 0.179190E+09 | 0.00 | 0.00 |
September | 0.179723E+09 | 0.100499E+09 | 0.141905E+09 | 101122.54 | 0.141804E+09 | 0.00 | 0.00 |
October | 74422719.77 | 0.224459E+09 | 0.109312E+09 | 0.00 | 0.109312E+09 | 0.00 | 0.00 |
November | 14142923.87 | 0.340262E+09 | 89836958.00 | 0.00 | 89836958.00 | 0.00 | 0.00 |
December | 767444.41 | 0.484455E+09 | 74125919.77 | 0.00 | 74125919.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.163390E+10 | 0.274087E+10 | 0.168748E+10 | 70798525.71 | 0.161669E+10 | 0.00 | 0.00 |
Minimum of Months | 767444.41 | 31352850.53 | 74125919.77 | 0.00 | 74125919.77 | 0.00 | 0.00 |
Maximum of Months | 0.345079E+09 | 0.484455E+09 | 0.208883E+09 | 34738123.00 | 0.181057E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119867E+10 | 0.141445E+10 | 0.136676E+10 | 0.940075E+09 | 0.426690E+09 | 0.00 | 0.00 |
February | 0.123093E+10 | 0.116618E+10 | 0.133151E+10 | 0.854726E+09 | 0.476789E+09 | 0.00 | 0.00 |
March | 0.149185E+10 | 0.989123E+09 | 0.149558E+10 | 0.875883E+09 | 0.619698E+09 | 0.00 | 0.00 |
April | 0.180827E+10 | 0.597200E+09 | 0.162803E+10 | 0.856756E+09 | 0.771271E+09 | 0.00 | 0.00 |
May | 0.177848E+10 | 0.423818E+09 | 0.147950E+10 | 0.738220E+09 | 0.741284E+09 | 0.00 | 0.00 |
June | 0.210006E+10 | 0.224336E+09 | 0.147268E+10 | 0.785030E+09 | 0.687651E+09 | 0.00 | 0.00 |
July | 0.224673E+10 | 0.110615E+09 | 0.145373E+10 | 0.714239E+09 | 0.739492E+09 | 0.00 | 0.00 |
August | 0.226087E+10 | 0.141920E+09 | 0.154319E+10 | 0.760257E+09 | 0.782934E+09 | 0.00 | 0.00 |
September | 0.196772E+10 | 0.315945E+09 | 0.146248E+10 | 0.820101E+09 | 0.642378E+09 | 0.00 | 0.00 |
October | 0.180898E+10 | 0.696673E+09 | 0.157552E+10 | 0.107417E+10 | 0.501352E+09 | 0.00 | 0.00 |
November | 0.137762E+10 | 0.105527E+10 | 0.143420E+10 | 0.987714E+09 | 0.446487E+09 | 0.00 | 0.00 |
December | 0.124558E+10 | 0.144303E+10 | 0.140994E+10 | 0.104882E+10 | 0.361123E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.205157E+11 | 0.857856E+10 | 0.176531E+11 | 0.104560E+11 | 0.719715E+10 | 0.00 | 0.00 |
Minimum of Months | 0.119867E+10 | 0.110615E+09 | 0.133151E+10 | 0.714239E+09 | 0.361123E+09 | 0.00 | 0.00 |
Maximum of Months | 0.226087E+10 | 0.144303E+10 | 0.162803E+10 | 0.107417E+10 | 0.782934E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.357075E+09 | 0.146576E+10 | 0.672317E+09 | 0.315381E+09 | 0.356937E+09 | 0.00 | 0.00 |
February | 0.476968E+09 | 0.119354E+10 | 0.739199E+09 | 0.331304E+09 | 0.407895E+09 | 0.00 | 0.00 |
March | 0.905179E+09 | 0.100049E+10 | 0.107842E+10 | 0.516605E+09 | 0.561817E+09 | 0.00 | 0.00 |
April | 0.144569E+10 | 0.627483E+09 | 0.140227E+10 | 0.680258E+09 | 0.722012E+09 | 0.00 | 0.00 |
May | 0.163004E+10 | 0.452619E+09 | 0.141212E+10 | 0.684769E+09 | 0.727354E+09 | 0.00 | 0.00 |
June | 0.206389E+10 | 0.240500E+09 | 0.148755E+10 | 0.798884E+09 | 0.688663E+09 | 0.00 | 0.00 |
July | 0.212523E+10 | 0.125984E+09 | 0.141949E+10 | 0.691137E+09 | 0.728355E+09 | 0.00 | 0.00 |
August | 0.195175E+10 | 0.163336E+09 | 0.138967E+10 | 0.645049E+09 | 0.744625E+09 | 0.00 | 0.00 |
September | 0.141532E+10 | 0.355252E+09 | 0.111353E+10 | 0.523964E+09 | 0.589569E+09 | 0.00 | 0.00 |
October | 0.975245E+09 | 0.730859E+09 | 0.979444E+09 | 0.535210E+09 | 0.444234E+09 | 0.00 | 0.00 |
November | 0.512991E+09 | 0.109348E+10 | 0.746637E+09 | 0.372138E+09 | 0.374498E+09 | 0.00 | 0.00 |
December | 0.344006E+09 | 0.153459E+10 | 0.626583E+09 | 0.325687E+09 | 0.300896E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.142034E+11 | 0.898389E+10 | 0.130672E+11 | 0.642039E+10 | 0.664686E+10 | 0.00 | 0.00 |
Minimum of Months | 0.344006E+09 | 0.125984E+09 | 0.626583E+09 | 0.315381E+09 | 0.300896E+09 | 0.00 | 0.00 |
Maximum of Months | 0.212523E+10 | 0.153459E+10 | 0.148755E+10 | 0.798884E+09 | 0.744625E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133873E+10 | 0.198864E+10 | 0.158080E+10 | 0.108262E+10 | 0.498184E+09 | 0.00 | 0.00 |
February | 0.127935E+10 | 0.166396E+10 | 0.145243E+10 | 0.907107E+09 | 0.545321E+09 | 0.00 | 0.00 |
March | 0.119737E+10 | 0.147673E+10 | 0.131788E+10 | 0.622662E+09 | 0.695222E+09 | 0.00 | 0.00 |
April | 0.110041E+10 | 0.944789E+09 | 0.112558E+10 | 0.315715E+09 | 0.809864E+09 | 0.00 | 0.00 |
May | 0.994579E+09 | 0.665837E+09 | 0.938110E+09 | 0.145999E+09 | 0.792110E+09 | 0.00 | 0.00 |
June | 0.129303E+10 | 0.370633E+09 | 0.879189E+09 | 0.126489E+09 | 0.752700E+09 | 0.00 | 0.00 |
July | 0.153262E+10 | 0.220160E+09 | 0.916826E+09 | 0.113126E+09 | 0.803700E+09 | 0.00 | 0.00 |
August | 0.161977E+10 | 0.273289E+09 | 0.106184E+10 | 0.219134E+09 | 0.842703E+09 | 0.00 | 0.00 |
September | 0.164725E+10 | 0.533544E+09 | 0.121952E+10 | 0.513654E+09 | 0.705865E+09 | 0.00 | 0.00 |
October | 0.166067E+10 | 0.104945E+10 | 0.150660E+10 | 0.934037E+09 | 0.572562E+09 | 0.00 | 0.00 |
November | 0.143443E+10 | 0.150448E+10 | 0.158078E+10 | 0.106681E+10 | 0.513963E+09 | 0.00 | 0.00 |
December | 0.142614E+10 | 0.200661E+10 | 0.167872E+10 | 0.125320E+10 | 0.425515E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165244E+11 | 0.126981E+11 | 0.152583E+11 | 0.730056E+10 | 0.795771E+10 | 0.00 | 0.00 |
Minimum of Months | 0.994579E+09 | 0.220160E+09 | 0.879189E+09 | 0.113126E+09 | 0.425515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166067E+10 | 0.200661E+10 | 0.167872E+10 | 0.125320E+10 | 0.842703E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126304E+10 | 0.141384E+10 | 0.138440E+10 | 0.956101E+09 | 0.428297E+09 | 0.00 | 0.00 |
February | 0.132960E+10 | 0.117545E+10 | 0.138949E+10 | 0.912504E+09 | 0.476990E+09 | 0.00 | 0.00 |
March | 0.143062E+10 | 0.101276E+10 | 0.142180E+10 | 0.801777E+09 | 0.620024E+09 | 0.00 | 0.00 |
April | 0.160876E+10 | 0.626795E+09 | 0.146896E+10 | 0.728239E+09 | 0.740720E+09 | 0.00 | 0.00 |
May | 0.156312E+10 | 0.434186E+09 | 0.131778E+10 | 0.592485E+09 | 0.725292E+09 | 0.00 | 0.00 |
June | 0.186183E+10 | 0.239388E+09 | 0.129125E+10 | 0.611578E+09 | 0.679674E+09 | 0.00 | 0.00 |
July | 0.195985E+10 | 0.109790E+09 | 0.125661E+10 | 0.520612E+09 | 0.735995E+09 | 0.00 | 0.00 |
August | 0.203287E+10 | 0.145920E+09 | 0.138041E+10 | 0.581448E+09 | 0.798965E+09 | 0.00 | 0.00 |
September | 0.189048E+10 | 0.326011E+09 | 0.140200E+10 | 0.758612E+09 | 0.643389E+09 | 0.00 | 0.00 |
October | 0.181007E+10 | 0.707637E+09 | 0.156081E+10 | 0.105477E+10 | 0.506037E+09 | 0.00 | 0.00 |
November | 0.138604E+10 | 0.104274E+10 | 0.142606E+10 | 0.983954E+09 | 0.442108E+09 | 0.00 | 0.00 |
December | 0.129322E+10 | 0.141922E+10 | 0.143165E+10 | 0.107011E+10 | 0.361543E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194295E+11 | 0.865373E+10 | 0.167312E+11 | 0.957219E+10 | 0.715903E+10 | 0.00 | 0.00 |
Minimum of Months | 0.126304E+10 | 0.109790E+09 | 0.125661E+10 | 0.520612E+09 | 0.361543E+09 | 0.00 | 0.00 |
Maximum of Months | 0.203287E+10 | 0.141922E+10 | 0.156081E+10 | 0.107011E+10 | 0.798965E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.482393E+09 | 0.150824E+10 | 0.689951E+09 | 0.331407E+09 | 0.358544E+09 | 0.00 | 0.00 |
February | 0.620960E+09 | 0.123478E+10 | 0.797177E+09 | 0.389082E+09 | 0.408096E+09 | 0.00 | 0.00 |
March | 0.870974E+09 | 0.105608E+10 | 0.100464E+10 | 0.442499E+09 | 0.562144E+09 | 0.00 | 0.00 |
April | 0.123315E+10 | 0.674795E+09 | 0.124320E+10 | 0.551740E+09 | 0.691462E+09 | 0.00 | 0.00 |
May | 0.140937E+10 | 0.467873E+09 | 0.125039E+10 | 0.539033E+09 | 0.711361E+09 | 0.00 | 0.00 |
June | 0.183109E+10 | 0.243491E+09 | 0.130612E+10 | 0.625431E+09 | 0.680687E+09 | 0.00 | 0.00 |
July | 0.186076E+10 | 0.122505E+09 | 0.122237E+10 | 0.497510E+09 | 0.724857E+09 | 0.00 | 0.00 |
August | 0.174680E+10 | 0.167045E+09 | 0.122690E+10 | 0.466241E+09 | 0.760656E+09 | 0.00 | 0.00 |
September | 0.135851E+10 | 0.378610E+09 | 0.105305E+10 | 0.462475E+09 | 0.590580E+09 | 0.00 | 0.00 |
October | 0.100525E+10 | 0.791176E+09 | 0.964732E+09 | 0.515813E+09 | 0.448919E+09 | 0.00 | 0.00 |
November | 0.570648E+09 | 0.111091E+10 | 0.738498E+09 | 0.368379E+09 | 0.370120E+09 | 0.00 | 0.00 |
December | 0.433440E+09 | 0.153879E+10 | 0.648295E+09 | 0.346979E+09 | 0.301316E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134233E+11 | 0.929430E+10 | 0.121453E+11 | 0.553659E+10 | 0.660874E+10 | 0.00 | 0.00 |
Minimum of Months | 0.433440E+09 | 0.122505E+09 | 0.648295E+09 | 0.331407E+09 | 0.301316E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186076E+10 | 0.153879E+10 | 0.130612E+10 | 0.625431E+09 | 0.760656E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124117E+10 | 0.731514E+09 | 0.117811E+10 | 0.916174E+09 | 0.261934E+09 | 0.00 | 0.00 |
February | 0.112676E+10 | 0.607140E+09 | 0.104890E+10 | 0.767649E+09 | 0.281248E+09 | 0.00 | 0.00 |
March | 0.943582E+09 | 0.526216E+09 | 0.863518E+09 | 0.526925E+09 | 0.336594E+09 | 0.00 | 0.00 |
April | 0.737347E+09 | 0.327879E+09 | 0.641790E+09 | 0.263014E+09 | 0.378775E+09 | 0.00 | 0.00 |
May | 0.539141E+09 | 0.223318E+09 | 0.446327E+09 | 0.100971E+09 | 0.345356E+09 | 0.00 | 0.00 |
June | 0.576519E+09 | 0.118053E+09 | 0.361081E+09 | 43357906.48 | 0.317723E+09 | 0.00 | 0.00 |
July | 0.727900E+09 | 52573804.09 | 0.413016E+09 | 64805143.36 | 0.348211E+09 | 0.00 | 0.00 |
August | 0.896218E+09 | 71010002.44 | 0.561843E+09 | 0.177203E+09 | 0.384640E+09 | 0.00 | 0.00 |
September | 0.108845E+10 | 0.164461E+09 | 0.771877E+09 | 0.434500E+09 | 0.337378E+09 | 0.00 | 0.00 |
October | 0.131927E+10 | 0.360522E+09 | 0.107458E+10 | 0.790438E+09 | 0.284137E+09 | 0.00 | 0.00 |
November | 0.128911E+10 | 0.543019E+09 | 0.117305E+10 | 0.902800E+09 | 0.270250E+09 | 0.00 | 0.00 |
December | 0.136886E+10 | 0.742012E+09 | 0.128474E+10 | 0.106054E+10 | 0.224202E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118543E+11 | 0.446772E+10 | 0.981882E+10 | 0.604837E+10 | 0.377045E+10 | 0.00 | 0.00 |
Minimum of Months | 0.539141E+09 | 52573804.09 | 0.361081E+09 | 43357906.48 | 0.224202E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136886E+10 | 0.742012E+09 | 0.128474E+10 | 0.106054E+10 | 0.384640E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 24066935.05 | 0.452283E+10 | 0.761900E+09 | 0.00 | 0.761900E+09 | 0.00 | 0.00 |
February | 0.104420E+09 | 0.370065E+10 | 0.860093E+09 | 0.00 | 0.860093E+09 | 0.00 | 0.00 |
March | 0.438313E+09 | 0.316661E+10 | 0.120138E+10 | 41761.91 | 0.120134E+10 | 0.00 | 0.00 |
April | 0.869986E+09 | 0.194124E+10 | 0.148288E+10 | 19864055.37 | 0.146301E+10 | 0.00 | 0.00 |
May | 0.141764E+10 | 0.137511E+10 | 0.165856E+10 | 0.107763E+09 | 0.155080E+10 | 0.00 | 0.00 |
June | 0.249405E+10 | 0.802449E+09 | 0.182741E+10 | 0.303907E+09 | 0.152351E+10 | 0.00 | 0.00 |
July | 0.268073E+10 | 0.515801E+09 | 0.173157E+10 | 0.147593E+09 | 0.158398E+10 | 0.00 | 0.00 |
August | 0.218958E+10 | 0.621408E+09 | 0.160698E+10 | 39327922.90 | 0.156765E+10 | 0.00 | 0.00 |
September | 0.134694E+10 | 0.115320E+10 | 0.124146E+10 | 884671.44 | 0.124058E+10 | 0.00 | 0.00 |
October | 0.504458E+09 | 0.234915E+10 | 0.956313E+09 | 0.00 | 0.956313E+09 | 0.00 | 0.00 |
November | 65057788.85 | 0.347251E+10 | 0.785939E+09 | 0.00 | 0.785939E+09 | 0.00 | 0.00 |
December | 3025693.89 | 0.472107E+10 | 0.648491E+09 | 0.00 | 0.648491E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.121383E+11 | 0.283420E+11 | 0.147630E+11 | 0.619382E+09 | 0.141436E+11 | 0.00 | 0.00 |
Minimum of Months | 3025693.89 | 0.515801E+09 | 0.648491E+09 | 0.00 | 0.648491E+09 | 0.00 | 0.00 |
Maximum of Months | 0.268073E+10 | 0.472107E+10 | 0.182741E+10 | 0.303907E+09 | 0.158398E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 17281109.28 | 0.467287E+10 | 0.761900E+09 | 0.00 | 0.761900E+09 | 0.00 | 0.00 |
February | 89616383.85 | 0.381487E+10 | 0.860093E+09 | 0.00 | 0.860093E+09 | 0.00 | 0.00 |
March | 0.405662E+09 | 0.324392E+10 | 0.120138E+10 | 41761.91 | 0.120134E+10 | 0.00 | 0.00 |
April | 0.835725E+09 | 0.198288E+10 | 0.148288E+10 | 19864055.37 | 0.146301E+10 | 0.00 | 0.00 |
May | 0.138362E+10 | 0.140558E+10 | 0.165856E+10 | 0.107763E+09 | 0.155080E+10 | 0.00 | 0.00 |
June | 0.246307E+10 | 0.822617E+09 | 0.182741E+10 | 0.303907E+09 | 0.152351E+10 | 0.00 | 0.00 |
July | 0.265161E+10 | 0.534865E+09 | 0.173157E+10 | 0.147593E+09 | 0.158398E+10 | 0.00 | 0.00 |
August | 0.216096E+10 | 0.642832E+09 | 0.160698E+10 | 39327922.90 | 0.156765E+10 | 0.00 | 0.00 |
September | 0.132131E+10 | 0.118212E+10 | 0.124146E+10 | 884671.44 | 0.124058E+10 | 0.00 | 0.00 |
October | 0.480659E+09 | 0.240831E+10 | 0.956313E+09 | 0.00 | 0.956313E+09 | 0.00 | 0.00 |
November | 54784226.22 | 0.357615E+10 | 0.785939E+09 | 0.00 | 0.785939E+09 | 0.00 | 0.00 |
December | 2392250.18 | 0.487847E+10 | 0.648491E+09 | 0.00 | 0.648491E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118667E+11 | 0.291655E+11 | 0.147630E+11 | 0.619382E+09 | 0.141436E+11 | 0.00 | 0.00 |
Minimum of Months | 2392250.18 | 0.534865E+09 | 0.648491E+09 | 0.00 | 0.648491E+09 | 0.00 | 0.00 |
Maximum of Months | 0.265161E+10 | 0.487847E+10 | 0.182741E+10 | 0.303907E+09 | 0.158398E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.139839E+10 | 0.334923E+10 | 0.203900E+10 | 0.125541E+10 | 0.783591E+09 | 0.00 | 0.00 |
February | 0.157618E+10 | 0.278723E+10 | 0.207063E+10 | 0.118598E+10 | 0.884643E+09 | 0.00 | 0.00 |
March | 0.227075E+10 | 0.244653E+10 | 0.257387E+10 | 0.139241E+10 | 0.118146E+10 | 0.00 | 0.00 |
April | 0.315893E+10 | 0.157374E+10 | 0.303013E+10 | 0.153692E+10 | 0.149321E+10 | 0.00 | 0.00 |
May | 0.332097E+10 | 0.122350E+10 | 0.289146E+10 | 0.142289E+10 | 0.146857E+10 | 0.00 | 0.00 |
June | 0.411303E+10 | 0.756358E+09 | 0.296005E+10 | 0.158381E+10 | 0.137625E+10 | 0.00 | 0.00 |
July | 0.433722E+10 | 0.523747E+09 | 0.287306E+10 | 0.140528E+10 | 0.146778E+10 | 0.00 | 0.00 |
August | 0.419305E+10 | 0.610090E+09 | 0.293270E+10 | 0.140522E+10 | 0.152749E+10 | 0.00 | 0.00 |
September | 0.336384E+10 | 0.981350E+09 | 0.257588E+10 | 0.134399E+10 | 0.123189E+10 | 0.00 | 0.00 |
October | 0.271911E+10 | 0.180398E+10 | 0.255485E+10 | 0.160930E+10 | 0.945543E+09 | 0.00 | 0.00 |
November | 0.175477E+10 | 0.256305E+10 | 0.218075E+10 | 0.135980E+10 | 0.820948E+09 | 0.00 | 0.00 |
December | 0.139671E+10 | 0.339843E+10 | 0.203645E+10 | 0.137446E+10 | 0.661990E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.336029E+11 | 0.220172E+11 | 0.307188E+11 | 0.168755E+11 | 0.138433E+11 | 0.00 | 0.00 |
Minimum of Months | 0.139671E+10 | 0.523747E+09 | 0.203645E+10 | 0.118598E+10 | 0.661990E+09 | 0.00 | 0.00 |
Maximum of Months | 0.433722E+10 | 0.339843E+10 | 0.303013E+10 | 0.160930E+10 | 0.152749E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.302099E+10 | 0.322670E+10 | 0.326012E+10 | 0.233217E+10 | 0.927948E+09 | 0.00 | 0.00 |
February | 0.281320E+10 | 0.274025E+10 | 0.296486E+10 | 0.195409E+10 | 0.101077E+10 | 0.00 | 0.00 |
March | 0.248404E+10 | 0.252365E+10 | 0.260997E+10 | 0.134133E+10 | 0.126864E+10 | 0.00 | 0.00 |
April | 0.212291E+10 | 0.166441E+10 | 0.214204E+10 | 0.676326E+09 | 0.146572E+10 | 0.00 | 0.00 |
May | 0.177253E+10 | 0.120110E+10 | 0.170471E+10 | 0.293969E+09 | 0.141074E+10 | 0.00 | 0.00 |
June | 0.219649E+10 | 0.683366E+09 | 0.154559E+10 | 0.214550E+09 | 0.133104E+10 | 0.00 | 0.00 |
July | 0.265766E+10 | 0.418661E+09 | 0.164494E+10 | 0.215560E+09 | 0.142938E+10 | 0.00 | 0.00 |
August | 0.294258E+10 | 0.516973E+09 | 0.198108E+10 | 0.464562E+09 | 0.151651E+10 | 0.00 | 0.00 |
September | 0.318702E+10 | 0.967116E+09 | 0.239043E+10 | 0.110634E+10 | 0.128409E+10 | 0.00 | 0.00 |
October | 0.344730E+10 | 0.181827E+10 | 0.306321E+10 | 0.201210E+10 | 0.105111E+10 | 0.00 | 0.00 |
November | 0.315164E+10 | 0.253494E+10 | 0.325548E+10 | 0.229813E+10 | 0.957356E+09 | 0.00 | 0.00 |
December | 0.327064E+10 | 0.323410E+10 | 0.349267E+10 | 0.269965E+10 | 0.793023E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330670E+11 | 0.215295E+11 | 0.300551E+11 | 0.156088E+11 | 0.144463E+11 | 0.00 | 0.00 |
Minimum of Months | 0.177253E+10 | 0.418661E+09 | 0.154559E+10 | 0.214550E+09 | 0.793023E+09 | 0.00 | 0.00 |
Maximum of Months | 0.344730E+10 | 0.323410E+10 | 0.349267E+10 | 0.269965E+10 | 0.151651E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.121844E+12 | -0.120048E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179666E+10 | 82.17 | 0.00 | 0.00 |
February | 0.110626E+12 | -0.108990E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.163560E+10 | 82.17 | 0.00 | 0.00 |
March | 0.120453E+12 | -0.118662E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.179120E+10 | 82.17 | 0.00 | 0.00 |
April | 0.112454E+12 | -0.110747E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.170679E+10 | 82.17 | 0.00 | 0.00 |
May | 0.110881E+12 | -0.109126E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175507E+10 | 82.17 | 0.00 | 0.00 |
June | 0.102495E+12 | -0.100798E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169688E+10 | 82.17 | 0.00 | 0.00 |
July | 0.102636E+12 | -0.100883E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
August | 0.101934E+12 | -0.100180E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
September | 0.100659E+12 | -0.989618E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169686E+10 | 82.17 | 0.00 | 0.00 |
October | 0.108300E+12 | -0.106547E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175366E+10 | 82.17 | 0.00 | 0.00 |
November | 0.109958E+12 | -0.108260E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169770E+10 | 82.17 | 0.00 | 0.00 |
December | 0.118570E+12 | -0.116797E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177284E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.132081E+13 | -0.130000E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.208101E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.100659E+12 | -0.120048E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.179666E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.121844E+12 | -0.989618E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.163560E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804709E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164122243.7 | 82.17 | 0.00 | 0.00 |
