Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2024-07-03 12:21:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11782.59 | 1038.54 | 1038.54 |
Net Site Energy | 11782.59 | 1038.54 | 1038.54 |
Total Source Energy | 27546.89 | 2428.05 | 2428.05 |
Net Source Energy | 27546.89 | 2428.05 | 2428.05 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 394.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1538.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 322.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1661.82 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 841.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1155.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2506.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 43.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 7092.93 | 4689.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 11.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 383.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1538.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 322.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 15.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 11.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1155.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 2506.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 394.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1538.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 322.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1661.82 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 841.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1155.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 2.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 2506.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 43.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 162.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 237.69 | 255.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.56 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 625.19 | 413.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 162.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 237.69 | 255.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.56 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 625.19 | 413.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 7092.928 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 7092.928 | 100.00 |
Total On-Site and Utility Electric Sources | 7092.928 | 100.00 |
Total Electricity End Uses | 7092.928 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 71.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7989.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 PTAC COOLING COIL | ROOM_2_FLR_3 PTAC COOLING COIL | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | ROOM_5_FLR_3 PTAC COOLING COIL | ROOM_6_FLR_3 PTAC COOLING COIL | ROOM_1_FLR_6 PTAC COOLING COIL | ROOM_2_FLR_6 PTAC COOLING COIL | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | PTAC_3 PTAC COOLING COIL | PTAC_6 PTAC COOLING COIL | VAV_FLR_1 COOLING COIL | VAV_FLR_6 COOLING COIL | VAV_FLR_0 COOLING COIL | PSZ_LAUNDRY COOLING COIL | PSZ_CAFE COOLING COIL | PSZ_KITCHEN COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_FLR_1 HEATING COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | VAV_FLR_6 HEATING COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 HEATING COIL | ROOM_2_FLR_3 HEATING COIL | ROOM_3_MULT19_FLR_3 HEATING COIL | ROOM_4_MULT19_FLR_3 HEATING COIL | ROOM_5_FLR_3 HEATING COIL | ROOM_6_FLR_3 HEATING COIL | ROOM_1_FLR_6 HEATING COIL | ROOM_2_FLR_6 HEATING COIL | ROOM_3_MULT9_FLR_6 HEATING COIL | VAV_FLR_0 HEATING COIL | PTAC_3 HEATING COIL | PTAC_6 HEATING COIL | PSZ_LAUNDRY HEATING COIL | PSZ_CAFE HEATING COIL | PSZ_KITCHEN HEATING COIL | ROOM_1_FLR_3 PTAC COOLING COIL | ROOM_2_FLR_3 PTAC COOLING COIL | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | ROOM_5_FLR_3 PTAC COOLING COIL | ROOM_6_FLR_3 PTAC COOLING COIL | ROOM_1_FLR_6 PTAC COOLING COIL | ROOM_2_FLR_6 PTAC COOLING COIL | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | PTAC_3 PTAC COOLING COIL | PTAC_6 PTAC COOLING COIL | VAV_FLR_1 COOLING COIL | VAV_FLR_6 COOLING COIL | VAV_FLR_0 COOLING COIL | PSZ_LAUNDRY COOLING COIL | PSZ_CAFE COOLING COIL | PSZ_KITCHEN COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| VAV_FLR_1 FAN | VAV_FLR_6 FAN | VAV_FLR_0 SZVAV FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | LAUNDRY_FLR_1 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3_PTAC_SUPPLY FAN | ROOM_2_FLR_3_PTAC_SUPPLY FAN | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | ROOM_5_FLR_3_PTAC_SUPPLY FAN | ROOM_6_FLR_3_PTAC_SUPPLY FAN | ROOM_1_FLR_6_PTAC_SUPPLY FAN | ROOM_2_FLR_6_PTAC_SUPPLY FAN | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | PTAC_3_PTAC_SUPPLY FAN | PTAC_6_PTAC_SUPPLY FAN | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |AirLoopSystemComponentLoadsMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |AirLoopSystemComponentEnergyUseMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1368.30 | 497.27 | 98.60 | 673.82 | 98.60 |
Gross Window-Wall Ratio [%] | 30.01 | 26.54 | 24.26 | 35.97 | 24.26 |
Above Ground Window-Wall Ratio [%] | 33.99 | 29.91 | 28.11 | 40.54 | 28.11 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1368.30 | 497.27 | 98.60 | 673.82 | 98.60 |
Gross Window-Wall Ratio [%] | 30.01 | 26.54 | 24.26 | 35.97 | 24.26 |
Above Ground Window-Wall Ratio [%] | 33.99 | 29.91 | 28.11 | 40.54 | 28.11 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 11.0679 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 16.1458 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 16.1458 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 15.0695 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 13.9931 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 4.22 | 4.22 | 12.2708 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 4.23 | 4.23 | 12.2708 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 18.31 | 18.31 | 5.3819 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 7.75 | 7.75 | 12.2709 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 36.97 | 36.97 | 15.0695 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 36.97 | 36.97 | 15.0695 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 30.28 | 30.28 | 12.9167 | 4.65 | 2935.6055 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 32.40 | 32.40 | 5.3819 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1368.30 | 1368.30 | 11.3147 | 7.07 | 41.0811 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1368.30 | 1368.30 | 11.3147 | 7.07 | 41.0811 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.0679 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 16.1458 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 16.1458 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 16.1458 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 8.6111 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 15.0695 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 13.9931 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 12.2708 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 12.2708 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 5.3819 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 12.2708 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 12.2708 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 12.2709 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 15.0695 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 15.0695 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 12.9167 | 4.65 | 2935.6055 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 5.3819 | 18.58 | 0.0000 | |
Total | 11345.29 | 11.3147 | 3.54 | 41.0811 | |||||||
Conditioned Total | 11345.29 | 11.3147 | 3.54 | 41.0811 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 6.0626 | 8.82 | 37.2091 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-JUN-19:10 | 26-DEC-19:10 | - | - | - | - | - | - | - | - | - | - | 07-FEB-21:00 |
Heating | 0.00 | 115108.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 180540.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86555.31 | 87619.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11860.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 54114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 226936.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1676.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 476535.94 | 429664.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 5255.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 109852.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 180540.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 365.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1288.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 9600.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 54114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 47.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 226936.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 770.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 664.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 427.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4872.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4833.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1021.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5262.99 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2666.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3658.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 8.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2717.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 22463.30 | 5083.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 37.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 429.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 89.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.89 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 322.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 239.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1979.97 | 448.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 37.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 429.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 89.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.89 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 322.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 239.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1979.97 | 448.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 3.77 | 0.399487 | 0.300000 | 1.13 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.522530 | 0.097810 | 0.300000 | 0.156759 | 0.300000 | 0.500000 | 0.003895 | 0.000055 | 0.309516 | 12.89 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.389208 | 0.152062 | 0.365000 | 0.142061 | 0.405498 | 0.500000 | 0.002506 | 0.000020 | 0.142061 | 12.89 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.455687 | 0.274648 | 0.300000 | 0.136706 | 0.732394 | 0.500000 | 0.001387 | 0.000027 | 0.148336 | 12.89 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.243357 | 0.296710 | 0.368000 | 0.089555 | 0.791228 | 0.500000 | 0.001284 | 0.000026 | 0.146619 | 12.89 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 7.06 | 0.141257 | 0.416000 | 2.94 | 0.416000 | 0.500000 | 0.002697 | 0.000397 | 2.94 | 12.89 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 3.31 | 0.076243 | 0.477000 | 1.58 | 0.477000 | 0.500000 | 0.004997 | 0.000200 | 1.58 | 12.89 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 3.46 | 0.072983 | 0.457000 | 1.58 | 0.457000 | 0.500000 | 0.005220 | 0.000202 | 1.58 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 6334.78 | 0.000055 | 147.75 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2297.71 | 0.000020 | 50.69 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3035.53 | 0.000027 | 70.80 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 3000.75 | 0.000026 | 69.99 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 45419.51 | 0.000397 | 993.21 |
ROOM_1_FLR_3 HEATING COIL | 15776.38 | 0.000138 | 393.04 |
ROOM_2_FLR_3 HEATING COIL | 15677.46 | 0.000137 | 390.54 |
ROOM_3_MULT19_FLR_3 HEATING COIL | 108597.17 | 0.000950 | 2660.36 |
ROOM_4_MULT19_FLR_3 HEATING COIL | 112763.40 | 0.000987 | 2766.24 |
ROOM_5_FLR_3 HEATING COIL | 13962.88 | 0.000122 | 347.15 |
ROOM_6_FLR_3 HEATING COIL | 13869.01 | 0.000121 | 344.77 |
PTAC_3 HEATING COIL | 35826.68 | 0.000313 | 847.89 |
ROOM_1_FLR_6 HEATING COIL | 4412.68 | 0.000039 | 110.11 |
ROOM_2_FLR_6 HEATING COIL | 4376.78 | 0.000038 | 109.21 |
ROOM_3_MULT9_FLR_6 HEATING COIL | 20919.02 | 0.000183 | 519.39 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 22885.08 | 0.000200 | 494.32 |
DINING_FLR_6 VAV BOX REHEAT COIL | 23053.41 | 0.000202 | 498.53 |
PTAC_6 HEATING COIL | 18667.72 | 0.000163 | 458.26 |
VAV_FLR_1 HEATING COIL | 49188.56 | 0.000430 | 801.61 |
VAV_FLR_6 HEATING COIL | 38596.01 | 0.000338 | 628.99 |
VAV_FLR_0 HEATING COIL | 36694.85 | 0.000321 | 2423.66 |
Design Size Maximum Air Flow Rate [m3/s] | |
LAUNDRY_FLR_1 DIRECT AIR | 4.45 |
CAFE_FLR_1 DIRECT AIR | 2.10 |
KITCHEN_FLR_6 DIRECT AIR | 3.05 |
Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | |
ROOM_1_FLR_3 | 1.19 | 1.19 | 1.19 | 0.061735 | 0.061735 | 0.061735 |
ROOM_2_FLR_3 | 1.18 | 1.18 | 1.18 | 0.061728 | 0.061728 | 0.061728 |
ROOM_3_MULT19_FLR_3 | 7.20 | 7.20 | 7.20 | 0.837072 | 0.837072 | 0.837072 |
ROOM_4_MULT19_FLR_3 | 7.55 | 7.55 | 7.55 | 0.837300 | 0.837300 | 0.837300 |
ROOM_5_FLR_3 | 1.03 | 1.03 | 1.03 | 0.061735 | 0.061735 | 0.061735 |
ROOM_6_FLR_3 | 1.03 | 1.03 | 1.03 | 0.061728 | 0.061728 | 0.061728 |
PTAC_3 | 1.91 | 1.91 | 1.91 | 0.474762 | 0.474762 | 0.474762 |
ROOM_1_FLR_6 | 0.336396 | 0.336396 | 0.336396 | 0.015434 | 0.015434 | 0.015434 |
ROOM_2_FLR_6 | 0.333366 | 0.333366 | 0.333366 | 0.015432 | 0.015432 | 0.015432 |
ROOM_3_MULT9_FLR_6 | 1.53 | 1.53 | 1.53 | 0.099154 | 0.099154 | 0.099154 |
PTAC_6 | 1.28 | 1.28 | 1.28 | 0.125616 | 0.125616 | 0.125616 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
ROOM_1_FLR_3 PTAC COOLING COIL | 1.19 | 19651.85 | 0.800655 |
ROOM_2_FLR_3 PTAC COOLING COIL | 1.18 | 19513.74 | 0.800655 |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 7.20 | 127518.67 | 0.800450 |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 7.55 | 131729.49 | 0.800714 |
ROOM_5_FLR_3 PTAC COOLING COIL | 1.03 | 17114.70 | 0.800655 |
ROOM_6_FLR_3 PTAC COOLING COIL | 1.03 | 16983.65 | 0.800655 |
PTAC_3 PTAC COOLING COIL | 1.91 | 36116.65 | 0.798574 |
ROOM_1_FLR_6 PTAC COOLING COIL | 0.336396 | 5568.55 | 0.800655 |
ROOM_2_FLR_6 PTAC COOLING COIL | 0.333366 | 5518.39 | 0.800655 |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 1.53 | 25614.64 | 0.800290 |
PTAC_6 PTAC COOLING COIL | 1.28 | 21365.08 | 0.800033 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3_PTAC_SUPPLY FAN | 1.19 |
ROOM_2_FLR_3_PTAC_SUPPLY FAN | 1.18 |
ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | 7.20 |
ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | 7.55 |
ROOM_5_FLR_3_PTAC_SUPPLY FAN | 1.03 |
ROOM_6_FLR_3_PTAC_SUPPLY FAN | 1.03 |
PTAC_3_PTAC_SUPPLY FAN | 1.91 |
ROOM_1_FLR_6_PTAC_SUPPLY FAN | 0.336396 |
ROOM_2_FLR_6_PTAC_SUPPLY FAN | 0.333366 |
ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | 1.53 |
PTAC_6_PTAC_SUPPLY FAN | 1.28 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_FLR_1 | 4.33 | 3.46 | 8.67 | 3.46 | 8.64 | 8.64 | 0.300000 | 0.400668 | 8.64 |
VAV_FLR_6 | 3.39 | 3.16 | 6.78 | 3.16 | 6.78 | 6.78 | 0.300000 | 0.466782 | 6.78 |
VAV_FLR_0 | 1.13 | 1.13 | 3.77 | 1.13 | 3.77 | 3.77 | 1.00 | 0.300000 | 3.77 |
PSZ_LAUNDRY | 4.45 | 4.45 | 4.45 | 4.45 | 4.45 | 4.45 | 1.00 | 1.00 | 4.45 |
PSZ_CAFE | 2.10 | 2.10 | 2.10 | 2.10 | 2.10 | 2.10 | 1.00 | 1.00 | 2.10 |
PSZ_KITCHEN | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 1.00 | 1.00 | 3.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_FLR_1_OA_CONTROLLER | 8.64 | |
VAV_FLR_6_OA_CONTROLLER | 6.78 | |
VAV_FLR_0_OA_CONTROLLER | 3.77 | |
PSZ_LAUNDRY_OA_CONTROLLER | 4.45 | 0.000000 |
PSZ_CAFE_OA_CONTROLLER | 2.10 | 0.676389 |
PSZ_KITCHEN_OA_CONTROLLER | 3.05 | 0.367350 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
VAV_FLR_1 COOLING COIL | 8.64 | 174625.31 | 0.772032 | 2.88 | 58202.62 | 0.772032 |
VAV_FLR_6 COOLING COIL | 6.78 | 147965.47 | 0.743764 | 2.26 | 49316.89 | 0.743764 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_FLR_1 FAN | 8.64 |
VAV_FLR_6 FAN | 6.78 |
VAV_FLR_0 SZVAV FAN | 3.77 |
Maximum Actuated Flow [m3/s] | |
VAV_FLR_1_HEATC_CONTROLLER | 0.000430 |
VAV_FLR_6_HEATC_CONTROLLER | 0.000338 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | Design Size Maximum Supply Air Temperature [C] | |
VAV_FLR_0_UNITARY_PACKAGE_DX | 3.77 | 3.77 | 3.77 | 1.13 | 62541.12 | 67499.48 | 1.00 | 12.89 | 32.11 | |
PSZ_LAUNDRY_UNITARY_PACKAGE_DX | 4.45 | 4.45 | 4.45 | 4.45 | 73683.71 | 51899.70 | 1.00 | 32.11 | ||
PSZ_CAFE_UNITARY_PACKAGE_DX | 2.10 | 2.10 | 2.10 | 2.10 | 45150.18 | 43131.11 | 1.00 | 32.11 | ||
PSZ_KITCHEN_UNITARY_PACKAGE_DX | 3.05 | 3.05 | 3.05 | 3.05 | 61493.60 | 46284.78 | 1.00 | 32.11 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
VAV_FLR_0 COOLING COIL | 3.77 | 1.89 | 2.52 | 62541.12 | 31270.56 | 0.800300 | 0.800300 |
PSZ_LAUNDRY COOLING COIL | 4.45 | 2.23 | 2.97 | 73683.71 | 36841.86 | 0.800660 | 0.800660 |
PSZ_CAFE COOLING COIL | 2.10 | 1.05 | 1.40 | 45150.18 | 22575.09 | 0.749640 | 0.749640 |
PSZ_KITCHEN COOLING COIL | 3.05 | 1.52 | 2.03 | 61493.60 | 30746.80 | 0.772620 | 0.772620 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | 4.45 | 7220.45 |
PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | 2.10 | 3497.28 |
PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | 3.05 | 4943.55 |
Design Size Nominal Capacity [W] | |
PSZ_LAUNDRY HEATING COIL | 51899.70 |
PSZ_CAFE HEATING COIL | 43131.11 |
PSZ_KITCHEN HEATING COIL | 46284.78 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.005208 | 0.625011 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.005208 | 1568.55 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 595355.36 | 595355.36 | 0.005208 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 6.92 | 4.22 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 6.92 | 4.23 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 30.00 | 18.31 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 12.69 | 7.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 60.57 | 36.97 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 60.57 | 36.97 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 57.04 | 30.28 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 53.08 | 32.40 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 11.068 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.448 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 16.146 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.906 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 16.146 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.906 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 16.146 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 21.526 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 8.611 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 11.301 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 15.069 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 20.449 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 13.993 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 22.063 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 15.069 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 82.889 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 15.069 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 82.889 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 12.917 | 516.346 | 2419.260 | 0.000 | 0.000 | 0.000 | 2948.522 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 21901.435 | 11.068 | 205.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21901.435 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1082.924 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1082.924 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1254.030 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1254.030 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 2651.846 | 16.146 | 999.942 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2651.846 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 815.983 | 8.611 | 399.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 815.983 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2846.047 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2846.047 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 18305.540 | 13.993 | 43.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18305.540 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 300.928 | 12.271 | 200.619 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 300.928 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 301.011 | 12.271 | 200.674 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 301.011 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2095.757 | 5.382 | 100.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2095.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 301.011 | 12.271 | 200.674 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 301.011 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4997.899 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4997.899 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4997.899 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4997.899 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1334.351 | 12.917 | 60.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1334.351 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2218.035 | 5.382 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2218.035 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 493.000 | 4.772 | 22.169 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 493.000 | 493.000 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 365.000 | 3.533 | 16.413 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 365.000 | 365.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 200.0 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | NONRES_EXT_WALL_MID | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_TOP | 23 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | RES_EXT_WALL_MID | 25 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | RES_EXT_WALL_TOP | 26 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5000E-02 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
13 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
14 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
15 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
19 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
20 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
21 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
23 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
24 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
25 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
26 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
27 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
28 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
31 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
36 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
37 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
38 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
39 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
40 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
42 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
44 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
46 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 200.00000 | 200.00000 | 200.00000 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
21 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
22 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
23 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
24 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
25 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
26 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
27 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
28 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
29 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
30 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
31 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
32 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
33 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
34 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
35 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
36 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
37 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
38 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
39 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
40 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
41 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
42 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
43 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
44 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
45 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
46 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
47 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
48 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
49 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
50 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
51 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
52 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
53 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
54 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
55 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
56 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
57 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
58 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
59 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
60 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
61 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
62 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
63 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
64 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
65 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
66 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
67 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
68 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
69 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
70 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
71 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
72 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
73 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
74 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
75 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
76 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
77 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
78 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
79 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
80 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
81 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
82 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
83 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
84 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
85 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
86 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
87 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
88 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
89 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
90 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
91 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
108 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
109 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
110 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
111 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
112 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
113 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
114 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
115 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
116 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
117 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
118 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
119 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
120 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
121 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
122 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
123 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.57_SHGC_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 8000.0 | 0.975 | 0.8950 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone RETAIL_1_FLR_1 | 1.2500 |
4 | Zone RETAIL_2_FLR_1 | 1.2500 |
5 | Zone MECH_FLR_1 | 1.2500 |
6 | Zone STORAGE_FLR_1 | 1.2500 |
7 | Zone LAUNDRY_FLR_1 | 1.2500 |
8 | Zone CAFE_FLR_1 | 1.2500 |
9 | Zone LOBBY_FLR_1 | 1.2500 |
10 | Zone ROOM_1_FLR_3 | 1.2500 |
11 | Zone ROOM_2_FLR_3 | 1.2500 |
12 | Zone ROOM_3_MULT19_FLR_3 | 1.2500 |
13 | Zone ROOM_4_MULT19_FLR_3 | 1.2500 |
14 | Zone ROOM_5_FLR_3 | 1.2500 |
15 | Zone ROOM_6_FLR_3 | 1.2500 |
16 | Zone CORRIDOR_FLR_3 | 1.2500 |
17 | Zone ROOM_1_FLR_6 | 1.2500 |
18 | Zone ROOM_2_FLR_6 | 1.2500 |
19 | Zone ROOM_3_MULT9_FLR_6 | 1.2500 |
20 | Zone BANQUET_FLR_6 | 1.2500 |
21 | Zone DINING_FLR_6 | 1.2500 |
22 | Zone KITCHEN_FLR_6 | 1.2500 |
23 | Zone CORRIDOR_FLR_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone RETAIL_1_FLR_1 | 1.1500 |
4 | Zone RETAIL_2_FLR_1 | 1.1500 |
5 | Zone MECH_FLR_1 | 1.1500 |
6 | Zone STORAGE_FLR_1 | 1.1500 |
7 | Zone LAUNDRY_FLR_1 | 1.1500 |
8 | Zone CAFE_FLR_1 | 1.1500 |
9 | Zone LOBBY_FLR_1 | 1.1500 |
10 | Zone ROOM_1_FLR_3 | 1.1500 |
11 | Zone ROOM_2_FLR_3 | 1.1500 |
12 | Zone ROOM_3_MULT19_FLR_3 | 1.1500 |
13 | Zone ROOM_4_MULT19_FLR_3 | 1.1500 |
14 | Zone ROOM_5_FLR_3 | 1.1500 |
15 | Zone ROOM_6_FLR_3 | 1.1500 |
16 | Zone CORRIDOR_FLR_3 | 1.1500 |
17 | Zone ROOM_1_FLR_6 | 1.1500 |
18 | Zone ROOM_2_FLR_6 | 1.1500 |
19 | Zone ROOM_3_MULT9_FLR_6 | 1.1500 |
20 | Zone BANQUET_FLR_6 | 1.1500 |
21 | Zone DINING_FLR_6 | 1.1500 |
22 | Zone KITCHEN_FLR_6 | 1.1500 |
23 | Zone CORRIDOR_FLR_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 38866.08999 | 44696.00349 | 3.28218 | 3.77451 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 30.62500 | 6.85962E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 5380.07463 | 6187.08583 | 0.45437 | 0.52253 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 38.10000 | 6.87148E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2930.02084 | 3662.52605 | 0.24761 | 0.30952 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 4007.24296 | 4608.32940 | 0.33844 | 0.38921 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 36.06333 | 6.86822E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 857.03909 | 1071.29886 | 7.24300E-002 | 9.17347E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 4692.76388 | 5396.67846 | 0.39625 | 0.45569 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1404.17179 | 1755.21473 | 0.11867 | 0.14834 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 2506.12214 | 2882.04046 | 0.21161 | 0.24336 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 36.06333 | 6.86822E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1387.91434 | 1734.89292 | 0.11729 | 0.14662 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45835.63776 | 52710.98343 | 3.87064 | 4.45123 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 35.97667 | 6.86808E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1935.52876 | 2419.41095 | 0.16357 | 0.20446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21646.99427 | 24894.04341 | 1.82979 | 2.10426 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7665.17329 | 9581.46662 | 0.64778 | 0.80973 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 72635.86215 | 83531.24148 | 6.13646 | 7.05692 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 16059.35685 | 20074.19606 | 1.35721 | 1.89399 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12226.72425 | 14060.73289 | 1.03232 | 1.18717 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5580.99661 | 6976.24577 | 0.47168 | 0.58960 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 12140.79911 | 13961.91897 | 1.02507 | 1.17883 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5572.98875 | 6966.23594 | 0.47100 | 0.58876 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 74117.13572 | 85234.70608 | 6.25759 | 7.19623 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 32157.15830 | 40196.44787 | 2.71788 | 3.39735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 77732.10661 | 89391.92260 | 6.56331 | 7.54781 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 32024.09027 | 40030.11284 | 2.70663 | 3.38329 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10648.19178 | 12245.42055 | 0.89904 | 1.03390 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 33.81000 | 6.86464E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5565.48198 | 6956.85247 | 0.47037 | 0.58796 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10566.66001 | 12151.65901 | 0.89216 | 1.02598 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5557.47177 | 6946.83971 | 0.46969 | 0.58712 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 19650.70245 | 22598.30782 | 1.65943 | 1.90834 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9324.13730 | 11655.17163 | 0.78801 | 0.98501 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3464.56420 | 3984.24884 | 0.29252 | 0.33640 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.86994E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1869.41750 | 2336.77187 | 0.15800 | 0.19749 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3433.36218 | 3948.36651 | 0.28988 | 0.33337 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 36.97333 | 6.86968E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1868.44808 | 2335.56010 | 0.15791 | 0.19739 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 15790.21700 | 18158.74955 | 1.33323 | 1.53322 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10000 | 6.87148E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9161.32981 | 11451.66226 | 0.77429 | 0.96786 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 34088.97292 | 39202.31886 | 2.88234 | 3.31469 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7385.16938 | 9231.46172 | 0.62413 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 35612.08580 | 40953.89867 | 3.01108 | 3.46275 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7510.36981 | 9387.96227 | 0.63471 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31296.62674 | 35991.12075 | 2.65007 | 3.04758 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2541.75230 | 3177.19037 | 0.21479 | 0.36735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 13195.71760 | 15175.07524 | 1.11431 | 1.28146 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 38.10000 | 6.87148E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8089.54423 | 10111.93029 | 0.68367 | 0.85458 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_FLR_1 | Cooling | Sensible | 142560.75 | 8.63748 | 8.63748 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_FLR_1 | Heating | Sensible | 49168.64 | 2.59020 | 2.59020 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | VAV_FLR_6 | Cooling | Sensible | 125835.76 | 6.77744 | 6.77744 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_FLR_6 | Heating | Sensible | 45094.94 | 2.37559 | 2.37559 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | VAV_FLR_0 | Cooling | Sensible | 49946.71 | 3.77451 | 3.77451 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | VAV_FLR_0 | Heating | Sensible | 33454.91 | 0.85446 | 0.85446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ_LAUNDRY | Cooling | Sensible | 51895.90 | 4.45123 | 4.45123 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
8 | PSZ_LAUNDRY | Heating | Sensible | 2383.93 | 0.20446 | 0.20446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
9 | PSZ_CAFE | Cooling | Sensible | 34449.07 | 2.10426 | 2.10426 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ_CAFE | Heating | Sensible | 28037.54 | 0.80973 | 0.80973 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
11 | PSZ_KITCHEN | Cooling | Sensible | 40371.24 | 3.04758 | 3.04758 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ_KITCHEN | Heating | Sensible | 14382.99 | 0.36735 | 0.36735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 3.77451 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.39949 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 1.13235 |
5 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52253 |
6 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.78095E-002 |
7 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15676 |
9 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
10 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.89533E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.54194E-005 |
13 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30952 |
14 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6334.77652 |
17 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.54194E-005 |
18 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 147.75322 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.38921 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15206 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36500 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14206 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40550 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50556E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.01014E-005 |
27 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14206 |
28 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2297.71315 |
31 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01014E-005 |
32 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 50.68788 |
33 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.45569 |
34 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27465 |
35 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13671 |
37 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73239 |
38 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38723E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.65561E-005 |
41 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14834 |
42 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3035.52858 |
45 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.65561E-005 |
46 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 70.79838 |
47 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24336 |
48 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29671 |
49 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36800 |
50 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.95554E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79123 |
52 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28408E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.62518E-005 |
55 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14662 |
56 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3000.74622 |
59 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.62518E-005 |
60 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 69.98946 |
61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LAUNDRY_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.45123 |
62 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CAFE_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.10426 |
63 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.05692 |
64 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14126 |
65 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.41600 |
66 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.93568 |
67 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41600 |
68 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
69 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69722E-003 |
70 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.97350E-004 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.93568 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
74 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 45419.50514 |
75 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.97350E-004 |
76 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 993.20725 |
77 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.18717 |
78 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.18717 |
79 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.18717 |
80 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17350E-002 |
81 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17350E-002 |
82 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17350E-002 |
83 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 15776.37813 |
84 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.38019E-004 |
85 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 393.04134 |
86 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.18717 |
87 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 19651.84974 |
88 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
89 | Fan:OnOff | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.18717 |
90 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.17883 |
91 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.17883 |
92 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.17883 |
93 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17278E-002 |
94 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17278E-002 |
95 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17278E-002 |
96 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 15677.46073 |
97 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37153E-004 |
98 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 390.53913 |
99 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.17883 |
100 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 19513.74376 |
101 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
102 | Fan:OnOff | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.17883 |
103 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.19623 |
104 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 7.19623 |
105 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 7.19623 |
106 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.83707 |
107 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.83707 |
108 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.83707 |
109 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 108597.16607 |
110 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.50055E-004 |
111 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2660.36336 |
112 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 7.19623 |
113 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 127518.67004 |
114 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80045 |
115 | Fan:OnOff | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 7.19623 |
116 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.54781 |
117 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 7.54781 |
118 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 7.54781 |
119 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.83730 |
120 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.83730 |
121 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.83730 |
122 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 112763.40404 |
123 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.86503E-004 |
124 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2766.23523 |
125 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 7.54781 |
126 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 131729.48913 |
127 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80071 |
128 | Fan:OnOff | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 7.54781 |
129 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.03390 |
130 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.03390 |
131 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03390 |
132 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17350E-002 |
133 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17350E-002 |
134 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17350E-002 |
135 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 13962.88279 |
136 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22153E-004 |
137 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 347.14505 |
138 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.03390 |
139 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 17114.69718 |
140 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
141 | Fan:OnOff | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.03390 |
142 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02598 |
143 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02598 |
144 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02598 |
145 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17278E-002 |
146 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17278E-002 |
147 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17278E-002 |
148 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 13869.01257 |
149 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21332E-004 |
150 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 344.76960 |
151 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.02598 |
152 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 16983.65242 |
153 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
154 | Fan:OnOff | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.02598 |
155 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.90834 |
156 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.90834 |
157 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.90834 |
158 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.47476 |
159 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.47476 |
160 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47476 |
161 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size Rated Capacity [W] | 35826.68142 |
162 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.13427E-004 |
163 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 847.89303 |
164 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.90834 |
165 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 36116.65247 |
166 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79857 |
167 | Fan:OnOff | PTAC_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.90834 |
168 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33640 |
169 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33640 |
170 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33640 |
171 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.54338E-002 |
172 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.54338E-002 |
173 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.54338E-002 |
174 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 4412.68088 |
175 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.86041E-005 |
176 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 110.11328 |
177 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33640 |
178 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5568.54504 |
179 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
180 | Fan:OnOff | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33640 |
181 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.33337 |
182 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 0.33337 |
183 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 0.33337 |
184 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.54319E-002 |
185 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.54319E-002 |
186 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.54319E-002 |
187 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 4376.78393 |
188 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.82900E-005 |
189 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 109.20541 |
190 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.33337 |
191 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5518.39453 |
192 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
193 | Fan:OnOff | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.33337 |
194 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53322 |
195 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53322 |
196 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.53322 |
197 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 9.91540E-002 |
198 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 9.91540E-002 |
199 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 9.91540E-002 |
200 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 20919.01558 |
201 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.83009E-004 |
202 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 519.39082 |
203 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.53322 |
204 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 25614.64087 |
205 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80029 |
206 | Fan:OnOff | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.53322 |
207 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.31469 |
208 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.62432E-002 |
209 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47700 |
210 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.58111 |
211 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47700 |
212 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.99716E-003 |
214 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.00209E-004 |
215 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.58111 |
216 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
217 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
218 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22885.07937 |
219 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.00209E-004 |
220 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 494.32339 |
221 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.46275 |
222 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.29834E-002 |
223 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45700 |
224 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.58247 |
225 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45700 |
226 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
227 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.22036E-003 |
228 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.01681E-004 |
229 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.58247 |
230 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
231 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
232 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23053.41356 |
233 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01681E-004 |
234 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 498.53190 |
235 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.04758 |
236 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.28146 |
237 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.28146 |
238 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.28146 |
239 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.12562 |
240 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.12562 |
241 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.12562 |
242 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size Rated Capacity [W] | 18667.71551 |
243 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63313E-004 |
244 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 458.25936 |
245 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.28146 |
246 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 21365.07833 |
247 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80003 |
248 | Fan:OnOff | PTAC_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.28146 |
249 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.33385 |
250 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.46076 |
251 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.66771 |
252 | AirLoopHVAC | VAV_FLR_1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.46076 |
253 | AirLoopHVAC | VAV_FLR_1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.63748 |
254 | AirLoopHVAC | VAV_FLR_1 | Adjusted Main Design Air Flow Rate [m3/s] | 8.63748 |
255 | AirLoopHVAC | VAV_FLR_1 | User Heating Air Flow Ratio [] | 0.30000 |
256 | AirLoopHVAC | VAV_FLR_1 | Calculated Heating Air Flow Ratio [] | 0.40067 |
257 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.38872 |
258 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.16358 |
259 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.77744 |
260 | AirLoopHVAC | VAV_FLR_6 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.16358 |
261 | AirLoopHVAC | VAV_FLR_6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.77744 |
262 | AirLoopHVAC | VAV_FLR_6 | Adjusted Main Design Air Flow Rate [m3/s] | 6.77744 |
263 | AirLoopHVAC | VAV_FLR_6 | User Heating Air Flow Ratio [] | 0.30000 |
264 | AirLoopHVAC | VAV_FLR_6 | Calculated Heating Air Flow Ratio [] | 0.46678 |
265 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.13235 |
266 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.13235 |
267 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.77451 |
268 | AirLoopHVAC | VAV_FLR_0 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13235 |
269 | AirLoopHVAC | VAV_FLR_0 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.77451 |
270 | AirLoopHVAC | VAV_FLR_0 | Adjusted Main Design Air Flow Rate [m3/s] | 3.77451 |
271 | AirLoopHVAC | VAV_FLR_0 | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | VAV_FLR_0 | Calculated Heating Air Flow Ratio [] | 0.30000 |
273 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.45123 |
274 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.45123 |
275 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.45123 |
276 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Heating Design Air Flow Rate [m3/s] | 4.45123 |
277 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.45123 |
278 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Main Design Air Flow Rate [m3/s] | 4.45123 |
279 | AirLoopHVAC | PSZ_LAUNDRY | User Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | PSZ_LAUNDRY | Calculated Heating Air Flow Ratio [] | 1.00000 |
281 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.10426 |
282 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.10426 |
283 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.10426 |
284 | AirLoopHVAC | PSZ_CAFE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.10426 |
285 | AirLoopHVAC | PSZ_CAFE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.10426 |
286 | AirLoopHVAC | PSZ_CAFE | Adjusted Main Design Air Flow Rate [m3/s] | 2.10426 |
287 | AirLoopHVAC | PSZ_CAFE | User Heating Air Flow Ratio [] | 1.00000 |
288 | AirLoopHVAC | PSZ_CAFE | Calculated Heating Air Flow Ratio [] | 1.00000 |
289 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.04758 |
290 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.04758 |
291 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.04758 |
292 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Heating Design Air Flow Rate [m3/s] | 3.04758 |
293 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.04758 |
294 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Main Design Air Flow Rate [m3/s] | 3.04758 |
295 | AirLoopHVAC | PSZ_KITCHEN | User Heating Air Flow Ratio [] | 1.00000 |
296 | AirLoopHVAC | PSZ_KITCHEN | Calculated Heating Air Flow Ratio [] | 1.00000 |
297 | AirLoopHVAC | VAV_FLR_1 | Design Supply Air Flow Rate [m3/s] | 8.63748 |
298 | AirLoopHVAC | VAV_FLR_6 | Design Supply Air Flow Rate [m3/s] | 6.77744 |
299 | AirLoopHVAC | VAV_FLR_0 | Design Supply Air Flow Rate [m3/s] | 3.77451 |
300 | AirLoopHVAC | PSZ_LAUNDRY | Design Supply Air Flow Rate [m3/s] | 4.45123 |
301 | AirLoopHVAC | PSZ_CAFE | Design Supply Air Flow Rate [m3/s] | 2.10426 |
302 | AirLoopHVAC | PSZ_KITCHEN | Design Supply Air Flow Rate [m3/s] | 3.04758 |
303 | Controller:OutdoorAir | VAV_FLR_1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.63748 |
304 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 8.63748 |
305 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 174625.30775 |
306 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77203 |
307 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.87887 |
308 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 58202.61507 |
309 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77203 |
310 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size Rated Capacity [W] | 49188.56177 |
311 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.30323E-004 |
312 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 801.61057 |
313 | Fan:VariableVolume | VAV_FLR_1 FAN | Design Size Maximum Flow Rate [m3/s] | 8.63748 |
314 | Controller:WaterCoil | VAV_FLR_1_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.30323E-004 |
315 | Controller:OutdoorAir | VAV_FLR_6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.77744 |
316 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.77744 |
317 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 147965.47019 |
318 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74376 |
319 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.25892 |
320 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 49316.89121 |
321 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74376 |
322 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 38596.01262 |
323 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.37655E-004 |
324 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 628.98711 |
325 | Fan:VariableVolume | VAV_FLR_6 FAN | Design Size Maximum Flow Rate [m3/s] | 6.77744 |
326 | Controller:WaterCoil | VAV_FLR_6_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.37655E-004 |
327 | Controller:OutdoorAir | VAV_FLR_0_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.77451 |
328 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.77451 |
329 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.77451 |
330 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.77451 |
331 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13235 |
332 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.77451 |
333 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.88725 |
334 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.51634 |
335 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 62541.12000 |
336 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31270.56000 |
337 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80030 |
338 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80030 |
339 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 62541.12000 |
340 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size Rated Capacity [W] | 36694.84513 |
341 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.21023E-004 |
342 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2423.66293 |
343 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67499.47868 |
344 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
345 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
346 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
347 | Fan:VariableVolume | VAV_FLR_0 SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 3.77451 |
348 | Controller:OutdoorAir | PSZ_LAUNDRY_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.45123 |
349 | Controller:OutdoorAir | PSZ_LAUNDRY_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.00000 |
350 | Fan:SystemModel | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 4.45123 |
351 | Fan:SystemModel | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 7220.45129 |
352 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 4.45123 |
353 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 4.45123 |
354 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 4.45123 |
355 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.45123 |
356 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 4.45123 |
357 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.22562 |
358 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.96749 |
359 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 73683.71000 |
360 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 36841.85500 |
361 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
362 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
363 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 73683.71000 |
364 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51899.70495 |
365 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
366 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Coil:Heating:Fuel | PSZ_LAUNDRY HEATING COIL | Design Size Nominal Capacity [W] | 51899.70495 |
368 | Controller:OutdoorAir | PSZ_CAFE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.10426 |
369 | Controller:OutdoorAir | PSZ_CAFE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.67639 |
370 | Fan:SystemModel | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.10426 |
371 | Fan:SystemModel | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3497.27969 |
372 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.10426 |
373 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.10426 |
374 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.10426 |
375 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.10426 |
376 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.10426 |
377 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.05213 |
378 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.40284 |
379 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 45150.18000 |
380 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22575.09000 |
381 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74964 |
382 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74964 |
383 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45150.18000 |
384 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 43131.10571 |
385 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
386 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Coil:Heating:Fuel | PSZ_CAFE HEATING COIL | Design Size Nominal Capacity [W] | 43131.10571 |
388 | Controller:OutdoorAir | PSZ_KITCHEN_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.04758 |
389 | Controller:OutdoorAir | PSZ_KITCHEN_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.36735 |
390 | Fan:SystemModel | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.04758 |
391 | Fan:SystemModel | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 4943.54780 |
392 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.04758 |
393 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.04758 |
394 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.04758 |
395 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.04758 |
396 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.04758 |
397 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.52379 |
398 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.03172 |
399 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 61493.60000 |
400 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30746.80000 |
401 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77262 |
402 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77262 |
403 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 61493.60000 |
404 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46284.78409 |
405 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
406 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
407 | Coil:Heating:Fuel | PSZ_KITCHEN HEATING COIL | Design Size Nominal Capacity [W] | 46284.78409 |
408 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.20843E-003 |
409 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.62501 |
410 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.20843E-003 |
411 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1568.54992 |
412 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
413 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 595355.36370 |
414 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 595355.36000 |
415 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.20843E-003 |
416 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
417 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
418 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
419 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
420 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 6011.26 |
2 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2180.91 |
3 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2880.51 |
4 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2847.50 |
5 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 43111.97 |
6 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | 16628.81 |
7 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | 16522.02 |
8 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | 111431.11 |
9 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | 115963.49 |
10 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | 14669.45 |
11 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | 14568.04 |
12 | Coil:Heating:Water | PTAC_3 HEATING COIL | 34817.65 |
13 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | 4663.14 |
14 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | 4624.40 |
15 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | 21931.38 |
16 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 21723.37 |
17 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 21883.07 |
18 | Coil:Heating:Water | PTAC_6 HEATING COIL | 19269.37 |
19 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | 37039.96 |
20 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | 29063.56 |
21 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | 66525.27 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | 18730.7 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
2 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | 18599.0 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
3 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 121933.3 | 2.68 | 9.16 | 9.72 | 9.19 | 9.20 |
4 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 125871.6 | 2.68 | 9.14 | 9.69 | 9.17 | 9.17 |
5 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | 16312.4 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
6 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | 16187.5 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
7 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | 34635.1 | 2.71 | 9.26 | 9.82 | 9.29 | 9.35 |
8 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | 5307.5 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
9 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | 5259.7 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
10 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 24424.9 | 2.66 | 9.07 | 9.62 | 9.10 | 9.06 |
11 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | 20370.7 | 2.66 | 9.06 | 9.61 | 9.09 | 9.06 |
12 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | 59583.0 | 10.16 | 10.16 | |||
13 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | 70195.2 | 10.40 | 10.40 | |||
14 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | 43494.6 | 10.63 | 10.63 | |||
15 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | 59098.2 | 10.53 | 10.53 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | N/A | N/A | 168241.67 | 574064.40 | 11.04 | 3.00 | 3.23 | 3.21 | 3.35 | 10.22 | 11.02 | 10.96 | 11.43 | 8.6642 | 6.9002 | 4.6305 | 1.8841 |
2 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | N/A | N/A | 142975.05 | 487851.14 | 11.18 | 3.03 | 3.27 | 3.26 | 3.37 | 10.34 | 11.16 | 11.11 | 11.51 | 6.7984 | 5.4010 | 3.6235 | 1.5123 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 200.000 | 200.000 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 6.92 | 11.15 | 6.92 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.22 | 4.22 | 4.22 | 180.00 | 90.00 | 3.02 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 6.92 | 11.15 | 6.92 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 4.23 | 4.23 | 4.23 | 0.00 | 90.00 | 3.02 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 90.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 90.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 4.04 | 6.50 | 4.04 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 2.47 | 2.47 | 2.47 | 0.00 | 90.00 | 1.76 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 4.04 | 6.50 | 4.04 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 2.46 | 2.46 | 2.46 | 180.00 | 90.00 | 1.76 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 12.69 | 20.44 | 12.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.75 | 7.75 | 7.75 | 180.00 | 90.00 | 5.53 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.57 | 97.55 | 60.57 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 36.97 | 36.97 | 36.97 | 0.00 | 90.00 | 26.40 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.57 | 97.55 | 60.57 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 36.97 | 36.97 | 36.97 | 0.00 | 90.00 | 26.40 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 16.08 | 21.37 | 16.08 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 32.31 | 52.03 | 32.31 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 19.72 | 19.72 | 19.72 | 90.00 | 90.00 | 14.08 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 9.81 | 15.79 | 9.81 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 5.99 | 5.99 | 5.99 | 0.00 | 90.00 | 4.27 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 32.31 | 52.03 | 32.31 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 19.72 | 19.72 | 19.72 | 180.00 | 90.00 | 14.08 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.5058137653E-004 | 1.1024654062E-003 | Pass | Pass | 1.4384800565E-002 | 3.5636724181E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.4339261633E-002 | 8.3565514487E-002 | Pass | Pass | 3.2655098222E-002 | 3.7071988837E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7434304034E-002 | 2.6339493812E-002 | Pass | Pass | 4.4420413954E-003 | 4.8530424455E-003 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1187428119E-002 | 2.1615072805E-002 | Pass | Pass | 3.1744977893E-003 | 3.5652753865E-003 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5288452728E-002 | 1.2465227361E-002 | Pass | Pass | 5.2145166323E-003 | 8.0086426899E-003 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.0141455045E-005 | 1.0388393221E-004 | Pass | Pass | 2.0689931876E-002 | 5.8806684916E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.8666499236E-002 | 9.4386857125E-002 | Pass | Pass | 2.6991371320E-002 | 3.0657256113E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.2822952336E-002 | 3.9655978089E-002 | Pass | Pass | 6.0007815751E-003 | 9.9126878286E-003 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.5807992857E-002 | 0.2891861571 | Pass | Pass | 0.1537612646 | 0.2704841973 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.0560229293E-002 | 0.2264738537 | Pass | Pass | 0.1940530941 | 0.4255769280 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0702353761E-002 | 2.3339711357E-002 | Pass | Pass | 7.3899151663E-002 | 0.2754898665 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.2488547109E-002 | 0.2439475100 | Pass | Pass | 0.1247610819 | 0.4524655026 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.9203576705E-002 | 0.3014762654 | Pass | Pass | 0.3050507503 | 1.3248161748 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.8932751445E-002 | 0.1924252622 | Pass | Pass | 0.1555697283 | 0.4961273699 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.1628330421E-005 | 2.0458824963E-004 | Pass | Pass | 9.2331504254E-002 | 0.3794285883 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.4586610337E-002 | 0.2448590742 | Pass | Pass | 0.1495997969 | 0.3653442936 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.9519407302E-002 | 0.2105715612 | Pass | Pass | 0.1882508990 | 0.4539033585 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.1528609733E-002 | 0.3249404299 | Pass | Pass | 0.2513392613 | 0.7845182334 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.3486596588E-002 | 8.2496060971E-002 | Pass | Pass | 7.7334455999E-003 | 1.8212532542E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.8005171865E-002 | 7.1528469803E-002 | Pass | Pass | 8.3693947385E-003 | 2.2584055133E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.7310645709E-003 | 2.7986228056E-003 | Pass | Pass | 2.3079724869E-002 | 4.4148157209E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.9344500243E-002 | 3.4783311285E-002 | Pass | Pass | 5.9153415781E-002 | 0.1811057863 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4647.71 | 70.55 | 794.95 | 2870.20 | 7251.62 | 15635.06 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.06 | 64.62 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.05 | 64.61 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 847.14 | 526.04 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 847.37 | 526.16 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.06 | 64.62 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.05 | 64.61 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 70.60 | 43.85 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 26.01 | 16.14 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 26.02 | 16.16 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 70.60 | 43.85 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 13.94 | 8.65 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 26.01 | 16.15 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 13.94 | 8.65 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 26.01 | 16.15 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 183.96 | 114.24 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 97.55 | 60.57 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 97.55 | 60.57 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 21.37 | 16.08 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 52.03 | 32.31 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 13.94 | 8.65 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 17.65 | 10.96 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 15.79 | 9.81 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 52.03 | 32.31 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 3.241 | 0.251 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 3.241 | 0.251 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 3.241 | 0.251 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.22 | 0.00 | 0.00 | 4.22 | 321.10 | 3.241 | 0.251 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 4.23 | 0.00 | 0.00 | 4.23 | 321.20 | 3.241 | 0.251 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.251 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.251 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 26.76 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 2.47 | 0.00 | 0.00 | 2.47 | 9.86 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 2.46 | 0.00 | 0.00 | 2.46 | 9.86 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 26.76 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 9.86 | 3.241 | 0.251 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 9.86 | 0.00 | 0.00 | 9.86 | 9.86 | 3.241 | 0.251 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.25 | 7.75 | 0.00 | 0.00 | 7.75 | 69.72 | 3.241 | 0.251 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 36.97 | 0.00 | 0.00 | 36.97 | 36.97 | 3.241 | 0.251 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 36.97 | 0.00 | 0.00 | 36.97 | 36.97 | 3.241 | 0.251 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 19.72 | 0.00 | 0.00 | 19.72 | 19.72 | 3.241 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.251 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 5.99 | 0.00 | 0.00 | 5.99 | 5.99 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.25 | 19.72 | 0.00 | 0.00 | 19.72 | 19.72 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1368.30 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 497.27 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 871.02 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 6.464 | 200.000 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.0679 | 1978.83 | 21901.44 | LightsWired | LTG_SCH_BASEMENT | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 241.03 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 16.1458 | 67.07 | 1082.92 | LightsWired | LTG_SCH_RETAIL | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 11.92 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 16.1458 | 77.67 | 1254.03 | LightsWired | LTG_SCH_RETAIL | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.80 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 16.1458 | 164.24 | 2651.85 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.18 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 8.6111 | 94.76 | 815.98 | LightsWired | LTG_SCH_STORAGE | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.98 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 15.0695 | 188.86 | 2846.05 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 31.32 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 13.9931 | 1308.19 | 18305.54 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 201.46 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 12.2708 | 156.09 | 1915.33 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 12.2708 | 156.07 | 1915.11 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 12.2708 | 1863.81 | 22870.56 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 297.14 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 12.2708 | 1864.32 | 22876.81 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 297.22 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 12.2708 | 156.09 | 1915.33 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 12.2708 | 156.07 | 1915.11 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 5.3819 | 1557.62 | 8383.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 92.26 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 12.2708 | 39.02 | 478.83 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.22 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 12.2708 | 39.02 | 478.78 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.22 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 12.2709 | 220.77 | 2709.10 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 35.20 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 15.0695 | 331.66 | 4997.90 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 55.00 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 15.0695 | 331.66 | 4997.90 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 55.00 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 12.9167 | 103.30 | 1334.35 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.68 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 5.3819 | 412.12 | 2218.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 24.41 |
Interior Lighting Total | 11.3147 | 11345.29 | 128367.98 | 764.46 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 20502.98 | AstronomicalClock | - | 83.77 | 83.77 | 322.39 | |
Exterior Lighting Total | 20502.98 | 322.39 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 595355.36 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19651.85 | 15734.36 | 3917.49 | 0.80 | 3.20 | |||
ROOM_2_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19513.74 | 15623.78 | 3889.96 | 0.80 | 3.20 | |||
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 127518.67 | 102072.28 | 25446.39 | 0.80 | 3.20 | |||
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 131729.49 | 105477.71 | 26251.78 | 0.80 | 3.20 | |||
ROOM_5_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 17114.70 | 13702.97 | 3411.72 | 0.80 | 3.20 | |||
ROOM_6_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16983.65 | 13598.05 | 3385.60 | 0.80 | 3.20 | |||
PTAC_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 36116.65 | 28841.81 | 7274.84 | 0.80 | 3.20 | |||
ROOM_1_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5568.55 | 4458.48 | 1110.06 | 0.80 | 3.20 | |||
ROOM_2_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5518.39 | 4418.33 | 1100.06 | 0.80 | 3.20 | |||
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 25614.64 | 20499.13 | 5115.51 | 0.80 | 3.20 | |||
PTAC_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 21365.08 | 17092.77 | 4272.31 | 0.80 | 3.20 | |||
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 174625.31 | 134816.25 | 39809.06 | 0.77 | 3.50 | |||
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 147965.47 | 110051.44 | 37914.03 | 0.74 | 3.50 | |||
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 62541.12 | 50051.66 | 12489.46 | 0.80 | 3.40 | |||
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | 73683.71 | 58995.60 | 14688.11 | 0.80 | 3.50 | |||
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 45150.18 | 33846.38 | 11303.80 | 0.75 | 3.40 | |||
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | 61493.60 | 47511.19 | 13982.41 | 0.77 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
ROOM_1_FLR_3 PTAC COOLING COIL | 18730.7 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_2_FLR_3 PTAC COOLING COIL | 18599.0 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 121933.3 | 2.68 | 9.16 | 9.72 | 9.19 | 9.20 | |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 125871.6 | 2.68 | 9.14 | 9.69 | 9.17 | 9.17 | |
ROOM_5_FLR_3 PTAC COOLING COIL | 16312.4 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_6_FLR_3 PTAC COOLING COIL | 16187.5 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
PTAC_3 PTAC COOLING COIL | 34635.1 | 2.71 | 9.26 | 9.82 | 9.29 | 9.35 | |
ROOM_1_FLR_6 PTAC COOLING COIL | 5307.5 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_2_FLR_6 PTAC COOLING COIL | 5259.7 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 24424.9 | 2.66 | 9.07 | 9.62 | 9.10 | 9.06 | |
PTAC_6 PTAC COOLING COIL | 20370.7 | 2.66 | 9.06 | 9.61 | 9.09 | 9.06 | |
VAV_FLR_1 COOLING COIL | 168241.7 | 3.00 | 10.22 | N/A | N/A | 11.04 | |
VAV_FLR_6 COOLING COIL | 142975.1 | 3.03 | 10.34 | N/A | N/A | 11.18 | |
VAV_FLR_0 COOLING COIL | 59583.0 | 10.16 | 10.16 | ||||
PSZ_LAUNDRY COOLING COIL | 70195.2 | 10.40 | 10.40 | ||||
PSZ_CAFE COOLING COIL | 43494.6 | 10.63 | 10.63 | ||||
PSZ_KITCHEN COOLING COIL | 59098.2 | 10.53 | 10.53 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
ROOM_1_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_2_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_5_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_6_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PTAC_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_1_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_2_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PTAC_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6334.78 | 6011.26 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2297.71 | 2180.91 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3035.53 | 2880.51 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3000.75 | 2847.50 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 45419.51 | 43111.97 | - |
ROOM_1_FLR_3 HEATING COIL | Coil:Heating:Water | 15776.38 | 16628.81 | - |
ROOM_2_FLR_3 HEATING COIL | Coil:Heating:Water | 15677.46 | 16522.02 | - |
ROOM_3_MULT19_FLR_3 HEATING COIL | Coil:Heating:Water | 108597.17 | 111431.11 | - |
ROOM_4_MULT19_FLR_3 HEATING COIL | Coil:Heating:Water | 112763.40 | 115963.49 | - |
ROOM_5_FLR_3 HEATING COIL | Coil:Heating:Water | 13962.88 | 14669.45 | - |
ROOM_6_FLR_3 HEATING COIL | Coil:Heating:Water | 13869.01 | 14568.04 | - |
PTAC_3 HEATING COIL | Coil:Heating:Water | 35826.68 | 34817.65 | - |
ROOM_1_FLR_6 HEATING COIL | Coil:Heating:Water | 4412.68 | 4663.14 | - |
ROOM_2_FLR_6 HEATING COIL | Coil:Heating:Water | 4376.78 | 4624.40 | - |
ROOM_3_MULT9_FLR_6 HEATING COIL | Coil:Heating:Water | 20919.02 | 21931.38 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 22885.08 | 21723.37 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 23053.41 | 21883.07 | - |
PTAC_6 HEATING COIL | Coil:Heating:Water | 18667.72 | 19269.37 | - |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | 49188.56 | 37039.96 | - |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | 38596.01 | 29063.56 | - |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | 67499.48 | 66525.27 | - |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | 51899.70 | 0.80 | |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | 43131.11 | 0.80 | |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | 46284.78 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.19 | 756.07 | 636.87 | 1.00 | 1.46 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.18 | 750.75 | 636.87 | 1.00 | 1.47 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 7.20 | 4583.03 | 636.87 | 1.00 | 1.21 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 7.55 | 4806.94 | 636.87 | 1.00 | 1.21 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.03 | 658.45 | 636.87 | 1.00 | 1.50 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.03 | 653.41 | 636.87 | 1.00 | 1.50 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 |
PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.91 | 1215.36 | 636.87 | 1.00 | 1.36 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.34 | 214.24 | 636.87 | 1.00 | 2.05 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 |
ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.33 | 212.31 | 636.87 | 1.00 | 2.06 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 |
ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.53 | 976.45 | 636.87 | 1.00 | 1.40 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 1.89 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.28 | 816.12 | 636.87 | 1.00 | 1.44 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
VAV_FLR_1 FAN | Fan:VariableVolume | 0.61 | 1337.13 | 8.64 | 18983.30 | 2197.78 | 1.00 | 1.12 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
VAV_FLR_6 FAN | Fan:VariableVolume | 0.61 | 1337.13 | 6.78 | 14895.33 | 2197.78 | 1.00 | 1.13 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 0.60 | 1337.13 | 3.77 | 8403.28 | 2226.32 | 1.00 | 1.15 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 |
PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 4.45 | 7220.45 | 1622.12 | 1.00 | 1.18 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 2.10 | 3497.28 | 1662.00 | 1.00 | 1.21 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 3.05 | 4943.55 | 1622.12 | 1.00 | 1.21 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.005208 | 1568.55 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 0.80 | 0.98 | 0.90 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 168241.67 | 3.00 | 10.22 | 11.04 | 8.6642 | 3.23 | 11.02 | 6.9002 | 3.21 | 10.96 | 4.6305 | 3.35 | 11.43 | 1.8841 |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 142975.05 | 3.03 | 10.34 | 11.18 | 6.7984 | 3.27 | 11.16 | 5.4010 | 3.26 | 11.11 | 3.6235 | 3.37 | 11.51 | 1.5123 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 38866.09 | 44696.00 | 22.59 | 3.282 | 3.775 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00912 | 30.62 | 0.00686 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5380.07 | 6187.09 | 92.25 | 0.454 | 0.523 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00891 | 38.10 | 0.00687 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 4007.24 | 4608.33 | 59.33 | 0.338 | 0.389 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00918 | 36.06 | 0.00687 | 0.092 | 0.00 |
