Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2024-07-03 12:25:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10971.25 | 967.03 | 967.03 |
Net Site Energy | 10971.25 | 967.03 | 967.03 |
Total Source Energy | 25253.37 | 2225.89 | 2225.89 |
Net Source Energy | 25253.37 | 2225.89 | 2225.89 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 172.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 974.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 322.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1661.82 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 841.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1041.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2596.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 44.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6414.08 | 4557.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 170.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 974.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 322.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 15.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 11.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 22.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 789.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1041.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 2596.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 21.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 172.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 974.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1526.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 322.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1661.82 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 841.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1041.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 2.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 2596.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 44.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 162.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 177.83 | 244.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.59 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 565.35 | 401.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 162.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 177.83 | 244.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 224.59 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 565.35 | 401.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6414.082 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6414.082 | 100.00 |
Total On-Site and Utility Electric Sources | 6414.082 | 100.00 |
Total Electricity End Uses | 6414.082 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 116.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8311.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 PTAC COOLING COIL | ROOM_2_FLR_3 PTAC COOLING COIL | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | ROOM_5_FLR_3 PTAC COOLING COIL | ROOM_6_FLR_3 PTAC COOLING COIL | ROOM_1_FLR_6 PTAC COOLING COIL | ROOM_2_FLR_6 PTAC COOLING COIL | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | PTAC_3 PTAC COOLING COIL | PTAC_6 PTAC COOLING COIL | VAV_FLR_1 COOLING COIL | VAV_FLR_6 COOLING COIL | VAV_FLR_0 COOLING COIL | PSZ_LAUNDRY COOLING COIL | PSZ_CAFE COOLING COIL | PSZ_KITCHEN COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH LAUNDRY G WATER HEATER | SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV_FLR_1 HEATING COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | VAV_FLR_6 HEATING COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | ROOM_1_FLR_3 HEATING COIL | ROOM_2_FLR_3 HEATING COIL | ROOM_3_MULT19_FLR_3 HEATING COIL | ROOM_4_MULT19_FLR_3 HEATING COIL | ROOM_5_FLR_3 HEATING COIL | ROOM_6_FLR_3 HEATING COIL | ROOM_1_FLR_6 HEATING COIL | ROOM_2_FLR_6 HEATING COIL | ROOM_3_MULT9_FLR_6 HEATING COIL | VAV_FLR_0 HEATING COIL | PTAC_3 HEATING COIL | PTAC_6 HEATING COIL | PSZ_LAUNDRY HEATING COIL | PSZ_CAFE HEATING COIL | PSZ_KITCHEN HEATING COIL | ROOM_1_FLR_3 PTAC COOLING COIL | ROOM_2_FLR_3 PTAC COOLING COIL | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | ROOM_5_FLR_3 PTAC COOLING COIL | ROOM_6_FLR_3 PTAC COOLING COIL | ROOM_1_FLR_6 PTAC COOLING COIL | ROOM_2_FLR_6 PTAC COOLING COIL | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | PTAC_3 PTAC COOLING COIL | PTAC_6 PTAC COOLING COIL | VAV_FLR_1 COOLING COIL | VAV_FLR_6 COOLING COIL | VAV_FLR_0 COOLING COIL | PSZ_LAUNDRY COOLING COIL | PSZ_CAFE COOLING COIL | PSZ_KITCHEN COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| VAV_FLR_1 FAN | VAV_FLR_6 FAN | VAV_FLR_0 SZVAV FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | LAUNDRY_FLR_1 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3_PTAC_SUPPLY FAN | ROOM_2_FLR_3_PTAC_SUPPLY FAN | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | ROOM_5_FLR_3_PTAC_SUPPLY FAN | ROOM_6_FLR_3_PTAC_SUPPLY FAN | ROOM_1_FLR_6_PTAC_SUPPLY FAN | ROOM_2_FLR_6_PTAC_SUPPLY FAN | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | PTAC_3_PTAC_SUPPLY FAN | PTAC_6_PTAC_SUPPLY FAN | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |AirLoopSystemComponentLoadsMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |AirLoopSystemComponentEnergyUseMonthly
| VAV_FLR_1 | VAV_FLR_6 | VAV_FLR_0 | PSZ_LAUNDRY | PSZ_CAFE | PSZ_KITCHEN |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1368.30 | 497.27 | 98.60 | 673.82 | 98.60 |
Gross Window-Wall Ratio [%] | 30.01 | 26.54 | 24.26 | 35.97 | 24.26 |
Above Ground Window-Wall Ratio [%] | 33.99 | 29.91 | 28.11 | 40.54 | 28.11 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1368.30 | 497.27 | 98.60 | 673.82 | 98.60 |
Gross Window-Wall Ratio [%] | 30.01 | 26.54 | 24.26 | 35.97 | 24.26 |
Above Ground Window-Wall Ratio [%] | 33.99 | 29.91 | 28.11 | 40.54 | 28.11 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 11.0679 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 16.1458 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 16.1458 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 15.0695 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 13.9931 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 4.22 | 4.22 | 12.2708 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 4.23 | 4.23 | 12.2708 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 18.31 | 18.31 | 5.3819 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 15.14 | 15.14 | 12.2708 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 7.75 | 7.75 | 12.2709 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 36.97 | 36.97 | 15.0695 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 36.97 | 36.97 | 15.0695 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 30.28 | 30.28 | 12.9167 | 4.65 | 2935.6055 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 32.40 | 32.40 | 5.3819 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1368.30 | 1368.30 | 11.3147 | 7.07 | 41.0811 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1368.30 | 1368.30 | 11.3147 | 7.07 | 41.0811 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 11.0679 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 16.1458 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 16.1458 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 16.1458 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 8.6111 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 6.4583 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 15.0695 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 13.9931 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 12.2708 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 12.2708 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 12.2708 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 5.3819 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 12.2708 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 12.2708 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 12.2709 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 15.0695 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 15.0695 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 12.9167 | 4.65 | 2935.6055 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 5.3819 | 18.58 | 0.0000 | |
Total | 11345.29 | 11.3147 | 3.54 | 41.0811 | |||||||
Conditioned Total | 11345.29 | 11.3147 | 3.54 | 41.0811 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 6.0626 | 8.82 | 37.2091 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-SEP-19:10 | 07-MAR-18:00 | - | - | - | - | - | - | - | - | - | - | 19-JAN-21:19 |
Heating | 0.00 | 38263.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 125594.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86555.31 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11860.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 44612.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 227431.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1339.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 411750.79 | 369942.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 38263.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 125594.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 365.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1288.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 9600.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 44612.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 47.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 0.00 | 227431.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 430.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 667.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 186.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3084.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4833.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1020.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5262.99 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2666.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3297.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2814.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 140.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 20313.40 | 4939.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 89.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.89 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 290.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 248.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1790.47 | 435.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 426.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 89.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 463.89 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 235.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 290.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 248.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 12.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1790.47 | 435.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 3.21 | 0.470471 | 0.300000 | 0.961506 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.564244 | 0.090579 | 0.300000 | 0.169273 | 0.300000 | 0.500000 | 0.004206 | 0.000048 | 0.236094 | 12.89 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.338011 | 0.175094 | 0.407000 | 0.137570 | 0.466918 | 0.500000 | 0.002176 | 0.000019 | 0.137570 | 12.89 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.374045 | 0.334594 | 0.300000 | 0.112214 | 0.892251 | 0.500000 | 0.001139 | 0.000021 | 0.112214 | 12.89 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.180091 | 0.400946 | 0.481000 | 0.086624 | 1.00 | 0.500000 | 0.000950 | 0.000019 | 0.093330 | 12.89 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 6.53 | 0.152617 | 0.435000 | 2.84 | 0.435000 | 0.500000 | 0.002496 | 0.000391 | 2.84 | 12.89 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.83 | 0.089447 | 0.518000 | 1.46 | 0.518000 | 0.500000 | 0.004260 | 0.000193 | 1.46 | 12.89 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.95 | 0.085644 | 0.496000 | 1.46 | 0.496000 | 0.500000 | 0.004449 | 0.000194 | 1.46 | 12.89 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5468.31 | 0.000048 | 127.55 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2158.62 | 0.000019 | 46.28 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2384.36 | 0.000021 | 54.39 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 2161.58 | 0.000019 | 50.42 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 44671.92 | 0.000391 | 958.13 |
ROOM_1_FLR_3 HEATING COIL | 19451.06 | 0.000170 | 487.47 |
ROOM_2_FLR_3 HEATING COIL | 18791.70 | 0.000164 | 470.80 |
ROOM_3_MULT19_FLR_3 HEATING COIL | 124019.60 | 0.001085 | 3075.46 |
ROOM_4_MULT19_FLR_3 HEATING COIL | 104388.34 | 0.000913 | 2577.99 |
ROOM_5_FLR_3 HEATING COIL | 17055.95 | 0.000149 | 426.92 |
ROOM_6_FLR_3 HEATING COIL | 16315.45 | 0.000143 | 408.20 |
PTAC_3 HEATING COIL | 34563.30 | 0.000302 | 833.54 |
ROOM_1_FLR_6 HEATING COIL | 5170.14 | 0.000045 | 129.64 |
ROOM_2_FLR_6 HEATING COIL | 4984.91 | 0.000044 | 124.96 |
ROOM_3_MULT9_FLR_6 HEATING COIL | 24025.87 | 0.000210 | 600.51 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 22010.61 | 0.000193 | 468.66 |
DINING_FLR_6 VAV BOX REHEAT COIL | 22152.63 | 0.000194 | 472.17 |
PTAC_6 HEATING COIL | 17814.08 | 0.000156 | 440.19 |
VAV_FLR_1 HEATING COIL | 25738.36 | 0.000225 | 442.87 |
VAV_FLR_6 HEATING COIL | 18703.31 | 0.000164 | 321.82 |
VAV_FLR_0 HEATING COIL | 30138.11 | 0.000264 | 2534.05 |
Design Size Maximum Air Flow Rate [m3/s] | |
LAUNDRY_FLR_1 DIRECT AIR | 3.91 |
CAFE_FLR_1 DIRECT AIR | 2.18 |
KITCHEN_FLR_6 DIRECT AIR | 2.70 |
Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | |
ROOM_1_FLR_3 | 1.36 | 1.36 | 1.36 | 0.061735 | 0.061735 | 0.061735 |
ROOM_2_FLR_3 | 1.31 | 1.31 | 1.31 | 0.061728 | 0.061728 | 0.061728 |
ROOM_3_MULT19_FLR_3 | 7.96 | 7.96 | 7.96 | 0.837072 | 0.837072 | 0.837072 |
ROOM_4_MULT19_FLR_3 | 6.49 | 6.49 | 6.49 | 0.837300 | 0.837300 | 0.837300 |
ROOM_5_FLR_3 | 1.18 | 1.18 | 1.18 | 0.061735 | 0.061735 | 0.061735 |
ROOM_6_FLR_3 | 1.12 | 1.12 | 1.12 | 0.061728 | 0.061728 | 0.061728 |
PTAC_3 | 1.85 | 1.85 | 1.85 | 0.474762 | 0.474762 | 0.474762 |
ROOM_1_FLR_6 | 0.362105 | 0.362105 | 0.362105 | 0.015434 | 0.015434 | 0.015434 |
ROOM_2_FLR_6 | 0.348274 | 0.348274 | 0.348274 | 0.015432 | 0.015432 | 0.015432 |
ROOM_3_MULT9_FLR_6 | 1.64 | 1.64 | 1.64 | 0.099154 | 0.099154 | 0.099154 |
PTAC_6 | 1.14 | 1.14 | 1.14 | 0.125616 | 0.125616 | 0.125616 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
ROOM_1_FLR_3 PTAC COOLING COIL | 1.36 | 22456.39 | 0.800655 |
ROOM_2_FLR_3 PTAC COOLING COIL | 1.31 | 21641.36 | 0.800655 |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 7.96 | 131746.21 | 0.800655 |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 6.49 | 111825.49 | 0.800331 |
ROOM_5_FLR_3 PTAC COOLING COIL | 1.18 | 19495.15 | 0.800655 |
ROOM_6_FLR_3 PTAC COOLING COIL | 1.12 | 18579.81 | 0.800655 |
PTAC_3 PTAC COOLING COIL | 1.85 | 33237.86 | 0.800084 |
ROOM_1_FLR_6 PTAC COOLING COIL | 0.362105 | 5994.13 | 0.800655 |
ROOM_2_FLR_6 PTAC COOLING COIL | 0.348274 | 5765.16 | 0.800655 |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 1.64 | 27147.60 | 0.800655 |
PTAC_6 PTAC COOLING COIL | 1.14 | 18804.38 | 0.800655 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3_PTAC_SUPPLY FAN | 1.36 |
ROOM_2_FLR_3_PTAC_SUPPLY FAN | 1.31 |
ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | 7.96 |
ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | 6.49 |
ROOM_5_FLR_3_PTAC_SUPPLY FAN | 1.18 |
ROOM_6_FLR_3_PTAC_SUPPLY FAN | 1.12 |
PTAC_3_PTAC_SUPPLY FAN | 1.85 |
ROOM_1_FLR_6_PTAC_SUPPLY FAN | 0.362105 |
ROOM_2_FLR_6_PTAC_SUPPLY FAN | 0.348274 |
ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | 1.64 |
PTAC_6_PTAC_SUPPLY FAN | 1.14 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_FLR_1 | 3.99 | 3.35 | 7.99 | 3.35 | 7.95 | 7.95 | 0.300000 | 0.421056 | 7.95 |
VAV_FLR_6 | 2.94 | 2.93 | 5.78 | 2.93 | 5.78 | 5.78 | 0.300000 | 0.506761 | 5.78 |
VAV_FLR_0 | 0.961506 | 0.961506 | 3.21 | 0.961506 | 3.21 | 3.21 | 1.00 | 0.300000 | 3.21 |
PSZ_LAUNDRY | 3.91 | 3.91 | 3.91 | 3.91 | 3.91 | 3.91 | 1.00 | 1.00 | 3.91 |
PSZ_CAFE | 2.18 | 2.18 | 2.18 | 2.18 | 2.18 | 2.18 | 1.00 | 1.00 | 2.18 |
PSZ_KITCHEN | 2.70 | 2.70 | 2.70 | 2.70 | 2.70 | 2.70 | 1.00 | 1.00 | 2.70 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_FLR_1_OA_CONTROLLER | 7.95 | |
VAV_FLR_6_OA_CONTROLLER | 5.78 | |
VAV_FLR_0_OA_CONTROLLER | 3.21 | |
PSZ_LAUNDRY_OA_CONTROLLER | 3.91 | 0.000000 |
PSZ_CAFE_OA_CONTROLLER | 2.18 | 0.676389 |
PSZ_KITCHEN_OA_CONTROLLER | 2.70 | 0.367350 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
VAV_FLR_1 COOLING COIL | 7.95 | 160773.89 | 0.771901 | 2.65 | 53585.94 | 0.771901 |
VAV_FLR_6 COOLING COIL | 5.78 | 124623.91 | 0.748082 | 1.93 | 41537.15 | 0.748082 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_FLR_1 FAN | 7.95 |
VAV_FLR_6 FAN | 5.78 |
VAV_FLR_0 SZVAV FAN | 3.21 |
Maximum Actuated Flow [m3/s] | |
VAV_FLR_1_HEATC_CONTROLLER | 0.000225 |
VAV_FLR_6_HEATC_CONTROLLER | 0.000164 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | User-Specified Minimum Supply Air Temperature [C] | User-Specified Maximum Supply Air Temperature [C] | Design Size Maximum Supply Air Temperature [C] | |
VAV_FLR_0_UNITARY_PACKAGE_DX | 3.21 | 3.21 | 3.21 | 0.961506 | 56567.23 | 59737.57 | 1.00 | 12.89 | 32.11 | |
PSZ_LAUNDRY_UNITARY_PACKAGE_DX | 3.91 | 3.91 | 3.91 | 3.91 | 64765.76 | 51620.63 | 1.00 | 32.11 | ||
PSZ_CAFE_UNITARY_PACKAGE_DX | 2.18 | 2.18 | 2.18 | 2.18 | 43995.80 | 42512.10 | 1.00 | 32.11 | ||
PSZ_KITCHEN_UNITARY_PACKAGE_DX | 2.70 | 2.70 | 2.70 | 2.70 | 52226.33 | 43897.01 | 1.00 | 32.11 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
VAV_FLR_0 COOLING COIL | 3.21 | 1.60 | 2.14 | 56567.23 | 28283.62 | 0.800820 | 0.800820 |
PSZ_LAUNDRY COOLING COIL | 3.91 | 1.96 | 2.61 | 64765.76 | 32382.88 | 0.800660 | 0.800660 |
PSZ_CAFE COOLING COIL | 2.18 | 1.09 | 1.45 | 43995.80 | 21997.90 | 0.771880 | 0.771880 |
PSZ_KITCHEN COOLING COIL | 2.70 | 1.35 | 1.80 | 52226.33 | 26113.17 | 0.789280 | 0.789280 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | 3.91 | 6346.56 |
PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | 2.18 | 3614.92 |
PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | 2.70 | 4374.81 |
Design Size Nominal Capacity [W] | |
PSZ_LAUNDRY HEATING COIL | 51620.63 |
PSZ_CAFE HEATING COIL | 42512.10 |
PSZ_KITCHEN HEATING COIL | 43897.01 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004918 | 0.590171 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.004918 | 1481.11 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 562168.20 | 562168.20 | 0.004918 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 6.92 | 4.22 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 6.92 | 4.23 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 30.00 | 18.31 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 24.81 | 15.14 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 24.80 | 15.14 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 12.69 | 7.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 60.57 | 36.97 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 60.57 | 36.97 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 57.04 | 30.28 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 53.08 | 32.40 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 11.068 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 16.448 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 16.146 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.906 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 16.146 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 26.906 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 16.146 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 21.526 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 8.611 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 11.301 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 15.069 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 20.449 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 13.993 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 22.063 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 12.271 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 19.021 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 12.271 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 22.791 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 15.069 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 82.889 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 15.069 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 82.889 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 12.917 | 516.346 | 2419.260 | 0.000 | 0.000 | 0.000 | 2948.522 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 21901.435 | 11.068 | 205.649 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21901.435 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 1082.924 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1082.924 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1254.030 | 16.146 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1254.030 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 2651.846 | 16.146 | 999.942 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2651.846 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 815.983 | 8.611 | 399.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 815.983 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.005 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.005 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2846.047 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2846.047 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 18305.540 | 13.993 | 43.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18305.540 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 300.928 | 12.271 | 200.619 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 300.928 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 301.011 | 12.271 | 200.674 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 301.011 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2095.757 | 5.382 | 100.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2095.757 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 478.833 | 12.271 | 319.222 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.833 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 478.777 | 12.271 | 319.185 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 478.777 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 301.011 | 12.271 | 200.674 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 301.011 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4997.899 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4997.899 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4997.899 | 15.069 | 20.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4997.899 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1334.351 | 12.917 | 60.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1334.351 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 2218.035 | 5.382 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2218.035 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 493.000 | 4.772 | 22.169 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 493.000 | 493.000 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 365.000 | 3.533 | 16.413 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 365.000 | 365.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 200.0 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | NONRES_EXT_WALL_MID | 22 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_TOP | 23 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | RES_EXT_WALL_MID | 25 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | RES_EXT_WALL_TOP | 26 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.3181 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5000E-02 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
13 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
14 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
15 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
19 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
20 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
21 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
23 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
24 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
25 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
26 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
27 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
28 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
31 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
33 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
36 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
37 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.883 |
38 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
39 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
40 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
42 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
44 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
46 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 200.00000 | 200.00000 | 200.00000 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
21 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
22 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
23 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
24 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
25 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
26 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
27 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
28 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
29 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
30 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
31 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
32 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
33 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
34 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
35 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
36 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
37 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
38 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
39 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
40 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
41 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
42 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
43 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
44 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
45 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
46 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
47 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
48 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
49 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
50 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
51 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
52 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
53 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
54 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
55 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
56 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
57 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
58 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
59 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
60 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
61 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
62 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
63 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
64 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
65 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
66 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
67 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
68 | 7 | -0.11407965E-14 | 0.23474115E-16 | -0.22119674E-13 | 0.51962024E-15 |
69 | 6 | 0.16676876E-10 | 0.39440661E-11 | 0.52102403E-09 | -0.18553030E-10 |
70 | 5 | -0.80001662E-07 | 0.19215958E-07 | -0.21848785E-05 | 0.17095694E-06 |
71 | 4 | 0.10228101E-03 | 0.72538432E-05 | 0.17630655E-02 | -0.28160064E-03 |
72 | 3 | -0.15120274E-01 | 0.25611913E-03 | -0.21515117 | 0.43248511E-01 |
73 | 2 | 0.21482172 | 0.11124906E-02 | 2.8969963 | -0.61829830 |
74 | 1 | -0.54366453 | 0.69706713E-03 | -7.1337069 | 1.5687761 |
75 | 0 | 0.34594624 | 0.12518961E-04 | 4.4521846 | |
76 | 7 | -0.22119674E-13 | 0.23474115E-16 | -0.11407965E-14 | 0.51962024E-15 |
77 | 6 | 0.52102403E-09 | 0.39440661E-11 | 0.16676876E-10 | -0.18553030E-10 |
78 | 5 | -0.21848785E-05 | 0.19215958E-07 | -0.80001662E-07 | 0.17095694E-06 |
79 | 4 | 0.17630655E-02 | 0.72538432E-05 | 0.10228101E-03 | -0.28160064E-03 |
80 | 3 | -0.21515117 | 0.25611913E-03 | -0.15120274E-01 | 0.43248511E-01 |
81 | 2 | 2.8969963 | 0.11124906E-02 | 0.21482172 | -0.61829830 |
82 | 1 | -7.1337069 | 0.69706713E-03 | -0.54366453 | 1.5687761 |
83 | 0 | 4.4521846 | 0.12518961E-04 | 0.34594624 | |
84 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
85 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
86 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
87 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
88 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
89 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
90 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
91 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
108 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
109 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
110 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
111 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
112 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
113 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
114 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
115 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
116 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
117 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
118 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
119 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
120 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
121 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
122 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
123 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_1.22_SHGC_0.39 | 37 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.391 | ||
2 | RESWINDOW_U_1.22_SHGC_0.34 | 38 | 1 | VerySmooth | 6.926 | 5.835 | 1.184 | 0.341 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.22227 | 0.21411 | 0.21411 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.17779 | 0.27613 | 0.27613 | 0.37400 | 0.14055 | 0.18699 | 0.00000 | 0.84000 | 0.84000 | 0.39956 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 11.511 | 0.4388 |
2 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 8000.0 | 0.975 | 0.8950 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 5.775 | 0.3748 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.38 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.38 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.38 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.38 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.38 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.35 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.38 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone BASEMENT | 1.2500 |
3 | Zone RETAIL_1_FLR_1 | 1.2500 |
4 | Zone RETAIL_2_FLR_1 | 1.2500 |
5 | Zone MECH_FLR_1 | 1.2500 |
6 | Zone STORAGE_FLR_1 | 1.2500 |
7 | Zone LAUNDRY_FLR_1 | 1.2500 |
8 | Zone CAFE_FLR_1 | 1.2500 |
9 | Zone LOBBY_FLR_1 | 1.2500 |
10 | Zone ROOM_1_FLR_3 | 1.2500 |
11 | Zone ROOM_2_FLR_3 | 1.2500 |
12 | Zone ROOM_3_MULT19_FLR_3 | 1.2500 |
13 | Zone ROOM_4_MULT19_FLR_3 | 1.2500 |
14 | Zone ROOM_5_FLR_3 | 1.2500 |
15 | Zone ROOM_6_FLR_3 | 1.2500 |
16 | Zone CORRIDOR_FLR_3 | 1.2500 |
17 | Zone ROOM_1_FLR_6 | 1.2500 |
18 | Zone ROOM_2_FLR_6 | 1.2500 |
19 | Zone ROOM_3_MULT9_FLR_6 | 1.2500 |
20 | Zone BANQUET_FLR_6 | 1.2500 |
21 | Zone DINING_FLR_6 | 1.2500 |
22 | Zone KITCHEN_FLR_6 | 1.2500 |
23 | Zone CORRIDOR_FLR_6 | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone BASEMENT | 1.1500 |
3 | Zone RETAIL_1_FLR_1 | 1.1500 |
4 | Zone RETAIL_2_FLR_1 | 1.1500 |
5 | Zone MECH_FLR_1 | 1.1500 |
6 | Zone STORAGE_FLR_1 | 1.1500 |
7 | Zone LAUNDRY_FLR_1 | 1.1500 |
8 | Zone CAFE_FLR_1 | 1.1500 |
9 | Zone LOBBY_FLR_1 | 1.1500 |
10 | Zone ROOM_1_FLR_3 | 1.1500 |
11 | Zone ROOM_2_FLR_3 | 1.1500 |
12 | Zone ROOM_3_MULT19_FLR_3 | 1.1500 |
13 | Zone ROOM_4_MULT19_FLR_3 | 1.1500 |
14 | Zone ROOM_5_FLR_3 | 1.1500 |
15 | Zone ROOM_6_FLR_3 | 1.1500 |
16 | Zone CORRIDOR_FLR_3 | 1.1500 |
17 | Zone ROOM_1_FLR_6 | 1.1500 |
18 | Zone ROOM_2_FLR_6 | 1.1500 |
19 | Zone ROOM_3_MULT9_FLR_6 | 1.1500 |
20 | Zone BANQUET_FLR_6 | 1.1500 |
21 | Zone DINING_FLR_6 | 1.1500 |
22 | Zone KITCHEN_FLR_6 | 1.1500 |
23 | Zone CORRIDOR_FLR_6 | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 37345.83985 | 42947.71583 | 2.78697 | 3.20502 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:30:00 | 27.33950 | 8.22721E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 3.80000 | 5.05843E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 6574.22283 | 7560.35625 | 0.49065 | 0.56424 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2529.06008 | 3161.32510 | 0.18888 | 0.23609 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3938.18997 | 4528.91847 | 0.29392 | 0.33801 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 30.05400 | 8.23151E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 651.60414 | 814.50518 | 4.86641E-002 | 9.17347E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 4358.94961 | 5012.79205 | 0.32526 | 0.37405 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 30.94400 | 8.23292E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1030.55209 | 1288.19012 | 7.69651E-002 | 9.62064E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 2098.67565 | 2413.47700 | 0.15660 | 0.18009 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 999.73753 | 1249.67191 | 7.46638E-002 | 9.33297E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45590.29968 | 52428.84463 | 3.40217 | 3.91250 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 29.25300 | 8.23024E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1373.55929 | 1716.94911 | 0.10258 | 0.12823 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 25322.11527 | 29120.43256 | 1.89134 | 2.17504 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.85500 | 8.23278E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6747.45181 | 8434.31476 | 0.50392 | 0.67639 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 76079.83570 | 87491.81105 | 5.67966 | 6.53161 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 13527.63042 | 16909.53803 | 1.01029 | 1.89399 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 15810.27084 | 18181.81146 | 1.17964 | 1.35659 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 30.64733 | 8.23245E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5487.58520 | 6859.48150 | 0.40986 | 0.51232 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 15236.44783 | 17521.91500 | 1.13683 | 1.30735 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5490.33722 | 6862.92153 | 0.41006 | 0.51258 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 92758.79975 | 106672.61971 | 6.92069 | 7.95879 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 31842.64324 | 39803.30404 | 2.37831 | 2.97289 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 75659.92289 | 87008.91132 | 5.64537 | 6.49217 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 31906.52880 | 39883.16099 | 2.38309 | 2.97886 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 13725.42290 | 15784.23634 | 1.02409 | 1.17770 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 27.41367 | 8.22733E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5481.76825 | 6852.21031 | 0.40942 | 0.51178 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 13080.98174 | 15043.12901 | 0.97601 | 1.12241 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 26.90933 | 8.22654E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5484.52071 | 6855.65088 | 0.40963 | 0.51203 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 21515.29542 | 24742.58973 | 1.60556 | 1.84640 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 31.22583 | 8.23338E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9023.30505 | 11279.13131 | 0.67390 | 0.84237 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 4220.12799 | 4853.14719 | 0.31487 | 0.36211 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 30.76600 | 8.23264E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1722.69586 | 2153.36982 | 0.12866 | 0.16083 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 4058.92527 | 4667.76406 | 0.30285 | 0.34827 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.52867 | 8.23226E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1720.26034 | 2150.32542 | 0.12848 | 0.16060 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 19112.60879 | 21979.50011 | 1.42608 | 1.63999 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8404.79023 | 10505.98779 | 0.62774 | 0.78468 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 32883.56822 | 37816.10345 | 2.45687 | 2.82540 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30000 | 8.23349E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6166.13621 | 7707.67027 | 0.46051 | 1.18780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 34343.99216 | 39495.59098 | 2.56595 | 2.95084 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30000 | 8.23349E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6279.24645 | 7849.05806 | 0.46895 | 1.18780 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31346.85312 | 36048.88108 | 2.34519 | 2.69696 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 27.66583 | 8.22773E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2022.09540 | 2527.61925 | 0.15100 | 0.36735 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 3.80000 | 5.05843E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 13237.16081 | 15222.73493 | 0.98780 | 1.13597 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 31.15167 | 8.23326E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6597.95727 | 8247.44659 | 0.49276 | 0.61595 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 3.80000 | 5.05843E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_FLR_1 | Cooling | Sensible | 129167.32 | 7.94890 | 7.94890 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_FLR_1 | Heating | Sensible | 26026.38 | 2.41136 | 2.41136 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | VAV_FLR_6 | Cooling | Sensible | 103629.36 | 5.77624 | 5.77624 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_FLR_6 | Heating | Sensible | 25640.39 | 2.37559 | 2.37559 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | VAV_FLR_0 | Cooling | Sensible | 45673.63 | 3.20502 | 3.20502 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | VAV_FLR_0 | Heating | Sensible | 28725.80 | 0.85446 | 0.85446 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ_LAUNDRY | Cooling | Sensible | 51618.12 | 3.91250 | 3.91250 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | PSZ_LAUNDRY | Heating | Sensible | 1691.77 | 0.12823 | 0.12823 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
9 | PSZ_CAFE | Cooling | Sensible | 34185.22 | 2.17504 | 2.17504 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ_CAFE | Heating | Sensible | 22739.33 | 0.67639 | 0.67639 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | PSZ_KITCHEN | Cooling | Sensible | 37044.59 | 2.69696 | 2.69696 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ_KITCHEN | Heating | Sensible | 12349.84 | 0.36735 | 0.36735 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 3.20502 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.47047 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.96151 |
5 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56424 |
6 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.05786E-002 |
7 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16927 |
9 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
10 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.20629E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.78391E-005 |
13 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23609 |
14 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5468.30854 |
17 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.78391E-005 |
18 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 127.54532 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.33801 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17509 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.40700 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13757 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46692 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17597E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.88846E-005 |
27 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13757 |
28 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2158.62140 |
31 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.88846E-005 |
32 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 46.28298 |
33 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.37405 |
34 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33459 |
35 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11221 |
37 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89225 |
38 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13869E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.08594E-005 |
41 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11221 |
42 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2384.36312 |
45 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.08594E-005 |
46 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 54.38533 |
47 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.18009 |
48 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40095 |
49 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
50 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66236E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.50253E-004 |
54 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.89104E-005 |
55 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.33297E-002 |
56 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2161.57742 |
59 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89104E-005 |
60 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 50.41709 |
61 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LAUNDRY_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.91250 |
62 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CAFE_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.17504 |
63 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.53161 |
64 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15262 |
65 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43500 |
66 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84125 |
67 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43500 |
68 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
69 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49644E-003 |
70 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.90809E-004 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84125 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
74 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 44671.91817 |
75 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.90809E-004 |
76 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 958.13408 |
77 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35659 |
78 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35659 |
79 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35659 |
80 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17350E-002 |
81 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17350E-002 |
82 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17350E-002 |
83 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 19451.06312 |
84 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70166E-004 |
85 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 487.47390 |
86 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.35659 |
87 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 22456.39408 |
88 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
89 | Fan:OnOff | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.35659 |
90 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30735 |
91 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30735 |
92 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30735 |
93 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17278E-002 |
94 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17278E-002 |
95 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17278E-002 |
96 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 18791.69768 |
97 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.64398E-004 |
98 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 470.80464 |
99 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.30735 |
100 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 21641.36390 |
101 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
102 | Fan:OnOff | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.30735 |
103 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.95879 |
104 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 7.95879 |
105 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 7.95879 |
106 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.83707 |
107 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.83707 |
108 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.83707 |
109 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 124019.59806 |
110 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08498E-003 |
111 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3075.46216 |
112 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 7.95879 |
113 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 131746.20744 |
114 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
115 | Fan:OnOff | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 7.95879 |
116 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.49217 |
117 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 6.49217 |
118 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 6.49217 |
119 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.83730 |
120 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.83730 |
121 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_4_MULT19_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.83730 |
122 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 104388.33931 |
123 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.13235E-004 |
124 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2577.99107 |
125 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 6.49217 |
126 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 111825.49244 |
127 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80033 |
128 | Fan:OnOff | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 6.49217 |
129 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.17770 |
130 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.17770 |
131 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.17770 |
132 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17350E-002 |
133 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17350E-002 |
134 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_5_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17350E-002 |
135 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 17055.94512 |
136 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49213E-004 |
137 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 426.91875 |
138 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.17770 |
139 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 19495.15267 |
140 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
141 | Fan:OnOff | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.17770 |
142 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12241 |
143 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12241 |
144 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12241 |
145 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 6.17278E-002 |
146 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 6.17278E-002 |
147 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_6_FLR_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 6.17278E-002 |
148 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size Rated Capacity [W] | 16315.44673 |
149 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42735E-004 |
150 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 408.19545 |
151 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.12241 |
152 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 18579.81249 |
153 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
154 | Fan:OnOff | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.12241 |
155 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.84640 |
156 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.84640 |
157 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.84640 |
158 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.47476 |
159 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.47476 |
160 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_3 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47476 |
161 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size Rated Capacity [W] | 34563.30097 |
162 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.02375E-004 |
163 | Coil:Heating:Water | PTAC_3 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 833.54297 |
164 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.84640 |
165 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 33237.85511 |
166 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80008 |
167 | Fan:OnOff | PTAC_3_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.84640 |
168 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36211 |
169 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36211 |
170 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36211 |
171 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.54338E-002 |
172 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.54338E-002 |
173 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_1_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.54338E-002 |
174 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 5170.14143 |
175 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.52307E-005 |
176 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 129.63782 |
177 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36211 |
178 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5994.12979 |
179 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
180 | Fan:OnOff | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36211 |
181 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.34827 |
182 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 0.34827 |
183 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 0.34827 |
184 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.54319E-002 |
185 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.54319E-002 |
186 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_2_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.54319E-002 |
187 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 4984.91129 |
188 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.36102E-005 |
189 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 124.95536 |
190 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.34827 |
191 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5765.16416 |
192 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
193 | Fan:OnOff | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.34827 |
194 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.63999 |
195 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.63999 |
196 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.63999 |
197 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 9.91540E-002 |
198 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 9.91540E-002 |
199 | ZoneHVAC:PackagedTerminalAirConditioner | ROOM_3_MULT9_FLR_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 9.91540E-002 |
200 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 24025.87199 |
201 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10189E-004 |
202 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 600.50922 |
203 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.63999 |
204 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 27147.59884 |
205 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
206 | Fan:OnOff | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.63999 |
207 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.82540 |
208 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.94469E-002 |
209 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51800 |
210 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.46356 |
211 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51800 |
212 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
213 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.25951E-003 |
214 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92558E-004 |
215 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.46356 |
216 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
217 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
218 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22010.60538 |
219 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92558E-004 |
220 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 468.66097 |
221 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.95084 |
222 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.56445E-002 |
223 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.49600 |
224 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.46362 |
225 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49600 |
226 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
227 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.44862E-003 |
228 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.93801E-004 |
229 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.46362 |
230 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
231 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
232 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22152.62822 |
233 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.93801E-004 |
234 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 472.16821 |
235 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.69696 |
236 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.13597 |
237 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Heating Supply Air Flow Rate [m3/s] | 1.13597 |
238 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size No Load Supply Air Flow Rate [m3/s] | 1.13597 |
239 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.12562 |
240 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.12562 |
241 | ZoneHVAC:PackagedTerminalAirConditioner | PTAC_6 | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.12562 |
242 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size Rated Capacity [W] | 17814.08052 |
243 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55845E-004 |
244 | Coil:Heating:Water | PTAC_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 440.18732 |
245 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.13597 |
246 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 18804.38135 |
247 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
248 | Fan:OnOff | PTAC_6_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.13597 |
249 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.99400 |
250 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.34693 |
251 | AirLoopHVAC | VAV_FLR_1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.98800 |
252 | AirLoopHVAC | VAV_FLR_1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.34693 |
253 | AirLoopHVAC | VAV_FLR_1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.94890 |
254 | AirLoopHVAC | VAV_FLR_1 | Adjusted Main Design Air Flow Rate [m3/s] | 7.94890 |
255 | AirLoopHVAC | VAV_FLR_1 | User Heating Air Flow Ratio [] | 0.30000 |
256 | AirLoopHVAC | VAV_FLR_1 | Calculated Heating Air Flow Ratio [] | 0.42106 |
257 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.93897 |
258 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.92717 |
259 | AirLoopHVAC | VAV_FLR_6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.77624 |
260 | AirLoopHVAC | VAV_FLR_6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.92717 |
261 | AirLoopHVAC | VAV_FLR_6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.77624 |
262 | AirLoopHVAC | VAV_FLR_6 | Adjusted Main Design Air Flow Rate [m3/s] | 5.77624 |
263 | AirLoopHVAC | VAV_FLR_6 | User Heating Air Flow Ratio [] | 0.30000 |
264 | AirLoopHVAC | VAV_FLR_6 | Calculated Heating Air Flow Ratio [] | 0.50676 |
265 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96151 |
266 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96151 |
267 | AirLoopHVAC | VAV_FLR_0 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.20502 |
268 | AirLoopHVAC | VAV_FLR_0 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96151 |
269 | AirLoopHVAC | VAV_FLR_0 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.20502 |
270 | AirLoopHVAC | VAV_FLR_0 | Adjusted Main Design Air Flow Rate [m3/s] | 3.20502 |
271 | AirLoopHVAC | VAV_FLR_0 | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | VAV_FLR_0 | Calculated Heating Air Flow Ratio [] | 0.30000 |
273 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.91250 |
274 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.91250 |
275 | AirLoopHVAC | PSZ_LAUNDRY | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.91250 |