February | 0.727160E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148237852.6 | 82.17 | 0.00 | 0.00 |
March | 0.804567E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164115175.1 | 82.17 | 0.00 | 0.00 |
April | 0.779701E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158810355.9 | 82.17 | 0.00 | 0.00 |
May | 0.804706E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164094940.2 | 82.17 | 0.00 | 0.00 |
June | 0.778856E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158792969.0 | 82.17 | 0.00 | 0.00 |
July | 0.805548E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164079401.7 | 82.17 | 0.00 | 0.00 |
August | 0.804704E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164080786.3 | 82.17 | 0.00 | 0.00 |
September | 0.779840E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158793110.6 | 82.17 | 0.00 | 0.00 |
October | 0.804566E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164103268.6 | 82.17 | 0.00 | 0.00 |
November | 0.778015E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158828044.2 | 82.17 | 0.00 | 0.00 |
December | 0.805552E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164122144.3 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947792E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193218E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727160E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164122243.7 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805552E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148237852.6 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.727626E+11 | -0.711963E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156631E+10 | 60.05 | 0.00 | 0.00 |
February | 0.662354E+11 | -0.648029E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.143248E+10 | 60.05 | 0.00 | 0.00 |
March | 0.716216E+11 | -0.700629E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.155874E+10 | 60.05 | 0.00 | 0.00 |
April | 0.657066E+11 | -0.642351E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147154E+10 | 60.05 | 0.00 | 0.00 |
May | 0.633064E+11 | -0.617978E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150866E+10 | 60.05 | 0.00 | 0.00 |
June | 0.571307E+11 | -0.556729E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145780E+10 | 60.05 | 0.00 | 0.00 |
July | 0.561524E+11 | -0.546460E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
August | 0.556016E+11 | -0.540952E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
September | 0.555189E+11 | -0.540611E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145778E+10 | 60.05 | 0.00 | 0.00 |
October | 0.610428E+11 | -0.595361E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150670E+10 | 60.05 | 0.00 | 0.00 |
November | 0.635209E+11 | -0.620619E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145895E+10 | 60.05 | 0.00 | 0.00 |
December | 0.699181E+11 | -0.683848E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.153329E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.758518E+12 | -0.740553E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.179650E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.555189E+11 | -0.711963E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.156631E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.727626E+11 | -0.540611E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.143248E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_1 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.432927E+11 | 41038.85 | 21-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314396E+11 | 36909.81 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152137E+11 | 30685.07 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407170E+10 | 17578.56 | 08-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.684324E+09 | 11115.32 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21619895.62 | 2821.94 | 09-JUN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1171987.39 | 6.52 | 28-JUL-19:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 748630.08 | 6.96 | 07-AUG-19:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59791.04 | 5.19 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615804E+10 | 28497.90 | 26-OCT-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178996E+11 | 31262.69 | 27-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.439587E+11 | 42792.21 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 59791.04 | 5.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.439587E+11 | 42792.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139083E+10 | 2255.07 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.988734E+09 | 2081.36 | 04-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.623755E+09 | 1727.42 | 04-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189657E+09 | 1113.72 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62677894.94 | 834.00 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5540733.80 | 419.88 | 09-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94102.50 | 73.45 | 09-SEP-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223828E+09 | 1772.28 | 26-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.532581E+09 | 1529.71 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132039E+10 | 2172.17 | 09-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139083E+10 | 2255.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3400111.44 | 180.84 | 19-JAN-10:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3400111.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3400111.44 | 180.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 52096667.72 | 608.68 | 20-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18136411.14 | 578.62 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4671572.10 | 272.00 | 09-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 74904650.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52096667.72 | 608.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.918509E+09 | 1017.61 | 20-JAN-02:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.654747E+09 | 1085.20 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183732E+09 | 757.54 | 04-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9860744.16 | 337.59 | 08-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17280.45 | 22.35 | 06-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47838201.32 | 630.65 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180744E+09 | 716.59 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.905558E+09 | 961.63 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.918509E+09 | 1085.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6072622.34 | 1264.00 | 19-JAN-11:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6072622.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6072622.34 | 1264.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.573681E+11 | 47952.96 | 21-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.422982E+11 | 43752.09 | 05-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218719E+11 | 37141.89 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.698536E+10 | 23078.86 | 08-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140828E+10 | 16584.13 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 70092432.21 | 6748.49 | 09-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 776406.97 | 5.87 | 12-JUL-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 330348.50 | 5.51 | 08-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3647.07 | 0.90 | 05-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.988502E+10 | 34871.08 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279407E+11 | 38145.45 | 27-NOV-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.600651E+11 | 49583.67 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227894E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3647.07 | 0.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.600651E+11 | 49583.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32837.64 | 54.73 | 15-DEC-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32837.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32837.64 | 54.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.210296E+10 | 17073.88 | 17-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139565E+10 | 11224.56 | 16-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.585398E+09 | 5820.67 | 22-MAR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86626551.88 | 5796.26 | 28-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23328634.96 | 5545.84 | 17-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5259381.75 | 4805.53 | 08-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22971.41 | 382.86 | 06-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 364504.74 | 1632.10 | 28-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5406651.24 | 4812.70 | 27-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.227004E+09 | 10553.43 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.656705E+09 | 7355.56 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200280E+10 | 14794.36 | 21-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.709152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22971.41 | 382.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.210296E+10 | 17073.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.282776E+10 | 17736.31 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187394E+10 | 17922.54 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.664233E+09 | 6484.52 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82431567.57 | 8598.75 | 02-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17553713.22 | 5766.59 | 07-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4561377.42 | 4485.77 | 02-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 320227.13 | 3451.14 | 27-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2107241.19 | 4193.83 | 23-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7485344.69 | 7228.35 | 19-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.279737E+09 | 12918.75 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.976028E+09 | 12806.99 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290794E+10 | 18846.25 | 15-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.964411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 320227.13 | 3451.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.290794E+10 | 18846.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167551E+11 | 61357.74 | 01-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114359E+11 | 61854.87 | 18-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352173E+10 | 56973.18 | 10-MAR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.366464E+09 | 51237.87 | 06-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54825292.81 | 35577.98 | 25-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5141180.01 | 27937.18 | 09-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10681658.48 | 25447.40 | 08-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130405E+10 | 56565.31 | 13-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.529379E+10 | 56718.71 | 26-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180353E+11 | 95377.70 | 14-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.567831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180353E+11 | 95377.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.230082E+10 | 15749.57 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154754E+10 | 12560.20 | 16-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.651708E+09 | 6145.93 | 19-MAR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109887E+09 | 5500.28 | 15-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18040972.82 | 5263.13 | 11-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1032332.99 | 2116.04 | 08-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 470494.32 | 4704.94 | 08-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.258027E+09 | 10458.91 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.748495E+09 | 7656.71 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220188E+10 | 13956.61 | 08-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.783790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230082E+10 | 15749.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.297672E+10 | 15675.97 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198783E+10 | 13989.78 | 16-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749559E+09 | 8951.25 | 24-MAR-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122748E+09 | 8624.28 | 01-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19724606.45 | 6876.52 | 03-MAY-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2331224.52 | 5037.83 | 10-JUN-19:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 441296.61 | 1814.05 | 13-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 169109.64 | 1155.41 | 29-AUG-20:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2650355.19 | 3959.39 | 15-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.312953E+09 | 11069.67 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104644E+10 | 9302.57 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300895E+10 | 14992.69 | 21-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 169109.64 | 1155.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.300895E+10 | 15675.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113900E+10 | 4904.72 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797036E+09 | 4936.27 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.435143E+09 | 3462.01 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110198E+09 | 1629.19 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31203480.28 | 1318.59 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4908840.20 | 1256.64 | 01-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26083.60 | 88.51 | 10-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 605891.48 | 905.83 | 31-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2335082.28 | 1007.02 | 22-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188047E+09 | 4593.27 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.493515E+09 | 4469.17 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112520E+10 | 4879.42 | 22-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 26083.60 | 88.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113900E+10 | 4936.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146993E+10 | 4852.23 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100564E+10 | 5053.58 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.477133E+09 | 4412.52 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98844764.29 | 2169.25 | 01-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25639180.51 | 1782.63 | 16-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3596367.93 | 1869.95 | 19-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 248323.65 | 598.35 | 16-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 756654.88 | 1023.97 | 12-AUG-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1731908.36 | 1664.99 | 17-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211280E+09 | 4544.05 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.679715E+09 | 4722.81 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153924E+10 | 5144.82 | 15-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.551375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 248323.65 | 598.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153924E+10 | 5144.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.389578E+10 | 21354.75 | 20-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275693E+10 | 19392.33 | 16-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157554E+10 | 9639.22 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.471880E+09 | 8133.94 | 15-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139228E+09 | 7624.72 | 04-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11390196.66 | 4443.29 | 09-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 380169.02 | 2899.08 | 28-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1030999.50 | 5730.73 | 08-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594119E+09 | 19686.29 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147067E+10 | 10493.83 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373926E+10 | 20337.25 | 08-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.389578E+10 | 21354.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_0 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.297994E+09 | 5637.68 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.907200E+09 | 7395.80 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51549265.21 | 3785.05 | 06-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.907200E+09 | 7395.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6 HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.944340E+09 | 4819.12 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380003E+09 | 3717.37 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11025416.60 | 1387.19 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6705156.24 | 1028.20 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.995315E+09 | 4415.74 | 15-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.995315E+09 | 4819.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.758964E+10 | 14404.54 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.480264E+10 | 13103.67 | 04-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149866E+10 | 8707.39 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137892E+09 | 4711.10 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415107.73 | 316.13 | 05-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.669284E+09 | 9823.49 | 26-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138019E+10 | 10174.25 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.675194E+10 | 14806.88 | 15-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.758964E+10 | 14806.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN HEATING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.272001E+10 | 0.271826E+10 | 22580.75 | 30-JAN-16:12 | 22580.75 | 0.00 |
