Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:24
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2024-07-03 12:24:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11926.02 | 1051.19 | 1051.19 |
Net Site Energy | 11926.02 | 1051.19 | 1051.19 |
Total Source Energy | 29180.75 | 2572.06 | 2572.06 |
Net Source Energy | 29180.75 | 2572.06 | 2572.06 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 84.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2141.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 322.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1661.82 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 841.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1178.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2334.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 7802.66 | 4123.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 84.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 2141.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 322.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 15.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 11.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1178.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 2334.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 84.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2141.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 322.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1661.82 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 841.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1178.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 2334.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 162.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 300.24 | 205.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.56 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 687.74 | 363.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 162.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 300.24 | 205.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.56 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 687.74 | 363.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 7802.660 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 7802.660 | 100.00 |
Total On-Site and Utility Electric Sources | 7802.660 | 100.00 |
Total Electricity End Uses | 7802.660 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 39.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7787.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |DXReportMonthly
| ROOM_1_FLR_3 PTAC COOLING COIL | ROOM_2_FLR_3 PTAC COOLING COIL | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | ROOM_5_FLR_3 PTAC COOLING COIL | ROOM_6_FLR_3 PTAC COOLING COIL | ROOM_1_FLR_6 PTAC COOLING COIL | ROOM_2_FLR_6 PTAC COOLING COIL | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | PTAC_3 PTAC COOLING COIL | PTAC_6 PTAC COOLING COIL | VAV_FLR_1 COOLING COIL | VAV_FLR_6 COOLING COIL | VAV_FLR_0 COOLING COIL | PSZ_LAUNDRY HP COOLING COIL | PSZ_CAFE HP COOLING COIL | PSZ_KITCHEN HP COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_FLR_1 HEATING COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | VAV_FLR_6 HEATING COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3_SUPPHEATCOIL | ROOM_2_FLR_3_SUPPHEATCOIL | ROOM_3_MULT19_FLR_3_SUPPHEATCOIL | ROOM_4_MULT19_FLR_3_SUPPHEATCOIL | ROOM_5_FLR_3_SUPPHEATCOIL | ROOM_6_FLR_3_SUPPHEATCOIL | ROOM_1_FLR_6_SUPPHEATCOIL | ROOM_2_FLR_6_SUPPHEATCOIL | ROOM_3_MULT9_FLR_6_SUPPHEATCOIL | VAV_FLR_0 HEATING COIL | PSZ_LAUNDRY_SUPPHEATCOIL | PSZ_CAFE_SUPPHEATCOIL | PTAC_3_SUPPHEATCOIL | PTAC_6_SUPPHEATCOIL | PSZ_KITCHEN_SUPPHEATCOIL | ROOM_1_FLR_3 PTAC HEATING COIL | ROOM_2_FLR_3 PTAC HEATING COIL | ROOM_3_MULT19_FLR_3 PTAC HEATING COIL | ROOM_4_MULT19_FLR_3 PTAC HEATING COIL | ROOM_5_FLR_3 PTAC HEATING COIL | ROOM_6_FLR_3 PTAC HEATING COIL | ROOM_1_FLR_6 PTAC HEATING COIL | ROOM_2_FLR_6 PTAC HEATING COIL | ROOM_3_MULT9_FLR_6 PTAC HEATING COIL | PTAC_3 PTAC HEATING COIL | PTAC_6 PTAC HEATING COIL | PSZ_LAUNDRY HEATING COIL | PSZ_CAFE HEATING COIL | PSZ_KITCHEN HEATING COIL | ROOM_1_FLR_3 PTAC COOLING COIL | ROOM_2_FLR_3 PTAC COOLING COIL | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | ROOM_5_FLR_3 PTAC COOLING COIL | ROOM_6_FLR_3 PTAC COOLING COIL | ROOM_1_FLR_6 PTAC COOLING COIL | ROOM_2_FLR_6 PTAC COOLING COIL | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | PTAC_3 PTAC COOLING COIL | PTAC_6 PTAC COOLING COIL | VAV_FLR_1 COOLING COIL | VAV_FLR_6 COOLING COIL | VAV_FLR_0 COOLING COIL | PSZ_LAUNDRY HP COOLING COIL | PSZ_CAFE HP COOLING COIL | PSZ_KITCHEN HP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| RETAIL_1_FLR_1 PIU FAN | RETAIL_2_FLR_1 PIU FAN | MECH_FLR_1 PIU FAN | STORAGE_FLR_1 PIU FAN | LOBBY_FLR_1 PIU FAN | BANQUET_FLR_6 PIU FAN | DINING_FLR_6 PIU FAN | VAV_FLR_1 FAN | VAV_FLR_6 FAN | VAV_FLR_0 SZVAV FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | LAUNDRY_FLR_1 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3_PTAC_SUPPLY FAN | ROOM_2_FLR_3_PTAC_SUPPLY FAN | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | ROOM_5_FLR_3_PTAC_SUPPLY FAN | ROOM_6_FLR_3_PTAC_SUPPLY FAN | ROOM_1_FLR_6_PTAC_SUPPLY FAN | ROOM_2_FLR_6_PTAC_SUPPLY FAN | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | PTAC_3_PTAC_SUPPLY FAN | PTAC_6_PTAC_SUPPLY FAN | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |AirLoopSystemComponentLoadsMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |AirLoopSystemComponentEnergyUseMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1368.30 | 497.27 | 98.60 | 673.82 | 98.60 |
Gross Window-Wall Ratio [%] | 30.01 | 26.54 | 24.26 | 35.97 | 24.26 |
Above Ground Window-Wall Ratio [%] | 33.99 | 29.91 | 28.11 | 40.54 | 28.11 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1368.30 | 497.27 | 98.60 | 673.82 | 98.60 |
Gross Window-Wall Ratio [%] | 30.01 | 26.54 | 24.26 | 35.97 | 24.26 |
Above Ground Window-Wall Ratio [%] | 33.99 | 29.91 | 28.11 | 40.54 | 28.11 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 11.0679 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 16.1458 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 16.1458 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 15.0695 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 13.9931 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 4.22 | 4.22 | 12.2708 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 4.23 | 4.23 | 12.2708 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 18.31 | 18.31 | 5.3819 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 7.75 | 7.75 | 12.2709 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 36.97 | 36.97 | 15.0695 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 36.97 | 36.97 | 15.0695 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 30.28 | 30.28 | 12.9167 | 4.65 | 2935.6055 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 32.40 | 32.40 | 5.3819 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1368.30 | 1368.30 | 11.3147 | 7.07 | 41.0811 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1368.30 | 1368.30 | 11.3147 | 7.07 | 41.0811 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.0679 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 16.1458 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 16.1458 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 16.1458 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 8.6111 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 15.0695 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 13.9931 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 12.2708 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 12.2708 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 5.3819 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 12.2708 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 12.2708 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 12.2709 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 15.0695 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 15.0695 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 12.9167 | 4.65 | 2935.6055 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 5.3819 | 18.58 | 0.0000 | |
Total | 11345.29 | 11.3147 | 3.54 | 41.0811 | |||||||
Conditioned Total | 11345.29 | 11.3147 | 3.54 | 41.0811 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 6.0626 | 8.82 | 37.2091 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-18:10 | 23-JAN-18:30 | - | - | - | - | - | - | - | - | - | - | 18-APR-20:49 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 269751.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 107831.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 77688.87 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 29010.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58721.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 224512.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1687.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 544738.40 | 328760.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 269751.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 107831.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 47590.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 365.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1069.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 26968.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 58721.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 47.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 224512.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 228.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 791.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 666.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 268.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6781.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4833.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1021.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5262.99 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2666.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3733.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2530.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 24711.03 | 4469.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 23.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 597.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.89 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 329.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 223.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2178.09 | 393.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 23.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 597.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 90.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.89 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 329.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 223.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2178.09 | 393.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 3.77 | 0.399605 | 0.300000 | 1.13 |
Design Size Maximum Primary Air Flow Rate [m3/s] | Design Size Maximum Secondary Air Flow Rate [m3/s] | Design Size Minimum Primary Air Flow Fraction | User-Specified Minimum Primary Air Flow Fraction | |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.582088 | 0.582088 | 0.136093 | 0.300000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.380196 | 0.380196 | 0.241282 | 0.375000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.446243 | 0.446243 | ||
STORAGE_FLR_1 VAV BOX COMPONENT | 0.243477 | 0.243477 | 0.237251 | 0.369000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 7.10 | 7.10 | 0.266778 | 0.415000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 3.28 | 3.28 | 0.361614 | 0.480000 |
DINING_FLR_6 VAV BOX COMPONENT | 3.42 | 3.42 | 0.346874 | 0.460000 |
Design Size Maximum Flow Rate [m3/s] | |
RETAIL_1_FLR_1 PIU FAN | 0.582088 |
RETAIL_2_FLR_1 PIU FAN | 0.380196 |
MECH_FLR_1 PIU FAN | 0.446243 |
STORAGE_FLR_1 PIU FAN | 0.243477 |
LOBBY_FLR_1 PIU FAN | 7.10 |
BANQUET_FLR_6 PIU FAN | 3.28 |
DINING_FLR_6 PIU FAN | 3.42 |
Design Size Nominal Capacity [W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 11425.44 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 8247.60 |
MECH_FLR_1 VAV BOX REHEAT COIL | 8758.94 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 5240.62 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 162123.21 |
ROOM_1_FLR_3_SUPPHEATCOIL | 9237.59 |
ROOM_2_FLR_3_SUPPHEATCOIL | 9259.62 |
ROOM_3_MULT19_FLR_3_SUPPHEATCOIL | 64283.78 |
ROOM_4_MULT19_FLR_3_SUPPHEATCOIL | 64711.39 |
ROOM_5_FLR_3_SUPPHEATCOIL | 9193.12 |
ROOM_6_FLR_3_SUPPHEATCOIL | 9215.16 |
PTAC_3_SUPPHEATCOIL | 23668.30 |
ROOM_1_FLR_6_SUPPHEATCOIL | 2824.01 |
ROOM_2_FLR_6_SUPPHEATCOIL | 2826.87 |
ROOM_3_MULT9_FLR_6_SUPPHEATCOIL | 14273.26 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 81312.23 |
DINING_FLR_6 VAV BOX REHEAT COIL | 82717.75 |
PTAC_6_SUPPHEATCOIL | 12469.01 |
VAV_FLR_1 HEATING COIL | 35592.88 |
VAV_FLR_6 HEATING COIL | 27391.39 |
VAV_FLR_0 HEATING COIL | 33057.48 |
PSZ_LAUNDRY_SUPPHEATCOIL | 70703.09 |
PSZ_CAFE_SUPPHEATCOIL | 48423.56 |
PSZ_KITCHEN_SUPPHEATCOIL | 60998.59 |
Design Size Maximum Air Flow Rate [m3/s] | |
LAUNDRY_FLR_1 DIRECT AIR | 4.27 |
CAFE_FLR_1 DIRECT AIR | 2.24 |
KITCHEN_FLR_6 DIRECT AIR | 2.97 |
Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | |
ROOM_1_FLR_3 | 1.45 | 1.45 | 1.45 | 0.061735 | 0.061735 | 0.061735 | 32.22 |
ROOM_2_FLR_3 | 1.44 | 1.44 | 1.44 | 0.061728 | 0.061728 | 0.061728 | 32.22 |
ROOM_3_MULT19_FLR_3 | 8.38 | 8.38 | 8.38 | 0.837072 | 0.837072 | 0.837072 | 32.22 |
ROOM_4_MULT19_FLR_3 | 8.52 | 8.52 | 8.52 | 0.837300 | 0.837300 | 0.837300 | 32.22 |
ROOM_5_FLR_3 | 1.26 | 1.26 | 1.26 | 0.061735 | 0.061735 | 0.061735 | 32.22 |
ROOM_6_FLR_3 | 1.25 | 1.25 | 1.25 | 0.061728 | 0.061728 | 0.061728 | 32.22 |
PTAC_3 | 2.14 | 2.14 | 2.14 | 0.474762 | 0.474762 | 0.474762 | 32.11 |
ROOM_1_FLR_6 | 0.400114 | 0.400114 | 0.400114 | 0.015434 | 0.015434 | 0.015434 | 32.22 |
ROOM_2_FLR_6 | 0.397401 | 0.397401 | 0.397401 | 0.015432 | 0.015432 | 0.015432 | 32.22 |
ROOM_3_MULT9_FLR_6 | 1.78 | 1.78 | 1.78 | 0.099154 | 0.099154 | 0.099154 | 32.22 |
PTAC_6 | 1.35 | 1.35 | 1.35 | 0.125616 | 0.125616 | 0.125616 | 32.11 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
ROOM_1_FLR_3 PTAC COOLING COIL | 1.45 | 24908.39 | 0.800035 |
ROOM_2_FLR_3 PTAC COOLING COIL | 1.44 | 24693.91 | 0.800948 |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 8.38 | 158710.41 | 0.798447 |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 8.52 | 159287.15 | 0.800665 |
ROOM_5_FLR_3 PTAC COOLING COIL | 1.26 | 20998.11 | 0.800289 |
ROOM_6_FLR_3 PTAC COOLING COIL | 1.25 | 20697.72 | 0.800090 |
PTAC_3 PTAC COOLING COIL | 2.14 | 42025.03 | 0.782557 |
ROOM_1_FLR_6 PTAC COOLING COIL | 0.400114 | 6844.81 | 0.800757 |
ROOM_2_FLR_6 PTAC COOLING COIL | 0.397401 | 6781.29 | 0.800655 |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 1.78 | 31790.13 | 0.800979 |
PTAC_6 PTAC COOLING COIL | 1.35 | 23648.34 | 0.800541 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Heating Capacity [W] | |
ROOM_1_FLR_3 PTAC HEATING COIL | 1.45 | 24908.39 |
ROOM_2_FLR_3 PTAC HEATING COIL | 1.44 | 24693.91 |
ROOM_3_MULT19_FLR_3 PTAC HEATING COIL | 8.38 | 158710.41 |
ROOM_4_MULT19_FLR_3 PTAC HEATING COIL | 8.52 | 159287.15 |
ROOM_5_FLR_3 PTAC HEATING COIL | 1.26 | 20998.11 |
ROOM_6_FLR_3 PTAC HEATING COIL | 1.25 | 20697.72 |
PTAC_3 PTAC HEATING COIL | 2.14 | 42025.03 |
ROOM_1_FLR_6 PTAC HEATING COIL | 0.400114 | 6844.81 |
ROOM_2_FLR_6 PTAC HEATING COIL | 0.397401 | 6781.29 |
ROOM_3_MULT9_FLR_6 PTAC HEATING COIL | 1.78 | 31790.13 |
PTAC_6 PTAC HEATING COIL | 1.35 | 23648.34 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3_PTAC_SUPPLY FAN | 1.45 |
ROOM_2_FLR_3_PTAC_SUPPLY FAN | 1.44 |
ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | 8.38 |
ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | 8.52 |
ROOM_5_FLR_3_PTAC_SUPPLY FAN | 1.26 |
ROOM_6_FLR_3_PTAC_SUPPLY FAN | 1.25 |
PTAC_3_PTAC_SUPPLY FAN | 2.14 |
ROOM_1_FLR_6_PTAC_SUPPLY FAN | 0.400114 |
ROOM_2_FLR_6_PTAC_SUPPLY FAN | 0.397401 |
ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | 1.78 |
PTAC_6_PTAC_SUPPLY FAN | 1.35 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_FLR_1 | 3.49 | 3.49 | 8.75 | 3.49 | 8.72 | 8.72 | 0.300000 | 0.400010 | 8.72 |
VAV_FLR_6 | 3.15 | 3.15 | 6.71 | 3.15 | 6.71 | 6.71 | 0.300000 | 0.469792 | 6.71 |
VAV_FLR_0 | 1.13 | 1.13 | 3.77 | 1.13 | 3.77 | 3.77 | 1.00 | 0.300000 | 3.77 |
PSZ_LAUNDRY | 4.27 | 4.27 | 4.27 | 4.27 | 4.27 | 4.27 | 1.00 | 1.00 | 4.27 |
PSZ_CAFE | 2.24 | 2.24 | 2.24 | 2.24 | 2.24 | 2.24 | 1.00 | 1.00 | 2.24 |
PSZ_KITCHEN | 2.97 | 2.97 | 2.97 | 2.97 | 2.97 | 2.97 | 1.00 | 1.00 | 2.97 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_FLR_1_OA_CONTROLLER | 8.72 | |
VAV_FLR_6_OA_CONTROLLER | 6.71 | |
VAV_FLR_0_OA_CONTROLLER | 3.77 | |
PSZ_LAUNDRY_OA_CONTROLLER | 4.27 | 0.000000 |
PSZ_CAFE_OA_CONTROLLER | 2.24 | 0.676389 |
PSZ_KITCHEN_OA_CONTROLLER | 2.97 | 0.367350 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
VAV_FLR_1 COOLING COIL | 8.72 | 189608.58 | 0.744821 | 2.91 | 63196.54 | 0.744821 |
VAV_FLR_6 COOLING COIL | 6.71 | 162016.44 | 0.710017 | 2.24 | 54000.08 | 0.710017 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_FLR_1 FAN | 8.72 |
VAV_FLR_6 FAN | 6.71 |
VAV_FLR_0 SZVAV FAN | 2.52 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | User-Specified Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | Design Size Minimum Supply Air Temperature [C] | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size Maximum Supply Air Temperature [C] | User-Specified Supplemental Heating Coil Nominal Capacity [W] | |
VAV_FLR_0_UNITARY_PACKAGE_DX | 2.52 | 2.52 | 2.52 | 0.754680 | 66436.07 | 33057.48 | 1.00 | 7.35 | 12.89 | 32.11 | |||
PSZ_LAUNDRY_UNITARY_PACKAGE_DX | 4.27 | 4.27 | 4.27 | 72144.62 | 47371.07 | 1.00 | 4.27 | 32.11 | 70703.09 | ||||
PSZ_CAFE_UNITARY_PACKAGE_DX | 2.24 | 2.24 | 2.24 | 49947.54 | 32443.79 | 1.00 | 2.24 | 32.11 | 48423.56 | ||||
PSZ_KITCHEN_UNITARY_PACKAGE_DX | 2.97 | 2.97 | 2.97 | 63140.63 | 40869.05 | 1.00 | 2.97 | 32.11 | 60998.59 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | Design Size Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
VAV_FLR_0 COOLING COIL | 2.52 | 3.77 | 1.26 | 2.52 | 66436.07 | 33218.04 | 0.701104 | 0.800670 | 0.800670 |
PSZ_LAUNDRY HP COOLING COIL | 4.27 | 2.14 | 2.85 | 72144.62 | 36072.31 | 0.800310 | 0.800310 | ||
PSZ_CAFE HP COOLING COIL | 2.24 | 1.12 | 1.49 | 49947.54 | 24973.77 | 0.735900 | 0.735900 | ||
PSZ_KITCHEN HP COOLING COIL | 2.97 | 1.49 | 1.98 | 63140.63 | 31570.31 | 0.753290 | 0.753290 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | 4.27 | 6928.37 |
PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | 2.24 | 3722.38 |
PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | 2.97 | 4817.96 |
Design Size Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | Design Size Speed 2 Gross Rated Heating Capacity [W] | Design Size Speed 1 Gross Rated Heating Capacity [W] | Design Size Resistive Defrost Heater Capacity | |
PSZ_LAUNDRY HEATING COIL | 4.27 | 2.14 | 70703.09 | 35351.55 | 0.000000 |
PSZ_CAFE HEATING COIL | 2.24 | 1.12 | 48423.56 | 24211.78 | 0.000000 |
PSZ_KITCHEN HEATING COIL | 2.97 | 1.49 | 60998.59 | 30499.29 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 6.92 | 4.22 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 6.92 | 4.23 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 30.00 | 18.31 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 12.69 | 7.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 60.57 | 36.97 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 60.57 | 36.97 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 57.04 | 30.28 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 53.08 | 32.40 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 11.068 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.448 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 16.146 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.906 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 16.146 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.906 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 16.146 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 21.526 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 8.611 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 11.301 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 15.069 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 20.449 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 13.993 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 22.063 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 15.069 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 82.889 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 15.069 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 82.889 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 12.917 | 516.346 | 2419.260 | 0.000 | 0.000 | 0.000 | 2948.522 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 21901.435 | 11.068 | 205.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21901.435 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1082.924 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1082.924 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1254.030 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1254.030 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 2651.846 | 16.146 | 999.942 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2651.846 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 815.983 | 8.611 | 399.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 815.983 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2846.047 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2846.047 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 18305.540 | 13.993 | 43.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18305.540 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 300.928 | 12.271 | 200.619 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 300.928 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 301.011 | 12.271 | 200.674 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 301.011 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2095.757 | 5.382 | 100.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2095.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 301.011 | 12.271 | 200.674 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 301.011 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4997.899 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4997.899 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4997.899 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4997.899 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1334.351 | 12.917 | 60.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1334.351 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2218.035 | 5.382 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2218.035 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 493.000 | 4.772 | 22.169 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 493.000 | 493.000 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 365.000 | 3.533 | 16.413 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 365.000 | 365.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 200.0 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | NONRES_EXT_WALL_MID | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_TOP | 23 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | RES_EXT_WALL_MID | 25 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | RES_EXT_WALL_TOP | 26 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5000E-02 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
13 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
14 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
15 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
19 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
20 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
21 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
23 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
24 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
25 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
26 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
27 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
28 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
31 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
36 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
37 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
38 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
39 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
40 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
42 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
44 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
46 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 200.00000 | 200.00000 | 200.00000 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
21 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
22 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
23 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
24 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
25 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
26 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
27 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
28 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
29 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
30 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
31 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
32 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
33 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
34 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
35 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
36 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
37 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
38 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
39 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
40 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
41 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
42 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
43 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
44 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
45 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
46 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
47 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
48 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
49 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
50 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
51 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
52 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
53 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
54 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
55 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
56 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
57 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
58 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
59 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
60 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
61 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
62 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
63 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
64 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
65 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
66 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
67 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
68 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
69 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
70 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
71 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
72 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
73 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
74 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
75 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
76 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
77 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
78 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
79 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
80 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
81 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
82 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
83 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
84 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
85 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
86 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
87 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
88 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
89 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
90 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
91 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
108 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
109 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
110 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
111 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
112 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
113 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
114 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
115 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
116 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
117 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
118 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
119 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
120 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
121 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
122 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
123 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_0.25 | 37 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 | ||
2 | RESWINDOW_U_1.22_SHGC_0.25 | 38 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.10958 | 0.41397 | 0.41397 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 8000.0 | 0.975 | 0.8950 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone RETAIL_1_FLR_1 | 1.2500 |
4 | Zone RETAIL_2_FLR_1 | 1.2500 |
5 | Zone MECH_FLR_1 | 1.2500 |
6 | Zone STORAGE_FLR_1 | 1.2500 |
7 | Zone LAUNDRY_FLR_1 | 1.2500 |
8 | Zone CAFE_FLR_1 | 1.2500 |
9 | Zone LOBBY_FLR_1 | 1.2500 |
10 | Zone ROOM_1_FLR_3 | 1.2500 |
11 | Zone ROOM_2_FLR_3 | 1.2500 |
12 | Zone ROOM_3_MULT19_FLR_3 | 1.2500 |
13 | Zone ROOM_4_MULT19_FLR_3 | 1.2500 |
14 | Zone ROOM_5_FLR_3 | 1.2500 |
15 | Zone ROOM_6_FLR_3 | 1.2500 |
16 | Zone CORRIDOR_FLR_3 | 1.2500 |
17 | Zone ROOM_1_FLR_6 | 1.2500 |
18 | Zone ROOM_2_FLR_6 | 1.2500 |
19 | Zone ROOM_3_MULT9_FLR_6 | 1.2500 |
20 | Zone BANQUET_FLR_6 | 1.2500 |
21 | Zone DINING_FLR_6 | 1.2500 |
22 | Zone KITCHEN_FLR_6 | 1.2500 |
23 | Zone CORRIDOR_FLR_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone RETAIL_1_FLR_1 | 1.1500 |
4 | Zone RETAIL_2_FLR_1 | 1.1500 |
5 | Zone MECH_FLR_1 | 1.1500 |
6 | Zone STORAGE_FLR_1 | 1.1500 |
7 | Zone LAUNDRY_FLR_1 | 1.1500 |
8 | Zone CAFE_FLR_1 | 1.1500 |
9 | Zone LOBBY_FLR_1 | 1.1500 |
10 | Zone ROOM_1_FLR_3 | 1.1500 |
11 | Zone ROOM_2_FLR_3 | 1.1500 |
12 | Zone ROOM_3_MULT19_FLR_3 | 1.1500 |
13 | Zone ROOM_4_MULT19_FLR_3 | 1.1500 |
14 | Zone ROOM_5_FLR_3 | 1.1500 |
15 | Zone ROOM_6_FLR_3 | 1.1500 |
16 | Zone CORRIDOR_FLR_3 | 1.1500 |
17 | Zone ROOM_1_FLR_6 | 1.1500 |
18 | Zone ROOM_2_FLR_6 | 1.1500 |
19 | Zone ROOM_3_MULT9_FLR_6 | 1.1500 |
20 | Zone BANQUET_FLR_6 | 1.1500 |
21 | Zone DINING_FLR_6 | 1.1500 |
22 | Zone KITCHEN_FLR_6 | 1.1500 |
23 | Zone CORRIDOR_FLR_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 40672.76747 | 46773.68259 | 3.28122 | 3.77340 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 32.75350 | 5.61869E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 0.50000 | 4.31558E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 6273.85944 | 7214.93836 | 0.50616 | 0.58209 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2891.98402 | 3614.98002 | 0.23348 | 0.29185 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 4097.65428 | 4712.30242 | 0.33061 | 0.38020 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 38.27300 | 5.62717E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 701.02226 | 876.27782 | 5.65971E-002 | 9.17347E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 4810.55078 | 5532.13339 | 0.38804 | 0.44624 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 39.47000 | 5.62903E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1088.04225 | 1360.05281 | 8.78430E-002 | 0.10980 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 2624.68951 | 3018.39293 | 0.21172 | 0.24348 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 38.27300 | 5.62717E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1093.20244 | 1366.50305 | 8.82596E-002 | 0.11032 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 46039.98739 | 52945.98550 | 3.71406 | 4.27117 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | 39.07100 | 5.62841E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1543.26806 | 1929.08508 | 0.12459 | 0.15574 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 24119.58954 | 27737.52797 | 1.94757 | 2.23970 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 40.80000 | 5.63111E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7705.70051 | 9632.12564 | 0.62211 | 0.77764 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 76494.84837 | 87969.07563 | 6.17348 | 7.09950 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 14826.84463 | 18533.55579 | 1.19705 | 1.89399 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 15665.66683 | 18015.51685 | 1.26354 | 1.45307 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 39.29267 | 5.62876E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6255.46980 | 7819.33725 | 0.50507 | 0.63133 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 15570.70310 | 17906.30857 | 1.25588 | 1.44426 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6273.22273 | 7841.52841 | 0.50650 | 0.63312 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 90377.07703 | 103933.63858 | 7.28929 | 8.38268 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 36041.29822 | 45051.62277 | 2.91003 | 3.63753 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 91888.83149 | 105672.15622 | 7.41178 | 8.52354 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 36379.18029 | 45473.97537 | 2.93731 | 3.67164 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 13587.77698 | 15625.94353 | 1.09594 | 1.26033 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 37.07600 | 5.62532E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6219.89226 | 7774.86533 | 0.50219 | 0.62774 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 13459.44647 | 15478.36344 | 1.08559 | 1.24843 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 36.74350 | 5.62481E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6237.65613 | 7797.07016 | 0.50363 | 0.62953 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 23040.96398 | 26497.10857 | 1.85874 | 2.13755 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80000 | 5.63111E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 10255.17992 | 12818.97490 | 0.82796 | 1.03495 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50000 | 4.31558E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 4313.67384 | 4960.72491 | 0.34793 | 0.40011 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 39.47000 | 5.62903E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1975.56132 | 2469.45165 | 0.15951 | 0.19938 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 4284.42611 | 4927.09003 | 0.34557 | 0.39740 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 39.29267 | 5.62876E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1977.88524 | 2472.35654 | 0.15969 | 0.19962 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 19201.64328 | 22081.88977 | 1.54878 | 1.78110 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9596.23834 | 11995.29793 | 0.77481 | 0.96851 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 0.50000 | 4.31558E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 35362.81996 | 40667.24295 | 2.85627 | 3.28471 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 40.80000 | 5.63111E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7179.82382 | 8974.77977 | 0.57966 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 36865.93588 | 42395.82626 | 2.97764 | 3.42429 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 40.80000 | 5.63111E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7308.21033 | 9135.26292 | 0.59003 | 1.18780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 0.50000 | 4.31558E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31931.45792 | 36721.17661 | 2.58274 | 2.97015 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2602.86291 | 3253.57863 | 0.21012 | 0.36735 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 0.50000 | 4.31558E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 14556.74867 | 16740.26097 | 1.17429 | 1.35044 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80000 | 5.63111E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 7678.76054 | 9598.45067 | 0.61995 | 0.77493 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 0.50000 | 4.31558E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_FLR_1 | Cooling | Sensible | 158606.87 | 8.71780 | 8.71780 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_FLR_1 | Heating | Sensible | 33991.92 | 2.49770 | 2.49770 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 |
3 | VAV_FLR_6 | Cooling | Sensible | 140285.87 | 6.70900 | 6.70900 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_FLR_6 | Heating | Sensible | 32330.11 | 2.37559 | 2.37559 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | VAV_FLR_0 | Cooling | Sensible | 54268.09 | 3.77340 | 3.77340 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | VAV_FLR_0 | Heating | Sensible | 29670.03 | 0.85446 | 0.85446 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ_LAUNDRY | Cooling | Sensible | 52127.27 | 4.27117 | 4.27117 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
8 | PSZ_LAUNDRY | Heating | Sensible | 1900.80 | 0.15574 | 0.15574 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 |
9 | PSZ_CAFE | Cooling | Sensible | 39799.85 | 2.23970 | 2.23970 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ_CAFE | Heating | Sensible | 24722.49 | 0.77764 | 0.77764 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 |
11 | PSZ_KITCHEN | Cooling | Sensible | 42402.25 | 2.97015 | 2.97015 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ_KITCHEN | Heating | Sensible | 12755.79 | 0.36735 | 0.36735 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 3.77340 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.39961 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 1.13202 |
5 | AirTerminal:SingleDuct:ParallelPIU:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.58209 |
6 | AirTerminal:SingleDuct:ParallelPIU:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.58209 |
7 | AirTerminal:SingleDuct:ParallelPIU:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.13609 |
8 | AirTerminal:SingleDuct:ParallelPIU:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.30000 |
9 | Fan:ConstantVolume | RETAIL_1_FLR_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.58209 |
10 | Coil:Heating:Electric | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11425.43849 |
11 | AirTerminal:SingleDuct:ParallelPIU:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.38020 |
12 | AirTerminal:SingleDuct:ParallelPIU:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.38020 |
13 | AirTerminal:SingleDuct:ParallelPIU:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.24128 |
14 | AirTerminal:SingleDuct:ParallelPIU:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.37500 |
15 | Fan:ConstantVolume | RETAIL_2_FLR_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.38020 |
16 | Coil:Heating:Electric | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8247.60408 |
17 | AirTerminal:SingleDuct:ParallelPIU:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.44624 |
18 | AirTerminal:SingleDuct:ParallelPIU:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.44624 |
19 | Fan:ConstantVolume | MECH_FLR_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.44624 |
20 | Coil:Heating:Electric | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8758.94436 |
21 | AirTerminal:SingleDuct:ParallelPIU:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 0.24348 |
22 | AirTerminal:SingleDuct:ParallelPIU:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 0.24348 |
23 | AirTerminal:SingleDuct:ParallelPIU:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.23725 |
24 | AirTerminal:SingleDuct:ParallelPIU:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.36900 |
25 | Fan:ConstantVolume | STORAGE_FLR_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 0.24348 |
26 | Coil:Heating:Electric | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5240.62323 |
27 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LAUNDRY_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.27117 |
28 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CAFE_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.23970 |
29 | AirTerminal:SingleDuct:ParallelPIU:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 7.09950 |
30 | AirTerminal:SingleDuct:ParallelPIU:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 7.09950 |
31 | AirTerminal:SingleDuct:ParallelPIU:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.26678 |
32 | AirTerminal:SingleDuct:ParallelPIU:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.41500 |
33 | Fan:ConstantVolume | LOBBY_FLR_1 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 7.09950 |
34 | Coil:Heating:Electric | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 162123.21237 |
35 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.45307 |
36 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.45307 |
37 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.45307 |
38 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17350E-002 |
39 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17350E-002 |
40 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17350E-002 |
41 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_3 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.22110 |
42 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.45307 |
43 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 24908.39218 |
44 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80004 |
45 | Coil:Heating:DX:SingleSpeed | ROOM_1_FLR_3 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.45307 |
46 | Coil:Heating:DX:SingleSpeed | ROOM_1_FLR_3 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 24908.39218 |
47 | Fan:OnOff | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.45307 |
48 | Coil:Heating:Electric | ROOM_1_FLR_3_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 9237.59048 |
49 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.44426 |
50 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.44426 |
51 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.44426 |
52 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17278E-002 |
53 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17278E-002 |
54 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17278E-002 |
55 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_3 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.22110 |
56 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.44426 |
57 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 24693.91198 |
58 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80095 |
59 | Coil:Heating:DX:SingleSpeed | ROOM_2_FLR_3 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.44426 |
60 | Coil:Heating:DX:SingleSpeed | ROOM_2_FLR_3 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 24693.91198 |
61 | Fan:OnOff | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.44426 |
62 | Coil:Heating:Electric | ROOM_2_FLR_3_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 9259.61507 |
63 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT19_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.38268 |
64 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT19_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 8.38268 |
65 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT19_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 8.38268 |
66 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.83707 |
67 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.83707 |
68 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.83707 |
69 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT19_FLR_3 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.22110 |
70 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 8.38268 |
71 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 158710.41437 |
72 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79845 |
73 | Coil:Heating:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 8.38268 |
74 | Coil:Heating:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 158710.41437 |
75 | Fan:OnOff | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 8.38268 |
76 | Coil:Heating:Electric | ROOM_3_MULT19_FLR_3_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 64283.77507 |
77 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_4_MULT19_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.52354 |
78 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_4_MULT19_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 8.52354 |
79 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_4_MULT19_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 8.52354 |
80 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.83730 |
81 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.83730 |
82 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.83730 |
83 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_4_MULT19_FLR_3 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.22110 |
84 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 8.52354 |
85 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 159287.15360 |
86 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80067 |
87 | Coil:Heating:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 8.52354 |
88 | Coil:Heating:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 159287.15360 |
89 | Fan:OnOff | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 8.52354 |
90 | Coil:Heating:Electric | ROOM_4_MULT19_FLR_3_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 64711.38560 |
91 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_5_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26033 |
92 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_5_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26033 |
93 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_5_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.26033 |
94 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17350E-002 |
95 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17350E-002 |
96 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17350E-002 |
97 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_5_FLR_3 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.22110 |
98 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.26033 |
99 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 20998.11036 |
100 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80029 |
101 | Coil:Heating:DX:SingleSpeed | ROOM_5_FLR_3 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.26033 |
102 | Coil:Heating:DX:SingleSpeed | ROOM_5_FLR_3 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 20998.11036 |
103 | Fan:OnOff | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.26033 |
104 | Coil:Heating:Electric | ROOM_5_FLR_3_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 9193.11931 |
105 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_6_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24843 |
106 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_6_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24843 |
107 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_6_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24843 |
108 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17278E-002 |
109 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17278E-002 |
110 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17278E-002 |
111 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_6_FLR_3 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.22110 |
112 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.24843 |
113 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 20697.71592 |
114 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80009 |
115 | Coil:Heating:DX:SingleSpeed | ROOM_6_FLR_3 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.24843 |
116 | Coil:Heating:DX:SingleSpeed | ROOM_6_FLR_3 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 20697.71592 |
117 | Fan:OnOff | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.24843 |
118 | Coil:Heating:Electric | ROOM_6_FLR_3_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 9215.15757 |
119 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.13755 |
120 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 2.13755 |
121 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 2.13755 |
122 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.47476 |
123 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.47476 |
124 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47476 |
125 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_3 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.11110 |
126 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 2.13755 |
127 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 42025.02621 |
128 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.78256 |
129 | Coil:Heating:DX:SingleSpeed | PTAC_3 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 2.13755 |
130 | Coil:Heating:DX:SingleSpeed | PTAC_3 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 42025.02621 |
131 | Fan:OnOff | PTAC_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 2.13755 |
132 | Coil:Heating:Electric | PTAC_3_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 23668.30263 |
133 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40011 |
134 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40011 |
135 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40011 |
136 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.54338E-002 |
137 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.54338E-002 |
138 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.54338E-002 |
139 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_1_FLR_6 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.22110 |
140 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40011 |
141 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6844.81369 |
142 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80076 |
143 | Coil:Heating:DX:SingleSpeed | ROOM_1_FLR_6 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40011 |
144 | Coil:Heating:DX:SingleSpeed | ROOM_1_FLR_6 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6844.81369 |
145 | Fan:OnOff | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40011 |
146 | Coil:Heating:Electric | ROOM_1_FLR_6_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 2824.00761 |
147 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39740 |
148 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39740 |
149 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39740 |
150 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.54319E-002 |
151 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.54319E-002 |
152 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.54319E-002 |
153 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_2_FLR_6 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.22110 |
154 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39740 |
155 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6781.28582 |
156 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
157 | Coil:Heating:DX:SingleSpeed | ROOM_2_FLR_6 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39740 |
158 | Coil:Heating:DX:SingleSpeed | ROOM_2_FLR_6 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 6781.28582 |
159 | Fan:OnOff | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39740 |
160 | Coil:Heating:Electric | ROOM_2_FLR_6_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 2826.87091 |
161 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT9_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.78110 |
162 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT9_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.78110 |
163 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT9_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.78110 |
164 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 9.91540E-002 |
165 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 9.91540E-002 |
166 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 9.91540E-002 |
167 | ZoneHVAC:PackagedTerminalHeatPump | ROOM_3_MULT9_FLR_6 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.22110 |
168 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.78110 |
169 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 31790.13192 |
170 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80098 |
171 | Coil:Heating:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.78110 |
172 | Coil:Heating:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 31790.13192 |
173 | Fan:OnOff | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.78110 |
174 | Coil:Heating:Electric | ROOM_3_MULT9_FLR_6_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14273.25796 |
175 | AirTerminal:SingleDuct:ParallelPIU:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 3.28471 |
176 | AirTerminal:SingleDuct:ParallelPIU:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 3.28471 |
177 | AirTerminal:SingleDuct:ParallelPIU:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.36161 |
178 | AirTerminal:SingleDuct:ParallelPIU:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.48000 |
179 | Fan:ConstantVolume | BANQUET_FLR_6 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 3.28471 |
180 | Coil:Heating:Electric | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 81312.22548 |
181 | AirTerminal:SingleDuct:ParallelPIU:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Primary Air Flow Rate [m3/s] | 3.42429 |
182 | AirTerminal:SingleDuct:ParallelPIU:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Secondary Air Flow Rate [m3/s] | 3.42429 |
183 | AirTerminal:SingleDuct:ParallelPIU:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Primary Air Flow Fraction | 0.34687 |
184 | AirTerminal:SingleDuct:ParallelPIU:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Minimum Primary Air Flow Fraction | 0.46000 |
185 | Fan:ConstantVolume | DINING_FLR_6 PIU FAN | Design Size Maximum Flow Rate [m3/s] | 3.42429 |
186 | Coil:Heating:Electric | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 82717.74900 |
187 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.97015 |
188 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35044 |
189 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35044 |
190 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35044 |
191 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.12562 |
192 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.12562 |
193 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.12562 |
194 | ZoneHVAC:PackagedTerminalHeatPump | PTAC_6 | Design Size Maximum Supply Air Temperature from Supplemental Heater [C] | 32.11110 |
195 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.35044 |
196 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 23648.34383 |
197 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80054 |
198 | Coil:Heating:DX:SingleSpeed | PTAC_6 PTAC HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.35044 |
199 | Coil:Heating:DX:SingleSpeed | PTAC_6 PTAC HEATING COIL | Design Size Gross Rated Heating Capacity [W] | 23648.34383 |
200 | Fan:OnOff | PTAC_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.35044 |
201 | Coil:Heating:Electric | PTAC_6_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 12469.01484 |
202 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.48721 |
203 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.48721 |
204 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.75151 |
205 | AirLoopHVAC | VAV_FLR_1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.48721 |
206 | AirLoopHVAC | VAV_FLR_1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.71780 |
207 | AirLoopHVAC | VAV_FLR_1 | Adjusted Main Design Air Flow Rate [m3/s] | 8.71780 |
208 | AirLoopHVAC | VAV_FLR_1 | User Heating Air Flow Ratio [] | 0.30000 |
209 | AirLoopHVAC | VAV_FLR_1 | Calculated Heating Air Flow Ratio [] | 0.40001 |
210 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.15183 |
211 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.15183 |
212 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.70900 |
213 | AirLoopHVAC | VAV_FLR_6 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.15183 |
214 | AirLoopHVAC | VAV_FLR_6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.70900 |
215 | AirLoopHVAC | VAV_FLR_6 | Adjusted Main Design Air Flow Rate [m3/s] | 6.70900 |
216 | AirLoopHVAC | VAV_FLR_6 | User Heating Air Flow Ratio [] | 0.30000 |
217 | AirLoopHVAC | VAV_FLR_6 | Calculated Heating Air Flow Ratio [] | 0.46979 |
218 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13202 |
219 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13202 |
220 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.77340 |
221 | AirLoopHVAC | VAV_FLR_0 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13202 |
222 | AirLoopHVAC | VAV_FLR_0 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.77340 |
223 | AirLoopHVAC | VAV_FLR_0 | Adjusted Main Design Air Flow Rate [m3/s] | 3.77340 |
224 | AirLoopHVAC | VAV_FLR_0 | User Heating Air Flow Ratio [] | 1.00000 |
225 | AirLoopHVAC | VAV_FLR_0 | Calculated Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.27117 |
227 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.27117 |
228 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.27117 |
229 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Heating Design Air Flow Rate [m3/s] | 4.27117 |
230 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.27117 |
231 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Main Design Air Flow Rate [m3/s] | 4.27117 |
232 | AirLoopHVAC | PSZ_LAUNDRY | User Heating Air Flow Ratio [] | 1.00000 |
233 | AirLoopHVAC | PSZ_LAUNDRY | Calculated Heating Air Flow Ratio [] | 1.00000 |
234 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.23970 |
235 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.23970 |
236 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.23970 |
237 | AirLoopHVAC | PSZ_CAFE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.23970 |
238 | AirLoopHVAC | PSZ_CAFE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.23970 |
239 | AirLoopHVAC | PSZ_CAFE | Adjusted Main Design Air Flow Rate [m3/s] | 2.23970 |
240 | AirLoopHVAC | PSZ_CAFE | User Heating Air Flow Ratio [] | 1.00000 |
241 | AirLoopHVAC | PSZ_CAFE | Calculated Heating Air Flow Ratio [] | 1.00000 |
242 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.97015 |
243 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.97015 |
244 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.97015 |
245 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Heating Design Air Flow Rate [m3/s] | 2.97015 |
246 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.97015 |
247 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Main Design Air Flow Rate [m3/s] | 2.97015 |
248 | AirLoopHVAC | PSZ_KITCHEN | User Heating Air Flow Ratio [] | 1.00000 |
249 | AirLoopHVAC | PSZ_KITCHEN | Calculated Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | VAV_FLR_1 | Design Supply Air Flow Rate [m3/s] | 8.71780 |
251 | AirLoopHVAC | VAV_FLR_6 | Design Supply Air Flow Rate [m3/s] | 6.70900 |
252 | AirLoopHVAC | VAV_FLR_0 | Design Supply Air Flow Rate [m3/s] | 3.77340 |
253 | AirLoopHVAC | PSZ_LAUNDRY | Design Supply Air Flow Rate [m3/s] | 4.27117 |
254 | AirLoopHVAC | PSZ_CAFE | Design Supply Air Flow Rate [m3/s] | 2.23970 |
255 | AirLoopHVAC | PSZ_KITCHEN | Design Supply Air Flow Rate [m3/s] | 2.97015 |
256 | Controller:OutdoorAir | VAV_FLR_1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.71780 |
257 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 8.71780 |
258 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 189608.57806 |
259 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74482 |
260 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.90564 |
261 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 63196.53907 |
262 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74482 |
263 | Coil:Heating:Electric | VAV_FLR_1 HEATING COIL | Design Size Nominal Capacity [W] | 35592.87807 |
264 | Fan:VariableVolume | VAV_FLR_1 FAN | Design Size Maximum Flow Rate [m3/s] | 8.71780 |
265 | Controller:OutdoorAir | VAV_FLR_6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.70900 |
266 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.70900 |
267 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 162016.43556 |
268 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71002 |
269 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.23611 |
270 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 54000.07797 |
271 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71002 |
272 | Coil:Heating:Electric | VAV_FLR_6 HEATING COIL | Design Size Nominal Capacity [W] | 27391.38948 |
273 | Fan:VariableVolume | VAV_FLR_6 FAN | Design Size Maximum Flow Rate [m3/s] | 6.70900 |
274 | Controller:OutdoorAir | VAV_FLR_0_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.77340 |
275 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.51560 |
276 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.51560 |
277 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Cooling Supply Air Flow Rate [m3/s] | 2.51560 |
278 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75468 |
279 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 2.51560 |
280 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.77340 |
281 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.25780 |
282 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.51560 |
283 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 66436.07000 |
284 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 33218.03500 |
285 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | Design Size Speed 2 Rated Sensible Heat Ratio | 0.70110 |
286 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80067 |
287 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80067 |
288 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 66436.07000 |
289 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33057.48321 |
290 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
291 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Minimum Supply Air Temperature [C] | 7.35195 |
292 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
293 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
294 | Coil:Heating:Electric | VAV_FLR_0 HEATING COIL | Design Size Nominal Capacity [W] | 33057.48321 |
295 | Fan:VariableVolume | VAV_FLR_0 SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 2.51560 |
296 | Controller:OutdoorAir | PSZ_LAUNDRY_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.27117 |
297 | Controller:OutdoorAir | PSZ_LAUNDRY_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.00000 |
298 | Fan:SystemModel | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.27117 |
299 | Fan:SystemModel | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 6928.37361 |
300 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.27117 |
301 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.27117 |
302 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.27117 |
303 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.27117 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.27117 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.13559 |
306 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.84745 |
307 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 72144.62000 |
308 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 36072.31000 |
309 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80031 |
310 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80031 |
311 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 72144.62000 |
312 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 47371.07285 |
313 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
314 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 70703.09380 |
315 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
316 | Coil:Heating:DX:MultiSpeed | PSZ_LAUNDRY HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 4.27117 |
317 | Coil:Heating:DX:MultiSpeed | PSZ_LAUNDRY HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.13559 |
318 | Coil:Heating:DX:MultiSpeed | PSZ_LAUNDRY HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 70703.09380 |
319 | Coil:Heating:DX:MultiSpeed | PSZ_LAUNDRY HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 35351.54690 |
320 | Coil:Heating:DX:MultiSpeed | PSZ_LAUNDRY HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
321 | Coil:Heating:Electric | PSZ_LAUNDRY_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 70703.09380 |
322 | Controller:OutdoorAir | PSZ_CAFE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.23970 |
323 | Controller:OutdoorAir | PSZ_CAFE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.67639 |
324 | Fan:SystemModel | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.23970 |
325 | Fan:SystemModel | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3722.37730 |
326 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.23970 |
327 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.23970 |
328 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.23970 |
329 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.23970 |
330 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.23970 |
331 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.11985 |
332 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.49313 |
333 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49947.54000 |
334 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24973.77000 |
335 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73590 |
336 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73590 |
337 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49947.54000 |
338 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32443.78594 |
339 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
340 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 48423.56111 |
341 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
342 | Coil:Heating:DX:MultiSpeed | PSZ_CAFE HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 2.23970 |
343 | Coil:Heating:DX:MultiSpeed | PSZ_CAFE HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.11985 |
344 | Coil:Heating:DX:MultiSpeed | PSZ_CAFE HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 48423.56111 |
345 | Coil:Heating:DX:MultiSpeed | PSZ_CAFE HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 24211.78055 |
346 | Coil:Heating:DX:MultiSpeed | PSZ_CAFE HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
347 | Coil:Heating:Electric | PSZ_CAFE_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 48423.56111 |
348 | Controller:OutdoorAir | PSZ_KITCHEN_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.97015 |
349 | Controller:OutdoorAir | PSZ_KITCHEN_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.36735 |
350 | Fan:SystemModel | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.97015 |
351 | Fan:SystemModel | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 4817.95889 |
352 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.97015 |
353 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.97015 |
354 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.97015 |
355 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.97015 |
356 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN HP COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.97015 |
357 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN HP COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.48508 |
358 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN HP COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.98010 |
359 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN HP COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 63140.63000 |
360 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN HP COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31570.31500 |
361 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN HP COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75329 |
362 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN HP COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75329 |
363 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63140.63000 |
364 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 40869.05463 |
365 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
366 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | User-Specified Supplemental Heating Coil Nominal Capacity [W] | 60998.58900 |
367 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
368 | Coil:Heating:DX:MultiSpeed | PSZ_KITCHEN HEATING COIL | Design Size Speed 2 Rated Air Flow Rate [m3/s] | 2.97015 |
369 | Coil:Heating:DX:MultiSpeed | PSZ_KITCHEN HEATING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.48508 |
370 | Coil:Heating:DX:MultiSpeed | PSZ_KITCHEN HEATING COIL | Design Size Speed 2 Gross Rated Heating Capacity [W] | 60998.58900 |
371 | Coil:Heating:DX:MultiSpeed | PSZ_KITCHEN HEATING COIL | Design Size Speed 1 Gross Rated Heating Capacity [W] | 30499.29450 |
372 | Coil:Heating:DX:MultiSpeed | PSZ_KITCHEN HEATING COIL | Design Size Resistive Defrost Heater Capacity | 0.00000 |
373 | Coil:Heating:Electric | PSZ_KITCHEN_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 60998.58900 |
374 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
375 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
376 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
377 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
378 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | 23780.7 | 2.60 | 8.86 | 9.40 | 8.89 | 8.90 |
2 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | 23573.1 | 2.60 | 8.86 | 9.39 | 8.89 | 8.89 |
3 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 152202.6 | 2.64 | 9.00 | 9.55 | 9.04 | 9.12 |
4 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 152670.3 | 2.63 | 8.99 | 9.53 | 9.02 | 9.09 |
5 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | 20020.1 | 2.58 | 8.82 | 9.35 | 8.85 | 8.83 |
6 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | 19729.0 | 2.58 | 8.81 | 9.34 | 8.84 | 8.82 |
7 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | 40365.3 | 2.65 | 9.06 | 9.61 | 9.09 | 9.19 |
8 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | 6534.3 | 2.60 | 8.86 | 9.39 | 8.89 | 8.89 |
9 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | 6472.9 | 2.59 | 8.85 | 9.39 | 8.88 | 8.89 |
10 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 30407.7 | 2.61 | 8.92 | 9.46 | 8.95 | 8.99 |
11 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | 22600.3 | 2.61 | 8.89 | 9.43 | 8.92 | 8.95 |
12 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | 63476.3 | 10.28 | 10.28 | |||
13 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY HP COOLING COIL | 68796.4 | 9.45 | 9.45 | |||
14 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE HP COOLING COIL | 48184.2 | 10.15 | 10.15 | |||
15 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN HP COOLING COIL | 60804.1 | 10.08 | 10.08 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {W} | Low Temperature Heating (net) Rating Capacity {W} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:SingleSpeed | ROOM_1_FLR_3 PTAC HEATING COIL | 26062.2 | 14497.4 | 6.91 | 4 |
2 | Coil:Heating:DX:SingleSpeed | ROOM_2_FLR_3 PTAC HEATING COIL | 25840.7 | 14375.5 | 6.91 | 4 |
3 | Coil:Heating:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC HEATING COIL | 165385.2 | 91696.8 | 6.33 | 4 |
4 | Coil:Heating:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC HEATING COIL | 166071.5 | 92115.4 | 6.32 | 4 |
5 | Coil:Heating:DX:SingleSpeed | ROOM_5_FLR_3 PTAC HEATING COIL | 21998.2 | 12248.9 | 6.90 | 4 |
6 | Coil:Heating:DX:SingleSpeed | ROOM_6_FLR_3 PTAC HEATING COIL | 21688.2 | 12078.4 | 6.90 | 4 |
7 | Coil:Heating:DX:SingleSpeed | PTAC_3 PTAC HEATING COIL | 43728.9 | 24217.0 | 6.96 | 4 |
8 | Coil:Heating:DX:SingleSpeed | ROOM_1_FLR_6 PTAC HEATING COIL | 7162.5 | 3984.5 | 6.91 | 4 |
9 | Coil:Heating:DX:SingleSpeed | ROOM_2_FLR_6 PTAC HEATING COIL | 7096.8 | 3948.3 | 6.91 | 4 |
10 | Coil:Heating:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC HEATING COIL | 33206.0 | 18446.0 | 6.93 | 4 |
11 | Coil:Heating:DX:SingleSpeed | PTAC_6 PTAC HEATING COIL | 24721.3 | 13741.5 | 6.92 | 4 |
12 | Coil:Heating:DX:MultiSpeed | PSZ_LAUNDRY HEATING COIL | 74091.7 | 41264.7 | 7.39 | 2 |
13 | Coil:Heating:DX:MultiSpeed | PSZ_CAFE HEATING COIL | 50214.2 | 27731.4 | 7.83 | 2 |
14 | Coil:Heating:DX:MultiSpeed | PSZ_KITCHEN HEATING COIL | 63369.4 | 35048.1 | 7.64 | 2 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | N/A | N/A | 183188.20 | 625064.10 | 11.09 | 3.03 | 3.25 | 3.23 | 3.35 | 10.34 | 11.07 | 11.02 | 11.45 | 9.1539 | 7.2748 | 4.8812 | 2.0246 |
2 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | N/A | N/A | 157102.74 | 536056.80 | 11.28 | 3.07 | 3.30 | 3.29 | 3.39 | 10.49 | 11.27 | 11.22 | 11.56 | 7.0446 | 5.5783 | 3.7411 | 1.6056 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 200.000 | 200.000 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 6.92 | 11.15 | 6.92 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 4.22 | 4.22 | 4.22 | 180.00 | 90.00 | 3.02 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 6.92 | 11.15 | 6.92 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 4.23 | 4.23 | 4.23 | 0.00 | 90.00 | 3.02 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 90.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 90.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 4.04 | 6.50 | 4.04 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 2.47 | 2.47 | 2.47 | 0.00 | 90.00 | 1.76 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 4.04 | 6.50 | 4.04 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 2.46 | 2.46 | 2.46 | 180.00 | 90.00 | 1.76 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 12.69 | 20.44 | 12.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 7.75 | 7.75 | 7.75 | 180.00 | 90.00 | 5.53 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.57 | 97.55 | 60.57 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 36.97 | 36.97 | 36.97 | 0.00 | 90.00 | 26.40 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.57 | 97.55 | 60.57 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 36.97 | 36.97 | 36.97 | 0.00 | 90.00 | 26.40 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 16.08 | 21.37 | 16.08 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 32.31 | 52.03 | 32.31 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 19.72 | 19.72 | 19.72 | 90.00 | 90.00 | 14.08 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 9.81 | 15.79 | 9.81 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 5.99 | 5.99 | 5.99 | 0.00 | 90.00 | 4.27 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 32.31 | 52.03 | 32.31 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.25 | N/A | 6.926 | No | 19.72 | 19.72 | 19.72 | 180.00 | 90.00 | 14.08 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.2805053490E-002 | 1.6607471329E-002 | Pass | Pass | 1.7915891604E-002 | 3.4549802109E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6939753719E-002 | 7.9795148496E-002 | Pass | Pass | 0.1811271056 | 0.6505331677 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.1407670988E-002 | 2.5107558533E-002 | Pass | Pass | 4.6894148200E-003 | 4.2215256353E-003 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.2796155247E-002 | 2.2482796533E-002 | Pass | Pass | 3.6017853068E-003 | 3.6171561116E-003 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0229776369E-002 | 1.3390851020E-002 | Pass | Pass | 0.1779747356 | 0.5548863799 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.0394001492E-005 | 4.5120797656E-005 | Pass | Pass | 2.1061540377E-002 | 5.9462708896E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.9947491130E-002 | 8.4011258501E-002 | Pass | Pass | 3.1611683318E-002 | 4.2362230250E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.6459517537E-002 | 3.6124303369E-002 | Pass | Pass | 5.4619434120E-003 | 6.1985600113E-003 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.6996072437E-002 | 0.2284359536 | Pass | Pass | 0.3803454465 | 2.1758937586 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.3762250017E-002 | 0.2701019156 | Pass | Pass | 0.2643314393 | 0.8542060247 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.5435461608E-002 | 7.5041726946E-002 | Pass | Pass | 6.0766975990E-002 | 0.1546680075 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.8683967832E-002 | 9.3063814100E-002 | Pass | Pass | 0.3670552382 | 1.8636633684 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.9850954164E-002 | 0.2567719141 | Pass | Pass | 0.2428932419 | 1.2006936072 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.3286295774E-002 | 9.0284959390E-002 | Pass | Pass | 0.2688013018 | 1.2931095648 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.5894792101E-002 | 1.6416130686E-002 | Pass | Pass | 0.1057195019 | 0.3741325478 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.3369081534E-002 | 0.2781121682 | Pass | Pass | 0.3372670679 | 1.5471493801 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.5975589078E-002 | 0.3036431246 | Pass | Pass | 0.1612144807 | 0.4576118850 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.5699172472E-002 | 0.2731249032 | Pass | Pass | 0.1743969847 | 0.4852321509 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.2843505199E-002 | 8.9922546184E-002 | Pass | Pass | 8.9916823016E-003 | 1.9682315924E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.1377764020E-002 | 8.7010637661E-002 | Pass | Pass | 8.4638523809E-003 | 1.8054979457E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1761537230E-003 | 2.0669999106E-003 | Pass | Pass | 2.6765242571E-002 | 5.0893247144E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.2244786431E-002 | 4.0318333931E-002 | Pass | Pass | 8.6041512847E-002 | 0.4549014560 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4160.32 | 45.43 | 490.59 | 2098.71 | -NAN | -NAN |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.06 | 64.62 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.05 | 64.61 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 847.14 | 526.04 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 847.37 | 526.16 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.06 | 64.62 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.05 | 64.61 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 70.60 | 43.85 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 26.01 | 16.14 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 26.02 | 16.16 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 70.60 | 43.85 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 13.94 | 8.65 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 26.01 | 16.15 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 13.94 | 8.65 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 26.01 | 16.15 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 183.96 | 114.24 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 97.55 | 60.57 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 97.55 | 60.57 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 21.37 | 16.08 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 52.03 | 32.31 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 13.94 | 8.65 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 17.65 | 10.96 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 15.79 | 9.81 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 52.03 | 32.31 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 6.926 | 0.251 | 0.277 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 6.926 | 0.251 | 0.277 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 6.926 | 0.251 | 0.277 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 6.926 | 0.251 | 0.277 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 6.926 | 0.251 | 0.277 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 6.926 | 0.251 | 0.277 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 6.926 | 0.251 | 0.277 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 4.22 | 0.00 | 0.00 | 4.22 | 321.10 | 6.926 | 0.251 | 0.277 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 4.23 | 0.00 | 0.00 | 4.23 | 321.20 | 6.926 | 0.251 | 0.277 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 6.926 | 0.251 | 0.277 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 6.926 | 0.251 | 0.277 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 6.926 | 0.251 | 0.277 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 6.926 | 0.251 | 0.277 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 26.76 | 6.926 | 0.251 | 0.277 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 2.47 | 0.00 | 0.00 | 2.47 | 9.86 | 6.926 | 0.251 | 0.277 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 2.46 | 0.00 | 0.00 | 2.46 | 9.86 | 6.926 | 0.251 | 0.277 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 26.76 | 6.926 | 0.251 | 0.277 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 6.926 | 0.251 | 0.277 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 9.86 | 6.926 | 0.251 | 0.277 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 6.926 | 0.251 | 0.277 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 9.86 | 6.926 | 0.251 | 0.277 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.25 | 7.75 | 0.00 | 0.00 | 7.75 | 69.72 | 6.926 | 0.251 | 0.277 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 36.97 | 0.00 | 0.00 | 36.97 | 36.97 | 6.926 | 0.251 | 0.277 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 36.97 | 0.00 | 0.00 | 36.97 | 36.97 | 6.926 | 0.251 | 0.277 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 6.926 | 0.251 | 0.277 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 19.72 | 0.00 | 0.00 | 19.72 | 19.72 | 6.926 | 0.251 | 0.277 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 6.926 | 0.251 | 0.277 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 6.926 | 0.251 | 0.277 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 5.99 | 0.00 | 0.00 | 5.99 | 5.99 | 6.926 | 0.251 | 0.277 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.25 | 19.72 | 0.00 | 0.00 | 19.72 | 19.72 | 6.926 | 0.251 | 0.277 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1368.30 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
North Total or Average | 497.27 | 6.926 | 0.251 | 0.277 | |||||||||||||||||
Non-North Total or Average | 871.02 | 6.926 | 0.251 | 0.277 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 6.464 | 200.000 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.0679 | 1978.83 | 21901.44 | LightsWired | LTG_SCH_BASEMENT | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 241.03 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 16.1458 | 67.07 | 1082.92 | LightsWired | LTG_SCH_RETAIL | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 11.92 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 16.1458 | 77.67 | 1254.03 | LightsWired | LTG_SCH_RETAIL | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.80 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 16.1458 | 164.24 | 2651.85 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.18 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 8.6111 | 94.76 | 815.98 | LightsWired | LTG_SCH_STORAGE | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.98 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 15.0695 | 188.86 | 2846.05 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 31.32 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 13.9931 | 1308.19 | 18305.54 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 201.46 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 12.2708 | 156.09 | 1915.33 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 12.2708 | 156.07 | 1915.11 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 12.2708 | 1863.81 | 22870.56 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 297.14 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 12.2708 | 1864.32 | 22876.81 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 297.22 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 12.2708 | 156.09 | 1915.33 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 12.2708 | 156.07 | 1915.11 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 5.3819 | 1557.62 | 8383.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 92.26 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 12.2708 | 39.02 | 478.83 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.22 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 12.2708 | 39.02 | 478.78 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.22 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 12.2709 | 220.77 | 2709.10 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 35.20 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 15.0695 | 331.66 | 4997.90 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 55.00 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 15.0695 | 331.66 | 4997.90 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 55.00 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 12.9167 | 103.30 | 1334.35 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.68 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 5.3819 | 412.12 | 2218.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 24.41 |
Interior Lighting Total | 11.3147 | 11345.29 | 128367.98 | 764.46 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 20502.98 | AstronomicalClock | - | 83.79 | 83.79 | 322.47 | |
Exterior Lighting Total | 20502.98 | 322.47 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 24908.39 | 19927.59 | 4980.80 | 0.80 | 3.10 | |||
ROOM_2_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 24693.91 | 19778.54 | 4915.37 | 0.80 | 3.10 | |||
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 158710.41 | 126721.85 | 31988.56 | 0.80 | 3.10 | |||
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 159287.15 | 127535.69 | 31751.47 | 0.80 | 3.10 | |||
ROOM_5_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 20998.11 | 16804.55 | 4193.56 | 0.80 | 3.10 | |||
ROOM_6_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 20697.72 | 16560.04 | 4137.68 | 0.80 | 3.10 | |||
PTAC_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 42025.03 | 32886.99 | 9138.04 | 0.78 | 3.10 | |||
ROOM_1_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6844.81 | 5481.03 | 1363.78 | 0.80 | 3.10 | |||
ROOM_2_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6781.29 | 5429.47 | 1351.81 | 0.80 | 3.10 | |||
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 31790.13 | 25463.24 | 6326.89 | 0.80 | 3.10 | |||
PTAC_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 23648.34 | 18931.46 | 4716.88 | 0.80 | 3.10 | |||
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 189608.58 | 141224.51 | 48384.07 | 0.74 | 3.50 | |||
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 162016.44 | 115034.50 | 46981.93 | 0.71 | 3.50 | |||
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 66436.07 | 53193.37 | 13242.70 | 0.80 | 3.40 | |||
PSZ_LAUNDRY HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 72144.62 | 57738.06 | 14406.56 | 0.80 | 3.10 | |||
PSZ_CAFE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49947.54 | 36756.39 | 13191.15 | 0.74 | 3.20 | |||
PSZ_KITCHEN HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | 63140.63 | 47563.21 | 15577.42 | 0.75 | 3.20 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
ROOM_1_FLR_3 PTAC COOLING COIL | 23780.7 | 2.60 | 8.86 | 9.40 | 8.89 | 8.90 | |
ROOM_2_FLR_3 PTAC COOLING COIL | 23573.1 | 2.60 | 8.86 | 9.39 | 8.89 | 8.89 | |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 152202.6 | 2.64 | 9.00 | 9.55 | 9.04 | 9.12 | |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 152670.3 | 2.63 | 8.99 | 9.53 | 9.02 | 9.09 | |
ROOM_5_FLR_3 PTAC COOLING COIL | 20020.1 | 2.58 | 8.82 | 9.35 | 8.85 | 8.83 | |
ROOM_6_FLR_3 PTAC COOLING COIL | 19729.0 | 2.58 | 8.81 | 9.34 | 8.84 | 8.82 | |
PTAC_3 PTAC COOLING COIL | 40365.3 | 2.65 | 9.06 | 9.61 | 9.09 | 9.19 | |
ROOM_1_FLR_6 PTAC COOLING COIL | 6534.3 | 2.60 | 8.86 | 9.39 | 8.89 | 8.89 | |
ROOM_2_FLR_6 PTAC COOLING COIL | 6472.9 | 2.59 | 8.85 | 9.39 | 8.88 | 8.89 | |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 30407.7 | 2.61 | 8.92 | 9.46 | 8.95 | 8.99 | |
PTAC_6 PTAC COOLING COIL | 22600.3 | 2.61 | 8.89 | 9.43 | 8.92 | 8.95 | |
VAV_FLR_1 COOLING COIL | 183188.2 | 3.03 | 10.34 | N/A | N/A | 11.09 | |
VAV_FLR_6 COOLING COIL | 157102.7 | 3.07 | 10.49 | N/A | N/A | 11.28 | |
VAV_FLR_0 COOLING COIL | 63476.3 | 10.28 | 10.28 | ||||
PSZ_LAUNDRY HP COOLING COIL | 68796.4 | 9.45 | 9.45 | ||||
PSZ_CAFE HP COOLING COIL | 48184.2 | 10.15 | 10.15 | ||||