276 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Heating Design Air Flow Rate [m3/s] | 3.91250 |
277 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.91250 |
278 | AirLoopHVAC | PSZ_LAUNDRY | Adjusted Main Design Air Flow Rate [m3/s] | 3.91250 |
279 | AirLoopHVAC | PSZ_LAUNDRY | User Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | PSZ_LAUNDRY | Calculated Heating Air Flow Ratio [] | 1.00000 |
281 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.17504 |
282 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.17504 |
283 | AirLoopHVAC | PSZ_CAFE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.17504 |
284 | AirLoopHVAC | PSZ_CAFE | Adjusted Heating Design Air Flow Rate [m3/s] | 2.17504 |
285 | AirLoopHVAC | PSZ_CAFE | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.17504 |
286 | AirLoopHVAC | PSZ_CAFE | Adjusted Main Design Air Flow Rate [m3/s] | 2.17504 |
287 | AirLoopHVAC | PSZ_CAFE | User Heating Air Flow Ratio [] | 1.00000 |
288 | AirLoopHVAC | PSZ_CAFE | Calculated Heating Air Flow Ratio [] | 1.00000 |
289 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.69696 |
290 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.69696 |
291 | AirLoopHVAC | PSZ_KITCHEN | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.69696 |
292 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Heating Design Air Flow Rate [m3/s] | 2.69696 |
293 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.69696 |
294 | AirLoopHVAC | PSZ_KITCHEN | Adjusted Main Design Air Flow Rate [m3/s] | 2.69696 |
295 | AirLoopHVAC | PSZ_KITCHEN | User Heating Air Flow Ratio [] | 1.00000 |
296 | AirLoopHVAC | PSZ_KITCHEN | Calculated Heating Air Flow Ratio [] | 1.00000 |
297 | AirLoopHVAC | VAV_FLR_1 | Design Supply Air Flow Rate [m3/s] | 7.94890 |
298 | AirLoopHVAC | VAV_FLR_6 | Design Supply Air Flow Rate [m3/s] | 5.77624 |
299 | AirLoopHVAC | VAV_FLR_0 | Design Supply Air Flow Rate [m3/s] | 3.20502 |
300 | AirLoopHVAC | PSZ_LAUNDRY | Design Supply Air Flow Rate [m3/s] | 3.91250 |
301 | AirLoopHVAC | PSZ_CAFE | Design Supply Air Flow Rate [m3/s] | 2.17504 |
302 | AirLoopHVAC | PSZ_KITCHEN | Design Supply Air Flow Rate [m3/s] | 2.69696 |
303 | Controller:OutdoorAir | VAV_FLR_1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.94890 |
304 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 7.94890 |
305 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 160773.88704 |
306 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77190 |
307 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.64937 |
308 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 53585.93655 |
309 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77190 |
310 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size Rated Capacity [W] | 25738.36119 |
311 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.25170E-004 |
312 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 442.87213 |
313 | Fan:VariableVolume | VAV_FLR_1 FAN | Design Size Maximum Flow Rate [m3/s] | 7.94890 |
314 | Controller:WaterCoil | VAV_FLR_1_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.25170E-004 |
315 | Controller:OutdoorAir | VAV_FLR_6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.77624 |
316 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.77624 |
317 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 124623.90685 |
318 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74808 |
319 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.92522 |
320 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 41537.14815 |
321 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74808 |
322 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size Rated Capacity [W] | 18703.31250 |
323 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63625E-004 |
324 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 321.82219 |
325 | Fan:VariableVolume | VAV_FLR_6 FAN | Design Size Maximum Flow Rate [m3/s] | 5.77624 |
326 | Controller:WaterCoil | VAV_FLR_6_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.63625E-004 |
327 | Controller:OutdoorAir | VAV_FLR_0_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.20502 |
328 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.20502 |
329 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.20502 |
330 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.20502 |
331 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96151 |
332 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.20502 |
333 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.60251 |
334 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.13668 |
335 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 56567.23000 |
336 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 28283.61500 |
337 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80082 |
338 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80082 |
339 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 56567.23000 |
340 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size Rated Capacity [W] | 30138.10839 |
341 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.63661E-004 |
342 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2534.05297 |
343 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59737.57460 |
344 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
345 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Minimum Supply Air Temperature [C] | 12.88890 |
346 | AirLoopHVAC:UnitarySystem | VAV_FLR_0_UNITARY_PACKAGE_DX | User-Specified Maximum Supply Air Temperature [C] | 32.11110 |
347 | Fan:VariableVolume | VAV_FLR_0 SZVAV FAN | Design Size Maximum Flow Rate [m3/s] | 3.20502 |
348 | Controller:OutdoorAir | PSZ_LAUNDRY_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.91250 |
349 | Controller:OutdoorAir | PSZ_LAUNDRY_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.00000 |
350 | Fan:SystemModel | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.91250 |
351 | Fan:SystemModel | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 6346.55979 |
352 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.91250 |
353 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.91250 |
354 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.91250 |
355 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.91250 |
356 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.91250 |
357 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.95625 |
358 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.60833 |
359 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 64765.76000 |
360 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32382.88000 |
361 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
362 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
363 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 64765.76000 |
364 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 51620.62628 |
365 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
366 | AirLoopHVAC:UnitarySystem | PSZ_LAUNDRY_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Coil:Heating:Fuel | PSZ_LAUNDRY HEATING COIL | Design Size Nominal Capacity [W] | 51620.62628 |
368 | Controller:OutdoorAir | PSZ_CAFE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.17504 |
369 | Controller:OutdoorAir | PSZ_CAFE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.67639 |
370 | Fan:SystemModel | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.17504 |
371 | Fan:SystemModel | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3614.91888 |
372 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.17504 |
373 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.17504 |
374 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.17504 |
375 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.17504 |
376 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.17504 |
377 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.08752 |
378 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.45003 |
379 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 43995.80000 |
380 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21997.90000 |
381 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77188 |
382 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77188 |
383 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43995.80000 |
384 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 42512.10082 |
385 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
386 | AirLoopHVAC:UnitarySystem | PSZ_CAFE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Coil:Heating:Fuel | PSZ_CAFE HEATING COIL | Design Size Nominal Capacity [W] | 42512.10082 |
388 | Controller:OutdoorAir | PSZ_KITCHEN_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.69696 |
389 | Controller:OutdoorAir | PSZ_KITCHEN_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.36735 |
390 | Fan:SystemModel | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.69696 |
391 | Fan:SystemModel | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 4374.81078 |
392 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.69696 |
393 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.69696 |
394 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.69696 |
395 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.69696 |
396 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.69696 |
397 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.34848 |
398 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.79797 |
399 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 52226.33000 |
400 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 26113.16500 |
401 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78928 |
402 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78928 |
403 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 52226.33000 |
404 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 43897.01134 |
405 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
406 | AirLoopHVAC:UnitarySystem | PSZ_KITCHEN_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
407 | Coil:Heating:Fuel | PSZ_KITCHEN HEATING COIL | Design Size Nominal Capacity [W] | 43897.01134 |
408 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.91809E-003 |
409 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.59017 |
410 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.91809E-003 |
411 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1481.11353 |
412 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
413 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 562168.20056 |
414 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 562168.20000 |
415 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.91809E-003 |
416 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
417 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
418 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
419 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
420 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5187.72 |
2 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2048.76 |
3 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2262.40 |
4 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2050.66 |
5 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 42398.26 |
6 | Coil:Heating:Water | ROOM_1_FLR_3 HEATING COIL | 20691.63 |
7 | Coil:Heating:Water | ROOM_2_FLR_3 HEATING COIL | 19980.60 |
8 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 HEATING COIL | 129749.09 |
9 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 HEATING COIL | 108496.03 |
10 | Coil:Heating:Water | ROOM_5_FLR_3 HEATING COIL | 18108.50 |
11 | Coil:Heating:Water | ROOM_6_FLR_3 HEATING COIL | 17309.77 |
12 | Coil:Heating:Water | PTAC_3 HEATING COIL | 34656.74 |
13 | Coil:Heating:Water | ROOM_1_FLR_6 HEATING COIL | 5504.33 |
14 | Coil:Heating:Water | ROOM_2_FLR_6 HEATING COIL | 5304.60 |
15 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 HEATING COIL | 25450.86 |
16 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 20891.08 |
17 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 21025.77 |
18 | Coil:Heating:Water | PTAC_6 HEATING COIL | 18579.71 |
19 | Coil:Heating:Water | VAV_FLR_1 HEATING COIL | 21601.60 |
20 | Coil:Heating:Water | VAV_FLR_6 HEATING COIL | 15697.25 |
21 | Coil:Heating:Water | VAV_FLR_0 HEATING COIL | 60166.67 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_3 PTAC COOLING COIL | 21403.7 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
2 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_3 PTAC COOLING COIL | 20626.9 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
3 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 125570.5 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
4 | Coil:Cooling:DX:SingleSpeed | ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 106787.1 | 2.67 | 9.12 | 9.67 | 9.15 | 9.13 |
5 | Coil:Cooling:DX:SingleSpeed | ROOM_5_FLR_3 PTAC COOLING COIL | 18581.3 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
6 | Coil:Cooling:DX:SingleSpeed | ROOM_6_FLR_3 PTAC COOLING COIL | 17708.9 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
7 | Coil:Cooling:DX:SingleSpeed | PTAC_3 PTAC COOLING COIL | 31804.7 | 2.69 | 9.18 | 9.74 | 9.22 | 9.24 |
8 | Coil:Cooling:DX:SingleSpeed | ROOM_1_FLR_6 PTAC COOLING COIL | 5713.2 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
9 | Coil:Cooling:DX:SingleSpeed | ROOM_2_FLR_6 PTAC COOLING COIL | 5494.9 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
10 | Coil:Cooling:DX:SingleSpeed | ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 25875.0 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
11 | Coil:Cooling:DX:SingleSpeed | PTAC_6 PTAC COOLING COIL | 17922.9 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 |
12 | Coil:Cooling:DX:MultiSpeed | VAV_FLR_0 COOLING COIL | 54053.2 | 10.28 | 10.28 | |||
13 | Coil:Cooling:DX:MultiSpeed | PSZ_LAUNDRY COOLING COIL | 61699.5 | 10.16 | 10.16 | |||
14 | Coil:Cooling:DX:MultiSpeed | PSZ_CAFE COOLING COIL | 42286.2 | 10.53 | 10.53 | |||
15 | Coil:Cooling:DX:MultiSpeed | PSZ_KITCHEN COOLING COIL | 50107.9 | 10.45 | 10.45 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_1 COOLING COIL | N/A | N/A | 154899.27 | 528538.24 | 10.81 | 3.00 | 3.16 | 3.14 | 3.30 | 10.22 | 10.77 | 10.71 | 11.25 | 9.0229 | 7.1943 | 4.8293 | 1.9342 |
2 | Coil:Cooling:DX:TwoSpeed | VAV_FLR_6 COOLING COIL | N/A | N/A | 120368.19 | 410713.32 | 10.93 | 3.03 | 3.20 | 3.18 | 3.32 | 10.32 | 10.91 | 10.85 | 11.33 | 6.5566 | 5.2180 | 3.5018 | 1.4328 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 200.000 | 200.000 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 6.92 | 11.15 | 6.92 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 4.22 | 4.22 | 4.22 | 180.00 | 90.00 | 3.02 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 6.92 | 11.15 | 6.92 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 4.23 | 4.23 | 4.23 | 0.00 | 90.00 | 3.02 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 90.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 90.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 4.04 | 6.50 | 4.04 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 2.47 | 2.47 | 2.47 | 0.00 | 90.00 | 1.76 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 4.04 | 6.50 | 4.04 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 2.46 | 2.46 | 2.46 | 180.00 | 90.00 | 1.76 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.318 | 0.300 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 8.65 | 13.94 | 8.65 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 16.15 | 26.01 | 16.15 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 9.86 | 9.86 | 9.86 | 270.00 | 90.00 | 7.04 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.514 | 0.477 | 12.69 | 20.44 | 12.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_1.22_SHGC_0.34 | N/A | 6.926 | No | 7.75 | 7.75 | 7.75 | 180.00 | 90.00 | 5.53 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.57 | 97.55 | 60.57 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 36.97 | 36.97 | 36.97 | 0.00 | 90.00 | 26.40 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 60.57 | 97.55 | 60.57 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 36.97 | 36.97 | 36.97 | 0.00 | 90.00 | 26.40 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 16.08 | 21.37 | 16.08 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 0.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 32.31 | 52.03 | 32.31 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 19.72 | 19.72 | 19.72 | 90.00 | 90.00 | 14.08 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 8.65 | 13.94 | 8.65 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 5.28 | 5.28 | 5.28 | 180.00 | 90.00 | 3.77 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 10.96 | 17.65 | 10.96 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 4.78 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 9.81 | 15.79 | 9.81 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 5.99 | 5.99 | 5.99 | 0.00 | 90.00 | 4.27 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.787 | 0.704 | 32.31 | 52.03 | 32.31 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_1.22_SHGC_0.39 | N/A | 6.926 | No | 19.72 | 19.72 | 19.72 | 180.00 | 90.00 | 14.08 | 1.40 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.318 | 0.295 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 4.2376517606E-003 | 1.1317107294E-002 | Pass | Pass | 1.4632168752E-002 | 3.4481521456E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.9965793973E-002 | 9.8963790216E-002 | Pass | Pass | 0.4125434557 | 1.9203088744 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7589508842E-002 | 3.1270816898E-002 | Pass | Pass | 4.2549265382E-003 | 5.0949036252E-003 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.2073160697E-002 | 2.3014210947E-002 | Pass | Pass | 3.1867651265E-003 | 3.3944224524E-003 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0996370893E-002 | 1.3457651108E-002 | Pass | Pass | 2.2078145313E-002 | 6.0654858971E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5598164113E-005 | 5.6146492811E-005 | Pass | Pass | 2.1075773147E-002 | 5.9198115079E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.8310817755E-002 | 9.9724517872E-002 | Pass | Pass | 2.5389837773E-002 | 3.7227570252E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3755524605E-002 | 4.6234223764E-002 | Pass | Pass | 6.4774978205E-003 | 7.3761448789E-003 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.3600218439E-002 | 0.2567537038 | Pass | Pass | 0.3799054008 | 1.0566002797 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.3483038014E-002 | 0.1226696672 | Pass | Pass | 0.5108122625 | 2.0477284537 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.1898871594E-002 | 8.1650391356E-002 | Pass | Pass | 0.2618363906 | 1.4659469108 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.3535930880E-002 | 0.1937160810 | Pass | Pass | 0.4224057483 | 2.0123362394 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.8059315532E-002 | 0.2469510671 | Pass | Pass | 1.3606228828 | 13.8191139363 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.0340700383E-002 | 0.2066178585 | Pass | Pass | 0.6105731318 | 3.2724519663 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.0237858016E-002 | 2.2395841796E-002 | Pass | Pass | 0.2029303921 | 0.6501210431 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.8183296195E-002 | 0.1693116177 | Pass | Pass | 1.4528458454 | 10.9975284835 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.8427708433E-002 | 0.1261948877 | Pass | Pass | 0.2677945231 | 1.4228221062 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.2721136715E-002 | 0.2730071203 | Pass | Pass | 0.6343022105 | 4.2755368173 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.1674804975E-002 | 9.1064922444E-002 | Pass | Pass | 7.3811090255E-003 | 1.4922700959E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.7103229377E-002 | 8.2216788475E-002 | Pass | Pass | 8.5928922683E-003 | 1.9705877566E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1002346013E-003 | 1.8585227114E-003 | Pass | Pass | 2.6641838594E-002 | 4.8908080645E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.7795590594E-002 | 4.1205484800E-002 | Pass | Pass | 0.3684437682 | 3.4539885887 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5255.05 | 83.71 | 1012.23 | 3887.99 | 4701.91 | 14940.89 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.06 | 64.62 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.05 | 64.61 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 847.14 | 526.04 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 847.37 | 526.16 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.06 | 64.62 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 55.74 | 34.61 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 104.05 | 64.61 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 70.60 | 43.85 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 26.01 | 16.14 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 26.02 | 16.16 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.704 | 0.787 | 70.60 | 43.85 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 13.94 | 8.65 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 26.01 | 16.15 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 13.94 | 8.65 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 26.01 | 16.15 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 183.96 | 114.24 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.30 | 0.358 | 0.376 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 97.55 | 60.57 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 97.55 | 60.57 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 21.37 | 16.08 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 52.03 | 32.31 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 13.94 | 8.65 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 17.65 | 10.96 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 15.79 | 9.81 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.704 | 0.787 | 52.03 | 32.31 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.293 | 0.318 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.298 | 0.318 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.288 | 0.318 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 6.926 | 0.391 | 0.431 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 6.926 | 0.391 | 0.431 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 6.926 | 0.391 | 0.431 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 6.926 | 0.341 | 0.376 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 6.926 | 0.341 | 0.376 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 6.926 | 0.341 | 0.376 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 6.926 | 0.341 | 0.376 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 4.22 | 0.00 | 0.00 | 4.22 | 321.10 | 6.926 | 0.341 | 0.376 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 4.23 | 0.00 | 0.00 | 4.23 | 321.20 | 6.926 | 0.341 | 0.376 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 6.926 | 0.341 | 0.376 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 6.926 | 0.341 | 0.376 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 5.28 | 0.00 | 0.00 | 5.28 | 21.13 | 6.926 | 0.341 | 0.376 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 9.86 | 0.00 | 0.00 | 9.86 | 39.44 | 6.926 | 0.341 | 0.376 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 6.69 | 0.00 | 0.00 | 6.69 | 26.76 | 6.926 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 2.47 | 0.00 | 0.00 | 2.47 | 9.86 | 6.926 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 2.46 | 0.00 | 0.00 | 2.46 | 9.86 | 6.926 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 6.69 | 0.00 | 0.00 | 6.69 | 26.76 | 6.926 | 0.391 | 0.431 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 6.926 | 0.341 | 0.376 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 9.86 | 0.00 | 0.00 | 9.86 | 9.86 | 6.926 | 0.341 | 0.376 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 6.926 | 0.341 | 0.376 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 9.86 | 0.00 | 0.00 | 9.86 | 9.86 | 6.926 | 0.341 | 0.376 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_1.22_SHGC_0.34 | 7.75 | 0.00 | 0.00 | 7.75 | 69.72 | 6.926 | 0.341 | 0.376 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 36.97 | 0.00 | 0.00 | 36.97 | 36.97 | 6.926 | 0.391 | 0.431 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 36.97 | 0.00 | 0.00 | 36.97 | 36.97 | 6.926 | 0.391 | 0.431 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 6.926 | 0.391 | 0.431 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 19.72 | 0.00 | 0.00 | 19.72 | 19.72 | 6.926 | 0.391 | 0.431 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 5.28 | 0.00 | 0.00 | 5.28 | 5.28 | 6.926 | 0.391 | 0.431 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 6.926 | 0.391 | 0.431 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 5.99 | 0.00 | 0.00 | 5.99 | 5.99 | 6.926 | 0.391 | 0.431 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_1.22_SHGC_0.39 | 19.72 | 0.00 | 0.00 | 19.72 | 19.72 | 6.926 | 0.391 | 0.431 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1368.30 | 6.926 | 0.355 | 0.391 | |||||||||||||||||
North Total or Average | 497.27 | 6.926 | 0.354 | 0.390 | |||||||||||||||||
Non-North Total or Average | 871.02 | 6.926 | 0.355 | 0.392 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 6.464 | 200.000 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 11.0679 | 1978.83 | 21901.44 | LightsWired | LTG_SCH_BASEMENT | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 241.03 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 16.1458 | 67.07 | 1082.92 | LightsWired | LTG_SCH_RETAIL | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 11.92 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 16.1458 | 77.67 | 1254.03 | LightsWired | LTG_SCH_RETAIL | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.80 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 16.1458 | 164.24 | 2651.85 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 29.18 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 8.6111 | 94.76 | 815.98 | LightsWired | LTG_SCH_STORAGE | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.98 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 6.4583 | 78.04 | 504.01 | LightsWired | LTG_SCH_LAUNDRY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 15.0695 | 188.86 | 2846.05 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 31.32 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 13.9931 | 1308.19 | 18305.54 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 201.46 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 12.2708 | 156.09 | 1915.33 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 12.2708 | 156.07 | 1915.11 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 12.2708 | 1863.81 | 22870.56 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 297.14 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 12.2708 | 1864.32 | 22876.81 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 297.22 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 12.2708 | 156.09 | 1915.33 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 12.2708 | 156.07 | 1915.11 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 24.88 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 5.3819 | 1557.62 | 8383.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 92.26 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 12.2708 | 39.02 | 478.83 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.22 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 12.2708 | 39.02 | 478.78 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 6.22 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 12.2709 | 220.77 | 2709.10 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 35.20 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 15.0695 | 331.66 | 4997.90 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 55.00 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 15.0695 | 331.66 | 4997.90 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 55.00 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 12.9167 | 103.30 | 1334.35 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.68 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 5.3819 | 412.12 | 2218.03 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 24.41 |
Interior Lighting Total | 11.3147 | 11345.29 | 128367.98 | 764.46 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 20502.98 | AstronomicalClock | - | 83.75 | 83.75 | 322.34 | |
Exterior Lighting Total | 20502.98 | 322.34 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 562168.20 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 22456.39 | 17979.83 | 4476.56 | 0.80 | 3.20 | |||
ROOM_2_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 21641.36 | 17327.27 | 4314.09 | 0.80 | 3.20 | |||
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 131746.21 | 105483.29 | 26262.91 | 0.80 | 3.20 | |||
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 111825.49 | 89497.36 | 22328.14 | 0.80 | 3.20 | |||
ROOM_5_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19495.15 | 15608.90 | 3886.26 | 0.80 | 3.20 | |||
ROOM_6_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 18579.81 | 14876.02 | 3703.79 | 0.80 | 3.20 | |||
PTAC_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 33237.86 | 26593.07 | 6644.79 | 0.80 | 3.20 | |||
ROOM_1_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5994.13 | 4799.23 | 1194.90 | 0.80 | 3.20 | |||
ROOM_2_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5765.16 | 4615.91 | 1149.26 | 0.80 | 3.20 | |||
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 27147.60 | 21735.87 | 5411.73 | 0.80 | 3.20 | |||
PTAC_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 18804.38 | 15055.83 | 3748.55 | 0.80 | 3.20 | |||
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 160773.89 | 124101.53 | 36672.36 | 0.77 | 3.50 | |||
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 124623.91 | 93228.91 | 31395.00 | 0.75 | 3.50 | |||
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 56567.23 | 45300.17 | 11267.06 | 0.80 | 3.40 | |||
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | 64765.76 | 51855.35 | 12910.41 | 0.80 | 3.40 | |||
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43995.80 | 33959.48 | 10036.32 | 0.77 | 3.40 | |||
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | 52226.33 | 41221.20 | 11005.13 | 0.79 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
ROOM_1_FLR_3 PTAC COOLING COIL | 21403.7 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_2_FLR_3 PTAC COOLING COIL | 20626.9 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | 125570.5 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | 106787.1 | 2.67 | 9.12 | 9.67 | 9.15 | 9.13 | |
ROOM_5_FLR_3 PTAC COOLING COIL | 18581.3 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_6_FLR_3 PTAC COOLING COIL | 17708.9 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
PTAC_3 PTAC COOLING COIL | 31804.7 | 2.69 | 9.18 | 9.74 | 9.22 | 9.24 | |
ROOM_1_FLR_6 PTAC COOLING COIL | 5713.2 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_2_FLR_6 PTAC COOLING COIL | 5494.9 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | 25875.0 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
PTAC_6 PTAC COOLING COIL | 17922.9 | 2.65 | 9.05 | 9.60 | 9.08 | 9.04 | |
VAV_FLR_1 COOLING COIL | 154899.3 | 3.00 | 10.22 | N/A | N/A | 10.81 | |
VAV_FLR_6 COOLING COIL | 120368.2 | 3.03 | 10.32 | N/A | N/A | 10.93 | |
VAV_FLR_0 COOLING COIL | 54053.2 | 10.28 | 10.28 | ||||
PSZ_LAUNDRY COOLING COIL | 61699.5 | 10.16 | 10.16 | ||||
PSZ_CAFE COOLING COIL | 42286.2 | 10.53 | 10.53 | ||||
PSZ_KITCHEN COOLING COIL | 50107.9 | 10.45 | 10.45 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
ROOM_1_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_2_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_5_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_6_FLR_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PTAC_3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_1_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_2_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
PTAC_6 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5468.31 | 5187.72 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2158.62 | 2048.76 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2384.36 | 2262.40 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2161.58 | 2050.66 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 44671.92 | 42398.26 | - |
ROOM_1_FLR_3 HEATING COIL | Coil:Heating:Water | 19451.06 | 20691.63 | - |
ROOM_2_FLR_3 HEATING COIL | Coil:Heating:Water | 18791.70 | 19980.60 | - |
ROOM_3_MULT19_FLR_3 HEATING COIL | Coil:Heating:Water | 124019.60 | 129749.09 | - |
ROOM_4_MULT19_FLR_3 HEATING COIL | Coil:Heating:Water | 104388.34 | 108496.03 | - |
ROOM_5_FLR_3 HEATING COIL | Coil:Heating:Water | 17055.95 | 18108.50 | - |
ROOM_6_FLR_3 HEATING COIL | Coil:Heating:Water | 16315.45 | 17309.77 | - |
PTAC_3 HEATING COIL | Coil:Heating:Water | 34563.30 | 34656.74 | - |
ROOM_1_FLR_6 HEATING COIL | Coil:Heating:Water | 5170.14 | 5504.33 | - |
ROOM_2_FLR_6 HEATING COIL | Coil:Heating:Water | 4984.91 | 5304.60 | - |
ROOM_3_MULT9_FLR_6 HEATING COIL | Coil:Heating:Water | 24025.87 | 25450.86 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 22010.61 | 20891.08 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 22152.63 | 21025.77 | - |
PTAC_6 HEATING COIL | Coil:Heating:Water | 17814.08 | 18579.71 | - |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | 25738.36 | 21601.60 | - |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | 18703.31 | 15697.25 | - |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | 59737.57 | 60166.67 | - |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | 51620.63 | 0.80 | |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | 42512.10 | 0.80 | |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | 43897.01 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.36 | 863.97 | 636.87 | 1.00 | 1.43 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.31 | 832.61 | 636.87 | 1.00 | 1.44 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 7.96 | 5068.68 | 636.87 | 1.00 | 1.20 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 6.49 | 4134.64 | 636.87 | 1.00 | 1.22 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.18 | 750.04 | 636.87 | 1.00 | 1.47 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 |
ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.12 | 714.82 | 636.87 | 1.00 | 1.48 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 |
PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.85 | 1175.91 | 636.87 | 1.00 | 1.37 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.36 | 230.61 | 636.87 | 1.00 | 2.00 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 |
ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.35 | 221.80 | 636.87 | 1.00 | 2.03 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 |
ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.64 | 1044.45 | 636.87 | 1.00 | 1.39 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 1.89 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.14 | 723.46 | 636.87 | 1.00 | 1.48 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
VAV_FLR_1 FAN | Fan:VariableVolume | 0.61 | 1337.13 | 7.95 | 17469.95 | 2197.78 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
VAV_FLR_6 FAN | Fan:VariableVolume | 0.60 | 1337.13 | 5.78 | 12776.80 | 2211.96 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 |
VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 0.60 | 1337.13 | 3.21 | 7189.88 | 2243.32 | 1.00 | 1.15 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:30:00 |
PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 3.91 | 6346.56 | 1622.12 | 1.00 | 1.19 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 2.18 | 3614.92 | 1662.00 | 1.00 | 1.21 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 2.70 | 4374.81 | 1622.12 | 1.00 | 1.22 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004918 | 1481.11 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 11.51 | 0.44 |
SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 0.80 | 0.98 | 0.90 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 5.78 | 0.37 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 154899.27 | 3.00 | 10.22 | 10.81 | 9.0229 | 3.16 | 10.77 | 7.1943 | 3.14 | 10.71 | 4.8293 | 3.30 | 11.25 | 1.9342 |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 120368.19 | 3.03 | 10.32 | 10.93 | 6.5566 | 3.20 | 10.91 | 5.2180 | 3.18 | 10.85 | 3.5018 | 3.32 | 11.33 | 1.4328 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 37345.84 | 42947.72 | 21.70 | 2.787 | 3.205 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:30:00 | 24.00 | 24.00 | 0.00914 | 27.34 | 0.00823 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6574.22 | 7560.36 | 112.72 | 0.491 | 0.564 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00886 | 31.00 | 0.00823 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3938.19 | 4528.92 | 58.31 | 0.294 | 0.338 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00920 | 30.05 | 0.00823 | 0.092 | 0.00 |
MECH_FLR_1 | 4358.95 | 5012.79 | 30.52 | 0.325 | 0.374 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00863 | 30.94 | 0.00823 | 0.000 | 0.00 |
STORAGE_FLR_1 | 2098.68 | 2413.48 | 25.47 | 0.157 | 0.180 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00870 | 31.30 | 0.00823 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45590.30 | 52428.84 | 671.82 | 3.402 | 3.912 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 24.00 | 24.00 | 0.00854 | 29.25 | 0.00823 | 0.000 | 0.00 |
CAFE_FLR_1 | 25322.12 | 29120.43 | 154.19 | 1.891 | 2.175 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 23.99 | 0.00974 | 30.86 | 0.00823 | 0.676 | 0.00 |
LOBBY_FLR_1 | 76079.84 | 87491.81 | 66.88 | 5.680 | 6.532 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.00973 | 31.08 | 0.00823 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 15810.27 | 18181.81 | 465.94 | 1.180 | 1.357 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 21.11 | 21.11 | 0.00856 | 30.65 | 0.00823 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 15236.45 | 17521.92 | 449.08 | 1.137 | 1.307 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00856 | 30.53 | 0.00823 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 92758.80 | 106672.62 | 4349.75 | 6.921 | 7.959 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 21.11 | 21.11 | 0.00850 | 31.00 | 0.00823 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 75659.92 | 87008.91 | 3546.96 | 5.645 | 6.492 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 21.11 | 21.11 | 0.00874 | 31.30 | 0.00823 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 13725.42 | 15784.24 | 404.50 | 1.024 | 1.178 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 21.11 | 21.11 | 0.00857 | 27.41 | 0.00823 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 13080.98 | 15043.13 | 385.55 | 0.976 | 1.122 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 21.11 | 21.11 | 0.00857 | 26.91 | 0.00823 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 21515.30 | 24742.59 | 63.54 | 1.606 | 1.846 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00937 | 31.23 | 0.00823 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 4220.13 | 4853.15 | 124.37 | 0.315 | 0.362 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 21.11 | 21.11 | 0.00855 | 30.77 | 0.00823 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 4058.93 | 4667.76 | 119.63 | 0.303 | 0.348 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 21.11 | 21.11 | 0.00856 | 30.53 | 0.00823 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 19112.61 | 21979.50 | 896.01 | 1.426 | 1.640 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 21.11 | 21.11 | 0.00861 | 31.00 | 0.00823 | 0.099 | 0.00 |
BANQUET_FLR_6 | 32883.57 | 37816.10 | 114.02 | 2.457 | 2.825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 23.99 | 0.01019 | 31.30 | 0.00823 | 1.188 | 0.00 |
DINING_FLR_6 | 34343.99 | 39495.59 | 119.09 | 2.566 | 2.951 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 23.99 | 0.01012 | 31.30 | 0.00823 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31346.85 | 36048.88 | 348.96 | 2.345 | 2.697 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 23.97 | 0.00995 | 27.67 | 0.00823 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 13237.16 | 15222.73 | 36.94 | 0.988 | 1.136 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00887 | 31.15 | 0.00823 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 21.56 | 0.00506 | 3.80 | 0.00506 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 2529.06 | 3161.33 | 47.13 | 0.189 | 0.236 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00785 | 3.80 | 0.00506 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 651.60 | 814.51 | 10.49 | 0.049 | 0.092 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00778 | 3.80 | 0.00506 | 0.092 | 0.00 |
MECH_FLR_1 | 1030.55 | 1288.19 | 7.84 | 0.077 | 0.096 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00768 | 3.80 | 0.00506 | 0.000 | 0.00 |
STORAGE_FLR_1 | 999.74 | 1249.67 | 13.19 | 0.075 | 0.093 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00780 | 3.80 | 0.00506 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1373.56 | 1716.95 | 22.00 | 0.103 | 0.128 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00767 | 3.80 | 0.00506 | 0.000 | 0.00 |
CAFE_FLR_1 | 6747.45 | 8434.31 | 44.66 | 0.504 | 0.676 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | 3.80 | 0.00506 | 0.676 | 0.00 |
LOBBY_FLR_1 | 13527.63 | 16909.54 | 12.93 | 1.010 | 1.894 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5487.59 | 6859.48 | 175.78 | 0.410 | 0.512 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00784 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5490.34 | 6862.92 | 175.89 | 0.410 | 0.513 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00784 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 31842.64 | 39803.30 | 1623.05 | 2.378 | 2.973 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00785 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 31906.53 | 39883.16 | 1625.86 | 2.383 | 2.979 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00785 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5481.77 | 6852.21 | 175.60 | 0.409 | 0.512 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00784 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5484.52 | 6855.65 | 175.71 | 0.410 | 0.512 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00784 | 3.80 | 0.00506 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9023.31 | 11279.13 | 28.97 | 0.674 | 0.842 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00788 | 3.80 | 0.00506 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1722.70 | 2153.37 | 55.18 | 0.129 | 0.161 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00787 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1720.26 | 2150.33 | 55.11 | 0.128 | 0.161 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00787 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8404.79 | 10505.99 | 428.28 | 0.628 | 0.785 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00788 | 3.80 | 0.00506 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6166.14 | 7707.67 | 23.24 | 0.461 | 1.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00791 | 3.80 | 0.00506 | 1.188 | 0.00 |
DINING_FLR_6 | 6279.25 | 7849.06 | 23.67 | 0.469 | 1.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00791 | 3.80 | 0.00506 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2022.10 | 2527.62 | 24.47 | 0.151 | 0.367 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00739 | 3.80 | 0.00506 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6597.96 | 8247.45 | 20.01 | 0.493 | 0.616 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00793 | 3.80 | 0.00506 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_FLR_1 | 7.95 | 7.95 | 2.41 | 2.41 | 7.9489 | 3.3469 | 7.9489 | 0.4211 | 0.3000 |
VAV_FLR_6 | 5.78 | 5.78 | 2.38 | 2.38 | 5.7762 | 2.9272 | 5.7762 | 0.5068 | 0.3000 |
VAV_FLR_0 | 3.21 | 3.21 | 0.85 | 0.85 | 3.2050 | 0.9615 | 3.2050 | 0.3000 | 1.0000 |
PSZ_LAUNDRY | 3.91 | 3.91 | 0.13 | 0.13 | 3.9125 | 3.9125 | 3.9125 | 1.0000 | 1.0000 |
PSZ_CAFE | 2.18 | 2.18 | 0.68 | 0.68 | 2.1750 | 2.1750 | 2.1750 | 1.0000 | 1.0000 |
PSZ_KITCHEN | 2.70 | 2.70 | 0.37 | 0.37 | 2.6970 | 2.6970 | 2.6970 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5468.309 | 5468.309 | 0.236094 | 0.00004784 | 127.545 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5468.31 | 5468.31 | 0.236094 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00784799 | 49.8043 | 3161.33 | 0.00 | 5192.69 | 5192.69 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2158.621 | 2158.621 | 0.137570 | 0.00001888 | 46.283 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2158.62 | 2158.62 | 0.137570 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00777792 | 49.3645 | 814.51 | 0.00 | 2050.26 | 2050.26 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2384.363 | 2384.363 | 0.112214 | 0.00002086 | 54.385 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2384.36 | 2384.36 | 0.112214 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00767999 | 48.7506 | 1288.19 | 0.00 | 2264.43 | 2264.43 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 2161.577 | 2161.577 | 0.093330 | 0.00001891 | 50.417 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2161.58 | 2161.58 | 0.093330 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00780098 | 49.5091 | 1249.67 | 0.00 | 2052.63 | 2052.63 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 44671.918 | 44671.918 | 2.841251 | 0.00039081 | 958.134 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 44671.92 | 44671.92 | 2.841251 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782214 | 49.6417 | 16909.54 | 0.00 | 42429.37 | 42429.37 |
ROOM_1_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | 19451.063 | 19451.063 | 1.356591 | 0.00017017 | 487.474 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 19451.06 | 19451.06 | 1.356591 | 20.32 | 14.15 | 0.00771146 | 32.22 | 18.56 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 4.5507 | 21.11 | 0.00783795 | 49.4034 | 6859.48 | 0.00 | 20705.43 | 20705.43 |
ROOM_1_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | 22456.394 | 17979.830 | 1.356591 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | 8/21 16:10:00 | 20485.67 | 20273.15 | 1.356591 | 21.54 | 15.35 | 0.00854307 | 9.47 | 9.47 | 0.00850000 | 30.65 | 0.00823245 | 18.24 | 4.5507 | 21.11 | 0.00855788 | 53.8800 | 18181.81 | 0.00 | 22467.39 | 17790.57 |
ROOM_2_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | 18791.698 | 18791.698 | 1.307355 | 0.00016440 | 470.805 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 18791.70 | 18791.70 | 1.307355 | 20.29 | 14.13 | 0.00770680 | 32.22 | 18.56 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 4.7216 | 21.11 | 0.00783804 | 49.4040 | 6862.92 | 0.00 | 19993.92 | 19993.92 |
ROOM_2_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | 21641.364 | 17327.272 | 1.307355 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 19773.40 | 19562.23 | 1.307355 | 21.56 | 15.36 | 0.00854440 | 9.47 | 9.47 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 4.7216 | 21.11 | 0.00855987 | 53.8923 | 17521.92 | 0.00 | 21651.96 | 17144.88 |
ROOM_3_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | 124019.598 | 124019.598 | 7.958788 | 0.00108498 | 3075.462 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 124019.60 | 124019.60 | 7.958788 | 19.29 | 13.61 | 0.00755751 | 32.22 | 18.56 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 10.5176 | 21.11 | 0.00785125 | 49.4856 | 39803.30 | 0.00 | 129834.96 | 129834.96 |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | 131746.207 | 105483.294 | 7.958788 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | unknown | 8/21 13:20:00 | 120291.63 | 120291.62 | 7.958788 | 22.15 | 15.51 | 0.00846802 | 9.47 | 9.47 | 0.00846802 | 31.00 | 0.00823302 | 18.35 | 10.5176 | 21.11 | 0.00849564 | 53.4919 | 106672.62 | 0.00 | 131810.70 | 104372.94 |
ROOM_4_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | 104388.339 | 104388.339 | 6.492173 | 0.00091323 | 2577.991 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 104388.34 | 104388.34 | 6.492173 | 18.88 | 13.39 | 0.00749127 | 32.22 | 18.56 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 12.8971 | 21.11 | 0.00785149 | 49.4872 | 39883.16 | 0.00 | 108567.32 | 108567.32 |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | 111825.492 | 89497.357 | 6.492173 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | unknown | 8/21 14:40:00 | 102707.71 | 98764.28 | 6.492173 | 22.42 | 15.79 | 0.00867805 | 9.47 | 9.47 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 12.8971 | 21.11 | 0.00874388 | 55.0360 | 87008.91 | 0.00 | 111880.23 | 88568.30 |
ROOM_5_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | 17055.945 | 17055.945 | 1.177702 | 0.00014921 | 426.919 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 17055.95 | 17055.95 | 1.177702 | 20.20 | 14.09 | 0.00769209 | 32.22 | 18.56 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 5.2420 | 21.11 | 0.00783779 | 49.4024 | 6852.21 | 0.00 | 18120.56 | 18120.56 |
ROOM_5_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | 19495.153 | 15608.897 | 1.177702 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | unknown | 8/21 09:40:00 | 18451.20 | 18233.83 | 1.177702 | 21.44 | 15.32 | 0.00854849 | 9.47 | 9.47 | 0.00850000 | 27.41 | 0.00822733 | 17.15 | 5.2420 | 21.11 | 0.00856626 | 53.9320 | 15784.24 | 0.00 | 19504.70 | 15444.59 |
ROOM_6_FLR_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | 16315.447 | 16315.447 | 1.122406 | 0.00014273 | 408.195 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 16315.45 | 16315.45 | 1.122406 | 20.16 | 14.06 | 0.00768502 | 32.22 | 18.56 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 5.4996 | 21.11 | 0.00783787 | 49.4029 | 6855.65 | 0.00 | 17321.30 | 17321.30 |
ROOM_6_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | 18579.812 | 14876.025 | 1.122406 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | unknown | 8/21 09:20:00 | 17685.80 | 17467.93 | 1.122406 | 21.43 | 15.32 | 0.00855068 | 9.47 | 9.47 | 0.00850000 | 26.91 | 0.00822654 | 16.98 | 5.4996 | 21.11 | 0.00856954 | 53.9524 | 15043.13 | 0.00 | 18588.91 | 14719.44 |
PTAC_3 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | 34563.301 | 34563.301 | 1.846398 | 0.00030237 | 833.543 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 34563.30 | 34563.30 | 1.846398 | 16.58 | 12.14 | 0.00715379 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 25.7129 | 21.00 | 0.00787905 | 49.9982 | 11279.13 | 0.00 | 34678.23 | 34678.23 |
PTAC_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | 33237.855 | 26593.070 | 1.846398 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | unknown | 8/21 13:50:00 | 32177.58 | 29283.40 | 1.846398 | 25.86 | 17.32 | 0.00907548 | 12.36 | 11.75 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 25.7129 | 24.00 | 0.00936695 | 49.4212 | 24742.59 | 0.00 | 33254.12 | 26316.23 |
ROOM_1_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | 5170.141 | 5170.141 | 0.362105 | 0.00004523 | 129.638 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 5170.14 | 5170.14 | 0.362105 | 20.37 | 14.20 | 0.00774965 | 32.22 | 18.56 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 4.2622 | 21.11 | 0.00786946 | 49.5995 | 2153.37 | 0.00 | 5508.03 | 5508.03 |
ROOM_1_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | 5994.130 | 4799.232 | 0.362105 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | unknown | 8/21 16:00:00 | 5458.49 | 5404.98 | 0.362105 | 21.52 | 15.34 | 0.00854059 | 9.47 | 9.47 | 0.00850000 | 30.77 | 0.00823264 | 18.27 | 4.2622 | 21.11 | 0.00855430 | 53.8577 | 4853.15 | 0.00 | 5997.06 | 4748.71 |
ROOM_2_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | 4984.911 | 4984.911 | 0.348274 | 0.00004361 | 124.955 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 4984.91 | 4984.91 | 0.348274 | 20.34 | 14.19 | 0.00774474 | 32.22 | 18.56 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 4.4310 | 21.11 | 0.00786929 | 49.5985 | 2150.33 | 0.00 | 5308.17 | 5308.17 |
ROOM_2_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | 5765.164 | 4615.909 | 0.348274 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | 8/21 16:20:00 | 5265.44 | 5212.09 | 0.348274 | 21.53 | 15.35 | 0.00854199 | 9.47 | 9.47 | 0.00850000 | 30.53 | 0.00823226 | 18.20 | 4.4310 | 21.11 | 0.00855635 | 53.8704 | 4667.76 | 0.00 | 5767.99 | 4567.32 |
ROOM_3_MULT9_FLR_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | 24025.872 | 24025.872 | 1.639986 | 0.00021019 | 600.509 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 24025.87 | 24025.87 | 1.639986 | 20.06 | 14.05 | 0.00770611 | 32.22 | 18.56 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 6.0460 | 21.11 | 0.00787649 | 49.6431 | 10505.99 | 0.00 | 25467.99 | 25467.99 |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | 27147.599 | 21735.868 | 1.639986 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | unknown | 8/21 13:20:00 | 24742.76 | 24223.79 | 1.639986 | 21.71 | 15.45 | 0.00858943 | 9.47 | 9.47 | 0.00850000 | 31.00 | 0.00823302 | 18.35 | 6.0460 | 21.11 | 0.00861236 | 54.2192 | 21979.50 | 0.00 | 27160.89 | 21507.07 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 22010.605 | 22010.605 | 1.463555 | 0.00019256 | 468.661 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 22010.61 | 22010.61 | 1.463555 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00790967 | 50.1902 | 7707.67 | 0.00 | 20905.99 | 20905.99 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 22152.628 | 22152.628 | 1.463616 | 0.00019380 | 472.168 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 22152.63 | 22152.63 | 1.463616 | 12.89 | 11.47 | 0.00800000 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00791124 | 50.2001 | 7849.06 | 0.00 | 21040.84 | 21040.84 |
PTAC_6 HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | 17814.081 | 17814.081 | 1.135973 | 0.00015585 | 440.187 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 17814.08 | 17814.08 | 1.135973 | 19.10 | 13.58 | 0.00760856 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 11.0580 | 21.00 | 0.00792562 | 50.2901 | 8247.45 | 0.00 | 18592.25 | 18592.25 |
PTAC_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | 18804.381 | 15055.827 | 1.135973 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 17855.95 | 16918.54 | 1.135973 | 24.79 | 16.73 | 0.00879918 | 12.36 | 11.75 | 0.00850000 | 31.15 | 0.00823326 | 18.40 | 11.0580 | 24.00 | 0.00886954 | 46.8333 | 15222.73 | 0.00 | 18813.59 | 14897.34 |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_FLR_1 | 160773.887 | 124101.527 | 7.948903 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 158044.58 | 143935.39 | 7.948903 | 26.60 | 17.59 | 0.00909967 | 11.07 | 11.07 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 35.6062 | 24.00 | 0.00958019 | 50.5403 | 92398.68 | 0.00 | 161238.88 | 123055.54 |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_1 | 25738.361 | 25738.361 | 2.384671 | 0.00022517 | 442.872 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 25738.36 | 25738.36 | 2.384671 | 3.80 | 3.80 | 0.00505843 | 12.89 | 11.47 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 118.6872 | 21.00 | 0.00781514 | 49.5979 | 18738.58 | 0.00 | 26149.35 | 26149.35 |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_FLR_6 | 124623.907 | 93228.907 | 5.776235 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 123826.17 | 113575.86 | 5.776235 | 28.00 | 18.06 | 0.00910188 | 11.06 | 11.06 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 54.8368 | 23.99 | 0.01015627 | 53.5615 | 67227.56 | 0.00 | 124984.35 | 92479.00 |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_6 | 18703.313 | 18703.313 | 1.732871 | 0.00016362 | 321.822 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 18703.31 | 18703.31 | 1.732871 | 3.80 | 3.80 | 0.00505843 | 12.89 | 11.47 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 182.7892 | 21.00 | 0.00791044 | 50.1953 | 12444.05 | 0.00 | 19001.96 | 19001.96 |
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | VAV_FLR_0 | 56567.230 | 45300.169 | 3.205020 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:30:00 | 28283.62 | 26357.97 | 2.136680 | 24.89 | 16.84 | 0.00889736 | 11.03 | 11.03 | 0.00850000 | 27.34 | 0.00822721 | 17.13 | 39.9900 | 24.00 | 0.00914145 | 48.2494 | 37320.30 | 0.00 | -999.00 | -999.00 |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_FLR_0 | 59737.575 | 59737.575 | 3.205020 | 0.00026366 | 2534.053 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 59737.57 | 59737.57 | 3.205020 | 16.41 | 12.13 | 0.00721578 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 26.6600 | 21.56 | 0.00505843 | 31.1569 | 0.00 | 0.00 | 60197.64 | 60197.64 |