February | 0.00 | 0.00 | 0.348967E+10 | 0.348290E+10 | 22580.75 | 10-FEB-16:12 | 22580.75 | 0.00 |
March | 0.00 | 0.00 | 0.522988E+10 | 0.521206E+10 | 22580.75 | 04-MAR-16:12 | 22580.75 | 0.00 |
April | 0.00 | 0.00 | 0.833714E+10 | 0.831849E+10 | 23457.99 | 15-APR-08:62 | 20521.02 | 0.00 |
May | 0.00 | 0.00 | 0.103712E+11 | 0.100188E+11 | 24949.07 | 24-MAY-18:02 | 17970.75 | 0.00 |
June | 0.00 | 0.00 | 0.138608E+11 | 0.131550E+11 | 24808.96 | 08-JUN-15:12 | 18102.93 | 0.00 |
July | 0.00 | 0.00 | 0.169316E+11 | 0.150094E+11 | 25952.59 | 01-JUL-08:62 | 16290.35 | 0.00 |
August | 0.00 | 0.00 | 0.166188E+11 | 0.147714E+11 | 25842.34 | 26-AUG-08:62 | 16577.33 | 0.00 |
September | 0.00 | 0.00 | 0.134927E+11 | 0.122974E+11 | 25401.66 | 06-SEP-08:62 | 16513.03 | 0.00 |
October | 0.00 | 0.00 | 0.931147E+10 | 0.893922E+10 | 25194.54 | 11-OCT-08:62 | 17300.52 | 0.00 |
November | 0.00 | 0.00 | 0.433296E+10 | 0.429212E+10 | 23296.55 | 09-NOV-09:02 | 20884.42 | 0.00 |
December | 0.00 | 0.00 | 0.251558E+10 | 0.251435E+10 | 22580.75 | 04-DEC-16:12 | 22580.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107212E+12 | 0.100729E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.251558E+10 | 0.251435E+10 | 22580.75 | 16290.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169316E+11 | 0.150094E+11 | 25952.59 | 22580.75 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.847145E+09 | 0.846452E+09 | 22472.74 | 05-JAN-17:01 | 22472.74 | 0.00 |
February | 0.00 | 0.00 | 0.149312E+10 | 0.148893E+10 | 22487.17 | 15-FEB-18:01 | 22487.17 | 0.00 |
March | 0.00 | 0.00 | 0.269526E+10 | 0.267743E+10 | 22975.24 | 07-MAR-19:31 | 22975.24 | 0.00 |
April | 0.00 | 0.00 | 0.555834E+10 | 0.553411E+10 | 23285.54 | 14-APR-21:51 | 23285.54 | 0.00 |
May | 0.00 | 0.00 | 0.853712E+10 | 0.823310E+10 | 25353.61 | 24-MAY-19:41 | 18985.33 | 0.00 |
June | 0.00 | 0.00 | 0.128111E+11 | 0.121641E+11 | 25667.24 | 24-JUN-08:51 | 19609.70 | 0.00 |
July | 0.00 | 0.00 | 0.153179E+11 | 0.136343E+11 | 27354.33 | 01-JUL-08:51 | 16725.37 | 0.00 |
August | 0.00 | 0.00 | 0.141455E+11 | 0.125776E+11 | 27365.99 | 13-AUG-08:51 | 16976.55 | 0.00 |
September | 0.00 | 0.00 | 0.987309E+10 | 0.888138E+10 | 26258.07 | 05-SEP-21:51 | 17633.85 | 0.00 |
October | 0.00 | 0.00 | 0.512008E+10 | 0.480489E+10 | 26052.43 | 02-OCT-21:51 | 18873.91 | 0.00 |
November | 0.00 | 0.00 | 0.187133E+10 | 0.183963E+10 | 23792.57 | 02-NOV-18:11 | 22466.50 | 0.00 |
December | 0.00 | 0.00 | 0.605148E+09 | 0.604796E+09 | 22362.43 | 18-DEC-16:12 | 22362.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.788751E+11 | 0.732868E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.605148E+09 | 0.604796E+09 | 22362.43 | 16725.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.153179E+11 | 0.136343E+11 | 27365.99 | 23285.54 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.373631E+11 | 0.373631E+11 | 73501.00 | 01-JAN-14:00 | 73501.00 | 0.00 |
February | 0.00 | 0.00 | 0.365359E+11 | 0.365359E+11 | 76594.58 | 14-FEB-13:00 | 76594.58 | 0.00 |
March | 0.00 | 0.00 | 0.376866E+11 | 0.376866E+11 | 66761.51 | 08-MAR-13:30 | 66761.51 | 0.00 |
April | 0.00 | 0.00 | 0.411196E+11 | 0.411196E+11 | 52753.88 | 01-APR-14:10 | 52753.88 | 0.00 |
May | 0.00 | 0.00 | 0.417160E+11 | 0.414544E+11 | 43269.15 | 13-MAY-14:10 | 43269.15 | 0.00 |
June | 0.00 | 0.00 | 0.532971E+11 | 0.528542E+11 | 52968.95 | 29-JUN-14:30 | 52968.95 | 0.00 |
July | 0.00 | 0.00 | 0.704126E+11 | 0.672272E+11 | 56371.87 | 23-JUL-14:10 | 56371.87 | 0.00 |
August | 0.00 | 0.00 | 0.751852E+11 | 0.721954E+11 | 64380.36 | 20-AUG-14:10 | 64380.36 | 0.00 |
September | 0.00 | 0.00 | 0.734132E+11 | 0.717574E+11 | 73607.85 | 28-SEP-13:30 | 73607.85 | 0.00 |
October | 0.00 | 0.00 | 0.666733E+11 | 0.663531E+11 | 75995.81 | 31-OCT-13:00 | 75995.81 | 0.00 |
November | 0.00 | 0.00 | 0.488923E+11 | 0.488923E+11 | 72916.88 | 20-NOV-13:30 | 72916.88 | 0.00 |
December | 0.00 | 0.00 | 0.399613E+11 | 0.399613E+11 | 71695.65 | 31-DEC-13:50 | 71695.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.622256E+12 | 0.613401E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.365359E+11 | 0.365359E+11 | 43269.15 | 43269.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.751852E+11 | 0.721954E+11 | 76594.58 | 76594.58 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.331729E+10 | 0.331564E+10 | 119647.42 | 01-JAN-16:12 | 119647.42 | 0.00 |
February | 0.00 | 0.00 | 0.684126E+10 | 0.682118E+10 | 119647.42 | 17-FEB-16:12 | 118780.69 | 0.00 |
March | 0.00 | 0.00 | 0.186289E+11 | 0.184706E+11 | 119647.42 | 02-MAR-19:02 | 119647.42 | 0.00 |
April | 0.00 | 0.00 | 0.375111E+11 | 0.373441E+11 | 121546.02 | 14-APR-21:51 | 121546.02 | 0.00 |
May | 0.00 | 0.00 | 0.621358E+11 | 0.592363E+11 | 132377.98 | 24-MAY-19:41 | 100102.13 | 0.00 |
June | 0.00 | 0.00 | 0.921486E+11 | 0.863878E+11 | 135764.83 | 05-JUN-21:51 | 99278.34 | 0.00 |
July | 0.00 | 0.00 | 0.115161E+12 | 0.990162E+11 | 147095.95 | 31-JUL-20:11 | 88020.32 | 0.00 |
August | 0.00 | 0.00 | 0.103769E+12 | 0.890691E+11 | 143986.29 | 13-AUG-08:51 | 89287.42 | 0.00 |
September | 0.00 | 0.00 | 0.714767E+11 | 0.624071E+11 | 139614.30 | 05-SEP-21:51 | 91612.76 | 0.00 |
October | 0.00 | 0.00 | 0.368307E+11 | 0.340901E+11 | 137610.57 | 02-OCT-21:51 | 98739.67 | 0.00 |
November | 0.00 | 0.00 | 0.121943E+11 | 0.119316E+11 | 119862.56 | 02-NOV-18:11 | 116681.10 | 0.00 |
December | 0.00 | 0.00 | 0.223757E+10 | 0.223501E+10 | 119647.42 | 01-DEC-16:12 | 119647.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.562252E+12 | 0.510325E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.223757E+10 | 0.223501E+10 | 119647.42 | 88020.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.115161E+12 | 0.990162E+11 | 147095.95 | 121546.02 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.256169E+10 | 0.255874E+10 | 19666.34 | 03-JAN-09:02 | 19666.34 | 0.00 |
February | 0.00 | 0.00 | 0.313950E+10 | 0.312993E+10 | 19666.34 | 09-FEB-16:12 | 19666.34 | 0.00 |
March | 0.00 | 0.00 | 0.533109E+10 | 0.530457E+10 | 19985.60 | 29-MAR-08:62 | 18369.61 | 0.00 |
April | 0.00 | 0.00 | 0.886034E+10 | 0.883664E+10 | 20088.06 | 15-APR-08:62 | 18480.87 | 0.00 |
May | 0.00 | 0.00 | 0.109775E+11 | 0.105858E+11 | 21692.07 | 24-MAY-18:02 | 15673.67 | 0.00 |
June | 0.00 | 0.00 | 0.146159E+11 | 0.138620E+11 | 21495.72 | 08-JUN-08:62 | 15725.60 | 0.00 |
July | 0.00 | 0.00 | 0.179358E+11 | 0.159232E+11 | 22463.25 | 01-JUL-08:62 | 14387.09 | 0.00 |
August | 0.00 | 0.00 | 0.173184E+11 | 0.153910E+11 | 21901.15 | 23-AUG-08:62 | 15443.76 | 0.00 |
September | 0.00 | 0.00 | 0.135524E+11 | 0.123321E+11 | 21803.34 | 06-SEP-08:62 | 15454.13 | 0.00 |
October | 0.00 | 0.00 | 0.908824E+10 | 0.870413E+10 | 21577.97 | 11-OCT-08:62 | 15972.44 | 0.00 |
November | 0.00 | 0.00 | 0.420273E+10 | 0.416078E+10 | 19984.40 | 09-NOV-09:02 | 18732.90 | 0.00 |
December | 0.00 | 0.00 | 0.233055E+10 | 0.232884E+10 | 19666.34 | 01-DEC-09:02 | 19666.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109914E+12 | 0.103118E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.233055E+10 | 0.232884E+10 | 19666.34 | 14387.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.179358E+11 | 0.159232E+11 | 22463.25 | 19666.34 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.611462E+09 | 0.609592E+09 | 19474.67 | 01-JAN-09:02 | 19474.67 | 0.00 |
February | 0.00 | 0.00 | 0.110175E+10 | 0.109457E+10 | 19474.67 | 13-FEB-09:02 | 19474.67 | 0.00 |
March | 0.00 | 0.00 | 0.301845E+10 | 0.299387E+10 | 19803.66 | 29-MAR-08:62 | 18156.97 | 0.00 |
April | 0.00 | 0.00 | 0.652003E+10 | 0.649263E+10 | 20208.14 | 14-APR-21:51 | 20208.14 | 0.00 |
May | 0.00 | 0.00 | 0.921965E+10 | 0.887824E+10 | 21940.39 | 24-MAY-19:41 | 16226.71 | 0.00 |
June | 0.00 | 0.00 | 0.132039E+11 | 0.125098E+11 | 22968.51 | 24-JUN-08:32 | 18421.73 | 0.00 |
July | 0.00 | 0.00 | 0.158888E+11 | 0.141214E+11 | 24594.95 | 09-JUL-08:22 | 18074.88 | 0.00 |
August | 0.00 | 0.00 | 0.144462E+11 | 0.127996E+11 | 24366.41 | 26-AUG-08:32 | 16073.55 | 0.00 |
September | 0.00 | 0.00 | 0.977782E+10 | 0.876455E+10 | 22851.17 | 05-SEP-21:51 | 15143.73 | 0.00 |
October | 0.00 | 0.00 | 0.524632E+10 | 0.492747E+10 | 22926.73 | 02-OCT-21:51 | 15945.68 | 0.00 |
November | 0.00 | 0.00 | 0.164580E+10 | 0.161350E+10 | 20070.05 | 02-NOV-18:11 | 18345.29 | 0.00 |
December | 0.00 | 0.00 | 0.439803E+09 | 0.439057E+09 | 19474.67 | 10-DEC-09:02 | 19474.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.811200E+11 | 0.752443E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.439803E+09 | 0.439057E+09 | 19474.67 | 15143.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.158888E+11 | 0.141214E+11 | 24594.95 | 20208.14 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.518559E+09 | 0.518336E+09 | 6230.76 | 21-JAN-16:12 | 6230.76 | 0.00 |
February | 0.00 | 0.00 | 0.722897E+09 | 0.721786E+09 | 6230.76 | 15-FEB-16:12 | 6230.76 | 0.00 |
March | 0.00 | 0.00 | 0.112494E+10 | 0.112256E+10 | 6230.76 | 23-MAR-15:12 | 6230.76 | 0.00 |
April | 0.00 | 0.00 | 0.200155E+10 | 0.199747E+10 | 6230.76 | 12-APR-18:02 | 6230.76 | 0.00 |
May | 0.00 | 0.00 | 0.259491E+10 | 0.251261E+10 | 6896.00 | 29-MAY-08:62 | 4867.37 | 0.00 |
June | 0.00 | 0.00 | 0.368588E+10 | 0.351385E+10 | 6873.88 | 08-JUN-15:12 | 4908.35 | 0.00 |
July | 0.00 | 0.00 | 0.457615E+10 | 0.408951E+10 | 7292.72 | 01-JUL-08:62 | 4282.38 | 0.00 |
August | 0.00 | 0.00 | 0.444442E+10 | 0.397859E+10 | 7247.26 | 26-AUG-08:62 | 4383.24 | 0.00 |
September | 0.00 | 0.00 | 0.342785E+10 | 0.313609E+10 | 6919.09 | 10-SEP-08:62 | 4623.61 | 0.00 |
October | 0.00 | 0.00 | 0.219310E+10 | 0.210534E+10 | 6743.21 | 02-OCT-08:62 | 5261.09 | 0.00 |
November | 0.00 | 0.00 | 0.830928E+09 | 0.823685E+09 | 6277.46 | 02-NOV-18:02 | 6076.32 | 0.00 |
December | 0.00 | 0.00 | 0.437873E+09 | 0.437774E+09 | 6230.76 | 05-DEC-16:12 | 6230.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.265591E+11 | 0.249576E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.437873E+09 | 0.437774E+09 | 6230.76 | 4282.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.457615E+10 | 0.408951E+10 | 7292.72 | 6230.76 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.139003E+09 | 0.138938E+09 | 6186.83 | 05-JAN-17:01 | 6186.83 | 0.00 |
February | 0.00 | 0.00 | 0.272927E+09 | 0.272248E+09 | 6210.54 | 15-FEB-18:01 | 6210.54 | 0.00 |
March | 0.00 | 0.00 | 0.515283E+09 | 0.512682E+09 | 6345.82 | 07-MAR-19:31 | 6345.82 | 0.00 |
April | 0.00 | 0.00 | 0.132615E+10 | 0.132049E+10 | 6404.11 | 14-APR-21:51 | 6404.11 | 0.00 |
May | 0.00 | 0.00 | 0.217824E+10 | 0.210627E+10 | 6963.91 | 24-MAY-19:41 | 5175.52 | 0.00 |
June | 0.00 | 0.00 | 0.346405E+10 | 0.330450E+10 | 7051.24 | 24-JUN-08:51 | 5430.52 | 0.00 |
July | 0.00 | 0.00 | 0.421508E+10 | 0.378724E+10 | 7584.25 | 01-JUL-08:51 | 4509.71 | 0.00 |
August | 0.00 | 0.00 | 0.386788E+10 | 0.347038E+10 | 7557.55 | 26-AUG-08:51 | 4578.71 | 0.00 |
September | 0.00 | 0.00 | 0.256321E+10 | 0.231977E+10 | 7225.02 | 05-SEP-21:51 | 4803.96 | 0.00 |
October | 0.00 | 0.00 | 0.116618E+10 | 0.109182E+10 | 7166.01 | 02-OCT-21:51 | 5224.47 | 0.00 |
November | 0.00 | 0.00 | 0.286944E+09 | 0.282021E+09 | 6566.62 | 02-NOV-18:11 | 6225.09 | 0.00 |
December | 0.00 | 0.00 | 80366453.47 | 80297610.52 | 6057.50 | 31-DEC-16:12 | 6057.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200753E+11 | 0.186867E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 80366453.47 | 80297610.52 | 6057.50 | 4509.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.421508E+10 | 0.378724E+10 | 7584.25 | 6404.11 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.756269E+10 | 0.755119E+10 | 26075.12 | 25-JAN-16:12 | 26075.12 | 0.00 |
February | 0.00 | 0.00 | 0.759892E+10 | 0.757759E+10 | 26215.09 | 21-FEB-16:12 | 25147.70 | 0.00 |
March | 0.00 | 0.00 | 0.800648E+10 | 0.797422E+10 | 26075.12 | 05-MAR-16:12 | 26075.12 | 0.00 |
April | 0.00 | 0.00 | 0.988888E+10 | 0.985878E+10 | 27120.28 | 15-APR-08:62 | 23411.62 | 0.00 |
May | 0.00 | 0.00 | 0.115842E+11 | 0.110953E+11 | 28680.19 | 24-MAY-15:12 | 20303.26 | 0.00 |
June | 0.00 | 0.00 | 0.161483E+11 | 0.151298E+11 | 28816.06 | 08-JUN-15:12 | 20408.58 | 0.00 |
July | 0.00 | 0.00 | 0.221051E+11 | 0.192209E+11 | 30498.45 | 01-JUL-08:62 | 17794.31 | 0.00 |
August | 0.00 | 0.00 | 0.225669E+11 | 0.197734E+11 | 30215.07 | 26-AUG-08:62 | 18419.21 | 0.00 |
September | 0.00 | 0.00 | 0.196393E+11 | 0.178294E+11 | 29380.83 | 06-SEP-08:62 | 18109.61 | 0.00 |
October | 0.00 | 0.00 | 0.154139E+11 | 0.148358E+11 | 28897.36 | 11-OCT-08:62 | 19632.99 | 0.00 |
November | 0.00 | 0.00 | 0.978888E+10 | 0.971559E+10 | 26741.80 | 01-NOV-08:62 | 23702.07 | 0.00 |
December | 0.00 | 0.00 | 0.804112E+10 | 0.803449E+10 | 26075.12 | 06-DEC-16:12 | 26075.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158345E+12 | 0.148596E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.756269E+10 | 0.755119E+10 | 26075.12 | 17794.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.225669E+11 | 0.197734E+11 | 30498.45 | 26075.12 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.500286E+10 | 0.337114E+10 | 9331.80 | 01-JAN-13:00 | 7262.70 | 0.00 |
February | 0.00 | 0.00 | 0.617970E+10 | 0.434650E+10 | 11030.23 | 14-FEB-16:10 | 11030.23 | 0.00 |
March | 0.00 | 0.00 | 0.983403E+10 | 0.774993E+10 | 10630.57 | 08-MAR-14:00 | 9970.10 | 0.00 |
April | 0.00 | 0.00 | 0.140113E+11 | 0.124403E+11 | 11527.45 | 11-APR-18:15 | 11527.45 | 0.00 |
May | 0.00 | 0.00 | 0.177409E+11 | 0.153828E+11 | 14286.76 | 19-MAY-18:15 | 14286.76 | 0.00 |
June | 0.00 | 0.00 | 0.243216E+11 | 0.213534E+11 | 17947.58 | 23-JUN-18:03 | 17947.58 | 0.00 |
July | 0.00 | 0.00 | 0.309495E+11 | 0.252195E+11 | 19590.66 | 21-JUL-18:13 | 19590.66 | 0.00 |
August | 0.00 | 0.00 | 0.301031E+11 | 0.244976E+11 | 17567.51 | 18-AUG-18:15 | 16747.96 | 0.00 |
September | 0.00 | 0.00 | 0.243736E+11 | 0.200397E+11 | 16089.89 | 03-SEP-13:30 | 15342.24 | 0.00 |
October | 0.00 | 0.00 | 0.169016E+11 | 0.142372E+11 | 14551.50 | 02-OCT-15:10 | 13386.36 | 0.00 |
November | 0.00 | 0.00 | 0.893838E+10 | 0.678516E+10 | 10756.82 | 02-NOV-15:10 | 9172.15 | 0.00 |
December | 0.00 | 0.00 | 0.461534E+10 | 0.292208E+10 | 8663.45 | 30-DEC-12:40 | 6087.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192972E+12 | 0.158345E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.461534E+10 | 0.292208E+10 | 8663.45 | 6087.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.309495E+11 | 0.252195E+11 | 19590.66 | 19590.66 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.543378E+09 | 0.398808E+09 | 4258.37 | 01-JAN-13:00 | 3064.00 | 0.00 |
February | 0.00 | 0.00 | 0.114310E+10 | 0.891324E+09 | 6754.45 | 14-FEB-13:10 | 5949.48 | 0.00 |
March | 0.00 | 0.00 | 0.274274E+10 | 0.224168E+10 | 7238.28 | 08-MAR-13:30 | 6577.86 | 0.00 |
April | 0.00 | 0.00 | 0.623206E+10 | 0.565543E+10 | 8482.89 | 13-APR-13:00 | 8482.89 | 0.00 |
May | 0.00 | 0.00 | 0.909477E+10 | 0.824679E+10 | 9512.58 | 28-MAY-13:30 | 9125.64 | 0.00 |
June | 0.00 | 0.00 | 0.135862E+11 | 0.125178E+11 | 12356.92 | 28-JUN-14:10 | 12356.92 | 0.00 |
July | 0.00 | 0.00 | 0.172900E+11 | 0.153451E+11 | 12154.01 | 20-JUL-14:10 | 12154.01 | 0.00 |
August | 0.00 | 0.00 | 0.164607E+11 | 0.145710E+11 | 12262.57 | 21-AUG-14:10 | 11703.34 | 0.00 |
September | 0.00 | 0.00 | 0.122809E+11 | 0.108141E+11 | 11983.37 | 03-SEP-13:30 | 11780.25 | 0.00 |
October | 0.00 | 0.00 | 0.699877E+10 | 0.614460E+10 | 10498.83 | 01-OCT-13:10 | 10366.77 | 0.00 |
November | 0.00 | 0.00 | 0.187599E+10 | 0.139140E+10 | 7068.81 | 02-NOV-13:00 | 5326.22 | 0.00 |
December | 0.00 | 0.00 | 0.256456E+09 | 0.173399E+09 | 5032.56 | 02-DEC-12:50 | 2848.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.885051E+11 | 0.783914E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.256456E+09 | 0.173399E+09 | 4258.37 | 2848.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.172900E+11 | 0.153451E+11 | 12356.92 | 12356.92 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_1 COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.214940E+09 | 0.214940E+09 | 6974.95 | 05-JAN-15:20 | 6974.95 | 0.00 |
February | 0.00 | 0.00 | 0.160687E+10 | 0.160687E+10 | 38276.68 | 14-FEB-16:10 | 38276.68 | 0.00 |
March | 0.00 | 0.00 | 0.560001E+10 | 0.559835E+10 | 36829.24 | 08-MAR-16:10 | 36829.24 | 0.00 |
April | 0.00 | 0.00 | 0.245166E+11 | 0.245027E+11 | 58692.08 | 13-APR-18:03 | 58692.08 | 0.00 |
May | 0.00 | 0.00 | 0.500120E+11 | 0.486998E+11 | 73255.71 | 19-MAY-18:03 | 73255.71 | 0.00 |
June | 0.00 | 0.00 | 0.964554E+11 | 0.937919E+11 | 92520.77 | 27-JUN-18:03 | 92520.77 | 0.00 |
July | 0.00 | 0.00 | 0.141715E+12 | 0.123687E+12 | 97679.99 | 21-JUL-18:17 | 97679.99 | 0.00 |
August | 0.00 | 0.00 | 0.126806E+12 | 0.112034E+12 | 85988.55 | 18-AUG-18:03 | 85988.55 | 0.00 |
September | 0.00 | 0.00 | 0.798687E+11 | 0.729789E+11 | 75679.14 | 20-SEP-15:10 | 75679.14 | 0.00 |
October | 0.00 | 0.00 | 0.314821E+11 | 0.298753E+11 | 68074.97 | 06-OCT-15:10 | 68074.97 | 0.00 |
November | 0.00 | 0.00 | 0.733623E+09 | 0.706240E+09 | 17455.45 | 09-NOV-14:00 | 17455.45 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.559012E+12 | 0.513696E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141715E+12 | 0.123687E+12 | 97679.99 | 97679.99 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_6 COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.185591E+09 | 0.185591E+09 | 5610.89 | 05-JAN-14:10 | 5610.89 | 0.00 |