PSZ_KITCHEN HP COOLING COIL | 60804.1 | 10.08 | 10.08 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
ROOM_1_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_2_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_5_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_6_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PTAC_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_1_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_2_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PTAC_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_LAUNDRY HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_CAFE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_KITCHEN HP COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
ROOM_1_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 26062.2 | 14497.4 | 6.91 | 4 |
ROOM_2_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 25840.7 | 14375.5 | 6.91 | 4 |
ROOM_3_MULT19_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 165385.2 | 91696.8 | 6.33 | 4 |
ROOM_4_MULT19_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 166071.5 | 92115.4 | 6.32 | 4 |
ROOM_5_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 21998.2 | 12248.9 | 6.90 | 4 |
ROOM_6_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 21688.2 | 12078.4 | 6.90 | 4 |
PTAC_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 43728.9 | 24217.0 | 6.96 | 4 |
ROOM_1_FLR_6 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 7162.5 | 3984.5 | 6.91 | 4 |
ROOM_2_FLR_6 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 7096.8 | 3948.3 | 6.91 | 4 |
ROOM_3_MULT9_FLR_6 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 33206.0 | 18446.0 | 6.93 | 4 |
PTAC_6 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 24721.3 | 13741.5 | 6.92 | 4 |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:DX:MultiSpeed | 74091.7 | 41264.7 | 7.39 | 2 |
PSZ_CAFE HEATING COIL | Coil:Heating:DX:MultiSpeed | 50214.2 | 27731.4 | 7.83 | 2 |
PSZ_KITCHEN HEATING COIL | Coil:Heating:DX:MultiSpeed | 63369.4 | 35048.1 | 7.64 | 2 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11425.44 | 1.00 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8247.60 | 1.00 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8758.94 | 1.00 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5240.62 | 1.00 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 162123.21 | 1.00 | |
ROOM_1_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 24908.39 | 3.10 | |
ROOM_1_FLR_3_SUPPHEATCOIL | Coil:Heating:Electric | 9237.59 | 1.00 | |
ROOM_2_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 24693.91 | 3.10 | |
ROOM_2_FLR_3_SUPPHEATCOIL | Coil:Heating:Electric | 9259.62 | 1.00 | |
ROOM_3_MULT19_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 158710.41 | 3.10 | |
ROOM_3_MULT19_FLR_3_SUPPHEATCOIL | Coil:Heating:Electric | 64283.78 | 1.00 | |
ROOM_4_MULT19_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 159287.15 | 3.10 | |
ROOM_4_MULT19_FLR_3_SUPPHEATCOIL | Coil:Heating:Electric | 64711.39 | 1.00 | |
ROOM_5_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 20998.11 | 3.10 | |
ROOM_5_FLR_3_SUPPHEATCOIL | Coil:Heating:Electric | 9193.12 | 1.00 | |
ROOM_6_FLR_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 20697.72 | 3.10 | |
ROOM_6_FLR_3_SUPPHEATCOIL | Coil:Heating:Electric | 9215.16 | 1.00 | |
PTAC_3 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 42025.03 | 3.10 | |
PTAC_3_SUPPHEATCOIL | Coil:Heating:Electric | 23668.30 | 1.00 | |
ROOM_1_FLR_6 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 6844.81 | 3.10 | |
ROOM_1_FLR_6_SUPPHEATCOIL | Coil:Heating:Electric | 2824.01 | 1.00 | |
ROOM_2_FLR_6 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 6781.29 | 3.10 | |
ROOM_2_FLR_6_SUPPHEATCOIL | Coil:Heating:Electric | 2826.87 | 1.00 | |
ROOM_3_MULT9_FLR_6 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 31790.13 | 3.10 | |
ROOM_3_MULT9_FLR_6_SUPPHEATCOIL | Coil:Heating:Electric | 14273.26 | 1.00 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 81312.23 | 1.00 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 82717.75 | 1.00 | |
PTAC_6 PTAC HEATING COIL | Coil:Heating:DX:SingleSpeed | 23648.34 | 3.10 | |
PTAC_6_SUPPHEATCOIL | Coil:Heating:Electric | 12469.01 | 1.00 | |
VAV_FLR_1 HEATING COIL | Coil:Heating:Electric | 35592.88 | 1.00 | |
VAV_FLR_6 HEATING COIL | Coil:Heating:Electric | 27391.39 | 1.00 | |
VAV_FLR_0 HEATING COIL | Coil:Heating:Electric | 33057.48 | 1.00 | |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:DX:MultiSpeed | 70703.09 | 3.40 | |
PSZ_LAUNDRY_SUPPHEATCOIL | Coil:Heating:Electric | 70703.09 | 1.00 | |
PSZ_CAFE HEATING COIL | Coil:Heating:DX:MultiSpeed | 48423.56 | 3.40 | |
PSZ_CAFE_SUPPHEATCOIL | Coil:Heating:Electric | 48423.56 | 1.00 | |
PSZ_KITCHEN HEATING COIL | Coil:Heating:DX:MultiSpeed | 60998.59 | 3.40 | |
PSZ_KITCHEN_SUPPHEATCOIL | Coil:Heating:Electric | 60998.59 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
RETAIL_1_FLR_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.58 | 431.48 | 741.25 | 1.00 | 1.64 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
RETAIL_2_FLR_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.38 | 281.82 | 741.25 | 1.00 | 1.87 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 |
MECH_FLR_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.45 | 330.78 | 741.25 | 1.00 | 1.77 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
STORAGE_FLR_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 0.24 | 180.48 | 741.25 | 1.00 | 2.22 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
LOBBY_FLR_1 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 7.10 | 5262.53 | 741.25 | 1.00 | 1.17 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.45 | 925.41 | 636.87 | 1.00 | 1.42 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.44 | 919.80 | 636.87 | 1.00 | 1.42 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 8.38 | 5338.64 | 636.87 | 1.00 | 1.20 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 8.52 | 5428.35 | 636.87 | 1.00 | 1.20 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.26 | 802.66 | 636.87 | 1.00 | 1.45 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 |
ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.25 | 795.08 | 636.87 | 1.00 | 1.45 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 |
PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 2.14 | 1361.33 | 636.87 | 1.00 | 1.34 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.40 | 254.82 | 636.87 | 1.00 | 1.93 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.40 | 253.09 | 636.87 | 1.00 | 1.93 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.78 | 1134.32 | 636.87 | 1.00 | 1.37 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
BANQUET_FLR_6 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 3.28 | 2434.81 | 741.25 | 1.00 | 1.23 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 PIU FAN | Fan:ConstantVolume | 0.52 | 385.45 | 3.42 | 2538.27 | 741.25 | 1.00 | 1.23 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 1.89 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.35 | 860.05 | 636.87 | 1.00 | 1.43 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
VAV_FLR_1 FAN | Fan:VariableVolume | 0.61 | 1337.13 | 8.72 | 19159.81 | 2197.78 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
VAV_FLR_6 FAN | Fan:VariableVolume | 0.61 | 1337.13 | 6.71 | 14744.91 | 2197.78 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 0.60 | 1337.13 | 2.52 | 5600.54 | 2226.32 | 1.00 | 1.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 |
PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 4.27 | 6928.37 | 1622.12 | 1.00 | 1.18 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 |
PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 2.24 | 3722.38 | 1662.00 | 1.00 | 1.21 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 |
PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 2.97 | 4817.96 | 1622.12 | 1.00 | 1.21 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 0.80 | 0.98 | 0.90 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 183188.20 | 3.03 | 10.34 | 11.09 | 9.1539 | 3.25 | 11.07 | 7.2748 | 3.23 | 11.02 | 4.8812 | 3.35 | 11.45 | 2.0246 |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 157102.74 | 3.07 | 10.49 | 11.28 | 7.0446 | 3.30 | 11.27 | 5.5783 | 3.29 | 11.22 | 3.7411 | 3.39 | 11.56 | 1.6056 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 40672.77 | 46773.68 | 23.64 | 3.281 | 3.773 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 24.00 | 24.00 | 0.00909 | 32.75 | 0.00562 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6273.86 | 7214.94 | 107.57 | 0.506 | 0.582 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00883 | 40.80 | 0.00563 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 4097.65 | 4712.30 | 60.67 | 0.331 | 0.380 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00915 | 38.27 | 0.00563 | 0.092 | 0.00 |
MECH_FLR_1 | 4810.55 | 5532.13 | 33.68 | 0.388 | 0.446 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00856 | 39.47 | 0.00563 | 0.000 | 0.00 |
STORAGE_FLR_1 | 2624.69 | 3018.39 | 31.85 | 0.212 | 0.243 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00861 | 38.27 | 0.00563 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 46039.99 | 52945.99 | 678.45 | 3.714 | 4.271 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | 24.00 | 24.00 | 0.00853 | 39.07 | 0.00563 | 0.000 | 0.00 |
CAFE_FLR_1 | 24119.59 | 27737.53 | 146.87 | 1.948 | 2.240 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.00978 | 40.80 | 0.00563 | 0.676 | 0.00 |
LOBBY_FLR_1 | 76494.85 | 87969.08 | 67.25 | 6.173 | 7.100 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.99 | 0.00970 | 40.80 | 0.00563 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 15665.67 | 18015.52 | 461.68 | 1.264 | 1.453 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00852 | 39.29 | 0.00563 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 15570.70 | 17906.31 | 458.93 | 1.256 | 1.444 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 39.12 | 0.00563 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 90377.08 | 103933.64 | 4238.07 | 7.289 | 8.383 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00846 | 40.80 | 0.00563 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 91888.83 | 105672.16 | 4307.78 | 7.412 | 8.524 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 21.11 | 21.11 | 0.00866 | 40.53 | 0.00563 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 13587.78 | 15625.94 | 400.44 | 1.096 | 1.260 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 21.11 | 21.11 | 0.00852 | 37.08 | 0.00563 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 13459.45 | 15478.36 | 396.70 | 1.086 | 1.248 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 21.11 | 21.11 | 0.00852 | 36.74 | 0.00562 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 23040.96 | 26497.11 | 68.05 | 1.859 | 2.138 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00927 | 40.80 | 0.00563 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 4313.67 | 4960.72 | 127.13 | 0.348 | 0.400 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00851 | 39.47 | 0.00563 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 4284.43 | 4927.09 | 126.28 | 0.346 | 0.397 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00851 | 39.29 | 0.00563 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 19201.64 | 22081.89 | 900.18 | 1.549 | 1.781 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00857 | 40.80 | 0.00563 | 0.099 | 0.00 |
BANQUET_FLR_6 | 35362.82 | 40667.24 | 122.62 | 2.856 | 3.285 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.99 | 0.01006 | 40.80 | 0.00563 | 1.188 | 0.00 |
DINING_FLR_6 | 36865.94 | 42395.83 | 127.83 | 2.978 | 3.424 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.99 | 0.01000 | 40.80 | 0.00563 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31931.46 | 36721.18 | 355.47 | 2.583 | 2.970 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.00998 | 39.60 | 0.00563 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 14556.75 | 16740.26 | 40.62 | 1.174 | 1.350 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00881 | 40.80 | 0.00563 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 24.00 | 0.00817 | 0.50 | 0.00432 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 2891.98 | 3614.98 | 53.90 | 0.233 | 0.292 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00784 | 0.50 | 0.00432 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 701.02 | 876.28 | 11.28 | 0.057 | 0.092 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00776 | 0.50 | 0.00432 | 0.092 | 0.00 |
MECH_FLR_1 | 1088.04 | 1360.05 | 8.28 | 0.088 | 0.110 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00764 | 0.50 | 0.00432 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1093.20 | 1366.50 | 14.42 | 0.088 | 0.110 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1543.27 | 1929.09 | 24.72 | 0.125 | 0.156 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00765 | 0.50 | 0.00432 | 0.000 | 0.00 |
CAFE_FLR_1 | 7705.70 | 9632.13 | 51.00 | 0.622 | 0.778 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00787 | 0.50 | 0.00432 | 0.676 | 0.00 |
LOBBY_FLR_1 | 14826.84 | 18533.56 | 14.17 | 1.197 | 1.894 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6255.47 | 7819.34 | 200.38 | 0.505 | 0.631 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.11 | 21.11 | 0.00783 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6273.22 | 7841.53 | 200.97 | 0.506 | 0.633 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.11 | 21.11 | 0.00783 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 36041.30 | 45051.62 | 1837.05 | 2.910 | 3.638 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00784 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 36379.18 | 45473.98 | 1853.77 | 2.937 | 3.672 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00785 | 0.50 | 0.00432 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6219.89 | 7774.87 | 199.24 | 0.502 | 0.628 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.11 | 21.11 | 0.00783 | 0.50 | 0.00432 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6237.66 | 7797.07 | 199.84 | 0.504 | 0.630 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.11 | 21.11 | 0.00783 | 0.50 | 0.00432 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 10255.18 | 12818.97 | 32.92 | 0.828 | 1.035 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | 0.50 | 0.00432 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1975.56 | 2469.45 | 63.28 | 0.160 | 0.199 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.11 | 21.11 | 0.00787 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1977.89 | 2472.36 | 63.37 | 0.160 | 0.200 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.11 | 21.11 | 0.00787 | 0.50 | 0.00432 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9596.24 | 11995.30 | 488.99 | 0.775 | 0.969 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 21.11 | 21.11 | 0.00787 | 0.50 | 0.00432 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7179.82 | 8974.78 | 27.06 | 0.580 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00791 | 0.50 | 0.00432 | 1.188 | 0.00 |
DINING_FLR_6 | 7308.21 | 9135.26 | 27.54 | 0.590 | 1.188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 21.00 | 21.00 | 0.00791 | 0.50 | 0.00432 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2602.86 | 3253.58 | 31.50 | 0.210 | 0.367 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00755 | 0.50 | 0.00432 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 7678.76 | 9598.45 | 23.29 | 0.620 | 0.775 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00792 | 0.50 | 0.00432 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_FLR_1 | 8.72 | 8.72 | 2.50 | 2.50 | 8.7178 | 3.4872 | 8.7178 | 0.4000 | 0.3000 |
VAV_FLR_6 | 6.71 | 6.71 | 2.38 | 2.38 | 6.7090 | 3.1518 | 6.7090 | 0.4698 | 0.3000 |
VAV_FLR_0 | 3.77 | 3.77 | 0.85 | 0.85 | 3.7734 | 1.1320 | 3.7734 | 0.3000 | 1.0000 |
PSZ_LAUNDRY | 4.27 | 4.27 | 0.16 | 0.16 | 4.2712 | 4.2712 | 4.2712 | 1.0000 | 1.0000 |
PSZ_CAFE | 2.24 | 2.24 | 0.78 | 0.78 | 2.2397 | 2.2397 | 2.2397 | 1.0000 | 1.0000 |
PSZ_KITCHEN | 2.97 | 2.97 | 0.37 | 0.37 | 2.9702 | 2.9702 | 2.9702 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 11425.438 | 11425.438 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 11425.44 | 4406.55 | 0.291849 | 18.57 | 4.43 | -999.0 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00784247 | 46.0389 | 3614.98 | 0.00 | -999.00 | -999.00 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 8247.604 | 8247.604 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 8247.60 | 1447.27 | 0.091735 | 17.96 | 4.12 | -999.0 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00775534 | 45.5333 | 876.28 | 0.00 | -999.00 | -999.00 |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 8758.944 | 8758.944 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 8758.94 | 1657.89 | 0.109804 | 18.57 | 4.43 | -999.0 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00763994 | 44.8639 | 1360.05 | 0.00 | -999.00 | -999.00 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 5240.623 | 5240.623 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 5240.62 | 1734.58 | 0.110324 | 18.01 | 4.14 | -999.0 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778427 | 45.7011 | 1366.50 | 0.00 | -999.00 | -999.00 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 162123.212 | 162123.212 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 162123.21 | 30566.00 | 1.893991 | 17.63 | 3.96 | -999.0 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780783 | 45.8376 | 18533.56 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_3 | 24908.392 | 19927.591 | 1.453065 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 19812.04 | 19812.04 | 1.453065 | 21.88 | 14.57 | 0.00839359 | 9.43 | 9.43 | 0.00839359 | 39.29 | 0.00562876 | 18.11 | 4.2486 | 21.11 | 0.00851627 | 49.6012 | 18015.52 | 0.00 | 24920.58 | 18956.67 |
ROOM_1_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_3 | 24908.392 | 24908.392 | 1.453065 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 24908.39 | 21261.11 | 1.453065 | 19.10 | 12.73 | 0.00748766 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 4.2486 | 21.11 | 0.00783146 | 45.6627 | 7819.34 | 0.00 | 24941.13 | 24941.13 |
ROOM_1_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_3 | 9237.590 | 9237.590 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 9237.59 | 9237.59 | 0.631332 | 19.10 | 12.73 | 0.00748766 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 9.7785 | 21.11 | 0.00783146 | 45.6627 | 7819.34 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_3 | 24693.912 | 19778.540 | 1.444257 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 19687.45 | 19687.45 | 1.444257 | 21.88 | 14.57 | 0.00839294 | 9.43 | 9.43 | 0.00839294 | 39.12 | 0.00562848 | 18.06 | 4.2740 | 21.11 | 0.00851636 | 49.6017 | 17906.31 | 0.00 | 24706.00 | 18812.49 |
ROOM_2_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_3 | 24693.912 | 24693.912 | 1.444257 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 24693.91 | 21122.66 | 1.444257 | 19.10 | 12.73 | 0.00748909 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 4.2740 | 21.11 | 0.00783192 | 45.6654 | 7841.53 | 0.00 | 24726.36 | 24726.36 |
ROOM_2_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_3 | 9259.615 | 9259.615 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 9259.62 | 9259.62 | 0.633124 | 19.10 | 12.73 | 0.00748909 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 9.7497 | 21.11 | 0.00783192 | 45.6654 | 7841.53 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT19_FLR_3 | 158710.414 | 126721.850 | 8.382679 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 124751.12 | 124751.12 | 8.382679 | 23.08 | 14.80 | 0.00817457 | 9.43 | 9.43 | 0.00817457 | 40.80 | 0.00563111 | 18.58 | 9.9857 | 21.11 | 0.00845673 | 49.2582 | 103933.64 | 0.00 | 158788.10 | 120548.73 |
ROOM_3_MULT19_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT19_FLR_3 | 158710.414 | 158710.414 | 8.382679 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 158710.41 | 148141.62 | 8.382679 | 16.37 | 11.23 | 0.00703231 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 9.9857 | 21.11 | 0.00784435 | 45.7368 | 45051.62 | 0.00 | 158918.98 | 158918.98 |
ROOM_3_MULT19_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT19_FLR_3 | 64283.775 | 64283.775 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 64283.78 | 64283.78 | 3.637534 | 16.37 | 11.23 | 0.00703231 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 23.0121 | 21.11 | 0.00784435 | 45.7368 | 45051.62 | 0.00 | -999.00 | -999.00 |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_4_MULT19_FLR_3 | 159287.154 | 127535.687 | 8.523544 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | unknown | 7/21 15:20:00 | 126330.56 | 126330.56 | 8.523544 | 23.02 | 14.95 | 0.00836560 | 9.43 | 9.43 | 0.00836560 | 40.53 | 0.00563070 | 18.50 | 9.8234 | 21.11 | 0.00866352 | 50.4487 | 105672.16 | 0.00 | 159365.12 | 121303.70 |
ROOM_4_MULT19_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_4_MULT19_FLR_3 | 159287.154 | 159287.154 | 8.523544 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 159287.15 | 150224.69 | 8.523544 | 16.41 | 11.26 | 0.00704067 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 9.8234 | 21.11 | 0.00784570 | 45.7446 | 45473.98 | 0.00 | 159496.48 | 159496.48 |
ROOM_4_MULT19_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_4_MULT19_FLR_3 | 64711.386 | 64711.386 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 64711.39 | 64711.39 | 3.671636 | 16.41 | 11.26 | 0.00704067 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 22.8046 | 21.11 | 0.00784570 | 45.7446 | 45473.98 | 0.00 | -999.00 | -999.00 |
ROOM_5_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_5_FLR_3 | 20998.110 | 16804.551 | 1.260331 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | unknown | 7/21 10:40:00 | 17196.74 | 17196.74 | 1.260331 | 21.89 | 14.56 | 0.00837641 | 9.43 | 9.43 | 0.00837641 | 37.08 | 0.00562532 | 17.41 | 4.8983 | 21.11 | 0.00851810 | 49.6117 | 15625.94 | 0.00 | 21008.39 | 15984.12 |
ROOM_5_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_5_FLR_3 | 20998.110 | 20998.110 | 1.260331 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 20998.11 | 18457.23 | 1.260331 | 19.08 | 12.72 | 0.00748486 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 4.8983 | 21.11 | 0.00783054 | 45.6574 | 7774.87 | 0.00 | 21025.70 | 21025.70 |
ROOM_5_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_5_FLR_3 | 9193.119 | 9193.119 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 9193.12 | 9193.12 | 0.627742 | 19.08 | 12.72 | 0.00748486 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 9.8345 | 21.11 | 0.00783054 | 45.6574 | 7774.87 | 0.00 | -999.00 | -999.00 |
ROOM_6_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_6_FLR_3 | 20697.716 | 16560.040 | 1.248427 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | 7/21 10:30:00 | 17022.43 | 17022.43 | 1.248427 | 21.88 | 14.55 | 0.00837515 | 9.43 | 9.43 | 0.00837515 | 36.74 | 0.00562481 | 17.31 | 4.9444 | 21.11 | 0.00851822 | 49.6124 | 15478.36 | 0.00 | 20707.85 | 15751.51 |
ROOM_6_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_6_FLR_3 | 20697.716 | 20697.716 | 1.248427 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 20697.72 | 18274.54 | 1.248427 | 19.09 | 12.73 | 0.00748631 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 4.9444 | 21.11 | 0.00783101 | 45.6601 | 7797.07 | 0.00 | 20724.92 | 20724.92 |
ROOM_6_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_6_FLR_3 | 9215.158 | 9215.158 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 9215.16 | 9215.16 | 0.629534 | 19.09 | 12.73 | 0.00748631 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 9.8053 | 21.11 | 0.00783101 | 45.6601 | 7797.07 | 0.00 | -999.00 | -999.00 |
PTAC_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_3 | 42025.026 | 32886.987 | 2.137553 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 35384.22 | 35384.22 | 2.137553 | 27.73 | 16.63 | 0.00846307 | 12.32 | 11.00 | 0.00846307 | 40.80 | 0.00563111 | 18.58 | 22.2105 | 24.00 | 0.00927166 | 45.2583 | 26497.11 | 0.00 | 42045.60 | 31334.85 |
PTAC_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_3 | 42025.026 | 42025.026 | 2.137553 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 42025.03 | 42025.03 | 2.137553 | 11.60 | 8.41 | 0.00624173 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 22.2105 | 21.00 | 0.00787416 | 46.2222 | 12818.97 | 0.00 | 42080.25 | 42080.25 |
PTAC_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_3 | 23668.303 | 23668.303 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23668.30 | 23668.30 | 1.034948 | 11.60 | 8.41 | 0.00624173 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 45.8731 | 21.00 | 0.00787416 | 46.2222 | 12818.97 | 0.00 | -999.00 | -999.00 |
ROOM_1_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_6 | 6844.814 | 5481.035 | 0.400114 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 5428.42 | 5428.42 | 0.400114 | 21.82 | 14.55 | 0.00840351 | 9.43 | 9.43 | 0.00840351 | 39.47 | 0.00562903 | 18.17 | 3.8573 | 21.11 | 0.00851483 | 49.5929 | 4960.72 | 0.00 | 6848.16 | 5213.46 |
ROOM_1_FLR_6 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_6 | 6844.814 | 6844.814 | 0.400114 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 6844.81 | 5667.09 | 0.400114 | 19.52 | 12.99 | 0.00759050 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.8573 | 21.11 | 0.00786527 | 45.8574 | 2469.45 | 0.00 | 6853.81 | 6853.81 |
ROOM_1_FLR_6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_6 | 2824.008 | 2824.008 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 2824.01 | 2824.01 | 0.199383 | 19.52 | 12.99 | 0.00759050 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.7407 | 21.11 | 0.00786527 | 45.8574 | 2469.45 | 0.00 | -999.00 | -999.00 |
ROOM_2_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_6 | 6781.286 | 5429.473 | 0.397401 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 5390.72 | 5390.72 | 0.397401 | 21.82 | 14.55 | 0.00840282 | 9.43 | 9.43 | 0.00840282 | 39.29 | 0.00562876 | 18.11 | 3.8832 | 21.11 | 0.00851490 | 49.5933 | 4927.09 | 0.00 | 6784.61 | 5164.50 |
ROOM_2_FLR_6 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_6 | 6781.286 | 6781.286 | 0.397401 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 6781.29 | 5627.75 | 0.397401 | 19.52 | 12.99 | 0.00759100 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.8832 | 21.11 | 0.00786543 | 45.8583 | 2472.36 | 0.00 | 6790.20 | 6790.20 |
ROOM_2_FLR_6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_6 | 2826.871 | 2826.871 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 2826.87 | 2826.87 | 0.199618 | 19.52 | 12.99 | 0.00759100 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 7.7307 | 21.11 | 0.00786543 | 45.8583 | 2472.36 | 0.00 | -999.00 | -999.00 |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT9_FLR_6 | 31790.132 | 25463.237 | 1.781100 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 24888.50 | 24888.50 | 1.781100 | 22.21 | 14.70 | 0.00840870 | 9.43 | 9.43 | 0.00840870 | 40.80 | 0.00563111 | 18.58 | 5.5670 | 21.11 | 0.00857245 | 49.9250 | 22081.89 | 0.00 | 31805.69 | 24221.81 |
ROOM_3_MULT9_FLR_6 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT9_FLR_6 | 31790.132 | 31790.132 | 1.781100 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 31790.13 | 26248.73 | 1.781100 | 19.00 | 12.71 | 0.00750793 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 5.5670 | 21.11 | 0.00787204 | 45.8962 | 11995.30 | 0.00 | 31831.91 | 31831.91 |
ROOM_3_MULT9_FLR_6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT9_FLR_6 | 14273.258 | 14273.258 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 14273.26 | 14273.26 | 0.968508 | 19.00 | 12.71 | 0.00750793 | 32.22 | 17.72 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 10.2378 | 21.11 | 0.00787204 | 45.8962 | 11995.30 | 0.00 | -999.00 | -999.00 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 81312.225 | 81312.225 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 81312.23 | 19867.30 | 1.187797 | 17.11 | 3.68 | -999.0 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00790837 | 46.4207 | 8974.78 | 0.00 | -999.00 | -999.00 |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | 82717.749 | 82717.749 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | 82717.75 | 19652.51 | 1.187797 | 17.27 | 3.77 | -999.0 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00790994 | 46.4298 | 9135.26 | 0.00 | -999.00 | -999.00 |
PTAC_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_6 | 23648.344 | 18931.459 | 1.350437 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | 7/21 14:30:00 | 19405.39 | 19354.91 | 1.350437 | 25.56 | 15.95 | 0.00851610 | 12.32 | 11.04 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | 9.3018 | 24.00 | 0.00881198 | 43.0454 | 16740.26 | 0.00 | 23659.92 | 18005.92 |
PTAC_6 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_6 | 23648.344 | 23648.344 | 1.350437 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 23648.34 | 21729.13 | 1.350437 | 17.68 | 12.05 | 0.00733958 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 9.3018 | 21.00 | 0.00792459 | 46.5146 | 9598.45 | 0.00 | 23679.42 | 23679.42 |
PTAC_6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_6 | 12469.015 | 12469.015 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 12469.01 | 12469.01 | 0.774933 | 17.68 | 12.05 | 0.00733958 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 16.2099 | 21.00 | 0.00792459 | 46.5146 | 9598.45 | 0.00 | -999.00 | -999.00 |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_FLR_1 | 189608.578 | 141224.511 | 8.717799 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 173116.36 | 173116.35 | 8.717799 | 29.45 | 17.04 | 0.00826813 | 10.92 | 10.23 | 0.00826813 | 40.80 | 0.00563111 | 18.58 | 32.4658 | 24.00 | 0.00953582 | 46.5389 | 93938.32 | 0.00 | 190156.97 | 135274.55 |
VAV_FLR_1 HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_FLR_1 | 35592.878 | 35592.878 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 35592.88 | 35592.88 | 2.615340 | 0.50 | 0.50 | 0.00431558 | 12.89 | 10.78 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 108.2192 | 21.00 | 0.00780079 | 45.7969 | 20601.10 | 0.00 | -999.00 | -999.00 |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_FLR_6 | 162016.436 | 115034.501 | 6.709000 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 149803.77 | 149803.77 | 6.709000 | 31.92 | 17.59 | 0.00795415 | 10.92 | 9.91 | 0.00795415 | 40.80 | 0.00563111 | 18.58 | 47.2127 | 23.99 | 0.01003186 | 48.9502 | 72228.76 | 0.00 | 162485.02 | 110624.07 |
VAV_FLR_6 HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_FLR_6 | 27391.389 | 27391.389 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 27391.39 | 27391.39 | 2.012700 | 0.50 | 0.50 | 0.00431558 | 12.89 | 10.78 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 157.3757 | 21.00 | 0.00790916 | 46.4254 | 14487.35 | 0.00 | -999.00 | -999.00 |
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | VAV_FLR_0 | 66436.070 | 53193.368 | 3.773400 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 33218.04 | 33218.03 | 2.515600 | 25.98 | 15.91 | 0.00830281 | 10.89 | 10.26 | 0.00830281 | 32.75 | 0.00561869 | 15.99 | 33.9664 | 24.00 | 0.00908901 | 44.3805 | 40640.95 | 0.00 | -999.00 | -999.00 |
VAV_FLR_0 HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_FLR_0 | 33057.483 | 33057.483 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 33057.48 | 33057.48 | 2.515600 | 14.04 | 9.99 | 0.00674854 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 33.9664 | 24.00 | 0.00817113 | 39.9531 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ_LAUNDRY HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_LAUNDRY | 72144.620 | 57738.061 | 4.271170 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | 36072.31 | 35864.92 | 2.847447 | 24.00 | 15.43 | 0.00853212 | 11.44 | 10.68 | 0.00850000 | 39.07 | 0.00562841 | 18.04 | 0.0000 | 24.00 | 0.00853212 | 41.6970 | 46039.99 | 0.00 | -999.00 | -999.00 |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ_LAUNDRY | 70703.094 | 70703.094 | 4.271174 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 35351.55 | 26449.88 | 2.135587 | 21.00 | 13.60 | 0.00765211 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00765211 | 44.9350 | 1543.27 | 0.00 | -999.00 | -999.00 |
PSZ_LAUNDRY_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ_LAUNDRY | 70703.094 | 70703.094 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 70703.09 | 52899.77 | 4.271174 | 21.00 | 13.60 | 0.00765211 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00765211 | 44.9350 | 1543.27 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_CAFE | 49947.540 | 36756.395 | 2.239700 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24973.77 | 24883.89 | 1.493133 | 29.07 | 17.12 | 0.00852730 | 11.40 | 10.66 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | 45.3000 | 23.99 | 0.00978038 | 47.7326 | 24119.59 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ_CAFE | 48423.561 | 48423.561 | 2.239701 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 24211.78 | 21597.92 | 1.119851 | 14.81 | 10.36 | 0.00679542 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 60.4000 | 21.00 | 0.00786835 | 46.1888 | 7705.70 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ_CAFE | 48423.561 | 48423.561 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | 48423.56 | 43195.83 | 2.239701 | 14.81 | 10.36 | 0.00679542 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 30.2000 | 21.00 | 0.00786835 | 46.1888 | 7705.70 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_KITCHEN | 63140.630 | 47563.205 | 2.970150 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31570.31 | 27451.24 | 1.980100 | 25.88 | 16.81 | 0.00944563 | 11.44 | 10.68 | 0.00850000 | 39.60 | 0.00562924 | 18.21 | 18.5521 | 23.97 | 0.00998426 | 48.7651 | 31931.46 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoopHVAC | PSZ_KITCHEN | 60998.589 | 60998.589 | 2.970155 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 30499.29 | 22918.36 | 1.485077 | 18.27 | 12.10 | 0.00715095 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 24.7361 | 21.00 | 0.00753831 | 44.2765 | 1698.43 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoopHVAC | PSZ_KITCHEN | 60998.589 | 60998.589 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 60998.59 | 45836.71 | 2.970155 | 18.27 | 12.10 | 0.00715095 | 32.11 | 17.68 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 12.3681 | 21.00 | 0.00753831 | 44.2765 | 1698.43 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11425.438 | 11425.438 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 11425.44 | 4406.55 | 1.0000 | 0.31904730 | 0.291849 | 18.57 | 4.43 | -999.0 | -999.0 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11425.44 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00784247 | 21.00 | 0.00784247 | 46.0389 | 3614.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8247.604 | 8247.604 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 8247.60 | 1447.27 | 1.0000 | 0.10028379 | 0.091735 | 17.96 | 4.12 | -999.0 | -999.0 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8247.60 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00775534 | 21.00 | 0.00775534 | 45.5333 | 876.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8758.944 | 8758.944 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 8758.94 | 1657.89 | 1.0000 | 0.12003678 | 0.109804 | 18.57 | 4.43 | -999.0 | -999.0 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8758.94 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00763994 | 21.00 | 0.00763994 | 44.8639 | 1360.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5240.623 | 5240.623 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 5240.62 | 1734.58 | 1.0000 | 0.12060609 | 0.110324 | 18.01 | 4.14 | -999.0 | -999.0 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5240.62 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00778427 | 21.00 | 0.00778427 | 45.7011 | 1366.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | No | unknown | No | 162123.212 | 162123.212 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 162123.21 | 30566.00 | 1.0000 | 2.07049952 | 1.893991 | 17.63 | 3.96 | -999.0 | -999.0 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 162123.21 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00780783 | 21.00 | 0.00780783 | 45.8376 | 18533.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 24908.392 | 19927.591 | 1.453065 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4433 | 1004.8586 | 1.0932 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.453065 | 1.58848278 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 19812.04 | 19812.04 | 0.7954 | 1.58848278 | 1.453065 | 21.88 | 14.57 | 0.00839359 | 43322.6 | 9.43 | 9.43 | 0.00839359 | 30612.6 | -999.0 | -999.00 | -999.00 | -999.00 | 925.407 | 18886.63 | 39.29 | 0.00562876 | 18.11 | 0.06173502 | 4.2486 | 21.11 | 0.00851627 | 21.11 | 0.00851627 | 49.6012 | 18015.52 | 0.00 | 24920.58 | 18956.67 | 1.52574971 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.52 | 13.90 | 0.00965209 | 38989.0 | |
ROOM_1_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 24908.392 | 24908.392 | 1.453065 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.453065 | 1.58848278 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 24908.39 | 21261.11 | 1.0000 | 1.58848278 | 1.453065 | 19.10 | 12.73 | 0.00748766 | 38179.7 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24908.39 | 0.50 | 0.00431558 | 0.50 | 0.06173502 | 4.2486 | 21.11 | 0.00783146 | 21.11 | 0.00783146 | 45.6627 | 7819.34 | 0.00 | 24941.13 | 24941.13 | 1.56041379 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.76 | 20.76 | 0.00875166 | 59427.8 | |
ROOM_1_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9237.590 | 9237.590 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.453065 | 1.58848278 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 9237.59 | 9237.59 | 1.0000 | 0.69016882 | 0.631332 | 19.10 | 12.73 | 0.00748766 | 38179.7 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9237.59 | 0.50 | 0.00431558 | 0.50 | 0.06173502 | 9.7785 | 21.11 | 0.00783146 | 21.11 | 0.00783146 | 45.6627 | 7819.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 24693.912 | 19778.540 | 1.444257 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4420 | 1004.8586 | 1.0932 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.444257 | 1.57885353 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 19687.45 | 19687.45 | 0.7973 | 1.57885353 | 1.444257 | 21.88 | 14.57 | 0.00839294 | 43317.9 | 9.43 | 9.43 | 0.00839294 | 30611.0 | -999.0 | -999.00 | -999.00 | -999.00 | 919.797 | 18767.66 | 39.12 | 0.00562848 | 18.06 | 0.06172779 | 4.2740 | 21.11 | 0.00851636 | 21.11 | 0.00851636 | 49.6017 | 17906.31 | 0.00 | 24706.00 | 18812.49 | 1.51650075 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.54 | 13.92 | 0.00966095 | 39030.9 | |
ROOM_2_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 24693.912 | 24693.912 | 1.444257 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.444257 | 1.57885353 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 24693.91 | 21122.66 | 1.0000 | 1.57885353 | 1.444257 | 19.10 | 12.73 | 0.00748909 | 38189.4 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24693.91 | 0.50 | 0.00431558 | 0.50 | 0.06172779 | 4.2740 | 21.11 | 0.00783192 | 21.11 | 0.00783192 | 45.6654 | 7841.53 | 0.00 | 24726.36 | 24726.36 | 1.55095470 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.72 | 20.75 | 0.00875166 | 59386.8 | |
ROOM_2_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9259.615 | 9259.615 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.444257 | 1.57885353 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 9259.62 | 9259.62 | 1.0000 | 0.69212752 | 0.633124 | 19.10 | 12.73 | 0.00748909 | 38189.4 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9259.62 | 0.50 | 0.00431558 | 0.50 | 0.06172779 | 9.7497 | 21.11 | 0.00783192 | 21.11 | 0.00783192 | 45.6654 | 7841.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 158710.414 | 126721.850 | 8.382679 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0361 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 8.382679 | 9.16389584 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 124751.12 | 124751.12 | 0.7860 | 9.16389584 | 8.382679 | 23.08 | 14.80 | 0.00817457 | 43983.7 | 9.43 | 9.43 | 0.00817457 | 30060.8 | -999.0 | -999.00 | -999.00 | -999.00 | 5338.638 | 119412.48 | 40.80 | 0.00563111 | 18.58 | 0.83707151 | 9.9857 | 21.11 | 0.00845673 | 21.11 | 0.00845673 | 49.2582 | 103933.64 | 0.00 | 158788.10 | 120548.73 | 8.80199123 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.27 | 13.25 | 0.00948132 | 37282.4 | |
ROOM_3_MULT19_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 158710.414 | 158710.414 | 8.382679 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 8.382679 | 9.16389584 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 158710.41 | 148141.62 | 1.0000 | 9.16389584 | 8.382679 | 16.37 | 11.23 | 0.00703231 | 34248.4 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 158710.41 | 0.50 | 0.00431558 | 0.50 | 0.83707151 | 9.9857 | 21.11 | 0.00784435 | 21.11 | 0.00784435 | 45.7368 | 45051.62 | 0.00 | 158918.98 | 158918.98 | 9.00196696 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 38.40 | 21.25 | 0.00875166 | 61097.9 | |
ROOM_3_MULT19_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 64283.775 | 64283.775 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 8.382679 | 9.16389584 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 64283.78 | 64283.78 | 1.0000 | 3.97653162 | 3.637534 | 16.37 | 11.23 | 0.00703231 | 34248.4 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64283.78 | 0.50 | 0.00431558 | 0.50 | 0.83707151 | 23.0121 | 21.11 | 0.00784435 | 21.11 | 0.00784435 | 45.7368 | 45051.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 159287.154 | 127535.687 | 8.523544 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3912 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 8.523544 | 9.31788905 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | unknown | unknown | unknown | 7/21 15:20:00 | Sensible | 126330.56 | 126330.56 | 0.7931 | 9.31788905 | 8.523544 | 23.02 | 14.95 | 0.00836560 | 44409.6 | 9.43 | 9.43 | 0.00836560 | 30542.1 | -999.0 | -999.00 | -999.00 | -999.00 | 5428.350 | 120902.21 | 40.53 | 0.00563070 | 18.50 | 0.83730041 | 9.8234 | 21.11 | 0.00866352 | 21.11 | 0.00866352 | 50.4487 | 105672.16 | 0.00 | 159365.12 | 121303.70 | 8.94990287 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.41 | 13.34 | 0.00951727 | 37516.0 | |
ROOM_4_MULT19_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 159287.154 | 159287.154 | 8.523544 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 8.523544 | 9.31788905 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 159287.15 | 150224.69 | 1.0000 | 9.31788905 | 8.523544 | 16.41 | 11.26 | 0.00704067 | 34313.1 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 159287.15 | 0.50 | 0.00431558 | 0.50 | 0.83730041 | 9.8234 | 21.11 | 0.00784570 | 21.11 | 0.00784570 | 45.7446 | 45473.98 | 0.00 | 159496.48 | 159496.48 | 9.15323906 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 38.18 | 21.18 | 0.00875166 | 60869.2 | |
ROOM_4_MULT19_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 64711.386 | 64711.386 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 8.523544 | 9.31788905 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 64711.39 | 64711.39 | 1.0000 | 4.01381110 | 3.671636 | 16.41 | 11.26 | 0.00704067 | 34313.1 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64711.39 | 0.50 | 0.00431558 | 0.50 | 0.83730041 | 22.8046 | 21.11 | 0.00784570 | 21.11 | 0.00784570 | 45.7446 | 45473.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_5_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 20998.110 | 16804.551 | 1.260331 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4113 | 1004.8586 | 1.0932 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.260331 | 1.37778623 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | unknown | unknown | unknown | 7/21 10:40:00 | Sensible | 17196.74 | 17196.74 | 0.8190 | 1.37778623 | 1.260331 | 21.89 | 14.56 | 0.00837641 | 43288.6 | 9.43 | 9.43 | 0.00837641 | 30569.3 | -999.0 | -999.00 | -999.00 | -999.00 | 802.661 | 16394.08 | 37.08 | 0.00562532 | 17.41 | 0.06173502 | 4.8983 | 21.11 | 0.00851810 | 21.11 | 0.00851810 | 49.6117 | 15625.94 | 0.00 | 21008.39 | 15984.12 | 1.32337409 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.86 | 14.08 | 0.00969612 | 39447.5 | |
ROOM_5_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 20998.110 | 20998.110 | 1.260331 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.260331 | 1.37778623 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 20998.11 | 18457.23 | 1.0000 | 1.37778623 | 1.260331 | 19.08 | 12.72 | 0.00748486 | 38160.8 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20998.11 | 0.50 | 0.00431558 | 0.50 | 0.06173502 | 4.8983 | 21.11 | 0.00783054 | 21.11 | 0.00783054 | 45.6574 | 7774.87 | 0.00 | 21025.70 | 21025.70 | 1.35344032 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.32 | 20.63 | 0.00875166 | 58979.1 | |
ROOM_5_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9193.119 | 9193.119 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.260331 | 1.37778623 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 9193.12 | 9193.12 | 1.0000 | 0.68624353 | 0.627742 | 19.08 | 12.72 | 0.00748486 | 38160.8 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9193.12 | 0.50 | 0.00431558 | 0.50 | 0.06173502 | 9.8345 | 21.11 | 0.00783054 | 21.11 | 0.00783054 | 45.6574 | 7774.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_6_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 20697.716 | 16560.040 | 1.248427 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4090 | 1004.8586 | 1.0932 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.248427 | 1.36477360 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | unknown | unknown | unknown | 7/21 10:30:00 | Sensible | 17022.43 | 17022.43 | 0.8224 | 1.36477360 | 1.248427 | 21.88 | 14.55 | 0.00837515 | 43276.2 | 9.43 | 9.43 | 0.00837515 | 30566.1 | -999.0 | -999.00 | -999.00 | -999.00 | 795.080 | 16227.35 | 36.74 | 0.00562481 | 17.31 | 0.06172779 | 4.9444 | 21.11 | 0.00851822 | 21.11 | 0.00851822 | 49.6124 | 15478.36 | 0.00 | 20707.85 | 15751.51 | 1.31087536 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.92 | 14.11 | 0.00970224 | 39525.4 | |
ROOM_6_FLR_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 20697.716 | 20697.716 | 1.248427 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.248427 | 1.36477360 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 20697.72 | 18274.54 | 1.0000 | 1.36477360 | 1.248427 | 19.09 | 12.73 | 0.00748631 | 38170.6 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20697.72 | 0.50 | 0.00431558 | 0.50 | 0.06172779 | 4.9444 | 21.11 | 0.00783101 | 21.11 | 0.00783101 | 45.6601 | 7797.07 | 0.00 | 20724.92 | 20724.92 | 1.34065762 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.25 | 20.61 | 0.00875166 | 58902.9 | |
ROOM_6_FLR_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9215.158 | 9215.158 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.248427 | 1.36477360 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 9215.16 | 9215.16 | 1.0000 | 0.68820343 | 0.629534 | 19.09 | 12.73 | 0.00748631 | 38170.6 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9215.16 | 0.50 | 0.00431558 | 0.50 | 0.06172779 | 9.8053 | 21.11 | 0.00783101 | 21.11 | 0.00783101 | 45.6601 | 7797.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PTAC_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 42025.026 | 32886.987 | 2.137553 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5724 | 1004.8586 | 1.0932 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 2.137553 | 2.33676088 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | Sensible | 35384.22 | 35384.22 | 0.8420 | 2.33676088 | 2.137553 | 27.73 | 16.63 | 0.00846307 | 49466.6 | 12.32 | 11.00 | 0.00846307 | 33737.1 | -999.0 | -999.00 | -999.00 | -999.00 | 1361.334 | 34022.89 | 40.80 | 0.00563111 | 18.58 | 0.47476218 | 22.2105 | 24.00 | 0.00927166 | 24.00 | 0.00927166 | 45.2583 | 26497.11 | 0.00 | 42045.60 | 31334.85 | 2.24447649 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.01 | 12.99 | 0.00931365 | 36589.5 | |
PTAC_3 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 42025.026 | 42025.026 | 2.137553 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 2.137553 | 2.33676088 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 42025.03 | 42025.03 | 1.0000 | 2.33676088 | 2.137553 | 11.60 | 8.41 | 0.00624173 | 27396.9 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42025.03 | 0.50 | 0.00431558 | 0.50 | 0.47476218 | 22.2105 | 21.00 | 0.00787416 | 21.00 | 0.00787416 | 46.2222 | 12818.97 | 0.00 | 42080.25 | 42080.25 | 2.29546960 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 39.06 | 21.45 | 0.00875166 | 61776.0 | |
PTAC_3_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | No | unknown | No | 23668.303 | 23668.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 2.137553 | 2.33676088 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23668.30 | 23668.30 | 1.0000 | 1.13139896 | 1.034948 | 11.60 | 8.41 | 0.00624173 | 27396.9 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23668.30 | 0.50 | 0.00431558 | 0.50 | 0.47476218 | 45.8731 | 21.00 | 0.00787416 | 21.00 | 0.00787416 | 46.2222 | 12818.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_1_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 6844.814 | 5481.035 | 0.400114 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4617 | 1004.8586 | 1.0932 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.400114 | 0.43740208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 5428.42 | 5428.42 | 0.7931 | 0.43740208 | 0.400114 | 21.82 | 14.55 | 0.00840351 | 43282.2 | 9.43 | 9.43 | 0.00840351 | 30637.6 | -999.0 | -999.00 | -999.00 | -999.00 | 254.819 | 5173.60 | 39.47 | 0.00562903 | 18.17 | 0.01543376 | 3.8573 | 21.11 | 0.00851483 | 21.11 | 0.00851483 | 49.5929 | 4960.72 | 0.00 | 6848.16 | 5213.46 | 0.42012800 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.53 | 13.92 | 0.00965910 | 39022.2 | |
ROOM_1_FLR_6 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 6844.814 | 6844.814 | 0.400114 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.400114 | 0.43740208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 6844.81 | 5667.09 | 1.0000 | 0.43740208 | 0.400114 | 19.52 | 12.99 | 0.00759050 | 38868.5 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6844.81 | 0.50 | 0.00431558 | 0.50 | 0.01543376 | 3.8573 | 21.11 | 0.00786527 | 21.11 | 0.00786527 | 45.8574 | 2469.45 | 0.00 | 6853.81 | 6853.81 | 0.42967305 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.73 | 20.75 | 0.00875166 | 59395.3 | |
ROOM_1_FLR_6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 2824.008 | 2824.008 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.400114 | 0.43740208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 2824.01 | 2824.01 | 1.0000 | 0.21796485 | 0.199383 | 19.52 | 12.99 | 0.00759050 | 38868.5 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2824.01 | 0.50 | 0.00431558 | 0.50 | 0.01543376 | 7.7407 | 21.11 | 0.00786527 | 21.11 | 0.00786527 | 45.8574 | 2469.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_2_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 6781.286 | 5429.473 | 0.397401 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4604 | 1004.8586 | 1.0932 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.397401 | 0.43443639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 5390.72 | 5390.72 | 0.7949 | 0.43443639 | 0.397401 | 21.82 | 14.55 | 0.00840282 | 43278.3 | 9.43 | 9.43 | 0.00840282 | 30635.9 | -999.0 | -999.00 | -999.00 | -999.00 | 253.091 | 5137.63 | 39.29 | 0.00562876 | 18.11 | 0.01543195 | 3.8832 | 21.11 | 0.00851490 | 21.11 | 0.00851490 | 49.5933 | 4927.09 | 0.00 | 6784.61 | 5164.50 | 0.41727944 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.57 | 13.93 | 0.00966240 | 39063.2 | |
ROOM_2_FLR_6 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 6781.286 | 6781.286 | 0.397401 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.397401 | 0.43443639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 6781.29 | 5627.75 | 1.0000 | 0.43443639 | 0.397401 | 19.52 | 12.99 | 0.00759100 | 38871.9 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6781.29 | 0.50 | 0.00431558 | 0.50 | 0.01543195 | 3.8832 | 21.11 | 0.00786543 | 21.11 | 0.00786543 | 45.8583 | 2472.36 | 0.00 | 6790.20 | 6790.20 | 0.42675976 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 36.69 | 20.74 | 0.00875166 | 59355.2 | |
ROOM_2_FLR_6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 2826.871 | 2826.871 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.397401 | 0.43443639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 2826.87 | 2826.87 | 1.0000 | 0.21822125 | 0.199618 | 19.52 | 12.99 | 0.00759100 | 38871.9 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2826.87 | 0.50 | 0.00431558 | 0.50 | 0.01543195 | 7.7307 | 21.11 | 0.00786543 | 21.11 | 0.00786543 | 45.8583 | 2472.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 31790.132 | 25463.237 | 1.781100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4714 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.781100 | 1.94708861 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 24888.50 | 24888.50 | 0.7829 | 1.94708861 | 1.781100 | 22.21 | 14.70 | 0.00840870 | 43690.9 | 9.43 | 9.43 | 0.00840870 | 30650.7 | -999.0 | -999.00 | -999.00 | -999.00 | 1134.321 | 23754.17 | 40.80 | 0.00563111 | 18.58 | 0.09915400 | 5.5670 | 21.11 | 0.00857245 | 21.11 | 0.00857245 | 49.9250 | 22081.89 | 0.00 | 31805.69 | 24221.81 | 1.87019333 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.00 | 13.65 | 0.00959473 | 38315.8 | |
ROOM_3_MULT9_FLR_6 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 31790.132 | 31790.132 | 1.781100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.781100 | 1.94708861 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 31790.13 | 26248.73 | 1.0000 | 1.94708861 | 1.781100 | 19.00 | 12.71 | 0.00750793 | 38134.7 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31790.13 | 0.50 | 0.00431558 | 0.50 | 0.09915400 | 5.5670 | 21.11 | 0.00787204 | 21.11 | 0.00787204 | 45.8962 | 11995.30 | 0.00 | 31831.91 | 31831.91 | 1.91268295 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 37.41 | 20.96 | 0.00875166 | 60086.6 | |
ROOM_3_MULT9_FLR_6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 14273.258 | 14273.258 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.781100 | 1.94708861 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 14273.26 | 14273.26 | 1.0000 | 1.05876754 | 0.968508 | 19.00 | 12.71 | 0.00750793 | 38134.7 | 32.22 | 17.72 | 0.00800000 | 52863.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14273.26 | 0.50 | 0.00431558 | 0.50 | 0.09915400 | 10.2378 | 21.11 | 0.00787204 | 21.11 | 0.00787204 | 45.8962 | 11995.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 81312.225 | 81312.225 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 81312.23 | 19867.30 | 1.0000 | 1.29849281 | 1.187797 | 17.11 | 3.68 | -999.0 | -999.0 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81312.23 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00790837 | 21.00 | 0.00790837 | 46.4207 | 8974.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Electric | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 82717.749 | 82717.749 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | Sensible | 82717.75 | 19652.51 | 1.0000 | 1.29849281 | 1.187797 | 17.27 | 3.77 | -999.0 | -999.0 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82717.75 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00790994 | 21.00 | 0.00790994 | 46.4298 | 9135.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PTAC_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 23648.344 | 18931.459 | 1.350437 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6710 | 1004.8586 | 1.0932 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.350437 | 1.47628995 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | unknown | unknown | 7/21 14:30:00 | Sensible | 19405.39 | 19354.91 | 0.8206 | 1.47628995 | 1.350437 | 25.56 | 15.95 | 0.00851610 | 47388.5 | 12.32 | 11.04 | 0.00850000 | 33830.4 | -999.0 | -999.00 | -999.00 | -999.00 | 860.047 | 18545.35 | 40.80 | 0.00563111 | 18.58 | 0.12561561 | 9.3018 | 24.00 | 0.00881198 | 24.00 | 0.00881198 | 43.0454 | 16740.26 | 0.00 | 23659.92 | 18005.92 | 1.41798765 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.25 | 13.77 | 0.00962132 | 38636.8 | |
PTAC_6 PTAC HEATING COIL | COIL:HEATING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 23648.344 | 23648.344 | 1.350437 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.350437 | 1.47628995 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 23648.34 | 21729.13 | 1.0000 | 1.47628995 | 1.350437 | 17.68 | 12.05 | 0.00733958 | 36359.5 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23648.34 | 0.50 | 0.00431558 | 0.50 | 0.12561561 | 9.3018 | 21.00 | 0.00792459 | 21.00 | 0.00792459 | 46.5146 | 9598.45 | 0.00 | 23679.42 | 23679.42 | 1.45020345 | 21.11 | 15.56 | 0.00875166 | 43444.1 | 37.10 | 20.86 | 0.00875166 | 59772.4 | |
PTAC_6_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALHEATPUMP | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | No | unknown | No | 12469.015 | 12469.015 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.350437 | 1.47628995 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 12469.01 | 12469.01 | 1.0000 | 0.84715234 | 0.774933 | 17.68 | 12.05 | 0.00733958 | 36359.5 | 32.11 | 17.68 | 0.00800000 | 52751.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12469.01 | 0.50 | 0.00431558 | 0.50 | 0.12561561 | 16.2099 | 21.00 | 0.00792459 | 21.00 | 0.00792459 | 46.5146 | 9598.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_FLR_1 | RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LOBBY_FLR_1; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 189608.578 | 141224.511 | 8.717799 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2100 | 1004.8586 | 1.0932 | VAV_FLR_1 FAN | Fan:VariableVolume | 8.717799 | 9.53024698 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 173116.36 | 173116.35 | 0.9130 | 9.53024698 | 8.717799 | 29.45 | 17.04 | 0.00826813 | 50724.2 | 10.92 | 10.23 | 0.00826813 | 31817.0 | -999.0 | -999.00 | -999.00 | -999.00 | 19159.813 | 153956.54 | 40.80 | 0.00563111 | 18.58 | 2.83030000 | 32.4658 | 24.00 | 0.00953582 | 24.00 | 0.00953582 | 46.5389 | 93938.32 | 0.00 | 190156.97 | 135274.55 | 9.15387426 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.20 | 12.18 | 0.00883394 | 34549.0 | |
VAV_FLR_1 HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_FLR_1 | RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LOBBY_FLR_1; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35592.878 | 35592.878 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_FLR_1 FAN | Fan:VariableVolume | 8.717799 | 9.53024698 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 35592.88 | 35592.88 | 1.0000 | 2.85907409 | 2.615340 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 12.89 | 10.78 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35592.88 | 0.50 | 0.00431558 | 0.50 | 2.83030000 | 108.2192 | 21.00 | 0.00780153 | 21.00 | 0.00780079 | 45.7969 | 20601.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_FLR_6 | BANQUET_FLR_6; DINING_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 162016.436 | 115034.501 | 6.709000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6264 | 1004.8586 | 1.0932 | VAV_FLR_6 FAN | Fan:VariableVolume | 6.709000 | 7.33423991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 149803.77 | 149803.77 | 0.9246 | 7.33423991 | 6.709000 | 31.92 | 17.59 | 0.00795415 | 52443.3 | 10.92 | 9.91 | 0.00795415 | 31024.3 | -999.0 | -999.00 | -999.00 | -999.00 | 14744.913 | 135058.86 | 40.80 | 0.00563111 | 18.58 | 3.16750000 | 47.2127 | 23.99 | 0.01003186 | 23.99 | 0.01003186 | 48.9502 | 72228.76 | 0.00 | 162485.02 | 110624.07 | 7.04459287 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.28 | 11.26 | 0.00829826 | 32257.2 | |
VAV_FLR_6 HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_FLR_6 | BANQUET_FLR_6; DINING_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27391.389 | 27391.389 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_FLR_6 FAN | Fan:VariableVolume | 6.709000 | 7.33423991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 27391.39 | 27391.39 | 1.0000 | 2.20027197 | 2.012700 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 12.89 | 10.78 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27391.39 | 0.50 | 0.00431558 | 0.50 | 3.16750000 | 157.3757 | 21.00 | 0.00790915 | 21.00 | 0.00790916 | 46.4254 | 14487.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | VAV_FLR_0 | BASEMENT | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 66436.070 | 53193.368 | 3.773400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2745 | 1004.8586 | 1.0932 | VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 2.515600 | 2.75003937 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | Sensible | 33218.04 | 33218.03 | 1.0000 | 2.75003937 | 2.515600 | 25.98 | 15.91 | 0.00830281 | 47272.6 | 10.89 | 10.26 | 0.00830281 | 31878.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33218.04 | 32.75 | 0.00561869 | 15.99 | 0.85445887 | 33.9664 | 24.00 | 0.00908853 | 24.00 | 0.00908901 | 44.3805 | 40640.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_FLR_0 HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_FLR_0 | BASEMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33057.483 | 33057.483 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 2.515600 | 2.75003937 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 33057.48 | 33057.48 | 1.0000 | 2.75003937 | 2.515600 | 14.04 | 9.99 | 0.00674854 | 31158.6 | 32.11 | 17.68 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33057.48 | 0.50 | 0.00431558 | 0.50 | 0.85445887 | 33.9664 | 21.00 | 0.00800000 | 24.00 | 0.00817113 | 39.9531 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_LAUNDRY HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 72144.620 | 57738.061 | 4.271170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7008 | 1004.8586 | 1.0932 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 4.271174 | 4.66922260 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | Sensible | 36072.31 | 35864.92 | 1.0000 | 3.11281223 | 2.847447 | 24.00 | 15.43 | 0.00853212 | 45834.1 | 11.44 | 10.68 | 0.00850000 | 32929.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36072.31 | 39.07 | 0.00562841 | 18.04 | 0.00000000 | 0.0000 | 24.00 | 0.00853212 | 24.00 | 0.00853212 | 41.6970 | 46039.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 70703.094 | 70703.094 | 4.271174 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 4.271174 | 4.66922260 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 35351.55 | 26449.88 | 1.0000 | 2.33461130 | 2.135587 | 21.00 | 13.60 | 0.00765211 | 40537.4 | 32.11 | 17.68 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35351.55 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00765211 | 21.00 | 0.00765211 | 44.9350 | 1543.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_LAUNDRY_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 70703.094 | 70703.094 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 4.271174 | 4.66922260 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 70703.09 | 52899.77 | 1.0000 | 4.66922260 | 4.271174 | 21.00 | 13.60 | 0.00765211 | 40537.4 | 32.11 | 17.68 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 70703.09 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00765211 | 21.00 | 0.00765211 | 44.9350 | 1543.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49947.540 | 36756.395 | 2.239700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6918 | 1004.8586 | 1.0932 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.239701 | 2.44842819 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 24973.77 | 24883.89 | 1.0000 | 1.63228472 | 1.493133 | 29.07 | 17.12 | 0.00852730 | 50993.3 | 11.40 | 10.66 | 0.00850000 | 32892.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24973.77 | 40.80 | 0.00563111 | 18.58 | 0.67638938 | 45.3000 | 23.99 | 0.00978038 | 23.99 | 0.00978038 | 47.7326 | 24119.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 48423.561 | 48423.561 | 2.239701 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.239701 | 2.44842819 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 24211.78 | 21597.92 | 1.0000 | 1.22421409 | 1.119851 | 14.81 | 10.36 | 0.00679542 | 32062.4 | 32.11 | 17.68 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24211.78 | 0.50 | 0.00431558 | 0.50 | 0.67638938 | 60.4000 | 21.00 | 0.00786835 | 21.00 | 0.00786835 | 46.1888 | 7705.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48423.561 | 48423.561 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.239701 | 2.44842819 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | Sensible | 48423.56 | 43195.83 | 1.0000 | 2.44842819 | 2.239701 | 14.81 | 10.36 | 0.00679542 | 32062.4 | 32.11 | 17.68 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48423.56 | 0.50 | 0.00431558 | 0.50 | 0.67638938 | 30.2000 | 21.00 | 0.00786835 | 21.00 | 0.00786835 | 46.1888 | 7705.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN HP COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 63140.630 | 47563.205 | 2.970150 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3990 | 1004.8586 | 1.0932 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.970155 | 3.24695575 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 31570.31 | 27451.24 | 1.0000 | 2.16463387 | 1.980100 | 25.88 | 16.81 | 0.00944563 | 50087.6 | 11.44 | 10.68 | 0.00850000 | 32931.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31570.31 | 39.60 | 0.00562924 | 18.21 | 0.36735036 | 18.5521 | 23.95 | 0.00998426 | 23.97 | 0.00998426 | 48.7651 | 31931.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN HEATING COIL | Coil:Heating:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 60998.589 | 60998.589 | 2.970155 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.970155 | 3.24695575 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 30499.29 | 22918.36 | 1.0000 | 1.62347788 | 1.485077 | 18.27 | 12.10 | 0.00715095 | 36481.4 | 32.11 | 17.68 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30499.29 | 0.50 | 0.00431558 | 0.50 | 0.36735036 | 24.7361 | 20.77 | 0.00755113 | 21.00 | 0.00753831 | 44.2765 | 1698.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN_SUPPHEATCOIL | COIL:HEATING:ELECTRIC | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60998.589 | 60998.589 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.970155 | 3.24695575 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | Sensible | 60998.59 | 45836.71 | 1.0000 | 3.24695575 | 2.970155 | 18.27 | 12.10 | 0.00715095 | 36481.4 | 32.11 | 17.68 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60998.59 | 0.50 | 0.00431558 | 0.50 | 0.36735036 | 12.3681 | 20.77 | 0.00755113 | 21.00 | 0.00753831 | 44.2765 | 1698.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_FLR_1_OA_CONTROLLER | FixedDryBulb | 0.00 | 8.72 | - | |||
VAV_FLR_6_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.71 | - | |||
VAV_FLR_0_OA_CONTROLLER | FixedDryBulb | 0.00 | 3.77 | - | |||
PSZ_LAUNDRY_OA_CONTROLLER | FixedDryBulb | 0.00 | 4.27 | - | |||
PSZ_CAFE_OA_CONTROLLER | FixedDryBulb | 0.68 | 2.24 | - | |||
PSZ_KITCHEN_OA_CONTROLLER | FixedDryBulb | 0.37 | 2.97 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_FLR_6_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_FLR_6_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1406.83 | 4059.17 | 2.17 |
RETAIL_1_FLR_1 | 3703.67 | 4369.00 | 568.17 |
RETAIL_2_FLR_1 | 2237.17 | 4537.00 | 430.00 |
MECH_FLR_1 | 1838.83 | 5159.83 | 0.00 |
STORAGE_FLR_1 | 1632.33 | 5918.83 | 44.17 |
LAUNDRY_FLR_1 | 8755.17 | 4310.83 | 4310.83 |
CAFE_FLR_1 | 4923.67 | 2620.83 | 497.00 |
LOBBY_FLR_1 | 2978.00 | 3302.00 | 884.83 |
ROOM_1_FLR_3 | 861.67 | 7426.50 | 404.00 |
ROOM_2_FLR_3 | 1129.00 | 7311.00 | 590.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 268.67 | 8597.00 | 238.17 |
ROOM_5_FLR_3 | 872.50 | 7326.17 | 385.50 |
ROOM_6_FLR_3 | 1180.83 | 7258.00 | 554.17 |
CORRIDOR_FLR_3 | 4916.00 | 2459.17 | 2456.17 |
ROOM_1_FLR_6 | 1774.17 | 7164.67 | 1006.17 |
ROOM_2_FLR_6 | 2009.67 | 7106.83 | 1211.33 |
ROOM_3_MULT9_FLR_6 | 1180.33 | 7119.67 | 515.33 |
BANQUET_FLR_6 | 4490.33 | 3209.67 | 969.17 |
DINING_FLR_6 | 5106.00 | 2376.17 | 931.00 |
KITCHEN_FLR_6 | 8600.50 | 6156.00 | 6156.00 |
CORRIDOR_FLR_6 | 5629.50 | 2354.50 | 2018.67 |
Facility | 8760.00 | 8760.00 | 7787.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.50 | 0.00 | 0.50 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 3.33 | 0.00 | 3.33 |
ROOM_2_FLR_3 | 0.00 | 9.83 | 0.00 | 9.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 26.00 | 0.00 | 26.00 |
ROOM_5_FLR_3 | 0.00 | 0.67 | 0.00 | 0.67 |
ROOM_6_FLR_3 | 0.00 | 24.00 | 0.00 | 24.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 5.17 | 0.00 | 5.17 |
ROOM_2_FLR_6 | 0.00 | 8.33 | 0.00 | 8.33 |
ROOM_3_MULT9_FLR_6 | 0.00 | 1.33 | 0.00 | 1.33 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 39.33 | 0.00 | 39.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.794 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.297 | 0.134 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.378 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.648 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.688 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.397 | 0.143 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 5.179 | 0.105 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.696 | 0.043 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.365 | 0.172 | 0.000 | 0.053 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.361 | 0.173 | 0.000 | 0.048 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.401 | 0.077 | 0.000 | 0.087 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.371 | 0.172 | 0.000 | 0.053 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.365 | 0.173 | 0.000 | 0.053 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.073 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.366 | 0.173 | 0.000 | 0.061 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.363 | 0.173 | 0.000 | 0.054 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.422 | 0.140 | 0.000 | 0.097 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.980 | 0.050 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 5.164 | 0.050 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 16.404 | 0.144 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.072 | 0.035 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.640 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.062 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.943 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.399 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.457 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 0.000 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 3.240 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 1.242 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.172 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.276 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 4.223 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.000 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV_FLR_0 | 61.78 | 106.50 | 4826.41 | 1978.83 | 0.8545 | 0.854 |
RETAIL_1_FLR_1 | VAV_FLR_1 | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV_FLR_1 | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV_FLR_1 | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV_FLR_1 | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | PSZ_CAFE | 82.55 | 142.30 | 748.35 | 188.86 | 0.6764 | 0.676 |
LOBBY_FLR_1 | VAV_FLR_1 | 245.05 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 39.02 | 0.062 | ||
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 39.02 | 0.062 | ||
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | 24.52 | 0.837 | |||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 24.53 | 0.837 | ||
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 39.02 | 0.062 | ||
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 39.02 | 0.062 | ||
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 389.40 | 0.475 | ||
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 39.02 | 0.015 | ||
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 39.02 | 0.015 | ||
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 24.53 | 0.099 | ||
BANQUET_FLR_6 | VAV_FLR_6 | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV_FLR_6 | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | PSZ_KITCHEN | 12.90 | 22.24 | 314.87 | 103.30 | 0.3674 | 0.367 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 412.12 | 0.126 | ||
Total Facility | 873.11 | 1604.23 | 35184.81 | 11345.29 | 1.8982 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 32870239.28 | 0.00 | 32870239.28 | 0.00 | 32870239.28 | 26946214.98 | 0.00 | 4244.97 | 4515.03 | 0.00 |
RETAIL_1_FLR_1 | 5250921.42 | 0.00 | 5250921.42 | 305216.72 | 5556138.14 | 2498216.28 | 0.03 | 0.08 | 8759.89 | 0.00 |
RETAIL_2_FLR_1 | 3638014.52 | 0.00 | 3638014.52 | 117814.04 | 3755828.56 | 2892943.94 | 2694.92 | 330.35 | 5734.73 | 0.00 |
MECH_FLR_1 | 3620369.04 | 0.00 | 3620369.04 | 278442.40 | 3898811.44 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2224881.12 | 0.00 | 2224881.12 | 160645.93 | 2385527.05 | 1821682.01 | 3080.25 | 238.26 | 5441.49 | 0.00 |
LAUNDRY_FLR_1 | 51502462.82 | 0.00 | 51502462.82 | 380198.88 | 51882661.70 | 0.00 | 0.00 | 0.00 | 4995.00 | 0.00 |
CAFE_FLR_1 | 33225890.80 | 0.00 | 33225890.80 | 674698.84 | 33900589.64 | 21330615.53 | 0.00 | 5387.86 | 3372.14 | 0.00 |
LOBBY_FLR_1 | 75349596.16 | 0.00 | 75349596.16 | 1927768.70 | 77277364.86 | 59728886.00 | 2764.04 | 466.60 | 5529.36 | 0.00 |
ROOM_1_FLR_3 | 1501341.60 | 54071.07 | 1555412.67 | 177156.17 | 1732568.85 | 1946875.62 | 2433.25 | 5688.25 | 638.50 | 0.00 |
ROOM_2_FLR_3 | 1483452.36 | 49373.34 | 1532825.70 | 177142.66 | 1709968.35 | 1946647.51 | 2432.41 | 5792.24 | 535.36 | 0.00 |
ROOM_3_MULT19_FLR_3 | 4589593.87 | 212.02 | 4589805.89 | 49428.56 | 4639234.45 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 6905.25 |
ROOM_4_MULT19_FLR_3 | 19674078.39 | 55992.83 | 19730071.22 | 49442.08 | 19779513.30 | 26405105.73 | 2432.37 | 5703.71 | 623.92 | 0.00 |
ROOM_5_FLR_3 | 1524283.65 | 54201.74 | 1578485.39 | 177156.17 | 1755641.56 | 1946875.62 | 2433.33 | 5688.17 | 638.50 | 0.00 |
ROOM_6_FLR_3 | 1499732.67 | 53656.51 | 1553389.19 | 177142.66 | 1730531.84 | 1946647.51 | 2431.46 | 5713.85 | 614.69 | 0.00 |
CORRIDOR_FLR_3 | 2942955.76 | 0.00 | 2942955.76 | 214217.46 | 3157173.22 | 14972100.18 | 8760.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 376363.93 | 62821.07 | 439185.00 | 177191.96 | 616376.97 | 486718.90 | 2213.61 | 5693.58 | 852.81 | 0.00 |
ROOM_2_FLR_6 | 372364.88 | 54795.75 | 427160.63 | 177178.45 | 604339.08 | 486661.88 | 2250.49 | 5790.18 | 719.33 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2454465.00 | 63007.29 | 2517472.29 | 90657.61 | 2608129.90 | 3126920.42 | 2433.33 | 5688.33 | 638.33 | 0.00 |
BANQUET_FLR_6 | 43140184.96 | 0.00 | 43140184.96 | 432658.25 | 43572843.20 | 37458366.31 | 1235.06 | 3373.37 | 4151.57 | 0.00 |
DINING_FLR_6 | 44713278.23 | 0.00 | 44713278.23 | 432658.25 | 45145936.47 | 37458366.31 | 0.00 | 1097.87 | 7662.13 | 0.00 |
KITCHEN_FLR_6 | 44251423.69 | 0.00 | 44251423.69 | 387329.44 | 44638753.13 | 11584760.86 | 0.00 | 3765.83 | 4994.17 | 0.00 |
CORRIDOR_FLR_6 | 770754.75 | 0.00 | 770754.75 | 379096.44 | 1149851.19 | 3961413.96 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.22E+10 | 5801461.58 | 0.22E+10 | 17852245.51 | 0.23E+10 | 0.43E+10 | 8760.00 | 7525.98 | 8760.00 | 6905.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.0423 | 0.0000 | 1.0423 | 0.0000 | 1.0423 | 0.8545 | 0.00 | 4244.97 | 4515.03 |
RETAIL_1_FLR_1 | 0.1665 | 0.0000 | 0.1665 | 0.0097 | 0.1762 | 0.0792 | 0.03 | 0.08 | 8759.89 |
RETAIL_2_FLR_1 | 0.1154 | 0.0000 | 0.1154 | 0.0037 | 0.1191 | 0.0917 | 2694.92 | 330.35 | 5734.73 |
MECH_FLR_1 | 0.1148 | 0.0000 | 0.1148 | 0.0088 | 0.1236 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0706 | 0.0000 | 0.0706 | 0.0051 | 0.0756 | 0.0578 | 3080.25 | 238.26 | 5441.49 |
LAUNDRY_FLR_1 | 1.6331 | 0.0000 | 1.6331 | 0.0121 | 1.6452 | 0.0000 | 0.00 | 0.00 | 4995.00 |
CAFE_FLR_1 | 1.0536 | 0.0000 | 1.0536 | 0.0214 | 1.0750 | 0.6764 | 0.00 | 5387.86 | 3372.14 |
LOBBY_FLR_1 | 2.3893 | 0.0000 | 2.3893 | 0.0611 | 2.4504 | 1.8940 | 2764.04 | 466.60 | 5529.36 |
ROOM_1_FLR_3 | 0.0476 | 0.0017 | 0.0493 | 0.0056 | 0.0549 | 0.0617 | 2433.25 | 5688.25 | 638.50 |
ROOM_2_FLR_3 | 0.0470 | 0.0016 | 0.0486 | 0.0056 | 0.0542 | 0.0617 | 2432.41 | 5792.24 | 535.36 |
ROOM_4_MULT19_FLR_3 | 0.6239 | 0.0018 | 0.6256 | 0.0016 | 0.6272 | 0.8373 | 2432.37 | 5703.71 | 623.92 |
ROOM_5_FLR_3 | 0.0483 | 0.0017 | 0.0501 | 0.0056 | 0.0557 | 0.0617 | 2433.33 | 5688.17 | 638.50 |
ROOM_6_FLR_3 | 0.0476 | 0.0017 | 0.0493 | 0.0056 | 0.0549 | 0.0617 | 2431.46 | 5713.85 | 614.69 |
CORRIDOR_FLR_3 | 0.0933 | 0.0000 | 0.0933 | 0.0068 | 0.1001 | 0.4748 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.0119 | 0.0020 | 0.0139 | 0.0056 | 0.0195 | 0.0154 | 2213.61 | 5693.58 | 852.81 |
ROOM_2_FLR_6 | 0.0118 | 0.0017 | 0.0135 | 0.0056 | 0.0192 | 0.0154 | 2250.49 | 5790.18 | 719.33 |
ROOM_3_MULT9_FLR_6 | 0.0778 | 0.0020 | 0.0798 | 0.0029 | 0.0827 | 0.0992 | 2433.33 | 5688.33 | 638.33 |
BANQUET_FLR_6 | 1.3680 | 0.0000 | 1.3680 | 0.0137 | 1.3817 | 1.1878 | 1235.06 | 3373.37 | 4151.57 |
DINING_FLR_6 | 1.4178 | 0.0000 | 1.4178 | 0.0137 | 1.4316 | 1.1878 | 0.00 | 1097.87 | 7662.13 |
KITCHEN_FLR_6 | 1.4032 | 0.0000 | 1.4032 | 0.0123 | 1.4155 | 0.3674 | 0.00 | 3765.83 | 4994.17 |
CORRIDOR_FLR_6 | 0.0244 | 0.0000 | 0.0244 | 0.0120 | 0.0365 | 0.1256 | 8760.00 | 0.00 | 0.00 |
Total Facility | 60.0721 | 0.1835 | 60.2556 | 0.4470 | 60.7025 | 73.9670 | 8760.00 | 7525.98 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_FLR_1 | 0.11E+09 | 0.00 | 0.11E+09 | 66941728.23 | 0.00 | 0.00 | 8760.00 | 0.00 |
VAV_FLR_6 | 0.10E+09 | 0.00 | 0.10E+09 | 74916732.61 | 0.00 | 0.00 | 8760.00 | 0.00 |
VAV_FLR_0 | 39283433.21 | 0.00 | 39283433.21 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
PSZ_LAUNDRY | 61549233.42 | 0.00 | 61549233.42 | 0.00 | 0.00 | 0.00 | 4995.00 | 0.00 |
PSZ_CAFE | 39707384.78 | 0.00 | 39707384.78 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
PSZ_KITCHEN | 52883708.02 | 0.00 | 52883708.02 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_FLR_1 | 3.4138 | 0.0000 | 3.4138 | 2.1227 | 0.00 | 0.00 | 8760.00 |
VAV_FLR_6 | 3.3293 | 0.0000 | 3.3293 | 2.3756 | 0.00 | 0.00 | 8760.00 |
VAV_FLR_0 | 1.2457 | 0.0000 | 1.2457 | 0.8545 | 0.00 | 0.00 | 8760.00 |
PSZ_LAUNDRY | 1.9517 | 0.0000 | 1.9517 | 0.0000 | 0.00 | 0.00 | 4995.00 |
PSZ_CAFE | 1.2591 | 0.0000 | 1.2591 | 0.6764 | 0.00 | 0.00 | 8760.00 |
PSZ_KITCHEN | 1.6769 | 0.0000 | 1.6769 | 0.3674 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_FLR_1 | 0.00 | 64.50 | 4911.50 | 0.00 | 0.00 | 0.00 | 3784.00 | 0.00 | 0.00 | 0.00 |
VAV_FLR_6 | 0.00 | 64.67 | 4085.83 | 0.00 | 0.00 | 0.00 | 4609.50 | 0.00 | 0.00 | 0.00 |
VAV_FLR_0 | 0.00 | 0.00 | 4548.99 | 0.00 | 0.00 | 0.00 | 4211.01 | 0.00 | 0.00 | 0.00 |
PSZ_LAUNDRY | 0.00 | 0.00 | 4995.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_CAFE | 0.00 | 5373.59 | 3386.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_KITCHEN | 0.00 | 3765.67 | 4994.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_FLR_1 | 0.0000 | 4.1064 | 3.8812 | 0.0000 | 0.0000 | 0.0000 | 2.7971 | 0.0000 | 0.0000 | 0.0000 |
VAV_FLR_6 | 0.0000 | 3.7802 | 3.8218 | 0.0000 | 0.0000 | 0.0000 | 2.8880 | 0.0000 | 0.0000 | 0.0000 |
VAV_FLR_0 | 0.0000 | 0.0000 | 1.4538 | 0.0000 | 0.0000 | 0.0000 | 1.0211 | 0.0000 | 0.0000 | 0.0000 |
PSZ_LAUNDRY | 0.0000 | 0.0000 | 3.4228 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ_CAFE | 0.0000 | 0.8084 | 1.9747 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ_KITCHEN | 0.0000 | 0.4391 | 2.6105 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 6 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1285 |
Defaulted Fields | 1318 |
Fields with Defaults | 4098 |
Autosized Fields | 374 |
Autosizable Fields | 572 |
Autocalculated Fields | 278 |
Autocalculatable Fields | 537 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 7802.66 | 109014.68 | 01-MAR-02:30 | 544738.40 | 28-JUN-18:10 |
Electricity:Building | 3195.05 | 37866.17 | 02-JAN-02:10 | 208035.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 384.14 | 4218.04 | 02-JAN-02:10 | 29343.82 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 3187.96 | 37725.02 | 02-JAN-02:10 | 207793.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 241.03 | 2190.14 | 02-JAN-02:10 | 19711.29 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 241.03 | 2190.14 | 02-JAN-02:10 | 19711.29 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 22.10 | 252.63 | 02-JAN-02:10 | 1660.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.92 | 108.29 | 02-JAN-02:10 | 974.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.92 | 108.29 | 02-JAN-02:10 | 974.63 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 25.60 | 292.55 | 02-JAN-02:10 | 1922.56 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.80 | 125.40 | 02-JAN-02:10 | 1128.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.80 | 125.40 | 02-JAN-02:10 | 1128.63 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 41.66 | 441.91 | 02-JAN-02:10 | 3226.11 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 29.18 | 265.18 | 02-JAN-02:10 | 2386.66 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 29.18 | 265.18 | 02-JAN-02:10 | 2386.66 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 12.58 | 132.58 | 02-JAN-02:10 | 976.54 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 8.98 | 81.60 | 02-JAN-02:10 | 734.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 8.98 | 81.60 | 02-JAN-02:10 | 734.39 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 45.66 | 487.82 | 02-JAN-02:10 | 3526.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 31.32 | 284.60 | 02-JAN-02:10 | 2561.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 31.32 | 284.60 | 02-JAN-02:10 | 2561.44 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 350.46 | 3941.97 | 02-JAN-02:10 | 26504.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 201.46 | 1830.55 | 02-JAN-02:10 | 16474.99 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 201.46 | 1830.55 | 02-JAN-02:10 | 16474.99 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 35.36 | 389.80 | 01-JAN-02:10 | 2642.31 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 35.36 | 389.75 | 01-JAN-02:10 | 2642.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 492.14 | 5849.00 | 01-JAN-02:10 | 36399.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 297.14 | 2515.76 | 01-JAN-02:10 | 22870.56 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 297.14 | 2515.76 | 01-JAN-02:10 | 22870.56 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 492.27 | 5850.60 | 01-JAN-02:10 | 36409.55 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 297.22 | 2516.45 | 01-JAN-02:10 | 22876.81 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 297.22 | 2516.45 | 01-JAN-02:10 | 22876.81 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 35.36 | 389.80 | 01-JAN-02:10 | 2642.31 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 35.36 | 389.75 | 01-JAN-02:10 | 2642.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.84 | 97.45 | 01-JAN-02:10 | 660.58 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.83 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.83 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.84 | 97.44 | 01-JAN-02:10 | 660.50 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.78 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.78 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 58.30 | 692.83 | 01-JAN-02:10 | 4311.66 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.20 | 298.00 | 01-JAN-02:10 | 2709.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.20 | 298.00 | 01-JAN-02:10 | 2709.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 230.86 | 2749.09 | 02-JAN-02:10 | 11246.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 230.86 | 2749.09 | 02-JAN-02:10 | 11246.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 459.16 | 6380.86 | 02-JAN-02:10 | 19096.59 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.69 | 133.44 | 02-JAN-02:10 | 1200.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.69 | 133.44 | 02-JAN-02:10 | 1200.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1661.82 | 24317.47 | 02-JAN-02:10 | 89286.95 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1661.82 | 24317.47 | 02-JAN-02:10 | 89286.95 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 437.38 | 6106.28 | 01-JAN-00:10 | 16602.84 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.96 | 732.77 | 31-MAR-22:30 | 2792.39 | 03-SEP-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 38.38 | 685.58 | 30-MAR-22:20 | 2063.66 | 05-SEP-06:10 |
LowTempRefrigeration:Refrigeration:Electricity | 15.83 | 0.00 | 01-JAN-11:10 | 1306.77 | 26-SEP-06:50 |
MedTempRefrigeration:Refrigeration:Electricity | 21.04 | 636.02 | 20-MAY-05:00 | 718.94 | 13-NOV-15:00 |
Fans:Electricity | 1178.73 | 25070.53 | 03-JAN-08:10 | 59236.70 | 28-JUN-18:40 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 3427.02 | 25731.05 | 24-MAR-10:00 | 329542.87 | 28-JUN-18:10 |
ExteriorEquipment:Electricity | 841.97 | 10954.76 | 02-JAN-02:20 | 50420.89 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.24 | 382.76 | 02-JAN-02:20 | 1343.17 | 18-JAN-21:10 |
ElectricityPurchased:Facility | 7802.66 | 109014.68 | 01-MAR-02:30 | 544738.40 | 28-JUN-18:10 |
ElectricityPurchased:Plant | 7802.66 | 109014.68 | 01-MAR-02:30 | 544738.40 | 28-JUN-18:10 |
Cogeneration:ElectricityPurchased | 7802.66 | 109014.68 | 01-MAR-02:30 | 544738.40 | 28-JUN-18:10 |
General:Cogeneration:ElectricityPurchased | 7802.66 | 109014.68 | 01-MAR-02:30 | 544738.40 | 28-JUN-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 7802.66 | 109014.68 | 01-MAR-02:30 | 544738.40 | 28-JUN-18:10 |
ElectricityNet:Plant | 7802.66 | 109014.68 | 01-MAR-02:30 | 544738.40 | 28-JUN-18:10 |
Cogeneration:ElectricityNet | 7802.66 | 109014.68 | 01-MAR-02:30 | 544738.40 | 28-JUN-18:10 |
General:Cogeneration:ElectricityNet | 7802.66 | 109014.68 | 01-MAR-02:30 | 544738.40 | 28-JUN-18:10 |
General:Fans:Electricity | 1178.73 | 25070.53 | 03-JAN-08:10 | 59236.70 | 28-JUN-18:40 |
Heating:Electricity | 84.75 | 0.00 | 01-JAN-11:50 | 91482.41 | 07-DEC-05:00 |
General:Heating:Electricity | 84.75 | 0.00 | 01-JAN-11:50 | 91482.41 | 07-DEC-05:00 |
Cooling:Electricity | 2141.30 | 0.00 | 01-JAN-00:10 | 269751.30 | 28-JUN-18:10 |
General:Cooling:Electricity | 2141.30 | 0.00 | 01-JAN-00:10 | 269751.30 | 28-JUN-18:10 |
ExteriorLights:Electricity | 322.47 | 0.00 | 01-JAN-07:30 | 20502.98 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 322.47 | 0.00 | 01-JAN-07:30 | 20502.98 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
Pumps:Electricity | 1.51 | 47.91 | 08-JAN-10:00 | 47.91 | 04-JAN-20:50 |
General:Pumps:Electricity | 1.51 | 47.91 | 08-JAN-10:00 | 47.91 | 04-JAN-20:50 |
WIRED_LTG_ELECTRICITY | 53.72 | 0.00 | 01-JAN-00:10 | 4267.60 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4123.36 | 22985.75 | 29-JUL-01:50 | 328760.48 | 23-JAN-18:30 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 2334.52 | 9623.85 | 29-JUL-01:50 | 227554.38 | 18-JAN-21:30 |
WaterSystems:NaturalGas | 2334.52 | 9623.85 | 29-JUL-01:50 | 227554.38 | 18-JAN-21:30 |
Water Heater:WaterSystems:NaturalGas | 2334.52 | 9623.85 | 29-JUL-01:50 | 227554.38 | 18-JAN-21:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 18-APR-20:50 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 18-APR-20:50 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 18-APR-20:50 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 18-APR-20:50 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 18-APR-20:50 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 18-APR-20:50 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 03-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:20 | 0.00 | 03-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 14500.68 | 107067.93 | 19-FEB-14:30 | 1244916.52 | 28-JUN-18:20 |
EnergyTransfer:Building | 6692.10 | 88142.35 | 12-FEB-15:00 | 498701.80 | 28-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 725.38 | 7497.86 | 07-DEC-04:00 | 37765.58 | 28-JUN-10:40 |
Refrigeration:EnergyTransfer | 182.77 | 4015.95 | 30-MAR-22:20 | 10385.77 | 05-SEP-06:10 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.39 | 2007.97 | 30-MAR-22:20 | 5192.89 | 05-SEP-06:10 |
General:Refrigeration:EnergyTransfer | 91.39 | 2007.97 | 30-MAR-22:20 | 5192.89 | 05-SEP-06:10 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.39 | 2007.97 | 30-MAR-22:20 | 5192.89 | 05-SEP-06:10 |
EnergyTransfer:Plant | 693.47 | 9032.55 | 06-JUL-02:30 | 52176.32 | 20-JAN-07:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.59 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.80 | 1996.41 | 20-MAY-05:00 | 2575.17 | 13-NOV-15:00 |
EnergyTransfer:Zone:BASEMENT | 521.27 | 4030.73 | 27-MAR-11:50 | 30605.78 | 08-SEP-20:00 |
Heating:EnergyTransfer | 42.42 | 0.00 | 01-JAN-11:00 | 45904.29 | 07-DEC-05:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 42.42 | 0.00 | 01-JAN-11:00 | 45904.29 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 6558.29 | 85065.78 | 19-FEB-14:30 | 495117.73 | 28-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 521.27 | 4030.73 | 27-MAR-11:50 | 30605.78 | 08-SEP-20:00 |
