Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:24
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2024-07-03 12:24:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 13005.59 | 1146.34 | 1146.34 |
Net Site Energy | 13005.59 | 1146.34 | 1146.34 |
Total Source Energy | 28400.87 | 2503.32 | 2503.32 |
Net Source Energy | 28400.87 | 2503.32 | 2503.32 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1589.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1461.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 321.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1661.82 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 841.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1001.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2760.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6866.45 | 6139.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 97.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1492.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1461.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 321.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 15.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 11.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1001.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 6.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 2760.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1589.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1461.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 321.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1661.82 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 841.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1001.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 6.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 2760.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 162.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 217.75 | 383.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.59 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 605.22 | 541.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 162.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 217.75 | 383.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.59 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 605.22 | 541.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6866.446 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6866.446 | 100.00 |
Total On-Site and Utility Electric Sources | 6866.446 | 100.00 |
Total Electricity End Uses | 6866.446 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 115.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8357.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 PTAC COOLING COIL | ROOM_2_FLR_3 PTAC COOLING COIL | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | ROOM_5_FLR_3 PTAC COOLING COIL | ROOM_6_FLR_3 PTAC COOLING COIL | ROOM_1_FLR_6 PTAC COOLING COIL | ROOM_2_FLR_6 PTAC COOLING COIL | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | PTAC_3 PTAC COOLING COIL | PTAC_6 PTAC COOLING COIL | VAV_FLR_1 COOLING COIL | VAV_FLR_6 COOLING COIL | VAV_FLR_0 COOLING COIL | PSZ_LAUNDRY COOLING COIL | PSZ_CAFE COOLING COIL | PSZ_KITCHEN COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_FLR_1 HEATING COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | VAV_FLR_6 HEATING COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 HEATING COIL | ROOM_2_FLR_3 HEATING COIL | ROOM_3_MULT19_FLR_3 HEATING COIL | ROOM_4_MULT19_FLR_3 HEATING COIL | ROOM_5_FLR_3 HEATING COIL | ROOM_6_FLR_3 HEATING COIL | ROOM_1_FLR_6 HEATING COIL | ROOM_2_FLR_6 HEATING COIL | ROOM_3_MULT9_FLR_6 HEATING COIL | VAV_FLR_0 HEATING COIL | PTAC_3 HEATING COIL | PTAC_6 HEATING COIL | PSZ_LAUNDRY HEATING COIL | PSZ_CAFE HEATING COIL | PSZ_KITCHEN HEATING COIL | ROOM_1_FLR_3 PTAC COOLING COIL | ROOM_2_FLR_3 PTAC COOLING COIL | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | ROOM_5_FLR_3 PTAC COOLING COIL | ROOM_6_FLR_3 PTAC COOLING COIL | ROOM_1_FLR_6 PTAC COOLING COIL | ROOM_2_FLR_6 PTAC COOLING COIL | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | PTAC_3 PTAC COOLING COIL | PTAC_6 PTAC COOLING COIL | VAV_FLR_1 COOLING COIL | VAV_FLR_6 COOLING COIL | VAV_FLR_0 COOLING COIL | PSZ_LAUNDRY COOLING COIL | PSZ_CAFE COOLING COIL | PSZ_KITCHEN COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| VAV_FLR_1 FAN | VAV_FLR_6 FAN | VAV_FLR_0 SZVAV FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | LAUNDRY_FLR_1 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3_PTAC_SUPPLY FAN | ROOM_2_FLR_3_PTAC_SUPPLY FAN | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | ROOM_5_FLR_3_PTAC_SUPPLY FAN | ROOM_6_FLR_3_PTAC_SUPPLY FAN | ROOM_1_FLR_6_PTAC_SUPPLY FAN | ROOM_2_FLR_6_PTAC_SUPPLY FAN | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | PTAC_3_PTAC_SUPPLY FAN | PTAC_6_PTAC_SUPPLY FAN | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |AirLoopSystemComponentLoadsMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |AirLoopSystemComponentEnergyUseMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:24 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1368.30 | 497.27 | 98.60 | 673.82 | 98.60 |
Gross Window-Wall Ratio [%] | 30.01 | 26.54 | 24.26 | 35.97 | 24.26 |
Above Ground Window-Wall Ratio [%] | 33.99 | 29.91 | 28.11 | 40.54 | 28.11 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1368.30 | 497.27 | 98.60 | 673.82 | 98.60 |
Gross Window-Wall Ratio [%] | 30.01 | 26.54 | 24.26 | 35.97 | 24.26 |
Above Ground Window-Wall Ratio [%] | 33.99 | 29.91 | 28.11 | 40.54 | 28.11 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 11.0679 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 16.1458 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 16.1458 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 15.0695 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 13.9931 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 4.22 | 4.22 | 12.2708 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 4.23 | 4.23 | 12.2708 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 18.31 | 18.31 | 5.3819 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 7.75 | 7.75 | 12.2709 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 36.97 | 36.97 | 15.0695 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 36.97 | 36.97 | 15.0695 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 30.28 | 30.28 | 12.9167 | 4.65 | 2935.6055 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 32.40 | 32.40 | 5.3819 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1368.30 | 1368.30 | 11.3147 | 7.07 | 41.0811 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1368.30 | 1368.30 | 11.3147 | 7.07 | 41.0811 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.0679 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 16.1458 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 16.1458 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 16.1458 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 8.6111 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 15.0695 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 13.9931 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 12.2708 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 12.2708 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 5.3819 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 12.2708 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 12.2708 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 12.2709 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 15.0695 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 15.0695 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 12.9167 | 4.65 | 2935.6055 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 5.3819 | 18.58 | 0.0000 | |
Total | 11345.29 | 11.3147 | 3.54 | 41.0811 | |||||||
Conditioned Total | 11345.29 | 11.3147 | 3.54 | 41.0811 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 6.0626 | 8.82 | 37.2091 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-19:10 | 14-JAN-17:10 | - | - | - | - | - | - | - | - | - | - | 27-MAR-20:30 |
Heating | 0.00 | 332395.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 210702.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86555.31 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11860.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47787.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 228981.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1344.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 500039.02 | 650989.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 24111.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 308284.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 210702.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 365.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1288.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 9600.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 47787.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 47.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 228981.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 431.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 671.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1723.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4629.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4833.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1019.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5262.99 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2666.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3172.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2992.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 139.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 21746.04 | 6654.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 151.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 408.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 89.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.89 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 279.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 263.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1916.75 | 586.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 151.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 408.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 89.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.89 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 279.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 263.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1916.75 | 586.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 2.98 | 0.505431 | 0.300000 | 0.895000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.507415 | 0.100723 | 0.300000 | 0.152224 | 0.300000 | 0.500000 | 0.003783 | 0.000069 | 0.335825 | 12.89 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.328835 | 0.179980 | 0.412000 | 0.135480 | 0.479947 | 0.500000 | 0.002117 | 0.000024 | 0.135480 | 12.89 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.374866 | 0.333861 | 0.300000 | 0.112460 | 0.890297 | 0.500000 | 0.001141 | 0.000035 | 0.169389 | 12.89 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.186389 | 0.387397 | 0.457000 | 0.085180 | 1.00 | 0.500000 | 0.000983 | 0.000036 | 0.174734 | 12.89 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 6.27 | 0.158927 | 0.445000 | 2.79 | 0.445000 | 0.500000 | 0.002397 | 0.000468 | 2.79 | 12.89 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.77 | 0.091350 | 0.524000 | 1.45 | 0.524000 | 0.500000 | 0.004171 | 0.000224 | 1.45 | 12.89 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.89 | 0.087351 | 0.501000 | 1.45 | 0.501000 | 0.500000 | 0.004362 | 0.000226 | 1.45 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 7921.17 | 0.000069 | 184.75 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2731.93 | 0.000024 | 61.29 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3994.82 | 0.000035 | 93.17 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 4121.47 | 0.000036 | 96.13 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 53546.46 | 0.000468 | 1188.29 |
ROOM_1_FLR_3 HEATING COIL | 18242.27 | 0.000160 | 452.99 |
ROOM_2_FLR_3 HEATING COIL | 17823.04 | 0.000156 | 442.38 |
ROOM_3_MULT19_FLR_3 HEATING COIL | 131662.88 | 0.001152 | 3206.71 |
ROOM_4_MULT19_FLR_3 HEATING COIL | 118861.10 | 0.001040 | 2880.00 |
ROOM_5_FLR_3 HEATING COIL | 16853.07 | 0.000147 | 417.81 |
ROOM_6_FLR_3 HEATING COIL | 16434.28 | 0.000144 | 407.20 |
PTAC_3 HEATING COIL | 42386.55 | 0.000371 | 985.72 |
ROOM_1_FLR_6 HEATING COIL | 4917.19 | 0.000043 | 122.27 |
ROOM_2_FLR_6 HEATING COIL | 4794.68 | 0.000042 | 119.17 |
ROOM_3_MULT9_FLR_6 HEATING COIL | 24158.14 | 0.000211 | 597.31 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 25594.57 | 0.000224 | 558.63 |
DINING_FLR_6 VAV BOX REHEAT COIL | 25782.56 | 0.000226 | 563.53 |
PTAC_6 HEATING COIL | 19292.45 | 0.000169 | 468.15 |
VAV_FLR_1 HEATING COIL | 65381.84 | 0.000572 | 1035.86 |
VAV_FLR_6 HEATING COIL | 48440.59 | 0.000424 | 767.46 |
VAV_FLR_0 HEATING COIL | 44785.42 | 0.000392 | 2156.17 |
Design Size Maximum Air Flow Rate [m3/s] | |
LAUNDRY_FLR_1 DIRECT AIR | 3.84 |
CAFE_FLR_1 DIRECT AIR | 2.00 |
KITCHEN_FLR_6 DIRECT AIR | 2.64 |
Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | |
ROOM_1_FLR_3 | 1.16 | 1.16 | 1.16 | 0.061735 | 0.061735 | 0.061735 |
ROOM_2_FLR_3 | 1.13 | 1.13 | 1.13 | 0.061728 | 0.061728 | 0.061728 |
ROOM_3_MULT19_FLR_3 | 7.26 | 7.26 | 7.26 | 0.837072 | 0.837072 | 0.837072 |
ROOM_4_MULT19_FLR_3 | 6.32 | 6.32 | 6.32 | 0.837300 | 0.837300 | 0.837300 |
ROOM_5_FLR_3 | 1.06 | 1.06 | 1.06 | 0.061735 | 0.061735 | 0.061735 |
ROOM_6_FLR_3 | 1.03 | 1.03 | 1.03 | 0.061728 | 0.061728 | 0.061728 |
PTAC_3 | 1.75 | 1.75 | 1.75 | 0.474762 | 0.474762 | 0.474762 |
ROOM_1_FLR_6 | 0.316392 | 0.316392 | 0.316392 | 0.015434 | 0.015434 | 0.015434 |
ROOM_2_FLR_6 | 0.307414 | 0.307414 | 0.307414 | 0.015432 | 0.015432 | 0.015432 |
ROOM_3_MULT9_FLR_6 | 1.49 | 1.49 | 1.49 | 0.099154 | 0.099154 | 0.099154 |
PTAC_6 | 1.06 | 1.06 | 1.06 | 0.125616 | 0.125616 | 0.125616 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
ROOM_1_FLR_3 PTAC COOLING COIL | 1.16 | 20283.95 | 0.800335 |
ROOM_2_FLR_3 PTAC COOLING COIL | 1.13 | 19745.10 | 0.800372 |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 7.26 | 137546.58 | 0.798176 |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 6.32 | 126782.09 | 0.775348 |
ROOM_5_FLR_3 PTAC COOLING COIL | 1.06 | 18033.63 | 0.800423 |
ROOM_6_FLR_3 PTAC COOLING COIL | 1.03 | 17456.54 | 0.800540 |
PTAC_3 PTAC COOLING COIL | 1.75 | 39766.93 | 0.730391 |
ROOM_1_FLR_6 PTAC COOLING COIL | 0.316392 | 5480.14 | 0.800371 |
ROOM_2_FLR_6 PTAC COOLING COIL | 0.307414 | 5331.70 | 0.800906 |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 1.49 | 26825.30 | 0.800517 |
PTAC_6 PTAC COOLING COIL | 1.06 | 19823.33 | 0.800304 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3_PTAC_SUPPLY FAN | 1.16 |
ROOM_2_FLR_3_PTAC_SUPPLY FAN | 1.13 |
ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | 7.26 |
ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | 6.32 |
ROOM_5_FLR_3_PTAC_SUPPLY FAN | 1.06 |
ROOM_6_FLR_3_PTAC_SUPPLY FAN | 1.03 |
PTAC_3_PTAC_SUPPLY FAN | 1.75 |
ROOM_1_FLR_6_PTAC_SUPPLY FAN | 0.316392 |
ROOM_2_FLR_6_PTAC_SUPPLY FAN | 0.307414 |
ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | 1.49 |
PTAC_6_PTAC_SUPPLY FAN | 1.06 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_FLR_1 | 3.83 | 3.28 | 7.67 | 3.28 | 7.64 | 7.64 | 0.300000 | 0.428914 | 7.64 |
VAV_FLR_6 | 2.90 | 2.90 | 5.66 | 2.90 | 5.66 | 5.66 | 0.300000 | 0.512243 | 5.66 |
VAV_FLR_0 | 0.895000 | 0.895000 | 2.98 | 0.895000 | 2.98 | 2.98 | 1.00 | 0.300000 | 2.98 |
PSZ_LAUNDRY | 3.84 | 3.84 | 3.84 | 3.84 | 3.84 | 3.84 | 1.00 | 1.00 | 3.84 |
PSZ_CAFE | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 1.00 | 1.00 | 2.00 |
PSZ_KITCHEN | 2.64 | 2.64 | 2.64 | 2.64 | 2.64 | 2.64 | 1.00 | 1.00 | 2.64 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_FLR_1_OA_CONTROLLER | 7.64 | |
VAV_FLR_6_OA_CONTROLLER | 5.66 | |
VAV_FLR_0_OA_CONTROLLER | 2.98 | |
PSZ_LAUNDRY_OA_CONTROLLER | 3.84 | 0.000000 |
PSZ_CAFE_OA_CONTROLLER | 2.00 | 0.676389 |
PSZ_KITCHEN_OA_CONTROLLER | 2.64 | 0.367350 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
VAV_FLR_1 COOLING COIL | 7.64 | 189697.33 | 0.701083 | 2.55 | 63226.12 | 0.701083 |
VAV_FLR_6 COOLING COIL | 5.66 | 140544.40 | 0.701083 | 1.89 | 46843.45 | 0.701083 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_FLR_1 FAN | 7.64 |
VAV_FLR_6 FAN | 5.66 |
VAV_FLR_0 SZVAV FAN | 2.98 |
Maximum Actuated Flow [m3/s] | |
VAV_FLR_1_HEATC_CONTROLLER | 0.000572 |
VAV_FLR_6_HEATC_CONTROLLER | 0.000424 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | User-Specified Minimum Supply Air Temperature [C] | Design Size Maximum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | |
VAV_FLR_0_UNITARY_PACKAGE_DX | 2.98 | 2.98 | 2.98 | 0.895000 | 67740.84 | 72846.18 | 1.00 | 12.89 | 21.81 | 32.11 |
PSZ_LAUNDRY_UNITARY_PACKAGE_DX | 3.84 | 3.84 | 3.84 | 3.84 | 63638.29 | 51661.60 | 1.00 | 32.11 | ||
PSZ_CAFE_UNITARY_PACKAGE_DX | 2.00 | 2.00 | 2.00 | 2.00 | 49753.16 | 52855.23 | 1.00 | 32.11 | ||
PSZ_KITCHEN_UNITARY_PACKAGE_DX | 2.64 | 2.64 | 2.64 | 2.64 | 58528.91 | 50056.70 | 1.00 | 32.11 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
VAV_FLR_0 COOLING COIL | 2.98 | 1.49 | 1.99 | 67740.84 | 33870.42 | 0.730030 | 0.730030 |
PSZ_LAUNDRY COOLING COIL | 3.84 | 1.92 | 2.56 | 63638.29 | 31819.15 | 0.800660 | 0.800660 |
PSZ_CAFE COOLING COIL | 2.00 | 1.00 | 1.34 | 49753.16 | 24876.58 | 0.701080 | 0.701080 |
PSZ_KITCHEN COOLING COIL | 2.64 | 1.32 | 1.76 | 58528.91 | 29264.46 | 0.738850 | 0.738850 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | 3.84 | 6236.08 |
PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | 2.00 | 3329.91 |
PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | 2.64 | 4287.68 |
Design Size Nominal Capacity [W] | |
PSZ_LAUNDRY HEATING COIL | 51661.60 |
PSZ_CAFE HEATING COIL | 52855.23 |
PSZ_KITCHEN HEATING COIL | 50056.70 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.006104 | 0.732482 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.006104 | 1838.26 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 697726.50 | 697726.50 | 0.006104 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 6.92 | 4.22 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 6.92 | 4.23 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 30.00 | 18.31 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 12.69 | 7.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 60.57 | 36.97 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 60.57 | 36.97 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 57.04 | 30.28 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 53.08 | 32.40 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 11.068 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.448 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 16.146 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.906 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 16.146 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.906 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 16.146 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 21.526 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 8.611 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 11.301 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 15.069 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 20.449 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 13.993 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 22.063 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 15.069 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 82.889 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 15.069 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 82.889 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 12.917 | 516.346 | 2419.260 | 0.000 | 0.000 | 0.000 | 2948.522 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 21901.435 | 11.068 | 205.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21901.435 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1082.924 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1082.924 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1254.030 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1254.030 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 2651.846 | 16.146 | 999.942 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2651.846 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 815.983 | 8.611 | 399.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 815.983 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2846.047 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2846.047 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 18305.540 | 13.993 | 43.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18305.540 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 300.928 | 12.271 | 200.619 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 300.928 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 301.011 | 12.271 | 200.674 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 301.011 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2095.757 | 5.382 | 100.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2095.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 301.011 | 12.271 | 200.674 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 301.011 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4997.899 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4997.899 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4997.899 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4997.899 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1334.351 | 12.917 | 60.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1334.351 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2218.035 | 5.382 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2218.035 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 493.000 | 4.772 | 22.169 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 493.000 | 493.000 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 365.000 | 3.533 | 16.413 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 365.000 | 365.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 200.0 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | NONRES_EXT_WALL_MID | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_TOP | 23 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | RES_EXT_WALL_MID | 25 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | RES_EXT_WALL_TOP | 26 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5000E-02 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
13 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
14 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
15 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
19 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
20 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
21 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
23 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
24 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
25 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
26 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
27 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
28 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
31 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
36 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
37 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
38 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
39 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
40 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
42 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
44 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
46 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 200.00000 | 200.00000 | 200.00000 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
21 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
22 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
23 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
24 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
25 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
26 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
27 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
28 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
29 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
30 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
31 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
32 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
33 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
34 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
35 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
36 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
37 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
38 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
39 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
40 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
41 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
42 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
43 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
44 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
45 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
46 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
47 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
48 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
49 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
50 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
51 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
52 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
53 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
54 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
55 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
56 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
57 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
58 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
59 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
60 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
61 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
62 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
63 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
64 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
65 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
66 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
67 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
68 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
69 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
70 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
71 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
72 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
73 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
74 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
75 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
76 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
77 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
78 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
79 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
80 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
81 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
82 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
83 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
84 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
85 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
86 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
87 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
88 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
89 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
90 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
91 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
108 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
109 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
110 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
111 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
112 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
113 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
114 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
115 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
116 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
117 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
118 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
119 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
120 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
121 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
122 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
123 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | RESWINDOW_U_0.57_SHGC_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 8000.0 | 0.975 | 0.8950 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone RETAIL_1_FLR_1 | 1.2500 |
4 | Zone RETAIL_2_FLR_1 | 1.2500 |
5 | Zone MECH_FLR_1 | 1.2500 |
6 | Zone STORAGE_FLR_1 | 1.2500 |
7 | Zone LAUNDRY_FLR_1 | 1.2500 |
8 | Zone CAFE_FLR_1 | 1.2500 |
9 | Zone LOBBY_FLR_1 | 1.2500 |
10 | Zone ROOM_1_FLR_3 | 1.2500 |
11 | Zone ROOM_2_FLR_3 | 1.2500 |
12 | Zone ROOM_3_MULT19_FLR_3 | 1.2500 |
13 | Zone ROOM_4_MULT19_FLR_3 | 1.2500 |
14 | Zone ROOM_5_FLR_3 | 1.2500 |
15 | Zone ROOM_6_FLR_3 | 1.2500 |
16 | Zone CORRIDOR_FLR_3 | 1.2500 |
17 | Zone ROOM_1_FLR_6 | 1.2500 |
18 | Zone ROOM_2_FLR_6 | 1.2500 |
19 | Zone ROOM_3_MULT9_FLR_6 | 1.2500 |
20 | Zone BANQUET_FLR_6 | 1.2500 |
21 | Zone DINING_FLR_6 | 1.2500 |
22 | Zone KITCHEN_FLR_6 | 1.2500 |
23 | Zone CORRIDOR_FLR_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone RETAIL_1_FLR_1 | 1.1500 |
4 | Zone RETAIL_2_FLR_1 | 1.1500 |
5 | Zone MECH_FLR_1 | 1.1500 |
6 | Zone STORAGE_FLR_1 | 1.1500 |
7 | Zone LAUNDRY_FLR_1 | 1.1500 |
8 | Zone CAFE_FLR_1 | 1.1500 |
9 | Zone LOBBY_FLR_1 | 1.1500 |
10 | Zone ROOM_1_FLR_3 | 1.1500 |
11 | Zone ROOM_2_FLR_3 | 1.1500 |
12 | Zone ROOM_3_MULT19_FLR_3 | 1.1500 |
13 | Zone ROOM_4_MULT19_FLR_3 | 1.1500 |
14 | Zone ROOM_5_FLR_3 | 1.1500 |
15 | Zone ROOM_6_FLR_3 | 1.1500 |
16 | Zone CORRIDOR_FLR_3 | 1.1500 |
17 | Zone ROOM_1_FLR_6 | 1.1500 |
18 | Zone ROOM_2_FLR_6 | 1.1500 |
19 | Zone ROOM_3_MULT9_FLR_6 | 1.1500 |
20 | Zone BANQUET_FLR_6 | 1.1500 |
21 | Zone DINING_FLR_6 | 1.1500 |
22 | Zone KITCHEN_FLR_6 | 1.1500 |
23 | Zone CORRIDOR_FLR_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 35404.40546 | 40715.06628 | 2.59420 | 2.98333 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 28.53567 | 1.41132E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 2369.08436 | 2961.35546 | 0.17373 | 0.85446 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6020.83696 | 6923.96250 | 0.44123 | 0.50741 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3664.00171 | 4580.00214 | 0.26866 | 0.33583 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3901.92710 | 4487.21616 | 0.28594 | 0.32883 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.06400 | 1.41178E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1107.27354 | 1384.09193 | 8.11943E-002 | 0.10149 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 4449.04070 | 5116.39680 | 0.32597 | 0.37487 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 31.80400 | 1.41191E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1848.02017 | 2310.02521 | 0.13551 | 0.16939 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 2212.10999 | 2543.92649 | 0.16208 | 0.18639 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1906.32965 | 2382.91207 | 0.13979 | 0.17473 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45621.01991 | 52464.17290 | 3.34295 | 3.84439 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 30.52133 | 1.41168E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2464.53516 | 3080.66895 | 0.18071 | 0.22589 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 23755.08820 | 27318.35142 | 1.74223 | 2.00356 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 9570.41753 | 11963.02191 | 0.70175 | 0.87719 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 74406.74362 | 85567.75516 | 5.45418 | 6.27231 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.41193E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 20620.93689 | 25776.17112 | 1.51209 | 1.89399 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 13779.11221 | 15845.97904 | 1.00953 | 1.16096 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 31.45867 | 1.41185E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7013.80769 | 8767.25961 | 0.51432 | 0.64290 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 13414.49264 | 15426.66653 | 0.98282 | 1.13024 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7054.45915 | 8818.07393 | 0.51730 | 0.64663 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 86158.52074 | 99082.29885 | 6.31194 | 7.25873 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 39633.54715 | 49541.93393 | 2.90647 | 3.63309 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 75001.94085 | 86252.23198 | 5.49502 | 6.31927 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 40385.13739 | 50481.42174 | 2.96159 | 3.70199 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 12570.03318 | 14455.53816 | 0.92095 | 1.05909 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 29.07833 | 1.41142E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6932.61524 | 8665.76905 | 0.50837 | 0.63546 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 12205.78848 | 14036.65676 | 0.89426 | 1.02840 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.65900 | 1.41134E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6973.31297 | 8716.64122 | 0.51135 | 0.63919 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 20812.31591 | 23934.16329 | 1.52497 | 1.75371 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 32.10000 | 1.41196E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 11896.64185 | 14870.80231 | 0.87237 | 1.09047 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3755.17426 | 4318.45040 | 0.27512 | 0.31639 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 31.45867 | 1.41185E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2286.52828 | 2858.16035 | 0.16767 | 0.20959 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3648.61225 | 4195.90408 | 0.26732 | 0.30741 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.41183E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2300.05892 | 2875.07365 | 0.16866 | 0.21083 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 17656.62156 | 20305.11479 | 1.29363 | 1.48768 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 11008.07539 | 13760.09423 | 0.80724 | 1.00905 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 32792.43062 | 37711.29522 | 2.40568 | 2.76653 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.41196E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 8934.34456 | 11167.93071 | 0.65514 | 1.18780 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 34294.25537 | 39438.39367 | 2.51582 | 2.89319 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.41196E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 9086.05732 | 11357.57165 | 0.66626 | 1.18780 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31288.39442 | 35981.65359 | 2.29848 | 2.64325 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29.28800 | 1.41146E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3561.15864 | 4451.44830 | 0.26110 | 0.36735 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -10.70000 | 1.50390E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 12536.05169 | 14416.45945 | 0.91854 | 1.05632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 32.03833 | 1.41195E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 9556.43809 | 11945.54761 | 0.70076 | 0.87595 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | -10.70000 | 1.50390E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_FLR_1 | Cooling | Sensible | 130263.43 | 7.63911 | 7.63911 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_FLR_1 | Heating | Sensible | 76328.52 | 2.67543 | 2.67543 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | VAV_FLR_6 | Cooling | Sensible | 107043.04 | 5.65972 | 5.65972 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_FLR_6 | Heating | Sensible | 67774.33 | 2.37559 | 2.37559 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
5 | VAV_FLR_0 | Cooling | Sensible | 44774.24 | 2.98333 | 2.98333 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | VAV_FLR_0 | Heating | Sensible | 44240.67 | 0.85446 | 0.85446 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
7 | PSZ_LAUNDRY | Cooling | Sensible | 51652.90 | 3.84439 | 3.84439 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
8 | PSZ_LAUNDRY | Heating | Sensible | 3035.50 | 0.22589 | 0.22589 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
9 | PSZ_CAFE | Cooling | Sensible | 33279.51 | 2.00356 | 2.00356 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ_CAFE | Heating | Sensible | 37719.28 | 0.87719 | 0.87719 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
11 | PSZ_KITCHEN | Cooling | Sensible | 37729.26 | 2.64325 | 2.64325 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ_KITCHEN | Heating | Sensible | 19020.02 | 0.36735 | 0.36735 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 2.98333 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.50543 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.89500 |
5 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50741 |
6 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10072 |
7 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15222 |
9 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
10 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.78265E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.92979E-005 |
13 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33583 |
14 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7921.17056 |
17 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.92979E-005 |
18 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 184.75284 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.32883 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17998 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.41200 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13548 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47995 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11690E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.39001E-005 |
27 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13548 |
28 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2731.93373 |
31 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.39001E-005 |
32 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 61.28704 |
33 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.37487 |
34 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33386 |
35 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11246 |
37 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89030 |
38 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14119E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.49485E-005 |
41 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16939 |
42 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3994.82284 |
45 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.49485E-005 |
46 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 93.17120 |
47 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18639 |
48 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38740 |
49 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45700 |
50 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51797E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.83486E-004 |
54 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.60564E-005 |
55 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17473 |
56 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4121.47088 |
59 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.60564E-005 |
60 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 96.12885 |
61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LAUNDRY_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.84439 |
62 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CAFE_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.00356 |
63 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.27231 |
64 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15893 |
65 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44500 |
66 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.79118 |
67 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44500 |
68 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
69 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39733E-003 |
70 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.68448E-004 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.79118 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
74 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 53546.45875 |
75 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.68448E-004 |
76 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1188.28525 |
77 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16096 |
78 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16096 |
79 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.16096 |
80 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17350E-002 |
81 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17350E-002 |
82 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17350E-002 |
83 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 18242.26746 |
84 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59591E-004 |
85 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 452.99354 |
86 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.16096 |
87 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 20283.95398 |
88 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80034 |
89 | Fan:OnOff | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.16096 |
90 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13024 |
91 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13024 |
92 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13024 |
93 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17278E-002 |
94 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17278E-002 |
95 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17278E-002 |
96 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 17823.04463 |
97 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55924E-004 |
98 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 442.37887 |
99 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.13024 |
100 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 19745.10051 |
101 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80037 |
102 | Fan:OnOff | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.13024 |
103 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.25873 |
104 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 7.25873 |
105 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 7.25873 |
106 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.83707 |
107 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.83707 |
108 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.83707 |
109 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 131662.88461 |
110 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15184E-003 |
111 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3206.70886 |
112 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 7.25873 |
113 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 137546.58495 |
114 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79818 |
115 | Fan:OnOff | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 7.25873 |
116 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.31927 |
117 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 6.31927 |
118 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 6.31927 |
119 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.83730 |
120 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.83730 |
121 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.83730 |
122 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 118861.10097 |
123 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03985E-003 |
124 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2879.99852 |
125 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 6.31927 |
126 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 126782.09351 |
127 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.77535 |
128 | Fan:OnOff | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 6.31927 |
129 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05909 |
130 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05909 |
131 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05909 |
132 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17350E-002 |
133 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17350E-002 |
134 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17350E-002 |
135 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 16853.07204 |
136 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47438E-004 |
137 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 417.81248 |
138 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.05909 |
139 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 18033.63477 |
140 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80042 |
141 | Fan:OnOff | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.05909 |
142 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02840 |
143 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02840 |
144 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02840 |
145 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17278E-002 |
146 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17278E-002 |
147 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17278E-002 |
148 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 16434.28109 |
149 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43774E-004 |
150 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 407.20457 |
151 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.02840 |
152 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 17456.54135 |
153 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80054 |
154 | Fan:OnOff | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.02840 |
155 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.75371 |
156 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.75371 |
157 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.75371 |
158 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.47476 |
159 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.47476 |
160 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47476 |
161 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size Rated Capacity [W] | 42386.54753 |
162 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.70816E-004 |
163 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 985.71507 |
164 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.75371 |
165 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 39766.93099 |
166 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.73039 |
167 | Fan:OnOff | PTAC_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.75371 |
168 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.31639 |
169 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 0.31639 |
170 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 0.31639 |
171 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.54338E-002 |
172 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.54338E-002 |
173 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.54338E-002 |
174 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 4917.18654 |
175 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.30177E-005 |
176 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 122.27412 |
177 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.31639 |
178 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5480.13723 |
179 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80037 |
180 | Fan:OnOff | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.31639 |
181 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.30741 |
182 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 0.30741 |
183 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 0.30741 |
184 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.54319E-002 |
185 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.54319E-002 |
186 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.54319E-002 |
187 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 4794.68125 |
188 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.19460E-005 |
189 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 119.17328 |
190 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.30741 |
191 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5331.69596 |
192 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80091 |
193 | Fan:OnOff | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.30741 |
194 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.48768 |
195 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.48768 |
196 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.48768 |
197 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 9.91540E-002 |
198 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 9.91540E-002 |
199 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 9.91540E-002 |
200 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 24158.13915 |
201 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.11346E-004 |
202 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 597.31017 |
203 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.48768 |
204 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 26825.30161 |
205 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80052 |
206 | Fan:OnOff | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.48768 |
207 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.76653 |
208 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.13502E-002 |
209 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52400 |
210 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.44966 |
211 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52400 |
212 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.17076E-003 |
214 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.23912E-004 |
215 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.44966 |
216 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
217 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
218 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25594.57165 |
219 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.23912E-004 |
220 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 558.63121 |
221 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.89319 |
222 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.73509E-002 |
223 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50100 |
224 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.44949 |
225 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50100 |
226 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
227 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.36172E-003 |
228 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.25557E-004 |
229 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.44949 |
230 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
231 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
232 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25782.56368 |
233 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.25557E-004 |
234 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 563.53299 |
235 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.64325 |
236 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05632 |
237 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05632 |
238 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05632 |
239 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.12562 |
240 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.12562 |
241 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.12562 |
242 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size Rated Capacity [W] | 19292.44816 |
243 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.68779E-004 |
244 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 468.15318 |
245 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.05632 |
246 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 19823.33213 |
247 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80030 |
248 | Fan:OnOff | PTAC_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.05632 |
249 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.83491 |
250 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.27652 |
251 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.66982 |
252 | AirLoopHVAC | VAV_FLR_1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.27652 |
253 | AirLoopHVAC | VAV_FLR_1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.63911 |
254 | AirLoopHVAC | VAV_FLR_1 | Adjusted Main Design Air Flow Rate [m3/s] | 7.63911 |
255 | AirLoopHVAC | VAV_FLR_1 | User Heating Air Flow Ratio [] | 0.30000 |
256 | AirLoopHVAC | VAV_FLR_1 | Calculated Heating Air Flow Ratio [] | 0.42891 |
257 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.89915 |
258 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.89915 |
259 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.65972 |
260 | AirLoopHVAC | VAV_FLR_6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.89915 |
261 | AirLoopHVAC | VAV_FLR_6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.65972 |
262 | AirLoopHVAC | VAV_FLR_6 | Adjusted Main Design Air Flow Rate [m3/s] | 5.65972 |
263 | AirLoopHVAC | VAV_FLR_6 | User Heating Air Flow Ratio [] | 0.30000 |
264 | AirLoopHVAC | VAV_FLR_6 | Calculated Heating Air Flow Ratio [] | 0.51224 |
265 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89500 |
266 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89500 |
267 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.98333 |
268 | AirLoopHVAC | VAV_FLR_0 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89500 |
269 | AirLoopHVAC | VAV_FLR_0 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.98333 |
270 | AirLoopHVAC | VAV_FLR_0 | Adjusted Main Design Air Flow Rate [m3/s] | 2.98333 |
271 | AirLoopHVAC | VAV_FLR_0 | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | VAV_FLR_0 | Calculated Heating Air Flow Ratio [] | 0.30000 |
273 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.84439 |
274 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.84439 |
275 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.84439 |
276 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Heating Design Air Flow Rate [m3/s] | 3.84439 |
277 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.84439 |
278 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Main Design Air Flow Rate [m3/s] | 3.84439 |
279 | AirLoopHVAC | PSZ_LAUNDRY | User Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | PSZ_LAUNDRY | Calculated Heating Air Flow Ratio [] | 1.00000 |
281 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.00356 |
282 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.00356 |
283 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.00356 |
284 | AirLoopHVAC | PSZ_CAFE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.00356 |
285 | AirLoopHVAC | PSZ_CAFE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.00356 |
286 | AirLoopHVAC | PSZ_CAFE | Adjusted Main Design Air Flow Rate [m3/s] | 2.00356 |
287 | AirLoopHVAC | PSZ_CAFE | User Heating Air Flow Ratio [] | 1.00000 |
288 | AirLoopHVAC | PSZ_CAFE | Calculated Heating Air Flow Ratio [] | 1.00000 |
289 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.64325 |
290 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.64325 |
291 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.64325 |
292 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Heating Design Air Flow Rate [m3/s] | 2.64325 |
293 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.64325 |
294 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Main Design Air Flow Rate [m3/s] | 2.64325 |
295 | AirLoopHVAC | PSZ_KITCHEN | User Heating Air Flow Ratio [] | 1.00000 |
296 | AirLoopHVAC | PSZ_KITCHEN | Calculated Heating Air Flow Ratio [] | 1.00000 |
297 | AirLoopHVAC | VAV_FLR_1 | Design Supply Air Flow Rate [m3/s] | 7.63911 |
298 | AirLoopHVAC | VAV_FLR_6 | Design Supply Air Flow Rate [m3/s] | 5.65972 |
299 | AirLoopHVAC | VAV_FLR_0 | Design Supply Air Flow Rate [m3/s] | 2.98333 |
300 | AirLoopHVAC | PSZ_LAUNDRY | Design Supply Air Flow Rate [m3/s] | 3.84439 |
301 | AirLoopHVAC | PSZ_CAFE | Design Supply Air Flow Rate [m3/s] | 2.00356 |
302 | AirLoopHVAC | PSZ_KITCHEN | Design Supply Air Flow Rate [m3/s] | 2.64325 |
303 | Controller:OutdoorAir | VAV_FLR_1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.63911 |
304 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 7.63911 |
305 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 189697.33204 |
306 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
307 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.54612 |
308 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 63226.12077 |
309 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
310 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size Rated Capacity [W] | 65381.83631 |
311 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.71989E-004 |
312 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1035.86234 |
313 | Fan:VariableVolume | VAV_FLR_1 FAN | Design Size Maximum Flow Rate [m3/s] | 7.63911 |
314 | Controller:WaterCoil | VAV_FLR_1_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.71989E-004 |
315 | Controller:OutdoorAir | VAV_FLR_6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.65972 |
316 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.65972 |
317 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 140544.40119 |
318 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
319 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.88639 |
320 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 46843.44892 |
321 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
322 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 48440.59183 |
323 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.23779E-004 |
324 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 767.45757 |
325 | Fan:VariableVolume | VAV_FLR_6 FAN | Design Size Maximum Flow Rate [m3/s] | 5.65972 |
326 | Controller:WaterCoil | VAV_FLR_6_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.23779E-004 |
327 | Controller:OutdoorAir | VAV_FLR_0_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.98333 |
328 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.98333 |
329 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.98333 |
330 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.98333 |
331 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89500 |
332 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.98333 |
333 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.49167 |
334 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.98889 |
335 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 67740.84000 |
336 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 33870.42000 |
337 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73003 |
338 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73003 |
339 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 67740.84000 |
340 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size Rated Capacity [W] | 44785.42416 |
341 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.91802E-004 |
342 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2156.17358 |
343 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 72846.18168 |
344 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
345 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
346 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 21.80878 |
347 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
348 | Fan:VariableVolume | VAV_FLR_0 SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 2.98333 |
349 | Controller:OutdoorAir | PSZ_LAUNDRY_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.84439 |
350 | Controller:OutdoorAir | PSZ_LAUNDRY_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.00000 |
351 | Fan:SystemModel | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.84439 |
352 | Fan:SystemModel | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 6236.07604 |
353 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.84439 |
354 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.84439 |
355 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.84439 |
356 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.84439 |
357 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.84439 |
358 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.92219 |
359 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.56293 |
360 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 63638.29000 |
361 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31819.14500 |
362 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
363 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
364 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 63638.29000 |
365 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51661.60059 |
366 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
367 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
368 | Coil:Heating:Fuel | PSZ_LAUNDRY HEATING COIL | Design Size Nominal Capacity [W] | 51661.60059 |
369 | Controller:OutdoorAir | PSZ_CAFE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.00356 |
370 | Controller:OutdoorAir | PSZ_CAFE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.67639 |
371 | Fan:SystemModel | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.00356 |
372 | Fan:SystemModel | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3329.91090 |
373 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.00356 |
374 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.00356 |
375 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.00356 |
376 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.00356 |
377 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.00356 |
378 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00178 |
379 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33571 |
380 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49753.16000 |
381 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24876.58000 |
382 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
383 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
384 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49753.16000 |
385 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52855.22821 |
386 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
387 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
388 | Coil:Heating:Fuel | PSZ_CAFE HEATING COIL | Design Size Nominal Capacity [W] | 52855.22821 |
389 | Controller:OutdoorAir | PSZ_KITCHEN_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.64325 |
390 | Controller:OutdoorAir | PSZ_KITCHEN_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.36735 |
391 | Fan:SystemModel | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.64325 |
392 | Fan:SystemModel | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 4287.67547 |
393 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.64325 |
394 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.64325 |
395 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.64325 |
396 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.64325 |
397 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.64325 |
398 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.32162 |
399 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.76217 |
400 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 58528.91000 |
401 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 29264.45500 |
402 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.73885 |
403 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.73885 |
404 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 58528.91000 |
405 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50056.70019 |
406 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
407 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
408 | Coil:Heating:Fuel | PSZ_KITCHEN HEATING COIL | Design Size Nominal Capacity [W] | 50056.70019 |
409 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.10402E-003 |
410 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.73248 |
411 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.10402E-003 |
412 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1838.26150 |
413 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
414 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 697726.49782 |
415 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 697726.50000 |
416 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.10402E-003 |
417 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
418 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
419 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
420 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
421 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 7514.46 |
2 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2592.28 |
3 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3789.71 |
4 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 3909.85 |
5 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 50811.71 |
6 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | 19124.68 |
7 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | 18671.48 |
8 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | 133796.69 |
9 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | 119771.83 |
10 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | 17622.36 |
11 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | 17169.33 |
12 | Coil:Heating:Water | PTAC_3 HEATING COIL | 39961.68 |
13 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | 5166.54 |
14 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | 5034.18 |
15 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | 25153.66 |
16 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 24289.27 |
17 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 24467.51 |
18 | Coil:Heating:Water | PTAC_6 HEATING COIL | 19540.13 |
19 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | 46323.28 |
20 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | 34320.35 |
21 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | 68425.89 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | 19382.9 | 2.68 | 9.14 | 9.69 | 9.17 | 9.17 |
2 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | 18867.9 | 2.68 | 9.14 | 9.69 | 9.17 | 9.17 |
3 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 131911.3 | 2.71 | 9.26 | 9.83 | 9.29 | 9.35 |
4 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 121875.0 | 2.74 | 9.34 | 9.91 | 9.38 | 9.48 |
5 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | 17211.7 | 2.67 | 9.10 | 9.65 | 9.13 | 9.11 |
6 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | 16658.5 | 2.67 | 9.09 | 9.64 | 9.12 | 9.10 |
7 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | 38404.4 | 2.79 | 9.51 | 10.09 | 9.55 | 9.73 |
8 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | 5234.6 | 2.67 | 9.13 | 9.68 | 9.15 | 9.15 |
9 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | 5093.1 | 2.67 | 9.13 | 9.68 | 9.16 | 9.15 |
10 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 25670.6 | 2.69 | 9.19 | 9.75 | 9.22 | 9.24 |
11 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | 19003.3 | 2.71 | 9.25 | 9.81 | 9.28 | 9.33 |
12 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | 65391.2 | 10.72 | 10.72 | |||
13 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | 60625.4 | 10.16 | 10.16 | |||
14 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | 48172.5 | 10.86 | 10.86 | |||
15 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | 56448.1 | 10.68 | 10.68 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | N/A | N/A | 184111.26 | 628213.69 | 11.17 | 3.09 | 3.27 | 3.25 | 3.36 | 10.53 | 11.15 | 11.10 | 11.47 | 8.8313 | 6.9901 | 4.6799 | 2.0085 |
2 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | N/A | N/A | 136405.75 | 465435.73 | 11.17 | 3.09 | 3.27 | 3.25 | 3.36 | 10.53 | 11.15 | 11.10 | 11.47 | 6.5430 | 5.1789 | 3.4673 | 1.4880 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 200.000 | 200.000 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 6.92 | 11.15 | 6.92 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 4.22 | 4.22 | 4.22 | 180.00 | 90.00 | 3.02 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 6.92 | 11.15 | 6.92 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 4.23 | 4.23 | 4.23 | 0.00 | 90.00 | 3.02 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 90.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 90.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 4.04 | 6.50 | 4.04 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.47 | 2.47 | 2.47 | 0.00 | 90.00 | 1.76 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 4.04 | 6.50 | 4.04 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.46 | 2.46 | 2.46 | 180.00 | 90.00 | 1.76 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 12.69 | 20.44 | 12.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.75 | 7.75 | 7.75 | 180.00 | 90.00 | 5.53 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.57 | 97.55 | 60.57 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 36.97 | 36.97 | 36.97 | 0.00 | 90.00 | 26.40 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.57 | 97.55 | 60.57 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 36.97 | 36.97 | 36.97 | 0.00 | 90.00 | 26.40 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 16.08 | 21.37 | 16.08 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 32.31 | 52.03 | 32.31 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 19.72 | 19.72 | 19.72 | 90.00 | 90.00 | 14.08 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 9.81 | 15.79 | 9.81 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 5.99 | 5.99 | 5.99 | 0.00 | 90.00 | 4.27 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 32.31 | 52.03 | 32.31 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 19.72 | 19.72 | 19.72 | 180.00 | 90.00 | 14.08 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 3.7877361248E-005 | 8.0397102646E-005 | Pass | Pass | 1.4260497973E-002 | 3.6066146173E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2026505643E-002 | 3.3300405889E-002 | Pass | Pass | 0.6060690965 | 4.9256191476 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.0940857533E-003 | 1.2907475561E-002 | Pass | Pass | 3.2249285680E-002 | 6.3095635786E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5575713997E-003 | 5.2454792445E-003 | Pass | Pass | 0.3576840605 | 0.8260836897 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.0721696216E-004 | 5.6219593803E-004 | Pass | Pass | 1.9334298725E-002 | 2.0846917168E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1664573094E-006 | 5.8311176941E-006 | Pass | Pass | 2.2489009718E-002 | 6.4912256185E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8498055687E-006 | 8.6581828949E-006 | Pass | Pass | 0.1809342215 | 0.4560938610 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.5845830668E-002 | 3.5882557085E-002 | Pass | Pass | 2.2774874819E-002 | 5.7993862487E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 0.1058076378 | 0.3227839124 | Pass | Pass | 0.3908460418 | 2.6715377819 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2680722893E-002 | 0.3449328507 | Pass | Pass | 0.1033932019 | 0.2366989516 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.1414919310E-002 | 9.9689346500E-002 | Pass | Pass | 7.4976993233E-003 | 7.4302781992E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.1893982868E-002 | 0.1628232872 | Pass | Pass | 0.1609563886 | 0.7047862529 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.9887993880E-002 | 0.2721171323 | Pass | Pass | 0.1262780200 | 0.3737832986 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.9887875241E-002 | 0.2899507694 | Pass | Pass | 0.1287944943 | 0.5272389134 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.7529684522E-003 | 1.6799536143E-002 | Pass | Pass | 0.1513391342 | 0.4702816461 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.3299991504E-002 | 0.3557583602 | Pass | Pass | 0.1523912026 | 0.3915010390 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2700276379E-002 | 0.3668581370 | Pass | Pass | 0.1084711817 | 0.3512375400 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.9990566920E-002 | 0.2485934699 | Pass | Pass | 8.8895161185E-002 | 0.2848473171 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.4109158230E-002 | 7.0785192821E-002 | Pass | Pass | 1.8051510945E-002 | 4.8428051945E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.5159662564E-002 | 7.9315063439E-002 | Pass | Pass | 1.4991650245E-002 | 3.8310158544E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.7815473391E-002 | 8.1160392962E-002 | Pass | Pass | 2.4596925652E-002 | 4.2977011046E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.2061629195E-005 | 5.4466311137E-005 | Pass | Pass | 4.6911462635E-002 | 6.8797952553E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4019.86 | 106.05 | 1485.52 | 2220.01 | 7647.91 | 15479.37 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 55.74 | 34.61 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 104.06 | 64.62 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 55.74 | 34.61 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 104.05 | 64.61 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 847.14 | 526.04 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 847.37 | 526.16 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 104.06 | 64.62 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 55.74 | 34.61 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 55.74 | 34.61 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 104.05 | 64.61 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 70.60 | 43.85 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 26.01 | 16.14 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 26.02 | 16.16 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 70.60 | 43.85 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 13.94 | 8.65 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 26.01 | 16.15 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 13.94 | 8.65 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 26.01 | 16.15 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 183.96 | 114.24 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 97.55 | 60.57 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 97.55 | 60.57 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 21.37 | 16.08 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 52.03 | 32.31 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 13.94 | 8.65 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 17.65 | 10.96 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 15.79 | 9.81 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 52.03 | 32.31 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 3.241 | 0.391 | 0.431 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 3.241 | 0.391 | 0.431 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 3.241 | 0.391 | 0.431 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.391 | 0.431 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.391 | 0.431 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.391 | 0.431 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.391 | 0.431 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 4.22 | 0.00 | 0.00 | 4.22 | 321.10 | 3.241 | 0.391 | 0.431 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 4.23 | 0.00 | 0.00 | 4.23 | 321.20 | 3.241 | 0.391 | 0.431 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.391 | 0.431 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.391 | 0.431 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 3.241 | 0.391 | 0.431 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 3.241 | 0.391 | 0.431 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 6.69 | 0.00 | 0.00 | 6.69 | 26.76 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.47 | 0.00 | 0.00 | 2.47 | 9.86 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.46 | 0.00 | 0.00 | 2.46 | 9.86 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 6.69 | 0.00 | 0.00 | 6.69 | 26.76 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.391 | 0.431 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 9.86 | 3.241 | 0.391 | 0.431 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.391 | 0.431 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 9.86 | 0.00 | 0.00 | 9.86 | 9.86 | 3.241 | 0.391 | 0.431 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.57_SHGC_0.39 | 7.75 | 0.00 | 0.00 | 7.75 | 69.72 | 3.241 | 0.391 | 0.431 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 36.97 | 0.00 | 0.00 | 36.97 | 36.97 | 3.241 | 0.391 | 0.431 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 36.97 | 0.00 | 0.00 | 36.97 | 36.97 | 3.241 | 0.391 | 0.431 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.391 | 0.431 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 19.72 | 0.00 | 0.00 | 19.72 | 19.72 | 3.241 | 0.391 | 0.431 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 3.241 | 0.391 | 0.431 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 5.99 | 0.00 | 0.00 | 5.99 | 5.99 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_0.39 | 19.72 | 0.00 | 0.00 | 19.72 | 19.72 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1368.30 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
North Total or Average | 497.27 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 871.02 | 3.241 | 0.391 | 0.431 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 6.464 | 200.000 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.0679 | 1978.83 | 21901.44 | LightsWired | LTG_SCH_BASEMENT | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 241.03 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 16.1458 | 67.07 | 1082.92 | LightsWired | LTG_SCH_RETAIL | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 11.92 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 16.1458 | 77.67 | 1254.03 | LightsWired | LTG_SCH_RETAIL | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.80 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 16.1458 | 164.24 | 2651.85 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.18 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 8.6111 | 94.76 | 815.98 | LightsWired | LTG_SCH_STORAGE | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.98 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 15.0695 | 188.86 | 2846.05 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 31.32 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 13.9931 | 1308.19 | 18305.54 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 201.46 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 12.2708 | 156.09 | 1915.33 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 12.2708 | 156.07 | 1915.11 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 12.2708 | 1863.81 | 22870.56 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 297.14 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 12.2708 | 1864.32 | 22876.81 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 297.22 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 12.2708 | 156.09 | 1915.33 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 12.2708 | 156.07 | 1915.11 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 5.3819 | 1557.62 | 8383.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 92.26 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 12.2708 | 39.02 | 478.83 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.22 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 12.2708 | 39.02 | 478.78 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.22 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 12.2709 | 220.77 | 2709.10 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 35.20 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 15.0695 | 331.66 | 4997.90 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 55.00 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 15.0695 | 331.66 | 4997.90 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 55.00 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 12.9167 | 103.30 | 1334.35 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.68 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 5.3819 | 412.12 | 2218.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 24.41 |
Interior Lighting Total | 11.3147 | 11345.29 | 128367.98 | 764.46 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 20502.98 | AstronomicalClock | - | 83.64 | 83.64 | 321.91 | |
Exterior Lighting Total | 20502.98 | 321.91 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 697726.50 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 20283.95 | 16233.96 | 4049.99 | 0.80 | 3.20 | |||
ROOM_2_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19745.10 | 15803.43 | 3941.67 | 0.80 | 3.20 | |||
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 137546.58 | 109786.36 | 27760.23 | 0.80 | 3.20 | |||
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 126782.09 | 98300.25 | 28481.84 | 0.78 | 3.20 | |||
ROOM_5_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 18033.63 | 14434.54 | 3599.10 | 0.80 | 3.20 | |||
ROOM_6_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 17456.54 | 13974.65 | 3481.89 | 0.80 | 3.20 | |||
PTAC_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 39766.93 | 29045.42 | 10721.51 | 0.73 | 3.20 | |||
ROOM_1_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5480.14 | 4386.15 | 1093.99 | 0.80 | 3.20 | |||
ROOM_2_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5331.70 | 4270.19 | 1061.51 | 0.80 | 3.20 | |||
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 26825.30 | 21474.12 | 5351.18 | 0.80 | 3.20 | |||
PTAC_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19823.33 | 15864.69 | 3958.64 | 0.80 | 3.20 | |||
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 189697.33 | 132993.62 | 56703.72 | 0.70 | 3.50 | |||
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 140544.40 | 98533.32 | 42011.08 | 0.70 | 3.50 | |||
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 67740.84 | 49452.85 | 18287.99 | 0.73 | 3.40 | |||
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | 63638.29 | 50952.63 | 12685.66 | 0.80 | 3.40 | |||
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49753.16 | 34880.95 | 14872.21 | 0.70 | 3.40 | |||
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | 58528.91 | 43244.09 | 15284.82 | 0.74 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
ROOM_1_FLR_3 PTAC COOLING COIL | 19382.9 | 2.68 | 9.14 | 9.69 | 9.17 | 9.17 | |
ROOM_2_FLR_3 PTAC COOLING COIL | 18867.9 | 2.68 | 9.14 | 9.69 | 9.17 | 9.17 | |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 131911.3 | 2.71 | 9.26 | 9.83 | 9.29 | 9.35 | |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 121875.0 | 2.74 | 9.34 | 9.91 | 9.38 | 9.48 | |
ROOM_5_FLR_3 PTAC COOLING COIL | 17211.7 | 2.67 | 9.10 | 9.65 | 9.13 | 9.11 | |
ROOM_6_FLR_3 PTAC COOLING COIL | 16658.5 | 2.67 | 9.09 | 9.64 | 9.12 | 9.10 | |
PTAC_3 PTAC COOLING COIL | 38404.4 | 2.79 | 9.51 | 10.09 | 9.55 | 9.73 | |
ROOM_1_FLR_6 PTAC COOLING COIL | 5234.6 | 2.67 | 9.13 | 9.68 | 9.15 | 9.15 | |
ROOM_2_FLR_6 PTAC COOLING COIL | 5093.1 | 2.67 | 9.13 | 9.68 | 9.16 | 9.15 | |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 25670.6 | 2.69 | 9.19 | 9.75 | 9.22 | 9.24 | |
PTAC_6 PTAC COOLING COIL | 19003.3 | 2.71 | 9.25 | 9.81 | 9.28 | 9.33 | |
VAV_FLR_1 COOLING COIL | 184111.3 | 3.09 | 10.53 | N/A | N/A | 11.17 | |
VAV_FLR_6 COOLING COIL | 136405.7 | 3.09 | 10.53 | N/A | N/A | 11.17 | |
VAV_FLR_0 COOLING COIL | 65391.2 | 10.72 | 10.72 | ||||
PSZ_LAUNDRY COOLING COIL | 60625.4 | 10.16 | 10.16 | ||||
PSZ_CAFE COOLING COIL | 48172.5 | 10.86 | 10.86 | ||||
PSZ_KITCHEN COOLING COIL | 56448.1 | 10.68 | 10.68 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
ROOM_1_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_2_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_5_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_6_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PTAC_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_1_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_2_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PTAC_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7921.17 | 7514.46 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2731.93 | 2592.28 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3994.82 | 3789.71 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4121.47 | 3909.85 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 53546.46 | 50811.71 | - |
ROOM_1_FLR_3 HEATING COIL | Coil:Heating:Water | 18242.27 | 19124.68 | - |
ROOM_2_FLR_3 HEATING COIL | Coil:Heating:Water | 17823.04 | 18671.48 | - |
ROOM_3_MULT19_FLR_3 HEATING COIL | Coil:Heating:Water | 131662.88 | 133796.69 | - |
ROOM_4_MULT19_FLR_3 HEATING COIL | Coil:Heating:Water | 118861.10 | 119771.83 | - |
ROOM_5_FLR_3 HEATING COIL | Coil:Heating:Water | 16853.07 | 17622.36 | - |
ROOM_6_FLR_3 HEATING COIL | Coil:Heating:Water | 16434.28 | 17169.33 | - |
PTAC_3 HEATING COIL | Coil:Heating:Water | 42386.55 | 39961.68 | - |
ROOM_1_FLR_6 HEATING COIL | Coil:Heating:Water | 4917.19 | 5166.54 | - |
ROOM_2_FLR_6 HEATING COIL | Coil:Heating:Water | 4794.68 | 5034.18 | - |
ROOM_3_MULT9_FLR_6 HEATING COIL | Coil:Heating:Water | 24158.14 | 25153.66 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 25594.57 | 24289.27 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 25782.56 | 24467.51 | - |
PTAC_6 HEATING COIL | Coil:Heating:Water | 19292.45 | 19540.13 | - |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | 65381.84 | 46323.28 | - |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | 48440.59 | 34320.35 | - |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | 72846.18 | 68425.89 | - |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | 51661.60 | 0.80 | |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | 52855.23 | 0.80 | |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | 50056.70 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.16 | 739.38 | 636.87 | 1.00 | 1.47 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 |
ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.13 | 719.81 | 636.87 | 1.00 | 1.48 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 7.26 | 4622.83 | 636.87 | 1.00 | 1.21 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 6.32 | 4024.53 | 636.87 | 1.00 | 1.22 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.06 | 674.50 | 636.87 | 1.00 | 1.50 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.03 | 654.95 | 636.87 | 1.00 | 1.50 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 |
PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.75 | 1116.88 | 636.87 | 1.00 | 1.38 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.32 | 201.50 | 636.87 | 1.00 | 2.10 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 |
ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.31 | 195.78 | 636.87 | 1.00 | 2.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.49 | 947.45 | 636.87 | 1.00 | 1.41 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 1.89 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.06 | 672.74 | 636.87 | 1.00 | 1.50 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
VAV_FLR_1 FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.64 | 16789.09 | 2197.78 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
VAV_FLR_6 FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.66 | 12519.08 | 2211.96 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 0.60 | 1337.13 | 2.98 | 6692.57 | 2243.32 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 |
PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 3.84 | 6236.08 | 1622.12 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 2.00 | 3329.91 | 1662.00 | 1.00 | 1.22 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 2.64 | 4287.68 | 1622.12 | 1.00 | 1.22 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.006104 | 1838.26 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 0.80 | 0.98 | 0.90 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 184111.26 | 3.09 | 10.53 | 11.17 | 8.8313 | 3.27 | 11.15 | 6.9901 | 3.25 | 11.10 | 4.6799 | 3.36 | 11.47 | 2.0085 |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 136405.75 | 3.09 | 10.53 | 11.17 | 6.5430 | 3.27 | 11.15 | 5.1789 | 3.25 | 11.10 | 3.4673 | 3.36 | 11.47 | 1.4880 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 35404.41 | 40715.07 | 20.58 | 2.594 | 2.983 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 24.00 | 24.00 | 0.00918 | 28.54 | 0.01411 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6020.84 | 6923.96 | 103.23 | 0.441 | 0.507 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00901 | 31.85 | 0.01412 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3901.93 | 4487.22 | 57.77 | 0.286 | 0.329 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00928 | 31.06 | 0.01412 | 0.092 | 0.00 |
MECH_FLR_1 | 4449.04 | 5116.40 | 31.15 | 0.326 | 0.375 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00877 | 31.80 | 0.01412 | 0.000 | 0.00 |
STORAGE_FLR_1 | 2212.11 | 2543.93 | 26.85 | 0.162 | 0.186 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00887 | 32.10 | 0.01412 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45621.02 | 52464.17 | 672.28 | 3.343 | 3.844 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 24.00 | 24.00 | 0.00856 | 30.52 | 0.01412 | 0.000 | 0.00 |
CAFE_FLR_1 | 23755.09 | 27318.35 | 144.65 | 1.742 | 2.004 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 23.99 | 0.00989 | 31.79 | 0.01412 | 0.676 | 0.00 |
LOBBY_FLR_1 | 74406.74 | 85567.76 | 65.41 | 5.454 | 6.272 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00982 | 31.92 | 0.01412 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 13779.11 | 15845.98 | 406.08 | 1.010 | 1.161 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 21.11 | 21.11 | 0.00869 | 31.46 | 0.01412 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 13414.49 | 15426.67 | 395.38 | 0.983 | 1.130 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00869 | 31.26 | 0.01412 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 86158.52 | 99082.30 | 4040.24 | 6.312 | 7.259 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 21.11 | 21.11 | 0.00860 | 31.85 | 0.01412 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 75001.94 | 86252.23 | 3516.12 | 5.495 | 6.319 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 21.11 | 21.11 | 0.00886 | 32.10 | 0.01412 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 12570.03 | 14455.54 | 370.45 | 0.921 | 1.059 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00871 | 29.08 | 0.01411 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 12205.79 | 14036.66 | 359.75 | 0.894 | 1.028 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 21.11 | 21.11 | 0.00871 | 28.66 | 0.01411 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 20812.32 | 23934.16 | 61.46 | 1.525 | 1.754 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00949 | 32.10 | 0.01412 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3755.17 | 4318.45 | 110.67 | 0.275 | 0.316 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 21.11 | 21.11 | 0.00867 | 31.46 | 0.01412 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3648.61 | 4195.90 | 107.54 | 0.267 | 0.307 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00868 | 31.36 | 0.01412 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 17656.62 | 20305.11 | 827.75 | 1.294 | 1.488 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 21.11 | 21.11 | 0.00873 | 31.85 | 0.01412 | 0.099 | 0.00 |
BANQUET_FLR_6 | 32792.43 | 37711.30 | 113.71 | 2.406 | 2.767 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.01023 | 32.10 | 0.01412 | 1.188 | 0.00 |
DINING_FLR_6 | 34294.26 | 39438.39 | 118.91 | 2.516 | 2.893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.01015 | 32.10 | 0.01412 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31288.39 | 35981.65 | 348.31 | 2.298 | 2.643 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 23.97 | 0.00998 | 29.29 | 0.01411 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 12536.05 | 14416.46 | 34.98 | 0.919 | 1.056 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00896 | 32.04 | 0.01412 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 2369.08 | 2961.36 | 1.50 | 0.174 | 0.854 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3664.00 | 4580.00 | 68.29 | 0.269 | 0.336 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00775 | -10.70 | 0.00150 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1107.27 | 1384.09 | 17.82 | 0.081 | 0.101 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00768 | -10.70 | 0.00150 | 0.092 | 0.00 |
MECH_FLR_1 | 1848.02 | 2310.03 | 14.06 | 0.136 | 0.169 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00756 | -10.70 | 0.00150 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1906.33 | 2382.91 | 25.15 | 0.140 | 0.175 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00774 | -10.70 | 0.00150 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2464.54 | 3080.67 | 39.48 | 0.181 | 0.226 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00755 | -10.70 | 0.00150 | 0.000 | 0.00 |
CAFE_FLR_1 | 9570.42 | 11963.02 | 63.34 | 0.702 | 0.877 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00778 | -10.70 | 0.00150 | 0.676 | 0.00 |
LOBBY_FLR_1 | 20620.94 | 25776.17 | 19.70 | 1.512 | 1.894 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00772 | -10.70 | 0.00150 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 7013.81 | 8767.26 | 224.67 | 0.514 | 0.643 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00769 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7054.46 | 8818.07 | 226.00 | 0.517 | 0.647 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00770 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 39633.55 | 49541.93 | 2020.15 | 2.906 | 3.633 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00771 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 40385.14 | 50481.42 | 2057.90 | 2.962 | 3.702 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00772 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6932.62 | 8665.77 | 222.07 | 0.508 | 0.635 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00769 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6973.31 | 8716.64 | 223.40 | 0.511 | 0.639 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00769 | -10.70 | 0.00150 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 11896.64 | 14870.80 | 38.19 | 0.872 | 1.090 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00778 | -10.70 | 0.00150 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2286.53 | 2858.16 | 73.24 | 0.168 | 0.210 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00776 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2300.06 | 2875.07 | 73.69 | 0.169 | 0.211 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00776 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11008.08 | 13760.09 | 560.94 | 0.807 | 1.009 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -10.70 | 0.00150 | 0.099 | 0.00 |
BANQUET_FLR_6 | 8934.34 | 11167.93 | 33.67 | 0.655 | 1.188 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00785 | -10.70 | 0.00150 | 1.188 | 0.00 |
DINING_FLR_6 | 9086.06 | 11357.57 | 34.24 | 0.666 | 1.188 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00785 | -10.70 | 0.00150 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 3561.16 | 4451.45 | 43.09 | 0.261 | 0.367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00749 | -10.70 | 0.00150 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9556.44 | 11945.55 | 28.99 | 0.701 | 0.876 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00788 | -10.70 | 0.00150 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_FLR_1 | 7.64 | 7.64 | 2.68 | 2.68 | 7.6391 | 3.2765 | 7.6391 | 0.4289 | 0.3000 |
VAV_FLR_6 | 5.66 | 5.66 | 2.38 | 2.38 | 5.6597 | 2.8992 | 5.6597 | 0.5122 | 0.3000 |
VAV_FLR_0 | 2.98 | 2.98 | 0.85 | 0.85 | 2.9833 | 0.8950 | 2.9833 | 0.3000 | 1.0000 |
PSZ_LAUNDRY | 3.84 | 3.84 | 0.23 | 0.23 | 3.8444 | 3.8444 | 3.8444 | 1.0000 | 1.0000 |
PSZ_CAFE | 2.00 | 2.00 | 0.88 | 0.88 | 2.0036 | 2.0036 | 2.0036 | 1.0000 | 1.0000 |
PSZ_KITCHEN | 2.64 | 2.64 | 0.37 | 0.37 | 2.6432 | 2.6432 | 2.6432 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 7921.171 | 7921.171 | 0.335825 | 0.00006930 | 184.753 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7921.17 | 7921.17 | 0.335825 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00774627 | 50.0764 | 4580.00 | 0.00 | 7521.92 | 7521.92 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2731.934 | 2731.934 | 0.135480 | 0.00002390 | 61.287 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2731.93 | 2731.93 | 0.135480 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00767940 | 49.6476 | 1384.09 | 0.00 | 2594.58 | 2594.58 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3994.823 | 3994.823 | 0.169389 | 0.00003495 | 93.171 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3994.82 | 3994.82 | 0.169389 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00755514 | 48.8540 | 2310.03 | 0.00 | 3793.47 | 3793.47 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 4121.471 | 4121.471 | 0.174734 | 0.00003606 | 96.129 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4121.47 | 4121.47 | 0.174734 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00774345 | 50.0567 | 2382.91 | 0.00 | 3913.74 | 3913.74 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 53546.459 | 53546.459 | 2.791178 | 0.00046845 | 1188.285 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 53546.46 | 53546.46 | 2.791178 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00771661 | 49.8853 | 25776.17 | 0.00 | 50855.09 | 50855.09 |
ROOM_1_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | 18242.267 | 18242.267 | 1.160962 | 0.00015959 | 452.994 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 18242.27 | 18242.27 | 1.160962 | 19.42 | 13.65 | 0.00736561 | 32.22 | 18.76 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 5.3176 | 21.11 | 0.00769482 | 49.4103 | 8767.26 | 0.00 | 19136.92 | 19136.92 |
ROOM_1_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | 20283.954 | 16233.960 | 1.160962 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | unknown | 7/21 16:20:00 | 18701.24 | 16728.76 | 1.160962 | 21.66 | 15.96 | 0.00897683 | 9.48 | 9.48 | 0.00850000 | 31.46 | 0.01411849 | 22.95 | 5.3176 | 21.11 | 0.00868806 | 55.7006 | 15845.98 | 0.00 | 20293.88 | 16219.20 |
ROOM_2_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | 17823.045 | 17823.045 | 1.130241 | 0.00015592 | 442.379 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 17823.04 | 17823.04 | 1.130241 | 19.37 | 13.62 | 0.00735831 | 32.22 | 18.76 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 5.4615 | 21.11 | 0.00769651 | 49.4210 | 8818.07 | 0.00 | 18683.42 | 18683.42 |
ROOM_2_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | 19745.101 | 15803.432 | 1.130241 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 18254.50 | 16284.03 | 1.130241 | 21.66 | 15.97 | 0.00898955 | 9.48 | 9.48 | 0.00850000 | 31.26 | 0.01411813 | 22.90 | 5.4615 | 21.11 | 0.00869327 | 55.7335 | 15426.67 | 0.00 | 19754.77 | 15789.05 |
ROOM_3_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | 131662.885 | 131662.885 | 7.258731 | 0.00115184 | 3206.709 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 131662.88 | 131662.88 | 7.258731 | 17.44 | 12.50 | 0.00699686 | 32.22 | 18.76 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 11.5319 | 21.11 | 0.00771288 | 49.5230 | 49541.93 | 0.00 | 133876.25 | 133876.25 |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | 137546.585 | 109786.357 | 7.258731 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | 7/21 13:20:00 | 128254.39 | 109586.07 | 7.258731 | 22.35 | 16.43 | 0.00923571 | 9.48 | 9.48 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 11.5319 | 21.11 | 0.00859914 | 55.1353 | 99082.30 | 0.00 | 137613.91 | 109681.00 |
ROOM_4_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | 118861.101 | 118861.101 | 6.319274 | 0.00103985 | 2879.999 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 118861.10 | 118861.10 | 6.319274 | 16.90 | 12.18 | 0.00689456 | 32.22 | 18.76 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 13.2499 | 21.11 | 0.00771791 | 49.5549 | 50481.42 | 0.00 | 119841.02 | 119841.02 |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | 126782.094 | 98300.251 | 6.319274 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | unknown | 7/21 14:50:00 | 119307.52 | 96147.88 | 6.319274 | 22.57 | 16.78 | 0.00956104 | 9.48 | 9.48 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 13.2499 | 21.11 | 0.00886477 | 56.8174 | 86252.23 | 0.00 | 126844.15 | 98234.75 |
ROOM_5_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | 16853.072 | 16853.072 | 1.059092 | 0.00014744 | 417.812 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16853.07 | 16853.07 | 1.059092 | 19.26 | 13.55 | 0.00733074 | 32.22 | 18.76 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 5.8291 | 21.11 | 0.00769141 | 49.3887 | 8665.77 | 0.00 | 17633.58 | 17633.58 |
ROOM_5_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | 18033.635 | 14434.536 | 1.059092 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 17098.39 | 15128.22 | 1.059092 | 21.57 | 15.97 | 0.00902220 | 9.48 | 9.48 | 0.00850000 | 29.08 | 0.01411420 | 22.28 | 5.8291 | 21.11 | 0.00870701 | 55.8204 | 14455.54 | 0.00 | 18042.46 | 14422.77 |
ROOM_6_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | 16434.281 | 16434.281 | 1.028403 | 0.00014377 | 407.205 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16434.28 | 16434.28 | 1.028403 | 19.20 | 13.52 | 0.00732165 | 32.22 | 18.76 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 6.0023 | 21.11 | 0.00769315 | 49.3997 | 8716.64 | 0.00 | 17180.25 | 17180.25 |
ROOM_6_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | 17456.541 | 13974.653 | 1.028403 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | 7/21 09:30:00 | 16635.95 | 14667.90 | 1.028403 | 21.56 | 15.98 | 0.00903740 | 9.48 | 9.48 | 0.00850000 | 28.66 | 0.01411345 | 22.16 | 6.0023 | 21.11 | 0.00871326 | 55.8600 | 14036.66 | 0.00 | 17465.09 | 13963.11 |
PTAC_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | 42386.548 | 42386.548 | 1.753713 | 0.00037082 | 985.715 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 42386.55 | 42386.55 | 1.753713 | 12.42 | 9.39 | 0.00608055 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 27.0718 | 21.00 | 0.00777946 | 50.2859 | 14870.80 | 0.00 | 39976.82 | 39976.82 |
PTAC_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | 39766.931 | 29045.420 | 1.753713 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 40339.91 | 29143.81 | 1.753713 | 26.19 | 18.96 | 0.01074536 | 12.37 | 11.92 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 27.0718 | 24.00 | 0.00949279 | 50.9999 | 23934.16 | 0.00 | 39786.40 | 29034.89 |
ROOM_1_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | 4917.187 | 4917.187 | 0.316392 | 0.00004302 | 122.274 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4917.19 | 4917.19 | 0.316392 | 19.56 | 13.79 | 0.00745799 | 32.22 | 18.76 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 4.8780 | 21.11 | 0.00776332 | 49.8446 | 2858.16 | 0.00 | 5169.94 | 5169.94 |
ROOM_1_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | 5480.137 | 4386.146 | 0.316392 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | unknown | 7/21 16:20:00 | 5044.08 | 4548.47 | 0.316392 | 21.61 | 15.91 | 0.00893866 | 9.48 | 9.48 | 0.00850000 | 31.46 | 0.01411849 | 22.95 | 4.8780 | 21.11 | 0.00867303 | 55.6055 | 4318.45 | 0.00 | 5482.82 | 4382.40 |
ROOM_2_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | 4794.681 | 4794.681 | 0.307414 | 0.00004195 | 119.173 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4794.68 | 4794.68 | 0.307414 | 19.51 | 13.77 | 0.00745040 | 32.22 | 18.76 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 5.0199 | 21.11 | 0.00776468 | 49.8532 | 2875.07 | 0.00 | 5037.48 | 5037.48 |
ROOM_2_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | 5331.696 | 4270.186 | 0.307414 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 4915.50 | 4420.93 | 0.307414 | 21.62 | 15.92 | 0.00895081 | 9.48 | 9.48 | 0.00850000 | 31.36 | 0.01411830 | 22.93 | 5.0199 | 21.11 | 0.00867770 | 55.6350 | 4195.90 | 0.00 | 5334.31 | 4266.39 |
ROOM_3_MULT9_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | 24158.139 | 24158.139 | 1.487678 | 0.00021135 | 597.310 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 24158.14 | 24158.14 | 1.487678 | 18.99 | 13.47 | 0.00735542 | 32.22 | 18.76 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 6.6650 | 21.11 | 0.00777327 | 49.9070 | 13760.09 | 0.00 | 25169.98 | 25169.98 |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | 26825.302 | 21474.120 | 1.487678 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | 7/21 13:20:00 | 24749.43 | 21641.43 | 1.487678 | 21.83 | 16.12 | 0.00909025 | 9.48 | 9.48 | 0.00850000 | 31.85 | 0.01411920 | 23.06 | 6.6650 | 21.11 | 0.00873114 | 55.9733 | 20305.11 | 0.00 | 26838.43 | 21454.77 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 25594.572 | 25594.572 | 1.449662 | 0.00022391 | 558.631 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 25594.57 | 25594.57 | 1.449662 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00785005 | 50.7371 | 11167.93 | 0.00 | 24308.86 | 24308.86 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 25782.564 | 25782.564 | 1.449490 | 0.00022556 | 563.533 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 25782.56 | 25782.56 | 1.449490 | 12.89 | 11.63 | 0.00800000 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00785249 | 50.7527 | 11357.57 | 0.00 | 24487.34 | 24487.34 |
PTAC_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | 19292.448 | 19292.448 | 1.056323 | 0.00016878 | 468.153 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 19292.45 | 19292.45 | 1.056323 | 17.23 | 12.54 | 0.00711882 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 11.8918 | 21.00 | 0.00787665 | 50.9065 | 11945.55 | 0.00 | 19552.38 | 19552.38 |
PTAC_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | 19823.332 | 15864.690 | 1.056323 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 19210.38 | 15996.63 | 1.056323 | 24.95 | 17.62 | 0.00957570 | 12.37 | 11.92 | 0.00850000 | 32.04 | 0.01411953 | 23.12 | 11.8918 | 24.00 | 0.00896243 | 48.1909 | 14416.46 | 0.00 | 19833.04 | 15855.04 |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_FLR_1 | 189697.332 | 132993.616 | 7.639112 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 194240.16 | 133223.91 | 7.639112 | 27.00 | 19.66 | 0.01132347 | 11.11 | 11.11 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 37.0501 | 23.99 | 0.00967545 | 51.9781 | 90547.02 | 0.00 | 190245.98 | 133131.62 |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_1 | 65381.836 | 65381.836 | 2.291733 | 0.00057199 | 1035.862 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 65381.84 | 65381.84 | 2.291733 | -10.70 | -10.70 | 0.00150390 | 12.89 | 11.63 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 123.5004 | 21.00 | 0.00771044 | 49.8461 | 29146.56 | 0.00 | 56004.75 | 56004.75 |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_FLR_6 | 140544.401 | 98533.321 | 5.659723 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 147520.94 | 93681.14 | 5.659723 | 28.53 | 20.92 | 0.01238962 | 11.10 | 11.10 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 55.9656 | 23.99 | 0.01019084 | 54.7334 | 67086.69 | 0.00 | 140950.89 | 98635.57 |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_6 | 48440.592 | 48440.592 | 1.697917 | 0.00042378 | 767.458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 48440.59 | 48440.59 | 1.697917 | -10.70 | -10.70 | 0.00150390 | 12.89 | 11.63 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 186.5521 | 21.00 | 0.00785127 | 50.7449 | 18020.19 | 0.00 | 41493.23 | 41493.23 |
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | VAV_FLR_0 | 67740.840 | 49452.845 | 2.983330 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | 33870.42 | 24531.61 | 1.988887 | 25.30 | 18.55 | 0.01059016 | 11.07 | 11.07 | 0.00850000 | 28.54 | 0.01411323 | 22.13 | 42.9617 | 24.00 | 0.00917661 | 49.3264 | 35381.27 | 0.00 | -999.00 | -999.00 |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_0 | 72846.182 | 72846.182 | 2.983335 | 0.00039180 | 2156.174 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 72846.18 | 72846.18 | 2.983335 | 11.92 | 9.23 | 0.00613944 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 28.6411 | 21.00 | 0.00799965 | 51.6906 | 2367.04 | 0.00 | 68452.02 | 68452.02 |
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_LAUNDRY | 63638.290 | 50952.633 | 3.844390 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 31819.15 | 31436.59 | 2.562927 | 24.00 | 16.43 | 0.00856054 | 11.57 | 11.57 | 0.00850000 | 30.52 | 0.01411680 | 22.69 | 0.0000 | 24.00 | 0.00856054 | 46.0611 | 45621.02 | 0.00 | -999.00 | -999.00 |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_LAUNDRY | 51661.601 | 51661.601 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 51661.60 | 51661.60 | 3.844389 | 21.00 | 14.43 | 0.00754524 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00754524 | 48.7927 | 2464.54 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_CAFE | 49753.160 | 34880.945 | 2.003560 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24876.58 | 16938.92 | 1.335707 | 26.62 | 19.54 | 0.01131881 | 11.54 | 11.54 | 0.00850000 | 31.79 | 0.01411909 | 23.05 | 50.6391 | 23.99 | 0.00989654 | 53.1680 | 23714.68 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_CAFE | 52855.228 | 52855.228 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 52855.23 | 52855.23 | 2.003560 | 10.30 | 7.94 | 0.00566386 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 33.7594 | 21.00 | 0.00778397 | 50.3166 | 9570.42 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_KITCHEN | 58528.910 | 43244.085 | 2.643250 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 29264.46 | 21022.54 | 1.762167 | 24.69 | 18.32 | 0.01055813 | 11.57 | 11.57 | 0.00850000 | 29.29 | 0.01411458 | 22.34 | 20.8465 | 23.97 | 0.01005623 | 54.0699 | 31215.81 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_KITCHEN | 50056.700 | 50056.700 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 50056.70 | 50056.70 | 2.643248 | 16.45 | 11.75 | 0.00665655 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 13.8977 | 21.00 | 0.00746192 | 48.2613 | 2529.38 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7921.171 | 7921.171 | 0.335825 | 0.00006930 | 184.753 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 1.1129 | 1.135283 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7921.17 | 7921.17 | 1.0000 | 0.40419755 | 0.335825 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.06929079 | 60.00 | 32.22 | 27.78 | 0.000 | 7921.17 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00774627 | 21.00 | 0.00774627 | 50.0764 | 4580.00 | 0.00 | 7521.92 | 7521.92 | 0.40419755 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55544.2 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2731.934 | 2731.934 | 0.135480 | 0.00002390 | 61.287 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 0.3838 | 0.391548 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2731.93 | 2731.93 | 1.0000 | 0.16306299 | 0.135480 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.02389771 | 60.00 | 32.22 | 27.78 | 0.000 | 2731.93 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00767940 | 21.00 | 0.00767940 | 49.6476 | 1384.09 | 0.00 | 2594.58 | 2594.58 | 0.16306299 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.20 | 18.76 | 0.00800000 | 52846.2 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3994.823 | 3994.823 | 0.169389 | 0.00003495 | 93.171 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 0.5613 | 0.572549 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 3994.82 | 3994.82 | 1.0000 | 0.20387582 | 0.169389 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.03494489 | 60.00 | 32.22 | 27.78 | 0.000 | 3994.82 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00755514 | 21.00 | 0.00755514 | 48.8540 | 2310.03 | 0.00 | 3793.47 | 3793.47 | 0.20387582 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55541.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4121.471 | 4121.471 | 0.174734 | 0.00003606 | 96.129 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 0.5790 | 0.590700 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4121.47 | 4121.47 | 1.0000 | 0.21030882 | 0.174734 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.03605275 | 60.00 | 32.22 | 27.78 | 0.000 | 4121.47 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00774345 | 21.00 | 0.00774345 | 50.0567 | 2382.91 | 0.00 | 3913.74 | 3913.74 | 0.21030882 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55544.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 53546.459 | 53546.459 | 2.791178 | 0.00046845 | 1188.285 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 7.5230 | 7.674420 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 53546.46 | 53546.46 | 1.0000 | 3.35944814 | 2.791178 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.46839999 | 60.00 | 32.22 | 27.78 | 0.000 | 53546.46 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00771661 | 21.00 | 0.00771661 | 49.8853 | 25776.17 | 0.00 | 50855.09 | 50855.09 | 3.35944814 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 31.45 | 18.52 | 0.00800000 | 52072.7 | |
ROOM_1_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18242.267 | 18242.267 | 1.160962 | 0.00015959 | 452.994 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.160962 | 1.39732763 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 2.5629 | 2.614530 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 18242.27 | 18242.27 | 1.0000 | 1.39732763 | 1.160962 | 19.42 | 13.65 | 0.00736561 | 38199.2 | 32.22 | 18.76 | 0.00800000 | 52863.7 | 0.15957503 | 60.00 | 32.22 | 27.78 | 0.000 | 18242.27 | -10.70 | 0.00150390 | -10.70 | 0.06173502 | 5.3176 | 21.11 | 0.00769482 | 21.11 | 0.00769482 | 49.4103 | 8767.26 | 0.00 | 19136.92 | 19136.92 | 1.39732763 | 16.60 | 12.53 | 0.00736561 | 35328.6 | 30.05 | 17.53 | 0.00736561 | 49024.0 | |
ROOM_1_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 20283.954 | 16233.960 | 1.160962 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5275 | 1004.8586 | 1.2036 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.160962 | 1.39732763 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | unknown | unknown | unknown | 7/21 16:20:00 | Sensible | 18701.24 | 16728.76 | 0.9220 | 1.39732763 | 1.160962 | 21.66 | 15.96 | 0.00897683 | 44576.9 | 9.48 | 9.48 | 0.00850000 | 30934.6 | -999.0 | -999.00 | -999.00 | -999.00 | 739.376 | 17961.87 | 31.46 | 0.01411849 | 22.95 | 0.06173502 | 5.3176 | 21.11 | 0.00868806 | 21.11 | 0.00868806 | 55.7006 | 15845.98 | 0.00 | 20293.88 | 16219.20 | 1.34214375 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.86 | 14.35 | 0.00999433 | 40201.9 | |
ROOM_2_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17823.045 | 17823.045 | 1.130241 | 0.00015592 | 442.379 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.130241 | 1.36035230 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 2.5041 | 2.554446 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 17823.04 | 17823.04 | 1.0000 | 1.36035230 | 1.130241 | 19.37 | 13.62 | 0.00735831 | 38134.0 | 32.22 | 18.76 | 0.00800000 | 52863.7 | 0.15590786 | 60.00 | 32.22 | 27.78 | 0.000 | 17823.04 | -10.70 | 0.00150390 | -10.70 | 0.06172779 | 5.4615 | 21.11 | 0.00769651 | 21.11 | 0.00769651 | 49.4210 | 8818.07 | 0.00 | 18683.42 | 18683.42 | 1.36035230 | 16.60 | 12.52 | 0.00735831 | 35310.1 | 30.08 | 17.54 | 0.00735831 | 49044.3 | |
ROOM_2_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 19745.101 | 15803.432 | 1.130241 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5511 | 1004.8586 | 1.2036 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.130241 | 1.36035230 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 18254.50 | 16284.03 | 0.9245 | 1.36035230 | 1.130241 | 21.66 | 15.97 | 0.00898955 | 44613.4 | 9.48 | 9.48 | 0.00850000 | 30934.6 | -999.0 | -999.00 | -999.00 | -999.00 | 719.811 | 17534.69 | 31.26 | 0.01411813 | 22.90 | 0.06172779 | 5.4615 | 21.11 | 0.00869327 | 21.11 | 0.00869327 | 55.7335 | 15426.67 | 0.00 | 19754.77 | 15789.05 | 1.30662867 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.86 | 14.35 | 0.00999468 | 40203.5 | |
ROOM_3_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 131662.885 | 131662.885 | 7.258731 | 0.00115184 | 3206.709 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 7.258731 | 8.73657198 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 18.4980 | 18.870272 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 131662.88 | 131662.88 | 1.0000 | 8.73657198 | 7.258731 | 17.44 | 12.50 | 0.00699686 | 35252.1 | 32.22 | 18.76 | 0.00800000 | 52863.7 | 1.15172685 | 60.00 | 32.22 | 27.78 | 0.000 | 131662.88 | -10.70 | 0.00150390 | -10.70 | 0.83707151 | 11.5319 | 21.11 | 0.00771288 | 21.11 | 0.00771288 | 49.5230 | 49541.93 | 0.00 | 133876.25 | 133876.25 | 8.73657198 | 16.60 | 12.16 | 0.00699686 | 34395.0 | 31.65 | 17.77 | 0.00699686 | 49718.6 | |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 137546.585 | 109786.357 | 7.258731 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0087 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 7.258731 | 8.73657198 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | unknown | unknown | 7/21 13:20:00 | Sensible | 128254.39 | 109586.07 | 0.9324 | 8.73657198 | 7.258731 | 22.35 | 16.43 | 0.00923571 | 45939.3 | 9.48 | 9.48 | 0.00850000 | 30934.9 | -999.0 | -999.00 | -999.00 | -999.00 | 4622.834 | 123631.56 | 31.85 | 0.01411920 | 23.06 | 0.83707151 | 11.5319 | 21.11 | 0.00859914 | 21.11 | 0.00859914 | 55.1353 | 99082.30 | 0.00 | 137613.91 | 109681.00 | 8.39154343 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.89 | 13.87 | 0.00987955 | 38923.3 | |
ROOM_4_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 118861.101 | 118861.101 | 6.319274 | 0.00103985 | 2879.999 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 6.319274 | 7.60584679 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 16.6994 | 17.035486 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 118861.10 | 118861.10 | 1.0000 | 7.60584679 | 6.319274 | 16.90 | 12.18 | 0.00689456 | 34436.8 | 32.22 | 18.76 | 0.00800000 | 52863.7 | 1.03974269 | 60.00 | 32.22 | 27.78 | 0.000 | 118861.10 | -10.70 | 0.00150390 | -10.70 | 0.83730041 | 13.2499 | 21.11 | 0.00771791 | 21.11 | 0.00771791 | 49.5549 | 50481.42 | 0.00 | 119841.02 | 119841.02 | 7.60584679 | 16.60 | 12.06 | 0.00689456 | 34136.0 | 32.08 | 17.83 | 0.00689456 | 49892.4 | |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 126782.094 | 98300.251 | 6.319274 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6135 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 6.319274 | 7.60584679 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | unknown | unknown | unknown | 7/21 14:50:00 | Sensible | 119307.52 | 96147.88 | 0.9410 | 7.60584679 | 6.319274 | 22.57 | 16.78 | 0.00956104 | 46987.9 | 9.48 | 9.48 | 0.00850000 | 30935.2 | -999.0 | -999.00 | -999.00 | -999.00 | 4024.527 | 115282.99 | 32.10 | 0.01411964 | 23.13 | 0.83730041 | 13.2499 | 21.11 | 0.00886477 | 21.11 | 0.00886477 | 56.8174 | 86252.23 | 0.00 | 126844.15 | 98234.75 | 7.30547334 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.52 | 13.51 | 0.00964922 | 37959.5 | |
ROOM_5_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16853.072 | 16853.072 | 1.059092 | 0.00014744 | 417.812 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.059092 | 1.27471816 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 2.3678 | 2.415427 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 16853.07 | 16853.07 | 1.0000 | 1.27471816 | 1.059092 | 19.26 | 13.55 | 0.00733074 | 37945.0 | 32.22 | 18.76 | 0.00800000 | 52863.7 | 0.14742299 | 60.00 | 32.22 | 27.78 | 0.000 | 16853.07 | -10.70 | 0.00150390 | -10.70 | 0.06173502 | 5.8291 | 21.11 | 0.00769141 | 21.11 | 0.00769141 | 49.3887 | 8665.77 | 0.00 | 17633.58 | 17633.58 | 1.27471816 | 16.60 | 12.50 | 0.00733074 | 35240.3 | 30.18 | 17.55 | 0.00733074 | 49073.6 | |
ROOM_5_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 18033.635 | 14434.536 | 1.059092 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6118 | 1004.8586 | 1.2036 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.059092 | 1.27471816 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 17098.39 | 15128.22 | 0.9481 | 1.27471816 | 1.059092 | 21.57 | 15.97 | 0.00902220 | 44604.5 | 9.48 | 9.48 | 0.00850000 | 30934.6 | -999.0 | -999.00 | -999.00 | -999.00 | 674.499 | 16423.89 | 29.08 | 0.01411420 | 22.28 | 0.06173502 | 5.8291 | 21.11 | 0.00870701 | 21.11 | 0.00870701 | 55.8204 | 14455.54 | 0.00 | 18042.46 | 14422.77 | 1.22437643 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.16 | 14.49 | 0.01002554 | 40586.3 | |
ROOM_6_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16434.281 | 16434.281 | 1.028403 | 0.00014377 | 407.205 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.028403 | 1.23778095 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 2.3089 | 2.355404 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 16434.28 | 16434.28 | 1.0000 | 1.23778095 | 1.028403 | 19.20 | 13.52 | 0.00732165 | 37865.8 | 32.22 | 18.76 | 0.00800000 | 52863.7 | 0.14375959 | 60.00 | 32.22 | 27.78 | 0.000 | 16434.28 | -10.70 | 0.00150390 | -10.70 | 0.06172779 | 6.0023 | 21.11 | 0.00769315 | 21.11 | 0.00769315 | 49.3997 | 8716.64 | 0.00 | 17180.25 | 17180.25 | 1.23778095 | 16.60 | 12.49 | 0.00732165 | 35217.3 | 30.23 | 17.56 | 0.00732165 | 49097.2 | |
ROOM_6_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 17456.541 | 13974.653 | 1.028403 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6401 | 1004.8586 | 1.2036 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.028403 | 1.23778095 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | unknown | unknown | 7/21 09:30:00 | Sensible | 16635.95 | 14667.90 | 0.9530 | 1.23778095 | 1.028403 | 21.56 | 15.98 | 0.00903740 | 44631.5 | 9.48 | 9.48 | 0.00850000 | 30934.7 | -999.0 | -999.00 | -999.00 | -999.00 | 654.954 | 15980.99 | 28.66 | 0.01411345 | 22.16 | 0.06172779 | 6.0023 | 21.11 | 0.00871326 | 21.11 | 0.00871326 | 55.8600 | 14036.66 | 0.00 | 17465.09 | 13963.11 | 1.18889796 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.19 | 14.51 | 0.01002977 | 40632.2 | |
PTAC_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 42386.548 | 42386.548 | 1.753713 | 0.00037082 | 985.715 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.753713 | 2.11076030 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 5.9551 | 6.074952 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 42386.55 | 42386.55 | 1.0000 | 2.11076030 | 1.753713 | 12.42 | 9.39 | 0.00608055 | 27825.7 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.37077818 | 60.00 | 32.22 | 27.78 | 0.000 | 42386.55 | -10.70 | 0.00150390 | -10.70 | 0.47476218 | 27.0718 | 21.00 | 0.00777946 | 21.00 | 0.00777946 | 50.2859 | 14870.80 | 0.00 | 39976.82 | 39976.82 | 2.11076030 | 16.60 | 11.23 | 0.00608055 | 32075.1 | 35.24 | 18.22 | 0.00608055 | 51014.6 | |
PTAC_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 39766.931 | 29045.420 | 1.753713 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8151 | 1004.8586 | 1.2036 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.753713 | 2.11076030 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 40339.91 | 29143.81 | 1.0144 | 2.11076030 | 1.753713 | 26.19 | 18.96 | 0.01074536 | 53715.3 | 12.37 | 11.92 | 0.00850000 | 33885.9 | -999.0 | -999.00 | -999.00 | -999.00 | 1116.879 | 39223.03 | 32.10 | 0.01411964 | 23.13 | 0.47476218 | 27.0718 | 24.00 | 0.00949279 | 24.00 | 0.00949279 | 50.9999 | 23934.16 | 0.00 | 39786.40 | 29034.89 | 2.02740123 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.65 | 12.64 | 0.00910544 | 35698.1 | |
ROOM_1_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4917.187 | 4917.187 | 0.316392 | 0.00004302 | 122.274 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.316392 | 0.38080826 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 0.6908 | 0.704744 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4917.19 | 4917.19 | 1.0000 | 0.38080826 | 0.316392 | 19.56 | 13.79 | 0.00745799 | 38576.0 | 32.22 | 18.76 | 0.00800000 | 52863.7 | 0.04301330 | 60.00 | 32.22 | 27.78 | 0.000 | 4917.19 | -10.70 | 0.00150390 | -10.70 | 0.01543376 | 4.8780 | 21.11 | 0.00776332 | 21.11 | 0.00776332 | 49.8446 | 2858.16 | 0.00 | 5169.94 | 5169.94 | 0.38080826 | 16.60 | 12.62 | 0.00745799 | 35562.5 | 29.93 | 17.57 | 0.00745799 | 49138.7 | |
ROOM_1_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 5480.137 | 4386.146 | 0.316392 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4565 | 1004.8586 | 1.2036 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.316392 | 0.38080826 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | unknown | unknown | unknown | 7/21 16:20:00 | Sensible | 5044.08 | 4548.47 | 0.9204 | 0.38080826 | 0.316392 | 21.61 | 15.91 | 0.00893866 | 44433.4 | 9.48 | 9.48 | 0.00850000 | 30934.6 | -999.0 | -999.00 | -999.00 | -999.00 | 201.499 | 4842.58 | 31.46 | 0.01411849 | 22.95 | 0.01543376 | 4.8780 | 21.11 | 0.00867303 | 21.11 | 0.00867303 | 55.6055 | 4318.45 | 0.00 | 5482.82 | 4382.40 | 0.36576921 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.96 | 14.40 | 0.01000509 | 40332.6 | |
ROOM_2_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4794.681 | 4794.681 | 0.307414 | 0.00004195 | 119.173 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.307414 | 0.37000224 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 0.6736 | 0.687186 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 4794.68 | 4794.68 | 1.0000 | 0.37000224 | 0.307414 | 19.51 | 13.77 | 0.00745040 | 38510.8 | 32.22 | 18.76 | 0.00800000 | 52863.7 | 0.04194168 | 60.00 | 32.22 | 27.78 | 0.000 | 4794.68 | -10.70 | 0.00150390 | -10.70 | 0.01543195 | 5.0199 | 21.11 | 0.00776468 | 21.11 | 0.00776468 | 49.8532 | 2875.07 | 0.00 | 5037.48 | 5037.48 | 0.37000224 | 16.60 | 12.61 | 0.00745040 | 35543.2 | 29.96 | 17.58 | 0.00745040 | 49158.0 | |
ROOM_2_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 5331.696 | 4270.186 | 0.307414 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4791 | 1004.8586 | 1.2036 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.307414 | 0.37000224 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 4915.50 | 4420.93 | 0.9219 | 0.37000224 | 0.307414 | 21.62 | 15.92 | 0.00895081 | 44474.3 | 9.48 | 9.48 | 0.00850000 | 30934.6 | -999.0 | -999.00 | -999.00 | -999.00 | 195.781 | 4719.72 | 31.36 | 0.01411830 | 22.93 | 0.01543195 | 5.0199 | 21.11 | 0.00867770 | 21.11 | 0.00867770 | 55.6350 | 4195.90 | 0.00 | 5334.31 | 4266.39 | 0.35538995 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.94 | 14.39 | 0.01000650 | 40312.7 | |
ROOM_3_MULT9_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24158.139 | 24158.139 | 1.487678 | 0.00021135 | 597.310 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.487678 | 1.79056118 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 3.3941 | 3.462408 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 24158.14 | 24158.14 | 1.0000 | 1.79056118 | 1.487678 | 18.99 | 13.47 | 0.00735542 | 37737.0 | 32.22 | 18.76 | 0.00800000 | 52863.7 | 0.21132438 | 60.00 | 32.22 | 27.78 | 0.000 | 24158.14 | -10.70 | 0.00150390 | -10.70 | 0.09915400 | 6.6650 | 21.11 | 0.00777327 | 21.11 | 0.00777327 | 49.9070 | 13760.09 | 0.00 | 25169.98 | 25169.98 | 1.79056118 | 16.60 | 12.52 | 0.00735542 | 35302.8 | 30.40 | 17.64 | 0.00735542 | 49359.8 | |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 26825.302 | 21474.120 | 1.487678 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7383 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.487678 | 1.79056118 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | unknown | unknown | 7/21 13:20:00 | Sensible | 24749.43 | 21641.43 | 0.9226 | 1.79056118 | 1.487678 | 21.83 | 16.12 | 0.00909025 | 45034.4 | 9.48 | 9.48 | 0.00850000 | 30934.7 | -999.0 | -999.00 | -999.00 | -999.00 | 947.450 | 23801.98 | 31.85 | 0.01411920 | 23.06 | 0.09915400 | 6.6650 | 21.11 | 0.00873114 | 21.11 | 0.00873114 | 55.9733 | 20305.11 | 0.00 | 26838.43 | 21454.77 | 1.71984755 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.48 | 14.17 | 0.00995734 | 39717.3 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25594.572 | 25594.572 | 1.449662 | 0.00022391 | 558.631 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 3.5959 | 3.668281 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 25594.57 | 25594.57 | 1.0000 | 1.74480575 | 1.449662 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.22388964 | 60.00 | 32.22 | 27.78 | 0.000 | 25594.57 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00785005 | 21.00 | 0.00785005 | 50.7371 | 11167.93 | 0.00 | 24308.86 | 24308.86 | 1.74480575 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.26 | 18.13 | 0.00800000 | 50866.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25782.564 | 25782.564 | 1.449490 | 0.00022556 | 563.533 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 3.6223 | 3.695225 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 25782.56 | 25782.56 | 1.0000 | 1.74459837 | 1.449490 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.22553411 | 60.00 | 32.22 | 27.78 | 0.000 | 25782.56 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00785249 | 21.00 | 0.00785249 | 50.7527 | 11357.57 | 0.00 | 24487.34 | 24487.34 | 1.74459837 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.36 | 18.16 | 0.00800000 | 50970.8 | |
PTAC_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19292.448 | 19292.448 | 1.056323 | 0.00016878 | 468.153 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.056323 | 1.27138554 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 2.7105 | 2.765045 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 19292.45 | 19292.45 | 1.0000 | 1.27138554 | 1.056323 | 17.23 | 12.54 | 0.00711882 | 35345.2 | 32.11 | 18.73 | 0.00800000 | 52751.6 | 0.16876154 | 60.00 | 32.22 | 27.78 | 0.000 | 19292.45 | -10.70 | 0.00150390 | -10.70 | 0.12561561 | 11.8918 | 21.00 | 0.00787665 | 21.00 | 0.00787665 | 50.9065 | 11945.55 | 0.00 | 19552.38 | 19552.38 | 1.27138554 | 16.60 | 12.28 | 0.00711882 | 34703.8 | 31.71 | 17.89 | 0.00711882 | 50082.6 | |
PTAC_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 19823.332 | 15864.690 | 1.056323 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6408 | 1004.8586 | 1.2036 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.056323 | 1.27138554 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 19210.38 | 15996.63 | 0.9691 | 1.27138554 | 1.056323 | 24.95 | 17.62 | 0.00957570 | 49468.1 | 12.37 | 11.92 | 0.00850000 | 33884.8 | -999.0 | -999.00 | -999.00 | -999.00 | 672.736 | 18537.64 | 32.04 | 0.01411953 | 23.12 | 0.12561561 | 11.8918 | 24.00 | 0.00896243 | 24.00 | 0.00896243 | 48.1909 | 14416.46 | 0.00 | 19833.04 | 15855.04 | 1.22117542 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.98 | 13.93 | 0.00990746 | 39081.4 | |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_FLR_1 | RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LOBBY_FLR_1; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 189697.332 | 132993.616 | 7.639112 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.93681 | 1025.8898 | 1004.8586 | 1.2036 | VAV_FLR_1 FAN | Fan:VariableVolume | 7.639112 | 9.19439634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 194240.16 | 133223.91 | 1.0239 | 9.19439634 | 7.639112 | 27.00 | 19.66 | 0.01132347 | 56018.8 | 11.11 | 11.11 | 0.00850000 | 32596.3 | -999.0 | -999.00 | -999.00 | -999.00 | 16789.095 | 177451.07 | 32.10 | 0.01411964 | 23.13 | 2.83030000 | 37.0501 | 23.99 | 0.00967545 | 23.99 | 0.00967545 | 51.9781 | 90547.02 | 0.00 | 190245.98 | 133131.62 | 8.83128719 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.90 | 11.88 | 0.00864899 | 33780.1 | |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_1 | RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LOBBY_FLR_1; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 65381.836 | 65381.836 | 2.291733 | 0.00057199 | 1035.862 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_FLR_1 FAN | Fan:VariableVolume | 7.639112 | 9.19439634 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 9.1858 | 9.370697 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 65381.84 | 65381.84 | 1.0000 | 2.75831890 | 2.291733 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 0.57193048 | 60.00 | 32.22 | 27.78 | 0.000 | 65381.84 | -10.70 | 0.00150390 | -10.70 | 2.83030000 | 123.5004 | 21.00 | 0.00771045 | 21.00 | 0.00771044 | 49.8461 | 29146.56 | 0.00 | 56004.75 | 56004.75 | 2.75831890 | 2.80 | -1.97 | 0.00150390 | 6582.5 | 22.95 | 9.06 | 0.00150390 | 26886.5 | |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_FLR_6 | BANQUET_FLR_6; DINING_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 140544.401 | 98533.321 | 5.659723 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.81692 | 1027.8717 | 1004.8586 | 1.2036 | VAV_FLR_6 FAN | Fan:VariableVolume | 5.659723 | 6.81201424 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | Sensible | 147520.94 | 93681.14 | 1.0496 | 6.81201424 | 5.659723 | 28.53 | 20.92 | 0.01238962 | 60307.6 | 11.10 | 11.10 | 0.00850000 | 32588.1 | -999.0 | -999.00 | -999.00 | -999.00 | 12519.083 | 135001.86 | 32.10 | 0.01411964 | 23.13 | 3.16750000 | 55.9656 | 23.99 | 0.01019084 | 23.99 | 0.01019084 | 54.7334 | 67086.69 | 0.00 | 140950.89 | 98635.57 | 6.54299118 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.90 | 11.88 | 0.00864899 | 33780.1 | |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_6 | BANQUET_FLR_6; DINING_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 48440.592 | 48440.592 | 1.697917 | 0.00042378 | 767.458 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_FLR_6 FAN | Fan:VariableVolume | 5.659723 | 6.81201424 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 6.8057 | 6.942633 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 48440.59 | 48440.59 | 1.0000 | 2.04360427 | 1.697917 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 12.89 | 11.63 | 0.00800000 | 33150.5 | 0.42373620 | 60.00 | 32.22 | 27.78 | 0.000 | 48440.59 | -10.70 | 0.00150390 | -10.70 | 3.16750000 | 186.5521 | 21.00 | 0.00785126 | 21.00 | 0.00785127 | 50.7449 | 18020.19 | 0.00 | 41493.23 | 41493.23 | 2.04360427 | 2.80 | -1.97 | 0.00150390 | 6582.5 | 22.95 | 9.06 | 0.00150390 | 26886.5 | |
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | VAV_FLR_0 | BASEMENT | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 67740.840 | 49452.845 | 2.983330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5266 | 1004.8586 | 1.2036 | VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 2.983335 | 3.59072663 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:50:00 | Sensible | 33870.42 | 24531.61 | 1.0000 | 2.39381401 | 1.988887 | 25.30 | 18.55 | 0.01059016 | 52403.8 | 11.07 | 11.07 | 0.00850000 | 32556.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33870.42 | 28.54 | 0.01411323 | 22.13 | 0.85445887 | 42.9617 | 24.00 | 0.00917612 | 24.00 | 0.00917661 | 49.3264 | 35381.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_0 | BASEMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 72846.182 | 72846.182 | 2.983335 | 0.00039180 | 2156.174 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 2.983335 | 3.59072663 | 4197.9300 | 999.8980 | 6.10339311 | 54.44 | 82.22 | 27.78 | 711768.52 | 10.2345 | 6.418765 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 72846.18 | 72846.18 | 1.0000 | 3.59072663 | 2.983335 | 11.92 | 9.23 | 0.00613944 | 27468.9 | 32.11 | 18.73 | 0.00800000 | 52750.5 | 0.39176246 | 60.00 | 32.22 | 27.78 | 0.000 | 72846.18 | -10.70 | 0.00150390 | -10.70 | 0.85445887 | 28.6411 | 21.00 | 0.00799998 | 21.00 | 0.00799965 | 51.6906 | 2367.04 | 0.00 | 68452.02 | 68452.02 | 3.59072663 | 16.60 | 11.29 | 0.00613944 | 32224.2 | 35.36 | 18.31 | 0.00613944 | 51287.7 | |
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 63638.290 | 50952.633 | 3.844390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7536 | 1004.8586 | 1.2036 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.844389 | 4.62708764 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | Sensible | 31819.15 | 31436.59 | 1.0000 | 3.08472567 | 2.562927 | 24.00 | 16.43 | 0.00856054 | 45905.5 | 11.57 | 11.57 | 0.00850000 | 33065.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31819.15 | 30.52 | 0.01411680 | 22.69 | 0.00000000 | 0.0000 | 24.00 | 0.00856054 | 24.00 | 0.00856054 | 46.0611 | 45621.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51661.601 | 51661.601 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.844389 | 4.62708764 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 51661.60 | 51661.60 | 1.0000 | 4.62708764 | 3.844389 | 21.00 | 14.43 | 0.00754524 | 40265.3 | 32.11 | 18.73 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51661.60 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00754524 | 21.00 | 0.00754524 | 48.7927 | 2464.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49753.160 | 34880.945 | 2.003560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.8811 | 1004.8586 | 1.2036 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.003560 | 2.41147429 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | Sensible | 24876.58 | 16938.92 | 1.0000 | 1.60764984 | 1.335707 | 26.62 | 19.54 | 0.01131881 | 55619.3 | 11.54 | 11.54 | 0.00850000 | 33039.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24876.58 | 31.79 | 0.01411909 | 23.05 | 0.67638938 | 50.6391 | 23.99 | 0.00989165 | 23.99 | 0.00989654 | 53.1680 | 23714.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52855.228 | 52855.228 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.003560 | 2.41147429 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 52855.23 | 52855.23 | 1.0000 | 2.41147429 | 2.003560 | 10.30 | 7.94 | 0.00566386 | 24621.0 | 32.11 | 18.73 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52855.23 | -10.70 | 0.00150390 | -10.70 | 0.67638938 | 33.7594 | 21.00 | 0.00778397 | 21.00 | 0.00778397 | 50.3166 | 9570.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 58528.910 | 43244.085 | 2.643250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4670 | 1004.8586 | 1.2036 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.643248 | 3.18139965 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | Sensible | 29264.46 | 21022.54 | 1.0000 | 2.12093496 | 1.762167 | 24.69 | 18.32 | 0.01055813 | 51700.2 | 11.57 | 11.57 | 0.00850000 | 33070.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29264.46 | 29.29 | 0.01411458 | 22.34 | 0.36735036 | 20.8465 | 23.95 | 0.00998409 | 23.97 | 0.01005623 | 54.0699 | 31215.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50056.700 | 50056.700 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.643248 | 3.18139965 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 50056.70 | 50056.70 | 1.0000 | 3.18139965 | 2.643248 | 16.45 | 11.75 | 0.00665655 | 33382.7 | 32.11 | 18.73 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50056.70 | -10.70 | 0.00150390 | -10.70 | 0.36735036 | 13.8977 | 20.83 | 0.00748823 | 21.00 | 0.00746192 | 48.2613 | 2529.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_FLR_6_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_FLR_6_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2206.67 | 5198.50 | 702.17 |
RETAIL_1_FLR_1 | 4225.50 | 5674.50 | 1817.67 |
RETAIL_2_FLR_1 | 2566.83 | 5533.33 | 209.00 |
MECH_FLR_1 | 2743.17 | 5621.17 | 592.17 |
STORAGE_FLR_1 | 2717.17 | 6894.17 | 1649.00 |
LAUNDRY_FLR_1 | 8760.00 | 4077.00 | 4077.00 |
CAFE_FLR_1 | 4958.17 | 5301.33 | 1983.83 |
LOBBY_FLR_1 | 3210.17 | 5205.83 | 503.17 |
ROOM_1_FLR_3 | 2048.67 | 7786.67 | 1654.33 |
ROOM_2_FLR_3 | 3284.17 | 7490.50 | 2565.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1814.67 | 8309.33 | 1596.33 |
ROOM_5_FLR_3 | 1930.67 | 7753.33 | 1594.83 |
ROOM_6_FLR_3 | 3101.17 | 7405.50 | 2414.33 |
CORRIDOR_FLR_3 | 5511.17 | 3879.50 | 3797.33 |
ROOM_1_FLR_6 | 3286.83 | 7733.83 | 2751.50 |
ROOM_2_FLR_6 | 4441.00 | 7521.67 | 3664.33 |
ROOM_3_MULT9_FLR_6 | 2277.67 | 7719.33 | 1821.33 |
BANQUET_FLR_6 | 4102.50 | 4612.50 | 711.67 |
DINING_FLR_6 | 4428.17 | 3971.17 | 550.00 |
KITCHEN_FLR_6 | 8536.00 | 6231.17 | 6126.00 |
CORRIDOR_FLR_6 | 5594.33 | 4527.67 | 2859.33 |
Facility | 8760.00 | 8760.00 | 8357.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 1.83 | 0.00 | 1.83 |
ROOM_2_FLR_3 | 0.00 | 40.50 | 0.00 | 40.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 101.33 | 0.00 | 101.33 |
ROOM_5_FLR_3 | 0.00 | 1.83 | 0.00 | 1.83 |
ROOM_6_FLR_3 | 0.00 | 60.33 | 0.00 | 60.33 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 2.33 | 0.00 | 2.33 |
ROOM_2_FLR_6 | 0.00 | 39.33 | 0.00 | 39.33 |
ROOM_3_MULT9_FLR_6 | 0.00 | 0.50 | 0.00 | 0.50 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 115.17 | 0.00 | 115.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.648 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.584 | 0.137 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.104 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.461 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.550 | 0.051 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 0.000 | 0.148 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 3.310 | 0.108 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.354 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.178 | 0.000 | 0.065 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.354 | 0.178 | 0.000 | 0.036 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.395 | 0.079 | 0.000 | 0.106 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.357 | 0.178 | 0.000 | 0.066 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.178 | 0.000 | 0.051 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.051 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.357 | 0.178 | 0.000 | 0.080 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.357 | 0.178 | 0.000 | 0.042 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.408 | 0.145 | 0.000 | 0.127 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.325 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.443 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 4.298 | 0.148 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.062 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.76 | 106.50 | 4826.41 | 0.620 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.229 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.983 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.385 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.468 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 0.000 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.52 | 142.30 | 748.35 | 3.165 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.270 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.123 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.259 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 4.117 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.000 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV_FLR_0 | 61.76 | 106.50 | 4826.41 | 1978.83 | 0.8545 | 0.854 |
RETAIL_1_FLR_1 | VAV_FLR_1 | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV_FLR_1 | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV_FLR_1 | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV_FLR_1 | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | PSZ_CAFE | 82.52 | 142.30 | 748.35 | 188.86 | 0.6764 | 0.676 |
LOBBY_FLR_1 | VAV_FLR_1 | 244.96 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 39.02 | 0.062 | ||
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 39.02 | 0.062 | ||
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | 24.52 | 0.837 | |||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 24.53 | 0.837 | ||
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 39.02 | 0.062 | ||
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 39.02 | 0.062 | ||
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 389.40 | 0.475 | ||
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 39.02 | 0.015 | ||
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 39.02 | 0.015 | ||
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 24.53 | 0.099 | ||
BANQUET_FLR_6 | VAV_FLR_6 | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV_FLR_6 | 144.91 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | PSZ_KITCHEN | 12.90 | 22.24 | 314.87 | 103.30 | 0.3674 | 0.367 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 412.12 | 0.126 | ||
Total Facility | 872.83 | 1604.23 | 35184.81 | 11345.29 | 1.8982 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 26945836.20 | 0.00 | 26945836.20 | 0.00 | 26945836.20 | 26946214.98 | 0.00 | 8760.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 3631379.78 | 0.00 | 3631379.78 | 315162.19 | 3946541.96 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 2928114.74 | 0.00 | 2928114.74 | 121653.00 | 3049767.75 | 2892943.94 | 3276.50 | 4289.22 | 1194.28 | 0.00 |
MECH_FLR_1 | 2588217.25 | 0.00 | 2588217.25 | 287515.42 | 2875732.67 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1785539.65 | 0.00 | 1785539.65 | 165880.56 | 1951420.21 | 1821682.01 | 4736.01 | 3814.77 | 209.22 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 392587.63 | 392587.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 21330615.53 | 0.00 | 21330615.53 | 696683.85 | 22027299.38 | 21330615.53 | 0.00 | 8760.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 60368447.75 | 0.00 | 60368447.75 | 1990584.90 | 62359032.65 | 59728886.00 | 3240.90 | 3830.46 | 1688.64 | 0.00 |
ROOM_1_FLR_3 | 1465002.76 | 67209.67 | 1532212.43 | 182929.66 | 1715142.09 | 1946875.62 | 2432.58 | 5673.62 | 653.81 | 0.00 |
ROOM_2_FLR_3 | 1454523.32 | 36824.23 | 1491347.55 | 182915.70 | 1674263.25 | 1946647.51 | 2432.42 | 5992.85 | 334.73 | 0.00 |
ROOM_3_MULT19_FLR_3 | 3620700.04 | 0.00 | 3620700.04 | 51039.43 | 3671739.46 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 5651.89 |
ROOM_4_MULT19_FLR_3 | 19429720.37 | 68032.04 | 19497752.40 | 51053.38 | 19548805.79 | 26405105.73 | 2432.21 | 5721.15 | 606.64 | 0.00 |
ROOM_5_FLR_3 | 1470094.19 | 67274.97 | 1537369.16 | 182929.66 | 1720298.82 | 1946875.62 | 2433.17 | 5673.50 | 653.33 | 0.00 |
ROOM_6_FLR_3 | 1458503.65 | 51502.71 | 1510006.35 | 182915.70 | 1692922.06 | 1946647.51 | 2431.89 | 5850.55 | 477.56 | 0.00 |
CORRIDOR_FLR_3 | 2080161.97 | 0.00 | 2080161.97 | 221198.76 | 2301360.73 | 14972100.18 | 8760.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 368062.66 | 81631.08 | 449693.75 | 182967.83 | 632661.58 | 486718.90 | 2212.08 | 5673.33 | 874.59 | 0.00 |
ROOM_2_FLR_6 | 367103.35 | 43189.54 | 410292.89 | 182953.87 | 593246.76 | 486661.88 | 2288.34 | 5993.47 | 478.19 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2376508.53 | 81625.21 | 2458133.74 | 93612.75 | 2551746.48 | 3126920.42 | 2433.33 | 5671.33 | 655.33 | 0.00 |
BANQUET_FLR_6 | 37594946.30 | 0.00 | 37594946.30 | 446761.45 | 38041707.75 | 37458366.31 | 940.92 | 5212.63 | 2606.45 | 0.00 |
DINING_FLR_6 | 38585254.89 | 0.00 | 38585254.89 | 446761.45 | 39032016.34 | 37458366.31 | 74.83 | 2423.25 | 6261.92 | 0.00 |
KITCHEN_FLR_6 | 11584760.86 | 0.00 | 11584760.86 | 399955.08 | 11984715.94 | 11584760.86 | 0.00 | 8760.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 663636.56 | 0.00 | 663636.56 | 391453.71 | 1055090.27 | 3961413.96 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.20E+10 | 6921128.73 | 0.20E+10 | 18434047.20 | 0.20E+10 | 0.43E+10 | 8760.00 | 8760.00 | 8760.00 | 5651.89 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.8544 | 0.0000 | 0.8544 | 0.0000 | 0.8544 | 0.8545 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 0.1152 | 0.0000 | 0.1152 | 0.0100 | 0.1251 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.0928 | 0.0000 | 0.0928 | 0.0039 | 0.0967 | 0.0917 | 3276.50 | 4289.22 | 1194.28 |
MECH_FLR_1 | 0.0821 | 0.0000 | 0.0821 | 0.0091 | 0.0912 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0566 | 0.0000 | 0.0566 | 0.0053 | 0.0619 | 0.0578 | 4736.01 | 3814.77 | 209.22 |
LAUNDRY_FLR_1 | 0.0000 | 0.0000 | 0.0000 | 0.0124 | 0.0124 | 0.0000 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.6764 | 0.0000 | 0.6764 | 0.0221 | 0.6985 | 0.6764 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 1.9143 | 0.0000 | 1.9143 | 0.0631 | 1.9774 | 1.8940 | 3240.90 | 3830.46 | 1688.64 |
ROOM_1_FLR_3 | 0.0465 | 0.0021 | 0.0486 | 0.0058 | 0.0544 | 0.0617 | 2432.58 | 5673.62 | 653.81 |
ROOM_2_FLR_3 | 0.0461 | 0.0012 | 0.0473 | 0.0058 | 0.0531 | 0.0617 | 2432.42 | 5992.85 | 334.73 |
ROOM_4_MULT19_FLR_3 | 0.6161 | 0.0022 | 0.6183 | 0.0016 | 0.6199 | 0.8373 | 2432.21 | 5721.15 | 606.64 |
ROOM_5_FLR_3 | 0.0466 | 0.0021 | 0.0487 | 0.0058 | 0.0546 | 0.0617 | 2433.17 | 5673.50 | 653.33 |
ROOM_6_FLR_3 | 0.0462 | 0.0016 | 0.0479 | 0.0058 | 0.0537 | 0.0617 | 2431.89 | 5850.55 | 477.56 |
CORRIDOR_FLR_3 | 0.0660 | 0.0000 | 0.0660 | 0.0070 | 0.0730 | 0.4748 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.0117 | 0.0026 | 0.0143 | 0.0058 | 0.0201 | 0.0154 | 2212.08 | 5673.33 | 874.59 |
ROOM_2_FLR_6 | 0.0116 | 0.0014 | 0.0130 | 0.0058 | 0.0188 | 0.0154 | 2288.34 | 5993.47 | 478.19 |
ROOM_3_MULT9_FLR_6 | 0.0754 | 0.0026 | 0.0779 | 0.0030 | 0.0809 | 0.0992 | 2433.33 | 5671.33 | 655.33 |
BANQUET_FLR_6 | 1.1921 | 0.0000 | 1.1921 | 0.0142 | 1.2063 | 1.1878 | 940.92 | 5212.63 | 2606.45 |
DINING_FLR_6 | 1.2235 | 0.0000 | 1.2235 | 0.0142 | 1.2377 | 1.1878 | 74.83 | 2423.25 | 6261.92 |
KITCHEN_FLR_6 | 0.3674 | 0.0000 | 0.3674 | 0.0127 | 0.3800 | 0.3674 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 0.0210 | 0.0000 | 0.0210 | 0.0124 | 0.0335 | 0.1256 | 8760.00 | 0.00 | 0.00 |
Total Facility | 55.1275 | 0.2195 | 55.3470 | 0.4615 | 55.8086 | 73.9670 | 8760.00 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_FLR_1 | 0.10E+09 | 0.00 | 0.10E+09 | 66941728.23 | 0.00 | 0.00 | 8760.00 | 0.00 |
VAV_FLR_6 | 0.11E+09 | 0.00 | 0.11E+09 | 74916732.61 | 0.00 | 0.00 | 8760.00 | 0.00 |
VAV_FLR_0 | 39035388.57 | 0.00 | 39035388.57 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
PSZ_LAUNDRY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_CAFE | 30900401.64 | 0.00 | 30900401.64 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
PSZ_KITCHEN | 16782158.16 | 0.00 | 16782158.16 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_FLR_1 | 3.2753 | 0.0000 | 3.2753 | 2.1227 | 0.00 | 0.00 | 8760.00 |
VAV_FLR_6 | 3.4994 | 0.0000 | 3.4994 | 2.3756 | 0.00 | 0.00 | 8760.00 |
VAV_FLR_0 | 1.2378 | 0.0000 | 1.2378 | 0.8545 | 0.00 | 0.00 | 8760.00 |
PSZ_LAUNDRY | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.00 | 0.00 | 0.00 |
PSZ_CAFE | 0.9798 | 0.0000 | 0.9798 | 0.6764 | 0.00 | 0.00 | 8760.00 |
PSZ_KITCHEN | 0.5322 | 0.0000 | 0.5322 | 0.3674 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
VAV_FLR_6 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 | 8759.83 | 0.00 | 0.00 | 0.00 |
VAV_FLR_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
PSZ_LAUNDRY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_CAFE | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_KITCHEN | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_FLR_1 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 3.2753 | 0.0000 | 0.0000 | 0.0000 |
VAV_FLR_6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 3.4998 | 0.0000 | 0.0000 | 0.0000 |
VAV_FLR_0 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2378 | 0.0000 | 0.0000 | 0.0000 |
PSZ_LAUNDRY | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ_CAFE | 0.0000 | 0.9798 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ_KITCHEN | 0.0000 | 0.5322 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 6 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1309 |
Defaulted Fields | 1279 |
Fields with Defaults | 4096 |
Autosized Fields | 364 |
Autosizable Fields | 530 |
Autocalculated Fields | 279 |
Autocalculatable Fields | 538 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6866.45 | 100689.89 | 14-MAY-04:50 | 500039.02 | 04-AUG-19:10 |
Electricity:Building | 3195.05 | 37866.17 | 02-JAN-02:10 | 208035.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 384.14 | 4218.04 | 02-JAN-02:10 | 29343.82 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 3187.96 | 37725.02 | 02-JAN-02:10 | 207793.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 241.03 | 2190.14 | 02-JAN-02:10 | 19711.29 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 241.03 | 2190.14 | 02-JAN-02:10 | 19711.29 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 22.10 | 252.63 | 02-JAN-02:10 | 1660.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.92 | 108.29 | 02-JAN-02:10 | 974.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.92 | 108.29 | 02-JAN-02:10 | 974.63 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 25.60 | 292.55 | 02-JAN-02:10 | 1922.56 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.80 | 125.40 | 02-JAN-02:10 | 1128.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.80 | 125.40 | 02-JAN-02:10 | 1128.63 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 41.66 | 441.91 | 02-JAN-02:10 | 3226.11 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 29.18 | 265.18 | 02-JAN-02:10 | 2386.66 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 29.18 | 265.18 | 02-JAN-02:10 | 2386.66 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 12.58 | 132.58 | 02-JAN-02:10 | 976.54 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 8.98 | 81.60 | 02-JAN-02:10 | 734.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 8.98 | 81.60 | 02-JAN-02:10 | 734.39 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 45.66 | 487.82 | 02-JAN-02:10 | 3526.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 31.32 | 284.60 | 02-JAN-02:10 | 2561.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 31.32 | 284.60 | 02-JAN-02:10 | 2561.44 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 350.46 | 3941.97 | 02-JAN-02:10 | 26504.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 201.46 | 1830.55 | 02-JAN-02:10 | 16474.99 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 201.46 | 1830.55 | 02-JAN-02:10 | 16474.99 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 35.36 | 389.80 | 01-JAN-02:10 | 2642.31 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 35.36 | 389.75 | 01-JAN-02:10 | 2642.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 492.14 | 5849.00 | 01-JAN-02:10 | 36399.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 297.14 | 2515.76 | 01-JAN-02:10 | 22870.56 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 297.14 | 2515.76 | 01-JAN-02:10 | 22870.56 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 492.27 | 5850.60 | 01-JAN-02:10 | 36409.55 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 297.22 | 2516.45 | 01-JAN-02:10 | 22876.81 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 297.22 | 2516.45 | 01-JAN-02:10 | 22876.81 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 35.36 | 389.80 | 01-JAN-02:10 | 2642.31 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 35.36 | 389.75 | 01-JAN-02:10 | 2642.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.84 | 97.45 | 01-JAN-02:10 | 660.58 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.83 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.83 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.84 | 97.44 | 01-JAN-02:10 | 660.50 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.78 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.78 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 58.30 | 692.83 | 01-JAN-02:10 | 4311.66 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.20 | 298.00 | 01-JAN-02:10 | 2709.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.20 | 298.00 | 01-JAN-02:10 | 2709.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 230.86 | 2749.09 | 02-JAN-02:10 | 11246.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 230.86 | 2749.09 | 02-JAN-02:10 | 11246.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 459.16 | 6380.86 | 02-JAN-02:10 | 19096.59 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.69 | 133.44 | 02-JAN-02:10 | 1200.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.69 | 133.44 | 02-JAN-02:10 | 1200.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1661.82 | 24317.47 | 02-JAN-02:10 | 89286.95 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1661.82 | 24317.47 | 02-JAN-02:10 | 89286.95 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 437.38 | 6106.28 | 01-JAN-00:10 | 16602.84 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.20 | 743.83 | 05-FEB-23:30 | 2788.79 | 09-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 43.85 | 701.19 | 10-APR-22:30 | 3018.01 | 05-FEB-23:40 |
LowTempRefrigeration:Refrigeration:Electricity | 15.85 | 0.00 | 01-JAN-11:10 | 1306.73 | 24-OCT-04:20 |
MedTempRefrigeration:Refrigeration:Electricity | 21.26 | 599.30 | 06-FEB-05:00 | 713.31 | 02-AUG-13:10 |
Fans:Electricity | 1001.85 | 23659.17 | 12-JAN-12:00 | 48841.16 | 04-AUG-20:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2485.89 | 31319.39 | 14-JAN-08:00 | 260540.32 | 04-AUG-18:20 |
ExteriorEquipment:Electricity | 841.97 | 10954.76 | 02-JAN-02:20 | 50420.89 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.24 | 382.76 | 02-JAN-02:20 | 1343.17 | 31-MAY-20:10 |
ElectricityPurchased:Facility | 6866.45 | 100689.89 | 14-MAY-04:50 | 500039.02 | 04-AUG-19:10 |
ElectricityPurchased:Plant | 6866.45 | 100689.89 | 14-MAY-04:50 | 500039.02 | 04-AUG-19:10 |
Cogeneration:ElectricityPurchased | 6866.45 | 100689.89 | 14-MAY-04:50 | 500039.02 | 04-AUG-19:10 |
General:Cogeneration:ElectricityPurchased | 6866.45 | 100689.89 | 14-MAY-04:50 | 500039.02 | 04-AUG-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6866.45 | 100689.89 | 14-MAY-04:50 | 500039.02 | 04-AUG-19:10 |
ElectricityNet:Plant | 6866.45 | 100689.89 | 14-MAY-04:50 | 500039.02 | 04-AUG-19:10 |
Cogeneration:ElectricityNet | 6866.45 | 100689.89 | 14-MAY-04:50 | 500039.02 | 04-AUG-19:10 |
General:Cogeneration:ElectricityNet | 6866.45 | 100689.89 | 14-MAY-04:50 | 500039.02 | 04-AUG-19:10 |
General:Fans:Electricity | 1001.85 | 23659.17 | 12-JAN-12:00 | 48841.16 | 04-AUG-20:10 |
Cooling:Electricity | 1461.80 | 3482.25 | 06-FEB-05:00 | 212659.83 | 04-AUG-18:20 |
General:Cooling:Electricity | 1461.80 | 3482.25 | 06-FEB-05:00 | 212659.83 | 04-AUG-18:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorLights:Electricity | 321.91 | 0.00 | 01-JAN-07:30 | 20502.98 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 321.91 | 0.00 | 01-JAN-07:30 | 20502.98 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 6.74 | 47.91 | 31-MAY-16:30 | 1176.24 | 14-JAN-16:20 |
General:Pumps:Electricity | 6.74 | 47.91 | 31-MAY-16:30 | 1176.24 | 14-JAN-16:20 |
WIRED_LTG_ELECTRICITY | 53.72 | 0.00 | 01-JAN-00:10 | 4267.60 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6139.14 | 25142.72 | 07-AUG-02:00 | 650989.18 | 14-JAN-17:10 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:HVAC | 97.22 | 0.00 | 17-JAN-10:10 | 34606.51 | 06-FEB-03:00 |
Heating:NaturalGas | 1589.51 | 0.00 | 02-MAR-15:10 | 411771.69 | 06-FEB-03:00 |
General:Heating:NaturalGas | 97.22 | 0.00 | 17-JAN-10:10 | 34606.51 | 06-FEB-03:00 |
NaturalGas:Plant | 4253.08 | 11780.82 | 07-AUG-02:00 | 572236.68 | 05-FEB-24:00 |
WaterSystems:NaturalGas | 2760.80 | 11780.82 | 07-AUG-02:00 | 260847.80 | 16-FEB-21:20 |
Water Heater:WaterSystems:NaturalGas | 2760.80 | 11780.82 | 07-AUG-02:00 | 260847.80 | 16-FEB-21:20 |
Boiler:Heating:NaturalGas | 1492.28 | 0.00 | 02-MAR-15:10 | 377165.18 | 06-FEB-03:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 27-MAR-20:30 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 13835.74 | 162710.13 | 26-NOV-14:40 | 1196614.61 | 04-AUG-18:10 |
EnergyTransfer:Building | 5393.83 | 72327.95 | 06-FEB-15:00 | 406191.90 | 19-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 692.42 | 8354.34 | 06-FEB-04:00 | 37105.81 | 09-JUL-10:40 |
Refrigeration:EnergyTransfer | 186.00 | 3958.77 | 06-FEB-04:00 | 10342.34 | 04-AUG-07:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.00 | 1979.38 | 06-FEB-04:00 | 5171.17 | 04-AUG-07:20 |
General:Refrigeration:EnergyTransfer | 93.00 | 1979.38 | 06-FEB-04:00 | 5171.17 | 04-AUG-07:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.00 | 1979.38 | 06-FEB-04:00 | 5171.17 | 04-AUG-07:20 |
EnergyTransfer:Plant | 1850.12 | 11290.83 | 08-AUG-01:10 | 329077.92 | 06-FEB-07:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.68 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.32 | 1740.12 | 06-FEB-05:00 | 2535.92 | 02-AUG-13:10 |
EnergyTransfer:Zone:BASEMENT | 426.15 | 14.39 | 09-MAY-11:40 | 27672.31 | 05-OCT-20:00 |
Heating:EnergyTransfer | 127.51 | 0.00 | 13-JAN-12:00 | 104160.97 | 14-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.10 | 0.00 | 01-JAN-00:10 | 4816.45 | 07-APR-13:00 |
General:Heating:EnergyTransfer | 127.51 | 0.00 | 13-JAN-12:00 | 104160.97 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.10 | 0.00 | 01-JAN-00:10 | 4816.45 | 07-APR-13:00 |
Cooling:EnergyTransfer | 5173.32 | 54951.47 | 08-JAN-15:00 | 402565.96 | 19-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 426.06 | 0.00 | 27-MAR-13:00 | 27672.31 | 05-OCT-20:00 |
General:Cooling:EnergyTransfer | 5173.32 | 54951.47 | 08-JAN-15:00 | 402565.96 | 19-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 426.06 | 0.00 | 27-MAR-13:00 | 27672.31 | 05-OCT-20:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 41.51 | 0.00 | 09-MAR-18:30 | 5027.77 | 04-OCT-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 3.30 | 0.00 | 01-JAN-08:50 | 2336.79 | 06-FEB-05:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 3.30 | 0.00 | 01-JAN-08:50 | 2336.79 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 38.22 | 0.00 | 01-JAN-00:10 | 5027.77 | 04-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 38.22 | 0.00 | 01-JAN-00:10 | 5027.77 | 04-OCT-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.77 | 131.83 | 08-JAN-15:50 | 2663.65 | 19-JUN-19:20 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.77 | 131.83 | 08-JAN-15:50 | 2663.65 | 19-JUN-19:20 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 38.77 | 131.83 | 08-JAN-15:50 | 2663.65 | 19-JUN-19:20 |
EnergyTransfer:Zone:MECH_FLR_1 | 33.97 | 0.38 | 15-FEB-03:20 | 3196.87 | 19-JUN-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.06 | 0.00 | 01-JAN-07:10 | 593.11 | 06-FEB-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.06 | 0.00 | 01-JAN-07:10 | 593.11 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 33.90 | 0.00 | 01-JAN-00:10 | 3196.87 | 19-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 33.90 | 0.00 | 01-JAN-00:10 | 3196.87 | 19-JUN-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 17.74 | 0.06 | 15-APR-11:40 | 1496.72 | 19-JUN-18:20 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 2.26 | 0.00 | 03-JAN-19:10 | 1306.00 | 06-FEB-05:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 2.26 | 0.00 | 03-JAN-19:10 | 1306.00 | 06-FEB-05:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.47 | 0.00 | 01-JAN-00:10 | 1496.72 | 19-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.47 | 0.00 | 01-JAN-00:10 | 1496.72 | 19-JUN-18:20 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 585.18 | 6839.42 | 06-FEB-05:00 | 39328.19 | 04-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 585.18 | 6839.42 | 06-FEB-05:00 | 39328.19 | 04-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 585.18 | 6839.42 | 06-FEB-05:00 | 39328.19 | 04-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 231.80 | 8.34 | 25-JAN-14:40 | 16939.77 | 30-SEP-12:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.11 | 0.00 | 01-JAN-00:10 | 5862.46 | 06-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.11 | 0.00 | 01-JAN-00:10 | 5862.46 | 06-JAN-07:20 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 231.68 | 0.00 | 01-JAN-16:50 | 16939.77 | 30-SEP-12:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 231.68 | 0.00 | 01-JAN-16:50 | 16939.77 | 30-SEP-12:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 836.50 | 4645.17 | 08-JAN-16:00 | 49302.63 | 04-AUG-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 836.50 | 4645.17 | 08-JAN-16:00 | 49302.63 | 04-AUG-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 836.50 | 4645.17 | 08-JAN-16:00 | 49302.63 | 04-AUG-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 78.82 | 0.00 | 01-JAN-08:00 | 15171.43 | 30-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 12.43 | 0.00 | 01-JAN-08:00 | 6995.82 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 12.43 | 0.00 | 01-JAN-08:00 | 6995.82 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 66.39 | 0.00 | 01-JAN-00:10 | 15171.43 | 30-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 66.39 | 0.00 | 01-JAN-00:10 | 15171.43 | 30-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 64.66 | 0.00 | 01-JAN-08:00 | 14186.45 | 30-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 16.11 | 0.00 | 01-JAN-08:00 | 7122.96 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 16.11 | 0.00 | 01-JAN-08:00 | 7122.96 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 48.56 | 0.00 | 01-JAN-00:10 | 14186.45 | 30-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 48.56 | 0.00 | 01-JAN-00:10 | 14186.45 | 30-AUG-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 429.52 | 0.00 | 01-JAN-00:10 | 68754.26 | 04-OCT-12:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 429.52 | 0.00 | 01-JAN-00:10 | 68754.26 | 04-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 429.52 | 0.00 | 01-JAN-00:10 | 68754.26 | 04-OCT-12:10 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 486.82 | 0.00 | 01-JAN-08:00 | 104989.56 | 27-MAY-22:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 22.06 | 0.00 | 01-JAN-08:00 | 48764.37 | 06-FEB-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 22.06 | 0.00 | 01-JAN-08:00 | 48764.37 | 06-FEB-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 464.77 | 0.00 | 01-JAN-00:10 | 104989.56 | 27-MAY-22:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 464.77 | 0.00 | 01-JAN-00:10 | 104989.56 | 27-MAY-22:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 78.18 | 0.00 | 01-JAN-08:00 | 13236.65 | 22-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 12.25 | 0.00 | 01-JAN-08:00 | 7092.09 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 12.25 | 0.00 | 01-JAN-08:00 | 7092.09 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 65.93 | 0.00 | 01-JAN-00:10 | 13236.65 | 22-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 65.93 | 0.00 | 01-JAN-00:10 | 13236.65 | 22-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 63.93 | 0.00 | 01-JAN-08:00 | 15170.12 | 04-JUN-09:00 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 15.59 | 0.00 | 01-JAN-08:00 | 7212.71 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 15.59 | 0.00 | 01-JAN-08:00 | 7212.71 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 48.34 | 0.00 | 01-JAN-00:10 | 15170.12 | 04-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 48.34 | 0.00 | 01-JAN-00:10 | 15170.12 | 04-JUN-09:00 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 123.90 | 0.00 | 01-JAN-08:00 | 13761.41 | 19-JUN-18:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.28 | 0.00 | 01-JAN-08:00 | 3839.85 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.28 | 0.00 | 01-JAN-08:00 | 3839.85 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 123.62 | 0.00 | 01-JAN-00:10 | 13761.41 | 19-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 123.62 | 0.00 | 01-JAN-00:10 | 13761.41 | 19-JUN-18:20 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.60 | 0.00 | 01-JAN-11:00 | 4197.66 | 30-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 6.93 | 0.00 | 01-JAN-11:00 | 2423.33 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 6.93 | 0.00 | 01-JAN-11:00 | 2423.33 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 15.67 | 0.00 | 01-JAN-00:10 | 4197.66 | 30-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 15.67 | 0.00 | 01-JAN-00:10 | 4197.66 | 30-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 20.16 | 0.00 | 01-JAN-11:00 | 3929.86 | 30-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.36 | 0.00 | 01-JAN-11:00 | 2452.39 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.36 | 0.00 | 01-JAN-11:00 | 2452.39 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.81 | 0.00 | 01-JAN-00:10 | 3929.86 | 30-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 11.81 | 0.00 | 01-JAN-00:10 | 3929.86 | 30-AUG-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 115.99 | 0.00 | 01-JAN-08:00 | 19673.13 | 04-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 18.47 | 0.00 | 01-JAN-08:00 | 11630.01 | 14-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 18.47 | 0.00 | 01-JAN-08:00 | 11630.01 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 97.52 | 0.00 | 01-JAN-00:10 | 19673.13 | 04-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 97.52 | 0.00 | 01-JAN-00:10 | 19673.13 | 04-OCT-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 455.12 | 4903.32 | 06-FEB-09:20 | 25061.16 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 455.12 | 4903.32 | 06-FEB-09:20 | 25061.16 | 04-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 455.12 | 4903.32 | 06-FEB-09:20 | 25061.16 | 04-AUG-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 482.78 | 6212.30 | 06-FEB-09:20 | 26260.15 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 482.78 | 6212.30 | 06-FEB-09:20 | 26260.15 | 04-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 482.78 | 6212.30 | 06-FEB-09:20 | 26260.15 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 599.42 | 6156.20 | 03-JAN-04:00 | 32023.52 | 09-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 599.42 | 6156.20 | 03-JAN-04:00 | 32023.52 | 09-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 67.31 | 0.00 | 03-JAN-20:10 | 10001.63 | 16-AUG-12:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 9.20 | 0.00 | 03-JAN-20:10 | 6251.88 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 9.20 | 0.00 | 03-JAN-20:10 | 6251.88 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 58.10 | 0.00 | 01-JAN-00:10 | 10001.63 | 16-AUG-12:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 58.10 | 0.00 | 01-JAN-00:10 | 10001.63 | 16-AUG-12:50 |
PlantLoopHeatingDemand:Facility | 1765.66 | 8899.07 | 10-AUG-00:10 | 330176.19 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 760.18 | 8899.07 | 10-AUG-00:10 | 57491.80 | 09-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 760.18 | 8899.07 | 10-AUG-00:10 | 57491.80 | 09-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 760.18 | 8899.07 | 10-AUG-00:10 | 57491.80 | 09-FEB-07:10 |
EnergyTransfer:HVAC | 6591.79 | 37767.37 | 03-MAR-02:10 | 776622.78 | 04-AUG-18:10 |
HeatingCoils:EnergyTransfer | 1083.25 | 0.00 | 02-MAR-15:10 | 307189.07 | 06-FEB-03:00 |
PlantLoopHeatingDemand:HVAC | 1005.47 | 0.00 | 02-MAR-15:10 | 283215.69 | 02-JAN-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 1005.47 | 0.00 | 02-MAR-15:10 | 283215.69 | 02-JAN-09:10 |
CoolingCoils:EnergyTransfer | 5508.53 | 13075.49 | 06-FEB-05:00 | 776622.78 | 04-AUG-18:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 760.18 | 8899.07 | 10-AUG-00:10 | 57491.80 | 09-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 760.18 | 8899.07 | 10-AUG-00:10 | 57491.80 | 09-FEB-07:10 |
Boilers:EnergyTransfer | 996.93 | 0.00 | 02-MAR-15:10 | 277200.27 | 06-FEB-03:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.098 | -426.056 | 0.000 | 0.000 | 142.897 | 241.034 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -101.078 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 3.296 | -38.217 | 0.000 | 0.000 | 15.182 | 11.918 | 10.186 | 25.052 | 0.000 | 0.148 | 0.000 | 0.000 | -14.172 | 0.000 | -4.037 | -9.356 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -38.769 | 0.000 | 0.000 | 16.975 | 13.801 | 11.795 | 0.000 | 0.000 | 0.058 | 0.000 | 0.000 | 0.000 | 0.000 | -1.615 | -2.245 |
MECH_FLR_1 | 0.000 | 0.000 | 0.062 | -33.904 | 0.000 | 0.000 | 3.603 | 29.185 | 12.471 | 0.000 | 0.000 | 0.131 | 0.000 | 0.000 | 0.000 | 0.000 | -3.809 | -7.738 |
STORAGE_FLR_1 | 0.000 | 0.000 | 2.264 | -15.472 | 0.000 | 0.000 | 2.881 | 8.980 | 3.598 | 0.000 | 0.000 | 0.082 | 0.000 | 0.000 | 0.000 | 0.000 | -2.074 | -0.259 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -585.184 | 0.000 | 0.000 | 10.551 | 5.547 | 658.131 | 0.000 | 0.000 | 0.179 | 0.000 | 0.000 | 0.000 | 0.000 | -5.846 | -83.378 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.114 | -231.683 | 0.000 | 0.000 | 193.780 | 31.322 | 14.341 | 69.545 | 0.000 | 0.317 | 0.000 | 0.000 | -41.690 | 0.000 | -9.226 | -26.819 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -836.502 | 0.000 | 0.000 | 560.972 | 201.459 | 148.998 | 93.038 | 0.000 | 0.937 | 0.000 | 0.000 | -57.710 | 0.000 | -27.127 | -84.065 |
ROOM_1_FLR_3 | 12.427 | -66.387 | 0.000 | 0.000 | 0.000 | 0.000 | 9.683 | 24.885 | 10.478 | 53.858 | 0.000 | 0.773 | 1.565 | 0.000 | -37.596 | 0.000 | -9.686 | -0.002 |
ROOM_2_FLR_3 | 16.109 | -48.552 | 0.000 | 0.000 | 0.000 | 0.000 | 9.431 | 24.882 | 10.477 | 37.639 | 0.000 | 0.591 | 0.000 | 0.000 | -40.294 | 0.000 | -10.028 | -0.255 |
ROOM_3_MULT19_FLR_3 | 0.000 | -429.516 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 297.141 | 194.997 | 310.961 | 0.000 | 0.575 | 0.017 | 0.000 | -277.489 | 0.000 | -65.823 | -30.845 |
ROOM_4_MULT19_FLR_3 | 22.056 | -464.731 | 0.000 | 0.000 | 0.000 | 0.000 | 180.452 | 297.222 | 195.050 | 101.162 | 0.000 | 3.270 | 0.000 | 0.000 | -228.581 | 0.000 | -74.563 | -31.339 |
ROOM_5_FLR_3 | 12.254 | -65.928 | 0.000 | 0.000 | 0.000 | 0.000 | 9.677 | 24.885 | 10.478 | 53.358 | 0.000 | 0.773 | 1.288 | 0.000 | -37.074 | 0.000 | -9.711 | -0.001 |
ROOM_6_FLR_3 | 15.591 | -48.339 | 0.000 | 0.000 | 0.000 | 0.000 | 9.473 | 24.882 | 10.477 | 36.705 | 0.000 | 0.587 | 0.191 | 0.000 | -39.139 | 0.000 | -10.428 | -0.001 |
CORRIDOR_FLR_3 | 0.281 | -123.614 | 0.000 | 0.000 | 0.000 | 0.000 | 107.701 | 92.258 | 0.000 | 46.938 | 0.000 | 0.397 | 0.000 | 0.000 | -54.623 | 0.000 | -12.807 | -56.530 |
ROOM_1_FLR_6 | 6.928 | -15.671 | 0.000 | 0.000 | 0.000 | 0.000 | 2.429 | 6.221 | 2.620 | 13.366 | 0.000 | 0.197 | 0.000 | 0.000 | -9.144 | 0.000 | -2.436 | -4.508 |
ROOM_2_FLR_6 | 8.358 | -11.805 | 0.000 | 0.000 | 0.000 | 0.000 | 2.364 | 6.220 | 2.619 | 9.335 | 0.000 | 0.146 | 0.000 | 0.000 | -9.831 | 0.000 | -2.512 | -4.895 |
ROOM_3_MULT9_FLR_6 | 18.471 | -97.516 | 0.000 | 0.000 | 0.000 | 0.000 | 21.765 | 35.197 | 23.098 | 74.654 | 0.000 | 1.093 | 0.000 | 0.000 | -43.058 | 0.000 | -12.282 | -21.423 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -455.124 | 0.000 | 0.000 | 327.087 | 55.004 | 175.857 | 9.891 | 0.000 | 0.199 | 0.000 | 0.000 | -30.375 | 0.000 | -6.237 | -76.301 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -482.779 | 0.000 | 0.000 | 323.257 | 55.004 | 175.857 | 9.618 | 0.000 | 0.197 | 0.000 | 0.000 | -31.471 | 0.000 | -6.356 | -43.327 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -599.411 | 0.000 | 0.000 | 28.001 | 14.685 | 554.015 | 21.143 | 0.000 | 0.176 | 12.141 | 0.000 | -24.764 | 0.000 | -5.986 | -0.000 |
CORRIDOR_FLR_6 | 9.203 | -58.103 | 0.000 | 0.000 | 0.000 | 0.000 | 29.715 | 24.410 | 0.000 | 23.287 | 0.000 | 0.172 | 0.002 | 0.000 | -22.795 | 0.000 | -5.367 | -0.523 |
Total Facility | 121.677 | -1430.162 | 5.835 | -3743.100 | 0.000 | 0.000 | 2007.876 | 1526.141 | 2368.647 | 989.549 | 0.000 | 10.998 | 15.205 | 0.000 | -999.805 | 0.000 | -287.957 | -584.888 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-OCT-20:00 | 0.00 | 0.00 | 0.00 | -27670.24 | 0.00 | 0.00 | 5183.75 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6857.33 |
RETAIL_1_FLR_1 | 04-OCT-13:00 | 0.00 | 0.00 | 0.00 | -5027.72 | 0.00 | 0.00 | 150.60 | 270.73 | 252.59 | 5792.27 | 0.00 | 11.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1450.15 |
RETAIL_2_FLR_1 | 19-JUN-19:20 | 0.00 | 0.00 | 0.00 | -2663.60 | 0.00 | 0.00 | 610.40 | 1128.63 | 793.93 | 0.00 | 0.00 | 31.59 | 99.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 19-JUN-20:00 | 0.00 | 0.00 | 0.00 | -3196.83 | 0.00 | 0.00 | 129.08 | 2386.66 | 839.45 | 0.00 | 0.00 | 63.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -221.42 |