February | 0.00 | 0.00 | 0.124337E+10 | 0.124337E+10 | 28102.73 | 14-FEB-16:10 | 28102.73 | 0.00 |
March | 0.00 | 0.00 | 0.514900E+10 | 0.514899E+10 | 32252.56 | 08-MAR-16:13 | 32252.56 | 0.00 |
April | 0.00 | 0.00 | 0.242403E+11 | 0.242382E+11 | 51967.14 | 28-APR-18:03 | 51967.14 | 0.00 |
May | 0.00 | 0.00 | 0.504216E+11 | 0.497226E+11 | 67931.39 | 19-MAY-18:03 | 67931.39 | 0.00 |
June | 0.00 | 0.00 | 0.963152E+11 | 0.952230E+11 | 91150.04 | 28-JUN-16:00 | 91150.04 | 0.00 |
July | 0.00 | 0.00 | 0.133194E+12 | 0.122926E+12 | 91258.82 | 21-JUL-18:03 | 91258.82 | 0.00 |
August | 0.00 | 0.00 | 0.115544E+12 | 0.107364E+12 | 79319.59 | 01-AUG-15:40 | 79319.59 | 0.00 |
September | 0.00 | 0.00 | 0.690027E+11 | 0.651070E+11 | 67826.90 | 02-SEP-17:07 | 67826.90 | 0.00 |
October | 0.00 | 0.00 | 0.255052E+11 | 0.246714E+11 | 53202.98 | 06-OCT-15:10 | 53202.98 | 0.00 |
November | 0.00 | 0.00 | 0.646450E+09 | 0.638888E+09 | 16310.11 | 09-NOV-14:00 | 16310.11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.521447E+12 | 0.496468E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.133194E+12 | 0.122926E+12 | 91258.82 | 91258.82 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_0 COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1084031.41 | 1084031.41 | 722.45 | 14-FEB-16:10 | 722.45 | 0.00 |
March | 0.00 | 0.00 | 206.03 | 206.03 | 0.79 | 15-MAR-18:53 | 0.79 | 0.00 |
April | 0.00 | 0.00 | 0.389870E+10 | 0.388599E+10 | 18350.34 | 28-APR-19:10 | 18350.34 | 0.00 |
May | 0.00 | 0.00 | 0.117679E+11 | 0.113781E+11 | 22526.62 | 19-MAY-19:20 | 22526.62 | 0.00 |
June | 0.00 | 0.00 | 0.295978E+11 | 0.279181E+11 | 29708.34 | 27-JUN-18:20 | 29708.34 | 0.00 |
July | 0.00 | 0.00 | 0.535509E+11 | 0.426256E+11 | 43459.53 | 31-JUL-19:55 | 22218.69 | 0.00 |
August | 0.00 | 0.00 | 0.527526E+11 | 0.418843E+11 | 38175.54 | 08-AUG-19:40 | 27317.02 | 0.00 |
September | 0.00 | 0.00 | 0.395294E+11 | 0.322826E+11 | 34732.42 | 04-SEP-19:35 | 23995.95 | 0.00 |
October | 0.00 | 0.00 | 0.181832E+11 | 0.158200E+11 | 35000.74 | 02-OCT-19:20 | 21624.04 | 0.00 |
November | 0.00 | 0.00 | 0.214290E+10 | 0.189688E+10 | 12649.19 | 08-NOV-22:00 | 10232.78 | 0.00 |
December | 0.00 | 0.00 | 76836722.47 | 73540581.24 | 4938.63 | 01-DEC-21:00 | 4692.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.211501E+12 | 0.177766E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.535509E+11 | 0.426256E+11 | 43459.53 | 29708.34 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 90600.99 | 90600.99 | 6.04 | 28-JAN-18:05 | 6.04 | 0.00 |
February | 0.00 | 0.00 | 0.261973E+09 | 0.261973E+09 | 14635.20 | 14-FEB-16:00 | 14635.20 | 0.00 |
March | 0.00 | 0.00 | 0.977839E+09 | 0.977838E+09 | 17713.01 | 08-MAR-14:00 | 17713.01 | 0.00 |
April | 0.00 | 0.00 | 0.125110E+11 | 0.125063E+11 | 43791.44 | 28-APR-19:00 | 43791.44 | 0.00 |
May | 0.00 | 0.00 | 0.262918E+11 | 0.258729E+11 | 46474.42 | 19-MAY-20:00 | 46474.42 | 0.00 |
June | 0.00 | 0.00 | 0.455896E+11 | 0.445723E+11 | 49441.63 | 06-JUN-20:02 | 43218.29 | 0.00 |
July | 0.00 | 0.00 | 0.643259E+11 | 0.572222E+11 | 72543.79 | 31-JUL-20:00 | 37623.09 | 0.00 |
August | 0.00 | 0.00 | 0.576843E+11 | 0.515232E+11 | 61260.54 | 08-AUG-19:40 | 45274.79 | 0.00 |
September | 0.00 | 0.00 | 0.359791E+11 | 0.330527E+11 | 51753.25 | 04-SEP-19:02 | 40850.60 | 0.00 |
October | 0.00 | 0.00 | 0.123942E+11 | 0.116463E+11 | 42784.59 | 10-OCT-18:02 | 39727.48 | 0.00 |
November | 0.00 | 0.00 | 2144362.28 | 2142476.27 | 914.79 | 09-NOV-14:00 | 914.79 | 0.00 |
December | 0.00 | 0.00 | 70250.99 | 70249.84 | 8.83 | 25-DEC-08:63 | 8.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.256018E+12 | 0.237638E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 70250.99 | 70249.84 | 6.04 | 6.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.643259E+11 | 0.572222E+11 | 72543.79 | 46474.42 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 845595.07 | 845595.07 | 276.05 | 01-JAN-14:10 | 276.05 | 0.00 |
February | 0.00 | 0.00 | 0.464430E+09 | 0.464430E+09 | 14895.45 | 14-FEB-15:10 | 14895.45 | 0.00 |
March | 0.00 | 0.00 | 0.905433E+09 | 0.905433E+09 | 16452.78 | 08-MAR-14:00 | 16452.78 | 0.00 |
April | 0.00 | 0.00 | 0.533413E+10 | 0.533405E+10 | 18262.36 | 13-APR-15:10 | 18262.36 | 0.00 |
May | 0.00 | 0.00 | 0.114475E+11 | 0.113777E+11 | 19366.09 | 19-MAY-15:10 | 19366.09 | 0.00 |
June | 0.00 | 0.00 | 0.250145E+11 | 0.243274E+11 | 26744.07 | 28-JUN-15:12 | 26744.07 | 0.00 |
July | 0.00 | 0.00 | 0.378530E+11 | 0.329096E+11 | 26584.77 | 22-JUL-14:00 | 26584.77 | 0.00 |
August | 0.00 | 0.00 | 0.333915E+11 | 0.294553E+11 | 26339.55 | 21-AUG-14:10 | 24272.52 | 0.00 |
September | 0.00 | 0.00 | 0.200640E+11 | 0.187168E+11 | 26860.17 | 05-SEP-12:50 | 16743.78 | 0.00 |
October | 0.00 | 0.00 | 0.787464E+10 | 0.759158E+10 | 23872.45 | 01-OCT-12:00 | 23167.11 | 0.00 |
November | 0.00 | 0.00 | 9654886.05 | 8829977.62 | 2967.53 | 02-NOV-15:05 | 2745.35 | 0.00 |
December | 0.00 | 0.00 | 25968.41 | 25968.41 | 20.17 | 01-DEC-20:50 | 20.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142360E+12 | 0.131092E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 25968.41 | 25968.41 | 20.17 | 20.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.378530E+11 | 0.329096E+11 | 26860.17 | 26744.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN COOLING COIL
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 15304085.08 | 15304085.08 | 2275.50 | 05-JAN-14:00 | 2275.50 | 0.00 |
February | 0.00 | 0.00 | 0.991441E+09 | 0.991441E+09 | 23211.41 | 14-FEB-16:12 | 23211.41 | 0.00 |
March | 0.00 | 0.00 | 0.401693E+10 | 0.401628E+10 | 25792.55 | 08-MAR-14:00 | 25792.55 | 0.00 |
April | 0.00 | 0.00 | 0.176546E+11 | 0.171155E+11 | 42070.89 | 11-APR-17:20 | 33029.37 | 0.00 |
May | 0.00 | 0.00 | 0.343969E+11 | 0.314285E+11 | 45092.48 | 23-MAY-10:40 | 35734.77 | 0.00 |
June | 0.00 | 0.00 | 0.585737E+11 | 0.510301E+11 | 50499.60 | 25-JUN-10:40 | 39102.91 | 0.00 |
July | 0.00 | 0.00 | 0.828596E+11 | 0.638915E+11 | 57295.48 | 01-JUL-10:50 | 31565.56 | 0.00 |
August | 0.00 | 0.00 | 0.743055E+11 | 0.578681E+11 | 56768.63 | 26-AUG-10:40 | 31107.38 | 0.00 |
September | 0.00 | 0.00 | 0.485413E+11 | 0.397535E+11 | 49710.85 | 03-SEP-10:40 | 38963.43 | 0.00 |
October | 0.00 | 0.00 | 0.188848E+11 | 0.168353E+11 | 44080.41 | 10-OCT-17:15 | 32883.99 | 0.00 |
November | 0.00 | 0.00 | 0.252113E+09 | 0.236778E+09 | 11862.70 | 09-NOV-14:00 | 11862.70 | 0.00 |
December | 0.00 | 0.00 | 43854.75 | 43854.75 | 35.74 | 20-DEC-03:50 | 35.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.340492E+12 | 0.283182E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 43854.75 | 43854.75 | 35.74 | 35.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.828596E+11 | 0.638915E+11 | 57295.48 | 39102.91 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 50986.24 | 200342.26 | 20-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 40765.73 | 159886.84 | 16-FEB-16:12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17254.97 | 103494.57 | 05-MAR-06:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4862.56 | 87524.73 | 06-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 920.55 | 41721.47 | 25-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 51.19 | 31349.71 | 09-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1.79 | 3745.53 | 27-JUL-21:54 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2.32 | 4725.13 | 23-AUG-21:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.48 | 26434.47 | 08-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7297.72 | 135705.72 | 25-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22164.47 | 111844.37 | 27-NOV-06:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 52490.50 | 257806.21 | 21-DEC-16:12 |
Annual Sum or Average | 0.00 | 16306.13 | ||||
Minimum of Months | 0.00 | 0.00 | 1.79 | 3745.53 | ||
Maximum of Months | 0.00 | 0.00 | 52490.50 | 257806.21 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 26472.64 | 55812.91 | 31-JAN-07:54 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 26677.67 | 55856.50 | 07-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 26050.08 | 55333.24 | 01-MAR-07:57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24675.70 | 52887.66 | 03-APR-06:54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22968.82 | 49773.55 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 21377.17 | 46109.60 | 01-JUN-06:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20302.37 | 43131.18 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20097.06 | 42367.18 | 31-AUG-06:42 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20756.19 | 44452.39 | 29-SEP-06:45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22125.59 | 47965.44 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23838.55 | 51512.80 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25424.49 | 54288.33 | 29-DEC-07:57 |
Annual Sum or Average | 0.00 | 23378.29 | ||||
Minimum of Months | 0.00 | 0.00 | 20097.06 | 42367.18 | ||
Maximum of Months | 0.00 | 0.00 | 26677.67 | 55856.50 |
Report: FanReportMonthly
For: VAV_FLR_1 FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109035E+11 | 1.12 | 6271.59 | 03-JAN-19:05 | 1.34 |
February | 0.997637E+10 | 1.13 | 7090.29 | 14-FEB-21:10 | 1.41 |
March | 0.113507E+11 | 1.14 | 7394.96 | 08-MAR-21:02 | 1.43 |
April | 0.120184E+11 | 1.18 | 9507.66 | 13-APR-20:10 | 1.60 |
May | 0.131577E+11 | 1.20 | 10776.22 | 19-MAY-20:10 | 1.68 |
June | 0.148966E+11 | 1.27 | 12630.70 | 27-JUN-20:10 | 1.79 |
July | 0.165909E+11 | 1.30 | 13104.64 | 21-JUL-19:10 | 1.82 |
August | 0.167845E+11 | 1.31 | 12018.76 | 18-AUG-20:10 | 1.74 |
September | 0.151428E+11 | 1.28 | 10761.09 | 13-SEP-20:04 | 1.67 |
October | 0.137654E+11 | 1.22 | 9960.39 | 04-OCT-20:10 | 1.61 |
November | 0.112230E+11 | 1.15 | 7675.25 | 02-NOV-20:10 | 1.46 |
December | 0.108674E+11 | 1.12 | 6008.27 | 31-DEC-13:00 | 1.32 |
Annual Sum or Average | 0.156677E+12 | 1.20 | |||
Minimum of Months | 0.997637E+10 | 1.12 | 6008.27 | 1.32 | |
Maximum of Months | 0.167845E+11 | 1.31 | 13104.64 | 1.82 |
Report: FanReportMonthly
For: VAV_FLR_6 FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109744E+11 | 1.25 | 5983.26 | 05-JAN-22:10 | 1.46 |
February | 0.101366E+11 | 1.26 | 7356.71 | 14-FEB-22:10 | 1.59 |
March | 0.120231E+11 | 1.29 | 7996.10 | 16-MAR-21:10 | 1.66 |
April | 0.133347E+11 | 1.36 | 9799.03 | 28-APR-21:10 | 1.81 |
May | 0.152561E+11 | 1.42 | 10390.24 | 19-MAY-21:10 | 1.85 |
June | 0.171481E+11 | 1.50 | 11822.70 | 27-JUN-21:10 | 1.94 |
July | 0.184296E+11 | 1.52 | 11950.11 | 21-JUL-21:10 | 1.95 |
August | 0.177727E+11 | 1.50 | 11110.93 | 17-AUG-21:10 | 1.88 |
September | 0.151025E+11 | 1.42 | 10081.29 | 13-SEP-21:10 | 1.81 |
October | 0.131812E+11 | 1.34 | 9392.29 | 02-OCT-21:10 | 1.75 |
November | 0.110971E+11 | 1.27 | 7699.98 | 02-NOV-21:10 | 1.62 |
December | 0.109193E+11 | 1.25 | 6629.14 | 01-DEC-22:10 | 1.53 |
Annual Sum or Average | 0.165375E+12 | 1.37 | |||
Minimum of Months | 0.101366E+11 | 1.25 | 5983.26 | 1.46 | |
Maximum of Months | 0.184296E+11 | 1.52 | 11950.11 | 1.95 |
Report: FanReportMonthly
For: VAV_FLR_0 SZVAV FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.670775E+10 | 1.33 | 2504.39 | 01-JAN-00:05 | 1.33 |
February | 0.605861E+10 | 1.33 | 2504.39 | 14-FEB-16:25 | 1.34 |
March | 0.670775E+10 | 1.33 | 2504.39 | 01-MAR-00:10 | 1.33 |
April | 0.649137E+10 | 1.33 | 2504.39 | 01-APR-16:51 | 1.34 |
May | 0.670775E+10 | 1.33 | 2504.39 | 01-MAY-01:40 | 1.33 |
June | 0.650361E+10 | 1.33 | 3078.40 | 27-JUN-18:20 | 1.45 |
July | 0.684576E+10 | 1.33 | 4308.45 | 31-JUL-19:55 | 1.65 |
August | 0.685665E+10 | 1.33 | 3737.43 | 08-AUG-19:40 | 1.56 |
September | 0.652078E+10 | 1.33 | 3306.68 | 01-SEP-20:00 | 1.48 |
October | 0.672118E+10 | 1.33 | 3351.88 | 02-OCT-19:20 | 1.49 |
November | 0.649137E+10 | 1.33 | 2504.39 | 01-NOV-01:00 | 1.32 |
December | 0.670775E+10 | 1.33 | 2504.39 | 02-DEC-22:30 | 1.34 |
Annual Sum or Average | 0.793203E+11 | 1.33 | |||
Minimum of Months | 0.605861E+10 | 1.33 | 2504.39 | 1.32 | |
Maximum of Months | 0.685665E+10 | 1.33 | 4308.45 | 1.65 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | -0.0 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | -0.0 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: ROOM_1_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.187773E+10 | 0.55 | 944.39 | 01-JAN-00:05 | 0.63 |
February | 0.170757E+10 | 0.56 | 944.39 | 01-FEB-00:05 | 0.63 |
March | 0.189681E+10 | 0.58 | 944.39 | 01-MAR-00:10 | 0.63 |
April | 0.186158E+10 | 0.60 | 944.39 | 01-APR-00:10 | 0.63 |
May | 0.192756E+10 | 0.61 | 944.39 | 01-MAY-00:20 | 0.64 |
June | 0.191206E+10 | 0.62 | 944.39 | 01-JUN-00:10 | 0.63 |
July | 0.199793E+10 | 0.63 | 944.39 | 01-JUL-00:10 | 0.63 |
August | 0.199817E+10 | 0.63 | 944.39 | 01-AUG-00:10 | 0.63 |
September | 0.191650E+10 | 0.62 | 944.39 | 01-SEP-00:10 | 0.63 |
October | 0.193935E+10 | 0.60 | 944.39 | 01-OCT-00:10 | 0.63 |
November | 0.183334E+10 | 0.57 | 944.39 | 01-NOV-00:10 | 0.63 |
December | 0.187526E+10 | 0.55 | 944.39 | 01-DEC-00:10 | 0.63 |
Annual Sum or Average | 0.227439E+11 | 0.59 | |||
Minimum of Months | 0.170757E+10 | 0.55 | 944.39 | 0.63 | |
Maximum of Months | 0.199817E+10 | 0.63 | 944.39 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182133E+10 | 0.50 | 935.26 | 01-JAN-00:05 | 0.63 |
February | 0.165422E+10 | 0.51 | 935.26 | 01-FEB-00:05 | 0.63 |
March | 0.184055E+10 | 0.53 | 935.26 | 01-MAR-00:10 | 0.63 |
April | 0.181039E+10 | 0.58 | 935.26 | 01-APR-00:10 | 0.63 |
May | 0.189924E+10 | 0.60 | 935.26 | 01-MAY-00:10 | 0.64 |
June | 0.189340E+10 | 0.61 | 935.26 | 01-JUN-00:10 | 0.63 |
July | 0.197467E+10 | 0.61 | 935.26 | 01-JUL-00:20 | 0.63 |
August | 0.196144E+10 | 0.61 | 935.26 | 01-AUG-00:10 | 0.63 |
September | 0.186020E+10 | 0.60 | 935.26 | 01-SEP-00:10 | 0.63 |
October | 0.186378E+10 | 0.55 | 935.26 | 01-OCT-00:10 | 0.63 |
November | 0.177182E+10 | 0.52 | 935.26 | 01-NOV-00:10 | 0.63 |
December | 0.181799E+10 | 0.50 | 935.26 | 01-DEC-00:10 | 0.63 |
Annual Sum or Average | 0.221690E+11 | 0.56 | |||
Minimum of Months | 0.165422E+10 | 0.50 | 935.26 | 0.63 | |
Maximum of Months | 0.197467E+10 | 0.61 | 935.26 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.214837E+10 | 0.39 | 5196.74 | 01-JAN-15:10 | 0.64 |
February | 0.206737E+10 | 0.44 | 5196.74 | 01-FEB-15:10 | 0.64 |
March | 0.218812E+10 | 0.48 | 5196.74 | 01-MAR-15:10 | 0.64 |
April | 0.234730E+10 | 0.58 | 5196.74 | 01-APR-14:10 | 0.64 |
May | 0.239335E+10 | 0.64 | 5196.74 | 01-MAY-14:10 | 0.63 |
June | 0.288496E+10 | 0.69 | 5196.74 | 01-JUN-14:10 | 0.63 |
July | 0.353390E+10 | 0.71 | 5196.74 | 01-JUL-14:10 | 0.63 |
August | 0.369122E+10 | 0.71 | 5196.74 | 01-AUG-14:10 | 0.63 |
September | 0.355771E+10 | 0.71 | 5196.74 | 01-SEP-14:10 | 0.63 |
October | 0.334510E+10 | 0.60 | 5196.74 | 01-OCT-14:10 | 0.63 |
November | 0.264406E+10 | 0.50 | 5196.74 | 01-NOV-14:10 | 0.63 |
December | 0.227379E+10 | 0.40 | 5196.74 | 01-DEC-15:10 | 0.64 |
Annual Sum or Average | 0.330753E+11 | 0.57 | |||
Minimum of Months | 0.206737E+10 | 0.39 | 5196.74 | 0.63 | |
Maximum of Months | 0.369122E+10 | 0.71 | 5196.74 | 0.64 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.967973E+10 | 0.46 | 5003.99 | 01-JAN-00:05 | 0.63 |
February | 0.874363E+10 | 0.46 | 5003.99 | 01-FEB-00:05 | 0.64 |
March | 0.969217E+10 | 0.48 | 5003.99 | 01-MAR-00:10 | 0.63 |
April | 0.948565E+10 | 0.55 | 5003.99 | 01-APR-00:10 | 0.63 |
May | 0.995382E+10 | 0.58 | 5003.99 | 01-MAY-00:10 | 0.64 |
June | 0.991040E+10 | 0.60 | 5003.99 | 01-JUN-00:10 | 0.63 |
July | 0.103819E+11 | 0.60 | 5003.99 | 01-JUL-00:10 | 0.63 |
August | 0.102639E+11 | 0.60 | 5003.99 | 01-AUG-00:10 | 0.63 |
September | 0.971228E+10 | 0.59 | 5003.99 | 01-SEP-00:10 | 0.63 |
October | 0.977315E+10 | 0.52 | 5003.99 | 01-OCT-00:10 | 0.63 |
November | 0.936808E+10 | 0.46 | 5003.99 | 01-NOV-00:10 | 0.63 |
December | 0.967973E+10 | 0.46 | 5003.99 | 01-DEC-00:10 | 0.63 |
Annual Sum or Average | 0.116644E+12 | 0.53 | |||
Minimum of Months | 0.874363E+10 | 0.46 | 5003.99 | 0.63 | |
Maximum of Months | 0.103819E+11 | 0.60 | 5003.99 | 0.64 |
Report: FanReportMonthly
For: ROOM_5_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163080E+10 | 0.56 | 822.50 | 01-JAN-00:05 | 0.63 |
February | 0.148272E+10 | 0.58 | 822.50 | 01-FEB-00:05 | 0.63 |
March | 0.166186E+10 | 0.60 | 822.50 | 01-MAR-00:10 | 0.63 |
April | 0.164831E+10 | 0.64 | 822.50 | 01-APR-00:10 | 0.63 |
May | 0.171017E+10 | 0.64 | 822.50 | 01-MAY-00:10 | 0.64 |
June | 0.170584E+10 | 0.64 | 822.50 | 01-JUN-00:10 | 0.63 |
July | 0.179036E+10 | 0.64 | 822.50 | 01-JUL-00:10 | 0.63 |
August | 0.178429E+10 | 0.64 | 822.50 | 01-AUG-00:10 | 0.63 |
September | 0.169399E+10 | 0.64 | 822.50 | 01-SEP-00:10 | 0.63 |
October | 0.170274E+10 | 0.62 | 822.50 | 01-OCT-00:10 | 0.63 |
November | 0.159645E+10 | 0.59 | 822.50 | 01-NOV-00:10 | 0.63 |
December | 0.162337E+10 | 0.57 | 822.50 | 01-DEC-00:10 | 0.63 |
Annual Sum or Average | 0.200309E+11 | 0.61 | |||
Minimum of Months | 0.148272E+10 | 0.56 | 822.50 | 0.63 | |
Maximum of Months | 0.179036E+10 | 0.64 | 822.50 | 0.64 |
Report: FanReportMonthly
For: ROOM_6_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157597E+10 | 0.46 | 814.49 | 01-JAN-00:05 | 0.63 |
February | 0.142812E+10 | 0.50 | 814.49 | 01-FEB-01:50 | 0.64 |
March | 0.160516E+10 | 0.58 | 814.49 | 01-MAR-00:40 | 0.63 |
April | 0.160578E+10 | 0.63 | 814.49 | 01-APR-00:40 | 0.63 |
May | 0.168142E+10 | 0.62 | 814.49 | 01-MAY-00:20 | 0.64 |
June | 0.167667E+10 | 0.62 | 814.49 | 01-JUN-01:10 | 0.63 |
July | 0.175407E+10 | 0.61 | 814.49 | 01-JUL-01:30 | 0.63 |
August | 0.173368E+10 | 0.61 | 814.49 | 01-AUG-00:40 | 0.63 |
September | 0.163279E+10 | 0.61 | 814.49 | 01-SEP-00:30 | 0.63 |