General:Cooling:EnergyTransfer | 6558.29 | 85065.78 | 19-FEB-14:30 | 495117.73 | 28-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 521.27 | 4030.73 | 27-MAR-11:50 | 30605.78 | 08-SEP-20:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 61.97 | 0.01 | 22-JAN-07:20 | 5790.03 | 02-OCT-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.25 | 0.00 | 01-JAN-00:10 | 1117.56 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.25 | 0.00 | 01-JAN-00:10 | 1117.56 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 61.73 | 0.00 | 01-JAN-01:30 | 5790.03 | 02-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 61.73 | 0.00 | 01-JAN-01:30 | 5790.03 | 02-OCT-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 46.35 | 925.54 | 12-FEB-15:20 | 3183.39 | 28-JUN-19:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 46.35 | 925.54 | 12-FEB-15:20 | 3183.39 | 28-JUN-19:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 46.35 | 925.54 | 12-FEB-15:20 | 3183.39 | 28-JUN-19:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 47.25 | 865.64 | 07-DEC-05:00 | 3791.43 | 28-JUN-19:50 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 47.25 | 865.64 | 07-DEC-05:00 | 3791.43 | 28-JUN-19:50 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 47.25 | 865.64 | 07-DEC-05:00 | 3791.43 | 28-JUN-19:50 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 26.24 | 0.01 | 17-DEC-05:30 | 2288.55 | 28-JUN-18:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 134.56 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 134.56 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 26.24 | 0.00 | 01-JAN-05:10 | 2288.55 | 28-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 26.24 | 0.00 | 01-JAN-05:10 | 2288.55 | 28-JUN-18:30 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 616.12 | 8240.65 | 07-DEC-05:00 | 40005.77 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 616.12 | 8240.65 | 07-DEC-05:00 | 40005.77 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 616.12 | 8240.65 | 07-DEC-05:00 | 40005.77 | 28-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 280.60 | 440.28 | 26-MAR-17:00 | 18621.62 | 28-SEP-15:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 280.60 | 440.28 | 26-MAR-17:00 | 18621.62 | 28-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 280.60 | 440.28 | 26-MAR-17:00 | 18621.62 | 28-SEP-15:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 968.15 | 19069.00 | 12-FEB-15:20 | 54358.29 | 28-JUN-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 968.15 | 19069.00 | 12-FEB-15:20 | 54358.29 | 28-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 968.15 | 19069.00 | 12-FEB-15:20 | 54358.29 | 28-JUN-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 117.08 | 0.00 | 01-JAN-08:00 | 16882.86 | 05-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.37 | 0.00 | 01-JAN-08:00 | 4170.41 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 4.37 | 0.00 | 01-JAN-08:00 | 4170.41 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 112.71 | 0.00 | 01-JAN-00:10 | 16882.86 | 05-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 112.71 | 0.00 | 01-JAN-00:10 | 16882.86 | 05-OCT-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 98.53 | 0.00 | 01-JAN-08:00 | 16857.71 | 29-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 6.37 | 0.00 | 01-JAN-08:00 | 5523.31 | 07-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 6.37 | 0.00 | 01-JAN-08:00 | 5523.31 | 07-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 92.16 | 0.00 | 01-JAN-00:10 | 16857.71 | 29-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 92.16 | 0.00 | 01-JAN-00:10 | 16857.71 | 29-JUN-18:20 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 629.61 | 0.00 | 01-JAN-00:10 | 72756.43 | 20-NOV-13:40 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 629.61 | 0.00 | 01-JAN-00:10 | 72756.43 | 20-NOV-13:40 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 629.61 | 0.00 | 01-JAN-00:10 | 72756.43 | 20-NOV-13:40 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 731.89 | 0.00 | 01-JAN-08:00 | 104818.91 | 30-JUN-18:30 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 8.90 | 0.00 | 01-JAN-08:00 | 16342.46 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 8.90 | 0.00 | 01-JAN-08:00 | 16342.46 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 722.98 | 0.00 | 01-JAN-00:10 | 104818.91 | 30-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 722.98 | 0.00 | 01-JAN-00:10 | 104818.91 | 30-JUN-18:30 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 120.39 | 0.00 | 01-JAN-08:00 | 13846.32 | 29-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 4.29 | 0.00 | 01-JAN-08:00 | 4170.96 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 4.29 | 0.00 | 01-JAN-08:00 | 4170.96 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 116.10 | 0.00 | 01-JAN-00:10 | 13846.32 | 29-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 116.10 | 0.00 | 01-JAN-00:10 | 13846.32 | 29-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 100.38 | 0.00 | 01-JAN-08:00 | 15668.01 | 06-MAY-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 5.87 | 0.00 | 01-JAN-08:00 | 4565.49 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 5.87 | 0.00 | 01-JAN-08:00 | 4565.49 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 94.51 | 0.00 | 01-JAN-00:10 | 15668.01 | 06-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 94.51 | 0.00 | 01-JAN-00:10 | 15668.01 | 06-MAY-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 194.02 | 0.00 | 01-JAN-00:10 | 18400.94 | 28-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 194.02 | 0.00 | 01-JAN-00:10 | 18400.94 | 28-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 194.02 | 0.00 | 01-JAN-00:10 | 18400.94 | 28-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 31.69 | 0.00 | 01-JAN-08:50 | 4722.91 | 28-SEP-15:30 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.64 | 0.00 | 01-JAN-08:50 | 1586.17 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.64 | 0.00 | 01-JAN-08:50 | 1586.17 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 29.05 | 0.00 | 01-JAN-00:10 | 4722.91 | 28-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 29.05 | 0.00 | 01-JAN-00:10 | 4722.91 | 28-SEP-15:30 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 27.70 | 0.00 | 01-JAN-11:00 | 4648.40 | 29-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.35 | 0.00 | 01-JAN-11:00 | 1686.44 | 07-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.35 | 0.00 | 01-JAN-11:00 | 1686.44 | 07-DEC-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 24.35 | 0.00 | 01-JAN-00:10 | 4648.40 | 29-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 24.35 | 0.00 | 01-JAN-00:10 | 4648.40 | 29-JUN-18:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 177.00 | 0.00 | 01-JAN-08:00 | 22699.38 | 05-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 6.30 | 0.00 | 01-JAN-08:00 | 6170.92 | 07-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 6.30 | 0.00 | 01-JAN-08:00 | 6170.92 | 07-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 170.70 | 0.00 | 01-JAN-00:10 | 22699.38 | 05-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 170.70 | 0.00 | 01-JAN-00:10 | 22699.38 | 05-OCT-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 515.09 | 9532.90 | 07-DEC-09:30 | 27564.01 | 28-JUN-18:30 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 515.09 | 9532.90 | 07-DEC-09:30 | 27564.01 | 28-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 515.09 | 9532.90 | 07-DEC-09:30 | 27564.01 | 28-JUN-18:30 |
EnergyTransfer:Zone:DINING_FLR_6 | 542.10 | 10278.69 | 07-DEC-09:20 | 28853.70 | 28-JUN-18:30 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 542.10 | 10278.69 | 07-DEC-09:20 | 28853.70 | 28-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 542.10 | 10278.69 | 07-DEC-09:20 | 28853.70 | 28-JUN-18:30 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 633.99 | 5251.88 | 07-DEC-04:00 | 32724.27 | 28-JUN-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 633.99 | 5251.88 | 07-DEC-04:00 | 32724.27 | 28-JUN-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 113.28 | 0.00 | 01-JAN-00:10 | 12092.82 | 07-SEP-13:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.09 | 0.00 | 01-JAN-00:10 | 1919.06 | 07-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.09 | 0.00 | 01-JAN-00:10 | 1919.06 | 07-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 113.19 | 0.00 | 01-JAN-00:10 | 12092.82 | 07-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 113.19 | 0.00 | 01-JAN-00:10 | 12092.82 | 07-SEP-13:30 |
PlantLoopHeatingDemand:Facility | 602.08 | 6712.17 | 25-JUL-00:20 | 47162.69 | 23-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 602.08 | 6712.17 | 25-JUL-00:20 | 47162.69 | 23-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 602.08 | 6712.17 | 25-JUL-00:20 | 47162.69 | 23-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 602.08 | 6712.17 | 25-JUL-00:20 | 47162.69 | 23-JAN-07:10 |
EnergyTransfer:HVAC | 7115.11 | 0.00 | 14-JAN-08:00 | 732212.84 | 10-SEP-21:50 |
HeatingCoils:EnergyTransfer | 114.15 | 0.00 | 01-JAN-11:50 | 128889.28 | 07-DEC-05:00 |
CoolingCoils:EnergyTransfer | 7000.97 | 0.00 | 01-JAN-00:10 | 732212.84 | 10-SEP-21:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 602.08 | 6712.17 | 25-JUL-00:20 | 47162.69 | 23-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 602.08 | 6712.17 | 25-JUL-00:20 | 47162.69 | 23-JAN-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -521.272 | 0.000 | 0.000 | 133.891 | 241.034 | 143.105 | 0.000 | 0.000 | 0.000 | 3.242 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.247 | -61.725 | 0.000 | 0.000 | 14.643 | 11.918 | 10.186 | 31.737 | 0.000 | 0.905 | 5.461 | 0.000 | -11.945 | 0.000 | -1.427 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -46.351 | 0.000 | 0.000 | 16.141 | 13.801 | 11.795 | 0.000 | 0.000 | 0.348 | 4.892 | 0.000 | 0.000 | 0.000 | -0.625 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -47.254 | 0.000 | 0.000 | 3.424 | 29.185 | 12.471 | 0.000 | 0.000 | 0.815 | 2.827 | 0.000 | 0.000 | 0.000 | -1.468 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.001 | -26.240 | 0.000 | 0.000 | 2.738 | 8.980 | 3.598 | 0.000 | 0.000 | 0.480 | 11.188 | 0.000 | 0.000 | 0.000 | -0.746 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -616.123 | 0.000 | 0.000 | 10.551 | 5.547 | 658.131 | 0.000 | 0.000 | 1.105 | 0.000 | 0.000 | 0.000 | 0.000 | -2.188 | -57.023 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -280.606 | 0.000 | 0.000 | 182.575 | 31.322 | 14.341 | 86.922 | 0.000 | 1.961 | 5.420 | 0.000 | -38.274 | 0.000 | -3.661 | -0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -968.156 | 0.000 | 0.000 | 538.415 | 201.459 | 148.998 | 118.735 | 0.000 | 5.644 | 16.829 | 0.000 | -51.385 | 0.000 | -10.540 | -0.002 |
ROOM_1_FLR_3 | 4.368 | -112.709 | 0.000 | 0.000 | 0.000 | 0.000 | 9.622 | 24.885 | 10.478 | 81.069 | 0.000 | 2.827 | 12.687 | 0.000 | -29.554 | 0.000 | -3.672 | -0.001 |
ROOM_2_FLR_3 | 6.368 | -92.163 | 0.000 | 0.000 | 0.000 | 0.000 | 9.457 | 24.882 | 10.477 | 63.921 | 0.000 | 2.727 | 10.569 | 0.000 | -32.004 | 0.000 | -4.233 | -0.000 |
ROOM_3_MULT19_FLR_3 | 0.000 | -629.597 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 297.141 | 194.997 | 382.750 | 0.000 | 6.862 | 32.487 | 0.000 | -256.585 | 0.000 | -28.055 | -0.002 |
ROOM_4_MULT19_FLR_3 | 8.905 | -722.967 | 0.000 | 0.000 | 0.000 | 0.000 | 180.470 | 297.222 | 195.050 | 216.085 | 0.000 | 14.662 | 20.257 | 0.000 | -173.546 | 0.000 | -36.137 | -0.000 |
ROOM_5_FLR_3 | 4.289 | -116.102 | 0.000 | 0.000 | 0.000 | 0.000 | 9.611 | 24.885 | 10.478 | 83.031 | 0.000 | 2.824 | 12.620 | 0.000 | -27.925 | 0.000 | -3.711 | -0.001 |
ROOM_6_FLR_3 | 5.868 | -94.506 | 0.000 | 0.000 | 0.000 | 0.000 | 9.458 | 24.882 | 10.477 | 64.426 | 0.000 | 2.724 | 10.113 | 0.000 | -29.104 | 0.000 | -4.337 | -0.001 |
CORRIDOR_FLR_3 | 0.000 | -194.018 | 0.000 | 0.000 | 0.000 | 0.000 | 105.458 | 92.258 | 0.000 | 70.822 | 0.000 | 2.474 | 0.004 | 0.000 | -46.053 | 0.000 | -4.934 | -26.007 |
ROOM_1_FLR_6 | 2.639 | -29.050 | 0.000 | 0.000 | 0.000 | 0.000 | 2.409 | 6.221 | 2.620 | 19.792 | 0.000 | 0.704 | 2.796 | 0.000 | -7.197 | 0.000 | -0.934 | -0.000 |
ROOM_2_FLR_6 | 3.348 | -24.351 | 0.000 | 0.000 | 0.000 | 0.000 | 2.371 | 6.220 | 2.619 | 15.617 | 0.000 | 0.677 | 2.325 | 0.000 | -7.764 | 0.000 | -1.063 | -0.000 |
ROOM_3_MULT9_FLR_6 | 6.301 | -170.697 | 0.000 | 0.000 | 0.000 | 0.000 | 21.640 | 35.197 | 23.098 | 101.047 | 0.000 | 3.320 | 18.746 | 0.000 | -33.473 | 0.000 | -5.179 | -0.000 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -515.094 | 0.000 | 0.000 | 318.968 | 55.004 | 175.857 | 18.702 | 0.000 | 1.249 | 0.000 | 0.000 | -27.220 | 0.000 | -2.365 | -25.100 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -542.108 | 0.000 | 0.000 | 317.136 | 55.004 | 175.857 | 18.228 | 0.000 | 1.242 | 5.196 | 0.000 | -28.140 | 0.000 | -2.414 | -0.002 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -633.975 | 0.000 | 0.000 | 27.937 | 14.685 | 554.015 | 25.816 | 0.000 | 1.108 | 38.092 | 0.000 | -25.424 | 0.000 | -2.254 | -0.002 |
CORRIDOR_FLR_6 | 0.087 | -113.185 | 0.000 | 0.000 | 0.000 | 0.000 | 28.291 | 24.410 | 0.000 | 32.742 | 0.000 | 1.085 | 48.885 | 0.000 | -20.195 | 0.000 | -2.119 | -0.001 |
Total Facility | 42.173 | -2299.346 | 0.249 | -4258.905 | 0.000 | 0.000 | 1945.206 | 1526.141 | 2368.647 | 1431.442 | 0.000 | 55.743 | 264.636 | 0.000 | -845.788 | 0.000 | -122.064 | -108.144 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-SEP-20:00 | 0.00 | 0.00 | 0.00 | -30603.83 | 0.00 | 0.00 | 5183.79 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3923.79 |
RETAIL_1_FLR_1 | 02-OCT-12:40 | 0.00 | 0.00 | 0.00 | -5790.31 | 0.00 | 0.00 | 150.60 | 270.73 | 252.59 | 5372.67 | 0.00 | 103.03 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -359.31 |
RETAIL_2_FLR_1 | 28-JUN-19:10 | 0.00 | 0.00 | 0.00 | -3182.86 | 0.00 | 0.00 | 610.37 | 1128.63 | 793.93 | 0.00 | 0.00 | 60.39 | 589.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 28-JUN-19:50 | 0.00 | 0.00 | 0.00 | -3790.73 | 0.00 | 0.00 | 129.08 | 2386.66 | 839.45 | 0.00 | 0.00 | 125.00 | 310.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 28-JUN-18:25 | 0.00 | 0.00 | 0.00 | -2288.46 | 0.00 | 0.00 | 99.29 | 652.79 | 229.41 | 0.00 | 0.00 | 87.40 | 1219.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -40003.42 | 0.00 | 0.00 | 408.85 | 453.60 | 44299.38 | 0.00 | 0.00 | 164.59 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5323.00 |
CAFE_FLR_1 | 28-SEP-15:10 | 0.00 | 0.00 | 0.00 | -18622.36 | 0.00 | 0.00 | 4947.34 | 711.51 | 355.63 | 10892.14 | 0.00 | 304.49 | 1411.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 28-JUN-20:10 | 0.00 | 0.00 | 0.00 | -54352.55 | 0.00 | 0.00 | 23498.88 | 14644.43 | 9501.36 | 2879.56 | 0.00 | 814.02 | 3014.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 15-NOV-16:12 | 0.00 | -21017.88 | 0.00 | 0.00 | 0.00 | 0.00 | 235.29 | 536.29 | 200.18 | 12222.45 | 0.00 | 0.00 | 7924.55 | 0.00 | -0.00 | 0.00 | -100.89 | 0.00 |
ROOM_2_FLR_3 | 23-OCT-16:41 | 0.00 | -21723.88 | 0.00 | 0.00 | 0.00 | 0.00 | 193.47 | 536.23 | 505.67 | 4898.72 | 0.00 | 0.00 | 15610.63 | 0.00 | -0.00 | 0.00 | -20.83 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-NOV-13:40 | 0.00 | -72750.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6403.76 | 2352.88 | 79682.61 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5.92 | -15683.29 |
ROOM_4_MULT19_FLR_3 | 16-MAR-21:51 | 0.00 | -147246.78 | 0.00 | 0.00 | 0.00 | 0.00 | 7279.80 | 15327.46 | 6668.31 | 0.00 | 0.00 | 0.00 | 126015.78 | 0.00 | -7448.26 | 0.00 | -596.31 | 0.00 |
ROOM_5_FLR_3 | 13-MAY-08:62 | 0.00 | -17635.77 | 0.00 | 0.00 | 0.00 | 0.00 | 130.72 | 1072.59 | 653.23 | 9248.04 | 0.00 | 0.00 | 6560.43 | 0.00 | -0.00 | 0.00 | -29.22 | 0.00 |
ROOM_6_FLR_3 | 27-APR-08:51 | 0.00 | -18687.36 | 0.00 | 0.00 | 0.00 | 0.00 | 71.56 | 842.65 | 452.99 | 7619.43 | 0.00 | 0.00 | 9879.27 | 0.00 | -0.00 | 0.00 | -178.54 | 0.00 |
CORRIDOR_FLR_3 | 28-JUN-18:25 | 0.00 | -18406.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4080.36 | 6706.42 | 0.00 | 7789.28 | 0.00 | 465.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -634.96 |
ROOM_1_FLR_6 | 15-NOV-16:12 | 0.00 | -5721.07 | 0.00 | 0.00 | 0.00 | 0.00 | 58.82 | 134.07 | 50.05 | 2965.71 | 0.00 | 0.00 | 2537.99 | 0.00 | -0.00 | 0.00 | -25.57 | 0.00 |
ROOM_2_FLR_6 | 23-OCT-16:41 | 0.00 | -5919.41 | 0.00 | 0.00 | 0.00 | 0.00 | 48.37 | 134.06 | 126.42 | 1143.17 | 0.00 | 0.00 | 4472.40 | 0.00 | -0.00 | 0.00 | -5.01 | 0.00 |
ROOM_3_MULT9_FLR_6 | 09-JAN-16:12 | 0.00 | -27265.14 | 0.00 | 0.00 | 0.00 | 0.00 | 529.40 | 758.55 | 441.28 | 9422.28 | 0.00 | 0.00 | 17034.90 | 0.00 | -0.00 | 0.00 | -921.27 | 0.00 |
BANQUET_FLR_6 | 28-JUN-18:25 | 0.00 | 0.00 | 0.00 | -27562.75 | 0.00 | 0.00 | 12163.39 | 3998.32 | 6747.90 | 4649.18 | 0.00 | 233.94 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -229.98 |
DINING_FLR_6 | 28-JUN-18:25 | 0.00 | 0.00 | 0.00 | -28852.36 | 0.00 | 0.00 | 12163.39 | 3998.32 | 6747.90 | 4619.42 | 0.00 | 233.94 | 1089.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 28-JUN-10:40 | 0.00 | 0.00 | 0.00 | -32707.98 | 0.00 | 0.00 | 309.22 | 333.59 | 24375.41 | 4390.27 | 0.00 | 175.24 | 3124.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 07-SEP-13:30 | 0.00 | -12092.83 | 0.00 | 0.00 | 0.00 | 0.00 | 308.46 | 554.51 | 0.00 | 4633.94 | 0.00 | 156.07 | 6439.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-JUN-18:13 | 0.00 | -275335.53 | 0.00 | -227933.17 | 0.00 | 0.00 | 74718.44 | 107831.13 | 120597.93 | 149168.73 | 0.00 | 10020.26 | 40932.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 07-DEC-05:00 | 0.00 | 0.00 | 1117.55 | 0.00 | 0.00 | 0.00 | 805.58 | 108.29 | 144.34 | 0.00 | 0.00 | 0.00 | 186.82 | 0.00 | -2107.10 | 0.00 | -255.48 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 07-DEC-05:00 | 0.00 | 0.00 | 134.56 | 0.00 | 0.00 | 0.00 | 151.76 | 81.60 | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -134.47 | -284.43 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 27-MAR-08:62 | 10026.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.65 | 842.75 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1544.91 | 0.00 | -290.29 | -9591.45 |
ROOM_2_FLR_3 | 07-DEC-09:02 | 17518.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.88 | 842.65 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2469.71 | 0.00 | -370.78 | -16082.85 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 27-JAN-09:53 | 63989.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1700.69 | 10065.80 | 8433.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -85.89 | 0.00 | -155.04 | -83948.10 |
ROOM_5_FLR_3 | 08-MAR-16:14 | 5875.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.99 | 536.29 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54.82 | 0.00 | -221.87 | -6571.13 |
ROOM_6_FLR_3 | 18-MAR-21:53 | 9454.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.65 | 1627.84 | 358.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2791.47 | 0.00 | -157.54 | -8806.40 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 26-MAR-08:62 | 4268.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 268.15 | 163.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -413.22 | 0.00 | -85.76 | -4242.29 |
ROOM_2_FLR_6 | 07-DEC-09:02 | 4585.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 210.66 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -597.96 | 0.00 | -92.90 | -4245.69 |
ROOM_3_MULT9_FLR_6 | 27-MAR-08:62 | 15204.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.26 | 1192.00 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -965.99 | 0.00 | -336.33 | -16329.32 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 07-DEC-07:10 | 1919.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.32 | 1109.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3005.52 | 0.00 | -281.70 | -474.87 |
Total Facility | 07-DEC-09:02 | -59412.51 | 107409.51 | 0.00 | -107409.51 | 0.00 | 0.00 | 23218.20 | 53630.19 | 88294.42 | 63592.34 | 0.00 | 0.00 | 0.00 | 0.00 | -22689.09 | 0.00 | -10420.87 | -136212.69 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_FLR_1 | 8.7515 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.7178 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_6 | 6.7090 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.7090 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_0 | 3.7734 | 0.0000 | 106.4990 | 1.0000 | Calculated from schedules | 0.8545 | 3.7734 | 0.2264 | 1.0000 | Not calculated | 0.8545 | 0.2264 | ||
PSZ_LAUNDRY | 4.2712 | 0.0000 | 8.4000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2712 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PSZ_CAFE | 2.2397 | 0.0000 | 142.3000 | 1.0000 | Calculated from schedules | 0.6764 | 2.2397 | 0.3020 | 1.0000 | Not calculated | 0.6764 | 0.3020 | ||
PSZ_KITCHEN | 2.9702 | 0.0000 | 22.2380 | 1.0000 | Calculated from schedules | 0.3674 | 2.9702 | 0.1237 | 1.0000 | Not calculated | 0.3674 | 0.1237 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_FLR_1 | 3.4872 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4872 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_6 | 3.1518 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1518 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_0 | 1.1320 | 0.0000 | 106.4990 | 1.0000 | Calculated from schedules | 0.8545 | 1.1320 | 1.0000 | 1.0000 | Not calculated | 0.8545 | 0.7548 | ||
PSZ_LAUNDRY | 4.2712 | 0.0000 | 8.4000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2712 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PSZ_CAFE | 2.2397 | 0.0000 | 142.3000 | 1.0000 | Calculated from schedules | 0.6764 | 2.2397 | 1.0000 | 1.0000 | Not calculated | 0.6764 | 0.3020 | ||
PSZ_KITCHEN | 2.9702 | 0.0000 | 22.2380 | 1.0000 | Calculated from schedules | 0.3674 | 2.9702 | 1.0000 | 1.0000 | Not calculated | 0.3674 | 0.1237 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV_FLR_0 | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.8545 | 1.0000 | 0.8545 | 1.000 | 0.8545 |
RETAIL_1_FLR_1 | VAV_FLR_1 | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV_FLR_1 | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | PSZ_CAFE | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.6764 | 1.0000 | 0.6764 | 1.000 | 0.6764 |
LOBBY_FLR_1 | VAV_FLR_1 | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV_FLR_6 | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.3674 | 1.0000 | 0.3674 | 1.000 | 0.3674 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_FLR_1 | 0.00 | 0.001240 | 1711.9288 | 0.0000 | 0.0000 | 0.0000 | |
VAV_FLR_6 | 0.00 | 0.003581 | 663.3149 | 0.0000 | 0.0000 | 0.0000 | |
VAV_FLR_0 | 0.000000 | 106.50 | 0.000432 | 1978.8302 | 0.8545 | 0.8545 | 0.8545 |
PSZ_LAUNDRY | 0.000000 | 8.40 | 0.000000 | 78.0395 | 0.0000 | 0.0000 | 0.0000 |
PSZ_CAFE | 0.000000 | 142.30 | 0.003581 | 188.8619 | 0.6764 | 0.6764 | 0.6764 |
PSZ_KITCHEN | 0.000000 | 22.24 | 0.003556 | 103.3045 | 0.3674 | 0.3674 | 0.3674 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV_FLR_0 | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 3.7734 | 3.7734 | 1.1320 | No | 0.8545 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.5821 | 0.5821 | 0.1746 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.3802 | 0.3802 | 0.1426 | No | 0.0000 | 0.0000 | 0.3750 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.4462 | 0.4462 | 0.1339 | No | 0.0000 | 0.0000 | 0.3000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.2435 | 0.2435 | 0.0898 | No | 0.0000 | 0.0000 | 0.3690 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.2712 | 4.2712 | 4.2712 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | PSZ_CAFE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2397 | 2.2397 | 2.2397 | No | 0.6764 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 7.0995 | 7.0995 | 2.9463 | No | 0.0000 | 0.0000 | 0.4150 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 3.2847 | 3.2847 | 1.5767 | No | 0.0000 | 0.0000 | 0.4800 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 3.4243 | 3.4243 | 1.5752 | No | 0.0000 | 0.0000 | 0.4600 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.9702 | 2.9702 | 2.9702 | No | 0.3674 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_FLR_1 | 8.7515 | 8.7178 | 8.7515 | 3.4872 | 0.0000 | 1.0000 |
VAV_FLR_6 | 6.7090 | 6.7090 | 6.7090 | 3.1518 | 0.0000 | 1.0000 |
VAV_FLR_0 | 3.7734 | 3.7734 | 3.7734 | 1.1320 | 0.8545 | 1.0000 |
PSZ_LAUNDRY | 4.2712 | 4.2712 | 4.2712 | 4.2712 | 0.0000 | 1.0000 |
PSZ_CAFE | 2.2397 | 2.2397 | 2.2397 | 2.2397 | 0.6764 | 1.0000 |
PSZ_KITCHEN | 2.9702 | 2.9702 | 2.9702 | 2.9702 | 0.3674 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV_FLR_0 | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 1.1320 | 1.1320 | 1.1320 | No | 0.8545 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.1746 | 0.7567 | 0.1746 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.1426 | 0.5228 | 0.1426 | No | 0.0000 | 0.0000 | 0.2727 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.1339 | 0.5801 | 0.1339 | No | 0.0000 | 0.0000 | 0.2308 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 0.0898 | 0.3333 | 0.0898 | No | 0.0000 | 0.0000 | 0.2695 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.2712 | 4.2712 | 4.2712 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | PSZ_CAFE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.2397 | 2.2397 | 2.2397 | No | 0.6764 | 0.8698 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 2.9463 | 10.0458 | 2.9463 | No | 0.0000 | 0.0000 | 0.2933 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.5767 | 4.8614 | 1.5767 | No | 0.0000 | 0.0000 | 0.3243 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:PARALLELPIU:REHEAT | 1.5752 | 4.9995 | 1.5752 | No | 0.0000 | 0.0000 | 0.3151 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.9702 | 2.9702 | 2.9702 | No | 0.3674 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_FLR_1 | 3.4872 | 3.4872 | 12.2387 | 3.4872 | 0.0000 | 1.0000 |
VAV_FLR_6 | 3.1518 | 3.1518 | 9.8608 | 3.1518 | 0.0000 | 1.0000 |
VAV_FLR_0 | 1.1320 | 1.1320 | 1.1320 | 1.1320 | 0.8545 | 1.0000 |
PSZ_LAUNDRY | 4.2712 | 4.2712 | 4.2712 | 4.2712 | 0.0000 | 1.0000 |
PSZ_CAFE | 2.2397 | 2.2397 | 2.2397 | 2.2397 | 0.6764 | 1.0000 |
PSZ_KITCHEN | 2.9702 | 2.9702 | 2.9702 | 2.9702 | 0.3674 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 39.33 |
Number of hours not met | 39.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 84.75 | 91482.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2141.30 | 269751.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1526.14 | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 322.47 | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 15.55 | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 11.51 | 365.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.24 | 1343.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1178.73 | 59236.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1.51 | 47.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 2334.52 | 227554.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.83 | 1306.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.04 | 718.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1705.78 | 7802.66 |
Natural Gas | 1788.84 | 4123.36 |
Additional | 0.00 | 0.00 |
Total | 3494.62 | 11926.02 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 134.52 |
Space Heating | 7.47 |
Space Cooling | 188.74 |
Fans (All) | 103.90 |
Service Water Heating | 0.00 |
Receptacle Equipment | 146.48 |
Miscellaneous (All) | 687.74 |
Subtotal | 687.74 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 205.77 |
Miscellaneous (All) | 363.44 |
Subtotal | 363.44 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.80 |
Space Heating | 0.71 |
Space Cooling | 17.95 |
Fans (All) | 9.88 |
Service Water Heating | 19.58 |
Receptacle Equipment | 28.93 |
Miscellaneous | 10.15 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 3061. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 3061. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 3061. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | RETAIL_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | RETAIL_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8696.00 | 64.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8710.50 | 49.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 64.00 | 0.00 | 0.00 | 0.00 |
Average | 8752.93 | 7.07 | 0.00 | 0.00 | 0.00 |
Sum | 192564.50 | 155.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4149.50 | 4.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4153.67 | 0.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4147.67 | 6.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 6.33 | 0.00 | 0.00 | 0.00 |
Average | 288886.54 | 0.51 | 0.00 | 0.00 | 0.00 |
Sum | 6355503.83 | 11.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8688.33 | 71.67 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8560.00 | 200.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8608.17 | 151.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8716.17 | 43.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8277.50 | 482.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8720.33 | 39.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8697.67 | 62.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 6885.50 | 1874.50 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8719.33 | 40.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8542.33 | 217.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8589.17 | 170.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8677.50 | 82.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 7563.33 | 1196.67 | 0.00 | 0.00 | 0.00 |
Min | 6885.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1874.50 | 0.00 | 0.00 | 0.00 |
Average | 8549.28 | 210.72 | 0.00 | 0.00 | 0.00 |
Sum | 188084.17 | 4635.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 36861.33 | 341.67 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 690462.50 | 19954.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2060008.17 | 55420.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4141.17 | 12.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4141.50 | 12.50 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4142.83 | 11.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 80023.00 | 20335.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4142.00 | 12.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1198745.17 | 46969.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1208823.33 | 36891.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 107122.00 | 1147.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 92920.33 | 13025.67 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2060008.17 | 55420.83 | 0.00 | 0.00 | 0.00 |
Average | 280062.74 | 8824.30 | 0.00 | 0.00 | 0.00 |
Sum | 6161380.33 | 194134.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:41
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.427226E+11 | 25618.83 | 27-JAN-21:00 | 17.00 | 6.99 | 0.822212E+10 | 4837.53 | 09-JAN-22:10 | 17.00 | 6.99 |
February | 0.327989E+11 | 23983.51 | 01-FEB-21:00 | 11.00 | 5.83 | 0.741996E+10 | 4837.50 | 07-FEB-22:10 | 10.00 | 7.84 |
March | 0.329764E+11 | 21682.77 | 01-MAR-21:00 | 15.50 | 11.31 | 0.820157E+10 | 4837.45 | 10-MAR-22:30 | 14.70 | 9.43 |
April | 0.354612E+11 | 23167.39 | 14-APR-20:00 | 31.00 | 13.66 | 0.798108E+10 | 4837.41 | 26-APR-21:00 | 16.00 | 9.61 |
May | 0.347371E+11 | 22282.78 | 01-MAY-20:00 | 26.00 | 10.19 | 0.825020E+10 | 4837.35 | 11-MAY-00:00 | 24.00 | 14.04 |
June | 0.368147E+11 | 23604.12 | 30-JUN-20:00 | 36.00 | 16.46 | 0.799875E+10 | 4837.33 | 27-JUN-21:19 | 36.00 | 16.46 |
July | 0.464099E+11 | 27063.44 | 21-JUL-20:00 | 37.00 | 20.84 | 0.823277E+10 | 4837.36 | 29-JUL-03:49 | 21.17 | 17.78 |
August | 0.501548E+11 | 28378.27 | 15-AUG-20:00 | 35.00 | 18.06 | 0.826760E+10 | 4837.36 | 07-AUG-04:10 | 35.00 | 18.06 |
September | 0.536813E+11 | 30605.78 | 08-SEP-20:00 | 33.80 | 19.77 | 0.797810E+10 | 4837.44 | 22-SEP-01:49 | 17.88 | 14.36 |
October | 0.541701E+11 | 30202.92 | 04-OCT-20:00 | 28.00 | 16.16 | 0.823676E+10 | 4837.47 | 23-OCT-23:19 | 15.67 | 10.77 |
November | 0.512643E+11 | 29782.83 | 01-NOV-20:00 | 21.00 | 13.76 | 0.796358E+10 | 4837.48 | 20-NOV-23:30 | 13.50 | 9.17 |
December | 0.500777E+11 | 28836.07 | 01-DEC-21:00 | 11.00 | 4.29 | 0.821750E+10 | 4837.50 | 12-DEC-23:10 | 12.00 | 9.47 |
Annual Sum or Average | 0.521269E+12 | 0.969700E+11 | ||||||||
Minimum of Months | 0.327989E+11 | 21682.77 | 11.00 | 4.29 | 0.741996E+10 | 4837.33 | 10.00 | 6.99 | ||
Maximum of Months | 0.541701E+11 | 30605.78 | 37.00 | 20.84 | 0.826760E+10 | 4837.53 | 36.00 | 18.06 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.464140E+10 | 5378.27 | 14-JAN-13:40 | 26.67 | 10.98 | 0.702430E+09 | 461.16 | 19-JAN-22:10 | 14.67 | 6.84 |
February | 0.268067E+10 | 3883.04 | 21-FEB-14:20 | 20.33 | 11.62 | 0.604441E+09 | 435.94 | 21-FEB-22:10 | 14.00 | 12.80 |
March | 0.337772E+10 | 4330.95 | 18-MAR-13:40 | 26.27 | 12.12 | 0.697989E+09 | 491.85 | 17-MAR-21:10 | 26.27 | 12.12 |
April | 0.535994E+10 | 4744.59 | 14-APR-14:10 | 34.17 | 14.15 | 0.737251E+09 | 491.85 | 18-APR-21:19 | 22.67 | 8.95 |
May | 0.559494E+10 | 3942.58 | 04-MAY-14:10 | 35.00 | 13.92 | 0.780409E+09 | 491.85 | 11-MAY-21:30 | 25.50 | 12.63 |
June | 0.665790E+10 | 4677.99 | 28-JUN-18:02 | 40.83 | 17.83 | 0.790985E+09 | 491.85 | 28-JUN-21:10 | 34.67 | 14.46 |
July | 0.662580E+10 | 4425.94 | 19-JUL-13:30 | 40.00 | 22.22 | 0.817989E+09 | 491.85 | 03-JUL-22:10 | 40.00 | 22.22 |
August | 0.681172E+10 | 5225.40 | 28-AUG-12:30 | 37.00 | 20.85 | 0.816842E+09 | 491.85 | 01-AUG-21:40 | 37.00 | 20.85 |
September | 0.646263E+10 | 5752.68 | 28-SEP-13:30 | 36.10 | 16.03 | 0.779778E+09 | 491.85 | 21-SEP-21:10 | 36.10 | 16.03 |
October | 0.555910E+10 | 5790.03 | 02-OCT-12:40 | 34.00 | 19.29 | 0.748376E+09 | 491.85 | 10-OCT-21:30 | 23.00 | 11.48 |
November | 0.432039E+10 | 5497.31 | 20-NOV-14:10 | 27.00 | 11.68 | 0.678665E+09 | 490.53 | 01-NOV-21:10 | 27.00 | 11.68 |
December | 0.363291E+10 | 5170.84 | 25-DEC-13:30 | 25.50 | 11.81 | 0.676403E+09 | 453.64 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.617251E+11 | 0.883156E+10 | ||||||||
Minimum of Months | 0.268067E+10 | 3883.04 | 20.33 | 10.98 | 0.604441E+09 | 435.94 | 14.00 | 6.84 | ||
Maximum of Months | 0.681172E+10 | 5790.03 | 40.83 | 22.22 | 0.817989E+09 | 491.85 | 40.00 | 22.22 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344782E+10 | 2034.55 | 31-JAN-20:20 | 17.33 | 6.39 | 0.914705E+09 | 569.56 | 17-JAN-22:40 | 17.33 | 6.39 |
February | 0.286061E+10 | 1790.52 | 28-FEB-20:20 | 13.67 | 8.73 | 0.801926E+09 | 569.56 | 09-FEB-22:30 | 13.67 | 8.73 |
March | 0.337223E+10 | 2255.66 | 16-MAR-19:20 | 23.27 | 12.61 | 0.910569E+09 | 569.56 | 30-MAR-21:10 | 15.22 | 5.04 |
April | 0.396790E+10 | 2839.29 | 14-APR-18:15 | 33.00 | 13.86 | 0.920227E+09 | 569.56 | 27-APR-21:10 | 21.83 | 10.30 |
May | 0.427257E+10 | 2832.69 | 31-MAY-19:10 | 33.50 | 12.61 | 0.959744E+09 | 569.56 | 02-MAY-00:10 | 33.50 | 12.61 |
June | 0.459281E+10 | 3183.39 | 28-JUN-19:10 | 39.50 | 16.83 | 0.940470E+09 | 569.56 | 02-JUN-22:30 | 39.50 | 16.83 |
July | 0.458549E+10 | 3012.48 | 20-JUL-19:10 | 36.83 | 18.90 | 0.967837E+09 | 569.56 | 01-JUL-00:40 | 36.83 | 18.90 |
August | 0.456350E+10 | 2982.82 | 25-AUG-18:20 | 38.33 | 16.79 | 0.971102E+09 | 569.56 | 01-AUG-03:09 | 38.33 | 16.79 |
September | 0.424607E+10 | 2876.18 | 07-SEP-18:15 | 35.53 | 19.30 | 0.934979E+09 | 569.56 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.388234E+10 | 2680.14 | 05-OCT-18:20 | 31.00 | 15.12 | 0.941493E+09 | 569.56 | 24-OCT-21:30 | 16.50 | 5.95 |
November | 0.336399E+10 | 2306.49 | 01-NOV-18:17 | 23.33 | 14.33 | 0.888604E+09 | 569.56 | 01-NOV-21:10 | 18.00 | 13.11 |
December | 0.319550E+10 | 1920.43 | 22-DEC-20:20 | 16.00 | 6.52 | 0.891024E+09 | 569.56 | 27-DEC-22:10 | 11.77 | 6.16 |
Annual Sum or Average | 0.463508E+11 | 0.110427E+11 | ||||||||
Minimum of Months | 0.286061E+10 | 1790.52 | 13.67 | 6.39 | 0.801926E+09 | 569.56 | 11.77 | 5.04 | ||
Maximum of Months | 0.459281E+10 | 3183.39 | 39.50 | 19.30 | 0.971102E+09 | 569.56 | 39.50 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307355E+10 | 2007.16 | 27-JAN-21:00 | 17.00 | 6.99 | 0.189854E+09 | 120.45 | 06-JAN-22:19 | 17.00 | 6.99 |
February | 0.262459E+10 | 1525.64 | 22-FEB-21:00 | 13.00 | 10.72 | 0.167460E+09 | 120.45 | 22-FEB-22:10 | 13.00 | 10.46 |
March | 0.314052E+10 | 2384.40 | 17-MAR-20:00 | 20.50 | 13.06 | 0.191406E+09 | 120.45 | 30-MAR-21:10 | 15.22 | 5.04 |
April | 0.392140E+10 | 3090.09 | 14-APR-20:00 | 31.00 | 13.66 | 0.195366E+09 | 120.45 | 27-APR-21:10 | 21.83 | 10.30 |
May | 0.453776E+10 | 3314.66 | 31-MAY-19:50 | 31.50 | 12.08 | 0.204153E+09 | 120.45 | 03-MAY-22:10 | 31.50 | 12.08 |
June | 0.524070E+10 | 3791.43 | 28-JUN-19:50 | 37.50 | 15.82 | 0.199051E+09 | 120.45 | 08-JUN-23:10 | 37.50 | 15.82 |
July | 0.526575E+10 | 3570.83 | 20-JUL-20:00 | 36.00 | 18.39 | 0.204885E+09 | 120.45 | 01-JUL-00:00 | 36.00 | 18.39 |
August | 0.507847E+10 | 3416.21 | 10-AUG-20:00 | 36.00 | 18.37 | 0.205650E+09 | 120.45 | 30-AUG-21:49 | 31.17 | 17.37 |
September | 0.462857E+10 | 3313.86 | 08-SEP-20:00 | 33.80 | 19.77 | 0.198186E+09 | 120.45 | 05-SEP-22:10 | 33.80 | 19.77 |
October | 0.379987E+10 | 3086.87 | 03-OCT-20:00 | 30.00 | 18.25 | 0.199258E+09 | 120.45 | 24-OCT-21:30 | 16.50 | 5.95 |
November | 0.308007E+10 | 2392.53 | 02-NOV-20:00 | 21.00 | 15.83 | 0.186062E+09 | 120.45 | 08-NOV-22:30 | 11.50 | 4.74 |
December | 0.286258E+10 | 1704.43 | 26-DEC-21:00 | 15.00 | 6.89 | 0.183444E+09 | 120.45 | 26-DEC-22:49 | 14.17 | 6.88 |
Annual Sum or Average | 0.472538E+11 | 0.232477E+10 | ||||||||
Minimum of Months | 0.262459E+10 | 1525.64 | 13.00 | 6.89 | 0.167460E+09 | 120.45 | 11.50 | 4.74 | ||
Maximum of Months | 0.526575E+10 | 3791.43 | 37.50 | 19.77 | 0.205650E+09 | 120.45 | 37.50 | 19.77 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168664E+10 | 750.49 | 27-JAN-21:00 | 17.00 | 6.99 | 0.129967E+09 | 84.44 | 31-JAN-22:10 | 14.48 | 5.13 |
February | 0.145748E+10 | 704.91 | 16-FEB-21:20 | 13.67 | 12.88 | 0.113521E+09 | 81.24 | 22-FEB-22:10 | 13.00 | 10.46 |
March | 0.172404E+10 | 812.18 | 17-MAR-20:00 | 20.50 | 13.06 | 0.132424E+09 | 90.27 | 17-MAR-21:10 | 21.42 | 12.50 |
April | 0.209243E+10 | 1408.41 | 25-APR-18:20 | 31.33 | 14.97 | 0.144003E+09 | 92.66 | 18-APR-21:10 | 31.33 | 14.97 |
May | 0.248324E+10 | 1736.96 | 31-MAY-18:30 | 35.00 | 13.18 | 0.153268E+09 | 92.66 | 10-MAY-22:10 | 35.00 | 13.18 |
June | 0.312147E+10 | 2288.55 | 28-JUN-18:25 | 40.50 | 17.53 | 0.151909E+09 | 92.66 | 09-JUN-00:30 | 40.50 | 17.53 |
July | 0.305316E+10 | 2009.54 | 20-JUL-18:30 | 38.00 | 19.12 | 0.156426E+09 | 92.66 | 07-JUL-21:30 | 38.00 | 19.12 |
August | 0.284735E+10 | 1728.52 | 25-AUG-18:15 | 38.33 | 16.79 | 0.156435E+09 | 92.66 | 01-AUG-21:40 | 38.33 | 16.79 |
September | 0.252972E+10 | 1587.01 | 08-SEP-19:20 | 34.93 | 20.02 | 0.149834E+09 | 92.66 | 08-SEP-21:10 | 31.73 | 19.33 |
October | 0.205590E+10 | 1347.74 | 03-OCT-19:30 | 30.50 | 18.39 | 0.143498E+09 | 92.66 | 10-OCT-21:30 | 23.00 | 11.48 |
November | 0.170399E+10 | 813.53 | 02-NOV-20:00 | 21.00 | 15.83 | 0.128048E+09 | 89.83 | 02-NOV-21:10 | 20.00 | 15.60 |
December | 0.148424E+10 | 717.90 | 26-DEC-21:20 | 15.00 | 7.02 | 0.124403E+09 | 82.76 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.262396E+11 | 0.168374E+10 | ||||||||
Minimum of Months | 0.145748E+10 | 704.91 | 13.67 | 6.99 | 0.113521E+09 | 81.24 | 13.00 | 5.13 | ||
Maximum of Months | 0.312147E+10 | 2288.55 | 40.50 | 20.02 | 0.156435E+09 | 92.66 | 40.50 | 19.33 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506240E+11 | 38231.11 | 31-JAN-21:00 | 16.00 | 5.74 | 0.649337E+09 | 381.52 | 06-JAN-22:49 | 16.00 | 5.74 |
February | 0.451931E+11 | 37936.97 | 09-FEB-21:00 | 16.00 | 9.23 | 0.587070E+09 | 381.54 | 09-FEB-22:10 | 15.67 | 8.75 |
March | 0.508868E+11 | 38668.29 | 16-MAR-20:00 | 22.20 | 12.56 | 0.652395E+09 | 381.62 | 03-MAR-22:10 | 22.20 | 12.56 |
April | 0.511700E+11 | 39313.25 | 14-APR-20:00 | 31.00 | 13.66 | 0.629506E+09 | 381.54 | 16-APR-23:10 | 18.83 | 12.52 |
May | 0.536233E+11 | 39446.36 | 31-MAY-20:00 | 31.00 | 11.94 | 0.650722E+09 | 381.55 | 26-MAY-03:30 | 31.00 | 11.94 |
June | 0.530547E+11 | 40005.77 | 28-JUN-20:00 | 37.00 | 15.57 | 0.630889E+09 | 381.54 | 30-JUN-04:19 | 27.67 | 15.78 |
July | 0.543247E+11 | 39809.03 | 21-JUL-20:00 | 37.00 | 20.84 | 0.649376E+09 | 381.74 | 29-JUL-01:10 | 23.00 | 18.80 |
August | 0.543373E+11 | 39715.96 | 10-AUG-20:00 | 36.00 | 18.37 | 0.652132E+09 | 381.72 | 04-AUG-23:49 | 36.00 | 18.37 |
September | 0.518724E+11 | 39560.58 | 08-SEP-20:00 | 33.80 | 19.77 | 0.629314E+09 | 381.74 | 26-SEP-00:10 | 21.52 | 16.90 |
October | 0.520947E+11 | 39213.80 | 03-OCT-20:00 | 30.00 | 18.25 | 0.649660E+09 | 381.70 | 04-OCT-04:00 | 21.00 | 17.09 |
November | 0.492030E+11 | 38517.40 | 01-NOV-20:00 | 21.00 | 13.76 | 0.628137E+09 | 381.74 | 13-NOV-22:10 | 16.58 | 16.05 |
December | 0.497372E+11 | 37996.97 | 22-DEC-21:00 | 14.00 | 5.51 | 0.649332E+09 | 381.52 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.616121E+12 | 0.765787E+10 | ||||||||
Minimum of Months | 0.451931E+11 | 37936.97 | 14.00 | 5.51 | 0.587070E+09 | 381.52 | 14.83 | 5.74 | ||
Maximum of Months | 0.543373E+11 | 40005.77 | 37.00 | 20.84 | 0.652395E+09 | 381.74 | 36.00 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224131E+11 | 18617.24 | 14-JAN-13:30 | 26.50 | 10.97 | 0.103458E+11 | 6462.86 | 30-JAN-22:10 | 12.83 | 5.60 |
February | 0.154546E+11 | 13950.85 | 25-FEB-14:30 | 17.50 | 9.25 | 0.923815E+10 | 6462.77 | 09-FEB-23:10 | 17.50 | 9.25 |
March | 0.181164E+11 | 15549.46 | 18-MAR-13:30 | 26.35 | 12.25 | 0.104574E+11 | 6463.61 | 16-MAR-21:00 | 26.35 | 12.25 |
April | 0.233141E+11 | 16361.85 | 14-APR-15:10 | 35.00 | 14.57 | 0.106370E+11 | 6463.53 | 25-APR-02:09 | 24.00 | 12.37 |
May | 0.244226E+11 | 13915.14 | 04-MAY-15:10 | 35.00 | 13.92 | 0.110229E+11 | 6464.11 | 11-MAY-01:10 | 23.83 | 13.98 |
June | 0.276853E+11 | 16153.16 | 28-JUN-18:20 | 40.67 | 17.68 | 0.106876E+11 | 6463.95 | 10-JUN-01:30 | 40.67 | 17.68 |
July | 0.281261E+11 | 15325.67 | 20-JUL-18:02 | 38.67 | 19.18 | 0.110009E+11 | 6464.57 | 28-JUL-22:40 | 24.00 | 19.00 |
August | 0.286146E+11 | 17002.42 | 25-AUG-15:10 | 41.00 | 17.61 | 0.110474E+11 | 6464.57 | 03-AUG-02:00 | 41.00 | 17.61 |
September | 0.272549E+11 | 18621.62 | 28-SEP-15:10 | 37.52 | 15.49 | 0.106595E+11 | 6464.59 | 20-SEP-23:49 | 37.52 | 15.49 |
October | 0.245021E+11 | 18266.64 | 05-OCT-15:10 | 34.00 | 15.75 | 0.108570E+11 | 6464.54 | 04-OCT-00:40 | 34.00 | 15.75 |
November | 0.205893E+11 | 18490.23 | 01-NOV-15:10 | 28.83 | 16.12 | 0.101827E+11 | 6464.44 | 02-NOV-21:00 | 20.00 | 16.05 |
December | 0.201112E+11 | 18012.65 | 25-DEC-13:00 | 25.00 | 11.61 | 0.975700E+10 | 6462.55 | 13-DEC-02:09 | 25.00 | 11.61 |
Annual Sum or Average | 0.280604E+12 | 0.125893E+12 | ||||||||
Minimum of Months | 0.154546E+11 | 13915.14 | 17.50 | 9.25 | 0.923815E+10 | 6462.55 | 12.83 | 5.60 | ||
Maximum of Months | 0.286146E+11 | 18621.62 | 41.00 | 19.18 | 0.110474E+11 | 6464.59 | 41.00 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.745352E+11 | 39316.50 | 27-JAN-21:10 | 16.17 | 6.63 | 0.316369E+11 | 19186.74 | 11-JAN-23:30 | 16.17 | 6.63 |
February | 0.616453E+11 | 34826.37 | 21-FEB-21:10 | 14.83 | 11.70 | 0.278386E+11 | 19186.74 | 01-FEB-00:10 | 14.83 | 11.70 |
March | 0.712808E+11 | 42107.63 | 16-MAR-20:10 | 22.02 | 12.51 | 0.313902E+11 | 19186.75 | 30-MAR-21:10 | 15.22 | 5.04 |
April | 0.809378E+11 | 48560.77 | 14-APR-20:10 | 30.67 | 13.61 | 0.313771E+11 | 19186.74 | 27-APR-21:10 | 21.83 | 10.30 |
May | 0.861566E+11 | 48517.22 | 31-MAY-20:10 | 30.67 | 11.82 | 0.325722E+11 | 19186.74 | 17-MAY-03:39 | 30.67 | 11.82 |
June | 0.921380E+11 | 54358.29 | 28-JUN-20:10 | 36.67 | 15.41 | 0.317047E+11 | 19186.74 | 22-JUN-22:40 | 36.67 | 15.41 |
July | 0.938764E+11 | 53112.08 | 21-JUL-20:10 | 36.50 | 20.90 | 0.326290E+11 | 19186.74 | 01-JUL-00:30 | 36.50 | 20.90 |
August | 0.940149E+11 | 51998.09 | 10-AUG-20:10 | 35.67 | 18.37 | 0.327540E+11 | 19186.74 | 04-AUG-21:10 | 35.67 | 18.37 |
September | 0.892598E+11 | 51363.90 | 08-SEP-20:10 | 33.53 | 19.71 | 0.315859E+11 | 19186.74 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.826142E+11 | 48378.74 | 03-OCT-20:10 | 30.00 | 18.32 | 0.322213E+11 | 19186.77 | 24-OCT-21:30 | 16.50 | 5.95 |
November | 0.722380E+11 | 42981.34 | 01-NOV-20:10 | 20.50 | 13.68 | 0.306770E+11 | 19186.74 | 01-NOV-21:00 | 18.00 | 13.11 |
December | 0.694493E+11 | 37863.24 | 26-DEC-21:10 | 15.00 | 6.95 | 0.309241E+11 | 19186.74 | 19-DEC-22:49 | 15.00 | 6.95 |
Annual Sum or Average | 0.968146E+12 | 0.377311E+12 | ||||||||
Minimum of Months | 0.616453E+11 | 34826.37 | 14.83 | 6.63 | 0.278386E+11 | 19186.74 | 14.83 | 5.04 | ||
Maximum of Months | 0.940149E+11 | 54358.29 | 36.67 | 20.90 | 0.327540E+11 | 19186.77 | 36.67 | 20.90 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138023E+10 | 5217.07 | 09-JAN-16:12 | 18.00 | 10.38 | 98820965.59 | 56.69 | 01-JAN-05:10 | 18.00 | 10.38 |
February | 0.612350E+09 | 5202.50 | 27-FEB-16:12 | 17.67 | 9.39 | 88439724.74 | 56.69 | 13-FEB-05:10 | 17.67 | 9.39 |
March | 0.114324E+10 | 5165.79 | 07-MAR-16:12 | 18.80 | 10.08 | 98750658.80 | 57.06 | 04-MAR-01:39 | 18.80 | 10.08 |
April | 0.268995E+10 | 5069.23 | 07-APR-18:02 | 23.67 | 11.64 | 96075456.66 | 56.69 | 21-APR-04:00 | 8.00 | 0.42 |
May | 0.315911E+10 | 4968.30 | 09-MAY-08:61 | 26.33 | 12.09 | 99571900.80 | 56.69 | 10-MAY-23:49 | 25.17 | 14.84 |
June | 0.405881E+10 | 5033.85 | 11-JUN-08:61 | 26.33 | 12.62 | 96477332.49 | 56.69 | 01-JUN-04:30 | 26.33 | 12.62 |
July | 0.377356E+10 | 4785.52 | 01-JUL-08:61 | 27.50 | 10.46 | 99580890.71 | 56.69 | 09-JUL-04:00 | 23.00 | 18.89 |
August | 0.369886E+10 | 4718.88 | 24-AUG-08:62 | 26.50 | 12.85 | 99680128.02 | 56.69 | 01-AUG-01:10 | 26.50 | 12.85 |
September | 0.323261E+10 | 4802.41 | 19-SEP-08:62 | 26.47 | 13.15 | 96346298.48 | 56.69 | 01-SEP-01:10 | 26.47 | 13.15 |
October | 0.222297E+10 | 5158.45 | 28-OCT-15:12 | 23.33 | 11.60 | 99147159.73 | 56.69 | 26-OCT-04:10 | 23.33 | 11.60 |
November | 0.131976E+10 | 5254.59 | 15-NOV-16:12 | 21.00 | 11.19 | 95674311.65 | 56.69 | 24-NOV-03:20 | 5.33 | -1.0 |
December | 0.886418E+09 | 5167.81 | 13-DEC-16:12 | 15.67 | 7.72 | 98260572.85 | 56.93 | 23-DEC-00:40 | 10.00 | 3.00 |
Annual Sum or Average | 0.281778E+11 | 0.116683E+10 | ||||||||
Minimum of Months | 0.612350E+09 | 4718.88 | 15.67 | 7.72 | 88439724.74 | 56.69 | 5.33 | -1.0 | ||
Maximum of Months | 0.405881E+10 | 5254.59 | 27.50 | 13.15 | 99680128.02 | 57.06 | 26.50 | 18.89 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499142E+09 | 5314.89 | 07-JAN-22:51 | 18.00 | 11.23 | 0.103447E+09 | 75.53 | 06-JAN-22:30 | 18.00 | 11.23 |
February | 0.219205E+09 | 5251.06 | 01-FEB-17:11 | 14.67 | 6.54 | 90057061.04 | 69.83 | 09-FEB-22:40 | 14.67 | 8.47 |
March | 0.570330E+09 | 5417.38 | 16-MAR-21:51 | 20.00 | 12.36 | 0.106897E+09 | 90.73 | 17-MAR-21:10 | 21.42 | 12.50 |
April | 0.230218E+10 | 5402.78 | 15-APR-21:51 | 22.00 | 13.24 | 0.100448E+09 | 91.15 | 20-APR-21:10 | 17.00 | 5.46 |
May | 0.302104E+10 | 5269.55 | 13-MAY-08:51 | 22.00 | 11.02 | 0.101614E+09 | 65.11 | 13-MAY-21:00 | 22.00 | 7.76 |
June | 0.404876E+10 | 5272.47 | 04-JUN-06:41 | 25.67 | 14.69 | 98301865.68 | 62.68 | 05-JUN-05:00 | 25.00 | 13.62 |
July | 0.373868E+10 | 5080.40 | 06-JUL-07:11 | 26.33 | 14.72 | 0.100370E+09 | 59.61 | 15-JUL-05:00 | 24.00 | 21.09 |
August | 0.347845E+10 | 5131.69 | 23-AUG-08:11 | 27.33 | 14.86 | 0.101557E+09 | 90.56 | 04-AUG-21:10 | 27.33 | 14.86 |
September | 0.286201E+10 | 5175.38 | 28-SEP-08:51 | 27.20 | 15.18 | 99001518.22 | 90.98 | 21-SEP-21:10 | 27.20 | 15.18 |
October | 0.148759E+10 | 5430.99 | 23-OCT-16:41 | 24.00 | 12.49 | 0.105730E+09 | 85.67 | 17-OCT-21:19 | 24.00 | 12.49 |
November | 0.567444E+09 | 5227.97 | 20-NOV-22:01 | 14.00 | 9.66 | 0.100766E+09 | 86.96 | 01-NOV-21:10 | 14.00 | 9.66 |
December | 0.246410E+09 | 5316.39 | 13-DEC-17:11 | 14.33 | 6.99 | 99819530.30 | 67.48 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.230412E+11 | 0.120801E+10 | ||||||||
Minimum of Months | 0.219205E+09 | 5080.40 | 14.00 | 6.54 | 90057061.04 | 59.61 | 14.00 | 5.46 | ||
Maximum of Months | 0.404876E+10 | 5430.99 | 27.33 | 15.18 | 0.106897E+09 | 91.15 | 27.33 | 21.09 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.659872E+09 | 926.62 | 14-JAN-13:30 | 26.50 | 10.97 | 0.00 | 0.00 | 01-JAN-00:10 | 26.50 | 10.97 |
February | 0.251653E+09 | 655.63 | 23-FEB-14:00 | 18.00 | 10.78 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.78 |
March | 0.313560E+09 | 684.83 | 18-MAR-13:30 | 26.35 | 12.25 | 0.00 | 0.00 | 01-MAR-00:10 | 26.35 | 12.25 |
April | 0.685628E+09 | 717.51 | 14-APR-13:40 | 34.00 | 14.40 | 0.00 | 0.00 | 01-APR-00:10 | 34.00 | 14.40 |
May | 0.712496E+09 | 555.56 | 04-MAY-13:40 | 34.67 | 13.77 | 0.00 | 0.00 | 01-MAY-00:10 | 34.67 | 13.77 |
June | 0.925262E+09 | 668.72 | 28-JUN-18:03 | 40.83 | 17.83 | 0.00 | 0.00 | 01-JUN-00:10 | 40.83 | 17.83 |
July | 0.945809E+09 | 637.98 | 21-JUL-19:10 | 37.83 | 19.56 | 0.00 | 0.00 | 01-JUL-00:10 | 37.83 | 19.56 |
August | 0.985346E+09 | 794.44 | 27-AUG-14:00 | 40.00 | 18.27 | 0.00 | 0.00 | 01-AUG-00:10 | 40.00 | 18.27 |
September | 0.963878E+09 | 914.91 | 28-SEP-13:30 | 36.10 | 16.03 | 0.00 | 0.00 | 01-SEP-00:10 | 36.10 | 16.03 |
October | 0.794636E+09 | 945.64 | 18-OCT-13:10 | 30.17 | 11.86 | 0.00 | 0.00 | 01-OCT-00:10 | 30.17 | 11.86 |
November | 0.570605E+09 | 957.32 | 20-NOV-13:40 | 26.67 | 11.57 | 0.00 | 0.00 | 01-NOV-00:10 | 26.67 | 11.57 |
December | 0.475552E+09 | 930.75 | 25-DEC-13:30 | 25.50 | 11.81 | 0.00 | 0.00 | 01-DEC-00:10 | 25.50 | 11.81 |
Annual Sum or Average | 0.828430E+10 | 0.00 | ||||||||
Minimum of Months | 0.251653E+09 | 555.56 | 18.00 | 10.78 | 0.00 | 0.00 | 18.00 | 10.78 | ||
Maximum of Months | 0.985346E+09 | 957.32 | 40.83 | 19.56 | 0.00 | 0.00 | 40.83 | 19.56 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310245E+09 | 1931.55 | 07-JAN-22:51 | 18.00 | 11.23 | 0.101854E+09 | 77.30 | 06-JAN-22:49 | 18.00 | 11.23 |
February | 0.259230E+09 | 1862.99 | 09-FEB-22:51 | 14.00 | 8.26 | 89411268.80 | 72.88 | 09-FEB-22:49 | 14.00 | 8.26 |
March | 0.392046E+09 | 1937.44 | 16-MAR-21:51 | 20.00 | 12.36 | 0.104303E+09 | 85.88 | 17-MAR-21:49 | 20.68 | 11.95 |
April | 0.864732E+09 | 1914.15 | 15-APR-21:51 | 22.00 | 13.24 | 99263081.72 | 84.34 | 07-APR-21:40 | 22.00 | 13.24 |
May | 0.111955E+10 | 1859.45 | 13-MAY-08:51 | 22.00 | 11.02 | 0.101459E+09 | 62.01 | 13-MAY-21:00 | 22.00 | 7.76 |
June | 0.144665E+10 | 1836.42 | 04-JUN-06:41 | 25.67 | 14.69 | 98079962.38 | 59.84 | 05-JUN-05:00 | 25.00 | 13.62 |
July | 0.143035E+10 | 1797.67 | 06-JUL-07:11 | 26.33 | 14.72 | 0.100276E+09 | 57.45 | 05-JUL-05:00 | 26.33 | 14.72 |
August | 0.131146E+10 | 1790.40 | 23-AUG-08:11 | 27.33 | 14.86 | 0.101343E+09 | 90.43 | 04-AUG-21:10 | 27.33 | 14.86 |
September | 0.114543E+10 | 1821.89 | 16-SEP-08:51 | 26.60 | 14.56 | 98730569.81 | 87.71 | 21-SEP-21:00 | 21.10 | 16.77 |
October | 0.677531E+09 | 1914.34 | 23-OCT-21:51 | 16.00 | 10.88 | 0.104408E+09 | 82.61 | 17-OCT-21:30 | 16.00 | 10.88 |
November | 0.345518E+09 | 1934.38 | 20-NOV-22:01 | 14.00 | 9.66 | 99412948.69 | 85.03 | 02-NOV-21:00 | 14.00 | 9.66 |
December | 0.210201E+09 | 1879.55 | 02-DEC-22:11 | 13.33 | 5.45 | 99095340.00 | 68.68 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.951294E+10 | 0.119764E+10 | ||||||||
Minimum of Months | 0.210201E+09 | 1790.40 | 13.33 | 5.45 | 89411268.80 | 57.45 | 14.00 | 7.15 | ||
Maximum of Months | 0.144665E+10 | 1937.44 | 27.33 | 14.86 | 0.104408E+09 | 90.43 | 27.33 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131128E+10 | 4346.29 | 26-JAN-09:02 | 13.00 | 7.15 | 99198740.25 | 56.69 | 01-JAN-05:10 | 13.00 | 7.15 |
February | 0.682107E+09 | 4324.07 | 25-FEB-16:12 | 17.67 | 9.56 | 88787100.34 | 56.69 | 13-FEB-05:10 | 17.67 | 9.56 |
March | 0.118120E+10 | 4290.59 | 07-MAR-16:12 | 18.80 | 10.08 | 99114727.88 | 56.69 | 26-MAR-04:00 | 0.50 | -2.4 |
April | 0.273570E+10 | 4401.15 | 18-APR-08:62 | 20.50 | 11.76 | 96388816.08 | 57.04 | 08-APR-04:19 | 20.50 | 11.76 |
May | 0.327534E+10 | 4408.96 | 13-MAY-08:62 | 21.17 | 11.16 | 99662145.44 | 56.69 | 10-MAY-23:40 | 21.17 | 11.16 |
June | 0.417563E+10 | 4387.40 | 11-JUN-08:61 | 26.33 | 12.62 | 96473263.26 | 56.69 | 10-JUN-01:10 | 26.33 | 12.62 |
July | 0.402870E+10 | 4160.98 | 01-JUL-08:61 | 27.50 | 10.46 | 99588428.26 | 56.69 | 09-JUL-04:00 | 23.00 | 18.89 |
August | 0.389624E+10 | 4189.18 | 24-AUG-08:62 | 26.50 | 12.85 | 99690734.27 | 56.69 | 01-AUG-01:10 | 26.50 | 12.85 |
September | 0.333288E+10 | 4266.64 | 28-SEP-08:62 | 24.37 | 14.15 | 96388888.01 | 56.69 | 01-SEP-01:10 | 24.37 | 14.15 |
October | 0.229363E+10 | 4334.21 | 06-OCT-08:62 | 24.67 | 13.40 | 99462786.17 | 56.69 | 26-OCT-04:10 | 7.00 | 2.28 |
November | 0.123562E+10 | 4371.64 | 21-NOV-09:02 | 18.33 | 10.28 | 95917126.68 | 56.69 | 24-NOV-03:09 | 5.17 | -1.1 |
December | 0.877752E+09 | 4317.50 | 13-DEC-16:12 | 15.67 | 7.72 | 98707078.64 | 56.69 | 06-DEC-02:09 | 15.67 | 7.72 |
Annual Sum or Average | 0.290261E+11 | 0.116938E+10 | ||||||||
Minimum of Months | 0.682107E+09 | 4160.98 | 13.00 | 7.15 | 88787100.34 | 56.69 | 0.50 | -2.4 | ||
Maximum of Months | 0.417563E+10 | 4408.96 | 27.50 | 14.15 | 99690734.27 | 57.04 | 26.50 | 18.89 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472533E+09 | 4453.88 | 27-JAN-09:51 | 20.00 | 7.78 | 0.102400E+09 | 72.50 | 06-JAN-22:30 | 20.00 | 7.78 |
February | 0.295845E+09 | 4293.73 | 01-FEB-17:11 | 14.67 | 6.54 | 89791916.43 | 69.07 | 09-FEB-22:40 | 14.67 | 8.47 |
March | 0.660728E+09 | 4667.26 | 11-MAR-09:51 | 18.80 | 11.12 | 0.105062E+09 | 85.30 | 17-MAR-21:19 | 21.23 | 12.36 |
April | 0.226466E+10 | 4671.85 | 27-APR-08:51 | 18.00 | 10.08 | 0.100925E+09 | 84.48 | 27-APR-21:19 | 21.67 | 10.31 |
May | 0.300796E+10 | 4662.00 | 13-MAY-08:51 | 22.00 | 11.02 | 0.103636E+09 | 64.11 | 13-MAY-21:00 | 22.00 | 7.76 |
June | 0.412008E+10 | 4551.95 | 04-JUN-06:41 | 25.67 | 14.69 | 98965579.76 | 66.47 | 05-JUN-05:00 | 25.00 | 13.62 |
July | 0.397104E+10 | 4376.45 | 06-JUL-07:11 | 26.33 | 14.72 | 0.100716E+09 | 61.52 | 15-JUL-05:00 | 24.00 | 21.09 |
August | 0.364414E+10 | 4465.81 | 23-AUG-08:11 | 27.33 | 14.86 | 0.101922E+09 | 90.47 | 04-AUG-21:10 | 27.33 | 14.86 |
September | 0.291014E+10 | 4505.54 | 28-SEP-08:51 | 27.20 | 15.18 | 99540282.02 | 89.91 | 21-SEP-21:10 | 27.20 | 15.18 |
October | 0.153336E+10 | 4648.07 | 09-OCT-08:51 | 22.00 | 13.26 | 0.105348E+09 | 83.73 | 16-OCT-21:00 | 23.00 | 8.96 |
November | 0.501650E+09 | 4602.76 | 21-NOV-09:51 | 20.00 | 11.28 | 99863679.53 | 83.02 | 02-NOV-21:40 | 20.00 | 11.28 |
December | 0.245059E+09 | 4474.70 | 25-DEC-09:51 | 18.00 | 8.29 | 99494864.23 | 63.87 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.236272E+11 | 0.120766E+10 | ||||||||
Minimum of Months | 0.245059E+09 | 4293.73 | 14.67 | 6.54 | 89791916.43 | 61.52 | 14.67 | 7.15 | ||
Maximum of Months | 0.412008E+10 | 4671.85 | 27.33 | 15.18 | 0.105348E+09 | 90.47 | 27.33 | 21.09 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246206E+10 | 2740.19 | 31-JAN-16:10 | 29.00 | 10.73 | 0.161448E+10 | 951.85 | 26-JAN-05:19 | 29.00 | 10.73 |
February | 0.114780E+10 | 1851.30 | 22-FEB-16:10 | 20.83 | 11.61 | 0.145743E+10 | 951.85 | 04-FEB-05:10 | 20.83 | 11.61 |
March | 0.205444E+10 | 2587.42 | 16-MAR-15:13 | 28.80 | 13.79 | 0.162156E+10 | 951.86 | 09-MAR-03:00 | 28.80 | 13.79 |
April | 0.441707E+10 | 3455.95 | 14-APR-18:03 | 33.50 | 13.96 | 0.157044E+10 | 951.84 | 03-APR-22:10 | 33.50 | 13.96 |
May | 0.520023E+10 | 3655.46 | 31-MAY-18:15 | 35.33 | 13.34 | 0.162336E+10 | 951.80 | 17-MAY-22:00 | 35.33 | 13.34 |
June | 0.659511E+10 | 4601.60 | 28-JUN-18:25 | 40.50 | 17.53 | 0.157387E+10 | 951.82 | 09-JUN-23:10 | 40.50 | 17.53 |
July | 0.648961E+10 | 4201.86 | 20-JUL-18:15 | 38.33 | 19.15 | 0.161993E+10 | 951.83 | 07-JUL-22:10 | 38.33 | 19.15 |
August | 0.633588E+10 | 3993.14 | 25-AUG-18:15 | 38.33 | 16.79 | 0.162678E+10 | 951.84 | 04-AUG-21:19 | 38.33 | 16.79 |
September | 0.576347E+10 | 3847.75 | 28-SEP-15:10 | 37.52 | 15.49 | 0.156967E+10 | 951.84 | 21-SEP-22:10 | 37.52 | 15.49 |
October | 0.410620E+10 | 3588.94 | 06-OCT-15:10 | 35.00 | 14.90 | 0.162029E+10 | 951.85 | 26-OCT-02:20 | 8.33 | 2.78 |
November | 0.246356E+10 | 3186.96 | 01-NOV-15:10 | 28.83 | 16.12 | 0.156429E+10 | 951.85 | 06-NOV-04:49 | 8.33 | 2.99 |
December | 0.146990E+10 | 2630.51 | 22-DEC-16:10 | 24.83 | 10.00 | 0.160266E+10 | 951.85 | 27-DEC-05:10 | 6.83 | 2.55 |
Annual Sum or Average | 0.485053E+11 | 0.190647E+11 | ||||||||
Minimum of Months | 0.114780E+10 | 1851.30 | 20.83 | 10.00 | 0.145743E+10 | 951.80 | 6.83 | 2.55 | ||
Maximum of Months | 0.659511E+10 | 4601.60 | 40.50 | 19.15 | 0.162678E+10 | 951.86 | 40.50 | 19.15 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122543E+10 | 5674.77 | 09-JAN-16:12 | 18.00 | 10.38 | 98388949.95 | 56.69 | 01-JAN-05:10 | 18.00 | 10.38 |
February | 0.485745E+09 | 5645.79 | 27-FEB-16:12 | 17.67 | 9.39 | 87756613.72 | 56.69 | 13-FEB-05:10 | 17.67 | 9.39 |
March | 0.103970E+10 | 5623.63 | 09-MAR-16:12 | 22.70 | 11.30 | 98329692.35 | 57.55 | 17-MAR-03:00 | 15.00 | 10.28 |
April | 0.278013E+10 | 5515.04 | 07-APR-18:02 | 23.67 | 11.64 | 95910134.79 | 57.54 | 10-APR-04:00 | 15.00 | 7.67 |
May | 0.335917E+10 | 5409.45 | 09-MAY-08:61 | 26.33 | 12.09 | 99509172.39 | 56.69 | 10-MAY-23:49 | 25.17 | 14.84 |
June | 0.448725E+10 | 5487.41 | 11-JUN-08:61 | 26.33 | 12.62 | 96482591.02 | 56.69 | 10-JUN-01:19 | 26.33 | 12.62 |
July | 0.415743E+10 | 5215.11 | 01-JUL-08:61 | 27.50 | 10.46 | 99574692.89 | 56.69 | 09-JUL-04:00 | 23.00 | 18.89 |
August | 0.404021E+10 | 5096.27 | 24-AUG-08:62 | 26.50 | 12.85 | 99673436.23 | 56.69 | 01-AUG-01:19 | 26.50 | 12.85 |
September | 0.342372E+10 | 5202.15 | 19-SEP-08:62 | 26.47 | 13.15 | 96306993.23 | 56.69 | 01-SEP-01:10 | 26.47 | 13.15 |
October | 0.215650E+10 | 5626.68 | 28-OCT-15:12 | 23.33 | 11.60 | 98891865.90 | 57.70 | 14-OCT-02:20 | 23.33 | 11.60 |
November | 0.115163E+10 | 5721.21 | 15-NOV-16:12 | 21.00 | 11.19 | 95231515.89 | 57.62 | 20-NOV-02:20 | 16.00 | 8.15 |
December | 0.743438E+09 | 5607.68 | 13-DEC-16:12 | 15.67 | 7.72 | 97624580.88 | 57.21 | 27-DEC-22:40 | 11.97 | 6.10 |
Annual Sum or Average | 0.290504E+11 | 0.116368E+10 | ||||||||
Minimum of Months | 0.485745E+09 | 5096.27 | 15.67 | 7.72 | 87756613.72 | 56.69 | 11.97 | 6.10 | ||
Maximum of Months | 0.448725E+10 | 5721.21 | 27.50 | 13.15 | 99673436.23 | 57.70 | 26.50 | 18.89 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.409274E+09 | 5724.03 | 07-JAN-22:51 | 18.00 | 11.23 | 0.102525E+09 | 72.96 | 19-JAN-22:10 | 14.67 | 6.84 |
February | 0.136242E+09 | 5696.34 | 01-FEB-17:11 | 14.67 | 6.54 | 89141850.38 | 66.18 | 09-FEB-22:30 | 15.00 | 8.57 |
March | 0.501983E+09 | 5857.01 | 16-MAR-21:51 | 20.00 | 12.36 | 0.106385E+09 | 90.52 | 31-MAR-18:19 | 20.87 | 7.83 |
April | 0.241763E+10 | 5866.81 | 15-APR-21:51 | 22.00 | 13.24 | 0.100117E+09 | 93.19 | 20-APR-21:10 | 17.00 | 5.46 |
May | 0.325134E+10 | 5722.09 | 13-MAY-08:51 | 22.00 | 11.02 | 0.101171E+09 | 64.25 | 13-MAY-21:00 | 22.00 | 7.76 |
June | 0.449575E+10 | 5673.99 | 04-JUN-06:41 | 25.67 | 14.69 | 98111963.00 | 60.90 | 05-JUN-05:00 | 25.00 | 13.62 |
July | 0.412977E+10 | 5491.56 | 06-JUL-07:11 | 26.33 | 14.72 | 0.100265E+09 | 58.44 | 15-JUL-05:00 | 24.00 | 21.09 |
August | 0.383229E+10 | 5556.79 | 23-AUG-08:11 | 27.33 | 14.86 | 0.101419E+09 | 90.62 | 04-AUG-21:10 | 27.33 | 14.86 |
September | 0.307496E+10 | 5629.27 | 28-SEP-08:51 | 27.20 | 15.18 | 98735651.25 | 90.60 | 21-SEP-21:10 | 27.20 | 15.18 |
October | 0.146695E+10 | 5919.44 | 23-OCT-16:41 | 24.00 | 12.49 | 0.105011E+09 | 83.94 | 17-OCT-21:19 | 24.00 | 12.49 |
November | 0.461012E+09 | 5632.28 | 20-NOV-22:01 | 14.00 | 9.66 | 99830407.62 | 82.92 | 02-NOV-21:40 | 14.00 | 9.66 |
December | 0.174794E+09 | 5775.22 | 13-DEC-17:11 | 14.33 | 6.99 | 98864658.58 | 64.89 | 26-DEC-21:40 | 15.00 | 7.15 |
Annual Sum or Average | 0.243520E+11 | 0.120158E+10 | ||||||||
Minimum of Months | 0.136242E+09 | 5491.56 | 14.00 | 6.54 | 89141850.38 | 58.44 | 14.00 | 5.46 | ||
Maximum of Months | 0.449575E+10 | 5919.44 | 27.33 | 15.18 | 0.106385E+09 | 93.19 | 27.33 | 21.09 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133387E+10 | 3029.53 | 09-JAN-16:12 | 18.00 | 10.38 | 99084448.24 | 56.69 | 01-JAN-05:00 | 18.00 | 10.38 |
February | 0.604768E+09 | 2984.06 | 25-FEB-16:12 | 17.67 | 9.56 | 88617442.65 | 56.69 | 13-FEB-05:10 | 17.67 | 9.56 |
March | 0.804953E+09 | 2962.08 | 07-MAR-16:12 | 18.80 | 10.08 | 98722488.52 | 56.69 | 26-MAR-04:00 | 0.50 | -2.4 |
April | 0.160275E+10 | 2905.72 | 07-APR-15:12 | 24.67 | 12.07 | 95994272.24 | 56.69 | 21-APR-04:00 | 8.00 | 0.42 |
May | 0.174342E+10 | 2857.55 | 13-MAY-08:62 | 21.17 | 11.16 | 99536677.65 | 56.69 | 10-MAY-23:40 | 21.17 | 11.16 |
June | 0.225703E+10 | 2890.40 | 11-JUN-08:61 | 26.33 | 12.62 | 96460574.44 | 56.69 | 01-JUN-03:20 | 26.33 | 12.62 |
July | 0.227464E+10 | 2737.52 | 01-JUL-08:61 | 27.50 | 10.46 | 99575935.79 | 56.69 | 17-JUL-22:40 | 24.00 | 20.90 |
August | 0.231059E+10 | 2714.26 | 24-AUG-08:62 | 26.50 | 12.85 | 99669838.24 | 56.69 | 06-AUG-23:10 | 26.50 | 12.85 |
September | 0.216628E+10 | 2788.44 | 16-SEP-08:62 | 23.35 | 13.38 | 96337457.46 | 56.69 | 01-SEP-01:10 | 23.35 | 13.38 |
October | 0.166917E+10 | 2980.59 | 28-OCT-15:12 | 23.33 | 11.60 | 99188938.23 | 56.69 | 26-OCT-04:10 | 23.33 | 11.60 |
November | 0.116433E+10 | 3010.75 | 15-NOV-16:12 | 21.00 | 11.19 | 95849578.36 | 56.69 | 23-NOV-05:00 | 0.00 | -2.5 |
December | 0.103503E+10 | 2989.01 | 13-DEC-16:12 | 15.67 | 7.72 | 98731805.33 | 56.69 | 07-DEC-05:10 | 15.67 | 7.72 |
Annual Sum or Average | 0.189668E+11 | 0.116777E+10 | ||||||||
Minimum of Months | 0.604768E+09 | 2714.26 | 15.67 | 7.72 | 88617442.65 | 56.69 | 0.00 | -2.5 | ||
Maximum of Months | 0.231059E+10 | 3029.53 | 27.50 | 13.38 | 99669838.24 | 56.69 | 26.50 | 20.90 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371949E+11 | 19229.55 | 06-JAN-22:10 | 17.67 | 9.28 | 0.184290E+11 | 11350.12 | 13-JAN-22:00 | 10.00 | 6.03 |
February | 0.331019E+11 | 18894.36 | 21-FEB-22:10 | 14.00 | 12.80 | 0.165791E+11 | 11350.12 | 15-FEB-22:10 | 14.00 | 12.80 |
March | 0.387700E+11 | 21577.60 | 17-MAR-21:10 | 21.42 | 12.50 | 0.187327E+11 | 11350.14 | 30-MAR-21:10 | 15.22 | 5.04 |
April | 0.436537E+11 | 24243.59 | 14-APR-21:10 | 28.67 | 13.19 | 0.186088E+11 | 11350.13 | 03-APR-21:30 | 28.67 | 13.19 |
May | 0.478910E+11 | 24900.72 | 31-MAY-18:15 | 35.33 | 13.34 | 0.193176E+11 | 11350.12 | 01-MAY-00:10 | 35.33 | 13.34 |
June | 0.512231E+11 | 27564.01 | 28-JUN-18:30 | 40.50 | 17.53 | 0.187672E+11 | 11350.12 | 28-JUN-21:10 | 34.67 | 14.46 |
July | 0.517504E+11 | 26310.69 | 21-JUL-21:10 | 33.83 | 20.81 | 0.193142E+11 | 11350.12 | 10-JUL-21:19 | 33.83 | 20.81 |
August | 0.506197E+11 | 26136.52 | 10-AUG-21:10 | 33.33 | 18.08 | 0.193890E+11 | 11350.12 | 30-AUG-23:00 | 28.00 | 16.58 |
September | 0.468051E+11 | 25458.91 | 07-SEP-21:10 | 32.75 | 19.42 | 0.186893E+11 | 11350.12 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.420165E+11 | 24113.38 | 03-OCT-21:10 | 29.50 | 18.57 | 0.189915E+11 | 11350.16 | 24-OCT-21:30 | 16.50 | 5.95 |
November | 0.367261E+11 | 21054.18 | 02-NOV-21:10 | 20.00 | 15.60 | 0.179584E+11 | 11350.12 | 21-NOV-22:10 | 15.00 | 8.04 |
December | 0.353372E+11 | 18642.13 | 26-DEC-22:10 | 14.83 | 7.20 | 0.179627E+11 | 11350.12 | 26-DEC-22:10 | 14.83 | 7.20 |
Annual Sum or Average | 0.515090E+12 | 0.222740E+12 | ||||||||
Minimum of Months | 0.331019E+11 | 18642.13 | 14.00 | 7.20 | 0.165791E+11 | 11350.12 | 10.00 | 5.04 | ||
Maximum of Months | 0.517504E+11 | 27564.01 | 40.50 | 20.81 | 0.193890E+11 | 11350.16 | 35.33 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390667E+11 | 20625.93 | 06-JAN-22:10 | 17.67 | 9.28 | 0.187459E+11 | 11350.12 | 09-JAN-23:30 | 8.50 | 7.66 |
February | 0.347759E+11 | 20305.56 | 21-FEB-22:10 | 14.00 | 12.80 | 0.168959E+11 | 11350.12 | 15-FEB-22:10 | 14.00 | 12.80 |
March | 0.408184E+11 | 22823.31 | 17-MAR-21:10 | 21.42 | 12.50 | 0.189817E+11 | 11350.14 | 30-MAR-21:10 | 15.22 | 5.04 |
April | 0.460517E+11 | 25442.68 | 14-APR-21:10 | 28.67 | 13.19 | 0.186722E+11 | 11350.13 | 18-APR-21:19 | 22.67 | 8.95 |
May | 0.505168E+11 | 26184.48 | 31-MAY-18:15 | 35.33 | 13.34 | 0.193443E+11 | 11350.12 | 05-MAY-01:39 | 35.33 | 13.34 |
June | 0.538893E+11 | 28853.70 | 28-JUN-18:30 | 40.50 | 17.53 | 0.187685E+11 | 11350.12 | 28-JUN-21:10 | 34.67 | 14.46 |
July | 0.544670E+11 | 27503.87 | 21-JUL-21:10 | 33.83 | 20.81 | 0.193176E+11 | 11350.12 | 07-JUL-01:10 | 33.83 | 20.81 |
August | 0.532898E+11 | 27324.18 | 10-AUG-21:10 | 33.33 | 18.08 | 0.193977E+11 | 11350.12 | 07-AUG-21:30 | 33.33 | 18.08 |
September | 0.492991E+11 | 26636.42 | 07-SEP-21:10 | 32.75 | 19.42 | 0.187103E+11 | 11350.12 | 21-SEP-21:10 | 22.02 | 16.74 |
October | 0.442168E+11 | 25297.93 | 03-OCT-21:10 | 29.50 | 18.57 | 0.191340E+11 | 11350.16 | 24-OCT-21:30 | 16.50 | 5.95 |
November | 0.385554E+11 | 22304.49 | 02-NOV-21:10 | 20.00 | 15.60 | 0.182256E+11 | 11350.12 | 21-NOV-22:10 | 15.00 | 8.04 |
December | 0.371562E+11 | 20009.43 | 26-DEC-22:10 | 14.83 | 7.20 | 0.183782E+11 | 11350.12 | 14-DEC-23:19 | 14.83 | 7.20 |
Annual Sum or Average | 0.542103E+12 | 0.224572E+12 | ||||||||
Minimum of Months | 0.347759E+11 | 20009.43 | 14.00 | 7.20 | 0.168959E+11 | 11350.12 | 8.50 | 5.04 | ||
Maximum of Months | 0.544670E+11 | 28853.70 | 40.50 | 20.81 | 0.193977E+11 | 11350.16 | 35.33 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492973E+11 | 28533.76 | 29-JAN-11:40 | 21.33 | 8.67 | 0.188684E+11 | 11320.05 | 07-JAN-18:40 | 21.33 | 8.67 |
February | 0.436644E+11 | 28203.02 | 18-FEB-11:40 | 19.33 | 14.12 | 0.170436E+11 | 11320.07 | 18-FEB-18:30 | 15.50 | 14.56 |
March | 0.498513E+11 | 29395.40 | 18-MAR-10:50 | 24.12 | 14.75 | 0.188766E+11 | 11320.11 | 04-MAR-18:00 | 24.12 | 14.75 |
April | 0.535415E+11 | 31523.13 | 14-APR-10:50 | 30.67 | 13.78 | 0.182633E+11 | 11320.08 | 15-APR-17:49 | 26.33 | 13.34 |
May | 0.570185E+11 | 31711.66 | 07-MAY-10:50 | 30.50 | 13.03 | 0.188729E+11 | 11320.07 | 20-MAY-17:49 | 33.17 | 13.92 |
June | 0.583327E+11 | 32724.27 | 28-JUN-10:40 | 37.67 | 17.96 | 0.182673E+11 | 11320.07 | 10-JUN-17:49 | 37.67 | 17.96 |
July | 0.594201E+11 | 32321.38 | 10-JUL-10:50 | 35.67 | 19.19 | 0.188696E+11 | 11320.16 | 08-JUL-17:00 | 35.67 | 19.19 |
August | 0.589275E+11 | 32548.29 | 26-AUG-10:50 | 36.67 | 15.46 | 0.188769E+11 | 11320.23 | 05-AUG-17:00 | 36.67 | 15.46 |
September | 0.554728E+11 | 32285.11 | 09-SEP-10:50 | 33.62 | 20.75 | 0.182630E+11 | 11320.18 | 02-SEP-17:00 | 33.62 | 20.75 |
October | 0.530235E+11 | 31358.60 | 05-OCT-10:40 | 30.33 | 17.59 | 0.188697E+11 | 11320.13 | 07-OCT-17:00 | 20.00 | 13.38 |
November | 0.479983E+11 | 29282.23 | 01-NOV-10:50 | 24.67 | 16.10 | 0.182591E+11 | 11320.05 | 18-NOV-18:00 | 16.00 | 10.41 |
December | 0.474433E+11 | 28282.61 | 25-DEC-11:50 | 22.67 | 10.24 | 0.188680E+11 | 11319.96 | 02-DEC-18:40 | 22.67 | 10.24 |
Annual Sum or Average | 0.633991E+12 | 0.222198E+12 | ||||||||
Minimum of Months | 0.436644E+11 | 28203.02 | 19.33 | 8.67 | 0.170436E+11 | 11319.96 | 15.50 | 8.67 | ||
Maximum of Months | 0.594201E+11 | 32724.27 | 37.67 | 20.75 | 0.188769E+11 | 11320.23 | 37.67 | 20.75 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395195E+10 | 6898.87 | 24-JAN-13:50 | 24.83 | 10.33 | 0.163956E+10 | 1007.41 | 07-JAN-01:00 | 24.83 | 10.33 |
February | 0.179712E+10 | 6179.64 | 23-FEB-14:00 | 18.00 | 10.78 | 0.147449E+10 | 1007.40 | 01-FEB-00:30 | 18.00 | 10.78 |
March | 0.397003E+10 | 8227.11 | 18-MAR-14:30 | 26.65 | 12.20 | 0.166807E+10 | 1007.41 | 08-MAR-23:30 | 26.65 | 12.20 |
April | 0.107477E+11 | 10957.28 | 14-APR-15:10 | 35.00 | 14.57 | 0.165925E+10 | 1007.40 | 07-APR-03:20 | 35.00 | 14.57 |
May | 0.132195E+11 | 10281.94 | 09-MAY-12:50 | 33.83 | 14.32 | 0.171807E+10 | 1007.40 | 01-MAY-04:40 | 33.83 | 14.32 |
June | 0.173226E+11 | 11694.62 | 28-JUN-15:10 | 42.00 | 19.47 | 0.166575E+10 | 1007.39 | 09-JUN-23:19 | 42.00 | 19.47 |
July | 0.170240E+11 | 11573.39 | 20-JUL-13:20 | 39.00 | 20.25 | 0.171447E+10 | 1007.39 | 07-JUL-22:10 | 39.00 | 20.25 |
August | 0.164033E+11 | 12052.20 | 09-AUG-13:30 | 38.50 | 21.08 | 0.172172E+10 | 1007.39 | 04-AUG-21:19 | 38.50 | 21.08 |
September | 0.140805E+11 | 12092.82 | 07-SEP-13:30 | 36.35 | 19.54 | 0.166128E+10 | 1007.39 | 21-SEP-22:10 | 20.92 | 16.58 |
October | 0.851690E+10 | 11396.61 | 02-OCT-13:10 | 34.17 | 19.45 | 0.169930E+10 | 1007.40 | 25-OCT-22:10 | 11.50 | 4.39 |
November | 0.412119E+10 | 8504.29 | 01-NOV-15:10 | 28.83 | 16.12 | 0.160709E+10 | 1007.41 | 21-NOV-01:39 | 12.33 | 8.40 |
December | 0.203473E+10 | 6587.29 | 25-DEC-13:40 | 25.67 | 11.87 | 0.156024E+10 | 1007.40 | 27-DEC-22:30 | 11.90 | 6.12 |
Annual Sum or Average | 0.113190E+12 | 0.197893E+11 | ||||||||
Minimum of Months | 0.179712E+10 | 6179.64 | 18.00 | 10.33 | 0.147449E+10 | 1007.39 | 11.50 | 4.39 | ||
Maximum of Months | 0.173226E+11 | 12092.82 | 42.00 | 21.08 | 0.172172E+10 | 1007.41 | 42.00 | 21.08 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19842297.74 | 802.20 | 01-JAN-06:00 | 0.80 |
February | 12519722.77 | 263.36 | 09-FEB-07:10 | 6.17 |
March | 49385678.99 | 925.06 | 26-MAR-05:00 | 0.50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 224070.17 | 130.14 | 25-OCT-06:30 | 5.00 |
November | 15671535.73 | 699.44 | 23-NOV-07:00 | 0.00 |
December | 0.149513E+09 | 1117.56 | 07-DEC-05:00 | -1.1 |
Annual Sum or Average | 0.247157E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.149513E+09 | 1117.56 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98472.88 | 40.90 | 01-JAN-06:00 | 0.80 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 1261459.09 | 134.56 | 07-DEC-05:00 | -1.1 |
Annual Sum or Average | 1359931.97 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 1261459.09 | 134.56 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181587E+09 | 1543.83 | 01-JAN-09:02 | 5.90 |
February | 0.176856E+09 | 1643.64 | 20-FEB-19:03 | 13.83 |
March | 0.171898E+09 | 2506.63 | 27-MAR-08:62 | 9.77 |
April | 7404389.64 | 1623.05 | 10-APR-08:03 | 22.50 |
May | 2788979.56 | 1535.47 | 13-MAY-08:03 | 21.17 |
June | 188770.21 | 634.96 | 14-JUN-08:03 | 27.67 |
July | 56122.58 | 616.92 | 01-JUL-08:03 | 27.50 |
August | 262047.31 | 1194.52 | 30-AUG-08:03 | 26.67 |
September | 479106.56 | 962.56 | 29-SEP-08:04 | 26.65 |
October | 40957012.71 | 1496.58 | 11-OCT-08:03 | 19.17 |
November | 0.131160E+09 | 1618.44 | 26-NOV-19:03 | 14.00 |
December | 0.378335E+09 | 1967.75 | 07-DEC-09:02 | 6.67 |
Annual Sum or Average | 0.109197E+10 | |||
Minimum of Months | 56122.58 | 616.92 | 5.90 | |
Maximum of Months | 0.378335E+09 | 2506.63 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246800E+09 | 4016.82 | 01-JAN-09:02 | 5.90 |
February | 0.224814E+09 | 2158.64 | 03-FEB-09:02 | 10.33 |
March | 0.208598E+09 | 2955.30 | 26-MAR-08:62 | 7.75 |
April | 36910630.30 | 2581.64 | 06-APR-21:53 | 15.00 |
May | 25591061.78 | 2027.25 | 01-MAY-08:53 | 22.00 |
June | 16544167.35 | 921.49 | 16-JUN-06:44 | 26.50 |
July | 7413372.27 | 922.34 | 01-JUL-08:04 | 27.50 |
August | 16791312.36 | 854.45 | 30-AUG-08:04 | 26.67 |
September | 27605276.63 | 1051.13 | 20-SEP-06:04 | 24.30 |
October | 88255601.95 | 2128.42 | 28-OCT-21:53 | 15.00 |
November | 0.196754E+09 | 3038.35 | 24-NOV-09:02 | 9.00 |
December | 0.495922E+09 | 4379.87 | 07-DEC-09:02 | 6.67 |
Annual Sum or Average | 0.159200E+10 | |||
Minimum of Months | 7413372.27 | 854.45 | 5.90 | |
Maximum of Months | 0.495922E+09 | 4379.87 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15021011.70 | 841.98 | 27-JAN-09:53 | 20.00 |
February | 5578944.04 | 731.23 | 05-FEB-17:13 | 14.67 |
March | 12030507.87 | 741.31 | 12-MAR-19:14 | 14.20 |
April | 6964960.82 | 506.47 | 18-APR-08:54 | 23.00 |
May | 5106571.59 | 398.83 | 01-MAY-08:54 | 22.00 |
June | 4997917.23 | 287.89 | 09-JUN-08:05 | 28.17 |
July | 2270920.94 | 394.57 | 31-JUL-08:05 | 28.17 |
August | 4875924.90 | 514.11 | 11-AUG-08:05 | 28.67 |
September | 7370378.10 | 403.94 | 17-SEP-08:05 | 28.17 |
October | 9473588.19 | 672.92 | 30-OCT-08:04 | 14.50 |
November | 10739166.73 | 742.43 | 08-NOV-09:53 | 17.00 |
December | 32735959.65 | 826.24 | 14-DEC-17:02 | 13.67 |
Annual Sum or Average | 0.117166E+09 | |||
Minimum of Months | 2270920.94 | 287.89 | 13.67 | |
Maximum of Months | 32735959.65 | 841.98 | 28.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185421E+09 | 1293.05 | 13-JAN-19:03 | 16.67 |
February | 0.171766E+09 | 1372.59 | 20-FEB-19:03 | 13.83 |
March | 0.167192E+09 | 1468.96 | 08-MAR-16:14 | 19.20 |
April | 4384810.45 | 282.16 | 21-APR-05:00 | 8.00 |
May | 85270.79 | 558.84 | 26-MAY-08:04 | 24.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 38205308.97 | 1160.99 | 27-OCT-18:04 | 17.50 |
November | 0.133938E+09 | 1335.12 | 26-NOV-19:03 | 14.00 |
December | 0.371230E+09 | 1463.69 | 17-DEC-16:13 | 15.67 |
Annual Sum or Average | 0.107222E+10 | |||
Minimum of Months | 0.00 | 0.00 | 8.00 | |
Maximum of Months | 0.371230E+09 | 1468.96 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252532E+09 | 1661.19 | 10-JAN-20:13 | 14.67 |
February | 0.212642E+09 | 1487.29 | 09-FEB-22:53 | 14.00 |
March | 0.201315E+09 | 2363.59 | 18-MAR-21:53 | 15.00 |
April | 21303666.17 | 1919.02 | 26-APR-21:53 | 16.00 |
May | 6927699.89 | 693.34 | 13-MAY-21:54 | 22.00 |
June | 6566488.55 | 322.31 | 19-JUN-06:44 | 27.17 |
July | 3448551.26 | 177.68 | 15-JUL-05:23 | 23.50 |
August | 9836973.74 | 354.40 | 24-AUG-08:03 | 26.50 |
September | 16898545.31 | 860.34 | 20-SEP-06:04 | 24.30 |
October | 75278977.75 | 1675.18 | 28-OCT-21:53 | 15.00 |
November | 0.191135E+09 | 1694.71 | 30-NOV-19:13 | 14.00 |
December | 0.469070E+09 | 1799.13 | 12-DEC-20:13 | 15.00 |
Annual Sum or Average | 0.146695E+10 | |||
Minimum of Months | 3448551.26 | 177.68 | 14.00 | |
Maximum of Months | 0.469070E+09 | 2363.59 | 27.17 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456087E+09 | 4045.54 | 01-JAN-09:02 | 5.90 |
February | 0.468240E+09 | 2631.51 | 04-FEB-09:02 | 9.50 |
March | 0.402948E+09 | 4269.14 | 26-MAR-08:62 | 7.75 |
April | 34755945.30 | 1610.61 | 26-APR-08:03 | 24.33 |
May | 7249788.89 | 1647.32 | 02-MAY-08:03 | 24.33 |
June | 594590.31 | 1171.43 | 13-JUN-08:03 | 25.50 |
July | 206013.16 | 867.57 | 02-JUL-08:03 | 26.58 |
August | 695928.21 | 1575.81 | 24-AUG-08:03 | 26.50 |
September | 1363411.07 | 1598.78 | 28-SEP-08:03 | 24.37 |
October | 0.132487E+09 | 2878.14 | 25-OCT-08:62 | 8.50 |
November | 0.341275E+09 | 2741.79 | 24-NOV-09:02 | 9.00 |
December | 0.793483E+09 | 4146.20 | 07-DEC-09:02 | 6.67 |
Annual Sum or Average | 0.263939E+10 | |||
Minimum of Months | 206013.16 | 867.57 | 5.90 | |
Maximum of Months | 0.793483E+09 | 4269.14 | 26.58 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.564776E+09 | 4553.47 | 01-JAN-09:02 | 5.90 |
February | 0.553829E+09 | 4230.31 | 03-FEB-09:02 | 10.33 |
March | 0.437459E+09 | 4330.92 | 26-MAR-08:62 | 7.75 |
April | 61014785.43 | 2386.99 | 26-APR-21:53 | 16.00 |
May | 34442419.37 | 1856.66 | 13-MAY-08:53 | 22.00 |
June | 19934439.72 | 908.16 | 05-JUN-06:13 | 25.67 |
July | 9034110.63 | 230.57 | 29-JUL-08:10 | 26.33 |
August | 19768416.07 | 702.64 | 03-AUG-19:44 | 24.00 |
September | 32696735.52 | 1070.44 | 19-SEP-08:03 | 26.47 |
October | 0.187116E+09 | 3967.98 | 25-OCT-08:62 | 8.50 |
November | 0.436898E+09 | 4415.99 | 23-NOV-09:02 | 5.45 |
December | 0.990992E+09 | 4585.57 | 07-DEC-09:02 | 6.67 |
Annual Sum or Average | 0.334796E+10 | |||
Minimum of Months | 9034110.63 | 230.57 | 5.45 | |
Maximum of Months | 0.990992E+09 | 4585.57 | 26.47 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110367E+09 | 797.24 | 11-JAN-19:04 | 14.00 |
February | 0.117981E+09 | 839.53 | 03-FEB-19:04 | 13.83 |
March | 0.122078E+09 | 1689.47 | 27-MAR-08:62 | 9.77 |
April | 7261518.03 | 830.89 | 09-APR-08:03 | 21.33 |
May | 1241010.58 | 808.58 | 26-MAY-08:04 | 24.50 |
June | 123253.75 | 699.49 | 14-JUN-08:03 | 27.67 |
July | 42314.02 | 684.71 | 01-JUL-08:03 | 27.50 |
August | 87793.66 | 522.17 | 30-AUG-08:03 | 26.67 |
September | 133048.85 | 593.41 | 29-SEP-08:04 | 26.65 |
October | 28409220.26 | 831.68 | 25-OCT-18:04 | 14.83 |
November | 82963127.99 | 893.22 | 16-NOV-19:04 | 14.83 |
December | 0.229469E+09 | 1012.61 | 11-DEC-19:03 | 14.67 |
Annual Sum or Average | 0.700156E+09 | |||
Minimum of Months | 42314.02 | 522.17 | 9.77 | |
Maximum of Months | 0.229469E+09 | 1689.47 | 27.67 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16737999.71 | 1153.30 | 01-JAN-06:20 | 1.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 70609420.35 | 1919.92 | 07-DEC-07:10 | 1.33 |
Annual Sum or Average | 87347420.06 | |||
Minimum of Months | 0.00 | 0.00 | 1.03 | |
Maximum of Months | 70609420.35 | 1919.92 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.204643E+11 | 19711.29 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.184774E+11 | 19711.29 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.205273E+11 | 19711.29 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.197704E+11 | 19711.29 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.204997E+11 | 19711.29 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.198611E+11 | 19711.29 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.204091E+11 | 19711.29 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.205352E+11 | 19711.29 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.197783E+11 | 19711.29 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.204564E+11 | 19711.29 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.198453E+11 | 19711.29 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.204091E+11 | 19711.29 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.241034E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.184774E+11 | 19711.29 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.205352E+11 | 19711.29 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101186E+10 | 974.63 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.913620E+09 | 974.63 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.101498E+10 | 974.63 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.977556E+09 | 974.63 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.101362E+10 | 974.63 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.982039E+09 | 974.63 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.100913E+10 | 974.63 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.101537E+10 | 974.63 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.977945E+09 | 974.63 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.101147E+10 | 974.63 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.981259E+09 | 974.63 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.100913E+10 | 974.63 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.119180E+11 | 0.101856E+11 | ||||
Minimum of Months | 0.913620E+09 | 974.63 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.101537E+10 | 974.63 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117174E+10 | 1128.63 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.105798E+10 | 1128.63 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.117535E+10 | 1128.63 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.113201E+10 | 1128.63 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.117377E+10 | 1128.63 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.113720E+10 | 1128.63 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.116858E+10 | 1128.63 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.117580E+10 | 1128.63 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.113246E+10 | 1128.63 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.117129E+10 | 1128.63 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.113630E+10 | 1128.63 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.116858E+10 | 1128.63 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.138011E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.105798E+10 | 1128.63 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.117580E+10 | 1128.63 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.247783E+10 | 2386.66 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.223726E+10 | 2386.66 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.248547E+10 | 2386.66 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.239382E+10 | 2386.66 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.248213E+10 | 2386.66 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.240480E+10 | 2386.66 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.247115E+10 | 2386.66 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.248642E+10 | 2386.66 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.239478E+10 | 2386.66 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.247688E+10 | 2386.66 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.240289E+10 | 2386.66 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.247115E+10 | 2386.66 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.291846E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.223726E+10 | 2386.66 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.248642E+10 | 2386.66 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.762439E+09 | 734.39 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.688413E+09 | 734.39 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.764789E+09 | 734.39 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.736588E+09 | 734.39 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.763761E+09 | 734.39 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.739966E+09 | 734.39 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.760382E+09 | 734.39 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.765082E+09 | 734.39 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.736882E+09 | 734.39 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.762145E+09 | 734.39 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.739379E+09 | 734.39 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.760382E+09 | 734.39 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.898021E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.688413E+09 | 734.39 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.765082E+09 | 734.39 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.265929E+10 | 2561.44 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.240110E+10 | 2561.44 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.266749E+10 | 2561.44 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.256913E+10 | 2561.44 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.266390E+10 | 2561.44 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.258091E+10 | 2561.44 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.265212E+10 | 2561.44 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.266851E+10 | 2561.44 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.257015E+10 | 2561.44 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.265826E+10 | 2561.44 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.257886E+10 | 2561.44 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.265212E+10 | 2561.44 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.313218E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.240110E+10 | 2561.44 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.266851E+10 | 2561.44 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.171043E+11 | 16474.99 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.154437E+11 | 16474.99 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.171571E+11 | 16474.99 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.165244E+11 | 16474.99 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.171340E+11 | 16474.99 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.166002E+11 | 16474.99 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.170582E+11 | 16474.99 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.171636E+11 | 16474.99 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.165310E+11 | 16474.99 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.170977E+11 | 16474.99 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.165870E+11 | 16474.99 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.170582E+11 | 16474.99 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.201459E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.154437E+11 | 16474.99 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.171636E+11 | 16474.99 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332597E+09 | 300.93 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.300367E+09 | 300.93 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.329954E+09 | 300.93 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.322251E+09 | 300.93 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.331275E+09 | 300.93 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.319694E+09 | 300.93 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.333875E+09 | 300.93 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.329954E+09 | 300.93 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.322338E+09 | 300.93 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.332554E+09 | 300.93 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.320973E+09 | 300.93 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.333919E+09 | 300.93 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.390975E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.300367E+09 | 300.93 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.333919E+09 | 300.93 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332688E+09 | 301.01 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.300450E+09 | 301.01 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.330044E+09 | 301.01 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.322339E+09 | 301.01 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.331366E+09 | 301.01 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.319782E+09 | 301.01 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.333967E+09 | 301.01 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.330044E+09 | 301.01 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.322426E+09 | 301.01 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.332644E+09 | 301.01 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.321060E+09 | 301.01 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.334010E+09 | 301.01 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.391082E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.300450E+09 | 301.01 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.334010E+09 | 301.01 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.195823E+10 | 1886.18 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.176811E+10 | 1886.18 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.196427E+10 | 1886.18 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.189184E+10 | 1886.18 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.196163E+10 | 1886.18 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.190052E+10 | 1886.18 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.195295E+10 | 1886.18 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.196502E+10 | 1886.18 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.189259E+10 | 1886.18 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.195748E+10 | 1886.18 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.189901E+10 | 1886.18 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.195295E+10 | 1886.18 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.230646E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.176811E+10 | 1886.18 | 0.00 | 0.00 | |
Maximum of Months | 0.196502E+10 | 1886.18 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332688E+09 | 301.01 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.300450E+09 | 301.01 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.330044E+09 | 301.01 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.322339E+09 | 301.01 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.331366E+09 | 301.01 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.319782E+09 | 301.01 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.333967E+09 | 301.01 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.330044E+09 | 301.01 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.322426E+09 | 301.01 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.332644E+09 | 301.01 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.321060E+09 | 301.01 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.334010E+09 | 301.01 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.391082E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.300450E+09 | 301.01 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.334010E+09 | 301.01 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466994E+10 | 4498.11 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.421653E+10 | 4498.11 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.468433E+10 | 4498.11 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.451160E+10 | 4498.11 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.467803E+10 | 4498.11 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.453229E+10 | 4498.11 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.465734E+10 | 4498.11 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.468613E+10 | 4498.11 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.451340E+10 | 4498.11 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.466814E+10 | 4498.11 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.452870E+10 | 4498.11 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.465734E+10 | 4498.11 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.550038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.421653E+10 | 4498.11 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.468613E+10 | 4498.11 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466994E+10 | 4498.11 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.421653E+10 | 4498.11 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.468433E+10 | 4498.11 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.451160E+10 | 4498.11 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.467803E+10 | 4498.11 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.453229E+10 | 4498.11 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.465734E+10 | 4498.11 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.468613E+10 | 4498.11 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.451340E+10 | 4498.11 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.466814E+10 | 4498.11 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.452870E+10 | 4498.11 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.465734E+10 | 4498.11 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.550038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.421653E+10 | 4498.11 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.468613E+10 | 4498.11 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124679E+10 | 1200.92 | 02-JAN-20:10 | 0.371477E+11 | 16602.84 | 01-JAN-07:10 |