STORAGE_FLR_1 | 19-JUN-18:13 | 0.00 | 0.00 | 0.00 | -1496.80 | 0.00 | 0.00 | 99.29 | 652.79 | 229.41 | 0.00 | 0.00 | 48.32 | 466.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 04-AUG-20:00 | 0.00 | 0.00 | 0.00 | -39327.53 | 0.00 | 0.00 | 408.85 | 453.60 | 44299.38 | 0.00 | 0.00 | 116.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5950.98 |
CAFE_FLR_1 | 06-JAN-07:11 | 0.00 | 0.00 | 0.00 | -18172.40 | 0.00 | 0.00 | 4704.89 | 1423.02 | 609.65 | 0.00 | 0.00 | 0.00 | 16841.90 | 0.00 | -4604.06 | 0.00 | -803.00 | 0.00 |
LOBBY_FLR_1 | 04-AUG-20:10 | 0.00 | 0.00 | 0.00 | -49304.80 | 0.00 | 0.00 | 23501.51 | 14644.43 | 9501.36 | 1171.18 | 0.00 | 591.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -105.43 |
ROOM_1_FLR_3 | 29-MAR-15:12 | 0.00 | -18193.92 | 0.00 | 0.00 | 0.00 | 0.00 | 235.29 | 536.29 | 200.18 | 10936.88 | 0.00 | 0.00 | 6729.19 | 0.00 | -0.00 | 0.00 | -443.92 | 0.00 |
ROOM_2_FLR_3 | 15-MAY-16:21 | 0.00 | -18744.16 | 0.00 | 0.00 | 0.00 | 0.00 | 192.70 | 536.23 | 505.67 | 7094.09 | 0.00 | 0.00 | 10730.38 | 0.00 | -0.00 | 0.00 | -314.90 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:10 | 0.00 | -68754.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6403.76 | 2352.88 | 84204.68 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -319.78 | -23886.63 |
ROOM_4_MULT19_FLR_3 | 10-MAY-21:51 | 0.00 | -124899.44 | 0.00 | 0.00 | 0.00 | 0.00 | 7105.01 | 15327.46 | 6668.31 | 0.00 | 0.00 | 0.00 | 105952.96 | 0.00 | -8923.09 | 0.00 | -1231.21 | 0.00 |
ROOM_5_FLR_3 | 03-FEB-09:02 | 0.00 | -16267.34 | 0.00 | 0.00 | 0.00 | 0.00 | 90.01 | 842.75 | 453.05 | 8071.46 | 0.00 | 0.00 | 7641.34 | 0.00 | -0.00 | 0.00 | -831.25 | 0.00 |
ROOM_6_FLR_3 | 03-JUN-08:51 | 0.00 | -16697.15 | 0.00 | 0.00 | 0.00 | 0.00 | 107.47 | 1072.46 | 653.15 | 9518.65 | 0.00 | 0.00 | 5525.45 | 0.00 | -0.00 | 0.00 | -180.03 | 0.00 |
CORRIDOR_FLR_3 | 19-JUN-18:13 | 0.00 | -13764.95 | 0.00 | 0.00 | 0.00 | 0.00 | 4080.29 | 6706.42 | 0.00 | 2978.18 | 0.00 | 256.39 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -256.33 |
ROOM_1_FLR_6 | 11-MAY-15:11 | 0.00 | -4855.34 | 0.00 | 0.00 | 0.00 | 0.00 | 58.82 | 134.07 | 50.05 | 2496.94 | 0.00 | 0.00 | 2170.38 | 0.00 | -0.00 | 0.00 | -54.92 | 0.00 |
ROOM_2_FLR_6 | 15-MAY-16:21 | 0.00 | -5029.12 | 0.00 | 0.00 | 0.00 | 0.00 | 48.08 | 134.06 | 126.42 | 1741.36 | 0.00 | 0.00 | 3058.18 | 0.00 | -0.00 | 0.00 | -78.98 | 0.00 |
ROOM_3_MULT9_FLR_6 | 31-JAN-16:12 | 0.00 | -24472.72 | 0.00 | 0.00 | 0.00 | 0.00 | 529.40 | 758.55 | 441.28 | 2066.85 | 0.00 | 0.00 | 21509.27 | 0.00 | -0.00 | 0.00 | -832.62 | 0.00 |
BANQUET_FLR_6 | 04-AUG-21:10 | 0.00 | 0.00 | 0.00 | -25063.27 | 0.00 | 0.00 | 15643.61 | 2998.74 | 6747.90 | 539.80 | 0.00 | 120.93 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -987.71 |
DINING_FLR_6 | 04-AUG-21:10 | 0.00 | 0.00 | 0.00 | -26262.38 | 0.00 | 0.00 | 15643.55 | 2998.74 | 6747.90 | 520.18 | 0.00 | 120.93 | 231.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 09-JUL-10:40 | 0.00 | 0.00 | 0.00 | -32002.69 | 0.00 | 0.00 | 463.83 | 400.31 | 24375.41 | 3970.26 | 0.00 | 80.59 | 2712.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 16-AUG-12:50 | 0.00 | -10001.63 | 0.00 | 0.00 | 0.00 | 0.00 | 308.46 | 554.51 | 0.00 | 4704.70 | 0.00 | 111.29 | 4322.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-AUG-18:01 | 0.00 | -253177.90 | 0.00 | -190053.73 | 0.00 | 0.00 | 73660.47 | 107831.13 | 120597.93 | 11961.96 | 0.00 | 2315.23 | 127987.04 | 0.00 | -1122.13 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 07-APR-13:00 | 0.00 | 0.00 | 4816.80 | 0.00 | 0.00 | 0.00 | 1484.04 | 5475.36 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15325.03 |
RETAIL_1_FLR_1 | 06-FEB-05:00 | 0.00 | 0.00 | 2336.83 | 0.00 | 0.00 | 0.00 | 805.51 | 108.29 | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2052.63 | 0.00 | -455.90 | -886.44 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 06-FEB-05:00 | 0.00 | 0.00 | 593.12 | 0.00 | 0.00 | 0.00 | 197.29 | 265.18 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -415.86 | -816.46 |
STORAGE_FLR_1 | 06-FEB-05:00 | 0.00 | 0.00 | 1306.02 | 0.00 | 0.00 | 0.00 | 151.76 | 81.60 | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -239.93 | -1350.42 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 06-JAN-07:12 | 0.00 | 0.00 | 26996.87 | 0.00 | 0.00 | 0.00 | 4704.89 | 1423.02 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4604.06 | 0.00 | -819.74 | -28310.63 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 14-JAN-16:12 | 15854.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.33 | 632.06 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4022.86 | 0.00 | -805.27 | -12042.78 |
ROOM_2_FLR_3 | 14-JAN-16:12 | 15499.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.33 | 631.99 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4068.84 | 0.00 | -804.01 | -11643.15 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 06-FEB-16:12 | 93159.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5576.43 | 6405.51 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22232.75 | 0.00 | -4253.78 | -82381.77 |
ROOM_5_FLR_3 | 14-JAN-16:12 | 14641.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 | 632.06 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4116.60 | 0.00 | -801.88 | -10739.82 |
ROOM_6_FLR_3 | 14-JAN-16:12 | 14278.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 | 631.99 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4162.51 | 0.00 | -800.61 | -10331.81 |
CORRIDOR_FLR_3 | 02-JAN-07:10 | 3839.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2771.60 | 4191.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6228.77 | 0.00 | -1247.33 | -3326.46 |
ROOM_1_FLR_6 | 14-JAN-16:12 | 4337.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 158.02 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -996.93 | 0.00 | -201.28 | -3393.86 |
ROOM_2_FLR_6 | 14-JAN-16:12 | 4233.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 158.00 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1011.09 | 0.00 | -200.94 | -3275.99 |
ROOM_3_MULT9_FLR_6 | 14-JAN-16:12 | 20764.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.48 | 894.00 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4681.41 | 0.00 | -923.16 | -16908.82 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 06-FEB-07:10 | 6251.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.34 | 1109.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2758.65 | 0.00 | -566.91 | -4768.27 |
Total Facility | 14-JAN-16:12 | 123182.79 | 65627.17 | 4880.76 | -65627.17 | 0.00 | 0.00 | 37186.24 | 36657.99 | 74953.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -96380.20 | 0.00 | -20365.09 | -160116.26 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_FLR_1 | 7.6698 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 7.6391 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_6 | 5.6597 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.6597 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_0 | 2.9833 | 0.0000 | 106.4990 | 1.0000 | Calculated from schedules | 0.8545 | 2.9833 | 0.2864 | 1.0000 | Not calculated | 0.8545 | 0.2864 | ||
PSZ_LAUNDRY | 3.8444 | 0.0000 | 8.4000 | 1.0000 | Calculated from schedules | 0.0000 | 3.8444 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PSZ_CAFE | 2.0036 | 0.0000 | 142.3000 | 1.0000 | Calculated from schedules | 0.6764 | 2.0036 | 0.3376 | 1.0000 | Not calculated | 0.6764 | 0.3376 | ||
PSZ_KITCHEN | 2.6432 | 0.0000 | 22.2380 | 1.0000 | Calculated from schedules | 0.3674 | 2.6432 | 0.1390 | 1.0000 | Not calculated | 0.3674 | 0.1390 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_FLR_1 | 3.8349 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2765 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_6 | 2.8992 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8992 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_0 | 0.8950 | 0.0000 | 106.4990 | 1.0000 | Calculated from schedules | 0.8545 | 0.8950 | 1.0000 | 1.0000 | Not calculated | 0.8545 | 0.9547 | ||
PSZ_LAUNDRY | 3.8444 | 0.0000 | 8.4000 | 1.0000 | Calculated from schedules | 0.0000 | 3.8444 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PSZ_CAFE | 2.0036 | 0.0000 | 142.3000 | 1.0000 | Calculated from schedules | 0.6764 | 2.0036 | 1.0000 | 1.0000 | Not calculated | 0.6764 | 0.3376 | ||
PSZ_KITCHEN | 2.6432 | 0.0000 | 22.2380 | 1.0000 | Calculated from schedules | 0.3674 | 2.6432 | 1.0000 | 1.0000 | Not calculated | 0.3674 | 0.1390 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV_FLR_0 | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.8545 | 1.0000 | 0.8545 | 1.000 | 0.8545 |
RETAIL_1_FLR_1 | VAV_FLR_1 | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV_FLR_1 | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | PSZ_CAFE | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.6764 | 1.0000 | 0.6764 | 1.000 | 0.6764 |
LOBBY_FLR_1 | VAV_FLR_1 | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV_FLR_6 | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.3674 | 1.0000 | 0.3674 | 1.000 | 0.3674 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_FLR_1 | 0.00 | 0.001240 | 1711.9288 | 0.0000 | 0.0000 | 0.0000 | |
VAV_FLR_6 | 0.00 | 0.003581 | 663.3149 | 0.0000 | 0.0000 | 0.0000 | |
VAV_FLR_0 | 0.000000 | 106.50 | 0.000432 | 1978.8302 | 0.8545 | 0.8545 | 0.8545 |
PSZ_LAUNDRY | 0.000000 | 8.40 | 0.000000 | 78.0395 | 0.0000 | 0.0000 | 0.0000 |
PSZ_CAFE | 0.000000 | 142.30 | 0.003581 | 188.8619 | 0.6764 | 0.6764 | 0.6764 |
PSZ_KITCHEN | 0.000000 | 22.24 | 0.003556 | 103.3045 | 0.3674 | 0.3674 | 0.3674 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV_FLR_0 | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 2.9833 | 2.9833 | 0.8950 | No | 0.8545 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5074 | 0.5074 | 0.1522 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3288 | 0.3288 | 0.1355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3749 | 0.3749 | 0.1125 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1864 | 0.1864 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8444 | 3.8444 | 3.8444 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | PSZ_CAFE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0036 | 2.0036 | 2.0036 | No | 0.6764 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.2723 | 6.2723 | 2.7912 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7665 | 2.7665 | 1.4497 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8932 | 2.8932 | 1.4495 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6432 | 2.6432 | 2.6432 | No | 0.3674 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_FLR_1 | 7.6698 | 7.6391 | 7.6698 | 3.2765 | 0.0000 | 1.0000 |
VAV_FLR_6 | 5.6597 | 5.6597 | 5.6597 | 2.8992 | 0.0000 | 1.0000 |
VAV_FLR_0 | 2.9833 | 2.9833 | 2.9833 | 0.8950 | 0.8545 | 1.0000 |
PSZ_LAUNDRY | 3.8444 | 3.8444 | 3.8444 | 3.8444 | 0.0000 | 1.0000 |
PSZ_CAFE | 2.0036 | 2.0036 | 2.0036 | 2.0036 | 0.6764 | 1.0000 |
PSZ_KITCHEN | 2.6432 | 2.6432 | 2.6432 | 2.6432 | 0.3674 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV_FLR_0 | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.8950 | 0.8950 | 0.8950 | No | 0.8545 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2537 | 0.2537 | 0.1522 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1644 | 0.1644 | 0.1355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1874 | 0.1874 | 0.1125 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0932 | 0.0932 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.8444 | 3.8444 | 3.8444 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | PSZ_CAFE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0036 | 2.0036 | 2.0036 | No | 0.6764 | 0.7711 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1362 | 3.1362 | 2.7912 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4497 | 1.4497 | 1.4497 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4495 | 1.4495 | 1.4495 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6432 | 2.6432 | 2.6432 | No | 0.3674 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_FLR_1 | 3.8349 | 3.2765 | 3.2765 | 3.2765 | 0.0000 | 1.0000 |
VAV_FLR_6 | 2.8992 | 2.8992 | 2.8992 | 2.8992 | 0.0000 | 1.0000 |
VAV_FLR_0 | 0.8950 | 0.8950 | 0.8950 | 0.8950 | 0.8545 | 1.0000 |
PSZ_LAUNDRY | 3.8444 | 3.8444 | 3.8444 | 3.8444 | 0.0000 | 1.0000 |
PSZ_CAFE | 2.0036 | 2.0036 | 2.0036 | 2.0036 | 0.6764 | 1.0000 |
PSZ_KITCHEN | 2.6432 | 2.6432 | 2.6432 | 2.6432 | 0.3674 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 115.17 |
Number of hours not met | 115.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 97.22 | 34606.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1492.28 | 377165.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1461.80 | 212659.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1526.14 | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 321.91 | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 15.55 | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 11.51 | 365.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.24 | 1343.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1001.85 | 48841.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 6.74 | 1176.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 2760.80 | 260847.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.85 | 1306.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.26 | 713.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1706.02 | 6866.45 |
Natural Gas | 1788.84 | 6139.14 |
Additional | 0.00 | 0.00 |
Total | 3494.86 | 13005.59 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 134.52 |
Space Heating | 0.00 |
Space Cooling | 128.85 |
Fans (All) | 88.31 |
Service Water Heating | 0.00 |
Receptacle Equipment | 146.48 |
Miscellaneous (All) | 605.22 |
Subtotal | 605.22 |
Natural Gas [MJ/m2] | |
Space Heating | 140.10 |
Service Water Heating | 243.34 |
Miscellaneous (All) | 541.12 |
Subtotal | 541.12 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.73 |
Space Heating | 12.22 |
Space Cooling | 11.24 |
Fans (All) | 7.70 |
Service Water Heating | 21.23 |
Receptacle Equipment | 26.53 |
Miscellaneous | 9.34 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 3061. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 3061. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 3061. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | RETAIL_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | RETAIL_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8497.50 | 262.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8260.00 | 500.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8641.33 | 118.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8455.17 | 304.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8260.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 500.00 | 0.00 | 0.00 | 0.00 |
Average | 8705.88 | 54.12 | 0.00 | 0.00 | 0.00 |
Sum | 191529.33 | 1190.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4044.00 | 110.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4150.83 | 3.17 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4129.83 | 24.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4020.67 | 133.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 133.33 | 0.00 | 0.00 | 0.00 |
Average | 288874.74 | 12.30 | 0.00 | 0.00 | 0.00 |
Sum | 6355244.33 | 270.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8280.50 | 479.50 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7486.50 | 1273.50 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8174.83 | 585.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8164.50 | 595.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 6626.83 | 2133.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8344.17 | 415.83 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8259.83 | 500.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 4962.00 | 3798.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8148.83 | 611.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8045.83 | 714.17 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8110.17 | 649.83 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 6850.83 | 1909.17 | 0.00 | 0.00 | 0.00 |
Min | 4962.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3798.00 | 0.00 | 0.00 | 0.00 |
Average | 8136.45 | 623.55 | 0.00 | 0.00 | 0.00 |
Sum | 179002.00 | 13718.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 500365.00 | 28966.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 58991.67 | 164.33 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 586229.33 | 124187.67 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1907996.33 | 207432.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 3902.17 | 251.83 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3970.67 | 183.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 3956.17 | 197.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 57263.33 | 43094.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 3895.67 | 258.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1093504.17 | 152210.83 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1107214.83 | 138500.17 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 82583.50 | 23362.50 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1907996.33 | 207432.67 | 0.00 | 0.00 | 0.00 |
Average | 256213.86 | 32673.19 | 0.00 | 0.00 | 0.00 |
Sum | 5636704.83 | 718810.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:24:38
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407073E+11 | 25092.96 | 11-JAN-21:50 | -5.2 | -8.0 | 0.630748E+10 | 4534.42 | 24-JAN-22:10 | 6.60 | 4.01 |
February | 0.312900E+11 | 22298.75 | 14-FEB-22:00 | -2.8 | -6.1 | 0.554346E+10 | 3964.78 | 01-FEB-22:10 | -2.8 | -6.1 |
March | 0.303366E+11 | 20907.10 | 22-MAR-21:00 | -1.1 | -5.6 | 0.632527E+10 | 4602.72 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.242921E+11 | 17106.74 | 12-APR-06:00 | 3.90 | -0.6 | 0.670537E+10 | 4837.25 | 27-APR-21:10 | 14.40 | 13.08 |
May | 0.202266E+11 | 16286.41 | 31-MAY-21:00 | 20.60 | 17.62 | 0.790747E+10 | 4837.34 | 26-MAY-21:10 | 20.60 | 17.62 |
June | 0.255796E+11 | 19110.24 | 20-JUN-19:51 | 21.10 | 16.91 | 0.799827E+10 | 4837.40 | 06-JUN-21:10 | 21.10 | 16.91 |
July | 0.325308E+11 | 21504.16 | 21-JUL-21:00 | 25.60 | 23.64 | 0.823281E+10 | 4837.36 | 28-JUL-23:10 | 23.80 | 20.09 |
August | 0.386579E+11 | 23865.67 | 18-AUG-20:00 | 26.10 | 18.80 | 0.826765E+10 | 4837.76 | 17-AUG-01:10 | 26.10 | 18.80 |
September | 0.427277E+11 | 26297.32 | 07-SEP-20:00 | 23.90 | 21.88 | 0.797747E+10 | 4837.41 | 29-SEP-23:10 | 12.02 | 10.24 |
October | 0.475084E+11 | 27672.31 | 05-OCT-20:00 | 18.90 | 18.13 | 0.822708E+10 | 4837.44 | 19-OCT-22:30 | 13.30 | 12.22 |
November | 0.457271E+11 | 27045.47 | 03-NOV-20:00 | 12.80 | 10.92 | 0.760094E+10 | 4837.44 | 08-NOV-23:00 | 11.10 | 10.49 |
December | 0.464716E+11 | 26588.01 | 31-DEC-21:00 | -6.7 | -9.3 | 0.687120E+10 | 4837.20 | 04-DEC-22:10 | -6.7 | -9.3 |
Annual Sum or Average | 0.426056E+12 | 0.879645E+11 | ||||||||
Minimum of Months | 0.202266E+11 | 16286.41 | -6.7 | -9.3 | 0.554346E+10 | 3964.78 | -6.7 | -9.3 | ||
Maximum of Months | 0.475084E+11 | 27672.31 | 26.10 | 23.64 | 0.826765E+10 | 4837.76 | 26.10 | 20.09 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.726937E+09 | 3085.00 | 17-JAN-13:20 | 10.37 | 5.44 | 0.626000E+09 | 367.83 | 19-JAN-22:10 | 5.60 | 1.07 |
February | 0.954557E+09 | 2532.80 | 02-FEB-13:40 | 5.97 | -0.5 | 0.569934E+09 | 364.17 | 06-FEB-04:10 | -13.3 | -14.8 |
March | 0.180425E+10 | 3666.02 | 03-MAR-13:30 | 14.70 | 8.33 | 0.648817E+09 | 445.91 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.252112E+10 | 4253.55 | 07-APR-12:30 | 26.15 | 15.90 | 0.647592E+09 | 491.81 | 07-APR-21:19 | 19.03 | 13.70 |
May | 0.368557E+10 | 3787.32 | 30-MAY-12:50 | 29.90 | 17.93 | 0.712258E+09 | 491.84 | 31-MAY-21:40 | 20.13 | 17.44 |
June | 0.463080E+10 | 4187.39 | 19-JUN-13:10 | 34.90 | 23.89 | 0.758681E+09 | 491.84 | 01-JUN-22:10 | 34.90 | 23.89 |
July | 0.557658E+10 | 4199.61 | 07-JUL-12:40 | 33.17 | 23.31 | 0.808161E+09 | 491.84 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.617217E+10 | 4845.20 | 18-AUG-12:40 | 33.13 | 20.27 | 0.808908E+09 | 491.84 | 30-AUG-21:10 | 22.62 | 18.07 |
September | 0.485457E+10 | 4923.59 | 05-SEP-12:50 | 26.70 | 20.91 | 0.739365E+09 | 491.84 | 12-SEP-21:49 | 21.78 | 19.45 |
October | 0.442271E+10 | 5027.77 | 04-OCT-13:00 | 25.00 | 18.54 | 0.722063E+09 | 491.81 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 0.181379E+10 | 3839.76 | 04-NOV-12:30 | 17.80 | 12.61 | 0.621120E+09 | 447.81 | 03-NOV-21:10 | 17.80 | 12.61 |
December | 0.105421E+10 | 3559.08 | 17-DEC-13:00 | 12.20 | 4.95 | 0.629117E+09 | 364.14 | 07-DEC-03:09 | 12.20 | 4.95 |
Annual Sum or Average | 0.382173E+11 | 0.829201E+10 | ||||||||
Minimum of Months | 0.726937E+09 | 2532.80 | 5.97 | -0.5 | 0.569934E+09 | 364.14 | -13.3 | -14.8 | ||
Maximum of Months | 0.617217E+10 | 5027.77 | 34.90 | 23.89 | 0.808908E+09 | 491.84 | 34.90 | 23.89 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230808E+10 | 1231.00 | 19-JAN-22:00 | 5.60 | 1.07 | 0.754586E+09 | 520.49 | 19-JAN-22:10 | 5.60 | 1.07 |
February | 0.214706E+10 | 1211.47 | 22-FEB-22:00 | 2.20 | -1.1 | 0.686614E+09 | 514.78 | 22-FEB-22:10 | 2.20 | -1.1 |
March | 0.280154E+10 | 1452.05 | 27-MAR-20:10 | 15.82 | 11.86 | 0.811392E+09 | 569.51 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.299154E+10 | 2061.62 | 07-APR-19:20 | 23.17 | 15.28 | 0.824437E+09 | 569.55 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.349946E+10 | 2446.37 | 30-MAY-19:10 | 21.42 | 15.63 | 0.905909E+09 | 569.55 | 25-MAY-22:10 | 21.42 | 15.63 |
June | 0.386725E+10 | 2663.65 | 19-JUN-19:20 | 31.13 | 22.29 | 0.920013E+09 | 569.55 | 02-JUN-21:00 | 31.13 | 22.29 |
July | 0.423158E+10 | 2625.87 | 12-JUL-19:10 | 24.90 | 21.57 | 0.960007E+09 | 569.55 | 11-JUL-22:10 | 24.90 | 21.57 |
August | 0.432868E+10 | 2637.75 | 15-AUG-18:15 | 26.13 | 20.51 | 0.963835E+09 | 569.56 | 30-AUG-21:10 | 22.62 | 18.07 |
September | 0.372992E+10 | 2444.08 | 06-SEP-19:20 | 22.80 | 20.57 | 0.908173E+09 | 569.55 | 28-SEP-22:10 | 14.90 | 10.57 |
October | 0.352117E+10 | 2159.39 | 04-OCT-19:20 | 19.23 | 16.84 | 0.910608E+09 | 569.55 | 25-OCT-22:10 | 16.10 | 7.62 |
November | 0.277928E+10 | 1606.47 | 03-NOV-21:00 | 12.80 | 10.14 | 0.790096E+09 | 569.52 | 02-NOV-21:19 | 12.80 | 10.14 |
December | 0.256285E+10 | 1241.24 | 19-DEC-22:00 | 5.60 | 2.33 | 0.772598E+09 | 523.17 | 19-DEC-22:10 | 5.40 | 2.50 |
Annual Sum or Average | 0.387684E+11 | 0.102083E+11 | ||||||||
Minimum of Months | 0.214706E+10 | 1211.47 | 2.20 | -1.1 | 0.686614E+09 | 514.78 | 2.20 | -1.1 | ||
Maximum of Months | 0.432868E+10 | 2663.65 | 31.13 | 22.29 | 0.963835E+09 | 569.56 | 31.13 | 22.29 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146473E+10 | 959.10 | 24-JAN-22:00 | 6.70 | 4.17 | 0.155734E+09 | 104.97 | 24-JAN-22:10 | 6.60 | 4.01 |
February | 0.128894E+10 | 915.42 | 23-FEB-22:00 | 4.40 | 3.44 | 0.140417E+09 | 101.83 | 24-FEB-22:10 | 0.32 | -3.7 |
March | 0.215624E+10 | 1095.39 | 27-MAR-21:00 | 14.40 | 11.07 | 0.164609E+09 | 115.37 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.245452E+10 | 1849.87 | 10-APR-20:00 | 15.60 | 8.18 | 0.171948E+09 | 120.45 | 26-APR-21:10 | 13.72 | 10.80 |
May | 0.310661E+10 | 2762.32 | 30-MAY-19:50 | 20.28 | 15.58 | 0.194382E+09 | 120.45 | 25-MAY-21:00 | 20.28 | 15.58 |
June | 0.381800E+10 | 3196.87 | 19-JUN-20:00 | 30.00 | 22.01 | 0.197362E+09 | 120.45 | 09-JUN-21:10 | 30.00 | 22.01 |
July | 0.447107E+10 | 3115.06 | 10-JUL-20:00 | 28.30 | 20.24 | 0.204590E+09 | 120.45 | 11-JUL-21:10 | 22.80 | 17.48 |
August | 0.442861E+10 | 3164.37 | 04-AUG-20:00 | 32.20 | 24.21 | 0.205203E+09 | 120.46 | 30-AUG-21:10 | 22.62 | 18.07 |
September | 0.351248E+10 | 2882.69 | 01-SEP-20:00 | 26.70 | 17.87 | 0.194980E+09 | 120.46 | 28-SEP-21:10 | 16.42 | 11.03 |
October | 0.299625E+10 | 2285.90 | 05-OCT-20:00 | 18.90 | 18.13 | 0.192977E+09 | 120.45 | 18-OCT-21:10 | 9.13 | 6.16 |
November | 0.225811E+10 | 1235.92 | 03-NOV-21:00 | 12.80 | 10.14 | 0.165870E+09 | 120.45 | 03-NOV-21:10 | 12.80 | 10.17 |
December | 0.194859E+10 | 981.87 | 04-DEC-22:00 | 7.80 | 7.49 | 0.158217E+09 | 106.59 | 04-DEC-22:10 | 7.88 | 7.49 |
Annual Sum or Average | 0.339041E+11 | 0.214629E+10 | ||||||||
Minimum of Months | 0.128894E+10 | 915.42 | 4.40 | 3.44 | 0.140417E+09 | 101.83 | 0.32 | -3.7 | ||
Maximum of Months | 0.447107E+10 | 3196.87 | 32.20 | 24.21 | 0.205203E+09 | 120.46 | 30.00 | 22.01 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82617023.26 | 565.60 | 23-JAN-21:50 | 10.50 | 10.22 | 0.116692E+09 | 68.71 | 23-JAN-22:10 | 10.60 | 10.26 |
February | 61711664.80 | 376.20 | 23-FEB-22:00 | 4.40 | 3.44 | 0.105502E+09 | 68.57 | 16-FEB-00:10 | 4.40 | 3.44 |
March | 0.530707E+09 | 667.23 | 27-MAR-20:15 | 15.53 | 11.71 | 0.117677E+09 | 76.00 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.118692E+10 | 779.94 | 07-APR-20:00 | 21.70 | 14.73 | 0.117849E+09 | 84.27 | 07-APR-21:10 | 19.22 | 13.77 |
May | 0.186889E+10 | 1040.32 | 30-MAY-18:20 | 22.43 | 16.44 | 0.133740E+09 | 92.65 | 31-MAY-21:10 | 20.48 | 17.58 |
June | 0.214744E+10 | 1496.81 | 19-JUN-18:13 | 32.03 | 22.95 | 0.143762E+09 | 92.66 | 01-JUN-21:10 | 32.03 | 22.95 |
July | 0.243106E+10 | 1421.97 | 10-JUL-18:13 | 29.63 | 20.43 | 0.153254E+09 | 92.66 | 11-JUL-21:10 | 22.80 | 17.48 |
August | 0.240629E+10 | 1464.96 | 04-AUG-19:20 | 32.93 | 24.43 | 0.152958E+09 | 92.66 | 30-AUG-21:10 | 22.62 | 18.07 |
September | 0.200879E+10 | 1156.07 | 01-SEP-20:00 | 26.70 | 17.87 | 0.138587E+09 | 92.66 | 14-SEP-21:10 | 24.13 | 17.21 |
October | 0.177512E+10 | 817.08 | 05-OCT-20:20 | 18.90 | 18.02 | 0.130293E+09 | 87.36 | 05-OCT-21:10 | 18.90 | 17.74 |
November | 0.823410E+09 | 689.77 | 03-NOV-21:00 | 12.80 | 10.14 | 0.114548E+09 | 77.86 | 03-NOV-21:10 | 12.80 | 10.17 |
December | 0.148725E+09 | 575.22 | 04-DEC-22:00 | 7.80 | 7.49 | 0.116696E+09 | 69.39 | 04-DEC-22:10 | 7.88 | 7.49 |
Annual Sum or Average | 0.154717E+11 | 0.154156E+10 | ||||||||
Minimum of Months | 61711664.80 | 376.20 | 4.40 | 3.44 | 0.105502E+09 | 68.57 | 4.40 | 3.44 | ||
Maximum of Months | 0.243106E+10 | 1496.81 | 32.93 | 24.43 | 0.153254E+09 | 92.66 | 32.03 | 22.95 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460919E+11 | 36755.21 | 23-JAN-21:00 | 10.00 | 10.00 | 0.649358E+09 | 381.54 | 24-JAN-05:19 | 10.37 | 10.37 |
February | 0.416474E+11 | 36558.90 | 01-FEB-21:00 | 5.60 | 3.16 | 0.587091E+09 | 381.54 | 24-FEB-05:00 | 4.40 | 4.40 |
March | 0.478839E+11 | 37802.22 | 27-MAR-20:00 | 16.10 | 12.02 | 0.652413E+09 | 381.54 | 06-MAR-05:30 | 16.10 | 12.02 |
April | 0.476068E+11 | 38467.64 | 07-APR-20:00 | 21.70 | 14.73 | 0.629524E+09 | 381.54 | 28-APR-04:10 | 14.22 | 11.81 |
May | 0.510629E+11 | 38667.62 | 30-MAY-19:51 | 20.00 | 15.55 | 0.650740E+09 | 381.54 | 19-MAY-04:19 | 20.00 | 15.55 |
June | 0.507668E+11 | 39307.21 | 19-JUN-20:00 | 30.00 | 22.01 | 0.630905E+09 | 381.55 | 19-JUN-04:10 | 30.00 | 22.01 |
July | 0.530177E+11 | 39147.17 | 10-JUL-20:00 | 28.30 | 20.24 | 0.649375E+09 | 381.55 | 20-JUL-04:10 | 23.90 | 23.41 |
August | 0.532947E+11 | 39328.19 | 04-AUG-20:00 | 32.20 | 24.21 | 0.652120E+09 | 381.55 | 17-AUG-04:10 | 25.00 | 24.24 |
September | 0.501316E+11 | 38942.11 | 01-SEP-20:00 | 26.70 | 17.87 | 0.629225E+09 | 381.55 | 14-SEP-04:10 | 22.20 | 21.85 |
October | 0.504111E+11 | 38296.56 | 04-OCT-20:00 | 18.90 | 16.06 | 0.649672E+09 | 381.55 | 06-OCT-04:19 | 19.40 | 18.28 |
November | 0.465851E+11 | 37620.66 | 03-NOV-20:00 | 12.80 | 10.92 | 0.628149E+09 | 381.54 | 10-NOV-05:30 | 13.85 | 13.85 |
December | 0.466839E+11 | 36813.39 | 04-DEC-21:00 | 8.90 | 8.00 | 0.649359E+09 | 381.54 | 04-DEC-22:10 | 7.88 | 7.49 |
Annual Sum or Average | 0.585184E+12 | 0.765793E+10 | ||||||||
Minimum of Months | 0.416474E+11 | 36558.90 | 5.60 | 3.16 | 0.587091E+09 | 381.54 | 4.40 | 4.40 | ||
Maximum of Months | 0.532947E+11 | 39328.19 | 32.20 | 24.21 | 0.652413E+09 | 381.55 | 30.00 | 24.24 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129936E+11 | 18172.78 | 06-JAN-07:11 | -7.0 | -8.3 | 0.818415E+10 | 5674.30 | 23-JAN-23:10 | 10.50 | 10.22 |
February | 0.130734E+11 | 14402.76 | 26-FEB-15:21 | -2.2 | -5.8 | 0.739246E+10 | 4782.39 | 07-FEB-00:40 | -2.2 | -5.8 |
March | 0.176642E+11 | 13265.38 | 03-MAR-13:10 | 14.50 | 8.14 | 0.860299E+10 | 6463.89 | 27-MAR-21:10 | 14.13 | 10.87 |
April | 0.176151E+11 | 15228.82 | 08-APR-12:20 | 23.87 | 16.21 | 0.917635E+10 | 6464.53 | 07-APR-21:49 | 23.87 | 16.21 |
May | 0.190280E+11 | 13406.26 | 29-MAY-12:00 | 28.90 | 18.44 | 0.107777E+11 | 6464.37 | 12-MAY-21:49 | 28.90 | 18.44 |
June | 0.219819E+11 | 13532.88 | 19-JUN-12:40 | 35.57 | 24.06 | 0.106878E+11 | 6464.50 | 23-JUN-23:49 | 22.20 | 21.37 |
July | 0.254012E+11 | 13847.40 | 08-JUL-12:00 | 32.20 | 26.10 | 0.110009E+11 | 6464.55 | 24-JUL-21:10 | 22.98 | 20.55 |
August | 0.270906E+11 | 15707.57 | 13-AUG-12:00 | 30.60 | 18.83 | 0.110475E+11 | 6464.63 | 30-AUG-21:40 | 22.07 | 17.86 |
September | 0.225302E+11 | 16939.77 | 30-SEP-12:40 | 20.40 | 12.36 | 0.106301E+11 | 6464.53 | 14-SEP-22:40 | 20.40 | 12.36 |
October | 0.225631E+11 | 16882.55 | 04-OCT-12:10 | 24.50 | 18.64 | 0.104144E+11 | 6464.26 | 20-OCT-22:10 | 14.13 | 11.86 |
November | 0.165944E+11 | 14613.29 | 04-NOV-12:30 | 17.80 | 12.61 | 0.857449E+10 | 6463.88 | 03-NOV-22:10 | 17.80 | 12.61 |
December | 0.151460E+11 | 13341.07 | 17-DEC-13:00 | 12.20 | 4.95 | 0.819973E+10 | 5293.07 | 04-DEC-23:10 | 12.20 | 4.95 |
Annual Sum or Average | 0.231682E+12 | 0.114689E+12 | ||||||||
Minimum of Months | 0.129936E+11 | 13265.38 | -7.0 | -8.3 | 0.739246E+10 | 4782.39 | -2.2 | -5.8 | ||
Maximum of Months | 0.270906E+11 | 18172.78 | 35.57 | 26.10 | 0.110475E+11 | 6464.63 | 28.90 | 21.37 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541748E+11 | 26836.76 | 19-JAN-22:20 | 5.60 | 1.07 | 0.266980E+11 | 18263.85 | 19-JAN-22:30 | 5.60 | 1.07 |
February | 0.501544E+11 | 26254.06 | 22-FEB-22:20 | 2.20 | -1.0 | 0.243096E+11 | 17973.65 | 22-FEB-22:30 | 2.20 | -0.9 |
March | 0.617436E+11 | 31480.61 | 03-MAR-22:00 | 10.60 | 6.45 | 0.286308E+11 | 19201.74 | 03-MAR-23:10 | 9.82 | 6.12 |
April | 0.646973E+11 | 40617.27 | 07-APR-20:10 | 21.32 | 14.59 | 0.288515E+11 | 19186.22 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.741248E+11 | 43743.07 | 30-MAY-20:03 | 19.90 | 15.53 | 0.314046E+11 | 19186.33 | 25-MAY-22:10 | 19.90 | 15.53 |
June | 0.799715E+11 | 48718.45 | 19-JUN-20:10 | 29.82 | 21.80 | 0.313906E+11 | 19186.28 | 30-JUN-21:10 | 20.00 | 18.86 |
July | 0.874161E+11 | 47925.48 | 10-JUL-20:10 | 28.12 | 20.24 | 0.325261E+11 | 19186.24 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.895197E+11 | 49302.63 | 04-AUG-20:10 | 32.20 | 24.15 | 0.326905E+11 | 19186.32 | 25-AUG-22:10 | 20.92 | 14.50 |
September | 0.790755E+11 | 46807.94 | 01-SEP-20:10 | 26.70 | 17.93 | 0.311628E+11 | 19186.28 | 28-SEP-22:10 | 14.90 | 10.57 |
October | 0.760936E+11 | 42467.76 | 04-OCT-20:10 | 18.62 | 16.03 | 0.315929E+11 | 19186.29 | 25-OCT-22:10 | 16.10 | 7.62 |
November | 0.616219E+11 | 34876.36 | 03-NOV-21:00 | 12.80 | 10.14 | 0.279997E+11 | 19183.74 | 02-NOV-21:10 | 12.80 | 10.14 |
December | 0.579048E+11 | 27038.02 | 04-DEC-23:00 | 8.30 | 7.50 | 0.274973E+11 | 18344.63 | 19-DEC-22:19 | 5.20 | 2.67 |
Annual Sum or Average | 0.836498E+12 | 0.354754E+12 | ||||||||
Minimum of Months | 0.501544E+11 | 26254.06 | 2.20 | -1.0 | 0.243096E+11 | 17973.65 | 2.20 | -0.9 | ||
Maximum of Months | 0.895197E+11 | 49302.63 | 32.20 | 24.15 | 0.326905E+11 | 19201.74 | 22.62 | 18.86 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64747890.11 | 4457.20 | 31-JAN-16:12 | -1.5 | -5.9 | 94299451.04 | 56.70 | 05-JAN-05:10 | -1.5 | -5.9 |
February | 0.135719E+09 | 4446.90 | 14-FEB-16:12 | 0.40 | -3.9 | 85967345.68 | 56.70 | 07-FEB-00:00 | 0.40 | -3.9 |
March | 0.557402E+09 | 4548.50 | 29-MAR-15:12 | 7.20 | 5.09 | 97334968.90 | 56.69 | 13-MAR-02:39 | 7.20 | 5.09 |
April | 0.101644E+10 | 4484.67 | 14-APR-15:12 | 9.63 | 5.52 | 94984635.21 | 56.69 | 01-APR-04:10 | 9.63 | 5.52 |
May | 0.177237E+10 | 4523.14 | 14-MAY-15:12 | 13.70 | 9.24 | 99278500.44 | 56.69 | 01-MAY-04:00 | 13.70 | 9.24 |
June | 0.256218E+10 | 4423.98 | 04-JUN-15:12 | 23.33 | 13.88 | 96394915.38 | 56.69 | 23-JUN-02:09 | 21.60 | 16.78 |
July | 0.303223E+10 | 4110.20 | 11-JUL-18:02 | 26.73 | 16.72 | 99573800.49 | 56.69 | 17-JUL-01:10 | 23.48 | 20.44 |
August | 0.321175E+10 | 4323.13 | 25-AUG-15:11 | 26.70 | 15.45 | 99662707.32 | 56.69 | 25-AUG-22:10 | 20.92 | 14.50 |
September | 0.218819E+10 | 4484.76 | 10-SEP-15:11 | 24.03 | 13.63 | 96159461.51 | 56.69 | 28-SEP-21:30 | 15.85 | 10.88 |
October | 0.162549E+10 | 4460.45 | 09-OCT-15:12 | 13.50 | 8.01 | 99023425.52 | 56.69 | 29-OCT-04:19 | 2.40 | 0.70 |
November | 0.319765E+09 | 4420.64 | 03-NOV-15:12 | 16.47 | 10.76 | 93753412.76 | 56.69 | 21-NOV-01:49 | 0.68 | -1.3 |
December | 0.110832E+09 | 4361.34 | 18-DEC-16:12 | 4.83 | 1.95 | 95142185.29 | 56.69 | 02-DEC-01:19 | 4.83 | 1.95 |
Annual Sum or Average | 0.165971E+11 | 0.115157E+10 | ||||||||
Minimum of Months | 64747890.11 | 4110.20 | -1.5 | -5.9 | 85967345.68 | 56.69 | -1.5 | -5.9 | ||
Maximum of Months | 0.321175E+10 | 4548.50 | 26.73 | 16.72 | 99662707.32 | 56.70 | 23.48 | 20.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17287554.22 | 4230.65 | 17-JAN-16:12 | 8.90 | 4.28 | 93259783.05 | 56.70 | 05-JAN-02:49 | 8.90 | 4.28 |
February | 39378023.01 | 4268.06 | 14-FEB-16:12 | 0.40 | -3.9 | 84684729.91 | 56.70 | 09-FEB-01:00 | 0.40 | -3.9 |
March | 0.299633E+09 | 4396.11 | 29-MAR-15:12 | 7.20 | 5.09 | 97140669.16 | 85.55 | 27-MAR-21:10 | 7.20 | 5.09 |
April | 0.706609E+09 | 4593.90 | 10-APR-20:41 | 13.68 | 6.84 | 97783721.71 | 93.26 | 07-APR-21:10 | 13.68 | 6.84 |
May | 0.131141E+10 | 4686.02 | 15-MAY-16:21 | 14.15 | 10.32 | 0.109975E+09 | 100.91 | 10-MAY-21:10 | 14.15 | 10.32 |
June | 0.193652E+10 | 4660.96 | 02-JUN-21:41 | 15.60 | 9.69 | 0.113521E+09 | 103.85 | 13-JUN-21:10 | 19.40 | 19.07 |
July | 0.269495E+10 | 4066.16 | 11-JUL-08:51 | 23.90 | 16.36 | 0.107306E+09 | 98.34 | 24-JUL-21:10 | 22.98 | 20.55 |
August | 0.271250E+10 | 4510.26 | 25-AUG-21:51 | 21.10 | 14.56 | 0.106620E+09 | 98.27 | 23-AUG-21:10 | 21.10 | 14.56 |
September | 0.140676E+10 | 4628.04 | 28-SEP-21:51 | 15.00 | 10.61 | 0.110111E+09 | 99.53 | 12-SEP-21:10 | 15.00 | 10.61 |
October | 0.849621E+09 | 4669.78 | 19-OCT-16:41 | 14.60 | 11.60 | 0.107265E+09 | 94.45 | 03-OCT-21:10 | 14.60 | 11.60 |
November | 0.143671E+09 | 4529.51 | 03-NOV-16:31 | 13.53 | 9.80 | 92928492.02 | 56.69 | 23-NOV-05:00 | -3.9 | -5.7 |
December | 20439983.38 | 4166.92 | 17-DEC-16:12 | 9.63 | 4.17 | 93783215.67 | 56.69 | 21-DEC-01:49 | 2.30 | -1.5 |
Annual Sum or Average | 0.121388E+11 | 0.121438E+10 | ||||||||
Minimum of Months | 17287554.22 | 4066.16 | 0.40 | -3.9 | 84684729.91 | 56.69 | -3.9 | -5.7 | ||
Maximum of Months | 0.271250E+10 | 4686.02 | 23.90 | 16.36 | 0.113521E+09 | 103.85 | 22.98 | 20.55 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44791874.18 | 419.65 | 30-JAN-12:10 | 1.20 | -2.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.20 | -2.3 |
February | 0.123796E+09 | 593.90 | 02-FEB-13:50 | 5.78 | -0.8 | 0.00 | 0.00 | 01-FEB-00:10 | 5.78 | -0.8 |
March | 0.221329E+09 | 707.29 | 03-MAR-13:30 | 14.70 | 8.33 | 0.00 | 0.00 | 01-MAR-00:10 | 14.70 | 8.33 |
April | 0.328077E+09 | 773.81 | 07-APR-12:30 | 26.15 | 15.90 | 0.00 | 0.00 | 01-APR-00:10 | 26.15 | 15.90 |
May | 0.492500E+09 | 577.50 | 30-MAY-12:40 | 29.80 | 17.86 | 0.00 | 0.00 | 01-MAY-00:10 | 29.80 | 17.86 |
June | 0.679139E+09 | 609.71 | 19-JUN-12:50 | 35.28 | 24.00 | 0.00 | 0.00 | 01-JUN-00:10 | 35.28 | 24.00 |
July | 0.857790E+09 | 610.99 | 10-JUL-13:00 | 32.20 | 20.45 | 0.00 | 0.00 | 01-JUL-00:10 | 32.20 | 20.45 |
August | 0.974359E+09 | 770.36 | 30-AUG-13:00 | 27.20 | 15.60 | 0.00 | 0.00 | 01-AUG-00:10 | 27.20 | 15.60 |
September | 0.775840E+09 | 867.85 | 28-SEP-12:30 | 23.05 | 14.08 | 0.00 | 0.00 | 01-SEP-00:10 | 23.05 | 14.08 |
October | 0.760069E+09 | 904.66 | 04-OCT-12:10 | 24.50 | 18.64 | 0.00 | 0.00 | 01-OCT-00:10 | 24.50 | 18.64 |
November | 0.250750E+09 | 800.39 | 02-NOV-12:40 | 15.40 | 8.14 | 0.00 | 0.00 | 01-NOV-00:10 | 15.40 | 8.14 |
December | 0.143133E+09 | 747.74 | 17-DEC-12:40 | 12.20 | 4.80 | 0.00 | 0.00 | 01-DEC-00:10 | 12.20 | 4.80 |
Annual Sum or Average | 0.565157E+10 | 0.00 | ||||||||
Minimum of Months | 44791874.18 | 419.65 | 1.20 | -2.3 | 0.00 | 0.00 | 1.20 | -2.3 | ||
Maximum of Months | 0.974359E+09 | 904.66 | 35.28 | 24.00 | 0.00 | 0.00 | 35.28 | 24.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93471280.24 | 1516.32 | 21-JAN-09:02 | 1.97 | 1.97 | 95062945.93 | 56.69 | 02-JAN-04:10 | 1.97 | 1.97 |
February | 77178199.97 | 1629.40 | 19-FEB-09:02 | 4.37 | 2.79 | 85831878.82 | 56.69 | 07-FEB-05:10 | 4.37 | 2.79 |
March | 0.251007E+09 | 1625.22 | 29-MAR-08:62 | 4.60 | 2.26 | 97147166.96 | 76.64 | 27-MAR-21:10 | 4.60 | 2.26 |
April | 0.446211E+09 | 1611.15 | 12-APR-08:62 | 5.78 | 0.39 | 96236006.70 | 84.22 | 07-APR-21:49 | 5.78 | 0.39 |
May | 0.678518E+09 | 1643.41 | 10-MAY-21:51 | 16.70 | 10.84 | 0.105359E+09 | 93.56 | 31-MAY-21:10 | 20.48 | 17.58 |
June | 0.847996E+09 | 1614.90 | 02-JUN-21:41 | 15.60 | 9.69 | 0.107968E+09 | 94.83 | 14-JUN-21:19 | 20.93 | 19.53 |
July | 0.111417E+10 | 1391.87 | 11-JUL-08:51 | 23.90 | 16.36 | 0.106357E+09 | 91.76 | 26-JUL-21:10 | 22.70 | 21.19 |
August | 0.104327E+10 | 1533.72 | 25-AUG-21:51 | 21.10 | 14.56 | 0.105165E+09 | 90.95 | 23-AUG-21:19 | 21.10 | 14.56 |
September | 0.698245E+09 | 1635.50 | 28-SEP-21:51 | 15.00 | 10.61 | 0.106254E+09 | 93.76 | 12-SEP-21:19 | 15.00 | 10.61 |
October | 0.491513E+09 | 1610.63 | 28-OCT-08:62 | 6.28 | 1.99 | 0.103153E+09 | 85.67 | 03-OCT-21:00 | 6.28 | 1.99 |
November | 0.260915E+09 | 1638.85 | 19-NOV-09:02 | 2.38 | 0.10 | 93880641.59 | 56.69 | 22-NOV-02:49 | -1.6 | -3.2 |
December | 0.112856E+09 | 1612.43 | 10-DEC-09:02 | 4.50 | 1.71 | 95451021.21 | 56.69 | 31-DEC-05:19 | -1.3 | -4.2 |
Annual Sum or Average | 0.611535E+10 | 0.119787E+10 | ||||||||
Minimum of Months | 77178199.97 | 1391.87 | 1.97 | 0.10 | 85831878.82 | 56.69 | -1.6 | -4.2 | ||
Maximum of Months | 0.111417E+10 | 1643.41 | 23.90 | 16.36 | 0.107968E+09 | 94.83 | 22.70 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74218212.33 | 4025.34 | 30-JAN-09:02 | -3.0 | -4.8 | 94319610.42 | 56.70 | 14-JAN-04:10 | -3.0 | -4.8 |
February | 0.135829E+09 | 4066.96 | 03-FEB-09:02 | -5.9 | -8.2 | 86238970.95 | 56.70 | 06-FEB-23:49 | -8.3 | -10.5 |
March | 0.509673E+09 | 4053.93 | 09-MAR-09:02 | 3.90 | 2.31 | 97444910.61 | 56.69 | 10-MAR-03:49 | 2.20 | 1.75 |
April | 0.102294E+10 | 4019.85 | 03-APR-08:62 | 5.68 | 1.87 | 95190006.52 | 56.69 | 01-APR-03:00 | 5.68 | 1.87 |
May | 0.181372E+10 | 4022.49 | 01-MAY-08:62 | 12.48 | 6.26 | 99393312.74 | 56.69 | 01-MAY-04:00 | 12.48 | 6.26 |
June | 0.243807E+10 | 3990.21 | 02-JUN-08:62 | 16.10 | 9.14 | 96433833.74 | 56.69 | 23-JUN-02:09 | 21.60 | 16.78 |
July | 0.299532E+10 | 3684.59 | 11-JUL-08:62 | 22.98 | 16.14 | 99579742.45 | 56.69 | 17-JUL-01:10 | 23.48 | 20.44 |
August | 0.318697E+10 | 3864.23 | 25-AUG-08:62 | 19.60 | 12.89 | 99688939.36 | 56.69 | 25-AUG-22:10 | 20.92 | 14.50 |
September | 0.219676E+10 | 3917.82 | 11-SEP-08:62 | 16.28 | 10.38 | 96251149.85 | 56.69 | 28-SEP-21:30 | 15.85 | 10.88 |
October | 0.157152E+10 | 4049.28 | 07-OCT-08:61 | 10.10 | 5.98 | 99146532.43 | 56.69 | 29-OCT-04:19 | 2.40 | 0.70 |
November | 0.393366E+09 | 4048.44 | 18-NOV-09:02 | 4.60 | 2.83 | 93989458.65 | 56.69 | 29-NOV-03:09 | 4.32 | 2.05 |
December | 0.143972E+09 | 4020.74 | 20-DEC-09:02 | 6.47 | 4.26 | 95315891.33 | 56.70 | 31-DEC-05:00 | -1.7 | -4.5 |
Annual Sum or Average | 0.164823E+11 | 0.115299E+10 | ||||||||
Minimum of Months | 74218212.33 | 3684.59 | -5.9 | -8.2 | 86238970.95 | 56.69 | -8.3 | -10.5 | ||
Maximum of Months | 0.318697E+10 | 4066.96 | 22.98 | 16.14 | 99688939.36 | 56.70 | 23.48 | 20.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22432875.45 | 2929.28 | 19-JAN-09:02 | 4.97 | 3.19 | 93169334.80 | 56.70 | 31-JAN-03:09 | -6.8 | -9.7 |
February | 38755587.49 | 3905.97 | 25-FEB-09:02 | -2.0 | -5.5 | 84716401.87 | 56.70 | 06-FEB-03:09 | -2.0 | -5.5 |
March | 0.248381E+09 | 3926.52 | 29-MAR-08:62 | 4.60 | 2.26 | 96929433.64 | 73.32 | 27-MAR-21:10 | 4.60 | 2.26 |
April | 0.731411E+09 | 4089.31 | 07-APR-08:51 | 19.40 | 13.16 | 96729736.51 | 90.16 | 07-APR-21:10 | 19.22 | 13.77 |
May | 0.139686E+10 | 4165.23 | 27-MAY-08:51 | 17.80 | 12.23 | 0.107660E+09 | 93.84 | 31-MAY-21:10 | 20.48 | 17.58 |
June | 0.186403E+10 | 4174.26 | 03-JUN-08:51 | 18.90 | 12.49 | 0.111050E+09 | 98.17 | 27-JUN-21:10 | 21.02 | 18.51 |
July | 0.262818E+10 | 3757.96 | 11-JUL-08:32 | 23.53 | 16.28 | 0.107550E+09 | 92.24 | 11-JUL-21:19 | 22.80 | 17.52 |
August | 0.264449E+10 | 4093.07 | 25-AUG-08:32 | 20.20 | 12.87 | 0.106820E+09 | 94.80 | 23-AUG-21:10 | 20.20 | 12.87 |
September | 0.144838E+10 | 4151.02 | 11-SEP-08:51 | 17.20 | 10.37 | 0.108035E+09 | 96.49 | 12-SEP-21:10 | 22.12 | 19.59 |
October | 0.830579E+09 | 3920.76 | 07-OCT-08:61 | 10.10 | 5.98 | 0.104328E+09 | 85.07 | 03-OCT-21:00 | 10.10 | 5.98 |
November | 0.193853E+09 | 3880.31 | 18-NOV-09:02 | 4.60 | 2.83 | 93168826.13 | 56.70 | 23-NOV-05:00 | -3.9 | -5.7 |
December | 38392302.81 | 3831.89 | 20-DEC-09:02 | 6.47 | 4.26 | 93776028.94 | 56.70 | 31-DEC-05:00 | -1.7 | -4.5 |
Annual Sum or Average | 0.120857E+11 | 0.120393E+10 | ||||||||
Minimum of Months | 22432875.45 | 2929.28 | -2.0 | -5.5 | 84716401.87 | 56.70 | -6.8 | -9.7 | ||
Maximum of Months | 0.264449E+10 | 4174.26 | 23.53 | 16.28 | 0.111050E+09 | 98.17 | 22.80 | 19.59 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 | -11.5 | 0.135872E+10 | 920.24 | 20-JAN-22:30 | 3.35 | 2.73 |
February | 12663459.01 | 433.54 | 20-FEB-13:00 | 9.40 | 4.36 | 0.130823E+10 | 951.85 | 22-FEB-23:19 | 2.20 | -0.8 |
March | 0.672942E+09 | 1951.16 | 27-MAR-18:03 | 18.80 | 14.35 | 0.160076E+10 | 951.85 | 16-MAR-04:49 | 18.80 | 14.35 |
April | 0.186848E+10 | 2707.17 | 07-APR-15:10 | 25.60 | 15.98 | 0.156578E+10 | 951.85 | 04-APR-03:20 | 25.60 | 15.98 |
May | 0.349942E+10 | 3037.65 | 31-MAY-18:30 | 21.15 | 18.39 | 0.162335E+10 | 951.84 | 25-MAY-22:10 | 21.15 | 18.39 |
June | 0.483596E+10 | 3441.24 | 19-JUN-18:13 | 32.03 | 22.95 | 0.157386E+10 | 951.84 | 20-JUN-21:00 | 20.60 | 17.37 |
July | 0.557521E+10 | 3258.01 | 10-JUL-18:13 | 29.63 | 20.43 | 0.161993E+10 | 951.84 | 24-JUL-21:40 | 23.53 | 21.66 |
August | 0.577363E+10 | 3325.89 | 24-AUG-15:10 | 33.90 | 20.15 | 0.162678E+10 | 951.84 | 30-AUG-22:10 | 21.70 | 17.67 |
September | 0.440970E+10 | 3109.29 | 01-SEP-14:10 | 31.02 | 17.36 | 0.156967E+10 | 951.84 | 12-SEP-21:49 | 21.78 | 19.45 |
October | 0.340383E+10 | 2999.32 | 04-OCT-15:10 | 23.72 | 19.12 | 0.162058E+10 | 951.84 | 02-OCT-22:10 | 23.72 | 19.12 |
November | 0.795313E+09 | 2105.53 | 04-NOV-12:30 | 17.80 | 12.61 | 0.153141E+10 | 951.85 | 17-NOV-03:20 | 8.30 | 7.50 |
December | 56655180.55 | 645.13 | 03-DEC-13:00 | 8.30 | 3.59 | 0.150494E+10 | 951.85 | 05-DEC-00:49 | 7.30 | 6.80 |
Annual Sum or Average | 0.309038E+11 | 0.185040E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.130823E+10 | 920.24 | 2.20 | -0.8 | ||
Maximum of Months | 0.577363E+10 | 3441.24 | 33.90 | 22.95 | 0.162678E+10 | 951.85 | 25.60 | 21.66 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35830763.22 | 4698.51 | 31-JAN-16:12 | -1.5 | -5.9 | 93249361.35 | 56.70 | 04-JAN-04:30 | -1.5 | -5.9 |
February | 79453046.64 | 4701.66 | 14-FEB-16:12 | 0.40 | -3.9 | 84925021.21 | 56.71 | 06-FEB-03:20 | 0.40 | -3.9 |
March | 0.381428E+09 | 4851.84 | 29-MAR-15:12 | 7.20 | 5.09 | 96178419.11 | 56.70 | 17-MAR-04:10 | 7.20 | 5.09 |
April | 0.815310E+09 | 4797.83 | 28-APR-15:12 | 14.23 | 9.69 | 94164888.75 | 56.70 | 21-APR-22:00 | 14.23 | 9.69 |
May | 0.159986E+10 | 4855.40 | 11-MAY-15:11 | 14.80 | 10.66 | 98950847.29 | 57.03 | 20-MAY-03:39 | 13.50 | 12.07 |
June | 0.259001E+10 | 4762.14 | 04-JUN-15:12 | 23.33 | 13.88 | 96333242.44 | 56.69 | 23-JUN-02:20 | 21.50 | 16.80 |
July | 0.319442E+10 | 4465.33 | 11-JUL-15:12 | 28.30 | 17.46 | 99565815.30 | 56.69 | 17-JUL-01:10 | 23.48 | 20.44 |
August | 0.336321E+10 | 4671.69 | 25-AUG-15:11 | 26.70 | 15.45 | 99635346.88 | 56.69 | 01-AUG-04:10 | 26.70 | 15.45 |
September | 0.207904E+10 | 4830.61 | 10-SEP-15:11 | 24.03 | 13.63 | 95980559.70 | 56.72 | 30-SEP-01:30 | 10.85 | 9.64 |
October | 0.132707E+10 | 4773.67 | 09-OCT-15:12 | 13.50 | 8.01 | 98544418.48 | 56.99 | 22-OCT-03:00 | 13.30 | 13.30 |
November | 0.163427E+09 | 4736.73 | 03-NOV-15:12 | 16.47 | 10.76 | 92257938.60 | 56.70 | 23-NOV-04:40 | -3.7 | -5.8 |
December | 42617852.73 | 4624.07 | 18-DEC-16:12 | 4.83 | 1.95 | 93750647.78 | 56.70 | 31-DEC-05:00 | -1.7 | -4.5 |
Annual Sum or Average | 0.156717E+11 | 0.114354E+10 | ||||||||
Minimum of Months | 35830763.22 | 4465.33 | -1.5 | -5.9 | 84925021.21 | 56.69 | -3.7 | -5.9 | ||
Maximum of Months | 0.336321E+10 | 4855.40 | 28.30 | 17.46 | 99635346.88 | 57.03 | 26.70 | 20.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5537834.73 | 4512.16 | 17-JAN-16:12 | 8.90 | 4.28 | 92363706.68 | 56.70 | 02-JAN-05:10 | 8.90 | 4.28 |
February | 17597497.36 | 4512.56 | 20-FEB-16:12 | 7.03 | 4.35 | 83804865.00 | 56.70 | 06-FEB-00:10 | 7.03 | 4.35 |
March | 0.176238E+09 | 4673.66 | 29-MAR-15:12 | 7.20 | 5.09 | 95803153.75 | 85.30 | 27-MAR-21:10 | 7.20 | 5.09 |
April | 0.529854E+09 | 4936.85 | 10-APR-20:41 | 13.68 | 6.84 | 97023762.83 | 94.05 | 07-APR-21:10 | 13.68 | 6.84 |
May | 0.118842E+10 | 5029.09 | 15-MAY-16:21 | 14.15 | 10.32 | 0.110155E+09 | 106.10 | 10-MAY-21:10 | 14.15 | 10.32 |
June | 0.205468E+10 | 5007.47 | 02-JUN-21:41 | 15.60 | 9.69 | 0.114275E+09 | 109.39 | 13-JUN-21:10 | 19.40 | 19.07 |
July | 0.290093E+10 | 4503.75 | 01-JUL-18:52 | 21.70 | 19.40 | 0.107288E+09 | 99.71 | 24-JUL-21:10 | 22.98 | 20.55 |
August | 0.289924E+10 | 4857.75 | 25-AUG-21:51 | 21.10 | 14.56 | 0.106533E+09 | 100.19 | 28-AUG-21:10 | 19.90 | 14.71 |
September | 0.136688E+10 | 4980.62 | 28-SEP-21:51 | 15.00 | 10.61 | 0.110198E+09 | 101.87 | 12-SEP-21:10 | 15.00 | 10.61 |
October | 0.617325E+09 | 5000.55 | 19-OCT-16:41 | 14.60 | 11.60 | 0.106622E+09 | 95.57 | 03-OCT-21:10 | 14.60 | 11.60 |
November | 44586366.83 | 4834.15 | 03-NOV-16:31 | 13.53 | 9.80 | 91349064.25 | 56.85 | 09-NOV-22:40 | 12.20 | 12.20 |
December | 4889108.65 | 3666.73 | 17-DEC-16:12 | 9.63 | 4.17 | 92479365.27 | 56.70 | 31-DEC-03:00 | -1.1 | -3.9 |
Annual Sum or Average | 0.118062E+11 | 0.120790E+10 | ||||||||
Minimum of Months | 4889108.65 | 3666.73 | 7.03 | 4.17 | 83804865.00 | 56.70 | -1.1 | -3.9 | ||
Maximum of Months | 0.290093E+10 | 5029.09 | 21.70 | 19.40 | 0.114275E+09 | 109.39 | 22.98 | 20.55 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167772E+09 | 2719.23 | 31-JAN-16:12 | -1.5 | -5.9 | 95232886.96 | 56.70 | 04-JAN-04:30 | -1.5 | -5.9 |
February | 0.242423E+09 | 2705.91 | 08-FEB-16:12 | -3.2 | -6.7 | 86916113.11 | 56.70 | 06-FEB-05:10 | -3.2 | -6.7 |
March | 0.428837E+09 | 2708.61 | 29-MAR-15:12 | 7.20 | 5.09 | 97198770.58 | 56.70 | 17-MAR-04:10 | 7.20 | 5.09 |
April | 0.585038E+09 | 2672.16 | 14-APR-15:12 | 9.63 | 5.52 | 94690385.19 | 56.69 | 01-APR-00:49 | 9.63 | 5.52 |
May | 0.909784E+09 | 2623.09 | 13-MAY-15:12 | 14.23 | 8.93 | 99051171.20 | 56.69 | 01-MAY-04:00 | 14.23 | 8.93 |
June | 0.136824E+10 | 2589.26 | 04-JUN-15:12 | 23.33 | 13.88 | 96295050.38 | 56.69 | 02-JUN-21:00 | 23.33 | 13.88 |
July | 0.180307E+10 | 2375.71 | 11-JUL-15:12 | 28.30 | 17.46 | 99567039.80 | 56.69 | 17-JUL-01:10 | 23.48 | 20.44 |
August | 0.198395E+10 | 2519.39 | 25-AUG-15:11 | 26.70 | 15.45 | 99636064.67 | 56.69 | 25-AUG-22:10 | 20.92 | 14.50 |
September | 0.145133E+10 | 2640.44 | 28-SEP-15:12 | 23.13 | 12.60 | 96097056.12 | 56.69 | 24-SEP-03:49 | 23.13 | 12.60 |
October | 0.124665E+10 | 2665.88 | 09-OCT-15:12 | 13.50 | 8.01 | 98979767.14 | 56.69 | 09-OCT-03:00 | 13.50 | 8.01 |
November | 0.382967E+09 | 2683.44 | 18-NOV-09:02 | 4.60 | 2.83 | 94283932.86 | 56.70 | 23-NOV-05:00 | -3.9 | -5.7 |
December | 0.265311E+09 | 2660.26 | 20-DEC-09:02 | 6.47 | 4.26 | 95907224.66 | 56.70 | 31-DEC-05:30 | -1.4 | -4.2 |
Annual Sum or Average | 0.108354E+11 | 0.115386E+10 | ||||||||
Minimum of Months | 0.167772E+09 | 2375.71 | -3.2 | -6.7 | 86916113.11 | 56.69 | -3.9 | -6.7 | ||
Maximum of Months | 0.198395E+10 | 2719.23 | 28.30 | 17.46 | 99636064.67 | 56.70 | 23.48 | 20.44 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304503E+11 | 15926.11 | 23-JAN-23:00 | 10.60 | 10.26 | 0.165485E+11 | 11343.75 | 23-JAN-23:19 | 10.40 | 10.17 |
February | 0.275221E+11 | 15489.18 | 05-FEB-22:00 | -11.1 | -12.8 | 0.148640E+11 | 11339.37 | 23-FEB-23:10 | 4.90 | 4.18 |
March | 0.342221E+11 | 19341.71 | 27-MAR-21:02 | 14.13 | 10.87 | 0.177569E+11 | 11349.25 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.364102E+11 | 21437.90 | 07-APR-21:10 | 19.22 | 13.77 | 0.178640E+11 | 11349.20 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.418026E+11 | 22604.20 | 31-MAY-21:05 | 20.48 | 17.58 | 0.190750E+11 | 11349.27 | 25-MAY-22:10 | 20.48 | 17.58 |
June | 0.443074E+11 | 24816.18 | 19-JUN-21:10 | 28.72 | 20.62 | 0.186902E+11 | 11349.30 | 30-JUN-21:10 | 20.00 | 18.86 |
July | 0.478252E+11 | 24269.86 | 10-JUL-21:10 | 27.12 | 20.12 | 0.192875E+11 | 11349.21 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.472954E+11 | 25061.16 | 04-AUG-21:10 | 31.55 | 23.93 | 0.193586E+11 | 11349.27 | 25-AUG-22:10 | 20.92 | 14.50 |
September | 0.417057E+11 | 23661.09 | 01-SEP-21:10 | 26.60 | 18.09 | 0.185342E+11 | 11349.24 | 18-SEP-22:10 | 17.12 | 11.49 |
October | 0.389965E+11 | 21127.71 | 05-OCT-21:52 | 18.90 | 17.46 | 0.186833E+11 | 11349.24 | 25-OCT-22:10 | 16.10 | 7.62 |
November | 0.331024E+11 | 18753.76 | 03-NOV-22:00 | 12.80 | 10.33 | 0.170694E+11 | 11345.05 | 02-NOV-21:19 | 12.80 | 10.33 |
December | 0.314818E+11 | 15729.71 | 04-DEC-23:00 | 8.30 | 7.50 | 0.168893E+11 | 11344.59 | 19-DEC-23:10 | 4.60 | 3.31 |
Annual Sum or Average | 0.455122E+12 | 0.214621E+12 | ||||||||
Minimum of Months | 0.275221E+11 | 15489.18 | -11.1 | -12.8 | 0.148640E+11 | 11339.37 | 4.60 | 3.31 | ||
Maximum of Months | 0.478252E+11 | 25061.16 | 31.55 | 23.93 | 0.193586E+11 | 11349.30 | 22.62 | 18.86 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328332E+11 | 18072.45 | 23-JAN-23:00 | 10.60 | 10.26 | 0.171839E+11 | 11344.94 | 20-JAN-22:10 | 10.60 | 10.26 |
February | 0.296285E+11 | 16973.14 | 23-FEB-23:00 | 5.00 | 4.23 | 0.154139E+11 | 11344.69 | 16-FEB-22:10 | 5.00 | 4.23 |
March | 0.364007E+11 | 20900.08 | 27-MAR-21:02 | 14.13 | 10.87 | 0.183120E+11 | 11349.25 | 27-MAR-21:19 | 13.87 | 10.67 |
April | 0.385082E+11 | 22784.20 | 07-APR-21:10 | 19.22 | 13.77 | 0.181965E+11 | 11349.20 | 07-APR-22:10 | 18.22 | 13.39 |
May | 0.441877E+11 | 23792.53 | 31-MAY-21:05 | 20.48 | 17.58 | 0.192088E+11 | 11349.28 | 25-MAY-22:10 | 20.48 | 17.58 |
June | 0.468243E+11 | 26021.54 | 19-JUN-21:10 | 28.72 | 20.62 | 0.187325E+11 | 11349.30 | 30-JUN-21:10 | 20.00 | 18.86 |
July | 0.505286E+11 | 25457.51 | 10-JUL-21:10 | 27.12 | 20.12 | 0.193046E+11 | 11349.21 | 11-JUL-22:10 | 22.62 | 17.84 |
August | 0.499399E+11 | 26260.15 | 04-AUG-21:10 | 31.55 | 23.93 | 0.193845E+11 | 11349.27 | 25-AUG-22:10 | 20.92 | 14.50 |
September | 0.440117E+11 | 24880.56 | 01-SEP-21:10 | 26.60 | 18.09 | 0.186265E+11 | 11349.24 | 18-SEP-22:10 | 17.12 | 11.49 |
October | 0.410151E+11 | 22376.36 | 05-OCT-21:10 | 18.90 | 17.74 | 0.189230E+11 | 11349.24 | 25-OCT-22:10 | 16.10 | 7.62 |
November | 0.351257E+11 | 20107.64 | 03-NOV-22:00 | 12.80 | 10.33 | 0.175702E+11 | 11345.23 | 02-NOV-21:19 | 12.80 | 10.33 |
December | 0.337732E+11 | 17707.95 | 04-DEC-23:00 | 8.30 | 7.50 | 0.175943E+11 | 11345.10 | 19-DEC-22:40 | 4.80 | 2.97 |
Annual Sum or Average | 0.482777E+12 | 0.218451E+12 | ||||||||
Minimum of Months | 0.296285E+11 | 16973.14 | 5.00 | 4.23 | 0.154139E+11 | 11344.69 | 4.80 | 2.97 | ||
Maximum of Months | 0.505286E+11 | 26260.15 | 31.55 | 23.93 | 0.193845E+11 | 11349.30 | 22.62 | 18.86 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439380E+11 | 26005.92 | 17-JAN-11:50 | 9.13 | 4.92 | 0.188404E+11 | 11320.19 | 14-JAN-18:00 | 9.13 | 4.92 |
February | 0.399597E+11 | 26843.47 | 19-FEB-11:50 | 7.88 | 4.27 | 0.170092E+11 | 11320.14 | 04-FEB-18:00 | 7.88 | 4.27 |
March | 0.475587E+11 | 28137.50 | 24-MAR-10:40 | 9.40 | 5.11 | 0.188757E+11 | 11320.10 | 18-MAR-17:00 | 9.40 | 5.11 |
April | 0.487802E+11 | 30441.57 | 08-APR-10:50 | 23.35 | 15.96 | 0.182638E+11 | 11320.07 | 08-APR-17:49 | 15.87 | 13.07 |
May | 0.536702E+11 | 31495.92 | 29-MAY-10:40 | 27.43 | 17.92 | 0.188732E+11 | 11320.06 | 20-MAY-17:49 | 27.43 | 17.92 |
June | 0.543786E+11 | 31794.35 | 19-JUN-10:40 | 35.17 | 23.99 | 0.182674E+11 | 11320.15 | 24-JUN-17:00 | 22.80 | 22.32 |
July | 0.577366E+11 | 32023.52 | 09-JUL-10:40 | 29.60 | 25.14 | 0.188696E+11 | 11320.15 | 01-JUL-17:40 | 29.60 | 25.14 |
August | 0.579212E+11 | 31787.31 | 13-AUG-10:40 | 29.63 | 19.31 | 0.188769E+11 | 11320.14 | 26-AUG-17:00 | 23.90 | 18.82 |
September | 0.530387E+11 | 31582.49 | 04-SEP-10:40 | 25.60 | 17.74 | 0.182630E+11 | 11320.16 | 09-SEP-17:00 | 21.70 | 19.78 |
October | 0.518471E+11 | 29915.93 | 12-OCT-10:40 | 19.03 | 15.82 | 0.188703E+11 | 11320.10 | 14-OCT-17:00 | 16.70 | 15.98 |
November | 0.456999E+11 | 28191.92 | 04-NOV-10:50 | 17.02 | 11.62 | 0.182571E+11 | 11320.12 | 25-NOV-18:00 | 2.20 | 1.27 |
December | 0.448913E+11 | 26702.33 | 17-DEC-11:50 | 11.93 | 4.48 | 0.188678E+11 | 11320.13 | 30-DEC-18:00 | 2.80 | 0.69 |
Annual Sum or Average | 0.599420E+12 | 0.222135E+12 | ||||||||
Minimum of Months | 0.399597E+11 | 26005.92 | 7.88 | 4.27 | 0.170092E+11 | 11320.06 | 2.20 | 0.69 | ||
Maximum of Months | 0.579212E+11 | 32023.52 | 35.17 | 25.14 | 0.188769E+11 | 11320.19 | 29.60 | 25.14 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 | -11.5 | 0.128708E+10 | 824.62 | 19-JAN-22:49 | 5.60 | 1.07 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -1.1 | -4.2 | 0.116977E+10 | 807.41 | 21-FEB-00:10 | 2.70 | 1.78 |
March | 0.281417E+09 | 3043.21 | 28-MAR-12:30 | 13.60 | 8.44 | 0.145824E+10 | 1007.40 | 27-MAR-23:49 | 13.60 | 8.44 |
April | 0.214373E+10 | 7463.31 | 08-APR-12:30 | 23.60 | 16.18 | 0.156618E+10 | 1007.40 | 25-APR-23:00 | 11.10 | 9.05 |
May | 0.610432E+10 | 9105.96 | 30-MAY-12:20 | 29.60 | 17.72 | 0.171345E+10 | 1007.42 | 09-MAY-03:09 | 29.60 | 17.72 |
June | 0.101837E+11 | 9835.69 | 19-JUN-14:10 | 34.22 | 23.63 | 0.166572E+10 | 1007.39 | 02-JUN-21:00 | 34.22 | 23.63 |
July | 0.130402E+11 | 9852.94 | 07-JUL-12:30 | 33.35 | 23.31 | 0.171446E+10 | 1007.39 | 24-JUL-21:40 | 23.53 | 21.66 |
August | 0.131301E+11 | 10001.63 | 16-AUG-12:50 | 31.93 | 25.44 | 0.172172E+10 | 1007.39 | 30-AUG-22:10 | 21.70 | 17.67 |
September | 0.835629E+10 | 9182.58 | 01-SEP-13:00 | 30.60 | 18.37 | 0.166074E+10 | 1007.40 | 30-SEP-01:00 | 11.10 | 9.88 |
October | 0.443952E+10 | 7531.26 | 04-OCT-13:00 | 25.00 | 18.54 | 0.168611E+10 | 1007.41 | 11-OCT-04:00 | 12.80 | 12.80 |
November | 0.424814E+09 | 4889.46 | 04-NOV-12:30 | 17.80 | 12.61 | 0.142401E+10 | 1007.40 | 10-NOV-00:20 | 12.20 | 12.20 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 | 2.86 | 0.129741E+10 | 839.48 | 04-DEC-23:10 | 8.22 | 7.50 |
Annual Sum or Average | 0.581041E+11 | 0.183649E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.116977E+10 | 807.41 | 2.70 | 1.07 | ||
Maximum of Months | 0.131301E+11 | 10001.63 | 34.22 | 25.44 | 0.172172E+10 | 1007.42 | 34.22 | 23.63 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -1.1 |
March | 6761685.26 | 1447.58 | 27-MAR-15:53 | 22.20 |
April | 83797250.18 | 4816.45 | 07-APR-13:00 | 26.70 |
May | 7711206.47 | 880.37 | 09-MAY-13:00 | 22.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 |
Annual Sum or Average | 98270141.91 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 83797250.18 | 4816.45 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115825E+10 | 2243.69 | 02-JAN-05:00 | -12.2 |
February | 0.947747E+09 | 2336.79 | 06-FEB-05:00 | -13.3 |
March | 0.261961E+09 | 1087.63 | 23-MAR-06:10 | -4.7 |
April | 66737209.48 | 594.73 | 02-APR-05:00 | 3.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 1878276.64 | 187.25 | 29-OCT-05:00 | 2.80 |
November | 0.202993E+09 | 1210.67 | 23-NOV-06:00 | -3.9 |
December | 0.656761E+09 | 1359.60 | 31-DEC-24:00 | -8.3 |
Annual Sum or Average | 0.329632E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.115825E+10 | 2336.79 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26236650.70 | 568.14 | 02-JAN-04:50 | -12.1 |
February | 35394396.07 | 593.11 | 06-FEB-05:00 | -13.3 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 |
Annual Sum or Average | 61631046.77 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 35394396.07 | 593.11 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.800188E+09 | 1134.06 | 02-JAN-05:00 | -12.2 |
February | 0.780929E+09 | 1306.00 | 06-FEB-05:00 | -13.3 |
March | 0.170141E+09 | 733.98 | 16-MAR-14:00 | 0.00 |
April | 26271590.36 | 347.99 | 21-APR-13:10 | 6.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.120832E+09 | 577.22 | 23-NOV-05:50 | -3.9 |
December | 0.365962E+09 | 772.61 | 31-DEC-24:00 | -8.3 |
Annual Sum or Average | 0.226433E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.800188E+09 | 1306.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90143398.88 | 26998.37 | 06-JAN-07:12 | -7.0 |
February | 16216017.38 | 21415.27 | 26-FEB-15:29 | -2.2 |
March | 3817022.49 | 647.49 | 16-MAR-14:00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 4024224.64 | 691.30 | 10-DEC-15:05 | 2.20 |
Annual Sum or Average | 0.114201E+09 | |||
Minimum of Months | 0.00 | 0.00 | -7.0 | |
Maximum of Months | 90143398.88 | 26998.37 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100832E+10 | 3963.61 | 14-JAN-16:12 | -6.1 |
February | 0.787150E+09 | 3948.72 | 06-FEB-16:12 | -7.0 |
March | 0.266751E+09 | 3524.13 | 16-MAR-15:12 | 0.77 |
April | 82969582.58 | 2305.72 | 21-APR-15:12 | 7.40 |
May | 3848714.69 | 1687.58 | 02-MAY-08:03 | 14.68 |
June | 265155.30 | 568.56 | 02-JUN-08:03 | 16.10 |
July | 197422.55 | 449.03 | 24-JUL-08:05 | 22.07 |
August | 74995.30 | 217.85 | 06-AUG-08:05 | 22.12 |
September | 1124773.28 | 1152.30 | 23-SEP-08:03 | 13.30 |
October | 23642528.07 | 1546.38 | 30-OCT-08:03 | 12.38 |
November | 0.284535E+09 | 3482.38 | 25-NOV-09:02 | -0.3 |
December | 0.647863E+09 | 3880.29 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.310674E+10 | |||
Minimum of Months | 74995.30 | 217.85 | -7.0 | |
Maximum of Months | 0.100832E+10 | 3963.61 | 22.12 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120446E+10 | 3874.90 | 14-JAN-16:12 | -6.1 |
February | 0.101431E+10 | 3869.97 | 06-FEB-16:12 | -7.0 |
March | 0.332807E+09 | 3563.98 | 22-MAR-08:62 | -2.0 |
April | 95079339.53 | 2403.69 | 21-APR-15:12 | 7.40 |
May | 17222862.76 | 1645.35 | 02-MAY-08:03 | 14.68 |
June | 27665913.56 | 1403.01 | 09-JUN-08:54 | 19.40 |
July | 25666274.62 | 337.88 | 15-JUL-21:26 | 23.05 |
August | 25058399.91 | 1513.66 | 25-AUG-08:54 | 20.60 |
September | 34063157.36 | 2455.78 | 23-SEP-18:43 | 15.60 |
October | 44646411.74 | 1707.77 | 07-OCT-08:03 | 10.10 |
November | 0.383667E+09 | 3505.58 | 24-NOV-09:02 | -1.5 |
December | 0.822699E+09 | 3801.83 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.402734E+10 | |||
Minimum of Months | 17222862.76 | 337.88 | -7.0 | |
Maximum of Months | 0.120446E+10 | 3874.90 | 23.05 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98007990.57 | 1219.10 | 14-JAN-16:12 | -6.1 |
February | 0.104597E+09 | 1225.80 | 06-FEB-16:12 | -7.0 |
March | 11907758.85 | 1089.25 | 16-MAR-15:12 | 0.77 |
April | 2920699.86 | 731.82 | 03-APR-08:03 | 5.68 |
May | 1796547.68 | 520.77 | 03-MAY-08:05 | 12.80 |
June | 3546821.09 | 363.10 | 02-JUN-08:54 | 16.10 |
July | 5719310.93 | 210.16 | 18-JUL-08:07 | 24.32 |
August | 4195977.89 | 181.84 | 15-AUG-08:07 | 26.70 |
September | 3702739.71 | 573.28 | 15-SEP-06:15 | 15.73 |
October | 2282338.36 | 745.01 | 07-OCT-15:15 | 12.40 |
November | 16433305.72 | 1075.32 | 22-NOV-16:12 | 0.60 |
December | 35106592.00 | 1167.70 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.290217E+09 | |||
Minimum of Months | 1796547.68 | 181.84 | -7.0 | |
Maximum of Months | 0.104597E+09 | 1225.80 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.999970E+09 | 3660.45 | 14-JAN-16:12 | -6.1 |
February | 0.759130E+09 | 3641.34 | 06-FEB-16:12 | -7.0 |
March | 0.278593E+09 | 3257.68 | 16-MAR-15:12 | 0.77 |
April | 85324359.55 | 2395.63 | 21-APR-15:12 | 7.40 |
May | 3731656.36 | 913.27 | 07-MAY-08:04 | 12.88 |
June | 329639.00 | 513.45 | 06-JUN-18:05 | 18.22 |
July | 1237.86 | 12.38 | 18-JUL-08:05 | 24.32 |
August | 53774.10 | 233.47 | 07-AUG-08:05 | 20.28 |
September | 690131.70 | 827.86 | 23-SEP-18:05 | 15.60 |
October | 24443651.64 | 1124.22 | 28-OCT-18:04 | 8.22 |
November | 0.269503E+09 | 3217.78 | 25-NOV-09:02 | -0.3 |
December | 0.641712E+09 | 3585.12 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.306348E+10 | |||
Minimum of Months | 1237.86 | 12.38 | -7.0 | |
Maximum of Months | 0.999970E+09 | 3660.45 | 24.32 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118716E+10 | 3569.63 | 14-JAN-16:12 | -6.1 |
February | 0.967810E+09 | 3561.83 | 06-FEB-16:12 | -7.0 |
March | 0.344073E+09 | 3179.36 | 17-MAR-15:12 | -0.6 |
April | 99543428.10 | 2489.80 | 21-APR-15:12 | 7.40 |
May | 16685304.04 | 1339.32 | 15-MAY-16:24 | 14.15 |
June | 24334594.38 | 439.78 | 02-JUN-21:44 | 15.60 |
July | 19177524.23 | 212.81 | 01-JUL-19:04 | 21.42 |
August | 16118003.87 | 460.25 | 19-AUG-21:16 | 20.73 |
September | 28897330.77 | 1219.32 | 23-SEP-18:43 | 15.60 |
October | 51243128.38 | 1582.01 | 19-OCT-16:43 | 14.60 |
November | 0.348442E+09 | 3162.04 | 23-NOV-19:02 | -0.7 |
December | 0.794396E+09 | 3501.67 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.389788E+10 | |||
Minimum of Months | 16118003.87 | 212.81 | -7.0 | |
Maximum of Months | 0.118716E+10 | 3569.63 | 21.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70137936.28 | 959.96 | 02-JAN-07:10 | -11.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 |
Annual Sum or Average | 70137936.28 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 70137936.28 | 959.96 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182123E+10 | 4337.94 | 14-JAN-16:12 | -6.1 |
February | 0.155568E+10 | 4308.48 | 06-FEB-19:02 | -8.2 |
March | 0.763321E+09 | 3973.02 | 22-MAR-08:62 | -2.0 |
April | 0.336756E+09 | 3456.59 | 03-APR-08:62 | 5.68 |
May | 39504017.93 | 1642.91 | 10-MAY-08:03 | 14.60 |
June | 555425.27 | 1349.37 | 09-JUN-08:03 | 18.48 |
July | 189812.58 | 546.85 | 24-JUL-08:05 | 22.07 |
August | 77844.19 | 419.96 | 06-AUG-08:05 | 22.12 |
September | 6595178.65 | 1487.94 | 29-SEP-08:03 | 15.37 |
October | 0.131624E+09 | 1738.43 | 29-OCT-08:62 | 6.88 |
November | 0.820305E+09 | 3860.59 | 23-NOV-09:02 | -1.5 |
December | 0.145177E+10 | 4227.04 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.692761E+10 | |||
Minimum of Months | 77844.19 | 419.96 | -8.2 | |
Maximum of Months | 0.182123E+10 | 4337.94 | 22.12 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209378E+10 | 4233.91 | 14-JAN-16:12 | -6.1 |
February | 0.188485E+10 | 4232.65 | 06-FEB-16:12 | -7.0 |
March | 0.898035E+09 | 3897.37 | 22-MAR-08:62 | -2.0 |
April | 0.362608E+09 | 3408.75 | 03-APR-08:62 | 5.68 |
May | 52471793.70 | 1484.26 | 25-MAY-21:54 | 16.10 |
June | 33168487.36 | 1915.24 | 02-JUN-08:53 | 16.10 |
July | 29005296.70 | 909.24 | 11-JUL-21:55 | 22.80 |
August | 29833496.41 | 721.42 | 25-AUG-08:54 | 20.60 |
September | 46581199.50 | 1939.53 | 19-SEP-08:53 | 18.30 |
October | 0.179375E+09 | 3395.47 | 29-OCT-08:62 | 6.88 |
November | 0.100728E+10 | 3802.27 | 24-NOV-09:02 | -1.5 |
December | 0.174070E+10 | 4145.44 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.835768E+10 | |||
Minimum of Months | 29005296.70 | 721.42 | -7.0 | |
Maximum of Months | 0.209378E+10 | 4233.91 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.604456E+09 | 2307.15 | 14-JAN-16:12 | -6.1 |
February | 0.473504E+09 | 2265.52 | 06-FEB-19:02 | -8.2 |
March | 0.228036E+09 | 2057.17 | 17-MAR-08:62 | -1.1 |
April | 93443340.37 | 1784.78 | 21-APR-15:12 | 7.40 |
May | 6528957.17 | 945.24 | 02-MAY-08:03 | 14.68 |
June | 521347.88 | 732.67 | 02-JUN-08:03 | 16.10 |
July | 151402.54 | 336.07 | 05-JUL-08:05 | 22.98 |
August | 168157.91 | 318.83 | 31-AUG-08:05 | 22.98 |
September | 875335.20 | 696.29 | 24-SEP-18:04 | 16.02 |
October | 21936803.33 | 921.98 | 01-OCT-15:13 | 13.90 |
November | 0.187945E+09 | 1941.57 | 25-NOV-09:02 | -0.3 |
December | 0.434770E+09 | 2220.72 | 31-DEC-19:02 | -5.7 |
Annual Sum or Average | 0.205234E+10 | |||
Minimum of Months | 151402.54 | 318.83 | -8.2 | |
Maximum of Months | 0.604456E+09 | 2307.15 | 22.98 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353454E+10 | 6206.69 | 02-JAN-07:10 | -11.6 |
February | 0.304845E+10 | 6251.88 | 06-FEB-07:10 | -13.2 |
March | 0.311428E+09 | 2880.64 | 23-MAR-06:10 | -4.7 |
April | 371958.58 | 89.18 | 02-APR-05:40 | 3.50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.524766E+09 | 3245.12 | 23-NOV-06:00 | -3.9 |
December | 0.178407E+10 | 3663.13 | 31-DEC-24:00 | -8.3 |
Annual Sum or Average | 0.920362E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.353454E+10 | 6251.88 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.204643E+11 | 19711.29 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.184774E+11 | 19711.29 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.205273E+11 | 19711.29 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.197704E+11 | 19711.29 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.204997E+11 | 19711.29 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.198611E+11 | 19711.29 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.204091E+11 | 19711.29 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.205352E+11 | 19711.29 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.197783E+11 | 19711.29 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.204564E+11 | 19711.29 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.198453E+11 | 19711.29 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.204091E+11 | 19711.29 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.241034E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.184774E+11 | 19711.29 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.205352E+11 | 19711.29 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101186E+10 | 974.63 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.913620E+09 | 974.63 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.101498E+10 | 974.63 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.977556E+09 | 974.63 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.101362E+10 | 974.63 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.982039E+09 | 974.63 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.100913E+10 | 974.63 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.101537E+10 | 974.63 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.977945E+09 | 974.63 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.101147E+10 | 974.63 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.981259E+09 | 974.63 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.100913E+10 | 974.63 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.119180E+11 | 0.101856E+11 | ||||
Minimum of Months | 0.913620E+09 | 974.63 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.101537E+10 | 974.63 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117174E+10 | 1128.63 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.105798E+10 | 1128.63 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.117535E+10 | 1128.63 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.113201E+10 | 1128.63 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.117377E+10 | 1128.63 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.113720E+10 | 1128.63 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.116858E+10 | 1128.63 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.117580E+10 | 1128.63 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.113246E+10 | 1128.63 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.117129E+10 | 1128.63 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.113630E+10 | 1128.63 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.116858E+10 | 1128.63 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.138011E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.105798E+10 | 1128.63 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.117580E+10 | 1128.63 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.247783E+10 | 2386.66 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.223726E+10 | 2386.66 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.248547E+10 | 2386.66 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.239382E+10 | 2386.66 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.248213E+10 | 2386.66 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.240480E+10 | 2386.66 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.247115E+10 | 2386.66 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.248642E+10 | 2386.66 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.239478E+10 | 2386.66 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.247688E+10 | 2386.66 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.240289E+10 | 2386.66 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.247115E+10 | 2386.66 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.291846E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.223726E+10 | 2386.66 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.248642E+10 | 2386.66 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.762439E+09 | 734.39 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.688413E+09 | 734.39 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.764789E+09 | 734.39 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.736588E+09 | 734.39 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.763761E+09 | 734.39 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.739966E+09 | 734.39 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.760382E+09 | 734.39 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.765082E+09 | 734.39 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.736882E+09 | 734.39 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.762145E+09 | 734.39 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.739379E+09 | 734.39 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.760382E+09 | 734.39 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.898021E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.688413E+09 | 734.39 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.765082E+09 | 734.39 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.265929E+10 | 2561.44 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.240110E+10 | 2561.44 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.266749E+10 | 2561.44 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.256913E+10 | 2561.44 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.266390E+10 | 2561.44 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.258091E+10 | 2561.44 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.265212E+10 | 2561.44 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.266851E+10 | 2561.44 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.257015E+10 | 2561.44 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.265826E+10 | 2561.44 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.257886E+10 | 2561.44 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.265212E+10 | 2561.44 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.313218E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.240110E+10 | 2561.44 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.266851E+10 | 2561.44 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.171043E+11 | 16474.99 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.154437E+11 | 16474.99 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.171571E+11 | 16474.99 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.165244E+11 | 16474.99 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.171340E+11 | 16474.99 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.166002E+11 | 16474.99 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.170582E+11 | 16474.99 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.171636E+11 | 16474.99 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.165310E+11 | 16474.99 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.170977E+11 | 16474.99 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.165870E+11 | 16474.99 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.170582E+11 | 16474.99 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.201459E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.154437E+11 | 16474.99 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.171636E+11 | 16474.99 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332597E+09 | 300.93 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.300367E+09 | 300.93 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.329954E+09 | 300.93 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.322251E+09 | 300.93 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.331275E+09 | 300.93 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.319694E+09 | 300.93 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.333875E+09 | 300.93 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.329954E+09 | 300.93 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.322338E+09 | 300.93 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.332554E+09 | 300.93 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.320973E+09 | 300.93 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.333919E+09 | 300.93 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.390975E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.300367E+09 | 300.93 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.333919E+09 | 300.93 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332688E+09 | 301.01 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.300450E+09 | 301.01 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.330044E+09 | 301.01 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.322339E+09 | 301.01 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.331366E+09 | 301.01 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.319782E+09 | 301.01 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.333967E+09 | 301.01 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.330044E+09 | 301.01 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.322426E+09 | 301.01 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.332644E+09 | 301.01 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.321060E+09 | 301.01 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.334010E+09 | 301.01 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.391082E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.300450E+09 | 301.01 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.334010E+09 | 301.01 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.195823E+10 | 1886.18 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.176811E+10 | 1886.18 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.196427E+10 | 1886.18 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.189184E+10 | 1886.18 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.196163E+10 | 1886.18 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.190052E+10 | 1886.18 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.195295E+10 | 1886.18 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.196502E+10 | 1886.18 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.189259E+10 | 1886.18 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.195748E+10 | 1886.18 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.189901E+10 | 1886.18 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.195295E+10 | 1886.18 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.230646E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.176811E+10 | 1886.18 | 0.00 | 0.00 | |
Maximum of Months | 0.196502E+10 | 1886.18 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332688E+09 | 301.01 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.300450E+09 | 301.01 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.330044E+09 | 301.01 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.322339E+09 | 301.01 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.331366E+09 | 301.01 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.319782E+09 | 301.01 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.333967E+09 | 301.01 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.330044E+09 | 301.01 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.322426E+09 | 301.01 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.332644E+09 | 301.01 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.321060E+09 | 301.01 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.334010E+09 | 301.01 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.391082E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.300450E+09 | 301.01 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.334010E+09 | 301.01 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466994E+10 | 4498.11 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.421653E+10 | 4498.11 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.468433E+10 | 4498.11 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.451160E+10 | 4498.11 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.467803E+10 | 4498.11 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.453229E+10 | 4498.11 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.465734E+10 | 4498.11 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.468613E+10 | 4498.11 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.451340E+10 | 4498.11 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.466814E+10 | 4498.11 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.452870E+10 | 4498.11 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.465734E+10 | 4498.11 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.550038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.421653E+10 | 4498.11 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.468613E+10 | 4498.11 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466994E+10 | 4498.11 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.421653E+10 | 4498.11 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.468433E+10 | 4498.11 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.451160E+10 | 4498.11 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.467803E+10 | 4498.11 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.453229E+10 | 4498.11 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.465734E+10 | 4498.11 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.468613E+10 | 4498.11 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.451340E+10 | 4498.11 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.466814E+10 | 4498.11 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.452870E+10 | 4498.11 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.465734E+10 | 4498.11 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.550038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.421653E+10 | 4498.11 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.468613E+10 | 4498.11 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124679E+10 | 1200.92 | 02-JAN-20:10 | 0.371477E+11 | 16602.84 | 01-JAN-07:10 |
February | 0.112574E+10 | 1200.92 | 01-FEB-20:10 | 0.335528E+11 | 16602.84 | 01-FEB-07:10 |
March | 0.125063E+10 | 1200.92 | 01-MAR-20:10 | 0.371477E+11 | 16602.84 | 01-MAR-07:10 |
April | 0.120452E+10 | 1200.92 | 03-APR-19:10 | 0.359494E+11 | 16602.84 | 01-APR-06:10 |
May | 0.124895E+10 | 1200.92 | 01-MAY-19:10 | 0.371477E+11 | 16602.84 | 01-MAY-06:10 |
June | 0.121004E+10 | 1200.92 | 01-JUN-19:10 | 0.359494E+11 | 16602.84 | 01-JUN-06:10 |
July | 0.124343E+10 | 1200.92 | 03-JUL-19:10 | 0.371477E+11 | 16602.84 | 01-JUL-06:10 |
August | 0.125111E+10 | 1200.92 | 01-AUG-19:10 | 0.371477E+11 | 16602.84 | 01-AUG-06:10 |
September | 0.120500E+10 | 1200.92 | 01-SEP-19:10 | 0.359494E+11 | 16602.84 | 01-SEP-06:10 |
October | 0.124631E+10 | 1200.92 | 02-OCT-19:10 | 0.371477E+11 | 16602.84 | 01-OCT-06:10 |
November | 0.120908E+10 | 1200.92 | 01-NOV-19:10 | 0.359494E+11 | 16602.84 | 01-NOV-06:10 |
December | 0.124343E+10 | 1200.92 | 01-DEC-20:10 | 0.371477E+11 | 16602.84 | 01-DEC-07:10 |
Annual Sum or Average | 0.146850E+11 | 0.437384E+12 | ||||
Minimum of Months | 0.112574E+10 | 1200.92 | 0.335528E+11 | 16602.84 | ||
Maximum of Months | 0.125111E+10 | 1200.92 | 0.371477E+11 | 16602.84 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.207249E+10 | 1996.23 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.187127E+10 | 1996.23 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.207888E+10 | 1996.23 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.200222E+10 | 1996.23 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.207608E+10 | 1996.23 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.201140E+10 | 1996.23 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.206690E+10 | 1996.23 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.207967E+10 | 1996.23 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.200302E+10 | 1996.23 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.207169E+10 | 1996.23 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.200981E+10 | 1996.23 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.206690E+10 | 1996.23 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.244103E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.187127E+10 | 1996.23 | 0.00 | 0.00 | |
Maximum of Months | 0.207967E+10 | 1996.23 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.204643E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.184774E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.205273E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.197704E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.204997E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.198611E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.204091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.205352E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.197783E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.204564E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.198453E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.204091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.241034E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.184774E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.205352E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.101186E+10 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690771E+09 |
February | 0.179968E+10 | 0.913620E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667083E+09 |
March | 0.199990E+10 | 0.101498E+10 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540699E+09 |
April | 0.192973E+10 | 0.977556E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 518064.26 | 0.351660E+09 |
May | 0.199475E+10 | 0.101362E+10 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3411154.84 | 0.212627E+09 |
June | 0.193394E+10 | 0.982039E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20297125.62 | 72505969.21 |
July | 0.199054E+10 | 0.100913E+10 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54429488.45 | 12943565.16 |
August | 0.199896E+10 | 0.101537E+10 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60566837.65 | 26900881.74 |
September | 0.192879E+10 | 0.977945E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8516549.35 | 0.108729E+09 |
October | 0.199148E+10 | 0.101147E+10 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 105502.04 | 0.285849E+09 |
November | 0.192552E+10 | 0.981259E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460861E+09 |
December | 0.199054E+10 | 0.100913E+10 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605931E+09 |
Annual Sum or Average | 0.234744E+11 | 0.119180E+11 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147845E+09 | 0.403656E+10 |
Minimum of Months | 0.179968E+10 | 0.913620E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12943565.16 |
Maximum of Months | 0.199990E+10 | 0.101537E+10 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60566837.65 | 0.690771E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.117174E+10 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268710E+09 |
February | 0.208403E+10 | 0.105798E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258753E+09 |
March | 0.231589E+10 | 0.117535E+10 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213903E+09 |
April | 0.223463E+10 | 0.113201E+10 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 284564.04 | 0.143502E+09 |
May | 0.230993E+10 | 0.117377E+10 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1474071.07 | 90848626.38 |
June | 0.223950E+10 | 0.113720E+10 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8226996.33 | 32195732.15 |
July | 0.230505E+10 | 0.116858E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21056619.72 | 7112662.08 |
August | 0.231480E+10 | 0.117580E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23431195.71 | 12880039.76 |
September | 0.223354E+10 | 0.113246E+10 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3521839.97 | 47444419.05 |
October | 0.230614E+10 | 0.117129E+10 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89448.27 | 0.117392E+09 |
November | 0.222975E+10 | 0.113630E+10 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185119E+09 |
December | 0.230505E+10 | 0.116858E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237580E+09 |
Annual Sum or Average | 0.271834E+11 | 0.138011E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58084735.11 | 0.161544E+10 |
Minimum of Months | 0.208403E+10 | 0.105798E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7112662.08 |
Maximum of Months | 0.231589E+10 | 0.117580E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23431195.71 | 0.268710E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.247783E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629688E+09 |
February | 0.440737E+09 | 0.223726E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604196E+09 |
March | 0.489771E+09 | 0.248547E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.35 | 0.495867E+09 |
April | 0.472586E+09 | 0.239382E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 718435.94 | 0.337545E+09 |
May | 0.488511E+09 | 0.248213E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3058325.02 | 0.221388E+09 |
June | 0.473617E+09 | 0.240480E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18058333.58 | 81223290.56 |
July | 0.487480E+09 | 0.247115E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47773959.88 | 18141178.34 |
August | 0.489542E+09 | 0.248642E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53890500.34 | 32094100.18 |
September | 0.472357E+09 | 0.239478E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7651487.01 | 0.118029E+09 |
October | 0.487709E+09 | 0.247688E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126190.15 | 0.279738E+09 |
November | 0.471555E+09 | 0.240289E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437313E+09 |
December | 0.487480E+09 | 0.247115E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553924E+09 |
Annual Sum or Average | 0.574883E+10 | 0.291846E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131277E+09 | 0.380915E+10 |
Minimum of Months | 0.440737E+09 | 0.223726E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18141178.34 |
Maximum of Months | 0.489771E+09 | 0.248642E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53890500.34 | 0.629688E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.762439E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359842E+09 |
February | 0.339028E+09 | 0.688413E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345785E+09 |
March | 0.376747E+09 | 0.764789E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7934.48 | 0.275194E+09 |
April | 0.363528E+09 | 0.736588E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 625066.84 | 0.177282E+09 |
May | 0.375778E+09 | 0.763761E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2137521.47 | 0.109394E+09 |
June | 0.364321E+09 | 0.739966E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11372606.02 | 38602985.33 |
July | 0.374985E+09 | 0.760382E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29036840.71 | 7811757.77 |
August | 0.376571E+09 | 0.765082E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32818779.94 | 15021896.08 |
September | 0.363352E+09 | 0.736882E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5292984.46 | 55523303.79 |
October | 0.375161E+09 | 0.762145E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 281388.34 | 0.139454E+09 |
November | 0.362735E+09 | 0.739379E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236078E+09 |
December | 0.374985E+09 | 0.760382E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313704E+09 |