October | 0.162856E+10 | 0.59 | 814.49 | 01-OCT-00:10 | 0.63 |
November | 0.153076E+10 | 0.50 | 814.49 | 01-NOV-00:10 | 0.63 |
December | 0.157579E+10 | 0.46 | 814.49 | 01-DEC-00:10 | 0.63 |
Annual Sum or Average | 0.194288E+11 | 0.57 | |||
Minimum of Months | 0.142812E+10 | 0.46 | 814.49 | 0.63 | |
Maximum of Months | 0.175407E+10 | 0.63 | 814.49 | 0.64 |
Report: FanReportMonthly
For: ROOM_1_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.516424E+09 | 0.54 | 260.59 | 01-JAN-00:05 | 0.63 |
February | 0.469171E+09 | 0.55 | 260.59 | 01-FEB-00:05 | 0.63 |
March | 0.521189E+09 | 0.57 | 260.59 | 01-MAR-00:20 | 0.63 |
April | 0.513696E+09 | 0.60 | 260.59 | 01-APR-00:10 | 0.63 |
May | 0.533837E+09 | 0.60 | 260.59 | 01-MAY-00:20 | 0.64 |
June | 0.531946E+09 | 0.62 | 260.59 | 01-JUN-00:10 | 0.63 |
July | 0.556799E+09 | 0.63 | 260.59 | 01-JUL-00:10 | 0.63 |
August | 0.555928E+09 | 0.63 | 260.59 | 01-AUG-00:10 | 0.63 |
September | 0.530715E+09 | 0.61 | 260.59 | 01-SEP-00:10 | 0.63 |
October | 0.534287E+09 | 0.59 | 260.59 | 01-OCT-00:20 | 0.63 |
November | 0.502781E+09 | 0.55 | 260.59 | 01-NOV-00:10 | 0.63 |
December | 0.515535E+09 | 0.54 | 260.59 | 01-DEC-00:20 | 0.63 |
Annual Sum or Average | 0.628231E+10 | 0.59 | |||
Minimum of Months | 0.469171E+09 | 0.54 | 260.59 | 0.63 | |
Maximum of Months | 0.556799E+09 | 0.63 | 260.59 | 0.64 |
Report: FanReportMonthly
For: ROOM_2_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.504898E+09 | 0.52 | 257.55 | 01-JAN-00:15 | 0.63 |
February | 0.455862E+09 | 0.51 | 257.55 | 01-FEB-00:05 | 0.63 |
March | 0.505705E+09 | 0.52 | 257.55 | 01-MAR-00:10 | 0.63 |
April | 0.499250E+09 | 0.57 | 257.55 | 01-APR-00:10 | 0.63 |
May | 0.525404E+09 | 0.59 | 257.55 | 01-MAY-00:10 | 0.64 |
June | 0.526132E+09 | 0.61 | 257.55 | 01-JUN-00:10 | 0.63 |
July | 0.549844E+09 | 0.61 | 257.55 | 01-JUL-00:10 | 0.63 |
August | 0.545552E+09 | 0.61 | 257.55 | 01-AUG-00:10 | 0.63 |
September | 0.514975E+09 | 0.60 | 257.55 | 01-SEP-00:10 | 0.63 |
October | 0.513630E+09 | 0.55 | 257.55 | 01-OCT-00:10 | 0.63 |
November | 0.486237E+09 | 0.51 | 257.55 | 01-NOV-00:10 | 0.63 |
December | 0.505553E+09 | 0.52 | 257.55 | 01-DEC-00:10 | 0.63 |
Annual Sum or Average | 0.613304E+10 | 0.56 | |||
Minimum of Months | 0.455862E+09 | 0.51 | 257.55 | 0.63 | |
Maximum of Months | 0.549844E+09 | 0.61 | 257.55 | 0.64 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.226997E+10 | 0.57 | 1090.54 | 01-JAN-00:05 | 0.63 |
February | 0.205864E+10 | 0.58 | 1090.54 | 01-FEB-00:05 | 0.63 |
March | 0.224438E+10 | 0.58 | 1090.54 | 01-MAR-00:10 | 0.63 |
April | 0.217269E+10 | 0.60 | 1090.54 | 01-APR-00:10 | 0.63 |
May | 0.222789E+10 | 0.60 | 1090.54 | 01-MAY-00:10 | 0.64 |
June | 0.220589E+10 | 0.62 | 1090.54 | 01-JUN-00:10 | 0.63 |
July | 0.233437E+10 | 0.63 | 1090.54 | 01-JUL-00:10 | 0.63 |
August | 0.235836E+10 | 0.62 | 1090.54 | 01-AUG-00:10 | 0.63 |
September | 0.229231E+10 | 0.61 | 1090.54 | 01-SEP-00:10 | 0.63 |
October | 0.234476E+10 | 0.60 | 1090.54 | 01-OCT-00:10 | 0.63 |
November | 0.222237E+10 | 0.60 | 1090.54 | 01-NOV-00:10 | 0.63 |
December | 0.228137E+10 | 0.57 | 1090.54 | 01-DEC-00:10 | 0.63 |
Annual Sum or Average | 0.270130E+11 | 0.60 | |||
Minimum of Months | 0.205864E+10 | 0.57 | 1090.54 | 0.63 | |
Maximum of Months | 0.235836E+10 | 0.63 | 1090.54 | 0.64 |
Report: FanReportMonthly
For: PTAC_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.223892E+09 | 0.39 | 417.31 | 01-JAN-13:00 | 0.71 |
February | 0.277592E+09 | 0.48 | 511.42 | 14-FEB-16:10 | 0.70 |
March | 0.450514E+09 | 0.64 | 479.53 | 08-MAR-14:00 | 0.70 |
April | 0.650785E+09 | 0.72 | 530.27 | 11-APR-18:15 | 0.70 |
May | 0.808786E+09 | 0.72 | 666.68 | 19-MAY-18:15 | 0.69 |
June | 0.110257E+10 | 0.71 | 864.55 | 23-JUN-18:03 | 0.67 |
July | 0.135043E+10 | 0.70 | 933.84 | 21-JUL-18:13 | 0.67 |
August | 0.130964E+10 | 0.70 | 793.41 | 20-AUG-18:03 | 0.68 |
September | 0.107216E+10 | 0.71 | 732.25 | 03-SEP-13:30 | 0.68 |
October | 0.765055E+09 | 0.68 | 656.50 | 06-OCT-15:10 | 0.69 |
November | 0.410683E+09 | 0.63 | 482.40 | 02-NOV-15:10 | 0.70 |
December | 0.206311E+09 | 0.39 | 393.17 | 30-DEC-13:40 | 0.71 |
Annual Sum or Average | 0.862843E+10 | 0.62 | |||
Minimum of Months | 0.206311E+09 | 0.39 | 393.17 | 0.67 | |
Maximum of Months | 0.135043E+10 | 0.72 | 933.84 | 0.71 |
Report: FanReportMonthly
For: PTAC_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131904E+09 | 0.22 | 362.08 | 21-JAN-07:10 | 0.63 |
February | 94280228.20 | 0.19 | 314.01 | 06-FEB-07:10 | 0.63 |
March | 0.122317E+09 | 0.29 | 322.01 | 08-MAR-13:30 | 0.70 |
April | 0.284785E+09 | 0.53 | 387.03 | 13-APR-14:10 | 0.69 |
May | 0.414505E+09 | 0.65 | 434.20 | 30-MAY-14:30 | 0.69 |
June | 0.629524E+09 | 0.70 | 620.45 | 28-JUN-15:10 | 0.66 |
July | 0.784342E+09 | 0.70 | 594.20 | 20-JUL-14:10 | 0.66 |
August | 0.740244E+09 | 0.70 | 572.81 | 20-AUG-14:00 | 0.67 |
September | 0.549202E+09 | 0.71 | 554.27 | 03-SEP-13:30 | 0.67 |
October | 0.316146E+09 | 0.51 | 478.00 | 01-OCT-13:30 | 0.68 |
November | 83302622.53 | 0.23 | 302.93 | 02-NOV-13:10 | 0.70 |
December | 0.128915E+09 | 0.21 | 344.14 | 09-DEC-07:30 | 0.63 |
Annual Sum or Average | 0.427947E+10 | 0.47 | |||
Minimum of Months | 83302622.53 | 0.19 | 302.93 | 0.63 | |
Maximum of Months | 0.784342E+09 | 0.71 | 620.45 | 0.70 |
Report: FanReportMonthly
For: PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.201798E+11 | 1.61 | 7534.29 | 15-JAN-13:50 | 1.61 |
February | 0.182269E+11 | 1.61 | 7534.29 | 01-FEB-11:25 | 1.61 |
March | 0.201798E+11 | 1.61 | 7534.29 | 10-MAR-10:54 | 1.61 |
April | 0.195289E+11 | 1.61 | 7534.29 | 01-APR-00:50 | 1.61 |
May | 0.201798E+11 | 1.60 | 7534.29 | 13-MAY-22:20 | 1.61 |
June | 0.195289E+11 | 1.60 | 7534.29 | 02-JUN-07:03 | 1.60 |
July | 0.201798E+11 | 1.59 | 7534.29 | 01-JUL-01:20 | 1.57 |
August | 0.201798E+11 | 1.59 | 7534.29 | 01-AUG-01:30 | 1.59 |
September | 0.195289E+11 | 1.59 | 7534.29 | 22-SEP-06:30 | 1.60 |
October | 0.201798E+11 | 1.60 | 7534.29 | 12-OCT-06:53 | 1.61 |
November | 0.195289E+11 | 1.61 | 7534.29 | 01-NOV-03:20 | 1.60 |
December | 0.201798E+11 | 1.61 | 7534.29 | 03-DEC-16:00 | 1.61 |
Annual Sum or Average | 0.237601E+12 | 1.60 | |||
Minimum of Months | 0.182269E+11 | 1.59 | 7534.29 | 1.57 | |
Maximum of Months | 0.201798E+11 | 1.61 | 7534.29 | 1.61 |
Report: FanReportMonthly
For: PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.101409E+11 | 1.62 | 3786.20 | 01-JAN-14:30 | 1.62 |
February | 0.915956E+10 | 1.62 | 3786.20 | 03-FEB-18:40 | 1.62 |
March | 0.101409E+11 | 1.62 | 3786.20 | 01-MAR-03:40 | 1.62 |
April | 0.981382E+10 | 1.62 | 3786.20 | 12-APR-19:20 | 1.62 |
May | 0.101409E+11 | 1.61 | 3786.20 | 02-MAY-13:00 | 1.62 |
June | 0.981382E+10 | 1.61 | 3786.20 | 11-JUN-21:37 | 1.61 |
July | 0.101409E+11 | 1.60 | 3786.20 | 03-JUL-15:10 | 1.61 |
August | 0.101409E+11 | 1.60 | 3786.20 | 01-AUG-05:10 | 1.60 |
September | 0.981382E+10 | 1.60 | 3786.20 | 01-SEP-15:12 | 1.60 |
October | 0.101409E+11 | 1.61 | 3786.20 | 01-OCT-11:10 | 1.61 |
November | 0.981382E+10 | 1.62 | 3786.20 | 04-NOV-23:40 | 1.61 |
December | 0.101409E+11 | 1.62 | 3786.20 | 01-DEC-06:30 | 1.62 |
Annual Sum or Average | 0.119401E+12 | 1.61 | |||
Minimum of Months | 0.915956E+10 | 1.60 | 3786.20 | 1.60 | |
Maximum of Months | 0.101409E+11 | 1.62 | 3786.20 | 1.62 |
Report: FanReportMonthly
For: PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140440E+11 | 1.62 | 5243.44 | 23-JAN-16:00 | 1.62 |
February | 0.126849E+11 | 1.62 | 5243.44 | 12-FEB-16:13 | 1.62 |
March | 0.140440E+11 | 1.62 | 5243.44 | 08-MAR-16:50 | 1.62 |
April | 0.135910E+11 | 1.62 | 5243.44 | 01-APR-20:50 | 1.63 |
May | 0.140440E+11 | 1.61 | 5243.44 | 02-MAY-10:15 | 1.62 |
June | 0.135910E+11 | 1.61 | 5243.44 | 02-JUN-15:21 | 1.61 |
July | 0.140440E+11 | 1.60 | 5243.44 | 01-JUL-02:30 | 1.59 |
August | 0.140440E+11 | 1.60 | 5243.44 | 01-AUG-01:40 | 1.61 |
September | 0.135910E+11 | 1.60 | 5243.44 | 01-SEP-19:02 | 1.61 |
October | 0.140440E+11 | 1.61 | 5243.44 | 01-OCT-16:20 | 1.60 |
November | 0.135910E+11 | 1.62 | 5243.44 | 09-NOV-10:50 | 1.61 |
December | 0.140440E+11 | 1.62 | 5243.44 | 01-DEC-00:10 | 1.61 |
Annual Sum or Average | 0.165357E+12 | 1.61 | |||
Minimum of Months | 0.126849E+11 | 1.60 | 5243.44 | 1.59 | |
Maximum of Months | 0.140440E+11 | 1.62 | 5243.44 | 1.63 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.701724E+09 | 0.631552E+09 | 954.07 | 17-JAN-09:02 | 858.66 | 858.66 | 45.13 | 1.44 |
February | 0.505052E+09 | 0.454547E+09 | 775.28 | 16-FEB-16:12 | 697.76 | 697.76 | 37.44 | 1.05 |
March | 0.242290E+09 | 0.218061E+09 | 494.51 | 10-MAR-09:03 | 445.06 | 445.06 | 32.87 | 0.59 |
April | 68274503.39 | 61447053.05 | 453.77 | 06-APR-08:03 | 408.39 | 408.39 | 32.20 | 0.53 |
May | 13447102.06 | 12102391.85 | 232.14 | 25-MAY-08:05 | 208.93 | 208.93 | 26.15 | 0.25 |
June | 739541.46 | 665587.32 | 170.42 | 09-JUN-08:05 | 153.38 | 153.38 | 24.46 | 0.18 |
July | 28392.11 | 25552.90 | 22.25 | 27-JUL-21:54 | 20.03 | 20.03 | 26.30 | 0.02 |
August | 37865.27 | 34078.74 | 28.71 | 23-AUG-21:54 | 25.84 | 25.84 | 27.24 | 0.03 |
September | 197098.07 | 177388.26 | 156.42 | 08-SEP-08:05 | 140.78 | 140.78 | 27.62 | 0.17 |
October | 0.103813E+09 | 93431683.46 | 678.32 | 25-OCT-08:62 | 610.49 | 610.49 | 38.21 | 0.87 |
November | 0.302778E+09 | 0.272500E+09 | 535.83 | 27-NOV-06:00 | 482.25 | 482.25 | 38.67 | 0.65 |
December | 0.727662E+09 | 0.654895E+09 | 1085.96 | 21-DEC-16:12 | 977.37 | 977.37 | 43.13 | 1.84 |
Annual Sum or Average | 0.266604E+10 | 0.239944E+10 | ||||||
Minimum of Months | 28392.11 | 25552.90 | 22.25 | 20.03 | 20.03 | 24.46 | 0.02 | |
Maximum of Months | 0.727662E+09 | 0.654895E+09 | 1085.96 | 977.37 | 977.37 | 45.13 | 1.84 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.84 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 49.73 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 50.06 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.81 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 53.26 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.76 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.15 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.34 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.27 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.23 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 53.49 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 50.74 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.84 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.34 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 30.89 | 73.27 | 50986.24 | 200342.26 | 20-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 35.96 | 78.80 | 40765.73 | 159886.84 | 16-FEB-16:12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 29.26 | 73.10 | 17254.97 | 103494.57 | 05-MAR-06:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.01 | 68.59 | 4862.56 | 87524.73 | 06-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.67 | 26.67 | 920.55 | 41721.47 | 25-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 27.01 | 27.01 | 51.19 | 31349.71 | 09-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.24 | 25.24 | 1.79 | 3745.53 | 27-JUL-21:54 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 26.65 | 26.65 | 2.32 | 4725.13 | 23-AUG-21:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.35 | 27.35 | 12.48 | 26434.47 | 08-SEP-08:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.27 | 28.27 | 7297.72 | 135705.72 | 25-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 28.71 | 28.71 | 22164.47 | 111844.37 | 27-NOV-06:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25.63 | 70.45 | 52490.50 | 257806.21 | 21-DEC-16:12 |
Annual Sum or Average | 0.00 | 16306.13 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.24 | 25.24 | 1.79 | 3745.53 | ||
Maximum of Months | 0.00 | 0.00 | 35.96 | 78.80 | 52490.50 | 257806.21 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.84 | 60.05 | 26472.64 | 55812.91 | 31-JAN-07:54 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49.73 | 60.05 | 26677.67 | 55856.50 | 07-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 50.06 | 60.05 | 26050.08 | 55333.24 | 01-MAR-07:57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.81 | 60.05 | 24675.70 | 52887.66 | 03-APR-06:54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 53.26 | 60.05 | 22968.82 | 49773.55 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.76 | 60.05 | 21377.17 | 46109.60 | 01-JUN-06:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.15 | 60.05 | 20302.37 | 43131.18 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.34 | 60.05 | 20097.06 | 42367.18 | 31-AUG-06:42 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.27 | 60.05 | 20756.19 | 44452.39 | 29-SEP-06:45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.23 | 60.05 | 22125.59 | 47965.44 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.49 | 60.05 | 23838.55 | 51512.80 | 30-NOV-07:57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 50.74 | 60.05 | 25424.49 | 54288.33 | 29-DEC-07:57 |
Annual Sum or Average | 0.00 | 23378.29 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.84 | 60.05 | 20097.06 | 42367.18 | ||
Maximum of Months | 0.00 | 0.00 | 54.34 | 60.05 | 26677.67 | 55856.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.456636E+11 | 0.00 | 0.00 | 0.109743E+11 | 0.00 | 0.00 |
February | 0.331012E+11 | 0.00 | 0.00 | 0.104610E+11 | 0.00 | 0.00 |
March | 0.160212E+11 | 0.00 | 0.00 | 0.130844E+11 | 0.00 | 0.00 |
April | 0.427122E+10 | 0.00 | 0.00 | 0.191232E+11 | 0.00 | 0.00 |
May | 0.747019E+09 | 0.00 | 0.00 | 0.272399E+11 | 0.00 | 0.00 |
June | 27160629.42 | 0.00 | 0.00 | 0.417678E+11 | 0.00 | 0.00 |
July | 1171987.39 | 0.00 | 0.00 | 0.551879E+11 | 0.00 | 0.00 |
August | 748630.08 | 0.00 | 0.00 | 0.512653E+11 | 0.00 | 0.00 |
September | 153893.54 | 0.00 | 0.00 | 0.371715E+11 | 0.00 | 0.00 |
October | 0.642971E+10 | 0.00 | 0.00 | 0.226820E+11 | 0.00 | 0.00 |
November | 0.186129E+11 | 0.00 | 0.00 | 0.114606E+11 | 0.00 | 0.00 |
December | 0.461893E+11 | 0.00 | 0.00 | 0.108674E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.171065E+12 | 0.00 | 0.00 | 0.311285E+12 | 0.00 | 0.00 |
Minimum of Months | 153893.54 | 0.00 | 0.00 | 0.104610E+11 | 0.00 | 0.00 |
Maximum of Months | 0.461893E+11 | 0.00 | 0.00 | 0.551879E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.573681E+11 | 0.00 | 0.00 | 0.110356E+11 | 0.00 | 0.00 |
February | 0.422982E+11 | 0.00 | 0.00 | 0.105170E+11 | 0.00 | 0.00 |
March | 0.218719E+11 | 0.00 | 0.00 | 0.136101E+11 | 0.00 | 0.00 |
April | 0.698536E+10 | 0.00 | 0.00 | 0.202206E+11 | 0.00 | 0.00 |
May | 0.140828E+10 | 0.00 | 0.00 | 0.291475E+11 | 0.00 | 0.00 |
June | 70092432.21 | 0.00 | 0.00 | 0.436940E+11 | 0.00 | 0.00 |
July | 776406.97 | 0.00 | 0.00 | 0.545275E+11 | 0.00 | 0.00 |
August | 330348.50 | 0.00 | 0.00 | 0.490429E+11 | 0.00 | 0.00 |
September | 3647.07 | 0.00 | 0.00 | 0.341279E+11 | 0.00 | 0.00 |
October | 0.988502E+10 | 0.00 | 0.00 | 0.204671E+11 | 0.00 | 0.00 |
November | 0.279407E+11 | 0.00 | 0.00 | 0.113060E+11 | 0.00 | 0.00 |
December | 0.600651E+11 | 0.00 | 0.00 | 0.109193E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.227894E+12 | 0.00 | 0.00 | 0.308616E+12 | 0.00 | 0.00 |
Minimum of Months | 3647.07 | 0.00 | 0.00 | 0.105170E+11 | 0.00 | 0.00 |
Maximum of Months | 0.600651E+11 | 0.00 | 0.00 | 0.545275E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.297994E+09 | 0.00 | 0.00 | 0.670775E+10 | 0.00 | 0.00 |
February | 0.907200E+09 | 0.00 | 0.00 | 0.605897E+10 | 0.00 | 0.00 |
March | 51549265.21 | 0.00 | 0.00 | 0.670775E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.767557E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.102699E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.156000E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.224062E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.218205E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.175357E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.118303E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.714676E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.673196E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125674E+10 | 0.00 | 0.00 | 0.140491E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.605897E+10 | 0.00 | 0.00 |