February | 0.112574E+10 | 1200.92 | 01-FEB-20:10 | 0.335528E+11 | 16602.84 | 01-FEB-07:10 |
March | 0.125063E+10 | 1200.92 | 01-MAR-20:10 | 0.371477E+11 | 16602.84 | 01-MAR-07:10 |
April | 0.120452E+10 | 1200.92 | 03-APR-19:10 | 0.359494E+11 | 16602.84 | 01-APR-06:10 |
May | 0.124895E+10 | 1200.92 | 01-MAY-19:10 | 0.371477E+11 | 16602.84 | 01-MAY-06:10 |
June | 0.121004E+10 | 1200.92 | 01-JUN-19:10 | 0.359494E+11 | 16602.84 | 01-JUN-06:10 |
July | 0.124343E+10 | 1200.92 | 03-JUL-19:10 | 0.371477E+11 | 16602.84 | 01-JUL-06:10 |
August | 0.125111E+10 | 1200.92 | 01-AUG-19:10 | 0.371477E+11 | 16602.84 | 01-AUG-06:10 |
September | 0.120500E+10 | 1200.92 | 01-SEP-19:10 | 0.359494E+11 | 16602.84 | 01-SEP-06:10 |
October | 0.124631E+10 | 1200.92 | 02-OCT-19:10 | 0.371477E+11 | 16602.84 | 01-OCT-06:10 |
November | 0.120908E+10 | 1200.92 | 01-NOV-19:10 | 0.359494E+11 | 16602.84 | 01-NOV-06:10 |
December | 0.124343E+10 | 1200.92 | 01-DEC-20:10 | 0.371477E+11 | 16602.84 | 01-DEC-07:10 |
Annual Sum or Average | 0.146850E+11 | 0.437384E+12 | ||||
Minimum of Months | 0.112574E+10 | 1200.92 | 0.335528E+11 | 16602.84 | ||
Maximum of Months | 0.125111E+10 | 1200.92 | 0.371477E+11 | 16602.84 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.207249E+10 | 1996.23 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.187127E+10 | 1996.23 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.207888E+10 | 1996.23 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.200222E+10 | 1996.23 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.207608E+10 | 1996.23 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.201140E+10 | 1996.23 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.206690E+10 | 1996.23 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.207967E+10 | 1996.23 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.200302E+10 | 1996.23 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.207169E+10 | 1996.23 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.200981E+10 | 1996.23 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.206690E+10 | 1996.23 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.244103E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.187127E+10 | 1996.23 | 0.00 | 0.00 | |
Maximum of Months | 0.207967E+10 | 1996.23 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.204643E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.184774E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.205273E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.197704E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.204997E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.198611E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.204091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.205352E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.197783E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.204564E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.198453E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.204091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.241034E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.184774E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.205352E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.101186E+10 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2316173.55 | 0.233437E+09 |
February | 0.179968E+10 | 0.913620E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248709E+09 |
March | 0.199990E+10 | 0.101498E+10 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5546508.98 | 0.210057E+09 |
April | 0.192973E+10 | 0.977556E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63022203.00 | 60766445.81 |
May | 0.199475E+10 | 0.101362E+10 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108494E+09 | 27167619.82 |
June | 0.193394E+10 | 0.982039E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200956E+09 | 3495589.96 |
July | 0.199054E+10 | 0.100913E+10 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185553E+09 | 2201960.50 |
August | 0.199896E+10 | 0.101537E+10 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171466E+09 | 3568659.46 |
September | 0.192879E+10 | 0.977945E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118981E+09 | 8735443.20 |
October | 0.199148E+10 | 0.101147E+10 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43553302.72 | 0.109310E+09 |
November | 0.192552E+10 | 0.981259E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4188956.04 | 0.207981E+09 |
December | 0.199054E+10 | 0.100913E+10 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 585402.90 | 0.311203E+09 |
Annual Sum or Average | 0.234744E+11 | 0.119180E+11 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904662E+09 | 0.142663E+10 |
Minimum of Months | 0.179968E+10 | 0.913620E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201960.50 |
Maximum of Months | 0.199990E+10 | 0.101537E+10 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200956E+09 | 0.311203E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.117174E+10 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1232997.43 | 99294981.31 |
February | 0.208403E+10 | 0.105798E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105872E+09 |
March | 0.231589E+10 | 0.117535E+10 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2620584.62 | 91380321.69 |
April | 0.223463E+10 | 0.113201E+10 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24874506.46 | 30476731.76 |
May | 0.230993E+10 | 0.117377E+10 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41784309.94 | 15848458.48 |
June | 0.223950E+10 | 0.113720E+10 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76682796.85 | 2807740.61 |
July | 0.230505E+10 | 0.116858E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70566005.79 | 1761822.45 |
August | 0.231480E+10 | 0.117580E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65091929.69 | 2725292.45 |
September | 0.223354E+10 | 0.113246E+10 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45375351.62 | 5864603.36 |
October | 0.230614E+10 | 0.117129E+10 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17078954.63 | 49343768.03 |
November | 0.222975E+10 | 0.113630E+10 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1847792.78 | 89992840.83 |
December | 0.230505E+10 | 0.116858E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 368274.29 | 0.129830E+09 |
Annual Sum or Average | 0.271834E+11 | 0.138011E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347524E+09 | 0.625199E+09 |
Minimum of Months | 0.208403E+10 | 0.105798E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1761822.45 |
Maximum of Months | 0.231589E+10 | 0.117580E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76682796.85 | 0.129830E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.247783E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3627930.96 | 0.230843E+09 |
February | 0.440737E+09 | 0.223726E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248629E+09 |
March | 0.489771E+09 | 0.248547E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5790279.28 | 0.215866E+09 |
April | 0.472586E+09 | 0.239382E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57174147.01 | 73163720.40 |
May | 0.488511E+09 | 0.248213E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96450179.25 | 38297925.41 |
June | 0.473617E+09 | 0.240480E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180752E+09 | 6668159.83 |
July | 0.487480E+09 | 0.247115E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166319E+09 | 4246403.74 |
August | 0.489542E+09 | 0.248642E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153184E+09 | 6583026.30 |
September | 0.472357E+09 | 0.239478E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106254E+09 | 14206569.69 |
October | 0.487709E+09 | 0.247688E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39889943.03 | 0.117634E+09 |
November | 0.471555E+09 | 0.240289E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4586313.57 | 0.211177E+09 |
December | 0.487480E+09 | 0.247115E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1107255.60 | 0.300563E+09 |
Annual Sum or Average | 0.574883E+10 | 0.291846E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815135E+09 | 0.146788E+10 |
Minimum of Months | 0.440737E+09 | 0.223726E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4246403.74 |
Maximum of Months | 0.489771E+09 | 0.248642E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180752E+09 | 0.300563E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.762439E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3405088.03 | 0.117186E+09 |
February | 0.339028E+09 | 0.688413E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126668E+09 |
March | 0.376747E+09 | 0.764789E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4317472.62 | 0.109686E+09 |
April | 0.363528E+09 | 0.736588E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34554560.66 | 37253699.84 |
May | 0.375778E+09 | 0.763761E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56400681.54 | 19315166.92 |
June | 0.364321E+09 | 0.739966E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104487E+09 | 3153767.92 |
July | 0.374985E+09 | 0.760382E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96415110.33 | 2002376.39 |
August | 0.376571E+09 | 0.765082E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89078534.35 | 3019579.16 |
September | 0.363352E+09 | 0.736882E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62143873.49 | 6591481.40 |
October | 0.375161E+09 | 0.762145E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24557880.82 | 59079967.32 |
November | 0.362735E+09 | 0.739379E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3761344.41 | 0.106786E+09 |
December | 0.374985E+09 | 0.760382E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1140251.85 | 0.155566E+09 |
Annual Sum or Average | 0.442217E+10 | 0.898021E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480262E+09 | 0.746308E+09 |
Minimum of Months | 0.339028E+09 | 0.688413E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2002376.39 |
Maximum of Months | 0.376747E+09 | 0.765082E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104487E+09 | 0.155566E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 2885185.38 | 0.344858E+09 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377320E+09 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 6517006.28 | 0.324316E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 76929699.52 | 0.104943E+09 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.131636E+09 | 54055451.99 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.246806E+09 | 9265148.75 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.227074E+09 | 5946052.15 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.209114E+09 | 9246131.50 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.145017E+09 | 20014459.94 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 53428297.01 | 0.171463E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 4835073.70 | 0.312195E+09 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 723794.46 | 0.454700E+09 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.110497E+10 | 0.218832E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5946052.15 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.246806E+09 | 0.454700E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.265929E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5120033.02 | 0.575084E+09 |
February | 0.236489E+11 | 0.240110E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626134E+09 |
March | 0.262800E+11 | 0.266749E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11564983.74 | 0.539181E+09 |
April | 0.253579E+11 | 0.256913E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136519E+09 | 0.184519E+09 |
May | 0.262123E+11 | 0.266390E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233599E+09 | 95889417.33 |
June | 0.254132E+11 | 0.258091E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437978E+09 | 16441084.66 |
July | 0.261570E+11 | 0.265212E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402951E+09 | 10546965.56 |
August | 0.262677E+11 | 0.266851E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371078E+09 | 16394191.63 |
September | 0.253456E+11 | 0.257015E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257336E+09 | 35429993.82 |
October | 0.261693E+11 | 0.265826E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94810318.48 | 0.294889E+09 |
November | 0.253025E+11 | 0.257886E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8580014.41 | 0.528605E+09 |
December | 0.261570E+11 | 0.265212E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1284441.98 | 0.738179E+09 |
Annual Sum or Average | 0.308468E+12 | 0.313218E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196082E+10 | 0.366129E+10 |
Minimum of Months | 0.236489E+11 | 0.240110E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10546965.56 |
Maximum of Months | 0.262800E+11 | 0.266851E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437978E+09 | 0.738179E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.171043E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14794711.35 | 0.167883E+10 |
February | 0.702046E+11 | 0.154437E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178375E+10 |
March | 0.780153E+11 | 0.171571E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38580078.97 | 0.153430E+10 |
April | 0.752779E+11 | 0.165244E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397335E+09 | 0.513165E+09 |
May | 0.778146E+11 | 0.171340E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677966E+09 | 0.268041E+09 |
June | 0.754422E+11 | 0.166002E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125416E+10 | 46693079.08 |
July | 0.776503E+11 | 0.170582E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115461E+10 | 29796052.64 |
August | 0.779788E+11 | 0.171636E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106425E+10 | 45882993.45 |
September | 0.752414E+11 | 0.165310E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739946E+09 | 98934129.01 |
October | 0.776868E+11 | 0.170977E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272523E+09 | 0.834854E+09 |
November | 0.751137E+11 | 0.165870E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26287915.83 | 0.151911E+10 |
December | 0.776503E+11 | 0.170582E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3905775.45 | 0.218685E+10 |
Annual Sum or Average | 0.915726E+12 | 0.201459E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564436E+10 | 0.105402E+11 |
Minimum of Months | 0.702046E+11 | 0.154437E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29796052.64 |
Maximum of Months | 0.780153E+11 | 0.171636E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125416E+10 | 0.218685E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3242333.08 | 0.123710E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.04 | 0.138531E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5656662.27 | 0.114548E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51353931.32 | 29109999.73 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82751858.54 | 11053884.96 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144747E+09 | 546614.61 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138426E+09 | 437254.82 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128802E+09 | 635554.87 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94567753.47 | 2071676.91 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35976760.81 | 53829255.92 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4252227.25 | 0.110139E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 876931.43 | 0.172196E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690654E+09 | 0.756808E+09 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.04 | 437254.82 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144747E+09 | 0.172196E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2944027.47 | 0.129321E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140198E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5126712.69 | 0.124262E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49958351.15 | 34041406.95 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81144769.67 | 13934929.11 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142784E+09 | 1696054.12 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137637E+09 | 1037932.08 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127395E+09 | 2317784.59 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92559512.98 | 4782505.09 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34766971.73 | 61385102.44 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3998173.27 | 0.116884E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 739579.16 | 0.173158E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679053E+09 | 0.803018E+09 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1037932.08 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142784E+09 | 0.173158E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.332597E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47527.34 | 55642371.60 |
February | 0.00 | 0.300367E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58104521.60 |
March | 0.00 | 0.329954E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 127165.88 | 51794656.28 |
April | 0.00 | 0.322251E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5116381.95 | 20585788.85 |
May | 0.00 | 0.331275E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10181776.46 | 12429009.52 |
June | 0.00 | 0.319694E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22622020.25 | 3538184.24 |
July | 0.00 | 0.333875E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19309763.47 | 2835671.96 |
August | 0.00 | 0.329954E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17784384.65 | 4094237.82 |
September | 0.00 | 0.322338E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11305981.78 | 7027859.34 |
October | 0.00 | 0.332554E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3731061.35 | 31108077.84 |
November | 0.00 | 0.320973E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68148.69 | 51048688.79 |
December | 0.00 | 0.333919E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68985031.88 |
Annual Sum or Average | 0.00 | 0.390975E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90294211.82 | 0.367194E+09 |
Minimum of Months | 0.00 | 0.300367E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2835671.96 |
Maximum of Months | 0.00 | 0.333919E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22622020.25 | 68985031.88 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.332688E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 861758.21 | 35443089.20 |
February | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38885829.38 |
March | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1446537.49 | 33809491.74 |
April | 0.293479E+09 | 0.322339E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13997524.39 | 9153995.35 |
May | 0.303504E+09 | 0.331366E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22705202.38 | 3828784.09 |
June | 0.293842E+09 | 0.319782E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39898985.70 | 408179.87 |
July | 0.303141E+09 | 0.333967E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38448336.46 | 259785.40 |
August | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35598194.86 | 581134.15 |
September | 0.293479E+09 | 0.322426E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25873971.60 | 1236597.02 |
October | 0.303322E+09 | 0.332644E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9747638.94 | 16702131.45 |
November | 0.293661E+09 | 0.321060E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1136133.90 | 32038296.69 |
December | 0.303141E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 221313.00 | 47959195.19 |
Annual Sum or Average | 0.357224E+10 | 0.391082E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189936E+09 | 0.220307E+09 |
Minimum of Months | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259785.40 |
Maximum of Months | 0.303685E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39898985.70 | 47959195.19 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3245778.71 | 0.124710E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 483.49 | 0.139532E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5644416.58 | 0.115645E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51314115.98 | 29809042.43 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82657922.83 | 11269405.13 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144665E+09 | 549714.25 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138314E+09 | 447840.94 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128719E+09 | 666157.79 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94509451.32 | 2164989.21 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35965636.83 | 54602145.53 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4248749.31 | 0.110802E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 877065.79 | 0.173403E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690162E+09 | 0.763601E+09 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 483.49 | 447840.94 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144665E+09 | 0.173403E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2946494.29 | 0.128920E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140884E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5102086.66 | 0.123338E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49842611.72 | 36431032.63 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80937495.44 | 17748417.04 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142713E+09 | 2740309.45 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137511E+09 | 1558498.30 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127239E+09 | 3001042.65 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92399456.48 | 5942897.92 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34676050.69 | 62186822.31 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3967207.80 | 0.116629E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 725978.05 | 0.173638E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678061E+09 | 0.813018E+09 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1558498.30 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142713E+09 | 0.173638E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.195823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1582398.02 | 0.194411E+09 |
February | 0.348285E+10 | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212290E+09 |
March | 0.387034E+10 | 0.196427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3599830.72 | 0.182604E+09 |
April | 0.373454E+10 | 0.189184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42972543.45 | 59568692.61 |
May | 0.386038E+10 | 0.196163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73658905.70 | 30778554.99 |
June | 0.374269E+10 | 0.190052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138388E+09 | 5338906.86 |
July | 0.385223E+10 | 0.195295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127208E+09 | 3432928.95 |
August | 0.386853E+10 | 0.196502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117134E+09 | 5335545.37 |
September | 0.373273E+10 | 0.189259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81131075.52 | 11469552.16 |
October | 0.385404E+10 | 0.195748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29848264.29 | 97127645.91 |
November | 0.372639E+10 | 0.189901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2661058.00 | 0.176314E+09 |
December | 0.385223E+10 | 0.195295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393596.78 | 0.254877E+09 |
Annual Sum or Average | 0.454292E+11 | 0.230646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618578E+09 | 0.123355E+10 |
Minimum of Months | 0.348285E+10 | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3432928.95 |
Maximum of Months | 0.387034E+10 | 0.196502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138388E+09 | 0.254877E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3136747.45 | 0.123623E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 322.80 | 0.137647E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5537606.86 | 0.114356E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50807102.17 | 29167976.79 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82053194.42 | 11211916.77 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143864E+09 | 579971.70 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137513E+09 | 459892.19 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127896E+09 | 664719.48 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93749701.76 | 2100869.04 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35592520.68 | 53827788.13 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4141577.35 | 0.110001E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 840096.30 | 0.171689E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685133E+09 | 0.755329E+09 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 322.80 | 459892.19 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143864E+09 | 0.171689E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2889818.70 | 0.128427E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138782E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5039103.48 | 0.123867E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49464430.55 | 33705259.54 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80525689.28 | 13452036.94 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141985E+09 | 1506408.51 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136761E+09 | 939801.04 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126552E+09 | 2187993.52 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91822881.94 | 4482328.34 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34456574.60 | 60661453.06 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3907515.16 | 0.115855E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 731330.15 | 0.171877E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674135E+09 | 0.795743E+09 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 939801.04 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141985E+09 | 0.171877E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.332688E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1602550.44 | 64139258.43 |
February | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.48 | 71594769.03 |
March | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2823849.40 | 59116972.73 |
April | 0.293479E+09 | 0.322339E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25994499.04 | 15020573.83 |
May | 0.303504E+09 | 0.331366E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41986709.57 | 5758578.14 |
June | 0.293842E+09 | 0.319782E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73649520.77 | 296724.25 |
July | 0.303141E+09 | 0.333967E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70361139.52 | 235904.16 |
August | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65445208.51 | 345081.83 |
September | 0.293479E+09 | 0.322426E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47947301.06 | 1100637.09 |
October | 0.303322E+09 | 0.332644E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18194167.65 | 27928199.13 |
November | 0.293661E+09 | 0.321060E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2110598.88 | 57039534.74 |
December | 0.303141E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 428650.74 | 89220951.80 |
Annual Sum or Average | 0.357224E+10 | 0.391082E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350544E+09 | 0.391797E+09 |
Minimum of Months | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.48 | 235904.16 |
Maximum of Months | 0.303685E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73649520.77 | 89220951.80 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.466994E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5141124.43 | 0.370089E+09 |
February | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404049E+09 |
March | 0.461508E+11 | 0.468433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8254598.43 | 0.351037E+09 |
April | 0.445315E+11 | 0.451160E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86781890.32 | 0.118171E+09 |
May | 0.460320E+11 | 0.467803E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147944E+09 | 62323130.02 |
June | 0.446286E+11 | 0.453229E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277570E+09 | 11109509.57 |
July | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254879E+09 | 7141060.90 |
August | 0.461292E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234875E+09 | 11009240.53 |
September | 0.445099E+11 | 0.451340E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163168E+09 | 23355756.20 |
October | 0.459565E+11 | 0.466814E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61212086.58 | 0.187528E+09 |
November | 0.444343E+11 | 0.452870E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7087022.47 | 0.337041E+09 |
December | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1594950.40 | 0.481844E+09 |
Annual Sum or Average | 0.541708E+12 | 0.550038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124851E+10 | 0.236470E+10 |
Minimum of Months | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7141060.90 |
Maximum of Months | 0.461508E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277570E+09 | 0.481844E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.466994E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4138378.65 | 0.378317E+09 |
February | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413207E+09 |
March | 0.461508E+11 | 0.468433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7613028.13 | 0.358130E+09 |
April | 0.445315E+11 | 0.451160E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86032537.08 | 0.119755E+09 |
May | 0.460320E+11 | 0.467803E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147428E+09 | 62809541.60 |
June | 0.446286E+11 | 0.453229E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277554E+09 | 11128087.24 |
July | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254786E+09 | 7175848.50 |
August | 0.461292E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234611E+09 | 11123531.12 |
September | 0.445099E+11 | 0.451340E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162462E+09 | 23655202.88 |
October | 0.459565E+11 | 0.466814E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60179987.80 | 0.191214E+09 |
November | 0.444343E+11 | 0.452870E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6155719.88 | 0.344145E+09 |
December | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1206732.43 | 0.493006E+09 |
Annual Sum or Average | 0.541708E+12 | 0.550038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124217E+10 | 0.241367E+10 |
Minimum of Months | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7175848.50 |
Maximum of Months | 0.461508E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277554E+09 | 0.493006E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.124679E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 2746164.40 | 0.354783E+09 |
February | 0.369574E+10 | 0.112574E+10 | 0.304050E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387586E+09 |
March | 0.410691E+10 | 0.125063E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 6318519.03 | 0.333717E+09 |
April | 0.396281E+10 | 0.120452E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 76713947.14 | 0.108802E+09 |
May | 0.409635E+10 | 0.124895E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.131840E+09 | 56467962.40 |
June | 0.397146E+10 | 0.121004E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.248442E+09 | 9963237.13 |
July | 0.408770E+10 | 0.124343E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.228017E+09 | 6430511.20 |
August | 0.410499E+10 | 0.125111E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.209921E+09 | 9996680.37 |
September | 0.396089E+10 | 0.120500E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.145134E+09 | 21334279.78 |
October | 0.408962E+10 | 0.124631E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 53285622.86 | 0.177198E+09 |
November | 0.395417E+10 | 0.120908E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4643581.69 | 0.321290E+09 |
December | 0.408770E+10 | 0.124343E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 673598.16 | 0.466730E+09 |
Annual Sum or Average | 0.482060E+11 | 0.146850E+11 | 0.396352E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.110774E+10 | 0.225430E+10 |
Minimum of Months | 0.369574E+10 | 0.112574E+10 | 0.304050E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6430511.20 |
Maximum of Months | 0.410691E+10 | 0.125111E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.248442E+09 | 0.466730E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.207249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2689935.23 | 0.332225E+09 |
February | 0.368610E+10 | 0.187127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363675E+09 |
March | 0.409620E+10 | 0.207888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6189315.79 | 0.315146E+09 |
April | 0.395248E+10 | 0.200222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75107718.37 | 0.105940E+09 |
May | 0.408566E+10 | 0.207608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129069E+09 | 55265658.08 |
June | 0.396110E+10 | 0.201140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243210E+09 | 9748068.32 |
July | 0.407704E+10 | 0.206690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223261E+09 | 6288450.77 |
August | 0.409429E+10 | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205546E+09 | 9771928.20 |
September | 0.395056E+10 | 0.200302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142118E+09 | 20858790.46 |
October | 0.407896E+10 | 0.207169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52176860.49 | 0.170134E+09 |
November | 0.394385E+10 | 0.200981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4548601.24 | 0.304493E+09 |
December | 0.407704E+10 | 0.206690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660104.69 | 0.425608E+09 |
Annual Sum or Average | 0.480803E+11 | 0.244103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108458E+10 | 0.211915E+10 |
Minimum of Months | 0.368610E+10 | 0.187127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6288450.77 |
Maximum of Months | 0.409620E+10 | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243210E+09 | 0.425608E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 19711.29 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 19711.29 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 19711.29 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 19711.29 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 19711.29 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 19711.29 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 19711.29 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 19711.29 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 19711.29 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 19711.29 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 19711.29 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 19711.29 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 974.63 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 31-JAN-16:12 | 237.26 | 01-JAN-07:52 |
February | 1169.53 | 01-FEB-00:10 | 974.63 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 182.10 | 28-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 974.63 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.21 | 16-MAR-15:00 | 236.45 | 26-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 974.63 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.52 | 14-APR-15:15 | 145.92 | 21-APR-04:00 |
May | 1169.53 | 01-MAY-00:10 | 974.63 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.37 | 31-MAY-16:51 | 101.57 | 01-MAY-04:00 |
June | 1169.53 | 01-JUN-00:10 | 974.63 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.62 | 28-JUN-16:00 | 46.60 | 21-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 974.63 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.60 | 19-JUL-13:00 | 47.03 | 01-JUL-05:55 |
August | 1169.53 | 01-AUG-00:10 | 974.63 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.91 | 25-AUG-14:00 | 67.00 | 05-AUG-18:00 |
September | 1169.53 | 01-SEP-00:10 | 974.63 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.70 | 08-SEP-15:00 | 56.24 | 22-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 974.63 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.84 | 01-OCT-13:00 | 181.01 | 25-OCT-06:53 |
November | 1169.53 | 01-NOV-00:10 | 974.63 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.31 | 01-NOV-15:00 | 243.46 | 23-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 974.63 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 | 21-DEC-15:00 | 255.96 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 974.63 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.60 | |||||
Maximum of Months | 1169.53 | 974.63 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 180.62 | 255.96 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 1128.63 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 | 31-JAN-16:00 | 96.71 | 01-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 1128.63 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 78.58 | 01-FEB-06:40 |
March | 1354.32 | 01-MAR-00:10 | 1128.63 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 | 16-MAR-15:00 | 96.35 | 26-MAR-04:00 |
April | 1354.32 | 01-APR-00:10 | 1128.63 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 14-APR-15:00 | 65.41 | 21-APR-04:30 |
May | 1354.32 | 01-MAY-00:10 | 1128.63 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.09 | 31-MAY-16:51 | 48.84 | 01-MAY-04:00 |
June | 1354.32 | 01-JUN-00:10 | 1128.63 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 | 28-JUN-16:00 | 24.83 | 21-JUN-06:00 |
July | 1354.32 | 01-JUL-00:10 | 1128.63 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.76 | 19-JUL-13:00 | 24.68 | 01-JUL-05:55 |
August | 1354.32 | 01-AUG-00:10 | 1128.63 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.36 | 25-AUG-14:00 | 29.52 | 05-AUG-18:00 |
September | 1354.32 | 01-SEP-00:10 | 1128.63 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.24 | 08-SEP-15:00 | 29.92 | 22-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 1128.63 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.28 | 01-OCT-13:10 | 78.38 | 25-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 1128.63 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 | 01-NOV-15:00 | 100.78 | 23-NOV-06:30 |
December | 1354.32 | 01-DEC-00:10 | 1128.63 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 | 25-DEC-14:00 | 104.93 | 06-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 | |||||
Maximum of Months | 1354.32 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 | 104.93 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 2386.66 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 | 31-JAN-16:00 | 223.87 | 01-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 2386.66 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 186.13 | 01-FEB-08:00 |
March | 286.42 | 01-MAR-00:10 | 2386.66 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.14 | 16-MAR-15:00 | 227.32 | 26-MAR-04:00 |
April | 286.42 | 01-APR-00:10 | 2386.66 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.65 | 14-APR-15:00 | 153.96 | 21-APR-04:30 |
May | 286.42 | 01-MAY-00:10 | 2386.66 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.75 | 31-MAY-16:57 | 115.45 | 01-MAY-04:00 |
June | 286.42 | 01-JUN-00:10 | 2386.66 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.78 | 28-JUN-16:00 | 59.12 | 21-JUN-06:00 |
July | 286.42 | 01-JUL-00:10 | 2386.66 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.33 | 19-JUL-13:00 | 59.55 | 01-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 2386.66 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.83 | 25-AUG-14:00 | 69.78 | 05-AUG-18:00 |
September | 286.42 | 01-SEP-00:10 | 2386.66 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.92 | 08-SEP-15:00 | 72.60 | 22-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 2386.66 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.19 | 01-OCT-14:00 | 187.04 | 25-OCT-06:53 |
November | 286.42 | 01-NOV-00:10 | 2386.66 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.11 | 01-NOV-15:00 | 238.37 | 23-NOV-06:30 |
December | 286.42 | 01-DEC-00:10 | 2386.66 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 | 21-DEC-15:00 | 245.71 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.12 | |||||
Maximum of Months | 286.42 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 164.78 | 245.71 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 734.39 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.73 | 31-JAN-16:00 | 124.88 | 01-JAN-07:52 |
February | 220.32 | 01-FEB-00:10 | 734.39 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 98.28 | 01-FEB-05:00 |
March | 220.32 | 01-MAR-00:10 | 734.39 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 16-MAR-15:00 | 124.45 | 26-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 734.39 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.22 | 14-APR-15:25 | 82.67 | 21-APR-04:00 |
May | 220.32 | 01-MAY-00:10 | 734.39 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.67 | 31-MAY-16:51 | 62.40 | 01-MAY-04:00 |
June | 220.32 | 01-JUN-00:10 | 734.39 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.07 | 28-JUN-16:00 | 31.86 | 21-JUN-06:00 |
July | 220.32 | 01-JUL-00:10 | 734.39 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.58 | 19-JUL-13:00 | 31.95 | 01-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 734.39 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.48 | 25-AUG-14:00 | 38.34 | 05-AUG-18:00 |
September | 220.32 | 01-SEP-00:10 | 734.39 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.69 | 08-SEP-15:00 | 37.16 | 22-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 734.39 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.92 | 01-OCT-13:10 | 99.10 | 25-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 734.39 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 01-NOV-15:00 | 128.65 | 23-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 734.39 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 | 21-DEC-15:00 | 134.72 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.86 | |||||
Maximum of Months | 220.32 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 95.07 | 134.72 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 65.42 | 31-JAN-16:00 | 338.79 | 01-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 269.35 | 28-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 62.55 | 16-MAR-15:00 | 337.62 | 26-MAR-06:00 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 140.16 | 14-APR-15:00 | 223.69 | 21-APR-04:00 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 164.88 | 31-MAY-17:00 | 165.65 | 01-MAY-04:00 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 224.99 | 28-JUN-16:00 | 80.72 | 21-JUN-06:00 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 202.54 | 19-JUL-13:00 | 81.31 | 01-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 214.14 | 25-AUG-14:00 | 95.33 | 05-AUG-18:00 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 181.49 | 08-SEP-15:00 | 100.72 | 22-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 165.48 | 01-OCT-14:00 | 267.75 | 25-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 65.16 | 01-NOV-15:00 | 346.58 | 23-NOV-06:10 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 26.41 | 21-DEC-15:00 | 362.31 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 80.72 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 224.99 | 362.31 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2561.44 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.09 | 31-JAN-16:30 | 524.48 | 01-JAN-07:57 |
February | 15368.40 | 01-FEB-00:10 | 2561.44 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 409.76 | 01-FEB-05:00 |
March | 15368.40 | 01-MAR-00:10 | 2561.44 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.00 | 16-MAR-15:00 | 522.68 | 26-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 2561.44 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.72 | 14-APR-15:15 | 359.48 | 21-APR-04:00 |
May | 15368.40 | 01-MAY-00:10 | 2561.44 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.60 | 31-MAY-16:54 | 293.89 | 01-MAY-04:00 |
June | 15368.40 | 01-JUN-00:10 | 2561.44 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.27 | 28-JUN-16:00 | 143.23 | 21-JUN-05:55 |
July | 15368.40 | 01-JUL-00:10 | 2561.44 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.41 | 19-JUL-13:00 | 144.26 | 01-JUL-05:55 |
August | 15368.40 | 01-AUG-00:10 | 2561.44 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.02 | 25-AUG-14:00 | 169.04 | 05-AUG-18:00 |
September | 15368.40 | 01-SEP-00:10 | 2561.44 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.07 | 08-SEP-15:00 | 178.69 | 22-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 2561.44 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.66 | 01-OCT-13:40 | 400.23 | 25-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 2561.44 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.63 | 01-NOV-15:00 | 538.17 | 23-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 2561.44 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.87 | 21-DEC-15:00 | 565.81 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2561.44 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.23 | |||||
Maximum of Months | 15368.40 | 2561.44 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 399.27 | 565.81 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 16474.99 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.70 | 31-JAN-16:20 | 1612.21 | 01-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 16474.99 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1319.44 | 01-FEB-05:30 |
March | 45622.98 | 01-MAR-00:10 | 16474.99 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.16 | 16-MAR-15:00 | 1590.63 | 26-MAR-04:00 |
April | 45622.98 | 01-APR-00:10 | 16474.99 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.65 | 14-APR-15:00 | 1102.00 | 21-APR-04:30 |
May | 45622.98 | 01-MAY-00:10 | 16474.99 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 836.03 | 31-MAY-16:51 | 828.79 | 01-MAY-04:00 |
June | 45622.98 | 01-JUN-00:10 | 16474.99 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.81 | 28-JUN-16:00 | 409.33 | 21-JUN-06:00 |
July | 45622.98 | 01-JUL-00:10 | 16474.99 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.97 | 19-JUL-13:00 | 412.28 | 01-JUL-05:55 |
August | 45622.98 | 01-AUG-00:10 | 16474.99 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1085.79 | 25-AUG-14:00 | 483.11 | 05-AUG-18:00 |
September | 45622.98 | 01-SEP-00:10 | 16474.99 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 920.24 | 08-SEP-15:00 | 507.12 | 22-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 16474.99 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 839.05 | 01-OCT-13:50 | 1302.03 | 25-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 16474.99 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.39 | 01-NOV-15:00 | 1662.86 | 23-NOV-06:30 |
December | 45622.98 | 01-DEC-00:10 | 16474.99 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.93 | 21-DEC-15:00 | 1751.37 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 16474.99 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.33 | |||||
Maximum of Months | 45622.98 | 16474.99 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.81 | 1751.37 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.85 | 31-JAN-17:00 | 137.54 | 01-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 18-FEB-16:20 | 106.71 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 16-MAR-15:20 | 138.27 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.21 | 14-APR-16:00 | 85.69 | 21-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.66 | 31-MAY-16:50 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.39 | 28-JUN-16:00 | 19.78 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.96 | 20-JUL-15:20 | 19.92 | 01-JUL-05:55 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.38 | 25-AUG-16:50 | 38.43 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.35 | 08-SEP-15:20 | 28.89 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 | 03-OCT-16:00 | 106.07 | 25-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 01-NOV-15:20 | 142.34 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 25-DEC-16:20 | 149.60 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 19.78 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 121.39 | 149.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 31-JAN-17:00 | 137.53 | 01-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 106.70 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 16-MAR-15:20 | 138.26 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.20 | 14-APR-15:20 | 85.69 | 21-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.65 | 31-MAY-16:50 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.38 | 28-JUN-16:00 | 33.78 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.95 | 20-JUL-15:20 | 32.24 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 25-AUG-16:50 | 40.30 | 05-AUG-18:10 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.35 | 08-SEP-15:20 | 37.34 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 | 03-OCT-16:00 | 106.06 | 25-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 | 01-NOV-15:20 | 142.33 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 25-DEC-16:20 | 149.59 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.24 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 121.38 | 149.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 300.93 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 31-JAN-16:00 | 44.59 | 01-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 300.93 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 38.93 | 01-FEB-08:00 |
March | 0.00 | 01-MAR-00:10 | 300.93 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 16-MAR-15:00 | 43.01 | 26-MAR-04:00 |
April | 0.00 | 01-APR-00:10 | 300.93 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 | 14-APR-15:00 | 31.25 | 21-APR-04:00 |
May | 0.00 | 01-MAY-00:10 | 300.93 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 | 31-MAY-16:51 | 25.25 | 01-MAY-04:00 |
June | 0.00 | 01-JUN-00:10 | 300.93 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 28-JUN-16:00 | 15.23 | 21-JUN-06:00 |
July | 0.00 | 01-JUL-00:10 | 300.93 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 19-JUL-13:00 | 15.34 | 01-JUL-05:55 |
August | 0.00 | 01-AUG-00:10 | 300.93 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.40 | 25-AUG-14:00 | 17.18 | 05-AUG-18:00 |
September | 0.00 | 01-SEP-00:10 | 300.93 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 | 08-SEP-15:00 | 17.89 | 22-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 300.93 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 | 01-OCT-13:00 | 38.36 | 25-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 300.93 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 | 01-NOV-15:00 | 45.13 | 23-NOV-06:30 |
December | 0.00 | 01-DEC-00:10 | 300.93 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 47.01 | 05-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 300.93 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 | |||||
Maximum of Months | 0.00 | 300.93 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 47.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 301.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 | 31-JAN-17:00 | 38.63 | 01-JAN-07:52 |
February | 180.00 | 01-FEB-00:10 | 301.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 30.69 | 01-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 301.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 | 16-MAR-15:20 | 38.59 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 301.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 14-APR-16:00 | 23.92 | 21-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 301.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 | 31-MAY-16:50 | 16.43 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 301.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 28-JUN-16:00 | 9.21 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 301.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 20-JUL-15:20 | 8.54 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 301.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 25-AUG-16:50 | 10.72 | 05-AUG-18:10 |
September | 180.00 | 01-SEP-00:10 | 301.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 | 08-SEP-15:20 | 10.55 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 301.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 | 03-OCT-16:00 | 30.93 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 301.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 | 01-NOV-15:20 | 39.73 | 23-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 301.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 25-DEC-16:20 | 41.75 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | |||||
Maximum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 41.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.85 | 31-JAN-17:00 | 138.19 | 01-JAN-07:52 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 18-FEB-16:20 | 110.57 | 01-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 16-MAR-15:20 | 138.27 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.21 | 14-APR-15:20 | 85.69 | 21-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.66 | 31-MAY-16:50 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.41 | 28-JUN-16:00 | 19.78 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.96 | 20-JUL-15:20 | 19.92 | 01-JUL-05:55 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.38 | 25-AUG-16:50 | 38.45 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.36 | 08-SEP-15:20 | 30.13 | 22-SEP-07:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 | 03-OCT-16:00 | 109.49 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 01-NOV-15:20 | 142.34 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 | 25-DEC-16:20 | 149.61 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 19.78 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 121.41 | 149.61 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 31-JAN-17:00 | 137.67 | 01-JAN-07:52 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 108.43 | 01-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 16-MAR-15:20 | 138.26 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.20 | 14-APR-16:00 | 85.69 | 21-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.65 | 31-MAY-16:50 | 58.88 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.41 | 28-JUN-16:00 | 39.75 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.95 | 20-JUL-15:20 | 36.90 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 25-AUG-16:50 | 40.21 | 05-AUG-18:10 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.35 | 08-SEP-15:20 | 36.84 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 | 03-OCT-16:00 | 109.10 | 25-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 | 01-NOV-15:20 | 142.33 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 25-DEC-16:20 | 149.59 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.84 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 121.41 | 149.59 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1886.18 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.55 | 31-JAN-16:10 | 183.70 | 01-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1886.18 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 151.24 | 02-FEB-04:00 |
March | 2263.36 | 01-MAR-00:10 | 1886.18 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 | 16-MAR-15:00 | 184.99 | 26-MAR-04:00 |
April | 2263.36 | 01-APR-00:10 | 1886.18 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.67 | 14-APR-15:10 | 126.37 | 21-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1886.18 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.60 | 31-MAY-16:50 | 93.66 | 01-MAY-04:00 |
June | 2263.36 | 01-JUN-00:10 | 1886.18 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.47 | 28-JUN-16:00 | 45.80 | 21-JUN-05:55 |
July | 2263.36 | 01-JUL-00:10 | 1886.18 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.82 | 19-JUL-13:00 | 46.13 | 01-JUL-05:55 |
August | 2263.36 | 01-AUG-00:10 | 1886.18 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.36 | 25-AUG-14:00 | 54.00 | 05-AUG-18:00 |
September | 2263.36 | 01-SEP-00:10 | 1886.18 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.96 | 08-SEP-15:00 | 57.07 | 22-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1886.18 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.93 | 01-OCT-13:00 | 150.00 | 25-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1886.18 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 01-NOV-15:00 | 191.24 | 23-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1886.18 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 | 21-DEC-15:00 | 200.11 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1886.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.80 | ||||
Maximum of Months | 2263.36 | 1886.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.47 | 200.11 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 | 31-JAN-16:20 | 137.97 | 01-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 18-FEB-16:20 | 107.13 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.07 | 16-MAR-15:20 | 138.70 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.87 | 14-APR-15:20 | 86.10 | 21-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.32 | 31-MAY-16:50 | 59.28 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.02 | 28-JUN-16:20 | 20.16 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.63 | 20-JUL-15:20 | 20.30 | 01-JUL-05:55 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.02 | 25-AUG-16:50 | 38.08 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.01 | 08-SEP-15:20 | 29.27 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.09 | 03-OCT-16:00 | 106.48 | 25-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.32 | 01-NOV-15:20 | 142.77 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 25-DEC-16:20 | 150.04 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 20.16 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 121.02 | 150.04 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 | 31-JAN-16:20 | 137.96 | 01-JAN-07:50 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 107.12 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.07 | 16-MAR-15:20 | 138.69 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.87 | 14-APR-15:20 | 86.09 | 21-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.32 | 31-MAY-16:50 | 59.27 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.96 | 28-JUN-16:40 | 31.45 | 21-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.62 | 20-JUL-15:20 | 30.20 | 01-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.04 | 25-AUG-16:50 | 39.84 | 05-AUG-18:10 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.02 | 08-SEP-15:20 | 34.83 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.09 | 03-OCT-16:00 | 106.48 | 25-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.31 | 01-NOV-15:20 | 142.76 | 23-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 25-DEC-16:20 | 150.03 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.20 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 120.96 | 150.03 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 301.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.30 | 31-JAN-17:00 | 70.62 | 01-JAN-07:52 |
February | 180.00 | 01-FEB-00:10 | 301.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 18-FEB-16:20 | 54.81 | 28-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 301.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 16-MAR-15:20 | 70.96 | 26-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 301.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 14-APR-16:00 | 44.05 | 21-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 301.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.75 | 31-MAY-16:50 | 30.33 | 01-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 301.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.96 | 28-JUN-16:00 | 10.31 | 21-JUN-05:55 |
July | 180.00 | 01-JUL-00:10 | 301.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.58 | 20-JUL-15:20 | 10.39 | 01-JUL-05:55 |
August | 180.00 | 01-AUG-00:10 | 301.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.38 | 25-AUG-16:50 | 19.46 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 301.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 08-SEP-15:20 | 14.98 | 22-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 301.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 03-OCT-16:00 | 54.48 | 25-OCT-06:50 |
November | 180.00 | 01-NOV-00:10 | 301.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 | 01-NOV-15:20 | 73.05 | 23-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 301.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 | 25-DEC-16:20 | 76.77 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 10.31 | |||||
Maximum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 61.96 | 76.77 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 4498.11 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.13 | 31-JAN-16:00 | 359.10 | 01-JAN-07:52 |
February | 26988.77 | 01-FEB-00:10 | 4498.11 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 296.88 | 01-FEB-05:20 |
March | 26988.77 | 01-MAR-00:10 | 4498.11 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.67 | 16-MAR-15:00 | 356.64 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 4498.11 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.01 | 14-APR-15:00 | 250.41 | 21-APR-04:00 |
May | 26988.77 | 01-MAY-00:10 | 4498.11 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.16 | 31-MAY-16:56 | 190.01 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 4498.11 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.58 | 28-JUN-16:00 | 93.43 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 4498.11 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.01 | 19-JUL-13:00 | 94.10 | 01-JUL-05:55 |
August | 26988.77 | 01-AUG-00:10 | 4498.11 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.22 | 25-AUG-14:00 | 110.01 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 4498.11 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.06 | 08-SEP-15:00 | 116.20 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 4498.11 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.83 | 01-OCT-13:10 | 295.83 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 4498.11 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 01-NOV-15:00 | 365.08 | 23-NOV-06:30 |
December | 26988.77 | 01-DEC-00:10 | 4498.11 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 | 21-DEC-15:00 | 380.66 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.43 | |||||
Maximum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 254.58 | 380.66 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 4498.11 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.52 | 31-JAN-16:00 | 364.88 | 01-JAN-07:52 |
February | 26988.77 | 01-FEB-00:10 | 4498.11 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 299.98 | 01-FEB-05:20 |
March | 26988.77 | 01-MAR-00:10 | 4498.11 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.67 | 16-MAR-15:00 | 361.02 | 26-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 4498.11 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.01 | 14-APR-15:20 | 253.22 | 21-APR-04:00 |
May | 26988.77 | 01-MAY-00:10 | 4498.11 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.16 | 31-MAY-16:52 | 190.11 | 01-MAY-04:00 |
June | 26988.77 | 01-JUN-00:10 | 4498.11 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.58 | 28-JUN-16:00 | 93.43 | 21-JUN-06:00 |
July | 26988.77 | 01-JUL-00:10 | 4498.11 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.01 | 19-JUL-13:00 | 94.10 | 01-JUL-05:55 |
August | 26988.77 | 01-AUG-00:10 | 4498.11 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.22 | 25-AUG-14:00 | 110.01 | 05-AUG-18:00 |
September | 26988.77 | 01-SEP-00:10 | 4498.11 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.06 | 08-SEP-15:00 | 116.20 | 22-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 4498.11 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.83 | 01-OCT-13:50 | 299.54 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 4498.11 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 01-NOV-15:00 | 368.71 | 23-NOV-06:30 |
December | 26988.77 | 01-DEC-00:10 | 4498.11 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.61 | 21-DEC-15:00 | 384.89 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.43 | |||||
Maximum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 254.58 | 384.89 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1200.92 | 02-JAN-20:10 | 15028.36 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 65.28 | 31-JAN-16:10 | 346.60 | 01-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1200.92 | 01-FEB-20:10 | 15028.36 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 275.74 | 28-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1200.92 | 01-MAR-20:10 | 15028.36 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 62.36 | 16-MAR-15:00 | 345.34 | 26-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 1200.92 | 03-APR-19:10 | 15028.36 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 141.45 | 14-APR-15:15 | 229.29 | 21-APR-04:00 |
May | 2401.70 | 01-MAY-00:10 | 1200.92 | 01-MAY-19:10 | 15028.36 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 166.65 | 31-MAY-16:57 | 170.14 | 01-MAY-04:00 |
June | 2401.70 | 01-JUN-00:10 | 1200.92 | 01-JUN-19:10 | 15028.36 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 227.89 | 28-JUN-16:00 | 83.64 | 21-JUN-05:55 |
July | 2401.70 | 01-JUL-00:10 | 1200.92 | 03-JUL-19:10 | 15028.36 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 204.99 | 19-JUL-13:00 | 84.25 | 01-JUL-05:55 |
August | 2401.70 | 01-AUG-00:10 | 1200.92 | 01-AUG-19:10 | 15028.36 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 216.83 | 25-AUG-14:00 | 98.55 | 05-AUG-18:00 |
September | 2401.70 | 01-SEP-00:10 | 1200.92 | 01-SEP-19:10 | 15028.36 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 183.54 | 08-SEP-15:00 | 103.87 | 22-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1200.92 | 02-OCT-19:10 | 15028.36 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 167.23 | 01-OCT-14:00 | 274.16 | 25-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1200.92 | 01-NOV-19:10 | 15028.36 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 65.01 | 01-NOV-15:00 | 354.54 | 23-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 1200.92 | 01-DEC-20:10 | 15028.36 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 25.53 | 21-DEC-15:00 | 370.59 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1200.92 | 15028.36 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 83.64 | ||||||
Maximum of Months | 2401.70 | 1200.92 | 15028.36 | 22492.83 | 0.00 | 0.00 | 0.00 | 227.89 | 370.59 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1996.23 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.91 | 31-JAN-16:10 | 296.17 | 01-JAN-07:53 |
February | 2395.44 | 01-FEB-00:10 | 1996.23 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 253.54 | 01-FEB-05:00 |
March | 2395.44 | 01-MAR-00:10 | 1996.23 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.05 | 16-MAR-15:00 | 302.91 | 26-MAR-04:00 |
April | 2395.44 | 01-APR-00:10 | 1996.23 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.46 | 14-APR-15:00 | 214.59 | 21-APR-04:00 |
May | 2395.44 | 01-MAY-00:10 | 1996.23 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.12 | 31-MAY-16:50 | 166.58 | 01-MAY-04:00 |
June | 2395.44 | 01-JUN-00:10 | 1996.23 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.07 | 28-JUN-16:00 | 81.86 | 21-JUN-05:55 |
July | 2395.44 | 01-JUL-00:10 | 1996.23 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.66 | 19-JUL-13:00 | 82.45 | 01-JUL-05:55 |
August | 2395.44 | 01-AUG-00:10 | 1996.23 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.24 | 25-AUG-14:00 | 96.38 | 05-AUG-18:00 |
September | 2395.44 | 01-SEP-00:10 | 1996.23 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.67 | 08-SEP-15:00 | 101.81 | 22-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1996.23 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.70 | 01-OCT-13:00 | 250.98 | 25-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1996.23 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.65 | 01-NOV-15:00 | 313.90 | 23-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1996.23 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 21-DEC-15:00 | 326.33 | 05-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.86 | ||||
Maximum of Months | 2395.44 | 1996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.07 | 326.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 25618.83 | 27-JAN-21:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23983.51 | 01-FEB-21:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21682.77 | 01-MAR-21:00 | 17891.83 | 39422.58 | 19265.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23167.39 | 14-APR-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22282.78 | 01-MAY-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23604.12 | 30-JUN-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27063.44 | 21-JUL-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28378.27 | 15-AUG-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30605.78 | 08-SEP-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30202.92 | 04-OCT-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29782.83 | 01-NOV-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28836.07 | 01-DEC-21:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21682.77 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30605.78 | 17891.83 | 39422.58 | 19265.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5378.27 | 14-JAN-13:40 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 | 0.00 |
February | 3883.04 | 21-FEB-14:20 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.49 |
March | 4330.95 | 18-MAR-13:40 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | 0.00 |
April | 4744.59 | 14-APR-14:10 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 104.36 | 0.00 |
May | 3942.58 | 04-MAY-14:10 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 113.11 | 0.00 |
June | 4677.99 | 28-JUN-18:02 | 5457.82 | 5198.04 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 169.25 | 0.00 |
July | 4425.94 | 19-JUL-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 162.51 | 0.00 |
August | 5225.40 | 28-AUG-12:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 132.85 | 0.00 |
September | 5752.68 | 28-SEP-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 124.10 | 0.00 |
October | 5790.03 | 02-OCT-12:40 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 103.03 | 0.00 |
November | 5497.31 | 20-NOV-14:10 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 | 0.00 |
December | 5170.84 | 25-DEC-13:30 | 259.90 | 216.58 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3883.04 | 259.90 | 216.58 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5790.03 | 5457.82 | 5198.04 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 169.25 | 39.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2034.55 | 31-JAN-20:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.11 |
February | 1790.52 | 28-FEB-20:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.98 |
March | 2255.66 | 16-MAR-19:20 | 6320.16 | 6771.76 | 4763.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 |
April | 2839.29 | 14-APR-18:15 | 2106.72 | 2006.45 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 35.71 | 0.00 |
May | 2832.69 | 31-MAY-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 37.68 | 0.00 |
June | 3183.39 | 28-JUN-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 | 0.00 |
July | 3012.48 | 20-JUL-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 50.59 | 0.00 |
August | 2982.82 | 25-AUG-18:20 | 2106.72 | 2006.45 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 56.35 | 0.00 |
September | 2876.18 | 07-SEP-18:15 | 2106.72 | 2006.45 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 45.70 | 0.00 |
October | 2680.14 | 05-OCT-18:20 | 2106.72 | 2006.45 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 0.00 |
November | 2306.49 | 01-NOV-18:17 | 4213.44 | 4012.90 | 3008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
December | 1920.43 | 22-DEC-20:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1790.52 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3183.39 | 6320.16 | 6771.76 | 4763.59 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 | 43.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2007.16 | 27-JAN-21:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 |
February | 1525.64 | 22-FEB-21:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.73 |
March | 2384.40 | 17-MAR-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 |
April | 3090.09 | 14-APR-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 66.03 | 0.00 |
May | 3314.66 | 31-MAY-19:50 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 70.76 | 0.00 |
June | 3791.43 | 28-JUN-19:50 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 125.00 | 0.00 |
July | 3570.83 | 20-JUL-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 112.10 | 0.00 |
August | 3416.21 | 10-AUG-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 111.73 | 0.00 |
September | 3313.86 | 08-SEP-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 92.26 | 0.00 |
October | 3086.87 | 03-OCT-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.05 | 0.00 |
November | 2392.53 | 02-NOV-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 |
December | 1704.43 | 26-DEC-21:00 | 445.54 | 4773.32 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1525.64 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3791.43 | 445.54 | 4773.32 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 125.00 | 110.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 750.49 | 27-JAN-21:00 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.44 |
February | 704.91 | 16-FEB-21:20 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.93 |
March | 812.18 | 17-MAR-20:00 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 |
April | 1408.41 | 25-APR-18:20 | 342.72 | 1305.57 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 | 0.00 |
May | 1736.96 | 31-MAY-18:30 | 171.36 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 59.23 | 0.00 |
June | 2288.55 | 28-JUN-18:25 | 342.72 | 1305.57 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 0.00 |
July | 2009.54 | 20-JUL-18:30 | 171.36 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 75.01 | 0.00 |
August | 1728.52 | 25-AUG-18:15 | 342.72 | 1305.57 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 76.84 | 0.00 |
September | 1587.01 | 08-SEP-19:20 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 59.16 | 0.00 |
October | 1347.74 | 03-OCT-19:30 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 0.00 |
November | 813.53 | 02-NOV-20:00 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
December | 717.90 | 26-DEC-21:20 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 704.91 | 171.36 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2288.55 | 342.72 | 1305.57 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 51.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38231.11 | 31-JAN-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 109.27 |
February | 37936.97 | 09-FEB-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 109.13 |
March | 38668.29 | 16-MAR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 |
April | 39313.25 | 14-APR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 90.17 | 0.00 |
May | 39446.36 | 31-MAY-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 90.32 | 0.00 |
June | 40005.77 | 28-JUN-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 164.59 | 0.00 |
July | 39809.03 | 21-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 165.22 | 0.00 |
August | 39715.96 | 10-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 152.55 | 0.00 |
September | 39560.58 | 08-SEP-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 125.96 | 0.00 |
October | 39213.80 | 03-OCT-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 77.89 | 0.00 |
November | 38517.40 | 01-NOV-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 |
December | 37996.97 | 22-DEC-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 137.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37936.97 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40005.77 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 165.22 | 137.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18617.24 | 14-JAN-13:30 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 | 0.00 |
February | 13950.85 | 25-FEB-14:30 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.66 |
March | 15549.46 | 18-MAR-13:30 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 55.13 | 0.00 |
April | 16361.85 | 14-APR-15:10 | 8538.00 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 248.72 | 0.00 |
May | 13915.14 | 04-MAY-15:10 | 8538.00 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 249.98 | 0.00 |
June | 16153.16 | 28-JUN-18:20 | 35859.60 | 6830.51 | 2743.41 | 0.00 | 0.00 | 0.00 | 0.00 | 370.61 | 0.00 |
July | 15325.67 | 20-JUL-18:02 | 71719.20 | 13661.02 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 329.45 | 0.00 |
August | 17002.42 | 25-AUG-15:10 | 8538.00 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 379.65 | 0.00 |
September | 18621.62 | 28-SEP-15:10 | 8538.00 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 304.49 | 0.00 |
October | 18266.64 | 05-OCT-15:10 | 8538.00 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 227.14 | 0.00 |
November | 18490.23 | 01-NOV-15:10 | 8538.00 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 111.81 | 0.00 |
December | 18012.65 | 25-DEC-13:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13915.14 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18621.62 | 71719.20 | 13661.02 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 379.65 | 155.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39316.50 | 27-JAN-21:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.60 |
February | 34826.37 | 21-FEB-21:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 635.54 |
March | 42107.63 | 16-MAR-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.26 |
April | 48560.77 | 14-APR-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 435.88 | 0.00 |
May | 48517.22 | 31-MAY-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 436.63 | 0.00 |
June | 54358.29 | 28-JUN-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 814.02 | 0.00 |
July | 53112.08 | 21-JUL-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 807.02 | 0.00 |
August | 51998.09 | 10-AUG-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 753.03 | 0.00 |
September | 51363.90 | 08-SEP-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 621.88 | 0.00 |
October | 48378.74 | 03-OCT-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 395.05 | 0.00 |
November | 42981.34 | 01-NOV-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.10 |
December | 37863.24 | 26-DEC-21:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 34826.37 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54358.29 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 814.02 | 635.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5217.07 | 09-JAN-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.38 |
February | 5202.50 | 27-FEB-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 |
March | 5165.79 | 07-MAR-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 |
April | 5069.23 | 07-APR-18:02 | 831.60 | 2556.97 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 | 0.00 |
May | 4968.30 | 09-MAY-08:61 | 360.00 | 2106.87 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 24.89 | 0.00 |
June | 5033.85 | 11-JUN-08:61 | 540.00 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 24.81 | 0.00 |
July | 4785.52 | 01-JUL-08:61 | 540.00 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 31.49 | 0.00 |
August | 4718.88 | 24-AUG-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 | 0.00 |
September | 4802.41 | 19-SEP-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 29.09 | 0.00 |
October | 5158.45 | 28-OCT-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 | 0.00 |
November | 5254.59 | 15-NOV-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 |
December | 5167.81 | 13-DEC-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4718.88 | 216.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5254.59 | 831.60 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 31.49 | 39.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5314.89 | 07-JAN-22:51 | 1386.00 | 4069.61 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.43 |
February | 5251.06 | 01-FEB-17:11 | 874.80 | 1206.52 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.46 |
March | 5417.38 | 16-MAR-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.84 |
April | 5402.78 | 15-APR-21:51 | 1386.00 | 4069.61 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.57 |
May | 5269.55 | 13-MAY-08:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 |
June | 5272.47 | 04-JUN-06:41 | 954.00 | 1962.99 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 | 0.00 |
July | 5080.40 | 06-JUL-07:11 | 619.20 | 1685.30 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 0.00 |
August | 5131.69 | 23-AUG-08:11 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 | 0.00 |
September | 5175.38 | 28-SEP-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 | 0.00 |
October | 5430.99 | 23-OCT-16:41 | 972.00 | 1340.58 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 |
November | 5227.97 | 20-NOV-22:01 | 1620.00 | 2887.03 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.79 |
December | 5316.39 | 13-DEC-17:11 | 874.80 | 1206.52 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5080.40 | 360.00 | 1206.52 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5430.99 | 1800.00 | 4069.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 | 60.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 926.62 | 14-JAN-13:30 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
February | 655.63 | 23-FEB-14:00 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 |
March | 684.83 | 18-MAR-13:30 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 717.51 | 14-APR-13:40 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 0.00 |
May | 555.56 | 04-MAY-13:40 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 0.00 |
June | 668.72 | 28-JUN-18:03 | 0.00 | 1606.96 | 712.05 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 0.00 |
July | 637.98 | 21-JUL-19:10 | 0.00 | 300.93 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 0.00 |
August | 794.44 | 27-AUG-14:00 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 | 0.00 |
September | 914.91 | 28-SEP-13:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 0.00 |
October | 945.64 | 18-OCT-13:10 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 | 0.00 |
November | 957.32 | 20-NOV-13:40 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
December | 930.75 | 25-DEC-13:30 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 555.56 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 957.32 | 0.00 | 1606.96 | 712.05 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 15.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1931.55 | 07-JAN-22:51 | 1386.00 | 2558.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 |
February | 1862.99 | 09-FEB-22:51 | 1260.00 | 1411.74 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 |
March | 1937.44 | 16-MAR-21:51 | 1800.00 | 2016.77 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.85 |
April | 1914.15 | 15-APR-21:51 | 1386.00 | 2558.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 |
May | 1859.45 | 13-MAY-08:51 | 540.00 | 1685.66 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 |
June | 1836.42 | 04-JUN-06:41 | 954.00 | 1234.14 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 0.00 |
July | 1797.67 | 06-JUL-07:11 | 619.20 | 1059.56 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 | 0.00 |
August | 1790.40 | 23-AUG-08:11 | 360.00 | 1324.45 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 | 0.00 |
September | 1821.89 | 16-SEP-08:51 | 540.00 | 1685.66 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 0.00 |
October | 1914.34 | 23-OCT-21:51 | 1800.00 | 2016.77 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.22 |
November | 1934.38 | 20-NOV-22:01 | 1620.00 | 1815.09 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 |
December | 1879.55 | 02-DEC-22:11 | 1108.80 | 2046.87 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1790.40 | 360.00 | 1059.56 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1937.44 | 1800.00 | 2558.59 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 | 17.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4346.29 | 26-JAN-09:02 | 180.00 | 1053.43 | 566.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.16 |
February | 4324.07 | 25-FEB-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 |
March | 4290.59 | 07-MAR-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 |
April | 4401.15 | 18-APR-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 |
May | 4408.96 | 13-MAY-08:62 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 |
June | 4387.40 | 11-JUN-08:61 | 540.00 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 0.00 |
July | 4160.98 | 01-JUL-08:61 | 540.00 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 | 0.00 |
August | 4189.18 | 24-AUG-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 | 0.00 |
September | 4266.64 | 28-SEP-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.53 | 0.00 |
October | 4334.21 | 06-OCT-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 | 0.00 |
November | 4371.64 | 21-NOV-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 |
December | 4317.50 | 13-DEC-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4160.98 | 180.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4408.96 | 583.20 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 | 57.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4453.88 | 27-JAN-09:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 |
February | 4293.73 | 01-FEB-17:11 | 874.80 | 1206.52 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.03 |
March | 4667.26 | 11-MAR-09:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 |
April | 4671.85 | 27-APR-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 |
May | 4662.00 | 13-MAY-08:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 |
June | 4551.95 | 04-JUN-06:41 | 954.00 | 1962.99 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 0.00 |
July | 4376.45 | 06-JUL-07:11 | 619.20 | 1685.30 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 | 0.00 |
August | 4465.81 | 23-AUG-08:11 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 | 0.00 |
September | 4505.54 | 28-SEP-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 | 0.00 |
October | 4648.07 | 09-OCT-08:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.18 |
November | 4602.76 | 21-NOV-09:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
December | 4474.70 | 25-DEC-09:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4293.73 | 360.00 | 1206.52 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4671.85 | 954.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 | 44.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2740.19 | 31-JAN-16:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.55 | 0.00 |
February | 1851.30 | 22-FEB-16:10 | 2514.84 | 1047.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.19 |
March | 2587.42 | 16-MAR-15:13 | 7544.52 | 3143.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.92 | 0.00 |
April | 3455.95 | 14-APR-18:03 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.14 | 0.00 |
May | 3655.46 | 31-MAY-18:15 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 0.00 |
June | 4601.60 | 28-JUN-18:25 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.25 | 0.00 |
July | 4201.86 | 20-JUL-18:15 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.02 | 0.00 |
August | 3993.14 | 25-AUG-18:15 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.16 | 0.00 |
September | 3847.75 | 28-SEP-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.38 | 0.00 |
October | 3588.94 | 06-OCT-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 | 0.00 |
November | 3186.96 | 01-NOV-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.19 | 0.00 |
December | 2630.51 | 22-DEC-16:10 | 2514.84 | 1047.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1851.30 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4601.60 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.25 | 24.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5674.77 | 09-JAN-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.99 |
February | 5645.79 | 27-FEB-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 |
March | 5623.63 | 09-MAR-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 0.00 |
April | 5515.04 | 07-APR-18:02 | 831.60 | 2556.97 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 | 0.00 |
May | 5409.45 | 09-MAY-08:61 | 360.00 | 2106.87 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 25.25 | 0.00 |