Annual Sum or Average | 0.442217E+10 | 0.898021E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81573122.26 | 0.207369E+10 |
Minimum of Months | 0.339028E+09 | 0.688413E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7811757.77 |
Maximum of Months | 0.376747E+09 | 0.765082E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32818779.94 | 0.359842E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979653E+09 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933767E+09 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776046E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 644276.65 | 0.523427E+09 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 4168175.59 | 0.327350E+09 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 24607454.14 | 0.114114E+09 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 65201439.24 | 25356908.74 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 73565791.88 | 44798604.04 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 10442421.60 | 0.169090E+09 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 131239.71 | 0.410194E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674108E+09 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868175E+09 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.178761E+09 | 0.584608E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25356908.74 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 73565791.88 | 0.979653E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.265929E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151596E+10 |
February | 0.236489E+11 | 0.240110E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145820E+10 |
March | 0.262800E+11 | 0.266749E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119277E+10 |
April | 0.253579E+11 | 0.256913E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1142877.77 | 0.819070E+09 |
May | 0.262123E+11 | 0.266390E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7394933.70 | 0.562317E+09 |
June | 0.254132E+11 | 0.258091E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43659862.34 | 0.202499E+09 |
July | 0.261570E+11 | 0.265212E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115686E+09 | 44994256.60 |
August | 0.262677E+11 | 0.266851E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130524E+09 | 79497087.11 |
September | 0.253456E+11 | 0.257015E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18526057.94 | 0.297897E+09 |
October | 0.261693E+11 | 0.265826E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 232788.29 | 0.686236E+09 |
November | 0.253025E+11 | 0.257886E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104017E+10 |
December | 0.261570E+11 | 0.265212E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132660E+10 |
Annual Sum or Average | 0.308468E+12 | 0.313218E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317167E+09 | 0.922621E+10 |
Minimum of Months | 0.236489E+11 | 0.240110E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44994256.60 |
Maximum of Months | 0.262800E+11 | 0.266851E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130524E+09 | 0.151596E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.171043E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447967E+10 |
February | 0.702046E+11 | 0.154437E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431371E+10 |
March | 0.780153E+11 | 0.171571E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358711E+10 |
April | 0.752779E+11 | 0.165244E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3717943.12 | 0.241651E+10 |
May | 0.778146E+11 | 0.171340E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22749198.61 | 0.153840E+10 |
June | 0.754422E+11 | 0.166002E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132408E+09 | 0.545369E+09 |
July | 0.776503E+11 | 0.170582E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343136E+09 | 0.124055E+09 |
August | 0.779788E+11 | 0.171636E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378615E+09 | 0.219898E+09 |
September | 0.752414E+11 | 0.165310E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55600776.83 | 0.811008E+09 |
October | 0.776868E+11 | 0.170977E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 930431.88 | 0.198519E+10 |
November | 0.751137E+11 | 0.165870E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312095E+10 |
December | 0.776503E+11 | 0.170582E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398521E+10 |
Annual Sum or Average | 0.915726E+12 | 0.201459E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937157E+09 | 0.271271E+11 |
Minimum of Months | 0.702046E+11 | 0.154437E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124055E+09 |
Maximum of Months | 0.780153E+11 | 0.171636E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378615E+09 | 0.447967E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395983E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383441E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17377.37 | 0.311645E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 685335.90 | 0.200135E+09 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3629704.58 | 0.112633E+09 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21891135.58 | 25084376.43 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59186645.06 | 1356041.00 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59785185.57 | 7086488.28 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12549169.00 | 47185789.81 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 426668.98 | 0.149038E+09 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265883E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348347E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158171E+09 | 0.224782E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1356041.00 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59785185.57 | 0.395983E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391426E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378001E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309074E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 580445.25 | 0.203855E+09 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2967094.64 | 0.128016E+09 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19200404.98 | 48474040.36 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54605420.07 | 8892625.85 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57078653.33 | 15324054.17 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10216523.32 | 66350542.30 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 194053.67 | 0.160670E+09 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262162E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342860E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144843E+09 | 0.231510E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8892625.85 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57078653.33 | 0.391426E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.332597E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121931E+09 |
February | 0.00 | 0.300367E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126370E+09 |
March | 0.00 | 0.329954E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111535E+09 |
April | 0.00 | 0.322251E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80081292.11 |
May | 0.00 | 0.331275E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 124981.10 | 56119073.50 |
June | 0.00 | 0.319694E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1102171.47 | 26191674.98 |
July | 0.00 | 0.333875E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2578570.17 | 11187070.93 |
August | 0.00 | 0.329954E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3490613.23 | 13539979.46 |
September | 0.00 | 0.322338E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 273237.52 | 34477994.54 |
October | 0.00 | 0.332554E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67369153.10 |
November | 0.00 | 0.320973E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98586807.13 |
December | 0.00 | 0.333919E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118703E+09 |
Annual Sum or Average | 0.00 | 0.390975E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7569573.50 | 0.866092E+09 |
Minimum of Months | 0.00 | 0.300367E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11187070.93 |
Maximum of Months | 0.00 | 0.333919E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3490613.23 | 0.126370E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.332688E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110904E+09 |
February | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106514E+09 |
March | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86512256.39 |
April | 0.293479E+09 | 0.322339E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 164953.80 | 56295440.65 |
May | 0.303504E+09 | 0.331366E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 821688.31 | 33886751.62 |
June | 0.293842E+09 | 0.319782E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5302897.77 | 11357455.51 |
July | 0.303141E+09 | 0.333967E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15127008.04 | 2043277.43 |
August | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15935479.22 | 3726028.93 |
September | 0.293479E+09 | 0.322426E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2819311.74 | 16954928.06 |
October | 0.303322E+09 | 0.332644E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55301.34 | 43112962.64 |
November | 0.293661E+09 | 0.321060E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73928975.76 |
December | 0.303141E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97157224.09 |
Annual Sum or Average | 0.357224E+10 | 0.391082E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40226640.21 | 0.642393E+09 |
Minimum of Months | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2043277.43 |
Maximum of Months | 0.303685E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15935479.22 | 0.110904E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396133E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384428E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17359.79 | 0.312532E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 685567.65 | 0.200842E+09 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3620895.33 | 0.112985E+09 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21858192.90 | 25199058.24 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59111761.22 | 1374710.10 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59746057.16 | 7188245.26 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12536494.40 | 47425512.35 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 427965.25 | 0.149471E+09 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266580E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348855E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158004E+09 | 0.225301E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1374710.10 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59746057.16 | 0.396133E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391199E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378167E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310110E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 577720.54 | 0.203178E+09 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2893801.78 | 0.125582E+09 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19032855.77 | 46070710.98 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54312074.16 | 9569361.25 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56868387.67 | 16607214.81 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10103892.56 | 64370629.10 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 188758.40 | 0.157487E+09 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263074E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342772E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143977E+09 | 0.230818E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9569361.25 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56868387.67 | 0.391199E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.195823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508061E+09 |
February | 0.348285E+10 | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500783E+09 |
March | 0.387034E+10 | 0.196427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433533E+09 |
April | 0.373454E+10 | 0.189184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353400.64 | 0.294925E+09 |
May | 0.386038E+10 | 0.196163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2307913.08 | 0.185344E+09 |
June | 0.374269E+10 | 0.190052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13668025.96 | 64992593.14 |
July | 0.385223E+10 | 0.195295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36187612.93 | 14652885.05 |
August | 0.386853E+10 | 0.196502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40908247.79 | 25615164.52 |
September | 0.373273E+10 | 0.189259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5763930.00 | 96054978.75 |
October | 0.385404E+10 | 0.195748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67530.26 | 0.232046E+09 |
November | 0.372639E+10 | 0.189901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374766E+09 |
December | 0.385223E+10 | 0.195295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470979E+09 |
Annual Sum or Average | 0.454292E+11 | 0.230646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99256660.66 | 0.320175E+10 |
Minimum of Months | 0.348285E+10 | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14652885.05 |
Maximum of Months | 0.387034E+10 | 0.196502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40908247.79 | 0.508061E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393212E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380741E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15412.90 | 0.308668E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 664591.85 | 0.198561E+09 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3547464.36 | 0.112718E+09 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21440585.45 | 25552311.82 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58196712.22 | 1432651.30 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58919716.02 | 7243102.79 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12205837.84 | 47478468.29 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 402003.53 | 0.148824E+09 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261995E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344616E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155392E+09 | 0.223104E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1432651.30 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58919716.02 | 0.393212E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389205E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375875E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305361E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 565249.52 | 0.202153E+09 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2915235.51 | 0.128690E+09 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18867180.81 | 49847011.92 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53777029.20 | 9019666.05 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56313224.85 | 15294836.67 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9971220.39 | 66865006.90 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 181303.28 | 0.159750E+09 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257711E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339280E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142590E+09 | 0.229905E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9019666.05 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56313224.85 | 0.389205E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.332688E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205178E+09 |
February | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198676E+09 |
March | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7881.94 | 0.160029E+09 |
April | 0.293479E+09 | 0.322339E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 340007.29 | 0.102516E+09 |
May | 0.303504E+09 | 0.331366E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1816811.30 | 57826113.95 |
June | 0.293842E+09 | 0.319782E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10979887.85 | 13015228.31 |
July | 0.303141E+09 | 0.333967E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29789651.35 | 733807.92 |
August | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30161834.63 | 3715827.69 |
September | 0.293479E+09 | 0.322426E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6242707.24 | 24446772.85 |
October | 0.303322E+09 | 0.332644E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 204377.12 | 76814070.02 |
November | 0.293661E+09 | 0.321060E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137595E+09 |
December | 0.303141E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180272E+09 |
Annual Sum or Average | 0.357224E+10 | 0.391082E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79543158.72 | 0.116082E+10 |
Minimum of Months | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733807.92 |
Maximum of Months | 0.303685E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30161834.63 | 0.205178E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.466994E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102634E+10 |
February | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981400E+09 |
March | 0.461508E+11 | 0.468433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828544E+09 |
April | 0.445315E+11 | 0.451160E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 806916.24 | 0.567708E+09 |
May | 0.460320E+11 | 0.467803E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4578503.53 | 0.364171E+09 |
June | 0.446286E+11 | 0.453229E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27418980.37 | 0.129573E+09 |
July | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72256673.25 | 30069178.79 |
August | 0.461292E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81949302.88 | 51774288.19 |
September | 0.445099E+11 | 0.451340E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11977471.66 | 0.188016E+09 |
October | 0.459565E+11 | 0.466814E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 371456.24 | 0.445864E+09 |
November | 0.444343E+11 | 0.452870E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713980E+09 |
December | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909930E+09 |
Annual Sum or Average | 0.541708E+12 | 0.550038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199359E+09 | 0.623737E+10 |
Minimum of Months | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30069178.79 |
Maximum of Months | 0.461508E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81949302.88 | 0.102634E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.466994E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104461E+10 |
February | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997009E+09 |
March | 0.461508E+11 | 0.468433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845718E+09 |
April | 0.445315E+11 | 0.451160E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 718726.63 | 0.578649E+09 |
May | 0.460320E+11 | 0.467803E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4546716.21 | 0.369681E+09 |
June | 0.446286E+11 | 0.453229E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27092886.06 | 0.131494E+09 |
July | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71679036.38 | 30373425.85 |
August | 0.461292E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81220123.19 | 52435403.85 |
September | 0.445099E+11 | 0.451340E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11437404.57 | 0.191756E+09 |
October | 0.459565E+11 | 0.466814E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 235740.28 | 0.454307E+09 |
November | 0.444343E+11 | 0.452870E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729377E+09 |
December | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930650E+09 |
Annual Sum or Average | 0.541708E+12 | 0.550038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196931E+09 | 0.635606E+10 |
Minimum of Months | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30373425.85 |
Maximum of Months | 0.461508E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81220123.19 | 0.104461E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.124679E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996685E+09 |
February | 0.369574E+10 | 0.112574E+10 | 0.304050E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.948382E+09 |
March | 0.410691E+10 | 0.125063E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794708E+09 |
April | 0.396281E+10 | 0.120452E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 613509.39 | 0.537409E+09 |
May | 0.409635E+10 | 0.124895E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4064556.58 | 0.337559E+09 |
June | 0.397146E+10 | 0.121004E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 24188328.65 | 0.119406E+09 |
July | 0.408770E+10 | 0.124343E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 63940420.90 | 27501646.03 |
August | 0.410499E+10 | 0.125111E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 72496030.11 | 47342683.26 |
September | 0.396089E+10 | 0.120500E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 10102657.61 | 0.175801E+09 |
October | 0.408962E+10 | 0.124631E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 105962.92 | 0.422152E+09 |
November | 0.395417E+10 | 0.120908E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690411E+09 |
December | 0.408770E+10 | 0.124343E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888605E+09 |
Annual Sum or Average | 0.482060E+11 | 0.146850E+11 | 0.396352E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.175511E+09 | 0.598596E+10 |
Minimum of Months | 0.369574E+10 | 0.112574E+10 | 0.304050E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27501646.03 |
Maximum of Months | 0.410691E+10 | 0.125111E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 72496030.11 | 0.996685E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.207249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.860589E+09 |
February | 0.368610E+10 | 0.187127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829749E+09 |
March | 0.409620E+10 | 0.207888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708277E+09 |
April | 0.395248E+10 | 0.200222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601444.17 | 0.501572E+09 |
May | 0.408566E+10 | 0.207608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3982583.74 | 0.329317E+09 |
June | 0.396110E+10 | 0.201140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23699909.11 | 0.116796E+09 |
July | 0.407704E+10 | 0.206690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62664076.93 | 26875211.34 |
August | 0.409429E+10 | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71032206.95 | 46291246.11 |
September | 0.395056E+10 | 0.200302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9903554.83 | 0.171860E+09 |
October | 0.407896E+10 | 0.207169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104487.33 | 0.406127E+09 |
November | 0.394385E+10 | 0.200981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613598E+09 |
December | 0.407704E+10 | 0.206690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756018E+09 |
Annual Sum or Average | 0.480803E+11 | 0.244103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171988E+09 | 0.536707E+10 |
Minimum of Months | 0.368610E+10 | 0.187127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26875211.34 |
Maximum of Months | 0.409620E+10 | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71032206.95 | 0.860589E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 19711.29 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 19711.29 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 19711.29 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 19711.29 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 19711.29 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 19711.29 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 19711.29 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 19711.29 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 19711.29 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 19711.29 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 19711.29 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 19711.29 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 974.63 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 452.55 | 02-JAN-05:00 |
February | 1169.53 | 01-FEB-00:10 | 974.63 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 464.92 | 06-FEB-03:00 |
March | 1169.53 | 01-MAR-00:10 | 974.63 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 343.22 | 23-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 974.63 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 07-APR-13:00 | 242.01 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 974.63 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.45 | 30-MAY-13:00 | 187.97 | 01-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 974.63 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.94 | 19-JUN-12:00 | 100.90 | 03-JUN-03:00 |
July | 1169.53 | 01-JUL-00:10 | 974.63 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.64 | 07-JUL-12:00 | 51.39 | 01-JUL-21:55 |
August | 1169.53 | 01-AUG-00:10 | 974.63 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.87 | 24-AUG-15:00 | 83.44 | 08-AUG-05:00 |
September | 1169.53 | 01-SEP-00:10 | 974.63 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.76 | 01-SEP-14:00 | 139.78 | 30-SEP-01:00 |
October | 1169.53 | 01-OCT-23:10 | 974.63 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 | 04-OCT-13:00 | 243.51 | 09-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 974.63 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 334.32 | 24-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 974.63 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 389.30 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 974.63 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.39 | |||||
Maximum of Months | 1169.53 | 974.63 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 142.94 | 464.92 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 1128.63 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 174.66 | 02-JAN-05:00 |
February | 1354.32 | 01-FEB-00:10 | 1128.63 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 179.44 | 06-FEB-03:00 |
March | 1354.32 | 01-MAR-00:10 | 1128.63 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 134.35 | 23-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 1128.63 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 07-APR-13:00 | 96.38 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 1128.63 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.80 | 30-MAY-13:00 | 78.21 | 01-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 1128.63 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.47 | 19-JUN-12:00 | 46.91 | 03-JUN-03:00 |
July | 1354.32 | 01-JUL-00:10 | 1128.63 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 | 07-JUL-12:00 | 23.98 | 02-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 1128.63 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.18 | 24-AUG-15:00 | 39.68 | 08-AUG-05:00 |
September | 1354.32 | 01-SEP-00:10 | 1128.63 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 01-SEP-14:00 | 61.93 | 30-SEP-01:00 |
October | 1354.32 | 01-OCT-23:10 | 1128.63 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 25-OCT-11:00 | 100.09 | 09-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 1128.63 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 129.69 | 24-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 1128.63 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 150.45 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | |||||
Maximum of Months | 1354.32 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 55.47 | 179.44 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 2386.66 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 412.80 | 02-JAN-05:00 |
February | 286.42 | 01-FEB-00:10 | 2386.66 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 424.10 | 06-FEB-03:00 |
March | 286.42 | 01-MAR-00:10 | 2386.66 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 | 27-MAR-15:53 | 313.10 | 23-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 2386.66 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 07-APR-13:00 | 223.39 | 03-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 2386.66 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.35 | 30-MAY-13:00 | 184.56 | 01-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 2386.66 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.40 | 19-JUN-12:00 | 112.32 | 03-JUN-03:00 |
July | 286.42 | 01-JUL-00:10 | 2386.66 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.76 | 07-JUL-12:00 | 60.34 | 02-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 2386.66 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.05 | 24-AUG-15:00 | 95.54 | 08-AUG-05:00 |
September | 286.42 | 01-SEP-00:10 | 2386.66 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.67 | 01-SEP-14:00 | 148.79 | 24-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 2386.66 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.51 | 25-OCT-11:00 | 236.90 | 09-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 2386.66 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 304.94 | 24-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 2386.66 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 355.13 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.34 | |||||
Maximum of Months | 286.42 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 130.40 | 424.10 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 734.39 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 238.15 | 02-JAN-05:00 |
February | 220.32 | 01-FEB-00:10 | 734.39 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 244.68 | 06-FEB-03:00 |
March | 220.32 | 01-MAR-00:10 | 734.39 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 27-MAR-15:53 | 180.65 | 23-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 734.39 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 | 07-APR-13:00 | 127.38 | 03-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 734.39 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.30 | 30-MAY-13:00 | 98.92 | 01-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 734.39 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.23 | 19-JUN-12:00 | 58.10 | 03-JUN-03:00 |
July | 220.32 | 01-JUL-00:10 | 734.39 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.29 | 07-JUL-12:00 | 29.24 | 02-JUL-03:00 |
August | 220.32 | 01-AUG-00:10 | 734.39 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.88 | 24-AUG-15:00 | 49.07 | 08-AUG-05:00 |
September | 220.32 | 01-SEP-00:10 | 734.39 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 | 01-SEP-14:00 | 76.60 | 24-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 734.39 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 25-OCT-11:00 | 128.16 | 09-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 734.39 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 175.93 | 24-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 734.39 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 204.89 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | |||||
Maximum of Months | 220.32 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 75.23 | 244.68 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 614.56 | 02-JAN-05:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 628.85 | 06-FEB-03:00 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 476.84 | 23-MAR-06:00 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 38.98 | 07-APR-13:00 | 349.58 | 03-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 86.51 | 30-MAY-13:00 | 281.23 | 01-MAY-05:00 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 178.05 | 19-JUN-12:00 | 162.68 | 03-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 140.31 | 07-JUL-12:00 | 85.26 | 02-JUL-05:00 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 139.34 | 24-AUG-15:00 | 137.04 | 08-AUG-05:00 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 100.58 | 01-SEP-14:00 | 217.25 | 24-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 14.54 | 04-OCT-13:00 | 351.72 | 09-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 465.55 | 24-NOV-07:00 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 534.55 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 85.26 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 178.05 | 628.85 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2561.44 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1000.22 | 02-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 2561.44 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1027.63 | 06-FEB-03:00 |
March | 15368.40 | 01-MAR-00:10 | 2561.44 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 758.66 | 23-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 2561.44 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 07-APR-13:00 | 534.99 | 03-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 2561.44 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.51 | 30-MAY-13:00 | 415.50 | 01-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 2561.44 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.92 | 19-JUN-12:00 | 288.69 | 03-JUN-03:00 |
July | 15368.40 | 01-JUL-00:10 | 2561.44 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.96 | 07-JUL-12:00 | 151.29 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 2561.44 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.27 | 24-AUG-15:00 | 243.22 | 08-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 2561.44 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.49 | 01-SEP-14:00 | 361.03 | 30-SEP-01:00 |
October | 15368.40 | 01-OCT-23:10 | 2561.44 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.81 | 04-OCT-13:00 | 538.27 | 09-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 2561.44 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 738.90 | 24-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 2561.44 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 860.51 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2561.44 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.29 | |||||
Maximum of Months | 15368.40 | 2561.44 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 315.92 | 1027.63 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 16474.99 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2859.82 | 02-JAN-05:00 |
February | 45622.98 | 01-FEB-00:10 | 16474.99 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2947.87 | 06-FEB-03:00 |
March | 45622.98 | 01-MAR-00:10 | 16474.99 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2257.30 | 23-MAR-04:40 |
April | 45622.98 | 01-APR-00:10 | 16474.99 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.36 | 07-APR-13:00 | 1622.38 | 03-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 16474.99 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.65 | 30-MAY-13:00 | 1340.62 | 01-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 16474.99 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 902.81 | 19-JUN-12:00 | 807.39 | 03-JUN-03:00 |
July | 45622.98 | 01-JUL-00:10 | 16474.99 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 711.48 | 07-JUL-12:00 | 410.04 | 02-JUL-03:00 |
August | 45622.98 | 01-AUG-00:10 | 16474.99 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 706.59 | 24-AUG-15:00 | 690.27 | 08-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 16474.99 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.07 | 01-SEP-14:00 | 1049.73 | 30-SEP-01:00 |
October | 45622.98 | 01-OCT-23:10 | 16474.99 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.48 | 25-OCT-11:00 | 1673.91 | 29-OCT-07:00 |
November | 45622.98 | 01-NOV-00:10 | 16474.99 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2188.01 | 24-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 16474.99 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2509.32 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 16474.99 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.04 | |||||
Maximum of Months | 45622.98 | 16474.99 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 902.81 | 2947.87 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.85 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 271.03 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 27-MAR-15:57 | 200.38 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 07-APR-16:50 | 141.62 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.25 | 30-MAY-16:00 | 110.21 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.05 | 19-JUN-12:00 | 58.22 | 02-JUN-07:00 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.48 | 10-JUL-15:20 | 19.90 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.59 | 24-AUG-15:20 | 43.66 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.90 | 14-SEP-15:50 | 80.65 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 04-OCT-15:20 | 142.49 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 195.19 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 227.14 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 87.05 | 271.03 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.83 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 271.01 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 200.37 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 07-APR-16:50 | 141.61 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.24 | 30-MAY-16:00 | 110.20 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.04 | 19-JUN-12:00 | 86.61 | 03-JUN-18:50 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.47 | 10-JUL-15:20 | 56.54 | 01-JUL-18:45 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.59 | 24-AUG-15:20 | 48.34 | 28-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.90 | 14-SEP-15:50 | 80.64 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 | 25-OCT-09:51 | 142.48 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 195.18 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 227.13 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.34 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 87.04 | 271.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 300.93 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 72.66 | 31-JAN-09:50 |
February | 0.00 | 01-FEB-00:10 | 300.93 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 78.30 | 05-FEB-24:00 |
March | 0.00 | 01-MAR-00:10 | 300.93 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 63.49 | 23-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 300.93 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 47.98 | 03-APR-06:20 |
May | 0.00 | 01-MAY-00:10 | 300.93 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 30-MAY-13:00 | 39.92 | 01-MAY-05:20 |
June | 0.00 | 01-JUN-00:10 | 300.93 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 19-JUN-12:00 | 26.35 | 03-JUN-03:00 |
July | 0.00 | 01-JUL-00:10 | 300.93 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 07-JUL-12:00 | 16.35 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 300.93 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 | 24-AUG-15:00 | 23.18 | 08-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 300.93 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 | 01-SEP-14:00 | 33.04 | 24-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 300.93 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 50.47 | 29-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 300.93 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 62.65 | 24-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 300.93 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 66.26 | 31-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 300.93 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | |||||
Maximum of Months | 0.00 | 300.93 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 78.30 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 301.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 73.64 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 301.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 75.64 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 301.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 55.92 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 301.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 07-APR-16:50 | 39.53 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 301.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 30-MAY-16:00 | 30.76 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 301.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 19-JUN-12:00 | 18.33 | 02-JUN-21:20 |
July | 180.00 | 01-JUL-00:10 | 301.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 10-JUL-15:20 | 12.48 | 01-JUL-20:50 |
August | 180.00 | 01-AUG-00:10 | 301.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 24-AUG-16:00 | 12.19 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 301.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 | 14-SEP-15:50 | 22.51 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 301.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 25-OCT-09:51 | 40.35 | 29-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 301.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 54.47 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 301.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 63.39 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 | |||||
Maximum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 75.64 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.86 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 271.03 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 27-MAR-16:00 | 200.38 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 07-APR-16:50 | 146.52 | 03-APR-07:10 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.24 | 30-MAY-16:00 | 110.21 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.05 | 19-JUN-12:00 | 63.01 | 02-JUN-06:59 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.48 | 10-JUL-15:20 | 19.90 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.60 | 24-AUG-15:20 | 43.66 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.90 | 14-SEP-15:50 | 81.30 | 30-SEP-07:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 04-OCT-15:20 | 143.85 | 29-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 195.19 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 227.14 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 87.05 | 271.03 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.84 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 271.01 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 200.37 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 07-APR-16:50 | 146.08 | 03-APR-07:10 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.24 | 30-MAY-16:00 | 110.20 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.04 | 19-JUN-12:00 | 76.92 | 02-JUN-08:30 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.47 | 10-JUL-15:20 | 46.38 | 01-JUL-07:40 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.59 | 24-AUG-15:20 | 58.48 | 25-AUG-08:10 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.90 | 14-SEP-15:50 | 81.28 | 30-SEP-07:10 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 | 25-OCT-09:50 | 142.48 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 195.18 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 227.12 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.38 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 87.04 | 271.01 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1886.18 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 317.98 | 02-JAN-05:00 |
February | 2263.36 | 01-FEB-00:10 | 1886.18 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 333.85 | 06-FEB-03:00 |
March | 2263.36 | 01-MAR-00:10 | 1886.18 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 264.12 | 23-MAR-04:00 |
April | 2263.36 | 01-APR-00:10 | 1886.18 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.62 | 07-APR-13:00 | 194.82 | 03-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1886.18 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 | 30-MAY-13:00 | 158.83 | 01-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1886.18 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.98 | 19-JUN-12:00 | 92.01 | 03-JUN-03:00 |
July | 2263.36 | 01-JUL-00:10 | 1886.18 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.72 | 07-JUL-12:00 | 48.38 | 02-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1886.18 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.18 | 24-AUG-15:00 | 77.57 | 08-AUG-05:00 |
September | 2263.36 | 01-SEP-00:10 | 1886.18 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.34 | 01-SEP-14:00 | 122.77 | 24-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1886.18 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.85 | 04-OCT-13:00 | 198.36 | 09-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1886.18 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 252.75 | 24-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1886.18 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 282.59 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1886.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.38 | ||||
Maximum of Months | 2263.36 | 1886.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.98 | 333.85 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 264.39 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 271.56 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 | 27-MAR-16:00 | 200.89 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 | 07-APR-16:50 | 142.10 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.85 | 30-MAY-16:00 | 110.67 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.68 | 19-JUN-12:00 | 56.64 | 02-JUN-07:00 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 | 10-JUL-15:20 | 20.32 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.22 | 24-AUG-16:00 | 44.10 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.52 | 14-SEP-16:00 | 81.10 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 04-OCT-15:20 | 142.97 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 195.69 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 227.65 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.68 | 271.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 264.38 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 271.53 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 200.88 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 | 07-APR-16:50 | 142.09 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.85 | 30-MAY-16:00 | 110.66 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.67 | 19-JUN-12:00 | 94.15 | 03-JUN-18:50 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.09 | 10-JUL-15:20 | 62.35 | 01-JUL-18:40 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.21 | 24-AUG-15:20 | 50.90 | 28-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.52 | 14-SEP-15:50 | 81.09 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 25-OCT-09:51 | 142.96 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 195.68 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 227.63 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.90 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.67 | 271.53 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 301.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 135.27 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 301.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 138.94 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 301.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 27-MAR-16:00 | 102.78 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 301.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 07-APR-16:50 | 72.70 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 301.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 | 30-MAY-16:00 | 56.62 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 301.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 | 19-JUN-12:00 | 29.63 | 02-JUN-07:00 |
July | 180.00 | 01-JUL-00:10 | 301.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.42 | 10-JUL-15:20 | 10.39 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 301.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.58 | 24-AUG-15:20 | 22.56 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 301.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 14-SEP-15:50 | 41.49 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 301.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 | 04-OCT-15:20 | 73.15 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 301.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 100.12 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 301.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 116.47 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | |||||
Maximum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 | 138.94 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 4498.11 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 643.42 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 4498.11 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 660.97 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 4498.11 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 516.75 | 23-MAR-04:30 |
April | 26988.77 | 01-APR-00:10 | 4498.11 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.08 | 07-APR-13:00 | 380.63 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 4498.11 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.78 | 30-MAY-13:00 | 313.85 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 4498.11 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.00 | 19-JUN-12:00 | 186.79 | 03-JUN-03:00 |
July | 26988.77 | 01-JUL-00:10 | 4498.11 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.04 | 07-JUL-12:00 | 93.01 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 4498.11 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.97 | 24-AUG-15:00 | 157.62 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 4498.11 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.85 | 01-SEP-14:00 | 242.31 | 24-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 4498.11 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.69 | 25-OCT-11:00 | 383.77 | 29-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 4498.11 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 501.15 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 4498.11 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 570.49 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.01 | |||||
Maximum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 201.00 | 660.97 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 4498.11 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 643.47 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 4498.11 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 661.00 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 4498.11 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 523.05 | 23-MAR-04:30 |
April | 26988.77 | 01-APR-00:10 | 4498.11 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 07-APR-13:00 | 387.50 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 4498.11 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.78 | 30-MAY-13:00 | 317.71 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 4498.11 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.00 | 19-JUN-12:00 | 186.79 | 03-JUN-03:00 |
July | 26988.77 | 01-JUL-00:10 | 4498.11 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.04 | 07-JUL-12:00 | 96.01 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 4498.11 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.97 | 24-AUG-15:00 | 157.62 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 4498.11 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.85 | 01-SEP-14:00 | 246.20 | 24-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 4498.11 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 | 25-OCT-11:00 | 389.59 | 29-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 4498.11 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 507.60 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 4498.11 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 578.67 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.01 | |||||
Maximum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 201.00 | 661.00 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1200.92 | 02-JAN-20:10 | 15028.36 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 609.40 | 02-JAN-07:30 |
February | 2401.70 | 01-FEB-00:10 | 1200.92 | 01-FEB-20:10 | 15028.36 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 627.79 | 05-FEB-24:00 |
March | 2401.70 | 01-MAR-00:10 | 1200.92 | 01-MAR-20:10 | 15028.36 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 487.27 | 23-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 1200.92 | 03-APR-19:10 | 15028.36 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 38.19 | 07-APR-13:00 | 357.83 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1200.92 | 01-MAY-19:10 | 15028.36 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 86.60 | 30-MAY-13:00 | 288.16 | 01-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 1200.92 | 01-JUN-19:10 | 15028.36 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 179.90 | 19-JUN-12:00 | 167.34 | 03-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1200.92 | 03-JUL-19:10 | 15028.36 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 141.43 | 07-JUL-12:00 | 88.40 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1200.92 | 01-AUG-19:10 | 15028.36 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 140.47 | 24-AUG-15:20 | 141.25 | 08-AUG-05:00 |
September | 2401.70 | 01-SEP-00:10 | 1200.92 | 01-SEP-19:10 | 15028.36 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 100.97 | 01-SEP-14:00 | 222.99 | 24-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1200.92 | 02-OCT-19:10 | 15028.36 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 13.26 | 04-OCT-13:00 | 360.03 | 09-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1200.92 | 01-NOV-19:10 | 15028.36 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 476.00 | 24-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1200.92 | 01-DEC-20:10 | 15028.36 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 546.32 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1200.92 | 15028.36 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 88.40 | ||||||
Maximum of Months | 2401.70 | 1200.92 | 15028.36 | 22492.83 | 0.00 | 0.00 | 0.00 | 179.90 | 627.79 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1996.23 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 563.75 | 02-JAN-05:00 |
February | 2395.44 | 01-FEB-00:10 | 1996.23 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 579.12 | 06-FEB-03:00 |
March | 2395.44 | 01-MAR-00:10 | 1996.23 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 427.97 | 23-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1996.23 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.41 | 07-APR-13:00 | 308.99 | 01-APR-04:00 |
May | 2395.44 | 01-MAY-00:10 | 1996.23 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.79 | 30-MAY-13:00 | 267.40 | 01-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1996.23 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.10 | 19-JUN-12:00 | 163.74 | 03-JUN-03:00 |
July | 2395.44 | 01-JUL-00:10 | 1996.23 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.47 | 07-JUL-12:00 | 86.51 | 02-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1996.23 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.51 | 24-AUG-15:00 | 138.18 | 08-AUG-05:00 |
September | 2395.44 | 01-SEP-00:10 | 1996.23 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 01-SEP-14:00 | 211.53 | 24-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1996.23 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 | 04-OCT-13:00 | 323.99 | 09-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1996.23 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 416.85 | 24-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1996.23 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 485.20 | 31-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | ||||
Maximum of Months | 2395.44 | 1996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.10 | 579.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 25092.96 | 11-JAN-21:50 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22298.75 | 14-FEB-22:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20907.10 | 22-MAR-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17106.74 | 12-APR-06:00 | 8945.92 | 8760.57 | 5069.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16286.41 | 31-MAY-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19110.24 | 20-JUN-19:51 | 89459.16 | 197112.92 | 96325.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21504.16 | 21-JUL-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23865.67 | 18-AUG-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26297.32 | 07-SEP-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27672.31 | 05-OCT-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27045.47 | 03-NOV-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26588.01 | 31-DEC-21:00 | 7667.93 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16286.41 | 7667.93 | 8760.57 | 5069.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27672.31 | 89459.16 | 197112.92 | 96325.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3085.00 | 17-JAN-13:20 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.28 |
February | 2532.80 | 02-FEB-13:40 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.95 |
March | 3666.02 | 03-MAR-13:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.42 |
April | 4253.55 | 07-APR-12:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | 0.00 |
May | 3787.32 | 30-MAY-12:50 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 68.32 | 0.00 |
June | 4187.39 | 19-JUN-13:10 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 123.39 | 0.00 |
July | 4199.61 | 07-JUL-12:40 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 104.56 | 0.00 |
August | 4845.20 | 18-AUG-12:40 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 103.70 | 0.00 |
September | 4923.59 | 05-SEP-12:50 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 31.62 | 0.00 |
October | 5027.77 | 04-OCT-13:00 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 | 0.00 |
November | 3839.76 | 04-NOV-12:30 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.10 |
December | 3559.08 | 17-DEC-13:00 | 389.84 | 324.88 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2532.80 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5027.77 | 389.84 | 324.88 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 123.39 | 222.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1231.00 | 19-JAN-22:00 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.34 |
February | 1211.47 | 22-FEB-22:00 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.65 |
March | 1452.05 | 27-MAR-20:10 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 |
April | 2061.62 | 07-APR-19:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 |
May | 2446.37 | 30-MAY-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 |
June | 2663.65 | 19-JUN-19:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 | 0.00 |
July | 2625.87 | 12-JUL-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 0.00 |
August | 2637.75 | 15-AUG-18:15 | 2106.72 | 2006.45 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 | 0.00 |
September | 2444.08 | 06-SEP-19:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 |
October | 2159.39 | 04-OCT-19:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 |
November | 1606.47 | 03-NOV-21:00 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.81 |
December | 1241.24 | 19-DEC-22:00 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1211.47 | 1053.36 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2663.65 | 2106.72 | 2006.45 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 | 101.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 959.10 | 24-JAN-22:00 | 254.59 | 2121.48 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.09 |
February | 915.42 | 23-FEB-22:00 | 254.59 | 2121.48 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.78 |
March | 1095.39 | 27-MAR-21:00 | 254.59 | 2121.48 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.92 |
April | 1849.87 | 10-APR-20:00 | 445.54 | 4773.32 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.02 |
May | 2762.32 | 30-MAY-19:50 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.57 |
June | 3196.87 | 19-JUN-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 63.06 | 0.00 |
July | 3115.06 | 10-JUL-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 0.00 |
August | 3164.37 | 04-AUG-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 85.46 | 0.00 |
September | 2882.69 | 01-SEP-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 28.47 | 0.00 |
October | 2285.90 | 05-OCT-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.48 |
November | 1235.92 | 03-NOV-21:00 | 254.59 | 2121.48 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.82 |
December | 981.87 | 04-DEC-22:00 | 254.59 | 2121.48 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 915.42 | 222.77 | 2121.48 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3196.87 | 445.54 | 4773.32 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 85.46 | 203.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 565.60 | 23-JAN-21:50 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.34 |
February | 376.20 | 23-FEB-22:00 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.26 |
March | 667.23 | 27-MAR-20:15 | 391.68 | 1305.57 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 |
April | 779.94 | 07-APR-20:00 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 |
May | 1040.32 | 30-MAY-18:20 | 342.72 | 1305.57 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 |
June | 1496.81 | 19-JUN-18:13 | 514.08 | 1958.36 | 688.24 | 0.00 | 0.00 | 0.00 | 0.00 | 48.32 | 0.00 |
July | 1421.97 | 10-JUL-18:13 | 514.08 | 1958.36 | 688.24 | 0.00 | 0.00 | 0.00 | 0.00 | 34.09 | 0.00 |
August | 1464.96 | 04-AUG-19:20 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 53.59 | 0.00 |
September | 1156.07 | 01-SEP-20:00 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | 0.00 |
October | 817.08 | 05-OCT-20:20 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.08 |
November | 689.77 | 03-NOV-21:00 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 |
December | 575.22 | 04-DEC-22:00 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 376.20 | 171.36 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1496.81 | 514.08 | 1958.36 | 688.24 | 0.00 | 0.00 | 0.00 | 0.00 | 53.59 | 109.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36755.21 | 23-JAN-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 216.05 |
February | 36558.90 | 01-FEB-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 283.07 |
March | 37802.22 | 27-MAR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 119.47 |
April | 38467.64 | 07-APR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 33.86 |
May | 38667.62 | 30-MAY-19:51 | 7056.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 59.68 |
June | 39307.21 | 19-JUN-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 86.10 | 0.00 |
July | 39147.17 | 10-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 61.89 | 0.00 |
August | 39328.19 | 04-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 116.68 | 0.00 |
September | 38942.11 | 01-SEP-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 38.87 | 0.00 |
October | 38296.56 | 04-OCT-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 76.09 |
November | 37620.66 | 03-NOV-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 170.48 |
December | 36813.39 | 04-DEC-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 229.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36558.90 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39328.19 | 7056.00 | 4536.05 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 116.68 | 283.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18172.78 | 06-JAN-07:11 | 68304.00 | 14230.23 | 6096.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.00 |
February | 14402.76 | 26-FEB-15:21 | 30736.80 | 5122.88 | 2743.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 655.77 |
March | 13265.38 | 03-MAR-13:10 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.36 |
April | 15228.82 | 08-APR-12:20 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
May | 13406.26 | 29-MAY-12:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 125.58 | 0.00 |
June | 13532.88 | 19-JUN-12:40 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 288.78 | 0.00 |
July | 13847.40 | 08-JUL-12:00 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 207.98 | 0.00 |
August | 15707.57 | 13-AUG-12:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 166.92 | 0.00 |
September | 16939.77 | 30-SEP-12:40 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.68 |
October | 16882.55 | 04-OCT-12:10 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 | 0.00 |
November | 14613.29 | 04-NOV-12:30 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.83 |
December | 13341.07 | 17-DEC-13:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13265.38 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18172.78 | 68304.00 | 14230.23 | 6096.46 | 0.00 | 0.00 | 0.00 | 0.00 | 288.78 | 803.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26836.76 | 19-JAN-22:20 | 45622.98 | 10983.32 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1413.41 |
February | 26254.06 | 22-FEB-22:20 | 45622.98 | 10983.32 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.49 |
March | 31480.61 | 03-MAR-22:00 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1048.38 |
April | 40617.27 | 07-APR-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.40 |
May | 43743.07 | 30-MAY-20:03 | 121661.28 | 43933.30 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.20 |
June | 48718.45 | 19-JUN-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 423.68 | 0.00 |
July | 47925.48 | 10-JUL-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 300.82 | 0.00 |
August | 49302.63 | 04-AUG-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 591.75 | 0.00 |
September | 46807.94 | 01-SEP-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 197.26 | 0.00 |
October | 42467.76 | 04-OCT-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.44 |
November | 34876.36 | 03-NOV-21:00 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 864.05 |
December | 27038.02 | 04-DEC-23:00 | 45622.98 | 10983.32 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1172.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26254.06 | 40553.76 | 10983.32 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49302.63 | 121661.28 | 43933.30 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 591.75 | 1693.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4457.20 | 31-JAN-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.24 |
February | 4446.90 | 14-FEB-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.98 |
March | 4548.50 | 29-MAR-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.98 |
April | 4484.67 | 14-APR-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.36 |
May | 4523.14 | 14-MAY-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.74 |
June | 4423.98 | 04-JUN-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 0.00 |
July | 4110.20 | 11-JUL-18:02 | 831.60 | 2556.97 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 28.25 | 0.00 |
August | 4323.13 | 25-AUG-15:11 | 680.40 | 938.51 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 26.61 | 0.00 |
September | 4484.76 | 10-SEP-15:11 | 378.00 | 1106.11 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 | 0.00 |
October | 4460.45 | 09-OCT-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.62 |
November | 4420.64 | 03-NOV-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 |
December | 4361.34 | 18-DEC-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4110.20 | 324.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4548.50 | 831.60 | 2556.97 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 28.25 | 179.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4230.65 | 17-JAN-16:12 | 583.20 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.12 |
February | 4268.06 | 14-FEB-16:12 | 583.20 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.53 |
March | 4396.11 | 29-MAR-15:12 | 583.20 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.00 |
April | 4593.90 | 10-APR-20:41 | 1602.00 | 4261.12 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.69 |
May | 4686.02 | 15-MAY-16:21 | 972.00 | 1340.58 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.72 |
June | 4660.96 | 02-JUN-21:41 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.39 |
July | 4066.16 | 11-JUL-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
August | 4510.26 | 25-AUG-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.60 |
September | 4628.04 | 28-SEP-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.39 |
October | 4669.78 | 19-OCT-16:41 | 972.00 | 1340.58 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.30 |
November | 4529.51 | 03-NOV-16:31 | 874.80 | 1206.52 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.13 |
December | 4166.92 | 17-DEC-16:12 | 324.00 | 947.98 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4066.16 | 324.00 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | |
Maximum of Months | 4686.02 | 1800.00 | 4261.12 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 419.65 | 30-JAN-12:10 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 |
February | 593.90 | 02-FEB-13:50 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 |
March | 707.29 | 03-MAR-13:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.72 |
April | 773.81 | 07-APR-12:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
May | 577.50 | 30-MAY-12:40 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 0.00 |
June | 609.71 | 19-JUN-12:50 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 |
July | 610.99 | 10-JUL-13:00 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.15 | 0.00 |
August | 770.36 | 30-AUG-13:00 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
September | 867.85 | 28-SEP-12:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 |
October | 904.66 | 04-OCT-12:10 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 |
November | 800.39 | 02-NOV-12:40 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.19 |
December | 747.74 | 17-DEC-12:40 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 419.65 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 904.66 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 53.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1516.32 | 21-JAN-09:02 | 270.00 | 842.83 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.85 |
February | 1629.40 | 19-FEB-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.91 |
March | 1625.22 | 29-MAR-08:62 | 216.00 | 794.67 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.56 |
April | 1611.15 | 12-APR-08:62 | 216.00 | 794.67 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 |
May | 1643.41 | 10-MAY-21:51 | 1800.00 | 2016.77 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.20 |
June | 1614.90 | 02-JUN-21:41 | 1800.00 | 2016.77 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 |
July | 1391.87 | 11-JUL-08:51 | 360.00 | 1324.45 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 |
August | 1533.72 | 25-AUG-21:51 | 1800.00 | 2016.77 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 |
September | 1635.50 | 28-SEP-21:51 | 1800.00 | 2016.77 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 |
October | 1610.63 | 28-OCT-08:62 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.76 |
November | 1638.85 | 19-NOV-09:02 | 270.00 | 842.83 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.86 |
December | 1612.43 | 10-DEC-09:02 | 270.00 | 842.83 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1391.87 | 216.00 | 794.67 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | |
Maximum of Months | 1643.41 | 1800.00 | 2016.77 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4025.34 | 30-JAN-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.29 |
February | 4066.96 | 03-FEB-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.81 |
March | 4053.93 | 09-MAR-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.25 |
April | 4019.85 | 03-APR-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.91 |
May | 4022.49 | 01-MAY-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.55 |
June | 3990.21 | 02-JUN-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.59 |
July | 3684.59 | 11-JUL-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
August | 3864.23 | 25-AUG-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 |
September | 3917.82 | 11-SEP-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.81 |
October | 4049.28 | 07-OCT-08:61 | 378.00 | 1877.03 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.95 |
November | 4048.44 | 18-NOV-09:02 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.46 |
December | 4020.74 | 20-DEC-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3684.59 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4066.96 | 378.00 | 1877.03 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 207.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2929.28 | 19-JAN-09:02 | 216.00 | 1263.97 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.38 |
February | 3905.97 | 25-FEB-09:02 | 324.00 | 1608.69 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.99 |
March | 3926.52 | 29-MAR-08:62 | 216.00 | 1263.97 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.79 |
April | 4089.31 | 07-APR-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 |
May | 4165.23 | 27-MAY-08:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.95 |
June | 4174.26 | 03-JUN-08:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.01 |
July | 3757.96 | 11-JUL-08:32 | 180.00 | 1053.31 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 |
August | 4093.07 | 25-AUG-08:32 | 180.00 | 1053.31 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.42 |
September | 4151.02 | 11-SEP-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.39 |
October | 3920.76 | 07-OCT-08:61 | 378.00 | 1876.81 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.84 |
November | 3880.31 | 18-NOV-09:02 | 324.00 | 1608.69 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.58 |
December | 3831.89 | 20-DEC-09:02 | 216.00 | 1263.97 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2929.28 | 180.00 | 1053.31 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 | |
Maximum of Months | 4174.26 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 3520.78 | 1257.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.80 |
February | 433.54 | 20-FEB-13:00 | 754.45 | 628.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.06 |
March | 1951.16 | 27-MAR-18:03 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.19 |
April | 2707.17 | 07-APR-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 0.00 |
May | 3037.65 | 31-MAY-18:30 | 1760.39 | 1676.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 |
June | 3441.24 | 19-JUN-18:13 | 5281.16 | 5029.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.10 | 0.00 |
July | 3258.01 | 10-JUL-18:13 | 5281.16 | 5029.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.12 | 0.00 |
August | 3325.89 | 24-AUG-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.17 | 0.00 |
September | 3109.29 | 01-SEP-14:10 | 754.45 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 0.00 |
October | 2999.32 | 04-OCT-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 |
November | 2105.53 | 04-NOV-12:30 | 754.45 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.35 |
December | 645.13 | 03-DEC-13:00 | 754.45 | 628.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 754.45 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3441.24 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.17 | 288.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4698.51 | 31-JAN-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.25 |
February | 4701.66 | 14-FEB-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.23 |
March | 4851.84 | 29-MAR-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.56 |
April | 4797.83 | 28-APR-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.01 |
May | 4855.40 | 11-MAY-15:11 | 680.40 | 938.51 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.92 |
June | 4762.14 | 04-JUN-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 | 0.00 |
July | 4465.33 | 11-JUL-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 0.00 |
August | 4671.69 | 25-AUG-15:11 | 680.40 | 938.51 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 26.27 | 0.00 |
September | 4830.61 | 10-SEP-15:11 | 378.00 | 1106.11 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 0.00 |
October | 4773.67 | 09-OCT-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.39 |
November | 4736.73 | 03-NOV-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.13 |
December | 4624.07 | 18-DEC-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4465.33 | 324.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4855.40 | 680.40 | 1106.11 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 178.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4512.16 | 17-JAN-16:12 | 583.20 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.64 |
February | 4512.56 | 20-FEB-16:12 | 324.00 | 947.98 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.88 |
March | 4673.66 | 29-MAR-15:12 | 583.20 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.38 |
April | 4936.85 | 10-APR-20:41 | 1602.00 | 4261.12 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.56 |
May | 5029.09 | 15-MAY-16:21 | 972.00 | 1340.58 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.98 |
June | 5007.47 | 02-JUN-21:41 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.07 |
July | 4503.75 | 01-JUL-18:52 | 585.00 | 2393.89 | 605.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.41 |
August | 4857.75 | 25-AUG-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 |
September | 4980.62 | 28-SEP-21:51 | 1800.00 | 3207.81 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.31 |
October | 5000.55 | 19-OCT-16:41 | 972.00 | 1340.58 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.89 |
November | 4834.15 | 03-NOV-16:31 | 874.80 | 1206.52 | 1137.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.89 |
December | 3666.73 | 17-DEC-16:12 | 324.00 | 947.98 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3666.73 | 324.00 | 804.35 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 | |
Maximum of Months | 5029.09 | 1800.00 | 4261.12 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2719.23 | 31-JAN-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.51 |
February | 2705.91 | 08-FEB-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.88 |
March | 2708.61 | 29-MAR-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.76 |
April | 2672.16 | 14-APR-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.77 |
May | 2623.09 | 13-MAY-15:12 | 324.00 | 596.00 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.97 |
June | 2589.26 | 04-JUN-15:12 | 324.00 | 596.00 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 0.00 |
July | 2375.71 | 11-JUL-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 | 0.00 |
August | 2519.39 | 25-AUG-15:11 | 680.40 | 589.98 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 | 0.00 |
September | 2640.44 | 28-SEP-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
October | 2665.88 | 09-OCT-15:12 | 324.00 | 596.00 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 |
November | 2683.44 | 18-NOV-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.43 |
December | 2660.26 | 20-DEC-09:02 | 216.00 | 794.67 | 665.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2375.71 | 216.00 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2719.23 | 680.40 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 | 95.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15926.11 | 23-JAN-23:00 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.04 |
February | 15489.18 | 05-FEB-22:00 | 23990.02 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.52 |
March | 19341.71 | 27-MAR-21:02 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.87 |
April | 21437.90 | 07-APR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.47 |
May | 22604.20 | 31-MAY-21:05 | 107955.07 | 11994.96 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.22 |
June | 24816.18 | 19-JUN-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.80 | 0.00 |
July | 24269.86 | 10-JUL-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.69 | 0.00 |
August | 25061.16 | 04-AUG-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.93 | 0.00 |
September | 23661.09 | 01-SEP-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.03 | 0.00 |
October | 21127.71 | 05-OCT-21:52 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.89 |
November | 18753.76 | 03-NOV-22:00 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.45 |
December | 15729.71 | 04-DEC-23:00 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15489.18 | 23990.02 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25061.16 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 120.93 | 600.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18072.45 | 23-JAN-23:00 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.05 |
February | 16973.14 | 23-FEB-23:00 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.46 |
March | 20900.08 | 27-MAR-21:02 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.87 |
April | 22784.20 | 07-APR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.47 |
May | 23792.53 | 31-MAY-21:05 | 107955.07 | 11994.96 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.22 |
June | 26021.54 | 19-JUN-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.80 | 0.00 |
July | 25457.51 | 10-JUL-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.69 | 0.00 |
August | 26260.15 | 04-AUG-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.93 | 0.00 |
September | 24880.56 | 01-SEP-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 41.03 | 0.00 |
October | 22376.36 | 05-OCT-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.83 |
November | 20107.64 | 03-NOV-22:00 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.45 |
December | 17707.95 | 04-DEC-23:00 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16973.14 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26260.15 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 120.93 | 337.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26005.92 | 17-JAN-11:50 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 237.04 |
February | 26843.47 | 19-FEB-11:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 257.46 |
March | 28137.50 | 24-MAR-10:40 | 1067.42 | 667.18 | 30056.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 234.44 |
April | 30441.57 | 08-APR-10:50 | 800.57 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 11.30 |
May | 31495.92 | 29-MAY-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 49.20 | 0.00 |
June | 31794.35 | 19-JUN-10:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 158.80 | 0.00 |
July | 32023.52 | 09-JUL-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 80.59 | 0.00 |
August | 31787.31 | 13-AUG-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 80.57 | 0.00 |
September | 31582.49 | 04-SEP-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 22.29 | 0.00 |
October | 29915.93 | 12-OCT-10:40 | 1067.42 | 667.18 | 30056.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 77.44 |
November | 28191.92 | 04-NOV-10:50 | 800.57 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 107.98 |
December | 26702.33 | 17-DEC-11:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 187.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26005.92 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32023.52 | 1067.42 | 667.18 | 30056.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 158.80 | 257.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 3726.24 | 1330.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.09 |
February | 0.00 | 01-FEB-00:05 | 4790.88 | 887.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.38 |
March | 3043.21 | 28-MAR-12:30 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.84 |
April | 7463.31 | 08-APR-12:30 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 |
May | 9105.96 | 30-MAY-12:20 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.19 | 0.00 |
June | 9835.69 | 19-JUN-14:10 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.53 | 0.00 |
July | 9852.94 | 07-JUL-12:30 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.93 | 0.00 |
August | 10001.63 | 16-AUG-12:50 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.29 | 0.00 |
September | 9182.58 | 01-SEP-13:00 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.97 | 0.00 |
October | 7531.26 | 04-OCT-13:00 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 | 0.00 |
November | 4889.46 | 04-NOV-12:30 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.52 |
December | 0.00 | 01-DEC-00:05 | 4790.88 | 887.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10001.63 | 4790.88 | 1330.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.53 | 512.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.486690E+12 | 296378.03 | 23-JAN-19:10 | 0.810060E+12 | 650989.18 | 14-JAN-17:10 |
February | 0.438784E+12 | 291182.78 | 01-FEB-20:00 | 0.767255E+12 | 649196.65 | 06-FEB-19:10 |
March | 0.494671E+12 | 327191.46 | 27-MAR-18:10 | 0.627231E+12 | 509377.98 | 16-MAR-16:40 |
April | 0.504404E+12 | 356484.65 | 07-APR-19:10 | 0.461290E+12 | 420954.77 | 13-APR-17:49 |
May | 0.571411E+12 | 414419.73 | 31-MAY-19:49 | 0.390024E+12 | 342644.79 | 01-MAY-17:30 |
June | 0.657347E+12 | 467276.25 | 19-JUN-19:30 | 0.360237E+12 | 330254.61 | 01-JUN-17:49 |
July | 0.769458E+12 | 469642.28 | 20-JUL-19:19 | 0.363789E+12 | 319734.11 | 03-JUL-17:00 |
August | 0.751588E+12 | 500039.02 | 04-AUG-19:10 | 0.361929E+12 | 316679.30 | 31-AUG-17:19 |
September | 0.630997E+12 | 439249.77 | 07-SEP-19:00 | 0.354973E+12 | 322489.92 | 29-SEP-17:30 |
October | 0.580969E+12 | 371859.27 | 05-OCT-19:10 | 0.407145E+12 | 359866.17 | 27-OCT-17:49 |
November | 0.489696E+12 | 329394.09 | 03-NOV-19:00 | 0.535469E+12 | 490573.28 | 22-NOV-19:10 |
December | 0.490431E+12 | 298351.65 | 04-DEC-20:00 | 0.699741E+12 | 589666.62 | 31-DEC-19:10 |
Annual Sum or Average | 0.686645E+13 | 0.613914E+13 | ||||
Minimum of Months | 0.438784E+12 | 291182.78 | 0.354973E+12 | 316679.30 | ||