Maximum of Months | 0.907200E+09 | 0.00 | 0.00 | 0.224062E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.201799E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.182974E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.204447E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.226721E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.268301E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.317191E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.371304E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.351080E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.286734E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.233274E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.195295E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.201799E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.304092E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.182974E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.371304E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.101412E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.928002E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.103849E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.112223E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.132132E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.167808E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.203697E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.189939E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.150202E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.121636E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.981662E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.101410E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.157527E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.928002E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.203697E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.140485E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.129414E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.150969E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.179598E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.226004E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.291010E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.358520E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.331830E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.256988E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.187421E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.136613E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.140440E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.252929E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.129414E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.358520E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109035E+11 | 0.214940E+09 | 0.456636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.997637E+10 | 0.160687E+10 | 0.331012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113507E+11 | 0.560001E+10 | 0.160212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120184E+11 | 0.245166E+11 | 0.427122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131577E+11 | 0.500120E+11 | 0.747019E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148966E+11 | 0.964554E+11 | 27160629.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165909E+11 | 0.141715E+12 | 1171987.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167845E+11 | 0.126806E+12 | 748630.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151428E+11 | 0.798687E+11 | 153893.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137654E+11 | 0.314821E+11 | 0.642971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112230E+11 | 0.733623E+09 | 0.186129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108674E+11 | 0.00 | 0.461893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156677E+12 | 0.559012E+12 | 0.171065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.997637E+10 | 0.00 | 153893.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167845E+11 | 0.141715E+12 | 0.461893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109744E+11 | 0.185591E+09 | 0.573681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101366E+11 | 0.124337E+10 | 0.422982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120231E+11 | 0.514900E+10 | 0.218719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133347E+11 | 0.242403E+11 | 0.698536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152561E+11 | 0.504216E+11 | 0.140828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171481E+11 | 0.963152E+11 | 70092432.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.184296E+11 | 0.133194E+12 | 776406.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177727E+11 | 0.115544E+12 | 330348.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151025E+11 | 0.690027E+11 | 3647.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131812E+11 | 0.255052E+11 | 0.988502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110971E+11 | 0.646450E+09 | 0.279407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109193E+11 | 0.00 | 0.600651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165375E+12 | 0.521447E+12 | 0.227894E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101366E+11 | 0.00 | 3647.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184296E+11 | 0.133194E+12 | 0.600651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.670775E+10 | 0.00 | 0.297994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.605861E+10 | 1084031.41 | 0.907200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.670775E+10 | 206.03 | 51549265.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.649137E+10 | 0.389870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.670775E+10 | 0.117679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.650361E+10 | 0.295978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.684576E+10 | 0.535509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.685665E+10 | 0.527526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.652078E+10 | 0.395294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.672118E+10 | 0.181832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.649137E+10 | 0.214290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670775E+10 | 76836722.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793203E+11 | 0.211501E+12 | 0.125674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.605861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.685665E+10 | 0.535509E+11 | 0.907200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.201798E+11 | 90600.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182269E+11 | 0.261973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201798E+11 | 0.977839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195289E+11 | 0.125110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201798E+11 | 0.262918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195289E+11 | 0.455896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201798E+11 | 0.643259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201798E+11 | 0.576843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195289E+11 | 0.359791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201798E+11 | 0.123942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195289E+11 | 2144362.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201798E+11 | 70250.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237601E+12 | 0.256018E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.182269E+11 | 70250.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201798E+11 | 0.643259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.101409E+11 | 845595.07 | 0.758964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.915956E+10 | 0.464430E+09 | 0.480264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101409E+11 | 0.905433E+09 | 0.149866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.981382E+10 | 0.533413E+10 | 0.137892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101409E+11 | 0.114475E+11 | 415107.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.981382E+10 | 0.250145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101409E+11 | 0.378530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101409E+11 | 0.333915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.981382E+10 | 0.200640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101409E+11 | 0.787464E+10 | 0.669284E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.981382E+10 | 9654886.05 | 0.138019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101409E+11 | 25968.41 | 0.675194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119401E+12 | 0.142360E+12 | 0.228307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.915956E+10 | 25968.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101409E+11 | 0.378530E+11 | 0.758964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140440E+11 | 15304085.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126849E+11 | 0.991441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140440E+11 | 0.401693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135910E+11 | 0.176546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140440E+11 | 0.343969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135910E+11 | 0.585737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140440E+11 | 0.828596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140440E+11 | 0.743055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135910E+11 | 0.485413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140440E+11 | 0.188848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135910E+11 | 0.252113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140440E+11 | 43854.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165357E+12 | 0.340492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126849E+11 | 43854.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140440E+11 | 0.828596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109035E+11 | 0.456636E+11 | 0.00 | 0.00 | 70882107.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.997637E+10 | 0.331012E+11 | 0.00 | 0.00 | 0.484612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113507E+11 | 0.160212E+11 | 0.00 | 0.00 | 0.173365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120184E+11 | 0.427122E+10 | 0.00 | 0.00 | 0.710474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131577E+11 | 0.747019E+09 | 0.00 | 0.00 | 0.140822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148966E+11 | 27160629.42 | 0.00 | 0.00 | 0.268712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165909E+11 | 1171987.39 | 0.00 | 0.00 | 0.385970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167845E+11 | 748630.08 | 0.00 | 0.00 | 0.344808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151428E+11 | 153893.54 | 0.00 | 0.00 | 0.220287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137654E+11 | 0.642971E+10 | 0.00 | 0.00 | 0.891651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112230E+11 | 0.186129E+11 | 0.00 | 0.00 | 0.237558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108674E+11 | 0.461893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156677E+12 | 0.171065E+12 | 0.00 | 0.00 | 0.154608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.997637E+10 | 153893.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167845E+11 | 0.461893E+11 | 0.00 | 0.00 | 0.385970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109744E+11 | 0.573681E+11 | 0.00 | 0.00 | 61205653.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101366E+11 | 0.422982E+11 | 0.00 | 0.00 | 0.380461E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120231E+11 | 0.218719E+11 | 0.00 | 0.00 | 0.158707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133347E+11 | 0.698536E+10 | 0.00 | 0.00 | 0.688587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152561E+11 | 0.140828E+10 | 0.00 | 0.00 | 0.138914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171481E+11 | 70092432.21 | 0.00 | 0.00 | 0.265459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.184296E+11 | 776406.97 | 0.00 | 0.00 | 0.360980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.177727E+11 | 330348.50 | 0.00 | 0.00 | 0.312702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151025E+11 | 3647.07 | 0.00 | 0.00 | 0.190254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131812E+11 | 0.988502E+10 | 0.00 | 0.00 | 0.728593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110971E+11 | 0.279407E+11 | 0.00 | 0.00 | 0.208942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109193E+11 | 0.600651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165375E+12 | 0.227894E+12 | 0.00 | 0.00 | 0.143240E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101366E+11 | 3647.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.184296E+11 | 0.600651E+11 | 0.00 | 0.00 | 0.360980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.670775E+10 | 0.297994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.605861E+10 | 0.907200E+09 | 0.00 | 0.00 | 356393.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.670775E+10 | 51549265.21 | 0.00 | 0.00 | 67.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.649137E+10 | 0.00 | 0.00 | 0.00 | 0.118421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.670775E+10 | 0.00 | 0.00 | 0.00 | 0.356214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.650361E+10 | 0.00 | 0.00 | 0.00 | 0.909639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.684576E+10 | 0.00 | 0.00 | 0.00 | 0.155604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.685665E+10 | 0.00 | 0.00 | 0.00 | 0.149638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.652078E+10 | 0.00 | 0.00 | 0.00 | 0.110150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.672118E+10 | 0.00 | 0.00 | 0.00 | 0.510915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.649137E+10 | 0.00 | 0.00 | 0.00 | 0.655396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670775E+10 | 0.00 | 0.00 | 0.00 | 24208319.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.793203E+11 | 0.125674E+10 | 0.00 | 0.00 | 0.611710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.605861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.685665E+10 | 0.907200E+09 | 0.00 | 0.00 | 0.155604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.201798E+11 | 0.00 | 0.00 | 0.00 | 26266.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182269E+11 | 0.00 | 0.00 | 0.00 | 70427983.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201798E+11 | 0.00 | 0.00 | 0.00 | 0.264871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195289E+11 | 0.00 | 0.00 | 0.00 | 0.314324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201798E+11 | 0.00 | 0.00 | 0.00 | 0.665029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195289E+11 | 0.00 | 0.00 | 0.00 | 0.121902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201798E+11 | 0.00 | 0.00 | 0.00 | 0.169506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201798E+11 | 0.00 | 0.00 | 0.00 | 0.149282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195289E+11 | 0.00 | 0.00 | 0.00 | 0.914453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201798E+11 | 0.00 | 0.00 | 0.00 | 0.314759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195289E+11 | 0.00 | 0.00 | 0.00 | 618281.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201798E+11 | 0.00 | 0.00 | 0.00 | 20366.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237601E+12 | 0.00 | 0.00 | 0.00 | 0.664905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.182269E+11 | 0.00 | 0.00 | 0.00 | 20366.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201798E+11 | 0.00 | 0.00 | 0.00 | 0.169506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.101409E+11 | 0.00 | 0.00 | 0.00 | 251514.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.915956E+10 | 0.00 | 0.00 | 0.00 | 0.120452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101409E+11 | 0.00 | 0.00 | 0.00 | 0.243973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.981382E+10 | 0.00 | 0.00 | 0.00 | 0.140852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101409E+11 | 0.00 | 0.00 | 0.00 | 0.307224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.981382E+10 | 0.00 | 0.00 | 0.00 | 0.696698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101409E+11 | 0.00 | 0.00 | 0.00 | 0.102287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101409E+11 | 0.00 | 0.00 | 0.00 | 0.885300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.981382E+10 | 0.00 | 0.00 | 0.00 | 0.520641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101409E+11 | 0.00 | 0.00 | 0.00 | 0.202263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.981382E+10 | 0.00 | 0.00 | 0.00 | 2799847.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101409E+11 | 0.00 | 0.00 | 0.00 | 7748.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119401E+12 | 0.00 | 0.00 | 0.00 | 0.381260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.915956E+10 | 0.00 | 0.00 | 0.00 | 7748.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101409E+11 | 0.00 | 0.00 | 0.00 | 0.102287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140440E+11 | 0.00 | 0.00 | 0.00 | 4512114.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126849E+11 | 0.00 | 0.00 | 0.00 | 0.256504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140440E+11 | 0.00 | 0.00 | 0.00 | 0.105292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135910E+11 | 0.00 | 0.00 | 0.00 | 0.436884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140440E+11 | 0.00 | 0.00 | 0.00 | 0.855643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135910E+11 | 0.00 | 0.00 | 0.00 | 0.155100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140440E+11 | 0.00 | 0.00 | 0.00 | 0.218080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140440E+11 | 0.00 | 0.00 | 0.00 | 0.191390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135910E+11 | 0.00 | 0.00 | 0.00 | 0.121078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140440E+11 | 0.00 | 0.00 | 0.00 | 0.469806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135910E+11 | 0.00 | 0.00 | 0.00 | 70345995.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140440E+11 | 0.00 | 0.00 | 0.00 | 13084.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165357E+12 | 0.00 | 0.00 | 0.00 | 0.875724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126849E+11 | 0.00 | 0.00 | 0.00 | 13084.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140440E+11 | 0.00 | 0.00 | 0.00 | 0.218080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.460602E+11 | 0.00 | 0.00 | 4994918.48 | 0.00 | 0.00 | 0.707428E+10 | 0.00 | 0.65 |
February | 0.414016E+11 | 0.00 | 0.00 | 1584108.69 | 0.00 | 0.00 | 0.178950E+10 | 0.00 | 0.65 |
March | 0.350170E+11 | 0.00 | 0.00 | 4269924.11 | 0.00 | 0.00 | 0.465681E+10 | 0.00 | 0.65 |
April | 0.143705E+11 | 9164636.70 | 0.00 | 31066040.08 | 0.00 | 0.00 | 0.184401E+11 | 0.00 | 0.85 |
May | 0.291532E+10 | 0.287616E+09 | 0.00 | 58456725.84 | 0.00 | 0.00 | 0.253330E+11 | 0.00 | 0.98 |
June | 0.00 | 0.354906E+10 | 0.00 | 57367284.28 | 0.00 | 0.00 | 0.175761E+11 | 0.00 | 1.01 |