MECH_FLR_1 | 4692.76 | 5396.68 | 32.86 | 0.396 | 0.456 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00859 | 36.63 | 0.00687 | 0.000 | 0.00 |
STORAGE_FLR_1 | 2506.12 | 2882.04 | 30.41 | 0.212 | 0.243 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 36.06 | 0.00687 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45835.64 | 52710.98 | 675.44 | 3.871 | 4.451 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 24.00 | 24.00 | 0.00854 | 35.98 | 0.00687 | 0.000 | 0.00 |
CAFE_FLR_1 | 21646.99 | 24894.04 | 131.81 | 1.830 | 2.104 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 23.99 | 0.00994 | 37.99 | 0.00687 | 0.676 | 0.00 |
LOBBY_FLR_1 | 72635.86 | 83531.24 | 63.85 | 6.136 | 7.057 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.99 | 0.00978 | 38.10 | 0.00687 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12226.72 | 14060.73 | 360.33 | 1.032 | 1.187 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00855 | 36.80 | 0.00687 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 12140.80 | 13961.92 | 357.84 | 1.025 | 1.179 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00855 | 36.63 | 0.00687 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 74117.14 | 85234.71 | 3475.59 | 6.258 | 7.196 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00847 | 38.10 | 0.00687 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 77732.11 | 89391.92 | 3644.11 | 6.563 | 7.548 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 21.11 | 21.11 | 0.00872 | 37.84 | 0.00687 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10648.19 | 12245.42 | 313.81 | 0.899 | 1.034 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00855 | 33.81 | 0.00686 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10566.66 | 12151.66 | 311.44 | 0.892 | 1.026 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 21.11 | 21.11 | 0.00855 | 33.48 | 0.00686 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 19650.70 | 22598.31 | 58.03 | 1.659 | 1.908 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00942 | 37.97 | 0.00687 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3464.56 | 3984.25 | 102.10 | 0.293 | 0.336 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 21.11 | 21.11 | 0.00854 | 37.15 | 0.00687 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3433.36 | 3948.37 | 101.19 | 0.290 | 0.333 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 21.11 | 21.11 | 0.00854 | 36.97 | 0.00687 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 15790.22 | 18158.75 | 740.25 | 1.333 | 1.533 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00861 | 38.10 | 0.00687 | 0.099 | 0.00 |
BANQUET_FLR_6 | 34088.97 | 39202.32 | 118.20 | 2.882 | 3.315 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01013 | 38.10 | 0.00687 | 1.188 | 0.00 |
DINING_FLR_6 | 35612.09 | 40953.90 | 123.48 | 3.011 | 3.463 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01006 | 38.10 | 0.00687 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31296.63 | 35991.12 | 348.40 | 2.650 | 3.048 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01002 | 36.93 | 0.00687 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 13195.72 | 15175.08 | 36.82 | 1.114 | 1.281 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00886 | 38.10 | 0.00687 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.91 | 0.00281 | -5.20 | 0.00281 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2930.02 | 3662.53 | 54.61 | 0.248 | 0.310 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00779 | -5.20 | 0.00281 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 857.04 | 1071.30 | 13.79 | 0.072 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00772 | -5.20 | 0.00281 | 0.092 | 0.00 |
MECH_FLR_1 | 1404.17 | 1755.21 | 10.69 | 0.119 | 0.148 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00761 | -5.20 | 0.00281 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1387.91 | 1734.89 | 18.31 | 0.117 | 0.147 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00776 | -5.20 | 0.00281 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1935.53 | 2419.41 | 31.00 | 0.164 | 0.204 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00761 | -5.20 | 0.00281 | 0.000 | 0.00 |
CAFE_FLR_1 | 7665.17 | 9581.47 | 50.73 | 0.648 | 0.810 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00782 | -5.20 | 0.00281 | 0.676 | 0.00 |
LOBBY_FLR_1 | 16059.36 | 20074.20 | 15.35 | 1.357 | 1.894 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00775 | -5.20 | 0.00281 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5581.00 | 6976.25 | 178.78 | 0.472 | 0.590 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00774 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5572.99 | 6966.24 | 178.54 | 0.471 | 0.589 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00774 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 32157.16 | 40196.45 | 1639.08 | 2.718 | 3.397 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00776 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 32024.09 | 40030.11 | 1631.85 | 2.707 | 3.383 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00776 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5565.48 | 6956.85 | 178.28 | 0.470 | 0.588 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00774 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5557.47 | 6946.84 | 178.04 | 0.470 | 0.587 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00774 | -5.20 | 0.00281 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9324.14 | 11655.17 | 29.93 | 0.788 | 0.985 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00781 | -5.20 | 0.00281 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1869.42 | 2336.77 | 59.88 | 0.158 | 0.197 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00780 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1868.45 | 2335.56 | 59.86 | 0.158 | 0.197 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00780 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9161.33 | 11451.66 | 466.83 | 0.774 | 0.968 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00782 | -5.20 | 0.00281 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7385.17 | 9231.46 | 27.83 | 0.624 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -5.20 | 0.00281 | 1.188 | 0.00 |
DINING_FLR_6 | 7510.37 | 9387.96 | 28.31 | 0.635 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00788 | -5.20 | 0.00281 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2541.75 | 3177.19 | 30.76 | 0.215 | 0.367 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00748 | -5.20 | 0.00281 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 8089.54 | 10111.93 | 24.54 | 0.684 | 0.855 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00790 | -5.20 | 0.00281 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_FLR_1 | 8.64 | 8.64 | 2.59 | 2.59 | 8.6375 | 3.4608 | 8.6375 | 0.4007 | 0.3000 |
VAV_FLR_6 | 6.78 | 6.78 | 2.38 | 2.38 | 6.7774 | 3.1636 | 6.7774 | 0.4668 | 0.3000 |
VAV_FLR_0 | 3.77 | 3.77 | 0.85 | 0.85 | 3.7745 | 1.1324 | 3.7745 | 0.3000 | 1.0000 |
PSZ_LAUNDRY | 4.45 | 4.45 | 0.20 | 0.20 | 4.4512 | 4.4512 | 4.4512 | 1.0000 | 1.0000 |
PSZ_CAFE | 2.10 | 2.10 | 0.81 | 0.81 | 2.1043 | 2.1043 | 2.1043 | 1.0000 | 1.0000 |
PSZ_KITCHEN | 3.05 | 3.05 | 0.37 | 0.37 | 3.0476 | 3.0476 | 3.0476 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 6334.777 | 6334.777 | 0.309516 | 0.00005542 | 147.753 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6334.78 | 6334.78 | 0.309516 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00778541 | 43.6660 | 3662.53 | 0.00 | 6015.49 | 6015.49 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2297.713 | 2297.713 | 0.142061 | 0.00002010 | 50.688 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2297.71 | 2297.71 | 0.142061 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00772050 | 43.3054 | 1071.30 | 0.00 | 2182.25 | 2182.25 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3035.529 | 3035.529 | 0.148336 | 0.00002656 | 70.798 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3035.53 | 3035.53 | 0.148336 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00760617 | 42.6720 | 1755.21 | 0.00 | 2882.53 | 2882.53 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 3000.746 | 3000.746 | 0.146619 | 0.00002625 | 69.989 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3000.75 | 3000.75 | 0.146619 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00776265 | 43.5390 | 1734.89 | 0.00 | 2849.50 | 2849.50 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 45419.505 | 45419.505 | 2.935681 | 0.00039735 | 993.207 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 45419.51 | 45419.51 | 2.935681 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00775426 | 43.4924 | 20074.20 | 0.00 | 43137.75 | 43137.75 |
ROOM_1_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | 15776.378 | 15776.378 | 1.187168 | 0.00013802 | 393.041 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15776.38 | 15776.38 | 1.187168 | 19.74 | 12.54 | 0.00748431 | 32.22 | 17.22 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.2002 | 21.11 | 0.00774080 | 43.1241 | 6976.25 | 0.00 | 16636.50 | 16636.50 |
ROOM_1_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | 19651.850 | 15734.357 | 1.187168 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 15940.63 | 15940.63 | 1.187168 | 21.93 | 14.18 | 0.00846083 | 9.40 | 9.40 | 0.00846083 | 36.80 | 0.00686940 | 17.78 | 5.2002 | 21.11 | 0.00854812 | 47.5595 | 14060.73 | 0.00 | 19661.47 | 14636.27 |
ROOM_2_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | 15677.461 | 15677.461 | 1.178825 | 0.00013715 | 390.539 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15677.46 | 15677.46 | 1.178825 | 19.73 | 12.53 | 0.00748221 | 32.22 | 17.22 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.2364 | 21.11 | 0.00774047 | 43.1222 | 6966.24 | 0.00 | 16529.65 | 16529.65 |
ROOM_2_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | 19513.744 | 15623.782 | 1.178825 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 15864.30 | 15864.30 | 1.178825 | 21.92 | 14.18 | 0.00846051 | 9.40 | 9.40 | 0.00846051 | 36.63 | 0.00686912 | 17.72 | 5.2364 | 21.11 | 0.00854845 | 47.5613 | 13961.92 | 0.00 | 19523.30 | 14533.41 |
ROOM_3_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | 108597.166 | 108597.166 | 7.196229 | 0.00095006 | 2660.363 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 108597.17 | 108597.17 | 7.196229 | 18.05 | 11.62 | 0.00718453 | 32.22 | 17.22 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 11.6321 | 21.11 | 0.00776057 | 43.2319 | 40196.45 | 0.00 | 111476.68 | 111476.68 |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | 127518.670 | 102072.279 | 7.196229 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 102586.65 | 102586.65 | 7.196229 | 23.09 | 14.44 | 0.00828517 | 9.40 | 9.22 | 0.00828517 | 38.10 | 0.00687148 | 18.17 | 11.6321 | 21.11 | 0.00847126 | 47.1364 | 85234.71 | 0.00 | 127581.09 | 94979.95 |
ROOM_4_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | 112763.404 | 112763.404 | 7.547812 | 0.00098650 | 2766.235 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 112763.40 | 112763.40 | 7.547812 | 18.19 | 11.70 | 0.00721032 | 32.22 | 17.22 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 11.0933 | 21.11 | 0.00775956 | 43.2263 | 40030.11 | 0.00 | 116011.52 | 116011.52 |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | 131729.489 | 105477.712 | 7.547812 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | unknown | 7/21 15:20:00 | 106909.93 | 106690.95 | 7.547812 | 22.97 | 14.59 | 0.00851112 | 9.40 | 9.40 | 0.00850000 | 37.84 | 0.00687107 | 18.09 | 11.0933 | 21.11 | 0.00871576 | 48.4807 | 89391.92 | 0.00 | 131793.97 | 98120.41 |
ROOM_5_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | 13962.883 | 13962.883 | 1.033899 | 0.00012215 | 347.145 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13962.88 | 13962.88 | 1.033899 | 19.54 | 12.42 | 0.00744564 | 32.22 | 17.22 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 5.9711 | 21.11 | 0.00774012 | 43.1203 | 6956.85 | 0.00 | 14676.14 | 14676.14 |
ROOM_5_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | 17114.697 | 13702.972 | 1.033899 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 14422.87 | 14422.87 | 1.033899 | 21.87 | 14.16 | 0.00845354 | 9.40 | 9.39 | 0.00845354 | 33.81 | 0.00686464 | 16.84 | 5.9711 | 21.11 | 0.00855444 | 47.5942 | 12245.42 | 0.00 | 17123.07 | 12746.65 |
ROOM_6_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | 13869.013 | 13869.013 | 1.025982 | 0.00012133 | 344.770 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13869.01 | 13869.01 | 1.025982 | 19.53 | 12.42 | 0.00744308 | 32.22 | 17.22 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.0165 | 21.11 | 0.00773978 | 43.1184 | 6946.84 | 0.00 | 14574.68 | 14574.68 |
ROOM_6_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | 16983.652 | 13598.051 | 1.025982 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | 7/21 10:10:00 | 14369.66 | 14369.66 | 1.025982 | 21.86 | 14.15 | 0.00845308 | 9.40 | 9.39 | 0.00845308 | 33.48 | 0.00686412 | 16.74 | 6.0165 | 21.11 | 0.00855480 | 47.5962 | 12151.66 | 0.00 | 16991.97 | 12649.05 |
PTAC_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | 35826.681 | 35826.681 | 1.908342 | 0.00031343 | 847.893 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 35826.68 | 35826.68 | 1.908342 | 14.48 | 9.59 | 0.00656549 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 24.8783 | 21.00 | 0.00780974 | 43.7995 | 11655.17 | 0.00 | 34826.27 | 34826.27 |
PTAC_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | 36116.652 | 28841.810 | 1.908342 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | 7/21 15:10:00 | 31155.66 | 29954.79 | 1.908342 | 27.47 | 16.32 | 0.00878877 | 12.29 | 10.62 | 0.00850000 | 37.97 | 0.00687126 | 18.13 | 24.8783 | 24.00 | 0.00942379 | 43.9345 | 22598.31 | 0.00 | 36134.33 | 26837.34 |
ROOM_1_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | 4412.681 | 4412.681 | 0.336396 | 0.00003860 | 110.113 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4412.68 | 4412.68 | 0.336396 | 19.90 | 12.68 | 0.00757483 | 32.22 | 17.22 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 4.5880 | 21.11 | 0.00780402 | 43.4718 | 2336.77 | 0.00 | 4665.38 | 4665.38 |
ROOM_1_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | 5568.545 | 4458.485 | 0.336396 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | unknown | 7/21 16:10:00 | 4492.31 | 4492.31 | 0.336396 | 21.85 | 14.16 | 0.00846585 | 9.40 | 9.40 | 0.00846585 | 37.15 | 0.00686994 | 17.88 | 4.5880 | 21.11 | 0.00854259 | 47.5291 | 3984.25 | 0.00 | 5571.27 | 4147.33 |
ROOM_2_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | 4376.784 | 4376.784 | 0.333366 | 0.00003829 | 109.205 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4376.78 | 4376.78 | 0.333366 | 19.89 | 12.67 | 0.00757269 | 32.22 | 17.22 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 4.6291 | 21.11 | 0.00780394 | 43.4714 | 2335.56 | 0.00 | 4626.62 | 4626.62 |
ROOM_2_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | 5518.395 | 4418.332 | 0.333366 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | unknown | 7/21 16:20:00 | 4462.05 | 4462.05 | 0.333366 | 21.85 | 14.16 | 0.00846549 | 9.40 | 9.40 | 0.00846549 | 36.97 | 0.00686968 | 17.83 | 4.6291 | 21.11 | 0.00854295 | 47.5311 | 3948.37 | 0.00 | 5521.10 | 4109.98 |
ROOM_3_MULT9_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | 20919.016 | 20919.016 | 1.533215 | 0.00018301 | 519.391 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 20919.02 | 20919.02 | 1.533215 | 19.41 | 12.42 | 0.00749163 | 32.22 | 17.22 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 6.4671 | 21.11 | 0.00781544 | 43.5343 | 11451.66 | 0.00 | 21941.64 | 21941.64 |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | 25614.641 | 20499.133 | 1.533215 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 20514.85 | 20514.85 | 1.533215 | 22.21 | 14.31 | 0.00849964 | 9.40 | 9.40 | 0.00849964 | 38.10 | 0.00687148 | 18.17 | 6.4671 | 21.11 | 0.00861221 | 47.9122 | 18158.75 | 0.00 | 25627.18 | 19071.17 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 22885.079 | 22885.079 | 1.581109 | 0.00020021 | 494.323 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 22885.08 | 22885.08 | 1.581109 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00787709 | 44.1728 | 9231.46 | 0.00 | 21735.92 | 21735.92 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 23053.414 | 23053.414 | 1.582474 | 0.00020168 | 498.532 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 23053.41 | 23053.41 | 1.582474 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00787909 | 44.1839 | 9387.96 | 0.00 | 21895.75 | 21895.75 |
PTAC_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | 18667.716 | 18667.716 | 1.281459 | 0.00016331 | 458.259 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 18667.72 | 18667.72 | 1.281459 | 18.43 | 11.97 | 0.00740199 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 9.8025 | 21.00 | 0.00790122 | 44.3062 | 10111.93 | 0.00 | 19278.17 | 19278.17 |
PTAC_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | 21365.078 | 17092.769 | 1.281459 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 17879.98 | 17434.34 | 1.281459 | 25.38 | 15.53 | 0.00866297 | 12.29 | 10.62 | 0.00850000 | 38.10 | 0.00687148 | 18.17 | 9.8025 | 24.00 | 0.00885766 | 41.3318 | 15175.08 | 0.00 | 21375.54 | 15902.74 |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_FLR_1 | 174625.308 | 134816.252 | 8.637485 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 162387.08 | 158010.22 | 8.637485 | 28.62 | 16.62 | 0.00871200 | 10.83 | 10.03 | 0.00850000 | 38.10 | 0.00687148 | 18.17 | 32.7676 | 23.99 | 0.00960904 | 44.7956 | 88910.54 | 0.00 | 175130.36 | 126100.23 |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_1 | 49188.562 | 49188.562 | 2.591245 | 0.00043032 | 801.611 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 49188.56 | 49188.56 | 2.591245 | -5.20 | -5.20 | 0.00280840 | 12.89 | 10.37 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 109.2255 | 21.00 | 0.00774834 | 43.4598 | 22638.50 | 0.00 | 44799.14 | 44799.14 |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_FLR_6 | 147965.470 | 110051.436 | 6.777439 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 138082.21 | 136665.52 | 6.777439 | 30.58 | 17.15 | 0.00858735 | 10.83 | 10.02 | 0.00850000 | 38.10 | 0.00687148 | 18.17 | 46.7359 | 23.98 | 0.01009293 | 47.0438 | 69698.24 | 0.00 | 148393.42 | 103378.54 |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_6 | 38596.013 | 38596.013 | 2.033232 | 0.00033765 | 628.987 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 38596.01 | 38596.01 | 2.033232 | -5.20 | -5.20 | 0.00280840 | 12.89 | 10.37 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 155.7865 | 21.00 | 0.00787802 | 44.1781 | 14893.43 | 0.00 | 35151.83 | 35151.83 |
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | VAV_FLR_0 | 62541.120 | 50051.658 | 3.774510 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 31270.56 | 30766.95 | 2.516340 | 25.50 | 15.52 | 0.00860512 | 10.80 | 10.01 | 0.00850000 | 30.62 | 0.00685962 | 15.81 | 33.9564 | 24.00 | 0.00911634 | 42.5226 | 38838.28 | 0.00 | -999.00 | -999.00 |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_0 | 67499.479 | 67499.479 | 3.774510 | 0.00032102 | 2423.663 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 67499.48 | 67499.48 | 3.774510 | 15.07 | 10.09 | 0.00682474 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 22.6376 | 22.97 | 0.00280840 | 14.0827 | 0.00 | 0.00 | 66546.53 | 66546.53 |
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_LAUNDRY | 73683.710 | 58995.599 | 4.451230 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 36841.86 | 36614.13 | 2.967487 | 24.00 | 14.96 | 0.00853625 | 11.37 | 10.24 | 0.00850000 | 35.98 | 0.00686808 | 17.52 | 0.0000 | 24.00 | 0.00853625 | 39.8526 | 45835.64 | 0.00 | -999.00 | -999.00 |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_LAUNDRY | 51899.705 | 51899.705 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 51899.70 | 51899.70 | 4.451233 | 21.00 | 13.11 | 0.00760964 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00760964 | 42.6922 | 1935.53 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_CAFE | 45150.180 | 33846.381 | 2.104260 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 22575.09 | 21303.82 | 1.402840 | 28.49 | 16.77 | 0.00895371 | 11.33 | 10.23 | 0.00850000 | 37.99 | 0.00687130 | 18.14 | 48.2157 | 23.99 | 0.00994152 | 46.3403 | 21638.46 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_CAFE | 43131.106 | 43131.106 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 43131.11 | 43131.11 | 2.104263 | 12.58 | 8.42 | 0.00620739 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 32.1438 | 21.00 | 0.00781751 | 43.8435 | 7665.17 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_KITCHEN | 61493.600 | 47511.185 | 3.047580 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 30746.80 | 26111.17 | 2.031720 | 25.51 | 16.35 | 0.00964110 | 11.37 | 10.25 | 0.00850000 | 36.93 | 0.00686961 | 17.82 | 18.0808 | 23.97 | 0.01002096 | 46.7566 | 31296.63 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_KITCHEN | 46284.784 | 46284.784 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 46284.78 | 46284.78 | 3.047577 | 17.64 | 11.20 | 0.00691289 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 12.0538 | 21.00 | 0.00745919 | 41.8592 | 1652.13 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6334.777 | 6334.777 | 0.309516 | 0.00005542 | 147.753 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 1.0430 | 1.064033 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6334.78 | 6334.78 | 1.0000 | 0.32323725 | 0.309516 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05541374 | 60.00 | 32.22 | 27.78 | 0.000 | 6334.78 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00778541 | 21.00 | 0.00778541 | 43.6660 | 3662.53 | 0.00 | 6015.49 | 6015.49 | 0.32323725 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55544.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2297.713 | 2297.713 | 0.142061 | 0.00002010 | 50.688 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 0.3783 | 0.385940 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2297.71 | 2297.71 | 1.0000 | 0.14835882 | 0.142061 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.02009935 | 60.00 | 32.22 | 27.78 | 0.000 | 2297.71 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00772050 | 21.00 | 0.00772050 | 43.3054 | 1071.30 | 0.00 | 2182.25 | 2182.25 | 0.14835882 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.02 | 18.38 | 0.00800000 | 51644.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3035.529 | 3035.529 | 0.148336 | 0.00002656 | 70.798 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 0.4998 | 0.509868 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3035.53 | 3035.53 | 1.0000 | 0.15491196 | 0.148336 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.02655342 | 60.00 | 32.22 | 27.78 | 0.000 | 3035.53 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00760617 | 21.00 | 0.00760617 | 42.6720 | 1755.21 | 0.00 | 2882.53 | 2882.53 | 0.15491196 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55542.3 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3000.746 | 3000.746 | 0.146619 | 0.00002625 | 69.989 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 0.4941 | 0.504026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3000.75 | 3000.75 | 1.0000 | 0.15311849 | 0.146619 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.02624916 | 60.00 | 32.22 | 27.78 | 0.000 | 3000.75 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00776265 | 21.00 | 0.00776265 | 43.5390 | 1734.89 | 0.00 | 2849.50 | 2849.50 | 0.15311849 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55544.5 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 45419.505 | 45419.505 | 2.935681 | 0.00039735 | 993.207 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 7.4785 | 7.628974 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 45419.51 | 45419.51 | 1.0000 | 3.06582457 | 2.935681 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.39730911 | 60.00 | 32.22 | 27.78 | 0.000 | 45419.51 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00775426 | 21.00 | 0.00775426 | 43.4924 | 20074.20 | 0.00 | 43137.75 | 43137.75 | 3.06582457 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.40 | 18.17 | 0.00800000 | 51005.3 | |
ROOM_1_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15776.378 | 15776.378 | 1.187168 | 0.00013802 | 393.041 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.187168 | 1.23979747 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 2.5976 | 2.649909 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15776.38 | 15776.38 | 1.0000 | 1.23979747 | 1.187168 | 19.74 | 12.54 | 0.00748431 | 38830.1 | 32.22 | 17.22 | 0.00800000 | 52863.7 | 0.13800456 | 60.00 | 32.22 | 27.78 | 0.000 | 15776.38 | -5.20 | 0.00280840 | -5.20 | 0.06173502 | 5.2002 | 21.11 | 0.00774080 | 21.11 | 0.00774080 | 43.1241 | 6976.25 | 0.00 | 16636.50 | 16636.50 | 1.23979747 | 16.60 | 12.65 | 0.00748431 | 35629.1 | 29.77 | 17.54 | 0.00748431 | 49047.8 | |
ROOM_1_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 19651.850 | 15734.357 | 1.187168 | -999.0 | -999.000 | -999.0000 | 1.02521 | 1.00000 | 1020.5683 | 1004.8586 | 1.0443 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.187168 | 1.23979747 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 15940.63 | 15940.63 | 0.8112 | 1.23979747 | 1.187168 | 21.93 | 14.18 | 0.00846083 | 43537.6 | 9.40 | 9.40 | 0.00846083 | 30754.7 | -999.0 | -999.00 | -999.00 | -999.00 | 756.066 | 15184.56 | 36.80 | 0.00686940 | 17.78 | 0.06173502 | 5.2002 | 21.11 | 0.00854812 | 21.11 | 0.00854812 | 47.5595 | 14060.73 | 0.00 | 19661.47 | 14636.27 | 1.19083484 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953013 | 38811.7 | |
ROOM_2_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15677.461 | 15677.461 | 1.178825 | 0.00013715 | 390.539 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.178825 | 1.23108463 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 2.5813 | 2.633295 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15677.46 | 15677.46 | 1.0000 | 1.23108463 | 1.178825 | 19.73 | 12.53 | 0.00748221 | 38815.1 | 32.22 | 17.22 | 0.00800000 | 52863.7 | 0.13713927 | 60.00 | 32.22 | 27.78 | 0.000 | 15677.46 | -5.20 | 0.00280840 | -5.20 | 0.06172779 | 5.2364 | 21.11 | 0.00774047 | 21.11 | 0.00774047 | 43.1222 | 6966.24 | 0.00 | 16529.65 | 16529.65 | 1.23108463 | 16.60 | 12.64 | 0.00748221 | 35623.8 | 29.78 | 17.54 | 0.00748221 | 49050.7 | |
ROOM_2_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 19513.744 | 15623.782 | 1.178825 | -999.0 | -999.000 | -999.0000 | 1.02779 | 1.00000 | 1020.5677 | 1004.8586 | 1.0443 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.178825 | 1.23108463 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 15864.30 | 15864.30 | 0.8130 | 1.23108463 | 1.178825 | 21.92 | 14.18 | 0.00846051 | 43533.3 | 9.40 | 9.40 | 0.00846051 | 30754.0 | -999.0 | -999.00 | -999.00 | -999.00 | 750.753 | 15113.55 | 36.63 | 0.00686912 | 17.72 | 0.06172779 | 5.2364 | 21.11 | 0.00854845 | 21.11 | 0.00854845 | 47.5613 | 13961.92 | 0.00 | 19523.30 | 14533.41 | 1.18246609 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953013 | 38811.7 | |
ROOM_3_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 108597.166 | 108597.166 | 7.196229 | 0.00095006 | 2660.363 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 7.196229 | 7.51524977 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 17.8809 | 18.240730 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 108597.17 | 108597.17 | 1.0000 | 7.51524977 | 7.196229 | 18.05 | 11.62 | 0.00718453 | 36346.7 | 32.22 | 17.22 | 0.00800000 | 52863.7 | 0.94995847 | 60.00 | 32.22 | 27.78 | 0.000 | 108597.17 | -5.20 | 0.00280840 | -5.20 | 0.83707151 | 11.6321 | 21.11 | 0.00776057 | 21.11 | 0.00776057 | 43.2319 | 40196.45 | 0.00 | 111476.68 | 111476.68 | 7.51524977 | 16.60 | 12.35 | 0.00718453 | 34870.1 | 31.17 | 17.76 | 0.00718453 | 49703.5 | |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 127518.670 | 102072.279 | 7.196229 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2417 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 7.196229 | 7.51524977 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 102586.65 | 102586.65 | 0.8045 | 7.51524977 | 7.196229 | 23.09 | 14.44 | 0.00828517 | 44275.3 | 9.40 | 9.22 | 0.00828517 | 30312.2 | -999.0 | -999.00 | -999.00 | -999.00 | 4583.029 | 98003.62 | 38.10 | 0.00687148 | 18.17 | 0.83707151 | 11.6321 | 21.11 | 0.00847126 | 21.11 | 0.00847126 | 47.1364 | 85234.71 | 0.00 | 127581.09 | 94979.95 | 7.21845422 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.80 | 13.40 | 0.00941390 | 37648.1 | |
ROOM_4_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 112763.404 | 112763.404 | 7.547812 | 0.00098650 | 2766.235 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 7.547812 | 7.88241941 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 18.5669 | 18.940520 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 112763.40 | 112763.40 | 1.0000 | 7.88241941 | 7.547812 | 18.19 | 11.70 | 0.00721032 | 36556.4 | 32.22 | 17.22 | 0.00800000 | 52863.7 | 0.98640282 | 60.00 | 32.22 | 27.78 | 0.000 | 112763.40 | -5.20 | 0.00280840 | -5.20 | 0.83730041 | 11.0933 | 21.11 | 0.00775956 | 21.11 | 0.00775956 | 43.2263 | 40030.11 | 0.00 | 116011.52 | 116011.52 | 7.88241941 | 16.60 | 12.38 | 0.00721032 | 34935.4 | 31.05 | 17.75 | 0.00721032 | 49653.2 | |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 131729.489 | 105477.712 | 7.547812 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6617 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 7.547812 | 7.88241941 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | unknown | unknown | unknown | 7/21 15:20:00 | Sensible | 106909.93 | 106690.95 | 0.8116 | 7.88241941 | 7.547812 | 22.97 | 14.59 | 0.00851112 | 44726.4 | 9.40 | 9.40 | 0.00850000 | 30853.5 | -999.0 | -999.00 | -999.00 | -999.00 | 4806.940 | 102102.99 | 37.84 | 0.00687107 | 18.09 | 0.83730041 | 11.0933 | 21.11 | 0.00871576 | 21.11 | 0.00871576 | 48.4807 | 89391.92 | 0.00 | 131793.97 | 98120.41 | 7.57112343 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.50 | 0.00944084 | 37914.9 | |
ROOM_5_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13962.883 | 13962.883 | 1.033899 | 0.00012215 | 347.145 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.033899 | 1.07973338 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 2.2990 | 2.345302 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 13962.88 | 13962.88 | 1.0000 | 1.07973338 | 1.033899 | 19.54 | 12.42 | 0.00744564 | 38525.4 | 32.22 | 17.22 | 0.00800000 | 52863.7 | 0.12214093 | 60.00 | 32.22 | 27.78 | 0.000 | 13962.88 | -5.20 | 0.00280840 | -5.20 | 0.06173502 | 5.9711 | 21.11 | 0.00774012 | 21.11 | 0.00774012 | 43.1203 | 6956.85 | 0.00 | 14676.14 | 14676.14 | 1.07973338 | 16.60 | 12.61 | 0.00744564 | 35531.2 | 29.94 | 17.56 | 0.00744564 | 49123.6 | |
ROOM_5_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 17114.697 | 13702.972 | 1.033899 | -999.0 | -999.000 | -999.0000 | 1.06983 | 1.00000 | 1020.5547 | 1004.8586 | 1.0443 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.033899 | 1.07973338 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 14422.87 | 14422.87 | 0.8427 | 1.07973338 | 1.033899 | 21.87 | 14.16 | 0.00845354 | 43460.3 | 9.40 | 9.39 | 0.00845354 | 30736.4 | -999.0 | -999.00 | -999.00 | -999.00 | 658.454 | 13764.42 | 33.81 | 0.00686464 | 16.84 | 0.06173502 | 5.9711 | 21.11 | 0.00855444 | 21.11 | 0.00855444 | 47.5942 | 12245.42 | 0.00 | 17123.07 | 12746.65 | 1.03709208 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953013 | 38811.7 | |
ROOM_6_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13869.013 | 13869.013 | 1.025982 | 0.00012133 | 344.770 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.025982 | 1.07146602 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 2.2836 | 2.329535 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 13869.01 | 13869.01 | 1.0000 | 1.07146602 | 1.025982 | 19.53 | 12.42 | 0.00744308 | 38506.8 | 32.22 | 17.22 | 0.00800000 | 52863.7 | 0.12131980 | 60.00 | 32.22 | 27.78 | 0.000 | 13869.01 | -5.20 | 0.00280840 | -5.20 | 0.06172779 | 6.0165 | 21.11 | 0.00773978 | 21.11 | 0.00773978 | 43.1184 | 6946.84 | 0.00 | 14574.68 | 14574.68 | 1.07146602 | 16.60 | 12.61 | 0.00744308 | 35524.7 | 29.95 | 17.57 | 0.00744308 | 49127.3 | |
ROOM_6_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 16983.652 | 13598.051 | 1.025982 | -999.0 | -999.000 | -999.0000 | 1.07525 | 1.00000 | 1020.5539 | 1004.8586 | 1.0443 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.025982 | 1.07146602 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | unknown | unknown | 7/21 10:10:00 | Sensible | 14369.66 | 14369.66 | 0.8461 | 1.07146602 | 1.025982 | 21.86 | 14.15 | 0.00845308 | 43445.0 | 9.40 | 9.39 | 0.00845308 | 30735.2 | -999.0 | -999.00 | -999.00 | -999.00 | 653.413 | 13716.25 | 33.48 | 0.00686412 | 16.74 | 0.06172779 | 6.0165 | 21.11 | 0.00855480 | 21.11 | 0.00855480 | 47.5962 | 12151.66 | 0.00 | 16991.97 | 12649.05 | 1.02915121 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953013 | 38811.7 | |
PTAC_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35826.681 | 35826.681 | 1.908342 | 0.00031343 | 847.893 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.908342 | 1.99294159 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 5.8990 | 6.017697 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 35826.68 | 35826.68 | 1.0000 | 1.99294159 | 1.908342 | 14.48 | 9.59 | 0.00656549 | 31148.6 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.31339547 | 60.00 | 32.22 | 27.78 | 0.000 | 35826.68 | -5.20 | 0.00280840 | -5.20 | 0.47476218 | 24.8783 | 21.00 | 0.00780974 | 21.00 | 0.00780974 | 43.7995 | 11655.17 | 0.00 | 34826.27 | 34826.27 | 1.99294159 | 16.60 | 11.73 | 0.00656549 | 33302.8 | 33.78 | 18.13 | 0.00656549 | 50777.7 | |
PTAC_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 36116.652 | 28841.810 | 1.908342 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1779 | 1004.8586 | 1.0443 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.908342 | 1.99294159 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | unknown | unknown | 7/21 15:10:00 | Sensible | 31155.66 | 29954.79 | 0.8626 | 1.99294159 | 1.908342 | 27.47 | 16.32 | 0.00878877 | 50036.6 | 12.29 | 10.62 | 0.00850000 | 33803.4 | -999.0 | -999.00 | -999.00 | -999.00 | 1215.357 | 29940.31 | 37.97 | 0.00687126 | 18.13 | 0.47476218 | 24.8783 | 24.00 | 0.00942379 | 24.00 | 0.00942379 | 43.9345 | 22598.31 | 0.00 | 36134.33 | 26837.34 | 1.91423546 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.95 | 12.93 | 0.00928043 | 36445.7 | |
ROOM_1_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4412.681 | 4412.681 | 0.336396 | 0.00003860 | 110.113 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.336396 | 0.35130881 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 0.7266 | 0.741184 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4412.68 | 4412.68 | 1.0000 | 0.35130881 | 0.336396 | 19.90 | 12.68 | 0.00757483 | 39224.0 | 32.22 | 17.22 | 0.00800000 | 52863.7 | 0.03860012 | 60.00 | 32.22 | 27.78 | 0.000 | 4412.68 | -5.20 | 0.00280840 | -5.20 | 0.01543376 | 4.5880 | 21.11 | 0.00780402 | 21.11 | 0.00780402 | 43.4718 | 2336.77 | 0.00 | 4665.38 | 4665.38 | 0.35130881 | 16.60 | 12.74 | 0.00757483 | 35858.3 | 29.63 | 17.57 | 0.00757483 | 49138.3 | |
ROOM_1_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 5568.545 | 4458.485 | 0.336396 | -999.0 | -999.000 | -999.0000 | 1.02592 | 1.00000 | 1020.5776 | 1004.8586 | 1.0443 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.336396 | 0.35130881 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | unknown | unknown | unknown | 7/21 16:10:00 | Sensible | 4492.31 | 4492.31 | 0.8067 | 0.35130881 | 0.336396 | 21.85 | 14.16 | 0.00846585 | 43468.6 | 9.40 | 9.40 | 0.00846585 | 30767.4 | -999.0 | -999.00 | -999.00 | -999.00 | 214.239 | 4278.07 | 37.15 | 0.00686994 | 17.88 | 0.01543376 | 4.5880 | 21.11 | 0.00854259 | 21.11 | 0.00854259 | 47.5291 | 3984.25 | 0.00 | 5571.27 | 4147.33 | 0.33743477 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953013 | 38811.7 | |
ROOM_2_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4376.784 | 4376.784 | 0.333366 | 0.00003829 | 109.205 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.333366 | 0.34814491 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 0.7207 | 0.735155 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4376.78 | 4376.78 | 1.0000 | 0.34814491 | 0.333366 | 19.89 | 12.67 | 0.00757269 | 39207.5 | 32.22 | 17.22 | 0.00800000 | 52863.7 | 0.03828611 | 60.00 | 32.22 | 27.78 | 0.000 | 4376.78 | -5.20 | 0.00280840 | -5.20 | 0.01543195 | 4.6291 | 21.11 | 0.00780394 | 21.11 | 0.00780394 | 43.4714 | 2335.56 | 0.00 | 4626.62 | 4626.62 | 0.34814491 | 16.60 | 12.73 | 0.00757269 | 35852.9 | 29.64 | 17.57 | 0.00757269 | 49142.2 | |
ROOM_2_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 5518.395 | 4418.332 | 0.333366 | -999.0 | -999.000 | -999.0000 | 1.02838 | 1.00000 | 1020.5769 | 1004.8586 | 1.0443 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.333366 | 0.34814491 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | unknown | unknown | unknown | 7/21 16:20:00 | Sensible | 4462.05 | 4462.05 | 0.8086 | 0.34814491 | 0.333366 | 21.85 | 14.16 | 0.00846549 | 43466.2 | 9.40 | 9.40 | 0.00846549 | 30766.5 | -999.0 | -999.00 | -999.00 | -999.00 | 212.309 | 4249.74 | 36.97 | 0.00686968 | 17.83 | 0.01543195 | 4.6291 | 21.11 | 0.00854295 | 21.11 | 0.00854295 | 47.5311 | 3948.37 | 0.00 | 5521.10 | 4109.98 | 0.33439582 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 13.84 | 0.00953013 | 38811.7 | |
ROOM_3_MULT9_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20919.016 | 20919.016 | 1.533215 | 0.00018301 | 519.391 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.533215 | 1.60118555 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 3.4444 | 3.513702 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 20919.02 | 20919.02 | 1.0000 | 1.60118555 | 1.533215 | 19.41 | 12.42 | 0.00749163 | 38509.3 | 32.22 | 17.22 | 0.00800000 | 52863.7 | 0.18299001 | 60.00 | 32.22 | 27.78 | 0.000 | 20919.02 | -5.20 | 0.00280840 | -5.20 | 0.09915400 | 6.4671 | 21.11 | 0.00781544 | 21.11 | 0.00781544 | 43.5343 | 11451.66 | 0.00 | 21941.64 | 21941.64 | 1.60118555 | 16.60 | 12.65 | 0.00749163 | 35647.6 | 30.05 | 17.64 | 0.00749163 | 49351.0 | |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 25614.641 | 20499.133 | 1.533215 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6404 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.533215 | 1.60118555 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 20514.85 | 20514.85 | 0.8009 | 1.60118555 | 1.533215 | 22.21 | 14.31 | 0.00849964 | 43924.6 | 9.40 | 9.40 | 0.00849964 | 30852.5 | -999.0 | -999.00 | -999.00 | -999.00 | 976.452 | 19538.40 | 38.10 | 0.00687148 | 18.17 | 0.09915400 | 6.4671 | 21.11 | 0.00861221 | 21.11 | 0.00861221 | 47.9122 | 18158.75 | 0.00 | 25627.18 | 19071.17 | 1.53795082 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.54 | 13.78 | 0.00951331 | 38659.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22885.079 | 22885.079 | 1.581109 | 0.00020021 | 494.323 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 3.7681 | 3.843936 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 22885.08 | 22885.08 | 1.0000 | 1.65120221 | 1.581109 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.20018823 | 60.00 | 32.22 | 27.78 | 0.000 | 22885.08 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00787709 | 21.00 | 0.00787709 | 44.1728 | 9231.46 | 0.00 | 21735.92 | 21735.92 | 1.65120221 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.51 | 17.87 | 0.00800000 | 50098.4 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23053.414 | 23053.414 | 1.582474 | 0.00020168 | 498.532 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 3.7958 | 3.872211 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 23053.41 | 23053.41 | 1.0000 | 1.65262832 | 1.582474 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.20166075 | 60.00 | 32.22 | 27.78 | 0.000 | 23053.41 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00787909 | 21.00 | 0.00787909 | 44.1839 | 9387.96 | 0.00 | 21895.75 | 21895.75 | 1.65262832 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.59 | 17.90 | 0.00800000 | 50183.8 | |
PTAC_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18667.716 | 18667.716 | 1.281459 | 0.00016331 | 458.259 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.281459 | 1.33826835 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 3.0737 | 3.135558 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 18667.72 | 18667.72 | 1.0000 | 1.33826835 | 1.281459 | 18.43 | 11.97 | 0.00740199 | 37286.3 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.16329666 | 60.00 | 32.22 | 27.78 | 0.000 | 18667.72 | -5.20 | 0.00280840 | -5.20 | 0.12561561 | 9.8025 | 21.00 | 0.00790122 | 21.00 | 0.00790122 | 44.3062 | 10111.93 | 0.00 | 19278.17 | 19278.17 | 1.33826835 | 16.60 | 12.57 | 0.00740199 | 35420.7 | 30.74 | 17.80 | 0.00740199 | 49826.0 | |
PTAC_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 21365.078 | 17092.769 | 1.281459 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9440 | 1004.8586 | 1.0443 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.281459 | 1.33826835 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 17879.98 | 17434.34 | 0.8369 | 1.33826835 | 1.281459 | 25.38 | 15.53 | 0.00866297 | 47578.3 | 12.29 | 10.62 | 0.00850000 | 33803.3 | -999.0 | -999.00 | -999.00 | -999.00 | 816.117 | 17063.86 | 38.10 | 0.00687148 | 18.17 | 0.12561561 | 9.8025 | 24.00 | 0.00885766 | 24.00 | 0.00885766 | 41.3318 | 15175.08 | 0.00 | 21375.54 | 15902.74 | 1.28541687 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.57 | 13.79 | 0.00951535 | 38693.1 | |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_FLR_1 | RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LOBBY_FLR_1; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 174625.308 | 134816.252 | 8.637485 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0352 | 1004.8586 | 1.0443 | VAV_FLR_1 FAN | Fan:VariableVolume | 8.637485 | 9.02039930 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 162387.08 | 158010.22 | 0.9299 | 9.02039930 | 8.637485 | 28.62 | 16.62 | 0.00871200 | 51006.9 | 10.83 | 10.03 | 0.00850000 | 32309.3 | -999.0 | -999.00 | -999.00 | -999.00 | 18983.300 | 143403.78 | 38.10 | 0.00687148 | 18.17 | 2.83030000 | 32.7676 | 23.99 | 0.00960904 | 23.99 | 0.00960904 | 44.7956 | 88910.54 | 0.00 | 175130.36 | 126100.23 | 8.66416172 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.42 | 12.41 | 0.00896591 | 35109.2 | |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_1 | RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LOBBY_FLR_1; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 49188.562 | 49188.562 | 2.591245 | 0.00043032 | 801.611 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_FLR_1 FAN | Fan:VariableVolume | 8.637485 | 9.02039930 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 8.0991 | 8.262051 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 49188.56 | 49188.56 | 1.0000 | 2.70611979 | 2.591245 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 0.43027910 | 60.00 | 32.22 | 27.78 | 0.000 | 49188.56 | -5.20 | 0.00280840 | -5.20 | 2.83030000 | 109.2255 | 21.00 | 0.00774878 | 21.00 | 0.00774834 | 43.4598 | 22638.50 | 0.00 | 44799.14 | 44799.14 | 2.70611979 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 19.19 | 8.81 | 0.00280840 | 26406.6 | |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_FLR_6 | BANQUET_FLR_6; DINING_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 147965.470 | 110051.436 | 6.777439 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8035 | 1004.8586 | 1.0443 | VAV_FLR_6 FAN | Fan:VariableVolume | 6.777439 | 7.07789439 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 138082.21 | 136665.52 | 0.9332 | 7.07789439 | 6.777439 | 30.58 | 17.15 | 0.00858735 | 52694.3 | 10.83 | 10.02 | 0.00850000 | 32308.8 | -999.0 | -999.00 | -999.00 | -999.00 | 14895.327 | 123186.88 | 38.10 | 0.00687148 | 18.17 | 3.16750000 | 46.7359 | 23.98 | 0.01009293 | 23.98 | 0.01009293 | 47.0438 | 69698.24 | 0.00 | 148393.42 | 103378.54 | 6.79837106 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.77 | 11.76 | 0.00858855 | 33494.6 | |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_6 | BANQUET_FLR_6; DINING_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 38596.013 | 38596.013 | 2.033232 | 0.00033765 | 628.987 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_FLR_6 FAN | Fan:VariableVolume | 6.777439 | 7.07789439 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 6.3550 | 6.482853 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 38596.01 | 38596.01 | 1.0000 | 2.12336832 | 2.033232 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 0.33762031 | 60.00 | 32.22 | 27.78 | 0.000 | 38596.01 | -5.20 | 0.00280840 | -5.20 | 3.16750000 | 155.7865 | 21.00 | 0.00787801 | 21.00 | 0.00787802 | 44.1781 | 14893.43 | 0.00 | 35151.83 | 35151.83 | 2.12336832 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 19.19 | 8.81 | 0.00280840 | 26406.6 | |
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | VAV_FLR_0 | BASEMENT | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 62541.120 | 50051.658 | 3.774510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8365 | 1004.8586 | 1.0443 | VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 3.774510 | 3.94184006 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | Sensible | 31270.56 | 30766.95 | 1.0000 | 2.62789371 | 2.516340 | 25.50 | 15.52 | 0.00860512 | 47550.7 | 10.80 | 10.01 | 0.00850000 | 32281.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31270.56 | 30.62 | 0.00685962 | 15.81 | 0.85445887 | 33.9564 | 24.00 | 0.00911589 | 24.00 | 0.00911634 | 42.5226 | 38838.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_0 | BASEMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 67499.479 | 67499.479 | 3.774510 | 0.00032102 | 2423.663 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 3.774510 | 3.94184006 | 4197.9300 | 999.8980 | 5.20789712 | 54.44 | 82.22 | 27.78 | 607337.13 | 11.1140 | 6.163520 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 67499.48 | 67499.48 | 1.0000 | 3.94184006 | 3.774510 | 15.07 | 10.09 | 0.00682474 | 32401.3 | 32.11 | 17.18 | 0.00800000 | 52750.5 | 0.32098977 | 60.00 | 32.22 | 27.78 | 0.000 | 67499.48 | -5.20 | 0.00280840 | -5.20 | 0.85445887 | 22.6376 | 21.00 | 0.00800000 | 22.97 | 0.00280840 | 14.0827 | 0.00 | 0.00 | 66546.53 | 66546.53 | 3.94184006 | 16.60 | 11.99 | 0.00682474 | 33959.2 | 33.19 | 18.15 | 0.00682474 | 50841.3 | |
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 73683.710 | 58995.599 | 4.451230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7085 | 1004.8586 | 1.0443 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 4.451233 | 4.64856354 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | Sensible | 36841.86 | 36614.13 | 1.0000 | 3.09904049 | 2.967487 | 24.00 | 14.96 | 0.00853625 | 45844.4 | 11.37 | 10.24 | 0.00850000 | 32859.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36841.86 | 35.98 | 0.00686808 | 17.52 | 0.00000000 | 0.0000 | 24.00 | 0.00853625 | 24.00 | 0.00853625 | 39.8526 | 45835.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51899.705 | 51899.705 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 4.451233 | 4.64856354 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 51899.70 | 51899.70 | 1.0000 | 4.64856354 | 4.451233 | 21.00 | 13.11 | 0.00760964 | 40429.2 | 32.11 | 17.18 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51899.70 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00760964 | 21.00 | 0.00760964 | 42.6922 | 1935.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 45150.180 | 33846.381 | 2.104260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4845 | 1004.8586 | 1.0443 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.104263 | 2.19754863 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 22575.09 | 21303.82 | 1.0000 | 1.46503033 | 1.402840 | 28.49 | 16.77 | 0.00895371 | 51494.0 | 11.33 | 10.23 | 0.00850000 | 32822.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22575.09 | 37.99 | 0.00687130 | 18.14 | 0.67638938 | 48.2157 | 23.99 | 0.00994016 | 23.99 | 0.00994152 | 46.3403 | 21638.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 43131.106 | 43131.106 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.104263 | 2.19754863 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 43131.11 | 43131.11 | 1.0000 | 2.19754863 | 2.104263 | 12.58 | 8.42 | 0.00620739 | 28308.3 | 32.11 | 17.18 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43131.11 | -5.20 | 0.00280840 | -5.20 | 0.67638938 | 32.1438 | 21.00 | 0.00781751 | 21.00 | 0.00781751 | 43.8435 | 7665.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 61493.600 | 47511.185 | 3.047580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.7623 | 1004.8586 | 1.0443 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.047577 | 3.18268141 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 30746.80 | 26111.17 | 1.0000 | 2.12178967 | 2.031720 | 25.51 | 16.35 | 0.00964110 | 50204.8 | 11.37 | 10.25 | 0.00850000 | 32862.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30746.80 | 36.93 | 0.00686961 | 17.82 | 0.36735036 | 18.0808 | 23.95 | 0.01002096 | 23.97 | 0.01002096 | 46.7566 | 31296.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46284.784 | 46284.784 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.047577 | 3.18268141 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | Sensible | 46284.78 | 46284.78 | 1.0000 | 3.18268141 | 3.047577 | 17.64 | 11.20 | 0.00691289 | 35238.4 | 32.11 | 17.18 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46284.78 | -5.20 | 0.00280840 | -5.20 | 0.36735036 | 12.0538 | 20.77 | 0.00747545 | 21.00 | 0.00745919 | 41.8592 | 1652.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_FLR_1_OA_CONTROLLER | FixedDryBulb | 0.00 | 8.64 | - | |||
VAV_FLR_6_OA_CONTROLLER | FixedDryBulb | 0.00 | 6.78 | - | |||
VAV_FLR_0_OA_CONTROLLER | FixedDryBulb | 0.00 | 3.77 | - | |||
PSZ_LAUNDRY_OA_CONTROLLER | FixedDryBulb | 0.00 | 4.45 | - | |||
PSZ_CAFE_OA_CONTROLLER | FixedDryBulb | 0.68 | 2.10 | - | |||
PSZ_KITCHEN_OA_CONTROLLER | FixedDryBulb | 0.37 | 3.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_FLR_6_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_FLR_6_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2120.67 | 4361.67 | 166.83 |
RETAIL_1_FLR_1 | 3755.50 | 4937.17 | 1170.00 |
RETAIL_2_FLR_1 | 2938.83 | 5182.33 | 937.17 |
MECH_FLR_1 | 2410.00 | 5211.00 | 199.83 |
STORAGE_FLR_1 | 2035.67 | 6024.00 | 423.50 |
LAUNDRY_FLR_1 | 8750.00 | 4375.33 | 4375.33 |
CAFE_FLR_1 | 4664.67 | 3383.00 | 775.00 |
LOBBY_FLR_1 | 3606.67 | 4373.50 | 1262.83 |
ROOM_1_FLR_3 | 760.67 | 7698.83 | 445.17 |
ROOM_2_FLR_3 | 1508.67 | 7283.33 | 825.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 513.83 | 8478.00 | 400.83 |
ROOM_5_FLR_3 | 611.17 | 7629.17 | 421.17 |
ROOM_6_FLR_3 | 1211.50 | 7315.00 | 778.17 |
CORRIDOR_FLR_3 | 6201.50 | 2898.50 | 2898.50 |
ROOM_1_FLR_6 | 1935.17 | 7486.17 | 1333.83 |
ROOM_2_FLR_6 | 2706.50 | 7144.67 | 1803.50 |
ROOM_3_MULT9_FLR_6 | 1100.50 | 7384.33 | 677.33 |
BANQUET_FLR_6 | 4368.67 | 3973.67 | 1457.83 |
DINING_FLR_6 | 4781.83 | 3109.33 | 1416.50 |
KITCHEN_FLR_6 | 8655.33 | 6391.50 | 6391.50 |
CORRIDOR_FLR_6 | 6483.17 | 2919.17 | 2667.50 |
Facility | 8760.00 | 8760.00 | 7989.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 1.17 | 0.00 | 1.17 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.33 | 0.00 | 0.33 |
ROOM_2_FLR_3 | 0.00 | 29.50 | 0.00 | 29.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 49.00 | 0.00 | 49.00 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 50.33 | 0.00 | 50.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.50 | 0.00 | 0.50 |
ROOM_2_FLR_6 | 0.00 | 22.00 | 0.00 | 22.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.50 | 0.00 | 0.50 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.67 | 0.00 | 0.67 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 71.50 | 0.00 | 71.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.966 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.021 | 0.135 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 1.409 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.659 | 0.050 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.684 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 22.523 | 0.145 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 5.255 | 0.106 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.731 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.359 | 0.175 | 0.000 | 0.056 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.175 | 0.000 | 0.045 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.396 | 0.078 | 0.000 | 0.097 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.362 | 0.175 | 0.000 | 0.056 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.358 | 0.175 | 0.000 | 0.056 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.069 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.360 | 0.175 | 0.000 | 0.066 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.358 | 0.175 | 0.000 | 0.052 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.415 | 0.142 | 0.000 | 0.105 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.128 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 5.345 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 18.659 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.063 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 0.633 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.088 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 0.965 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.430 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.450 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 0.000 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 3.215 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 1.248 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.176 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 4.277 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 4.207 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 0.000 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV_FLR_0 | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.8545 | 0.854 |
RETAIL_1_FLR_1 | VAV_FLR_1 | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV_FLR_1 | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV_FLR_1 | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV_FLR_1 | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | PSZ_CAFE | 82.58 | 142.30 | 748.35 | 188.86 | 0.6764 | 0.676 |
LOBBY_FLR_1 | VAV_FLR_1 | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 39.02 | 0.062 | ||
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 39.02 | 0.062 | ||
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | 24.52 | 0.837 | |||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 24.53 | 0.837 | ||
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 39.02 | 0.062 | ||
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 39.02 | 0.062 | ||
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 389.40 | 0.475 | ||
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 39.02 | 0.015 | ||
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 39.02 | 0.015 | ||
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 24.53 | 0.099 | ||
BANQUET_FLR_6 | VAV_FLR_6 | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV_FLR_6 | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | PSZ_KITCHEN | 12.90 | 22.24 | 314.87 | 103.30 | 0.3674 | 0.367 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 412.12 | 0.126 | ||
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 1.8982 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 40078493.71 | 0.00 | 40078493.71 | 0.00 | 40078493.71 | 26946214.98 | 0.00 | 3989.36 | 4770.64 | 0.00 |
RETAIL_1_FLR_1 | 4626358.90 | 0.00 | 4626358.90 | 309826.10 | 4936185.00 | 2498216.28 | 0.00 | 0.10 | 8759.90 | 0.00 |
RETAIL_2_FLR_1 | 3727463.16 | 0.00 | 3727463.16 | 119593.27 | 3847056.43 | 2892943.94 | 1888.36 | 1116.27 | 5755.37 | 0.00 |
MECH_FLR_1 | 3691035.39 | 0.00 | 3691035.39 | 282647.43 | 3973682.82 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2214852.69 | 0.00 | 2214852.69 | 163072.00 | 2377924.69 | 1821682.01 | 2425.77 | 1249.52 | 5084.71 | 0.00 |
LAUNDRY_FLR_1 | 59886312.04 | 0.00 | 59886312.04 | 385940.64 | 60272252.68 | 0.00 | 0.00 | 0.00 | 6145.17 | 0.00 |
CAFE_FLR_1 | 33775823.60 | 0.00 | 33775823.60 | 684888.14 | 34460711.74 | 21330615.53 | 0.00 | 5000.58 | 3759.42 | 0.00 |
LOBBY_FLR_1 | 77019438.72 | 0.00 | 77019438.72 | 1956881.84 | 78976320.57 | 59728886.00 | 2201.44 | 1324.21 | 5234.35 | 0.00 |
ROOM_1_FLR_3 | 1482088.86 | 57392.75 | 1539481.62 | 179831.92 | 1719313.54 | 1946875.62 | 2432.76 | 5685.17 | 642.08 | 0.00 |
ROOM_2_FLR_3 | 1466673.19 | 46089.98 | 1512763.17 | 179818.20 | 1692581.37 | 1946647.51 | 2432.27 | 5869.50 | 458.23 | 0.00 |
ROOM_3_MULT19_FLR_3 | 4768753.26 | 0.00 | 4768753.26 | 50175.12 | 4818928.38 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 7335.20 |
ROOM_4_MULT19_FLR_3 | 19502769.02 | 62425.55 | 19565194.57 | 50188.84 | 19615383.41 | 26405105.73 | 2432.28 | 5711.53 | 616.19 | 0.00 |
ROOM_5_FLR_3 | 1493858.46 | 57548.50 | 1551406.96 | 179831.92 | 1731238.88 | 1946875.62 | 2432.81 | 5685.17 | 642.03 | 0.00 |
ROOM_6_FLR_3 | 1473736.56 | 57450.81 | 1531187.37 | 179818.20 | 1711005.58 | 1946647.51 | 2431.18 | 5730.22 | 598.61 | 0.00 |
CORRIDOR_FLR_3 | 2789700.63 | 0.00 | 2789700.63 | 217452.98 | 3007153.61 | 14972100.18 | 8760.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 371451.26 | 67941.24 | 439392.50 | 179868.73 | 619261.23 | 486718.90 | 2253.91 | 5686.39 | 819.70 | 0.00 |
ROOM_2_FLR_6 | 368390.80 | 53252.00 | 421642.79 | 179855.01 | 601497.80 | 486661.88 | 2290.55 | 5867.63 | 601.82 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2419013.44 | 68006.26 | 2487019.70 | 92027.14 | 2579046.84 | 3126920.42 | 2433.17 | 5682.50 | 644.33 | 0.00 |
BANQUET_FLR_6 | 44501414.26 | 0.00 | 44501414.26 | 439194.23 | 44940608.49 | 37458366.31 | 1096.11 | 2871.93 | 4791.95 | 0.00 |
DINING_FLR_6 | 46366450.78 | 0.00 | 46366450.78 | 439194.23 | 46805645.01 | 37458366.31 | 0.00 | 649.27 | 8110.73 | 0.00 |
KITCHEN_FLR_6 | 50432076.19 | 0.00 | 50432076.19 | 393180.66 | 50825256.85 | 11584760.86 | 0.00 | 2614.83 | 6145.17 | 0.00 |
CORRIDOR_FLR_6 | 673676.34 | 0.00 | 673676.34 | 384823.29 | 1058499.63 | 3961413.96 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.23E+10 | 6351519.46 | 0.23E+10 | 18121884.23 | 0.23E+10 | 0.43E+10 | 8760.00 | 7639.16 | 8760.00 | 7335.20 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.2709 | 0.0000 | 1.2709 | 0.0000 | 1.2709 | 0.8545 | 0.00 | 3989.36 | 4770.64 |
RETAIL_1_FLR_1 | 0.1467 | 0.0000 | 0.1467 | 0.0098 | 0.1565 | 0.0792 | 0.00 | 0.10 | 8759.90 |
RETAIL_2_FLR_1 | 0.1182 | 0.0000 | 0.1182 | 0.0038 | 0.1220 | 0.0917 | 1888.36 | 1116.27 | 5755.37 |
MECH_FLR_1 | 0.1170 | 0.0000 | 0.1170 | 0.0090 | 0.1260 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0702 | 0.0000 | 0.0702 | 0.0052 | 0.0754 | 0.0578 | 2425.77 | 1249.52 | 5084.71 |
LAUNDRY_FLR_1 | 1.8990 | 0.0000 | 1.8990 | 0.0122 | 1.9112 | 0.0000 | 0.00 | 0.00 | 6145.17 |
CAFE_FLR_1 | 1.0710 | 0.0000 | 1.0710 | 0.0217 | 1.0927 | 0.6764 | 0.00 | 5000.58 | 3759.42 |
LOBBY_FLR_1 | 2.4423 | 0.0000 | 2.4423 | 0.0621 | 2.5043 | 1.8940 | 2201.44 | 1324.21 | 5234.35 |
ROOM_1_FLR_3 | 0.0470 | 0.0018 | 0.0488 | 0.0057 | 0.0545 | 0.0617 | 2432.76 | 5685.17 | 642.08 |
ROOM_2_FLR_3 | 0.0465 | 0.0015 | 0.0480 | 0.0057 | 0.0537 | 0.0617 | 2432.27 | 5869.50 | 458.23 |
ROOM_4_MULT19_FLR_3 | 0.6184 | 0.0020 | 0.6204 | 0.0016 | 0.6220 | 0.8373 | 2432.28 | 5711.53 | 616.19 |
ROOM_5_FLR_3 | 0.0474 | 0.0018 | 0.0492 | 0.0057 | 0.0549 | 0.0617 | 2432.81 | 5685.17 | 642.03 |
ROOM_6_FLR_3 | 0.0467 | 0.0018 | 0.0486 | 0.0057 | 0.0543 | 0.0617 | 2431.18 | 5730.22 | 598.61 |
CORRIDOR_FLR_3 | 0.0885 | 0.0000 | 0.0885 | 0.0069 | 0.0954 | 0.4748 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.0118 | 0.0022 | 0.0139 | 0.0057 | 0.0196 | 0.0154 | 2253.91 | 5686.39 | 819.70 |
ROOM_2_FLR_6 | 0.0117 | 0.0017 | 0.0134 | 0.0057 | 0.0191 | 0.0154 | 2290.55 | 5867.63 | 601.82 |
ROOM_3_MULT9_FLR_6 | 0.0767 | 0.0022 | 0.0789 | 0.0029 | 0.0818 | 0.0992 | 2433.17 | 5682.50 | 644.33 |
BANQUET_FLR_6 | 1.4111 | 0.0000 | 1.4111 | 0.0139 | 1.4251 | 1.1878 | 1096.11 | 2871.93 | 4791.95 |
DINING_FLR_6 | 1.4703 | 0.0000 | 1.4703 | 0.0139 | 1.4842 | 1.1878 | 0.00 | 649.27 | 8110.73 |
KITCHEN_FLR_6 | 1.5992 | 0.0000 | 1.5992 | 0.0125 | 1.6117 | 0.3674 | 0.00 | 2614.83 | 6145.17 |
CORRIDOR_FLR_6 | 0.0214 | 0.0000 | 0.0214 | 0.0122 | 0.0336 | 0.1256 | 8760.00 | 0.00 | 0.00 |
Total Facility | 60.4560 | 0.2014 | 60.6574 | 0.4537 | 61.1111 | 73.9670 | 8760.00 | 7639.16 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_FLR_1 | 99551665.49 | 0.00 | 99551665.49 | 66941728.23 | 0.00 | 0.00 | 8760.00 | 0.00 |
VAV_FLR_6 | 99103107.53 | 0.00 | 99103107.53 | 74916732.61 | 0.00 | 0.00 | 8760.00 | 0.00 |
VAV_FLR_0 | 43710893.44 | 0.00 | 43710893.44 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
PSZ_LAUNDRY | 65313734.60 | 0.00 | 65313734.60 | 0.00 | 0.00 | 0.00 | 6145.17 | 0.00 |
PSZ_CAFE | 36836884.82 | 0.00 | 36836884.82 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
PSZ_KITCHEN | 55002673.02 | 0.00 | 55002673.02 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_FLR_1 | 3.1568 | 0.0000 | 3.1568 | 2.1227 | 0.00 | 0.00 | 8760.00 |
VAV_FLR_6 | 3.1425 | 0.0000 | 3.1425 | 2.3756 | 0.00 | 0.00 | 8760.00 |
VAV_FLR_0 | 1.3861 | 0.0000 | 1.3861 | 0.8545 | 0.00 | 0.00 | 8760.00 |
PSZ_LAUNDRY | 2.0711 | 0.0000 | 2.0711 | 0.0000 | 0.00 | 0.00 | 6145.17 |
PSZ_CAFE | 1.1681 | 0.0000 | 1.1681 | 0.6764 | 0.00 | 0.00 | 8760.00 |
PSZ_KITCHEN | 1.7441 | 0.0000 | 1.7441 | 0.3674 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_FLR_1 | 0.00 | 59.33 | 6050.17 | 0.00 | 0.00 | 0.00 | 2650.50 | 0.00 | 0.00 | 0.00 |
VAV_FLR_6 | 0.00 | 59.50 | 5079.12 | 0.00 | 0.00 | 0.00 | 3621.38 | 0.00 | 0.00 | 0.00 |
VAV_FLR_0 | 0.00 | 0.00 | 4787.48 | 0.00 | 0.00 | 0.00 | 3972.52 | 0.00 | 0.00 | 0.00 |
PSZ_LAUNDRY | 0.00 | 0.00 | 6145.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_CAFE | 0.00 | 4988.01 | 3771.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_KITCHEN | 0.00 | 2614.83 | 6145.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_FLR_1 | 0.0000 | 3.6836 | 3.4205 | 0.0000 | 0.0000 | 0.0000 | 2.5441 | 0.0000 | 0.0000 | 0.0000 |
VAV_FLR_6 | 0.0000 | 3.4489 | 3.4975 | 0.0000 | 0.0000 | 0.0000 | 2.6405 | 0.0000 | 0.0000 | 0.0000 |
VAV_FLR_0 | 0.0000 | 0.0000 | 1.7631 | 0.0000 | 0.0000 | 0.0000 | 0.9320 | 0.0000 | 0.0000 | 0.0000 |
PSZ_LAUNDRY | 0.0000 | 0.0000 | 2.9524 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ_CAFE | 0.0000 | 0.7377 | 1.7377 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ_KITCHEN | 0.0000 | 0.4008 | 2.3159 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 6 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1309 |
Defaulted Fields | 1279 |
Fields with Defaults | 4096 |
Autosized Fields | 364 |
Autosizable Fields | 530 |
Autocalculated Fields | 279 |
Autocalculatable Fields | 538 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 7092.93 | 105562.81 | 29-NOV-03:00 | 476535.94 | 05-JUN-19:10 |
Electricity:Building | 3195.05 | 37866.17 | 02-JAN-02:10 | 208035.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 384.14 | 4218.04 | 02-JAN-02:10 | 29343.82 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 3187.96 | 37725.02 | 02-JAN-02:10 | 207793.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 241.03 | 2190.14 | 02-JAN-02:10 | 19711.29 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 241.03 | 2190.14 | 02-JAN-02:10 | 19711.29 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 22.10 | 252.63 | 02-JAN-02:10 | 1660.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.92 | 108.29 | 02-JAN-02:10 | 974.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.92 | 108.29 | 02-JAN-02:10 | 974.63 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 25.60 | 292.55 | 02-JAN-02:10 | 1922.56 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.80 | 125.40 | 02-JAN-02:10 | 1128.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.80 | 125.40 | 02-JAN-02:10 | 1128.63 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 41.66 | 441.91 | 02-JAN-02:10 | 3226.11 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 29.18 | 265.18 | 02-JAN-02:10 | 2386.66 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 29.18 | 265.18 | 02-JAN-02:10 | 2386.66 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 12.58 | 132.58 | 02-JAN-02:10 | 976.54 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 8.98 | 81.60 | 02-JAN-02:10 | 734.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 8.98 | 81.60 | 02-JAN-02:10 | 734.39 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 45.66 | 487.82 | 02-JAN-02:10 | 3526.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 31.32 | 284.60 | 02-JAN-02:10 | 2561.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 31.32 | 284.60 | 02-JAN-02:10 | 2561.44 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 350.46 | 3941.97 | 02-JAN-02:10 | 26504.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 201.46 | 1830.55 | 02-JAN-02:10 | 16474.99 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 201.46 | 1830.55 | 02-JAN-02:10 | 16474.99 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 35.36 | 389.80 | 01-JAN-02:10 | 2642.31 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 35.36 | 389.75 | 01-JAN-02:10 | 2642.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 492.14 | 5849.00 | 01-JAN-02:10 | 36399.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 297.14 | 2515.76 | 01-JAN-02:10 | 22870.56 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 297.14 | 2515.76 | 01-JAN-02:10 | 22870.56 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 492.27 | 5850.60 | 01-JAN-02:10 | 36409.55 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 297.22 | 2516.45 | 01-JAN-02:10 | 22876.81 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 297.22 | 2516.45 | 01-JAN-02:10 | 22876.81 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 35.36 | 389.80 | 01-JAN-02:10 | 2642.31 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 35.36 | 389.75 | 01-JAN-02:10 | 2642.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.84 | 97.45 | 01-JAN-02:10 | 660.58 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.83 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.83 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.84 | 97.44 | 01-JAN-02:10 | 660.50 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.78 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.78 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 58.30 | 692.83 | 01-JAN-02:10 | 4311.66 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.20 | 298.00 | 01-JAN-02:10 | 2709.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.20 | 298.00 | 01-JAN-02:10 | 2709.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 230.86 | 2749.09 | 02-JAN-02:10 | 11246.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 230.86 | 2749.09 | 02-JAN-02:10 | 11246.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 459.16 | 6380.86 | 02-JAN-02:10 | 19096.59 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.69 | 133.44 | 02-JAN-02:10 | 1200.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.69 | 133.44 | 02-JAN-02:10 | 1200.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1661.82 | 24317.47 | 02-JAN-02:10 | 89286.95 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1661.82 | 24317.47 | 02-JAN-02:10 | 89286.95 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 437.38 | 6106.28 | 01-JAN-00:10 | 16602.84 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 43.91 | 732.77 | 06-MAR-23:30 | 2787.85 | 24-SEP-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 39.63 | 685.54 | 09-MAR-23:10 | 2642.19 | 03-FEB-07:00 |
LowTempRefrigeration:Refrigeration:Electricity | 15.82 | 0.00 | 01-JAN-11:10 | 1324.96 | 21-JUL-07:20 |
MedTempRefrigeration:Refrigeration:Electricity | 21.00 | 636.02 | 08-APR-05:00 | 716.54 | 21-JUL-08:10 |
Fans:Electricity | 1155.27 | 26075.27 | 05-JAN-08:00 | 54998.50 | 15-JUN-20:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2716.12 | 26621.99 | 15-JAN-14:10 | 252131.21 | 14-JUN-18:10 |
ExteriorEquipment:Electricity | 841.97 | 10954.76 | 02-JAN-02:20 | 50420.89 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.24 | 382.76 | 02-JAN-02:20 | 1343.17 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 7092.93 | 105562.81 | 29-NOV-03:00 | 476535.94 | 05-JUN-19:10 |
ElectricityPurchased:Plant | 7092.93 | 105562.81 | 29-NOV-03:00 | 476535.94 | 05-JUN-19:10 |
Cogeneration:ElectricityPurchased | 7092.93 | 105562.81 | 29-NOV-03:00 | 476535.94 | 05-JUN-19:10 |
General:Cogeneration:ElectricityPurchased | 7092.93 | 105562.81 | 29-NOV-03:00 | 476535.94 | 05-JUN-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 7092.93 | 105562.81 | 29-NOV-03:00 | 476535.94 | 05-JUN-19:10 |
ElectricityNet:Plant | 7092.93 | 105562.81 | 29-NOV-03:00 | 476535.94 | 05-JUN-19:10 |
Cogeneration:ElectricityNet | 7092.93 | 105562.81 | 29-NOV-03:00 | 476535.94 | 05-JUN-19:10 |
General:Cogeneration:ElectricityNet | 7092.93 | 105562.81 | 29-NOV-03:00 | 476535.94 | 05-JUN-19:10 |
General:Fans:Electricity | 1155.27 | 26075.27 | 05-JAN-08:00 | 54998.50 | 15-JUN-20:10 |
Cooling:Electricity | 1538.61 | 0.00 | 02-JAN-06:30 | 196774.46 | 14-JUN-18:10 |
General:Cooling:Electricity | 1538.61 | 0.00 | 02-JAN-06:30 | 196774.46 | 14-JUN-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorLights:Electricity | 322.39 | 0.00 | 01-JAN-07:20 | 20502.98 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 322.39 | 0.00 | 01-JAN-07:20 | 20502.98 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 2.81 | 47.91 | 19-JUL-09:00 | 678.66 | 27-DEC-05:00 |
General:Pumps:Electricity | 2.81 | 47.91 | 19-JUL-09:00 | 678.66 | 27-DEC-05:00 |
WIRED_LTG_ELECTRICITY | 53.72 | 0.00 | 01-JAN-00:10 | 4267.60 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4689.66 | 25063.55 | 01-AUG-02:20 | 429664.05 | 26-DEC-19:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:HVAC | 11.12 | 0.00 | 01-JAN-00:10 | 16807.10 | 27-DEC-07:20 |
Heating:NaturalGas | 394.33 | 0.00 | 01-JAN-10:50 | 189138.04 | 27-DEC-05:00 |
General:Heating:NaturalGas | 11.12 | 0.00 | 01-JAN-00:10 | 16807.10 | 27-DEC-07:20 |
NaturalGas:Plant | 2889.69 | 11701.65 | 01-AUG-02:20 | 336788.91 | 26-DEC-19:10 |
WaterSystems:NaturalGas | 2506.49 | 11701.65 | 01-AUG-02:20 | 241650.99 | 25-JAN-21:50 |
Water Heater:WaterSystems:NaturalGas | 2506.49 | 11701.65 | 01-AUG-02:20 | 241650.99 | 25-JAN-21:50 |
Boiler:Heating:NaturalGas | 383.21 | 0.00 | 01-JAN-10:50 | 177761.36 | 27-DEC-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-22:00 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-22:00 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-22:00 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-22:00 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-22:00 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 07-FEB-22:00 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 12710.85 | 112454.66 | 13-FEB-15:00 | 1073552.84 | 21-JUL-18:20 |
EnergyTransfer:Building | 6052.74 | 89178.36 | 15-JAN-15:00 | 418662.08 | 15-JUN-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 721.20 | 8638.35 | 19-DEC-04:00 | 36685.52 | 02-JUL-10:40 |
Refrigeration:EnergyTransfer | 182.18 | 4015.42 | 09-MAR-23:10 | 10477.96 | 21-JUL-07:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.09 | 2007.71 | 09-MAR-23:10 | 5238.98 | 21-JUL-07:20 |
General:Refrigeration:EnergyTransfer | 91.09 | 2007.71 | 09-MAR-23:10 | 5238.98 | 21-JUL-07:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.09 | 2007.71 | 09-MAR-23:10 | 5238.98 | 21-JUL-07:20 |
EnergyTransfer:Plant | 998.11 | 9968.62 | 11-AUG-02:00 | 174333.90 | 03-FEB-07:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.57 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.52 | 1996.39 | 08-APR-05:00 | 2558.45 | 21-JUL-08:10 |
EnergyTransfer:Zone:BASEMENT | 471.87 | 399.98 | 03-MAR-14:30 | 29029.23 | 21-SEP-20:00 |
Heating:EnergyTransfer | 33.81 | 0.00 | 01-JAN-08:00 | 28478.63 | 27-DEC-05:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 33.81 | 0.00 | 01-JAN-08:00 | 28478.63 | 27-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5927.84 | 85390.09 | 20-DEC-04:00 | 415095.91 | 15-JUN-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 471.87 | 399.98 | 03-MAR-14:30 | 29029.23 | 21-SEP-20:00 |
General:Cooling:EnergyTransfer | 5927.84 | 85390.09 | 20-DEC-04:00 | 415095.91 | 15-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 471.87 | 399.98 | 03-MAR-14:30 | 29029.23 | 21-SEP-20:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.64 | 0.31 | 15-FEB-05:20 | 4580.89 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.26 | 0.00 | 01-JAN-00:10 | 1093.45 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.26 | 0.00 | 01-JAN-00:10 | 1093.45 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.38 | 0.00 | 02-JAN-05:50 | 4580.89 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 49.38 | 0.00 | 02-JAN-05:50 | 4580.89 | 03-OCT-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.32 | 848.96 | 26-DEC-12:00 | 2892.68 | 15-JUN-18:40 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.32 | 848.96 | 26-DEC-12:00 | 2892.68 | 15-JUN-18:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.32 | 848.96 | 26-DEC-12:00 | 2892.68 | 15-JUN-18:40 |
EnergyTransfer:Zone:MECH_FLR_1 | 42.85 | 782.86 | 28-DEC-05:00 | 3475.49 | 15-JUN-19:50 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 42.85 | 782.86 | 28-DEC-05:00 | 3475.49 | 15-JUN-19:50 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 42.85 | 782.86 | 28-DEC-05:00 | 3475.49 | 15-JUN-19:50 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 22.37 | 0.20 | 10-JAN-05:00 | 1897.98 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 287.50 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 287.50 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 22.33 | 0.00 | 07-JAN-04:20 | 1897.98 | 15-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 22.33 | 0.00 | 07-JAN-04:20 | 1897.98 | 15-JUN-18:30 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.03 | 8028.72 | 28-JAN-06:00 | 39547.68 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.03 | 8028.72 | 28-JAN-06:00 | 39547.68 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 607.03 | 8028.72 | 28-JAN-06:00 | 39547.68 | 15-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 257.25 | 1015.36 | 27-DEC-07:30 | 15188.28 | 22-OCT-12:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 257.25 | 1015.36 | 27-DEC-07:30 | 15188.28 | 22-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 257.25 | 1015.36 | 27-DEC-07:30 | 15188.28 | 22-OCT-12:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 901.86 | 17818.90 | 26-DEC-11:30 | 49889.12 | 15-JUN-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 901.86 | 17818.90 | 26-DEC-11:30 | 49889.12 | 15-JUN-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 901.86 | 17818.90 | 26-DEC-11:30 | 49889.12 | 15-JUN-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 89.47 | 0.00 | 01-JAN-08:00 | 13646.18 | 19-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 3.00 | 0.00 | 01-JAN-00:10 | 3231.01 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 3.00 | 0.00 | 01-JAN-00:10 | 3231.01 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 86.47 | 0.00 | 01-JAN-03:20 | 13646.18 | 19-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 86.47 | 0.00 | 01-JAN-03:20 | 13646.18 | 19-SEP-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 73.25 | 0.00 | 01-JAN-08:00 | 13088.11 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 4.99 | 0.00 | 01-JAN-08:00 | 4159.62 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 4.99 | 0.00 | 01-JAN-08:00 | 4159.62 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 68.26 | 0.00 | 01-JAN-00:10 | 13088.11 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 68.26 | 0.00 | 01-JAN-00:10 | 13088.11 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 549.11 | 0.00 | 01-JAN-00:30 | 58863.42 | 22-OCT-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 549.11 | 0.00 | 01-JAN-00:30 | 58863.42 | 22-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 549.11 | 0.00 | 01-JAN-00:30 | 58863.42 | 22-OCT-13:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 610.98 | 0.00 | 01-JAN-08:00 | 92478.05 | 20-MAY-09:00 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 6.27 | 0.00 | 01-JAN-00:10 | 9134.02 | 13-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 6.27 | 0.00 | 01-JAN-00:10 | 9134.02 | 13-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 604.70 | 0.00 | 01-JAN-08:00 | 92478.05 | 20-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 604.70 | 0.00 | 01-JAN-08:00 | 92478.05 | 20-MAY-09:00 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 90.17 | 0.00 | 01-JAN-08:00 | 11147.26 | 17-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 2.99 | 0.00 | 01-JAN-00:10 | 3241.63 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 2.99 | 0.00 | 01-JAN-00:10 | 3241.63 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 87.18 | 0.00 | 01-JAN-00:40 | 11147.26 | 17-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 87.18 | 0.00 | 01-JAN-00:40 | 11147.26 | 17-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 72.72 | 0.00 | 01-JAN-08:00 | 13504.41 | 20-MAY-09:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 4.61 | 0.00 | 01-JAN-08:00 | 3482.41 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 4.61 | 0.00 | 01-JAN-08:00 | 3482.41 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 68.11 | 0.00 | 01-JAN-00:10 | 13504.41 | 20-MAY-09:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 68.11 | 0.00 | 01-JAN-00:10 | 13504.41 | 20-MAY-09:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 162.95 | 0.00 | 01-JAN-08:10 | 13832.33 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 162.95 | 0.00 | 01-JAN-08:10 | 13832.33 | 15-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 162.95 | 0.00 | 01-JAN-08:10 | 13832.33 | 15-JUN-18:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 24.13 | 0.00 | 01-JAN-08:00 | 3903.92 | 19-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.55 | 0.00 | 01-JAN-08:00 | 1334.13 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.55 | 0.00 | 01-JAN-08:00 | 1334.13 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 21.58 | 0.00 | 01-JAN-00:10 | 3903.92 | 19-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 21.58 | 0.00 | 01-JAN-00:10 | 3903.92 | 19-SEP-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 20.98 | 0.00 | 01-JAN-08:00 | 3802.63 | 18-JUN-15:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.41 | 0.00 | 01-JAN-08:00 | 1361.87 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.41 | 0.00 | 01-JAN-08:00 | 1361.87 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.57 | 0.00 | 01-JAN-00:10 | 3802.63 | 18-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.57 | 0.00 | 01-JAN-00:10 | 3802.63 | 18-JUN-15:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 136.18 | 0.00 | 01-JAN-08:00 | 18795.28 | 22-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 5.55 | 0.00 | 01-JAN-00:10 | 5338.75 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 5.55 | 0.00 | 01-JAN-00:10 | 5338.75 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 130.62 | 0.00 | 01-JAN-01:30 | 18795.28 | 22-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 130.62 | 0.00 | 01-JAN-01:30 | 18795.28 | 22-OCT-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 493.63 | 9607.43 | 27-DEC-09:30 | 25116.86 | 05-JUN-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 493.63 | 9607.43 | 27-DEC-09:30 | 25116.86 | 05-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 493.63 | 9607.43 | 27-DEC-09:30 | 25116.86 | 05-JUN-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 522.05 | 10483.27 | 27-DEC-09:30 | 26319.24 | 05-JUN-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 522.05 | 10483.27 | 27-DEC-09:30 | 26319.24 | 05-JUN-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 522.05 | 10483.27 | 27-DEC-09:30 | 26319.24 | 05-JUN-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 630.11 | 6394.61 | 19-DEC-04:00 | 31632.33 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 630.11 | 6394.61 | 19-DEC-04:00 | 31632.33 | 02-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 89.72 | 0.00 | 01-JAN-00:10 | 10470.71 | 03-JUL-12:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.13 | 0.00 | 01-JAN-00:10 | 2290.71 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.13 | 0.00 | 01-JAN-00:10 | 2290.71 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 89.59 | 0.00 | 01-JAN-00:10 | 10470.71 | 03-JUL-12:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 89.59 | 0.00 | 01-JAN-00:10 | 10470.71 | 03-JUL-12:50 |
PlantLoopHeatingDemand:Facility | 909.00 | 7610.31 | 31-JUL-00:10 | 170856.92 | 03-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 666.01 | 7610.31 | 31-JUL-00:10 | 51272.17 | 30-JAN-07:30 |
WaterSystems:PlantLoopHeatingDemand | 666.01 | 7610.31 | 31-JUL-00:10 | 51272.17 | 30-JAN-07:30 |
General:WaterSystems:PlantLoopHeatingDemand | 666.01 | 7610.31 | 31-JUL-00:10 | 51272.17 | 30-JAN-07:30 |
EnergyTransfer:HVAC | 5660.00 | 0.25 | 16-JAN-16:00 | 690133.48 | 20-JUL-22:00 |
HeatingCoils:EnergyTransfer | 251.89 | 0.00 | 01-JAN-10:50 | 135688.23 | 27-DEC-05:00 |
PlantLoopHeatingDemand:HVAC | 242.99 | 0.00 | 01-JAN-10:50 | 126586.89 | 27-DEC-05:00 |
HeatingCoils:PlantLoopHeatingDemand | 242.99 | 0.00 | 01-JAN-10:50 | 126586.89 | 27-DEC-05:00 |
CoolingCoils:EnergyTransfer | 5408.11 | 0.00 | 02-JAN-06:30 | 690133.48 | 20-JUL-22:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 666.01 | 7610.31 | 31-JUL-00:10 | 51272.17 | 30-JAN-07:30 |
WaterUse:WaterSystems:EnergyTransfer | 666.01 | 7610.31 | 31-JUL-00:10 | 51272.17 | 30-JAN-07:30 |
Boilers:EnergyTransfer | 241.01 | 0.00 | 01-JAN-10:50 | 127762.18 | 27-DEC-05:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -471.875 | 0.000 | 0.000 | 134.404 | 241.034 | 143.105 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -46.667 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.264 | -49.376 | 0.000 | 0.000 | 14.634 | 11.918 | 10.186 | 23.144 | 0.000 | 0.453 | 1.109 | 0.000 | -10.146 | 0.000 | -2.186 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -43.322 | 0.000 | 0.000 | 16.197 | 13.801 | 11.795 | 0.000 | 0.000 | 0.176 | 2.265 | 0.000 | 0.000 | 0.000 | -0.912 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -42.852 | 0.000 | 0.000 | 3.466 | 29.185 | 12.471 | 0.000 | 0.000 | 0.412 | 0.000 | 0.000 | 0.000 | 0.000 | -2.107 | -0.575 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.041 | -22.330 | 0.000 | 0.000 | 2.781 | 8.980 | 3.598 | 0.000 | 0.000 | 0.243 | 7.788 | 0.000 | 0.000 | 0.000 | -1.102 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -607.029 | 0.000 | 0.000 | 10.551 | 5.547 | 658.131 | 0.000 | 0.000 | 0.560 | 0.000 | 0.000 | 0.000 | 0.000 | -3.145 | -64.614 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -257.251 | 0.000 | 0.000 | 185.258 | 31.322 | 14.341 | 64.064 | 0.000 | 0.994 | 0.001 | 0.000 | -30.401 | 0.000 | -5.190 | -3.138 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -901.870 | 0.000 | 0.000 | 539.278 | 201.459 | 148.998 | 86.075 | 0.000 | 2.873 | 0.002 | 0.000 | -41.635 | 0.000 | -15.287 | -19.891 |
ROOM_1_FLR_3 | 2.996 | -86.468 | 0.000 | 0.000 | 0.000 | 0.000 | 9.626 | 24.885 | 10.478 | 57.499 | 0.000 | 1.633 | 9.370 | 0.000 | -24.823 | 0.000 | -5.195 | -0.001 |
ROOM_2_FLR_3 | 4.994 | -68.257 | 0.000 | 0.000 | 0.000 | 0.000 | 9.418 | 24.882 | 10.477 | 42.988 | 0.000 | 1.492 | 6.627 | 0.000 | -26.953 | 0.000 | -5.667 | -0.000 |
ROOM_3_MULT19_FLR_3 | 0.000 | -549.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 297.141 | 194.997 | 286.998 | 0.000 | 2.970 | 6.414 | 0.000 | -200.443 | 0.000 | -38.973 | -0.001 |
ROOM_4_MULT19_FLR_3 | 6.272 | -604.677 | 0.000 | 0.000 | 0.000 | 0.000 | 180.113 | 297.222 | 195.050 | 113.395 | 0.000 | 8.182 | 0.000 | 0.000 | -147.414 | 0.000 | -44.482 | -3.661 |
ROOM_5_FLR_3 | 2.993 | -87.177 | 0.000 | 0.000 | 0.000 | 0.000 | 9.616 | 24.885 | 10.478 | 57.367 | 0.000 | 1.631 | 9.261 | 0.000 | -23.824 | 0.000 | -5.231 | -0.001 |
ROOM_6_FLR_3 | 4.612 | -68.109 | 0.000 | 0.000 | 0.000 | 0.000 | 9.430 | 24.882 | 10.477 | 41.937 | 0.000 | 1.489 | 6.308 | 0.000 | -25.078 | 0.000 | -5.947 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | -162.950 | 0.000 | 0.000 | 0.000 | 0.000 | 105.387 | 92.258 | 0.000 | 46.221 | 0.000 | 1.252 | 0.000 | 0.000 | -37.104 | 0.000 | -7.103 | -37.961 |
ROOM_1_FLR_6 | 2.548 | -21.584 | 0.000 | 0.000 | 0.000 | 0.000 | 2.411 | 6.221 | 2.620 | 14.221 | 0.000 | 0.409 | 0.458 | 0.000 | -5.989 | 0.000 | -1.315 | -0.000 |
ROOM_2_FLR_6 | 3.407 | -17.573 | 0.000 | 0.000 | 0.000 | 0.000 | 2.361 | 6.220 | 2.619 | 10.621 | 0.000 | 0.371 | 0.000 | 0.000 | -6.496 | 0.000 | -1.427 | -0.103 |
ROOM_3_MULT9_FLR_6 | 5.552 | -130.621 | 0.000 | 0.000 | 0.000 | 0.000 | 21.649 | 35.197 | 23.098 | 72.022 | 0.000 | 2.016 | 5.694 | 0.000 | -27.772 | 0.000 | -6.836 | -0.000 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -493.630 | 0.000 | 0.000 | 318.456 | 55.004 | 175.857 | 10.467 | 0.000 | 0.627 | 0.000 | 0.000 | -21.125 | 0.000 | -3.461 | -42.195 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -522.059 | 0.000 | 0.000 | 316.626 | 55.004 | 175.857 | 10.196 | 0.000 | 0.625 | 0.000 | 0.000 | -21.786 | 0.000 | -3.516 | -10.948 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -630.095 | 0.000 | 0.000 | 27.940 | 14.685 | 554.015 | 23.645 | 0.000 | 0.559 | 28.785 | 0.000 | -16.301 | 0.000 | -3.233 | -0.000 |
CORRIDOR_FLR_6 | 0.129 | -89.585 | 0.000 | 0.000 | 0.000 | 0.000 | 28.448 | 24.410 | 0.000 | 22.333 | 0.000 | 0.547 | 32.768 | 0.000 | -16.005 | 0.000 | -3.046 | -0.001 |
Total Facility | 33.502 | -1886.107 | 0.305 | -4041.689 | 0.000 | 0.000 | 1948.050 | 1526.141 | 2368.647 | 983.194 | 0.000 | 29.515 | 116.853 | 0.000 | -683.295 | 0.000 | -165.358 | -229.758 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 21-SEP-20:00 | 0.00 | 0.00 | 0.00 | -29028.65 | 0.00 | 0.00 | 5183.81 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5498.98 |
RETAIL_1_FLR_1 | 03-OCT-13:30 | 0.00 | 0.00 | 0.00 | -4581.28 | 0.00 | 0.00 | 150.60 | 270.73 | 252.59 | 4082.54 | 0.00 | 76.58 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -251.76 |
RETAIL_2_FLR_1 | 15-JUN-18:40 | 0.00 | 0.00 | 0.00 | -2892.96 | 0.00 | 0.00 | 610.38 | 1003.22 | 752.15 | 0.00 | 0.00 | 42.94 | 484.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 15-JUN-19:50 | 0.00 | 0.00 | 0.00 | -3475.74 | 0.00 | 0.00 | 129.08 | 2386.66 | 839.45 | 0.00 | 0.00 | 90.11 | 30.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 15-JUN-18:17 | 0.00 | 0.00 | 0.00 | -1898.14 | 0.00 | 0.00 | 99.29 | 652.79 | 229.41 | 0.00 | 0.00 | 60.39 | 856.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 15-JUN-20:00 | 0.00 | 0.00 | 0.00 | -39548.77 | 0.00 | 0.00 | 408.86 | 453.60 | 44299.38 | 0.00 | 0.00 | 120.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5733.88 |
CAFE_FLR_1 | 22-OCT-12:00 | 0.00 | 0.00 | 0.00 | -15191.00 | 0.00 | 0.00 | 2968.36 | 853.81 | 406.43 | 12816.37 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2.33 | -1851.64 |
LOBBY_FLR_1 | 15-JUN-20:10 | 0.00 | 0.00 | 0.00 | -49893.85 | 0.00 | 0.00 | 23501.38 | 14644.43 | 9501.36 | 1027.40 | 0.00 | 607.11 | 612.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 17-APR-18:01 | 0.00 | -16868.04 | 0.00 | 0.00 | 0.00 | 0.00 | 335.50 | 1704.65 | 484.65 | 1528.03 | 0.00 | 0.00 | 13023.62 | 0.00 | -0.00 | 0.00 | -208.42 | 0.00 |
ROOM_2_FLR_3 | 17-APR-18:01 | 0.00 | -17413.97 | 0.00 | 0.00 | 0.00 | 0.00 | 280.90 | 1704.45 | 484.60 | 1411.90 | 0.00 | 0.00 | 13796.97 | 0.00 | -0.00 | 0.00 | -264.84 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-13:20 | 0.00 | -58863.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7547.28 | 2548.95 | 58789.61 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -92.97 | -9929.08 |