June | 5487.41 | 11-JUN-08:61 | 540.00 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 25.14 | 0.00 |
July | 5215.11 | 01-JUL-08:61 | 540.00 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 31.80 | 0.00 |
August | 5096.27 | 24-AUG-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 0.00 |
September | 5202.15 | 19-SEP-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 29.81 | 0.00 |
October | 5626.68 | 28-OCT-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 0.00 |
November | 5721.21 | 15-NOV-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 |
December | 5607.68 | 13-DEC-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5096.27 | 216.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5721.21 | 831.60 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 31.80 | 39.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5724.03 | 07-JAN-22:51 | 1386.00 | 4069.61 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 |
February | 5696.34 | 01-FEB-17:11 | 874.80 | 1206.52 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.62 |
March | 5857.01 | 16-MAR-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 |
April | 5866.81 | 15-APR-21:51 | 1386.00 | 4069.61 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 |
May | 5722.09 | 13-MAY-08:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 |
June | 5673.99 | 04-JUN-06:41 | 954.00 | 1962.99 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 | 0.00 |
July | 5491.56 | 06-JUL-07:11 | 619.20 | 1685.30 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | 0.00 |
August | 5556.79 | 23-AUG-08:11 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 20.09 | 0.00 |
September | 5629.27 | 28-SEP-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 0.00 |
October | 5919.44 | 23-OCT-16:41 | 972.00 | 1340.58 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
November | 5632.28 | 20-NOV-22:01 | 1620.00 | 2887.03 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.12 |
December | 5775.22 | 13-DEC-17:11 | 874.80 | 1206.52 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5491.56 | 360.00 | 1206.52 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5919.44 | 1800.00 | 4069.61 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 20.09 | 59.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3029.53 | 09-JAN-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 |
February | 2984.06 | 25-FEB-16:12 | 324.00 | 596.00 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 |
March | 2962.08 | 07-MAR-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 |
April | 2905.72 | 07-APR-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 0.00 |
May | 2857.55 | 13-MAY-08:62 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 |
June | 2890.40 | 11-JUN-08:61 | 540.00 | 1685.66 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 | 0.00 |
July | 2737.52 | 01-JUL-08:61 | 540.00 | 1685.66 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 | 0.00 |
August | 2714.26 | 24-AUG-08:62 | 216.00 | 794.67 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 0.00 |
September | 2788.44 | 16-SEP-08:62 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 0.00 |
October | 2980.59 | 28-OCT-15:12 | 324.00 | 596.00 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 | 0.00 |
November | 3010.75 | 15-NOV-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
December | 2989.01 | 13-DEC-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2714.26 | 216.00 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3029.53 | 583.20 | 1685.66 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 | 20.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19229.55 | 06-JAN-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.74 |
February | 18894.36 | 21-FEB-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.70 |
March | 21577.60 | 17-MAR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.05 |
April | 24243.59 | 14-APR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 0.00 |
May | 24900.72 | 31-MAY-18:15 | 41982.53 | 7996.64 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 162.73 | 0.00 |
June | 27564.01 | 28-JUN-18:30 | 41982.53 | 7996.64 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 233.94 | 0.00 |
July | 26310.69 | 21-JUL-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 142.35 | 0.00 |
August | 26136.52 | 10-AUG-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 134.90 | 0.00 |
September | 25458.91 | 07-SEP-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 127.18 | 0.00 |
October | 24113.38 | 03-OCT-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 79.98 | 0.00 |
November | 21054.18 | 02-NOV-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.76 |
December | 18642.13 | 26-DEC-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18642.13 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27564.01 | 41982.53 | 7996.64 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 233.94 | 157.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20625.93 | 06-JAN-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.74 |
February | 20305.56 | 21-FEB-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.70 |
March | 22823.31 | 17-MAR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.05 |
April | 25442.68 | 14-APR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 0.00 |
May | 26184.48 | 31-MAY-18:15 | 41982.53 | 7996.64 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 162.73 | 0.00 |
June | 28853.70 | 28-JUN-18:30 | 41982.53 | 7996.64 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 233.94 | 0.00 |
July | 27503.87 | 21-JUL-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 142.35 | 0.00 |
August | 27324.18 | 10-AUG-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 134.90 | 0.00 |
September | 26636.42 | 07-SEP-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 127.18 | 0.00 |
October | 25297.93 | 03-OCT-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 79.98 | 0.00 |
November | 22304.49 | 02-NOV-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.76 |
December | 20009.43 | 26-DEC-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20009.43 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28853.70 | 41982.53 | 7996.64 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 233.94 | 157.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28533.76 | 29-JAN-11:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 38.11 |
February | 28203.02 | 18-FEB-11:40 | 1601.14 | 667.18 | 30056.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 |
March | 29395.40 | 18-MAR-10:50 | 800.57 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.14 | 0.00 |
April | 31523.13 | 14-APR-10:50 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 86.76 | 0.00 |
May | 31711.66 | 07-MAY-10:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 84.88 | 0.00 |
June | 32724.27 | 28-JUN-10:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 175.24 | 0.00 |
July | 32321.38 | 10-JUL-10:50 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 150.77 | 0.00 |
August | 32548.29 | 26-AUG-10:50 | 800.57 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 163.44 | 0.00 |
September | 32285.11 | 09-SEP-10:50 | 800.57 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 125.08 | 0.00 |
October | 31358.60 | 05-OCT-10:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 82.51 | 0.00 |
November | 29282.23 | 01-NOV-10:50 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 7.55 | 0.00 |
December | 28282.61 | 25-DEC-11:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28203.02 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32724.27 | 1601.14 | 667.18 | 30056.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 175.24 | 65.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6898.87 | 24-JAN-13:50 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 | 0.00 |
February | 6179.64 | 23-FEB-14:00 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.06 |
March | 8227.11 | 18-MAR-14:30 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.55 | 0.00 |
April | 10957.28 | 14-APR-15:10 | 1330.80 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.46 | 0.00 |
May | 10281.94 | 09-MAY-12:50 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.52 | 0.00 |
June | 11694.62 | 28-JUN-15:10 | 1330.80 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.02 | 0.00 |
July | 11573.39 | 20-JUL-13:20 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.46 | 0.00 |
August | 12052.20 | 09-AUG-13:30 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.16 | 0.00 |
September | 12092.82 | 07-SEP-13:30 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.07 | 0.00 |
October | 11396.61 | 02-OCT-13:10 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 | 0.00 |
November | 8504.29 | 01-NOV-15:10 | 1330.80 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.50 | 0.00 |
December | 6587.29 | 25-DEC-13:40 | 532.32 | 443.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6179.64 | 532.32 | 443.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12092.82 | 1330.80 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.02 | 82.06 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.554156E+12 | 371168.39 | 31-JAN-19:10 | 0.375081E+12 | 328760.48 | 23-JAN-18:30 |
February | 0.460610E+12 | 322872.90 | 16-FEB-20:19 | 0.337326E+12 | 328697.34 | 03-FEB-18:30 |
March | 0.542523E+12 | 388918.05 | 16-MAR-18:30 | 0.366050E+12 | 323040.66 | 01-MAR-18:40 |
April | 0.633577E+12 | 449766.02 | 14-APR-18:10 | 0.342514E+12 | 312267.00 | 03-APR-17:00 |
May | 0.701596E+12 | 472938.66 | 31-MAY-18:10 | 0.341111E+12 | 300953.88 | 01-MAY-17:49 |
June | 0.788446E+12 | 544738.40 | 28-JUN-18:10 | 0.320014E+12 | 289255.96 | 01-JUN-17:00 |
July | 0.823167E+12 | 519791.90 | 21-JUL-19:30 | 0.325271E+12 | 280733.76 | 03-JUL-17:49 |
August | 0.814888E+12 | 515985.35 | 10-AUG-19:10 | 0.327105E+12 | 285204.19 | 31-AUG-17:00 |
September | 0.757778E+12 | 498849.26 | 08-SEP-19:10 | 0.323975E+12 | 294448.38 | 29-SEP-17:30 |
October | 0.635022E+12 | 468077.91 | 03-OCT-18:10 | 0.346778E+12 | 307098.25 | 31-OCT-17:30 |
November | 0.542516E+12 | 395553.22 | 01-NOV-18:10 | 0.348172E+12 | 318440.44 | 30-NOV-18:49 |
December | 0.548382E+12 | 348930.18 | 06-DEC-07:10 | 0.369964E+12 | 327186.96 | 29-DEC-18:30 |
Annual Sum or Average | 0.780266E+13 | 0.412336E+13 | ||||
Minimum of Months | 0.460610E+12 | 322872.90 | 0.320014E+12 | 280733.76 | ||
Maximum of Months | 0.823167E+12 | 544738.40 | 0.375081E+12 | 328760.48 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.129696E+12 | 0.315787E+11 | 0.141138E+12 | 0.715096E+11 | 0.933029E+11 | 0.128314E+09 | 0.134104E+11 | 0.696771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117116E+12 | 0.270885E+11 | 0.127470E+12 | 0.645894E+11 | 0.819514E+11 | 0.115896E+09 | 0.112735E+11 | 0.276291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129400E+12 | 0.278512E+11 | 0.141191E+12 | 0.715122E+11 | 0.923432E+11 | 0.128314E+09 | 0.126812E+11 | 0.636904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125475E+12 | 0.247635E+11 | 0.136545E+12 | 0.692026E+11 | 0.970294E+11 | 0.124175E+09 | 0.233306E+09 | 0.176604E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129561E+12 | 0.237055E+11 | 0.141170E+12 | 0.715109E+11 | 0.103097E+12 | 0.128314E+09 | 5004028.48 | 0.228687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125286E+12 | 0.221555E+11 | 0.136635E+12 | 0.692051E+11 | 0.107881E+12 | 0.124175E+09 | 634696.90 | 0.323531E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129759E+12 | 0.231889E+11 | 0.141079E+12 | 0.715085E+11 | 0.109823E+12 | 0.128314E+09 | 2060891.39 | 0.343934E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129426E+12 | 0.247389E+11 | 0.141202E+12 | 0.715122E+11 | 0.109286E+12 | 0.128314E+09 | 5030907.86 | 0.334828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125517E+12 | 0.259814E+11 | 0.136555E+12 | 0.692027E+11 | 0.103774E+12 | 0.124175E+09 | 2823905.38 | 0.292975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129662E+12 | 0.291306E+11 | 0.141127E+12 | 0.715095E+11 | 0.984956E+11 | 0.128314E+09 | 0.225133E+10 | 0.158988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125477E+12 | 0.301025E+11 | 0.136629E+12 | 0.692036E+11 | 0.902874E+11 | 0.124175E+09 | 0.957355E+10 | 0.775184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129767E+12 | 0.321815E+11 | 0.141079E+12 | 0.715085E+11 | 0.914636E+11 | 0.128314E+09 | 0.353115E+11 | 0.432418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152614E+13 | 0.322467E+12 | 0.166182E+13 | 0.841975E+12 | 0.117873E+13 | 0.151079E+10 | 0.847503E+11 | 0.214130E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117116E+12 | 0.221555E+11 | 0.127470E+12 | 0.645894E+11 | 0.819514E+11 | 0.115896E+09 | 634696.90 | 0.276291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129767E+12 | 0.321815E+11 | 0.141202E+12 | 0.715122E+11 | 0.109823E+12 | 0.128314E+09 | 0.353115E+11 | 0.343934E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.00 | 0.00 | 0.223162E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.200123E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.00 | 0.00 | 0.214026E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.00 | 0.00 | 0.195559E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.00 | 0.00 | 0.189133E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.00 | 0.00 | 0.172900E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.173450E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.175066E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.00 | 0.00 | 0.177004E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.00 | 0.00 | 0.194875E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.00 | 0.00 | 0.201081E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.00 | 0.00 | 0.218143E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.00 | 0.00 | 0.233452E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.00 | 0.00 | 0.172900E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.00 | 0.00 | 0.223162E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 121238.68 | 02-JAN-20:10 | 20502.98 | 01-JAN-00:10 | 89286.95 | 02-JAN-07:10 | 50420.89 | 02-JAN-07:19 | 42380.25 | 31-JAN-16:19 | 47.91 | 04-JAN-20:49 | 87104.24 | 01-JAN-05:00 |
February | 121238.68 | 01-FEB-20:10 | 20502.98 | 01-FEB-00:10 | 89286.95 | 01-FEB-07:10 | 50420.89 | 01-FEB-07:19 | 40209.23 | 21-FEB-22:10 | 47.91 | 01-FEB-10:00 | 41089.62 | 28-FEB-04:00 |
March | 121238.68 | 01-MAR-20:10 | 20502.98 | 01-MAR-00:10 | 89286.95 | 01-MAR-07:10 | 50420.89 | 01-MAR-07:19 | 44890.30 | 16-MAR-20:10 | 47.91 | 02-MAR-10:00 | 80457.78 | 26-MAR-04:00 |
April | 121238.68 | 03-APR-19:10 | 20502.98 | 01-APR-00:10 | 89286.95 | 03-APR-06:10 | 50420.89 | 03-APR-06:19 | 51047.70 | 14-APR-20:10 | 47.91 | 01-APR-08:00 | 16068.43 | 21-APR-04:00 |
May | 121238.68 | 01-MAY-19:10 | 20502.98 | 01-MAY-00:10 | 89286.95 | 01-MAY-06:10 | 50420.89 | 01-MAY-06:19 | 52884.70 | 31-MAY-18:19 | 47.91 | 01-MAY-08:00 | 960.69 | 01-MAY-08:00 |
June | 121238.68 | 01-JUN-19:10 | 20502.98 | 01-JUN-00:10 | 89286.95 | 01-JUN-06:10 | 50420.89 | 01-JUN-06:19 | 59236.70 | 28-JUN-18:40 | 47.91 | 01-JUN-07:30 | 471.24 | 09-JUN-08:09 |
July | 121238.68 | 03-JUL-19:10 | 20502.98 | 01-JUL-00:10 | 89286.95 | 03-JUL-06:10 | 50420.89 | 03-JUL-06:19 | 57319.12 | 21-JUL-20:10 | 47.91 | 01-JUL-08:09 | 880.58 | 31-JUL-08:09 |
August | 121238.68 | 01-AUG-19:10 | 20502.98 | 01-AUG-00:10 | 89286.95 | 01-AUG-06:10 | 50420.89 | 01-AUG-06:19 | 56060.29 | 25-AUG-18:19 | 47.91 | 01-AUG-09:00 | 1310.15 | 11-AUG-08:09 |
September | 121238.68 | 01-SEP-19:10 | 20502.98 | 01-SEP-00:10 | 89286.95 | 01-SEP-06:10 | 50420.89 | 01-SEP-06:19 | 55361.13 | 08-SEP-20:10 | 47.91 | 01-SEP-06:00 | 916.67 | 17-SEP-08:09 |
October | 121238.68 | 02-OCT-19:10 | 20502.98 | 01-OCT-00:10 | 89286.95 | 02-OCT-06:10 | 50420.89 | 02-OCT-06:19 | 51804.33 | 03-OCT-20:10 | 47.91 | 01-OCT-07:49 | 36013.38 | 25-OCT-06:30 |
November | 121238.68 | 01-NOV-19:10 | 20502.98 | 01-NOV-00:10 | 89286.95 | 01-NOV-06:10 | 50420.89 | 01-NOV-06:19 | 45494.05 | 02-NOV-20:10 | 47.91 | 01-NOV-08:00 | 81377.24 | 23-NOV-05:00 |
December | 121238.68 | 01-DEC-20:10 | 20502.98 | 01-DEC-00:10 | 89286.95 | 01-DEC-07:10 | 50420.89 | 01-DEC-07:19 | 41684.62 | 22-DEC-16:19 | 47.91 | 03-DEC-19:19 | 91482.41 | 07-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 121238.68 | 20502.98 | 89286.95 | 50420.89 | 40209.23 | 47.91 | 471.24 | |||||||
Maximum of Months | 121238.68 | 20502.98 | 89286.95 | 50420.89 | 59236.70 | 47.91 | 91482.41 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 131809.49 | 31-JAN-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53324.18 | 22-FEB-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 129937.66 | 16-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 187699.09 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 204107.31 | 31-MAY-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 269751.30 | 28-JUN-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 245385.60 | 20-JUL-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 248684.91 | 25-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 226397.73 | 08-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 193243.84 | 06-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 151783.50 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 113508.36 | 22-DEC-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 53324.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 269751.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 371168.39 | 31-JAN-19:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 41765.50 | 47.91 | 789.32 | 92214.01 | 0.00 |
February | 322872.90 | 16-FEB-20:19 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 38217.62 | 47.91 | 81.48 | 42678.01 | 0.00 |
March | 388918.05 | 16-MAR-18:30 | 107831.13 | 77688.87 | 20502.98 | 29030.08 | 43804.13 | 47.91 | 0.00 | 108330.28 | 0.00 |
April | 449766.02 | 14-APR-18:10 | 107831.13 | 77688.87 | 0.00 | 29010.56 | 50916.29 | 47.91 | 0.00 | 182950.97 | 0.00 |
May | 472938.66 | 31-MAY-18:10 | 107831.13 | 77688.87 | 0.00 | 29010.56 | 52569.63 | 47.91 | 0.00 | 204107.31 | 0.00 |
June | 544738.40 | 28-JUN-18:10 | 107831.13 | 77688.87 | 0.00 | 29010.56 | 58721.62 | 47.91 | 0.00 | 269751.30 | 0.00 |
July | 519791.90 | 21-JUL-19:30 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 56164.99 | 47.91 | 0.00 | 222071.81 | 0.00 |
August | 515985.35 | 10-AUG-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 55355.88 | 47.91 | 0.00 | 218746.42 | 0.00 |
September | 498849.26 | 08-SEP-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 54710.52 | 47.91 | 0.00 | 202594.54 | 0.00 |
October | 468077.91 | 03-OCT-18:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 50374.62 | 47.91 | 0.00 | 181297.62 | 0.00 |
November | 395553.22 | 01-NOV-18:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 44469.09 | 47.91 | 500.96 | 113816.79 | 0.00 |
December | 348930.18 | 06-DEC-07:10 | 67608.49 | 89286.95 | 20502.98 | 50408.87 | 37532.09 | 47.91 | 82256.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 322872.90 | 67608.49 | 77688.87 | 0.00 | 11860.16 | 37532.09 | 47.91 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 544738.40 | 121238.68 | 89286.95 | 20502.98 | 50408.87 | 58721.62 | 47.91 | 82256.77 | 269751.30 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 0.00 | 0.00 | 227554.38 | 18-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 0.00 | 0.00 | 226931.03 | 06-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 0.00 | 0.00 | 221878.31 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 0.00 | 0.00 | 210701.47 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 0.00 | 0.00 | 198767.38 | 01-MAY-20:10 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 0.00 | 0.00 | 187602.95 | 01-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 0.00 | 0.00 | 178954.55 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 0.00 | 0.00 | 181212.96 | 31-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 0.00 | 0.00 | 190660.19 | 29-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 0.00 | 0.00 | 205718.34 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 0.00 | 0.00 | 217230.31 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 0.00 | 0.00 | 224401.05 | 29-DEC-21:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 178954.55 | 0.00 | ||
Maximum of Months | 104248.32 | 0.00 | 0.00 | 0.00 | 227554.38 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.68 | 0.50 | 24.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.68 | 0.50 | 24.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.68 | 0.50 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.83 | 2.33 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.87 | 0.83 | 21.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 21.83 | 3.33 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.87 | 2.33 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.86 | 4.33 | 21.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.75 | 0.83 | 21.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.83 | 1.83 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.79 | 2.33 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.83 | 21.82 | 9.83 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.86 | 4.33 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.77 | 1.17 | 21.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.78 | 2.00 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.80 | 4.67 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.79 | 7.00 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.92 | 1.83 | 21.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.17 | 2.50 | 22.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.09 | 4.00 | 22.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.86 | 1.67 | 21.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.90 | 1.17 | 21.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.00 | 21.89 | 26.00 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 22.17 | 7.00 | 22.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.82 | 1.00 | 21.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.99 | 4.50 | 21.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 22.14 | 4.67 | 22.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.92 | 2.00 | 21.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.24 | 1.17 | 22.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.18 | 2.17 | 22.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 22.14 | 3.83 | 22.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.93 | 3.17 | 21.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.80 | 1.50 | 21.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 24.00 | 22.04 | 24.00 | 22.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 22.24 | 4.67 | 22.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.83 | 3.00 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.88 | 1.67 | 21.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.17 | 21.84 | 5.17 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.88 | 3.00 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.88 | 4.50 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.81 | 2.00 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.78 | 1.33 | 21.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.33 | 21.84 | 8.33 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.88 | 4.50 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.88 | 0.50 | 21.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 21.79 | 1.33 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.88 | 0.83 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 450.17 | 23.98 | 13.67 | 23.98 | 0.00 | 23.98 |
February | 203.00 | 23.95 | 81.67 | 23.97 | 0.00 | 23.97 |
March | 441.50 | 23.88 | 10.50 | 23.89 | 0.00 | 23.89 |
April | 620.00 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
May | 716.50 | 24.00 | 0.00 | 24.00 | 0.00 | 24.00 |
June | 446.00 | 24.00 | 5.50 | 24.00 | 0.00 | 24.00 |
July | 102.83 | 24.00 | 377.00 | 24.00 | 2.17 | 24.00 |
August | 44.33 | 24.00 | 423.17 | 24.00 | 0.00 | 24.00 |
September | 0.17 | 24.00 | 365.00 | 24.00 | 0.00 | 24.00 |
October | 204.83 | 24.00 | 54.67 | 24.00 | 0.00 | 24.00 |
November | 246.17 | 24.00 | 72.00 | 24.00 | 0.00 | 24.00 |
December | 583.67 | 23.98 | 3.67 | 23.98 | 0.00 | 23.98 |
Annual Sum or Average | 4059.17 | 23.98 | 1406.83 | 23.99 | 2.17 | 23.99 |
Minimum of Months | 0.17 | 23.88 | 0.00 | 23.89 | 0.00 | 23.89 |
Maximum of Months | 716.50 | 24.00 | 423.17 | 24.00 | 2.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.33 | 21.82 | 193.17 | 22.34 | 23.17 | 22.29 |
February | 537.50 | 21.50 | 92.00 | 21.85 | 3.17 | 21.84 |
March | 559.00 | 21.75 | 133.83 | 21.98 | 47.83 | 21.91 |
April | 348.83 | 22.21 | 191.50 | 22.80 | 7.17 | 22.78 |
May | 329.00 | 22.53 | 163.33 | 23.02 | 0.00 | 23.02 |
June | 162.17 | 23.02 | 421.33 | 23.73 | 0.00 | 23.73 |
July | 158.00 | 23.30 | 623.83 | 23.78 | 91.00 | 23.77 |
August | 161.33 | 23.22 | 598.33 | 23.76 | 79.67 | 23.75 |
September | 208.00 | 23.02 | 548.50 | 23.63 | 90.50 | 23.61 |
October | 375.33 | 22.10 | 278.33 | 22.85 | 18.17 | 22.83 |
November | 482.17 | 21.80 | 207.83 | 22.24 | 54.33 | 22.16 |
December | 555.33 | 21.61 | 251.67 | 21.78 | 153.17 | 21.66 |
Annual Sum or Average | 4369.00 | 22.06 | 3703.67 | 22.81 | 568.17 | 22.78 |
Minimum of Months | 158.00 | 21.50 | 92.00 | 21.78 | 0.00 | 21.66 |
Maximum of Months | 559.00 | 23.30 | 623.83 | 23.78 | 153.17 | 23.77 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 560.50 | 23.10 | 7.83 | 23.11 | 0.00 | 23.11 |
February | 554.00 | 22.73 | 27.17 | 22.79 | 0.67 | 22.79 |
March | 580.83 | 22.93 | 3.83 | 22.93 | 0.00 | 22.93 |
April | 396.67 | 23.50 | 12.50 | 23.52 | 0.00 | 23.52 |
May | 385.50 | 23.68 | 6.17 | 23.68 | 0.00 | 23.68 |
June | 45.67 | 23.83 | 160.17 | 23.96 | 0.00 | 23.96 |
July | 178.00 | 23.96 | 582.67 | 23.97 | 137.33 | 23.98 |
August | 140.50 | 23.97 | 638.67 | 23.96 | 123.17 | 23.97 |
September | 116.33 | 23.94 | 551.67 | 23.95 | 115.33 | 23.95 |
October | 371.00 | 23.31 | 154.67 | 23.50 | 11.00 | 23.51 |
November | 523.17 | 23.16 | 91.83 | 23.24 | 42.50 | 23.25 |
December | 684.83 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
Annual Sum or Average | 4537.00 | 23.21 | 2237.17 | 23.45 | 430.00 | 23.48 |
Minimum of Months | 45.67 | 22.73 | 0.00 | 22.79 | 0.00 | 22.79 |
Maximum of Months | 684.83 | 23.97 | 638.67 | 23.97 | 137.33 | 23.98 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 715.50 | 23.11 | 3.00 | 23.11 | 0.00 | 23.11 |
February | 634.00 | 22.81 | 4.50 | 22.81 | 0.00 | 22.81 |
March | 663.17 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
April | 540.83 | 23.77 | 0.00 | 23.77 | 0.00 | 23.77 |
May | 534.17 | 23.93 | 0.00 | 23.93 | 0.00 | 23.93 |
June | 140.67 | 23.98 | 45.00 | 23.99 | 0.00 | 23.99 |
July | 65.83 | 23.98 | 541.83 | 23.99 | 0.00 | 23.99 |
August | 47.83 | 23.98 | 615.67 | 23.99 | 0.00 | 23.99 |
September | 7.17 | 23.78 | 489.83 | 23.99 | 0.00 | 23.99 |
October | 468.33 | 23.51 | 106.33 | 23.60 | 0.00 | 23.60 |
November | 598.33 | 23.19 | 32.67 | 23.23 | 0.00 | 23.23 |
December | 744.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
Annual Sum or Average | 5159.83 | 23.26 | 1838.83 | 23.45 | 0.00 | 23.45 |
Minimum of Months | 7.17 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
Maximum of Months | 744.00 | 23.98 | 615.67 | 23.99 | 0.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
February | 672.00 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
March | 744.00 | 22.14 | 0.50 | 22.14 | 0.50 | 22.14 |
April | 667.33 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
May | 625.50 | 23.66 | 0.00 | 23.66 | 0.00 | 23.66 |
June | 182.83 | 23.76 | 45.33 | 23.81 | 0.00 | 23.81 |
July | 77.50 | 23.78 | 527.33 | 23.94 | 0.00 | 23.94 |
August | 60.00 | 23.66 | 539.17 | 23.92 | 0.00 | 23.92 |
September | 100.50 | 23.43 | 397.00 | 23.81 | 0.00 | 23.81 |
October | 586.00 | 22.77 | 79.33 | 22.91 | 0.00 | 22.91 |
November | 715.17 | 22.20 | 0.00 | 22.20 | 0.00 | 22.20 |
December | 744.00 | 21.62 | 43.67 | 21.58 | 43.67 | 21.55 |
Annual Sum or Average | 5918.83 | 22.48 | 1632.33 | 22.78 | 44.17 | 22.77 |
Minimum of Months | 60.00 | 21.62 | 0.00 | 21.58 | 0.00 | 21.55 |
Maximum of Months | 744.00 | 23.78 | 539.17 | 23.94 | 43.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 223.50 | 24.00 | 744.00 | 24.00 | 223.50 | 24.00 |
February | 282.00 | 24.00 | 672.00 | 24.00 | 282.00 | 24.00 |
March | 273.00 | 24.00 | 744.00 | 24.00 | 273.00 | 24.00 |
April | 257.33 | 24.00 | 720.00 | 24.00 | 257.33 | 24.00 |
May | 298.83 | 24.00 | 744.00 | 24.00 | 298.83 | 24.00 |
June | 454.50 | 24.00 | 720.00 | 24.00 | 454.50 | 24.00 |
July | 562.83 | 24.00 | 744.00 | 24.00 | 562.83 | 24.00 |
August | 582.67 | 24.00 | 744.00 | 24.00 | 582.67 | 24.00 |
September | 580.00 | 24.00 | 720.00 | 24.00 | 580.00 | 24.00 |
October | 340.83 | 24.00 | 744.00 | 24.00 | 340.83 | 24.00 |
November | 294.83 | 24.00 | 719.83 | 24.00 | 294.83 | 24.00 |
December | 160.50 | 24.00 | 739.33 | 24.00 | 160.50 | 24.00 |
Annual Sum or Average | 4310.83 | 24.00 | 8755.17 | 24.00 | 4310.83 | 24.00 |
Minimum of Months | 160.50 | 24.00 | 672.00 | 24.00 | 160.50 | 24.00 |
Maximum of Months | 582.67 | 24.00 | 744.00 | 24.00 | 582.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 317.83 | 22.72 | 240.33 | 23.27 | 11.67 | 23.28 |
February | 347.83 | 22.63 | 234.00 | 23.16 | 43.67 | 23.21 |
March | 300.00 | 22.65 | 197.83 | 23.15 | 11.33 | 23.13 |
April | 186.17 | 23.90 | 321.33 | 23.96 | 0.00 | 23.96 |
May | 153.83 | 24.00 | 365.50 | 24.00 | 0.00 | 24.00 |
June | 10.83 | 24.00 | 574.50 | 24.00 | 0.00 | 24.00 |
July | 111.00 | 24.00 | 691.00 | 24.00 | 90.33 | 24.00 |
August | 93.00 | 24.00 | 702.17 | 24.00 | 91.33 | 24.00 |
September | 111.17 | 24.00 | 684.50 | 24.00 | 111.17 | 24.00 |
October | 196.83 | 23.47 | 385.00 | 23.82 | 23.17 | 23.83 |
November | 322.33 | 23.13 | 335.33 | 23.56 | 77.00 | 23.60 |
December | 470.00 | 22.38 | 192.17 | 22.68 | 37.33 | 22.59 |
Annual Sum or Average | 2620.83 | 23.06 | 4923.67 | 23.65 | 497.00 | 23.66 |
Minimum of Months | 10.83 | 22.38 | 192.17 | 22.68 | 0.00 | 22.59 |
Maximum of Months | 470.00 | 24.00 | 702.17 | 24.00 | 111.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 328.83 | 23.28 | 46.17 | 23.35 | 4.33 | 23.36 |
February | 422.83 | 22.95 | 87.83 | 23.10 | 27.00 | 23.12 |
March | 419.00 | 23.02 | 73.17 | 23.16 | 1.83 | 23.16 |
April | 179.50 | 23.52 | 46.17 | 23.62 | 0.00 | 23.62 |
May | 118.83 | 23.64 | 43.17 | 23.74 | 0.00 | 23.74 |
June | 6.17 | 23.80 | 324.50 | 24.00 | 2.17 | 24.00 |
July | 283.17 | 23.99 | 611.50 | 23.98 | 275.33 | 23.99 |
August | 257.00 | 23.99 | 662.50 | 23.98 | 257.00 | 23.98 |
September | 221.00 | 23.98 | 673.50 | 23.97 | 221.00 | 23.97 |
October | 209.50 | 23.47 | 243.17 | 23.74 | 38.33 | 23.75 |
November | 310.00 | 23.33 | 166.17 | 23.50 | 57.83 | 23.50 |
December | 546.17 | 23.17 | 0.17 | 23.17 | 0.00 | 23.17 |
Annual Sum or Average | 3302.00 | 23.39 | 2978.00 | 23.66 | 884.83 | 23.70 |
Minimum of Months | 6.17 | 22.95 | 0.17 | 23.10 | 0.00 | 23.12 |
Maximum of Months | 546.17 | 23.99 | 673.50 | 24.00 | 275.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 668.17 | 21.52 | 52.33 | 21.51 | 45.17 | 21.48 |
February | 643.00 | 21.48 | 12.17 | 21.48 | 9.67 | 21.47 |
March | 702.33 | 21.57 | 61.33 | 21.54 | 56.00 | 21.50 |
April | 609.83 | 21.49 | 23.33 | 21.53 | 9.00 | 21.52 |
May | 637.00 | 21.55 | 9.50 | 21.57 | 0.00 | 21.57 |
June | 546.50 | 21.39 | 72.50 | 21.61 | 0.00 | 21.61 |
July | 555.83 | 21.33 | 89.67 | 21.60 | 0.00 | 21.60 |
August | 539.33 | 21.30 | 111.17 | 21.65 | 0.17 | 21.65 |
September | 535.83 | 21.31 | 95.00 | 21.61 | 2.33 | 21.62 |
October | 636.67 | 21.49 | 51.33 | 21.57 | 17.33 | 21.56 |
November | 650.33 | 21.54 | 77.67 | 21.56 | 60.50 | 21.54 |
December | 701.67 | 21.54 | 205.67 | 21.43 | 203.83 | 21.36 |
Annual Sum or Average | 7426.50 | 21.47 | 861.67 | 21.55 | 404.00 | 21.53 |
Minimum of Months | 535.83 | 21.30 | 9.50 | 21.43 | 0.00 | 21.36 |
Maximum of Months | 702.33 | 21.57 | 205.67 | 21.65 | 203.83 | 21.65 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 691.33 | 21.84 | 87.67 | 21.88 | 68.00 | 21.81 |
February | 643.00 | 21.53 | 33.83 | 21.58 | 22.83 | 21.55 |
March | 649.17 | 21.86 | 100.17 | 22.09 | 62.00 | 22.09 |
April | 606.00 | 21.82 | 35.17 | 22.00 | 8.67 | 22.04 |
May | 623.67 | 21.77 | 13.67 | 21.81 | 0.00 | 21.81 |
June | 518.83 | 21.48 | 78.33 | 21.75 | 0.00 | 21.75 |
July | 547.17 | 21.38 | 89.17 | 21.67 | 4.50 | 21.69 |
August | 530.50 | 21.45 | 111.67 | 21.83 | 13.17 | 21.89 |
September | 515.50 | 21.53 | 104.83 | 21.93 | 18.00 | 22.00 |
October | 610.67 | 21.83 | 68.50 | 22.06 | 20.67 | 22.05 |
November | 651.50 | 21.88 | 125.50 | 21.98 | 99.33 | 21.95 |
December | 723.67 | 21.62 | 280.50 | 21.47 | 273.67 | 21.37 |
Annual Sum or Average | 7311.00 | 21.68 | 1129.00 | 21.83 | 590.83 | 21.81 |
Minimum of Months | 515.50 | 21.38 | 13.67 | 21.47 | 0.00 | 21.37 |
Maximum of Months | 723.67 | 21.88 | 280.50 | 22.09 | 273.67 | 22.09 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.33 | 21.90 | 9.00 | 21.90 | 9.00 | 21.89 |
February | 672.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
March | 720.67 | 22.00 | 13.33 | 21.99 | 12.00 | 21.97 |
April | 712.67 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
May | 738.67 | 22.02 | 0.00 | 22.02 | 0.00 | 22.02 |
June | 703.67 | 21.92 | 0.17 | 21.92 | 0.00 | 21.92 |
July | 720.50 | 21.83 | 6.83 | 21.85 | 6.50 | 21.87 |
August | 717.83 | 21.90 | 20.33 | 21.98 | 14.33 | 22.03 |
September | 687.33 | 21.97 | 32.17 | 22.08 | 20.33 | 22.14 |
October | 725.50 | 22.10 | 8.00 | 22.13 | 1.83 | 22.14 |
November | 710.83 | 21.97 | 48.50 | 22.01 | 43.83 | 22.03 |
December | 744.00 | 21.62 | 130.33 | 21.55 | 130.33 | 21.49 |
Annual Sum or Average | 8597.00 | 21.91 | 268.67 | 21.92 | 238.17 | 21.92 |
Minimum of Months | 672.00 | 21.61 | 0.00 | 21.55 | 0.00 | 21.49 |
Maximum of Months | 744.00 | 22.10 | 130.33 | 22.13 | 130.33 | 22.14 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 695.17 | 21.65 | 49.33 | 21.61 | 49.33 | 21.58 |
February | 658.83 | 21.59 | 10.67 | 21.58 | 10.67 | 21.57 |
March | 709.67 | 21.65 | 47.67 | 21.62 | 47.67 | 21.59 |
April | 582.67 | 21.46 | 9.67 | 21.46 | 8.00 | 21.45 |
May | 589.33 | 21.42 | 0.17 | 21.42 | 0.00 | 21.42 |
June | 499.67 | 21.17 | 52.83 | 21.38 | 0.00 | 21.38 |
July | 520.33 | 21.18 | 131.17 | 21.62 | 0.00 | 21.62 |
August | 522.67 | 21.19 | 144.33 | 21.65 | 0.17 | 21.65 |
September | 518.00 | 21.23 | 118.00 | 21.62 | 1.00 | 21.62 |
October | 613.83 | 21.47 | 55.33 | 21.57 | 15.33 | 21.56 |
November | 678.00 | 21.65 | 63.00 | 21.63 | 63.00 | 21.61 |
December | 738.00 | 21.69 | 190.33 | 21.57 | 190.33 | 21.49 |
Annual Sum or Average | 7326.17 | 21.47 | 872.50 | 21.57 | 385.50 | 21.55 |
Minimum of Months | 499.67 | 21.17 | 0.17 | 21.38 | 0.00 | 21.38 |
Maximum of Months | 738.00 | 21.69 | 190.33 | 21.65 | 190.33 | 21.65 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.67 | 22.02 | 62.17 | 21.96 | 62.17 | 21.90 |
February | 671.67 | 21.71 | 19.17 | 21.69 | 19.17 | 21.68 |
March | 692.50 | 22.04 | 58.00 | 22.03 | 46.33 | 21.98 |
April | 566.67 | 21.78 | 49.50 | 22.11 | 10.83 | 22.15 |
May | 547.17 | 21.71 | 57.33 | 22.21 | 18.17 | 22.39 |
June | 470.17 | 21.27 | 91.17 | 21.77 | 4.33 | 21.82 |
July | 508.00 | 21.24 | 145.33 | 21.78 | 5.50 | 21.82 |
August | 505.00 | 21.35 | 166.67 | 21.96 | 14.50 | 22.04 |
September | 489.83 | 21.50 | 125.67 | 22.07 | 21.00 | 22.19 |
October | 631.00 | 21.98 | 58.83 | 22.16 | 17.50 | 22.15 |
November | 689.83 | 22.01 | 113.50 | 22.03 | 101.17 | 21.99 |
December | 743.50 | 21.73 | 233.50 | 21.58 | 233.50 | 21.49 |
Annual Sum or Average | 7258.00 | 21.73 | 1180.83 | 21.93 | 554.17 | 21.93 |
Minimum of Months | 470.17 | 21.24 | 19.17 | 21.58 | 4.33 | 21.49 |
Maximum of Months | 743.50 | 22.04 | 233.50 | 22.21 | 233.50 | 22.39 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 338.00 | 23.93 | 431.67 | 23.93 | 338.00 | 23.93 |
February | 541.33 | 23.93 | 617.17 | 23.93 | 541.33 | 23.93 |
March | 465.67 | 23.93 | 581.83 | 23.94 | 465.67 | 23.94 |
April | 39.83 | 24.00 | 143.67 | 24.00 | 39.83 | 24.00 |
May | 0.00 | 0.00 | 43.67 | 24.00 | 0.00 | 24.00 |
June | 0.00 | 0.00 | 62.50 | 24.00 | 0.00 | 24.00 |
July | 28.33 | 24.00 | 548.83 | 24.00 | 25.33 | 24.00 |
August | 22.50 | 24.00 | 613.00 | 24.00 | 22.50 | 24.00 |
September | 35.33 | 24.00 | 507.33 | 24.00 | 35.33 | 24.00 |
October | 131.83 | 23.98 | 347.50 | 23.99 | 131.83 | 23.99 |
November | 342.17 | 23.96 | 445.83 | 23.97 | 342.17 | 23.97 |
December | 514.17 | 23.85 | 573.00 | 23.86 | 514.17 | 23.86 |
Annual Sum or Average | 2459.17 | 23.92 | 4916.00 | 23.95 | 2456.17 | 23.94 |
Minimum of Months | 0.00 | 0.00 | 43.67 | 23.86 | 0.00 | 23.86 |
Maximum of Months | 541.33 | 24.00 | 617.17 | 24.00 | 541.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 662.50 | 21.44 | 200.83 | 21.38 | 186.33 | 21.31 |
February | 638.50 | 21.34 | 106.83 | 21.29 | 100.67 | 21.23 |
March | 693.00 | 21.48 | 115.50 | 21.42 | 106.67 | 21.36 |
April | 571.83 | 21.36 | 71.00 | 21.47 | 30.00 | 21.46 |
May | 585.00 | 21.39 | 54.00 | 21.53 | 8.00 | 21.52 |
June | 489.17 | 21.29 | 125.50 | 21.70 | 0.00 | 21.70 |
July | 521.00 | 21.27 | 147.50 | 21.72 | 0.00 | 21.72 |
August | 514.67 | 21.28 | 160.50 | 21.75 | 0.83 | 21.75 |
September | 519.67 | 21.29 | 140.67 | 21.71 | 4.50 | 21.72 |
October | 623.83 | 21.42 | 130.83 | 21.52 | 74.67 | 21.47 |
November | 647.17 | 21.46 | 180.17 | 21.45 | 157.50 | 21.40 |
December | 698.33 | 21.43 | 340.83 | 21.30 | 337.00 | 21.22 |
Annual Sum or Average | 7164.67 | 21.38 | 1774.17 | 21.50 | 1006.17 | 21.45 |
Minimum of Months | 489.17 | 21.27 | 54.00 | 21.29 | 0.00 | 21.22 |
Maximum of Months | 698.33 | 21.48 | 340.83 | 21.75 | 337.00 | 21.75 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 693.00 | 21.74 | 239.17 | 21.63 | 220.17 | 21.50 |
February | 642.33 | 21.37 | 142.50 | 21.32 | 131.50 | 21.23 |
March | 648.83 | 21.80 | 147.67 | 21.97 | 111.00 | 21.93 |
April | 573.67 | 21.69 | 64.50 | 21.92 | 22.33 | 21.95 |
May | 576.17 | 21.61 | 50.50 | 21.73 | 7.00 | 21.73 |
June | 462.33 | 21.41 | 128.50 | 21.82 | 0.00 | 21.82 |
July | 512.83 | 21.34 | 150.00 | 21.79 | 4.83 | 21.81 |
August | 503.17 | 21.45 | 167.00 | 21.95 | 14.17 | 22.01 |
September | 504.33 | 21.51 | 148.50 | 21.99 | 21.50 | 22.07 |
October | 609.33 | 21.77 | 130.83 | 21.94 | 72.67 | 21.87 |
November | 656.67 | 21.78 | 226.33 | 21.78 | 198.17 | 21.69 |
December | 724.17 | 21.48 | 414.17 | 21.30 | 408.00 | 21.20 |
Annual Sum or Average | 7106.83 | 21.59 | 2009.67 | 21.73 | 1211.33 | 21.67 |
Minimum of Months | 462.33 | 21.34 | 50.50 | 21.30 | 0.00 | 21.20 |
Maximum of Months | 724.17 | 21.80 | 414.17 | 21.99 | 408.00 | 22.07 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 601.17 | 21.37 | 137.50 | 21.53 | 67.50 | 21.49 |
February | 591.83 | 21.35 | 36.83 | 21.40 | 19.67 | 21.39 |
March | 674.17 | 21.50 | 81.50 | 21.49 | 67.33 | 21.45 |
April | 594.33 | 21.43 | 34.33 | 21.48 | 14.67 | 21.47 |
May | 629.50 | 21.52 | 2.33 | 21.51 | 2.33 | 21.51 |
June | 551.50 | 21.35 | 38.83 | 21.48 | 0.00 | 21.48 |
July | 562.50 | 21.33 | 93.50 | 21.61 | 0.67 | 21.61 |
August | 554.83 | 21.30 | 132.83 | 21.69 | 2.17 | 21.70 |
September | 539.17 | 21.31 | 120.33 | 21.67 | 4.33 | 21.68 |
October | 597.33 | 21.38 | 108.67 | 21.58 | 31.50 | 21.56 |
November | 602.00 | 21.42 | 135.83 | 21.54 | 83.50 | 21.52 |
December | 621.33 | 21.38 | 257.83 | 21.39 | 221.67 | 21.33 |
Annual Sum or Average | 7119.67 | 21.39 | 1180.33 | 21.53 | 515.33 | 21.51 |
Minimum of Months | 539.17 | 21.30 | 2.33 | 21.39 | 0.00 | 21.33 |
Maximum of Months | 674.17 | 21.52 | 257.83 | 21.69 | 221.67 | 21.70 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 441.83 | 22.99 | 57.50 | 23.10 | 5.67 | 23.11 |
February | 370.83 | 22.88 | 173.67 | 23.19 | 44.17 | 23.23 |
March | 291.00 | 22.92 | 204.17 | 23.34 | 4.67 | 23.35 |
April | 59.00 | 23.42 | 316.67 | 23.90 | 0.00 | 23.90 |
May | 11.50 | 23.54 | 436.00 | 23.98 | 0.00 | 23.98 |
June | 1.83 | 24.00 | 674.50 | 24.00 | 1.83 | 24.00 |
July | 288.33 | 24.00 | 707.33 | 24.00 | 288.33 | 24.00 |
August | 283.50 | 23.99 | 716.33 | 23.99 | 283.50 | 23.99 |
September | 235.83 | 23.99 | 716.67 | 23.97 | 235.83 | 23.97 |
October | 209.67 | 23.29 | 300.17 | 23.67 | 45.17 | 23.69 |
November | 390.67 | 23.13 | 178.83 | 23.34 | 60.00 | 23.38 |
December | 625.67 | 22.87 | 8.50 | 22.89 | 0.00 | 22.89 |
Annual Sum or Average | 3209.67 | 23.25 | 4490.33 | 23.67 | 969.17 | 23.70 |
Minimum of Months | 1.83 | 22.87 | 8.50 | 22.89 | 0.00 | 22.89 |
Maximum of Months | 625.67 | 24.00 | 716.67 | 24.00 | 288.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 275.67 | 23.09 | 103.00 | 23.32 | 4.50 | 23.32 |
February | 236.33 | 23.07 | 284.50 | 23.49 | 48.50 | 23.52 |
March | 169.50 | 23.04 | 311.33 | 23.63 | 4.00 | 23.63 |
April | 18.67 | 23.57 | 415.83 | 23.97 | 0.00 | 23.97 |
May | 5.17 | 23.63 | 509.67 | 24.00 | 0.00 | 24.00 |
June | 0.33 | 24.00 | 692.00 | 24.00 | 0.33 | 24.00 |
July | 271.50 | 24.00 | 712.83 | 24.00 | 271.50 | 24.00 |
August | 271.50 | 24.00 | 725.67 | 24.00 | 271.50 | 24.00 |
September | 227.50 | 24.00 | 720.00 | 23.99 | 227.50 | 23.99 |
October | 128.50 | 23.42 | 381.67 | 23.83 | 44.33 | 23.84 |
November | 268.33 | 23.32 | 239.50 | 23.56 | 58.83 | 23.59 |
December | 503.17 | 23.04 | 10.00 | 23.06 | 0.00 | 23.06 |
Annual Sum or Average | 2376.17 | 23.42 | 5106.00 | 23.80 | 931.00 | 23.82 |
Minimum of Months | 0.33 | 23.04 | 10.00 | 23.06 | 0.00 | 23.06 |
Maximum of Months | 503.17 | 24.00 | 725.67 | 24.00 | 271.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 471.50 | 24.00 | 724.33 | 24.00 | 471.50 | 24.00 |
February | 453.17 | 23.99 | 670.67 | 23.99 | 453.17 | 23.99 |
March | 489.67 | 24.00 | 725.50 | 24.00 | 489.67 | 24.00 |
April | 491.83 | 24.00 | 712.33 | 24.00 | 491.83 | 24.00 |
May | 522.50 | 24.00 | 743.17 | 24.00 | 522.50 | 24.00 |
June | 534.17 | 24.00 | 720.00 | 24.00 | 534.17 | 24.00 |
July | 593.67 | 24.00 | 744.00 | 24.00 | 593.67 | 24.00 |
August | 589.83 | 24.00 | 744.00 | 24.00 | 589.83 | 24.00 |
September | 572.00 | 24.00 | 720.00 | 24.00 | 572.00 | 24.00 |
October | 504.33 | 24.00 | 734.67 | 24.00 | 504.33 | 24.00 |
November | 491.33 | 24.00 | 697.67 | 24.00 | 491.33 | 24.00 |
December | 442.00 | 23.99 | 664.17 | 23.99 | 442.00 | 23.99 |
Annual Sum or Average | 6156.00 | 24.00 | 8600.50 | 24.00 | 6156.00 | 24.00 |
Minimum of Months | 442.00 | 23.99 | 664.17 | 23.99 | 442.00 | 23.99 |
Maximum of Months | 593.67 | 24.00 | 744.00 | 24.00 | 593.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 392.17 | 23.24 | 427.67 | 23.30 | 325.33 | 23.26 |
February | 472.67 | 23.33 | 516.83 | 23.36 | 459.17 | 23.35 |
March | 360.00 | 23.36 | 465.00 | 23.46 | 337.83 | 23.43 |
April | 53.17 | 23.79 | 289.83 | 23.94 | 47.33 | 23.93 |
May | 3.83 | 23.96 | 244.50 | 24.00 | 0.00 | 24.00 |
June | 0.00 | 0.00 | 423.00 | 24.00 | 0.00 | 24.00 |
July | 0.00 | 0.00 | 647.67 | 24.00 | 0.00 | 24.00 |
August | 0.00 | 0.00 | 678.67 | 24.00 | 0.00 | 24.00 |
September | 2.50 | 24.00 | 629.50 | 24.00 | 2.50 | 24.00 |
October | 145.17 | 23.55 | 405.33 | 23.77 | 134.50 | 23.72 |
November | 370.83 | 23.46 | 433.33 | 23.53 | 309.50 | 23.50 |
December | 554.17 | 22.88 | 468.17 | 22.87 | 402.50 | 22.82 |
Annual Sum or Average | 2354.50 | 23.26 | 5629.50 | 23.58 | 2018.67 | 23.51 |
Minimum of Months | 0.00 | 0.00 | 244.50 | 22.87 | 0.00 | 22.82 |
Maximum of Months | 554.17 | 24.00 | 678.67 | 24.00 | 459.17 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.98910 | 24.39401 | 0.24885 | 6.36444 |
February | 672.00000 | 23.97516 | 36.89026 | 0.31187 | 7.11105 |
March | 744.00000 | 23.92287 | 29.59498 | 0.23872 | 6.32774 |
April | 720.00000 | 23.99986 | 20.70057 | 0.20579 | 5.95607 |
May | 744.00000 | 24.00001 | 19.56038 | -0.7208 | 15.97076 |
June | 720.00000 | 24.00011 | 26.99171 | -0.6557 | 14.08566 |
July | 744.00000 | 24.00001 | 39.89540 | -0.5316 | 11.04857 |
August | 744.00000 | 24.00002 | 41.05743 | -0.5104 | 10.51488 |
September | 720.00000 | 24.00078 | 40.21771 | -0.4961 | 10.21591 |
October | 744.00000 | 24.00013 | 26.77937 | 0.29772 | 6.93853 |
November | 720.00000 | 23.99972 | 26.10610 | 0.28986 | 6.85825 |
December | 744.00000 | 23.98568 | 18.11142 | 0.22389 | 6.07806 |
Annual Sum or Average | 8760.00000 | 23.98945 | 29.13587 | -0.0940 | 8.96745 |
Minimum of Months | 672.00000 | 23.92287 | 18.11142 | -0.7208 | 5.95607 |
Maximum of Months | 744.00000 | 24.00078 | 41.05743 | 0.31187 | 15.97076 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.55214 | 27.23060 | 0.00649 | 8.35027 |
February | 672.00000 | 21.98147 | 42.36156 | -0.1038 | 7.52463 |
March | 744.00000 | 22.29459 | 32.31720 | -0.0702 | 7.67151 |
April | 720.00000 | 23.12330 | 21.00618 | 0.14649 | 7.80474 |
May | 744.00000 | 23.33995 | 19.73556 | -0.7170 | 18.79963 |
June | 720.00000 | 23.75451 | 27.89967 | -0.4531 | 10.85448 |
July | 744.00000 | 23.79629 | 46.82548 | -0.3207 | 8.59670 |
August | 744.00000 | 23.74021 | 49.41218 | -0.3166 | 8.75849 |
September | 720.00000 | 23.64566 | 48.76488 | -0.3608 | 9.78838 |
October | 744.00000 | 23.01484 | 30.74936 | 0.18267 | 8.90591 |
November | 720.00000 | 22.50691 | 32.29840 | 0.02274 | 8.11439 |
December | 744.00000 | 22.20930 | 20.31708 | -0.1629 | 9.18797 |
Annual Sum or Average | 8760.00000 | 23.00208 | 33.17646 | -0.1797 | 9.55050 |
Minimum of Months | 672.00000 | 21.98147 | 19.73556 | -0.7170 | 7.52463 |
Maximum of Months | 744.00000 | 23.79629 | 49.41218 | 0.18267 | 18.79963 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.31073 | 27.36668 | 0.13478 | 5.75883 |
February | 672.00000 | 22.92937 | 41.30316 | 0.12128 | 5.72298 |
March | 744.00000 | 23.14603 | 31.96187 | 0.12196 | 5.84502 |
April | 720.00000 | 23.71442 | 21.63296 | 0.21668 | 6.25538 |
May | 744.00000 | 23.82772 | 20.50472 | -0.6533 | 14.24083 |
June | 720.00000 | 23.97451 | 28.81395 | -0.5224 | 10.87268 |
July | 744.00000 | 23.97446 | 47.51992 | -0.3998 | 8.61778 |
August | 744.00000 | 23.96090 | 49.93108 | -0.3894 | 8.34937 |
September | 720.00000 | 23.92876 | 49.14411 | -0.4130 | 8.77486 |
October | 744.00000 | 23.61838 | 31.09930 | 0.25185 | 6.88258 |
November | 720.00000 | 23.35664 | 31.96661 | 0.17798 | 6.16338 |
December | 744.00000 | 23.02612 | 20.92214 | 0.01419 | 5.49952 |
Annual Sum or Average | 8760.00000 | 23.56725 | 33.45670 | -0.1133 | 7.76231 |
Minimum of Months | 672.00000 | 22.92937 | 20.50472 | -0.6533 | 5.49952 |
Maximum of Months | 744.00000 | 23.97451 | 49.93108 | 0.25185 | 14.24083 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99981 | 21.00019 | 0.86027 | 21.42627 |
February | 672.00000 | 23.99973 | 33.50364 | 0.93421 | 24.21019 |
March | 744.00000 | 23.99989 | 25.64610 | 0.89656 | 22.77739 |
April | 720.00000 | 23.99992 | 17.98204 | 0.88717 | 22.45019 |
May | 744.00000 | 23.99996 | 17.75679 | 0.29091 | 8.54119 |
June | 720.00000 | 24.00003 | 27.77886 | 0.39508 | 10.06286 |
July | 744.00000 | 24.00030 | 35.88012 | 0.43955 | 10.67740 |
August | 744.00000 | 24.00044 | 38.28970 | 0.45313 | 10.92539 |
September | 720.00000 | 24.00163 | 41.13441 | 0.45478 | 10.88191 |
October | 744.00000 | 24.00006 | 25.64752 | 0.92389 | 23.85022 |
November | 720.00000 | 24.00000 | 26.55327 | 0.90273 | 23.16062 |
December | 744.00000 | 23.99974 | 13.84384 | 0.79234 | 19.01521 |
Annual Sum or Average | 8760.00000 | 24.00013 | 27.01795 | 0.68413 | 17.28262 |
Minimum of Months | 672.00000 | 23.99973 | 13.84384 | 0.29091 | 8.54119 |
Maximum of Months | 744.00000 | 24.00163 | 41.13441 | 0.93421 | 24.21019 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.44809 | 29.39037 | 0.26941 | 8.51602 |
February | 672.00000 | 23.27315 | 43.40538 | 0.24145 | 7.84960 |
March | 744.00000 | 23.45329 | 33.70450 | 0.24132 | 7.95895 |
April | 720.00000 | 23.97301 | 22.96123 | 0.38741 | 8.75153 |
May | 744.00000 | 23.99939 | 21.44027 | -0.4436 | 9.80524 |
June | 720.00000 | 24.00005 | 29.98966 | -0.2952 | 7.40031 |
July | 744.00000 | 24.00044 | 45.92582 | -0.1915 | 6.33508 |
August | 744.00000 | 24.00047 | 47.99330 | -0.1723 | 6.25467 |
September | 720.00000 | 24.00038 | 48.37944 | -0.1795 | 6.39646 |
October | 744.00000 | 23.85840 | 31.73438 | 0.42261 | 10.03098 |
November | 720.00000 | 23.60612 | 34.28751 | 0.32784 | 9.13055 |
December | 744.00000 | 22.97401 | 22.98335 | 0.07592 | 8.18063 |
Annual Sum or Average | 8760.00000 | 23.71724 | 34.28005 | 0.05543 | 8.05393 |
Minimum of Months | 672.00000 | 22.97401 | 21.44027 | -0.4436 | 6.25467 |
Maximum of Months | 744.00000 | 24.00047 | 48.37944 | 0.42261 | 10.03098 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.62936 | 29.54271 | 0.25587 | 6.61859 |
February | 672.00000 | 23.23325 | 43.27612 | 0.23232 | 6.49458 |
March | 744.00000 | 23.37903 | 34.20087 | 0.21758 | 6.45338 |
April | 720.00000 | 23.85167 | 23.91742 | 0.29684 | 7.02526 |
May | 744.00000 | 23.90773 | 22.75184 | -0.5643 | 11.83470 |
June | 720.00000 | 23.98227 | 30.86135 | -0.4488 | 9.34237 |
July | 744.00000 | 23.98006 | 49.52991 | -0.3241 | 7.45234 |
August | 744.00000 | 23.97274 | 51.91457 | -0.3108 | 7.18397 |
September | 720.00000 | 23.96033 | 51.06525 | -0.3260 | 7.40094 |
October | 744.00000 | 23.80535 | 33.21423 | 0.34750 | 7.93911 |
November | 720.00000 | 23.63742 | 34.11120 | 0.28982 | 7.14269 |
December | 744.00000 | 23.37055 | 23.27242 | 0.13656 | 5.80393 |
Annual Sum or Average | 8760.00000 | 23.72842 | 35.58250 | -0.0182 | 7.56453 |
Minimum of Months | 672.00000 | 23.23325 | 22.75184 | -0.5643 | 5.80393 |
Maximum of Months | 744.00000 | 23.98227 | 51.91457 | 0.34750 | 11.83470 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.70348 | 32.78091 | -0.2310 | 7.87790 |
February | 672.00000 | 21.56036 | 45.47023 | -0.2431 | 7.37561 |
March | 744.00000 | 21.66713 | 36.90487 | -0.2313 | 7.61089 |
April | 720.00000 | 21.76820 | 27.70552 | -0.1440 | 7.10465 |
May | 744.00000 | 21.79991 | 26.41607 | -1.1742 | 36.19633 |
June | 720.00000 | 21.81804 | 33.62390 | -1.0371 | 30.23874 |
July | 744.00000 | 21.81313 | 42.84784 | -1.0141 | 29.01103 |
August | 744.00000 | 21.81222 | 44.56643 | -1.0112 | 29.11422 |
September | 720.00000 | 21.80569 | 45.47870 | -1.0351 | 30.07035 |
October | 744.00000 | 21.74755 | 34.57042 | -0.1435 | 7.18230 |
November | 720.00000 | 21.70664 | 36.04397 | -0.2073 | 7.58897 |
December | 744.00000 | 21.63873 | 26.40156 | -0.3343 | 9.16834 |
Annual Sum or Average | 8760.00000 | 21.73779 | 35.99414 | -0.5694 | 17.44545 |
Minimum of Months | 672.00000 | 21.56036 | 26.40156 | -1.1742 | 7.10465 |
Maximum of Months | 744.00000 | 21.81804 | 45.47870 | -0.1435 | 36.19633 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.05378 | 33.10843 | -0.2201 | 8.18995 |
February | 672.00000 | 21.67148 | 46.54670 | -0.2516 | 7.74739 |
March | 744.00000 | 22.27765 | 36.92582 | -0.1349 | 8.26939 |
April | 720.00000 | 22.15963 | 27.67792 | -0.0852 | 7.19239 |
May | 744.00000 | 22.06927 | 26.16558 | -1.1095 | 33.31624 |
June | 720.00000 | 22.01223 | 33.34328 | -0.9813 | 27.99725 |
July | 744.00000 | 21.89610 | 42.84877 | -0.9922 | 28.09241 |
August | 744.00000 | 21.99697 | 44.71474 | -0.9730 | 27.62991 |
September | 720.00000 | 22.09791 | 45.86506 | -0.9782 | 27.83905 |
October | 744.00000 | 22.27114 | 34.59662 | -0.0785 | 7.34834 |
November | 720.00000 | 22.13611 | 36.53065 | -0.1667 | 7.97616 |
December | 744.00000 | 21.70683 | 26.60637 | -0.3809 | 9.92813 |
Annual Sum or Average | 8760.00000 | 22.03124 | 36.16376 | -0.5314 | 16.85775 |
Minimum of Months | 672.00000 | 21.67148 | 26.16558 | -1.1095 | 7.19239 |
Maximum of Months | 744.00000 | 22.27765 | 46.54670 | -0.0785 | 33.31624 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.90509 | 31.06069 | -0.2740 | 7.33102 |
February | 672.00000 | 21.61213 | 43.33106 | -0.2704 | 6.98798 |
March | 744.00000 | 22.08598 | 34.58735 | -0.1965 | 6.94167 |
April | 720.00000 | 22.07019 | 25.88621 | -0.1971 | 6.82310 |
May | 744.00000 | 22.04368 | 24.22196 | -1.2669 | 39.74665 |
June | 720.00000 | 21.98691 | 31.86834 | -1.1832 | 35.80817 |
July | 744.00000 | 21.88247 | 43.59686 | -1.1526 | 34.29991 |
August | 744.00000 | 21.97370 | 45.64974 | -1.1280 | 33.43712 |
September | 720.00000 | 22.06702 | 46.73061 | -1.1090 | 32.70244 |
October | 744.00000 | 22.16846 | 33.13281 | -0.1531 | 6.69433 |
November | 720.00000 | 22.00195 | 34.70585 | -0.2185 | 7.22234 |
December | 744.00000 | 21.62230 | 23.88158 | -0.4003 | 8.97558 |
Annual Sum or Average | 8760.00000 | 21.95357 | 34.81934 | -0.6316 | 18.99331 |
Minimum of Months | 672.00000 | 21.61213 | 23.88158 | -1.2669 | 6.69433 |
Maximum of Months | 744.00000 | 22.16846 | 46.73061 | -0.1531 | 39.74665 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.76059 | 32.42638 | -0.2216 | 7.67231 |
February | 672.00000 | 21.62417 | 44.67597 | -0.2238 | 7.22799 |
March | 744.00000 | 21.73137 | 36.39824 | -0.2115 | 7.39280 |
April | 720.00000 | 21.81335 | 27.32031 | -0.1274 | 6.98840 |
May | 744.00000 | 21.81845 | 26.06343 | -1.1527 | 35.17052 |
June | 720.00000 | 21.82334 | 33.17367 | -1.0217 | 29.55965 |
July | 744.00000 | 21.82056 | 42.36037 | -0.9891 | 28.10824 |
August | 744.00000 | 21.81901 | 44.08888 | -0.9908 | 28.33381 |
September | 720.00000 | 21.81508 | 45.03330 | -1.0225 | 29.55865 |
October | 744.00000 | 21.79332 | 34.15550 | -0.1272 | 7.08473 |
November | 720.00000 | 21.74632 | 36.01825 | -0.2021 | 7.40017 |
December | 744.00000 | 21.70777 | 26.14672 | -0.3172 | 8.81526 |
Annual Sum or Average | 8760.00000 | 21.77371 | 35.58389 | -0.5528 | 17.00684 |
Minimum of Months | 672.00000 | 21.62417 | 26.06343 | -1.1527 | 6.98840 |
Maximum of Months | 744.00000 | 21.82334 | 45.03330 | -0.1272 | 35.17052 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.02777 | 32.79023 | -0.2276 | 7.46117 |
February | 672.00000 | 21.71404 | 45.44667 | -0.2373 | 7.18208 |
March | 744.00000 | 22.22164 | 36.06648 | -0.1414 | 7.27694 |
April | 720.00000 | 22.31387 | 27.12702 | -0.0472 | 7.61228 |
May | 744.00000 | 22.31092 | 26.01094 | -1.0229 | 32.23414 |
June | 720.00000 | 22.08181 | 32.85160 | -0.9475 | 27.55590 |
July | 744.00000 | 21.93507 | 42.32219 | -0.9585 | 27.26588 |
August | 744.00000 | 22.04745 | 44.14582 | -0.9402 | 26.97254 |
September | 720.00000 | 22.17994 | 45.22418 | -0.9450 | 27.49277 |
October | 744.00000 | 22.32337 | 33.91524 | -0.0614 | 7.18778 |
November | 720.00000 | 22.12119 | 36.64366 | -0.1727 | 7.40827 |
December | 744.00000 | 21.73338 | 26.44307 | -0.3716 | 9.17302 |
Annual Sum or Average | 8760.00000 | 22.08626 | 35.67237 | -0.5081 | 16.29559 |
Minimum of Months | 672.00000 | 21.71404 | 26.01094 | -1.0229 | 7.18208 |
Maximum of Months | 744.00000 | 22.32337 | 45.44667 | -0.0472 | 32.23414 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.64408 | 33.39588 | -0.2848 | 8.97938 |
February | 672.00000 | 21.44197 | 47.52809 | -0.3091 | 8.52716 |
March | 744.00000 | 21.60248 | 37.70341 | -0.2767 | 8.55331 |
April | 720.00000 | 21.74707 | 27.72509 | -0.1481 | 7.67940 |
May | 744.00000 | 21.79365 | 26.33424 | -1.1593 | 36.19996 |
June | 720.00000 | 21.81914 | 33.64419 | -0.9923 | 29.16814 |
July | 744.00000 | 21.81291 | 42.81454 | -0.9746 | 28.03385 |
August | 744.00000 | 21.81186 | 44.65120 | -0.9764 | 28.41927 |
September | 720.00000 | 21.80095 | 45.73422 | -1.0158 | 29.86001 |
October | 744.00000 | 21.71147 | 34.94735 | -0.1683 | 7.88261 |
November | 720.00000 | 21.64444 | 37.08712 | -0.2559 | 8.51263 |
December | 744.00000 | 21.55003 | 26.79697 | -0.4073 | 10.83430 |
Annual Sum or Average | 8760.00000 | 21.69985 | 36.44509 | -0.5827 | 17.78452 |
Minimum of Months | 672.00000 | 21.44197 | 26.33424 | -1.1593 | 7.67940 |
Maximum of Months | 744.00000 | 21.81914 | 47.52809 | -0.1481 | 36.19996 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.94367 | 33.77457 | -0.2852 | 9.33272 |
February | 672.00000 | 21.51836 | 48.70425 | -0.3256 | 9.02389 |
March | 744.00000 | 22.19911 | 37.79720 | -0.1799 | 9.20189 |
April | 720.00000 | 22.11090 | 27.77249 | -0.0917 | 7.71569 |
May | 744.00000 | 22.01982 | 26.17329 | -1.1044 | 33.63046 |
June | 720.00000 | 21.99416 | 33.37268 | -0.9411 | 27.02279 |
July | 744.00000 | 21.88641 | 42.76505 | -0.9553 | 27.16941 |
August | 744.00000 | 21.98322 | 44.69776 | -0.9414 | 26.94745 |
September | 720.00000 | 22.06769 | 45.96143 | -0.9653 | 27.70366 |
October | 744.00000 | 22.18768 | 34.98936 | -0.1107 | 7.94980 |
November | 720.00000 | 22.01827 | 37.58651 | -0.2266 | 8.90609 |
December | 744.00000 | 21.57051 | 27.03184 | -0.4659 | 11.83029 |
Annual Sum or Average | 8760.00000 | 21.96095 | 36.62634 | -0.5512 | 17.26312 |
Minimum of Months | 672.00000 | 21.51836 | 26.17329 | -1.1044 | 7.71569 |
Maximum of Months | 744.00000 | 22.19911 | 48.70425 | -0.0917 | 33.63046 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.74482 | 32.98315 | -0.1957 | 8.23311 |
February | 672.00000 | 21.58917 | 45.48202 | -0.2321 | 7.70189 |
March | 744.00000 | 21.67287 | 37.42047 | -0.2398 | 8.01881 |
April | 720.00000 | 21.75869 | 28.82213 | -0.1697 | 7.50520 |
May | 744.00000 | 21.79554 | 27.74721 | -1.2282 | 38.72226 |
June | 720.00000 | 21.81356 | 34.76530 | -1.0977 | 32.76855 |
July | 744.00000 | 21.81241 | 43.67779 | -1.0494 | 30.60155 |
August | 744.00000 | 21.81126 | 45.30050 | -1.0372 | 30.42382 |
September | 720.00000 | 21.80630 | 46.11343 | -1.0437 | 30.82611 |
October | 744.00000 | 21.75774 | 34.96597 | -0.1352 | 7.58883 |
November | 720.00000 | 21.73464 | 36.67432 | -0.1849 | 7.87111 |
December | 744.00000 | 21.70599 | 27.07028 | -0.2847 | 9.28480 |
Annual Sum or Average | 8760.00000 | 21.75127 | 36.68186 | -0.5772 | 18.36671 |
Minimum of Months | 672.00000 | 21.58917 | 27.07028 | -1.2282 | 7.50520 |
Maximum of Months | 744.00000 | 21.81356 | 46.11343 | -0.1352 | 38.72226 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.32039 | 30.40014 | 0.20521 | 6.35201 |
February | 672.00000 | 23.22841 | 43.68116 | 0.26489 | 6.99832 |
March | 744.00000 | 23.44680 | 34.53100 | 0.28259 | 7.20198 |
April | 720.00000 | 23.88678 | 24.61611 | 0.39090 | 8.42522 |
May | 744.00000 | 23.96486 | 23.24696 | -0.3975 | 8.54389 |
June | 720.00000 | 23.99908 | 31.30053 | -0.2608 | 6.63908 |
July | 744.00000 | 23.99658 | 49.78106 | -0.1477 | 5.77166 |
August | 744.00000 | 23.98859 | 52.36488 | -0.1495 | 5.70984 |
September | 720.00000 | 23.96292 | 51.58722 | -0.1937 | 6.03085 |
October | 744.00000 | 23.70592 | 34.12797 | 0.37946 | 8.68838 |
November | 720.00000 | 23.40729 | 34.88970 | 0.26627 | 7.18440 |
December | 744.00000 | 23.03523 | 23.82739 | 0.06886 | 5.73937 |
Annual Sum or Average | 8760.00000 | 23.66380 | 36.14121 | 0.05747 | 6.93852 |
Minimum of Months | 672.00000 | 23.03523 | 23.24696 | -0.3975 | 5.70984 |
Maximum of Months | 744.00000 | 23.99908 | 52.36488 | 0.39090 | 8.68838 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.54108 | 29.98961 | 0.27834 | 6.98770 |
February | 672.00000 | 23.47043 | 43.07169 | 0.34336 | 7.89898 |
March | 744.00000 | 23.63238 | 34.06331 | 0.34805 | 7.94648 |
April | 720.00000 | 23.94573 | 24.27102 | 0.42762 | 9.01629 |
May | 744.00000 | 23.98958 | 22.92994 | -0.3549 | 7.85692 |
June | 720.00000 | 23.99997 | 31.02726 | -0.2255 | 6.29650 |
July | 744.00000 | 23.99976 | 49.49608 | -0.1119 | 5.58715 |
August | 744.00000 | 23.99800 | 52.05763 | -0.1121 | 5.50669 |
September | 720.00000 | 23.98867 | 51.22783 | -0.1517 | 5.70934 |
October | 744.00000 | 23.82038 | 33.72668 | 0.42800 | 9.39492 |
November | 720.00000 | 23.60676 | 34.44702 | 0.33396 | 7.91361 |
December | 744.00000 | 23.30976 | 23.51913 | 0.15597 | 6.04227 |
Annual Sum or Average | 8760.00000 | 23.77651 | 35.76563 | 0.11157 | 7.17323 |
Minimum of Months | 672.00000 | 23.30976 | 22.92994 | -0.3549 | 5.50669 |
Maximum of Months | 744.00000 | 23.99997 | 52.05763 | 0.42800 | 9.39492 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99506 | 29.87176 | 0.99169 | 27.79265 |
February | 672.00000 | 23.99162 | 40.52817 | 1.04247 | 29.52300 |
March | 744.00000 | 23.99550 | 33.50774 | 1.02855 | 29.27646 |
April | 720.00000 | 23.99903 | 33.20535 | 1.13994 | 34.98618 |
May | 744.00000 | 24.00003 | 35.61384 | 0.65485 | 20.34697 |
June | 720.00000 | 24.00097 | 42.69927 | 0.79591 | 23.91352 |
July | 744.00000 | 24.00205 | 48.78642 | 0.81470 | 23.55135 |
August | 744.00000 | 24.00214 | 49.78584 | 0.80451 | 23.17194 |
September | 720.00000 | 24.00195 | 50.39366 | 0.76317 | 21.52470 |
October | 744.00000 | 23.99819 | 35.28071 | 1.10643 | 33.00483 |
November | 720.00000 | 23.99550 | 34.37111 | 1.02907 | 29.31891 |
December | 744.00000 | 23.99210 | 23.10158 | 0.90689 | 24.42288 |
Annual Sum or Average | 8760.00000 | 23.99788 | 38.05275 | 0.92210 | 26.70554 |
Minimum of Months | 672.00000 | 23.99162 | 23.10158 | 0.65485 | 20.34697 |
Maximum of Months | 744.00000 | 24.00214 | 50.39366 | 1.13994 | 34.98618 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.03270 | 26.14983 | -0.2125 | 6.25468 |
February | 672.00000 | 21.67411 | 40.99430 | -0.2104 | 6.17025 |
March | 744.00000 | 22.13779 | 30.62727 | -0.1580 | 6.12562 |
April | 720.00000 | 23.38050 | 19.19255 | 0.07619 | 5.55111 |
May | 744.00000 | 23.71613 | 17.86509 | -0.7664 | 17.73584 |
June | 720.00000 | 23.93369 | 26.24132 | -0.6033 | 12.82689 |
July | 744.00000 | 23.93528 | 45.07593 | -0.4796 | 10.12928 |
August | 744.00000 | 23.89362 | 47.56453 | -0.4864 | 10.21275 |
September | 720.00000 | 23.81436 | 46.89578 | -0.5273 | 11.12766 |
October | 744.00000 | 23.00220 | 29.13727 | 0.05175 | 6.12985 |
November | 720.00000 | 22.21451 | 30.74703 | -0.1365 | 6.09017 |
December | 744.00000 | 21.61625 | 19.20077 | -0.3587 | 8.04186 |
Annual Sum or Average | 8760.00000 | 22.95211 | 31.57365 | -0.3187 | 8.88813 |
Minimum of Months | 672.00000 | 21.61625 | 17.86509 | -0.7664 | 5.55111 |
Maximum of Months | 744.00000 | 23.93528 | 47.56453 | 0.07619 | 17.73584 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.96541 | 59.29432 | 0.41862 | 8.75529 |
February | 672.00000 | 23.94134 | 73.77788 | 0.49681 | 10.29017 |
March | 744.00000 | 23.95583 | 64.20581 | 0.44545 | 9.22993 |
April | 720.00000 | 23.99918 | 46.33034 | 0.36057 | 7.75848 |
May | 744.00000 | 23.99923 | 43.18056 | -0.5719 | 11.86572 |
June | 720.00000 | 23.99926 | 42.37532 | -0.5551 | 11.47009 |
July | 744.00000 | 23.99922 | 49.19294 | -0.5119 | 10.51103 |
August | 744.00000 | 23.99921 | 50.20448 | -0.5076 | 10.40515 |
September | 720.00000 | 23.99920 | 50.60432 | -0.5087 | 10.44555 |
October | 744.00000 | 23.99585 | 51.30161 | 0.39003 | 8.21343 |
November | 720.00000 | 23.98174 | 58.64428 | 0.41980 | 8.75895 |
December | 744.00000 | 23.89722 | 68.63696 | 0.45313 | 9.40923 |
Annual Sum or Average | 8760.00000 | 23.97784 | 54.71487 | 0.02465 | 9.75671 |
Minimum of Months | 672.00000 | 23.89722 | 42.37532 | -0.5719 | 7.75848 |
Maximum of Months | 744.00000 | 23.99926 | 73.77788 | 0.49681 | 11.86572 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.59482 | 57.63842 | 0.32599 | 7.53257 |
February | 672.00000 | 23.52467 | 71.08257 | 0.37916 | 8.27096 |
March | 744.00000 | 23.68825 | 58.52933 | 0.35953 | 7.97284 |
April | 720.00000 | 23.98291 | 41.87529 | 0.38589 | 8.20198 |
May | 744.00000 | 23.99905 | 38.05620 | -0.5039 | 10.42167 |
June | 720.00000 | 23.99940 | 38.15700 | -0.4461 | 9.27330 |
July | 744.00000 | 23.99929 | 43.80725 | -0.4159 | 8.73073 |
August | 744.00000 | 23.99928 | 44.89168 | -0.4172 | 8.76649 |
September | 720.00000 | 23.99927 | 45.42082 | -0.4352 | 9.07907 |
October | 744.00000 | 23.90872 | 48.61098 | 0.38917 | 8.27114 |
November | 720.00000 | 23.71981 | 56.53989 | 0.35488 | 7.90617 |
December | 744.00000 | 23.16223 | 62.72703 | 0.22963 | 6.86417 |
Annual Sum or Average | 8760.00000 | 23.79899 | 50.49915 | 0.01476 | 8.44041 |
Minimum of Months | 672.00000 | 23.16223 | 38.05620 | -0.5039 | 6.86417 |
Maximum of Months | 744.00000 | 23.99940 | 71.08257 | 0.38917 | 10.42167 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.14203 | 24.36103 | 0.04103 | 5.39874 |
February | 672.00000 | 22.86474 | 38.08804 | 0.06030 | 5.37961 |
March | 744.00000 | 23.15840 | 28.71397 | 0.07561 | 5.57951 |
April | 720.00000 | 23.82349 | 18.54221 | 0.18368 | 5.88986 |
May | 744.00000 | 23.94950 | 17.44164 | -0.6823 | 14.90233 |
June | 720.00000 | 23.99533 | 25.97495 | -0.5831 | 12.23170 |
July | 744.00000 | 23.99545 | 44.73372 | -0.4569 | 9.60684 |
August | 744.00000 | 23.99183 | 47.09376 | -0.4475 | 9.33896 |
September | 720.00000 | 23.98194 | 46.23212 | -0.4636 | 9.65146 |
October | 744.00000 | 23.67498 | 27.93847 | 0.20902 | 6.42029 |
November | 720.00000 | 23.29026 | 28.81429 | 0.10949 | 5.80284 |
December | 744.00000 | 22.78621 | 17.81904 | -0.0897 | 5.60488 |
Annual Sum or Average | 8760.00000 | 23.55779 | 30.42335 | -0.1720 | 8.00083 |
Minimum of Months | 672.00000 | 22.78621 | 17.44164 | -0.6823 | 5.37961 |
Maximum of Months | 744.00000 | 23.99545 | 47.09376 | 0.20902 | 14.90233 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.644460E+10 | 0.194631E+10 | 483.03 | 0.631749E+10 | 0.127109E+09 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 24885.27 | 08-JAN-16:12 | 23560.64 | 07-JAN-16:12 | 4859.66 | 08-JAN-19:03 | 6647.68 | 08-JAN-16:12 | 0.00 |
February | 0.320313E+10 | 0.973554E+09 | 374.31 | 0.289115E+10 | 0.311974E+09 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-01:40 | 25332.34 | 17-FEB-16:12 | 23513.87 | 21-FEB-16:12 | 7852.46 | 20-FEB-09:02 | 6760.08 | 17-FEB-16:12 | 0.00 |
March | 0.567510E+10 | 0.173179E+10 | 498.29 | 0.545740E+10 | 0.217709E+09 | 0.00 | 1.00 | 02-MAR-16:12 | 0.00 | 01-MAR-02:20 | 24263.28 | 05-MAR-16:12 | 23487.48 | 07-MAR-16:12 | 6564.11 | 06-MAR-16:12 | 6608.42 | 20-MAR-15:12 | 0.00 |
April | 0.128645E+11 | 0.415290E+10 | 671.78 | 0.128178E+11 | 46679333.13 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-06:53 | 23931.47 | 15-APR-08:62 | 23486.16 | 07-APR-18:02 | 2504.06 | 16-APR-08:62 | 6956.59 | 14-APR-15:12 | 0.00 |
May | 0.152289E+11 | 0.509466E+10 | 717.56 | 0.152173E+11 | 11607915.05 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-06:52 | 23617.04 | 11-MAY-08:62 | 23462.96 | 13-MAY-08:62 | 571.01 | 11-MAY-08:12 | 7026.82 | 31-MAY-15:12 | 0.00 |
June | 0.196449E+11 | 0.707170E+10 | 707.04 | 0.195336E+11 | 0.111223E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:51 | 23026.63 | 11-JUN-08:61 | 23026.63 | 11-JUN-08:61 | 2460.49 | 30-JUN-08:62 | 7859.89 | 17-JUN-15:12 | 0.00 |
July | 0.202522E+11 | 0.702801E+10 | 728.84 | 0.183483E+11 | 0.190391E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-06:51 | 26254.98 | 27-JUL-08:62 | 22259.72 | 05-JUL-08:62 | 8684.17 | 27-JUL-08:62 | 7731.95 | 20-JUL-15:12 | 0.00 |
August | 0.199415E+11 | 0.689414E+10 | 725.78 | 0.179787E+11 | 0.196279E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 27074.48 | 04-AUG-08:62 | 22748.68 | 24-AUG-08:62 | 10271.71 | 04-AUG-08:62 | 7669.97 | 10-AUG-15:12 | 0.00 |
September | 0.176026E+11 | 0.585691E+10 | 698.87 | 0.156794E+11 | 0.192318E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 27678.11 | 03-SEP-08:62 | 23007.33 | 19-SEP-08:62 | 12108.79 | 03-SEP-08:62 | 7587.92 | 08-SEP-15:12 | 0.00 |
October | 0.111310E+11 | 0.355115E+10 | 644.02 | 0.106311E+11 | 0.499920E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 25557.71 | 03-OCT-08:61 | 23489.43 | 08-OCT-18:02 | 7590.04 | 03-OCT-08:02 | 7273.44 | 02-OCT-15:12 | 0.00 |
November | 0.663826E+10 | 0.201382E+10 | 504.90 | 0.615887E+10 | 0.479390E+09 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:53 | 27719.92 | 12-NOV-16:12 | 23523.29 | 15-NOV-16:12 | 12388.57 | 12-NOV-16:12 | 7282.62 | 12-NOV-16:12 | 0.00 |
December | 0.403498E+10 | 0.122277E+10 | 375.99 | 0.402510E+10 | 9880381.29 | 0.00 | 1.00 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 | 23395.47 | 13-DEC-16:12 | 23395.47 | 13-DEC-16:12 | 1254.84 | 13-DEC-09:02 | 6272.41 | 25-DEC-16:12 | 0.00 |
Annual Sum or Average | 0.142662E+12 | 0.475377E+11 | 7130.42 | 0.135056E+12 | 0.760538E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.320313E+10 | 0.973554E+09 | 374.31 | 0.289115E+10 | 9880381.29 | 0.00 | 1.00 | 0.00 | 23026.63 | 22259.72 | 571.01 | 6272.41 | 0.00 | ||||||
Maximum of Months | 0.202522E+11 | 0.707170E+10 | 728.84 | 0.195336E+11 | 0.196279E+10 | 0.00 | 1.00 | 0.00 | 27719.92 | 23560.64 | 12388.57 | 7859.89 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.253712E+10 | 0.777581E+09 | 310.36 | 0.246351E+10 | 73609893.58 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 26725.85 | 08-JAN-20:11 | 23795.44 | 07-JAN-22:51 | 10310.33 | 08-JAN-20:11 | 7063.53 | 08-JAN-20:11 | 0.00 |
February | 0.135402E+10 | 0.416196E+09 | 259.77 | 0.114467E+10 | 0.209358E+09 | 0.00 | 1.00 | 01-FEB-17:11 | 0.00 | 01-FEB-01:30 | 25651.86 | 17-FEB-20:01 | 23656.34 | 25-FEB-19:11 | 7976.92 | 17-FEB-20:01 | 6825.12 | 17-FEB-20:01 | 0.00 |
March | 0.296812E+10 | 0.916319E+09 | 346.11 | 0.280989E+10 | 0.158231E+09 | 0.00 | 1.00 | 01-MAR-20:41 | 0.00 | 01-MAR-02:70 | 24770.21 | 05-MAR-22:51 | 24342.49 | 16-MAR-21:51 | 5383.03 | 06-MAR-19:02 | 6614.93 | 05-MAR-22:51 | 0.00 |
April | 0.110335E+11 | 0.357927E+10 | 586.68 | 0.109895E+11 | 43979192.30 | 0.00 | 1.00 | 01-APR-08:51 | 0.00 | 01-APR-06:53 | 24485.56 | 16-APR-08:51 | 24407.98 | 15-APR-21:51 | 2974.76 | 16-APR-08:52 | 6906.94 | 14-APR-15:12 | 0.00 |
May | 0.144673E+11 | 0.484768E+10 | 639.16 | 0.144577E+11 | 9599574.30 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 23948.52 | 11-MAY-08:41 | 23948.52 | 11-MAY-08:41 | 741.91 | 11-MAY-08:53 | 6969.35 | 31-MAY-15:12 | 0.00 |
June | 0.194689E+11 | 0.701445E+10 | 666.62 | 0.193604E+11 | 0.108511E+09 | 0.00 | 1.00 | 01-JUN-07:21 | 0.00 | 01-JUN-05:13 | 24067.15 | 04-JUN-06:41 | 24067.15 | 04-JUN-06:41 | 2325.26 | 30-JUN-08:62 | 7794.72 | 17-JUN-15:12 | 0.00 |
July | 0.200139E+11 | 0.694226E+10 | 708.82 | 0.181339E+11 | 0.187999E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-05:15 | 28039.10 | 27-JUL-08:11 | 23665.45 | 06-JUL-07:11 | 11747.74 | 27-JUL-08:13 | 7668.81 | 20-JUL-15:12 | 0.00 |
August | 0.188009E+11 | 0.651108E+10 | 682.73 | 0.169280E+11 | 0.187293E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 28542.74 | 04-AUG-08:51 | 23550.01 | 23-AUG-08:11 | 12037.97 | 04-AUG-08:54 | 7609.19 | 10-AUG-15:12 | 0.00 |
September | 0.156917E+11 | 0.523774E+10 | 626.57 | 0.139398E+11 | 0.175198E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-05:12 | 29536.24 | 04-SEP-08:51 | 23747.71 | 28-SEP-08:51 | 14539.17 | 03-SEP-08:52 | 7684.69 | 04-SEP-08:51 | 0.00 |
October | 0.772149E+10 | 0.250012E+10 | 497.29 | 0.728606E+10 | 0.435423E+09 | 0.00 | 1.00 | 01-OCT-07:41 | 0.00 | 01-OCT-05:13 | 27299.99 | 03-OCT-08:61 | 24500.76 | 21-OCT-16:21 | 10940.31 | 03-OCT-08:03 | 7414.69 | 03-OCT-08:61 | 0.00 |
November | 0.310053E+10 | 0.951311E+09 | 334.78 | 0.278855E+10 | 0.311982E+09 | 0.00 | 1.00 | 01-NOV-08:51 | 0.00 | 01-NOV-05:13 | 28252.86 | 11-NOV-22:51 | 23478.75 | 20-NOV-22:01 | 13709.74 | 12-NOV-22:52 | 7370.20 | 11-NOV-22:51 | 0.00 |
December | 0.122115E+10 | 0.375041E+09 | 214.26 | 0.121720E+10 | 3953584.31 | 0.00 | 1.00 | 02-DEC-22:11 | 0.00 | 01-DEC-00:10 | 23841.73 | 13-DEC-17:11 | 23841.73 | 13-DEC-17:11 | 532.36 | 13-DEC-19:02 | 6378.82 | 13-DEC-17:11 | 0.00 |
Annual Sum or Average | 0.118379E+12 | 0.400691E+11 | 5873.15 | 0.111519E+12 | 0.685955E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.122115E+10 | 0.375041E+09 | 214.26 | 0.114467E+10 | 3953584.31 | 0.00 | 1.00 | 0.00 | 23841.73 | 23478.75 | 532.36 | 6378.82 | 0.00 | ||||||
Maximum of Months | 0.200139E+11 | 0.701445E+10 | 708.82 | 0.193604E+11 | 0.187999E+10 | 0.00 | 1.00 | 0.00 | 29536.24 | 24500.76 | 14539.17 | 7794.72 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.503742E+11 | 0.151941E+11 | 471.04 | 0.502977E+11 | 76485371.84 | 0.00 | 0.53 | 14-JAN-13:50 | 0.00 | 01-JAN-00:05 | 73204.80 | 14-JAN-13:40 | 73204.80 | 14-JAN-13:40 | 3351.64 | 09-JAN-10:00 | 22399.36 | 14-JAN-13:50 | 0.00 |
February | 0.185725E+11 | 0.568014E+10 | 314.96 | 0.183764E+11 | 0.196080E+09 | 0.00 | 0.36 | 01-FEB-14:00 | 0.00 | 01-FEB-00:10 | 49153.74 | 23-FEB-14:00 | 49153.74 | 23-FEB-14:00 | 3584.55 | 18-FEB-10:35 | 14648.01 | 23-FEB-14:00 | 0.00 |
March | 0.240858E+11 | 0.747876E+10 | 405.86 | 0.240834E+11 | 2425973.88 | 0.00 | 0.41 | 18-MAR-14:50 | 0.00 | 01-MAR-00:10 | 56548.72 | 18-MAR-14:40 | 56548.72 | 18-MAR-14:40 | 173.65 | 05-MAR-23:00 | 17672.59 | 18-MAR-14:50 | 0.00 |
April | 0.554583E+11 | 0.183821E+11 | 608.46 | 0.554583E+11 | 0.00 | 0.00 | 0.52 | 14-APR-14:20 | 0.00 | 01-APR-00:10 | 66014.45 | 14-APR-14:10 | 66014.45 | 14-APR-14:10 | 0.00 | 16-APR-14:40 | 23827.98 | 14-APR-14:20 | 0.00 |
May | 0.587524E+11 | 0.203040E+11 | 693.03 | 0.587524E+11 | 0.00 | 0.00 | 0.45 | 04-MAY-14:10 | 0.00 | 01-MAY-01:30 | 54720.58 | 04-MAY-14:10 | 54720.58 | 04-MAY-14:10 | 0.00 | 13-MAY-14:40 | 20410.24 | 04-MAY-14:10 | 0.00 |
June | 0.785586E+11 | 0.291932E+11 | 720.00 | 0.785556E+11 | 3014985.37 | 0.00 | 0.53 | 28-JUN-15:00 | 0.01 | 11-JUN-05:00 | 64563.93 | 28-JUN-15:00 | 64563.93 | 28-JUN-15:00 | 501.67 | 17-JUN-19:50 | 27492.56 | 28-JUN-15:00 | 0.00 |
July | 0.824805E+11 | 0.293153E+11 | 739.56 | 0.791731E+11 | 0.330744E+10 | 0.00 | 0.48 | 19-JUL-14:10 | 0.00 | 02-JUL-05:00 | 63465.01 | 19-JUL-14:10 | 62311.11 | 19-JUL-14:10 | 7134.85 | 13-JUL-21:00 | 25278.78 | 19-JUL-14:10 | 0.00 |
August | 0.854463E+11 | 0.302394E+11 | 741.94 | 0.822653E+11 | 0.318099E+10 | 0.00 | 0.63 | 25-AUG-14:10 | 0.00 | 06-AUG-04:10 | 77709.89 | 27-AUG-14:10 | 77709.89 | 27-AUG-14:10 | 5899.98 | 09-AUG-18:03 | 31466.36 | 25-AUG-14:10 | 0.00 |
September | 0.826297E+11 | 0.280296E+11 | 716.83 | 0.790808E+11 | 0.354893E+10 | 0.00 | 0.64 | 28-SEP-14:10 | 0.00 | 22-SEP-02:00 | 82933.21 | 28-SEP-14:10 | 82933.21 | 28-SEP-14:10 | 7937.83 | 04-SEP-08:52 | 31190.07 | 28-SEP-14:10 | 0.00 |
October | 0.636469E+11 | 0.204608E+11 | 597.92 | 0.630640E+11 | 0.582828E+09 | 0.00 | 0.60 | 18-OCT-14:10 | 0.00 | 08-OCT-01:10 | 78998.03 | 10-OCT-14:10 | 78998.03 | 10-OCT-14:10 | 5560.35 | 03-OCT-09:00 | 28241.37 | 10-OCT-14:10 | 0.00 |
November | 0.439390E+11 | 0.133438E+11 | 478.16 | 0.433842E+11 | 0.554766E+09 | 0.00 | 0.55 | 20-NOV-14:20 | 0.00 | 02-NOV-01:10 | 75670.69 | 20-NOV-13:40 | 75670.69 | 20-NOV-13:40 | 7720.17 | 14-NOV-11:40 | 23312.64 | 01-NOV-15:00 | 0.00 |
December | 0.356331E+11 | 0.107548E+11 | 404.07 | 0.356329E+11 | 253766.38 | 0.00 | 0.53 | 25-DEC-13:30 | 0.00 | 01-DEC-00:10 | 73033.40 | 25-DEC-13:30 | 73033.40 | 25-DEC-13:30 | 81.05 | 13-DEC-10:20 | 21830.13 | 25-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.679577E+12 | 0.228376E+12 | 6891.83 | 0.668124E+12 | 0.114532E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.185725E+11 | 0.568014E+10 | 314.96 | 0.183764E+11 | 0.00 | 0.00 | 0.36 | 0.00 | 49153.74 | 49153.74 | 0.00 | 14648.01 | 0.00 | ||||||
Maximum of Months | 0.854463E+11 | 0.302394E+11 | 741.94 | 0.822653E+11 | 0.354893E+10 | 0.00 | 0.64 | 0.01 | 82933.21 | 82933.21 | 7937.83 | 31466.36 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.208394E+11 | 0.631396E+10 | 357.61 | 0.200540E+11 | 0.785434E+09 | 0.00 | 1.00 | 02-JAN-20:02 | 0.00 | 01-JAN-00:05 | 171958.79 | 08-JAN-20:11 | 152788.60 | 07-JAN-22:51 | 66495.76 | 08-JAN-20:14 | 45470.02 | 08-JAN-20:11 | 0.00 |
February | 0.184471E+11 | 0.560028E+10 | 307.81 | 0.152926E+11 | 0.315455E+10 | 0.00 | 1.00 | 01-FEB-17:11 | 0.00 | 01-FEB-03:20 | 165307.64 | 18-FEB-19:11 | 147280.10 | 09-FEB-22:51 | 54991.06 | 12-FEB-09:02 | 43988.50 | 18-FEB-19:11 | 0.00 |
March | 0.290389E+11 | 0.880372E+10 | 389.52 | 0.273121E+11 | 0.172684E+10 | 0.00 | 1.00 | 01-MAR-20:41 | 0.00 | 01-MAR-04:00 | 159515.77 | 06-MAR-19:02 | 154868.89 | 17-MAR-21:51 | 37025.05 | 06-MAR-19:02 | 42604.43 | 06-MAR-19:02 | 0.00 |
April | 0.768209E+11 | 0.243464E+11 | 576.63 | 0.765190E+11 | 0.301848E+09 | 0.00 | 1.00 | 01-APR-08:51 | 0.00 | 01-APR-06:53 | 155961.61 | 15-APR-21:51 | 154896.40 | 15-APR-21:51 | 13488.42 | 15-APR-22:03 | 44836.26 | 14-APR-15:12 | 0.00 |
May | 0.102572E+12 | 0.334739E+11 | 627.21 | 0.102494E+12 | 78197370.23 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 151249.94 | 11-MAY-08:41 | 151249.94 | 11-MAY-08:41 | 3038.40 | 11-MAY-02:30 | 45185.81 | 31-MAY-15:12 | 0.00 |
June | 0.137787E+12 | 0.483096E+11 | 656.51 | 0.137079E+12 | 0.707413E+09 | 0.00 | 1.00 | 01-JUN-07:21 | 0.00 | 01-JUN-05:13 | 154282.11 | 04-JUN-06:41 | 152275.63 | 04-JUN-06:41 | 15350.51 | 17-JUN-18:08 | 51007.17 | 17-JUN-15:12 | 0.00 |
July | 0.153649E+12 | 0.515261E+11 | 695.68 | 0.135776E+12 | 0.178731E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-05:15 | 181143.41 | 15-JUL-06:41 | 151120.65 | 06-JUL-07:11 | 78691.30 | 15-JUL-06:44 | 50385.05 | 18-JUL-15:12 | 0.00 |
August | 0.142604E+12 | 0.475988E+11 | 670.08 | 0.124851E+12 | 0.177531E+11 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 183254.23 | 04-AUG-08:51 | 150267.40 | 23-AUG-08:11 | 79281.12 | 04-AUG-08:54 | 49985.31 | 10-AUG-15:12 | 0.00 |
September | 0.123744E+12 | 0.398545E+11 | 615.21 | 0.106882E+12 | 0.168622E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-05:12 | 189715.01 | 04-SEP-08:51 | 151866.06 | 16-SEP-08:51 | 96713.75 | 03-SEP-08:52 | 49439.53 | 04-SEP-08:51 | 0.00 |
October | 0.618568E+11 | 0.194234E+11 | 519.07 | 0.578418E+11 | 0.401492E+10 | 0.00 | 1.00 | 01-OCT-07:41 | 0.00 | 01-OCT-05:13 | 174940.43 | 03-OCT-08:61 | 154530.86 | 23-OCT-16:41 | 68358.81 | 03-OCT-08:05 | 47609.73 | 03-OCT-08:61 | 0.00 |
November | 0.272093E+11 | 0.819585E+10 | 359.89 | 0.238425E+11 | 0.336689E+10 | 0.00 | 1.00 | 01-NOV-08:51 | 0.00 | 01-NOV-05:13 | 182575.02 | 11-NOV-22:51 | 150659.33 | 03-NOV-19:11 | 85167.84 | 12-NOV-22:53 | 47603.47 | 11-NOV-22:51 | 0.00 |
December | 0.117130E+11 | 0.356185E+10 | 253.20 | 0.116363E+11 | 76712505.32 | 0.00 | 1.00 | 01-DEC-19:12 | 0.00 | 01-DEC-01:30 | 147412.40 | 13-DEC-17:11 | 146708.16 | 03-DEC-19:11 | 29128.10 | 13-DEC-09:02 | 40192.43 | 25-DEC-16:12 | 0.00 |
Annual Sum or Average | 0.906281E+12 | 0.297008E+12 | 6028.40 | 0.839580E+12 | 0.667012E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.117130E+11 | 0.356185E+10 | 253.20 | 0.116363E+11 | 76712505.32 | 0.00 | 1.00 | 0.00 | 147412.40 | 146708.16 | 3038.40 | 40192.43 | 0.00 | ||||||
Maximum of Months | 0.153649E+12 | 0.515261E+11 | 695.68 | 0.137079E+12 | 0.178731E+11 | 0.00 | 1.00 | 0.00 | 189715.01 | 154896.40 | 96713.75 | 51007.17 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.601035E+10 | 0.181397E+10 | 489.51 | 0.587540E+10 | 0.134956E+09 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 21342.17 | 09-JAN-09:02 | 19841.92 | 07-JAN-16:12 | 5054.11 | 09-JAN-09:02 | 5692.79 | 09-JAN-09:02 | 0.00 |
February | 0.338627E+10 | 0.102470E+10 | 385.75 | 0.303832E+10 | 0.347949E+09 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-01:20 | 21876.07 | 18-FEB-09:02 | 19772.45 | 27-FEB-16:12 | 6665.75 | 18-FEB-09:02 | 5818.24 | 18-FEB-09:02 | 0.00 |
March | 0.568296E+10 | 0.172848E+10 | 512.29 | 0.544634E+10 | 0.236612E+09 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-01:30 | 20796.83 | 02-MAR-09:02 | 19763.52 | 07-MAR-16:12 | 5134.95 | 06-MAR-16:12 | 5560.29 | 20-MAR-15:12 | 0.00 |
April | 0.128363E+11 | 0.408043E+10 | 699.79 | 0.127822E+11 | 54161855.23 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-06:53 | 20290.60 | 16-APR-08:62 | 19814.62 | 07-APR-18:02 | 1561.60 | 16-APR-08:62 | 5863.41 | 14-APR-15:12 | 0.00 |
May | 0.154770E+11 | 0.507442E+10 | 736.36 | 0.154647E+11 | 12308278.54 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-06:52 | 19766.38 | 11-MAY-08:62 | 19766.38 | 11-MAY-08:62 | 667.12 | 11-MAY-08:07 | 5914.69 | 31-MAY-15:12 | 0.00 |
June | 0.199309E+11 | 0.701627E+10 | 715.72 | 0.198198E+11 | 0.111150E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:51 | 19365.66 | 11-JUN-08:61 | 19365.66 | 11-JUN-08:61 | 2116.98 | 30-JUN-08:05 | 6633.17 | 17-JUN-15:12 | 0.00 |
July | 0.211523E+11 | 0.720173E+10 | 737.57 | 0.192008E+11 | 0.195144E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-06:51 | 21211.18 | 09-JUL-08:62 | 18824.06 | 06-JUL-08:62 | 5149.41 | 09-JUL-08:62 | 6532.94 | 20-JUL-15:12 | 0.00 |
August | 0.206007E+11 | 0.698576E+10 | 734.88 | 0.185847E+11 | 0.201597E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 22784.71 | 04-AUG-08:62 | 19131.95 | 24-AUG-08:62 | 8564.74 | 04-AUG-08:62 | 6483.90 | 10-AUG-15:12 | 0.00 |
September | 0.178428E+11 | 0.584085E+10 | 708.59 | 0.158783E+11 | 0.196455E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 23330.55 | 03-SEP-08:62 | 19388.33 | 28-SEP-08:62 | 10232.39 | 03-SEP-08:62 | 6412.21 | 08-SEP-15:12 | 0.00 |
October | 0.112265E+11 | 0.353774E+10 | 659.80 | 0.107098E+11 | 0.516733E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 21466.14 | 22-OCT-08:62 | 19818.35 | 23-OCT-18:02 | 5200.89 | 22-OCT-08:62 | 6142.24 | 03-OCT-15:12 | 0.00 |
November | 0.608420E+10 | 0.184165E+10 | 515.67 | 0.563331E+10 | 0.450890E+09 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-06:53 | 23617.57 | 12-NOV-16:12 | 19846.48 | 18-NOV-16:12 | 11409.53 | 12-NOV-16:12 | 6188.86 | 12-NOV-16:12 | 0.00 |
December | 0.387775E+10 | 0.117235E+10 | 386.76 | 0.386530E+10 | 12443021.61 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 21280.45 | 13-DEC-09:02 | 19702.27 | 13-DEC-16:12 | 5188.88 | 13-DEC-09:02 | 5677.92 | 13-DEC-09:02 | 0.00 |
Annual Sum or Average | 0.144108E+12 | 0.473183E+11 | 7282.69 | 0.136299E+12 | 0.780916E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.338627E+10 | 0.102470E+10 | 385.75 | 0.303832E+10 | 12308278.54 | 0.00 | 1.00 | 0.00 | 19365.66 | 18824.06 | 667.12 | 5560.29 | 0.00 | ||||||
Maximum of Months | 0.211523E+11 | 0.720173E+10 | 737.57 | 0.198198E+11 | 0.201597E+10 | 0.00 | 1.00 | 0.00 | 23617.57 | 19846.48 | 11409.53 | 6633.17 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.233638E+10 | 0.711722E+09 | 345.38 | 0.224579E+10 | 90586780.67 | 0.00 | 1.00 | 03-JAN-09:02 | 0.00 | 01-JAN-00:05 | 22405.62 | 08-JAN-20:11 | 19685.81 | 27-JAN-09:51 | 8986.17 | 08-JAN-20:11 | 5921.47 | 08-JAN-20:11 | 0.00 |
February | 0.164032E+10 | 0.498271E+09 | 280.27 | 0.137013E+10 | 0.270193E+09 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-01:10 | 21659.70 | 18-FEB-09:02 | 19220.15 | 25-FEB-19:11 | 6858.81 | 18-FEB-09:02 | 5757.09 | 18-FEB-09:02 | 0.00 |
March | 0.325300E+10 | 0.994835E+09 | 383.20 | 0.307177E+10 | 0.181229E+09 | 0.00 | 1.00 | 01-MAR-20:41 | 0.00 | 01-MAR-00:40 | 21012.46 | 18-MAR-08:51 | 20480.97 | 11-MAR-09:51 | 3742.02 | 11-MAR-19:02 | 5605.48 | 18-MAR-08:51 | 0.00 |
April | 0.107238E+11 | 0.343070E+10 | 608.15 | 0.106724E+11 | 51325789.56 | 0.00 | 1.00 | 01-APR-08:51 | 0.00 | 01-APR-06:53 | 21146.18 | 15-APR-08:22 | 21146.18 | 15-APR-08:22 | 3145.34 | 16-APR-08:54 | 5790.22 | 14-APR-15:12 | 0.00 |
May | 0.142401E+11 | 0.469220E+10 | 656.44 | 0.142263E+11 | 13793775.25 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 20968.30 | 13-MAY-08:32 | 20968.30 | 13-MAY-08:32 | 1720.83 | 11-MAY-08:46 | 5832.87 | 19-MAY-15:12 | 0.00 |
June | 0.196012E+11 | 0.691152E+10 | 679.16 | 0.194910E+11 | 0.110216E+09 | 0.00 | 1.00 | 01-JUN-07:02 | 0.00 | 01-JUN-05:13 | 20761.80 | 01-JUN-07:02 | 20761.80 | 01-JUN-07:02 | 2024.36 | 30-JUN-08:15 | 6539.06 | 17-JUN-15:12 | 0.00 |
July | 0.208338E+11 | 0.708954E+10 | 717.80 | 0.189031E+11 | 0.193070E+10 | 0.00 | 1.00 | 01-JUL-07:42 | 0.00 | 01-JUL-05:15 | 23931.40 | 27-JUL-07:52 | 20008.18 | 06-JUL-07:11 | 8675.07 | 15-JUL-06:45 | 6440.85 | 20-JUL-15:12 | 0.00 |
August | 0.193574E+11 | 0.657612E+10 | 693.61 | 0.174264E+11 | 0.193094E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 23975.65 | 04-AUG-08:51 | 20349.18 | 24-AUG-08:62 | 9850.69 | 04-AUG-08:54 | 6394.70 | 10-AUG-15:12 | 0.00 |
September | 0.157655E+11 | 0.518002E+10 | 637.32 | 0.139664E+11 | 0.179913E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-05:12 | 25229.24 | 04-SEP-08:32 | 20385.23 | 28-SEP-08:32 | 12334.50 | 03-SEP-08:52 | 6467.57 | 04-SEP-08:32 | 0.00 |
October | 0.778246E+10 | 0.248447E+10 | 523.88 | 0.732358E+10 | 0.458883E+09 | 0.00 | 1.00 | 01-OCT-07:41 | 0.00 | 01-OCT-05:13 | 23009.05 | 04-OCT-08:12 | 20474.09 | 09-OCT-08:51 | 8245.46 | 03-OCT-08:05 | 6220.96 | 03-OCT-08:61 | 0.00 |
November | 0.268789E+10 | 0.818643E+09 | 345.94 | 0.239890E+10 | 0.288991E+09 | 0.00 | 1.00 | 01-NOV-08:51 | 0.00 | 01-NOV-05:13 | 23626.24 | 11-NOV-22:51 | 20298.18 | 21-NOV-09:51 | 11676.72 | 12-NOV-22:52 | 6167.18 | 11-NOV-22:51 | 0.00 |
December | 0.115687E+10 | 0.352363E+09 | 212.08 | 0.114941E+10 | 7465005.41 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 19658.09 | 25-DEC-09:51 | 19658.09 | 25-DEC-09:51 | 4445.38 | 13-DEC-09:02 | 5260.02 | 25-DEC-09:51 | 0.00 |
Annual Sum or Average | 0.119379E+12 | 0.397404E+11 | 6083.21 | 0.112245E+12 | 0.713346E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.115687E+10 | 0.352363E+09 | 212.08 | 0.114941E+10 | 7465005.41 | 0.00 | 1.00 | 0.00 | 19658.09 | 19220.15 | 1720.83 | 5260.02 | 0.00 | ||||||
Maximum of Months | 0.208338E+11 | 0.708954E+10 | 717.80 | 0.194910E+11 | 0.193094E+10 | 0.00 | 1.00 | 0.00 | 25229.24 | 21146.18 | 12334.50 | 6539.06 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.145673E+10 | 0.440633E+09 | 412.91 | 0.142982E+10 | 26911500.78 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 6873.57 | 08-JAN-16:12 | 6474.40 | 07-JAN-16:12 | 1263.51 | 08-JAN-16:12 | 1835.44 | 08-JAN-16:12 | 0.00 |
February | 0.642273E+09 | 0.195123E+09 | 279.76 | 0.585703E+09 | 56569654.76 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-00:20 | 6736.46 | 18-FEB-16:12 | 6470.75 | 21-FEB-16:12 | 1508.34 | 17-FEB-16:12 | 1801.18 | 18-FEB-16:12 | 0.00 |
March | 0.131290E+10 | 0.401375E+09 | 425.85 | 0.126659E+10 | 46310642.14 | 0.00 | 1.00 | 02-MAR-16:12 | 0.00 | 01-MAR-00:10 | 6688.46 | 05-MAR-16:12 | 6460.91 | 07-MAR-16:12 | 1131.60 | 06-MAR-16:12 | 1815.79 | 20-MAR-15:12 | 0.00 |
April | 0.334193E+10 | 0.108520E+10 | 649.00 | 0.333110E+10 | 10829859.45 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-04:00 | 6571.38 | 15-APR-08:62 | 6457.37 | 07-APR-18:02 | 501.66 | 16-APR-08:62 | 1909.53 | 14-APR-15:12 | 0.00 |
May | 0.406109E+10 | 0.136719E+10 | 713.32 | 0.405838E+10 | 2707914.81 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-03:50 | 6349.19 | 11-MAY-08:62 | 6308.74 | 10-MAY-08:62 | 137.28 | 11-MAY-08:12 | 1929.39 | 31-MAY-15:12 | 0.00 |
June | 0.540403E+10 | 0.195555E+10 | 707.28 | 0.537352E+10 | 30508766.48 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:51 | 6340.14 | 04-JUN-08:62 | 6328.53 | 11-JUN-08:61 | 724.16 | 30-JUN-08:62 | 2155.04 | 17-JUN-15:12 | 0.00 |
July | 0.552327E+10 | 0.192735E+10 | 729.41 | 0.503182E+10 | 0.491446E+09 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-06:51 | 7277.33 | 27-JUL-08:62 | 6113.61 | 05-JUL-08:62 | 2561.98 | 27-JUL-08:62 | 2121.75 | 20-JUL-15:12 | 0.00 |
August | 0.540189E+10 | 0.187880E+10 | 725.36 | 0.489646E+10 | 0.505432E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 7559.39 | 04-AUG-08:62 | 6245.72 | 24-AUG-08:62 | 3149.49 | 04-AUG-08:62 | 2104.18 | 10-AUG-15:12 | 0.00 |
September | 0.465372E+10 | 0.155806E+10 | 695.52 | 0.416425E+10 | 0.489463E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 7760.47 | 03-SEP-08:62 | 6320.62 | 19-SEP-08:62 | 3741.87 | 03-SEP-08:62 | 2082.48 | 08-SEP-15:12 | 0.00 |
October | 0.273751E+10 | 0.880062E+09 | 602.74 | 0.261512E+10 | 0.122387E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 7108.46 | 03-OCT-08:61 | 6461.27 | 11-OCT-15:12 | 2242.03 | 03-OCT-08:61 | 1995.19 | 02-OCT-15:12 | 0.00 |
November | 0.148386E+10 | 0.451174E+09 | 435.25 | 0.137876E+10 | 0.105105E+09 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:53 | 7786.60 | 12-NOV-16:12 | 6468.71 | 15-NOV-16:12 | 3854.08 | 12-NOV-16:12 | 2034.43 | 12-NOV-16:12 | 0.00 |
December | 0.871412E+09 | 0.264341E+09 | 304.42 | 0.869313E+09 | 2098940.20 | 0.00 | 1.00 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 | 6441.42 | 13-DEC-16:12 | 6441.42 | 13-DEC-16:12 | 283.39 | 13-DEC-09:04 | 1724.62 | 25-DEC-16:12 | 0.00 |
Annual Sum or Average | 0.368906E+11 | 0.124049E+11 | 6680.82 | 0.350008E+11 | 0.188977E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.642273E+09 | 0.195123E+09 | 279.76 | 0.585703E+09 | 2098940.20 | 0.00 | 1.00 | 0.00 | 6340.14 | 6113.61 | 137.28 | 1724.62 | 0.00 | ||||||
Maximum of Months | 0.552327E+10 | 0.195555E+10 | 729.41 | 0.537352E+10 | 0.505432E+09 | 0.00 | 1.00 | 0.00 | 7786.60 | 6474.40 | 3854.08 | 2155.04 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.527958E+09 | 0.161992E+09 | 235.23 | 0.514735E+09 | 13223205.25 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 7314.91 | 08-JAN-20:11 | 6481.52 | 07-JAN-22:51 | 2967.78 | 08-JAN-20:11 | 1934.53 | 08-JAN-20:11 | 0.00 |
February | 0.214642E+09 | 65930724.10 | 161.86 | 0.183799E+09 | 30842493.64 | 0.00 | 1.00 | 01-FEB-17:11 | 0.00 | 01-FEB-00:20 | 6925.74 | 16-FEB-20:11 | 6510.70 | 25-FEB-19:11 | 1818.21 | 15-FEB-21:11 | 1846.45 | 16-FEB-20:11 | 0.00 |
March | 0.662853E+09 | 0.205143E+09 | 281.44 | 0.631428E+09 | 31424440.18 | 0.00 | 1.00 | 01-MAR-20:41 | 0.00 | 01-MAR-00:10 | 6783.81 | 17-MAR-21:51 | 6651.59 | 16-MAR-21:51 | 1505.02 | 05-MAR-09:51 | 1812.01 | 17-MAR-21:51 | 0.00 |
April | 0.290887E+10 | 0.949322E+09 | 574.72 | 0.289832E+10 | 10552776.60 | 0.00 | 1.00 | 01-APR-08:51 | 0.00 | 01-APR-04:50 | 6693.76 | 15-APR-21:51 | 6693.76 | 15-APR-21:51 | 671.82 | 16-APR-08:51 | 1894.08 | 14-APR-15:12 | 0.00 |
May | 0.389647E+10 | 0.131340E+10 | 639.42 | 0.389415E+10 | 2324179.50 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-03:50 | 6582.17 | 11-MAY-08:41 | 6582.17 | 11-MAY-08:41 | 187.47 | 11-MAY-08:53 | 1912.04 | 31-MAY-15:12 | 0.00 |
June | 0.537589E+10 | 0.194591E+10 | 667.13 | 0.534562E+10 | 30265382.42 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-05:13 | 6583.53 | 04-JUN-06:41 | 6539.35 | 04-JUN-06:41 | 685.82 | 30-JUN-08:62 | 2135.21 | 17-JUN-15:12 | 0.00 |
July | 0.547016E+10 | 0.190793E+10 | 709.39 | 0.498375E+10 | 0.486417E+09 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-05:15 | 7716.17 | 27-JUL-08:11 | 6465.62 | 06-JUL-07:11 | 3275.90 | 27-JUL-08:13 | 2102.31 | 20-JUL-15:12 | 0.00 |
August | 0.512718E+10 | 0.178643E+10 | 683.59 | 0.464325E+10 | 0.483929E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 7871.93 | 04-AUG-08:51 | 6431.06 | 23-AUG-08:11 | 3392.78 | 04-AUG-08:53 | 2085.18 | 10-AUG-15:12 | 0.00 |
September | 0.419427E+10 | 0.140890E+10 | 627.10 | 0.374653E+10 | 0.447733E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-05:12 | 8137.77 | 04-SEP-08:51 | 6514.24 | 28-SEP-08:51 | 4235.39 | 03-SEP-08:52 | 2114.59 | 04-SEP-08:51 | 0.00 |
October | 0.192452E+10 | 0.628682E+09 | 466.19 | 0.181766E+10 | 0.106861E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-05:13 | 7510.88 | 03-OCT-08:61 | 6726.24 | 21-OCT-16:21 | 3065.78 | 03-OCT-08:02 | 2038.78 | 03-OCT-08:61 | 0.00 |