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_LAUNDRY | 64765.760 | 51855.353 | 3.912500 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 32382.88 | 32128.02 | 2.608333 | 24.00 | 16.23 | 0.00854034 | 11.54 | 11.41 | 0.00850000 | 29.25 | 0.00823024 | 17.77 | 0.0000 | 24.00 | 0.00854034 | 45.1192 | 45590.30 | 0.00 | -999.00 | -999.00 |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_LAUNDRY | 51620.626 | 51620.626 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 51620.63 | 51620.63 | 3.912500 | 21.00 | 14.37 | 0.00767319 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00767319 | 48.7085 | 1373.56 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_CAFE | 43995.800 | 33959.478 | 2.175040 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 21997.90 | 19460.38 | 1.450027 | 26.12 | 17.57 | 0.00927304 | 11.51 | 11.40 | 0.00850000 | 30.86 | 0.00823278 | 18.30 | 46.6467 | 23.99 | 0.00974673 | 51.4245 | 25286.99 | 0.00 | -999.00 | -999.00 |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_CAFE | 42512.101 | 42512.101 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 42512.10 | 42512.10 | 2.175045 | 15.65 | 11.60 | 0.00699768 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 31.0977 | 21.00 | 0.00787276 | 49.9597 | 6746.02 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ_KITCHEN | 52226.330 | 41221.198 | 2.696960 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 26113.17 | 21209.88 | 1.797973 | 24.46 | 17.37 | 0.00971761 | 11.55 | 11.41 | 0.00850000 | 27.67 | 0.00822773 | 17.24 | 20.4314 | 23.97 | 0.01004284 | 53.0190 | 30855.79 | 0.00 | -999.00 | -999.00 |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ_KITCHEN | 43897.011 | 43897.011 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:20:00 | 43897.01 | 43897.01 | 2.696964 | 18.40 | 12.80 | 0.00707185 | 32.11 | 18.53 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 13.6209 | 21.00 | 0.00740328 | 47.0170 | 1165.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5468.309 | 5468.309 | 0.236094 | 0.00004784 | 127.545 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 0.9535 | 0.972718 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5468.31 | 5468.31 | 1.0000 | 0.27901133 | 0.236094 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.04783427 | 60.00 | 32.22 | 27.78 | 0.000 | 5468.31 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00784799 | 21.00 | 0.00784799 | 49.8043 | 3161.33 | 0.00 | 5192.69 | 5192.69 | 0.27901133 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55545.8 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2158.621 | 2158.621 | 0.137570 | 0.00001888 | 46.283 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 0.3764 | 0.383981 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2158.62 | 2158.62 | 1.0000 | 0.16257762 | 0.137570 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.01888264 | 60.00 | 32.22 | 27.78 | 0.000 | 2158.62 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00777792 | 21.00 | 0.00777792 | 49.3645 | 814.51 | 0.00 | 2050.26 | 2050.26 | 0.16257762 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.97 | 17.69 | 0.00800000 | 49545.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2384.363 | 2384.363 | 0.112214 | 0.00002086 | 54.385 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 0.4158 | 0.424137 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2384.36 | 2384.36 | 1.0000 | 0.13261152 | 0.112214 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.02085732 | 60.00 | 32.22 | 27.78 | 0.000 | 2384.36 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00767999 | 21.00 | 0.00767999 | 48.7506 | 1288.19 | 0.00 | 2264.43 | 2264.43 | 0.13261152 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 33.35 | 19.13 | 0.00800000 | 54010.4 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2161.577 | 2161.577 | 0.093330 | 0.00001891 | 50.417 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 0.3769 | 0.384507 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2161.58 | 2161.58 | 1.0000 | 0.11029509 | 0.093330 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.01890849 | 60.00 | 32.22 | 27.78 | 0.000 | 2161.58 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00780098 | 21.00 | 0.00780098 | 49.5091 | 1249.67 | 0.00 | 2052.63 | 2052.63 | 0.11029509 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 34.85 | 19.61 | 0.00800000 | 55545.1 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44671.918 | 44671.918 | 2.841251 | 0.00039081 | 958.134 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 7.7896 | 7.946362 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 44671.92 | 44671.92 | 1.0000 | 3.35772954 | 2.841251 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.39076956 | 60.00 | 32.22 | 27.78 | 0.000 | 44671.92 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00782214 | 21.00 | 0.00782214 | 49.6417 | 16909.54 | 0.00 | 42429.37 | 42429.37 | 3.35772954 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.99 | 17.70 | 0.00800000 | 49571.1 | |
ROOM_1_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19451.063 | 19451.063 | 1.356591 | 0.00017017 | 487.474 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.356591 | 1.60319002 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 3.3917 | 3.460008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 19451.06 | 19451.06 | 1.0000 | 1.60319002 | 1.356591 | 20.32 | 14.15 | 0.00771146 | 39998.5 | 32.22 | 18.56 | 0.00800000 | 52863.7 | 0.17014903 | 60.00 | 32.22 | 27.78 | 0.000 | 19451.06 | 3.80 | 0.00505843 | 3.80 | 0.06173502 | 4.5507 | 21.11 | 0.00783795 | 21.11 | 0.00783795 | 49.4034 | 6859.48 | 0.00 | 20705.43 | 20705.43 | 1.60319002 | 16.60 | 12.87 | 0.00771146 | 36204.2 | 29.27 | 17.56 | 0.00771146 | 49119.4 | |
ROOM_1_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_3 | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 22456.394 | 17979.830 | 1.356591 | -999.0 | -999.000 | -999.0000 | 1.04654 | 1.00000 | 1020.7211 | 1004.8586 | 1.1818 | ROOM_1_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.356591 | 1.60319002 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | unknown | unknown | 8/21 16:10:00 | Sensible | 20485.67 | 20273.15 | 0.9122 | 1.60319002 | 1.356591 | 21.54 | 15.35 | 0.00854307 | 43356.7 | 9.47 | 9.47 | 0.00850000 | 30924.4 | -999.0 | -999.00 | -999.00 | -999.00 | 863.966 | 19621.71 | 30.65 | 0.00823245 | 18.24 | 0.06173502 | 4.5507 | 21.11 | 0.00855788 | 21.11 | 0.00855788 | 53.8800 | 18181.81 | 0.00 | 22467.39 | 17790.57 | 1.53987614 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999387 | 40732.0 | |
ROOM_2_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18791.698 | 18791.698 | 1.307355 | 0.00016440 | 470.805 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.307355 | 1.54500400 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 3.2768 | 3.342718 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 18791.70 | 18791.70 | 1.0000 | 1.54500400 | 1.307355 | 20.29 | 14.13 | 0.00770680 | 39956.5 | 32.22 | 18.56 | 0.00800000 | 52863.7 | 0.16438120 | 60.00 | 32.22 | 27.78 | 0.000 | 18791.70 | 3.80 | 0.00505843 | 3.80 | 0.06172779 | 4.7216 | 21.11 | 0.00783804 | 21.11 | 0.00783804 | 49.4040 | 6862.92 | 0.00 | 19993.92 | 19993.92 | 1.54500400 | 16.60 | 12.87 | 0.00770680 | 36192.4 | 29.30 | 17.56 | 0.00770680 | 49133.4 | |
ROOM_2_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_3 | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 21641.364 | 17327.272 | 1.307355 | -999.0 | -999.000 | -999.0000 | 1.04703 | 1.00000 | 1020.7236 | 1004.8586 | 1.1818 | ROOM_2_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.307355 | 1.54500400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 19773.40 | 19562.23 | 0.9137 | 1.54500400 | 1.307355 | 21.56 | 15.36 | 0.00854440 | 43371.0 | 9.47 | 9.47 | 0.00850000 | 30924.4 | -999.0 | -999.00 | -999.00 | -999.00 | 832.609 | 18940.79 | 30.53 | 0.00823226 | 18.20 | 0.06172779 | 4.7216 | 21.11 | 0.00855987 | 21.11 | 0.00855987 | 53.8923 | 17521.92 | 0.00 | 21651.96 | 17144.88 | 1.48398802 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999387 | 40732.0 | |
ROOM_3_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 124019.598 | 124019.598 | 7.958788 | 0.00108498 | 3075.462 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 7.958788 | 9.40552631 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 21.6257 | 22.060942 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 124019.60 | 124019.60 | 1.0000 | 9.40552631 | 7.958788 | 19.29 | 13.61 | 0.00755751 | 38555.4 | 32.22 | 18.56 | 0.00800000 | 52863.7 | 1.08486687 | 60.00 | 32.22 | 27.78 | 0.000 | 124019.60 | 3.80 | 0.00505843 | 3.80 | 0.83707151 | 10.5176 | 21.11 | 0.00785125 | 21.11 | 0.00785125 | 49.4856 | 39803.30 | 0.00 | 129834.96 | 129834.96 | 9.40552631 | 16.60 | 12.72 | 0.00755751 | 35814.4 | 30.15 | 17.73 | 0.00755751 | 49618.6 | |
ROOM_3_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 131746.207 | 105483.294 | 7.958788 | -999.0 | -999.000 | -999.0000 | 1.00815 | 1.00000 | 1020.5816 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 7.958788 | 9.40552631 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | unknown | unknown | unknown | 8/21 13:20:00 | Sensible | 120291.63 | 120291.62 | 0.9131 | 9.40552631 | 7.958788 | 22.15 | 15.51 | 0.00846802 | 43785.4 | 9.47 | 9.47 | 0.00846802 | 30843.8 | -999.0 | -999.00 | -999.00 | -999.00 | 5068.677 | 115222.95 | 31.00 | 0.00823302 | 18.35 | 0.83707151 | 10.5176 | 21.11 | 0.00849564 | 21.11 | 0.00849564 | 53.4919 | 106672.62 | 0.00 | 131810.70 | 104372.94 | 9.03407912 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999387 | 40732.0 | |
ROOM_4_MULT19_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 104388.339 | 104388.339 | 6.492173 | 0.00091323 | 2577.991 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 6.492173 | 7.67231098 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 18.2025 | 18.568880 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 104388.34 | 104388.34 | 1.0000 | 7.67231098 | 6.492173 | 18.88 | 13.39 | 0.00749127 | 37967.7 | 32.22 | 18.56 | 0.00800000 | 52863.7 | 0.91314157 | 60.00 | 32.22 | 27.78 | 0.000 | 104388.34 | 3.80 | 0.00505843 | 3.80 | 0.83730041 | 12.8971 | 21.11 | 0.00785149 | 21.11 | 0.00785149 | 49.4872 | 39883.16 | 0.00 | 108567.32 | 108567.32 | 7.67231098 | 16.60 | 12.65 | 0.00749127 | 35646.7 | 30.49 | 17.79 | 0.00749127 | 49797.3 | |
ROOM_4_MULT19_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 111825.492 | 89497.357 | 6.492173 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9721 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 6.492173 | 7.67231098 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | unknown | unknown | unknown | 8/21 14:40:00 | Sensible | 102707.71 | 98764.28 | 0.9185 | 7.67231098 | 6.492173 | 22.42 | 15.79 | 0.00867805 | 44598.0 | 9.47 | 9.47 | 0.00850000 | 30924.5 | -999.0 | -999.00 | -999.00 | -999.00 | 4134.640 | 98573.07 | 31.30 | 0.00823349 | 18.45 | 0.83730041 | 12.8971 | 21.11 | 0.00874388 | 21.11 | 0.00874388 | 55.0360 | 87008.91 | 0.00 | 111880.23 | 88568.30 | 7.36931270 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.92 | 14.33 | 0.00994437 | 40140.5 | |
ROOM_5_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17055.945 | 17055.945 | 1.177702 | 0.00014921 | 426.919 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.177702 | 1.39178330 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 2.9741 | 3.033958 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 17055.95 | 17055.95 | 1.0000 | 1.39178330 | 1.177702 | 20.20 | 14.09 | 0.00769209 | 39827.4 | 32.22 | 18.56 | 0.00800000 | 52863.7 | 0.14919763 | 60.00 | 32.22 | 27.78 | 0.000 | 17055.95 | 3.80 | 0.00505843 | 3.80 | 0.06173502 | 5.2420 | 21.11 | 0.00783779 | 21.11 | 0.00783779 | 49.4024 | 6852.21 | 0.00 | 18120.56 | 18120.56 | 1.39178330 | 16.60 | 12.85 | 0.00769209 | 36155.2 | 29.38 | 17.57 | 0.00769209 | 49174.8 | |
ROOM_5_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_5_FLR_3 | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 19495.153 | 15608.897 | 1.177702 | -999.0 | -999.000 | -999.0000 | 1.09351 | 1.00000 | 1020.7312 | 1004.8586 | 1.1818 | ROOM_5_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.177702 | 1.39178330 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | unknown | unknown | unknown | 8/21 09:40:00 | Sensible | 18451.20 | 18233.83 | 0.9465 | 1.39178330 | 1.177702 | 21.44 | 15.32 | 0.00854849 | 43264.7 | 9.47 | 9.47 | 0.00850000 | 30924.4 | -999.0 | -999.00 | -999.00 | -999.00 | 750.038 | 17701.16 | 27.41 | 0.00822733 | 17.15 | 0.06173502 | 5.2420 | 21.11 | 0.00856626 | 21.11 | 0.00856626 | 53.9320 | 15784.24 | 0.00 | 19504.70 | 15444.59 | 1.33681838 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999387 | 40732.0 | |
ROOM_6_FLR_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16315.447 | 16315.447 | 1.122406 | 0.00014273 | 408.195 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.122406 | 1.32643602 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 2.8450 | 2.902236 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 16315.45 | 16315.45 | 1.0000 | 1.32643602 | 1.122406 | 20.16 | 14.06 | 0.00768502 | 39764.0 | 32.22 | 18.56 | 0.00800000 | 52863.7 | 0.14272008 | 60.00 | 32.22 | 27.78 | 0.000 | 16315.45 | 3.80 | 0.00505843 | 3.80 | 0.06172779 | 5.4996 | 21.11 | 0.00783787 | 21.11 | 0.00783787 | 49.4029 | 6855.65 | 0.00 | 17321.30 | 17321.30 | 1.32643602 | 16.60 | 12.84 | 0.00768502 | 36137.3 | 29.41 | 17.58 | 0.00768502 | 49195.8 | |
ROOM_6_FLR_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_6_FLR_3 | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 18579.812 | 14876.025 | 1.122406 | -999.0 | -999.000 | -999.0000 | 1.10030 | 1.00000 | 1020.7353 | 1004.8586 | 1.1818 | ROOM_6_FLR_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.122406 | 1.32643602 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | unknown | unknown | unknown | 8/21 09:20:00 | Sensible | 17685.80 | 17467.93 | 0.9519 | 1.32643602 | 1.122406 | 21.43 | 15.32 | 0.00855068 | 43258.5 | 9.47 | 9.47 | 0.00850000 | 30924.4 | -999.0 | -999.00 | -999.00 | -999.00 | 714.822 | 16970.98 | 26.91 | 0.00822654 | 16.98 | 0.06172779 | 5.4996 | 21.11 | 0.00856954 | 21.11 | 0.00856954 | 53.9524 | 15043.13 | 0.00 | 18588.91 | 14719.44 | 1.27405183 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999387 | 40732.0 | |
PTAC_3 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34563.301 | 34563.301 | 1.846398 | 0.00030237 | 833.543 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.846398 | 2.18203422 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 6.0269 | 6.148213 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 34563.30 | 34563.30 | 1.0000 | 2.18203422 | 1.846398 | 16.58 | 12.14 | 0.00715379 | 34769.2 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.30234399 | 60.00 | 32.22 | 27.78 | 0.000 | 34563.30 | 3.80 | 0.00505843 | 3.80 | 0.47476218 | 25.7129 | 21.00 | 0.00787905 | 21.00 | 0.00787905 | 49.9982 | 11279.13 | 0.00 | 34678.23 | 34678.23 | 2.18203422 | 16.60 | 12.32 | 0.00715379 | 34792.3 | 32.21 | 18.09 | 0.00715379 | 50684.9 | |
PTAC_3 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_3 | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 33237.855 | 26593.070 | 1.846398 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7109 | 1004.8586 | 1.1818 | PTAC_3_PTAC_SUPPLY FAN | Fan:OnOff | 1.846398 | 2.18203422 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | unknown | unknown | unknown | 8/21 13:50:00 | Sensible | 32177.58 | 29283.40 | 0.9681 | 2.18203422 | 1.846398 | 25.86 | 17.32 | 0.00907548 | 49115.7 | 12.36 | 11.75 | 0.00850000 | 33874.6 | -999.0 | -999.00 | -999.00 | -999.00 | 1175.907 | 31001.67 | 31.23 | 0.00823338 | 18.43 | 0.47476218 | 25.7129 | 24.00 | 0.00936695 | 24.00 | 0.00936695 | 49.4212 | 24742.59 | 0.00 | 33254.12 | 26316.23 | 2.09586036 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.40 | 14.07 | 0.00988677 | 39455.8 | |
ROOM_1_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5170.141 | 5170.141 | 0.362105 | 0.00004523 | 129.638 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.362105 | 0.42792841 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 0.9015 | 0.919679 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 5170.14 | 5170.14 | 1.0000 | 0.42792841 | 0.362105 | 20.37 | 14.20 | 0.00774965 | 40146.4 | 32.22 | 18.56 | 0.00800000 | 52863.7 | 0.04522604 | 60.00 | 32.22 | 27.78 | 0.000 | 5170.14 | 3.80 | 0.00505843 | 3.80 | 0.01543376 | 4.2622 | 21.11 | 0.00786946 | 21.11 | 0.00786946 | 49.5995 | 2153.37 | 0.00 | 5508.03 | 5508.03 | 0.42792841 | 16.60 | 12.91 | 0.00774965 | 36300.9 | 29.23 | 17.57 | 0.00774965 | 49172.3 | |
ROOM_1_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_1_FLR_6 | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 5994.130 | 4799.232 | 0.362105 | -999.0 | -999.000 | -999.0000 | 1.04708 | 1.00000 | 1020.7165 | 1004.8586 | 1.1818 | ROOM_1_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.362105 | 0.42792841 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | unknown | unknown | unknown | 8/21 16:00:00 | Sensible | 5458.49 | 5404.98 | 0.9106 | 0.42792841 | 0.362105 | 21.52 | 15.34 | 0.00854059 | 43327.5 | 9.47 | 9.47 | 0.00850000 | 30924.4 | -999.0 | -999.00 | -999.00 | -999.00 | 230.612 | 5227.87 | 30.77 | 0.00823264 | 18.27 | 0.01543376 | 4.2622 | 21.11 | 0.00855430 | 21.11 | 0.00855430 | 53.8577 | 4853.15 | 0.00 | 5997.06 | 4748.71 | 0.41102848 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999387 | 40732.0 | |
ROOM_2_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4984.911 | 4984.911 | 0.348274 | 0.00004361 | 124.955 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.348274 | 0.41158227 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 0.8692 | 0.886730 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 4984.91 | 4984.91 | 1.0000 | 0.41158227 | 0.348274 | 20.34 | 14.19 | 0.00774474 | 40104.1 | 32.22 | 18.56 | 0.00800000 | 52863.7 | 0.04360573 | 60.00 | 32.22 | 27.78 | 0.000 | 4984.91 | 3.80 | 0.00505843 | 3.80 | 0.01543195 | 4.4310 | 21.11 | 0.00786929 | 21.11 | 0.00786929 | 49.5985 | 2150.33 | 0.00 | 5308.17 | 5308.17 | 0.41158227 | 16.60 | 12.90 | 0.00774474 | 36288.5 | 29.25 | 17.58 | 0.00774474 | 49185.5 | |
ROOM_2_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_2_FLR_6 | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 5765.164 | 4615.909 | 0.348274 | -999.0 | -999.000 | -999.0000 | 1.04938 | 1.00000 | 1020.7191 | 1004.8586 | 1.1818 | ROOM_2_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 0.348274 | 0.41158227 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | unknown | unknown | unknown | 8/21 16:20:00 | Sensible | 5265.44 | 5212.09 | 0.9133 | 0.41158227 | 0.348274 | 21.53 | 15.35 | 0.00854199 | 43336.9 | 9.47 | 9.47 | 0.00850000 | 30924.4 | -999.0 | -999.00 | -999.00 | -999.00 | 221.803 | 5043.63 | 30.53 | 0.00823226 | 18.20 | 0.01543195 | 4.4310 | 21.11 | 0.00855635 | 21.11 | 0.00855635 | 53.8704 | 4667.76 | 0.00 | 5767.99 | 4567.32 | 0.39532788 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999387 | 40732.0 | |
ROOM_3_MULT9_FLR_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24025.872 | 24025.872 | 1.639986 | 0.00021019 | 600.509 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.639986 | 1.93810099 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 4.1895 | 4.273787 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 24025.87 | 24025.87 | 1.0000 | 1.93810099 | 1.639986 | 20.06 | 14.05 | 0.00770611 | 39721.2 | 32.22 | 18.56 | 0.00800000 | 52863.7 | 0.21016737 | 60.00 | 32.22 | 27.78 | 0.000 | 24025.87 | 3.80 | 0.00505843 | 3.80 | 0.09915400 | 6.0460 | 21.11 | 0.00787649 | 21.11 | 0.00787649 | 49.6431 | 10505.99 | 0.00 | 25467.99 | 25467.99 | 1.93810099 | 16.60 | 12.86 | 0.00770611 | 36190.6 | 29.49 | 17.63 | 0.00770611 | 49331.3 | |
ROOM_3_MULT9_FLR_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 27147.599 | 21735.868 | 1.639986 | -999.0 | -999.000 | -999.0000 | 1.02278 | 1.00000 | 1020.8073 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.639986 | 1.93810099 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | unknown | unknown | unknown | 8/21 13:20:00 | Sensible | 24742.76 | 24223.79 | 0.9114 | 1.93810099 | 1.639986 | 21.71 | 15.45 | 0.00858943 | 43641.8 | 9.47 | 9.47 | 0.00850000 | 30924.5 | -999.0 | -999.00 | -999.00 | -999.00 | 1044.451 | 23698.31 | 31.00 | 0.00823302 | 18.35 | 0.09915400 | 6.0460 | 21.11 | 0.00861236 | 21.11 | 0.00861236 | 54.2192 | 21979.50 | 0.00 | 27160.89 | 21507.07 | 1.86156065 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999387 | 40732.0 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22010.605 | 22010.605 | 1.463555 | 0.00019256 | 468.661 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 3.8381 | 3.915306 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 22010.61 | 22010.61 | 1.0000 | 1.72959840 | 1.463555 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.19253873 | 60.00 | 32.22 | 27.78 | 0.000 | 22010.61 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00790967 | 21.00 | 0.00790967 | 50.1902 | 7707.67 | 0.00 | 20905.99 | 20905.99 | 1.72959840 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.45 | 17.52 | 0.00800000 | 49021.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22152.628 | 22152.628 | 1.463616 | 0.00019380 | 472.168 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 3.8628 | 3.940569 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 22152.63 | 22152.63 | 1.0000 | 1.72967019 | 1.463616 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.19378109 | 60.00 | 32.22 | 27.78 | 0.000 | 22152.63 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00791124 | 21.00 | 0.00791124 | 50.2001 | 7849.06 | 0.00 | 21040.84 | 21040.84 | 1.72967019 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.53 | 17.54 | 0.00800000 | 49099.4 | |
PTAC_6 HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17814.081 | 17814.081 | 1.135973 | 0.00015585 | 440.187 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.135973 | 1.34246827 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 3.1063 | 3.168817 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 17814.08 | 17814.08 | 1.0000 | 1.34246827 | 1.135973 | 19.10 | 13.58 | 0.00760856 | 38489.1 | 32.11 | 18.53 | 0.00800000 | 52751.6 | 0.15582945 | 60.00 | 32.22 | 27.78 | 0.000 | 17814.08 | 3.80 | 0.00505843 | 3.80 | 0.12561561 | 11.0580 | 21.00 | 0.00792562 | 21.00 | 0.00792562 | 50.2901 | 8247.45 | 0.00 | 18592.25 | 18592.25 | 1.34246827 | 16.60 | 12.77 | 0.00760856 | 35943.7 | 30.19 | 17.78 | 0.00760856 | 49793.0 | |
PTAC_6 PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | PTAC_6 | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | unknown | No | 18804.381 | 15055.827 | 1.135973 | -999.0 | -999.000 | -999.0000 | 1.01820 | 1.00000 | 1021.1972 | 1004.8586 | 1.1818 | PTAC_6_PTAC_SUPPLY FAN | Fan:OnOff | 1.135973 | 1.34246827 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 17855.95 | 16918.54 | 0.9496 | 1.34246827 | 1.135973 | 24.79 | 16.73 | 0.00879918 | 47321.6 | 12.36 | 11.75 | 0.00850000 | 33874.3 | -999.0 | -999.00 | -999.00 | -999.00 | 723.462 | 17132.49 | 31.15 | 0.00823326 | 18.40 | 0.12561561 | 11.0580 | 24.00 | 0.00886954 | 24.00 | 0.00886954 | 46.8333 | 15222.73 | 0.00 | 18813.59 | 14897.34 | 1.28945092 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.38 | 14.55 | 0.00999387 | 40732.0 | |
VAV_FLR_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_FLR_1 | RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LOBBY_FLR_1; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 160773.887 | 124101.527 | 7.948903 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7558 | 1004.8586 | 1.1818 | VAV_FLR_1 FAN | Fan:VariableVolume | 7.948903 | 9.39384440 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | Sensible | 158044.58 | 143935.39 | 0.9830 | 9.39384440 | 7.948903 | 26.60 | 17.59 | 0.00909967 | 49938.1 | 11.07 | 11.07 | 0.00850000 | 32555.2 | -999.0 | -999.00 | -999.00 | -999.00 | 17469.949 | 140574.63 | 31.30 | 0.00823349 | 18.45 | 2.83030000 | 35.6062 | 24.00 | 0.00958019 | 24.00 | 0.00958019 | 50.5403 | 92398.68 | 0.00 | 161238.88 | 123055.54 | 9.02285855 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.33 | 13.32 | 0.00952545 | 37452.3 | |
VAV_FLR_1 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_1 | RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LOBBY_FLR_1; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25738.361 | 25738.361 | 2.384671 | 0.00022517 | 442.872 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_FLR_1 FAN | Fan:VariableVolume | 7.948903 | 9.39384440 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 4.4881 | 4.578409 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 25738.36 | 25738.36 | 1.0000 | 2.81815332 | 2.384671 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 0.22514744 | 60.00 | 32.22 | 27.78 | 0.000 | 25738.36 | 3.80 | 0.00505843 | 3.80 | 2.83030000 | 118.6872 | 21.00 | 0.00781650 | 21.00 | 0.00781514 | 49.5979 | 18738.58 | 0.00 | 26149.35 | 26149.35 | 2.81815332 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 11.95 | 8.02 | 0.00505843 | 24769.6 | |
VAV_FLR_6 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_FLR_6 | BANQUET_FLR_6; DINING_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 124623.907 | 93228.907 | 5.776235 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7599 | 1004.8586 | 1.1818 | VAV_FLR_6 FAN | Fan:VariableVolume | 5.776235 | 6.82623132 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 123826.17 | 113575.86 | 0.9936 | 6.82623132 | 5.776235 | 28.00 | 18.06 | 0.00910188 | 51369.0 | 11.06 | 11.06 | 0.00850000 | 32543.3 | -999.0 | -999.00 | -999.00 | -999.00 | 12776.803 | 111049.36 | 31.30 | 0.00823349 | 18.45 | 3.16750000 | 54.8368 | 23.99 | 0.01015627 | 23.99 | 0.01015627 | 53.5615 | 67227.56 | 0.00 | 124984.35 | 92479.00 | 6.55664679 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.87 | 12.86 | 0.00924089 | 36260.2 | |
VAV_FLR_6 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_6 | BANQUET_FLR_6; DINING_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 18703.313 | 18703.313 | 1.732871 | 0.00016362 | 321.822 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_FLR_6 FAN | Fan:VariableVolume | 5.776235 | 6.82623132 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 3.2614 | 3.326996 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 18703.31 | 18703.31 | 1.0000 | 2.04786940 | 1.732871 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.89 | 11.47 | 0.00800000 | 33150.5 | 0.16360805 | 60.00 | 32.22 | 27.78 | 0.000 | 18703.31 | 3.80 | 0.00505843 | 3.80 | 3.16750000 | 182.7892 | 21.00 | 0.00791043 | 21.00 | 0.00791044 | 50.1953 | 12444.05 | 0.00 | 19001.96 | 19001.96 | 2.04786940 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 11.95 | 8.02 | 0.00505843 | 24769.6 | |
VAV_FLR_0 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | VAV_FLR_0 | BASEMENT | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 56567.230 | 45300.169 | 3.205020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3798 | 1004.8586 | 1.1818 | VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 3.205020 | 3.78762375 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:30:00 | Sensible | 28283.62 | 26357.97 | 1.0000 | 2.52508284 | 2.136680 | 24.89 | 16.84 | 0.00889736 | 47673.1 | 11.03 | 11.03 | 0.00850000 | 32516.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28283.62 | 27.34 | 0.00822721 | 17.13 | 0.85445887 | 39.9900 | 24.00 | 0.00914097 | 24.00 | 0.00914145 | 48.2494 | 37320.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_FLR_0 HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_FLR_0 | BASEMENT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 59737.575 | 59737.575 | 3.205020 | 0.00026366 | 2534.053 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_FLR_0 SZVAV FAN | Fan:VariableVolume | 3.205020 | 3.78762375 | 4197.9300 | 999.8980 | 4.91759096 | 54.44 | 82.22 | 27.78 | 573482.06 | 10.4166 | 5.361048 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 59737.57 | 59737.57 | 1.0000 | 3.78762375 | 3.205020 | 16.41 | 12.13 | 0.00721578 | 34760.3 | 32.11 | 18.53 | 0.00800000 | 52750.5 | 0.26363442 | 60.00 | 32.22 | 27.78 | 0.000 | 59737.57 | 3.80 | 0.00505843 | 3.80 | 0.85445887 | 26.6600 | 21.00 | 0.00800000 | 21.56 | 0.00505843 | 31.1569 | 0.00 | 0.00 | 60197.64 | 60197.64 | 3.78762375 | 16.60 | 12.38 | 0.00721578 | 34949.2 | 32.21 | 18.14 | 0.00721578 | 50842.5 | |
PSZ_LAUNDRY COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 64765.760 | 51855.353 | 3.912500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7161 | 1004.8586 | 1.1818 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.912500 | 4.62370881 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | Sensible | 32382.88 | 32128.02 | 1.0000 | 3.08247268 | 2.608333 | 24.00 | 16.23 | 0.00854034 | 45854.8 | 11.54 | 11.41 | 0.00850000 | 33040.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32382.88 | 29.25 | 0.00823024 | 17.77 | 0.00000000 | 0.0000 | 24.00 | 0.00854034 | 24.00 | 0.00854034 | 45.1192 | 45590.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_LAUNDRY HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_LAUNDRY | LAUNDRY_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51620.626 | 51620.626 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.912500 | 4.62370881 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 51620.63 | 51620.63 | 1.0000 | 4.62370881 | 3.912500 | 21.00 | 14.37 | 0.00767319 | 40591.0 | 32.11 | 18.53 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51620.63 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00767319 | 21.00 | 0.00767319 | 48.7085 | 1373.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43995.800 | 33959.478 | 2.175040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0781 | 1004.8586 | 1.1818 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.175045 | 2.57042156 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 21997.90 | 19460.38 | 1.0000 | 1.71361058 | 1.450027 | 26.12 | 17.57 | 0.00927304 | 49892.1 | 11.51 | 11.40 | 0.00850000 | 33008.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21997.90 | 30.86 | 0.00823278 | 18.30 | 0.67638938 | 46.6467 | 23.99 | 0.00974253 | 23.99 | 0.00974673 | 51.4245 | 25286.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_CAFE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_CAFE | CAFE_FLR_1 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 42512.101 | 42512.101 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.175045 | 2.57042156 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 42512.10 | 42512.10 | 1.0000 | 2.57042156 | 2.175045 | 15.65 | 11.60 | 0.00699768 | 33431.1 | 32.11 | 18.53 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 42512.10 | 3.80 | 0.00505843 | 3.80 | 0.67638938 | 31.0977 | 21.00 | 0.00787293 | 21.00 | 0.00787276 | 49.9597 | 6746.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 52226.330 | 41221.198 | 2.696960 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9045 | 1004.8586 | 1.1818 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.696964 | 3.18721509 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | Sensible | 26113.17 | 21209.88 | 1.0000 | 2.12480652 | 1.797973 | 24.46 | 17.37 | 0.00971761 | 49318.9 | 11.55 | 11.41 | 0.00850000 | 33043.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26113.17 | 27.67 | 0.00822773 | 17.24 | 0.36735036 | 20.4314 | 23.95 | 0.00995254 | 23.97 | 0.01004284 | 53.0190 | 30855.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ_KITCHEN HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ_KITCHEN | KITCHEN_FLR_6 | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 43897.011 | 43897.011 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.696964 | 3.18721509 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:20:00 | Sensible | 43897.01 | 43897.01 | 1.0000 | 3.18721509 | 2.696964 | 18.40 | 12.80 | 0.00707185 | 36421.0 | 32.11 | 18.53 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43897.01 | 3.80 | 0.00505843 | 3.80 | 0.36735036 | 13.6209 | 20.71 | 0.00738934 | 21.00 | 0.00740328 | 47.0170 | 1165.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_FLR_1_OA_CONTROLLER | FixedDryBulb | 0.00 | 7.95 | - | |||
VAV_FLR_6_OA_CONTROLLER | FixedDryBulb | 0.00 | 5.78 | - | |||
VAV_FLR_0_OA_CONTROLLER | FixedDryBulb | 0.00 | 3.21 | - | |||
PSZ_LAUNDRY_OA_CONTROLLER | FixedDryBulb | 0.00 | 3.91 | - | |||
PSZ_CAFE_OA_CONTROLLER | FixedDryBulb | 0.68 | 2.18 | - | |||
PSZ_KITCHEN_OA_CONTROLLER | FixedDryBulb | 0.37 | 2.70 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_FLR_1_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_FLR_6_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_FLR_6_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2806.17 | 1356.00 | 173.00 |
RETAIL_1_FLR_1 | 2785.00 | 5490.00 | 103.67 |
RETAIL_2_FLR_1 | 2270.83 | 4351.83 | 16.33 |
MECH_FLR_1 | 1805.67 | 4560.17 | 0.00 |
STORAGE_FLR_1 | 75.33 | 8126.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 5293.67 | 5293.67 |
CAFE_FLR_1 | 6082.67 | 3039.67 | 1268.67 |
LOBBY_FLR_1 | 4531.83 | 2477.67 | 477.17 |
ROOM_1_FLR_3 | 649.00 | 7407.00 | 103.00 |
ROOM_2_FLR_3 | 1668.50 | 7169.83 | 840.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 703.50 | 8107.67 | 311.17 |
ROOM_5_FLR_3 | 247.67 | 7394.00 | 104.33 |
ROOM_6_FLR_3 | 1277.33 | 7026.00 | 483.33 |
CORRIDOR_FLR_3 | 4985.50 | 2740.83 | 2721.00 |
ROOM_1_FLR_6 | 1120.17 | 7260.83 | 432.00 |
ROOM_2_FLR_6 | 2177.83 | 7170.67 | 1325.17 |
ROOM_3_MULT9_FLR_6 | 842.17 | 7300.33 | 171.50 |
BANQUET_FLR_6 | 5580.83 | 2298.17 | 621.17 |
DINING_FLR_6 | 6467.33 | 1422.83 | 516.83 |
KITCHEN_FLR_6 | 8685.50 | 6464.83 | 6464.83 |
CORRIDOR_FLR_6 | 5338.00 | 3117.33 | 2664.50 |
Facility | 8760.00 | 8760.00 | 8311.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 1.00 | 0.00 | 1.00 |
ROOM_2_FLR_3 | 0.00 | 39.33 | 0.00 | 39.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 89.67 | 0.00 | 89.67 |
ROOM_5_FLR_3 | 0.00 | 0.33 | 0.00 | 0.33 |
ROOM_6_FLR_3 | 0.00 | 60.67 | 0.00 | 60.67 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 0.83 | 0.00 | 0.83 |
ROOM_2_FLR_6 | 0.00 | 38.83 | 0.00 | 38.83 |
ROOM_3_MULT9_FLR_6 | 0.00 | 1.00 | 0.00 | 1.00 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 116.50 | 0.00 | 116.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 1.055 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.607 | 0.136 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.555 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.629 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.762 | 0.051 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 30.315 | 0.146 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 6.070 | 0.107 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.01 | 422.44 | 5183.56 | 1.903 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.361 | 0.175 | 0.000 | 0.094 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.176 | 0.000 | 0.055 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.396 | 0.078 | 0.000 | 0.171 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.361 | 0.175 | 0.000 | 0.094 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.176 | 0.000 | 0.090 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.067 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.361 | 0.175 | 0.000 | 0.105 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.356 | 0.176 | 0.000 | 0.058 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.417 | 0.143 | 0.000 | 0.168 |
BANQUET_FLR_6 | 144.94 | 249.90 | 1010.89 | 5.267 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.94 | 249.90 | 1010.89 | 5.450 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 23.417 | 0.146 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.055 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 0.639 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.378 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.907 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 0.353 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 0.460 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 0.000 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 3.231 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.01 | 422.44 | 5183.56 | 1.284 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.000 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.94 | 249.90 | 1010.89 | 4.230 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.94 | 249.90 | 1010.89 | 4.275 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 4.211 | 0.002 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 0.000 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV_FLR_0 | 61.77 | 106.50 | 4826.41 | 1978.83 | 0.8545 | 0.854 |
RETAIL_1_FLR_1 | VAV_FLR_1 | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV_FLR_1 | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV_FLR_1 | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV_FLR_1 | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | PSZ_CAFE | 82.53 | 142.30 | 748.35 | 188.86 | 0.6764 | 0.676 |
LOBBY_FLR_1 | VAV_FLR_1 | 245.01 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 39.02 | 0.062 | ||
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 39.02 | 0.062 | ||
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | 24.52 | 0.837 | |||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 24.53 | 0.837 | ||
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 39.02 | 0.062 | ||
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 39.02 | 0.062 | ||
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 389.40 | 0.475 | ||
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 39.02 | 0.015 | ||
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 39.02 | 0.015 | ||
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 24.53 | 0.099 | ||
BANQUET_FLR_6 | VAV_FLR_6 | 144.94 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV_FLR_6 | 144.94 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | PSZ_KITCHEN | 12.90 | 22.24 | 314.87 | 103.30 | 0.3674 | 0.367 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 412.12 | 0.126 | ||
Total Facility | 872.97 | 1604.23 | 35184.81 | 11345.29 | 1.8982 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 43546861.73 | 0.00 | 43546861.73 | 0.00 | 43546861.73 | 26946214.98 | 0.00 | 907.80 | 7852.20 | 0.00 |
RETAIL_1_FLR_1 | 5951065.39 | 0.00 | 5951065.39 | 310101.36 | 6261166.74 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 4099915.31 | 0.00 | 4099915.31 | 119699.52 | 4219614.82 | 2892943.94 | 806.14 | 369.76 | 7584.10 | 0.00 |
MECH_FLR_1 | 3506135.90 | 0.00 | 3506135.90 | 282898.54 | 3789034.44 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 2460865.62 | 0.00 | 2460865.62 | 163216.88 | 2624082.50 | 1821682.01 | 894.67 | 364.63 | 7500.71 | 0.00 |
LAUNDRY_FLR_1 | 80193069.53 | 0.00 | 80193069.53 | 386283.51 | 80579353.04 | 0.00 | 0.00 | 0.00 | 8403.83 | 0.00 |
CAFE_FLR_1 | 38820656.04 | 0.00 | 38820656.04 | 685496.60 | 39506152.64 | 21330615.53 | 0.00 | 2592.34 | 6167.66 | 0.00 |
LOBBY_FLR_1 | 84354352.87 | 0.00 | 84354352.87 | 1958620.37 | 86312973.24 | 59728886.00 | 635.60 | 405.59 | 7718.80 | 0.00 |
ROOM_1_FLR_3 | 1482965.89 | 96628.97 | 1579594.85 | 179991.83 | 1759586.68 | 1946875.62 | 2433.33 | 5214.83 | 1111.83 | 0.00 |
ROOM_2_FLR_3 | 1455652.00 | 56102.52 | 1511754.52 | 179978.09 | 1691732.61 | 1946647.51 | 2432.67 | 5806.20 | 521.13 | 0.00 |
ROOM_3_MULT19_FLR_3 | 3829853.43 | 0.00 | 3829853.43 | 50219.74 | 3880073.16 | 26397887.27 | 8395.00 | 365.00 | 0.00 | 6057.14 |
ROOM_4_MULT19_FLR_3 | 19368467.49 | 109539.39 | 19478006.88 | 50233.47 | 19528240.35 | 26405105.73 | 2433.07 | 5222.03 | 1104.89 | 0.00 |
ROOM_5_FLR_3 | 1484422.67 | 96807.70 | 1581230.37 | 179991.83 | 1761222.20 | 1946875.62 | 2433.25 | 5214.92 | 1111.83 | 0.00 |
ROOM_6_FLR_3 | 1452363.61 | 91439.41 | 1543803.02 | 179978.09 | 1723781.11 | 1946647.51 | 2433.02 | 5380.17 | 946.81 | 0.00 |
CORRIDOR_FLR_3 | 2712625.43 | 0.00 | 2712625.43 | 217646.33 | 2930271.76 | 14972100.18 | 8760.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 370648.63 | 108181.16 | 478829.79 | 180028.86 | 658858.65 | 486718.90 | 2008.18 | 5225.00 | 1526.82 | 0.00 |
ROOM_2_FLR_6 | 364366.75 | 58918.49 | 423285.24 | 180015.12 | 603300.36 | 486661.88 | 2160.93 | 5820.80 | 778.27 | 0.00 |
ROOM_3_MULT9_FLR_6 | 2422903.94 | 108187.69 | 2531091.63 | 92109.06 | 2623200.69 | 3126920.42 | 2433.21 | 5214.96 | 1111.83 | 0.00 |
BANQUET_FLR_6 | 45525239.31 | 0.00 | 45525239.31 | 439585.22 | 45964824.53 | 37458366.31 | 52.20 | 1740.05 | 6967.75 | 0.00 |
DINING_FLR_6 | 47083240.69 | 0.00 | 47083240.69 | 439585.22 | 47522825.92 | 37458366.31 | 0.00 | 1119.15 | 7640.85 | 0.00 |
KITCHEN_FLR_6 | 62994439.47 | 0.00 | 62994439.47 | 393530.69 | 63387970.16 | 11584760.86 | 0.00 | 356.17 | 8403.83 | 0.00 |
CORRIDOR_FLR_6 | 585946.22 | 0.00 | 585946.22 | 385165.88 | 971112.10 | 3961413.96 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.22E+10 | 10829696.99 | 0.22E+10 | 18137997.94 | 0.23E+10 | 0.43E+10 | 8760.00 | 6705.86 | 8760.00 | 6057.14 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.3809 | 0.0000 | 1.3809 | 0.0000 | 1.3809 | 0.8545 | 0.00 | 907.80 | 7852.20 |
RETAIL_1_FLR_1 | 0.1887 | 0.0000 | 0.1887 | 0.0098 | 0.1985 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.1300 | 0.0000 | 0.1300 | 0.0038 | 0.1338 | 0.0917 | 806.14 | 369.76 | 7584.10 |
MECH_FLR_1 | 0.1112 | 0.0000 | 0.1112 | 0.0090 | 0.1201 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.0780 | 0.0000 | 0.0780 | 0.0052 | 0.0832 | 0.0578 | 894.67 | 364.63 | 7500.71 |
LAUNDRY_FLR_1 | 2.5429 | 0.0000 | 2.5429 | 0.0122 | 2.5552 | 0.0000 | 0.00 | 0.00 | 8403.83 |
CAFE_FLR_1 | 1.2310 | 0.0000 | 1.2310 | 0.0217 | 1.2527 | 0.6764 | 0.00 | 2592.34 | 6167.66 |
LOBBY_FLR_1 | 2.6749 | 0.0000 | 2.6749 | 0.0621 | 2.7370 | 1.8940 | 635.60 | 405.59 | 7718.80 |
ROOM_1_FLR_3 | 0.0470 | 0.0031 | 0.0501 | 0.0057 | 0.0558 | 0.0617 | 2433.33 | 5214.83 | 1111.83 |
ROOM_2_FLR_3 | 0.0462 | 0.0018 | 0.0479 | 0.0057 | 0.0536 | 0.0617 | 2432.67 | 5806.20 | 521.13 |
ROOM_4_MULT19_FLR_3 | 0.6142 | 0.0035 | 0.6176 | 0.0016 | 0.6192 | 0.8373 | 2433.07 | 5222.03 | 1104.89 |
ROOM_5_FLR_3 | 0.0471 | 0.0031 | 0.0501 | 0.0057 | 0.0558 | 0.0617 | 2433.25 | 5214.92 | 1111.83 |
ROOM_6_FLR_3 | 0.0461 | 0.0029 | 0.0490 | 0.0057 | 0.0547 | 0.0617 | 2433.02 | 5380.17 | 946.81 |
CORRIDOR_FLR_3 | 0.0860 | 0.0000 | 0.0860 | 0.0069 | 0.0929 | 0.4748 | 8760.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.0118 | 0.0034 | 0.0152 | 0.0057 | 0.0209 | 0.0154 | 2008.18 | 5225.00 | 1526.82 |
ROOM_2_FLR_6 | 0.0116 | 0.0019 | 0.0134 | 0.0057 | 0.0191 | 0.0154 | 2160.93 | 5820.80 | 778.27 |
ROOM_3_MULT9_FLR_6 | 0.0768 | 0.0034 | 0.0803 | 0.0029 | 0.0832 | 0.0992 | 2433.21 | 5214.96 | 1111.83 |
BANQUET_FLR_6 | 1.4436 | 0.0000 | 1.4436 | 0.0139 | 1.4575 | 1.1878 | 52.20 | 1740.05 | 6967.75 |
DINING_FLR_6 | 1.4930 | 0.0000 | 1.4930 | 0.0139 | 1.5069 | 1.1878 | 0.00 | 1119.15 | 7640.85 |
KITCHEN_FLR_6 | 1.9975 | 0.0000 | 1.9975 | 0.0125 | 2.0100 | 0.3674 | 0.00 | 356.17 | 8403.83 |
CORRIDOR_FLR_6 | 0.0186 | 0.0000 | 0.0186 | 0.0122 | 0.0308 | 0.1256 | 8760.00 | 0.00 | 0.00 |
Total Facility | 61.7713 | 0.3434 | 62.1147 | 0.4541 | 62.5688 | 73.9670 | 8760.00 | 6705.86 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_FLR_1 | 0.14E+09 | 0.00 | 0.14E+09 | 66941728.23 | 0.00 | 0.00 | 8760.00 | 0.00 |
VAV_FLR_6 | 0.13E+09 | 0.00 | 0.13E+09 | 74916732.61 | 0.00 | 0.00 | 8760.00 | 0.00 |
VAV_FLR_0 | 60817617.56 | 0.00 | 60817617.56 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
PSZ_LAUNDRY | 0.11E+09 | 0.00 | 0.11E+09 | 0.00 | 0.00 | 0.00 | 8403.83 | 0.00 |
PSZ_CAFE | 54216959.67 | 0.00 | 54216959.67 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
PSZ_KITCHEN | 87978085.19 | 0.00 | 87978085.19 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_FLR_1 | 4.4451 | 0.0000 | 4.4451 | 2.1227 | 0.00 | 0.00 | 8760.00 |
VAV_FLR_6 | 4.1013 | 0.0000 | 4.1013 | 2.3756 | 0.00 | 0.00 | 8760.00 |
VAV_FLR_0 | 1.9285 | 0.0000 | 1.9285 | 0.8545 | 0.00 | 0.00 | 8760.00 |
PSZ_LAUNDRY | 3.5514 | 0.0000 | 3.5514 | 0.0000 | 0.00 | 0.00 | 8403.83 |
PSZ_CAFE | 1.7192 | 0.0000 | 1.7192 | 0.6764 | 0.00 | 0.00 | 8760.00 |
PSZ_KITCHEN | 2.7898 | 0.0000 | 2.7898 | 0.3674 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_FLR_1 | 0.00 | 9.50 | 8394.33 | 0.00 | 0.00 | 0.00 | 356.17 | 0.00 | 0.00 | 0.00 |
VAV_FLR_6 | 0.00 | 9.50 | 7404.75 | 0.00 | 0.00 | 0.00 | 1345.75 | 0.00 | 0.00 | 0.00 |
VAV_FLR_0 | 0.00 | 0.00 | 7868.04 | 0.00 | 0.00 | 0.00 | 891.96 | 0.00 | 0.00 | 0.00 |
PSZ_LAUNDRY | 0.00 | 0.00 | 8403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_CAFE | 0.00 | 2572.47 | 6187.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ_KITCHEN | 0.00 | 356.17 | 8403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_FLR_1 | 0.0000 | 4.9581 | 4.4916 | 0.0000 | 0.0000 | 0.0000 | 3.3486 | 0.0000 | 0.0000 | 0.0000 |
VAV_FLR_6 | 0.0000 | 4.7727 | 4.2367 | 0.0000 | 0.0000 | 0.0000 | 3.3573 | 0.0000 | 0.0000 | 0.0000 |
VAV_FLR_0 | 0.0000 | 0.0000 | 2.0119 | 0.0000 | 0.0000 | 0.0000 | 1.1946 | 0.0000 | 0.0000 | 0.0000 |
PSZ_LAUNDRY | 0.0000 | 0.0000 | 3.7023 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ_CAFE | 0.0000 | 0.9448 | 2.0414 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ_KITCHEN | 0.0000 | 0.5133 | 2.8865 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 6 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1309 |
Defaulted Fields | 1279 |
Fields with Defaults | 4096 |
Autosized Fields | 364 |
Autosizable Fields | 530 |
Autocalculated Fields | 279 |
Autocalculatable Fields | 538 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6414.08 | 83422.92 | 13-MAY-05:00 | 411750.79 | 29-SEP-19:10 |
Electricity:Building | 3195.05 | 37866.17 | 02-JAN-02:10 | 208035.32 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 384.14 | 4218.04 | 02-JAN-02:10 | 29343.82 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 3187.96 | 37725.02 | 02-JAN-02:10 | 207793.99 | 02-JAN-20:10 |
InteriorLights:Electricity | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 241.03 | 2190.14 | 02-JAN-02:10 | 19711.29 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 241.03 | 2190.14 | 02-JAN-02:10 | 19711.29 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1526.14 | 13407.55 | 02-JAN-02:10 | 121238.68 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 22.10 | 252.63 | 02-JAN-02:10 | 1660.24 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.92 | 108.29 | 02-JAN-02:10 | 974.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 11.92 | 108.29 | 02-JAN-02:10 | 974.63 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 25.60 | 292.55 | 02-JAN-02:10 | 1922.56 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.80 | 125.40 | 02-JAN-02:10 | 1128.63 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 13.80 | 125.40 | 02-JAN-02:10 | 1128.63 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 41.66 | 441.91 | 02-JAN-02:10 | 3226.11 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 29.18 | 265.18 | 02-JAN-02:10 | 2386.66 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 29.18 | 265.18 | 02-JAN-02:10 | 2386.66 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 12.58 | 132.58 | 02-JAN-02:10 | 976.54 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 8.98 | 81.60 | 02-JAN-02:10 | 734.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 8.98 | 81.60 | 02-JAN-02:10 | 734.39 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.60 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 45.66 | 487.82 | 02-JAN-02:10 | 3526.71 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 31.32 | 284.60 | 02-JAN-02:10 | 2561.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 31.32 | 284.60 | 02-JAN-02:10 | 2561.44 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 350.46 | 3941.97 | 02-JAN-02:10 | 26504.19 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 201.46 | 1830.55 | 02-JAN-02:10 | 16474.99 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 201.46 | 1830.55 | 02-JAN-02:10 | 16474.99 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 35.36 | 389.80 | 01-JAN-02:10 | 2642.31 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 35.36 | 389.75 | 01-JAN-02:10 | 2642.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 492.14 | 5849.00 | 01-JAN-02:10 | 36399.59 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 297.14 | 2515.76 | 01-JAN-02:10 | 22870.56 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 297.14 | 2515.76 | 01-JAN-02:10 | 22870.56 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 492.27 | 5850.60 | 01-JAN-02:10 | 36409.55 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 297.22 | 2516.45 | 01-JAN-02:10 | 22876.81 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 297.22 | 2516.45 | 01-JAN-02:10 | 22876.81 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 35.36 | 389.80 | 01-JAN-02:10 | 2642.31 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 24.88 | 210.69 | 01-JAN-02:10 | 1915.33 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 35.36 | 389.75 | 01-JAN-02:10 | 2642.00 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 24.88 | 210.66 | 01-JAN-02:10 | 1915.11 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 92.26 | 838.30 | 02-JAN-02:10 | 7544.72 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.84 | 97.45 | 01-JAN-02:10 | 660.58 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.83 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.83 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.84 | 97.44 | 01-JAN-02:10 | 660.50 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.78 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 6.22 | 52.67 | 01-JAN-02:10 | 478.78 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 58.30 | 692.83 | 01-JAN-02:10 | 4311.66 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.20 | 298.00 | 01-JAN-02:10 | 2709.10 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 35.20 | 298.00 | 01-JAN-02:10 | 2709.10 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 230.86 | 2749.09 | 02-JAN-02:10 | 11246.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 230.86 | 2749.09 | 02-JAN-02:10 | 11246.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 55.00 | 499.79 | 02-JAN-02:10 | 4498.11 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 459.16 | 6380.86 | 02-JAN-02:10 | 19096.59 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.69 | 133.44 | 02-JAN-02:10 | 1200.92 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.69 | 133.44 | 02-JAN-02:10 | 1200.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 24.41 | 221.80 | 02-JAN-02:10 | 1996.23 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1661.82 | 24317.47 | 02-JAN-02:10 | 89286.95 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1661.82 | 24317.47 | 02-JAN-02:10 | 89286.95 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 872.72 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 437.38 | 6106.28 | 01-JAN-00:10 | 16602.84 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 11.51 | 365.00 | 01-JAN-00:10 | 365.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 44.24 | 732.80 | 27-NOV-23:30 | 2791.44 | 01-OCT-10:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 39.29 | 685.62 | 27-NOV-23:30 | 2472.90 | 03-JAN-05:00 |
LowTempRefrigeration:Refrigeration:Electricity | 15.86 | 0.00 | 01-JAN-11:10 | 1311.15 | 04-OCT-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 21.29 | 636.03 | 28-NOV-05:00 | 718.47 | 12-FEB-14:10 |
Fans:Electricity | 1041.33 | 24332.69 | 02-JAN-08:00 | 44612.31 | 29-SEP-19:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2037.66 | 24880.15 | 12-FEB-15:00 | 220445.76 | 16-OCT-12:10 |
ExteriorEquipment:Electricity | 841.97 | 10954.76 | 02-JAN-02:20 | 50420.89 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 22.24 | 382.76 | 02-JAN-02:20 | 1343.17 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 6414.08 | 83422.92 | 13-MAY-05:00 | 411750.79 | 29-SEP-19:10 |
ElectricityPurchased:Plant | 6414.08 | 83422.92 | 13-MAY-05:00 | 411750.79 | 29-SEP-19:10 |
Cogeneration:ElectricityPurchased | 6414.08 | 83422.92 | 13-MAY-05:00 | 411750.79 | 29-SEP-19:10 |
General:Cogeneration:ElectricityPurchased | 6414.08 | 83422.92 | 13-MAY-05:00 | 411750.79 | 29-SEP-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6414.08 | 83422.92 | 13-MAY-05:00 | 411750.79 | 29-SEP-19:10 |
ElectricityNet:Plant | 6414.08 | 83422.92 | 13-MAY-05:00 | 411750.79 | 29-SEP-19:10 |
Cogeneration:ElectricityNet | 6414.08 | 83422.92 | 13-MAY-05:00 | 411750.79 | 29-SEP-19:10 |
General:Cogeneration:ElectricityNet | 6414.08 | 83422.92 | 13-MAY-05:00 | 411750.79 | 29-SEP-19:10 |
General:Fans:Electricity | 1041.33 | 24332.69 | 02-JAN-08:00 | 44612.31 | 29-SEP-19:10 |
Cooling:Electricity | 974.09 | 0.00 | 01-JAN-00:10 | 177411.47 | 16-OCT-12:10 |
General:Cooling:Electricity | 974.09 | 0.00 | 01-JAN-00:10 | 177411.47 | 16-OCT-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorLights:Electricity | 322.34 | 0.00 | 01-JAN-07:00 | 20502.98 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 322.34 | 0.00 | 01-JAN-07:00 | 20502.98 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 789.09 | 9600.00 | 01-JAN-00:10 | 48128.80 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 2.14 | 47.91 | 30-APR-09:00 | 560.71 | 08-JAN-06:50 |
General:Pumps:Electricity | 2.14 | 47.91 | 30-APR-09:00 | 560.71 | 08-JAN-06:50 |
WIRED_LTG_ELECTRICITY | 53.72 | 0.00 | 01-JAN-00:10 | 4267.60 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4557.17 | 25154.57 | 14-AUG-01:10 | 369942.91 | 07-MAR-19:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:HVAC | 1.35 | 0.00 | 01-JAN-00:10 | 9851.94 | 08-JAN-06:50 |
Heating:NaturalGas | 172.04 | 0.00 | 01-JAN-09:40 | 142407.59 | 08-JAN-06:50 |
General:Heating:NaturalGas | 1.35 | 0.00 | 01-JAN-00:10 | 9851.94 | 08-JAN-06:50 |
NaturalGas:Plant | 2766.98 | 11792.67 | 14-AUG-01:10 | 291586.81 | 12-DEC-22:00 |
WaterSystems:NaturalGas | 2596.29 | 11792.67 | 14-AUG-01:10 | 231995.64 | 09-FEB-21:30 |
Water Heater:WaterSystems:NaturalGas | 2596.29 | 11792.67 | 14-AUG-01:10 | 231995.64 | 09-FEB-21:30 |
Boiler:Heating:NaturalGas | 170.69 | 0.00 | 01-JAN-09:40 | 132555.65 | 08-JAN-06:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:20 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:20 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:20 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:20 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:20 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 19-JAN-21:20 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 10068.41 | 110048.47 | 12-FEB-14:50 | 1004363.04 | 29-SEP-15:20 |
EnergyTransfer:Building | 5582.48 | 89154.95 | 12-FEB-15:00 | 418456.02 | 16-OCT-15:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 704.15 | 7929.16 | 13-DEC-04:00 | 37685.10 | 29-SEP-10:40 |
Refrigeration:EnergyTransfer | 186.43 | 4016.49 | 27-NOV-23:30 | 10427.35 | 28-JUL-06:10 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.21 | 2008.24 | 27-NOV-23:30 | 5213.68 | 28-JUL-06:10 |
General:Refrigeration:EnergyTransfer | 93.21 | 2008.24 | 27-NOV-23:30 | 5213.68 | 28-JUL-06:10 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.21 | 2008.24 | 27-NOV-23:30 | 5213.68 | 28-JUL-06:10 |
EnergyTransfer:Plant | 895.11 | 11527.73 | 22-AUG-03:00 | 123526.62 | 08-JAN-06:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.68 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.53 | 1996.46 | 28-NOV-05:00 | 2571.92 | 12-FEB-14:10 |
EnergyTransfer:Zone:BASEMENT | 443.25 | 5561.96 | 31-MAR-11:50 | 25340.10 | 17-OCT-20:00 |
Heating:EnergyTransfer | 29.46 | 0.00 | 01-JAN-08:00 | 36165.20 | 29-MAR-04:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 29.46 | 0.00 | 01-JAN-08:00 | 36165.20 | 29-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5459.81 | 85550.91 | 29-MAR-04:00 | 415837.91 | 16-OCT-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 443.25 | 5561.96 | 31-MAR-11:50 | 25340.10 | 17-OCT-20:00 |
General:Cooling:EnergyTransfer | 5459.81 | 85550.91 | 29-MAR-04:00 | 415837.91 | 16-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 443.25 | 5561.96 | 31-MAR-11:50 | 25340.10 | 17-OCT-20:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.71 | 0.04 | 11-FEB-06:20 | 7664.52 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.08 | 0.00 | 01-JAN-00:10 | 949.10 | 29-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.08 | 0.00 | 01-JAN-00:10 | 949.10 | 29-MAR-04:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.63 | 0.00 | 01-JAN-00:30 | 7664.52 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.63 | 0.00 | 01-JAN-00:30 | 7664.52 | 16-OCT-12:20 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 42.61 | 946.33 | 29-MAR-12:10 | 2456.69 | 29-SEP-19:20 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 42.61 | 946.33 | 29-MAR-12:10 | 2456.69 | 29-SEP-19:20 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 42.61 | 946.33 | 29-MAR-12:10 | 2456.69 | 29-SEP-19:20 |