ROOM_4_MULT19_FLR_3 | 30-MAR-19:51 | 0.00 | -123670.03 | 0.00 | 0.00 | 0.00 | 0.00 | 6158.38 | 22876.81 | 12159.85 | 0.00 | 0.00 | 0.00 | 97195.96 | 0.00 | -12987.02 | 0.00 | -1733.95 | 0.00 |
ROOM_5_FLR_3 | 30-DEC-09:02 | 0.00 | -14987.73 | 0.00 | 0.00 | 0.00 | 0.00 | 130.71 | 1072.59 | 653.23 | 6864.93 | 0.00 | 0.00 | 6803.32 | 0.00 | -0.00 | 0.00 | -537.06 | 0.00 |
ROOM_6_FLR_3 | 28-APR-08:51 | 0.00 | -15383.12 | 0.00 | 0.00 | 0.00 | 0.00 | 71.66 | 842.65 | 452.99 | 7515.15 | 0.00 | 0.00 | 6600.40 | 0.00 | -0.00 | 0.00 | -99.73 | 0.00 |
CORRIDOR_FLR_3 | 15-JUN-18:25 | 0.00 | -13835.79 | 0.00 | 0.00 | 0.00 | 0.00 | 4080.34 | 6706.42 | 0.00 | 3385.91 | 0.00 | 316.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -652.94 |
ROOM_1_FLR_6 | 17-APR-18:01 | 0.00 | -4732.57 | 0.00 | 0.00 | 0.00 | 0.00 | 83.88 | 426.16 | 121.16 | 363.95 | 0.00 | 0.00 | 3789.20 | 0.00 | -0.00 | 0.00 | -51.79 | 0.00 |
ROOM_2_FLR_6 | 17-APR-18:01 | 0.00 | -4925.47 | 0.00 | 0.00 | 0.00 | 0.00 | 68.97 | 426.11 | 121.15 | 322.93 | 0.00 | 0.00 | 4053.42 | 0.00 | -0.00 | 0.00 | -67.12 | 0.00 |
ROOM_3_MULT9_FLR_6 | 26-JAN-16:12 | 0.00 | -22311.29 | 0.00 | 0.00 | 0.00 | 0.00 | 529.40 | 758.55 | 441.28 | 3629.70 | 0.00 | 0.00 | 17386.81 | 0.00 | -0.00 | 0.00 | -434.45 | 0.00 |
BANQUET_FLR_6 | 05-JUN-21:10 | 0.00 | 0.00 | 0.00 | -25121.75 | 0.00 | 0.00 | 15644.11 | 2998.74 | 6747.90 | 434.71 | 0.00 | 121.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -824.78 |
DINING_FLR_6 | 05-JUN-21:10 | 0.00 | 0.00 | 0.00 | -26324.50 | 0.00 | 0.00 | 15644.05 | 2998.74 | 6747.90 | 416.01 | 0.00 | 121.06 | 396.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 02-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31614.57 | 0.00 | 0.00 | 463.80 | 400.31 | 24375.41 | 2934.46 | 0.00 | 102.50 | 3338.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 03-JUL-12:50 | 0.00 | -10470.75 | 0.00 | 0.00 | 0.00 | 0.00 | 308.46 | 554.51 | 0.00 | 2372.42 | 0.00 | 151.15 | 7084.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-18:02 | 0.00 | -228267.63 | 0.00 | -207228.75 | 0.00 | 0.00 | 73658.00 | 107831.13 | 120597.93 | 52069.52 | 0.00 | 5720.67 | 75619.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 27-DEC-07:05 | 0.00 | 0.00 | 1093.59 | 0.00 | 0.00 | 0.00 | 357.99 | 541.46 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1430.38 | 0.00 | -286.33 | -709.35 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 27-DEC-06:00 | 0.00 | 0.00 | 287.51 | 0.00 | 0.00 | 0.00 | 151.76 | 163.20 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -144.07 | -534.87 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 26-DEC-09:02 | 10213.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.83 | 842.75 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1720.33 | 0.00 | -555.75 | -9338.29 |
ROOM_2_FLR_3 | 27-JAN-09:02 | 12482.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.00 | 842.65 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2359.90 | 0.00 | -564.56 | -10962.08 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 23-DEC-09:03 | 51611.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2651.27 | 12811.01 | 12159.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8547.48 | 0.00 | -2093.84 | -68592.34 |
ROOM_5_FLR_3 | 26-DEC-16:12 | 10277.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.23 | 536.29 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2531.40 | 0.00 | -485.08 | -8282.18 |
ROOM_6_FLR_3 | 26-DEC-16:12 | 10303.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.37 | 536.23 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2487.23 | 0.00 | -474.06 | -8368.28 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 27-JAN-09:02 | 3500.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 210.69 | 113.26 | 175.59 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -141.51 | -3885.72 |
ROOM_2_FLR_6 | 27-JAN-09:02 | 3519.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 210.66 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -568.76 | 0.00 | -140.59 | -3160.84 |
ROOM_3_MULT9_FLR_6 | 26-DEC-19:02 | 14320.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.21 | 2411.10 | 1068.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3054.93 | 0.00 | -571.36 | -15081.72 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 27-DEC-07:30 | 2290.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.33 | 1109.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2166.94 | 0.00 | -354.62 | -1610.83 |
Total Facility | 26-DEC-16:12 | -13880.73 | 98081.38 | 31.55 | -98081.38 | 0.00 | 0.00 | 58871.88 | 33804.24 | 74028.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63973.25 | 0.00 | -13062.96 | -75818.83 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_FLR_1 | 8.6677 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.6375 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_6 | 6.7774 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.7774 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_0 | 3.7745 | 0.0000 | 106.4990 | 1.0000 | Calculated from schedules | 0.8545 | 3.7745 | 0.2264 | 1.0000 | Not calculated | 0.8545 | 0.2264 | ||
PSZ_LAUNDRY | 4.4512 | 0.0000 | 8.4000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4512 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PSZ_CAFE | 2.1043 | 0.0000 | 142.3000 | 1.0000 | Calculated from schedules | 0.6764 | 2.1043 | 0.3214 | 1.0000 | Not calculated | 0.6764 | 0.3214 | ||
PSZ_KITCHEN | 3.0476 | 0.0000 | 22.2380 | 1.0000 | Calculated from schedules | 0.3674 | 3.0476 | 0.1205 | 1.0000 | Not calculated | 0.3674 | 0.1205 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_FLR_1 | 4.3339 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4608 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_6 | 3.3887 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1636 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_0 | 1.1324 | 0.0000 | 106.4990 | 1.0000 | Calculated from schedules | 0.8545 | 1.1324 | 1.0000 | 1.0000 | Not calculated | 0.8545 | 0.7546 | ||
PSZ_LAUNDRY | 4.4512 | 0.0000 | 8.4000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4512 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PSZ_CAFE | 2.1043 | 0.0000 | 142.3000 | 1.0000 | Calculated from schedules | 0.6764 | 2.1043 | 1.0000 | 1.0000 | Not calculated | 0.6764 | 0.3214 | ||
PSZ_KITCHEN | 3.0476 | 0.0000 | 22.2380 | 1.0000 | Calculated from schedules | 0.3674 | 3.0476 | 1.0000 | 1.0000 | Not calculated | 0.3674 | 0.1205 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV_FLR_0 | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.8545 | 1.0000 | 0.8545 | 1.000 | 0.8545 |
RETAIL_1_FLR_1 | VAV_FLR_1 | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV_FLR_1 | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | PSZ_CAFE | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.6764 | 1.0000 | 0.6764 | 1.000 | 0.6764 |
LOBBY_FLR_1 | VAV_FLR_1 | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV_FLR_6 | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.3674 | 1.0000 | 0.3674 | 1.000 | 0.3674 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_FLR_1 | 0.00 | 0.001240 | 1711.9288 | 0.0000 | 0.0000 | 0.0000 | |
VAV_FLR_6 | 0.00 | 0.003581 | 663.3149 | 0.0000 | 0.0000 | 0.0000 | |
VAV_FLR_0 | 0.000000 | 106.50 | 0.000432 | 1978.8302 | 0.8545 | 0.8545 | 0.8545 |
PSZ_LAUNDRY | 0.000000 | 8.40 | 0.000000 | 78.0395 | 0.0000 | 0.0000 | 0.0000 |
PSZ_CAFE | 0.000000 | 142.30 | 0.003581 | 188.8619 | 0.6764 | 0.6764 | 0.6764 |
PSZ_KITCHEN | 0.000000 | 22.24 | 0.003556 | 103.3045 | 0.3674 | 0.3674 | 0.3674 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV_FLR_0 | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 3.7745 | 3.7745 | 1.1324 | No | 0.8545 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5225 | 0.5225 | 0.1568 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3892 | 0.3892 | 0.1421 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4557 | 0.4557 | 0.1367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2434 | 0.2434 | 0.0896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4512 | 4.4512 | 4.4512 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | PSZ_CAFE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1043 | 2.1043 | 2.1043 | No | 0.6764 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0569 | 7.0569 | 2.9357 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3147 | 3.3147 | 1.5811 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4627 | 3.4627 | 1.5825 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0476 | 3.0476 | 3.0476 | No | 0.3674 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_FLR_1 | 8.6677 | 8.6375 | 8.6677 | 3.4608 | 0.0000 | 1.0000 |
VAV_FLR_6 | 6.7774 | 6.7774 | 6.7774 | 3.1636 | 0.0000 | 1.0000 |
VAV_FLR_0 | 3.7745 | 3.7745 | 3.7745 | 1.1324 | 0.8545 | 1.0000 |
PSZ_LAUNDRY | 4.4512 | 4.4512 | 4.4512 | 4.4512 | 0.0000 | 1.0000 |
PSZ_CAFE | 2.1043 | 2.1043 | 2.1043 | 2.1043 | 0.6764 | 1.0000 |
PSZ_KITCHEN | 3.0476 | 3.0476 | 3.0476 | 3.0476 | 0.3674 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV_FLR_0 | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 1.1324 | 1.1324 | 1.1324 | No | 0.8545 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2613 | 0.2613 | 0.1568 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1946 | 0.1946 | 0.1421 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2278 | 0.2278 | 0.1367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1217 | 0.1217 | 0.0896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4512 | 4.4512 | 4.4512 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | PSZ_CAFE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1043 | 2.1043 | 2.1043 | No | 0.6764 | 0.8353 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5285 | 3.5285 | 2.9357 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6573 | 1.6573 | 1.5811 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7314 | 1.7314 | 1.5825 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0476 | 3.0476 | 3.0476 | No | 0.3674 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_FLR_1 | 4.3339 | 3.4608 | 3.4608 | 3.4608 | 0.0000 | 1.0000 |
VAV_FLR_6 | 3.3887 | 3.1636 | 3.1636 | 3.1636 | 0.0000 | 1.0000 |
VAV_FLR_0 | 1.1324 | 1.1324 | 1.1324 | 1.1324 | 0.8545 | 1.0000 |
PSZ_LAUNDRY | 4.4512 | 4.4512 | 4.4512 | 4.4512 | 0.0000 | 1.0000 |
PSZ_CAFE | 2.1043 | 2.1043 | 2.1043 | 2.1043 | 0.6764 | 1.0000 |
PSZ_KITCHEN | 3.0476 | 3.0476 | 3.0476 | 3.0476 | 0.3674 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 71.50 |
Number of hours not met | 71.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 11.12 | 16807.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 383.21 | 177761.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1538.61 | 196774.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1526.14 | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 322.39 | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 15.55 | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 11.51 | 365.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.24 | 1343.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1155.27 | 54998.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 2.81 | 678.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 2506.49 | 241650.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.82 | 1324.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.00 | 716.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1705.73 | 7092.93 |
Natural Gas | 1788.84 | 4689.66 |
Additional | 0.00 | 0.00 |
Total | 3494.57 | 11782.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 134.52 |
Space Heating | 0.00 |
Space Cooling | 135.62 |
Fans (All) | 101.83 |
Service Water Heating | 0.00 |
Receptacle Equipment | 146.48 |
Miscellaneous (All) | 625.19 |
Subtotal | 625.19 |
Natural Gas [MJ/m2] | |
Space Heating | 34.76 |
Service Water Heating | 220.93 |
Miscellaneous (All) | 413.36 |
Subtotal | 413.36 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.95 |
Space Heating | 3.35 |
Space Cooling | 13.06 |
Fans (All) | 9.80 |
Service Water Heating | 21.27 |
Receptacle Equipment | 29.29 |
Miscellaneous | 10.28 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 3061. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 3061. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 3061. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | RETAIL_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | RETAIL_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8659.50 | 100.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8718.33 | 41.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8659.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 100.50 | 0.00 | 0.00 | 0.00 |
Average | 8751.59 | 8.41 | 0.00 | 0.00 | 0.00 |
Sum | 192535.00 | 185.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4152.00 | 2.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4149.00 | 5.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 5.00 | 0.00 | 0.00 | 0.00 |
Average | 288886.73 | 0.32 | 0.00 | 0.00 | 0.00 |
Sum | 6355508.00 | 7.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8641.33 | 118.67 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8480.67 | 279.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8661.17 | 98.83 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8624.50 | 135.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8567.50 | 192.50 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8666.00 | 94.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8563.83 | 196.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 7162.83 | 1597.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8629.50 | 130.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8582.17 | 177.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8643.67 | 116.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8635.50 | 124.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 7332.00 | 1428.00 | 0.00 | 0.00 | 0.00 |
Min | 7162.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1597.17 | 0.00 | 0.00 | 0.00 |
Average | 8545.58 | 214.42 | 0.00 | 0.00 | 0.00 |
Sum | 188002.67 | 4717.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 527063.00 | 2268.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 36517.83 | 685.17 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 680922.17 | 29494.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2079473.00 | 35956.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4118.17 | 35.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4126.33 | 27.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4124.83 | 29.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 83351.00 | 17007.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4120.33 | 33.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1207130.33 | 38584.67 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1220423.00 | 25292.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 106148.50 | 2120.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 90174.83 | 15771.17 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2079473.00 | 38584.67 | 0.00 | 0.00 | 0.00 |
Average | 281282.24 | 7604.80 | 0.00 | 0.00 | 0.00 |
Sum | 6188209.33 | 167305.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394545E+11 | 24068.66 | 04-JAN-21:00 | 6.10 | -0.4 | 0.812400E+10 | 4837.19 | 03-JAN-22:10 | 6.10 | -0.4 |
February | 0.295798E+11 | 22451.33 | 03-FEB-07:00 | -5.6 | -7.5 | 0.724766E+10 | 4837.20 | 07-FEB-23:10 | 15.60 | 8.42 |
March | 0.279532E+11 | 20889.86 | 02-MAR-05:20 | -3.9 | -6.5 | 0.807029E+10 | 4837.12 | 14-MAR-21:10 | 13.62 | 5.68 |
April | 0.279451E+11 | 20044.93 | 21-APR-21:00 | 25.00 | 9.75 | 0.796193E+10 | 4837.34 | 25-APR-21:10 | 17.88 | 11.65 |
May | 0.317717E+11 | 21134.06 | 31-MAY-21:00 | 28.30 | 13.66 | 0.825013E+10 | 4837.34 | 22-MAY-23:19 | 28.30 | 13.66 |
June | 0.335306E+11 | 22218.41 | 16-JUN-21:00 | 32.80 | 14.71 | 0.799871E+10 | 4837.37 | 22-JUN-23:19 | 22.60 | 15.65 |
July | 0.416898E+11 | 25745.52 | 18-JUL-20:32 | 21.67 | 20.48 | 0.823284E+10 | 4837.39 | 31-JUL-04:49 | 21.78 | 17.84 |
August | 0.470644E+11 | 27174.99 | 08-AUG-20:00 | 27.20 | 18.82 | 0.826765E+10 | 4837.44 | 16-AUG-23:19 | 17.20 | 16.32 |
September | 0.498808E+11 | 29029.23 | 21-SEP-20:00 | 25.60 | 16.42 | 0.797742E+10 | 4837.44 | 15-SEP-04:00 | 25.60 | 16.42 |
October | 0.508222E+11 | 28847.98 | 05-OCT-20:00 | 23.90 | 16.65 | 0.823657E+10 | 4837.45 | 17-OCT-00:10 | 16.52 | 14.41 |
November | 0.471959E+11 | 28204.34 | 10-NOV-20:57 | 16.70 | 9.22 | 0.795916E+10 | 4837.42 | 02-NOV-21:30 | 16.70 | 9.22 |
December | 0.449850E+11 | 26610.22 | 01-DEC-21:00 | 6.70 | 2.22 | 0.813139E+10 | 4837.26 | 14-DEC-22:10 | 5.10 | 3.99 |
Annual Sum or Average | 0.471873E+12 | 0.964577E+11 | ||||||||
Minimum of Months | 0.279451E+11 | 20044.93 | -5.6 | -7.5 | 0.724766E+10 | 4837.12 | 5.10 | -0.4 | ||
Maximum of Months | 0.508222E+11 | 29029.23 | 32.80 | 20.48 | 0.826765E+10 | 4837.45 | 28.30 | 17.84 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268584E+10 | 3630.90 | 12-JAN-14:20 | 18.50 | 9.82 | 0.675331E+09 | 455.77 | 03-JAN-22:10 | 18.50 | 9.82 |
February | 0.275913E+10 | 3573.95 | 07-FEB-13:40 | 20.20 | 9.50 | 0.622937E+09 | 484.61 | 06-FEB-22:10 | 20.20 | 9.50 |
March | 0.313271E+10 | 3178.32 | 14-MAR-14:10 | 22.98 | 9.45 | 0.709159E+09 | 491.37 | 15-MAR-21:10 | 19.90 | 7.59 |
April | 0.392373E+10 | 3224.24 | 03-APR-14:10 | 26.70 | 11.67 | 0.733808E+09 | 491.84 | 28-APR-22:10 | 21.52 | 12.87 |
May | 0.460715E+10 | 3168.96 | 30-MAY-15:10 | 34.32 | 17.72 | 0.792155E+09 | 491.84 | 17-MAY-22:10 | 34.32 | 17.72 |
June | 0.529846E+10 | 3533.50 | 14-JUN-18:03 | 37.02 | 14.90 | 0.793425E+09 | 491.86 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.545689E+10 | 3515.29 | 26-JUL-15:10 | 36.60 | 20.09 | 0.819622E+09 | 491.85 | 05-JUL-22:10 | 36.60 | 20.09 |
August | 0.544356E+10 | 3606.10 | 29-AUG-13:30 | 31.40 | 19.83 | 0.816719E+09 | 491.87 | 22-AUG-00:10 | 31.40 | 19.83 |
September | 0.535702E+10 | 4376.83 | 19-SEP-13:30 | 33.35 | 16.80 | 0.770800E+09 | 491.84 | 06-SEP-21:10 | 33.35 | 16.80 |
October | 0.480657E+10 | 4580.89 | 03-OCT-13:30 | 31.70 | 19.34 | 0.761135E+09 | 491.84 | 05-OCT-21:49 | 22.88 | 16.22 |
November | 0.346498E+10 | 4023.60 | 09-NOV-13:10 | 22.88 | 12.16 | 0.679325E+09 | 491.81 | 09-NOV-22:19 | 18.17 | 10.78 |
December | 0.243935E+10 | 3158.58 | 16-DEC-13:30 | 14.45 | 3.99 | 0.666095E+09 | 447.84 | 15-DEC-22:10 | 14.45 | 3.99 |
Annual Sum or Average | 0.493754E+11 | 0.884051E+10 | ||||||||
Minimum of Months | 0.243935E+10 | 3158.58 | 14.45 | 3.99 | 0.622937E+09 | 447.84 | 14.45 | 3.99 | ||
Maximum of Months | 0.545689E+10 | 4580.89 | 37.02 | 20.09 | 0.819622E+09 | 491.87 | 36.60 | 20.09 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296176E+10 | 1724.33 | 12-JAN-21:10 | 12.43 | 7.05 | 0.881290E+09 | 569.53 | 31-JAN-23:10 | 8.12 | 2.56 |
February | 0.277565E+10 | 1906.49 | 21-FEB-20:30 | 16.10 | 5.05 | 0.811027E+09 | 569.55 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.323278E+10 | 2129.17 | 14-MAR-19:10 | 20.27 | 8.17 | 0.914813E+09 | 569.55 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.357745E+10 | 2508.78 | 28-APR-19:10 | 26.42 | 13.25 | 0.913958E+09 | 569.55 | 28-APR-22:10 | 21.52 | 12.87 |
May | 0.404867E+10 | 2691.12 | 19-MAY-19:20 | 31.83 | 14.82 | 0.961139E+09 | 569.58 | 18-MAY-00:10 | 31.83 | 14.82 |
June | 0.427962E+10 | 2892.68 | 15-JUN-18:40 | 35.37 | 14.55 | 0.939961E+09 | 569.57 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.438011E+10 | 2863.81 | 25-JUL-18:40 | 34.07 | 19.43 | 0.967817E+09 | 569.55 | 05-JUL-22:10 | 34.07 | 19.43 |
August | 0.430519E+10 | 2815.83 | 04-AUG-19:20 | 34.03 | 18.20 | 0.970172E+09 | 569.58 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.402488E+10 | 2677.26 | 01-SEP-18:20 | 30.57 | 18.02 | 0.931774E+09 | 569.56 | 06-SEP-21:10 | 23.72 | 16.97 |
October | 0.373937E+10 | 2507.94 | 04-OCT-19:10 | 27.52 | 18.59 | 0.945919E+09 | 569.57 | 10-OCT-21:10 | 14.13 | 9.16 |
November | 0.311453E+10 | 2079.78 | 09-NOV-21:10 | 19.82 | 11.24 | 0.879824E+09 | 569.55 | 08-NOV-23:10 | 19.82 | 11.24 |
December | 0.288128E+10 | 1533.45 | 15-DEC-22:00 | 14.40 | 4.62 | 0.868690E+09 | 569.52 | 05-DEC-22:19 | 14.40 | 4.62 |
Annual Sum or Average | 0.433213E+11 | 0.109864E+11 | ||||||||
Minimum of Months | 0.277565E+10 | 1533.45 | 12.43 | 4.62 | 0.811027E+09 | 569.52 | 8.12 | 2.56 | ||
Maximum of Months | 0.438011E+10 | 2892.68 | 35.37 | 19.43 | 0.970172E+09 | 569.58 | 34.07 | 19.43 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263239E+10 | 1208.57 | 12-JAN-22:00 | 10.60 | 5.73 | 0.176813E+09 | 119.86 | 03-JAN-22:10 | 10.60 | 5.73 |
February | 0.248371E+10 | 1605.50 | 22-FEB-20:55 | 16.10 | 5.55 | 0.164308E+09 | 120.45 | 23-FEB-22:10 | 11.93 | 4.94 |
March | 0.290195E+10 | 1939.69 | 16-MAR-20:00 | 17.20 | 5.94 | 0.188135E+09 | 120.45 | 22-MAR-21:10 | 11.52 | 4.66 |
April | 0.341794E+10 | 2776.49 | 21-APR-20:00 | 26.10 | 11.77 | 0.192208E+09 | 120.45 | 10-APR-21:10 | 26.10 | 11.77 |
May | 0.422341E+10 | 3161.30 | 19-MAY-19:50 | 31.28 | 14.64 | 0.203494E+09 | 120.46 | 18-MAY-00:10 | 31.28 | 14.64 |
June | 0.475235E+10 | 3475.49 | 15-JUN-19:50 | 34.08 | 14.10 | 0.198810E+09 | 120.46 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.487252E+10 | 3349.64 | 25-JUL-20:00 | 32.80 | 18.91 | 0.204681E+09 | 120.46 | 05-JUL-22:10 | 32.80 | 18.91 |
August | 0.461563E+10 | 3305.55 | 04-AUG-20:00 | 33.30 | 17.89 | 0.205224E+09 | 120.46 | 22-AUG-00:10 | 24.22 | 16.48 |
September | 0.406357E+10 | 2957.76 | 01-SEP-20:00 | 27.20 | 17.85 | 0.196907E+09 | 120.46 | 06-SEP-21:19 | 23.53 | 16.95 |
October | 0.353479E+10 | 2831.63 | 04-OCT-20:00 | 26.10 | 17.91 | 0.198723E+09 | 120.46 | 10-OCT-21:19 | 13.87 | 9.12 |
November | 0.279163E+10 | 2073.40 | 09-NOV-21:00 | 20.00 | 11.27 | 0.180159E+09 | 120.45 | 24-NOV-22:19 | 7.60 | 1.71 |
December | 0.256213E+10 | 1171.66 | 15-DEC-22:10 | 14.32 | 4.61 | 0.173554E+09 | 117.96 | 15-DEC-22:10 | 14.32 | 4.61 |
Annual Sum or Average | 0.428520E+11 | 0.228302E+10 | ||||||||
Minimum of Months | 0.248371E+10 | 1171.66 | 10.60 | 4.61 | 0.164308E+09 | 117.96 | 7.60 | 1.71 | ||
Maximum of Months | 0.487252E+10 | 3475.49 | 34.08 | 18.91 | 0.205224E+09 | 120.46 | 32.80 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120319E+10 | 636.95 | 12-JAN-21:20 | 12.07 | 6.79 | 0.119838E+09 | 78.66 | 03-JAN-22:10 | 12.07 | 6.79 |
February | 0.123477E+10 | 681.56 | 07-FEB-21:43 | 15.10 | 7.52 | 0.111489E+09 | 82.49 | 07-FEB-22:10 | 15.10 | 7.63 |
March | 0.154182E+10 | 719.31 | 15-MAR-21:00 | 20.00 | 7.66 | 0.128378E+09 | 86.03 | 15-MAR-21:10 | 19.90 | 7.59 |
April | 0.181269E+10 | 1072.38 | 21-APR-18:03 | 29.95 | 11.64 | 0.138000E+09 | 92.66 | 28-APR-21:30 | 22.25 | 12.88 |
May | 0.224491E+10 | 1518.26 | 19-MAY-18:20 | 32.93 | 15.38 | 0.151804E+09 | 92.66 | 15-MAY-21:10 | 32.93 | 15.38 |
June | 0.266129E+10 | 1898.11 | 15-JUN-18:17 | 35.73 | 14.50 | 0.151158E+09 | 92.66 | 30-JUN-22:10 | 28.43 | 17.10 |
July | 0.269713E+10 | 1740.37 | 03-JUL-18:30 | 34.45 | 19.49 | 0.155763E+09 | 92.66 | 05-JUL-22:10 | 27.70 | 17.66 |
August | 0.246844E+10 | 1620.51 | 07-AUG-18:20 | 33.50 | 18.31 | 0.155142E+09 | 92.66 | 07-AUG-22:30 | 27.55 | 18.81 |
September | 0.210831E+10 | 1208.69 | 01-SEP-18:03 | 31.13 | 18.07 | 0.146658E+09 | 92.66 | 06-SEP-21:19 | 23.53 | 16.95 |
October | 0.187643E+10 | 1088.44 | 04-OCT-19:30 | 26.95 | 18.32 | 0.141784E+09 | 92.66 | 05-OCT-21:49 | 22.88 | 16.22 |
November | 0.144754E+10 | 737.15 | 09-NOV-21:20 | 19.63 | 11.21 | 0.122242E+09 | 87.07 | 09-NOV-22:10 | 18.53 | 10.92 |
December | 0.103333E+10 | 613.97 | 15-DEC-22:10 | 14.32 | 4.61 | 0.118782E+09 | 77.12 | 15-DEC-22:10 | 14.32 | 4.61 |
Annual Sum or Average | 0.223298E+11 | 0.164104E+10 | ||||||||
Minimum of Months | 0.103333E+10 | 613.97 | 12.07 | 4.61 | 0.111489E+09 | 77.12 | 12.07 | 4.61 | ||
Maximum of Months | 0.269713E+10 | 1898.11 | 35.73 | 19.49 | 0.155763E+09 | 92.66 | 32.93 | 18.81 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489856E+11 | 37772.34 | 03-JAN-21:00 | 14.40 | 6.79 | 0.649330E+09 | 381.52 | 26-JAN-05:00 | 1.70 | -1.3 |
February | 0.448543E+11 | 37981.64 | 22-FEB-20:53 | 16.10 | 5.55 | 0.587068E+09 | 381.53 | 07-FEB-22:10 | 16.10 | 5.55 |
March | 0.504195E+11 | 38300.72 | 15-MAR-20:00 | 18.90 | 6.98 | 0.652386E+09 | 381.52 | 15-MAR-21:19 | 19.80 | 7.53 |
April | 0.502521E+11 | 39003.71 | 19-APR-20:00 | 28.30 | 12.40 | 0.629505E+09 | 381.64 | 25-APR-21:10 | 17.88 | 11.65 |
May | 0.530502E+11 | 39260.61 | 19-MAY-20:00 | 31.10 | 14.57 | 0.650739E+09 | 381.71 | 21-MAY-23:30 | 21.40 | 15.51 |
June | 0.522979E+11 | 39547.68 | 15-JUN-20:00 | 33.90 | 14.00 | 0.630928E+09 | 381.73 | 30-JUN-00:40 | 21.87 | 16.06 |
July | 0.537379E+11 | 39480.69 | 25-JUL-20:00 | 32.80 | 18.91 | 0.649573E+09 | 409.71 | 20-JUL-21:10 | 32.80 | 18.91 |
August | 0.536414E+11 | 39491.63 | 04-AUG-20:00 | 33.30 | 17.89 | 0.652178E+09 | 391.83 | 01-AUG-21:10 | 33.30 | 17.89 |
September | 0.512293E+11 | 39077.50 | 01-SEP-20:00 | 27.20 | 17.85 | 0.629260E+09 | 381.76 | 15-SEP-23:00 | 21.10 | 16.71 |
October | 0.515976E+11 | 38881.83 | 04-OCT-20:00 | 26.10 | 17.91 | 0.649678E+09 | 381.76 | 03-OCT-23:10 | 26.10 | 17.91 |
November | 0.483758E+11 | 38216.35 | 09-NOV-21:00 | 20.00 | 11.27 | 0.628121E+09 | 381.58 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 0.485861E+11 | 37602.85 | 15-DEC-21:00 | 14.40 | 4.76 | 0.649331E+09 | 381.52 | 13-DEC-05:00 | 14.40 | 4.76 |
Annual Sum or Average | 0.607028E+12 | 0.765810E+10 | ||||||||
Minimum of Months | 0.448543E+11 | 37602.85 | 14.40 | 4.76 | 0.587068E+09 | 381.52 | 1.70 | -1.3 | ||
Maximum of Months | 0.537379E+11 | 39547.68 | 33.90 | 18.91 | 0.652386E+09 | 409.71 | 33.30 | 18.91 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190787E+11 | 12751.23 | 12-JAN-13:40 | 17.77 | 9.43 | 0.939140E+10 | 6461.17 | 31-JAN-22:10 | 9.73 | 2.42 |
February | 0.173778E+11 | 13141.08 | 20-FEB-13:00 | 21.10 | 8.39 | 0.891689E+10 | 6463.17 | 06-FEB-22:19 | 21.10 | 8.39 |
March | 0.188638E+11 | 12470.16 | 14-MAR-15:10 | 23.98 | 9.90 | 0.102569E+11 | 6463.18 | 15-MAR-21:19 | 19.80 | 7.53 |
April | 0.199880E+11 | 12415.76 | 01-APR-13:20 | 27.97 | 11.94 | 0.105046E+11 | 6464.13 | 18-APR-21:10 | 22.02 | 14.14 |
May | 0.222018E+11 | 12265.22 | 19-MAY-21:10 | 29.90 | 13.55 | 0.110186E+11 | 6464.48 | 22-MAY-23:00 | 22.20 | 15.41 |
June | 0.241691E+11 | 13050.81 | 14-JUN-18:05 | 37.02 | 14.90 | 0.106878E+11 | 6464.57 | 23-JUN-00:20 | 22.03 | 15.39 |
July | 0.250079E+11 | 12868.61 | 26-JUL-18:02 | 33.77 | 19.75 | 0.110009E+11 | 6464.56 | 28-JUL-04:19 | 23.70 | 17.41 |
August | 0.249615E+11 | 13033.43 | 07-AUG-21:10 | 31.25 | 17.07 | 0.110472E+11 | 6464.66 | 15-AUG-21:30 | 22.25 | 18.02 |
September | 0.242270E+11 | 14766.01 | 19-SEP-15:10 | 33.40 | 16.39 | 0.106523E+11 | 6464.63 | 15-SEP-21:00 | 33.40 | 16.39 |
October | 0.226932E+11 | 15188.28 | 22-OCT-12:00 | 23.90 | 13.84 | 0.109473E+11 | 6464.63 | 02-OCT-21:00 | 23.90 | 13.84 |
November | 0.200326E+11 | 14099.37 | 11-NOV-10:53 | 16.10 | 7.51 | 0.964559E+10 | 6463.40 | 09-NOV-22:10 | 16.10 | 7.51 |
December | 0.186476E+11 | 12507.06 | 16-DEC-13:30 | 14.45 | 3.99 | 0.914058E+10 | 6462.53 | 18-DEC-00:10 | 11.02 | 3.01 |
Annual Sum or Average | 0.257249E+12 | 0.123210E+12 | ||||||||
Minimum of Months | 0.173778E+11 | 12265.22 | 14.45 | 3.99 | 0.891689E+10 | 6461.17 | 9.73 | 2.42 | ||
Maximum of Months | 0.250079E+11 | 15188.28 | 37.02 | 19.75 | 0.110472E+11 | 6464.66 | 33.40 | 18.02 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.648403E+11 | 35773.93 | 12-JAN-21:10 | 12.43 | 7.05 | 0.308063E+11 | 19183.76 | 31-JAN-23:19 | 7.83 | 2.46 |
February | 0.603785E+11 | 37698.30 | 06-FEB-22:00 | 18.90 | 6.99 | 0.282388E+11 | 19186.20 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.687127E+11 | 39181.56 | 16-MAR-20:10 | 17.20 | 5.94 | 0.316628E+11 | 19186.21 | 14-MAR-21:19 | 17.20 | 5.94 |
April | 0.736147E+11 | 44971.09 | 19-APR-20:10 | 28.30 | 12.40 | 0.312427E+11 | 19189.05 | 17-APR-01:10 | 28.30 | 12.40 |
May | 0.817469E+11 | 47460.48 | 19-MAY-20:10 | 30.92 | 14.42 | 0.325614E+11 | 19186.17 | 17-MAY-22:10 | 30.92 | 14.42 |
June | 0.853437E+11 | 49889.12 | 15-JUN-20:10 | 33.80 | 13.95 | 0.316797E+11 | 19186.14 | 22-JUN-22:10 | 23.22 | 16.10 |
July | 0.879971E+11 | 49416.28 | 25-JUL-20:10 | 32.62 | 18.69 | 0.326054E+11 | 19186.14 | 21-JUL-22:10 | 32.62 | 18.69 |
August | 0.871774E+11 | 49314.02 | 04-AUG-20:10 | 33.12 | 17.96 | 0.327204E+11 | 19186.16 | 15-AUG-21:00 | 21.70 | 17.81 |
September | 0.824395E+11 | 46701.78 | 19-SEP-20:10 | 26.73 | 15.91 | 0.315608E+11 | 19186.21 | 26-SEP-22:10 | 17.52 | 10.69 |
October | 0.788594E+11 | 45727.77 | 04-OCT-20:10 | 26.02 | 17.88 | 0.323654E+11 | 19186.29 | 10-OCT-21:49 | 13.07 | 8.95 |
November | 0.674252E+11 | 41568.25 | 09-NOV-21:10 | 19.82 | 11.24 | 0.305395E+11 | 19186.19 | 08-NOV-23:10 | 19.82 | 11.24 |
December | 0.633269E+11 | 33750.04 | 15-DEC-22:00 | 14.40 | 4.62 | 0.304652E+11 | 19183.65 | 16-DEC-00:30 | 11.35 | 4.06 |
Annual Sum or Average | 0.901862E+12 | 0.376448E+12 | ||||||||
Minimum of Months | 0.603785E+11 | 33750.04 | 12.43 | 4.62 | 0.282388E+11 | 19183.65 | 7.83 | 2.46 | ||
Maximum of Months | 0.879971E+11 | 49889.12 | 33.80 | 18.69 | 0.327204E+11 | 19189.05 | 32.62 | 18.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613466E+09 | 4171.55 | 26-JAN-16:12 | 7.20 | -1.2 | 98023773.99 | 56.69 | 26-JAN-05:10 | 7.20 | -1.2 |
February | 0.761738E+09 | 4153.70 | 09-FEB-16:12 | 10.93 | 2.51 | 88949992.41 | 56.69 | 01-FEB-05:49 | 10.93 | 2.51 |
March | 0.114329E+10 | 4173.62 | 01-MAR-16:12 | 8.53 | 1.46 | 98855864.62 | 56.69 | 02-MAR-02:20 | -2.1 | -5.4 |
April | 0.188408E+10 | 4217.06 | 17-APR-18:01 | 14.13 | 8.88 | 96002576.29 | 56.69 | 17-APR-02:39 | 14.13 | 8.88 |
May | 0.250940E+10 | 4026.31 | 01-MAY-18:02 | 19.72 | 8.08 | 99502406.14 | 56.69 | 18-MAY-03:09 | 18.72 | 12.20 |
June | 0.293378E+10 | 3879.46 | 12-JUN-08:62 | 23.35 | 9.75 | 96444721.51 | 56.69 | 28-JUN-00:10 | 20.63 | 17.69 |
July | 0.294394E+10 | 3624.77 | 24-JUL-18:02 | 32.12 | 17.33 | 99568652.54 | 56.69 | 24-JUL-04:10 | 32.12 | 17.33 |
August | 0.279663E+10 | 3709.53 | 22-AUG-18:02 | 31.60 | 15.31 | 99637508.89 | 56.69 | 07-AUG-23:10 | 31.60 | 15.31 |
September | 0.253452E+10 | 4074.18 | 24-SEP-15:12 | 24.40 | 11.24 | 96260078.54 | 56.69 | 22-SEP-01:19 | 24.40 | 11.24 |
October | 0.196472E+10 | 4127.84 | 23-OCT-18:01 | 12.62 | 8.15 | 99271916.78 | 56.69 | 25-OCT-04:00 | 7.20 | 5.55 |
November | 0.101994E+10 | 4127.98 | 05-NOV-15:12 | 17.80 | 8.85 | 95472732.08 | 56.69 | 28-NOV-02:30 | 0.00 | -1.5 |
December | 0.512163E+09 | 4150.67 | 27-DEC-16:12 | 7.60 | 2.51 | 97821933.40 | 56.70 | 26-DEC-04:30 | 7.60 | 2.51 |
Annual Sum or Average | 0.216177E+11 | 0.116581E+10 | ||||||||
Minimum of Months | 0.512163E+09 | 3624.77 | 7.20 | -1.2 | 88949992.41 | 56.69 | -2.1 | -5.4 | ||
Maximum of Months | 0.294394E+10 | 4217.06 | 32.12 | 17.33 | 99637508.89 | 56.70 | 32.12 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237297E+09 | 4066.59 | 26-JAN-16:12 | 7.20 | -1.2 | 97314650.94 | 56.76 | 12-JAN-19:40 | 7.20 | -1.2 |
February | 0.319245E+09 | 4151.76 | 07-FEB-21:41 | 15.10 | 7.52 | 90998680.35 | 79.45 | 06-FEB-22:49 | 15.10 | 7.52 |
March | 0.593890E+09 | 4275.17 | 20-MAR-19:41 | 13.68 | 4.78 | 0.106084E+09 | 89.83 | 15-MAR-21:10 | 13.68 | 4.78 |
April | 0.149790E+10 | 4353.62 | 17-APR-18:01 | 14.13 | 8.88 | 0.103741E+09 | 94.01 | 07-APR-21:10 | 14.13 | 8.88 |
May | 0.232291E+10 | 4250.08 | 01-MAY-21:51 | 15.60 | 7.13 | 0.104506E+09 | 94.93 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.285581E+10 | 4096.19 | 07-JUN-06:51 | 26.10 | 13.99 | 99594944.07 | 93.57 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.282796E+10 | 3734.73 | 16-JUL-06:51 | 25.60 | 17.70 | 0.103205E+09 | 86.24 | 21-JUL-21:00 | 23.90 | 20.39 |
August | 0.254935E+10 | 4060.08 | 23-AUG-08:51 | 26.10 | 14.44 | 0.103984E+09 | 94.57 | 15-AUG-21:10 | 26.10 | 14.44 |
September | 0.204518E+10 | 4320.94 | 24-SEP-21:31 | 15.00 | 9.83 | 0.102875E+09 | 93.40 | 13-SEP-21:10 | 15.00 | 9.83 |
October | 0.120414E+10 | 4321.41 | 19-OCT-21:51 | 19.40 | 9.71 | 0.110914E+09 | 95.17 | 05-OCT-21:10 | 19.40 | 9.71 |
November | 0.443767E+09 | 4243.85 | 09-NOV-22:51 | 16.70 | 10.18 | 97781620.75 | 84.38 | 09-NOV-22:30 | 16.70 | 10.18 |
December | 0.167577E+09 | 4057.48 | 27-DEC-16:12 | 7.60 | 2.51 | 96728117.38 | 56.69 | 26-DEC-02:00 | 7.60 | 2.51 |
Annual Sum or Average | 0.170650E+11 | 0.121773E+10 | ||||||||
Minimum of Months | 0.167577E+09 | 3734.73 | 7.20 | -1.2 | 90998680.35 | 56.69 | 7.20 | -1.2 | ||
Maximum of Months | 0.285581E+10 | 4353.62 | 26.10 | 17.70 | 0.110914E+09 | 95.17 | 26.10 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422258E+09 | 704.67 | 12-JAN-14:20 | 18.50 | 9.82 | 0.00 | 0.00 | 01-JAN-00:10 | 18.50 | 9.82 |
February | 0.419765E+09 | 651.97 | 06-FEB-13:40 | 22.43 | 9.16 | 0.00 | 0.00 | 01-FEB-00:10 | 22.43 | 9.16 |
March | 0.424968E+09 | 541.26 | 14-MAR-13:30 | 22.50 | 9.10 | 0.00 | 0.00 | 01-MAR-00:10 | 22.50 | 9.10 |
April | 0.531599E+09 | 516.61 | 01-APR-13:30 | 28.05 | 11.99 | 0.00 | 0.00 | 01-APR-00:10 | 28.05 | 11.99 |
May | 0.623640E+09 | 460.09 | 19-MAY-20:20 | 30.73 | 14.26 | 0.00 | 0.00 | 01-MAY-00:10 | 30.73 | 14.26 |
June | 0.729746E+09 | 505.55 | 05-JUN-19:20 | 35.73 | 16.11 | 0.00 | 0.00 | 01-JUN-00:10 | 35.73 | 16.11 |
July | 0.768728E+09 | 524.50 | 02-JUL-19:10 | 35.32 | 16.46 | 0.00 | 0.00 | 01-JUL-00:10 | 35.32 | 16.46 |
August | 0.782873E+09 | 546.20 | 27-AUG-13:40 | 34.40 | 16.46 | 0.00 | 0.00 | 01-AUG-00:10 | 34.40 | 16.46 |
September | 0.812931E+09 | 676.01 | 19-SEP-13:30 | 33.35 | 16.80 | 0.00 | 0.00 | 01-SEP-00:10 | 33.35 | 16.80 |
October | 0.759971E+09 | 774.52 | 22-OCT-13:20 | 25.97 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 25.97 | 14.61 |
November | 0.559539E+09 | 717.43 | 09-NOV-12:40 | 22.23 | 11.70 | 0.00 | 0.00 | 01-NOV-00:10 | 22.23 | 11.70 |
December | 0.389124E+09 | 633.39 | 16-DEC-13:30 | 14.45 | 3.99 | 0.00 | 0.00 | 01-DEC-00:10 | 14.45 | 3.99 |
Annual Sum or Average | 0.722514E+10 | 0.00 | ||||||||
Minimum of Months | 0.389124E+09 | 460.09 | 14.45 | 3.99 | 0.00 | 0.00 | 14.45 | 3.99 | ||
Maximum of Months | 0.812931E+09 | 774.52 | 35.73 | 16.80 | 0.00 | 0.00 | 35.73 | 16.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263782E+09 | 1597.58 | 21-JAN-09:02 | 6.28 | 3.76 | 97375677.94 | 56.69 | 28-JAN-05:00 | -3.3 | -6.4 |
February | 0.295272E+09 | 1618.77 | 05-FEB-09:02 | 5.67 | 1.57 | 90089001.90 | 79.75 | 22-FEB-22:10 | 14.40 | 4.90 |
March | 0.416275E+09 | 1627.24 | 30-MAR-19:51 | 10.00 | 1.67 | 0.102589E+09 | 87.07 | 15-MAR-21:00 | 10.00 | 1.67 |
April | 0.687025E+09 | 1604.82 | 11-APR-08:62 | 6.88 | 1.77 | 0.101078E+09 | 87.86 | 25-APR-21:00 | 18.30 | 11.64 |
May | 0.949718E+09 | 1574.28 | 01-MAY-21:51 | 15.60 | 7.13 | 0.103461E+09 | 88.21 | 23-MAY-21:00 | 21.10 | 15.71 |
June | 0.112396E+10 | 1495.95 | 10-JUN-06:51 | 24.40 | 11.62 | 99153743.71 | 88.84 | 23-JUN-21:00 | 23.30 | 15.34 |
July | 0.114943E+10 | 1332.30 | 16-JUL-06:51 | 25.60 | 17.70 | 0.102725E+09 | 82.54 | 20-JUL-21:00 | 21.10 | 21.10 |
August | 0.103803E+10 | 1505.44 | 23-AUG-08:51 | 26.10 | 14.44 | 0.103454E+09 | 91.11 | 14-AUG-21:40 | 26.10 | 14.44 |
September | 0.841204E+09 | 1613.82 | 24-SEP-21:31 | 15.00 | 9.83 | 0.101792E+09 | 87.68 | 13-SEP-21:00 | 15.00 | 9.83 |
October | 0.625123E+09 | 1622.27 | 20-OCT-21:51 | 14.40 | 9.21 | 0.107013E+09 | 89.34 | 05-OCT-21:10 | 14.40 | 9.21 |
November | 0.346832E+09 | 1621.32 | 26-NOV-09:02 | 5.68 | 2.55 | 96650588.73 | 83.86 | 09-NOV-22:49 | 5.68 | 2.55 |
December | 0.219996E+09 | 1626.47 | 17-DEC-09:02 | 4.87 | -0.7 | 96949958.00 | 56.69 | 28-DEC-05:10 | -3.0 | -3.8 |
Annual Sum or Average | 0.795664E+10 | 0.120233E+10 | ||||||||
Minimum of Months | 0.219996E+09 | 1332.30 | 4.87 | -0.7 | 90089001.90 | 56.69 | -3.3 | -6.4 | ||
Maximum of Months | 0.114943E+10 | 1627.24 | 26.10 | 17.70 | 0.107013E+09 | 91.11 | 26.10 | 21.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.576548E+09 | 3729.68 | 07-JAN-09:02 | 2.77 | -1.5 | 98332389.48 | 56.69 | 09-JAN-05:00 | 2.80 | -1.4 |
February | 0.810879E+09 | 3741.99 | 09-FEB-09:02 | 2.38 | -1.5 | 89323319.43 | 56.69 | 09-FEB-02:20 | 2.38 | -1.5 |
March | 0.114771E+10 | 3727.84 | 01-MAR-09:02 | 3.48 | -0.5 | 99270582.06 | 56.69 | 02-MAR-00:30 | -0.3 | -4.2 |
April | 0.194503E+10 | 3694.83 | 11-APR-08:62 | 6.88 | 1.77 | 96330980.00 | 56.69 | 17-APR-02:30 | 16.95 | 12.70 |
May | 0.255387E+10 | 3612.98 | 12-MAY-08:62 | 18.68 | 9.91 | 99649474.77 | 56.69 | 18-MAY-03:09 | 18.72 | 12.20 |
June | 0.300384E+10 | 3553.44 | 10-JUN-08:62 | 25.18 | 12.93 | 96468153.23 | 56.69 | 28-JUN-00:10 | 20.63 | 17.69 |
July | 0.301097E+10 | 3231.42 | 11-JUL-08:61 | 27.48 | 17.81 | 99582858.81 | 56.69 | 24-JUL-04:10 | 22.80 | 18.88 |
August | 0.285128E+10 | 3452.83 | 23-AUG-08:62 | 24.27 | 13.78 | 99674250.61 | 56.69 | 07-AUG-23:10 | 24.27 | 13.78 |
September | 0.254576E+10 | 3555.66 | 11-SEP-08:62 | 21.57 | 11.25 | 96378437.16 | 56.69 | 19-SEP-04:10 | 17.62 | 13.58 |
October | 0.186108E+10 | 3612.27 | 31-OCT-08:62 | 15.37 | 7.32 | 99429700.09 | 56.69 | 25-OCT-04:00 | 15.37 | 7.32 |
November | 0.989184E+09 | 3722.98 | 16-NOV-09:02 | 6.38 | 3.44 | 95645795.13 | 56.69 | 27-NOV-05:10 | 3.30 | -1.2 |
December | 0.498573E+09 | 3747.06 | 30-DEC-09:02 | 1.05 | -1.3 | 98212258.66 | 56.69 | 27-DEC-05:10 | 1.05 | -1.3 |
Annual Sum or Average | 0.217947E+11 | 0.116830E+10 | ||||||||
Minimum of Months | 0.498573E+09 | 3231.42 | 1.05 | -1.5 | 89323319.43 | 56.69 | -0.3 | -4.2 | ||
Maximum of Months | 0.301097E+10 | 3747.06 | 27.48 | 17.81 | 99674250.61 | 56.69 | 24.27 | 18.88 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199712E+09 | 3654.08 | 30-JAN-09:02 | 4.45 | -0.5 | 97309890.31 | 56.69 | 28-JAN-05:00 | 4.45 | -0.5 |
February | 0.375783E+09 | 3686.79 | 09-FEB-09:02 | 2.38 | -1.5 | 90682577.11 | 77.55 | 06-FEB-22:40 | 2.38 | -1.5 |
March | 0.665203E+09 | 3709.26 | 30-MAR-19:51 | 10.00 | 1.67 | 0.103692E+09 | 84.98 | 15-MAR-21:40 | 10.00 | 1.67 |
April | 0.155674E+10 | 3845.79 | 28-APR-08:51 | 21.10 | 12.61 | 0.102675E+09 | 87.72 | 25-APR-21:10 | 21.10 | 12.61 |
May | 0.228546E+10 | 3807.52 | 27-MAY-08:32 | 22.23 | 13.98 | 0.105406E+09 | 89.28 | 23-MAY-21:10 | 22.23 | 13.98 |
June | 0.285570E+10 | 3699.29 | 02-JUN-07:52 | 25.00 | 11.78 | 0.100670E+09 | 91.68 | 23-JUN-21:10 | 23.30 | 15.34 |
July | 0.283202E+10 | 3461.01 | 16-JUL-06:51 | 25.60 | 17.70 | 0.104153E+09 | 84.83 | 20-JUL-21:00 | 21.10 | 21.10 |
August | 0.253708E+10 | 3697.44 | 23-AUG-08:32 | 25.37 | 14.19 | 0.104839E+09 | 92.67 | 11-AUG-21:10 | 25.37 | 14.19 |
September | 0.197553E+10 | 3842.11 | 30-SEP-08:51 | 20.00 | 10.63 | 0.103529E+09 | 90.02 | 07-SEP-21:10 | 20.00 | 10.63 |
October | 0.115766E+10 | 3837.56 | 20-OCT-08:51 | 18.30 | 9.71 | 0.107753E+09 | 92.43 | 05-OCT-21:10 | 18.30 | 9.71 |
November | 0.424793E+09 | 3783.38 | 10-NOV-09:51 | 19.40 | 12.21 | 97308234.37 | 82.02 | 09-NOV-22:30 | 19.40 | 12.21 |
December | 0.162586E+09 | 3654.27 | 07-DEC-09:02 | 4.37 | -0.4 | 96728337.41 | 56.70 | 27-DEC-05:10 | -3.8 | -4.9 |
Annual Sum or Average | 0.170283E+11 | 0.121475E+10 | ||||||||
Minimum of Months | 0.162586E+09 | 3461.01 | 2.38 | -1.5 | 90682577.11 | 56.69 | -3.8 | -4.9 | ||
Maximum of Months | 0.285570E+10 | 3845.79 | 25.60 | 17.70 | 0.107753E+09 | 92.67 | 25.37 | 21.10 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127615E+10 | 1812.87 | 12-JAN-15:10 | 18.90 | 10.04 | 0.161518E+10 | 951.86 | 26-JAN-02:20 | 5.00 | 2.44 |
February | 0.166852E+10 | 1904.42 | 21-FEB-16:13 | 22.60 | 8.05 | 0.146211E+10 | 951.85 | 16-FEB-04:30 | 22.60 | 8.05 |
March | 0.230809E+10 | 2159.16 | 16-MAR-18:03 | 19.82 | 7.14 | 0.162647E+10 | 951.85 | 02-MAR-01:10 | 19.82 | 7.14 |
April | 0.351040E+10 | 2680.13 | 19-APR-18:15 | 29.80 | 13.54 | 0.157043E+10 | 951.84 | 04-APR-22:10 | 29.80 | 13.54 |
May | 0.452327E+10 | 3115.06 | 19-MAY-18:15 | 32.93 | 15.38 | 0.162334E+10 | 951.84 | 01-MAY-22:10 | 32.93 | 15.38 |
June | 0.521947E+10 | 3458.94 | 15-JUN-18:25 | 35.55 | 14.53 | 0.157385E+10 | 951.84 | 22-JUN-22:10 | 23.22 | 16.10 |
July | 0.533578E+10 | 3317.75 | 26-JUL-18:15 | 33.13 | 19.73 | 0.161992E+10 | 951.84 | 20-JUL-22:10 | 33.13 | 19.73 |
August | 0.512421E+10 | 3205.28 | 07-AUG-18:15 | 33.50 | 18.31 | 0.162677E+10 | 951.84 | 01-AUG-22:10 | 33.50 | 18.31 |
September | 0.469493E+10 | 2945.70 | 19-SEP-18:03 | 31.23 | 16.53 | 0.156967E+10 | 951.84 | 08-SEP-22:10 | 31.23 | 16.53 |
October | 0.388553E+10 | 2849.14 | 05-OCT-15:10 | 30.68 | 17.34 | 0.162068E+10 | 951.84 | 10-OCT-21:49 | 13.07 | 8.95 |
November | 0.217697E+10 | 2248.64 | 03-NOV-15:10 | 23.40 | 13.55 | 0.156498E+10 | 951.86 | 29-NOV-01:49 | 7.88 | 3.72 |
December | 0.101458E+10 | 1517.78 | 16-DEC-14:20 | 15.00 | 4.28 | 0.160891E+10 | 951.85 | 12-DEC-03:30 | 15.00 | 4.28 |
Annual Sum or Average | 0.407379E+11 | 0.190823E+11 | ||||||||
Minimum of Months | 0.101458E+10 | 1517.78 | 15.00 | 4.28 | 0.146211E+10 | 951.84 | 5.00 | 2.44 | ||
Maximum of Months | 0.533578E+10 | 3458.94 | 35.55 | 19.73 | 0.162677E+10 | 951.86 | 33.50 | 19.73 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400749E+09 | 4619.43 | 22-JAN-16:12 | 12.93 | 7.06 | 96987330.61 | 56.70 | 28-JAN-05:00 | -3.3 | -6.4 |
February | 0.568327E+09 | 4614.02 | 09-FEB-16:12 | 10.93 | 2.51 | 88293190.30 | 56.70 | 03-FEB-05:10 | 10.93 | 2.51 |
March | 0.959404E+09 | 4623.68 | 17-MAR-15:12 | 13.50 | 4.20 | 98378036.51 | 56.86 | 13-MAR-23:40 | 13.50 | 4.20 |
April | 0.184901E+10 | 4732.62 | 17-APR-18:01 | 14.13 | 8.88 | 95790361.10 | 56.69 | 11-APR-04:00 | 14.13 | 8.88 |
May | 0.262259E+10 | 4498.10 | 01-MAY-18:02 | 19.72 | 8.08 | 99420839.22 | 56.69 | 06-MAY-04:40 | 11.50 | 2.83 |
June | 0.326123E+10 | 4331.66 | 12-JUN-08:62 | 23.35 | 9.75 | 96428992.70 | 56.69 | 28-JUN-00:10 | 20.63 | 17.69 |
July | 0.326967E+10 | 4108.64 | 24-JUL-18:02 | 32.12 | 17.33 | 99556792.33 | 56.69 | 24-JUL-04:10 | 32.12 | 17.33 |
August | 0.304587E+10 | 4220.13 | 15-AUG-15:12 | 24.60 | 17.24 | 99597079.38 | 56.69 | 07-AUG-23:10 | 24.60 | 17.24 |
September | 0.265618E+10 | 4577.48 | 24-SEP-15:12 | 24.40 | 11.24 | 96156650.29 | 57.06 | 30-SEP-02:00 | 11.70 | 7.16 |
October | 0.182985E+10 | 4627.09 | 24-OCT-15:12 | 17.97 | 10.28 | 98966500.89 | 57.17 | 23-OCT-04:49 | 17.97 | 10.28 |
November | 0.813947E+09 | 4621.85 | 05-NOV-15:12 | 17.80 | 8.85 | 94788040.74 | 57.31 | 09-NOV-04:00 | 13.90 | 6.30 |
December | 0.307633E+09 | 4592.44 | 27-DEC-16:12 | 7.60 | 2.51 | 96747756.66 | 56.70 | 27-DEC-05:40 | 7.60 | 2.51 |
Annual Sum or Average | 0.215845E+11 | 0.116111E+10 | ||||||||
Minimum of Months | 0.307633E+09 | 4108.64 | 7.60 | 2.51 | 88293190.30 | 56.69 | -3.3 | -6.4 | ||
Maximum of Months | 0.326967E+10 | 4732.62 | 32.12 | 17.33 | 99597079.38 | 57.31 | 32.12 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108497E+09 | 4476.82 | 27-JAN-16:12 | 9.60 | 0.88 | 95979024.75 | 56.70 | 28-JAN-05:00 | -3.3 | -6.4 |
February | 0.180328E+09 | 4619.79 | 20-FEB-21:11 | 14.33 | 5.02 | 90044359.80 | 76.01 | 06-FEB-22:49 | 14.33 | 5.02 |
March | 0.433634E+09 | 4785.55 | 20-MAR-19:41 | 13.68 | 4.78 | 0.105560E+09 | 90.25 | 16-MAR-21:10 | 13.68 | 4.78 |
April | 0.149279E+10 | 4925.57 | 17-APR-18:01 | 14.13 | 8.88 | 0.103611E+09 | 96.32 | 07-APR-21:10 | 14.13 | 8.88 |
May | 0.247759E+10 | 4762.45 | 01-MAY-21:51 | 15.60 | 7.13 | 0.104181E+09 | 95.45 | 23-MAY-21:10 | 22.02 | 16.25 |
June | 0.321368E+10 | 4569.19 | 07-JUN-06:51 | 26.10 | 13.99 | 99359050.19 | 94.22 | 23-JUN-21:19 | 23.30 | 15.34 |
July | 0.318481E+10 | 4090.11 | 24-JUL-18:02 | 32.12 | 17.33 | 0.103016E+09 | 86.13 | 21-JUL-21:00 | 32.12 | 17.33 |
August | 0.283238E+10 | 4590.04 | 23-AUG-08:51 | 26.10 | 14.44 | 0.103711E+09 | 95.31 | 15-AUG-21:10 | 26.10 | 14.44 |
September | 0.220663E+10 | 4820.11 | 26-SEP-21:51 | 17.80 | 10.65 | 0.102441E+09 | 93.44 | 13-SEP-21:10 | 17.80 | 10.65 |
October | 0.110274E+10 | 4816.21 | 19-OCT-21:51 | 19.40 | 9.71 | 0.110788E+09 | 95.61 | 05-OCT-21:10 | 19.40 | 9.71 |
November | 0.278953E+09 | 4738.69 | 09-NOV-22:51 | 16.70 | 10.18 | 96883999.17 | 82.97 | 09-NOV-22:40 | 16.70 | 10.18 |
December | 61386089.57 | 4467.84 | 07-DEC-17:01 | 13.80 | 5.73 | 95341102.12 | 56.70 | 28-DEC-05:10 | -3.0 | -3.8 |
Annual Sum or Average | 0.175734E+11 | 0.121092E+10 | ||||||||
Minimum of Months | 61386089.57 | 4090.11 | 9.60 | 0.88 | 90044359.80 | 56.70 | -3.3 | -6.4 | ||
Maximum of Months | 0.321368E+10 | 4925.57 | 32.12 | 17.33 | 0.110788E+09 | 96.32 | 32.12 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.696772E+09 | 2479.09 | 26-JAN-16:12 | 7.20 | -1.2 | 98356961.15 | 56.69 | 28-JAN-05:00 | -3.3 | -6.4 |
February | 0.715007E+09 | 2459.21 | 02-FEB-16:12 | 10.60 | 1.90 | 89154657.47 | 56.69 | 03-FEB-05:10 | -3.8 | -6.3 |
March | 0.762054E+09 | 2452.28 | 01-MAR-16:12 | 8.53 | 1.46 | 98846358.45 | 56.70 | 02-MAR-05:00 | -3.9 | -6.5 |
April | 0.108922E+10 | 2377.72 | 17-APR-18:01 | 14.13 | 8.88 | 95899775.86 | 56.69 | 12-APR-04:00 | 14.13 | 8.88 |
May | 0.137052E+10 | 2316.89 | 06-MAY-08:62 | 17.48 | 6.46 | 99439585.07 | 56.69 | 18-MAY-03:09 | 18.72 | 12.20 |
June | 0.168819E+10 | 2269.62 | 10-JUN-08:62 | 25.18 | 12.93 | 96428078.22 | 56.69 | 28-JUN-00:10 | 20.63 | 17.69 |
July | 0.175867E+10 | 2059.26 | 05-JUL-18:02 | 33.90 | 16.02 | 99560019.86 | 56.69 | 24-JUL-04:10 | 22.80 | 18.88 |
August | 0.173295E+10 | 2179.30 | 23-AUG-08:62 | 24.27 | 13.78 | 99612220.26 | 56.69 | 07-AUG-23:10 | 24.27 | 13.78 |
September | 0.167765E+10 | 2365.70 | 24-SEP-15:12 | 24.40 | 11.24 | 96228215.24 | 56.69 | 22-SEP-01:10 | 24.40 | 11.24 |
October | 0.142353E+10 | 2406.03 | 24-OCT-15:12 | 17.97 | 10.28 | 99258106.10 | 56.69 | 25-OCT-04:00 | 7.20 | 5.55 |
November | 0.947622E+09 | 2451.35 | 17-NOV-09:02 | 5.55 | 1.49 | 95688879.65 | 56.69 | 28-NOV-05:10 | -0.3 | -1.6 |
December | 0.651695E+09 | 2476.57 | 27-DEC-16:12 | 7.60 | 2.51 | 98337336.91 | 56.70 | 27-DEC-04:00 | 7.60 | 2.51 |
Annual Sum or Average | 0.145139E+11 | 0.116681E+10 | ||||||||
Minimum of Months | 0.651695E+09 | 2059.26 | 5.55 | -1.2 | 89154657.47 | 56.69 | -3.9 | -6.5 | ||
Maximum of Months | 0.175867E+10 | 2479.09 | 33.90 | 16.02 | 99612220.26 | 56.70 | 24.40 | 18.88 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347265E+11 | 18466.08 | 12-JAN-22:10 | 10.03 | 5.38 | 0.182796E+11 | 11346.13 | 30-JAN-00:10 | 4.22 | -0.7 |
February | 0.326858E+11 | 19988.96 | 06-FEB-22:10 | 18.62 | 6.93 | 0.167910E+11 | 11349.09 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.380562E+11 | 21096.13 | 15-MAR-21:52 | 19.40 | 7.29 | 0.189424E+11 | 11349.11 | 14-MAR-21:19 | 19.40 | 7.29 |
April | 0.412780E+11 | 23546.74 | 19-APR-21:10 | 28.12 | 12.29 | 0.185932E+11 | 11349.56 | 17-APR-00:00 | 28.12 | 12.29 |
May | 0.461590E+11 | 24403.71 | 19-MAY-21:10 | 29.90 | 13.55 | 0.193181E+11 | 11349.10 | 17-MAY-22:10 | 29.90 | 13.55 |
June | 0.481893E+11 | 25116.86 | 05-JUN-21:10 | 32.75 | 15.06 | 0.187585E+11 | 11349.09 | 23-JUN-22:10 | 23.40 | 15.27 |
July | 0.494647E+11 | 25011.74 | 25-JUL-21:10 | 31.42 | 17.57 | 0.193050E+11 | 11349.07 | 21-JUL-22:10 | 31.42 | 17.57 |
August | 0.481499E+11 | 25091.85 | 07-AUG-21:10 | 31.25 | 17.07 | 0.193773E+11 | 11349.10 | 31-AUG-22:10 | 23.43 | 16.88 |
September | 0.442077E+11 | 23529.47 | 12-SEP-21:10 | 26.52 | 16.78 | 0.186738E+11 | 11349.17 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.414712E+11 | 22967.34 | 04-OCT-21:10 | 25.32 | 17.67 | 0.191399E+11 | 11349.11 | 10-OCT-21:49 | 13.07 | 8.95 |
November | 0.354391E+11 | 20871.27 | 09-NOV-22:10 | 18.53 | 10.92 | 0.180192E+11 | 11349.09 | 08-NOV-23:10 | 18.53 | 10.92 |
December | 0.337984E+11 | 18505.43 | 15-DEC-23:00 | 13.90 | 4.56 | 0.180538E+11 | 11345.29 | 16-DEC-00:30 | 11.35 | 4.06 |
Annual Sum or Average | 0.493626E+12 | 0.223252E+12 | ||||||||
Minimum of Months | 0.326858E+11 | 18466.08 | 10.03 | 4.56 | 0.167910E+11 | 11345.29 | 4.22 | -0.7 | ||
Maximum of Months | 0.494647E+11 | 25116.86 | 32.75 | 17.67 | 0.193773E+11 | 11349.56 | 31.42 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367627E+11 | 19921.01 | 03-JAN-22:10 | 12.43 | 6.06 | 0.186755E+11 | 11346.25 | 30-JAN-00:10 | 4.22 | -0.7 |
February | 0.345943E+11 | 21423.30 | 06-FEB-22:10 | 18.62 | 6.93 | 0.170610E+11 | 11349.10 | 22-FEB-22:19 | 14.40 | 4.92 |
March | 0.403101E+11 | 22374.13 | 15-MAR-21:10 | 19.90 | 7.59 | 0.191479E+11 | 11349.11 | 14-MAR-21:19 | 19.90 | 7.59 |
April | 0.437271E+11 | 24801.42 | 19-APR-21:10 | 28.12 | 12.29 | 0.186637E+11 | 11349.72 | 17-APR-00:00 | 28.12 | 12.29 |
May | 0.488335E+11 | 25622.23 | 19-MAY-21:10 | 29.90 | 13.55 | 0.193421E+11 | 11349.10 | 17-MAY-22:10 | 29.90 | 13.55 |
June | 0.508635E+11 | 26319.24 | 05-JUN-21:10 | 32.75 | 15.06 | 0.187611E+11 | 11349.09 | 23-JUN-22:10 | 23.40 | 15.27 |
July | 0.522109E+11 | 26210.47 | 25-JUL-21:10 | 31.42 | 17.57 | 0.193090E+11 | 11349.07 | 21-JUL-22:10 | 31.42 | 17.57 |
August | 0.508448E+11 | 26280.43 | 07-AUG-21:10 | 31.25 | 17.07 | 0.193879E+11 | 11349.10 | 31-AUG-22:10 | 23.43 | 16.88 |
September | 0.467342E+11 | 24748.35 | 12-SEP-21:10 | 26.52 | 16.78 | 0.187008E+11 | 11349.17 | 28-SEP-22:10 | 24.40 | 12.24 |
October | 0.438364E+11 | 24175.22 | 04-OCT-21:10 | 25.32 | 17.67 | 0.192291E+11 | 11349.11 | 10-OCT-21:49 | 13.07 | 8.95 |
November | 0.374502E+11 | 22165.21 | 09-NOV-22:10 | 18.53 | 10.92 | 0.182922E+11 | 11349.09 | 08-NOV-23:10 | 18.53 | 10.92 |
December | 0.358866E+11 | 20014.07 | 15-DEC-22:10 | 14.32 | 4.61 | 0.185110E+11 | 11345.45 | 16-DEC-00:30 | 11.35 | 4.06 |
Annual Sum or Average | 0.522054E+12 | 0.225081E+12 | ||||||||
Minimum of Months | 0.345943E+11 | 19921.01 | 12.43 | 4.61 | 0.170610E+11 | 11345.45 | 4.22 | -0.7 | ||
Maximum of Months | 0.522109E+11 | 26319.24 | 32.75 | 17.67 | 0.193879E+11 | 11349.72 | 31.42 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482370E+11 | 27427.49 | 29-JAN-11:50 | 11.60 | 4.50 | 0.188675E+11 | 11319.21 | 21-JAN-18:10 | 11.60 | 4.50 |
February | 0.447628E+11 | 28761.01 | 19-FEB-11:40 | 19.03 | 7.40 | 0.170434E+11 | 11319.95 | 18-FEB-18:00 | 19.03 | 7.40 |
March | 0.508852E+11 | 29066.31 | 19-MAR-10:40 | 18.67 | 7.01 | 0.188761E+11 | 11319.96 | 04-MAR-18:40 | 18.67 | 7.01 |
April | 0.525338E+11 | 30718.66 | 30-APR-10:50 | 24.53 | 12.98 | 0.182630E+11 | 11320.09 | 29-APR-17:49 | 24.53 | 12.98 |
May | 0.564685E+11 | 31035.26 | 21-MAY-10:50 | 30.03 | 14.61 | 0.188729E+11 | 11320.12 | 27-MAY-17:00 | 30.00 | 16.23 |
June | 0.567690E+11 | 31380.98 | 18-JUN-10:50 | 32.62 | 16.28 | 0.182674E+11 | 11320.17 | 03-JUN-17:00 | 32.62 | 16.28 |
July | 0.584510E+11 | 31632.33 | 02-JUL-10:40 | 32.23 | 20.13 | 0.188698E+11 | 11320.14 | 08-JUL-17:00 | 25.00 | 20.65 |
August | 0.577644E+11 | 31356.97 | 06-AUG-10:50 | 31.93 | 18.13 | 0.188768E+11 | 11320.11 | 12-AUG-17:00 | 33.30 | 18.73 |
September | 0.548218E+11 | 30988.52 | 17-SEP-10:50 | 30.03 | 15.56 | 0.182628E+11 | 11320.16 | 09-SEP-17:49 | 30.03 | 15.56 |
October | 0.535364E+11 | 30702.22 | 01-OCT-10:50 | 27.23 | 14.39 | 0.188696E+11 | 11320.21 | 07-OCT-17:49 | 17.98 | 13.46 |
November | 0.482737E+11 | 28223.45 | 03-NOV-10:50 | 17.43 | 12.82 | 0.182585E+11 | 11319.94 | 18-NOV-18:10 | 14.45 | 4.06 |
December | 0.476045E+11 | 27216.93 | 10-DEC-11:50 | 16.32 | 7.64 | 0.188675E+11 | 11319.24 | 02-DEC-18:10 | 16.32 | 7.64 |
Annual Sum or Average | 0.630108E+12 | 0.222195E+12 | ||||||||
Minimum of Months | 0.447628E+11 | 27216.93 | 11.60 | 4.50 | 0.170434E+11 | 11319.21 | 11.60 | 4.06 | ||
Maximum of Months | 0.584510E+11 | 31632.33 | 32.62 | 20.13 | 0.188768E+11 | 11320.21 | 33.30 | 20.65 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.810630E+09 | 4747.89 | 12-JAN-14:30 | 18.60 | 9.87 | 0.156703E+10 | 1007.40 | 20-JAN-22:10 | 10.40 | 4.96 |
February | 0.181785E+10 | 6124.10 | 22-FEB-13:50 | 21.52 | 7.85 | 0.146615E+10 | 1007.40 | 13-FEB-00:30 | 21.52 | 7.85 |
March | 0.339186E+10 | 6449.51 | 14-MAR-15:10 | 23.98 | 9.90 | 0.167050E+10 | 1007.40 | 31-MAR-23:30 | 11.30 | 2.42 |
April | 0.768352E+10 | 8640.26 | 30-APR-13:00 | 29.40 | 12.28 | 0.165470E+10 | 1007.40 | 12-APR-23:00 | 29.40 | 12.28 |
May | 0.111037E+11 | 9059.48 | 30-MAY-14:10 | 34.40 | 17.53 | 0.171804E+10 | 1007.40 | 08-MAY-04:10 | 34.40 | 17.53 |
June | 0.142646E+11 | 9724.98 | 05-JUN-15:10 | 36.88 | 17.24 | 0.166573E+10 | 1007.39 | 22-JUN-22:10 | 23.22 | 16.10 |
July | 0.145961E+11 | 10470.71 | 03-JUL-12:50 | 36.52 | 18.58 | 0.171446E+10 | 1007.39 | 20-JUL-22:10 | 21.10 | 21.10 |
August | 0.135920E+11 | 10160.23 | 08-AUG-13:30 | 33.85 | 18.83 | 0.172172E+10 | 1007.39 | 14-AUG-22:10 | 22.12 | 18.68 |
September | 0.114964E+11 | 10053.47 | 15-SEP-13:00 | 32.80 | 18.37 | 0.166099E+10 | 1007.40 | 25-SEP-02:39 | 11.30 | 9.30 |
October | 0.760802E+10 | 9514.15 | 03-OCT-13:40 | 32.07 | 19.44 | 0.171219E+10 | 1007.41 | 16-OCT-02:49 | 14.08 | 12.23 |
November | 0.282014E+10 | 6420.45 | 03-NOV-14:10 | 22.88 | 13.55 | 0.157829E+10 | 1007.40 | 01-NOV-02:00 | 22.88 | 13.55 |
December | 0.403169E+09 | 3283.38 | 16-DEC-13:50 | 14.82 | 4.21 | 0.150295E+10 | 1007.39 | 16-DEC-00:10 | 14.82 | 4.21 |
Annual Sum or Average | 0.895880E+11 | 0.196328E+11 | ||||||||
Minimum of Months | 0.403169E+09 | 3283.38 | 14.82 | 4.21 | 0.146615E+10 | 1007.39 | 10.40 | 2.42 | ||
Maximum of Months | 0.145961E+11 | 10470.71 | 36.88 | 19.44 | 0.172172E+10 | 1007.41 | 34.40 | 21.10 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45739860.27 | 807.10 | 28-JAN-07:05 | -2.9 |
February | 39456688.02 | 812.89 | 03-FEB-07:05 | -5.1 |
March | 19118411.31 | 683.37 | 02-MAR-05:00 | -3.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 18103015.51 | 637.10 | 28-NOV-05:00 | -0.6 |
December | 0.141523E+09 | 1093.64 | 27-DEC-07:05 | -4.3 |
Annual Sum or Average | 0.263941E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.141523E+09 | 1093.64 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6750045.45 | 283.03 | 28-JAN-06:00 | -3.3 |
February | 5882110.79 | 227.90 | 03-FEB-05:00 | -3.9 |
March | 1958373.54 | 185.83 | 02-MAR-05:00 | -3.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 1314990.32 | 157.78 | 28-NOV-05:00 | -0.6 |
December | 25468519.92 | 287.50 | 27-DEC-06:00 | -3.3 |
Annual Sum or Average | 41374040.01 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 25468519.92 | 287.50 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181287E+09 | 1494.99 | 27-JAN-09:02 | -1.2 |
February | 0.123932E+09 | 1591.83 | 14-FEB-19:03 | 14.22 |
March | 65682604.02 | 1721.46 | 02-MAR-09:02 | 0.47 |
April | 7616211.48 | 1466.68 | 23-APR-08:03 | 13.33 |
May | 925443.12 | 1296.06 | 02-MAY-08:03 | 14.68 |
June | 13705.95 | 88.12 | 29-JUN-08:05 | 18.58 |
July | 158838.75 | 271.57 | 09-JUL-08:04 | 24.68 |
August | 104232.47 | 308.11 | 09-AUG-08:04 | 26.05 |
September | 417122.96 | 995.88 | 25-SEP-08:03 | 16.57 |
October | 1999337.38 | 1309.80 | 27-OCT-08:03 | 14.68 |
November | 93114047.11 | 1551.11 | 27-NOV-09:02 | 3.98 |
December | 0.273711E+09 | 2553.56 | 26-DEC-09:02 | -0.5 |
Annual Sum or Average | 0.748962E+09 | |||
Minimum of Months | 13705.95 | 88.12 | -1.2 | |
Maximum of Months | 0.273711E+09 | 2553.56 | 26.05 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263101E+09 | 3120.88 | 27-JAN-09:02 | -1.2 |
February | 0.175748E+09 | 3003.00 | 03-FEB-09:02 | 2.95 |
March | 89652260.83 | 2507.08 | 02-MAR-09:02 | 0.47 |
April | 32781442.39 | 2018.77 | 06-APR-08:53 | 18.90 |
May | 28210372.55 | 1674.27 | 01-MAY-08:53 | 17.20 |
June | 20954730.29 | 264.67 | 24-JUN-21:55 | 22.20 |
July | 24162444.39 | 185.08 | 16-JUL-06:12 | 24.47 |
August | 27229186.83 | 727.59 | 24-AUG-08:54 | 21.10 |
September | 35636166.59 | 1672.36 | 25-SEP-08:53 | 18.90 |
October | 38356420.42 | 1689.75 | 20-OCT-08:53 | 18.30 |
November | 0.134386E+09 | 2155.21 | 28-NOV-09:02 | 4.18 |
December | 0.378196E+09 | 3100.39 | 27-DEC-09:02 | -0.7 |
Annual Sum or Average | 0.124841E+10 | |||
Minimum of Months | 20954730.29 | 185.08 | -1.2 | |
Maximum of Months | 0.378196E+09 | 3120.88 | 24.47 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6578843.44 | 663.37 | 12-JAN-09:03 | 8.68 |
February | 6727209.80 | 666.11 | 24-FEB-09:03 | 5.87 |
March | 6830404.27 | 657.73 | 29-MAR-08:03 | 8.87 |
April | 5757862.89 | 394.24 | 24-APR-08:05 | 15.37 |
May | 6150106.38 | 362.41 | 02-MAY-08:05 | 14.68 |
June | 6052567.96 | 84.23 | 14-JUN-08:10 | 27.57 |
July | 7741905.04 | 76.55 | 16-JUL-06:12 | 24.47 |
August | 6579306.90 | 80.66 | 26-AUG-08:10 | 26.88 |
September | 7037433.38 | 452.11 | 25-SEP-08:54 | 18.90 |
October | 6535657.99 | 467.55 | 20-OCT-08:54 | 18.30 |
November | 5072953.97 | 657.40 | 21-NOV-09:03 | 8.77 |
December | 11454085.17 | 679.12 | 23-DEC-09:03 | 5.55 |
Annual Sum or Average | 82518337.20 | |||
Minimum of Months | 5072953.97 | 76.55 | 5.55 | |
Maximum of Months | 11454085.17 | 679.12 | 27.57 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187134E+09 | 1340.11 | 28-JAN-19:03 | 10.82 |
February | 0.118051E+09 | 1353.31 | 03-FEB-19:03 | 11.42 |
March | 66187596.27 | 1320.11 | 10-MAR-09:03 | 13.48 |
April | 5550841.51 | 1573.86 | 17-APR-18:03 | 14.13 |
May | 79242.21 | 623.94 | 03-MAY-08:04 | 19.18 |
June | 31449.60 | 314.50 | 29-JUN-08:05 | 18.58 |
July | 82490.67 | 327.84 | 19-JUL-08:06 | 20.78 |
August | 52944.93 | 193.34 | 16-AUG-18:05 | 18.98 |
September | 80784.54 | 228.85 | 24-SEP-08:05 | 16.93 |
October | 1446879.22 | 1405.74 | 06-OCT-18:03 | 14.22 |
November | 96139788.69 | 1410.56 | 29-NOV-16:13 | 13.53 |
December | 0.273385E+09 | 2569.52 | 26-DEC-16:12 | 2.03 |
Annual Sum or Average | 0.748222E+09 | |||
Minimum of Months | 31449.60 | 193.34 | 2.03 | |
Maximum of Months | 0.273385E+09 | 2569.52 | 20.78 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258551E+09 | 1399.05 | 30-JAN-16:13 | 15.60 |
February | 0.160289E+09 | 1712.54 | 12-FEB-21:13 | 13.70 |
March | 94645701.11 | 1899.36 | 29-MAR-18:53 | 12.80 |
April | 26667126.87 | 1261.33 | 07-APR-21:54 | 18.30 |
May | 14951876.15 | 1042.07 | 02-MAY-21:54 | 17.80 |
June | 9048680.62 | 285.86 | 12-JUN-08:34 | 25.00 |
July | 13418140.27 | 266.34 | 30-JUL-08:34 | 25.03 |
August | 15169959.97 | 285.71 | 23-AUG-08:34 | 25.37 |
September | 20344554.32 | 1120.98 | 30-SEP-21:54 | 17.20 |
October | 35474567.83 | 1510.91 | 24-OCT-18:43 | 14.18 |
November | 0.139129E+09 | 1470.90 | 17-NOV-19:03 | 13.72 |
December | 0.365239E+09 | 2575.99 | 26-DEC-16:12 | 2.03 |
Annual Sum or Average | 0.115293E+10 | |||
Minimum of Months | 9048680.62 | 266.34 | 2.03 | |
Maximum of Months | 0.365239E+09 | 2575.99 | 25.37 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.606968E+09 | 3500.62 | 27-JAN-09:02 | -1.2 |
February | 0.414695E+09 | 3382.12 | 03-FEB-09:02 | 2.95 |
March | 0.288657E+09 | 3399.74 | 02-MAR-09:02 | 0.47 |
April | 53360180.31 | 1772.25 | 11-APR-08:62 | 6.88 |
May | 2926219.32 | 1318.28 | 10-MAY-08:03 | 20.78 |
June | 104046.49 | 379.43 | 12-JUN-08:03 | 23.35 |
July | 13352.70 | 205.65 | 06-JUL-08:03 | 26.38 |
August | 300259.25 | 812.47 | 17-AUG-08:04 | 18.48 |
September | 3706230.93 | 1242.10 | 11-SEP-08:03 | 21.57 |
October | 30526880.08 | 1225.44 | 21-OCT-08:03 | 16.15 |
November | 0.367443E+09 | 3200.45 | 28-NOV-09:02 | 4.18 |
December | 0.779164E+09 | 3475.51 | 27-DEC-09:02 | -0.7 |
Annual Sum or Average | 0.254786E+10 | |||
Minimum of Months | 13352.70 | 205.65 | -1.2 | |
Maximum of Months | 0.779164E+09 | 3500.62 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.797795E+09 | 3519.16 | 27-JAN-09:02 | -1.2 |
February | 0.519851E+09 | 3397.61 | 10-FEB-09:02 | 2.95 |
March | 0.312105E+09 | 3392.52 | 02-MAR-09:02 | 0.47 |
April | 75857030.29 | 2121.26 | 08-APR-08:53 | 19.40 |
May | 36232616.90 | 1746.15 | 07-MAY-08:53 | 20.00 |
June | 25174762.63 | 1041.31 | 02-JUN-08:14 | 26.30 |
July | 28226438.57 | 651.13 | 19-JUL-21:54 | 22.20 |
August | 33398547.39 | 907.85 | 30-AUG-08:54 | 23.30 |
September | 46565995.28 | 1727.25 | 28-SEP-08:53 | 20.60 |
October | 64602682.59 | 1603.88 | 18-OCT-08:53 | 20.00 |
November | 0.454305E+09 | 3196.43 | 28-NOV-09:02 | 4.18 |
December | 0.101303E+10 | 3488.09 | 27-DEC-09:02 | -0.7 |
Annual Sum or Average | 0.340715E+10 | |||
Minimum of Months | 25174762.63 | 651.13 | -1.2 | |
Maximum of Months | 0.101303E+10 | 3519.16 | 26.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142978E+09 | 1143.02 | 14-JAN-16:12 | 7.97 |
February | 99234772.20 | 824.15 | 17-FEB-19:04 | 10.92 |
March | 71879445.80 | 1003.11 | 02-MAR-09:02 | 0.47 |
April | 12310111.51 | 925.41 | 17-APR-18:03 | 14.13 |
May | 618902.29 | 723.60 | 12-MAY-08:03 | 18.68 |
June | 43116.10 | 122.23 | 30-JUN-08:05 | 22.38 |
July | 312856.20 | 305.10 | 07-JUL-08:05 | 23.80 |
August | 257267.73 | 356.25 | 09-AUG-08:04 | 26.05 |
September | 382207.45 | 553.74 | 25-SEP-08:03 | 16.57 |
October | 1836351.59 | 818.99 | 06-OCT-18:03 | 14.22 |
November | 79862359.23 | 1056.37 | 27-NOV-09:02 | 3.98 |
December | 0.207202E+09 | 1591.20 | 26-DEC-19:02 | 1.78 |
Annual Sum or Average | 0.616918E+09 | |||
Minimum of Months | 43116.10 | 122.23 | 0.47 | |
Maximum of Months | 0.207202E+09 | 1591.20 | 26.05 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8808333.25 | 966.99 | 28-JAN-07:20 | -2.6 |
February | 7266837.32 | 1136.23 | 03-FEB-07:30 | -4.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 422625.02 | 157.52 | 28-NOV-07:10 | 0.87 |
December | 0.112699E+09 | 2290.71 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 0.129197E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.2 | |
Maximum of Months | 0.112699E+09 | 2290.71 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.204643E+11 | 19711.29 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.184774E+11 | 19711.29 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.205273E+11 | 19711.29 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.197704E+11 | 19711.29 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.204997E+11 | 19711.29 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.198611E+11 | 19711.29 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.204091E+11 | 19711.29 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.205352E+11 | 19711.29 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.197783E+11 | 19711.29 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.204564E+11 | 19711.29 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.198453E+11 | 19711.29 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.204091E+11 | 19711.29 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.241034E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.184774E+11 | 19711.29 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.205352E+11 | 19711.29 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101186E+10 | 974.63 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.913620E+09 | 974.63 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.101498E+10 | 974.63 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.977556E+09 | 974.63 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.101362E+10 | 974.63 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.982039E+09 | 974.63 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.100913E+10 | 974.63 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.101537E+10 | 974.63 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.977945E+09 | 974.63 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.101147E+10 | 974.63 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.981259E+09 | 974.63 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.100913E+10 | 974.63 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.119180E+11 | 0.101856E+11 | ||||
Minimum of Months | 0.913620E+09 | 974.63 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.101537E+10 | 974.63 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117174E+10 | 1128.63 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.105798E+10 | 1128.63 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.117535E+10 | 1128.63 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.113201E+10 | 1128.63 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.117377E+10 | 1128.63 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.113720E+10 | 1128.63 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.116858E+10 | 1128.63 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.117580E+10 | 1128.63 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.113246E+10 | 1128.63 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.117129E+10 | 1128.63 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.113630E+10 | 1128.63 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.116858E+10 | 1128.63 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.138011E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.105798E+10 | 1128.63 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.117580E+10 | 1128.63 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.247783E+10 | 2386.66 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.223726E+10 | 2386.66 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.248547E+10 | 2386.66 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.239382E+10 | 2386.66 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.248213E+10 | 2386.66 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.240480E+10 | 2386.66 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.247115E+10 | 2386.66 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.248642E+10 | 2386.66 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.239478E+10 | 2386.66 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.247688E+10 | 2386.66 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.240289E+10 | 2386.66 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.247115E+10 | 2386.66 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.291846E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.223726E+10 | 2386.66 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.248642E+10 | 2386.66 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.762439E+09 | 734.39 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.688413E+09 | 734.39 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.764789E+09 | 734.39 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.736588E+09 | 734.39 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.763761E+09 | 734.39 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.739966E+09 | 734.39 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.760382E+09 | 734.39 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.765082E+09 | 734.39 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.736882E+09 | 734.39 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.762145E+09 | 734.39 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.739379E+09 | 734.39 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.760382E+09 | 734.39 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.898021E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.688413E+09 | 734.39 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.765082E+09 | 734.39 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.265929E+10 | 2561.44 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.240110E+10 | 2561.44 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.266749E+10 | 2561.44 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.256913E+10 | 2561.44 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.266390E+10 | 2561.44 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.258091E+10 | 2561.44 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.265212E+10 | 2561.44 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.266851E+10 | 2561.44 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.257015E+10 | 2561.44 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.265826E+10 | 2561.44 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.257886E+10 | 2561.44 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.265212E+10 | 2561.44 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.313218E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.240110E+10 | 2561.44 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.266851E+10 | 2561.44 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.171043E+11 | 16474.99 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.154437E+11 | 16474.99 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.171571E+11 | 16474.99 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.165244E+11 | 16474.99 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.171340E+11 | 16474.99 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.166002E+11 | 16474.99 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.170582E+11 | 16474.99 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.171636E+11 | 16474.99 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.165310E+11 | 16474.99 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.170977E+11 | 16474.99 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.165870E+11 | 16474.99 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.170582E+11 | 16474.99 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.201459E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.154437E+11 | 16474.99 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.171636E+11 | 16474.99 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332597E+09 | 300.93 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.300367E+09 | 300.93 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.329954E+09 | 300.93 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.322251E+09 | 300.93 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.331275E+09 | 300.93 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.319694E+09 | 300.93 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.333875E+09 | 300.93 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.329954E+09 | 300.93 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.322338E+09 | 300.93 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.332554E+09 | 300.93 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.320973E+09 | 300.93 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.333919E+09 | 300.93 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.390975E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.300367E+09 | 300.93 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.333919E+09 | 300.93 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332688E+09 | 301.01 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.300450E+09 | 301.01 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.330044E+09 | 301.01 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.322339E+09 | 301.01 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.331366E+09 | 301.01 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.319782E+09 | 301.01 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.333967E+09 | 301.01 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.330044E+09 | 301.01 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.322426E+09 | 301.01 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.332644E+09 | 301.01 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.321060E+09 | 301.01 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.334010E+09 | 301.01 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.391082E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.300450E+09 | 301.01 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.334010E+09 | 301.01 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.195823E+10 | 1886.18 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.176811E+10 | 1886.18 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.196427E+10 | 1886.18 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.189184E+10 | 1886.18 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.196163E+10 | 1886.18 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.190052E+10 | 1886.18 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.195295E+10 | 1886.18 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.196502E+10 | 1886.18 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.189259E+10 | 1886.18 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.195748E+10 | 1886.18 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.189901E+10 | 1886.18 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.195295E+10 | 1886.18 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.230646E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.176811E+10 | 1886.18 | 0.00 | 0.00 | |
Maximum of Months | 0.196502E+10 | 1886.18 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332688E+09 | 301.01 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.300450E+09 | 301.01 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.330044E+09 | 301.01 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.322339E+09 | 301.01 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.331366E+09 | 301.01 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.319782E+09 | 301.01 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.333967E+09 | 301.01 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.330044E+09 | 301.01 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.322426E+09 | 301.01 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.332644E+09 | 301.01 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.321060E+09 | 301.01 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.334010E+09 | 301.01 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.391082E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.300450E+09 | 301.01 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.334010E+09 | 301.01 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466994E+10 | 4498.11 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.421653E+10 | 4498.11 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.468433E+10 | 4498.11 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.451160E+10 | 4498.11 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.467803E+10 | 4498.11 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.453229E+10 | 4498.11 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.465734E+10 | 4498.11 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.468613E+10 | 4498.11 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.451340E+10 | 4498.11 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.466814E+10 | 4498.11 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.452870E+10 | 4498.11 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.465734E+10 | 4498.11 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.550038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.421653E+10 | 4498.11 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.468613E+10 | 4498.11 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466994E+10 | 4498.11 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.421653E+10 | 4498.11 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.468433E+10 | 4498.11 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.451160E+10 | 4498.11 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.467803E+10 | 4498.11 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.453229E+10 | 4498.11 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.465734E+10 | 4498.11 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.468613E+10 | 4498.11 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.451340E+10 | 4498.11 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.466814E+10 | 4498.11 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.452870E+10 | 4498.11 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.465734E+10 | 4498.11 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.550038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.421653E+10 | 4498.11 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.468613E+10 | 4498.11 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124679E+10 | 1200.92 | 02-JAN-20:10 | 0.371477E+11 | 16602.84 | 01-JAN-07:10 |
February | 0.112574E+10 | 1200.92 | 01-FEB-20:10 | 0.335528E+11 | 16602.84 | 01-FEB-07:10 |
March | 0.125063E+10 | 1200.92 | 01-MAR-20:10 | 0.371477E+11 | 16602.84 | 01-MAR-07:10 |
April | 0.120452E+10 | 1200.92 | 03-APR-19:10 | 0.359494E+11 | 16602.84 | 01-APR-06:10 |
May | 0.124895E+10 | 1200.92 | 01-MAY-19:10 | 0.371477E+11 | 16602.84 | 01-MAY-06:10 |
June | 0.121004E+10 | 1200.92 | 01-JUN-19:10 | 0.359494E+11 | 16602.84 | 01-JUN-06:10 |
July | 0.124343E+10 | 1200.92 | 03-JUL-19:10 | 0.371477E+11 | 16602.84 | 01-JUL-06:10 |
August | 0.125111E+10 | 1200.92 | 01-AUG-19:10 | 0.371477E+11 | 16602.84 | 01-AUG-06:10 |
September | 0.120500E+10 | 1200.92 | 01-SEP-19:10 | 0.359494E+11 | 16602.84 | 01-SEP-06:10 |
October | 0.124631E+10 | 1200.92 | 02-OCT-19:10 | 0.371477E+11 | 16602.84 | 01-OCT-06:10 |
November | 0.120908E+10 | 1200.92 | 01-NOV-19:10 | 0.359494E+11 | 16602.84 | 01-NOV-06:10 |
December | 0.124343E+10 | 1200.92 | 01-DEC-20:10 | 0.371477E+11 | 16602.84 | 01-DEC-07:10 |
Annual Sum or Average | 0.146850E+11 | 0.437384E+12 | ||||
Minimum of Months | 0.112574E+10 | 1200.92 | 0.335528E+11 | 16602.84 | ||
Maximum of Months | 0.125111E+10 | 1200.92 | 0.371477E+11 | 16602.84 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.207249E+10 | 1996.23 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.187127E+10 | 1996.23 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.207888E+10 | 1996.23 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.200222E+10 | 1996.23 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.207608E+10 | 1996.23 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.201140E+10 | 1996.23 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.206690E+10 | 1996.23 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.207967E+10 | 1996.23 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.200302E+10 | 1996.23 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.207169E+10 | 1996.23 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.200981E+10 | 1996.23 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.206690E+10 | 1996.23 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.244103E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.187127E+10 | 1996.23 | 0.00 | 0.00 | |
Maximum of Months | 0.207967E+10 | 1996.23 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.204643E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.184774E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.205273E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.197704E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.204997E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.198611E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.204091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.205352E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.197783E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.204564E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.198453E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.204091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.241034E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.184774E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.205352E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.101186E+10 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404877E+09 |
February | 0.179968E+10 | 0.913620E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313784E+09 |
March | 0.199990E+10 | 0.101498E+10 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 140928.44 | 0.283951E+09 |
April | 0.192973E+10 | 0.977556E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20365509.00 | 0.126232E+09 |
May | 0.199475E+10 | 0.101362E+10 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57934052.20 | 49955901.14 |
June | 0.193394E+10 | 0.982039E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118174E+09 | 14173205.99 |
July | 0.199054E+10 | 0.100913E+10 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108525E+09 | 9185921.35 |
August | 0.199896E+10 | 0.101537E+10 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87831836.67 | 20617869.96 |
September | 0.192879E+10 | 0.977945E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48706417.65 | 55351598.39 |
October | 0.199148E+10 | 0.101147E+10 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11505921.56 | 0.148454E+09 |
November | 0.192552E+10 | 0.981259E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314944E+09 |
December | 0.199054E+10 | 0.100913E+10 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444512E+09 |
Annual Sum or Average | 0.234744E+11 | 0.119180E+11 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453183E+09 | 0.218604E+10 |
Minimum of Months | 0.179968E+10 | 0.913620E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9185921.35 |
Maximum of Months | 0.199990E+10 | 0.101537E+10 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118174E+09 | 0.444512E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.117174E+10 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164879E+09 |
February | 0.208403E+10 | 0.105798E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128951E+09 |
March | 0.231589E+10 | 0.117535E+10 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115078.87 | 0.118129E+09 |
April | 0.223463E+10 | 0.113201E+10 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8336216.09 | 55145692.67 |
May | 0.230993E+10 | 0.117377E+10 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22622679.94 | 23542670.35 |
June | 0.223950E+10 | 0.113720E+10 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45480199.67 | 7261982.54 |
July | 0.230505E+10 | 0.116858E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41694891.92 | 5017356.87 |
August | 0.231480E+10 | 0.117580E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33892009.26 | 10164193.35 |
September | 0.223354E+10 | 0.113246E+10 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19121503.37 | 25267281.81 |
October | 0.230614E+10 | 0.117129E+10 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4567388.10 | 63433321.25 |
November | 0.222975E+10 | 0.113630E+10 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 0.130136E+09 |
December | 0.230505E+10 | 0.116858E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179927E+09 |
Annual Sum or Average | 0.271834E+11 | 0.138011E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175830E+09 | 0.911855E+09 |
Minimum of Months | 0.208403E+10 | 0.105798E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5017356.87 |
Maximum of Months | 0.231589E+10 | 0.117580E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45480199.67 | 0.179927E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.247783E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377190E+09 |
February | 0.440737E+09 | 0.223726E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9317.07 | 0.295509E+09 |
March | 0.489771E+09 | 0.248547E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 465471.97 | 0.273431E+09 |
April | 0.472586E+09 | 0.239382E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19465978.47 | 0.130215E+09 |
May | 0.488511E+09 | 0.248213E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52426030.93 | 56321753.96 |
June | 0.473617E+09 | 0.240480E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107026E+09 | 17215437.07 |
July | 0.487480E+09 | 0.247115E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98050298.91 | 11845762.72 |
August | 0.489542E+09 | 0.248642E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79535541.36 | 24334313.94 |
September | 0.472357E+09 | 0.239478E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44510542.69 | 59836931.36 |
October | 0.487709E+09 | 0.247688E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10881010.40 | 0.149413E+09 |
November | 0.471555E+09 | 0.240289E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18512.10 | 0.299939E+09 |
December | 0.487480E+09 | 0.247115E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411606E+09 |
Annual Sum or Average | 0.574883E+10 | 0.291846E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412389E+09 | 0.210686E+10 |
Minimum of Months | 0.440737E+09 | 0.223726E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11845762.72 |
Maximum of Months | 0.489771E+09 | 0.248642E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107026E+09 | 0.411606E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.762439E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199979E+09 |
February | 0.339028E+09 | 0.688413E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83465.81 | 0.154764E+09 |
March | 0.376747E+09 | 0.764789E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 641852.23 | 0.141223E+09 |
April | 0.363528E+09 | 0.736588E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12597676.54 | 66508303.57 |
May | 0.375778E+09 | 0.763761E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31078074.10 | 28811796.31 |
June | 0.364321E+09 | 0.739966E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61953013.09 | 8761421.00 |
July | 0.374985E+09 | 0.760382E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56867076.63 | 5823312.75 |
August | 0.376571E+09 | 0.765082E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46338755.05 | 12027809.66 |
September | 0.363352E+09 | 0.736882E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26515035.22 | 30704820.87 |
October | 0.375161E+09 | 0.762145E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7252002.31 | 75867815.49 |
November | 0.362735E+09 | 0.739379E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94984.76 | 0.155802E+09 |
December | 0.374985E+09 | 0.760382E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221291E+09 |
Annual Sum or Average | 0.442217E+10 | 0.898021E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243422E+09 | 0.110156E+10 |
Minimum of Months | 0.339028E+09 | 0.688413E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5823312.75 |
Maximum of Months | 0.376747E+09 | 0.765082E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61953013.09 | 0.221291E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572811E+09 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446285E+09 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 175469.10 | 0.409314E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 25310211.21 | 0.189254E+09 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 71309937.98 | 79766670.92 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.146124E+09 | 23971981.17 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.133849E+09 | 16634317.77 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.108573E+09 | 34134827.25 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 60549837.61 | 84209329.09 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 14311983.20 | 0.215992E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446345E+09 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626571E+09 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.560203E+09 | 0.314529E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16634317.77 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.146124E+09 | 0.626571E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.265929E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920123E+09 |
February | 0.236489E+11 | 0.240110E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731143E+09 |
March | 0.262800E+11 | 0.266749E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311387.89 | 0.677264E+09 |
April | 0.253579E+11 | 0.256913E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44915230.48 | 0.325633E+09 |
May | 0.262123E+11 | 0.266390E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126544E+09 | 0.141199E+09 |
June | 0.254132E+11 | 0.258091E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259305E+09 | 42512926.42 |
July | 0.261570E+11 | 0.265212E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237518E+09 | 29377245.00 |
August | 0.262677E+11 | 0.266851E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192665E+09 | 60515408.55 |
September | 0.253456E+11 | 0.257015E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107448E+09 | 0.148944E+09 |
October | 0.261693E+11 | 0.265826E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25398144.86 | 0.378882E+09 |
November | 0.253025E+11 | 0.257886E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732343E+09 |
December | 0.261570E+11 | 0.265212E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100174E+10 |
Annual Sum or Average | 0.308468E+12 | 0.313218E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994106E+09 | 0.518968E+10 |
Minimum of Months | 0.236489E+11 | 0.240110E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29377245.00 |
Maximum of Months | 0.262800E+11 | 0.266851E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259305E+09 | 0.100174E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.171043E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276571E+10 |