Maximum of Months | 0.769458E+12 | 500039.02 | 0.810060E+12 | 650989.18 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.129696E+12 | 0.333132E+11 | 0.141138E+12 | 0.715096E+11 | 0.803686E+11 | 0.145791E+10 | 0.00 | 0.254724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117116E+12 | 0.279374E+11 | 0.127470E+12 | 0.645894E+11 | 0.726933E+11 | 0.139584E+10 | 0.00 | 0.242172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129400E+12 | 0.279743E+11 | 0.141191E+12 | 0.715122E+11 | 0.807657E+11 | 0.844235E+09 | 0.00 | 0.392342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125475E+12 | 0.241115E+11 | 0.136545E+12 | 0.692026E+11 | 0.795093E+11 | 0.368701E+09 | 0.00 | 0.655644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129561E+12 | 0.222908E+11 | 0.141170E+12 | 0.715109E+11 | 0.849729E+11 | 0.146952E+09 | 0.00 | 0.117998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125286E+12 | 0.201872E+11 | 0.136635E+12 | 0.692051E+11 | 0.869073E+11 | 0.124232E+09 | 0.00 | 0.215350E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129759E+12 | 0.214789E+11 | 0.141079E+12 | 0.715085E+11 | 0.934336E+11 | 0.128327E+09 | 0.00 | 0.308308E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129426E+12 | 0.237178E+11 | 0.141202E+12 | 0.715122E+11 | 0.941337E+11 | 0.128330E+09 | 0.00 | 0.287695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125517E+12 | 0.257722E+11 | 0.136555E+12 | 0.692027E+11 | 0.854528E+11 | 0.125889E+09 | 0.00 | 0.184723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129662E+12 | 0.297088E+11 | 0.141127E+12 | 0.715095E+11 | 0.848893E+11 | 0.229520E+09 | 0.00 | 0.120083E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125477E+12 | 0.314557E+11 | 0.136629E+12 | 0.692036E+11 | 0.783265E+11 | 0.649213E+09 | 0.00 | 0.443311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129767E+12 | 0.339652E+11 | 0.141079E+12 | 0.715085E+11 | 0.803964E+11 | 0.114334E+10 | 0.00 | 0.288268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152614E+13 | 0.321913E+12 | 0.166182E+13 | 0.841975E+12 | 0.100185E+13 | 0.674249E+10 | 0.00 | 0.146180E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117116E+12 | 0.201872E+11 | 0.127470E+12 | 0.645894E+11 | 0.726933E+11 | 0.124232E+09 | 0.00 | 0.242172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129767E+12 | 0.339652E+11 | 0.141202E+12 | 0.715122E+11 | 0.941337E+11 | 0.145791E+10 | 0.00 | 0.308308E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.400875E+12 | 0.00 | 0.257267E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.395901E+12 | 0.00 | 0.234150E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.220305E+12 | 0.00 | 0.254902E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.772471E+11 | 0.00 | 0.237087E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.579394E+10 | 0.00 | 0.232252E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 18079255.95 | 0.00 | 0.213106E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 3957262.93 | 0.00 | 0.211965E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 4852198.94 | 0.00 | 0.209885E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.517786E+09 | 0.00 | 0.207484E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.309433E+11 | 0.00 | 0.224298E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.159043E+12 | 0.00 | 0.229335E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.298852E+12 | 0.00 | 0.249068E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.158951E+13 | 0.00 | 0.276080E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 3957262.93 | 0.00 | 0.207484E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.400875E+12 | 0.00 | 0.257267E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 121238.68 | 02-JAN-20:10 | 20502.98 | 01-JAN-00:10 | 89286.95 | 02-JAN-07:10 | 50420.89 | 02-JAN-07:19 | 32960.18 | 30-JAN-13:09 | 1176.24 | 14-JAN-16:19 | 0.00 | 01-JAN-00:10 |
February | 121238.68 | 01-FEB-20:10 | 20502.98 | 01-FEB-00:10 | 89286.95 | 01-FEB-07:10 | 50420.89 | 01-FEB-07:19 | 33644.51 | 20-FEB-13:30 | 1142.08 | 06-FEB-09:09 | 0.00 | 01-FEB-00:10 |
March | 121238.68 | 01-MAR-20:10 | 20502.98 | 01-MAR-00:10 | 89286.95 | 01-MAR-07:10 | 50420.89 | 01-MAR-07:19 | 35546.20 | 27-MAR-21:10 | 839.75 | 23-MAR-03:00 | 0.00 | 01-MAR-00:10 |
April | 121238.68 | 03-APR-19:10 | 20502.98 | 01-APR-00:10 | 89286.95 | 03-APR-06:10 | 50420.89 | 03-APR-06:19 | 39910.43 | 07-APR-20:10 | 506.69 | 01-APR-03:00 | 0.00 | 01-APR-00:10 |
May | 121238.68 | 01-MAY-19:10 | 20502.98 | 01-MAY-00:10 | 89286.95 | 01-MAY-06:10 | 50420.89 | 01-MAY-06:19 | 41543.38 | 30-MAY-20:10 | 286.16 | 01-MAY-04:49 | 0.00 | 01-MAY-00:10 |
June | 121238.68 | 01-JUN-19:10 | 20502.98 | 01-JUN-00:10 | 89286.95 | 01-JUN-06:10 | 50420.89 | 01-JUN-06:19 | 46603.28 | 19-JUN-20:10 | 67.49 | 02-JUN-08:00 | 0.00 | 01-JUN-00:10 |
July | 121238.68 | 03-JUL-19:10 | 20502.98 | 01-JUL-00:10 | 89286.95 | 03-JUL-06:10 | 50420.89 | 03-JUL-06:19 | 46151.54 | 20-JUL-20:10 | 56.41 | 18-JUL-08:09 | 0.00 | 01-JUL-00:10 |
August | 121238.68 | 01-AUG-19:10 | 20502.98 | 01-AUG-00:10 | 89286.95 | 01-AUG-06:10 | 50420.89 | 01-AUG-06:19 | 48841.16 | 04-AUG-20:10 | 51.89 | 25-AUG-08:00 | 0.00 | 01-AUG-00:10 |
September | 121238.68 | 01-SEP-19:10 | 20502.98 | 01-SEP-00:10 | 89286.95 | 01-SEP-06:10 | 50420.89 | 01-SEP-06:19 | 44278.01 | 01-SEP-20:10 | 110.22 | 24-SEP-05:00 | 0.00 | 01-SEP-00:10 |
October | 121238.68 | 02-OCT-19:10 | 20502.98 | 01-OCT-00:10 | 89286.95 | 02-OCT-06:10 | 50420.89 | 02-OCT-06:19 | 40839.59 | 05-OCT-20:10 | 479.65 | 29-OCT-03:00 | 0.00 | 01-OCT-00:10 |
November | 121238.68 | 01-NOV-19:10 | 20502.98 | 01-NOV-00:10 | 89286.95 | 01-NOV-06:10 | 50420.89 | 01-NOV-06:19 | 36261.26 | 03-NOV-21:10 | 814.94 | 23-NOV-05:00 | 0.00 | 01-NOV-00:10 |
December | 121238.68 | 01-DEC-20:10 | 20502.98 | 01-DEC-00:10 | 89286.95 | 01-DEC-07:10 | 50420.89 | 01-DEC-07:19 | 34325.94 | 17-DEC-13:09 | 932.00 | 31-DEC-23:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 121238.68 | 20502.98 | 89286.95 | 50420.89 | 32960.18 | 51.89 | 0.00 | |||||||
Maximum of Months | 121238.68 | 20502.98 | 89286.95 | 50420.89 | 48841.16 | 1176.24 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 27596.51 | 23-JAN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29678.11 | 19-FEB-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 61466.98 | 27-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 111561.77 | 07-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 132296.93 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 202240.79 | 19-JUN-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 196723.95 | 20-JUL-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 212659.83 | 04-AUG-18:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 172341.28 | 07-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 124553.15 | 25-OCT-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 69097.27 | 10-NOV-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36368.93 | 17-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 27596.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 212659.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 296378.03 | 23-JAN-19:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 31817.07 | 242.72 | 0.00 | 27596.51 | 0.00 |
February | 291182.78 | 01-FEB-20:00 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 31949.19 | 255.93 | 0.00 | 17135.71 | 0.00 |
March | 327191.46 | 27-MAR-18:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 34220.39 | 47.92 | 0.00 | 56201.58 | 0.00 |
April | 356484.65 | 07-APR-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 38907.59 | 47.91 | 0.00 | 76033.85 | 0.00 |
May | 414419.73 | 31-MAY-19:49 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 40585.24 | 47.91 | 0.00 | 131935.21 | 0.00 |
June | 467276.25 | 19-JUN-19:30 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 45804.02 | 47.93 | 0.00 | 179573.85 | 0.00 |
July | 469642.28 | 20-JUL-19:19 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 45088.56 | 47.91 | 0.00 | 182652.91 | 0.00 |
August | 500039.02 | 04-AUG-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 47787.22 | 47.92 | 0.00 | 210702.52 | 0.00 |
September | 439249.77 | 07-SEP-19:00 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 43207.54 | 47.91 | 0.00 | 154142.85 | 0.00 |
October | 371859.27 | 05-OCT-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 39678.97 | 47.91 | 0.00 | 90293.99 | 0.00 |
November | 329394.09 | 03-NOV-19:00 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 34633.77 | 47.91 | 0.00 | 53206.44 | 0.00 |
December | 298351.65 | 04-DEC-20:00 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 32146.34 | 132.57 | 0.00 | 24227.84 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 291182.78 | 107831.13 | 77688.87 | 20502.98 | 11860.16 | 31817.07 | 47.91 | 0.00 | 17135.71 | 0.00 | |
Maximum of Months | 500039.02 | 121238.68 | 86555.31 | 20502.98 | 29010.56 | 47787.22 | 255.93 | 0.00 | 210702.52 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 401160.47 | 02-JAN-04:00 | 0.00 | 260752.72 | 31-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 411771.69 | 06-FEB-02:00 | 0.00 | 260847.80 | 16-FEB-21:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 256129.77 | 23-MAR-03:00 | 0.00 | 259586.58 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 141580.06 | 01-APR-03:00 | 0.00 | 252369.58 | 03-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 73310.16 | 01-MAY-04:49 | 0.00 | 241775.57 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 6335.02 | 02-JUN-08:00 | 0.00 | 229174.48 | 01-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 2609.05 | 18-JUL-08:09 | 0.00 | 218002.29 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 1203.68 | 25-AUG-08:00 | 0.00 | 214552.46 | 30-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 19328.28 | 24-SEP-05:00 | 0.00 | 220843.14 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 130675.33 | 29-OCT-03:00 | 0.00 | 232972.29 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 239009.35 | 23-NOV-05:00 | 0.00 | 245657.29 | 30-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 295134.68 | 31-DEC-23:00 | 0.00 | 255895.39 | 28-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 1203.68 | 0.00 | 214552.46 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 411771.69 | 0.00 | 260847.80 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.77 | 0.33 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.83 | 21.80 | 1.83 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.87 | 1.50 | 21.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.93 | 4.50 | 21.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 22.16 | 10.67 | 22.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 22.23 | 7.50 | 22.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.99 | 6.83 | 21.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 22.05 | 7.33 | 22.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.88 | 2.00 | 21.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.50 | 22.07 | 40.50 | 22.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 22.23 | 10.67 | 22.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.86 | 1.33 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 22.25 | 7.00 | 22.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 22.55 | 26.17 | 22.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 22.43 | 30.17 | 22.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 22.29 | 16.00 | 22.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 22.50 | 16.33 | 22.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 22.09 | 4.17 | 22.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 101.33 | 22.42 | 101.33 | 22.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 22.55 | 30.17 | 22.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.76 | 0.83 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.83 | 21.75 | 1.83 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.77 | 0.83 | 21.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.12 | 0.67 | 22.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.24 | 6.17 | 22.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 22.39 | 15.17 | 22.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 22.48 | 14.67 | 22.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 22.37 | 11.00 | 22.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 22.32 | 10.50 | 22.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.19 | 2.17 | 22.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 60.33 | 22.37 | 60.33 | 22.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 22.48 | 15.17 | 22.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.83 | 1.83 | 21.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 21.82 | 2.33 | 21.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.83 | 1.83 | 21.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.86 | 1.33 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.92 | 4.33 | 21.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 22.13 | 10.33 | 22.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 22.16 | 7.67 | 22.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 21.94 | 7.00 | 21.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 22.00 | 7.17 | 22.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.90 | 1.33 | 21.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 39.33 | 22.04 | 39.33 | 22.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 22.16 | 10.33 | 22.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.28 | 78.00 | 21.25 | 78.00 | 21.23 |
February | 672.00 | 21.04 | 204.50 | 21.03 | 204.50 | 21.03 |
March | 744.00 | 21.26 | 58.17 | 21.24 | 58.17 | 21.22 |
April | 692.17 | 22.07 | 8.33 | 22.06 | 8.33 | 22.05 |
May | 596.33 | 23.42 | 63.17 | 23.47 | 38.17 | 23.49 |
June | 229.83 | 24.00 | 418.33 | 24.00 | 147.50 | 24.00 |
July | 150.17 | 24.00 | 660.67 | 24.00 | 150.17 | 24.00 |
August | 27.17 | 24.00 | 401.83 | 24.00 | 17.33 | 24.00 |
September | 15.33 | 24.00 | 218.17 | 24.00 | 0.00 | 24.00 |
October | 176.67 | 23.96 | 92.50 | 23.97 | 0.00 | 23.97 |
November | 409.67 | 23.06 | 3.00 | 23.06 | 0.00 | 23.06 |
December | 741.17 | 22.04 | 0.00 | 22.04 | 0.00 | 22.04 |
Annual Sum or Average | 5198.50 | 22.16 | 2206.67 | 22.56 | 702.17 | 22.56 |
Minimum of Months | 15.33 | 21.04 | 0.00 | 21.03 | 0.00 | 21.03 |
Maximum of Months | 744.00 | 24.00 | 660.67 | 24.00 | 204.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 724.33 | 21.13 | 479.33 | 21.09 | 476.17 | 21.06 |
February | 641.00 | 21.20 | 444.17 | 21.12 | 443.33 | 21.09 |
March | 669.00 | 21.30 | 236.33 | 21.34 | 201.67 | 21.28 |
April | 592.83 | 21.43 | 136.17 | 21.64 | 64.33 | 21.59 |
May | 515.83 | 21.82 | 145.50 | 22.30 | 0.00 | 22.30 |
June | 231.17 | 22.50 | 389.83 | 23.39 | 0.00 | 23.39 |
July | 68.00 | 22.78 | 595.00 | 23.77 | 0.00 | 23.77 |
August | 116.17 | 22.67 | 571.00 | 23.70 | 0.00 | 23.70 |
September | 304.50 | 22.18 | 329.67 | 23.10 | 0.00 | 23.10 |
October | 444.33 | 21.86 | 242.17 | 22.55 | 12.33 | 22.52 |
November | 659.67 | 21.30 | 197.67 | 21.33 | 168.17 | 21.28 |
December | 707.67 | 21.16 | 458.67 | 21.12 | 451.67 | 21.08 |
Annual Sum or Average | 5674.50 | 21.50 | 4225.50 | 22.00 | 1817.67 | 21.84 |
Minimum of Months | 68.00 | 21.13 | 136.17 | 21.09 | 0.00 | 21.06 |
Maximum of Months | 724.33 | 22.78 | 595.00 | 23.77 | 476.17 | 23.77 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 110.00 | 21.32 | 110.00 | 21.28 |
February | 672.00 | 21.44 | 95.83 | 21.38 | 95.83 | 21.34 |
March | 739.00 | 21.95 | 0.00 | 21.95 | 0.00 | 21.95 |
April | 648.00 | 22.33 | 20.83 | 22.38 | 0.00 | 22.38 |
May | 504.83 | 22.82 | 83.17 | 22.98 | 0.00 | 22.98 |
June | 99.83 | 23.19 | 457.33 | 23.74 | 0.00 | 23.74 |
July | 0.00 | 0.00 | 719.67 | 23.88 | 0.00 | 23.88 |
August | 8.83 | 23.35 | 608.33 | 23.92 | 0.00 | 23.92 |
September | 223.50 | 23.03 | 329.17 | 23.54 | 0.00 | 23.54 |
October | 449.00 | 22.91 | 139.33 | 23.14 | 0.00 | 23.14 |
November | 700.33 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
December | 744.00 | 21.58 | 3.17 | 21.58 | 3.17 | 21.57 |
Annual Sum or Average | 5533.33 | 22.04 | 2566.83 | 22.55 | 209.00 | 22.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.32 | 0.00 | 21.28 |
Maximum of Months | 744.00 | 23.35 | 719.67 | 23.92 | 110.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.19 | 241.33 | 21.15 | 241.33 | 21.12 |
February | 672.00 | 21.17 | 246.33 | 21.13 | 246.33 | 21.10 |
March | 744.00 | 21.65 | 31.83 | 21.62 | 31.83 | 21.60 |
April | 694.83 | 22.37 | 0.00 | 22.37 | 0.00 | 22.37 |
May | 532.17 | 23.17 | 48.33 | 23.24 | 0.00 | 23.24 |
June | 55.17 | 23.65 | 462.33 | 23.94 | 0.00 | 23.94 |
July | 0.00 | 0.00 | 726.17 | 23.99 | 0.00 | 23.99 |
August | 4.33 | 23.57 | 562.50 | 23.99 | 0.00 | 23.99 |
September | 195.33 | 23.44 | 278.83 | 23.76 | 0.00 | 23.76 |
October | 520.33 | 23.09 | 72.83 | 23.20 | 0.00 | 23.20 |
November | 715.00 | 22.08 | 29.33 | 22.04 | 29.33 | 22.00 |
December | 744.00 | 21.33 | 43.33 | 21.32 | 43.33 | 21.30 |
Annual Sum or Average | 5621.17 | 22.00 | 2743.17 | 22.44 | 592.17 | 22.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.13 | 0.00 | 21.10 |
Maximum of Months | 744.00 | 23.65 | 726.17 | 23.99 | 246.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 453.33 | 21.00 | 453.33 | 21.00 |
February | 672.00 | 21.00 | 498.00 | 21.00 | 498.00 | 21.00 |
March | 744.00 | 21.03 | 188.33 | 21.02 | 188.33 | 21.02 |
April | 720.00 | 21.37 | 12.50 | 21.37 | 12.50 | 21.36 |
May | 705.33 | 22.21 | 13.00 | 22.24 | 0.00 | 22.24 |
June | 360.83 | 23.01 | 160.17 | 23.28 | 0.00 | 23.28 |
July | 46.17 | 23.14 | 482.67 | 23.84 | 0.00 | 23.84 |
August | 167.17 | 23.18 | 347.50 | 23.68 | 0.00 | 23.68 |
September | 528.50 | 22.73 | 64.83 | 22.85 | 0.00 | 22.85 |
October | 742.17 | 22.03 | 0.00 | 22.03 | 0.00 | 22.03 |
November | 720.00 | 21.13 | 118.00 | 21.11 | 118.00 | 21.10 |
December | 744.00 | 21.00 | 378.83 | 21.00 | 378.83 | 21.00 |
Annual Sum or Average | 6894.17 | 21.59 | 2717.17 | 21.75 | 1649.00 | 21.64 |
Minimum of Months | 46.17 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 23.18 | 498.00 | 23.84 | 498.00 | 23.84 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 194.83 | 24.00 | 744.00 | 24.00 | 194.83 | 24.00 |
February | 180.17 | 24.00 | 672.00 | 24.00 | 180.17 | 24.00 |
March | 250.83 | 24.00 | 744.00 | 24.00 | 250.83 | 24.00 |
April | 294.83 | 24.00 | 720.00 | 24.00 | 294.83 | 24.00 |
May | 374.00 | 24.00 | 744.00 | 24.00 | 374.00 | 24.00 |
June | 447.50 | 24.00 | 720.00 | 24.00 | 447.50 | 24.00 |
July | 542.00 | 24.00 | 744.00 | 24.00 | 542.00 | 24.00 |
August | 555.33 | 24.00 | 744.00 | 24.00 | 555.33 | 24.00 |
September | 415.33 | 24.00 | 720.00 | 24.00 | 415.33 | 24.00 |
October | 348.00 | 24.00 | 744.00 | 24.00 | 348.00 | 24.00 |
November | 252.67 | 24.00 | 720.00 | 24.00 | 252.67 | 24.00 |
December | 221.50 | 24.00 | 744.00 | 24.00 | 221.50 | 24.00 |
Annual Sum or Average | 4077.00 | 24.00 | 8760.00 | 24.00 | 4077.00 | 24.00 |
Minimum of Months | 180.17 | 24.00 | 672.00 | 24.00 | 180.17 | 24.00 |
Maximum of Months | 555.33 | 24.00 | 744.00 | 24.00 | 555.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 734.17 | 21.03 | 300.17 | 21.04 | 294.33 | 21.03 |
February | 657.33 | 21.04 | 280.00 | 21.04 | 276.33 | 21.03 |
March | 660.17 | 21.24 | 122.00 | 21.40 | 68.33 | 21.37 |
April | 471.00 | 21.67 | 188.00 | 22.33 | 0.83 | 22.33 |
May | 182.17 | 23.06 | 473.50 | 23.73 | 50.83 | 23.75 |
June | 243.50 | 24.00 | 681.33 | 24.00 | 242.83 | 24.00 |
July | 410.83 | 24.00 | 744.00 | 24.00 | 410.83 | 24.00 |
August | 203.50 | 24.00 | 744.00 | 24.00 | 203.50 | 24.00 |
September | 142.00 | 23.87 | 634.83 | 23.98 | 119.50 | 23.98 |
October | 271.83 | 22.52 | 441.33 | 23.43 | 49.50 | 23.47 |
November | 600.17 | 21.42 | 135.33 | 21.66 | 62.17 | 21.64 |
December | 724.67 | 21.06 | 213.67 | 21.07 | 204.83 | 21.06 |
Annual Sum or Average | 5301.33 | 21.86 | 4958.17 | 22.63 | 1983.83 | 22.63 |
Minimum of Months | 142.00 | 21.03 | 122.00 | 21.04 | 0.83 | 21.03 |
Maximum of Months | 734.17 | 24.00 | 744.00 | 24.00 | 410.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.75 | 29.50 | 21.72 | 29.50 | 21.69 |
February | 672.00 | 21.85 | 16.50 | 21.83 | 16.50 | 21.81 |
March | 726.00 | 22.33 | 1.67 | 22.34 | 0.00 | 22.34 |
April | 557.83 | 22.57 | 55.67 | 22.69 | 0.00 | 22.69 |
May | 303.17 | 22.90 | 206.17 | 23.31 | 0.00 | 23.31 |
June | 132.83 | 23.84 | 589.83 | 23.87 | 112.33 | 23.88 |
July | 194.17 | 23.99 | 738.50 | 23.94 | 194.17 | 23.95 |
August | 88.17 | 23.99 | 726.50 | 23.95 | 88.17 | 23.96 |
September | 119.33 | 23.36 | 517.17 | 23.81 | 46.50 | 23.82 |
October | 275.83 | 23.13 | 311.33 | 23.53 | 14.67 | 23.54 |
November | 648.50 | 22.41 | 16.00 | 22.45 | 0.00 | 22.45 |
December | 744.00 | 22.04 | 1.33 | 22.04 | 1.33 | 22.04 |
Annual Sum or Average | 5205.83 | 22.41 | 3210.17 | 22.96 | 503.17 | 23.01 |
Minimum of Months | 88.17 | 21.75 | 1.33 | 21.72 | 0.00 | 21.69 |
Maximum of Months | 744.00 | 23.99 | 738.50 | 23.95 | 194.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.67 | 20.92 | 487.50 | 20.82 | 487.50 | 20.78 |
February | 670.83 | 21.08 | 428.33 | 20.95 | 428.33 | 20.90 |
March | 721.83 | 21.35 | 142.67 | 21.27 | 142.67 | 21.21 |
April | 669.83 | 21.45 | 34.67 | 21.45 | 26.17 | 21.43 |
May | 658.83 | 21.55 | 18.17 | 21.59 | 0.00 | 21.59 |
June | 557.17 | 21.36 | 73.50 | 21.59 | 3.33 | 21.60 |
July | 545.17 | 21.27 | 110.00 | 21.62 | 3.83 | 21.63 |
August | 543.67 | 21.27 | 113.83 | 21.63 | 1.67 | 21.63 |
September | 586.33 | 21.43 | 47.83 | 21.57 | 2.83 | 21.58 |
October | 639.83 | 21.47 | 38.00 | 21.56 | 3.83 | 21.57 |
November | 706.33 | 21.35 | 130.67 | 21.28 | 130.67 | 21.24 |
December | 743.17 | 21.08 | 423.50 | 20.97 | 423.50 | 20.91 |
Annual Sum or Average | 7786.67 | 21.29 | 2048.67 | 21.29 | 1654.33 | 21.21 |
Minimum of Months | 543.67 | 20.92 | 18.17 | 20.82 | 0.00 | 20.78 |
Maximum of Months | 743.67 | 21.55 | 487.50 | 21.63 | 487.50 | 21.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.69 | 588.17 | 20.64 | 588.17 | 20.62 |
February | 672.00 | 20.78 | 537.50 | 20.71 | 537.50 | 20.69 |
March | 739.00 | 21.25 | 197.83 | 21.19 | 194.33 | 21.14 |
April | 669.67 | 21.58 | 66.17 | 21.80 | 41.33 | 21.86 |
May | 601.00 | 22.14 | 132.67 | 22.87 | 51.67 | 23.16 |
June | 478.83 | 22.88 | 271.00 | 23.85 | 135.33 | 24.28 |
July | 511.33 | 21.96 | 213.83 | 22.71 | 85.33 | 23.00 |
August | 478.17 | 21.55 | 178.17 | 22.36 | 26.00 | 22.46 |
September | 516.17 | 22.36 | 185.83 | 23.25 | 70.00 | 23.52 |
October | 617.67 | 21.90 | 132.17 | 22.48 | 55.17 | 22.64 |
November | 718.67 | 21.18 | 212.33 | 21.09 | 211.67 | 21.03 |
December | 744.00 | 20.80 | 568.50 | 20.75 | 568.50 | 20.72 |
Annual Sum or Average | 7490.50 | 21.50 | 3284.17 | 21.74 | 2565.00 | 21.71 |
Minimum of Months | 478.17 | 20.69 | 66.17 | 20.64 | 26.00 | 20.62 |
Maximum of Months | 744.00 | 22.88 | 588.17 | 23.85 | 588.17 | 24.28 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.99 | 364.67 | 20.93 | 364.67 | 20.90 |
February | 672.00 | 20.98 | 401.33 | 20.92 | 401.33 | 20.89 |
March | 744.00 | 21.32 | 97.50 | 21.28 | 97.50 | 21.25 |
April | 714.17 | 21.65 | 2.67 | 21.66 | 0.00 | 21.66 |
May | 665.50 | 21.96 | 52.83 | 22.18 | 12.50 | 22.21 |
June | 620.33 | 22.58 | 180.33 | 23.09 | 127.00 | 23.33 |
July | 680.17 | 22.27 | 119.83 | 22.65 | 104.00 | 22.89 |
August | 661.17 | 22.03 | 75.50 | 22.32 | 33.67 | 22.42 |
September | 623.67 | 22.37 | 112.83 | 22.76 | 58.67 | 22.92 |
October | 720.33 | 21.96 | 46.83 | 22.09 | 36.67 | 22.18 |
November | 720.00 | 21.33 | 91.00 | 21.29 | 91.00 | 21.25 |
December | 744.00 | 21.07 | 269.33 | 21.02 | 269.33 | 20.99 |
Annual Sum or Average | 8309.33 | 21.68 | 1814.67 | 21.76 | 1596.33 | 21.76 |
Minimum of Months | 620.33 | 20.98 | 2.67 | 20.92 | 0.00 | 20.89 |
Maximum of Months | 744.00 | 22.58 | 401.33 | 23.09 | 401.33 | 23.33 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.92 | 476.50 | 20.84 | 476.50 | 20.80 |
February | 672.00 | 21.13 | 399.33 | 21.01 | 399.33 | 20.95 |
March | 737.83 | 21.44 | 139.00 | 21.35 | 139.00 | 21.29 |
April | 669.67 | 21.49 | 24.33 | 21.47 | 23.17 | 21.45 |
May | 638.83 | 21.51 | 13.67 | 21.55 | 0.00 | 21.55 |
June | 543.67 | 21.32 | 41.33 | 21.46 | 3.33 | 21.47 |
July | 533.83 | 21.23 | 114.83 | 21.60 | 3.00 | 21.61 |
August | 534.50 | 21.23 | 119.33 | 21.61 | 1.17 | 21.62 |
September | 573.00 | 21.40 | 39.33 | 21.52 | 3.00 | 21.53 |
October | 645.00 | 21.50 | 21.17 | 21.55 | 4.50 | 21.55 |
November | 717.00 | 21.41 | 120.00 | 21.35 | 120.00 | 21.30 |
December | 744.00 | 21.11 | 421.83 | 20.99 | 421.83 | 20.93 |
Annual Sum or Average | 7753.33 | 21.30 | 1930.67 | 21.29 | 1594.83 | 21.22 |
Minimum of Months | 533.83 | 20.92 | 13.67 | 20.84 | 0.00 | 20.80 |
Maximum of Months | 744.00 | 21.51 | 476.50 | 21.61 | 476.50 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.68 | 583.17 | 20.63 | 583.17 | 20.61 |
February | 672.00 | 20.78 | 523.83 | 20.73 | 523.83 | 20.71 |
March | 741.50 | 21.32 | 171.00 | 21.23 | 171.00 | 21.17 |
April | 669.67 | 21.58 | 41.00 | 21.62 | 28.33 | 21.59 |
May | 564.50 | 21.84 | 124.67 | 22.48 | 24.83 | 22.59 |
June | 442.00 | 22.51 | 260.33 | 23.54 | 120.50 | 23.87 |
July | 502.33 | 22.03 | 226.33 | 22.81 | 86.67 | 23.13 |
August | 473.50 | 21.71 | 186.67 | 22.57 | 40.17 | 22.79 |
September | 481.00 | 22.19 | 170.33 | 23.01 | 57.83 | 23.24 |
October | 651.00 | 21.94 | 82.83 | 22.17 | 47.00 | 22.26 |
November | 720.00 | 21.24 | 187.00 | 21.14 | 187.00 | 21.08 |
December | 744.00 | 20.80 | 544.00 | 20.75 | 544.00 | 20.73 |
Annual Sum or Average | 7405.50 | 21.46 | 3101.17 | 21.66 | 2414.33 | 21.62 |
Minimum of Months | 442.00 | 20.68 | 41.00 | 20.63 | 24.83 | 20.61 |
Maximum of Months | 744.00 | 22.51 | 583.17 | 23.54 | 583.17 | 23.87 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.14 | 664.33 | 22.20 | 664.33 | 22.22 |
February | 672.00 | 22.80 | 672.00 | 22.80 | 672.00 | 22.80 |
March | 637.67 | 23.77 | 673.17 | 23.78 | 637.67 | 23.77 |
April | 355.50 | 23.92 | 471.67 | 23.93 | 355.50 | 23.93 |
May | 84.00 | 24.00 | 226.17 | 24.00 | 84.00 | 24.00 |
June | 0.00 | 0.00 | 222.33 | 24.00 | 0.00 | 24.00 |
July | 0.00 | 0.00 | 468.50 | 24.00 | 0.00 | 24.00 |
August | 0.00 | 0.00 | 347.83 | 24.00 | 0.00 | 24.00 |
September | 10.33 | 24.00 | 182.17 | 24.00 | 10.33 | 24.00 |
October | 81.17 | 23.99 | 231.83 | 24.00 | 78.67 | 23.99 |
November | 550.83 | 23.66 | 607.17 | 23.67 | 550.83 | 23.67 |
December | 744.00 | 23.19 | 744.00 | 23.19 | 744.00 | 23.19 |
Annual Sum or Average | 3879.50 | 23.18 | 5511.17 | 23.35 | 3797.33 | 23.32 |
Minimum of Months | 0.00 | 0.00 | 182.17 | 22.20 | 0.00 | 22.22 |
Maximum of Months | 744.00 | 24.00 | 744.00 | 24.00 | 744.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.71 | 643.67 | 20.65 | 643.67 | 20.63 |
February | 671.33 | 20.86 | 560.83 | 20.78 | 560.83 | 20.74 |
March | 722.67 | 21.13 | 336.83 | 21.00 | 336.83 | 20.94 |
April | 666.00 | 21.28 | 163.83 | 21.22 | 151.83 | 21.15 |
May | 642.17 | 21.45 | 38.17 | 21.53 | 5.67 | 21.53 |
June | 546.83 | 21.32 | 108.83 | 21.65 | 10.33 | 21.67 |
July | 534.50 | 21.25 | 147.67 | 21.69 | 7.17 | 21.71 |
August | 530.17 | 21.26 | 149.00 | 21.70 | 2.33 | 21.71 |
September | 579.50 | 21.39 | 71.67 | 21.59 | 6.33 | 21.61 |
October | 643.00 | 21.40 | 108.17 | 21.47 | 68.33 | 21.44 |
November | 709.67 | 21.08 | 348.17 | 20.97 | 348.17 | 20.91 |
December | 744.00 | 20.83 | 610.00 | 20.75 | 610.00 | 20.72 |
Annual Sum or Average | 7733.83 | 21.14 | 3286.83 | 21.14 | 2751.50 | 21.05 |
Minimum of Months | 530.17 | 20.71 | 38.17 | 20.65 | 2.33 | 20.63 |
Maximum of Months | 744.00 | 21.45 | 643.67 | 21.70 | 643.67 | 21.71 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.51 | 703.50 | 20.49 | 703.50 | 20.48 |
February | 672.00 | 20.59 | 636.83 | 20.56 | 636.83 | 20.55 |
March | 739.67 | 21.00 | 426.83 | 20.90 | 423.50 | 20.84 |
April | 672.17 | 21.44 | 206.00 | 21.55 | 181.83 | 21.52 |
May | 601.17 | 22.17 | 149.83 | 22.92 | 67.83 | 23.25 |
June | 491.00 | 23.05 | 295.67 | 23.97 | 150.00 | 24.42 |
July | 508.00 | 21.98 | 256.83 | 22.75 | 88.33 | 23.02 |
August | 477.50 | 21.62 | 207.50 | 22.43 | 34.17 | 22.57 |
September | 528.83 | 22.47 | 198.67 | 23.35 | 90.33 | 23.68 |
October | 624.67 | 21.82 | 208.50 | 22.28 | 137.17 | 22.35 |
November | 718.67 | 20.88 | 437.17 | 20.77 | 437.17 | 20.72 |
December | 744.00 | 20.55 | 713.67 | 20.54 | 713.67 | 20.53 |
Annual Sum or Average | 7521.67 | 21.40 | 4441.00 | 21.58 | 3664.33 | 21.53 |
Minimum of Months | 477.50 | 20.51 | 149.83 | 20.49 | 34.17 | 20.48 |
Maximum of Months | 744.00 | 23.05 | 713.67 | 23.97 | 713.67 | 24.42 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 731.17 | 21.07 | 465.67 | 20.95 | 465.67 | 20.89 |
February | 651.83 | 21.22 | 416.33 | 21.08 | 416.33 | 21.01 |
March | 696.83 | 21.27 | 202.00 | 21.19 | 199.50 | 21.13 |
April | 657.17 | 21.36 | 97.17 | 21.33 | 85.83 | 21.29 |
May | 657.50 | 21.50 | 11.33 | 21.53 | 0.50 | 21.53 |
June | 585.50 | 21.43 | 65.83 | 21.61 | 17.83 | 21.64 |
July | 571.00 | 21.35 | 117.17 | 21.68 | 11.00 | 21.70 |
August | 565.83 | 21.33 | 129.33 | 21.70 | 3.00 | 21.71 |
September | 590.00 | 21.43 | 85.00 | 21.66 | 8.33 | 21.67 |
October | 607.83 | 21.36 | 99.17 | 21.55 | 29.67 | 21.54 |
November | 685.00 | 21.39 | 158.83 | 21.33 | 155.00 | 21.28 |
December | 719.67 | 21.15 | 429.83 | 21.03 | 428.67 | 20.97 |
Annual Sum or Average | 7719.33 | 21.32 | 2277.67 | 21.33 | 1821.33 | 21.26 |
Minimum of Months | 565.83 | 21.07 | 11.33 | 20.95 | 0.50 | 20.89 |
Maximum of Months | 731.17 | 21.50 | 465.67 | 21.70 | 465.67 | 21.71 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 735.33 | 22.06 | 60.50 | 21.99 | 58.17 | 21.92 |
February | 671.00 | 22.04 | 69.83 | 21.95 | 69.83 | 21.86 |
March | 640.83 | 22.59 | 16.83 | 22.62 | 0.00 | 22.62 |
April | 349.50 | 22.80 | 189.67 | 23.19 | 0.00 | 23.19 |
May | 82.00 | 23.14 | 541.67 | 23.78 | 19.50 | 23.79 |
June | 118.00 | 23.99 | 704.67 | 23.92 | 118.00 | 23.93 |
July | 184.00 | 23.99 | 744.00 | 23.97 | 184.00 | 23.97 |
August | 132.83 | 23.99 | 743.00 | 23.96 | 132.83 | 23.97 |
September | 87.67 | 23.86 | 624.83 | 23.88 | 76.17 | 23.89 |
October | 289.00 | 23.05 | 358.50 | 23.45 | 44.00 | 23.48 |
November | 582.17 | 22.50 | 45.00 | 22.60 | 5.17 | 22.61 |
December | 740.17 | 22.25 | 4.00 | 22.25 | 4.00 | 22.24 |
Annual Sum or Average | 4612.50 | 22.57 | 4102.50 | 23.16 | 711.67 | 23.18 |
Minimum of Months | 82.00 | 22.04 | 4.00 | 21.95 | 0.00 | 21.86 |
Maximum of Months | 740.17 | 23.99 | 744.00 | 23.97 | 184.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 696.50 | 22.36 | 28.33 | 22.35 | 16.50 | 22.32 |
February | 645.67 | 22.34 | 19.83 | 22.30 | 19.83 | 22.26 |
March | 524.00 | 22.83 | 59.17 | 22.94 | 0.00 | 22.94 |
April | 231.00 | 22.96 | 291.50 | 23.49 | 0.00 | 23.49 |
May | 30.83 | 23.46 | 632.00 | 23.89 | 15.33 | 23.90 |
June | 108.50 | 23.99 | 713.17 | 23.96 | 108.50 | 23.97 |
July | 175.00 | 23.99 | 744.00 | 23.99 | 175.00 | 23.99 |
August | 116.50 | 23.99 | 744.00 | 23.99 | 116.50 | 23.99 |
September | 59.17 | 23.99 | 681.00 | 23.92 | 59.17 | 23.93 |
October | 203.50 | 23.20 | 418.83 | 23.64 | 34.17 | 23.65 |
November | 480.67 | 22.73 | 92.67 | 22.91 | 5.00 | 22.92 |
December | 699.83 | 22.62 | 3.67 | 22.63 | 0.00 | 22.63 |
Annual Sum or Average | 3971.17 | 22.78 | 4428.17 | 23.38 | 550.00 | 23.41 |
Minimum of Months | 30.83 | 22.34 | 3.67 | 22.30 | 0.00 | 22.26 |
Maximum of Months | 699.83 | 23.99 | 744.00 | 23.99 | 175.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.83 | 23.83 | 669.00 | 23.93 | 453.67 | 23.95 |
February | 462.17 | 23.78 | 589.67 | 23.90 | 413.33 | 23.93 |
March | 500.50 | 23.99 | 724.83 | 24.00 | 497.17 | 24.00 |
April | 503.00 | 24.00 | 720.00 | 24.00 | 503.00 | 24.00 |
May | 543.33 | 24.00 | 744.00 | 24.00 | 543.33 | 24.00 |
June | 547.33 | 24.00 | 720.00 | 24.00 | 547.33 | 24.00 |
July | 582.33 | 24.00 | 744.00 | 24.00 | 582.33 | 24.00 |
August | 575.00 | 24.00 | 744.00 | 24.00 | 575.00 | 24.00 |
September | 531.67 | 24.00 | 720.00 | 24.00 | 531.67 | 24.00 |
October | 524.00 | 24.00 | 744.00 | 24.00 | 524.00 | 24.00 |
November | 488.83 | 23.99 | 702.17 | 24.00 | 482.67 | 24.00 |
December | 474.17 | 24.00 | 714.33 | 24.00 | 472.50 | 24.00 |
Annual Sum or Average | 6231.17 | 23.97 | 8536.00 | 23.99 | 6126.00 | 23.99 |
Minimum of Months | 462.17 | 23.78 | 589.67 | 23.90 | 413.33 | 23.93 |
Maximum of Months | 582.33 | 24.00 | 744.00 | 24.00 | 582.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.17 | 406.00 | 21.16 | 406.00 | 21.15 |
February | 672.00 | 21.26 | 318.00 | 21.21 | 318.00 | 21.19 |
March | 692.50 | 22.22 | 486.33 | 22.32 | 472.50 | 22.34 |
April | 491.00 | 23.12 | 545.00 | 23.17 | 472.83 | 23.14 |
May | 175.00 | 23.90 | 395.00 | 23.94 | 170.67 | 23.94 |
June | 1.00 | 24.00 | 531.50 | 24.00 | 1.00 | 24.00 |
July | 0.00 | 0.00 | 719.33 | 24.00 | 0.00 | 24.00 |
August | 0.00 | 0.00 | 608.50 | 24.00 | 0.00 | 24.00 |
September | 50.17 | 23.96 | 432.00 | 23.99 | 50.17 | 23.99 |
October | 296.50 | 23.59 | 423.83 | 23.68 | 253.17 | 23.65 |
November | 661.50 | 22.32 | 533.67 | 22.45 | 519.83 | 22.48 |
December | 744.00 | 21.28 | 195.17 | 21.30 | 195.17 | 21.31 |
Annual Sum or Average | 4527.67 | 22.04 | 5594.33 | 22.66 | 2859.33 | 22.60 |
Minimum of Months | 0.00 | 0.00 | 195.17 | 21.16 | 0.00 | 21.15 |
Maximum of Months | 744.00 | 24.00 | 719.33 | 24.00 | 519.83 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.28078 | 25.53148 | -0.3993 | 8.81132 |
February | 672.00000 | 21.04361 | 20.81352 | -0.5014 | 10.35045 |
March | 744.00000 | 21.25658 | 32.26930 | -0.3955 | 8.63230 |
April | 720.00000 | 22.14417 | 39.78989 | -0.1514 | 6.89487 |
May | 744.00000 | 23.52647 | 46.53690 | -0.7580 | 17.82419 |
June | 720.00000 | 23.99966 | 55.13557 | -0.5085 | 10.51727 |
July | 744.00000 | 24.00003 | 59.61864 | -0.4519 | 9.28607 |
August | 744.00000 | 24.00008 | 52.11654 | -0.4790 | 9.85781 |
September | 720.00000 | 24.00011 | 44.53977 | -0.5066 | 10.45199 |
October | 744.00000 | 23.99009 | 36.80137 | 0.34808 | 7.64003 |
November | 720.00000 | 23.46112 | 30.39317 | 0.17529 | 6.64022 |
December | 744.00000 | 22.05125 | 25.23098 | -0.2008 | 6.43710 |
Annual Sum or Average | 8760.00000 | 22.90585 | 39.17751 | -0.3184 | 9.44684 |
Minimum of Months | 672.00000 | 21.04361 | 20.81352 | -0.7580 | 6.43710 |
Maximum of Months | 744.00000 | 24.00011 | 59.61864 | 0.34808 | 17.82419 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.20817 | 26.07298 | -0.5416 | 12.41659 |
February | 672.00000 | 21.33161 | 20.95573 | -0.5147 | 12.31092 |
March | 744.00000 | 21.56459 | 32.16045 | -0.3253 | 9.41296 |
April | 720.00000 | 21.86552 | 39.81276 | -0.1637 | 8.26675 |
May | 744.00000 | 22.45969 | 46.86950 | -0.9437 | 27.57345 |
June | 720.00000 | 23.36627 | 55.41953 | -0.5064 | 12.56398 |
July | 744.00000 | 23.70076 | 60.05039 | -0.3135 | 8.20460 |
August | 744.00000 | 23.66900 | 55.91302 | -0.3228 | 9.02619 |
September | 720.00000 | 23.13410 | 51.84294 | -0.6016 | 16.45837 |
October | 744.00000 | 22.68541 | 43.71317 | 0.14796 | 8.74011 |
November | 720.00000 | 21.51603 | 35.30452 | -0.3154 | 9.11507 |
December | 744.00000 | 21.29718 | 26.39718 | -0.4825 | 11.37306 |
Annual Sum or Average | 8760.00000 | 22.32294 | 41.32776 | -0.4062 | 12.12599 |
Minimum of Months | 672.00000 | 21.20817 | 20.95573 | -0.9437 | 8.20460 |
Maximum of Months | 744.00000 | 23.70076 | 60.05039 | 0.14796 | 27.57345 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36635 | 26.94874 | -0.3815 | 8.49047 |
February | 672.00000 | 21.43618 | 21.96317 | -0.3899 | 8.58053 |
March | 744.00000 | 21.96028 | 32.61322 | -0.1828 | 6.39336 |
April | 720.00000 | 22.48145 | 39.60109 | -0.0024 | 6.01678 |
May | 744.00000 | 23.14068 | 46.05153 | -0.7541 | 17.95442 |
June | 720.00000 | 23.68342 | 55.17007 | -0.4772 | 10.17685 |
July | 744.00000 | 23.86900 | 59.97027 | -0.3672 | 7.92338 |
August | 744.00000 | 23.86651 | 56.08960 | -0.3897 | 8.38264 |
September | 720.00000 | 23.56532 | 51.56283 | -0.5486 | 12.05260 |
October | 744.00000 | 23.23179 | 43.60769 | 0.22951 | 6.85879 |
November | 720.00000 | 22.09718 | 35.30973 | -0.1301 | 6.25439 |
December | 744.00000 | 21.57970 | 27.18584 | -0.3185 | 7.46439 |
Annual Sum or Average | 8760.00000 | 22.69720 | 41.45412 | -0.3089 | 8.88429 |
Minimum of Months | 672.00000 | 21.36635 | 21.96317 | -0.7541 | 6.01678 |
Maximum of Months | 744.00000 | 23.86900 | 59.97027 | 0.22951 | 17.95442 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.00008 | 38.58224 | 0.88131 | 22.09892 |
February | 672.00000 | 24.00005 | 38.28725 | 0.88125 | 22.10142 |
March | 744.00000 | 24.00012 | 39.22113 | 0.92584 | 23.79939 |
April | 720.00000 | 24.00016 | 39.57215 | 0.95772 | 25.05331 |
May | 744.00000 | 24.00020 | 39.87169 | 0.36869 | 9.43714 |
June | 720.00000 | 24.00027 | 40.42466 | 0.41349 | 10.14407 |
July | 744.00000 | 24.00032 | 41.09015 | 0.43742 | 10.48251 |
August | 744.00000 | 24.00028 | 40.87185 | 0.44124 | 10.62476 |
September | 720.00000 | 24.00024 | 40.22712 | 0.39554 | 9.79442 |
October | 744.00000 | 24.00019 | 39.76114 | 0.98724 | 26.20437 |
November | 720.00000 | 24.00013 | 39.38506 | 0.93212 | 24.02137 |
December | 744.00000 | 24.00009 | 39.01024 | 0.89867 | 22.71946 |
Annual Sum or Average | 8760.00000 | 24.00018 | 39.70130 | 0.70902 | 18.01534 |
Minimum of Months | 672.00000 | 24.00005 | 38.28725 | 0.36869 | 9.43714 |
Maximum of Months | 744.00000 | 24.00032 | 41.09015 | 0.98724 | 26.20437 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06370 | 29.45321 | -0.4746 | 10.45430 |
February | 672.00000 | 21.08941 | 24.37062 | -0.4684 | 10.46232 |
March | 744.00000 | 21.53520 | 35.43605 | -0.2370 | 8.29404 |
April | 720.00000 | 22.46238 | 42.16437 | 0.04945 | 8.17655 |
May | 744.00000 | 23.74534 | 48.44777 | -0.4589 | 10.91010 |
June | 720.00000 | 24.00030 | 57.85822 | -0.2167 | 6.39028 |
July | 744.00000 | 24.00055 | 64.04912 | -0.1139 | 5.57655 |
August | 744.00000 | 24.00062 | 57.83442 | -0.1272 | 5.93662 |
September | 720.00000 | 23.96964 | 53.18420 | -0.2546 | 7.27090 |
October | 744.00000 | 23.43816 | 45.92537 | 0.39263 | 10.75030 |
November | 720.00000 | 21.82521 | 38.06778 | -0.1559 | 8.17443 |
December | 744.00000 | 21.12433 | 29.69135 | -0.4219 | 9.58962 |
Annual Sum or Average | 8760.00000 | 22.69692 | 43.99060 | -0.2058 | 8.49361 |
Minimum of Months | 672.00000 | 21.06370 | 24.37062 | -0.4746 | 5.57655 |
Maximum of Months | 744.00000 | 24.00062 | 64.04912 | 0.39263 | 10.91010 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.74917 | 29.25503 | -0.2650 | 7.08554 |
February | 672.00000 | 21.84544 | 24.35434 | -0.2656 | 6.99794 |
March | 744.00000 | 22.36881 | 34.83677 | -0.0549 | 5.74810 |
April | 720.00000 | 22.82434 | 41.74212 | 0.11617 | 6.21792 |
May | 744.00000 | 23.39977 | 48.20505 | -0.6111 | 13.60602 |
June | 720.00000 | 23.78964 | 57.39696 | -0.3772 | 8.26679 |
July | 744.00000 | 23.91440 | 62.09997 | -0.2815 | 6.73265 |
August | 744.00000 | 23.93593 | 58.18859 | -0.2933 | 6.92149 |
September | 720.00000 | 23.75128 | 53.63320 | -0.4186 | 9.19024 |
October | 744.00000 | 23.54491 | 45.65011 | 0.35309 | 8.25833 |
November | 720.00000 | 22.54702 | 37.35775 | 0.01113 | 5.95770 |
December | 744.00000 | 22.03902 | 29.39870 | -0.1828 | 6.19336 |
Annual Sum or Average | 8760.00000 | 22.98234 | 43.62324 | -0.1887 | 7.60502 |
Minimum of Months | 672.00000 | 21.74917 | 24.35434 | -0.6111 | 5.74810 |
Maximum of Months | 744.00000 | 23.93593 | 62.09997 | 0.35309 | 13.60602 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91641 | 31.75181 | -0.5887 | 13.25918 |
February | 672.00000 | 21.07975 | 26.58277 | -0.5522 | 12.63726 |
March | 744.00000 | 21.40678 | 36.70044 | -0.3351 | 8.64063 |
April | 720.00000 | 21.57994 | 42.07977 | -0.2153 | 7.36262 |
May | 744.00000 | 21.75002 | 47.05058 | -1.1727 | 35.84987 |
June | 720.00000 | 21.79937 | 53.28427 | -1.0340 | 29.76949 |
July | 744.00000 | 21.81023 | 56.41616 | -0.9806 | 27.54033 |
August | 744.00000 | 21.80940 | 52.47654 | -0.9887 | 28.16837 |
September | 720.00000 | 21.77873 | 50.72396 | -1.0939 | 32.46071 |
October | 744.00000 | 21.72504 | 44.95324 | -0.1096 | 6.81875 |
November | 720.00000 | 21.38532 | 39.75769 | -0.3482 | 8.60406 |
December | 744.00000 | 21.08266 | 32.18332 | -0.5142 | 11.51371 |
Annual Sum or Average | 8760.00000 | 21.51247 | 42.92379 | -0.6619 | 18.58977 |
Minimum of Months | 672.00000 | 20.91641 | 26.58277 | -1.1727 | 6.81875 |
Maximum of Months | 744.00000 | 21.81023 | 56.41616 | -0.1096 | 35.84987 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.68848 | 31.90039 | -0.6670 | 15.06733 |
February | 672.00000 | 20.77606 | 26.78450 | -0.6585 | 14.94354 |
March | 744.00000 | 21.27952 | 37.18870 | -0.3916 | 9.47442 |
April | 720.00000 | 21.79572 | 42.15615 | -0.1894 | 8.30788 |
May | 744.00000 | 22.61499 | 46.25250 | -0.9374 | 31.21824 |
June | 720.00000 | 23.25934 | 52.27988 | -0.6161 | 22.05334 |
July | 744.00000 | 22.46975 | 56.67250 | -0.7951 | 22.96002 |
August | 744.00000 | 22.40299 | 52.73819 | -0.8426 | 24.09616 |
September | 720.00000 | 22.97582 | 50.64520 | -0.7813 | 24.84725 |
October | 744.00000 | 22.36488 | 45.61018 | -0.0113 | 8.77319 |
November | 720.00000 | 21.18903 | 40.49138 | -0.4204 | 9.64057 |
December | 744.00000 | 20.80190 | 32.60806 | -0.6079 | 13.26754 |
Annual Sum or Average | 8760.00000 | 21.88938 | 43.03899 | -0.5767 | 17.08070 |
Minimum of Months | 672.00000 | 20.68848 | 26.78450 | -0.9374 | 8.30788 |
Maximum of Months | 744.00000 | 23.25934 | 56.67250 | -0.0113 | 31.21824 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.98823 | 28.54612 | -0.5450 | 11.65372 |
February | 672.00000 | 20.97763 | 23.80968 | -0.5771 | 12.33567 |
March | 744.00000 | 21.32227 | 34.12208 | -0.3954 | 8.67678 |
April | 720.00000 | 21.67329 | 39.78820 | -0.2503 | 7.13581 |
May | 744.00000 | 22.26041 | 44.80169 | -1.1201 | 33.98257 |
June | 720.00000 | 22.83539 | 53.92413 | -0.8320 | 23.95024 |
July | 744.00000 | 22.40639 | 57.99073 | -0.9289 | 26.71356 |
August | 744.00000 | 22.29490 | 53.81418 | -1.0041 | 28.96424 |
September | 720.00000 | 22.67066 | 50.50444 | -0.9402 | 27.29099 |
October | 744.00000 | 22.03096 | 45.06479 | -0.1204 | 6.92119 |
November | 720.00000 | 21.33223 | 36.91864 | -0.3775 | 8.41298 |
December | 744.00000 | 21.06998 | 29.25714 | -0.5111 | 10.62393 |
Annual Sum or Average | 8760.00000 | 21.82545 | 41.64995 | -0.6343 | 17.26771 |
Minimum of Months | 672.00000 | 20.97763 | 23.80968 | -1.1201 | 6.92119 |
Maximum of Months | 744.00000 | 22.83539 | 57.99073 | -0.1204 | 33.98257 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.92340 | 31.69432 | -0.5855 | 13.09355 |
February | 672.00000 | 21.13414 | 26.51275 | -0.5362 | 12.20804 |
March | 744.00000 | 21.45132 | 36.62747 | -0.3295 | 8.55393 |
April | 720.00000 | 21.61771 | 41.82922 | -0.2060 | 7.30282 |
May | 744.00000 | 21.76912 | 46.79391 | -1.1619 | 35.34594 |
June | 720.00000 | 21.80759 | 53.48644 | -1.0405 | 29.94120 |
July | 744.00000 | 21.81535 | 56.30847 | -0.9816 | 27.54189 |
August | 744.00000 | 21.81701 | 52.25372 | -0.9875 | 28.05551 |
September | 720.00000 | 21.79255 | 50.54977 | -1.0878 | 32.15584 |
October | 744.00000 | 21.74736 | 44.87543 | -0.1081 | 6.74601 |
November | 720.00000 | 21.42250 | 39.48807 | -0.3327 | 8.42104 |
December | 744.00000 | 21.10816 | 32.11062 | -0.5051 | 11.31004 |
Annual Sum or Average | 8760.00000 | 21.53575 | 42.80423 | -0.6561 | 18.42878 |
Minimum of Months | 672.00000 | 20.92340 | 26.51275 | -1.1619 | 6.74601 |
Maximum of Months | 744.00000 | 21.81701 | 56.30847 | -0.1081 | 35.34594 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67637 | 31.86108 | -0.6675 | 15.02708 |
February | 672.00000 | 20.78434 | 26.77611 | -0.6512 | 14.59088 |
March | 744.00000 | 21.33069 | 37.11328 | -0.3849 | 9.06344 |
April | 720.00000 | 21.75569 | 41.92023 | -0.1963 | 7.50414 |
May | 744.00000 | 22.48786 | 46.25042 | -0.9682 | 30.18588 |
June | 720.00000 | 23.13447 | 53.11944 | -0.6589 | 21.10375 |
July | 744.00000 | 22.52276 | 56.63491 | -0.7799 | 23.25987 |
August | 744.00000 | 22.48400 | 52.51233 | -0.8177 | 24.36500 |
September | 720.00000 | 22.87206 | 50.67335 | -0.8070 | 24.32359 |
October | 744.00000 | 22.19246 | 46.02235 | -0.0486 | 7.38782 |
November | 720.00000 | 21.23765 | 40.15654 | -0.4010 | 9.30722 |
December | 744.00000 | 20.79656 | 32.53113 | -0.6042 | 13.10933 |
Annual Sum or Average | 8760.00000 | 21.86074 | 43.05893 | -0.5823 | 16.63029 |
Minimum of Months | 672.00000 | 20.67637 | 26.77611 | -0.9682 | 7.38782 |
Maximum of Months | 744.00000 | 23.13447 | 56.63491 | -0.0486 | 30.18588 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.71144 | 32.41458 | -0.7070 | 16.49771 |
February | 672.00000 | 20.86376 | 26.95102 | -0.6824 | 16.11399 |
March | 744.00000 | 21.19178 | 37.96660 | -0.4482 | 10.85640 |
April | 720.00000 | 21.43509 | 43.77415 | -0.2909 | 8.64080 |
May | 744.00000 | 21.69843 | 48.81382 | -1.2124 | 38.09586 |
June | 720.00000 | 21.79158 | 54.14697 | -1.0308 | 30.07079 |
July | 744.00000 | 21.80989 | 56.79581 | -0.9627 | 27.27153 |
August | 744.00000 | 21.80662 | 52.84406 | -0.9743 | 28.13432 |
September | 720.00000 | 21.75453 | 52.03759 | -1.1132 | 33.74712 |
October | 744.00000 | 21.65470 | 46.77342 | -0.1568 | 7.46956 |
November | 720.00000 | 21.11521 | 41.55167 | -0.4771 | 11.12329 |
December | 744.00000 | 20.82732 | 32.90105 | -0.6534 | 14.98987 |
Annual Sum or Average | 8760.00000 | 21.39119 | 44.01022 | -0.7261 | 20.27788 |
Minimum of Months | 672.00000 | 20.71144 | 26.95102 | -1.2124 | 7.46956 |
Maximum of Months | 744.00000 | 21.80989 | 56.79581 | -0.1568 | 38.09586 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.51042 | 32.44215 | -0.7810 | 18.57243 |
February | 672.00000 | 20.59076 | 27.02975 | -0.7842 | 18.76196 |
March | 744.00000 | 21.02635 | 38.44660 | -0.5156 | 12.18050 |
April | 720.00000 | 21.64388 | 43.82578 | -0.2660 | 9.76490 |
May | 744.00000 | 22.59337 | 47.71316 | -0.9614 | 33.73770 |
June | 720.00000 | 23.29531 | 52.29858 | -0.5913 | 22.98145 |
July | 744.00000 | 22.46325 | 56.72133 | -0.7759 | 22.73393 |
August | 744.00000 | 22.38470 | 52.83929 | -0.8302 | 24.11452 |
September | 720.00000 | 22.95834 | 51.44747 | -0.7918 | 26.35072 |
October | 744.00000 | 22.25690 | 47.21144 | -0.0664 | 9.60817 |
November | 720.00000 | 20.88730 | 42.27494 | -0.5583 | 12.73392 |
December | 744.00000 | 20.55355 | 33.08812 | -0.7481 | 17.31925 |
Annual Sum or Average | 8760.00000 | 21.76858 | 43.87551 | -0.6389 | 19.08637 |
Minimum of Months | 672.00000 | 20.51042 | 27.02975 | -0.9614 | 9.60817 |
Maximum of Months | 744.00000 | 23.29531 | 56.72133 | -0.0664 | 33.73770 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.10454 | 32.78702 | -0.5365 | 12.59326 |
February | 672.00000 | 21.28655 | 27.83088 | -0.4931 | 12.03220 |
March | 744.00000 | 21.40145 | 37.71829 | -0.3589 | 9.39214 |
April | 720.00000 | 21.53202 | 43.29093 | -0.2602 | 8.05163 |
May | 744.00000 | 21.71427 | 48.80167 | -1.2428 | 39.20577 |
June | 720.00000 | 21.78409 | 55.89685 | -1.0929 | 32.33023 |
July | 744.00000 | 21.80844 | 57.96900 | -1.0207 | 29.27322 |
August | 744.00000 | 21.80588 | 53.54210 | -1.0238 | 29.88053 |
September | 720.00000 | 21.77137 | 51.92994 | -1.1140 | 33.77861 |
October | 744.00000 | 21.72295 | 45.88071 | -0.1092 | 7.21339 |
November | 720.00000 | 21.48458 | 40.31209 | -0.3257 | 8.72705 |
December | 744.00000 | 21.22380 | 33.08334 | -0.4769 | 11.46700 |
Annual Sum or Average | 8760.00000 | 21.55454 | 44.17919 | -0.6724 | 19.54332 |
Minimum of Months | 672.00000 | 21.10454 | 27.83088 | -1.2428 | 7.21339 |
Maximum of Months | 744.00000 | 21.80844 | 57.96900 | -0.1092 | 39.20577 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.08000 | 28.78262 | -0.2021 | 6.97163 |
February | 672.00000 | 22.04680 | 24.06154 | -0.2388 | 7.19038 |
March | 744.00000 | 22.75740 | 34.27966 | 0.05191 | 5.98986 |
April | 720.00000 | 23.28180 | 41.47398 | 0.27208 | 7.40180 |
May | 744.00000 | 23.72037 | 48.82415 | -0.3949 | 8.81096 |
June | 720.00000 | 23.90547 | 57.96771 | -0.2059 | 6.12421 |
July | 744.00000 | 23.96920 | 61.76405 | -0.1257 | 5.41246 |
August | 744.00000 | 23.95599 | 58.99399 | -0.1591 | 5.67164 |
September | 720.00000 | 23.79644 | 54.96693 | -0.3048 | 7.40117 |
October | 744.00000 | 23.44464 | 46.98791 | 0.36753 | 8.70369 |
November | 720.00000 | 22.73973 | 37.18522 | 0.06566 | 6.32698 |
December | 744.00000 | 22.26136 | 29.05631 | -0.1428 | 6.18250 |
Annual Sum or Average | 8760.00000 | 23.16951 | 43.81065 | -0.0839 | 6.84652 |
Minimum of Months | 672.00000 | 22.04680 | 24.06154 | -0.3949 | 5.41246 |
Maximum of Months | 744.00000 | 23.96920 | 61.76405 | 0.36753 | 8.81096 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.45794 | 28.36104 | -0.0783 | 6.39275 |
February | 672.00000 | 22.40501 | 23.77889 | -0.1208 | 6.47723 |
March | 744.00000 | 23.11665 | 33.71492 | 0.16505 | 6.35063 |
April | 720.00000 | 23.52499 | 40.85785 | 0.35371 | 8.27409 |
May | 744.00000 | 23.84099 | 48.22445 | -0.3214 | 7.55475 |
June | 720.00000 | 23.95702 | 57.46313 | -0.1546 | 5.68913 |
July | 744.00000 | 23.98895 | 61.34738 | -0.0844 | 5.22314 |
August | 744.00000 | 23.98705 | 58.55794 | -0.1145 | 5.39661 |
September | 720.00000 | 23.89372 | 54.37624 | -0.2399 | 6.54743 |
October | 744.00000 | 23.62932 | 46.38540 | 0.43226 | 9.64827 |
November | 720.00000 | 23.07580 | 36.59919 | 0.17221 | 6.63419 |
December | 744.00000 | 22.69595 | 28.60324 | -0.0065 | 5.73807 |
Annual Sum or Average | 8760.00000 | 23.38660 | 43.30336 | 0.00088 | 6.66065 |
Minimum of Months | 672.00000 | 22.40501 | 23.77889 | -0.3214 | 5.22314 |
Maximum of Months | 744.00000 | 23.98895 | 61.34738 | 0.43226 | 9.64827 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.87131 | 42.33335 | 0.93616 | 26.34767 |
February | 672.00000 | 23.82854 | 40.48462 | 0.92061 | 26.22621 |
March | 744.00000 | 23.99408 | 44.02235 | 1.05529 | 30.49532 |
April | 720.00000 | 24.00186 | 46.46682 | 1.13327 | 33.85068 |
May | 744.00000 | 24.00161 | 49.19896 | 0.65689 | 18.40997 |
June | 720.00000 | 24.00185 | 53.88886 | 0.76253 | 21.15217 |
July | 744.00000 | 24.00241 | 57.01673 | 0.83010 | 23.17719 |
August | 744.00000 | 24.00238 | 54.58522 | 0.81659 | 23.08313 |
September | 720.00000 | 24.00180 | 52.12786 | 0.71001 | 19.57565 |
October | 744.00000 | 24.00158 | 48.62157 | 1.17847 | 35.84587 |
November | 720.00000 | 23.98796 | 44.98706 | 1.05345 | 30.29368 |
December | 744.00000 | 23.99492 | 42.31998 | 0.98576 | 27.41880 |
Annual Sum or Average | 8760.00000 | 23.97512 | 48.05132 | 0.91998 | 26.32498 |
Minimum of Months | 672.00000 | 23.82854 | 40.48462 | 0.65689 | 18.40997 |
Maximum of Months | 744.00000 | 24.00241 | 57.01673 | 1.17847 | 35.84587 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00016 | 24.27051 | -0.5631 | 11.83417 |
February | 672.00000 | 21.00014 | 19.21775 | -0.5938 | 12.50113 |
March | 744.00000 | 21.02822 | 30.94541 | -0.4720 | 9.83211 |
April | 720.00000 | 21.37327 | 38.71166 | -0.3131 | 7.66742 |
May | 744.00000 | 22.28767 | 45.01552 | -1.0934 | 31.13795 |
June | 720.00000 | 23.34879 | 53.55511 | -0.6593 | 14.74627 |
July | 744.00000 | 23.73672 | 58.24574 | -0.4849 | 10.11235 |
August | 744.00000 | 23.66283 | 54.29861 | -0.5382 | 11.45863 |
September | 720.00000 | 22.97722 | 50.36699 | -0.8127 | 19.94043 |
October | 744.00000 | 22.02904 | 43.24758 | -0.1011 | 6.18210 |
November | 720.00000 | 21.12910 | 34.00156 | -0.4151 | 8.93233 |
December | 744.00000 | 21.00045 | 24.76837 | -0.5374 | 11.10717 |
Annual Sum or Average | 8760.00000 | 22.05467 | 39.84028 | -0.5483 | 12.95952 |
Minimum of Months | 672.00000 | 21.00014 | 19.21775 | -1.0934 | 6.18210 |
Maximum of Months | 744.00000 | 23.73672 | 58.24574 | -0.1011 | 31.13795 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.13869 | 90.49649 | 0.12081 | 7.01392 |
February | 672.00000 | 22.79656 | 97.44685 | 0.34037 | 8.14293 |
March | 744.00000 | 23.80211 | 85.64107 | 0.53506 | 11.14793 |
April | 720.00000 | 23.95863 | 68.82575 | 0.47555 | 9.92747 |
May | 744.00000 | 23.99916 | 54.02790 | -0.5207 | 10.70080 |
June | 720.00000 | 23.99919 | 52.37932 | -0.5077 | 10.40479 |
July | 744.00000 | 23.99921 | 55.11823 | -0.4804 | 9.82916 |
August | 744.00000 | 23.99919 | 52.92825 | -0.4930 | 10.09777 |
September | 720.00000 | 23.99917 | 52.29375 | -0.5146 | 10.57868 |
October | 744.00000 | 23.99836 | 54.14588 | 0.40529 | 8.46136 |
November | 720.00000 | 23.73827 | 83.15083 | 0.50176 | 10.43492 |
December | 744.00000 | 23.18938 | 97.39083 | 0.44222 | 9.43745 |
Annual Sum or Average | 8760.00000 | 23.63855 | 70.16496 | 0.02320 | 9.68690 |
Minimum of Months | 672.00000 | 22.13869 | 52.29375 | -0.5207 | 7.01392 |
Maximum of Months | 744.00000 | 23.99921 | 97.44685 | 0.53506 | 11.14793 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.16923 | 50.72041 | -0.3989 | 9.23227 |
February | 672.00000 | 21.26080 | 47.22801 | -0.3926 | 9.23717 |
March | 744.00000 | 22.34346 | 78.49489 | 0.10162 | 6.56604 |
April | 720.00000 | 23.39449 | 74.63950 | 0.36785 | 8.26676 |
May | 744.00000 | 23.97566 | 55.90472 | -0.4824 | 9.96177 |
June | 720.00000 | 23.99928 | 50.80340 | -0.4458 | 9.21408 |
July | 744.00000 | 23.99922 | 51.94321 | -0.4046 | 8.47512 |
August | 744.00000 | 23.99924 | 50.73137 | -0.4137 | 8.66041 |
September | 720.00000 | 23.99621 | 52.21690 | -0.4640 | 9.59408 |
October | 744.00000 | 23.83339 | 60.25956 | 0.41172 | 8.71542 |
November | 720.00000 | 22.45311 | 77.05419 | 0.12121 | 7.76433 |
December | 744.00000 | 21.27727 | 59.18516 | -0.3066 | 7.71008 |
Annual Sum or Average | 8760.00000 | 22.98388 | 59.14582 | -0.1915 | 8.61034 |
Minimum of Months | 672.00000 | 21.16923 | 47.22801 | -0.4824 | 6.56604 |
Maximum of Months | 744.00000 | 23.99928 | 78.49489 | 0.41172 | 9.96177 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.19405 | 23.84837 | -0.4589 | 9.73935 |
February | 672.00000 | 21.17422 | 18.90239 | -0.4929 | 10.29819 |
March | 744.00000 | 21.64638 | 29.67588 | -0.3004 | 7.41430 |
April | 720.00000 | 22.42598 | 36.32783 | -0.0660 | 5.97681 |
May | 744.00000 | 23.38235 | 42.21157 | -0.7462 | 17.41024 |
June | 720.00000 | 23.91602 | 51.74397 | -0.4726 | 9.85753 |
July | 744.00000 | 23.98472 | 57.18035 | -0.3960 | 8.29706 |
August | 744.00000 | 23.97540 | 53.16054 | -0.4285 | 8.92586 |
September | 720.00000 | 23.79725 | 48.01674 | -0.5476 | 11.68507 |
October | 744.00000 | 23.31296 | 40.20574 | 0.18811 | 6.43999 |
November | 720.00000 | 22.09295 | 31.94214 | -0.1754 | 6.58792 |
December | 744.00000 | 21.33354 | 24.21598 | -0.4122 | 8.76815 |
Annual Sum or Average | 8760.00000 | 22.69467 | 38.23463 | -0.3584 | 9.28332 |
Minimum of Months | 672.00000 | 21.17422 | 18.90239 | -0.7462 | 5.97681 |
Maximum of Months | 744.00000 | 23.98472 | 57.18035 | 0.18811 | 17.41024 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.257810E+12 | 0.00 | 744.00 | 415372.92 | 02-JAN-09:02 | 0.00 | 36.68 | 74.32 | 0.62 | 0.00 | 0.14 | 0.60 | 02-JAN-09:02 |
February | 0.256655E+12 | 0.00 | 672.00 | 411112.52 | 06-FEB-09:02 | 0.00 | 36.82 | 75.46 | 0.66 | 0.00 | 0.15 | 0.59 | 06-FEB-09:02 |
March | 0.134829E+12 | 0.00 | 708.38 | 293088.83 | 16-MAR-15:12 | 0.00 | 30.81 | 68.54 | 0.30 | 0.00 | 0.07 | 0.42 | 16-MAR-15:12 |
April | 0.443231E+11 | 0.00 | 487.58 | 137480.53 | 21-APR-15:12 | 0.00 | 26.87 | 54.02 | 0.10 | 0.00 | 0.02 | 0.20 | 21-APR-15:12 |
May | 0.327918E+10 | 0.00 | 158.77 | 55685.17 | 03-MAY-08:05 | 0.00 | 24.52 | 33.29 | 0.01 | 0.00 | 0.00 | 0.08 | 03-MAY-08:05 |
June | 10182350.59 | 0.00 | 29.02 | 32095.49 | 02-JUN-08:54 | 0.00 | 24.97 | 26.61 | 0.00 | 0.00 | 0.00 | 0.05 | 02-JUN-08:54 |
July | 2228755.36 | 0.00 | 22.59 | 8331.90 | 18-JUL-08:07 | 0.00 | 25.40 | 26.63 | 0.00 | 0.00 | 0.00 | 0.01 | 18-JUL-08:07 |
August | 2732850.66 | 0.00 | 43.42 | 6779.23 | 25-AUG-08:54 | 0.00 | 25.76 | 28.09 | 0.00 | 0.00 | 0.00 | 0.01 | 25-AUG-08:54 |
September | 0.299013E+09 | 0.00 | 39.52 | 58567.51 | 15-SEP-06:15 | 0.00 | 25.88 | 28.08 | 0.00 | 0.00 | 0.00 | 0.08 | 15-SEP-06:15 |
October | 0.180916E+11 | 0.00 | 278.25 | 92929.03 | 07-OCT-15:15 | 0.00 | 26.34 | 41.19 | 0.04 | 0.00 | 0.01 | 0.13 | 07-OCT-15:15 |
November | 0.965564E+11 | 0.00 | 630.25 | 252706.88 | 22-NOV-16:12 | 0.00 | 29.72 | 64.11 | 0.23 | 0.00 | 0.05 | 0.36 | 22-NOV-16:12 |
December | 0.185075E+12 | 0.00 | 744.00 | 342489.98 | 31-DEC-19:02 | 0.00 | 34.34 | 72.25 | 0.44 | 0.00 | 0.10 | 0.49 | 31-DEC-19:02 |
Annual Sum or Average | 0.996934E+12 | 0.00 | 4557.79 | 0.00 | 28.97 | 49.23 | 0.20 | 0.00 | 0.05 | ||||
Minimum of Months | 2228755.36 | 0.00 | 22.59 | 6779.23 | 0.00 | 24.52 | 26.61 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.257810E+12 | 0.00 | 744.00 | 415372.92 | 0.00 | 36.82 | 75.46 | 0.66 | 0.00 | 0.15 | 0.60 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.172902E+09 | 51018772.93 | 34.28 | 0.171458E+09 | 1444078.59 | 0.00 | 1.00 | 16-JAN-16:12 | 0.00 | 01-JAN-00:05 | 19051.94 | 17-JAN-16:12 | 19051.94 | 17-JAN-16:12 | 1456.42 | 24-JAN-16:14 | 4937.58 | 17-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.397996E+09 | 0.117336E+09 | 63.82 | 0.397877E+09 | 118765.86 | 0.00 | 1.00 | 02-FEB-16:12 | 0.00 | 01-FEB-00:05 | 19033.64 | 19-FEB-16:12 | 19033.64 | 19-FEB-16:12 | 346.34 | 28-FEB-19:04 | 4932.71 | 19-FEB-16:12 | 0.00 | 01-FEB-00:05 |
March | 0.210146E+10 | 0.612895E+09 | 252.43 | 0.202429E+10 | 77170519.47 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:05 | 21294.19 | 06-MAR-16:12 | 19445.36 | 28-MAR-15:12 | 5628.68 | 06-MAR-16:12 | 5480.54 | 06-MAR-16:12 | 0.00 | 01-MAR-00:05 |
April | 0.454529E+10 | 0.132140E+10 | 430.15 | 0.415841E+10 | 0.386885E+09 | 0.00 | 1.00 | 02-APR-15:12 | 0.00 | 01-APR-00:10 | 21897.26 | 30-APR-15:12 | 19546.55 | 16-APR-18:02 | 7783.09 | 30-APR-15:12 | 5609.23 | 30-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.873780E+10 | 0.254082E+10 | 653.33 | 0.773093E+10 | 0.100687E+10 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-01:10 | 22354.75 | 18-MAY-18:02 | 19666.09 | 20-MAY-15:12 | 9100.37 | 24-MAY-18:03 | 5702.18 | 18-MAY-18:02 | 0.00 | 01-MAY-00:10 |
June | 0.150063E+11 | 0.435376E+10 | 689.59 | 0.117553E+11 | 0.325100E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:52 | 23146.44 | 18-JUN-08:62 | 19656.90 | 04-JUN-15:12 | 10489.64 | 18-JUN-08:62 | 5861.75 | 19-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.190115E+11 | 0.557149E+10 | 724.51 | 0.142528E+11 | 0.475869E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 23179.33 | 30-JUL-08:62 | 18600.46 | 11-JUL-18:02 | 10548.69 | 28-JUL-08:03 | 5879.59 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.185677E+11 | 0.549655E+10 | 723.11 | 0.149479E+11 | 0.361981E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 23079.65 | 06-AUG-08:62 | 19326.24 | 25-AUG-18:01 | 10429.89 | 06-AUG-08:03 | 5841.32 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.121947E+11 | 0.353141E+10 | 675.96 | 0.998989E+10 | 0.220478E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 24015.72 | 22-SEP-18:02 | 19674.96 | 28-SEP-15:12 | 13047.29 | 22-SEP-18:02 | 6006.41 | 22-SEP-18:02 | 0.00 | 01-SEP-00:10 |
October | 0.822467E+10 | 0.237757E+10 | 605.45 | 0.693648E+10 | 0.128819E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:55 | 22736.37 | 25-OCT-08:62 | 19580.64 | 15-OCT-18:02 | 10040.61 | 23-OCT-18:03 | 5776.67 | 25-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.134445E+10 | 0.397002E+09 | 223.78 | 0.122846E+10 | 0.115995E+09 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-00:20 | 22000.04 | 10-NOV-09:02 | 19508.00 | 03-NOV-15:12 | 8723.63 | 10-NOV-09:02 | 5630.46 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.325953E+09 | 96623716.96 | 75.04 | 0.323300E+09 | 2653410.99 | 0.00 | 1.00 | 02-DEC-16:12 | 0.00 | 01-DEC-00:05 | 20403.60 | 25-DEC-16:12 | 18943.96 | 16-DEC-16:12 | 3468.14 | 25-DEC-16:12 | 5277.35 | 25-DEC-16:12 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.906306E+11 | 0.264679E+11 | 5151.45 | 0.739170E+11 | 0.167136E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.172902E+09 | 51018772.93 | 34.28 | 0.171458E+09 | 118765.86 | 0.00 | 1.00 | 0.00 | 19033.64 | 18600.46 | 346.34 | 4932.71 | 0.00 | |||||||
Maximum of Months | 0.190115E+11 | 0.557149E+10 | 724.51 | 0.149479E+11 | 0.475869E+10 | 0.00 | 1.00 | 0.00 | 24015.72 | 19674.96 | 13047.29 | 6006.41 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 32774998.28 | 9473196.27 | 6.93 | 31331960.84 | 1443037.44 | 0.00 | 1.00 | 17-JAN-16:12 | 0.00 | 01-JAN-00:05 | 18588.54 | 17-JAN-16:12 | 18588.54 | 17-JAN-16:12 | 1313.77 | 18-JAN-16:14 | 4817.75 | 17-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 95798708.06 | 28019660.45 | 20.89 | 95684532.16 | 114175.90 | 0.00 | 1.00 | 02-FEB-16:12 | 0.00 | 01-FEB-00:05 | 18567.05 | 19-FEB-16:12 | 18567.05 | 19-FEB-16:12 | 300.41 | 24-FEB-09:04 | 4812.05 | 19-FEB-16:12 | 0.00 | 01-FEB-00:05 |
March | 0.109077E+10 | 0.319195E+09 | 163.01 | 0.103823E+10 | 52541446.30 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:05 | 21187.55 | 27-MAR-21:01 | 18828.11 | 03-MAR-16:12 | 5916.33 | 06-MAR-16:12 | 5433.49 | 27-MAR-21:01 | 0.00 | 01-MAR-00:05 |
April | 0.317357E+10 | 0.927487E+09 | 357.13 | 0.283344E+10 | 0.340132E+09 | 0.00 | 1.00 | 02-APR-15:12 | 0.00 | 01-APR-00:10 | 21702.80 | 27-APR-18:02 | 19592.38 | 10-APR-20:41 | 7606.91 | 30-APR-15:12 | 5539.12 | 27-APR-18:02 | 0.00 | 01-APR-00:10 |
May | 0.646107E+10 | 0.188212E+10 | 524.02 | 0.561502E+10 | 0.846046E+09 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-01:10 | 22432.42 | 18-MAY-21:51 | 19998.98 | 28-MAY-08:51 | 9118.76 | 18-MAY-21:52 | 5735.27 | 31-MAY-08:51 | 0.00 | 01-MAY-00:10 |
June | 0.112104E+11 | 0.324717E+10 | 484.52 | 0.877231E+10 | 0.243814E+10 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-05:42 | 24608.31 | 21-JUN-18:32 | 20328.09 | 10-JUN-18:22 | 12696.30 | 25-JUN-07:51 | 6056.52 | 25-JUN-07:51 | 0.00 | 01-JUN-00:10 |
July | 0.168179E+11 | 0.491134E+10 | 614.68 | 0.125711E+11 | 0.424682E+10 | 0.00 | 1.00 | 01-JUL-08:31 | 0.00 | 01-JUL-05:12 | 25020.69 | 28-JUL-08:51 | 18297.42 | 01-JUL-18:52 | 13836.60 | 28-JUL-08:51 | 6123.67 | 30-JUL-08:51 | 0.00 | 01-JUL-00:10 |
August | 0.158947E+11 | 0.470381E+10 | 612.48 | 0.126249E+11 | 0.326981E+10 | 0.00 | 1.00 | 01-AUG-06:51 | 0.00 | 01-AUG-05:12 | 24716.40 | 06-AUG-08:51 | 19757.52 | 25-AUG-21:51 | 13611.32 | 06-AUG-08:51 | 6054.26 | 06-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.802704E+10 | 0.232560E+10 | 473.47 | 0.639441E+10 | 0.163263E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 25048.58 | 14-SEP-08:51 | 19889.43 | 10-SEP-21:51 | 14099.65 | 14-SEP-08:51 | 6100.48 | 14-SEP-08:51 | 0.00 | 01-SEP-00:10 |
October | 0.440949E+10 | 0.128622E+10 | 439.28 | 0.358912E+10 | 0.820370E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:55 | 23453.91 | 05-OCT-21:51 | 19964.71 | 19-OCT-16:41 | 10803.70 | 23-OCT-21:54 | 5859.56 | 05-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.624811E+09 | 0.185396E+09 | 142.47 | 0.543216E+09 | 81594961.08 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-00:10 | 21440.92 | 10-NOV-09:12 | 19503.31 | 03-NOV-16:31 | 8763.85 | 10-NOV-09:12 | 5486.09 | 10-NOV-09:12 | 0.00 | 01-NOV-00:10 |
December | 35886782.45 | 10328610.99 | 8.75 | 35070595.28 | 816187.17 | 0.00 | 1.00 | 03-DEC-16:12 | 0.00 | 01-DEC-00:05 | 18441.28 | 17-DEC-16:12 | 18441.28 | 17-DEC-16:12 | 2824.67 | 25-DEC-16:12 | 4778.49 | 17-DEC-16:12 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.678743E+11 | 0.198362E+11 | 3847.65 | 0.541438E+11 | 0.137305E+11 | 0.00 | ||||||||||||||
Minimum of Months | 32774998.28 | 9473196.27 | 6.93 | 31331960.84 | 114175.90 | 0.00 | 1.00 | 0.00 | 18441.28 | 18297.42 | 300.41 | 4778.49 | 0.00 | |||||||
Maximum of Months | 0.168179E+11 | 0.491134E+10 | 614.68 | 0.126249E+11 | 0.424682E+10 | 0.00 | 1.00 | 0.00 | 25048.58 | 20328.09 | 14099.65 | 6123.67 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.155210E+10 | 0.462438E+09 | 40.87 | 0.155210E+10 | -0.0 | 0.00 | 0.24 | 30-JAN-12:20 | 0.00 | 01-JAN-00:05 | 27456.52 | 30-JAN-12:10 | 27456.52 | 30-JAN-12:10 | 0.00 | 20-JAN-15:50 | 8063.03 | 30-JAN-12:10 | 0.00 | 01-JAN-00:05 |
February | 0.671329E+10 | 0.198779E+10 | 147.01 | 0.671329E+10 | -0.0 | 0.00 | 0.35 | 02-FEB-13:40 | 0.00 | 01-FEB-00:05 | 40162.15 | 02-FEB-13:40 | 40162.15 | 02-FEB-13:40 | 0.00 | 02-FEB-16:00 | 11605.05 | 02-FEB-13:30 | 0.00 | 01-FEB-00:05 |
March | 0.141742E+11 | 0.418627E+10 | 276.03 | 0.141255E+11 | 48656616.74 | 0.00 | 0.42 | 03-MAR-13:30 | 0.00 | 01-MAR-00:05 | 51048.88 | 03-MAR-13:30 | 51048.88 | 03-MAR-13:30 | 2172.97 | 27-MAR-13:10 | 14584.12 | 03-MAR-13:30 | 0.00 | 01-MAR-00:05 |
April | 0.234557E+11 | 0.692489E+10 | 418.96 | 0.231268E+11 | 0.328836E+09 | 0.00 | 0.48 | 07-APR-12:30 | 0.00 | 01-APR-00:10 | 60785.04 | 07-APR-12:30 | 60785.04 | 07-APR-12:30 | 2528.49 | 09-APR-12:10 | 17809.73 | 07-APR-12:30 | 0.00 | 01-APR-00:10 |
May | 0.376537E+11 | 0.111703E+11 | 632.65 | 0.363089E+11 | 0.134487E+10 | 0.00 | 0.38 | 30-MAY-14:10 | 0.00 | 01-MAY-00:10 | 47212.31 | 30-MAY-14:10 | 47212.31 | 30-MAY-14:10 | 4731.79 | 31-MAY-17:15 | 14897.93 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 0.598879E+11 | 0.177984E+11 | 716.83 | 0.524531E+11 | 0.743476E+10 | 0.00 | 0.50 | 19-JUN-14:10 | 0.00 | 03-JUN-02:70 | 63616.88 | 19-JUN-14:10 | 56530.28 | 19-JUN-14:10 | 10046.19 | 15-JUN-14:50 | 21244.91 | 19-JUN-14:10 | 0.00 | 01-JUN-00:10 |
July | 0.826137E+11 | 0.246913E+11 | 744.00 | 0.680402E+11 | 0.145736E+11 | 0.00 | 0.48 | 09-JUL-14:10 | 0.03 | 02-JUL-04:30 | 63972.72 | 09-JUL-14:10 | 54627.76 | 10-JUL-14:10 | 16405.86 | 20-JUL-15:00 | 19966.48 | 09-JUL-14:10 | 0.00 | 01-JUL-00:10 |
August | 0.882406E+11 | 0.265355E+11 | 744.00 | 0.773272E+11 | 0.109134E+11 | 0.00 | 0.56 | 16-AUG-14:10 | 0.01 | 08-AUG-04:00 | 74796.51 | 16-AUG-12:30 | 64688.29 | 18-AUG-14:10 | 17081.54 | 03-AUG-15:00 | 23514.24 | 16-AUG-14:10 | 0.00 | 01-AUG-00:10 |
September | 0.639328E+11 | 0.187065E+11 | 701.33 | 0.590582E+11 | 0.487456E+10 | 0.00 | 0.54 | 14-SEP-12:40 | 0.00 | 20-SEP-02:30 | 73069.34 | 14-SEP-12:30 | 66558.98 | 28-SEP-12:30 | 13780.50 | 07-SEP-15:00 | 21717.93 | 14-SEP-12:40 | 0.00 | 01-SEP-00:10 |
October | 0.582800E+11 | 0.168845E+11 | 647.08 | 0.552600E+11 | 0.301998E+10 | 0.00 | 0.56 | 04-OCT-12:10 | 0.00 | 01-OCT-03:00 | 74752.54 | 04-OCT-12:00 | 70162.38 | 04-OCT-12:10 | 8381.43 | 24-OCT-15:05 | 20912.85 | 04-OCT-12:10 | 0.00 | 01-OCT-00:10 |
November | 0.166617E+11 | 0.490886E+10 | 294.15 | 0.165663E+11 | 95318823.51 | 0.00 | 0.48 | 02-NOV-12:40 | 0.00 | 01-NOV-00:10 | 58022.78 | 02-NOV-12:40 | 58022.78 | 02-NOV-12:40 | 4353.06 | 10-NOV-10:00 | 16429.30 | 02-NOV-12:40 | 0.00 | 01-NOV-00:10 |
December | 0.827946E+10 | 0.243745E+10 | 160.63 | 0.827946E+10 | 0.00 | 0.00 | 0.44 | 17-DEC-13:00 | 0.00 | 01-DEC-00:05 | 52919.27 | 17-DEC-12:40 | 52919.27 | 17-DEC-12:40 | 0.00 | 18-DEC-15:50 | 15063.62 | 17-DEC-12:40 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.461445E+12 | 0.136694E+12 | 5523.56 | 0.418811E+12 | 0.426340E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.155210E+10 | 0.462438E+09 | 40.87 | 0.155210E+10 | -0.0 | 0.00 | 0.24 | 0.00 | 27456.52 | 27456.52 | 0.00 | 8063.03 | 0.00 | |||||||
Maximum of Months | 0.882406E+11 | 0.265355E+11 | 744.00 | 0.773272E+11 | 0.145736E+11 | 0.00 | 0.56 | 0.03 | 74796.51 | 70162.38 | 17081.54 | 23514.24 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.123961E+10 | 0.362940E+09 | 43.57 | 0.104851E+10 | 0.191097E+09 | 0.00 | 1.00 | 18-JAN-19:02 | 0.00 | 01-JAN-00:05 | 126137.81 | 24-JAN-09:02 | 108214.29 | 28-JAN-09:02 | 34712.25 | 24-JAN-09:02 | 32652.03 | 24-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.508789E+09 | 0.147240E+09 | 24.92 | 0.501749E+09 | 7040246.54 | 0.00 | 1.00 | 18-FEB-09:02 | 0.00 | 01-FEB-00:05 | 116627.48 | 18-FEB-09:02 | 116627.48 | 18-FEB-09:02 | 7199.37 | 28-FEB-19:02 | 30196.81 | 18-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.755768E+10 | 0.220802E+10 | 178.95 | 0.689371E+10 | 0.663966E+09 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:05 | 129276.26 | 06-MAR-16:12 | 118940.62 | 02-MAR-21:41 | 36520.56 | 06-MAR-16:12 | 33394.48 | 06-MAR-16:12 | 0.00 | 01-MAR-00:05 |
April | 0.265180E+11 | 0.769112E+10 | 384.39 | 0.228339E+11 | 0.368417E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:10 | 132864.94 | 10-APR-08:51 | 118240.79 | 10-APR-20:41 | 42608.76 | 30-APR-15:13 | 34204.49 | 10-APR-08:51 | 0.00 | 01-APR-00:10 |
May | 0.552305E+11 | 0.157947E+11 | 518.16 | 0.462232E+11 | 0.900723E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-03:00 | 145743.31 | 31-MAY-19:41 | 124310.92 | 28-MAY-08:51 | 60043.89 | 18-MAY-21:55 | 36782.34 | 31-MAY-19:41 | 0.00 | 01-MAY-00:10 |
June | 0.947797E+11 | 0.265573E+11 | 470.36 | 0.691447E+11 | 0.256350E+11 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-05:42 | 159979.07 | 24-JUN-20:21 | 124495.08 | 04-JUN-08:51 | 91742.56 | 24-JUN-20:21 | 39053.27 | 24-JUN-20:21 | 0.00 | 01-JUN-00:10 |
July | 0.143003E+12 | 0.402503E+11 | 596.72 | 0.978194E+11 | 0.451838E+11 | 0.00 | 1.00 | 01-JUL-08:31 | 0.00 | 01-JUL-05:12 | 160428.41 | 28-JUL-08:51 | 114382.33 | 11-JUL-18:02 | 94435.66 | 28-JUL-08:51 | 39564.86 | 30-JUL-08:51 | 0.00 | 01-JUL-00:10 |
August | 0.125783E+12 | 0.360544E+11 | 591.96 | 0.919453E+11 | 0.338381E+11 | 0.00 | 1.00 | 01-AUG-06:51 | 0.00 | 01-AUG-05:12 | 157504.67 | 06-AUG-08:51 | 120282.11 | 25-AUG-08:51 | 91162.40 | 06-AUG-08:51 | 38976.06 | 12-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.720677E+11 | 0.202482E+11 | 463.65 | 0.545621E+11 | 0.175056E+11 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 160195.23 | 14-SEP-08:51 | 122431.96 | 28-SEP-21:51 | 95386.55 | 14-SEP-08:51 | 39083.14 | 14-SEP-08:51 | 0.00 | 01-SEP-00:10 |
October | 0.376495E+11 | 0.107887E+11 | 425.39 | 0.295361E+11 | 0.811343E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:55 | 147781.93 | 23-OCT-21:51 | 118717.23 | 17-OCT-15:12 | 71186.74 | 23-OCT-21:52 | 37144.42 | 23-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.106131E+11 | 0.310916E+10 | 230.77 | 0.919189E+10 | 0.142124E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-01:40 | 136123.92 | 10-NOV-09:12 | 118942.74 | 04-NOV-19:41 | 55709.30 | 10-NOV-09:12 | 34904.90 | 10-NOV-09:12 | 0.00 | 01-NOV-00:10 |
December | 0.109366E+10 | 0.318424E+09 | 39.17 | 0.103004E+10 | 63615632.95 | 0.00 | 1.00 | 10-DEC-09:02 | 0.00 | 01-DEC-00:05 | 123848.34 | 25-DEC-09:02 | 116627.48 | 10-DEC-09:02 | 24702.80 | 25-DEC-09:02 | 32089.81 | 25-DEC-09:02 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.576045E+12 | 0.163531E+12 | 3968.01 | 0.430731E+12 | 0.145314E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.508789E+09 | 0.147240E+09 | 24.92 | 0.501749E+09 | 7040246.54 | 0.00 | 1.00 | 0.00 | 116627.48 | 108214.29 | 7199.37 | 30196.81 | 0.00 | |||||||
Maximum of Months | 0.143003E+12 | 0.402503E+11 | 596.72 | 0.978194E+11 | 0.451838E+11 | 0.00 | 1.00 | 0.00 | 160428.41 | 124495.08 | 95386.55 | 39564.86 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.182156E+09 | 53389839.29 | 31.14 | 0.180558E+09 | 1597096.99 | 0.00 | 1.00 | 17-JAN-16:12 | 0.00 | 01-JAN-00:05 | 17100.88 | 19-JAN-09:02 | 17100.88 | 19-JAN-09:02 | 1154.17 | 18-JAN-19:04 | 4432.70 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.342825E+09 | 0.100507E+09 | 66.39 | 0.342587E+09 | 237976.44 | 0.00 | 1.00 | 02-FEB-09:02 | 0.00 | 01-FEB-00:05 | 16919.90 | 19-FEB-16:12 | 16919.90 | 19-FEB-16:12 | 193.53 | 24-FEB-09:04 | 4384.90 | 19-FEB-16:12 | 0.00 | 01-FEB-00:05 |
March | 0.184794E+10 | 0.540272E+09 | 250.82 | 0.178247E+10 | 65471878.14 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:05 | 18550.82 | 27-MAR-15:12 | 17299.12 | 28-MAR-15:12 | 5808.00 | 06-MAR-16:12 | 4787.36 | 27-MAR-15:12 | 0.00 | 01-MAR-00:05 |
April | 0.448856E+10 | 0.130372E+10 | 441.81 | 0.410025E+10 | 0.388308E+09 | 0.00 | 1.00 | 02-APR-15:12 | 0.00 | 01-APR-00:10 | 19462.11 | 30-APR-15:12 | 17389.41 | 16-APR-18:02 | 6965.18 | 30-APR-15:12 | 4985.73 | 30-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.878700E+10 | 0.254630E+10 | 664.61 | 0.777717E+10 | 0.100983E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:50 | 19874.13 | 19-MAY-18:02 | 17507.57 | 20-MAY-15:12 | 8379.09 | 24-MAY-18:03 | 5069.47 | 19-MAY-18:02 | 0.00 | 01-MAY-00:10 |
June | 0.143235E+11 | 0.414401E+10 | 697.33 | 0.111308E+11 | 0.319275E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:52 | 20719.40 | 18-JUN-08:62 | 17463.91 | 04-JUN-15:12 | 9741.97 | 18-JUN-08:62 | 5229.92 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.187790E+11 | 0.547270E+10 | 730.63 | 0.139885E+11 | 0.479046E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 20534.61 | 24-JUL-08:62 | 16287.44 | 11-JUL-18:02 | 9287.32 | 24-JUL-08:03 | 5196.14 | 24-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.183808E+11 | 0.540284E+10 | 732.20 | 0.147268E+11 | 0.365405E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 20517.98 | 06-AUG-08:62 | 16995.84 | 25-AUG-15:11 | 9274.14 | 06-AUG-08:03 | 5225.94 | 16-AUG-15:12 | 0.00 | 01-AUG-00:10 |
September | 0.120989E+11 | 0.348547E+10 | 685.86 | 0.989956E+10 | 0.219931E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 21385.93 | 22-SEP-18:02 | 17523.01 | 28-SEP-15:12 | 11707.49 | 22-SEP-18:02 | 5345.83 | 22-SEP-18:02 | 0.00 | 01-SEP-00:10 |
October | 0.785232E+10 | 0.226441E+10 | 606.92 | 0.660542E+10 | 0.124690E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:55 | 20164.15 | 06-OCT-08:62 | 17395.60 | 15-OCT-18:02 | 9152.58 | 23-OCT-18:03 | 5126.23 | 06-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.157596E+10 | 0.462214E+09 | 232.72 | 0.145188E+10 | 0.124079E+09 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:20 | 19666.36 | 10-NOV-09:02 | 17331.76 | 03-NOV-15:12 | 7549.69 | 10-NOV-09:02 | 5027.70 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.420545E+09 | 0.123126E+09 | 72.75 | 0.418406E+09 | 2138537.38 | 0.00 | 1.00 | 02-DEC-09:02 | 0.00 | 01-DEC-00:05 | 17460.58 | 26-DEC-09:02 | 17063.57 | 20-DEC-09:02 | 1043.88 | 26-DEC-09:02 | 4525.35 | 26-DEC-09:02 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.890795E+11 | 0.258990E+11 | 5213.20 | 0.724044E+11 | 0.166751E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.182156E+09 | 53389839.29 | 31.14 | 0.180558E+09 | 237976.44 | 0.00 | 1.00 | 0.00 | 16919.90 | 16287.44 | 193.53 | 4384.90 | 0.00 | |||||||
Maximum of Months | 0.187790E+11 | 0.547270E+10 | 732.20 | 0.147268E+11 | 0.479046E+10 | 0.00 | 1.00 | 0.00 | 21385.93 | 17523.01 | 11707.49 | 5345.83 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 41948806.24 | 12474202.11 | 11.12 | 40422636.41 | 1526169.83 | 0.00 | 0.80 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 | 12651.19 | 19-JAN-09:02 | 12342.60 | 19-JAN-09:02 | 1499.43 | 18-JAN-16:14 | 3393.25 | 19-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 83741729.27 | 24614439.26 | 16.35 | 83636715.11 | 105014.16 | 0.00 | 1.00 | 19-FEB-09:02 | 0.00 | 01-FEB-00:05 | 16378.27 | 20-FEB-09:02 | 16378.27 | 20-FEB-09:02 | 256.50 | 24-FEB-09:04 | 4244.54 | 20-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.837193E+09 | 0.244988E+09 | 146.23 | 0.798248E+09 | 38944915.19 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:05 | 17703.57 | 02-MAR-16:12 | 16673.53 | 03-MAR-09:02 | 3877.88 | 06-MAR-16:12 | 4575.64 | 02-MAR-16:12 | 0.00 | 01-MAR-00:05 |
April | 0.320536E+10 | 0.932773E+09 | 377.92 | 0.286626E+10 | 0.339104E+09 | 0.00 | 1.00 | 03-APR-08:62 | 0.00 | 01-APR-00:10 | 18966.91 | 10-APR-08:51 | 17439.38 | 07-APR-08:51 | 6777.31 | 30-APR-15:12 | 4852.50 | 10-APR-08:51 | 0.00 | 01-APR-00:10 |
May | 0.670564E+10 | 0.193937E+10 | 536.02 | 0.587032E+10 | 0.835317E+09 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:40 | 20682.04 | 31-MAY-08:22 | 18400.08 | 30-MAY-07:52 | 8247.60 | 18-MAY-21:54 | 5172.08 | 31-MAY-08:22 | 0.00 | 01-MAY-00:10 |
June | 0.108136E+11 | 0.311134E+10 | 487.89 | 0.840041E+10 | 0.241320E+10 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-05:42 | 22040.51 | 27-JUN-08:32 | 18266.47 | 04-JUN-08:32 | 11170.58 | 18-JUN-08:52 | 5385.25 | 27-JUN-08:32 | 0.00 | 01-JUN-00:10 |
July | 0.164920E+11 | 0.478566E+10 | 620.00 | 0.122158E+11 | 0.427615E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-05:12 | 21942.78 | 23-JUL-20:11 | 16863.19 | 11-JUL-08:32 | 11871.24 | 23-JUL-08:21 | 5396.75 | 23-JUL-08:21 | 0.00 | 01-JUL-00:10 |
August | 0.155726E+11 | 0.457368E+10 | 621.87 | 0.122634E+11 | 0.330927E+10 | 0.00 | 1.00 | 01-AUG-06:51 | 0.00 | 01-AUG-05:12 | 21914.31 | 27-AUG-08:32 | 18452.63 | 25-AUG-08:32 | 12099.15 | 06-AUG-08:51 | 5361.42 | 27-AUG-08:32 | 0.00 | 01-AUG-00:10 |
September | 0.811475E+10 | 0.233195E+10 | 488.38 | 0.648559E+10 | 0.162917E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 22157.21 | 14-SEP-08:51 | 17695.67 | 10-SEP-08:32 | 12410.30 | 14-SEP-08:51 | 5395.02 | 14-SEP-08:51 | 0.00 | 01-SEP-00:10 |
October | 0.422952E+10 | 0.122402E+10 | 455.89 | 0.343520E+10 | 0.794316E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:55 | 20439.21 | 05-OCT-21:51 | 16745.78 | 30-OCT-08:62 | 9638.43 | 23-OCT-21:54 | 5130.22 | 05-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.775800E+09 | 0.228369E+09 | 150.93 | 0.681268E+09 | 94532818.75 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-00:10 | 19081.64 | 10-NOV-09:12 | 16671.78 | 04-NOV-19:41 | 7517.73 | 10-NOV-09:12 | 4875.85 | 10-NOV-09:12 | 0.00 | 01-NOV-00:10 |
December | 77122008.18 | 22675221.48 | 16.14 | 76019619.91 | 1102388.27 | 0.00 | 1.00 | 03-DEC-09:02 | 0.00 | 01-DEC-00:05 | 16409.08 | 20-DEC-09:02 | 16409.08 | 20-DEC-09:02 | 995.02 | 26-DEC-09:02 | 4252.73 | 20-DEC-09:02 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.669493E+11 | 0.194319E+11 | 3928.74 | 0.532166E+11 | 0.137327E+11 | 0.00 | ||||||||||||||
Minimum of Months | 41948806.24 | 12474202.11 | 11.12 | 40422636.41 | 105014.16 | 0.00 | 0.80 | 0.00 | 12651.19 | 12342.60 | 256.50 | 3393.25 | 0.00 | |||||||
Maximum of Months | 0.164920E+11 | 0.478566E+10 | 621.87 | 0.122634E+11 | 0.427615E+10 | 0.00 | 1.00 | 0.00 | 22157.21 | 18452.63 | 12410.30 | 5396.75 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 24607997.64 | 7213992.05 | 17.68 | 24451863.55 | 156134.09 | 0.00 | 1.00 | 16-JAN-16:12 | 0.00 | 01-JAN-00:05 | 5157.95 | 17-JAN-16:12 | 5157.95 | 17-JAN-16:12 | 383.40 | 24-JAN-09:05 | 1336.82 | 17-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 62332076.93 | 18402396.74 | 35.77 | 62332076.93 | -0.0 | 0.00 | 1.00 | 02-FEB-16:12 | 0.00 | 01-FEB-00:05 | 5155.12 | 19-FEB-16:12 | 5155.12 | 19-FEB-16:12 | 0.00 | 19-FEB-17:10 | 1336.07 | 19-FEB-16:12 | 0.00 | 01-FEB-00:05 |
March | 0.384325E+09 | 0.111977E+09 | 156.46 | 0.369690E+09 | 14635885.18 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:05 | 5581.72 | 27-MAR-15:12 | 5222.73 | 03-MAR-16:12 | 1727.87 | 06-MAR-16:12 | 1442.03 | 27-MAR-15:12 | 0.00 | 01-MAR-00:05 |
April | 0.953757E+09 | 0.276924E+09 | 317.77 | 0.872901E+09 | 80855506.35 | 0.00 | 1.00 | 02-APR-15:12 | 0.00 | 01-APR-00:10 | 5812.86 | 09-APR-08:62 | 5280.23 | 28-APR-15:12 | 2117.02 | 30-APR-15:12 | 1493.66 | 09-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.201871E+10 | 0.586754E+09 | 592.18 | 0.179141E+10 | 0.227304E+09 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-00:10 | 6074.61 | 19-MAY-18:02 | 5310.18 | 20-MAY-15:12 | 2646.17 | 19-MAY-08:62 | 1547.48 | 19-MAY-18:02 | 0.00 | 01-MAY-00:10 |
June | 0.383672E+10 | 0.111545E+10 | 685.18 | 0.300333E+10 | 0.833391E+09 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:52 | 6407.81 | 18-JUN-08:62 | 5304.01 | 04-JUN-15:12 | 3267.23 | 18-JUN-08:62 | 1609.03 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.498728E+10 | 0.146597E+10 | 724.27 | 0.376629E+10 | 0.122100E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 6387.53 | 30-JUL-08:62 | 5028.14 | 11-JUL-18:02 | 3195.06 | 24-JUL-08:62 | 1610.63 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.485140E+10 | 0.144003E+10 | 721.37 | 0.392950E+10 | 0.921896E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 6370.87 | 06-AUG-08:62 | 5221.85 | 25-AUG-18:01 | 3190.44 | 06-AUG-08:62 | 1602.59 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.296819E+10 | 0.860722E+09 | 656.10 | 0.242143E+10 | 0.546759E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 6633.33 | 22-SEP-18:02 | 5313.73 | 28-SEP-15:12 | 3923.89 | 22-SEP-18:02 | 1646.34 | 22-SEP-18:02 | 0.00 | 01-SEP-00:10 |
October | 0.176822E+10 | 0.510958E+09 | 520.55 | 0.146804E+10 | 0.300186E+09 | 0.00 | 1.00 | 02-OCT-15:12 | 0.00 | 01-OCT-02:50 | 6193.60 | 25-OCT-08:62 | 5287.16 | 15-OCT-18:02 | 2924.32 | 06-OCT-08:62 | 1570.35 | 25-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.188664E+09 | 55817519.04 | 120.27 | 0.171850E+09 | 16813471.87 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-00:10 | 5727.68 | 10-NOV-16:12 | 5289.03 | 03-NOV-15:12 | 1567.16 | 10-NOV-16:12 | 1475.09 | 10-NOV-16:12 | 0.00 | 01-NOV-00:10 |
December | 33561559.90 | 9877632.41 | 28.97 | 33307105.31 | 254454.59 | 0.00 | 1.00 | 02-DEC-16:12 | 0.00 | 01-DEC-00:05 | 5126.15 | 03-DEC-16:12 | 5126.15 | 03-DEC-16:12 | 789.17 | 25-DEC-16:12 | 1328.36 | 03-DEC-16:12 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.220778E+11 | 0.646009E+10 | 4576.57 | 0.179145E+11 | 0.416325E+10 | 0.00 | ||||||||||||||
Minimum of Months | 24607997.64 | 7213992.05 | 17.68 | 24451863.55 | -0.0 | 0.00 | 1.00 | 0.00 | 5126.15 | 5028.14 | 0.00 | 1328.36 | 0.00 | |||||||
Maximum of Months | 0.498728E+10 | 0.146597E+10 | 724.27 | 0.392950E+10 | 0.122100E+10 | 0.00 | 1.00 | 0.00 | 6633.33 | 5313.73 | 3923.89 | 1646.34 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 2882309.59 | 828066.73 | 1.60 | 2779646.51 | 102663.08 | 0.00 | 1.00 | 17-JAN-16:12 | 0.00 | 01-JAN-00:05 | 5025.40 | 17-JAN-16:12 | 5025.40 | 17-JAN-16:12 | 392.47 | 24-JAN-09:05 | 1302.51 | 17-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 10380369.26 | 3001256.73 | 8.79 | 10380219.39 | 149.86 | 0.00 | 1.00 | 19-FEB-16:12 | 0.00 | 01-FEB-00:05 | 5009.97 | 19-FEB-16:12 | 5009.97 | 19-FEB-16:12 | 1.00 | 20-FEB-19:05 | 1298.42 | 19-FEB-16:12 | 0.00 | 01-FEB-00:05 |
March | 0.174755E+09 | 51176606.38 | 93.05 | 0.165808E+09 | 8947163.68 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:05 | 5739.66 | 27-MAR-21:01 | 5093.62 | 03-MAR-16:12 | 1454.46 | 27-MAR-21:03 | 1471.05 | 27-MAR-21:01 | 0.00 | 01-MAR-00:05 |
April | 0.633927E+09 | 0.185071E+09 | 259.18 | 0.563973E+09 | 69953919.97 | 0.00 | 1.00 | 02-APR-15:12 | 0.00 | 01-APR-00:10 | 5857.66 | 27-APR-18:02 | 5310.27 | 10-APR-20:41 | 2067.69 | 30-APR-15:12 | 1495.17 | 27-APR-18:02 | 0.00 | 01-APR-00:10 |
May | 0.149953E+10 | 0.436397E+09 | 472.03 | 0.130706E+10 | 0.192468E+09 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-00:10 | 6061.08 | 18-MAY-21:51 | 5423.63 | 16-MAY-18:22 | 2594.01 | 19-MAY-08:53 | 1547.40 | 31-MAY-08:51 | 0.00 | 01-MAY-00:10 |
June | 0.295873E+10 | 0.858614E+09 | 486.94 | 0.233796E+10 | 0.620763E+09 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-05:42 | 6692.49 | 18-JUN-08:51 | 5584.03 | 10-JUN-18:22 | 3546.43 | 18-JUN-08:51 | 1641.11 | 25-JUN-07:51 | 0.00 | 01-JUN-00:10 |
July | 0.446895E+10 | 0.130891E+10 | 616.65 | 0.338384E+10 | 0.108511E+10 | 0.00 | 1.00 | 01-JUL-08:31 | 0.00 | 01-JUL-05:12 | 6803.00 | 28-JUL-08:51 | 5208.03 | 01-JUL-18:52 | 3855.11 | 28-JUL-08:51 | 1660.44 | 30-JUL-08:51 | 0.00 | 01-JUL-00:10 |
August | 0.420960E+10 | 0.124935E+10 | 613.95 | 0.337752E+10 | 0.832082E+09 | 0.00 | 1.00 | 01-AUG-06:51 | 0.00 | 01-AUG-05:12 | 6741.25 | 06-AUG-08:51 | 5362.53 | 25-AUG-21:51 | 3867.04 | 06-AUG-08:51 | 1644.21 | 06-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.198442E+10 | 0.575976E+09 | 462.82 | 0.158188E+10 | 0.402531E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 6829.48 | 14-SEP-08:51 | 5386.38 | 28-SEP-21:51 | 3997.07 | 14-SEP-08:51 | 1656.07 | 14-SEP-08:51 | 0.00 | 01-SEP-00:10 |
October | 0.873691E+09 | 0.254867E+09 | 350.72 | 0.690591E+09 | 0.183100E+09 | 0.00 | 1.00 | 02-OCT-21:51 | 0.00 | 01-OCT-03:50 | 6346.43 | 05-OCT-21:51 | 5395.38 | 19-OCT-16:41 | 3068.19 | 23-OCT-21:52 | 1584.43 | 05-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 58303196.58 | 17321934.89 | 64.97 | 49899240.44 | 8403956.15 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-00:10 | 5352.09 | 08-NOV-16:12 | 5258.31 | 03-NOV-16:31 | 1394.04 | 10-NOV-16:12 | 1384.54 | 08-NOV-16:12 | 0.00 | 01-NOV-00:10 |
December | 2020750.72 | 588902.06 | 1.01 | 1926249.11 | 94501.61 | 0.00 | 0.85 | 17-DEC-16:12 | 0.00 | 01-DEC-00:05 | 4109.62 | 17-DEC-16:12 | 4109.62 | 17-DEC-16:12 | 181.23 | 04-DEC-19:05 | 1091.83 | 17-DEC-16:12 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.168772E+11 | 0.494210E+10 | 3431.69 | 0.134736E+11 | 0.340356E+10 | 0.00 | ||||||||||||||
Minimum of Months | 2020750.72 | 588902.06 | 1.01 | 1926249.11 | 149.86 | 0.00 | 0.85 | 0.00 | 4109.62 | 4109.62 | 1.00 | 1091.83 | 0.00 | |||||||
Maximum of Months | 0.446895E+10 | 0.130891E+10 | 616.65 | 0.338384E+10 | 0.108511E+10 | 0.00 | 1.00 | 0.00 | 6829.48 | 5584.03 | 3997.07 | 1660.44 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.114034E+10 | 0.334070E+09 | 90.55 | 0.113857E+10 | 1771310.49 | 0.00 | 1.00 | 04-JAN-16:12 | 0.00 | 01-JAN-00:05 | 25140.34 | 17-JAN-16:12 | 25140.34 | 17-JAN-16:12 | 1469.90 | 24-JAN-19:04 | 6515.06 | 17-JAN-16:12 | 0.00 | 01-JAN-00:05 |
February | 0.166341E+10 | 0.487996E+09 | 132.56 | 0.166312E+10 | 292152.20 | 0.00 | 1.00 | 01-FEB-16:12 | 0.00 | 01-FEB-00:05 | 25228.30 | 18-FEB-16:12 | 25228.30 | 18-FEB-16:12 | 380.37 | 24-FEB-09:04 | 6538.48 | 18-FEB-16:12 | 0.00 | 01-FEB-00:05 |
March | 0.346140E+10 | 0.100629E+10 | 232.70 | 0.336466E+10 | 96738582.98 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:05 | 27387.98 | 27-MAR-18:02 | 25612.05 | 03-MAR-19:02 | 7858.45 | 06-MAR-16:12 | 7073.88 | 27-MAR-18:02 | 0.00 | 01-MAR-00:05 |
April | 0.569563E+10 | 0.165833E+10 | 372.63 | 0.518538E+10 | 0.510251E+09 | 0.00 | 1.00 | 02-APR-15:12 | 0.00 | 01-APR-00:10 | 28857.98 | 30-APR-15:12 | 25796.80 | 16-APR-18:02 | 10660.73 | 30-APR-15:12 | 7397.13 | 30-APR-15:12 | 0.00 | 01-APR-00:10 |
May | 0.100997E+11 | 0.295131E+10 | 614.27 | 0.877141E+10 | 0.132825E+10 | 0.00 | 1.00 | 01-MAY-15:12 | 0.00 | 01-MAY-00:10 | 29702.98 | 19-MAY-18:02 | 26048.16 | 20-MAY-15:12 | 12798.37 | 18-MAY-18:02 | 7568.58 | 19-MAY-18:02 | 0.00 | 01-MAY-00:10 |
June | 0.190745E+11 | 0.554218E+10 | 677.52 | 0.142263E+11 | 0.484825E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-06:52 | 31508.36 | 18-JUN-08:62 | 26037.24 | 04-JUN-15:12 | 16440.40 | 18-JUN-08:62 | 7900.69 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.263253E+11 | 0.769929E+10 | 721.96 | 0.191284E+11 | 0.719694E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 31448.53 | 28-JUL-08:62 | 24345.07 | 11-JUL-18:02 | 16209.96 | 28-JUL-08:62 | 7910.33 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.261748E+11 | 0.772841E+10 | 720.17 | 0.207396E+11 | 0.543514E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:51 | 31125.69 | 06-AUG-08:62 | 25325.62 | 25-AUG-18:01 | 15474.00 | 06-AUG-08:62 | 7834.15 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.179995E+11 | 0.517692E+10 | 667.89 | 0.145950E+11 | 0.340452E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:51 | 32667.60 | 22-SEP-18:02 | 26031.13 | 28-SEP-15:12 | 19792.15 | 22-SEP-18:02 | 8089.72 | 22-SEP-18:02 | 0.00 | 01-SEP-00:10 |
October | 0.135035E+11 | 0.385994E+10 | 586.85 | 0.115143E+11 | 0.198925E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-04:30 | 30211.25 | 25-OCT-08:62 | 25889.74 | 15-OCT-18:02 | 13871.00 | 06-OCT-08:62 | 7666.76 | 25-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.328587E+10 | 0.958159E+09 | 254.27 | 0.310726E+10 | 0.178610E+09 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-00:10 | 29184.17 | 10-NOV-09:02 | 25812.80 | 03-NOV-15:12 | 11873.25 | 10-NOV-09:02 | 7464.54 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.195930E+10 | 0.570488E+09 | 137.92 | 0.195405E+10 | 5252647.05 | 0.00 | 1.00 | 02-DEC-09:02 | 0.00 | 01-DEC-00:05 | 27106.82 | 25-DEC-16:12 | 25359.75 | 20-DEC-09:02 | 5563.04 | 25-DEC-16:12 | 7008.35 | 25-DEC-16:12 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.130383E+12 | 0.379734E+11 | 5209.26 | 0.105388E+12 | 0.249953E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.114034E+10 | 0.334070E+09 | 90.55 | 0.113857E+10 | 292152.20 | 0.00 | 1.00 | 0.00 | 25140.34 | 24345.07 | 380.37 | 6515.06 | 0.00 | |||||||
Maximum of Months | 0.263253E+11 | 0.772841E+10 | 721.96 | 0.207396E+11 | 0.719694E+10 | 0.00 | 1.00 | 0.00 | 32667.60 | 26048.16 | 19792.15 | 8089.72 | 0.00 |
Report: DXReportMonthly
For: PTAC_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 83066029.34 | 24777138.67 | 21.92 | 32599547.00 | 50466482.34 | 0.00 | 0.08 | 20-FEB-13:00 | 0.00 | 01-FEB-00:05 | 3217.89 | 20-FEB-13:00 | 1202.83 | 20-FEB-13:00 | 2015.06 | 20-FEB-13:00 | 946.58 | 20-FEB-13:00 | 0.00 | 01-FEB-00:05 |
March | 0.365600E+10 | 0.108376E+10 | 333.57 | 0.206412E+10 | 0.159188E+10 | 0.00 | 0.29 | 27-MAR-18:03 | 0.00 | 01-MAR-00:05 | 10980.99 | 27-MAR-18:03 | 7297.48 | 27-MAR-18:03 | 4420.13 | 27-MAR-13:00 | 3175.71 | 27-MAR-18:03 | 0.00 | 01-MAR-00:05 |
April | 0.951417E+10 | 0.281217E+10 | 579.87 | 0.642745E+10 | 0.308672E+10 | 0.00 | 0.37 | 08-APR-12:30 | 0.00 | 01-APR-00:50 | 13829.80 | 08-APR-12:20 | 11535.67 | 07-APR-15:10 | 4736.68 | 16-APR-09:53 | 3979.90 | 08-APR-12:00 | 0.00 | 01-APR-00:10 |
May | 0.177378E+11 | 0.522577E+10 | 744.00 | 0.128397E+11 | 0.489807E+10 | 0.00 | 0.44 | 31-MAY-18:30 | 0.00 | 04-MAY-08:62 | 16892.36 | 31-MAY-18:15 | 12453.54 | 30-MAY-15:10 | 4938.66 | 31-MAY-18:30 | 4773.50 | 31-MAY-18:15 | 0.00 | 01-MAY-00:10 |
June | 0.288075E+11 | 0.840802E+10 | 720.00 | 0.195470E+11 | 0.926049E+10 | 0.00 | 0.61 | 19-JUN-18:03 | 0.12 | 04-JUN-04:30 | 23582.40 | 19-JUN-18:03 | 17133.80 | 19-JUN-18:13 | 7155.57 | 15-JUN-21:52 | 7397.95 | 19-JUN-18:03 | 0.00 | 01-JUN-00:10 |
July | 0.381778E+11 | 0.111337E+11 | 744.00 | 0.240904E+11 | 0.140874E+11 | 0.00 | 0.58 | 08-JUL-12:30 | 0.18 | 02-JUL-04:30 | 23425.73 | 08-JUL-12:30 | 15250.13 | 10-JUL-15:10 | 9529.97 | 20-JUL-18:20 | 7214.25 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 0.366320E+11 | 0.108038E+11 | 744.00 | 0.249588E+11 | 0.116732E+11 | 0.00 | 0.62 | 16-AUG-15:10 | 0.14 | 20-AUG-05:00 | 24738.24 | 16-AUG-15:10 | 16740.16 | 24-AUG-15:10 | 10138.82 | 16-AUG-22:00 | 7645.24 | 16-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 0.246184E+11 | 0.717443E+10 | 720.00 | 0.173568E+11 | 0.726159E+10 | 0.00 | 0.51 | 07-SEP-14:10 | 0.05 | 24-SEP-05:00 | 20064.25 | 07-SEP-14:10 | 14618.92 | 01-SEP-14:10 | 7066.19 | 13-SEP-21:10 | 5845.52 | 07-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 0.174596E+11 | 0.510859E+10 | 728.97 | 0.121852E+11 | 0.527442E+10 | 0.00 | 0.44 | 04-OCT-15:10 | 0.00 | 09-OCT-04:00 | 16457.84 | 04-OCT-15:10 | 12405.88 | 04-OCT-14:10 | 5131.13 | 25-OCT-10:25 | 4660.81 | 04-OCT-15:10 | 0.00 | 01-OCT-00:10 |