November | 0.651575E+09 | 0.200516E+09 | 270.50 | 0.586005E+09 | 65570794.60 | 0.00 | 1.00 | 01-NOV-08:51 | 0.00 | 01-NOV-05:13 | 7764.49 | 11-NOV-22:51 | 6411.73 | 20-NOV-22:01 | 3969.91 | 12-NOV-22:51 | 2025.06 | 11-NOV-22:51 | 0.00 |
December | 0.223796E+09 | 68807824.50 | 144.32 | 0.223110E+09 | 685993.98 | 0.00 | 1.00 | 13-DEC-17:11 | 0.00 | 01-DEC-00:10 | 6557.48 | 13-DEC-17:11 | 6557.48 | 13-DEC-17:11 | 402.77 | 13-DEC-09:04 | 1754.39 | 13-DEC-17:11 | 0.00 |
Annual Sum or Average | 0.311782E+11 | 0.106430E+11 | 5460.88 | 0.294684E+11 | 0.170983E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.214642E+09 | 65930724.10 | 144.32 | 0.183799E+09 | 685993.98 | 0.00 | 1.00 | 0.00 | 6557.48 | 6411.73 | 187.47 | 1754.39 | 0.00 | ||||||
Maximum of Months | 0.547016E+10 | 0.194591E+10 | 709.39 | 0.534562E+10 | 0.486417E+09 | 0.00 | 1.00 | 0.00 | 8137.77 | 6726.24 | 4235.39 | 2135.21 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.131067E+11 | 0.388657E+10 | 492.83 | 0.128993E+11 | 0.207421E+09 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 32873.89 | 09-JAN-09:02 | 30105.72 | 07-JAN-16:12 | 9361.86 | 09-JAN-09:02 | 8751.77 | 09-JAN-09:02 | 0.00 |
February | 0.628162E+10 | 0.189075E+10 | 357.65 | 0.579499E+10 | 0.486633E+09 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-01:30 | 33389.58 | 18-FEB-09:02 | 30019.77 | 21-FEB-16:12 | 11961.66 | 18-FEB-09:02 | 8870.13 | 18-FEB-09:02 | 0.00 |
March | 0.850884E+10 | 0.258764E+10 | 484.97 | 0.819754E+10 | 0.311297E+09 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-01:30 | 31686.30 | 05-MAR-09:02 | 29957.51 | 10-MAR-19:02 | 7720.42 | 06-MAR-16:12 | 8465.86 | 05-MAR-09:02 | 0.00 |
April | 0.171067E+11 | 0.552279E+10 | 663.55 | 0.170358E+11 | 70942011.69 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-04:50 | 30393.67 | 15-APR-08:62 | 30101.59 | 07-APR-18:02 | 2409.42 | 16-APR-08:62 | 8925.43 | 14-APR-15:12 | 0.00 |
May | 0.190701E+11 | 0.639078E+10 | 714.42 | 0.190508E+11 | 19339967.51 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-06:52 | 29985.79 | 13-MAY-08:62 | 29985.79 | 13-MAY-08:62 | 462.66 | 11-MAY-08:12 | 9020.65 | 31-MAY-15:12 | 0.00 |
June | 0.249913E+11 | 0.899416E+10 | 705.91 | 0.248129E+11 | 0.178469E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:51 | 29480.46 | 11-JUN-08:61 | 29480.46 | 11-JUN-08:61 | 3144.57 | 30-JUN-08:62 | 10091.33 | 17-JUN-15:12 | 0.00 |
July | 0.277601E+11 | 0.958250E+10 | 728.77 | 0.249521E+11 | 0.280800E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-06:51 | 33980.31 | 27-JUL-08:62 | 28493.05 | 05-JUL-08:62 | 12307.44 | 27-JUL-08:62 | 9923.03 | 20-JUL-15:12 | 0.00 |
August | 0.281275E+11 | 0.966148E+10 | 725.74 | 0.251973E+11 | 0.293019E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 35224.44 | 04-AUG-08:62 | 28994.69 | 24-AUG-08:62 | 14950.87 | 04-AUG-08:62 | 9840.96 | 10-AUG-15:12 | 0.00 |
September | 0.261936E+11 | 0.864212E+10 | 699.19 | 0.232705E+11 | 0.292305E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 35783.06 | 03-SEP-08:62 | 29416.51 | 19-SEP-08:62 | 16753.06 | 03-SEP-08:62 | 9730.24 | 08-SEP-15:12 | 0.00 |
October | 0.180090E+11 | 0.567788E+10 | 639.18 | 0.172492E+11 | 0.759846E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:52 | 33136.22 | 22-OCT-08:62 | 30051.68 | 11-OCT-15:12 | 10355.84 | 22-OCT-08:62 | 9313.82 | 02-OCT-15:12 | 0.00 |
November | 0.121237E+11 | 0.362323E+10 | 511.76 | 0.114278E+11 | 0.695843E+09 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:53 | 35837.57 | 12-NOV-16:12 | 30013.82 | 15-NOV-16:12 | 17420.60 | 12-NOV-16:12 | 9385.62 | 12-NOV-16:12 | 0.00 |
December | 0.979659E+10 | 0.291083E+10 | 401.06 | 0.977689E+10 | 19704480.50 | 0.00 | 1.00 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 | 29794.74 | 13-DEC-16:12 | 29794.74 | 13-DEC-16:12 | 6008.41 | 13-DEC-09:02 | 8022.60 | 25-DEC-16:12 | 0.00 |
Annual Sum or Average | 0.211076E+12 | 0.693707E+11 | 7125.04 | 0.199665E+12 | 0.114107E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.628162E+10 | 0.189075E+10 | 357.65 | 0.579499E+10 | 19339967.51 | 0.00 | 1.00 | 0.00 | 29480.46 | 28493.05 | 462.66 | 8022.60 | 0.00 | ||||||
Maximum of Months | 0.281275E+11 | 0.966148E+10 | 728.77 | 0.251973E+11 | 0.293019E+10 | 0.00 | 1.00 | 0.00 | 35837.57 | 30105.72 | 17420.60 | 10091.33 | 0.00 |
Report: DXReportMonthly
For: PTAC_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.119935E+11 | 0.366632E+10 | 621.49 | 0.947966E+10 | 0.251388E+10 | 0.00 | 0.35 | 31-JAN-16:13 | 0.00 | 01-JAN-00:05 | 12699.16 | 14-JAN-13:30 | 12237.46 | 31-JAN-16:10 | 4697.38 | 21-JAN-11:30 | 4035.79 | 31-JAN-16:10 | 0.00 |
February | 0.675928E+10 | 0.206163E+10 | 470.98 | 0.408217E+10 | 0.267711E+10 | 0.00 | 0.25 | 16-FEB-13:30 | 0.00 | 01-FEB-04:40 | 10075.36 | 16-FEB-13:30 | 7343.40 | 22-FEB-16:10 | 5447.99 | 20-FEB-10:53 | 3018.71 | 16-FEB-13:30 | 0.00 |
March | 0.108044E+11 | 0.332134E+10 | 600.83 | 0.796099E+10 | 0.284346E+10 | 0.00 | 0.34 | 16-MAR-15:13 | 0.00 | 01-MAR-06:10 | 11981.42 | 16-MAR-15:13 | 11550.55 | 16-MAR-15:13 | 3793.17 | 02-MAR-11:40 | 3929.98 | 16-MAR-15:13 | 0.00 |
April | 0.203288E+11 | 0.658424E+10 | 719.02 | 0.189290E+11 | 0.139989E+10 | 0.00 | 0.49 | 14-APR-18:03 | 0.00 | 21-APR-06:05 | 16731.69 | 14-APR-18:03 | 16731.69 | 14-APR-18:03 | 2054.23 | 01-APR-10:25 | 6061.25 | 14-APR-15:10 | 0.00 |
May | 0.241049E+11 | 0.805517E+10 | 744.00 | 0.231194E+11 | 0.985487E+09 | 0.00 | 0.55 | 31-MAY-18:15 | 0.05 | 01-MAY-06:05 | 18380.37 | 31-MAY-18:15 | 18380.37 | 31-MAY-18:15 | 1722.74 | 26-MAY-05:00 | 6792.14 | 31-MAY-18:03 | 0.00 |
June | 0.328299E+11 | 0.117145E+11 | 720.00 | 0.317653E+11 | 0.106465E+10 | 0.00 | 0.75 | 28-JUN-18:25 | 0.14 | 11-JUN-05:00 | 25613.47 | 28-JUN-18:25 | 25613.47 | 28-JUN-18:25 | 2623.89 | 30-JUN-07:30 | 10159.21 | 28-JUN-18:13 | 0.00 |
July | 0.365355E+11 | 0.124569E+11 | 744.00 | 0.308626E+11 | 0.567292E+10 | 0.00 | 0.64 | 20-JUL-18:15 | 0.12 | 02-JUL-05:00 | 22557.56 | 20-JUL-18:30 | 22185.67 | 20-JUL-18:15 | 6886.08 | 13-JUL-21:00 | 8549.79 | 20-JUL-18:15 | 0.00 |
August | 0.357782E+11 | 0.121517E+11 | 744.00 | 0.299792E+11 | 0.579905E+10 | 0.00 | 0.65 | 25-AUG-15:14 | 0.10 | 06-AUG-05:00 | 21463.11 | 25-AUG-18:03 | 21463.11 | 25-AUG-18:03 | 5875.12 | 09-AUG-22:00 | 8782.24 | 25-AUG-15:10 | 0.00 |
September | 0.320847E+11 | 0.105309E+11 | 720.00 | 0.262667E+11 | 0.581804E+10 | 0.00 | 0.60 | 28-SEP-15:10 | 0.09 | 22-SEP-06:05 | 20705.22 | 08-SEP-18:15 | 20134.23 | 28-SEP-15:10 | 5926.11 | 04-SEP-09:53 | 7675.23 | 28-SEP-15:10 | 0.00 |
October | 0.203257E+11 | 0.647154E+10 | 719.33 | 0.173235E+11 | 0.300223E+10 | 0.00 | 0.53 | 06-OCT-15:10 | 0.00 | 12-OCT-05:10 | 18709.88 | 03-OCT-12:30 | 17842.89 | 06-OCT-15:10 | 4358.90 | 02-OCT-23:00 | 6538.96 | 02-OCT-13:30 | 0.00 |
November | 0.125343E+11 | 0.383718E+10 | 639.82 | 0.945421E+10 | 0.308008E+10 | 0.00 | 0.42 | 01-NOV-15:10 | 0.00 | 04-NOV-04:10 | 15393.47 | 01-NOV-15:10 | 14284.51 | 01-NOV-15:10 | 5031.08 | 14-NOV-12:20 | 4972.56 | 01-NOV-15:10 | 0.00 |
December | 0.755774E+10 | 0.230960E+10 | 502.34 | 0.551341E+10 | 0.204433E+10 | 0.00 | 0.33 | 25-DEC-13:00 | 0.00 | 01-DEC-03:50 | 12656.83 | 25-DEC-13:00 | 11042.29 | 22-DEC-16:10 | 4444.53 | 13-DEC-12:30 | 3845.28 | 25-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.251637E+12 | 0.831611E+11 | 7945.84 | 0.214736E+12 | 0.369011E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.675928E+10 | 0.206163E+10 | 470.98 | 0.408217E+10 | 0.985487E+09 | 0.00 | 0.25 | 0.00 | 10075.36 | 7343.40 | 1722.74 | 3018.71 | 0.00 | ||||||
Maximum of Months | 0.365355E+11 | 0.124569E+11 | 744.00 | 0.317653E+11 | 0.581804E+10 | 0.00 | 0.75 | 0.14 | 25613.47 | 25613.47 | 6886.08 | 10159.21 | 0.00 |
Report: DXReportMonthly
For: PTAC_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.477038E+10 | 0.145299E+10 | 409.73 | 0.406164E+10 | 0.708733E+09 | 0.00 | 0.37 | 14-JAN-13:40 | 0.00 | 01-JAN-00:05 | 7713.54 | 14-JAN-13:30 | 7254.11 | 14-JAN-14:00 | 3269.96 | 09-JAN-11:15 | 2401.76 | 14-JAN-13:30 | 0.00 |
February | 0.247128E+10 | 0.748782E+09 | 271.55 | 0.178822E+10 | 0.683059E+09 | 0.00 | 0.36 | 16-FEB-13:30 | 0.00 | 01-FEB-00:30 | 8005.19 | 18-FEB-11:25 | 6206.24 | 23-FEB-14:00 | 4129.32 | 18-FEB-11:15 | 2327.32 | 18-FEB-11:25 | 0.00 |
March | 0.488886E+10 | 0.150295E+10 | 450.19 | 0.408797E+10 | 0.800890E+09 | 0.00 | 0.44 | 18-MAR-15:00 | 0.00 | 01-MAR-00:10 | 8906.76 | 18-MAR-13:30 | 8756.03 | 18-MAR-14:50 | 2641.69 | 02-MAR-11:40 | 2746.15 | 18-MAR-13:20 | 0.00 |
April | 0.120165E+11 | 0.390855E+10 | 674.30 | 0.115296E+11 | 0.486814E+09 | 0.00 | 0.66 | 14-APR-15:10 | 0.00 | 01-APR-01:10 | 12467.85 | 14-APR-15:10 | 12467.85 | 14-APR-15:10 | 2020.30 | 01-APR-09:50 | 4486.34 | 14-APR-15:10 | 0.00 |
May | 0.147689E+11 | 0.496997E+10 | 739.50 | 0.144027E+11 | 0.366234E+09 | 0.00 | 0.62 | 04-MAY-14:10 | 0.00 | 01-MAY-04:40 | 11655.38 | 04-MAY-14:10 | 11655.38 | 04-MAY-14:10 | 1074.67 | 13-MAY-08:52 | 4255.83 | 16-MAY-14:00 | 0.00 |
June | 0.199446E+11 | 0.717623E+10 | 720.00 | 0.195330E+11 | 0.411649E+09 | 0.00 | 0.79 | 15-JUN-15:10 | 0.09 | 21-JUN-05:13 | 14221.67 | 28-JUN-15:10 | 14221.67 | 28-JUN-15:10 | 1071.48 | 17-JUN-16:52 | 5866.00 | 28-JUN-15:10 | 0.00 |
July | 0.209293E+11 | 0.725374E+10 | 744.00 | 0.190280E+11 | 0.190123E+10 | 0.00 | 0.73 | 19-JUL-13:00 | 0.07 | 02-JUL-05:00 | 14157.41 | 19-JUL-13:00 | 13626.95 | 19-JUL-13:00 | 1885.33 | 13-JUL-18:10 | 5542.35 | 19-JUL-13:00 | 0.00 |
August | 0.202550E+11 | 0.699723E+10 | 744.00 | 0.183110E+11 | 0.194391E+10 | 0.00 | 0.79 | 26-AUG-15:00 | 0.07 | 06-AUG-05:00 | 14541.29 | 09-AUG-13:30 | 14322.38 | 26-AUG-14:40 | 1717.96 | 06-AUG-09:30 | 5801.15 | 26-AUG-15:00 | 0.00 |
September | 0.173446E+11 | 0.578481E+10 | 720.00 | 0.154447E+11 | 0.189989E+10 | 0.00 | 0.71 | 07-SEP-14:10 | 0.04 | 22-SEP-06:05 | 14090.72 | 07-SEP-13:30 | 13880.02 | 07-SEP-13:30 | 2390.36 | 04-SEP-09:53 | 5139.54 | 07-SEP-14:10 | 0.00 |
October | 0.100503E+11 | 0.323374E+10 | 619.96 | 0.908626E+10 | 0.964023E+09 | 0.00 | 0.66 | 02-OCT-13:10 | 0.00 | 08-OCT-04:20 | 13268.65 | 02-OCT-13:10 | 12857.30 | 02-OCT-13:10 | 3104.98 | 23-OCT-10:25 | 4626.12 | 02-OCT-13:10 | 0.00 |
November | 0.511964E+10 | 0.156433E+10 | 461.65 | 0.422597E+10 | 0.893678E+09 | 0.00 | 0.47 | 01-NOV-15:10 | 0.00 | 03-NOV-23:10 | 9431.42 | 01-NOV-15:10 | 9192.45 | 01-NOV-15:10 | 3656.37 | 14-NOV-11:15 | 3037.40 | 01-NOV-15:10 | 0.00 |
December | 0.255084E+10 | 0.776695E+09 | 254.49 | 0.207533E+10 | 0.475511E+09 | 0.00 | 0.36 | 25-DEC-13:00 | 0.00 | 01-DEC-00:10 | 7688.11 | 25-DEC-13:00 | 6963.83 | 25-DEC-13:40 | 2908.73 | 13-DEC-12:30 | 2328.76 | 25-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.135110E+12 | 0.453700E+11 | 6809.36 | 0.123574E+12 | 0.115356E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.247128E+10 | 0.748782E+09 | 254.49 | 0.178822E+10 | 0.366234E+09 | 0.00 | 0.36 | 0.00 | 7688.11 | 6206.24 | 1071.48 | 2327.32 | 0.00 | ||||||
Maximum of Months | 0.209293E+11 | 0.725374E+10 | 744.00 | 0.195330E+11 | 0.194391E+10 | 0.00 | 0.79 | 0.09 | 14541.29 | 14322.38 | 4129.32 | 5866.00 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_1 COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.304087E+11 | 0.894920E+10 | 358.60 | 0.297789E+11 | 0.629824E+09 | 0.00 | 1.00 | 31-JAN-16:10 | 0.00 | 01-JAN-00:05 | 65962.34 | 31-JAN-16:10 | 65962.34 | 31-JAN-16:10 | 16655.28 | 08-JAN-16:00 | 17234.28 | 31-JAN-16:10 | 0.00 |
February | 0.789753E+10 | 0.248707E+10 | 205.00 | 0.678090E+10 | 0.111663E+10 | 0.00 | 0.60 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 33475.25 | 18-FEB-14:00 | 29104.76 | 18-FEB-14:30 | 8063.51 | 18-FEB-17:40 | 9778.71 | 18-FEB-14:00 | 0.00 |
March | 0.321480E+11 | 0.950321E+10 | 403.67 | 0.312243E+11 | 0.923709E+09 | 0.00 | 0.99 | 20-MAR-18:03 | 0.00 | 01-MAR-00:10 | 61091.06 | 20-MAR-18:03 | 61091.06 | 20-MAR-18:03 | 5118.05 | 06-MAR-16:00 | 16020.62 | 20-MAR-18:03 | 0.00 |
April | 0.976679E+11 | 0.272702E+11 | 659.33 | 0.975062E+11 | 0.161640E+09 | 0.00 | 1.00 | 01-APR-12:40 | 0.00 | 01-APR-04:10 | 91533.44 | 14-APR-18:03 | 91533.44 | 14-APR-18:03 | 3125.82 | 17-APR-00:10 | 26076.86 | 14-APR-18:03 | 0.00 |
May | 0.128400E+12 | 0.360704E+11 | 734.83 | 0.128390E+12 | 9988673.44 | 0.00 | 1.00 | 01-MAY-17:20 | 0.00 | 01-MAY-02:40 | 97223.69 | 31-MAY-18:20 | 97223.69 | 31-MAY-18:20 | 3027.58 | 26-MAY-03:00 | 29026.77 | 31-MAY-18:03 | 0.00 |
June | 0.174721E+12 | 0.511795E+11 | 720.00 | 0.174609E+12 | 0.112610E+09 | 0.00 | 1.00 | 01-JUN-11:00 | 0.27 | 21-JUN-05:17 | 120776.04 | 28-JUN-18:20 | 120776.04 | 28-JUN-18:20 | 12054.61 | 17-JUN-17:05 | 40763.29 | 28-JUN-18:20 | 0.00 |
July | 0.194940E+12 | 0.536229E+11 | 744.00 | 0.173314E+12 | 0.216264E+11 | 0.00 | 1.00 | 01-JUL-00:10 | 0.27 | 01-JUL-05:55 | 123973.66 | 13-JUL-21:00 | 111279.77 | 20-JUL-18:20 | 57179.95 | 14-JUL-01:00 | 35500.62 | 20-JUL-18:03 | 0.00 |
August | 0.189096E+12 | 0.522499E+11 | 744.00 | 0.169016E+12 | 0.200795E+11 | 0.00 | 1.00 | 01-AUG-00:10 | 0.35 | 24-AUG-05:55 | 115309.57 | 09-AUG-21:10 | 110012.00 | 25-AUG-18:03 | 51184.80 | 18-AUG-22:10 | 35433.72 | 25-AUG-17:10 | 0.00 |
September | 0.169643E+12 | 0.458398E+11 | 720.00 | 0.145934E+12 | 0.237089E+11 | 0.00 | 1.00 | 01-SEP-00:50 | 0.27 | 22-SEP-06:00 | 120487.27 | 10-SEP-20:40 | 101245.88 | 08-SEP-18:20 | 70001.91 | 02-SEP-20:57 | 30668.10 | 08-SEP-15:10 | 0.00 |
October | 0.843593E+11 | 0.236314E+11 | 600.00 | 0.807797E+11 | 0.357953E+10 | 0.00 | 1.00 | 01-OCT-09:30 | 0.00 | 08-OCT-02:50 | 97621.92 | 02-OCT-20:10 | 90921.21 | 10-OCT-15:10 | 42434.14 | 03-OCT-03:00 | 26672.18 | 10-OCT-15:10 | 0.00 |
November | 0.352524E+11 | 0.103163E+11 | 404.79 | 0.298298E+11 | 0.542262E+10 | 0.00 | 1.00 | 01-NOV-14:10 | 0.00 | 02-NOV-01:20 | 73457.38 | 01-NOV-15:10 | 73457.38 | 01-NOV-15:10 | 29388.52 | 12-NOV-15:00 | 19187.74 | 01-NOV-15:10 | 0.00 |
December | 0.157285E+11 | 0.473820E+10 | 246.56 | 0.157038E+11 | 24678984.16 | 0.00 | 0.89 | 22-DEC-16:10 | 0.00 | 01-DEC-00:10 | 53511.80 | 22-DEC-16:10 | 53511.80 | 22-DEC-16:10 | 1981.45 | 12-DEC-16:00 | 14438.30 | 22-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.116026E+13 | 0.325858E+12 | 6540.77 | 0.108287E+13 | 0.773960E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.789753E+10 | 0.248707E+10 | 205.00 | 0.678090E+10 | 9988673.44 | 0.00 | 0.60 | 0.00 | 33475.25 | 29104.76 | 1981.45 | 9778.71 | 0.00 | ||||||
Maximum of Months | 0.194940E+12 | 0.536229E+11 | 744.00 | 0.174609E+12 | 0.237089E+11 | 0.00 | 1.00 | 0.35 | 123973.66 | 120776.04 | 70001.91 | 40763.29 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_6 COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.254279E+11 | 0.755047E+10 | 364.50 | 0.248605E+11 | 0.567330E+09 | 0.00 | 0.98 | 31-JAN-16:30 | 0.00 | 01-JAN-00:05 | 51685.72 | 31-JAN-16:30 | 51685.72 | 31-JAN-16:30 | 15434.27 | 08-JAN-16:00 | 13584.49 | 31-JAN-16:30 | 0.00 |
February | 0.739537E+10 | 0.232248E+10 | 213.17 | 0.637702E+10 | 0.101835E+10 | 0.00 | 0.63 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 30053.35 | 18-FEB-14:00 | 26462.43 | 18-FEB-14:00 | 7409.44 | 18-FEB-17:40 | 8718.10 | 18-FEB-14:00 | 0.00 |
March | 0.301742E+11 | 0.883004E+10 | 410.83 | 0.294313E+11 | 0.742851E+09 | 0.00 | 1.00 | 15-MAR-18:02 | 0.00 | 01-MAR-00:10 | 55452.01 | 16-MAR-15:40 | 55452.01 | 16-MAR-15:40 | 4755.83 | 06-MAR-16:00 | 14488.71 | 16-MAR-15:40 | 0.00 |
April | 0.925101E+11 | 0.255913E+11 | 663.00 | 0.923957E+11 | 0.114417E+09 | 0.00 | 1.00 | 01-APR-11:50 | 0.00 | 01-APR-04:20 | 82379.20 | 14-APR-18:03 | 82379.20 | 14-APR-18:03 | 2483.69 | 17-APR-00:20 | 24071.51 | 14-APR-15:10 | 0.00 |
May | 0.126456E+12 | 0.351759E+11 | 735.67 | 0.126453E+12 | 2357551.03 | 0.00 | 1.00 | 01-MAY-15:10 | 0.00 | 01-MAY-02:50 | 92130.94 | 31-MAY-18:03 | 92130.94 | 31-MAY-18:03 | 1196.99 | 26-MAY-03:00 | 27527.94 | 31-MAY-18:03 | 0.00 |
June | 0.172206E+12 | 0.501351E+11 | 720.00 | 0.172077E+12 | 0.129801E+09 | 0.00 | 1.00 | 01-JUN-09:10 | 0.32 | 21-JUN-05:10 | 112807.32 | 28-JUN-18:17 | 112807.32 | 28-JUN-18:17 | 14072.13 | 17-JUN-16:20 | 38213.00 | 28-JUN-18:03 | 0.00 |
July | 0.192299E+12 | 0.525784E+11 | 744.00 | 0.169677E+12 | 0.226222E+11 | 0.00 | 1.00 | 01-JUL-00:10 | 0.30 | 02-JUL-05:00 | 119193.46 | 13-JUL-21:10 | 103457.42 | 20-JUL-18:03 | 59247.70 | 13-JUL-21:00 | 32889.93 | 20-JUL-18:03 | 0.00 |
August | 0.182069E+12 | 0.499304E+11 | 744.00 | 0.161984E+12 | 0.200857E+11 | 0.00 | 1.00 | 01-AUG-00:10 | 0.38 | 24-AUG-06:10 | 112505.84 | 09-AUG-21:10 | 101904.28 | 10-AUG-18:03 | 53646.83 | 18-AUG-22:10 | 34520.15 | 25-AUG-15:10 | 0.00 |
September | 0.159464E+12 | 0.427598E+11 | 720.00 | 0.135916E+12 | 0.235478E+11 | 0.00 | 1.00 | 01-SEP-00:30 | 0.32 | 22-SEP-06:00 | 110029.39 | 10-SEP-20:40 | 92067.48 | 08-SEP-15:30 | 63614.08 | 02-SEP-21:15 | 28827.43 | 08-SEP-15:40 | 0.00 |
October | 0.745585E+11 | 0.208315E+11 | 604.67 | 0.713151E+11 | 0.324340E+10 | 0.00 | 1.00 | 01-OCT-08:50 | 0.00 | 08-OCT-03:00 | 93431.69 | 02-OCT-22:00 | 78626.64 | 02-OCT-15:10 | 41823.19 | 03-OCT-03:00 | 23509.83 | 02-OCT-22:00 | 0.00 |
November | 0.310058E+11 | 0.908826E+10 | 409.07 | 0.258056E+11 | 0.520017E+10 | 0.00 | 1.00 | 01-NOV-15:10 | 0.00 | 02-NOV-01:30 | 55316.38 | 01-NOV-15:10 | 55316.38 | 01-NOV-15:10 | 26869.60 | 12-NOV-15:00 | 14453.35 | 01-NOV-15:10 | 0.00 |
December | 0.135449E+11 | 0.410147E+10 | 250.83 | 0.135289E+11 | 16042498.44 | 0.00 | 0.77 | 25-DEC-14:00 | 0.00 | 01-DEC-00:10 | 38075.73 | 25-DEC-14:00 | 38075.73 | 25-DEC-14:00 | 1476.61 | 12-DEC-16:00 | 10636.20 | 25-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.110711E+13 | 0.308895E+12 | 6579.73 | 0.102982E+13 | 0.772905E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.739537E+10 | 0.232248E+10 | 213.17 | 0.637702E+10 | 2357551.03 | 0.00 | 0.63 | 0.00 | 30053.35 | 26462.43 | 1196.99 | 8718.10 | 0.00 | ||||||
Maximum of Months | 0.192299E+12 | 0.525784E+11 | 744.00 | 0.172077E+12 | 0.235478E+11 | 0.00 | 1.00 | 0.38 | 119193.46 | 112807.32 | 63614.08 | 38213.00 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_0 COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.192501E+11 | 0.579452E+10 | 605.81 | 0.171186E+11 | 0.213143E+10 | 0.00 | 0.91 | 08-JAN-20:11 | 0.00 | 01-JAN-00:05 | 25611.05 | 08-JAN-20:11 | 22731.86 | 31-JAN-19:02 | 13936.14 | 08-JAN-20:11 | 6726.71 | 08-JAN-20:11 | 0.00 | 01-JAN-00:05 |
February | 0.707102E+10 | 0.213977E+10 | 317.82 | 0.461113E+10 | 0.245989E+10 | 0.00 | 0.88 | 17-FEB-21:00 | 0.00 | 01-FEB-02:20 | 24293.17 | 17-FEB-21:00 | 12983.74 | 09-FEB-20:20 | 14050.77 | 17-FEB-21:00 | 6448.65 | 17-FEB-21:00 | 0.00 | 01-FEB-00:10 |
March | 0.128007E+11 | 0.391366E+10 | 418.46 | 0.112488E+11 | 0.155192E+10 | 0.00 | 0.88 | 17-MAR-19:30 | 0.00 | 01-MAR-00:10 | 23793.07 | 17-MAR-19:40 | 22460.48 | 20-MAR-18:02 | 5965.15 | 01-MAR-21:00 | 6659.36 | 20-MAR-18:05 | 0.00 | 01-MAR-00:10 |
April | 0.355334E+11 | 0.111166E+11 | 681.17 | 0.349205E+11 | 0.612882E+09 | 0.00 | 1.00 | 03-APR-18:02 | 0.00 | 01-APR-01:30 | 31947.81 | 14-APR-20:00 | 31947.81 | 14-APR-20:00 | 4518.41 | 15-APR-20:55 | 10307.22 | 14-APR-18:02 | 0.00 | 01-APR-00:10 |
May | 0.435191E+11 | 0.140164E+11 | 738.50 | 0.433011E+11 | 0.218012E+09 | 0.00 | 1.00 | 02-MAY-19:10 | 0.00 | 01-MAY-02:50 | 32732.65 | 31-MAY-18:15 | 32732.65 | 31-MAY-18:15 | 3021.15 | 26-MAY-03:00 | 11348.83 | 31-MAY-18:02 | 0.00 | 01-MAY-00:10 |
June | 0.594464E+11 | 0.199016E+11 | 720.00 | 0.587705E+11 | 0.675826E+09 | 0.00 | 1.00 | 01-JUN-17:05 | 0.32 | 21-JUN-05:00 | 40777.51 | 28-JUN-19:10 | 40777.51 | 28-JUN-19:10 | 6797.56 | 30-JUN-07:00 | 15093.67 | 28-JUN-18:13 | 0.00 | 01-JUN-00:10 |
July | 0.842728E+11 | 0.253335E+11 | 744.00 | 0.680291E+11 | 0.162437E+11 | 0.00 | 1.00 | 01-JUL-14:50 | 0.33 | 01-JUL-05:00 | 57976.25 | 14-JUL-01:00 | 43635.16 | 21-JUL-20:00 | 38964.68 | 14-JUL-01:00 | 16383.26 | 21-JUL-20:00 | 0.00 | 01-JUL-00:10 |
August | 0.882688E+11 | 0.261587E+11 | 744.00 | 0.702565E+11 | 0.180123E+11 | 0.00 | 1.00 | 01-AUG-00:10 | 0.56 | 24-AUG-03:00 | 64602.61 | 18-AUG-22:00 | 44192.65 | 10-AUG-19:20 | 35889.31 | 18-AUG-22:00 | 16068.35 | 18-AUG-22:00 | 0.00 | 01-AUG-00:10 |
September | 0.895004E+11 | 0.254541E+11 | 720.00 | 0.678925E+11 | 0.216078E+11 | 0.00 | 1.00 | 01-SEP-00:20 | 0.67 | 29-SEP-04:00 | 68194.20 | 03-SEP-21:51 | 44941.90 | 08-SEP-19:20 | 42299.25 | 02-SEP-22:03 | 16834.01 | 03-SEP-21:00 | 0.00 | 01-SEP-00:10 |
October | 0.528970E+11 | 0.152396E+11 | 744.00 | 0.460605E+11 | 0.683652E+10 | 0.00 | 1.00 | 01-OCT-00:10 | 0.05 | 25-OCT-09:20 | 52200.89 | 02-OCT-20:00 | 39662.19 | 03-OCT-19:20 | 24668.91 | 03-OCT-03:00 | 14281.40 | 02-OCT-19:20 | 0.00 | 01-OCT-00:10 |
November | 0.364261E+11 | 0.103341E+11 | 717.00 | 0.270362E+11 | 0.938991E+10 | 0.00 | 1.00 | 01-NOV-17:15 | 0.00 | 23-NOV-04:30 | 45716.96 | 11-NOV-21:00 | 28411.26 | 02-NOV-18:13 | 27634.24 | 11-NOV-21:00 | 11458.32 | 11-NOV-21:00 | 0.00 | 01-NOV-00:10 |
December | 0.183262E+11 | 0.555074E+10 | 677.83 | 0.171892E+11 | 0.113705E+10 | 0.00 | 0.83 | 12-DEC-22:00 | 0.00 | 04-DEC-02:50 | 22134.10 | 12-DEC-22:00 | 18991.39 | 26-DEC-20:10 | 7836.27 | 12-DEC-22:00 | 5936.19 | 12-DEC-22:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.547312E+12 | 0.164953E+12 | 7828.58 | 0.466435E+12 | 0.808773E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.707102E+10 | 0.213977E+10 | 317.82 | 0.461113E+10 | 0.218012E+09 | 0.00 | 0.83 | 0.00 | 22134.10 | 12983.74 | 3021.15 | 5936.19 | 0.00 | |||||||
Maximum of Months | 0.895004E+11 | 0.261587E+11 | 744.00 | 0.702565E+11 | 0.216078E+11 | 0.00 | 1.00 | 0.67 | 68194.20 | 44941.90 | 42299.25 | 16834.01 | 0.00 |
Report: DXReportMonthly
For: PSZ_LAUNDRY HP COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.119306E+11 | 0.350047E+10 | 299.15 | 0.118910E+11 | 39608745.77 | 0.00 | 1.00 | 31-JAN-19:08 | 0.00 | 01-JAN-00:05 | 36557.67 | 31-JAN-19:08 | 36557.67 | 31-JAN-19:08 | 1552.96 | 08-JAN-12:30 | 9299.47 | 31-JAN-19:08 | 0.00 |
February | 0.761965E+09 | 0.234111E+09 | 175.91 | 0.684398E+09 | 77567219.15 | 0.00 | 0.46 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 15098.45 | 18-FEB-14:00 | 13082.51 | 18-FEB-14:00 | 3697.96 | 15-FEB-20:10 | 4452.96 | 18-FEB-14:00 | 0.00 |
March | 0.147250E+11 | 0.423454E+10 | 323.12 | 0.145069E+11 | 0.218060E+09 | 0.00 | 1.00 | 15-MAR-18:02 | 0.00 | 01-MAR-00:10 | 43129.57 | 16-MAR-18:50 | 43129.57 | 16-MAR-18:50 | 3844.91 | 05-MAR-21:00 | 11614.07 | 20-MAR-18:20 | 0.00 |
April | 0.455295E+11 | 0.135906E+11 | 526.31 | 0.455169E+11 | 12545988.39 | 0.00 | 1.00 | 01-APR-17:30 | 0.00 | 01-APR-00:10 | 46241.63 | 14-APR-20:00 | 46241.63 | 14-APR-20:00 | 1072.47 | 15-APR-23:00 | 14399.33 | 14-APR-20:00 | 0.00 |
May | 0.574165E+11 | 0.177136E+11 | 637.12 | 0.574142E+11 | 2250510.35 | 0.00 | 1.00 | 01-MAY-17:50 | 0.00 | 01-MAY-00:10 | 46374.74 | 31-MAY-20:00 | 46374.74 | 31-MAY-20:00 | 450.84 | 26-MAY-03:00 | 15130.60 | 31-MAY-19:10 | 0.00 |
June | 0.678706E+11 | 0.225967E+11 | 714.17 | 0.677899E+11 | 80744614.12 | 0.00 | 1.00 | 01-JUN-17:05 | 0.00 | 11-JUN-04:50 | 47505.87 | 28-JUN-20:00 | 46930.40 | 28-JUN-20:00 | 614.18 | 18-JUN-19:40 | 17467.38 | 28-JUN-19:10 | 0.00 |
July | 0.728213E+11 | 0.232364E+11 | 738.75 | 0.708547E+11 | 0.196664E+10 | 0.00 | 1.00 | 01-JUL-17:05 | 0.00 | 01-JUL-03:30 | 50923.99 | 27-JUL-06:51 | 46734.09 | 21-JUL-20:00 | 30824.27 | 14-JUL-01:00 | 16773.20 | 21-JUL-19:20 | 0.00 |
August | 0.732995E+11 | 0.231037E+11 | 743.33 | 0.696092E+11 | 0.369028E+10 | 0.00 | 1.00 | 01-AUG-17:20 | 0.00 | 24-AUG-02:50 | 76189.16 | 04-AUG-19:10 | 46640.47 | 10-AUG-20:00 | 36462.15 | 18-AUG-22:00 | 19969.55 | 04-AUG-19:10 | 0.00 |
September | 0.696820E+11 | 0.209862E+11 | 703.67 | 0.630253E+11 | 0.665669E+10 | 0.00 | 1.00 | 01-SEP-05:10 | 0.00 | 15-SEP-02:20 | 79315.67 | 10-SEP-18:55 | 46484.90 | 08-SEP-20:00 | 48306.60 | 10-SEP-18:55 | 20548.38 | 03-SEP-21:00 | 0.00 |
October | 0.362130E+11 | 0.107386E+11 | 482.03 | 0.353135E+11 | 0.899576E+09 | 0.00 | 1.00 | 01-OCT-18:02 | 0.00 | 05-OCT-02:40 | 46863.96 | 02-OCT-20:00 | 46138.67 | 03-OCT-20:00 | 20120.20 | 03-OCT-06:58 | 14065.22 | 03-OCT-19:20 | 0.00 |
November | 0.121792E+11 | 0.353549E+10 | 296.18 | 0.111577E+11 | 0.102154E+10 | 0.00 | 1.00 | 01-NOV-18:02 | 0.00 | 01-NOV-00:10 | 45063.73 | 02-NOV-20:00 | 39887.59 | 01-NOV-18:08 | 21724.67 | 11-NOV-21:00 | 11491.50 | 02-NOV-18:02 | 0.00 |
December | 0.452091E+10 | 0.134134E+10 | 184.80 | 0.451993E+10 | 984487.12 | 0.00 | 0.74 | 25-DEC-13:00 | 0.00 | 01-DEC-00:10 | 24920.56 | 25-DEC-12:40 | 24920.56 | 25-DEC-12:40 | 146.63 | 12-DEC-21:00 | 7146.40 | 25-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.466950E+12 | 0.144812E+12 | 5824.53 | 0.452284E+12 | 0.146665E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.761965E+09 | 0.234111E+09 | 175.91 | 0.684398E+09 | 984487.12 | 0.00 | 0.46 | 0.00 | 15098.45 | 13082.51 | 146.63 | 4452.96 | 0.00 | ||||||
Maximum of Months | 0.732995E+11 | 0.232364E+11 | 743.33 | 0.708547E+11 | 0.665669E+10 | 0.00 | 1.00 | 0.00 | 79315.67 | 46930.40 | 48306.60 | 20548.38 | 0.00 |
Report: DXReportMonthly
For: PSZ_CAFE HP COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.851805E+10 | 0.235830E+10 | 210.53 | 0.848499E+10 | 33058127.46 | 0.00 | 0.98 | 14-JAN-14:00 | 0.00 | 01-JAN-00:05 | 24288.93 | 14-JAN-13:50 | 24288.93 | 14-JAN-13:50 | 1518.27 | 08-JAN-11:40 | 6618.62 | 31-JAN-16:10 | 0.00 |
February | 0.452005E+09 | 0.133274E+09 | 30.81 | 0.417792E+09 | 34212160.66 | 0.00 | 0.43 | 18-FEB-14:30 | 0.00 | 01-FEB-00:10 | 9463.94 | 18-FEB-14:30 | 9051.28 | 21-FEB-15:10 | 1509.41 | 18-FEB-14:10 | 2730.89 | 18-FEB-14:30 | 0.00 |
March | 0.632316E+10 | 0.183402E+10 | 191.76 | 0.625711E+10 | 66049455.30 | 0.00 | 0.91 | 16-MAR-15:10 | 0.00 | 01-MAR-00:10 | 22135.83 | 16-MAR-15:10 | 22135.83 | 16-MAR-15:10 | 1762.58 | 18-MAR-09:51 | 6338.42 | 16-MAR-15:10 | 0.00 |
April | 0.265524E+11 | 0.790081E+10 | 488.00 | 0.265050E+11 | 47363318.64 | 0.00 | 1.00 | 01-APR-12:40 | 0.00 | 01-APR-00:10 | 28294.02 | 14-APR-15:10 | 28294.02 | 14-APR-15:10 | 993.73 | 15-APR-20:55 | 9310.46 | 14-APR-15:10 | 0.00 |
May | 0.347427E+11 | 0.106545E+11 | 623.58 | 0.346996E+11 | 43181339.56 | 0.00 | 1.00 | 04-MAY-12:40 | 0.00 | 01-MAY-00:10 | 26125.62 | 18-MAY-15:10 | 26125.62 | 18-MAY-15:10 | 2401.63 | 10-MAY-24:00 | 8925.71 | 31-MAY-16:00 | 0.00 |
June | 0.505311E+11 | 0.162912E+11 | 713.33 | 0.501135E+11 | 0.417559E+09 | 0.00 | 1.00 | 01-JUN-12:30 | 0.00 | 11-JUN-04:40 | 34680.91 | 17-JUN-16:10 | 32672.48 | 28-JUN-15:12 | 5486.01 | 17-JUN-16:50 | 12670.71 | 16-JUN-16:00 | 0.00 |
July | 0.606925E+11 | 0.179554E+11 | 738.33 | 0.503244E+11 | 0.103680E+11 | 0.00 | 1.00 | 01-JUL-12:00 | 0.00 | 01-JUL-04:00 | 33599.18 | 14-JUL-00:10 | 30501.01 | 20-JUL-15:10 | 22080.00 | 14-JUL-01:00 | 11293.75 | 19-JUL-13:20 | 0.00 |
August | 0.591568E+11 | 0.175665E+11 | 737.83 | 0.491535E+11 | 0.100033E+11 | 0.00 | 1.00 | 01-AUG-12:50 | 0.00 | 05-AUG-17:30 | 34079.18 | 12-AUG-13:10 | 33447.72 | 25-AUG-15:10 | 14354.31 | 18-AUG-22:00 | 12878.13 | 25-AUG-15:10 | 0.00 |
September | 0.514859E+11 | 0.148503E+11 | 699.17 | 0.418425E+11 | 0.964340E+10 | 0.00 | 1.00 | 01-SEP-10:02 | 0.00 | 03-SEP-07:03 | 34183.84 | 01-SEP-13:30 | 32427.83 | 28-SEP-15:10 | 17291.81 | 10-SEP-21:00 | 11504.09 | 28-SEP-15:10 | 0.00 |
October | 0.236848E+11 | 0.684438E+10 | 424.83 | 0.218645E+11 | 0.182031E+10 | 0.00 | 1.00 | 01-OCT-10:50 | 0.00 | 04-OCT-06:10 | 32972.25 | 03-OCT-12:30 | 29860.01 | 10-OCT-15:10 | 11887.23 | 03-OCT-03:00 | 9794.47 | 06-OCT-15:10 | 0.00 |
November | 0.747570E+10 | 0.208846E+10 | 179.40 | 0.715188E+10 | 0.323817E+09 | 0.00 | 1.00 | 01-NOV-14:10 | 0.00 | 01-NOV-00:10 | 27087.74 | 01-NOV-15:10 | 25837.42 | 01-NOV-15:10 | 6175.74 | 14-NOV-13:00 | 7460.73 | 01-NOV-15:10 | 0.00 |
December | 0.390464E+10 | 0.109155E+10 | 115.92 | 0.390446E+10 | 172204.80 | 0.00 | 0.92 | 25-DEC-13:00 | 0.00 | 01-DEC-00:10 | 22478.65 | 25-DEC-13:00 | 22478.65 | 25-DEC-13:00 | 97.61 | 27-DEC-13:00 | 5951.98 | 25-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.333520E+12 | 0.995686E+11 | 5153.50 | 0.300719E+12 | 0.328004E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.452005E+09 | 0.133274E+09 | 30.81 | 0.417792E+09 | 172204.80 | 0.00 | 0.43 | 0.00 | 9463.94 | 9051.28 | 97.61 | 2730.89 | 0.00 | ||||||
Maximum of Months | 0.606925E+11 | 0.179554E+11 | 738.33 | 0.503244E+11 | 0.103680E+11 | 0.00 | 1.00 | 0.00 | 34680.91 | 33447.72 | 22080.00 | 12878.13 | 0.00 |
Report: DXReportMonthly
For: PSZ_KITCHEN HP COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.192673E+11 | 0.515799E+10 | 310.50 | 0.185676E+11 | 0.699671E+09 | 0.00 | 1.00 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 37292.65 | 31-JAN-16:40 | 32711.23 | 31-JAN-16:50 | 8591.74 | 08-JAN-16:10 | 10340.16 | 31-JAN-16:40 | 0.00 |
February | 0.408703E+10 | 0.115699E+10 | 140.00 | 0.348125E+10 | 0.605781E+09 | 0.00 | 0.81 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 25394.22 | 18-FEB-14:00 | 21104.91 | 18-FEB-14:00 | 7162.94 | 18-FEB-11:40 | 6553.57 | 18-FEB-14:00 | 0.00 |
March | 0.212937E+11 | 0.570257E+10 | 331.33 | 0.195777E+11 | 0.171607E+10 | 0.00 | 1.00 | 10-MAR-16:00 | 0.00 | 01-MAR-00:10 | 43932.63 | 20-MAR-17:20 | 34161.04 | 18-MAR-10:50 | 10088.40 | 17-MAR-17:10 | 12055.62 | 20-MAR-17:20 | 0.00 |
April | 0.543705E+11 | 0.151124E+11 | 540.00 | 0.500803E+11 | 0.429018E+10 | 0.00 | 1.00 | 01-APR-09:20 | 0.00 | 01-APR-00:10 | 46377.54 | 25-APR-17:20 | 38911.10 | 14-APR-10:50 | 10261.13 | 16-APR-17:20 | 14531.78 | 14-APR-17:20 | 0.00 |
May | 0.676968E+11 | 0.194726E+11 | 660.67 | 0.626642E+11 | 0.503258E+10 | 0.00 | 1.00 | 01-MAY-10:40 | 0.00 | 01-MAY-00:10 | 46728.45 | 15-MAY-17:20 | 39530.43 | 31-MAY-17:20 | 8253.40 | 30-MAY-10:10 | 15344.77 | 15-MAY-17:20 | 0.00 |
June | 0.837848E+11 | 0.261236E+11 | 718.33 | 0.761723E+11 | 0.761251E+10 | 0.00 | 1.00 | 01-JUN-07:03 | 0.00 | 11-JUN-05:00 | 55661.00 | 17-JUN-17:20 | 43060.95 | 28-JUN-17:20 | 14747.46 | 17-JUN-17:20 | 19250.59 | 17-JUN-15:50 | 0.00 |
July | 0.974614E+11 | 0.289761E+11 | 741.33 | 0.778450E+11 | 0.196164E+11 | 0.00 | 1.00 | 01-JUL-08:15 | 0.00 | 01-JUL-04:00 | 56428.53 | 23-JUL-10:40 | 42154.38 | 12-JUL-10:50 | 27480.07 | 15-JUL-05:47 | 18256.94 | 20-JUL-17:20 | 0.00 |
August | 0.966491E+11 | 0.285374E+11 | 744.00 | 0.759629E+11 | 0.206862E+11 | 0.00 | 1.00 | 01-AUG-05:30 | 0.05 | 24-AUG-03:00 | 60657.73 | 28-AUG-16:40 | 42368.66 | 26-AUG-10:50 | 34224.67 | 28-AUG-16:40 | 17943.54 | 18-AUG-10:40 | 0.00 |
September | 0.887776E+11 | 0.251607E+11 | 713.00 | 0.674789E+11 | 0.212986E+11 | 0.00 | 1.00 | 01-SEP-05:10 | 0.00 | 16-SEP-02:30 | 68477.01 | 10-SEP-18:55 | 40917.16 | 09-SEP-10:50 | 42047.64 | 10-SEP-18:55 | 17248.63 | 08-SEP-17:20 | 0.00 |
October | 0.464991E+11 | 0.128525E+11 | 497.17 | 0.402730E+11 | 0.622616E+10 | 0.00 | 1.00 | 01-OCT-07:20 | 0.00 | 05-OCT-05:00 | 52670.36 | 03-OCT-10:40 | 39543.58 | 02-OCT-10:50 | 21759.34 | 03-OCT-07:03 | 15692.62 | 03-OCT-17:20 | 0.00 |
November | 0.198892E+11 | 0.531432E+10 | 316.08 | 0.169459E+11 | 0.294331E+10 | 0.00 | 1.00 | 01-NOV-09:51 | 0.00 | 01-NOV-00:10 | 44798.73 | 01-NOV-10:40 | 34239.94 | 01-NOV-10:50 | 15869.75 | 12-NOV-11:50 | 11765.82 | 01-NOV-15:40 | 0.00 |
December | 0.975913E+10 | 0.264908E+10 | 197.83 | 0.962653E+10 | 0.132597E+09 | 0.00 | 1.00 | 21-DEC-16:20 | 0.00 | 01-DEC-00:10 | 35921.43 | 25-DEC-16:40 | 31578.25 | 22-DEC-11:50 | 6215.70 | 25-DEC-16:40 | 9116.25 | 25-DEC-16:40 | 0.00 |
Annual Sum or Average | 0.609536E+12 | 0.176216E+12 | 5910.25 | 0.518675E+12 | 0.908601E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.408703E+10 | 0.115699E+10 | 140.00 | 0.348125E+10 | 0.132597E+09 | 0.00 | 0.81 | 0.00 | 25394.22 | 21104.91 | 6215.70 | 6553.57 | 0.00 | ||||||
Maximum of Months | 0.974614E+11 | 0.289761E+11 | 744.00 | 0.778450E+11 | 0.212986E+11 | 0.00 | 1.00 | 0.05 | 68477.01 | 43060.95 | 42047.64 | 19250.59 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 591.95 | 470.38 | 121.57 | 1435.93 | 671.41 | 0.00 | 0.00 | 0.00 |
February | 376.61 | 252.29 | 124.32 | 761.12 | 663.24 | 7.50 | 0.00 | 0.00 |
March | 322.33 | 168.31 | 154.02 | 717.47 | 604.27 | 3.33 | 0.00 | 0.00 |
April | 295.06 | 133.90 | 161.16 | 917.56 | 310.42 | 0.00 | 0.00 | 0.00 |
May | 196.15 | 44.89 | 151.26 | 714.32 | 204.09 | 0.00 | 0.00 | 0.00 |
June | 162.35 | 19.18 | 143.17 | 881.58 | 72.28 | 0.00 | 0.00 | 0.00 |
July | 164.75 | 22.62 | 142.13 | 856.92 | 53.78 | 0.00 | 0.00 | 0.00 |
August | 209.02 | 69.51 | 139.51 | 973.74 | 72.13 | 0.00 | 0.00 | 0.00 |
September | 288.05 | 128.78 | 159.27 | 1091.81 | 104.52 | 0.00 | 0.00 | 0.00 |
October | 447.19 | 310.92 | 136.27 | 1236.08 | 393.68 | 0.50 | 0.00 | 0.00 |
November | 512.40 | 391.67 | 120.74 | 1216.30 | 603.04 | 0.00 | 0.00 | 0.00 |
December | 549.25 | 432.32 | 116.94 | 1252.67 | 806.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.96 | 203.72 | 139.24 | 1006.38 | 378.77 | 11.33 | 0.00 | 0.00 |
Minimum of Months | 162.35 | 19.18 | 116.94 | 714.32 | 53.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 591.95 | 470.38 | 161.16 | 1435.93 | 806.19 | 7.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1666.89 | 1324.56 | 342.33 | 3959.18 | 2085.45 | 0.50 | 0.00 | 0.00 |
February | 1060.50 | 710.43 | 350.07 | 2062.31 | 2156.39 | 12.50 | 0.00 | 0.00 |
March | 907.67 | 473.96 | 433.71 | 1912.07 | 1931.30 | 5.83 | 0.00 | 0.00 |
April | 830.86 | 377.05 | 453.80 | 2500.13 | 1027.17 | 0.00 | 0.00 | 0.00 |
May | 552.35 | 126.42 | 425.93 | 1934.39 | 687.11 | 0.00 | 0.00 | 0.00 |
June | 457.16 | 54.01 | 403.15 | 2422.70 | 248.98 | 0.00 | 0.00 | 0.00 |
July | 463.92 | 63.71 | 400.22 | 2350.76 | 195.93 | 0.00 | 0.00 | 0.00 |
August | 588.60 | 195.74 | 392.86 | 2682.13 | 262.34 | 0.83 | 0.00 | 0.00 |
September | 811.14 | 362.64 | 448.50 | 3010.03 | 369.74 | 0.00 | 0.00 | 0.00 |
October | 1259.26 | 875.54 | 383.72 | 3395.39 | 1274.68 | 2.17 | 0.00 | 0.00 |
November | 1442.89 | 1102.91 | 339.99 | 3333.29 | 1925.83 | 8.33 | 0.00 | 0.00 |
December | 1546.66 | 1217.37 | 329.29 | 3453.63 | 2448.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 965.76 | 573.66 | 392.09 | 2756.28 | 1213.65 | 30.17 | 0.00 | 0.00 |
Minimum of Months | 457.16 | 54.01 | 329.29 | 1912.07 | 195.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1666.89 | 1324.56 | 453.80 | 3959.18 | 2448.73 | 12.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2165.38 | 1720.68 | 444.70 | 5327.75 | 2829.97 | 0.00 | 0.00 | 0.00 |
February | 1377.65 | 922.90 | 454.76 | 2814.42 | 2914.01 | 10.50 | 0.00 | 0.00 |
March | 1179.11 | 615.70 | 563.41 | 2650.72 | 2617.68 | 5.83 | 0.00 | 0.00 |
April | 1079.33 | 489.81 | 589.52 | 3442.92 | 1345.54 | 0.00 | 0.00 | 0.00 |
May | 717.53 | 164.23 | 553.30 | 2692.23 | 897.02 | 0.00 | 0.00 | 0.00 |
June | 593.88 | 70.16 | 523.71 | 3360.11 | 317.09 | 0.00 | 0.00 | 0.00 |
July | 602.66 | 82.76 | 519.90 | 3258.24 | 244.05 | 0.00 | 0.00 | 0.00 |
August | 764.62 | 254.27 | 510.35 | 3690.51 | 324.99 | 0.00 | 0.00 | 0.00 |
September | 1053.71 | 471.09 | 582.63 | 4116.49 | 462.94 | 0.00 | 0.00 | 0.00 |
October | 1635.85 | 1137.37 | 498.48 | 4608.47 | 1684.88 | 1.00 | 0.00 | 0.00 |
November | 1874.40 | 1432.74 | 441.66 | 4499.83 | 2587.30 | 0.00 | 0.00 | 0.00 |
December | 2009.20 | 1581.44 | 427.77 | 4638.66 | 3393.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1254.57 | 745.22 | 509.35 | 3765.06 | 1629.40 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 593.88 | 70.16 | 427.77 | 2650.72 | 244.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2165.38 | 1720.68 | 589.52 | 5327.75 | 3393.38 | 10.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.43 | 106.82 | 27.61 | 329.32 | 149.89 | 0.00 | 0.00 | 0.00 |
February | 85.53 | 57.30 | 28.23 | 172.80 | 152.81 | 11.83 | 0.00 | 0.00 |
March | 73.20 | 38.22 | 34.98 | 161.97 | 137.91 | 3.33 | 0.00 | 0.00 |
April | 67.01 | 30.41 | 36.60 | 219.88 | 58.61 | 0.00 | 0.00 | 0.00 |
May | 44.55 | 10.20 | 34.35 | 183.64 | 33.56 | 0.00 | 0.00 | 0.00 |
June | 36.87 | 4.36 | 32.51 | 243.66 | 7.82 | 0.00 | 0.00 | 0.00 |
July | 37.41 | 5.14 | 32.28 | 240.40 | 5.76 | 0.00 | 0.00 | 0.00 |
August | 47.47 | 15.79 | 31.68 | 259.72 | 6.69 | 0.00 | 0.00 | 0.00 |
September | 65.42 | 29.25 | 36.17 | 277.37 | 10.51 | 0.00 | 0.00 | 0.00 |
October | 101.56 | 70.61 | 30.95 | 289.09 | 78.73 | 0.00 | 0.00 | 0.00 |
November | 116.37 | 88.95 | 27.42 | 277.81 | 133.35 | 0.00 | 0.00 | 0.00 |
December | 124.74 | 98.18 | 26.56 | 290.07 | 185.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.89 | 46.26 | 31.62 | 245.97 | 79.77 | 15.17 | 0.00 | 0.00 |
Minimum of Months | 36.87 | 4.36 | 26.56 | 161.97 | 5.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.43 | 106.82 | 36.60 | 329.32 | 185.14 | 11.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.71 | 65.93 | 39.77 | 231.98 | 315.25 | 0.00 | 0.00 | 0.00 |
February | 85.42 | 41.44 | 43.99 | 133.18 | 315.97 | 11.50 | 0.00 | 0.00 |
March | 112.45 | 53.45 | 59.00 | 224.03 | 264.10 | 3.50 | 0.00 | 0.00 |
April | 171.82 | 97.48 | 74.34 | 512.41 | 109.91 | 0.00 | 0.00 | 0.00 |
May | 172.79 | 96.38 | 76.41 | 584.27 | 63.04 | 0.00 | 0.00 | 0.00 |
June | 183.02 | 107.11 | 75.91 | 775.00 | 14.53 | 0.00 | 0.00 | 0.00 |
July | 133.66 | 62.08 | 71.58 | 623.63 | 10.54 | 0.00 | 0.00 | 0.00 |
August | 127.71 | 63.92 | 63.79 | 584.07 | 12.43 | 0.00 | 0.00 | 0.00 |
September | 111.34 | 46.63 | 64.71 | 468.88 | 20.17 | 0.00 | 0.00 | 0.00 |
October | 114.36 | 65.44 | 48.93 | 322.94 | 161.15 | 0.00 | 0.00 | 0.00 |
November | 104.99 | 63.34 | 41.65 | 226.00 | 280.16 | 0.00 | 0.00 | 0.00 |
December | 84.98 | 48.49 | 36.48 | 158.20 | 393.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.83 | 67.74 | 58.09 | 404.93 | 162.76 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 84.98 | 41.44 | 36.48 | 133.18 | 10.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.02 | 107.11 | 76.41 | 775.00 | 393.41 | 11.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.65 | 0.00 | 16.65 | 16.53 | 174.40 | 0.00 | 0.00 | 0.00 |
February | 18.97 | 0.00 | 18.97 | 7.61 | 175.95 | 11.83 | 0.00 | 0.00 |
March | 25.22 | 0.00 | 25.22 | 31.16 | 155.44 | 4.33 | 0.00 | 0.00 |
April | 31.14 | 0.71 | 30.43 | 100.36 | 60.70 | 0.00 | 0.00 | 0.00 |
May | 37.30 | 4.15 | 33.15 | 149.52 | 29.98 | 0.00 | 0.00 | 0.00 |
June | 43.83 | 9.64 | 34.19 | 259.47 | 6.75 | 0.00 | 0.00 | 0.00 |
July | 36.90 | 4.96 | 31.94 | 235.08 | 5.24 | 0.00 | 0.00 | 0.00 |
August | 29.13 | 1.04 | 28.09 | 193.27 | 7.28 | 0.00 | 0.00 | 0.00 |
September | 27.17 | 0.03 | 27.14 | 153.72 | 12.34 | 0.00 | 0.00 | 0.00 |
October | 21.00 | 0.00 | 21.00 | 62.07 | 93.85 | 0.00 | 0.00 | 0.00 |
November | 17.49 | 0.00 | 17.49 | 17.64 | 158.53 | 2.83 | 0.00 | 0.00 |
December | 15.55 | 0.00 | 15.55 | 8.54 | 214.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.72 | 1.72 | 25.01 | 103.37 | 90.91 | 19.00 | 0.00 | 0.00 |
Minimum of Months | 15.55 | 0.00 | 15.55 | 7.61 | 5.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.83 | 9.64 | 34.19 | 259.47 | 214.66 | 11.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.71 | 65.93 | 39.77 | 240.61 | 319.19 | 0.00 | 0.00 | 0.00 |
February | 85.42 | 41.44 | 43.99 | 137.38 | 313.67 | 11.83 | 0.00 | 0.00 |
March | 112.45 | 53.45 | 59.00 | 222.51 | 275.26 | 3.50 | 0.00 | 0.00 |
April | 171.82 | 97.48 | 74.34 | 511.80 | 116.19 | 0.00 | 0.00 | 0.00 |
May | 172.79 | 96.38 | 76.41 | 580.73 | 65.33 | 0.00 | 0.00 | 0.00 |
June | 183.02 | 107.11 | 75.91 | 770.37 | 15.75 | 0.00 | 0.00 | 0.00 |
July | 133.66 | 62.08 | 71.58 | 622.28 | 11.08 | 0.00 | 0.00 | 0.00 |
August | 127.71 | 63.92 | 63.79 | 583.94 | 14.72 | 0.00 | 0.00 | 0.00 |
September | 111.34 | 46.63 | 64.71 | 469.48 | 23.41 | 0.00 | 0.00 | 0.00 |
October | 114.36 | 65.44 | 48.93 | 326.61 | 169.96 | 0.00 | 0.00 | 0.00 |
November | 104.99 | 63.34 | 41.65 | 231.69 | 286.25 | 2.83 | 0.00 | 0.00 |
December | 84.98 | 48.49 | 36.48 | 167.42 | 388.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.83 | 67.74 | 58.09 | 406.61 | 166.05 | 18.17 | 0.00 | 0.00 |
Minimum of Months | 84.98 | 41.44 | 36.48 | 137.38 | 11.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.02 | 107.11 | 76.41 | 770.37 | 388.94 | 11.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.52 | 85.44 | 22.08 | 231.51 | 176.88 | 0.00 | 0.00 | 0.00 |
February | 68.41 | 45.83 | 22.58 | 114.67 | 185.60 | 6.67 | 0.00 | 0.00 |
March | 58.55 | 30.57 | 27.98 | 103.04 | 167.31 | 0.00 | 0.00 | 0.00 |
April | 53.60 | 24.32 | 29.27 | 144.13 | 91.89 | 0.00 | 0.00 | 0.00 |
May | 35.63 | 8.15 | 27.47 | 110.90 | 64.25 | 0.00 | 0.00 | 0.00 |
June | 29.49 | 3.48 | 26.01 | 145.01 | 26.54 | 0.00 | 0.00 | 0.00 |
July | 29.93 | 4.11 | 25.82 | 136.64 | 22.76 | 0.00 | 0.00 | 0.00 |
August | 37.97 | 12.63 | 25.34 | 158.76 | 30.36 | 0.00 | 0.00 | 0.00 |
September | 52.32 | 23.39 | 28.93 | 176.67 | 40.46 | 0.00 | 0.00 | 0.00 |
October | 81.23 | 56.48 | 24.75 | 196.22 | 111.86 | 0.00 | 0.00 | 0.00 |
November | 93.07 | 71.14 | 21.93 | 192.36 | 165.06 | 0.00 | 0.00 | 0.00 |
December | 99.77 | 78.53 | 21.24 | 202.72 | 205.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.30 | 37.00 | 25.29 | 159.70 | 107.06 | 6.67 | 0.00 | 0.00 |
Minimum of Months | 29.49 | 3.48 | 21.24 | 103.04 | 22.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.52 | 85.44 | 29.27 | 231.51 | 205.95 | 6.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 0.00 | 13.32 | 15.66 | 139.63 | 0.00 | 0.00 | 0.00 |
February | 15.18 | 0.00 | 15.18 | 7.05 | 142.74 | 3.67 | 0.00 | 0.00 |
March | 20.18 | 0.00 | 20.17 | 27.84 | 123.56 | 0.00 | 0.00 | 0.00 |
April | 24.91 | 0.57 | 24.35 | 89.87 | 46.57 | 0.00 | 0.00 | 0.00 |
May | 29.84 | 3.32 | 26.52 | 130.87 | 22.76 | 0.00 | 0.00 | 0.00 |
June | 35.07 | 7.71 | 27.36 | 223.45 | 4.57 | 0.00 | 0.00 | 0.00 |
July | 29.52 | 3.97 | 25.56 | 201.96 | 3.72 | 0.00 | 0.00 | 0.00 |
August | 23.31 | 0.83 | 22.47 | 167.54 | 5.19 | 0.00 | 0.00 | 0.00 |
September | 21.74 | 0.02 | 21.71 | 133.45 | 8.85 | 0.00 | 0.00 | 0.00 |
October | 16.80 | 0.00 | 16.80 | 55.28 | 73.91 | 0.00 | 0.00 | 0.00 |
November | 14.00 | 0.00 | 14.00 | 16.35 | 126.47 | 2.83 | 0.00 | 0.00 |
December | 12.44 | 0.00 | 12.44 | 7.85 | 174.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.38 | 1.37 | 20.01 | 90.16 | 72.41 | 6.50 | 0.00 | 0.00 |
Minimum of Months | 12.44 | 0.00 | 12.44 | 7.05 | 3.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.07 | 7.71 | 27.36 | 223.45 | 174.41 | 3.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.89 | 63.48 | 37.41 | 179.02 | 281.74 | 0.00 | 0.00 | 0.00 |
February | 99.48 | 57.06 | 42.41 | 151.01 | 294.43 | 11.67 | 0.00 | 0.00 |
March | 123.20 | 62.98 | 60.22 | 231.09 | 243.58 | 3.50 | 0.00 | 0.00 |
April | 175.18 | 103.74 | 71.44 | 517.38 | 95.60 | 0.00 | 0.00 | 0.00 |
May | 182.03 | 107.42 | 74.61 | 614.23 | 53.84 | 0.00 | 0.00 | 0.00 |
June | 189.51 | 117.21 | 72.30 | 813.24 | 12.45 | 0.00 | 0.00 | 0.00 |
July | 160.46 | 90.09 | 70.36 | 715.76 | 9.59 | 0.00 | 0.00 | 0.00 |
August | 152.21 | 86.46 | 65.75 | 656.54 | 11.91 | 0.00 | 0.00 | 0.00 |
September | 125.01 | 59.94 | 65.07 | 504.97 | 18.46 | 0.00 | 0.00 | 0.00 |
October | 125.47 | 76.06 | 49.41 | 339.35 | 145.75 | 0.00 | 0.00 | 0.00 |
November | 97.17 | 58.35 | 38.82 | 173.58 | 255.46 | 0.00 | 0.00 | 0.00 |
December | 89.26 | 54.22 | 35.04 | 131.82 | 358.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.15 | 78.18 | 56.97 | 420.29 | 147.85 | 15.17 | 0.00 | 0.00 |
Minimum of Months | 89.26 | 54.22 | 35.04 | 131.82 | 9.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.51 | 117.21 | 74.61 | 813.24 | 358.84 | 11.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.43 | 106.82 | 27.61 | 326.97 | 148.56 | 0.00 | 0.00 | 0.00 |
February | 85.53 | 57.30 | 28.23 | 169.52 | 152.20 | 11.67 | 0.00 | 0.00 |
March | 73.20 | 38.22 | 34.98 | 158.85 | 137.48 | 3.33 | 0.00 | 0.00 |
April | 67.01 | 30.41 | 36.60 | 218.54 | 59.20 | 0.00 | 0.00 | 0.00 |
May | 44.55 | 10.20 | 34.35 | 182.26 | 33.87 | 0.00 | 0.00 | 0.00 |
June | 36.87 | 4.36 | 32.51 | 242.34 | 7.68 | 0.00 | 0.00 | 0.00 |
July | 37.41 | 5.14 | 32.28 | 238.02 | 5.72 | 0.00 | 0.00 | 0.00 |
August | 47.47 | 15.79 | 31.68 | 257.70 | 6.75 | 0.00 | 0.00 | 0.00 |
September | 65.42 | 29.25 | 36.17 | 275.98 | 10.53 | 0.00 | 0.00 | 0.00 |
October | 101.56 | 70.61 | 30.95 | 286.35 | 78.16 | 0.00 | 0.00 | 0.00 |
November | 116.37 | 88.95 | 27.42 | 275.99 | 131.91 | 0.00 | 0.00 | 0.00 |
December | 124.74 | 98.18 | 26.56 | 287.19 | 184.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.89 | 46.26 | 31.62 | 243.81 | 79.40 | 15.00 | 0.00 | 0.00 |
Minimum of Months | 36.87 | 4.36 | 26.56 | 158.85 | 5.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.43 | 106.82 | 36.60 | 326.97 | 184.23 | 11.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.65 | 0.00 | 16.65 | 15.01 | 172.30 | 0.00 | 0.00 | 0.00 |
February | 18.97 | 0.00 | 18.97 | 6.19 | 176.66 | 12.00 | 0.00 | 0.00 |
March | 25.22 | 0.00 | 25.22 | 29.09 | 153.77 | 4.33 | 0.00 | 0.00 |
April | 31.14 | 0.71 | 30.43 | 97.93 | 61.95 | 0.00 | 0.00 | 0.00 |
May | 37.30 | 4.15 | 33.15 | 144.03 | 29.99 | 0.00 | 0.00 | 0.00 |
June | 43.83 | 9.64 | 34.19 | 256.82 | 6.59 | 0.00 | 0.00 | 0.00 |
July | 36.90 | 4.96 | 31.94 | 232.09 | 5.17 | 0.00 | 0.00 | 0.00 |
August | 29.13 | 1.04 | 28.09 | 190.50 | 7.35 | 0.00 | 0.00 | 0.00 |
September | 27.17 | 0.03 | 27.14 | 151.57 | 12.72 | 0.00 | 0.00 | 0.00 |
October | 21.00 | 0.00 | 21.00 | 60.18 | 94.22 | 0.00 | 0.00 | 0.00 |
November | 17.49 | 0.00 | 17.49 | 16.60 | 156.74 | 2.83 | 0.00 | 0.00 |
December | 15.55 | 0.00 | 15.55 | 7.36 | 214.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.72 | 1.72 | 25.01 | 101.06 | 90.63 | 19.17 | 0.00 | 0.00 |
Minimum of Months | 15.55 | 0.00 | 15.55 | 6.19 | 5.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.83 | 9.64 | 34.19 | 256.82 | 214.42 | 12.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.89 | 63.48 | 37.41 | 189.09 | 283.30 | 0.00 | 0.00 | 0.00 |
February | 99.48 | 57.06 | 42.41 | 156.44 | 291.87 | 11.83 | 0.00 | 0.00 |
March | 123.20 | 62.98 | 60.22 | 232.56 | 252.59 | 4.17 | 0.00 | 0.00 |
April | 175.18 | 103.74 | 71.44 | 509.47 | 100.02 | 0.00 | 0.00 | 0.00 |
May | 182.03 | 107.42 | 74.61 | 598.22 | 54.55 | 0.00 | 0.00 | 0.00 |
June | 189.51 | 117.21 | 72.30 | 803.32 | 12.62 | 0.00 | 0.00 | 0.00 |
July | 160.46 | 90.09 | 70.36 | 712.21 | 9.72 | 0.00 | 0.00 | 0.00 |
August | 152.21 | 86.46 | 65.75 | 653.30 | 13.55 | 0.00 | 0.00 | 0.00 |
September | 125.01 | 59.94 | 65.07 | 500.66 | 20.68 | 0.00 | 0.00 | 0.00 |
October | 125.47 | 76.06 | 49.41 | 340.76 | 153.11 | 0.00 | 0.00 | 0.00 |
November | 97.17 | 58.35 | 38.82 | 178.48 | 258.53 | 2.83 | 0.00 | 0.00 |
December | 89.26 | 54.22 | 35.04 | 140.45 | 351.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.15 | 78.18 | 56.97 | 419.18 | 149.60 | 18.83 | 0.00 | 0.00 |
Minimum of Months | 89.26 | 54.22 | 35.04 | 140.45 | 9.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.51 | 117.21 | 74.61 | 803.32 | 351.74 | 11.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.08 | 0.00 | 21.08 | 14.33 | 271.13 | 242.33 | 0.00 | 0.00 |
February | 24.03 | 0.00 | 24.03 | 5.40 | 286.29 | 376.33 | 0.00 | 0.00 |
March | 31.94 | 0.00 | 31.93 | 33.04 | 237.95 | 245.67 | 0.00 | 0.00 |
April | 39.43 | 0.90 | 38.53 | 122.36 | 101.33 | 6.17 | 0.00 | 0.00 |
May | 47.23 | 5.25 | 41.98 | 182.61 | 57.36 | 0.00 | 0.00 | 0.00 |
June | 55.51 | 12.21 | 43.30 | 317.73 | 16.94 | 0.00 | 0.00 | 0.00 |
July | 46.73 | 6.28 | 40.45 | 277.58 | 13.20 | 0.00 | 0.00 | 0.00 |
August | 36.89 | 1.32 | 35.57 | 227.69 | 18.13 | 0.00 | 0.00 | 0.00 |
September | 34.41 | 0.04 | 34.37 | 180.72 | 29.41 | 0.00 | 0.00 | 0.00 |
October | 26.59 | 0.00 | 26.59 | 71.13 | 149.48 | 69.50 | 0.00 | 0.00 |
November | 22.15 | 0.00 | 22.15 | 17.04 | 248.46 | 188.17 | 0.00 | 0.00 |
December | 19.69 | 0.00 | 19.69 | 6.06 | 336.15 | 408.83 | 0.00 | 0.00 |
Annual Sum or Average | 33.84 | 2.17 | 31.67 | 121.84 | 146.54 | 1537.00 | 0.00 | 0.00 |
Minimum of Months | 19.69 | 0.00 | 19.69 | 5.40 | 13.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.51 | 12.21 | 43.30 | 317.73 | 336.15 | 408.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.77 | 0.00 | 7.77 | 5.28 | 99.95 | 242.33 | 0.00 | 0.00 |
February | 8.86 | 0.00 | 8.86 | 1.99 | 105.54 | 376.33 | 0.00 | 0.00 |
March | 11.77 | 0.00 | 11.77 | 12.18 | 87.72 | 245.67 | 0.00 | 0.00 |
April | 14.54 | 0.33 | 14.21 | 45.11 | 37.35 | 6.17 | 0.00 | 0.00 |
May | 17.41 | 1.94 | 15.48 | 67.32 | 21.14 | 0.00 | 0.00 | 0.00 |
June | 20.46 | 4.50 | 15.96 | 117.13 | 6.24 | 0.00 | 0.00 | 0.00 |
July | 17.23 | 2.31 | 14.91 | 102.33 | 4.87 | 0.00 | 0.00 | 0.00 |
August | 13.60 | 0.49 | 13.11 | 83.94 | 6.68 | 0.00 | 0.00 | 0.00 |
September | 12.68 | 0.01 | 12.67 | 66.62 | 10.84 | 0.00 | 0.00 | 0.00 |
October | 9.80 | 0.00 | 9.80 | 26.22 | 55.10 | 69.50 | 0.00 | 0.00 |
November | 8.17 | 0.00 | 8.17 | 6.28 | 91.59 | 188.17 | 0.00 | 0.00 |
December | 7.26 | 0.00 | 7.26 | 2.23 | 123.92 | 408.83 | 0.00 | 0.00 |
Annual Sum or Average | 12.48 | 0.80 | 11.68 | 44.92 | 54.02 | 1537.00 | 0.00 | 0.00 |
Minimum of Months | 7.26 | 0.00 | 7.26 | 1.99 | 4.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.46 | 4.50 | 15.96 | 117.13 | 123.92 | 408.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.73 | 49.84 | 12.88 | 149.81 | 86.18 | 186.83 | 0.00 | 0.00 |
February | 39.91 | 26.73 | 13.17 | 76.74 | 90.96 | 311.67 | 0.00 | 0.00 |
March | 34.16 | 17.84 | 16.32 | 71.61 | 81.39 | 212.00 | 0.00 | 0.00 |
April | 31.27 | 14.19 | 17.08 | 100.34 | 37.94 | 6.17 | 0.00 | 0.00 |
May | 20.78 | 4.76 | 16.03 | 82.72 | 23.88 | 0.00 | 0.00 | 0.00 |
June | 17.20 | 2.03 | 15.17 | 108.79 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 17.46 | 2.40 | 15.06 | 104.51 | 5.39 | 0.00 | 0.00 | 0.00 |
August | 22.15 | 7.37 | 14.78 | 114.76 | 7.09 | 0.00 | 0.00 | 0.00 |
September | 30.52 | 13.65 | 16.88 | 123.84 | 10.72 | 0.00 | 0.00 | 0.00 |
October | 47.39 | 32.95 | 14.44 | 131.08 | 48.87 | 54.67 | 0.00 | 0.00 |
November | 54.30 | 41.50 | 12.79 | 125.91 | 78.42 | 149.50 | 0.00 | 0.00 |
December | 58.20 | 45.81 | 12.39 | 131.01 | 104.23 | 318.83 | 0.00 | 0.00 |
Annual Sum or Average | 36.34 | 21.59 | 14.75 | 110.32 | 48.35 | 1239.67 | 0.00 | 0.00 |
Minimum of Months | 17.20 | 2.03 | 12.39 | 71.61 | 5.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.73 | 49.84 | 17.08 | 149.81 | 104.23 | 318.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.25 | 135.29 | 34.96 | 406.60 | 233.92 | 186.83 | 0.00 | 0.00 |
February | 108.32 | 72.56 | 35.75 | 208.29 | 246.89 | 311.67 | 0.00 | 0.00 |
March | 92.71 | 48.41 | 44.30 | 194.36 | 220.91 | 212.00 | 0.00 | 0.00 |
April | 84.86 | 38.51 | 46.35 | 272.33 | 102.99 | 6.17 | 0.00 | 0.00 |
May | 56.41 | 12.91 | 43.50 | 224.52 | 64.83 | 0.00 | 0.00 | 0.00 |
June | 46.69 | 5.52 | 41.18 | 295.27 | 19.99 | 0.00 | 0.00 | 0.00 |
July | 47.38 | 6.51 | 40.88 | 283.66 | 14.63 | 0.00 | 0.00 | 0.00 |
August | 60.12 | 19.99 | 40.13 | 311.48 | 19.23 | 0.00 | 0.00 | 0.00 |
September | 82.85 | 37.04 | 45.81 | 336.12 | 29.09 | 0.00 | 0.00 | 0.00 |
October | 128.62 | 89.42 | 39.19 | 355.78 | 132.64 | 54.67 | 0.00 | 0.00 |
November | 147.37 | 112.65 | 34.72 | 341.76 | 212.85 | 149.50 | 0.00 | 0.00 |
December | 157.97 | 124.34 | 33.63 | 355.58 | 282.89 | 318.83 | 0.00 | 0.00 |
Annual Sum or Average | 98.64 | 58.59 | 40.05 | 299.42 | 131.24 | 1239.67 | 0.00 | 0.00 |
Minimum of Months | 46.69 | 5.52 | 33.63 | 194.36 | 14.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 170.25 | 135.29 | 46.35 | 406.60 | 282.89 | 318.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.43 | 106.82 | 27.61 | 322.12 | 147.95 | 0.00 | 0.00 | 0.00 |
February | 85.53 | 57.30 | 28.23 | 168.45 | 148.74 | 17.50 | 0.00 | 0.00 |
March | 73.20 | 38.22 | 34.98 | 156.49 | 136.30 | 6.67 | 0.00 | 0.00 |
April | 67.01 | 30.41 | 36.60 | 213.26 | 56.65 | 0.00 | 0.00 | 0.00 |
May | 44.55 | 10.20 | 34.35 | 179.79 | 31.78 | 0.00 | 0.00 | 0.00 |
June | 36.87 | 4.36 | 32.51 | 242.10 | 6.95 | 0.00 | 0.00 | 0.00 |
July | 37.41 | 5.14 | 32.28 | 238.46 | 5.39 | 0.00 | 0.00 | 0.00 |
August | 47.47 | 15.79 | 31.68 | 256.74 | 6.18 | 0.00 | 0.00 | 0.00 |
September | 65.42 | 29.25 | 36.17 | 272.65 | 9.53 | 0.00 | 0.00 | 0.00 |
October | 101.56 | 70.61 | 30.95 | 281.62 | 76.55 | 0.00 | 0.00 | 0.00 |
November | 116.37 | 88.95 | 27.42 | 271.02 | 131.13 | 0.17 | 0.00 | 0.00 |
December | 124.74 | 98.18 | 26.56 | 285.95 | 182.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.89 | 46.26 | 31.62 | 241.21 | 78.01 | 24.33 | 0.00 | 0.00 |
Minimum of Months | 36.87 | 4.36 | 26.56 | 156.49 | 5.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.43 | 106.82 | 36.60 | 322.12 | 182.40 | 17.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.71 | 65.93 | 39.77 | 223.79 | 307.48 | 0.00 | 0.00 | 0.00 |
February | 85.42 | 41.44 | 43.99 | 126.78 | 305.74 | 17.50 | 0.00 | 0.00 |
March | 112.45 | 53.45 | 59.00 | 214.24 | 258.75 | 6.00 | 0.00 | 0.00 |
April | 171.82 | 97.48 | 74.34 | 493.81 | 105.71 | 0.00 | 0.00 | 0.00 |
May | 172.79 | 96.38 | 76.41 | 567.37 | 59.67 | 0.00 | 0.00 | 0.00 |
June | 183.02 | 107.11 | 75.91 | 758.95 | 13.10 | 0.00 | 0.00 | 0.00 |
July | 133.66 | 62.08 | 71.58 | 612.67 | 9.90 | 0.00 | 0.00 | 0.00 |
August | 127.71 | 63.92 | 63.79 | 574.43 | 11.58 | 0.00 | 0.00 | 0.00 |
September | 111.34 | 46.63 | 64.71 | 460.02 | 18.46 | 0.00 | 0.00 | 0.00 |
October | 114.36 | 65.44 | 48.93 | 313.01 | 155.43 | 0.00 | 0.00 | 0.00 |
November | 104.99 | 63.34 | 41.65 | 217.47 | 273.11 | 0.00 | 0.00 | 0.00 |
December | 84.98 | 48.49 | 36.48 | 152.84 | 383.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.83 | 67.74 | 58.09 | 394.15 | 157.95 | 23.50 | 0.00 | 0.00 |
Minimum of Months | 84.98 | 41.44 | 36.48 | 126.78 | 9.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.02 | 107.11 | 76.41 | 758.95 | 383.67 | 17.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.65 | 0.00 | 16.65 | 16.38 | 170.13 | 0.00 | 0.00 | 0.00 |
February | 18.97 | 0.00 | 18.97 | 7.26 | 170.56 | 17.50 | 0.00 | 0.00 |
March | 25.22 | 0.00 | 25.22 | 29.75 | 153.60 | 6.83 | 0.00 | 0.00 |
April | 31.14 | 0.71 | 30.43 | 97.67 | 58.86 | 0.00 | 0.00 | 0.00 |
May | 37.30 | 4.15 | 33.15 | 147.26 | 28.43 | 0.00 | 0.00 | 0.00 |
June | 43.83 | 9.64 | 34.19 | 257.31 | 6.13 | 0.00 | 0.00 | 0.00 |
July | 36.90 | 4.96 | 31.94 | 233.11 | 4.94 | 0.00 | 0.00 | 0.00 |
August | 29.13 | 1.04 | 28.09 | 191.79 | 6.86 | 0.00 | 0.00 | 0.00 |
September | 27.17 | 0.03 | 27.14 | 152.35 | 11.32 | 0.00 | 0.00 | 0.00 |
October | 21.00 | 0.00 | 21.00 | 61.23 | 90.91 | 0.00 | 0.00 | 0.00 |
November | 17.49 | 0.00 | 17.49 | 17.35 | 154.71 | 3.17 | 0.00 | 0.00 |
December | 15.55 | 0.00 | 15.55 | 8.85 | 209.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.72 | 1.72 | 25.01 | 102.15 | 88.48 | 27.50 | 0.00 | 0.00 |
Minimum of Months | 15.55 | 0.00 | 15.55 | 7.26 | 4.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.83 | 9.64 | 34.19 | 257.31 | 209.25 | 17.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.71 | 65.93 | 39.77 | 234.00 | 310.80 | 0.00 | 0.00 | 0.00 |
February | 85.42 | 41.44 | 43.99 | 131.90 | 302.65 | 17.50 | 0.00 | 0.00 |
March | 112.45 | 53.45 | 59.00 | 212.83 | 270.91 | 6.17 | 0.00 | 0.00 |
April | 171.82 | 97.48 | 74.34 | 493.28 | 112.29 | 0.00 | 0.00 | 0.00 |
May | 172.79 | 96.38 | 76.41 | 563.99 | 61.38 | 0.00 | 0.00 | 0.00 |
June | 183.02 | 107.11 | 75.91 | 754.27 | 14.06 | 0.00 | 0.00 | 0.00 |
July | 133.66 | 62.08 | 71.58 | 611.34 | 10.31 | 0.00 | 0.00 | 0.00 |
August | 127.71 | 63.92 | 63.79 | 574.27 | 13.74 | 0.00 | 0.00 | 0.00 |
September | 111.34 | 46.63 | 64.71 | 460.67 | 21.46 | 0.00 | 0.00 | 0.00 |
October | 114.36 | 65.44 | 48.93 | 317.36 | 164.14 | 0.00 | 0.00 | 0.00 |
November | 104.99 | 63.34 | 41.65 | 224.41 | 278.61 | 2.83 | 0.00 | 0.00 |
December | 84.98 | 48.49 | 36.48 | 163.93 | 378.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.83 | 67.74 | 58.09 | 396.39 | 161.02 | 26.50 | 0.00 | 0.00 |
Minimum of Months | 84.98 | 41.44 | 36.48 | 131.90 | 10.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 183.02 | 107.11 | 76.41 | 754.27 | 378.58 | 17.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 197.16 | 156.67 | 40.49 | 461.89 | 225.22 | 0.00 | 0.00 | 0.00 |
February | 125.43 | 84.03 | 41.41 | 238.92 | 228.33 | 12.67 | 0.00 | 0.00 |
March | 107.36 | 56.06 | 51.30 | 225.74 | 204.64 | 4.67 | 0.00 | 0.00 |
April | 98.27 | 44.60 | 53.68 | 320.36 | 82.85 | 0.00 | 0.00 | 0.00 |
May | 65.33 | 14.95 | 50.38 | 276.82 | 45.92 | 0.00 | 0.00 | 0.00 |
June | 54.07 | 6.39 | 47.68 | 374.25 | 9.47 | 0.00 | 0.00 | 0.00 |
July | 54.87 | 7.53 | 47.34 | 364.10 | 7.59 | 0.00 | 0.00 | 0.00 |
August | 69.62 | 23.15 | 46.47 | 388.33 | 8.82 | 0.00 | 0.00 | 0.00 |
September | 95.94 | 42.89 | 53.05 | 406.57 | 13.96 | 0.00 | 0.00 | 0.00 |
October | 148.94 | 103.56 | 45.39 | 410.18 | 115.29 | 0.00 | 0.00 | 0.00 |
November | 170.66 | 130.45 | 40.21 | 389.25 | 199.29 | 0.00 | 0.00 | 0.00 |
December | 182.94 | 143.99 | 38.95 | 406.66 | 279.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 114.23 | 67.85 | 46.38 | 356.02 | 117.94 | 17.33 | 0.00 | 0.00 |
Minimum of Months | 54.07 | 6.39 | 38.95 | 225.74 | 7.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.16 | 156.67 | 53.68 | 461.89 | 279.18 | 12.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.53 | 0.00 | 116.53 | 69.85 | 1540.02 | 0.00 | 0.00 | 0.00 |
February | 132.79 | 0.00 | 132.79 | 22.38 | 1633.79 | 12.67 | 0.00 | 0.00 |
March | 176.51 | 0.01 | 176.50 | 150.66 | 1396.19 | 5.83 | 0.00 | 0.00 |
April | 217.94 | 4.96 | 212.98 | 580.19 | 636.92 | 0.00 | 0.00 | 0.00 |
May | 261.06 | 29.03 | 232.03 | 877.20 | 379.81 | 0.00 | 0.00 | 0.00 |
June | 306.82 | 67.49 | 239.32 | 1581.51 | 127.91 | 0.00 | 0.00 | 0.00 |
July | 258.29 | 34.71 | 223.58 | 1359.73 | 110.72 | 0.00 | 0.00 | 0.00 |
August | 203.90 | 7.28 | 196.61 | 1113.26 | 153.74 | 0.00 | 0.00 | 0.00 |
September | 190.17 | 0.21 | 189.96 | 878.62 | 232.08 | 0.00 | 0.00 | 0.00 |
October | 146.97 | 0.00 | 146.97 | 340.68 | 898.03 | 1.00 | 0.00 | 0.00 |
November | 122.45 | 0.00 | 122.45 | 80.53 | 1432.55 | 0.00 | 0.00 | 0.00 |
December | 108.85 | 0.00 | 108.85 | 30.58 | 1857.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 187.05 | 12.01 | 175.05 | 593.02 | 863.14 | 19.50 | 0.00 | 0.00 |
Minimum of Months | 108.85 | 0.00 | 108.85 | 22.38 | 110.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 306.82 | 67.49 | 239.32 | 1581.51 | 1857.46 | 12.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.53 | 0.00 | 116.53 | 58.92 | 1589.60 | 0.00 | 0.00 | 0.00 |
February | 132.79 | 0.00 | 132.79 | 17.47 | 1694.16 | 12.67 | 0.00 | 0.00 |
March | 176.51 | 0.01 | 176.50 | 136.87 | 1439.77 | 5.83 | 0.00 | 0.00 |
April | 217.94 | 4.96 | 212.98 | 562.44 | 654.81 | 0.00 | 0.00 | 0.00 |
May | 261.06 | 29.03 | 232.03 | 857.90 | 391.15 | 0.00 | 0.00 | 0.00 |
June | 306.82 | 67.49 | 239.32 | 1560.31 | 133.24 | 0.00 | 0.00 | 0.00 |
July | 258.29 | 34.71 | 223.58 | 1338.29 | 116.41 | 0.00 | 0.00 | 0.00 |
August | 203.90 | 7.28 | 196.61 | 1093.81 | 162.13 | 0.00 | 0.00 | 0.00 |
September | 190.17 | 0.21 | 189.96 | 859.58 | 243.62 | 0.00 | 0.00 | 0.00 |
October | 146.97 | 0.00 | 146.97 | 325.34 | 926.77 | 1.00 | 0.00 | 0.00 |
November | 122.45 | 0.00 | 122.45 | 70.59 | 1479.64 | 0.00 | 0.00 | 0.00 |
December | 108.85 | 0.00 | 108.85 | 24.08 | 1920.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 187.05 | 12.01 | 175.05 | 578.00 | 892.33 | 19.50 | 0.00 | 0.00 |
Minimum of Months | 108.85 | 0.00 | 108.85 | 17.47 | 116.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 306.82 | 67.49 | 239.32 | 1560.31 | 1920.10 | 12.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.65 | 0.00 | 16.65 | 0.93 | 285.52 | 0.00 | 0.00 | 0.00 |
February | 18.97 | 0.00 | 18.97 | 0.16 | 308.14 | 14.00 | 0.00 | 0.00 |
March | 25.22 | 0.00 | 25.22 | 7.37 | 262.00 | 6.17 | 0.00 | 0.00 |
April | 31.14 | 0.71 | 30.43 | 49.99 | 124.18 | 0.00 | 0.00 | 0.00 |
May | 37.30 | 4.15 | 33.15 | 83.81 | 77.23 | 0.00 | 0.00 | 0.00 |
June | 43.83 | 9.64 | 34.19 | 173.87 | 29.90 | 0.00 | 0.00 | 0.00 |
July | 36.90 | 4.96 | 31.94 | 142.98 | 29.14 | 0.00 | 0.00 | 0.00 |
August | 29.13 | 1.04 | 28.09 | 117.04 | 42.20 | 0.00 | 0.00 | 0.00 |
September | 27.17 | 0.03 | 27.14 | 86.74 | 58.82 | 0.00 | 0.00 | 0.00 |
October | 21.00 | 0.00 | 21.00 | 26.12 | 176.53 | 2.33 | 0.00 | 0.00 |
November | 17.49 | 0.00 | 17.49 | 2.56 | 269.77 | 4.83 | 0.00 | 0.00 |
December | 15.55 | 0.00 | 15.55 | 0.34 | 335.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.72 | 1.72 | 25.01 | 57.91 | 165.92 | 27.33 | 0.00 | 0.00 |
Minimum of Months | 15.55 | 0.00 | 15.55 | 0.16 | 29.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.83 | 9.64 | 34.19 | 173.87 | 335.54 | 14.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 201.76 | 126.94 | 74.82 | 237.13 | 920.99 | 0.00 | 0.00 | 0.00 |
February | 198.94 | 114.12 | 84.82 | 215.22 | 1014.43 | 14.00 | 0.00 | 0.00 |
March | 246.38 | 125.95 | 120.43 | 300.51 | 845.55 | 6.00 | 0.00 | 0.00 |
April | 350.33 | 207.47 | 142.86 | 790.31 | 398.64 | 0.00 | 0.00 | 0.00 |
May | 364.03 | 214.82 | 149.21 | 947.21 | 274.37 | 0.00 | 0.00 | 0.00 |
June | 379.00 | 234.40 | 144.59 | 1277.06 | 111.51 | 0.00 | 0.00 | 0.00 |
July | 320.89 | 180.18 | 140.71 | 1077.07 | 110.74 | 0.00 | 0.00 | 0.00 |
August | 304.40 | 172.90 | 131.49 | 1007.80 | 155.51 | 0.00 | 0.00 | 0.00 |
September | 250.00 | 119.87 | 130.13 | 727.93 | 201.18 | 0.00 | 0.00 | 0.00 |
October | 250.92 | 152.11 | 98.81 | 490.41 | 566.43 | 2.17 | 0.00 | 0.00 |
November | 194.32 | 116.69 | 77.63 | 229.37 | 879.67 | 4.83 | 0.00 | 0.00 |
December | 178.51 | 108.43 | 70.08 | 172.86 | 1089.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 270.28 | 156.36 | 113.93 | 624.63 | 545.16 | 27.00 | 0.00 | 0.00 |
Minimum of Months | 178.51 | 108.43 | 70.08 | 172.86 | 110.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 379.00 | 234.40 | 149.21 | 1277.06 | 1089.33 | 14.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.43 | 106.82 | 27.61 | 278.57 | 229.80 | 0.00 | 0.00 | 0.00 |
February | 85.53 | 57.30 | 28.23 | 132.68 | 251.49 | 14.00 | 0.00 | 0.00 |
March | 73.20 | 38.22 | 34.98 | 112.36 | 229.38 | 6.00 | 0.00 | 0.00 |
April | 67.01 | 30.41 | 36.60 | 161.70 | 123.69 | 0.00 | 0.00 | 0.00 |
May | 44.55 | 10.20 | 34.35 | 117.67 | 86.89 | 0.00 | 0.00 | 0.00 |
June | 36.87 | 4.36 | 32.51 | 158.98 | 35.51 | 0.00 | 0.00 | 0.00 |
July | 37.41 | 5.14 | 32.28 | 150.91 | 32.97 | 0.00 | 0.00 | 0.00 |
August | 47.47 | 15.79 | 31.68 | 182.90 | 45.07 | 0.00 | 0.00 | 0.00 |
September | 65.42 | 29.25 | 36.17 | 204.82 | 58.11 | 0.00 | 0.00 | 0.00 |
October | 101.56 | 70.61 | 30.95 | 229.39 | 147.09 | 2.17 | 0.00 | 0.00 |
November | 116.37 | 88.95 | 27.42 | 229.33 | 216.81 | 4.83 | 0.00 | 0.00 |
December | 124.74 | 98.18 | 26.56 | 245.96 | 267.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.89 | 46.26 | 31.62 | 184.14 | 143.15 | 27.00 | 0.00 | 0.00 |
Minimum of Months | 36.87 | 4.36 | 26.56 | 112.36 | 32.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.43 | 106.82 | 36.60 | 278.57 | 267.02 | 14.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.08 | 0.00 | 21.08 | 11.32 | 267.02 | 264.00 | 0.00 | 0.00 |
February | 24.03 | 0.00 | 24.03 | 3.80 | 283.11 | 370.00 | 0.00 | 0.00 |
March | 31.94 | 0.00 | 31.93 | 28.04 | 238.07 | 229.33 | 0.00 | 0.00 |
April | 39.43 | 0.90 | 38.53 | 112.00 | 104.28 | 13.67 | 0.00 | 0.00 |
May | 47.23 | 5.25 | 41.98 | 170.88 | 59.78 | 0.00 | 0.00 | 0.00 |
June | 55.51 | 12.21 | 43.30 | 303.76 | 18.30 | 0.00 | 0.00 | 0.00 |
July | 46.73 | 6.28 | 40.45 | 263.41 | 14.77 | 0.00 | 0.00 | 0.00 |
August | 36.89 | 1.32 | 35.57 | 215.26 | 20.39 | 0.00 | 0.00 | 0.00 |
September | 34.41 | 0.04 | 34.37 | 169.75 | 32.47 | 0.00 | 0.00 | 0.00 |
October | 26.59 | 0.00 | 26.59 | 64.57 | 151.67 | 78.33 | 0.00 | 0.00 |
November | 22.15 | 0.00 | 22.15 | 13.97 | 248.21 | 204.00 | 0.00 | 0.00 |
December | 19.69 | 0.00 | 19.69 | 4.89 | 321.98 | 357.33 | 0.00 | 0.00 |
Annual Sum or Average | 33.84 | 2.17 | 31.67 | 113.97 | 146.05 | 1516.67 | 0.00 | 0.00 |
Minimum of Months | 19.69 | 0.00 | 19.69 | 3.80 | 14.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.51 | 12.21 | 43.30 | 303.76 | 321.98 | 370.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.86 | 0.00 | 18.86 | 10.13 | 238.88 | 264.00 | 0.00 | 0.00 |
February | 21.50 | 0.00 | 21.50 | 3.40 | 253.30 | 370.00 | 0.00 | 0.00 |
March | 28.57 | 0.00 | 28.57 | 25.09 | 213.00 | 229.33 | 0.00 | 0.00 |
April | 35.28 | 0.80 | 34.48 | 100.20 | 93.30 | 13.67 | 0.00 | 0.00 |
May | 42.26 | 4.70 | 37.56 | 152.88 | 53.48 | 0.00 | 0.00 | 0.00 |
June | 49.67 | 10.93 | 38.74 | 271.78 | 16.38 | 0.00 | 0.00 | 0.00 |
July | 41.81 | 5.62 | 36.19 | 235.67 | 13.22 | 0.00 | 0.00 | 0.00 |
August | 33.01 | 1.18 | 31.83 | 192.60 | 18.24 | 0.00 | 0.00 | 0.00 |
September | 30.78 | 0.03 | 30.75 | 151.88 | 29.05 | 0.00 | 0.00 | 0.00 |
October | 23.79 | 0.00 | 23.79 | 57.77 | 135.70 | 78.33 | 0.00 | 0.00 |
November | 19.82 | 0.00 | 19.82 | 12.50 | 222.07 | 203.83 | 0.00 | 0.00 |
December | 17.62 | 0.00 | 17.62 | 4.38 | 288.05 | 357.33 | 0.00 | 0.00 |
Annual Sum or Average | 30.28 | 1.94 | 28.34 | 101.97 | 130.67 | 1516.50 | 0.00 | 0.00 |
Minimum of Months | 17.62 | 0.00 | 17.62 | 3.40 | 13.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.67 | 10.93 | 38.74 | 271.78 | 288.05 | 370.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 501.87 | 398.80 | 103.07 | 1162.32 | 681.83 | 213.33 | 0.00 | 0.00 |
February | 319.30 | 213.90 | 105.40 | 589.72 | 716.51 | 317.00 | 0.00 | 0.00 |
March | 273.28 | 142.70 | 130.58 | 540.22 | 653.12 | 209.00 | 0.00 | 0.00 |
April | 250.16 | 113.52 | 136.63 | 757.94 | 314.01 | 15.00 | 0.00 | 0.00 |
May | 166.30 | 38.06 | 128.24 | 623.64 | 199.69 | 0.00 | 0.00 | 0.00 |
June | 137.64 | 16.26 | 121.38 | 832.26 | 63.47 | 0.00 | 0.00 | 0.00 |
July | 139.68 | 19.18 | 120.50 | 794.51 | 48.13 | 0.00 | 0.00 | 0.00 |
August | 177.22 | 58.93 | 118.28 | 875.67 | 63.65 | 0.00 | 0.00 | 0.00 |
September | 244.22 | 109.18 | 135.04 | 945.38 | 94.90 | 0.00 | 0.00 | 0.00 |
October | 379.14 | 263.61 | 115.53 | 1002.11 | 396.87 | 64.17 | 0.00 | 0.00 |
November | 434.43 | 332.07 | 102.36 | 970.32 | 626.56 | 166.17 | 0.00 | 0.00 |
December | 465.68 | 366.53 | 99.14 | 1031.16 | 801.40 | 296.67 | 0.00 | 0.00 |
Annual Sum or Average | 290.77 | 172.72 | 118.05 | 845.50 | 386.89 | 1281.33 | 0.00 | 0.00 |
Minimum of Months | 137.64 | 16.26 | 99.14 | 540.22 | 48.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 501.87 | 398.80 | 136.63 | 1162.32 | 801.40 | 317.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158548E+10 | 0.125987E+10 | 0.325609E+09 | 0.384598E+10 | 0.179830E+10 |
February | 0.911090E+09 | 0.610343E+09 | 0.300747E+09 | 0.184130E+10 | 0.160451E+10 |
March | 0.863334E+09 | 0.450810E+09 | 0.412524E+09 | 0.192166E+10 | 0.161848E+10 |
April | 0.764784E+09 | 0.347069E+09 | 0.417715E+09 | 0.237831E+10 | 0.804608E+09 |
May | 0.525370E+09 | 0.120245E+09 | 0.405124E+09 | 0.191325E+10 | 0.546631E+09 |
June | 0.420807E+09 | 49716938.98 | 0.371090E+09 | 0.228506E+10 | 0.187340E+09 |
July | 0.441262E+09 | 60594031.24 | 0.380668E+09 | 0.229518E+10 | 0.144041E+09 |
August | 0.559851E+09 | 0.186178E+09 | 0.373673E+09 | 0.260808E+10 | 0.193201E+09 |
September | 0.746633E+09 | 0.333800E+09 | 0.412833E+09 | 0.282996E+10 | 0.270923E+09 |
October | 0.119776E+10 | 0.832776E+09 | 0.364980E+09 | 0.331072E+10 | 0.105443E+10 |
November | 0.132815E+10 | 0.101520E+10 | 0.312949E+09 | 0.315265E+10 | 0.156308E+10 |
December | 0.147112E+10 | 0.115791E+10 | 0.313208E+09 | 0.335515E+10 | 0.215931E+10 |
Annual Sum or Average | 0.108156E+11 | 0.642451E+10 | 0.439112E+10 | 0.317373E+11 | 0.119448E+11 |
Minimum of Months | 0.420807E+09 | 49716938.98 | 0.300747E+09 | 0.184130E+10 | 0.144041E+09 |
Maximum of Months | 0.158548E+10 | 0.125987E+10 | 0.417715E+09 | 0.384598E+10 | 0.215931E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.446460E+10 | 0.354770E+10 | 0.916894E+09 | 0.106043E+11 | 0.558568E+10 |
February | 0.256557E+10 | 0.171868E+10 | 0.846884E+09 | 0.498915E+10 | 0.521675E+10 |
March | 0.243109E+10 | 0.126945E+10 | 0.116164E+10 | 0.512128E+10 | 0.517279E+10 |
April | 0.215358E+10 | 0.977322E+09 | 0.117626E+10 | 0.648033E+10 | 0.266243E+10 |
May | 0.147941E+10 | 0.338603E+09 | 0.114080E+10 | 0.518106E+10 | 0.184035E+10 |
June | 0.118496E+10 | 0.140000E+09 | 0.104496E+10 | 0.627964E+10 | 0.645357E+09 |
July | 0.124257E+10 | 0.170629E+09 | 0.107194E+10 | 0.629629E+10 | 0.524775E+09 |
August | 0.157650E+10 | 0.524264E+09 | 0.105224E+10 | 0.718381E+10 | 0.702642E+09 |
September | 0.210247E+10 | 0.939959E+09 | 0.116251E+10 | 0.780201E+10 | 0.958365E+09 |
October | 0.337280E+10 | 0.234504E+10 | 0.102776E+10 | 0.909420E+10 | 0.341410E+10 |
November | 0.373998E+10 | 0.285874E+10 | 0.881242E+09 | 0.863989E+10 | 0.499176E+10 |
December | 0.414258E+10 | 0.326061E+10 | 0.881974E+09 | 0.925019E+10 | 0.655868E+10 |
Annual Sum or Average | 0.304561E+11 | 0.180910E+11 | 0.123651E+11 | 0.869221E+11 | 0.382737E+11 |
Minimum of Months | 0.118496E+10 | 0.140000E+09 | 0.846884E+09 | 0.498915E+10 | 0.524775E+09 |
Maximum of Months | 0.446460E+10 | 0.354770E+10 | 0.117626E+10 | 0.106043E+11 | 0.655868E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.579976E+10 | 0.460867E+10 | 0.119110E+10 | 0.142698E+11 | 0.757979E+10 |
February | 0.333282E+10 | 0.223267E+10 | 0.110015E+10 | 0.680864E+10 | 0.704957E+10 |
March | 0.315812E+10 | 0.164909E+10 | 0.150904E+10 | 0.709968E+10 | 0.701119E+10 |
April | 0.279762E+10 | 0.126960E+10 | 0.152803E+10 | 0.892404E+10 | 0.348764E+10 |
May | 0.192183E+10 | 0.439865E+09 | 0.148197E+10 | 0.721088E+10 | 0.240259E+10 |
June | 0.153934E+10 | 0.181867E+09 | 0.135747E+10 | 0.870940E+10 | 0.821909E+09 |
July | 0.161416E+10 | 0.221657E+09 | 0.139251E+10 | 0.872688E+10 | 0.653655E+09 |
August | 0.204797E+10 | 0.681049E+09 | 0.136692E+10 | 0.988467E+10 | 0.870440E+09 |
September | 0.273123E+10 | 0.122106E+10 | 0.151017E+10 | 0.106700E+11 | 0.119995E+10 |
October | 0.438146E+10 | 0.304634E+10 | 0.133512E+10 | 0.123433E+11 | 0.451279E+10 |
November | 0.485845E+10 | 0.371366E+10 | 0.114478E+10 | 0.116636E+11 | 0.670629E+10 |
December | 0.538145E+10 | 0.423572E+10 | 0.114573E+10 | 0.124242E+11 | 0.908883E+10 |
Annual Sum or Average | 0.395642E+11 | 0.235012E+11 | 0.160630E+11 | 0.118735E+12 | 0.513846E+11 |
Minimum of Months | 0.153934E+10 | 0.181867E+09 | 0.110015E+10 | 0.680864E+10 | 0.653655E+09 |
Maximum of Months | 0.579976E+10 | 0.460867E+10 | 0.152803E+10 | 0.142698E+11 | 0.908883E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.360062E+09 | 0.286116E+09 | 73945903.68 | 0.882062E+09 | 0.401463E+09 |
February | 0.206909E+09 | 0.138609E+09 | 68299730.85 | 0.418038E+09 | 0.369673E+09 |
March | 0.196063E+09 | 0.102379E+09 | 93684261.73 | 0.433809E+09 | 0.369372E+09 |
April | 0.173683E+09 | 78819381.17 | 94863249.09 | 0.569941E+09 | 0.151911E+09 |
May | 0.119312E+09 | 27307767.65 | 92003812.81 | 0.491862E+09 | 89891198.45 |
June | 95565332.75 | 11290730.77 | 84274601.99 | 0.631564E+09 | 20261707.30 |
July | 0.100211E+09 | 13760921.47 | 86449855.19 | 0.643883E+09 | 15431727.25 |
August | 0.127142E+09 | 42281024.42 | 84861196.39 | 0.695627E+09 | 17926658.23 |
September | 0.169561E+09 | 75806073.28 | 93754523.57 | 0.718950E+09 | 27240412.58 |
October | 0.272011E+09 | 0.189124E+09 | 82887129.41 | 0.774291E+09 | 0.210876E+09 |
November | 0.301623E+09 | 0.230552E+09 | 71070699.81 | 0.720094E+09 | 0.345637E+09 |
December | 0.334092E+09 | 0.262963E+09 | 71129671.63 | 0.776931E+09 | 0.495868E+09 |
Annual Sum or Average | 0.245623E+10 | 0.145901E+10 | 0.997225E+09 | 0.775705E+10 | 0.251555E+10 |
Minimum of Months | 95565332.75 | 11290730.77 | 68299730.85 | 0.418038E+09 | 15431727.25 |
Maximum of Months | 0.360062E+09 | 0.286116E+09 | 94863249.09 | 0.882062E+09 | 0.495868E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283127E+09 | 0.176597E+09 | 0.106530E+09 | 0.621341E+09 | 0.844367E+09 |
February | 0.206656E+09 | 0.100247E+09 | 0.106409E+09 | 0.322198E+09 | 0.764400E+09 |
March | 0.301178E+09 | 0.143150E+09 | 0.158028E+09 | 0.600038E+09 | 0.707353E+09 |
April | 0.445349E+09 | 0.252655E+09 | 0.192694E+09 | 0.132818E+10 | 0.284897E+09 |
May | 0.462813E+09 | 0.258156E+09 | 0.204657E+09 | 0.156492E+10 | 0.168836E+09 |
June | 0.474395E+09 | 0.277638E+09 | 0.196756E+09 | 0.200880E+10 | 37672658.56 |
July | 0.357982E+09 | 0.166275E+09 | 0.191707E+09 | 0.167033E+10 | 28221835.49 |
August | 0.342052E+09 | 0.171208E+09 | 0.170843E+09 | 0.156438E+10 | 33299135.60 |
September | 0.288591E+09 | 0.120871E+09 | 0.167720E+09 | 0.121534E+10 | 52285728.35 |
October | 0.306310E+09 | 0.175264E+09 | 0.131046E+09 | 0.864966E+09 | 0.431620E+09 |
November | 0.272127E+09 | 0.164182E+09 | 0.107945E+09 | 0.585780E+09 | 0.726162E+09 |
December | 0.227598E+09 | 0.129885E+09 | 97712979.69 | 0.423725E+09 | 0.105370E+10 |
Annual Sum or Average | 0.396818E+10 | 0.213613E+10 | 0.183205E+10 | 0.127700E+11 | 0.513281E+10 |
Minimum of Months | 0.206656E+09 | 0.100247E+09 | 97712979.69 | 0.322198E+09 | 28221835.49 |
Maximum of Months | 0.474395E+09 | 0.277638E+09 | 0.204657E+09 | 0.200880E+10 | 0.105370E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44591305.74 | 0.00 | 44591305.74 | 44263963.17 | 0.467103E+09 |
February | 45893547.70 | 0.00 | 45893547.70 | 18421833.81 | 0.425670E+09 |
March | 67541929.80 | 5598.57 | 67536331.22 | 83463489.08 | 0.416333E+09 |
April | 80703148.09 | 1835548.57 | 78867599.52 | 0.260134E+09 | 0.157338E+09 |
May | 99893011.33 | 11107874.05 | 88785137.28 | 0.400469E+09 | 80309527.55 |
June | 0.113614E+09 | 24993211.65 | 88620984.29 | 0.672556E+09 | 17503670.41 |
July | 98832509.86 | 13280332.99 | 85552176.87 | 0.629641E+09 | 14036792.65 |
August | 78020401.42 | 2787291.79 | 75233109.62 | 0.517659E+09 | 19492219.44 |
September | 70419103.78 | 78555.52 | 70340548.26 | 0.398435E+09 | 31981825.26 |
October | 56235579.65 | 0.00 | 56235579.65 | 0.166248E+09 | 0.251379E+09 |
November | 45343146.70 | 0.00 | 45343146.70 | 45730217.77 | 0.410901E+09 |
December | 41652399.35 | 0.00 | 41652399.35 | 22871173.49 | 0.574936E+09 |
Annual Sum or Average | 0.842740E+09 | 54088413.14 | 0.788652E+09 | 0.325989E+10 | 0.286698E+10 |
Minimum of Months | 41652399.35 | 0.00 | 41652399.35 | 18421833.81 | 14036792.65 |
Maximum of Months | 0.113614E+09 | 24993211.65 | 88785137.28 | 0.672556E+09 | 0.574936E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283127E+09 | 0.176597E+09 | 0.106530E+09 | 0.644456E+09 | 0.854917E+09 |
February | 0.206656E+09 | 0.100247E+09 | 0.106409E+09 | 0.332352E+09 | 0.758819E+09 |
March | 0.301178E+09 | 0.143150E+09 | 0.158028E+09 | 0.595976E+09 | 0.737246E+09 |
April | 0.445349E+09 | 0.252655E+09 | 0.192694E+09 | 0.132657E+10 | 0.301157E+09 |
May | 0.462813E+09 | 0.258156E+09 | 0.204657E+09 | 0.155543E+10 | 0.174987E+09 |
June | 0.474395E+09 | 0.277638E+09 | 0.196756E+09 | 0.199680E+10 | 40836547.30 |
July | 0.357982E+09 | 0.166275E+09 | 0.191707E+09 | 0.166671E+10 | 29669142.76 |
August | 0.342052E+09 | 0.171208E+09 | 0.170843E+09 | 0.156402E+10 | 39413854.51 |
September | 0.288591E+09 | 0.120871E+09 | 0.167720E+09 | 0.121689E+10 | 60669803.92 |
October | 0.306310E+09 | 0.175264E+09 | 0.131046E+09 | 0.874783E+09 | 0.455211E+09 |
November | 0.272127E+09 | 0.164182E+09 | 0.107945E+09 | 0.600535E+09 | 0.741969E+09 |
December | 0.227598E+09 | 0.129885E+09 | 97712979.69 | 0.448428E+09 | 0.104175E+10 |
Annual Sum or Average | 0.396818E+10 | 0.213613E+10 | 0.183205E+10 | 0.128230E+11 | 0.523664E+10 |
Minimum of Months | 0.206656E+09 | 0.100247E+09 | 97712979.69 | 0.332352E+09 | 29669142.76 |
Maximum of Months | 0.474395E+09 | 0.277638E+09 | 0.204657E+09 | 0.199680E+10 | 0.104175E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287992E+09 | 0.228847E+09 | 59144960.60 | 0.620081E+09 | 0.473752E+09 |
February | 0.165494E+09 | 0.110865E+09 | 54628920.46 | 0.277407E+09 | 0.448997E+09 |
March | 0.156819E+09 | 81886934.78 | 74932507.33 | 0.275973E+09 | 0.448136E+09 |
April | 0.138918E+09 | 63042967.39 | 75875509.68 | 0.373588E+09 | 0.238176E+09 |
May | 95430285.85 | 21841870.36 | 73588415.50 | 0.297030E+09 | 0.172086E+09 |
June | 76437064.93 | 9030788.63 | 67406276.30 | 0.375859E+09 | 68789687.65 |
July | 80152681.12 | 11006548.27 | 69146132.85 | 0.365987E+09 | 60951989.81 |
August | 0.101694E+09 | 33818094.03 | 67875458.52 | 0.425215E+09 | 81314043.99 |
September | 0.135622E+09 | 60632800.40 | 74988705.62 | 0.457923E+09 | 0.104871E+09 |
October | 0.217565E+09 | 0.151269E+09 | 66296518.94 | 0.525558E+09 | 0.299598E+09 |
November | 0.241250E+09 | 0.184405E+09 | 56845254.86 | 0.498604E+09 | 0.427830E+09 |
December | 0.267221E+09 | 0.210328E+09 | 56892422.94 | 0.542963E+09 | 0.551622E+09 |
Annual Sum or Average | 0.196460E+10 | 0.116697E+10 | 0.797621E+09 | 0.503619E+10 | 0.337612E+10 |
Minimum of Months | 76437064.93 | 9030788.63 | 54628920.46 | 0.275973E+09 | 60951989.81 |
Maximum of Months | 0.287992E+09 | 0.228847E+09 | 75875509.68 | 0.620081E+09 | 0.551622E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35677773.26 | 0.00 | 35677773.26 | 41930440.84 | 0.373995E+09 |
February | 36719704.92 | 0.00 | 36719704.92 | 17057357.97 | 0.345320E+09 |
March | 54040706.29 | 4479.45 | 54036226.84 | 74559193.61 | 0.330956E+09 |
April | 64571076.60 | 1468633.50 | 63102443.09 | 0.232933E+09 | 0.120715E+09 |
May | 79925002.18 | 8887477.17 | 71037525.00 | 0.350520E+09 | 60949154.01 |
June | 90903404.92 | 19997219.71 | 70906185.21 | 0.579172E+09 | 11846194.42 |
July | 79076488.54 | 10625674.70 | 68450813.84 | 0.540933E+09 | 9975190.62 |
August | 62424594.77 | 2230129.01 | 60194465.76 | 0.448735E+09 | 13898591.03 |
September | 56342750.58 | 62852.75 | 56279897.84 | 0.345902E+09 | 22937531.07 |
October | 44994427.20 | 0.00 | 44994427.20 | 0.148059E+09 | 0.197950E+09 |
November | 36279325.75 | 0.00 | 36279325.75 | 42383278.56 | 0.327823E+09 |
December | 33326336.49 | 0.00 | 33326336.49 | 21037758.13 | 0.467130E+09 |
Annual Sum or Average | 0.674282E+09 | 43276466.30 | 0.631005E+09 | 0.284322E+10 | 0.228350E+10 |
Minimum of Months | 33326336.49 | 0.00 | 33326336.49 | 17057357.97 | 9975190.62 |
Maximum of Months | 90903404.92 | 19997219.71 | 71037525.00 | 0.579172E+09 | 0.467130E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270222E+09 | 0.170013E+09 | 0.100209E+09 | 0.479486E+09 | 0.754620E+09 |
February | 0.240659E+09 | 0.138051E+09 | 0.102608E+09 | 0.365324E+09 | 0.712278E+09 |
March | 0.329971E+09 | 0.168684E+09 | 0.161287E+09 | 0.618941E+09 | 0.652399E+09 |
April | 0.454059E+09 | 0.268898E+09 | 0.185161E+09 | 0.134106E+10 | 0.247800E+09 |
May | 0.487542E+09 | 0.287712E+09 | 0.199830E+09 | 0.164514E+10 | 0.144198E+09 |
June | 0.491213E+09 | 0.303810E+09 | 0.187404E+09 | 0.210791E+10 | 32269984.24 |
July | 0.429769E+09 | 0.241310E+09 | 0.188459E+09 | 0.191709E+10 | 25690578.05 |
August | 0.407675E+09 | 0.231569E+09 | 0.176106E+09 | 0.175848E+10 | 31891528.58 |
September | 0.324025E+09 | 0.155365E+09 | 0.168660E+09 | 0.130889E+10 | 47861261.15 |
October | 0.336055E+09 | 0.203719E+09 | 0.132337E+09 | 0.908906E+09 | 0.390369E+09 |
November | 0.251855E+09 | 0.151245E+09 | 0.100610E+09 | 0.449924E+09 | 0.662142E+09 |
December | 0.239076E+09 | 0.145223E+09 | 93853095.01 | 0.353075E+09 | 0.961118E+09 |
Annual Sum or Average | 0.426212E+10 | 0.246560E+10 | 0.179652E+10 | 0.132542E+11 | 0.466264E+10 |
Minimum of Months | 0.239076E+09 | 0.138051E+09 | 93853095.01 | 0.353075E+09 | 25690578.05 |
Maximum of Months | 0.491213E+09 | 0.303810E+09 | 0.199830E+09 | 0.210791E+10 | 0.961118E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.360062E+09 | 0.286116E+09 | 73945903.68 | 0.875769E+09 | 0.397903E+09 |
February | 0.206909E+09 | 0.138609E+09 | 68299730.85 | 0.410107E+09 | 0.368211E+09 |
March | 0.196063E+09 | 0.102379E+09 | 93684261.73 | 0.425452E+09 | 0.368228E+09 |
April | 0.173683E+09 | 78819381.17 | 94863249.09 | 0.566451E+09 | 0.153436E+09 |
May | 0.119312E+09 | 27307767.65 | 92003812.81 | 0.488161E+09 | 90718090.36 |
June | 95565332.75 | 11290730.77 | 84274601.99 | 0.628139E+09 | 19917963.48 |
July | 0.100211E+09 | 13760921.47 | 86449855.19 | 0.637523E+09 | 15325697.31 |
August | 0.127142E+09 | 42281024.42 | 84861196.39 | 0.690227E+09 | 18077379.12 |
September | 0.169561E+09 | 75806073.28 | 93754523.57 | 0.715345E+09 | 27296764.49 |
October | 0.272011E+09 | 0.189124E+09 | 82887129.41 | 0.766957E+09 | 0.209346E+09 |
November | 0.301623E+09 | 0.230552E+09 | 71070699.81 | 0.715357E+09 | 0.341912E+09 |
December | 0.334092E+09 | 0.262963E+09 | 71129671.63 | 0.769223E+09 | 0.493440E+09 |
Annual Sum or Average | 0.245623E+10 | 0.145901E+10 | 0.997225E+09 | 0.768871E+10 | 0.250381E+10 |
Minimum of Months | 95565332.75 | 11290730.77 | 68299730.85 | 0.410107E+09 | 15325697.31 |
Maximum of Months | 0.360062E+09 | 0.286116E+09 | 94863249.09 | 0.875769E+09 | 0.493440E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44591305.74 | 0.00 | 44591305.74 | 40213111.32 | 0.461483E+09 |
February | 45893547.70 | 0.00 | 45893547.70 | 14965845.88 | 0.427378E+09 |
March | 67541929.80 | 5598.57 | 67536331.22 | 77912396.26 | 0.411853E+09 |
April | 80703148.09 | 1835548.57 | 78867599.52 | 0.253838E+09 | 0.160571E+09 |
May | 99893011.33 | 11107874.05 | 88785137.28 | 0.385764E+09 | 80320760.95 |
June | 0.113614E+09 | 24993211.65 | 88620984.29 | 0.665682E+09 | 17093825.19 |
July | 98832509.86 | 13280332.99 | 85552176.87 | 0.621640E+09 | 13849942.53 |
August | 78020401.42 | 2787291.79 | 75233109.62 | 0.510228E+09 | 19689666.58 |
September | 70419103.78 | 78555.52 | 70340548.26 | 0.392861E+09 | 32975089.08 |
October | 56235579.65 | 0.00 | 56235579.65 | 0.161192E+09 | 0.252357E+09 |
November | 45343146.70 | 0.00 | 45343146.70 | 43018538.26 | 0.406268E+09 |
December | 41652399.35 | 0.00 | 41652399.35 | 19718849.74 | 0.574315E+09 |
Annual Sum or Average | 0.842740E+09 | 54088413.14 | 0.788652E+09 | 0.318704E+10 | 0.285815E+10 |
Minimum of Months | 41652399.35 | 0.00 | 41652399.35 | 14965845.88 | 13849942.53 |
Maximum of Months | 0.113614E+09 | 24993211.65 | 88785137.28 | 0.665682E+09 | 0.574315E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270222E+09 | 0.170013E+09 | 0.100209E+09 | 0.506453E+09 | 0.758802E+09 |
February | 0.240659E+09 | 0.138051E+09 | 0.102608E+09 | 0.378468E+09 | 0.706103E+09 |
March | 0.329971E+09 | 0.168684E+09 | 0.161287E+09 | 0.622877E+09 | 0.676538E+09 |
April | 0.454059E+09 | 0.268898E+09 | 0.185161E+09 | 0.132054E+10 | 0.259247E+09 |
May | 0.487542E+09 | 0.287712E+09 | 0.199830E+09 | 0.160227E+10 | 0.146103E+09 |
June | 0.491213E+09 | 0.303810E+09 | 0.187404E+09 | 0.208220E+10 | 32705089.44 |
July | 0.429769E+09 | 0.241310E+09 | 0.188459E+09 | 0.190760E+10 | 26026707.43 |
August | 0.407675E+09 | 0.231569E+09 | 0.176106E+09 | 0.174979E+10 | 36296061.58 |
September | 0.324025E+09 | 0.155365E+09 | 0.168660E+09 | 0.129770E+10 | 53612307.10 |
October | 0.336055E+09 | 0.203719E+09 | 0.132337E+09 | 0.912684E+09 | 0.410093E+09 |
November | 0.251855E+09 | 0.151245E+09 | 0.100610E+09 | 0.462620E+09 | 0.670117E+09 |
December | 0.239076E+09 | 0.145223E+09 | 93853095.01 | 0.376180E+09 | 0.942097E+09 |
Annual Sum or Average | 0.426212E+10 | 0.246560E+10 | 0.179652E+10 | 0.132194E+11 | 0.471774E+10 |
Minimum of Months | 0.239076E+09 | 0.138051E+09 | 93853095.01 | 0.376180E+09 | 26026707.43 |
Maximum of Months | 0.491213E+09 | 0.303810E+09 | 0.199830E+09 | 0.208220E+10 | 0.942097E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56472075.16 | 0.00 | 56472075.16 | 38387736.76 | 0.726206E+09 |
February | 58121282.43 | 0.00 | 58121282.43 | 13061203.40 | 0.692600E+09 |
March | 85537592.43 | 7090.24 | 85530502.19 | 88506558.62 | 0.637327E+09 |
April | 0.102205E+09 | 2324606.45 | 99880838.52 | 0.317149E+09 | 0.262634E+09 |
May | 0.126508E+09 | 14067421.62 | 0.112441E+09 | 0.489097E+09 | 0.153625E+09 |
June | 0.143885E+09 | 31652325.57 | 0.112233E+09 | 0.823545E+09 | 43908233.32 |
July | 0.125165E+09 | 16818703.78 | 0.108346E+09 | 0.743477E+09 | 35361251.14 |
August | 98807915.58 | 3529929.19 | 95277986.39 | 0.609848E+09 | 48567628.83 |
September | 89181351.73 | 99485.61 | 89081866.12 | 0.468431E+09 | 76219960.84 |
October | 71218813.36 | 0.00 | 71218813.36 | 0.190514E+09 | 0.400364E+09 |
November | 57424234.30 | 0.00 | 57424234.30 | 44170669.24 | 0.644016E+09 |
December | 52750135.65 | 0.00 | 52750135.65 | 16235814.62 | 0.900333E+09 |
Annual Sum or Average | 0.106728E+10 | 68499562.46 | 0.998778E+09 | 0.384242E+10 | 0.462116E+10 |
Minimum of Months | 52750135.65 | 0.00 | 52750135.65 | 13061203.40 | 35361251.14 |
Maximum of Months | 0.143885E+09 | 31652325.57 | 0.112441E+09 | 0.823545E+09 | 0.900333E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 20817945.23 | 0.00 | 20817945.23 | 14151309.28 | 0.267709E+09 |
February | 21425911.32 | 0.00 | 21425911.32 | 4814900.40 | 0.255321E+09 |
March | 31532698.40 | 2613.76 | 31530084.65 | 32627182.28 | 0.234945E+09 |
April | 37677159.01 | 856946.19 | 36820212.82 | 0.116914E+09 | 96817931.31 |
May | 46636159.32 | 5185834.10 | 41450325.23 | 0.180301E+09 | 56632644.44 |
June | 53042046.41 | 11668357.82 | 41373688.58 | 0.303593E+09 | 16186392.90 |
July | 46141052.46 | 6200070.62 | 39940981.83 | 0.274077E+09 | 13035621.36 |
August | 36424689.00 | 1301278.06 | 35123410.94 | 0.224815E+09 | 17904039.02 |
September | 32875938.96 | 36674.52 | 32839264.44 | 0.172683E+09 | 28097833.59 |
October | 26254203.54 | 0.00 | 26254203.54 | 70231338.07 | 0.147591E+09 |
November | 21168950.51 | 0.00 | 21168950.51 | 16283137.65 | 0.237411E+09 |
December | 19445884.21 | 0.00 | 19445884.21 | 5985193.54 | 0.331900E+09 |
Annual Sum or Average | 0.393443E+09 | 25251775.07 | 0.368191E+09 | 0.141648E+10 | 0.170355E+10 |
Minimum of Months | 19445884.21 | 0.00 | 19445884.21 | 4814900.40 | 13035621.36 |
Maximum of Months | 53042046.41 | 11668357.82 | 41450325.23 | 0.303593E+09 | 0.331900E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168003E+09 | 0.133501E+09 | 34502860.68 | 0.401241E+09 | 0.230831E+09 |
February | 96542761.56 | 64674382.37 | 31868379.19 | 0.185654E+09 | 0.220051E+09 |
March | 91482339.44 | 47769640.44 | 43712699.00 | 0.191796E+09 | 0.217996E+09 |
April | 81039615.39 | 36776805.64 | 44262809.76 | 0.260069E+09 | 98351690.50 |
May | 55670302.65 | 12741694.34 | 42928608.31 | 0.221557E+09 | 63972115.07 |
June | 44590399.16 | 5268209.48 | 39322189.69 | 0.281975E+09 | 19089776.95 |
July | 46757944.57 | 6420790.50 | 40337154.07 | 0.279919E+09 | 14436119.20 |
August | 59324047.89 | 19728155.62 | 39595892.27 | 0.307372E+09 | 18979235.28 |
September | 79116291.21 | 35370808.32 | 43745482.90 | 0.320982E+09 | 27780679.69 |
October | 0.126919E+09 | 88244357.63 | 38674800.57 | 0.351088E+09 | 0.130893E+09 |
November | 0.140736E+09 | 0.107575E+09 | 33161302.14 | 0.326371E+09 | 0.203269E+09 |
December | 0.155886E+09 | 0.122697E+09 | 33188818.15 | 0.350892E+09 | 0.279162E+09 |
Annual Sum or Average | 0.114607E+10 | 0.680768E+09 | 0.465301E+09 | 0.347892E+10 | 0.152481E+10 |
Minimum of Months | 44590399.16 | 5268209.48 | 31868379.19 | 0.185654E+09 | 14436119.20 |
Maximum of Months | 0.168003E+09 | 0.133501E+09 | 44262809.76 | 0.401241E+09 | 0.279162E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.455996E+09 | 0.362348E+09 | 93647821.28 | 0.108905E+10 | 0.626522E+09 |
February | 0.262037E+09 | 0.175540E+09 | 86497299.65 | 0.503903E+09 | 0.597265E+09 |
March | 0.248302E+09 | 0.129657E+09 | 0.118645E+09 | 0.520574E+09 | 0.591684E+09 |
April | 0.219958E+09 | 99819773.03 | 0.120138E+09 | 0.705882E+09 | 0.266946E+09 |
May | 0.151101E+09 | 34583564.70 | 0.116517E+09 | 0.601350E+09 | 0.173633E+09 |
June | 0.121027E+09 | 14298998.11 | 0.106728E+09 | 0.765338E+09 | 51813559.36 |
July | 0.126911E+09 | 17427338.77 | 0.109483E+09 | 0.759758E+09 | 39182580.36 |
August | 0.161018E+09 | 53546249.64 | 0.107471E+09 | 0.834271E+09 | 51513526.67 |
September | 0.214738E+09 | 96003608.71 | 0.118734E+09 | 0.871211E+09 | 75402447.10 |
October | 0.344485E+09 | 0.239513E+09 | 0.104971E+09 | 0.952924E+09 | 0.355271E+09 |
November | 0.381986E+09 | 0.291980E+09 | 90006556.99 | 0.885838E+09 | 0.551712E+09 |
December | 0.423107E+09 | 0.333026E+09 | 90081241.09 | 0.952394E+09 | 0.757702E+09 |
Annual Sum or Average | 0.311066E+10 | 0.184774E+10 | 0.126292E+10 | 0.944249E+10 | 0.413865E+10 |
Minimum of Months | 0.121027E+09 | 14298998.11 | 86497299.65 | 0.503903E+09 | 39182580.36 |
Maximum of Months | 0.455996E+09 | 0.362348E+09 | 0.120138E+09 | 0.108905E+10 | 0.757702E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.360062E+09 | 0.286116E+09 | 73945903.68 | 0.862757E+09 | 0.396259E+09 |
February | 0.206909E+09 | 0.138609E+09 | 68299730.85 | 0.407521E+09 | 0.359827E+09 |
March | 0.196063E+09 | 0.102379E+09 | 93684261.73 | 0.419130E+09 | 0.365059E+09 |
April | 0.173683E+09 | 78819381.17 | 94863249.09 | 0.552767E+09 | 0.146826E+09 |
May | 0.119312E+09 | 27307767.65 | 92003812.81 | 0.481537E+09 | 85127117.81 |
June | 95565332.75 | 11290730.77 | 84274601.99 | 0.627512E+09 | 18019378.52 |
July | 0.100211E+09 | 13760921.47 | 86449855.19 | 0.638698E+09 | 14430716.53 |
August | 0.127142E+09 | 42281024.42 | 84861196.39 | 0.687645E+09 | 16550631.04 |
September | 0.169561E+09 | 75806073.28 | 93754523.57 | 0.706709E+09 | 24713297.29 |
October | 0.272011E+09 | 0.189124E+09 | 82887129.41 | 0.754278E+09 | 0.205030E+09 |
November | 0.301623E+09 | 0.230552E+09 | 71070699.81 | 0.702490E+09 | 0.339889E+09 |
December | 0.334092E+09 | 0.262963E+09 | 71129671.63 | 0.765881E+09 | 0.488550E+09 |
Annual Sum or Average | 0.245623E+10 | 0.145901E+10 | 0.997225E+09 | 0.760693E+10 | 0.246028E+10 |
Minimum of Months | 95565332.75 | 11290730.77 | 68299730.85 | 0.407521E+09 | 14430716.53 |
Maximum of Months | 0.360062E+09 | 0.286116E+09 | 94863249.09 | 0.862757E+09 | 0.488550E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283127E+09 | 0.176597E+09 | 0.106530E+09 | 0.599396E+09 | 0.823545E+09 |
February | 0.206656E+09 | 0.100247E+09 | 0.106409E+09 | 0.306702E+09 | 0.739643E+09 |
March | 0.301178E+09 | 0.143150E+09 | 0.158028E+09 | 0.573822E+09 | 0.693046E+09 |
April | 0.445349E+09 | 0.252655E+09 | 0.192694E+09 | 0.127996E+10 | 0.273997E+09 |
May | 0.462813E+09 | 0.258156E+09 | 0.204657E+09 | 0.151965E+10 | 0.159833E+09 |
June | 0.474395E+09 | 0.277638E+09 | 0.196756E+09 | 0.196720E+10 | 33968033.20 |
July | 0.357982E+09 | 0.166275E+09 | 0.191707E+09 | 0.164099E+10 | 26528950.86 |
August | 0.342052E+09 | 0.171208E+09 | 0.170843E+09 | 0.153855E+10 | 31024464.44 |
September | 0.288591E+09 | 0.120871E+09 | 0.167720E+09 | 0.119237E+10 | 47842810.49 |
October | 0.306310E+09 | 0.175264E+09 | 0.131046E+09 | 0.838357E+09 | 0.416311E+09 |
November | 0.272127E+09 | 0.164182E+09 | 0.107945E+09 | 0.563670E+09 | 0.707907E+09 |
December | 0.227598E+09 | 0.129885E+09 | 97712979.69 | 0.409366E+09 | 0.102762E+10 |