February | 0.702046E+11 | 0.154437E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216502E+10 |
March | 0.780153E+11 | 0.171571E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1372073.27 | 0.198053E+10 |
April | 0.752779E+11 | 0.165244E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133450E+09 | 0.923959E+09 |
May | 0.778146E+11 | 0.171340E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370654E+09 | 0.393658E+09 |
June | 0.754422E+11 | 0.166002E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745523E+09 | 0.119590E+09 |
July | 0.776503E+11 | 0.170582E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684133E+09 | 82460415.16 |
August | 0.779788E+11 | 0.171636E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554779E+09 | 0.167298E+09 |
September | 0.752414E+11 | 0.165310E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309723E+09 | 0.420628E+09 |
October | 0.776868E+11 | 0.170977E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73305666.30 | 0.106641E+10 |
November | 0.751137E+11 | 0.165870E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218390E+10 |
December | 0.776503E+11 | 0.170582E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301746E+10 |
Annual Sum or Average | 0.915726E+12 | 0.201459E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287294E+10 | 0.152866E+11 |
Minimum of Months | 0.702046E+11 | 0.154437E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82460415.16 |
Maximum of Months | 0.780153E+11 | 0.171636E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745523E+09 | 0.301746E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226933E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 119304.83 | 0.173257E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 746709.97 | 0.153820E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19736351.82 | 61620830.34 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50445586.49 | 19903494.78 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92945511.30 | 3332717.89 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89658673.35 | 1085356.06 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74117064.42 | 5274262.95 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42551819.31 | 20117051.89 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12042273.62 | 70312211.83 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 163383.06 | 0.170991E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251344E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382527E+09 | 0.115799E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1085356.06 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92945511.30 | 0.251344E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223727E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174900E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 374713.42 | 0.162333E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18649143.12 | 70220273.91 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48793519.64 | 25745384.17 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90742858.79 | 6651127.12 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86857571.91 | 4516097.44 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71984661.17 | 10133505.72 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40615681.76 | 27407137.73 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10753181.52 | 83529771.11 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9799.56 | 0.173339E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247316E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368781E+09 | 0.120982E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4516097.44 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90742858.79 | 0.247316E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.332597E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85626564.21 |
February | 0.00 | 0.300367E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68322887.51 |
March | 0.00 | 0.329954E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64754512.52 |
April | 0.00 | 0.322251E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1043671.83 | 33932037.29 |
May | 0.00 | 0.331275E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4354707.79 | 17408509.69 |
June | 0.00 | 0.319694E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11753262.31 | 7328960.40 |
July | 0.00 | 0.333875E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9926664.83 | 6572877.98 |
August | 0.00 | 0.329954E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7719909.64 | 9981044.37 |
September | 0.00 | 0.322338E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3627103.74 | 18324106.81 |
October | 0.00 | 0.332554E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 656829.70 | 39052823.62 |
November | 0.00 | 0.320973E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69305473.95 |
December | 0.00 | 0.333919E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92193793.97 |
Annual Sum or Average | 0.00 | 0.390975E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39082149.85 | 0.512804E+09 |
Minimum of Months | 0.00 | 0.300367E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6572877.98 |
Maximum of Months | 0.00 | 0.333919E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11753262.31 | 92193793.97 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.332688E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62485240.50 |
February | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48410155.13 |
March | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 109349.64 | 44035444.87 |
April | 0.293479E+09 | 0.322339E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5232715.71 | 18701912.81 |
May | 0.303504E+09 | 0.331366E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13652136.89 | 6833806.25 |
June | 0.293842E+09 | 0.319782E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25354864.88 | 1679702.89 |
July | 0.303141E+09 | 0.333967E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24243567.03 | 1064874.04 |
August | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20117317.42 | 2617702.41 |
September | 0.293479E+09 | 0.322426E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11367438.58 | 7319438.07 |
October | 0.303322E+09 | 0.332644E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3017251.37 | 21998356.50 |
November | 0.293661E+09 | 0.321060E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2740.51 | 47854625.07 |
December | 0.303141E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69121485.16 |
Annual Sum or Average | 0.357224E+10 | 0.391082E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103097E+09 | 0.332123E+09 |
Minimum of Months | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1064874.04 |
Maximum of Months | 0.303685E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25354864.88 | 69121485.16 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227918E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 119508.76 | 0.174294E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 752304.97 | 0.155003E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19738859.64 | 62443746.70 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50396661.24 | 20275967.97 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92860457.18 | 3413517.77 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89544310.76 | 1117321.88 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74042054.22 | 5369521.99 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42531014.68 | 20396112.56 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12056557.36 | 70704523.94 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 163647.73 | 0.171480E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252479E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382205E+09 | 0.116489E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1117321.88 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92860457.18 | 0.252479E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224392E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175361E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 382806.67 | 0.160366E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18643407.09 | 70156416.06 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48707190.53 | 28322556.40 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90593490.04 | 8624962.29 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86606058.20 | 6168232.52 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71779768.54 | 11919601.15 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40434806.70 | 29522248.46 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10755434.91 | 80309330.59 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9795.41 | 0.173382E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247665E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367913E+09 | 0.121619E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6168232.52 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90593490.04 | 0.247665E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.195823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322823E+09 |
February | 0.348285E+10 | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251851E+09 |
March | 0.387034E+10 | 0.196427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89994.32 | 0.231271E+09 |
April | 0.373454E+10 | 0.189184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14064256.74 | 0.107224E+09 |
May | 0.386038E+10 | 0.196163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39777869.48 | 45338285.69 |
June | 0.374269E+10 | 0.190052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81783586.56 | 13713263.39 |
July | 0.385223E+10 | 0.195295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74841969.65 | 9543103.06 |
August | 0.386853E+10 | 0.196502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60674554.10 | 19508843.51 |
September | 0.373273E+10 | 0.189259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33774521.62 | 47866327.57 |
October | 0.385404E+10 | 0.195748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7951756.30 | 0.122395E+09 |
November | 0.372639E+10 | 0.189901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251945E+09 |
December | 0.385223E+10 | 0.195295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352334E+09 |
Annual Sum or Average | 0.454292E+11 | 0.230646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312959E+09 | 0.177581E+10 |
Minimum of Months | 0.348285E+10 | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9543103.06 |
Maximum of Months | 0.387034E+10 | 0.196502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81783586.56 | 0.352334E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225267E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 111224.30 | 0.172545E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 713766.72 | 0.153526E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19411635.11 | 61764637.83 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49837084.39 | 20084228.18 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92156905.00 | 3424899.98 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 88792772.31 | 1138882.48 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73355891.42 | 5377859.31 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41996525.29 | 20278582.40 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11827703.41 | 70346343.12 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 155221.33 | 0.170238E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249630E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378359E+09 | 0.115362E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1138882.48 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92156905.00 | 0.249630E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220992E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173462E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 360666.50 | 0.161908E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18371399.34 | 70396042.43 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48251253.35 | 25537905.32 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90028611.78 | 6462050.11 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86095817.30 | 4397602.55 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71300759.92 | 9905497.82 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40123836.53 | 27040096.43 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10582110.08 | 83761298.99 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7667.48 | 0.172063E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244449E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365122E+09 | 0.120037E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4397602.55 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90028611.78 | 0.244449E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.332688E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117116E+09 |
February | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56607.28 | 89420029.55 |
March | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 365549.79 | 79284365.31 |
April | 0.293479E+09 | 0.322339E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9936053.96 | 31764520.34 |
May | 0.303504E+09 | 0.331366E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25514972.58 | 10297200.79 |
June | 0.293842E+09 | 0.319782E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47169589.89 | 1752667.78 |
July | 0.303141E+09 | 0.333967E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45438863.98 | 585589.63 |
August | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37532780.72 | 2765390.33 |
September | 0.293479E+09 | 0.322426E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21478658.28 | 10453591.96 |
October | 0.303322E+09 | 0.332644E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6044798.47 | 36374114.49 |
November | 0.293661E+09 | 0.321060E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78893.68 | 88279347.75 |
December | 0.303141E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129873E+09 |
Annual Sum or Average | 0.357224E+10 | 0.391082E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193617E+09 | 0.597966E+09 |
Minimum of Months | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585589.63 |
Maximum of Months | 0.303685E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47169589.89 | 0.129873E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.466994E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621910E+09 |
February | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488962E+09 |
March | 0.461508E+11 | 0.468433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 256749.74 | 0.452724E+09 |
April | 0.445315E+11 | 0.451160E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28223741.32 | 0.213242E+09 |
May | 0.460320E+11 | 0.467803E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79562367.13 | 91390029.15 |
June | 0.446286E+11 | 0.453229E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163672E+09 | 28162128.70 |
July | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149747E+09 | 19713051.25 |
August | 0.461292E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121311E+09 | 39507121.02 |
September | 0.445099E+11 | 0.451340E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67673553.75 | 96612803.84 |
October | 0.459565E+11 | 0.466814E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16054445.00 | 0.241736E+09 |
November | 0.444343E+11 | 0.452870E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13095.23 | 0.489270E+09 |
December | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677537E+09 |
Annual Sum or Average | 0.541708E+12 | 0.550038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626513E+09 | 0.346077E+10 |
Minimum of Months | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19713051.25 |
Maximum of Months | 0.461508E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163672E+09 | 0.677537E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.466994E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633077E+09 |
February | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497055E+09 |
March | 0.461508E+11 | 0.468433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186404.44 | 0.459508E+09 |
April | 0.445315E+11 | 0.451160E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27883568.75 | 0.215728E+09 |
May | 0.460320E+11 | 0.467803E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79259130.19 | 92218004.74 |
June | 0.446286E+11 | 0.453229E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163665E+09 | 28269158.11 |
July | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149609E+09 | 19808866.38 |
August | 0.461292E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121166E+09 | 39955080.09 |
September | 0.445099E+11 | 0.451340E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67294858.54 | 97414815.94 |
October | 0.459565E+11 | 0.466814E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15777681.68 | 0.245060E+09 |
November | 0.444343E+11 | 0.452870E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1914.98 | 0.497570E+09 |
December | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690182E+09 |
Annual Sum or Average | 0.541708E+12 | 0.550038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624842E+09 | 0.351584E+10 |
Minimum of Months | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19808866.38 |
Maximum of Months | 0.461508E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163665E+09 | 0.690182E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.124679E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586854E+09 |
February | 0.369574E+10 | 0.112574E+10 | 0.304050E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457694E+09 |
March | 0.410691E+10 | 0.125063E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 141183.32 | 0.420359E+09 |
April | 0.396281E+10 | 0.120452E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 24914314.35 | 0.195318E+09 |
May | 0.409635E+10 | 0.124895E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 70861879.50 | 83003381.30 |
June | 0.397146E+10 | 0.121004E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.146410E+09 | 25380929.47 |
July | 0.408770E+10 | 0.124343E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.133757E+09 | 17897274.55 |
August | 0.410499E+10 | 0.125111E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.108356E+09 | 36077842.78 |
September | 0.396089E+10 | 0.120500E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 60145675.14 | 87680666.97 |
October | 0.408962E+10 | 0.124631E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 14079416.86 | 0.223050E+09 |
November | 0.395417E+10 | 0.120908E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457996E+09 |
December | 0.408770E+10 | 0.124343E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641635E+09 |
Annual Sum or Average | 0.482060E+11 | 0.146850E+11 | 0.396352E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.558665E+09 | 0.323295E+10 |
Minimum of Months | 0.369574E+10 | 0.112574E+10 | 0.304050E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17897274.55 |
Maximum of Months | 0.410691E+10 | 0.125111E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.146410E+09 | 0.641635E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.207249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544280E+09 |
February | 0.368610E+10 | 0.187127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431467E+09 |
March | 0.409620E+10 | 0.207888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138573.93 | 0.401109E+09 |
April | 0.395248E+10 | 0.200222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24397400.63 | 0.189818E+09 |
May | 0.408566E+10 | 0.207608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69389404.65 | 81235581.91 |
June | 0.396110E+10 | 0.201140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143350E+09 | 24820946.35 |
July | 0.407704E+10 | 0.206690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130998E+09 | 17444140.67 |
August | 0.409429E+10 | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106116E+09 | 35279035.02 |
September | 0.395056E+10 | 0.200302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58909643.06 | 85743073.26 |
October | 0.407896E+10 | 0.207169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13791899.65 | 0.217736E+09 |
November | 0.394385E+10 | 0.200981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432094E+09 |
December | 0.407704E+10 | 0.206690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584500E+09 |
Annual Sum or Average | 0.480803E+11 | 0.244103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547092E+09 | 0.304553E+10 |
Minimum of Months | 0.368610E+10 | 0.187127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17444140.67 |
Maximum of Months | 0.409620E+10 | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143350E+09 | 0.584500E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 19711.29 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 19711.29 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 19711.29 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 19711.29 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 19711.29 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 19711.29 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 19711.29 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 19711.29 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 19711.29 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 19711.29 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 19711.29 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 19711.29 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 974.63 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 286.23 | 27-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 974.63 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 300.76 | 03-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 974.63 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.06 | 21-MAR-16:00 | 282.98 | 02-MAR-05:40 |
April | 1169.53 | 01-APR-00:10 | 974.63 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.90 | 21-APR-14:00 | 192.62 | 12-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 974.63 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.34 | 21-MAY-14:00 | 126.00 | 02-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 974.63 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.64 | 02-JUN-16:00 | 79.69 | 13-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 974.63 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.37 | 02-JUL-16:00 | 49.89 | 05-JUL-06:00 |
August | 1169.53 | 01-AUG-00:10 | 974.63 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.08 | 07-AUG-16:00 | 62.85 | 16-AUG-21:00 |
September | 1169.53 | 01-SEP-00:10 | 974.63 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.62 | 19-SEP-14:00 | 138.97 | 30-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 974.63 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.26 | 01-OCT-15:00 | 155.46 | 25-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 974.63 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 242.57 | 28-NOV-05:00 |
December | 1169.53 | 01-DEC-00:10 | 974.63 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 287.30 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 974.63 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | |||||
Maximum of Months | 1169.53 | 974.63 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 144.64 | 300.76 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 1128.63 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 115.72 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 1128.63 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 121.33 | 03-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 1128.63 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 22-MAR-13:00 | 114.32 | 02-MAR-05:30 |
April | 1354.32 | 01-APR-00:10 | 1128.63 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.48 | 21-APR-14:00 | 82.46 | 12-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 1128.63 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.82 | 21-MAY-14:00 | 57.72 | 02-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 1128.63 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.83 | 02-JUN-16:00 | 36.30 | 13-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 1128.63 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.80 | 02-JUL-16:00 | 24.60 | 05-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 1128.63 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 07-AUG-16:00 | 29.49 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 1128.63 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.68 | 19-SEP-14:00 | 62.54 | 30-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 1128.63 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.68 | 01-OCT-15:00 | 69.14 | 25-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 1128.63 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 08-NOV-15:00 | 100.48 | 27-NOV-23:00 |
December | 1354.32 | 01-DEC-00:10 | 1128.63 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 114.72 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.60 | |||||
Maximum of Months | 1354.32 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 55.83 | 121.33 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 2386.66 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 267.94 | 27-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 2386.66 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 20-FEB-15:00 | 279.92 | 03-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 2386.66 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 21-MAR-16:00 | 263.43 | 02-MAR-05:30 |
April | 286.42 | 01-APR-00:10 | 2386.66 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.80 | 21-APR-14:00 | 193.23 | 12-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 2386.66 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.84 | 21-MAY-14:00 | 136.42 | 02-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 2386.66 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.95 | 02-JUN-16:00 | 84.73 | 13-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 2386.66 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.14 | 02-JUL-16:00 | 58.29 | 05-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 2386.66 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.75 | 07-AUG-16:00 | 69.75 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 2386.66 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.05 | 19-SEP-14:00 | 147.76 | 30-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 2386.66 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.60 | 01-OCT-15:00 | 162.44 | 11-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 2386.66 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 03-NOV-15:55 | 232.32 | 27-NOV-23:00 |
December | 286.42 | 01-DEC-00:10 | 2386.66 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 265.05 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.29 | |||||
Maximum of Months | 286.42 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 131.95 | 279.92 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 734.39 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 150.64 | 27-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 734.39 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 | 20-FEB-15:00 | 158.31 | 03-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 734.39 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 | 21-MAR-16:00 | 148.92 | 02-MAR-05:10 |
April | 220.32 | 01-APR-00:10 | 734.39 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.59 | 21-APR-14:00 | 103.38 | 12-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 734.39 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.02 | 21-MAY-14:00 | 73.17 | 02-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 734.39 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.13 | 02-JUN-16:00 | 45.52 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 734.39 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.35 | 02-JUL-16:00 | 30.55 | 05-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 734.39 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | 07-AUG-16:00 | 36.15 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 734.39 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.38 | 19-SEP-14:00 | 79.59 | 30-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 734.39 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.74 | 01-OCT-15:00 | 86.51 | 11-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 734.39 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 | 03-NOV-15:55 | 127.68 | 28-NOV-05:00 |
December | 220.32 | 01-DEC-00:10 | 734.39 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 151.20 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 | |||||
Maximum of Months | 220.32 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 76.13 | 158.31 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 398.61 | 27-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 416.88 | 03-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 12.53 | 21-MAR-16:00 | 394.89 | 02-MAR-05:00 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 100.78 | 21-APR-14:00 | 280.58 | 12-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 134.96 | 21-MAY-14:00 | 193.71 | 02-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 180.18 | 02-JUN-16:00 | 117.73 | 13-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 173.60 | 02-JUL-16:00 | 80.54 | 05-JUL-06:00 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 160.78 | 07-AUG-16:00 | 95.66 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 121.60 | 19-SEP-14:00 | 210.17 | 30-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 108.69 | 01-OCT-15:00 | 234.24 | 25-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 344.11 | 28-NOV-05:00 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 400.10 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 80.54 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 180.18 | 416.88 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2561.44 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 632.66 | 27-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 2561.44 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 664.84 | 03-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 2561.44 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.23 | 21-MAR-16:00 | 625.43 | 02-MAR-05:10 |
April | 15368.40 | 01-APR-00:10 | 2561.44 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.84 | 21-APR-14:00 | 425.79 | 12-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 2561.44 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.50 | 21-MAY-14:00 | 327.02 | 02-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 2561.44 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.74 | 02-JUN-16:00 | 208.82 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 2561.44 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.07 | 02-JUL-16:00 | 142.86 | 05-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 2561.44 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.32 | 07-AUG-16:00 | 169.71 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 2561.44 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.78 | 19-SEP-14:00 | 346.64 | 25-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 2561.44 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.89 | 01-OCT-15:00 | 375.35 | 25-OCT-03:00 |
November | 15368.40 | 01-NOV-00:10 | 2561.44 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 536.21 | 28-NOV-05:00 |
December | 15368.40 | 01-DEC-00:10 | 2561.44 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 635.03 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2561.44 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.86 | |||||
Maximum of Months | 15368.40 | 2561.44 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 319.74 | 664.84 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 16474.99 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1928.05 | 27-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 16474.99 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2016.56 | 03-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 16474.99 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.93 | 22-MAR-13:00 | 1920.98 | 02-MAR-05:30 |
April | 45622.98 | 01-APR-00:10 | 16474.99 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 513.50 | 21-APR-14:00 | 1376.32 | 12-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 16474.99 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 685.58 | 21-MAY-14:00 | 968.77 | 02-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 16474.99 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 913.62 | 02-JUN-16:00 | 596.75 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 16474.99 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 880.28 | 02-JUL-16:00 | 408.22 | 05-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 16474.99 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.33 | 07-AUG-16:00 | 484.96 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 16474.99 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.58 | 19-SEP-14:00 | 1046.53 | 30-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 16474.99 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 551.15 | 01-OCT-15:00 | 1159.11 | 25-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 16474.99 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1680.00 | 17-NOV-04:00 |
December | 45622.98 | 01-DEC-00:10 | 16474.99 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1926.51 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 16474.99 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.22 | |||||
Maximum of Months | 45622.98 | 16474.99 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 913.62 | 2016.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.13 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 20-FEB-16:20 | 175.58 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.24 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.15 | 21-APR-15:20 | 112.77 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.87 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 | 02-JUN-16:00 | 37.51 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.00 | 02-JUL-16:00 | 20.30 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 | 07-AUG-16:00 | 30.87 | 14-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 01-OCT-15:20 | 91.19 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 | 03-NOV-16:00 | 141.80 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.75 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 | 175.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.12 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 175.57 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.23 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.14 | 21-APR-15:20 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.87 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 02-JUN-16:00 | 39.35 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.99 | 02-JUL-16:00 | 34.88 | 18-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 | 07-AUG-16:00 | 43.53 | 16-AUG-21:50 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 01-OCT-15:20 | 91.18 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | 08-NOV-15:00 | 141.79 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.74 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 175.57 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 300.93 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 54.30 | 27-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 300.93 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 55.96 | 03-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 300.93 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 52.17 | 02-MAR-05:00 |
April | 0.00 | 01-APR-00:10 | 300.93 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 21-APR-14:00 | 40.11 | 12-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 300.93 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 | 21-MAY-14:00 | 29.86 | 02-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 300.93 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 02-JUN-16:00 | 19.91 | 13-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 300.93 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.29 | 02-JUL-16:00 | 15.04 | 05-JUL-06:00 |
August | 0.00 | 01-AUG-00:10 | 300.93 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 | 07-AUG-16:00 | 17.05 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 300.93 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 19-SEP-14:00 | 31.92 | 30-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 300.93 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 01-OCT-15:00 | 35.14 | 25-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 300.93 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 47.60 | 27-NOV-23:00 |
December | 0.00 | 01-DEC-00:10 | 300.93 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 52.90 | 19-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 300.93 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | |||||
Maximum of Months | 0.00 | 300.93 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 55.96 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 301.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 46.64 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 301.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 49.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 301.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 21-MAR-16:00 | 46.12 | 02-MAR-05:00 |
April | 180.00 | 01-APR-00:10 | 301.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 21-APR-15:20 | 31.47 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 301.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 | 19-MAY-16:00 | 20.28 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 301.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 02-JUN-16:00 | 10.71 | 13-JUN-06:00 |
July | 180.00 | 01-JUL-00:10 | 301.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 | 02-JUL-16:00 | 9.00 | 18-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 301.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.42 | 07-AUG-16:00 | 12.67 | 16-AUG-21:50 |
September | 180.00 | 01-SEP-00:10 | 301.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 19-SEP-16:00 | 22.38 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 301.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 | 01-OCT-15:20 | 25.45 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 301.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 08-NOV-15:00 | 39.57 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 301.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 46.82 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | |||||
Maximum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 49.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.13 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 20-FEB-16:20 | 175.58 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.24 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.15 | 21-APR-15:20 | 112.77 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.87 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 | 02-JUN-16:00 | 37.51 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.00 | 02-JUL-16:00 | 23.96 | 05-JUL-06:56 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.08 | 07-AUG-16:00 | 33.91 | 30-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 01-OCT-15:20 | 91.60 | 25-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 | 03-NOV-16:00 | 141.80 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.75 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 | 175.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.12 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 175.57 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 21-MAR-16:00 | 165.23 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.14 | 21-APR-15:20 | 112.76 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.87 | 19-MAY-16:00 | 72.67 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 02-JUN-16:00 | 46.78 | 28-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.99 | 02-JUL-16:00 | 42.85 | 05-JUL-07:00 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.07 | 07-AUG-16:00 | 42.89 | 30-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 19-SEP-16:00 | 80.18 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 01-OCT-15:20 | 91.18 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | 08-NOV-15:00 | 141.79 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 167.74 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.85 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 175.57 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1886.18 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 221.46 | 27-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1886.18 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 231.55 | 03-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1886.18 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 21-MAR-16:00 | 220.43 | 02-MAR-05:00 |
April | 2263.36 | 01-APR-00:10 | 1886.18 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.49 | 21-APR-14:00 | 158.42 | 12-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1886.18 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.75 | 21-MAY-14:00 | 109.46 | 02-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1886.18 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 02-JUN-16:00 | 66.64 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1886.18 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.52 | 02-JUL-16:00 | 45.68 | 05-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 1886.18 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.30 | 07-AUG-16:00 | 54.21 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1886.18 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.22 | 19-SEP-14:00 | 118.74 | 30-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1886.18 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.95 | 01-OCT-15:00 | 132.30 | 25-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1886.18 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 192.45 | 17-NOV-04:00 |
December | 2263.36 | 01-DEC-00:10 | 1886.18 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 221.21 | 19-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1886.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.68 | ||||
Maximum of Months | 2263.36 | 1886.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 | 231.55 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.56 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.24 | 20-FEB-16:20 | 176.01 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 21-MAR-16:00 | 165.67 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.82 | 21-APR-15:20 | 113.17 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.55 | 19-MAY-16:00 | 73.05 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.68 | 02-JUN-16:00 | 37.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 02-JUL-16:00 | 20.67 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 | 07-AUG-16:00 | 29.30 | 14-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.52 | 19-SEP-16:00 | 80.57 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 01-OCT-15:20 | 91.59 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 03-NOV-16:00 | 142.22 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 168.19 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 99.68 | 176.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.55 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 176.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 21-MAR-16:00 | 165.66 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.81 | 21-APR-15:20 | 113.16 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 | 19-MAY-16:00 | 73.05 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.67 | 02-JUN-16:00 | 37.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.66 | 02-JUL-16:00 | 35.26 | 18-JUL-21:50 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 | 07-AUG-16:00 | 42.85 | 16-AUG-21:50 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.52 | 19-SEP-16:00 | 80.57 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 01-OCT-15:20 | 91.58 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 | 08-NOV-15:00 | 142.21 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 168.18 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.26 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 99.67 | 176.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 301.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 85.73 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 301.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 | 20-FEB-16:20 | 90.05 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 301.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 21-MAR-16:00 | 84.76 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 301.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.12 | 21-APR-15:20 | 57.90 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 301.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 | 19-MAY-16:00 | 37.38 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 301.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 02-JUN-16:00 | 19.38 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 301.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.46 | 02-JUL-16:00 | 10.57 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 301.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 | 07-AUG-16:00 | 14.84 | 14-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 301.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.11 | 19-SEP-16:00 | 41.22 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 301.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.09 | 01-OCT-15:20 | 46.86 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 301.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 03-NOV-16:00 | 72.76 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 301.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 86.05 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 | |||||
Maximum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 90.05 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 4498.11 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 438.24 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 4498.11 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 456.66 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 4498.11 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.06 | 22-MAR-13:00 | 436.56 | 02-MAR-05:20 |
April | 26988.77 | 01-APR-00:10 | 4498.11 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.27 | 21-APR-14:00 | 315.98 | 12-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 4498.11 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.17 | 21-MAY-14:00 | 221.92 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 4498.11 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.67 | 02-JUN-16:00 | 135.39 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 4498.11 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.16 | 02-JUL-16:00 | 93.09 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 4498.11 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.61 | 07-AUG-16:00 | 110.32 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 4498.11 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.96 | 19-SEP-14:00 | 240.52 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 4498.11 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.27 | 01-OCT-15:00 | 265.16 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 4498.11 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 08-NOV-15:00 | 382.32 | 27-NOV-23:00 |
December | 26988.77 | 01-DEC-00:10 | 4498.11 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 436.98 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.09 | |||||
Maximum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 203.67 | 456.66 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 4498.11 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 443.71 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 4498.11 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 462.07 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 4498.11 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 | 22-MAR-13:00 | 440.76 | 02-MAR-05:20 |
April | 26988.77 | 01-APR-00:10 | 4498.11 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.27 | 21-APR-14:00 | 319.65 | 12-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 4498.11 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.17 | 21-MAY-14:00 | 221.92 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 4498.11 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.67 | 02-JUN-16:00 | 135.40 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 4498.11 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.16 | 02-JUL-16:00 | 93.09 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 4498.11 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.61 | 07-AUG-16:00 | 110.32 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 4498.11 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.96 | 19-SEP-14:00 | 240.66 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 4498.11 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.27 | 01-OCT-15:00 | 268.05 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 4498.11 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 08-NOV-15:00 | 386.16 | 28-NOV-01:00 |
December | 26988.77 | 01-DEC-00:10 | 4498.11 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 443.24 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.09 | |||||
Maximum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 203.67 | 462.07 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1200.92 | 02-JAN-20:10 | 15028.36 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 407.41 | 27-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1200.92 | 01-FEB-20:10 | 15028.36 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 426.03 | 03-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1200.92 | 01-MAR-20:10 | 15028.36 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 11.45 | 21-MAR-16:00 | 403.74 | 02-MAR-05:00 |
April | 2401.70 | 01-APR-00:10 | 1200.92 | 03-APR-19:10 | 15028.36 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 101.38 | 21-APR-14:00 | 287.12 | 12-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1200.92 | 01-MAY-19:10 | 15028.36 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 136.19 | 21-MAY-14:00 | 198.57 | 02-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1200.92 | 01-JUN-19:10 | 15028.36 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 182.27 | 02-JUN-16:00 | 121.21 | 13-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1200.92 | 03-JUL-19:10 | 15028.36 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 175.57 | 02-JUL-16:00 | 83.45 | 05-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 1200.92 | 01-AUG-19:10 | 15028.36 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 162.50 | 07-AUG-16:00 | 98.68 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1200.92 | 01-SEP-19:10 | 15028.36 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 122.58 | 19-SEP-14:00 | 215.38 | 30-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1200.92 | 02-OCT-19:10 | 15028.36 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 109.43 | 01-OCT-15:00 | 239.91 | 25-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1200.92 | 01-NOV-19:10 | 15028.36 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 351.98 | 28-NOV-05:00 |
December | 2401.70 | 01-DEC-00:10 | 1200.92 | 01-DEC-20:10 | 15028.36 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 408.96 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1200.92 | 15028.36 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 83.45 | ||||||
Maximum of Months | 2401.70 | 1200.92 | 15028.36 | 22492.83 | 0.00 | 0.00 | 0.00 | 182.27 | 426.03 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1996.23 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 356.92 | 27-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1996.23 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 375.00 | 03-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1996.23 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 | 21-MAR-16:00 | 359.66 | 02-MAR-05:00 |
April | 2395.44 | 01-APR-00:10 | 1996.23 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.24 | 21-APR-14:00 | 265.65 | 12-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1996.23 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.32 | 21-MAY-14:00 | 193.20 | 02-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1996.23 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.42 | 02-JUN-16:00 | 118.71 | 13-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1996.23 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.86 | 02-JUL-16:00 | 81.61 | 05-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 1996.23 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.08 | 07-AUG-16:00 | 96.71 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1996.23 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.99 | 19-SEP-14:00 | 207.50 | 30-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1996.23 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.13 | 01-OCT-15:00 | 226.94 | 11-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1996.23 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 317.35 | 17-NOV-04:00 |
December | 2395.44 | 01-DEC-00:10 | 1996.23 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 358.26 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.61 | ||||
Maximum of Months | 2395.44 | 1996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.42 | 375.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 24068.66 | 04-JAN-21:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22451.33 | 03-FEB-07:00 | 8945.92 | 8760.57 | 5069.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20889.86 | 02-MAR-05:20 | 11501.89 | 4380.29 | 3041.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20044.93 | 21-APR-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21134.06 | 31-MAY-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22218.41 | 16-JUN-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25745.52 | 18-JUL-20:32 | 51119.52 | 87605.74 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27174.99 | 08-AUG-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29029.23 | 21-SEP-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28847.98 | 05-OCT-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28204.34 | 10-NOV-20:57 | 26837.75 | 59133.87 | 28897.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26610.22 | 01-DEC-21:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 20044.93 | 8945.92 | 4380.29 | 3041.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29029.23 | 51119.52 | 87605.74 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3630.90 | 12-JAN-14:20 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.57 |
February | 3573.95 | 07-FEB-13:40 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 |
March | 3178.32 | 14-MAR-14:10 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 |
April | 3224.24 | 03-APR-14:10 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 0.00 |
May | 3168.96 | 30-MAY-15:10 | 649.74 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 101.95 | 0.00 |
June | 3533.50 | 14-JUN-18:03 | 5457.82 | 5198.04 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 126.95 | 0.00 |
July | 3515.29 | 26-JUL-15:10 | 649.74 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 123.66 | 0.00 |
August | 3606.10 | 29-AUG-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 73.90 | 0.00 |
September | 4376.83 | 19-SEP-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 92.36 | 0.00 |
October | 4580.89 | 03-OCT-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 76.58 | 0.00 |
November | 4023.60 | 09-NOV-13:10 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 |
December | 3158.58 | 16-DEC-13:30 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3158.58 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4580.89 | 5457.82 | 5198.04 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 126.95 | 101.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1724.33 | 12-JAN-21:10 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 |
February | 1906.49 | 21-FEB-20:30 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.03 |
March | 2129.17 | 14-MAR-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 |
April | 2508.78 | 28-APR-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 | 0.00 |
May | 2691.12 | 19-MAY-19:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 29.96 | 0.00 |
June | 2892.68 | 15-JUN-18:40 | 1053.36 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 | 0.00 |
July | 2863.81 | 25-JUL-18:40 | 1053.36 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 0.00 |
August | 2815.83 | 04-AUG-19:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 38.26 | 0.00 |
September | 2677.26 | 01-SEP-18:20 | 2106.72 | 2006.45 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 25.15 | 0.00 |
October | 2507.94 | 04-OCT-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 0.00 |
November | 2079.78 | 09-NOV-21:10 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 |
December | 1533.45 | 15-DEC-22:00 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1533.45 | 1053.36 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2892.68 | 2106.72 | 2006.45 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 42.94 | 47.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1208.57 | 12-JAN-22:00 | 254.59 | 2121.48 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.88 |
February | 1605.50 | 22-FEB-20:55 | 891.07 | 9546.65 | 3357.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.06 |
March | 1939.69 | 16-MAR-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.44 |
April | 2776.49 | 21-APR-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 19.19 | 0.00 |
May | 3161.30 | 19-MAY-19:50 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 65.91 | 0.00 |
June | 3475.49 | 15-JUN-19:50 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 90.11 | 0.00 |
July | 3349.64 | 25-JUL-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 79.86 | 0.00 |
August | 3305.55 | 04-AUG-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 83.75 | 0.00 |
September | 2957.76 | 01-SEP-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 0.00 |
October | 2831.63 | 04-OCT-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 19.32 | 0.00 |
November | 2073.40 | 09-NOV-21:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.63 |
December | 1171.66 | 15-DEC-22:10 | 286.42 | 1591.11 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1171.66 | 222.77 | 1591.11 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3475.49 | 891.07 | 9546.65 | 3357.79 | 0.00 | 0.00 | 0.00 | 0.00 | 90.11 | 130.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 636.95 | 12-JAN-21:20 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.65 |
February | 681.56 | 07-FEB-21:43 | 1958.40 | 6527.87 | 2294.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.10 |
March | 719.31 | 15-MAR-21:00 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 |
April | 1072.38 | 21-APR-18:03 | 1028.16 | 3916.72 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 31.02 | 0.00 |
May | 1518.26 | 19-MAY-18:20 | 342.72 | 1305.57 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 46.44 | 0.00 |
June | 1898.11 | 15-JUN-18:17 | 514.08 | 1958.36 | 688.24 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 | 0.00 |
July | 1740.37 | 03-JUL-18:30 | 171.36 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 54.14 | 0.00 |
August | 1620.51 | 07-AUG-18:20 | 342.72 | 1305.57 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 49.44 | 0.00 |
September | 1208.69 | 01-SEP-18:03 | 1028.16 | 3916.72 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 0.00 |
October | 1088.44 | 04-OCT-19:30 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 | 0.00 |
November | 737.15 | 09-NOV-21:20 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 |
December | 613.97 | 15-DEC-22:10 | 220.32 | 489.59 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 613.97 | 171.36 | 489.59 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1898.11 | 1958.40 | 6527.87 | 2294.12 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 | 57.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37772.34 | 03-JAN-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 125.33 |
February | 37981.64 | 22-FEB-20:53 | 2822.40 | 1814.42 | 18291.20 | 158906.31 | 0.00 | 0.00 | 0.00 | 0.00 | 102.49 |
March | 38300.72 | 15-MAR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 |
April | 39003.71 | 19-APR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 53.67 | 0.00 |
May | 39260.61 | 19-MAY-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 87.75 | 0.00 |
June | 39547.68 | 15-JUN-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 120.81 | 0.00 |
July | 39480.69 | 25-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 109.03 | 0.00 |
August | 39491.63 | 04-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 114.35 | 0.00 |
September | 39077.50 | 01-SEP-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 40.05 | 0.00 |
October | 38881.83 | 04-OCT-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 26.36 | 0.00 |
November | 38216.35 | 09-NOV-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 51.39 |
December | 37602.85 | 15-DEC-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 125.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37602.85 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39547.68 | 2822.40 | 1814.42 | 18291.20 | 158906.31 | 0.00 | 0.00 | 0.00 | 120.81 | 125.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12751.23 | 12-JAN-13:40 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.60 |
February | 13141.08 | 20-FEB-13:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.43 |
March | 12470.16 | 14-MAR-15:10 | 8538.00 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
April | 12415.76 | 01-APR-13:20 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 87.82 | 0.00 |
May | 12265.22 | 19-MAY-21:10 | 15368.40 | 1707.63 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 129.90 | 0.00 |
June | 13050.81 | 14-JUN-18:05 | 71719.20 | 13661.02 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 280.64 | 0.00 |
July | 12868.61 | 26-JUL-18:02 | 71719.20 | 13661.02 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 213.65 | 0.00 |
August | 13033.43 | 07-AUG-21:10 | 15368.40 | 1707.63 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 159.79 | 0.00 |
September | 14766.01 | 19-SEP-15:10 | 8538.00 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 204.96 | 0.00 |
October | 15188.28 | 22-OCT-12:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 |
November | 14099.37 | 11-NOV-10:53 | 68304.00 | 6830.51 | 3251.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.20 |
December | 12507.06 | 16-DEC-13:30 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12265.22 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15188.28 | 71719.20 | 13661.02 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 280.64 | 224.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35773.93 | 12-JAN-21:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780.62 |
February | 37698.30 | 06-FEB-22:00 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.62 |
March | 39181.56 | 16-MAR-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.13 |
April | 44971.09 | 19-APR-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 272.27 | 0.00 |
May | 47460.48 | 19-MAY-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 433.86 | 0.00 |
June | 49889.12 | 15-JUN-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 607.11 | 0.00 |
July | 49416.28 | 25-JUL-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 541.77 | 0.00 |
August | 49314.02 | 04-AUG-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 569.31 | 0.00 |
September | 46701.78 | 19-SEP-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 174.30 | 0.00 |
October | 45727.77 | 04-OCT-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 128.60 | 0.00 |
November | 41568.25 | 09-NOV-21:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.50 |
December | 33750.04 | 15-DEC-22:00 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 33750.04 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49889.12 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 607.11 | 780.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4171.55 | 26-JAN-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.12 |
February | 4153.70 | 09-FEB-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.74 |
March | 4173.62 | 01-MAR-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.42 |
April | 4217.06 | 17-APR-18:01 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.10 |
May | 4026.31 | 01-MAY-18:02 | 831.60 | 2556.97 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 |
June | 3879.46 | 12-JUN-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 | 0.00 |
July | 3624.77 | 24-JUL-18:02 | 831.60 | 2556.97 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 54.58 | 0.00 |
August | 3709.53 | 22-AUG-18:02 | 831.60 | 2556.97 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 52.19 | 0.00 |
September | 4074.18 | 24-SEP-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 0.00 |
October | 4127.84 | 23-OCT-18:01 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.68 |
November | 4127.98 | 05-NOV-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 |
December | 4150.67 | 27-DEC-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3624.77 | 216.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4217.06 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 54.58 | 93.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4066.59 | 26-JAN-16:12 | 583.20 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.56 |
February | 4151.76 | 07-FEB-21:41 | 1602.00 | 4261.12 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.46 |
March | 4275.17 | 20-MAR-19:41 | 1386.00 | 4787.77 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.16 |
April | 4353.62 | 17-APR-18:01 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.21 |
May | 4250.08 | 01-MAY-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.10 |
June | 4096.19 | 07-JUN-06:51 | 619.20 | 2144.92 | 1896.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 | 0.00 |
July | 3734.73 | 16-JUL-06:51 | 763.20 | 1570.39 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 0.00 |
August | 4060.08 | 23-AUG-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 0.00 |
September | 4320.94 | 24-SEP-21:31 | 1386.00 | 4069.61 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.25 |
October | 4321.41 | 19-OCT-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 |
November | 4243.85 | 09-NOV-22:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.44 |
December | 4057.48 | 27-DEC-16:12 | 583.20 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3734.73 | 360.00 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4353.62 | 1800.00 | 4787.77 | 1896.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 91.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 704.67 | 12-JAN-14:20 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.91 |
February | 651.97 | 06-FEB-13:40 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 |
March | 541.26 | 14-MAR-13:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
April | 516.61 | 01-APR-13:30 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 0.00 |
May | 460.09 | 19-MAY-20:20 | 0.00 | 267.83 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 | 0.00 |
June | 505.55 | 05-JUN-19:20 | 0.00 | 300.93 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 0.00 |
July | 524.50 | 02-JUL-19:10 | 0.00 | 300.93 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 | 0.00 |
August | 546.20 | 27-AUG-13:40 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 | 0.00 |
September | 676.01 | 19-SEP-13:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 0.00 |
October | 774.52 | 22-OCT-13:20 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
November | 717.43 | 09-NOV-12:40 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 |
December | 633.39 | 16-DEC-13:30 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 460.09 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 774.52 | 0.00 | 300.93 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 21.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1597.58 | 21-JAN-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 |
February | 1618.77 | 05-FEB-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.87 |
March | 1627.24 | 30-MAR-19:51 | 1386.00 | 3010.11 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.82 |
April | 1604.82 | 11-APR-08:62 | 216.00 | 794.67 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 |
May | 1574.28 | 01-MAY-21:51 | 1800.00 | 2016.77 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.57 |
June | 1495.95 | 10-JUN-06:51 | 763.20 | 987.32 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
July | 1332.30 | 16-JUL-06:51 | 763.20 | 987.32 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 | 0.00 |
August | 1505.44 | 23-AUG-08:51 | 360.00 | 1324.45 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 |
September | 1613.82 | 24-SEP-21:31 | 1386.00 | 2558.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 |
October | 1622.27 | 20-OCT-21:51 | 1800.00 | 2016.77 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 |
November | 1621.32 | 26-NOV-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.32 |
December | 1626.47 | 17-DEC-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1332.30 | 216.00 | 794.67 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1627.24 | 1800.00 | 3010.11 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 | 29.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3729.68 | 07-JAN-09:02 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.99 |
February | 3741.99 | 09-FEB-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.61 |
March | 3727.84 | 01-MAR-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.11 |
April | 3694.83 | 11-APR-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.21 |
May | 3612.98 | 12-MAY-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.59 |
June | 3553.44 | 10-JUN-08:62 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 | 0.00 |
July | 3231.42 | 11-JUL-08:61 | 252.00 | 1474.81 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 27.65 | 0.00 |
August | 3452.83 | 23-AUG-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 0.00 |
September | 3555.66 | 11-SEP-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 |
October | 3612.27 | 31-OCT-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.56 |
November | 3722.98 | 16-NOV-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.72 |
December | 3747.06 | 30-DEC-09:02 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3231.42 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3747.06 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 27.65 | 134.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3654.08 | 30-JAN-09:02 | 216.00 | 1263.97 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.63 |
February | 3686.79 | 09-FEB-09:02 | 216.00 | 1263.97 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.74 |
March | 3709.26 | 30-MAR-19:51 | 1386.00 | 4787.77 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.46 |
April | 3845.79 | 28-APR-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.93 |
May | 3807.52 | 27-MAY-08:32 | 270.00 | 1340.58 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 |
June | 3699.29 | 02-JUN-07:52 | 464.40 | 1263.97 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.80 |
July | 3461.01 | 16-JUL-06:51 | 763.20 | 1570.39 | 1306.30 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 0.00 |
August | 3697.44 | 23-AUG-08:32 | 180.00 | 1053.31 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 |
September | 3842.11 | 30-SEP-08:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 |
October | 3837.56 | 20-OCT-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.18 |
November | 3783.38 | 10-NOV-09:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.52 |
December | 3654.27 | 07-DEC-09:02 | 216.00 | 1263.97 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3461.01 | 180.00 | 1053.31 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3845.79 | 1386.00 | 4787.77 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 124.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1812.87 | 12-JAN-15:10 | 754.45 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.73 |
February | 1904.42 | 21-FEB-16:13 | 7544.52 | 3143.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
March | 2159.16 | 16-MAR-18:03 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 |
April | 2680.13 | 19-APR-18:15 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.31 | 0.00 |
May | 3115.06 | 19-MAY-18:15 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.63 | 0.00 |
June | 3458.94 | 15-JUN-18:25 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 | 0.00 |
July | 3317.75 | 26-JUL-18:15 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.28 | 0.00 |
August | 3205.28 | 07-AUG-18:15 | 3520.78 | 3353.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.64 | 0.00 |
September | 2945.70 | 19-SEP-18:03 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 | 0.00 |
October | 2849.14 | 05-OCT-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.51 | 0.00 |
November | 2248.64 | 03-NOV-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 |
December | 1517.78 | 16-DEC-14:20 | 754.45 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1517.78 | 754.45 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3458.94 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 | 67.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4619.43 | 22-JAN-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.26 |
February | 4614.02 | 09-FEB-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.95 |
March | 4623.68 | 17-MAR-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 |
April | 4732.62 | 17-APR-18:01 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 |
May | 4498.10 | 01-MAY-18:02 | 831.60 | 2556.97 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 |
June | 4331.66 | 12-JUN-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 | 0.00 |
July | 4108.64 | 24-JUL-18:02 | 831.60 | 2556.97 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 54.60 | 0.00 |
August | 4220.13 | 15-AUG-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 | 0.00 |
September | 4577.48 | 24-SEP-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 | 0.00 |
October | 4627.09 | 24-OCT-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 |
November | 4621.85 | 05-NOV-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.92 |
December | 4592.44 | 27-DEC-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4108.64 | 216.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4732.62 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 54.60 | 89.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4476.82 | 27-JAN-16:12 | 583.20 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.49 |
February | 4619.79 | 20-FEB-21:11 | 1386.00 | 4787.77 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.59 |
March | 4785.55 | 20-MAR-19:41 | 1386.00 | 4787.77 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.14 |
April | 4925.57 | 17-APR-18:01 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.12 |
May | 4762.45 | 01-MAY-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.84 |
June | 4569.19 | 07-JUN-06:51 | 619.20 | 2144.92 | 1896.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.22 | 0.00 |
July | 4090.11 | 24-JUL-18:02 | 831.60 | 2556.67 | 726.90 | 0.00 | 0.00 | 0.00 | 0.00 | 54.33 | 0.00 |
August | 4590.04 | 23-AUG-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 0.00 |
September | 4820.11 | 26-SEP-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.69 |
October | 4816.21 | 19-OCT-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.73 |
November | 4738.69 | 09-NOV-22:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.90 |
December | 4467.84 | 07-DEC-17:01 | 680.40 | 938.40 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4090.11 | 360.00 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4925.57 | 1800.00 | 4787.77 | 1896.25 | 0.00 | 0.00 | 0.00 | 0.00 | 54.33 | 75.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2479.09 | 26-JAN-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.27 |
February | 2459.21 | 02-FEB-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.45 |
March | 2452.28 | 01-MAR-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.89 |
April | 2377.72 | 17-APR-18:01 | 1386.00 | 2679.00 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 |
May | 2316.89 | 06-MAY-08:62 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 |
June | 2269.62 | 10-JUN-08:62 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 0.00 |
July | 2059.26 | 05-JUL-18:02 | 831.60 | 1607.40 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 33.23 | 0.00 |
August | 2179.30 | 23-AUG-08:62 | 216.00 | 794.67 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 0.00 |
September | 2365.70 | 24-SEP-15:12 | 324.00 | 596.00 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 5.65 | 0.00 |
October | 2406.03 | 24-OCT-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
November | 2451.35 | 17-NOV-09:02 | 216.00 | 794.67 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.81 |
December | 2476.57 | 27-DEC-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2059.26 | 216.00 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2479.09 | 1386.00 | 2679.00 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 33.23 | 52.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18466.08 | 12-JAN-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.86 |
February | 19988.96 | 06-FEB-22:10 | 53977.54 | 5997.48 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 |
March | 21096.13 | 15-MAR-21:52 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 |
April | 23546.74 | 19-APR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 0.00 |
May | 24403.71 | 19-MAY-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 81.93 | 0.00 |
June | 25116.86 | 05-JUN-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 121.06 | 0.00 |
July | 25011.74 | 25-JUL-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 | 0.00 |
August | 25091.85 | 07-AUG-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 101.09 | 0.00 |
September | 23529.47 | 12-SEP-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 0.00 |
October | 22967.34 | 04-OCT-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 0.00 |
November | 20871.27 | 09-NOV-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.62 |
December | 18505.43 | 15-DEC-23:00 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18466.08 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25116.86 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 121.06 | 214.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19921.01 | 03-JAN-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.47 |
February | 21423.30 | 06-FEB-22:10 | 53977.54 | 5997.48 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 |
March | 22374.13 | 15-MAR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.18 |
April | 24801.42 | 19-APR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 0.00 |
May | 25622.23 | 19-MAY-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 81.93 | 0.00 |
June | 26319.24 | 05-JUN-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 121.06 | 0.00 |
July | 26210.47 | 25-JUL-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 | 0.00 |
August | 26280.43 | 07-AUG-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 101.09 | 0.00 |
September | 24748.35 | 12-SEP-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 0.00 |
October | 24175.22 | 04-OCT-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 0.00 |
November | 22165.21 | 09-NOV-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.63 |
December | 20014.07 | 15-DEC-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19921.01 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26319.24 | 53977.54 | 5997.48 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 121.06 | 174.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27427.49 | 29-JAN-11:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 168.31 |
February | 28761.01 | 19-FEB-11:40 | 1601.14 | 800.61 | 30056.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 66.96 |
March | 29066.31 | 19-MAR-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 71.18 |
April | 30718.66 | 30-APR-10:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 5.54 | 0.00 |
May | 31035.26 | 21-MAY-10:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 75.12 | 0.00 |
June | 31380.98 | 18-JUN-10:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 107.49 | 0.00 |
July | 31632.33 | 02-JUL-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 102.50 | 0.00 |
August | 31356.97 | 06-AUG-10:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 99.03 | 0.00 |
September | 30988.52 | 17-SEP-10:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 75.36 | 0.00 |
October | 30702.22 | 01-OCT-10:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 40.00 | 0.00 |
November | 28223.45 | 03-NOV-10:50 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 88.45 |
December | 27216.93 | 10-DEC-11:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 103.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27216.93 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31632.33 | 1601.14 | 800.61 | 30056.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 107.49 | 168.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4747.89 | 12-JAN-14:30 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 |
February | 6124.10 | 22-FEB-13:50 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.99 |
March | 6449.51 | 14-MAR-15:10 | 1330.80 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
April | 8640.26 | 30-APR-13:00 | 532.32 | 443.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.23 | 0.00 |
May | 9059.48 | 30-MAY-14:10 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.48 | 0.00 |
June | 9724.98 | 05-JUN-15:10 | 1330.80 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 | 0.00 |
July | 10470.71 | 03-JUL-12:50 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.15 | 0.00 |
August | 10160.23 | 08-AUG-13:30 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.81 | 0.00 |
September | 10053.47 | 15-SEP-13:00 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.09 | 0.00 |
October | 9514.15 | 03-OCT-13:40 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.18 | 0.00 |
November | 6420.45 | 03-NOV-14:10 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 |
December | 3283.38 | 16-DEC-13:50 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3283.38 | 532.32 | 443.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10470.71 | 1330.80 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 | 122.28 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.488121E+12 | 314056.28 | 03-JAN-20:40 | 0.483492E+12 | 409811.41 | 26-JAN-18:00 |
February | 0.451618E+12 | 324857.18 | 22-FEB-20:40 | 0.415311E+12 | 391293.99 | 08-FEB-18:00 |
March | 0.510221E+12 | 344966.88 | 14-MAR-18:10 | 0.424077E+12 | 394499.00 | 01-MAR-18:49 |
April | 0.564005E+12 | 413879.97 | 19-APR-19:10 | 0.365057E+12 | 329463.46 | 03-APR-17:30 |
May | 0.651196E+12 | 439800.09 | 19-MAY-19:10 | 0.358627E+12 | 318295.96 | 01-MAY-17:30 |
June | 0.705481E+12 | 476535.94 | 05-JUN-19:10 | 0.336287E+12 | 305401.33 | 02-JUN-17:19 |
July | 0.762606E+12 | 468189.95 | 25-JUL-19:10 | 0.340847E+12 | 296695.51 | 03-JUL-17:40 |
August | 0.725797E+12 | 466620.84 | 04-AUG-19:10 | 0.341168E+12 | 296899.37 | 31-AUG-17:30 |
September | 0.662758E+12 | 438339.89 | 19-SEP-18:10 | 0.336401E+12 | 306479.46 | 29-SEP-17:49 |
October | 0.591963E+12 | 435608.29 | 03-OCT-19:30 | 0.360222E+12 | 318363.58 | 31-OCT-17:30 |
November | 0.494061E+12 | 337918.22 | 09-NOV-20:00 | 0.412725E+12 | 381908.40 | 27-NOV-21:00 |
December | 0.485102E+12 | 303652.73 | 15-DEC-20:10 | 0.515442E+12 | 429664.05 | 26-DEC-19:10 |
Annual Sum or Average | 0.709293E+13 | 0.468966E+13 | ||||
Minimum of Months | 0.451618E+12 | 303652.73 | 0.336287E+12 | 296695.51 | ||
Maximum of Months | 0.762606E+12 | 476535.94 | 0.515442E+12 | 429664.05 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.129696E+12 | 0.316648E+11 | 0.141138E+12 | 0.715096E+11 | 0.904040E+11 | 0.438175E+09 | 0.00 | 0.195606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117116E+12 | 0.270885E+11 | 0.127470E+12 | 0.645894E+11 | 0.825047E+11 | 0.327746E+09 | 0.00 | 0.291779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129400E+12 | 0.278389E+11 | 0.141191E+12 | 0.715122E+11 | 0.924345E+11 | 0.263787E+09 | 0.00 | 0.438793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125475E+12 | 0.247758E+11 | 0.136545E+12 | 0.692026E+11 | 0.941128E+11 | 0.142394E+09 | 0.00 | 0.110161E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129561E+12 | 0.237425E+11 | 0.141170E+12 | 0.715109E+11 | 0.101552E+12 | 0.128548E+09 | 0.00 | 0.179794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125286E+12 | 0.220448E+11 | 0.136635E+12 | 0.692051E+11 | 0.103794E+12 | 0.124178E+09 | 0.00 | 0.244758E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129759E+12 | 0.231889E+11 | 0.141079E+12 | 0.715085E+11 | 0.107360E+12 | 0.128343E+09 | 0.00 | 0.285828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129426E+12 | 0.247758E+11 | 0.141202E+12 | 0.715122E+11 | 0.105840E+12 | 0.128333E+09 | 0.00 | 0.249149E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125517E+12 | 0.259814E+11 | 0.136555E+12 | 0.692027E+11 | 0.100103E+12 | 0.124623E+09 | 0.00 | 0.201631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129662E+12 | 0.291060E+11 | 0.141127E+12 | 0.715095E+11 | 0.978338E+11 | 0.133362E+09 | 0.00 | 0.118848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125477E+12 | 0.300533E+11 | 0.136629E+12 | 0.692036E+11 | 0.894241E+11 | 0.297343E+09 | 0.00 | 0.393911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129767E+12 | 0.321323E+11 | 0.141079E+12 | 0.715085E+11 | 0.899064E+11 | 0.570354E+09 | 0.00 | 0.164330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152614E+13 | 0.322393E+12 | 0.166182E+13 | 0.841975E+12 | 0.115527E+13 | 0.280719E+10 | 0.00 | 0.153861E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117116E+12 | 0.220448E+11 | 0.127470E+12 | 0.645894E+11 | 0.825047E+11 | 0.124178E+09 | 0.00 | 0.164330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129767E+12 | 0.321323E+11 | 0.141202E+12 | 0.715122E+11 | 0.107360E+12 | 0.570354E+09 | 0.00 | 0.285828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.947033E+11 | 0.00 | 0.236871E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.642813E+11 | 0.00 | 0.213826E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.415473E+11 | 0.00 | 0.230506E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.577844E+10 | 0.00 | 0.212323E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 69334911.61 | 0.00 | 0.206579E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 1034414.48 | 0.00 | 0.189172E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 8406726.39 | 0.00 | 0.189019E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 5361076.74 | 0.00 | 0.189124E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.132663E+09 | 0.00 | 0.189298E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.158326E+10 | 0.00 | 0.206736E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.531743E+11 | 0.00 | 0.212460E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.133048E+12 | 0.00 | 0.230574E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.394333E+12 | 0.00 | 0.250649E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 1034414.48 | 0.00 | 0.189019E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.133048E+12 | 0.00 | 0.236871E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 121238.68 | 02-JAN-20:10 | 20502.98 | 01-JAN-00:10 | 89286.95 | 02-JAN-07:10 | 50420.89 | 02-JAN-07:19 | 41012.82 | 12-JAN-21:10 | 630.24 | 28-JAN-05:00 | 0.00 | 01-JAN-00:10 |