EnergyTransfer:Zone:MECH_FLR_1 | 37.31 | 832.71 | 30-MAR-04:00 | 2788.53 | 29-SEP-20:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 37.31 | 832.71 | 30-MAR-04:00 | 2788.53 | 29-SEP-20:00 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 37.31 | 832.71 | 30-MAR-04:00 | 2788.53 | 29-SEP-20:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 22.40 | 17.80 | 29-MAR-04:00 | 1136.85 | 16-OCT-13:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 22.40 | 17.80 | 29-MAR-04:00 | 1136.85 | 16-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 22.40 | 17.80 | 29-MAR-04:00 | 1136.85 | 16-OCT-13:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 601.79 | 8515.46 | 30-MAR-04:00 | 38898.04 | 29-SEP-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 601.79 | 8515.46 | 30-MAR-04:00 | 38898.04 | 29-SEP-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 601.79 | 8515.46 | 30-MAR-04:00 | 38898.04 | 29-SEP-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 253.71 | 755.21 | 29-MAR-12:10 | 24371.24 | 15-OCT-11:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 253.71 | 755.21 | 29-MAR-12:10 | 24371.24 | 15-OCT-11:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 253.71 | 755.21 | 29-MAR-12:10 | 24371.24 | 15-OCT-11:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 906.16 | 18768.16 | 29-MAR-12:10 | 47072.80 | 15-OCT-12:00 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 906.16 | 18768.16 | 29-MAR-12:10 | 47072.80 | 15-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 906.16 | 18768.16 | 29-MAR-12:10 | 47072.80 | 15-OCT-12:00 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 84.54 | 0.00 | 01-JAN-08:00 | 17782.02 | 17-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 3.19 | 0.00 | 01-JAN-07:40 | 4445.96 | 28-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 3.19 | 0.00 | 01-JAN-07:40 | 4445.96 | 28-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 81.35 | 0.00 | 01-JAN-00:10 | 17782.02 | 17-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 81.35 | 0.00 | 01-JAN-00:10 | 17782.02 | 17-OCT-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 50.68 | 0.00 | 01-JAN-08:00 | 16265.50 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 5.01 | 0.00 | 01-JAN-08:00 | 4484.37 | 28-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 5.01 | 0.00 | 01-JAN-08:00 | 4484.37 | 28-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 45.67 | 0.00 | 01-JAN-00:10 | 16265.50 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 45.67 | 0.00 | 01-JAN-00:10 | 16265.50 | 29-SEP-15:30 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 459.02 | 0.00 | 01-JAN-00:10 | 91887.83 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 459.02 | 0.00 | 01-JAN-00:10 | 91887.83 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 459.02 | 0.00 | 01-JAN-00:10 | 91887.83 | 16-OCT-12:10 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 439.00 | 0.00 | 01-JAN-08:00 | 90842.45 | 14-OCT-22:00 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 2.65 | 0.00 | 01-JAN-00:10 | 10985.37 | 29-MAR-04:00 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 2.65 | 0.00 | 01-JAN-00:10 | 10985.37 | 29-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 436.34 | 0.00 | 01-JAN-00:40 | 90842.45 | 14-OCT-22:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 436.34 | 0.00 | 01-JAN-00:40 | 90842.45 | 14-OCT-22:00 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 80.32 | 0.00 | 01-JAN-11:00 | 15327.37 | 29-SEP-08:20 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 3.29 | 0.00 | 01-JAN-07:00 | 4170.14 | 28-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 3.29 | 0.00 | 01-JAN-07:00 | 4170.14 | 28-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 77.04 | 0.00 | 01-JAN-00:10 | 15327.37 | 29-SEP-08:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 77.04 | 0.00 | 01-JAN-00:10 | 15327.37 | 29-SEP-08:20 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 49.86 | 0.00 | 01-JAN-08:00 | 15265.26 | 30-SEP-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 4.90 | 0.00 | 01-JAN-07:10 | 4206.03 | 28-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 4.90 | 0.00 | 01-JAN-07:10 | 4206.03 | 28-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 44.96 | 0.00 | 01-JAN-00:10 | 15265.26 | 30-SEP-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 44.96 | 0.00 | 01-JAN-00:10 | 15265.26 | 30-SEP-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 152.67 | 0.00 | 01-JAN-00:10 | 17363.65 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 152.67 | 0.00 | 01-JAN-00:10 | 17363.65 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 152.67 | 0.00 | 01-JAN-00:10 | 17363.65 | 16-OCT-12:30 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 21.13 | 0.00 | 01-JAN-08:00 | 4744.03 | 17-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.40 | 0.00 | 01-JAN-08:00 | 1361.26 | 28-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.40 | 0.00 | 01-JAN-08:00 | 1361.26 | 28-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 18.73 | 0.00 | 01-JAN-00:10 | 4744.03 | 17-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 18.73 | 0.00 | 01-JAN-00:10 | 4744.03 | 17-OCT-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 13.48 | 0.00 | 01-JAN-08:00 | 4394.89 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 2.98 | 0.00 | 01-JAN-08:00 | 1380.79 | 13-DEC-04:30 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 2.98 | 0.00 | 01-JAN-08:00 | 1380.79 | 13-DEC-04:30 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.50 | 0.00 | 01-JAN-00:10 | 4394.89 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 10.50 | 0.00 | 01-JAN-00:10 | 4394.89 | 29-SEP-15:30 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 121.84 | 0.00 | 01-JAN-08:00 | 21893.37 | 17-OCT-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.96 | 0.00 | 01-JAN-07:20 | 5657.01 | 28-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.96 | 0.00 | 01-JAN-07:20 | 5657.01 | 28-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 116.87 | 0.00 | 01-JAN-00:10 | 21893.37 | 17-OCT-15:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 116.87 | 0.00 | 01-JAN-00:10 | 21893.37 | 17-OCT-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 473.59 | 10221.85 | 29-MAR-12:10 | 22275.80 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 473.59 | 10221.85 | 29-MAR-12:10 | 22275.80 | 29-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 473.59 | 10221.85 | 29-MAR-12:10 | 22275.80 | 29-SEP-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 498.62 | 10915.46 | 29-MAR-12:10 | 23459.44 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 498.62 | 10915.46 | 29-MAR-12:10 | 23459.44 | 29-SEP-21:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 498.62 | 10915.46 | 29-MAR-12:10 | 23459.44 | 29-SEP-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 610.94 | 5571.79 | 13-DEC-04:00 | 32626.15 | 29-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 610.94 | 5571.79 | 13-DEC-04:00 | 32626.15 | 29-SEP-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 71.65 | 0.00 | 01-JAN-00:10 | 11614.73 | 29-SEP-12:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 71.65 | 0.00 | 01-JAN-00:10 | 11614.73 | 29-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 71.65 | 0.00 | 01-JAN-00:10 | 11614.73 | 29-SEP-12:50 |
PlantLoopHeatingDemand:Facility | 802.72 | 9088.53 | 04-AUG-00:30 | 119635.61 | 08-JAN-06:50 |
PlantLoopHeatingDemand:Plant | 699.43 | 9088.53 | 04-AUG-00:30 | 48539.47 | 02-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 699.43 | 9088.53 | 04-AUG-00:30 | 48539.47 | 02-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 699.43 | 9088.53 | 04-AUG-00:30 | 48539.47 | 02-FEB-07:10 |
EnergyTransfer:HVAC | 3590.82 | 0.00 | 02-JAN-09:00 | 586560.80 | 18-JUL-18:10 |
HeatingCoils:EnergyTransfer | 104.37 | 0.00 | 01-JAN-09:40 | 100473.97 | 08-JAN-06:50 |
PlantLoopHeatingDemand:HVAC | 103.29 | 0.00 | 01-JAN-09:40 | 92592.42 | 08-JAN-06:50 |
HeatingCoils:PlantLoopHeatingDemand | 103.29 | 0.00 | 01-JAN-09:40 | 92592.42 | 08-JAN-06:50 |
CoolingCoils:EnergyTransfer | 3486.45 | 0.00 | 01-JAN-00:10 | 586560.80 | 18-JUL-18:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 699.43 | 9088.53 | 04-AUG-00:30 | 48539.47 | 02-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 699.43 | 9088.53 | 04-AUG-00:30 | 48539.47 | 02-FEB-07:10 |
Boilers:EnergyTransfer | 102.47 | 0.00 | 01-JAN-09:40 | 93285.61 | 08-JAN-06:50 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -443.252 | 0.000 | 0.000 | 133.911 | 241.034 | 143.105 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -74.798 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.082 | -54.630 | 0.000 | 0.000 | 15.167 | 11.918 | 10.186 | 36.051 | 0.000 | 0.030 | 0.000 | 0.000 | -15.863 | 0.000 | -2.490 | -0.451 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -42.606 | 0.000 | 0.000 | 16.376 | 13.801 | 11.795 | 0.000 | 0.000 | 0.014 | 1.702 | 0.000 | 0.000 | 0.000 | -1.082 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -37.314 | 0.000 | 0.000 | 3.433 | 29.185 | 12.471 | 0.000 | 0.000 | 0.028 | 0.000 | 0.000 | 0.000 | 0.000 | -2.620 | -5.183 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -22.404 | 0.000 | 0.000 | 2.831 | 8.980 | 3.598 | 0.000 | 0.000 | 0.023 | 8.268 | 0.000 | 0.000 | 0.000 | -1.296 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -601.788 | 0.000 | 0.000 | 10.551 | 5.547 | 658.131 | 0.000 | 0.000 | 0.036 | 0.000 | 0.000 | 0.000 | 0.000 | -3.793 | -68.685 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -253.717 | 0.000 | 0.000 | 183.051 | 31.322 | 14.341 | 98.280 | 0.000 | 0.065 | 0.001 | 0.000 | -51.681 | 0.000 | -6.470 | -15.190 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -906.160 | 0.000 | 0.000 | 542.851 | 201.459 | 148.998 | 133.941 | 0.000 | 0.202 | 0.000 | 0.000 | -68.808 | 0.000 | -18.269 | -34.213 |
ROOM_1_FLR_3 | 3.185 | -81.350 | 0.000 | 0.000 | 0.000 | 0.000 | 9.622 | 24.885 | 10.478 | 72.115 | 0.000 | 0.165 | 7.703 | 0.000 | -39.849 | 0.000 | -6.955 | -0.000 |
ROOM_2_FLR_3 | 5.013 | -45.665 | 0.000 | 0.000 | 0.000 | 0.000 | 9.132 | 24.882 | 10.477 | 48.097 | 0.000 | 0.119 | 0.000 | 0.000 | -43.304 | 0.000 | -7.518 | -1.231 |
ROOM_3_MULT19_FLR_3 | 0.000 | -459.014 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 297.141 | 194.997 | 367.303 | 0.000 | 0.141 | 0.011 | 0.000 | -343.753 | 0.000 | -48.553 | -8.262 |
ROOM_4_MULT19_FLR_3 | 2.653 | -436.307 | 0.000 | 0.000 | 0.000 | 0.000 | 178.088 | 297.222 | 195.050 | 96.867 | 0.000 | 0.668 | 0.002 | 0.000 | -230.427 | 0.000 | -84.600 | -19.215 |
ROOM_5_FLR_3 | 3.285 | -77.037 | 0.000 | 0.000 | 0.000 | 0.000 | 9.617 | 24.885 | 10.478 | 67.567 | 0.000 | 0.165 | 6.954 | 0.000 | -38.930 | 0.000 | -6.982 | -0.002 |
ROOM_6_FLR_3 | 4.902 | -44.955 | 0.000 | 0.000 | 0.000 | 0.000 | 9.296 | 24.882 | 10.477 | 43.736 | 0.000 | 0.115 | 0.943 | 0.000 | -41.006 | 0.000 | -8.391 | -0.002 |
CORRIDOR_FLR_3 | 0.000 | -152.660 | 0.000 | 0.000 | 0.000 | 0.000 | 105.372 | 92.258 | 0.000 | 65.504 | 0.000 | 0.081 | 0.000 | 0.000 | -61.589 | 0.000 | -8.580 | -40.387 |
ROOM_1_FLR_6 | 2.395 | -18.733 | 0.000 | 0.000 | 0.000 | 0.000 | 2.409 | 6.221 | 2.620 | 17.279 | 0.000 | 0.041 | 0.000 | 0.000 | -9.746 | 0.000 | -1.783 | -0.704 |
ROOM_2_FLR_6 | 2.981 | -10.494 | 0.000 | 0.000 | 0.000 | 0.000 | 2.283 | 6.220 | 2.619 | 11.349 | 0.000 | 0.029 | 0.000 | 0.000 | -10.673 | 0.000 | -1.888 | -2.427 |
ROOM_3_MULT9_FLR_6 | 4.962 | -116.870 | 0.000 | 0.000 | 0.000 | 0.000 | 21.650 | 35.197 | 23.098 | 90.450 | 0.000 | 0.230 | 0.003 | 0.000 | -46.214 | 0.000 | -10.352 | -2.150 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -473.590 | 0.000 | 0.000 | 319.762 | 55.004 | 175.857 | 9.339 | 0.000 | 0.043 | 0.000 | 0.000 | -34.339 | 0.000 | -4.166 | -47.910 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -498.618 | 0.000 | 0.000 | 317.431 | 55.004 | 175.857 | 8.781 | 0.000 | 0.041 | 0.000 | 0.000 | -35.337 | 0.000 | -4.242 | -18.917 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -610.936 | 0.000 | 0.000 | 27.942 | 14.685 | 554.015 | 23.918 | 0.000 | 0.036 | 27.496 | 0.000 | -33.247 | 0.000 | -3.909 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | -71.648 | 0.000 | 0.000 | 0.000 | 0.000 | 28.211 | 24.410 | 0.000 | 31.425 | 0.000 | 0.035 | 18.643 | 0.000 | -27.321 | 0.000 | -3.755 | -0.000 |
Total Facility | 29.377 | -1514.733 | 0.082 | -3945.016 | 0.000 | 0.000 | 1948.985 | 1526.141 | 2368.647 | 1222.002 | 0.000 | 2.308 | 71.730 | 0.000 | -1132.086 | 0.000 | -237.695 | -339.727 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 17-OCT-20:00 | 0.00 | 0.00 | 0.00 | -25333.36 | 0.00 | 0.00 | 5183.71 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9194.17 |
RETAIL_1_FLR_1 | 16-OCT-12:20 | 0.00 | 0.00 | 0.00 | -7664.50 | 0.00 | 0.00 | 149.35 | 270.73 | 252.59 | 8422.43 | 0.00 | 124.67 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1555.26 |
RETAIL_2_FLR_1 | 29-SEP-19:20 | 0.00 | 0.00 | 0.00 | -2456.14 | 0.00 | 0.00 | 610.42 | 1128.63 | 793.93 | 0.00 | 0.00 | 16.05 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -92.89 |
MECH_FLR_1 | 29-SEP-20:00 | 0.00 | 0.00 | 0.00 | -2788.21 | 0.00 | 0.00 | 129.09 | 2386.66 | 839.45 | 0.00 | 0.00 | 10.41 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -577.39 |
STORAGE_FLR_1 | 16-OCT-13:00 | 0.00 | 0.00 | 0.00 | -1136.87 | 0.00 | 0.00 | 28.86 | 204.00 | 89.22 | 0.00 | 0.00 | 60.71 | 754.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 29-SEP-20:00 | 0.00 | 0.00 | 0.00 | -38897.97 | 0.00 | 0.00 | 408.86 | 453.60 | 44299.38 | 0.00 | 0.00 | 14.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6278.08 |
CAFE_FLR_1 | 15-OCT-11:40 | 0.00 | 0.00 | 0.00 | -24372.88 | 0.00 | 0.00 | 2968.41 | 853.81 | 406.43 | 23453.20 | 0.00 | 198.56 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3507.53 |
LOBBY_FLR_1 | 15-OCT-12:00 | 0.00 | 0.00 | 0.00 | -47078.36 | 0.00 | 0.00 | 8812.42 | 5491.66 | 4222.82 | 30767.25 | 0.00 | 567.21 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2783.00 |
ROOM_1_FLR_3 | 26-MAY-18:01 | 0.00 | -19671.36 | 0.00 | 0.00 | 0.00 | 0.00 | 335.50 | 1704.65 | 484.65 | 784.00 | 0.00 | 0.00 | 16602.14 | 0.00 | -0.00 | 0.00 | -239.58 | 0.00 |
ROOM_2_FLR_3 | 18-APR-16:51 | 0.00 | -20327.23 | 0.00 | 0.00 | 0.00 | 0.00 | 164.66 | 536.23 | 505.67 | 4870.14 | 0.00 | 0.00 | 14563.86 | 0.00 | -0.00 | 0.00 | -313.33 | 0.00 |
ROOM_3_MULT19_FLR_3 | 16-OCT-12:10 | 0.00 | -91890.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6403.76 | 2352.88 | 99909.65 | 0.00 | 1223.32 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17998.89 |
ROOM_4_MULT19_FLR_3 | 26-MAY-18:01 | 0.00 | -110212.20 | 0.00 | 0.00 | 0.00 | 0.00 | 5895.15 | 20360.36 | 9021.83 | 0.00 | 0.00 | 0.00 | 80877.75 | 0.00 | -4441.97 | 0.00 | -1500.92 | 0.00 |
ROOM_5_FLR_3 | 11-MAR-09:02 | 0.00 | -17147.86 | 0.00 | 0.00 | 0.00 | 0.00 | 130.71 | 1072.59 | 653.23 | 13754.10 | 0.00 | 0.00 | 1594.83 | 0.00 | -0.00 | 0.00 | -57.60 | 0.00 |
ROOM_6_FLR_3 | 27-MAY-08:51 | 0.00 | -17566.73 | 0.00 | 0.00 | 0.00 | 0.00 | 107.49 | 1072.46 | 653.15 | 8776.82 | 0.00 | 0.00 | 7155.05 | 0.00 | -0.00 | 0.00 | -198.24 | 0.00 |
CORRIDOR_FLR_3 | 16-OCT-12:30 | 0.00 | -17361.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1165.83 | 2095.76 | 0.00 | 16425.43 | 0.00 | 343.08 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2668.69 |
ROOM_1_FLR_6 | 26-MAY-18:01 | 0.00 | -5216.02 | 0.00 | 0.00 | 0.00 | 0.00 | 83.88 | 426.16 | 121.16 | 140.38 | 0.00 | 0.00 | 4504.26 | 0.00 | -0.00 | 0.00 | -59.82 | 0.00 |
ROOM_2_FLR_6 | 22-FEB-17:01 | 0.00 | -5305.58 | 0.00 | 0.00 | 0.00 | 0.00 | 48.24 | 134.06 | 126.42 | 541.77 | 0.00 | 0.00 | 4532.09 | 0.00 | -0.00 | 0.00 | -76.99 | 0.00 |
ROOM_3_MULT9_FLR_6 | 19-NOV-10:54 | 0.00 | -24414.30 | 0.00 | 0.00 | 0.00 | 0.00 | 332.95 | 1110.73 | 301.93 | 23031.15 | 0.00 | 75.56 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -438.02 |
BANQUET_FLR_6 | 29-SEP-21:10 | 0.00 | 0.00 | 0.00 | -22279.98 | 0.00 | 0.00 | 15643.54 | 2998.74 | 6747.90 | 0.00 | 0.00 | 7.84 | 0.00 | 0.00 | -574.50 | 0.00 | 0.00 | -2543.55 |
DINING_FLR_6 | 29-SEP-21:10 | 0.00 | 0.00 | 0.00 | -23463.92 | 0.00 | 0.00 | 15643.48 | 2998.74 | 6747.90 | 0.00 | 0.00 | 7.84 | 0.00 | 0.00 | -602.43 | 0.00 | 0.00 | -1331.61 |
KITCHEN_FLR_6 | 29-SEP-10:40 | 0.00 | 0.00 | 0.00 | -32614.87 | 0.00 | 0.00 | 309.24 | 333.59 | 24375.41 | 4958.05 | 0.00 | 162.43 | 2476.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 29-SEP-12:50 | 0.00 | -11613.87 | 0.00 | 0.00 | 0.00 | 0.00 | 308.46 | 554.51 | 0.00 | 7068.59 | 0.00 | 163.13 | 3519.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-OCT-15:12 | 0.00 | -278254.37 | 0.00 | -165850.19 | 0.00 | 0.00 | 52501.18 | 33804.24 | 74028.09 | 154109.61 | 0.00 | 3051.32 | 126610.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 29-MAR-04:00 | 0.00 | 0.00 | 949.14 | 0.00 | 0.00 | 0.00 | 805.49 | 108.29 | 144.34 | 0.00 | 0.00 | 0.00 | 464.58 | 0.00 | -2314.66 | 0.00 | -157.18 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 28-MAR-08:62 | 12601.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.74 | 842.75 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4193.73 | 0.00 | -310.85 | -9500.49 |
ROOM_2_FLR_3 | 30-MAR-08:62 | 12339.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.43 | 842.65 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1255.69 | 0.00 | -324.56 | -12158.85 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 05-FEB-17:13 | 46502.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4619.83 | 7549.35 | 7845.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13434.66 | 0.00 | -999.84 | -52082.27 |
ROOM_5_FLR_3 | 28-MAR-08:62 | 11133.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.16 | 842.75 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4245.78 | 0.00 | -310.38 | -7980.16 |
ROOM_6_FLR_3 | 28-MAR-08:62 | 10686.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.28 | 842.65 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4234.97 | 0.00 | -308.39 | -7546.13 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 30-MAR-08:62 | 3483.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 210.69 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3.35 | 0.00 | -78.16 | -3752.76 |
ROOM_2_FLR_6 | 03-JAN-09:02 | 3420.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 210.66 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -190.12 | 0.00 | -63.70 | -3517.81 |
ROOM_3_MULT9_FLR_6 | 28-MAR-08:62 | 15542.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.62 | 1192.00 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4871.98 | 0.00 | -360.47 | -12741.06 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-MAR-08:62 | -32935.75 | 98215.72 | 578.31 | -98215.72 | 0.00 | 0.00 | 23093.49 | 53630.19 | 88294.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -121713.21 | 0.00 | -8978.77 | -1968.69 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_FLR_1 | 7.9880 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 7.9489 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_6 | 5.7762 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7762 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_0 | 3.2050 | 0.0000 | 106.4990 | 1.0000 | Calculated from schedules | 0.8545 | 3.2050 | 0.2666 | 1.0000 | Not calculated | 0.8545 | 0.2666 | ||
PSZ_LAUNDRY | 3.9125 | 0.0000 | 8.4000 | 1.0000 | Calculated from schedules | 0.0000 | 3.9125 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PSZ_CAFE | 2.1750 | 0.0000 | 142.3000 | 1.0000 | Calculated from schedules | 0.6764 | 2.1750 | 0.3110 | 1.0000 | Not calculated | 0.6764 | 0.3110 | ||
PSZ_KITCHEN | 2.6970 | 0.0000 | 22.2380 | 1.0000 | Calculated from schedules | 0.3674 | 2.6970 | 0.1362 | 1.0000 | Not calculated | 0.3674 | 0.1362 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_FLR_1 | 3.9940 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.3469 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_6 | 2.9390 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9272 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_FLR_0 | 0.9615 | 0.0000 | 106.4990 | 1.0000 | Calculated from schedules | 0.8545 | 0.9615 | 1.0000 | 1.0000 | Not calculated | 0.8545 | 0.8887 | ||
PSZ_LAUNDRY | 3.9125 | 0.0000 | 8.4000 | 1.0000 | Calculated from schedules | 0.0000 | 3.9125 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PSZ_CAFE | 2.1750 | 0.0000 | 142.3000 | 1.0000 | Calculated from schedules | 0.6764 | 2.1750 | 1.0000 | 1.0000 | Not calculated | 0.6764 | 0.3110 | ||
PSZ_KITCHEN | 2.6970 | 0.0000 | 22.2380 | 1.0000 | Calculated from schedules | 0.3674 | 2.6970 | 1.0000 | 1.0000 | Not calculated | 0.3674 | 0.1362 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV_FLR_0 | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.8545 | 1.0000 | 0.8545 | 1.000 | 0.8545 |
RETAIL_1_FLR_1 | VAV_FLR_1 | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV_FLR_1 | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | PSZ_CAFE | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.6764 | 1.0000 | 0.6764 | 1.000 | 0.6764 |
LOBBY_FLR_1 | VAV_FLR_1 | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV_FLR_6 | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.3674 | 1.0000 | 0.3674 | 1.000 | 0.3674 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_FLR_1 | 0.00 | 0.001240 | 1711.9288 | 0.0000 | 0.0000 | 0.0000 | |
VAV_FLR_6 | 0.00 | 0.003581 | 663.3149 | 0.0000 | 0.0000 | 0.0000 | |
VAV_FLR_0 | 0.000000 | 106.50 | 0.000432 | 1978.8302 | 0.8545 | 0.8545 | 0.8545 |
PSZ_LAUNDRY | 0.000000 | 8.40 | 0.000000 | 78.0395 | 0.0000 | 0.0000 | 0.0000 |
PSZ_CAFE | 0.000000 | 142.30 | 0.003581 | 188.8619 | 0.6764 | 0.6764 | 0.6764 |
PSZ_KITCHEN | 0.000000 | 22.24 | 0.003556 | 103.3045 | 0.3674 | 0.3674 | 0.3674 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV_FLR_0 | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 3.2050 | 3.2050 | 0.9615 | No | 0.8545 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5642 | 0.5642 | 0.1693 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3380 | 0.3380 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3740 | 0.3740 | 0.1122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1801 | 0.1801 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.9125 | 3.9125 | 3.9125 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | PSZ_CAFE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1750 | 2.1750 | 2.1750 | No | 0.6764 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5316 | 6.5316 | 2.8413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8254 | 2.8254 | 1.4636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9508 | 2.9508 | 1.4636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6970 | 2.6970 | 2.6970 | No | 0.3674 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_FLR_1 | 7.9880 | 7.9489 | 7.9880 | 3.3469 | 0.0000 | 1.0000 |
VAV_FLR_6 | 5.7762 | 5.7762 | 5.7762 | 2.9272 | 0.0000 | 1.0000 |
VAV_FLR_0 | 3.2050 | 3.2050 | 3.2050 | 0.9615 | 0.8545 | 1.0000 |
PSZ_LAUNDRY | 3.9125 | 3.9125 | 3.9125 | 3.9125 | 0.0000 | 1.0000 |
PSZ_CAFE | 2.1750 | 2.1750 | 2.1750 | 2.1750 | 0.6764 | 1.0000 |
PSZ_KITCHEN | 2.6970 | 2.6970 | 2.6970 | 2.6970 | 0.3674 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV_FLR_0 | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.9615 | 0.9615 | 0.9615 | No | 0.8545 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2821 | 0.2821 | 0.1693 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1690 | 0.1690 | 0.1376 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1870 | 0.1870 | 0.1122 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0900 | 0.0900 | 0.0866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | PSZ_LAUNDRY | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.9125 | 3.9125 | 3.9125 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | PSZ_CAFE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1750 | 2.1750 | 2.1750 | No | 0.6764 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV_FLR_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2658 | 3.2658 | 2.8413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4636 | 1.4636 | 1.4636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV_FLR_6 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4754 | 1.4754 | 1.4636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | PSZ_KITCHEN | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6970 | 2.6970 | 2.6970 | No | 0.3674 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_FLR_1 | 3.9940 | 3.3469 | 3.3469 | 3.3469 | 0.0000 | 1.0000 |
VAV_FLR_6 | 2.9390 | 2.9272 | 2.9272 | 2.9272 | 0.0000 | 1.0000 |
VAV_FLR_0 | 0.9615 | 0.9615 | 0.9615 | 0.9615 | 0.8545 | 1.0000 |
PSZ_LAUNDRY | 3.9125 | 3.9125 | 3.9125 | 3.9125 | 0.0000 | 1.0000 |
PSZ_CAFE | 2.1750 | 2.1750 | 2.1750 | 2.1750 | 0.6764 | 1.0000 |
PSZ_KITCHEN | 2.6970 | 2.6970 | 2.6970 | 2.6970 | 0.3674 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 116.50 |
Number of hours not met | 116.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1.35 | 9851.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 170.69 | 132555.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 974.09 | 177411.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1526.14 | 121238.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 322.34 | 20502.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.72 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 15.55 | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 11.51 | 365.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 22.24 | 1343.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 789.09 | 48128.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1041.33 | 44612.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 2.14 | 560.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 2596.29 | 231995.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.86 | 1311.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 21.29 | 718.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1706.06 | 6414.08 |
Natural Gas | 1788.84 | 4557.17 |
Additional | 0.00 | 0.00 |
Total | 3494.90 | 10971.25 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 134.52 |
Space Heating | 0.00 |
Space Cooling | 85.86 |
Fans (All) | 91.79 |
Service Water Heating | 0.00 |
Receptacle Equipment | 146.48 |
Miscellaneous (All) | 565.35 |
Subtotal | 565.35 |
Natural Gas [MJ/m2] | |
Space Heating | 15.16 |
Service Water Heating | 228.84 |
Miscellaneous (All) | 401.68 |
Subtotal | 401.68 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.91 |
Space Heating | 1.57 |
Space Cooling | 8.88 |
Fans (All) | 9.49 |
Service Water Heating | 23.66 |
Receptacle Equipment | 31.45 |
Miscellaneous | 11.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 486. | 5110. |
ELEVATOR_STANDBY_SCH | 7671. | 8760. |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 3061. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 3061. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 3061. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 3061. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | RETAIL_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | RETAIL_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8163.00 | 597.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8329.17 | 430.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8618.50 | 141.17 | 0.33 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8091.00 | 669.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8091.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 669.00 | 0.33 | 0.00 | 0.00 |
Average | 8676.44 | 83.55 | 0.02 | 0.00 | 0.00 |
Sum | 190881.67 | 1838.00 | 0.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 3991.00 | 163.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4153.67 | 0.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 3938.67 | 215.33 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 215.33 | 0.00 | 0.00 | 0.00 |
Average | 288869.83 | 17.21 | 0.00 | 0.00 | 0.00 |
Sum | 6355136.33 | 378.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8594.83 | 165.17 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8504.33 | 255.67 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 7623.67 | 1136.33 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8379.83 | 380.17 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 7832.83 | 927.17 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 7152.17 | 1607.83 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8388.67 | 371.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8194.50 | 565.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 6063.00 | 2697.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 7819.50 | 940.50 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8231.67 | 528.33 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8297.67 | 462.33 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8275.67 | 484.33 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 6297.50 | 2462.50 | 0.00 | 0.00 | 0.00 |
Min | 6063.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2697.00 | 0.00 | 0.00 | 0.00 |
Average | 8169.80 | 590.20 | 0.00 | 0.00 | 0.00 |
Sum | 179735.67 | 12984.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 514824.83 | 14506.17 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 35730.67 | 1472.33 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 591278.17 | 119138.83 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 1975417.33 | 140011.67 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 3773.33 | 380.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3951.33 | 202.67 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 3938.33 | 215.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 68383.00 | 31975.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 3769.00 | 385.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1131522.50 | 114192.50 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1146302.33 | 99412.67 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 99878.50 | 8390.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 73870.00 | 32076.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 1975417.33 | 140011.67 | 0.00 | 0.00 | 0.00 |
Average | 263325.24 | 25561.80 | 0.00 | 0.00 | 0.00 |
Sum | 5793155.33 | 562359.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405133E+11 | 24764.05 | 20-JAN-21:00 | 14.00 | 13.42 | 0.820597E+10 | 4837.37 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.321459E+11 | 23482.25 | 01-FEB-21:00 | 13.00 | 11.87 | 0.742515E+10 | 4837.36 | 13-FEB-22:10 | 14.00 | 13.42 |
March | 0.347050E+11 | 22387.78 | 24-MAR-21:00 | 13.00 | 11.87 | 0.820633E+10 | 4837.37 | 23-MAR-21:10 | 13.00 | 11.87 |
April | 0.331074E+11 | 22203.07 | 13-APR-21:00 | 14.00 | 13.42 | 0.797551E+10 | 4837.39 | 26-APR-21:49 | 16.00 | 15.39 |
May | 0.342374E+11 | 22273.53 | 04-MAY-19:55 | 17.00 | 15.07 | 0.824314E+10 | 4837.38 | 03-MAY-21:30 | 17.00 | 15.07 |
June | 0.327520E+11 | 21939.12 | 30-JUN-21:00 | 16.00 | 14.76 | 0.799853E+10 | 4837.39 | 16-JUN-21:00 | 16.00 | 14.76 |
July | 0.369143E+11 | 23197.52 | 26-JUL-20:00 | 17.00 | 16.37 | 0.823283E+10 | 4837.39 | 19-JUL-23:10 | 17.00 | 16.37 |
August | 0.377473E+11 | 23419.40 | 18-AUG-20:00 | 19.00 | 17.66 | 0.826766E+10 | 4837.40 | 11-AUG-22:00 | 19.00 | 17.66 |
September | 0.385072E+11 | 24438.49 | 29-SEP-20:00 | 25.00 | 13.58 | 0.797742E+10 | 4837.40 | 05-SEP-23:10 | 25.00 | 13.58 |
October | 0.417571E+11 | 25340.10 | 17-OCT-20:00 | 17.00 | 15.07 | 0.823658E+10 | 4837.37 | 04-OCT-04:00 | 17.00 | 15.07 |
November | 0.404555E+11 | 25182.79 | 29-NOV-21:00 | 11.00 | 6.33 | 0.796214E+10 | 4837.38 | 09-NOV-23:40 | 11.00 | 6.33 |
December | 0.404099E+11 | 24680.69 | 19-DEC-21:00 | 8.00 | 1.45 | 0.821884E+10 | 4837.36 | 08-DEC-22:10 | 8.00 | 1.45 |
Annual Sum or Average | 0.443252E+12 | 0.969501E+11 | ||||||||
Minimum of Months | 0.321459E+11 | 21939.12 | 8.00 | 1.45 | 0.742515E+10 | 4837.36 | 8.00 | 1.45 | ||
Maximum of Months | 0.417571E+11 | 25340.10 | 25.00 | 17.66 | 0.826766E+10 | 4837.40 | 25.00 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496610E+10 | 6958.07 | 14-JAN-12:40 | 25.33 | 11.70 | 0.684536E+09 | 455.26 | 18-JAN-22:10 | 16.83 | 13.41 |
February | 0.380559E+10 | 5944.34 | 02-FEB-12:30 | 19.50 | 11.91 | 0.610247E+09 | 440.13 | 01-FEB-22:10 | 19.50 | 11.91 |
March | 0.365743E+10 | 5684.36 | 11-MAR-12:50 | 24.00 | 13.82 | 0.673397E+09 | 447.01 | 23-MAR-21:10 | 13.83 | 13.26 |
April | 0.407194E+10 | 4306.95 | 02-APR-12:00 | 24.00 | 12.73 | 0.673707E+09 | 458.07 | 26-APR-21:10 | 16.00 | 15.39 |
May | 0.350060E+10 | 3365.26 | 03-MAY-12:30 | 24.00 | 15.05 | 0.687611E+09 | 465.25 | 04-MAY-21:10 | 17.00 | 15.07 |
June | 0.373377E+10 | 2397.01 | 27-JUN-12:50 | 24.00 | 18.72 | 0.690935E+09 | 464.37 | 27-JUN-21:10 | 17.00 | 16.37 |
July | 0.440975E+10 | 3418.40 | 31-JUL-12:40 | 28.00 | 21.19 | 0.738120E+09 | 477.29 | 31-JUL-21:10 | 18.95 | 17.72 |
August | 0.505015E+10 | 4033.39 | 30-AUG-12:40 | 23.67 | 17.83 | 0.748366E+09 | 478.82 | 18-AUG-21:10 | 23.67 | 17.83 |
September | 0.516172E+10 | 6699.99 | 29-SEP-13:00 | 36.00 | 18.20 | 0.709510E+09 | 491.81 | 29-SEP-21:10 | 24.58 | 13.52 |
October | 0.591253E+10 | 7664.52 | 16-OCT-12:20 | 35.37 | 17.35 | 0.732922E+09 | 491.79 | 16-OCT-21:10 | 18.33 | 11.06 |
November | 0.503935E+10 | 7205.64 | 19-NOV-12:30 | 26.50 | 15.22 | 0.670320E+09 | 447.24 | 27-NOV-22:10 | 16.00 | 5.61 |
December | 0.532040E+10 | 7109.76 | 19-DEC-12:30 | 25.50 | 11.42 | 0.687380E+09 | 463.15 | 05-DEC-22:10 | 25.50 | 11.42 |
Annual Sum or Average | 0.546293E+11 | 0.830705E+10 | ||||||||
Minimum of Months | 0.350060E+10 | 2397.01 | 19.50 | 11.42 | 0.610247E+09 | 440.13 | 13.83 | 5.61 | ||
Maximum of Months | 0.591253E+10 | 7664.52 | 36.00 | 21.19 | 0.748366E+09 | 491.81 | 25.50 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340782E+10 | 1870.86 | 18-JAN-21:10 | 17.83 | 13.82 | 0.899837E+09 | 569.55 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.304581E+10 | 1846.74 | 03-FEB-21:10 | 12.33 | 6.81 | 0.809009E+09 | 569.52 | 14-FEB-22:10 | 13.00 | 12.44 |
March | 0.333395E+10 | 1998.32 | 23-MAR-18:20 | 16.00 | 14.20 | 0.892015E+09 | 569.54 | 10-MAR-22:10 | 16.00 | 14.20 |
April | 0.346362E+10 | 2186.47 | 26-APR-19:10 | 17.00 | 15.62 | 0.885660E+09 | 569.55 | 25-APR-21:30 | 17.00 | 15.62 |
May | 0.351533E+10 | 2162.58 | 03-MAY-19:20 | 16.00 | 14.55 | 0.911207E+09 | 569.55 | 25-MAY-21:30 | 15.00 | 13.49 |
June | 0.358481E+10 | 2256.71 | 30-JUN-19:10 | 17.67 | 16.02 | 0.897936E+09 | 569.55 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.389470E+10 | 2341.10 | 19-JUL-19:10 | 20.67 | 18.37 | 0.937740E+09 | 569.55 | 17-JUL-22:10 | 20.67 | 18.37 |
August | 0.396477E+10 | 2335.14 | 18-AUG-19:10 | 19.83 | 17.97 | 0.946001E+09 | 569.55 | 10-AUG-22:10 | 19.83 | 17.97 |
September | 0.371604E+10 | 2456.69 | 29-SEP-19:20 | 27.67 | 14.55 | 0.906640E+09 | 569.55 | 20-SEP-22:10 | 27.67 | 14.55 |
October | 0.382262E+10 | 2375.39 | 16-OCT-19:20 | 22.33 | 14.20 | 0.933997E+09 | 569.55 | 13-OCT-22:10 | 22.33 | 14.20 |
November | 0.339761E+10 | 1831.90 | 10-NOV-21:10 | 15.83 | 14.61 | 0.882654E+09 | 569.55 | 09-NOV-23:10 | 15.83 | 14.61 |
December | 0.345904E+10 | 1973.40 | 05-DEC-21:10 | 16.17 | 9.15 | 0.904924E+09 | 569.55 | 06-DEC-22:19 | 15.00 | 9.64 |
Annual Sum or Average | 0.426061E+11 | 0.108076E+11 | ||||||||
Minimum of Months | 0.304581E+10 | 1831.90 | 12.33 | 6.81 | 0.809009E+09 | 569.52 | 13.00 | 9.64 | ||
Maximum of Months | 0.396477E+10 | 2456.69 | 27.67 | 18.37 | 0.946001E+09 | 569.55 | 27.67 | 18.37 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282992E+10 | 2028.18 | 18-JAN-21:00 | 18.00 | 13.89 | 0.190675E+09 | 120.45 | 20-JAN-23:10 | 13.83 | 13.83 |
February | 0.255108E+10 | 1850.66 | 03-FEB-21:00 | 13.00 | 7.33 | 0.172786E+09 | 120.45 | 24-FEB-22:10 | 13.00 | 11.29 |
March | 0.278779E+10 | 1907.71 | 23-MAR-20:00 | 14.00 | 13.42 | 0.190477E+09 | 120.45 | 10-MAR-22:10 | 14.00 | 13.42 |
April | 0.294556E+10 | 2258.48 | 26-APR-20:00 | 17.00 | 15.07 | 0.189437E+09 | 120.45 | 26-APR-21:10 | 16.00 | 15.39 |
May | 0.311363E+10 | 2397.15 | 04-MAY-19:55 | 17.00 | 15.07 | 0.196864E+09 | 120.45 | 25-MAY-22:10 | 15.00 | 13.80 |
June | 0.330025E+10 | 2573.70 | 30-JUN-19:40 | 16.67 | 15.66 | 0.194519E+09 | 120.45 | 30-JUN-21:00 | 16.10 | 16.10 |
July | 0.364505E+10 | 2686.37 | 19-JUL-19:40 | 19.67 | 18.38 | 0.202357E+09 | 120.45 | 05-JUL-21:00 | 19.67 | 18.38 |
August | 0.364459E+10 | 2581.90 | 18-AUG-20:00 | 19.00 | 17.66 | 0.203355E+09 | 120.45 | 27-AUG-23:10 | 15.02 | 14.97 |
September | 0.331777E+10 | 2788.53 | 29-SEP-20:00 | 25.00 | 13.58 | 0.194682E+09 | 120.45 | 20-SEP-21:00 | 25.00 | 13.58 |
October | 0.344301E+10 | 2665.93 | 16-OCT-20:00 | 21.00 | 13.07 | 0.200549E+09 | 120.45 | 11-OCT-22:10 | 21.00 | 13.07 |
November | 0.286116E+10 | 1904.75 | 10-NOV-21:00 | 16.00 | 14.77 | 0.188100E+09 | 120.45 | 28-NOV-23:10 | 9.33 | 4.92 |
December | 0.287366E+10 | 2063.33 | 05-DEC-21:00 | 16.00 | 9.09 | 0.192135E+09 | 120.45 | 21-DEC-22:10 | 10.67 | 10.67 |
Annual Sum or Average | 0.373135E+11 | 0.231593E+10 | ||||||||
Minimum of Months | 0.255108E+10 | 1850.66 | 13.00 | 7.33 | 0.172786E+09 | 120.45 | 9.33 | 4.92 | ||
Maximum of Months | 0.364505E+10 | 2788.53 | 25.00 | 18.38 | 0.203355E+09 | 120.45 | 25.00 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171992E+10 | 895.25 | 14-JAN-12:40 | 25.33 | 11.70 | 0.127289E+09 | 84.86 | 18-JAN-22:10 | 16.83 | 13.41 |
February | 0.156846E+10 | 761.11 | 01-FEB-12:10 | 25.67 | 14.54 | 0.115040E+09 | 82.08 | 01-FEB-22:10 | 13.00 | 11.77 |
March | 0.168938E+10 | 763.51 | 23-MAR-20:20 | 14.00 | 13.42 | 0.127143E+09 | 83.23 | 23-MAR-21:10 | 13.83 | 13.26 |
April | 0.180737E+10 | 811.30 | 26-APR-20:00 | 17.00 | 15.07 | 0.128998E+09 | 86.56 | 26-APR-21:10 | 16.00 | 15.39 |
May | 0.190660E+10 | 830.96 | 04-MAY-19:50 | 17.17 | 15.14 | 0.135168E+09 | 88.39 | 04-MAY-21:10 | 17.00 | 15.07 |
June | 0.196801E+10 | 863.45 | 29-JUN-18:20 | 21.00 | 18.14 | 0.136993E+09 | 89.46 | 28-JUN-21:10 | 21.00 | 18.14 |
July | 0.211650E+10 | 913.20 | 19-JUL-18:30 | 22.00 | 18.69 | 0.144857E+09 | 91.26 | 19-JUL-21:10 | 18.00 | 17.89 |
August | 0.210735E+10 | 863.80 | 18-AUG-19:40 | 19.33 | 17.79 | 0.144931E+09 | 90.74 | 18-AUG-21:10 | 19.00 | 17.66 |
September | 0.196663E+10 | 1012.03 | 29-SEP-13:00 | 36.00 | 18.20 | 0.136269E+09 | 92.65 | 29-SEP-21:10 | 24.58 | 13.52 |
October | 0.202956E+10 | 1136.85 | 16-OCT-13:00 | 34.10 | 16.81 | 0.140164E+09 | 91.65 | 16-OCT-21:10 | 18.33 | 11.06 |
November | 0.176117E+10 | 969.69 | 19-NOV-12:30 | 26.50 | 15.22 | 0.126166E+09 | 83.55 | 10-NOV-22:10 | 26.50 | 15.22 |
December | 0.176275E+10 | 945.93 | 19-DEC-12:40 | 25.67 | 11.48 | 0.128008E+09 | 85.00 | 05-DEC-22:10 | 25.67 | 11.48 |
Annual Sum or Average | 0.224037E+11 | 0.159103E+10 | ||||||||
Minimum of Months | 0.156846E+10 | 761.11 | 14.00 | 11.48 | 0.115040E+09 | 82.08 | 13.00 | 11.06 | ||
Maximum of Months | 0.211650E+10 | 1136.85 | 36.00 | 18.69 | 0.144931E+09 | 92.65 | 26.50 | 18.14 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.502796E+11 | 38080.01 | 18-JAN-21:00 | 18.00 | 13.89 | 0.649341E+09 | 381.66 | 18-JAN-22:10 | 16.83 | 13.41 |
February | 0.453272E+11 | 37798.91 | 01-FEB-21:00 | 13.00 | 11.87 | 0.587070E+09 | 381.52 | 03-FEB-03:49 | 12.67 | 3.85 |
March | 0.503031E+11 | 38022.08 | 23-MAR-20:00 | 14.00 | 13.42 | 0.652387E+09 | 381.52 | 14-MAR-04:10 | 14.00 | 13.42 |
April | 0.494160E+11 | 38298.17 | 26-APR-20:00 | 17.00 | 15.07 | 0.629507E+09 | 381.68 | 26-APR-21:10 | 16.00 | 15.39 |
May | 0.511156E+11 | 38350.08 | 04-MAY-19:55 | 17.00 | 15.07 | 0.650725E+09 | 381.69 | 02-MAY-21:10 | 17.00 | 15.07 |
June | 0.500620E+11 | 38394.80 | 29-JUN-20:00 | 16.00 | 14.76 | 0.630923E+09 | 381.69 | 26-JUN-21:10 | 16.00 | 14.76 |
July | 0.520683E+11 | 38568.55 | 19-JUL-20:00 | 19.00 | 18.34 | 0.649409E+09 | 381.69 | 03-JUL-21:10 | 19.00 | 18.34 |
August | 0.523593E+11 | 38483.30 | 17-AUG-20:00 | 19.00 | 17.66 | 0.652156E+09 | 381.69 | 29-AUG-21:10 | 17.05 | 15.13 |
September | 0.499729E+11 | 38898.04 | 29-SEP-20:00 | 25.00 | 13.58 | 0.629252E+09 | 381.72 | 22-SEP-00:10 | 25.00 | 13.58 |
October | 0.515949E+11 | 38593.89 | 16-OCT-20:00 | 21.00 | 13.07 | 0.649694E+09 | 381.70 | 05-OCT-00:10 | 21.00 | 13.07 |
November | 0.490248E+11 | 37920.79 | 01-NOV-20:00 | 15.00 | 11.57 | 0.628125E+09 | 381.66 | 09-NOV-22:10 | 16.00 | 14.87 |
December | 0.502641E+11 | 38092.29 | 05-DEC-21:00 | 16.00 | 9.09 | 0.649335E+09 | 381.52 | 04-DEC-22:49 | 16.00 | 9.09 |
Annual Sum or Average | 0.601788E+12 | 0.765792E+10 | ||||||||
Minimum of Months | 0.453272E+11 | 37798.91 | 13.00 | 9.09 | 0.587070E+09 | 381.52 | 12.67 | 3.85 | ||
Maximum of Months | 0.523593E+11 | 38898.04 | 25.00 | 18.34 | 0.652387E+09 | 381.72 | 25.00 | 18.34 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236506E+11 | 23355.86 | 14-JAN-12:20 | 25.67 | 11.76 | 0.101287E+11 | 6462.85 | 24-JAN-23:10 | 14.33 | 10.84 |
February | 0.186015E+11 | 19983.91 | 02-FEB-12:30 | 19.50 | 11.91 | 0.934544E+10 | 6462.67 | 14-FEB-01:00 | 14.00 | 13.42 |
March | 0.194535E+11 | 19370.08 | 11-MAR-12:30 | 24.00 | 13.82 | 0.100773E+11 | 6462.53 | 13-MAR-00:10 | 12.00 | 11.46 |
April | 0.191953E+11 | 15824.29 | 02-APR-12:00 | 24.00 | 12.73 | 0.103985E+11 | 6462.88 | 25-APR-21:30 | 14.50 | 13.91 |
May | 0.172947E+11 | 12289.80 | 04-MAY-12:00 | 24.00 | 16.55 | 0.107623E+11 | 6463.06 | 10-MAY-04:10 | 12.67 | 10.65 |
June | 0.177085E+11 | 9937.98 | 25-JUN-12:00 | 24.00 | 17.65 | 0.106672E+11 | 6462.91 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.204336E+11 | 12167.81 | 31-JUL-12:30 | 28.00 | 21.19 | 0.109986E+11 | 6462.90 | 05-JUL-22:10 | 28.00 | 21.19 |
August | 0.225759E+11 | 14417.31 | 27-AUG-12:00 | 23.00 | 18.42 | 0.110448E+11 | 6463.20 | 19-AUG-02:20 | 23.00 | 18.42 |
September | 0.224562E+11 | 21351.58 | 29-SEP-12:00 | 36.00 | 18.21 | 0.106452E+11 | 6463.81 | 22-SEP-01:39 | 36.00 | 18.21 |
October | 0.251537E+11 | 24371.24 | 15-OCT-11:40 | 32.00 | 16.72 | 0.109204E+11 | 6464.25 | 04-OCT-23:30 | 32.00 | 16.72 |
November | 0.226185E+11 | 23894.36 | 19-NOV-10:53 | 26.00 | 15.07 | 0.102306E+11 | 6462.80 | 10-NOV-22:30 | 26.00 | 15.07 |
December | 0.245724E+11 | 23019.73 | 19-DEC-12:30 | 25.50 | 11.42 | 0.101981E+11 | 6462.87 | 06-DEC-22:19 | 25.50 | 11.42 |
Annual Sum or Average | 0.253715E+12 | 0.125417E+12 | ||||||||
Minimum of Months | 0.172947E+11 | 9937.98 | 19.50 | 11.42 | 0.934544E+10 | 6462.53 | 12.00 | 10.65 | ||
Maximum of Months | 0.251537E+11 | 24371.24 | 36.00 | 21.19 | 0.110448E+11 | 6464.25 | 36.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.756676E+11 | 41717.85 | 14-JAN-12:40 | 25.33 | 11.70 | 0.313161E+11 | 19186.17 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.664671E+11 | 37589.91 | 02-FEB-19:05 | 13.83 | 10.17 | 0.280883E+11 | 19183.86 | 24-FEB-22:10 | 13.00 | 11.29 |
March | 0.716250E+11 | 37953.58 | 23-MAR-20:10 | 14.00 | 13.42 | 0.309176E+11 | 19184.32 | 10-MAR-22:10 | 14.00 | 13.42 |
April | 0.723529E+11 | 39142.14 | 26-APR-20:10 | 16.83 | 15.13 | 0.305068E+11 | 19186.26 | 25-APR-21:30 | 16.83 | 15.13 |
May | 0.731767E+11 | 39773.80 | 04-MAY-20:05 | 17.00 | 15.07 | 0.313108E+11 | 19186.22 | 02-MAY-22:10 | 17.00 | 15.07 |
June | 0.735436E+11 | 39216.69 | 27-JUN-20:10 | 17.00 | 16.37 | 0.308166E+11 | 19186.31 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.788374E+11 | 41273.35 | 19-JUL-20:10 | 18.83 | 18.28 | 0.320913E+11 | 19186.28 | 17-JUL-22:10 | 18.83 | 18.28 |
August | 0.809521E+11 | 41652.60 | 18-AUG-20:10 | 19.00 | 17.66 | 0.324414E+11 | 19186.24 | 10-AUG-22:10 | 19.00 | 17.66 |
September | 0.781261E+11 | 46010.34 | 29-SEP-20:10 | 24.93 | 13.57 | 0.311837E+11 | 19186.22 | 13-SEP-22:10 | 24.93 | 13.57 |
October | 0.830974E+11 | 47072.80 | 15-OCT-12:00 | 32.00 | 16.89 | 0.321352E+11 | 19186.29 | 13-OCT-22:10 | 32.00 | 16.89 |
November | 0.750342E+11 | 46047.38 | 19-NOV-10:53 | 26.00 | 15.07 | 0.306016E+11 | 19186.12 | 10-NOV-22:30 | 26.00 | 15.07 |
December | 0.772753E+11 | 41186.55 | 16-DEC-13:00 | 26.00 | 13.31 | 0.314661E+11 | 19186.14 | 06-DEC-22:19 | 26.00 | 13.31 |
Annual Sum or Average | 0.906155E+12 | 0.372875E+12 | ||||||||
Minimum of Months | 0.664671E+11 | 37589.91 | 13.83 | 10.17 | 0.280883E+11 | 19183.86 | 13.00 | 11.29 | ||
Maximum of Months | 0.830974E+11 | 47072.80 | 32.00 | 18.28 | 0.324414E+11 | 19186.31 | 32.00 | 18.28 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119639E+10 | 4805.38 | 02-JAN-16:12 | 12.33 | 8.28 | 98767456.24 | 56.70 | 03-JAN-03:00 | 4.00 | 3.12 |
February | 0.957296E+09 | 4840.75 | 20-FEB-16:12 | 17.00 | 10.93 | 88952288.31 | 56.70 | 26-FEB-04:19 | 10.33 | 9.21 |
March | 0.105263E+10 | 4869.54 | 11-MAR-16:12 | 20.67 | 12.56 | 98615675.45 | 56.70 | 30-MAR-01:39 | 4.37 | 3.79 |
April | 0.166242E+10 | 4766.14 | 16-APR-15:12 | 18.00 | 11.97 | 95939776.46 | 56.95 | 10-APR-04:49 | 18.00 | 11.97 |
May | 0.154040E+10 | 4917.89 | 26-MAY-18:01 | 13.83 | 9.72 | 99218468.36 | 56.69 | 17-MAY-04:40 | 13.83 | 9.72 |
June | 0.193769E+10 | 4607.34 | 03-JUN-15:12 | 19.00 | 14.25 | 96212611.20 | 56.69 | 01-JUN-03:39 | 19.00 | 14.25 |
July | 0.250059E+10 | 4656.65 | 09-JUL-15:11 | 21.67 | 16.27 | 99444860.18 | 56.69 | 22-JUL-04:10 | 16.00 | 16.00 |
August | 0.256140E+10 | 4635.67 | 29-AUG-15:11 | 22.67 | 17.12 | 99539020.75 | 56.69 | 31-AUG-04:10 | 14.17 | 14.07 |
September | 0.217428E+10 | 4691.41 | 19-SEP-15:12 | 18.67 | 14.12 | 96136873.97 | 56.69 | 20-SEP-04:10 | 11.17 | 10.03 |
October | 0.213193E+10 | 4850.50 | 12-OCT-15:12 | 22.00 | 13.53 | 99294052.24 | 56.69 | 12-OCT-04:19 | 22.00 | 13.53 |
November | 0.133443E+10 | 4866.97 | 04-NOV-15:12 | 16.47 | 10.72 | 95842818.18 | 56.69 | 05-NOV-04:00 | 7.00 | 5.54 |
December | 0.128846E+10 | 4785.57 | 31-DEC-16:12 | 15.33 | 10.50 | 98793608.84 | 57.04 | 10-DEC-03:00 | 15.33 | 10.50 |
Annual Sum or Average | 0.203379E+11 | 0.116676E+10 | ||||||||
Minimum of Months | 0.957296E+09 | 4607.34 | 12.33 | 8.28 | 88952288.31 | 56.69 | 4.00 | 3.12 | ||
Maximum of Months | 0.256140E+10 | 4917.89 | 22.67 | 17.12 | 99539020.75 | 57.04 | 22.00 | 16.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.458890E+09 | 4599.91 | 14-JAN-21:01 | 14.33 | 8.29 | 99952942.02 | 76.00 | 17-JAN-22:19 | 17.67 | 13.75 |
February | 0.453055E+09 | 5006.86 | 22-FEB-17:01 | 13.83 | 12.08 | 89726674.31 | 62.08 | 13-FEB-21:19 | 13.83 | 12.08 |
March | 0.584827E+09 | 4775.55 | 11-MAR-18:21 | 13.00 | 8.95 | 0.100604E+09 | 75.82 | 22-MAR-18:10 | 15.50 | 14.39 |
April | 0.996798E+09 | 5081.78 | 18-APR-16:51 | 15.00 | 11.13 | 0.104922E+09 | 92.53 | 26-APR-18:10 | 18.67 | 15.37 |
May | 0.106633E+10 | 4943.85 | 26-MAY-18:01 | 13.83 | 9.72 | 0.110145E+09 | 91.74 | 03-MAY-21:10 | 13.83 | 9.72 |
June | 0.124765E+10 | 4947.86 | 30-JUN-17:32 | 20.00 | 17.05 | 0.116264E+09 | 96.13 | 28-JUN-21:10 | 20.00 | 17.05 |
July | 0.163543E+10 | 4800.71 | 15-JUL-17:52 | 19.00 | 17.08 | 0.124314E+09 | 99.22 | 10-JUL-18:10 | 19.00 | 17.08 |
August | 0.154654E+10 | 4323.83 | 19-AUG-15:12 | 25.67 | 18.89 | 0.123425E+09 | 97.70 | 02-AUG-21:10 | 25.67 | 18.89 |
September | 0.125239E+10 | 4683.53 | 30-SEP-08:61 | 25.38 | 14.89 | 0.111289E+09 | 89.68 | 13-SEP-21:10 | 25.38 | 14.89 |
October | 0.111569E+10 | 4870.58 | 15-OCT-21:51 | 19.00 | 10.37 | 0.111076E+09 | 88.85 | 16-OCT-21:10 | 18.33 | 11.06 |
November | 0.585404E+09 | 4770.72 | 04-NOV-17:01 | 13.67 | 10.10 | 97621308.70 | 74.36 | 10-NOV-22:10 | 15.00 | 13.80 |
December | 0.474340E+09 | 4639.47 | 05-DEC-22:51 | 18.00 | 9.37 | 99980894.20 | 76.08 | 05-DEC-22:00 | 18.00 | 9.37 |
Annual Sum or Average | 0.114173E+11 | 0.128932E+10 | ||||||||
Minimum of Months | 0.453055E+09 | 4323.83 | 13.00 | 8.29 | 89726674.31 | 62.08 | 13.83 | 9.37 | ||
Maximum of Months | 0.163543E+10 | 5081.78 | 25.67 | 18.89 | 0.124314E+09 | 99.22 | 25.67 | 18.89 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.648092E+09 | 1122.63 | 14-JAN-12:20 | 25.67 | 11.76 | 0.00 | 0.00 | 01-JAN-00:10 | 25.67 | 11.76 |
February | 0.403969E+09 | 956.75 | 02-FEB-12:30 | 19.50 | 11.91 | 0.00 | 0.00 | 01-FEB-00:10 | 19.50 | 11.91 |
March | 0.318368E+09 | 838.34 | 11-MAR-12:50 | 24.00 | 13.82 | 0.00 | 0.00 | 01-MAR-00:10 | 24.00 | 13.82 |
April | 0.364678E+09 | 612.58 | 08-APR-12:30 | 22.50 | 16.84 | 0.00 | 0.00 | 01-APR-00:10 | 22.50 | 16.84 |
May | 0.227667E+09 | 441.95 | 04-MAY-12:00 | 24.00 | 16.55 | 0.00 | 0.00 | 01-MAY-00:10 | 24.00 | 16.55 |
June | 0.294369E+09 | 295.27 | 27-JUN-12:40 | 24.00 | 18.72 | 0.00 | 0.00 | 01-JUN-00:10 | 24.00 | 18.72 |
July | 0.432478E+09 | 463.29 | 31-JUL-12:30 | 28.00 | 21.19 | 0.00 | 0.00 | 01-JUL-00:10 | 28.00 | 21.19 |
August | 0.561712E+09 | 565.42 | 30-AUG-12:30 | 23.50 | 17.69 | 0.00 | 0.00 | 01-AUG-00:10 | 23.50 | 17.69 |
September | 0.628627E+09 | 1045.64 | 29-SEP-12:10 | 36.00 | 18.21 | 0.00 | 0.00 | 01-SEP-00:10 | 36.00 | 18.21 |
October | 0.796845E+09 | 1209.05 | 16-OCT-12:10 | 35.68 | 17.48 | 0.00 | 0.00 | 01-OCT-00:10 | 35.68 | 17.48 |
November | 0.648037E+09 | 1162.69 | 19-NOV-12:30 | 26.50 | 15.22 | 0.00 | 0.00 | 01-NOV-00:10 | 26.50 | 15.22 |
December | 0.714840E+09 | 1176.19 | 19-DEC-12:20 | 25.33 | 11.36 | 0.00 | 0.00 | 01-DEC-00:10 | 25.33 | 11.36 |
Annual Sum or Average | 0.603968E+10 | 0.00 | ||||||||
Minimum of Months | 0.227667E+09 | 295.27 | 19.50 | 11.36 | 0.00 | 0.00 | 19.50 | 11.36 | ||
Maximum of Months | 0.796845E+09 | 1209.05 | 36.00 | 21.19 | 0.00 | 0.00 | 36.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.314448E+09 | 1393.28 | 14-JAN-21:01 | 14.33 | 8.29 | 99803470.89 | 80.82 | 17-JAN-22:49 | 17.17 | 13.55 |
February | 0.314289E+09 | 1385.74 | 04-FEB-19:02 | 12.67 | 10.97 | 89242257.21 | 64.57 | 13-FEB-21:19 | 14.67 | 14.08 |
March | 0.363526E+09 | 1410.08 | 10-MAR-19:11 | 13.00 | 8.09 | 99156439.91 | 56.96 | 23-MAR-19:19 | 14.00 | 13.42 |
April | 0.477782E+09 | 1378.99 | 01-APR-21:51 | 15.00 | 8.92 | 98760259.03 | 80.73 | 25-APR-21:10 | 14.83 | 14.24 |
May | 0.555152E+09 | 1450.16 | 26-MAY-18:01 | 13.83 | 9.72 | 0.103349E+09 | 82.80 | 04-MAY-21:00 | 13.83 | 9.72 |
June | 0.596063E+09 | 1316.35 | 12-JUN-19:31 | 14.33 | 12.21 | 0.105671E+09 | 85.36 | 28-JUN-21:00 | 17.00 | 16.37 |
July | 0.692585E+09 | 1240.75 | 04-JUL-08:51 | 22.00 | 15.83 | 0.112734E+09 | 87.07 | 28-JUL-21:00 | 18.00 | 17.35 |
August | 0.647962E+09 | 1195.96 | 22-AUG-08:51 | 19.00 | 14.76 | 0.112146E+09 | 86.60 | 18-AUG-21:00 | 19.00 | 14.76 |
September | 0.555568E+09 | 1343.45 | 30-SEP-08:61 | 25.38 | 14.89 | 0.103965E+09 | 85.41 | 21-SEP-21:49 | 25.38 | 14.89 |
October | 0.551173E+09 | 1415.91 | 12-OCT-21:11 | 13.67 | 8.65 | 0.107694E+09 | 90.37 | 04-OCT-21:00 | 13.67 | 8.65 |
November | 0.361578E+09 | 1392.07 | 28-NOV-19:01 | 12.33 | 7.07 | 96798947.98 | 76.79 | 10-NOV-22:10 | 12.33 | 7.07 |
December | 0.311239E+09 | 1428.43 | 06-DEC-22:01 | 14.50 | 9.28 | 99647379.06 | 78.99 | 05-DEC-22:00 | 14.50 | 9.28 |
Annual Sum or Average | 0.574136E+10 | 0.122897E+10 | ||||||||
Minimum of Months | 0.311239E+09 | 1195.96 | 12.33 | 7.07 | 89242257.21 | 56.96 | 12.33 | 7.07 | ||
Maximum of Months | 0.692585E+09 | 1450.16 | 25.38 | 15.83 | 0.112734E+09 | 90.37 | 25.38 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125053E+10 | 4282.13 | 08-JAN-09:02 | 10.50 | 4.86 | 98990789.14 | 56.69 | 09-JAN-02:49 | 4.33 | 2.89 |
February | 0.917711E+09 | 4215.91 | 08-FEB-09:02 | 13.33 | 8.24 | 88975039.80 | 56.91 | 25-FEB-00:20 | 13.00 | 10.79 |
March | 0.105361E+10 | 4286.90 | 11-MAR-09:02 | 20.50 | 12.52 | 98735787.23 | 56.70 | 29-MAR-04:19 | 7.67 | 5.89 |
April | 0.156614E+10 | 4196.54 | 02-APR-08:62 | 17.33 | 8.66 | 96106238.12 | 56.69 | 01-APR-00:20 | 17.33 | 8.66 |
May | 0.139693E+10 | 4180.90 | 24-MAY-08:62 | 18.00 | 8.80 | 99359198.27 | 56.79 | 02-MAY-02:39 | 18.00 | 8.80 |
June | 0.171041E+10 | 3964.24 | 23-JUN-08:62 | 18.50 | 14.15 | 96290454.04 | 56.69 | 13-JUN-03:00 | 18.50 | 14.15 |
July | 0.232422E+10 | 3952.22 | 04-JUL-08:62 | 19.50 | 14.97 | 99558745.74 | 56.69 | 22-JUL-04:10 | 16.00 | 16.00 |
August | 0.246617E+10 | 3866.77 | 23-AUG-08:62 | 19.33 | 15.40 | 99660107.04 | 56.69 | 31-AUG-04:10 | 14.17 | 14.07 |
September | 0.193703E+10 | 4223.20 | 30-SEP-08:61 | 25.38 | 14.89 | 96136554.81 | 56.69 | 20-SEP-03:00 | 25.38 | 14.89 |
October | 0.205511E+10 | 4271.08 | 30-OCT-08:62 | 17.67 | 10.17 | 99379941.50 | 56.90 | 25-OCT-00:30 | 17.67 | 10.17 |
November | 0.128415E+10 | 4283.26 | 08-NOV-09:02 | 18.67 | 10.91 | 95875112.44 | 56.69 | 05-NOV-04:00 | 18.67 | 10.91 |
December | 0.129784E+10 | 4277.89 | 23-DEC-09:02 | 11.33 | 4.68 | 98937468.43 | 56.70 | 13-DEC-04:40 | 11.33 | 4.68 |
Annual Sum or Average | 0.192599E+11 | 0.116801E+10 | ||||||||
Minimum of Months | 0.917711E+09 | 3866.77 | 10.50 | 4.68 | 88975039.80 | 56.69 | 4.33 | 2.89 | ||
Maximum of Months | 0.246617E+10 | 4286.90 | 25.38 | 15.40 | 99660107.04 | 56.91 | 25.38 | 16.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472538E+09 | 4223.32 | 24-JAN-09:51 | 23.00 | 13.97 | 0.100377E+09 | 75.63 | 17-JAN-22:30 | 23.00 | 13.97 |
February | 0.423256E+09 | 4201.93 | 01-FEB-09:51 | 24.00 | 12.54 | 89412767.44 | 59.83 | 13-FEB-21:19 | 14.67 | 14.08 |
March | 0.616821E+09 | 4316.25 | 10-MAR-09:51 | 21.00 | 12.00 | 99693234.04 | 56.76 | 23-MAR-18:49 | 14.50 | 13.63 |
April | 0.105833E+10 | 4365.47 | 03-APR-08:51 | 20.00 | 11.88 | 0.100242E+09 | 78.13 | 26-APR-21:00 | 16.00 | 15.39 |
May | 0.105388E+10 | 4391.67 | 27-MAY-08:51 | 18.00 | 11.97 | 0.105097E+09 | 80.86 | 04-MAY-21:49 | 18.00 | 11.97 |
June | 0.121435E+10 | 4238.18 | 13-JUN-08:32 | 20.33 | 14.77 | 0.108346E+09 | 81.77 | 27-JUN-21:00 | 17.00 | 16.37 |
July | 0.161758E+10 | 4140.99 | 04-JUL-08:22 | 20.50 | 15.34 | 0.117121E+09 | 88.22 | 19-JUL-21:10 | 18.00 | 17.89 |
August | 0.158375E+10 | 4070.04 | 22-AUG-08:32 | 18.43 | 14.55 | 0.116462E+09 | 88.81 | 18-AUG-21:10 | 18.43 | 14.55 |
September | 0.114051E+10 | 4325.60 | 30-SEP-07:42 | 24.78 | 14.58 | 0.105334E+09 | 83.67 | 21-SEP-21:49 | 24.78 | 14.58 |
October | 0.109367E+10 | 4320.61 | 12-OCT-08:51 | 19.00 | 10.08 | 0.108424E+09 | 85.06 | 04-OCT-21:00 | 19.00 | 10.08 |
November | 0.526376E+09 | 4264.70 | 08-NOV-09:51 | 22.00 | 12.06 | 97416359.71 | 70.74 | 10-NOV-22:10 | 15.00 | 13.80 |
December | 0.438665E+09 | 4300.62 | 16-DEC-09:51 | 20.00 | 12.77 | 0.100375E+09 | 74.68 | 05-DEC-22:00 | 20.00 | 12.77 |
Annual Sum or Average | 0.112397E+11 | 0.124830E+10 | ||||||||
Minimum of Months | 0.423256E+09 | 4070.04 | 18.00 | 10.08 | 89412767.44 | 56.76 | 14.50 | 10.08 | ||
Maximum of Months | 0.161758E+10 | 4391.67 | 24.78 | 15.34 | 0.117121E+09 | 88.81 | 24.78 | 17.89 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257705E+10 | 3313.34 | 14-JAN-13:20 | 24.67 | 12.16 | 0.161593E+10 | 951.85 | 11-JAN-01:49 | 24.67 | 12.16 |
February | 0.193917E+10 | 2863.02 | 01-FEB-12:10 | 25.67 | 14.54 | 0.146171E+10 | 951.86 | 21-FEB-04:00 | 8.00 | 6.97 |
March | 0.193059E+10 | 2919.26 | 11-MAR-13:20 | 24.00 | 13.46 | 0.162019E+10 | 951.85 | 10-MAR-03:20 | 24.00 | 13.46 |
April | 0.280611E+10 | 2472.64 | 26-APR-18:03 | 18.67 | 15.37 | 0.156975E+10 | 951.84 | 25-APR-21:30 | 18.67 | 15.37 |
May | 0.277137E+10 | 2376.07 | 04-MAY-18:03 | 18.83 | 14.89 | 0.162333E+10 | 951.85 | 13-MAY-04:30 | 10.00 | 9.41 |
June | 0.348671E+10 | 2757.74 | 29-JUN-18:03 | 21.50 | 18.39 | 0.157388E+10 | 951.84 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.429436E+10 | 2752.20 | 19-JUL-18:20 | 22.33 | 18.80 | 0.161995E+10 | 951.84 | 05-JUL-22:10 | 22.33 | 18.80 |
August | 0.447940E+10 | 2697.62 | 18-AUG-15:10 | 26.50 | 20.71 | 0.162680E+10 | 951.84 | 01-AUG-22:10 | 26.50 | 20.71 |
September | 0.398960E+10 | 4035.29 | 29-SEP-13:00 | 36.00 | 18.20 | 0.156970E+10 | 951.84 | 21-SEP-22:10 | 36.00 | 18.20 |
October | 0.426347E+10 | 4340.91 | 16-OCT-12:30 | 35.05 | 17.21 | 0.162071E+10 | 951.84 | 13-OCT-22:10 | 35.05 | 17.21 |
November | 0.284794E+10 | 3736.54 | 19-NOV-13:00 | 27.00 | 14.96 | 0.156658E+10 | 951.85 | 08-NOV-05:49 | 27.00 | 14.96 |
December | 0.278052E+10 | 3471.58 | 19-DEC-13:00 | 26.00 | 11.60 | 0.161767E+10 | 951.85 | 20-DEC-04:49 | 7.17 | 0.46 |
Annual Sum or Average | 0.381663E+11 | 0.190862E+11 | ||||||||
Minimum of Months | 0.193059E+10 | 2376.07 | 18.67 | 11.60 | 0.146171E+10 | 951.84 | 7.17 | 0.46 | ||
Maximum of Months | 0.447940E+10 | 4340.91 | 36.00 | 20.71 | 0.162680E+10 | 951.86 | 36.00 | 20.71 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.977886E+09 | 5077.83 | 05-JAN-16:12 | 14.27 | 11.45 | 98189019.77 | 57.22 | 21-JAN-01:39 | 14.00 | 13.42 |
February | 0.778363E+09 | 5118.06 | 20-FEB-16:12 | 17.00 | 10.93 | 88385754.38 | 57.14 | 02-FEB-00:20 | 17.00 | 10.93 |
March | 0.911110E+09 | 5176.01 | 11-MAR-16:12 | 20.67 | 12.56 | 98089021.27 | 57.12 | 15-MAR-23:10 | 13.00 | 11.87 |
April | 0.155892E+10 | 5057.34 | 16-APR-15:12 | 18.00 | 11.97 | 95705111.39 | 57.12 | 21-APR-01:10 | 13.00 | 12.44 |
May | 0.141905E+10 | 5216.07 | 26-MAY-18:01 | 13.83 | 9.72 | 98996046.59 | 57.33 | 24-MAY-03:20 | 13.83 | 9.72 |
June | 0.186281E+10 | 4907.53 | 03-JUN-15:12 | 19.00 | 14.25 | 96090026.63 | 57.36 | 17-JUN-02:00 | 15.20 | 14.20 |
July | 0.251643E+10 | 5013.45 | 09-JUL-15:11 | 21.67 | 16.27 | 99376886.90 | 56.69 | 06-JUL-03:09 | 21.67 | 16.27 |
August | 0.255285E+10 | 4949.19 | 29-AUG-15:11 | 22.67 | 17.12 | 99454502.40 | 57.45 | 06-AUG-04:19 | 22.67 | 17.12 |
September | 0.203354E+10 | 4982.34 | 19-SEP-15:12 | 18.67 | 14.12 | 95983927.22 | 57.54 | 23-SEP-04:19 | 17.00 | 16.37 |
October | 0.195528E+10 | 5147.91 | 12-OCT-15:12 | 22.00 | 13.53 | 99065957.83 | 57.45 | 24-OCT-03:39 | 16.00 | 14.12 |
November | 0.110760E+10 | 5153.02 | 04-NOV-15:12 | 16.47 | 10.72 | 95398176.89 | 57.19 | 01-NOV-01:39 | 16.47 | 10.72 |
December | 0.105969E+10 | 5068.84 | 31-DEC-16:12 | 15.33 | 10.50 | 98207957.30 | 56.70 | 13-DEC-04:40 | 15.33 | 10.50 |
Annual Sum or Average | 0.187335E+11 | 0.116294E+10 | ||||||||
Minimum of Months | 0.778363E+09 | 4907.53 | 13.83 | 9.72 | 88385754.38 | 56.69 | 13.00 | 9.72 | ||
Maximum of Months | 0.255285E+10 | 5216.07 | 22.67 | 17.12 | 99454502.40 | 57.54 | 22.67 | 17.12 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304177E+09 | 4833.95 | 07-JAN-16:12 | 13.67 | 10.74 | 98983965.47 | 72.61 | 18-JAN-22:30 | 16.50 | 13.26 |
February | 0.310166E+09 | 5305.56 | 22-FEB-17:01 | 13.83 | 12.08 | 88977960.77 | 58.30 | 13-FEB-21:19 | 13.83 | 12.08 |
March | 0.456373E+09 | 5056.90 | 11-MAR-18:21 | 13.00 | 8.95 | 0.100123E+09 | 79.51 | 22-MAR-18:10 | 15.50 | 14.39 |
April | 0.899555E+09 | 5270.19 | 18-APR-16:51 | 15.00 | 11.13 | 0.105243E+09 | 98.56 | 26-APR-18:10 | 18.67 | 15.37 |
May | 0.967129E+09 | 5293.09 | 26-MAY-18:01 | 13.83 | 9.72 | 0.110391E+09 | 94.52 | 03-MAY-21:10 | 13.83 | 9.72 |
June | 0.124776E+10 | 5293.89 | 30-JUN-17:32 | 20.00 | 17.05 | 0.117376E+09 | 100.58 | 19-JUN-18:10 | 20.00 | 17.05 |
July | 0.175278E+10 | 5142.72 | 15-JUL-17:52 | 19.00 | 17.08 | 0.126061E+09 | 107.70 | 10-JUL-18:10 | 19.00 | 17.08 |
August | 0.163549E+10 | 4632.09 | 19-AUG-15:12 | 25.67 | 18.89 | 0.124877E+09 | 101.62 | 02-AUG-21:10 | 25.67 | 18.89 |
September | 0.119355E+10 | 4911.05 | 30-SEP-08:61 | 25.38 | 14.89 | 0.111469E+09 | 90.62 | 13-SEP-21:10 | 25.38 | 14.89 |
October | 0.101232E+10 | 5146.66 | 15-OCT-21:51 | 19.00 | 10.37 | 0.110390E+09 | 87.59 | 16-OCT-21:10 | 18.33 | 11.06 |
November | 0.403667E+09 | 5033.39 | 04-NOV-17:01 | 13.67 | 10.10 | 96789849.46 | 70.28 | 10-NOV-22:10 | 15.00 | 13.80 |
December | 0.312226E+09 | 4892.95 | 31-DEC-17:01 | 13.83 | 10.08 | 98938867.30 | 72.46 | 05-DEC-22:00 | 13.83 | 10.08 |
Annual Sum or Average | 0.104952E+11 | 0.128962E+10 | ||||||||
Minimum of Months | 0.304177E+09 | 4632.09 | 13.00 | 8.95 | 88977960.77 | 58.30 | 13.83 | 9.72 | ||
Maximum of Months | 0.175278E+10 | 5305.56 | 25.67 | 18.89 | 0.126061E+09 | 107.70 | 25.67 | 18.89 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127352E+10 | 2657.14 | 02-JAN-16:12 | 12.33 | 8.28 | 99155240.38 | 56.69 | 10-JAN-03:20 | 5.67 | 2.07 |
February | 0.829080E+09 | 2624.23 | 06-FEB-16:12 | 14.67 | 10.54 | 89089941.50 | 56.84 | 13-FEB-00:10 | 15.83 | 13.51 |
March | 0.766530E+09 | 2638.08 | 07-MAR-16:12 | 13.67 | 8.91 | 98604368.23 | 56.79 | 18-MAR-01:00 | 13.00 | 12.44 |
April | 0.882713E+09 | 2568.97 | 01-APR-15:12 | 22.67 | 11.21 | 95795550.38 | 56.76 | 25-APR-01:30 | 13.00 | 12.72 |
May | 0.626492E+09 | 2601.18 | 26-MAY-18:01 | 13.83 | 9.72 | 98866655.92 | 56.90 | 06-MAY-04:49 | 13.83 | 9.72 |
June | 0.754447E+09 | 2406.95 | 12-JUN-15:12 | 18.67 | 12.83 | 95964663.34 | 56.81 | 02-JUN-04:49 | 18.67 | 12.83 |
July | 0.107116E+10 | 2393.75 | 09-JUL-15:11 | 21.67 | 16.27 | 99337384.63 | 56.69 | 06-JUL-03:49 | 21.67 | 16.27 |
August | 0.129630E+10 | 2418.83 | 29-AUG-15:11 | 22.67 | 17.12 | 99447891.80 | 56.69 | 31-AUG-04:10 | 14.17 | 14.07 |
September | 0.130314E+10 | 2482.97 | 19-SEP-15:12 | 18.67 | 14.12 | 96002931.47 | 56.69 | 20-SEP-02:39 | 11.33 | 10.20 |
October | 0.157356E+10 | 2617.78 | 12-OCT-15:12 | 22.00 | 13.53 | 99264327.48 | 56.69 | 12-OCT-04:00 | 22.00 | 13.53 |
November | 0.124448E+10 | 2712.65 | 19-NOV-10:54 | 26.00 | 15.07 | 96028183.17 | 56.69 | 05-NOV-04:00 | 26.00 | 15.07 |
December | 0.136451E+10 | 2657.00 | 23-DEC-09:02 | 11.33 | 4.68 | 99155355.61 | 56.70 | 13-DEC-04:40 | 11.33 | 4.68 |
Annual Sum or Average | 0.129859E+11 | 0.116671E+10 | ||||||||
Minimum of Months | 0.626492E+09 | 2393.75 | 11.33 | 4.68 | 89089941.50 | 56.69 | 5.67 | 2.07 | ||
Maximum of Months | 0.157356E+10 | 2712.65 | 26.00 | 17.12 | 99447891.80 | 56.90 | 26.00 | 16.27 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370105E+11 | 19727.19 | 18-JAN-22:10 | 16.83 | 13.41 | 0.182428E+11 | 11349.10 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.336321E+11 | 18837.67 | 17-FEB-22:10 | 13.67 | 12.71 | 0.166830E+11 | 11345.22 | 24-FEB-22:10 | 13.00 | 11.29 |