Annual Sum or Average | 0.396818E+10 | 0.213613E+10 | 0.183205E+10 | 0.124300E+11 | 0.498126E+10 |
Minimum of Months | 0.206656E+09 | 0.100247E+09 | 97712979.69 | 0.306702E+09 | 26528950.86 |
Maximum of Months | 0.474395E+09 | 0.277638E+09 | 0.204657E+09 | 0.196720E+10 | 0.102762E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44591305.74 | 0.00 | 44591305.74 | 43869396.49 | 0.455665E+09 |
February | 45893547.70 | 0.00 | 45893547.70 | 17570242.46 | 0.412613E+09 |
March | 67541929.80 | 5598.57 | 67536331.22 | 79679954.47 | 0.411401E+09 |
April | 80703148.09 | 1835548.57 | 78867599.52 | 0.253151E+09 | 0.152563E+09 |
May | 99893011.33 | 11107874.05 | 88785137.28 | 0.394414E+09 | 76139548.88 |
June | 0.113614E+09 | 24993211.65 | 88620984.29 | 0.666957E+09 | 15878503.69 |
July | 98832509.86 | 13280332.99 | 85552176.87 | 0.624372E+09 | 13244302.58 |
August | 78020401.42 | 2787291.79 | 75233109.62 | 0.513682E+09 | 18373285.38 |
September | 70419103.78 | 78555.52 | 70340548.26 | 0.394891E+09 | 29347706.90 |
October | 56235579.65 | 0.00 | 56235579.65 | 0.163993E+09 | 0.243490E+09 |
November | 45343146.70 | 0.00 | 45343146.70 | 44974198.70 | 0.401015E+09 |
December | 41652399.35 | 0.00 | 41652399.35 | 23708014.13 | 0.560468E+09 |
Annual Sum or Average | 0.842740E+09 | 54088413.14 | 0.788652E+09 | 0.322126E+10 | 0.279020E+10 |
Minimum of Months | 41652399.35 | 0.00 | 41652399.35 | 17570242.46 | 13244302.58 |
Maximum of Months | 0.113614E+09 | 24993211.65 | 88785137.28 | 0.666957E+09 | 0.560468E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283127E+09 | 0.176597E+09 | 0.106530E+09 | 0.626758E+09 | 0.832451E+09 |
February | 0.206656E+09 | 0.100247E+09 | 0.106409E+09 | 0.319102E+09 | 0.732171E+09 |
March | 0.301178E+09 | 0.143150E+09 | 0.158028E+09 | 0.570038E+09 | 0.725604E+09 |
April | 0.445349E+09 | 0.252655E+09 | 0.192694E+09 | 0.127858E+10 | 0.291050E+09 |
May | 0.462813E+09 | 0.258156E+09 | 0.204657E+09 | 0.151060E+10 | 0.164404E+09 |
June | 0.474395E+09 | 0.277638E+09 | 0.196756E+09 | 0.195507E+10 | 36435689.64 |
July | 0.357982E+09 | 0.166275E+09 | 0.191707E+09 | 0.163742E+10 | 27626085.54 |
August | 0.342052E+09 | 0.171208E+09 | 0.170843E+09 | 0.153812E+10 | 36801943.07 |
September | 0.288591E+09 | 0.120871E+09 | 0.167720E+09 | 0.119407E+10 | 55611520.88 |
October | 0.306310E+09 | 0.175264E+09 | 0.131046E+09 | 0.850011E+09 | 0.439636E+09 |
November | 0.272127E+09 | 0.164182E+09 | 0.107945E+09 | 0.581668E+09 | 0.722153E+09 |
December | 0.227598E+09 | 0.129885E+09 | 97712979.69 | 0.439063E+09 | 0.101398E+10 |
Annual Sum or Average | 0.396818E+10 | 0.213613E+10 | 0.183205E+10 | 0.125005E+11 | 0.507792E+10 |
Minimum of Months | 0.206656E+09 | 0.100247E+09 | 97712979.69 | 0.319102E+09 | 27626085.54 |
Maximum of Months | 0.474395E+09 | 0.277638E+09 | 0.204657E+09 | 0.195507E+10 | 0.101398E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.528065E+09 | 0.419617E+09 | 0.108449E+09 | 0.123712E+10 | 0.603237E+09 |
February | 0.303451E+09 | 0.203283E+09 | 0.100168E+09 | 0.578003E+09 | 0.552386E+09 |
March | 0.287546E+09 | 0.150149E+09 | 0.137397E+09 | 0.604621E+09 | 0.548102E+09 |
April | 0.254722E+09 | 0.115596E+09 | 0.139126E+09 | 0.830363E+09 | 0.214757E+09 |
May | 0.174982E+09 | 40049461.99 | 0.134932E+09 | 0.741431E+09 | 0.123005E+09 |
June | 0.140156E+09 | 16558940.25 | 0.123597E+09 | 0.970053E+09 | 24549174.28 |
July | 0.146969E+09 | 20181711.97 | 0.126787E+09 | 0.975199E+09 | 20334909.25 |
August | 0.186466E+09 | 62009180.04 | 0.124457E+09 | 0.104010E+10 | 23625872.49 |
September | 0.248677E+09 | 0.111177E+09 | 0.137500E+09 | 0.105383E+10 | 36173848.32 |
October | 0.398930E+09 | 0.277368E+09 | 0.121562E+09 | 0.109863E+10 | 0.308781E+09 |
November | 0.442359E+09 | 0.338127E+09 | 0.104232E+09 | 0.100894E+10 | 0.516552E+09 |
December | 0.489978E+09 | 0.385660E+09 | 0.104318E+09 | 0.108919E+10 | 0.747769E+09 |
Annual Sum or Average | 0.360230E+10 | 0.213978E+10 | 0.146253E+10 | 0.112275E+11 | 0.371927E+10 |
Minimum of Months | 0.140156E+09 | 16558940.25 | 0.100168E+09 | 0.578003E+09 | 20334909.25 |
Maximum of Months | 0.528065E+09 | 0.419617E+09 | 0.139126E+09 | 0.123712E+10 | 0.747769E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312127E+09 | 0.00 | 0.312127E+09 | 0.187096E+09 | 0.412480E+10 |
February | 0.321243E+09 | 0.00 | 0.321243E+09 | 54132676.03 | 0.395246E+10 |
March | 0.472776E+09 | 39188.53 | 0.472736E+09 | 0.403539E+09 | 0.373954E+10 |
April | 0.564901E+09 | 12848353.36 | 0.552052E+09 | 0.150385E+10 | 0.165089E+10 |
May | 0.699225E+09 | 77752173.55 | 0.621472E+09 | 0.234948E+10 | 0.101728E+10 |
June | 0.795269E+09 | 0.174946E+09 | 0.620323E+09 | 0.409929E+10 | 0.331539E+09 |
July | 0.691801E+09 | 92958810.13 | 0.598843E+09 | 0.364191E+10 | 0.296566E+09 |
August | 0.546122E+09 | 19510303.62 | 0.526612E+09 | 0.298176E+10 | 0.411782E+09 |
September | 0.492915E+09 | 549867.82 | 0.492365E+09 | 0.227739E+10 | 0.601541E+09 |
October | 0.393634E+09 | 0.00 | 0.393634E+09 | 0.912467E+09 | 0.240527E+10 |
November | 0.317390E+09 | 0.00 | 0.317390E+09 | 0.208725E+09 | 0.371317E+10 |
December | 0.291556E+09 | 0.00 | 0.291556E+09 | 81914034.52 | 0.497503E+10 |
Annual Sum or Average | 0.589896E+10 | 0.378605E+09 | 0.552035E+10 | 0.187016E+11 | 0.272199E+11 |
Minimum of Months | 0.291556E+09 | 0.00 | 0.291556E+09 | 54132676.03 | 0.296566E+09 |
Maximum of Months | 0.795269E+09 | 0.174946E+09 | 0.621472E+09 | 0.409929E+10 | 0.497503E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312127E+09 | 0.00 | 0.312127E+09 | 0.157799E+09 | 0.425760E+10 |
February | 0.321243E+09 | 0.00 | 0.321243E+09 | 42257127.62 | 0.409852E+10 |
March | 0.472776E+09 | 39188.53 | 0.472736E+09 | 0.366606E+09 | 0.385627E+10 |
April | 0.564901E+09 | 12848353.36 | 0.552052E+09 | 0.145785E+10 | 0.169728E+10 |
May | 0.699225E+09 | 77752173.55 | 0.621472E+09 | 0.229779E+10 | 0.104765E+10 |
June | 0.795269E+09 | 0.174946E+09 | 0.620323E+09 | 0.404433E+10 | 0.345359E+09 |
July | 0.691801E+09 | 92958810.13 | 0.598843E+09 | 0.358448E+10 | 0.311791E+09 |
August | 0.546122E+09 | 19510303.62 | 0.526612E+09 | 0.292967E+10 | 0.434241E+09 |
September | 0.492915E+09 | 549867.82 | 0.492365E+09 | 0.222802E+10 | 0.631469E+09 |
October | 0.393634E+09 | 0.00 | 0.393634E+09 | 0.871383E+09 | 0.248225E+10 |
November | 0.317390E+09 | 0.00 | 0.317390E+09 | 0.182960E+09 | 0.383521E+10 |
December | 0.291556E+09 | 0.00 | 0.291556E+09 | 64496195.30 | 0.514281E+10 |
Annual Sum or Average | 0.589896E+10 | 0.378605E+09 | 0.552035E+10 | 0.182277E+11 | 0.281405E+11 |
Minimum of Months | 0.291556E+09 | 0.00 | 0.291556E+09 | 42257127.62 | 0.311791E+09 |
Maximum of Months | 0.795269E+09 | 0.174946E+09 | 0.621472E+09 | 0.404433E+10 | 0.514281E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44591305.74 | 0.00 | 44591305.74 | 2478876.29 | 0.764732E+09 |
February | 45893547.70 | 0.00 | 45893547.70 | 383275.45 | 0.745443E+09 |
March | 67541929.80 | 5598.57 | 67536331.22 | 19727345.21 | 0.701749E+09 |
April | 80703148.09 | 1835548.57 | 78867599.52 | 0.129586E+09 | 0.321886E+09 |
May | 99893011.33 | 11107874.05 | 88785137.28 | 0.224470E+09 | 0.206842E+09 |
June | 0.113614E+09 | 24993211.65 | 88620984.29 | 0.450667E+09 | 77510560.63 |
July | 98832509.86 | 13280332.99 | 85552176.87 | 0.382958E+09 | 78045910.51 |
August | 78020401.42 | 2787291.79 | 75233109.62 | 0.313491E+09 | 0.113037E+09 |
September | 70419103.78 | 78555.52 | 70340548.26 | 0.224833E+09 | 0.152465E+09 |
October | 56235579.65 | 0.00 | 56235579.65 | 69967809.44 | 0.472811E+09 |
November | 45343146.70 | 0.00 | 45343146.70 | 6647435.97 | 0.699251E+09 |
December | 41652399.35 | 0.00 | 41652399.35 | 921746.02 | 0.898697E+09 |
Annual Sum or Average | 0.842740E+09 | 54088413.14 | 0.788652E+09 | 0.182613E+10 | 0.523247E+10 |
Minimum of Months | 41652399.35 | 0.00 | 41652399.35 | 383275.45 | 77510560.63 |
Maximum of Months | 0.113614E+09 | 24993211.65 | 88785137.28 | 0.450667E+09 | 0.898697E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.540406E+09 | 0.340002E+09 | 0.200404E+09 | 0.635117E+09 | 0.246679E+10 |
February | 0.481285E+09 | 0.276083E+09 | 0.205202E+09 | 0.520665E+09 | 0.245411E+10 |
March | 0.659896E+09 | 0.337344E+09 | 0.322551E+09 | 0.804875E+09 | 0.226472E+10 |
April | 0.908053E+09 | 0.537757E+09 | 0.370296E+09 | 0.204847E+10 | 0.103327E+10 |
May | 0.975016E+09 | 0.575384E+09 | 0.399632E+09 | 0.253701E+10 | 0.734880E+09 |
June | 0.982357E+09 | 0.607576E+09 | 0.374781E+09 | 0.331014E+10 | 0.289042E+09 |
July | 0.859476E+09 | 0.482586E+09 | 0.376891E+09 | 0.288483E+10 | 0.296615E+09 |
August | 0.815292E+09 | 0.463104E+09 | 0.352188E+09 | 0.269930E+10 | 0.416516E+09 |
September | 0.648004E+09 | 0.310708E+09 | 0.337296E+09 | 0.188681E+10 | 0.521460E+09 |
October | 0.672062E+09 | 0.407408E+09 | 0.264654E+09 | 0.131351E+10 | 0.151711E+10 |
November | 0.503674E+09 | 0.302468E+09 | 0.201206E+09 | 0.594527E+09 | 0.228010E+10 |
December | 0.478119E+09 | 0.290426E+09 | 0.187693E+09 | 0.463000E+09 | 0.291766E+10 |
Annual Sum or Average | 0.852364E+10 | 0.493085E+10 | 0.359279E+10 | 0.196982E+11 | 0.171923E+11 |
Minimum of Months | 0.478119E+09 | 0.276083E+09 | 0.187693E+09 | 0.463000E+09 | 0.289042E+09 |
Maximum of Months | 0.982357E+09 | 0.607576E+09 | 0.399632E+09 | 0.331014E+10 | 0.291766E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.360062E+09 | 0.286116E+09 | 73945903.68 | 0.746135E+09 | 0.615486E+09 |
February | 0.206909E+09 | 0.138609E+09 | 68299730.85 | 0.320981E+09 | 0.608415E+09 |
March | 0.196063E+09 | 0.102379E+09 | 93684261.73 | 0.300942E+09 | 0.614382E+09 |
April | 0.173683E+09 | 78819381.17 | 94863249.09 | 0.419116E+09 | 0.320613E+09 |
May | 0.119312E+09 | 27307767.65 | 92003812.81 | 0.315169E+09 | 0.232715E+09 |
June | 95565332.75 | 11290730.77 | 84274601.99 | 0.412086E+09 | 92044898.99 |
July | 0.100211E+09 | 13760921.47 | 86449855.19 | 0.404202E+09 | 88310211.02 |
August | 0.127142E+09 | 42281024.42 | 84861196.39 | 0.489888E+09 | 0.120714E+09 |
September | 0.169561E+09 | 75806073.28 | 93754523.57 | 0.530883E+09 | 0.150628E+09 |
October | 0.272011E+09 | 0.189124E+09 | 82887129.41 | 0.614398E+09 | 0.393962E+09 |
November | 0.301623E+09 | 0.230552E+09 | 71070699.81 | 0.594419E+09 | 0.561984E+09 |
December | 0.334092E+09 | 0.262963E+09 | 71129671.63 | 0.658789E+09 | 0.715189E+09 |
Annual Sum or Average | 0.245623E+10 | 0.145901E+10 | 0.997225E+09 | 0.580701E+10 | 0.451444E+10 |
Minimum of Months | 95565332.75 | 11290730.77 | 68299730.85 | 0.300942E+09 | 88310211.02 |
Maximum of Months | 0.360062E+09 | 0.286116E+09 | 94863249.09 | 0.746135E+09 | 0.715189E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56472075.16 | 0.00 | 56472075.16 | 30326705.27 | 0.715173E+09 |
February | 58121282.43 | 0.00 | 58121282.43 | 9201903.65 | 0.684893E+09 |
March | 85537592.43 | 7090.24 | 85530502.19 | 75100579.00 | 0.637648E+09 |
April | 0.102205E+09 | 2324606.45 | 99880838.52 | 0.290291E+09 | 0.270291E+09 |
May | 0.126508E+09 | 14067421.62 | 0.112441E+09 | 0.457677E+09 | 0.160103E+09 |
June | 0.143885E+09 | 31652325.57 | 0.112233E+09 | 0.787358E+09 | 47443730.07 |
July | 0.125165E+09 | 16818703.78 | 0.108346E+09 | 0.705513E+09 | 39565100.03 |
August | 98807915.58 | 3529929.19 | 95277986.39 | 0.576562E+09 | 54601648.00 |
September | 89181351.73 | 99485.61 | 89081866.12 | 0.439991E+09 | 84149951.21 |
October | 71218813.36 | 0.00 | 71218813.36 | 0.172941E+09 | 0.406234E+09 |
November | 57424234.30 | 0.00 | 57424234.30 | 36215149.38 | 0.643366E+09 |
December | 52750135.65 | 0.00 | 52750135.65 | 13103149.40 | 0.862387E+09 |
Annual Sum or Average | 0.106728E+10 | 68499562.46 | 0.998778E+09 | 0.359428E+10 | 0.460586E+10 |
Minimum of Months | 52750135.65 | 0.00 | 52750135.65 | 9201903.65 | 39565100.03 |
Maximum of Months | 0.143885E+09 | 31652325.57 | 0.112441E+09 | 0.787358E+09 | 0.862387E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50525779.62 | 0.00 | 50525779.62 | 27133418.12 | 0.639810E+09 |
February | 52001331.61 | 0.00 | 52001331.61 | 8232978.06 | 0.612776E+09 |
March | 76530808.05 | 6343.66 | 76524464.38 | 67192772.59 | 0.570506E+09 |
April | 91443598.87 | 2079834.19 | 89363764.67 | 0.259725E+09 | 0.241830E+09 |
May | 0.113187E+09 | 12586175.42 | 0.100601E+09 | 0.409485E+09 | 0.143245E+09 |
June | 0.128735E+09 | 28319455.62 | 0.100415E+09 | 0.704452E+09 | 42448085.05 |
July | 0.111986E+09 | 15047758.00 | 96937965.00 | 0.631225E+09 | 35399044.91 |
August | 88403816.45 | 3158241.02 | 85245575.43 | 0.515852E+09 | 48852301.35 |
September | 79790893.30 | 89010.15 | 79701883.15 | 0.393662E+09 | 75289280.19 |
October | 63719742.16 | 0.00 | 63719742.16 | 0.154731E+09 | 0.363464E+09 |
November | 51377680.00 | 0.00 | 51377680.00 | 32401831.37 | 0.575607E+09 |
December | 47195746.24 | 0.00 | 47195746.24 | 11723437.42 | 0.771503E+09 |
Annual Sum or Average | 0.954897E+09 | 61286818.07 | 0.893610E+09 | 0.321582E+10 | 0.412073E+10 |
Minimum of Months | 47195746.24 | 0.00 | 47195746.24 | 8232978.06 | 35399044.91 |
Maximum of Months | 0.128735E+09 | 28319455.62 | 0.100601E+09 | 0.704452E+09 | 0.771503E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134422E+10 | 0.106816E+10 | 0.276062E+09 | 0.311315E+10 | 0.182621E+10 |
February | 0.772452E+09 | 0.517469E+09 | 0.254983E+09 | 0.142665E+10 | 0.173337E+10 |
March | 0.731963E+09 | 0.382211E+09 | 0.349751E+09 | 0.144693E+10 | 0.174932E+10 |
April | 0.648409E+09 | 0.294256E+09 | 0.354153E+09 | 0.196458E+10 | 0.813915E+09 |
May | 0.445426E+09 | 0.101948E+09 | 0.343478E+09 | 0.167037E+10 | 0.534856E+09 |
June | 0.356774E+09 | 42151662.43 | 0.314622E+09 | 0.215723E+10 | 0.164506E+09 |
July | 0.374117E+09 | 51373620.38 | 0.322743E+09 | 0.212803E+10 | 0.128914E+09 |
August | 0.474660E+09 | 0.157848E+09 | 0.316812E+09 | 0.234540E+10 | 0.170487E+09 |
September | 0.633020E+09 | 0.283007E+09 | 0.350014E+09 | 0.245041E+10 | 0.245991E+09 |
October | 0.101550E+10 | 0.706055E+09 | 0.309442E+09 | 0.268406E+10 | 0.106299E+10 |
November | 0.112605E+10 | 0.860720E+09 | 0.265328E+09 | 0.251508E+10 | 0.162406E+10 |
December | 0.124727E+10 | 0.981718E+09 | 0.265548E+09 | 0.276186E+10 | 0.214647E+10 |
Annual Sum or Average | 0.916985E+10 | 0.544691E+10 | 0.372294E+10 | 0.266637E+11 | 0.122011E+11 |
Minimum of Months | 0.356774E+09 | 42151662.43 | 0.254983E+09 | 0.142665E+10 | 0.128914E+09 |
Maximum of Months | 0.134422E+10 | 0.106816E+10 | 0.354153E+09 | 0.311315E+10 | 0.214647E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1435.93 | 671.41 | 591.95 | 470.38 | 121.57 | 0.00 | 0.00 |
February | 761.12 | 663.24 | 376.61 | 252.29 | 124.32 | 0.00 | 0.00 |
March | 717.47 | 604.27 | 322.33 | 168.31 | 154.02 | 0.00 | 0.00 |
April | 917.56 | 310.42 | 295.06 | 133.90 | 161.16 | 0.00 | 0.00 |
May | 714.32 | 204.09 | 196.15 | 44.89 | 151.26 | 0.00 | 0.00 |
June | 881.58 | 72.28 | 162.35 | 19.18 | 143.17 | 0.00 | 0.00 |
July | 856.92 | 53.78 | 164.75 | 22.62 | 142.13 | 0.00 | 0.00 |
August | 973.74 | 72.13 | 209.02 | 69.51 | 139.51 | 0.00 | 0.00 |
September | 1091.81 | 104.52 | 288.05 | 128.78 | 159.27 | 0.00 | 0.00 |
October | 1236.08 | 393.68 | 447.19 | 310.92 | 136.27 | 0.00 | 0.00 |
November | 1216.30 | 603.04 | 512.40 | 391.67 | 120.74 | 0.00 | 0.00 |
December | 1252.67 | 806.19 | 549.25 | 432.32 | 116.94 | 0.00 | 0.00 |
Annual Sum or Average | 1006.38 | 378.77 | 342.96 | 203.72 | 139.24 | 0.00 | 0.00 |
Minimum of Months | 714.32 | 53.78 | 162.35 | 19.18 | 116.94 | 0.00 | 0.00 |
Maximum of Months | 1435.93 | 806.19 | 591.95 | 470.38 | 161.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3959.18 | 2085.45 | 1666.89 | 1324.56 | 342.33 | 0.00 | 0.00 |
February | 2062.31 | 2156.39 | 1060.50 | 710.43 | 350.07 | 0.00 | 0.00 |
March | 1912.07 | 1931.30 | 907.67 | 473.96 | 433.71 | 0.00 | 0.00 |
April | 2500.13 | 1027.17 | 830.86 | 377.05 | 453.80 | 0.00 | 0.00 |
May | 1934.39 | 687.11 | 552.35 | 126.42 | 425.93 | 0.00 | 0.00 |
June | 2422.70 | 248.98 | 457.16 | 54.01 | 403.15 | 0.00 | 0.00 |
July | 2350.76 | 195.93 | 463.92 | 63.71 | 400.22 | 0.00 | 0.00 |
August | 2682.13 | 262.34 | 588.60 | 195.74 | 392.86 | 0.00 | 0.00 |
September | 3010.03 | 369.74 | 811.14 | 362.64 | 448.50 | 0.00 | 0.00 |
October | 3395.39 | 1274.68 | 1259.26 | 875.54 | 383.72 | 0.00 | 0.00 |
November | 3333.29 | 1925.83 | 1442.89 | 1102.91 | 339.99 | 0.00 | 0.00 |
December | 3453.63 | 2448.73 | 1546.66 | 1217.37 | 329.29 | 0.00 | 0.00 |
Annual Sum or Average | 2756.28 | 1213.65 | 965.76 | 573.66 | 392.09 | 0.00 | 0.00 |
Minimum of Months | 1912.07 | 195.93 | 457.16 | 54.01 | 329.29 | 0.00 | 0.00 |
Maximum of Months | 3959.18 | 2448.73 | 1666.89 | 1324.56 | 453.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5327.75 | 2829.97 | 2165.38 | 1720.68 | 444.70 | 0.00 | 0.00 |
February | 2814.42 | 2914.01 | 1377.65 | 922.90 | 454.76 | 0.00 | 0.00 |
March | 2650.72 | 2617.68 | 1179.11 | 615.70 | 563.41 | 0.00 | 0.00 |
April | 3442.92 | 1345.54 | 1079.33 | 489.81 | 589.52 | 0.00 | 0.00 |
May | 2692.23 | 897.02 | 717.53 | 164.23 | 553.30 | 0.00 | 0.00 |
June | 3360.11 | 317.09 | 593.88 | 70.16 | 523.71 | 0.00 | 0.00 |
July | 3258.24 | 244.05 | 602.66 | 82.76 | 519.90 | 0.00 | 0.00 |
August | 3690.51 | 324.99 | 764.62 | 254.27 | 510.35 | 0.00 | 0.00 |
September | 4116.49 | 462.94 | 1053.71 | 471.09 | 582.63 | 0.00 | 0.00 |
October | 4608.47 | 1684.88 | 1635.85 | 1137.37 | 498.48 | 0.00 | 0.00 |
November | 4499.83 | 2587.30 | 1874.40 | 1432.74 | 441.66 | 0.00 | 0.00 |
December | 4638.66 | 3393.38 | 2009.20 | 1581.44 | 427.77 | 0.00 | 0.00 |
Annual Sum or Average | 3765.06 | 1629.40 | 1254.57 | 745.22 | 509.35 | 0.00 | 0.00 |
Minimum of Months | 2650.72 | 244.05 | 593.88 | 70.16 | 427.77 | 0.00 | 0.00 |
Maximum of Months | 5327.75 | 3393.38 | 2165.38 | 1720.68 | 589.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 541.17 | 445.01 | 240.14 | 172.76 | 67.38 | 0.00 | 0.00 |
February | 287.93 | 450.73 | 170.95 | 98.73 | 72.22 | 0.00 | 0.00 |
March | 379.26 | 395.27 | 185.65 | 91.67 | 93.98 | 0.00 | 0.00 |
April | 731.63 | 167.85 | 238.82 | 127.88 | 110.94 | 0.00 | 0.00 |
May | 767.91 | 96.59 | 217.34 | 106.58 | 110.76 | 0.00 | 0.00 |
June | 1018.66 | 22.35 | 219.89 | 111.47 | 108.42 | 0.00 | 0.00 |
July | 863.92 | 16.19 | 171.07 | 67.22 | 103.85 | 0.00 | 0.00 |
August | 843.79 | 19.12 | 175.18 | 79.71 | 95.47 | 0.00 | 0.00 |
September | 746.20 | 30.63 | 176.76 | 75.88 | 100.88 | 0.00 | 0.00 |
October | 604.61 | 232.46 | 215.92 | 136.05 | 79.87 | 0.00 | 0.00 |
November | 485.82 | 395.52 | 221.35 | 152.29 | 69.06 | 0.00 | 0.00 |
December | 420.10 | 550.37 | 209.71 | 146.67 | 63.04 | 0.00 | 0.00 |
Annual Sum or Average | 642.67 | 234.29 | 203.72 | 114.00 | 89.72 | 0.00 | 0.00 |
Minimum of Months | 287.93 | 16.19 | 170.95 | 67.22 | 63.04 | 0.00 | 0.00 |
Maximum of Months | 1018.66 | 550.37 | 240.14 | 172.76 | 110.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 253.12 | 489.56 | 122.36 | 65.93 | 56.42 | 0.00 | 0.00 |
February | 137.51 | 482.13 | 104.39 | 41.44 | 62.96 | 0.00 | 0.00 |
March | 247.40 | 424.42 | 137.66 | 53.45 | 84.22 | 0.00 | 0.00 |
April | 611.36 | 176.09 | 202.95 | 98.18 | 104.77 | 0.00 | 0.00 |
May | 727.68 | 92.75 | 210.09 | 100.53 | 109.56 | 0.00 | 0.00 |
June | 1027.78 | 20.44 | 226.86 | 116.76 | 110.10 | 0.00 | 0.00 |
July | 856.60 | 15.56 | 170.55 | 67.04 | 103.52 | 0.00 | 0.00 |
August | 776.86 | 21.64 | 156.84 | 64.96 | 91.87 | 0.00 | 0.00 |
September | 623.19 | 35.74 | 138.51 | 46.66 | 91.84 | 0.00 | 0.00 |
October | 385.78 | 260.92 | 135.36 | 65.44 | 69.92 | 0.00 | 0.00 |
November | 243.86 | 439.31 | 122.48 | 63.34 | 59.14 | 0.00 | 0.00 |
December | 169.37 | 597.01 | 100.53 | 48.49 | 52.03 | 0.00 | 0.00 |
Annual Sum or Average | 506.73 | 253.71 | 152.55 | 69.45 | 83.10 | 0.00 | 0.00 |
Minimum of Months | 137.51 | 15.56 | 100.53 | 41.44 | 52.03 | 0.00 | 0.00 |
Maximum of Months | 1027.78 | 597.01 | 226.86 | 116.76 | 110.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 231.51 | 176.88 | 107.52 | 85.44 | 22.08 | 0.00 | 0.00 |
February | 114.67 | 185.60 | 68.41 | 45.83 | 22.58 | 0.00 | 0.00 |
March | 103.04 | 167.31 | 58.55 | 30.57 | 27.98 | 0.00 | 0.00 |
April | 144.13 | 91.89 | 53.60 | 24.32 | 29.27 | 0.00 | 0.00 |
May | 110.90 | 64.25 | 35.63 | 8.15 | 27.47 | 0.00 | 0.00 |
June | 145.01 | 26.54 | 29.49 | 3.48 | 26.01 | 0.00 | 0.00 |
July | 136.64 | 22.76 | 29.93 | 4.11 | 25.82 | 0.00 | 0.00 |
August | 158.76 | 30.36 | 37.97 | 12.63 | 25.34 | 0.00 | 0.00 |
September | 176.67 | 40.46 | 52.32 | 23.39 | 28.93 | 0.00 | 0.00 |
October | 196.22 | 111.86 | 81.23 | 56.48 | 24.75 | 0.00 | 0.00 |
November | 192.36 | 165.06 | 93.07 | 71.14 | 21.93 | 0.00 | 0.00 |
December | 202.72 | 205.95 | 99.77 | 78.53 | 21.24 | 0.00 | 0.00 |
Annual Sum or Average | 159.70 | 107.06 | 62.30 | 37.00 | 25.29 | 0.00 | 0.00 |
Minimum of Months | 103.04 | 22.76 | 29.49 | 3.48 | 21.24 | 0.00 | 0.00 |
Maximum of Months | 231.51 | 205.95 | 107.52 | 85.44 | 29.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.66 | 139.63 | 13.32 | 0.00 | 13.32 | 0.00 | 0.00 |
February | 7.05 | 142.74 | 15.18 | 0.00 | 15.18 | 0.00 | 0.00 |
March | 27.84 | 123.56 | 20.18 | 0.00 | 20.17 | 0.00 | 0.00 |
April | 89.87 | 46.57 | 24.91 | 0.57 | 24.35 | 0.00 | 0.00 |
May | 130.87 | 22.76 | 29.84 | 3.32 | 26.52 | 0.00 | 0.00 |
June | 223.45 | 4.57 | 35.07 | 7.71 | 27.36 | 0.00 | 0.00 |
July | 201.96 | 3.72 | 29.52 | 3.97 | 25.56 | 0.00 | 0.00 |
August | 167.54 | 5.19 | 23.31 | 0.83 | 22.47 | 0.00 | 0.00 |
September | 133.45 | 8.85 | 21.74 | 0.02 | 21.71 | 0.00 | 0.00 |
October | 55.28 | 73.91 | 16.80 | 0.00 | 16.80 | 0.00 | 0.00 |
November | 16.35 | 126.47 | 14.00 | 0.00 | 14.00 | 0.00 | 0.00 |
December | 7.85 | 174.41 | 12.44 | 0.00 | 12.44 | 0.00 | 0.00 |
Annual Sum or Average | 90.16 | 72.41 | 21.38 | 1.37 | 20.01 | 0.00 | 0.00 |
Minimum of Months | 7.05 | 3.72 | 12.44 | 0.00 | 12.44 | 0.00 | 0.00 |
Maximum of Months | 223.45 | 174.41 | 35.07 | 7.71 | 27.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 499.55 | 423.86 | 235.32 | 170.30 | 65.02 | 0.00 | 0.00 |
February | 308.63 | 434.73 | 185.01 | 114.36 | 70.65 | 0.00 | 0.00 |
March | 381.30 | 372.43 | 196.40 | 101.20 | 95.20 | 0.00 | 0.00 |
April | 727.81 | 146.68 | 242.18 | 134.15 | 108.03 | 0.00 | 0.00 |
May | 791.59 | 82.81 | 226.57 | 117.62 | 108.96 | 0.00 | 0.00 |
June | 1054.53 | 19.09 | 226.38 | 121.57 | 104.81 | 0.00 | 0.00 |
July | 953.25 | 14.78 | 197.87 | 95.23 | 102.64 | 0.00 | 0.00 |
August | 913.84 | 18.25 | 199.68 | 102.24 | 97.43 | 0.00 | 0.00 |
September | 780.26 | 28.30 | 190.43 | 89.19 | 101.24 | 0.00 | 0.00 |
October | 621.81 | 220.02 | 227.03 | 146.67 | 80.36 | 0.00 | 0.00 |
November | 439.76 | 377.56 | 213.53 | 147.30 | 66.23 | 0.00 | 0.00 |
December | 404.45 | 528.50 | 214.00 | 152.40 | 61.60 | 0.00 | 0.00 |
Annual Sum or Average | 658.22 | 221.37 | 213.04 | 124.45 | 88.59 | 0.00 | 0.00 |
Minimum of Months | 308.63 | 14.78 | 185.01 | 89.19 | 61.60 | 0.00 | 0.00 |
Maximum of Months | 1054.53 | 528.50 | 242.18 | 170.30 | 108.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 186.06 | 437.56 | 117.54 | 63.48 | 54.06 | 0.00 | 0.00 |
February | 143.34 | 449.25 | 118.45 | 57.06 | 61.38 | 0.00 | 0.00 |
March | 246.80 | 391.51 | 148.41 | 62.98 | 85.43 | 0.00 | 0.00 |
April | 598.69 | 153.26 | 206.31 | 104.45 | 101.86 | 0.00 | 0.00 |
May | 741.34 | 83.63 | 219.32 | 111.57 | 107.76 | 0.00 | 0.00 |
June | 1060.13 | 19.20 | 233.34 | 126.85 | 106.49 | 0.00 | 0.00 |
July | 944.26 | 14.84 | 197.36 | 95.05 | 102.30 | 0.00 | 0.00 |
August | 843.54 | 20.65 | 181.34 | 87.50 | 93.84 | 0.00 | 0.00 |
September | 650.61 | 31.79 | 152.18 | 59.97 | 92.21 | 0.00 | 0.00 |
October | 389.50 | 235.89 | 146.46 | 76.06 | 70.40 | 0.00 | 0.00 |
November | 177.72 | 397.92 | 114.66 | 58.35 | 56.31 | 0.00 | 0.00 |
December | 125.59 | 543.95 | 104.81 | 54.22 | 50.59 | 0.00 | 0.00 |
Annual Sum or Average | 510.73 | 230.72 | 161.87 | 79.90 | 81.98 | 0.00 | 0.00 |
Minimum of Months | 125.59 | 14.84 | 104.81 | 54.22 | 50.59 | 0.00 | 0.00 |
Maximum of Months | 1060.13 | 543.95 | 233.34 | 126.85 | 107.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 541.85 | 657.00 | 261.83 | 185.13 | 76.70 | 0.00 | 0.00 |
February | 259.10 | 696.36 | 181.10 | 99.29 | 81.81 | 0.00 | 0.00 |
March | 300.57 | 617.34 | 170.57 | 66.25 | 104.32 | 0.00 | 0.00 |
April | 539.65 | 279.13 | 170.09 | 53.93 | 116.17 | 0.00 | 0.00 |
May | 554.24 | 164.29 | 141.84 | 24.86 | 116.99 | 0.00 | 0.00 |
June | 836.28 | 47.91 | 139.87 | 24.26 | 115.61 | 0.00 | 0.00 |
July | 767.05 | 37.05 | 128.80 | 17.50 | 111.30 | 0.00 | 0.00 |
August | 737.33 | 50.60 | 132.76 | 29.16 | 103.59 | 0.00 | 0.00 |
September | 707.17 | 79.93 | 160.46 | 50.74 | 109.72 | 0.00 | 0.00 |
October | 571.44 | 373.32 | 212.39 | 122.37 | 90.02 | 0.00 | 0.00 |
November | 458.35 | 598.69 | 231.99 | 154.15 | 77.84 | 0.00 | 0.00 |
December | 444.51 | 796.81 | 243.13 | 170.15 | 72.98 | 0.00 | 0.00 |
Annual Sum or Average | 561.44 | 365.09 | 181.30 | 83.15 | 98.15 | 0.00 | 0.00 |
Minimum of Months | 259.10 | 37.05 | 128.80 | 17.50 | 72.98 | 0.00 | 0.00 |
Maximum of Months | 836.28 | 796.81 | 261.83 | 185.13 | 116.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 527.39 | 436.91 | 240.14 | 172.76 | 67.38 | 0.00 | 0.00 |
February | 277.74 | 436.98 | 170.95 | 98.73 | 72.22 | 0.00 | 0.00 |
March | 364.09 | 388.41 | 185.65 | 91.67 | 93.98 | 0.00 | 0.00 |
April | 706.38 | 161.66 | 238.82 | 127.88 | 110.94 | 0.00 | 0.00 |
May | 747.16 | 91.46 | 217.34 | 106.58 | 110.76 | 0.00 | 0.00 |
June | 1001.04 | 20.06 | 219.89 | 111.47 | 108.42 | 0.00 | 0.00 |
July | 851.03 | 15.19 | 171.07 | 67.22 | 103.85 | 0.00 | 0.00 |
August | 831.16 | 17.76 | 175.18 | 79.71 | 95.47 | 0.00 | 0.00 |
September | 732.63 | 27.95 | 176.76 | 75.88 | 100.88 | 0.00 | 0.00 |
October | 587.69 | 225.05 | 215.92 | 136.05 | 79.87 | 0.00 | 0.00 |
November | 471.60 | 387.36 | 221.35 | 152.29 | 69.06 | 0.00 | 0.00 |
December | 412.39 | 539.68 | 209.71 | 146.67 | 63.04 | 0.00 | 0.00 |
Annual Sum or Average | 627.60 | 228.20 | 203.72 | 114.00 | 89.72 | 0.00 | 0.00 |
Minimum of Months | 277.74 | 15.19 | 170.95 | 67.22 | 63.04 | 0.00 | 0.00 |
Maximum of Months | 1001.04 | 539.68 | 240.14 | 172.76 | 110.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 246.22 | 476.77 | 122.36 | 65.93 | 56.42 | 0.00 | 0.00 |
February | 131.39 | 465.43 | 104.39 | 41.44 | 62.96 | 0.00 | 0.00 |
March | 235.88 | 417.81 | 137.66 | 53.45 | 84.22 | 0.00 | 0.00 |
April | 590.05 | 170.25 | 202.95 | 98.18 | 104.77 | 0.00 | 0.00 |
May | 708.85 | 87.40 | 210.09 | 100.53 | 109.56 | 0.00 | 0.00 |
June | 1009.82 | 18.42 | 226.86 | 116.76 | 110.10 | 0.00 | 0.00 |
July | 843.80 | 14.60 | 170.55 | 67.04 | 103.52 | 0.00 | 0.00 |
August | 765.73 | 20.27 | 156.84 | 64.96 | 91.87 | 0.00 | 0.00 |
September | 613.02 | 32.77 | 138.51 | 46.66 | 91.84 | 0.00 | 0.00 |
October | 375.59 | 252.05 | 135.36 | 65.44 | 69.92 | 0.00 | 0.00 |
November | 236.01 | 427.57 | 122.48 | 63.34 | 59.14 | 0.00 | 0.00 |
December | 166.13 | 581.18 | 100.53 | 48.49 | 52.03 | 0.00 | 0.00 |
Annual Sum or Average | 495.22 | 246.18 | 152.55 | 69.45 | 83.10 | 0.00 | 0.00 |
Minimum of Months | 131.39 | 14.60 | 100.53 | 41.44 | 52.03 | 0.00 | 0.00 |
Maximum of Months | 1009.82 | 581.18 | 226.86 | 116.76 | 110.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 461.89 | 225.22 | 197.16 | 156.67 | 40.49 | 0.00 | 0.00 |
February | 238.92 | 228.33 | 125.43 | 84.03 | 41.41 | 0.00 | 0.00 |
March | 225.74 | 204.64 | 107.36 | 56.06 | 51.30 | 0.00 | 0.00 |
April | 320.36 | 82.85 | 98.27 | 44.60 | 53.68 | 0.00 | 0.00 |
May | 276.82 | 45.92 | 65.33 | 14.95 | 50.38 | 0.00 | 0.00 |
June | 374.25 | 9.47 | 54.07 | 6.39 | 47.68 | 0.00 | 0.00 |
July | 364.10 | 7.59 | 54.87 | 7.53 | 47.34 | 0.00 | 0.00 |
August | 388.33 | 8.82 | 69.62 | 23.15 | 46.47 | 0.00 | 0.00 |
September | 406.57 | 13.96 | 95.94 | 42.89 | 53.05 | 0.00 | 0.00 |
October | 410.18 | 115.29 | 148.94 | 103.56 | 45.39 | 0.00 | 0.00 |
November | 389.25 | 199.29 | 170.66 | 130.45 | 40.21 | 0.00 | 0.00 |
December | 406.66 | 279.18 | 182.94 | 143.99 | 38.95 | 0.00 | 0.00 |
Annual Sum or Average | 356.02 | 117.94 | 114.23 | 67.85 | 46.38 | 0.00 | 0.00 |
Minimum of Months | 225.74 | 7.59 | 54.07 | 6.39 | 38.95 | 0.00 | 0.00 |
Maximum of Months | 461.89 | 279.18 | 197.16 | 156.67 | 53.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 69.85 | 1540.02 | 116.53 | 0.00 | 116.53 | 0.00 | 0.00 |
February | 22.38 | 1633.79 | 132.79 | 0.00 | 132.79 | 0.00 | 0.00 |
March | 150.66 | 1396.19 | 176.51 | 0.01 | 176.50 | 0.00 | 0.00 |
April | 580.19 | 636.92 | 217.94 | 4.96 | 212.98 | 0.00 | 0.00 |
May | 877.20 | 379.81 | 261.06 | 29.03 | 232.03 | 0.00 | 0.00 |
June | 1581.51 | 127.91 | 306.82 | 67.49 | 239.32 | 0.00 | 0.00 |
July | 1359.73 | 110.72 | 258.29 | 34.71 | 223.58 | 0.00 | 0.00 |
August | 1113.26 | 153.74 | 203.90 | 7.28 | 196.61 | 0.00 | 0.00 |
September | 878.62 | 232.08 | 190.17 | 0.21 | 189.96 | 0.00 | 0.00 |
October | 340.68 | 898.03 | 146.97 | 0.00 | 146.97 | 0.00 | 0.00 |
November | 80.53 | 1432.55 | 122.45 | 0.00 | 122.45 | 0.00 | 0.00 |
December | 30.58 | 1857.46 | 108.85 | 0.00 | 108.85 | 0.00 | 0.00 |
Annual Sum or Average | 593.02 | 863.14 | 187.05 | 12.01 | 175.05 | 0.00 | 0.00 |
Minimum of Months | 22.38 | 110.72 | 108.85 | 0.00 | 108.85 | 0.00 | 0.00 |
Maximum of Months | 1581.51 | 1857.46 | 306.82 | 67.49 | 239.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 58.92 | 1589.60 | 116.53 | 0.00 | 116.53 | 0.00 | 0.00 |
February | 17.47 | 1694.16 | 132.79 | 0.00 | 132.79 | 0.00 | 0.00 |
March | 136.87 | 1439.77 | 176.51 | 0.01 | 176.50 | 0.00 | 0.00 |
April | 562.44 | 654.81 | 217.94 | 4.96 | 212.98 | 0.00 | 0.00 |
May | 857.90 | 391.15 | 261.06 | 29.03 | 232.03 | 0.00 | 0.00 |
June | 1560.31 | 133.24 | 306.82 | 67.49 | 239.32 | 0.00 | 0.00 |
July | 1338.29 | 116.41 | 258.29 | 34.71 | 223.58 | 0.00 | 0.00 |
August | 1093.81 | 162.13 | 203.90 | 7.28 | 196.61 | 0.00 | 0.00 |
September | 859.58 | 243.62 | 190.17 | 0.21 | 189.96 | 0.00 | 0.00 |
October | 325.34 | 926.77 | 146.97 | 0.00 | 146.97 | 0.00 | 0.00 |
November | 70.59 | 1479.64 | 122.45 | 0.00 | 122.45 | 0.00 | 0.00 |
December | 24.08 | 1920.10 | 108.85 | 0.00 | 108.85 | 0.00 | 0.00 |
Annual Sum or Average | 578.00 | 892.33 | 187.05 | 12.01 | 175.05 | 0.00 | 0.00 |
Minimum of Months | 17.47 | 116.41 | 108.85 | 0.00 | 108.85 | 0.00 | 0.00 |
Maximum of Months | 1560.31 | 1920.10 | 306.82 | 67.49 | 239.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 421.47 | 1341.16 | 352.84 | 233.77 | 119.08 | 0.00 | 0.00 |
February | 257.19 | 1483.19 | 303.44 | 171.42 | 132.03 | 0.00 | 0.00 |
March | 362.34 | 1279.05 | 344.80 | 164.18 | 180.62 | 0.00 | 0.00 |
April | 967.19 | 611.71 | 448.47 | 238.58 | 209.89 | 0.00 | 0.00 |
May | 1131.98 | 421.77 | 445.87 | 229.17 | 216.70 | 0.00 | 0.00 |
June | 1603.77 | 170.79 | 459.70 | 248.40 | 211.29 | 0.00 | 0.00 |
July | 1367.15 | 169.04 | 395.21 | 190.27 | 204.93 | 0.00 | 0.00 |
August | 1302.15 | 237.18 | 380.99 | 189.73 | 191.26 | 0.00 | 0.00 |
September | 1010.48 | 309.10 | 342.59 | 149.15 | 193.44 | 0.00 | 0.00 |
October | 700.13 | 844.25 | 373.47 | 222.72 | 150.75 | 0.00 | 0.00 |
November | 368.30 | 1273.29 | 328.18 | 205.64 | 122.54 | 0.00 | 0.00 |
December | 298.72 | 1571.43 | 318.80 | 206.61 | 112.18 | 0.00 | 0.00 |
Annual Sum or Average | 818.62 | 806.18 | 374.89 | 204.34 | 170.56 | 0.00 | 0.00 |
Minimum of Months | 257.19 | 169.04 | 303.44 | 149.15 | 112.18 | 0.00 | 0.00 |
Maximum of Months | 1603.77 | 1571.43 | 459.70 | 248.40 | 216.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1132.50 | 1136.46 | 541.82 | 398.80 | 143.02 | 0.00 | 0.00 |
February | 544.50 | 1200.48 | 364.82 | 213.90 | 150.92 | 0.00 | 0.00 |
March | 575.46 | 1086.30 | 333.79 | 142.71 | 191.09 | 0.00 | 0.00 |
April | 969.29 | 510.74 | 324.87 | 115.22 | 209.64 | 0.00 | 0.00 |
May | 942.70 | 308.25 | 255.79 | 48.01 | 207.78 | 0.00 | 0.00 |
June | 1402.76 | 93.10 | 242.82 | 39.40 | 203.42 | 0.00 | 0.00 |
July | 1291.46 | 73.99 | 228.22 | 31.08 | 197.14 | 0.00 | 0.00 |
August | 1282.51 | 101.26 | 247.11 | 61.43 | 185.68 | 0.00 | 0.00 |
September | 1266.78 | 156.20 | 309.41 | 109.26 | 200.15 | 0.00 | 0.00 |
October | 1103.80 | 663.60 | 429.52 | 263.61 | 165.91 | 0.00 | 0.00 |
November | 945.55 | 1045.60 | 476.41 | 332.07 | 144.34 | 0.00 | 0.00 |
December | 967.59 | 1338.58 | 502.99 | 366.53 | 136.46 | 0.00 | 0.00 |
Annual Sum or Average | 1038.23 | 640.39 | 354.90 | 176.84 | 178.06 | 0.00 | 0.00 |
Minimum of Months | 544.50 | 73.99 | 228.22 | 31.08 | 136.46 | 0.00 | 0.00 |
Maximum of Months | 1402.76 | 1338.58 | 541.82 | 398.80 | 209.64 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.384598E+10 | 0.179830E+10 | 0.158548E+10 | 0.125987E+10 | 0.325609E+09 | 0.00 | 0.00 |
February | 0.184130E+10 | 0.160451E+10 | 0.911090E+09 | 0.610343E+09 | 0.300747E+09 | 0.00 | 0.00 |
March | 0.192166E+10 | 0.161848E+10 | 0.863334E+09 | 0.450810E+09 | 0.412524E+09 | 0.00 | 0.00 |
April | 0.237831E+10 | 0.804608E+09 | 0.764784E+09 | 0.347069E+09 | 0.417715E+09 | 0.00 | 0.00 |
May | 0.191325E+10 | 0.546631E+09 | 0.525370E+09 | 0.120245E+09 | 0.405124E+09 | 0.00 | 0.00 |
June | 0.228506E+10 | 0.187340E+09 | 0.420807E+09 | 49716938.98 | 0.371090E+09 | 0.00 | 0.00 |
July | 0.229518E+10 | 0.144041E+09 | 0.441262E+09 | 60594031.24 | 0.380668E+09 | 0.00 | 0.00 |
August | 0.260808E+10 | 0.193201E+09 | 0.559851E+09 | 0.186178E+09 | 0.373673E+09 | 0.00 | 0.00 |
September | 0.282996E+10 | 0.270923E+09 | 0.746633E+09 | 0.333800E+09 | 0.412833E+09 | 0.00 | 0.00 |
October | 0.331072E+10 | 0.105443E+10 | 0.119776E+10 | 0.832776E+09 | 0.364980E+09 | 0.00 | 0.00 |
November | 0.315265E+10 | 0.156308E+10 | 0.132815E+10 | 0.101520E+10 | 0.312949E+09 | 0.00 | 0.00 |
December | 0.335515E+10 | 0.215931E+10 | 0.147112E+10 | 0.115791E+10 | 0.313208E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.317373E+11 | 0.119448E+11 | 0.108156E+11 | 0.642451E+10 | 0.439112E+10 | 0.00 | 0.00 |
Minimum of Months | 0.184130E+10 | 0.144041E+09 | 0.420807E+09 | 49716938.98 | 0.300747E+09 | 0.00 | 0.00 |
Maximum of Months | 0.384598E+10 | 0.215931E+10 | 0.158548E+10 | 0.125987E+10 | 0.417715E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106043E+11 | 0.558568E+10 | 0.446460E+10 | 0.354770E+10 | 0.916894E+09 | 0.00 | 0.00 |
February | 0.498915E+10 | 0.521675E+10 | 0.256557E+10 | 0.171868E+10 | 0.846884E+09 | 0.00 | 0.00 |
March | 0.512128E+10 | 0.517279E+10 | 0.243109E+10 | 0.126945E+10 | 0.116164E+10 | 0.00 | 0.00 |
April | 0.648033E+10 | 0.266243E+10 | 0.215358E+10 | 0.977322E+09 | 0.117626E+10 | 0.00 | 0.00 |
May | 0.518106E+10 | 0.184035E+10 | 0.147941E+10 | 0.338603E+09 | 0.114080E+10 | 0.00 | 0.00 |
June | 0.627964E+10 | 0.645357E+09 | 0.118496E+10 | 0.140000E+09 | 0.104496E+10 | 0.00 | 0.00 |
July | 0.629629E+10 | 0.524775E+09 | 0.124257E+10 | 0.170629E+09 | 0.107194E+10 | 0.00 | 0.00 |
August | 0.718381E+10 | 0.702642E+09 | 0.157650E+10 | 0.524264E+09 | 0.105224E+10 | 0.00 | 0.00 |
September | 0.780201E+10 | 0.958365E+09 | 0.210247E+10 | 0.939959E+09 | 0.116251E+10 | 0.00 | 0.00 |
October | 0.909420E+10 | 0.341410E+10 | 0.337280E+10 | 0.234504E+10 | 0.102776E+10 | 0.00 | 0.00 |
November | 0.863989E+10 | 0.499176E+10 | 0.373998E+10 | 0.285874E+10 | 0.881242E+09 | 0.00 | 0.00 |
December | 0.925019E+10 | 0.655868E+10 | 0.414258E+10 | 0.326061E+10 | 0.881974E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.869221E+11 | 0.382737E+11 | 0.304561E+11 | 0.180910E+11 | 0.123651E+11 | 0.00 | 0.00 |
Minimum of Months | 0.498915E+10 | 0.524775E+09 | 0.118496E+10 | 0.140000E+09 | 0.846884E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106043E+11 | 0.655868E+10 | 0.446460E+10 | 0.354770E+10 | 0.117626E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142698E+11 | 0.757979E+10 | 0.579976E+10 | 0.460867E+10 | 0.119110E+10 | 0.00 | 0.00 |
February | 0.680864E+10 | 0.704957E+10 | 0.333282E+10 | 0.223267E+10 | 0.110015E+10 | 0.00 | 0.00 |
March | 0.709968E+10 | 0.701119E+10 | 0.315812E+10 | 0.164909E+10 | 0.150904E+10 | 0.00 | 0.00 |
April | 0.892404E+10 | 0.348764E+10 | 0.279762E+10 | 0.126960E+10 | 0.152803E+10 | 0.00 | 0.00 |
May | 0.721088E+10 | 0.240259E+10 | 0.192183E+10 | 0.439865E+09 | 0.148197E+10 | 0.00 | 0.00 |
June | 0.870940E+10 | 0.821909E+09 | 0.153934E+10 | 0.181867E+09 | 0.135747E+10 | 0.00 | 0.00 |
July | 0.872688E+10 | 0.653655E+09 | 0.161416E+10 | 0.221657E+09 | 0.139251E+10 | 0.00 | 0.00 |
August | 0.988467E+10 | 0.870440E+09 | 0.204797E+10 | 0.681049E+09 | 0.136692E+10 | 0.00 | 0.00 |
September | 0.106700E+11 | 0.119995E+10 | 0.273123E+10 | 0.122106E+10 | 0.151017E+10 | 0.00 | 0.00 |
October | 0.123433E+11 | 0.451279E+10 | 0.438146E+10 | 0.304634E+10 | 0.133512E+10 | 0.00 | 0.00 |
November | 0.116636E+11 | 0.670629E+10 | 0.485845E+10 | 0.371366E+10 | 0.114478E+10 | 0.00 | 0.00 |
December | 0.124242E+11 | 0.908883E+10 | 0.538145E+10 | 0.423572E+10 | 0.114573E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.118735E+12 | 0.513846E+11 | 0.395642E+11 | 0.235012E+11 | 0.160630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.680864E+10 | 0.653655E+09 | 0.153934E+10 | 0.181867E+09 | 0.110015E+10 | 0.00 | 0.00 |
Maximum of Months | 0.142698E+11 | 0.908883E+10 | 0.579976E+10 | 0.460867E+10 | 0.152803E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144948E+10 | 0.119190E+10 | 0.643189E+09 | 0.462713E+09 | 0.180476E+09 | 0.00 | 0.00 |
February | 0.696563E+09 | 0.109040E+10 | 0.413565E+09 | 0.238856E+09 | 0.174709E+09 | 0.00 | 0.00 |
March | 0.101580E+10 | 0.105868E+10 | 0.497241E+09 | 0.245529E+09 | 0.251712E+09 | 0.00 | 0.00 |
April | 0.189637E+10 | 0.435060E+09 | 0.619032E+09 | 0.331475E+09 | 0.287557E+09 | 0.00 | 0.00 |
May | 0.205677E+10 | 0.258720E+09 | 0.582124E+09 | 0.285464E+09 | 0.296661E+09 | 0.00 | 0.00 |
June | 0.264036E+10 | 57930631.60 | 0.569960E+09 | 0.288929E+09 | 0.281031E+09 | 0.00 | 0.00 |
July | 0.231393E+10 | 43368137.79 | 0.458193E+09 | 0.180036E+09 | 0.278157E+09 | 0.00 | 0.00 |
August | 0.226000E+10 | 51219347.14 | 0.469194E+09 | 0.213489E+09 | 0.255704E+09 | 0.00 | 0.00 |
September | 0.193416E+10 | 79392778.34 | 0.458152E+09 | 0.196677E+09 | 0.261475E+09 | 0.00 | 0.00 |
October | 0.161939E+10 | 0.622630E+09 | 0.578321E+09 | 0.364388E+09 | 0.213933E+09 | 0.00 | 0.00 |
November | 0.125925E+10 | 0.102518E+10 | 0.573750E+09 | 0.394734E+09 | 0.179016E+09 | 0.00 | 0.00 |
December | 0.112519E+10 | 0.147410E+10 | 0.561690E+09 | 0.392847E+09 | 0.168843E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.202673E+11 | 0.738858E+10 | 0.642441E+10 | 0.359514E+10 | 0.282927E+10 | 0.00 | 0.00 |
Minimum of Months | 0.696563E+09 | 43368137.79 | 0.413565E+09 | 0.180036E+09 | 0.168843E+09 | 0.00 | 0.00 |
Maximum of Months | 0.264036E+10 | 0.147410E+10 | 0.643189E+09 | 0.462713E+09 | 0.296661E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.677945E+09 | 0.131125E+10 | 0.327718E+09 | 0.176597E+09 | 0.151121E+09 | 0.00 | 0.00 |
February | 0.332665E+09 | 0.116638E+10 | 0.252550E+09 | 0.100247E+09 | 0.152302E+09 | 0.00 | 0.00 |
March | 0.662631E+09 | 0.113677E+10 | 0.368720E+09 | 0.143155E+09 | 0.225564E+09 | 0.00 | 0.00 |
April | 0.158465E+10 | 0.456436E+09 | 0.526053E+09 | 0.254491E+09 | 0.271562E+09 | 0.00 | 0.00 |
May | 0.194903E+10 | 0.248420E+09 | 0.562706E+09 | 0.269264E+09 | 0.293442E+09 | 0.00 | 0.00 |
June | 0.266400E+10 | 52980744.29 | 0.588009E+09 | 0.302631E+09 | 0.285377E+09 | 0.00 | 0.00 |
July | 0.229431E+10 | 41668326.24 | 0.456814E+09 | 0.179555E+09 | 0.277259E+09 | 0.00 | 0.00 |
August | 0.208074E+10 | 57971090.15 | 0.420072E+09 | 0.173996E+09 | 0.246076E+09 | 0.00 | 0.00 |
September | 0.161531E+10 | 92630537.72 | 0.359010E+09 | 0.120949E+09 | 0.238061E+09 | 0.00 | 0.00 |
October | 0.103328E+10 | 0.698843E+09 | 0.362546E+09 | 0.175264E+09 | 0.187281E+09 | 0.00 | 0.00 |
November | 0.632086E+09 | 0.113869E+10 | 0.317470E+09 | 0.164182E+09 | 0.153288E+09 | 0.00 | 0.00 |
December | 0.453648E+09 | 0.159903E+10 | 0.269250E+09 | 0.129885E+09 | 0.139365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.159803E+11 | 0.800107E+10 | 0.481092E+10 | 0.219022E+10 | 0.262070E+10 | 0.00 | 0.00 |
Minimum of Months | 0.332665E+09 | 41668326.24 | 0.252550E+09 | 0.100247E+09 | 0.139365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.266400E+10 | 0.159903E+10 | 0.588009E+09 | 0.302631E+09 | 0.293442E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.620081E+09 | 0.473752E+09 | 0.287992E+09 | 0.228847E+09 | 59144960.60 | 0.00 | 0.00 |
February | 0.277407E+09 | 0.448997E+09 | 0.165494E+09 | 0.110865E+09 | 54628920.46 | 0.00 | 0.00 |
March | 0.275973E+09 | 0.448136E+09 | 0.156819E+09 | 81886934.78 | 74932507.33 | 0.00 | 0.00 |
April | 0.373588E+09 | 0.238176E+09 | 0.138918E+09 | 63042967.39 | 75875509.68 | 0.00 | 0.00 |
May | 0.297030E+09 | 0.172086E+09 | 95430285.85 | 21841870.36 | 73588415.50 | 0.00 | 0.00 |
June | 0.375859E+09 | 68789687.65 | 76437064.93 | 9030788.63 | 67406276.30 | 0.00 | 0.00 |
July | 0.365987E+09 | 60951989.81 | 80152681.12 | 11006548.27 | 69146132.85 | 0.00 | 0.00 |
August | 0.425215E+09 | 81314043.99 | 0.101694E+09 | 33818094.03 | 67875458.52 | 0.00 | 0.00 |
September | 0.457923E+09 | 0.104871E+09 | 0.135622E+09 | 60632800.40 | 74988705.62 | 0.00 | 0.00 |
October | 0.525558E+09 | 0.299598E+09 | 0.217565E+09 | 0.151269E+09 | 66296518.94 | 0.00 | 0.00 |
November | 0.498604E+09 | 0.427830E+09 | 0.241250E+09 | 0.184405E+09 | 56845254.86 | 0.00 | 0.00 |
December | 0.542963E+09 | 0.551622E+09 | 0.267221E+09 | 0.210328E+09 | 56892422.94 | 0.00 | 0.00 |
Annual Sum or Average | 0.503619E+10 | 0.337612E+10 | 0.196460E+10 | 0.116697E+10 | 0.797621E+09 | 0.00 | 0.00 |
Minimum of Months | 0.275973E+09 | 60951989.81 | 76437064.93 | 9030788.63 | 54628920.46 | 0.00 | 0.00 |
Maximum of Months | 0.620081E+09 | 0.551622E+09 | 0.287992E+09 | 0.228847E+09 | 75875509.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 41930440.84 | 0.373995E+09 | 35677773.26 | 0.00 | 35677773.26 | 0.00 | 0.00 |
February | 17057357.97 | 0.345320E+09 | 36719704.92 | 0.00 | 36719704.92 | 0.00 | 0.00 |
March | 74559193.61 | 0.330956E+09 | 54040706.29 | 4479.45 | 54036226.84 | 0.00 | 0.00 |
April | 0.232933E+09 | 0.120715E+09 | 64571076.60 | 1468633.50 | 63102443.09 | 0.00 | 0.00 |
May | 0.350520E+09 | 60949154.01 | 79925002.18 | 8887477.17 | 71037525.00 | 0.00 | 0.00 |
June | 0.579172E+09 | 11846194.42 | 90903404.92 | 19997219.71 | 70906185.21 | 0.00 | 0.00 |
July | 0.540933E+09 | 9975190.62 | 79076488.54 | 10625674.70 | 68450813.84 | 0.00 | 0.00 |
August | 0.448735E+09 | 13898591.03 | 62424594.77 | 2230129.01 | 60194465.76 | 0.00 | 0.00 |
September | 0.345902E+09 | 22937531.07 | 56342750.58 | 62852.75 | 56279897.84 | 0.00 | 0.00 |
October | 0.148059E+09 | 0.197950E+09 | 44994427.20 | 0.00 | 44994427.20 | 0.00 | 0.00 |
November | 42383278.56 | 0.327823E+09 | 36279325.75 | 0.00 | 36279325.75 | 0.00 | 0.00 |
December | 21037758.13 | 0.467130E+09 | 33326336.49 | 0.00 | 33326336.49 | 0.00 | 0.00 |
Annual Sum or Average | 0.284322E+10 | 0.228350E+10 | 0.674282E+09 | 43276466.30 | 0.631005E+09 | 0.00 | 0.00 |
Minimum of Months | 17057357.97 | 9975190.62 | 33326336.49 | 0.00 | 33326336.49 | 0.00 | 0.00 |
Maximum of Months | 0.579172E+09 | 0.467130E+09 | 90903404.92 | 19997219.71 | 71037525.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133799E+10 | 0.113526E+10 | 0.630284E+09 | 0.456129E+09 | 0.174155E+09 | 0.00 | 0.00 |
February | 0.746631E+09 | 0.105169E+10 | 0.447568E+09 | 0.276660E+09 | 0.170908E+09 | 0.00 | 0.00 |
March | 0.102128E+10 | 0.997512E+09 | 0.526035E+09 | 0.271063E+09 | 0.254971E+09 | 0.00 | 0.00 |
April | 0.188647E+10 | 0.380198E+09 | 0.627741E+09 | 0.347717E+09 | 0.280024E+09 | 0.00 | 0.00 |
May | 0.212018E+10 | 0.221793E+09 | 0.606854E+09 | 0.315020E+09 | 0.291834E+09 | 0.00 | 0.00 |
June | 0.273334E+10 | 49473461.96 | 0.586779E+09 | 0.315101E+09 | 0.271678E+09 | 0.00 | 0.00 |
July | 0.255319E+10 | 39594648.69 | 0.529980E+09 | 0.255071E+09 | 0.274909E+09 | 0.00 | 0.00 |
August | 0.244762E+10 | 48884044.46 | 0.534817E+09 | 0.273850E+09 | 0.260967E+09 | 0.00 | 0.00 |
September | 0.202245E+10 | 73364689.38 | 0.493586E+09 | 0.231171E+09 | 0.262414E+09 | 0.00 | 0.00 |
October | 0.166545E+10 | 0.589306E+09 | 0.608066E+09 | 0.392842E+09 | 0.215224E+09 | 0.00 | 0.00 |
November | 0.113986E+10 | 0.978635E+09 | 0.553478E+09 | 0.381797E+09 | 0.171681E+09 | 0.00 | 0.00 |
December | 0.108327E+10 | 0.141553E+10 | 0.573169E+09 | 0.408186E+09 | 0.164983E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.207577E+11 | 0.698124E+10 | 0.671836E+10 | 0.392461E+10 | 0.279375E+10 | 0.00 | 0.00 |
Minimum of Months | 0.746631E+09 | 39594648.69 | 0.447568E+09 | 0.231171E+09 | 0.164983E+09 | 0.00 | 0.00 |
Maximum of Months | 0.273334E+10 | 0.141553E+10 | 0.630284E+09 | 0.456129E+09 | 0.291834E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.498345E+09 | 0.117196E+10 | 0.314813E+09 | 0.170013E+09 | 0.144800E+09 | 0.00 | 0.00 |
February | 0.346769E+09 | 0.108682E+10 | 0.286553E+09 | 0.138051E+09 | 0.148502E+09 | 0.00 | 0.00 |
March | 0.661019E+09 | 0.104862E+10 | 0.397513E+09 | 0.168690E+09 | 0.228823E+09 | 0.00 | 0.00 |
April | 0.155181E+10 | 0.397252E+09 | 0.534762E+09 | 0.270733E+09 | 0.264029E+09 | 0.00 | 0.00 |
May | 0.198560E+10 | 0.223991E+09 | 0.587435E+09 | 0.298820E+09 | 0.288615E+09 | 0.00 | 0.00 |
June | 0.274786E+10 | 49776533.46 | 0.604828E+09 | 0.328803E+09 | 0.276025E+09 | 0.00 | 0.00 |
July | 0.252911E+10 | 39749693.85 | 0.528601E+09 | 0.254590E+09 | 0.274011E+09 | 0.00 | 0.00 |
August | 0.225934E+10 | 55303770.67 | 0.485695E+09 | 0.234356E+09 | 0.251339E+09 | 0.00 | 0.00 |
September | 0.168638E+10 | 82403217.61 | 0.394444E+09 | 0.155444E+09 | 0.239000E+09 | 0.00 | 0.00 |
October | 0.104324E+10 | 0.631818E+09 | 0.392291E+09 | 0.203719E+09 | 0.188572E+09 | 0.00 | 0.00 |
November | 0.460654E+09 | 0.103140E+10 | 0.297198E+09 | 0.151245E+09 | 0.145954E+09 | 0.00 | 0.00 |
December | 0.336389E+09 | 0.145690E+10 | 0.280729E+09 | 0.145223E+09 | 0.135505E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.161065E+11 | 0.727600E+10 | 0.510486E+10 | 0.251969E+10 | 0.258518E+10 | 0.00 | 0.00 |
Minimum of Months | 0.336389E+09 | 39749693.85 | 0.280729E+09 | 0.138051E+09 | 0.135505E+09 | 0.00 | 0.00 |
Maximum of Months | 0.274786E+10 | 0.145690E+10 | 0.604828E+09 | 0.328803E+09 | 0.288615E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145128E+10 | 0.175972E+10 | 0.701289E+09 | 0.495849E+09 | 0.205441E+09 | 0.00 | 0.00 |
February | 0.626822E+09 | 0.168463E+10 | 0.438127E+09 | 0.240214E+09 | 0.197913E+09 | 0.00 | 0.00 |
March | 0.805048E+09 | 0.165350E+10 | 0.456854E+09 | 0.177436E+09 | 0.279418E+09 | 0.00 | 0.00 |
April | 0.139876E+10 | 0.723495E+09 | 0.440880E+09 | 0.139778E+09 | 0.301102E+09 | 0.00 | 0.00 |
May | 0.148447E+10 | 0.440028E+09 | 0.379915E+09 | 66578514.76 | 0.313337E+09 | 0.00 | 0.00 |
June | 0.216764E+10 | 0.124193E+09 | 0.362545E+09 | 62887890.98 | 0.299657E+09 | 0.00 | 0.00 |
July | 0.205446E+10 | 99241408.78 | 0.344975E+09 | 46866903.68 | 0.298108E+09 | 0.00 | 0.00 |
August | 0.197487E+10 | 0.135526E+09 | 0.355574E+09 | 78105612.51 | 0.277469E+09 | 0.00 | 0.00 |
September | 0.183297E+10 | 0.207168E+09 | 0.415911E+09 | 0.131511E+09 | 0.284401E+09 | 0.00 | 0.00 |
October | 0.153053E+10 | 0.999896E+09 | 0.568877E+09 | 0.327758E+09 | 0.241119E+09 | 0.00 | 0.00 |
November | 0.118805E+10 | 0.155179E+10 | 0.601316E+09 | 0.399555E+09 | 0.201761E+09 | 0.00 | 0.00 |
December | 0.119057E+10 | 0.213416E+10 | 0.651189E+09 | 0.455723E+09 | 0.195466E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.177055E+11 | 0.115133E+11 | 0.571745E+10 | 0.262226E+10 | 0.309519E+10 | 0.00 | 0.00 |
Minimum of Months | 0.626822E+09 | 99241408.78 | 0.344975E+09 | 46866903.68 | 0.195466E+09 | 0.00 | 0.00 |
Maximum of Months | 0.216764E+10 | 0.213416E+10 | 0.701289E+09 | 0.495849E+09 | 0.313337E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.141257E+10 | 0.117022E+10 | 0.643189E+09 | 0.462713E+09 | 0.180476E+09 | 0.00 | 0.00 |
February | 0.671899E+09 | 0.105715E+10 | 0.413565E+09 | 0.238856E+09 | 0.174709E+09 | 0.00 | 0.00 |
March | 0.975174E+09 | 0.104033E+10 | 0.497241E+09 | 0.245529E+09 | 0.251712E+09 | 0.00 | 0.00 |
April | 0.183093E+10 | 0.419031E+09 | 0.619032E+09 | 0.331475E+09 | 0.287557E+09 | 0.00 | 0.00 |
May | 0.200118E+10 | 0.244954E+09 | 0.582124E+09 | 0.285464E+09 | 0.296661E+09 | 0.00 | 0.00 |
June | 0.259471E+10 | 51985303.27 | 0.569960E+09 | 0.288929E+09 | 0.281031E+09 | 0.00 | 0.00 |
July | 0.227940E+10 | 40671964.84 | 0.458193E+09 | 0.180036E+09 | 0.278157E+09 | 0.00 | 0.00 |
August | 0.222619E+10 | 47563576.13 | 0.469194E+09 | 0.213489E+09 | 0.255704E+09 | 0.00 | 0.00 |
September | 0.189898E+10 | 72453677.12 | 0.458152E+09 | 0.196677E+09 | 0.261475E+09 | 0.00 | 0.00 |
October | 0.157407E+10 | 0.602772E+09 | 0.578321E+09 | 0.364388E+09 | 0.213933E+09 | 0.00 | 0.00 |
November | 0.122239E+10 | 0.100403E+10 | 0.573750E+09 | 0.394734E+09 | 0.179016E+09 | 0.00 | 0.00 |
December | 0.110455E+10 | 0.144547E+10 | 0.561690E+09 | 0.392847E+09 | 0.168843E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.197920E+11 | 0.719662E+10 | 0.642441E+10 | 0.359514E+10 | 0.282927E+10 | 0.00 | 0.00 |
Minimum of Months | 0.671899E+09 | 40671964.84 | 0.413565E+09 | 0.180036E+09 | 0.168843E+09 | 0.00 | 0.00 |
Maximum of Months | 0.259471E+10 | 0.144547E+10 | 0.643189E+09 | 0.462713E+09 | 0.296661E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.659484E+09 | 0.127697E+10 | 0.327718E+09 | 0.176597E+09 | 0.151121E+09 | 0.00 | 0.00 |
February | 0.317868E+09 | 0.112598E+10 | 0.252550E+09 | 0.100247E+09 | 0.152302E+09 | 0.00 | 0.00 |
March | 0.631771E+09 | 0.111906E+10 | 0.368720E+09 | 0.143155E+09 | 0.225564E+09 | 0.00 | 0.00 |
April | 0.152941E+10 | 0.441284E+09 | 0.526053E+09 | 0.254491E+09 | 0.271562E+09 | 0.00 | 0.00 |
May | 0.189857E+10 | 0.234104E+09 | 0.562706E+09 | 0.269264E+09 | 0.293442E+09 | 0.00 | 0.00 |
June | 0.261745E+10 | 47735187.30 | 0.588009E+09 | 0.302631E+09 | 0.285377E+09 | 0.00 | 0.00 |
July | 0.226003E+10 | 39113747.78 | 0.456814E+09 | 0.179555E+09 | 0.277259E+09 | 0.00 | 0.00 |
August | 0.205093E+10 | 54302285.22 | 0.420072E+09 | 0.173996E+09 | 0.246076E+09 | 0.00 | 0.00 |
September | 0.158895E+10 | 84948187.96 | 0.359010E+09 | 0.120949E+09 | 0.238061E+09 | 0.00 | 0.00 |
October | 0.100597E+10 | 0.675093E+09 | 0.362546E+09 | 0.175264E+09 | 0.187281E+09 | 0.00 | 0.00 |
November | 0.611743E+09 | 0.110827E+10 | 0.317470E+09 | 0.164182E+09 | 0.153288E+09 | 0.00 | 0.00 |
December | 0.444967E+09 | 0.155664E+10 | 0.269250E+09 | 0.129885E+09 | 0.139365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.156171E+11 | 0.776350E+10 | 0.481092E+10 | 0.219022E+10 | 0.262070E+10 | 0.00 | 0.00 |
Minimum of Months | 0.317868E+09 | 39113747.78 | 0.252550E+09 | 0.100247E+09 | 0.139365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.261745E+10 | 0.155664E+10 | 0.588009E+09 | 0.302631E+09 | 0.293442E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123712E+10 | 0.603237E+09 | 0.528065E+09 | 0.419617E+09 | 0.108449E+09 | 0.00 | 0.00 |
February | 0.578003E+09 | 0.552386E+09 | 0.303451E+09 | 0.203283E+09 | 0.100168E+09 | 0.00 | 0.00 |
March | 0.604621E+09 | 0.548102E+09 | 0.287546E+09 | 0.150149E+09 | 0.137397E+09 | 0.00 | 0.00 |
April | 0.830363E+09 | 0.214757E+09 | 0.254722E+09 | 0.115596E+09 | 0.139126E+09 | 0.00 | 0.00 |
May | 0.741431E+09 | 0.123005E+09 | 0.174982E+09 | 40049461.99 | 0.134932E+09 | 0.00 | 0.00 |
June | 0.970053E+09 | 24549174.28 | 0.140156E+09 | 16558940.25 | 0.123597E+09 | 0.00 | 0.00 |
July | 0.975199E+09 | 20334909.25 | 0.146969E+09 | 20181711.97 | 0.126787E+09 | 0.00 | 0.00 |
August | 0.104010E+10 | 23625872.49 | 0.186466E+09 | 62009180.04 | 0.124457E+09 | 0.00 | 0.00 |
September | 0.105383E+10 | 36173848.32 | 0.248677E+09 | 0.111177E+09 | 0.137500E+09 | 0.00 | 0.00 |
October | 0.109863E+10 | 0.308781E+09 | 0.398930E+09 | 0.277368E+09 | 0.121562E+09 | 0.00 | 0.00 |
November | 0.100894E+10 | 0.516552E+09 | 0.442359E+09 | 0.338127E+09 | 0.104232E+09 | 0.00 | 0.00 |
December | 0.108919E+10 | 0.747769E+09 | 0.489978E+09 | 0.385660E+09 | 0.104318E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112275E+11 | 0.371927E+10 | 0.360230E+10 | 0.213978E+10 | 0.146253E+10 | 0.00 | 0.00 |
Minimum of Months | 0.578003E+09 | 20334909.25 | 0.140156E+09 | 16558940.25 | 0.100168E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123712E+10 | 0.747769E+09 | 0.528065E+09 | 0.419617E+09 | 0.139126E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187096E+09 | 0.412480E+10 | 0.312127E+09 | 0.00 | 0.312127E+09 | 0.00 | 0.00 |
February | 54132676.03 | 0.395246E+10 | 0.321243E+09 | 0.00 | 0.321243E+09 | 0.00 | 0.00 |
March | 0.403539E+09 | 0.373954E+10 | 0.472776E+09 | 39188.53 | 0.472736E+09 | 0.00 | 0.00 |
April | 0.150385E+10 | 0.165089E+10 | 0.564901E+09 | 12848353.36 | 0.552052E+09 | 0.00 | 0.00 |
May | 0.234948E+10 | 0.101728E+10 | 0.699225E+09 | 77752173.55 | 0.621472E+09 | 0.00 | 0.00 |
June | 0.409929E+10 | 0.331539E+09 | 0.795269E+09 | 0.174946E+09 | 0.620323E+09 | 0.00 | 0.00 |
July | 0.364191E+10 | 0.296566E+09 | 0.691801E+09 | 92958810.13 | 0.598843E+09 | 0.00 | 0.00 |
August | 0.298176E+10 | 0.411782E+09 | 0.546122E+09 | 19510303.62 | 0.526612E+09 | 0.00 | 0.00 |
September | 0.227739E+10 | 0.601541E+09 | 0.492915E+09 | 549867.82 | 0.492365E+09 | 0.00 | 0.00 |
October | 0.912467E+09 | 0.240527E+10 | 0.393634E+09 | 0.00 | 0.393634E+09 | 0.00 | 0.00 |
November | 0.208725E+09 | 0.371317E+10 | 0.317390E+09 | 0.00 | 0.317390E+09 | 0.00 | 0.00 |
December | 81914034.52 | 0.497503E+10 | 0.291556E+09 | 0.00 | 0.291556E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187016E+11 | 0.272199E+11 | 0.589896E+10 | 0.378605E+09 | 0.552035E+10 | 0.00 | 0.00 |
Minimum of Months | 54132676.03 | 0.296566E+09 | 0.291556E+09 | 0.00 | 0.291556E+09 | 0.00 | 0.00 |
Maximum of Months | 0.409929E+10 | 0.497503E+10 | 0.795269E+09 | 0.174946E+09 | 0.621472E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.157799E+09 | 0.425760E+10 | 0.312127E+09 | 0.00 | 0.312127E+09 | 0.00 | 0.00 |
February | 42257127.62 | 0.409852E+10 | 0.321243E+09 | 0.00 | 0.321243E+09 | 0.00 | 0.00 |
March | 0.366606E+09 | 0.385627E+10 | 0.472776E+09 | 39188.53 | 0.472736E+09 | 0.00 | 0.00 |
April | 0.145785E+10 | 0.169728E+10 | 0.564901E+09 | 12848353.36 | 0.552052E+09 | 0.00 | 0.00 |
May | 0.229779E+10 | 0.104765E+10 | 0.699225E+09 | 77752173.55 | 0.621472E+09 | 0.00 | 0.00 |
June | 0.404433E+10 | 0.345359E+09 | 0.795269E+09 | 0.174946E+09 | 0.620323E+09 | 0.00 | 0.00 |
July | 0.358448E+10 | 0.311791E+09 | 0.691801E+09 | 92958810.13 | 0.598843E+09 | 0.00 | 0.00 |
August | 0.292967E+10 | 0.434241E+09 | 0.546122E+09 | 19510303.62 | 0.526612E+09 | 0.00 | 0.00 |
September | 0.222802E+10 | 0.631469E+09 | 0.492915E+09 | 549867.82 | 0.492365E+09 | 0.00 | 0.00 |
October | 0.871383E+09 | 0.248225E+10 | 0.393634E+09 | 0.00 | 0.393634E+09 | 0.00 | 0.00 |
November | 0.182960E+09 | 0.383521E+10 | 0.317390E+09 | 0.00 | 0.317390E+09 | 0.00 | 0.00 |
December | 64496195.30 | 0.514281E+10 | 0.291556E+09 | 0.00 | 0.291556E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.182277E+11 | 0.281405E+11 | 0.589896E+10 | 0.378605E+09 | 0.552035E+10 | 0.00 | 0.00 |
Minimum of Months | 42257127.62 | 0.311791E+09 | 0.291556E+09 | 0.00 | 0.291556E+09 | 0.00 | 0.00 |
Maximum of Months | 0.404433E+10 | 0.514281E+10 | 0.795269E+09 | 0.174946E+09 | 0.621472E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112888E+10 | 0.359215E+10 | 0.945059E+09 | 0.626118E+09 | 0.318941E+09 | 0.00 | 0.00 |
February | 0.622199E+09 | 0.358813E+10 | 0.734087E+09 | 0.414692E+09 | 0.319395E+09 | 0.00 | 0.00 |
March | 0.970503E+09 | 0.342581E+10 | 0.923501E+09 | 0.439729E+09 | 0.483772E+09 | 0.00 | 0.00 |
April | 0.250695E+10 | 0.158555E+10 | 0.116244E+10 | 0.618412E+09 | 0.544027E+09 | 0.00 | 0.00 |
May | 0.303189E+10 | 0.112968E+10 | 0.119422E+10 | 0.613799E+09 | 0.580421E+09 | 0.00 | 0.00 |
June | 0.415697E+10 | 0.442680E+09 | 0.119154E+10 | 0.643860E+09 | 0.547676E+09 | 0.00 | 0.00 |
July | 0.366177E+10 | 0.452754E+09 | 0.105852E+10 | 0.509627E+09 | 0.548893E+09 | 0.00 | 0.00 |
August | 0.348768E+10 | 0.635268E+09 | 0.102045E+10 | 0.508173E+09 | 0.512282E+09 | 0.00 | 0.00 |
September | 0.261915E+10 | 0.801186E+09 | 0.887984E+09 | 0.386593E+09 | 0.501391E+09 | 0.00 | 0.00 |
October | 0.187522E+10 | 0.226123E+10 | 0.100031E+10 | 0.596532E+09 | 0.403777E+09 | 0.00 | 0.00 |
November | 0.954632E+09 | 0.330037E+10 | 0.850640E+09 | 0.533020E+09 | 0.317620E+09 | 0.00 | 0.00 |
December | 0.800089E+09 | 0.420892E+10 | 0.853863E+09 | 0.553388E+09 | 0.300475E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.258159E+11 | 0.254237E+11 | 0.118226E+11 | 0.644394E+10 | 0.537867E+10 | 0.00 | 0.00 |
Minimum of Months | 0.622199E+09 | 0.442680E+09 | 0.734087E+09 | 0.386593E+09 | 0.300475E+09 | 0.00 | 0.00 |
Maximum of Months | 0.415697E+10 | 0.420892E+10 | 0.119422E+10 | 0.643860E+09 | 0.580421E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.303330E+10 | 0.304388E+10 | 0.145122E+10 | 0.106816E+10 | 0.383060E+09 | 0.00 | 0.00 |
February | 0.131725E+10 | 0.290420E+10 | 0.882574E+09 | 0.517469E+09 | 0.365106E+09 | 0.00 | 0.00 |
March | 0.154130E+10 | 0.290955E+10 | 0.894031E+09 | 0.382225E+09 | 0.511806E+09 | 0.00 | 0.00 |
April | 0.251240E+10 | 0.132384E+10 | 0.842058E+09 | 0.298661E+09 | 0.543397E+09 | 0.00 | 0.00 |
May | 0.252494E+10 | 0.825607E+09 | 0.685121E+09 | 0.128602E+09 | 0.556520E+09 | 0.00 | 0.00 |
June | 0.363596E+10 | 0.241323E+09 | 0.629394E+09 | 0.102123E+09 | 0.527270E+09 | 0.00 | 0.00 |
July | 0.345906E+10 | 0.198172E+09 | 0.611268E+09 | 83240082.17 | 0.528027E+09 | 0.00 | 0.00 |
August | 0.343508E+10 | 0.271203E+09 | 0.661872E+09 | 0.164536E+09 | 0.497336E+09 | 0.00 | 0.00 |
September | 0.328350E+10 | 0.404861E+09 | 0.801992E+09 | 0.283195E+09 | 0.518797E+09 | 0.00 | 0.00 |
October | 0.295643E+10 | 0.177739E+10 | 0.115044E+10 | 0.706055E+09 | 0.444381E+09 | 0.00 | 0.00 |
November | 0.245087E+10 | 0.271020E+10 | 0.123485E+10 | 0.860720E+09 | 0.374130E+09 | 0.00 | 0.00 |
December | 0.259159E+10 | 0.358526E+10 | 0.134721E+10 | 0.981718E+09 | 0.365494E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.327417E+11 | 0.201955E+11 | 0.111920E+11 | 0.557670E+10 | 0.561532E+10 | 0.00 | 0.00 |
Minimum of Months | 0.131725E+10 | 0.198172E+09 | 0.611268E+09 | 83240082.17 | 0.365106E+09 | 0.00 | 0.00 |
Maximum of Months | 0.363596E+10 | 0.358526E+10 | 0.145122E+10 | 0.106816E+10 | 0.556520E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.109316E+12 | -0.107562E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175375E+10 | 82.17 | 0.00 | 0.00 |
February | 0.981060E+11 | -0.965216E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158441E+10 | 82.17 | 0.00 | 0.00 |
March | 0.105349E+12 | -0.103594E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175573E+10 | 82.17 | 0.00 | 0.00 |
April | 0.969767E+11 | -0.952798E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169687E+10 | 82.17 | 0.00 | 0.00 |
May | 0.946301E+11 | -0.928767E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
June | 0.872018E+11 | -0.855049E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169686E+10 | 82.17 | 0.00 | 0.00 |
July | 0.878781E+11 | -0.861247E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
August | 0.885564E+11 | -0.868030E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
September | 0.889751E+11 | -0.872783E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169684E+10 | 82.17 | 0.00 | 0.00 |
October | 0.971209E+11 | -0.953675E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
November | 0.993785E+11 | -0.976816E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169687E+10 | 82.17 | 0.00 | 0.00 |
December | 0.107149E+12 | -0.105395E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175385E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.116064E+13 | -0.113999E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206489E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.872018E+11 | -0.107562E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.175573E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.109316E+12 | -0.855049E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158441E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804706E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164098577.1 | 82.17 | 0.00 | 0.00 |
February | 0.727159E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148226651.3 | 82.17 | 0.00 | 0.00 |
March | 0.804565E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164097292.1 | 82.17 | 0.00 | 0.00 |
April | 0.779700E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158794315.6 | 82.17 | 0.00 | 0.00 |
May | 0.804705E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164084753.3 | 82.17 | 0.00 | 0.00 |
June | 0.778855E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158789192.3 | 82.17 | 0.00 | 0.00 |
July | 0.805548E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164079153.8 | 82.17 | 0.00 | 0.00 |
August | 0.804704E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164078926.2 | 82.17 | 0.00 | 0.00 |
September | 0.779840E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158786566.1 | 82.17 | 0.00 | 0.00 |
October | 0.804565E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164089845.2 | 82.17 | 0.00 | 0.00 |
November | 0.778012E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158803859.0 | 82.17 | 0.00 | 0.00 |
December | 0.805551E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164106789.6 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947791E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193204E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727159E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164106789.6 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805551E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148226651.3 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.619234E+11 | -0.604165E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150683E+10 | 60.05 | 0.00 | 0.00 |
February | 0.553972E+11 | -0.540357E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.136153E+10 | 60.05 | 0.00 | 0.00 |
March | 0.585506E+11 | -0.570410E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150957E+10 | 60.05 | 0.00 | 0.00 |
April | 0.523342E+11 | -0.508765E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145779E+10 | 60.05 | 0.00 | 0.00 |
May | 0.492681E+11 | -0.477617E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
June | 0.439149E+11 | -0.424571E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145778E+10 | 60.05 | 0.00 | 0.00 |
July | 0.434113E+11 | -0.419050E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
August | 0.440406E+11 | -0.425343E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
September | 0.454275E+11 | -0.439698E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145775E+10 | 60.05 | 0.00 | 0.00 |
October | 0.513913E+11 | -0.498849E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
November | 0.543870E+11 | -0.529292E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145779E+10 | 60.05 | 0.00 | 0.00 |
December | 0.600483E+11 | -0.585413E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150697E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.620095E+12 | -0.602353E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.177415E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.434113E+11 | -0.604165E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.150957E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.619234E+11 | -0.419050E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.136153E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 309.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 344.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 403.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 399.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 361.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 350.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 348.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 288.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 290.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4135.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 241.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_1 HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.299455E+10 | 23545.30 | 01-JAN-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.247954E+10 | 11925.32 | 01-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326465E+10 | 23645.15 | 26-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29064547.84 | 3783.81 | 21-APR-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.428958E+09 | 11966.10 | 25-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217606E+10 | 24509.85 | 23-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.971858E+10 | 27190.44 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.971858E+10 | 27190.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174398E+09 | 1414.45 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259758E+09 | 879.30 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.253100E+09 | 1535.30 | 26-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3420805.79 | 339.47 | 21-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35879229.14 | 741.33 | 25-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123423E+09 | 1309.99 | 23-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.499855E+09 | 1725.59 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.499855E+09 | 1725.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13790584.31 | 397.46 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5419434.30 | 228.94 | 27-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 781161.28 | 101.27 | 24-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45912723.12 | 489.01 | 07-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 65903903.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45912723.12 | 489.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.711565E+10 | 27391.39 | 01-JAN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.587855E+10 | 18089.98 | 01-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.634419E+10 | 27391.39 | 26-MAR-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145665E+09 | 9305.48 | 21-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133792E+10 | 17991.50 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.503944E+10 | 27391.39 | 23-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162490E+11 | 27391.39 | 05-DEC-02:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162490E+11 | 27391.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_0 HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN_SUPPHEATCOIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.685892E+09 | 7320.27 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.625751E+09 | 5784.27 | 20-FEB-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.655406E+09 | 11571.46 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20420605.42 | 5102.66 | 10-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6017595.14 | 4738.28 | 13-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 137723.94 | 1023.63 | 14-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57699.63 | 961.66 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 363208.58 | 3307.32 | 30-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 530826.67 | 2097.97 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131449E+09 | 4901.34 | 08-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.489512E+09 | 5604.49 | 26-NOV-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159322E+10 | 9284.69 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.420876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 57699.63 | 961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159322E+10 | 11571.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.783839E+09 | 18804.89 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.730963E+09 | 9888.57 | 03-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.612940E+09 | 13754.89 | 26-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9148441.29 | 9453.17 | 06-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 998026.02 | 6911.52 | 01-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 373436.31 | 2180.50 | 16-JUN-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 179335.36 | 2127.67 | 01-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 116926.86 | 1948.78 | 30-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 433646.23 | 2799.00 | 20-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122204E+09 | 7917.69 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.566030E+09 | 14050.09 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193079E+10 | 20448.67 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 116926.86 | 1948.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193079E+10 | 20448.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225807E+10 | 60108.44 | 04-JAN-20:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200954E+10 | 55690.68 | 09-FEB-22:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177919E+10 | 56542.15 | 12-MAR-19:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18452591.07 | 30930.31 | 18-APR-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2137012.38 | 23725.87 | 01-MAY-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 915191.73 | 9151.92 | 09-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6171529.96 | 17209.51 | 31-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15415704.79 | 25775.76 | 11-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6747550.42 | 17925.00 | 17-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170190E+09 | 51651.43 | 12-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160178E+10 | 55557.10 | 28-NOV-20:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.773482E+10 | 63927.68 | 14-DEC-17:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 915191.73 | 9151.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.773482E+10 | 63927.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.787481E+09 | 4363.57 | 13-JAN-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690161E+09 | 4963.63 | 20-FEB-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.709630E+09 | 5014.56 | 24-MAR-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15130740.92 | 1216.99 | 21-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76534.64 | 637.79 | 26-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147068E+09 | 3799.53 | 27-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.559471E+09 | 4804.85 | 26-NOV-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168605E+10 | 5336.42 | 05-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168605E+10 | 5336.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.917321E+09 | 6047.45 | 10-JAN-20:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.786884E+09 | 5279.58 | 05-FEB-17:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.692163E+09 | 8877.29 | 18-MAR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11127602.64 | 7053.02 | 26-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 107737.39 | 1795.62 | 13-MAY-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 234064.89 | 2035.27 | 20-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142397E+09 | 6166.57 | 28-OCT-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.640748E+09 | 6234.83 | 30-NOV-19:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198225E+10 | 6624.35 | 12-DEC-20:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.517324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198225E+10 | 8877.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.407143E+09 | 4800.27 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398858E+09 | 3157.11 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355984E+09 | 5027.89 | 26-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17128520.43 | 1182.72 | 30-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2951099.02 | 1246.28 | 27-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 143312.58 | 698.97 | 13-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35339.31 | 353.39 | 02-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 315745.42 | 1109.37 | 24-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 689113.31 | 1168.77 | 28-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99777371.29 | 3379.71 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.296729E+09 | 3211.66 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.776879E+09 | 4916.50 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 35339.31 | 353.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.776879E+09 | 5027.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.458048E+09 | 5342.42 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.453814E+09 | 4943.23 | 03-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.334202E+09 | 5085.89 | 26-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9329952.98 | 2126.86 | 26-APR-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 429962.70 | 1454.24 | 13-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23486.75 | 391.45 | 05-JUN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21785.79 | 269.92 | 03-AUG-19:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 192457.48 | 675.59 | 21-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95935870.04 | 4655.27 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332858E+09 | 5211.61 | 23-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.925201E+09 | 5357.19 | 07-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.925201E+09 | 5357.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117922E+10 | 6344.71 | 11-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118357E+10 | 6829.81 | 24-FEB-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126660E+10 | 17533.48 | 27-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 56301180.05 | 5974.26 | 09-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3515498.54 | 5274.92 | 26-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 464792.76 | 4276.98 | 14-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 249629.65 | 4160.49 | 01-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 153136.26 | 2552.27 | 30-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356734.41 | 2972.79 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275718E+09 | 6555.54 | 25-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.865321E+09 | 7117.88 | 16-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252992E+10 | 8322.38 | 11-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.736139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 153136.26 | 2552.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.252992E+10 | 17533.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6 PTAC HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18641441.62 | 1308.65 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79068763.41 | 2140.29 | 07-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97710205.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79068763.41 | 2140.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276296E+09 | 7522.83 | 01-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137297E+09 | 4240.16 | 01-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.549349E+09 | 8568.40 | 27-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26518478.78 | 4152.58 | 25-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230911E+09 | 7682.19 | 23-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154352E+10 | 11349.24 | 06-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154352E+10 | 11349.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN HEATING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.644460E+10 | 0.631749E+10 | 24885.27 | 08-JAN-16:12 | 20621.35 | 0.00 |
February | 0.00 | 0.00 | 0.320313E+10 | 0.289115E+10 | 25332.34 | 17-FEB-16:12 | 18765.37 | 0.00 |
March | 0.00 | 0.00 | 0.567510E+10 | 0.545740E+10 | 24263.28 | 05-MAR-16:12 | 22041.61 | 0.00 |
April | 0.00 | 0.00 | 0.128645E+11 | 0.128178E+11 | 23931.47 | 15-APR-08:62 | 22616.67 | 0.00 |
May | 0.00 | 0.00 | 0.152289E+11 | 0.152173E+11 | 23617.04 | 11-MAY-08:62 | 23284.76 | 0.00 |
June | 0.00 | 0.00 | 0.196449E+11 | 0.195336E+11 | 23026.63 | 11-JUN-08:61 | 23026.63 | 0.00 |
July | 0.00 | 0.00 | 0.202522E+11 | 0.183483E+11 | 26254.98 | 27-JUL-08:62 | 17570.81 | 0.00 |
August | 0.00 | 0.00 | 0.199415E+11 | 0.179787E+11 | 27074.48 | 04-AUG-08:62 | 16802.78 | 0.00 |
September | 0.00 | 0.00 | 0.176026E+11 | 0.156794E+11 | 27678.11 | 03-SEP-08:62 | 15569.32 | 0.00 |
October | 0.00 | 0.00 | 0.111310E+11 | 0.106311E+11 | 25557.71 | 03-OCT-08:61 | 18283.12 | 0.00 |
November | 0.00 | 0.00 | 0.663826E+10 | 0.615887E+10 | 27719.92 | 12-NOV-16:12 | 15331.35 | 0.00 |
December | 0.00 | 0.00 | 0.403498E+10 | 0.402510E+10 | 23395.47 | 13-DEC-16:12 | 23395.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142662E+12 | 0.135056E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.320313E+10 | 0.289115E+10 | 23026.63 | 15331.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202522E+11 | 0.195336E+11 | 27719.92 | 23395.47 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.253712E+10 | 0.246351E+10 | 26725.85 | 08-JAN-20:11 | 16415.52 | 0.00 |
February | 0.00 | 0.00 | 0.135402E+10 | 0.114467E+10 | 25651.86 | 17-FEB-20:01 | 17674.94 | 0.00 |
March | 0.00 | 0.00 | 0.296812E+10 | 0.280989E+10 | 24770.21 | 05-MAR-22:51 | 21242.14 | 0.00 |
April | 0.00 | 0.00 | 0.110335E+11 | 0.109895E+11 | 24485.56 | 16-APR-08:51 | 22181.81 | 0.00 |
May | 0.00 | 0.00 | 0.144673E+11 | 0.144577E+11 | 23948.52 | 11-MAY-08:41 | 23948.52 | 0.00 |
June | 0.00 | 0.00 | 0.194689E+11 | 0.193604E+11 | 24067.15 | 04-JUN-06:41 | 24067.15 | 0.00 |
July | 0.00 | 0.00 | 0.200139E+11 | 0.181339E+11 | 28039.10 | 27-JUL-08:11 | 16739.75 | 0.00 |
August | 0.00 | 0.00 | 0.188009E+11 | 0.169280E+11 | 28542.74 | 04-AUG-08:51 | 17045.55 | 0.00 |
September | 0.00 | 0.00 | 0.156917E+11 | 0.139398E+11 | 29536.24 | 04-SEP-08:51 | 15340.47 | 0.00 |
October | 0.00 | 0.00 | 0.772149E+10 | 0.728606E+10 | 27299.99 | 03-OCT-08:61 | 16827.30 | 0.00 |
November | 0.00 | 0.00 | 0.310053E+10 | 0.278855E+10 | 28252.86 | 11-NOV-22:51 | 15803.60 | 0.00 |
December | 0.00 | 0.00 | 0.122115E+10 | 0.121720E+10 | 23841.73 | 13-DEC-17:11 | 23841.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118379E+12 | 0.111519E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.122115E+10 | 0.114467E+10 | 23841.73 | 15340.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200139E+11 | 0.193604E+11 | 29536.24 | 24067.15 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.503742E+11 | 0.502977E+11 | 73204.80 | 14-JAN-13:40 | 73204.80 | 0.00 |
February | 0.00 | 0.00 | 0.185725E+11 | 0.183764E+11 | 49153.74 | 23-FEB-14:00 | 49153.74 | 0.00 |
March | 0.00 | 0.00 | 0.240858E+11 | 0.240834E+11 | 56548.72 | 18-MAR-14:40 | 56548.72 | 0.00 |
April | 0.00 | 0.00 | 0.554583E+11 | 0.554583E+11 | 66014.45 | 14-APR-14:10 | 66014.45 | 0.00 |
May | 0.00 | 0.00 | 0.587524E+11 | 0.587524E+11 | 54720.58 | 04-MAY-14:10 | 54720.58 | 0.00 |
June | 0.00 | 0.00 | 0.785586E+11 | 0.785556E+11 | 64563.93 | 28-JUN-15:00 | 64563.93 | 0.00 |
July | 0.00 | 0.00 | 0.824805E+11 | 0.791731E+11 | 63465.01 | 19-JUL-14:10 | 62311.11 | 0.00 |
August | 0.00 | 0.00 | 0.854463E+11 | 0.822653E+11 | 77709.89 | 27-AUG-14:10 | 77709.89 | 0.00 |
September | 0.00 | 0.00 | 0.826297E+11 | 0.790808E+11 | 82933.21 | 28-SEP-14:10 | 82933.21 | 0.00 |
October | 0.00 | 0.00 | 0.636469E+11 | 0.630640E+11 | 78998.03 | 10-OCT-14:10 | 78998.03 | 0.00 |
November | 0.00 | 0.00 | 0.439390E+11 | 0.433842E+11 | 75670.69 | 20-NOV-13:40 | 75670.69 | 0.00 |
December | 0.00 | 0.00 | 0.356331E+11 | 0.356329E+11 | 73033.40 | 25-DEC-13:30 | 73033.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.679577E+12 | 0.668124E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.185725E+11 | 0.183764E+11 | 49153.74 | 49153.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.854463E+11 | 0.822653E+11 | 82933.21 | 82933.21 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.208394E+11 | 0.200540E+11 | 171958.79 | 08-JAN-20:11 | 107454.92 | 0.00 |
February | 0.00 | 0.00 | 0.184471E+11 | 0.152926E+11 | 165307.64 | 18-FEB-19:11 | 118546.23 | 0.00 |
March | 0.00 | 0.00 | 0.290389E+11 | 0.273121E+11 | 159515.77 | 06-MAR-19:02 | 122490.72 | 0.00 |
April | 0.00 | 0.00 | 0.768209E+11 | 0.765190E+11 | 155961.61 | 15-APR-21:51 | 154896.40 | 0.00 |
May | 0.00 | 0.00 | 0.102572E+12 | 0.102494E+12 | 151249.94 | 11-MAY-08:41 | 151249.94 | 0.00 |
June | 0.00 | 0.00 | 0.137787E+12 | 0.137079E+12 | 154282.11 | 04-JUN-06:41 | 152275.63 | 0.00 |
July | 0.00 | 0.00 | 0.153649E+12 | 0.135776E+12 | 181143.41 | 15-JUL-06:41 | 104238.21 | 0.00 |
August | 0.00 | 0.00 | 0.142604E+12 | 0.124851E+12 | 183254.23 | 04-AUG-08:51 | 105389.87 | 0.00 |
September | 0.00 | 0.00 | 0.123744E+12 | 0.106882E+12 | 189715.01 | 04-SEP-08:51 | 95449.34 | 0.00 |
October | 0.00 | 0.00 | 0.618568E+11 | 0.578418E+11 | 174940.43 | 03-OCT-08:61 | 109088.09 | 0.00 |
November | 0.00 | 0.00 | 0.272093E+11 | 0.238425E+11 | 182575.02 | 11-NOV-22:51 | 101424.56 | 0.00 |
December | 0.00 | 0.00 | 0.117130E+11 | 0.116363E+11 | 147412.40 | 13-DEC-17:11 | 144331.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.906281E+12 | 0.839580E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.117130E+11 | 0.116363E+11 | 147412.40 | 95449.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.153649E+12 | 0.137079E+12 | 189715.01 | 154896.40 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.601035E+10 | 0.587540E+10 | 21342.17 | 09-JAN-09:02 | 16288.06 | 0.00 |
February | 0.00 | 0.00 | 0.338627E+10 | 0.303832E+10 | 21876.07 | 18-FEB-09:02 | 15210.32 | 0.00 |
March | 0.00 | 0.00 | 0.568296E+10 | 0.544634E+10 | 20796.83 | 02-MAR-09:02 | 17453.58 | 0.00 |
April | 0.00 | 0.00 | 0.128363E+11 | 0.127822E+11 | 20290.60 | 16-APR-08:62 | 18729.00 | 0.00 |
May | 0.00 | 0.00 | 0.154770E+11 | 0.154647E+11 | 19766.38 | 11-MAY-08:62 | 19766.38 | 0.00 |
June | 0.00 | 0.00 | 0.199309E+11 | 0.198198E+11 | 19365.66 | 11-JUN-08:61 | 19365.66 | 0.00 |
July | 0.00 | 0.00 | 0.211523E+11 | 0.192008E+11 | 21211.18 | 09-JUL-08:62 | 16061.77 | 0.00 |
August | 0.00 | 0.00 | 0.206007E+11 | 0.185847E+11 | 22784.71 | 04-AUG-08:62 | 14219.98 | 0.00 |
September | 0.00 | 0.00 | 0.178428E+11 | 0.158783E+11 | 23330.55 | 03-SEP-08:62 | 13098.15 | 0.00 |
October | 0.00 | 0.00 | 0.112265E+11 | 0.107098E+11 | 21466.14 | 22-OCT-08:62 | 16265.26 | 0.00 |
November | 0.00 | 0.00 | 0.608420E+10 | 0.563331E+10 | 23617.57 | 12-NOV-16:12 | 12208.03 | 0.00 |
December | 0.00 | 0.00 | 0.387775E+10 | 0.386530E+10 | 21280.45 | 13-DEC-09:02 | 16091.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144108E+12 | 0.136299E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.338627E+10 | 0.303832E+10 | 19365.66 | 12208.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211523E+11 | 0.198198E+11 | 23617.57 | 19766.38 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.233638E+10 | 0.224579E+10 | 22405.62 | 08-JAN-20:11 | 13419.45 | 0.00 |
February | 0.00 | 0.00 | 0.164032E+10 | 0.137013E+10 | 21659.70 | 18-FEB-09:02 | 14800.89 | 0.00 |
March | 0.00 | 0.00 | 0.325300E+10 | 0.307177E+10 | 21012.46 | 18-MAR-08:51 | 19683.44 | 0.00 |
April | 0.00 | 0.00 | 0.107238E+11 | 0.106724E+11 | 21146.18 | 15-APR-08:22 | 21146.18 | 0.00 |
May | 0.00 | 0.00 | 0.142401E+11 | 0.142263E+11 | 20968.30 | 13-MAY-08:32 | 20968.30 | 0.00 |
June | 0.00 | 0.00 | 0.196012E+11 | 0.194910E+11 | 20761.80 | 01-JUN-07:02 | 20761.80 | 0.00 |
July | 0.00 | 0.00 | 0.208338E+11 | 0.189031E+11 | 23931.40 | 27-JUL-07:52 | 16560.19 | 0.00 |
August | 0.00 | 0.00 | 0.193574E+11 | 0.174264E+11 | 23975.65 | 04-AUG-08:51 | 14532.61 | 0.00 |
September | 0.00 | 0.00 | 0.157655E+11 | 0.139664E+11 | 25229.24 | 04-SEP-08:32 | 14915.44 | 0.00 |
October | 0.00 | 0.00 | 0.778246E+10 | 0.732358E+10 | 23009.05 | 04-OCT-08:12 | 17691.71 | 0.00 |
November | 0.00 | 0.00 | 0.268789E+10 | 0.239890E+10 | 23626.24 | 11-NOV-22:51 | 12851.64 | 0.00 |
December | 0.00 | 0.00 | 0.115687E+10 | 0.114941E+10 | 19658.09 | 25-DEC-09:51 | 19658.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119379E+12 | 0.112245E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.115687E+10 | 0.114941E+10 | 19658.09 | 12851.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208338E+11 | 0.194910E+11 | 25229.24 | 21146.18 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.145673E+10 | 0.142982E+10 | 6873.57 | 08-JAN-16:12 | 5610.06 | 0.00 |
February | 0.00 | 0.00 | 0.642273E+09 | 0.585703E+09 | 6736.46 | 18-FEB-16:12 | 5928.35 | 0.00 |
March | 0.00 | 0.00 | 0.131290E+10 | 0.126659E+10 | 6688.46 | 05-MAR-16:12 | 6022.88 | 0.00 |
April | 0.00 | 0.00 | 0.334193E+10 | 0.333110E+10 | 6571.38 | 15-APR-08:62 | 6229.19 | 0.00 |
May | 0.00 | 0.00 | 0.406109E+10 | 0.405838E+10 | 6349.19 | 11-MAY-08:62 | 6292.94 | 0.00 |
June | 0.00 | 0.00 | 0.540403E+10 | 0.537352E+10 | 6340.14 | 04-JUN-08:62 | 5851.79 | 0.00 |
July | 0.00 | 0.00 | 0.552327E+10 | 0.503182E+10 | 7277.33 | 27-JUL-08:62 | 4715.35 | 0.00 |
August | 0.00 | 0.00 | 0.540189E+10 | 0.489646E+10 | 7559.39 | 04-AUG-08:62 | 4409.90 | 0.00 |
September | 0.00 | 0.00 | 0.465372E+10 | 0.416425E+10 | 7760.47 | 03-SEP-08:62 | 4018.60 | 0.00 |
October | 0.00 | 0.00 | 0.273751E+10 | 0.261512E+10 | 7108.46 | 03-OCT-08:61 | 4866.42 | 0.00 |
November | 0.00 | 0.00 | 0.148386E+10 | 0.137876E+10 | 7786.60 | 12-NOV-16:12 | 3932.52 | 0.00 |
December | 0.00 | 0.00 | 0.871412E+09 | 0.869313E+09 | 6441.42 | 13-DEC-16:12 | 6441.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.368906E+11 | 0.350008E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.642273E+09 | 0.585703E+09 | 6340.14 | 3932.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.552327E+10 | 0.537352E+10 | 7786.60 | 6441.42 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.527958E+09 | 0.514735E+09 | 7314.91 | 08-JAN-20:11 | 4347.13 | 0.00 |
February | 0.00 | 0.00 | 0.214642E+09 | 0.183799E+09 | 6925.74 | 16-FEB-20:11 | 5138.00 | 0.00 |
March | 0.00 | 0.00 | 0.662853E+09 | 0.631428E+09 | 6783.81 | 17-MAR-21:51 | 6562.89 | 0.00 |
April | 0.00 | 0.00 | 0.290887E+10 | 0.289832E+10 | 6693.76 | 15-APR-21:51 | 6693.76 | 0.00 |
May | 0.00 | 0.00 | 0.389647E+10 | 0.389415E+10 | 6582.17 | 11-MAY-08:41 | 6582.17 | 0.00 |
June | 0.00 | 0.00 | 0.537589E+10 | 0.534562E+10 | 6583.53 | 04-JUN-06:41 | 6539.35 | 0.00 |
July | 0.00 | 0.00 | 0.547016E+10 | 0.498375E+10 | 7716.17 | 27-JUL-08:11 | 4563.33 | 0.00 |
August | 0.00 | 0.00 | 0.512718E+10 | 0.464325E+10 | 7871.93 | 04-AUG-08:51 | 4593.02 | 0.00 |
September | 0.00 | 0.00 | 0.419427E+10 | 0.374653E+10 | 8137.77 | 04-SEP-08:51 | 4186.31 | 0.00 |
October | 0.00 | 0.00 | 0.192452E+10 | 0.181766E+10 | 7510.88 | 03-OCT-08:61 | 4498.59 | 0.00 |
November | 0.00 | 0.00 | 0.651575E+09 | 0.586005E+09 | 7764.49 | 11-NOV-22:51 | 4223.74 | 0.00 |
December | 0.00 | 0.00 | 0.223796E+09 | 0.223110E+09 | 6557.48 | 13-DEC-17:11 | 6557.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.311782E+11 | 0.294684E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.214642E+09 | 0.183799E+09 | 6557.48 | 4186.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.547016E+10 | 0.534562E+10 | 8137.77 | 6693.76 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.131067E+11 | 0.128993E+11 | 32873.89 | 09-JAN-09:02 | 23512.03 | 0.00 |
February | 0.00 | 0.00 | 0.628162E+10 | 0.579499E+10 | 33389.58 | 18-FEB-09:02 | 21427.92 | 0.00 |
March | 0.00 | 0.00 | 0.850884E+10 | 0.819754E+10 | 31686.30 | 05-MAR-09:02 | 26053.86 | 0.00 |
April | 0.00 | 0.00 | 0.171067E+11 | 0.170358E+11 | 30393.67 | 15-APR-08:62 | 29289.98 | 0.00 |
May | 0.00 | 0.00 | 0.190701E+11 | 0.190508E+11 | 29985.79 | 13-MAY-08:62 | 29985.79 | 0.00 |
June | 0.00 | 0.00 | 0.249913E+11 | 0.248129E+11 | 29480.46 | 11-JUN-08:61 | 29480.46 | 0.00 |
July | 0.00 | 0.00 | 0.277601E+11 | 0.249521E+11 | 33980.31 | 27-JUL-08:62 | 21672.87 | 0.00 |
August | 0.00 | 0.00 | 0.281275E+11 | 0.251973E+11 | 35224.44 | 04-AUG-08:62 | 20273.57 | 0.00 |
September | 0.00 | 0.00 | 0.261936E+11 | 0.232705E+11 | 35783.06 | 03-SEP-08:62 | 19030.00 | 0.00 |
October | 0.00 | 0.00 | 0.180090E+11 | 0.172492E+11 | 33136.22 | 22-OCT-08:62 | 22780.37 | 0.00 |
November | 0.00 | 0.00 | 0.121237E+11 | 0.114278E+11 | 35837.57 | 12-NOV-16:12 | 18416.97 | 0.00 |
December | 0.00 | 0.00 | 0.979659E+10 | 0.977689E+10 | 29794.74 | 13-DEC-16:12 | 29794.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.211076E+12 | 0.199665E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.628162E+10 | 0.579499E+10 | 29480.46 | 18416.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.281275E+11 | 0.251973E+11 | 35837.57 | 29985.79 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.119935E+11 | 0.947966E+10 | 12699.16 | 14-JAN-13:30 | 10849.57 | 0.00 |
February | 0.00 | 0.00 | 0.675928E+10 | 0.408217E+10 | 10075.36 | 16-FEB-13:30 | 6312.12 | 0.00 |
March | 0.00 | 0.00 | 0.108044E+11 | 0.796099E+10 | 11981.42 | 16-MAR-15:13 | 11550.55 | 0.00 |
April | 0.00 | 0.00 | 0.203288E+11 | 0.189290E+11 | 16731.69 | 14-APR-18:03 | 16731.69 | 0.00 |
May | 0.00 | 0.00 | 0.241049E+11 | 0.231194E+11 | 18380.37 | 31-MAY-18:15 | 18380.37 | 0.00 |
June | 0.00 | 0.00 | 0.328299E+11 | 0.317653E+11 | 25613.47 | 28-JUN-18:25 | 25613.47 | 0.00 |
July | 0.00 | 0.00 | 0.365355E+11 | 0.308626E+11 | 22557.56 | 20-JUL-18:30 | 22058.97 | 0.00 |
August | 0.00 | 0.00 | 0.357782E+11 | 0.299792E+11 | 21463.11 | 25-AUG-18:03 | 21463.11 | 0.00 |
September | 0.00 | 0.00 | 0.320847E+11 | 0.262667E+11 | 20705.22 | 08-SEP-18:15 | 18939.50 | 0.00 |
October | 0.00 | 0.00 | 0.203257E+11 | 0.173235E+11 | 18709.88 | 03-OCT-12:30 | 15789.43 | 0.00 |
November | 0.00 | 0.00 | 0.125343E+11 | 0.945421E+10 | 15393.47 | 01-NOV-15:10 | 14284.51 | 0.00 |
December | 0.00 | 0.00 | 0.755774E+10 | 0.551341E+10 | 12656.83 | 25-DEC-13:00 | 10486.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.251637E+12 | 0.214736E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.675928E+10 | 0.408217E+10 | 10075.36 | 6312.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.365355E+11 | 0.317653E+11 | 25613.47 | 25613.47 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.477038E+10 | 0.406164E+10 | 7713.54 | 14-JAN-13:30 | 7072.04 | 0.00 |
February | 0.00 | 0.00 | 0.247128E+10 | 0.178822E+10 | 8005.19 | 18-FEB-11:25 | 3876.72 | 0.00 |
March | 0.00 | 0.00 | 0.488886E+10 | 0.408797E+10 | 8906.76 | 18-MAR-13:30 | 8689.23 | 0.00 |
April | 0.00 | 0.00 | 0.120165E+11 | 0.115296E+11 | 12467.85 | 14-APR-15:10 | 12467.85 | 0.00 |
May | 0.00 | 0.00 | 0.147689E+11 | 0.144027E+11 | 11655.38 | 04-MAY-14:10 | 11655.38 | 0.00 |