February | 121238.68 | 01-FEB-20:10 | 20502.98 | 01-FEB-00:10 | 89286.95 | 01-FEB-07:10 | 50420.89 | 01-FEB-07:19 | 43057.79 | 06-FEB-22:10 | 667.91 | 03-FEB-06:00 | 0.00 | 01-FEB-00:10 |
March | 121238.68 | 01-MAR-20:10 | 20502.98 | 01-MAR-00:10 | 89286.95 | 01-MAR-07:10 | 50420.89 | 01-MAR-07:19 | 44371.42 | 15-MAR-21:10 | 628.40 | 02-MAR-04:00 | 0.00 | 01-MAR-00:10 |
April | 121238.68 | 03-APR-19:10 | 20502.98 | 01-APR-00:10 | 89286.95 | 03-APR-06:10 | 50420.89 | 03-APR-06:19 | 49024.53 | 19-APR-21:10 | 273.36 | 12-APR-05:00 | 0.00 | 01-APR-00:10 |
May | 121238.68 | 01-MAY-19:10 | 20502.98 | 01-MAY-00:10 | 89286.95 | 01-MAY-06:10 | 50420.89 | 01-MAY-06:19 | 51607.92 | 19-MAY-20:10 | 93.39 | 02-MAY-08:09 | 0.00 | 01-MAY-00:10 |
June | 121238.68 | 01-JUN-19:10 | 20502.98 | 01-JUN-00:10 | 89286.95 | 01-JUN-06:10 | 50420.89 | 01-JUN-06:19 | 54998.50 | 15-JUN-20:10 | 48.51 | 29-JUN-08:09 | 0.00 | 01-JUN-00:10 |
July | 121238.68 | 03-JUL-19:10 | 20502.98 | 01-JUL-00:10 | 89286.95 | 03-JUL-06:10 | 50420.89 | 03-JUL-06:19 | 54724.47 | 25-JUL-20:10 | 49.24 | 07-JUL-08:09 | 0.00 | 01-JUL-00:10 |
August | 121238.68 | 01-AUG-19:10 | 20502.98 | 01-AUG-00:10 | 89286.95 | 01-AUG-06:10 | 50420.89 | 01-AUG-06:19 | 54877.36 | 04-AUG-20:10 | 49.26 | 24-AUG-08:00 | 0.00 | 01-AUG-00:10 |
September | 121238.68 | 01-SEP-19:10 | 20502.98 | 01-SEP-00:10 | 89286.95 | 01-SEP-06:10 | 50420.89 | 01-SEP-06:19 | 51768.51 | 22-SEP-20:10 | 108.42 | 30-SEP-05:00 | 0.00 | 01-SEP-00:10 |
October | 121238.68 | 02-OCT-19:10 | 20502.98 | 01-OCT-00:10 | 89286.95 | 02-OCT-06:10 | 50420.89 | 02-OCT-06:19 | 52092.81 | 03-OCT-20:10 | 166.53 | 25-OCT-05:00 | 0.00 | 01-OCT-00:10 |
November | 121238.68 | 01-NOV-19:10 | 20502.98 | 01-NOV-00:10 | 89286.95 | 01-NOV-06:10 | 50420.89 | 01-NOV-06:19 | 44955.67 | 09-NOV-21:10 | 527.62 | 28-NOV-04:00 | 0.00 | 01-NOV-00:10 |
December | 121238.68 | 01-DEC-20:10 | 20502.98 | 01-DEC-00:10 | 89286.95 | 01-DEC-07:10 | 50420.89 | 01-DEC-07:19 | 40690.15 | 15-DEC-22:10 | 678.66 | 27-DEC-04:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 121238.68 | 20502.98 | 89286.95 | 50420.89 | 40690.15 | 48.51 | 0.00 | |||||||
Maximum of Months | 121238.68 | 20502.98 | 89286.95 | 50420.89 | 54998.50 | 678.66 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 41557.10 | 03-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61436.92 | 20-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90496.28 | 14-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 134228.92 | 19-APR-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 162509.84 | 19-MAY-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 196774.46 | 14-JUN-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 189184.05 | 03-JUL-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 185712.17 | 04-AUG-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 161725.04 | 20-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 151820.01 | 04-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75081.83 | 03-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32029.40 | 15-DEC-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 32029.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 196774.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 314056.28 | 03-JAN-20:40 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 39584.70 | 50.56 | 0.00 | 32939.59 | 0.00 |
February | 324857.18 | 22-FEB-20:40 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 40968.33 | 53.33 | 0.00 | 42017.59 | 0.00 |
March | 344966.88 | 14-MAR-18:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 42648.08 | 47.91 | 0.00 | 65940.57 | 0.00 |
April | 413879.97 | 19-APR-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 47478.06 | 47.91 | 0.00 | 124523.13 | 0.00 |
May | 439800.09 | 19-MAY-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 50510.06 | 47.91 | 0.00 | 147749.76 | 0.00 |
June | 476535.94 | 05-JUN-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 54114.12 | 47.91 | 0.00 | 180540.77 | 0.00 |
July | 468189.95 | 25-JUL-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 53809.05 | 47.97 | 0.00 | 172837.26 | 0.00 |
August | 466620.84 | 04-AUG-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 53835.24 | 47.91 | 0.00 | 171242.93 | 0.00 |
September | 438339.89 | 19-SEP-18:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 49928.22 | 47.91 | 0.00 | 152008.07 | 0.00 |
October | 435608.29 | 03-OCT-19:30 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 50610.07 | 47.91 | 0.00 | 143442.69 | 0.00 |
November | 337918.22 | 09-NOV-20:00 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 43626.79 | 47.91 | 0.00 | 52412.72 | 0.00 |
December | 303652.73 | 15-DEC-20:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 38461.94 | 47.91 | 0.00 | 23676.75 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 303652.73 | 107831.13 | 77688.87 | 20502.98 | 11860.16 | 38461.94 | 47.91 | 0.00 | 23676.75 | 0.00 | |
Maximum of Months | 476535.94 | 121238.68 | 86555.31 | 20502.98 | 29010.56 | 54114.12 | 53.33 | 0.00 | 180540.77 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 175087.69 | 28-JAN-05:00 | 0.00 | 241650.99 | 25-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 186565.42 | 03-FEB-06:00 | 0.00 | 241626.20 | 03-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 176548.13 | 02-MAR-04:00 | 0.00 | 238101.60 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 69177.92 | 12-APR-05:00 | 0.00 | 227756.91 | 04-APR-20:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 13922.09 | 02-MAY-08:09 | 0.00 | 217095.02 | 01-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 175.83 | 29-JUN-08:09 | 0.00 | 203875.59 | 01-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 386.17 | 07-JUL-08:09 | 0.00 | 195398.00 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 375.39 | 24-AUG-08:00 | 0.00 | 195954.34 | 30-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 19032.47 | 30-SEP-05:00 | 0.00 | 203258.66 | 28-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 38189.55 | 25-OCT-05:00 | 0.00 | 217123.75 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 144595.75 | 28-NOV-04:00 | 0.00 | 228567.37 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 189138.04 | 27-DEC-04:00 | 0.00 | 236348.43 | 29-DEC-21:49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 175.83 | 0.00 | 195398.00 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 189138.04 | 0.00 | 241650.99 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.88 | 1.17 | 24.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 24.88 | 1.17 | 24.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.88 | 1.17 | 24.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.75 | 2.67 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.78 | 4.33 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.85 | 4.00 | 21.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 22.06 | 4.17 | 22.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.90 | 4.50 | 21.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21.86 | 6.00 | 21.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.79 | 3.17 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 29.50 | 21.86 | 29.50 | 21.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.06 | 6.00 | 22.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.72 | 1.00 | 21.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.82 | 1.67 | 21.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.92 | 4.17 | 21.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.03 | 5.83 | 22.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 22.10 | 5.50 | 22.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 22.22 | 9.67 | 22.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.24 | 7.17 | 22.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 22.18 | 8.33 | 22.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 22.08 | 5.33 | 22.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.84 | 0.33 | 21.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 49.00 | 22.12 | 49.00 | 22.12 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 22.24 | 9.67 | 22.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.96 | 4.17 | 21.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 22.13 | 7.33 | 22.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.31 | 5.83 | 22.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 22.39 | 9.50 | 22.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 22.27 | 8.83 | 22.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 22.25 | 10.33 | 22.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.97 | 3.50 | 21.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 50.33 | 22.22 | 50.33 | 22.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 22.39 | 10.33 | 22.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.75 | 1.17 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.76 | 2.67 | 21.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.79 | 4.33 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.97 | 4.17 | 21.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.84 | 4.00 | 21.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.85 | 3.83 | 21.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.77 | 1.67 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.00 | 21.84 | 22.00 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.97 | 4.33 | 21.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 21.69 | 0.50 | 21.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.67 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 24.65 | 0.67 | 24.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.67 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 559.83 | 23.82 | 1.50 | 23.82 | 0.00 | 23.82 |
February | 621.33 | 23.70 | 4.50 | 23.70 | 0.00 | 23.70 |
March | 724.50 | 23.73 | 0.00 | 23.73 | 0.00 | 23.73 |
April | 626.00 | 23.97 | 0.00 | 23.97 | 0.00 | 23.97 |
May | 447.00 | 24.00 | 63.67 | 24.00 | 0.00 | 24.00 |
June | 212.67 | 24.00 | 95.67 | 24.00 | 8.00 | 24.00 |
July | 109.17 | 24.00 | 654.83 | 24.00 | 109.17 | 24.00 |
August | 28.17 | 24.00 | 534.00 | 24.00 | 28.17 | 24.00 |
September | 21.83 | 24.00 | 473.50 | 24.00 | 21.50 | 24.00 |
October | 32.67 | 24.00 | 275.17 | 24.00 | 0.00 | 24.00 |
November | 369.67 | 23.99 | 17.83 | 23.99 | 0.00 | 23.99 |
December | 608.83 | 23.84 | 0.00 | 23.84 | 0.00 | 23.84 |
Annual Sum or Average | 4361.67 | 23.86 | 2120.67 | 23.91 | 166.83 | 23.91 |
Minimum of Months | 21.83 | 23.70 | 0.00 | 23.70 | 0.00 | 23.70 |
Maximum of Months | 724.50 | 24.00 | 654.83 | 24.00 | 109.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 601.33 | 21.66 | 135.67 | 21.76 | 81.33 | 21.69 |
February | 532.83 | 21.86 | 105.33 | 21.89 | 68.50 | 21.80 |
March | 573.33 | 21.99 | 83.00 | 21.95 | 63.67 | 21.87 |
April | 419.83 | 22.40 | 110.67 | 22.71 | 4.50 | 22.70 |
May | 295.17 | 22.74 | 296.67 | 23.36 | 1.50 | 23.36 |
June | 128.33 | 23.16 | 487.67 | 23.79 | 19.50 | 23.79 |
July | 366.83 | 23.70 | 727.17 | 23.79 | 363.00 | 23.77 |
August | 232.17 | 23.38 | 619.33 | 23.73 | 156.17 | 23.71 |
September | 308.33 | 23.03 | 529.00 | 23.50 | 174.67 | 23.49 |
October | 356.00 | 22.24 | 300.33 | 23.02 | 18.17 | 23.04 |
November | 509.50 | 21.83 | 165.00 | 22.14 | 48.00 | 22.07 |
December | 613.50 | 21.58 | 195.67 | 21.53 | 171.00 | 21.44 |
Annual Sum or Average | 4937.17 | 22.25 | 3755.50 | 22.82 | 1170.00 | 22.79 |
Minimum of Months | 128.33 | 21.58 | 83.00 | 21.53 | 1.50 | 21.44 |
Maximum of Months | 613.50 | 23.70 | 727.17 | 23.79 | 363.00 | 23.79 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 704.83 | 22.81 | 0.00 | 22.81 | 0.00 | 22.81 |
February | 651.83 | 23.04 | 0.17 | 23.04 | 0.00 | 23.04 |
March | 652.67 | 23.09 | 2.67 | 23.10 | 0.00 | 23.10 |
April | 443.17 | 23.42 | 23.17 | 23.45 | 0.00 | 23.45 |
May | 194.83 | 23.59 | 220.83 | 23.77 | 3.67 | 23.77 |
June | 58.17 | 23.91 | 467.67 | 23.96 | 25.17 | 23.96 |
July | 443.83 | 23.97 | 742.50 | 23.97 | 443.83 | 23.97 |
August | 195.50 | 23.96 | 689.67 | 23.95 | 195.50 | 23.96 |
September | 260.00 | 23.87 | 545.33 | 23.91 | 232.33 | 23.91 |
October | 268.33 | 23.34 | 238.17 | 23.61 | 36.67 | 23.62 |
November | 575.83 | 23.07 | 8.67 | 23.08 | 0.00 | 23.08 |
December | 733.33 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
Annual Sum or Average | 5182.33 | 23.21 | 2938.83 | 23.48 | 937.17 | 23.52 |
Minimum of Months | 58.17 | 22.72 | 0.00 | 22.72 | 0.00 | 22.72 |
Maximum of Months | 733.33 | 23.97 | 742.50 | 23.97 | 443.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.39 | 0.00 | 22.39 | 0.00 | 22.39 |
February | 671.83 | 22.68 | 0.00 | 22.68 | 0.00 | 22.68 |
March | 739.67 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
April | 600.50 | 23.55 | 1.83 | 23.56 | 0.00 | 23.56 |
May | 288.00 | 23.80 | 132.83 | 23.86 | 0.00 | 23.86 |
June | 70.83 | 23.97 | 329.00 | 23.98 | 0.00 | 23.98 |
July | 129.50 | 23.96 | 732.83 | 23.98 | 129.50 | 23.98 |
August | 32.83 | 23.95 | 605.33 | 23.98 | 32.83 | 23.98 |
September | 102.17 | 23.70 | 471.33 | 23.91 | 37.50 | 23.91 |
October | 394.83 | 23.43 | 136.83 | 23.57 | 0.00 | 23.57 |
November | 692.83 | 22.90 | 0.00 | 22.90 | 0.00 | 22.90 |
December | 744.00 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
Annual Sum or Average | 5211.00 | 22.94 | 2410.00 | 23.27 | 199.83 | 23.29 |
Minimum of Months | 32.83 | 22.22 | 0.00 | 22.22 | 0.00 | 22.22 |
Maximum of Months | 744.00 | 23.97 | 732.83 | 23.98 | 129.50 | 23.98 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.23 | 62.33 | 21.21 | 62.33 | 21.20 |
February | 672.00 | 21.52 | 36.33 | 21.49 | 36.33 | 21.47 |
March | 744.00 | 21.84 | 11.00 | 21.83 | 11.00 | 21.82 |
April | 689.00 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
May | 423.83 | 23.35 | 76.33 | 23.45 | 0.00 | 23.45 |
June | 113.50 | 23.66 | 234.00 | 23.87 | 0.00 | 23.87 |
July | 157.33 | 23.75 | 711.67 | 23.88 | 155.33 | 23.86 |
August | 107.00 | 23.45 | 449.33 | 23.83 | 40.17 | 23.82 |
September | 275.83 | 23.22 | 330.17 | 23.56 | 49.83 | 23.55 |
October | 633.50 | 22.73 | 57.83 | 22.83 | 1.83 | 22.83 |
November | 720.00 | 21.75 | 0.00 | 21.75 | 0.00 | 21.75 |
December | 744.00 | 21.16 | 66.67 | 21.15 | 66.67 | 21.14 |
Annual Sum or Average | 6024.00 | 22.13 | 2035.67 | 22.52 | 423.50 | 22.52 |
Minimum of Months | 107.00 | 21.16 | 0.00 | 21.15 | 0.00 | 21.14 |
Maximum of Months | 744.00 | 23.75 | 711.67 | 23.88 | 155.33 | 23.87 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 172.83 | 24.00 | 741.17 | 24.00 | 172.83 | 24.00 |
February | 160.00 | 24.00 | 669.50 | 24.00 | 160.00 | 24.00 |
March | 180.00 | 24.00 | 742.83 | 24.00 | 180.00 | 24.00 |
April | 266.17 | 24.00 | 720.00 | 24.00 | 266.17 | 24.00 |
May | 400.50 | 24.00 | 744.00 | 24.00 | 400.50 | 24.00 |
June | 524.33 | 24.00 | 720.00 | 24.00 | 524.33 | 24.00 |
July | 653.17 | 24.00 | 744.00 | 24.00 | 653.17 | 24.00 |
August | 630.00 | 24.00 | 744.00 | 24.00 | 630.00 | 24.00 |
September | 604.33 | 24.00 | 720.00 | 24.00 | 604.33 | 24.00 |
October | 430.00 | 24.00 | 744.00 | 24.00 | 430.00 | 24.00 |
November | 199.50 | 24.00 | 720.00 | 24.00 | 199.50 | 24.00 |
December | 154.50 | 24.00 | 740.50 | 24.00 | 154.50 | 24.00 |
Annual Sum or Average | 4375.33 | 24.00 | 8750.00 | 24.00 | 4375.33 | 24.00 |
Minimum of Months | 154.50 | 24.00 | 669.50 | 24.00 | 154.50 | 24.00 |
Maximum of Months | 653.17 | 24.00 | 744.00 | 24.00 | 653.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 536.00 | 21.94 | 107.67 | 22.23 | 11.17 | 22.21 |
February | 424.50 | 22.37 | 107.50 | 22.63 | 12.17 | 22.60 |
March | 401.33 | 22.60 | 114.00 | 22.87 | 6.00 | 22.85 |
April | 206.50 | 23.43 | 242.00 | 23.74 | 0.00 | 23.74 |
May | 82.17 | 23.95 | 474.67 | 23.99 | 13.17 | 23.99 |
June | 40.33 | 24.00 | 662.17 | 24.00 | 26.17 | 24.00 |
July | 261.17 | 24.00 | 744.00 | 24.00 | 261.17 | 24.00 |
August | 143.50 | 24.00 | 736.17 | 24.00 | 143.50 | 24.00 |
September | 199.33 | 23.98 | 647.67 | 23.99 | 194.67 | 24.00 |
October | 128.00 | 23.65 | 534.50 | 23.93 | 81.83 | 23.94 |
November | 380.00 | 22.21 | 193.17 | 22.81 | 1.17 | 22.82 |
December | 580.17 | 21.85 | 101.17 | 22.06 | 24.00 | 22.03 |
Annual Sum or Average | 3383.00 | 22.68 | 4664.67 | 23.43 | 775.00 | 23.46 |
Minimum of Months | 40.33 | 21.85 | 101.17 | 22.06 | 0.00 | 22.03 |
Maximum of Months | 580.17 | 24.00 | 744.00 | 24.00 | 261.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 615.50 | 23.10 | 0.00 | 23.10 | 0.00 | 23.10 |
February | 511.50 | 23.24 | 9.00 | 23.26 | 0.00 | 23.26 |
March | 536.67 | 23.28 | 9.50 | 23.29 | 0.00 | 23.29 |
April | 267.00 | 23.46 | 84.67 | 23.59 | 0.00 | 23.59 |
May | 103.33 | 23.62 | 316.67 | 23.86 | 22.83 | 23.87 |
June | 58.17 | 23.99 | 554.00 | 23.96 | 56.50 | 23.97 |
July | 531.83 | 23.97 | 744.00 | 23.96 | 531.83 | 23.96 |
August | 272.83 | 23.98 | 739.83 | 23.96 | 272.83 | 23.96 |
September | 297.00 | 23.97 | 657.33 | 23.96 | 296.00 | 23.97 |
October | 128.83 | 23.65 | 425.50 | 23.87 | 82.83 | 23.88 |
November | 371.67 | 23.22 | 66.17 | 23.33 | 0.00 | 23.33 |
December | 679.17 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
Annual Sum or Average | 4373.50 | 23.42 | 3606.67 | 23.66 | 1262.83 | 23.71 |
Minimum of Months | 58.17 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
Maximum of Months | 679.17 | 23.99 | 744.00 | 23.96 | 531.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 723.50 | 21.53 | 85.83 | 21.48 | 85.83 | 21.44 |
February | 653.17 | 21.60 | 81.50 | 21.54 | 81.50 | 21.49 |
March | 717.67 | 21.62 | 50.00 | 21.59 | 50.00 | 21.55 |
April | 660.50 | 21.61 | 9.17 | 21.61 | 5.67 | 21.61 |
May | 634.50 | 21.52 | 21.00 | 21.58 | 0.00 | 21.58 |
June | 580.50 | 21.45 | 43.00 | 21.58 | 0.00 | 21.58 |
July | 565.33 | 21.34 | 83.17 | 21.59 | 5.00 | 21.60 |
August | 578.00 | 21.38 | 66.83 | 21.58 | 1.00 | 21.58 |
September | 553.17 | 21.34 | 71.50 | 21.57 | 1.67 | 21.57 |
October | 635.83 | 21.50 | 31.33 | 21.58 | 0.17 | 21.58 |
November | 661.17 | 21.51 | 51.17 | 21.49 | 48.17 | 21.46 |
December | 735.50 | 21.54 | 166.17 | 21.44 | 166.17 | 21.38 |
Annual Sum or Average | 7698.83 | 21.50 | 760.67 | 21.55 | 445.17 | 21.52 |
Minimum of Months | 553.17 | 21.34 | 9.17 | 21.44 | 0.00 | 21.38 |
Maximum of Months | 735.50 | 21.62 | 166.17 | 21.61 | 166.17 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.17 | 21.38 | 140.17 | 21.31 | 140.17 | 21.26 |
February | 645.17 | 21.62 | 135.67 | 21.59 | 123.50 | 21.51 |
March | 658.00 | 21.76 | 118.17 | 22.11 | 56.83 | 22.07 |
April | 604.17 | 21.89 | 58.17 | 22.28 | 8.83 | 22.34 |
May | 573.67 | 21.74 | 63.00 | 22.05 | 3.33 | 22.07 |
June | 515.33 | 21.54 | 88.67 | 21.93 | 4.67 | 21.95 |
July | 527.00 | 21.68 | 155.50 | 22.23 | 57.50 | 22.43 |
August | 530.83 | 21.69 | 125.33 | 22.17 | 36.67 | 22.32 |
September | 517.50 | 21.81 | 137.00 | 22.37 | 47.33 | 22.51 |
October | 550.17 | 21.82 | 142.17 | 22.66 | 17.00 | 22.74 |
November | 675.33 | 21.63 | 85.67 | 21.66 | 70.83 | 21.61 |
December | 744.00 | 21.32 | 259.17 | 21.22 | 259.17 | 21.15 |
Annual Sum or Average | 7283.33 | 21.64 | 1508.67 | 21.91 | 825.83 | 21.91 |
Minimum of Months | 515.33 | 21.32 | 58.17 | 21.22 | 3.33 | 21.15 |
Maximum of Months | 744.00 | 21.89 | 259.17 | 22.66 | 259.17 | 22.74 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.39 | 80.17 | 21.36 | 80.17 | 21.34 |
February | 672.00 | 21.67 | 42.17 | 21.64 | 42.17 | 21.61 |
March | 740.67 | 21.94 | 9.33 | 21.93 | 9.33 | 21.92 |
April | 694.00 | 22.05 | 5.50 | 22.08 | 0.00 | 22.08 |
May | 709.50 | 22.04 | 14.17 | 22.10 | 0.00 | 22.10 |
June | 678.67 | 21.95 | 23.83 | 22.06 | 1.17 | 22.06 |
July | 716.33 | 22.08 | 75.00 | 22.31 | 64.83 | 22.46 |
August | 708.83 | 22.07 | 56.00 | 22.25 | 37.50 | 22.35 |
September | 681.50 | 22.17 | 64.17 | 22.35 | 50.17 | 22.47 |
October | 673.50 | 22.11 | 37.17 | 22.26 | 9.17 | 22.29 |
November | 715.00 | 21.68 | 2.67 | 21.68 | 2.67 | 21.67 |
December | 744.00 | 21.34 | 103.67 | 21.30 | 103.67 | 21.28 |
Annual Sum or Average | 8478.00 | 21.87 | 513.83 | 21.93 | 400.83 | 21.95 |
Minimum of Months | 672.00 | 21.34 | 2.67 | 21.30 | 0.00 | 21.28 |
Maximum of Months | 744.00 | 22.17 | 103.67 | 22.35 | 103.67 | 22.47 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.64 | 80.67 | 21.58 | 80.67 | 21.54 |
February | 671.33 | 21.71 | 75.17 | 21.65 | 75.17 | 21.60 |
March | 743.33 | 21.75 | 50.33 | 21.71 | 50.33 | 21.67 |
April | 669.50 | 21.69 | 6.83 | 21.68 | 6.83 | 21.68 |
May | 610.67 | 21.48 | 1.83 | 21.49 | 0.00 | 21.49 |
June | 522.33 | 21.25 | 9.67 | 21.28 | 0.00 | 21.28 |
July | 528.50 | 21.20 | 68.33 | 21.44 | 1.50 | 21.45 |
August | 542.67 | 21.25 | 44.83 | 21.41 | 0.67 | 21.41 |
September | 529.50 | 21.27 | 59.17 | 21.47 | 0.00 | 21.47 |
October | 619.17 | 21.47 | 8.33 | 21.50 | 0.00 | 21.50 |
November | 704.17 | 21.65 | 49.33 | 21.61 | 49.33 | 21.58 |
December | 744.00 | 21.62 | 156.67 | 21.53 | 156.67 | 21.46 |
Annual Sum or Average | 7629.17 | 21.52 | 611.17 | 21.54 | 421.17 | 21.52 |
Minimum of Months | 522.33 | 21.20 | 1.83 | 21.28 | 0.00 | 21.28 |
Maximum of Months | 744.00 | 21.75 | 156.67 | 21.71 | 156.67 | 21.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.42 | 122.67 | 21.38 | 122.67 | 21.34 |
February | 672.00 | 21.80 | 95.83 | 21.71 | 95.83 | 21.65 |
March | 726.17 | 22.04 | 50.17 | 21.98 | 50.17 | 21.93 |
April | 611.67 | 21.95 | 40.17 | 22.16 | 7.33 | 22.18 |
May | 536.67 | 21.79 | 71.33 | 22.30 | 18.17 | 22.47 |
June | 475.83 | 21.55 | 78.33 | 22.15 | 21.17 | 22.35 |
July | 509.83 | 21.78 | 169.50 | 22.46 | 59.00 | 22.75 |
August | 502.33 | 21.72 | 118.33 | 22.36 | 45.00 | 22.60 |
September | 493.50 | 21.95 | 115.00 | 22.58 | 54.33 | 22.85 |
October | 596.17 | 21.96 | 53.67 | 22.24 | 11.83 | 22.28 |
November | 702.83 | 21.75 | 72.83 | 21.70 | 69.00 | 21.65 |
December | 744.00 | 21.34 | 223.67 | 21.27 | 223.67 | 21.22 |
Annual Sum or Average | 7315.00 | 21.75 | 1211.50 | 21.97 | 778.17 | 22.01 |
Minimum of Months | 475.83 | 21.34 | 40.17 | 21.27 | 7.33 | 21.22 |
Maximum of Months | 744.00 | 22.04 | 223.67 | 22.58 | 223.67 | 22.85 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 569.17 | 23.95 | 663.17 | 23.95 | 569.17 | 23.95 |
February | 407.83 | 23.97 | 496.33 | 23.97 | 407.83 | 23.97 |
March | 330.33 | 23.98 | 456.67 | 23.98 | 330.33 | 23.98 |
April | 67.00 | 24.00 | 254.17 | 24.00 | 67.00 | 24.00 |
May | 18.00 | 24.00 | 314.00 | 24.00 | 18.00 | 24.00 |
June | 16.33 | 24.00 | 418.50 | 24.00 | 16.33 | 24.00 |
July | 124.33 | 24.00 | 744.00 | 24.00 | 124.33 | 24.00 |
August | 91.67 | 24.00 | 675.67 | 24.00 | 91.67 | 24.00 |
September | 126.17 | 24.00 | 584.50 | 24.00 | 126.17 | 24.00 |
October | 173.67 | 24.00 | 464.17 | 24.00 | 173.67 | 24.00 |
November | 342.50 | 23.96 | 439.17 | 23.97 | 342.50 | 23.96 |
December | 631.50 | 23.91 | 691.17 | 23.92 | 631.50 | 23.91 |
Annual Sum or Average | 2898.50 | 23.96 | 6201.50 | 23.97 | 2898.50 | 23.97 |
Minimum of Months | 16.33 | 23.91 | 254.17 | 23.92 | 16.33 | 23.91 |
Maximum of Months | 631.50 | 24.00 | 744.00 | 24.00 | 631.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 725.67 | 21.37 | 290.67 | 21.23 | 290.67 | 21.16 |
February | 647.50 | 21.47 | 216.83 | 21.35 | 216.83 | 21.28 |
March | 710.83 | 21.53 | 198.50 | 21.41 | 198.50 | 21.34 |
April | 635.67 | 21.51 | 72.83 | 21.53 | 53.67 | 21.49 |
May | 597.17 | 21.41 | 59.50 | 21.58 | 2.67 | 21.57 |
June | 533.67 | 21.32 | 93.17 | 21.61 | 0.00 | 21.61 |
July | 539.67 | 21.28 | 144.83 | 21.70 | 8.17 | 21.71 |
August | 548.67 | 21.29 | 119.17 | 21.65 | 3.17 | 21.66 |
September | 531.67 | 21.27 | 126.67 | 21.66 | 6.50 | 21.67 |
October | 619.50 | 21.40 | 55.00 | 21.56 | 0.83 | 21.56 |
November | 657.50 | 21.38 | 196.17 | 21.31 | 191.00 | 21.25 |
December | 738.67 | 21.38 | 361.83 | 21.23 | 361.83 | 21.16 |
Annual Sum or Average | 7486.17 | 21.39 | 1935.17 | 21.46 | 1333.83 | 21.40 |
Minimum of Months | 531.67 | 21.27 | 55.00 | 21.23 | 0.00 | 21.16 |
Maximum of Months | 738.67 | 21.53 | 361.83 | 21.70 | 361.83 | 21.71 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.17 | 21.16 | 390.00 | 21.03 | 390.00 | 20.97 |
February | 647.17 | 21.47 | 279.50 | 21.38 | 266.83 | 21.27 |
March | 662.17 | 21.70 | 242.83 | 21.90 | 189.17 | 21.80 |
April | 587.50 | 21.84 | 108.67 | 22.21 | 51.67 | 22.25 |
May | 545.00 | 21.65 | 94.83 | 22.03 | 5.00 | 22.06 |
June | 477.17 | 21.42 | 132.33 | 21.95 | 5.00 | 21.97 |
July | 511.83 | 21.65 | 219.17 | 22.30 | 58.83 | 22.48 |
August | 511.17 | 21.64 | 169.33 | 22.20 | 38.67 | 22.34 |
September | 497.33 | 21.71 | 184.50 | 22.34 | 50.83 | 22.47 |
October | 539.33 | 21.78 | 150.67 | 22.66 | 23.83 | 22.79 |
November | 678.83 | 21.50 | 242.67 | 21.41 | 231.67 | 21.31 |
December | 744.00 | 21.08 | 492.00 | 20.98 | 492.00 | 20.93 |
Annual Sum or Average | 7144.67 | 21.53 | 2706.50 | 21.76 | 1803.50 | 21.69 |
Minimum of Months | 477.17 | 21.08 | 94.83 | 20.98 | 5.00 | 20.93 |
Maximum of Months | 744.00 | 21.84 | 492.00 | 22.66 | 492.00 | 22.79 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 660.83 | 21.42 | 118.17 | 21.39 | 109.83 | 21.35 |
February | 598.50 | 21.48 | 116.33 | 21.42 | 116.33 | 21.38 |
March | 681.67 | 21.54 | 110.50 | 21.48 | 110.50 | 21.43 |
April | 645.17 | 21.56 | 32.67 | 21.53 | 32.67 | 21.52 |
May | 641.67 | 21.53 | 4.00 | 21.54 | 1.33 | 21.54 |
June | 574.83 | 21.42 | 12.17 | 21.46 | 0.00 | 21.46 |
July | 572.33 | 21.35 | 97.00 | 21.63 | 10.17 | 21.65 |
August | 578.00 | 21.36 | 93.17 | 21.63 | 2.83 | 21.64 |
September | 550.67 | 21.32 | 125.33 | 21.69 | 6.33 | 21.71 |
October | 606.50 | 21.41 | 85.50 | 21.65 | 0.33 | 21.65 |
November | 605.33 | 21.38 | 104.50 | 21.40 | 85.83 | 21.36 |
December | 668.83 | 21.45 | 201.17 | 21.36 | 201.17 | 21.31 |
Annual Sum or Average | 7384.33 | 21.44 | 1100.50 | 21.51 | 677.33 | 21.48 |
Minimum of Months | 550.67 | 21.32 | 4.00 | 21.36 | 0.00 | 21.31 |
Maximum of Months | 681.67 | 21.56 | 201.17 | 21.69 | 201.17 | 21.71 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 577.50 | 22.96 | 10.33 | 22.97 | 0.00 | 22.97 |
February | 435.33 | 23.10 | 34.17 | 23.16 | 0.00 | 23.16 |
March | 319.17 | 23.16 | 20.83 | 23.21 | 0.33 | 23.21 |
April | 78.00 | 23.35 | 246.50 | 23.83 | 0.00 | 23.83 |
May | 44.33 | 23.91 | 552.00 | 23.98 | 37.67 | 23.98 |
June | 81.50 | 24.00 | 684.17 | 23.99 | 81.50 | 23.99 |
July | 573.00 | 23.99 | 744.00 | 23.99 | 573.00 | 23.99 |
August | 337.00 | 23.99 | 744.00 | 23.98 | 337.00 | 23.98 |
September | 321.83 | 23.98 | 703.50 | 23.97 | 321.83 | 23.97 |
October | 142.33 | 23.71 | 542.33 | 23.87 | 104.50 | 23.88 |
November | 409.33 | 23.10 | 86.83 | 23.25 | 2.00 | 23.25 |
December | 654.33 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
Annual Sum or Average | 3973.67 | 23.38 | 4368.67 | 23.69 | 1457.83 | 23.73 |
Minimum of Months | 44.33 | 22.91 | 0.00 | 22.91 | 0.00 | 22.91 |
Maximum of Months | 654.33 | 24.00 | 744.00 | 23.99 | 573.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 422.00 | 23.10 | 59.33 | 23.21 | 0.00 | 23.21 |
February | 278.33 | 23.22 | 54.17 | 23.34 | 0.00 | 23.34 |
March | 187.67 | 23.27 | 43.50 | 23.40 | 0.00 | 23.40 |
April | 31.33 | 23.41 | 337.17 | 23.94 | 0.00 | 23.94 |
May | 34.00 | 24.00 | 605.33 | 23.99 | 34.00 | 23.99 |
June | 75.83 | 24.00 | 691.00 | 24.00 | 75.83 | 24.00 |
July | 566.83 | 23.99 | 744.00 | 23.99 | 566.83 | 23.99 |
August | 328.00 | 24.00 | 744.00 | 23.99 | 328.00 | 23.99 |
September | 316.33 | 23.99 | 716.67 | 23.99 | 316.33 | 23.99 |
October | 100.83 | 23.93 | 643.67 | 23.94 | 94.00 | 23.94 |
November | 246.33 | 23.24 | 128.67 | 23.48 | 1.50 | 23.48 |
December | 521.83 | 23.09 | 14.33 | 23.12 | 0.00 | 23.12 |
Annual Sum or Average | 3109.33 | 23.54 | 4781.83 | 23.81 | 1416.50 | 23.84 |
Minimum of Months | 31.33 | 23.09 | 14.33 | 23.12 | 0.00 | 23.12 |
Maximum of Months | 566.83 | 24.00 | 744.00 | 24.00 | 566.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.67 | 23.98 | 715.50 | 23.99 | 472.67 | 23.99 |
February | 437.67 | 23.99 | 654.33 | 23.99 | 437.67 | 23.99 |
March | 483.83 | 23.99 | 732.83 | 23.99 | 483.83 | 23.99 |
April | 496.83 | 24.00 | 718.67 | 24.00 | 496.83 | 24.00 |
May | 539.67 | 24.00 | 744.00 | 24.00 | 539.67 | 24.00 |
June | 556.83 | 24.00 | 720.00 | 24.00 | 556.83 | 24.00 |
July | 660.00 | 24.00 | 744.00 | 24.00 | 660.00 | 24.00 |
August | 618.67 | 24.00 | 744.00 | 24.00 | 618.67 | 24.00 |
September | 627.17 | 24.00 | 720.00 | 24.00 | 627.17 | 24.00 |
October | 551.33 | 24.00 | 744.00 | 24.00 | 551.33 | 24.00 |
November | 479.33 | 23.99 | 708.50 | 23.99 | 479.33 | 23.99 |
December | 467.50 | 23.98 | 709.50 | 23.99 | 467.50 | 23.98 |
Annual Sum or Average | 6391.50 | 24.00 | 8655.33 | 24.00 | 6391.50 | 24.00 |
Minimum of Months | 437.67 | 23.98 | 654.33 | 23.99 | 437.67 | 23.98 |
Maximum of Months | 660.00 | 24.00 | 744.00 | 24.00 | 660.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 636.00 | 23.02 | 635.67 | 23.03 | 601.83 | 23.01 |
February | 457.33 | 23.25 | 460.83 | 23.27 | 402.17 | 23.25 |
March | 356.17 | 23.40 | 425.00 | 23.46 | 328.33 | 23.44 |
April | 93.67 | 23.70 | 298.17 | 23.86 | 84.17 | 23.84 |
May | 12.33 | 23.98 | 419.17 | 24.00 | 12.33 | 24.00 |
June | 0.00 | 0.00 | 594.33 | 24.00 | 0.00 | 24.00 |
July | 0.00 | 0.00 | 744.00 | 24.00 | 0.00 | 24.00 |
August | 3.67 | 24.00 | 699.67 | 24.00 | 3.67 | 24.00 |
September | 37.67 | 23.96 | 607.50 | 23.99 | 37.67 | 23.99 |
October | 177.33 | 23.92 | 479.33 | 23.96 | 177.33 | 23.95 |
November | 446.67 | 23.25 | 459.33 | 23.28 | 377.33 | 23.24 |
December | 698.33 | 22.72 | 660.17 | 22.72 | 642.67 | 22.71 |
Annual Sum or Average | 2919.17 | 23.16 | 6483.17 | 23.49 | 2667.50 | 23.41 |
Minimum of Months | 0.00 | 0.00 | 298.17 | 22.72 | 0.00 | 22.71 |
Maximum of Months | 698.33 | 24.00 | 744.00 | 24.00 | 642.67 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.86410 | 23.01096 | 0.19912 | 5.97626 |
February | 672.00000 | 23.71610 | 20.73650 | 0.12717 | 5.56501 |
March | 744.00000 | 23.73975 | 19.88974 | 0.11284 | 5.43281 |
April | 720.00000 | 23.97682 | 21.97362 | 0.18655 | 5.82248 |
May | 744.00000 | 23.99995 | 29.99590 | -0.6607 | 14.29484 |
June | 720.00000 | 24.00006 | 36.08891 | -0.6066 | 12.83531 |
July | 744.00000 | 24.00009 | 50.08047 | -0.4790 | 9.83138 |
August | 744.00000 | 24.00007 | 45.08824 | -0.4936 | 10.13025 |
September | 720.00000 | 24.00006 | 43.16548 | -0.4896 | 10.09573 |
October | 744.00000 | 23.99995 | 36.46013 | 0.35663 | 7.73660 |
November | 720.00000 | 23.99560 | 23.08607 | 0.25748 | 6.44083 |
December | 744.00000 | 23.87104 | 20.04803 | 0.19643 | 5.88891 |
Annual Sum or Average | 8760.00000 | 23.93137 | 30.88170 | -0.1091 | 8.35527 |
Minimum of Months | 672.00000 | 23.71610 | 19.88974 | -0.6607 | 5.43281 |
Maximum of Months | 744.00000 | 24.00009 | 50.08047 | 0.35663 | 14.29484 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.10649 | 25.92031 | -0.1857 | 8.35918 |
February | 672.00000 | 22.29657 | 22.53848 | -0.1445 | 7.94532 |
March | 744.00000 | 22.44604 | 21.10640 | -0.1110 | 7.68466 |
April | 720.00000 | 23.05920 | 22.89054 | 0.08853 | 7.16649 |
May | 744.00000 | 23.46906 | 31.54425 | -0.6433 | 16.08684 |
June | 720.00000 | 23.77836 | 38.48424 | -0.4406 | 10.10949 |
July | 744.00000 | 23.81262 | 55.35839 | -0.3131 | 7.77945 |
August | 744.00000 | 23.73236 | 50.46691 | -0.3770 | 9.15829 |
September | 720.00000 | 23.54439 | 48.57597 | -0.4512 | 11.73493 |
October | 744.00000 | 23.12079 | 40.80132 | 0.25006 | 8.41781 |
November | 720.00000 | 22.45433 | 26.39154 | -0.0595 | 8.16063 |
December | 744.00000 | 22.00088 | 22.82185 | -0.2442 | 8.87590 |
Annual Sum or Average | 8760.00000 | 22.98829 | 33.99986 | -0.2200 | 9.30093 |
Minimum of Months | 672.00000 | 22.00088 | 21.10640 | -0.6433 | 7.16649 |
Maximum of Months | 744.00000 | 23.81262 | 55.35839 | 0.25006 | 16.08684 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.86875 | 26.01909 | 0.00026 | 5.44416 |
February | 672.00000 | 23.06881 | 22.72579 | 0.03107 | 5.40803 |
March | 744.00000 | 23.20300 | 21.29671 | 0.06027 | 5.48751 |
April | 720.00000 | 23.61884 | 23.20415 | 0.18965 | 6.08419 |
May | 744.00000 | 23.84031 | 31.86308 | -0.5819 | 12.52151 |
June | 720.00000 | 23.96475 | 39.00403 | -0.4710 | 9.81894 |
July | 744.00000 | 23.96897 | 55.58379 | -0.3562 | 7.70631 |
August | 744.00000 | 23.93905 | 50.71875 | -0.4043 | 8.53808 |
September | 720.00000 | 23.88616 | 48.55987 | -0.4434 | 9.39032 |
October | 744.00000 | 23.66682 | 40.51831 | 0.32226 | 7.46804 |
November | 720.00000 | 23.24209 | 26.43404 | 0.10363 | 5.74237 |
December | 744.00000 | 22.73510 | 23.15912 | -0.0533 | 5.50093 |
Annual Sum or Average | 8760.00000 | 23.50182 | 34.18167 | -0.1347 | 7.43880 |
Minimum of Months | 672.00000 | 22.73510 | 21.29671 | -0.5819 | 5.40803 |
Maximum of Months | 744.00000 | 23.96897 | 55.58379 | 0.32226 | 12.52151 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99969 | 17.86145 | 0.80269 | 19.38320 |
February | 672.00000 | 23.99972 | 15.44379 | 0.80124 | 19.31990 |
March | 744.00000 | 23.99976 | 14.70275 | 0.81122 | 19.66905 |
April | 720.00000 | 23.99990 | 18.80845 | 0.87314 | 21.94822 |
May | 744.00000 | 24.00021 | 27.14510 | 0.33941 | 9.26108 |
June | 720.00000 | 24.00063 | 34.21556 | 0.41741 | 10.32575 |
July | 744.00000 | 24.00266 | 43.43367 | 0.47619 | 11.15326 |
August | 744.00000 | 24.00118 | 41.89712 | 0.45870 | 10.90486 |
September | 720.00000 | 24.00083 | 42.22740 | 0.44406 | 10.58660 |
October | 744.00000 | 24.00040 | 35.08057 | 0.97930 | 25.96904 |
November | 720.00000 | 23.99975 | 19.47318 | 0.83547 | 20.54393 |
December | 744.00000 | 23.99971 | 15.06123 | 0.77572 | 18.45659 |
Annual Sum or Average | 8760.00000 | 24.00038 | 27.19124 | 0.66706 | 16.44329 |
Minimum of Months | 672.00000 | 23.99969 | 14.70275 | 0.33941 | 9.26108 |
Maximum of Months | 744.00000 | 24.00266 | 43.43367 | 0.97930 | 25.96904 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.50390 | 28.49626 | -0.0166 | 7.45110 |
February | 672.00000 | 22.95737 | 24.89327 | 0.07603 | 7.34127 |
March | 744.00000 | 23.23601 | 23.26704 | 0.13131 | 7.20773 |
April | 720.00000 | 23.83402 | 24.60103 | 0.31898 | 7.89792 |
May | 744.00000 | 23.99458 | 32.68419 | -0.4059 | 9.03853 |
June | 720.00000 | 24.00025 | 39.12252 | -0.2963 | 7.17444 |
July | 744.00000 | 24.00049 | 54.85783 | -0.1842 | 5.89360 |
August | 744.00000 | 24.00032 | 49.77576 | -0.2238 | 6.36716 |
September | 720.00000 | 23.99279 | 48.80269 | -0.2356 | 6.86887 |
October | 744.00000 | 23.93090 | 41.53788 | 0.48881 | 10.62630 |
November | 720.00000 | 23.04459 | 28.62383 | 0.14490 | 8.05801 |
December | 744.00000 | 22.30485 | 25.59109 | -0.0920 | 7.77392 |
Annual Sum or Average | 8760.00000 | 23.48509 | 35.27130 | -0.0254 | 7.64559 |
Minimum of Months | 672.00000 | 22.30485 | 23.26704 | -0.4059 | 5.89360 |
Maximum of Months | 744.00000 | 24.00049 | 54.85783 | 0.48881 | 10.62630 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.23952 | 28.22198 | 0.12447 | 5.66002 |
February | 672.00000 | 23.40397 | 25.00179 | 0.14924 | 5.74246 |
March | 744.00000 | 23.46973 | 23.66394 | 0.16197 | 5.83582 |
April | 720.00000 | 23.76182 | 25.52932 | 0.26632 | 6.72162 |
May | 744.00000 | 23.88529 | 34.08977 | -0.5090 | 10.73346 |
June | 720.00000 | 23.96110 | 41.09880 | -0.4093 | 8.65495 |
July | 744.00000 | 23.96003 | 57.65470 | -0.2948 | 6.86557 |
August | 744.00000 | 23.94342 | 52.77731 | -0.3382 | 7.49611 |
September | 720.00000 | 23.94720 | 50.55022 | -0.3583 | 7.87369 |
October | 744.00000 | 23.83486 | 42.50325 | 0.40999 | 8.72497 |
November | 720.00000 | 23.55166 | 28.64780 | 0.21853 | 6.39723 |
December | 744.00000 | 23.13326 | 25.42440 | 0.07554 | 5.46864 |
Annual Sum or Average | 8760.00000 | 23.67511 | 36.35406 | -0.0432 | 7.19051 |
Minimum of Months | 672.00000 | 23.13326 | 23.66394 | -0.5090 | 5.46864 |
Maximum of Months | 744.00000 | 23.96110 | 57.65470 | 0.40999 | 10.73346 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57718 | 31.14254 | -0.3252 | 8.47791 |
February | 672.00000 | 21.64597 | 27.68219 | -0.3067 | 8.31454 |
March | 744.00000 | 21.68295 | 26.33844 | -0.2779 | 7.98440 |
April | 720.00000 | 21.75067 | 28.71551 | -0.1879 | 7.15784 |
May | 744.00000 | 21.78713 | 35.35362 | -1.1677 | 35.62439 |
June | 720.00000 | 21.80806 | 39.12829 | -1.0905 | 32.06600 |
July | 744.00000 | 21.80836 | 47.89342 | -1.0439 | 29.96289 |
August | 744.00000 | 21.80252 | 45.58546 | -1.0733 | 31.32147 |
September | 720.00000 | 21.79300 | 45.08763 | -1.0939 | 32.48878 |
October | 744.00000 | 21.76113 | 41.41676 | -0.1054 | 6.55476 |
November | 720.00000 | 21.65693 | 31.33624 | -0.2630 | 7.91425 |
December | 744.00000 | 21.55794 | 28.32833 | -0.3610 | 9.02041 |
Annual Sum or Average | 8760.00000 | 21.71956 | 35.72862 | -0.6099 | 18.13410 |
Minimum of Months | 672.00000 | 21.55794 | 26.33844 | -1.1677 | 6.55476 |
Maximum of Months | 744.00000 | 21.80836 | 47.89342 | -0.1054 | 35.62439 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38662 | 31.77935 | -0.4110 | 9.39739 |
February | 672.00000 | 21.77241 | 27.98695 | -0.3249 | 8.93191 |
March | 744.00000 | 22.23985 | 26.68702 | -0.1943 | 8.79562 |
April | 720.00000 | 22.37410 | 28.63535 | -0.0776 | 7.78054 |
May | 744.00000 | 22.25608 | 34.99233 | -1.0431 | 30.92358 |
June | 720.00000 | 22.16514 | 38.92640 | -0.9903 | 28.41066 |
July | 744.00000 | 22.19777 | 48.26910 | -0.9313 | 26.30695 |
August | 744.00000 | 22.23800 | 45.92827 | -0.9601 | 27.34914 |
September | 720.00000 | 22.38768 | 45.63746 | -0.9546 | 27.44627 |
October | 744.00000 | 22.66229 | 41.42688 | 0.04509 | 8.15006 |
November | 720.00000 | 21.82072 | 31.55686 | -0.2778 | 8.41203 |
December | 744.00000 | 21.31921 | 28.92794 | -0.4592 | 10.22766 |
Annual Sum or Average | 8760.00000 | 22.06945 | 35.95796 | -0.5498 | 16.89655 |
Minimum of Months | 672.00000 | 21.31921 | 26.68702 | -1.0431 | 7.78054 |
Maximum of Months | 744.00000 | 22.66229 | 48.26910 | 0.04509 | 30.92358 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.39256 | 28.81917 | -0.4157 | 8.87171 |
February | 672.00000 | 21.67025 | 25.29875 | -0.3620 | 8.35308 |
March | 744.00000 | 21.95217 | 23.87551 | -0.2910 | 7.65585 |
April | 720.00000 | 22.16076 | 26.65693 | -0.1908 | 6.94356 |
May | 744.00000 | 22.16945 | 34.00309 | -1.1863 | 36.18713 |
June | 720.00000 | 22.11755 | 38.78272 | -1.1427 | 34.23973 |
July | 744.00000 | 22.15363 | 49.80051 | -1.0640 | 31.09243 |
August | 744.00000 | 22.18491 | 46.98555 | -1.0887 | 32.03503 |
September | 720.00000 | 22.30385 | 46.40060 | -1.0782 | 31.63768 |
October | 744.00000 | 22.36553 | 40.48471 | -0.0660 | 6.51865 |
November | 720.00000 | 21.69830 | 29.23286 | -0.3274 | 7.86781 |
December | 744.00000 | 21.33558 | 26.03856 | -0.4526 | 9.48989 |
Annual Sum or Average | 8760.00000 | 21.95986 | 34.76926 | -0.6406 | 18.47102 |
Minimum of Months | 672.00000 | 21.33558 | 23.87551 | -1.1863 | 6.51865 |
Maximum of Months | 744.00000 | 22.36553 | 49.80051 | -0.0660 | 36.18713 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63512 | 30.90345 | -0.3152 | 8.28020 |
February | 672.00000 | 21.71376 | 27.40905 | -0.2852 | 8.06700 |
March | 744.00000 | 21.75327 | 26.09326 | -0.2592 | 7.80014 |
April | 720.00000 | 21.80224 | 28.36484 | -0.1690 | 7.03266 |
May | 744.00000 | 21.81325 | 35.00416 | -1.1516 | 34.83173 |
June | 720.00000 | 21.81879 | 38.67486 | -1.0786 | 31.53690 |
July | 744.00000 | 21.81753 | 47.35010 | -1.0344 | 29.59168 |
August | 744.00000 | 21.81311 | 45.08545 | -1.0640 | 30.93183 |
September | 720.00000 | 21.81214 | 44.48528 | -1.0859 | 32.10509 |
October | 744.00000 | 21.78402 | 41.29687 | -0.1062 | 6.52611 |
November | 720.00000 | 21.68675 | 31.22070 | -0.2586 | 7.77385 |
December | 744.00000 | 21.62462 | 28.11558 | -0.3461 | 8.76867 |
Annual Sum or Average | 8760.00000 | 21.75630 | 35.39490 | -0.5982 | 17.83006 |
Minimum of Months | 672.00000 | 21.62462 | 26.09326 | -1.1516 | 6.52611 |
Maximum of Months | 744.00000 | 21.81879 | 47.35010 | -0.1062 | 34.83173 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.42485 | 31.56863 | -0.4055 | 9.02469 |
February | 672.00000 | 21.79967 | 27.62387 | -0.3116 | 8.21887 |
March | 744.00000 | 22.11301 | 25.88107 | -0.2190 | 7.61790 |
April | 720.00000 | 22.36918 | 27.95960 | -0.0722 | 7.33799 |
May | 744.00000 | 22.42210 | 34.58316 | -0.9846 | 30.28102 |
June | 720.00000 | 22.30269 | 38.44784 | -0.9396 | 28.36306 |
July | 744.00000 | 22.31699 | 47.63478 | -0.8881 | 26.44223 |
August | 744.00000 | 22.36252 | 45.30778 | -0.9164 | 27.28431 |
September | 720.00000 | 22.53555 | 44.80737 | -0.9076 | 27.28195 |
October | 744.00000 | 22.46189 | 41.29023 | -0.0028 | 6.92163 |
November | 720.00000 | 21.82118 | 31.53734 | -0.2798 | 7.96565 |
December | 744.00000 | 21.33818 | 28.73689 | -0.4539 | 9.87549 |
Annual Sum or Average | 8760.00000 | 22.10651 | 35.50990 | -0.5334 | 16.43686 |
Minimum of Months | 672.00000 | 21.33818 | 25.88107 | -0.9846 | 6.92163 |
Maximum of Months | 744.00000 | 22.53555 | 47.63478 | -0.0028 | 30.28102 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41512 | 32.12033 | -0.4243 | 10.38902 |
February | 672.00000 | 21.53767 | 28.35258 | -0.3839 | 9.84772 |
March | 744.00000 | 21.60663 | 26.72180 | -0.3360 | 9.19311 |
April | 720.00000 | 21.72129 | 28.86349 | -0.2058 | 7.78607 |
May | 744.00000 | 21.77811 | 35.40977 | -1.1615 | 35.90499 |
June | 720.00000 | 21.80793 | 39.06466 | -1.0560 | 31.21655 |
July | 744.00000 | 21.80847 | 47.78104 | -1.0105 | 29.14552 |
August | 744.00000 | 21.79878 | 45.66685 | -1.0490 | 30.87990 |
September | 720.00000 | 21.78066 | 45.54519 | -1.0872 | 32.90379 |
October | 744.00000 | 21.71700 | 42.63077 | -0.1283 | 7.04193 |
November | 720.00000 | 21.54974 | 32.15004 | -0.3355 | 9.29406 |
December | 744.00000 | 21.39357 | 29.06328 | -0.4668 | 11.20969 |
Annual Sum or Average | 8760.00000 | 21.65998 | 36.17475 | -0.6388 | 18.79024 |
Minimum of Months | 672.00000 | 21.39357 | 26.72180 | -1.1615 | 7.04193 |
Maximum of Months | 744.00000 | 21.80847 | 47.78104 | -0.1283 | 35.90499 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.15965 | 32.75900 | -0.5285 | 11.90502 |
February | 672.00000 | 21.61429 | 28.72229 | -0.4142 | 10.73120 |
March | 744.00000 | 22.15427 | 27.15519 | -0.2511 | 10.06242 |
April | 720.00000 | 22.34363 | 28.79236 | -0.0914 | 8.45032 |
May | 744.00000 | 22.21867 | 35.01760 | -1.0417 | 31.35701 |
June | 720.00000 | 22.14198 | 38.81479 | -0.9605 | 27.70614 |
July | 744.00000 | 22.18056 | 48.00822 | -0.9013 | 25.57179 |
August | 744.00000 | 22.20880 | 45.81801 | -0.9414 | 27.04144 |
September | 720.00000 | 22.33729 | 45.82486 | -0.9564 | 27.97082 |
October | 744.00000 | 22.62762 | 42.44964 | 0.02829 | 8.69365 |
November | 720.00000 | 21.68018 | 32.42563 | -0.3593 | 10.00288 |
December | 744.00000 | 21.08479 | 29.66197 | -0.5846 | 13.10894 |
Annual Sum or Average | 8760.00000 | 21.98071 | 36.34770 | -0.5848 | 17.76528 |
Minimum of Months | 672.00000 | 21.08479 | 27.15519 | -1.0417 | 8.45032 |
Maximum of Months | 744.00000 | 22.62762 | 48.00822 | 0.02829 | 31.35701 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63249 | 31.79624 | -0.3001 | 8.78264 |
February | 672.00000 | 21.68509 | 28.39906 | -0.2899 | 8.65919 |
March | 744.00000 | 21.69275 | 27.06769 | -0.2934 | 8.56073 |
April | 720.00000 | 21.74077 | 29.70334 | -0.2185 | 7.64473 |
May | 744.00000 | 21.77860 | 36.40971 | -1.2257 | 38.36849 |
June | 720.00000 | 21.80549 | 40.08561 | -1.1379 | 34.21718 |
July | 744.00000 | 21.80762 | 48.83460 | -1.0815 | 31.68814 |
August | 744.00000 | 21.80026 | 46.36484 | -1.1032 | 32.83957 |
September | 720.00000 | 21.79149 | 45.82807 | -1.1109 | 33.72950 |
October | 744.00000 | 21.76325 | 41.97704 | -0.1080 | 6.95920 |
November | 720.00000 | 21.69202 | 31.94265 | -0.2454 | 8.28273 |
December | 744.00000 | 21.64318 | 29.18515 | -0.3243 | 9.19372 |
Annual Sum or Average | 8760.00000 | 21.73627 | 36.52783 | -0.6220 | 19.14205 |
Minimum of Months | 672.00000 | 21.63249 | 27.06769 | -1.2257 | 6.95920 |
Maximum of Months | 744.00000 | 21.80762 | 48.83460 | -0.1080 | 38.36849 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.16476 | 28.36183 | 0.12050 | 5.81804 |
February | 672.00000 | 23.38388 | 25.21770 | 0.17179 | 6.06326 |
March | 744.00000 | 23.57295 | 23.82810 | 0.23123 | 6.43662 |
April | 720.00000 | 23.85899 | 25.91233 | 0.36770 | 8.09383 |
May | 744.00000 | 23.95556 | 34.66984 | -0.3437 | 7.85298 |
June | 720.00000 | 23.99313 | 41.81397 | -0.2281 | 6.29605 |
July | 744.00000 | 23.98804 | 57.99834 | -0.1209 | 5.39367 |
August | 744.00000 | 23.97483 | 53.50903 | -0.1771 | 5.80510 |
September | 720.00000 | 23.95286 | 51.27734 | -0.2357 | 6.46375 |
October | 744.00000 | 23.80281 | 43.30885 | 0.46121 | 9.76419 |
November | 720.00000 | 23.42387 | 29.15048 | 0.21314 | 6.40827 |
December | 744.00000 | 23.03602 | 25.55590 | 0.05723 | 5.57969 |
Annual Sum or Average | 8760.00000 | 23.67660 | 36.80797 | 0.04220 | 6.66791 |
Minimum of Months | 672.00000 | 23.03602 | 23.82810 | -0.3437 | 5.39367 |
Maximum of Months | 744.00000 | 23.99313 | 57.99834 | 0.46121 | 9.76419 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.43806 | 27.91106 | 0.20955 | 6.31907 |
February | 672.00000 | 23.60458 | 24.80733 | 0.24750 | 6.60802 |
March | 744.00000 | 23.74348 | 23.41264 | 0.29496 | 7.03908 |
April | 720.00000 | 23.93261 | 25.52172 | 0.40893 | 8.71552 |
May | 744.00000 | 23.98457 | 34.31720 | -0.2987 | 7.22022 |
June | 720.00000 | 23.99614 | 41.51718 | -0.1915 | 5.98800 |
July | 744.00000 | 23.99404 | 57.68603 | -0.0835 | 5.23971 |
August | 744.00000 | 23.98996 | 53.16602 | -0.1370 | 5.53686 |
September | 720.00000 | 23.98404 | 50.88875 | -0.1907 | 6.03444 |
October | 744.00000 | 23.89356 | 42.81308 | 0.50536 | 10.60553 |
November | 720.00000 | 23.63514 | 28.69951 | 0.28608 | 7.03787 |
December | 744.00000 | 23.34310 | 25.13834 | 0.15602 | 5.90380 |
Annual Sum or Average | 8760.00000 | 23.79550 | 36.41423 | 0.09961 | 6.85504 |
Minimum of Months | 672.00000 | 23.34310 | 23.41264 | -0.2987 | 5.23971 |
Maximum of Months | 744.00000 | 23.99614 | 57.68603 | 0.50536 | 10.60553 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.98747 | 27.57802 | 0.95851 | 26.18951 |
February | 672.00000 | 23.99015 | 24.16764 | 0.96488 | 26.48211 |
March | 744.00000 | 23.99238 | 22.72482 | 0.98426 | 27.37066 |
April | 720.00000 | 23.99726 | 28.93892 | 1.09854 | 32.69300 |
May | 744.00000 | 24.00004 | 38.28250 | 0.67014 | 19.65342 |
June | 720.00000 | 24.00159 | 45.51951 | 0.78269 | 22.61916 |
July | 744.00000 | 24.00387 | 53.49470 | 0.83210 | 23.32048 |
August | 744.00000 | 24.00208 | 50.70192 | 0.79093 | 22.20024 |
September | 720.00000 | 24.00084 | 49.94931 | 0.75184 | 21.12024 |
October | 744.00000 | 23.99744 | 41.50038 | 1.16692 | 35.21394 |
November | 720.00000 | 23.99082 | 27.61519 | 0.99571 | 27.77320 |
December | 744.00000 | 23.98715 | 25.76643 | 0.93212 | 25.17579 |
Annual Sum or Average | 8760.00000 | 23.99595 | 36.43533 | 0.91031 | 25.80962 |
Minimum of Months | 672.00000 | 23.98715 | 22.72482 | 0.67014 | 19.65342 |
Maximum of Months | 744.00000 | 24.00387 | 53.49470 | 1.16692 | 35.21394 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.23287 | 24.98623 | -0.4247 | 8.93581 |
February | 672.00000 | 21.51668 | 21.27090 | -0.3743 | 8.20554 |
March | 744.00000 | 21.84309 | 19.64748 | -0.3014 | 7.23846 |
April | 720.00000 | 22.92330 | 21.11242 | -0.0281 | 5.60836 |
May | 744.00000 | 23.59915 | 29.45416 | -0.7366 | 17.18968 |
June | 720.00000 | 23.88842 | 36.57299 | -0.5681 | 11.99661 |
July | 744.00000 | 23.89814 | 53.39500 | -0.4509 | 9.34715 |
August | 744.00000 | 23.80507 | 48.56583 | -0.5268 | 11.03757 |
September | 720.00000 | 23.59032 | 46.80579 | -0.6242 | 13.79139 |
October | 744.00000 | 22.87874 | 39.42703 | 0.08192 | 5.67868 |
November | 720.00000 | 21.75429 | 25.27809 | -0.2888 | 7.21644 |
December | 744.00000 | 21.16095 | 21.74554 | -0.4671 | 9.67099 |
Annual Sum or Average | 8760.00000 | 22.67977 | 32.44527 | -0.3927 | 9.67175 |
Minimum of Months | 672.00000 | 21.16095 | 19.64748 | -0.7366 | 5.60836 |
Maximum of Months | 744.00000 | 23.89814 | 53.39500 | 0.08192 | 17.18968 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.96159 | 68.85519 | 0.46859 | 9.73221 |
February | 672.00000 | 23.97973 | 59.95492 | 0.41990 | 8.76496 |
March | 744.00000 | 23.99062 | 55.54476 | 0.39814 | 8.36388 |
April | 720.00000 | 23.99913 | 48.15124 | 0.36382 | 7.79945 |
May | 744.00000 | 23.99916 | 47.53874 | -0.5504 | 11.35091 |
June | 720.00000 | 23.99919 | 47.08898 | -0.5401 | 11.11834 |
July | 744.00000 | 23.99920 | 52.67097 | -0.5021 | 10.27320 |
August | 744.00000 | 23.99918 | 51.12266 | -0.5163 | 10.57989 |
September | 720.00000 | 23.99916 | 50.80104 | -0.5214 | 10.71814 |
October | 744.00000 | 23.99913 | 50.82068 | 0.38660 | 8.13465 |
November | 720.00000 | 23.98109 | 58.86383 | 0.41726 | 8.79083 |
December | 744.00000 | 23.92455 | 72.28357 | 0.47921 | 9.92665 |
Annual Sum or Average | 8760.00000 | 23.98593 | 55.31459 | 0.02307 | 9.63678 |
Minimum of Months | 672.00000 | 23.92455 | 47.08898 | -0.5504 | 7.79945 |
Maximum of Months | 744.00000 | 23.99920 | 72.28357 | 0.47921 | 11.35091 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.15748 | 73.58386 | 0.28570 | 7.15518 |
February | 672.00000 | 23.48894 | 62.31303 | 0.31051 | 7.41231 |
March | 744.00000 | 23.70781 | 54.90431 | 0.33261 | 7.51642 |
April | 720.00000 | 23.95793 | 44.22550 | 0.36788 | 7.90751 |
May | 744.00000 | 23.99892 | 42.11153 | -0.4997 | 10.30657 |
June | 720.00000 | 23.99933 | 40.95900 | -0.4597 | 9.49823 |
July | 744.00000 | 23.99924 | 45.23008 | -0.4312 | 8.95996 |
August | 744.00000 | 23.99926 | 44.32908 | -0.4513 | 9.34177 |
September | 720.00000 | 23.99736 | 45.50758 | -0.4674 | 9.70333 |
October | 744.00000 | 23.98103 | 48.84969 | 0.40201 | 8.43312 |
November | 720.00000 | 23.53164 | 59.92371 | 0.31382 | 7.38312 |
December | 744.00000 | 22.79749 | 75.56567 | 0.20021 | 6.68976 |
Annual Sum or Average | 8760.00000 | 23.71824 | 53.10970 | -0.0101 | 8.36382 |
Minimum of Months | 672.00000 | 22.79749 | 40.95900 | -0.4997 | 6.68976 |
Maximum of Months | 744.00000 | 23.99933 | 75.56567 | 0.40201 | 10.30657 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.39466 | 23.19817 | -0.1531 | 5.81947 |
February | 672.00000 | 22.67724 | 19.74106 | -0.1059 | 5.60773 |
March | 744.00000 | 22.97328 | 18.26266 | -0.0423 | 5.37933 |
April | 720.00000 | 23.62416 | 20.06368 | 0.13623 | 5.68055 |
May | 744.00000 | 23.90952 | 28.70974 | -0.6263 | 13.56139 |
June | 720.00000 | 23.98628 | 36.15082 | -0.5291 | 11.01334 |
July | 744.00000 | 23.98833 | 52.88275 | -0.4132 | 8.59830 |
August | 744.00000 | 23.97414 | 47.86945 | -0.4606 | 9.51262 |
September | 720.00000 | 23.91965 | 45.69924 | -0.5049 | 10.58018 |
October | 744.00000 | 23.64371 | 37.57170 | 0.26117 | 6.69220 |
November | 720.00000 | 22.93957 | 23.46394 | -0.0161 | 5.47800 |
December | 744.00000 | 22.22102 | 20.31512 | -0.2134 | 6.27589 |
Annual Sum or Average | 8760.00000 | 23.35698 | 31.25254 | -0.2232 | 7.86464 |
Minimum of Months | 672.00000 | 22.22102 | 18.26266 | -0.6263 | 5.37933 |
Maximum of Months | 744.00000 | 23.98833 | 52.88275 | 0.26117 | 13.56139 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.576856E+11 | 0.00 | 579.17 | 118369.04 | 28-JAN-06:00 | 0.00 | 28.93 | 60.12 | 0.13 | 0.00 | 0.04 | 0.20 | 28-JAN-06:00 |
February | 0.396466E+11 | 0.00 | 399.48 | 123877.52 | 03-FEB-07:00 | 0.00 | 28.79 | 52.45 | 0.10 | 0.00 | 0.03 | 0.21 | 03-FEB-07:00 |
March | 0.248941E+11 | 0.00 | 314.39 | 119069.24 | 02-MAR-05:00 | 0.00 | 28.28 | 45.07 | 0.06 | 0.00 | 0.02 | 0.20 | 02-MAR-05:00 |
April | 0.326601E+10 | 0.00 | 81.33 | 44784.63 | 11-APR-08:03 | 0.00 | 26.61 | 31.14 | 0.01 | 0.00 | 0.00 | 0.08 | 11-APR-08:03 |
May | 39050431.03 | 0.00 | 11.53 | 29720.38 | 02-MAY-08:05 | 0.00 | 26.97 | 27.56 | 0.00 | 0.00 | 0.00 | 0.05 | 02-MAY-08:05 |
June | 582684.20 | 0.00 | 14.95 | 706.65 | 02-JUN-08:14 | 0.00 | 27.04 | 27.84 | 0.00 | 0.00 | 0.00 | 0.00 | 02-JUN-08:14 |
July | 4739348.08 | 0.00 | 119.30 | 1304.95 | 07-JUL-08:05 | 0.00 | 27.72 | 33.77 | 0.00 | 0.00 | 0.00 | 0.00 | 07-JUL-08:05 |
August | 3022015.81 | 0.00 | 65.69 | 1902.82 | 24-AUG-08:54 | 0.00 | 28.96 | 32.20 | 0.00 | 0.00 | 0.00 | 0.00 | 24-AUG-08:54 |
September | 74912210.24 | 0.00 | 43.07 | 34929.44 | 25-SEP-08:54 | 0.00 | 29.01 | 31.20 | 0.00 | 0.00 | 0.00 | 0.06 | 25-SEP-08:54 |
October | 0.896277E+09 | 0.00 | 71.38 | 38196.01 | 20-OCT-08:54 | 0.00 | 26.07 | 29.91 | 0.00 | 0.00 | 0.00 | 0.06 | 20-OCT-08:54 |
November | 0.318226E+11 | 0.00 | 370.02 | 96168.88 | 28-NOV-05:00 | 0.00 | 28.41 | 48.94 | 0.07 | 0.00 | 0.02 | 0.16 | 28-NOV-05:00 |
December | 0.826775E+11 | 0.00 | 599.59 | 171612.16 | 26-DEC-16:12 | 0.00 | 30.34 | 62.27 | 0.19 | 0.00 | 0.05 | 0.29 | 26-DEC-16:12 |
Annual Sum or Average | 0.241011E+12 | 0.00 | 2669.89 | 0.00 | 28.09 | 40.17 | 0.05 | 0.00 | 0.01 | ||||
Minimum of Months | 582684.20 | 0.00 | 11.53 | 706.65 | 0.00 | 26.07 | 27.56 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.826775E+11 | 0.00 | 599.59 | 171612.16 | 0.00 | 30.34 | 62.27 | 0.19 | 0.00 | 0.05 | 0.29 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.252385E+10 | 0.741867E+09 | 348.41 | 0.248305E+10 | 40801549.55 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:30 | 18358.05 | 01-JAN-16:12 | 18235.12 | 02-JAN-16:12 | 3164.62 | 16-JAN-16:12 | 4756.86 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.328224E+10 | 0.960376E+09 | 402.63 | 0.325136E+10 | 30883532.80 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-00:10 | 18512.42 | 08-FEB-09:02 | 18159.56 | 14-FEB-16:12 | 3114.04 | 13-FEB-19:02 | 4798.04 | 08-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.500805E+10 | 0.145779E+10 | 527.82 | 0.498527E+10 | 22776102.09 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 18776.90 | 11-MAR-16:12 | 18174.75 | 12-MAR-15:12 | 4504.82 | 11-MAR-09:02 | 4867.30 | 11-MAR-16:12 | 0.00 | 01-MAR-00:10 |
April | 0.883006E+10 | 0.262888E+10 | 641.85 | 0.871089E+10 | 0.119162E+09 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-06:53 | 19295.04 | 29-APR-08:62 | 18234.15 | 25-APR-15:12 | 2820.69 | 29-APR-08:62 | 5181.01 | 29-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.123999E+11 | 0.379941E+10 | 706.19 | 0.118864E+11 | 0.513450E+09 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-06:52 | 20447.79 | 28-MAY-08:62 | 18398.88 | 14-MAY-08:62 | 6174.35 | 25-MAY-08:62 | 5460.23 | 19-MAY-15:12 | 0.00 | 01-MAY-00:10 |
June | 0.150171E+11 | 0.484043E+10 | 697.29 | 0.141033E+11 | 0.913814E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:51 | 20629.93 | 28-JUN-08:62 | 18088.88 | 01-JUN-08:62 | 6747.44 | 28-JUN-08:62 | 5583.03 | 05-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.169523E+11 | 0.532240E+10 | 721.50 | 0.141862E+11 | 0.276611E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 22138.02 | 19-JUL-08:62 | 16784.48 | 05-JUL-18:02 | 10770.64 | 19-JUL-08:62 | 5724.74 | 02-JUL-15:12 | 0.00 | 01-JUL-00:10 |
August | 0.154314E+11 | 0.480778E+10 | 715.99 | 0.134184E+11 | 0.201293E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-06:51 | 21061.85 | 14-AUG-08:62 | 17343.58 | 23-AUG-08:62 | 7989.69 | 14-AUG-08:62 | 5611.00 | 04-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.137124E+11 | 0.414145E+10 | 688.16 | 0.118717E+11 | 0.184073E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 21264.28 | 14-SEP-08:62 | 18301.45 | 25-SEP-18:02 | 8399.18 | 14-SEP-08:62 | 5444.66 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.995878E+10 | 0.292083E+10 | 681.84 | 0.894608E+10 | 0.101270E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:53 | 20920.63 | 04-OCT-08:62 | 18324.68 | 21-OCT-18:02 | 7455.31 | 04-OCT-08:62 | 5372.50 | 04-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.447694E+10 | 0.130606E+10 | 455.41 | 0.436084E+10 | 0.116099E+09 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:53 | 19841.87 | 01-NOV-15:12 | 18374.07 | 09-NOV-16:12 | 5062.85 | 01-NOV-15:12 | 5130.40 | 01-NOV-15:12 | 0.00 | 01-NOV-00:10 |
December | 0.204983E+10 | 0.604677E+09 | 312.43 | 0.203427E+10 | 15558481.12 | 0.00 | 1.00 | 01-DEC-16:12 | 0.00 | 01-DEC-00:40 | 18289.97 | 25-DEC-16:12 | 18209.90 | 05-DEC-16:12 | 802.84 | 14-DEC-16:12 | 4738.52 | 25-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.109643E+12 | 0.335319E+11 | 6899.52 | 0.100238E+12 | 0.940502E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.204983E+10 | 0.604677E+09 | 312.43 | 0.203427E+10 | 15558481.12 | 0.00 | 1.00 | 0.00 | 18289.97 | 16784.48 | 802.84 | 4738.52 | 0.00 | |||||||
Maximum of Months | 0.169523E+11 | 0.532240E+10 | 721.50 | 0.141862E+11 | 0.276611E+10 | 0.00 | 1.00 | 0.00 | 22138.02 | 18398.88 | 10770.64 | 5724.74 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.991726E+09 | 0.293364E+09 | 212.33 | 0.968485E+09 | 23241227.55 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 18409.67 | 01-JAN-16:12 | 18144.90 | 12-JAN-19:42 | 2262.35 | 16-JAN-16:12 | 4771.56 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.139892E+10 | 0.414311E+09 | 260.83 | 0.137501E+10 | 23912450.29 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-00:10 | 18120.40 | 18-FEB-19:21 | 18120.40 | 18-FEB-19:21 | 2997.77 | 13-FEB-19:02 | 4694.24 | 18-FEB-19:21 | 0.00 | 01-FEB-00:10 |
March | 0.258734E+10 | 0.761371E+09 | 391.13 | 0.256538E+10 | 21962976.51 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 18841.06 | 11-MAR-16:12 | 18421.58 | 12-MAR-20:31 | 4529.17 | 11-MAR-09:02 | 4883.42 | 11-MAR-16:12 | 0.00 | 01-MAR-00:10 |
April | 0.700867E+10 | 0.209626E+10 | 530.67 | 0.690231E+10 | 0.106358E+09 | 0.00 | 1.00 | 01-APR-08:51 | 0.00 | 01-APR-06:53 | 19905.43 | 29-APR-08:51 | 18958.30 | 28-APR-21:51 | 3608.33 | 29-APR-08:53 | 5147.60 | 29-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.113558E+11 | 0.348594E+10 | 605.31 | 0.109014E+11 | 0.454419E+09 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 21418.45 | 28-MAY-08:51 | 18781.09 | 14-MAY-08:51 | 7335.54 | 28-MAY-08:54 | 5468.20 | 28-MAY-08:51 | 0.00 | 01-MAY-00:10 |
June | 0.144540E+11 | 0.467059E+10 | 625.92 | 0.136134E+11 | 0.840592E+09 | 0.00 | 1.00 | 01-JUN-08:31 | 0.00 | 01-JUN-05:13 | 21372.16 | 28-JUN-08:51 | 18740.55 | 07-JUN-06:51 | 7589.45 | 29-JUN-08:53 | 5543.75 | 05-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.160905E+11 | 0.505822E+10 | 643.28 | 0.135178E+11 | 0.257274E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 23967.29 | 21-JUL-08:51 | 17148.15 | 16-JUL-06:51 | 13016.26 | 19-JUL-08:51 | 5915.93 | 21-JUL-08:51 | 0.00 | 01-JUL-00:10 |
August | 0.139959E+11 | 0.437235E+10 | 618.91 | 0.121818E+11 | 0.181412E+10 | 0.00 | 1.00 | 01-AUG-07:51 | 0.00 | 01-AUG-05:12 | 22793.35 | 02-AUG-08:51 | 18300.54 | 23-AUG-08:51 | 10596.07 | 02-AUG-08:53 | 5833.95 | 02-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.111745E+11 | 0.338383E+10 | 554.88 | 0.958223E+10 | 0.159229E+10 | 0.00 | 1.00 | 01-SEP-08:51 | 0.00 | 01-SEP-05:13 | 22667.85 | 22-SEP-08:51 | 18999.65 | 25-SEP-21:51 | 10410.60 | 22-SEP-08:53 | 5703.41 | 22-SEP-08:51 | 0.00 | 01-SEP-00:10 |
October | 0.638115E+10 | 0.189060E+10 | 512.64 | 0.553995E+10 | 0.841204E+09 | 0.00 | 1.00 | 01-OCT-08:51 | 0.00 | 01-OCT-06:53 | 21772.34 | 16-OCT-21:51 | 18999.05 | 19-OCT-21:51 | 8566.73 | 16-OCT-21:54 | 5537.93 | 16-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.201301E+10 | 0.595237E+09 | 326.19 | 0.192720E+10 | 85809339.03 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:53 | 19876.22 | 02-NOV-19:21 | 18533.90 | 09-NOV-22:51 | 5034.59 | 01-NOV-15:12 | 5134.97 | 02-NOV-19:21 | 0.00 | 01-NOV-00:10 |
December | 0.684833E+09 | 0.202715E+09 | 172.49 | 0.677253E+09 | 7579446.96 | 0.00 | 1.00 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 | 18229.17 | 03-DEC-16:12 | 18026.55 | 05-DEC-16:12 | 740.42 | 03-DEC-16:12 | 4723.47 | 03-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.881364E+11 | 0.272248E+11 | 5454.59 | 0.797521E+11 | 0.838423E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.684833E+09 | 0.202715E+09 | 172.49 | 0.677253E+09 | 7579446.96 | 0.00 | 1.00 | 0.00 | 18120.40 | 17148.15 | 740.42 | 4694.24 | 0.00 | |||||||
Maximum of Months | 0.160905E+11 | 0.505822E+10 | 643.28 | 0.136134E+11 | 0.257274E+10 | 0.00 | 1.00 | 0.00 | 23967.29 | 18999.65 | 13016.26 | 5915.93 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.294682E+11 | 0.864203E+10 | 442.62 | 0.294620E+11 | 6118897.85 | 0.00 | 0.48 | 12-JAN-14:30 | 0.00 | 01-JAN-00:30 | 52617.48 | 12-JAN-14:30 | 52617.48 | 12-JAN-14:30 | 588.23 | 16-JAN-12:30 | 14900.48 | 12-JAN-14:30 | 0.00 | 01-JAN-00:05 |
February | 0.302214E+11 | 0.885551E+10 | 449.53 | 0.302157E+11 | 5681915.16 | 0.00 | 0.46 | 06-FEB-13:50 | 0.00 | 01-FEB-00:10 | 50105.68 | 06-FEB-13:50 | 50105.68 | 06-FEB-13:50 | 586.48 | 13-FEB-22:00 | 14224.13 | 06-FEB-13:50 | 0.00 | 01-FEB-00:10 |
March | 0.312545E+11 | 0.921733E+10 | 518.70 | 0.312533E+11 | 1215918.09 | 0.00 | 0.39 | 14-MAR-14:10 | 0.00 | 01-MAR-00:10 | 42038.83 | 14-MAR-14:10 | 42038.83 | 14-MAR-14:10 | 116.49 | 11-MAR-11:30 | 12064.59 | 14-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.413763E+11 | 0.125788E+11 | 632.50 | 0.413676E+11 | 8696498.27 | 0.00 | 0.43 | 01-APR-14:10 | 0.00 | 01-APR-00:10 | 44580.25 | 01-APR-14:10 | 44580.25 | 01-APR-14:10 | 416.39 | 18-APR-21:00 | 14764.69 | 21-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.505859E+11 | 0.159162E+11 | 728.83 | 0.500525E+11 | 0.533390E+09 | 0.00 | 0.41 | 21-MAY-14:10 | 0.00 | 02-MAY-00:50 | 41972.45 | 19-MAY-14:10 | 41972.45 | 19-MAY-14:10 | 3039.91 | 28-MAY-08:00 | 14981.15 | 21-MAY-14:10 | 0.00 | 01-MAY-00:10 |
June | 0.614629E+11 | 0.204258E+11 | 720.00 | 0.604566E+11 | 0.100634E+10 | 0.00 | 0.48 | 15-JUN-14:10 | 0.01 | 28-JUN-03:10 | 45961.53 | 15-JUN-14:10 | 45961.53 | 15-JUN-14:10 | 4671.93 | 03-JUN-19:10 | 17704.97 | 15-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.692915E+11 | 0.222912E+11 | 744.00 | 0.631182E+11 | 0.617336E+10 | 0.00 | 0.47 | 03-JUL-14:10 | 0.03 | 05-JUL-04:00 | 48331.92 | 03-JUL-14:10 | 48331.92 | 03-JUL-14:10 | 8594.76 | 20-JUL-15:00 | 18091.00 | 03-JUL-14:10 | 0.00 | 01-JUL-00:10 |
August | 0.672541E+11 | 0.214353E+11 | 744.00 | 0.636240E+11 | 0.363009E+10 | 0.00 | 0.51 | 27-AUG-14:10 | 0.02 | 17-AUG-03:10 | 52599.58 | 27-AUG-14:10 | 52599.58 | 27-AUG-14:10 | 6113.75 | 03-AUG-06:53 | 18408.78 | 27-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.684646E+11 | 0.210504E+11 | 712.50 | 0.647190E+11 | 0.374558E+10 | 0.00 | 0.57 | 19-SEP-14:10 | 0.00 | 25-SEP-01:50 | 61189.41 | 19-SEP-14:10 | 61189.41 | 19-SEP-14:10 | 5936.23 | 14-SEP-10:10 | 20772.33 | 19-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 0.599340E+11 | 0.176883E+11 | 685.67 | 0.581515E+11 | 0.178249E+10 | 0.00 | 0.59 | 01-OCT-14:10 | 0.00 | 07-OCT-00:50 | 64309.59 | 18-OCT-14:10 | 63459.67 | 01-OCT-14:10 | 5259.71 | 04-OCT-10:50 | 20894.87 | 01-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.406318E+11 | 0.118064E+11 | 504.94 | 0.405670E+11 | 64765420.66 | 0.00 | 0.49 | 09-NOV-13:00 | 0.00 | 01-NOV-01:30 | 55211.46 | 09-NOV-13:10 | 55211.46 | 09-NOV-13:10 | 1441.43 | 03-NOV-09:00 | 15591.36 | 09-NOV-13:10 | 0.00 | 01-NOV-00:10 |
December | 0.269011E+11 | 0.790327E+10 | 437.24 | 0.269011E+11 | 0.00 | 0.00 | 0.43 | 16-DEC-13:30 | 0.00 | 01-DEC-00:10 | 45886.80 | 16-DEC-13:30 | 45886.80 | 16-DEC-13:30 | 0.00 | 12-DEC-15:05 | 13074.91 | 16-DEC-13:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.576846E+12 | 0.177811E+12 | 7320.53 | 0.559889E+12 | 0.169577E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.269011E+11 | 0.790327E+10 | 437.24 | 0.269011E+11 | 0.00 | 0.00 | 0.39 | 0.00 | 41972.45 | 41972.45 | 0.00 | 12064.59 | 0.00 | |||||||
Maximum of Months | 0.692915E+11 | 0.222912E+11 | 744.00 | 0.647190E+11 | 0.617336E+10 | 0.00 | 0.59 | 0.03 | 64309.59 | 63459.67 | 8594.76 | 20894.87 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.113059E+11 | 0.332726E+10 | 268.26 | 0.109145E+11 | 0.391346E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-03:40 | 127772.12 | 15-JAN-19:03 | 121178.61 | 02-JAN-19:02 | 29837.44 | 15-JAN-19:03 | 33113.92 | 15-JAN-19:03 | 0.00 | 01-JAN-00:05 |
February | 0.158035E+11 | 0.462034E+10 | 295.69 | 0.153881E+11 | 0.415329E+09 | 0.00 | 1.00 | 03-FEB-19:02 | 0.00 | 01-FEB-00:40 | 128924.41 | 13-FEB-19:02 | 121178.61 | 23-FEB-19:43 | 29044.94 | 13-FEB-19:02 | 33402.60 | 13-FEB-19:02 | 0.00 | 01-FEB-00:10 |
March | 0.247508E+11 | 0.720187E+10 | 391.82 | 0.244800E+11 | 0.270821E+09 | 0.00 | 1.00 | 02-MAR-19:03 | 0.00 | 01-MAR-01:30 | 127229.05 | 11-MAR-09:02 | 121178.61 | 05-MAR-09:02 | 23306.53 | 11-MAR-09:03 | 32976.34 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.559680E+11 | 0.164031E+11 | 521.71 | 0.550527E+11 | 0.915302E+09 | 0.00 | 1.00 | 01-APR-08:51 | 0.00 | 01-APR-06:53 | 132770.02 | 18-APR-21:51 | 125074.69 | 28-APR-21:51 | 25053.54 | 18-APR-21:56 | 35049.49 | 29-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.874980E+11 | 0.261826E+11 | 591.57 | 0.835151E+11 | 0.398294E+10 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 141555.46 | 28-MAY-08:51 | 124292.69 | 14-MAY-08:51 | 44218.64 | 28-MAY-08:56 | 37042.02 | 19-MAY-15:12 | 0.00 | 01-MAY-00:10 |
June | 0.111593E+12 | 0.349630E+11 | 611.22 | 0.103958E+12 | 0.763431E+10 | 0.00 | 1.00 | 01-JUN-08:31 | 0.00 | 01-JUN-05:13 | 141536.60 | 28-JUN-08:51 | 125296.70 | 06-JUN-07:31 | 50258.52 | 29-JUN-08:55 | 37736.46 | 05-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.131536E+12 | 0.399030E+11 | 628.36 | 0.106047E+12 | 0.254885E+11 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 160272.71 | 21-JUL-08:51 | 113707.48 | 05-JUL-18:02 | 90698.35 | 19-JUL-08:51 | 39703.06 | 21-JUL-08:51 | 0.00 | 01-JUL-00:10 |
August | 0.112588E+12 | 0.340181E+11 | 605.26 | 0.950349E+11 | 0.175535E+11 | 0.00 | 1.00 | 01-AUG-07:51 | 0.00 | 01-AUG-05:12 | 152028.99 | 02-AUG-08:51 | 125012.60 | 23-AUG-08:51 | 70647.66 | 02-AUG-08:53 | 39079.60 | 02-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.890242E+11 | 0.261123E+11 | 541.24 | 0.732405E+11 | 0.157837E+11 | 0.00 | 1.00 | 01-SEP-08:51 | 0.00 | 01-SEP-05:13 | 151431.95 | 03-SEP-21:51 | 125794.68 | 25-SEP-21:51 | 70416.75 | 22-SEP-08:53 | 38217.94 | 03-SEP-21:51 | 0.00 | 01-SEP-00:10 |
October | 0.565520E+11 | 0.163685E+11 | 494.35 | 0.483655E+11 | 0.818655E+10 | 0.00 | 1.00 | 01-OCT-08:51 | 0.00 | 01-OCT-06:53 | 147967.15 | 03-OCT-21:51 | 127020.94 | 21-OCT-21:51 | 61818.17 | 03-OCT-21:55 | 37574.69 | 03-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.195217E+11 | 0.570110E+10 | 325.72 | 0.186730E+11 | 0.848659E+09 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-06:53 | 131627.02 | 02-NOV-19:21 | 125198.74 | 09-NOV-22:51 | 30612.76 | 02-NOV-19:24 | 34062.74 | 02-NOV-19:21 | 0.00 | 01-NOV-00:10 |
December | 0.843827E+10 | 0.248397E+10 | 212.81 | 0.834046E+10 | 97804553.86 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-02:20 | 121178.61 | 10-DEC-09:02 | 121178.61 | 20-DEC-19:02 | 9258.28 | 14-DEC-19:03 | 31375.18 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.724579E+12 | 0.217285E+12 | 5488.00 | 0.643010E+12 | 0.815688E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.843827E+10 | 0.248397E+10 | 212.81 | 0.834046E+10 | 97804553.86 | 0.00 | 1.00 | 0.00 | 121178.61 | 113707.48 | 9258.28 | 31375.18 | 0.00 | |||||||
Maximum of Months | 0.131536E+12 | 0.399030E+11 | 628.36 | 0.106047E+12 | 0.254885E+11 | 0.00 | 1.00 | 0.00 | 160272.71 | 127020.94 | 90698.35 | 39703.06 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.228159E+10 | 0.670735E+09 | 355.99 | 0.223614E+10 | 45454914.72 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 16324.94 | 24-JAN-09:02 | 15871.85 | 02-JAN-16:12 | 2551.17 | 16-JAN-16:12 | 4231.71 | 24-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.334826E+10 | 0.978768E+09 | 428.10 | 0.331421E+10 | 34051830.98 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-00:10 | 16445.38 | 27-FEB-16:12 | 15758.04 | 14-FEB-16:12 | 2956.06 | 13-FEB-19:02 | 4262.78 | 27-FEB-16:12 | 0.00 | 01-FEB-00:10 |
March | 0.486990E+10 | 0.142024E+10 | 546.65 | 0.484617E+10 | 23732863.89 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:10 | 17012.00 | 11-MAR-09:02 | 15786.76 | 12-MAR-15:12 | 4384.29 | 11-MAR-09:02 | 4403.99 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.890055E+10 | 0.263065E+10 | 671.72 | 0.877142E+10 | 0.129123E+09 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-06:53 | 16578.65 | 29-APR-08:62 | 15869.22 | 25-APR-15:12 | 2093.38 | 29-APR-08:03 | 4517.86 | 29-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.123983E+11 | 0.374814E+10 | 729.68 | 0.118688E+11 | 0.529527E+09 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-06:52 | 17288.92 | 23-MAY-08:62 | 15983.96 | 14-MAY-08:62 | 3756.32 | 23-MAY-08:62 | 4767.42 | 19-MAY-15:12 | 0.00 | 01-MAY-00:10 |
June | 0.151511E+11 | 0.480022E+10 | 711.21 | 0.142106E+11 | 0.940429E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:51 | 17870.55 | 29-JUN-08:62 | 15830.02 | 10-JUN-08:62 | 5678.27 | 29-JUN-08:62 | 4862.49 | 05-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.171118E+11 | 0.529190E+10 | 732.73 | 0.142796E+11 | 0.283217E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 19326.58 | 19-JUL-08:62 | 14693.78 | 05-JUL-18:02 | 9522.88 | 19-JUL-08:62 | 4998.66 | 02-JUL-15:12 | 0.00 | 01-JUL-00:10 |
August | 0.155196E+11 | 0.476232E+10 | 728.15 | 0.134540E+11 | 0.206557E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-06:51 | 18358.17 | 14-AUG-08:62 | 15434.10 | 23-AUG-08:62 | 7035.57 | 14-AUG-08:62 | 4908.01 | 04-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.136335E+11 | 0.406425E+10 | 704.76 | 0.117278E+11 | 0.190571E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 18115.80 | 22-SEP-08:62 | 15912.28 | 24-SEP-15:12 | 6290.41 | 24-SEP-08:62 | 4738.04 | 01-SEP-15:12 | 0.00 | 01-SEP-00:10 |
October | 0.932796E+10 | 0.272657E+10 | 694.64 | 0.833052E+10 | 0.997444E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:53 | 18037.36 | 04-OCT-08:62 | 15967.09 | 21-OCT-18:02 | 6179.64 | 13-OCT-15:12 | 4644.11 | 03-OCT-15:12 | 0.00 | 01-OCT-00:10 |
November | 0.420557E+10 | 0.122533E+10 | 459.79 | 0.409608E+10 | 0.109483E+09 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:53 | 17211.30 | 01-NOV-15:12 | 15975.68 | 09-NOV-16:12 | 4596.77 | 01-NOV-15:12 | 4451.76 | 01-NOV-15:12 | 0.00 | 01-NOV-00:10 |
December | 0.190321E+10 | 0.559895E+09 | 325.32 | 0.188501E+10 | 18197976.86 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:20 | 15949.27 | 11-DEC-09:02 | 15827.98 | 05-DEC-16:12 | 858.05 | 03-DEC-16:12 | 4132.32 | 11-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.108651E+12 | 0.328790E+11 | 7088.75 | 0.990205E+11 | 0.963090E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.190321E+10 | 0.559895E+09 | 325.32 | 0.188501E+10 | 18197976.86 | 0.00 | 1.00 | 0.00 | 15949.27 | 14693.78 | 858.05 | 4132.32 | 0.00 | |||||||
Maximum of Months | 0.171118E+11 | 0.529190E+10 | 732.73 | 0.142796E+11 | 0.283217E+10 | 0.00 | 1.00 | 0.00 | 19326.58 | 15983.96 | 9522.88 | 4998.66 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.762759E+09 | 0.225596E+09 | 187.72 | 0.736496E+09 | 26262947.46 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 16078.53 | 01-JAN-16:12 | 15654.60 | 12-JAN-19:42 | 1760.59 | 24-JAN-09:02 | 4167.60 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.152666E+10 | 0.448966E+09 | 280.68 | 0.149749E+10 | 29164341.36 | 0.00 | 1.00 | 04-FEB-09:02 | 0.00 | 01-FEB-00:10 | 16311.43 | 28-FEB-09:02 | 15678.10 | 07-FEB-21:41 | 2779.83 | 13-FEB-19:02 | 4228.09 | 28-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.276184E+10 | 0.809931E+09 | 421.89 | 0.273883E+10 | 23013505.11 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:10 | 16867.50 | 11-MAR-09:02 | 15662.98 | 10-MAR-19:02 | 4278.17 | 11-MAR-09:02 | 4366.82 | 11-MAR-09:02 | 0.00 | 01-MAR-00:10 |
April | 0.711042E+10 | 0.210749E+10 | 564.26 | 0.699669E+10 | 0.113738E+09 | 0.00 | 1.00 | 01-APR-08:51 | 0.00 | 01-APR-06:53 | 17793.36 | 29-APR-08:32 | 17211.36 | 19-APR-08:32 | 3391.69 | 29-APR-08:56 | 4580.88 | 29-APR-08:32 | 0.00 | 01-APR-00:10 |
May | 0.110780E+11 | 0.336127E+10 | 625.17 | 0.106034E+11 | 0.474628E+09 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 19088.21 | 28-MAY-08:32 | 17251.50 | 27-MAY-08:32 | 5546.13 | 28-MAY-21:54 | 4846.55 | 28-MAY-08:32 | 0.00 | 01-MAY-00:10 |
June | 0.143471E+11 | 0.456602E+10 | 638.44 | 0.134786E+11 | 0.868539E+09 | 0.00 | 1.00 | 01-JUN-08:12 | 0.00 | 01-JUN-05:13 | 19014.84 | 30-JUN-08:32 | 16778.45 | 17-JUN-07:12 | 6654.06 | 29-JUN-08:54 | 4880.06 | 04-JUN-08:32 | 0.00 | 01-JUN-00:10 |
July | 0.160129E+11 | 0.496344E+10 | 654.12 | 0.133962E+11 | 0.261670E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 21118.19 | 21-JUL-08:32 | 15604.46 | 11-JUL-07:32 | 11517.50 | 19-JUL-08:51 | 5187.19 | 21-JUL-08:32 | 0.00 | 01-JUL-00:10 |
August | 0.138569E+11 | 0.426607E+10 | 630.76 | 0.119937E+11 | 0.186318E+10 | 0.00 | 1.00 | 01-AUG-07:32 | 0.00 | 01-AUG-05:12 | 20113.73 | 02-AUG-08:32 | 17043.68 | 23-AUG-08:32 | 8217.52 | 16-AUG-21:53 | 5090.34 | 02-AUG-08:32 | 0.00 | 01-AUG-00:10 |
September | 0.108267E+11 | 0.323920E+10 | 571.77 | 0.917472E+10 | 0.165195E+10 | 0.00 | 1.00 | 01-SEP-08:32 | 0.00 | 01-SEP-05:13 | 19985.60 | 09-SEP-08:32 | 16656.41 | 11-SEP-08:51 | 9045.22 | 22-SEP-08:54 | 5008.41 | 09-SEP-08:32 | 0.00 | 01-SEP-00:10 |
October | 0.600873E+10 | 0.176987E+10 | 538.62 | 0.520648E+10 | 0.802245E+09 | 0.00 | 1.00 | 01-OCT-08:51 | 0.00 | 01-OCT-06:53 | 19070.93 | 04-OCT-08:51 | 16504.46 | 20-OCT-08:51 | 7491.61 | 03-OCT-21:54 | 4843.25 | 04-OCT-08:51 | 0.00 | 01-OCT-00:10 |
November | 0.181572E+10 | 0.533206E+09 | 324.77 | 0.173913E+10 | 76590470.62 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:53 | 17213.09 | 02-NOV-19:21 | 16329.39 | 10-NOV-09:51 | 4630.66 | 01-NOV-15:12 | 4449.14 | 02-NOV-19:21 | 0.00 | 01-NOV-00:10 |
December | 0.594649E+09 | 0.175825E+09 | 146.86 | 0.584731E+09 | 9918698.99 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 15840.64 | 11-DEC-09:02 | 15696.80 | 09-DEC-09:02 | 654.24 | 13-DEC-09:02 | 4104.32 | 11-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.867024E+11 | 0.264669E+11 | 5585.06 | 0.781465E+11 | 0.855593E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.594649E+09 | 0.175825E+09 | 146.86 | 0.584731E+09 | 9918698.99 | 0.00 | 1.00 | 0.00 | 15840.64 | 15604.46 | 654.24 | 4104.32 | 0.00 | |||||||
Maximum of Months | 0.160129E+11 | 0.496344E+10 | 654.12 | 0.134786E+11 | 0.261670E+10 | 0.00 | 1.00 | 0.00 | 21118.19 | 17251.50 | 11517.50 | 5187.19 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.440784E+09 | 0.129688E+09 | 235.06 | 0.435067E+09 | 5716670.32 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 5211.60 | 01-JAN-16:12 | 5172.46 | 02-JAN-16:12 | 490.69 | 16-JAN-16:12 | 1350.50 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.646379E+09 | 0.189201E+09 | 292.76 | 0.643284E+09 | 3094573.42 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-00:10 | 5140.94 | 26-FEB-16:12 | 5140.94 | 26-FEB-16:12 | 512.70 | 27-FEB-16:12 | 1331.41 | 26-FEB-16:12 | 0.00 | 01-FEB-00:10 |
March | 0.109657E+10 | 0.319476E+09 | 411.09 | 0.109287E+10 | 3699118.84 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 5394.84 | 11-MAR-16:12 | 5163.05 | 12-MAR-15:12 | 676.19 | 11-MAR-16:12 | 1398.19 | 11-MAR-16:12 | 0.00 | 01-MAR-00:10 |
April | 0.221652E+10 | 0.663135E+09 | 596.74 | 0.218805E+10 | 28466641.09 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-00:10 | 5485.23 | 29-APR-08:62 | 5167.61 | 25-APR-15:12 | 960.67 | 30-APR-08:62 | 1466.05 | 29-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.327069E+10 | 0.100934E+10 | 702.29 | 0.314080E+10 | 0.129890E+09 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-06:52 | 5842.61 | 28-MAY-08:62 | 5202.94 | 14-MAY-08:62 | 1898.94 | 25-MAY-08:62 | 1544.78 | 19-MAY-15:12 | 0.00 | 01-MAY-00:10 |
June | 0.415014E+10 | 0.134770E+10 | 699.25 | 0.391543E+10 | 0.234710E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:51 | 5896.64 | 28-JUN-08:62 | 5122.53 | 12-JUN-08:62 | 2045.51 | 28-JUN-08:62 | 1578.80 | 05-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.464573E+10 | 0.146994E+10 | 723.37 | 0.393567E+10 | 0.710060E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 6383.13 | 19-JUL-08:62 | 4748.73 | 05-JUL-18:02 | 3337.15 | 19-JUL-08:62 | 1618.14 | 02-JUL-15:12 | 0.00 | 01-JUL-00:10 |
August | 0.417792E+10 | 0.131135E+10 | 715.51 | 0.366493E+10 | 0.512995E+09 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-06:51 | 6022.15 | 14-AUG-08:62 | 4913.18 | 23-AUG-08:62 | 2498.11 | 14-AUG-08:62 | 1584.01 | 04-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.360342E+10 | 0.109601E+10 | 678.47 | 0.314567E+10 | 0.457753E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 6113.37 | 04-SEP-08:62 | 5188.33 | 25-SEP-18:02 | 2610.03 | 04-SEP-08:62 | 1560.69 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.238086E+10 | 0.701187E+09 | 629.05 | 0.214318E+10 | 0.237674E+09 | 0.00 | 1.00 | 01-OCT-15:12 | 0.00 | 01-OCT-06:53 | 6002.05 | 04-OCT-08:62 | 5191.93 | 21-OCT-18:02 | 2330.80 | 04-OCT-08:62 | 1537.95 | 04-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.935754E+09 | 0.273306E+09 | 361.08 | 0.912854E+09 | 22899985.91 | 0.00 | 1.00 | 02-NOV-15:12 | 0.00 | 01-NOV-01:00 | 5483.24 | 02-NOV-18:02 | 5206.89 | 09-NOV-16:12 | 1323.02 | 01-NOV-15:12 | 1420.24 | 02-NOV-18:02 | 0.00 | 01-NOV-00:10 |
December | 0.336168E+09 | 99332373.19 | 202.87 | 0.334191E+09 | 1976617.72 | 0.00 | 1.00 | 01-DEC-16:12 | 0.00 | 01-DEC-00:10 | 5205.42 | 03-DEC-16:12 | 5155.69 | 05-DEC-16:12 | 190.63 | 03-DEC-16:12 | 1348.84 | 03-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.279009E+11 | 0.860967E+10 | 6247.53 | 0.255520E+11 | 0.234894E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.336168E+09 | 99332373.19 | 202.87 | 0.334191E+09 | 1976617.72 | 0.00 | 1.00 | 0.00 | 5140.94 | 4748.73 | 190.63 | 1331.41 | 0.00 | |||||||
Maximum of Months | 0.464573E+10 | 0.146994E+10 | 723.37 | 0.393567E+10 | 0.710060E+09 | 0.00 | 1.00 | 0.00 | 6383.13 | 5206.89 | 3337.15 | 1618.14 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.127771E+09 | 37697235.58 | 103.40 | 0.125026E+09 | 2744315.10 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 5233.70 | 01-JAN-16:12 | 5115.05 | 19-JAN-16:12 | 405.17 | 16-JAN-09:04 | 1356.62 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.218203E+09 | 64679280.41 | 164.23 | 0.216837E+09 | 1365788.66 | 0.00 | 1.00 | 02-FEB-16:12 | 0.00 | 01-FEB-00:10 | 5136.89 | 18-FEB-19:21 | 5136.89 | 18-FEB-19:21 | 405.38 | 27-FEB-17:32 | 1330.89 | 18-FEB-19:21 | 0.00 | 01-FEB-00:10 |
March | 0.507300E+09 | 0.149340E+09 | 285.35 | 0.503980E+09 | 3320012.83 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 5434.50 | 11-MAR-16:12 | 5222.52 | 20-MAR-19:41 | 932.99 | 11-MAR-16:12 | 1407.61 | 11-MAR-16:12 | 0.00 | 01-MAR-00:10 |
April | 0.178539E+10 | 0.536605E+09 | 494.68 | 0.175980E+10 | 25592429.25 | 0.00 | 1.00 | 01-APR-08:51 | 0.00 | 01-APR-01:10 | 5625.84 | 29-APR-08:51 | 5356.37 | 28-APR-21:51 | 1049.61 | 29-APR-08:53 | 1453.35 | 29-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.304431E+10 | 0.940684E+09 | 607.68 | 0.292879E+10 | 0.115516E+09 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 6073.24 | 28-MAY-08:51 | 5307.92 | 14-MAY-08:51 | 2033.45 | 28-MAY-08:53 | 1549.62 | 28-MAY-08:51 | 0.00 | 01-MAY-00:10 |
June | 0.403516E+10 | 0.131212E+10 | 628.81 | 0.381821E+10 | 0.216951E+09 | 0.00 | 1.00 | 01-JUN-08:31 | 0.00 | 01-JUN-05:13 | 6069.47 | 28-JUN-08:51 | 5288.31 | 07-JUN-06:51 | 2223.02 | 29-JUN-08:53 | 1574.38 | 05-JUN-16:54 | 0.00 | 01-JUN-00:10 |
July | 0.445549E+10 | 0.141037E+10 | 646.19 | 0.379392E+10 | 0.661566E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 6785.68 | 21-JUL-08:51 | 4703.62 | 05-JUL-18:02 | 3801.61 | 19-JUL-08:51 | 1674.18 | 21-JUL-08:51 | 0.00 | 01-JUL-00:10 |
August | 0.384709E+10 | 0.121003E+10 | 622.15 | 0.338219E+10 | 0.464897E+09 | 0.00 | 1.00 | 01-AUG-07:51 | 0.00 | 01-AUG-05:12 | 6421.00 | 02-AUG-08:51 | 5217.15 | 23-AUG-08:51 | 2936.18 | 02-AUG-08:53 | 1645.76 | 02-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.300170E+10 | 0.915698E+09 | 554.99 | 0.260310E+10 | 0.398601E+09 | 0.00 | 1.00 | 01-SEP-08:51 | 0.00 | 01-SEP-05:13 | 6446.20 | 22-SEP-08:51 | 5362.38 | 25-SEP-21:51 | 3023.81 | 22-SEP-08:53 | 1619.17 | 22-SEP-08:51 | 0.00 | 01-SEP-00:10 |
October | 0.151515E+10 | 0.451407E+09 | 486.42 | 0.131816E+10 | 0.196997E+09 | 0.00 | 1.00 | 01-OCT-08:51 | 0.00 | 01-OCT-06:53 | 6157.71 | 16-OCT-21:51 | 5360.81 | 19-OCT-21:51 | 2505.17 | 04-OCT-08:53 | 1566.22 | 16-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.348061E+09 | 0.103037E+09 | 231.06 | 0.332718E+09 | 15342800.93 | 0.00 | 1.00 | 02-NOV-19:21 | 0.00 | 01-NOV-01:20 | 5612.22 | 02-NOV-19:21 | 5246.20 | 09-NOV-22:51 | 1269.46 | 01-NOV-15:12 | 1450.13 | 02-NOV-19:21 | 0.00 | 01-NOV-00:10 |
December | 75076453.43 | 22098624.31 | 76.89 | 74354936.96 | 721516.47 | 0.00 | 1.00 | 04-DEC-16:12 | 0.00 | 01-DEC-00:10 | 5169.38 | 04-DEC-16:12 | 5076.40 | 06-DEC-16:12 | 260.17 | 03-DEC-16:12 | 1339.59 | 04-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.229607E+11 | 0.715377E+10 | 4901.85 | 0.208571E+11 | 0.210362E+10 | 0.00 | ||||||||||||||
Minimum of Months | 75076453.43 | 22098624.31 | 76.89 | 74354936.96 | 721516.47 | 0.00 | 1.00 | 0.00 | 5136.89 | 4703.62 | 260.17 | 1330.89 | 0.00 | |||||||
Maximum of Months | 0.445549E+10 | 0.141037E+10 | 646.19 | 0.381821E+10 | 0.661566E+09 | 0.00 | 1.00 | 0.00 | 6785.68 | 5362.38 | 3801.61 | 1674.18 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.615113E+10 | 0.178353E+10 | 372.95 | 0.606746E+10 | 83664295.08 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:05 | 24826.18 | 16-JAN-16:12 | 23749.56 | 12-JAN-16:12 | 3858.91 | 16-JAN-16:12 | 6434.17 | 16-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.654719E+10 | 0.189577E+10 | 403.55 | 0.650175E+10 | 45441237.42 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-00:10 | 24748.76 | 14-FEB-09:02 | 23712.74 | 26-FEB-16:12 | 4081.79 | 27-FEB-19:02 | 6414.56 | 14-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.724153E+10 | 0.210454E+10 | 488.14 | 0.720834E+10 | 33193134.49 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 24664.82 | 11-MAR-16:12 | 23674.65 | 12-MAR-15:12 | 6320.10 | 11-MAR-09:02 | 6393.17 | 11-MAR-16:12 | 0.00 | 01-MAR-00:10 |
April | 0.114455E+11 | 0.341270E+10 | 614.67 | 0.112634E+11 | 0.182070E+09 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-01:20 | 25096.08 | 30-APR-08:62 | 23898.21 | 25-APR-15:12 | 4054.74 | 30-APR-08:62 | 6776.36 | 29-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.155492E+11 | 0.477362E+10 | 700.66 | 0.147747E+11 | 0.774522E+09 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-06:52 | 26747.06 | 28-MAY-08:62 | 23865.47 | 14-MAY-08:62 | 8543.97 | 25-MAY-08:62 | 7154.75 | 19-MAY-15:12 | 0.00 | 01-MAY-00:10 |
June | 0.198570E+11 | 0.639252E+10 | 696.70 | 0.184835E+11 | 0.137345E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:51 | 27033.63 | 28-JUN-08:62 | 23627.13 | 10-JUN-08:62 | 9556.12 | 28-JUN-08:62 | 7315.25 | 05-JUN-15:12 | 0.00 | 01-JUN-00:10 |
July | 0.233415E+11 | 0.730008E+10 | 720.90 | 0.191965E+11 | 0.414505E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 29567.37 | 19-JUL-08:62 | 21997.38 | 05-JUL-18:02 | 15959.04 | 19-JUL-08:62 | 7494.84 | 02-JUL-15:12 | 0.00 | 01-JUL-00:10 |
August | 0.217477E+11 | 0.674472E+10 | 715.20 | 0.187019E+11 | 0.304578E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-06:51 | 27656.37 | 18-AUG-08:62 | 22822.91 | 23-AUG-08:62 | 11384.27 | 14-AUG-08:62 | 7346.20 | 04-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.202738E+11 | 0.608708E+10 | 685.43 | 0.174624E+11 | 0.281141E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 28121.76 | 14-SEP-08:62 | 23868.11 | 24-SEP-15:12 | 12091.55 | 14-SEP-08:62 | 7179.20 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.156741E+11 | 0.454765E+10 | 670.38 | 0.141391E+11 | 0.153499E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:53 | 27509.05 | 04-OCT-08:62 | 23945.97 | 21-OCT-18:02 | 10418.62 | 04-OCT-08:62 | 7053.54 | 04-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.887989E+10 | 0.254767E+10 | 451.77 | 0.869940E+10 | 0.180486E+09 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:53 | 25892.51 | 01-NOV-15:12 | 23822.73 | 09-NOV-19:02 | 7228.03 | 01-NOV-15:12 | 6694.18 | 01-NOV-15:12 | 0.00 | 01-NOV-00:10 |
December | 0.562600E+10 | 0.163432E+10 | 358.21 | 0.558791E+10 | 38091167.27 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 24234.76 | 14-DEC-16:12 | 23680.42 | 09-DEC-09:02 | 1734.17 | 14-DEC-16:12 | 6281.66 | 14-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.162335E+12 | 0.492242E+11 | 6878.55 | 0.148086E+12 | 0.142482E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.562600E+10 | 0.163432E+10 | 358.21 | 0.558791E+10 | 33193134.49 | 0.00 | 1.00 | 0.00 | 24234.76 | 21997.38 | 1734.17 | 6281.66 | 0.00 | |||||||
Maximum of Months | 0.233415E+11 | 0.730008E+10 | 720.90 | 0.191965E+11 | 0.414505E+10 | 0.00 | 1.00 | 0.00 | 29567.37 | 23945.97 | 15959.04 | 7494.84 | 0.00 |
Report: DXReportMonthly
For: PTAC_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.633590E+10 | 0.188633E+10 | 559.32 | 0.418916E+10 | 0.214675E+10 | 0.00 | 0.27 | 12-JAN-15:10 | 0.00 | 01-JAN-08:65 | 8322.95 | 12-JAN-15:10 | 6941.15 | 12-JAN-15:10 | 3166.84 | 18-JAN-13:00 | 2435.68 | 12-JAN-15:10 | 0.00 | 01-JAN-00:05 |
February | 0.768503E+10 | 0.228500E+10 | 585.93 | 0.583399E+10 | 0.185104E+10 | 0.00 | 0.27 | 20-FEB-13:00 | 0.00 | 01-FEB-03:30 | 8425.59 | 20-FEB-13:00 | 7748.00 | 21-FEB-16:13 | 2776.96 | 13-FEB-22:10 | 2464.40 | 20-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 0.103012E+11 | 0.305796E+10 | 696.08 | 0.835122E+10 | 0.194995E+10 | 0.00 | 0.30 | 14-MAR-18:03 | 0.00 | 01-MAR-04:10 | 9077.37 | 14-MAR-18:03 | 8707.45 | 14-MAR-18:03 | 2354.79 | 25-MAR-11:40 | 2645.64 | 14-MAR-18:03 | 0.00 | 01-MAR-00:10 |
April | 0.157559E+11 | 0.474640E+10 | 718.83 | 0.140423E+11 | 0.171364E+10 | 0.00 | 0.41 | 19-APR-18:03 | 0.00 | 11-APR-06:05 | 12274.79 | 19-APR-18:03 | 12274.79 | 19-APR-18:03 | 2278.87 | 18-APR-21:10 | 3955.42 | 19-APR-18:03 | 0.00 | 01-APR-00:10 |
May | 0.217786E+11 | 0.669790E+10 | 744.00 | 0.192656E+11 | 0.251301E+10 | 0.00 | 0.50 | 19-MAY-18:15 | 0.07 | 02-MAY-06:05 | 15110.20 | 19-MAY-18:15 | 15110.20 | 19-MAY-18:15 | 3633.28 | 24-MAY-21:52 | 5097.98 | 19-MAY-18:15 | 0.00 | 01-MAY-00:10 |
June | 0.268933E+11 | 0.863558E+10 | 720.00 | 0.238556E+11 | 0.303776E+10 | 0.00 | 0.62 | 14-JUN-18:03 | 0.14 | 12-JUN-06:05 | 17974.80 | 15-JUN-18:13 | 17974.80 | 15-JUN-18:13 | 4277.38 | 19-JUN-18:10 | 6547.79 | 14-JUN-18:03 | 0.00 | 01-JUN-00:10 |
July | 0.320658E+11 | 0.995950E+10 | 744.00 | 0.243467E+11 | 0.771913E+10 | 0.00 | 0.60 | 26-JUL-18:15 | 0.19 | 05-JUL-06:05 | 19385.20 | 26-JUL-18:15 | 16614.20 | 26-JUL-18:03 | 6611.55 | 20-JUL-21:52 | 6373.13 | 26-JUL-18:03 | 0.00 | 01-JUL-00:10 |
August | 0.286857E+11 | 0.887495E+10 | 744.00 | 0.228129E+11 | 0.587279E+10 | 0.00 | 0.55 | 04-AUG-18:15 | 0.13 | 17-AUG-08:62 | 17209.56 | 07-AUG-18:15 | 16312.22 | 04-AUG-18:15 | 5229.42 | 02-AUG-21:00 | 5934.72 | 04-AUG-18:15 | 0.00 | 01-AUG-00:10 |
September | 0.255983E+11 | 0.772803E+10 | 720.00 | 0.199287E+11 | 0.566960E+10 | 0.00 | 0.49 | 01-SEP-18:03 | 0.05 | 25-SEP-06:05 | 15721.15 | 01-SEP-18:15 | 14441.03 | 20-SEP-15:10 | 4562.80 | 03-SEP-21:52 | 5049.70 | 01-SEP-18:03 | 0.00 | 01-SEP-00:10 |
October | 0.193837E+11 | 0.573738E+10 | 744.00 | 0.152038E+11 | 0.417991E+10 | 0.00 | 0.47 | 04-OCT-15:13 | 0.00 | 25-OCT-06:05 | 15356.87 | 04-OCT-18:15 | 13385.90 | 05-OCT-15:10 | 4514.18 | 03-OCT-21:52 | 4959.54 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.991592E+10 | 0.293544E+10 | 634.60 | 0.770715E+10 | 0.220877E+10 | 0.00 | 0.34 | 03-NOV-15:10 | 0.00 | 02-NOV-08:62 | 10867.16 | 03-NOV-15:10 | 9286.23 | 03-NOV-15:10 | 3720.69 | 30-NOV-12:20 | 3141.81 | 03-NOV-15:10 | 0.00 | 01-NOV-00:10 |
December | 0.514966E+10 | 0.153560E+10 | 510.58 | 0.328912E+10 | 0.186054E+10 | 0.00 | 0.22 | 10-DEC-12:30 | 0.00 | 01-DEC-06:00 | 7097.95 | 10-DEC-12:30 | 5457.53 | 16-DEC-14:20 | 3031.40 | 04-DEC-13:40 | 2086.76 | 10-DEC-12:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.209549E+12 | 0.640801E+11 | 8121.35 | 0.168826E+12 | 0.407229E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.514966E+10 | 0.153560E+10 | 510.58 | 0.328912E+10 | 0.171364E+10 | 0.00 | 0.22 | 0.00 | 7097.95 | 5457.53 | 2278.87 | 2086.76 | 0.00 | |||||||