July | 0.00 | 0.810429E+10 | 0.00 | 30719889.74 | 0.00 | 0.00 | 0.559175E+10 | 0.00 | 1.00 |
August | 0.00 | 0.549119E+10 | 0.00 | 55283016.85 | 0.00 | 0.00 | 0.846618E+10 | 0.00 | 1.07 |
September | 0.00 | 0.152942E+10 | 0.00 | 97722354.56 | 0.00 | 0.00 | 0.211772E+11 | 0.00 | 1.20 |
October | 57898754.54 | 0.219405E+09 | 0.00 | 0.112531E+09 | 0.00 | 0.00 | 0.453611E+11 | 0.00 | 1.16 |
November | 0.306566E+09 | 0.00 | 0.00 | 92860263.47 | 0.00 | 0.00 | 0.567613E+11 | 0.00 | 0.89 |
December | 0.319335E+11 | 0.00 | 0.00 | 24145481.44 | 0.00 | 0.00 | 0.260750E+11 | 0.00 | 0.67 |
Annual Sum or Average | 0.172063E+12 | 0.191902E+11 | 0.00 | 0.571001E+09 | 0.00 | 0.00 | 0.238302E+12 | 0.00 | 0.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1584108.69 | 0.00 | 0.00 | 0.178950E+10 | 0.00 | 0.65 |
Maximum of Months | 0.460602E+11 | 0.810429E+10 | 0.00 | 0.112531E+09 | 0.00 | 0.00 | 0.567613E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.362784E+10 | 0.00 | 0.00 | 4066854.06 | 0.00 | 0.274214E+10 | 0.229650E+10 | 0.00 | 1.96 |
February | 0.327890E+10 | 0.00 | 0.00 | 3965958.56 | 0.00 | 0.188348E+10 | 0.225076E+10 | 0.00 | 2.04 |
March | 0.410643E+10 | 0.00 | 0.00 | 4169081.57 | 0.00 | 0.705906E+09 | 0.203212E+10 | 0.00 | 2.17 |
April | 0.335414E+10 | 200522.40 | 0.00 | 5507852.92 | 0.00 | 27519958.97 | 0.173908E+10 | 0.00 | 2.34 |
May | 0.294709E+10 | 31136421.60 | 0.00 | 4822033.95 | 1191007.28 | 0.00 | 0.100074E+10 | 0.00 | 2.31 |
June | 0.164633E+10 | 0.552876E+09 | 0.00 | 3359578.27 | 119546.40 | 0.00 | 0.671946E+09 | 0.00 | 2.23 |
July | 0.520916E+09 | 0.916338E+09 | 0.00 | 2717683.21 | 4497524.71 | 0.00 | 0.496612E+09 | 0.00 | 2.29 |
August | 0.783805E+09 | 0.609003E+09 | 0.00 | 4408886.47 | 1725025.87 | 0.00 | 0.731972E+09 | 0.00 | 2.51 |
September | 0.174780E+10 | 0.179138E+09 | 0.00 | 7890825.00 | 0.00 | 0.00 | 0.124992E+10 | 0.00 | 2.91 |
October | 0.291881E+10 | 8874485.27 | 0.00 | 9144047.36 | 0.00 | 0.260277E+09 | 0.285126E+10 | 0.00 | 2.90 |
November | 0.411983E+10 | 0.00 | 0.00 | 4999873.12 | 0.00 | 0.550876E+09 | 0.315796E+10 | 0.00 | 2.16 |
December | 0.367219E+10 | 0.00 | 0.00 | 4369796.64 | 0.00 | 0.250758E+10 | 0.273969E+10 | 0.00 | 1.85 |
Annual Sum or Average | 0.327241E+11 | 0.229757E+10 | 0.00 | 59422471.13 | 7533104.26 | 0.867778E+10 | 0.212186E+11 | 0.00 | 2.31 |
Minimum of Months | 0.520916E+09 | 0.00 | 0.00 | 2717683.21 | 0.00 | 0.00 | 0.496612E+09 | 0.00 | 1.85 |
Maximum of Months | 0.411983E+10 | 0.916338E+09 | 0.00 | 9144047.36 | 4497524.71 | 0.274214E+10 | 0.315796E+10 | 0.00 | 2.91 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.514375E+10 | 0.00 | 0.00 | 587190.30 | 0.00 | 0.00 | 0.113985E+10 | 0.00 | 1.11 |
February | 0.408684E+10 | 0.00 | 0.00 | 993322.74 | 0.00 | 0.00 | 0.132257E+10 | 0.00 | 1.16 |
March | 0.343166E+10 | 0.00 | 0.00 | 2178325.68 | 0.00 | 0.00 | 0.182332E+10 | 0.00 | 1.31 |
April | 0.179302E+10 | 90063.74 | 0.00 | 4361251.74 | 0.00 | 0.00 | 0.247759E+10 | 0.00 | 1.57 |
May | 0.884874E+09 | 16939481.24 | 0.00 | 5518411.37 | 1096440.76 | 0.00 | 0.256649E+10 | 0.00 | 1.66 |
June | 0.213696E+09 | 0.297294E+09 | 0.00 | 5514966.88 | 1475009.18 | 0.00 | 0.186556E+10 | 0.00 | 1.55 |
July | 3678899.87 | 0.477453E+09 | 0.00 | 5510453.49 | 4313062.74 | 0.00 | 0.926884E+09 | 0.00 | 1.50 |
August | 19356483.98 | 0.276476E+09 | 0.00 | 6567349.67 | 3046081.21 | 0.00 | 0.136127E+10 | 0.00 | 1.60 |
September | 0.160078E+09 | 63488518.22 | 0.00 | 6874000.61 | 155387.81 | 0.00 | 0.247249E+10 | 0.00 | 1.79 |
October | 0.153181E+10 | 3628819.02 | 0.00 | 5275648.43 | 13100.03 | 0.00 | 0.293015E+10 | 0.00 | 1.60 |
November | 0.323724E+10 | 0.00 | 0.00 | 1708516.30 | 0.00 | 0.00 | 0.217064E+10 | 0.00 | 1.20 |
December | 0.516405E+10 | 0.00 | 0.00 | 551852.92 | 0.00 | 0.00 | 0.117513E+10 | 0.00 | 1.08 |
Annual Sum or Average | 0.256701E+11 | 0.113537E+10 | 0.00 | 45641290.12 | 10099081.72 | 0.00 | 0.222320E+11 | 0.00 | 1.43 |
Minimum of Months | 3678899.87 | 0.00 | 0.00 | 551852.92 | 0.00 | 0.00 | 0.926884E+09 | 0.00 | 1.08 |
Maximum of Months | 0.516405E+10 | 0.477453E+09 | 0.00 | 6874000.61 | 4313062.74 | 0.00 | 0.293015E+10 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.598303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
February | 0.506191E+10 | 0.00 | 0.00 | 29114.36 | 0.00 | 0.00 | 55864781.89 | 0.00 | 0.51 |
March | 0.454855E+10 | 0.00 | 0.00 | 215318.68 | 0.00 | 0.00 | 0.318239E+09 | 0.00 | 0.57 |
April | 0.295570E+10 | 0.00 | 0.00 | 2087084.66 | 86025.55 | 0.00 | 0.980614E+09 | 0.00 | 0.68 |
May | 0.173546E+10 | 16898763.98 | 0.00 | 4878128.25 | 437302.63 | 0.00 | 0.157129E+10 | 0.00 | 0.75 |
June | 0.465981E+09 | 0.333475E+09 | 0.00 | 6383098.01 | 0.00 | 0.00 | 0.159529E+10 | 0.00 | 0.76 |
July | 18773011.37 | 0.539713E+09 | 0.00 | 5880808.86 | 0.00 | 0.00 | 0.907282E+09 | 0.00 | 0.76 |
August | 60699896.00 | 0.298016E+09 | 0.00 | 7209581.40 | 152240.42 | 0.00 | 0.130719E+10 | 0.00 | 0.78 |
September | 0.645479E+09 | 60428386.65 | 0.00 | 6558888.20 | 48808.12 | 0.00 | 0.191470E+10 | 0.00 | 0.82 |
October | 0.284342E+10 | 3129529.76 | 0.00 | 2784083.41 | 25519.62 | 0.00 | 0.127118E+10 | 0.00 | 0.69 |
November | 0.481159E+10 | 0.00 | 0.00 | 154148.72 | 0.00 | 0.00 | 0.239053E+09 | 0.00 | 0.53 |
December | 0.603944E+10 | 0.00 | 0.00 | 609.84 | 0.00 | 0.00 | 7817127.21 | 0.00 | 0.48 |
Annual Sum or Average | 0.351700E+11 | 0.125166E+10 | 0.00 | 36180864.40 | 749896.35 | 0.00 | 0.101685E+11 | 0.00 | 0.65 |
Minimum of Months | 18773011.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.603944E+10 | 0.539713E+09 | 0.00 | 7209581.40 | 437302.63 | 0.00 | 0.191470E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154549E+10 | 0.00 | 0.00 | 0.57 |
February | 0.238109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996845E+09 | 0.00 | 0.00 | 0.59 |
March | 0.307821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131702E+09 | 0.00 | 0.00 | 0.64 |
April | 0.246494E+10 | 0.00 | 0.00 | 22607.71 | 56780.00 | 0.00 | 29512280.56 | 0.00 | 0.73 |
May | 0.186928E+10 | 6588609.43 | 0.00 | 582283.01 | 3788563.93 | 0.00 | 0.132325E+09 | 0.00 | 0.76 |
June | 0.959511E+09 | 0.200705E+09 | 0.00 | 1334127.63 | 2663412.98 | 0.00 | 0.240506E+09 | 0.00 | 0.74 |
July | 0.314428E+09 | 0.319010E+09 | 0.00 | 1538721.64 | 4904464.96 | 0.00 | 0.215756E+09 | 0.00 | 0.72 |
August | 0.522601E+09 | 0.166932E+09 | 0.00 | 1393254.87 | 7071787.47 | 0.00 | 0.248883E+09 | 0.00 | 0.73 |
September | 0.121102E+10 | 28894896.96 | 0.00 | 850074.12 | 5453955.54 | 0.00 | 0.239016E+09 | 0.00 | 0.77 |
October | 0.249105E+10 | 1173046.90 | 0.00 | 77553.64 | 641760.19 | 28195349.35 | 60296812.82 | 0.00 | 0.72 |
November | 0.322293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105360E+09 | 0.00 | 0.00 | 0.60 |
December | 0.252441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146700E+10 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.234430E+11 | 0.723303E+09 | 0.00 | 5798622.61 | 24580725.07 | 0.427460E+10 | 0.116629E+10 | 0.00 | 0.68 |
Minimum of Months | 0.314428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.322293E+10 | 0.319010E+09 | 0.00 | 1538721.64 | 7071787.47 | 0.154549E+10 | 0.248883E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.108366E+09 | 0.00 | 0.00 | 0.685341E+11 | 0.00 | 15.06 |
February | 0.00 | 0.00 | 0.00 | 98521752.41 | 0.00 | 0.00 | 0.620789E+11 | 0.00 | 17.28 |
March | 0.00 | 0.00 | 0.00 | 0.118287E+09 | 0.00 | 0.00 | 0.693367E+11 | 0.00 | 24.02 |
April | 0.00 | 802830.41 | 0.00 | 0.119680E+09 | 0.00 | 0.00 | 0.568483E+11 | 0.00 | 30.68 |
May | 0.00 | 4921002.32 | 0.00 | 0.124263E+09 | 0.00 | 0.00 | 0.461796E+11 | 0.00 | 31.12 |
June | 0.00 | 82891154.70 | 0.00 | 85208151.78 | 0.00 | 0.00 | 0.259414E+11 | 0.00 | 24.53 |
July | 0.00 | 0.212748E+10 | 0.00 | 40390811.30 | 0.00 | 0.00 | 0.119381E+11 | 0.00 | 23.68 |
August | 0.00 | 0.139056E+10 | 0.00 | 65866074.77 | 0.00 | 0.00 | 0.178327E+11 | 0.00 | 27.16 |
September | 0.00 | 0.202262E+09 | 0.00 | 0.110286E+09 | 0.00 | 0.00 | 0.349771E+11 | 0.00 | 32.37 |
October | 0.00 | 15919187.88 | 0.00 | 0.122423E+09 | 0.00 | 0.00 | 0.591312E+11 | 0.00 | 30.18 |
November | 0.00 | 0.00 | 0.00 | 0.106974E+09 | 0.00 | 0.00 | 0.676716E+11 | 0.00 | 19.42 |
December | 0.00 | 0.00 | 0.00 | 0.108711E+09 | 0.00 | 0.00 | 0.684335E+11 | 0.00 | 14.22 |
Annual Sum or Average | 0.00 | 0.382484E+10 | 0.00 | 0.120898E+10 | 0.00 | 0.00 | 0.588903E+12 | 0.00 | 24.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 40390811.30 | 0.00 | 0.00 | 0.119381E+11 | 0.00 | 14.22 |
Maximum of Months | 0.00 | 0.212748E+10 | 0.00 | 0.124263E+09 | 0.00 | 0.00 | 0.693367E+11 | 0.00 | 32.37 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.330190E+11 | 0.00 | 0.00 | 16000400.93 | 0.00 | 0.00 | 0.135585E+11 | 0.00 | 3.79 |
February | 0.246316E+11 | 0.00 | 0.00 | 17799216.26 | 0.00 | 0.00 | 0.156502E+11 | 0.00 | 3.97 |
March | 0.151691E+11 | 0.00 | 0.00 | 27485685.81 | 0.00 | 0.00 | 0.250630E+11 | 0.00 | 4.66 |
April | 0.511155E+10 | 219489.91 | 0.00 | 40839643.62 | 0.00 | 0.00 | 0.292237E+11 | 0.00 | 6.02 |
May | 0.101284E+10 | 90122167.31 | 0.00 | 48734368.11 | 0.00 | 0.00 | 0.284629E+11 | 0.00 | 6.40 |
June | 45369334.10 | 0.207529E+10 | 0.00 | 40511662.48 | 0.00 | 0.00 | 0.194798E+11 | 0.00 | 6.28 |
July | 0.00 | 0.398214E+10 | 0.00 | 32435036.22 | 0.00 | 0.00 | 0.125900E+11 | 0.00 | 6.76 |
August | 0.00 | 0.257570E+10 | 0.00 | 40532319.55 | 0.00 | 0.00 | 0.165997E+11 | 0.00 | 7.15 |
September | 0.00 | 0.550480E+09 | 0.00 | 54597087.11 | 0.00 | 0.00 | 0.257577E+11 | 0.00 | 7.36 |
October | 0.585613E+10 | 41438095.19 | 0.00 | 50305421.19 | 0.00 | 0.00 | 0.316673E+11 | 0.00 | 6.30 |
November | 0.147562E+11 | 0.00 | 0.00 | 27013555.02 | 0.00 | 0.00 | 0.268851E+11 | 0.00 | 4.09 |
December | 0.321647E+11 | 0.00 | 0.00 | 15001496.69 | 0.00 | 0.00 | 0.141512E+11 | 0.00 | 3.52 |
Annual Sum or Average | 0.131766E+12 | 0.931539E+10 | 0.00 | 0.411256E+09 | 0.00 | 0.00 | 0.259089E+12 | 0.00 | 5.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 15001496.69 | 0.00 | 0.00 | 0.125900E+11 | 0.00 | 3.52 |
Maximum of Months | 0.330190E+11 | 0.398214E+10 | 0.00 | 54597087.11 | 0.00 | 0.00 | 0.316673E+11 | 0.00 | 7.36 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.637812E+11 | 0.00 | 0.00 | 38141590.88 | 0.00 | 0.00 | 0.670625E+11 | 0.00 | 1.38 |
February | 0.504654E+11 | 0.00 | 0.00 | 42448266.95 | 0.00 | 0.00 | 0.619543E+11 | 0.00 | 1.43 |
March | 0.287467E+11 | 0.00 | 0.00 | 74160624.89 | 0.00 | 0.00 | 0.803423E+11 | 0.00 | 1.61 |
April | 0.108854E+11 | 1860103.96 | 0.00 | 0.116644E+09 | 0.00 | 0.00 | 0.774209E+11 | 0.00 | 1.92 |
May | 0.619736E+10 | 0.356271E+09 | 0.00 | 0.141951E+09 | 3638435.26 | 0.00 | 0.663447E+11 | 0.00 | 2.03 |
June | 0.144260E+10 | 0.570387E+10 | 0.00 | 0.133924E+09 | 10219104.02 | 0.00 | 0.437302E+11 | 0.00 | 1.92 |
July | 462313.68 | 0.940357E+10 | 0.00 | 0.122704E+09 | 60378587.52 | 0.00 | 0.210977E+11 | 0.00 | 1.90 |
August | 0.185000E+09 | 0.562583E+10 | 0.00 | 0.144487E+09 | 21235759.58 | 0.00 | 0.305809E+11 | 0.00 | 2.02 |
September | 0.894552E+09 | 0.139643E+10 | 0.00 | 0.168778E+09 | 47389.03 | 0.00 | 0.559961E+11 | 0.00 | 2.25 |
October | 0.104347E+11 | 73690791.97 | 0.00 | 0.148024E+09 | 0.00 | 0.00 | 0.840438E+11 | 0.00 | 2.02 |
November | 0.207528E+11 | 0.00 | 0.00 | 78984575.33 | 0.00 | 0.00 | 0.932302E+11 | 0.00 | 1.51 |
December | 0.598097E+11 | 0.00 | 0.00 | 37566755.84 | 0.00 | 0.00 | 0.721301E+11 | 0.00 | 1.33 |
Annual Sum or Average | 0.253596E+12 | 0.225615E+11 | 0.00 | 0.124781E+10 | 95519275.40 | 0.00 | 0.753934E+12 | 0.00 | 1.78 |
Minimum of Months | 462313.68 | 0.00 | 0.00 | 37566755.84 | 0.00 | 0.00 | 0.210977E+11 | 0.00 | 1.33 |
Maximum of Months | 0.637812E+11 | 0.940357E+10 | 0.00 | 0.168778E+09 | 60378587.52 | 0.00 | 0.932302E+11 | 0.00 | 2.25 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 42705354.55 | 0.00 | 0.00 | 7163508.55 | 0.00 | 0.198948E+10 | 0.106909E+10 | 0.00 | 0.35 |
February | 10731399.35 | 0.00 | 0.00 | 9046528.99 | 0.00 | 0.146030E+10 | 0.112920E+10 | 0.00 | 0.35 |
March | 10150965.65 | 0.00 | 0.00 | 14298585.47 | 0.00 | 0.921304E+09 | 0.134926E+10 | 0.00 | 0.35 |
April | 1517488.00 | 332487.23 | 0.00 | 21861707.19 | 0.00 | 0.226860E+09 | 0.127780E+10 | 0.00 | 0.36 |
May | 0.00 | 21309007.53 | 4840.63 | 20660150.24 | 0.00 | 51750267.83 | 0.864363E+09 | 304.29 | 0.36 |
June | 0.00 | 0.274227E+09 | 19055.17 | 9433135.85 | 0.00 | 10732746.84 | 0.298717E+09 | 2580.57 | 0.36 |
July | 0.00 | 0.100503E+10 | 24139.06 | 147796.77 | 0.00 | 0.00 | 1232007.95 | 1617.77 | 0.37 |
August | 0.00 | 0.759426E+09 | 0.00 | 1099887.85 | 0.00 | 53038.49 | 12257419.88 | 0.00 | 0.37 |
September | 0.00 | 0.213177E+09 | 10928.27 | 9381469.65 | 0.00 | 681138.00 | 0.287345E+09 | 1326.51 | 0.37 |
October | 5045804.07 | 33575121.00 | 0.00 | 17968919.10 | 0.00 | 0.337112E+09 | 0.109958E+10 | 0.00 | 0.36 |
November | 8944661.44 | 0.00 | 0.00 | 10175047.42 | 0.00 | 0.979569E+09 | 0.142882E+10 | 0.00 | 0.35 |
December | 25242077.58 | 0.00 | 0.00 | 6725212.40 | 0.00 | 0.190795E+10 | 0.118594E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.104338E+09 | 0.230708E+10 | 58963.13 | 0.127962E+09 | 0.00 | 0.788580E+10 | 0.100036E+11 | 5829.14 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 147796.77 | 0.00 | 0.00 | 1232007.95 | 0.00 | 0.35 |
Maximum of Months | 42705354.55 | 0.100503E+10 | 24139.06 | 21861707.19 | 0.00 | 0.198948E+10 | 0.142882E+10 | 2580.57 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124058E+09 | 0.00 | 0.00 | 2670000.82 | 0.00 | 0.246099E+10 | 0.481400E+09 | 0.00 | 0.34 |
February | 0.114395E+09 | 0.00 | 0.00 | 3985002.18 | 0.00 | 0.180696E+10 | 0.664918E+09 | 0.00 | 0.34 |
March | 0.194614E+09 | 0.00 | 0.00 | 7388062.39 | 0.00 | 0.961826E+09 | 0.120806E+10 | 0.00 | 0.35 |
April | 0.314613E+09 | 233369.92 | 0.00 | 14625484.05 | 0.00 | 0.208116E+09 | 0.122107E+10 | 0.00 | 0.35 |
May | 0.251327E+09 | 13718737.92 | 558.82 | 18096204.40 | 278930.92 | 41602086.95 | 0.810851E+09 | 3624.02 | 0.36 |
June | 0.122297E+09 | 0.250057E+09 | 18737.72 | 9181036.46 | 565294.76 | 8506421.63 | 0.278008E+09 | 13846.10 | 0.37 |
July | 44766048.21 | 0.832594E+09 | 44449.09 | 1119970.74 | 20929542.54 | 0.00 | 3067124.95 | 8882.18 | 0.37 |
August | 85177754.56 | 0.602204E+09 | 55793.74 | 3097633.06 | 12126325.39 | 64999.87 | 12203277.16 | 18087.10 | 0.37 |
September | 0.226221E+09 | 0.143934E+09 | 28067.46 | 10426955.03 | 2313849.54 | 963908.63 | 0.258823E+09 | 9517.10 | 0.36 |
October | 0.286604E+09 | 16051454.03 | 0.00 | 9892133.48 | 757826.48 | 0.385559E+09 | 0.954343E+09 | 0.00 | 0.35 |
November | 85314339.05 | 0.00 | 0.00 | 4600507.08 | 0.00 | 0.131859E+10 | 0.993312E+09 | 0.00 | 0.34 |
December | 0.139342E+09 | 0.00 | 0.00 | 2074718.69 | 0.00 | 0.248598E+10 | 0.447477E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.198873E+10 | 0.185879E+10 | 147606.84 | 87157708.39 | 36971769.63 | 0.967915E+10 | 0.733354E+10 | 53956.50 | 0.35 |
Minimum of Months | 44766048.21 | 0.00 | 0.00 | 1119970.74 | 0.00 | 0.00 | 3067124.95 | 0.00 | 0.34 |
Maximum of Months | 0.314613E+09 | 0.832594E+09 | 55793.74 | 18096204.40 | 20929542.54 | 0.248598E+10 | 0.122107E+10 | 18087.10 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262255E+09 | 0.00 | 0.00 | 0.102566E+09 | 0.00 | 0.00 | 0.584775E+10 | 0.00 | 0.08 |
February | 0.133180E+09 | 0.00 | 0.00 | 97395124.06 | 0.00 | 0.00 | 0.542400E+10 | 0.00 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 0.102550E+09 | 0.00 | 0.00 | 0.461980E+10 | 0.00 | 0.08 |
April | 0.00 | 0.00 | 0.00 | 0.113137E+09 | 0.00 | 0.00 | 0.353202E+10 | 0.00 | 0.09 |
May | 0.00 | 4684742.16 | 0.00 | 0.117985E+09 | 0.00 | 0.00 | 0.232743E+10 | 0.00 | 0.08 |
June | 0.00 | 0.650499E+09 | 0.00 | 91089653.58 | 0.00 | 0.00 | 0.953645E+09 | 0.00 | 0.11 |
July | 0.00 | 0.197310E+10 | 0.00 | 28999266.82 | 0.00 | 0.00 | 0.130878E+09 | 0.00 | 0.13 |
August | 0.00 | 0.131123E+10 | 0.00 | 65046196.29 | 0.00 | 0.00 | 0.362344E+09 | 0.00 | 0.13 |
September | 0.00 | 0.278080E+09 | 0.00 | 0.156833E+09 | 0.00 | 0.00 | 0.157826E+10 | 0.00 | 0.13 |
October | 0.122900E+09 | 10144150.54 | 0.00 | 0.176596E+09 | 0.00 | 0.00 | 0.464892E+10 | 0.00 | 0.12 |
November | 0.117201E+09 | 0.00 | 0.00 | 0.129473E+09 | 0.00 | 0.00 | 0.697084E+10 | 0.00 | 0.10 |
December | 0.332985E+09 | 0.00 | 0.00 | 0.111465E+09 | 0.00 | 0.00 | 0.716745E+10 | 0.00 | 0.08 |
Annual Sum or Average | 0.968521E+09 | 0.422774E+10 | 0.00 | 0.129313E+10 | 0.00 | 0.00 | 0.435633E+11 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 28999266.82 | 0.00 | 0.00 | 0.130878E+09 | 0.00 | 0.08 |
Maximum of Months | 0.332985E+09 | 0.197310E+10 | 0.00 | 0.176596E+09 | 0.00 | 0.00 | 0.716745E+10 | 0.00 | 0.13 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148851E+10 | 0.00 | 0.00 | 26993609.46 | 0.00 | 0.129505E+11 | 0.249698E+11 | 0.00 | 0.38 |
February | 0.153738E+10 | 0.00 | 0.00 | 36363953.31 | 0.00 | 0.838738E+10 | 0.230928E+11 | 0.00 | 0.39 |
March | 0.223380E+10 | 0.00 | 0.00 | 81402490.98 | 0.00 | 0.853459E+09 | 0.260056E+11 | 0.00 | 0.39 |
April | 0.285744E+10 | 9141498.39 | 0.00 | 0.142641E+09 | 0.00 | 50333401.69 | 0.169971E+11 | 0.00 | 0.39 |
May | 0.244407E+10 | 0.221948E+09 | 0.00 | 0.188799E+09 | 3848150.28 | 22682729.26 | 0.102688E+11 | 0.00 | 0.40 |
June | 0.132736E+10 | 0.334283E+10 | 0.00 | 0.109278E+09 | 6232458.47 | 1820113.69 | 0.370388E+10 | 0.00 | 0.41 |
July | 0.606518E+09 | 0.102583E+11 | 0.00 | 27143560.76 | 0.219721E+09 | 0.00 | 62663640.66 | 0.00 | 0.41 |
August | 0.109194E+10 | 0.716571E+10 | 0.00 | 65618380.84 | 0.132236E+09 | 0.00 | 0.216040E+09 | 0.00 | 0.41 |
September | 0.249848E+10 | 0.165717E+10 | 141911.13 | 0.147140E+09 | 24956047.29 | 2855837.53 | 0.329575E+10 | 9499.37 | 0.40 |
October | 0.285495E+10 | 0.166765E+09 | 0.00 | 0.120214E+09 | 9037268.53 | 0.258712E+09 | 0.161052E+11 | 0.00 | 0.39 |