March | 0.377512E+11 | 19427.89 | 24-MAR-21:10 | 13.00 | 11.77 | 0.185665E+11 | 11346.76 | 31-MAR-21:40 | 10.73 | 9.95 |
April | 0.389504E+11 | 20785.69 | 26-APR-21:52 | 16.00 | 15.39 | 0.183690E+11 | 11349.19 | 25-APR-21:30 | 16.00 | 15.39 |
May | 0.409948E+11 | 21259.71 | 04-MAY-21:10 | 17.00 | 15.07 | 0.190609E+11 | 11349.19 | 02-MAY-22:10 | 17.00 | 15.07 |
June | 0.417787E+11 | 21549.82 | 27-JUN-21:52 | 17.00 | 16.37 | 0.186396E+11 | 11349.21 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.444642E+11 | 21685.99 | 19-JUL-21:52 | 18.00 | 17.35 | 0.192420E+11 | 11349.21 | 17-JUL-22:10 | 18.00 | 17.35 |
August | 0.439520E+11 | 21578.25 | 02-AUG-21:10 | 17.88 | 16.64 | 0.193133E+11 | 11349.19 | 01-AUG-22:10 | 17.88 | 16.64 |
September | 0.405559E+11 | 22275.80 | 29-SEP-21:10 | 24.58 | 13.52 | 0.185336E+11 | 11349.18 | 06-SEP-22:10 | 24.58 | 13.52 |
October | 0.410336E+11 | 21807.11 | 04-OCT-21:52 | 21.00 | 18.98 | 0.190066E+11 | 11349.22 | 13-OCT-22:10 | 18.17 | 10.35 |
November | 0.365669E+11 | 19247.90 | 10-NOV-22:12 | 15.00 | 13.80 | 0.179455E+11 | 11348.99 | 10-NOV-22:30 | 15.00 | 13.80 |
December | 0.368981E+11 | 19753.70 | 05-DEC-22:52 | 18.00 | 9.37 | 0.183434E+11 | 11349.10 | 06-DEC-22:19 | 15.00 | 9.64 |
Annual Sum or Average | 0.473589E+12 | 0.221946E+12 | ||||||||
Minimum of Months | 0.336321E+11 | 18837.67 | 13.00 | 9.37 | 0.166830E+11 | 11345.22 | 10.73 | 9.64 | ||
Maximum of Months | 0.444642E+11 | 22275.80 | 24.58 | 18.98 | 0.193133E+11 | 11349.22 | 24.58 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387890E+11 | 21067.80 | 18-JAN-22:10 | 16.83 | 13.41 | 0.185825E+11 | 11349.10 | 18-JAN-23:10 | 15.67 | 12.73 |
February | 0.352536E+11 | 20197.90 | 17-FEB-22:10 | 13.67 | 12.71 | 0.169852E+11 | 11345.66 | 08-FEB-00:30 | 13.67 | 12.71 |
March | 0.396841E+11 | 20702.63 | 24-MAR-21:10 | 13.00 | 11.77 | 0.188868E+11 | 11346.82 | 31-MAR-21:40 | 10.73 | 9.95 |
April | 0.410777E+11 | 21954.91 | 26-APR-21:52 | 16.00 | 15.39 | 0.185479E+11 | 11349.20 | 25-APR-21:30 | 16.00 | 15.39 |
May | 0.432784E+11 | 22444.21 | 04-MAY-21:10 | 17.00 | 15.07 | 0.192134E+11 | 11349.19 | 02-MAY-22:10 | 17.00 | 15.07 |
June | 0.441860E+11 | 22753.87 | 29-JUN-18:02 | 21.50 | 18.39 | 0.187068E+11 | 11349.22 | 30-JUN-22:10 | 16.13 | 16.03 |
July | 0.470203E+11 | 22852.65 | 18-JUL-18:03 | 23.33 | 19.62 | 0.192889E+11 | 11349.21 | 17-JUL-22:10 | 23.33 | 19.62 |
August | 0.464458E+11 | 22795.18 | 02-AUG-21:10 | 17.88 | 16.64 | 0.193639E+11 | 11349.19 | 01-AUG-22:10 | 17.88 | 16.64 |
September | 0.427809E+11 | 23459.44 | 29-SEP-21:10 | 24.58 | 13.52 | 0.186294E+11 | 11349.19 | 06-SEP-22:10 | 24.58 | 13.52 |
October | 0.431790E+11 | 23028.77 | 04-OCT-21:52 | 21.00 | 18.98 | 0.191565E+11 | 11349.22 | 13-OCT-22:10 | 18.17 | 10.35 |
November | 0.382907E+11 | 20579.86 | 10-NOV-22:10 | 15.00 | 13.80 | 0.182377E+11 | 11348.99 | 10-NOV-22:30 | 15.00 | 13.80 |
December | 0.386308E+11 | 21025.98 | 05-DEC-22:52 | 18.00 | 9.37 | 0.186779E+11 | 11349.11 | 06-DEC-22:19 | 15.00 | 9.64 |
Annual Sum or Average | 0.498616E+12 | 0.224277E+12 | ||||||||
Minimum of Months | 0.352536E+11 | 20197.90 | 13.00 | 9.37 | 0.169852E+11 | 11345.66 | 10.73 | 9.64 | ||
Maximum of Months | 0.470203E+11 | 23459.44 | 24.58 | 19.62 | 0.193639E+11 | 11349.22 | 24.58 | 19.62 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495445E+11 | 29437.74 | 14-JAN-11:50 | 26.00 | 11.78 | 0.188681E+11 | 11319.97 | 14-JAN-18:40 | 19.67 | 10.96 |
February | 0.444277E+11 | 29197.78 | 01-FEB-11:35 | 25.00 | 14.29 | 0.170435E+11 | 11319.93 | 11-FEB-18:40 | 15.20 | 11.67 |
March | 0.496620E+11 | 30495.76 | 23-MAR-10:40 | 22.00 | 16.70 | 0.188760E+11 | 11319.95 | 18-MAR-17:00 | 22.00 | 16.70 |
April | 0.505750E+11 | 30992.42 | 30-APR-10:40 | 25.67 | 16.97 | 0.182626E+11 | 11320.15 | 29-APR-17:00 | 25.67 | 16.97 |
May | 0.520677E+11 | 30563.48 | 02-MAY-10:40 | 21.67 | 15.55 | 0.188721E+11 | 11320.14 | 06-MAY-17:00 | 16.00 | 13.58 |
June | 0.518845E+11 | 30396.82 | 25-JUN-10:40 | 23.00 | 17.26 | 0.182667E+11 | 11320.17 | 10-JUN-17:00 | 23.00 | 17.26 |
July | 0.550920E+11 | 31086.85 | 30-JUL-10:40 | 24.67 | 20.10 | 0.188691E+11 | 11320.12 | 22-JUL-17:00 | 24.67 | 20.10 |
August | 0.551854E+11 | 31285.82 | 15-AUG-10:40 | 27.00 | 20.85 | 0.188764E+11 | 11320.08 | 05-AUG-17:49 | 27.00 | 20.85 |
September | 0.517382E+11 | 32626.15 | 29-SEP-10:40 | 35.67 | 17.51 | 0.182624E+11 | 11320.16 | 23-SEP-17:49 | 35.67 | 17.51 |
October | 0.528281E+11 | 32278.12 | 15-OCT-10:40 | 31.67 | 16.43 | 0.188698E+11 | 11320.10 | 28-OCT-17:40 | 16.33 | 14.26 |
November | 0.484677E+11 | 29878.10 | 19-NOV-11:50 | 26.00 | 15.39 | 0.182588E+11 | 11320.08 | 18-NOV-18:00 | 26.00 | 15.39 |
December | 0.494676E+11 | 29337.93 | 19-DEC-11:50 | 25.00 | 11.20 | 0.188680E+11 | 11319.96 | 16-DEC-18:30 | 25.00 | 11.20 |
Annual Sum or Average | 0.610940E+12 | 0.222193E+12 | ||||||||
Minimum of Months | 0.444277E+11 | 29197.78 | 21.67 | 11.20 | 0.170435E+11 | 11319.93 | 15.20 | 10.96 | ||
Maximum of Months | 0.551854E+11 | 32626.15 | 35.67 | 20.85 | 0.188764E+11 | 11320.17 | 35.67 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359674E+10 | 8654.33 | 18-JAN-13:30 | 25.30 | 14.77 | 0.163540E+10 | 1007.40 | 26-JAN-02:49 | 14.00 | 14.00 |
February | 0.281277E+10 | 7328.16 | 01-FEB-12:20 | 25.33 | 14.40 | 0.149745E+10 | 1007.40 | 16-FEB-02:39 | 13.00 | 12.44 |
March | 0.321152E+10 | 8237.99 | 11-MAR-12:50 | 24.00 | 13.82 | 0.165090E+10 | 1007.40 | 21-MAR-23:10 | 10.00 | 9.41 |
April | 0.572174E+10 | 8439.91 | 26-APR-13:00 | 27.00 | 17.13 | 0.164418E+10 | 1007.40 | 22-APR-00:40 | 27.00 | 17.13 |
May | 0.561451E+10 | 8047.84 | 04-MAY-12:00 | 24.00 | 16.55 | 0.170425E+10 | 1007.41 | 11-MAY-01:10 | 12.00 | 10.35 |
June | 0.745584E+10 | 7207.79 | 27-JUN-12:50 | 24.00 | 18.72 | 0.166421E+10 | 1007.41 | 13-JUN-02:30 | 24.00 | 18.72 |
July | 0.958009E+10 | 8288.94 | 31-JUL-12:30 | 28.00 | 21.19 | 0.171446E+10 | 1007.40 | 06-JUL-01:00 | 28.00 | 21.19 |
August | 0.983358E+10 | 8449.39 | 18-AUG-12:20 | 27.00 | 20.90 | 0.172176E+10 | 1007.40 | 24-AUG-03:20 | 15.33 | 14.73 |
September | 0.795049E+10 | 11614.73 | 29-SEP-12:50 | 36.00 | 18.21 | 0.166002E+10 | 1007.40 | 12-SEP-04:49 | 36.00 | 18.21 |
October | 0.784484E+10 | 11613.88 | 15-OCT-11:50 | 32.00 | 16.80 | 0.170618E+10 | 1007.40 | 12-OCT-23:00 | 32.00 | 16.80 |
November | 0.421598E+10 | 9290.38 | 19-NOV-13:00 | 27.00 | 14.96 | 0.162181E+10 | 1007.40 | 21-NOV-04:19 | 13.00 | 11.87 |
December | 0.381681E+10 | 9173.69 | 19-DEC-12:30 | 25.50 | 11.42 | 0.164833E+10 | 1007.40 | 11-DEC-23:10 | 25.50 | 11.42 |
Annual Sum or Average | 0.716549E+11 | 0.198690E+11 | ||||||||
Minimum of Months | 0.281277E+10 | 7207.79 | 24.00 | 11.42 | 0.149745E+10 | 1007.40 | 10.00 | 9.41 | ||
Maximum of Months | 0.983358E+10 | 11614.73 | 36.00 | 21.19 | 0.172176E+10 | 1007.41 | 36.00 | 21.19 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20787173.63 | 590.22 | 08-JAN-06:50 | 1.33 |
February | 4896449.33 | 492.91 | 26-FEB-04:20 | 10.33 |
March | 44155408.38 | 949.10 | 29-MAR-04:00 | 8.00 |
April | 2647066.89 | 267.15 | 01-APR-06:10 | 7.67 |
May | 373305.04 | 111.48 | 14-MAY-04:50 | 8.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 50032.30 | 41.58 | 13-NOV-04:50 | 11.17 |
December | 8724085.48 | 892.95 | 13-DEC-04:30 | 7.00 |
Annual Sum or Average | 81633521.06 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 44155408.38 | 949.10 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176059E+09 | 1376.18 | 08-JAN-09:03 | 10.50 |
February | 0.115115E+09 | 1566.71 | 07-FEB-19:03 | 13.00 |
March | 0.187131E+09 | 3150.53 | 28-MAR-08:62 | 9.33 |
April | 30755189.79 | 1293.43 | 14-APR-18:03 | 12.83 |
May | 26660872.76 | 1469.09 | 27-MAY-08:03 | 16.33 |
June | 2018261.58 | 990.86 | 06-JUN-08:04 | 17.00 |
July | 190341.80 | 717.36 | 12-JUL-08:04 | 17.17 |
August | 262306.59 | 640.77 | 22-AUG-08:03 | 17.58 |
September | 1326241.27 | 921.17 | 19-SEP-08:03 | 16.17 |
October | 15542702.32 | 1305.69 | 12-OCT-08:03 | 16.50 |
November | 84852670.26 | 1437.72 | 23-NOV-19:03 | 12.67 |
December | 0.156463E+09 | 1477.02 | 28-DEC-19:03 | 12.83 |
Annual Sum or Average | 0.796377E+09 | |||
Minimum of Months | 190341.80 | 640.77 | 9.33 | |
Maximum of Months | 0.187131E+09 | 3150.53 | 17.58 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249457E+09 | 2185.08 | 03-JAN-09:02 | 11.33 |
February | 0.146583E+09 | 1658.76 | 25-FEB-16:12 | 11.00 |
March | 0.206575E+09 | 3084.82 | 30-MAR-08:62 | 9.50 |
April | 35679289.07 | 1876.80 | 02-APR-08:53 | 19.00 |
May | 30525261.60 | 1780.15 | 15-MAY-08:53 | 17.00 |
June | 31585656.16 | 1346.31 | 11-JUN-21:13 | 15.33 |
July | 45007709.90 | 977.48 | 06-JUL-08:54 | 20.00 |
August | 52553276.15 | 1004.25 | 19-AUG-21:55 | 18.00 |
September | 37799013.65 | 1639.20 | 20-SEP-08:53 | 18.00 |
October | 62096685.95 | 2047.44 | 26-OCT-08:53 | 23.00 |
November | 0.127179E+09 | 2153.14 | 29-NOV-09:53 | 20.00 |
December | 0.228291E+09 | 2257.12 | 13-DEC-09:02 | 11.33 |
Annual Sum or Average | 0.125333E+10 | |||
Minimum of Months | 30525261.60 | 977.48 | 9.50 | |
Maximum of Months | 0.249457E+09 | 3084.82 | 23.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8639952.15 | 588.01 | 02-JAN-16:13 | 12.33 |
February | 2026006.99 | 611.87 | 05-FEB-17:13 | 14.33 |
March | 5992632.37 | 522.60 | 10-MAR-19:15 | 13.00 |
April | 1345759.64 | 430.42 | 16-APR-18:15 | 13.67 |
May | 456657.06 | 272.84 | 09-MAY-08:06 | 13.83 |
June | 1029359.31 | 229.68 | 12-JUN-08:56 | 17.00 |
July | 2039754.29 | 80.36 | 18-JUL-18:12 | 22.67 |
August | 2974448.72 | 61.59 | 13-AUG-16:21 | 23.50 |
September | 1252747.02 | 106.75 | 18-SEP-19:06 | 14.00 |
October | 2516124.59 | 426.64 | 27-OCT-08:54 | 19.00 |
November | 1727862.66 | 536.52 | 23-NOV-19:05 | 12.67 |
December | 4908316.63 | 577.54 | 10-DEC-16:15 | 14.00 |
Annual Sum or Average | 34909621.42 | |||
Minimum of Months | 456657.06 | 61.59 | 12.33 | |
Maximum of Months | 8639952.15 | 611.87 | 23.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171516E+09 | 1143.19 | 15-JAN-19:04 | 14.50 |
February | 0.121234E+09 | 1371.30 | 25-FEB-16:12 | 11.00 |
March | 0.191501E+09 | 2783.47 | 28-MAR-08:62 | 9.33 |
April | 34153801.50 | 1613.44 | 19-APR-18:03 | 14.00 |
May | 31010241.67 | 1521.80 | 10-MAY-18:03 | 13.67 |
June | 2125118.08 | 829.99 | 11-JUN-08:05 | 17.00 |
July | 17727.91 | 140.91 | 20-JUL-18:05 | 17.83 |
August | 37042.63 | 218.69 | 21-AUG-08:05 | 17.33 |
September | 2277902.23 | 916.51 | 18-SEP-18:04 | 15.67 |
October | 17166823.96 | 892.78 | 07-OCT-18:04 | 15.67 |
November | 90961945.09 | 1363.76 | 24-NOV-16:14 | 15.67 |
December | 0.159253E+09 | 1417.80 | 29-DEC-19:03 | 12.17 |
Annual Sum or Average | 0.821255E+09 | |||
Minimum of Months | 17727.91 | 140.91 | 9.33 | |
Maximum of Months | 0.191501E+09 | 2783.47 | 17.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232914E+09 | 1570.90 | 09-JAN-16:13 | 15.00 |
February | 0.154311E+09 | 1604.68 | 25-FEB-16:12 | 11.00 |
March | 0.215939E+09 | 2671.77 | 28-MAR-08:62 | 9.33 |
April | 47189237.91 | 1583.42 | 10-APR-18:53 | 13.00 |
May | 39283055.96 | 1500.21 | 25-MAY-21:14 | 15.00 |
June | 27625709.09 | 1174.60 | 03-JUN-21:54 | 16.00 |
July | 34132691.51 | 888.58 | 17-JUL-21:55 | 18.00 |
August | 38197944.29 | 978.68 | 29-AUG-21:54 | 17.30 |
September | 33849298.21 | 1629.65 | 18-SEP-19:03 | 14.00 |
October | 56197774.15 | 1707.60 | 20-OCT-21:54 | 16.00 |
November | 0.128243E+09 | 1450.29 | 10-NOV-22:14 | 15.00 |
December | 0.217712E+09 | 2052.84 | 05-DEC-22:53 | 18.00 |
Annual Sum or Average | 0.122559E+10 | |||
Minimum of Months | 27625709.09 | 888.58 | 9.33 | |
Maximum of Months | 0.232914E+09 | 2671.77 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457316E+09 | 1626.14 | 25-JAN-16:13 | 15.00 |
February | 0.355155E+09 | 3288.25 | 25-FEB-16:12 | 11.00 |
March | 0.465152E+09 | 3483.59 | 30-MAR-08:62 | 9.50 |
April | 0.147739E+09 | 1586.58 | 21-APR-15:13 | 14.67 |
May | 0.130934E+09 | 1571.88 | 24-MAY-08:03 | 18.00 |
June | 25204855.36 | 1249.00 | 07-JUN-08:03 | 15.33 |
July | 1412269.27 | 1029.19 | 11-JUL-08:04 | 18.17 |
August | 1055063.94 | 1054.91 | 22-AUG-08:03 | 17.58 |
September | 13833696.11 | 1013.87 | 15-SEP-08:03 | 16.33 |
October | 83836088.73 | 1255.48 | 23-OCT-15:14 | 17.00 |
November | 0.283109E+09 | 1834.37 | 30-NOV-19:03 | 13.67 |
December | 0.430446E+09 | 2037.40 | 12-DEC-19:03 | 9.67 |
Annual Sum or Average | 0.239519E+10 | |||
Minimum of Months | 1055063.94 | 1013.87 | 9.50 | |
Maximum of Months | 0.465152E+09 | 3483.59 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594405E+09 | 3420.83 | 03-JAN-09:02 | 11.33 |
February | 0.412331E+09 | 3191.61 | 25-FEB-16:12 | 11.00 |
March | 0.493866E+09 | 3401.11 | 30-MAR-08:62 | 9.50 |
April | 0.126567E+09 | 1499.97 | 21-APR-18:03 | 13.00 |
May | 96784185.61 | 1923.63 | 15-MAY-08:53 | 17.00 |
June | 44273972.82 | 1570.67 | 16-JUN-21:54 | 16.00 |
July | 51681140.00 | 1125.78 | 17-JUL-08:54 | 21.00 |
August | 61659096.92 | 1173.77 | 29-AUG-08:54 | 19.00 |
September | 53704691.25 | 1959.69 | 19-SEP-08:53 | 17.00 |
October | 0.130592E+09 | 2219.70 | 25-OCT-21:53 | 19.00 |
November | 0.355295E+09 | 2858.50 | 05-NOV-08:62 | 11.33 |
December | 0.560228E+09 | 3374.99 | 22-DEC-09:02 | 12.50 |
Annual Sum or Average | 0.298139E+10 | |||
Minimum of Months | 44273972.82 | 1125.78 | 9.50 | |
Maximum of Months | 0.594405E+09 | 3420.83 | 21.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100842E+09 | 685.53 | 31-JAN-19:04 | 11.83 |
February | 75111749.66 | 968.43 | 25-FEB-16:12 | 11.00 |
March | 0.136349E+09 | 1727.00 | 28-MAR-08:62 | 9.33 |
April | 33880967.29 | 1008.09 | 19-APR-18:03 | 14.00 |
May | 41073333.93 | 1228.03 | 10-MAY-18:03 | 13.67 |
June | 5343302.76 | 584.89 | 11-JUN-18:04 | 16.83 |
July | 790918.71 | 509.97 | 17-JUL-08:03 | 17.67 |
August | 629978.60 | 356.33 | 29-AUG-08:04 | 18.00 |
September | 2206861.15 | 616.98 | 18-SEP-18:04 | 15.67 |
October | 12752415.26 | 532.39 | 07-OCT-18:04 | 15.67 |
November | 52000203.84 | 790.60 | 02-NOV-18:03 | 13.00 |
December | 90318345.10 | 669.63 | 11-DEC-19:04 | 12.00 |
Annual Sum or Average | 0.551299E+09 | |||
Minimum of Months | 629978.60 | 356.33 | 9.33 | |
Maximum of Months | 0.136349E+09 | 1727.00 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.204643E+11 | 19711.29 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.184774E+11 | 19711.29 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.205273E+11 | 19711.29 | 01-MAR-20:10 | 0.121771E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.197704E+11 | 19711.29 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.204997E+11 | 19711.29 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.198611E+11 | 19711.29 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.204091E+11 | 19711.29 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.205352E+11 | 19711.29 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.197783E+11 | 19711.29 | 01-SEP-19:10 | 0.117482E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.204564E+11 | 19711.29 | 02-OCT-19:10 | 0.121479E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.198453E+11 | 19711.29 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.204091E+11 | 19711.29 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.241034E+12 | 0.143105E+12 | ||||
Minimum of Months | 0.184774E+11 | 19711.29 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.205352E+11 | 19711.29 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101186E+10 | 974.63 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.913620E+09 | 974.63 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.101498E+10 | 974.63 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.977556E+09 | 974.63 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.101362E+10 | 974.63 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.982039E+09 | 974.63 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.100913E+10 | 974.63 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.101537E+10 | 974.63 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.977945E+09 | 974.63 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.101147E+10 | 974.63 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.981259E+09 | 974.63 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.100913E+10 | 974.63 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.119180E+11 | 0.101856E+11 | ||||
Minimum of Months | 0.913620E+09 | 974.63 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.101537E+10 | 974.63 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117174E+10 | 1128.63 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.105798E+10 | 1128.63 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.117535E+10 | 1128.63 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.113201E+10 | 1128.63 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.117377E+10 | 1128.63 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.113720E+10 | 1128.63 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.116858E+10 | 1128.63 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.117580E+10 | 1128.63 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.113246E+10 | 1128.63 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.117129E+10 | 1128.63 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.113630E+10 | 1128.63 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.116858E+10 | 1128.63 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.138011E+11 | 0.117950E+11 | ||||
Minimum of Months | 0.105798E+10 | 1128.63 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.117580E+10 | 1128.63 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.247783E+10 | 2386.66 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.223726E+10 | 2386.66 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.248547E+10 | 2386.66 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.239382E+10 | 2386.66 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.248213E+10 | 2386.66 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.240480E+10 | 2386.66 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.247115E+10 | 2386.66 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.248642E+10 | 2386.66 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.239478E+10 | 2386.66 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.247688E+10 | 2386.66 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.240289E+10 | 2386.66 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.247115E+10 | 2386.66 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.291846E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.223726E+10 | 2386.66 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.248642E+10 | 2386.66 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.762439E+09 | 734.39 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.688413E+09 | 734.39 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.764789E+09 | 734.39 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.736588E+09 | 734.39 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.763761E+09 | 734.39 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.739966E+09 | 734.39 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.760382E+09 | 734.39 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.765082E+09 | 734.39 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.736882E+09 | 734.39 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.762145E+09 | 734.39 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.739379E+09 | 734.39 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.760382E+09 | 734.39 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.898021E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.688413E+09 | 734.39 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.765082E+09 | 734.39 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.60 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425209E+09 | 453.60 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472384E+09 | 453.60 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.60 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471749E+09 | 453.60 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457052E+09 | 453.60 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469662E+09 | 453.60 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.60 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.455147E+09 | 453.60 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470751E+09 | 453.60 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456689E+09 | 453.60 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469662E+09 | 453.60 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554677E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.425209E+09 | 453.60 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.60 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.265929E+10 | 2561.44 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.240110E+10 | 2561.44 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.266749E+10 | 2561.44 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.256913E+10 | 2561.44 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.266390E+10 | 2561.44 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.258091E+10 | 2561.44 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.265212E+10 | 2561.44 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.266851E+10 | 2561.44 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.257015E+10 | 2561.44 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.265826E+10 | 2561.44 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.257886E+10 | 2561.44 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.265212E+10 | 2561.44 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.313218E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.240110E+10 | 2561.44 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.266851E+10 | 2561.44 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.171043E+11 | 16474.99 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.154437E+11 | 16474.99 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.171571E+11 | 16474.99 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.165244E+11 | 16474.99 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.171340E+11 | 16474.99 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.166002E+11 | 16474.99 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.170582E+11 | 16474.99 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.171636E+11 | 16474.99 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.165310E+11 | 16474.99 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.170977E+11 | 16474.99 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.165870E+11 | 16474.99 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.170582E+11 | 16474.99 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.201459E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.154437E+11 | 16474.99 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.171636E+11 | 16474.99 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332597E+09 | 300.93 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.300367E+09 | 300.93 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.329954E+09 | 300.93 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.322251E+09 | 300.93 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.331275E+09 | 300.93 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.319694E+09 | 300.93 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.333875E+09 | 300.93 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.329954E+09 | 300.93 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.322338E+09 | 300.93 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.332554E+09 | 300.93 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.320973E+09 | 300.93 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.333919E+09 | 300.93 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.390975E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.300367E+09 | 300.93 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.333919E+09 | 300.93 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332688E+09 | 301.01 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.300450E+09 | 301.01 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.330044E+09 | 301.01 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.322339E+09 | 301.01 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.331366E+09 | 301.01 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.319782E+09 | 301.01 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.333967E+09 | 301.01 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.330044E+09 | 301.01 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.322426E+09 | 301.01 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.332644E+09 | 301.01 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.321060E+09 | 301.01 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.334010E+09 | 301.01 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.391082E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.300450E+09 | 301.01 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.334010E+09 | 301.01 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.195823E+10 | 1886.18 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.176811E+10 | 1886.18 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.196427E+10 | 1886.18 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.189184E+10 | 1886.18 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.196163E+10 | 1886.18 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.190052E+10 | 1886.18 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.195295E+10 | 1886.18 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.196502E+10 | 1886.18 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.189259E+10 | 1886.18 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.195748E+10 | 1886.18 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.189901E+10 | 1886.18 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.195295E+10 | 1886.18 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.230646E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.176811E+10 | 1886.18 | 0.00 | 0.00 | |
Maximum of Months | 0.196502E+10 | 1886.18 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529224E+09 | 478.83 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.477941E+09 | 478.83 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.525018E+09 | 478.83 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.512762E+09 | 478.83 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.527121E+09 | 478.83 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.508693E+09 | 478.83 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.531258E+09 | 478.83 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.525018E+09 | 478.83 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.512899E+09 | 478.83 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.529155E+09 | 478.83 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.510727E+09 | 478.83 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.531327E+09 | 478.83 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.622114E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.477941E+09 | 478.83 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.531327E+09 | 478.83 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.529162E+09 | 478.78 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.477885E+09 | 478.78 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.524956E+09 | 478.78 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.512701E+09 | 478.78 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.527059E+09 | 478.78 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.508634E+09 | 478.78 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.531196E+09 | 478.78 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.524956E+09 | 478.78 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.512839E+09 | 478.78 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.529093E+09 | 478.78 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.510668E+09 | 478.78 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.531265E+09 | 478.78 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.622041E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.477885E+09 | 478.78 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.531265E+09 | 478.78 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332688E+09 | 301.01 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.300450E+09 | 301.01 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.330044E+09 | 301.01 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.322339E+09 | 301.01 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.331366E+09 | 301.01 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.319782E+09 | 301.01 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.333967E+09 | 301.01 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.330044E+09 | 301.01 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.322426E+09 | 301.01 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.332644E+09 | 301.01 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.321060E+09 | 301.01 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.334010E+09 | 301.01 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.391082E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.300450E+09 | 301.01 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.334010E+09 | 301.01 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466994E+10 | 4498.11 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.421653E+10 | 4498.11 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.468433E+10 | 4498.11 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.451160E+10 | 4498.11 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.467803E+10 | 4498.11 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.453229E+10 | 4498.11 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.465734E+10 | 4498.11 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.468613E+10 | 4498.11 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.451340E+10 | 4498.11 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.466814E+10 | 4498.11 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.452870E+10 | 4498.11 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.465734E+10 | 4498.11 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.550038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.421653E+10 | 4498.11 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.468613E+10 | 4498.11 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.466994E+10 | 4498.11 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.421653E+10 | 4498.11 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.468433E+10 | 4498.11 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.451160E+10 | 4498.11 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.467803E+10 | 4498.11 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.453229E+10 | 4498.11 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.465734E+10 | 4498.11 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.468613E+10 | 4498.11 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.451340E+10 | 4498.11 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.466814E+10 | 4498.11 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.452870E+10 | 4498.11 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.465734E+10 | 4498.11 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.550038E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.421653E+10 | 4498.11 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.468613E+10 | 4498.11 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124679E+10 | 1200.92 | 02-JAN-20:10 | 0.371477E+11 | 16602.84 | 01-JAN-07:10 |
February | 0.112574E+10 | 1200.92 | 01-FEB-20:10 | 0.335528E+11 | 16602.84 | 01-FEB-07:10 |
March | 0.125063E+10 | 1200.92 | 01-MAR-20:10 | 0.371477E+11 | 16602.84 | 01-MAR-07:10 |
April | 0.120452E+10 | 1200.92 | 03-APR-19:10 | 0.359494E+11 | 16602.84 | 01-APR-06:10 |
May | 0.124895E+10 | 1200.92 | 01-MAY-19:10 | 0.371477E+11 | 16602.84 | 01-MAY-06:10 |
June | 0.121004E+10 | 1200.92 | 01-JUN-19:10 | 0.359494E+11 | 16602.84 | 01-JUN-06:10 |
July | 0.124343E+10 | 1200.92 | 03-JUL-19:10 | 0.371477E+11 | 16602.84 | 01-JUL-06:10 |
August | 0.125111E+10 | 1200.92 | 01-AUG-19:10 | 0.371477E+11 | 16602.84 | 01-AUG-06:10 |
September | 0.120500E+10 | 1200.92 | 01-SEP-19:10 | 0.359494E+11 | 16602.84 | 01-SEP-06:10 |
October | 0.124631E+10 | 1200.92 | 02-OCT-19:10 | 0.371477E+11 | 16602.84 | 01-OCT-06:10 |
November | 0.120908E+10 | 1200.92 | 01-NOV-19:10 | 0.359494E+11 | 16602.84 | 01-NOV-06:10 |
December | 0.124343E+10 | 1200.92 | 01-DEC-20:10 | 0.371477E+11 | 16602.84 | 01-DEC-07:10 |
Annual Sum or Average | 0.146850E+11 | 0.437384E+12 | ||||
Minimum of Months | 0.112574E+10 | 1200.92 | 0.335528E+11 | 16602.84 | ||
Maximum of Months | 0.125111E+10 | 1200.92 | 0.371477E+11 | 16602.84 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.207249E+10 | 1996.23 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.187127E+10 | 1996.23 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.207888E+10 | 1996.23 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.200222E+10 | 1996.23 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.207608E+10 | 1996.23 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.201140E+10 | 1996.23 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.206690E+10 | 1996.23 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.207967E+10 | 1996.23 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.200302E+10 | 1996.23 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.207169E+10 | 1996.23 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.200981E+10 | 1996.23 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.206690E+10 | 1996.23 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.244103E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.187127E+10 | 1996.23 | 0.00 | 0.00 | |
Maximum of Months | 0.207967E+10 | 1996.23 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.204643E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.184774E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.205273E+11 | 0.121771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.197704E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.204997E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.198611E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.204091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.205352E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.197783E+11 | 0.117482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.204564E+11 | 0.121479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.198453E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.204091E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.241034E+12 | 0.143105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.184774E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.205352E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.101186E+10 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 568349.62 | 0.296720E+09 |
February | 0.179968E+10 | 0.913620E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68584.99 | 0.257115E+09 |
March | 0.199990E+10 | 0.101498E+10 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302841E+09 |
April | 0.192973E+10 | 0.977556E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 509024.55 | 0.220911E+09 |
May | 0.199475E+10 | 0.101362E+10 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213414E+09 |
June | 0.193394E+10 | 0.982039E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75395.11 | 0.150060E+09 |
July | 0.199054E+10 | 0.100913E+10 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3248921.86 | 0.113754E+09 |
August | 0.199896E+10 | 0.101537E+10 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3647851.77 | 0.109810E+09 |
September | 0.192879E+10 | 0.977945E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7462652.56 | 0.141869E+09 |
October | 0.199148E+10 | 0.101147E+10 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13481486.87 | 0.144181E+09 |
November | 0.192552E+10 | 0.981259E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 624017.99 | 0.253918E+09 |
December | 0.199054E+10 | 0.100913E+10 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 393062.63 | 0.284917E+09 |
Annual Sum or Average | 0.234744E+11 | 0.119180E+11 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30079347.95 | 0.248951E+10 |
Minimum of Months | 0.179968E+10 | 0.913620E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109810E+09 |
Maximum of Months | 0.199990E+10 | 0.101537E+10 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13481486.87 | 0.302841E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.117174E+10 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 423711.50 | 0.124945E+09 |
February | 0.208403E+10 | 0.105798E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55860.48 | 0.109789E+09 |
March | 0.231589E+10 | 0.117535E+10 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29944.83 | 0.128595E+09 |
April | 0.223463E+10 | 0.113201E+10 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 358248.45 | 95964659.93 |
May | 0.230993E+10 | 0.117377E+10 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19300.72 | 94551479.83 |
June | 0.223950E+10 | 0.113720E+10 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 217034.60 | 68130441.81 |
July | 0.230505E+10 | 0.116858E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1859657.68 | 52444873.12 |
August | 0.231480E+10 | 0.117580E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2050117.38 | 50511987.20 |
September | 0.223354E+10 | 0.113246E+10 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882271.28 | 63132134.78 |
October | 0.230614E+10 | 0.117129E+10 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5636754.71 | 64442541.21 |
November | 0.222975E+10 | 0.113630E+10 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 342277.69 | 0.108405E+09 |
December | 0.230505E+10 | 0.116858E+10 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 325932.13 | 0.120793E+09 |
Annual Sum or Average | 0.271834E+11 | 0.138011E+11 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14201111.46 | 0.108171E+10 |
Minimum of Months | 0.208403E+10 | 0.105798E+10 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19300.72 | 50511987.20 |
Maximum of Months | 0.231589E+10 | 0.117580E+10 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5636754.71 | 0.128595E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.247783E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 831685.09 | 0.296529E+09 |
February | 0.440737E+09 | 0.223726E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 100423.89 | 0.263420E+09 |
March | 0.489771E+09 | 0.248547E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72379.95 | 0.308782E+09 |
April | 0.472586E+09 | 0.239382E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 630279.81 | 0.231863E+09 |
May | 0.488511E+09 | 0.248213E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3655.28 | 0.232694E+09 |
June | 0.473617E+09 | 0.240480E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54618.60 | 0.170731E+09 |
July | 0.487480E+09 | 0.247115E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2858062.60 | 0.131208E+09 |
August | 0.489542E+09 | 0.248642E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3256388.49 | 0.125153E+09 |
September | 0.472357E+09 | 0.239478E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6482117.26 | 0.155387E+09 |
October | 0.487709E+09 | 0.247688E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12528026.57 | 0.157918E+09 |
November | 0.471555E+09 | 0.240289E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 768249.80 | 0.259273E+09 |
December | 0.487480E+09 | 0.247115E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662947.14 | 0.287159E+09 |
Annual Sum or Average | 0.574883E+10 | 0.291846E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28248834.49 | 0.262012E+10 |
Minimum of Months | 0.440737E+09 | 0.223726E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3655.28 | 0.125153E+09 |
Maximum of Months | 0.489771E+09 | 0.248642E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12528026.57 | 0.308782E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.762439E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1038389.22 | 0.148564E+09 |
February | 0.339028E+09 | 0.688413E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 150385.58 | 0.130916E+09 |
March | 0.376747E+09 | 0.764789E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 179272.37 | 0.155464E+09 |
April | 0.363528E+09 | 0.736588E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 786384.53 | 0.114833E+09 |
May | 0.375778E+09 | 0.763761E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43784.98 | 0.115518E+09 |
June | 0.364321E+09 | 0.739966E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 292017.49 | 84218636.80 |
July | 0.374985E+09 | 0.760382E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2738537.29 | 64439436.81 |
August | 0.376571E+09 | 0.765082E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3284748.36 | 60531336.03 |
September | 0.363352E+09 | 0.736882E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4150074.43 | 74582200.50 |
October | 0.375161E+09 | 0.762145E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8479675.27 | 76168549.91 |
November | 0.362735E+09 | 0.739379E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 869226.59 | 0.128283E+09 |
December | 0.374985E+09 | 0.760382E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1016292.12 | 0.142843E+09 |
Annual Sum or Average | 0.442217E+10 | 0.898021E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23028788.24 | 0.129636E+10 |
Minimum of Months | 0.339028E+09 | 0.688413E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43784.98 | 60531336.03 |
Maximum of Months | 0.376747E+09 | 0.765082E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8479675.27 | 0.155464E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 651583.99 | 0.436049E+09 |
February | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 85448.87 | 0.387466E+09 |
March | 0.155131E+10 | 0.472384E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456130E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 632117.23 | 0.336480E+09 |
May | 0.154732E+10 | 0.471749E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336169E+09 |
June | 0.150015E+10 | 0.457052E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 51169.32 | 0.242265E+09 |
July | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 3871328.65 | 0.183579E+09 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 4420256.16 | 0.174963E+09 |
September | 0.149615E+10 | 0.455147E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 8771838.96 | 0.219800E+09 |
October | 0.154478E+10 | 0.470751E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 16700666.04 | 0.224362E+09 |
November | 0.149361E+10 | 0.456689E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 777574.95 | 0.375735E+09 |
December | 0.154405E+10 | 0.469662E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 489738.34 | 0.419732E+09 |
Annual Sum or Average | 0.182090E+11 | 0.554677E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 36451722.50 | 0.379273E+10 |
Minimum of Months | 0.139600E+10 | 0.425209E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174963E+09 |
Maximum of Months | 0.155131E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 16700666.04 | 0.456130E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.265929E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1156284.21 | 0.723146E+09 |
February | 0.236489E+11 | 0.240110E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 151644.15 | 0.648892E+09 |
March | 0.262800E+11 | 0.266749E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747383E+09 |
April | 0.253579E+11 | 0.256913E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1121670.23 | 0.580490E+09 |
May | 0.262123E+11 | 0.266390E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581299E+09 |
June | 0.254132E+11 | 0.258091E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90785.58 | 0.428675E+09 |
July | 0.261570E+11 | 0.265212E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6868912.67 | 0.325618E+09 |
August | 0.262677E+11 | 0.266851E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7844268.99 | 0.310296E+09 |
September | 0.253456E+11 | 0.257015E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15567020.04 | 0.389135E+09 |
October | 0.261693E+11 | 0.265826E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29637009.89 | 0.392926E+09 |
November | 0.253025E+11 | 0.257886E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1379858.15 | 0.644114E+09 |
December | 0.261570E+11 | 0.265212E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 869094.37 | 0.698178E+09 |
Annual Sum or Average | 0.308468E+12 | 0.313218E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64686548.26 | 0.647015E+10 |
Minimum of Months | 0.236489E+11 | 0.240110E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310296E+09 |
Maximum of Months | 0.262800E+11 | 0.266851E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29637009.89 | 0.747383E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.171043E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4156080.91 | 0.211890E+10 |
February | 0.702046E+11 | 0.154437E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 434428.81 | 0.185452E+10 |
March | 0.780153E+11 | 0.171571E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216340E+10 |
April | 0.752779E+11 | 0.165244E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3946182.24 | 0.161424E+10 |
May | 0.778146E+11 | 0.171340E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87764.78 | 0.158247E+10 |
June | 0.754422E+11 | 0.166002E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2574968.18 | 0.114413E+10 |
July | 0.776503E+11 | 0.170582E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27221910.53 | 0.882315E+09 |
August | 0.779788E+11 | 0.171636E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26395284.29 | 0.856132E+09 |
September | 0.752414E+11 | 0.165310E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45568983.89 | 0.107561E+10 |
October | 0.776868E+11 | 0.170977E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85042729.35 | 0.109412E+10 |
November | 0.751137E+11 | 0.165870E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3944049.81 | 0.183591E+10 |
December | 0.776503E+11 | 0.170582E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2484304.11 | 0.204750E+10 |
Annual Sum or Average | 0.915726E+12 | 0.201459E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201857E+09 | 0.182692E+11 |
Minimum of Months | 0.702046E+11 | 0.154437E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856132E+09 |
Maximum of Months | 0.780153E+11 | 0.171636E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85042729.35 | 0.216340E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 927595.93 | 0.161621E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 171357.52 | 0.141872E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 140259.48 | 0.169554E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 849215.15 | 0.117661E+09 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68067.05 | 0.115777E+09 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 973942.25 | 74975161.86 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5186066.55 | 49340745.04 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6072807.85 | 46000888.11 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6201063.06 | 65941557.31 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10919603.43 | 67617368.28 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 772194.24 | 0.135469E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 854930.74 | 0.154283E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33137103.23 | 0.130011E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68067.05 | 46000888.11 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10919603.43 | 0.169554E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 802575.48 | 0.162617E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 140957.79 | 0.142966E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 134615.78 | 0.172712E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 643215.63 | 0.132271E+09 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40970.60 | 0.133728E+09 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 605475.67 | 0.104899E+09 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4252126.07 | 85214647.99 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4878832.43 | 79922252.46 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5896660.17 | 89375416.48 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10182769.41 | 85333647.90 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 727706.65 | 0.138485E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 760184.36 | 0.155666E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29066090.04 | 0.148319E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40970.60 | 79922252.46 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10182769.41 | 0.172712E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.332597E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68882051.79 |
February | 0.00 | 0.300367E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60759687.76 |
March | 0.00 | 0.329954E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69841330.45 |
April | 0.00 | 0.322251E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 586.27 | 55700381.29 |
May | 0.00 | 0.331275E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56123331.89 |
June | 0.00 | 0.319694E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44263180.18 |
July | 0.00 | 0.333875E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43999.36 | 36937503.47 |
August | 0.00 | 0.329954E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30173.07 | 35806670.48 |
September | 0.00 | 0.322338E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 657864.53 | 41173399.86 |
October | 0.00 | 0.332554E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127568.96 | 41421936.52 |
November | 0.00 | 0.320973E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.50 | 61059861.56 |
December | 0.00 | 0.333919E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66889361.72 |
Annual Sum or Average | 0.00 | 0.390975E+10 | 0.256575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1860644.69 | 0.638859E+09 |
Minimum of Months | 0.00 | 0.300367E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35806670.48 |
Maximum of Months | 0.00 | 0.333919E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1127568.96 | 69841330.45 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.332688E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 236579.79 | 45151226.91 |
February | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41582.45 | 39582176.65 |
March | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40983.53 | 47483667.09 |
April | 0.293479E+09 | 0.322339E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 185076.89 | 34171701.94 |
May | 0.303504E+09 | 0.331366E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12022.40 | 34398675.25 |
June | 0.293842E+09 | 0.319782E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 166615.50 | 25199808.02 |
July | 0.303141E+09 | 0.333967E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1160207.98 | 19458920.23 |
August | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1341917.84 | 18084973.51 |
September | 0.293479E+09 | 0.322426E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1649057.85 | 21910955.80 |
October | 0.303322E+09 | 0.332644E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2856151.87 | 22365532.48 |
November | 0.293661E+09 | 0.321060E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 214055.56 | 38112992.35 |
December | 0.303141E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 225460.23 | 43135954.06 |
Annual Sum or Average | 0.357224E+10 | 0.391082E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8129711.91 | 0.389057E+09 |
Minimum of Months | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12022.40 | 18084973.51 |
Maximum of Months | 0.303685E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2856151.87 | 47483667.09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 923091.95 | 0.162263E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 170292.98 | 0.142085E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 138851.69 | 0.170081E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 842013.81 | 0.118173E+09 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67119.03 | 0.116248E+09 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 949747.29 | 75221407.85 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5166904.82 | 49664332.12 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6041338.10 | 46308837.00 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6190263.65 | 65991303.65 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10899439.20 | 67867080.39 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 769372.28 | 0.135712E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 851253.67 | 0.154711E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33009688.48 | 0.130433E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67119.03 | 46308837.00 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10899439.20 | 0.170081E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 771609.32 | 0.164324E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 131614.55 | 0.142946E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121273.78 | 0.171975E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 612588.09 | 0.125968E+09 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39773.40 | 0.127489E+09 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 516418.00 | 95980184.42 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4033937.76 | 78120500.02 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4559943.02 | 73173077.21 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5830262.00 | 81923349.68 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10052065.04 | 82278152.31 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 696812.67 | 0.138879E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 704414.52 | 0.157266E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28070712.14 | 0.144032E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39773.40 | 73173077.21 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10052065.04 | 0.171975E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.195823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351842.78 | 0.246102E+09 |
February | 0.348285E+10 | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46349.61 | 0.218634E+09 |
March | 0.387034E+10 | 0.196427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256804E+09 |
April | 0.373454E+10 | 0.189184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346978.11 | 0.190398E+09 |
May | 0.386038E+10 | 0.196163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190336E+09 |
June | 0.374269E+10 | 0.190052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26656.88 | 0.137377E+09 |
July | 0.385223E+10 | 0.195295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2130132.08 | 0.104278E+09 |
August | 0.386853E+10 | 0.196502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2423278.48 | 99407065.90 |
September | 0.373273E+10 | 0.189259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4897819.47 | 0.124668E+09 |
October | 0.385404E+10 | 0.195748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9322732.24 | 0.127233E+09 |
November | 0.372639E+10 | 0.189901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426271.05 | 0.212549E+09 |
December | 0.385223E+10 | 0.195295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263876.77 | 0.237140E+09 |
Annual Sum or Average | 0.454292E+11 | 0.230646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20235937.46 | 0.214493E+10 |
Minimum of Months | 0.348285E+10 | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99407065.90 |
Maximum of Months | 0.387034E+10 | 0.196502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9322732.24 | 0.256804E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529224E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 886021.54 | 0.161375E+09 |
February | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 165035.91 | 0.141391E+09 |
March | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 130466.13 | 0.169138E+09 |
April | 0.293479E+09 | 0.512762E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 808561.69 | 0.118140E+09 |
May | 0.303504E+09 | 0.527121E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59525.77 | 0.116317E+09 |
June | 0.293842E+09 | 0.508693E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 892241.52 | 75681083.37 |
July | 0.303141E+09 | 0.531258E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4969903.75 | 50092720.38 |
August | 0.303685E+09 | 0.525018E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5822889.13 | 46660840.77 |
September | 0.293479E+09 | 0.512899E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6111862.32 | 66534483.98 |
October | 0.303322E+09 | 0.529155E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10755806.95 | 68003867.99 |
November | 0.293661E+09 | 0.510727E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 744004.28 | 0.135564E+09 |
December | 0.303141E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 818472.59 | 0.154041E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622114E+10 | 0.261953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32164791.60 | 0.130294E+10 |
Minimum of Months | 0.273974E+09 | 0.477941E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59525.77 | 46660840.77 |
Maximum of Months | 0.303685E+09 | 0.531327E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10755806.95 | 0.169138E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.529162E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 779488.97 | 0.161453E+09 |
February | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 136979.66 | 0.141941E+09 |
March | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 123922.28 | 0.172279E+09 |
April | 0.293479E+09 | 0.512701E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 613473.85 | 0.133467E+09 |
May | 0.303504E+09 | 0.527059E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35660.83 | 0.134804E+09 |
June | 0.293842E+09 | 0.508634E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 555557.82 | 0.106932E+09 |
July | 0.303141E+09 | 0.531196E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4094348.31 | 88002516.94 |
August | 0.303685E+09 | 0.524956E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4691629.69 | 82258211.12 |
September | 0.293479E+09 | 0.512839E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5833731.58 | 90214702.24 |
October | 0.303322E+09 | 0.529093E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10098434.14 | 84922014.75 |
November | 0.293661E+09 | 0.510668E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 713281.08 | 0.137712E+09 |
December | 0.303141E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 760855.43 | 0.154315E+09 |
Annual Sum or Average | 0.357224E+10 | 0.622041E+10 | 0.261922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28437363.62 | 0.148830E+10 |
Minimum of Months | 0.273974E+09 | 0.477885E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35660.83 | 82258211.12 |
Maximum of Months | 0.303685E+09 | 0.531265E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10098434.14 | 0.172279E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.332688E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 449249.01 | 83720646.75 |
February | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83657.94 | 73293544.17 |
March | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65843.16 | 87333913.68 |
April | 0.293479E+09 | 0.322339E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 412590.31 | 60581758.77 |
May | 0.303504E+09 | 0.331366E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30474.01 | 59407845.91 |
June | 0.293842E+09 | 0.319782E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 459005.32 | 38562351.34 |
July | 0.303141E+09 | 0.333967E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2550818.58 | 25543549.74 |
August | 0.303685E+09 | 0.330044E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2979836.56 | 23841095.14 |
September | 0.293479E+09 | 0.322426E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3122186.58 | 34071321.22 |
October | 0.303322E+09 | 0.332644E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5486341.77 | 35050114.99 |
November | 0.293661E+09 | 0.321060E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 378253.27 | 70104819.65 |
December | 0.303141E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 415089.00 | 79930779.99 |
Annual Sum or Average | 0.357224E+10 | 0.391082E+10 | 0.256645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16433345.48 | 0.671442E+09 |
Minimum of Months | 0.273974E+09 | 0.300450E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30474.01 | 23841095.14 |
Maximum of Months | 0.303685E+09 | 0.334010E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5486341.77 | 87333913.68 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.466994E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1341290.21 | 0.466137E+09 |
February | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191919.31 | 0.417765E+09 |
March | 0.461508E+11 | 0.468433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1487.71 | 0.494934E+09 |
April | 0.445315E+11 | 0.451160E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 716052.12 | 0.374588E+09 |
May | 0.460320E+11 | 0.467803E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376090E+09 |
June | 0.446286E+11 | 0.453229E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55014.05 | 0.274519E+09 |
July | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4281901.55 | 0.210304E+09 |
August | 0.461292E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4862968.14 | 0.199788E+09 |
September | 0.445099E+11 | 0.451340E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9926848.19 | 0.246487E+09 |
October | 0.459565E+11 | 0.466814E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19540195.64 | 0.248048E+09 |
November | 0.444343E+11 | 0.452870E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1068240.15 | 0.406539E+09 |
December | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1288866.41 | 0.450347E+09 |
Annual Sum or Average | 0.541708E+12 | 0.550038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 43274783.48 | 0.416555E+10 |
Minimum of Months | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199788E+09 |
Maximum of Months | 0.461508E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19540195.64 | 0.494934E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.466994E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 980384.13 | 0.476314E+09 |
February | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136859.86 | 0.427091E+09 |
March | 0.461508E+11 | 0.468433E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505056E+09 |
April | 0.445315E+11 | 0.451160E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 674298.75 | 0.380829E+09 |
May | 0.460320E+11 | 0.467803E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381734E+09 |
June | 0.446286E+11 | 0.453229E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47480.98 | 0.277518E+09 |
July | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4157591.63 | 0.212277E+09 |
August | 0.461292E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4708647.71 | 0.202053E+09 |
September | 0.445099E+11 | 0.451340E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9831821.04 | 0.250576E+09 |
October | 0.459565E+11 | 0.466814E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18899877.99 | 0.252999E+09 |
November | 0.444343E+11 | 0.452870E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 895361.36 | 0.415575E+09 |
December | 0.459349E+11 | 0.465734E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 926079.45 | 0.460292E+09 |
Annual Sum or Average | 0.541708E+12 | 0.550038E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 41258402.89 | 0.424231E+10 |
Minimum of Months | 0.415303E+11 | 0.421653E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202053E+09 |
Maximum of Months | 0.461508E+11 | 0.468613E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18899877.99 | 0.505056E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.124679E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 595586.21 | 0.448043E+09 |
February | 0.369574E+10 | 0.112574E+10 | 0.304050E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 78977.08 | 0.398183E+09 |
March | 0.410691E+10 | 0.125063E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468511E+09 |
April | 0.396281E+10 | 0.120452E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 602314.09 | 0.346554E+09 |
May | 0.409635E+10 | 0.124895E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346430E+09 |
June | 0.397146E+10 | 0.121004E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 42188.96 | 0.250652E+09 |
July | 0.408770E+10 | 0.124343E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3712819.03 | 0.190799E+09 |
August | 0.410499E+10 | 0.125111E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4198532.29 | 0.181952E+09 |
September | 0.396089E+10 | 0.120500E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 8737434.78 | 0.227561E+09 |
October | 0.408962E+10 | 0.124631E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16623885.66 | 0.232176E+09 |
November | 0.395417E+10 | 0.120908E+10 | 0.325768E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 738807.27 | 0.386501E+09 |
December | 0.408770E+10 | 0.124343E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 444979.19 | 0.431415E+09 |
Annual Sum or Average | 0.482060E+11 | 0.146850E+11 | 0.396352E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 35775524.56 | 0.390878E+10 |
Minimum of Months | 0.369574E+10 | 0.112574E+10 | 0.304050E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181952E+09 |
Maximum of Months | 0.410691E+10 | 0.125111E+10 | 0.336627E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16623885.66 | 0.468511E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.207249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584151.22 | 0.422521E+09 |
February | 0.368610E+10 | 0.187127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77470.28 | 0.378668E+09 |
March | 0.409620E+10 | 0.207888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443462E+09 |
April | 0.395248E+10 | 0.200222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590751.69 | 0.335768E+09 |
May | 0.408566E+10 | 0.207608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336589E+09 |
June | 0.396110E+10 | 0.201140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41601.22 | 0.245084E+09 |
July | 0.407704E+10 | 0.206690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3640333.91 | 0.186721E+09 |
August | 0.409429E+10 | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4117888.22 | 0.178063E+09 |
September | 0.395056E+10 | 0.200302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8555646.62 | 0.222504E+09 |
October | 0.407896E+10 | 0.207169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16279105.70 | 0.225385E+09 |
November | 0.394385E+10 | 0.200981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 724302.33 | 0.371429E+09 |
December | 0.407704E+10 | 0.206690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436358.12 | 0.409146E+09 |
Annual Sum or Average | 0.480803E+11 | 0.244103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35047609.31 | 0.375534E+10 |
Minimum of Months | 0.368610E+10 | 0.187127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178063E+09 |
Maximum of Months | 0.409620E+10 | 0.207967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16279105.70 | 0.443462E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 19711.29 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 19711.29 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 19711.29 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 19711.29 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 19711.29 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 19711.29 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 19711.29 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 19711.29 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 19711.29 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 19711.29 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 19711.29 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 19711.29 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 974.63 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 14-JAN-11:00 | 250.87 | 08-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 974.63 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 01-FEB-12:00 | 196.97 | 04-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 974.63 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 210.81 | 08-MAR-04:00 |
April | 1169.53 | 01-APR-00:10 | 974.63 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 26-APR-13:00 | 170.86 | 01-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 974.63 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 158.99 | 15-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 974.63 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 | 29-JUN-11:00 | 123.50 | 12-JUN-21:00 |
July | 1169.53 | 01-JUL-00:10 | 974.63 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.47 | 19-JUL-12:00 | 99.12 | 06-JUL-01:00 |
August | 1169.53 | 01-AUG-00:10 | 974.63 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.56 | 18-AUG-12:00 | 98.65 | 21-AUG-20:00 |
September | 1169.53 | 01-SEP-00:10 | 974.63 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.69 | 29-SEP-11:00 | 120.33 | 20-SEP-03:00 |
October | 1169.53 | 01-OCT-23:10 | 974.63 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.56 | 16-OCT-11:00 | 146.04 | 30-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 974.63 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 | 19-NOV-13:00 | 181.65 | 29-NOV-23:00 |
December | 1169.53 | 01-DEC-00:10 | 974.63 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.02 | 16-DEC-13:00 | 197.49 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 974.63 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.65 | |||||
Maximum of Months | 1169.53 | 974.63 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 143.56 | 250.87 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 1128.63 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.63 | 14-JAN-12:00 | 102.93 | 08-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 1128.63 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 | 01-FEB-12:00 | 84.29 | 04-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 1128.63 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 | 11-MAR-10:51 | 89.47 | 08-MAR-02:00 |
April | 1354.32 | 01-APR-00:10 | 1128.63 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 | 26-APR-13:00 | 71.50 | 01-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 1128.63 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 | 03-MAY-12:00 | 69.69 | 19-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 1128.63 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 29-JUN-11:00 | 55.86 | 12-JUN-21:00 |
July | 1354.32 | 01-JUL-00:10 | 1128.63 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 19-JUL-11:00 | 48.27 | 06-JUL-01:00 |
August | 1354.32 | 01-AUG-00:10 | 1128.63 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.47 | 14-AUG-11:00 | 43.02 | 24-AUG-02:00 |
September | 1354.32 | 01-SEP-00:10 | 1128.63 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.57 | 29-SEP-11:40 | 55.91 | 20-SEP-03:00 |
October | 1354.32 | 01-OCT-23:10 | 1128.63 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.36 | 16-OCT-11:00 | 65.69 | 27-OCT-04:30 |
November | 1354.32 | 01-NOV-00:10 | 1128.63 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.07 | 19-NOV-13:00 | 80.32 | 29-NOV-23:00 |
December | 1354.32 | 01-DEC-00:10 | 1128.63 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 16-DEC-13:00 | 85.70 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 | 43.02 | |||||
Maximum of Months | 1354.32 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 57.36 | 102.93 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 2386.66 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.87 | 13-JAN-14:00 | 244.59 | 08-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 2386.66 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 | 01-FEB-12:00 | 199.59 | 04-FEB-06:00 |
March | 286.42 | 01-MAR-00:10 | 2386.66 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 11-MAR-10:51 | 209.78 | 08-MAR-02:00 |
April | 286.42 | 01-APR-00:10 | 2386.66 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 | 26-APR-13:00 | 169.83 | 01-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 2386.66 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 03-MAY-12:00 | 166.67 | 27-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 2386.66 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 | 29-JUN-11:00 | 133.75 | 13-JUN-04:40 |
July | 286.42 | 01-JUL-00:10 | 2386.66 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 | 19-JUL-12:00 | 116.50 | 06-JUL-01:00 |
August | 286.42 | 01-AUG-00:10 | 2386.66 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.56 | 18-AUG-12:00 | 106.33 | 28-AUG-07:00 |
September | 286.42 | 01-SEP-00:10 | 2386.66 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.05 | 29-SEP-11:00 | 133.38 | 20-SEP-03:00 |
October | 286.42 | 01-OCT-23:10 | 2386.66 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.97 | 16-OCT-11:00 | 158.06 | 12-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 2386.66 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.09 | 19-NOV-13:00 | 189.84 | 29-NOV-23:00 |
December | 286.42 | 01-DEC-00:10 | 2386.66 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.99 | 16-DEC-13:00 | 204.57 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 106.33 | |||||
Maximum of Months | 286.42 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 130.97 | 244.59 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 734.39 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 13-JAN-14:00 | 132.04 | 08-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 734.39 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.27 | 01-FEB-12:00 | 105.78 | 04-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 734.39 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 11-MAR-10:51 | 110.95 | 08-MAR-04:00 |
April | 220.32 | 01-APR-00:10 | 734.39 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 26-APR-13:00 | 89.93 | 01-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 734.39 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 03-MAY-12:00 | 87.71 | 27-MAY-03:00 |
June | 220.32 | 01-JUN-00:10 | 734.39 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 29-JUN-11:00 | 69.81 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 734.39 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.23 | 31-JUL-12:00 | 60.43 | 06-JUL-01:00 |
August | 220.32 | 01-AUG-00:10 | 734.39 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.85 | 14-AUG-11:00 | 53.55 | 28-AUG-07:00 |
September | 220.32 | 01-SEP-00:10 | 734.39 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.85 | 29-SEP-11:00 | 69.18 | 20-SEP-03:00 |
October | 220.32 | 01-OCT-23:10 | 734.39 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.47 | 16-OCT-11:00 | 81.66 | 27-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 734.39 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.44 | 19-NOV-13:00 | 99.45 | 29-NOV-23:00 |
December | 220.32 | 01-DEC-00:10 | 734.39 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.39 | 16-DEC-13:00 | 107.19 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 53.55 | |||||
Maximum of Months | 220.32 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 77.47 | 132.04 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.60 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 28.61 | 14-JAN-11:00 | 359.35 | 08-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 453.60 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 28.46 | 01-FEB-12:00 | 291.33 | 04-FEB-06:00 |
March | 907.20 | 01-MAR-00:10 | 453.60 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 308.90 | 08-MAR-04:00 |
April | 907.20 | 01-APR-00:10 | 453.60 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 42.55 | 26-APR-13:00 | 258.43 | 01-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 453.60 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 243.70 | 15-MAY-02:00 |
June | 907.20 | 01-JUN-00:10 | 453.60 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 14.25 | 29-JUN-11:00 | 196.17 | 13-JUN-04:10 |
July | 907.20 | 01-JUL-00:10 | 453.60 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 56.63 | 19-JUL-12:00 | 163.77 | 06-JUL-01:00 |
August | 907.20 | 01-AUG-00:10 | 453.60 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 56.74 | 18-AUG-12:00 | 148.24 | 24-AUG-02:00 |
September | 907.20 | 01-SEP-00:10 | 453.60 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 165.29 | 29-SEP-11:00 | 194.80 | 20-SEP-03:10 |
October | 907.20 | 01-OCT-23:10 | 453.60 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 178.83 | 16-OCT-11:00 | 227.38 | 30-OCT-04:00 |
November | 907.20 | 01-NOV-00:10 | 453.60 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 42.57 | 19-NOV-13:00 | 259.62 | 24-NOV-01:00 |
December | 907.20 | 01-DEC-00:10 | 453.60 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 28.65 | 16-DEC-13:00 | 292.07 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 148.24 | ||||||
Maximum of Months | 907.20 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 178.83 | 359.35 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2561.44 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 14-JAN-10:55 | 554.53 | 08-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 2561.44 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.51 | 01-FEB-12:00 | 438.77 | 04-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 2561.44 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 465.97 | 08-MAR-02:00 |
April | 15368.40 | 01-APR-00:10 | 2561.44 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.51 | 26-APR-13:00 | 377.71 | 01-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 2561.44 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 377.17 | 15-MAY-02:00 |
June | 15368.40 | 01-JUN-00:10 | 2561.44 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 29-JUN-11:00 | 328.71 | 13-JUN-04:00 |
July | 15368.40 | 01-JUL-00:10 | 2561.44 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.49 | 19-JUL-12:00 | 290.56 | 06-JUL-01:00 |
August | 15368.40 | 01-AUG-00:10 | 2561.44 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.69 | 18-AUG-12:00 | 263.00 | 31-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 2561.44 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.33 | 29-SEP-11:00 | 330.01 | 20-SEP-03:00 |
October | 15368.40 | 01-OCT-23:10 | 2561.44 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.35 | 16-OCT-11:00 | 370.87 | 30-OCT-03:00 |
November | 15368.40 | 01-NOV-00:10 | 2561.44 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.55 | 19-NOV-13:00 | 433.74 | 29-NOV-23:00 |
December | 15368.40 | 01-DEC-00:10 | 2561.44 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.85 | 16-DEC-13:00 | 436.56 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2561.44 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.00 | |||||
Maximum of Months | 15368.40 | 2561.44 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 317.35 | 554.53 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 16474.99 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.08 | 14-JAN-11:00 | 1707.68 | 08-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 16474.99 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.34 | 01-FEB-12:00 | 1420.41 | 04-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 16474.99 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1495.41 | 08-MAR-02:00 |
April | 45622.98 | 01-APR-00:10 | 16474.99 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.33 | 26-APR-13:00 | 1199.84 | 01-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 16474.99 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 | 03-MAY-12:00 | 1177.13 | 19-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 16474.99 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.26 | 29-JUN-11:00 | 951.28 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 16474.99 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.81 | 19-JUL-11:00 | 814.50 | 06-JUL-01:00 |
August | 45622.98 | 01-AUG-00:10 | 16474.99 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.55 | 14-AUG-11:00 | 735.80 | 28-AUG-04:40 |
September | 45622.98 | 01-SEP-00:10 | 16474.99 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 838.10 | 29-SEP-11:00 | 952.70 | 20-SEP-03:00 |
October | 45622.98 | 01-OCT-23:10 | 16474.99 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 906.76 | 16-OCT-11:00 | 1114.89 | 27-OCT-04:30 |
November | 45622.98 | 01-NOV-00:10 | 16474.99 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.96 | 19-NOV-13:00 | 1316.12 | 23-NOV-22:00 |
December | 45622.98 | 01-DEC-00:10 | 16474.99 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.39 | 16-DEC-13:00 | 1421.92 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 16474.99 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 735.80 | |||||
Maximum of Months | 45622.98 | 16474.99 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 906.76 | 1707.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 14-JAN-10:51 | 146.73 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 01-FEB-09:51 | 115.42 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 | 11-MAR-10:50 | 123.46 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | 26-APR-13:00 | 100.26 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 | 03-MAY-09:51 | 93.36 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | 29-JUN-09:50 | 71.40 | 13-JUN-04:40 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 19-JUL-09:50 | 56.57 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 | 15-AUG-09:50 | 57.25 | 28-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.09 | 29-SEP-09:50 | 70.90 | 20-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 16-OCT-11:00 | 85.85 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-09:55 | 100.72 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 | 05-DEC-10:00 | 115.71 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 | 56.57 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 146.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 14-JAN-10:51 | 146.72 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 01-FEB-09:58 | 115.41 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 | 11-MAR-10:50 | 123.45 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | 26-APR-13:00 | 100.25 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 03-MAY-09:51 | 94.97 | 20-MAY-17:55 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | 29-JUN-09:50 | 87.54 | 22-JUN-18:55 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 19-JUL-09:50 | 87.03 | 10-JUL-18:02 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 | 15-AUG-09:50 | 80.65 | 02-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.08 | 29-SEP-09:50 | 81.09 | 14-SEP-19:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 16-OCT-11:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 | 19-NOV-10:00 | 100.72 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 05-DEC-10:00 | 115.70 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 80.65 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 146.72 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 300.93 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 47.17 | 08-JAN-07:00 |
February | 0.00 | 01-FEB-00:10 | 300.93 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 39.47 | 04-FEB-06:00 |
March | 0.00 | 01-MAR-00:10 | 300.93 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 41.66 | 08-MAR-02:00 |
April | 0.00 | 01-APR-00:10 | 300.93 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 26-APR-13:00 | 34.81 | 15-APR-22:00 |
May | 0.00 | 01-MAY-00:10 | 300.93 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 33.81 | 15-MAY-02:00 |
June | 0.00 | 01-JUN-00:10 | 300.93 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 28.73 | 12-JUN-21:00 |
July | 0.00 | 01-JUL-00:10 | 300.93 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 | 19-JUL-12:00 | 25.62 | 06-JUL-01:00 |
August | 0.00 | 01-AUG-00:10 | 300.93 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 18-AUG-12:00 | 24.42 | 28-AUG-07:00 |
September | 0.00 | 01-SEP-00:10 | 300.93 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 29-SEP-11:00 | 28.79 | 20-SEP-03:00 |
October | 0.00 | 01-OCT-00:10 | 300.93 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 16-OCT-11:00 | 32.90 | 29-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 300.93 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 19-NOV-13:00 | 39.13 | 23-NOV-22:00 |
December | 0.00 | 01-DEC-00:10 | 300.93 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 41.75 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 300.93 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 | |||||
Maximum of Months | 0.00 | 300.93 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 47.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 301.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 14-JAN-10:51 | 40.95 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 301.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 01-FEB-09:58 | 32.21 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 301.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 11-MAR-10:50 | 34.45 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 301.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 | 30-APR-09:51 | 27.98 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 301.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 03-MAY-09:51 | 26.06 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 301.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 29-JUN-09:50 | 20.41 | 02-JUN-20:00 |
July | 180.00 | 01-JUL-00:10 | 301.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 19-JUL-09:50 | 19.74 | 08-JUL-21:00 |
August | 180.00 | 01-AUG-00:10 | 301.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 15-AUG-09:50 | 18.76 | 21-AUG-20:10 |
September | 180.00 | 01-SEP-00:10 | 301.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 | 29-SEP-09:51 | 19.79 | 20-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 301.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 16-OCT-09:51 | 23.96 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 301.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 19-NOV-10:00 | 28.11 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 301.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 05-DEC-10:00 | 32.29 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 18.76 | |||||
Maximum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 | 40.95 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.19 | 14-JAN-10:51 | 146.73 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 01-FEB-09:51 | 115.42 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 | 11-MAR-10:50 | 123.46 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | 26-APR-13:00 | 100.26 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 03-MAY-09:51 | 93.36 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | 29-JUN-09:50 | 71.40 | 13-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 | 19-JUL-09:50 | 56.57 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 | 15-AUG-09:45 | 63.95 | 28-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.09 | 29-SEP-09:50 | 71.85 | 20-SEP-07:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 16-OCT-11:00 | 85.85 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-10:00 | 103.52 | 05-NOV-07:10 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.32 | 05-DEC-10:00 | 115.71 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 56.57 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 146.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.81 | 14-JAN-10:51 | 146.72 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 01-FEB-10:00 | 115.41 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 | 11-MAR-10:50 | 123.45 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 | 26-APR-13:00 | 100.25 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 03-MAY-09:51 | 93.35 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 | 29-JUN-09:50 | 77.82 | 23-JUN-07:40 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.02 | 19-JUL-09:50 | 79.91 | 06-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.80 | 15-AUG-09:50 | 86.66 | 26-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.08 | 29-SEP-09:50 | 73.85 | 10-SEP-08:00 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 16-OCT-11:00 | 85.84 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 | 19-NOV-10:10 | 100.72 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 05-DEC-10:00 | 115.70 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 73.85 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 146.72 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1886.18 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 | 14-JAN-10:53 | 198.24 | 08-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1886.18 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.71 | 01-FEB-12:00 | 163.90 | 04-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1886.18 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 173.16 | 08-MAR-02:00 |
April | 2263.36 | 01-APR-00:10 | 1886.18 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.64 | 26-APR-13:00 | 142.06 | 01-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1886.18 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 137.68 | 15-MAY-02:00 |
June | 2263.36 | 01-JUN-00:10 | 1886.18 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 | 29-JUN-11:00 | 110.89 | 13-JUN-04:00 |
July | 2263.36 | 01-JUL-00:10 | 1886.18 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 | 19-JUL-12:00 | 92.63 | 06-JUL-01:00 |
August | 2263.36 | 01-AUG-00:10 | 1886.18 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | 18-AUG-12:00 | 83.87 | 31-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1886.18 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.81 | 29-SEP-11:00 | 110.11 | 20-SEP-04:00 |
October | 2263.36 | 01-OCT-23:10 | 1886.18 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.44 | 16-OCT-11:00 | 128.47 | 30-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1886.18 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 19-NOV-13:00 | 146.65 | 24-NOV-01:00 |
December | 2263.36 | 01-DEC-00:10 | 1886.18 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 | 16-DEC-13:00 | 164.80 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1886.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.87 | ||||
Maximum of Months | 2263.36 | 1886.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.44 | 198.24 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.83 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.99 | 14-JAN-10:51 | 147.19 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.83 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 01-FEB-09:51 | 115.87 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.83 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 | 11-MAR-10:50 | 123.91 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 478.83 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 26-APR-13:00 | 100.70 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.83 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.66 | 03-MAY-09:51 | 93.80 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 478.83 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 | 29-JUN-09:50 | 71.83 | 13-JUN-04:40 |
July | 180.00 | 01-JUL-00:10 | 478.83 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.23 | 19-JUL-09:50 | 56.99 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 478.83 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.16 | 15-AUG-09:50 | 55.26 | 28-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 478.83 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.72 | 29-SEP-09:50 | 71.33 | 20-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 478.83 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.97 | 16-OCT-11:00 | 86.29 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 478.83 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 19-NOV-09:55 | 101.17 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 478.83 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 | 05-DEC-10:00 | 116.16 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 9.66 | 55.26 | |||||
Maximum of Months | 180.00 | 478.83 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.97 | 147.19 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 478.78 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.75 | 14-JAN-10:51 | 147.19 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 478.78 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 01-FEB-09:58 | 115.86 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 478.78 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 11-MAR-10:50 | 123.90 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 478.78 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.57 | 26-APR-13:00 | 100.70 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 478.78 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 | 03-MAY-09:51 | 99.00 | 20-MAY-17:55 |
June | 180.00 | 01-JUN-00:10 | 478.78 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 29-JUN-09:50 | 93.20 | 22-JUN-18:55 |
July | 180.00 | 01-JUL-00:10 | 478.78 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.23 | 19-JUL-09:50 | 95.49 | 10-JUL-18:02 |
August | 180.00 | 01-AUG-00:10 | 478.78 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.16 | 15-AUG-09:50 | 86.18 | 02-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 478.78 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.72 | 29-SEP-09:50 | 83.51 | 14-SEP-18:35 |
October | 180.00 | 01-OCT-00:10 | 478.78 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.96 | 16-OCT-11:00 | 86.28 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 478.78 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 19-NOV-10:00 | 101.16 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 478.78 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.92 | 05-DEC-10:00 | 116.15 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 | 83.51 | |||||
Maximum of Months | 180.00 | 478.78 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.96 | 147.19 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 301.01 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 14-JAN-10:50 | 75.31 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 301.01 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 01-FEB-09:51 | 59.28 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 301.01 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 | 11-MAR-10:50 | 63.40 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 301.01 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 26-APR-13:00 | 51.52 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 301.01 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 03-MAY-09:51 | 47.99 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 301.01 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 | 29-JUN-09:50 | 36.75 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 301.01 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 19-JUL-09:50 | 29.16 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 301.01 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 15-AUG-09:50 | 29.23 | 28-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 301.01 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 | 29-SEP-09:50 | 36.49 | 20-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 301.01 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 16-OCT-11:00 | 44.15 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 301.01 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 | 19-NOV-10:00 | 51.76 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 301.01 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 05-DEC-10:00 | 59.43 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 29.16 | |||||
Maximum of Months | 180.00 | 301.01 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 75.31 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 4498.11 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.27 | 13-JAN-14:00 | 357.51 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 4498.11 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.43 | 01-FEB-12:00 | 315.70 | 04-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 4498.11 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 | 11-MAR-10:51 | 327.42 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 4498.11 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.81 | 26-APR-13:00 | 281.18 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 4498.11 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 272.18 | 15-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 4498.11 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 | 29-JUN-11:00 | 223.25 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 4498.11 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.82 | 19-JUL-12:00 | 188.01 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 4498.11 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.95 | 18-AUG-12:00 | 170.32 | 24-AUG-02:00 |
September | 26988.77 | 01-SEP-00:10 | 4498.11 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.50 | 29-SEP-11:00 | 218.87 | 20-SEP-03:00 |
October | 26988.77 | 01-OCT-23:10 | 4498.11 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.92 | 16-OCT-11:00 | 252.97 | 12-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 4498.11 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.10 | 19-NOV-13:00 | 297.10 | 23-NOV-22:00 |
December | 26988.77 | 01-DEC-00:10 | 4498.11 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.57 | 05-DEC-09:53 | 314.03 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.32 | |||||
Maximum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 201.92 | 357.51 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 4498.11 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.16 | 13-JAN-14:00 | 359.94 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 4498.11 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.26 | 01-FEB-12:00 | 319.31 | 04-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 4498.11 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 331.80 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 4498.11 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.81 | 26-APR-13:00 | 286.04 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 4498.11 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 275.67 | 15-MAY-02:00 |
June | 26988.77 | 01-JUN-00:10 | 4498.11 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 | 29-JUN-11:00 | 224.85 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 4498.11 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.82 | 19-JUL-12:00 | 188.01 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 4498.11 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.95 | 18-AUG-12:00 | 170.33 | 31-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 4498.11 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.50 | 29-SEP-11:00 | 221.85 | 20-SEP-03:00 |
October | 26988.77 | 01-OCT-23:10 | 4498.11 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.92 | 16-OCT-11:00 | 256.30 | 12-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 4498.11 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.84 | 19-NOV-13:00 | 297.10 | 23-NOV-22:00 |
December | 26988.77 | 01-DEC-00:10 | 4498.11 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.68 | 05-DEC-09:53 | 317.65 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.33 | |||||
Maximum of Months | 26988.77 | 4498.11 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 201.92 | 359.94 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1200.92 | 02-JAN-20:10 | 15028.36 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 27.66 | 14-JAN-10:56 | 367.60 | 08-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1200.92 | 01-FEB-20:10 | 15028.36 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 27.50 | 01-FEB-12:00 | 298.34 | 04-FEB-06:00 |
March | 2401.70 | 01-MAR-00:10 | 1200.92 | 01-MAR-20:10 | 15028.36 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 316.27 | 08-MAR-04:00 |
April | 2401.70 | 01-APR-00:10 | 1200.92 | 03-APR-19:10 | 15028.36 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 41.85 | 26-APR-13:00 | 264.73 | 01-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1200.92 | 01-MAY-19:10 | 15028.36 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 249.83 | 15-MAY-02:00 |
June | 2401.70 | 01-JUN-00:10 | 1200.92 | 01-JUN-19:10 | 15028.36 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 13.01 | 29-JUN-11:00 | 201.36 | 13-JUN-04:00 |
July | 2401.70 | 01-JUL-00:10 | 1200.92 | 03-JUL-19:10 | 15028.36 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 56.19 | 19-JUL-12:00 | 168.35 | 06-JUL-01:00 |
August | 2401.70 | 01-AUG-00:10 | 1200.92 | 01-AUG-19:10 | 15028.36 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 56.30 | 18-AUG-12:00 | 152.53 | 24-AUG-02:00 |
September | 2401.70 | 01-SEP-00:10 | 1200.92 | 01-SEP-19:10 | 15028.36 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 166.95 | 29-SEP-11:00 | 199.97 | 20-SEP-03:00 |
October | 2401.70 | 01-OCT-23:10 | 1200.92 | 02-OCT-19:10 | 15028.36 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 180.74 | 16-OCT-11:00 | 233.18 | 30-OCT-04:00 |
November | 2401.70 | 01-NOV-00:10 | 1200.92 | 01-NOV-19:10 | 15028.36 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 41.87 | 19-NOV-13:00 | 266.03 | 24-NOV-01:00 |
December | 2401.70 | 01-DEC-00:10 | 1200.92 | 01-DEC-20:10 | 15028.36 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 27.68 | 16-DEC-13:00 | 298.99 | 22-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1200.92 | 15028.36 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 152.53 | ||||||
Maximum of Months | 2401.70 | 1200.92 | 15028.36 | 22492.83 | 0.00 | 0.00 | 0.00 | 180.74 | 367.60 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1996.23 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 | 14-JAN-11:20 | 319.81 | 08-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1996.23 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.96 | 01-FEB-12:00 | 274.24 | 04-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1996.23 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 286.20 | 08-MAR-02:00 |
April | 2395.44 | 01-APR-00:10 | 1996.23 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 26-APR-13:00 | 231.31 | 01-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1996.23 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 233.85 | 15-MAY-02:00 |
June | 2395.44 | 01-JUN-00:10 | 1996.23 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.78 | 29-JUN-11:00 | 192.62 | 13-JUN-04:00 |
July | 2395.44 | 01-JUL-00:10 | 1996.23 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.04 | 19-JUL-12:00 | 164.81 | 06-JUL-01:00 |
August | 2395.44 | 01-AUG-00:10 | 1996.23 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.15 | 18-AUG-12:00 | 149.32 | 31-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1996.23 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.42 | 29-SEP-11:00 | 190.17 | 20-SEP-03:00 |
October | 2395.44 | 01-OCT-23:10 | 1996.23 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.92 | 16-OCT-11:00 | 219.37 | 30-OCT-03:00 |
November | 2395.44 | 01-NOV-00:10 | 1996.23 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.01 | 19-NOV-13:00 | 259.39 | 29-NOV-23:00 |
December | 2395.44 | 01-DEC-00:10 | 1996.23 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.13 | 16-DEC-13:00 | 278.84 | 03-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.32 | ||||
Maximum of Months | 2395.44 | 1996.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.92 | 319.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 24764.05 | 20-JAN-21:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23482.25 | 01-FEB-21:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22387.78 | 24-MAR-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22203.07 | 13-APR-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22273.53 | 04-MAY-19:55 | 17891.83 | 39422.58 | 19265.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21939.12 | 30-JUN-21:00 | 10223.90 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23197.52 | 26-JUL-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23419.40 | 18-AUG-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24438.49 | 29-SEP-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25340.10 | 17-OCT-20:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25182.79 | 29-NOV-21:00 | 8945.92 | 19711.29 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24680.69 | 19-DEC-21:00 | 17891.83 | 39422.58 | 19265.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21939.12 | 8945.92 | 17521.15 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25340.10 | 17891.83 | 39422.58 | 19265.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6958.07 | 14-JAN-12:40 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 | 0.00 |
February | 5944.34 | 02-FEB-12:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 |
March | 5684.36 | 11-MAR-12:50 | 389.84 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
April | 4306.95 | 02-APR-12:00 | 389.84 | 324.88 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
May | 3365.26 | 03-MAY-12:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
June | 2397.01 | 27-JUN-12:50 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
July | 3418.40 | 31-JUL-12:40 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 45.38 | 0.00 |
August | 4033.39 | 30-AUG-12:40 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 |
September | 6699.99 | 29-SEP-13:00 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 132.44 | 0.00 |
October | 7664.52 | 16-OCT-12:20 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 124.67 | 0.00 |
November | 7205.64 | 19-NOV-12:30 | 389.84 | 324.88 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 | 0.00 |
December | 7109.76 | 19-DEC-12:30 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2397.01 | 259.90 | 270.73 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7664.52 | 389.84 | 324.88 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 132.44 | 52.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1870.86 | 18-JAN-21:10 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.20 |
February | 1846.74 | 03-FEB-21:10 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.15 |
March | 1998.32 | 23-MAR-18:20 | 1053.36 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 |
April | 2186.47 | 26-APR-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 |
May | 2162.58 | 03-MAY-19:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.68 |
June | 2256.71 | 30-JUN-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.76 |
July | 2341.10 | 19-JUL-19:10 | 2106.72 | 2257.25 | 1587.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 |
August | 2335.14 | 18-AUG-19:10 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 |
September | 2456.69 | 29-SEP-19:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 | 0.00 |
October | 2375.39 | 16-OCT-19:20 | 1053.36 | 1128.63 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
November | 1831.90 | 10-NOV-21:10 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.49 |
December | 1973.40 | 05-DEC-21:10 | 1203.84 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1831.90 | 1053.36 | 1003.22 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2456.69 | 2106.72 | 2257.25 | 1587.86 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 | 54.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2028.18 | 18-JAN-21:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.81 |
February | 1850.66 | 03-FEB-21:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.39 |
March | 1907.71 | 23-MAR-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.77 |
April | 2258.48 | 26-APR-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.37 |
May | 2397.15 | 04-MAY-19:55 | 445.54 | 4773.32 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.45 |
June | 2573.70 | 30-JUN-19:40 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.98 |
July | 2686.37 | 19-JUL-19:40 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.23 |
August | 2581.90 | 18-AUG-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 |
September | 2788.53 | 29-SEP-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 | 0.00 |
October | 2665.93 | 16-OCT-20:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.85 |
November | 1904.75 | 10-NOV-21:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.78 |
December | 2063.33 | 05-DEC-21:00 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1850.66 | 222.77 | 2386.66 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2788.53 | 445.54 | 4773.32 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 | 120.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 895.25 | 14-JAN-12:40 | 73.44 | 204.00 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 | 0.00 |
February | 761.11 | 01-FEB-12:10 | 48.96 | 204.00 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 | 0.00 |
March | 763.51 | 23-MAR-20:20 | 195.84 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.76 |
April | 811.30 | 26-APR-20:00 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 |
May | 830.96 | 04-MAY-19:50 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.62 |
June | 863.45 | 29-JUN-18:20 | 1370.88 | 5222.29 | 1835.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
July | 913.20 | 19-JUL-18:30 | 171.36 | 652.79 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 |
August | 863.80 | 18-AUG-19:40 | 171.36 | 734.39 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.74 |
September | 1012.03 | 29-SEP-13:00 | 48.96 | 204.00 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 70.61 | 0.00 |
October | 1136.85 | 16-OCT-13:00 | 48.96 | 204.00 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 60.71 | 0.00 |
November | 969.69 | 19-NOV-12:30 | 73.44 | 244.80 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 22.87 | 0.00 |
December | 945.93 | 19-DEC-12:40 | 48.96 | 204.00 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 761.11 | 48.96 | 204.00 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1136.85 | 1370.88 | 5222.29 | 1835.30 | 0.00 | 0.00 | 0.00 | 0.00 | 70.61 | 55.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38080.01 | 18-JAN-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 88.55 |
February | 37798.91 | 01-FEB-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 163.88 |
March | 38022.08 | 23-MAR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 148.51 |
April | 38298.17 | 26-APR-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 102.98 |
May | 38350.08 | 04-MAY-19:55 | 1411.20 | 907.21 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 |
June | 38394.80 | 29-JUN-20:00 | 1411.20 | 907.21 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 117.95 |
July | 38568.55 | 19-JUL-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.05 |
August | 38483.30 | 17-AUG-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 73.18 |
September | 38898.04 | 29-SEP-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.21 | 0.00 |
October | 38593.89 | 16-OCT-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 |
November | 37920.79 | 01-NOV-20:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 133.28 |
December | 38092.29 | 05-DEC-21:00 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 118.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37798.91 | 705.60 | 453.60 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38898.04 | 1411.20 | 907.21 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 14.21 | 163.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23355.86 | 14-JAN-12:20 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 42.25 | 0.00 |
February | 19983.91 | 02-FEB-12:30 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 |
March | 19370.08 | 11-MAR-12:30 | 5122.80 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
April | 15824.29 | 02-APR-12:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
May | 12289.80 | 04-MAY-12:00 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
June | 9937.98 | 25-JUN-12:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
July | 12167.81 | 31-JUL-12:30 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 100.29 | 0.00 |
August | 14417.31 | 27-AUG-12:00 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.60 |
September | 21351.58 | 29-SEP-12:00 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 293.06 | 0.00 |
October | 24371.24 | 15-OCT-11:40 | 5122.80 | 853.81 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 198.56 | 0.00 |
November | 23894.36 | 19-NOV-10:53 | 68304.00 | 6830.51 | 3251.45 | 0.00 | 0.00 | 0.00 | 0.00 | 50.62 | 0.00 |
December | 23019.73 | 19-DEC-12:30 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9937.98 | 3415.20 | 711.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24371.24 | 68304.00 | 6830.51 | 3251.45 | 0.00 | 0.00 | 0.00 | 0.00 | 293.06 | 116.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41717.85 | 14-JAN-12:40 | 15207.66 | 4576.38 | 3694.97 | 0.00 | 0.00 | 0.00 | 0.00 | 96.65 | 0.00 |
February | 37589.91 | 02-FEB-19:05 | 212907.24 | 87866.59 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 765.57 |
March | 37953.58 | 23-MAR-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752.93 |
April | 39142.14 | 26-APR-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.44 |
May | 39773.80 | 04-MAY-20:05 | 81107.52 | 29288.86 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.27 |
June | 39216.69 | 27-JUN-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.94 |
July | 41273.35 | 19-JUL-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.57 |
August | 41652.60 | 18-AUG-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.32 |
September | 46010.34 | 29-SEP-20:10 | 40553.76 | 14644.43 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 67.38 | 0.00 |
October | 47072.80 | 15-OCT-12:00 | 15207.66 | 5491.66 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 567.21 | 0.00 |
November | 46047.38 | 19-NOV-10:53 | 202768.80 | 43933.30 | 33782.60 | 0.00 | 0.00 | 0.00 | 0.00 | 144.63 | 0.00 |
December | 41186.55 | 16-DEC-13:00 | 15207.66 | 4576.38 | 3694.97 | 0.00 | 0.00 | 0.00 | 0.00 | 145.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 37589.91 | 15207.66 | 4576.38 | 3694.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47072.80 | 212907.24 | 87866.59 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 567.21 | 765.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4805.38 | 02-JAN-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.91 |
February | 4840.75 | 20-FEB-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.43 |
March | 4869.54 | 11-MAR-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 |
April | 4766.14 | 16-APR-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.74 |
May | 4917.89 | 26-MAY-18:01 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.89 |
June | 4607.34 | 03-JUN-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.88 |
July | 4656.65 | 09-JUL-15:11 | 378.00 | 1106.11 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 |
August | 4635.67 | 29-AUG-15:11 | 680.40 | 938.51 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
September | 4691.41 | 19-SEP-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 |
October | 4850.50 | 12-OCT-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 |
November | 4866.97 | 04-NOV-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 |
December | 4785.57 | 31-DEC-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4607.34 | 324.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | |
Maximum of Months | 4917.89 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4599.91 | 14-JAN-21:01 | 1108.80 | 3830.22 | 1453.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.23 |
February | 5006.86 | 22-FEB-17:01 | 972.00 | 1340.58 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.99 |
March | 4775.55 | 11-MAR-18:21 | 680.40 | 2848.72 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.72 |
April | 5081.78 | 18-APR-16:51 | 777.60 | 1072.46 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 |
May | 4943.85 | 26-MAY-18:01 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.85 |
June | 4947.86 | 30-JUN-17:32 | 583.20 | 1924.68 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.34 |
July | 4800.71 | 15-JUL-17:52 | 583.20 | 2441.76 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.65 |
August | 4323.83 | 19-AUG-15:12 | 324.00 | 947.98 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 19.65 | 0.00 |
September | 4683.53 | 30-SEP-08:61 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 0.00 |
October | 4870.58 | 15-OCT-21:51 | 1386.00 | 4069.61 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.02 |
November | 4770.72 | 04-NOV-17:01 | 680.40 | 2848.72 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.55 |
December | 4639.47 | 05-DEC-22:51 | 1620.00 | 2887.03 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4323.83 | 324.00 | 947.98 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5081.78 | 1620.00 | 4261.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 19.65 | 78.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1122.63 | 14-JAN-12:20 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 |
February | 956.75 | 02-FEB-12:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 |
March | 838.34 | 11-MAR-12:50 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
April | 612.58 | 08-APR-12:30 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 |
May | 441.95 | 04-MAY-12:00 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 |
June | 295.27 | 27-JUN-12:40 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
July | 463.29 | 31-JUL-12:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 | 0.00 |
August | 565.42 | 30-AUG-12:30 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 |
September | 1045.64 | 29-SEP-12:10 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 0.00 |
October | 1209.05 | 16-OCT-12:10 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 16.10 | 0.00 |
November | 1162.69 | 19-NOV-12:30 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
December | 1176.19 | 19-DEC-12:20 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 295.27 | 0.00 | 84.26 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1209.05 | 0.00 | 99.31 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 13.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1393.28 | 14-JAN-21:01 | 1108.80 | 2408.09 | 1424.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 |
February | 1385.74 | 04-FEB-19:02 | 702.00 | 1806.06 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.29 |
March | 1410.08 | 10-MAR-19:11 | 1108.80 | 2143.20 | 949.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.48 |
April | 1378.99 | 01-APR-21:51 | 1108.80 | 2046.87 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 |
May | 1450.16 | 26-MAY-18:01 | 1386.00 | 2679.00 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
June | 1316.35 | 12-JUN-19:31 | 1386.00 | 3010.11 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 |
July | 1240.75 | 04-JUL-08:51 | 540.00 | 1685.66 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
August | 1195.96 | 22-AUG-08:51 | 360.00 | 1324.45 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 |
September | 1343.45 | 30-SEP-08:61 | 540.00 | 1685.66 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 0.00 |
October | 1415.91 | 12-OCT-21:11 | 1440.00 | 1613.42 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 |
November | 1392.07 | 28-NOV-19:01 | 970.20 | 1875.30 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
December | 1428.43 | 06-DEC-22:01 | 1620.00 | 1815.09 | 789.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1195.96 | 360.00 | 1324.45 | 701.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1450.16 | 1620.00 | 3010.11 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 21.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4282.13 | 08-JAN-09:02 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.95 |
February | 4215.91 | 08-FEB-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.61 |
March | 4286.90 | 11-MAR-09:02 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.40 |
April | 4196.54 | 02-APR-08:62 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.18 |
May | 4180.90 | 24-MAY-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 |
June | 3964.24 | 23-JUN-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.89 |
July | 3952.22 | 04-JUL-08:62 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 |
August | 3866.77 | 23-AUG-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 |
September | 4223.20 | 30-SEP-08:61 | 540.00 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 0.00 |
October | 4271.08 | 30-OCT-08:62 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.98 |
November | 4283.26 | 08-NOV-09:02 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.41 |
December | 4277.89 | 23-DEC-09:02 | 324.00 | 1608.88 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3866.77 | 216.00 | 1264.12 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4286.90 | 540.00 | 2681.47 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 82.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4223.32 | 24-JAN-09:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 |
February | 4201.93 | 01-FEB-09:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 |
March | 4316.25 | 10-MAR-09:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.68 |
April | 4365.47 | 03-APR-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.09 |
May | 4391.67 | 27-MAY-08:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.56 |
June | 4238.18 | 13-JUN-08:32 | 180.00 | 1053.31 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.42 |
July | 4140.99 | 04-JUL-08:22 | 270.00 | 1340.58 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.90 |
August | 4070.04 | 22-AUG-08:32 | 180.00 | 1053.31 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.12 |
September | 4325.60 | 30-SEP-07:42 | 572.40 | 1608.69 | 1422.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 |
October | 4320.61 | 12-OCT-08:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.39 |
November | 4264.70 | 08-NOV-09:51 | 360.00 | 2106.62 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.56 |
December | 4300.62 | 16-DEC-09:51 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4070.04 | 180.00 | 1053.31 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 | |
Maximum of Months | 4391.67 | 572.40 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3313.34 | 14-JAN-13:20 | 754.45 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 | 0.00 |
February | 2863.02 | 01-FEB-12:10 | 502.97 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.04 | 0.00 |
March | 2919.26 | 11-MAR-13:20 | 754.45 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
April | 2472.64 | 26-APR-18:03 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.24 |
May | 2376.07 | 04-MAY-18:03 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.92 |
June | 2757.74 | 29-JUN-18:03 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 |
July | 2752.20 | 19-JUL-18:20 | 1760.39 | 1676.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.91 |
August | 2697.62 | 18-AUG-15:10 | 1257.42 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 | 0.00 |
September | 4035.29 | 29-SEP-13:00 | 502.97 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.63 | 0.00 |
October | 4340.91 | 16-OCT-12:30 | 502.97 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.77 | 0.00 |
November | 3736.54 | 19-NOV-13:00 | 754.45 | 628.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 0.00 |
December | 3471.58 | 19-DEC-13:00 | 502.97 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2376.07 | 502.97 | 523.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4340.91 | 10562.33 | 10059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.63 | 44.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5077.83 | 05-JAN-16:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.77 |
February | 5118.06 | 20-FEB-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.16 |
March | 5176.01 | 11-MAR-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 |
April | 5057.34 | 16-APR-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 |
May | 5216.07 | 26-MAY-18:01 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 |
June | 4907.53 | 03-JUN-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.89 |
July | 5013.45 | 09-JUL-15:11 | 378.00 | 1106.11 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 |
August | 4949.19 | 29-AUG-15:11 | 680.40 | 938.51 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
September | 4982.34 | 19-SEP-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 |
October | 5147.91 | 12-OCT-15:12 | 583.20 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
November | 5153.02 | 04-NOV-15:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.36 |
December | 5068.84 | 31-DEC-16:12 | 324.00 | 948.09 | 331.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4907.53 | 324.00 | 804.44 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | |
Maximum of Months | 5216.07 | 1386.00 | 4261.62 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4833.95 | 07-JAN-16:12 | 324.00 | 947.98 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.57 |
February | 5305.56 | 22-FEB-17:01 | 972.00 | 1340.58 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.99 |
March | 5056.90 | 11-MAR-18:21 | 680.40 | 2848.72 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.55 |
April | 5270.19 | 18-APR-16:51 | 777.60 | 1072.46 | 1011.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.04 |
May | 5293.09 | 26-MAY-18:01 | 1386.00 | 4261.12 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.19 |
June | 5293.89 | 30-JUN-17:32 | 583.20 | 1924.68 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.82 |
July | 5142.72 | 15-JUL-17:52 | 583.20 | 2441.76 | 758.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.15 |
August | 4632.09 | 19-AUG-15:12 | 324.00 | 947.98 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 | 0.00 |
September | 4911.05 | 30-SEP-08:61 | 540.00 | 2681.15 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 0.00 |
October | 5146.66 | 15-OCT-21:51 | 1386.00 | 4069.61 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.43 |
November | 5033.39 | 04-NOV-17:01 | 680.40 | 2848.72 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.15 |
December | 4892.95 | 31-DEC-17:01 | 667.80 | 1105.98 | 737.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4632.09 | 324.00 | 947.98 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5305.56 | 1386.00 | 4261.12 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 | 78.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2657.14 | 02-JAN-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.74 |
February | 2624.23 | 06-FEB-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 |
March | 2638.08 | 07-MAR-16:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 |
April | 2568.97 | 01-APR-15:12 | 324.00 | 596.00 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 |
May | 2601.18 | 26-MAY-18:01 | 1386.00 | 2679.00 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 |
June | 2406.95 | 12-JUN-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 |
July | 2393.75 | 09-JUL-15:11 | 378.00 | 695.33 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 |
August | 2418.83 | 29-AUG-15:11 | 680.40 | 589.98 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
September | 2482.97 | 19-SEP-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 |
October | 2617.78 | 12-OCT-15:12 | 583.20 | 505.70 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 |
November | 2712.65 | 19-NOV-10:54 | 432.00 | 987.32 | 268.38 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 0.00 |
December | 2657.00 | 23-DEC-09:02 | 324.00 | 1011.40 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2393.75 | 324.00 | 505.70 | 268.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2712.65 | 1386.00 | 2679.00 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 39.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19727.19 | 18-JAN-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.40 |
February | 18837.67 | 17-FEB-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.34 |
March | 19427.89 | 24-MAR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.92 |
April | 20785.69 | 26-APR-21:52 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.16 |
May | 21259.71 | 04-MAY-21:10 | 53977.54 | 5997.48 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.89 |
June | 21549.82 | 27-JUN-21:52 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.73 |
July | 21685.99 | 19-JUL-21:52 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.68 |
August | 21578.25 | 02-AUG-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.00 |
September | 22275.80 | 29-SEP-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 0.00 |
October | 21807.11 | 04-OCT-21:52 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.19 |
November | 19247.90 | 10-NOV-22:12 | 215910.14 | 23989.91 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.75 |
December | 19753.70 | 05-DEC-22:52 | 242898.91 | 26988.65 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18837.67 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22275.80 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 187.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21067.80 | 18-JAN-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.40 |
February | 20197.90 | 17-FEB-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.34 |
March | 20702.63 | 24-MAR-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.92 |
April | 21954.91 | 26-APR-21:52 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.16 |
May | 22444.21 | 04-MAY-21:10 | 53977.54 | 5997.48 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.89 |
June | 22753.87 | 29-JUN-18:02 | 125947.58 | 23989.91 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 |
July | 22852.65 | 18-JUL-18:03 | 125947.58 | 23989.91 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 |
August | 22795.18 | 02-AUG-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.00 |
September | 23459.44 | 29-SEP-21:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 0.00 |
October | 23028.77 | 04-OCT-21:52 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.19 |
November | 20579.86 | 10-NOV-22:10 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.68 |
December | 21025.98 | 05-DEC-22:52 | 242898.91 | 26988.65 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20197.90 | 26988.77 | 2998.74 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23459.44 | 269887.68 | 29987.39 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 187.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29437.74 | 14-JAN-11:50 | 800.57 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 27.60 | 0.00 |
February | 29197.78 | 01-FEB-11:35 | 1067.42 | 667.18 | 30056.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 13.07 | 0.00 |
March | 30495.76 | 23-MAR-10:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 31.10 |
April | 30992.42 | 30-APR-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 22.74 | 0.00 |
May | 30563.48 | 02-MAY-10:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.94 |
June | 30396.82 | 25-JUN-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 |
July | 31086.85 | 30-JUL-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 8.15 | 0.00 |
August | 31285.82 | 15-AUG-10:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 41.91 | 0.00 |
September | 32626.15 | 29-SEP-10:40 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 162.43 | 0.00 |
October | 32278.12 | 15-OCT-10:40 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 107.95 | 0.00 |
November | 29878.10 | 19-NOV-11:50 | 800.57 | 400.31 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 27.52 | 0.00 |
December | 29337.93 | 19-DEC-11:50 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 13.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29197.78 | 533.71 | 333.59 | 15028.36 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32626.15 | 1067.42 | 667.18 | 30056.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 162.43 | 35.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8654.33 | 18-JAN-13:30 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 | 0.00 |
February | 7328.16 | 01-FEB-12:20 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.51 | 0.00 |
March | 8237.99 | 11-MAR-12:50 | 798.48 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
April | 8439.91 | 26-APR-13:00 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 0.00 |
May | 8047.84 | 04-MAY-12:00 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 |
June | 7207.79 | 27-JUN-12:50 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 |
July | 8288.94 | 31-JUL-12:30 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.93 | 0.00 |
August | 8449.39 | 18-AUG-12:20 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.13 | 0.00 |
September | 11614.73 | 29-SEP-12:50 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.13 | 0.00 |
October | 11613.88 | 15-OCT-11:50 | 798.48 | 665.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.13 | 0.00 |
November | 9290.38 | 19-NOV-13:00 | 798.48 | 665.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.01 | 0.00 |
December | 9173.69 | 19-DEC-12:30 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 7207.79 | 532.32 | 554.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11614.73 | 798.48 | 665.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.13 | 1.50 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.514823E+12 | 324950.91 | 17-JAN-20:10 | 0.423392E+12 | 364158.14 | 02-JAN-20:00 |
February | 0.451024E+12 | 308949.88 | 13-FEB-19:19 | 0.364925E+12 | 341555.52 | 26-FEB-20:00 |
March | 0.495221E+12 | 323207.61 | 23-MAR-19:30 | 0.417117E+12 | 369942.91 | 07-MAR-18:00 |
April | 0.503994E+12 | 327894.49 | 11-APR-19:30 | 0.368530E+12 | 330062.42 | 04-APR-17:30 |
May | 0.515136E+12 | 329745.65 | 24-MAY-19:30 | 0.376518E+12 | 326998.92 | 01-MAY-17:00 |
June | 0.533383E+12 | 359728.39 | 30-JUN-18:10 | 0.355818E+12 | 321403.71 | 06-JUN-17:49 |
July | 0.603178E+12 | 408320.36 | 18-JUL-18:10 | 0.364900E+12 | 319196.74 | 03-JUL-17:30 |
August | 0.616943E+12 | 367650.80 | 14-AUG-19:10 | 0.364945E+12 | 318442.65 | 31-AUG-17:49 |
September | 0.566322E+12 | 411750.79 | 29-SEP-19:10 | 0.354943E+12 | 320798.40 | 28-SEP-17:49 |
October | 0.591549E+12 | 410315.97 | 04-OCT-20:30 | 0.372286E+12 | 325174.47 | 31-OCT-17:49 |
November | 0.503567E+12 | 325176.63 | 19-NOV-09:00 | 0.378960E+12 | 334478.44 | 04-NOV-19:00 |
December | 0.518941E+12 | 319209.96 | 05-DEC-19:10 | 0.414833E+12 | 366710.56 | 12-DEC-21:00 |
Annual Sum or Average | 0.641408E+13 | 0.455717E+13 | ||||
Minimum of Months | 0.451024E+12 | 308949.88 | 0.354943E+12 | 318442.65 | ||
Maximum of Months | 0.616943E+12 | 411750.79 | 0.423392E+12 | 369942.91 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.129696E+12 | 0.317632E+11 | 0.141138E+12 | 0.715096E+11 | 0.871896E+11 | 0.291017E+09 | 0.00 | 0.494937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117116E+12 | 0.271500E+11 | 0.127470E+12 | 0.645894E+11 | 0.778263E+11 | 0.192019E+09 | 0.00 | 0.332976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129400E+12 | 0.278266E+11 | 0.141191E+12 | 0.715122E+11 | 0.856450E+11 | 0.269174E+09 | 0.00 | 0.356220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125475E+12 | 0.247389E+11 | 0.136545E+12 | 0.692026E+11 | 0.843978E+11 | 0.143520E+09 | 0.00 | 0.598583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129561E+12 | 0.236194E+11 | 0.141170E+12 | 0.715109E+11 | 0.867822E+11 | 0.147173E+09 | 0.00 | 0.585867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125286E+12 | 0.218972E+11 | 0.136635E+12 | 0.692051E+11 | 0.859316E+11 | 0.125079E+09 | 0.00 | 0.906509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129759E+12 | 0.230536E+11 | 0.141079E+12 | 0.715085E+11 | 0.908204E+11 | 0.128356E+09 | 0.00 | 0.143063E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129426E+12 | 0.246897E+11 | 0.141202E+12 | 0.715122E+11 | 0.914328E+11 | 0.128346E+09 | 0.00 | 0.154767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125517E+12 | 0.259937E+11 | 0.136555E+12 | 0.692027E+11 | 0.874617E+11 | 0.124746E+09 | 0.00 | 0.117810E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129662E+12 | 0.291306E+11 | 0.141127E+12 | 0.715095E+11 | 0.912092E+11 | 0.135993E+09 | 0.00 | 0.125017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125477E+12 | 0.301763E+11 | 0.136629E+12 | 0.692036E+11 | 0.849111E+11 | 0.183484E+09 | 0.00 | 0.533681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129767E+12 | 0.323045E+11 | 0.141079E+12 | 0.715085E+11 | 0.877243E+11 | 0.266663E+09 | 0.00 | 0.525581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152614E+13 | 0.322344E+12 | 0.166182E+13 | 0.841975E+12 | 0.104133E+13 | 0.213557E+10 | 0.00 | 0.974092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117116E+12 | 0.218972E+11 | 0.127470E+12 | 0.645894E+11 | 0.778263E+11 | 0.124746E+09 | 0.00 | 0.332976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129767E+12 | 0.323045E+11 | 0.141202E+12 | 0.715122E+11 | 0.914328E+11 | 0.291017E+09 | 0.00 | 0.154767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.435064E+11 | 0.00 | 0.227968E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.216331E+11 | 0.00 | 0.206089E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.386524E+11 | 0.00 | 0.226441E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.573805E+10 | 0.00 | 0.215837E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.556411E+10 | 0.00 | 0.218975E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.288167E+09 | 0.00 | 0.208416E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 13630136.31 | 0.00 | 0.213066E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 10264737.42 | 0.00 | 0.212896E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.181137E+09 | 0.00 | 0.207791E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.229985E+10 | 0.00 | 0.218083E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.169018E+11 | 0.00 | 0.214967E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.372508E+11 | 0.00 | 0.225761E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.172040E+12 | 0.00 | 0.259629E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 10264737.42 | 0.00 | 0.206089E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.435064E+11 | 0.00 | 0.227968E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 121238.68 | 02-JAN-20:10 | 20502.98 | 01-JAN-00:10 | 89286.95 | 02-JAN-07:10 | 50420.89 | 02-JAN-07:19 | 39916.74 | 22-JAN-10:50 | 560.71 | 08-JAN-06:49 | 0.00 | 01-JAN-00:10 |
February | 121238.68 | 01-FEB-20:10 | 20502.98 | 01-FEB-00:10 | 89286.95 | 01-FEB-07:10 | 50420.89 | 01-FEB-07:19 | 39059.58 | 01-FEB-13:09 | 421.91 | 05-FEB-05:00 | 0.00 | 01-FEB-00:10 |
March | 121238.68 | 01-MAR-20:10 | 20502.98 | 01-MAR-00:10 | 89286.95 | 01-MAR-07:10 | 50420.89 | 01-MAR-07:19 | 39650.22 | 11-MAR-13:09 | 498.30 | 30-MAR-02:00 | 0.00 | 01-MAR-00:10 |
April | 121238.68 | 03-APR-19:10 | 20502.98 | 01-APR-00:10 | 89286.95 | 03-APR-06:10 | 50420.89 | 03-APR-06:19 | 40053.52 | 26-APR-20:10 | 336.18 | 01-APR-05:00 | 0.00 | 01-APR-00:10 |
May | 121238.68 | 01-MAY-19:10 | 20502.98 | 01-MAY-00:10 | 89286.95 | 01-MAY-06:10 | 50420.89 | 01-MAY-06:19 | 40475.48 | 04-MAY-21:10 | 272.96 | 14-MAY-04:49 | 0.00 | 01-MAY-00:10 |
June | 121238.68 | 01-JUN-19:10 | 20502.98 | 01-JUN-00:10 | 89286.95 | 01-JUN-06:10 | 50420.89 | 01-JUN-06:19 | 41350.18 | 29-JUN-18:10 | 91.41 | 13-JUN-03:00 | 0.00 | 01-JUN-00:10 |
July | 121238.68 | 03-JUL-19:10 | 20502.98 | 01-JUL-00:10 | 89286.95 | 03-JUL-06:10 | 50420.89 | 03-JUL-06:19 | 43171.70 | 18-JUL-18:10 | 53.76 | 12-JUL-08:09 | 0.00 | 01-JUL-00:10 |
August | 121238.68 | 01-AUG-19:10 | 20502.98 | 01-AUG-00:10 | 89286.95 | 01-AUG-06:10 | 50420.89 | 01-AUG-06:19 | 42231.34 | 18-AUG-20:10 | 51.79 | 22-AUG-08:09 | 0.00 | 01-AUG-00:10 |
September | 121238.68 | 01-SEP-19:10 | 20502.98 | 01-SEP-00:10 | 89286.95 | 01-SEP-06:10 | 50420.89 | 01-SEP-06:19 | 44612.31 | 29-SEP-19:10 | 89.82 | 20-SEP-03:00 | 0.00 | 01-SEP-00:10 |
October | 121238.68 | 02-OCT-19:10 | 20502.98 | 01-OCT-00:10 | 89286.95 | 02-OCT-06:10 | 50420.89 | 02-OCT-06:19 | 44497.65 | 15-OCT-09:30 | 188.12 | 28-OCT-04:00 | 0.00 | 01-OCT-00:10 |
November | 121238.68 | 01-NOV-19:10 | 20502.98 | 01-NOV-00:10 | 89286.95 | 01-NOV-06:10 | 50420.89 | 01-NOV-06:19 | 42495.82 | 19-NOV-09:00 | 352.83 | 05-NOV-04:00 | 0.00 | 01-NOV-00:10 |
December | 121238.68 | 01-DEC-20:10 | 20502.98 | 01-DEC-00:10 | 89286.95 | 01-DEC-07:10 | 50420.89 | 01-DEC-07:19 | 39874.33 | 05-DEC-22:10 | 469.48 | 13-DEC-04:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 121238.68 | 20502.98 | 89286.95 | 50420.89 | 39059.58 | 51.79 | 0.00 | |||||||
Maximum of Months | 121238.68 | 20502.98 | 89286.95 | 50420.89 | 44612.31 | 560.71 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 102244.88 | 14-JAN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98697.98 | 01-FEB-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96512.75 | 11-MAR-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97053.14 | 26-APR-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79717.85 | 03-MAY-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 107848.69 | 29-JUN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 149241.35 | 18-JUL-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 142404.54 | 17-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 173981.36 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 177411.47 | 16-OCT-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 128662.39 | 19-NOV-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 117862.65 | 05-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 79717.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 177411.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 324950.91 | 17-JAN-20:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 36373.88 | 47.91 | 0.00 | 47034.66 | 0.00 |
February | 308949.88 | 13-FEB-19:19 | 107831.13 | 77688.87 | 20502.98 | 29030.08 | 33919.69 | 49.45 | 0.00 | 38234.42 | 0.00 |
March | 323207.61 | 23-MAR-19:30 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 37625.35 | 47.91 | 0.00 | 43681.85 | 0.00 |
April | 327894.49 | 11-APR-19:30 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 37666.23 | 47.91 | 0.00 | 48664.89 | 0.00 |
May | 329745.65 | 24-MAY-19:30 | 121238.68 | 86555.31 | 20502.98 | 11871.54 | 37862.39 | 47.91 | 0.00 | 49986.35 | 0.00 |
June | 359728.39 | 30-JUN-18:10 | 107831.13 | 77688.87 | 0.00 | 29010.56 | 40552.69 | 47.91 | 0.00 | 103267.48 | 0.00 |
July | 408320.36 | 18-JUL-18:10 | 107831.13 | 77688.87 | 0.00 | 29010.56 | 43171.70 | 47.91 | 0.00 | 149241.35 | 0.00 |
August | 367650.80 | 14-AUG-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 41717.20 | 47.91 | 0.00 | 84042.72 | 0.00 |
September | 411750.79 | 29-SEP-19:10 | 121238.68 | 86555.31 | 20502.98 | 11860.16 | 44612.31 | 47.91 | 0.00 | 125594.17 | 0.00 |
October | 410315.97 | 04-OCT-20:30 | 107831.13 | 88334.05 | 20502.98 | 11903.47 | 43451.24 | 47.91 | 0.00 | 136722.34 | 0.00 |
November | 325176.63 | 19-NOV-09:00 | 53349.88 | 70483.19 | 0.00 | 28853.88 | 42495.82 | 47.91 | 0.00 | 128662.39 | 0.00 |
December | 319209.96 | 05-DEC-19:10 | 107831.13 | 77688.87 | 20502.98 | 29010.56 | 37866.81 | 48.27 | 0.00 | 44956.93 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 308949.88 | 53349.88 | 70483.19 | 0.00 | 11860.16 | 33919.69 | 47.91 | 0.00 | 38234.42 | 0.00 | |
Maximum of Months | 411750.79 | 121238.68 | 88334.05 | 20502.98 | 29030.08 | 44612.31 | 49.45 | 0.00 | 149241.35 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 142407.59 | 08-JAN-06:49 | 0.00 | 231771.32 | 23-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 98976.77 | 05-FEB-05:00 | 0.00 | 231995.64 | 09-FEB-21:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 121346.78 | 30-MAR-02:00 | 0.00 | 230707.31 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 78255.57 | 01-APR-05:40 | 0.00 | 228850.10 | 05-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 61636.01 | 14-MAY-04:49 | 0.00 | 223802.80 | 02-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 14089.64 | 13-JUN-03:00 | 0.00 | 220299.52 | 01-JUN-20:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 1889.81 | 12-JUL-08:09 | 0.00 | 217706.32 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 1241.54 | 22-AUG-08:09 | 0.00 | 217232.26 | 31-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 13218.47 | 20-SEP-03:00 | 0.00 | 219161.59 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 42263.26 | 12-OCT-04:00 | 0.00 | 222713.15 | 31-OCT-20:30 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 79510.55 | 05-NOV-04:00 | 0.00 | 227703.46 | 28-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 110593.24 | 13-DEC-04:30 | 0.00 | 230558.36 | 26-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 1241.54 | 0.00 | 217232.26 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 142407.59 | 0.00 | 231995.64 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.89 | 0.33 | 21.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.79 | 1.00 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.89 | 0.67 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.75 | 2.67 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.77 | 3.83 | 21.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.88 | 6.33 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 21.96 | 10.50 | 21.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 21.94 | 9.17 | 21.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.75 | 3.83 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.87 | 2.17 | 21.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 39.33 | 21.88 | 39.33 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 21.96 | 10.50 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.89 | 1.00 | 21.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.85 | 2.67 | 21.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.89 | 5.83 | 21.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 22.19 | 12.33 | 22.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 22.37 | 23.17 | 22.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 22.30 | 21.33 | 22.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 22.09 | 10.67 | 22.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 22.25 | 11.00 | 22.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
Annual Sum or Average | 0.00 | 0.00 | 89.67 | 22.22 | 89.67 | 22.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 22.37 | 23.17 | 22.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.96 | 1.17 | 21.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.85 | 0.83 | 21.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.18 | 0.50 | 22.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 22.32 | 1.83 | 22.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.18 | 3.50 | 22.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 22.42 | 6.50 | 22.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 22.41 | 15.83 | 22.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 22.53 | 15.17 | 22.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 22.26 | 5.50 | 22.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 21.99 | 5.83 | 21.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.94 | 1.83 | 21.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.93 | 2.17 | 21.93 |
Annual Sum or Average | 0.00 | 0.00 | 60.67 | 22.32 | 60.67 | 22.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.85 | 0.50 | 21.85 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 22.53 | 15.83 | 22.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.93 | 0.33 | 21.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 21.81 | 0.83 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.93 | 0.50 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.77 | 3.00 | 21.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.79 | 3.83 | 21.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 21.89 | 6.33 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 21.96 | 10.67 | 21.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 21.94 | 8.83 | 21.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.73 | 3.67 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.85 | 1.50 | 21.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 38.83 | 21.88 | 38.83 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 21.96 | 10.67 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.88 | 0.33 | 21.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.90 | 0.67 | 21.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.89 | 1.00 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.90 | 0.67 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 205.83 | 23.92 | 53.33 | 23.94 | 0.00 | 23.94 |
February | 153.33 | 23.95 | 60.17 | 23.96 | 0.00 | 23.96 |
March | 166.67 | 23.71 | 66.00 | 23.79 | 0.00 | 23.79 |
April | 42.17 | 23.94 | 146.67 | 23.99 | 0.00 | 23.99 |
May | 27.33 | 23.93 | 72.83 | 23.98 | 0.00 | 23.98 |
June | 16.33 | 24.00 | 284.50 | 24.00 | 11.67 | 24.00 |
July | 73.17 | 24.00 | 582.33 | 24.00 | 73.17 | 24.00 |
August | 74.00 | 24.00 | 681.50 | 24.00 | 74.00 | 24.00 |
September | 15.17 | 24.00 | 474.17 | 24.00 | 11.67 | 24.00 |
October | 135.67 | 24.00 | 225.00 | 24.00 | 2.50 | 24.00 |
November | 134.83 | 24.00 | 116.67 | 24.00 | 0.00 | 24.00 |
December | 311.50 | 23.98 | 43.00 | 23.99 | 0.00 | 23.99 |
Annual Sum or Average | 1356.00 | 23.94 | 2806.17 | 23.98 | 173.00 | 23.98 |
Minimum of Months | 15.17 | 23.71 | 43.00 | 23.79 | 0.00 | 23.79 |
Maximum of Months | 311.50 | 24.00 | 681.50 | 24.00 | 74.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 507.00 | 21.62 | 224.67 | 22.23 | 28.33 | 22.19 |
February | 500.50 | 21.53 | 156.50 | 22.05 | 15.67 | 22.02 |
March | 573.83 | 21.49 | 155.83 | 21.97 | 13.33 | 21.95 |
April | 465.00 | 21.62 | 206.67 | 22.34 | 1.33 | 22.34 |
May | 543.83 | 21.68 | 135.83 | 22.12 | 0.00 | 22.12 |
June | 453.50 | 21.85 | 198.33 | 22.47 | 0.00 | 22.47 |
July | 361.50 | 22.00 | 330.00 | 22.91 | 0.00 | 22.91 |
August | 334.50 | 22.03 | 363.83 | 23.02 | 0.00 | 23.02 |
September | 362.67 | 21.90 | 298.17 | 22.82 | 0.00 | 22.82 |
October | 396.83 | 22.00 | 276.83 | 22.80 | 5.00 | 22.81 |
November | 482.17 | 21.75 | 214.00 | 22.38 | 13.50 | 22.36 |
December | 508.67 | 21.67 | 224.33 | 22.27 | 26.50 | 22.23 |
Annual Sum or Average | 5490.00 | 21.74 | 2785.00 | 22.44 | 103.67 | 22.43 |
Minimum of Months | 334.50 | 21.49 | 135.83 | 21.97 | 0.00 | 21.95 |
Maximum of Months | 573.83 | 22.03 | 363.83 | 23.02 | 28.33 | 23.02 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 521.33 | 22.90 | 44.83 | 22.99 | 0.00 | 22.99 |
February | 494.50 | 22.81 | 49.50 | 22.92 | 0.00 | 22.92 |
March | 552.33 | 22.69 | 70.17 | 22.83 | 0.00 | 22.83 |
April | 411.17 | 22.91 | 171.83 | 23.22 | 0.00 | 23.22 |
May | 473.83 | 22.89 | 134.83 | 23.13 | 0.00 | 23.13 |
June | 310.17 | 23.00 | 225.33 | 23.39 | 0.17 | 23.39 |
July | 93.83 | 23.16 | 401.00 | 23.71 | 6.83 | 23.70 |
August | 32.67 | 23.21 | 490.17 | 23.77 | 8.17 | 23.77 |
September | 143.50 | 23.10 | 327.17 | 23.65 | 1.17 | 23.65 |
October | 282.83 | 23.17 | 241.33 | 23.49 | 0.00 | 23.49 |
November | 469.00 | 23.07 | 81.83 | 23.20 | 0.00 | 23.20 |
December | 566.67 | 23.06 | 32.83 | 23.11 | 0.00 | 23.11 |
Annual Sum or Average | 4351.83 | 22.94 | 2270.83 | 23.26 | 16.33 | 23.26 |
Minimum of Months | 32.67 | 22.69 | 32.83 | 22.83 | 0.00 | 22.83 |
Maximum of Months | 566.67 | 23.21 | 490.17 | 23.77 | 8.17 | 23.77 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 625.50 | 23.09 | 11.17 | 23.10 | 0.00 | 23.10 |
February | 579.50 | 23.11 | 4.33 | 23.12 | 0.00 | 23.12 |
March | 624.67 | 22.99 | 9.33 | 23.01 | 0.00 | 23.01 |
April | 454.00 | 23.25 | 54.67 | 23.33 | 0.00 | 23.33 |
May | 475.33 | 23.34 | 40.83 | 23.39 | 0.00 | 23.39 |
June | 149.00 | 23.40 | 200.50 | 23.74 | 0.00 | 23.74 |
July | 19.67 | 23.44 | 466.33 | 23.95 | 0.00 | 23.95 |
August | 6.33 | 23.45 | 550.17 | 23.97 | 0.00 | 23.97 |
September | 92.17 | 23.43 | 263.17 | 23.83 | 0.00 | 23.83 |
October | 295.83 | 23.55 | 177.83 | 23.71 | 0.00 | 23.71 |
November | 571.67 | 23.31 | 23.17 | 23.34 | 0.00 | 23.34 |
December | 666.50 | 23.23 | 4.17 | 23.23 | 0.00 | 23.23 |
Annual Sum or Average | 4560.17 | 23.22 | 1805.67 | 23.43 | 0.00 | 23.43 |
Minimum of Months | 6.33 | 22.99 | 4.17 | 23.01 | 0.00 | 23.01 |
Maximum of Months | 666.50 | 23.55 | 550.17 | 23.97 | 0.00 | 23.97 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
February | 672.00 | 21.84 | 0.00 | 21.84 | 0.00 | 21.84 |
March | 744.00 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
April | 720.00 | 22.29 | 0.00 | 22.29 | 0.00 | 22.29 |
May | 741.83 | 22.41 | 0.00 | 22.41 | 0.00 | 22.41 |
June | 666.33 | 22.80 | 2.83 | 22.81 | 0.00 | 22.81 |
July | 505.83 | 22.96 | 37.67 | 23.02 | 0.00 | 23.02 |
August | 513.83 | 22.94 | 28.50 | 22.98 | 0.00 | 22.98 |
September | 681.67 | 22.78 | 3.83 | 22.79 | 0.00 | 22.79 |
October | 672.50 | 22.72 | 2.50 | 22.72 | 0.00 | 22.72 |
November | 720.00 | 22.10 | 0.00 | 22.10 | 0.00 | 22.10 |
December | 744.00 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
Annual Sum or Average | 8126.00 | 22.33 | 75.33 | 22.34 | 0.00 | 22.34 |
Minimum of Months | 505.83 | 21.79 | 0.00 | 21.79 | 0.00 | 21.79 |
Maximum of Months | 744.00 | 22.96 | 37.67 | 23.02 | 0.00 | 23.02 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 294.17 | 24.00 | 744.00 | 24.00 | 294.17 | 24.00 |
February | 298.17 | 24.00 | 672.00 | 24.00 | 298.17 | 24.00 |
March | 385.33 | 24.00 | 744.00 | 24.00 | 385.33 | 24.00 |
April | 446.33 | 24.00 | 720.00 | 24.00 | 446.33 | 24.00 |
May | 450.67 | 24.00 | 744.00 | 24.00 | 450.67 | 24.00 |
June | 538.67 | 24.00 | 720.00 | 24.00 | 538.67 | 24.00 |
July | 626.33 | 24.00 | 744.00 | 24.00 | 626.33 | 24.00 |
August | 657.00 | 24.00 | 744.00 | 24.00 | 657.00 | 24.00 |
September | 564.17 | 24.00 | 720.00 | 24.00 | 564.17 | 24.00 |
October | 450.17 | 24.00 | 744.00 | 24.00 | 450.17 | 24.00 |
November | 328.17 | 24.00 | 720.00 | 24.00 | 328.17 | 24.00 |
December | 254.50 | 24.00 | 744.00 | 24.00 | 254.50 | 24.00 |
Annual Sum or Average | 5293.67 | 24.00 | 8760.00 | 24.00 | 5293.67 | 24.00 |
Minimum of Months | 254.50 | 24.00 | 672.00 | 24.00 | 254.50 | 24.00 |
Maximum of Months | 657.00 | 24.00 | 744.00 | 24.00 | 657.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 308.83 | 22.39 | 345.17 | 23.23 | 29.33 | 23.27 |
February | 268.83 | 22.58 | 301.50 | 23.32 | 19.00 | 23.34 |
March | 343.67 | 22.20 | 327.33 | 23.07 | 4.33 | 23.08 |
April | 155.67 | 23.02 | 498.83 | 23.76 | 21.83 | 23.77 |
May | 157.33 | 23.08 | 494.83 | 23.78 | 16.50 | 23.78 |
June | 97.83 | 23.92 | 681.33 | 23.99 | 84.50 | 23.99 |
July | 291.67 | 24.00 | 744.00 | 24.00 | 291.67 | 24.00 |
August | 388.00 | 24.00 | 744.00 | 24.00 | 388.00 | 24.00 |
September | 204.17 | 23.97 | 693.00 | 23.99 | 194.50 | 23.99 |
October | 258.17 | 23.80 | 559.67 | 23.94 | 173.33 | 23.95 |
November | 230.67 | 23.05 | 404.00 | 23.65 | 33.33 | 23.66 |
December | 334.83 | 22.64 | 289.00 | 23.26 | 12.33 | 23.28 |
Annual Sum or Average | 3039.67 | 23.16 | 6082.67 | 23.72 | 1268.67 | 23.75 |
Minimum of Months | 97.83 | 22.20 | 289.00 | 23.07 | 4.33 | 23.08 |
Maximum of Months | 388.00 | 24.00 | 744.00 | 24.00 | 388.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 273.67 | 23.10 | 232.00 | 23.48 | 6.50 | 23.48 |
February | 303.50 | 22.93 | 188.00 | 23.30 | 3.50 | 23.30 |
March | 363.33 | 22.80 | 197.50 | 23.18 | 0.00 | 23.18 |
April | 168.50 | 23.02 | 344.83 | 23.57 | 6.17 | 23.57 |
May | 277.33 | 22.98 | 232.17 | 23.39 | 2.00 | 23.39 |
June | 105.17 | 23.20 | 424.00 | 23.68 | 35.17 | 23.69 |
July | 135.83 | 23.89 | 655.17 | 23.80 | 135.83 | 23.81 |
August | 179.50 | 23.90 | 728.33 | 23.85 | 179.50 | 23.86 |
September | 64.83 | 23.66 | 629.50 | 23.85 | 50.17 | 23.85 |
October | 145.33 | 23.54 | 456.67 | 23.82 | 54.50 | 23.83 |
November | 182.17 | 23.26 | 280.17 | 23.64 | 3.83 | 23.64 |
December | 278.50 | 23.23 | 163.50 | 23.48 | 0.00 | 23.48 |
Annual Sum or Average | 2477.67 | 23.19 | 4531.83 | 23.62 | 477.17 | 23.64 |
Minimum of Months | 64.83 | 22.80 | 163.50 | 23.18 | 0.00 | 23.18 |
Maximum of Months | 363.33 | 23.90 | 728.33 | 23.85 | 179.50 | 23.86 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 647.67 | 21.47 | 54.00 | 21.52 | 27.83 | 21.51 |
February | 607.33 | 21.47 | 36.50 | 21.53 | 13.83 | 21.52 |
March | 671.83 | 21.47 | 41.00 | 21.53 | 14.00 | 21.51 |
April | 612.00 | 21.48 | 44.50 | 21.60 | 0.00 | 21.60 |
May | 653.00 | 21.53 | 19.00 | 21.58 | 0.00 | 21.58 |
June | 613.00 | 21.51 | 44.00 | 21.63 | 0.00 | 21.63 |
July | 588.50 | 21.40 | 82.00 | 21.63 | 0.00 | 21.63 |
August | 568.17 | 21.33 | 93.00 | 21.61 | 0.17 | 21.61 |
September | 567.17 | 21.37 | 68.00 | 21.58 | 0.00 | 21.58 |
October | 615.17 | 21.46 | 58.33 | 21.62 | 0.17 | 21.62 |
November | 618.33 | 21.47 | 53.83 | 21.58 | 14.17 | 21.57 |
December | 644.83 | 21.47 | 54.83 | 21.51 | 32.83 | 21.49 |
Annual Sum or Average | 7407.00 | 21.45 | 649.00 | 21.58 | 103.00 | 21.57 |
Minimum of Months | 567.17 | 21.33 | 19.00 | 21.51 | 0.00 | 21.49 |
Maximum of Months | 671.83 | 21.53 | 93.00 | 21.63 | 32.83 | 21.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 701.00 | 21.66 | 48.17 | 21.62 | 48.17 | 21.58 |
February | 626.00 | 21.55 | 32.33 | 21.61 | 19.17 | 21.59 |
March | 682.67 | 21.62 | 53.50 | 21.81 | 26.33 | 21.88 |
April | 603.17 | 22.24 | 122.00 | 22.99 | 55.50 | 23.39 |
May | 616.33 | 22.38 | 128.83 | 23.15 | 60.83 | 23.56 |
June | 520.00 | 23.13 | 222.00 | 24.23 | 101.33 | 24.79 |
July | 498.00 | 23.66 | 305.17 | 24.73 | 160.17 | 25.30 |
August | 520.67 | 23.61 | 307.17 | 24.59 | 179.67 | 25.11 |
September | 506.50 | 22.57 | 221.83 | 23.53 | 79.50 | 23.89 |
October | 533.17 | 22.14 | 152.67 | 22.84 | 43.50 | 23.02 |
November | 653.17 | 21.73 | 27.67 | 21.75 | 19.67 | 21.73 |
December | 709.17 | 21.71 | 47.17 | 21.67 | 47.00 | 21.64 |
Annual Sum or Average | 7169.83 | 22.25 | 1668.50 | 22.92 | 840.83 | 23.25 |
Minimum of Months | 498.00 | 21.55 | 27.67 | 21.61 | 19.17 | 21.58 |
Maximum of Months | 709.17 | 23.66 | 307.17 | 24.73 | 179.67 | 25.30 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 737.00 | 21.70 | 4.33 | 21.70 | 3.67 | 21.69 |
February | 672.00 | 21.65 | 5.33 | 21.64 | 5.33 | 21.64 |
March | 743.67 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
April | 696.33 | 21.95 | 11.17 | 21.99 | 0.00 | 21.99 |
May | 702.00 | 22.04 | 9.83 | 22.07 | 0.00 | 22.07 |
June | 559.17 | 22.15 | 109.17 | 22.56 | 6.83 | 22.59 |
July | 582.00 | 22.51 | 212.00 | 23.12 | 82.00 | 23.29 |
August | 627.17 | 22.61 | 205.83 | 23.11 | 121.00 | 23.30 |
September | 634.00 | 22.29 | 67.83 | 22.48 | 31.17 | 22.56 |
October | 690.83 | 22.36 | 59.33 | 22.54 | 42.50 | 22.65 |
November | 719.50 | 21.80 | 9.00 | 21.79 | 9.00 | 21.78 |
December | 744.00 | 21.73 | 9.67 | 21.73 | 9.67 | 21.72 |
Annual Sum or Average | 8107.67 | 22.02 | 703.50 | 22.22 | 311.17 | 22.29 |
Minimum of Months | 559.17 | 21.65 | 0.00 | 21.64 | 0.00 | 21.64 |
Maximum of Months | 744.00 | 22.61 | 212.00 | 23.12 | 121.00 | 23.30 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 666.17 | 21.56 | 28.67 | 21.54 | 27.83 | 21.52 |
February | 618.00 | 21.52 | 13.67 | 21.51 | 13.50 | 21.50 |
March | 668.00 | 21.49 | 14.83 | 21.48 | 12.67 | 21.48 |
April | 593.00 | 21.44 | 4.00 | 21.46 | 0.00 | 21.46 |
May | 670.67 | 21.60 | 2.17 | 21.61 | 0.00 | 21.61 |
June | 597.67 | 21.47 | 7.83 | 21.50 | 0.00 | 21.50 |
July | 551.17 | 21.28 | 25.00 | 21.37 | 0.00 | 21.37 |
August | 546.33 | 21.27 | 48.83 | 21.44 | 0.00 | 21.44 |
September | 559.50 | 21.34 | 19.00 | 21.40 | 0.00 | 21.40 |
October | 604.50 | 21.43 | 30.33 | 21.52 | 0.17 | 21.52 |
November | 645.67 | 21.57 | 19.00 | 21.57 | 15.83 | 21.56 |
December | 673.33 | 21.57 | 34.33 | 21.55 | 34.33 | 21.53 |
Annual Sum or Average | 7394.00 | 21.47 | 247.67 | 21.50 | 104.33 | 21.49 |
Minimum of Months | 546.33 | 21.27 | 2.17 | 21.37 | 0.00 | 21.37 |
Maximum of Months | 673.33 | 21.60 | 48.83 | 21.61 | 34.33 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 730.17 | 21.81 | 44.00 | 21.81 | 36.83 | 21.78 |
February | 663.50 | 21.68 | 19.83 | 21.68 | 17.17 | 21.67 |
March | 716.17 | 21.70 | 23.83 | 21.72 | 17.17 | 21.72 |
April | 602.00 | 21.87 | 42.00 | 22.11 | 6.17 | 22.16 |
May | 581.17 | 21.89 | 66.67 | 22.26 | 9.00 | 22.33 |
June | 424.83 | 22.11 | 179.00 | 23.10 | 32.50 | 23.32 |
July | 388.50 | 22.66 | 300.00 | 23.92 | 97.00 | 24.26 |
August | 411.67 | 22.75 | 300.50 | 23.85 | 120.17 | 24.19 |
September | 483.17 | 22.10 | 128.67 | 22.69 | 43.83 | 22.86 |
October | 590.50 | 22.22 | 91.33 | 22.60 | 38.83 | 22.71 |
November | 704.83 | 21.87 | 30.33 | 21.89 | 22.33 | 21.88 |
December | 729.50 | 21.81 | 51.17 | 21.82 | 42.33 | 21.79 |
Annual Sum or Average | 7026.00 | 21.98 | 1277.33 | 22.43 | 483.33 | 22.56 |
Minimum of Months | 388.50 | 21.68 | 19.83 | 21.68 | 6.17 | 21.67 |
Maximum of Months | 730.17 | 22.75 | 300.50 | 23.92 | 120.17 | 24.26 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 287.67 | 23.94 | 395.83 | 23.95 | 287.50 | 23.95 |
February | 363.50 | 23.95 | 441.17 | 23.96 | 363.50 | 23.95 |
March | 463.83 | 23.92 | 563.17 | 23.93 | 463.83 | 23.92 |
April | 270.00 | 23.99 | 417.17 | 23.99 | 270.00 | 23.99 |
May | 272.00 | 24.00 | 437.50 | 24.00 | 272.00 | 24.00 |
June | 132.83 | 24.00 | 371.33 | 24.00 | 132.83 | 24.00 |
July | 78.17 | 24.00 | 454.17 | 24.00 | 78.17 | 24.00 |
August | 109.67 | 24.00 | 469.17 | 24.00 | 109.67 | 24.00 |
September | 147.67 | 24.00 | 387.67 | 24.00 | 147.67 | 24.00 |
October | 123.33 | 24.00 | 344.33 | 24.00 | 123.33 | 24.00 |
November | 233.17 | 23.99 | 350.83 | 23.99 | 225.00 | 23.99 |
December | 259.00 | 23.96 | 353.17 | 23.97 | 247.50 | 23.97 |
Annual Sum or Average | 2740.83 | 23.97 | 4985.50 | 23.98 | 2721.00 | 23.97 |
Minimum of Months | 78.17 | 23.92 | 344.33 | 23.93 | 78.17 | 23.92 |
Maximum of Months | 463.83 | 24.00 | 563.17 | 24.00 | 463.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 647.50 | 21.38 | 132.17 | 21.41 | 104.17 | 21.37 |
February | 608.00 | 21.38 | 80.83 | 21.41 | 55.33 | 21.37 |
March | 666.33 | 21.36 | 109.50 | 21.40 | 76.00 | 21.35 |
April | 590.67 | 21.38 | 68.83 | 21.55 | 10.83 | 21.54 |
May | 633.33 | 21.44 | 37.17 | 21.55 | 0.00 | 21.55 |
June | 582.67 | 21.40 | 63.17 | 21.59 | 0.00 | 21.59 |
July | 556.33 | 21.29 | 105.33 | 21.61 | 0.33 | 21.61 |
August | 549.00 | 21.26 | 117.83 | 21.63 | 1.83 | 21.63 |
September | 554.83 | 21.31 | 83.00 | 21.57 | 1.00 | 21.57 |
October | 610.17 | 21.41 | 79.00 | 21.60 | 8.50 | 21.60 |
November | 616.33 | 21.41 | 97.00 | 21.50 | 53.33 | 21.47 |
December | 645.67 | 21.39 | 146.33 | 21.41 | 120.67 | 21.37 |
Annual Sum or Average | 7260.83 | 21.37 | 1120.17 | 21.51 | 432.00 | 21.49 |
Minimum of Months | 549.00 | 21.26 | 37.17 | 21.40 | 0.00 | 21.35 |
Maximum of Months | 666.33 | 21.44 | 146.33 | 21.63 | 120.67 | 21.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 711.33 | 21.56 | 146.00 | 21.45 | 146.00 | 21.38 |
February | 626.67 | 21.42 | 89.17 | 21.43 | 75.83 | 21.37 |
March | 680.00 | 21.53 | 127.00 | 21.66 | 98.83 | 21.67 |
April | 594.67 | 22.26 | 145.00 | 23.03 | 70.83 | 23.44 |
May | 606.50 | 22.41 | 143.33 | 23.22 | 67.83 | 23.68 |
June | 511.17 | 23.30 | 234.67 | 24.42 | 115.00 | 25.05 |
July | 501.50 | 23.94 | 324.00 | 24.97 | 178.83 | 25.59 |
August | 524.33 | 23.80 | 326.17 | 24.76 | 192.50 | 25.33 |
September | 497.17 | 22.59 | 237.50 | 23.59 | 91.17 | 23.98 |
October | 544.83 | 22.11 | 162.50 | 22.79 | 54.67 | 22.96 |
November | 656.00 | 21.63 | 76.50 | 21.61 | 68.00 | 21.57 |
December | 716.50 | 21.59 | 166.00 | 21.48 | 165.67 | 21.40 |
Annual Sum or Average | 7170.67 | 22.25 | 2177.83 | 22.87 | 1325.17 | 23.14 |
Minimum of Months | 497.17 | 21.42 | 76.50 | 21.43 | 54.67 | 21.37 |
Maximum of Months | 716.50 | 23.94 | 326.17 | 24.97 | 192.50 | 25.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 604.00 | 21.39 | 128.83 | 21.61 | 39.50 | 21.59 |
February | 581.50 | 21.41 | 68.33 | 21.55 | 20.17 | 21.53 |
March | 654.00 | 21.42 | 88.83 | 21.53 | 35.50 | 21.50 |
April | 596.50 | 21.40 | 36.00 | 21.50 | 2.83 | 21.50 |
May | 674.50 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
June | 635.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
July | 604.00 | 21.41 | 10.33 | 21.45 | 0.33 | 21.45 |
August | 585.33 | 21.36 | 73.67 | 21.58 | 1.33 | 21.58 |
September | 572.33 | 21.35 | 96.50 | 21.64 | 0.33 | 21.64 |
October | 609.33 | 21.43 | 106.83 | 21.71 | 1.33 | 21.71 |
November | 582.00 | 21.39 | 98.00 | 21.59 | 24.17 | 21.58 |
December | 601.83 | 21.39 | 134.83 | 21.61 | 46.00 | 21.58 |
Annual Sum or Average | 7300.33 | 21.42 | 842.17 | 21.57 | 171.50 | 21.56 |
Minimum of Months | 572.33 | 21.35 | 0.00 | 21.45 | 0.00 | 21.45 |
Maximum of Months | 674.50 | 21.54 | 134.83 | 21.71 | 46.00 | 21.71 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 390.33 | 22.86 | 180.00 | 23.17 | 16.67 | 23.19 |
February | 277.33 | 22.93 | 198.00 | 23.31 | 10.83 | 23.31 |
March | 240.83 | 22.81 | 307.00 | 23.36 | 5.17 | 23.37 |
April | 54.00 | 23.35 | 560.50 | 23.79 | 17.33 | 23.80 |
May | 28.83 | 23.32 | 615.00 | 23.83 | 11.83 | 23.83 |
June | 43.17 | 23.99 | 691.33 | 23.91 | 43.17 | 23.91 |
July | 146.83 | 23.97 | 744.00 | 23.94 | 146.83 | 23.94 |
August | 207.50 | 23.95 | 744.00 | 23.93 | 207.50 | 23.93 |
September | 89.50 | 23.93 | 697.50 | 23.85 | 87.17 | 23.86 |
October | 127.83 | 23.57 | 523.00 | 23.78 | 63.83 | 23.80 |
November | 258.33 | 23.10 | 223.50 | 23.43 | 10.83 | 23.43 |
December | 433.67 | 22.99 | 97.00 | 23.15 | 0.00 | 23.15 |
Annual Sum or Average | 2298.17 | 23.20 | 5580.83 | 23.67 | 621.17 | 23.69 |
Minimum of Months | 28.83 | 22.81 | 97.00 | 23.15 | 0.00 | 23.15 |
Maximum of Months | 433.67 | 23.99 | 744.00 | 23.94 | 207.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 258.50 | 22.99 | 288.33 | 23.45 | 13.33 | 23.46 |
February | 148.67 | 23.13 | 322.33 | 23.61 | 11.00 | 23.61 |
March | 129.50 | 22.96 | 456.50 | 23.65 | 4.67 | 23.65 |
April | 25.83 | 23.69 | 643.33 | 23.89 | 14.50 | 23.90 |
May | 13.17 | 23.75 | 692.50 | 23.91 | 9.67 | 23.91 |
June | 33.50 | 23.99 | 716.83 | 23.95 | 33.50 | 23.95 |
July | 128.83 | 23.98 | 744.00 | 23.98 | 128.83 | 23.98 |
August | 179.17 | 23.97 | 744.00 | 23.97 | 179.17 | 23.97 |
September | 60.83 | 23.96 | 713.17 | 23.92 | 60.83 | 23.93 |
October | 73.50 | 23.77 | 591.50 | 23.89 | 51.67 | 23.89 |
November | 114.67 | 23.29 | 358.33 | 23.69 | 9.67 | 23.69 |
December | 256.67 | 23.12 | 196.50 | 23.44 | 0.00 | 23.44 |
Annual Sum or Average | 1422.83 | 23.39 | 6467.33 | 23.82 | 516.83 | 23.83 |
Minimum of Months | 13.17 | 22.96 | 196.50 | 23.44 | 0.00 | 23.44 |
Maximum of Months | 258.50 | 23.99 | 744.00 | 23.98 | 179.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.83 | 23.99 | 728.83 | 23.99 | 499.83 | 23.99 |
February | 454.83 | 23.99 | 657.67 | 23.99 | 454.83 | 23.99 |
March | 507.83 | 23.99 | 743.33 | 23.99 | 507.83 | 23.99 |
April | 510.67 | 23.99 | 720.00 | 24.00 | 510.67 | 24.00 |
May | 534.33 | 24.00 | 744.00 | 24.00 | 534.33 | 24.00 |
June | 539.33 | 24.00 | 720.00 | 24.00 | 539.33 | 24.00 |
July | 640.67 | 24.00 | 744.00 | 24.00 | 640.67 | 24.00 |
August | 679.33 | 24.00 | 744.00 | 24.00 | 679.33 | 24.00 |
September | 554.67 | 24.00 | 720.00 | 24.00 | 554.67 | 24.00 |
October | 558.67 | 24.00 | 743.50 | 24.00 | 558.67 | 24.00 |
November | 493.00 | 23.99 | 704.00 | 23.99 | 493.00 | 23.99 |
December | 491.67 | 23.99 | 716.17 | 23.99 | 491.67 | 23.99 |
Annual Sum or Average | 6464.83 | 24.00 | 8685.50 | 24.00 | 6464.83 | 24.00 |
Minimum of Months | 454.83 | 23.99 | 657.67 | 23.99 | 454.83 | 23.99 |
Maximum of Months | 679.33 | 24.00 | 744.00 | 24.00 | 679.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 441.67 | 23.33 | 429.00 | 23.38 | 320.00 | 23.33 |
February | 421.50 | 23.51 | 454.33 | 23.54 | 372.83 | 23.52 |
March | 465.17 | 23.39 | 526.67 | 23.45 | 426.50 | 23.42 |
April | 267.00 | 23.76 | 430.67 | 23.82 | 257.67 | 23.81 |
May | 249.00 | 23.82 | 423.00 | 23.86 | 245.50 | 23.85 |
June | 115.00 | 23.96 | 421.00 | 23.98 | 115.00 | 23.98 |
July | 39.67 | 24.00 | 498.00 | 24.00 | 39.67 | 24.00 |
August | 51.17 | 24.00 | 502.33 | 24.00 | 51.17 | 24.00 |
September | 138.17 | 23.97 | 437.17 | 23.98 | 138.17 | 23.98 |
October | 137.50 | 23.76 | 420.67 | 23.88 | 136.33 | 23.86 |
November | 340.00 | 23.62 | 392.33 | 23.67 | 271.00 | 23.65 |
December | 451.50 | 23.46 | 402.83 | 23.48 | 290.67 | 23.44 |
Annual Sum or Average | 3117.33 | 23.58 | 5338.00 | 23.71 | 2664.50 | 23.67 |
Minimum of Months | 39.67 | 23.33 | 392.33 | 23.38 | 39.67 | 23.33 |
Maximum of Months | 465.17 | 24.00 | 526.67 | 24.00 | 426.50 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.97422 | 37.30327 | 0.32795 | 7.36078 |
February | 672.00000 | 23.97847 | 40.38670 | 0.33488 | 7.45830 |
March | 744.00000 | 23.92651 | 44.16676 | 0.34537 | 7.58931 |
April | 720.00000 | 23.99441 | 47.12774 | 0.38024 | 8.08350 |
May | 744.00000 | 23.99371 | 46.50684 | -0.5388 | 11.11459 |
June | 720.00000 | 23.99989 | 51.64731 | -0.5025 | 10.30438 |
July | 744.00000 | 24.00006 | 55.20862 | -0.4648 | 9.53421 |
August | 744.00000 | 24.00007 | 56.40521 | -0.4532 | 9.30443 |
September | 720.00000 | 24.00007 | 51.60921 | -0.4760 | 9.79213 |
October | 744.00000 | 23.99996 | 42.38877 | 0.37340 | 8.04430 |
November | 720.00000 | 23.99839 | 38.15822 | 0.34379 | 7.61733 |
December | 744.00000 | 23.98681 | 32.83387 | 0.29979 | 7.02585 |
Annual Sum or Average | 8760.00000 | 23.98768 | 45.33237 | -0.0046 | 8.60803 |
Minimum of Months | 672.00000 | 23.92651 | 32.83387 | -0.5388 | 7.02585 |
Maximum of Months | 744.00000 | 24.00007 | 56.40521 | 0.38024 | 11.11459 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.35539 | 41.11963 | 0.06068 | 9.01378 |
February | 672.00000 | 22.14181 | 44.39406 | 0.00127 | 8.34466 |
March | 744.00000 | 22.03684 | 48.40542 | -0.0200 | 8.24383 |
April | 720.00000 | 22.41638 | 50.96537 | 0.11637 | 8.17565 |
May | 744.00000 | 22.23547 | 50.68750 | -1.0062 | 29.96026 |
June | 720.00000 | 22.55339 | 55.09163 | -0.8454 | 23.44791 |
July | 744.00000 | 22.93249 | 58.47174 | -0.6597 | 17.51213 |
August | 744.00000 | 23.02701 | 59.67561 | -0.5865 | 16.00733 |
September | 720.00000 | 22.85711 | 55.38453 | -0.6620 | 19.14255 |
October | 744.00000 | 22.86643 | 45.99850 | 0.25678 | 9.48138 |
November | 720.00000 | 22.46971 | 42.03649 | 0.10575 | 8.81268 |
December | 744.00000 | 22.39296 | 36.10750 | 0.05034 | 9.04946 |
Annual Sum or Average | 8760.00000 | 22.52634 | 49.04607 | -0.2673 | 13.96802 |
Minimum of Months | 672.00000 | 22.03684 | 36.10750 | -1.0062 | 8.17565 |
Maximum of Months | 744.00000 | 23.02701 | 59.67561 | 0.25678 | 29.96026 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.16487 | 40.69117 | 0.18769 | 6.25710 |
February | 672.00000 | 23.07592 | 43.49102 | 0.18155 | 6.17228 |
March | 744.00000 | 22.96926 | 47.37699 | 0.17936 | 6.24743 |
April | 720.00000 | 23.28920 | 49.75129 | 0.28366 | 7.12399 |
May | 744.00000 | 23.21490 | 49.20226 | -0.7067 | 16.23022 |
June | 720.00000 | 23.39452 | 53.63424 | -0.6045 | 13.24014 |
July | 744.00000 | 23.57947 | 57.35863 | -0.5041 | 10.68482 |
August | 744.00000 | 23.63830 | 58.67640 | -0.4710 | 9.94583 |
September | 720.00000 | 23.56299 | 54.40214 | -0.5313 | 11.35953 |
October | 744.00000 | 23.54489 | 45.49642 | 0.32978 | 7.67467 |
November | 720.00000 | 23.32038 | 41.48048 | 0.23517 | 6.56043 |
December | 744.00000 | 23.23920 | 35.88134 | 0.17547 | 6.03761 |
Annual Sum or Average | 8760.00000 | 23.33429 | 48.13965 | -0.1055 | 8.97741 |
Minimum of Months | 672.00000 | 22.96926 | 35.88134 | -0.7067 | 6.03761 |
Maximum of Months | 744.00000 | 23.63830 | 58.67640 | 0.32978 | 16.23022 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99986 | 33.42401 | 0.94034 | 24.51754 |
February | 672.00000 | 23.99972 | 36.05713 | 0.95615 | 25.11785 |
March | 744.00000 | 23.99980 | 39.40674 | 0.98093 | 26.07080 |
April | 720.00000 | 24.00008 | 43.51493 | 1.02754 | 27.98377 |
May | 744.00000 | 24.00018 | 43.16941 | 0.39383 | 9.91420 |
June | 720.00000 | 24.00095 | 49.59630 | 0.45677 | 10.98619 |
July | 744.00000 | 24.00129 | 54.24048 | 0.50278 | 11.81858 |
August | 744.00000 | 24.00125 | 56.09114 | 0.52104 | 12.20828 |
September | 720.00000 | 24.00113 | 51.89527 | 0.47286 | 11.23379 |
October | 744.00000 | 24.00078 | 41.24614 | 1.02247 | 27.87939 |
November | 720.00000 | 23.99981 | 35.04705 | 0.95897 | 25.26808 |
December | 744.00000 | 23.99975 | 28.77474 | 0.90875 | 23.28253 |
Annual Sum or Average | 8760.00000 | 24.00039 | 42.73463 | 0.76063 | 19.65448 |
Minimum of Months | 672.00000 | 23.99972 | 28.77474 | 0.39383 | 9.91420 |
Maximum of Months | 744.00000 | 24.00129 | 56.09114 | 1.02754 | 27.98377 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.30112 | 42.92672 | 0.34104 | 10.26987 |
February | 672.00000 | 23.40040 | 45.91463 | 0.34353 | 9.48221 |
March | 744.00000 | 23.13486 | 49.89740 | 0.28975 | 9.40212 |
April | 720.00000 | 23.75941 | 52.08859 | 0.47228 | 10.65837 |
May | 744.00000 | 23.78629 | 51.59324 | -0.4618 | 10.72249 |
June | 720.00000 | 23.98276 | 56.39995 | -0.3336 | 7.72254 |
July | 744.00000 | 23.99901 | 61.54864 | -0.2440 | 6.65450 |
August | 744.00000 | 23.99849 | 63.17515 | -0.1924 | 6.39342 |
September | 720.00000 | 23.98762 | 57.77158 | -0.2265 | 7.21161 |
October | 744.00000 | 23.92746 | 48.27713 | 0.56023 | 12.67351 |
November | 720.00000 | 23.67385 | 43.76581 | 0.43808 | 10.73856 |
December | 744.00000 | 23.35305 | 38.09129 | 0.33245 | 9.89924 |
Annual Sum or Average | 8760.00000 | 23.69268 | 50.97859 | 0.10825 | 9.32028 |
Minimum of Months | 672.00000 | 23.13486 | 38.09129 | -0.4618 | 6.39342 |
Maximum of Months | 744.00000 | 23.99901 | 63.17515 | 0.56023 | 12.67351 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.54549 | 42.67581 | 0.32902 | 7.68575 |
February | 672.00000 | 23.39702 | 45.54115 | 0.30493 | 7.37825 |
March | 744.00000 | 23.26431 | 49.41166 | 0.29270 | 7.33994 |