Maximum of Months | 0.320658E+11 | 0.995950E+10 | 744.00 | 0.243467E+11 | 0.771913E+10 | 0.00 | 0.62 | 0.19 | 19385.20 | 17974.80 | 6611.55 | 6547.79 | 0.00 |
Report: DXReportMonthly
For: PTAC_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.115869E+10 | 0.343211E+09 | 187.15 | 0.787723E+09 | 0.370970E+09 | 0.00 | 0.30 | 12-JAN-13:50 | 0.00 | 01-JAN-00:05 | 5727.14 | 12-JAN-13:30 | 4790.44 | 12-JAN-14:30 | 2112.00 | 12-JAN-11:25 | 1664.43 | 12-JAN-13:30 | 0.00 | 01-JAN-00:05 |
February | 0.228111E+10 | 0.674032E+09 | 296.10 | 0.181653E+10 | 0.464585E+09 | 0.00 | 0.36 | 22-FEB-13:40 | 0.00 | 01-FEB-00:10 | 6678.60 | 22-FEB-13:30 | 6301.24 | 22-FEB-13:50 | 2674.24 | 28-FEB-11:25 | 1926.39 | 22-FEB-13:30 | 0.00 | 01-FEB-00:10 |
March | 0.399753E+10 | 0.118209E+10 | 444.58 | 0.341464E+10 | 0.582888E+09 | 0.00 | 0.37 | 14-MAR-15:10 | 0.00 | 01-MAR-00:10 | 6746.98 | 14-MAR-15:10 | 6746.98 | 14-MAR-15:10 | 1946.52 | 25-MAR-11:40 | 1946.24 | 14-MAR-15:10 | 0.00 | 01-MAR-00:10 |
April | 0.867248E+10 | 0.261542E+10 | 642.31 | 0.802773E+10 | 0.644754E+09 | 0.00 | 0.53 | 30-APR-14:10 | 0.00 | 01-APR-00:10 | 9415.01 | 30-APR-13:00 | 9415.01 | 30-APR-13:00 | 1817.68 | 18-APR-10:25 | 2957.35 | 30-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.128315E+11 | 0.397900E+10 | 740.00 | 0.118750E+11 | 0.956502E+09 | 0.00 | 0.60 | 30-MAY-14:10 | 0.00 | 02-MAY-04:50 | 10322.25 | 30-MAY-14:10 | 10322.25 | 30-MAY-14:10 | 1694.04 | 25-MAY-09:40 | 3572.79 | 30-MAY-14:10 | 0.00 | 01-MAY-00:10 |
June | 0.168507E+11 | 0.546941E+10 | 720.00 | 0.157031E+11 | 0.114762E+10 | 0.00 | 0.69 | 02-JUN-13:40 | 0.08 | 11-JUN-05:00 | 11384.16 | 02-JUN-13:40 | 11384.16 | 02-JUN-13:40 | 1372.27 | 04-JUN-08:32 | 4190.95 | 02-JUN-13:40 | 0.00 | 01-JUN-00:10 |
July | 0.187326E+11 | 0.592806E+10 | 744.00 | 0.160337E+11 | 0.269894E+10 | 0.00 | 0.70 | 03-JUL-12:50 | 0.12 | 05-JUL-05:13 | 12162.75 | 03-JUL-12:50 | 12144.54 | 03-JUL-12:50 | 2100.04 | 21-JUL-08:00 | 4339.50 | 03-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 0.168605E+11 | 0.528837E+10 | 744.00 | 0.147828E+11 | 0.207768E+10 | 0.00 | 0.66 | 04-AUG-15:20 | 0.10 | 17-AUG-06:10 | 12191.01 | 03-AUG-12:50 | 11528.84 | 08-AUG-13:40 | 1827.42 | 02-AUG-08:52 | 4124.38 | 04-AUG-15:20 | 0.00 | 01-AUG-00:10 |
September | 0.142510E+11 | 0.435074E+10 | 710.83 | 0.123043E+11 | 0.194669E+10 | 0.00 | 0.66 | 15-SEP-12:50 | 0.00 | 25-SEP-02:40 | 12119.13 | 02-SEP-13:10 | 11314.94 | 15-SEP-13:00 | 2107.05 | 25-SEP-10:25 | 3921.11 | 15-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 0.925484E+10 | 0.274627E+10 | 674.65 | 0.788846E+10 | 0.136638E+10 | 0.00 | 0.62 | 03-OCT-13:40 | 0.00 | 07-OCT-02:40 | 11266.96 | 03-OCT-13:40 | 10648.98 | 03-OCT-13:40 | 2504.61 | 08-OCT-10:25 | 3680.11 | 03-OCT-13:50 | 0.00 | 01-OCT-00:10 |
November | 0.343197E+10 | 0.100986E+10 | 369.75 | 0.281720E+10 | 0.614764E+09 | 0.00 | 0.39 | 03-NOV-13:30 | 0.00 | 01-NOV-03:10 | 7407.95 | 03-NOV-13:10 | 6678.14 | 03-NOV-14:10 | 2921.99 | 02-NOV-12:10 | 2125.36 | 03-NOV-13:10 | 0.00 | 01-NOV-00:10 |
December | 0.621115E+09 | 0.184147E+09 | 116.49 | 0.390890E+09 | 0.230225E+09 | 0.00 | 0.22 | 16-DEC-12:50 | 0.00 | 01-DEC-00:10 | 4157.98 | 16-DEC-12:50 | 3223.87 | 16-DEC-14:00 | 1784.68 | 09-DEC-12:00 | 1221.72 | 16-DEC-12:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.108944E+12 | 0.337706E+11 | 6389.87 | 0.958419E+11 | 0.131020E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.621115E+09 | 0.184147E+09 | 116.49 | 0.390890E+09 | 0.230225E+09 | 0.00 | 0.22 | 0.00 | 4157.98 | 3223.87 | 1372.27 | 1221.72 | 0.00 | |||||||
Maximum of Months | 0.187326E+11 | 0.592806E+10 | 744.00 | 0.160337E+11 | 0.269894E+10 | 0.00 | 0.70 | 0.12 | 12191.01 | 12144.54 | 2921.99 | 4339.50 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_1 COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.167103E+10 | 0.533254E+09 | 61.83 | 0.165772E+10 | 13312374.86 | 0.00 | 0.47 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 23153.03 | 03-JAN-15:00 | 23153.03 | 03-JAN-15:00 | 595.88 | 01-JAN-15:00 | 7004.27 | 03-JAN-15:00 | 0.00 |
February | 0.825143E+10 | 0.253510E+10 | 159.67 | 0.822754E+10 | 23886722.97 | 0.00 | 0.66 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 34224.30 | 20-FEB-15:00 | 34224.30 | 20-FEB-15:00 | 1419.26 | 27-FEB-16:30 | 9847.79 | 20-FEB-15:00 | 0.00 |
March | 0.166713E+11 | 0.505305E+10 | 276.17 | 0.166657E+11 | 5559276.06 | 0.00 | 0.81 | 14-MAR-18:03 | 0.00 | 01-MAR-00:10 | 44048.47 | 14-MAR-18:03 | 44048.47 | 14-MAR-18:03 | 927.79 | 11-MAR-16:00 | 12148.04 | 14-MAR-18:03 | 0.00 |
April | 0.595787E+11 | 0.168308E+11 | 547.00 | 0.592229E+11 | 0.355852E+09 | 0.00 | 1.00 | 01-APR-17:03 | 0.00 | 01-APR-00:10 | 75722.52 | 19-APR-18:30 | 75722.52 | 19-APR-18:30 | 5563.96 | 17-APR-02:00 | 20036.53 | 19-APR-18:15 | 0.00 |
May | 0.105134E+12 | 0.291099E+11 | 712.67 | 0.102267E+12 | 0.286715E+10 | 0.00 | 1.00 | 06-MAY-17:07 | 0.00 | 01-MAY-05:00 | 86159.60 | 19-MAY-18:15 | 86159.60 | 19-MAY-18:15 | 15589.66 | 27-MAY-24:00 | 24251.12 | 19-MAY-18:15 | 0.00 |
June | 0.144144E+12 | 0.403094E+11 | 720.00 | 0.139307E+12 | 0.483689E+10 | 0.00 | 1.00 | 01-JUN-11:20 | 0.05 | 13-JUN-05:00 | 100379.67 | 14-JUN-18:17 | 100379.67 | 14-JUN-18:17 | 24925.22 | 27-JUN-24:00 | 30866.78 | 14-JUN-18:03 | 0.00 |
July | 0.179510E+12 | 0.472816E+11 | 744.00 | 0.142771E+12 | 0.367390E+11 | 0.00 | 1.00 | 01-JUL-00:10 | 0.54 | 05-JUL-06:10 | 119229.05 | 18-JUL-21:00 | 95434.20 | 03-JUL-18:03 | 82544.23 | 18-JUL-21:00 | 29641.82 | 18-JUL-21:00 | 0.00 |
August | 0.149832E+12 | 0.404542E+11 | 744.00 | 0.130477E+12 | 0.193547E+11 | 0.00 | 1.00 | 01-AUG-00:10 | 0.32 | 31-AUG-06:00 | 116032.97 | 01-AUG-20:54 | 95323.57 | 04-AUG-18:20 | 65964.82 | 01-AUG-20:54 | 28887.60 | 01-AUG-20:54 | 0.00 |
September | 0.118857E+12 | 0.320013E+11 | 692.33 | 0.994103E+11 | 0.194463E+11 | 0.00 | 1.00 | 01-SEP-10:50 | 0.00 | 12-SEP-05:30 | 85874.97 | 22-SEP-20:10 | 82558.66 | 19-SEP-18:03 | 50414.28 | 22-SEP-02:00 | 22455.13 | 19-SEP-18:03 | 0.00 |
October | 0.588717E+11 | 0.165943E+11 | 532.33 | 0.523412E+11 | 0.653057E+10 | 0.00 | 1.00 | 01-OCT-11:20 | 0.00 | 01-OCT-02:50 | 97133.93 | 03-OCT-19:53 | 72641.27 | 04-OCT-18:15 | 41045.81 | 03-OCT-20:03 | 24488.40 | 03-OCT-19:53 | 0.00 |
November | 0.107501E+11 | 0.329731E+10 | 211.00 | 0.105257E+11 | 0.224402E+09 | 0.00 | 0.79 | 03-NOV-15:13 | 0.00 | 01-NOV-00:10 | 42533.11 | 03-NOV-15:13 | 42533.11 | 03-NOV-15:13 | 4997.14 | 02-NOV-16:52 | 11805.78 | 03-NOV-15:13 | 0.00 |
December | 0.996999E+09 | 0.324070E+09 | 51.50 | 0.996603E+09 | 396212.25 | 0.00 | 0.30 | 23-DEC-15:00 | 0.00 | 01-DEC-00:10 | 14375.10 | 23-DEC-15:00 | 14375.10 | 23-DEC-15:00 | 138.22 | 25-DEC-15:00 | 4533.36 | 23-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.854268E+12 | 0.234324E+12 | 5452.50 | 0.763870E+12 | 0.903981E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.996999E+09 | 0.324070E+09 | 51.50 | 0.996603E+09 | 396212.25 | 0.00 | 0.30 | 0.00 | 14375.10 | 14375.10 | 138.22 | 4533.36 | 0.00 | ||||||
Maximum of Months | 0.179510E+12 | 0.472816E+11 | 744.00 | 0.142771E+12 | 0.367390E+11 | 0.00 | 1.00 | 0.54 | 119229.05 | 100379.67 | 82544.23 | 30866.78 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_6 COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.156399E+10 | 0.497510E+09 | 63.33 | 0.155506E+10 | 8930545.12 | 0.00 | 0.49 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 20663.44 | 03-JAN-15:00 | 20663.44 | 03-JAN-15:00 | 469.43 | 01-JAN-14:50 | 6215.55 | 03-JAN-15:00 | 0.00 |
February | 0.763544E+10 | 0.233324E+10 | 161.42 | 0.761989E+10 | 15555542.06 | 0.00 | 0.70 | 22-FEB-16:10 | 0.00 | 01-FEB-00:10 | 30973.48 | 22-FEB-16:10 | 30973.48 | 22-FEB-16:10 | 1186.24 | 27-FEB-16:30 | 8821.70 | 22-FEB-16:10 | 0.00 |
March | 0.161106E+11 | 0.482270E+10 | 282.61 | 0.161060E+11 | 4597516.22 | 0.00 | 0.88 | 14-MAR-16:00 | 0.00 | 01-MAR-00:10 | 41072.48 | 14-MAR-16:00 | 41072.48 | 14-MAR-16:00 | 798.15 | 11-MAR-16:00 | 11119.26 | 14-MAR-16:00 | 0.00 |
April | 0.590397E+11 | 0.163660E+11 | 551.33 | 0.588351E+11 | 0.204622E+09 | 0.00 | 1.00 | 01-APR-16:10 | 0.00 | 01-APR-00:10 | 68933.15 | 19-APR-21:10 | 68933.15 | 19-APR-21:10 | 4616.73 | 17-APR-02:00 | 18058.35 | 21-APR-15:10 | 0.00 |
May | 0.104467E+12 | 0.284947E+11 | 716.67 | 0.102447E+12 | 0.202054E+10 | 0.00 | 1.00 | 02-MAY-18:02 | 0.00 | 01-MAY-05:20 | 79945.93 | 19-MAY-18:03 | 79945.93 | 19-MAY-18:03 | 13227.05 | 27-MAY-24:00 | 22696.42 | 19-MAY-16:00 | 0.00 |
June | 0.142959E+12 | 0.396100E+11 | 720.00 | 0.139393E+12 | 0.356607E+10 | 0.00 | 1.00 | 01-JUN-00:10 | 0.08 | 13-JUN-05:00 | 93638.95 | 14-JUN-18:03 | 93638.95 | 14-JUN-18:03 | 25073.27 | 19-JUN-18:10 | 29015.85 | 02-JUN-16:00 | 0.00 |
July | 0.179197E+12 | 0.469067E+11 | 744.00 | 0.142203E+12 | 0.369940E+11 | 0.00 | 1.00 | 01-JUL-00:10 | 0.59 | 05-JUL-06:05 | 110272.33 | 21-JUL-18:10 | 91436.38 | 01-JUL-17:10 | 75219.21 | 18-JUL-21:10 | 28148.82 | 01-JUL-17:05 | 0.00 |
August | 0.145332E+12 | 0.388754E+11 | 744.00 | 0.127782E+12 | 0.175504E+11 | 0.00 | 1.00 | 01-AUG-00:10 | 0.37 | 30-AUG-06:20 | 111179.26 | 01-AUG-21:52 | 88269.15 | 04-AUG-18:03 | 61691.98 | 01-AUG-21:02 | 27601.89 | 01-AUG-21:52 | 0.00 |
September | 0.111835E+12 | 0.298382E+11 | 693.50 | 0.938718E+11 | 0.179632E+11 | 0.00 | 1.00 | 01-SEP-08:00 | 0.00 | 12-SEP-05:30 | 80027.66 | 01-SEP-21:10 | 73674.96 | 19-SEP-16:00 | 50263.52 | 22-SEP-02:00 | 21169.13 | 19-SEP-16:00 | 0.00 |
October | 0.530595E+11 | 0.148785E+11 | 537.50 | 0.473480E+11 | 0.571153E+10 | 0.00 | 1.00 | 01-OCT-11:10 | 0.00 | 01-OCT-03:00 | 83704.30 | 03-OCT-20:03 | 67246.86 | 01-OCT-23:00 | 36545.39 | 03-OCT-21:52 | 21153.87 | 03-OCT-20:03 | 0.00 |
November | 0.963134E+10 | 0.295036E+10 | 213.57 | 0.945621E+10 | 0.175129E+09 | 0.00 | 0.81 | 03-NOV-15:13 | 0.00 | 01-NOV-00:10 | 37389.27 | 03-NOV-15:13 | 37389.27 | 03-NOV-15:13 | 4162.82 | 02-NOV-15:00 | 10308.14 | 03-NOV-15:13 | 0.00 |
December | 0.966478E+09 | 0.313204E+09 | 54.17 | 0.966235E+09 | 242478.47 | 0.00 | 0.32 | 10-DEC-15:00 | 0.00 | 01-DEC-00:10 | 12995.63 | 10-DEC-15:00 | 12995.63 | 10-DEC-15:00 | 90.57 | 25-DEC-15:00 | 4079.35 | 10-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.831798E+12 | 0.225886E+12 | 5482.10 | 0.747583E+12 | 0.842148E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.966478E+09 | 0.313204E+09 | 54.17 | 0.966235E+09 | 242478.47 | 0.00 | 0.32 | 0.00 | 12995.63 | 12995.63 | 90.57 | 4079.35 | 0.00 | ||||||
Maximum of Months | 0.179197E+12 | 0.469067E+11 | 744.00 | 0.142203E+12 | 0.369940E+11 | 0.00 | 1.00 | 0.59 | 111179.26 | 93638.95 | 75219.21 | 29015.85 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_0 COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.458228E+09 | 0.142552E+09 | 60.05 | 0.426533E+09 | 31694941.83 | 0.00 | 0.45 | 03-JAN-19:03 | 0.00 | 01-JAN-00:05 | 10510.21 | 03-JAN-19:03 | 10510.21 | 03-JAN-19:03 | 978.28 | 12-JAN-21:00 | 3049.24 | 03-JAN-19:03 | 0.00 | 01-JAN-00:05 |
February | 0.132848E+10 | 0.409599E+09 | 89.85 | 0.132139E+10 | 7083565.37 | 0.00 | 0.51 | 06-FEB-22:00 | 0.00 | 01-FEB-00:10 | 12254.08 | 06-FEB-22:00 | 12254.08 | 06-FEB-22:00 | 622.33 | 07-FEB-23:00 | 3490.58 | 06-FEB-22:00 | 0.00 | 01-FEB-00:10 |
March | 0.231786E+10 | 0.711940E+09 | 141.78 | 0.231743E+10 | 431414.19 | 0.00 | 0.61 | 14-MAR-18:10 | 0.00 | 01-MAR-00:10 | 14955.70 | 14-MAR-18:10 | 14955.70 | 14-MAR-18:10 | 71.53 | 12-MAR-19:40 | 4277.99 | 14-MAR-18:10 | 0.00 | 01-MAR-00:10 |
April | 0.168974E+11 | 0.509266E+10 | 434.31 | 0.166480E+11 | 0.249412E+09 | 0.00 | 0.97 | 19-APR-19:20 | 0.00 | 01-APR-00:10 | 26326.56 | 19-APR-19:20 | 26326.56 | 19-APR-19:20 | 4247.31 | 18-APR-21:00 | 7645.94 | 19-APR-19:10 | 0.00 | 01-APR-00:10 |
May | 0.347015E+11 | 0.104207E+11 | 656.58 | 0.327104E+11 | 0.199106E+10 | 0.00 | 1.00 | 15-MAY-19:10 | 0.00 | 01-MAY-02:70 | 32093.96 | 24-MAY-20:02 | 30613.37 | 19-MAY-19:20 | 11260.29 | 24-MAY-21:51 | 9246.04 | 19-MAY-19:20 | 0.00 | 01-MAY-00:10 |
June | 0.515713E+11 | 0.157702E+11 | 717.67 | 0.472541E+11 | 0.431716E+10 | 0.00 | 1.00 | 01-JUN-17:05 | 0.00 | 12-JUN-03:00 | 36116.75 | 05-JUN-19:20 | 36116.75 | 05-JUN-19:20 | 12669.88 | 23-JUN-19:53 | 12142.18 | 14-JUN-18:17 | 0.00 | 01-JUN-00:10 |
July | 0.789102E+11 | 0.217684E+11 | 744.00 | 0.563317E+11 | 0.225785E+11 | 0.00 | 1.00 | 01-JUL-17:05 | 0.43 | 05-JUL-04:00 | 68383.96 | 18-JUL-20:12 | 37877.17 | 25-JUL-19:20 | 47826.62 | 20-JUL-21:52 | 16150.61 | 18-JUL-20:12 | 0.00 | 01-JUL-00:10 |
August | 0.730309E+11 | 0.202507E+11 | 744.00 | 0.570498E+11 | 0.159811E+11 | 0.00 | 1.00 | 01-AUG-17:03 | 0.40 | 30-AUG-03:00 | 66620.17 | 01-AUG-20:50 | 40509.93 | 04-AUG-19:20 | 36031.93 | 01-AUG-20:52 | 15878.41 | 01-AUG-20:50 | 0.00 | 01-AUG-00:10 |
September | 0.656459E+11 | 0.176349E+11 | 702.67 | 0.484643E+11 | 0.171817E+11 | 0.00 | 1.00 | 01-SEP-06:35 | 0.00 | 24-SEP-04:50 | 53581.40 | 09-SEP-20:10 | 36604.59 | 12-SEP-19:20 | 28842.87 | 03-SEP-21:00 | 12972.30 | 09-SEP-20:10 | 0.00 | 01-SEP-00:10 |
October | 0.355059E+11 | 0.970698E+10 | 596.83 | 0.279053E+11 | 0.760051E+10 | 0.00 | 1.00 | 01-OCT-17:20 | 0.00 | 06-OCT-03:40 | 62185.71 | 03-OCT-19:53 | 36066.31 | 04-OCT-19:20 | 28499.38 | 03-OCT-19:53 | 14992.56 | 03-OCT-19:53 | 0.00 | 01-OCT-00:10 |
November | 0.747556E+10 | 0.219149E+10 | 313.53 | 0.681879E+10 | 0.656770E+09 | 0.00 | 0.91 | 09-NOV-21:00 | 0.00 | 01-NOV-00:10 | 24714.56 | 09-NOV-21:00 | 22605.25 | 09-NOV-21:00 | 8007.17 | 02-NOV-20:00 | 6231.01 | 09-NOV-21:00 | 0.00 | 01-NOV-00:10 |
December | 0.890335E+09 | 0.278323E+09 | 103.83 | 0.817787E+09 | 72548316.46 | 0.00 | 0.42 | 15-DEC-20:20 | 0.00 | 01-DEC-00:10 | 9780.72 | 15-DEC-20:20 | 9780.72 | 15-DEC-20:20 | 1415.50 | 14-DEC-21:00 | 2859.74 | 15-DEC-20:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.368733E+12 | 0.104378E+12 | 5305.09 | 0.298066E+12 | 0.706679E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.458228E+09 | 0.142552E+09 | 60.05 | 0.426533E+09 | 431414.19 | 0.00 | 0.42 | 0.00 | 9780.72 | 9780.72 | 71.53 | 2859.74 | 0.00 | |||||||
Maximum of Months | 0.789102E+11 | 0.217684E+11 | 744.00 | 0.570498E+11 | 0.225785E+11 | 0.00 | 1.00 | 0.43 | 68383.96 | 40509.93 | 47826.62 | 16150.61 | 0.00 |
Report: DXReportMonthly
For: PSZ_LAUNDRY COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.131327E+09 | 36010301.69 | 99.80 | 0.131323E+09 | 4658.97 | 0.00 | 0.37 | 03-JAN-19:03 | 0.00 | 01-JAN-00:05 | 11535.33 | 03-JAN-19:03 | 11535.33 | 03-JAN-19:03 | 2.38 | 03-JAN-20:45 | 3035.71 | 03-JAN-19:03 | 0.00 | 01-JAN-00:05 |
February | 0.238915E+10 | 0.635762E+09 | 161.08 | 0.238888E+10 | 278605.59 | 0.00 | 0.60 | 06-FEB-22:00 | 0.00 | 01-FEB-00:10 | 19861.56 | 06-FEB-22:00 | 19861.56 | 06-FEB-22:00 | 66.06 | 07-FEB-21:30 | 4900.51 | 06-FEB-22:00 | 0.00 | 01-FEB-00:10 |
March | 0.686628E+10 | 0.176627E+10 | 228.35 | 0.686627E+10 | 6397.43 | 0.00 | 0.98 | 14-MAR-18:08 | 0.00 | 01-MAR-00:10 | 36501.12 | 14-MAR-18:08 | 36501.12 | 14-MAR-18:08 | 5.71 | 10-MAR-18:03 | 8260.33 | 14-MAR-18:08 | 0.00 | 01-MAR-00:10 |
April | 0.308719E+11 | 0.786367E+10 | 428.30 | 0.306771E+11 | 0.194829E+09 | 0.00 | 1.00 | 01-APR-18:02 | 0.00 | 01-APR-00:10 | 46448.02 | 28-APR-20:00 | 46224.16 | 19-APR-20:00 | 5416.11 | 18-APR-21:00 | 11942.26 | 19-APR-19:20 | 0.00 | 01-APR-00:10 |
May | 0.524480E+11 | 0.136948E+11 | 618.12 | 0.509559E+11 | 0.149206E+10 | 0.00 | 1.00 | 02-MAY-18:02 | 0.00 | 01-MAY-01:10 | 57886.56 | 24-MAY-20:02 | 46478.27 | 19-MAY-20:00 | 17507.51 | 28-MAY-19:10 | 13572.93 | 24-MAY-20:02 | 0.00 | 01-MAY-00:10 |
June | 0.655122E+11 | 0.179823E+11 | 695.25 | 0.630287E+11 | 0.248345E+10 | 0.00 | 1.00 | 01-JUN-17:05 | 0.00 | 01-JUN-05:00 | 60948.02 | 23-JUN-19:53 | 46768.13 | 15-JUN-20:00 | 20605.53 | 23-JUN-19:53 | 14295.69 | 14-JUN-19:10 | 0.00 | 01-JUN-00:10 |
July | 0.778585E+11 | 0.204395E+11 | 738.17 | 0.670442E+11 | 0.108143E+11 | 0.00 | 1.00 | 01-JUL-17:20 | 0.00 | 05-JUL-00:40 | 81105.63 | 20-JUL-21:51 | 46697.48 | 25-JUL-20:00 | 57682.51 | 20-JUL-21:51 | 18484.41 | 18-JUL-20:12 | 0.00 | 01-JUL-00:10 |
August | 0.687321E+11 | 0.180595E+11 | 713.92 | 0.613504E+11 | 0.738161E+10 | 0.00 | 1.00 | 01-AUG-06:45 | 0.00 | 13-AUG-23:50 | 79489.06 | 01-AUG-20:45 | 46708.94 | 04-AUG-20:00 | 45263.14 | 01-AUG-20:52 | 18396.85 | 01-AUG-20:45 | 0.00 | 01-AUG-00:10 |
September | 0.536733E+11 | 0.137038E+11 | 589.46 | 0.469235E+11 | 0.674976E+10 | 0.00 | 1.00 | 01-SEP-07:50 | 0.00 | 01-SEP-04:50 | 67663.93 | 09-SEP-20:00 | 46294.32 | 01-SEP-20:00 | 31517.39 | 03-SEP-19:35 | 15682.50 | 03-SEP-19:02 | 0.00 | 01-SEP-00:10 |
October | 0.274272E+11 | 0.691832E+10 | 408.99 | 0.244344E+11 | 0.299282E+10 | 0.00 | 1.00 | 01-OCT-18:02 | 0.00 | 01-OCT-00:10 | 78080.65 | 03-OCT-19:53 | 46098.81 | 04-OCT-20:00 | 35696.17 | 03-OCT-19:53 | 18248.68 | 03-OCT-19:53 | 0.00 | 01-OCT-00:10 |
November | 0.249760E+10 | 0.646961E+09 | 148.51 | 0.244774E+10 | 49860080.49 | 0.00 | 0.77 | 09-NOV-21:00 | 0.00 | 01-NOV-00:10 | 27064.04 | 09-NOV-21:00 | 26713.40 | 08-NOV-19:02 | 2621.94 | 02-NOV-18:08 | 6335.40 | 09-NOV-21:00 | 0.00 | 01-NOV-00:10 |
December | 2511892.48 | 722215.75 | 76.41 | 2511802.19 | 90.30 | 0.00 | 0.05 | 15-DEC-20:10 | 0.00 | 01-DEC-01:10 | 1309.90 | 15-DEC-20:10 | 1309.90 | 15-DEC-20:10 | 0.14 | 14-DEC-18:05 | 375.43 | 15-DEC-20:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.388410E+12 | 0.101748E+12 | 4906.36 | 0.356251E+12 | 0.321590E+11 | 0.00 | ||||||||||||||
Minimum of Months | 2511892.48 | 722215.75 | 76.41 | 2511802.19 | 90.30 | 0.00 | 0.05 | 0.00 | 1309.90 | 1309.90 | 0.14 | 375.43 | 0.00 | |||||||
Maximum of Months | 0.778585E+11 | 0.204395E+11 | 738.17 | 0.670442E+11 | 0.108143E+11 | 0.00 | 1.00 | 0.00 | 81105.63 | 46768.13 | 57682.51 | 18484.41 | 0.00 |
Report: DXReportMonthly
For: PSZ_CAFE COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.109924E+09 | 31010927.50 | 9.83 | 0.108390E+09 | 1534075.44 | 0.00 | 0.31 | 03-JAN-14:20 | 0.00 | 01-JAN-00:05 | 5780.80 | 03-JAN-14:20 | 5780.80 | 03-JAN-14:20 | 155.57 | 12-JAN-14:00 | 1592.83 | 03-JAN-14:20 | 0.00 | 01-JAN-00:05 |
February | 0.143714E+10 | 0.389465E+09 | 69.33 | 0.143712E+10 | 13341.95 | 0.00 | 0.65 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 13365.07 | 20-FEB-15:00 | 13365.07 | 20-FEB-15:00 | 12.26 | 27-FEB-23:00 | 3477.20 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.283455E+10 | 0.772724E+09 | 135.36 | 0.283455E+10 | 2689.81 | 0.00 | 0.76 | 14-MAR-15:10 | 0.00 | 01-MAR-00:10 | 15952.19 | 14-MAR-15:10 | 15952.19 | 14-MAR-15:10 | 1.80 | 11-MAR-12:40 | 4074.76 | 14-MAR-15:10 | 0.00 | 01-MAR-00:10 |
April | 0.143480E+11 | 0.392848E+10 | 371.08 | 0.142290E+11 | 0.119089E+09 | 0.00 | 0.94 | 21-APR-15:10 | 0.00 | 01-APR-00:10 | 20673.68 | 21-APR-15:10 | 20673.68 | 21-APR-15:10 | 2188.95 | 18-APR-18:50 | 5904.77 | 21-APR-15:10 | 0.00 | 01-APR-00:10 |
May | 0.271340E+11 | 0.750545E+10 | 581.17 | 0.259399E+11 | 0.119411E+10 | 0.00 | 1.00 | 19-MAY-16:00 | 0.00 | 01-MAY-01:30 | 22743.96 | 30-MAY-15:10 | 22743.96 | 30-MAY-15:10 | 5762.86 | 27-MAY-20:52 | 6653.77 | 19-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.409995E+11 | 0.115640E+11 | 687.50 | 0.379102E+11 | 0.308929E+10 | 0.00 | 1.00 | 01-JUN-13:40 | 0.00 | 01-JUN-05:13 | 26011.08 | 02-JUN-16:00 | 26011.08 | 02-JUN-16:00 | 8034.76 | 19-JUN-18:20 | 8825.98 | 02-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.536560E+11 | 0.140697E+11 | 740.50 | 0.392500E+11 | 0.144061E+11 | 0.00 | 1.00 | 01-JUL-11:30 | 0.00 | 05-JUL-03:00 | 31046.88 | 18-JUL-20:12 | 25960.44 | 01-JUL-17:05 | 17910.23 | 18-JUL-20:12 | 8321.59 | 26-JUL-15:10 | 0.00 | 01-JUL-00:10 |
August | 0.434693E+11 | 0.115832E+11 | 693.50 | 0.351405E+11 | 0.832871E+10 | 0.00 | 1.00 | 01-AUG-15:10 | 0.00 | 12-AUG-05:23 | 27515.33 | 02-AUG-21:10 | 25376.25 | 07-AUG-16:00 | 14194.05 | 01-AUG-21:51 | 7884.10 | 07-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 0.324818E+11 | 0.853322E+10 | 561.33 | 0.261315E+11 | 0.635033E+10 | 0.00 | 1.00 | 01-SEP-12:20 | 0.00 | 02-SEP-05:00 | 27491.69 | 09-SEP-12:30 | 25085.66 | 19-SEP-14:10 | 10496.81 | 22-SEP-24:00 | 7320.05 | 19-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 0.151974E+11 | 0.396274E+10 | 342.46 | 0.130692E+11 | 0.212820E+10 | 0.00 | 1.00 | 01-OCT-12:00 | 0.00 | 01-OCT-00:10 | 27659.55 | 04-OCT-15:20 | 23852.07 | 03-OCT-13:40 | 10832.59 | 03-OCT-20:03 | 7627.86 | 03-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.189386E+10 | 0.509527E+09 | 91.67 | 0.184816E+10 | 45702174.53 | 0.00 | 0.77 | 03-NOV-15:10 | 0.00 | 01-NOV-00:10 | 16663.95 | 03-NOV-15:10 | 16029.91 | 03-NOV-15:10 | 2074.22 | 03-NOV-12:30 | 4193.31 | 03-NOV-15:10 | 0.00 | 01-NOV-00:10 |
December | 929370.12 | 275595.72 | 1.00 | 929370.12 | -0.0 | 0.00 | 0.03 | 09-DEC-13:00 | 0.00 | 01-DEC-00:10 | 566.75 | 09-DEC-13:00 | 566.75 | 09-DEC-13:00 | 0.00 | 09-DEC-13:10 | 167.78 | 09-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.233563E+12 | 0.628498E+11 | 4284.74 | 0.197900E+12 | 0.356630E+11 | 0.00 | ||||||||||||||
Minimum of Months | 929370.12 | 275595.72 | 1.00 | 929370.12 | -0.0 | 0.00 | 0.03 | 0.00 | 566.75 | 566.75 | 0.00 | 167.78 | 0.00 | |||||||
Maximum of Months | 0.536560E+11 | 0.140697E+11 | 740.50 | 0.392500E+11 | 0.144061E+11 | 0.00 | 1.00 | 0.00 | 31046.88 | 26011.08 | 17910.23 | 8825.98 | 0.00 |
Report: DXReportMonthly
For: PSZ_KITCHEN COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.881057E+09 | 0.239005E+09 | 41.00 | 0.869089E+09 | 11967838.99 | 0.00 | 0.64 | 03-JAN-17:00 | 0.00 | 01-JAN-00:05 | 17881.23 | 03-JAN-17:00 | 17881.23 | 03-JAN-17:00 | 562.22 | 02-JAN-13:00 | 4489.00 | 03-JAN-17:00 | 0.00 | 01-JAN-00:05 |
February | 0.578059E+10 | 0.148782E+10 | 138.50 | 0.576935E+10 | 11236858.29 | 0.00 | 0.86 | 20-FEB-16:12 | 0.00 | 01-FEB-00:10 | 25743.36 | 20-FEB-16:12 | 25743.36 | 20-FEB-16:12 | 751.94 | 27-FEB-16:12 | 6245.65 | 20-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 0.121363E+11 | 0.307063E+10 | 244.14 | 0.120412E+11 | 95085248.54 | 0.00 | 1.00 | 14-MAR-15:40 | 0.00 | 01-MAR-00:10 | 39385.98 | 14-MAR-17:15 | 32248.65 | 14-MAR-17:20 | 7413.29 | 14-MAR-17:10 | 9442.17 | 14-MAR-17:15 | 0.00 | 01-MAR-00:10 |
April | 0.382709E+11 | 0.965983E+10 | 462.17 | 0.352401E+11 | 0.303084E+10 | 0.00 | 1.00 | 01-APR-11:20 | 0.00 | 01-APR-00:10 | 45341.63 | 29-APR-10:40 | 36503.26 | 19-APR-10:50 | 12656.64 | 18-APR-16:40 | 12358.02 | 19-APR-17:20 | 0.00 | 01-APR-00:10 |
May | 0.644385E+11 | 0.166748E+11 | 624.00 | 0.554112E+11 | 0.902726E+10 | 0.00 | 1.00 | 02-MAY-15:18 | 0.00 | 01-MAY-01:10 | 49818.03 | 21-MAY-17:20 | 38188.96 | 21-MAY-10:50 | 14924.80 | 24-MAY-17:20 | 14064.10 | 19-MAY-17:20 | 0.00 | 01-MAY-00:10 |
June | 0.811642E+11 | 0.220986E+11 | 700.83 | 0.682218E+11 | 0.129424E+11 | 0.00 | 1.00 | 01-JUN-08:18 | 0.00 | 11-JUN-02:20 | 50602.59 | 28-JUN-10:50 | 40351.60 | 15-JUN-10:50 | 19738.30 | 28-JUN-10:50 | 15626.22 | 06-JUN-17:20 | 0.00 | 01-JUN-00:10 |
July | 0.100835E+12 | 0.264640E+11 | 742.00 | 0.714906E+11 | 0.293444E+11 | 0.00 | 1.00 | 01-JUL-06:20 | 0.00 | 05-JUL-02:70 | 67944.81 | 21-JUL-08:00 | 40236.75 | 03-JUL-10:50 | 46472.90 | 21-JUL-06:35 | 16271.73 | 03-JUL-17:20 | 0.00 | 01-JUL-00:10 |
August | 0.874195E+11 | 0.228351E+11 | 723.17 | 0.659104E+11 | 0.215091E+11 | 0.00 | 1.00 | 01-AUG-06:15 | 0.00 | 13-AUG-24:00 | 61385.91 | 02-AUG-07:50 | 39266.16 | 06-AUG-10:50 | 31883.04 | 02-AUG-07:50 | 15460.93 | 07-AUG-17:20 | 0.00 | 01-AUG-00:10 |
September | 0.698339E+11 | 0.177507E+11 | 610.83 | 0.519296E+11 | 0.179043E+11 | 0.00 | 1.00 | 01-SEP-06:25 | 0.00 | 03-SEP-04:00 | 54979.67 | 09-SEP-09:20 | 38141.09 | 17-SEP-10:50 | 26581.85 | 22-SEP-08:00 | 14011.20 | 01-SEP-17:20 | 0.00 | 01-SEP-00:10 |
October | 0.371468E+11 | 0.923909E+10 | 438.00 | 0.300842E+11 | 0.706262E+10 | 0.00 | 1.00 | 01-OCT-09:50 | 0.00 | 01-OCT-00:10 | 51558.31 | 03-OCT-17:17 | 36766.49 | 01-OCT-10:50 | 23513.77 | 03-OCT-19:53 | 13416.68 | 04-OCT-17:20 | 0.00 | 01-OCT-00:10 |
November | 0.679439E+10 | 0.175878E+10 | 169.15 | 0.658323E+10 | 0.211162E+09 | 0.00 | 1.00 | 03-NOV-15:55 | 0.00 | 01-NOV-00:10 | 35255.43 | 03-NOV-16:00 | 30731.70 | 03-NOV-15:55 | 5278.15 | 03-NOV-10:50 | 8360.14 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.390999E+09 | 0.110552E+09 | 27.17 | 0.390999E+09 | 195.74 | 0.00 | 0.35 | 09-DEC-13:00 | 0.00 | 01-DEC-00:10 | 9140.58 | 09-DEC-13:00 | 9140.58 | 09-DEC-13:00 | 0.33 | 10-DEC-11:30 | 2487.84 | 09-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.505092E+12 | 0.131389E+12 | 4920.95 | 0.403942E+12 | 0.101150E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.390999E+09 | 0.110552E+09 | 27.17 | 0.390999E+09 | 195.74 | 0.00 | 0.35 | 0.00 | 9140.58 | 9140.58 | 0.33 | 2487.84 | 0.00 | |||||||
Maximum of Months | 0.100835E+12 | 0.264640E+11 | 742.00 | 0.714906E+11 | 0.293444E+11 | 0.00 | 1.00 | 0.00 | 67944.81 | 40351.60 | 46472.90 | 16271.73 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.15 | 535.07 | 171.08 | 912.05 | 598.78 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 471.17 | 193.21 | 876.11 | 534.12 | 0.00 | 0.00 | 0.00 |
March | 519.74 | 294.46 | 225.28 | 700.18 | 469.26 | 0.00 | 0.00 | 0.00 |
April | 362.15 | 135.95 | 226.20 | 561.70 | 280.59 | 0.00 | 0.00 | 0.00 |
May | 257.00 | 37.69 | 219.31 | 454.36 | 157.69 | 0.00 | 0.00 | 0.00 |
June | 219.82 | 13.83 | 205.99 | 496.39 | 72.86 | 0.00 | 0.00 | 0.00 |
July | 223.23 | 19.79 | 203.44 | 504.93 | 55.17 | 0.00 | 0.00 | 0.00 |
August | 281.79 | 71.59 | 210.20 | 589.28 | 84.29 | 0.00 | 0.00 | 0.00 |
September | 446.25 | 231.85 | 214.40 | 838.01 | 177.50 | 0.00 | 0.00 | 0.00 |
October | 612.55 | 416.17 | 196.38 | 964.15 | 297.59 | 0.00 | 0.00 | 0.00 |
November | 737.24 | 563.91 | 173.33 | 1008.14 | 503.44 | 0.00 | 0.00 | 0.00 |
December | 724.95 | 544.65 | 180.31 | 914.12 | 641.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 478.50 | 276.88 | 201.63 | 733.89 | 321.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.82 | 13.83 | 171.08 | 454.36 | 55.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 737.24 | 563.91 | 226.20 | 1008.14 | 641.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1988.48 | 1506.73 | 481.75 | 2543.98 | 1753.28 | 0.00 | 0.00 | 0.00 |
February | 1870.85 | 1326.79 | 544.06 | 2432.71 | 1593.37 | 0.00 | 0.00 | 0.00 |
March | 1463.55 | 829.18 | 634.37 | 1922.60 | 1410.89 | 0.00 | 0.00 | 0.00 |
April | 1019.80 | 382.82 | 636.98 | 1532.17 | 868.10 | 0.00 | 0.00 | 0.00 |
May | 723.68 | 106.13 | 617.55 | 1238.33 | 493.88 | 0.00 | 0.00 | 0.00 |
June | 618.99 | 38.95 | 580.04 | 1371.03 | 226.90 | 0.00 | 0.00 | 0.00 |
July | 628.60 | 55.73 | 572.87 | 1396.52 | 174.15 | 0.00 | 0.00 | 0.00 |
August | 793.51 | 201.60 | 591.90 | 1631.10 | 264.88 | 0.00 | 0.00 | 0.00 |
September | 1256.61 | 652.87 | 603.74 | 2325.90 | 542.00 | 0.00 | 0.00 | 0.00 |
October | 1724.89 | 1171.91 | 552.99 | 2666.27 | 921.31 | 0.00 | 0.00 | 0.00 |
November | 2076.02 | 1587.93 | 488.09 | 2803.33 | 1494.04 | 0.00 | 0.00 | 0.00 |
December | 2041.42 | 1533.69 | 507.73 | 2549.52 | 1862.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1347.44 | 779.68 | 567.76 | 2031.47 | 964.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 618.99 | 38.95 | 481.75 | 1238.33 | 174.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2076.02 | 1587.93 | 636.98 | 2803.33 | 1862.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2583.15 | 1957.32 | 625.82 | 3366.74 | 2462.30 | 0.00 | 0.00 | 0.00 |
February | 2430.34 | 1723.58 | 706.76 | 3231.24 | 2200.21 | 0.00 | 0.00 | 0.00 |
March | 1901.24 | 1077.15 | 824.09 | 2583.70 | 1936.95 | 0.00 | 0.00 | 0.00 |
April | 1324.78 | 497.31 | 827.47 | 2090.13 | 1162.30 | 0.00 | 0.00 | 0.00 |
May | 940.11 | 137.87 | 802.24 | 1707.67 | 651.91 | 0.00 | 0.00 | 0.00 |
June | 804.10 | 50.59 | 753.51 | 1887.41 | 296.02 | 0.00 | 0.00 | 0.00 |
July | 816.59 | 72.40 | 744.19 | 1918.08 | 224.63 | 0.00 | 0.00 | 0.00 |
August | 1030.81 | 261.90 | 768.91 | 2226.18 | 343.47 | 0.00 | 0.00 | 0.00 |
September | 1632.41 | 848.12 | 784.29 | 3132.84 | 709.70 | 0.00 | 0.00 | 0.00 |
October | 2240.73 | 1522.37 | 718.36 | 3572.67 | 1214.44 | 0.00 | 0.00 | 0.00 |
November | 2696.87 | 2062.81 | 634.06 | 3714.17 | 2067.15 | 0.00 | 0.00 | 0.00 |
December | 2651.92 | 1992.35 | 659.58 | 3367.67 | 2625.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1750.40 | 1012.84 | 737.56 | 2729.41 | 1320.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 804.10 | 50.59 | 625.82 | 1707.67 | 224.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2696.87 | 2062.81 | 827.47 | 3714.17 | 2625.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.37 | 121.52 | 38.85 | 207.74 | 137.12 | 0.00 | 0.00 | 0.00 |
February | 150.88 | 107.00 | 43.88 | 200.05 | 120.63 | 0.00 | 0.00 | 0.00 |
March | 118.03 | 66.87 | 51.16 | 159.09 | 104.39 | 0.00 | 0.00 | 0.00 |
April | 82.25 | 30.87 | 51.37 | 132.46 | 55.39 | 0.00 | 0.00 | 0.00 |
May | 58.36 | 8.56 | 49.80 | 114.80 | 25.56 | 0.00 | 0.00 | 0.00 |
June | 49.92 | 3.14 | 46.78 | 133.70 | 8.56 | 0.00 | 0.00 | 0.00 |
July | 50.70 | 4.49 | 46.20 | 134.84 | 4.82 | 0.00 | 0.00 | 0.00 |
August | 63.99 | 16.26 | 47.74 | 150.59 | 9.91 | 0.00 | 0.00 | 0.00 |
September | 101.34 | 52.65 | 48.69 | 200.22 | 28.95 | 0.00 | 0.00 | 0.00 |
October | 139.11 | 94.51 | 44.60 | 224.55 | 58.85 | 0.00 | 0.00 | 0.00 |
November | 167.43 | 128.06 | 39.36 | 231.64 | 111.60 | 0.00 | 0.00 | 0.00 |
December | 164.64 | 123.69 | 40.95 | 209.34 | 147.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.67 | 62.88 | 45.79 | 174.72 | 67.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.92 | 3.14 | 38.85 | 114.80 | 4.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.43 | 128.06 | 51.37 | 231.64 | 147.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 123.37 | 69.54 | 53.83 | 119.25 | 288.26 | 0.00 | 0.00 | 0.00 |
February | 138.86 | 73.68 | 65.18 | 147.72 | 252.28 | 0.00 | 0.00 | 0.00 |
March | 189.48 | 101.60 | 87.88 | 230.05 | 204.01 | 0.00 | 0.00 | 0.00 |
April | 217.44 | 117.29 | 100.15 | 331.66 | 102.49 | 0.00 | 0.00 | 0.00 |
May | 234.65 | 125.58 | 109.07 | 417.16 | 47.60 | 0.00 | 0.00 | 0.00 |
June | 228.33 | 122.60 | 105.73 | 482.61 | 16.12 | 0.00 | 0.00 | 0.00 |
July | 202.77 | 100.75 | 102.02 | 435.67 | 8.82 | 0.00 | 0.00 | 0.00 |
August | 196.34 | 100.03 | 96.31 | 398.20 | 18.54 | 0.00 | 0.00 | 0.00 |
September | 201.57 | 112.53 | 89.04 | 369.83 | 55.12 | 0.00 | 0.00 | 0.00 |
October | 173.68 | 101.68 | 72.00 | 263.69 | 116.22 | 0.00 | 0.00 | 0.00 |
November | 144.91 | 88.17 | 56.74 | 166.75 | 234.25 | 0.00 | 0.00 | 0.00 |
December | 116.88 | 63.46 | 53.42 | 105.45 | 316.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 180.84 | 98.14 | 82.70 | 289.63 | 137.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.88 | 63.46 | 53.42 | 105.45 | 8.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 234.65 | 125.58 | 109.07 | 482.61 | 316.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.43 | 0.00 | 23.43 | 1.82 | 159.60 | 0.00 | 0.00 | 0.00 |
February | 28.61 | 0.00 | 28.61 | 8.73 | 140.86 | 0.00 | 0.00 | 0.00 |
March | 37.45 | 0.00 | 37.45 | 20.09 | 117.78 | 0.00 | 0.00 | 0.00 |
April | 43.49 | 0.55 | 42.93 | 50.97 | 59.02 | 0.00 | 0.00 | 0.00 |
May | 51.37 | 3.79 | 47.58 | 93.19 | 25.55 | 0.00 | 0.00 | 0.00 |
June | 54.63 | 6.81 | 47.82 | 138.39 | 8.66 | 0.00 | 0.00 | 0.00 |
July | 50.47 | 4.95 | 45.52 | 128.95 | 5.16 | 0.00 | 0.00 | 0.00 |
August | 42.68 | 1.02 | 41.67 | 100.18 | 10.77 | 0.00 | 0.00 | 0.00 |
September | 37.13 | 0.05 | 37.09 | 70.04 | 32.34 | 0.00 | 0.00 | 0.00 |
October | 30.78 | 0.00 | 30.78 | 33.03 | 70.13 | 0.00 | 0.00 | 0.00 |
November | 24.85 | 0.00 | 24.85 | 5.82 | 131.70 | 0.00 | 0.00 | 0.00 |
December | 23.25 | 0.00 | 23.25 | 1.36 | 175.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.39 | 1.44 | 35.95 | 54.63 | 77.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.25 | 0.00 | 23.25 | 1.36 | 5.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.63 | 6.81 | 47.82 | 138.39 | 175.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 123.37 | 69.54 | 53.83 | 125.35 | 281.66 | 0.00 | 0.00 | 0.00 |
February | 138.86 | 73.68 | 65.18 | 152.37 | 251.14 | 0.00 | 0.00 | 0.00 |
March | 189.48 | 101.60 | 87.88 | 230.07 | 209.38 | 0.00 | 0.00 | 0.00 |
April | 217.44 | 117.29 | 100.15 | 329.59 | 109.49 | 0.00 | 0.00 | 0.00 |
May | 234.65 | 125.58 | 109.07 | 413.39 | 51.57 | 0.00 | 0.00 | 0.00 |
June | 228.33 | 122.60 | 105.73 | 477.88 | 17.31 | 0.00 | 0.00 | 0.00 |
July | 202.77 | 100.75 | 102.02 | 430.82 | 10.14 | 0.00 | 0.00 | 0.00 |
August | 196.34 | 100.03 | 96.31 | 395.27 | 21.12 | 0.00 | 0.00 | 0.00 |
September | 201.57 | 112.53 | 89.04 | 369.74 | 60.75 | 0.00 | 0.00 | 0.00 |
October | 173.68 | 101.68 | 72.00 | 264.03 | 126.96 | 0.00 | 0.00 | 0.00 |
November | 144.91 | 88.17 | 56.74 | 171.66 | 233.69 | 0.00 | 0.00 | 0.00 |
December | 116.88 | 63.46 | 53.42 | 111.77 | 308.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 180.84 | 98.14 | 82.70 | 289.93 | 139.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.88 | 63.46 | 53.42 | 111.77 | 10.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 234.65 | 125.58 | 109.07 | 477.88 | 308.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.27 | 97.19 | 31.08 | 149.39 | 149.25 | 0.00 | 0.00 | 0.00 |
February | 120.68 | 85.59 | 35.09 | 142.99 | 134.46 | 0.00 | 0.00 | 0.00 |
March | 94.41 | 53.49 | 40.92 | 110.08 | 118.76 | 0.00 | 0.00 | 0.00 |
April | 65.78 | 24.69 | 41.09 | 88.57 | 75.42 | 0.00 | 0.00 | 0.00 |
May | 46.68 | 6.85 | 39.84 | 70.83 | 45.56 | 0.00 | 0.00 | 0.00 |
June | 39.93 | 2.51 | 37.42 | 79.84 | 23.69 | 0.00 | 0.00 | 0.00 |
July | 40.55 | 3.60 | 36.95 | 80.45 | 20.24 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 13.00 | 38.18 | 96.08 | 28.14 | 0.00 | 0.00 | 0.00 |
September | 81.06 | 42.11 | 38.94 | 141.62 | 49.49 | 0.00 | 0.00 | 0.00 |
October | 111.27 | 75.59 | 35.67 | 161.33 | 78.89 | 0.00 | 0.00 | 0.00 |
November | 133.92 | 102.43 | 31.48 | 167.87 | 126.18 | 0.00 | 0.00 | 0.00 |
December | 131.68 | 98.93 | 32.75 | 150.13 | 156.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 86.92 | 50.29 | 36.62 | 119.75 | 83.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.93 | 2.51 | 31.08 | 70.83 | 20.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.92 | 102.43 | 41.09 | 167.87 | 156.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.75 | 0.00 | 18.75 | 1.60 | 129.41 | 0.00 | 0.00 | 0.00 |
February | 22.89 | 0.00 | 22.89 | 7.88 | 112.94 | 0.00 | 0.00 | 0.00 |
March | 29.96 | 0.00 | 29.96 | 18.25 | 91.96 | 0.00 | 0.00 | 0.00 |
April | 34.79 | 0.44 | 34.35 | 45.11 | 44.82 | 0.00 | 0.00 | 0.00 |
May | 41.10 | 3.03 | 38.07 | 80.60 | 19.10 | 0.00 | 0.00 | 0.00 |
June | 43.71 | 5.45 | 38.26 | 118.17 | 6.14 | 0.00 | 0.00 | 0.00 |
July | 40.38 | 3.96 | 36.42 | 110.14 | 3.43 | 0.00 | 0.00 | 0.00 |
August | 34.15 | 0.81 | 33.34 | 86.55 | 7.77 | 0.00 | 0.00 | 0.00 |
September | 29.71 | 0.04 | 29.67 | 60.94 | 24.27 | 0.00 | 0.00 | 0.00 |
October | 24.63 | 0.00 | 24.63 | 29.31 | 53.14 | 0.00 | 0.00 | 0.00 |
November | 19.88 | 0.00 | 19.88 | 5.54 | 104.88 | 0.00 | 0.00 | 0.00 |
December | 18.60 | 0.00 | 18.60 | 1.15 | 143.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.91 | 1.15 | 28.76 | 47.31 | 61.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.60 | 0.00 | 18.60 | 1.15 | 3.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.71 | 5.45 | 38.26 | 118.17 | 143.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.82 | 63.30 | 53.52 | 96.75 | 275.76 | 0.00 | 0.00 | 0.00 |
February | 156.78 | 89.40 | 67.38 | 161.14 | 234.51 | 0.00 | 0.00 | 0.00 |
March | 193.25 | 106.41 | 86.84 | 223.04 | 186.89 | 0.00 | 0.00 | 0.00 |
April | 232.96 | 129.21 | 103.75 | 348.60 | 91.47 | 0.00 | 0.00 | 0.00 |
May | 240.15 | 130.46 | 109.69 | 424.32 | 42.77 | 0.00 | 0.00 | 0.00 |
June | 240.26 | 133.59 | 106.66 | 502.97 | 14.98 | 0.00 | 0.00 | 0.00 |
July | 215.60 | 112.72 | 102.88 | 457.96 | 8.55 | 0.00 | 0.00 | 0.00 |
August | 205.38 | 105.17 | 100.21 | 414.40 | 17.35 | 0.00 | 0.00 | 0.00 |
September | 203.76 | 116.36 | 87.40 | 367.47 | 49.95 | 0.00 | 0.00 | 0.00 |
October | 155.96 | 84.01 | 71.95 | 223.74 | 108.29 | 0.00 | 0.00 | 0.00 |
November | 139.64 | 81.11 | 58.53 | 141.18 | 218.41 | 0.00 | 0.00 | 0.00 |
December | 116.91 | 61.95 | 54.96 | 92.45 | 302.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.81 | 101.08 | 83.72 | 288.31 | 128.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.82 | 61.95 | 53.52 | 92.45 | 8.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 240.26 | 133.59 | 109.69 | 502.97 | 302.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.37 | 121.52 | 38.85 | 206.44 | 136.36 | 0.00 | 0.00 | 0.00 |
February | 150.88 | 107.00 | 43.88 | 197.91 | 120.07 | 0.00 | 0.00 | 0.00 |
March | 118.03 | 66.87 | 51.16 | 157.16 | 103.74 | 0.00 | 0.00 | 0.00 |
April | 82.25 | 30.87 | 51.37 | 130.90 | 55.32 | 0.00 | 0.00 | 0.00 |
May | 58.36 | 8.56 | 49.80 | 113.76 | 25.49 | 0.00 | 0.00 | 0.00 |
June | 49.92 | 3.14 | 46.78 | 132.67 | 8.39 | 0.00 | 0.00 | 0.00 |
July | 50.70 | 4.49 | 46.20 | 133.98 | 4.68 | 0.00 | 0.00 | 0.00 |
August | 63.99 | 16.26 | 47.74 | 149.88 | 9.79 | 0.00 | 0.00 | 0.00 |
September | 101.34 | 52.65 | 48.69 | 199.35 | 28.60 | 0.00 | 0.00 | 0.00 |
October | 139.11 | 94.51 | 44.60 | 223.90 | 57.92 | 0.00 | 0.00 | 0.00 |
November | 167.43 | 128.06 | 39.36 | 230.54 | 110.69 | 0.00 | 0.00 | 0.00 |
December | 164.64 | 123.69 | 40.95 | 207.87 | 147.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.67 | 62.88 | 45.79 | 173.50 | 67.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.92 | 3.14 | 38.85 | 113.76 | 4.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.43 | 128.06 | 51.37 | 230.54 | 147.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.43 | 0.00 | 23.43 | 1.35 | 159.60 | 0.00 | 0.00 | 0.00 |
February | 28.61 | 0.00 | 28.61 | 7.81 | 141.10 | 0.00 | 0.00 | 0.00 |
March | 37.45 | 0.00 | 37.45 | 19.07 | 115.97 | 0.00 | 0.00 | 0.00 |
April | 43.49 | 0.55 | 42.93 | 49.08 | 58.00 | 0.00 | 0.00 | 0.00 |
May | 51.37 | 3.79 | 47.58 | 90.29 | 25.17 | 0.00 | 0.00 | 0.00 |
June | 54.63 | 6.81 | 47.82 | 136.01 | 8.52 | 0.00 | 0.00 | 0.00 |
July | 50.47 | 4.95 | 45.52 | 126.91 | 5.03 | 0.00 | 0.00 | 0.00 |
August | 42.68 | 1.02 | 41.67 | 98.22 | 10.63 | 0.00 | 0.00 | 0.00 |
September | 37.13 | 0.05 | 37.09 | 68.12 | 32.34 | 0.00 | 0.00 | 0.00 |
October | 30.78 | 0.00 | 30.78 | 32.38 | 66.97 | 0.00 | 0.00 | 0.00 |
November | 24.85 | 0.00 | 24.85 | 4.97 | 130.71 | 0.00 | 0.00 | 0.00 |
December | 23.25 | 0.00 | 23.25 | 1.01 | 175.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.39 | 1.44 | 35.95 | 53.18 | 77.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.25 | 0.00 | 23.25 | 1.01 | 5.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.63 | 6.81 | 47.82 | 136.01 | 175.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.82 | 63.30 | 53.52 | 100.80 | 266.63 | 0.00 | 0.00 | 0.00 |
February | 156.78 | 89.40 | 67.38 | 165.44 | 232.02 | 0.00 | 0.00 | 0.00 |
March | 193.25 | 106.41 | 86.84 | 225.54 | 190.18 | 0.00 | 0.00 | 0.00 |
April | 232.96 | 129.21 | 103.75 | 346.36 | 97.09 | 0.00 | 0.00 | 0.00 |
May | 240.15 | 130.46 | 109.69 | 416.02 | 45.97 | 0.00 | 0.00 | 0.00 |
June | 240.26 | 133.59 | 106.66 | 494.27 | 15.86 | 0.00 | 0.00 | 0.00 |
July | 215.60 | 112.72 | 102.88 | 449.74 | 9.65 | 0.00 | 0.00 | 0.00 |
August | 205.38 | 105.17 | 100.21 | 407.69 | 19.33 | 0.00 | 0.00 | 0.00 |
September | 203.76 | 116.36 | 87.40 | 362.77 | 54.45 | 0.00 | 0.00 | 0.00 |
October | 155.96 | 84.01 | 71.95 | 225.67 | 115.89 | 0.00 | 0.00 | 0.00 |
November | 139.64 | 81.11 | 58.53 | 145.34 | 216.11 | 0.00 | 0.00 | 0.00 |
December | 116.91 | 61.95 | 54.96 | 96.17 | 291.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.81 | 101.08 | 83.72 | 286.75 | 129.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.82 | 61.95 | 53.52 | 96.17 | 9.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 240.26 | 133.59 | 109.69 | 494.27 | 291.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.67 | 0.00 | 29.67 | 0.63 | 248.77 | 362.83 | 0.00 | 0.00 |
February | 36.23 | 0.00 | 36.23 | 7.63 | 215.12 | 164.00 | 0.00 | 0.00 |
March | 47.43 | 0.00 | 47.42 | 21.51 | 173.93 | 82.50 | 0.00 | 0.00 |
April | 55.07 | 0.70 | 54.37 | 61.00 | 89.88 | 3.67 | 0.00 | 0.00 |
May | 65.06 | 4.79 | 60.26 | 113.75 | 43.66 | 0.00 | 0.00 | 0.00 |
June | 69.18 | 8.62 | 60.56 | 168.79 | 18.48 | 0.00 | 0.00 | 0.00 |
July | 63.91 | 6.27 | 57.65 | 156.01 | 13.26 | 0.00 | 0.00 | 0.00 |
August | 54.06 | 1.29 | 52.77 | 120.34 | 22.22 | 0.00 | 0.00 | 0.00 |
September | 47.03 | 0.06 | 46.97 | 85.71 | 53.07 | 0.00 | 0.00 | 0.00 |
October | 38.98 | 0.00 | 38.98 | 37.61 | 102.76 | 0.33 | 0.00 | 0.00 |
November | 31.47 | 0.00 | 31.47 | 4.21 | 201.87 | 161.17 | 0.00 | 0.00 |
December | 29.44 | 0.00 | 29.44 | 0.45 | 271.12 | 424.83 | 0.00 | 0.00 |
Annual Sum or Average | 47.35 | 1.82 | 45.53 | 65.11 | 120.74 | 1199.33 | 0.00 | 0.00 |
Minimum of Months | 29.44 | 0.00 | 29.44 | 0.45 | 13.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.18 | 8.62 | 60.56 | 168.79 | 271.12 | 424.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.94 | 0.00 | 10.94 | 0.23 | 91.71 | 362.83 | 0.00 | 0.00 |
February | 13.36 | 0.00 | 13.36 | 2.81 | 79.30 | 164.00 | 0.00 | 0.00 |
March | 17.48 | 0.00 | 17.48 | 7.93 | 64.12 | 82.50 | 0.00 | 0.00 |
April | 20.30 | 0.26 | 20.04 | 22.49 | 33.13 | 3.67 | 0.00 | 0.00 |
May | 23.98 | 1.77 | 22.21 | 41.93 | 16.10 | 0.00 | 0.00 | 0.00 |
June | 25.50 | 3.18 | 22.33 | 62.22 | 6.81 | 0.00 | 0.00 | 0.00 |
July | 23.56 | 2.31 | 21.25 | 57.51 | 4.89 | 0.00 | 0.00 | 0.00 |
August | 19.93 | 0.47 | 19.45 | 44.36 | 8.19 | 0.00 | 0.00 | 0.00 |
September | 17.34 | 0.02 | 17.31 | 31.60 | 19.56 | 0.00 | 0.00 | 0.00 |
October | 14.37 | 0.00 | 14.37 | 13.87 | 37.88 | 0.33 | 0.00 | 0.00 |
November | 11.60 | 0.00 | 11.60 | 1.55 | 74.42 | 161.17 | 0.00 | 0.00 |
December | 10.85 | 0.00 | 10.85 | 0.16 | 99.95 | 424.83 | 0.00 | 0.00 |
Annual Sum or Average | 17.45 | 0.67 | 16.78 | 24.00 | 44.51 | 1199.33 | 0.00 | 0.00 |
Minimum of Months | 10.85 | 0.00 | 10.85 | 0.16 | 4.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.50 | 3.18 | 22.33 | 62.22 | 99.95 | 424.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.83 | 56.70 | 18.13 | 94.33 | 75.65 | 272.67 | 0.00 | 0.00 |
February | 70.40 | 49.93 | 20.47 | 90.79 | 66.99 | 118.00 | 0.00 | 0.00 |
March | 55.07 | 31.20 | 23.87 | 71.86 | 58.29 | 69.00 | 0.00 | 0.00 |
April | 38.38 | 14.41 | 23.97 | 60.01 | 33.34 | 4.17 | 0.00 | 0.00 |
May | 27.23 | 3.99 | 23.24 | 51.26 | 17.39 | 0.00 | 0.00 | 0.00 |
June | 23.29 | 1.47 | 21.83 | 58.86 | 7.19 | 0.00 | 0.00 | 0.00 |
July | 23.65 | 2.10 | 21.56 | 59.06 | 5.20 | 0.00 | 0.00 | 0.00 |
August | 29.86 | 7.59 | 22.27 | 67.12 | 8.55 | 0.00 | 0.00 | 0.00 |
September | 47.29 | 24.57 | 22.72 | 91.88 | 19.25 | 0.00 | 0.00 | 0.00 |
October | 64.91 | 44.10 | 20.81 | 102.90 | 35.01 | 0.33 | 0.00 | 0.00 |
November | 78.12 | 59.75 | 18.37 | 105.77 | 62.22 | 125.00 | 0.00 | 0.00 |
December | 76.82 | 57.71 | 19.11 | 94.74 | 80.44 | 312.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.70 | 29.34 | 21.37 | 78.95 | 38.99 | 901.17 | 0.00 | 0.00 |
Minimum of Months | 23.29 | 1.47 | 18.13 | 51.26 | 5.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.12 | 59.75 | 23.97 | 105.77 | 80.44 | 312.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.10 | 153.89 | 49.20 | 256.04 | 205.33 | 272.67 | 0.00 | 0.00 |
February | 191.08 | 135.51 | 55.57 | 246.42 | 181.84 | 118.00 | 0.00 | 0.00 |
March | 149.48 | 84.69 | 64.79 | 195.05 | 158.22 | 69.00 | 0.00 | 0.00 |
April | 104.16 | 39.10 | 65.06 | 162.87 | 90.49 | 4.17 | 0.00 | 0.00 |
May | 73.91 | 10.84 | 63.07 | 139.13 | 47.21 | 0.00 | 0.00 | 0.00 |
June | 63.22 | 3.98 | 59.24 | 159.76 | 19.52 | 0.00 | 0.00 | 0.00 |
July | 64.20 | 5.69 | 58.51 | 160.29 | 14.10 | 0.00 | 0.00 | 0.00 |
August | 81.05 | 20.59 | 60.45 | 182.17 | 23.20 | 0.00 | 0.00 | 0.00 |
September | 128.35 | 66.68 | 61.66 | 249.37 | 52.24 | 0.00 | 0.00 | 0.00 |
October | 176.17 | 119.69 | 56.48 | 279.30 | 95.03 | 0.33 | 0.00 | 0.00 |
November | 212.04 | 162.18 | 49.85 | 287.08 | 168.89 | 125.00 | 0.00 | 0.00 |
December | 208.50 | 156.64 | 51.86 | 257.15 | 218.34 | 312.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.62 | 79.63 | 57.99 | 214.29 | 105.84 | 901.17 | 0.00 | 0.00 |
Minimum of Months | 63.22 | 3.98 | 49.20 | 139.13 | 14.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 212.04 | 162.18 | 65.06 | 287.08 | 218.34 | 312.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.37 | 121.52 | 38.85 | 207.06 | 132.84 | 0.00 | 0.00 | 0.00 |
February | 150.88 | 107.00 | 43.88 | 198.86 | 117.08 | 0.00 | 0.00 | 0.00 |
March | 118.03 | 66.87 | 51.16 | 157.28 | 101.51 | 0.00 | 0.00 | 0.00 |
April | 82.25 | 30.87 | 51.37 | 130.16 | 53.38 | 0.00 | 0.00 | 0.00 |
May | 58.36 | 8.56 | 49.80 | 113.00 | 24.17 | 0.00 | 0.00 | 0.00 |
June | 49.92 | 3.14 | 46.78 | 132.01 | 7.91 | 0.00 | 0.00 | 0.00 |
July | 50.70 | 4.49 | 46.20 | 132.76 | 4.41 | 0.00 | 0.00 | 0.00 |
August | 63.99 | 16.26 | 47.74 | 148.33 | 9.22 | 0.00 | 0.00 | 0.00 |
September | 101.34 | 52.65 | 48.69 | 197.33 | 27.66 | 0.00 | 0.00 | 0.00 |
October | 139.11 | 94.51 | 44.60 | 222.24 | 56.91 | 0.00 | 0.00 | 0.00 |
November | 167.43 | 128.06 | 39.36 | 230.47 | 108.07 | 0.00 | 0.00 | 0.00 |
December | 164.64 | 123.69 | 40.95 | 209.47 | 143.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.67 | 62.88 | 45.79 | 173.05 | 65.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.92 | 3.14 | 38.85 | 113.00 | 4.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.43 | 128.06 | 51.37 | 230.47 | 143.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 123.37 | 69.54 | 53.83 | 118.11 | 278.00 | 0.00 | 0.00 | 0.00 |
February | 138.86 | 73.68 | 65.18 | 145.75 | 243.75 | 0.00 | 0.00 | 0.00 |
March | 189.48 | 101.60 | 87.88 | 226.53 | 197.47 | 0.00 | 0.00 | 0.00 |
April | 217.44 | 117.29 | 100.15 | 326.65 | 98.46 | 0.00 | 0.00 | 0.00 |
May | 234.65 | 125.58 | 109.07 | 411.34 | 44.95 | 0.00 | 0.00 | 0.00 |
June | 228.33 | 122.60 | 105.73 | 476.82 | 14.97 | 0.00 | 0.00 | 0.00 |
July | 202.77 | 100.75 | 102.02 | 429.96 | 8.04 | 0.00 | 0.00 | 0.00 |
August | 196.34 | 100.03 | 96.31 | 392.90 | 17.26 | 0.00 | 0.00 | 0.00 |
September | 201.57 | 112.53 | 89.04 | 364.57 | 52.57 | 0.00 | 0.00 | 0.00 |
October | 173.68 | 101.68 | 72.00 | 260.31 | 111.73 | 0.00 | 0.00 | 0.00 |
November | 144.91 | 88.17 | 56.74 | 164.93 | 225.82 | 0.00 | 0.00 | 0.00 |
December | 116.88 | 63.46 | 53.42 | 105.03 | 304.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 180.84 | 98.14 | 82.70 | 285.86 | 132.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.88 | 63.46 | 53.42 | 105.03 | 8.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 234.65 | 125.58 | 109.07 | 476.82 | 304.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.43 | 0.00 | 23.43 | 2.31 | 153.35 | 0.00 | 0.00 | 0.00 |
February | 28.61 | 0.00 | 28.61 | 9.01 | 136.01 | 0.00 | 0.00 | 0.00 |
March | 37.45 | 0.00 | 37.45 | 19.97 | 114.92 | 0.00 | 0.00 | 0.00 |
April | 43.49 | 0.55 | 42.93 | 49.84 | 57.55 | 0.00 | 0.00 | 0.00 |
May | 51.37 | 3.79 | 47.58 | 91.81 | 24.45 | 0.00 | 0.00 | 0.00 |
June | 54.63 | 6.81 | 47.82 | 136.40 | 8.10 | 0.00 | 0.00 | 0.00 |
July | 50.47 | 4.95 | 45.52 | 126.76 | 4.80 | 0.00 | 0.00 | 0.00 |
August | 42.68 | 1.02 | 41.67 | 98.49 | 10.17 | 0.00 | 0.00 | 0.00 |
September | 37.13 | 0.05 | 37.09 | 68.36 | 31.08 | 0.00 | 0.00 | 0.00 |
October | 30.78 | 0.00 | 30.78 | 32.31 | 68.74 | 0.00 | 0.00 | 0.00 |
November | 24.85 | 0.00 | 24.85 | 6.03 | 127.26 | 0.00 | 0.00 | 0.00 |
December | 23.25 | 0.00 | 23.25 | 1.73 | 168.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.39 | 1.44 | 35.95 | 53.83 | 75.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.25 | 0.00 | 23.25 | 1.73 | 4.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.63 | 6.81 | 47.82 | 136.40 | 168.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 123.37 | 69.54 | 53.83 | 125.88 | 270.60 | 0.00 | 0.00 | 0.00 |
February | 138.86 | 73.68 | 65.18 | 151.55 | 242.23 | 0.00 | 0.00 | 0.00 |
March | 189.48 | 101.60 | 87.88 | 226.80 | 203.57 | 0.00 | 0.00 | 0.00 |
April | 217.44 | 117.29 | 100.15 | 324.36 | 106.26 | 0.00 | 0.00 | 0.00 |
May | 234.65 | 125.58 | 109.07 | 407.54 | 49.04 | 0.00 | 0.00 | 0.00 |
June | 228.33 | 122.60 | 105.73 | 472.04 | 16.10 | 0.00 | 0.00 | 0.00 |
July | 202.77 | 100.75 | 102.02 | 424.98 | 9.36 | 0.00 | 0.00 | 0.00 |
August | 196.34 | 100.03 | 96.31 | 389.90 | 19.82 | 0.00 | 0.00 | 0.00 |
September | 201.57 | 112.53 | 89.04 | 364.57 | 58.30 | 0.00 | 0.00 | 0.00 |
October | 173.68 | 101.68 | 72.00 | 260.58 | 123.85 | 0.00 | 0.00 | 0.00 |
November | 144.91 | 88.17 | 56.74 | 170.80 | 225.02 | 0.00 | 0.00 | 0.00 |
December | 116.88 | 63.46 | 53.42 | 113.14 | 296.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 180.84 | 98.14 | 82.70 | 286.60 | 134.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.88 | 63.46 | 53.42 | 113.14 | 9.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 234.65 | 125.58 | 109.07 | 472.04 | 296.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.19 | 178.21 | 56.98 | 295.47 | 202.63 | 0.00 | 0.00 | 0.00 |
February | 221.28 | 156.93 | 64.35 | 285.08 | 177.37 | 0.00 | 0.00 | 0.00 |
March | 173.11 | 98.07 | 75.03 | 227.48 | 150.88 | 0.00 | 0.00 | 0.00 |
April | 120.62 | 45.28 | 75.34 | 193.14 | 77.44 | 0.00 | 0.00 | 0.00 |
May | 85.60 | 12.55 | 73.04 | 172.51 | 34.39 | 0.00 | 0.00 | 0.00 |
June | 73.21 | 4.61 | 68.61 | 202.45 | 10.93 | 0.00 | 0.00 | 0.00 |
July | 74.35 | 6.59 | 67.76 | 202.55 | 5.92 | 0.00 | 0.00 | 0.00 |
August | 93.85 | 23.85 | 70.01 | 223.59 | 12.99 | 0.00 | 0.00 | 0.00 |
September | 148.63 | 77.22 | 71.41 | 291.96 | 39.88 | 0.00 | 0.00 | 0.00 |
October | 204.02 | 138.61 | 65.41 | 324.21 | 84.32 | 0.00 | 0.00 | 0.00 |
November | 245.55 | 187.82 | 57.73 | 331.83 | 163.80 | 0.00 | 0.00 | 0.00 |
December | 241.46 | 181.40 | 60.05 | 297.96 | 218.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.37 | 92.22 | 67.15 | 253.76 | 97.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.21 | 4.61 | 56.98 | 172.51 | 5.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 245.55 | 187.82 | 75.34 | 331.83 | 218.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 164.00 | 0.00 | 164.00 | 4.51 | 1335.69 | 0.00 | 0.00 | 0.00 |
February | 200.26 | 0.00 | 200.26 | 40.05 | 1171.02 | 0.00 | 0.00 | 0.00 |
March | 262.13 | 0.01 | 262.12 | 109.22 | 966.51 | 0.00 | 0.00 | 0.00 |
April | 304.39 | 3.88 | 300.52 | 305.08 | 519.91 | 0.00 | 0.00 | 0.00 |
May | 359.57 | 26.50 | 333.07 | 577.21 | 266.30 | 0.00 | 0.00 | 0.00 |
June | 382.38 | 47.65 | 334.73 | 867.95 | 123.02 | 0.00 | 0.00 | 0.00 |
July | 353.26 | 34.65 | 318.61 | 798.43 | 95.25 | 0.00 | 0.00 | 0.00 |
August | 298.77 | 7.11 | 291.66 | 611.13 | 146.89 | 0.00 | 0.00 | 0.00 |
September | 259.93 | 0.33 | 259.60 | 436.83 | 315.93 | 0.00 | 0.00 | 0.00 |
October | 215.46 | 0.00 | 215.46 | 188.94 | 587.72 | 0.00 | 0.00 | 0.00 |
November | 173.94 | 0.00 | 173.94 | 21.89 | 1101.23 | 0.00 | 0.00 | 0.00 |
December | 162.73 | 0.00 | 162.73 | 3.22 | 1437.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.70 | 10.06 | 251.64 | 331.91 | 669.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.73 | 0.00 | 162.73 | 3.22 | 95.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.38 | 47.65 | 334.73 | 867.95 | 1437.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 164.00 | 0.00 | 164.00 | 3.06 | 1380.09 | 0.00 | 0.00 | 0.00 |
February | 200.26 | 0.00 | 200.26 | 34.62 | 1205.47 | 0.00 | 0.00 | 0.00 |
March | 262.13 | 0.01 | 262.12 | 99.28 | 991.93 | 0.00 | 0.00 | 0.00 |
April | 304.39 | 3.88 | 300.52 | 293.69 | 533.90 | 0.00 | 0.00 | 0.00 |
May | 359.57 | 26.50 | 333.07 | 564.72 | 274.81 | 0.00 | 0.00 | 0.00 |
June | 382.38 | 47.65 | 334.73 | 855.50 | 128.18 | 0.00 | 0.00 | 0.00 |
July | 353.26 | 34.65 | 318.61 | 785.90 | 100.45 | 0.00 | 0.00 | 0.00 |
August | 298.77 | 7.11 | 291.66 | 599.09 | 153.50 | 0.00 | 0.00 | 0.00 |
September | 259.93 | 0.33 | 259.60 | 427.10 | 325.86 | 0.00 | 0.00 | 0.00 |
October | 215.46 | 0.00 | 215.46 | 179.01 | 603.66 | 0.00 | 0.00 | 0.00 |
November | 173.94 | 0.00 | 173.94 | 17.70 | 1135.22 | 0.00 | 0.00 | 0.00 |
December | 162.73 | 0.00 | 162.73 | 1.96 | 1485.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.70 | 10.06 | 251.64 | 323.32 | 690.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.73 | 0.00 | 162.73 | 1.96 | 100.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.38 | 47.65 | 334.73 | 855.50 | 1485.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.43 | 0.00 | 23.43 | 0.26 | 203.40 | 0.00 | 0.00 | 0.00 |
February | 28.61 | 0.00 | 28.61 | 5.16 | 177.31 | 0.00 | 0.00 | 0.00 |
March | 37.45 | 0.00 | 37.45 | 14.10 | 146.96 | 0.00 | 0.00 | 0.00 |
April | 43.49 | 0.55 | 42.93 | 46.00 | 80.92 | 0.00 | 0.00 | 0.00 |
May | 51.37 | 3.79 | 47.58 | 86.82 | 44.58 | 0.00 | 0.00 | 0.00 |
June | 54.63 | 6.81 | 47.82 | 131.07 | 22.72 | 0.00 | 0.00 | 0.00 |
July | 50.47 | 4.95 | 45.52 | 122.35 | 18.93 | 0.00 | 0.00 | 0.00 |
August | 42.68 | 1.02 | 41.67 | 95.04 | 26.44 | 0.00 | 0.00 | 0.00 |
September | 37.13 | 0.05 | 37.09 | 70.16 | 48.97 | 0.00 | 0.00 | 0.00 |
October | 30.78 | 0.00 | 30.78 | 29.29 | 89.29 | 0.00 | 0.00 | 0.00 |
November | 24.85 | 0.00 | 24.85 | 2.88 | 166.38 | 0.00 | 0.00 | 0.00 |
December | 23.25 | 0.00 | 23.25 | 0.25 | 217.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.39 | 1.44 | 35.95 | 50.52 | 103.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.25 | 0.00 | 23.25 | 0.25 | 18.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.63 | 6.81 | 47.82 | 131.07 | 217.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 233.62 | 126.59 | 107.03 | 180.68 | 678.83 | 0.00 | 0.00 | 0.00 |
February | 313.55 | 178.79 | 134.76 | 308.71 | 585.79 | 0.00 | 0.00 | 0.00 |
March | 386.47 | 212.80 | 173.68 | 422.26 | 480.12 | 0.00 | 0.00 | 0.00 |
April | 465.90 | 258.40 | 207.49 | 675.41 | 272.97 | 0.00 | 0.00 | 0.00 |
May | 480.27 | 260.91 | 219.37 | 817.79 | 162.48 | 0.00 | 0.00 | 0.00 |
June | 480.48 | 267.17 | 213.31 | 968.08 | 85.24 | 0.00 | 0.00 | 0.00 |
July | 431.17 | 225.42 | 205.75 | 879.50 | 71.91 | 0.00 | 0.00 | 0.00 |
August | 410.72 | 210.32 | 200.40 | 802.34 | 98.12 | 0.00 | 0.00 | 0.00 |
September | 407.49 | 232.69 | 174.80 | 733.57 | 171.69 | 0.00 | 0.00 | 0.00 |
October | 311.89 | 168.00 | 143.89 | 434.38 | 309.87 | 0.00 | 0.00 | 0.00 |
November | 279.27 | 162.21 | 117.06 | 270.01 | 550.67 | 0.00 | 0.00 | 0.00 |
December | 233.80 | 123.89 | 109.91 | 173.49 | 722.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 369.59 | 202.15 | 167.43 | 556.38 | 348.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.62 | 123.89 | 107.03 | 173.49 | 71.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 480.48 | 267.17 | 219.37 | 968.08 | 722.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.37 | 121.52 | 38.85 | 201.72 | 167.25 | 0.00 | 0.00 | 0.00 |
February | 150.88 | 107.00 | 43.88 | 193.59 | 149.98 | 0.00 | 0.00 | 0.00 |
March | 118.03 | 66.87 | 51.16 | 150.65 | 131.94 | 0.00 | 0.00 | 0.00 |
April | 82.25 | 30.87 | 51.37 | 125.20 | 80.78 | 0.00 | 0.00 | 0.00 |
May | 58.36 | 8.56 | 49.80 | 105.38 | 47.35 | 0.00 | 0.00 | 0.00 |
June | 49.92 | 3.14 | 46.78 | 123.11 | 23.48 | 0.00 | 0.00 | 0.00 |
July | 50.70 | 4.49 | 46.20 | 125.16 | 19.65 | 0.00 | 0.00 | 0.00 |
August | 63.99 | 16.26 | 47.74 | 143.74 | 27.20 | 0.00 | 0.00 | 0.00 |
September | 101.34 | 52.65 | 48.69 | 199.40 | 48.40 | 0.00 | 0.00 | 0.00 |
October | 139.11 | 94.51 | 44.60 | 220.97 | 82.58 | 0.00 | 0.00 | 0.00 |
November | 167.43 | 128.06 | 39.36 | 227.30 | 138.60 | 0.00 | 0.00 | 0.00 |
December | 164.64 | 123.69 | 40.95 | 203.97 | 175.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 108.67 | 62.88 | 45.79 | 168.14 | 90.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.92 | 3.14 | 38.85 | 105.38 | 19.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.43 | 128.06 | 51.37 | 227.30 | 175.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.67 | 0.00 | 29.67 | 0.52 | 238.30 | 442.17 | 0.00 | 0.00 |
February | 36.23 | 0.00 | 36.23 | 6.54 | 209.41 | 234.33 | 0.00 | 0.00 |
March | 47.43 | 0.00 | 47.42 | 19.17 | 171.65 | 146.83 | 0.00 | 0.00 |
April | 55.07 | 0.70 | 54.37 | 56.09 | 90.95 | 17.17 | 0.00 | 0.00 |
May | 65.06 | 4.79 | 60.26 | 107.18 | 45.15 | 0.00 | 0.00 | 0.00 |
June | 69.18 | 8.62 | 60.56 | 160.37 | 19.98 | 0.00 | 0.00 | 0.00 |
July | 63.91 | 6.27 | 57.65 | 147.42 | 14.97 | 0.00 | 0.00 | 0.00 |
August | 54.06 | 1.29 | 52.77 | 112.78 | 24.06 | 0.00 | 0.00 | 0.00 |
September | 47.03 | 0.06 | 46.97 | 79.56 | 55.04 | 0.50 | 0.00 | 0.00 |
October | 38.98 | 0.00 | 38.98 | 33.44 | 104.50 | 17.33 | 0.00 | 0.00 |
November | 31.47 | 0.00 | 31.47 | 3.22 | 197.51 | 228.33 | 0.00 | 0.00 |
December | 29.44 | 0.00 | 29.44 | 0.41 | 254.11 | 470.83 | 0.00 | 0.00 |
Annual Sum or Average | 47.35 | 1.82 | 45.53 | 60.85 | 118.36 | 1557.50 | 0.00 | 0.00 |
Minimum of Months | 29.44 | 0.00 | 29.44 | 0.41 | 14.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.18 | 8.62 | 60.56 | 160.37 | 254.11 | 470.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.55 | 0.00 | 26.55 | 0.47 | 213.21 | 442.17 | 0.00 | 0.00 |
February | 32.42 | 0.00 | 32.42 | 5.85 | 187.36 | 234.33 | 0.00 | 0.00 |
March | 42.43 | 0.00 | 42.43 | 17.16 | 153.57 | 146.83 | 0.00 | 0.00 |
April | 49.27 | 0.63 | 48.65 | 50.19 | 81.37 | 17.17 | 0.00 | 0.00 |
May | 58.21 | 4.29 | 53.92 | 95.89 | 40.40 | 0.00 | 0.00 | 0.00 |
June | 61.90 | 7.71 | 54.18 | 143.49 | 17.88 | 0.00 | 0.00 | 0.00 |
July | 57.18 | 5.61 | 51.58 | 131.90 | 13.39 | 0.00 | 0.00 | 0.00 |
August | 48.36 | 1.15 | 47.21 | 100.90 | 21.53 | 0.00 | 0.00 | 0.00 |
September | 42.08 | 0.05 | 42.02 | 71.18 | 49.25 | 0.50 | 0.00 | 0.00 |
October | 34.88 | 0.00 | 34.88 | 29.92 | 93.50 | 17.33 | 0.00 | 0.00 |
November | 28.16 | 0.00 | 28.16 | 2.88 | 176.71 | 228.33 | 0.00 | 0.00 |
December | 26.34 | 0.00 | 26.34 | 0.37 | 227.35 | 470.83 | 0.00 | 0.00 |
Annual Sum or Average | 42.36 | 1.63 | 40.73 | 54.44 | 105.90 | 1557.50 | 0.00 | 0.00 |
Minimum of Months | 26.34 | 0.00 | 26.34 | 0.37 | 13.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.90 | 7.71 | 54.18 | 143.49 | 227.35 | 470.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 598.70 | 453.65 | 145.05 | 750.40 | 577.85 | 351.00 | 0.00 | 0.00 |
February | 563.28 | 399.48 | 163.81 | 717.60 | 521.53 | 183.83 | 0.00 | 0.00 |
March | 440.65 | 249.65 | 191.00 | 560.25 | 459.19 | 125.00 | 0.00 | 0.00 |
April | 307.05 | 115.26 | 191.78 | 460.82 | 269.90 | 17.00 | 0.00 | 0.00 |
May | 217.89 | 31.95 | 185.94 | 389.88 | 144.09 | 0.00 | 0.00 | 0.00 |
June | 186.37 | 11.73 | 174.64 | 447.04 | 62.22 | 0.00 | 0.00 | 0.00 |
July | 189.26 | 16.78 | 172.48 | 447.39 | 47.09 | 0.00 | 0.00 | 0.00 |
August | 238.91 | 60.70 | 178.21 | 512.99 | 74.31 | 0.00 | 0.00 | 0.00 |
September | 378.35 | 196.57 | 181.78 | 712.73 | 160.07 | 0.50 | 0.00 | 0.00 |
October | 519.34 | 352.84 | 166.50 | 803.72 | 284.22 | 15.00 | 0.00 | 0.00 |
November | 625.06 | 478.10 | 146.96 | 836.20 | 484.04 | 176.17 | 0.00 | 0.00 |
December | 614.64 | 461.77 | 152.87 | 760.74 | 602.67 | 377.00 | 0.00 | 0.00 |
Annual Sum or Average | 405.69 | 234.75 | 170.94 | 615.84 | 306.20 | 1245.50 | 0.00 | 0.00 |
Minimum of Months | 186.37 | 11.73 | 145.05 | 389.88 | 47.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 625.06 | 478.10 | 191.78 | 836.20 | 602.67 | 377.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.244284E+10 | 0.160376E+10 |
February | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.211949E+10 | 0.129215E+10 |
March | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.187537E+10 | 0.125687E+10 |
April | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.145593E+10 | 0.727294E+09 |
May | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.121697E+10 | 0.422368E+09 |
June | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.128664E+10 | 0.188846E+09 |
July | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.135241E+10 | 0.147758E+09 |
August | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.157833E+10 | 0.225771E+09 |
September | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.217212E+10 | 0.460082E+09 |
October | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.258237E+10 | 0.797054E+09 |
November | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.261310E+10 | 0.130492E+10 |
December | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.244837E+10 | 0.171946E+10 |
Annual Sum or Average | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.231439E+11 | 0.101463E+11 |
Minimum of Months | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.121697E+10 | 0.147758E+09 |
Maximum of Months | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.261310E+10 | 0.171946E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.681379E+10 | 0.469598E+10 |
February | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.588521E+10 | 0.385467E+10 |
March | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.514950E+10 | 0.377893E+10 |
April | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.397140E+10 | 0.225011E+10 |
May | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.331674E+10 | 0.132281E+10 |
June | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.355371E+10 | 0.588124E+09 |
July | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.374043E+10 | 0.466435E+09 |
August | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.436874E+10 | 0.709455E+09 |
September | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.602873E+10 | 0.140487E+10 |
October | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.714133E+10 | 0.246763E+10 |
November | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.726624E+10 | 0.387254E+10 |
December | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.682863E+10 | 0.498921E+10 |
Annual Sum or Average | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.640644E+11 | 0.304008E+11 |
Minimum of Months | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.331674E+10 | 0.466435E+09 |
Maximum of Months | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.726624E+10 | 0.498921E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.901748E+10 | 0.659502E+10 |
February | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.781702E+10 | 0.532275E+10 |
March | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.692019E+10 | 0.518793E+10 |
April | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.541761E+10 | 0.301269E+10 |
May | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.457383E+10 | 0.174607E+10 |
June | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.489215E+10 | 0.767282E+09 |
July | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.513739E+10 | 0.601661E+09 |
August | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.596259E+10 | 0.919939E+09 |
September | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.812032E+10 | 0.183953E+10 |
October | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.956904E+10 | 0.325276E+10 |
November | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.962712E+10 | 0.535804E+10 |
December | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.901998E+10 | 0.703169E+10 |
Annual Sum or Average | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.860747E+11 | 0.416354E+11 |
Minimum of Months | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.457383E+10 | 0.601661E+09 |
Maximum of Months | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.962712E+10 | 0.703169E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429528E+09 | 0.325466E+09 | 0.104062E+09 | 0.556414E+09 | 0.367251E+09 |
February | 0.365011E+09 | 0.258863E+09 | 0.106148E+09 | 0.483961E+09 | 0.291828E+09 |
March | 0.316140E+09 | 0.179109E+09 | 0.137030E+09 | 0.426097E+09 | 0.279611E+09 |
April | 0.213179E+09 | 80025465.26 | 0.133154E+09 | 0.343339E+09 | 0.143572E+09 |
May | 0.156322E+09 | 22925126.41 | 0.133396E+09 | 0.307474E+09 | 68459795.29 |
June | 0.129394E+09 | 8141585.29 | 0.121252E+09 | 0.346563E+09 | 22177673.23 |
July | 0.135783E+09 | 12038590.35 | 0.123744E+09 | 0.361151E+09 | 12910500.38 |
August | 0.171404E+09 | 43548311.75 | 0.127856E+09 | 0.403331E+09 | 26531079.23 |
September | 0.262683E+09 | 0.136477E+09 | 0.126206E+09 | 0.518958E+09 | 75031938.85 |
October | 0.372591E+09 | 0.253142E+09 | 0.119450E+09 | 0.601431E+09 | 0.157623E+09 |
November | 0.433973E+09 | 0.331942E+09 | 0.102031E+09 | 0.600412E+09 | 0.289264E+09 |
December | 0.440964E+09 | 0.331289E+09 | 0.109675E+09 | 0.560695E+09 | 0.395328E+09 |
Annual Sum or Average | 0.342697E+10 | 0.198297E+10 | 0.144400E+10 | 0.550983E+10 | 0.212959E+10 |
Minimum of Months | 0.129394E+09 | 8141585.29 | 0.102031E+09 | 0.307474E+09 | 12910500.38 |
Maximum of Months | 0.440964E+09 | 0.331942E+09 | 0.137030E+09 | 0.601431E+09 | 0.395328E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.330424E+09 | 0.186243E+09 | 0.144180E+09 | 0.319388E+09 | 0.772066E+09 |
February | 0.335937E+09 | 0.178255E+09 | 0.157682E+09 | 0.357354E+09 | 0.610306E+09 |
March | 0.507506E+09 | 0.272127E+09 | 0.235379E+09 | 0.616157E+09 | 0.546431E+09 |
April | 0.563605E+09 | 0.304014E+09 | 0.259591E+09 | 0.859662E+09 | 0.265651E+09 |
May | 0.628494E+09 | 0.336351E+09 | 0.292144E+09 | 0.111731E+10 | 0.127504E+09 |
June | 0.591824E+09 | 0.317774E+09 | 0.274049E+09 | 0.125093E+10 | 41787032.21 |
July | 0.543111E+09 | 0.269860E+09 | 0.273251E+09 | 0.116691E+10 | 23625816.14 |
August | 0.525876E+09 | 0.267919E+09 | 0.257957E+09 | 0.106653E+10 | 49644443.43 |
September | 0.522469E+09 | 0.291669E+09 | 0.230800E+09 | 0.958595E+09 | 0.142879E+09 |
October | 0.465173E+09 | 0.272329E+09 | 0.192844E+09 | 0.706256E+09 | 0.311293E+09 |
November | 0.375612E+09 | 0.228541E+09 | 0.147071E+09 | 0.432207E+09 | 0.607186E+09 |
December | 0.313040E+09 | 0.169961E+09 | 0.143079E+09 | 0.282448E+09 | 0.846618E+09 |
Annual Sum or Average | 0.570307E+10 | 0.309504E+10 | 0.260803E+10 | 0.913375E+10 | 0.434499E+10 |
Minimum of Months | 0.313040E+09 | 0.169961E+09 | 0.143079E+09 | 0.282448E+09 | 23625816.14 |
Maximum of Months | 0.628494E+09 | 0.336351E+09 | 0.292144E+09 | 0.125093E+10 | 0.846618E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62753809.85 | 0.00 | 62753809.85 | 4886508.95 | 0.427485E+09 |
February | 69213320.82 | 0.00 | 69213320.82 | 21112460.34 | 0.340773E+09 |
March | 0.100304E+09 | 3970.73 | 0.100300E+09 | 53797169.57 | 0.315452E+09 |
April | 0.112717E+09 | 1435975.66 | 0.111281E+09 | 0.132123E+09 | 0.152979E+09 |
May | 0.137588E+09 | 10139899.01 | 0.127448E+09 | 0.249612E+09 | 68430534.83 |
June | 0.141594E+09 | 17644380.82 | 0.123950E+09 | 0.358708E+09 | 22436071.35 |
July | 0.135173E+09 | 13259181.16 | 0.121914E+09 | 0.345381E+09 | 13823629.20 |
August | 0.114323E+09 | 2719894.44 | 0.111604E+09 | 0.268322E+09 | 28857098.17 |
September | 96252924.54 | 121649.16 | 96131275.38 | 0.181549E+09 | 83825482.61 |
October | 82444804.21 | 0.00 | 82444804.21 | 88467378.37 | 0.187826E+09 |
November | 64410259.22 | 0.00 | 64410259.22 | 15077332.77 | 0.341375E+09 |
December | 62267831.94 | 0.00 | 62267831.94 | 3644685.73 | 0.470574E+09 |
Annual Sum or Average | 0.117904E+10 | 45324950.99 | 0.113372E+10 | 0.172268E+10 | 0.245384E+10 |
Minimum of Months | 62267831.94 | 0.00 | 62267831.94 | 3644685.73 | 13823629.20 |
Maximum of Months | 0.141594E+09 | 17644380.82 | 0.127448E+09 | 0.358708E+09 | 0.470574E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.330424E+09 | 0.186243E+09 | 0.144180E+09 | 0.335738E+09 | 0.754411E+09 |
February | 0.335937E+09 | 0.178255E+09 | 0.157682E+09 | 0.368622E+09 | 0.607563E+09 |
March | 0.507506E+09 | 0.272127E+09 | 0.235379E+09 | 0.616223E+09 | 0.560814E+09 |
April | 0.563605E+09 | 0.304014E+09 | 0.259591E+09 | 0.854285E+09 | 0.283803E+09 |
May | 0.628494E+09 | 0.336351E+09 | 0.292144E+09 | 0.110722E+10 | 0.138119E+09 |
June | 0.591824E+09 | 0.317774E+09 | 0.274049E+09 | 0.123867E+10 | 44878317.32 |
July | 0.543111E+09 | 0.269860E+09 | 0.273251E+09 | 0.115391E+10 | 27170187.85 |
August | 0.525876E+09 | 0.267919E+09 | 0.257957E+09 | 0.105869E+10 | 56573279.88 |
September | 0.522469E+09 | 0.291669E+09 | 0.230800E+09 | 0.958379E+09 | 0.157452E+09 |
October | 0.465173E+09 | 0.272329E+09 | 0.192844E+09 | 0.707167E+09 | 0.340039E+09 |
November | 0.375612E+09 | 0.228541E+09 | 0.147071E+09 | 0.444948E+09 | 0.605725E+09 |
December | 0.313040E+09 | 0.169961E+09 | 0.143079E+09 | 0.299351E+09 | 0.826708E+09 |
Annual Sum or Average | 0.570307E+10 | 0.309504E+10 | 0.260803E+10 | 0.914320E+10 | 0.440326E+10 |
Minimum of Months | 0.313040E+09 | 0.169961E+09 | 0.143079E+09 | 0.299351E+09 | 27170187.85 |
Maximum of Months | 0.628494E+09 | 0.336351E+09 | 0.292144E+09 | 0.123867E+10 | 0.826708E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.343554E+09 | 0.260321E+09 | 83233276.21 | 0.400135E+09 | 0.399753E+09 |
February | 0.291951E+09 | 0.207050E+09 | 84901543.05 | 0.345911E+09 | 0.325294E+09 |
March | 0.252861E+09 | 0.143259E+09 | 0.109602E+09 | 0.294829E+09 | 0.318094E+09 |
April | 0.170510E+09 | 64007642.82 | 0.106502E+09 | 0.229578E+09 | 0.195488E+09 |
May | 0.125032E+09 | 18336454.50 | 0.106696E+09 | 0.189711E+09 | 0.122019E+09 |
June | 0.103494E+09 | 6511973.18 | 96982365.64 | 0.206941E+09 | 61413851.02 |
July | 0.108605E+09 | 9628957.34 | 98975670.82 | 0.215469E+09 | 54222551.36 |
August | 0.137096E+09 | 34831722.31 | 0.102264E+09 | 0.257344E+09 | 75361869.51 |
September | 0.210104E+09 | 0.109160E+09 | 0.100945E+09 | 0.367066E+09 | 0.128280E+09 |
October | 0.298014E+09 | 0.202473E+09 | 95540760.93 | 0.432100E+09 | 0.211308E+09 |
November | 0.347109E+09 | 0.265501E+09 | 81608843.31 | 0.435111E+09 | 0.327051E+09 |
December | 0.352701E+09 | 0.264979E+09 | 87722444.88 | 0.402099E+09 | 0.419117E+09 |
Annual Sum or Average | 0.274103E+10 | 0.158606E+10 | 0.115497E+10 | 0.377629E+10 | 0.263740E+10 |
Minimum of Months | 0.103494E+09 | 6511973.18 | 81608843.31 | 0.189711E+09 | 54222551.36 |
Maximum of Months | 0.352701E+09 | 0.265501E+09 | 0.109602E+09 | 0.435111E+09 | 0.419117E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50209702.58 | 0.00 | 50209702.58 | 4281975.90 | 0.346622E+09 |
February | 55377996.35 | 0.00 | 55377996.35 | 19054780.22 | 0.273228E+09 |
March | 80253494.35 | 3177.00 | 80250317.34 | 48869388.16 | 0.246296E+09 |
April | 90185743.44 | 1148932.80 | 89036810.63 | 0.116926E+09 | 0.116173E+09 |
May | 0.110085E+09 | 8112994.49 | 0.101972E+09 | 0.215881E+09 | 51169277.25 |
June | 0.113290E+09 | 14117375.75 | 99173041.59 | 0.306294E+09 | 15913111.63 |
July | 0.108153E+09 | 10608751.00 | 97544172.60 | 0.295010E+09 | 9184090.99 |
August | 91470882.32 | 2176203.98 | 89294678.34 | 0.231805E+09 | 20813743.96 |
September | 77012546.73 | 97332.23 | 76915214.50 | 0.157959E+09 | 62897617.18 |
October | 65964586.19 | 0.00 | 65964586.19 | 78506004.28 | 0.142328E+09 |
November | 51535037.73 | 0.00 | 51535037.73 | 14356390.86 | 0.271854E+09 |
December | 49820868.72 | 0.00 | 49820868.72 | 3091270.89 | 0.383175E+09 |
Annual Sum or Average | 0.943359E+09 | 36264767.25 | 0.907094E+09 | 0.149204E+10 | 0.193965E+10 |
Minimum of Months | 49820868.72 | 0.00 | 49820868.72 | 3091270.89 | 9184090.99 |
Maximum of Months | 0.113290E+09 | 14117375.75 | 0.101972E+09 | 0.306294E+09 | 0.383175E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312887E+09 | 0.169539E+09 | 0.143348E+09 | 0.259144E+09 | 0.738585E+09 |
February | 0.379292E+09 | 0.216276E+09 | 0.163016E+09 | 0.389842E+09 | 0.567320E+09 |
March | 0.517601E+09 | 0.284996E+09 | 0.232604E+09 | 0.597379E+09 | 0.500571E+09 |
April | 0.603845E+09 | 0.334914E+09 | 0.268931E+09 | 0.903578E+09 | 0.237092E+09 |
May | 0.643228E+09 | 0.349432E+09 | 0.293796E+09 | 0.113651E+10 | 0.114560E+09 |
June | 0.622742E+09 | 0.346275E+09 | 0.276467E+09 | 0.130371E+10 | 38839203.67 |
July | 0.577458E+09 | 0.301900E+09 | 0.275558E+09 | 0.122659E+10 | 22892999.38 |
August | 0.550079E+09 | 0.281685E+09 | 0.268395E+09 | 0.110993E+10 | 46470678.31 |
September | 0.528145E+09 | 0.301592E+09 | 0.226553E+09 | 0.952470E+09 | 0.129467E+09 |
October | 0.417719E+09 | 0.225006E+09 | 0.192713E+09 | 0.599273E+09 | 0.290055E+09 |
November | 0.361959E+09 | 0.210237E+09 | 0.151722E+09 | 0.365948E+09 | 0.566108E+09 |
December | 0.313124E+09 | 0.165927E+09 | 0.147196E+09 | 0.247614E+09 | 0.810068E+09 |
Annual Sum or Average | 0.582808E+10 | 0.318778E+10 | 0.264030E+10 | 0.909199E+10 | 0.406203E+10 |
Minimum of Months | 0.312887E+09 | 0.165927E+09 | 0.143348E+09 | 0.247614E+09 | 22892999.38 |
Maximum of Months | 0.643228E+09 | 0.349432E+09 | 0.293796E+09 | 0.130371E+10 | 0.810068E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429528E+09 | 0.325466E+09 | 0.104062E+09 | 0.552937E+09 | 0.365223E+09 |
February | 0.365011E+09 | 0.258863E+09 | 0.106148E+09 | 0.478795E+09 | 0.290478E+09 |
March | 0.316140E+09 | 0.179109E+09 | 0.137030E+09 | 0.420945E+09 | 0.277846E+09 |
April | 0.213179E+09 | 80025465.26 | 0.133154E+09 | 0.339283E+09 | 0.143400E+09 |
May | 0.156322E+09 | 22925126.41 | 0.133396E+09 | 0.304706E+09 | 68267928.89 |
June | 0.129394E+09 | 8141585.29 | 0.121252E+09 | 0.343890E+09 | 21747765.71 |
July | 0.135783E+09 | 12038590.35 | 0.123744E+09 | 0.358839E+09 | 12523087.53 |
August | 0.171404E+09 | 43548311.75 | 0.127856E+09 | 0.401439E+09 | 26225363.59 |
September | 0.262683E+09 | 0.136477E+09 | 0.126206E+09 | 0.516724E+09 | 74124376.19 |
October | 0.372591E+09 | 0.253142E+09 | 0.119450E+09 | 0.599688E+09 | 0.155141E+09 |
November | 0.433973E+09 | 0.331942E+09 | 0.102031E+09 | 0.597562E+09 | 0.286908E+09 |
December | 0.440964E+09 | 0.331289E+09 | 0.109675E+09 | 0.556764E+09 | 0.393827E+09 |
Annual Sum or Average | 0.342697E+10 | 0.198297E+10 | 0.144400E+10 | 0.547157E+10 | 0.211571E+10 |
Minimum of Months | 0.129394E+09 | 8141585.29 | 0.102031E+09 | 0.304706E+09 | 12523087.53 |
Maximum of Months | 0.440964E+09 | 0.331942E+09 | 0.137030E+09 | 0.599688E+09 | 0.393827E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62753809.85 | 0.00 | 62753809.85 | 3626186.66 | 0.427485E+09 |
February | 69213320.82 | 0.00 | 69213320.82 | 18898887.44 | 0.341345E+09 |
March | 0.100304E+09 | 3970.73 | 0.100300E+09 | 51066906.91 | 0.310618E+09 |
April | 0.112717E+09 | 1435975.66 | 0.111281E+09 | 0.127205E+09 | 0.150340E+09 |
May | 0.137588E+09 | 10139899.01 | 0.127448E+09 | 0.241836E+09 | 67405386.75 |
June | 0.141594E+09 | 17644380.82 | 0.123950E+09 | 0.352539E+09 | 22073105.61 |
July | 0.135173E+09 | 13259181.16 | 0.121914E+09 | 0.339905E+09 | 13482482.40 |
August | 0.114323E+09 | 2719894.44 | 0.111604E+09 | 0.263078E+09 | 28468891.26 |
September | 96252924.54 | 121649.16 | 96131275.38 | 0.176559E+09 | 83815513.85 |
October | 82444804.21 | 0.00 | 82444804.21 | 86720417.68 | 0.179374E+09 |
November | 64410259.22 | 0.00 | 64410259.22 | 12879917.78 | 0.338800E+09 |
December | 62267831.94 | 0.00 | 62267831.94 | 2697313.01 | 0.471195E+09 |
Annual Sum or Average | 0.117904E+10 | 45324950.99 | 0.113372E+10 | 0.167701E+10 | 0.243440E+10 |
Minimum of Months | 62267831.94 | 0.00 | 62267831.94 | 2697313.01 | 13482482.40 |
Maximum of Months | 0.141594E+09 | 17644380.82 | 0.127448E+09 | 0.352539E+09 | 0.471195E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312887E+09 | 0.169539E+09 | 0.143348E+09 | 0.269981E+09 | 0.714147E+09 |
February | 0.379292E+09 | 0.216276E+09 | 0.163016E+09 | 0.400236E+09 | 0.561307E+09 |
March | 0.517601E+09 | 0.284996E+09 | 0.232604E+09 | 0.604097E+09 | 0.509382E+09 |
April | 0.603845E+09 | 0.334914E+09 | 0.268931E+09 | 0.897777E+09 | 0.251662E+09 |
May | 0.643228E+09 | 0.349432E+09 | 0.293796E+09 | 0.111427E+10 | 0.123124E+09 |
June | 0.622742E+09 | 0.346275E+09 | 0.276467E+09 | 0.128115E+10 | 41120529.33 |
July | 0.577458E+09 | 0.301900E+09 | 0.275558E+09 | 0.120458E+10 | 25857971.14 |
August | 0.550079E+09 | 0.281685E+09 | 0.268395E+09 | 0.109194E+10 | 51785700.49 |
September | 0.528145E+09 | 0.301592E+09 | 0.226553E+09 | 0.940313E+09 | 0.141136E+09 |
October | 0.417719E+09 | 0.225006E+09 | 0.192713E+09 | 0.604442E+09 | 0.310405E+09 |
November | 0.361959E+09 | 0.210237E+09 | 0.151722E+09 | 0.376726E+09 | 0.560160E+09 |
December | 0.313124E+09 | 0.165927E+09 | 0.147196E+09 | 0.257575E+09 | 0.780914E+09 |
Annual Sum or Average | 0.582808E+10 | 0.318778E+10 | 0.264030E+10 | 0.904308E+10 | 0.407100E+10 |
Minimum of Months | 0.312887E+09 | 0.165927E+09 | 0.143348E+09 | 0.257575E+09 | 25857971.14 |
Maximum of Months | 0.643228E+09 | 0.349432E+09 | 0.293796E+09 | 0.128115E+10 | 0.780914E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 79473740.63 | 0.00 | 79473740.63 | 1676519.63 | 0.666293E+09 |
February | 87654303.70 | 0.00 | 87654303.70 | 18463134.64 | 0.520408E+09 |
March | 0.127028E+09 | 5028.68 | 0.127023E+09 | 57615180.78 | 0.465851E+09 |
April | 0.142749E+09 | 1818572.57 | 0.140931E+09 | 0.158116E+09 | 0.232965E+09 |
May | 0.174247E+09 | 12841542.31 | 0.161405E+09 | 0.304679E+09 | 0.116947E+09 |
June | 0.179320E+09 | 22345495.01 | 0.156975E+09 | 0.437510E+09 | 47894708.63 |
July | 0.171188E+09 | 16791916.34 | 0.154396E+09 | 0.417862E+09 | 35508458.60 |
August | 0.144783E+09 | 3444574.69 | 0.141339E+09 | 0.322320E+09 | 59515872.38 |
September | 0.121898E+09 | 154060.98 | 0.121744E+09 | 0.222164E+09 | 0.137556E+09 |
October | 0.104411E+09 | 0.00 | 0.104411E+09 | 0.100739E+09 | 0.275233E+09 |
November | 81571529.24 | 0.00 | 81571529.24 | 10923302.79 | 0.523250E+09 |
December | 78858280.27 | 0.00 | 78858280.27 | 1192611.52 | 0.726164E+09 |
Annual Sum or Average | 0.149318E+10 | 57401190.58 | 0.143578E+10 | 0.205326E+10 | 0.380759E+10 |
Minimum of Months | 78858280.27 | 0.00 | 78858280.27 | 1192611.52 | 35508458.60 |
Maximum of Months | 0.179320E+09 | 22345495.01 | 0.161405E+09 | 0.437510E+09 | 0.726164E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 29297311.54 | 0.00 | 29297311.54 | 618034.55 | 0.245623E+09 |
February | 32313005.82 | 0.00 | 32313005.82 | 6806275.93 | 0.191844E+09 |
March | 46827834.18 | 1853.78 | 46825980.40 | 21239341.29 | 0.171732E+09 |
April | 52623291.65 | 670401.15 | 51952890.50 | 58288111.80 | 85880499.35 |
May | 64234514.90 | 4733924.22 | 59500590.68 | 0.112317E+09 | 43111582.56 |
June | 66104845.90 | 8237474.72 | 57867371.19 | 0.161284E+09 | 17655972.77 |
July | 63107123.41 | 6190195.66 | 56916927.75 | 0.154041E+09 | 13089888.13 |
August | 53373168.91 | 1269812.86 | 52103356.05 | 0.118821E+09 | 21940014.92 |
September | 44936744.46 | 56793.26 | 44879951.21 | 81898708.45 | 50708832.12 |
October | 38490270.47 | 0.00 | 38490270.47 | 37136426.36 | 0.101462E+09 |
November | 30070643.29 | 0.00 | 30070643.29 | 4026781.71 | 0.192892E+09 |
December | 29070427.37 | 0.00 | 29070427.37 | 439645.99 | 0.267694E+09 |
Annual Sum or Average | 0.550449E+09 | 21160455.64 | 0.529289E+09 | 0.756916E+09 | 0.140363E+10 |
Minimum of Months | 29070427.37 | 0.00 | 29070427.37 | 439645.99 | 13089888.13 |
Maximum of Months | 66104845.90 | 8237474.72 | 59500590.68 | 0.161284E+09 | 0.267694E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.200416E+09 | 0.151861E+09 | 48555043.46 | 0.252662E+09 | 0.202619E+09 |
February | 0.170313E+09 | 0.120785E+09 | 49528245.20 | 0.219636E+09 | 0.162073E+09 |
March | 0.147509E+09 | 83571664.90 | 63937771.11 | 0.192474E+09 | 0.156133E+09 |
April | 99468670.55 | 37339559.61 | 62129110.93 | 0.155534E+09 | 86414229.10 |
May | 72939025.15 | 10696771.60 | 62242253.55 | 0.137299E+09 | 46587878.32 |
June | 60374556.29 | 3798830.89 | 56575725.40 | 0.152565E+09 | 18644855.99 |
July | 63355699.56 | 5617157.75 | 57738541.81 | 0.158175E+09 | 13917123.89 |
August | 79976362.75 | 20319466.78 | 59656895.97 | 0.179768E+09 | 22891112.47 |
September | 0.122567E+09 | 63679450.00 | 58887306.05 | 0.238142E+09 | 49891941.65 |
October | 0.173850E+09 | 0.118115E+09 | 55734749.50 | 0.275615E+09 | 93772320.74 |
November | 0.202490E+09 | 0.154883E+09 | 47607412.73 | 0.274152E+09 | 0.161285E+09 |
December | 0.205752E+09 | 0.154578E+09 | 51173849.19 | 0.253756E+09 | 0.215456E+09 |
Annual Sum or Average | 0.159901E+10 | 0.925244E+09 | 0.673767E+09 | 0.248978E+10 | 0.122969E+10 |
Minimum of Months | 60374556.29 | 3798830.89 | 47607412.73 | 0.137299E+09 | 13917123.89 |
Maximum of Months | 0.205752E+09 | 0.154883E+09 | 63937771.11 | 0.275615E+09 | 0.215456E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.543970E+09 | 0.412182E+09 | 0.131788E+09 | 0.685776E+09 | 0.549950E+09 |
February | 0.462264E+09 | 0.327834E+09 | 0.134430E+09 | 0.596137E+09 | 0.439899E+09 |
March | 0.400371E+09 | 0.226831E+09 | 0.173540E+09 | 0.522413E+09 | 0.423778E+09 |
April | 0.269978E+09 | 0.101347E+09 | 0.168631E+09 | 0.422151E+09 | 0.234546E+09 |
May | 0.197971E+09 | 29033226.10 | 0.168938E+09 | 0.372659E+09 | 0.126449E+09 |
June | 0.163869E+09 | 10310804.07 | 0.153558E+09 | 0.414092E+09 | 50605952.87 |
July | 0.171960E+09 | 15246115.09 | 0.156714E+09 | 0.429318E+09 | 37773920.93 |
August | 0.217072E+09 | 55151189.09 | 0.161921E+09 | 0.487928E+09 | 62131161.52 |
September | 0.332671E+09 | 0.172839E+09 | 0.159832E+09 | 0.646365E+09 | 0.135417E+09 |
October | 0.471864E+09 | 0.320588E+09 | 0.151276E+09 | 0.748077E+09 | 0.254517E+09 |
November | 0.549599E+09 | 0.420383E+09 | 0.129216E+09 | 0.744104E+09 | 0.437761E+09 |
December | 0.558453E+09 | 0.419557E+09 | 0.138896E+09 | 0.688744E+09 | 0.584791E+09 |
Annual Sum or Average | 0.434004E+10 | 0.251130E+10 | 0.182874E+10 | 0.675776E+10 | 0.333762E+10 |
Minimum of Months | 0.163869E+09 | 10310804.07 | 0.129216E+09 | 0.372659E+09 | 37773920.93 |
Maximum of Months | 0.558453E+09 | 0.420383E+09 | 0.173540E+09 | 0.748077E+09 | 0.584791E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429528E+09 | 0.325466E+09 | 0.104062E+09 | 0.554589E+09 | 0.355787E+09 |
February | 0.365011E+09 | 0.258863E+09 | 0.106148E+09 | 0.481094E+09 | 0.283249E+09 |
March | 0.316140E+09 | 0.179109E+09 | 0.137030E+09 | 0.421249E+09 | 0.271890E+09 |
April | 0.213179E+09 | 80025465.26 | 0.133154E+09 | 0.337376E+09 | 0.138356E+09 |
May | 0.156322E+09 | 22925126.41 | 0.133396E+09 | 0.302672E+09 | 64746722.27 |
June | 0.129394E+09 | 8141585.29 | 0.121252E+09 | 0.342168E+09 | 20497953.36 |
July | 0.135783E+09 | 12038590.35 | 0.123744E+09 | 0.355581E+09 | 11804838.77 |
August | 0.171404E+09 | 43548311.75 | 0.127856E+09 | 0.397282E+09 | 24697876.51 |
September | 0.262683E+09 | 0.136477E+09 | 0.126206E+09 | 0.511475E+09 | 71687134.94 |
October | 0.372591E+09 | 0.253142E+09 | 0.119450E+09 | 0.595252E+09 | 0.152431E+09 |
November | 0.433973E+09 | 0.331942E+09 | 0.102031E+09 | 0.597391E+09 | 0.280110E+09 |
December | 0.440964E+09 | 0.331289E+09 | 0.109675E+09 | 0.561045E+09 | 0.383035E+09 |
Annual Sum or Average | 0.342697E+10 | 0.198297E+10 | 0.144400E+10 | 0.545717E+10 | 0.205829E+10 |
Minimum of Months | 0.129394E+09 | 8141585.29 | 0.102031E+09 | 0.302672E+09 | 11804838.77 |
Maximum of Months | 0.440964E+09 | 0.331942E+09 | 0.137030E+09 | 0.597391E+09 | 0.383035E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.330424E+09 | 0.186243E+09 | 0.144180E+09 | 0.316344E+09 | 0.744608E+09 |
February | 0.335937E+09 | 0.178255E+09 | 0.157682E+09 | 0.352602E+09 | 0.589684E+09 |
March | 0.507506E+09 | 0.272127E+09 | 0.235379E+09 | 0.606727E+09 | 0.528897E+09 |
April | 0.563605E+09 | 0.304014E+09 | 0.259591E+09 | 0.846674E+09 | 0.255213E+09 |
May | 0.628494E+09 | 0.336351E+09 | 0.292144E+09 | 0.110174E+10 | 0.120382E+09 |
June | 0.591824E+09 | 0.317774E+09 | 0.274049E+09 | 0.123592E+10 | 38800237.77 |
July | 0.543111E+09 | 0.269860E+09 | 0.273251E+09 | 0.115161E+10 | 21540722.56 |
August | 0.525876E+09 | 0.267919E+09 | 0.257957E+09 | 0.105233E+10 | 46232443.31 |
September | 0.522469E+09 | 0.291669E+09 | 0.230800E+09 | 0.944957E+09 | 0.136268E+09 |
October | 0.465173E+09 | 0.272329E+09 | 0.192844E+09 | 0.697211E+09 | 0.299257E+09 |
November | 0.375612E+09 | 0.228541E+09 | 0.147071E+09 | 0.427504E+09 | 0.585328E+09 |
December | 0.313040E+09 | 0.169961E+09 | 0.143079E+09 | 0.281320E+09 | 0.815318E+09 |
Annual Sum or Average | 0.570307E+10 | 0.309504E+10 | 0.260803E+10 | 0.901495E+10 | 0.418153E+10 |
Minimum of Months | 0.313040E+09 | 0.169961E+09 | 0.143079E+09 | 0.281320E+09 | 21540722.56 |
Maximum of Months | 0.628494E+09 | 0.336351E+09 | 0.292144E+09 | 0.123592E+10 | 0.815318E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62753809.85 | 0.00 | 62753809.85 | 6199557.94 | 0.410726E+09 |
February | 69213320.82 | 0.00 | 69213320.82 | 21785998.59 | 0.329027E+09 |
March | 0.100304E+09 | 3970.73 | 0.100300E+09 | 53482805.13 | 0.307802E+09 |
April | 0.112717E+09 | 1435975.66 | 0.111281E+09 | 0.129181E+09 | 0.149177E+09 |
May | 0.137588E+09 | 10139899.01 | 0.127448E+09 | 0.245895E+09 | 65483745.95 |
June | 0.141594E+09 | 17644380.82 | 0.123950E+09 | 0.353560E+09 | 20986786.00 |
July | 0.135173E+09 | 13259181.16 | 0.121914E+09 | 0.339523E+09 | 12867467.07 |
August | 0.114323E+09 | 2719894.44 | 0.111604E+09 | 0.263803E+09 | 27236712.31 |
September | 96252924.54 | 121649.16 | 96131275.38 | 0.177199E+09 | 80556058.41 |
October | 82444804.21 | 0.00 | 82444804.21 | 86538886.03 | 0.184121E+09 |
November | 64410259.22 | 0.00 | 64410259.22 | 15623896.53 | 0.329861E+09 |
December | 62267831.94 | 0.00 | 62267831.94 | 4632658.66 | 0.451363E+09 |
Annual Sum or Average | 0.117904E+10 | 45324950.99 | 0.113372E+10 | 0.169743E+10 | 0.236921E+10 |
Minimum of Months | 62267831.94 | 0.00 | 62267831.94 | 4632658.66 | 12867467.07 |
Maximum of Months | 0.141594E+09 | 17644380.82 | 0.127448E+09 | 0.353560E+09 | 0.451363E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.330424E+09 | 0.186243E+09 | 0.144180E+09 | 0.337144E+09 | 0.724780E+09 |
February | 0.335937E+09 | 0.178255E+09 | 0.157682E+09 | 0.366639E+09 | 0.586006E+09 |
March | 0.507506E+09 | 0.272127E+09 | 0.235379E+09 | 0.607452E+09 | 0.545229E+09 |
April | 0.563605E+09 | 0.304014E+09 | 0.259591E+09 | 0.840731E+09 | 0.275434E+09 |
May | 0.628494E+09 | 0.336351E+09 | 0.292144E+09 | 0.109155E+10 | 0.131349E+09 |
June | 0.591824E+09 | 0.317774E+09 | 0.274049E+09 | 0.122353E+10 | 41727752.95 |
July | 0.543111E+09 | 0.269860E+09 | 0.273251E+09 | 0.113827E+10 | 25062004.77 |
August | 0.525876E+09 | 0.267919E+09 | 0.257957E+09 | 0.104432E+10 | 53095563.55 |
September | 0.522469E+09 | 0.291669E+09 | 0.230800E+09 | 0.944976E+09 | 0.151119E+09 |
October | 0.465173E+09 | 0.272329E+09 | 0.192844E+09 | 0.697940E+09 | 0.331720E+09 |
November | 0.375612E+09 | 0.228541E+09 | 0.147071E+09 | 0.442722E+09 | 0.583260E+09 |
December | 0.313040E+09 | 0.169961E+09 | 0.143079E+09 | 0.303032E+09 | 0.793501E+09 |
Annual Sum or Average | 0.570307E+10 | 0.309504E+10 | 0.260803E+10 | 0.903830E+10 | 0.424228E+10 |
Minimum of Months | 0.313040E+09 | 0.169961E+09 | 0.143079E+09 | 0.303032E+09 | 25062004.77 |
Maximum of Months | 0.628494E+09 | 0.336351E+09 | 0.292144E+09 | 0.122353E+10 | 0.793501E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.629944E+09 | 0.477327E+09 | 0.152617E+09 | 0.791388E+09 | 0.542730E+09 |
February | 0.535324E+09 | 0.379648E+09 | 0.155676E+09 | 0.689665E+09 | 0.429102E+09 |
March | 0.463649E+09 | 0.262681E+09 | 0.200968E+09 | 0.609281E+09 | 0.404110E+09 |
April | 0.312648E+09 | 0.117365E+09 | 0.195283E+09 | 0.500610E+09 | 0.200717E+09 |
May | 0.229261E+09 | 33621898.01 | 0.195639E+09 | 0.462057E+09 | 92117691.53 |
June | 0.189768E+09 | 11940416.18 | 0.177828E+09 | 0.524759E+09 | 28325532.63 |
July | 0.199138E+09 | 17655748.10 | 0.181483E+09 | 0.542497E+09 | 15847326.32 |
August | 0.251380E+09 | 63867778.53 | 0.187512E+09 | 0.598870E+09 | 34784293.92 |
September | 0.385250E+09 | 0.200156E+09 | 0.185094E+09 | 0.756769E+09 | 0.103376E+09 |
October | 0.546441E+09 | 0.371257E+09 | 0.175184E+09 | 0.868353E+09 | 0.225855E+09 |
November | 0.636463E+09 | 0.486824E+09 | 0.149639E+09 | 0.860111E+09 | 0.424569E+09 |
December | 0.646716E+09 | 0.485868E+09 | 0.160849E+09 | 0.798061E+09 | 0.584290E+09 |
Annual Sum or Average | 0.502598E+10 | 0.290821E+10 | 0.211777E+10 | 0.800242E+10 | 0.308582E+10 |
Minimum of Months | 0.189768E+09 | 11940416.18 | 0.149639E+09 | 0.462057E+09 | 15847326.32 |
Maximum of Months | 0.646716E+09 | 0.486824E+09 | 0.200968E+09 | 0.868353E+09 | 0.584290E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.439260E+09 | 0.00 | 0.439260E+09 | 12081239.61 | 0.357751E+10 |
February | 0.484475E+09 | 0.00 | 0.484475E+09 | 96879023.89 | 0.283293E+10 |
March | 0.702098E+09 | 27794.05 | 0.702071E+09 | 0.292548E+09 | 0.258870E+10 |
April | 0.788991E+09 | 10051448.91 | 0.778939E+09 | 0.790759E+09 | 0.134760E+10 |
May | 0.963080E+09 | 70976604.89 | 0.892103E+09 | 0.154600E+10 | 0.713246E+09 |
June | 0.991122E+09 | 0.123506E+09 | 0.867616E+09 | 0.224973E+10 | 0.318879E+09 |
July | 0.946177E+09 | 92810752.99 | 0.853366E+09 | 0.213850E+10 | 0.255112E+09 |
August | 0.800234E+09 | 19038540.01 | 0.781195E+09 | 0.163685E+10 | 0.393439E+09 |