November | 0.415228E+10 | 0.123320E+10 | 346.31 | 0.258193E+10 | 0.157034E+10 | 0.00 | 0.30 | 04-NOV-12:30 | 0.00 | 01-NOV-05:10 | 10702.84 | 04-NOV-12:30 | 7762.89 | 04-NOV-12:30 | 3570.46 | 18-NOV-11:40 | 3107.66 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 0.374541E+09 | 0.111354E+09 | 64.53 | 0.152281E+09 | 0.222260E+09 | 0.00 | 0.11 | 03-DEC-13:00 | 0.00 | 01-DEC-00:05 | 4234.22 | 03-DEC-13:00 | 1798.68 | 03-DEC-13:00 | 2435.54 | 03-DEC-13:00 | 1249.18 | 03-DEC-13:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.181213E+12 | 0.531195E+11 | 5747.16 | 0.122236E+12 | 0.589768E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.381778E+11 | 0.111337E+11 | 744.00 | 0.249588E+11 | 0.140874E+11 | 0.00 | 0.62 | 0.18 | 24738.24 | 17133.80 | 10138.82 | 7645.24 | 0.00 |
Report: DXReportMonthly
For: PTAC_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.415166E+09 | 0.122301E+09 | 72.74 | 0.264063E+09 | 0.151103E+09 | 0.00 | 0.24 | 27-MAR-13:20 | 0.00 | 01-MAR-00:05 | 5039.29 | 27-MAR-13:20 | 2863.23 | 28-MAR-12:40 | 2679.02 | 27-MAR-13:10 | 1427.94 | 27-MAR-13:20 | 0.00 | 01-MAR-00:05 |
April | 0.270756E+10 | 0.794196E+09 | 314.03 | 0.210699E+10 | 0.600567E+09 | 0.00 | 0.47 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 8705.20 | 08-APR-12:10 | 7759.98 | 08-APR-12:20 | 3002.28 | 06-APR-10:25 | 2478.24 | 08-APR-12:00 | 0.00 | 01-APR-00:10 |
May | 0.741294E+10 | 0.217639E+10 | 681.00 | 0.608680E+10 | 0.132613E+10 | 0.00 | 0.58 | 30-MAY-12:20 | 0.00 | 01-MAY-00:10 | 10351.00 | 31-MAY-13:00 | 9955.94 | 30-MAY-12:20 | 2302.15 | 01-MAY-10:25 | 3159.16 | 30-MAY-12:30 | 0.00 | 01-MAY-00:10 |
June | 0.132333E+11 | 0.388844E+10 | 720.00 | 0.105766E+11 | 0.265672E+10 | 0.00 | 0.74 | 19-JUN-12:30 | 0.03 | 04-JUN-04:00 | 13297.84 | 19-JUN-12:50 | 11522.69 | 19-JUN-12:30 | 2453.18 | 18-JUN-11:00 | 4490.13 | 19-JUN-12:10 | 0.00 | 01-JUN-00:10 |
July | 0.181230E+11 | 0.535157E+10 | 744.00 | 0.139385E+11 | 0.418449E+10 | 0.00 | 0.73 | 08-JUL-12:00 | 0.08 | 02-JUL-04:30 | 13842.60 | 08-JUL-12:10 | 11325.00 | 07-JUL-12:20 | 3102.47 | 09-JUL-09:53 | 4306.86 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 0.174596E+11 | 0.520065E+10 | 744.00 | 0.140443E+11 | 0.341533E+10 | 0.00 | 0.75 | 16-AUG-12:50 | 0.06 | 20-AUG-05:00 | 14290.30 | 16-AUG-12:40 | 11407.66 | 16-AUG-13:00 | 3051.63 | 16-AUG-12:00 | 4416.33 | 16-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 0.105778E+11 | 0.309145E+10 | 705.58 | 0.857292E+10 | 0.200483E+10 | 0.00 | 0.60 | 01-SEP-13:00 | 0.00 | 20-SEP-05:10 | 11088.00 | 07-SEP-12:50 | 10148.20 | 01-SEP-13:00 | 2285.61 | 27-SEP-11:00 | 3299.87 | 01-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 0.570782E+10 | 0.166339E+10 | 535.87 | 0.439014E+10 | 0.131769E+10 | 0.00 | 0.49 | 04-OCT-12:50 | 0.00 | 01-OCT-02:50 | 9064.39 | 13-OCT-12:30 | 7920.84 | 04-OCT-13:00 | 3086.27 | 02-OCT-09:30 | 2576.07 | 04-OCT-12:50 | 0.00 | 01-OCT-00:10 |
November | 0.629761E+09 | 0.184867E+09 | 110.11 | 0.403550E+09 | 0.226211E+09 | 0.00 | 0.34 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 | 6303.34 | 04-NOV-12:10 | 4812.61 | 04-NOV-12:30 | 2582.77 | 10-NOV-10:00 | 1809.90 | 04-NOV-12:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.762669E+11 | 0.224733E+11 | 4627.33 | 0.603838E+11 | 0.158831E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.181230E+11 | 0.535157E+10 | 744.00 | 0.140443E+11 | 0.418449E+10 | 0.00 | 0.75 | 0.08 | 14290.30 | 11522.69 | 3102.47 | 4490.13 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_1 COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 53309181.30 | 17855752.07 | 7.58 | 30891983.40 | 22417197.90 | 0.00 | 0.08 | 18-JAN-16:00 | 0.00 | 01-JAN-00:05 | 3744.13 | 18-JAN-16:00 | 2116.02 | 18-JAN-16:00 | 1628.11 | 18-JAN-16:00 | 1246.64 | 18-JAN-16:00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.321496E+10 | 0.100510E+10 | 87.21 | 0.257623E+10 | 0.638731E+09 | 0.00 | 0.71 | 27-MAR-16:00 | 0.00 | 01-MAR-00:05 | 40327.60 | 27-MAR-16:00 | 31399.64 | 27-MAR-16:00 | 13508.06 | 27-MAR-12:40 | 11457.41 | 27-MAR-16:00 | 0.00 |
April | 0.196422E+11 | 0.596800E+10 | 320.42 | 0.154531E+11 | 0.418904E+10 | 0.00 | 0.85 | 07-APR-19:10 | 0.00 | 01-APR-00:10 | 50746.67 | 07-APR-19:10 | 50746.67 | 07-APR-19:10 | 15090.27 | 09-APR-11:00 | 13839.29 | 07-APR-19:10 | 0.00 |
May | 0.591135E+11 | 0.174624E+11 | 692.50 | 0.446402E+11 | 0.144733E+11 | 0.00 | 1.00 | 31-MAY-18:02 | 0.00 | 01-MAY-00:10 | 72087.39 | 31-MAY-18:10 | 59499.59 | 30-MAY-15:10 | 24136.50 | 31-MAY-18:02 | 18337.93 | 31-MAY-18:20 | 0.00 |
June | 0.149107E+12 | 0.389088E+11 | 720.00 | 0.911543E+11 | 0.579530E+11 | 0.00 | 1.00 | 01-JUN-18:02 | 0.20 | 03-JUN-04:00 | 124025.94 | 19-JUN-18:03 | 87982.56 | 19-JUN-18:13 | 61956.12 | 15-JUN-21:52 | 32463.70 | 19-JUN-17:03 | 0.00 |
July | 0.233877E+12 | 0.578893E+11 | 744.00 | 0.126017E+12 | 0.107860E+12 | 0.00 | 1.00 | 01-JUL-08:31 | 0.66 | 11-JUL-05:10 | 151069.11 | 20-JUL-21:00 | 80048.42 | 10-JUL-18:13 | 79280.29 | 19-JUL-22:00 | 36625.46 | 20-JUL-21:00 | 0.00 |
August | 0.203706E+12 | 0.517609E+11 | 744.00 | 0.127538E+12 | 0.761687E+11 | 0.00 | 1.00 | 01-AUG-00:10 | 0.37 | 08-AUG-05:00 | 156138.41 | 16-AUG-22:00 | 92394.50 | 04-AUG-19:10 | 90087.13 | 16-AUG-22:50 | 37779.21 | 16-AUG-22:00 | 0.00 |
September | 0.115671E+12 | 0.311413E+11 | 718.17 | 0.777627E+11 | 0.379082E+11 | 0.00 | 1.00 | 01-SEP-00:10 | 0.00 | 24-SEP-04:40 | 119939.37 | 13-SEP-21:00 | 72899.83 | 01-SEP-20:10 | 62219.54 | 13-SEP-21:00 | 29443.94 | 13-SEP-21:00 | 0.00 |
October | 0.546352E+11 | 0.156518E+11 | 573.67 | 0.354980E+11 | 0.191372E+11 | 0.00 | 1.00 | 04-OCT-15:10 | 0.00 | 01-OCT-02:40 | 69934.60 | 05-OCT-19:10 | 50006.90 | 04-OCT-15:10 | 31085.80 | 05-OCT-19:10 | 17793.92 | 05-OCT-19:10 | 0.00 |
November | 0.601449E+10 | 0.191371E+10 | 181.19 | 0.452022E+10 | 0.149427E+10 | 0.00 | 0.56 | 10-NOV-08:00 | 0.00 | 01-NOV-00:10 | 30457.79 | 10-NOV-08:00 | 22517.03 | 04-NOV-12:30 | 15516.32 | 10-NOV-08:00 | 9009.94 | 10-NOV-08:00 | 0.00 |
December | 73968757.88 | 24495208.26 | 4.67 | 73968757.88 | 0.00 | 0.00 | 0.12 | 17-DEC-13:00 | 0.00 | 01-DEC-00:05 | 5738.81 | 17-DEC-13:00 | 5738.81 | 17-DEC-13:00 | 0.00 | 17-DEC-12:10 | 1893.03 | 17-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.845109E+12 | 0.221744E+12 | 4793.40 | 0.525264E+12 | 0.319845E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.233877E+12 | 0.578893E+11 | 744.00 | 0.127538E+12 | 0.107860E+12 | 0.00 | 1.00 | 0.66 | 156138.41 | 92394.50 | 90087.13 | 37779.21 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_6 COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.184732E+10 | 0.559978E+09 | 55.17 | 0.149535E+10 | 0.351970E+09 | 0.00 | 0.80 | 27-MAR-16:00 | 0.00 | 01-MAR-00:05 | 34572.36 | 27-MAR-16:00 | 29113.84 | 27-MAR-16:00 | 11543.09 | 27-MAR-12:25 | 9578.91 | 27-MAR-16:00 | 0.00 |
April | 0.142932E+11 | 0.423892E+10 | 253.10 | 0.118679E+11 | 0.242536E+10 | 0.00 | 1.00 | 07-APR-19:00 | 0.00 | 01-APR-00:10 | 46307.20 | 07-APR-19:00 | 46307.20 | 07-APR-19:00 | 12439.13 | 09-APR-11:00 | 12100.30 | 07-APR-19:00 | 0.00 |
May | 0.494061E+11 | 0.141204E+11 | 641.72 | 0.388070E+11 | 0.105991E+11 | 0.00 | 1.00 | 19-MAY-18:03 | 0.00 | 01-MAY-00:10 | 68406.76 | 31-MAY-18:10 | 60123.30 | 30-MAY-15:10 | 24091.53 | 31-MAY-18:10 | 17371.79 | 31-MAY-18:10 | 0.00 |
June | 0.144908E+12 | 0.370540E+11 | 720.00 | 0.874247E+11 | 0.574831E+11 | 0.00 | 1.00 | 01-JUN-10:50 | 0.11 | 03-JUN-04:30 | 124272.34 | 19-JUN-16:52 | 81512.52 | 19-JUN-18:03 | 63458.45 | 25-JUN-06:53 | 32573.41 | 19-JUN-16:52 | 0.00 |
July | 0.233680E+12 | 0.575249E+11 | 744.00 | 0.121739E+12 | 0.111942E+12 | 0.00 | 1.00 | 01-JUL-00:10 | 0.75 | 11-JUL-06:10 | 146234.19 | 20-JUL-21:10 | 75490.59 | 10-JUL-15:10 | 78738.85 | 20-JUL-21:10 | 35338.89 | 20-JUL-21:10 | 0.00 |
August | 0.193861E+12 | 0.486517E+11 | 744.00 | 0.118354E+12 | 0.755067E+11 | 0.00 | 1.00 | 01-AUG-00:10 | 0.35 | 20-AUG-03:00 | 150218.33 | 16-AUG-22:00 | 83645.85 | 04-AUG-21:10 | 86480.37 | 16-AUG-22:00 | 36295.81 | 16-AUG-22:00 | 0.00 |
September | 0.102497E+12 | 0.269782E+11 | 696.67 | 0.681456E+11 | 0.343512E+11 | 0.00 | 1.00 | 01-SEP-00:10 | 0.00 | 11-SEP-04:40 | 112094.86 | 13-SEP-21:10 | 65195.95 | 01-SEP-21:10 | 57187.50 | 13-SEP-21:10 | 27533.49 | 13-SEP-21:10 | 0.00 |
October | 0.416839E+11 | 0.116084E+11 | 471.83 | 0.260002E+11 | 0.156837E+11 | 0.00 | 1.00 | 03-OCT-14:30 | 0.00 | 01-OCT-00:10 | 67435.38 | 05-OCT-23:00 | 38459.50 | 04-OCT-15:13 | 32190.22 | 05-OCT-23:00 | 17086.70 | 05-OCT-23:00 | 0.00 |
November | 0.283260E+10 | 0.895561E+09 | 104.00 | 0.213226E+10 | 0.700341E+09 | 0.00 | 0.58 | 10-NOV-08:00 | 0.00 | 01-NOV-00:10 | 23619.65 | 10-NOV-08:00 | 15531.02 | 04-NOV-17:10 | 12996.51 | 10-NOV-08:00 | 6945.85 | 10-NOV-08:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.785009E+12 | 0.201632E+12 | 4430.49 | 0.475966E+12 | 0.309043E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.233680E+12 | 0.575249E+11 | 744.00 | 0.121739E+12 | 0.111942E+12 | 0.00 | 1.00 | 0.75 | 150218.33 | 83645.85 | 86480.37 | 36295.81 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_0 COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.685760E+09 | 0.213681E+09 | 47.37 | 0.531797E+09 | 0.153964E+09 | 0.00 | 0.49 | 07-APR-19:10 | 0.00 | 01-APR-00:10 | 13223.33 | 07-APR-19:10 | 10595.44 | 07-APR-19:10 | 2703.48 | 07-APR-20:00 | 3955.89 | 07-APR-19:10 | 0.00 | 01-APR-00:10 |
May | 0.638482E+10 | 0.191499E+10 | 239.73 | 0.459879E+10 | 0.178603E+10 | 0.00 | 0.79 | 31-MAY-21:00 | 0.00 | 01-MAY-00:10 | 24682.86 | 31-MAY-19:53 | 15857.60 | 29-MAY-19:20 | 10690.82 | 31-MAY-19:53 | 6465.21 | 31-MAY-19:53 | 0.00 | 01-MAY-00:10 |
June | 0.427299E+11 | 0.118656E+11 | 715.50 | 0.245359E+11 | 0.181940E+11 | 0.00 | 1.00 | 14-JUN-19:03 | 0.00 | 01-JUN-03:30 | 41684.99 | 19-JUN-19:20 | 28533.00 | 19-JUN-19:20 | 20494.81 | 24-JUN-18:40 | 11400.66 | 19-JUN-19:10 | 0.00 | 01-JUN-00:10 |
July | 0.776081E+11 | 0.202961E+11 | 744.00 | 0.411239E+11 | 0.364842E+11 | 0.00 | 1.00 | 02-JUL-19:10 | 0.44 | 02-JUL-05:00 | 55048.85 | 20-JUL-21:00 | 28950.39 | 20-JUL-21:00 | 26168.64 | 20-JUL-19:10 | 13702.24 | 20-JUL-21:00 | 0.00 | 01-JUL-00:10 |
August | 0.766680E+11 | 0.202759E+11 | 744.00 | 0.467150E+11 | 0.299530E+11 | 0.00 | 1.00 | 01-AUG-17:03 | 0.33 | 08-AUG-04:00 | 59324.53 | 03-AUG-20:00 | 37228.78 | 04-AUG-19:20 | 28704.09 | 03-AUG-20:00 | 15569.70 | 04-AUG-19:10 | 0.00 | 01-AUG-00:10 |
September | 0.565834E+11 | 0.150495E+11 | 720.00 | 0.370619E+11 | 0.195214E+11 | 0.00 | 1.00 | 01-SEP-05:10 | 0.15 | 24-SEP-05:00 | 52341.53 | 13-SEP-20:00 | 31049.08 | 14-SEP-19:20 | 22704.78 | 22-SEP-18:02 | 12785.41 | 13-SEP-20:00 | 0.00 | 01-SEP-00:10 |
October | 0.372953E+11 | 0.101552E+11 | 702.17 | 0.250075E+11 | 0.122878E+11 | 0.00 | 1.00 | 02-OCT-19:10 | 0.00 | 08-OCT-02:70 | 41646.74 | 05-OCT-19:20 | 25824.00 | 03-OCT-20:00 | 16776.71 | 05-OCT-19:10 | 10081.26 | 05-OCT-19:20 | 0.00 | 01-OCT-00:10 |
November | 0.966882E+10 | 0.281059E+10 | 354.08 | 0.728494E+10 | 0.238387E+10 | 0.00 | 0.90 | 09-NOV-20:20 | 0.00 | 01-NOV-03:10 | 27125.87 | 09-NOV-20:20 | 17322.05 | 03-NOV-20:00 | 10516.21 | 09-NOV-20:10 | 6893.72 | 09-NOV-20:20 | 0.00 | 01-NOV-00:10 |
December | 13141179.33 | 4200711.13 | 2.00 | 8991051.98 | 4150127.35 | 0.00 | 0.11 | 04-DEC-21:00 | 0.00 | 01-DEC-00:05 | 2570.29 | 04-DEC-21:00 | 1770.77 | 04-DEC-21:00 | 799.53 | 04-DEC-21:00 | 816.17 | 04-DEC-21:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.307637E+12 | 0.825857E+11 | 4268.84 | 0.186869E+12 | 0.120768E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.776081E+11 | 0.202961E+11 | 744.00 | 0.467150E+11 | 0.364842E+11 | 0.00 | 1.00 | 0.44 | 59324.53 | 37228.78 | 28704.09 | 15569.70 | 0.00 |
Report: DXReportMonthly
For: PSZ_LAUNDRY COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.629950E+11 | 0.153290E+11 | 744.00 | 0.627940E+11 | 0.200986E+09 | 0.00 | 1.00 | 01-JAN-19:30 | 0.45 | 02-JAN-05:00 | 43424.17 | 23-JAN-21:00 | 42988.85 | 23-JAN-21:00 | 625.81 | 03-JAN-19:40 | 10031.23 | 23-JAN-21:00 | 0.00 | 01-JAN-00:05 |
February | 0.568393E+11 | 0.138289E+11 | 672.00 | 0.567334E+11 | 0.105903E+09 | 0.00 | 1.00 | 01-FEB-19:02 | 0.45 | 06-FEB-05:00 | 43053.37 | 23-FEB-21:00 | 42793.85 | 01-FEB-21:00 | 447.54 | 02-FEB-06:20 | 9939.52 | 23-FEB-21:00 | 0.00 | 01-FEB-00:05 |
March | 0.648990E+11 | 0.157387E+11 | 744.00 | 0.645857E+11 | 0.313361E+09 | 0.00 | 1.00 | 01-MAR-19:03 | 0.48 | 23-MAR-04:00 | 44463.65 | 27-MAR-20:00 | 44035.87 | 27-MAR-20:00 | 868.35 | 06-MAR-19:02 | 10294.91 | 27-MAR-20:00 | 0.00 | 01-MAR-00:05 |
April | 0.642196E+11 | 0.155488E+11 | 720.00 | 0.637693E+11 | 0.450269E+09 | 0.00 | 1.00 | 01-APR-18:03 | 0.49 | 03-APR-04:00 | 45186.27 | 07-APR-20:00 | 44700.85 | 07-APR-20:00 | 776.03 | 07-APR-18:02 | 10714.41 | 07-APR-19:20 | 0.00 | 01-APR-00:10 |
May | 0.684171E+11 | 0.165694E+11 | 744.00 | 0.677635E+11 | 0.653605E+09 | 0.00 | 1.00 | 01-MAY-18:02 | 0.51 | 01-MAY-04:00 | 45393.66 | 31-MAY-19:53 | 44901.64 | 30-MAY-19:51 | 974.81 | 31-MAY-18:02 | 10530.46 | 31-MAY-19:53 | 0.00 | 01-MAY-00:10 |
June | 0.679494E+11 | 0.168036E+11 | 720.00 | 0.669274E+11 | 0.102192E+10 | 0.00 | 1.00 | 01-JUN-17:20 | 0.53 | 03-JUN-05:00 | 46266.04 | 19-JUN-20:00 | 45538.87 | 19-JUN-20:00 | 1147.17 | 15-JUN-18:02 | 12833.86 | 19-JUN-19:20 | 0.00 | 01-JUN-00:10 |
July | 0.710709E+11 | 0.181849E+11 | 744.00 | 0.697161E+11 | 0.135480E+10 | 0.00 | 1.00 | 01-JUL-17:25 | 0.55 | 05-JUL-04:00 | 46001.61 | 07-JUL-20:00 | 45379.78 | 10-JUL-20:00 | 1298.58 | 20-JUL-18:02 | 12133.36 | 10-JUL-19:40 | 0.00 | 01-JUL-00:10 |
August | 0.711288E+11 | 0.182587E+11 | 744.00 | 0.699937E+11 | 0.113510E+10 | 0.00 | 1.00 | 01-AUG-17:03 | 0.54 | 26-AUG-05:00 | 46265.32 | 04-AUG-20:00 | 45559.94 | 04-AUG-20:00 | 1309.24 | 03-AUG-18:02 | 13322.75 | 04-AUG-19:20 | 0.00 | 01-AUG-00:10 |
September | 0.671491E+11 | 0.164290E+11 | 720.00 | 0.662928E+11 | 0.856311E+09 | 0.00 | 1.00 | 01-SEP-17:15 | 0.53 | 30-SEP-05:00 | 45669.92 | 01-SEP-20:00 | 45175.27 | 01-SEP-20:00 | 1153.72 | 22-SEP-18:02 | 11671.62 | 01-SEP-20:00 | 0.00 | 01-SEP-00:10 |
October | 0.677476E+11 | 0.163660E+11 | 744.00 | 0.671118E+11 | 0.635792E+09 | 0.00 | 1.00 | 01-OCT-18:02 | 0.51 | 28-OCT-05:00 | 45068.16 | 04-OCT-20:00 | 44529.50 | 04-OCT-20:00 | 919.38 | 05-OCT-18:02 | 10448.09 | 04-OCT-20:00 | 0.00 | 01-OCT-00:10 |
November | 0.631021E+11 | 0.152952E+11 | 720.00 | 0.627480E+11 | 0.354184E+09 | 0.00 | 1.00 | 01-NOV-18:02 | 0.48 | 24-NOV-05:00 | 44246.48 | 03-NOV-20:00 | 43854.51 | 03-NOV-20:00 | 702.73 | 09-NOV-19:02 | 10240.96 | 03-NOV-20:00 | 0.00 | 01-NOV-00:10 |
December | 0.635989E+11 | 0.154567E+11 | 744.00 | 0.633860E+11 | 0.212865E+09 | 0.00 | 1.00 | 01-DEC-19:02 | 0.48 | 15-DEC-05:00 | 43443.11 | 04-DEC-21:00 | 43047.92 | 19-DEC-21:00 | 495.14 | 04-DEC-19:03 | 10038.04 | 04-DEC-21:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.789117E+12 | 0.193809E+12 | 8760.00 | 0.781822E+12 | 0.729509E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.568393E+11 | 0.138289E+11 | 672.00 | 0.567334E+11 | 0.105903E+09 | 0.00 | 1.00 | 0.45 | 43053.37 | 42793.85 | 447.54 | 9939.52 | 0.00 | |||||||
Maximum of Months | 0.711288E+11 | 0.182587E+11 | 744.00 | 0.699937E+11 | 0.135480E+10 | 0.00 | 1.00 | 0.55 | 46266.04 | 45559.94 | 1309.24 | 13322.75 | 0.00 |
Report: DXReportMonthly
For: PSZ_CAFE COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 31432127.62 | 9066318.39 | 4.50 | 31431150.93 | 976.69 | 0.00 | 0.17 | 17-JAN-13:50 | 0.00 | 01-JAN-00:05 | 3486.00 | 17-JAN-13:50 | 3486.00 | 17-JAN-13:50 | 1.63 | 17-JAN-12:00 | 995.11 | 17-JAN-13:50 | 0.00 | 01-JAN-00:05 |
February | 3738675.27 | 1101888.84 | 1.58 | 3735474.14 | 3201.13 | 0.00 | 0.07 | 20-FEB-13:00 | 0.00 | 01-FEB-00:05 | 1459.91 | 20-FEB-13:00 | 1459.91 | 20-FEB-13:00 | 3.39 | 19-FEB-12:50 | 427.56 | 20-FEB-13:00 | 0.00 | 01-FEB-00:05 |
March | 0.936573E+09 | 0.259095E+09 | 62.47 | 0.828940E+09 | 0.107633E+09 | 0.00 | 0.57 | 27-MAR-15:53 | 0.00 | 01-MAR-00:05 | 13771.07 | 27-MAR-15:53 | 10136.94 | 27-MAR-15:57 | 4394.52 | 27-MAR-13:00 | 3587.65 | 27-MAR-15:53 | 0.00 | 01-MAR-00:05 |
April | 0.493983E+10 | 0.133141E+10 | 213.91 | 0.402951E+10 | 0.910322E+09 | 0.00 | 0.87 | 07-APR-13:00 | 0.00 | 01-APR-00:10 | 22124.58 | 08-APR-12:00 | 20265.55 | 07-APR-12:50 | 4957.19 | 09-APR-11:10 | 5641.18 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.139810E+11 | 0.376710E+10 | 544.92 | 0.108479E+11 | 0.313313E+10 | 0.00 | 0.92 | 29-MAY-12:00 | 0.00 | 01-MAY-00:10 | 24851.77 | 31-MAY-13:10 | 21058.90 | 30-MAY-13:00 | 7711.94 | 31-MAY-18:10 | 6321.66 | 29-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 0.416748E+11 | 0.104981E+11 | 719.67 | 0.256462E+11 | 0.160286E+11 | 0.00 | 1.00 | 15-JUN-10:50 | 0.00 | 02-JUN-06:10 | 36304.30 | 19-JUN-12:10 | 27284.96 | 19-JUN-12:00 | 15109.23 | 22-JUN-01:00 | 10560.33 | 19-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 0.656948E+11 | 0.158933E+11 | 744.00 | 0.366362E+11 | 0.290586E+11 | 0.00 | 1.00 | 06-JUL-09:40 | 0.39 | 02-JUL-03:00 | 41736.90 | 08-JUL-12:00 | 24962.71 | 07-JUL-12:00 | 19674.60 | 20-JUL-21:10 | 10867.73 | 08-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 0.601687E+11 | 0.149219E+11 | 744.00 | 0.377530E+11 | 0.224157E+11 | 0.00 | 1.00 | 01-AUG-09:51 | 0.15 | 08-AUG-05:10 | 42367.87 | 16-AUG-12:30 | 26359.84 | 18-AUG-13:00 | 21189.60 | 16-AUG-22:00 | 10990.67 | 16-AUG-12:30 | 0.00 | 01-AUG-00:10 |
September | 0.335396E+11 | 0.849726E+10 | 679.03 | 0.225003E+11 | 0.110393E+11 | 0.00 | 1.00 | 01-SEP-12:10 | 0.00 | 11-SEP-05:10 | 35539.17 | 07-SEP-14:10 | 24491.81 | 01-SEP-14:10 | 14660.90 | 07-SEP-14:10 | 8825.93 | 14-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 0.162983E+11 | 0.420124E+10 | 473.10 | 0.111487E+11 | 0.514960E+10 | 0.00 | 0.99 | 04-OCT-12:20 | 0.00 | 01-OCT-00:10 | 27343.73 | 25-OCT-10:25 | 20863.64 | 04-OCT-13:00 | 8944.16 | 24-OCT-15:10 | 6465.29 | 04-OCT-12:50 | 0.00 | 01-OCT-00:10 |
November | 0.103724E+10 | 0.286926E+09 | 78.61 | 0.921370E+09 | 0.115867E+09 | 0.00 | 0.64 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 | 14935.22 | 04-NOV-12:30 | 12799.65 | 04-NOV-12:30 | 3102.85 | 10-NOV-10:00 | 3765.03 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 0.103482E+09 | 29103968.45 | 8.25 | 0.103473E+09 | 9095.59 | 0.00 | 0.33 | 17-DEC-13:00 | 0.00 | 01-DEC-00:05 | 6966.62 | 17-DEC-13:00 | 6966.62 | 17-DEC-13:00 | 9.33 | 17-DEC-10:20 | 1905.87 | 17-DEC-13:00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.238409E+12 | 0.596955E+11 | 4274.04 | 0.150451E+12 | 0.879588E+11 | 0.00 | ||||||||||||||
Minimum of Months | 3738675.27 | 1101888.84 | 1.58 | 3735474.14 | 976.69 | 0.00 | 0.07 | 0.00 | 1459.91 | 1459.91 | 1.63 | 427.56 | 0.00 | |||||||
Maximum of Months | 0.656948E+11 | 0.158933E+11 | 744.00 | 0.377530E+11 | 0.290586E+11 | 0.00 | 1.00 | 0.39 | 42367.87 | 27284.96 | 21189.60 | 10990.67 | 0.00 |
Report: DXReportMonthly
For: PSZ_KITCHEN COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.350004E+11 | 0.882263E+10 | 671.14 | 0.281086E+11 | 0.689179E+10 | 0.00 | 1.00 | 24-JAN-11:40 | 0.00 | 01-JAN-00:05 | 32545.65 | 24-JAN-11:40 | 23530.49 | 17-JAN-11:50 | 10318.15 | 24-JAN-11:40 | 7315.15 | 24-JAN-11:40 | 0.00 | 01-JAN-00:05 |
February | 0.293628E+11 | 0.744752E+10 | 596.11 | 0.243381E+11 | 0.502471E+10 | 0.00 | 0.96 | 19-FEB-11:40 | 0.00 | 03-FEB-00:30 | 29970.41 | 19-FEB-11:40 | 23863.63 | 20-FEB-11:45 | 8107.22 | 28-FEB-18:30 | 6841.76 | 19-FEB-11:40 | 0.00 | 01-FEB-00:05 |
March | 0.455795E+11 | 0.111841E+11 | 732.58 | 0.367571E+11 | 0.882245E+10 | 0.00 | 1.00 | 01-MAR-11:40 | 0.00 | 14-MAR-01:40 | 41497.04 | 27-MAR-17:15 | 29178.13 | 27-MAR-16:20 | 12457.95 | 27-MAR-17:10 | 9526.73 | 27-MAR-17:15 | 0.00 | 01-MAR-00:05 |
April | 0.561394E+11 | 0.134355E+11 | 720.00 | 0.444843E+11 | 0.116552E+11 | 0.00 | 1.00 | 04-APR-10:35 | 0.09 | 03-APR-03:00 | 45889.46 | 09-APR-10:35 | 34533.32 | 08-APR-10:40 | 14053.52 | 09-APR-10:35 | 11053.10 | 08-APR-10:40 | 0.00 | 01-APR-00:10 |
May | 0.718031E+11 | 0.169135E+11 | 744.00 | 0.553234E+11 | 0.164796E+11 | 0.00 | 1.00 | 01-MAY-10:35 | 0.22 | 01-MAY-03:00 | 50933.45 | 31-MAY-10:40 | 37628.66 | 30-MAY-10:50 | 17676.23 | 31-MAY-16:40 | 12616.84 | 31-MAY-10:40 | 0.00 | 01-MAY-00:10 |
June | 0.886707E+11 | 0.211953E+11 | 720.00 | 0.625584E+11 | 0.261122E+11 | 0.00 | 1.00 | 01-JUN-06:23 | 0.37 | 03-JUN-03:00 | 58100.81 | 19-JUN-17:20 | 41201.55 | 19-JUN-10:50 | 22007.24 | 24-JUN-17:13 | 17113.95 | 19-JUN-10:40 | 0.00 | 01-JUN-00:10 |
July | 0.105395E+12 | 0.258774E+11 | 744.00 | 0.702324E+11 | 0.351623E+11 | 0.00 | 1.00 | 01-JUL-05:53 | 0.57 | 11-JUL-03:00 | 61020.61 | 09-JUL-10:40 | 39651.41 | 07-JUL-10:50 | 23532.91 | 20-JUL-17:15 | 16247.91 | 08-JUL-10:40 | 0.00 | 01-JUL-00:10 |
August | 0.994896E+11 | 0.246368E+11 | 744.00 | 0.701071E+11 | 0.293825E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.46 | 20-AUG-03:00 | 61180.06 | 04-AUG-10:40 | 38770.32 | 18-AUG-10:50 | 23847.28 | 04-AUG-17:20 | 16238.19 | 04-AUG-10:40 | 0.00 | 01-AUG-00:10 |
September | 0.807728E+11 | 0.191189E+11 | 720.00 | 0.591820E+11 | 0.215907E+11 | 0.00 | 1.00 | 01-SEP-05:20 | 0.33 | 29-SEP-03:00 | 54184.30 | 14-SEP-10:40 | 37277.08 | 06-SEP-10:50 | 20135.96 | 13-SEP-17:15 | 13292.74 | 14-SEP-10:40 | 0.00 | 01-SEP-00:10 |
October | 0.672678E+11 | 0.158772E+11 | 744.00 | 0.510878E+11 | 0.161799E+11 | 0.00 | 1.00 | 01-OCT-17:15 | 0.08 | 29-OCT-03:00 | 49467.49 | 25-OCT-10:40 | 33874.36 | 25-OCT-10:40 | 16977.62 | 04-OCT-17:20 | 12001.50 | 25-OCT-10:40 | 0.00 | 01-OCT-00:10 |
November | 0.467072E+11 | 0.113888E+11 | 705.08 | 0.372412E+11 | 0.946599E+10 | 0.00 | 1.00 | 02-NOV-10:35 | 0.00 | 22-NOV-02:70 | 38409.03 | 04-NOV-10:40 | 29212.57 | 04-NOV-10:50 | 12116.91 | 10-NOV-11:40 | 8800.43 | 04-NOV-10:40 | 0.00 | 01-NOV-00:10 |
December | 0.382218E+11 | 0.961137E+10 | 730.83 | 0.314292E+11 | 0.679265E+10 | 0.00 | 0.97 | 17-DEC-11:35 | 0.00 | 07-DEC-02:20 | 30702.84 | 25-DEC-11:40 | 25487.91 | 17-DEC-11:50 | 9136.81 | 25-DEC-11:40 | 6993.77 | 25-DEC-11:40 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 0.764410E+12 | 0.185509E+12 | 8571.75 | 0.570850E+12 | 0.193560E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.293628E+11 | 0.744752E+10 | 596.11 | 0.243381E+11 | 0.502471E+10 | 0.00 | 0.96 | 0.00 | 29970.41 | 23530.49 | 8107.22 | 6841.76 | 0.00 | |||||||
Maximum of Months | 0.105395E+12 | 0.258774E+11 | 744.00 | 0.702324E+11 | 0.351623E+11 | 0.00 | 1.00 | 0.57 | 61180.06 | 41201.55 | 23847.28 | 17113.95 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 678.19 | 445.04 | 233.15 | 592.43 | 880.23 | 0.00 | 0.00 | 0.00 |
February | 897.52 | 596.52 | 301.00 | 801.28 | 874.87 | 0.00 | 0.00 | 0.00 |
March | 795.20 | 437.75 | 357.45 | 761.77 | 634.48 | 0.00 | 0.00 | 0.00 |
April | 632.96 | 256.08 | 376.88 | 639.85 | 456.09 | 0.00 | 0.00 | 0.00 |
May | 543.64 | 111.30 | 432.33 | 592.06 | 268.73 | 0.00 | 0.00 | 0.00 |
June | 513.33 | 79.09 | 434.23 | 665.56 | 137.52 | 0.00 | 0.00 | 0.00 |
July | 534.12 | 90.15 | 443.97 | 789.55 | 64.44 | 0.00 | 0.00 | 0.00 |
August | 715.40 | 263.90 | 451.50 | 1059.01 | 97.15 | 0.00 | 0.00 | 0.00 |
September | 754.94 | 379.05 | 375.90 | 975.86 | 206.17 | 0.00 | 0.00 | 0.00 |
October | 1066.86 | 669.01 | 397.85 | 1257.92 | 397.42 | 0.00 | 0.00 | 0.00 |
November | 738.73 | 443.14 | 295.59 | 714.56 | 612.91 | 0.00 | 0.00 | 0.00 |
December | 732.71 | 520.41 | 212.30 | 677.57 | 791.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 716.11 | 356.41 | 359.70 | 794.38 | 449.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.33 | 79.09 | 212.30 | 592.06 | 64.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1066.86 | 669.01 | 451.50 | 1257.92 | 880.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1909.75 | 1253.20 | 656.54 | 1668.32 | 2509.81 | 0.00 | 0.00 | 0.00 |
February | 2527.36 | 1679.75 | 847.60 | 2259.22 | 2482.31 | 0.00 | 0.00 | 0.00 |
March | 2239.24 | 1232.67 | 1006.56 | 2136.90 | 1820.31 | 0.00 | 0.00 | 0.00 |
April | 1782.37 | 721.11 | 1061.27 | 1761.46 | 1364.42 | 0.00 | 0.00 | 0.00 |
May | 1530.84 | 313.42 | 1217.42 | 1584.90 | 880.23 | 0.00 | 0.00 | 0.00 |
June | 1445.49 | 222.72 | 1222.77 | 1817.97 | 441.25 | 0.00 | 0.00 | 0.00 |
July | 1504.04 | 253.85 | 1250.19 | 2186.81 | 208.44 | 0.00 | 0.00 | 0.00 |
August | 2014.52 | 743.14 | 1271.38 | 2945.79 | 305.45 | 0.00 | 0.00 | 0.00 |
September | 2125.86 | 1067.37 | 1058.50 | 2692.93 | 667.35 | 0.00 | 0.00 | 0.00 |
October | 3004.20 | 1883.89 | 1120.31 | 3497.68 | 1211.08 | 0.00 | 0.00 | 0.00 |
November | 2080.21 | 1247.86 | 832.35 | 1990.27 | 1797.37 | 0.00 | 0.00 | 0.00 |
December | 2063.27 | 1465.44 | 597.83 | 1907.91 | 2255.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2016.51 | 1003.61 | 1012.90 | 2205.25 | 1321.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1445.49 | 222.72 | 597.83 | 1584.90 | 208.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3004.20 | 1883.89 | 1271.38 | 3497.68 | 2509.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2480.87 | 1627.98 | 852.89 | 2189.01 | 3507.90 | 0.00 | 0.00 | 0.00 |
February | 3283.18 | 2182.09 | 1101.09 | 2972.39 | 3463.91 | 0.00 | 0.00 | 0.00 |
March | 2908.90 | 1601.31 | 1307.58 | 2832.48 | 2586.92 | 0.00 | 0.00 | 0.00 |
April | 2315.40 | 936.76 | 1378.65 | 2369.20 | 1912.53 | 0.00 | 0.00 | 0.00 |
May | 1988.65 | 407.15 | 1581.50 | 2180.20 | 1157.29 | 0.00 | 0.00 | 0.00 |
June | 1877.78 | 289.33 | 1588.45 | 2487.44 | 571.98 | 0.00 | 0.00 | 0.00 |
July | 1953.84 | 329.77 | 1624.07 | 2966.25 | 262.51 | 0.00 | 0.00 | 0.00 |
August | 2616.97 | 965.38 | 1651.60 | 3967.46 | 388.89 | 0.00 | 0.00 | 0.00 |
September | 2761.62 | 1386.57 | 1375.05 | 3625.25 | 861.18 | 0.00 | 0.00 | 0.00 |
October | 3902.63 | 2447.28 | 1455.35 | 4667.59 | 1630.67 | 0.00 | 0.00 | 0.00 |
November | 2702.32 | 1621.04 | 1081.27 | 2624.85 | 2533.24 | 0.00 | 0.00 | 0.00 |
December | 2680.31 | 1903.69 | 776.61 | 2500.16 | 3194.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2619.56 | 1303.75 | 1315.81 | 2950.21 | 1829.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1877.78 | 289.33 | 776.61 | 2180.20 | 262.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3902.63 | 2447.28 | 1651.60 | 4667.59 | 3507.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 154.02 | 101.07 | 52.95 | 132.67 | 210.58 | 0.00 | 0.00 | 0.00 |
February | 203.83 | 135.47 | 68.36 | 179.31 | 210.36 | 0.00 | 0.00 | 0.00 |
March | 180.59 | 99.41 | 81.18 | 169.11 | 154.43 | 0.00 | 0.00 | 0.00 |
April | 143.75 | 58.16 | 85.59 | 142.03 | 108.94 | 0.00 | 0.00 | 0.00 |
May | 123.46 | 25.28 | 98.18 | 133.47 | 59.36 | 0.00 | 0.00 | 0.00 |
June | 116.58 | 17.96 | 98.61 | 157.49 | 22.66 | 0.00 | 0.00 | 0.00 |
July | 121.30 | 20.47 | 100.83 | 192.86 | 5.67 | 0.00 | 0.00 | 0.00 |
August | 162.47 | 59.93 | 102.53 | 253.70 | 12.85 | 0.00 | 0.00 | 0.00 |
September | 171.45 | 86.08 | 85.37 | 226.72 | 37.88 | 0.00 | 0.00 | 0.00 |
October | 242.28 | 151.93 | 90.35 | 286.68 | 85.96 | 0.00 | 0.00 | 0.00 |
November | 167.77 | 100.64 | 67.13 | 160.47 | 146.25 | 0.00 | 0.00 | 0.00 |
December | 166.40 | 118.19 | 48.21 | 152.26 | 189.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.63 | 80.94 | 81.69 | 182.37 | 103.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.58 | 17.96 | 48.21 | 132.67 | 5.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.28 | 151.93 | 102.53 | 286.68 | 210.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.47 | 46.99 | 67.48 | 51.76 | 435.52 | 0.00 | 0.00 | 0.00 |
February | 168.15 | 73.80 | 94.35 | 86.54 | 444.61 | 0.00 | 0.00 | 0.00 |
March | 249.77 | 115.75 | 134.02 | 183.63 | 291.32 | 0.00 | 0.00 | 0.00 |
April | 271.27 | 115.93 | 155.34 | 245.02 | 199.04 | 0.00 | 0.00 | 0.00 |
May | 316.90 | 120.47 | 196.43 | 347.24 | 105.94 | 0.00 | 0.00 | 0.00 |
June | 346.24 | 139.73 | 206.50 | 455.36 | 41.06 | 0.00 | 0.00 | 0.00 |
July | 323.93 | 121.73 | 202.20 | 480.02 | 10.55 | 0.00 | 0.00 | 0.00 |
August | 358.40 | 165.71 | 192.69 | 524.36 | 23.87 | 0.00 | 0.00 | 0.00 |
September | 254.99 | 111.32 | 143.67 | 315.76 | 70.96 | 0.00 | 0.00 | 0.00 |
October | 253.01 | 123.25 | 129.76 | 258.53 | 167.08 | 0.00 | 0.00 | 0.00 |
November | 119.15 | 34.81 | 84.34 | 57.93 | 300.62 | 0.00 | 0.00 | 0.00 |
December | 105.24 | 45.43 | 59.81 | 46.97 | 397.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.63 | 101.48 | 139.16 | 255.65 | 206.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.24 | 34.81 | 59.81 | 46.97 | 10.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.40 | 165.71 | 206.50 | 524.36 | 444.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.63 | 0.00 | 29.63 | 0.08 | 243.22 | 0.00 | 0.00 | 0.00 |
February | 40.55 | 0.00 | 40.55 | 0.73 | 252.71 | 0.00 | 0.00 | 0.00 |
March | 56.24 | 0.00 | 56.24 | 9.01 | 167.90 | 0.00 | 0.00 | 0.00 |
April | 67.69 | 0.28 | 67.41 | 29.67 | 111.76 | 0.00 | 0.00 | 0.00 |
May | 90.02 | 3.29 | 86.73 | 70.40 | 59.12 | 0.00 | 0.00 | 0.00 |
June | 94.97 | 5.05 | 89.92 | 110.76 | 28.08 | 0.00 | 0.00 | 0.00 |
July | 92.18 | 3.60 | 88.58 | 140.18 | 8.13 | 0.00 | 0.00 | 0.00 |
August | 81.52 | 1.08 | 80.44 | 123.56 | 15.21 | 0.00 | 0.00 | 0.00 |
September | 61.38 | 0.04 | 61.35 | 61.81 | 46.55 | 0.00 | 0.00 | 0.00 |
October | 53.08 | 0.00 | 53.08 | 30.06 | 97.54 | 0.00 | 0.00 | 0.00 |
November | 37.23 | 0.00 | 37.23 | 4.98 | 165.31 | 0.00 | 0.00 | 0.00 |
December | 25.85 | 0.00 | 25.85 | 0.12 | 221.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.98 | 1.12 | 59.86 | 48.80 | 117.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.85 | 0.00 | 25.85 | 0.08 | 8.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.97 | 5.05 | 89.92 | 140.18 | 252.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.47 | 46.99 | 67.48 | 55.98 | 429.15 | 0.00 | 0.00 | 0.00 |
February | 168.15 | 73.80 | 94.35 | 92.96 | 435.89 | 0.00 | 0.00 | 0.00 |
March | 249.77 | 115.75 | 134.02 | 189.60 | 287.78 | 0.00 | 0.00 | 0.00 |
April | 271.27 | 115.93 | 155.34 | 245.97 | 200.47 | 0.00 | 0.00 | 0.00 |
May | 316.90 | 120.47 | 196.43 | 339.20 | 113.55 | 0.00 | 0.00 | 0.00 |
June | 346.24 | 139.73 | 206.50 | 440.21 | 53.83 | 0.00 | 0.00 | 0.00 |
July | 323.93 | 121.73 | 202.20 | 474.33 | 15.37 | 0.00 | 0.00 | 0.00 |
August | 358.40 | 165.71 | 192.69 | 522.79 | 29.09 | 0.00 | 0.00 | 0.00 |
September | 254.99 | 111.32 | 143.67 | 311.00 | 84.03 | 0.00 | 0.00 | 0.00 |
October | 253.01 | 123.25 | 129.76 | 260.93 | 174.11 | 0.00 | 0.00 | 0.00 |
November | 119.15 | 34.81 | 84.34 | 62.85 | 294.57 | 0.00 | 0.00 | 0.00 |
December | 105.24 | 45.43 | 59.81 | 51.78 | 389.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.63 | 101.48 | 139.16 | 255.17 | 207.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.24 | 34.81 | 59.81 | 51.78 | 15.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.40 | 165.71 | 206.50 | 522.79 | 435.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 123.19 | 80.84 | 42.35 | 99.25 | 193.50 | 0.00 | 0.00 | 0.00 |
February | 163.03 | 108.35 | 54.68 | 130.00 | 208.12 | 0.00 | 0.00 | 0.00 |
March | 144.44 | 79.51 | 64.93 | 123.04 | 165.92 | 0.00 | 0.00 | 0.00 |
April | 114.97 | 46.52 | 68.46 | 100.22 | 127.11 | 0.00 | 0.00 | 0.00 |
May | 98.75 | 20.22 | 78.53 | 89.86 | 80.29 | 0.00 | 0.00 | 0.00 |
June | 93.24 | 14.37 | 78.88 | 105.12 | 43.22 | 0.00 | 0.00 | 0.00 |
July | 97.02 | 16.37 | 80.64 | 129.69 | 24.61 | 0.00 | 0.00 | 0.00 |
August | 129.95 | 47.94 | 82.01 | 179.38 | 31.69 | 0.00 | 0.00 | 0.00 |
September | 137.13 | 68.85 | 68.28 | 163.21 | 61.40 | 0.00 | 0.00 | 0.00 |
October | 193.79 | 121.52 | 72.27 | 211.94 | 105.30 | 0.00 | 0.00 | 0.00 |
November | 134.19 | 80.49 | 53.69 | 114.10 | 161.70 | 0.00 | 0.00 | 0.00 |
December | 133.09 | 94.53 | 38.56 | 109.98 | 193.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 130.08 | 64.74 | 65.34 | 129.74 | 115.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.24 | 14.37 | 38.56 | 89.86 | 24.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 193.79 | 121.52 | 82.01 | 211.94 | 208.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.71 | 0.00 | 23.71 | 0.02 | 204.61 | 0.00 | 0.00 | 0.00 |
February | 32.44 | 0.00 | 32.44 | 0.50 | 209.16 | 0.00 | 0.00 | 0.00 |
March | 45.00 | 0.00 | 45.00 | 7.86 | 135.74 | 0.00 | 0.00 | 0.00 |
April | 54.16 | 0.22 | 53.93 | 26.32 | 88.89 | 0.00 | 0.00 | 0.00 |
May | 72.03 | 2.64 | 69.39 | 62.15 | 45.54 | 0.00 | 0.00 | 0.00 |
June | 75.99 | 4.04 | 71.95 | 96.18 | 20.03 | 0.00 | 0.00 | 0.00 |
July | 73.76 | 2.88 | 70.88 | 119.06 | 5.54 | 0.00 | 0.00 | 0.00 |
August | 65.22 | 0.87 | 64.36 | 106.34 | 10.64 | 0.00 | 0.00 | 0.00 |
September | 49.11 | 0.03 | 49.08 | 53.55 | 34.44 | 0.00 | 0.00 | 0.00 |
October | 42.47 | 0.00 | 42.47 | 26.53 | 74.84 | 0.00 | 0.00 | 0.00 |
November | 29.79 | 0.00 | 29.79 | 4.25 | 136.96 | 0.00 | 0.00 | 0.00 |
December | 20.68 | 0.00 | 20.68 | 0.07 | 185.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.79 | 0.89 | 47.90 | 42.21 | 95.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.68 | 0.00 | 20.68 | 0.02 | 5.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.99 | 4.04 | 71.95 | 119.06 | 209.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.27 | 46.05 | 69.22 | 49.90 | 428.31 | 0.00 | 0.00 | 0.00 |
February | 178.97 | 83.34 | 95.63 | 92.44 | 429.34 | 0.00 | 0.00 | 0.00 |
March | 229.82 | 97.67 | 132.15 | 163.68 | 295.04 | 0.00 | 0.00 | 0.00 |
April | 275.12 | 120.75 | 154.36 | 246.54 | 193.01 | 0.00 | 0.00 | 0.00 |
May | 332.15 | 132.37 | 199.78 | 365.90 | 102.80 | 0.00 | 0.00 | 0.00 |
June | 308.42 | 111.72 | 196.71 | 406.08 | 39.13 | 0.00 | 0.00 | 0.00 |
July | 309.36 | 111.38 | 197.99 | 462.81 | 9.92 | 0.00 | 0.00 | 0.00 |
August | 349.00 | 157.45 | 191.54 | 510.95 | 22.24 | 0.00 | 0.00 | 0.00 |
September | 261.06 | 117.61 | 143.46 | 321.59 | 67.63 | 0.00 | 0.00 | 0.00 |
October | 235.85 | 106.76 | 129.09 | 235.27 | 161.69 | 0.00 | 0.00 | 0.00 |
November | 146.08 | 56.13 | 89.94 | 89.40 | 290.53 | 0.00 | 0.00 | 0.00 |
December | 114.20 | 53.89 | 60.32 | 57.09 | 389.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.32 | 99.71 | 138.61 | 251.26 | 201.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.20 | 46.05 | 60.32 | 49.90 | 9.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 349.00 | 157.45 | 199.78 | 510.95 | 429.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 154.02 | 101.07 | 52.95 | 131.90 | 210.13 | 0.00 | 0.00 | 0.00 |
February | 203.83 | 135.47 | 68.36 | 177.54 | 209.75 | 0.00 | 0.00 | 0.00 |
March | 180.59 | 99.41 | 81.18 | 167.61 | 153.03 | 0.00 | 0.00 | 0.00 |
April | 143.75 | 58.16 | 85.59 | 140.62 | 108.18 | 0.00 | 0.00 | 0.00 |
May | 123.46 | 25.28 | 98.18 | 132.01 | 58.54 | 0.00 | 0.00 | 0.00 |
June | 116.58 | 17.96 | 98.61 | 157.51 | 21.85 | 0.00 | 0.00 | 0.00 |
July | 121.30 | 20.47 | 100.83 | 192.81 | 5.34 | 0.00 | 0.00 | 0.00 |
August | 162.47 | 59.93 | 102.53 | 253.28 | 12.38 | 0.00 | 0.00 | 0.00 |
September | 171.45 | 86.08 | 85.37 | 225.86 | 37.29 | 0.00 | 0.00 | 0.00 |
October | 242.28 | 151.93 | 90.35 | 285.86 | 84.96 | 0.00 | 0.00 | 0.00 |
November | 167.77 | 100.64 | 67.13 | 159.05 | 146.23 | 0.00 | 0.00 | 0.00 |
December | 166.40 | 118.19 | 48.21 | 151.19 | 189.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.63 | 80.94 | 81.69 | 181.42 | 102.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.58 | 17.96 | 48.21 | 131.90 | 5.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.28 | 151.93 | 102.53 | 285.86 | 210.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.63 | 0.00 | 29.63 | 0.06 | 243.34 | 0.00 | 0.00 | 0.00 |
February | 40.55 | 0.00 | 40.55 | 0.51 | 253.03 | 0.00 | 0.00 | 0.00 |
March | 56.24 | 0.00 | 56.24 | 7.92 | 167.02 | 0.00 | 0.00 | 0.00 |
April | 67.69 | 0.28 | 67.41 | 28.38 | 110.33 | 0.00 | 0.00 | 0.00 |
May | 90.02 | 3.29 | 86.73 | 69.56 | 57.29 | 0.00 | 0.00 | 0.00 |
June | 94.97 | 5.05 | 89.92 | 111.14 | 26.06 | 0.00 | 0.00 | 0.00 |
July | 92.18 | 3.60 | 88.58 | 139.33 | 7.64 | 0.00 | 0.00 | 0.00 |
August | 81.52 | 1.08 | 80.44 | 121.89 | 14.46 | 0.00 | 0.00 | 0.00 |
September | 61.38 | 0.04 | 61.35 | 60.41 | 44.26 | 0.00 | 0.00 | 0.00 |
October | 53.08 | 0.00 | 53.08 | 28.67 | 93.91 | 0.00 | 0.00 | 0.00 |
November | 37.23 | 0.00 | 37.23 | 4.35 | 166.19 | 0.00 | 0.00 | 0.00 |
December | 25.85 | 0.00 | 25.85 | 0.07 | 222.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.98 | 1.12 | 59.86 | 48.04 | 116.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.85 | 0.00 | 25.85 | 0.06 | 7.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.97 | 5.05 | 89.92 | 139.33 | 253.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.27 | 46.05 | 69.22 | 51.67 | 419.17 | 0.00 | 0.00 | 0.00 |
February | 178.97 | 83.34 | 95.63 | 95.53 | 416.35 | 0.00 | 0.00 | 0.00 |
March | 229.82 | 97.67 | 132.15 | 167.38 | 289.33 | 0.00 | 0.00 | 0.00 |
April | 275.12 | 120.75 | 154.36 | 248.34 | 193.42 | 0.00 | 0.00 | 0.00 |
May | 332.15 | 132.37 | 199.78 | 360.76 | 109.90 | 0.00 | 0.00 | 0.00 |
June | 308.42 | 111.72 | 196.71 | 393.20 | 50.90 | 0.00 | 0.00 | 0.00 |
July | 309.36 | 111.38 | 197.99 | 455.53 | 14.69 | 0.00 | 0.00 | 0.00 |
August | 349.00 | 157.45 | 191.54 | 506.45 | 26.82 | 0.00 | 0.00 | 0.00 |
September | 261.06 | 117.61 | 143.46 | 316.97 | 78.58 | 0.00 | 0.00 | 0.00 |
October | 235.85 | 106.76 | 129.09 | 238.73 | 165.47 | 0.00 | 0.00 | 0.00 |
November | 146.08 | 56.13 | 89.94 | 92.75 | 283.41 | 0.00 | 0.00 | 0.00 |
December | 114.20 | 53.89 | 60.32 | 59.30 | 378.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.32 | 99.71 | 138.61 | 249.99 | 200.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.20 | 46.05 | 60.32 | 51.67 | 14.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 349.00 | 157.45 | 199.78 | 506.45 | 419.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.53 | 0.00 | 37.53 | 0.01 | 346.54 | 680.00 | 0.00 | 0.00 |
February | 51.35 | 0.00 | 51.35 | 0.17 | 367.12 | 672.00 | 0.00 | 0.00 |
March | 71.23 | 0.00 | 71.23 | 7.70 | 255.60 | 608.83 | 0.00 | 0.00 |
April | 85.72 | 0.35 | 85.37 | 33.36 | 171.90 | 276.67 | 0.00 | 0.00 |
May | 114.01 | 4.17 | 109.84 | 88.35 | 89.25 | 9.67 | 0.00 | 0.00 |
June | 120.28 | 6.40 | 113.88 | 144.40 | 40.05 | 0.00 | 0.00 | 0.00 |
July | 116.74 | 4.56 | 112.19 | 173.67 | 16.15 | 0.00 | 0.00 | 0.00 |
August | 103.24 | 1.37 | 101.87 | 151.94 | 25.82 | 0.00 | 0.00 | 0.00 |
September | 77.74 | 0.05 | 77.69 | 77.01 | 67.94 | 0.00 | 0.00 | 0.00 |
October | 67.22 | 0.00 | 67.22 | 34.07 | 144.91 | 36.67 | 0.00 | 0.00 |
November | 47.15 | 0.00 | 47.15 | 3.69 | 258.06 | 495.83 | 0.00 | 0.00 |
December | 32.73 | 0.00 | 32.73 | 0.01 | 334.72 | 744.00 | 0.00 | 0.00 |
Annual Sum or Average | 77.23 | 1.42 | 75.81 | 59.96 | 175.40 | 3523.67 | 0.00 | 0.00 |
Minimum of Months | 32.73 | 0.00 | 32.73 | 0.01 | 16.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.28 | 6.40 | 113.88 | 173.67 | 367.12 | 744.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.83 | 0.00 | 13.83 | 0.00 | 127.75 | 680.00 | 0.00 | 0.00 |
February | 18.93 | 0.00 | 18.93 | 0.06 | 135.34 | 672.00 | 0.00 | 0.00 |
March | 26.26 | 0.00 | 26.26 | 2.84 | 94.22 | 608.83 | 0.00 | 0.00 |
April | 31.60 | 0.13 | 31.47 | 12.30 | 63.37 | 276.67 | 0.00 | 0.00 |
May | 42.03 | 1.54 | 40.49 | 32.57 | 32.90 | 9.67 | 0.00 | 0.00 |
June | 44.34 | 2.36 | 41.98 | 53.23 | 14.77 | 0.00 | 0.00 | 0.00 |
July | 43.04 | 1.68 | 41.36 | 64.02 | 5.95 | 0.00 | 0.00 | 0.00 |
August | 38.06 | 0.51 | 37.55 | 56.01 | 9.52 | 0.00 | 0.00 | 0.00 |
September | 28.66 | 0.02 | 28.64 | 28.39 | 25.04 | 0.00 | 0.00 | 0.00 |
October | 24.78 | 0.00 | 24.78 | 12.56 | 53.42 | 36.67 | 0.00 | 0.00 |
November | 17.38 | 0.00 | 17.38 | 1.36 | 95.13 | 495.83 | 0.00 | 0.00 |
December | 12.07 | 0.00 | 12.07 | 0.00 | 123.39 | 744.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.47 | 0.52 | 27.95 | 22.10 | 64.66 | 3523.67 | 0.00 | 0.00 |
Minimum of Months | 12.07 | 0.00 | 12.07 | 0.00 | 5.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.34 | 2.36 | 41.98 | 64.02 | 135.34 | 744.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.86 | 47.16 | 24.71 | 61.00 | 108.27 | 610.83 | 0.00 | 0.00 |
February | 95.10 | 63.21 | 31.90 | 82.18 | 109.84 | 599.67 | 0.00 | 0.00 |
March | 84.26 | 46.39 | 37.88 | 77.31 | 85.02 | 526.67 | 0.00 | 0.00 |
April | 67.07 | 27.14 | 39.94 | 64.70 | 62.13 | 254.00 | 0.00 | 0.00 |
May | 57.61 | 11.79 | 45.81 | 60.53 | 35.53 | 9.50 | 0.00 | 0.00 |
June | 54.39 | 8.38 | 46.01 | 71.76 | 15.92 | 0.00 | 0.00 | 0.00 |
July | 56.60 | 9.55 | 47.04 | 87.21 | 6.18 | 0.00 | 0.00 | 0.00 |
August | 75.81 | 27.96 | 47.84 | 116.24 | 9.84 | 0.00 | 0.00 | 0.00 |
September | 80.00 | 40.17 | 39.83 | 104.29 | 24.56 | 0.00 | 0.00 | 0.00 |
October | 113.05 | 70.89 | 42.16 | 132.50 | 49.12 | 27.67 | 0.00 | 0.00 |
November | 78.28 | 46.96 | 31.32 | 72.40 | 81.39 | 445.83 | 0.00 | 0.00 |
December | 77.64 | 55.14 | 22.50 | 69.06 | 102.19 | 663.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.88 | 37.77 | 38.12 | 83.33 | 57.20 | 3137.17 | 0.00 | 0.00 |
Minimum of Months | 54.39 | 8.38 | 22.50 | 60.53 | 6.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 113.05 | 70.89 | 47.84 | 132.50 | 109.84 | 663.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.05 | 128.00 | 67.06 | 165.56 | 293.87 | 610.83 | 0.00 | 0.00 |
February | 258.13 | 171.56 | 86.57 | 223.06 | 298.13 | 599.67 | 0.00 | 0.00 |
March | 228.71 | 125.90 | 102.81 | 209.83 | 230.75 | 526.67 | 0.00 | 0.00 |
April | 182.04 | 73.65 | 108.39 | 175.60 | 168.64 | 254.00 | 0.00 | 0.00 |
May | 156.35 | 32.01 | 124.34 | 164.29 | 96.44 | 9.50 | 0.00 | 0.00 |
June | 147.64 | 22.75 | 124.89 | 194.78 | 43.21 | 0.00 | 0.00 | 0.00 |
July | 153.62 | 25.93 | 127.69 | 236.71 | 16.77 | 0.00 | 0.00 | 0.00 |
August | 205.75 | 75.90 | 129.85 | 315.50 | 26.72 | 0.00 | 0.00 | 0.00 |
September | 217.13 | 109.02 | 108.11 | 283.06 | 66.67 | 0.00 | 0.00 | 0.00 |
October | 306.84 | 192.41 | 114.42 | 359.64 | 133.32 | 27.67 | 0.00 | 0.00 |
November | 212.46 | 127.45 | 85.01 | 196.52 | 220.91 | 445.83 | 0.00 | 0.00 |
December | 210.73 | 149.67 | 61.06 | 187.45 | 277.36 | 663.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.96 | 102.51 | 103.45 | 226.17 | 155.24 | 3137.17 | 0.00 | 0.00 |
Minimum of Months | 147.64 | 22.75 | 61.06 | 164.29 | 16.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 306.84 | 192.41 | 129.85 | 359.64 | 298.13 | 663.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 154.02 | 101.07 | 52.95 | 132.65 | 207.00 | 0.33 | 0.00 | 0.00 |
February | 203.83 | 135.47 | 68.36 | 179.32 | 206.59 | 0.00 | 0.00 | 0.00 |
March | 180.59 | 99.41 | 81.18 | 168.55 | 150.26 | 0.00 | 0.00 | 0.00 |
April | 143.75 | 58.16 | 85.59 | 140.95 | 105.53 | 0.00 | 0.00 | 0.00 |
May | 123.46 | 25.28 | 98.18 | 131.52 | 57.81 | 0.00 | 0.00 | 0.00 |
June | 116.58 | 17.96 | 98.61 | 154.86 | 21.91 | 0.00 | 0.00 | 0.00 |
July | 121.30 | 20.47 | 100.83 | 190.25 | 5.18 | 0.00 | 0.00 | 0.00 |
August | 162.47 | 59.93 | 102.53 | 250.80 | 12.11 | 0.00 | 0.00 | 0.00 |
September | 171.45 | 86.08 | 85.37 | 224.43 | 36.41 | 0.00 | 0.00 | 0.00 |
October | 242.28 | 151.93 | 90.35 | 284.58 | 83.41 | 0.00 | 0.00 | 0.00 |
November | 167.77 | 100.64 | 67.13 | 161.24 | 140.73 | 0.00 | 0.00 | 0.00 |
December | 166.40 | 118.19 | 48.21 | 153.16 | 184.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.63 | 80.94 | 81.69 | 181.16 | 100.34 | 0.33 | 0.00 | 0.00 |
Minimum of Months | 116.58 | 17.96 | 48.21 | 131.52 | 5.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.28 | 151.93 | 102.53 | 284.58 | 207.00 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.47 | 46.99 | 67.48 | 51.98 | 428.29 | 0.33 | 0.00 | 0.00 |
February | 168.15 | 73.80 | 94.35 | 86.28 | 437.20 | 0.00 | 0.00 | 0.00 |
March | 249.77 | 115.75 | 134.02 | 182.65 | 282.27 | 0.00 | 0.00 | 0.00 |
April | 271.27 | 115.93 | 155.34 | 243.10 | 191.98 | 0.00 | 0.00 | 0.00 |
May | 316.90 | 120.47 | 196.43 | 343.30 | 102.70 | 0.00 | 0.00 | 0.00 |
June | 346.24 | 139.73 | 206.50 | 449.16 | 39.49 | 0.00 | 0.00 | 0.00 |
July | 323.93 | 121.73 | 202.20 | 474.35 | 9.62 | 0.00 | 0.00 | 0.00 |
August | 358.40 | 165.71 | 192.69 | 519.06 | 22.42 | 0.00 | 0.00 | 0.00 |
September | 254.99 | 111.32 | 143.67 | 312.38 | 67.95 | 0.00 | 0.00 | 0.00 |
October | 253.01 | 123.25 | 129.76 | 255.85 | 161.51 | 0.00 | 0.00 | 0.00 |
November | 119.15 | 34.81 | 84.34 | 58.91 | 288.90 | 0.00 | 0.00 | 0.00 |
December | 105.24 | 45.43 | 59.81 | 47.89 | 386.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.63 | 101.48 | 139.16 | 253.29 | 200.24 | 0.33 | 0.00 | 0.00 |
Minimum of Months | 105.24 | 34.81 | 59.81 | 47.89 | 9.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.40 | 165.71 | 206.50 | 519.06 | 437.20 | 0.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.63 | 0.00 | 29.63 | 0.15 | 239.06 | 0.50 | 0.00 | 0.00 |
February | 40.55 | 0.00 | 40.55 | 0.93 | 248.64 | 0.00 | 0.00 | 0.00 |
March | 56.24 | 0.00 | 56.24 | 9.72 | 162.67 | 0.00 | 0.00 | 0.00 |
April | 67.69 | 0.28 | 67.41 | 30.08 | 108.25 | 0.00 | 0.00 | 0.00 |
May | 90.02 | 3.29 | 86.73 | 68.95 | 58.46 | 0.00 | 0.00 | 0.00 |
June | 94.97 | 5.05 | 89.92 | 108.32 | 28.61 | 0.00 | 0.00 | 0.00 |
July | 92.18 | 3.60 | 88.58 | 138.14 | 8.02 | 0.00 | 0.00 | 0.00 |
August | 81.52 | 1.08 | 80.44 | 122.10 | 14.83 | 0.00 | 0.00 | 0.00 |
September | 61.38 | 0.04 | 61.35 | 60.93 | 46.13 | 0.33 | 0.00 | 0.00 |
October | 53.08 | 0.00 | 53.08 | 30.43 | 94.98 | 0.00 | 0.00 | 0.00 |
November | 37.23 | 0.00 | 37.23 | 5.72 | 158.08 | 0.00 | 0.00 | 0.00 |
December | 25.85 | 0.00 | 25.85 | 0.20 | 214.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.98 | 1.12 | 59.86 | 48.32 | 114.46 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 25.85 | 0.00 | 25.85 | 0.15 | 8.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.97 | 5.05 | 89.92 | 138.14 | 248.64 | 0.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.47 | 46.99 | 67.48 | 56.55 | 422.59 | 0.50 | 0.00 | 0.00 |
February | 168.15 | 73.80 | 94.35 | 93.35 | 429.42 | 0.00 | 0.00 | 0.00 |
March | 249.77 | 115.75 | 134.02 | 189.98 | 278.49 | 0.00 | 0.00 | 0.00 |
April | 271.27 | 115.93 | 155.34 | 244.38 | 193.71 | 0.00 | 0.00 | 0.00 |
May | 316.90 | 120.47 | 196.43 | 334.40 | 111.60 | 0.00 | 0.00 | 0.00 |
June | 346.24 | 139.73 | 206.50 | 432.69 | 54.58 | 0.00 | 0.00 | 0.00 |
July | 323.93 | 121.73 | 202.20 | 468.45 | 15.05 | 0.00 | 0.00 | 0.00 |
August | 358.40 | 165.71 | 192.69 | 517.58 | 28.19 | 0.00 | 0.00 | 0.00 |
September | 254.99 | 111.32 | 143.67 | 307.25 | 82.59 | 0.33 | 0.00 | 0.00 |
October | 253.01 | 123.25 | 129.76 | 259.25 | 169.11 | 0.00 | 0.00 | 0.00 |
November | 119.15 | 34.81 | 84.34 | 65.06 | 282.75 | 0.00 | 0.00 | 0.00 |
December | 105.24 | 45.43 | 59.81 | 53.57 | 379.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.63 | 101.48 | 139.16 | 253.06 | 202.66 | 0.83 | 0.00 | 0.00 |
Minimum of Months | 105.24 | 34.81 | 59.81 | 53.57 | 15.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.40 | 165.71 | 206.50 | 517.58 | 429.42 | 0.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.88 | 148.23 | 77.66 | 185.40 | 316.29 | 0.00 | 0.00 | 0.00 |
February | 298.93 | 198.68 | 100.25 | 251.45 | 315.49 | 0.00 | 0.00 | 0.00 |
March | 264.85 | 145.80 | 119.05 | 241.52 | 226.67 | 0.00 | 0.00 | 0.00 |
April | 210.82 | 85.29 | 125.53 | 204.83 | 157.31 | 0.00 | 0.00 | 0.00 |
May | 181.07 | 37.07 | 144.00 | 195.02 | 83.76 | 0.00 | 0.00 | 0.00 |
June | 170.97 | 26.34 | 144.63 | 232.93 | 30.01 | 0.00 | 0.00 | 0.00 |
July | 177.90 | 30.03 | 147.87 | 285.24 | 6.59 | 0.00 | 0.00 | 0.00 |
August | 238.27 | 87.90 | 150.38 | 372.87 | 16.64 | 0.00 | 0.00 | 0.00 |
September | 251.44 | 126.25 | 125.20 | 329.13 | 53.03 | 0.00 | 0.00 | 0.00 |
October | 355.33 | 222.82 | 132.51 | 412.71 | 125.08 | 0.00 | 0.00 | 0.00 |
November | 246.04 | 147.60 | 98.45 | 227.70 | 217.85 | 0.00 | 0.00 | 0.00 |
December | 244.04 | 173.33 | 70.71 | 214.58 | 282.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.51 | 118.71 | 119.80 | 263.03 | 151.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 170.97 | 26.34 | 70.71 | 185.40 | 6.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 355.33 | 222.82 | 150.38 | 412.71 | 316.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 207.41 | 0.00 | 207.41 | 0.03 | 1942.92 | 0.00 | 0.00 | 0.00 |
February | 283.83 | 0.00 | 283.83 | 1.64 | 1984.39 | 0.00 | 0.00 | 0.00 |
March | 393.70 | 0.01 | 393.69 | 47.99 | 1362.60 | 0.00 | 0.00 | 0.00 |
April | 473.78 | 1.95 | 471.83 | 181.73 | 941.49 | 0.00 | 0.00 | 0.00 |
May | 630.15 | 23.06 | 607.09 | 454.24 | 511.86 | 0.00 | 0.00 | 0.00 |
June | 664.79 | 35.36 | 629.43 | 746.40 | 247.91 | 0.00 | 0.00 | 0.00 |
July | 645.25 | 25.18 | 620.07 | 902.59 | 115.55 | 0.00 | 0.00 | 0.00 |
August | 570.62 | 7.58 | 563.04 | 789.42 | 165.70 | 0.00 | 0.00 | 0.00 |
September | 429.66 | 0.25 | 429.41 | 400.95 | 400.53 | 0.00 | 0.00 | 0.00 |
October | 371.53 | 0.00 | 371.53 | 188.01 | 795.45 | 0.00 | 0.00 | 0.00 |
November | 260.60 | 0.00 | 260.60 | 23.40 | 1374.30 | 0.00 | 0.00 | 0.00 |
December | 180.92 | 0.00 | 180.92 | 0.23 | 1785.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 426.85 | 7.83 | 419.02 | 313.64 | 963.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 180.92 | 0.00 | 180.92 | 0.03 | 115.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 664.79 | 35.36 | 629.43 | 902.59 | 1984.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 207.41 | 0.00 | 207.41 | 0.00 | 2010.09 | 0.00 | 0.00 | 0.00 |
February | 283.83 | 0.00 | 283.83 | 0.78 | 2047.41 | 0.00 | 0.00 | 0.00 |
March | 393.70 | 0.01 | 393.69 | 41.22 | 1416.35 | 0.00 | 0.00 | 0.00 |
April | 473.78 | 1.95 | 471.83 | 169.24 | 973.58 | 0.00 | 0.00 | 0.00 |
May | 630.15 | 23.06 | 607.09 | 438.48 | 526.23 | 0.00 | 0.00 | 0.00 |
June | 664.79 | 35.36 | 629.43 | 731.91 | 256.63 | 0.00 | 0.00 | 0.00 |
July | 645.25 | 25.18 | 620.07 | 890.22 | 122.67 | 0.00 | 0.00 | 0.00 |
August | 570.62 | 7.58 | 563.04 | 776.60 | 173.40 | 0.00 | 0.00 | 0.00 |
September | 429.66 | 0.25 | 429.41 | 387.68 | 414.33 | 0.00 | 0.00 | 0.00 |
October | 371.53 | 0.00 | 371.53 | 177.00 | 819.51 | 0.00 | 0.00 | 0.00 |
November | 260.60 | 0.00 | 260.60 | 20.19 | 1428.39 | 0.00 | 0.00 | 0.00 |
December | 180.92 | 0.00 | 180.92 | 0.10 | 1858.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 426.85 | 7.83 | 419.02 | 305.00 | 997.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 180.92 | 0.00 | 180.92 | 0.00 | 122.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 664.79 | 35.36 | 629.43 | 890.22 | 2047.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.63 | 0.00 | 29.63 | 0.00 | 306.74 | 0.00 | 0.00 | 0.00 |
February | 40.55 | 0.00 | 40.55 | 0.05 | 312.28 | 0.00 | 0.00 | 0.00 |
March | 56.24 | 0.00 | 56.24 | 4.29 | 216.09 | 0.00 | 0.00 | 0.00 |
April | 67.69 | 0.28 | 67.41 | 22.83 | 147.76 | 0.00 | 0.00 | 0.00 |
May | 90.02 | 3.29 | 86.73 | 64.74 | 81.08 | 0.00 | 0.00 | 0.00 |
June | 94.97 | 5.05 | 89.92 | 110.41 | 42.22 | 0.00 | 0.00 | 0.00 |
July | 92.18 | 3.60 | 88.58 | 135.35 | 22.31 | 0.00 | 0.00 | 0.00 |
August | 81.52 | 1.08 | 80.44 | 117.31 | 29.27 | 0.00 | 0.00 | 0.00 |
September | 61.38 | 0.04 | 61.35 | 58.73 | 63.76 | 0.00 | 0.00 | 0.00 |
October | 53.08 | 0.00 | 53.08 | 24.08 | 123.18 | 0.00 | 0.00 | 0.00 |
November | 37.23 | 0.00 | 37.23 | 2.33 | 218.67 | 0.00 | 0.00 | 0.00 |
December | 25.85 | 0.00 | 25.85 | 0.00 | 283.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.98 | 1.12 | 59.86 | 45.34 | 152.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.85 | 0.00 | 25.85 | 0.00 | 22.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.97 | 5.05 | 89.92 | 135.35 | 312.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 230.52 | 92.10 | 138.42 | 88.79 | 1057.71 | 0.00 | 0.00 | 0.00 |
February | 357.91 | 166.67 | 191.24 | 167.54 | 1023.05 | 0.00 | 0.00 | 0.00 |
March | 459.61 | 195.33 | 264.28 | 308.31 | 749.75 | 0.00 | 0.00 | 0.00 |
April | 550.19 | 241.49 | 308.71 | 468.08 | 519.30 | 0.00 | 0.00 | 0.00 |
May | 664.25 | 264.71 | 399.53 | 698.55 | 307.00 | 0.00 | 0.00 | 0.00 |
June | 616.80 | 223.41 | 393.39 | 782.26 | 162.15 | 0.00 | 0.00 | 0.00 |
July | 618.68 | 222.74 | 395.95 | 894.51 | 84.86 | 0.00 | 0.00 | 0.00 |
August | 697.94 | 314.88 | 383.06 | 994.16 | 109.16 | 0.00 | 0.00 | 0.00 |
September | 522.09 | 235.20 | 286.89 | 625.64 | 228.90 | 0.00 | 0.00 | 0.00 |
October | 471.66 | 213.50 | 258.16 | 455.61 | 431.45 | 0.00 | 0.00 | 0.00 |
November | 292.13 | 112.26 | 179.87 | 162.97 | 737.22 | 0.00 | 0.00 | 0.00 |
December | 228.39 | 107.77 | 120.63 | 102.61 | 960.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 476.61 | 199.40 | 277.21 | 481.31 | 528.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 228.39 | 92.10 | 120.63 | 88.79 | 84.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 697.94 | 314.88 | 399.53 | 994.16 | 1057.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 154.02 | 101.07 | 52.95 | 123.69 | 258.61 | 0.00 | 0.00 | 0.00 |
February | 203.83 | 135.47 | 68.36 | 169.13 | 249.61 | 0.00 | 0.00 | 0.00 |
March | 180.59 | 99.41 | 81.18 | 160.87 | 192.40 | 0.00 | 0.00 | 0.00 |
April | 143.75 | 58.16 | 85.59 | 134.40 | 144.30 | 0.00 | 0.00 | 0.00 |
May | 123.46 | 25.28 | 98.18 | 125.13 | 86.77 | 0.00 | 0.00 | 0.00 |
June | 116.58 | 17.96 | 98.61 | 149.39 | 45.64 | 0.00 | 0.00 | 0.00 |
July | 121.30 | 20.47 | 100.83 | 183.87 | 23.26 | 0.00 | 0.00 | 0.00 |
August | 162.47 | 59.93 | 102.53 | 246.50 | 30.02 | 0.00 | 0.00 | 0.00 |
September | 171.45 | 86.08 | 85.37 | 221.91 | 62.52 | 0.00 | 0.00 | 0.00 |
October | 242.28 | 151.93 | 90.35 | 281.04 | 113.41 | 0.00 | 0.00 | 0.00 |
November | 167.77 | 100.64 | 67.13 | 151.91 | 185.07 | 0.00 | 0.00 | 0.00 |
December | 166.40 | 118.19 | 48.21 | 143.71 | 233.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 162.63 | 80.94 | 81.69 | 174.45 | 134.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.58 | 17.96 | 48.21 | 123.69 | 23.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.28 | 151.93 | 102.53 | 281.04 | 258.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 37.53 | 0.00 | 37.53 | 0.02 | 331.97 | 206.17 | 0.00 | 0.00 |
February | 51.35 | 0.00 | 51.35 | 0.35 | 342.70 | 179.00 | 0.00 | 0.00 |
March | 71.23 | 0.00 | 71.23 | 8.01 | 233.79 | 536.33 | 0.00 | 0.00 |
April | 85.72 | 0.35 | 85.37 | 31.77 | 164.60 | 374.67 | 0.00 | 0.00 |
May | 114.01 | 4.17 | 109.84 | 83.04 | 90.65 | 41.00 | 0.00 | 0.00 |
June | 120.28 | 6.40 | 113.88 | 137.65 | 41.89 | 0.00 | 0.00 | 0.00 |
July | 116.74 | 4.56 | 112.19 | 166.11 | 18.19 | 0.00 | 0.00 | 0.00 |
August | 103.24 | 1.37 | 101.87 | 144.77 | 27.51 | 0.00 | 0.00 | 0.00 |
September | 77.74 | 0.05 | 77.69 | 72.17 | 69.90 | 5.17 | 0.00 | 0.00 |
October | 67.22 | 0.00 | 67.22 | 31.30 | 143.90 | 145.50 | 0.00 | 0.00 |
November | 47.15 | 0.00 | 47.15 | 3.36 | 237.90 | 468.67 | 0.00 | 0.00 |
December | 32.73 | 0.00 | 32.73 | 0.05 | 302.38 | 253.67 | 0.00 | 0.00 |
Annual Sum or Average | 77.23 | 1.42 | 75.81 | 56.96 | 166.10 | 2210.17 | 0.00 | 0.00 |
Minimum of Months | 32.73 | 0.00 | 32.73 | 0.02 | 18.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.28 | 6.40 | 113.88 | 166.11 | 342.70 | 536.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.57 | 0.00 | 33.57 | 0.02 | 297.01 | 206.17 | 0.00 | 0.00 |
February | 45.95 | 0.00 | 45.95 | 0.31 | 306.62 | 179.00 | 0.00 | 0.00 |
March | 63.73 | 0.00 | 63.73 | 7.17 | 209.18 | 536.33 | 0.00 | 0.00 |
April | 76.69 | 0.32 | 76.38 | 28.43 | 147.27 | 374.67 | 0.00 | 0.00 |
May | 102.01 | 3.73 | 98.27 | 74.29 | 81.10 | 41.00 | 0.00 | 0.00 |
June | 107.61 | 5.72 | 101.89 | 123.16 | 37.48 | 0.00 | 0.00 | 0.00 |
July | 104.45 | 4.08 | 100.37 | 148.62 | 16.28 | 0.00 | 0.00 | 0.00 |
August | 92.37 | 1.23 | 91.14 | 129.53 | 24.62 | 0.00 | 0.00 | 0.00 |
September | 69.55 | 0.04 | 69.51 | 64.57 | 62.54 | 5.17 | 0.00 | 0.00 |
October | 60.14 | 0.00 | 60.14 | 28.00 | 128.74 | 145.50 | 0.00 | 0.00 |
November | 42.18 | 0.00 | 42.18 | 3.00 | 212.85 | 468.67 | 0.00 | 0.00 |
December | 29.29 | 0.00 | 29.29 | 0.04 | 270.51 | 253.67 | 0.00 | 0.00 |
Annual Sum or Average | 69.10 | 1.27 | 67.83 | 50.96 | 148.60 | 2210.17 | 0.00 | 0.00 |
Minimum of Months | 29.29 | 0.00 | 29.29 | 0.02 | 16.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.61 | 5.72 | 101.89 | 148.62 | 306.62 | 536.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 574.99 | 377.32 | 197.68 | 487.40 | 827.66 | 192.67 | 0.00 | 0.00 |
February | 760.95 | 505.75 | 255.20 | 662.80 | 816.37 | 160.33 | 0.00 | 0.00 |
March | 674.20 | 371.14 | 303.06 | 621.99 | 625.83 | 484.83 | 0.00 | 0.00 |
April | 536.64 | 217.11 | 319.53 | 508.73 | 478.24 | 341.33 | 0.00 | 0.00 |
May | 460.91 | 94.37 | 366.55 | 466.38 | 289.33 | 44.83 | 0.00 | 0.00 |
June | 435.21 | 67.06 | 368.16 | 551.99 | 134.10 | 0.00 | 0.00 | 0.00 |
July | 452.84 | 76.43 | 376.41 | 672.91 | 55.98 | 0.00 | 0.00 | 0.00 |
August | 606.54 | 223.75 | 382.79 | 904.31 | 84.13 | 0.00 | 0.00 | 0.00 |
September | 640.06 | 321.37 | 318.70 | 815.02 | 202.24 | 3.83 | 0.00 | 0.00 |
October | 904.52 | 567.21 | 337.31 | 1043.56 | 390.28 | 115.17 | 0.00 | 0.00 |
November | 626.32 | 375.71 | 250.61 | 583.75 | 602.37 | 409.33 | 0.00 | 0.00 |
December | 621.22 | 441.22 | 180.00 | 563.57 | 738.90 | 224.83 | 0.00 | 0.00 |
Annual Sum or Average | 607.14 | 302.17 | 304.97 | 657.28 | 434.91 | 1977.17 | 0.00 | 0.00 |
Minimum of Months | 435.21 | 67.06 | 180.00 | 466.38 | 55.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 904.52 | 567.21 | 382.79 | 1043.56 | 827.66 | 484.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181647E+10 | 0.119199E+10 | 0.624478E+09 | 0.158676E+10 | 0.235761E+10 |
February | 0.217128E+10 | 0.144309E+10 | 0.728187E+09 | 0.193846E+10 | 0.211648E+10 |
March | 0.212987E+10 | 0.117247E+10 | 0.957401E+09 | 0.204032E+10 | 0.169938E+10 |
April | 0.164063E+10 | 0.663760E+09 | 0.976872E+09 | 0.165848E+10 | 0.118219E+10 |
May | 0.145607E+10 | 0.298110E+09 | 0.115796E+10 | 0.158578E+10 | 0.719779E+09 |
June | 0.133054E+10 | 0.205009E+09 | 0.112553E+10 | 0.172513E+10 | 0.356453E+09 |
July | 0.143058E+10 | 0.241454E+09 | 0.118913E+10 | 0.211472E+10 | 0.172594E+09 |
August | 0.191613E+10 | 0.706842E+09 | 0.120928E+10 | 0.283644E+10 | 0.260208E+09 |
September | 0.195681E+10 | 0.982486E+09 | 0.974320E+09 | 0.252943E+10 | 0.534380E+09 |
October | 0.285748E+10 | 0.179188E+10 | 0.106559E+10 | 0.336921E+10 | 0.106444E+10 |
November | 0.191479E+10 | 0.114863E+10 | 0.766160E+09 | 0.185213E+10 | 0.158867E+10 |
December | 0.196250E+10 | 0.139387E+10 | 0.568630E+09 | 0.181480E+10 | 0.211936E+10 |
Annual Sum or Average | 0.225831E+11 | 0.112396E+11 | 0.113436E+11 | 0.250517E+11 | 0.141715E+11 |
Minimum of Months | 0.133054E+10 | 0.205009E+09 | 0.568630E+09 | 0.158578E+10 | 0.172594E+09 |
Maximum of Months | 0.285748E+10 | 0.179188E+10 | 0.120928E+10 | 0.336921E+10 | 0.235761E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.511507E+10 | 0.335658E+10 | 0.175849E+10 | 0.446843E+10 | 0.672227E+10 |
February | 0.611418E+10 | 0.406366E+10 | 0.205053E+10 | 0.546551E+10 | 0.600520E+10 |
March | 0.599757E+10 | 0.330160E+10 | 0.269598E+10 | 0.572347E+10 | 0.487552E+10 |
April | 0.461991E+10 | 0.186910E+10 | 0.275081E+10 | 0.456570E+10 | 0.353658E+10 |
May | 0.410021E+10 | 0.839458E+09 | 0.326075E+10 | 0.424500E+10 | 0.235762E+10 |
June | 0.374672E+10 | 0.577290E+09 | 0.316943E+10 | 0.471219E+10 | 0.114371E+10 |
July | 0.402843E+10 | 0.679917E+09 | 0.334851E+10 | 0.585714E+10 | 0.558280E+09 |
August | 0.539569E+10 | 0.199042E+10 | 0.340527E+10 | 0.789000E+10 | 0.818127E+09 |
September | 0.551024E+10 | 0.276662E+10 | 0.274362E+10 | 0.698006E+10 | 0.172976E+10 |
October | 0.804646E+10 | 0.504582E+10 | 0.300065E+10 | 0.936819E+10 | 0.324375E+10 |
November | 0.539191E+10 | 0.323446E+10 | 0.215746E+10 | 0.515878E+10 | 0.465878E+10 |
December | 0.552626E+10 | 0.392504E+10 | 0.160122E+10 | 0.511014E+10 | 0.604041E+10 |
Annual Sum or Average | 0.635926E+11 | 0.316499E+11 | 0.319427E+11 | 0.695446E+11 | 0.416900E+11 |
Minimum of Months | 0.374672E+10 | 0.577290E+09 | 0.160122E+10 | 0.424500E+10 | 0.558280E+09 |
Maximum of Months | 0.804646E+10 | 0.504582E+10 | 0.340527E+10 | 0.936819E+10 | 0.672227E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.664476E+10 | 0.436038E+10 | 0.228438E+10 | 0.586306E+10 | 0.939557E+10 |
February | 0.794267E+10 | 0.527892E+10 | 0.266375E+10 | 0.719080E+10 | 0.837990E+10 |
March | 0.779119E+10 | 0.428896E+10 | 0.350223E+10 | 0.758652E+10 | 0.692880E+10 |
April | 0.600153E+10 | 0.242807E+10 | 0.357345E+10 | 0.614097E+10 | 0.495728E+10 |
May | 0.532640E+10 | 0.109050E+10 | 0.423590E+10 | 0.583945E+10 | 0.309970E+10 |
June | 0.486720E+10 | 0.749933E+09 | 0.411726E+10 | 0.644744E+10 | 0.148258E+10 |
July | 0.523316E+10 | 0.883251E+09 | 0.434990E+10 | 0.794480E+10 | 0.703115E+09 |
August | 0.700930E+10 | 0.258567E+10 | 0.442363E+10 | 0.106264E+11 | 0.104161E+10 |
September | 0.715811E+10 | 0.359399E+10 | 0.356412E+10 | 0.939666E+10 | 0.223217E+10 |
October | 0.104528E+11 | 0.655480E+10 | 0.389801E+10 | 0.125017E+11 | 0.436757E+10 |
November | 0.700440E+10 | 0.420174E+10 | 0.280266E+10 | 0.680362E+10 | 0.656615E+10 |
December | 0.717893E+10 | 0.509885E+10 | 0.208008E+10 | 0.669643E+10 | 0.855576E+10 |
Annual Sum or Average | 0.826105E+11 | 0.411151E+11 | 0.414954E+11 | 0.930379E+11 | 0.577102E+11 |
Minimum of Months | 0.486720E+10 | 0.749933E+09 | 0.208008E+10 | 0.583945E+10 | 0.703115E+09 |
Maximum of Months | 0.104528E+11 | 0.655480E+10 | 0.442363E+10 | 0.125017E+11 | 0.939557E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.412521E+09 | 0.270702E+09 | 0.141819E+09 | 0.355330E+09 | 0.564028E+09 |
February | 0.493098E+09 | 0.327727E+09 | 0.165371E+09 | 0.433799E+09 | 0.508896E+09 |
March | 0.483694E+09 | 0.266268E+09 | 0.217426E+09 | 0.452938E+09 | 0.413623E+09 |
April | 0.372588E+09 | 0.150740E+09 | 0.221848E+09 | 0.368133E+09 | 0.282362E+09 |
May | 0.330675E+09 | 67700844.96 | 0.262974E+09 | 0.357476E+09 | 0.158980E+09 |
June | 0.302166E+09 | 46557493.95 | 0.255609E+09 | 0.408209E+09 | 58733303.79 |
July | 0.324886E+09 | 54834170.96 | 0.270052E+09 | 0.516568E+09 | 15175745.59 |
August | 0.435153E+09 | 0.160524E+09 | 0.274629E+09 | 0.679513E+09 | 34425450.43 |
September | 0.444391E+09 | 0.223123E+09 | 0.221268E+09 | 0.587646E+09 | 98194419.74 |
October | 0.648933E+09 | 0.406936E+09 | 0.241997E+09 | 0.767855E+09 | 0.230235E+09 |
November | 0.434849E+09 | 0.260853E+09 | 0.173995E+09 | 0.415939E+09 | 0.379079E+09 |
December | 0.445684E+09 | 0.316548E+09 | 0.129136E+09 | 0.407826E+09 | 0.507327E+09 |
Annual Sum or Average | 0.512864E+10 | 0.255251E+10 | 0.257612E+10 | 0.575123E+10 | 0.325106E+10 |
Minimum of Months | 0.302166E+09 | 46557493.95 | 0.129136E+09 | 0.355330E+09 | 15175745.59 |
Maximum of Months | 0.648933E+09 | 0.406936E+09 | 0.274629E+09 | 0.767855E+09 | 0.564028E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306595E+09 | 0.125866E+09 | 0.180729E+09 | 0.138638E+09 | 0.116649E+10 |
February | 0.406788E+09 | 0.178528E+09 | 0.228260E+09 | 0.209363E+09 | 0.107559E+10 |
March | 0.668971E+09 | 0.310018E+09 | 0.358954E+09 | 0.491844E+09 | 0.780260E+09 |
April | 0.703127E+09 | 0.300478E+09 | 0.402648E+09 | 0.635090E+09 | 0.515917E+09 |
May | 0.848784E+09 | 0.322657E+09 | 0.526127E+09 | 0.930037E+09 | 0.283762E+09 |
June | 0.897447E+09 | 0.362187E+09 | 0.535260E+09 | 0.118029E+10 | 0.106418E+09 |
July | 0.867624E+09 | 0.326043E+09 | 0.541581E+09 | 0.128568E+10 | 28254962.34 |
August | 0.959928E+09 | 0.443831E+09 | 0.516097E+09 | 0.140444E+10 | 63940865.77 |
September | 0.660939E+09 | 0.288548E+09 | 0.372391E+09 | 0.818442E+09 | 0.183925E+09 |
October | 0.677659E+09 | 0.330113E+09 | 0.347546E+09 | 0.692455E+09 | 0.447503E+09 |
November | 0.308834E+09 | 90224391.19 | 0.218610E+09 | 0.150144E+09 | 0.779194E+09 |
December | 0.281882E+09 | 0.121681E+09 | 0.160201E+09 | 0.125795E+09 | 0.106550E+10 |
Annual Sum or Average | 0.758858E+10 | 0.320017E+10 | 0.438840E+10 | 0.806221E+10 | 0.649676E+10 |
Minimum of Months | 0.281882E+09 | 90224391.19 | 0.160201E+09 | 0.125795E+09 | 28254962.34 |
Maximum of Months | 0.959928E+09 | 0.443831E+09 | 0.541581E+09 | 0.140444E+10 | 0.116649E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 79364137.35 | 0.00 | 79364137.35 | 220744.57 | 0.651430E+09 |
February | 98096151.26 | 0.00 | 98096151.26 | 1775617.10 | 0.611345E+09 |
March | 0.150645E+09 | 3137.78 | 0.150642E+09 | 24130501.66 | 0.449694E+09 |
April | 0.175441E+09 | 722906.23 | 0.174718E+09 | 76909951.73 | 0.289691E+09 |
May | 0.241122E+09 | 8824489.88 | 0.232298E+09 | 0.188566E+09 | 0.158337E+09 |
June | 0.246172E+09 | 13093671.01 | 0.233079E+09 | 0.287095E+09 | 72773865.62 |
July | 0.246901E+09 | 9636002.91 | 0.237265E+09 | 0.375447E+09 | 21771037.42 |
August | 0.218343E+09 | 2901157.23 | 0.215442E+09 | 0.330941E+09 | 40730230.09 |
September | 0.159103E+09 | 92495.66 | 0.159011E+09 | 0.160219E+09 | 0.120653E+09 |
October | 0.142165E+09 | 0.00 | 0.142165E+09 | 80500888.44 | 0.261265E+09 |
November | 96498654.68 | 0.00 | 96498654.68 | 12920643.82 | 0.428496E+09 |
December | 69226616.93 | 0.00 | 69226616.93 | 312795.76 | 0.594522E+09 |
Annual Sum or Average | 0.192308E+10 | 35273860.71 | 0.188781E+10 | 0.153904E+10 | 0.370071E+10 |
Minimum of Months | 69226616.93 | 0.00 | 69226616.93 | 220744.57 | 21771037.42 |
Maximum of Months | 0.246901E+09 | 13093671.01 | 0.237265E+09 | 0.375447E+09 | 0.651430E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306595E+09 | 0.125866E+09 | 0.180729E+09 | 0.149944E+09 | 0.114944E+10 |
February | 0.406788E+09 | 0.178528E+09 | 0.228260E+09 | 0.224891E+09 | 0.105452E+10 |
March | 0.668971E+09 | 0.310018E+09 | 0.358954E+09 | 0.507826E+09 | 0.770802E+09 |
April | 0.703127E+09 | 0.300478E+09 | 0.402648E+09 | 0.637564E+09 | 0.519613E+09 |
May | 0.848784E+09 | 0.322657E+09 | 0.526127E+09 | 0.908518E+09 | 0.304123E+09 |
June | 0.897447E+09 | 0.362187E+09 | 0.535260E+09 | 0.114102E+10 | 0.139529E+09 |
July | 0.867624E+09 | 0.326043E+09 | 0.541581E+09 | 0.127044E+10 | 41162959.78 |
August | 0.959928E+09 | 0.443831E+09 | 0.516097E+09 | 0.140023E+10 | 77907947.47 |
September | 0.660939E+09 | 0.288548E+09 | 0.372391E+09 | 0.806103E+09 | 0.217815E+09 |
October | 0.677659E+09 | 0.330113E+09 | 0.347546E+09 | 0.698865E+09 | 0.466341E+09 |
November | 0.308834E+09 | 90224391.19 | 0.218610E+09 | 0.162920E+09 | 0.763527E+09 |
December | 0.281882E+09 | 0.121681E+09 | 0.160201E+09 | 0.138695E+09 | 0.104441E+10 |
Annual Sum or Average | 0.758858E+10 | 0.320017E+10 | 0.438840E+10 | 0.804702E+10 | 0.654919E+10 |
Minimum of Months | 0.281882E+09 | 90224391.19 | 0.160201E+09 | 0.138695E+09 | 41162959.78 |
Maximum of Months | 0.959928E+09 | 0.443831E+09 | 0.541581E+09 | 0.140023E+10 | 0.114944E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.329951E+09 | 0.216519E+09 | 0.113433E+09 | 0.265820E+09 | 0.518271E+09 |
February | 0.394400E+09 | 0.262129E+09 | 0.132271E+09 | 0.314502E+09 | 0.503484E+09 |
March | 0.386878E+09 | 0.212972E+09 | 0.173906E+09 | 0.329555E+09 | 0.444412E+09 |
April | 0.298011E+09 | 0.120568E+09 | 0.177443E+09 | 0.259763E+09 | 0.329467E+09 |
May | 0.264487E+09 | 54149907.01 | 0.210337E+09 | 0.240671E+09 | 0.215061E+09 |
June | 0.241685E+09 | 37238589.41 | 0.204446E+09 | 0.272464E+09 | 0.112021E+09 |
July | 0.259857E+09 | 43858614.47 | 0.215998E+09 | 0.347352E+09 | 65918306.02 |
August | 0.348053E+09 | 0.128394E+09 | 0.219659E+09 | 0.480460E+09 | 84875405.31 |
September | 0.355442E+09 | 0.178463E+09 | 0.176980E+09 | 0.423038E+09 | 0.159144E+09 |
October | 0.519043E+09 | 0.325484E+09 | 0.193559E+09 | 0.567649E+09 | 0.282042E+09 |
November | 0.347810E+09 | 0.208641E+09 | 0.139168E+09 | 0.295752E+09 | 0.419130E+09 |
December | 0.356476E+09 | 0.253188E+09 | 0.103288E+09 | 0.294570E+09 | 0.517350E+09 |
Annual Sum or Average | 0.410209E+10 | 0.204161E+10 | 0.206049E+10 | 0.409160E+10 | 0.365117E+10 |
Minimum of Months | 0.241685E+09 | 37238589.41 | 0.103288E+09 | 0.240671E+09 | 65918306.02 |
Maximum of Months | 0.519043E+09 | 0.325484E+09 | 0.219659E+09 | 0.567649E+09 | 0.518271E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 63499726.01 | 0.00 | 63499726.01 | 59922.84 | 0.548039E+09 |
February | 78487323.57 | 0.00 | 78487323.57 | 1202983.82 | 0.506008E+09 |
March | 0.120532E+09 | 2510.56 | 0.120530E+09 | 21049500.98 | 0.363575E+09 |
April | 0.140371E+09 | 578401.65 | 0.139793E+09 | 68228047.07 | 0.230392E+09 |
May | 0.192923E+09 | 7060527.70 | 0.185863E+09 | 0.166469E+09 | 0.121963E+09 |
June | 0.196964E+09 | 10476325.32 | 0.186488E+09 | 0.249288E+09 | 51920009.85 |
July | 0.197547E+09 | 7709824.18 | 0.189837E+09 | 0.318884E+09 | 14835472.03 |
August | 0.174698E+09 | 2321233.44 | 0.172376E+09 | 0.284833E+09 | 28505038.46 |
September | 0.127300E+09 | 74006.34 | 0.127226E+09 | 0.138813E+09 | 89278563.10 |
October | 0.113747E+09 | 0.00 | 0.113747E+09 | 71064331.53 | 0.200442E+09 |
November | 77209156.90 | 0.00 | 77209156.90 | 11008268.46 | 0.354994E+09 |
December | 55388634.65 | 0.00 | 55388634.65 | 184971.89 | 0.497690E+09 |
Annual Sum or Average | 0.153867E+10 | 28222829.17 | 0.151044E+10 | 0.133109E+10 | 0.300764E+10 |
Minimum of Months | 55388634.65 | 0.00 | 55388634.65 | 59922.84 | 14835472.03 |
Maximum of Months | 0.197547E+09 | 10476325.32 | 0.189837E+09 | 0.318884E+09 | 0.548039E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308740E+09 | 0.123352E+09 | 0.185388E+09 | 0.133640E+09 | 0.114718E+10 |
February | 0.432957E+09 | 0.201619E+09 | 0.231338E+09 | 0.223620E+09 | 0.103865E+10 |
March | 0.615555E+09 | 0.261608E+09 | 0.353948E+09 | 0.438390E+09 | 0.790234E+09 |
April | 0.713102E+09 | 0.312990E+09 | 0.400112E+09 | 0.639021E+09 | 0.500276E+09 |
May | 0.889620E+09 | 0.354528E+09 | 0.535092E+09 | 0.980039E+09 | 0.275330E+09 |
June | 0.799432E+09 | 0.289566E+09 | 0.509867E+09 | 0.105256E+10 | 0.101420E+09 |
July | 0.828596E+09 | 0.298309E+09 | 0.530288E+09 | 0.123958E+10 | 26564993.57 |
August | 0.934751E+09 | 0.421723E+09 | 0.513028E+09 | 0.136852E+10 | 59560398.32 |
September | 0.676680E+09 | 0.304840E+09 | 0.371840E+09 | 0.833565E+09 | 0.175308E+09 |
October | 0.631698E+09 | 0.285942E+09 | 0.345757E+09 | 0.630159E+09 | 0.433066E+09 |
November | 0.378629E+09 | 0.145499E+09 | 0.233130E+09 | 0.231715E+09 | 0.753049E+09 |
December | 0.305884E+09 | 0.144331E+09 | 0.161554E+09 | 0.152911E+09 | 0.104210E+10 |
Annual Sum or Average | 0.751565E+10 | 0.314431E+10 | 0.437134E+10 | 0.792372E+10 | 0.634274E+10 |
Minimum of Months | 0.305884E+09 | 0.123352E+09 | 0.161554E+09 | 0.133640E+09 | 26564993.57 |
Maximum of Months | 0.934751E+09 | 0.421723E+09 | 0.535092E+09 | 0.136852E+10 | 0.114718E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.412521E+09 | 0.270702E+09 | 0.141819E+09 | 0.353281E+09 | 0.562799E+09 |
February | 0.493098E+09 | 0.327727E+09 | 0.165371E+09 | 0.429498E+09 | 0.507434E+09 |
March | 0.483694E+09 | 0.266268E+09 | 0.217426E+09 | 0.448939E+09 | 0.409877E+09 |
April | 0.372588E+09 | 0.150740E+09 | 0.221848E+09 | 0.364486E+09 | 0.280409E+09 |
May | 0.330675E+09 | 67700844.96 | 0.262974E+09 | 0.353573E+09 | 0.156785E+09 |
June | 0.302166E+09 | 46557493.95 | 0.255609E+09 | 0.408275E+09 | 56648115.93 |
July | 0.324886E+09 | 54834170.96 | 0.270052E+09 | 0.516410E+09 | 14310989.20 |
August | 0.435153E+09 | 0.160524E+09 | 0.274629E+09 | 0.678381E+09 | 33161073.97 |
September | 0.444391E+09 | 0.223123E+09 | 0.221268E+09 | 0.585432E+09 | 96664996.62 |
October | 0.648933E+09 | 0.406936E+09 | 0.241997E+09 | 0.765648E+09 | 0.227552E+09 |
November | 0.434849E+09 | 0.260853E+09 | 0.173995E+09 | 0.412256E+09 | 0.379035E+09 |
December | 0.445684E+09 | 0.316548E+09 | 0.129136E+09 | 0.404936E+09 | 0.506361E+09 |
Annual Sum or Average | 0.512864E+10 | 0.255251E+10 | 0.257612E+10 | 0.572112E+10 | 0.323104E+10 |
Minimum of Months | 0.302166E+09 | 46557493.95 | 0.129136E+09 | 0.353281E+09 | 14310989.20 |
Maximum of Months | 0.648933E+09 | 0.406936E+09 | 0.274629E+09 | 0.765648E+09 | 0.562799E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 79364137.35 | 0.00 | 79364137.35 | 165229.08 | 0.651753E+09 |
February | 98096151.26 | 0.00 | 98096151.26 | 1229675.67 | 0.612142E+09 |
March | 0.150645E+09 | 3137.78 | 0.150642E+09 | 21212989.38 | 0.447339E+09 |
April | 0.175441E+09 | 722906.23 | 0.174718E+09 | 73553872.16 | 0.285971E+09 |
May | 0.241122E+09 | 8824489.88 | 0.232298E+09 | 0.186308E+09 | 0.153450E+09 |
June | 0.246172E+09 | 13093671.01 | 0.233079E+09 | 0.288080E+09 | 67544148.31 |
July | 0.246901E+09 | 9636002.91 | 0.237265E+09 | 0.373168E+09 | 20464706.63 |
August | 0.218343E+09 | 2901157.23 | 0.215442E+09 | 0.326474E+09 | 38718192.12 |
September | 0.159103E+09 | 92495.66 | 0.159011E+09 | 0.156587E+09 | 0.114718E+09 |
October | 0.142165E+09 | 0.00 | 0.142165E+09 | 76787729.62 | 0.251521E+09 |
November | 96498654.68 | 0.00 | 96498654.68 | 11274198.35 | 0.430762E+09 |
December | 69226616.93 | 0.00 | 69226616.93 | 197326.95 | 0.595123E+09 |
Annual Sum or Average | 0.192308E+10 | 35273860.71 | 0.188781E+10 | 0.151504E+10 | 0.366950E+10 |
Minimum of Months | 69226616.93 | 0.00 | 69226616.93 | 165229.08 | 20464706.63 |
Maximum of Months | 0.246901E+09 | 13093671.01 | 0.237265E+09 | 0.373168E+09 | 0.651753E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308740E+09 | 0.123352E+09 | 0.185388E+09 | 0.138396E+09 | 0.112269E+10 |
February | 0.432957E+09 | 0.201619E+09 | 0.231338E+09 | 0.231096E+09 | 0.100723E+10 |
March | 0.615555E+09 | 0.261608E+09 | 0.353948E+09 | 0.448300E+09 | 0.774954E+09 |
April | 0.713102E+09 | 0.312990E+09 | 0.400112E+09 | 0.643708E+09 | 0.501356E+09 |
May | 0.889620E+09 | 0.354528E+09 | 0.535092E+09 | 0.966247E+09 | 0.294359E+09 |
June | 0.799432E+09 | 0.289566E+09 | 0.509867E+09 | 0.101916E+10 | 0.131940E+09 |
July | 0.828596E+09 | 0.298309E+09 | 0.530288E+09 | 0.122008E+10 | 39344083.64 |
August | 0.934751E+09 | 0.421723E+09 | 0.513028E+09 | 0.135649E+10 | 71835737.35 |
September | 0.676680E+09 | 0.304840E+09 | 0.371840E+09 | 0.821581E+09 | 0.203688E+09 |
October | 0.631698E+09 | 0.285942E+09 | 0.345757E+09 | 0.639410E+09 | 0.443207E+09 |
November | 0.378629E+09 | 0.145499E+09 | 0.233130E+09 | 0.240419E+09 | 0.734590E+09 |
December | 0.305884E+09 | 0.144331E+09 | 0.161554E+09 | 0.158823E+09 | 0.101248E+10 |
Annual Sum or Average | 0.751565E+10 | 0.314431E+10 | 0.437134E+10 | 0.788371E+10 | 0.633768E+10 |
Minimum of Months | 0.305884E+09 | 0.123352E+09 | 0.161554E+09 | 0.138396E+09 | 39344083.64 |
Maximum of Months | 0.934751E+09 | 0.421723E+09 | 0.535092E+09 | 0.135649E+10 | 0.112269E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100510E+09 | 0.00 | 0.100510E+09 | 26710.34 | 0.928169E+09 |
February | 0.124233E+09 | 0.00 | 0.124233E+09 | 421932.41 | 0.888148E+09 |
March | 0.190783E+09 | 3973.80 | 0.190779E+09 | 20629904.35 | 0.684599E+09 |
April | 0.222184E+09 | 915515.13 | 0.221269E+09 | 86458687.92 | 0.445578E+09 |
May | 0.305366E+09 | 11175659.64 | 0.294191E+09 | 0.236625E+09 | 0.239052E+09 |
June | 0.311762E+09 | 16582308.17 | 0.295180E+09 | 0.374275E+09 | 0.103822E+09 |
July | 0.312685E+09 | 12203389.69 | 0.300482E+09 | 0.465163E+09 | 43255791.25 |
August | 0.276518E+09 | 3674132.58 | 0.272844E+09 | 0.406962E+09 | 69147353.23 |
September | 0.201494E+09 | 117139.92 | 0.201377E+09 | 0.199600E+09 | 0.176091E+09 |
October | 0.180043E+09 | 0.00 | 0.180043E+09 | 91253506.91 | 0.388116E+09 |
November | 0.122209E+09 | 0.00 | 0.122209E+09 | 9560327.45 | 0.668880E+09 |
December | 87671142.38 | 0.00 | 87671142.38 | 14542.53 | 0.896521E+09 |
Annual Sum or Average | 0.243546E+10 | 44672118.94 | 0.239079E+10 | 0.189099E+10 | 0.553138E+10 |
Minimum of Months | 87671142.38 | 0.00 | 87671142.38 | 14542.53 | 43255791.25 |
Maximum of Months | 0.312685E+09 | 16582308.17 | 0.300482E+09 | 0.465163E+09 | 0.928169E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37052027.01 | 0.00 | 37052027.01 | 9846.54 | 0.342162E+09 |
February | 45797275.28 | 0.00 | 45797275.28 | 155541.76 | 0.327408E+09 |
March | 70330436.59 | 1464.91 | 70328971.69 | 7605036.96 | 0.252371E+09 |
April | 81906406.45 | 337496.79 | 81568909.66 | 31872252.34 | 0.164258E+09 |
May | 0.112571E+09 | 4119810.89 | 0.108451E+09 | 87229626.46 | 88124429.86 |
June | 0.114928E+09 | 6112925.41 | 0.108815E+09 | 0.137973E+09 | 38273001.85 |
July | 0.115269E+09 | 4498674.74 | 0.110770E+09 | 0.171478E+09 | 15945875.74 |
August | 0.101936E+09 | 1354437.40 | 0.100581E+09 | 0.150023E+09 | 25490577.57 |
September | 74279187.78 | 43182.62 | 74236005.16 | 73580812.39 | 64914458.14 |
October | 66371413.33 | 0.00 | 66371413.33 | 33639821.16 | 0.143076E+09 |
November | 45051466.30 | 0.00 | 45051466.30 | 3524332.56 | 0.246577E+09 |
December | 32319213.26 | 0.00 | 32319213.26 | 5360.98 | 0.330495E+09 |
Annual Sum or Average | 0.897811E+09 | 16467992.77 | 0.881343E+09 | 0.697097E+09 | 0.203910E+10 |
Minimum of Months | 32319213.26 | 0.00 | 32319213.26 | 5360.98 | 15945875.74 |
Maximum of Months | 0.115269E+09 | 6112925.41 | 0.110770E+09 | 0.171478E+09 | 0.342162E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.192481E+09 | 0.126309E+09 | 66172224.49 | 0.163379E+09 | 0.289990E+09 |
February | 0.230078E+09 | 0.152916E+09 | 77161618.09 | 0.198819E+09 | 0.265725E+09 |
March | 0.225690E+09 | 0.124240E+09 | 0.101450E+09 | 0.207061E+09 | 0.227708E+09 |
April | 0.173848E+09 | 70334726.95 | 0.103513E+09 | 0.167694E+09 | 0.161044E+09 |
May | 0.154292E+09 | 31588941.45 | 0.122703E+09 | 0.162122E+09 | 95171733.78 |
June | 0.140990E+09 | 21723539.07 | 0.119266E+09 | 0.186006E+09 | 41265334.14 |
July | 0.151590E+09 | 25585403.21 | 0.126005E+09 | 0.233589E+09 | 16548233.87 |
August | 0.203041E+09 | 74899846.34 | 0.128141E+09 | 0.311343E+09 | 26364784.78 |
September | 0.207351E+09 | 0.104108E+09 | 0.103243E+09 | 0.270314E+09 | 63666645.79 |
October | 0.302790E+09 | 0.189875E+09 | 0.112915E+09 | 0.354893E+09 | 0.131562E+09 |
November | 0.202899E+09 | 0.121713E+09 | 81185403.72 | 0.187672E+09 | 0.210966E+09 |
December | 0.207954E+09 | 0.147700E+09 | 60254315.77 | 0.184980E+09 | 0.273699E+09 |
Annual Sum or Average | 0.239300E+10 | 0.119099E+10 | 0.120201E+10 | 0.262787E+10 | 0.180371E+10 |
Minimum of Months | 0.140990E+09 | 21723539.07 | 60254315.77 | 0.162122E+09 | 16548233.87 |
Maximum of Months | 0.302790E+09 | 0.189875E+09 | 0.128141E+09 | 0.354893E+09 | 0.289990E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.522432E+09 | 0.342827E+09 | 0.179605E+09 | 0.443443E+09 | 0.787091E+09 |
February | 0.624478E+09 | 0.415045E+09 | 0.209432E+09 | 0.539637E+09 | 0.721232E+09 |
March | 0.612568E+09 | 0.337212E+09 | 0.275356E+09 | 0.562005E+09 | 0.618046E+09 |
April | 0.471859E+09 | 0.190903E+09 | 0.280956E+09 | 0.455155E+09 | 0.437107E+09 |
May | 0.418779E+09 | 85738848.46 | 0.333040E+09 | 0.440033E+09 | 0.258316E+09 |
June | 0.382674E+09 | 58962128.47 | 0.323712E+09 | 0.504859E+09 | 0.112003E+09 |
July | 0.411447E+09 | 69444017.68 | 0.342003E+09 | 0.634008E+09 | 44915291.58 |
August | 0.551094E+09 | 0.203294E+09 | 0.347800E+09 | 0.845048E+09 | 71559418.69 |
September | 0.562793E+09 | 0.282571E+09 | 0.280223E+09 | 0.733686E+09 | 0.172804E+09 |
October | 0.821833E+09 | 0.515359E+09 | 0.306474E+09 | 0.963253E+09 | 0.357087E+09 |
November | 0.550708E+09 | 0.330354E+09 | 0.220354E+09 | 0.509381E+09 | 0.572606E+09 |
December | 0.564430E+09 | 0.400888E+09 | 0.163543E+09 | 0.502073E+09 | 0.742876E+09 |
Annual Sum or Average | 0.649510E+10 | 0.323260E+10 | 0.326250E+10 | 0.713258E+10 | 0.489564E+10 |
Minimum of Months | 0.382674E+09 | 58962128.47 | 0.163543E+09 | 0.440033E+09 | 44915291.58 |
Maximum of Months | 0.821833E+09 | 0.515359E+09 | 0.347800E+09 | 0.963253E+09 | 0.787091E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.412521E+09 | 0.270702E+09 | 0.141819E+09 | 0.355296E+09 | 0.554421E+09 |
February | 0.493098E+09 | 0.327727E+09 | 0.165371E+09 | 0.433813E+09 | 0.499779E+09 |
March | 0.483694E+09 | 0.266268E+09 | 0.217426E+09 | 0.451451E+09 | 0.402447E+09 |
April | 0.372588E+09 | 0.150740E+09 | 0.221848E+09 | 0.365352E+09 | 0.273541E+09 |
May | 0.330675E+09 | 67700844.96 | 0.262974E+09 | 0.352268E+09 | 0.154828E+09 |
June | 0.302166E+09 | 46557493.95 | 0.255609E+09 | 0.401397E+09 | 56783582.42 |
July | 0.324886E+09 | 54834170.96 | 0.270052E+09 | 0.509556E+09 | 13883498.36 |
August | 0.435153E+09 | 0.160524E+09 | 0.274629E+09 | 0.671741E+09 | 32432080.72 |
September | 0.444391E+09 | 0.223123E+09 | 0.221268E+09 | 0.581717E+09 | 94371854.55 |
October | 0.648933E+09 | 0.406936E+09 | 0.241997E+09 | 0.762215E+09 | 0.223417E+09 |
November | 0.434849E+09 | 0.260853E+09 | 0.173995E+09 | 0.417946E+09 | 0.364782E+09 |
December | 0.445684E+09 | 0.316548E+09 | 0.129136E+09 | 0.410236E+09 | 0.493526E+09 |
Annual Sum or Average | 0.512864E+10 | 0.255251E+10 | 0.257612E+10 | 0.571299E+10 | 0.316421E+10 |
Minimum of Months | 0.302166E+09 | 46557493.95 | 0.129136E+09 | 0.352268E+09 | 13883498.36 |
Maximum of Months | 0.648933E+09 | 0.406936E+09 | 0.274629E+09 | 0.762215E+09 | 0.554421E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306595E+09 | 0.125866E+09 | 0.180729E+09 | 0.139232E+09 | 0.114712E+10 |
February | 0.406788E+09 | 0.178528E+09 | 0.228260E+09 | 0.208725E+09 | 0.105768E+10 |
March | 0.668971E+09 | 0.310018E+09 | 0.358954E+09 | 0.489222E+09 | 0.756034E+09 |
April | 0.703127E+09 | 0.300478E+09 | 0.402648E+09 | 0.630124E+09 | 0.497618E+09 |
May | 0.848784E+09 | 0.322657E+09 | 0.526127E+09 | 0.919488E+09 | 0.275062E+09 |
June | 0.897447E+09 | 0.362187E+09 | 0.535260E+09 | 0.116421E+10 | 0.102351E+09 |
July | 0.867624E+09 | 0.326043E+09 | 0.541581E+09 | 0.127050E+10 | 25770455.73 |
August | 0.959928E+09 | 0.443831E+09 | 0.516097E+09 | 0.139026E+10 | 60048041.58 |
September | 0.660939E+09 | 0.288548E+09 | 0.372391E+09 | 0.809695E+09 | 0.176126E+09 |
October | 0.677659E+09 | 0.330113E+09 | 0.347546E+09 | 0.685260E+09 | 0.432600E+09 |
November | 0.308834E+09 | 90224391.19 | 0.218610E+09 | 0.152683E+09 | 0.748820E+09 |
December | 0.281882E+09 | 0.121681E+09 | 0.160201E+09 | 0.128262E+09 | 0.103539E+10 |
Annual Sum or Average | 0.758858E+10 | 0.320017E+10 | 0.438840E+10 | 0.798766E+10 | 0.631462E+10 |
Minimum of Months | 0.281882E+09 | 90224391.19 | 0.160201E+09 | 0.128262E+09 | 25770455.73 |
Maximum of Months | 0.959928E+09 | 0.443831E+09 | 0.541581E+09 | 0.139026E+10 | 0.114712E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 79364137.35 | 0.00 | 79364137.35 | 402889.45 | 0.640294E+09 |
February | 98096151.26 | 0.00 | 98096151.26 | 2258887.17 | 0.601503E+09 |
March | 0.150645E+09 | 3137.78 | 0.150642E+09 | 26024380.94 | 0.435696E+09 |
April | 0.175441E+09 | 722906.23 | 0.174718E+09 | 77958453.62 | 0.280585E+09 |
May | 0.241122E+09 | 8824489.88 | 0.232298E+09 | 0.184675E+09 | 0.156581E+09 |
June | 0.246172E+09 | 13093671.01 | 0.233079E+09 | 0.280757E+09 | 74145884.07 |
July | 0.246901E+09 | 9636002.91 | 0.237265E+09 | 0.370003E+09 | 21484567.61 |
August | 0.218343E+09 | 2901157.23 | 0.215442E+09 | 0.327023E+09 | 39732256.21 |
September | 0.159103E+09 | 92495.66 | 0.159011E+09 | 0.157940E+09 | 0.119580E+09 |
October | 0.142165E+09 | 0.00 | 0.142165E+09 | 81509869.66 | 0.254397E+09 |
November | 96498654.68 | 0.00 | 96498654.68 | 14827080.86 | 0.409741E+09 |
December | 69226616.93 | 0.00 | 69226616.93 | 532126.47 | 0.575831E+09 |
Annual Sum or Average | 0.192308E+10 | 35273860.71 | 0.188781E+10 | 0.152391E+10 | 0.360957E+10 |
Minimum of Months | 69226616.93 | 0.00 | 69226616.93 | 402889.45 | 21484567.61 |
Maximum of Months | 0.246901E+09 | 13093671.01 | 0.237265E+09 | 0.370003E+09 | 0.640294E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306595E+09 | 0.125866E+09 | 0.180729E+09 | 0.151455E+09 | 0.113187E+10 |
February | 0.406788E+09 | 0.178528E+09 | 0.228260E+09 | 0.225844E+09 | 0.103885E+10 |
March | 0.668971E+09 | 0.310018E+09 | 0.358954E+09 | 0.508848E+09 | 0.745903E+09 |
April | 0.703127E+09 | 0.300478E+09 | 0.402648E+09 | 0.633425E+09 | 0.502092E+09 |
May | 0.848784E+09 | 0.322657E+09 | 0.526127E+09 | 0.895644E+09 | 0.298914E+09 |
June | 0.897447E+09 | 0.362187E+09 | 0.535260E+09 | 0.112152E+10 | 0.141472E+09 |
July | 0.867624E+09 | 0.326043E+09 | 0.541581E+09 | 0.125471E+10 | 40301508.37 |
August | 0.959928E+09 | 0.443831E+09 | 0.516097E+09 | 0.138628E+10 | 75499765.88 |
September | 0.660939E+09 | 0.288548E+09 | 0.372391E+09 | 0.796386E+09 | 0.214067E+09 |
October | 0.677659E+09 | 0.330113E+09 | 0.347546E+09 | 0.694362E+09 | 0.452937E+09 |
November | 0.308834E+09 | 90224391.19 | 0.218610E+09 | 0.168634E+09 | 0.732879E+09 |
December | 0.281882E+09 | 0.121681E+09 | 0.160201E+09 | 0.143494E+09 | 0.101617E+10 |
Annual Sum or Average | 0.758858E+10 | 0.320017E+10 | 0.438840E+10 | 0.798061E+10 | 0.639095E+10 |
Minimum of Months | 0.281882E+09 | 90224391.19 | 0.160201E+09 | 0.143494E+09 | 40301508.37 |
Maximum of Months | 0.959928E+09 | 0.443831E+09 | 0.541581E+09 | 0.138628E+10 | 0.113187E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.605002E+09 | 0.397011E+09 | 0.207991E+09 | 0.496582E+09 | 0.847161E+09 |
February | 0.723176E+09 | 0.480643E+09 | 0.242533E+09 | 0.608318E+09 | 0.763236E+09 |
March | 0.709384E+09 | 0.390508E+09 | 0.318876E+09 | 0.646877E+09 | 0.607102E+09 |
April | 0.546436E+09 | 0.221075E+09 | 0.325361E+09 | 0.530931E+09 | 0.407753E+09 |
May | 0.484966E+09 | 99289786.41 | 0.385677E+09 | 0.522350E+09 | 0.224347E+09 |
June | 0.443156E+09 | 68281033.02 | 0.374875E+09 | 0.603747E+09 | 77773369.97 |
July | 0.476476E+09 | 80419574.17 | 0.396057E+09 | 0.763991E+09 | 17644049.84 |
August | 0.638193E+09 | 0.235424E+09 | 0.402770E+09 | 0.998682E+09 | 44576998.00 |
September | 0.651742E+09 | 0.327231E+09 | 0.324511E+09 | 0.853106E+09 | 0.137451E+09 |
October | 0.951723E+09 | 0.596811E+09 | 0.354912E+09 | 0.110540E+10 | 0.335003E+09 |
November | 0.637747E+09 | 0.382567E+09 | 0.255180E+09 | 0.590201E+09 | 0.564669E+09 |
December | 0.653638E+09 | 0.464248E+09 | 0.189390E+09 | 0.574738E+09 | 0.757517E+09 |
Annual Sum or Average | 0.752164E+10 | 0.374351E+10 | 0.377813E+10 | 0.829492E+10 | 0.478423E+10 |
Minimum of Months | 0.443156E+09 | 68281033.02 | 0.189390E+09 | 0.496582E+09 | 17644049.84 |
Maximum of Months | 0.951723E+09 | 0.596811E+09 | 0.402770E+09 | 0.110540E+10 | 0.847161E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555528E+09 | 0.00 | 0.555528E+09 | 71678.16 | 0.520391E+10 |
February | 0.686647E+09 | 0.00 | 0.686647E+09 | 3969175.62 | 0.480063E+10 |
March | 0.105448E+10 | 21963.65 | 0.105446E+10 | 0.128533E+09 | 0.364958E+10 |
April | 0.122804E+10 | 5060151.99 | 0.122298E+10 | 0.471047E+09 | 0.244034E+10 |
May | 0.168779E+10 | 61769089.72 | 0.162602E+10 | 0.121664E+10 | 0.137098E+10 |
June | 0.172314E+10 | 91652225.77 | 0.163149E+10 | 0.193467E+10 | 0.642585E+09 |
July | 0.172824E+10 | 67449465.79 | 0.166079E+10 | 0.241751E+10 | 0.309477E+09 |
August | 0.152834E+10 | 20307331.48 | 0.150804E+10 | 0.211437E+10 | 0.443809E+09 |
September | 0.111368E+10 | 647445.10 | 0.111303E+10 | 0.103925E+10 | 0.103816E+10 |
October | 0.995119E+09 | 0.00 | 0.995119E+09 | 0.503572E+09 | 0.213052E+10 |
November | 0.675465E+09 | 0.00 | 0.675465E+09 | 60665313.32 | 0.356220E+10 |
December | 0.484568E+09 | 0.00 | 0.484568E+09 | 614439.65 | 0.478326E+10 |
Annual Sum or Average | 0.134610E+11 | 0.246908E+09 | 0.132141E+11 | 0.989092E+10 | 0.303755E+11 |
Minimum of Months | 0.484568E+09 | 0.00 | 0.484568E+09 | 71678.16 | 0.309477E+09 |
Maximum of Months | 0.172824E+10 | 91652225.77 | 0.166079E+10 | 0.241751E+10 | 0.520391E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555528E+09 | 0.00 | 0.555528E+09 | 0.00 | 0.538383E+10 |
February | 0.686647E+09 | 0.00 | 0.686647E+09 | 1886539.95 | 0.495310E+10 |
March | 0.105448E+10 | 21963.65 | 0.105446E+10 | 0.110413E+09 | 0.379355E+10 |
April | 0.122804E+10 | 5060151.99 | 0.122298E+10 | 0.438683E+09 | 0.252353E+10 |
May | 0.168779E+10 | 61769089.72 | 0.162602E+10 | 0.117442E+10 | 0.140946E+10 |
June | 0.172314E+10 | 91652225.77 | 0.163149E+10 | 0.189711E+10 | 0.665197E+09 |
July | 0.172824E+10 | 67449465.79 | 0.166079E+10 | 0.238436E+10 | 0.328567E+09 |
August | 0.152834E+10 | 20307331.48 | 0.150804E+10 | 0.208004E+10 | 0.464436E+09 |
September | 0.111368E+10 | 647445.10 | 0.111303E+10 | 0.100487E+10 | 0.107395E+10 |
October | 0.995119E+09 | 0.00 | 0.995119E+09 | 0.474066E+09 | 0.219497E+10 |
November | 0.675465E+09 | 0.00 | 0.675465E+09 | 52332501.36 | 0.370240E+10 |
December | 0.484568E+09 | 0.00 | 0.484568E+09 | 257780.39 | 0.497792E+10 |
Annual Sum or Average | 0.134610E+11 | 0.246908E+09 | 0.132141E+11 | 0.961845E+10 | 0.314709E+11 |
Minimum of Months | 0.484568E+09 | 0.00 | 0.484568E+09 | 0.00 | 0.328567E+09 |
Maximum of Months | 0.172824E+10 | 91652225.77 | 0.166079E+10 | 0.238436E+10 | 0.538383E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 79364137.35 | 0.00 | 79364137.35 | 0.00 | 0.821571E+09 |
February | 98096151.26 | 0.00 | 98096151.26 | 110067.02 | 0.755456E+09 |
March | 0.150645E+09 | 3137.78 | 0.150642E+09 | 11479040.37 | 0.578783E+09 |
April | 0.175441E+09 | 722906.23 | 0.174718E+09 | 59172504.69 | 0.382984E+09 |