November | 0.147604E+10 | 0.00 | 0.00 | 52940551.19 | 0.00 | 0.161034E+10 | 0.273057E+11 | 0.00 | 0.38 |
December | 0.166754E+10 | 0.00 | 0.00 | 20945950.26 | 0.00 | 0.156186E+11 | 0.221766E+11 | 0.00 | 0.38 |
Annual Sum or Average | 0.220840E+11 | 0.228219E+11 | 141911.13 | 0.101948E+10 | 0.396031E+09 | 0.397567E+11 | 0.174200E+12 | 9499.37 | 0.39 |
Minimum of Months | 0.606518E+09 | 0.00 | 0.00 | 20945950.26 | 0.00 | 0.00 | 62663640.66 | 0.00 | 0.38 |
Maximum of Months | 0.285744E+10 | 0.102583E+11 | 141911.13 | 0.188799E+09 | 0.219721E+09 | 0.156186E+11 | 0.273057E+11 | 9499.37 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 46735284.68 | 0.00 | 0.00 | 7984264.29 | 0.00 | 0.196196E+10 | 0.108250E+10 | 0.00 | 0.35 |
February | 11399934.25 | 0.00 | 0.00 | 9052570.54 | 0.00 | 0.144356E+10 | 0.113830E+10 | 0.00 | 0.35 |
March | 10984101.83 | 0.00 | 0.00 | 14805270.89 | 0.00 | 0.875198E+09 | 0.140210E+10 | 0.00 | 0.35 |
April | 0.00 | 418491.85 | 0.00 | 23036230.50 | 0.00 | 0.239453E+09 | 0.128548E+10 | 0.00 | 0.36 |
May | 0.00 | 25697041.96 | 548.67 | 24070896.21 | 0.00 | 59004583.04 | 0.857190E+09 | 730.50 | 0.36 |
June | 0.00 | 0.297728E+09 | 0.00 | 13177706.09 | 0.00 | 6668809.19 | 0.302008E+09 | 0.00 | 0.37 |
July | 0.00 | 0.106698E+10 | 0.00 | 165397.88 | 0.00 | 0.00 | 1520352.76 | 0.00 | 0.38 |
August | 0.00 | 0.803784E+09 | 0.00 | 1329691.45 | 0.00 | 0.00 | 13753565.24 | 0.00 | 0.38 |
September | 0.00 | 0.224826E+09 | 0.00 | 11539907.06 | 0.00 | 74987.80 | 0.293722E+09 | 0.00 | 0.37 |
October | 5022878.02 | 36624209.75 | 0.00 | 18147254.52 | 0.00 | 0.352856E+09 | 0.109046E+10 | 0.00 | 0.36 |
November | 8878569.28 | 0.00 | 0.00 | 11192614.73 | 0.00 | 0.962825E+09 | 0.144284E+10 | 0.00 | 0.35 |
December | 24547375.33 | 0.00 | 0.00 | 7441285.34 | 0.00 | 0.193704E+10 | 0.114195E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.107568E+09 | 0.245606E+10 | 548.67 | 0.141943E+09 | 0.00 | 0.783864E+10 | 0.100518E+11 | 730.50 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 165397.88 | 0.00 | 0.00 | 1520352.76 | 0.00 | 0.34 |
Maximum of Months | 46735284.68 | 0.106698E+10 | 548.67 | 24070896.21 | 0.00 | 0.196196E+10 | 0.144284E+10 | 730.50 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128851E+09 | 0.00 | 0.00 | 2479806.41 | 0.00 | 0.235359E+10 | 0.570448E+09 | 0.00 | 0.34 |
February | 0.108752E+09 | 0.00 | 0.00 | 3529015.70 | 0.00 | 0.171343E+10 | 0.741831E+09 | 0.00 | 0.34 |
March | 0.126897E+09 | 0.00 | 0.00 | 8704130.83 | 0.00 | 0.928224E+09 | 0.124465E+10 | 0.00 | 0.35 |
April | 0.242287E+09 | 302251.63 | 0.00 | 17959250.26 | 0.00 | 0.246131E+09 | 0.118011E+10 | 0.00 | 0.36 |
May | 0.214731E+09 | 16058462.33 | 0.00 | 22274817.60 | 266003.08 | 53953204.05 | 0.802440E+09 | 0.00 | 0.36 |
June | 0.122893E+09 | 0.265824E+09 | 0.00 | 13848619.04 | 498302.41 | 4669743.60 | 0.295839E+09 | 0.00 | 0.37 |
July | 51029244.43 | 0.875389E+09 | 74250.11 | 2732817.07 | 18490898.10 | 0.00 | 14228712.36 | 12574.79 | 0.38 |
August | 89045988.97 | 0.631286E+09 | 63854.95 | 4832287.23 | 11547587.42 | 47144.20 | 30699383.03 | 3729.34 | 0.37 |
September | 0.214573E+09 | 0.153084E+09 | 9648.87 | 12715474.32 | 2002283.50 | 566422.51 | 0.275177E+09 | 2273.47 | 0.36 |
October | 0.221379E+09 | 18822573.96 | 0.00 | 11498135.94 | 754275.80 | 0.386090E+09 | 0.932806E+09 | 0.00 | 0.35 |
November | 0.102124E+09 | 0.00 | 0.00 | 4807952.89 | 0.00 | 0.120766E+10 | 0.107162E+10 | 0.00 | 0.34 |
December | 0.140958E+09 | 0.00 | 0.00 | 1926640.87 | 0.00 | 0.241507E+10 | 0.499312E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.176352E+10 | 0.196077E+10 | 147753.93 | 0.107309E+09 | 33559350.30 | 0.930943E+10 | 0.765916E+10 | 18577.60 | 0.35 |
Minimum of Months | 51029244.43 | 0.00 | 0.00 | 1926640.87 | 0.00 | 0.00 | 14228712.36 | 0.00 | 0.34 |
Maximum of Months | 0.242287E+09 | 0.875389E+09 | 74250.11 | 22274817.60 | 18490898.10 | 0.241507E+10 | 0.124465E+10 | 12574.79 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 9731092.86 | 0.00 | 0.00 | 0.286858E+10 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.00 | 12411273.68 | 0.00 | 0.00 | 0.326666E+10 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.00 | 22341675.13 | 0.00 | 0.00 | 0.443478E+10 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.00 | 35187492.62 | 0.00 | 0.00 | 0.495439E+10 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.00 | 44193047.11 | 0.00 | 0.00 | 0.427408E+10 | 0.00 | 0.07 |
June | 0.00 | 0.200087E+09 | 0.00 | 46811095.36 | 0.00 | 0.00 | 0.257770E+10 | 0.00 | 0.11 |
July | 0.00 | 0.112382E+10 | 0.00 | 24758459.81 | 0.00 | 0.00 | 0.691380E+09 | 0.00 | 0.13 |
August | 0.00 | 0.715842E+09 | 0.00 | 35117008.35 | 0.00 | 0.00 | 0.107974E+10 | 0.00 | 0.12 |
September | 0.00 | 0.102583E+09 | 0.00 | 48818352.43 | 0.00 | 0.00 | 0.248039E+10 | 0.00 | 0.10 |
October | 0.00 | 7685841.02 | 0.00 | 38578187.59 | 0.00 | 0.00 | 0.432732E+10 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.00 | 18825370.89 | 0.00 | 0.00 | 0.441077E+10 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 | 8804517.79 | 0.00 | 0.00 | 0.294830E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.215002E+10 | 0.00 | 0.345578E+09 | 0.00 | 0.00 | 0.383141E+11 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8804517.79 | 0.00 | 0.00 | 0.691380E+09 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.112382E+10 | 0.00 | 48818352.43 | 0.00 | 0.00 | 0.495439E+10 | 0.00 | 0.13 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11850135.87 | 0.00 | 0.00 | 1320193.64 | 0.00 | 0.636036E+09 | 0.130067E+09 | 0.00 | 0.35 |
February | 4495017.04 | 0.00 | 0.00 | 1849707.67 | 0.00 | 0.483704E+09 | 0.164384E+09 | 0.00 | 0.35 |
March | 5526103.82 | 0.00 | 0.00 | 3139897.69 | 0.00 | 0.359587E+09 | 0.207577E+09 | 0.00 | 0.35 |
April | 2792196.67 | 87645.03 | 0.00 | 5216486.87 | 0.00 | 0.144814E+09 | 0.228458E+09 | 0.00 | 0.36 |
May | 1530050.06 | 5377702.19 | 6485.40 | 4944882.59 | 0.00 | 56395324.14 | 0.175513E+09 | 663.79 | 0.36 |
June | 0.00 | 70255222.93 | 20828.12 | 2154366.68 | 0.00 | 9197270.42 | 73202549.32 | 1661.98 | 0.37 |
July | 0.00 | 0.252228E+09 | 49442.43 | 52652.96 | 0.00 | 0.00 | 392030.06 | 1851.33 | 0.37 |
August | 0.00 | 0.190006E+09 | 24660.88 | 270897.63 | 0.00 | 32773.43 | 4641581.29 | 2334.74 | 0.37 |
September | 0.00 | 52635058.65 | 345.39 | 2082500.33 | 0.00 | 4575020.55 | 75205935.83 | 1281.83 | 0.37 |
October | 2699775.21 | 7928568.67 | 0.00 | 4107922.37 | 0.00 | 0.179289E+09 | 0.183451E+09 | 0.00 | 0.36 |
November | 3898046.85 | 0.00 | 0.00 | 1904320.09 | 0.00 | 0.384050E+09 | 0.219799E+09 | 0.00 | 0.35 |
December | 5284335.77 | 0.00 | 0.00 | 1152943.09 | 0.00 | 0.630653E+09 | 0.145243E+09 | 0.00 | 0.35 |
Annual Sum or Average | 38075661.29 | 0.578518E+09 | 101762.23 | 28196771.63 | 0.00 | 0.288833E+10 | 0.160793E+10 | 7793.67 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 52652.96 | 0.00 | 0.00 | 392030.06 | 0.00 | 0.35 |
Maximum of Months | 11850135.87 | 0.252228E+09 | 49442.43 | 5216486.87 | 0.00 | 0.636036E+09 | 0.228458E+09 | 2334.74 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 27898596.05 | 0.00 | 0.00 | 439297.12 | 0.00 | 0.706517E+09 | 38331459.99 | 0.00 | 0.34 |
February | 28830193.94 | 0.00 | 0.00 | 738529.90 | 0.00 | 0.544162E+09 | 77354803.56 | 0.00 | 0.34 |
March | 50668137.13 | 0.00 | 0.00 | 1506006.32 | 0.00 | 0.388988E+09 | 0.155616E+09 | 0.00 | 0.35 |
April | 80334961.73 | 59312.40 | 0.00 | 3474188.56 | 0.00 | 0.124025E+09 | 0.236226E+09 | 0.00 | 0.35 |
May | 64224507.07 | 3567252.58 | 0.00 | 4446111.50 | 71866.49 | 41971837.79 | 0.175104E+09 | 448.13 | 0.36 |
June | 29768007.15 | 64858250.98 | 11123.32 | 2203140.44 | 139290.41 | 6566997.04 | 69316817.34 | 3750.87 | 0.37 |
July | 10350129.78 | 0.213630E+09 | 59451.45 | 274311.84 | 5097771.66 | 2347.26 | 1413787.36 | 8602.08 | 0.37 |
August | 20749449.31 | 0.154951E+09 | 38802.67 | 738920.88 | 2923013.54 | 13525.66 | 3923966.47 | 13987.47 | 0.37 |
September | 56630031.50 | 37179373.38 | 2420.34 | 2392376.03 | 550273.53 | 193238.10 | 69137378.53 | 1229.58 | 0.36 |
October | 74178237.26 | 4018512.04 | 0.00 | 2141055.44 | 179739.82 | 0.188773E+09 | 0.150645E+09 | 0.00 | 0.35 |
November | 27763224.82 | 0.00 | 0.00 | 755665.56 | 0.00 | 0.484586E+09 | 90292655.70 | 0.00 | 0.34 |
December | 28419747.65 | 0.00 | 0.00 | 310051.83 | 0.00 | 0.711410E+09 | 34767216.80 | 0.00 | 0.34 |
Annual Sum or Average | 0.499815E+09 | 0.478264E+09 | 111797.78 | 19419655.43 | 8961955.45 | 0.319721E+10 | 0.110213E+10 | 28018.14 | 0.35 |
Minimum of Months | 10350129.78 | 0.00 | 0.00 | 274311.84 | 0.00 | 2347.26 | 1413787.36 | 0.00 | 0.34 |
Maximum of Months | 80334961.73 | 0.213630E+09 | 59451.45 | 4446111.50 | 5097771.66 | 0.711410E+09 | 0.236226E+09 | 13987.47 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 21175100.03 | 0.00 | 0.00 | 20805592.17 | 0.00 | 0.312777E+10 | 0.209841E+10 | 0.00 | 0.41 |
February | 12728824.98 | 0.00 | 0.00 | 19989305.43 | 0.00 | 0.236364E+10 | 0.202042E+10 | 0.00 | 0.41 |
March | 13970159.21 | 0.00 | 0.00 | 21284456.71 | 0.00 | 0.173931E+10 | 0.207270E+10 | 0.00 | 0.41 |
April | 1414594.45 | 173257.57 | 0.00 | 25238552.42 | 0.00 | 0.701940E+09 | 0.183578E+10 | 0.00 | 0.41 |
May | 0.00 | 23639646.03 | 0.00 | 24720016.50 | 0.00 | 0.242117E+09 | 0.136946E+10 | 0.00 | 0.41 |
June | 0.00 | 0.391216E+09 | 14042.71 | 12679364.50 | 0.00 | 26833434.85 | 0.570285E+09 | 3314.22 | 0.41 |
July | 0.00 | 0.150204E+10 | 84795.88 | 677491.45 | 0.00 | 0.00 | 6887157.48 | 1760.79 | 0.42 |
August | 0.00 | 0.114482E+10 | 94272.81 | 2221302.35 | 0.00 | 84931.52 | 45356865.16 | 362.66 | 0.43 |
September | 0.00 | 0.335256E+09 | 0.00 | 14411675.53 | 0.00 | 291295.79 | 0.545346E+09 | 0.00 | 0.43 |
October | 8305014.62 | 55791054.88 | 0.00 | 30671473.96 | 0.00 | 0.679750E+09 | 0.177332E+10 | 0.00 | 0.43 |
November | 14116281.09 | 0.00 | 0.00 | 24296717.36 | 0.00 | 0.165032E+10 | 0.247102E+10 | 0.00 | 0.42 |
December | 41121588.98 | 0.00 | 0.00 | 22064464.38 | 0.00 | 0.301310E+10 | 0.228606E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.112832E+09 | 0.345293E+10 | 193111.39 | 0.219060E+09 | 0.00 | 0.135452E+11 | 0.170950E+11 | 5437.67 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 677491.45 | 0.00 | 0.00 | 6887157.48 | 0.00 | 0.41 |
Maximum of Months | 41121588.98 | 0.150204E+10 | 94272.81 | 30671473.96 | 0.00 | 0.312777E+10 | 0.247102E+10 | 3314.22 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168008E+11 | 0.00 | 0.00 | 26181882.22 | 0.00 | 0.00 | 0.670449E+11 | 0.00 | 4.39 |
February | 0.103466E+11 | 0.00 | 0.00 | 31945605.92 | 0.00 | 0.00 | 0.615559E+11 | 0.00 | 4.47 |
March | 0.243131E+10 | 0.00 | 0.00 | 58032584.41 | 0.00 | 0.00 | 0.664362E+11 | 0.00 | 4.83 |
April | 0.592143E+09 | 0.00 | 0.00 | 85606464.75 | 0.00 | 0.00 | 0.542711E+11 | 0.00 | 5.62 |
May | 0.195868E+09 | 0.168001E+09 | 0.00 | 0.105389E+09 | 0.00 | 0.00 | 0.450093E+11 | 0.00 | 5.96 |
June | 31499421.21 | 0.347195E+10 | 0.00 | 92940275.70 | 0.00 | 0.00 | 0.286244E+11 | 0.00 | 5.76 |
July | 0.00 | 0.471295E+10 | 0.00 | 85053322.35 | 0.00 | 0.00 | 0.161884E+11 | 0.00 | 5.66 |
August | 6876015.42 | 0.266457E+10 | 0.00 | 95636009.23 | 0.00 | 0.00 | 0.214096E+11 | 0.00 | 5.86 |
September | 66184435.99 | 0.528190E+09 | 0.00 | 99921122.60 | 0.00 | 0.00 | 0.348146E+11 | 0.00 | 6.20 |
October | 0.249578E+10 | 33969288.89 | 0.00 | 76642501.61 | 0.00 | 0.00 | 0.538029E+11 | 0.00 | 5.53 |
November | 0.454887E+10 | 0.00 | 0.00 | 40228262.09 | 0.00 | 0.00 | 0.655650E+11 | 0.00 | 4.53 |
December | 0.208419E+11 | 0.00 | 0.00 | 24260483.40 | 0.00 | 0.00 | 0.639198E+11 | 0.00 | 4.33 |
Annual Sum or Average | 0.583578E+11 | 0.115796E+11 | 0.00 | 0.821838E+09 | 0.00 | 0.00 | 0.578642E+12 | 0.00 | 5.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 24260483.40 | 0.00 | 0.00 | 0.161884E+11 | 0.00 | 4.33 |
Maximum of Months | 0.208419E+11 | 0.471295E+10 | 0.00 | 0.105389E+09 | 0.00 | 0.00 | 0.670449E+11 | 0.00 | 6.20 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.912588E+10 | 0.00 | 0.00 | 38318472.33 | 0.00 | 0.00 | 0.759492E+11 | 0.00 | 4.45 |
February | 0.479817E+10 | 0.00 | 0.00 | 44003966.63 | 0.00 | 0.00 | 0.685311E+11 | 0.00 | 4.55 |
March | 0.956569E+09 | 0.00 | 0.00 | 71728911.41 | 0.00 | 0.00 | 0.701856E+11 | 0.00 | 5.00 |
April | 0.192383E+09 | 0.00 | 0.00 | 97623243.22 | 0.00 | 0.00 | 0.571547E+11 | 0.00 | 5.91 |
May | 35706369.77 | 0.178331E+09 | 0.00 | 0.116734E+09 | 0.00 | 0.00 | 0.474675E+11 | 0.00 | 6.29 |
June | 0.00 | 0.369543E+10 | 0.00 | 0.100247E+09 | 0.00 | 0.00 | 0.301246E+11 | 0.00 | 6.08 |
July | 0.00 | 0.501492E+10 | 0.00 | 89952961.04 | 0.00 | 0.00 | 0.169713E+11 | 0.00 | 5.98 |
August | 0.00 | 0.283589E+10 | 0.00 | 0.103298E+09 | 0.00 | 0.00 | 0.224713E+11 | 0.00 | 6.18 |
September | 0.00 | 0.565059E+09 | 0.00 | 0.112067E+09 | 0.00 | 0.00 | 0.365847E+11 | 0.00 | 6.54 |
October | 0.840040E+09 | 36091497.46 | 0.00 | 89416561.20 | 0.00 | 0.00 | 0.576264E+11 | 0.00 | 5.77 |
November | 0.208125E+10 | 0.00 | 0.00 | 53468246.52 | 0.00 | 0.00 | 0.696824E+11 | 0.00 | 4.63 |
December | 0.113319E+11 | 0.00 | 0.00 | 35091580.74 | 0.00 | 0.00 | 0.745571E+11 | 0.00 | 4.38 |
Annual Sum or Average | 0.293619E+11 | 0.123257E+11 | 0.00 | 0.951950E+09 | 0.00 | 0.00 | 0.627306E+12 | 0.00 | 5.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 35091580.74 | 0.00 | 0.00 | 0.169713E+11 | 0.00 | 4.38 |
Maximum of Months | 0.113319E+11 | 0.501492E+10 | 0.00 | 0.116734E+09 | 0.00 | 0.00 | 0.759492E+11 | 0.00 | 6.54 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.110788E+09 | 0.00 | 0.00 | 0.825621E+11 | 0.00 | 13.96 |
February | 0.00 | 0.00 | 0.00 | 0.102370E+09 | 0.00 | 0.00 | 0.747172E+11 | 0.00 | 15.69 |
March | 0.00 | 0.00 | 0.00 | 0.124016E+09 | 0.00 | 0.00 | 0.824918E+11 | 0.00 | 20.86 |
April | 0.00 | 0.00 | 0.00 | 0.138169E+09 | 0.00 | 0.00 | 0.695110E+11 | 0.00 | 24.70 |
May | 0.00 | 0.00 | 0.00 | 0.158995E+09 | 0.00 | 0.00 | 0.570961E+11 | 0.00 | 24.56 |
June | 0.00 | 83963441.15 | 0.00 | 0.160898E+09 | 0.00 | 0.00 | 0.324022E+11 | 0.00 | 19.91 |
July | 0.00 | 0.130279E+10 | 0.00 | 98374249.38 | 0.00 | 0.00 | 0.128734E+11 | 0.00 | 18.88 |
August | 0.00 | 0.608981E+09 | 0.00 | 0.136340E+09 | 0.00 | 0.00 | 0.203598E+11 | 0.00 | 21.27 |
September | 0.00 | 55379702.66 | 0.00 | 0.156951E+09 | 0.00 | 0.00 | 0.405444E+11 | 0.00 | 24.87 |
October | 0.00 | 0.00 | 0.00 | 0.139087E+09 | 0.00 | 0.00 | 0.698064E+11 | 0.00 | 24.20 |
November | 0.00 | 0.00 | 0.00 | 0.110361E+09 | 0.00 | 0.00 | 0.819025E+11 | 0.00 | 17.82 |
December | 0.00 | 0.00 | 0.00 | 0.110322E+09 | 0.00 | 0.00 | 0.824298E+11 | 0.00 | 12.80 |
Annual Sum or Average | 0.00 | 0.205112E+10 | 0.00 | 0.154667E+10 | 0.00 | 0.00 | 0.706697E+12 | 0.00 | 19.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 98374249.38 | 0.00 | 0.00 | 0.128734E+11 | 0.00 | 12.80 |
Maximum of Months | 0.00 | 0.130279E+10 | 0.00 | 0.160898E+09 | 0.00 | 0.00 | 0.825621E+11 | 0.00 | 24.87 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 841759.18 | 0.00 | 0.716091E+09 | 0.101981E+09 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.00 | 2079390.57 | 0.00 | 0.323983E+09 | 0.190089E+09 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.00 | 5788551.90 | 0.00 | 0.00 | 0.417727E+09 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.00 | 15275312.16 | 0.00 | 0.00 | 0.724448E+09 | 0.00 | 0.04 |
May | 0.00 | 287307.13 | 0.00 | 22413166.85 | 0.00 | 0.00 | 0.649882E+09 | 0.00 | 0.06 |
June | 0.00 | 0.130429E+09 | 0.00 | 20633329.21 | 0.00 | 0.00 | 0.349343E+09 | 0.00 | 0.09 |
July | 0.00 | 0.586653E+09 | 0.00 | 5571825.08 | 0.00 | 0.00 | 55608693.16 | 0.00 | 0.11 |
August | 0.00 | 0.409589E+09 | 0.00 | 9511733.29 | 0.00 | 0.00 | 98566858.96 | 0.00 | 0.11 |
September | 0.00 | 91508997.07 | 0.00 | 18337357.90 | 0.00 | 0.00 | 0.301015E+09 | 0.00 | 0.08 |
October | 0.00 | 8749650.97 | 0.00 | 14455878.45 | 0.00 | 15811782.65 | 0.542678E+09 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.00 | 3152736.54 | 0.00 | 10231419.94 | 0.340838E+09 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 367047.94 | 0.00 | 0.851991E+09 | 56381917.78 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.122722E+10 | 0.00 | 0.118428E+09 | 0.00 | 0.191811E+10 | 0.382856E+10 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 367047.94 | 0.00 | 0.00 | 55608693.16 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.586653E+09 | 0.00 | 22413166.85 | 0.00 | 0.851991E+09 | 0.724448E+09 | 0.00 | 0.11 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:28
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.236638E+12 | 0.171365E+11 | 0.203679E+12 | 0.476531E+12 | 0.163618E+12 |
February | 0.300905E+12 | 0.144490E+11 | 0.168723E+12 | 0.416351E+12 | 0.159348E+12 |
March | 0.409223E+12 | 0.130697E+11 | 0.143262E+12 | 0.428959E+12 | 0.185601E+12 |
April | 0.509146E+12 | 0.914949E+10 | 0.986713E+11 | 0.361403E+12 | 0.317129E+12 |
May | 0.546635E+12 | 0.643135E+10 | 0.739900E+11 | 0.304666E+12 | 0.491712E+12 |
June | 0.504883E+12 | 0.253546E+10 | 0.348364E+11 | 0.176537E+12 | 0.806175E+12 |
July | 0.506363E+12 | -767264798.3 | -0.274846E+10 | 0.652894E+11 | 0.110174E+13 |
August | 0.483262E+12 | 0.379644E+09 | 0.122357E+11 | 0.114743E+12 | 0.101592E+13 |
September | 0.388055E+12 | 0.333012E+10 | 0.431591E+11 | 0.235747E+12 | 0.715044E+12 |
October | 0.310069E+12 | 0.911062E+10 | 0.103392E+12 | 0.386748E+12 | 0.397536E+12 |
November | 0.249061E+12 | 0.137297E+11 | 0.160955E+12 | 0.445591E+12 | 0.175472E+12 |
December | 0.217418E+12 | 0.175339E+11 | 0.211881E+12 | 0.480758E+12 | 0.167549E+12 |
Annual Sum or Average | 0.466166E+13 | 0.106088E+12 | 0.125204E+13 | 0.389332E+13 | 0.569684E+13 |
Minimum of Months | 0.217418E+12 | -767264798.3 | -0.274846E+10 | 0.652894E+11 | 0.159348E+12 |