September | 0.673745E+09 | 851511.84 | 0.672893E+09 | 0.113226E+10 | 0.818891E+09 |
October | 0.577092E+09 | 0.00 | 0.577092E+09 | 0.506044E+09 | 0.157415E+10 |
November | 0.450855E+09 | 0.00 | 0.450855E+09 | 56731519.08 | 0.285438E+10 |
December | 0.435858E+09 | 0.00 | 0.435858E+09 | 8633472.43 | 0.385015E+10 |
Annual Sum or Average | 0.825299E+10 | 0.317263E+09 | 0.793572E+10 | 0.104670E+11 | 0.211250E+11 |
Minimum of Months | 0.435858E+09 | 0.00 | 0.435858E+09 | 8633472.43 | 0.255112E+09 |
Maximum of Months | 0.991122E+09 | 0.123506E+09 | 0.892103E+09 | 0.224973E+10 | 0.385015E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.439260E+09 | 0.00 | 0.439260E+09 | 8186585.38 | 0.369642E+10 |
February | 0.484475E+09 | 0.00 | 0.484475E+09 | 83744537.30 | 0.291628E+10 |
March | 0.702098E+09 | 27794.05 | 0.702071E+09 | 0.265908E+09 | 0.265680E+10 |
April | 0.788991E+09 | 10051448.91 | 0.778939E+09 | 0.761239E+09 | 0.138387E+10 |
May | 0.963080E+09 | 70976604.89 | 0.892103E+09 | 0.151254E+10 | 0.736047E+09 |
June | 0.991122E+09 | 0.123506E+09 | 0.867616E+09 | 0.221745E+10 | 0.332240E+09 |
July | 0.946177E+09 | 92810752.99 | 0.853366E+09 | 0.210496E+10 | 0.269048E+09 |
August | 0.800234E+09 | 19038540.01 | 0.781195E+09 | 0.160460E+10 | 0.411124E+09 |
September | 0.673745E+09 | 851511.84 | 0.672893E+09 | 0.110703E+10 | 0.844632E+09 |
October | 0.577092E+09 | 0.00 | 0.577092E+09 | 0.479457E+09 | 0.161685E+10 |
November | 0.450855E+09 | 0.00 | 0.450855E+09 | 45887337.38 | 0.294249E+10 |
December | 0.435858E+09 | 0.00 | 0.435858E+09 | 5262233.79 | 0.397981E+10 |
Annual Sum or Average | 0.825299E+10 | 0.317263E+09 | 0.793572E+10 | 0.101963E+11 | 0.217856E+11 |
Minimum of Months | 0.435858E+09 | 0.00 | 0.435858E+09 | 5262233.79 | 0.269048E+09 |
Maximum of Months | 0.991122E+09 | 0.123506E+09 | 0.892103E+09 | 0.221745E+10 | 0.397981E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62753809.85 | 0.00 | 62753809.85 | 699325.59 | 0.544793E+09 |
February | 69213320.82 | 0.00 | 69213320.82 | 12483960.99 | 0.428954E+09 |
March | 0.100304E+09 | 3970.73 | 0.100300E+09 | 37767103.73 | 0.393623E+09 |
April | 0.112717E+09 | 1435975.66 | 0.111281E+09 | 0.119221E+09 | 0.209747E+09 |
May | 0.137588E+09 | 10139899.01 | 0.127448E+09 | 0.232532E+09 | 0.119393E+09 |
June | 0.141594E+09 | 17644380.82 | 0.123950E+09 | 0.339732E+09 | 58899923.92 |
July | 0.135173E+09 | 13259181.16 | 0.121914E+09 | 0.327698E+09 | 50700653.28 |
August | 0.114323E+09 | 2719894.44 | 0.111604E+09 | 0.254550E+09 | 70829151.06 |
September | 96252924.54 | 121649.16 | 96131275.38 | 0.181850E+09 | 0.126925E+09 |
October | 82444804.21 | 0.00 | 82444804.21 | 78451084.54 | 0.239153E+09 |
November | 64410259.22 | 0.00 | 64410259.22 | 7469916.50 | 0.431252E+09 |
December | 62267831.94 | 0.00 | 62267831.94 | 662377.54 | 0.582268E+09 |
Annual Sum or Average | 0.117904E+10 | 45324950.99 | 0.113372E+10 | 0.159312E+10 | 0.325654E+10 |
Minimum of Months | 62267831.94 | 0.00 | 62267831.94 | 662377.54 | 50700653.28 |
Maximum of Months | 0.141594E+09 | 17644380.82 | 0.127448E+09 | 0.339732E+09 | 0.582268E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.625731E+09 | 0.339055E+09 | 0.286676E+09 | 0.483946E+09 | 0.181817E+10 |
February | 0.758529E+09 | 0.432521E+09 | 0.326008E+09 | 0.746833E+09 | 0.141713E+10 |
March | 0.103513E+10 | 0.569952E+09 | 0.465175E+09 | 0.113098E+10 | 0.128596E+10 |
April | 0.120760E+10 | 0.669781E+09 | 0.537823E+09 | 0.175065E+10 | 0.707547E+09 |
May | 0.128636E+10 | 0.698815E+09 | 0.587549E+09 | 0.219037E+10 | 0.435185E+09 |
June | 0.124540E+10 | 0.692501E+09 | 0.552895E+09 | 0.250926E+10 | 0.220937E+09 |
July | 0.115483E+10 | 0.603758E+09 | 0.551077E+09 | 0.235566E+10 | 0.192595E+09 |
August | 0.110008E+10 | 0.563330E+09 | 0.536751E+09 | 0.214899E+10 | 0.262816E+09 |
September | 0.105622E+10 | 0.603142E+09 | 0.453073E+09 | 0.190142E+10 | 0.445031E+09 |
October | 0.835379E+09 | 0.449980E+09 | 0.385399E+09 | 0.116344E+10 | 0.829965E+09 |
November | 0.723866E+09 | 0.420444E+09 | 0.303423E+09 | 0.699876E+09 | 0.142735E+10 |
December | 0.626203E+09 | 0.331831E+09 | 0.294371E+09 | 0.464678E+09 | 0.193591E+10 |
Annual Sum or Average | 0.116553E+11 | 0.637511E+10 | 0.528022E+10 | 0.175461E+11 | 0.109786E+11 |
Minimum of Months | 0.625731E+09 | 0.331831E+09 | 0.286676E+09 | 0.464678E+09 | 0.192595E+09 |
Maximum of Months | 0.128636E+10 | 0.698815E+09 | 0.587549E+09 | 0.250926E+10 | 0.193591E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429528E+09 | 0.325466E+09 | 0.104062E+09 | 0.540286E+09 | 0.447966E+09 |
February | 0.365011E+09 | 0.258863E+09 | 0.106148E+09 | 0.468342E+09 | 0.362841E+09 |
March | 0.316140E+09 | 0.179109E+09 | 0.137030E+09 | 0.403506E+09 | 0.353387E+09 |
April | 0.213179E+09 | 80025465.26 | 0.133154E+09 | 0.324512E+09 | 0.209391E+09 |
May | 0.156322E+09 | 22925126.41 | 0.133396E+09 | 0.282242E+09 | 0.126832E+09 |
June | 0.129394E+09 | 8141585.29 | 0.121252E+09 | 0.319093E+09 | 60859296.44 |
July | 0.135783E+09 | 12038590.35 | 0.123744E+09 | 0.335224E+09 | 52626279.54 |
August | 0.171404E+09 | 43548311.75 | 0.127856E+09 | 0.385006E+09 | 72857233.98 |
September | 0.262683E+09 | 0.136477E+09 | 0.126206E+09 | 0.516842E+09 | 0.125458E+09 |
October | 0.372591E+09 | 0.253142E+09 | 0.119450E+09 | 0.591842E+09 | 0.221188E+09 |
November | 0.433973E+09 | 0.331942E+09 | 0.102031E+09 | 0.589166E+09 | 0.359255E+09 |
December | 0.440964E+09 | 0.331289E+09 | 0.109675E+09 | 0.546315E+09 | 0.469581E+09 |
Annual Sum or Average | 0.342697E+10 | 0.198297E+10 | 0.144400E+10 | 0.530238E+10 | 0.286224E+10 |
Minimum of Months | 0.129394E+09 | 8141585.29 | 0.102031E+09 | 0.282242E+09 | 52626279.54 |
Maximum of Months | 0.440964E+09 | 0.331942E+09 | 0.137030E+09 | 0.591842E+09 | 0.469581E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 79473740.63 | 0.00 | 79473740.63 | 1396956.55 | 0.638266E+09 |
February | 87654303.70 | 0.00 | 87654303.70 | 15822119.67 | 0.506597E+09 |
March | 0.127028E+09 | 5028.68 | 0.127023E+09 | 51357814.26 | 0.459742E+09 |
April | 0.142749E+09 | 1818572.57 | 0.140931E+09 | 0.145398E+09 | 0.235733E+09 |
May | 0.174247E+09 | 12841542.31 | 0.161405E+09 | 0.287059E+09 | 0.120927E+09 |
June | 0.179320E+09 | 22345495.01 | 0.156975E+09 | 0.415687E+09 | 51794691.70 |
July | 0.171188E+09 | 16791916.34 | 0.154396E+09 | 0.394859E+09 | 40089993.50 |
August | 0.144783E+09 | 3444574.69 | 0.141339E+09 | 0.302058E+09 | 64441055.93 |
September | 0.121898E+09 | 154060.98 | 0.121744E+09 | 0.206212E+09 | 0.142674E+09 |
October | 0.104411E+09 | 0.00 | 0.104411E+09 | 89557205.20 | 0.279896E+09 |
November | 81571529.24 | 0.00 | 81571529.24 | 8350957.79 | 0.511935E+09 |
December | 78858280.27 | 0.00 | 78858280.27 | 1103785.58 | 0.680621E+09 |
Annual Sum or Average | 0.149318E+10 | 57401190.58 | 0.143578E+10 | 0.191886E+10 | 0.373272E+10 |
Minimum of Months | 78858280.27 | 0.00 | 78858280.27 | 1103785.58 | 40089993.50 |
Maximum of Months | 0.179320E+09 | 22345495.01 | 0.161405E+09 | 0.415687E+09 | 0.680621E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71105456.86 | 0.00 | 71105456.86 | 1249862.32 | 0.571059E+09 |
February | 78424637.64 | 0.00 | 78424637.64 | 14156110.42 | 0.453254E+09 |
March | 0.113653E+09 | 4499.18 | 0.113648E+09 | 45950031.02 | 0.411333E+09 |
April | 0.127718E+09 | 1627083.77 | 0.126091E+09 | 0.130088E+09 | 0.210911E+09 |
May | 0.155899E+09 | 11489376.56 | 0.144410E+09 | 0.256833E+09 | 0.108194E+09 |
June | 0.160438E+09 | 19992599.05 | 0.140446E+09 | 0.371917E+09 | 46340906.92 |
July | 0.153163E+09 | 15023791.17 | 0.138139E+09 | 0.353282E+09 | 35868669.08 |
August | 0.129538E+09 | 3081874.03 | 0.126456E+09 | 0.270253E+09 | 57655656.91 |
September | 0.109063E+09 | 137838.94 | 0.108925E+09 | 0.184499E+09 | 0.127651E+09 |
October | 93417044.86 | 0.00 | 93417044.86 | 80127170.82 | 0.250424E+09 |
November | 72982356.28 | 0.00 | 72982356.28 | 7471633.58 | 0.458029E+09 |
December | 70554802.15 | 0.00 | 70554802.15 | 987561.14 | 0.608931E+09 |
Annual Sum or Average | 0.133596E+10 | 51357062.70 | 0.128460E+10 | 0.171681E+10 | 0.333965E+10 |
Minimum of Months | 70554802.15 | 0.00 | 70554802.15 | 987561.14 | 35868669.08 |
Maximum of Months | 0.160438E+09 | 19992599.05 | 0.144410E+09 | 0.371917E+09 | 0.608931E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160356E+10 | 0.121506E+10 | 0.388496E+09 | 0.200988E+10 | 0.154772E+10 |
February | 0.136270E+10 | 0.966414E+09 | 0.396282E+09 | 0.173602E+10 | 0.126167E+10 |
March | 0.118024E+10 | 0.668668E+09 | 0.511575E+09 | 0.150057E+10 | 0.122990E+10 |
April | 0.795862E+09 | 0.298759E+09 | 0.497103E+09 | 0.119445E+10 | 0.699573E+09 |
May | 0.583595E+09 | 85586328.24 | 0.498009E+09 | 0.104425E+10 | 0.385936E+09 |
June | 0.483065E+09 | 30394963.97 | 0.452670E+09 | 0.115873E+10 | 0.161283E+09 |
July | 0.506918E+09 | 44943645.10 | 0.461974E+09 | 0.119830E+10 | 0.126122E+09 |
August | 0.639902E+09 | 0.162579E+09 | 0.477323E+09 | 0.137398E+10 | 0.199036E+09 |
September | 0.980673E+09 | 0.509508E+09 | 0.471165E+09 | 0.184739E+10 | 0.414902E+09 |
October | 0.139100E+10 | 0.945054E+09 | 0.445941E+09 | 0.215268E+10 | 0.761253E+09 |
November | 0.162015E+10 | 0.123924E+10 | 0.380913E+09 | 0.216744E+10 | 0.125464E+10 |
December | 0.164625E+10 | 0.123680E+10 | 0.409449E+09 | 0.203757E+10 | 0.161418E+10 |
Annual Sum or Average | 0.127939E+11 | 0.740301E+10 | 0.539090E+10 | 0.194212E+11 | 0.965622E+10 |
Minimum of Months | 0.483065E+09 | 30394963.97 | 0.380913E+09 | 0.104425E+10 | 0.126122E+09 |
Maximum of Months | 0.164625E+10 | 0.123924E+10 | 0.511575E+09 | 0.216744E+10 | 0.161418E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 912.05 | 598.78 | 706.15 | 535.07 | 171.08 | 0.00 | 0.00 |
February | 876.11 | 534.12 | 664.38 | 471.17 | 193.21 | 0.00 | 0.00 |
March | 700.18 | 469.26 | 519.74 | 294.46 | 225.28 | 0.00 | 0.00 |
April | 561.70 | 280.59 | 362.15 | 135.95 | 226.20 | 0.00 | 0.00 |
May | 454.36 | 157.69 | 257.00 | 37.69 | 219.31 | 0.00 | 0.00 |
June | 496.39 | 72.86 | 219.82 | 13.83 | 205.99 | 0.00 | 0.00 |
July | 504.93 | 55.17 | 223.23 | 19.79 | 203.44 | 0.00 | 0.00 |
August | 589.28 | 84.29 | 281.79 | 71.59 | 210.20 | 0.00 | 0.00 |
September | 838.01 | 177.50 | 446.25 | 231.85 | 214.40 | 0.00 | 0.00 |
October | 964.15 | 297.59 | 612.55 | 416.17 | 196.38 | 0.00 | 0.00 |
November | 1008.14 | 503.44 | 737.24 | 563.91 | 173.33 | 0.00 | 0.00 |
December | 914.12 | 641.97 | 724.95 | 544.65 | 180.31 | 0.00 | 0.00 |
Annual Sum or Average | 733.89 | 321.74 | 478.50 | 276.88 | 201.63 | 0.00 | 0.00 |
Minimum of Months | 454.36 | 55.17 | 219.82 | 13.83 | 171.08 | 0.00 | 0.00 |
Maximum of Months | 1008.14 | 641.97 | 737.24 | 563.91 | 226.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2543.98 | 1753.28 | 1988.48 | 1506.73 | 481.75 | 0.00 | 0.00 |
February | 2432.71 | 1593.37 | 1870.85 | 1326.79 | 544.06 | 0.00 | 0.00 |
March | 1922.60 | 1410.89 | 1463.55 | 829.18 | 634.37 | 0.00 | 0.00 |
April | 1532.17 | 868.10 | 1019.80 | 382.82 | 636.98 | 0.00 | 0.00 |
May | 1238.33 | 493.88 | 723.68 | 106.13 | 617.55 | 0.00 | 0.00 |
June | 1371.03 | 226.90 | 618.99 | 38.95 | 580.04 | 0.00 | 0.00 |
July | 1396.52 | 174.15 | 628.60 | 55.73 | 572.87 | 0.00 | 0.00 |
August | 1631.10 | 264.88 | 793.51 | 201.60 | 591.90 | 0.00 | 0.00 |
September | 2325.90 | 542.00 | 1256.61 | 652.87 | 603.74 | 0.00 | 0.00 |
October | 2666.27 | 921.31 | 1724.89 | 1171.91 | 552.99 | 0.00 | 0.00 |
November | 2803.33 | 1494.04 | 2076.02 | 1587.93 | 488.09 | 0.00 | 0.00 |
December | 2549.52 | 1862.76 | 2041.42 | 1533.69 | 507.73 | 0.00 | 0.00 |
Annual Sum or Average | 2031.47 | 964.00 | 1347.44 | 779.68 | 567.76 | 0.00 | 0.00 |
Minimum of Months | 1238.33 | 174.15 | 618.99 | 38.95 | 481.75 | 0.00 | 0.00 |
Maximum of Months | 2803.33 | 1862.76 | 2076.02 | 1587.93 | 636.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3366.74 | 2462.30 | 2583.15 | 1957.32 | 625.82 | 0.00 | 0.00 |
February | 3231.24 | 2200.21 | 2430.34 | 1723.58 | 706.76 | 0.00 | 0.00 |
March | 2583.70 | 1936.95 | 1901.24 | 1077.15 | 824.09 | 0.00 | 0.00 |
April | 2090.13 | 1162.30 | 1324.78 | 497.31 | 827.47 | 0.00 | 0.00 |
May | 1707.67 | 651.91 | 940.11 | 137.87 | 802.24 | 0.00 | 0.00 |
June | 1887.41 | 296.02 | 804.10 | 50.59 | 753.51 | 0.00 | 0.00 |
July | 1918.08 | 224.63 | 816.59 | 72.40 | 744.19 | 0.00 | 0.00 |
August | 2226.18 | 343.47 | 1030.81 | 261.90 | 768.91 | 0.00 | 0.00 |
September | 3132.84 | 709.70 | 1632.41 | 848.12 | 784.29 | 0.00 | 0.00 |
October | 3572.67 | 1214.44 | 2240.73 | 1522.37 | 718.36 | 0.00 | 0.00 |
November | 3714.17 | 2067.15 | 2696.87 | 2062.81 | 634.06 | 0.00 | 0.00 |
December | 3367.67 | 2625.33 | 2651.92 | 1992.35 | 659.58 | 0.00 | 0.00 |
Annual Sum or Average | 2729.41 | 1320.25 | 1750.40 | 1012.84 | 737.56 | 0.00 | 0.00 |
Minimum of Months | 1707.67 | 224.63 | 804.10 | 50.59 | 625.82 | 0.00 | 0.00 |
Maximum of Months | 3714.17 | 2625.33 | 2696.87 | 2062.81 | 827.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.52 | 400.91 | 283.73 | 191.05 | 92.68 | 0.00 | 0.00 |
February | 329.71 | 354.85 | 289.74 | 180.69 | 109.06 | 0.00 | 0.00 |
March | 380.88 | 300.16 | 307.51 | 168.47 | 139.04 | 0.00 | 0.00 |
April | 462.37 | 156.12 | 299.69 | 148.16 | 151.52 | 0.00 | 0.00 |
May | 531.82 | 73.03 | 293.02 | 134.14 | 158.88 | 0.00 | 0.00 |
June | 616.31 | 24.68 | 278.25 | 125.74 | 152.51 | 0.00 | 0.00 |
July | 570.40 | 13.53 | 253.47 | 105.25 | 148.22 | 0.00 | 0.00 |
August | 548.72 | 28.38 | 260.33 | 116.29 | 144.05 | 0.00 | 0.00 |
September | 569.68 | 83.71 | 302.91 | 165.18 | 137.73 | 0.00 | 0.00 |
October | 484.71 | 171.55 | 312.79 | 196.19 | 116.60 | 0.00 | 0.00 |
November | 381.46 | 328.93 | 312.34 | 216.24 | 96.10 | 0.00 | 0.00 |
December | 285.76 | 434.65 | 281.51 | 187.15 | 94.37 | 0.00 | 0.00 |
Annual Sum or Average | 455.82 | 196.79 | 289.51 | 161.02 | 128.49 | 0.00 | 0.00 |
Minimum of Months | 285.76 | 13.53 | 253.47 | 105.25 | 92.68 | 0.00 | 0.00 |
Maximum of Months | 616.31 | 434.65 | 312.79 | 216.24 | 158.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.38 | 432.48 | 146.80 | 69.54 | 77.26 | 0.00 | 0.00 |
February | 154.23 | 385.14 | 167.47 | 73.68 | 93.79 | 0.00 | 0.00 |
March | 244.19 | 321.19 | 226.93 | 101.60 | 125.33 | 0.00 | 0.00 |
April | 378.54 | 166.50 | 260.93 | 117.84 | 143.08 | 0.00 | 0.00 |
May | 505.55 | 76.08 | 286.02 | 129.36 | 156.66 | 0.00 | 0.00 |
June | 615.70 | 25.40 | 282.95 | 129.41 | 153.55 | 0.00 | 0.00 |
July | 559.36 | 14.89 | 253.24 | 105.70 | 147.54 | 0.00 | 0.00 |
August | 495.12 | 31.57 | 239.02 | 101.04 | 137.98 | 0.00 | 0.00 |
September | 439.68 | 92.98 | 238.70 | 112.57 | 126.13 | 0.00 | 0.00 |
October | 294.78 | 194.81 | 204.46 | 101.68 | 102.78 | 0.00 | 0.00 |
November | 170.90 | 358.81 | 169.76 | 88.17 | 81.59 | 0.00 | 0.00 |
December | 102.72 | 473.94 | 140.12 | 63.46 | 76.67 | 0.00 | 0.00 |
Annual Sum or Average | 340.78 | 213.67 | 218.23 | 99.58 | 118.65 | 0.00 | 0.00 |
Minimum of Months | 102.72 | 14.89 | 140.12 | 63.46 | 76.67 | 0.00 | 0.00 |
Maximum of Months | 615.70 | 473.94 | 286.02 | 129.41 | 156.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 149.39 | 149.25 | 128.27 | 97.19 | 31.08 | 0.00 | 0.00 |
February | 142.99 | 134.46 | 120.68 | 85.59 | 35.09 | 0.00 | 0.00 |
March | 110.08 | 118.76 | 94.41 | 53.49 | 40.92 | 0.00 | 0.00 |
April | 88.57 | 75.42 | 65.78 | 24.69 | 41.09 | 0.00 | 0.00 |
May | 70.83 | 45.56 | 46.68 | 6.85 | 39.84 | 0.00 | 0.00 |
June | 79.84 | 23.69 | 39.93 | 2.51 | 37.42 | 0.00 | 0.00 |
July | 80.45 | 20.24 | 40.55 | 3.60 | 36.95 | 0.00 | 0.00 |
August | 96.08 | 28.14 | 51.19 | 13.00 | 38.18 | 0.00 | 0.00 |
September | 141.62 | 49.49 | 81.06 | 42.11 | 38.94 | 0.00 | 0.00 |
October | 161.33 | 78.89 | 111.27 | 75.59 | 35.67 | 0.00 | 0.00 |
November | 167.87 | 126.18 | 133.92 | 102.43 | 31.48 | 0.00 | 0.00 |
December | 150.13 | 156.48 | 131.68 | 98.93 | 32.75 | 0.00 | 0.00 |
Annual Sum or Average | 119.75 | 83.63 | 86.92 | 50.29 | 36.62 | 0.00 | 0.00 |
Minimum of Months | 70.83 | 20.24 | 39.93 | 2.51 | 31.08 | 0.00 | 0.00 |
Maximum of Months | 167.87 | 156.48 | 133.92 | 102.43 | 41.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.60 | 129.41 | 18.75 | 0.00 | 18.75 | 0.00 | 0.00 |
February | 7.88 | 112.94 | 22.89 | 0.00 | 22.89 | 0.00 | 0.00 |
March | 18.25 | 91.96 | 29.96 | 0.00 | 29.96 | 0.00 | 0.00 |
April | 45.11 | 44.82 | 34.79 | 0.44 | 34.35 | 0.00 | 0.00 |
May | 80.60 | 19.10 | 41.10 | 3.03 | 38.07 | 0.00 | 0.00 |
June | 118.17 | 6.14 | 43.71 | 5.45 | 38.26 | 0.00 | 0.00 |
July | 110.14 | 3.43 | 40.38 | 3.96 | 36.42 | 0.00 | 0.00 |
August | 86.55 | 7.77 | 34.15 | 0.81 | 33.34 | 0.00 | 0.00 |
September | 60.94 | 24.27 | 29.71 | 0.04 | 29.67 | 0.00 | 0.00 |
October | 29.31 | 53.14 | 24.63 | 0.00 | 24.63 | 0.00 | 0.00 |
November | 5.54 | 104.88 | 19.88 | 0.00 | 19.88 | 0.00 | 0.00 |
December | 1.15 | 143.06 | 18.60 | 0.00 | 18.60 | 0.00 | 0.00 |
Annual Sum or Average | 47.31 | 61.51 | 29.91 | 1.15 | 28.76 | 0.00 | 0.00 |
Minimum of Months | 1.15 | 3.43 | 18.60 | 0.00 | 18.60 | 0.00 | 0.00 |
Maximum of Months | 118.17 | 143.06 | 43.71 | 5.45 | 38.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 284.83 | 393.75 | 277.19 | 184.81 | 92.37 | 0.00 | 0.00 |
February | 347.86 | 343.38 | 307.66 | 196.40 | 111.26 | 0.00 | 0.00 |
March | 372.11 | 282.54 | 311.28 | 173.28 | 138.01 | 0.00 | 0.00 |
April | 473.24 | 140.53 | 315.21 | 160.08 | 155.13 | 0.00 | 0.00 |
May | 535.37 | 65.54 | 298.52 | 139.02 | 159.50 | 0.00 | 0.00 |
June | 635.22 | 22.95 | 290.18 | 136.73 | 153.44 | 0.00 | 0.00 |
July | 591.76 | 13.05 | 266.29 | 117.21 | 149.08 | 0.00 | 0.00 |
August | 563.72 | 26.58 | 269.37 | 121.43 | 147.94 | 0.00 | 0.00 |
September | 564.85 | 76.58 | 305.10 | 169.01 | 136.10 | 0.00 | 0.00 |
October | 446.12 | 164.70 | 295.07 | 178.52 | 116.55 | 0.00 | 0.00 |
November | 361.75 | 319.12 | 307.07 | 209.17 | 97.90 | 0.00 | 0.00 |
December | 277.12 | 426.28 | 281.54 | 185.64 | 95.90 | 0.00 | 0.00 |
Annual Sum or Average | 454.78 | 188.86 | 293.48 | 163.96 | 129.51 | 0.00 | 0.00 |
Minimum of Months | 277.12 | 13.05 | 266.29 | 117.21 | 92.37 | 0.00 | 0.00 |
Maximum of Months | 635.22 | 426.28 | 315.21 | 209.17 | 159.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 87.17 | 411.25 | 140.25 | 63.30 | 76.95 | 0.00 | 0.00 |
February | 157.31 | 357.18 | 185.39 | 89.40 | 95.99 | 0.00 | 0.00 |
March | 231.62 | 293.16 | 230.70 | 106.41 | 124.29 | 0.00 | 0.00 |
April | 389.29 | 148.95 | 276.45 | 129.76 | 146.69 | 0.00 | 0.00 |
May | 505.46 | 70.28 | 291.52 | 134.25 | 157.27 | 0.00 | 0.00 |
June | 630.24 | 24.34 | 294.88 | 140.40 | 154.48 | 0.00 | 0.00 |
July | 576.60 | 14.64 | 266.07 | 117.67 | 148.40 | 0.00 | 0.00 |
August | 505.60 | 29.65 | 248.06 | 106.18 | 141.88 | 0.00 | 0.00 |
September | 427.62 | 83.52 | 240.89 | 116.40 | 124.49 | 0.00 | 0.00 |
October | 253.19 | 178.01 | 186.74 | 84.01 | 102.73 | 0.00 | 0.00 |
November | 136.85 | 333.36 | 164.49 | 81.11 | 83.38 | 0.00 | 0.00 |
December | 79.76 | 450.07 | 140.16 | 61.95 | 78.20 | 0.00 | 0.00 |
Annual Sum or Average | 332.46 | 198.81 | 222.19 | 102.52 | 119.67 | 0.00 | 0.00 |
Minimum of Months | 79.76 | 14.64 | 140.16 | 61.95 | 76.95 | 0.00 | 0.00 |
Maximum of Months | 630.24 | 450.07 | 294.88 | 140.40 | 157.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.39 | 573.61 | 318.53 | 210.59 | 107.94 | 0.00 | 0.00 |
February | 315.82 | 511.41 | 311.07 | 185.44 | 125.63 | 0.00 | 0.00 |
March | 284.13 | 442.34 | 269.47 | 115.89 | 153.57 | 0.00 | 0.00 |
April | 305.31 | 245.78 | 217.91 | 54.47 | 163.44 | 0.00 | 0.00 |
May | 344.83 | 123.11 | 190.19 | 21.40 | 168.79 | 0.00 | 0.00 |
June | 448.76 | 51.13 | 181.20 | 17.24 | 163.96 | 0.00 | 0.00 |
July | 432.16 | 36.73 | 175.33 | 16.37 | 158.96 | 0.00 | 0.00 |
August | 413.58 | 61.75 | 184.89 | 29.94 | 154.95 | 0.00 | 0.00 |
September | 458.04 | 143.61 | 240.00 | 91.33 | 148.67 | 0.00 | 0.00 |
October | 427.66 | 264.66 | 294.44 | 163.79 | 130.64 | 0.00 | 0.00 |
November | 366.58 | 475.37 | 333.23 | 221.94 | 111.29 | 0.00 | 0.00 |
December | 295.48 | 612.82 | 325.62 | 214.36 | 111.26 | 0.00 | 0.00 |
Annual Sum or Average | 366.41 | 294.14 | 253.13 | 111.46 | 141.67 | 0.00 | 0.00 |
Minimum of Months | 284.13 | 36.73 | 175.33 | 16.37 | 107.94 | 0.00 | 0.00 |
Maximum of Months | 458.04 | 612.82 | 333.23 | 221.94 | 168.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.42 | 388.09 | 283.73 | 191.05 | 92.68 | 0.00 | 0.00 |
February | 327.66 | 343.88 | 289.74 | 180.69 | 109.06 | 0.00 | 0.00 |
March | 375.88 | 291.06 | 307.51 | 168.47 | 139.04 | 0.00 | 0.00 |
April | 455.05 | 150.08 | 299.69 | 148.16 | 151.52 | 0.00 | 0.00 |
May | 524.21 | 68.98 | 293.02 | 134.14 | 158.88 | 0.00 | 0.00 |
June | 608.83 | 22.87 | 278.25 | 125.74 | 152.51 | 0.00 | 0.00 |
July | 562.60 | 12.33 | 253.47 | 105.25 | 148.22 | 0.00 | 0.00 |
August | 541.16 | 26.41 | 260.33 | 116.29 | 144.05 | 0.00 | 0.00 |
September | 561.58 | 79.91 | 302.91 | 165.18 | 137.73 | 0.00 | 0.00 |
October | 479.46 | 165.55 | 312.79 | 196.19 | 116.60 | 0.00 | 0.00 |
November | 379.66 | 318.14 | 312.34 | 216.24 | 96.10 | 0.00 | 0.00 |
December | 287.55 | 420.46 | 281.51 | 187.15 | 94.37 | 0.00 | 0.00 |
Annual Sum or Average | 450.96 | 189.91 | 289.51 | 161.02 | 128.49 | 0.00 | 0.00 |
Minimum of Months | 287.55 | 12.33 | 253.47 | 105.25 | 92.68 | 0.00 | 0.00 |
Maximum of Months | 608.83 | 420.46 | 312.79 | 216.24 | 158.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.92 | 415.68 | 146.80 | 69.54 | 77.26 | 0.00 | 0.00 |
February | 153.92 | 371.60 | 167.47 | 73.68 | 93.79 | 0.00 | 0.00 |
March | 240.67 | 312.39 | 226.93 | 101.60 | 125.33 | 0.00 | 0.00 |
April | 372.03 | 161.65 | 260.93 | 117.84 | 143.08 | 0.00 | 0.00 |
May | 498.35 | 72.49 | 286.02 | 129.36 | 156.66 | 0.00 | 0.00 |
June | 607.96 | 23.71 | 282.95 | 129.41 | 153.55 | 0.00 | 0.00 |
July | 551.40 | 13.82 | 253.24 | 105.70 | 147.54 | 0.00 | 0.00 |
August | 488.10 | 29.70 | 239.02 | 101.04 | 137.98 | 0.00 | 0.00 |
September | 432.82 | 89.26 | 238.70 | 112.57 | 126.13 | 0.00 | 0.00 |
October | 290.46 | 190.16 | 204.46 | 101.68 | 102.78 | 0.00 | 0.00 |
November | 170.35 | 345.80 | 169.76 | 88.17 | 81.59 | 0.00 | 0.00 |
December | 105.24 | 455.15 | 140.12 | 63.46 | 76.67 | 0.00 | 0.00 |
Annual Sum or Average | 336.78 | 206.00 | 218.23 | 99.58 | 118.65 | 0.00 | 0.00 |
Minimum of Months | 105.24 | 13.82 | 140.12 | 63.46 | 76.67 | 0.00 | 0.00 |
Maximum of Months | 607.96 | 455.15 | 286.02 | 129.41 | 156.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 295.47 | 202.63 | 235.19 | 178.21 | 56.98 | 0.00 | 0.00 |
February | 285.08 | 177.37 | 221.28 | 156.93 | 64.35 | 0.00 | 0.00 |
March | 227.48 | 150.88 | 173.11 | 98.07 | 75.03 | 0.00 | 0.00 |
April | 193.14 | 77.44 | 120.62 | 45.28 | 75.34 | 0.00 | 0.00 |
May | 172.51 | 34.39 | 85.60 | 12.55 | 73.04 | 0.00 | 0.00 |
June | 202.45 | 10.93 | 73.21 | 4.61 | 68.61 | 0.00 | 0.00 |
July | 202.55 | 5.92 | 74.35 | 6.59 | 67.76 | 0.00 | 0.00 |
August | 223.59 | 12.99 | 93.85 | 23.85 | 70.01 | 0.00 | 0.00 |
September | 291.96 | 39.88 | 148.63 | 77.22 | 71.41 | 0.00 | 0.00 |
October | 324.21 | 84.32 | 204.02 | 138.61 | 65.41 | 0.00 | 0.00 |
November | 331.83 | 163.80 | 245.55 | 187.82 | 57.73 | 0.00 | 0.00 |
December | 297.96 | 218.15 | 241.46 | 181.40 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 253.76 | 97.85 | 159.37 | 92.22 | 67.15 | 0.00 | 0.00 |
Minimum of Months | 172.51 | 5.92 | 73.21 | 4.61 | 56.98 | 0.00 | 0.00 |
Maximum of Months | 331.83 | 218.15 | 245.55 | 187.82 | 75.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.51 | 1335.69 | 164.00 | 0.00 | 164.00 | 0.00 | 0.00 |
February | 40.05 | 1171.02 | 200.26 | 0.00 | 200.26 | 0.00 | 0.00 |
March | 109.22 | 966.51 | 262.13 | 0.01 | 262.12 | 0.00 | 0.00 |
April | 305.08 | 519.91 | 304.39 | 3.88 | 300.52 | 0.00 | 0.00 |
May | 577.21 | 266.30 | 359.57 | 26.50 | 333.07 | 0.00 | 0.00 |
June | 867.95 | 123.02 | 382.38 | 47.65 | 334.73 | 0.00 | 0.00 |
July | 798.43 | 95.25 | 353.26 | 34.65 | 318.61 | 0.00 | 0.00 |
August | 611.13 | 146.89 | 298.77 | 7.11 | 291.66 | 0.00 | 0.00 |
September | 436.83 | 315.93 | 259.93 | 0.33 | 259.60 | 0.00 | 0.00 |
October | 188.94 | 587.72 | 215.46 | 0.00 | 215.46 | 0.00 | 0.00 |
November | 21.89 | 1101.23 | 173.94 | 0.00 | 173.94 | 0.00 | 0.00 |
December | 3.22 | 1437.48 | 162.73 | 0.00 | 162.73 | 0.00 | 0.00 |
Annual Sum or Average | 331.91 | 669.87 | 261.70 | 10.06 | 251.64 | 0.00 | 0.00 |
Minimum of Months | 3.22 | 95.25 | 162.73 | 0.00 | 162.73 | 0.00 | 0.00 |
Maximum of Months | 867.95 | 1437.48 | 382.38 | 47.65 | 334.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.06 | 1380.09 | 164.00 | 0.00 | 164.00 | 0.00 | 0.00 |
February | 34.62 | 1205.47 | 200.26 | 0.00 | 200.26 | 0.00 | 0.00 |
March | 99.28 | 991.93 | 262.13 | 0.01 | 262.12 | 0.00 | 0.00 |
April | 293.69 | 533.90 | 304.39 | 3.88 | 300.52 | 0.00 | 0.00 |
May | 564.72 | 274.81 | 359.57 | 26.50 | 333.07 | 0.00 | 0.00 |
June | 855.50 | 128.18 | 382.38 | 47.65 | 334.73 | 0.00 | 0.00 |
July | 785.90 | 100.45 | 353.26 | 34.65 | 318.61 | 0.00 | 0.00 |
August | 599.09 | 153.50 | 298.77 | 7.11 | 291.66 | 0.00 | 0.00 |
September | 427.10 | 325.86 | 259.93 | 0.33 | 259.60 | 0.00 | 0.00 |
October | 179.01 | 603.66 | 215.46 | 0.00 | 215.46 | 0.00 | 0.00 |
November | 17.70 | 1135.22 | 173.94 | 0.00 | 173.94 | 0.00 | 0.00 |
December | 1.96 | 1485.89 | 162.73 | 0.00 | 162.73 | 0.00 | 0.00 |
Annual Sum or Average | 323.32 | 690.82 | 261.70 | 10.06 | 251.64 | 0.00 | 0.00 |
Minimum of Months | 1.96 | 100.45 | 162.73 | 0.00 | 162.73 | 0.00 | 0.00 |
Maximum of Months | 855.50 | 1485.89 | 382.38 | 47.65 | 334.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 314.34 | 981.15 | 417.42 | 248.10 | 169.31 | 0.00 | 0.00 |
February | 461.08 | 866.70 | 493.04 | 285.79 | 207.25 | 0.00 | 0.00 |
March | 556.79 | 728.80 | 541.95 | 279.67 | 262.29 | 0.00 | 0.00 |
April | 831.33 | 419.41 | 591.63 | 289.83 | 301.80 | 0.00 | 0.00 |
May | 1004.48 | 248.90 | 590.01 | 273.25 | 316.75 | 0.00 | 0.00 |
June | 1221.27 | 130.46 | 585.02 | 277.12 | 307.91 | 0.00 | 0.00 |
July | 1126.34 | 109.81 | 532.33 | 234.86 | 297.47 | 0.00 | 0.00 |
August | 1039.57 | 150.21 | 517.40 | 227.60 | 289.80 | 0.00 | 0.00 |
September | 997.26 | 263.20 | 545.97 | 285.39 | 260.58 | 0.00 | 0.00 |
October | 675.73 | 472.84 | 481.79 | 262.52 | 219.27 | 0.00 | 0.00 |
November | 458.33 | 813.78 | 471.55 | 290.27 | 181.27 | 0.00 | 0.00 |
December | 299.39 | 1037.18 | 421.68 | 247.58 | 174.10 | 0.00 | 0.00 |
Annual Sum or Average | 749.78 | 516.90 | 515.64 | 266.47 | 249.17 | 0.00 | 0.00 |
Minimum of Months | 299.39 | 109.81 | 417.42 | 227.60 | 169.31 | 0.00 | 0.00 |
Maximum of Months | 1221.27 | 1037.18 | 591.63 | 290.27 | 316.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 684.36 | 962.33 | 654.92 | 453.65 | 201.27 | 0.00 | 0.00 |
February | 683.66 | 871.96 | 631.93 | 399.48 | 232.46 | 0.00 | 0.00 |
March | 577.69 | 765.52 | 530.51 | 249.66 | 280.86 | 0.00 | 0.00 |
April | 565.28 | 440.39 | 411.39 | 116.59 | 294.80 | 0.00 | 0.00 |
May | 590.65 | 227.34 | 341.15 | 41.04 | 300.11 | 0.00 | 0.00 |
June | 749.14 | 98.32 | 317.45 | 28.06 | 289.39 | 0.00 | 0.00 |
July | 725.24 | 73.97 | 310.36 | 28.66 | 281.70 | 0.00 | 0.00 |
August | 725.91 | 119.14 | 341.33 | 63.14 | 278.20 | 0.00 | 0.00 |
September | 862.63 | 263.53 | 467.45 | 196.68 | 270.77 | 0.00 | 0.00 |
October | 857.50 | 472.65 | 593.20 | 352.84 | 240.36 | 0.00 | 0.00 |
November | 794.45 | 810.40 | 684.69 | 478.10 | 206.58 | 0.00 | 0.00 |
December | 683.65 | 1006.26 | 670.42 | 461.77 | 208.66 | 0.00 | 0.00 |
Annual Sum or Average | 708.17 | 507.50 | 495.40 | 238.20 | 257.21 | 0.00 | 0.00 |
Minimum of Months | 565.28 | 73.97 | 310.36 | 28.06 | 201.27 | 0.00 | 0.00 |
Maximum of Months | 862.63 | 1006.26 | 684.69 | 478.10 | 300.11 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244284E+10 | 0.160376E+10 | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.00 | 0.00 |
February | 0.211949E+10 | 0.129215E+10 | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.00 | 0.00 |
March | 0.187537E+10 | 0.125687E+10 | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.00 | 0.00 |
April | 0.145593E+10 | 0.727294E+09 | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.00 | 0.00 |
May | 0.121697E+10 | 0.422368E+09 | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.00 | 0.00 |
June | 0.128664E+10 | 0.188846E+09 | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.00 | 0.00 |
July | 0.135241E+10 | 0.147758E+09 | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.00 | 0.00 |
August | 0.157833E+10 | 0.225771E+09 | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.00 | 0.00 |
September | 0.217212E+10 | 0.460082E+09 | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.00 | 0.00 |
October | 0.258237E+10 | 0.797054E+09 | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.00 | 0.00 |
November | 0.261310E+10 | 0.130492E+10 | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.00 | 0.00 |
December | 0.244837E+10 | 0.171946E+10 | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.231439E+11 | 0.101463E+11 | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.00 | 0.00 |
Minimum of Months | 0.121697E+10 | 0.147758E+09 | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.261310E+10 | 0.171946E+10 | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.681379E+10 | 0.469598E+10 | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.00 | 0.00 |
February | 0.588521E+10 | 0.385467E+10 | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.00 | 0.00 |
March | 0.514950E+10 | 0.377893E+10 | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.00 | 0.00 |
April | 0.397140E+10 | 0.225011E+10 | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.00 | 0.00 |
May | 0.331674E+10 | 0.132281E+10 | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.00 | 0.00 |
June | 0.355371E+10 | 0.588124E+09 | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.00 | 0.00 |
July | 0.374043E+10 | 0.466435E+09 | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.00 | 0.00 |
August | 0.436874E+10 | 0.709455E+09 | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.00 | 0.00 |
September | 0.602873E+10 | 0.140487E+10 | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.00 | 0.00 |
October | 0.714133E+10 | 0.246763E+10 | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.00 | 0.00 |
November | 0.726624E+10 | 0.387254E+10 | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.00 | 0.00 |
December | 0.682863E+10 | 0.498921E+10 | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.640644E+11 | 0.304008E+11 | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.00 | 0.00 |
Minimum of Months | 0.331674E+10 | 0.466435E+09 | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.726624E+10 | 0.498921E+10 | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.901748E+10 | 0.659502E+10 | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.00 | 0.00 |
February | 0.781702E+10 | 0.532275E+10 | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.00 | 0.00 |
March | 0.692019E+10 | 0.518793E+10 | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.00 | 0.00 |
April | 0.541761E+10 | 0.301269E+10 | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.00 | 0.00 |
May | 0.457383E+10 | 0.174607E+10 | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.00 | 0.00 |
June | 0.489215E+10 | 0.767282E+09 | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.00 | 0.00 |
July | 0.513739E+10 | 0.601661E+09 | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.00 | 0.00 |
August | 0.596259E+10 | 0.919939E+09 | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.00 | 0.00 |
September | 0.812032E+10 | 0.183953E+10 | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.00 | 0.00 |
October | 0.956904E+10 | 0.325276E+10 | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.00 | 0.00 |
November | 0.962712E+10 | 0.535804E+10 | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.00 | 0.00 |
December | 0.901998E+10 | 0.703169E+10 | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.860747E+11 | 0.416354E+11 | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.00 | 0.00 |
Minimum of Months | 0.457383E+10 | 0.601661E+09 | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.962712E+10 | 0.703169E+10 | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.810272E+09 | 0.107379E+10 | 0.759952E+09 | 0.511709E+09 | 0.248243E+09 | 0.00 | 0.00 |
February | 0.797637E+09 | 0.858457E+09 | 0.700948E+09 | 0.437118E+09 | 0.263830E+09 | 0.00 | 0.00 |
March | 0.102016E+10 | 0.803944E+09 | 0.823645E+09 | 0.451236E+09 | 0.372409E+09 | 0.00 | 0.00 |
April | 0.119845E+10 | 0.404672E+09 | 0.776784E+09 | 0.384039E+09 | 0.392745E+09 | 0.00 | 0.00 |
May | 0.142442E+10 | 0.195598E+09 | 0.784816E+09 | 0.359276E+09 | 0.425540E+09 | 0.00 | 0.00 |
June | 0.159749E+10 | 63959314.82 | 0.721217E+09 | 0.325916E+09 | 0.395301E+09 | 0.00 | 0.00 |
July | 0.152777E+10 | 36243397.68 | 0.678894E+09 | 0.281899E+09 | 0.396995E+09 | 0.00 | 0.00 |
August | 0.146969E+10 | 76000668.48 | 0.697280E+09 | 0.311467E+09 | 0.385813E+09 | 0.00 | 0.00 |
September | 0.147661E+10 | 0.216964E+09 | 0.785151E+09 | 0.428145E+09 | 0.357006E+09 | 0.00 | 0.00 |
October | 0.129824E+10 | 0.459471E+09 | 0.837764E+09 | 0.525471E+09 | 0.312293E+09 | 0.00 | 0.00 |
November | 0.988744E+09 | 0.852575E+09 | 0.809585E+09 | 0.560483E+09 | 0.249102E+09 | 0.00 | 0.00 |
December | 0.765373E+09 | 0.116418E+10 | 0.754004E+09 | 0.501250E+09 | 0.252754E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143748E+11 | 0.620585E+10 | 0.913004E+10 | 0.507801E+10 | 0.405203E+10 | 0.00 | 0.00 |
Minimum of Months | 0.765373E+09 | 36243397.68 | 0.678894E+09 | 0.281899E+09 | 0.248243E+09 | 0.00 | 0.00 |
Maximum of Months | 0.159749E+10 | 0.116418E+10 | 0.837764E+09 | 0.560483E+09 | 0.425540E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.317072E+09 | 0.115834E+10 | 0.393177E+09 | 0.186243E+09 | 0.206934E+09 | 0.00 | 0.00 |
February | 0.373118E+09 | 0.931719E+09 | 0.405150E+09 | 0.178255E+09 | 0.226895E+09 | 0.00 | 0.00 |
March | 0.654033E+09 | 0.860279E+09 | 0.607809E+09 | 0.272131E+09 | 0.335679E+09 | 0.00 | 0.00 |
April | 0.981182E+09 | 0.431557E+09 | 0.676322E+09 | 0.305450E+09 | 0.370872E+09 | 0.00 | 0.00 |
May | 0.135406E+10 | 0.203779E+09 | 0.766082E+09 | 0.346491E+09 | 0.419592E+09 | 0.00 | 0.00 |
June | 0.159589E+10 | 65828343.52 | 0.733418E+09 | 0.335419E+09 | 0.397999E+09 | 0.00 | 0.00 |
July | 0.149819E+10 | 39891537.51 | 0.678285E+09 | 0.283120E+09 | 0.395165E+09 | 0.00 | 0.00 |
August | 0.132614E+10 | 84554787.53 | 0.640200E+09 | 0.270639E+09 | 0.369561E+09 | 0.00 | 0.00 |
September | 0.113965E+10 | 0.240996E+09 | 0.618721E+09 | 0.291790E+09 | 0.326931E+09 | 0.00 | 0.00 |
October | 0.789535E+09 | 0.521766E+09 | 0.547618E+09 | 0.272329E+09 | 0.275289E+09 | 0.00 | 0.00 |
November | 0.442962E+09 | 0.930038E+09 | 0.440022E+09 | 0.228541E+09 | 0.211481E+09 | 0.00 | 0.00 |
December | 0.275119E+09 | 0.126941E+10 | 0.375307E+09 | 0.169961E+09 | 0.205347E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107469E+11 | 0.673816E+10 | 0.688211E+10 | 0.314037E+10 | 0.374175E+10 | 0.00 | 0.00 |
Minimum of Months | 0.275119E+09 | 39891537.51 | 0.375307E+09 | 0.169961E+09 | 0.205347E+09 | 0.00 | 0.00 |
Maximum of Months | 0.159589E+10 | 0.126941E+10 | 0.766082E+09 | 0.346491E+09 | 0.419592E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.400135E+09 | 0.399753E+09 | 0.343554E+09 | 0.260321E+09 | 83233276.21 | 0.00 | 0.00 |
February | 0.345911E+09 | 0.325294E+09 | 0.291951E+09 | 0.207050E+09 | 84901543.05 | 0.00 | 0.00 |
March | 0.294829E+09 | 0.318094E+09 | 0.252861E+09 | 0.143259E+09 | 0.109602E+09 | 0.00 | 0.00 |
April | 0.229578E+09 | 0.195488E+09 | 0.170510E+09 | 64007642.82 | 0.106502E+09 | 0.00 | 0.00 |
May | 0.189711E+09 | 0.122019E+09 | 0.125032E+09 | 18336454.50 | 0.106696E+09 | 0.00 | 0.00 |
June | 0.206941E+09 | 61413851.02 | 0.103494E+09 | 6511973.18 | 96982365.64 | 0.00 | 0.00 |
July | 0.215469E+09 | 54222551.36 | 0.108605E+09 | 9628957.34 | 98975670.82 | 0.00 | 0.00 |
August | 0.257344E+09 | 75361869.51 | 0.137096E+09 | 34831722.31 | 0.102264E+09 | 0.00 | 0.00 |
September | 0.367066E+09 | 0.128280E+09 | 0.210104E+09 | 0.109160E+09 | 0.100945E+09 | 0.00 | 0.00 |
October | 0.432100E+09 | 0.211308E+09 | 0.298014E+09 | 0.202473E+09 | 95540760.93 | 0.00 | 0.00 |
November | 0.435111E+09 | 0.327051E+09 | 0.347109E+09 | 0.265501E+09 | 81608843.31 | 0.00 | 0.00 |
December | 0.402099E+09 | 0.419117E+09 | 0.352701E+09 | 0.264979E+09 | 87722444.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.377629E+10 | 0.263740E+10 | 0.274103E+10 | 0.158606E+10 | 0.115497E+10 | 0.00 | 0.00 |
Minimum of Months | 0.189711E+09 | 54222551.36 | 0.103494E+09 | 6511973.18 | 81608843.31 | 0.00 | 0.00 |
Maximum of Months | 0.435111E+09 | 0.419117E+09 | 0.352701E+09 | 0.265501E+09 | 0.109602E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4281975.90 | 0.346622E+09 | 50209702.58 | 0.00 | 50209702.58 | 0.00 | 0.00 |
February | 19054780.22 | 0.273228E+09 | 55377996.35 | 0.00 | 55377996.35 | 0.00 | 0.00 |
March | 48869388.16 | 0.246296E+09 | 80253494.35 | 3177.00 | 80250317.34 | 0.00 | 0.00 |
April | 0.116926E+09 | 0.116173E+09 | 90185743.44 | 1148932.80 | 89036810.63 | 0.00 | 0.00 |
May | 0.215881E+09 | 51169277.25 | 0.110085E+09 | 8112994.49 | 0.101972E+09 | 0.00 | 0.00 |
June | 0.306294E+09 | 15913111.63 | 0.113290E+09 | 14117375.75 | 99173041.59 | 0.00 | 0.00 |
July | 0.295010E+09 | 9184090.99 | 0.108153E+09 | 10608751.00 | 97544172.60 | 0.00 | 0.00 |
August | 0.231805E+09 | 20813743.96 | 91470882.32 | 2176203.98 | 89294678.34 | 0.00 | 0.00 |
September | 0.157959E+09 | 62897617.18 | 77012546.73 | 97332.23 | 76915214.50 | 0.00 | 0.00 |
October | 78506004.28 | 0.142328E+09 | 65964586.19 | 0.00 | 65964586.19 | 0.00 | 0.00 |
November | 14356390.86 | 0.271854E+09 | 51535037.73 | 0.00 | 51535037.73 | 0.00 | 0.00 |
December | 3091270.89 | 0.383175E+09 | 49820868.72 | 0.00 | 49820868.72 | 0.00 | 0.00 |
Annual Sum or Average | 0.149204E+10 | 0.193965E+10 | 0.943359E+09 | 36264767.25 | 0.907094E+09 | 0.00 | 0.00 |
Minimum of Months | 3091270.89 | 9184090.99 | 49820868.72 | 0.00 | 49820868.72 | 0.00 | 0.00 |
Maximum of Months | 0.306294E+09 | 0.383175E+09 | 0.113290E+09 | 14117375.75 | 0.101972E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.762881E+09 | 0.105461E+10 | 0.742416E+09 | 0.495005E+09 | 0.247410E+09 | 0.00 | 0.00 |
February | 0.841532E+09 | 0.830693E+09 | 0.744303E+09 | 0.475139E+09 | 0.269164E+09 | 0.00 | 0.00 |
March | 0.996668E+09 | 0.756760E+09 | 0.833740E+09 | 0.464106E+09 | 0.369635E+09 | 0.00 | 0.00 |
April | 0.122663E+10 | 0.364256E+09 | 0.817025E+09 | 0.414940E+09 | 0.402085E+09 | 0.00 | 0.00 |
May | 0.143393E+10 | 0.175540E+09 | 0.799549E+09 | 0.372357E+09 | 0.427192E+09 | 0.00 | 0.00 |
June | 0.164648E+10 | 59475678.03 | 0.752136E+09 | 0.354417E+09 | 0.397719E+09 | 0.00 | 0.00 |
July | 0.158497E+10 | 34951076.64 | 0.713241E+09 | 0.313939E+09 | 0.399302E+09 | 0.00 | 0.00 |
August | 0.150986E+10 | 71186520.07 | 0.721483E+09 | 0.325233E+09 | 0.396250E+09 | 0.00 | 0.00 |
September | 0.146409E+10 | 0.198488E+09 | 0.790828E+09 | 0.438069E+09 | 0.352759E+09 | 0.00 | 0.00 |
October | 0.119490E+10 | 0.441133E+09 | 0.790311E+09 | 0.478148E+09 | 0.312163E+09 | 0.00 | 0.00 |
November | 0.937659E+09 | 0.827164E+09 | 0.795932E+09 | 0.542178E+09 | 0.253753E+09 | 0.00 | 0.00 |
December | 0.742236E+09 | 0.114175E+10 | 0.754088E+09 | 0.497217E+09 | 0.256871E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143418E+11 | 0.595601E+10 | 0.925505E+10 | 0.517075E+10 | 0.408430E+10 | 0.00 | 0.00 |
Minimum of Months | 0.742236E+09 | 34951076.64 | 0.713241E+09 | 0.313939E+09 | 0.247410E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164648E+10 | 0.114175E+10 | 0.833740E+09 | 0.542178E+09 | 0.427192E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.233465E+09 | 0.110149E+10 | 0.375641E+09 | 0.169539E+09 | 0.206102E+09 | 0.00 | 0.00 |
February | 0.380575E+09 | 0.864092E+09 | 0.448505E+09 | 0.216276E+09 | 0.232229E+09 | 0.00 | 0.00 |
March | 0.620377E+09 | 0.785213E+09 | 0.617904E+09 | 0.285000E+09 | 0.332904E+09 | 0.00 | 0.00 |
April | 0.100905E+10 | 0.386067E+09 | 0.716562E+09 | 0.336350E+09 | 0.380212E+09 | 0.00 | 0.00 |
May | 0.135381E+10 | 0.188237E+09 | 0.780816E+09 | 0.359572E+09 | 0.421244E+09 | 0.00 | 0.00 |
June | 0.163358E+10 | 63090903.09 | 0.764337E+09 | 0.363919E+09 | 0.400417E+09 | 0.00 | 0.00 |
July | 0.154435E+10 | 39211211.26 | 0.712631E+09 | 0.315159E+09 | 0.397472E+09 | 0.00 | 0.00 |
August | 0.135419E+10 | 79421389.43 | 0.664403E+09 | 0.284405E+09 | 0.379998E+09 | 0.00 | 0.00 |
September | 0.110840E+10 | 0.216482E+09 | 0.624398E+09 | 0.301714E+09 | 0.322684E+09 | 0.00 | 0.00 |
October | 0.678157E+09 | 0.476774E+09 | 0.500164E+09 | 0.225006E+09 | 0.275158E+09 | 0.00 | 0.00 |
November | 0.354721E+09 | 0.864074E+09 | 0.426369E+09 | 0.210237E+09 | 0.216132E+09 | 0.00 | 0.00 |
December | 0.213628E+09 | 0.120547E+10 | 0.375391E+09 | 0.165927E+09 | 0.209464E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104843E+11 | 0.626962E+10 | 0.700712E+10 | 0.323311E+10 | 0.377402E+10 | 0.00 | 0.00 |
Minimum of Months | 0.213628E+09 | 39211211.26 | 0.375391E+09 | 0.165927E+09 | 0.206102E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163358E+10 | 0.120547E+10 | 0.780816E+09 | 0.363919E+09 | 0.421244E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.812607E+09 | 0.153636E+10 | 0.853157E+09 | 0.564043E+09 | 0.289114E+09 | 0.00 | 0.00 |
February | 0.764026E+09 | 0.123721E+10 | 0.752544E+09 | 0.448619E+09 | 0.303925E+09 | 0.00 | 0.00 |
March | 0.761008E+09 | 0.118476E+10 | 0.721736E+09 | 0.310409E+09 | 0.411327E+09 | 0.00 | 0.00 |
April | 0.791354E+09 | 0.637071E+09 | 0.564820E+09 | 0.141176E+09 | 0.423644E+09 | 0.00 | 0.00 |
May | 0.923593E+09 | 0.329735E+09 | 0.509392E+09 | 57305464.24 | 0.452086E+09 | 0.00 | 0.00 |
June | 0.116317E+10 | 0.132525E+09 | 0.469668E+09 | 44692604.69 | 0.424976E+09 | 0.00 | 0.00 |
July | 0.115749E+10 | 98380251.40 | 0.469612E+09 | 43845384.83 | 0.425766E+09 | 0.00 | 0.00 |
August | 0.110775E+10 | 0.165387E+09 | 0.495205E+09 | 80185043.42 | 0.415020E+09 | 0.00 | 0.00 |
September | 0.118724E+10 | 0.372242E+09 | 0.622073E+09 | 0.236729E+09 | 0.385344E+09 | 0.00 | 0.00 |
October | 0.114544E+10 | 0.708855E+09 | 0.788615E+09 | 0.438703E+09 | 0.349912E+09 | 0.00 | 0.00 |
November | 0.950171E+09 | 0.123215E+10 | 0.863732E+09 | 0.575266E+09 | 0.288466E+09 | 0.00 | 0.00 |
December | 0.791417E+09 | 0.164139E+10 | 0.872134E+09 | 0.574135E+09 | 0.297999E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115553E+11 | 0.927606E+10 | 0.798269E+10 | 0.351511E+10 | 0.446758E+10 | 0.00 | 0.00 |
Minimum of Months | 0.761008E+09 | 98380251.40 | 0.469612E+09 | 43845384.83 | 0.288466E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118724E+10 | 0.164139E+10 | 0.872134E+09 | 0.575266E+09 | 0.452086E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.809998E+09 | 0.103946E+10 | 0.759952E+09 | 0.511709E+09 | 0.248243E+09 | 0.00 | 0.00 |
February | 0.792679E+09 | 0.831917E+09 | 0.700948E+09 | 0.437118E+09 | 0.263830E+09 | 0.00 | 0.00 |
March | 0.100676E+10 | 0.779570E+09 | 0.823645E+09 | 0.451236E+09 | 0.372409E+09 | 0.00 | 0.00 |
April | 0.117950E+10 | 0.389019E+09 | 0.776784E+09 | 0.384039E+09 | 0.392745E+09 | 0.00 | 0.00 |
May | 0.140404E+10 | 0.184752E+09 | 0.784816E+09 | 0.359276E+09 | 0.425540E+09 | 0.00 | 0.00 |
June | 0.157808E+10 | 59289743.35 | 0.721217E+09 | 0.325916E+09 | 0.395301E+09 | 0.00 | 0.00 |
July | 0.150688E+10 | 33029359.22 | 0.678894E+09 | 0.281899E+09 | 0.396995E+09 | 0.00 | 0.00 |
August | 0.144943E+10 | 70748747.18 | 0.697280E+09 | 0.311467E+09 | 0.385813E+09 | 0.00 | 0.00 |
September | 0.145561E+10 | 0.207135E+09 | 0.785151E+09 | 0.428145E+09 | 0.357006E+09 | 0.00 | 0.00 |
October | 0.128419E+10 | 0.443412E+09 | 0.837764E+09 | 0.525471E+09 | 0.312293E+09 | 0.00 | 0.00 |
November | 0.984077E+09 | 0.824618E+09 | 0.809585E+09 | 0.560483E+09 | 0.249102E+09 | 0.00 | 0.00 |
December | 0.770175E+09 | 0.112616E+10 | 0.754004E+09 | 0.501250E+09 | 0.252754E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.142214E+11 | 0.598911E+10 | 0.913004E+10 | 0.507801E+10 | 0.405203E+10 | 0.00 | 0.00 |
Minimum of Months | 0.770175E+09 | 33029359.22 | 0.678894E+09 | 0.281899E+09 | 0.248243E+09 | 0.00 | 0.00 |
Maximum of Months | 0.157808E+10 | 0.112616E+10 | 0.837764E+09 | 0.560483E+09 | 0.425540E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.321201E+09 | 0.111336E+10 | 0.393177E+09 | 0.186243E+09 | 0.206934E+09 | 0.00 | 0.00 |
February | 0.372368E+09 | 0.898976E+09 | 0.405150E+09 | 0.178255E+09 | 0.226895E+09 | 0.00 | 0.00 |
March | 0.644611E+09 | 0.836707E+09 | 0.607809E+09 | 0.272131E+09 | 0.335679E+09 | 0.00 | 0.00 |
April | 0.964308E+09 | 0.419008E+09 | 0.676322E+09 | 0.305450E+09 | 0.370872E+09 | 0.00 | 0.00 |
May | 0.133477E+10 | 0.194159E+09 | 0.766082E+09 | 0.346491E+09 | 0.419592E+09 | 0.00 | 0.00 |
June | 0.157583E+10 | 61456673.22 | 0.733418E+09 | 0.335419E+09 | 0.397999E+09 | 0.00 | 0.00 |
July | 0.147687E+10 | 37013496.47 | 0.678285E+09 | 0.283120E+09 | 0.395165E+09 | 0.00 | 0.00 |
August | 0.130733E+10 | 79542446.17 | 0.640200E+09 | 0.270639E+09 | 0.369561E+09 | 0.00 | 0.00 |
September | 0.112186E+10 | 0.231363E+09 | 0.618721E+09 | 0.291790E+09 | 0.326931E+09 | 0.00 | 0.00 |
October | 0.777968E+09 | 0.509330E+09 | 0.547618E+09 | 0.272329E+09 | 0.275289E+09 | 0.00 | 0.00 |
November | 0.441543E+09 | 0.896319E+09 | 0.440022E+09 | 0.228541E+09 | 0.211481E+09 | 0.00 | 0.00 |
December | 0.281866E+09 | 0.121906E+10 | 0.375307E+09 | 0.169961E+09 | 0.205347E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106205E+11 | 0.649630E+10 | 0.688211E+10 | 0.314037E+10 | 0.374175E+10 | 0.00 | 0.00 |
Minimum of Months | 0.281866E+09 | 37013496.47 | 0.375307E+09 | 0.169961E+09 | 0.205347E+09 | 0.00 | 0.00 |
Maximum of Months | 0.157583E+10 | 0.121906E+10 | 0.766082E+09 | 0.346491E+09 | 0.419592E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.791388E+09 | 0.542730E+09 | 0.629944E+09 | 0.477327E+09 | 0.152617E+09 | 0.00 | 0.00 |
February | 0.689665E+09 | 0.429102E+09 | 0.535324E+09 | 0.379648E+09 | 0.155676E+09 | 0.00 | 0.00 |
March | 0.609281E+09 | 0.404110E+09 | 0.463649E+09 | 0.262681E+09 | 0.200968E+09 | 0.00 | 0.00 |
April | 0.500610E+09 | 0.200717E+09 | 0.312648E+09 | 0.117365E+09 | 0.195283E+09 | 0.00 | 0.00 |
May | 0.462057E+09 | 92117691.53 | 0.229261E+09 | 33621898.01 | 0.195639E+09 | 0.00 | 0.00 |
June | 0.524759E+09 | 28325532.63 | 0.189768E+09 | 11940416.18 | 0.177828E+09 | 0.00 | 0.00 |
July | 0.542497E+09 | 15847326.32 | 0.199138E+09 | 17655748.10 | 0.181483E+09 | 0.00 | 0.00 |
August | 0.598870E+09 | 34784293.92 | 0.251380E+09 | 63867778.53 | 0.187512E+09 | 0.00 | 0.00 |
September | 0.756769E+09 | 0.103376E+09 | 0.385250E+09 | 0.200156E+09 | 0.185094E+09 | 0.00 | 0.00 |
October | 0.868353E+09 | 0.225855E+09 | 0.546441E+09 | 0.371257E+09 | 0.175184E+09 | 0.00 | 0.00 |
November | 0.860111E+09 | 0.424569E+09 | 0.636463E+09 | 0.486824E+09 | 0.149639E+09 | 0.00 | 0.00 |
December | 0.798061E+09 | 0.584290E+09 | 0.646716E+09 | 0.485868E+09 | 0.160849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.800242E+10 | 0.308582E+10 | 0.502598E+10 | 0.290821E+10 | 0.211777E+10 | 0.00 | 0.00 |
Minimum of Months | 0.462057E+09 | 15847326.32 | 0.189768E+09 | 11940416.18 | 0.149639E+09 | 0.00 | 0.00 |
Maximum of Months | 0.868353E+09 | 0.584290E+09 | 0.646716E+09 | 0.486824E+09 | 0.200968E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 12081239.61 | 0.357751E+10 | 0.439260E+09 | 0.00 | 0.439260E+09 | 0.00 | 0.00 |
February | 96879023.89 | 0.283293E+10 | 0.484475E+09 | 0.00 | 0.484475E+09 | 0.00 | 0.00 |
March | 0.292548E+09 | 0.258870E+10 | 0.702098E+09 | 27794.05 | 0.702071E+09 | 0.00 | 0.00 |
April | 0.790759E+09 | 0.134760E+10 | 0.788991E+09 | 10051448.91 | 0.778939E+09 | 0.00 | 0.00 |
May | 0.154600E+10 | 0.713246E+09 | 0.963080E+09 | 70976604.89 | 0.892103E+09 | 0.00 | 0.00 |
June | 0.224973E+10 | 0.318879E+09 | 0.991122E+09 | 0.123506E+09 | 0.867616E+09 | 0.00 | 0.00 |
July | 0.213850E+10 | 0.255112E+09 | 0.946177E+09 | 92810752.99 | 0.853366E+09 | 0.00 | 0.00 |
August | 0.163685E+10 | 0.393439E+09 | 0.800234E+09 | 19038540.01 | 0.781195E+09 | 0.00 | 0.00 |
September | 0.113226E+10 | 0.818891E+09 | 0.673745E+09 | 851511.84 | 0.672893E+09 | 0.00 | 0.00 |
October | 0.506044E+09 | 0.157415E+10 | 0.577092E+09 | 0.00 | 0.577092E+09 | 0.00 | 0.00 |
November | 56731519.08 | 0.285438E+10 | 0.450855E+09 | 0.00 | 0.450855E+09 | 0.00 | 0.00 |
December | 8633472.43 | 0.385015E+10 | 0.435858E+09 | 0.00 | 0.435858E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104670E+11 | 0.211250E+11 | 0.825299E+10 | 0.317263E+09 | 0.793572E+10 | 0.00 | 0.00 |
Minimum of Months | 8633472.43 | 0.255112E+09 | 0.435858E+09 | 0.00 | 0.435858E+09 | 0.00 | 0.00 |
Maximum of Months | 0.224973E+10 | 0.385015E+10 | 0.991122E+09 | 0.123506E+09 | 0.892103E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8186585.38 | 0.369642E+10 | 0.439260E+09 | 0.00 | 0.439260E+09 | 0.00 | 0.00 |
February | 83744537.30 | 0.291628E+10 | 0.484475E+09 | 0.00 | 0.484475E+09 | 0.00 | 0.00 |
March | 0.265908E+09 | 0.265680E+10 | 0.702098E+09 | 27794.05 | 0.702071E+09 | 0.00 | 0.00 |
April | 0.761239E+09 | 0.138387E+10 | 0.788991E+09 | 10051448.91 | 0.778939E+09 | 0.00 | 0.00 |
May | 0.151254E+10 | 0.736047E+09 | 0.963080E+09 | 70976604.89 | 0.892103E+09 | 0.00 | 0.00 |
June | 0.221745E+10 | 0.332240E+09 | 0.991122E+09 | 0.123506E+09 | 0.867616E+09 | 0.00 | 0.00 |
July | 0.210496E+10 | 0.269048E+09 | 0.946177E+09 | 92810752.99 | 0.853366E+09 | 0.00 | 0.00 |
August | 0.160460E+10 | 0.411124E+09 | 0.800234E+09 | 19038540.01 | 0.781195E+09 | 0.00 | 0.00 |
September | 0.110703E+10 | 0.844632E+09 | 0.673745E+09 | 851511.84 | 0.672893E+09 | 0.00 | 0.00 |
October | 0.479457E+09 | 0.161685E+10 | 0.577092E+09 | 0.00 | 0.577092E+09 | 0.00 | 0.00 |
November | 45887337.38 | 0.294249E+10 | 0.450855E+09 | 0.00 | 0.450855E+09 | 0.00 | 0.00 |
December | 5262233.79 | 0.397981E+10 | 0.435858E+09 | 0.00 | 0.435858E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101963E+11 | 0.217856E+11 | 0.825299E+10 | 0.317263E+09 | 0.793572E+10 | 0.00 | 0.00 |
Minimum of Months | 5262233.79 | 0.269048E+09 | 0.435858E+09 | 0.00 | 0.435858E+09 | 0.00 | 0.00 |
Maximum of Months | 0.221745E+10 | 0.397981E+10 | 0.991122E+09 | 0.123506E+09 | 0.892103E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.841927E+09 | 0.262792E+10 | 0.111801E+10 | 0.664520E+09 | 0.453492E+09 | 0.00 | 0.00 |
February | 0.111546E+10 | 0.209672E+10 | 0.119275E+10 | 0.691384E+09 | 0.501370E+09 | 0.00 | 0.00 |
March | 0.149130E+10 | 0.195201E+10 | 0.145157E+10 | 0.749065E+09 | 0.702505E+09 | 0.00 | 0.00 |
April | 0.215481E+10 | 0.108711E+10 | 0.153350E+10 | 0.751243E+09 | 0.782258E+09 | 0.00 | 0.00 |
May | 0.269039E+10 | 0.666663E+09 | 0.158027E+10 | 0.731880E+09 | 0.848394E+09 | 0.00 | 0.00 |
June | 0.316553E+10 | 0.338144E+09 | 0.151638E+10 | 0.718287E+09 | 0.798097E+09 | 0.00 | 0.00 |
July | 0.301678E+10 | 0.294121E+09 | 0.142579E+10 | 0.629055E+09 | 0.796735E+09 | 0.00 | 0.00 |
August | 0.278437E+10 | 0.402334E+09 | 0.138581E+10 | 0.609598E+09 | 0.776210E+09 | 0.00 | 0.00 |
September | 0.258490E+10 | 0.682203E+09 | 0.141515E+10 | 0.739740E+09 | 0.675411E+09 | 0.00 | 0.00 |
October | 0.180987E+10 | 0.126644E+10 | 0.129042E+10 | 0.703122E+09 | 0.587293E+09 | 0.00 | 0.00 |
November | 0.118798E+10 | 0.210933E+10 | 0.122225E+10 | 0.752385E+09 | 0.469864E+09 | 0.00 | 0.00 |
December | 0.801887E+09 | 0.277799E+10 | 0.112943E+10 | 0.663121E+09 | 0.466314E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.236452E+11 | 0.163010E+11 | 0.162613E+11 | 0.840340E+10 | 0.785794E+10 | 0.00 | 0.00 |
Minimum of Months | 0.801887E+09 | 0.294121E+09 | 0.111801E+10 | 0.609598E+09 | 0.453492E+09 | 0.00 | 0.00 |
Maximum of Months | 0.316553E+10 | 0.277799E+10 | 0.158027E+10 | 0.752385E+09 | 0.848394E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.183299E+10 | 0.257751E+10 | 0.175414E+10 | 0.121506E+10 | 0.539075E+09 | 0.00 | 0.00 |
February | 0.165392E+10 | 0.210945E+10 | 0.152878E+10 | 0.966414E+09 | 0.562361E+09 | 0.00 | 0.00 |
March | 0.154727E+10 | 0.205037E+10 | 0.142092E+10 | 0.668678E+09 | 0.752246E+09 | 0.00 | 0.00 |
April | 0.146521E+10 | 0.114149E+10 | 0.106633E+10 | 0.302205E+09 | 0.764125E+09 | 0.00 | 0.00 |
May | 0.158199E+10 | 0.608909E+09 | 0.913741E+09 | 0.109917E+09 | 0.803824E+09 | 0.00 | 0.00 |
June | 0.194176E+10 | 0.254839E+09 | 0.822824E+09 | 72733058.04 | 0.750091E+09 | 0.00 | 0.00 |
July | 0.194249E+10 | 0.198130E+09 | 0.831269E+09 | 76759352.61 | 0.754510E+09 | 0.00 | 0.00 |
August | 0.194427E+10 | 0.319104E+09 | 0.914224E+09 | 0.169105E+09 | 0.745118E+09 | 0.00 | 0.00 |
September | 0.223593E+10 | 0.683060E+09 | 0.121163E+10 | 0.509800E+09 | 0.701835E+09 | 0.00 | 0.00 |
October | 0.229673E+10 | 0.126594E+10 | 0.158882E+10 | 0.945054E+09 | 0.643770E+09 | 0.00 | 0.00 |
November | 0.205921E+10 | 0.210055E+10 | 0.177470E+10 | 0.123924E+10 | 0.535467E+09 | 0.00 | 0.00 |
December | 0.183110E+10 | 0.269517E+10 | 0.179566E+10 | 0.123680E+10 | 0.558862E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223329E+11 | 0.160045E+11 | 0.156230E+11 | 0.751177E+10 | 0.811128E+10 | 0.00 | 0.00 |
Minimum of Months | 0.146521E+10 | 0.198130E+09 | 0.822824E+09 | 72733058.04 | 0.535467E+09 | 0.00 | 0.00 |
Maximum of Months | 0.229673E+10 | 0.269517E+10 | 0.179566E+10 | 0.123924E+10 | 0.803824E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.115225E+12 | -0.113468E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175750E+10 | 82.17 | 0.00 | 0.00 |
February | 0.104012E+12 | -0.102420E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.159143E+10 | 82.17 | 0.00 | 0.00 |
March | 0.112450E+12 | -0.110689E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176125E+10 | 82.17 | 0.00 | 0.00 |
April | 0.104203E+12 | -0.102506E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169754E+10 | 82.17 | 0.00 | 0.00 |
May | 0.102151E+12 | -0.100397E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175343E+10 | 82.17 | 0.00 | 0.00 |
June | 0.942140E+11 | -0.925171E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169686E+10 | 82.17 | 0.00 | 0.00 |
July | 0.945916E+11 | -0.928381E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
August | 0.946147E+11 | -0.928613E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
September | 0.942743E+11 | -0.925775E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169686E+10 | 82.17 | 0.00 | 0.00 |
October | 0.102236E+12 | -0.100482E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175343E+10 | 82.17 | 0.00 | 0.00 |
November | 0.104285E+12 | -0.102588E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169699E+10 | 82.17 | 0.00 | 0.00 |
December | 0.112508E+12 | -0.110750E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175730E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.123476E+13 | -0.121409E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206694E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.942140E+11 | -0.113468E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.176125E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.115225E+12 | -0.925171E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.159143E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804708E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164119662.2 | 82.17 | 0.00 | 0.00 |
February | 0.727159E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148230354.0 | 82.17 | 0.00 | 0.00 |
March | 0.804566E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164106015.3 | 82.17 | 0.00 | 0.00 |
April | 0.779700E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158799094.1 | 82.17 | 0.00 | 0.00 |
May | 0.804705E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164084726.0 | 82.17 | 0.00 | 0.00 |
June | 0.778855E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158787532.6 | 82.17 | 0.00 | 0.00 |
July | 0.805548E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164074051.4 | 82.17 | 0.00 | 0.00 |
August | 0.804704E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164079096.8 | 82.17 | 0.00 | 0.00 |
September | 0.779840E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158789523.4 | 82.17 | 0.00 | 0.00 |
October | 0.804565E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164091945.5 | 82.17 | 0.00 | 0.00 |
November | 0.778014E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158816414.2 | 82.17 | 0.00 | 0.00 |
December | 0.805552E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164120458.9 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947792E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193210E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727159E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164120458.9 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805552E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148230354.0 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.670274E+11 | -0.655153E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151203E+10 | 60.05 | 0.00 | 0.00 |
February | 0.605009E+11 | -0.591297E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.137126E+10 | 60.05 | 0.00 | 0.00 |
March | 0.646900E+11 | -0.631728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151721E+10 | 60.05 | 0.00 | 0.00 |
April | 0.585761E+11 | -0.571174E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145871E+10 | 60.05 | 0.00 | 0.00 |
May | 0.557646E+11 | -0.542582E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150638E+10 | 60.05 | 0.00 | 0.00 |
June | 0.499746E+11 | -0.485168E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145778E+10 | 60.05 | 0.00 | 0.00 |
July | 0.492073E+11 | -0.477009E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
August | 0.492763E+11 | -0.477700E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
September | 0.500046E+11 | -0.485468E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145778E+10 | 60.05 | 0.00 | 0.00 |
October | 0.558070E+11 | -0.543006E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
November | 0.586227E+11 | -0.571648E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145796E+10 | 60.05 | 0.00 | 0.00 |
December | 0.646765E+11 | -0.631648E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.151174E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.684128E+12 | -0.666358E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.177700E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.492073E+11 | -0.655153E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.151721E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.670274E+11 | -0.477009E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.137126E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_1 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167756E+11 | 33755.97 | 27-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118317E+11 | 36447.72 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.762460E+10 | 32807.28 | 02-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.891629E+09 | 14647.24 | 12-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19036.40 | 5.19 | 24-MAY-20:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87103.69 | 6.34 | 19-JUN-19:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 878652.47 | 6.90 | 06-JUL-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410745.76 | 6.66 | 30-AUG-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5033098.13 | 2490.54 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135858E+09 | 6603.04 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.940376E+10 | 25174.46 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.247782E+11 | 34403.17 | 27-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.714477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 19036.40 | 5.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247782E+11 | 36447.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.656019E+09 | 1698.35 | 28-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411996E+09 | 1704.53 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311455E+09 | 1575.27 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39806108.08 | 729.94 | 12-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4801617.01 | 389.56 | 25-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347417E+09 | 1531.68 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.871381E+09 | 1986.67 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.871381E+09 | 1986.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.233049E+09 | 792.69 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125851E+09 | 737.76 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42244275.68 | 695.75 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66054426.57 | 669.34 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401697E+09 | 798.37 | 27-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.868896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.401697E+09 | 798.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.258331E+11 | 40879.86 | 27-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177818E+11 | 43166.38 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120333E+11 | 39781.43 | 02-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188894E+10 | 20293.69 | 12-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21458494.95 | 3700.73 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 176763.55 | 5.36 | 29-JUN-19:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1474015.57 | 6.13 | 11-JUL-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 807334.66 | 5.68 | 03-AUG-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62325577.04 | 7435.19 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.622224E+09 | 11888.76 | 25-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150648E+11 | 31330.49 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.353354E+11 | 41188.26 | 27-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 176763.55 | 5.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.353354E+11 | 43166.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104691E+10 | 7487.38 | 27-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729812E+09 | 5804.06 | 14-FEB-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.408376E+09 | 8393.68 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43849484.03 | 5416.75 | 23-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2757495.67 | 4663.27 | 02-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1451.28 | 16.93 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 688645.48 | 3366.87 | 25-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6997791.73 | 4658.02 | 27-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.556496E+09 | 7390.42 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156314E+10 | 12219.82 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.435903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156314E+10 | 12219.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140369E+10 | 14781.01 | 27-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.912227E+09 | 14001.23 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.419681E+09 | 11932.05 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31504363.53 | 7334.34 | 06-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2974178.11 | 6087.32 | 01-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10114.45 | 146.15 | 24-JUN-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 269414.98 | 2041.69 | 24-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1895198.90 | 5972.31 | 25-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9841772.71 | 6078.44 | 20-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.683034E+09 | 10115.54 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203870E+10 | 14656.81 | 27-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203870E+10 | 14781.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.600921E+10 | 56171.50 | 12-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.410330E+10 | 58640.90 | 24-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167448E+10 | 55556.26 | 29-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45512088.61 | 29706.03 | 24-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6665551.77 | 27903.91 | 02-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2037431.56 | 31274.17 | 25-SEP-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40866685.24 | 32966.45 | 20-OCT-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.253307E+10 | 55616.27 | 21-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.963020E+10 | 60076.21 | 23-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.963020E+10 | 60076.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116326E+10 | 5206.66 | 28-JAN-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.750417E+09 | 5225.75 | 03-FEB-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450915E+09 | 4981.53 | 10-MAR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43669998.73 | 6011.04 | 17-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 195664.25 | 1630.54 | 03-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65655.43 | 656.55 | 29-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77058.00 | 540.18 | 19-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15267.08 | 152.67 | 16-AUG-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48971.30 | 416.98 | 24-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8529406.01 | 5327.90 | 06-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.623754E+09 | 5296.03 | 29-NOV-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165716E+10 | 12031.98 | 26-DEC-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15267.08 | 152.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165716E+10 | 12031.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147702E+10 | 5818.44 | 14-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.897036E+09 | 6576.61 | 12-FEB-21:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.483084E+09 | 7398.02 | 29-MAR-18:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38056150.50 | 4484.56 | 07-APR-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1000758.26 | 3646.21 | 02-MAY-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23662.75 | 315.50 | 17-AUG-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 715844.76 | 4001.37 | 30-SEP-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11644495.98 | 5656.08 | 24-OCT-18:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.763854E+09 | 6711.42 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208555E+10 | 12065.58 | 26-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.575798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208555E+10 | 12065.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.668229E+09 | 4175.53 | 27-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.454328E+09 | 3971.66 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.307104E+09 | 4033.24 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50372588.68 | 2025.14 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1381577.93 | 1007.03 | 10-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 105629.70 | 582.75 | 17-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2423091.02 | 930.80 | 11-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19790470.35 | 1085.61 | 06-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.395078E+09 | 3744.15 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880595E+09 | 4133.76 | 27-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.880595E+09 | 4175.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.852946E+09 | 4141.25 | 27-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542628E+09 | 3946.98 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302814E+09 | 4002.23 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40126654.86 | 2032.89 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1294693.55 | 1481.38 | 07-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 68054.04 | 700.84 | 02-JUN-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25305.90 | 379.59 | 19-JUL-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 137831.60 | 618.11 | 30-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1321905.10 | 1473.09 | 28-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13294737.65 | 1434.63 | 06-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.461843E+09 | 3723.56 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111202E+10 | 4099.88 | 27-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 25305.90 | 379.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111202E+10 | 4141.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.202442E+10 | 11948.76 | 14-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142318E+10 | 7488.94 | 25-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103841E+10 | 11331.17 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177296E+09 | 7961.24 | 17-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3726660.97 | 5574.72 | 12-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 563539.86 | 1305.34 | 07-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 458588.98 | 1530.21 | 09-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2942279.73 | 4220.32 | 25-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28655828.07 | 6986.79 | 06-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117569E+10 | 11455.98 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.283579E+10 | 17116.96 | 26-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.871112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.283579E+10 | 17116.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_0 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6 HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 15105964.57 | 1472.16 | 28-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12579235.95 | 1754.93 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1060490.28 | 339.46 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171429E+09 | 3136.35 | 27-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171429E+09 | 3136.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.192905E+10 | 12707.72 | 27-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141078E+10 | 13352.34 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.816536E+09 | 10201.27 | 02-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35909647.86 | 3689.84 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 120939.34 | 173.69 | 25-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.889295E+09 | 7453.28 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381758E+10 | 13445.91 | 27-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.381758E+10 | 13445.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.252385E+10 | 0.248305E+10 | 18358.05 | 01-JAN-16:12 | 18037.66 | 0.00 |
February | 0.00 | 0.00 | 0.328224E+10 | 0.325136E+10 | 18512.42 | 08-FEB-09:02 | 17207.12 | 0.00 |
March | 0.00 | 0.00 | 0.500805E+10 | 0.498527E+10 | 18776.90 | 11-MAR-16:12 | 17127.47 | 0.00 |
April | 0.00 | 0.00 | 0.883006E+10 | 0.871089E+10 | 19295.04 | 29-APR-08:62 | 16474.36 | 0.00 |
May | 0.00 | 0.00 | 0.123999E+11 | 0.118864E+11 | 20447.79 | 28-MAY-08:62 | 14382.85 | 0.00 |
June | 0.00 | 0.00 | 0.150171E+11 | 0.141033E+11 | 20629.93 | 28-JUN-08:62 | 13882.49 | 0.00 |
July | 0.00 | 0.00 | 0.169523E+11 | 0.141862E+11 | 22138.02 | 19-JUL-08:62 | 11367.37 | 0.00 |
August | 0.00 | 0.00 | 0.154314E+11 | 0.134184E+11 | 21061.85 | 14-AUG-08:62 | 13072.16 | 0.00 |
September | 0.00 | 0.00 | 0.137124E+11 | 0.118717E+11 | 21264.28 | 14-SEP-08:62 | 12865.10 | 0.00 |
October | 0.00 | 0.00 | 0.995878E+10 | 0.894608E+10 | 20920.63 | 04-OCT-08:62 | 13465.32 | 0.00 |
November | 0.00 | 0.00 | 0.447694E+10 | 0.436084E+10 | 19841.87 | 01-NOV-15:12 | 14779.01 | 0.00 |
December | 0.00 | 0.00 | 0.204983E+10 | 0.203427E+10 | 18289.97 | 25-DEC-16:12 | 18030.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109643E+12 | 0.100238E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.204983E+10 | 0.203427E+10 | 18289.97 | 11367.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169523E+11 | 0.141862E+11 | 22138.02 | 18037.66 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.991726E+09 | 0.968485E+09 | 18409.67 | 01-JAN-16:12 | 17530.78 | 0.00 |
February | 0.00 | 0.00 | 0.139892E+10 | 0.137501E+10 | 18120.40 | 18-FEB-19:21 | 18120.40 | 0.00 |
March | 0.00 | 0.00 | 0.258734E+10 | 0.256538E+10 | 18841.06 | 11-MAR-16:12 | 16608.46 | 0.00 |
April | 0.00 | 0.00 | 0.700867E+10 | 0.690231E+10 | 19905.43 | 29-APR-08:51 | 17245.53 | 0.00 |
May | 0.00 | 0.00 | 0.113558E+11 | 0.109014E+11 | 21418.45 | 28-MAY-08:51 | 14859.78 | 0.00 |
June | 0.00 | 0.00 | 0.144540E+11 | 0.136134E+11 | 21372.16 | 28-JUN-08:51 | 14271.22 | 0.00 |
July | 0.00 | 0.00 | 0.160905E+11 | 0.135178E+11 | 23967.29 | 21-JUL-08:51 | 10972.35 | 0.00 |
August | 0.00 | 0.00 | 0.139959E+11 | 0.121818E+11 | 22793.35 | 02-AUG-08:51 | 12366.24 | 0.00 |
September | 0.00 | 0.00 | 0.111745E+11 | 0.958223E+10 | 22667.85 | 22-SEP-08:51 | 12423.83 | 0.00 |
October | 0.00 | 0.00 | 0.638115E+10 | 0.553995E+10 | 21772.34 | 16-OCT-21:51 | 13768.13 | 0.00 |
November | 0.00 | 0.00 | 0.201301E+10 | 0.192720E+10 | 19876.22 | 02-NOV-19:21 | 15696.73 | 0.00 |
December | 0.00 | 0.00 | 0.684833E+09 | 0.677253E+09 | 18229.17 | 03-DEC-16:12 | 17488.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.881364E+11 | 0.797521E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.684833E+09 | 0.677253E+09 | 18120.40 | 10972.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.160905E+11 | 0.136134E+11 | 23967.29 | 18120.40 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.294682E+11 | 0.294620E+11 | 52617.48 | 12-JAN-14:30 | 52617.48 | 0.00 |
February | 0.00 | 0.00 | 0.302214E+11 | 0.302157E+11 | 50105.68 | 06-FEB-13:50 | 50105.68 | 0.00 |
March | 0.00 | 0.00 | 0.312545E+11 | 0.312533E+11 | 42038.83 | 14-MAR-14:10 | 42038.83 | 0.00 |
April | 0.00 | 0.00 | 0.413763E+11 | 0.413676E+11 | 44580.25 | 01-APR-14:10 | 44580.25 | 0.00 |
May | 0.00 | 0.00 | 0.505859E+11 | 0.500525E+11 | 41972.45 | 19-MAY-14:10 | 41972.45 | 0.00 |
June | 0.00 | 0.00 | 0.614629E+11 | 0.604566E+11 | 45961.53 | 15-JUN-14:10 | 45961.53 | 0.00 |
July | 0.00 | 0.00 | 0.692915E+11 | 0.631182E+11 | 48331.92 | 03-JUL-14:10 | 48331.92 | 0.00 |
August | 0.00 | 0.00 | 0.672541E+11 | 0.636240E+11 | 52599.58 | 27-AUG-14:10 | 52599.58 | 0.00 |
September | 0.00 | 0.00 | 0.684646E+11 | 0.647190E+11 | 61189.41 | 19-SEP-14:10 | 61189.41 | 0.00 |
October | 0.00 | 0.00 | 0.599340E+11 | 0.581515E+11 | 64309.59 | 18-OCT-14:10 | 62020.47 | 0.00 |
November | 0.00 | 0.00 | 0.406318E+11 | 0.405670E+11 | 55211.46 | 09-NOV-13:10 | 55211.46 | 0.00 |
December | 0.00 | 0.00 | 0.269011E+11 | 0.269011E+11 | 45886.80 | 16-DEC-13:30 | 45886.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.576846E+12 | 0.559889E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.269011E+11 | 0.269011E+11 | 41972.45 | 41972.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.692915E+11 | 0.647190E+11 | 64309.59 | 62020.47 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.113059E+11 | 0.109145E+11 | 127772.12 | 15-JAN-19:03 | 97934.68 | 0.00 |
February | 0.00 | 0.00 | 0.158035E+11 | 0.153881E+11 | 128924.41 | 13-FEB-19:02 | 99879.47 | 0.00 |
March | 0.00 | 0.00 | 0.247508E+11 | 0.244800E+11 | 127229.05 | 11-MAR-09:02 | 105831.92 | 0.00 |
April | 0.00 | 0.00 | 0.559680E+11 | 0.550527E+11 | 132770.02 | 18-APR-21:51 | 115979.46 | 0.00 |
May | 0.00 | 0.00 | 0.874980E+11 | 0.835151E+11 | 141555.46 | 28-MAY-08:51 | 101308.47 | 0.00 |
June | 0.00 | 0.00 | 0.111593E+12 | 0.103958E+12 | 141536.60 | 28-JUN-08:51 | 94734.00 | 0.00 |
July | 0.00 | 0.00 | 0.131536E+12 | 0.106047E+12 | 160272.71 | 21-JUL-08:51 | 71320.26 | 0.00 |
August | 0.00 | 0.00 | 0.112588E+12 | 0.950349E+11 | 152028.99 | 02-AUG-08:51 | 81929.79 | 0.00 |
September | 0.00 | 0.00 | 0.890242E+11 | 0.732405E+11 | 151431.95 | 03-SEP-21:51 | 83925.13 | 0.00 |
October | 0.00 | 0.00 | 0.565520E+11 | 0.483655E+11 | 147967.15 | 03-OCT-21:51 | 88202.47 | 0.00 |
November | 0.00 | 0.00 | 0.195217E+11 | 0.186730E+11 | 131627.02 | 02-NOV-19:21 | 104248.01 | 0.00 |
December | 0.00 | 0.00 | 0.843827E+10 | 0.834046E+10 | 121178.61 | 10-DEC-09:02 | 121178.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.724579E+12 | 0.643010E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.843827E+10 | 0.834046E+10 | 121178.61 | 71320.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.131536E+12 | 0.106047E+12 | 160272.71 | 121178.61 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.228159E+10 | 0.223614E+10 | 16324.94 | 24-JAN-09:02 | 14251.62 | 0.00 |
February | 0.00 | 0.00 | 0.334826E+10 | 0.331421E+10 | 16445.38 | 27-FEB-16:12 | 14298.86 | 0.00 |
March | 0.00 | 0.00 | 0.486990E+10 | 0.484617E+10 | 17012.00 | 11-MAR-09:02 | 12627.70 | 0.00 |
April | 0.00 | 0.00 | 0.890055E+10 | 0.877142E+10 | 16578.65 | 29-APR-08:62 | 14775.77 | 0.00 |
May | 0.00 | 0.00 | 0.123983E+11 | 0.118688E+11 | 17288.92 | 23-MAY-08:62 | 13532.60 | 0.00 |
June | 0.00 | 0.00 | 0.151511E+11 | 0.142106E+11 | 17870.55 | 29-JUN-08:62 | 12192.28 | 0.00 |
July | 0.00 | 0.00 | 0.171118E+11 | 0.142796E+11 | 19326.58 | 19-JUL-08:62 | 9803.69 | 0.00 |
August | 0.00 | 0.00 | 0.155196E+11 | 0.134540E+11 | 18358.17 | 14-AUG-08:62 | 11322.60 | 0.00 |
September | 0.00 | 0.00 | 0.136335E+11 | 0.117278E+11 | 18115.80 | 22-SEP-08:62 | 11999.08 | 0.00 |
October | 0.00 | 0.00 | 0.932796E+10 | 0.833052E+10 | 18037.36 | 04-OCT-08:62 | 12033.20 | 0.00 |
November | 0.00 | 0.00 | 0.420557E+10 | 0.409608E+10 | 17211.30 | 01-NOV-15:12 | 12614.53 | 0.00 |
December | 0.00 | 0.00 | 0.190321E+10 | 0.188501E+10 | 15949.27 | 11-DEC-09:02 | 15552.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108651E+12 | 0.990205E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.190321E+10 | 0.188501E+10 | 15949.27 | 9803.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.171118E+11 | 0.142796E+11 | 19326.58 | 15552.33 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.762759E+09 | 0.736496E+09 | 16078.53 | 01-JAN-16:12 | 14452.65 | 0.00 |
February | 0.00 | 0.00 | 0.152666E+10 | 0.149749E+10 | 16311.43 | 28-FEB-09:02 | 14143.47 | 0.00 |
March | 0.00 | 0.00 | 0.276184E+10 | 0.273883E+10 | 16867.50 | 11-MAR-09:02 | 12589.33 | 0.00 |
April | 0.00 | 0.00 | 0.711042E+10 | 0.699669E+10 | 17793.36 | 29-APR-08:32 | 16246.99 | 0.00 |
May | 0.00 | 0.00 | 0.110780E+11 | 0.106034E+11 | 19088.21 | 28-MAY-08:32 | 14317.88 | 0.00 |
June | 0.00 | 0.00 | 0.143471E+11 | 0.134786E+11 | 19014.84 | 30-JUN-08:32 | 14424.68 | 0.00 |
July | 0.00 | 0.00 | 0.160129E+11 | 0.133962E+11 | 21118.19 | 21-JUL-08:32 | 11126.93 | 0.00 |
August | 0.00 | 0.00 | 0.138569E+11 | 0.119937E+11 | 20113.73 | 02-AUG-08:32 | 12405.62 | 0.00 |
September | 0.00 | 0.00 | 0.108267E+11 | 0.917472E+10 | 19985.60 | 09-SEP-08:32 | 12819.18 | 0.00 |
October | 0.00 | 0.00 | 0.600873E+10 | 0.520648E+10 | 19070.93 | 04-OCT-08:51 | 12206.84 | 0.00 |
November | 0.00 | 0.00 | 0.181572E+10 | 0.173913E+10 | 17213.09 | 02-NOV-19:21 | 12988.43 | 0.00 |
December | 0.00 | 0.00 | 0.594649E+09 | 0.584731E+09 | 15840.64 | 11-DEC-09:02 | 15388.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.867024E+11 | 0.781465E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.594649E+09 | 0.584731E+09 | 15840.64 | 11126.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.160129E+11 | 0.134786E+11 | 21118.19 | 16246.99 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.440784E+09 | 0.435067E+09 | 5211.60 | 01-JAN-16:12 | 5106.39 | 0.00 |
February | 0.00 | 0.00 | 0.646379E+09 | 0.643284E+09 | 5140.94 | 26-FEB-16:12 | 5140.94 | 0.00 |
March | 0.00 | 0.00 | 0.109657E+10 | 0.109287E+10 | 5394.84 | 11-MAR-16:12 | 4718.66 | 0.00 |
April | 0.00 | 0.00 | 0.221652E+10 | 0.218805E+10 | 5485.23 | 29-APR-08:62 | 4637.48 | 0.00 |
May | 0.00 | 0.00 | 0.327069E+10 | 0.314080E+10 | 5842.61 | 28-MAY-08:62 | 3990.06 | 0.00 |
June | 0.00 | 0.00 | 0.415014E+10 | 0.391543E+10 | 5896.64 | 28-JUN-08:62 | 3851.13 | 0.00 |
July | 0.00 | 0.00 | 0.464573E+10 | 0.393567E+10 | 6383.13 | 19-JUL-08:62 | 3045.98 | 0.00 |
August | 0.00 | 0.00 | 0.417792E+10 | 0.366493E+10 | 6022.15 | 14-AUG-08:62 | 3524.04 | 0.00 |
September | 0.00 | 0.00 | 0.360342E+10 | 0.314567E+10 | 6113.37 | 04-SEP-08:62 | 3503.34 | 0.00 |
October | 0.00 | 0.00 | 0.238086E+10 | 0.214318E+10 | 6002.05 | 04-OCT-08:62 | 3671.25 | 0.00 |
November | 0.00 | 0.00 | 0.935754E+09 | 0.912854E+09 | 5483.24 | 02-NOV-18:02 | 4553.88 | 0.00 |
December | 0.00 | 0.00 | 0.336168E+09 | 0.334191E+09 | 5205.42 | 03-DEC-16:12 | 5014.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.279009E+11 | 0.255520E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.336168E+09 | 0.334191E+09 | 5140.94 | 3045.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.464573E+10 | 0.393567E+10 | 6383.13 | 5140.94 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127771E+09 | 0.125026E+09 | 5233.70 | 01-JAN-16:12 | 4916.14 | 0.00 |
February | 0.00 | 0.00 | 0.218203E+09 | 0.216837E+09 | 5136.89 | 18-FEB-19:21 | 5136.89 | 0.00 |
March | 0.00 | 0.00 | 0.507300E+09 | 0.503980E+09 | 5434.50 | 11-MAR-16:12 | 4501.51 | 0.00 |
April | 0.00 | 0.00 | 0.178539E+10 | 0.175980E+10 | 5625.84 | 29-APR-08:51 | 4875.28 | 0.00 |
May | 0.00 | 0.00 | 0.304431E+10 | 0.292879E+10 | 6073.24 | 28-MAY-08:51 | 4214.25 | 0.00 |
June | 0.00 | 0.00 | 0.403516E+10 | 0.381821E+10 | 6069.47 | 28-JUN-08:51 | 4044.47 | 0.00 |
July | 0.00 | 0.00 | 0.445549E+10 | 0.379392E+10 | 6785.68 | 21-JUL-08:51 | 3130.35 | 0.00 |
August | 0.00 | 0.00 | 0.384709E+10 | 0.338219E+10 | 6421.00 | 02-AUG-08:51 | 3536.89 | 0.00 |
September | 0.00 | 0.00 | 0.300170E+10 | 0.260310E+10 | 6446.20 | 22-SEP-08:51 | 3464.72 | 0.00 |
October | 0.00 | 0.00 | 0.151515E+10 | 0.131816E+10 | 6157.71 | 16-OCT-21:51 | 3905.26 | 0.00 |
November | 0.00 | 0.00 | 0.348061E+09 | 0.332718E+09 | 5612.22 | 02-NOV-19:21 | 4384.92 | 0.00 |
December | 0.00 | 0.00 | 75076453.43 | 74354936.96 | 5169.38 | 04-DEC-16:12 | 5024.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.229607E+11 | 0.208571E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 75076453.43 | 74354936.96 | 5136.89 | 3130.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.445549E+10 | 0.381821E+10 | 6785.68 | 5136.89 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.615113E+10 | 0.606746E+10 | 24826.18 | 16-JAN-16:12 | 20967.27 | 0.00 |
February | 0.00 | 0.00 | 0.654719E+10 | 0.650175E+10 | 24748.76 | 14-FEB-09:02 | 21354.80 | 0.00 |
March | 0.00 | 0.00 | 0.724153E+10 | 0.720834E+10 | 24664.82 | 11-MAR-16:12 | 21796.70 | 0.00 |
April | 0.00 | 0.00 | 0.114455E+11 | 0.112634E+11 | 25096.08 | 30-APR-08:62 | 21041.34 | 0.00 |
May | 0.00 | 0.00 | 0.155492E+11 | 0.147747E+11 | 26747.06 | 28-MAY-08:62 | 18556.58 | 0.00 |
June | 0.00 | 0.00 | 0.198570E+11 | 0.184835E+11 | 27033.63 | 28-JUN-08:62 | 17477.51 | 0.00 |
July | 0.00 | 0.00 | 0.233415E+11 | 0.191965E+11 | 29567.37 | 19-JUL-08:62 | 13608.33 | 0.00 |
August | 0.00 | 0.00 | 0.217477E+11 | 0.187019E+11 | 27656.37 | 18-AUG-08:62 | 16844.27 | 0.00 |
September | 0.00 | 0.00 | 0.202738E+11 | 0.174624E+11 | 28121.76 | 14-SEP-08:62 | 16030.21 | 0.00 |
October | 0.00 | 0.00 | 0.156741E+11 | 0.141391E+11 | 27509.05 | 04-OCT-08:62 | 17090.42 | 0.00 |
November | 0.00 | 0.00 | 0.887989E+10 | 0.869940E+10 | 25892.51 | 01-NOV-15:12 | 18664.48 | 0.00 |
December | 0.00 | 0.00 | 0.562600E+10 | 0.558791E+10 | 24234.76 | 14-DEC-16:12 | 22500.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162335E+12 | 0.148086E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.562600E+10 | 0.558791E+10 | 24234.76 | 13608.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.233415E+11 | 0.191965E+11 | 29567.37 | 22500.59 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.633590E+10 | 0.418916E+10 | 8322.95 | 12-JAN-15:10 | 6941.15 | 0.00 |
February | 0.00 | 0.00 | 0.768503E+10 | 0.583399E+10 | 8425.59 | 20-FEB-13:00 | 7519.32 | 0.00 |
March | 0.00 | 0.00 | 0.103012E+11 | 0.835122E+10 | 9077.37 | 14-MAR-18:03 | 8707.45 | 0.00 |
April | 0.00 | 0.00 | 0.157559E+11 | 0.140423E+11 | 12274.79 | 19-APR-18:03 | 12274.79 | 0.00 |
May | 0.00 | 0.00 | 0.217786E+11 | 0.192656E+11 | 15110.20 | 19-MAY-18:15 | 15110.20 | 0.00 |
June | 0.00 | 0.00 | 0.268933E+11 | 0.238556E+11 | 17974.80 | 15-JUN-18:13 | 17974.80 | 0.00 |
July | 0.00 | 0.00 | 0.320658E+11 | 0.243467E+11 | 19385.20 | 26-JUL-18:15 | 16559.02 | 0.00 |
August | 0.00 | 0.00 | 0.286857E+11 | 0.228129E+11 | 17209.56 | 07-AUG-18:15 | 15917.84 | 0.00 |
September | 0.00 | 0.00 | 0.255983E+11 | 0.199287E+11 | 15721.15 | 01-SEP-18:15 | 13524.62 | 0.00 |
October | 0.00 | 0.00 | 0.193837E+11 | 0.152038E+11 | 15356.87 | 04-OCT-18:15 | 12135.78 | 0.00 |
November | 0.00 | 0.00 | 0.991592E+10 | 0.770715E+10 | 10867.16 | 03-NOV-15:10 | 9286.23 | 0.00 |
December | 0.00 | 0.00 | 0.514966E+10 | 0.328912E+10 | 7097.95 | 10-DEC-12:30 | 5048.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.209549E+12 | 0.168826E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.514966E+10 | 0.328912E+10 | 7097.95 | 5048.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.320658E+11 | 0.243467E+11 | 19385.20 | 17974.80 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115869E+10 | 0.787723E+09 | 5727.14 | 12-JAN-13:30 | 4558.37 | 0.00 |
February | 0.00 | 0.00 | 0.228111E+10 | 0.181653E+10 | 6678.60 | 22-FEB-13:30 | 6222.61 | 0.00 |
March | 0.00 | 0.00 | 0.399753E+10 | 0.341464E+10 | 6746.98 | 14-MAR-15:10 | 6746.98 | 0.00 |
April | 0.00 | 0.00 | 0.867248E+10 | 0.802773E+10 | 9415.01 | 30-APR-13:00 | 9415.01 | 0.00 |
May | 0.00 | 0.00 | 0.128315E+11 | 0.118750E+11 | 10322.25 | 30-MAY-14:10 | 10322.25 | 0.00 |
June | 0.00 | 0.00 | 0.168507E+11 | 0.157031E+11 | 11384.16 | 02-JUN-13:40 | 11384.16 | 0.00 |
July | 0.00 | 0.00 | 0.187326E+11 | 0.160337E+11 | 12162.75 | 03-JUL-12:50 | 12144.54 | 0.00 |
August | 0.00 | 0.00 | 0.168605E+11 | 0.147828E+11 | 12191.01 | 03-AUG-12:50 | 11027.37 | 0.00 |
September | 0.00 | 0.00 | 0.142510E+11 | 0.123043E+11 | 12119.13 | 02-SEP-13:10 | 11020.43 | 0.00 |
October | 0.00 | 0.00 | 0.925484E+10 | 0.788846E+10 | 11266.96 | 03-OCT-13:40 | 10648.98 | 0.00 |
November | 0.00 | 0.00 | 0.343197E+10 | 0.281720E+10 | 7407.95 | 03-NOV-13:10 | 6385.76 | 0.00 |
December | 0.00 | 0.00 | 0.621115E+09 | 0.390890E+09 | 4157.98 | 16-DEC-12:50 | 2999.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108944E+12 | 0.958419E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.621115E+09 | 0.390890E+09 | 4157.98 | 2999.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.187326E+11 | 0.160337E+11 | 12191.01 | 12144.54 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_1 COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167103E+10 | 0.165772E+10 | 23153.03 | 03-JAN-15:00 | 23153.03 | 0.00 |
February | 0.00 | 0.00 | 0.825143E+10 | 0.822754E+10 | 34224.30 | 20-FEB-15:00 | 34224.30 | 0.00 |
March | 0.00 | 0.00 | 0.166713E+11 | 0.166657E+11 | 44048.47 | 14-MAR-18:03 | 44048.47 | 0.00 |
April | 0.00 | 0.00 | 0.595787E+11 | 0.592229E+11 | 75722.52 | 19-APR-18:30 | 75722.52 | 0.00 |
May | 0.00 | 0.00 | 0.105134E+12 | 0.102267E+12 | 86159.60 | 19-MAY-18:15 | 86159.60 | 0.00 |
June | 0.00 | 0.00 | 0.144144E+12 | 0.139307E+12 | 100379.67 | 14-JUN-18:17 | 100379.67 | 0.00 |
July | 0.00 | 0.00 | 0.179510E+12 | 0.142771E+12 | 119229.05 | 18-JUL-21:00 | 36684.82 | 0.00 |
August | 0.00 | 0.00 | 0.149832E+12 | 0.130477E+12 | 116032.97 | 01-AUG-20:54 | 50068.15 | 0.00 |
September | 0.00 | 0.00 | 0.118857E+12 | 0.994103E+11 | 85874.97 | 22-SEP-20:10 | 70396.34 | 0.00 |
October | 0.00 | 0.00 | 0.588717E+11 | 0.523412E+11 | 97133.93 | 03-OCT-19:53 | 56169.96 | 0.00 |
November | 0.00 | 0.00 | 0.107501E+11 | 0.105257E+11 | 42533.11 | 03-NOV-15:13 | 42533.11 | 0.00 |
December | 0.00 | 0.00 | 0.996999E+09 | 0.996603E+09 | 14375.10 | 23-DEC-15:00 | 14375.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.854268E+12 | 0.763870E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.996999E+09 | 0.996603E+09 | 14375.10 | 14375.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.179510E+12 | 0.142771E+12 | 119229.05 | 100379.67 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_6 COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.156399E+10 | 0.155506E+10 | 20663.44 | 03-JAN-15:00 | 20663.44 | 0.00 |
February | 0.00 | 0.00 | 0.763544E+10 | 0.761989E+10 | 30973.48 | 22-FEB-16:10 | 30973.48 | 0.00 |
March | 0.00 | 0.00 | 0.161106E+11 | 0.161060E+11 | 41072.48 | 14-MAR-16:00 | 41072.48 | 0.00 |
April | 0.00 | 0.00 | 0.590397E+11 | 0.588351E+11 | 68933.15 | 19-APR-21:10 | 68933.15 | 0.00 |
May | 0.00 | 0.00 | 0.104467E+12 | 0.102447E+12 | 79945.93 | 19-MAY-18:03 | 79945.93 | 0.00 |