June | 0.00 | 0.00 | 0.199446E+11 | 0.195330E+11 | 14221.67 | 28-JUN-15:10 | 14221.67 | 0.00 |
July | 0.00 | 0.00 | 0.209293E+11 | 0.190280E+11 | 14157.41 | 19-JUL-13:00 | 13626.95 | 0.00 |
August | 0.00 | 0.00 | 0.202550E+11 | 0.183110E+11 | 14541.29 | 09-AUG-13:30 | 14133.51 | 0.00 |
September | 0.00 | 0.00 | 0.173446E+11 | 0.154447E+11 | 14090.72 | 07-SEP-13:30 | 13880.02 | 0.00 |
October | 0.00 | 0.00 | 0.100503E+11 | 0.908626E+10 | 13268.65 | 02-OCT-13:10 | 12857.30 | 0.00 |
November | 0.00 | 0.00 | 0.511964E+10 | 0.422597E+10 | 9431.42 | 01-NOV-15:10 | 9192.45 | 0.00 |
December | 0.00 | 0.00 | 0.255084E+10 | 0.207533E+10 | 7688.11 | 25-DEC-13:00 | 6749.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135110E+12 | 0.123574E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.247128E+10 | 0.178822E+10 | 7688.11 | 3876.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.209293E+11 | 0.195330E+11 | 14541.29 | 14221.67 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_1 COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.304087E+11 | 0.297789E+11 | 65962.34 | 31-JAN-16:10 | 65962.34 | 0.00 |
February | 0.00 | 0.00 | 0.789753E+10 | 0.678090E+10 | 33475.25 | 18-FEB-14:00 | 28816.69 | 0.00 |
March | 0.00 | 0.00 | 0.321480E+11 | 0.312243E+11 | 61091.06 | 20-MAR-18:03 | 61091.06 | 0.00 |
April | 0.00 | 0.00 | 0.976679E+11 | 0.975062E+11 | 91533.44 | 14-APR-18:03 | 91533.44 | 0.00 |
May | 0.00 | 0.00 | 0.128400E+12 | 0.128390E+12 | 97223.69 | 31-MAY-18:20 | 97223.69 | 0.00 |
June | 0.00 | 0.00 | 0.174721E+12 | 0.174609E+12 | 120776.04 | 28-JUN-18:20 | 120776.04 | 0.00 |
July | 0.00 | 0.00 | 0.194940E+12 | 0.173314E+12 | 123973.66 | 13-JUL-21:00 | 66891.31 | 0.00 |
August | 0.00 | 0.00 | 0.189096E+12 | 0.169016E+12 | 115309.57 | 09-AUG-21:10 | 69372.17 | 0.00 |
September | 0.00 | 0.00 | 0.169643E+12 | 0.145934E+12 | 120487.27 | 10-SEP-20:40 | 53623.99 | 0.00 |
October | 0.00 | 0.00 | 0.843593E+11 | 0.807797E+11 | 97621.92 | 02-OCT-20:10 | 74067.06 | 0.00 |
November | 0.00 | 0.00 | 0.352524E+11 | 0.298298E+11 | 73457.38 | 01-NOV-15:10 | 73457.38 | 0.00 |
December | 0.00 | 0.00 | 0.157285E+11 | 0.157038E+11 | 53511.80 | 22-DEC-16:10 | 53511.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116026E+13 | 0.108287E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.789753E+10 | 0.678090E+10 | 33475.25 | 28816.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.194940E+12 | 0.174609E+12 | 123973.66 | 120776.04 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_6 COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.254279E+11 | 0.248605E+11 | 51685.72 | 31-JAN-16:30 | 51685.72 | 0.00 |
February | 0.00 | 0.00 | 0.739537E+10 | 0.637702E+10 | 30053.35 | 18-FEB-14:00 | 26462.43 | 0.00 |
March | 0.00 | 0.00 | 0.301742E+11 | 0.294313E+11 | 55452.01 | 16-MAR-15:40 | 55452.01 | 0.00 |
April | 0.00 | 0.00 | 0.925101E+11 | 0.923957E+11 | 82379.20 | 14-APR-18:03 | 82379.20 | 0.00 |
May | 0.00 | 0.00 | 0.126456E+12 | 0.126453E+12 | 92130.94 | 31-MAY-18:03 | 92130.94 | 0.00 |
June | 0.00 | 0.00 | 0.172206E+12 | 0.172077E+12 | 112807.32 | 28-JUN-18:17 | 112807.32 | 0.00 |
July | 0.00 | 0.00 | 0.192299E+12 | 0.169677E+12 | 119193.46 | 13-JUL-21:10 | 60742.21 | 0.00 |
August | 0.00 | 0.00 | 0.182069E+12 | 0.161984E+12 | 112505.84 | 09-AUG-21:10 | 65108.46 | 0.00 |
September | 0.00 | 0.00 | 0.159464E+12 | 0.135916E+12 | 110029.39 | 10-SEP-20:40 | 48720.58 | 0.00 |
October | 0.00 | 0.00 | 0.745585E+11 | 0.713151E+11 | 93431.69 | 02-OCT-22:00 | 71015.35 | 0.00 |
November | 0.00 | 0.00 | 0.310058E+11 | 0.258056E+11 | 55316.38 | 01-NOV-15:10 | 55316.38 | 0.00 |
December | 0.00 | 0.00 | 0.135449E+11 | 0.135289E+11 | 38075.73 | 25-DEC-14:00 | 38075.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110711E+13 | 0.102982E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.739537E+10 | 0.637702E+10 | 30053.35 | 26462.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.192299E+12 | 0.172077E+12 | 119193.46 | 112807.32 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_0 COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.192501E+11 | 0.171186E+11 | 25611.05 | 08-JAN-20:11 | 11674.92 | 0.00 |
February | 0.00 | 0.00 | 0.707102E+10 | 0.461113E+10 | 24293.17 | 17-FEB-21:00 | 10242.39 | 0.00 |
March | 0.00 | 0.00 | 0.128007E+11 | 0.112488E+11 | 23793.07 | 17-MAR-19:40 | 19103.32 | 0.00 |
April | 0.00 | 0.00 | 0.355334E+11 | 0.349205E+11 | 31947.81 | 14-APR-20:00 | 31947.81 | 0.00 |
May | 0.00 | 0.00 | 0.435191E+11 | 0.433011E+11 | 32732.65 | 31-MAY-18:15 | 32732.65 | 0.00 |
June | 0.00 | 0.00 | 0.594464E+11 | 0.587705E+11 | 40777.51 | 28-JUN-19:10 | 40777.51 | 0.00 |
July | 0.00 | 0.00 | 0.842728E+11 | 0.680291E+11 | 57976.25 | 14-JUL-01:00 | 19011.57 | 0.00 |
August | 0.00 | 0.00 | 0.882688E+11 | 0.702565E+11 | 64602.61 | 18-AUG-22:00 | 28713.30 | 0.00 |
September | 0.00 | 0.00 | 0.895004E+11 | 0.678925E+11 | 68194.20 | 03-SEP-21:51 | 26973.87 | 0.00 |
October | 0.00 | 0.00 | 0.528970E+11 | 0.460605E+11 | 52200.89 | 02-OCT-20:00 | 37022.96 | 0.00 |
November | 0.00 | 0.00 | 0.364261E+11 | 0.270362E+11 | 45716.96 | 11-NOV-21:00 | 18082.73 | 0.00 |
December | 0.00 | 0.00 | 0.183262E+11 | 0.171892E+11 | 22134.10 | 12-DEC-22:00 | 14297.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.547312E+12 | 0.466435E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.707102E+10 | 0.461113E+10 | 22134.10 | 10242.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.895004E+11 | 0.702565E+11 | 68194.20 | 40777.51 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY HP COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.119306E+11 | 0.118910E+11 | 36557.67 | 31-JAN-19:08 | 36557.67 | 0.00 |
February | 0.00 | 0.00 | 0.761965E+09 | 0.684398E+09 | 15098.45 | 18-FEB-14:00 | 13082.51 | 0.00 |
March | 0.00 | 0.00 | 0.147250E+11 | 0.145069E+11 | 43129.57 | 16-MAR-18:50 | 43129.57 | 0.00 |
April | 0.00 | 0.00 | 0.455295E+11 | 0.455169E+11 | 46241.63 | 14-APR-20:00 | 46241.63 | 0.00 |
May | 0.00 | 0.00 | 0.574165E+11 | 0.574142E+11 | 46374.74 | 31-MAY-20:00 | 46374.74 | 0.00 |
June | 0.00 | 0.00 | 0.678706E+11 | 0.677899E+11 | 47505.87 | 28-JUN-20:00 | 46930.40 | 0.00 |
July | 0.00 | 0.00 | 0.728213E+11 | 0.708547E+11 | 50923.99 | 27-JUL-06:51 | 26768.36 | 0.00 |
August | 0.00 | 0.00 | 0.732995E+11 | 0.696092E+11 | 76189.16 | 04-AUG-19:10 | 40193.40 | 0.00 |
September | 0.00 | 0.00 | 0.696820E+11 | 0.630253E+11 | 79315.67 | 10-SEP-18:55 | 31009.07 | 0.00 |
October | 0.00 | 0.00 | 0.362130E+11 | 0.353135E+11 | 46863.96 | 02-OCT-20:00 | 46071.50 | 0.00 |
November | 0.00 | 0.00 | 0.121792E+11 | 0.111577E+11 | 45063.73 | 02-NOV-20:00 | 31088.75 | 0.00 |
December | 0.00 | 0.00 | 0.452091E+10 | 0.451993E+10 | 24920.56 | 25-DEC-12:40 | 24920.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.466950E+12 | 0.452284E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.761965E+09 | 0.684398E+09 | 15098.45 | 13082.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.732995E+11 | 0.708547E+11 | 79315.67 | 46930.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE HP COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.851805E+10 | 0.848499E+10 | 24288.93 | 14-JAN-13:50 | 24288.93 | 0.00 |
February | 0.00 | 0.00 | 0.452005E+09 | 0.417792E+09 | 9463.94 | 18-FEB-14:30 | 7989.41 | 0.00 |
March | 0.00 | 0.00 | 0.632316E+10 | 0.625711E+10 | 22135.83 | 16-MAR-15:10 | 22135.83 | 0.00 |
April | 0.00 | 0.00 | 0.265524E+11 | 0.265050E+11 | 28294.02 | 14-APR-15:10 | 28294.02 | 0.00 |
May | 0.00 | 0.00 | 0.347427E+11 | 0.346996E+11 | 26125.62 | 18-MAY-15:10 | 26125.62 | 0.00 |
June | 0.00 | 0.00 | 0.505311E+11 | 0.501135E+11 | 34680.91 | 17-JUN-16:10 | 29968.73 | 0.00 |
July | 0.00 | 0.00 | 0.606925E+11 | 0.503244E+11 | 33599.18 | 14-JUL-00:10 | 13143.95 | 0.00 |
August | 0.00 | 0.00 | 0.591568E+11 | 0.491535E+11 | 34079.18 | 12-AUG-13:10 | 28109.56 | 0.00 |
September | 0.00 | 0.00 | 0.514859E+11 | 0.418425E+11 | 34183.84 | 01-SEP-13:30 | 28204.45 | 0.00 |
October | 0.00 | 0.00 | 0.236848E+11 | 0.218645E+11 | 32972.25 | 03-OCT-12:30 | 27555.69 | 0.00 |
November | 0.00 | 0.00 | 0.747570E+10 | 0.715188E+10 | 27087.74 | 01-NOV-15:10 | 25837.42 | 0.00 |
December | 0.00 | 0.00 | 0.390464E+10 | 0.390446E+10 | 22478.65 | 25-DEC-13:00 | 22478.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.333520E+12 | 0.300719E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.452005E+09 | 0.417792E+09 | 9463.94 | 7989.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.606925E+11 | 0.503244E+11 | 34680.91 | 29968.73 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN HP COOLING COIL
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.192673E+11 | 0.185676E+11 | 37292.65 | 31-JAN-16:40 | 32683.19 | 0.00 |
February | 0.00 | 0.00 | 0.408703E+10 | 0.348125E+10 | 25394.22 | 18-FEB-14:00 | 21104.91 | 0.00 |
March | 0.00 | 0.00 | 0.212937E+11 | 0.195777E+11 | 43932.63 | 20-MAR-17:20 | 34128.05 | 0.00 |
April | 0.00 | 0.00 | 0.543705E+11 | 0.500803E+11 | 46377.54 | 25-APR-17:20 | 37126.78 | 0.00 |
May | 0.00 | 0.00 | 0.676968E+11 | 0.626642E+11 | 46728.45 | 15-MAY-17:20 | 39474.00 | 0.00 |
June | 0.00 | 0.00 | 0.837848E+11 | 0.761723E+11 | 55661.00 | 17-JUN-17:20 | 40913.53 | 0.00 |
July | 0.00 | 0.00 | 0.974614E+11 | 0.778450E+11 | 56428.53 | 23-JUL-10:40 | 40871.75 | 0.00 |
August | 0.00 | 0.00 | 0.966491E+11 | 0.759629E+11 | 60657.73 | 28-AUG-16:40 | 26433.06 | 0.00 |
September | 0.00 | 0.00 | 0.887776E+11 | 0.674789E+11 | 68477.01 | 10-SEP-18:55 | 26429.37 | 0.00 |
October | 0.00 | 0.00 | 0.464991E+11 | 0.402730E+11 | 52670.36 | 03-OCT-10:40 | 37883.21 | 0.00 |
November | 0.00 | 0.00 | 0.198892E+11 | 0.169459E+11 | 44798.73 | 01-NOV-10:40 | 34009.19 | 0.00 |
December | 0.00 | 0.00 | 0.975913E+10 | 0.962653E+10 | 35921.43 | 25-DEC-16:40 | 29705.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.609536E+12 | 0.518675E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.408703E+10 | 0.348125E+10 | 25394.22 | 21104.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.974614E+11 | 0.778450E+11 | 68477.01 | 40913.53 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 22453.88 | 47070.62 | 23-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 22233.43 | 46982.87 | 01-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 21195.37 | 45631.29 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 19529.24 | 42354.08 | 03-APR-06:54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 17735.70 | 38873.47 | 01-MAY-06:57 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 16285.69 | 35277.70 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15552.20 | 32870.82 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 15786.81 | 33841.47 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16868.43 | 36672.08 | 29-SEP-06:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18527.30 | 40622.06 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 20320.12 | 44106.06 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21754.70 | 46393.76 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 19002.26 | ||||
Minimum of Months | 0.00 | 0.00 | 15552.20 | 32870.82 | ||
Maximum of Months | 0.00 | 0.00 | 22453.88 | 47070.62 |
Report: FanReportMonthly
For: RETAIL_1_FLR_1 PIU FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.306369E+09 | 0.18 | 431.48 | 01-JAN-00:05 | 0.67 |
February | 0.440860E+09 | 0.28 | 431.48 | 01-FEB-02:70 | 0.66 |
March | 0.335450E+09 | 0.19 | 431.48 | 01-MAR-01:50 | 0.66 |
April | 36032500.66 | 0.02 | 431.48 | 01-APR-03:00 | 0.67 |
May | 1682753.59 | 0.00 | 431.48 | 01-MAY-06:10 | 0.67 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.109552E+09 | 0.06 | 431.48 | 08-OCT-05:50 | 0.67 |
November | 0.236492E+09 | 0.14 | 431.48 | 04-NOV-00:10 | 0.67 |
December | 0.431126E+09 | 0.25 | 431.48 | 01-DEC-00:20 | 0.67 |
Annual Sum or Average | 0.189756E+10 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.440860E+09 | 0.28 | 431.48 | 0.67 |
Report: FanReportMonthly
For: RETAIL_2_FLR_1 PIU FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: MECH_FLR_1 PIU FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: STORAGE_FLR_1 PIU FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 14878623.04 | 0.02 | 180.48 | 01-JAN-00:05 | 0.67 |
February | 12570306.83 | 0.02 | 180.48 | 03-FEB-04:50 | 0.67 |
March | 16816958.94 | 0.02 | 180.48 | 26-MAR-01:30 | 0.67 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 5408931.74 | 0.01 | 180.48 | 23-NOV-05:50 | 0.67 |
December | 71925204.70 | 0.10 | 180.48 | 04-DEC-04:50 | 0.67 |
Annual Sum or Average | 0.121600E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71925204.70 | 0.10 | 180.48 | 0.67 |
Report: FanReportMonthly
For: LOBBY_FLR_1 PIU FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 PIU FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 730441.95 | 0.00 | 2434.81 | 06-DEC-07:10 | 0.67 |
Annual Sum or Average | 730441.95 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 730441.95 | 0.00 | 2434.81 | 0.67 |
Report: FanReportMonthly
For: DINING_FLR_6 PIU FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: VAV_FLR_1 FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118634E+11 | 1.07 | 7102.99 | 27-JAN-21:10 | 1.30 |
February | 0.982691E+10 | 1.03 | 5653.30 | 21-FEB-21:25 | 1.17 |
March | 0.113918E+11 | 1.05 | 8038.55 | 16-MAR-20:10 | 1.37 |
April | 0.135493E+11 | 1.14 | 10841.43 | 14-APR-20:10 | 1.55 |
May | 0.147149E+11 | 1.16 | 11177.44 | 31-MAY-19:10 | 1.58 |
June | 0.170052E+11 | 1.24 | 13889.73 | 28-JUN-19:10 | 1.72 |
July | 0.167394E+11 | 1.21 | 12772.63 | 20-JUL-20:10 | 1.65 |
August | 0.167155E+11 | 1.21 | 12294.65 | 10-AUG-20:10 | 1.63 |
September | 0.155597E+11 | 1.19 | 11882.48 | 07-SEP-20:10 | 1.60 |
October | 0.136985E+11 | 1.12 | 10474.58 | 03-OCT-20:10 | 1.51 |
November | 0.114251E+11 | 1.06 | 8297.84 | 01-NOV-15:10 | 1.38 |
December | 0.111183E+11 | 1.04 | 6752.04 | 22-DEC-16:10 | 1.28 |
Annual Sum or Average | 0.163608E+12 | 1.13 | |||
Minimum of Months | 0.982691E+10 | 1.03 | 5653.30 | 1.17 | |
Maximum of Months | 0.170052E+11 | 1.24 | 13889.73 | 1.72 |
Report: FanReportMonthly
For: VAV_FLR_6 FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113509E+11 | 1.17 | 6783.36 | 06-JAN-22:10 | 1.42 |
February | 0.100958E+11 | 1.16 | 6485.86 | 21-FEB-22:10 | 1.38 |
March | 0.119120E+11 | 1.19 | 8135.27 | 17-MAR-21:10 | 1.53 |
April | 0.140772E+11 | 1.29 | 9925.92 | 14-APR-21:10 | 1.67 |
May | 0.159817E+11 | 1.34 | 10400.92 | 31-MAY-18:15 | 1.71 |
June | 0.181760E+11 | 1.43 | 12236.87 | 28-JUN-18:30 | 1.83 |
July | 0.178166E+11 | 1.39 | 11216.27 | 21-JUL-21:10 | 1.74 |
August | 0.171531E+11 | 1.37 | 11138.63 | 10-AUG-21:10 | 1.74 |
September | 0.153988E+11 | 1.33 | 10599.53 | 07-SEP-21:10 | 1.70 |
October | 0.131105E+11 | 1.23 | 9660.89 | 03-OCT-21:10 | 1.64 |
November | 0.111478E+11 | 1.17 | 7725.12 | 02-NOV-21:10 | 1.49 |
December | 0.109751E+11 | 1.16 | 6445.97 | 26-DEC-22:10 | 1.40 |
Annual Sum or Average | 0.167196E+12 | 1.27 | |||
Minimum of Months | 0.100958E+11 | 1.16 | 6445.97 | 1.38 | |
Maximum of Months | 0.181760E+11 | 1.43 | 12236.87 | 1.83 |
Report: FanReportMonthly
For: VAV_FLR_0 SZVAV FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.449977E+10 | 1.21 | 1680.02 | 01-JAN-19:08 | 1.21 |
February | 0.406431E+10 | 1.20 | 1680.02 | 01-FEB-00:50 | 1.20 |
March | 0.449977E+10 | 1.20 | 1680.02 | 01-MAR-09:50 | 1.20 |
April | 0.437302E+10 | 1.21 | 2191.37 | 14-APR-20:00 | 1.35 |
May | 0.454811E+10 | 1.21 | 2408.30 | 31-MAY-18:15 | 1.41 |
June | 0.472460E+10 | 1.24 | 3455.73 | 27-JUN-19:10 | 1.64 |
July | 0.551739E+10 | 1.30 | 4406.98 | 13-JUL-21:00 | 1.80 |
August | 0.572332E+10 | 1.32 | 5278.62 | 18-AUG-22:00 | 1.94 |
September | 0.592650E+10 | 1.35 | 5595.50 | 02-SEP-20:30 | 1.99 |
October | 0.476937E+10 | 1.23 | 4127.71 | 02-OCT-20:00 | 1.75 |
November | 0.444495E+10 | 1.22 | 3212.91 | 11-NOV-21:00 | 1.57 |
December | 0.449977E+10 | 1.21 | 1680.02 | 01-DEC-00:20 | 1.21 |
Annual Sum or Average | 0.575909E+11 | 1.24 | |||
Minimum of Months | 0.406431E+10 | 1.20 | 1680.02 | 1.20 | |
Maximum of Months | 0.592650E+10 | 1.35 | 5595.50 | 1.99 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | -0.0 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | -0.0 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | -0.0 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | -0.0 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | -0.0 | 0.00 | 0.00 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | -0.0 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: ROOM_1_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.188036E+10 | 0.54 | 925.41 | 01-JAN-00:10 | 0.57 |
February | 0.164855E+10 | 0.49 | 925.41 | 01-FEB-00:10 | 0.58 |
March | 0.184718E+10 | 0.52 | 925.41 | 01-MAR-00:10 | 0.57 |
April | 0.188602E+10 | 0.56 | 925.41 | 01-APR-00:10 | 0.58 |
May | 0.196594E+10 | 0.57 | 925.41 | 01-MAY-00:10 | 0.58 |
June | 0.195699E+10 | 0.58 | 925.41 | 01-JUN-00:10 | 0.58 |
July | 0.198885E+10 | 0.58 | 925.41 | 01-JUL-00:10 | 0.57 |
August | 0.199669E+10 | 0.57 | 925.41 | 01-AUG-00:10 | 0.57 |
September | 0.191056E+10 | 0.57 | 925.41 | 01-SEP-00:10 | 0.57 |
October | 0.191723E+10 | 0.55 | 925.41 | 01-OCT-00:20 | 0.57 |
November | 0.181337E+10 | 0.53 | 925.41 | 01-NOV-00:10 | 0.57 |
December | 0.185240E+10 | 0.52 | 925.41 | 01-DEC-00:10 | 0.58 |
Annual Sum or Average | 0.226641E+11 | 0.55 | |||
Minimum of Months | 0.164855E+10 | 0.49 | 925.41 | 0.57 | |
Maximum of Months | 0.199669E+10 | 0.58 | 925.41 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.181601E+10 | 0.48 | 919.80 | 01-JAN-00:05 | 0.57 |
February | 0.161907E+10 | 0.46 | 919.80 | 01-FEB-00:10 | 0.58 |
March | 0.181126E+10 | 0.49 | 919.80 | 01-MAR-00:10 | 0.57 |
April | 0.184924E+10 | 0.55 | 919.80 | 01-APR-00:10 | 0.57 |
May | 0.194682E+10 | 0.56 | 919.80 | 01-MAY-00:10 | 0.58 |
June | 0.195098E+10 | 0.58 | 919.80 | 01-JUN-00:10 | 0.58 |
July | 0.197464E+10 | 0.58 | 919.80 | 01-JUL-00:10 | 0.57 |
August | 0.196950E+10 | 0.57 | 919.80 | 01-AUG-00:10 | 0.57 |
September | 0.187395E+10 | 0.56 | 919.80 | 01-SEP-00:20 | 0.57 |
October | 0.186109E+10 | 0.53 | 919.80 | 01-OCT-00:10 | 0.57 |
November | 0.176107E+10 | 0.49 | 919.80 | 01-NOV-00:10 | 0.57 |
December | 0.179995E+10 | 0.47 | 919.80 | 01-DEC-00:10 | 0.58 |
Annual Sum or Average | 0.222336E+11 | 0.53 | |||
Minimum of Months | 0.161907E+10 | 0.46 | 919.80 | 0.57 | |
Maximum of Months | 0.197464E+10 | 0.58 | 919.80 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.236570E+10 | 0.41 | 5338.64 | 01-JAN-15:10 | 0.58 |
February | 0.120081E+10 | 0.31 | 5338.64 | 01-FEB-15:10 | 0.58 |
March | 0.144914E+10 | 0.36 | 5338.64 | 01-MAR-15:10 | 0.57 |
April | 0.266023E+10 | 0.55 | 5338.64 | 01-APR-14:10 | 0.58 |
May | 0.288352E+10 | 0.61 | 5338.64 | 01-MAY-14:10 | 0.58 |
June | 0.369680E+10 | 0.65 | 5338.64 | 01-JUN-14:10 | 0.57 |
July | 0.366988E+10 | 0.64 | 5338.64 | 01-JUL-14:10 | 0.58 |
August | 0.373668E+10 | 0.64 | 5338.64 | 01-AUG-14:10 | 0.57 |
September | 0.354433E+10 | 0.64 | 5338.64 | 01-SEP-14:10 | 0.57 |
October | 0.288887E+10 | 0.52 | 5338.64 | 01-OCT-14:10 | 0.57 |
November | 0.212645E+10 | 0.43 | 5338.64 | 01-NOV-14:10 | 0.57 |
December | 0.187310E+10 | 0.36 | 5338.64 | 01-DEC-15:10 | 0.58 |
Annual Sum or Average | 0.320955E+11 | 0.51 | |||
Minimum of Months | 0.120081E+10 | 0.31 | 5338.64 | 0.57 | |
Maximum of Months | 0.373668E+10 | 0.65 | 5338.64 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105210E+11 | 0.45 | 5428.35 | 01-JAN-00:05 | 0.57 |
February | 0.948652E+10 | 0.42 | 5428.35 | 01-FEB-00:10 | 0.58 |
March | 0.105696E+11 | 0.47 | 5428.35 | 01-MAR-00:10 | 0.57 |
April | 0.105361E+11 | 0.54 | 5428.35 | 01-APR-00:10 | 0.58 |
May | 0.110732E+11 | 0.55 | 5428.35 | 01-MAY-00:10 | 0.58 |
June | 0.110974E+11 | 0.57 | 5428.35 | 01-JUN-00:10 | 0.58 |
July | 0.113155E+11 | 0.57 | 5428.35 | 01-JUL-00:10 | 0.57 |
August | 0.112432E+11 | 0.56 | 5428.35 | 01-AUG-00:10 | 0.57 |
September | 0.107710E+11 | 0.55 | 5428.35 | 01-SEP-00:10 | 0.57 |
October | 0.107451E+11 | 0.51 | 5428.35 | 01-OCT-00:10 | 0.57 |
November | 0.102051E+11 | 0.46 | 5428.35 | 01-NOV-00:10 | 0.57 |
December | 0.105057E+11 | 0.43 | 5428.35 | 01-DEC-00:10 | 0.58 |
Annual Sum or Average | 0.128069E+12 | 0.51 | |||
Minimum of Months | 0.948652E+10 | 0.42 | 5428.35 | 0.57 | |
Maximum of Months | 0.113155E+11 | 0.57 | 5428.35 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163372E+10 | 0.55 | 802.66 | 01-JAN-00:05 | 0.57 |
February | 0.143624E+10 | 0.51 | 802.66 | 01-FEB-00:10 | 0.58 |
March | 0.161196E+10 | 0.54 | 802.66 | 01-MAR-00:10 | 0.57 |
April | 0.166747E+10 | 0.58 | 802.66 | 01-APR-00:10 | 0.58 |
May | 0.174700E+10 | 0.59 | 802.66 | 01-MAY-00:10 | 0.58 |
June | 0.175481E+10 | 0.59 | 802.66 | 01-JUN-00:10 | 0.58 |
July | 0.178825E+10 | 0.58 | 802.66 | 01-JUL-00:10 | 0.57 |
August | 0.178797E+10 | 0.58 | 802.66 | 01-AUG-00:10 | 0.57 |
September | 0.169649E+10 | 0.58 | 802.66 | 01-SEP-00:10 | 0.57 |
October | 0.168830E+10 | 0.57 | 802.66 | 01-OCT-00:10 | 0.57 |
November | 0.157160E+10 | 0.54 | 802.66 | 01-NOV-00:10 | 0.57 |
December | 0.160529E+10 | 0.53 | 802.66 | 01-DEC-00:20 | 0.58 |
Annual Sum or Average | 0.199891E+11 | 0.56 | |||
Minimum of Months | 0.143624E+10 | 0.51 | 802.66 | 0.57 | |
Maximum of Months | 0.178825E+10 | 0.59 | 802.66 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155622E+10 | 0.52 | 795.08 | 01-JAN-00:05 | 0.57 |
February | 0.139598E+10 | 0.47 | 795.08 | 01-FEB-00:10 | 0.58 |
March | 0.157219E+10 | 0.52 | 795.08 | 01-MAR-00:10 | 0.57 |
April | 0.162036E+10 | 0.56 | 795.08 | 01-APR-00:10 | 0.58 |
May | 0.170957E+10 | 0.56 | 795.08 | 01-MAY-00:10 | 0.58 |
June | 0.174557E+10 | 0.58 | 795.08 | 01-JUN-00:10 | 0.58 |
July | 0.176887E+10 | 0.58 | 795.08 | 01-JUL-00:10 | 0.57 |
August | 0.175470E+10 | 0.57 | 795.08 | 01-AUG-00:10 | 0.57 |
September | 0.165075E+10 | 0.56 | 795.08 | 01-SEP-00:10 | 0.57 |
October | 0.162181E+10 | 0.55 | 795.08 | 01-OCT-00:10 | 0.57 |
November | 0.150849E+10 | 0.50 | 795.08 | 01-NOV-00:10 | 0.57 |
December | 0.154401E+10 | 0.46 | 795.08 | 01-DEC-00:10 | 0.58 |
Annual Sum or Average | 0.194485E+11 | 0.54 | |||
Minimum of Months | 0.139598E+10 | 0.46 | 795.08 | 0.57 | |
Maximum of Months | 0.176887E+10 | 0.58 | 795.08 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.515421E+09 | 0.53 | 254.82 | 01-JAN-00:05 | 0.57 |
February | 0.453135E+09 | 0.48 | 254.82 | 01-FEB-00:10 | 0.58 |
March | 0.507974E+09 | 0.52 | 254.82 | 01-MAR-00:20 | 0.57 |
April | 0.521845E+09 | 0.56 | 254.82 | 01-APR-00:10 | 0.58 |
May | 0.545287E+09 | 0.57 | 254.82 | 01-MAY-00:10 | 0.58 |
June | 0.544923E+09 | 0.58 | 254.82 | 01-JUN-00:20 | 0.58 |
July | 0.552999E+09 | 0.58 | 254.82 | 01-JUL-00:10 | 0.57 |
August | 0.554689E+09 | 0.57 | 254.82 | 01-AUG-00:10 | 0.57 |
September | 0.528489E+09 | 0.57 | 254.82 | 01-SEP-00:10 | 0.57 |
October | 0.527533E+09 | 0.55 | 254.82 | 01-OCT-00:10 | 0.57 |
November | 0.497556E+09 | 0.52 | 254.82 | 01-NOV-00:10 | 0.57 |
December | 0.508075E+09 | 0.51 | 254.82 | 01-DEC-00:10 | 0.58 |
Annual Sum or Average | 0.625793E+10 | 0.55 | |||
Minimum of Months | 0.453135E+09 | 0.48 | 254.82 | 0.57 | |
Maximum of Months | 0.554689E+09 | 0.58 | 254.82 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.498800E+09 | 0.48 | 253.09 | 01-JAN-00:05 | 0.57 |
February | 0.445140E+09 | 0.45 | 253.09 | 01-FEB-00:10 | 0.58 |
March | 0.498338E+09 | 0.49 | 253.09 | 01-MAR-00:10 | 0.57 |
April | 0.512018E+09 | 0.55 | 253.09 | 01-APR-00:10 | 0.57 |
May | 0.540094E+09 | 0.56 | 253.09 | 01-MAY-00:10 | 0.58 |
June | 0.542937E+09 | 0.58 | 253.09 | 01-JUN-00:10 | 0.58 |
July | 0.548897E+09 | 0.58 | 253.09 | 01-JUL-00:10 | 0.57 |
August | 0.547361E+09 | 0.57 | 253.09 | 01-AUG-00:10 | 0.57 |
September | 0.518882E+09 | 0.56 | 253.09 | 01-SEP-00:10 | 0.57 |
October | 0.512825E+09 | 0.52 | 253.09 | 01-OCT-00:10 | 0.57 |
November | 0.483691E+09 | 0.49 | 253.09 | 01-NOV-00:10 | 0.57 |
December | 0.494725E+09 | 0.47 | 253.09 | 01-DEC-00:10 | 0.58 |
Annual Sum or Average | 0.614371E+10 | 0.53 | |||
Minimum of Months | 0.445140E+09 | 0.45 | 253.09 | 0.57 | |
Maximum of Months | 0.548897E+09 | 0.58 | 253.09 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.240852E+10 | 0.55 | 1134.32 | 01-JAN-00:05 | 0.57 |
February | 0.206746E+10 | 0.50 | 1134.32 | 01-FEB-00:10 | 0.58 |
March | 0.229481E+10 | 0.53 | 1134.32 | 01-MAR-00:10 | 0.57 |
April | 0.233461E+10 | 0.56 | 1134.32 | 01-APR-00:10 | 0.58 |
May | 0.240074E+10 | 0.57 | 1134.32 | 01-MAY-00:10 | 0.58 |
June | 0.238741E+10 | 0.58 | 1134.32 | 01-JUN-00:10 | 0.58 |
July | 0.245287E+10 | 0.58 | 1134.32 | 01-JUL-00:10 | 0.57 |
August | 0.248057E+10 | 0.57 | 1134.32 | 01-AUG-00:10 | 0.57 |
September | 0.239498E+10 | 0.57 | 1134.32 | 01-SEP-00:10 | 0.57 |
October | 0.242767E+10 | 0.56 | 1134.32 | 01-OCT-00:10 | 0.57 |
November | 0.229837E+10 | 0.54 | 1134.32 | 01-NOV-00:10 | 0.57 |
December | 0.236792E+10 | 0.53 | 1134.32 | 01-DEC-00:10 | 0.58 |
Annual Sum or Average | 0.283159E+11 | 0.55 | |||
Minimum of Months | 0.206746E+10 | 0.50 | 1134.32 | 0.57 | |
Maximum of Months | 0.248057E+10 | 0.58 | 1134.32 | 0.58 |
Report: FanReportMonthly
For: PTAC_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.442512E+09 | 0.55 | 480.69 | 31-JAN-16:13 | 0.64 |
February | 0.237783E+09 | 0.46 | 344.19 | 16-FEB-13:30 | 0.65 |
March | 0.391941E+09 | 0.53 | 460.03 | 16-MAR-15:13 | 0.64 |
April | 0.786277E+09 | 0.65 | 672.30 | 14-APR-18:03 | 0.62 |
May | 0.948241E+09 | 0.65 | 751.92 | 31-MAY-18:15 | 0.62 |
June | 0.129931E+10 | 0.64 | 1018.97 | 28-JUN-18:25 | 0.60 |
July | 0.135396E+10 | 0.63 | 866.63 | 20-JUL-18:15 | 0.61 |
August | 0.132066E+10 | 0.63 | 888.72 | 25-AUG-15:14 | 0.61 |
September | 0.116983E+10 | 0.64 | 813.89 | 28-SEP-15:10 | 0.61 |
October | 0.759018E+09 | 0.63 | 714.81 | 06-OCT-15:10 | 0.62 |
November | 0.457373E+09 | 0.58 | 575.76 | 01-NOV-15:10 | 0.63 |
December | 0.275139E+09 | 0.45 | 454.85 | 25-DEC-13:00 | 0.64 |
Annual Sum or Average | 0.944205E+10 | 0.59 | |||
Minimum of Months | 0.237783E+09 | 0.45 | 344.19 | 0.60 | |
Maximum of Months | 0.135396E+10 | 0.65 | 1018.97 | 0.65 |
Report: FanReportMonthly
For: PTAC_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.197883E+09 | 0.37 | 322.24 | 14-JAN-13:40 | 0.63 |
February | 98300649.35 | 0.27 | 306.07 | 16-FEB-13:30 | 0.64 |
March | 0.201592E+09 | 0.40 | 375.08 | 18-MAR-15:00 | 0.63 |
April | 0.524885E+09 | 0.61 | 567.09 | 14-APR-15:10 | 0.61 |
May | 0.658889E+09 | 0.64 | 535.79 | 04-MAY-14:10 | 0.61 |
June | 0.902695E+09 | 0.63 | 676.42 | 15-JUN-15:10 | 0.60 |
July | 0.903770E+09 | 0.63 | 627.18 | 19-JUL-13:00 | 0.60 |
August | 0.870269E+09 | 0.63 | 681.24 | 26-AUG-15:00 | 0.59 |
September | 0.735240E+09 | 0.64 | 613.60 | 07-SEP-14:10 | 0.60 |
October | 0.426790E+09 | 0.54 | 569.92 | 02-OCT-13:10 | 0.60 |
November | 0.209790E+09 | 0.42 | 402.35 | 01-NOV-15:10 | 0.63 |
December | 0.108906E+09 | 0.25 | 313.37 | 25-DEC-13:00 | 0.64 |
Annual Sum or Average | 0.583901E+10 | 0.50 | |||
Minimum of Months | 98300649.35 | 0.25 | 306.07 | 0.59 | |
Maximum of Months | 0.903770E+09 | 0.64 | 681.24 | 0.64 |
Report: FanReportMonthly
For: PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.185570E+11 | 1.47 | 6928.37 | 03-JAN-10:40 | 1.47 |
February | 0.167611E+11 | 1.46 | 6928.37 | 01-FEB-15:00 | 1.47 |
March | 0.185570E+11 | 1.46 | 6928.37 | 01-MAR-10:30 | 1.46 |
April | 0.179583E+11 | 1.47 | 6928.37 | 01-APR-18:08 | 1.47 |
May | 0.185570E+11 | 1.47 | 6928.37 | 06-MAY-06:30 | 1.47 |
June | 0.179583E+11 | 1.46 | 6928.37 | 05-JUN-17:30 | 1.46 |
July | 0.185570E+11 | 1.46 | 6928.37 | 01-JUL-18:05 | 1.47 |
August | 0.185570E+11 | 1.46 | 6928.37 | 01-AUG-17:40 | 1.45 |
September | 0.179583E+11 | 1.45 | 6928.37 | 02-SEP-23:40 | 1.44 |
October | 0.185570E+11 | 1.46 | 6928.37 | 01-OCT-18:02 | 1.46 |
November | 0.179583E+11 | 1.46 | 6928.37 | 01-NOV-17:40 | 1.46 |
December | 0.185570E+11 | 1.47 | 6928.37 | 01-DEC-03:50 | 1.47 |
Annual Sum or Average | 0.218493E+12 | 1.46 | |||
Minimum of Months | 0.167611E+11 | 1.45 | 6928.37 | 1.44 | |
Maximum of Months | 0.185570E+11 | 1.47 | 6928.37 | 1.47 |
Report: FanReportMonthly
For: PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.997002E+10 | 1.50 | 3722.38 | 01-JAN-01:40 | 1.50 |
February | 0.900518E+10 | 1.49 | 3722.38 | 09-FEB-04:10 | 1.49 |
March | 0.997002E+10 | 1.50 | 3722.38 | 25-MAR-08:62 | 1.50 |
April | 0.964840E+10 | 1.50 | 3722.38 | 07-APR-21:30 | 1.50 |
May | 0.997002E+10 | 1.50 | 3722.38 | 02-MAY-05:35 | 1.50 |
June | 0.964840E+10 | 1.50 | 3722.38 | 01-JUN-19:20 | 1.49 |
July | 0.997002E+10 | 1.49 | 3722.38 | 19-JUL-16:40 | 1.49 |
August | 0.997002E+10 | 1.49 | 3722.38 | 08-AUG-17:05 | 1.49 |
September | 0.964840E+10 | 1.49 | 3722.38 | 04-SEP-11:00 | 1.48 |
October | 0.997002E+10 | 1.50 | 3722.38 | 15-OCT-07:55 | 1.51 |
November | 0.964840E+10 | 1.50 | 3722.38 | 04-NOV-13:00 | 1.50 |
December | 0.997002E+10 | 1.50 | 3722.38 | 09-DEC-11:35 | 1.51 |
Annual Sum or Average | 0.117389E+12 | 1.50 | |||
Minimum of Months | 0.900518E+10 | 1.49 | 3722.38 | 1.48 | |
Maximum of Months | 0.997002E+10 | 1.50 | 3722.38 | 1.51 |
Report: FanReportMonthly
For: PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129044E+11 | 1.46 | 4817.96 | 11-JAN-16:12 | 1.46 |
February | 0.116556E+11 | 1.46 | 4817.96 | 03-FEB-17:30 | 1.47 |
March | 0.129044E+11 | 1.46 | 4817.96 | 07-MAR-18:03 | 1.46 |
April | 0.124881E+11 | 1.46 | 4817.96 | 01-APR-23:40 | 1.47 |
May | 0.129044E+11 | 1.46 | 4817.96 | 03-MAY-05:50 | 1.47 |
June | 0.124881E+11 | 1.46 | 4817.96 | 11-JUN-09:00 | 1.45 |
July | 0.129044E+11 | 1.45 | 4817.96 | 01-JUL-05:40 | 1.47 |
August | 0.129044E+11 | 1.45 | 4817.96 | 02-AUG-08:05 | 1.45 |
September | 0.124881E+11 | 1.45 | 4817.96 | 06-SEP-06:25 | 1.45 |
October | 0.129044E+11 | 1.46 | 4817.96 | 02-OCT-07:05 | 1.45 |
November | 0.124881E+11 | 1.46 | 4817.96 | 10-NOV-12:00 | 1.46 |
December | 0.129044E+11 | 1.47 | 4817.96 | 08-DEC-11:25 | 1.47 |
Annual Sum or Average | 0.151939E+12 | 1.46 | |||
Minimum of Months | 0.116556E+11 | 1.45 | 4817.96 | 1.45 | |
Maximum of Months | 0.129044E+11 | 1.47 | 4817.96 | 1.47 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 50.48 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 51.57 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 51.81 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 54.24 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 54.75 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 55.24 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 55.55 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 55.62 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 55.43 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 54.41 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 54.50 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 52.07 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 50.48 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 55.62 | 0.37 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 50.48 | 60.05 | 22453.88 | 47070.62 | 23-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 51.57 | 60.05 | 22233.43 | 46982.87 | 01-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 51.81 | 60.05 | 21195.37 | 45631.29 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 54.24 | 60.05 | 19529.24 | 42354.08 | 03-APR-06:54 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 54.75 | 60.05 | 17735.70 | 38873.47 | 01-MAY-06:57 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 55.24 | 60.05 | 16285.69 | 35277.70 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.55 | 60.05 | 15552.20 | 32870.82 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 55.62 | 60.05 | 15786.81 | 33841.47 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 55.43 | 60.05 | 16868.43 | 36672.08 | 29-SEP-06:55 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.41 | 60.05 | 18527.30 | 40622.06 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 54.50 | 60.05 | 20320.12 | 44106.06 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 52.07 | 60.05 | 21754.70 | 46393.76 | 29-DEC-07:30 |
Annual Sum or Average | 0.00 | 19002.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.48 | 60.05 | 15552.20 | 32870.82 | ||
Maximum of Months | 0.00 | 0.00 | 55.62 | 60.05 | 22453.88 | 47070.62 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.243166E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.155067E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.247704E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.408880E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.507870E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.681847E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.703623E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.689654E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.613995E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.379043E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.242836E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.266238E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.513992E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.155067E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.703623E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.260170E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.182968E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.270863E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.398141E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.511576E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.683111E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.703951E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.670835E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.581585E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.352800E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.252755E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.313263E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.518202E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.182968E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.703951E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.102943E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.620408E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.841344E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.154896E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.185646E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.246262E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.308509E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.318821E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.313806E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.200090E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.147790E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.100505E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.222544E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.620408E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.318821E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.220596E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.169952E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.227953E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.315490E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.362706E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.405551E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.417933E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.416607E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.389446E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.292956E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.214962E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.199143E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.363329E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.169952E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.417933E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.124438E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.918725E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.120145E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.175492E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.206245E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.259396E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.279254E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.275366E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.244987E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.168238E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.118307E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.116825E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.218056E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.918725E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.279254E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.180646E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128126E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.186108E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.276005E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.323770E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.386117E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.418805E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.414418E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.376488E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.257569E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.178048E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.155696E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.328180E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.128126E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.418805E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.121846E+11 | 0.304087E+11 | 0.318274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102803E+11 | 0.789753E+10 | 0.273930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117440E+11 | 0.321480E+11 | 0.352317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135853E+11 | 0.976679E+11 | 32485353.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147166E+11 | 0.128400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170052E+11 | 0.174721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167394E+11 | 0.194940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167155E+11 | 0.189096E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155597E+11 | 0.169643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138081E+11 | 0.843593E+11 | 0.464838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116670E+11 | 0.352524E+11 | 0.230027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116213E+11 | 0.157285E+11 | 0.102643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165627E+12 | 0.116026E+13 | 0.225071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102803E+11 | 0.789753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170052E+11 | 0.194940E+12 | 0.102643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.113509E+11 | 0.254279E+11 | 0.711565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100958E+11 | 0.739537E+10 | 0.587855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119120E+11 | 0.301742E+11 | 0.634419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140772E+11 | 0.925101E+11 | 0.145665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159817E+11 | 0.126456E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181760E+11 | 0.172206E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178166E+11 | 0.192299E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171531E+11 | 0.182069E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153988E+11 | 0.159464E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131105E+11 | 0.745585E+11 | 0.133792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111478E+11 | 0.310058E+11 | 0.503944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109759E+11 | 0.135449E+11 | 0.162490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167196E+12 | 0.110711E+13 | 0.421104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100958E+11 | 0.739537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181760E+11 | 0.192299E+12 | 0.162490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.449977E+10 | 0.192501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406431E+10 | 0.707102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449977E+10 | 0.128007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437302E+10 | 0.355334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.454811E+10 | 0.435191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472460E+10 | 0.594464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.551739E+10 | 0.842728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572332E+10 | 0.882688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.592650E+10 | 0.895004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.476937E+10 | 0.528970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444495E+10 | 0.364261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.449977E+10 | 0.183262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.575909E+11 | 0.547312E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.406431E+10 | 0.707102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.592650E+10 | 0.895004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.185570E+11 | 0.119306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167611E+11 | 0.761965E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185570E+11 | 0.147250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179583E+11 | 0.455295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185570E+11 | 0.574165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179583E+11 | 0.678706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185570E+11 | 0.728213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185570E+11 | 0.732995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179583E+11 | 0.696820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185570E+11 | 0.362130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179583E+11 | 0.121792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185570E+11 | 0.452091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218493E+12 | 0.466950E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167611E+11 | 0.761965E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.185570E+11 | 0.732995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.997002E+10 | 0.851805E+10 | 0.276296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.900518E+10 | 0.452005E+09 | 0.137297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.997002E+10 | 0.632316E+10 | 0.549349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.964840E+10 | 0.265524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.997002E+10 | 0.347427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.964840E+10 | 0.505311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.997002E+10 | 0.606925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.997002E+10 | 0.591568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.964840E+10 | 0.514859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.997002E+10 | 0.236848E+11 | 26518478.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.964840E+10 | 0.747570E+10 | 0.230911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.997002E+10 | 0.390464E+10 | 0.154352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117389E+12 | 0.333520E+12 | 0.276389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.900518E+10 | 0.452005E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.997002E+10 | 0.606925E+11 | 0.154352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.129044E+11 | 0.192673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116556E+11 | 0.408703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129044E+11 | 0.212937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124881E+11 | 0.543705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129044E+11 | 0.676968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124881E+11 | 0.837848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129044E+11 | 0.974614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129044E+11 | 0.966491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124881E+11 | 0.887776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129044E+11 | 0.464991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124881E+11 | 0.198892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129044E+11 | 0.975913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151939E+12 | 0.609536E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.116556E+11 | 0.408703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129044E+11 | 0.974614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.121846E+11 | 0.00 | 0.00 | 0.00 | 0.894920E+10 | 0.318274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102803E+11 | 0.00 | 0.00 | 0.00 | 0.248707E+10 | 0.273930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117440E+11 | 0.00 | 0.00 | 0.00 | 0.950321E+10 | 0.352317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135853E+11 | 0.00 | 0.00 | 0.00 | 0.272702E+11 | 32485353.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147166E+11 | 0.00 | 0.00 | 0.00 | 0.360704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170052E+11 | 0.00 | 0.00 | 0.00 | 0.511795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167394E+11 | 0.00 | 0.00 | 0.00 | 0.536229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167155E+11 | 0.00 | 0.00 | 0.00 | 0.522499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155597E+11 | 0.00 | 0.00 | 0.00 | 0.458398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138081E+11 | 0.00 | 0.00 | 0.00 | 0.236314E+11 | 0.464838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116670E+11 | 0.00 | 0.00 | 0.00 | 0.103163E+11 | 0.230027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116213E+11 | 0.00 | 0.00 | 0.00 | 0.473820E+10 | 0.102643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165627E+12 | 0.00 | 0.00 | 0.00 | 0.325858E+12 | 0.225071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102803E+11 | 0.00 | 0.00 | 0.00 | 0.248707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170052E+11 | 0.00 | 0.00 | 0.00 | 0.536229E+11 | 0.102643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.113509E+11 | 0.00 | 0.00 | 0.00 | 0.755047E+10 | 0.711565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100958E+11 | 0.00 | 0.00 | 0.00 | 0.232248E+10 | 0.587855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119120E+11 | 0.00 | 0.00 | 0.00 | 0.883004E+10 | 0.634419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140772E+11 | 0.00 | 0.00 | 0.00 | 0.255913E+11 | 0.145665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159817E+11 | 0.00 | 0.00 | 0.00 | 0.351759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181760E+11 | 0.00 | 0.00 | 0.00 | 0.501351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178166E+11 | 0.00 | 0.00 | 0.00 | 0.525784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171531E+11 | 0.00 | 0.00 | 0.00 | 0.499304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153988E+11 | 0.00 | 0.00 | 0.00 | 0.427598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131105E+11 | 0.00 | 0.00 | 0.00 | 0.208315E+11 | 0.133792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111478E+11 | 0.00 | 0.00 | 0.00 | 0.908826E+10 | 0.503944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109759E+11 | 0.00 | 0.00 | 0.00 | 0.410147E+10 | 0.162490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167196E+12 | 0.00 | 0.00 | 0.00 | 0.308895E+12 | 0.421104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100958E+11 | 0.00 | 0.00 | 0.00 | 0.232248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181760E+11 | 0.00 | 0.00 | 0.00 | 0.525784E+11 | 0.162490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.449977E+10 | 0.00 | 0.00 | 0.00 | 0.579452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406431E+10 | 0.00 | 0.00 | 0.00 | 0.213977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449977E+10 | 0.00 | 0.00 | 0.00 | 0.391366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437302E+10 | 0.00 | 0.00 | 0.00 | 0.111166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.454811E+10 | 0.00 | 0.00 | 0.00 | 0.140164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472460E+10 | 0.00 | 0.00 | 0.00 | 0.199016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.551739E+10 | 0.00 | 0.00 | 0.00 | 0.253335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.572332E+10 | 0.00 | 0.00 | 0.00 | 0.261587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.592650E+10 | 0.00 | 0.00 | 0.00 | 0.254541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.476937E+10 | 0.00 | 0.00 | 0.00 | 0.152396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444495E+10 | 0.00 | 0.00 | 0.00 | 0.103341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.449977E+10 | 0.00 | 0.00 | 0.00 | 0.555074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.575909E+11 | 0.00 | 0.00 | 0.00 | 0.164953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.406431E+10 | 0.00 | 0.00 | 0.00 | 0.213977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.592650E+10 | 0.00 | 0.00 | 0.00 | 0.261587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.185570E+11 | 0.00 | 0.00 | 2160000.00 | 0.350047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167611E+11 | 0.00 | 0.00 | 0.00 | 0.234111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185570E+11 | 0.00 | 0.00 | 3840000.00 | 0.423454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179583E+11 | 0.00 | 0.00 | 0.00 | 0.135906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185570E+11 | 0.00 | 0.00 | 0.00 | 0.177136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179583E+11 | 0.00 | 0.00 | 0.00 | 0.225967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.185570E+11 | 0.00 | 0.00 | 0.00 | 0.232364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185570E+11 | 0.00 | 0.00 | 0.00 | 0.231037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179583E+11 | 0.00 | 0.00 | 0.00 | 0.209862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185570E+11 | 0.00 | 0.00 | 0.00 | 0.107386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179583E+11 | 0.00 | 0.00 | 2370000.00 | 0.353549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185570E+11 | 0.00 | 0.00 | 16049998.57 | 0.134134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218493E+12 | 0.00 | 0.00 | 24419998.57 | 0.144812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167611E+11 | 0.00 | 0.00 | 0.00 | 0.234111E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.185570E+11 | 0.00 | 0.00 | 16049998.57 | 0.232364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.997002E+10 | 0.00 | 0.00 | 0.115454E+09 | 0.235830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.900518E+10 | 0.00 | 0.00 | 48796868.46 | 0.133274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.997002E+10 | 0.00 | 0.00 | 0.210452E+09 | 0.183402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.964840E+10 | 0.00 | 0.00 | 0.00 | 0.790081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.997002E+10 | 0.00 | 0.00 | 0.00 | 0.106545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.964840E+10 | 0.00 | 0.00 | 0.00 | 0.162912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.997002E+10 | 0.00 | 0.00 | 0.00 | 0.179554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.997002E+10 | 0.00 | 0.00 | 0.00 | 0.175665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.964840E+10 | 0.00 | 0.00 | 0.00 | 0.148503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.997002E+10 | 0.00 | 0.00 | 9406435.35 | 0.684438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.964840E+10 | 0.00 | 0.00 | 93883341.12 | 0.208846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.997002E+10 | 0.00 | 0.00 | 0.620890E+09 | 0.109155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117389E+12 | 0.00 | 0.00 | 0.109888E+10 | 0.995686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.900518E+10 | 0.00 | 0.00 | 0.00 | 0.133274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.997002E+10 | 0.00 | 0.00 | 0.620890E+09 | 0.179554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.129044E+11 | 0.00 | 0.00 | 2160000.00 | 0.515799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116556E+11 | 0.00 | 0.00 | 0.00 | 0.115699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129044E+11 | 0.00 | 0.00 | 3840000.00 | 0.570257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124881E+11 | 0.00 | 0.00 | 0.00 | 0.151124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129044E+11 | 0.00 | 0.00 | 0.00 | 0.194726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124881E+11 | 0.00 | 0.00 | 0.00 | 0.261236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129044E+11 | 0.00 | 0.00 | 0.00 | 0.289761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129044E+11 | 0.00 | 0.00 | 0.00 | 0.285374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124881E+11 | 0.00 | 0.00 | 0.00 | 0.251607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129044E+11 | 0.00 | 0.00 | 0.00 | 0.128525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124881E+11 | 0.00 | 0.00 | 2370000.00 | 0.531432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129044E+11 | 0.00 | 0.00 | 16050000.00 | 0.264908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151939E+12 | 0.00 | 0.00 | 24420000.00 | 0.176216E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.116556E+11 | 0.00 | 0.00 | 0.00 | 0.115699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129044E+11 | 0.00 | 0.00 | 16050000.00 | 0.289761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169983E+09 | 56383713.35 | 0.00 | 98556075.17 | 0.00 | 0.00 | 0.359429E+11 | 0.00 | 0.86 |
February | 20994726.50 | 0.00 | 0.00 | 67418760.86 | 0.00 | 0.00 | 0.369963E+11 | 0.00 | 0.84 |
March | 0.314783E+10 | 0.214731E+09 | 0.00 | 64655900.25 | 0.00 | 0.00 | 0.299145E+11 | 0.00 | 0.83 |
April | 0.00 | 0.346783E+10 | 0.00 | 60300417.66 | 0.00 | 0.00 | 0.156921E+11 | 0.00 | 0.80 |
May | 0.00 | 0.636175E+10 | 0.00 | 45776003.75 | 0.00 | 0.00 | 0.103124E+11 | 0.00 | 0.76 |
June | 0.00 | 0.133232E+11 | 0.00 | 26676210.37 | 0.00 | 0.00 | 0.333454E+10 | 0.00 | 0.69 |
July | 0.00 | 0.253586E+11 | 0.00 | 8382830.73 | 0.00 | 0.00 | 0.115628E+10 | 0.00 | 0.68 |
August | 0.00 | 0.249363E+11 | 0.00 | 7258712.82 | 0.00 | 0.00 | 0.783924E+09 | 0.00 | 0.71 |
September | 0.00 | 0.230843E+11 | 0.00 | 14848359.52 | 0.00 | 0.00 | 0.111946E+10 | 0.00 | 0.78 |
October | 0.00 | 0.515375E+10 | 0.00 | 90878646.66 | 0.00 | 0.00 | 0.193338E+11 | 0.00 | 0.85 |
November | 0.00 | 0.163713E+10 | 0.00 | 0.104191E+09 | 0.00 | 0.00 | 0.287244E+11 | 0.00 | 0.90 |
December | 14317745.84 | 12281094.90 | 0.00 | 0.110617E+09 | 0.00 | 0.00 | 0.443092E+11 | 0.00 | 0.84 |
Annual Sum or Average | 0.335312E+10 | 0.103606E+12 | 0.00 | 0.699560E+09 | 0.00 | 0.00 | 0.227620E+12 | 0.00 | 0.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 7258712.82 | 0.00 | 0.00 | 0.783924E+09 | 0.00 | 0.68 |
Maximum of Months | 0.314783E+10 | 0.253586E+11 | 0.00 | 0.110617E+09 | 0.00 | 0.00 | 0.443092E+11 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.363277E+10 | 12613490.32 | 0.00 | 7250740.99 | 326629.16 | 0.186426E+09 | 0.171127E+10 | 0.00 | 2.67 |
February | 0.396476E+10 | 0.00 | 0.00 | 2535663.71 | 2721.14 | 0.326857E+09 | 0.118521E+10 | 0.00 | 2.22 |
March | 0.356895E+10 | 29143244.33 | 0.00 | 3156750.85 | 575997.74 | 0.466427E+09 | 0.838833E+09 | 0.00 | 2.22 |
April | 0.196425E+10 | 0.710214E+09 | 0.00 | 2738995.27 | 978971.37 | 0.00 | 0.497333E+09 | 0.00 | 2.38 |
May | 0.135710E+10 | 0.111729E+10 | 0.00 | 1457848.96 | 3464011.13 | 0.00 | 0.335403E+09 | 0.00 | 2.14 |
June | 0.360079E+09 | 0.233628E+10 | 0.00 | 1456272.85 | 1693731.82 | 0.00 | 0.312188E+09 | 0.00 | 2.05 |
July | 0.144143E+09 | 0.262009E+10 | 0.00 | 936774.56 | 32124659.67 | 0.00 | 0.149197E+09 | 0.00 | 1.97 |
August | 0.150563E+09 | 0.249849E+10 | 0.00 | 1111422.23 | 32803412.11 | 0.00 | 0.188648E+09 | 0.00 | 2.09 |
September | 0.321683E+09 | 0.196507E+10 | 0.00 | 1105216.90 | 91051152.63 | 0.00 | 0.246207E+09 | 0.00 | 2.23 |
October | 0.237219E+10 | 0.653085E+09 | 0.00 | 4620744.48 | 4431469.36 | 8162894.58 | 0.944823E+09 | 0.00 | 2.58 |
November | 0.336543E+10 | 33518422.50 | 0.00 | 5685309.28 | 13994473.15 | 0.180412E+09 | 0.146552E+10 | 0.00 | 2.60 |
December | 0.366925E+10 | 1514359.88 | 0.00 | 4996468.50 | 138528.81 | 0.110274E+10 | 0.157479E+10 | 0.00 | 2.40 |
Annual Sum or Average | 0.248712E+11 | 0.119773E+11 | 0.00 | 37052208.58 | 0.181586E+09 | 0.227103E+10 | 0.944942E+10 | 0.00 | 2.30 |
Minimum of Months | 0.144143E+09 | 0.00 | 0.00 | 936774.56 | 2721.14 | 0.00 | 0.149197E+09 | 0.00 | 1.97 |
Maximum of Months | 0.396476E+10 | 0.262009E+10 | 0.00 | 7250740.99 | 91051152.63 | 0.110274E+10 | 0.171127E+10 | 0.00 | 2.67 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.225178E+10 | 3767163.36 | 0.00 | 3468242.99 | 319048.69 | 0.00 | 0.202404E+10 | 0.00 | 1.47 |
February | 0.298707E+10 | 0.00 | 0.00 | 1203166.04 | 2221.67 | 0.00 | 0.126690E+10 | 0.00 | 1.43 |
March | 0.236190E+10 | 6643516.06 | 0.00 | 2666733.45 | 8576203.02 | 0.00 | 0.167731E+10 | 0.00 | 1.51 |
April | 0.368377E+09 | 0.300469E+09 | 0.00 | 3751570.27 | 13381011.66 | 0.00 | 0.175327E+10 | 0.00 | 1.50 |
May | 89997840.17 | 0.573291E+09 | 0.00 | 3125068.51 | 12876040.09 | 0.00 | 0.135625E+10 | 0.00 | 1.37 |
June | 700859.05 | 0.120166E+10 | 0.00 | 3373987.88 | 5428193.76 | 0.00 | 0.579184E+09 | 0.00 | 1.20 |
July | 899641.87 | 0.151348E+10 | 0.00 | 1712575.80 | 10273611.42 | 0.00 | 0.252643E+09 | 0.00 | 1.15 |
August | 1681746.55 | 0.129406E+10 | 0.00 | 2207283.68 | 17338586.07 | 0.00 | 0.294555E+09 | 0.00 | 1.21 |
September | 7476475.59 | 0.102035E+10 | 0.00 | 2349186.16 | 29132043.81 | 0.00 | 0.486221E+09 | 0.00 | 1.28 |
October | 0.942321E+09 | 0.250897E+09 | 0.00 | 3976149.23 | 6842390.42 | 0.00 | 0.182429E+10 | 0.00 | 1.53 |
November | 0.185650E+10 | 10544771.52 | 0.00 | 3071891.83 | 12696849.03 | 0.00 | 0.203579E+10 | 0.00 | 1.52 |
December | 0.321117E+10 | 432151.59 | 0.00 | 1707833.41 | 113101.62 | 0.00 | 0.158624E+10 | 0.00 | 1.36 |
Annual Sum or Average | 0.140799E+11 | 0.617560E+10 | 0.00 | 32613689.24 | 0.116979E+09 | 0.00 | 0.151367E+11 | 0.00 | 1.38 |
Minimum of Months | 700859.05 | 0.00 | 0.00 | 1203166.04 | 2221.67 | 0.00 | 0.252643E+09 | 0.00 | 1.15 |
Maximum of Months | 0.321117E+10 | 0.151348E+10 | 0.00 | 3976149.23 | 29132043.81 | 0.00 | 0.203579E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.299298E+10 | 246439.71 | 0.00 | 1286584.56 | 3464466.35 | 0.00 | 0.920314E+09 | 0.00 | 0.64 |
February | 0.346501E+10 | 0.00 | 0.00 | 369421.08 | 2086.09 | 0.00 | 0.480125E+09 | 0.00 | 0.63 |
March | 0.289893E+10 | 4449485.83 | 0.00 | 1601981.22 | 9592347.50 | 0.00 | 0.860979E+09 | 0.00 | 0.67 |
April | 0.839163E+09 | 0.295434E+09 | 0.00 | 3754557.39 | 11540466.30 | 0.00 | 0.118727E+10 | 0.00 | 0.69 |
May | 0.192147E+09 | 0.636414E+09 | 0.00 | 4526267.14 | 0.00 | 0.00 | 0.121158E+10 | 0.00 | 0.67 |
June | 0.00 | 0.144220E+10 | 0.00 | 3973686.63 | 0.00 | 0.00 | 0.576969E+09 | 0.00 | 0.64 |
July | 807912.08 | 0.181483E+10 | 0.00 | 1916091.69 | 101908.59 | 0.00 | 0.251158E+09 | 0.00 | 0.62 |
August | 475231.66 | 0.152197E+10 | 0.00 | 2363514.32 | 0.00 | 0.00 | 0.292914E+09 | 0.00 | 0.63 |
September | 10017065.70 | 0.117433E+10 | 0.00 | 2602597.09 | 259759.54 | 0.00 | 0.477941E+09 | 0.00 | 0.64 |
October | 0.142874E+10 | 0.264724E+09 | 0.00 | 3304689.94 | 4034789.98 | 0.00 | 0.118606E+10 | 0.00 | 0.70 |
November | 0.266480E+10 | 5662106.67 | 0.00 | 1511370.27 | 15652349.27 | 0.00 | 0.942236E+09 | 0.00 | 0.67 |
December | 0.396899E+10 | 0.00 | 0.00 | 422596.61 | 511978.30 | 0.00 | 0.482776E+09 | 0.00 | 0.59 |
Annual Sum or Average | 0.184621E+11 | 0.716026E+10 | 0.00 | 27633357.94 | 45160151.93 | 0.00 | 0.887032E+10 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 369421.08 | 0.00 | 0.00 | 0.251158E+09 | 0.00 | 0.59 |
Maximum of Months | 0.396899E+10 | 0.181483E+10 | 0.00 | 4526267.14 | 15652349.27 | 0.00 | 0.121158E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254925E+10 | 0.00 | 0.00 | 0.00 | 2490415.81 | 11929068.85 | 0.00 | 0.00 | 0.72 |
February | 0.264251E+10 | 0.00 | 0.00 | 0.00 | 1399.99 | 0.00 | 0.00 | 0.00 | 0.73 |
March | 0.243894E+10 | 0.00 | 0.00 | 7265.82 | 9387467.86 | 0.00 | 13141533.89 | 0.00 | 0.74 |
April | 0.109313E+10 | 0.141467E+09 | 0.00 | 606187.92 | 39607700.45 | 0.00 | 0.154686E+09 | 0.00 | 0.69 |
May | 0.692146E+09 | 0.372696E+09 | 0.00 | 748642.51 | 8306562.89 | 0.00 | 0.179275E+09 | 0.00 | 0.67 |
June | 0.142449E+09 | 0.952034E+09 | 0.00 | 1383586.96 | 712.86 | 0.00 | 0.205951E+09 | 0.00 | 0.68 |
July | 61254118.71 | 0.110517E+10 | 0.00 | 633353.12 | 11257618.96 | 0.00 | 90204746.33 | 0.00 | 0.64 |
August | 82851296.27 | 0.897711E+09 | 0.00 | 570363.40 | 14232865.55 | 0.00 | 91645116.67 | 0.00 | 0.62 |
September | 0.178528E+09 | 0.616052E+09 | 0.00 | 525624.37 | 67152252.00 | 0.00 | 0.112923E+09 | 0.00 | 0.64 |
October | 0.153178E+10 | 0.124564E+09 | 0.00 | 312391.15 | 34575294.39 | 0.00 | 95289362.91 | 0.00 | 0.72 |
November | 0.232984E+10 | 0.00 | 0.00 | 4404.55 | 14303065.92 | 0.00 | 8032061.71 | 0.00 | 0.74 |
December | 0.293272E+10 | 0.00 | 0.00 | 0.00 | 343592.33 | 41248795.24 | 0.00 | 0.00 | 0.69 |
Annual Sum or Average | 0.166754E+11 | 0.420970E+10 | 0.00 | 4791819.79 | 0.201659E+09 | 53177864.09 | 0.951147E+09 | 0.00 | 0.69 |
Minimum of Months | 61254118.71 | 0.00 | 0.00 | 0.00 | 712.86 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.293272E+10 | 0.110517E+10 | 0.00 | 1383586.96 | 67152252.00 | 41248795.24 | 0.205951E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 2177234.21 | 0.00 | 0.118184E+09 | 0.00 | 0.00 | 0.578376E+11 | 0.00 | 29.15 |
February | 0.00 | 0.00 | 0.00 | 0.100739E+09 | 0.00 | 0.00 | 0.616769E+11 | 0.00 | 26.96 |
March | 0.00 | 8035306.51 | 0.00 | 0.117114E+09 | 0.00 | 0.00 | 0.552819E+11 | 0.00 | 29.30 |
April | 0.00 | 20930559.11 | 0.00 | 67693245.78 | 0.00 | 0.00 | 0.241685E+11 | 0.00 | 20.06 |
May | 0.00 | 17487908.04 | 0.00 | 42627801.15 | 0.00 | 0.00 | 0.153119E+11 | 0.00 | 15.98 |
June | 0.00 | 4810276.60 | 0.00 | 15533827.16 | 0.00 | 0.00 | 0.367794E+10 | 0.00 | 6.75 |
July | 0.00 | 0.889712E+09 | 0.00 | 5750429.51 | 0.00 | 0.00 | 0.171638E+10 | 0.00 | 3.89 |
August | 0.00 | 0.158158E+10 | 0.00 | 8477416.93 | 0.00 | 0.00 | 0.190535E+10 | 0.00 | 6.71 |
September | 0.00 | 0.381758E+10 | 0.00 | 14732815.10 | 0.00 | 0.00 | 0.454851E+10 | 0.00 | 13.23 |
October | 0.00 | 0.284841E+09 | 0.00 | 87208549.13 | 0.00 | 0.00 | 0.352899E+11 | 0.00 | 25.23 |
November | 0.00 | 35536877.11 | 0.00 | 0.113997E+09 | 0.00 | 0.00 | 0.555632E+11 | 0.00 | 29.91 |
December | 0.00 | 591173.17 | 0.00 | 0.114245E+09 | 0.00 | 0.00 | 0.643044E+11 | 0.00 | 26.10 |
Annual Sum or Average | 0.00 | 0.666328E+10 | 0.00 | 0.806304E+09 | 0.00 | 0.00 | 0.381283E+12 | 0.00 | 19.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5750429.51 | 0.00 | 0.00 | 0.171638E+10 | 0.00 | 3.89 |
Maximum of Months | 0.00 | 0.381758E+10 | 0.00 | 0.118184E+09 | 0.00 | 0.00 | 0.643044E+11 | 0.00 | 29.91 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.662968E+10 | 21081630.05 | 0.00 | 43765436.77 | 0.00 | 0.00 | 0.275894E+11 | 0.00 | 5.77 |
February | 0.784732E+10 | 0.00 | 0.00 | 23378973.14 | 0.00 | 0.00 | 0.252385E+11 | 0.00 | 4.66 |
March | 0.675611E+10 | 59571546.87 | 0.00 | 33404890.93 | 0.00 | 0.00 | 0.258083E+11 | 0.00 | 5.64 |
April | 0.253553E+09 | 0.197254E+10 | 0.00 | 33767383.34 | 0.00 | 0.00 | 0.184802E+11 | 0.00 | 5.65 |
May | 0.00 | 0.386713E+10 | 0.00 | 28177766.42 | 0.00 | 0.00 | 0.142128E+11 | 0.00 | 5.49 |
June | 0.00 | 0.853344E+10 | 0.00 | 21103589.90 | 0.00 | 0.00 | 0.569704E+10 | 0.00 | 4.35 |
July | 0.00 | 0.138832E+11 | 0.00 | 7388540.35 | 0.00 | 0.00 | 0.222034E+10 | 0.00 | 3.92 |
August | 0.00 | 0.124728E+11 | 0.00 | 10006480.83 | 0.00 | 0.00 | 0.288140E+10 | 0.00 | 4.34 |
September | 0.00 | 0.947463E+10 | 0.00 | 14398915.92 | 0.00 | 0.00 | 0.547307E+10 | 0.00 | 5.31 |
October | 0.164344E+10 | 0.233369E+10 | 0.00 | 38291526.67 | 0.00 | 0.00 | 0.221303E+11 | 0.00 | 6.10 |
November | 0.450656E+10 | 0.107647E+09 | 0.00 | 41160940.00 | 0.00 | 0.00 | 0.284977E+11 | 0.00 | 5.80 |
December | 0.140113E+11 | 1224292.40 | 0.00 | 30627129.28 | 0.00 | 0.00 | 0.231794E+11 | 0.00 | 5.07 |
Annual Sum or Average | 0.416480E+11 | 0.527269E+11 | 0.00 | 0.325472E+09 | 0.00 | 0.00 | 0.201408E+12 | 0.00 | 5.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 7388540.35 | 0.00 | 0.00 | 0.222034E+10 | 0.00 | 3.92 |
Maximum of Months | 0.140113E+11 | 0.138832E+11 | 0.00 | 43765436.77 | 0.00 | 0.00 | 0.284977E+11 | 0.00 | 6.10 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155690E+11 | 89372991.58 | 0.00 | 0.107030E+09 | 5510877.23 | 0.00 | 0.725348E+11 | 0.00 | 1.82 |
February | 0.286709E+11 | 0.00 | 0.00 | 43341793.25 | 45910.91 | 0.00 | 0.593330E+11 | 0.00 | 1.76 |
March | 0.241026E+11 | 0.269804E+09 | 0.00 | 73494441.68 | 49016199.79 | 0.00 | 0.590436E+11 | 0.00 | 1.85 |
April | 0.363373E+10 | 0.628857E+10 | 0.00 | 93285397.48 | 80593372.17 | 0.00 | 0.405815E+11 | 0.00 | 1.81 |
May | 0.704107E+09 | 0.112385E+11 | 0.00 | 83745473.07 | 0.178151E+09 | 0.00 | 0.303663E+11 | 0.00 | 1.67 |
June | 1195842.93 | 0.232806E+11 | 0.00 | 76946842.65 | 69469703.33 | 0.00 | 0.131275E+11 | 0.00 | 1.47 |
July | 7142995.83 | 0.304964E+11 | 0.00 | 40559640.80 | 0.152510E+09 | 0.00 | 0.565490E+10 | 0.00 | 1.43 |
August | 12635540.41 | 0.264625E+11 | 0.00 | 50210136.84 | 0.202763E+09 | 0.00 | 0.664154E+10 | 0.00 | 1.50 |
September | 71742798.43 | 0.216904E+11 | 0.00 | 54705949.12 | 0.256618E+09 | 0.00 | 0.108808E+11 | 0.00 | 1.62 |
October | 0.639947E+10 | 0.560117E+10 | 0.00 | 0.108190E+09 | 24972413.19 | 0.00 | 0.510532E+11 | 0.00 | 1.90 |
November | 0.122233E+11 | 0.264779E+09 | 0.00 | 97834869.80 | 0.238690E+09 | 0.00 | 0.681029E+11 | 0.00 | 1.87 |
December | 0.340762E+11 | 9780887.23 | 0.00 | 63189056.86 | 2337253.87 | 0.00 | 0.651839E+11 | 0.00 | 1.68 |
Annual Sum or Average | 0.125472E+12 | 0.125692E+12 | 0.00 | 0.892534E+09 | 0.126068E+10 | 0.00 | 0.482504E+12 | 0.00 | 1.70 |
Minimum of Months | 1195842.93 | 0.00 | 0.00 | 40559640.80 | 45910.91 | 0.00 | 0.565490E+10 | 0.00 | 1.43 |
Maximum of Months | 0.340762E+11 | 0.304964E+11 | 0.00 | 0.108190E+09 | 0.256618E+09 | 0.00 | 0.725348E+11 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 2222926.17 | 38027.09 | 15501323.43 | 0.00 | 0.871172E+09 | 0.713744E+09 | 1027.62 | 0.36 |
February | 16877889.12 | 347778.99 | 0.00 | 6912147.91 | 0.00 | 0.823445E+09 | 0.630288E+09 | 0.00 | 0.35 |
March | 14092555.34 | 7100670.14 | 0.00 | 11596655.89 | 0.00 | 0.736361E+09 | 0.640250E+09 | 0.00 | 0.35 |
April | 0.00 | 0.152033E+09 | 7409.56 | 10763485.20 | 0.00 | 43145921.82 | 0.508956E+09 | 5347.87 | 0.37 |
May | 0.00 | 0.292423E+09 | 26242.27 | 7444069.74 | 0.00 | 429439.73 | 0.322336E+09 | 6947.78 | 0.37 |
June | 0.00 | 0.806028E+09 | 4401.63 | 3438759.79 | 0.00 | 21867.54 | 68011099.03 | 1224.63 | 0.38 |
July | 0.00 | 0.192284E+10 | 0.00 | 914085.89 | 0.00 | 3023.15 | 34565204.58 | 0.00 | 0.38 |
August | 0.00 | 0.182024E+10 | 56725.46 | 764838.89 | 0.00 | 34496.36 | 16209605.17 | 7509.98 | 0.38 |
September | 0.00 | 0.145176E+10 | 70213.51 | 793717.00 | 0.00 | 15796.00 | 12076639.96 | 7731.55 | 0.37 |
October | 0.00 | 0.316998E+09 | 66358.64 | 10432515.20 | 0.00 | 0.238153E+09 | 0.523877E+09 | 9282.67 | 0.36 |
November | 714201.77 | 50345952.65 | 15100.88 | 11560410.44 | 0.00 | 0.627724E+09 | 0.645558E+09 | 1070.02 | 0.36 |
December | 5385666.21 | 6289.06 | 0.00 | 9856636.23 | 0.00 | 0.135262E+10 | 0.749926E+09 | 0.00 | 0.35 |
Annual Sum or Average | 37070312.43 | 0.682234E+10 | 284479.05 | 89978645.60 | 0.00 | 0.469312E+10 | 0.486580E+10 | 40142.13 | 0.37 |
Minimum of Months | 0.00 | 6289.06 | 0.00 | 764838.89 | 0.00 | 3023.15 | 12076639.96 | 0.00 | 0.35 |
Maximum of Months | 16877889.12 | 0.192284E+10 | 70213.51 | 15501323.43 | 0.00 | 0.135262E+10 | 0.749926E+09 | 9282.67 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239501E+09 | 252411.43 | 0.00 | 5581493.61 | 245806.98 | 0.923078E+09 | 0.526135E+09 | 0.00 | 0.35 |
February | 0.184295E+09 | 51067.66 | 5718.58 | 2442441.98 | 0.00 | 0.921859E+09 | 0.443001E+09 | 28.42 | 0.35 |
March | 0.326208E+09 | 5924295.05 | 0.00 | 6159253.75 | 0.00 | 0.702067E+09 | 0.537884E+09 | 0.00 | 0.35 |
April | 0.155891E+09 | 0.138854E+09 | 4130.33 | 8783614.67 | 72157.85 | 21874425.83 | 0.463763E+09 | 2751.28 | 0.36 |
May | 0.103643E+09 | 0.284704E+09 | 13987.78 | 6133478.84 | 0.00 | 73517.48 | 0.258286E+09 | 8818.18 | 0.37 |
June | 42374291.27 | 0.802155E+09 | 18412.64 | 2646443.16 | 267094.30 | 18410.72 | 51362454.85 | 6118.27 | 0.38 |
July | 13405478.85 | 0.189439E+10 | 0.00 | 747324.31 | 10387975.13 | 7481.96 | 26625171.63 | 0.00 | 0.38 |
August | 15153548.63 | 0.172880E+10 | 30313.59 | 657171.18 | 16729328.58 | 213.48 | 12649038.26 | 4286.78 | 0.38 |
September | 21428164.14 | 0.129114E+10 | 111023.73 | 740748.49 | 42107267.85 | 4578.87 | 7698168.26 | 15185.35 | 0.37 |
October | 0.243661E+09 | 0.279171E+09 | 26044.04 | 6584435.67 | 4688417.65 | 0.236069E+09 | 0.408854E+09 | 5453.11 | 0.36 |
November | 0.252814E+09 | 21932003.42 | 0.00 | 5408909.12 | 714183.40 | 0.684668E+09 | 0.467146E+09 | 2384.12 | 0.35 |
December | 0.203782E+09 | 0.00 | 0.00 | 2880734.14 | 0.00 | 0.154219E+10 | 0.398386E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.180215E+10 | 0.644737E+10 | 209630.69 | 48766048.93 | 75212231.75 | 0.503191E+10 | 0.360179E+10 | 45025.50 | 0.36 |
Minimum of Months | 13405478.85 | 0.00 | 0.00 | 657171.18 | 0.00 | 213.48 | 7698168.26 | 0.00 | 0.34 |
Maximum of Months | 0.326208E+09 | 0.189439E+10 | 111023.73 | 8783614.67 | 42107267.85 | 0.154219E+10 | 0.537884E+09 | 15185.35 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 221979.43 | 0.00 | 0.130695E+09 | 0.00 | 0.00 | 0.286294E+10 | 0.00 | 0.08 |
February | 0.216640E+09 | 0.00 | 0.00 | 46236532.85 | 0.00 | 0.00 | 0.213298E+10 | 0.00 | 0.05 |
March | 63060948.54 | 2655570.87 | 0.00 | 60628953.96 | 0.00 | 0.00 | 0.166294E+10 | 0.00 | 0.05 |
April | 0.00 | 0.634383E+09 | 0.00 | 73877904.01 | 0.00 | 0.00 | 0.755887E+09 | 0.00 | 0.10 |
May | 0.00 | 0.121159E+10 | 0.00 | 54078651.96 | 0.00 | 0.00 | 0.367253E+09 | 0.00 | 0.10 |
June | 0.00 | 0.390743E+10 | 0.00 | 27166723.52 | 0.00 | 0.00 | 0.155944E+09 | 0.00 | 0.13 |
July | 0.00 | 0.494822E+10 | 0.00 | 7586129.44 | 0.00 | 0.00 | 54899394.05 | 0.00 | 0.13 |
August | 0.00 | 0.480135E+10 | 0.00 | 9945807.53 | 0.00 | 0.00 | 59171454.05 | 0.00 | 0.13 |
September | 0.00 | 0.367643E+10 | 0.00 | 17091324.65 | 0.00 | 0.00 | 0.109949E+09 | 0.00 | 0.13 |
October | 0.00 | 0.892577E+09 | 0.00 | 94391088.95 | 0.00 | 0.00 | 0.146209E+10 | 0.00 | 0.10 |
November | 0.00 | 15949001.15 | 0.00 | 0.110783E+09 | 0.00 | 0.00 | 0.250848E+10 | 0.00 | 0.08 |
December | 53903717.84 | 0.00 | 0.00 | 90754919.03 | 0.00 | 0.00 | 0.275796E+10 | 0.00 | 0.07 |
Annual Sum or Average | 0.333604E+09 | 0.200908E+11 | 0.00 | 0.723237E+09 | 0.00 | 0.00 | 0.148905E+11 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 7586129.44 | 0.00 | 0.00 | 54899394.05 | 0.00 | 0.05 |
Maximum of Months | 0.216640E+09 | 0.494822E+10 | 0.00 | 0.130695E+09 | 0.00 | 0.00 | 0.286294E+10 | 0.00 | 0.13 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.287982E+10 | 5052621.96 | 41818.86 | 74400830.59 | 2126992.68 | 0.158311E+10 | 0.163782E+11 | 33129.85 | 0.39 |
February | 0.222098E+10 | 1021872.67 | 0.00 | 49990301.67 | 0.00 | 0.160025E+10 | 0.147022E+11 | 0.00 | 0.39 |
March | 0.341643E+10 | 91594999.45 | 1221958.62 | 94851115.23 | 36175.34 | 0.136829E+10 | 0.139692E+11 | 101441.83 | 0.39 |
April | 0.151618E+10 | 0.219342E+10 | 1513878.55 | 82507314.49 | 2839466.00 | 5675607.49 | 0.611273E+10 | 56228.72 | 0.40 |
May | 0.116214E+10 | 0.454471E+10 | 137060.56 | 46878915.47 | 0.00 | 361189.43 | 0.331500E+10 | 15561.71 | 0.41 |
June | 0.485420E+09 | 0.112347E+11 | 228683.17 | 22055170.58 | 2248920.79 | 0.00 | 0.694371E+09 | 21043.82 | 0.42 |
July | 0.152582E+09 | 0.241434E+11 | 8581532.29 | 6039357.38 | 0.117697E+09 | 0.00 | 0.336007E+09 | 127833.01 | 0.42 |
August | 0.187943E+09 | 0.217460E+11 | 16877844.29 | 6486302.95 | 0.195342E+09 | 0.00 | 0.162756E+09 | 304201.69 | 0.41 |
September | 0.249752E+09 | 0.163381E+11 | 4452157.87 | 7945021.56 | 0.478791E+09 | 0.00 | 0.141853E+09 | 130461.42 | 0.41 |
October | 0.261029E+10 | 0.364401E+10 | 2996603.32 | 83077600.36 | 54971524.17 | 25279829.76 | 0.794262E+10 | 215802.01 | 0.40 |
November | 0.313509E+10 | 0.378554E+09 | 1384433.36 | 78608748.73 | 22054260.31 | 0.114783E+10 | 0.130202E+11 | 153179.84 | 0.39 |
December | 0.234573E+10 | 47229.05 | 0.00 | 44912341.06 | 2831238.16 | 0.771189E+10 | 0.167037E+11 | 1256.09 | 0.39 |
Annual Sum or Average | 0.203623E+11 | 0.843206E+11 | 37435970.89 | 0.597753E+09 | 0.878938E+09 | 0.134427E+11 | 0.934789E+11 | 1160139.98 | 0.40 |
Minimum of Months | 0.152582E+09 | 47229.05 | 0.00 | 6039357.38 | 0.00 | 0.00 | 0.141853E+09 | 0.00 | 0.39 |
Maximum of Months | 0.341643E+10 | 0.241434E+11 | 16877844.29 | 94851115.23 | 0.478791E+09 | 0.771189E+10 | 0.167037E+11 | 304201.69 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 1745725.81 | 0.00 | 15157711.94 | 0.00 | 0.863163E+09 | 0.721656E+09 | 0.00 | 0.36 |
February | 15590700.18 | 413114.14 | 6390.12 | 7621166.32 | 0.00 | 0.792494E+09 | 0.650463E+09 | 50.22 | 0.35 |
March | 9099221.59 | 8011915.98 | 0.00 | 12468957.50 | 0.00 | 0.708890E+09 | 0.670370E+09 | 0.00 | 0.35 |
April | 419007.59 | 0.156454E+09 | 0.00 | 15795745.97 | 0.00 | 44700415.45 | 0.509912E+09 | 0.00 | 0.37 |
May | 0.00 | 0.300797E+09 | 0.00 | 12599322.01 | 0.00 | 16078.14 | 0.326109E+09 | 0.00 | 0.38 |
June | 0.00 | 0.839910E+09 | 0.00 | 5160876.36 | 0.00 | 0.00 | 67514833.92 | 0.00 | 0.40 |
July | 0.00 | 0.200528E+10 | 0.00 | 1298847.67 | 0.00 | 0.00 | 34166855.09 | 0.00 | 0.39 |
August | 0.00 | 0.190288E+10 | 0.00 | 878764.88 | 0.00 | 0.00 | 16132328.88 | 0.00 | 0.39 |
September | 0.00 | 0.150568E+10 | 0.00 | 978894.02 | 0.00 | 0.00 | 12801614.92 | 0.00 | 0.38 |
October | 0.00 | 0.331774E+09 | 0.00 | 12221349.33 | 0.00 | 0.231587E+09 | 0.529931E+09 | 0.00 | 0.37 |
November | 1347124.11 | 42905727.26 | 19630.41 | 12337009.33 | 0.00 | 0.629216E+09 | 0.649137E+09 | 553.79 | 0.36 |
December | 4005119.26 | 4601.87 | 0.00 | 10346000.22 | 0.00 | 0.133039E+10 | 0.768611E+09 | 0.00 | 0.35 |
Annual Sum or Average | 30461172.74 | 0.709586E+10 | 26020.53 | 0.106865E+09 | 0.00 | 0.460046E+10 | 0.495681E+10 | 604.01 | 0.37 |
Minimum of Months | 0.00 | 4601.87 | 0.00 | 878764.88 | 0.00 | 0.00 | 12801614.92 | 0.00 | 0.35 |
Maximum of Months | 15590700.18 | 0.200528E+10 | 19630.41 | 15795745.97 | 0.00 | 0.133039E+10 | 0.768611E+09 | 553.79 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211839E+09 | 160317.45 | 0.00 | 5993017.73 | 10341.75 | 0.917895E+09 | 0.523527E+09 | 0.00 | 0.34 |
February | 0.152456E+09 | 0.00 | 48293.95 | 3400002.41 | 0.00 | 0.845699E+09 | 0.510134E+09 | 151.95 | 0.35 |
March | 0.262810E+09 | 6429523.29 | 0.00 | 8203598.66 | 0.00 | 0.672091E+09 | 0.567934E+09 | 0.00 | 0.35 |
April | 0.137804E+09 | 0.138669E+09 | 0.00 | 13490677.88 | 78467.19 | 27150588.39 | 0.475648E+09 | 0.00 | 0.37 |
May | 0.104944E+09 | 0.277557E+09 | 0.00 | 11784869.59 | 0.00 | 21207.07 | 0.282969E+09 | 0.00 | 0.38 |
June | 47199858.31 | 0.836302E+09 | 0.00 | 4573267.10 | 234041.40 | 0.00 | 55369245.47 | 0.00 | 0.40 |
July | 14484782.26 | 0.197819E+10 | 0.00 | 1169344.69 | 8832498.75 | 0.00 | 26952941.12 | 0.00 | 0.39 |
August | 16553989.33 | 0.180863E+10 | 0.00 | 1011719.20 | 15394713.11 | 0.00 | 14047059.52 | 0.00 | 0.39 |
September | 23322035.70 | 0.133809E+10 | 89508.17 | 1183233.32 | 39589681.80 | 0.00 | 11394952.98 | 5185.74 | 0.38 |
October | 0.215954E+09 | 0.291218E+09 | 0.00 | 8546022.72 | 4477348.40 | 0.224638E+09 | 0.422099E+09 | 0.00 | 0.36 |
November | 0.243699E+09 | 19884784.02 | 0.00 | 6493925.10 | 1019599.99 | 0.663576E+09 | 0.488156E+09 | 0.00 | 0.35 |
December | 0.193467E+09 | 0.00 | 0.00 | 3297796.92 | 0.00 | 0.145438E+10 | 0.472613E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.162453E+10 | 0.669513E+10 | 137802.12 | 69147475.33 | 69636692.39 | 0.480545E+10 | 0.385084E+10 | 5337.69 | 0.37 |
Minimum of Months | 14484782.26 | 0.00 | 0.00 | 1011719.20 | 0.00 | 0.00 | 11394952.98 | 0.00 | 0.34 |
Maximum of Months | 0.262810E+09 | 0.197819E+10 | 89508.17 | 13490677.88 | 39589681.80 | 0.145438E+10 | 0.567934E+09 | 5185.74 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 24958124.07 | 0.00 | 0.00 | 0.332511E+10 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.00 | 10534402.64 | 0.00 | 0.00 | 0.209260E+10 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.00 | 20899807.63 | 0.00 | 0.00 | 0.272417E+10 | 0.00 | 0.03 |
April | 0.00 | 864968.98 | 0.00 | 43660609.94 | 0.00 | 0.00 | 0.332452E+10 | 0.00 | 0.07 |
May | 0.00 | 18358852.32 | 0.00 | 47478493.36 | 0.00 | 0.00 | 0.310222E+10 | 0.00 | 0.09 |
June | 0.00 | 0.116898E+10 | 0.00 | 33136313.18 | 0.00 | 0.00 | 0.154780E+10 | 0.00 | 0.12 |
July | 0.00 | 0.338458E+10 | 0.00 | 10901226.83 | 0.00 | 0.00 | 0.498211E+09 | 0.00 | 0.12 |
August | 0.00 | 0.307578E+10 | 0.00 | 9719634.23 | 0.00 | 0.00 | 0.389737E+09 | 0.00 | 0.12 |
September | 0.00 | 0.219318E+10 | 0.00 | 13708503.03 | 0.00 | 0.00 | 0.567780E+09 | 0.00 | 0.11 |
October | 0.00 | 0.383982E+09 | 0.00 | 32474034.36 | 0.00 | 0.00 | 0.274132E+10 | 0.00 | 0.07 |
November | 0.00 | 2788877.38 | 0.00 | 24748769.33 | 0.00 | 0.00 | 0.288612E+10 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 | 14314327.52 | 0.00 | 0.00 | 0.268331E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.102285E+11 | 0.00 | 0.286534E+09 | 0.00 | 0.00 | 0.258829E+11 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 9719634.23 | 0.00 | 0.00 | 0.389737E+09 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.338458E+10 | 0.00 | 47478493.36 | 0.00 | 0.00 | 0.332511E+10 | 0.00 | 0.12 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 318793.89 | 485990.66 | 8405.12 | 3463090.29 | 0.00 | 0.270153E+09 | 0.131423E+09 | 767.41 | 0.35 |
February | 5451350.72 | 58298.35 | 17402.06 | 1416400.08 | 0.00 | 0.280704E+09 | 0.103086E+09 | 437.75 | 0.35 |
March | 4891524.79 | 1685095.61 | 0.00 | 2606585.16 | 0.00 | 0.241302E+09 | 0.109590E+09 | 0.00 | 0.35 |
April | 92683.25 | 39090100.01 | 1469.71 | 2398138.84 | 0.00 | 42991986.98 | 95612862.79 | 2628.83 | 0.37 |
May | 0.00 | 75177440.27 | 7120.84 | 1574792.07 | 0.00 | 7952660.16 | 73061540.30 | 2881.72 | 0.37 |
June | 0.00 | 0.204709E+09 | 7784.67 | 758443.97 | 0.00 | 5512.54 | 17389855.46 | 1391.79 | 0.39 |
July | 0.00 | 0.486114E+09 | 4704.34 | 191249.80 | 0.00 | 2358.57 | 8779481.74 | 443.49 | 0.38 |
August | 0.00 | 0.458575E+09 | 35899.84 | 172255.49 | 0.00 | 9100.81 | 4231792.77 | 4561.27 | 0.38 |
September | 0.00 | 0.362091E+09 | 33644.64 | 181025.16 | 0.00 | 5073.62 | 3513284.46 | 6832.92 | 0.38 |
October | 76803.63 | 78762573.55 | 27513.31 | 2252644.81 | 0.00 | 98497642.33 | 95059157.85 | 4583.55 | 0.36 |
November | 887510.82 | 9129393.78 | 74392.39 | 2515547.82 | 0.00 | 0.216449E+09 | 0.110327E+09 | 1135.57 | 0.35 |
December | 1312665.40 | 1006.01 | 0.00 | 2079094.71 | 0.00 | 0.401145E+09 | 0.126599E+09 | 0.00 | 0.35 |
Annual Sum or Average | 13031332.51 | 0.171588E+10 | 218336.92 | 19609268.20 | 0.00 | 0.155922E+10 | 0.878673E+09 | 25664.29 | 0.37 |
Minimum of Months | 0.00 | 1006.01 | 0.00 | 172255.49 | 0.00 | 2358.57 | 3513284.46 | 0.00 | 0.35 |
Maximum of Months | 5451350.72 | 0.486114E+09 | 74392.39 | 3463090.29 | 0.00 | 0.401145E+09 | 0.131423E+09 | 6832.92 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 59255843.58 | 44574.59 | 0.00 | 1166916.46 | 32698.14 | 0.294307E+09 | 72275618.77 | 0.00 | 0.35 |
February | 46671556.53 | 0.00 | 15018.71 | 419531.91 | 0.00 | 0.309065E+09 | 52249177.37 | 471.71 | 0.35 |
March | 81662205.58 | 1443720.02 | 0.00 | 1319836.15 | 0.00 | 0.239272E+09 | 78448532.64 | 0.00 | 0.35 |
April | 37988955.96 | 35805401.18 | 2759.23 | 1998302.79 | 19077.65 | 33838469.79 | 88640392.19 | 1068.41 | 0.37 |
May | 24472624.69 | 73018483.71 | 5275.33 | 1367728.36 | 0.00 | 5867744.38 | 59237488.36 | 412.16 | 0.37 |
June | 9862962.60 | 0.204063E+09 | 2331.25 | 605293.86 | 75767.27 | 0.00 | 13198626.94 | 714.35 | 0.39 |
July | 3160329.89 | 0.480272E+09 | 0.00 | 164954.99 | 2571061.84 | 462.57 | 6789634.17 | 0.00 | 0.38 |
August | 3656178.74 | 0.438379E+09 | 23418.50 | 156501.90 | 4087028.19 | 55.93 | 3321863.27 | 1095.80 | 0.38 |
September | 5284501.79 | 0.325827E+09 | 36531.20 | 177501.00 | 10329667.53 | 2538.75 | 2109589.30 | 3799.47 | 0.37 |
October | 59266354.69 | 70208948.61 | 39157.64 | 1393219.95 | 1166258.21 | 97889849.42 | 66060943.71 | 4308.30 | 0.36 |
November | 64073811.66 | 4024883.09 | 5660.17 | 1073965.06 | 116442.39 | 0.229145E+09 | 65031884.46 | 303.50 | 0.35 |
December | 50778291.10 | 0.00 | 0.00 | 534555.97 | 0.00 | 0.441271E+09 | 44942146.52 | 0.00 | 0.34 |
Annual Sum or Average | 0.446134E+09 | 0.163309E+10 | 130152.02 | 10378308.40 | 18398001.22 | 0.165066E+10 | 0.552306E+09 | 12173.70 | 0.36 |
Minimum of Months | 3160329.89 | 0.00 | 0.00 | 156501.90 | 0.00 | 0.00 | 2109589.30 | 0.00 | 0.34 |
Maximum of Months | 81662205.58 | 0.480272E+09 | 39157.64 | 1998302.79 | 10329667.53 | 0.441271E+09 | 88640392.19 | 4308.30 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 2791636.42 | 0.00 | 32085224.72 | 0.00 | 0.134858E+10 | 0.130077E+10 | 0.00 | 0.42 |
February | 23498119.94 | 470008.75 | 0.00 | 14005402.26 | 0.00 | 0.135868E+10 | 0.105366E+10 | 0.00 | 0.41 |
March | 14431789.99 | 9597488.34 | 0.00 | 17862037.27 | 0.00 | 0.123469E+10 | 0.106488E+10 | 0.00 | 0.40 |
April | 0.00 | 0.201098E+09 | 21450.75 | 15765116.25 | 0.00 | 0.132807E+09 | 0.836220E+09 | 2576.80 | 0.42 |
May | 0.00 | 0.386816E+09 | 32093.28 | 10451338.86 | 0.00 | 16212026.69 | 0.581736E+09 | 12331.38 | 0.42 |
June | 0.00 | 0.118995E+10 | 0.00 | 5167865.78 | 0.00 | 44142.10 | 0.142292E+09 | 0.00 | 0.43 |
July | 0.00 | 0.302317E+10 | 0.00 | 1251878.43 | 0.00 | 4344.14 | 66165761.87 | 0.00 | 0.43 |
August | 0.00 | 0.289538E+10 | 88698.35 | 1066002.82 | 0.00 | 0.00 | 34816428.25 | 5058.78 | 0.44 |
September | 0.00 | 0.232955E+10 | 471273.71 | 1421071.78 | 0.00 | 9101.67 | 29298645.79 | 6301.72 | 0.43 |
October | 0.00 | 0.516782E+09 | 0.00 | 18582964.13 | 0.00 | 0.412021E+09 | 0.866390E+09 | 0.00 | 0.43 |
November | 1136865.95 | 63311336.47 | 0.00 | 23934587.85 | 0.00 | 0.991484E+09 | 0.115806E+10 | 0.00 | 0.42 |
December | 979589.36 | 0.00 | 0.00 | 24603046.17 | 0.00 | 0.207266E+10 | 0.147020E+10 | 0.00 | 0.42 |
Annual Sum or Average | 40046365.23 | 0.106189E+11 | 613516.09 | 0.166197E+09 | 0.00 | 0.756718E+10 | 0.860449E+10 | 26268.68 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1066002.82 | 0.00 | 0.00 | 29298645.79 | 0.00 | 0.40 |
Maximum of Months | 23498119.94 | 0.302317E+10 | 471273.71 | 32085224.72 | 0.00 | 0.207266E+10 | 0.147020E+10 | 12331.38 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.392767E+10 | 62531635.64 | 0.00 | 52316415.83 | 0.00 | 0.00 | 0.483845E+11 | 0.00 | 5.11 |
February | 0.407004E+10 | 0.00 | 0.00 | 39952785.40 | 0.00 | 0.00 | 0.499822E+11 | 0.00 | 5.08 |
March | 0.282714E+10 | 0.124794E+09 | 0.00 | 62123216.38 | 0.00 | 0.00 | 0.489072E+11 | 0.00 | 5.33 |
April | 0.260281E+09 | 0.346387E+10 | 0.00 | 64478653.09 | 4692663.82 | 0.00 | 0.267443E+11 | 0.00 | 5.24 |
May | 14037467.55 | 0.676343E+10 | 0.00 | 62152129.37 | 2053695.00 | 0.00 | 0.193913E+11 | 0.00 | 5.02 |
June | 0.00 | 0.145316E+11 | 0.00 | 47619645.11 | 0.00 | 0.00 | 0.861104E+10 | 0.00 | 4.60 |
July | 0.00 | 0.186676E+11 | 0.00 | 25497904.67 | 0.00 | 0.00 | 0.397613E+10 | 0.00 | 4.46 |
August | 0.00 | 0.159129E+11 | 0.00 | 32186020.64 | 6612423.37 | 0.00 | 0.485348E+10 | 0.00 | 4.60 |
September | 1276647.93 | 0.126730E+11 | 0.00 | 34211973.47 | 29358035.73 | 0.00 | 0.733964E+10 | 0.00 | 4.84 |
October | 0.975553E+09 | 0.308201E+10 | 0.00 | 63197236.71 | 14709458.47 | 0.00 | 0.334176E+11 | 0.00 | 5.34 |
November | 0.257214E+10 | 0.217761E+09 | 0.00 | 53195744.48 | 6358574.10 | 0.00 | 0.450227E+11 | 0.00 | 5.27 |
December | 0.766567E+10 | 17727317.85 | 0.00 | 36806763.06 | 31777.78 | 0.00 | 0.527684E+11 | 0.00 | 4.89 |
Annual Sum or Average | 0.223138E+11 | 0.755172E+11 | 0.00 | 0.573738E+09 | 63816628.27 | 0.00 | 0.349399E+12 | 0.00 | 4.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 25497904.67 | 0.00 | 0.00 | 0.397613E+10 | 0.00 | 4.46 |
Maximum of Months | 0.766567E+10 | 0.186676E+11 | 0.00 | 64478653.09 | 29358035.73 | 0.00 | 0.527684E+11 | 0.00 | 5.34 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183394E+10 | 63074051.08 | 0.00 | 66310153.81 | 0.00 | 0.00 | 0.516719E+11 | 0.00 | 5.23 |
February | 0.171805E+10 | 0.00 | 0.00 | 51596812.08 | 0.00 | 0.00 | 0.533936E+11 | 0.00 | 5.17 |
March | 0.158506E+10 | 0.127617E+09 | 0.00 | 74188784.63 | 0.00 | 0.00 | 0.515021E+11 | 0.00 | 5.49 |
April | 88538168.11 | 0.369543E+10 | 0.00 | 72922146.46 | 114870.80 | 0.00 | 0.279410E+11 | 0.00 | 5.48 |
May | 1048215.30 | 0.719692E+10 | 0.00 | 68458897.41 | 0.00 | 0.00 | 0.202143E+11 | 0.00 | 5.27 |
June | 0.00 | 0.153722E+11 | 0.00 | 50001076.69 | 0.00 | 0.00 | 0.897937E+10 | 0.00 | 4.84 |
July | 0.00 | 0.197306E+11 | 0.00 | 26702415.01 | 0.00 | 0.00 | 0.414113E+10 | 0.00 | 4.69 |
August | 0.00 | 0.168414E+11 | 0.00 | 33935709.33 | 0.00 | 0.00 | 0.505868E+10 | 0.00 | 4.84 |
September | 0.00 | 0.134160E+11 | 0.00 | 36781427.32 | 1042152.11 | 0.00 | 0.765957E+10 | 0.00 | 5.08 |
October | 0.528333E+09 | 0.326624E+10 | 0.00 | 72679389.95 | 3071430.13 | 0.00 | 0.349628E+11 | 0.00 | 5.54 |
November | 0.128189E+10 | 0.224498E+09 | 0.00 | 65603129.95 | 802222.47 | 0.00 | 0.475064E+11 | 0.00 | 5.40 |
December | 0.424606E+10 | 17742304.48 | 0.00 | 49832041.78 | 0.00 | 0.00 | 0.571200E+11 | 0.00 | 4.95 |
Annual Sum or Average | 0.112829E+11 | 0.799517E+11 | 0.00 | 0.669012E+09 | 5030675.51 | 0.00 | 0.370151E+12 | 0.00 | 5.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 26702415.01 | 0.00 | 0.00 | 0.414113E+10 | 0.00 | 4.69 |
Maximum of Months | 0.424606E+10 | 0.197306E+11 | 0.00 | 74188784.63 | 3071430.13 | 0.00 | 0.571200E+11 | 0.00 | 5.54 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.126347E+09 | 0.00 | 0.00 | 0.649894E+11 | 0.00 | 21.84 |
February | 0.00 | 0.00 | 0.00 | 0.100588E+09 | 0.00 | 0.00 | 0.702509E+11 | 0.00 | 22.72 |
March | 0.00 | 0.00 | 0.00 | 0.127827E+09 | 0.00 | 0.00 | 0.633630E+11 | 0.00 | 22.57 |
April | 0.00 | 0.00 | 0.00 | 0.147195E+09 | 0.00 | 0.00 | 0.332641E+11 | 0.00 | 16.71 |
May | 0.00 | 0.00 | 0.00 | 0.153617E+09 | 0.00 | 0.00 | 0.243169E+11 | 0.00 | 14.26 |
June | 0.00 | 0.587601E+09 | 0.00 | 0.123421E+09 | 0.00 | 0.00 | 0.833526E+10 | 0.00 | 8.38 |
July | 0.00 | 0.720975E+10 | 0.00 | 37635406.90 | 0.00 | 0.00 | 0.309890E+10 | 0.00 | 6.67 |
August | 0.00 | 0.657267E+10 | 0.00 | 29507944.31 | 0.00 | 0.00 | 0.280448E+10 | 0.00 | 8.33 |
September | 0.00 | 0.598655E+10 | 0.00 | 50407781.46 | 0.00 | 0.00 | 0.555777E+10 | 0.00 | 12.32 |
October | 0.00 | 0.805390E+09 | 0.00 | 0.121337E+09 | 0.00 | 0.00 | 0.422044E+11 | 0.00 | 19.88 |
November | 0.00 | 484700.33 | 0.00 | 0.123523E+09 | 0.00 | 0.00 | 0.617348E+11 | 0.00 | 22.98 |
December | 0.00 | 0.00 | 0.00 | 0.115697E+09 | 0.00 | 0.00 | 0.728590E+11 | 0.00 | 20.60 |
Annual Sum or Average | 0.00 | 0.211624E+11 | 0.00 | 0.125710E+10 | 0.00 | 0.00 | 0.452779E+12 | 0.00 | 16.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 29507944.31 | 0.00 | 0.00 | 0.280448E+10 | 0.00 | 6.67 |
Maximum of Months | 0.00 | 0.720975E+10 | 0.00 | 0.153617E+09 | 0.00 | 0.00 | 0.728590E+11 | 0.00 | 22.98 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 123872.65 | 0.00 | 9962390.98 | 0.00 | 8216230.85 | 0.474579E+09 | 0.00 | 0.03 |
February | 0.00 | 0.00 | 0.00 | 4286791.16 | 0.00 | 0.00 | 0.274823E+09 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.00 | 10329450.06 | 0.00 | 0.00 | 0.406204E+09 | 0.00 | 0.03 |
April | 0.00 | 11252170.80 | 0.00 | 23930364.94 | 0.00 | 0.00 | 0.579627E+09 | 0.00 | 0.08 |
May | 0.00 | 50993194.60 | 0.00 | 24564462.64 | 0.00 | 0.00 | 0.538071E+09 | 0.00 | 0.10 |
June | 0.00 | 0.564514E+09 | 0.00 | 14751898.44 | 0.00 | 0.00 | 0.257374E+09 | 0.00 | 0.14 |
July | 0.00 | 0.132546E+10 | 0.00 | 4101620.12 | 0.00 | 0.00 | 81375829.92 | 0.00 | 0.13 |
August | 0.00 | 0.124893E+10 | 0.00 | 3095080.23 | 0.00 | 0.00 | 54021988.32 | 0.00 | 0.13 |
September | 0.00 | 0.868185E+09 | 0.00 | 4651511.22 | 0.00 | 0.00 | 76349413.31 | 0.00 | 0.11 |
October | 0.00 | 0.162865E+09 | 0.00 | 14441517.65 | 0.00 | 0.00 | 0.420053E+09 | 0.00 | 0.06 |
November | 0.00 | 4367866.44 | 0.00 | 9717051.89 | 0.00 | 0.00 | 0.408918E+09 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.00 | 4842684.84 | 0.00 | 33512717.56 | 0.310895E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.423669E+10 | 0.00 | 0.128675E+09 | 0.00 | 41728948.40 | 0.388229E+10 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3095080.23 | 0.00 | 0.00 | 54021988.32 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.132546E+10 | 0.00 | 24564462.64 | 0.00 | 33512717.56 | 0.579627E+09 | 0.00 | 0.14 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:24:41
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.239650E+12 | 0.949724E+10 | 0.984267E+11 | 0.356150E+12 | -NAN |
February | 0.270764E+12 | 0.946159E+10 | 0.108038E+12 | 0.361511E+12 | -NAN |
March | 0.366789E+12 | 0.887522E+10 | 0.909992E+11 | 0.342890E+12 | -NAN |
April | 0.457942E+12 | 0.350708E+10 | 0.482645E+11 | 0.167296E+12 | -NAN |
May | 0.477322E+12 | 0.178206E+10 | 0.355656E+11 | 0.102176E+12 | -NAN |
June | 0.487805E+12 | -0.140817E+10 | -0.105241E+11 | -0.654855E+10 | -NAN |
July | 0.435894E+12 | -0.431632E+10 | -0.566673E+11 | -0.710259E+11 | -NAN |
August | 0.367933E+12 | -0.389523E+10 | -0.526676E+11 | -0.593984E+11 | -NAN |
September | 0.313623E+12 | -0.272718E+10 | -0.337869E+11 | -0.333247E+11 | -NAN |
October | 0.301612E+12 | 0.459681E+10 | 0.497464E+11 | 0.215941E+12 | -NAN |
November | 0.247774E+12 | 0.824032E+10 | 0.885966E+11 | 0.325735E+12 | -NAN |
December | 0.193211E+12 | 0.118121E+11 | 0.124595E+12 | 0.397242E+12 | -NAN |
Annual Sum or Average | 0.416032E+13 | 0.454255E+11 | 0.490586E+12 | 0.209864E+13 | -NAN |
Minimum of Months | 0.193211E+12 | -0.431632E+10 | -0.566673E+11 | -0.710259E+11 | |
Maximum of Months | 0.487805E+12 | 0.118121E+11 | 0.124595E+12 | 0.397242E+12 |