May | 0.241122E+09 | 8824489.88 | 0.232298E+09 | 0.173413E+09 | 0.217159E+09 |
June | 0.246172E+09 | 13093671.01 | 0.233079E+09 | 0.286189E+09 | 0.109436E+09 |
July | 0.246901E+09 | 9636002.91 | 0.237265E+09 | 0.362521E+09 | 59742930.81 |
August | 0.218343E+09 | 2901157.23 | 0.215442E+09 | 0.314215E+09 | 78394144.64 |
September | 0.159103E+09 | 92495.66 | 0.159011E+09 | 0.152239E+09 | 0.165277E+09 |
October | 0.142165E+09 | 0.00 | 0.142165E+09 | 64507224.24 | 0.329920E+09 |
November | 96498654.68 | 0.00 | 96498654.68 | 6044707.32 | 0.566797E+09 |
December | 69226616.93 | 0.00 | 69226616.93 | 6659.92 | 0.758525E+09 |
Annual Sum or Average | 0.192308E+10 | 35273860.71 | 0.188781E+10 | 0.142990E+10 | 0.482404E+10 |
Minimum of Months | 69226616.93 | 0.00 | 69226616.93 | 0.00 | 59742930.81 |
Maximum of Months | 0.246901E+09 | 13093671.01 | 0.237265E+09 | 0.362521E+09 | 0.821571E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.617436E+09 | 0.246686E+09 | 0.370750E+09 | 0.237802E+09 | 0.283298E+10 |
February | 0.865852E+09 | 0.403210E+09 | 0.462642E+09 | 0.405325E+09 | 0.247497E+10 |
March | 0.123102E+10 | 0.523178E+09 | 0.707845E+09 | 0.825770E+09 | 0.200812E+10 |
April | 0.142610E+10 | 0.625935E+09 | 0.800167E+09 | 0.121325E+10 | 0.134603E+10 |
May | 0.177911E+10 | 0.709006E+09 | 0.107011E+10 | 0.187099E+10 | 0.822257E+09 |
June | 0.159875E+10 | 0.579090E+09 | 0.101966E+10 | 0.202762E+10 | 0.420304E+09 |
July | 0.165707E+10 | 0.596575E+09 | 0.106050E+10 | 0.239584E+10 | 0.227299E+09 |
August | 0.186937E+10 | 0.843386E+09 | 0.102598E+10 | 0.266276E+10 | 0.292362E+09 |
September | 0.135326E+10 | 0.609637E+09 | 0.743627E+09 | 0.162165E+10 | 0.593316E+09 |
October | 0.126331E+10 | 0.571843E+09 | 0.691464E+09 | 0.122030E+10 | 0.115560E+10 |
November | 0.757205E+09 | 0.290978E+09 | 0.466227E+09 | 0.422408E+09 | 0.191088E+10 |
December | 0.611725E+09 | 0.288641E+09 | 0.323084E+09 | 0.274818E+09 | 0.257203E+10 |
Annual Sum or Average | 0.150302E+11 | 0.628816E+10 | 0.874206E+10 | 0.151786E+11 | 0.166562E+11 |
Minimum of Months | 0.611725E+09 | 0.246686E+09 | 0.323084E+09 | 0.237802E+09 | 0.227299E+09 |
Maximum of Months | 0.186937E+10 | 0.843386E+09 | 0.107011E+10 | 0.266276E+10 | 0.283298E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.412521E+09 | 0.270702E+09 | 0.141819E+09 | 0.331294E+09 | 0.692661E+09 |
February | 0.493098E+09 | 0.327727E+09 | 0.165371E+09 | 0.409148E+09 | 0.603865E+09 |
March | 0.483694E+09 | 0.266268E+09 | 0.217426E+09 | 0.430879E+09 | 0.515326E+09 |
April | 0.372588E+09 | 0.150740E+09 | 0.221848E+09 | 0.348375E+09 | 0.374034E+09 |
May | 0.330675E+09 | 67700844.96 | 0.262974E+09 | 0.335140E+09 | 0.232414E+09 |
June | 0.302166E+09 | 46557493.95 | 0.255609E+09 | 0.387230E+09 | 0.118309E+09 |
July | 0.324886E+09 | 54834170.96 | 0.270052E+09 | 0.492491E+09 | 62304227.04 |
August | 0.435153E+09 | 0.160524E+09 | 0.274629E+09 | 0.660229E+09 | 80415650.56 |
September | 0.444391E+09 | 0.223123E+09 | 0.221268E+09 | 0.575186E+09 | 0.162040E+09 |
October | 0.648933E+09 | 0.406936E+09 | 0.241997E+09 | 0.752746E+09 | 0.303765E+09 |
November | 0.434849E+09 | 0.260853E+09 | 0.173995E+09 | 0.393747E+09 | 0.479699E+09 |
December | 0.445684E+09 | 0.316548E+09 | 0.129136E+09 | 0.384906E+09 | 0.625869E+09 |
Annual Sum or Average | 0.512864E+10 | 0.255251E+10 | 0.257612E+10 | 0.550137E+10 | 0.425070E+10 |
Minimum of Months | 0.302166E+09 | 46557493.95 | 0.129136E+09 | 0.331294E+09 | 62304227.04 |
Maximum of Months | 0.648933E+09 | 0.406936E+09 | 0.274629E+09 | 0.752746E+09 | 0.692661E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100510E+09 | 0.00 | 0.100510E+09 | 54486.56 | 0.889157E+09 |
February | 0.124233E+09 | 0.00 | 0.124233E+09 | 845924.08 | 0.829068E+09 |
March | 0.190783E+09 | 3973.80 | 0.190779E+09 | 21461273.97 | 0.626193E+09 |
April | 0.222184E+09 | 915515.13 | 0.221269E+09 | 82351384.95 | 0.426648E+09 |
May | 0.305366E+09 | 11175659.64 | 0.294191E+09 | 0.222405E+09 | 0.242794E+09 |
June | 0.311762E+09 | 16582308.17 | 0.295180E+09 | 0.356794E+09 | 0.108590E+09 |
July | 0.312685E+09 | 12203389.69 | 0.300482E+09 | 0.444915E+09 | 48731910.82 |
August | 0.276518E+09 | 3674132.58 | 0.272844E+09 | 0.387750E+09 | 73691632.99 |
September | 0.201494E+09 | 117139.92 | 0.201377E+09 | 0.187053E+09 | 0.181190E+09 |
October | 0.180043E+09 | 0.00 | 0.180043E+09 | 83825290.04 | 0.385413E+09 |
November | 0.122209E+09 | 0.00 | 0.122209E+09 | 8698189.17 | 0.616645E+09 |
December | 87671142.38 | 0.00 | 87671142.38 | 121232.06 | 0.809895E+09 |
Annual Sum or Average | 0.243546E+10 | 44672118.94 | 0.239079E+10 | 0.179627E+10 | 0.523802E+10 |
Minimum of Months | 87671142.38 | 0.00 | 87671142.38 | 54486.56 | 48731910.82 |
Maximum of Months | 0.312685E+09 | 16582308.17 | 0.300482E+09 | 0.444915E+09 | 0.889157E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89926384.68 | 0.00 | 89926384.68 | 48749.33 | 0.795502E+09 |
February | 0.111151E+09 | 0.00 | 0.111151E+09 | 756851.48 | 0.741771E+09 |
March | 0.170694E+09 | 3555.38 | 0.170691E+09 | 19201483.14 | 0.560258E+09 |
April | 0.198789E+09 | 819114.86 | 0.197970E+09 | 73680096.15 | 0.381724E+09 |
May | 0.273212E+09 | 9998905.03 | 0.263213E+09 | 0.198986E+09 | 0.217228E+09 |
June | 0.278935E+09 | 14836253.95 | 0.264098E+09 | 0.319225E+09 | 97155750.63 |
July | 0.279760E+09 | 10918419.00 | 0.268842E+09 | 0.398067E+09 | 43600625.25 |
August | 0.247402E+09 | 3287260.34 | 0.244114E+09 | 0.346922E+09 | 65932183.26 |
September | 0.180278E+09 | 104805.53 | 0.180173E+09 | 0.167357E+09 | 0.162111E+09 |
October | 0.161085E+09 | 0.00 | 0.161085E+09 | 74998804.61 | 0.344831E+09 |
November | 0.109341E+09 | 0.00 | 0.109341E+09 | 7782302.81 | 0.551710E+09 |
December | 78439703.27 | 0.00 | 78439703.27 | 108466.78 | 0.724528E+09 |
Annual Sum or Average | 0.217901E+10 | 39968314.07 | 0.213905E+10 | 0.160713E+10 | 0.468635E+10 |
Minimum of Months | 78439703.27 | 0.00 | 78439703.27 | 48749.33 | 43600625.25 |
Maximum of Months | 0.279760E+09 | 14836253.95 | 0.268842E+09 | 0.398067E+09 | 0.795502E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.154006E+10 | 0.101061E+10 | 0.529453E+09 | 0.130545E+10 | 0.221680E+10 |
February | 0.184088E+10 | 0.122350E+10 | 0.617381E+09 | 0.160344E+10 | 0.197496E+10 |
March | 0.180577E+10 | 0.994058E+09 | 0.811716E+09 | 0.166593E+10 | 0.167622E+10 |
April | 0.139098E+10 | 0.562758E+09 | 0.828224E+09 | 0.131862E+10 | 0.123961E+10 |
May | 0.123451E+10 | 0.252747E+09 | 0.981760E+09 | 0.124914E+10 | 0.774947E+09 |
June | 0.112808E+10 | 0.173813E+09 | 0.954264E+09 | 0.143075E+10 | 0.347585E+09 |
July | 0.121290E+10 | 0.204712E+09 | 0.100818E+10 | 0.180233E+10 | 0.149938E+09 |
August | 0.162456E+10 | 0.599284E+09 | 0.102527E+10 | 0.242211E+10 | 0.225325E+09 |
September | 0.165904E+10 | 0.832984E+09 | 0.826061E+09 | 0.211253E+10 | 0.524217E+09 |
October | 0.242266E+10 | 0.151922E+10 | 0.903447E+09 | 0.279506E+10 | 0.104534E+10 |
November | 0.162342E+10 | 0.973844E+09 | 0.649575E+09 | 0.151307E+10 | 0.156134E+10 |
December | 0.166387E+10 | 0.118177E+10 | 0.482103E+09 | 0.150947E+10 | 0.197907E+10 |
Annual Sum or Average | 0.191467E+11 | 0.952930E+10 | 0.961744E+10 | 0.207279E+11 | 0.137154E+11 |
Minimum of Months | 0.112808E+10 | 0.173813E+09 | 0.482103E+09 | 0.124914E+10 | 0.149938E+09 |
Maximum of Months | 0.242266E+10 | 0.151922E+10 | 0.102527E+10 | 0.279506E+10 | 0.221680E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 592.43 | 880.23 | 678.19 | 445.04 | 233.15 | 0.00 | 0.00 |
February | 801.28 | 874.87 | 897.52 | 596.52 | 301.00 | 0.00 | 0.00 |
March | 761.77 | 634.48 | 795.20 | 437.75 | 357.45 | 0.00 | 0.00 |
April | 639.85 | 456.09 | 632.96 | 256.08 | 376.88 | 0.00 | 0.00 |
May | 592.06 | 268.73 | 543.64 | 111.30 | 432.33 | 0.00 | 0.00 |
June | 665.56 | 137.52 | 513.33 | 79.09 | 434.23 | 0.00 | 0.00 |
July | 789.55 | 64.44 | 534.12 | 90.15 | 443.97 | 0.00 | 0.00 |
August | 1059.01 | 97.15 | 715.40 | 263.90 | 451.50 | 0.00 | 0.00 |
September | 975.86 | 206.17 | 754.94 | 379.05 | 375.90 | 0.00 | 0.00 |
October | 1257.92 | 397.42 | 1066.86 | 669.01 | 397.85 | 0.00 | 0.00 |
November | 714.56 | 612.91 | 738.73 | 443.14 | 295.59 | 0.00 | 0.00 |
December | 677.57 | 791.28 | 732.71 | 520.41 | 212.30 | 0.00 | 0.00 |
Annual Sum or Average | 794.38 | 449.38 | 716.11 | 356.41 | 359.70 | 0.00 | 0.00 |
Minimum of Months | 592.06 | 64.44 | 513.33 | 79.09 | 212.30 | 0.00 | 0.00 |
Maximum of Months | 1257.92 | 880.23 | 1066.86 | 669.01 | 451.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1668.32 | 2509.81 | 1909.75 | 1253.20 | 656.54 | 0.00 | 0.00 |
February | 2259.22 | 2482.31 | 2527.36 | 1679.75 | 847.60 | 0.00 | 0.00 |
March | 2136.90 | 1820.31 | 2239.24 | 1232.67 | 1006.56 | 0.00 | 0.00 |
April | 1761.46 | 1364.42 | 1782.37 | 721.11 | 1061.27 | 0.00 | 0.00 |
May | 1584.90 | 880.23 | 1530.84 | 313.42 | 1217.42 | 0.00 | 0.00 |
June | 1817.97 | 441.25 | 1445.49 | 222.72 | 1222.77 | 0.00 | 0.00 |
July | 2186.81 | 208.44 | 1504.04 | 253.85 | 1250.19 | 0.00 | 0.00 |
August | 2945.79 | 305.45 | 2014.52 | 743.14 | 1271.38 | 0.00 | 0.00 |
September | 2692.93 | 667.35 | 2125.86 | 1067.37 | 1058.50 | 0.00 | 0.00 |
October | 3497.68 | 1211.08 | 3004.20 | 1883.89 | 1120.31 | 0.00 | 0.00 |
November | 1990.27 | 1797.37 | 2080.21 | 1247.86 | 832.35 | 0.00 | 0.00 |
December | 1907.91 | 2255.23 | 2063.27 | 1465.44 | 597.83 | 0.00 | 0.00 |
Annual Sum or Average | 2205.25 | 1321.98 | 2016.51 | 1003.61 | 1012.90 | 0.00 | 0.00 |
Minimum of Months | 1584.90 | 208.44 | 1445.49 | 222.72 | 597.83 | 0.00 | 0.00 |
Maximum of Months | 3497.68 | 2509.81 | 3004.20 | 1883.89 | 1271.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2189.01 | 3507.90 | 2480.87 | 1627.98 | 852.89 | 0.00 | 0.00 |
February | 2972.39 | 3463.91 | 3283.18 | 2182.09 | 1101.09 | 0.00 | 0.00 |
March | 2832.48 | 2586.92 | 2908.90 | 1601.31 | 1307.58 | 0.00 | 0.00 |
April | 2369.20 | 1912.53 | 2315.40 | 936.76 | 1378.65 | 0.00 | 0.00 |
May | 2180.20 | 1157.29 | 1988.65 | 407.15 | 1581.50 | 0.00 | 0.00 |
June | 2487.44 | 571.98 | 1877.78 | 289.33 | 1588.45 | 0.00 | 0.00 |
July | 2966.25 | 262.51 | 1953.84 | 329.77 | 1624.07 | 0.00 | 0.00 |
August | 3967.46 | 388.89 | 2616.97 | 965.38 | 1651.60 | 0.00 | 0.00 |
September | 3625.25 | 861.18 | 2761.62 | 1386.57 | 1375.05 | 0.00 | 0.00 |
October | 4667.59 | 1630.67 | 3902.63 | 2447.28 | 1455.35 | 0.00 | 0.00 |
November | 2624.85 | 2533.24 | 2702.32 | 1621.04 | 1081.27 | 0.00 | 0.00 |
December | 2500.16 | 3194.35 | 2680.31 | 1903.69 | 776.61 | 0.00 | 0.00 |
Annual Sum or Average | 2950.21 | 1829.98 | 2619.56 | 1303.75 | 1315.81 | 0.00 | 0.00 |
Minimum of Months | 2180.20 | 262.51 | 1877.78 | 289.33 | 776.61 | 0.00 | 0.00 |
Maximum of Months | 4667.59 | 3507.90 | 3902.63 | 2447.28 | 1651.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 157.63 | 619.31 | 268.49 | 148.06 | 120.43 | 0.00 | 0.00 |
February | 229.17 | 618.28 | 371.98 | 209.27 | 162.71 | 0.00 | 0.00 |
March | 339.70 | 432.71 | 430.36 | 215.16 | 215.20 | 0.00 | 0.00 |
April | 382.72 | 303.65 | 415.01 | 174.08 | 240.93 | 0.00 | 0.00 |
May | 478.15 | 162.75 | 440.36 | 145.74 | 294.62 | 0.00 | 0.00 |
June | 612.16 | 63.03 | 462.81 | 157.69 | 305.12 | 0.00 | 0.00 |
July | 672.83 | 16.16 | 445.23 | 142.20 | 303.03 | 0.00 | 0.00 |
August | 777.95 | 36.61 | 520.86 | 225.64 | 295.22 | 0.00 | 0.00 |
September | 541.45 | 107.82 | 426.44 | 197.40 | 229.04 | 0.00 | 0.00 |
October | 540.91 | 248.73 | 495.29 | 275.18 | 220.11 | 0.00 | 0.00 |
November | 202.16 | 430.63 | 286.91 | 135.45 | 151.47 | 0.00 | 0.00 |
December | 170.51 | 558.51 | 271.64 | 163.62 | 108.03 | 0.00 | 0.00 |
Annual Sum or Average | 426.96 | 298.04 | 403.26 | 182.42 | 220.84 | 0.00 | 0.00 |
Minimum of Months | 157.63 | 16.16 | 268.49 | 135.45 | 108.03 | 0.00 | 0.00 |
Maximum of Months | 777.95 | 619.31 | 520.86 | 275.18 | 305.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 45.29 | 661.59 | 144.10 | 46.99 | 97.11 | 0.00 | 0.00 |
February | 78.96 | 673.87 | 208.70 | 73.80 | 134.90 | 0.00 | 0.00 |
March | 186.82 | 443.89 | 306.01 | 115.75 | 190.26 | 0.00 | 0.00 |
April | 271.40 | 307.98 | 338.95 | 116.20 | 222.75 | 0.00 | 0.00 |
May | 407.75 | 170.81 | 406.92 | 123.76 | 283.16 | 0.00 | 0.00 |
June | 550.04 | 80.97 | 441.21 | 144.78 | 296.43 | 0.00 | 0.00 |
July | 614.31 | 23.30 | 416.12 | 125.33 | 290.79 | 0.00 | 0.00 |
August | 646.11 | 44.06 | 439.92 | 166.79 | 273.13 | 0.00 | 0.00 |
September | 371.20 | 128.97 | 316.37 | 111.36 | 205.02 | 0.00 | 0.00 |
October | 286.33 | 267.00 | 306.09 | 123.25 | 182.84 | 0.00 | 0.00 |
November | 61.95 | 454.00 | 156.38 | 34.81 | 121.57 | 0.00 | 0.00 |
December | 41.12 | 601.13 | 131.09 | 45.43 | 85.66 | 0.00 | 0.00 |
Annual Sum or Average | 298.38 | 319.43 | 301.61 | 102.60 | 199.02 | 0.00 | 0.00 |
Minimum of Months | 41.12 | 23.30 | 131.09 | 34.81 | 85.66 | 0.00 | 0.00 |
Maximum of Months | 646.11 | 673.87 | 441.21 | 166.79 | 296.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 99.25 | 193.50 | 123.19 | 80.84 | 42.35 | 0.00 | 0.00 |
February | 130.00 | 208.12 | 163.03 | 108.35 | 54.68 | 0.00 | 0.00 |
March | 123.04 | 165.92 | 144.44 | 79.51 | 64.93 | 0.00 | 0.00 |
April | 100.22 | 127.11 | 114.97 | 46.52 | 68.46 | 0.00 | 0.00 |
May | 89.86 | 80.29 | 98.75 | 20.22 | 78.53 | 0.00 | 0.00 |
June | 105.12 | 43.22 | 93.24 | 14.37 | 78.88 | 0.00 | 0.00 |
July | 129.69 | 24.61 | 97.02 | 16.37 | 80.64 | 0.00 | 0.00 |
August | 179.38 | 31.69 | 129.95 | 47.94 | 82.01 | 0.00 | 0.00 |
September | 163.21 | 61.40 | 137.13 | 68.85 | 68.28 | 0.00 | 0.00 |
October | 211.94 | 105.30 | 193.79 | 121.52 | 72.27 | 0.00 | 0.00 |
November | 114.10 | 161.70 | 134.19 | 80.49 | 53.69 | 0.00 | 0.00 |
December | 109.98 | 193.16 | 133.09 | 94.53 | 38.56 | 0.00 | 0.00 |
Annual Sum or Average | 129.74 | 115.78 | 130.08 | 64.74 | 65.34 | 0.00 | 0.00 |
Minimum of Months | 89.86 | 24.61 | 93.24 | 14.37 | 38.56 | 0.00 | 0.00 |
Maximum of Months | 211.94 | 208.12 | 193.79 | 121.52 | 82.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.02 | 204.61 | 23.71 | 0.00 | 23.71 | 0.00 | 0.00 |
February | 0.50 | 209.16 | 32.44 | 0.00 | 32.44 | 0.00 | 0.00 |
March | 7.86 | 135.74 | 45.00 | 0.00 | 45.00 | 0.00 | 0.00 |
April | 26.32 | 88.89 | 54.16 | 0.22 | 53.93 | 0.00 | 0.00 |
May | 62.15 | 45.54 | 72.03 | 2.64 | 69.39 | 0.00 | 0.00 |
June | 96.18 | 20.03 | 75.99 | 4.04 | 71.95 | 0.00 | 0.00 |
July | 119.06 | 5.54 | 73.76 | 2.88 | 70.88 | 0.00 | 0.00 |
August | 106.34 | 10.64 | 65.22 | 0.87 | 64.36 | 0.00 | 0.00 |
September | 53.55 | 34.44 | 49.11 | 0.03 | 49.08 | 0.00 | 0.00 |
October | 26.53 | 74.84 | 42.47 | 0.00 | 42.47 | 0.00 | 0.00 |
November | 4.25 | 136.96 | 29.79 | 0.00 | 29.79 | 0.00 | 0.00 |
December | 0.07 | 185.82 | 20.68 | 0.00 | 20.68 | 0.00 | 0.00 |
Annual Sum or Average | 42.21 | 95.37 | 48.79 | 0.89 | 47.90 | 0.00 | 0.00 |
Minimum of Months | 0.02 | 5.54 | 20.68 | 0.00 | 20.68 | 0.00 | 0.00 |
Maximum of Months | 119.06 | 209.16 | 75.99 | 4.04 | 71.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 157.21 | 613.85 | 269.29 | 147.12 | 122.17 | 0.00 | 0.00 |
February | 239.07 | 608.19 | 382.79 | 218.81 | 163.98 | 0.00 | 0.00 |
March | 320.35 | 437.13 | 410.41 | 197.09 | 213.33 | 0.00 | 0.00 |
April | 381.86 | 295.90 | 418.86 | 178.91 | 239.95 | 0.00 | 0.00 |
May | 494.86 | 158.28 | 455.61 | 157.64 | 297.96 | 0.00 | 0.00 |
June | 562.75 | 60.14 | 425.00 | 129.68 | 295.32 | 0.00 | 0.00 |
July | 655.50 | 15.14 | 430.66 | 131.85 | 298.81 | 0.00 | 0.00 |
August | 763.77 | 34.16 | 511.46 | 217.39 | 294.08 | 0.00 | 0.00 |
September | 546.20 | 103.67 | 432.51 | 203.69 | 228.82 | 0.00 | 0.00 |
October | 517.73 | 243.24 | 478.13 | 258.69 | 219.44 | 0.00 | 0.00 |
November | 237.09 | 425.41 | 313.84 | 156.77 | 157.07 | 0.00 | 0.00 |
December | 182.87 | 552.72 | 280.60 | 172.07 | 108.53 | 0.00 | 0.00 |
Annual Sum or Average | 422.99 | 293.90 | 400.95 | 180.64 | 220.30 | 0.00 | 0.00 |
Minimum of Months | 157.21 | 15.14 | 269.29 | 129.68 | 108.53 | 0.00 | 0.00 |
Maximum of Months | 763.77 | 613.85 | 511.46 | 258.69 | 298.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 38.82 | 649.59 | 144.90 | 46.05 | 98.85 | 0.00 | 0.00 |
February | 73.26 | 646.61 | 219.52 | 83.34 | 136.17 | 0.00 | 0.00 |
March | 164.89 | 445.95 | 286.07 | 97.67 | 188.39 | 0.00 | 0.00 |
April | 270.72 | 297.76 | 342.80 | 121.03 | 221.77 | 0.00 | 0.00 |
May | 428.66 | 165.54 | 422.17 | 135.66 | 286.51 | 0.00 | 0.00 |
June | 503.54 | 76.17 | 403.40 | 116.77 | 286.63 | 0.00 | 0.00 |
July | 594.71 | 22.19 | 401.54 | 114.97 | 286.57 | 0.00 | 0.00 |
August | 628.08 | 41.01 | 430.52 | 158.54 | 271.98 | 0.00 | 0.00 |
September | 375.22 | 120.68 | 322.45 | 117.64 | 204.80 | 0.00 | 0.00 |
October | 263.13 | 255.12 | 288.93 | 106.76 | 182.17 | 0.00 | 0.00 |
November | 87.10 | 439.59 | 183.31 | 56.13 | 127.17 | 0.00 | 0.00 |
December | 44.83 | 585.67 | 140.05 | 53.89 | 86.16 | 0.00 | 0.00 |
Annual Sum or Average | 290.98 | 310.27 | 299.30 | 100.82 | 198.48 | 0.00 | 0.00 |
Minimum of Months | 38.82 | 22.19 | 140.05 | 46.05 | 86.16 | 0.00 | 0.00 |
Maximum of Months | 628.08 | 649.59 | 430.52 | 158.54 | 286.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 177.26 | 827.11 | 318.28 | 175.16 | 143.12 | 0.00 | 0.00 |
February | 241.51 | 846.46 | 423.52 | 234.77 | 188.75 | 0.00 | 0.00 |
March | 279.16 | 647.07 | 410.46 | 172.29 | 238.17 | 0.00 | 0.00 |
April | 283.16 | 463.25 | 366.43 | 101.27 | 265.16 | 0.00 | 0.00 |
May | 343.41 | 251.81 | 370.00 | 49.52 | 320.48 | 0.00 | 0.00 |
June | 462.29 | 112.08 | 366.65 | 39.88 | 326.76 | 0.00 | 0.00 |
July | 561.04 | 44.47 | 369.99 | 41.72 | 328.28 | 0.00 | 0.00 |
August | 639.45 | 71.64 | 422.86 | 105.74 | 317.12 | 0.00 | 0.00 |
September | 491.91 | 183.38 | 403.52 | 149.24 | 254.27 | 0.00 | 0.00 |
October | 529.45 | 371.45 | 511.89 | 263.30 | 248.58 | 0.00 | 0.00 |
November | 242.62 | 624.14 | 355.27 | 174.41 | 180.86 | 0.00 | 0.00 |
December | 201.00 | 782.13 | 333.17 | 204.82 | 128.36 | 0.00 | 0.00 |
Annual Sum or Average | 372.10 | 433.02 | 387.54 | 142.21 | 245.33 | 0.00 | 0.00 |
Minimum of Months | 177.26 | 44.47 | 318.28 | 39.88 | 128.36 | 0.00 | 0.00 |
Maximum of Months | 639.45 | 846.46 | 511.89 | 263.30 | 328.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.47 | 609.12 | 268.49 | 148.06 | 120.43 | 0.00 | 0.00 |
February | 229.83 | 608.02 | 371.98 | 209.27 | 162.71 | 0.00 | 0.00 |
March | 338.77 | 420.09 | 430.36 | 215.16 | 215.20 | 0.00 | 0.00 |
April | 379.79 | 293.25 | 415.01 | 174.08 | 240.93 | 0.00 | 0.00 |
May | 472.15 | 157.84 | 440.36 | 145.74 | 294.62 | 0.00 | 0.00 |
June | 603.28 | 60.65 | 462.81 | 157.69 | 305.12 | 0.00 | 0.00 |
July | 664.54 | 14.75 | 445.23 | 142.20 | 303.03 | 0.00 | 0.00 |
August | 769.73 | 34.40 | 520.86 | 225.64 | 295.22 | 0.00 | 0.00 |
September | 535.83 | 103.38 | 426.44 | 197.40 | 229.04 | 0.00 | 0.00 |
October | 536.60 | 241.10 | 495.29 | 275.18 | 220.11 | 0.00 | 0.00 |
November | 205.21 | 414.69 | 286.91 | 135.45 | 151.47 | 0.00 | 0.00 |
December | 173.97 | 543.75 | 271.64 | 163.62 | 108.03 | 0.00 | 0.00 |
Annual Sum or Average | 423.83 | 289.96 | 403.26 | 182.42 | 220.84 | 0.00 | 0.00 |
Minimum of Months | 158.47 | 14.75 | 268.49 | 135.45 | 108.03 | 0.00 | 0.00 |
Maximum of Months | 769.73 | 609.12 | 520.86 | 275.18 | 305.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 46.49 | 651.44 | 144.10 | 46.99 | 97.11 | 0.00 | 0.00 |
February | 80.31 | 664.07 | 208.70 | 73.80 | 134.90 | 0.00 | 0.00 |
March | 188.17 | 429.63 | 306.01 | 115.75 | 190.26 | 0.00 | 0.00 |
April | 270.07 | 297.58 | 338.95 | 116.20 | 222.75 | 0.00 | 0.00 |
May | 401.41 | 168.13 | 406.92 | 123.76 | 283.16 | 0.00 | 0.00 |
June | 540.06 | 82.24 | 441.21 | 144.78 | 296.43 | 0.00 | 0.00 |
July | 606.43 | 22.90 | 416.12 | 125.33 | 290.79 | 0.00 | 0.00 |
August | 639.44 | 42.79 | 439.92 | 166.79 | 273.13 | 0.00 | 0.00 |
September | 366.40 | 126.94 | 316.37 | 111.36 | 205.02 | 0.00 | 0.00 |
October | 284.93 | 259.34 | 306.09 | 123.25 | 182.84 | 0.00 | 0.00 |
November | 65.37 | 435.42 | 156.38 | 34.81 | 121.57 | 0.00 | 0.00 |
December | 43.86 | 584.47 | 131.09 | 45.43 | 85.66 | 0.00 | 0.00 |
Annual Sum or Average | 296.00 | 311.72 | 301.61 | 102.60 | 199.02 | 0.00 | 0.00 |
Minimum of Months | 43.86 | 22.90 | 131.09 | 34.81 | 85.66 | 0.00 | 0.00 |
Maximum of Months | 639.44 | 664.07 | 441.21 | 166.79 | 296.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.40 | 316.29 | 225.88 | 148.23 | 77.66 | 0.00 | 0.00 |
February | 251.45 | 315.49 | 298.93 | 198.68 | 100.25 | 0.00 | 0.00 |
March | 241.52 | 226.67 | 264.85 | 145.80 | 119.05 | 0.00 | 0.00 |
April | 204.83 | 157.31 | 210.82 | 85.29 | 125.53 | 0.00 | 0.00 |
May | 195.02 | 83.76 | 181.07 | 37.07 | 144.00 | 0.00 | 0.00 |
June | 232.93 | 30.01 | 170.97 | 26.34 | 144.63 | 0.00 | 0.00 |
July | 285.24 | 6.59 | 177.90 | 30.03 | 147.87 | 0.00 | 0.00 |
August | 372.87 | 16.64 | 238.27 | 87.90 | 150.38 | 0.00 | 0.00 |
September | 329.13 | 53.03 | 251.44 | 126.25 | 125.20 | 0.00 | 0.00 |
October | 412.71 | 125.08 | 355.33 | 222.82 | 132.51 | 0.00 | 0.00 |
November | 227.70 | 217.85 | 246.04 | 147.60 | 98.45 | 0.00 | 0.00 |
December | 214.58 | 282.82 | 244.04 | 173.33 | 70.71 | 0.00 | 0.00 |
Annual Sum or Average | 263.03 | 151.71 | 238.51 | 118.71 | 119.80 | 0.00 | 0.00 |
Minimum of Months | 185.40 | 6.59 | 170.97 | 26.34 | 70.71 | 0.00 | 0.00 |
Maximum of Months | 412.71 | 316.29 | 355.33 | 222.82 | 150.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.03 | 1942.92 | 207.41 | 0.00 | 207.41 | 0.00 | 0.00 |
February | 1.64 | 1984.39 | 283.83 | 0.00 | 283.83 | 0.00 | 0.00 |
March | 47.99 | 1362.60 | 393.70 | 0.01 | 393.69 | 0.00 | 0.00 |
April | 181.73 | 941.49 | 473.78 | 1.95 | 471.83 | 0.00 | 0.00 |
May | 454.24 | 511.86 | 630.15 | 23.06 | 607.09 | 0.00 | 0.00 |
June | 746.40 | 247.91 | 664.79 | 35.36 | 629.43 | 0.00 | 0.00 |
July | 902.59 | 115.55 | 645.25 | 25.18 | 620.07 | 0.00 | 0.00 |
August | 789.42 | 165.70 | 570.62 | 7.58 | 563.04 | 0.00 | 0.00 |
September | 400.95 | 400.53 | 429.66 | 0.25 | 429.41 | 0.00 | 0.00 |
October | 188.01 | 795.45 | 371.53 | 0.00 | 371.53 | 0.00 | 0.00 |
November | 23.40 | 1374.30 | 260.60 | 0.00 | 260.60 | 0.00 | 0.00 |
December | 0.23 | 1785.86 | 180.92 | 0.00 | 180.92 | 0.00 | 0.00 |
Annual Sum or Average | 313.64 | 963.20 | 426.85 | 7.83 | 419.02 | 0.00 | 0.00 |
Minimum of Months | 0.03 | 115.55 | 180.92 | 0.00 | 180.92 | 0.00 | 0.00 |
Maximum of Months | 902.59 | 1984.39 | 664.79 | 35.36 | 629.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2010.09 | 207.41 | 0.00 | 207.41 | 0.00 | 0.00 |
February | 0.78 | 2047.41 | 283.83 | 0.00 | 283.83 | 0.00 | 0.00 |
March | 41.22 | 1416.35 | 393.70 | 0.01 | 393.69 | 0.00 | 0.00 |
April | 169.24 | 973.58 | 473.78 | 1.95 | 471.83 | 0.00 | 0.00 |
May | 438.48 | 526.23 | 630.15 | 23.06 | 607.09 | 0.00 | 0.00 |
June | 731.91 | 256.63 | 664.79 | 35.36 | 629.43 | 0.00 | 0.00 |
July | 890.22 | 122.67 | 645.25 | 25.18 | 620.07 | 0.00 | 0.00 |
August | 776.60 | 173.40 | 570.62 | 7.58 | 563.04 | 0.00 | 0.00 |
September | 387.68 | 414.33 | 429.66 | 0.25 | 429.41 | 0.00 | 0.00 |
October | 177.00 | 819.51 | 371.53 | 0.00 | 371.53 | 0.00 | 0.00 |
November | 20.19 | 1428.39 | 260.60 | 0.00 | 260.60 | 0.00 | 0.00 |
December | 0.10 | 1858.54 | 180.92 | 0.00 | 180.92 | 0.00 | 0.00 |
Annual Sum or Average | 305.00 | 997.94 | 426.85 | 7.83 | 419.02 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 122.67 | 180.92 | 0.00 | 180.92 | 0.00 | 0.00 |
Maximum of Months | 890.22 | 2047.41 | 664.79 | 35.36 | 629.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 139.53 | 1550.12 | 414.17 | 193.17 | 221.00 | 0.00 | 0.00 |
February | 238.84 | 1487.07 | 602.28 | 302.14 | 300.14 | 0.00 | 0.00 |
March | 433.60 | 1118.38 | 696.45 | 294.75 | 401.70 | 0.00 | 0.00 |
April | 609.54 | 795.60 | 761.62 | 299.92 | 461.70 | 0.00 | 0.00 |
May | 881.70 | 468.12 | 877.73 | 293.28 | 584.45 | 0.00 | 0.00 |
June | 1039.39 | 247.34 | 828.35 | 246.43 | 581.92 | 0.00 | 0.00 |
July | 1212.85 | 129.55 | 832.16 | 246.81 | 585.36 | 0.00 | 0.00 |
August | 1356.57 | 167.04 | 941.93 | 375.90 | 566.03 | 0.00 | 0.00 |
September | 901.84 | 350.74 | 754.92 | 321.32 | 433.61 | 0.00 | 0.00 |
October | 746.41 | 653.72 | 767.03 | 365.43 | 401.59 | 0.00 | 0.00 |
November | 276.72 | 1100.48 | 497.13 | 212.90 | 284.23 | 0.00 | 0.00 |
December | 171.16 | 1402.00 | 420.64 | 225.95 | 194.69 | 0.00 | 0.00 |
Annual Sum or Average | 670.44 | 785.26 | 700.21 | 281.45 | 418.76 | 0.00 | 0.00 |
Minimum of Months | 139.53 | 129.55 | 414.17 | 193.17 | 194.69 | 0.00 | 0.00 |
Maximum of Months | 1356.57 | 1550.12 | 941.93 | 375.90 | 585.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 417.02 | 1386.22 | 646.10 | 377.32 | 268.78 | 0.00 | 0.00 |
February | 575.72 | 1377.95 | 858.25 | 505.75 | 352.50 | 0.00 | 0.00 |
March | 613.82 | 1045.45 | 809.16 | 371.14 | 438.02 | 0.00 | 0.00 |
April | 564.93 | 786.13 | 699.06 | 217.78 | 481.27 | 0.00 | 0.00 |
May | 619.80 | 457.18 | 676.93 | 102.27 | 574.66 | 0.00 | 0.00 |
June | 809.24 | 209.91 | 663.11 | 79.18 | 583.93 | 0.00 | 0.00 |
July | 986.37 | 89.17 | 674.04 | 85.06 | 588.97 | 0.00 | 0.00 |
August | 1178.08 | 135.73 | 802.15 | 226.35 | 575.80 | 0.00 | 0.00 |
September | 950.41 | 333.35 | 787.35 | 321.45 | 465.90 | 0.00 | 0.00 |
October | 1088.86 | 648.93 | 1031.88 | 567.21 | 464.67 | 0.00 | 0.00 |
November | 548.32 | 1011.34 | 715.65 | 375.71 | 339.94 | 0.00 | 0.00 |
December | 490.10 | 1238.23 | 683.24 | 441.22 | 242.02 | 0.00 | 0.00 |
Annual Sum or Average | 738.42 | 722.83 | 753.46 | 304.86 | 448.61 | 0.00 | 0.00 |
Minimum of Months | 417.02 | 89.17 | 646.10 | 79.18 | 242.02 | 0.00 | 0.00 |
Maximum of Months | 1178.08 | 1386.22 | 1031.88 | 567.21 | 588.97 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.158676E+10 | 0.235761E+10 | 0.181647E+10 | 0.119199E+10 | 0.624478E+09 | 0.00 | 0.00 |
February | 0.193846E+10 | 0.211648E+10 | 0.217128E+10 | 0.144309E+10 | 0.728187E+09 | 0.00 | 0.00 |
March | 0.204032E+10 | 0.169938E+10 | 0.212987E+10 | 0.117247E+10 | 0.957401E+09 | 0.00 | 0.00 |
April | 0.165848E+10 | 0.118219E+10 | 0.164063E+10 | 0.663760E+09 | 0.976872E+09 | 0.00 | 0.00 |
May | 0.158578E+10 | 0.719779E+09 | 0.145607E+10 | 0.298110E+09 | 0.115796E+10 | 0.00 | 0.00 |
June | 0.172513E+10 | 0.356453E+09 | 0.133054E+10 | 0.205009E+09 | 0.112553E+10 | 0.00 | 0.00 |
July | 0.211472E+10 | 0.172594E+09 | 0.143058E+10 | 0.241454E+09 | 0.118913E+10 | 0.00 | 0.00 |
August | 0.283644E+10 | 0.260208E+09 | 0.191613E+10 | 0.706842E+09 | 0.120928E+10 | 0.00 | 0.00 |
September | 0.252943E+10 | 0.534380E+09 | 0.195681E+10 | 0.982486E+09 | 0.974320E+09 | 0.00 | 0.00 |
October | 0.336921E+10 | 0.106444E+10 | 0.285748E+10 | 0.179188E+10 | 0.106559E+10 | 0.00 | 0.00 |
November | 0.185213E+10 | 0.158867E+10 | 0.191479E+10 | 0.114863E+10 | 0.766160E+09 | 0.00 | 0.00 |
December | 0.181480E+10 | 0.211936E+10 | 0.196250E+10 | 0.139387E+10 | 0.568630E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.250517E+11 | 0.141715E+11 | 0.225831E+11 | 0.112396E+11 | 0.113436E+11 | 0.00 | 0.00 |
Minimum of Months | 0.158578E+10 | 0.172594E+09 | 0.133054E+10 | 0.205009E+09 | 0.568630E+09 | 0.00 | 0.00 |
Maximum of Months | 0.336921E+10 | 0.235761E+10 | 0.285748E+10 | 0.179188E+10 | 0.120928E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.446843E+10 | 0.672227E+10 | 0.511507E+10 | 0.335658E+10 | 0.175849E+10 | 0.00 | 0.00 |
February | 0.546551E+10 | 0.600520E+10 | 0.611418E+10 | 0.406366E+10 | 0.205053E+10 | 0.00 | 0.00 |
March | 0.572347E+10 | 0.487552E+10 | 0.599757E+10 | 0.330160E+10 | 0.269598E+10 | 0.00 | 0.00 |
April | 0.456570E+10 | 0.353658E+10 | 0.461991E+10 | 0.186910E+10 | 0.275081E+10 | 0.00 | 0.00 |
May | 0.424500E+10 | 0.235762E+10 | 0.410021E+10 | 0.839458E+09 | 0.326075E+10 | 0.00 | 0.00 |
June | 0.471219E+10 | 0.114371E+10 | 0.374672E+10 | 0.577290E+09 | 0.316943E+10 | 0.00 | 0.00 |
July | 0.585714E+10 | 0.558280E+09 | 0.402843E+10 | 0.679917E+09 | 0.334851E+10 | 0.00 | 0.00 |
August | 0.789000E+10 | 0.818127E+09 | 0.539569E+10 | 0.199042E+10 | 0.340527E+10 | 0.00 | 0.00 |
September | 0.698006E+10 | 0.172976E+10 | 0.551024E+10 | 0.276662E+10 | 0.274362E+10 | 0.00 | 0.00 |
October | 0.936819E+10 | 0.324375E+10 | 0.804646E+10 | 0.504582E+10 | 0.300065E+10 | 0.00 | 0.00 |
November | 0.515878E+10 | 0.465878E+10 | 0.539191E+10 | 0.323446E+10 | 0.215746E+10 | 0.00 | 0.00 |
December | 0.511014E+10 | 0.604041E+10 | 0.552626E+10 | 0.392504E+10 | 0.160122E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.695446E+11 | 0.416900E+11 | 0.635926E+11 | 0.316499E+11 | 0.319427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.424500E+10 | 0.558280E+09 | 0.374672E+10 | 0.577290E+09 | 0.160122E+10 | 0.00 | 0.00 |
Maximum of Months | 0.936819E+10 | 0.672227E+10 | 0.804646E+10 | 0.504582E+10 | 0.340527E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.586306E+10 | 0.939557E+10 | 0.664476E+10 | 0.436038E+10 | 0.228438E+10 | 0.00 | 0.00 |
February | 0.719080E+10 | 0.837990E+10 | 0.794267E+10 | 0.527892E+10 | 0.266375E+10 | 0.00 | 0.00 |
March | 0.758652E+10 | 0.692880E+10 | 0.779119E+10 | 0.428896E+10 | 0.350223E+10 | 0.00 | 0.00 |
April | 0.614097E+10 | 0.495728E+10 | 0.600153E+10 | 0.242807E+10 | 0.357345E+10 | 0.00 | 0.00 |
May | 0.583945E+10 | 0.309970E+10 | 0.532640E+10 | 0.109050E+10 | 0.423590E+10 | 0.00 | 0.00 |
June | 0.644744E+10 | 0.148258E+10 | 0.486720E+10 | 0.749933E+09 | 0.411726E+10 | 0.00 | 0.00 |
July | 0.794480E+10 | 0.703115E+09 | 0.523316E+10 | 0.883251E+09 | 0.434990E+10 | 0.00 | 0.00 |
August | 0.106264E+11 | 0.104161E+10 | 0.700930E+10 | 0.258567E+10 | 0.442363E+10 | 0.00 | 0.00 |
September | 0.939666E+10 | 0.223217E+10 | 0.715811E+10 | 0.359399E+10 | 0.356412E+10 | 0.00 | 0.00 |
October | 0.125017E+11 | 0.436757E+10 | 0.104528E+11 | 0.655480E+10 | 0.389801E+10 | 0.00 | 0.00 |
November | 0.680362E+10 | 0.656615E+10 | 0.700440E+10 | 0.420174E+10 | 0.280266E+10 | 0.00 | 0.00 |
December | 0.669643E+10 | 0.855576E+10 | 0.717893E+10 | 0.509885E+10 | 0.208008E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.930379E+11 | 0.577102E+11 | 0.826105E+11 | 0.411151E+11 | 0.414954E+11 | 0.00 | 0.00 |
Minimum of Months | 0.583945E+10 | 0.703115E+09 | 0.486720E+10 | 0.749933E+09 | 0.208008E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125017E+11 | 0.939557E+10 | 0.104528E+11 | 0.655480E+10 | 0.442363E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.422206E+09 | 0.165875E+10 | 0.719117E+09 | 0.396569E+09 | 0.322548E+09 | 0.00 | 0.00 |
February | 0.554419E+09 | 0.149574E+10 | 0.899886E+09 | 0.506255E+09 | 0.393631E+09 | 0.00 | 0.00 |
March | 0.909862E+09 | 0.115896E+10 | 0.115267E+10 | 0.576286E+09 | 0.576380E+09 | 0.00 | 0.00 |
April | 0.992003E+09 | 0.787059E+09 | 0.107571E+10 | 0.451219E+09 | 0.624496E+09 | 0.00 | 0.00 |
May | 0.128068E+10 | 0.435909E+09 | 0.117946E+10 | 0.390358E+09 | 0.789101E+09 | 0.00 | 0.00 |
June | 0.158671E+10 | 0.163365E+09 | 0.119961E+10 | 0.408744E+09 | 0.790869E+09 | 0.00 | 0.00 |
July | 0.180211E+10 | 43293434.20 | 0.119251E+10 | 0.380877E+09 | 0.811632E+09 | 0.00 | 0.00 |
August | 0.208365E+10 | 98068442.47 | 0.139508E+10 | 0.604355E+09 | 0.790726E+09 | 0.00 | 0.00 |
September | 0.140344E+10 | 0.279470E+09 | 0.110533E+10 | 0.511670E+09 | 0.593660E+09 | 0.00 | 0.00 |
October | 0.144878E+10 | 0.666212E+09 | 0.132659E+10 | 0.737050E+09 | 0.589543E+09 | 0.00 | 0.00 |
November | 0.523994E+09 | 0.111618E+10 | 0.743683E+09 | 0.351078E+09 | 0.392605E+09 | 0.00 | 0.00 |
December | 0.456702E+09 | 0.149591E+10 | 0.727566E+09 | 0.438228E+09 | 0.289337E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134646E+11 | 0.939893E+10 | 0.127172E+11 | 0.575269E+10 | 0.696453E+10 | 0.00 | 0.00 |
Minimum of Months | 0.422206E+09 | 43293434.20 | 0.719117E+09 | 0.351078E+09 | 0.289337E+09 | 0.00 | 0.00 |
Maximum of Months | 0.208365E+10 | 0.165875E+10 | 0.139508E+10 | 0.737050E+09 | 0.811632E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121298E+09 | 0.177200E+10 | 0.385960E+09 | 0.125866E+09 | 0.260093E+09 | 0.00 | 0.00 |
February | 0.191027E+09 | 0.163022E+10 | 0.504884E+09 | 0.178528E+09 | 0.326356E+09 | 0.00 | 0.00 |
March | 0.500367E+09 | 0.118891E+10 | 0.819617E+09 | 0.310021E+09 | 0.509596E+09 | 0.00 | 0.00 |
April | 0.703463E+09 | 0.798294E+09 | 0.878567E+09 | 0.301201E+09 | 0.577366E+09 | 0.00 | 0.00 |
May | 0.109212E+10 | 0.457498E+09 | 0.108991E+10 | 0.331481E+09 | 0.758425E+09 | 0.00 | 0.00 |
June | 0.142569E+10 | 0.209881E+09 | 0.114362E+10 | 0.375280E+09 | 0.768339E+09 | 0.00 | 0.00 |
July | 0.164536E+10 | 62407585.04 | 0.111453E+10 | 0.335679E+09 | 0.778846E+09 | 0.00 | 0.00 |
August | 0.173054E+10 | 0.118010E+09 | 0.117827E+10 | 0.446732E+09 | 0.731539E+09 | 0.00 | 0.00 |
September | 0.962156E+09 | 0.334302E+09 | 0.820042E+09 | 0.288640E+09 | 0.531402E+09 | 0.00 | 0.00 |
October | 0.766906E+09 | 0.715145E+09 | 0.819824E+09 | 0.330113E+09 | 0.489711E+09 | 0.00 | 0.00 |
November | 0.160583E+09 | 0.117676E+10 | 0.405333E+09 | 90224391.19 | 0.315109E+09 | 0.00 | 0.00 |
December | 0.110149E+09 | 0.161007E+10 | 0.351108E+09 | 0.121681E+09 | 0.229428E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.940967E+10 | 0.100735E+11 | 0.951166E+10 | 0.323545E+10 | 0.627621E+10 | 0.00 | 0.00 |
Minimum of Months | 0.110149E+09 | 62407585.04 | 0.351108E+09 | 90224391.19 | 0.229428E+09 | 0.00 | 0.00 |
Maximum of Months | 0.173054E+10 | 0.177200E+10 | 0.117827E+10 | 0.446732E+09 | 0.778846E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.265820E+09 | 0.518271E+09 | 0.329951E+09 | 0.216519E+09 | 0.113433E+09 | 0.00 | 0.00 |
February | 0.314502E+09 | 0.503484E+09 | 0.394400E+09 | 0.262129E+09 | 0.132271E+09 | 0.00 | 0.00 |
March | 0.329555E+09 | 0.444412E+09 | 0.386878E+09 | 0.212972E+09 | 0.173906E+09 | 0.00 | 0.00 |
April | 0.259763E+09 | 0.329467E+09 | 0.298011E+09 | 0.120568E+09 | 0.177443E+09 | 0.00 | 0.00 |
May | 0.240671E+09 | 0.215061E+09 | 0.264487E+09 | 54149907.01 | 0.210337E+09 | 0.00 | 0.00 |
June | 0.272464E+09 | 0.112021E+09 | 0.241685E+09 | 37238589.41 | 0.204446E+09 | 0.00 | 0.00 |
July | 0.347352E+09 | 65918306.02 | 0.259857E+09 | 43858614.47 | 0.215998E+09 | 0.00 | 0.00 |
August | 0.480460E+09 | 84875405.31 | 0.348053E+09 | 0.128394E+09 | 0.219659E+09 | 0.00 | 0.00 |
September | 0.423038E+09 | 0.159144E+09 | 0.355442E+09 | 0.178463E+09 | 0.176980E+09 | 0.00 | 0.00 |
October | 0.567649E+09 | 0.282042E+09 | 0.519043E+09 | 0.325484E+09 | 0.193559E+09 | 0.00 | 0.00 |
November | 0.295752E+09 | 0.419130E+09 | 0.347810E+09 | 0.208641E+09 | 0.139168E+09 | 0.00 | 0.00 |
December | 0.294570E+09 | 0.517350E+09 | 0.356476E+09 | 0.253188E+09 | 0.103288E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.409160E+10 | 0.365117E+10 | 0.410209E+10 | 0.204161E+10 | 0.206049E+10 | 0.00 | 0.00 |
Minimum of Months | 0.240671E+09 | 65918306.02 | 0.241685E+09 | 37238589.41 | 0.103288E+09 | 0.00 | 0.00 |
Maximum of Months | 0.567649E+09 | 0.518271E+09 | 0.519043E+09 | 0.325484E+09 | 0.219659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59922.84 | 0.548039E+09 | 63499726.01 | 0.00 | 63499726.01 | 0.00 | 0.00 |
February | 1202983.82 | 0.506008E+09 | 78487323.57 | 0.00 | 78487323.57 | 0.00 | 0.00 |
March | 21049500.98 | 0.363575E+09 | 0.120532E+09 | 2510.56 | 0.120530E+09 | 0.00 | 0.00 |
April | 68228047.07 | 0.230392E+09 | 0.140371E+09 | 578401.65 | 0.139793E+09 | 0.00 | 0.00 |
May | 0.166469E+09 | 0.121963E+09 | 0.192923E+09 | 7060527.70 | 0.185863E+09 | 0.00 | 0.00 |
June | 0.249288E+09 | 51920009.85 | 0.196964E+09 | 10476325.32 | 0.186488E+09 | 0.00 | 0.00 |
July | 0.318884E+09 | 14835472.03 | 0.197547E+09 | 7709824.18 | 0.189837E+09 | 0.00 | 0.00 |
August | 0.284833E+09 | 28505038.46 | 0.174698E+09 | 2321233.44 | 0.172376E+09 | 0.00 | 0.00 |
September | 0.138813E+09 | 89278563.10 | 0.127300E+09 | 74006.34 | 0.127226E+09 | 0.00 | 0.00 |
October | 71064331.53 | 0.200442E+09 | 0.113747E+09 | 0.00 | 0.113747E+09 | 0.00 | 0.00 |
November | 11008268.46 | 0.354994E+09 | 77209156.90 | 0.00 | 77209156.90 | 0.00 | 0.00 |
December | 184971.89 | 0.497690E+09 | 55388634.65 | 0.00 | 55388634.65 | 0.00 | 0.00 |
Annual Sum or Average | 0.133109E+10 | 0.300764E+10 | 0.153867E+10 | 28222829.17 | 0.151044E+10 | 0.00 | 0.00 |
Minimum of Months | 59922.84 | 14835472.03 | 55388634.65 | 0.00 | 55388634.65 | 0.00 | 0.00 |
Maximum of Months | 0.318884E+09 | 0.548039E+09 | 0.197547E+09 | 10476325.32 | 0.189837E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.421078E+09 | 0.164413E+10 | 0.721261E+09 | 0.394054E+09 | 0.327207E+09 | 0.00 | 0.00 |
February | 0.578355E+09 | 0.147132E+10 | 0.926055E+09 | 0.529346E+09 | 0.396709E+09 | 0.00 | 0.00 |
March | 0.858024E+09 | 0.117081E+10 | 0.109925E+10 | 0.527876E+09 | 0.571374E+09 | 0.00 | 0.00 |
April | 0.989789E+09 | 0.766967E+09 | 0.108569E+10 | 0.463730E+09 | 0.621960E+09 | 0.00 | 0.00 |
May | 0.132544E+10 | 0.423941E+09 | 0.122030E+10 | 0.422229E+09 | 0.798066E+09 | 0.00 | 0.00 |
June | 0.145864E+10 | 0.155876E+09 | 0.110160E+10 | 0.336123E+09 | 0.765475E+09 | 0.00 | 0.00 |
July | 0.175568E+10 | 40563841.04 | 0.115348E+10 | 0.353143E+09 | 0.800339E+09 | 0.00 | 0.00 |
August | 0.204567E+10 | 91493019.70 | 0.136990E+10 | 0.582247E+09 | 0.787657E+09 | 0.00 | 0.00 |
September | 0.141574E+10 | 0.268716E+09 | 0.112107E+10 | 0.527963E+09 | 0.593108E+09 | 0.00 | 0.00 |
October | 0.138669E+10 | 0.651497E+09 | 0.128063E+10 | 0.692878E+09 | 0.587753E+09 | 0.00 | 0.00 |
November | 0.614540E+09 | 0.110265E+10 | 0.813478E+09 | 0.406353E+09 | 0.407125E+09 | 0.00 | 0.00 |
December | 0.489798E+09 | 0.148041E+10 | 0.751568E+09 | 0.460879E+09 | 0.290689E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.133394E+11 | 0.926838E+10 | 0.126443E+11 | 0.569682E+10 | 0.694746E+10 | 0.00 | 0.00 |
Minimum of Months | 0.421078E+09 | 40563841.04 | 0.721261E+09 | 0.336123E+09 | 0.290689E+09 | 0.00 | 0.00 |
Maximum of Months | 0.204567E+10 | 0.164413E+10 | 0.136990E+10 | 0.692878E+09 | 0.800339E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103982E+09 | 0.173987E+10 | 0.388104E+09 | 0.123352E+09 | 0.264752E+09 | 0.00 | 0.00 |
February | 0.177240E+09 | 0.156429E+10 | 0.531053E+09 | 0.201619E+09 | 0.329434E+09 | 0.00 | 0.00 |
March | 0.441653E+09 | 0.119443E+10 | 0.766201E+09 | 0.261611E+09 | 0.504590E+09 | 0.00 | 0.00 |
April | 0.701719E+09 | 0.771784E+09 | 0.888542E+09 | 0.313713E+09 | 0.574830E+09 | 0.00 | 0.00 |
May | 0.114813E+10 | 0.443384E+09 | 0.113074E+10 | 0.363353E+09 | 0.767390E+09 | 0.00 | 0.00 |
June | 0.130518E+10 | 0.197422E+09 | 0.104560E+10 | 0.302659E+09 | 0.742945E+09 | 0.00 | 0.00 |
July | 0.159288E+10 | 59435654.64 | 0.107550E+10 | 0.307945E+09 | 0.767553E+09 | 0.00 | 0.00 |
August | 0.168226E+10 | 0.109852E+09 | 0.115309E+10 | 0.424624E+09 | 0.728470E+09 | 0.00 | 0.00 |
September | 0.972572E+09 | 0.312810E+09 | 0.835783E+09 | 0.304932E+09 | 0.530851E+09 | 0.00 | 0.00 |
October | 0.704775E+09 | 0.683305E+09 | 0.773864E+09 | 0.285942E+09 | 0.487922E+09 | 0.00 | 0.00 |
November | 0.225767E+09 | 0.113943E+10 | 0.475128E+09 | 0.145499E+09 | 0.329629E+09 | 0.00 | 0.00 |
December | 0.120080E+09 | 0.156866E+10 | 0.375111E+09 | 0.144331E+09 | 0.230780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.917624E+10 | 0.978467E+10 | 0.943872E+10 | 0.317958E+10 | 0.625915E+10 | 0.00 | 0.00 |
Minimum of Months | 0.103982E+09 | 59435654.64 | 0.375111E+09 | 0.123352E+09 | 0.230780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.168226E+10 | 0.173987E+10 | 0.115309E+10 | 0.424624E+09 | 0.767553E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.474770E+09 | 0.221532E+10 | 0.852475E+09 | 0.469136E+09 | 0.383339E+09 | 0.00 | 0.00 |
February | 0.584270E+09 | 0.204775E+10 | 0.102459E+10 | 0.567961E+09 | 0.456624E+09 | 0.00 | 0.00 |
March | 0.747698E+09 | 0.173312E+10 | 0.109937E+10 | 0.461457E+09 | 0.637914E+09 | 0.00 | 0.00 |
April | 0.733947E+09 | 0.120075E+10 | 0.949798E+09 | 0.262491E+09 | 0.687308E+09 | 0.00 | 0.00 |
May | 0.919793E+09 | 0.674448E+09 | 0.991007E+09 | 0.132623E+09 | 0.858384E+09 | 0.00 | 0.00 |
June | 0.119826E+10 | 0.290509E+09 | 0.950354E+09 | 0.103381E+09 | 0.846973E+09 | 0.00 | 0.00 |
July | 0.150269E+10 | 0.119115E+09 | 0.990991E+09 | 0.111731E+09 | 0.879260E+09 | 0.00 | 0.00 |
August | 0.171270E+10 | 0.191885E+09 | 0.113259E+10 | 0.283222E+09 | 0.849366E+09 | 0.00 | 0.00 |
September | 0.127502E+10 | 0.475319E+09 | 0.104592E+10 | 0.386839E+09 | 0.659079E+09 | 0.00 | 0.00 |
October | 0.141808E+10 | 0.994880E+09 | 0.137104E+10 | 0.705234E+09 | 0.665803E+09 | 0.00 | 0.00 |
November | 0.628873E+09 | 0.161776E+10 | 0.920868E+09 | 0.452068E+09 | 0.468800E+09 | 0.00 | 0.00 |
December | 0.538352E+09 | 0.209487E+10 | 0.892375E+09 | 0.548588E+09 | 0.343787E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.117345E+11 | 0.136557E+11 | 0.122214E+11 | 0.448473E+10 | 0.773664E+10 | 0.00 | 0.00 |
Minimum of Months | 0.474770E+09 | 0.119115E+09 | 0.852475E+09 | 0.103381E+09 | 0.343787E+09 | 0.00 | 0.00 |
Maximum of Months | 0.171270E+10 | 0.221532E+10 | 0.137104E+10 | 0.705234E+09 | 0.879260E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.424449E+09 | 0.163146E+10 | 0.719117E+09 | 0.396569E+09 | 0.322548E+09 | 0.00 | 0.00 |
February | 0.556013E+09 | 0.147093E+10 | 0.899886E+09 | 0.506255E+09 | 0.393631E+09 | 0.00 | 0.00 |
March | 0.907364E+09 | 0.112517E+10 | 0.115267E+10 | 0.576286E+09 | 0.576380E+09 | 0.00 | 0.00 |
April | 0.984410E+09 | 0.760093E+09 | 0.107571E+10 | 0.451219E+09 | 0.624496E+09 | 0.00 | 0.00 |
May | 0.126462E+10 | 0.422752E+09 | 0.117946E+10 | 0.390358E+09 | 0.789101E+09 | 0.00 | 0.00 |
June | 0.156369E+10 | 0.157216E+09 | 0.119961E+10 | 0.408744E+09 | 0.790869E+09 | 0.00 | 0.00 |
July | 0.177990E+10 | 39493837.03 | 0.119251E+10 | 0.380877E+09 | 0.811632E+09 | 0.00 | 0.00 |
August | 0.206165E+10 | 92129050.90 | 0.139508E+10 | 0.604355E+09 | 0.790726E+09 | 0.00 | 0.00 |
September | 0.138887E+10 | 0.267951E+09 | 0.110533E+10 | 0.511670E+09 | 0.593660E+09 | 0.00 | 0.00 |
October | 0.143723E+10 | 0.645772E+09 | 0.132659E+10 | 0.737050E+09 | 0.589543E+09 | 0.00 | 0.00 |
November | 0.531906E+09 | 0.107488E+10 | 0.743683E+09 | 0.351078E+09 | 0.392605E+09 | 0.00 | 0.00 |
December | 0.465970E+09 | 0.145639E+10 | 0.727566E+09 | 0.438228E+09 | 0.289337E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.133661E+11 | 0.914424E+10 | 0.127172E+11 | 0.575269E+10 | 0.696453E+10 | 0.00 | 0.00 |
Minimum of Months | 0.424449E+09 | 39493837.03 | 0.719117E+09 | 0.351078E+09 | 0.289337E+09 | 0.00 | 0.00 |
Maximum of Months | 0.206165E+10 | 0.163146E+10 | 0.139508E+10 | 0.737050E+09 | 0.811632E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124521E+09 | 0.174483E+10 | 0.385960E+09 | 0.125866E+09 | 0.260093E+09 | 0.00 | 0.00 |
February | 0.194276E+09 | 0.160652E+10 | 0.504884E+09 | 0.178528E+09 | 0.326356E+09 | 0.00 | 0.00 |
March | 0.503991E+09 | 0.115072E+10 | 0.819617E+09 | 0.310021E+09 | 0.509596E+09 | 0.00 | 0.00 |
April | 0.700030E+09 | 0.771324E+09 | 0.878567E+09 | 0.301201E+09 | 0.577366E+09 | 0.00 | 0.00 |
May | 0.107514E+10 | 0.450314E+09 | 0.108991E+10 | 0.331481E+09 | 0.758425E+09 | 0.00 | 0.00 |
June | 0.139983E+10 | 0.213173E+09 | 0.114362E+10 | 0.375280E+09 | 0.768339E+09 | 0.00 | 0.00 |
July | 0.162425E+10 | 61326200.58 | 0.111453E+10 | 0.335679E+09 | 0.778846E+09 | 0.00 | 0.00 |
August | 0.171268E+10 | 0.114609E+09 | 0.117827E+10 | 0.446732E+09 | 0.731539E+09 | 0.00 | 0.00 |
September | 0.949713E+09 | 0.329035E+09 | 0.820042E+09 | 0.288640E+09 | 0.531402E+09 | 0.00 | 0.00 |
October | 0.763155E+09 | 0.694617E+09 | 0.819824E+09 | 0.330113E+09 | 0.489711E+09 | 0.00 | 0.00 |
November | 0.169440E+09 | 0.112860E+10 | 0.405333E+09 | 90224391.19 | 0.315109E+09 | 0.00 | 0.00 |
December | 0.117473E+09 | 0.156545E+10 | 0.351108E+09 | 0.121681E+09 | 0.229428E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.933451E+10 | 0.983051E+10 | 0.951166E+10 | 0.323545E+10 | 0.627621E+10 | 0.00 | 0.00 |
Minimum of Months | 0.117473E+09 | 61326200.58 | 0.351108E+09 | 90224391.19 | 0.229428E+09 | 0.00 | 0.00 |
Maximum of Months | 0.171268E+10 | 0.174483E+10 | 0.117827E+10 | 0.446732E+09 | 0.778846E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.496582E+09 | 0.847161E+09 | 0.605002E+09 | 0.397011E+09 | 0.207991E+09 | 0.00 | 0.00 |
February | 0.608318E+09 | 0.763236E+09 | 0.723176E+09 | 0.480643E+09 | 0.242533E+09 | 0.00 | 0.00 |
March | 0.646877E+09 | 0.607102E+09 | 0.709384E+09 | 0.390508E+09 | 0.318876E+09 | 0.00 | 0.00 |
April | 0.530931E+09 | 0.407753E+09 | 0.546436E+09 | 0.221075E+09 | 0.325361E+09 | 0.00 | 0.00 |
May | 0.522350E+09 | 0.224347E+09 | 0.484966E+09 | 99289786.41 | 0.385677E+09 | 0.00 | 0.00 |
June | 0.603747E+09 | 77773369.97 | 0.443156E+09 | 68281033.02 | 0.374875E+09 | 0.00 | 0.00 |
July | 0.763991E+09 | 17644049.84 | 0.476476E+09 | 80419574.17 | 0.396057E+09 | 0.00 | 0.00 |
August | 0.998682E+09 | 44576998.00 | 0.638193E+09 | 0.235424E+09 | 0.402770E+09 | 0.00 | 0.00 |
September | 0.853106E+09 | 0.137451E+09 | 0.651742E+09 | 0.327231E+09 | 0.324511E+09 | 0.00 | 0.00 |
October | 0.110540E+10 | 0.335003E+09 | 0.951723E+09 | 0.596811E+09 | 0.354912E+09 | 0.00 | 0.00 |
November | 0.590201E+09 | 0.564669E+09 | 0.637747E+09 | 0.382567E+09 | 0.255180E+09 | 0.00 | 0.00 |
December | 0.574738E+09 | 0.757517E+09 | 0.653638E+09 | 0.464248E+09 | 0.189390E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.829492E+10 | 0.478423E+10 | 0.752164E+10 | 0.374351E+10 | 0.377813E+10 | 0.00 | 0.00 |
Minimum of Months | 0.496582E+09 | 17644049.84 | 0.443156E+09 | 68281033.02 | 0.189390E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110540E+10 | 0.847161E+09 | 0.951723E+09 | 0.596811E+09 | 0.402770E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71678.16 | 0.520391E+10 | 0.555528E+09 | 0.00 | 0.555528E+09 | 0.00 | 0.00 |
February | 3969175.62 | 0.480063E+10 | 0.686647E+09 | 0.00 | 0.686647E+09 | 0.00 | 0.00 |
March | 0.128533E+09 | 0.364958E+10 | 0.105448E+10 | 21963.65 | 0.105446E+10 | 0.00 | 0.00 |
April | 0.471047E+09 | 0.244034E+10 | 0.122804E+10 | 5060151.99 | 0.122298E+10 | 0.00 | 0.00 |
May | 0.121664E+10 | 0.137098E+10 | 0.168779E+10 | 61769089.72 | 0.162602E+10 | 0.00 | 0.00 |
June | 0.193467E+10 | 0.642585E+09 | 0.172314E+10 | 91652225.77 | 0.163149E+10 | 0.00 | 0.00 |
July | 0.241751E+10 | 0.309477E+09 | 0.172824E+10 | 67449465.79 | 0.166079E+10 | 0.00 | 0.00 |
August | 0.211437E+10 | 0.443809E+09 | 0.152834E+10 | 20307331.48 | 0.150804E+10 | 0.00 | 0.00 |
September | 0.103925E+10 | 0.103816E+10 | 0.111368E+10 | 647445.10 | 0.111303E+10 | 0.00 | 0.00 |
October | 0.503572E+09 | 0.213052E+10 | 0.995119E+09 | 0.00 | 0.995119E+09 | 0.00 | 0.00 |
November | 60665313.32 | 0.356220E+10 | 0.675465E+09 | 0.00 | 0.675465E+09 | 0.00 | 0.00 |
December | 614439.65 | 0.478326E+10 | 0.484568E+09 | 0.00 | 0.484568E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.989092E+10 | 0.303755E+11 | 0.134610E+11 | 0.246908E+09 | 0.132141E+11 | 0.00 | 0.00 |
Minimum of Months | 71678.16 | 0.309477E+09 | 0.484568E+09 | 0.00 | 0.484568E+09 | 0.00 | 0.00 |
Maximum of Months | 0.241751E+10 | 0.520391E+10 | 0.172824E+10 | 91652225.77 | 0.166079E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.538383E+10 | 0.555528E+09 | 0.00 | 0.555528E+09 | 0.00 | 0.00 |
February | 1886539.95 | 0.495310E+10 | 0.686647E+09 | 0.00 | 0.686647E+09 | 0.00 | 0.00 |
March | 0.110413E+09 | 0.379355E+10 | 0.105448E+10 | 21963.65 | 0.105446E+10 | 0.00 | 0.00 |
April | 0.438683E+09 | 0.252353E+10 | 0.122804E+10 | 5060151.99 | 0.122298E+10 | 0.00 | 0.00 |
May | 0.117442E+10 | 0.140946E+10 | 0.168779E+10 | 61769089.72 | 0.162602E+10 | 0.00 | 0.00 |
June | 0.189711E+10 | 0.665197E+09 | 0.172314E+10 | 91652225.77 | 0.163149E+10 | 0.00 | 0.00 |
July | 0.238436E+10 | 0.328567E+09 | 0.172824E+10 | 67449465.79 | 0.166079E+10 | 0.00 | 0.00 |
August | 0.208004E+10 | 0.464436E+09 | 0.152834E+10 | 20307331.48 | 0.150804E+10 | 0.00 | 0.00 |
September | 0.100487E+10 | 0.107395E+10 | 0.111368E+10 | 647445.10 | 0.111303E+10 | 0.00 | 0.00 |
October | 0.474066E+09 | 0.219497E+10 | 0.995119E+09 | 0.00 | 0.995119E+09 | 0.00 | 0.00 |
November | 52332501.36 | 0.370240E+10 | 0.675465E+09 | 0.00 | 0.675465E+09 | 0.00 | 0.00 |
December | 257780.39 | 0.497792E+10 | 0.484568E+09 | 0.00 | 0.484568E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.961845E+10 | 0.314709E+11 | 0.134610E+11 | 0.246908E+09 | 0.132141E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.328567E+09 | 0.484568E+09 | 0.00 | 0.484568E+09 | 0.00 | 0.00 |
Maximum of Months | 0.238436E+10 | 0.538383E+10 | 0.172824E+10 | 91652225.77 | 0.166079E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.373712E+09 | 0.415183E+10 | 0.110932E+10 | 0.517388E+09 | 0.591933E+09 | 0.00 | 0.00 |
February | 0.577803E+09 | 0.359751E+10 | 0.145705E+10 | 0.730936E+09 | 0.726110E+09 | 0.00 | 0.00 |
March | 0.116136E+10 | 0.299547E+10 | 0.186536E+10 | 0.789450E+09 | 0.107591E+10 | 0.00 | 0.00 |
April | 0.157994E+10 | 0.206218E+10 | 0.197413E+10 | 0.777398E+09 | 0.119673E+10 | 0.00 | 0.00 |
May | 0.236154E+10 | 0.125382E+10 | 0.235091E+10 | 0.785532E+09 | 0.156538E+10 | 0.00 | 0.00 |
June | 0.269410E+10 | 0.641106E+09 | 0.214709E+10 | 0.638741E+09 | 0.150835E+10 | 0.00 | 0.00 |
July | 0.324850E+10 | 0.346993E+09 | 0.222886E+10 | 0.661045E+09 | 0.156782E+10 | 0.00 | 0.00 |
August | 0.363344E+10 | 0.447402E+09 | 0.252287E+10 | 0.100681E+10 | 0.151605E+10 | 0.00 | 0.00 |
September | 0.233757E+10 | 0.909125E+09 | 0.195676E+10 | 0.832852E+09 | 0.112391E+10 | 0.00 | 0.00 |
October | 0.199919E+10 | 0.175092E+10 | 0.205441E+10 | 0.978780E+09 | 0.107563E+10 | 0.00 | 0.00 |
November | 0.717255E+09 | 0.285243E+10 | 0.128855E+10 | 0.551831E+09 | 0.736721E+09 | 0.00 | 0.00 |
December | 0.458434E+09 | 0.375512E+10 | 0.112664E+10 | 0.605189E+09 | 0.521447E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.211428E+11 | 0.247639E+11 | 0.220819E+11 | 0.887595E+10 | 0.132060E+11 | 0.00 | 0.00 |
Minimum of Months | 0.373712E+09 | 0.346993E+09 | 0.110932E+10 | 0.517388E+09 | 0.521447E+09 | 0.00 | 0.00 |
Maximum of Months | 0.363344E+10 | 0.415183E+10 | 0.252287E+10 | 0.100681E+10 | 0.156782E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111695E+10 | 0.371285E+10 | 0.173050E+10 | 0.101061E+10 | 0.719889E+09 | 0.00 | 0.00 |
February | 0.139278E+10 | 0.333354E+10 | 0.207627E+10 | 0.122350E+10 | 0.852765E+09 | 0.00 | 0.00 |
March | 0.164405E+10 | 0.280013E+10 | 0.216725E+10 | 0.994066E+09 | 0.117319E+10 | 0.00 | 0.00 |
April | 0.146431E+10 | 0.203764E+10 | 0.181196E+10 | 0.564492E+09 | 0.124746E+10 | 0.00 | 0.00 |
May | 0.166007E+10 | 0.122450E+10 | 0.181309E+10 | 0.273922E+09 | 0.153916E+10 | 0.00 | 0.00 |
June | 0.209754E+10 | 0.544098E+09 | 0.171877E+10 | 0.205232E+09 | 0.151354E+10 | 0.00 | 0.00 |
July | 0.264189E+10 | 0.238844E+09 | 0.180534E+10 | 0.227834E+09 | 0.157751E+10 | 0.00 | 0.00 |
August | 0.315537E+10 | 0.363537E+09 | 0.214847E+10 | 0.606245E+09 | 0.154223E+10 | 0.00 | 0.00 |
September | 0.246346E+10 | 0.864040E+09 | 0.204082E+10 | 0.833206E+09 | 0.120761E+10 | 0.00 | 0.00 |
October | 0.291641E+10 | 0.173811E+10 | 0.276379E+10 | 0.151922E+10 | 0.124458E+10 | 0.00 | 0.00 |
November | 0.142126E+10 | 0.262140E+10 | 0.185497E+10 | 0.973844E+09 | 0.881126E+09 | 0.00 | 0.00 |
December | 0.131267E+10 | 0.331647E+10 | 0.182998E+10 | 0.118177E+10 | 0.648214E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.232868E+11 | 0.227952E+11 | 0.237612E+11 | 0.961394E+10 | 0.141473E+11 | 0.00 | 0.00 |
Minimum of Months | 0.111695E+10 | 0.238844E+09 | 0.171877E+10 | 0.205232E+09 | 0.648214E+09 | 0.00 | 0.00 |
Maximum of Months | 0.315537E+10 | 0.371285E+10 | 0.276379E+10 | 0.151922E+10 | 0.157751E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.123998E+12 | -0.122162E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.183537E+10 | 82.17 | 0.00 | 0.00 |
February | 0.112754E+12 | -0.111090E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.166422E+10 | 82.17 | 0.00 | 0.00 |
March | 0.122943E+12 | -0.121107E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.183608E+10 | 82.17 | 0.00 | 0.00 |
April | 0.114865E+12 | -0.113114E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175095E+10 | 82.17 | 0.00 | 0.00 |
May | 0.113213E+12 | -0.111446E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.176766E+10 | 82.17 | 0.00 | 0.00 |
June | 0.104529E+12 | -0.102832E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169687E+10 | 82.17 | 0.00 | 0.00 |
July | 0.104485E+12 | -0.102732E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
August | 0.103562E+12 | -0.101808E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
September | 0.102114E+12 | -0.100418E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169686E+10 | 82.17 | 0.00 | 0.00 |
October | 0.109808E+12 | -0.108054E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175372E+10 | 82.17 | 0.00 | 0.00 |
November | 0.111556E+12 | -0.109844E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.171256E+10 | 82.17 | 0.00 | 0.00 |
December | 0.120466E+12 | -0.118654E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181209E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.134429E+13 | -0.132326E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.210332E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.102114E+12 | -0.122162E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.183608E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.123998E+12 | -0.100418E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.166422E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804741E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164443941.7 | 82.17 | 0.00 | 0.00 |
February | 0.727200E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148638184.7 | 82.17 | 0.00 | 0.00 |
March | 0.804566E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164101450.2 | 82.17 | 0.00 | 0.00 |
April | 0.779699E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158786784.0 | 82.17 | 0.00 | 0.00 |
May | 0.804704E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164080369.8 | 82.17 | 0.00 | 0.00 |
June | 0.778855E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158786856.4 | 82.17 | 0.00 | 0.00 |
July | 0.805548E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164078214.9 | 82.17 | 0.00 | 0.00 |
August | 0.804704E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164078270.8 | 82.17 | 0.00 | 0.00 |
September | 0.779840E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158786973.5 | 82.17 | 0.00 | 0.00 |
October | 0.804564E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164080457.7 | 82.17 | 0.00 | 0.00 |
November | 0.778015E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158824327.5 | 82.17 | 0.00 | 0.00 |
December | 0.805550E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164098694.5 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947798E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193278E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727200E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164443941.7 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805550E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148638184.7 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.746418E+11 | -0.730219E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.161996E+10 | 60.05 | 0.00 | 0.00 |
February | 0.680879E+11 | -0.666157E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.147216E+10 | 60.05 | 0.00 | 0.00 |
March | 0.737963E+11 | -0.721754E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.162094E+10 | 60.05 | 0.00 | 0.00 |
April | 0.678121E+11 | -0.662793E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153275E+10 | 60.05 | 0.00 | 0.00 |
May | 0.653278E+11 | -0.638016E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.152611E+10 | 60.05 | 0.00 | 0.00 |
June | 0.588882E+11 | -0.574304E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145779E+10 | 60.05 | 0.00 | 0.00 |
July | 0.577489E+11 | -0.562425E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
August | 0.570087E+11 | -0.555024E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
September | 0.567763E+11 | -0.553185E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145778E+10 | 60.05 | 0.00 | 0.00 |
October | 0.623447E+11 | -0.608379E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150678E+10 | 60.05 | 0.00 | 0.00 |
November | 0.649090E+11 | -0.634295E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.147954E+10 | 60.05 | 0.00 | 0.00 |
December | 0.715760E+11 | -0.699883E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158770E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.778918E+12 | -0.760643E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.182743E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.567763E+11 | -0.730219E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.162094E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.746418E+11 | -0.553185E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.145778E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3472.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_1 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.729300E+11 | 64979.42 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736025E+11 | 67453.39 | 06-FEB-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413100E+11 | 44217.38 | 23-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129990E+11 | 24401.05 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.726541E+09 | 12608.89 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22657.68 | 6.20 | 20-JUN-19:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73094.96 | 6.69 | 10-JUL-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 92867.68 | 6.14 | 30-AUG-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4692842.77 | 1782.69 | 24-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.506096E+10 | 24005.84 | 09-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288663E+11 | 42705.53 | 24-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.554496E+11 | 53107.97 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290950E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22657.68 | 6.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.736025E+11 | 67453.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324332E+10 | 3238.50 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260377E+10 | 3331.40 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158946E+10 | 2083.87 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.815133E+09 | 1597.27 | 02-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101581E+09 | 960.65 | 01-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6730510.25 | 495.48 | 24-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163018E+09 | 1188.95 | 29-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137146E+10 | 2207.98 | 23-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250648E+10 | 2355.06 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324332E+10 | 3331.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242300E+09 | 758.59 | 08-JAN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181232E+09 | 653.78 | 06-FEB-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17546110.81 | 339.63 | 17-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3890744.74 | 231.59 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12337751.63 | 268.66 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82581611.67 | 469.35 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.539889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242300E+09 | 758.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.613311E+09 | 1304.41 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.590491E+09 | 1329.30 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 65860869.83 | 545.46 | 23-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 226476.74 | 105.58 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53703009.35 | 663.00 | 24-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154848E+09 | 731.98 | 31-DEC-17:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.613311E+09 | 1329.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.221728E+10 | 1691.32 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207191E+10 | 1863.43 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115001E+10 | 1294.34 | 16-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398317E+09 | 910.67 | 21-APR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3662749.85 | 209.55 | 01-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22638270.91 | 416.69 | 29-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.787929E+09 | 1135.68 | 23-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171745E+10 | 1330.09 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.836919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221728E+10 | 1863.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191199E+10 | 13703.63 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122769E+10 | 9019.92 | 27-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153990E+09 | 6041.90 | 16-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38794907.87 | 3505.60 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65427171.97 | 4014.88 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.840346E+09 | 8237.94 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.423824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.191199E+10 | 13703.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.912647E+11 | 59492.35 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.902487E+11 | 59876.32 | 06-FEB-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.572277E+11 | 53044.34 | 23-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216767E+11 | 31474.40 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208866E+10 | 19273.36 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 229765.94 | 5.73 | 19-JUN-18:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 201407.78 | 5.73 | 10-JUL-21:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 348256.75 | 5.43 | 08-AUG-21:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.247716E+09 | 7738.38 | 24-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101538E+11 | 31954.31 | 09-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422978E+11 | 51266.56 | 24-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.737421E+11 | 57417.36 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.388949E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 201407.78 | 5.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.912647E+11 | 59876.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.865577E+09 | 9898.18 | 02-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101687E+10 | 11279.10 | 06-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12176062.66 | 1185.63 | 16-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22753560.75 | 1242.13 | 23-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112401E+09 | 2492.59 | 31-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101687E+10 | 11279.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.391035E+09 | 8569.46 | 02-JAN-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.519998E+09 | 10020.24 | 06-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1396804.48 | 720.78 | 31-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.912430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.519998E+09 | 10020.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.551034E+10 | 18790.37 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.458348E+10 | 18813.16 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175459E+10 | 16858.89 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.547051E+09 | 10787.94 | 21-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23305501.89 | 6261.12 | 02-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 270880.39 | 1323.90 | 02-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 195982.36 | 903.58 | 15-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2895051.84 | 3952.25 | 23-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187366E+09 | 5804.80 | 26-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172020E+10 | 16609.85 | 25-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.369126E+10 | 18395.38 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.551034E+10 | 18813.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.639516E+10 | 18355.24 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.562633E+10 | 18378.08 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211019E+10 | 16771.50 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607478E+09 | 11216.39 | 21-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25951577.42 | 6142.90 | 02-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1246685.56 | 4898.82 | 09-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22506.06 | 375.10 | 15-JUL-21:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 624347.26 | 5248.48 | 25-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2941438.18 | 9346.24 | 23-SEP-18:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239768E+09 | 6790.57 | 07-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218679E+10 | 16729.25 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.450541E+10 | 17967.71 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22506.06 | 375.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.639516E+10 | 18378.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.335942E+11 | 119796.53 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340568E+11 | 120586.73 | 06-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123982E+11 | 103057.21 | 16-MAR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265392E+10 | 66974.42 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71867008.74 | 43698.10 | 03-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3269124.66 | 27497.27 | 02-JUN-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 833976.66 | 8339.77 | 18-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 365883.65 | 3658.84 | 15-AUG-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16521189.33 | 44689.68 | 15-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115484E+10 | 60969.90 | 07-OCT-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104154E+11 | 102965.04 | 22-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229382E+11 | 116189.70 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117304E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 365883.65 | 3658.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.340568E+11 | 120586.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.556242E+10 | 17325.66 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.451470E+10 | 17332.81 | 05-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187949E+10 | 15528.72 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.596168E+09 | 11139.46 | 21-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30730897.92 | 3482.64 | 07-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 372751.43 | 1458.13 | 06-JUN-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17871.26 | 178.71 | 07-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1433575.70 | 2787.69 | 23-SEP-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209502E+09 | 4607.12 | 28-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170779E+10 | 15322.21 | 25-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374550E+10 | 16979.42 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.556242E+10 | 17332.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.643464E+10 | 16914.57 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552860E+10 | 16897.55 | 05-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223823E+10 | 15160.92 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.659526E+09 | 11544.42 | 21-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34960739.04 | 5133.41 | 15-MAY-16:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 127739.97 | 1092.10 | 02-JUN-21:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 97516.15 | 1153.58 | 19-AUG-21:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1528645.03 | 4260.17 | 23-SEP-18:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270737E+09 | 5921.46 | 19-OCT-16:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209350E+10 | 15034.57 | 23-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.447609E+10 | 16551.96 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.643464E+10 | 16914.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217556E+10 | 5067.49 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191230E+10 | 5073.12 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944787E+09 | 4663.17 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394627E+09 | 4043.20 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38333347.46 | 1500.46 | 10-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 363085.17 | 1132.95 | 02-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 61379.97 | 294.60 | 15-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14270.39 | 142.70 | 06-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5261114.00 | 1334.88 | 29-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154731E+09 | 2073.40 | 31-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.959176E+09 | 4626.20 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172147E+10 | 4962.02 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.830668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 14270.39 | 142.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.217556E+10 | 5073.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247255E+10 | 4940.37 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226766E+10 | 4946.04 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109589E+10 | 4545.64 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.423523E+09 | 3943.19 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36437828.69 | 1344.43 | 25-MAY-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 191092.46 | 1725.68 | 02-JUN-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84067.55 | 650.10 | 11-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 94608.23 | 505.51 | 25-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4451380.84 | 1746.93 | 19-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189878E+09 | 3864.71 | 29-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115872E+10 | 4515.37 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203108E+10 | 4837.02 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.968056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 84067.55 | 505.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247255E+10 | 4946.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.805635E+10 | 24806.29 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.672963E+10 | 24802.96 | 06-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348551E+10 | 22324.80 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142265E+10 | 18669.88 | 21-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121303E+09 | 8104.92 | 02-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2798109.15 | 6036.20 | 02-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 357746.75 | 1532.15 | 15-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 250485.33 | 1489.05 | 31-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9423151.23 | 5659.60 | 24-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.423892E+09 | 7947.07 | 01-OCT-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.283382E+10 | 21125.55 | 25-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.593183E+10 | 24162.02 | 31-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 250485.33 | 1489.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.805635E+10 | 24806.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_0 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.990408E+10 | 19006.00 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171427E+11 | 22716.42 | 06-FEB-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.800587E+10 | 14584.20 | 23-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144462E+10 | 7517.12 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4693402.65 | 1076.55 | 25-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311873E+09 | 9744.94 | 31-DEC-17:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.368139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171427E+11 | 22716.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119609E+10 | 11649.37 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119609E+10 | 11649.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6 HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.512286E+10 | 8799.26 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.450966E+10 | 9034.52 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.503344E+09 | 4144.46 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1220222.47 | 263.09 | 02-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.792052E+09 | 4548.93 | 23-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.264801E+10 | 5351.16 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.512286E+10 | 9034.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220302E+11 | 47517.88 | 06-JAN-07:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.211526E+11 | 37899.59 | 26-FEB-15:29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.945502E+10 | 16701.20 | 23-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246375E+10 | 9360.58 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8833658.28 | 2450.24 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.541033E+09 | 6438.29 | 29-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.672433E+10 | 15927.50 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152576E+11 | 17581.86 | 31-DEC-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.776334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220302E+11 | 47517.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN HEATING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 48088077.85 | 3599.27 | 02-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 97639187.92 | 4640.34 | 06-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97639187.92 | 4640.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.172902E+09 | 0.171458E+09 | 19051.94 | 17-JAN-16:12 | 19051.94 | 0.00 |
February | 0.00 | 0.00 | 0.397996E+09 | 0.397877E+09 | 19033.64 | 19-FEB-16:12 | 19033.64 | 0.00 |
March | 0.00 | 0.00 | 0.210146E+10 | 0.202429E+10 | 21294.19 | 06-MAR-16:12 | 15665.51 | 0.00 |
April | 0.00 | 0.00 | 0.454529E+10 | 0.415841E+10 | 21897.26 | 30-APR-15:12 | 14114.17 | 0.00 |
May | 0.00 | 0.00 | 0.873780E+10 | 0.773093E+10 | 22354.75 | 18-MAY-18:02 | 13847.16 | 0.00 |
June | 0.00 | 0.00 | 0.150063E+11 | 0.117553E+11 | 23146.44 | 18-JUN-08:62 | 12656.80 | 0.00 |
July | 0.00 | 0.00 | 0.190115E+11 | 0.142528E+11 | 23179.33 | 30-JUL-08:62 | 12683.76 | 0.00 |
August | 0.00 | 0.00 | 0.185677E+11 | 0.149479E+11 | 23079.65 | 06-AUG-08:62 | 12687.98 | 0.00 |
September | 0.00 | 0.00 | 0.121947E+11 | 0.998989E+10 | 24015.72 | 22-SEP-18:02 | 10968.43 | 0.00 |
October | 0.00 | 0.00 | 0.822467E+10 | 0.693648E+10 | 22736.37 | 25-OCT-08:62 | 13118.55 | 0.00 |
November | 0.00 | 0.00 | 0.134445E+10 | 0.122846E+10 | 22000.04 | 10-NOV-09:02 | 13276.41 | 0.00 |
December | 0.00 | 0.00 | 0.325953E+09 | 0.323300E+09 | 20403.60 | 25-DEC-16:12 | 16935.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.906306E+11 | 0.739170E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.172902E+09 | 0.171458E+09 | 19033.64 | 10968.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.190115E+11 | 0.149479E+11 | 24015.72 | 19051.94 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 32774998.28 | 31331960.84 | 18588.54 | 17-JAN-16:12 | 18588.54 | 0.00 |
February | 0.00 | 0.00 | 95798708.06 | 95684532.16 | 18567.05 | 19-FEB-16:12 | 18567.05 | 0.00 |
March | 0.00 | 0.00 | 0.109077E+10 | 0.103823E+10 | 21187.55 | 27-MAR-21:01 | 16901.92 | 0.00 |
April | 0.00 | 0.00 | 0.317357E+10 | 0.283344E+10 | 21702.80 | 27-APR-18:02 | 18895.19 | 0.00 |
May | 0.00 | 0.00 | 0.646107E+10 | 0.561502E+10 | 22432.42 | 18-MAY-21:51 | 13486.79 | 0.00 |
June | 0.00 | 0.00 | 0.112104E+11 | 0.877231E+10 | 24608.31 | 21-JUN-18:32 | 14264.58 | 0.00 |
July | 0.00 | 0.00 | 0.168179E+11 | 0.125711E+11 | 25020.69 | 28-JUL-08:51 | 11184.09 | 0.00 |
August | 0.00 | 0.00 | 0.158947E+11 | 0.126249E+11 | 24716.40 | 06-AUG-08:51 | 11105.08 | 0.00 |
September | 0.00 | 0.00 | 0.802704E+10 | 0.639441E+10 | 25048.58 | 14-SEP-08:51 | 10948.93 | 0.00 |
October | 0.00 | 0.00 | 0.440949E+10 | 0.358912E+10 | 23453.91 | 05-OCT-21:51 | 13631.10 | 0.00 |
November | 0.00 | 0.00 | 0.624811E+09 | 0.543216E+09 | 21440.92 | 10-NOV-09:12 | 12677.06 | 0.00 |
December | 0.00 | 0.00 | 35886782.45 | 35070595.28 | 18441.28 | 17-DEC-16:12 | 18441.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.678743E+11 | 0.541438E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 32774998.28 | 31331960.84 | 18441.28 | 10948.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.168179E+11 | 0.126249E+11 | 25048.58 | 18895.19 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.155210E+10 | 0.155210E+10 | 27456.52 | 30-JAN-12:10 | 27456.52 | 0.00 |
February | 0.00 | 0.00 | 0.671329E+10 | 0.671329E+10 | 40162.15 | 02-FEB-13:40 | 40162.15 | 0.00 |
March | 0.00 | 0.00 | 0.141742E+11 | 0.141255E+11 | 51048.88 | 03-MAR-13:30 | 51048.88 | 0.00 |
April | 0.00 | 0.00 | 0.234557E+11 | 0.231268E+11 | 60785.04 | 07-APR-12:30 | 60785.04 | 0.00 |
May | 0.00 | 0.00 | 0.376537E+11 | 0.363089E+11 | 47212.31 | 30-MAY-14:10 | 47212.31 | 0.00 |
June | 0.00 | 0.00 | 0.598879E+11 | 0.524531E+11 | 63616.88 | 19-JUN-14:10 | 56530.28 | 0.00 |
July | 0.00 | 0.00 | 0.826137E+11 | 0.680402E+11 | 63972.72 | 09-JUL-14:10 | 52574.74 | 0.00 |
August | 0.00 | 0.00 | 0.882406E+11 | 0.773272E+11 | 74796.51 | 16-AUG-12:30 | 61155.85 | 0.00 |
September | 0.00 | 0.00 | 0.639328E+11 | 0.590582E+11 | 73069.34 | 14-SEP-12:30 | 62702.20 | 0.00 |
October | 0.00 | 0.00 | 0.582800E+11 | 0.552600E+11 | 74752.54 | 04-OCT-12:00 | 70104.01 | 0.00 |
November | 0.00 | 0.00 | 0.166617E+11 | 0.165663E+11 | 58022.78 | 02-NOV-12:40 | 58022.78 | 0.00 |
December | 0.00 | 0.00 | 0.827946E+10 | 0.827946E+10 | 52919.27 | 17-DEC-12:40 | 52919.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.461445E+12 | 0.418811E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.155210E+10 | 0.155210E+10 | 27456.52 | 27456.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.882406E+11 | 0.773272E+11 | 74796.51 | 70104.01 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.123961E+10 | 0.104851E+10 | 126137.81 | 24-JAN-09:02 | 91425.56 | 0.00 |
February | 0.00 | 0.00 | 0.508789E+09 | 0.501749E+09 | 116627.48 | 18-FEB-09:02 | 116627.48 | 0.00 |
March | 0.00 | 0.00 | 0.755768E+10 | 0.689371E+10 | 129276.26 | 06-MAR-16:12 | 92755.70 | 0.00 |
April | 0.00 | 0.00 | 0.265180E+11 | 0.228339E+11 | 132864.94 | 10-APR-08:51 | 99525.32 | 0.00 |
May | 0.00 | 0.00 | 0.552305E+11 | 0.462232E+11 | 145743.31 | 31-MAY-19:41 | 91625.15 | 0.00 |
June | 0.00 | 0.00 | 0.947797E+11 | 0.691447E+11 | 159979.07 | 24-JUN-20:21 | 68236.51 | 0.00 |
July | 0.00 | 0.00 | 0.143003E+12 | 0.978194E+11 | 160428.41 | 28-JUL-08:51 | 65992.75 | 0.00 |
August | 0.00 | 0.00 | 0.125783E+12 | 0.919453E+11 | 157504.67 | 06-AUG-08:51 | 66342.27 | 0.00 |
September | 0.00 | 0.00 | 0.720677E+11 | 0.545621E+11 | 160195.23 | 14-SEP-08:51 | 64808.68 | 0.00 |
October | 0.00 | 0.00 | 0.376495E+11 | 0.295361E+11 | 147781.93 | 23-OCT-21:51 | 76665.96 | 0.00 |
November | 0.00 | 0.00 | 0.106131E+11 | 0.919189E+10 | 136123.92 | 10-NOV-09:12 | 80414.62 | 0.00 |
December | 0.00 | 0.00 | 0.109366E+10 | 0.103004E+10 | 123848.34 | 25-DEC-09:02 | 99145.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.576045E+12 | 0.430731E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.508789E+09 | 0.501749E+09 | 116627.48 | 64808.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.143003E+12 | 0.978194E+11 | 160428.41 | 116627.48 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.182156E+09 | 0.180558E+09 | 17100.88 | 19-JAN-09:02 | 17100.88 | 0.00 |
February | 0.00 | 0.00 | 0.342825E+09 | 0.342587E+09 | 16919.90 | 19-FEB-16:12 | 16919.90 | 0.00 |
March | 0.00 | 0.00 | 0.184794E+10 | 0.178247E+10 | 18550.82 | 27-MAR-15:12 | 15116.21 | 0.00 |
April | 0.00 | 0.00 | 0.448856E+10 | 0.410025E+10 | 19462.11 | 30-APR-15:12 | 12496.93 | 0.00 |
May | 0.00 | 0.00 | 0.878700E+10 | 0.777717E+10 | 19874.13 | 19-MAY-18:02 | 12253.38 | 0.00 |
June | 0.00 | 0.00 | 0.143235E+11 | 0.111308E+11 | 20719.40 | 18-JUN-08:62 | 10977.43 | 0.00 |
July | 0.00 | 0.00 | 0.187790E+11 | 0.139885E+11 | 20534.61 | 24-JUL-08:62 | 11269.21 | 0.00 |
August | 0.00 | 0.00 | 0.183808E+11 | 0.147268E+11 | 20517.98 | 06-AUG-08:62 | 11270.65 | 0.00 |
September | 0.00 | 0.00 | 0.120989E+11 | 0.989956E+10 | 21385.93 | 22-SEP-18:02 | 9678.44 | 0.00 |
October | 0.00 | 0.00 | 0.785232E+10 | 0.660542E+10 | 20164.15 | 06-OCT-08:62 | 11263.62 | 0.00 |
November | 0.00 | 0.00 | 0.157596E+10 | 0.145188E+10 | 19666.36 | 10-NOV-09:02 | 12116.67 | 0.00 |
December | 0.00 | 0.00 | 0.420545E+09 | 0.418406E+09 | 17460.58 | 26-DEC-09:02 | 16416.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.890795E+11 | 0.724044E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.182156E+09 | 0.180558E+09 | 16919.90 | 9678.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.187790E+11 | 0.147268E+11 | 21385.93 | 17100.88 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 41948806.24 | 40422636.41 | 12651.19 | 19-JAN-09:02 | 12342.60 | 0.00 |
February | 0.00 | 0.00 | 83741729.27 | 83636715.11 | 16378.27 | 20-FEB-09:02 | 16378.27 | 0.00 |
March | 0.00 | 0.00 | 0.837193E+09 | 0.798248E+09 | 17703.57 | 02-MAR-16:12 | 14177.50 | 0.00 |
April | 0.00 | 0.00 | 0.320536E+10 | 0.286626E+10 | 18966.91 | 10-APR-08:51 | 15317.37 | 0.00 |
May | 0.00 | 0.00 | 0.670564E+10 | 0.587032E+10 | 20682.04 | 31-MAY-08:22 | 16868.74 | 0.00 |
June | 0.00 | 0.00 | 0.108136E+11 | 0.840041E+10 | 22040.51 | 27-JUN-08:32 | 12244.50 | 0.00 |
July | 0.00 | 0.00 | 0.164920E+11 | 0.122158E+11 | 21942.78 | 23-JUL-20:11 | 10120.96 | 0.00 |
August | 0.00 | 0.00 | 0.155726E+11 | 0.122634E+11 | 21914.31 | 27-AUG-08:32 | 12210.04 | 0.00 |
September | 0.00 | 0.00 | 0.811475E+10 | 0.648559E+10 | 22157.21 | 14-SEP-08:51 | 9746.91 | 0.00 |
October | 0.00 | 0.00 | 0.422952E+10 | 0.343520E+10 | 20439.21 | 05-OCT-21:51 | 11689.17 | 0.00 |
November | 0.00 | 0.00 | 0.775800E+09 | 0.681268E+09 | 19081.64 | 10-NOV-09:12 | 11563.91 | 0.00 |
December | 0.00 | 0.00 | 77122008.18 | 76019619.91 | 16409.08 | 20-DEC-09:02 | 16409.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.669493E+11 | 0.532166E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 41948806.24 | 40422636.41 | 12651.19 | 9746.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.164920E+11 | 0.122634E+11 | 22157.21 | 16868.74 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 24607997.64 | 24451863.55 | 5157.95 | 17-JAN-16:12 | 5157.95 | 0.00 |
February | 0.00 | 0.00 | 62332076.93 | 62332076.93 | 5155.12 | 19-FEB-16:12 | 5155.12 | 0.00 |
March | 0.00 | 0.00 | 0.384325E+09 | 0.369690E+09 | 5581.72 | 27-MAR-15:12 | 4722.06 | 0.00 |
April | 0.00 | 0.00 | 0.953757E+09 | 0.872901E+09 | 5812.86 | 09-APR-08:62 | 3969.90 | 0.00 |
May | 0.00 | 0.00 | 0.201871E+10 | 0.179141E+10 | 6074.61 | 19-MAY-18:02 | 3609.44 | 0.00 |
June | 0.00 | 0.00 | 0.383672E+10 | 0.300333E+10 | 6407.81 | 18-JUN-08:62 | 3140.59 | 0.00 |
July | 0.00 | 0.00 | 0.498728E+10 | 0.376629E+10 | 6387.53 | 30-JUL-08:62 | 3197.27 | 0.00 |
August | 0.00 | 0.00 | 0.485140E+10 | 0.392950E+10 | 6370.87 | 06-AUG-08:62 | 3180.43 | 0.00 |
September | 0.00 | 0.00 | 0.296819E+10 | 0.242143E+10 | 6633.33 | 22-SEP-18:02 | 2709.44 | 0.00 |
October | 0.00 | 0.00 | 0.176822E+10 | 0.146804E+10 | 6193.60 | 25-OCT-08:62 | 3286.70 | 0.00 |
November | 0.00 | 0.00 | 0.188664E+09 | 0.171850E+09 | 5727.68 | 10-NOV-16:12 | 4160.52 | 0.00 |
December | 0.00 | 0.00 | 33561559.90 | 33307105.31 | 5126.15 | 03-DEC-16:12 | 5126.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.220778E+11 | 0.179145E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 24607997.64 | 24451863.55 | 5126.15 | 2709.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.498728E+10 | 0.392950E+10 | 6633.33 | 5157.95 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2882309.59 | 2779646.51 | 5025.40 | 17-JAN-16:12 | 5025.40 | 0.00 |
February | 0.00 | 0.00 | 10380369.26 | 10380219.39 | 5009.97 | 19-FEB-16:12 | 5009.97 | 0.00 |
March | 0.00 | 0.00 | 0.174755E+09 | 0.165808E+09 | 5739.66 | 27-MAR-21:01 | 4535.57 | 0.00 |
April | 0.00 | 0.00 | 0.633927E+09 | 0.563973E+09 | 5857.66 | 27-APR-18:02 | 5119.85 | 0.00 |
May | 0.00 | 0.00 | 0.149953E+10 | 0.130706E+10 | 6061.08 | 18-MAY-21:51 | 3545.09 | 0.00 |
June | 0.00 | 0.00 | 0.295873E+10 | 0.233796E+10 | 6692.49 | 18-JUN-08:51 | 3146.07 | 0.00 |
July | 0.00 | 0.00 | 0.446895E+10 | 0.338384E+10 | 6803.00 | 28-JUL-08:51 | 2947.89 | 0.00 |
August | 0.00 | 0.00 | 0.420960E+10 | 0.337752E+10 | 6741.25 | 06-AUG-08:51 | 2874.22 | 0.00 |
September | 0.00 | 0.00 | 0.198442E+10 | 0.158188E+10 | 6829.48 | 14-SEP-08:51 | 2832.40 | 0.00 |
October | 0.00 | 0.00 | 0.873691E+09 | 0.690591E+09 | 6346.43 | 05-OCT-21:51 | 3678.33 | 0.00 |
November | 0.00 | 0.00 | 58303196.58 | 49899240.44 | 5352.09 | 08-NOV-16:12 | 4589.62 | 0.00 |
December | 0.00 | 0.00 | 2020750.72 | 1926249.11 | 4109.62 | 17-DEC-16:12 | 4109.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168772E+11 | 0.134736E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2020750.72 | 1926249.11 | 4109.62 | 2832.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.446895E+10 | 0.338384E+10 | 6829.48 | 5119.85 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.114034E+10 | 0.113857E+10 | 25140.34 | 17-JAN-16:12 | 25140.34 | 0.00 |
February | 0.00 | 0.00 | 0.166341E+10 | 0.166312E+10 | 25228.30 | 18-FEB-16:12 | 25228.30 | 0.00 |
March | 0.00 | 0.00 | 0.346140E+10 | 0.336466E+10 | 27387.98 | 27-MAR-18:02 | 22769.09 | 0.00 |
April | 0.00 | 0.00 | 0.569563E+10 | 0.518538E+10 | 28857.98 | 30-APR-15:12 | 18197.25 | 0.00 |
May | 0.00 | 0.00 | 0.100997E+11 | 0.877141E+10 | 29702.98 | 19-MAY-18:02 | 17187.73 | 0.00 |
June | 0.00 | 0.00 | 0.190745E+11 | 0.142263E+11 | 31508.36 | 18-JUN-08:62 | 15067.96 | 0.00 |
July | 0.00 | 0.00 | 0.263253E+11 | 0.191284E+11 | 31448.53 | 28-JUL-08:62 | 15238.56 | 0.00 |
August | 0.00 | 0.00 | 0.261748E+11 | 0.207396E+11 | 31125.69 | 06-AUG-08:62 | 15651.68 | 0.00 |
September | 0.00 | 0.00 | 0.179995E+11 | 0.145950E+11 | 32667.60 | 22-SEP-18:02 | 12875.45 | 0.00 |
October | 0.00 | 0.00 | 0.135035E+11 | 0.115143E+11 | 30211.25 | 25-OCT-08:62 | 16999.56 | 0.00 |
November | 0.00 | 0.00 | 0.328587E+10 | 0.310726E+10 | 29184.17 | 10-NOV-09:02 | 17310.92 | 0.00 |
December | 0.00 | 0.00 | 0.195930E+10 | 0.195405E+10 | 27106.82 | 25-DEC-16:12 | 21543.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130383E+12 | 0.105388E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.114034E+10 | 0.113857E+10 | 25140.34 | 12875.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.263253E+11 | 0.207396E+11 | 32667.60 | 25228.30 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 83066029.34 | 32599547.00 | 3217.89 | 20-FEB-13:00 | 1202.83 | 0.00 |
March | 0.00 | 0.00 | 0.365600E+10 | 0.206412E+10 | 10980.99 | 27-MAR-18:03 | 7297.48 | 0.00 |
April | 0.00 | 0.00 | 0.951417E+10 | 0.642745E+10 | 13829.80 | 08-APR-12:20 | 10847.51 | 0.00 |
May | 0.00 | 0.00 | 0.177378E+11 | 0.128397E+11 | 16892.36 | 31-MAY-18:15 | 11954.48 | 0.00 |
June | 0.00 | 0.00 | 0.288075E+11 | 0.195470E+11 | 23582.40 | 19-JUN-18:03 | 17112.80 | 0.00 |
July | 0.00 | 0.00 | 0.381778E+11 | 0.240904E+11 | 23425.73 | 08-JUL-12:30 | 14671.49 | 0.00 |
August | 0.00 | 0.00 | 0.366320E+11 | 0.249588E+11 | 24738.24 | 16-AUG-15:10 | 16351.15 | 0.00 |
September | 0.00 | 0.00 | 0.246184E+11 | 0.173568E+11 | 20064.25 | 07-SEP-14:10 | 13254.18 | 0.00 |
October | 0.00 | 0.00 | 0.174596E+11 | 0.121852E+11 | 16457.84 | 04-OCT-15:10 | 12398.84 | 0.00 |
November | 0.00 | 0.00 | 0.415228E+10 | 0.258193E+10 | 10702.84 | 04-NOV-12:30 | 7762.89 | 0.00 |
December | 0.00 | 0.00 | 0.374541E+09 | 0.152281E+09 | 4234.22 | 03-DEC-13:00 | 1798.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181213E+12 | 0.122236E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.381778E+11 | 0.249588E+11 | 24738.24 | 17112.80 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.415166E+09 | 0.264063E+09 | 5039.29 | 27-MAR-13:20 | 2419.49 | 0.00 |
April | 0.00 | 0.00 | 0.270756E+10 | 0.210699E+10 | 8705.20 | 08-APR-12:10 | 7754.06 | 0.00 |
May | 0.00 | 0.00 | 0.741294E+10 | 0.608680E+10 | 10351.00 | 31-MAY-13:00 | 9026.79 | 0.00 |
June | 0.00 | 0.00 | 0.132333E+11 | 0.105766E+11 | 13297.84 | 19-JUN-12:50 | 11494.90 | 0.00 |
July | 0.00 | 0.00 | 0.181230E+11 | 0.139385E+11 | 13842.60 | 08-JUL-12:10 | 10814.16 | 0.00 |
August | 0.00 | 0.00 | 0.174596E+11 | 0.140443E+11 | 14290.30 | 16-AUG-12:40 | 11348.86 | 0.00 |
September | 0.00 | 0.00 | 0.105778E+11 | 0.857292E+10 | 11088.00 | 07-SEP-12:50 | 9020.74 | 0.00 |