June | 0.00 | 0.00 | 0.142959E+12 | 0.139393E+12 | 93638.95 | 14-JUN-18:03 | 93638.95 | 0.00 |
July | 0.00 | 0.00 | 0.179197E+12 | 0.142203E+12 | 110272.33 | 21-JUL-18:10 | 73401.27 | 0.00 |
August | 0.00 | 0.00 | 0.145332E+12 | 0.127782E+12 | 111179.26 | 01-AUG-21:52 | 49704.60 | 0.00 |
September | 0.00 | 0.00 | 0.111835E+12 | 0.938718E+11 | 80027.66 | 01-SEP-21:10 | 60117.86 | 0.00 |
October | 0.00 | 0.00 | 0.530595E+11 | 0.473480E+11 | 83704.30 | 03-OCT-20:03 | 47744.44 | 0.00 |
November | 0.00 | 0.00 | 0.963134E+10 | 0.945621E+10 | 37389.27 | 03-NOV-15:13 | 37389.27 | 0.00 |
December | 0.00 | 0.00 | 0.966478E+09 | 0.966235E+09 | 12995.63 | 10-DEC-15:00 | 12995.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.831798E+12 | 0.747583E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.966478E+09 | 0.966235E+09 | 12995.63 | 12995.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.179197E+12 | 0.142203E+12 | 111179.26 | 93638.95 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_0 COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.458228E+09 | 0.426533E+09 | 10510.21 | 03-JAN-19:03 | 10510.21 | 0.00 |
February | 0.00 | 0.00 | 0.132848E+10 | 0.132139E+10 | 12254.08 | 06-FEB-22:00 | 12254.08 | 0.00 |
March | 0.00 | 0.00 | 0.231786E+10 | 0.231743E+10 | 14955.70 | 14-MAR-18:10 | 14955.70 | 0.00 |
April | 0.00 | 0.00 | 0.168974E+11 | 0.166480E+11 | 26326.56 | 19-APR-19:20 | 26326.56 | 0.00 |
May | 0.00 | 0.00 | 0.347015E+11 | 0.327104E+11 | 32093.96 | 24-MAY-20:02 | 22730.16 | 0.00 |
June | 0.00 | 0.00 | 0.515713E+11 | 0.472541E+11 | 36116.75 | 05-JUN-19:20 | 36116.75 | 0.00 |
July | 0.00 | 0.00 | 0.789102E+11 | 0.563317E+11 | 68383.96 | 18-JUL-20:12 | 29324.87 | 0.00 |
August | 0.00 | 0.00 | 0.730309E+11 | 0.570498E+11 | 66620.17 | 01-AUG-20:50 | 31838.61 | 0.00 |
September | 0.00 | 0.00 | 0.656459E+11 | 0.484643E+11 | 53581.40 | 09-SEP-20:10 | 28799.92 | 0.00 |
October | 0.00 | 0.00 | 0.355059E+11 | 0.279053E+11 | 62185.71 | 03-OCT-19:53 | 33686.33 | 0.00 |
November | 0.00 | 0.00 | 0.747556E+10 | 0.681879E+10 | 24714.56 | 09-NOV-21:00 | 22605.25 | 0.00 |
December | 0.00 | 0.00 | 0.890335E+09 | 0.817787E+09 | 9780.72 | 15-DEC-20:20 | 9780.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.368733E+12 | 0.298066E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.458228E+09 | 0.426533E+09 | 9780.72 | 9780.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.789102E+11 | 0.570498E+11 | 68383.96 | 36116.75 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.131327E+09 | 0.131323E+09 | 11535.33 | 03-JAN-19:03 | 11535.33 | 0.00 |
February | 0.00 | 0.00 | 0.238915E+10 | 0.238888E+10 | 19861.56 | 06-FEB-22:00 | 19861.56 | 0.00 |
March | 0.00 | 0.00 | 0.686628E+10 | 0.686627E+10 | 36501.12 | 14-MAR-18:08 | 36501.12 | 0.00 |
April | 0.00 | 0.00 | 0.308719E+11 | 0.306771E+11 | 46448.02 | 28-APR-20:00 | 46114.87 | 0.00 |
May | 0.00 | 0.00 | 0.524480E+11 | 0.509559E+11 | 57886.56 | 24-MAY-20:02 | 42919.36 | 0.00 |
June | 0.00 | 0.00 | 0.655122E+11 | 0.630287E+11 | 60948.02 | 23-JUN-19:53 | 40342.49 | 0.00 |
July | 0.00 | 0.00 | 0.778585E+11 | 0.670442E+11 | 81105.63 | 20-JUL-21:51 | 23423.12 | 0.00 |
August | 0.00 | 0.00 | 0.687321E+11 | 0.613504E+11 | 79489.06 | 01-AUG-20:45 | 38007.76 | 0.00 |
September | 0.00 | 0.00 | 0.536733E+11 | 0.469235E+11 | 67663.93 | 09-SEP-20:00 | 36839.01 | 0.00 |
October | 0.00 | 0.00 | 0.274272E+11 | 0.244344E+11 | 78080.65 | 03-OCT-19:53 | 42384.48 | 0.00 |
November | 0.00 | 0.00 | 0.249760E+10 | 0.244774E+10 | 27064.04 | 09-NOV-21:00 | 26540.55 | 0.00 |
December | 0.00 | 0.00 | 2511892.48 | 2511802.19 | 1309.90 | 15-DEC-20:10 | 1309.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.388410E+12 | 0.356251E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2511892.48 | 2511802.19 | 1309.90 | 1309.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.778585E+11 | 0.670442E+11 | 81105.63 | 46114.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.109924E+09 | 0.108390E+09 | 5780.80 | 03-JAN-14:20 | 5780.80 | 0.00 |
February | 0.00 | 0.00 | 0.143714E+10 | 0.143712E+10 | 13365.07 | 20-FEB-15:00 | 13365.07 | 0.00 |
March | 0.00 | 0.00 | 0.283455E+10 | 0.283455E+10 | 15952.19 | 14-MAR-15:10 | 15952.19 | 0.00 |
April | 0.00 | 0.00 | 0.143480E+11 | 0.142290E+11 | 20673.68 | 21-APR-15:10 | 20673.68 | 0.00 |
May | 0.00 | 0.00 | 0.271340E+11 | 0.259399E+11 | 22743.96 | 30-MAY-15:10 | 22743.96 | 0.00 |
June | 0.00 | 0.00 | 0.409995E+11 | 0.379102E+11 | 26011.08 | 02-JUN-16:00 | 26011.08 | 0.00 |
July | 0.00 | 0.00 | 0.536560E+11 | 0.392500E+11 | 31046.88 | 18-JUL-20:12 | 13136.65 | 0.00 |
August | 0.00 | 0.00 | 0.434693E+11 | 0.351405E+11 | 27515.33 | 02-AUG-21:10 | 17135.88 | 0.00 |
September | 0.00 | 0.00 | 0.324818E+11 | 0.261315E+11 | 27491.69 | 09-SEP-12:30 | 21049.43 | 0.00 |
October | 0.00 | 0.00 | 0.151974E+11 | 0.130692E+11 | 27659.55 | 04-OCT-15:20 | 22429.03 | 0.00 |
November | 0.00 | 0.00 | 0.189386E+10 | 0.184816E+10 | 16663.95 | 03-NOV-15:10 | 16029.91 | 0.00 |
December | 0.00 | 0.00 | 929370.12 | 929370.12 | 566.75 | 09-DEC-13:00 | 566.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.233563E+12 | 0.197900E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 929370.12 | 929370.12 | 566.75 | 566.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.536560E+11 | 0.392500E+11 | 31046.88 | 26011.08 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.881057E+09 | 0.869089E+09 | 17881.23 | 03-JAN-17:00 | 17881.23 | 0.00 |
February | 0.00 | 0.00 | 0.578059E+10 | 0.576935E+10 | 25743.36 | 20-FEB-16:12 | 25743.36 | 0.00 |
March | 0.00 | 0.00 | 0.121363E+11 | 0.120412E+11 | 39385.98 | 14-MAR-17:15 | 32244.15 | 0.00 |
April | 0.00 | 0.00 | 0.382709E+11 | 0.352401E+11 | 45341.63 | 29-APR-10:40 | 35375.55 | 0.00 |
May | 0.00 | 0.00 | 0.644385E+11 | 0.554112E+11 | 49818.03 | 21-MAY-17:20 | 34980.16 | 0.00 |
June | 0.00 | 0.00 | 0.811642E+11 | 0.682218E+11 | 50602.59 | 28-JUN-10:50 | 30864.30 | 0.00 |
July | 0.00 | 0.00 | 0.100835E+12 | 0.714906E+11 | 67944.81 | 21-JUL-08:00 | 22770.12 | 0.00 |
August | 0.00 | 0.00 | 0.874195E+11 | 0.659104E+11 | 61385.91 | 02-AUG-07:50 | 29502.87 | 0.00 |
September | 0.00 | 0.00 | 0.698339E+11 | 0.519296E+11 | 54979.67 | 09-SEP-09:20 | 30472.93 | 0.00 |
October | 0.00 | 0.00 | 0.371468E+11 | 0.300842E+11 | 51558.31 | 03-OCT-17:17 | 30794.45 | 0.00 |
November | 0.00 | 0.00 | 0.679439E+10 | 0.658323E+10 | 35255.43 | 03-NOV-16:00 | 30715.82 | 0.00 |
December | 0.00 | 0.00 | 0.390999E+09 | 0.390999E+09 | 9140.58 | 09-DEC-13:00 | 9140.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.505092E+12 | 0.403942E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.390999E+09 | 0.390999E+09 | 9140.58 | 9140.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100835E+12 | 0.714906E+11 | 67944.81 | 35375.55 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 21537.34 | 118369.04 | 28-JAN-06:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16388.32 | 123877.52 | 03-FEB-07:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 9294.39 | 119069.24 | 02-MAR-05:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1260.04 | 44784.63 | 11-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.58 | 29720.38 | 02-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.22 | 706.65 | 02-JUN-08:14 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1.77 | 1304.95 | 07-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1.13 | 1902.82 | 24-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.90 | 34929.44 | 25-SEP-08:54 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 334.63 | 38196.01 | 20-OCT-08:54 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12277.24 | 96168.88 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 30868.25 | 171612.16 | 26-DEC-16:12 |
Annual Sum or Average | 0.00 | 7642.41 | ||||
Minimum of Months | 0.00 | 0.00 | 0.22 | 706.65 | ||
Maximum of Months | 0.00 | 0.00 | 30868.25 | 171612.16 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 24354.76 | 51173.74 | 30-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 24335.99 | 51168.54 | 01-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 23481.45 | 50214.18 | 01-MAR-07:53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 21933.68 | 47296.74 | 03-APR-06:55 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20157.81 | 43944.16 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18620.16 | 40266.14 | 01-JUN-06:51 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 17713.04 | 37551.08 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17738.79 | 37702.22 | 31-AUG-06:55 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18631.73 | 40211.27 | 29-SEP-06:29 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20173.61 | 44003.88 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21951.94 | 47565.91 | 30-NOV-07:53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23478.45 | 50118.25 | 29-DEC-07:55 |
Annual Sum or Average | 0.00 | 21028.95 | ||||
Minimum of Months | 0.00 | 0.00 | 17713.04 | 37551.08 | ||
Maximum of Months | 0.00 | 0.00 | 24354.76 | 51173.74 |
Report: FanReportMonthly
For: VAV_FLR_1 FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108460E+11 | 1.08 | 6352.20 | 12-JAN-21:10 | 1.30 |
February | 0.997459E+10 | 1.09 | 7013.00 | 21-FEB-21:10 | 1.37 |
March | 0.113764E+11 | 1.10 | 7660.40 | 16-MAR-20:10 | 1.42 |
April | 0.124341E+11 | 1.15 | 10074.45 | 19-APR-20:10 | 1.58 |
May | 0.143135E+11 | 1.20 | 11312.33 | 19-MAY-20:10 | 1.66 |
June | 0.158106E+11 | 1.26 | 12622.01 | 15-JUN-20:10 | 1.74 |
July | 0.160229E+11 | 1.24 | 12124.21 | 25-JUL-20:10 | 1.69 |
August | 0.157482E+11 | 1.24 | 12092.55 | 04-AUG-20:10 | 1.69 |
September | 0.145814E+11 | 1.22 | 10729.75 | 19-SEP-20:10 | 1.61 |
October | 0.133902E+11 | 1.17 | 10209.87 | 04-OCT-20:10 | 1.57 |
November | 0.111360E+11 | 1.11 | 8391.71 | 09-NOV-21:10 | 1.46 |
December | 0.106953E+11 | 1.08 | 5857.20 | 15-DEC-22:00 | 1.27 |
Annual Sum or Average | 0.156329E+12 | 1.16 | |||
Minimum of Months | 0.997459E+10 | 1.08 | 5857.20 | 1.27 | |
Maximum of Months | 0.160229E+11 | 1.26 | 12622.01 | 1.74 |
Report: FanReportMonthly
For: VAV_FLR_6 FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112325E+11 | 1.21 | 6844.36 | 03-JAN-22:10 | 1.49 |
February | 0.104687E+11 | 1.23 | 7754.50 | 06-FEB-22:10 | 1.58 |
March | 0.122494E+11 | 1.26 | 8538.32 | 15-MAR-21:10 | 1.64 |
April | 0.138045E+11 | 1.33 | 10201.75 | 19-APR-21:10 | 1.76 |
May | 0.160250E+11 | 1.39 | 10795.20 | 19-MAY-21:10 | 1.80 |
June | 0.174712E+11 | 1.46 | 11316.75 | 05-JUN-21:10 | 1.84 |
July | 0.176483E+11 | 1.44 | 11089.05 | 25-JUL-21:10 | 1.81 |
August | 0.169372E+11 | 1.42 | 11186.08 | 07-AUG-21:10 | 1.82 |
September | 0.150331E+11 | 1.37 | 9995.80 | 12-SEP-21:10 | 1.73 |
October | 0.135093E+11 | 1.29 | 9572.55 | 04-OCT-21:10 | 1.70 |
November | 0.113225E+11 | 1.23 | 8302.45 | 09-NOV-22:10 | 1.61 |
December | 0.110422E+11 | 1.21 | 6934.54 | 15-DEC-22:10 | 1.50 |
Annual Sum or Average | 0.166744E+12 | 1.32 | |||
Minimum of Months | 0.104687E+11 | 1.21 | 6844.36 | 1.49 | |
Maximum of Months | 0.176483E+11 | 1.46 | 11316.75 | 1.84 |
Report: FanReportMonthly
For: VAV_FLR_0 SZVAV FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.675164E+10 | 1.26 | 2520.77 | 01-JAN-05:10 | 1.26 |
February | 0.609826E+10 | 1.26 | 2520.77 | 06-FEB-13:50 | 1.27 |
March | 0.675164E+10 | 1.26 | 2520.77 | 03-MAR-15:20 | 1.27 |
April | 0.653385E+10 | 1.26 | 2520.77 | 01-APR-11:40 | 1.27 |
May | 0.675817E+10 | 1.26 | 3004.04 | 19-MAY-19:20 | 1.35 |
June | 0.673669E+10 | 1.27 | 4235.10 | 14-JUN-19:10 | 1.57 |
July | 0.761730E+10 | 1.31 | 8395.72 | 18-JUL-20:12 | 2.07 |
August | 0.751433E+10 | 1.30 | 8220.78 | 01-AUG-20:50 | 2.05 |
September | 0.718093E+10 | 1.30 | 5924.26 | 09-SEP-20:10 | 1.79 |
October | 0.694384E+10 | 1.27 | 7552.85 | 03-OCT-19:53 | 1.98 |
November | 0.653385E+10 | 1.26 | 2520.77 | 01-NOV-01:10 | 1.26 |
December | 0.675164E+10 | 1.26 | 2520.77 | 01-DEC-20:10 | 1.26 |
Annual Sum or Average | 0.821721E+11 | 1.27 | |||
Minimum of Months | 0.609826E+10 | 1.26 | 2520.77 | 1.26 | |
Maximum of Months | 0.761730E+10 | 1.31 | 8395.72 | 2.07 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | -0.0 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | -0.0 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: ROOM_1_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149347E+10 | 0.51 | 756.07 | 01-JAN-00:05 | 0.60 |
February | 0.135782E+10 | 0.53 | 756.07 | 01-FEB-00:10 | 0.60 |
March | 0.151469E+10 | 0.55 | 756.07 | 01-MAR-00:10 | 0.60 |
April | 0.149963E+10 | 0.57 | 756.07 | 01-APR-00:10 | 0.60 |
May | 0.157645E+10 | 0.59 | 756.07 | 01-MAY-00:10 | 0.60 |
June | 0.155668E+10 | 0.60 | 756.07 | 01-JUN-00:10 | 0.60 |
July | 0.160386E+10 | 0.60 | 756.07 | 01-JUL-00:10 | 0.60 |
August | 0.159620E+10 | 0.59 | 756.07 | 01-AUG-00:10 | 0.60 |
September | 0.154817E+10 | 0.59 | 756.07 | 01-SEP-00:10 | 0.60 |
October | 0.155666E+10 | 0.57 | 756.07 | 01-OCT-00:10 | 0.60 |
November | 0.147003E+10 | 0.54 | 756.07 | 01-NOV-00:10 | 0.60 |
December | 0.148924E+10 | 0.51 | 756.07 | 01-DEC-00:10 | 0.60 |
Annual Sum or Average | 0.182629E+11 | 0.56 | |||
Minimum of Months | 0.135782E+10 | 0.51 | 756.07 | 0.60 | |
Maximum of Months | 0.160386E+10 | 0.60 | 756.07 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145933E+10 | 0.47 | 750.75 | 01-JAN-00:05 | 0.60 |
February | 0.132506E+10 | 0.48 | 750.75 | 01-FEB-00:10 | 0.60 |
March | 0.147641E+10 | 0.51 | 750.75 | 01-MAR-00:10 | 0.60 |
April | 0.147220E+10 | 0.55 | 750.75 | 01-APR-00:10 | 0.60 |
May | 0.156470E+10 | 0.58 | 750.75 | 01-MAY-00:10 | 0.60 |
June | 0.155158E+10 | 0.59 | 750.75 | 01-JUN-00:10 | 0.60 |
July | 0.159538E+10 | 0.59 | 750.75 | 01-JUL-00:10 | 0.60 |
August | 0.157720E+10 | 0.58 | 750.75 | 01-AUG-00:10 | 0.60 |
September | 0.151338E+10 | 0.57 | 750.75 | 01-SEP-00:10 | 0.60 |
October | 0.150636E+10 | 0.54 | 750.75 | 01-OCT-00:20 | 0.60 |
November | 0.142751E+10 | 0.49 | 750.75 | 01-NOV-00:10 | 0.60 |
December | 0.145671E+10 | 0.47 | 750.75 | 01-DEC-00:10 | 0.60 |
Annual Sum or Average | 0.179258E+11 | 0.53 | |||
Minimum of Months | 0.132506E+10 | 0.47 | 750.75 | 0.60 | |
Maximum of Months | 0.159538E+10 | 0.59 | 750.75 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169561E+10 | 0.41 | 4583.03 | 01-JAN-15:20 | 0.60 |
February | 0.168429E+10 | 0.46 | 4583.03 | 01-FEB-15:10 | 0.60 |
March | 0.176975E+10 | 0.48 | 4583.03 | 01-MAR-15:10 | 0.60 |
April | 0.216527E+10 | 0.60 | 4583.03 | 01-APR-14:10 | 0.60 |
May | 0.254697E+10 | 0.67 | 4583.03 | 01-MAY-14:10 | 0.60 |
June | 0.299953E+10 | 0.68 | 4583.03 | 01-JUN-14:20 | 0.60 |
July | 0.316884E+10 | 0.67 | 4583.03 | 01-JUL-14:10 | 0.60 |
August | 0.311104E+10 | 0.68 | 4583.03 | 01-AUG-14:10 | 0.60 |
September | 0.307951E+10 | 0.67 | 4583.03 | 01-SEP-14:10 | 0.60 |
October | 0.278175E+10 | 0.63 | 4583.03 | 01-OCT-14:10 | 0.60 |
November | 0.210397E+10 | 0.48 | 4583.03 | 01-NOV-14:10 | 0.60 |
December | 0.160602E+10 | 0.41 | 4583.03 | 01-DEC-15:20 | 0.60 |
Annual Sum or Average | 0.287126E+11 | 0.57 | |||
Minimum of Months | 0.160602E+10 | 0.41 | 4583.03 | 0.60 | |
Maximum of Months | 0.316884E+10 | 0.68 | 4583.03 | 0.60 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.929862E+10 | 0.43 | 4806.94 | 01-JAN-00:05 | 0.60 |
February | 0.840497E+10 | 0.45 | 4806.94 | 01-FEB-00:10 | 0.60 |
March | 0.932224E+10 | 0.47 | 4806.94 | 01-MAR-00:10 | 0.60 |
April | 0.918428E+10 | 0.54 | 4806.94 | 01-APR-00:10 | 0.60 |
May | 0.969814E+10 | 0.57 | 4806.94 | 01-MAY-00:10 | 0.60 |
June | 0.958828E+10 | 0.58 | 4806.94 | 01-JUN-00:10 | 0.60 |
July | 0.991354E+10 | 0.58 | 4806.94 | 01-JUL-00:10 | 0.60 |
August | 0.978599E+10 | 0.57 | 4806.94 | 01-AUG-00:10 | 0.60 |
September | 0.937257E+10 | 0.56 | 4806.94 | 01-SEP-00:10 | 0.60 |
October | 0.943883E+10 | 0.52 | 4806.94 | 01-OCT-00:10 | 0.60 |
November | 0.900366E+10 | 0.45 | 4806.94 | 01-NOV-00:10 | 0.60 |
December | 0.929857E+10 | 0.43 | 4806.94 | 01-DEC-00:10 | 0.60 |
Annual Sum or Average | 0.112310E+12 | 0.51 | |||
Minimum of Months | 0.840497E+10 | 0.43 | 4806.94 | 0.60 | |
Maximum of Months | 0.991354E+10 | 0.58 | 4806.94 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129479E+10 | 0.53 | 658.45 | 01-JAN-00:10 | 0.60 |
February | 0.118472E+10 | 0.56 | 658.45 | 01-FEB-00:10 | 0.60 |
March | 0.132411E+10 | 0.57 | 658.45 | 01-MAR-00:10 | 0.60 |
April | 0.132141E+10 | 0.60 | 658.45 | 01-APR-00:10 | 0.60 |
May | 0.139356E+10 | 0.61 | 658.45 | 01-MAY-00:10 | 0.60 |
June | 0.138571E+10 | 0.61 | 658.45 | 01-JUN-00:10 | 0.60 |
July | 0.142816E+10 | 0.61 | 658.45 | 01-JUL-00:10 | 0.60 |
August | 0.141703E+10 | 0.60 | 658.45 | 01-AUG-00:10 | 0.60 |
September | 0.136898E+10 | 0.60 | 658.45 | 01-SEP-00:10 | 0.60 |
October | 0.136218E+10 | 0.58 | 658.45 | 01-OCT-00:10 | 0.60 |
November | 0.127817E+10 | 0.55 | 658.45 | 01-NOV-00:10 | 0.60 |
December | 0.129041E+10 | 0.52 | 658.45 | 01-DEC-00:10 | 0.60 |
Annual Sum or Average | 0.160492E+11 | 0.58 | |||
Minimum of Months | 0.118472E+10 | 0.52 | 658.45 | 0.60 | |
Maximum of Months | 0.142816E+10 | 0.61 | 658.45 | 0.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126415E+10 | 0.44 | 653.41 | 01-JAN-00:05 | 0.60 |
February | 0.114947E+10 | 0.49 | 653.41 | 01-FEB-00:10 | 0.60 |
March | 0.128819E+10 | 0.55 | 653.41 | 01-MAR-00:10 | 0.60 |
April | 0.129403E+10 | 0.58 | 653.41 | 01-APR-00:10 | 0.60 |
May | 0.137516E+10 | 0.59 | 653.41 | 01-MAY-00:10 | 0.60 |
June | 0.137421E+10 | 0.59 | 653.41 | 01-JUN-00:10 | 0.60 |
July | 0.141354E+10 | 0.59 | 653.41 | 01-JUL-00:10 | 0.60 |
August | 0.139158E+10 | 0.58 | 653.41 | 01-AUG-00:10 | 0.60 |
September | 0.132710E+10 | 0.58 | 653.41 | 01-SEP-00:10 | 0.60 |
October | 0.131351E+10 | 0.56 | 653.41 | 01-OCT-00:10 | 0.60 |
November | 0.123096E+10 | 0.50 | 653.41 | 01-NOV-00:10 | 0.60 |
December | 0.126417E+10 | 0.44 | 653.41 | 01-DEC-00:10 | 0.60 |
Annual Sum or Average | 0.156861E+11 | 0.54 | |||
Minimum of Months | 0.114947E+10 | 0.44 | 653.41 | 0.60 | |
Maximum of Months | 0.141354E+10 | 0.59 | 653.41 | 0.60 |
Report: FanReportMonthly
For: ROOM_1_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.421034E+09 | 0.50 | 214.24 | 01-JAN-00:05 | 0.60 |
February | 0.383090E+09 | 0.52 | 214.24 | 01-FEB-00:10 | 0.60 |
March | 0.427660E+09 | 0.54 | 214.24 | 01-MAR-00:10 | 0.60 |
April | 0.426042E+09 | 0.57 | 214.24 | 01-APR-00:10 | 0.60 |
May | 0.449390E+09 | 0.59 | 214.24 | 01-MAY-00:10 | 0.60 |
June | 0.446584E+09 | 0.60 | 214.24 | 01-JUN-00:10 | 0.60 |
July | 0.459737E+09 | 0.60 | 214.24 | 01-JUL-00:10 | 0.60 |
August | 0.456682E+09 | 0.59 | 214.24 | 01-AUG-00:10 | 0.60 |
September | 0.441844E+09 | 0.59 | 214.24 | 01-SEP-00:10 | 0.60 |
October | 0.440909E+09 | 0.56 | 214.24 | 01-OCT-00:10 | 0.60 |
November | 0.414670E+09 | 0.53 | 214.24 | 01-NOV-00:10 | 0.60 |
December | 0.420338E+09 | 0.50 | 214.24 | 01-DEC-00:10 | 0.60 |
Annual Sum or Average | 0.518798E+10 | 0.56 | |||
Minimum of Months | 0.383090E+09 | 0.50 | 214.24 | 0.60 | |
Maximum of Months | 0.459737E+09 | 0.60 | 214.24 | 0.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.412473E+09 | 0.46 | 212.31 | 01-JAN-00:05 | 0.60 |
February | 0.374500E+09 | 0.48 | 212.31 | 01-FEB-00:10 | 0.60 |
March | 0.417003E+09 | 0.50 | 212.31 | 01-MAR-00:10 | 0.60 |
April | 0.418033E+09 | 0.55 | 212.31 | 01-APR-00:10 | 0.60 |
May | 0.445511E+09 | 0.58 | 212.31 | 01-MAY-00:10 | 0.60 |
June | 0.444403E+09 | 0.59 | 212.31 | 01-JUN-00:10 | 0.60 |
July | 0.456688E+09 | 0.59 | 212.31 | 01-JUL-00:10 | 0.60 |
August | 0.450907E+09 | 0.58 | 212.31 | 01-AUG-00:10 | 0.60 |
September | 0.431985E+09 | 0.57 | 212.31 | 01-SEP-00:10 | 0.60 |
October | 0.426909E+09 | 0.53 | 212.31 | 01-OCT-00:20 | 0.60 |
November | 0.402766E+09 | 0.49 | 212.31 | 01-NOV-00:10 | 0.60 |
December | 0.413040E+09 | 0.46 | 212.31 | 01-DEC-00:10 | 0.60 |
Annual Sum or Average | 0.509422E+10 | 0.53 | |||
Minimum of Months | 0.374500E+09 | 0.46 | 212.31 | 0.60 | |
Maximum of Months | 0.456688E+09 | 0.59 | 212.31 | 0.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199164E+10 | 0.54 | 976.45 | 01-JAN-00:05 | 0.60 |
February | 0.180780E+10 | 0.55 | 976.45 | 01-FEB-00:10 | 0.60 |
March | 0.198379E+10 | 0.56 | 976.45 | 01-MAR-00:10 | 0.60 |
April | 0.194688E+10 | 0.57 | 976.45 | 01-APR-00:10 | 0.60 |
May | 0.202433E+10 | 0.58 | 976.45 | 01-MAY-00:10 | 0.60 |
June | 0.200662E+10 | 0.60 | 976.45 | 01-JUN-00:10 | 0.60 |
July | 0.208068E+10 | 0.60 | 976.45 | 01-JUL-00:10 | 0.60 |
August | 0.208425E+10 | 0.59 | 976.45 | 01-AUG-00:10 | 0.60 |
September | 0.204951E+10 | 0.59 | 976.45 | 01-SEP-00:10 | 0.60 |
October | 0.207431E+10 | 0.57 | 976.45 | 01-OCT-00:10 | 0.60 |
November | 0.196571E+10 | 0.55 | 976.45 | 01-NOV-00:10 | 0.60 |
December | 0.198676E+10 | 0.54 | 976.45 | 01-DEC-00:10 | 0.60 |
Annual Sum or Average | 0.240023E+11 | 0.57 | |||
Minimum of Months | 0.180780E+10 | 0.54 | 976.45 | 0.60 | |
Maximum of Months | 0.208425E+10 | 0.60 | 976.45 | 0.60 |
Report: FanReportMonthly
For: PTAC_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.244636E+09 | 0.52 | 322.68 | 12-JAN-15:10 | 0.68 |
February | 0.302720E+09 | 0.60 | 329.49 | 20-FEB-13:00 | 0.68 |
March | 0.408931E+09 | 0.65 | 358.83 | 14-MAR-18:03 | 0.67 |
April | 0.626818E+09 | 0.68 | 496.03 | 19-APR-18:03 | 0.66 |
May | 0.853302E+09 | 0.68 | 608.04 | 19-MAY-18:15 | 0.65 |
June | 0.105531E+10 | 0.67 | 757.51 | 14-JUN-18:03 | 0.64 |
July | 0.118064E+10 | 0.66 | 725.80 | 26-JUL-18:15 | 0.64 |
August | 0.107550E+10 | 0.67 | 673.25 | 04-AUG-18:15 | 0.64 |
September | 0.956619E+09 | 0.67 | 597.49 | 01-SEP-18:03 | 0.65 |
October | 0.738230E+09 | 0.68 | 576.91 | 04-OCT-15:13 | 0.65 |
November | 0.390143E+09 | 0.61 | 410.46 | 03-NOV-15:10 | 0.67 |
December | 0.197920E+09 | 0.48 | 267.64 | 10-DEC-12:30 | 0.68 |
Annual Sum or Average | 0.803077E+10 | 0.63 | |||
Minimum of Months | 0.197920E+09 | 0.48 | 267.64 | 0.64 | |
Maximum of Months | 0.118064E+10 | 0.68 | 757.51 | 0.68 |
Report: FanReportMonthly
For: PTAC_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 50947198.72 | 0.18 | 245.36 | 12-JAN-13:50 | 0.67 |
February | 0.100978E+09 | 0.31 | 294.56 | 22-FEB-13:40 | 0.67 |
March | 0.177058E+09 | 0.41 | 303.29 | 14-MAR-15:10 | 0.67 |
April | 0.391736E+09 | 0.61 | 434.23 | 30-APR-14:10 | 0.65 |
May | 0.580667E+09 | 0.67 | 487.78 | 30-MAY-14:10 | 0.64 |
June | 0.772406E+09 | 0.67 | 560.41 | 02-JUN-13:40 | 0.63 |
July | 0.823148E+09 | 0.66 | 568.44 | 03-JUL-12:50 | 0.63 |
August | 0.746170E+09 | 0.67 | 542.17 | 04-AUG-15:20 | 0.63 |
September | 0.623463E+09 | 0.66 | 536.60 | 15-SEP-12:50 | 0.63 |
October | 0.403603E+09 | 0.62 | 505.89 | 03-OCT-13:40 | 0.64 |
November | 0.150059E+09 | 0.35 | 318.14 | 03-NOV-13:30 | 0.66 |
December | 46932084.81 | 0.14 | 275.72 | 27-DEC-07:30 | 0.59 |
Annual Sum or Average | 0.486717E+10 | 0.50 | |||
Minimum of Months | 46932084.81 | 0.14 | 245.36 | 0.59 | |
Maximum of Months | 0.823148E+09 | 0.67 | 568.44 | 0.67 |
Report: FanReportMonthly
For: PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193393E+11 | 1.54 | 7220.45 | 01-JAN-01:40 | 1.54 |
February | 0.174677E+11 | 1.54 | 7220.45 | 15-FEB-09:40 | 1.54 |
March | 0.193393E+11 | 1.54 | 7220.45 | 14-MAR-09:30 | 1.54 |
April | 0.187154E+11 | 1.53 | 7220.45 | 11-APR-19:41 | 1.54 |
May | 0.193393E+11 | 1.53 | 7220.45 | 01-MAY-10:15 | 1.54 |
June | 0.187154E+11 | 1.53 | 7220.45 | 01-JUN-21:40 | 1.53 |
July | 0.193393E+11 | 1.52 | 7220.45 | 01-JUL-17:20 | 1.52 |
August | 0.193393E+11 | 1.52 | 7220.45 | 01-AUG-16:30 | 1.52 |
September | 0.187154E+11 | 1.52 | 7220.45 | 01-SEP-02:20 | 1.51 |
October | 0.193393E+11 | 1.52 | 7220.45 | 16-OCT-17:07 | 1.52 |
November | 0.187154E+11 | 1.53 | 7220.45 | 01-NOV-10:05 | 1.52 |
December | 0.193393E+11 | 1.54 | 7220.45 | 23-DEC-15:10 | 1.54 |
Annual Sum or Average | 0.227704E+12 | 1.53 | |||
Minimum of Months | 0.174677E+11 | 1.52 | 7220.45 | 1.51 | |
Maximum of Months | 0.193393E+11 | 1.54 | 7220.45 | 1.54 |
Report: FanReportMonthly
For: PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.936711E+10 | 1.57 | 3497.28 | 01-JAN-08:65 | 1.57 |
February | 0.846062E+10 | 1.57 | 3497.28 | 28-FEB-07:05 | 1.56 |
March | 0.936711E+10 | 1.57 | 3497.28 | 01-MAR-08:15 | 1.57 |
April | 0.906495E+10 | 1.57 | 3497.28 | 03-APR-04:20 | 1.57 |
May | 0.936711E+10 | 1.57 | 3497.28 | 01-MAY-01:10 | 1.58 |
June | 0.906495E+10 | 1.56 | 3497.28 | 01-JUN-07:03 | 1.57 |
July | 0.936711E+10 | 1.55 | 3497.28 | 05-JUL-18:07 | 1.56 |
August | 0.936711E+10 | 1.56 | 3497.28 | 06-AUG-11:30 | 1.56 |
September | 0.906495E+10 | 1.56 | 3497.28 | 01-SEP-05:10 | 1.55 |
October | 0.936711E+10 | 1.56 | 3497.28 | 05-OCT-06:00 | 1.55 |
November | 0.906495E+10 | 1.57 | 3497.28 | 06-NOV-16:13 | 1.58 |
December | 0.936711E+10 | 1.57 | 3497.28 | 19-DEC-23:20 | 1.58 |
Annual Sum or Average | 0.110290E+12 | 1.56 | |||
Minimum of Months | 0.846062E+10 | 1.55 | 3497.28 | 1.55 | |
Maximum of Months | 0.936711E+10 | 1.57 | 3497.28 | 1.58 |
Report: FanReportMonthly
For: PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132408E+11 | 1.53 | 4943.55 | 02-JAN-14:00 | 1.53 |
February | 0.119594E+11 | 1.53 | 4943.55 | 03-FEB-15:10 | 1.54 |
March | 0.132408E+11 | 1.54 | 4943.55 | 04-MAR-11:20 | 1.53 |
April | 0.128137E+11 | 1.53 | 4943.55 | 01-APR-17:00 | 1.52 |
May | 0.132408E+11 | 1.53 | 4943.55 | 01-MAY-07:47 | 1.54 |
June | 0.128137E+11 | 1.52 | 4943.55 | 01-JUN-08:16 | 1.52 |
July | 0.132408E+11 | 1.52 | 4943.55 | 02-JUL-06:51 | 1.52 |
August | 0.132408E+11 | 1.52 | 4943.55 | 01-AUG-22:20 | 1.51 |
September | 0.128137E+11 | 1.52 | 4943.55 | 01-SEP-04:30 | 1.52 |
October | 0.132408E+11 | 1.52 | 4943.55 | 01-OCT-07:37 | 1.53 |
November | 0.128137E+11 | 1.53 | 4943.55 | 03-NOV-15:26 | 1.53 |
December | 0.132408E+11 | 1.53 | 4943.55 | 07-DEC-16:13 | 1.54 |
Annual Sum or Average | 0.155900E+12 | 1.53 | |||
Minimum of Months | 0.119594E+11 | 1.52 | 4943.55 | 1.51 | |
Maximum of Months | 0.132408E+11 | 1.54 | 4943.55 | 1.54 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.309861E+09 | 0.278875E+09 | 602.90 | 27-JAN-09:02 | 542.61 | 542.61 | 43.29 | 0.76 |
February | 0.211850E+09 | 0.190665E+09 | 620.00 | 03-FEB-07:00 | 558.00 | 558.00 | 43.63 | 0.79 |
March | 0.135473E+09 | 0.121926E+09 | 580.49 | 02-MAR-05:00 | 522.44 | 522.44 | 40.25 | 0.73 |
April | 18218890.92 | 16397001.83 | 251.50 | 11-APR-08:03 | 226.35 | 226.35 | 30.02 | 0.28 |
May | 234533.72 | 211080.35 | 171.31 | 02-MAY-08:05 | 154.18 | 154.18 | 26.91 | 0.18 |
June | 3551.46 | 3196.31 | 4.29 | 02-JUN-08:14 | 3.86 | 3.86 | 26.99 | 0.00 |
July | 29473.21 | 26525.89 | 8.01 | 07-JUL-08:05 | 7.21 | 7.21 | 27.43 | 0.01 |
August | 19345.26 | 17410.73 | 12.19 | 24-AUG-08:54 | 10.97 | 10.97 | 29.05 | 0.01 |
September | 448184.65 | 403366.19 | 201.89 | 25-SEP-08:54 | 181.70 | 181.70 | 27.40 | 0.22 |
October | 5048253.28 | 4543427.96 | 213.36 | 20-OCT-08:54 | 192.02 | 192.02 | 26.23 | 0.23 |
November | 0.173168E+09 | 0.155852E+09 | 481.76 | 27-NOV-09:02 | 433.58 | 433.58 | 34.73 | 0.58 |
December | 0.442040E+09 | 0.397836E+09 | 823.33 | 26-DEC-16:12 | 741.00 | 741.00 | 38.80 | 1.18 |
Annual Sum or Average | 0.129639E+10 | 0.116676E+10 | ||||||
Minimum of Months | 3551.46 | 3196.31 | 4.29 | 3.86 | 3.86 | 26.23 | 0.00 | |
Maximum of Months | 0.442040E+09 | 0.397836E+09 | 823.33 | 741.00 | 741.00 | 43.63 | 1.18 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 49.70 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 50.82 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 50.99 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.57 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 54.05 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 54.55 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.91 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 55.04 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.90 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.87 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 54.03 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 51.45 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.70 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 55.04 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 26.57 | 68.89 | 21537.34 | 118369.04 | 28-JAN-06:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.42 | 69.17 | 16388.32 | 123877.52 | 03-FEB-07:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 26.30 | 68.27 | 9294.39 | 119069.24 | 02-MAR-05:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.86 | 65.60 | 1260.04 | 44784.63 | 11-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 27.73 | 27.73 | 14.58 | 29720.38 | 02-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.99 | 26.99 | 0.22 | 706.65 | 02-JUN-08:14 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.13 | 27.13 | 1.77 | 1304.95 | 07-JUL-08:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.54 | 28.54 | 1.13 | 1902.82 | 24-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 29.21 | 29.21 | 28.90 | 34929.44 | 25-SEP-08:54 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.16 | 26.16 | 334.63 | 38196.01 | 20-OCT-08:54 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26.43 | 26.43 | 12277.24 | 96168.88 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 27.76 | 66.65 | 30868.25 | 171612.16 | 26-DEC-16:12 |
Annual Sum or Average | 0.00 | 7642.41 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.16 | 26.16 | 0.22 | 706.65 | ||
Maximum of Months | 0.00 | 0.00 | 29.21 | 69.17 | 30868.25 | 171612.16 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 49.70 | 60.05 | 24354.76 | 51173.74 | 30-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 50.82 | 60.05 | 24335.99 | 51168.54 | 01-FEB-08:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 50.99 | 60.05 | 23481.45 | 50214.18 | 01-MAR-07:53 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.57 | 60.05 | 21933.68 | 47296.74 | 03-APR-06:55 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 54.05 | 60.05 | 20157.81 | 43944.16 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 54.55 | 60.05 | 18620.16 | 40266.14 | 01-JUN-06:51 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.91 | 60.05 | 17713.04 | 37551.08 | 03-JUL-06:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 55.04 | 60.05 | 17738.79 | 37702.22 | 31-AUG-06:55 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.90 | 60.05 | 18631.73 | 40211.27 | 29-SEP-06:29 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.87 | 60.05 | 20173.61 | 44003.88 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 54.03 | 60.05 | 21951.94 | 47565.91 | 30-NOV-07:53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 51.45 | 60.05 | 23478.45 | 50118.25 | 29-DEC-07:55 |
Annual Sum or Average | 0.00 | 21028.95 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.70 | 60.05 | 17713.04 | 37551.08 | ||
Maximum of Months | 0.00 | 0.00 | 55.04 | 60.05 | 24354.76 | 51173.74 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.176646E+11 | 0.00 | 0.00 | 0.113793E+11 | 0.00 | 0.00 |
February | 0.123696E+11 | 0.00 | 0.00 | 0.125097E+11 | 0.00 | 0.00 |
March | 0.797830E+10 | 0.00 | 0.00 | 0.164295E+11 | 0.00 | 0.00 |
April | 0.931435E+09 | 0.00 | 0.00 | 0.292649E+11 | 0.00 | 0.00 |
May | 19036.40 | 0.00 | 0.00 | 0.434234E+11 | 0.00 | 0.00 |
June | 87103.69 | 0.00 | 0.00 | 0.561200E+11 | 0.00 | 0.00 |
July | 878652.47 | 0.00 | 0.00 | 0.633045E+11 | 0.00 | 0.00 |
August | 410745.76 | 0.00 | 0.00 | 0.562024E+11 | 0.00 | 0.00 |
September | 5033098.13 | 0.00 | 0.00 | 0.465827E+11 | 0.00 | 0.00 |
October | 0.140659E+09 | 0.00 | 0.00 | 0.299845E+11 | 0.00 | 0.00 |
November | 0.981723E+10 | 0.00 | 0.00 | 0.144333E+11 | 0.00 | 0.00 |
December | 0.260512E+11 | 0.00 | 0.00 | 0.110194E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.749595E+11 | 0.00 | 0.00 | 0.390654E+12 | 0.00 | 0.00 |
Minimum of Months | 19036.40 | 0.00 | 0.00 | 0.110194E+11 | 0.00 | 0.00 |
Maximum of Months | 0.260512E+11 | 0.00 | 0.00 | 0.633045E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.258331E+11 | 0.00 | 0.00 | 0.117300E+11 | 0.00 | 0.00 |
February | 0.177818E+11 | 0.00 | 0.00 | 0.128020E+11 | 0.00 | 0.00 |
March | 0.120333E+11 | 0.00 | 0.00 | 0.170721E+11 | 0.00 | 0.00 |
April | 0.188894E+10 | 0.00 | 0.00 | 0.301704E+11 | 0.00 | 0.00 |
May | 21458494.95 | 0.00 | 0.00 | 0.445197E+11 | 0.00 | 0.00 |
June | 176763.55 | 0.00 | 0.00 | 0.570812E+11 | 0.00 | 0.00 |
July | 1474015.57 | 0.00 | 0.00 | 0.645549E+11 | 0.00 | 0.00 |
August | 807334.66 | 0.00 | 0.00 | 0.558126E+11 | 0.00 | 0.00 |
September | 62325577.04 | 0.00 | 0.00 | 0.448713E+11 | 0.00 | 0.00 |
October | 0.622224E+09 | 0.00 | 0.00 | 0.283878E+11 | 0.00 | 0.00 |
November | 0.150648E+11 | 0.00 | 0.00 | 0.142729E+11 | 0.00 | 0.00 |
December | 0.353354E+11 | 0.00 | 0.00 | 0.113554E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.108646E+12 | 0.00 | 0.00 | 0.392630E+12 | 0.00 | 0.00 |
Minimum of Months | 176763.55 | 0.00 | 0.00 | 0.113554E+11 | 0.00 | 0.00 |
Maximum of Months | 0.353354E+11 | 0.00 | 0.00 | 0.645549E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.689419E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.650786E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.746358E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.116265E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.171789E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.225069E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.293857E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.277650E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.248158E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.166508E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.872533E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.702996E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.186551E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.650786E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.293857E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.193753E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.181035E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.211055E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.265791E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.330340E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.366977E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.397788E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.373988E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.324192E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.262576E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.193624E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.193400E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.329452E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.181035E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.397788E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.939812E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.885008E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.101398E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.129934E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.168726E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.206290E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.234368E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.209503E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.175982E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.133299E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.957448E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.936739E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.173140E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.885008E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.234368E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.134798E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134472E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.163114E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.224735E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.299156E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.349123E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.397048E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.360759E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.305644E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.224799E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145725E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.133513E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.287289E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133513E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.397048E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108460E+11 | 0.167103E+10 | 0.176646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.997459E+10 | 0.825143E+10 | 0.123696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113764E+11 | 0.166713E+11 | 0.797830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124341E+11 | 0.595787E+11 | 0.931435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143135E+11 | 0.105134E+12 | 19036.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158106E+11 | 0.144144E+12 | 87103.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160229E+11 | 0.179510E+12 | 878652.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157482E+11 | 0.149832E+12 | 410745.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145814E+11 | 0.118857E+12 | 5033098.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.588717E+11 | 0.140659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111360E+11 | 0.107501E+11 | 0.981723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106953E+11 | 0.996999E+09 | 0.260512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156329E+12 | 0.854268E+12 | 0.749595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.997459E+10 | 0.996999E+09 | 19036.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160229E+11 | 0.179510E+12 | 0.260512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.112325E+11 | 0.156399E+10 | 0.258331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104687E+11 | 0.763544E+10 | 0.177818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122494E+11 | 0.161106E+11 | 0.120333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138045E+11 | 0.590397E+11 | 0.188894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160250E+11 | 0.104467E+12 | 21458494.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174712E+11 | 0.142959E+12 | 176763.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176483E+11 | 0.179197E+12 | 1474015.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169372E+11 | 0.145332E+12 | 807334.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150331E+11 | 0.111835E+12 | 62325577.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135093E+11 | 0.530595E+11 | 0.622224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113225E+11 | 0.963134E+10 | 0.150648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110422E+11 | 0.966478E+09 | 0.353354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166744E+12 | 0.831798E+12 | 0.108646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104687E+11 | 0.966478E+09 | 176763.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176483E+11 | 0.179197E+12 | 0.353354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.675164E+10 | 0.458228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.609826E+10 | 0.132848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.675164E+10 | 0.231786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.653385E+10 | 0.168974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.675817E+10 | 0.347015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.673669E+10 | 0.515713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761730E+10 | 0.789102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.751433E+10 | 0.730309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.718093E+10 | 0.656459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.694384E+10 | 0.355059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653385E+10 | 0.747556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.675164E+10 | 0.890335E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.821721E+11 | 0.368733E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.609826E+10 | 0.458228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.761730E+10 | 0.789102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193393E+11 | 0.131327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174677E+11 | 0.238915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193393E+11 | 0.686628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187154E+11 | 0.308719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193393E+11 | 0.524480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187154E+11 | 0.655122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193393E+11 | 0.778585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.193393E+11 | 0.687321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.187154E+11 | 0.536733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193393E+11 | 0.274272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187154E+11 | 0.249760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193393E+11 | 2511892.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227704E+12 | 0.388410E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174677E+11 | 2511892.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193393E+11 | 0.778585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.936711E+10 | 0.109924E+09 | 0.192905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.846062E+10 | 0.143714E+10 | 0.141078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.936711E+10 | 0.283455E+10 | 0.816536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.906495E+10 | 0.143480E+11 | 35909647.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.936711E+10 | 0.271340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.906495E+10 | 0.409995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.936711E+10 | 0.536560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.936711E+10 | 0.434693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.906495E+10 | 0.324818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.936711E+10 | 0.151974E+11 | 120939.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.906495E+10 | 0.189386E+10 | 0.889295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936711E+10 | 929370.12 | 0.381758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110290E+12 | 0.233563E+12 | 0.889926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.846062E+10 | 929370.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.936711E+10 | 0.536560E+11 | 0.381758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132408E+11 | 0.881057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119594E+11 | 0.578059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132408E+11 | 0.121363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128137E+11 | 0.382709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132408E+11 | 0.644385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128137E+11 | 0.811642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132408E+11 | 0.100835E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132408E+11 | 0.874195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128137E+11 | 0.698339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132408E+11 | 0.371468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128137E+11 | 0.679439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132408E+11 | 0.390999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155900E+12 | 0.505092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119594E+11 | 0.390999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132408E+11 | 0.100835E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108460E+11 | 0.176646E+11 | 0.00 | 0.00 | 0.533254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.997459E+10 | 0.123696E+11 | 0.00 | 0.00 | 0.253510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113764E+11 | 0.797830E+10 | 0.00 | 0.00 | 0.505305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124341E+11 | 0.931435E+09 | 0.00 | 0.00 | 0.168308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143135E+11 | 19036.40 | 0.00 | 0.00 | 0.291099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158106E+11 | 87103.69 | 0.00 | 0.00 | 0.403094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160229E+11 | 878652.47 | 0.00 | 0.00 | 0.472816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157482E+11 | 410745.76 | 0.00 | 0.00 | 0.404542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145814E+11 | 5033098.13 | 0.00 | 0.00 | 0.320013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.140659E+09 | 0.00 | 0.00 | 0.165943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111360E+11 | 0.981723E+10 | 0.00 | 0.00 | 0.329731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106953E+11 | 0.260512E+11 | 0.00 | 0.00 | 0.324070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156329E+12 | 0.749595E+11 | 0.00 | 0.00 | 0.234324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.997459E+10 | 19036.40 | 0.00 | 0.00 | 0.324070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160229E+11 | 0.260512E+11 | 0.00 | 0.00 | 0.472816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.112325E+11 | 0.258331E+11 | 0.00 | 0.00 | 0.497510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104687E+11 | 0.177818E+11 | 0.00 | 0.00 | 0.233324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122494E+11 | 0.120333E+11 | 0.00 | 0.00 | 0.482270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138045E+11 | 0.188894E+10 | 0.00 | 0.00 | 0.163660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160250E+11 | 21458494.95 | 0.00 | 0.00 | 0.284947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174712E+11 | 176763.55 | 0.00 | 0.00 | 0.396100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176483E+11 | 1474015.57 | 0.00 | 0.00 | 0.469067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169372E+11 | 807334.66 | 0.00 | 0.00 | 0.388754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150331E+11 | 62325577.04 | 0.00 | 0.00 | 0.298382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135093E+11 | 0.622224E+09 | 0.00 | 0.00 | 0.148785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113225E+11 | 0.150648E+11 | 0.00 | 0.00 | 0.295036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110422E+11 | 0.353354E+11 | 0.00 | 0.00 | 0.313204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166744E+12 | 0.108646E+12 | 0.00 | 0.00 | 0.225886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104687E+11 | 176763.55 | 0.00 | 0.00 | 0.313204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176483E+11 | 0.353354E+11 | 0.00 | 0.00 | 0.469067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.675164E+10 | 0.00 | 0.00 | 0.00 | 0.142552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.609826E+10 | 0.00 | 0.00 | 0.00 | 0.409599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.675164E+10 | 0.00 | 0.00 | 0.00 | 0.711940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.653385E+10 | 0.00 | 0.00 | 0.00 | 0.509266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.675817E+10 | 0.00 | 0.00 | 0.00 | 0.104207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.673669E+10 | 0.00 | 0.00 | 0.00 | 0.157702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761730E+10 | 0.00 | 0.00 | 0.00 | 0.217684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.751433E+10 | 0.00 | 0.00 | 0.00 | 0.202507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.718093E+10 | 0.00 | 0.00 | 0.00 | 0.176349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.694384E+10 | 0.00 | 0.00 | 0.00 | 0.970698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653385E+10 | 0.00 | 0.00 | 0.00 | 0.219149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.675164E+10 | 0.00 | 0.00 | 0.00 | 0.278323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.821721E+11 | 0.00 | 0.00 | 0.00 | 0.104378E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.609826E+10 | 0.00 | 0.00 | 0.00 | 0.142552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.761730E+10 | 0.00 | 0.00 | 0.00 | 0.217684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.193393E+11 | 0.00 | 0.00 | 0.00 | 36010301.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174677E+11 | 0.00 | 0.00 | 0.00 | 0.635762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193393E+11 | 0.00 | 0.00 | 0.00 | 0.176627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187154E+11 | 0.00 | 0.00 | 0.00 | 0.786367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193393E+11 | 0.00 | 0.00 | 0.00 | 0.136948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187154E+11 | 0.00 | 0.00 | 0.00 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193393E+11 | 0.00 | 0.00 | 0.00 | 0.204395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.193393E+11 | 0.00 | 0.00 | 0.00 | 0.180595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.187154E+11 | 0.00 | 0.00 | 0.00 | 0.137038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193393E+11 | 0.00 | 0.00 | 0.00 | 0.691832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187154E+11 | 0.00 | 0.00 | 0.00 | 0.646961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193393E+11 | 0.00 | 0.00 | 0.00 | 722215.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227704E+12 | 0.00 | 0.00 | 0.00 | 0.101748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174677E+11 | 0.00 | 0.00 | 0.00 | 722215.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193393E+11 | 0.00 | 0.00 | 0.00 | 0.204395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.936711E+10 | 0.00 | 0.00 | 0.00 | 31010927.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.846062E+10 | 0.00 | 0.00 | 0.00 | 0.389465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.936711E+10 | 0.00 | 0.00 | 0.00 | 0.772724E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.906495E+10 | 0.00 | 0.00 | 0.00 | 0.392848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.936711E+10 | 0.00 | 0.00 | 0.00 | 0.750545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.906495E+10 | 0.00 | 0.00 | 0.00 | 0.115640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.936711E+10 | 0.00 | 0.00 | 0.00 | 0.140697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.936711E+10 | 0.00 | 0.00 | 0.00 | 0.115832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.906495E+10 | 0.00 | 0.00 | 0.00 | 0.853322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.936711E+10 | 0.00 | 0.00 | 0.00 | 0.396274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.906495E+10 | 0.00 | 0.00 | 0.00 | 0.509527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936711E+10 | 0.00 | 0.00 | 0.00 | 275595.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110290E+12 | 0.00 | 0.00 | 0.00 | 0.628498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.846062E+10 | 0.00 | 0.00 | 0.00 | 275595.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.936711E+10 | 0.00 | 0.00 | 0.00 | 0.140697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132408E+11 | 0.00 | 0.00 | 0.00 | 0.239005E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119594E+11 | 0.00 | 0.00 | 0.00 | 0.148782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132408E+11 | 0.00 | 0.00 | 0.00 | 0.307063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128137E+11 | 0.00 | 0.00 | 0.00 | 0.965983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132408E+11 | 0.00 | 0.00 | 0.00 | 0.166748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128137E+11 | 0.00 | 0.00 | 0.00 | 0.220986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132408E+11 | 0.00 | 0.00 | 0.00 | 0.264640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132408E+11 | 0.00 | 0.00 | 0.00 | 0.228351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128137E+11 | 0.00 | 0.00 | 0.00 | 0.177507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132408E+11 | 0.00 | 0.00 | 0.00 | 0.923909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128137E+11 | 0.00 | 0.00 | 0.00 | 0.175878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132408E+11 | 0.00 | 0.00 | 0.00 | 0.110552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155900E+12 | 0.00 | 0.00 | 0.00 | 0.131389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119594E+11 | 0.00 | 0.00 | 0.00 | 0.110552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132408E+11 | 0.00 | 0.00 | 0.00 | 0.264640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.466148E+10 | 0.00 | 0.00 | 62470362.78 | 0.00 | 0.00 | 0.491653E+11 | 0.00 | 0.82 |
February | 0.119231E+11 | 0.00 | 0.00 | 37510304.78 | 0.00 | 0.00 | 0.296211E+11 | 0.00 | 0.85 |
March | 0.130357E+11 | 0.00 | 0.00 | 38047402.96 | 0.00 | 0.00 | 0.273943E+11 | 0.00 | 0.89 |
April | 0.441340E+09 | 0.869417E+09 | 0.00 | 59476462.16 | 0.00 | 0.00 | 0.259243E+11 | 0.00 | 1.02 |
May | 0.00 | 0.387450E+10 | 0.00 | 53819354.29 | 0.00 | 0.00 | 0.157786E+11 | 0.00 | 1.00 |
June | 0.00 | 0.846983E+10 | 0.00 | 29334301.07 | 0.00 | 0.00 | 0.507889E+10 | 0.00 | 0.86 |
July | 0.00 | 0.215396E+11 | 0.00 | 2030918.71 | 0.00 | 0.00 | 0.195793E+09 | 0.00 | 0.87 |
August | 0.00 | 0.127553E+11 | 0.00 | 23033021.46 | 0.00 | 0.00 | 0.255420E+10 | 0.00 | 0.95 |
September | 0.00 | 0.100777E+11 | 0.00 | 50681594.95 | 0.00 | 0.00 | 0.954567E+10 | 0.00 | 1.10 |
October | 0.00 | 0.235735E+10 | 0.00 | 0.101466E+09 | 0.00 | 0.00 | 0.327369E+11 | 0.00 | 1.28 |
November | 0.00 | 0.00 | 0.00 | 0.105711E+09 | 0.00 | 0.00 | 0.540602E+11 | 0.00 | 1.12 |
December | 0.457808E+10 | 0.00 | 0.00 | 74619255.71 | 0.00 | 0.00 | 0.543304E+11 | 0.00 | 0.85 |
Annual Sum or Average | 0.346397E+11 | 0.599437E+11 | 0.00 | 0.638200E+09 | 0.00 | 0.00 | 0.306386E+12 | 0.00 | 0.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2030918.71 | 0.00 | 0.00 | 0.195793E+09 | 0.00 | 0.82 |
Maximum of Months | 0.130357E+11 | 0.215396E+11 | 0.00 | 0.105711E+09 | 0.00 | 0.00 | 0.543304E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.418428E+10 | 0.00 | 0.00 | 2472972.03 | 0.00 | 0.599338E+09 | 0.154401E+10 | 0.00 | 1.72 |
February | 0.345522E+10 | 0.00 | 0.00 | 2852937.07 | 0.00 | 0.495209E+09 | 0.133627E+10 | 0.00 | 1.93 |
March | 0.352801E+10 | 0.00 | 0.00 | 3526610.15 | 0.00 | 0.279017E+09 | 0.136583E+10 | 0.00 | 1.97 |
April | 0.224008E+10 | 0.121799E+09 | 0.00 | 4221965.08 | 5785.34 | 0.00 | 0.914384E+09 | 0.00 | 2.09 |
May | 0.123366E+10 | 0.473547E+09 | 0.00 | 3311902.74 | 2581071.06 | 0.00 | 0.660343E+09 | 0.00 | 2.00 |
June | 0.344627E+09 | 0.112326E+10 | 0.00 | 2755510.07 | 1108926.60 | 0.00 | 0.507420E+09 | 0.00 | 1.92 |
July | 39988551.32 | 0.169985E+10 | 0.00 | 1160453.79 | 92481978.51 | 0.00 | 0.170633E+09 | 0.00 | 1.86 |
August | 0.321035E+09 | 0.980750E+09 | 0.00 | 2381104.02 | 16335810.04 | 0.00 | 0.387537E+09 | 0.00 | 2.04 |
September | 0.889606E+09 | 0.666064E+09 | 0.00 | 4007498.17 | 11606375.01 | 0.00 | 0.577190E+09 | 0.00 | 2.35 |
October | 0.226321E+10 | 0.159463E+09 | 0.00 | 6680741.49 | 1305985.84 | 0.00 | 0.147291E+10 | 0.00 | 2.55 |
November | 0.351738E+10 | 0.00 | 0.00 | 4761728.92 | 0.00 | 0.261637E+09 | 0.206347E+10 | 0.00 | 2.19 |
December | 0.395257E+10 | 0.00 | 0.00 | 2152723.66 | 0.00 | 0.133074E+10 | 0.131138E+10 | 0.00 | 1.66 |
Annual Sum or Average | 0.259697E+11 | 0.522473E+10 | 0.00 | 40286147.17 | 0.125426E+09 | 0.296594E+10 | 0.123114E+11 | 0.00 | 2.02 |
Minimum of Months | 39988551.32 | 0.00 | 0.00 | 1160453.79 | 0.00 | 0.00 | 0.170633E+09 | 0.00 | 1.66 |
Maximum of Months | 0.418428E+10 | 0.169985E+10 | 0.00 | 6680741.49 | 92481978.51 | 0.133074E+10 | 0.206347E+10 | 0.00 | 2.55 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.398370E+10 | 0.00 | 0.00 | 971521.16 | 0.00 | 0.00 | 0.139469E+10 | 0.00 | 1.20 |
February | 0.297126E+10 | 0.00 | 0.00 | 1601113.47 | 0.00 | 0.00 | 0.159500E+10 | 0.00 | 1.33 |
March | 0.266340E+10 | 0.00 | 0.00 | 2763752.58 | 0.00 | 0.00 | 0.204722E+10 | 0.00 | 1.46 |
April | 0.855513E+09 | 63589055.43 | 0.00 | 4753850.96 | 1198825.31 | 0.00 | 0.216288E+10 | 0.00 | 1.58 |
May | 0.147361E+09 | 0.278400E+09 | 0.00 | 5095502.84 | 7051467.15 | 0.00 | 0.168484E+10 | 0.00 | 1.49 |
June | 1385167.75 | 0.665963E+09 | 0.00 | 4823106.55 | 5007531.51 | 0.00 | 0.826683E+09 | 0.00 | 1.33 |
July | 84805.14 | 0.121364E+10 | 0.00 | 2199844.08 | 17385978.44 | 0.00 | 0.206959E+09 | 0.00 | 1.28 |
August | 5885242.73 | 0.580601E+09 | 0.00 | 4187561.52 | 12422403.05 | 0.00 | 0.683640E+09 | 0.00 | 1.41 |
September | 66747053.87 | 0.321716E+09 | 0.00 | 5073213.85 | 20381310.86 | 0.00 | 0.134075E+10 | 0.00 | 1.58 |
October | 0.708066E+09 | 66434807.14 | 0.00 | 5361513.66 | 5693741.93 | 0.00 | 0.265049E+10 | 0.00 | 1.68 |
November | 0.256765E+10 | 0.00 | 0.00 | 2592481.48 | 0.00 | 0.00 | 0.228483E+10 | 0.00 | 1.39 |
December | 0.450436E+10 | 0.00 | 0.00 | 647882.54 | 0.00 | 0.00 | 0.113900E+10 | 0.00 | 1.18 |
Annual Sum or Average | 0.184754E+11 | 0.319035E+10 | 0.00 | 40071344.69 | 69141258.25 | 0.00 | 0.180170E+11 | 0.00 | 1.41 |
Minimum of Months | 84805.14 | 0.00 | 0.00 | 647882.54 | 0.00 | 0.00 | 0.206959E+09 | 0.00 | 1.18 |
Maximum of Months | 0.450436E+10 | 0.121364E+10 | 0.00 | 5361513.66 | 20381310.86 | 0.00 | 0.265049E+10 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.501395E+10 | 0.00 | 0.00 | 47919.37 | 0.00 | 0.00 | 0.115181E+09 | 0.00 | 0.54 |
February | 0.405779E+10 | 0.00 | 0.00 | 292142.39 | 0.00 | 0.00 | 0.273311E+09 | 0.00 | 0.59 |
March | 0.363346E+10 | 0.00 | 0.00 | 893998.86 | 0.00 | 0.00 | 0.751953E+09 | 0.00 | 0.64 |
April | 0.169670E+10 | 56604634.11 | 0.00 | 3560551.93 | 5574461.77 | 0.00 | 0.118348E+10 | 0.00 | 0.71 |
May | 0.405567E+09 | 0.304526E+09 | 0.00 | 5834534.27 | 911687.11 | 0.00 | 0.140774E+10 | 0.00 | 0.72 |
June | 1030571.55 | 0.775408E+09 | 0.00 | 5494372.87 | 0.00 | 0.00 | 0.834939E+09 | 0.00 | 0.69 |
July | 1708387.53 | 0.140116E+10 | 0.00 | 2239889.37 | 83001.99 | 0.00 | 0.203992E+09 | 0.00 | 0.67 |
August | 23480795.53 | 0.659833E+09 | 0.00 | 4536358.88 | 306427.37 | 0.00 | 0.663811E+09 | 0.00 | 0.70 |
September | 0.282550E+09 | 0.352122E+09 | 0.00 | 4895939.47 | 1806650.69 | 0.00 | 0.109202E+10 | 0.00 | 0.75 |
October | 0.180462E+10 | 65239364.30 | 0.00 | 3463070.84 | 6873449.26 | 0.00 | 0.137751E+10 | 0.00 | 0.75 |
November | 0.390023E+10 | 0.00 | 0.00 | 667592.79 | 0.00 | 0.00 | 0.647598E+09 | 0.00 | 0.61 |
December | 0.540568E+10 | 0.00 | 0.00 | 3533.42 | 0.00 | 0.00 | 12680720.17 | 0.00 | 0.53 |
Annual Sum or Average | 0.262268E+11 | 0.361489E+10 | 0.00 | 31929904.45 | 15555678.19 | 0.00 | 0.856422E+10 | 0.00 | 0.66 |
Minimum of Months | 1030571.55 | 0.00 | 0.00 | 3533.42 | 0.00 | 0.00 | 12680720.17 | 0.00 | 0.53 |
Maximum of Months | 0.540568E+10 | 0.140116E+10 | 0.00 | 5834534.27 | 6873449.26 | 0.00 | 0.140774E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.323717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122926E+09 | 0.00 | 0.00 | 0.61 |
February | 0.271566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112710E+09 | 0.00 | 0.00 | 0.67 |
March | 0.279636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37111691.54 | 0.00 | 0.00 | 0.71 |
April | 0.168545E+10 | 21102998.06 | 0.00 | 291467.65 | 16640254.31 | 0.00 | 72782048.28 | 0.00 | 0.73 |
May | 0.835261E+09 | 0.171416E+09 | 0.00 | 1095909.63 | 12118079.87 | 0.00 | 0.227461E+09 | 0.00 | 0.71 |
June | 0.221854E+09 | 0.489456E+09 | 0.00 | 1918428.66 | 778782.91 | 0.00 | 0.262237E+09 | 0.00 | 0.69 |
July | 35330063.83 | 0.753533E+09 | 0.00 | 685945.80 | 60562063.60 | 0.00 | 84004154.53 | 0.00 | 0.65 |
August | 0.248083E+09 | 0.362028E+09 | 0.00 | 1003997.98 | 21174566.03 | 0.00 | 0.149722E+09 | 0.00 | 0.68 |
September | 0.639714E+09 | 0.162570E+09 | 0.00 | 917941.88 | 40101471.00 | 0.00 | 0.154000E+09 | 0.00 | 0.71 |
October | 0.188621E+10 | 28008630.62 | 0.00 | 202577.71 | 12994120.91 | 0.00 | 47429132.82 | 0.00 | 0.77 |
November | 0.291829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29284181.85 | 0.00 | 0.00 | 0.68 |
December | 0.313416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415380E+09 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.203535E+11 | 0.198811E+10 | 0.00 | 6116269.31 | 0.164369E+09 | 0.717412E+09 | 0.997635E+09 | 0.00 | 0.68 |
Minimum of Months | 35330063.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.323717E+10 | 0.753533E+09 | 0.00 | 1918428.66 | 60562063.60 | 0.415380E+09 | 0.262237E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.106174E+09 | 0.00 | 0.00 | 0.687601E+11 | 0.00 | 19.94 |
February | 0.00 | 0.00 | 0.00 | 0.102828E+09 | 0.00 | 0.00 | 0.604150E+11 | 0.00 | 25.48 |
March | 0.00 | 0.00 | 0.00 | 0.119921E+09 | 0.00 | 0.00 | 0.634402E+11 | 0.00 | 29.41 |
April | 0.00 | 10751140.44 | 0.00 | 0.100479E+09 | 0.00 | 0.00 | 0.385961E+11 | 0.00 | 27.92 |
May | 0.00 | 0.371730E+09 | 0.00 | 66275499.93 | 0.00 | 0.00 | 0.209277E+11 | 0.00 | 21.83 |
June | 0.00 | 0.624250E+09 | 0.00 | 26043863.30 | 0.00 | 0.00 | 0.667417E+10 | 0.00 | 13.35 |
July | 0.00 | 0.594653E+10 | 0.00 | 5752965.85 | 0.00 | 0.00 | 0.184583E+10 | 0.00 | 12.79 |
August | 0.00 | 0.317194E+10 | 0.00 | 28009401.68 | 0.00 | 0.00 | 0.800173E+10 | 0.00 | 18.03 |
September | 0.00 | 0.240666E+10 | 0.00 | 55675636.82 | 0.00 | 0.00 | 0.192407E+11 | 0.00 | 24.65 |
October | 0.00 | 0.834826E+09 | 0.00 | 0.102811E+09 | 0.00 | 0.00 | 0.449350E+11 | 0.00 | 32.15 |
November | 0.00 | 0.00 | 0.00 | 0.112708E+09 | 0.00 | 0.00 | 0.650997E+11 | 0.00 | 26.77 |
December | 0.00 | 0.00 | 0.00 | 0.105480E+09 | 0.00 | 0.00 | 0.684917E+11 | 0.00 | 18.33 |
Annual Sum or Average | 0.00 | 0.133667E+11 | 0.00 | 0.932159E+09 | 0.00 | 0.00 | 0.466428E+12 | 0.00 | 22.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5752965.85 | 0.00 | 0.00 | 0.184583E+10 | 0.00 | 12.79 |
Maximum of Months | 0.00 | 0.594653E+10 | 0.00 | 0.119921E+09 | 0.00 | 0.00 | 0.687601E+11 | 0.00 | 32.15 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189871E+11 | 0.00 | 0.00 | 16821025.38 | 0.00 | 0.00 | 0.203782E+11 | 0.00 | 3.85 |
February | 0.121939E+11 | 0.00 | 0.00 | 22713804.51 | 0.00 | 0.00 | 0.222574E+11 | 0.00 | 4.63 |
March | 0.902750E+10 | 0.00 | 0.00 | 31089611.89 | 0.00 | 0.00 | 0.271374E+11 | 0.00 | 5.30 |
April | 0.145228E+10 | 0.379111E+09 | 0.00 | 41144974.17 | 0.00 | 0.00 | 0.238696E+11 | 0.00 | 6.03 |
May | 38841408.21 | 0.206430E+10 | 0.00 | 37038045.39 | 0.00 | 0.00 | 0.171907E+11 | 0.00 | 5.91 |
June | 0.00 | 0.499633E+10 | 0.00 | 25241263.59 | 0.00 | 0.00 | 0.766148E+10 | 0.00 | 5.07 |
July | 0.00 | 0.104358E+11 | 0.00 | 10512044.39 | 0.00 | 0.00 | 0.216046E+10 | 0.00 | 5.04 |
August | 0.00 | 0.593658E+10 | 0.00 | 21553958.08 | 0.00 | 0.00 | 0.772281E+10 | 0.00 | 5.67 |
September | 57512162.42 | 0.386977E+10 | 0.00 | 32448785.31 | 0.00 | 0.00 | 0.151497E+11 | 0.00 | 6.33 |
October | 0.639264E+09 | 0.933799E+09 | 0.00 | 46163757.47 | 0.00 | 0.00 | 0.278305E+11 | 0.00 | 6.46 |
November | 0.110503E+11 | 0.00 | 0.00 | 30821299.15 | 0.00 | 0.00 | 0.263879E+11 | 0.00 | 5.07 |
December | 0.235999E+11 | 0.00 | 0.00 | 13744045.49 | 0.00 | 0.00 | 0.170966E+11 | 0.00 | 3.69 |
Annual Sum or Average | 0.770466E+11 | 0.286156E+11 | 0.00 | 0.329293E+09 | 0.00 | 0.00 | 0.214843E+12 | 0.00 | 5.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 10512044.39 | 0.00 | 0.00 | 0.216046E+10 | 0.00 | 3.69 |
Maximum of Months | 0.235999E+11 | 0.104358E+11 | 0.00 | 46163757.47 | 0.00 | 0.00 | 0.278305E+11 | 0.00 | 6.46 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401041E+11 | 0.00 | 0.00 | 41418026.28 | 0.00 | 0.00 | 0.718017E+11 | 0.00 | 1.48 |
February | 0.273330E+11 | 0.00 | 0.00 | 56114513.47 | 0.00 | 0.00 | 0.677624E+11 | 0.00 | 1.64 |
March | 0.230144E+11 | 0.00 | 0.00 | 78509870.87 | 0.00 | 0.00 | 0.740845E+11 | 0.00 | 1.78 |
April | 0.661445E+10 | 0.126915E+10 | 0.00 | 0.114194E+09 | 4888568.20 | 0.00 | 0.561069E+11 | 0.00 | 1.92 |
May | 0.139654E+10 | 0.533532E+10 | 0.00 | 0.118671E+09 | 0.107884E+09 | 0.00 | 0.379024E+11 | 0.00 | 1.83 |
June | 24886390.83 | 0.123189E+11 | 0.00 | 0.104601E+09 | 0.109770E+09 | 0.00 | 0.185365E+11 | 0.00 | 1.62 |
July | 0.00 | 0.235892E+11 | 0.00 | 48975261.35 | 0.490772E+09 | 0.00 | 0.470397E+10 | 0.00 | 1.57 |
August | 82981633.47 | 0.112260E+11 | 0.00 | 91983770.39 | 0.251971E+09 | 0.00 | 0.153220E+11 | 0.00 | 1.74 |
September | 0.613228E+09 | 0.665501E+10 | 0.00 | 0.114358E+09 | 0.264875E+09 | 0.00 | 0.294703E+11 | 0.00 | 1.94 |
October | 0.493780E+10 | 0.143897E+10 | 0.00 | 0.138447E+09 | 39076432.55 | 0.00 | 0.652169E+11 | 0.00 | 2.07 |
November | 0.179815E+11 | 0.00 | 0.00 | 86897093.84 | 0.00 | 0.00 | 0.830073E+11 | 0.00 | 1.72 |
December | 0.549389E+11 | 0.00 | 0.00 | 31668207.20 | 0.00 | 0.00 | 0.623365E+11 | 0.00 | 1.46 |
Annual Sum or Average | 0.177042E+12 | 0.618325E+11 | 0.00 | 0.102584E+10 | 0.126924E+10 | 0.00 | 0.586251E+12 | 0.00 | 1.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 31668207.20 | 0.00 | 0.00 | 0.470397E+10 | 0.00 | 1.46 |
Maximum of Months | 0.549389E+11 | 0.235892E+11 | 0.00 | 0.138447E+09 | 0.490772E+09 | 0.00 | 0.830073E+11 | 0.00 | 2.07 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24603477.53 | 0.00 | 0.00 | 6369221.37 | 0.00 | 0.125185E+10 | 0.114935E+10 | 0.00 | 0.35 |
February | 7767214.35 | 0.00 | 0.00 | 8371900.10 | 0.00 | 0.833884E+09 | 0.107856E+10 | 0.00 | 0.35 |
March | 14272720.75 | 0.00 | 0.00 | 13445448.48 | 0.00 | 0.575442E+09 | 0.123091E+10 | 0.00 | 0.35 |
April | 2040547.07 | 41258188.88 | 0.00 | 14865646.37 | 0.00 | 76530369.04 | 0.807973E+09 | 0.00 | 0.36 |
May | 0.00 | 0.298026E+09 | 1531.64 | 9061488.64 | 0.00 | 526103.23 | 0.365314E+09 | 224.78 | 0.37 |
June | 0.00 | 0.806619E+09 | 0.00 | 1663653.01 | 0.00 | 2647.61 | 61871819.41 | 0.00 | 0.37 |
July | 0.00 | 0.194858E+10 | 720711.74 | 0.00 | 0.00 | 0.00 | 0.00 | 4959.95 | 0.37 |
August | 0.00 | 0.126573E+10 | 252380.03 | 494907.77 | 0.00 | 0.00 | 3046938.54 | 2858.37 | 0.37 |
September | 0.00 | 0.875941E+09 | 334706.53 | 4647707.71 | 0.00 | 186406.70 | 0.142571E+09 | 3727.09 | 0.37 |
October | 3556014.32 | 0.237408E+09 | 23313.87 | 12735533.80 | 0.00 | 10068501.23 | 0.673938E+09 | 562.52 | 0.36 |
November | 22398370.51 | 1383055.94 | 0.00 | 10511901.54 | 0.00 | 0.753695E+09 | 0.113973E+10 | 0.00 | 0.35 |
December | 33696139.76 | 0.00 | 0.00 | 5479217.20 | 0.00 | 0.152672E+10 | 0.107662E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.108334E+09 | 0.547494E+10 | 1332643.81 | 87646626.01 | 0.00 | 0.502890E+10 | 0.772988E+10 | 12332.70 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 33696139.76 | 0.194858E+10 | 720711.74 | 14865646.37 | 0.00 | 0.152672E+10 | 0.123091E+10 | 4959.95 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135291E+09 | 0.00 | 0.00 | 2744247.98 | 0.00 | 0.155083E+10 | 0.731272E+09 | 0.00 | 0.34 |
February | 0.193824E+09 | 0.00 | 0.00 | 3855890.85 | 0.00 | 0.968901E+09 | 0.796608E+09 | 0.00 | 0.34 |
March | 0.294284E+09 | 0.00 | 0.00 | 7833079.37 | 0.00 | 0.548697E+09 | 0.112727E+10 | 0.00 | 0.35 |
April | 0.222619E+09 | 31999430.01 | 0.00 | 13232974.29 | 239560.41 | 51784326.51 | 0.753308E+09 | 0.00 | 0.36 |
May | 0.131203E+09 | 0.260601E+09 | 18747.24 | 8476371.00 | 4984346.90 | 523162.12 | 0.313063E+09 | 2573.03 | 0.37 |
June | 46483709.26 | 0.748805E+09 | 20001.94 | 1878486.49 | 9001168.14 | 0.00 | 48811256.67 | 1415.88 | 0.37 |
July | 8865294.98 | 0.173463E+10 | 0.00 | 408396.40 | 76353910.84 | 0.00 | 260511.48 | 0.00 | 0.37 |
August | 38669449.68 | 0.110217E+10 | 27466.23 | 1484580.01 | 33080840.47 | 15446.32 | 1423546.13 | 3280.17 | 0.37 |
September | 0.108137E+09 | 0.691398E+09 | 102900.57 | 4838495.57 | 31127720.17 | 302682.51 | 0.119596E+09 | 8630.43 | 0.37 |
October | 0.267617E+09 | 0.151487E+09 | 39534.14 | 9624140.03 | 7630381.51 | 4898248.29 | 0.618080E+09 | 1177.01 | 0.35 |
November | 0.173437E+09 | 0.00 | 0.00 | 4961742.90 | 0.00 | 0.879355E+09 | 0.909121E+09 | 0.00 | 0.34 |
December | 0.134196E+09 | 0.00 | 0.00 | 2208700.55 | 0.00 | 0.187451E+10 | 0.610478E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.175463E+10 | 0.472109E+10 | 208650.13 | 61547105.43 | 0.162418E+09 | 0.587982E+10 | 0.602929E+10 | 17076.52 | 0.36 |
Minimum of Months | 8865294.98 | 0.00 | 0.00 | 408396.40 | 0.00 | 0.00 | 260511.48 | 0.00 | 0.34 |
Maximum of Months | 0.294284E+09 | 0.173463E+10 | 102900.57 | 13232974.29 | 76353910.84 | 0.187451E+10 | 0.112727E+10 | 8630.43 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187410E+09 | 0.00 | 0.00 | 73819583.98 | 0.00 | 0.00 | 0.459353E+10 | 0.00 | 0.07 |
February | 25847010.22 | 0.00 | 0.00 | 77731663.92 | 0.00 | 0.00 | 0.388210E+10 | 0.00 | 0.08 |
March | 0.00 | 0.00 | 0.00 | 82808695.02 | 0.00 | 0.00 | 0.336275E+10 | 0.00 | 0.07 |
April | 0.00 | 99540774.47 | 0.00 | 99428497.71 | 0.00 | 0.00 | 0.191297E+10 | 0.00 | 0.09 |
May | 0.00 | 0.821655E+09 | 0.00 | 71852031.84 | 0.00 | 0.00 | 0.975535E+09 | 0.00 | 0.10 |
June | 0.00 | 0.208586E+10 | 0.00 | 37918986.85 | 0.00 | 0.00 | 0.240786E+09 | 0.00 | 0.12 |
July | 0.00 | 0.454459E+10 | 0.00 | 1589614.37 | 0.00 | 0.00 | 6356069.86 | 0.00 | 0.13 |
August | 0.00 | 0.247421E+10 | 0.00 | 21480831.80 | 0.00 | 0.00 | 0.111200E+09 | 0.00 | 0.13 |
September | 0.00 | 0.190995E+10 | 0.00 | 59062571.06 | 0.00 | 0.00 | 0.680887E+09 | 0.00 | 0.13 |
October | 0.00 | 0.523570E+09 | 0.00 | 0.114136E+09 | 0.00 | 0.00 | 0.252615E+10 | 0.00 | 0.11 |
November | 0.106798E+09 | 0.00 | 0.00 | 0.108696E+09 | 0.00 | 0.00 | 0.434102E+10 | 0.00 | 0.09 |
December | 0.182167E+09 | 0.00 | 0.00 | 68240985.76 | 0.00 | 0.00 | 0.456932E+10 | 0.00 | 0.07 |
Annual Sum or Average | 0.502221E+09 | 0.124594E+11 | 0.00 | 0.816766E+09 | 0.00 | 0.00 | 0.272026E+11 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1589614.37 | 0.00 | 0.00 | 6356069.86 | 0.00 | 0.07 |
Maximum of Months | 0.187410E+09 | 0.454459E+10 | 0.00 | 0.114136E+09 | 0.00 | 0.00 | 0.459353E+10 | 0.00 | 0.13 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155362E+10 | 0.00 | 0.00 | 48249701.78 | 0.00 | 0.285113E+10 | 0.262514E+11 | 0.00 | 0.39 |
February | 0.221525E+10 | 0.00 | 0.00 | 65888118.52 | 0.00 | 0.217423E+10 | 0.200925E+11 | 0.00 | 0.39 |
March | 0.287694E+10 | 0.00 | 0.00 | 0.103441E+09 | 0.00 | 0.527343E+09 | 0.201933E+11 | 0.00 | 0.39 |
April | 0.216222E+10 | 0.522882E+09 | 3222.51 | 0.144333E+09 | 5076083.87 | 14258801.03 | 0.975318E+10 | 28167.39 | 0.39 |
May | 0.133506E+10 | 0.347262E+10 | 354858.32 | 87890614.88 | 66743969.22 | 2271137.32 | 0.392515E+10 | 23082.91 | 0.40 |
June | 0.501565E+09 | 0.960285E+10 | 0.00 | 15950274.23 | 0.119399E+09 | 0.00 | 0.635394E+09 | 0.00 | 0.41 |
July | 96932810.18 | 0.215954E+11 | 0.00 | 5402218.17 | 0.920823E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 0.480862E+09 | 0.136263E+11 | 956679.21 | 22728430.73 | 0.401562E+09 | 0.00 | 41978625.00 | 904.17 | 0.41 |
September | 0.123827E+10 | 0.839944E+10 | 0.00 | 62290595.76 | 0.384605E+09 | 642217.21 | 0.155480E+10 | 0.00 | 0.40 |
October | 0.257657E+10 | 0.187217E+10 | 0.00 | 0.130265E+09 | 90140157.63 | 14601798.78 | 0.753088E+10 | 0.00 | 0.39 |
November | 0.216538E+10 | 426507.29 | 0.00 | 74169248.05 | 0.00 | 0.608709E+09 | 0.217440E+11 | 0.00 | 0.39 |
December | 0.158410E+10 | 0.00 | 0.00 | 40580552.68 | 0.00 | 0.624302E+10 | 0.256746E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.187868E+11 | 0.590921E+11 | 1314760.03 | 0.801188E+09 | 0.198835E+10 | 0.124362E+11 | 0.137397E+12 | 52154.47 | 0.40 |
Minimum of Months | 96932810.18 | 0.00 | 0.00 | 5402218.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.287694E+10 | 0.215954E+11 | 956679.21 | 0.144333E+09 | 0.920823E+09 | 0.624302E+10 | 0.262514E+11 | 28167.39 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26099873.09 | 0.00 | 0.00 | 6381550.57 | 0.00 | 0.126165E+10 | 0.112697E+10 | 0.00 | 0.35 |
February | 7325540.13 | 0.00 | 0.00 | 9089880.53 | 0.00 | 0.789878E+09 | 0.112332E+10 | 0.00 | 0.35 |
March | 4053856.32 | 0.00 | 0.00 | 13067170.83 | 0.00 | 0.573693E+09 | 0.125123E+10 | 0.00 | 0.35 |
April | 0.00 | 43717631.73 | 0.00 | 17112041.38 | 0.00 | 79028518.85 | 0.814178E+09 | 0.00 | 0.36 |
May | 0.00 | 0.306179E+09 | 38164.22 | 12076376.97 | 0.00 | 34992.62 | 0.370007E+09 | 61.30 | 0.37 |
June | 0.00 | 0.827527E+09 | 0.00 | 2459545.50 | 0.00 | 787.35 | 61653613.90 | 0.00 | 0.38 |
July | 0.00 | 0.199767E+10 | 209190.60 | 0.00 | 0.00 | 0.00 | 0.00 | 2607.10 | 0.38 |
August | 0.00 | 0.130249E+10 | 95116.89 | 615526.78 | 0.00 | 0.00 | 3296831.94 | 1420.62 | 0.38 |
September | 0.00 | 0.908924E+09 | 150048.72 | 5068218.69 | 0.00 | 19756.00 | 0.145153E+09 | 1822.97 | 0.38 |
October | 3714248.16 | 0.234720E+09 | 49341.36 | 12597091.91 | 0.00 | 16431939.18 | 0.677263E+09 | 765.03 | 0.36 |
November | 22352885.95 | 1020733.81 | 0.00 | 10955839.40 | 0.00 | 0.758657E+09 | 0.113716E+10 | 0.00 | 0.35 |
December | 31165052.51 | 0.00 | 0.00 | 5630641.28 | 0.00 | 0.148794E+10 | 0.110537E+10 | 0.00 | 0.34 |
Annual Sum or Average | 94711456.16 | 0.562225E+10 | 541861.78 | 95053883.84 | 0.00 | 0.496733E+10 | 0.781560E+10 | 6677.02 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 31165052.51 | 0.199767E+10 | 209190.60 | 17112041.38 | 0.00 | 0.148794E+10 | 0.125123E+10 | 2607.10 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134945E+09 | 0.00 | 0.00 | 2447929.20 | 0.00 | 0.146429E+10 | 0.806694E+09 | 0.00 | 0.34 |
February | 0.168910E+09 | 0.00 | 0.00 | 4643155.42 | 0.00 | 0.893298E+09 | 0.872079E+09 | 0.00 | 0.34 |
March | 0.215650E+09 | 0.00 | 0.00 | 8129001.90 | 0.00 | 0.588354E+09 | 0.107887E+10 | 0.00 | 0.35 |
April | 0.181413E+09 | 33723969.36 | 0.00 | 16185490.73 | 201146.02 | 68773853.06 | 0.742293E+09 | 0.00 | 0.36 |
May | 0.122949E+09 | 0.260730E+09 | 0.00 | 12531322.92 | 4733610.69 | 223962.80 | 0.334174E+09 | 0.00 | 0.37 |
June | 48294291.54 | 0.759018E+09 | 32818.47 | 3329599.01 | 8176268.81 | 0.00 | 57781936.33 | 654.19 | 0.38 |
July | 9764487.77 | 0.176534E+10 | 0.00 | 770774.51 | 69342046.15 | 0.00 | 2825662.88 | 0.00 | 0.38 |
August | 41488856.55 | 0.112537E+10 | 0.00 | 2257129.77 | 29981553.62 | 18042.43 | 9101369.63 | 0.00 | 0.37 |
September | 0.106410E+09 | 0.707115E+09 | 36327.07 | 6018604.65 | 29036419.03 | 153556.29 | 0.131508E+09 | 1189.65 | 0.37 |
October | 0.213699E+09 | 0.152488E+09 | 0.00 | 9961201.50 | 6669865.85 | 19045590.77 | 0.606099E+09 | 551.92 | 0.35 |
November | 0.168831E+09 | 0.00 | 0.00 | 5450870.09 | 0.00 | 0.851518E+09 | 0.926121E+09 | 0.00 | 0.34 |
December | 0.131421E+09 | 0.00 | 0.00 | 2051811.04 | 0.00 | 0.176109E+10 | 0.713653E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.154378E+10 | 0.480378E+10 | 69145.54 | 73776890.74 | 0.148141E+09 | 0.564677E+10 | 0.628120E+10 | 2395.76 | 0.36 |
Minimum of Months | 9764487.77 | 0.00 | 0.00 | 770774.51 | 0.00 | 0.00 | 2825662.88 | 0.00 | 0.34 |
Maximum of Months | 0.215650E+09 | 0.176534E+10 | 36327.07 | 16185490.73 | 69342046.15 | 0.176109E+10 | 0.107887E+10 | 1189.65 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 10871152.94 | 0.00 | 0.00 | 0.317549E+10 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.00 | 15419813.94 | 0.00 | 0.00 | 0.343012E+10 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.00 | 22480825.30 | 0.00 | 0.00 | 0.413146E+10 | 0.00 | 0.04 |
April | 0.00 | 215608.26 | 0.00 | 36654755.27 | 0.00 | 0.00 | 0.398392E+10 | 0.00 | 0.06 |
May | 0.00 | 0.146266E+09 | 0.00 | 39837409.47 | 0.00 | 0.00 | 0.296682E+10 | 0.00 | 0.09 |
June | 0.00 | 0.533100E+09 | 0.00 | 30980374.65 | 0.00 | 0.00 | 0.137491E+10 | 0.00 | 0.11 |
July | 0.00 | 0.291544E+10 | 0.00 | 4602728.64 | 0.00 | 0.00 | 76174386.45 | 0.00 | 0.12 |
August | 0.00 | 0.127541E+10 | 0.00 | 18504640.24 | 0.00 | 0.00 | 0.594014E+09 | 0.00 | 0.11 |
September | 0.00 | 0.868497E+09 | 0.00 | 23255332.58 | 0.00 | 0.00 | 0.120991E+10 | 0.00 | 0.10 |
October | 0.00 | 0.187947E+09 | 0.00 | 32850704.12 | 0.00 | 0.00 | 0.293929E+10 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.00 | 20784741.73 | 0.00 | 0.00 | 0.369618E+10 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 | 8676402.13 | 0.00 | 0.00 | 0.279103E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.592687E+10 | 0.00 | 0.264919E+09 | 0.00 | 0.00 | 0.303693E+11 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4602728.64 | 0.00 | 0.00 | 76174386.45 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.291544E+10 | 0.00 | 39837409.47 | 0.00 | 0.00 | 0.413146E+10 | 0.00 | 0.12 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11119913.14 | 0.00 | 0.00 | 1098041.73 | 0.00 | 0.445675E+09 | 0.156005E+09 | 0.00 | 0.35 |
February | 5462294.40 | 0.00 | 0.00 | 1621894.74 | 0.00 | 0.325043E+09 | 0.153778E+09 | 0.00 | 0.35 |
March | 5813790.25 | 0.00 | 0.00 | 2935602.80 | 0.00 | 0.271675E+09 | 0.179178E+09 | 0.00 | 0.35 |
April | 595606.91 | 10585351.54 | 0.00 | 3429885.06 | 0.00 | 71229232.63 | 0.150941E+09 | 0.00 | 0.36 |
May | 0.00 | 75923407.71 | 334.83 | 2034669.07 | 0.00 | 6678537.07 | 86462144.12 | 57.39 | 0.37 |
June | 0.00 | 0.205517E+09 | 0.00 | 384429.67 | 0.00 | 10101.93 | 15711593.91 | 0.00 | 0.38 |
July | 0.00 | 0.493847E+09 | 9741.06 | 0.00 | 0.00 | 0.00 | 0.00 | 110.85 | 0.38 |
August | 0.00 | 0.318809E+09 | 13823.43 | 121296.99 | 0.00 | 10565.90 | 1166349.53 | 1012.47 | 0.37 |
September | 0.00 | 0.217795E+09 | 7801.21 | 1072034.94 | 0.00 | 6707063.57 | 32218699.69 | 108.68 | 0.37 |
October | 1568826.57 | 57894267.42 | 0.00 | 2825036.68 | 0.00 | 59604126.73 | 0.124682E+09 | 0.00 | 0.36 |
November | 5433148.68 | 361974.57 | 0.00 | 2106599.06 | 0.00 | 0.299608E+09 | 0.180526E+09 | 0.00 | 0.35 |
December | 11467499.11 | 0.00 | 0.00 | 880408.10 | 0.00 | 0.515310E+09 | 0.136942E+09 | 0.00 | 0.34 |
Annual Sum or Average | 41461079.06 | 0.138073E+10 | 31700.53 | 18509898.84 | 0.00 | 0.200155E+10 | 0.121761E+10 | 1289.40 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 11467499.11 | 0.493847E+09 | 13823.43 | 3429885.06 | 0.00 | 0.515310E+09 | 0.180526E+09 | 1012.47 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33465367.22 | 0.00 | 0.00 | 378572.38 | 0.00 | 0.517354E+09 | 59808870.26 | 0.00 | 0.34 |
February | 48423662.40 | 0.00 | 0.00 | 612428.04 | 0.00 | 0.357250E+09 | 88873213.04 | 0.00 | 0.34 |
March | 72739123.97 | 0.00 | 0.00 | 1575087.06 | 0.00 | 0.272119E+09 | 0.150728E+09 | 0.00 | 0.35 |
April | 55537624.65 | 8425560.01 | 0.00 | 3060949.32 | 65154.75 | 59899246.62 | 0.142814E+09 | 0.00 | 0.36 |
May | 31813442.20 | 67495393.55 | 7828.48 | 1941809.80 | 1237856.32 | 1476470.68 | 78255849.47 | 3545.50 | 0.37 |
June | 10895014.18 | 0.192565E+09 | 7050.18 | 436862.97 | 2246009.99 | 3494.27 | 12747461.03 | 429.56 | 0.38 |
July | 2382709.42 | 0.444087E+09 | 37757.67 | 109557.66 | 18747754.25 | 0.00 | 194740.10 | 739.69 | 0.38 |
August | 9622212.27 | 0.282013E+09 | 47353.01 | 359143.26 | 8105787.88 | 5104.16 | 435881.78 | 1451.60 | 0.37 |
September | 27090249.40 | 0.176696E+09 | 21259.36 | 1107943.43 | 7668449.29 | 4663419.69 | 27246758.09 | 2224.46 | 0.37 |
October | 68300483.61 | 38354342.35 | 1934.17 | 2033872.57 | 1886080.10 | 34889809.55 | 0.132483E+09 | 1010.73 | 0.35 |
November | 44033025.93 | 0.00 | 0.00 | 853625.75 | 0.00 | 0.338142E+09 | 0.114531E+09 | 0.00 | 0.34 |
December | 32212341.69 | 0.00 | 0.00 | 275965.86 | 0.00 | 0.584188E+09 | 43900398.56 | 0.00 | 0.34 |
Annual Sum or Average | 0.436515E+09 | 0.120964E+10 | 123182.87 | 12745818.11 | 39957092.58 | 0.216999E+10 | 0.852020E+09 | 9401.54 | 0.36 |
Minimum of Months | 2382709.42 | 0.00 | 0.00 | 109557.66 | 0.00 | 0.00 | 194740.10 | 0.00 | 0.34 |
Maximum of Months | 72739123.97 | 0.444087E+09 | 47353.01 | 3060949.32 | 18747754.25 | 0.584188E+09 | 0.150728E+09 | 3545.50 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28630888.27 | 0.00 | 0.00 | 15246218.93 | 0.00 | 0.207353E+10 | 0.196805E+10 | 0.00 | 0.41 |
February | 9431511.69 | 0.00 | 0.00 | 16491250.59 | 0.00 | 0.143248E+10 | 0.178980E+10 | 0.00 | 0.41 |
March | 5439064.13 | 89194.96 | 0.00 | 18662321.22 | 0.00 | 0.122421E+10 | 0.180828E+10 | 0.00 | 0.40 |
April | 1296317.40 | 50806482.55 | 0.00 | 20623367.64 | 0.00 | 0.290436E+09 | 0.122289E+10 | 0.00 | 0.41 |
May | 0.00 | 0.425216E+09 | 125517.05 | 12066214.36 | 0.00 | 5804600.41 | 0.646392E+09 | 2330.78 | 0.41 |
June | 0.00 | 0.119750E+10 | 103527.60 | 2303506.99 | 0.00 | 19811.38 | 0.110914E+09 | 1974.91 | 0.42 |
July | 0.00 | 0.303150E+10 | 1848718.95 | 0.00 | 0.00 | 0.00 | 0.00 | 24425.25 | 0.42 |
August | 0.00 | 0.197081E+10 | 1031206.10 | 850631.94 | 0.00 | 40822.64 | 10146124.10 | 17355.53 | 0.42 |
September | 0.00 | 0.139215E+10 | 947813.25 | 6971044.37 | 0.00 | 3087015.55 | 0.257953E+09 | 20339.15 | 0.43 |
October | 7634419.41 | 0.387399E+09 | 53811.64 | 20387557.68 | 0.00 | 67630337.53 | 0.111380E+10 | 2144.80 | 0.42 |
November | 36983733.66 | 1958113.79 | 0.00 | 21516594.71 | 0.00 | 0.133585E+10 | 0.184512E+10 | 0.00 | 0.41 |
December | 29093690.55 | 0.00 | 0.00 | 14427321.26 | 0.00 | 0.244004E+10 | 0.197080E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.118510E+09 | 0.845743E+10 | 4110594.58 | 0.149546E+09 | 0.00 | 0.887313E+10 | 0.127441E+11 | 68570.42 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 36983733.66 | 0.303150E+10 | 1848718.95 | 21516594.71 | 0.00 | 0.244004E+10 | 0.197080E+10 | 24425.25 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.725615E+10 | 0.00 | 0.00 | 38131278.73 | 0.00 | 0.00 | 0.635567E+11 | 0.00 | 4.56 |
February | 0.371262E+10 | 0.00 | 0.00 | 46328871.28 | 0.00 | 0.00 | 0.559103E+11 | 0.00 | 4.89 |
March | 0.180281E+10 | 0.00 | 0.00 | 66771078.09 | 0.00 | 0.00 | 0.589585E+11 | 0.00 | 5.24 |
April | 0.393347E+09 | 0.651106E+09 | 0.00 | 85456177.85 | 0.00 | 0.00 | 0.384577E+11 | 0.00 | 5.62 |
May | 65908161.64 | 0.280995E+10 | 0.00 | 82872035.57 | 0.00 | 0.00 | 0.244593E+11 | 0.00 | 5.43 |
June | 1015151.91 | 0.736523E+10 | 0.00 | 67856727.18 | 0.00 | 0.00 | 0.123827E+11 | 0.00 | 4.95 |
July | 0.00 | 0.142126E+11 | 0.00 | 31585901.79 | 15074590.45 | 0.00 | 0.369805E+10 | 0.00 | 4.80 |
August | 4976830.75 | 0.633841E+10 | 0.00 | 61158962.61 | 0.00 | 0.00 | 0.106102E+11 | 0.00 | 5.19 |
September | 44502703.35 | 0.362627E+10 | 0.00 | 70302547.62 | 3000401.90 | 0.00 | 0.187529E+11 | 0.00 | 5.59 |
October | 0.375035E+09 | 0.661452E+09 | 0.00 | 81765628.93 | 7299659.32 | 0.00 | 0.413313E+11 | 0.00 | 5.76 |
November | 0.308505E+10 | 0.00 | 0.00 | 52076876.31 | 0.00 | 0.00 | 0.585724E+11 | 0.00 | 4.99 |
December | 0.982091E+10 | 0.00 | 0.00 | 32807075.21 | 0.00 | 0.00 | 0.649051E+11 | 0.00 | 4.53 |
Annual Sum or Average | 0.265623E+11 | 0.356650E+11 | 0.00 | 0.717113E+09 | 25374651.67 | 0.00 | 0.451595E+12 | 0.00 | 5.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 31585901.79 | 0.00 | 0.00 | 0.369805E+10 | 0.00 | 4.53 |
Maximum of Months | 0.982091E+10 | 0.142126E+11 | 0.00 | 85456177.85 | 15074590.45 | 0.00 | 0.649051E+11 | 0.00 | 5.76 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274026E+10 | 0.00 | 0.00 | 50947711.96 | 0.00 | 0.00 | 0.696019E+11 | 0.00 | 4.65 |
February | 0.151504E+10 | 0.00 | 0.00 | 58319234.24 | 0.00 | 0.00 | 0.598404E+11 | 0.00 | 5.03 |
March | 0.617819E+09 | 0.00 | 0.00 | 79446023.31 | 0.00 | 0.00 | 0.623667E+11 | 0.00 | 5.44 |
April | 0.104812E+09 | 0.696366E+09 | 0.00 | 96708709.13 | 0.00 | 0.00 | 0.404730E+11 | 0.00 | 5.90 |
May | 6227979.34 | 0.299925E+10 | 0.00 | 91155148.82 | 0.00 | 0.00 | 0.256857E+11 | 0.00 | 5.72 |
June | 0.00 | 0.783024E+10 | 0.00 | 71934829.33 | 0.00 | 0.00 | 0.129600E+11 | 0.00 | 5.22 |
July | 0.00 | 0.150780E+11 | 0.00 | 33112312.85 | 0.00 | 0.00 | 0.386375E+10 | 0.00 | 5.06 |
August | 0.00 | 0.673402E+10 | 0.00 | 65714506.41 | 0.00 | 0.00 | 0.111175E+11 | 0.00 | 5.46 |
September | 11733083.72 | 0.385868E+10 | 0.00 | 77077587.58 | 0.00 | 0.00 | 0.196541E+11 | 0.00 | 5.88 |
October | 0.174758E+09 | 0.708063E+09 | 0.00 | 91970112.10 | 61316.42 | 0.00 | 0.434048E+11 | 0.00 | 6.03 |
November | 0.101639E+10 | 0.00 | 0.00 | 65069218.89 | 0.00 | 0.00 | 0.624745E+11 | 0.00 | 5.14 |
December | 0.422947E+10 | 0.00 | 0.00 | 45670182.79 | 0.00 | 0.00 | 0.719587E+11 | 0.00 | 4.61 |
Annual Sum or Average | 0.104165E+11 | 0.379046E+11 | 0.00 | 0.827126E+09 | 61316.42 | 0.00 | 0.483401E+12 | 0.00 | 5.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 33112312.85 | 0.00 | 0.00 | 0.386375E+10 | 0.00 | 4.61 |
Maximum of Months | 0.422947E+10 | 0.150780E+11 | 0.00 | 96708709.13 | 61316.42 | 0.00 | 0.719587E+11 | 0.00 | 6.03 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.107728E+09 | 0.00 | 0.00 | 0.823363E+11 | 0.00 | 17.92 |
February | 0.00 | 0.00 | 0.00 | 0.104970E+09 | 0.00 | 0.00 | 0.709034E+11 | 0.00 | 20.90 |
March | 0.00 | 0.00 | 0.00 | 0.125234E+09 | 0.00 | 0.00 | 0.743932E+11 | 0.00 | 23.18 |
April | 0.00 | 0.00 | 0.00 | 0.144387E+09 | 0.00 | 0.00 | 0.486843E+11 | 0.00 | 22.00 |
May | 0.00 | 0.219009E+09 | 0.00 | 0.142740E+09 | 0.00 | 0.00 | 0.275392E+11 | 0.00 | 17.83 |
June | 0.00 | 0.545054E+09 | 0.00 | 0.117132E+09 | 0.00 | 0.00 | 0.967965E+10 | 0.00 | 12.36 |
July | 0.00 | 0.929215E+10 | 0.00 | 11120600.26 | 0.00 | 0.00 | 0.122167E+10 | 0.00 | 11.92 |
August | 0.00 | 0.343202E+10 | 0.00 | 63891537.37 | 0.00 | 0.00 | 0.819838E+10 | 0.00 | 15.16 |
September | 0.00 | 0.204829E+10 | 0.00 | 91272169.73 | 0.00 | 0.00 | 0.205578E+11 | 0.00 | 19.59 |
October | 0.00 | 0.336113E+09 | 0.00 | 0.128181E+09 | 0.00 | 0.00 | 0.514464E+11 | 0.00 | 24.66 |
November | 0.00 | 0.00 | 0.00 | 0.115452E+09 | 0.00 | 0.00 | 0.755538E+11 | 0.00 | 21.92 |
December | 0.00 | 0.00 | 0.00 | 0.106907E+09 | 0.00 | 0.00 | 0.823039E+11 | 0.00 | 16.73 |
Annual Sum or Average | 0.00 | 0.158726E+11 | 0.00 | 0.125902E+10 | 0.00 | 0.00 | 0.552818E+12 | 0.00 | 18.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 11120600.26 | 0.00 | 0.00 | 0.122167E+10 | 0.00 | 11.92 |
Maximum of Months | 0.00 | 0.929215E+10 | 0.00 | 0.144387E+09 | 0.00 | 0.00 | 0.823363E+11 | 0.00 | 24.66 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 1699772.26 | 0.00 | 21879697.73 | 0.210914E+09 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.00 | 4294100.07 | 0.00 | 17360387.04 | 0.358603E+09 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.00 | 8636395.55 | 0.00 | 0.00 | 0.553682E+09 | 0.00 | 0.03 |
April | 0.00 | 3470301.32 | 0.00 | 19468115.18 | 0.00 | 0.00 | 0.651298E+09 | 0.00 | 0.06 |
May | 0.00 | 0.133421E+09 | 0.00 | 18675325.99 | 0.00 | 0.00 | 0.462832E+09 | 0.00 | 0.09 |
June | 0.00 | 0.419964E+09 | 0.00 | 10995914.23 | 0.00 | 0.00 | 0.171487E+09 | 0.00 | 0.12 |
July | 0.00 | 0.135902E+10 | 0.00 | 332408.97 | 0.00 | 0.00 | 1851428.82 | 0.00 | 0.13 |
August | 0.00 | 0.745625E+09 | 0.00 | 4639416.08 | 0.00 | 0.00 | 48665706.58 | 0.00 | 0.11 |
September | 0.00 | 0.511272E+09 | 0.00 | 8405095.11 | 0.00 | 0.00 | 0.146272E+09 | 0.00 | 0.10 |
October | 0.00 | 0.116837E+09 | 0.00 | 13593549.46 | 0.00 | 0.00 | 0.409188E+09 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.00 | 6956251.89 | 0.00 | 2542938.93 | 0.430905E+09 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 803996.84 | 0.00 | 0.183125E+09 | 0.130237E+09 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.328961E+10 | 0.00 | 98500341.64 | 0.00 | 0.224908E+09 | 0.357594E+10 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 332408.97 | 0.00 | 0.00 | 1851428.82 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.135902E+10 | 0.00 | 19468115.18 | 0.00 | 0.183125E+09 | 0.651298E+09 | 0.00 | 0.13 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.263857E+12 | 0.139914E+11 | 0.160252E+12 | 0.439962E+12 | 0.132724E+12 |
February | 0.280611E+12 | 0.113395E+11 | 0.123298E+12 | 0.378857E+12 | 0.163114E+12 |
March | 0.461955E+12 | 0.109749E+11 | 0.115130E+12 | 0.395093E+12 | 0.223548E+12 |
April | 0.492737E+12 | 0.589709E+10 | 0.678811E+11 | 0.259513E+12 | 0.514284E+12 |
May | 0.546372E+12 | 0.246804E+10 | 0.325533E+11 | 0.148584E+12 | 0.824777E+12 |
June | 0.507140E+12 | -517402760.3 | -476291134.9 | 0.374851E+11 | 0.108928E+13 |
July | 0.473112E+12 | -0.411541E+10 | -0.538671E+11 | -0.648459E+11 | 0.132098E+13 |
August | 0.428188E+12 | -0.152395E+10 | -0.154151E+11 | 0.197905E+11 | 0.114593E+13 |
September | 0.374784E+12 | 0.441260E+09 | 0.667648E+10 | 0.998845E+11 | 0.942669E+12 |
October | 0.338936E+12 | 0.525509E+10 | 0.608038E+11 | 0.287301E+12 | 0.556932E+12 |
November | 0.262879E+12 | 0.113044E+11 | 0.125656E+12 | 0.413521E+12 | 0.207015E+12 |
December | 0.217145E+12 | 0.150322E+11 | 0.172453E+12 | 0.454996E+12 | 0.130360E+12 |
Annual Sum or Average | 0.464771E+13 | 0.705472E+11 | 0.794946E+12 | 0.287014E+13 | 0.725161E+13 |
Minimum of Months | 0.217145E+12 | -0.411541E+10 | -0.538671E+11 | -0.648459E+11 | 0.130360E+12 |
Maximum of Months | 0.546372E+12 | 0.150322E+11 | 0.172453E+12 | 0.454996E+12 | 0.132098E+13 |