October | 0.00 | 0.00 | 0.570782E+10 | 0.439014E+10 | 9064.39 | 13-OCT-12:30 | 7707.07 | 0.00 |
November | 0.00 | 0.00 | 0.629761E+09 | 0.403550E+09 | 6303.34 | 04-NOV-12:10 | 4627.88 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.762669E+11 | 0.603838E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.181230E+11 | 0.140443E+11 | 14290.30 | 11494.90 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_1 COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 53309181.30 | 30891983.40 | 3744.13 | 18-JAN-16:00 | 2116.02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.321496E+10 | 0.257623E+10 | 40327.60 | 27-MAR-16:00 | 31399.64 | 0.00 |
April | 0.00 | 0.00 | 0.196422E+11 | 0.154531E+11 | 50746.67 | 07-APR-19:10 | 50746.67 | 0.00 |
May | 0.00 | 0.00 | 0.591135E+11 | 0.446402E+11 | 72087.39 | 31-MAY-18:10 | 48290.19 | 0.00 |
June | 0.00 | 0.00 | 0.149107E+12 | 0.911543E+11 | 124025.94 | 19-JUN-18:03 | 87468.26 | 0.00 |
July | 0.00 | 0.00 | 0.233877E+12 | 0.126017E+12 | 151069.11 | 20-JUL-21:00 | 73314.66 | 0.00 |
August | 0.00 | 0.00 | 0.203706E+12 | 0.127538E+12 | 156138.41 | 16-AUG-22:00 | 68444.26 | 0.00 |
September | 0.00 | 0.00 | 0.115671E+12 | 0.777627E+11 | 119939.37 | 13-SEP-21:00 | 57719.84 | 0.00 |
October | 0.00 | 0.00 | 0.546352E+11 | 0.354980E+11 | 69934.60 | 05-OCT-19:10 | 38848.80 | 0.00 |
November | 0.00 | 0.00 | 0.601449E+10 | 0.452022E+10 | 30457.79 | 10-NOV-08:00 | 14941.47 | 0.00 |
December | 0.00 | 0.00 | 73968757.88 | 73968757.88 | 5738.81 | 17-DEC-13:00 | 5738.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.845109E+12 | 0.525264E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.233877E+12 | 0.127538E+12 | 156138.41 | 87468.26 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_6 COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.184732E+10 | 0.149535E+10 | 34572.36 | 27-MAR-16:00 | 29113.84 | 0.00 |
April | 0.00 | 0.00 | 0.142932E+11 | 0.118679E+11 | 46307.20 | 07-APR-19:00 | 46307.20 | 0.00 |
May | 0.00 | 0.00 | 0.494061E+11 | 0.388070E+11 | 68406.76 | 31-MAY-18:10 | 44315.22 | 0.00 |
June | 0.00 | 0.00 | 0.144908E+12 | 0.874247E+11 | 124272.34 | 19-JUN-16:52 | 76626.10 | 0.00 |
July | 0.00 | 0.00 | 0.233680E+12 | 0.121739E+12 | 146234.19 | 20-JUL-21:10 | 67495.34 | 0.00 |
August | 0.00 | 0.00 | 0.193861E+12 | 0.118354E+12 | 150218.33 | 16-AUG-22:00 | 63737.96 | 0.00 |
September | 0.00 | 0.00 | 0.102497E+12 | 0.681456E+11 | 112094.86 | 13-SEP-21:10 | 54907.36 | 0.00 |
October | 0.00 | 0.00 | 0.416839E+11 | 0.260002E+11 | 67435.38 | 05-OCT-23:00 | 35245.16 | 0.00 |
November | 0.00 | 0.00 | 0.283260E+10 | 0.213226E+10 | 23619.65 | 10-NOV-08:00 | 10623.14 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.785009E+12 | 0.475966E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.233680E+12 | 0.121739E+12 | 150218.33 | 76626.10 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_0 COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.685760E+09 | 0.531797E+09 | 13223.33 | 07-APR-19:10 | 10595.44 | 0.00 |
May | 0.00 | 0.00 | 0.638482E+10 | 0.459879E+10 | 24682.86 | 31-MAY-19:53 | 13992.04 | 0.00 |
June | 0.00 | 0.00 | 0.427299E+11 | 0.245359E+11 | 41684.99 | 19-JUN-19:20 | 28533.00 | 0.00 |
July | 0.00 | 0.00 | 0.776081E+11 | 0.411239E+11 | 55048.85 | 20-JUL-21:00 | 28950.39 | 0.00 |
August | 0.00 | 0.00 | 0.766680E+11 | 0.467150E+11 | 59324.53 | 03-AUG-20:00 | 30620.44 | 0.00 |
September | 0.00 | 0.00 | 0.565834E+11 | 0.370619E+11 | 52341.53 | 13-SEP-20:00 | 29862.18 | 0.00 |
October | 0.00 | 0.00 | 0.372953E+11 | 0.250075E+11 | 41646.74 | 05-OCT-19:20 | 24926.56 | 0.00 |
November | 0.00 | 0.00 | 0.966882E+10 | 0.728494E+10 | 27125.87 | 09-NOV-20:20 | 16703.14 | 0.00 |
December | 0.00 | 0.00 | 13141179.33 | 8991051.98 | 2570.29 | 04-DEC-21:00 | 1770.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.307637E+12 | 0.186869E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.776081E+11 | 0.467150E+11 | 59324.53 | 30620.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.629950E+11 | 0.627940E+11 | 43424.17 | 23-JAN-21:00 | 42988.85 | 0.00 |
February | 0.00 | 0.00 | 0.568393E+11 | 0.567334E+11 | 43053.37 | 23-FEB-21:00 | 42708.61 | 0.00 |
March | 0.00 | 0.00 | 0.648990E+11 | 0.645857E+11 | 44463.65 | 27-MAR-20:00 | 44035.87 | 0.00 |
April | 0.00 | 0.00 | 0.642196E+11 | 0.637693E+11 | 45186.27 | 07-APR-20:00 | 44700.85 | 0.00 |
May | 0.00 | 0.00 | 0.684171E+11 | 0.677635E+11 | 45393.66 | 31-MAY-19:53 | 44866.65 | 0.00 |
June | 0.00 | 0.00 | 0.679494E+11 | 0.669274E+11 | 46266.04 | 19-JUN-20:00 | 45538.87 | 0.00 |
July | 0.00 | 0.00 | 0.710709E+11 | 0.697161E+11 | 46001.61 | 07-JUL-20:00 | 45255.25 | 0.00 |
August | 0.00 | 0.00 | 0.711288E+11 | 0.699937E+11 | 46265.32 | 04-AUG-20:00 | 45559.94 | 0.00 |
September | 0.00 | 0.00 | 0.671491E+11 | 0.662928E+11 | 45669.92 | 01-SEP-20:00 | 45175.27 | 0.00 |
October | 0.00 | 0.00 | 0.677476E+11 | 0.671118E+11 | 45068.16 | 04-OCT-20:00 | 44529.50 | 0.00 |
November | 0.00 | 0.00 | 0.631021E+11 | 0.627480E+11 | 44246.48 | 03-NOV-20:00 | 43854.51 | 0.00 |
December | 0.00 | 0.00 | 0.635989E+11 | 0.633860E+11 | 43443.11 | 04-DEC-21:00 | 43047.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.789117E+12 | 0.781822E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.568393E+11 | 0.567334E+11 | 43053.37 | 42708.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.711288E+11 | 0.699937E+11 | 46266.04 | 45559.94 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 31432127.62 | 31431150.93 | 3486.00 | 17-JAN-13:50 | 3486.00 | 0.00 |
February | 0.00 | 0.00 | 3738675.27 | 3735474.14 | 1459.91 | 20-FEB-13:00 | 1459.91 | 0.00 |
March | 0.00 | 0.00 | 0.936573E+09 | 0.828940E+09 | 13771.07 | 27-MAR-15:53 | 10135.66 | 0.00 |
April | 0.00 | 0.00 | 0.493983E+10 | 0.402951E+10 | 22124.58 | 08-APR-12:00 | 18813.92 | 0.00 |
May | 0.00 | 0.00 | 0.139810E+11 | 0.108479E+11 | 24851.77 | 31-MAY-13:10 | 17276.25 | 0.00 |
June | 0.00 | 0.00 | 0.416748E+11 | 0.256462E+11 | 36304.30 | 19-JUN-12:10 | 27118.02 | 0.00 |
July | 0.00 | 0.00 | 0.656948E+11 | 0.366362E+11 | 41736.90 | 08-JUL-12:00 | 24070.92 | 0.00 |
August | 0.00 | 0.00 | 0.601687E+11 | 0.377530E+11 | 42367.87 | 16-AUG-12:30 | 24899.38 | 0.00 |
September | 0.00 | 0.00 | 0.335396E+11 | 0.225003E+11 | 35539.17 | 07-SEP-14:10 | 20878.27 | 0.00 |
October | 0.00 | 0.00 | 0.162983E+11 | 0.111487E+11 | 27343.73 | 25-OCT-10:25 | 18533.23 | 0.00 |
November | 0.00 | 0.00 | 0.103724E+10 | 0.921370E+09 | 14935.22 | 04-NOV-12:30 | 12799.65 | 0.00 |
December | 0.00 | 0.00 | 0.103482E+09 | 0.103473E+09 | 6966.62 | 17-DEC-13:00 | 6966.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.238409E+12 | 0.150451E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 3738675.27 | 3735474.14 | 1459.91 | 1459.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.656948E+11 | 0.377530E+11 | 42367.87 | 27118.02 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN COOLING COIL
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.350004E+11 | 0.281086E+11 | 32545.65 | 24-JAN-11:40 | 22227.50 | 0.00 |
February | 0.00 | 0.00 | 0.293628E+11 | 0.243381E+11 | 29970.41 | 19-FEB-11:40 | 23832.78 | 0.00 |
March | 0.00 | 0.00 | 0.455795E+11 | 0.367571E+11 | 41497.04 | 27-MAR-17:15 | 29129.39 | 0.00 |
April | 0.00 | 0.00 | 0.561394E+11 | 0.444843E+11 | 45889.46 | 09-APR-10:35 | 31835.95 | 0.00 |
May | 0.00 | 0.00 | 0.718031E+11 | 0.553234E+11 | 50933.45 | 31-MAY-10:40 | 35988.82 | 0.00 |
June | 0.00 | 0.00 | 0.886707E+11 | 0.625584E+11 | 58100.81 | 19-JUN-17:20 | 37926.14 | 0.00 |
July | 0.00 | 0.00 | 0.105395E+12 | 0.702324E+11 | 61020.61 | 09-JUL-10:40 | 38717.43 | 0.00 |
August | 0.00 | 0.00 | 0.994896E+11 | 0.701071E+11 | 61180.06 | 04-AUG-10:40 | 38447.08 | 0.00 |
September | 0.00 | 0.00 | 0.807728E+11 | 0.591820E+11 | 54184.30 | 14-SEP-10:40 | 34221.04 | 0.00 |
October | 0.00 | 0.00 | 0.672678E+11 | 0.510878E+11 | 49467.49 | 25-OCT-10:40 | 33874.36 | 0.00 |
November | 0.00 | 0.00 | 0.467072E+11 | 0.372412E+11 | 38409.03 | 04-NOV-10:40 | 29041.46 | 0.00 |
December | 0.00 | 0.00 | 0.382218E+11 | 0.314292E+11 | 30702.84 | 25-DEC-11:40 | 21566.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.764410E+12 | 0.570850E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.293628E+11 | 0.243381E+11 | 29970.41 | 21566.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105395E+12 | 0.702324E+11 | 61180.06 | 38717.43 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 96255.13 | 415372.92 | 02-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 106090.89 | 411112.52 | 06-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 50339.56 | 293088.83 | 16-MAR-15:12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 17099.97 | 137480.53 | 21-APR-15:12 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1224.31 | 55685.17 | 03-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 3.93 | 32095.49 | 02-JUN-08:54 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.83 | 8331.90 | 18-JUL-08:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1.02 | 6779.23 | 25-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 115.36 | 58567.51 | 15-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6754.63 | 92929.03 | 07-OCT-15:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 37251.69 | 252706.88 | 22-NOV-16:12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 69099.10 | 342489.98 | 31-DEC-19:02 |
Annual Sum or Average | 0.00 | 31612.56 | ||||
Minimum of Months | 0.00 | 0.00 | 0.83 | 6779.23 | ||
Maximum of Months | 0.00 | 0.00 | 106090.89 | 415372.92 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 27153.39 | 57317.39 | 31-JAN-07:57 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 27426.07 | 57395.58 | 09-FEB-07:53 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 26837.75 | 56951.60 | 01-MAR-07:55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25463.19 | 54540.40 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 23715.88 | 51383.93 | 01-MAY-06:54 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22054.28 | 47597.87 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20897.63 | 44445.18 | 03-JUL-06:45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20621.69 | 43406.86 | 31-AUG-06:25 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21240.63 | 45448.33 | 29-SEP-06:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22610.96 | 49006.63 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24365.37 | 52672.48 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 26022.28 | 55608.86 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 24014.47 | ||||
Minimum of Months | 0.00 | 0.00 | 20621.69 | 43406.86 | ||
Maximum of Months | 0.00 | 0.00 | 27426.07 | 57395.58 |
Report: FanReportMonthly
For: VAV_FLR_1 FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.104093E+11 | 0.97 | 4187.12 | 17-JAN-13:20 | 1.00 |
February | 0.940562E+10 | 0.98 | 4078.14 | 02-FEB-13:40 | 1.00 |
March | 0.104428E+11 | 0.97 | 4442.62 | 03-MAR-22:00 | 1.03 |
April | 0.102682E+11 | 0.98 | 6882.48 | 07-APR-20:10 | 1.22 |
May | 0.110775E+11 | 0.99 | 8003.94 | 30-MAY-20:10 | 1.30 |
June | 0.120086E+11 | 1.03 | 10015.00 | 19-JUN-20:10 | 1.43 |
July | 0.134703E+11 | 1.06 | 9668.30 | 10-JUL-20:10 | 1.41 |
August | 0.140831E+11 | 1.08 | 10220.79 | 04-AUG-20:10 | 1.44 |
September | 0.118906E+11 | 1.03 | 9150.02 | 01-SEP-20:10 | 1.38 |
October | 0.113366E+11 | 1.00 | 7462.33 | 04-OCT-20:10 | 1.26 |
November | 0.101309E+11 | 0.97 | 5203.66 | 03-NOV-21:00 | 1.09 |
December | 0.104185E+11 | 0.97 | 4284.77 | 17-DEC-13:00 | 1.01 |
Annual Sum or Average | 0.134942E+12 | 1.00 | |||
Minimum of Months | 0.940562E+10 | 0.97 | 4078.14 | 1.00 | |
Maximum of Months | 0.140831E+11 | 1.08 | 10220.79 | 1.44 |
Report: FanReportMonthly
For: VAV_FLR_6 FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105127E+11 | 1.11 | 4852.20 | 23-JAN-23:00 | 1.20 |
February | 0.948589E+10 | 1.11 | 4391.11 | 23-FEB-23:00 | 1.16 |
March | 0.107118E+11 | 1.12 | 6534.58 | 27-MAR-21:02 | 1.37 |
April | 0.108738E+11 | 1.13 | 7747.64 | 07-APR-21:10 | 1.46 |
May | 0.124243E+11 | 1.18 | 8327.09 | 30-MAY-21:10 | 1.51 |
June | 0.136164E+11 | 1.23 | 9847.87 | 19-JUN-21:10 | 1.62 |
July | 0.150026E+11 | 1.27 | 9474.24 | 10-JUL-21:10 | 1.59 |
August | 0.147634E+11 | 1.26 | 10010.11 | 04-AUG-21:10 | 1.63 |
September | 0.124621E+11 | 1.19 | 9088.32 | 01-SEP-21:10 | 1.57 |
October | 0.115267E+11 | 1.14 | 7490.91 | 05-OCT-21:10 | 1.44 |
November | 0.103880E+11 | 1.12 | 6172.32 | 03-NOV-21:10 | 1.33 |
December | 0.105125E+11 | 1.11 | 4734.39 | 04-DEC-23:00 | 1.19 |
Annual Sum or Average | 0.142280E+12 | 1.16 | |||
Minimum of Months | 0.948589E+10 | 1.11 | 4391.11 | 1.16 | |
Maximum of Months | 0.150026E+11 | 1.27 | 10010.11 | 1.63 |
Report: FanReportMonthly
For: VAV_FLR_0 SZVAV FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.537717E+10 | 1.11 | 2007.60 | 01-JAN-00:05 | 1.11 |
February | 0.485679E+10 | 1.11 | 2007.60 | 01-FEB-00:05 | 1.11 |
March | 0.537717E+10 | 1.10 | 2007.60 | 01-MAR-00:05 | 1.10 |
April | 0.520371E+10 | 1.10 | 2007.60 | 07-APR-14:00 | 1.10 |
May | 0.537717E+10 | 1.10 | 2007.60 | 09-MAY-15:17 | 1.10 |
June | 0.522519E+10 | 1.10 | 2777.08 | 19-JUN-19:20 | 1.25 |
July | 0.566996E+10 | 1.11 | 4097.42 | 20-JUL-21:00 | 1.47 |
August | 0.585704E+10 | 1.13 | 4634.47 | 03-AUG-20:00 | 1.55 |
September | 0.536440E+10 | 1.11 | 3928.73 | 13-SEP-20:00 | 1.45 |
October | 0.542516E+10 | 1.10 | 2876.43 | 05-OCT-19:30 | 1.28 |
November | 0.520371E+10 | 1.10 | 2007.60 | 01-NOV-01:20 | 1.10 |
December | 0.537717E+10 | 1.11 | 2007.60 | 04-DEC-20:20 | 1.10 |
Annual Sum or Average | 0.643146E+11 | 1.11 | |||
Minimum of Months | 0.485679E+10 | 1.10 | 2007.60 | 1.10 | |
Maximum of Months | 0.585704E+10 | 1.13 | 4634.47 | 1.55 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | -0.0 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | -0.0 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | -0.0 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: ROOM_1_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144858E+10 | 0.41 | 739.38 | 01-JAN-00:05 | 0.52 |
February | 0.130491E+10 | 0.41 | 739.38 | 01-FEB-00:05 | 0.52 |
March | 0.145546E+10 | 0.43 | 739.38 | 01-MAR-00:05 | 0.52 |
April | 0.142707E+10 | 0.45 | 739.38 | 01-APR-00:10 | 0.52 |
May | 0.149998E+10 | 0.49 | 739.38 | 01-MAY-00:10 | 0.52 |
June | 0.149748E+10 | 0.51 | 739.38 | 01-JUN-00:10 | 0.52 |
July | 0.157780E+10 | 0.52 | 739.38 | 01-JUL-00:10 | 0.52 |
August | 0.159235E+10 | 0.52 | 739.38 | 01-AUG-00:10 | 0.52 |
September | 0.148063E+10 | 0.50 | 739.38 | 01-SEP-00:10 | 0.52 |
October | 0.150663E+10 | 0.48 | 739.38 | 01-OCT-00:10 | 0.52 |
November | 0.139515E+10 | 0.41 | 739.38 | 01-NOV-00:10 | 0.52 |
December | 0.144070E+10 | 0.41 | 739.38 | 01-DEC-00:05 | 0.52 |
Annual Sum or Average | 0.176267E+11 | 0.46 | |||
Minimum of Months | 0.130491E+10 | 0.41 | 739.38 | 0.52 | |
Maximum of Months | 0.159235E+10 | 0.52 | 739.38 | 0.52 |
Report: FanReportMonthly
For: ROOM_2_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142016E+10 | 0.42 | 719.81 | 01-JAN-00:05 | 0.52 |
February | 0.127792E+10 | 0.42 | 719.81 | 01-FEB-00:05 | 0.52 |
March | 0.140144E+10 | 0.41 | 719.81 | 01-MAR-00:05 | 0.52 |
April | 0.137214E+10 | 0.43 | 719.81 | 01-APR-00:10 | 0.52 |
May | 0.144436E+10 | 0.47 | 719.81 | 01-MAY-00:10 | 0.52 |
June | 0.144792E+10 | 0.49 | 719.81 | 01-JUN-00:10 | 0.52 |
July | 0.153132E+10 | 0.51 | 719.81 | 01-JUL-00:10 | 0.52 |
August | 0.153064E+10 | 0.51 | 719.81 | 01-AUG-00:10 | 0.52 |
September | 0.141464E+10 | 0.48 | 719.81 | 01-SEP-00:10 | 0.52 |
October | 0.143091E+10 | 0.45 | 719.81 | 01-OCT-00:10 | 0.52 |
November | 0.135025E+10 | 0.39 | 719.81 | 01-NOV-00:10 | 0.52 |
December | 0.140017E+10 | 0.40 | 719.81 | 01-DEC-00:05 | 0.52 |
Annual Sum or Average | 0.170219E+11 | 0.45 | |||
Minimum of Months | 0.127792E+10 | 0.39 | 719.81 | 0.52 | |
Maximum of Months | 0.153132E+10 | 0.51 | 719.81 | 0.52 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.578367E+09 | 0.05 | 4622.83 | 01-JAN-15:05 | 0.52 |
February | 0.729346E+09 | 0.15 | 4622.83 | 01-FEB-15:10 | 0.52 |
March | 0.104209E+10 | 0.23 | 4622.83 | 01-MAR-15:10 | 0.52 |
April | 0.133526E+10 | 0.36 | 4622.83 | 01-APR-14:05 | 0.52 |
May | 0.185020E+10 | 0.51 | 4622.83 | 01-MAY-14:10 | 0.52 |
June | 0.251467E+10 | 0.59 | 4622.83 | 01-JUN-14:10 | 0.52 |
July | 0.322084E+10 | 0.59 | 4622.83 | 01-JUL-14:10 | 0.52 |
August | 0.343340E+10 | 0.58 | 4622.83 | 01-AUG-14:10 | 0.52 |
September | 0.264961E+10 | 0.57 | 4622.83 | 01-SEP-14:10 | 0.52 |
October | 0.250169E+10 | 0.52 | 4622.83 | 01-OCT-14:10 | 0.52 |
November | 0.112417E+10 | 0.26 | 4622.83 | 01-NOV-14:10 | 0.52 |
December | 0.837504E+09 | 0.15 | 4622.83 | 01-DEC-15:05 | 0.52 |
Annual Sum or Average | 0.218172E+11 | 0.38 | |||
Minimum of Months | 0.578367E+09 | 0.05 | 4622.83 | 0.52 | |
Maximum of Months | 0.343340E+10 | 0.59 | 4622.83 | 0.52 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.778505E+10 | 0.38 | 4024.53 | 01-JAN-00:05 | 0.52 |
February | 0.703220E+10 | 0.38 | 4024.53 | 01-FEB-00:05 | 0.52 |
March | 0.778566E+10 | 0.38 | 4024.53 | 01-MAR-00:05 | 0.52 |
April | 0.756438E+10 | 0.40 | 4024.53 | 01-APR-00:10 | 0.52 |
May | 0.793699E+10 | 0.46 | 4024.53 | 01-MAY-00:20 | 0.52 |
June | 0.794224E+10 | 0.48 | 4024.53 | 01-JUN-00:10 | 0.52 |
July | 0.837215E+10 | 0.50 | 4024.53 | 01-JUL-00:10 | 0.52 |
August | 0.826506E+10 | 0.49 | 4024.53 | 01-AUG-00:10 | 0.52 |
September | 0.777200E+10 | 0.47 | 4024.53 | 01-SEP-00:10 | 0.52 |
October | 0.784551E+10 | 0.42 | 4024.53 | 01-OCT-00:10 | 0.52 |
November | 0.753431E+10 | 0.38 | 4024.53 | 01-NOV-00:20 | 0.52 |
December | 0.778505E+10 | 0.38 | 4024.53 | 01-DEC-00:05 | 0.52 |
Annual Sum or Average | 0.936206E+11 | 0.43 | |||
Minimum of Months | 0.703220E+10 | 0.38 | 4024.53 | 0.52 | |
Maximum of Months | 0.837215E+10 | 0.50 | 4024.53 | 0.52 |
Report: FanReportMonthly
For: ROOM_5_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131895E+10 | 0.40 | 674.50 | 01-JAN-00:05 | 0.52 |
February | 0.118522E+10 | 0.41 | 674.50 | 01-FEB-00:05 | 0.52 |
March | 0.132604E+10 | 0.44 | 674.50 | 01-MAR-00:05 | 0.52 |
April | 0.130630E+10 | 0.46 | 674.50 | 01-APR-00:10 | 0.52 |
May | 0.137982E+10 | 0.50 | 674.50 | 01-MAY-00:20 | 0.52 |
June | 0.137272E+10 | 0.52 | 674.50 | 01-JUN-00:10 | 0.52 |
July | 0.145732E+10 | 0.52 | 674.50 | 01-JUL-00:10 | 0.52 |
August | 0.147265E+10 | 0.53 | 674.50 | 01-AUG-00:10 | 0.52 |
September | 0.136231E+10 | 0.51 | 674.50 | 01-SEP-00:10 | 0.52 |
October | 0.137693E+10 | 0.49 | 674.50 | 01-OCT-00:10 | 0.52 |
November | 0.127389E+10 | 0.42 | 674.50 | 01-NOV-00:10 | 0.52 |
December | 0.131144E+10 | 0.40 | 674.50 | 01-DEC-00:05 | 0.52 |
Annual Sum or Average | 0.161436E+11 | 0.47 | |||
Minimum of Months | 0.118522E+10 | 0.40 | 674.50 | 0.52 | |
Maximum of Months | 0.147265E+10 | 0.53 | 674.50 | 0.52 |
Report: FanReportMonthly
For: ROOM_6_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129286E+10 | 0.42 | 654.95 | 01-JAN-00:05 | 0.52 |
February | 0.115944E+10 | 0.41 | 654.95 | 01-FEB-00:05 | 0.52 |
March | 0.127124E+10 | 0.40 | 654.95 | 01-MAR-00:10 | 0.52 |
April | 0.125092E+10 | 0.44 | 654.95 | 01-APR-00:10 | 0.52 |
May | 0.132649E+10 | 0.48 | 654.95 | 01-MAY-00:10 | 0.52 |
June | 0.132483E+10 | 0.49 | 654.95 | 01-JUN-00:10 | 0.52 |
July | 0.140889E+10 | 0.51 | 654.95 | 01-JUL-00:10 | 0.52 |
August | 0.140625E+10 | 0.51 | 654.95 | 01-AUG-00:10 | 0.52 |
September | 0.129580E+10 | 0.49 | 654.95 | 01-SEP-00:10 | 0.52 |
October | 0.129707E+10 | 0.46 | 654.95 | 01-OCT-00:10 | 0.52 |
November | 0.122731E+10 | 0.39 | 654.95 | 01-NOV-00:10 | 0.52 |
December | 0.127467E+10 | 0.40 | 654.95 | 01-DEC-00:05 | 0.52 |
Annual Sum or Average | 0.155358E+11 | 0.45 | |||
Minimum of Months | 0.115944E+10 | 0.39 | 654.95 | 0.52 | |
Maximum of Months | 0.140889E+10 | 0.51 | 654.95 | 0.52 |
Report: FanReportMonthly
For: ROOM_1_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.401545E+09 | 0.44 | 201.50 | 01-JAN-00:10 | 0.52 |
February | 0.361579E+09 | 0.44 | 201.50 | 01-FEB-00:05 | 0.52 |
March | 0.396234E+09 | 0.43 | 201.50 | 01-MAR-00:05 | 0.52 |
April | 0.388164E+09 | 0.44 | 201.50 | 01-APR-00:10 | 0.52 |
May | 0.409081E+09 | 0.48 | 201.50 | 01-MAY-00:10 | 0.52 |
June | 0.409793E+09 | 0.51 | 201.50 | 01-JUN-00:10 | 0.52 |
July | 0.432977E+09 | 0.52 | 201.50 | 01-JUL-00:10 | 0.52 |
August | 0.436778E+09 | 0.52 | 201.50 | 01-AUG-00:10 | 0.52 |
September | 0.403786E+09 | 0.50 | 201.50 | 01-SEP-00:10 | 0.52 |
October | 0.408426E+09 | 0.47 | 201.50 | 01-OCT-00:10 | 0.52 |
November | 0.379957E+09 | 0.40 | 201.50 | 01-NOV-00:10 | 0.52 |
December | 0.398306E+09 | 0.43 | 201.50 | 01-DEC-00:10 | 0.52 |
Annual Sum or Average | 0.482663E+10 | 0.46 | |||
Minimum of Months | 0.361579E+09 | 0.40 | 201.50 | 0.52 | |
Maximum of Months | 0.436778E+09 | 0.52 | 201.50 | 0.52 |
Report: FanReportMonthly
For: ROOM_2_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.396185E+09 | 0.46 | 195.78 | 01-JAN-00:05 | 0.52 |
February | 0.356915E+09 | 0.45 | 195.78 | 01-FEB-00:05 | 0.52 |
March | 0.382773E+09 | 0.41 | 195.78 | 01-MAR-00:05 | 0.52 |
April | 0.372946E+09 | 0.43 | 195.78 | 01-APR-00:10 | 0.52 |
May | 0.393528E+09 | 0.46 | 195.78 | 01-MAY-00:10 | 0.52 |
June | 0.396153E+09 | 0.49 | 195.78 | 01-JUN-00:10 | 0.52 |
July | 0.419878E+09 | 0.51 | 195.78 | 01-JUL-00:10 | 0.52 |
August | 0.419640E+09 | 0.51 | 195.78 | 01-AUG-00:10 | 0.52 |
September | 0.385605E+09 | 0.47 | 195.78 | 01-SEP-00:10 | 0.52 |
October | 0.388022E+09 | 0.44 | 195.78 | 01-OCT-00:10 | 0.52 |
November | 0.370402E+09 | 0.41 | 195.78 | 01-NOV-00:10 | 0.52 |
December | 0.391957E+09 | 0.45 | 195.78 | 01-DEC-00:05 | 0.52 |
Annual Sum or Average | 0.467400E+10 | 0.46 | |||
Minimum of Months | 0.356915E+09 | 0.41 | 195.78 | 0.52 | |
Maximum of Months | 0.419878E+09 | 0.51 | 195.78 | 0.52 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.187198E+10 | 0.43 | 947.45 | 01-JAN-00:05 | 0.52 |
February | 0.170028E+10 | 0.44 | 947.45 | 01-FEB-00:05 | 0.52 |
March | 0.189002E+10 | 0.44 | 947.45 | 01-MAR-00:05 | 0.52 |
April | 0.183808E+10 | 0.44 | 947.45 | 01-APR-00:20 | 0.52 |
May | 0.191550E+10 | 0.47 | 947.45 | 01-MAY-00:10 | 0.52 |
June | 0.190599E+10 | 0.50 | 947.45 | 01-JUN-00:10 | 0.52 |
July | 0.202725E+10 | 0.52 | 947.45 | 01-JUL-00:10 | 0.52 |
August | 0.206442E+10 | 0.52 | 947.45 | 01-AUG-00:10 | 0.52 |
September | 0.193206E+10 | 0.50 | 947.45 | 01-SEP-00:10 | 0.52 |
October | 0.198804E+10 | 0.48 | 947.45 | 01-OCT-00:10 | 0.52 |
November | 0.181703E+10 | 0.44 | 947.45 | 01-NOV-00:10 | 0.52 |
December | 0.188123E+10 | 0.43 | 947.45 | 01-DEC-00:05 | 0.52 |
Annual Sum or Average | 0.228319E+11 | 0.47 | |||
Minimum of Months | 0.170028E+10 | 0.43 | 947.45 | 0.52 | |
Maximum of Months | 0.206442E+10 | 0.52 | 947.45 | 0.52 |
Report: FanReportMonthly
For: PTAC_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 73644466.18 | 0.05 | 495.43 | 02-JAN-07:10 | 0.52 |
February | 2480044.50 | 0.02 | 92.40 | 20-FEB-13:00 | 0.60 |
March | 0.113342E+09 | 0.27 | 328.68 | 27-MAR-18:03 | 0.58 |
April | 0.299193E+09 | 0.48 | 417.65 | 08-APR-12:30 | 0.58 |
May | 0.555817E+09 | 0.59 | 495.85 | 31-MAY-18:30 | 0.57 |
June | 0.853931E+09 | 0.58 | 685.95 | 19-JUN-18:03 | 0.55 |
July | 0.108836E+10 | 0.58 | 652.79 | 08-JUL-12:30 | 0.56 |
August | 0.106961E+10 | 0.58 | 697.51 | 16-AUG-15:10 | 0.55 |
September | 0.742656E+09 | 0.59 | 568.74 | 07-SEP-14:10 | 0.56 |
October | 0.542766E+09 | 0.58 | 486.34 | 04-OCT-15:10 | 0.57 |
November | 0.130449E+09 | 0.29 | 331.02 | 04-NOV-12:30 | 0.58 |
December | 11129649.53 | 0.05 | 124.74 | 03-DEC-13:00 | 0.60 |
Annual Sum or Average | 0.548338E+10 | 0.39 | |||
Minimum of Months | 2480044.50 | 0.02 | 92.40 | 0.52 | |
Maximum of Months | 0.108836E+10 | 0.59 | 697.51 | 0.60 |
Report: FanReportMonthly
For: PTAC_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.376546E+09 | 0.36 | 407.47 | 02-JAN-07:10 | 0.52 |
February | 0.319958E+09 | 0.33 | 413.61 | 06-FEB-07:10 | 0.52 |
March | 63996660.08 | 0.12 | 263.23 | 23-MAR-06:10 | 0.52 |
April | 0.100535E+09 | 0.26 | 317.04 | 08-APR-12:00 | 0.57 |
May | 0.276551E+09 | 0.54 | 388.91 | 30-MAY-12:20 | 0.56 |
June | 0.482654E+09 | 0.58 | 495.44 | 19-JUN-12:30 | 0.54 |
July | 0.648246E+09 | 0.58 | 489.77 | 08-JUL-12:00 | 0.54 |
August | 0.633730E+09 | 0.58 | 505.49 | 16-AUG-12:50 | 0.54 |
September | 0.387928E+09 | 0.58 | 401.53 | 01-SEP-13:00 | 0.56 |
October | 0.209133E+09 | 0.43 | 326.86 | 04-OCT-12:50 | 0.57 |
November | 92238017.79 | 0.18 | 281.56 | 23-NOV-06:00 | 0.52 |
December | 0.250492E+09 | 0.30 | 300.53 | 31-DEC-24:00 | 0.52 |
Annual Sum or Average | 0.384201E+10 | 0.40 | |||
Minimum of Months | 63996660.08 | 0.12 | 263.23 | 0.52 | |
Maximum of Months | 0.648246E+09 | 0.58 | 505.49 | 0.57 |
Report: FanReportMonthly
For: PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167027E+11 | 1.32 | 6236.08 | 02-JAN-19:10 | 1.33 |
February | 0.150863E+11 | 1.32 | 6236.08 | 01-FEB-04:10 | 1.32 |
March | 0.167027E+11 | 1.32 | 6236.08 | 13-MAR-21:10 | 1.32 |
April | 0.161639E+11 | 1.32 | 6236.08 | 03-APR-17:40 | 1.32 |
May | 0.167027E+11 | 1.32 | 6236.08 | 01-MAY-04:00 | 1.32 |
June | 0.161639E+11 | 1.32 | 6236.08 | 03-JUN-01:20 | 1.32 |
July | 0.167027E+11 | 1.32 | 6236.08 | 01-JUL-02:70 | 1.32 |
August | 0.167027E+11 | 1.32 | 6236.08 | 01-AUG-06:15 | 1.32 |
September | 0.161639E+11 | 1.32 | 6236.08 | 03-SEP-18:03 | 1.32 |
October | 0.167027E+11 | 1.32 | 6236.08 | 03-OCT-21:58 | 1.32 |
November | 0.161639E+11 | 1.32 | 6236.08 | 03-NOV-19:30 | 1.32 |
December | 0.167027E+11 | 1.32 | 6236.08 | 07-DEC-22:50 | 1.32 |
Annual Sum or Average | 0.196661E+12 | 1.32 | |||
Minimum of Months | 0.150863E+11 | 1.32 | 6236.08 | 1.32 | |
Maximum of Months | 0.167027E+11 | 1.32 | 6236.08 | 1.33 |
Report: FanReportMonthly
For: PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.891883E+10 | 1.36 | 3329.91 | 17-JAN-03:40 | 1.36 |
February | 0.805572E+10 | 1.37 | 3329.91 | 20-FEB-18:30 | 1.36 |
March | 0.891883E+10 | 1.36 | 3329.91 | 07-MAR-18:00 | 1.36 |
April | 0.863113E+10 | 1.36 | 3329.91 | 21-APR-16:57 | 1.36 |
May | 0.891883E+10 | 1.35 | 3329.91 | 01-MAY-05:10 | 1.36 |
June | 0.863113E+10 | 1.35 | 3329.91 | 01-JUN-01:00 | 1.35 |
July | 0.891883E+10 | 1.35 | 3329.91 | 09-JUL-15:18 | 1.35 |
August | 0.891883E+10 | 1.35 | 3329.91 | 01-AUG-06:56 | 1.35 |
September | 0.863113E+10 | 1.35 | 3329.91 | 16-SEP-03:40 | 1.35 |
October | 0.891883E+10 | 1.36 | 3329.91 | 01-OCT-21:00 | 1.35 |
November | 0.863113E+10 | 1.36 | 3329.91 | 01-NOV-05:20 | 1.36 |
December | 0.891883E+10 | 1.36 | 3329.91 | 04-DEC-18:03 | 1.36 |
Annual Sum or Average | 0.105012E+12 | 1.36 | |||
Minimum of Months | 0.805572E+10 | 1.35 | 3329.91 | 1.35 | |
Maximum of Months | 0.891883E+10 | 1.37 | 3329.91 | 1.36 |
Report: FanReportMonthly
For: PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114841E+11 | 1.32 | 4287.68 | 17-JAN-01:10 | 1.33 |
February | 0.103727E+11 | 1.33 | 4287.68 | 10-FEB-04:40 | 1.33 |
March | 0.114841E+11 | 1.32 | 4287.68 | 01-MAR-00:05 | 1.32 |
April | 0.111137E+11 | 1.32 | 4287.68 | 06-APR-12:50 | 1.32 |
May | 0.114841E+11 | 1.32 | 4287.68 | 09-MAY-02:30 | 1.32 |
June | 0.111137E+11 | 1.32 | 4287.68 | 03-JUN-08:07 | 1.32 |
July | 0.114841E+11 | 1.32 | 4287.68 | 04-JUL-08:03 | 1.32 |
August | 0.114841E+11 | 1.32 | 4287.68 | 08-AUG-06:25 | 1.32 |
September | 0.111137E+11 | 1.32 | 4287.68 | 02-SEP-18:35 | 1.32 |
October | 0.114841E+11 | 1.32 | 4287.68 | 06-OCT-18:00 | 1.32 |
November | 0.111137E+11 | 1.32 | 4287.68 | 03-NOV-16:38 | 1.32 |
December | 0.114841E+11 | 1.32 | 4287.68 | 14-DEC-04:00 | 1.33 |
Annual Sum or Average | 0.135216E+12 | 1.32 | |||
Minimum of Months | 0.103727E+11 | 1.32 | 4287.68 | 1.32 | |
Maximum of Months | 0.114841E+11 | 1.33 | 4287.68 | 1.33 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.132960E+10 | 0.119664E+10 | 1403.26 | 02-JAN-09:02 | 1262.94 | 1262.94 | 50.73 | 3.16 |
February | 0.127995E+10 | 0.115195E+10 | 1377.49 | 06-FEB-09:02 | 1239.74 | 1239.74 | 48.80 | 2.94 |
March | 0.715921E+09 | 0.644329E+09 | 1290.73 | 16-MAR-15:12 | 1161.65 | 1161.65 | 45.78 | 2.42 |
April | 0.244526E+09 | 0.220074E+09 | 703.44 | 21-APR-15:12 | 633.10 | 633.10 | 31.31 | 0.89 |
May | 18638321.57 | 16774489.41 | 303.03 | 03-MAY-08:05 | 272.73 | 272.73 | 25.81 | 0.33 |
June | 57608.49 | 51847.64 | 175.46 | 02-JUN-08:54 | 157.91 | 157.91 | 24.55 | 0.19 |
July | 12958.82 | 11662.94 | 48.20 | 18-JUL-08:07 | 43.38 | 43.38 | 25.49 | 0.05 |
August | 16097.98 | 14488.18 | 39.81 | 25-AUG-08:54 | 35.83 | 35.83 | 26.00 | 0.04 |
September | 1714716.63 | 1543244.97 | 320.17 | 15-SEP-06:15 | 288.15 | 288.15 | 26.19 | 0.36 |
October | 0.101206E+09 | 91085301.20 | 487.15 | 07-OCT-15:15 | 438.44 | 438.44 | 26.62 | 0.57 |
November | 0.525038E+09 | 0.472535E+09 | 1145.99 | 22-NOV-16:12 | 1031.39 | 1031.39 | 42.42 | 1.86 |
December | 0.101503E+10 | 0.913525E+09 | 1342.58 | 31-DEC-19:02 | 1208.32 | 1208.32 | 50.86 | 2.70 |
Annual Sum or Average | 0.523170E+10 | 0.470853E+10 | ||||||
Minimum of Months | 12958.82 | 11662.94 | 39.81 | 35.83 | 35.83 | 24.55 | 0.04 | |
Maximum of Months | 0.132960E+10 | 0.119664E+10 | 1403.26 | 1262.94 | 1262.94 | 50.86 | 3.16 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.56 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 49.46 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:05 | 14.37 | 14.37 | 49.52 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.58 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 53.04 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.56 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.97 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.18 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.12 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.08 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 53.35 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 50.30 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.56 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.18 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 44.86 | 82.20 | 96255.13 | 415372.92 | 02-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 38.15 | 76.61 | 106090.89 | 411112.52 | 06-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 30.05 | 70.07 | 50339.56 | 293088.83 | 16-MAR-15:12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.60 | 70.31 | 17099.97 | 137480.53 | 21-APR-15:12 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 24.01 | 65.60 | 1224.31 | 55685.17 | 03-MAY-08:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.34 | 24.34 | 3.93 | 32095.49 | 02-JUN-08:54 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.23 | 25.23 | 0.83 | 8331.90 | 18-JUL-08:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.50 | 25.50 | 1.02 | 6779.23 | 25-AUG-08:54 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.05 | 26.05 | 115.36 | 58567.51 | 15-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24.53 | 65.60 | 6754.63 | 92929.03 | 07-OCT-15:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.99 | 65.60 | 37251.69 | 252706.88 | 22-NOV-16:12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 29.18 | 69.62 | 69099.10 | 342489.98 | 31-DEC-19:02 |
Annual Sum or Average | 0.00 | 31612.56 | ||||||
Minimum of Months | 0.00 | 0.00 | 24.01 | 24.34 | 0.83 | 6779.23 | ||
Maximum of Months | 0.00 | 0.00 | 44.86 | 82.20 | 106090.89 | 415372.92 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.56 | 60.05 | 27153.39 | 57317.39 | 31-JAN-07:57 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49.46 | 60.05 | 27426.07 | 57395.58 | 09-FEB-07:53 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 49.52 | 60.05 | 26837.75 | 56951.60 | 01-MAR-07:55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.58 | 60.05 | 25463.19 | 54540.40 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 53.04 | 60.05 | 23715.88 | 51383.93 | 01-MAY-06:54 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.56 | 60.05 | 22054.28 | 47597.87 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 53.97 | 60.05 | 20897.63 | 44445.18 | 03-JUL-06:45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.18 | 60.05 | 20621.69 | 43406.86 | 31-AUG-06:25 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.12 | 60.05 | 21240.63 | 45448.33 | 29-SEP-06:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.08 | 60.05 | 22610.96 | 49006.63 | 31-OCT-06:55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.35 | 60.05 | 24365.37 | 52672.48 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 50.30 | 60.05 | 26022.28 | 55608.86 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 24014.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.56 | 60.05 | 20621.69 | 43406.86 | ||
Maximum of Months | 0.00 | 0.00 | 54.18 | 60.05 | 27426.07 | 57395.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.811583E+11 | 0.00 | 0.00 | 0.104272E+11 | 0.00 | 0.00 |
February | 0.802776E+11 | 0.00 | 0.00 | 0.940562E+10 | 0.00 | 0.00 |
March | 0.442869E+11 | 0.00 | 0.00 | 0.114479E+11 | 0.00 | 0.00 |
April | 0.142554E+11 | 0.00 | 0.00 | 0.162362E+11 | 0.00 | 0.00 |
May | 0.831785E+09 | 0.00 | 0.00 | 0.285399E+11 | 0.00 | 0.00 |
June | 22657.68 | 0.00 | 0.00 | 0.509174E+11 | 0.00 | 0.00 |
July | 73094.96 | 0.00 | 0.00 | 0.713596E+11 | 0.00 | 0.00 |
August | 92867.68 | 0.00 | 0.00 | 0.658440E+11 | 0.00 | 0.00 |
September | 11423353.02 | 0.00 | 0.00 | 0.430319E+11 | 0.00 | 0.00 |
October | 0.524662E+10 | 0.00 | 0.00 | 0.269884E+11 | 0.00 | 0.00 |
November | 0.311572E+11 | 0.00 | 0.00 | 0.120446E+11 | 0.00 | 0.00 |
December | 0.607513E+11 | 0.00 | 0.00 | 0.104430E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.317977E+12 | 0.00 | 0.00 | 0.356686E+12 | 0.00 | 0.00 |
Minimum of Months | 22657.68 | 0.00 | 0.00 | 0.940562E+10 | 0.00 | 0.00 |
Maximum of Months | 0.811583E+11 | 0.00 | 0.00 | 0.713596E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.925214E+11 | 0.00 | 0.00 | 0.105127E+11 | 0.00 | 0.00 |
February | 0.917856E+11 | 0.00 | 0.00 | 0.948589E+10 | 0.00 | 0.00 |
March | 0.572399E+11 | 0.00 | 0.00 | 0.112718E+11 | 0.00 | 0.00 |
April | 0.216767E+11 | 0.00 | 0.00 | 0.151127E+11 | 0.00 | 0.00 |
May | 0.208866E+10 | 0.00 | 0.00 | 0.265447E+11 | 0.00 | 0.00 |
June | 229765.94 | 0.00 | 0.00 | 0.506704E+11 | 0.00 | 0.00 |
July | 201407.78 | 0.00 | 0.00 | 0.725276E+11 | 0.00 | 0.00 |
August | 348256.75 | 0.00 | 0.00 | 0.634151E+11 | 0.00 | 0.00 |
September | 0.247716E+09 | 0.00 | 0.00 | 0.394403E+11 | 0.00 | 0.00 |
October | 0.101538E+11 | 0.00 | 0.00 | 0.231351E+11 | 0.00 | 0.00 |
November | 0.423205E+11 | 0.00 | 0.00 | 0.112836E+11 | 0.00 | 0.00 |
December | 0.738559E+11 | 0.00 | 0.00 | 0.105125E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.391891E+12 | 0.00 | 0.00 | 0.343912E+12 | 0.00 | 0.00 |
Minimum of Months | 201407.78 | 0.00 | 0.00 | 0.948589E+10 | 0.00 | 0.00 |
Maximum of Months | 0.925214E+11 | 0.00 | 0.00 | 0.725276E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.990408E+10 | 0.00 | 0.00 | 0.537717E+10 | 0.00 | 0.00 |
February | 0.171427E+11 | 0.00 | 0.00 | 0.485679E+10 | 0.00 | 0.00 |
March | 0.800587E+10 | 0.00 | 0.00 | 0.537717E+10 | 0.00 | 0.00 |
April | 0.144462E+10 | 0.00 | 0.00 | 0.541739E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.729216E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.170908E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.259660E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.261330E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.204139E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.155803E+11 | 0.00 | 0.00 |
November | 4693402.65 | 0.00 | 0.00 | 0.801429E+10 | 0.00 | 0.00 |
December | 0.311873E+09 | 0.00 | 0.00 | 0.538137E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.368139E+11 | 0.00 | 0.00 | 0.146900E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.485679E+10 | 0.00 | 0.00 |
Maximum of Months | 0.171427E+11 | 0.00 | 0.00 | 0.261330E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.320317E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.289152E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.324414E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.317127E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.332721E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.329675E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.348876E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.349614E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.325929E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.330687E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.314591E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.321594E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.390470E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.289152E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.349614E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.892790E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.805682E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.917793E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.996254E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.126859E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.191292E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.248121E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.238407E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.171284E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.131201E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.891806E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.894794E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164708E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.805682E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.248121E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.203067E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.178203E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.226682E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.245492E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.283976E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.323090E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.373615E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.361209E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.302326E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.273614E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.225025E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.210955E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.320725E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.178203E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.373615E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.104093E+11 | 53309181.30 | 0.811583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.940562E+10 | 0.00 | 0.802776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104428E+11 | 0.321496E+10 | 0.442869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102682E+11 | 0.196422E+11 | 0.142554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110775E+11 | 0.591135E+11 | 0.831785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120086E+11 | 0.149107E+12 | 22657.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134703E+11 | 0.233877E+12 | 73094.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140831E+11 | 0.203706E+12 | 92867.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118906E+11 | 0.115671E+12 | 11423353.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113366E+11 | 0.546352E+11 | 0.524662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101309E+11 | 0.601449E+10 | 0.311572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104185E+11 | 73968757.88 | 0.607513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134942E+12 | 0.845109E+12 | 0.317977E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.940562E+10 | 0.00 | 22657.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140831E+11 | 0.233877E+12 | 0.811583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.105127E+11 | 0.00 | 0.925214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.948589E+10 | 0.00 | 0.917856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107118E+11 | 0.184732E+10 | 0.572399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108738E+11 | 0.142932E+11 | 0.216767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124243E+11 | 0.494061E+11 | 0.208866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136164E+11 | 0.144908E+12 | 229765.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150026E+11 | 0.233680E+12 | 201407.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147634E+11 | 0.193861E+12 | 348256.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124621E+11 | 0.102497E+12 | 0.247716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115267E+11 | 0.416839E+11 | 0.101538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103880E+11 | 0.283260E+10 | 0.423205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105125E+11 | 0.00 | 0.738559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142280E+12 | 0.785009E+12 | 0.391891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.948589E+10 | 0.00 | 201407.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150026E+11 | 0.233680E+12 | 0.925214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.537717E+10 | 0.00 | 0.990408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.485679E+10 | 0.00 | 0.171427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.537717E+10 | 0.00 | 0.800587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520371E+10 | 0.685760E+09 | 0.144462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.537717E+10 | 0.638482E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.522519E+10 | 0.427299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.566996E+10 | 0.776081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.585704E+10 | 0.766680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.536440E+10 | 0.565834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.542516E+10 | 0.372953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.520371E+10 | 0.966882E+10 | 4693402.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537717E+10 | 13141179.33 | 0.311873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643146E+11 | 0.307637E+12 | 0.368139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.485679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.585704E+10 | 0.776081E+11 | 0.171427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167027E+11 | 0.629950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150863E+11 | 0.568393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167027E+11 | 0.648990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161639E+11 | 0.642196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167027E+11 | 0.684171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161639E+11 | 0.679494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167027E+11 | 0.710709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167027E+11 | 0.711288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161639E+11 | 0.671491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167027E+11 | 0.677476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161639E+11 | 0.631021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167027E+11 | 0.635989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196661E+12 | 0.789117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150863E+11 | 0.568393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167027E+11 | 0.711288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.891883E+10 | 31432127.62 | 0.220302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.805572E+10 | 3738675.27 | 0.211526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.891883E+10 | 0.936573E+09 | 0.945502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.863113E+10 | 0.493983E+10 | 0.246375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.891883E+10 | 0.139810E+11 | 8833658.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.863113E+10 | 0.416748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.891883E+10 | 0.656948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.891883E+10 | 0.601687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.863113E+10 | 0.335396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.891883E+10 | 0.162983E+11 | 0.541033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.863113E+10 | 0.103724E+10 | 0.672433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.891883E+10 | 0.103482E+09 | 0.152576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105012E+12 | 0.238409E+12 | 0.776334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.805572E+10 | 3738675.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.891883E+10 | 0.656948E+11 | 0.220302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114841E+11 | 0.350004E+11 | 48088077.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103727E+11 | 0.293628E+11 | 97639187.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114841E+11 | 0.455795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111137E+11 | 0.561394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114841E+11 | 0.718031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111137E+11 | 0.886707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114841E+11 | 0.105395E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114841E+11 | 0.994896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111137E+11 | 0.807728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114841E+11 | 0.672678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111137E+11 | 0.467072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114841E+11 | 0.382218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135216E+12 | 0.764410E+12 | 0.145727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103727E+11 | 0.293628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114841E+11 | 0.105395E+12 | 97639187.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.104093E+11 | 0.811583E+11 | 0.00 | 0.00 | 17855752.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.940562E+10 | 0.802776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104428E+11 | 0.442869E+11 | 0.00 | 0.00 | 0.100510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102682E+11 | 0.142554E+11 | 0.00 | 0.00 | 0.596800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110775E+11 | 0.831785E+09 | 0.00 | 0.00 | 0.174624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120086E+11 | 22657.68 | 0.00 | 0.00 | 0.389088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134703E+11 | 73094.96 | 0.00 | 0.00 | 0.578893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140831E+11 | 92867.68 | 0.00 | 0.00 | 0.517609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118906E+11 | 11423353.02 | 0.00 | 0.00 | 0.311413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113366E+11 | 0.524662E+10 | 0.00 | 0.00 | 0.156518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101309E+11 | 0.311572E+11 | 0.00 | 0.00 | 0.191371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104185E+11 | 0.607513E+11 | 0.00 | 0.00 | 24495208.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134942E+12 | 0.317977E+12 | 0.00 | 0.00 | 0.221744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.940562E+10 | 22657.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140831E+11 | 0.811583E+11 | 0.00 | 0.00 | 0.578893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.105127E+11 | 0.925214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.948589E+10 | 0.917856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107118E+11 | 0.572399E+11 | 0.00 | 0.00 | 0.559978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108738E+11 | 0.216767E+11 | 0.00 | 0.00 | 0.423892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124243E+11 | 0.208866E+10 | 0.00 | 0.00 | 0.141204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136164E+11 | 229765.94 | 0.00 | 0.00 | 0.370540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150026E+11 | 201407.78 | 0.00 | 0.00 | 0.575249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147634E+11 | 348256.75 | 0.00 | 0.00 | 0.486517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124621E+11 | 0.247716E+09 | 0.00 | 0.00 | 0.269782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115267E+11 | 0.101538E+11 | 0.00 | 0.00 | 0.116084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103880E+11 | 0.423205E+11 | 0.00 | 0.00 | 0.895561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105125E+11 | 0.738559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142280E+12 | 0.391891E+12 | 0.00 | 0.00 | 0.201632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.948589E+10 | 201407.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150026E+11 | 0.925214E+11 | 0.00 | 0.00 | 0.575249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.537717E+10 | 0.990408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.485679E+10 | 0.171427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.537717E+10 | 0.800587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520371E+10 | 0.144462E+10 | 0.00 | 0.00 | 0.213681E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.537717E+10 | 0.00 | 0.00 | 0.00 | 0.191499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.522519E+10 | 0.00 | 0.00 | 0.00 | 0.118656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.566996E+10 | 0.00 | 0.00 | 0.00 | 0.202961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.585704E+10 | 0.00 | 0.00 | 0.00 | 0.202759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.536440E+10 | 0.00 | 0.00 | 0.00 | 0.150495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.542516E+10 | 0.00 | 0.00 | 0.00 | 0.101552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.520371E+10 | 4693402.65 | 0.00 | 0.00 | 0.281059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537717E+10 | 0.311873E+09 | 0.00 | 0.00 | 4200711.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643146E+11 | 0.368139E+11 | 0.00 | 0.00 | 0.825857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.485679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.585704E+10 | 0.171427E+11 | 0.00 | 0.00 | 0.202961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.167027E+11 | 0.00 | 0.00 | 0.00 | 0.153290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150863E+11 | 0.00 | 0.00 | 0.00 | 0.138289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167027E+11 | 0.00 | 0.00 | 0.00 | 0.157387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161639E+11 | 0.00 | 0.00 | 0.00 | 0.155488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167027E+11 | 0.00 | 0.00 | 0.00 | 0.165694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161639E+11 | 0.00 | 0.00 | 0.00 | 0.168036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167027E+11 | 0.00 | 0.00 | 0.00 | 0.181849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167027E+11 | 0.00 | 0.00 | 0.00 | 0.182587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161639E+11 | 0.00 | 0.00 | 0.00 | 0.164290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167027E+11 | 0.00 | 0.00 | 0.00 | 0.163660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161639E+11 | 0.00 | 0.00 | 0.00 | 0.152952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167027E+11 | 0.00 | 0.00 | 0.00 | 0.154567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196661E+12 | 0.00 | 0.00 | 0.00 | 0.193809E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150863E+11 | 0.00 | 0.00 | 0.00 | 0.138289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167027E+11 | 0.00 | 0.00 | 0.00 | 0.182587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.891883E+10 | 0.00 | 0.00 | 0.00 | 9066318.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.805572E+10 | 0.00 | 0.00 | 0.00 | 1101888.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.891883E+10 | 0.00 | 0.00 | 0.00 | 0.259095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.863113E+10 | 0.00 | 0.00 | 0.00 | 0.133141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.891883E+10 | 0.00 | 0.00 | 0.00 | 0.376710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.863113E+10 | 0.00 | 0.00 | 0.00 | 0.104981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.891883E+10 | 0.00 | 0.00 | 0.00 | 0.158933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.891883E+10 | 0.00 | 0.00 | 0.00 | 0.149219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.863113E+10 | 0.00 | 0.00 | 0.00 | 0.849726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.891883E+10 | 0.00 | 0.00 | 0.00 | 0.420124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.863113E+10 | 0.00 | 0.00 | 0.00 | 0.286926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.891883E+10 | 0.00 | 0.00 | 0.00 | 29103968.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105012E+12 | 0.00 | 0.00 | 0.00 | 0.596955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.805572E+10 | 0.00 | 0.00 | 0.00 | 1101888.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.891883E+10 | 0.00 | 0.00 | 0.00 | 0.158933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.114841E+11 | 0.00 | 0.00 | 0.00 | 0.882263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103727E+11 | 0.00 | 0.00 | 0.00 | 0.744752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114841E+11 | 0.00 | 0.00 | 0.00 | 0.111841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111137E+11 | 0.00 | 0.00 | 0.00 | 0.134355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114841E+11 | 0.00 | 0.00 | 0.00 | 0.169135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111137E+11 | 0.00 | 0.00 | 0.00 | 0.211953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114841E+11 | 0.00 | 0.00 | 0.00 | 0.258774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.114841E+11 | 0.00 | 0.00 | 0.00 | 0.246368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111137E+11 | 0.00 | 0.00 | 0.00 | 0.191189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114841E+11 | 0.00 | 0.00 | 0.00 | 0.158772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111137E+11 | 0.00 | 0.00 | 0.00 | 0.113888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114841E+11 | 0.00 | 0.00 | 0.00 | 0.961137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135216E+12 | 0.00 | 0.00 | 0.00 | 0.185509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103727E+11 | 0.00 | 0.00 | 0.00 | 0.744752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114841E+11 | 0.00 | 0.00 | 0.00 | 0.258774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.622575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
February | 0.587430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
March | 0.500095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
April | 0.343476E+11 | 104296.49 | 0.00 | 3636044.81 | 24014637.23 | 0.00 | 0.248290E+10 | 0.00 | 0.65 |
May | 0.176443E+11 | 0.466071E+09 | 0.00 | 19805634.76 | 0.00 | 0.00 | 0.988958E+10 | 0.00 | 0.65 |
June | 0.00 | 0.944848E+10 | 0.00 | 28420793.29 | 0.00 | 0.00 | 0.559624E+10 | 0.00 | 0.66 |
July | 0.00 | 0.311452E+11 | 0.00 | 1646576.86 | 0.00 | 0.00 | 0.125687E+09 | 0.00 | 0.65 |
August | 0.00 | 0.254159E+11 | 0.00 | 16644333.67 | 0.00 | 0.00 | 0.161918E+10 | 0.00 | 0.65 |
September | 0.00 | 0.894404E+10 | 0.00 | 54979185.63 | 0.00 | 0.00 | 0.844996E+10 | 0.00 | 0.65 |
October | 19571605.85 | 0.182568E+10 | 0.00 | 83384711.27 | 0.00 | 0.00 | 0.255658E+11 | 0.00 | 0.65 |
November | 0.178481E+11 | 0.00 | 0.00 | 54494639.34 | 0.00 | 0.00 | 0.309963E+11 | 0.00 | 0.65 |
December | 0.564396E+11 | 0.00 | 0.00 | 1407798.36 | 0.00 | 0.00 | 0.259564E+10 | 0.00 | 0.65 |
Annual Sum or Average | 0.297309E+12 | 0.772455E+11 | 0.00 | 0.264420E+09 | 24014637.23 | 0.00 | 0.873213E+11 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.622575E+11 | 0.311452E+11 | 0.00 | 83384711.27 | 24014637.23 | 0.00 | 0.309963E+11 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239960E+10 | 0.00 | 0.00 | 310724.65 | 0.00 | 0.546563E+10 | 0.305254E+09 | 0.00 | 1.41 |
February | 0.258697E+10 | 0.00 | 0.00 | 479352.00 | 0.00 | 0.474200E+10 | 0.486838E+09 | 0.00 | 1.42 |
March | 0.413668E+10 | 605547.48 | 0.00 | 1190331.37 | 0.00 | 0.223034E+10 | 0.702518E+09 | 0.00 | 1.46 |
April | 0.369720E+10 | 6000106.04 | 0.00 | 1880356.36 | 5833.69 | 0.765727E+09 | 0.598395E+09 | 0.00 | 1.48 |
May | 0.266525E+10 | 77919243.36 | 0.00 | 3007777.87 | 7724603.67 | 0.00 | 0.687381E+09 | 0.00 | 1.51 |
June | 0.550997E+09 | 0.140778E+10 | 0.00 | 2241843.04 | 0.196247E+09 | 0.00 | 0.276133E+09 | 0.00 | 1.64 |
July | 23239460.99 | 0.441797E+10 | 0.00 | 366748.86 | 0.326025E+09 | 0.00 | 19939390.46 | 0.00 | 1.77 |
August | 0.292655E+09 | 0.366857E+10 | 0.00 | 2359077.13 | 0.101210E+09 | 0.00 | 0.193632E+09 | 0.00 | 1.94 |
September | 0.116395E+10 | 0.745215E+09 | 0.00 | 4578948.58 | 0.139591E+09 | 0.00 | 0.606263E+09 | 0.00 | 1.76 |
October | 0.284940E+10 | 0.114274E+09 | 0.00 | 4745634.71 | 4473263.98 | 70878127.26 | 0.124374E+10 | 0.00 | 1.73 |
November | 0.406960E+10 | 0.00 | 0.00 | 931278.15 | 0.00 | 0.170409E+10 | 0.474646E+09 | 0.00 | 1.45 |
December | 0.290351E+10 | 0.00 | 0.00 | 632894.95 | 0.00 | 0.421101E+10 | 0.478364E+09 | 0.00 | 1.43 |
Annual Sum or Average | 0.273391E+11 | 0.104383E+11 | 0.00 | 22724967.67 | 0.775277E+09 | 0.191897E+11 | 0.607310E+10 | 0.00 | 1.58 |
Minimum of Months | 23239460.99 | 0.00 | 0.00 | 310724.65 | 0.00 | 0.00 | 19939390.46 | 0.00 | 1.41 |
Maximum of Months | 0.413668E+10 | 0.441797E+10 | 0.00 | 4745634.71 | 0.326025E+09 | 0.546563E+10 | 0.124374E+10 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.723974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
February | 0.689767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
March | 0.590368E+10 | 0.00 | 0.00 | 148126.99 | 451310.05 | 0.00 | 0.245143E+09 | 0.00 | 1.08 |
April | 0.375573E+10 | 413550.29 | 0.00 | 931463.13 | 2085710.12 | 0.00 | 0.702563E+09 | 0.00 | 1.09 |
May | 0.187605E+10 | 33963897.46 | 0.00 | 2510060.40 | 11537417.09 | 0.00 | 0.112222E+10 | 0.00 | 1.11 |
June | 0.152750E+09 | 0.926505E+09 | 0.00 | 2645733.11 | 0.183215E+09 | 0.00 | 0.604896E+09 | 0.00 | 1.14 |
July | 283294.40 | 0.311876E+10 | 0.00 | 585385.05 | 0.137597E+09 | 0.00 | 39800480.58 | 0.00 | 1.14 |
August | 35832900.94 | 0.226934E+10 | 0.00 | 2408241.84 | 66323011.56 | 0.00 | 0.404576E+09 | 0.00 | 1.15 |
September | 0.607177E+09 | 0.472531E+09 | 0.00 | 3128032.85 | 0.102910E+09 | 0.00 | 0.893945E+09 | 0.00 | 1.13 |
October | 0.219216E+10 | 31700974.00 | 0.00 | 2406025.15 | 14348045.22 | 0.00 | 0.126812E+10 | 0.00 | 1.10 |
November | 0.516979E+10 | 0.00 | 0.00 | 208316.30 | 0.00 | 0.00 | 0.300039E+09 | 0.00 | 1.08 |
December | 0.666917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
Annual Sum or Average | 0.405000E+11 | 0.685322E+10 | 0.00 | 14971384.83 | 0.518468E+09 | 0.00 | 0.558129E+10 | 0.00 | 1.10 |
Minimum of Months | 283294.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
Maximum of Months | 0.723974E+10 | 0.311876E+10 | 0.00 | 3128032.85 | 0.183215E+09 | 0.00 | 0.126812E+10 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.544461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564994E+09 | 0.00 | 0.00 | 0.42 |
February | 0.511777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607885E+09 | 0.00 | 0.00 | 0.42 |
March | 0.510397E+10 | 0.00 | 0.00 | 0.00 | 374625.64 | 0.00 | 0.00 | 0.00 | 0.42 |
April | 0.349691E+10 | 0.00 | 0.00 | 320473.08 | 2074598.25 | 0.00 | 0.195181E+09 | 0.00 | 0.43 |
May | 0.184172E+10 | 39255946.97 | 0.00 | 2270027.40 | 4657341.25 | 0.00 | 0.694470E+09 | 0.00 | 0.45 |
June | 0.197306E+09 | 0.110469E+10 | 0.00 | 3278798.03 | 11928281.30 | 0.00 | 0.486367E+09 | 0.00 | 0.52 |
July | 65373.60 | 0.345748E+10 | 0.00 | 694874.31 | 2313438.75 | 0.00 | 37486121.49 | 0.00 | 0.56 |
August | 48928171.88 | 0.249451E+10 | 0.00 | 3096524.81 | 189344.89 | 0.00 | 0.349174E+09 | 0.00 | 0.55 |
September | 0.635444E+09 | 0.533262E+09 | 0.00 | 3326860.63 | 24738426.76 | 0.00 | 0.671669E+09 | 0.00 | 0.49 |
October | 0.233973E+10 | 22265784.28 | 0.00 | 1539928.26 | 15564760.96 | 0.00 | 0.555301E+09 | 0.00 | 0.44 |
November | 0.445056E+10 | 0.00 | 0.00 | 54478.36 | 0.00 | 0.00 | 88095168.44 | 0.00 | 0.42 |
December | 0.553597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.342130E+11 | 0.765146E+10 | 0.00 | 14581964.86 | 61840817.80 | 0.117288E+10 | 0.307774E+10 | 0.00 | 0.46 |
Minimum of Months | 65373.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.553597E+10 | 0.345748E+10 | 0.00 | 3326860.63 | 24738426.76 | 0.607885E+09 | 0.694470E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.723296E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382852E+10 | 0.00 | 0.00 | 0.55 |
February | 0.729749E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360700E+10 | 0.00 | 0.00 | 0.55 |
March | 0.234619E+10 | 0.00 | 0.00 | 0.00 | 283750.27 | 0.151968E+10 | 0.00 | 0.00 | 0.55 |
April | 0.249626E+10 | 0.00 | 0.00 | 0.00 | 1571349.52 | 0.286726E+09 | 0.00 | 0.00 | 0.55 |
May | 0.182348E+10 | 15220359.36 | 0.00 | 119096.65 | 12384124.74 | 0.00 | 9494110.04 | 0.00 | 0.55 |
June | 0.411441E+09 | 0.316729E+09 | 0.00 | 241212.84 | 0.347303E+09 | 0.00 | 33503020.29 | 0.00 | 0.55 |
July | 16935834.42 | 0.143715E+10 | 0.00 | 122654.30 | 0.513626E+09 | 0.00 | 6860913.33 | 0.00 | 0.55 |
August | 0.214706E+09 | 0.116388E+10 | 0.00 | 312272.20 | 0.222015E+09 | 0.00 | 42602457.81 | 0.00 | 0.54 |
September | 0.880645E+09 | 0.108240E+09 | 0.00 | 89163.74 | 0.221256E+09 | 0.00 | 20053330.65 | 0.00 | 0.54 |
October | 0.213667E+10 | 0.00 | 0.00 | 0.00 | 28516936.28 | 0.00 | 0.00 | 0.00 | 0.55 |
November | 0.243695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100061E+10 | 0.00 | 0.00 | 0.55 |
December | 0.138476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280832E+10 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.156011E+11 | 0.304122E+10 | 0.00 | 884399.72 | 0.134696E+10 | 0.130508E+11 | 0.112514E+09 | 0.00 | 0.55 |
Minimum of Months | 16935834.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.249626E+10 | 0.143715E+10 | 0.00 | 312272.20 | 0.513626E+09 | 0.382852E+10 | 42602457.81 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.494987E+11 | 0.00 | 0.00 | 522432.45 | 0.00 | 0.153061E+10 | 0.670496E+09 | 0.00 | 3.26 |
February | 0.473555E+11 | 0.00 | 0.00 | 680778.62 | 0.00 | 0.753872E+09 | 0.125756E+10 | 0.00 | 3.28 |
March | 0.372266E+11 | 0.00 | 0.00 | 6064872.31 | 0.00 | 0.184533E+09 | 0.599158E+10 | 0.00 | 3.27 |
April | 0.198282E+11 | 42723063.91 | 0.00 | 17372305.78 | 0.00 | 0.00 | 0.128475E+11 | 0.00 | 3.30 |
May | 0.273317E+10 | 0.431171E+09 | 0.00 | 39232072.16 | 0.00 | 0.00 | 0.221355E+11 | 0.00 | 3.33 |
June | 0.00 | 0.649572E+10 | 0.00 | 28935740.68 | 0.00 | 0.00 | 0.621804E+10 | 0.00 | 3.35 |
July | 0.00 | 0.202231E+11 | 0.00 | 3704734.22 | 0.00 | 0.00 | 0.339628E+09 | 0.00 | 3.35 |
August | 0.00 | 0.157793E+11 | 0.00 | 17243635.18 | 0.00 | 0.00 | 0.293820E+10 | 0.00 | 3.34 |
September | 0.229285E+09 | 0.357332E+10 | 0.00 | 35572550.31 | 0.00 | 0.00 | 0.115392E+11 | 0.00 | 3.33 |
October | 0.680070E+10 | 0.592428E+09 | 0.00 | 35520576.62 | 0.00 | 0.00 | 0.197088E+11 | 0.00 | 3.31 |
November | 0.299685E+11 | 0.00 | 0.00 | 7679907.81 | 0.00 | 0.00 | 0.925647E+10 | 0.00 | 3.30 |
December | 0.453641E+11 | 0.00 | 0.00 | 1335477.75 | 0.00 | 0.273314E+09 | 0.149766E+10 | 0.00 | 3.29 |
Annual Sum or Average | 0.239005E+12 | 0.471378E+11 | 0.00 | 0.193865E+09 | 0.00 | 0.274232E+10 | 0.944007E+11 | 0.00 | 3.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 522432.45 | 0.00 | 0.00 | 0.339628E+09 | 0.00 | 3.26 |
Maximum of Months | 0.494987E+11 | 0.202231E+11 | 0.00 | 39232072.16 | 0.00 | 0.153061E+10 | 0.221355E+11 | 0.00 | 3.35 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145297E+12 | 0.00 | 0.00 | 598172.20 | 0.00 | 0.00 | 0.385680E+10 | 0.00 | 1.32 |
February | 0.139005E+12 | 0.00 | 0.00 | 301789.47 | 0.00 | 0.00 | 0.310142E+10 | 0.00 | 1.32 |
March | 0.106041E+12 | 0.00 | 0.00 | 8326710.78 | 9297957.36 | 0.00 | 0.206722E+11 | 0.00 | 1.32 |
April | 0.568492E+11 | 45659424.07 | 0.00 | 30164393.61 | 5831125.21 | 0.00 | 0.349437E+11 | 0.00 | 1.33 |
May | 0.149016E+11 | 0.739224E+09 | 0.00 | 75909961.19 | 0.182927E+09 | 0.00 | 0.466706E+11 | 0.00 | 1.35 |
June | 0.853548E+09 | 0.199306E+11 | 0.00 | 71742622.92 | 0.266502E+10 | 0.00 | 0.147060E+11 | 0.00 | 1.39 |
July | 3450584.16 | 0.648500E+11 | 0.00 | 13211919.54 | 0.214513E+10 | 0.00 | 0.860536E+09 | 0.00 | 1.39 |
August | 0.174314E+09 | 0.471365E+11 | 0.00 | 61325395.75 | 0.711558E+09 | 0.00 | 0.911015E+10 | 0.00 | 1.41 |
September | 0.352090E+10 | 0.103888E+11 | 0.00 | 95734863.29 | 0.155095E+10 | 0.00 | 0.276001E+11 | 0.00 | 1.39 |
October | 0.179742E+11 | 0.874637E+09 | 0.00 | 84910208.51 | 0.109440E+09 | 0.00 | 0.537801E+11 | 0.00 | 1.36 |
November | 0.854068E+11 | 0.00 | 0.00 | 14286423.84 | 0.00 | 0.00 | 0.274486E+11 | 0.00 | 1.33 |
December | 0.129715E+12 | 0.00 | 0.00 | 1223042.10 | 0.00 | 0.00 | 0.768292E+10 | 0.00 | 1.32 |
Annual Sum or Average | 0.699742E+12 | 0.143965E+12 | 0.00 | 0.457736E+09 | 0.738015E+10 | 0.00 | 0.250433E+12 | 0.00 | 1.35 |
Minimum of Months | 3450584.16 | 0.00 | 0.00 | 301789.47 | 0.00 | 0.00 | 0.860536E+09 | 0.00 | 1.32 |
Maximum of Months | 0.145297E+12 | 0.648500E+11 | 0.00 | 95734863.29 | 0.266502E+10 | 0.00 | 0.537801E+11 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127037E+09 | 0.00 | 0.00 | 832119.05 | 0.00 | 0.328966E+10 | 0.218227E+09 | 0.00 | 0.34 |
February | 0.129869E+09 | 0.00 | 0.00 | 1555417.36 | 0.00 | 0.290884E+10 | 0.414666E+09 | 0.00 | 0.34 |
March | 99749015.37 | 2001834.61 | 0.00 | 5802229.32 | 0.00 | 0.171181E+10 | 0.114726E+10 | 0.00 | 0.34 |
April | 45772907.57 | 10525292.13 | 0.00 | 9936723.29 | 0.00 | 0.720551E+09 | 0.116760E+10 | 0.00 | 0.35 |
May | 12500586.28 | 89773713.50 | 9167.51 | 15883988.98 | 0.00 | 46935293.58 | 0.913549E+09 | 975.66 | 0.36 |
June | 0.00 | 0.130151E+10 | 283230.76 | 4136484.45 | 0.00 | 89510.97 | 0.119526E+09 | 3804.75 | 0.37 |
July | 0.00 | 0.291976E+10 | 823100.82 | 9451.54 | 0.00 | 0.00 | 2289.88 | 6093.72 | 0.37 |
August | 0.00 | 0.224555E+10 | 209364.18 | 1245216.70 | 0.00 | 0.00 | 24754688.93 | 2036.96 | 0.38 |
September | 0.00 | 0.770791E+09 | 432667.22 | 8521977.55 | 0.00 | 837804.46 | 0.345688E+09 | 2953.69 | 0.36 |
October | 6952398.22 | 0.165184E+09 | 41233.90 | 10031035.40 | 0.00 | 0.263973E+09 | 0.100318E+10 | 2954.61 | 0.36 |
November | 95108537.14 | 0.00 | 0.00 | 3299912.61 | 0.00 | 0.166340E+10 | 0.831956E+09 | 0.00 | 0.34 |
December | 0.120197E+09 | 0.00 | 0.00 | 1308076.94 | 0.00 | 0.274320E+10 | 0.438839E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.637186E+09 | 0.750510E+10 | 1798764.39 | 62562633.21 | 0.00 | 0.133493E+11 | 0.662524E+10 | 18819.38 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 9451.54 | 0.00 | 0.00 | 2289.88 | 0.00 | 0.34 |
Maximum of Months | 0.129869E+09 | 0.291976E+10 | 823100.82 | 15883988.98 | 0.00 | 0.328966E+10 | 0.116760E+10 | 6093.72 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108739E+09 | 0.00 | 0.00 | 302159.82 | 0.00 | 0.347996E+10 | 56790608.54 | 0.00 | 0.34 |
February | 0.117339E+09 | 0.00 | 0.00 | 560922.17 | 0.00 | 0.321089E+10 | 0.132139E+09 | 0.00 | 0.35 |
March | 0.153303E+09 | 0.00 | 0.00 | 3651974.81 | 0.00 | 0.195975E+10 | 0.840362E+09 | 0.00 | 0.34 |
April | 0.153167E+09 | 5735782.99 | 0.00 | 8284729.36 | 0.00 | 0.772671E+09 | 0.106706E+10 | 0.00 | 0.35 |
May | 0.278066E+09 | 53203196.76 | 29573.30 | 14460147.22 | 2609274.53 | 47773323.29 | 0.860761E+09 | 590.30 | 0.35 |
June | 0.220432E+09 | 0.926200E+09 | 116444.23 | 6873041.80 | 76561107.10 | 167597.89 | 0.103411E+09 | 3846.52 | 0.37 |
July | 14601401.56 | 0.248801E+10 | 483430.23 | 546555.31 | 0.149206E+09 | 0.00 | 948972.72 | 2582.24 | 0.37 |
August | 61592523.33 | 0.197870E+10 | 7908.47 | 2912566.69 | 55096355.26 | 69322.27 | 21232059.16 | 1775.65 | 0.37 |
September | 0.275373E+09 | 0.495715E+09 | 76458.09 | 8606548.30 | 50508260.66 | 983502.86 | 0.300544E+09 | 5664.52 | 0.36 |
October | 0.257063E+09 | 57076622.38 | 7394.29 | 9023933.47 | 6720222.47 | 0.307826E+09 | 0.901019E+09 | 3741.87 | 0.35 |
November | 0.139806E+09 | 0.00 | 0.00 | 1668755.51 | 0.00 | 0.189103E+10 | 0.564553E+09 | 0.00 | 0.34 |
December | 0.140839E+09 | 0.00 | 0.00 | 336569.41 | 0.00 | 0.304940E+10 | 93322856.41 | 0.00 | 0.34 |
Annual Sum or Average | 0.192032E+10 | 0.600464E+10 | 721208.61 | 57227903.85 | 0.340702E+09 | 0.147205E+11 | 0.494214E+10 | 18201.11 | 0.35 |
Minimum of Months | 14601401.56 | 0.00 | 0.00 | 302159.82 | 0.00 | 0.00 | 948972.72 | 0.00 | 0.34 |
Maximum of Months | 0.278066E+09 | 0.248801E+10 | 483430.23 | 14460147.22 | 0.149206E+09 | 0.347996E+10 | 0.106706E+10 | 5664.52 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193505E+10 | 0.00 | 0.00 | 4700266.39 | 0.00 | 0.00 | 0.786582E+09 | 0.00 | 0.02 |
February | 0.156708E+10 | 0.00 | 0.00 | 18645687.66 | 0.00 | 0.00 | 0.221794E+10 | 0.00 | 0.03 |
March | 0.106553E+10 | 12029.15 | 0.00 | 37567471.63 | 0.00 | 0.00 | 0.297554E+10 | 0.00 | 0.04 |
April | 0.514810E+09 | 1256209.40 | 0.00 | 62956841.70 | 0.00 | 0.00 | 0.280913E+10 | 0.00 | 0.06 |
May | 32606733.45 | 0.109758E+09 | 0.00 | 93506990.87 | 0.00 | 0.00 | 0.277179E+10 | 0.00 | 0.07 |
June | 0.00 | 0.285871E+10 | 0.00 | 51487711.16 | 0.00 | 0.00 | 0.665813E+09 | 0.00 | 0.10 |
July | 0.00 | 0.828387E+10 | 0.00 | 3064485.77 | 0.00 | 0.00 | 15175663.51 | 0.00 | 0.13 |
August | 0.00 | 0.680819E+10 | 0.00 | 44466688.47 | 0.00 | 0.00 | 0.353535E+09 | 0.00 | 0.14 |
September | 0.00 | 0.167134E+10 | 0.00 | 95465899.81 | 0.00 | 0.00 | 0.179519E+10 | 0.00 | 0.11 |
October | 25149552.37 | 0.322673E+09 | 0.00 | 0.116989E+09 | 0.00 | 0.00 | 0.390931E+10 | 0.00 | 0.10 |
November | 0.116430E+10 | 0.00 | 0.00 | 42913140.49 | 0.00 | 0.00 | 0.278084E+10 | 0.00 | 0.05 |
December | 0.167994E+10 | 0.00 | 0.00 | 23148372.20 | 0.00 | 0.00 | 0.216273E+10 | 0.00 | 0.04 |
Annual Sum or Average | 0.798446E+10 | 0.200558E+11 | 0.00 | 0.594912E+09 | 0.00 | 0.00 | 0.232436E+11 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3064485.77 | 0.00 | 0.00 | 15175663.51 | 0.00 | 0.02 |
Maximum of Months | 0.193505E+10 | 0.828387E+10 | 0.00 | 0.116989E+09 | 0.00 | 0.00 | 0.390931E+10 | 0.00 | 0.14 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.218192E+10 | 0.00 | 0.00 | 14312365.36 | 0.00 | 0.258945E+11 | 0.186604E+11 | 0.00 | 0.38 |
February | 0.213572E+10 | 0.00 | 0.00 | 11488646.16 | 0.00 | 0.270009E+11 | 0.155588E+11 | 0.00 | 0.39 |
March | 0.198991E+10 | 0.00 | 0.00 | 47525172.02 | 1920139.46 | 0.649365E+10 | 0.293588E+11 | 0.00 | 0.38 |
April | 0.170007E+10 | 81581992.72 | 0.00 | 99365118.70 | 0.00 | 0.209523E+09 | 0.228279E+11 | 0.00 | 0.39 |
May | 0.264713E+10 | 0.732135E+09 | 0.00 | 0.171811E+09 | 38356499.98 | 24259221.29 | 0.108113E+11 | 0.00 | 0.40 |
June | 0.233212E+10 | 0.120257E+11 | 0.00 | 0.113380E+09 | 0.766078E+09 | 1439637.48 | 0.127379E+10 | 0.00 | 0.41 |
July | 0.285125E+09 | 0.322000E+11 | 6328904.51 | 18824574.38 | 0.172390E+10 | 0.00 | 61955724.67 | 24541.10 | 0.42 |
August | 0.760136E+09 | 0.252192E+11 | 3507633.55 | 50813383.55 | 0.657817E+09 | 0.00 | 0.265735E+09 | 14926.64 | 0.41 |
September | 0.286069E+10 | 0.656489E+10 | 1194839.17 | 0.138507E+09 | 0.538535E+09 | 5667754.41 | 0.352071E+10 | 4219.80 | 0.40 |
October | 0.304354E+10 | 0.778560E+09 | 98693.48 | 0.126189E+09 | 54979654.22 | 51208631.89 | 0.147329E+11 | 3265.02 | 0.39 |
November | 0.176141E+10 | 0.00 | 0.00 | 47649286.86 | 0.00 | 0.604541E+10 | 0.251517E+11 | 0.00 | 0.39 |
December | 0.208593E+10 | 0.00 | 0.00 | 17799464.39 | 0.00 | 0.170744E+11 | 0.234188E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.237837E+11 | 0.776021E+11 | 11130070.70 | 0.857665E+09 | 0.378158E+10 | 0.828009E+11 | 0.165643E+12 | 46952.57 | 0.40 |
Minimum of Months | 0.285125E+09 | 0.00 | 0.00 | 11488646.16 | 0.00 | 0.00 | 61955724.67 | 0.00 | 0.38 |
Maximum of Months | 0.304354E+10 | 0.322000E+11 | 6328904.51 | 0.171811E+09 | 0.172390E+10 | 0.270009E+11 | 0.293588E+11 | 24541.10 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134488E+09 | 0.00 | 0.00 | 856995.47 | 0.00 | 0.322267E+10 | 0.267940E+09 | 0.00 | 0.34 |
February | 0.133426E+09 | 0.00 | 0.00 | 1519857.32 | 0.00 | 0.279338E+10 | 0.514159E+09 | 0.00 | 0.34 |
March | 68536349.52 | 1266847.65 | 0.00 | 5581009.31 | 0.00 | 0.172564E+10 | 0.116818E+10 | 0.00 | 0.34 |
April | 37712764.63 | 12696707.38 | 0.00 | 10241606.46 | 0.00 | 0.737486E+09 | 0.116518E+10 | 0.00 | 0.35 |
May | 12384141.80 | 96496938.70 | 38921.31 | 16312322.43 | 0.00 | 57051306.24 | 0.915099E+09 | 2921.66 | 0.36 |
June | 0.00 | 0.128236E+10 | 418753.98 | 5134424.72 | 0.00 | 3567.02 | 0.122871E+09 | 7582.14 | 0.37 |
July | 0.00 | 0.294274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.226848E+10 | 107787.99 | 1696720.97 | 0.00 | 0.00 | 25918476.42 | 1459.88 | 0.38 |
September | 0.00 | 0.769368E+09 | 235761.73 | 8986513.35 | 0.00 | 551109.44 | 0.346408E+09 | 6400.99 | 0.37 |
October | 7349576.05 | 0.164695E+09 | 72765.09 | 10321794.71 | 0.00 | 0.283747E+09 | 0.991230E+09 | 3896.84 | 0.36 |
November | 94437899.56 | 58602.73 | 0.00 | 4225874.89 | 0.00 | 0.159794E+10 | 0.892780E+09 | 0.00 | 0.34 |
December | 0.129925E+09 | 0.00 | 0.00 | 1749899.04 | 0.00 | 0.268847E+10 | 0.475830E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.618259E+09 | 0.753816E+10 | 873990.10 | 66627018.67 | 0.00 | 0.131069E+11 | 0.688559E+10 | 22261.50 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.134488E+09 | 0.294274E+10 | 418753.98 | 16312322.43 | 0.00 | 0.322267E+10 | 0.116818E+10 | 7582.14 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 92111300.43 | 0.00 | 0.00 | 295990.11 | 0.00 | 0.344345E+10 | 0.104695E+09 | 0.00 | 0.35 |
February | 0.105074E+09 | 0.00 | 0.00 | 493306.58 | 0.00 | 0.316466E+10 | 0.176184E+09 | 0.00 | 0.34 |
March | 0.142461E+09 | 0.00 | 0.00 | 2998573.63 | 0.00 | 0.195808E+10 | 0.847517E+09 | 0.00 | 0.34 |
April | 0.118865E+09 | 7842326.98 | 0.00 | 8355671.36 | 0.00 | 0.769591E+09 | 0.108531E+10 | 0.00 | 0.35 |
May | 0.242229E+09 | 57212902.25 | 0.00 | 15946587.83 | 2704490.61 | 65055809.07 | 0.858266E+09 | 0.00 | 0.36 |
June | 0.210306E+09 | 0.911731E+09 | 28123.84 | 9027487.95 | 68033574.04 | 130457.54 | 0.111491E+09 | 446.02 | 0.37 |
July | 17162920.71 | 0.250053E+10 | 53376.27 | 939171.38 | 0.136806E+09 | 0.00 | 3016407.53 | 652.95 | 0.38 |
August | 62422784.44 | 0.199160E+10 | 18509.44 | 4440947.70 | 50738765.88 | 0.00 | 33694576.25 | 3203.28 | 0.38 |
September | 0.243690E+09 | 0.493781E+09 | 20650.42 | 10982471.87 | 46923811.00 | 613935.32 | 0.306927E+09 | 196.46 | 0.36 |
October | 0.219862E+09 | 62836899.95 | 0.00 | 8796699.97 | 6314885.81 | 0.338820E+09 | 0.878380E+09 | 0.00 | 0.35 |
November | 0.138335E+09 | 0.00 | 0.00 | 2242914.75 | 0.00 | 0.176356E+10 | 0.682937E+09 | 0.00 | 0.34 |
December | 0.134983E+09 | 0.00 | 0.00 | 499523.88 | 0.00 | 0.293817E+10 | 0.206679E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.172750E+10 | 0.602553E+10 | 120659.97 | 65019347.01 | 0.311521E+09 | 0.144421E+11 | 0.529510E+10 | 4498.72 | 0.35 |
Minimum of Months | 17162920.71 | 0.00 | 0.00 | 295990.11 | 0.00 | 0.00 | 3016407.53 | 0.00 | 0.34 |
Maximum of Months | 0.243690E+09 | 0.250053E+10 | 53376.27 | 15946587.83 | 0.136806E+09 | 0.344345E+10 | 0.108531E+10 | 3203.28 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162270E+10 | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.00 | 114416.43 | 0.00 | 0.00 | 59975097.33 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 6027268.23 | 0.00 | 0.00 | 0.177985E+10 | 0.00 | 0.01 |
April | 0.00 | 664854.69 | 0.00 | 17935333.35 | 0.00 | 0.00 | 0.273951E+10 | 0.00 | 0.03 |
May | 0.00 | 0.122183E+09 | 0.00 | 32785521.00 | 0.00 | 0.00 | 0.293669E+10 | 0.00 | 0.06 |
June | 0.00 | 0.259673E+10 | 0.00 | 17659726.01 | 0.00 | 0.00 | 0.731196E+09 | 0.00 | 0.10 |
July | 0.00 | 0.724877E+10 | 0.00 | 888005.15 | 0.00 | 0.00 | 23852298.85 | 0.00 | 0.12 |
August | 0.00 | 0.568808E+10 | 0.00 | 13494660.01 | 0.00 | 0.00 | 0.404733E+09 | 0.00 | 0.12 |
September | 0.00 | 0.135879E+10 | 0.00 | 24962023.88 | 0.00 | 0.00 | 0.148720E+10 | 0.00 | 0.08 |
October | 0.00 | 0.218510E+09 | 0.00 | 25746119.45 | 0.00 | 0.00 | 0.276668E+10 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.00 | 6800738.16 | 0.00 | 0.00 | 0.156803E+10 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 468793.53 | 0.00 | 0.00 | 0.251437E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.172337E+11 | 0.00 | 0.146883E+09 | 0.00 | 0.162270E+10 | 0.147492E+11 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.724877E+10 | 0.00 | 32785521.00 | 0.00 | 0.162270E+10 | 0.293669E+10 | 0.00 | 0.12 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26784534.56 | 0.00 | 0.00 | 124021.30 | 0.00 | 0.880157E+09 | 17995415.12 | 0.00 | 0.35 |
February | 27753836.25 | 0.00 | 0.00 | 234160.18 | 0.00 | 0.815788E+09 | 32997088.00 | 0.00 | 0.35 |
March | 23880859.82 | 462930.97 | 0.00 | 1035319.85 | 0.00 | 0.588112E+09 | 0.136741E+09 | 0.00 | 0.34 |
April | 12779541.24 | 2431782.72 | 0.00 | 2018538.61 | 0.00 | 0.322624E+09 | 0.165162E+09 | 0.00 | 0.35 |
May | 3428501.21 | 21675223.00 | 672.84 | 3590202.70 | 0.00 | 70578092.00 | 0.192554E+09 | 52.73 | 0.36 |
June | 0.00 | 0.316063E+09 | 36635.41 | 1038131.51 | 0.00 | 46994.57 | 32108128.98 | 788.81 | 0.37 |
July | 0.00 | 0.728283E+09 | 137655.87 | 4513.66 | 0.00 | 0.00 | 1059.63 | 1519.72 | 0.38 |
August | 0.00 | 0.560970E+09 | 31314.71 | 291001.66 | 0.00 | 0.00 | 7535370.50 | 457.55 | 0.38 |
September | 10861.25 | 0.185037E+09 | 62911.12 | 1895863.12 | 0.00 | 12530954.82 | 84775577.91 | 709.32 | 0.36 |
October | 3337106.65 | 35369425.88 | 5334.68 | 1974742.88 | 0.00 | 0.156865E+09 | 0.176353E+09 | 10.66 | 0.36 |
November | 24753538.18 | 0.00 | 0.00 | 449360.06 | 0.00 | 0.551412E+09 | 85909403.58 | 0.00 | 0.34 |
December | 25869561.66 | 0.00 | 0.00 | 152705.54 | 0.00 | 0.788106E+09 | 23470821.61 | 0.00 | 0.35 |
Annual Sum or Average | 0.148598E+09 | 0.185029E+10 | 274524.64 | 12808561.06 | 0.00 | 0.418622E+10 | 0.955603E+09 | 3538.78 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4513.66 | 0.00 | 0.00 | 1059.63 | 0.00 | 0.34 |
Maximum of Months | 27753836.25 | 0.728283E+09 | 137655.87 | 3590202.70 | 0.00 | 0.880157E+09 | 0.192554E+09 | 1519.72 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15527720.77 | 0.00 | 0.00 | 24693.95 | 0.00 | 0.915358E+09 | 2699279.10 | 0.00 | 0.35 |
February | 18029588.46 | 0.00 | 0.00 | 73444.10 | 0.00 | 0.852260E+09 | 14807935.33 | 0.00 | 0.35 |
March | 34536998.01 | 0.00 | 0.00 | 595529.91 | 0.00 | 0.629085E+09 | 85909167.45 | 0.00 | 0.34 |
April | 38187178.75 | 1348469.74 | 0.00 | 1679194.99 | 0.00 | 0.326531E+09 | 0.150160E+09 | 0.00 | 0.35 |
May | 70379331.21 | 13545264.58 | 2917.78 | 3361198.96 | 637759.66 | 62499166.29 | 0.184720E+09 | 827.61 | 0.35 |
June | 57352336.97 | 0.234608E+09 | 23594.02 | 1757272.53 | 18174121.34 | 39996.43 | 26805844.79 | 712.16 | 0.37 |
July | 4070497.70 | 0.628716E+09 | 118082.87 | 155888.41 | 35569696.57 | 0.00 | 463943.91 | 2828.11 | 0.38 |
August | 15610657.38 | 0.499707E+09 | 40999.59 | 701866.07 | 13130117.95 | 9534.96 | 5928956.63 | 2384.54 | 0.38 |
September | 70019958.71 | 0.123160E+09 | 41054.25 | 1967466.43 | 11674811.69 | 7448871.92 | 75310335.78 | 1161.01 | 0.36 |
October | 68575903.61 | 12648221.33 | 6894.13 | 1754200.54 | 1584429.58 | 0.173317E+09 | 0.140386E+09 | 790.98 | 0.35 |
November | 28384313.34 | 0.00 | 0.00 | 172941.79 | 0.00 | 0.595435E+09 | 43760635.39 | 0.00 | 0.34 |
December | 18812048.69 | 0.00 | 0.00 | 17376.55 | 0.00 | 0.820826E+09 | 1401606.75 | 0.00 | 0.35 |
Annual Sum or Average | 0.439487E+09 | 0.151373E+10 | 233542.65 | 12261074.22 | 80770936.78 | 0.438281E+10 | 0.732353E+09 | 8704.41 | 0.36 |
Minimum of Months | 4070497.70 | 0.00 | 0.00 | 17376.55 | 0.00 | 0.00 | 463943.91 | 0.00 | 0.34 |
Maximum of Months | 70379331.21 | 0.628716E+09 | 118082.87 | 3361198.96 | 35569696.57 | 0.915358E+09 | 0.184720E+09 | 2828.11 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144889E+09 | 0.00 | 0.00 | 3971817.72 | 0.00 | 0.499114E+10 | 0.876618E+09 | 0.00 | 0.39 |
February | 79403328.93 | 0.00 | 0.00 | 5499118.95 | 0.00 | 0.433890E+10 | 0.134435E+10 | 0.00 | 0.40 |
March | 88881437.44 | 2651634.74 | 0.00 | 9471367.29 | 0.00 | 0.294771E+10 | 0.187189E+10 | 0.00 | 0.40 |
April | 70726457.75 | 17104226.06 | 0.00 | 12239402.70 | 0.00 | 0.149726E+10 | 0.166675E+10 | 0.00 | 0.40 |
May | 20080722.84 | 0.122074E+09 | 109377.09 | 18398436.93 | 0.00 | 0.202450E+09 | 0.149659E+10 | 3223.96 | 0.40 |
June | 0.00 | 0.185440E+10 | 582579.04 | 5627456.97 | 0.00 | 288233.81 | 0.227643E+09 | 19452.78 | 0.42 |
July | 0.00 | 0.452897E+10 | 1470469.99 | 23095.55 | 0.00 | 0.00 | 8871.05 | 10526.28 | 0.43 |
August | 0.00 | 0.353964E+10 | 694815.16 | 2033309.16 | 0.00 | 65013.73 | 56766125.85 | 11748.19 | 0.43 |
September | 0.00 | 0.117191E+10 | 591836.64 | 13083166.42 | 0.00 | 16820667.28 | 0.592309E+09 | 11618.89 | 0.42 |
October | 11077657.67 | 0.258063E+09 | 61092.13 | 17495733.52 | 0.00 | 0.512973E+09 | 0.165390E+10 | 1712.60 | 0.42 |
November | 96485090.73 | 33766.20 | 0.00 | 8477622.68 | 0.00 | 0.260422E+10 | 0.159334E+10 | 0.00 | 0.40 |
December | 0.135614E+09 | 0.00 | 0.00 | 6086899.77 | 0.00 | 0.414515E+10 | 0.122759E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.647158E+09 | 0.114948E+11 | 3510170.05 | 0.102407E+09 | 0.00 | 0.212570E+11 | 0.126077E+11 | 58282.70 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23095.55 | 0.00 | 0.00 | 8871.05 | 0.00 | 0.39 |
Maximum of Months | 0.144889E+09 | 0.452897E+10 | 1470469.99 | 18398436.93 | 0.00 | 0.499114E+10 | 0.187189E+10 | 19452.78 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.484333E+11 | 0.00 | 0.00 | 13271328.10 | 0.00 | 0.00 | 0.511072E+11 | 0.00 | 4.32 |
February | 0.480144E+11 | 0.00 | 0.00 | 11099959.13 | 0.00 | 0.00 | 0.459188E+11 | 0.00 | 4.32 |
March | 0.216122E+11 | 0.00 | 0.00 | 27422314.22 | 0.00 | 0.00 | 0.639334E+11 | 0.00 | 4.33 |
April | 0.680471E+10 | 14268002.36 | 0.00 | 48551151.50 | 0.00 | 0.00 | 0.566924E+11 | 0.00 | 4.33 |
May | 0.494615E+09 | 0.372465E+09 | 0.00 | 85197011.81 | 505770.42 | 0.00 | 0.432734E+11 | 0.00 | 4.33 |
June | 35687002.29 | 0.128638E+11 | 0.00 | 57506595.37 | 0.140814E+09 | 0.00 | 0.115747E+11 | 0.00 | 4.32 |
July | 0.00 | 0.402380E+11 | 0.00 | 9434190.74 | 56840113.91 | 0.00 | 0.773945E+09 | 0.00 | 4.32 |
August | 16178473.82 | 0.280433E+11 | 0.00 | 43874501.43 | 25013135.10 | 0.00 | 0.711072E+10 | 0.00 | 4.32 |
September | 0.302137E+09 | 0.628047E+10 | 0.00 | 65853471.00 | 0.118916E+09 | 0.00 | 0.220792E+11 | 0.00 | 4.32 |
October | 0.287064E+10 | 0.381252E+09 | 0.00 | 57180594.67 | 29532701.28 | 0.00 | 0.454250E+11 | 0.00 | 4.33 |
November | 0.204372E+11 | 0.00 | 0.00 | 26576220.67 | 0.00 | 0.00 | 0.551780E+11 | 0.00 | 4.33 |
December | 0.362414E+11 | 0.00 | 0.00 | 16127940.81 | 0.00 | 0.00 | 0.553332E+11 | 0.00 | 4.33 |
Annual Sum or Average | 0.185262E+12 | 0.881936E+11 | 0.00 | 0.462095E+09 | 0.371622E+09 | 0.00 | 0.458400E+12 | 0.00 | 4.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 9434190.74 | 0.00 | 0.00 | 0.773945E+09 | 0.00 | 4.32 |
Maximum of Months | 0.484333E+11 | 0.402380E+11 | 0.00 | 85197011.81 | 0.140814E+09 | 0.00 | 0.639334E+11 | 0.00 | 4.33 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.392991E+11 | 0.00 | 0.00 | 20265301.15 | 0.00 | 0.00 | 0.605114E+11 | 0.00 | 4.34 |
February | 0.374960E+11 | 0.00 | 0.00 | 17281605.95 | 0.00 | 0.00 | 0.566314E+11 | 0.00 | 4.34 |
March | 0.138381E+11 | 0.00 | 0.00 | 38840682.60 | 0.00 | 0.00 | 0.726721E+11 | 0.00 | 4.38 |
April | 0.235324E+10 | 14290436.00 | 0.00 | 62445897.14 | 0.00 | 0.00 | 0.625948E+11 | 0.00 | 4.44 |
May | 0.184168E+09 | 0.398053E+09 | 0.00 | 98575203.91 | 72731.15 | 0.00 | 0.453702E+11 | 0.00 | 4.50 |
June | 4874364.76 | 0.136708E+11 | 0.00 | 63092375.46 | 28025446.18 | 0.00 | 0.121740E+11 | 0.00 | 4.54 |
July | 0.00 | 0.425480E+11 | 0.00 | 10186277.65 | 0.00 | 0.00 | 0.806226E+09 | 0.00 | 4.55 |
August | 0.00 | 0.296608E+11 | 0.00 | 48589544.74 | 0.00 | 0.00 | 0.745267E+10 | 0.00 | 4.55 |
September | 0.122824E+09 | 0.665270E+10 | 0.00 | 74659516.98 | 20171222.95 | 0.00 | 0.232207E+11 | 0.00 | 4.51 |
October | 0.967605E+09 | 0.393659E+09 | 0.00 | 70009055.84 | 20539774.42 | 0.00 | 0.485101E+11 | 0.00 | 4.44 |
November | 0.131261E+11 | 0.00 | 0.00 | 36495957.25 | 0.00 | 0.00 | 0.633452E+11 | 0.00 | 4.38 |
December | 0.266321E+11 | 0.00 | 0.00 | 24523405.11 | 0.00 | 0.00 | 0.652366E+11 | 0.00 | 4.35 |
Annual Sum or Average | 0.134024E+12 | 0.933384E+11 | 0.00 | 0.564965E+09 | 68809174.70 | 0.00 | 0.518525E+12 | 0.00 | 4.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 10186277.65 | 0.00 | 0.00 | 0.806226E+09 | 0.00 | 4.34 |
Maximum of Months | 0.392991E+11 | 0.425480E+11 | 0.00 | 98575203.91 | 28025446.18 | 0.00 | 0.726721E+11 | 0.00 | 4.55 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.100256E+09 | 0.00 | 0.00 | 0.410912E+11 | 0.00 | 4.27 |
February | 57968558.80 | 0.00 | 0.00 | 90864468.34 | 0.00 | 0.00 | 0.396858E+11 | 0.00 | 4.30 |
March | 0.00 | 0.00 | 0.00 | 0.107448E+09 | 0.00 | 0.00 | 0.339508E+11 | 0.00 | 4.28 |
April | 0.00 | 336874.46 | 0.00 | 0.115713E+09 | 0.00 | 0.00 | 0.236487E+11 | 0.00 | 4.29 |
May | 0.00 | 0.123443E+09 | 0.00 | 0.137209E+09 | 0.00 | 0.00 | 0.144009E+11 | 0.00 | 4.30 |
June | 0.00 | 0.537180E+10 | 0.00 | 63302504.43 | 0.00 | 0.00 | 0.298128E+10 | 0.00 | 4.32 |
July | 0.00 | 0.148736E+11 | 0.00 | 4542656.65 | 0.00 | 0.00 | 61031414.64 | 0.00 | 4.31 |
August | 0.00 | 0.102985E+11 | 0.00 | 46153416.72 | 0.00 | 0.00 | 0.143750E+10 | 0.00 | 4.31 |
September | 0.00 | 0.278063E+10 | 0.00 | 92474095.15 | 0.00 | 0.00 | 0.665005E+10 | 0.00 | 4.29 |
October | 0.00 | 0.219496E+09 | 0.00 | 0.116355E+09 | 0.00 | 0.00 | 0.170129E+11 | 0.00 | 4.29 |
November | 0.00 | 0.00 | 0.00 | 0.100820E+09 | 0.00 | 0.00 | 0.298697E+11 | 0.00 | 4.30 |
December | 0.00 | 0.00 | 0.00 | 0.102421E+09 | 0.00 | 0.00 | 0.387604E+11 | 0.00 | 4.31 |
Annual Sum or Average | 57968558.80 | 0.336678E+11 | 0.00 | 0.107756E+10 | 0.00 | 0.00 | 0.249550E+12 | 0.00 | 4.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4542656.65 | 0.00 | 0.00 | 61031414.64 | 0.00 | 4.27 |
Maximum of Months | 57968558.80 | 0.148736E+11 | 0.00 | 0.137209E+09 | 0.00 | 0.00 | 0.410912E+11 | 0.00 | 4.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274899E+10 | 0.00 | 0.00 | 0.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246928E+10 | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.00 | 642786.03 | 0.00 | 0.466735E+09 | 79374344.97 | 0.00 | 0.01 |
April | 0.00 | 709818.63 | 0.00 | 5414613.05 | 0.00 | 3057932.93 | 0.287116E+09 | 0.00 | 0.02 |
May | 0.00 | 46455995.37 | 0.00 | 14170020.17 | 0.00 | 0.00 | 0.534316E+09 | 0.00 | 0.05 |
June | 0.00 | 0.799809E+09 | 0.00 | 7758484.59 | 0.00 | 0.00 | 0.144199E+09 | 0.00 | 0.09 |
July | 0.00 | 0.217729E+10 | 0.00 | 373633.69 | 0.00 | 0.00 | 3721768.90 | 0.00 | 0.12 |
August | 0.00 | 0.169585E+10 | 0.00 | 5732870.44 | 0.00 | 0.00 | 73797890.19 | 0.00 | 0.12 |
September | 0.00 | 0.379170E+09 | 0.00 | 10385988.85 | 0.00 | 0.00 | 0.270841E+09 | 0.00 | 0.07 |
October | 0.00 | 62513148.73 | 0.00 | 7524970.45 | 0.00 | 0.00 | 0.348699E+09 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 | 926874.03 | 0.00 | 0.538835E+09 | 0.109830E+09 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182283E+10 | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.516180E+10 | 0.00 | 52930241.29 | 0.00 | 0.804973E+10 | 0.185189E+10 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.217729E+10 | 0.00 | 14170020.17 | 0.00 | 0.274899E+10 | 0.534316E+09 | 0.00 | 0.12 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:24:38
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.139418E+12 | 0.206152E+11 | 0.294557E+12 | 0.403899E+12 | 0.261365E+12 |
February | 0.220429E+12 | 0.198744E+11 | 0.283703E+12 | 0.383388E+12 | 0.249636E+12 |
March | 0.385549E+12 | 0.176516E+11 | 0.243078E+12 | 0.342663E+12 | 0.279593E+12 |
April | 0.406661E+12 | 0.123742E+11 | 0.168751E+12 | 0.253956E+12 | 0.353039E+12 |
May | 0.524659E+12 | 0.756352E+10 | 0.999764E+11 | 0.178664E+12 | 0.566398E+12 |
June | 0.510636E+12 | -0.207920E+10 | -0.269218E+11 | -0.762497E+10 | 0.104073E+13 |
July | 0.483957E+12 | -0.929531E+10 | -0.127491E+12 | -0.166842E+12 | 0.150049E+13 |
August | 0.460291E+12 | -0.570129E+10 | -0.811374E+11 | -0.980660E+11 | 0.137990E+13 |
September | 0.316941E+12 | 0.165825E+10 | 0.239759E+11 | 0.537635E+11 | 0.890787E+12 |
October | 0.309948E+12 | 0.881383E+10 | 0.116793E+12 | 0.193509E+12 | 0.590754E+12 |
November | 0.153571E+12 | 0.155083E+11 | 0.213770E+12 | 0.309430E+12 | 0.280926E+12 |
December | 0.107796E+12 | 0.190663E+11 | 0.276462E+12 | 0.373189E+12 | 0.254248E+12 |
Annual Sum or Average | 0.401986E+13 | 0.106050E+12 | 0.148552E+13 | 0.221993E+13 | 0.764787E+13 |
Minimum of Months | 0.107796E+12 | -0.929531E+10 | -0.127491E+12 | -0.166842E+12 | 0.249636E+12 |
Maximum of Months | 0.524659E+12 | 0.206152E+11 | 0.294557E+12 | 0.403899E+12 | 0.150049E+13 |