April | 720.00000 | 23.52505 | 51.90866 | 0.38390 | 8.37696 |
May | 744.00000 | 23.39111 | 51.50488 | -0.5952 | 12.89706 |
June | 720.00000 | 23.55067 | 55.93999 | -0.4979 | 10.52409 |
July | 744.00000 | 23.71703 | 59.65516 | -0.4023 | 8.56200 |
August | 744.00000 | 23.82410 | 60.76218 | -0.3495 | 7.67123 |
September | 720.00000 | 23.79334 | 56.36891 | -0.3905 | 8.46176 |
October | 744.00000 | 23.78092 | 47.54705 | 0.44171 | 9.36705 |
November | 720.00000 | 23.64685 | 43.49423 | 0.36538 | 8.10271 |
December | 744.00000 | 23.60434 | 37.97609 | 0.31563 | 7.39581 |
Annual Sum or Average | 8760.00000 | 23.58778 | 50.25212 | 0.01468 | 8.65490 |
Minimum of Months | 672.00000 | 23.26431 | 37.97609 | -0.5952 | 7.33994 |
Maximum of Months | 744.00000 | 23.82410 | 60.76218 | 0.44171 | 12.89706 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.70802 | 43.53132 | -0.1723 | 7.28361 |
February | 672.00000 | 21.65026 | 46.26854 | -0.1777 | 7.11459 |
March | 744.00000 | 21.64865 | 48.50345 | -0.1689 | 7.13119 |
April | 720.00000 | 21.74760 | 48.70503 | -0.0862 | 6.70313 |
May | 744.00000 | 21.74764 | 48.73419 | -1.1931 | 36.95416 |
June | 720.00000 | 21.77193 | 50.63694 | -1.1248 | 33.78268 |
July | 744.00000 | 21.79079 | 52.15265 | -1.0648 | 31.26562 |
August | 744.00000 | 21.79058 | 53.01953 | -1.0557 | 31.02376 |
September | 720.00000 | 21.77566 | 51.14618 | -1.0988 | 32.98889 |
October | 744.00000 | 21.76864 | 46.42760 | -0.0658 | 6.69387 |
November | 720.00000 | 21.73706 | 43.42791 | -0.1458 | 7.11480 |
December | 744.00000 | 21.71554 | 39.27565 | -0.1887 | 7.48380 |
Annual Sum or Average | 8760.00000 | 21.73819 | 47.65473 | -0.5475 | 18.02688 |
Minimum of Months | 672.00000 | 21.64865 | 39.27565 | -1.1931 | 6.69387 |
Maximum of Months | 744.00000 | 21.79079 | 53.01953 | -0.0658 | 36.95416 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.77161 | 45.09544 | -0.2114 | 7.45265 |
February | 672.00000 | 21.71907 | 47.51671 | -0.1988 | 7.28941 |
March | 744.00000 | 21.82232 | 49.42126 | -0.1577 | 7.83376 |
April | 720.00000 | 22.58392 | 48.06307 | 0.06303 | 10.12869 |
May | 744.00000 | 22.72807 | 47.35650 | -0.9211 | 32.42795 |
June | 720.00000 | 23.48512 | 48.61915 | -0.6345 | 26.90486 |
July | 744.00000 | 23.81194 | 50.31482 | -0.4855 | 23.73414 |
August | 744.00000 | 23.72123 | 52.07401 | -0.5170 | 23.24465 |
September | 720.00000 | 23.12168 | 50.97698 | -0.7469 | 25.38676 |
October | 744.00000 | 22.78258 | 46.71751 | 0.10704 | 8.45848 |
November | 720.00000 | 21.90957 | 44.90319 | -0.1558 | 7.10012 |
December | 744.00000 | 21.79787 | 40.51292 | -0.2303 | 7.52554 |
Annual Sum or Average | 8760.00000 | 22.60999 | 47.62632 | -0.3416 | 15.67317 |
Minimum of Months | 672.00000 | 21.71907 | 40.51292 | -0.9211 | 7.10012 |
Maximum of Months | 744.00000 | 23.81194 | 52.07401 | 0.10704 | 32.42795 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.72208 | 42.57411 | -0.2438 | 7.01873 |
February | 672.00000 | 21.64872 | 45.15767 | -0.2406 | 6.72605 |
March | 744.00000 | 21.67995 | 48.11202 | -0.2125 | 6.63137 |
April | 720.00000 | 22.02740 | 49.04956 | -0.1038 | 6.31100 |
May | 744.00000 | 22.15608 | 47.87399 | -1.1546 | 34.79288 |
June | 720.00000 | 22.65862 | 50.75967 | -0.9454 | 26.99987 |
July | 744.00000 | 22.96533 | 53.93059 | -0.8124 | 22.86291 |
August | 744.00000 | 22.89230 | 56.05943 | -0.8346 | 23.26596 |
September | 720.00000 | 22.50404 | 53.39790 | -0.9950 | 28.29675 |
October | 744.00000 | 22.49391 | 46.35560 | 0.00440 | 6.71703 |
November | 720.00000 | 21.79835 | 43.29242 | -0.2114 | 6.62709 |
December | 744.00000 | 21.73370 | 38.01489 | -0.2694 | 7.07451 |
Annual Sum or Average | 8760.00000 | 22.19386 | 47.89025 | -0.5031 | 15.32777 |
Minimum of Months | 672.00000 | 21.64872 | 38.01489 | -1.1546 | 6.31100 |
Maximum of Months | 744.00000 | 22.96533 | 56.05943 | 0.00440 | 34.79288 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.74238 | 43.28838 | -0.1610 | 7.09295 |
February | 672.00000 | 21.66300 | 46.45511 | -0.1773 | 6.98414 |
March | 744.00000 | 21.67698 | 48.47100 | -0.1615 | 7.01352 |
April | 720.00000 | 21.77647 | 48.90398 | -0.0834 | 6.59814 |
May | 744.00000 | 21.77320 | 49.03346 | -1.1952 | 36.87933 |
June | 720.00000 | 21.78719 | 51.15242 | -1.1375 | 34.19355 |
July | 744.00000 | 21.80956 | 52.30151 | -1.0718 | 31.46916 |
August | 744.00000 | 21.80916 | 52.99132 | -1.0562 | 30.96019 |
September | 720.00000 | 21.77905 | 51.83143 | -1.1160 | 33.54873 |
October | 744.00000 | 21.78326 | 46.65811 | -0.0652 | 6.57993 |
November | 720.00000 | 21.75067 | 43.55900 | -0.1459 | 6.91942 |
December | 744.00000 | 21.73855 | 39.25583 | -0.1825 | 7.27880 |
Annual Sum or Average | 8760.00000 | 21.75806 | 47.82503 | -0.5483 | 18.02422 |
Minimum of Months | 672.00000 | 21.66300 | 39.25583 | -1.1952 | 6.57993 |
Maximum of Months | 744.00000 | 21.80956 | 52.99132 | -0.0652 | 36.87933 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.86505 | 44.80857 | -0.1875 | 7.15367 |
February | 672.00000 | 21.71841 | 47.84083 | -0.2007 | 6.95248 |
March | 744.00000 | 21.78232 | 49.60000 | -0.1636 | 7.09304 |
April | 720.00000 | 22.23007 | 49.25702 | -0.0087 | 7.21414 |
May | 744.00000 | 22.38812 | 48.55873 | -1.0243 | 31.45403 |
June | 720.00000 | 22.98592 | 50.39459 | -0.7899 | 24.80760 |
July | 744.00000 | 23.43409 | 51.80517 | -0.6012 | 21.29285 |
August | 744.00000 | 23.36724 | 53.37911 | -0.6178 | 21.27710 |
September | 720.00000 | 22.70328 | 53.07843 | -0.8791 | 25.85927 |
October | 744.00000 | 22.62219 | 47.56708 | 0.07437 | 7.33352 |
November | 720.00000 | 21.93359 | 45.28048 | -0.1536 | 6.85320 |
December | 744.00000 | 21.88770 | 40.58857 | -0.2099 | 7.25522 |
Annual Sum or Average | 8760.00000 | 22.41493 | 48.50790 | -0.3978 | 14.58997 |
Minimum of Months | 672.00000 | 21.71841 | 40.58857 | -1.0243 | 6.85320 |
Maximum of Months | 744.00000 | 23.43409 | 53.37911 | 0.07437 | 31.45403 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63596 | 45.19551 | -0.2301 | 8.12701 |
February | 672.00000 | 21.56068 | 48.31656 | -0.2360 | 7.92886 |
March | 744.00000 | 21.56544 | 50.60491 | -0.2201 | 7.93319 |
April | 720.00000 | 21.71601 | 50.52809 | -0.1077 | 7.18421 |
May | 744.00000 | 21.71663 | 50.44907 | -1.2264 | 38.97238 |
June | 720.00000 | 21.75615 | 52.01376 | -1.1376 | 34.84098 |
July | 744.00000 | 21.78410 | 53.07797 | -1.0629 | 31.73507 |
August | 744.00000 | 21.78081 | 54.15157 | -1.0565 | 31.62377 |
September | 720.00000 | 21.75435 | 52.84141 | -1.1192 | 34.40545 |
October | 744.00000 | 21.73893 | 47.79855 | -0.0897 | 7.12337 |
November | 720.00000 | 21.68293 | 45.13135 | -0.1937 | 7.77066 |
December | 744.00000 | 21.64343 | 40.60541 | -0.2488 | 8.37636 |
Annual Sum or Average | 8760.00000 | 21.69536 | 49.22377 | -0.5795 | 18.90047 |
Minimum of Months | 672.00000 | 21.56068 | 40.60541 | -1.2264 | 7.12337 |
Maximum of Months | 744.00000 | 21.78410 | 54.15157 | -0.0897 | 38.97238 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.64875 | 47.06893 | -0.2820 | 8.46018 |
February | 672.00000 | 21.59644 | 49.81682 | -0.2643 | 8.19935 |
March | 744.00000 | 21.73815 | 51.60560 | -0.2085 | 8.72364 |
April | 720.00000 | 22.59195 | 49.58165 | 0.05404 | 11.01574 |
May | 744.00000 | 22.72592 | 48.67520 | -0.9372 | 34.63333 |
June | 720.00000 | 23.54224 | 49.05931 | -0.6141 | 28.94894 |
July | 744.00000 | 23.91339 | 50.01476 | -0.4387 | 25.64352 |
August | 744.00000 | 23.79982 | 51.93476 | -0.4806 | 24.94208 |
September | 720.00000 | 23.11258 | 51.86189 | -0.7560 | 27.01571 |
October | 744.00000 | 22.70459 | 47.87525 | 0.07671 | 8.76776 |
November | 720.00000 | 21.80589 | 46.98578 | -0.2141 | 7.80709 |
December | 744.00000 | 21.66338 | 42.16042 | -0.3054 | 8.63490 |
Annual Sum or Average | 8760.00000 | 22.57615 | 48.87373 | -0.3648 | 16.95116 |
Minimum of Months | 672.00000 | 21.59644 | 42.16042 | -0.9372 | 7.80709 |
Maximum of Months | 744.00000 | 23.91339 | 51.93476 | 0.07671 | 34.63333 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.75684 | 43.22162 | -0.1361 | 7.68342 |
February | 672.00000 | 21.67182 | 46.55172 | -0.1724 | 7.45551 |
March | 744.00000 | 21.64924 | 49.19868 | -0.1824 | 7.52262 |
April | 720.00000 | 21.73095 | 50.69261 | -0.1214 | 6.94200 |
May | 744.00000 | 21.70546 | 51.38355 | -1.2802 | 40.93537 |
June | 720.00000 | 21.73831 | 54.16523 | -1.2156 | 37.72837 |
July | 744.00000 | 21.77403 | 55.83755 | -1.1489 | 34.81735 |
August | 744.00000 | 21.77727 | 56.07188 | -1.1159 | 33.67776 |
September | 720.00000 | 21.75816 | 53.13734 | -1.1357 | 34.96013 |
October | 744.00000 | 21.76806 | 47.28089 | -0.0645 | 7.09918 |
November | 720.00000 | 21.76422 | 43.42942 | -0.1242 | 7.46764 |
December | 744.00000 | 21.76086 | 39.03344 | -0.1506 | 7.88501 |
Annual Sum or Average | 8760.00000 | 21.73837 | 49.17546 | -0.5731 | 19.58888 |
Minimum of Months | 672.00000 | 21.64924 | 39.03344 | -1.2802 | 6.94200 |
Maximum of Months | 744.00000 | 21.77727 | 56.07188 | -0.0645 | 40.93537 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.22623 | 43.80551 | 0.26905 | 7.18547 |
February | 672.00000 | 23.32855 | 46.31660 | 0.31516 | 7.49581 |
March | 744.00000 | 23.36732 | 49.75070 | 0.35403 | 8.13204 |
April | 720.00000 | 23.70768 | 52.42257 | 0.48706 | 10.23420 |
May | 744.00000 | 23.75451 | 51.52736 | -0.3745 | 8.26198 |
June | 720.00000 | 23.87179 | 56.09769 | -0.2687 | 6.75476 |
July | 744.00000 | 23.93333 | 59.73675 | -0.2015 | 5.98460 |
August | 744.00000 | 23.91828 | 61.11781 | -0.2064 | 6.01900 |
September | 720.00000 | 23.81566 | 57.32650 | -0.2993 | 7.09371 |
October | 744.00000 | 23.72364 | 48.70419 | 0.47335 | 10.04719 |
November | 720.00000 | 23.41232 | 44.74970 | 0.33193 | 7.71367 |
December | 744.00000 | 23.28060 | 39.14792 | 0.24977 | 6.71345 |
Annual Sum or Average | 8760.00000 | 23.61300 | 50.91029 | 0.09269 | 7.63405 |
Minimum of Months | 672.00000 | 23.22623 | 39.14792 | -0.3745 | 5.98460 |
Maximum of Months | 744.00000 | 23.93333 | 61.11781 | 0.48706 | 10.23420 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.45750 | 43.22041 | 0.34406 | 8.05586 |
February | 672.00000 | 23.55797 | 45.68722 | 0.38968 | 8.52595 |
March | 744.00000 | 23.59019 | 49.06736 | 0.42806 | 9.25311 |
April | 720.00000 | 23.85178 | 51.79796 | 0.54301 | 11.38718 |
May | 744.00000 | 23.88007 | 50.92312 | -0.3003 | 7.13639 |
June | 720.00000 | 23.94143 | 55.55492 | -0.2119 | 6.13761 |
July | 744.00000 | 23.98067 | 59.24013 | -0.1518 | 5.61292 |
August | 744.00000 | 23.97298 | 60.59334 | -0.1549 | 5.62316 |
September | 720.00000 | 23.91309 | 56.70628 | -0.2351 | 6.33731 |
October | 744.00000 | 23.84933 | 48.13289 | 0.52402 | 11.05284 |
November | 720.00000 | 23.62271 | 44.17130 | 0.40132 | 8.71586 |
December | 744.00000 | 23.50761 | 38.61993 | 0.32328 | 7.53582 |
Annual Sum or Average | 8760.00000 | 23.76132 | 50.32841 | 0.15675 | 7.94093 |
Minimum of Months | 672.00000 | 23.45750 | 38.61993 | -0.3003 | 5.61292 |
Maximum of Months | 744.00000 | 23.98067 | 60.59334 | 0.54301 | 11.38718 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.99286 | 41.61621 | 1.07482 | 31.29175 |
February | 672.00000 | 23.99189 | 43.44377 | 1.07976 | 31.36295 |
March | 744.00000 | 23.99165 | 46.96268 | 1.11301 | 32.91387 |
April | 720.00000 | 23.99531 | 49.43007 | 1.18381 | 36.11311 |
May | 744.00000 | 23.99612 | 48.77937 | 0.59508 | 16.70501 |
June | 720.00000 | 23.99835 | 53.87133 | 0.67521 | 18.66931 |
July | 744.00000 | 23.99997 | 58.48348 | 0.75049 | 20.91270 |
August | 744.00000 | 24.00017 | 60.10957 | 0.76094 | 21.21892 |
September | 720.00000 | 23.99867 | 55.98451 | 0.68375 | 18.93110 |
October | 744.00000 | 23.99904 | 48.13177 | 1.18803 | 36.40190 |
November | 720.00000 | 23.99379 | 42.12272 | 1.09052 | 31.90227 |
December | 744.00000 | 23.99256 | 37.09393 | 1.04291 | 29.94358 |
Annual Sum or Average | 8760.00000 | 23.99589 | 48.86348 | 0.93566 | 27.17166 |
Minimum of Months | 672.00000 | 23.99165 | 37.09393 | 0.59508 | 16.70501 |
Maximum of Months | 744.00000 | 24.00017 | 60.10957 | 1.18803 | 36.40190 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.85464 | 40.33878 | -0.1650 | 6.08246 |
February | 672.00000 | 21.83851 | 43.23842 | -0.1516 | 5.76793 |
March | 744.00000 | 21.78651 | 47.25348 | -0.1404 | 5.82958 |
April | 720.00000 | 22.28606 | 49.43568 | -0.0001 | 5.32067 |
May | 744.00000 | 22.41587 | 48.29099 | -1.0263 | 27.60659 |
June | 720.00000 | 22.85705 | 52.28238 | -0.8443 | 20.42129 |
July | 744.00000 | 23.14086 | 56.01827 | -0.7187 | 16.18785 |
August | 744.00000 | 23.10429 | 57.75235 | -0.7208 | 16.20790 |
September | 720.00000 | 22.83219 | 53.77471 | -0.8431 | 20.36733 |
October | 744.00000 | 22.79301 | 44.41662 | 0.09918 | 5.70190 |
November | 720.00000 | 22.09865 | 41.07531 | -0.0982 | 5.53485 |
December | 744.00000 | 21.91393 | 35.19311 | -0.1815 | 6.01152 |
Annual Sum or Average | 8760.00000 | 22.41364 | 47.43806 | -0.4007 | 11.78983 |
Minimum of Months | 672.00000 | 21.78651 | 35.19311 | -1.0263 | 5.32067 |
Maximum of Months | 744.00000 | 23.14086 | 57.75235 | 0.09918 | 27.60659 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.97691 | 61.61180 | 0.44072 | 9.16340 |
February | 672.00000 | 23.97314 | 66.91359 | 0.47072 | 9.79281 |
March | 744.00000 | 23.94914 | 70.02926 | 0.48373 | 10.00691 |
April | 720.00000 | 23.99556 | 60.55836 | 0.44149 | 9.15079 |
May | 744.00000 | 23.99906 | 60.33584 | -0.4883 | 10.01682 |
June | 720.00000 | 23.99932 | 57.14836 | -0.4965 | 10.16596 |
July | 744.00000 | 23.99934 | 56.25220 | -0.4916 | 10.06024 |
August | 744.00000 | 23.99933 | 56.54258 | -0.4873 | 9.97289 |
September | 720.00000 | 23.99931 | 56.26108 | -0.4944 | 10.14948 |
October | 744.00000 | 23.99930 | 54.76610 | 0.41793 | 8.67461 |
November | 720.00000 | 23.99678 | 58.02021 | 0.42547 | 8.85410 |
December | 744.00000 | 23.98670 | 58.70412 | 0.42545 | 8.88767 |
Annual Sum or Average | 8760.00000 | 23.98953 | 59.72252 | 0.05145 | 9.57279 |
Minimum of Months | 672.00000 | 23.94914 | 54.76610 | -0.4965 | 8.67461 |
Maximum of Months | 744.00000 | 23.99934 | 70.02926 | 0.48373 | 10.16596 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.60009 | 62.84134 | 0.36049 | 8.07713 |
February | 672.00000 | 23.68692 | 67.83029 | 0.41233 | 8.77073 |
March | 744.00000 | 23.61806 | 68.69761 | 0.40273 | 8.67275 |
April | 720.00000 | 23.90724 | 58.46155 | 0.43440 | 9.10266 |
May | 744.00000 | 23.93446 | 57.39036 | -0.4893 | 10.17468 |
June | 720.00000 | 23.99212 | 53.12219 | -0.4699 | 9.69967 |
July | 744.00000 | 23.99922 | 51.50667 | -0.4538 | 9.37927 |
August | 744.00000 | 23.99937 | 51.99052 | -0.4488 | 9.29688 |
September | 720.00000 | 23.99284 | 53.65316 | -0.4626 | 9.60322 |
October | 744.00000 | 23.95238 | 53.25333 | 0.42642 | 8.87052 |
November | 720.00000 | 23.81803 | 59.22428 | 0.40003 | 8.52607 |
December | 744.00000 | 23.66941 | 60.41265 | 0.36383 | 8.02454 |
Annual Sum or Average | 8760.00000 | 23.84796 | 58.14233 | 0.03729 | 9.01616 |
Minimum of Months | 672.00000 | 23.60009 | 51.50667 | -0.4893 | 8.02454 |
Maximum of Months | 744.00000 | 23.99937 | 68.69761 | 0.43440 | 10.17468 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.21401 | 37.21245 | 0.13915 | 5.88979 |
February | 672.00000 | 23.22735 | 39.81196 | 0.15863 | 5.81763 |
March | 744.00000 | 23.13602 | 43.62476 | 0.16154 | 5.93968 |
April | 720.00000 | 23.47736 | 46.09765 | 0.26654 | 6.74667 |
May | 744.00000 | 23.53564 | 45.23313 | -0.6728 | 14.84822 |
June | 720.00000 | 23.76102 | 49.57181 | -0.5566 | 11.69781 |
July | 744.00000 | 23.88808 | 53.54573 | -0.4783 | 9.89933 |
August | 744.00000 | 23.89689 | 55.05516 | -0.4653 | 9.62096 |
September | 720.00000 | 23.79838 | 50.77404 | -0.5346 | 11.18241 |
October | 744.00000 | 23.76917 | 41.88706 | 0.31960 | 7.42336 |
November | 720.00000 | 23.43071 | 37.96621 | 0.19945 | 6.14391 |
December | 744.00000 | 23.30035 | 32.37626 | 0.12819 | 5.66220 |
Annual Sum or Average | 8760.00000 | 23.53790 | 44.44931 | -0.1129 | 8.42139 |
Minimum of Months | 672.00000 | 23.13602 | 32.37626 | -0.6728 | 5.66220 |
Maximum of Months | 744.00000 | 23.89689 | 55.05516 | 0.31960 | 14.84822 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.265356E+11 | 0.00 | 391.33 | 93285.61 | 08-JAN-06:50 | 0.00 | 29.78 | 48.73 | 0.07 | 0.00 | 0.02 | 0.17 | 08-JAN-06:50 |
February | 0.125912E+11 | 0.00 | 356.90 | 68906.11 | 27-FEB-16:14 | 0.00 | 27.39 | 47.75 | 0.03 | 0.00 | 0.01 | 0.12 | 27-FEB-16:14 |
March | 0.231636E+11 | 0.00 | 394.27 | 139824.61 | 28-MAR-08:62 | 0.00 | 28.83 | 48.53 | 0.06 | 0.00 | 0.02 | 0.25 | 28-MAR-08:62 |
April | 0.329165E+10 | 0.00 | 204.02 | 48890.86 | 01-APR-05:40 | 0.00 | 25.06 | 36.45 | 0.01 | 0.00 | 0.00 | 0.09 | 01-APR-05:40 |
May | 0.314880E+10 | 0.00 | 192.82 | 36758.48 | 14-MAY-04:50 | 0.00 | 25.67 | 35.97 | 0.01 | 0.00 | 0.00 | 0.07 | 14-MAY-04:50 |
June | 0.162298E+09 | 0.00 | 65.75 | 19309.51 | 12-JUN-08:56 | 0.00 | 23.48 | 27.31 | 0.00 | 0.00 | 0.00 | 0.03 | 12-JUN-08:56 |
July | 7676578.45 | 0.00 | 5.98 | 5578.25 | 17-JUL-21:55 | 0.00 | 23.35 | 23.69 | 0.00 | 0.00 | 0.00 | 0.01 | 17-JUL-21:55 |
August | 5781164.63 | 0.00 | 1.66 | 4195.44 | 22-AUG-08:03 | 0.00 | 23.55 | 23.64 | 0.00 | 0.00 | 0.00 | 0.01 | 22-AUG-08:03 |
September | 0.102078E+09 | 0.00 | 24.14 | 11409.22 | 18-SEP-19:06 | 0.00 | 23.78 | 25.18 | 0.00 | 0.00 | 0.00 | 0.02 | 18-SEP-19:06 |
October | 0.129627E+10 | 0.00 | 84.98 | 37104.40 | 11-OCT-19:06 | 0.00 | 26.19 | 30.69 | 0.00 | 0.00 | 0.00 | 0.07 | 11-OCT-19:06 |
November | 0.979905E+10 | 0.00 | 273.64 | 58346.40 | 23-NOV-19:05 | 0.00 | 27.85 | 42.23 | 0.02 | 0.00 | 0.01 | 0.10 | 23-NOV-19:05 |
December | 0.223641E+11 | 0.00 | 378.77 | 73496.62 | 13-DEC-04:30 | 0.00 | 29.21 | 47.71 | 0.06 | 0.00 | 0.01 | 0.13 | 13-DEC-04:30 |
Annual Sum or Average | 0.102468E+12 | 0.00 | 2374.26 | 0.00 | 26.18 | 36.44 | 0.02 | 0.00 | 0.01 | ||||
Minimum of Months | 5781164.63 | 0.00 | 1.66 | 4195.44 | 0.00 | 23.35 | 23.64 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.265356E+11 | 0.00 | 394.27 | 139824.61 | 0.00 | 29.78 | 48.73 | 0.07 | 0.00 | 0.02 | 0.25 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.576381E+10 | 0.168526E+10 | 485.14 | 0.529005E+10 | 0.473764E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 23673.85 | 21-JAN-09:01 | 21477.86 | 02-JAN-16:12 | 6670.40 | 21-JAN-09:01 | 6089.14 | 21-JAN-09:01 | 0.00 | 01-JAN-00:05 |
February | 0.467824E+10 | 0.136276E+10 | 424.78 | 0.422430E+10 | 0.453940E+09 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-05:50 | 23796.19 | 14-FEB-09:02 | 21466.35 | 20-FEB-16:12 | 7059.28 | 14-FEB-09:02 | 6115.62 | 14-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.524848E+10 | 0.152266E+10 | 445.87 | 0.459798E+10 | 0.650503E+09 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:10 | 23801.90 | 18-MAR-08:61 | 21586.87 | 11-MAR-16:12 | 7278.53 | 19-MAR-08:61 | 6116.85 | 18-MAR-08:61 | 0.00 | 01-MAR-00:10 |
April | 0.845673E+10 | 0.244091E+10 | 617.35 | 0.736587E+10 | 0.109086E+10 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-00:10 | 23728.84 | 08-APR-08:61 | 21461.44 | 01-APR-15:12 | 7430.34 | 15-APR-08:61 | 6101.07 | 08-APR-08:61 | 0.00 | 01-APR-00:10 |
May | 0.803096E+10 | 0.233041E+10 | 633.44 | 0.693460E+10 | 0.109636E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-06:52 | 23799.49 | 03-MAY-08:62 | 21299.79 | 26-MAY-18:01 | 6973.65 | 05-MAY-08:62 | 6116.33 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.106572E+11 | 0.307714E+10 | 666.53 | 0.883971E+10 | 0.181753E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-03:20 | 24262.81 | 28-JUN-08:62 | 20904.38 | 12-JUN-15:12 | 8623.40 | 28-JUN-08:62 | 6214.20 | 28-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.141661E+11 | 0.407430E+10 | 707.61 | 0.114232E+11 | 0.274290E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 24662.17 | 24-JUL-08:62 | 20588.43 | 09-JUL-15:11 | 9147.34 | 24-JUL-08:62 | 6295.57 | 24-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.146788E+11 | 0.421825E+10 | 708.21 | 0.117149E+11 | 0.296386E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:53 | 24971.22 | 18-AUG-08:62 | 20513.09 | 22-AUG-15:12 | 10065.07 | 18-AUG-08:62 | 6356.65 | 18-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.120002E+11 | 0.349398E+10 | 674.82 | 0.995246E+10 | 0.204771E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:53 | 24844.00 | 22-SEP-08:62 | 20780.73 | 19-SEP-15:12 | 9702.87 | 22-SEP-08:62 | 6331.71 | 22-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.112037E+11 | 0.329502E+10 | 664.54 | 0.983704E+10 | 0.136664E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:53 | 24927.46 | 01-OCT-08:62 | 21587.58 | 12-OCT-18:02 | 9996.84 | 01-OCT-08:62 | 6348.11 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.654091E+10 | 0.190781E+10 | 523.84 | 0.592326E+10 | 0.617647E+09 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-06:53 | 23689.96 | 10-NOV-09:02 | 21543.01 | 19-NOV-09:02 | 6628.69 | 10-NOV-09:02 | 6092.64 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.599295E+10 | 0.174638E+10 | 485.33 | 0.569385E+10 | 0.299105E+09 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-01:30 | 23599.54 | 09-DEC-09:02 | 21548.38 | 06-DEC-16:12 | 6825.90 | 09-DEC-09:02 | 6072.92 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.107418E+12 | 0.311549E+11 | 7037.46 | 0.917972E+11 | 0.156208E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.467824E+10 | 0.136276E+10 | 424.78 | 0.422430E+10 | 0.299105E+09 | 0.00 | 1.00 | 0.00 | 23599.54 | 20513.09 | 6628.69 | 6072.92 | 0.00 | |||||||
Maximum of Months | 0.146788E+11 | 0.421825E+10 | 708.21 | 0.117149E+11 | 0.296386E+10 | 0.00 | 1.00 | 0.00 | 24971.22 | 21587.58 | 10065.07 | 6356.65 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.243968E+10 | 0.722200E+09 | 354.92 | 0.213973E+10 | 0.299956E+09 | 0.00 | 1.00 | 02-JAN-16:12 | 0.00 | 01-JAN-00:05 | 23002.06 | 16-JAN-22:51 | 20676.83 | 07-JAN-16:12 | 7616.60 | 21-JAN-09:01 | 5908.59 | 16-JAN-22:51 | 0.00 | 01-JAN-00:05 |
February | 0.240108E+10 | 0.707777E+09 | 335.08 | 0.207275E+10 | 0.328323E+09 | 0.00 | 1.00 | 01-FEB-09:51 | 0.00 | 01-FEB-05:50 | 23461.61 | 13-FEB-19:11 | 21691.98 | 22-FEB-17:01 | 8675.67 | 13-FEB-19:11 | 6005.06 | 13-FEB-19:11 | 0.00 | 01-FEB-00:10 |
March | 0.310640E+10 | 0.911942E+09 | 377.54 | 0.259715E+10 | 0.509251E+09 | 0.00 | 1.00 | 01-MAR-19:02 | 0.00 | 01-MAR-00:10 | 23521.21 | 22-MAR-18:51 | 21428.55 | 11-MAR-18:21 | 7315.89 | 19-MAR-08:61 | 6017.29 | 22-MAR-18:51 | 0.00 | 01-MAR-00:10 |
April | 0.533012E+10 | 0.155844E+10 | 509.00 | 0.442111E+10 | 0.909006E+09 | 0.00 | 1.00 | 01-APR-21:51 | 0.00 | 01-APR-00:10 | 24366.08 | 26-APR-21:51 | 22433.88 | 18-APR-16:51 | 8840.49 | 26-APR-21:54 | 6183.87 | 26-APR-21:51 | 0.00 | 01-APR-00:10 |
May | 0.565914E+10 | 0.165219E+10 | 511.41 | 0.472487E+10 | 0.934270E+09 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 24169.41 | 02-MAY-21:51 | 21516.19 | 10-MAY-17:42 | 8159.56 | 02-MAY-22:02 | 6146.22 | 02-MAY-21:51 | 0.00 | 01-MAY-00:10 |
June | 0.694964E+10 | 0.201212E+10 | 446.00 | 0.557821E+10 | 0.137143E+10 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-06:52 | 25049.96 | 27-JUN-21:51 | 22407.55 | 30-JUN-17:32 | 9966.73 | 27-JUN-21:54 | 6309.45 | 27-JUN-21:51 | 0.00 | 01-JUN-00:10 |
July | 0.935384E+10 | 0.268450E+10 | 441.25 | 0.732915E+10 | 0.202469E+10 | 0.00 | 1.00 | 01-JUL-08:51 | 0.00 | 01-JUL-05:13 | 25517.17 | 28-JUL-21:51 | 21693.99 | 15-JUL-17:52 | 11051.48 | 28-JUL-21:54 | 6406.04 | 19-JUL-08:51 | 0.00 | 01-JUL-00:10 |
August | 0.911849E+10 | 0.262016E+10 | 433.05 | 0.699328E+10 | 0.212521E+10 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-05:15 | 25576.36 | 19-AUG-08:51 | 19345.12 | 19-AUG-15:12 | 10905.93 | 16-AUG-21:54 | 6407.87 | 19-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.717903E+10 | 0.210821E+10 | 444.04 | 0.573664E+10 | 0.144239E+10 | 0.00 | 1.00 | 01-SEP-08:51 | 0.00 | 01-SEP-06:43 | 25432.67 | 22-SEP-08:51 | 21186.68 | 30-SEP-08:61 | 11323.43 | 22-SEP-08:54 | 6376.16 | 22-SEP-08:51 | 0.00 | 01-SEP-00:10 |
October | 0.609915E+10 | 0.181563E+10 | 444.84 | 0.520843E+10 | 0.890722E+09 | 0.00 | 1.00 | 01-OCT-08:51 | 0.00 | 01-OCT-05:13 | 25602.39 | 01-OCT-21:51 | 21564.43 | 15-OCT-21:51 | 11644.12 | 01-OCT-08:53 | 6404.93 | 01-OCT-21:51 | 0.00 | 01-OCT-00:10 |
November | 0.313023E+10 | 0.924795E+09 | 391.17 | 0.270031E+10 | 0.429914E+09 | 0.00 | 1.00 | 01-NOV-19:11 | 0.00 | 01-NOV-06:53 | 23462.57 | 10-NOV-22:11 | 21438.12 | 04-NOV-17:01 | 8068.66 | 11-NOV-20:01 | 6005.26 | 10-NOV-22:11 | 0.00 | 01-NOV-00:10 |
December | 0.240597E+10 | 0.711995E+09 | 347.20 | 0.220918E+10 | 0.196790E+09 | 0.00 | 1.00 | 02-DEC-16:12 | 0.00 | 01-DEC-00:20 | 22738.93 | 08-DEC-16:12 | 20920.68 | 31-DEC-17:01 | 7112.95 | 09-DEC-09:02 | 5851.62 | 08-DEC-16:12 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.631728E+11 | 0.184300E+11 | 5035.51 | 0.517108E+11 | 0.114620E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.240108E+10 | 0.707777E+09 | 335.08 | 0.207275E+10 | 0.196790E+09 | 0.00 | 1.00 | 0.00 | 22738.93 | 19345.12 | 7112.95 | 5851.62 | 0.00 | |||||||
Maximum of Months | 0.935384E+10 | 0.268450E+10 | 511.41 | 0.732915E+10 | 0.212521E+10 | 0.00 | 1.00 | 0.00 | 25602.39 | 22433.88 | 11644.12 | 6407.87 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.479403E+11 | 0.137705E+11 | 479.99 | 0.474434E+11 | 0.496928E+09 | 0.00 | 0.73 | 14-JAN-12:20 | 0.00 | 01-JAN-00:05 | 88294.04 | 14-JAN-12:20 | 88294.04 | 14-JAN-12:20 | 4336.58 | 21-JAN-09:00 | 24828.37 | 14-JAN-12:10 | 0.00 | 01-JAN-00:05 |
February | 0.296565E+11 | 0.857919E+10 | 353.12 | 0.292360E+11 | 0.420431E+09 | 0.00 | 0.61 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 74590.62 | 01-FEB-12:00 | 74590.62 | 01-FEB-12:00 | 4230.67 | 14-FEB-11:25 | 21399.36 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.239095E+11 | 0.696794E+10 | 355.67 | 0.230432E+11 | 0.866255E+09 | 0.00 | 0.53 | 11-MAR-12:50 | 0.00 | 01-MAR-00:10 | 65093.85 | 11-MAR-12:50 | 65093.85 | 11-MAR-12:50 | 3936.78 | 23-MAR-15:10 | 18260.37 | 11-MAR-12:50 | 0.00 | 01-MAR-00:10 |
April | 0.284254E+11 | 0.836760E+10 | 453.94 | 0.270335E+11 | 0.139193E+10 | 0.00 | 0.40 | 08-APR-12:20 | 0.00 | 01-APR-00:10 | 49782.61 | 08-APR-12:20 | 47088.06 | 08-APR-12:20 | 3250.73 | 27-APR-10:25 | 14179.32 | 08-APR-12:20 | 0.00 | 01-APR-00:10 |
May | 0.177279E+11 | 0.528005E+10 | 461.38 | 0.167283E+11 | 0.999569E+09 | 0.00 | 0.29 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 | 35747.50 | 04-MAY-12:00 | 34362.85 | 04-MAY-12:00 | 2802.09 | 06-MAY-08:40 | 10377.59 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 0.244511E+11 | 0.725784E+10 | 526.56 | 0.220280E+11 | 0.242309E+10 | 0.00 | 0.21 | 27-JUN-12:40 | 0.00 | 01-JUN-00:10 | 25979.52 | 28-JUN-12:00 | 22990.43 | 27-JUN-12:40 | 4242.85 | 30-JUN-06:52 | 7598.69 | 28-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 0.380336E+11 | 0.112221E+11 | 597.68 | 0.330452E+11 | 0.498836E+10 | 0.00 | 0.34 | 31-JUL-12:30 | 0.00 | 01-JUL-00:30 | 42202.04 | 31-JUL-12:30 | 37351.09 | 31-JUL-12:30 | 5757.28 | 30-JUL-08:52 | 12916.66 | 31-JUL-12:30 | 0.00 | 01-JUL-00:10 |
August | 0.493766E+11 | 0.144464E+11 | 628.64 | 0.430406E+11 | 0.633607E+10 | 0.00 | 0.39 | 26-AUG-13:00 | 0.00 | 01-AUG-02:00 | 49058.38 | 26-AUG-13:00 | 44475.52 | 26-AUG-13:00 | 6289.09 | 19-AUG-08:52 | 14817.84 | 18-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 0.520423E+11 | 0.153011E+11 | 589.30 | 0.478042E+11 | 0.423808E+10 | 0.00 | 0.79 | 29-SEP-12:50 | 0.00 | 01-SEP-00:10 | 90588.43 | 29-SEP-12:10 | 90588.43 | 29-SEP-12:10 | 6432.09 | 23-SEP-10:25 | 30947.15 | 29-SEP-12:10 | 0.00 | 01-SEP-00:10 |
October | 0.641160E+11 | 0.188323E+11 | 611.38 | 0.614248E+11 | 0.269118E+10 | 0.00 | 0.91 | 16-OCT-11:50 | 0.00 | 03-OCT-02:00 | 104908.42 | 16-OCT-12:00 | 104908.42 | 16-OCT-12:00 | 9030.70 | 01-OCT-11:30 | 35473.63 | 16-OCT-11:30 | 0.00 | 01-OCT-00:10 |
November | 0.485320E+11 | 0.139571E+11 | 491.87 | 0.476840E+11 | 0.847988E+09 | 0.00 | 0.74 | 19-NOV-12:30 | 0.00 | 01-NOV-00:40 | 91999.42 | 19-NOV-12:30 | 91999.42 | 19-NOV-12:30 | 7102.05 | 12-NOV-10:15 | 26121.26 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.530138E+11 | 0.151366E+11 | 484.96 | 0.527228E+11 | 0.291045E+09 | 0.00 | 0.77 | 19-DEC-12:30 | 0.00 | 01-DEC-00:10 | 92378.19 | 19-DEC-12:30 | 92378.19 | 19-DEC-12:30 | 2769.67 | 09-DEC-09:55 | 25743.50 | 19-DEC-12:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.477225E+12 | 0.139119E+12 | 6034.47 | 0.451234E+12 | 0.259909E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.177279E+11 | 0.528005E+10 | 353.12 | 0.167283E+11 | 0.291045E+09 | 0.00 | 0.21 | 0.00 | 25979.52 | 22990.43 | 2769.67 | 7598.69 | 0.00 | |||||||
Maximum of Months | 0.641160E+11 | 0.188323E+11 | 628.64 | 0.614248E+11 | 0.633607E+10 | 0.00 | 0.91 | 0.00 | 104908.42 | 104908.42 | 9030.70 | 35473.63 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.207631E+11 | 0.602090E+10 | 338.44 | 0.174774E+11 | 0.328569E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 118141.55 | 16-JAN-22:51 | 106437.70 | 18-JAN-09:51 | 39803.99 | 20-JAN-19:05 | 30376.94 | 16-JAN-22:51 | 0.00 | 01-JAN-00:05 |
February | 0.205792E+11 | 0.598480E+10 | 342.55 | 0.170109E+11 | 0.356833E+10 | 0.00 | 1.00 | 01-FEB-09:51 | 0.00 | 01-FEB-07:33 | 119277.68 | 13-FEB-19:11 | 106243.55 | 01-FEB-09:51 | 42945.87 | 13-FEB-19:14 | 30620.78 | 13-FEB-19:11 | 0.00 | 01-FEB-00:10 |
March | 0.245623E+11 | 0.711828E+10 | 397.95 | 0.197189E+11 | 0.484339E+10 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:10 | 118143.04 | 23-MAR-19:11 | 107692.84 | 11-MAR-09:51 | 40360.34 | 22-MAR-18:54 | 30377.26 | 23-MAR-19:11 | 0.00 | 01-MAR-00:10 |
April | 0.383205E+11 | 0.110214E+11 | 500.35 | 0.302942E+11 | 0.802629E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:10 | 122890.06 | 26-APR-21:51 | 104798.93 | 01-APR-08:62 | 46379.16 | 26-APR-21:57 | 31366.01 | 26-APR-21:51 | 0.00 | 01-APR-00:10 |
May | 0.446168E+11 | 0.127510E+11 | 509.71 | 0.361091E+11 | 0.850770E+10 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 121566.04 | 02-MAY-21:51 | 107519.53 | 26-MAY-18:01 | 41464.53 | 05-MAY-20:17 | 31098.15 | 02-MAY-21:51 | 0.00 | 01-MAY-00:10 |
June | 0.549808E+11 | 0.154641E+11 | 436.86 | 0.423688E+11 | 0.126121E+11 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-06:52 | 126653.19 | 29-JUN-17:51 | 98620.92 | 13-JUN-08:51 | 51298.11 | 27-JUN-21:57 | 32094.35 | 29-JUN-17:51 | 0.00 | 01-JUN-00:10 |
July | 0.714864E+11 | 0.198410E+11 | 427.17 | 0.524268E+11 | 0.190596E+11 | 0.00 | 1.00 | 01-JUL-08:51 | 0.00 | 01-JUL-05:13 | 130721.77 | 19-JUL-21:51 | 98208.63 | 04-JUL-08:51 | 59586.84 | 19-JUL-21:54 | 32827.47 | 19-JUL-21:51 | 0.00 | 01-JUL-00:10 |
August | 0.695265E+11 | 0.193172E+11 | 423.18 | 0.495144E+11 | 0.200120E+11 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-05:15 | 130594.15 | 19-AUG-08:51 | 93411.53 | 22-AUG-08:51 | 56455.17 | 15-AUG-21:55 | 32844.42 | 19-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.545256E+11 | 0.154946E+11 | 436.81 | 0.412548E+11 | 0.132708E+11 | 0.00 | 1.00 | 01-SEP-08:51 | 0.00 | 01-SEP-06:43 | 132821.44 | 21-SEP-21:51 | 110245.03 | 30-SEP-08:61 | 62600.40 | 21-SEP-21:54 | 33183.92 | 21-SEP-21:51 | 0.00 | 01-SEP-00:10 |
October | 0.498471E+11 | 0.142790E+11 | 453.51 | 0.409398E+11 | 0.890735E+10 | 0.00 | 1.00 | 01-OCT-08:51 | 0.00 | 01-OCT-05:13 | 132289.34 | 04-OCT-20:21 | 110055.72 | 16-OCT-21:51 | 63041.27 | 01-OCT-08:53 | 33095.00 | 04-OCT-20:21 | 0.00 | 01-OCT-00:10 |
November | 0.252998E+11 | 0.732557E+10 | 388.07 | 0.210157E+11 | 0.428420E+10 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-06:53 | 120586.68 | 09-NOV-22:51 | 106464.44 | 19-NOV-09:41 | 44077.68 | 09-NOV-22:56 | 30896.09 | 09-NOV-22:51 | 0.00 | 01-NOV-00:10 |
December | 0.192679E+11 | 0.560191E+10 | 333.16 | 0.171266E+11 | 0.214130E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-03:00 | 116434.54 | 07-DEC-19:02 | 107140.43 | 07-DEC-09:51 | 34704.87 | 07-DEC-19:03 | 30001.95 | 07-DEC-19:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.493776E+12 | 0.140220E+12 | 4987.75 | 0.385257E+12 | 0.108519E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.192679E+11 | 0.560191E+10 | 333.16 | 0.170109E+11 | 0.214130E+10 | 0.00 | 1.00 | 0.00 | 116434.54 | 93411.53 | 34704.87 | 30001.95 | 0.00 | |||||||
Maximum of Months | 0.714864E+11 | 0.198410E+11 | 509.71 | 0.524268E+11 | 0.200120E+11 | 0.00 | 1.00 | 0.00 | 132821.44 | 110245.03 | 63041.27 | 33183.92 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.580230E+10 | 0.168137E+10 | 501.95 | 0.533689E+10 | 0.465413E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 20132.77 | 20-JAN-19:02 | 18575.55 | 07-JAN-16:12 | 5049.30 | 20-JAN-19:02 | 5193.17 | 20-JAN-19:02 | 0.00 | 01-JAN-00:05 |
February | 0.432962E+10 | 0.125595E+10 | 417.15 | 0.391836E+10 | 0.411264E+09 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-05:40 | 20991.66 | 13-FEB-16:12 | 18619.26 | 01-FEB-09:02 | 7286.10 | 13-FEB-16:12 | 5379.85 | 13-FEB-16:12 | 0.00 | 01-FEB-00:10 |
March | 0.507572E+10 | 0.146731E+10 | 451.55 | 0.444982E+10 | 0.625904E+09 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:10 | 20296.21 | 26-MAR-08:62 | 18754.51 | 11-MAR-09:02 | 5457.58 | 16-MAR-15:13 | 5229.86 | 26-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.780768E+10 | 0.225000E+10 | 598.66 | 0.677430E+10 | 0.103339E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:10 | 20585.33 | 15-APR-08:61 | 18599.42 | 01-APR-15:12 | 6452.70 | 22-APR-08:62 | 5293.41 | 15-APR-08:61 | 0.00 | 01-APR-00:10 |
May | 0.717531E+10 | 0.207984E+10 | 623.27 | 0.614302E+10 | 0.103228E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-06:52 | 20503.75 | 09-MAY-15:12 | 18291.72 | 24-MAY-08:62 | 6066.21 | 09-MAY-15:12 | 5275.65 | 09-MAY-15:12 | 0.00 | 01-MAY-00:10 |
June | 0.941538E+10 | 0.271701E+10 | 675.37 | 0.770312E+10 | 0.171226E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-02:50 | 21146.60 | 28-JUN-08:62 | 17791.39 | 12-JUN-15:12 | 7456.21 | 28-JUN-08:62 | 5411.94 | 28-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.131493E+11 | 0.377441E+10 | 726.21 | 0.104834E+11 | 0.266589E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 20975.25 | 20-JUL-18:02 | 17248.15 | 04-JUL-08:62 | 6931.33 | 20-JUL-18:02 | 5376.43 | 20-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 0.140166E+11 | 0.401165E+10 | 725.55 | 0.111026E+11 | 0.291400E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:53 | 21282.45 | 08-AUG-08:62 | 17271.26 | 22-AUG-15:12 | 7734.50 | 08-AUG-08:62 | 5439.68 | 08-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.106897E+11 | 0.310843E+10 | 668.70 | 0.877068E+10 | 0.191907E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:53 | 21408.17 | 23-SEP-08:62 | 18316.25 | 30-SEP-08:61 | 8212.23 | 23-SEP-08:62 | 5481.63 | 29-SEP-09:54 | 0.00 | 01-SEP-00:10 |
October | 0.106032E+11 | 0.310894E+10 | 662.13 | 0.930802E+10 | 0.129518E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:53 | 21683.33 | 01-OCT-08:62 | 18742.37 | 25-OCT-08:62 | 8829.19 | 01-OCT-08:62 | 5519.40 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.611664E+10 | 0.177299E+10 | 524.29 | 0.553716E+10 | 0.579478E+09 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-06:53 | 20485.55 | 11-NOV-16:12 | 18733.71 | 08-NOV-09:02 | 6132.77 | 11-NOV-16:12 | 5271.67 | 11-NOV-16:12 | 0.00 | 01-NOV-00:10 |
December | 0.584055E+10 | 0.168979E+10 | 497.81 | 0.556079E+10 | 0.279765E+09 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:30 | 20459.96 | 08-DEC-09:02 | 18692.38 | 06-DEC-16:12 | 5769.67 | 08-DEC-09:02 | 5266.06 | 08-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.100022E+12 | 0.289177E+11 | 7072.61 | 0.850882E+11 | 0.149339E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.432962E+10 | 0.125595E+10 | 417.15 | 0.391836E+10 | 0.279765E+09 | 0.00 | 1.00 | 0.00 | 20132.77 | 17248.15 | 5049.30 | 5193.17 | 0.00 | |||||||
Maximum of Months | 0.140166E+11 | 0.401165E+10 | 726.21 | 0.111026E+11 | 0.291400E+10 | 0.00 | 1.00 | 0.00 | 21683.33 | 18754.51 | 8829.19 | 5519.40 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.236617E+10 | 0.690071E+09 | 353.73 | 0.206380E+10 | 0.302366E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 20007.77 | 17-JAN-09:51 | 18513.40 | 24-JAN-09:51 | 6858.63 | 20-JAN-19:02 | 5127.61 | 17-JAN-09:51 | 0.00 | 01-JAN-00:05 |
February | 0.212497E+10 | 0.620606E+09 | 323.57 | 0.183235E+10 | 0.292621E+09 | 0.00 | 1.00 | 01-FEB-09:51 | 0.00 | 01-FEB-05:30 | 20074.28 | 13-FEB-19:11 | 18498.50 | 01-FEB-09:51 | 7998.42 | 13-FEB-19:11 | 5141.44 | 13-FEB-19:11 | 0.00 | 01-FEB-00:10 |
March | 0.308518E+10 | 0.897118E+09 | 380.95 | 0.259743E+10 | 0.487743E+09 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:10 | 19868.01 | 23-MAR-19:11 | 19263.62 | 11-MAR-09:32 | 6493.35 | 22-MAR-18:52 | 5098.25 | 23-MAR-19:11 | 0.00 | 01-MAR-00:10 |
April | 0.535625E+10 | 0.154521E+10 | 505.91 | 0.452134E+10 | 0.834911E+09 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:10 | 20619.66 | 27-APR-08:32 | 19614.12 | 13-APR-08:32 | 7481.05 | 26-APR-21:53 | 5251.34 | 27-APR-08:32 | 0.00 | 01-APR-00:10 |
May | 0.536636E+10 | 0.155134E+10 | 510.87 | 0.452033E+10 | 0.846034E+09 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 20748.09 | 03-MAY-08:32 | 19464.15 | 22-MAY-08:32 | 6865.33 | 02-MAY-21:53 | 5276.32 | 03-MAY-08:32 | 0.00 | 01-MAY-00:10 |
June | 0.658711E+10 | 0.188334E+10 | 457.99 | 0.532185E+10 | 0.126526E+10 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-03:50 | 21977.53 | 30-JUN-08:22 | 19217.51 | 13-JUN-08:32 | 8725.58 | 27-JUN-21:54 | 5498.34 | 30-JUN-08:22 | 0.00 | 01-JUN-00:10 |
July | 0.908530E+10 | 0.257777E+10 | 454.91 | 0.714030E+10 | 0.194500E+10 | 0.00 | 1.00 | 01-JUL-08:22 | 0.00 | 01-JUL-05:13 | 22487.88 | 23-JUL-08:22 | 18759.95 | 04-JUL-08:22 | 9811.31 | 28-JUL-21:54 | 5587.35 | 23-JUL-08:22 | 0.00 | 01-JUL-00:10 |
August | 0.909946E+10 | 0.258061E+10 | 451.67 | 0.703380E+10 | 0.206566E+10 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-05:15 | 22842.93 | 19-AUG-08:22 | 18489.80 | 22-AUG-08:32 | 9697.68 | 16-AUG-21:54 | 5636.22 | 19-AUG-08:22 | 0.00 | 01-AUG-00:10 |
September | 0.647108E+10 | 0.188432E+10 | 459.75 | 0.515474E+10 | 0.131633E+10 | 0.00 | 1.00 | 01-SEP-08:51 | 0.00 | 01-SEP-06:43 | 22168.57 | 10-SEP-08:22 | 19323.63 | 30-SEP-07:42 | 9733.48 | 21-SEP-21:54 | 5530.08 | 10-SEP-08:22 | 0.00 | 01-SEP-00:10 |
October | 0.580523E+10 | 0.171837E+10 | 453.85 | 0.498179E+10 | 0.823446E+09 | 0.00 | 1.00 | 01-OCT-08:51 | 0.00 | 01-OCT-05:13 | 21987.67 | 01-OCT-08:51 | 19155.36 | 31-OCT-08:32 | 10154.17 | 01-OCT-08:53 | 5500.04 | 01-OCT-08:51 | 0.00 | 01-OCT-00:10 |
November | 0.271187E+10 | 0.792351E+09 | 387.17 | 0.232004E+10 | 0.391834E+09 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-06:53 | 20177.74 | 10-NOV-09:51 | 19110.29 | 19-NOV-09:22 | 7118.73 | 11-NOV-20:01 | 5162.77 | 10-NOV-09:51 | 0.00 | 01-NOV-00:10 |
December | 0.211681E+10 | 0.618429E+09 | 336.65 | 0.193694E+10 | 0.179869E+09 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 19619.67 | 07-DEC-19:02 | 18718.61 | 07-DEC-09:51 | 6350.20 | 07-DEC-19:02 | 5045.06 | 07-DEC-19:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.601758E+11 | 0.173595E+11 | 5077.03 | 0.494247E+11 | 0.107511E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.211681E+10 | 0.618429E+09 | 323.57 | 0.183235E+10 | 0.179869E+09 | 0.00 | 1.00 | 0.00 | 19619.67 | 18489.80 | 6350.20 | 5045.06 | 0.00 | |||||||
Maximum of Months | 0.909946E+10 | 0.258061E+10 | 510.87 | 0.714030E+10 | 0.206566E+10 | 0.00 | 1.00 | 0.00 | 22842.93 | 19614.12 | 10154.17 | 5636.22 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.119271E+10 | 0.349185E+09 | 381.27 | 0.109892E+10 | 93787880.67 | 0.00 | 1.00 | 02-JAN-16:12 | 0.00 | 01-JAN-00:05 | 6544.23 | 21-JAN-09:01 | 5718.28 | 07-JAN-16:12 | 2433.09 | 21-JAN-09:01 | 1672.64 | 21-JAN-09:01 | 0.00 | 01-JAN-00:05 |
February | 0.959086E+09 | 0.279222E+09 | 308.25 | 0.869782E+09 | 89304582.63 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-00:10 | 6462.40 | 13-FEB-16:12 | 5741.01 | 01-FEB-09:02 | 2395.28 | 14-FEB-09:02 | 1655.83 | 13-FEB-16:12 | 0.00 | 01-FEB-00:10 |
March | 0.114456E+10 | 0.331374E+09 | 339.83 | 0.100610E+10 | 0.138459E+09 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 6457.02 | 18-MAR-08:61 | 5765.38 | 11-MAR-16:12 | 2411.17 | 18-MAR-08:61 | 1654.71 | 18-MAR-08:61 | 0.00 | 01-MAR-00:10 |
April | 0.198571E+10 | 0.571743E+09 | 504.86 | 0.173685E+10 | 0.248861E+09 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-00:10 | 6428.94 | 08-APR-08:61 | 5730.21 | 01-APR-15:12 | 2318.69 | 11-APR-08:62 | 1648.83 | 08-APR-08:61 | 0.00 | 01-APR-00:10 |
May | 0.186224E+10 | 0.539355E+09 | 538.16 | 0.161364E+10 | 0.248594E+09 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-06:52 | 6418.02 | 03-MAY-08:62 | 5693.84 | 26-MAY-18:01 | 1991.04 | 03-MAY-08:62 | 1646.53 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.258916E+10 | 0.746477E+09 | 636.12 | 0.215329E+10 | 0.435865E+09 | 0.00 | 1.00 | 01-JUN-15:12 | 0.00 | 01-JUN-00:30 | 6531.85 | 28-JUN-08:62 | 5585.71 | 12-JUN-15:12 | 2587.79 | 28-JUN-08:62 | 1670.12 | 28-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.358475E+10 | 0.103013E+10 | 705.95 | 0.290446E+10 | 0.680294E+09 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 6649.60 | 24-JUL-08:62 | 5533.31 | 09-JUL-15:11 | 2631.96 | 24-JUL-08:62 | 1693.65 | 24-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.368637E+10 | 0.105862E+10 | 705.98 | 0.295311E+10 | 0.733261E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:53 | 6748.46 | 18-AUG-08:62 | 5493.87 | 22-AUG-15:12 | 2921.38 | 18-AUG-08:62 | 1712.71 | 18-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.285822E+10 | 0.832802E+09 | 657.54 | 0.237133E+10 | 0.486893E+09 | 0.00 | 1.00 | 01-SEP-15:12 | 0.00 | 01-SEP-06:53 | 6725.65 | 22-SEP-08:62 | 5556.19 | 19-SEP-15:12 | 2907.40 | 23-SEP-08:62 | 1708.37 | 22-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.261620E+10 | 0.771391E+09 | 606.19 | 0.229368E+10 | 0.322524E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:53 | 6795.13 | 01-OCT-08:62 | 5768.96 | 12-OCT-18:02 | 3067.87 | 01-OCT-08:62 | 1721.50 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.137854E+10 | 0.402243E+09 | 422.03 | 0.125031E+10 | 0.128227E+09 | 0.00 | 1.00 | 01-NOV-15:12 | 0.00 | 01-NOV-01:30 | 6265.24 | 14-NOV-09:02 | 5756.80 | 19-NOV-09:02 | 2069.81 | 10-NOV-09:02 | 1613.52 | 14-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.124850E+10 | 0.364241E+09 | 382.35 | 0.119187E+10 | 56634903.16 | 0.00 | 1.00 | 02-DEC-16:12 | 0.00 | 01-DEC-00:10 | 6382.66 | 10-DEC-09:01 | 5719.03 | 05-DEC-19:02 | 2117.24 | 10-DEC-09:01 | 1639.02 | 10-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.251061E+11 | 0.727679E+10 | 6188.53 | 0.214433E+11 | 0.366271E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.959086E+09 | 0.279222E+09 | 308.25 | 0.869782E+09 | 56634903.16 | 0.00 | 1.00 | 0.00 | 6265.24 | 5493.87 | 1991.04 | 1613.52 | 0.00 | |||||||
Maximum of Months | 0.368637E+10 | 0.105862E+10 | 705.98 | 0.295311E+10 | 0.733261E+09 | 0.00 | 1.00 | 0.00 | 6795.13 | 5768.96 | 3067.87 | 1721.50 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.415394E+09 | 0.122983E+09 | 234.53 | 0.366195E+09 | 49198490.27 | 0.00 | 1.00 | 02-JAN-16:12 | 0.00 | 01-JAN-00:05 | 6105.57 | 16-JAN-22:51 | 5513.36 | 07-JAN-16:12 | 2193.31 | 21-JAN-09:01 | 1569.28 | 16-JAN-22:51 | 0.00 | 01-JAN-00:05 |
February | 0.424077E+09 | 0.124950E+09 | 220.28 | 0.366707E+09 | 57369239.95 | 0.00 | 1.00 | 01-FEB-09:51 | 0.00 | 01-FEB-00:10 | 6263.81 | 13-FEB-19:11 | 5789.42 | 22-FEB-17:01 | 2563.61 | 13-FEB-19:11 | 1602.54 | 13-FEB-19:11 | 0.00 | 01-FEB-00:10 |
March | 0.621256E+09 | 0.182063E+09 | 274.55 | 0.518984E+09 | 0.102272E+09 | 0.00 | 1.00 | 01-MAR-19:02 | 0.00 | 01-MAR-00:10 | 6270.77 | 22-MAR-18:51 | 5721.74 | 11-MAR-18:21 | 2403.55 | 18-MAR-08:61 | 1603.97 | 22-MAR-18:51 | 0.00 | 01-MAR-00:10 |
April | 0.121747E+10 | 0.355029E+09 | 418.22 | 0.101170E+10 | 0.205770E+09 | 0.00 | 1.00 | 01-APR-21:51 | 0.00 | 01-APR-00:10 | 6517.15 | 26-APR-21:51 | 5858.24 | 18-APR-16:51 | 2346.42 | 26-APR-21:54 | 1652.29 | 26-APR-21:51 | 0.00 | 01-APR-00:10 |
May | 0.130432E+10 | 0.379712E+09 | 446.80 | 0.109157E+10 | 0.212745E+09 | 0.00 | 1.00 | 01-MAY-08:51 | 0.00 | 01-MAY-06:52 | 6455.60 | 02-MAY-21:51 | 5731.77 | 26-MAY-18:01 | 2164.66 | 02-MAY-22:02 | 1640.60 | 02-MAY-21:51 | 0.00 | 01-MAY-00:10 |
June | 0.174908E+10 | 0.505465E+09 | 438.99 | 0.141285E+10 | 0.336235E+09 | 0.00 | 1.00 | 01-JUN-08:51 | 0.00 | 01-JUN-01:40 | 6667.20 | 27-JUN-21:51 | 5978.57 | 30-JUN-17:32 | 2611.91 | 27-JUN-21:54 | 1679.74 | 27-JUN-21:51 | 0.00 | 01-JUN-00:10 |
July | 0.248609E+10 | 0.712970E+09 | 448.67 | 0.197299E+10 | 0.513099E+09 | 0.00 | 1.00 | 01-JUL-08:51 | 0.00 | 01-JUL-05:13 | 6794.47 | 28-JUL-21:51 | 5796.84 | 15-JUL-17:52 | 2901.67 | 28-JUL-21:54 | 1708.47 | 19-JUL-08:51 | 0.00 | 01-JUL-00:10 |
August | 0.239571E+10 | 0.688068E+09 | 438.04 | 0.185923E+10 | 0.536479E+09 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-05:15 | 6836.49 | 19-AUG-08:51 | 5183.35 | 19-AUG-15:12 | 2912.53 | 18-AUG-08:54 | 1710.88 | 19-AUG-08:51 | 0.00 | 01-AUG-00:10 |
September | 0.173982E+10 | 0.512049E+09 | 435.38 | 0.139213E+10 | 0.347698E+09 | 0.00 | 1.00 | 01-SEP-08:51 | 0.00 | 01-SEP-06:43 | 6791.57 | 22-SEP-08:51 | 5589.55 | 30-SEP-08:61 | 3110.78 | 22-SEP-08:53 | 1701.38 | 22-SEP-08:51 | 0.00 | 01-SEP-00:10 |
October | 0.141168E+10 | 0.422099E+09 | 396.42 | 0.120523E+10 | 0.206446E+09 | 0.00 | 1.00 | 01-OCT-08:51 | 0.00 | 01-OCT-05:13 | 6880.34 | 01-OCT-08:51 | 5738.47 | 15-OCT-21:51 | 3333.47 | 01-OCT-08:53 | 1716.20 | 01-OCT-08:51 | 0.00 | 01-OCT-00:10 |
November | 0.563241E+09 | 0.166651E+09 | 295.27 | 0.485155E+09 | 78085228.13 | 0.00 | 1.00 | 01-NOV-19:11 | 0.00 | 01-NOV-03:30 | 6239.21 | 10-NOV-22:11 | 5707.95 | 04-NOV-17:01 | 2321.25 | 11-NOV-09:52 | 1597.48 | 10-NOV-22:11 | 0.00 | 01-NOV-00:10 |
December | 0.408767E+09 | 0.121046E+09 | 232.87 | 0.379640E+09 | 29126961.30 | 0.00 | 1.00 | 02-DEC-16:12 | 0.00 | 01-DEC-00:10 | 5990.95 | 07-DEC-19:02 | 5574.61 | 31-DEC-17:01 | 1989.54 | 08-DEC-16:12 | 1544.21 | 07-DEC-19:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.147369E+11 | 0.429308E+10 | 4280.01 | 0.120624E+11 | 0.267452E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.408767E+09 | 0.121046E+09 | 220.28 | 0.366195E+09 | 29126961.30 | 0.00 | 1.00 | 0.00 | 5990.95 | 5183.35 | 1989.54 | 1544.21 | 0.00 | |||||||
Maximum of Months | 0.248609E+10 | 0.712970E+09 | 448.67 | 0.197299E+10 | 0.536479E+09 | 0.00 | 1.00 | 0.00 | 6880.34 | 5978.57 | 3333.47 | 1716.20 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.125980E+11 | 0.356865E+10 | 505.01 | 0.118153E+11 | 0.782703E+09 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:05 | 27961.60 | 17-JAN-09:02 | 25917.75 | 07-JAN-16:12 | 7234.24 | 16-JAN-19:03 | 7214.90 | 17-JAN-09:02 | 0.00 | 01-JAN-00:05 |
February | 0.836435E+10 | 0.238968E+10 | 410.56 | 0.769586E+10 | 0.668498E+09 | 0.00 | 1.00 | 01-FEB-09:02 | 0.00 | 01-FEB-05:30 | 28990.06 | 13-FEB-16:12 | 25891.89 | 04-FEB-19:02 | 9513.46 | 13-FEB-16:12 | 7440.80 | 13-FEB-16:12 | 0.00 | 01-FEB-00:10 |
March | 0.805133E+10 | 0.230914E+10 | 417.41 | 0.710392E+10 | 0.947411E+09 | 0.00 | 1.00 | 01-MAR-09:02 | 0.00 | 01-MAR-00:10 | 28761.18 | 18-MAR-08:61 | 26100.05 | 10-MAR-16:12 | 8850.05 | 17-MAR-08:62 | 7391.87 | 18-MAR-08:61 | 0.00 | 01-MAR-00:10 |
April | 0.993419E+10 | 0.287367E+10 | 533.10 | 0.850032E+10 | 0.143387E+10 | 0.00 | 1.00 | 01-APR-08:62 | 0.00 | 01-APR-00:10 | 28815.16 | 08-APR-08:61 | 25940.88 | 01-APR-15:12 | 9094.96 | 27-APR-08:62 | 7403.48 | 08-APR-08:61 | 0.00 | 01-APR-00:10 |
May | 0.752924E+10 | 0.220274E+10 | 531.51 | 0.623160E+10 | 0.129764E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-06:52 | 28915.03 | 03-MAY-08:62 | 25218.28 | 26-MAY-15:12 | 9073.60 | 09-MAY-15:12 | 7424.85 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.100575E+11 | 0.293220E+10 | 623.25 | 0.782080E+10 | 0.223673E+10 | 0.00 | 1.00 | 01-JUN-08:62 | 0.00 | 01-JUN-01:40 | 29502.56 | 29-JUN-08:62 | 24540.80 | 12-JUN-15:12 | 11601.25 | 28-JUN-08:62 | 7547.63 | 29-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.148299E+11 | 0.429797E+10 | 692.98 | 0.111655E+11 | 0.366444E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-06:51 | 30134.22 | 24-JUL-08:62 | 24090.93 | 09-JUL-15:11 | 12353.22 | 20-JUL-08:62 | 7674.12 | 24-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.174728E+11 | 0.503172E+10 | 698.65 | 0.132987E+11 | 0.417411E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-06:53 | 30591.83 | 18-AUG-08:62 | 24233.61 | 29-AUG-15:11 | 13389.43 | 18-AUG-08:62 | 7762.21 | 18-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.160160E+11 | 0.463957E+10 | 650.63 | 0.130838E+11 | 0.293229E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-06:53 | 30328.70 | 22-SEP-08:62 | 24932.44 | 29-SEP-08:61 | 12635.92 | 22-SEP-08:62 | 7711.92 | 22-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.177587E+11 | 0.513530E+10 | 641.68 | 0.156806E+11 | 0.207804E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-06:53 | 30503.06 | 01-OCT-08:62 | 26186.44 | 14-OCT-18:01 | 13220.23 | 01-OCT-08:62 | 7745.35 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.126279E+11 | 0.358548E+10 | 525.89 | 0.116608E+11 | 0.967094E+09 | 0.00 | 1.00 | 01-NOV-08:62 | 0.00 | 01-NOV-06:53 | 28613.25 | 10-NOV-09:02 | 25959.06 | 19-NOV-09:02 | 9219.09 | 10-NOV-19:03 | 7359.84 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.132204E+11 | 0.372354E+10 | 504.78 | 0.127112E+11 | 0.509267E+09 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-01:20 | 28473.79 | 09-DEC-09:02 | 26132.45 | 06-DEC-16:12 | 7894.28 | 08-DEC-09:02 | 7329.35 | 09-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.148460E+12 | 0.426897E+11 | 6735.45 | 0.126768E+12 | 0.216921E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.752924E+10 | 0.220274E+10 | 410.56 | 0.623160E+10 | 0.509267E+09 | 0.00 | 1.00 | 0.00 | 27961.60 | 24090.93 | 7234.24 | 7214.90 | 0.00 | |||||||
Maximum of Months | 0.177587E+11 | 0.513530E+10 | 698.65 | 0.156806E+11 | 0.417411E+10 | 0.00 | 1.00 | 0.00 | 30591.83 | 26186.44 | 13389.43 | 7762.21 | 0.00 |
Report: DXReportMonthly
For: PTAC_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.125516E+11 | 0.366380E+10 | 650.57 | 0.913700E+10 | 0.341464E+10 | 0.00 | 0.50 | 18-JAN-13:10 | 0.00 | 01-JAN-00:05 | 15702.93 | 20-JAN-12:00 | 14096.78 | 14-JAN-12:40 | 5114.64 | 20-JAN-09:52 | 4499.72 | 18-JAN-13:00 | 0.00 | 01-JAN-00:05 |
February | 0.960318E+10 | 0.281028E+10 | 570.15 | 0.670837E+10 | 0.289480E+10 | 0.00 | 0.47 | 01-FEB-12:00 | 0.00 | 04-FEB-05:30 | 14517.37 | 01-FEB-12:00 | 12414.23 | 01-FEB-12:00 | 5078.70 | 14-FEB-11:25 | 4241.90 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.102624E+11 | 0.299535E+10 | 594.99 | 0.666759E+10 | 0.359483E+10 | 0.00 | 0.46 | 11-MAR-12:00 | 0.00 | 01-MAR-00:40 | 14742.38 | 11-MAR-11:25 | 12166.98 | 11-MAR-13:20 | 5715.83 | 15-MAR-11:40 | 4155.48 | 11-MAR-11:25 | 0.00 | 01-MAR-00:10 |
April | 0.145224E+11 | 0.424373E+10 | 705.42 | 0.100588E+11 | 0.446361E+10 | 0.00 | 0.41 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 13373.58 | 08-APR-12:00 | 10782.95 | 26-APR-13:00 | 4687.82 | 01-APR-11:00 | 3809.25 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.143581E+11 | 0.420855E+10 | 740.64 | 0.987022E+10 | 0.448785E+10 | 0.00 | 0.37 | 04-MAY-18:03 | 0.00 | 06-MAY-08:62 | 11511.51 | 04-MAY-12:00 | 9171.11 | 04-MAY-12:00 | 3228.71 | 06-MAY-13:00 | 3299.58 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 0.185125E+11 | 0.538571E+10 | 720.00 | 0.128637E+11 | 0.564889E+10 | 0.00 | 0.47 | 29-JUN-18:10 | 0.05 | 12-JUN-06:05 | 15279.97 | 29-JUN-18:10 | 10942.10 | 29-JUN-18:03 | 4339.40 | 29-JUN-18:10 | 4289.23 | 29-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 0.240157E+11 | 0.693451E+10 | 744.00 | 0.164599E+11 | 0.755588E+10 | 0.00 | 0.48 | 18-JUL-18:03 | 0.11 | 17-JUL-06:05 | 15857.80 | 18-JUL-18:03 | 11185.24 | 19-JUL-18:03 | 4923.38 | 30-JUL-09:53 | 4432.18 | 18-JUL-18:03 | 0.00 | 01-JUL-00:10 |
August | 0.254575E+11 | 0.732762E+10 | 744.00 | 0.173103E+11 | 0.814725E+10 | 0.00 | 0.50 | 18-AUG-12:00 | 0.10 | 28-AUG-06:05 | 16033.48 | 18-AUG-12:00 | 12090.15 | 17-AUG-14:10 | 5023.02 | 27-AUG-09:53 | 4766.35 | 18-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 0.213496E+11 | 0.622101E+10 | 720.00 | 0.152162E+11 | 0.613347E+10 | 0.00 | 0.75 | 29-SEP-13:00 | 0.04 | 20-SEP-06:05 | 21948.68 | 29-SEP-13:00 | 21948.68 | 29-SEP-13:00 | 4719.97 | 24-SEP-11:30 | 7515.07 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 0.215801E+11 | 0.632919E+10 | 742.83 | 0.167564E+11 | 0.482374E+10 | 0.00 | 0.81 | 16-OCT-12:00 | 0.00 | 12-OCT-06:05 | 23548.22 | 16-OCT-12:00 | 23548.22 | 16-OCT-12:00 | 5903.79 | 01-OCT-12:00 | 8041.17 | 16-OCT-11:40 | 0.00 | 01-OCT-00:10 |
November | 0.136872E+11 | 0.399696E+10 | 690.51 | 0.101558E+11 | 0.353137E+10 | 0.00 | 0.57 | 19-NOV-13:00 | 0.00 | 03-NOV-06:05 | 17612.38 | 19-NOV-10:53 | 16487.06 | 19-NOV-13:00 | 6211.43 | 13-NOV-09:52 | 5072.86 | 19-NOV-10:53 | 0.00 | 01-NOV-00:10 |
December | 0.128170E+11 | 0.374018E+10 | 666.75 | 0.100210E+11 | 0.279594E+10 | 0.00 | 0.51 | 16-DEC-13:00 | 0.00 | 03-DEC-01:00 | 15764.85 | 16-DEC-12:30 | 14990.31 | 19-DEC-13:00 | 5357.77 | 16-DEC-09:52 | 4568.77 | 16-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.198717E+12 | 0.578569E+11 | 8289.87 | 0.141225E+12 | 0.574923E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.960318E+10 | 0.281028E+10 | 570.15 | 0.666759E+10 | 0.279594E+10 | 0.00 | 0.37 | 0.00 | 11511.51 | 9171.11 | 3228.71 | 3299.58 | 0.00 | |||||||
Maximum of Months | 0.254575E+11 | 0.732762E+10 | 744.00 | 0.173103E+11 | 0.814725E+10 | 0.00 | 0.81 | 0.11 | 23548.22 | 23548.22 | 6211.43 | 8041.17 | 0.00 |
Report: DXReportMonthly
For: PTAC_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.457172E+10 | 0.132258E+10 | 382.86 | 0.357557E+10 | 0.996154E+09 | 0.00 | 0.56 | 18-JAN-13:10 | 0.00 | 01-JAN-00:05 | 10198.92 | 20-JAN-11:25 | 9165.77 | 18-JAN-13:20 | 3754.33 | 20-JAN-09:25 | 2828.85 | 20-JAN-11:25 | 0.00 | 01-JAN-00:05 |
February | 0.358118E+10 | 0.103631E+10 | 336.71 | 0.275987E+10 | 0.821310E+09 | 0.00 | 0.52 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 9302.46 | 18-FEB-12:20 | 7801.40 | 01-FEB-12:10 | 3953.34 | 18-FEB-11:25 | 2630.52 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.423504E+10 | 0.122119E+10 | 367.06 | 0.316651E+10 | 0.106853E+10 | 0.00 | 0.55 | 11-MAR-11:25 | 0.00 | 01-MAR-00:10 | 10003.94 | 11-MAR-11:25 | 8614.17 | 11-MAR-12:50 | 3819.53 | 23-MAR-09:40 | 2785.48 | 11-MAR-11:25 | 0.00 | 01-MAR-00:10 |
April | 0.718052E+10 | 0.207138E+10 | 539.76 | 0.571369E+10 | 0.146683E+10 | 0.00 | 0.57 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 9777.96 | 26-APR-12:30 | 9086.84 | 26-APR-13:00 | 3278.81 | 05-APR-10:35 | 2867.58 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.707405E+10 | 0.205342E+10 | 598.79 | 0.558960E+10 | 0.148445E+10 | 0.00 | 0.53 | 04-MAY-11:50 | 0.00 | 01-MAY-23:40 | 9511.53 | 02-MAY-10:25 | 8425.96 | 04-MAY-12:00 | 2949.85 | 02-MAY-09:40 | 2651.15 | 02-MAY-10:25 | 0.00 | 01-MAY-00:10 |
June | 0.941217E+10 | 0.272492E+10 | 688.00 | 0.750974E+10 | 0.190243E+10 | 0.00 | 0.49 | 27-JUN-12:30 | 0.00 | 01-JUN-02:00 | 8742.33 | 27-JUN-12:30 | 7560.37 | 27-JUN-12:40 | 2813.60 | 01-JUN-09:30 | 2462.98 | 27-JUN-12:30 | 0.00 | 01-JUN-00:10 |
July | 0.122930E+11 | 0.354703E+10 | 741.17 | 0.979096E+10 | 0.250200E+10 | 0.00 | 0.61 | 31-JUL-12:30 | 0.00 | 06-JUL-02:00 | 10665.42 | 31-JUL-12:30 | 9068.89 | 31-JUL-12:30 | 2445.45 | 30-JUL-09:35 | 3160.90 | 31-JUL-12:30 | 0.00 | 01-JUL-00:10 |
August | 0.127629E+11 | 0.367071E+10 | 744.00 | 0.100851E+11 | 0.267781E+10 | 0.00 | 0.61 | 18-AUG-12:00 | 0.01 | 06-AUG-05:00 | 10831.94 | 18-AUG-12:10 | 9177.13 | 18-AUG-12:10 | 2756.72 | 24-AUG-09:50 | 3197.37 | 18-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 0.100951E+11 | 0.293718E+10 | 695.76 | 0.810780E+10 | 0.198732E+10 | 0.00 | 0.85 | 29-SEP-12:50 | 0.00 | 03-SEP-00:40 | 13716.62 | 29-SEP-12:50 | 13716.62 | 29-SEP-12:50 | 3234.71 | 16-SEP-10:25 | 4671.84 | 29-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 0.968862E+10 | 0.284913E+10 | 653.24 | 0.812642E+10 | 0.156220E+10 | 0.00 | 0.85 | 16-OCT-12:00 | 0.00 | 07-OCT-23:05 | 13638.26 | 16-OCT-12:00 | 13638.26 | 16-OCT-12:00 | 3452.38 | 10-OCT-09:30 | 4652.72 | 16-OCT-12:00 | 0.00 | 01-OCT-00:10 |
November | 0.527633E+10 | 0.152507E+10 | 461.73 | 0.419080E+10 | 0.108553E+10 | 0.00 | 0.60 | 19-NOV-12:30 | 0.00 | 01-NOV-03:20 | 10461.34 | 19-NOV-11:25 | 9974.33 | 19-NOV-13:00 | 4371.22 | 12-NOV-10:24 | 3004.10 | 19-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 0.466711E+10 | 0.134933E+10 | 384.42 | 0.382056E+10 | 0.846556E+09 | 0.00 | 0.58 | 19-DEC-12:50 | 0.00 | 01-DEC-00:10 | 9717.47 | 19-DEC-12:40 | 9717.47 | 19-DEC-12:40 | 3530.17 | 02-DEC-10:00 | 2803.60 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.908377E+11 | 0.263082E+11 | 6593.50 | 0.724366E+11 | 0.184011E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.358118E+10 | 0.103631E+10 | 336.71 | 0.275987E+10 | 0.821310E+09 | 0.00 | 0.49 | 0.00 | 8742.33 | 7560.37 | 2445.45 | 2462.98 | 0.00 | |||||||
Maximum of Months | 0.127629E+11 | 0.367071E+10 | 744.00 | 0.100851E+11 | 0.267781E+10 | 0.00 | 0.85 | 0.01 | 13716.62 | 13716.62 | 4371.22 | 4671.84 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_1 COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.174625E+11 | 0.514993E+10 | 269.00 | 0.157333E+11 | 0.172925E+10 | 0.00 | 1.00 | 13-JAN-13:20 | 0.00 | 01-JAN-00:05 | 63760.16 | 14-JAN-12:00 | 63760.16 | 14-JAN-12:00 | 8948.46 | 17-JAN-13:00 | 16653.77 | 14-JAN-12:00 | 0.00 |
February | 0.102182E+11 | 0.310937E+10 | 204.00 | 0.842739E+10 | 0.179081E+10 | 0.00 | 1.00 | 01-FEB-11:35 | 0.00 | 01-FEB-00:10 | 56938.94 | 01-FEB-12:00 | 56938.94 | 01-FEB-12:00 | 15891.63 | 11-FEB-14:00 | 14876.10 | 01-FEB-12:00 | 0.00 |
March | 0.114446E+11 | 0.339351E+10 | 184.67 | 0.887351E+10 | 0.257113E+10 | 0.00 | 1.00 | 11-MAR-12:50 | 0.00 | 01-MAR-00:10 | 52328.67 | 11-MAR-12:50 | 52328.67 | 11-MAR-12:50 | 13101.89 | 23-MAR-15:57 | 13691.18 | 11-MAR-12:50 | 0.00 |
April | 0.245631E+11 | 0.723120E+10 | 326.48 | 0.196394E+11 | 0.492376E+10 | 0.00 | 0.94 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 48386.40 | 26-APR-13:00 | 48386.40 | 26-APR-13:00 | 13118.50 | 26-APR-18:55 | 12868.62 | 26-APR-13:00 | 0.00 |
May | 0.267373E+11 | 0.801916E+10 | 407.33 | 0.207029E+11 | 0.603436E+10 | 0.00 | 0.82 | 04-MAY-12:10 | 0.00 | 01-MAY-01:00 | 40705.33 | 04-MAY-12:10 | 39435.70 | 04-MAY-12:00 | 15207.58 | 05-MAY-15:00 | 11218.27 | 04-MAY-12:10 | 0.00 |
June | 0.505499E+11 | 0.146562E+11 | 604.50 | 0.346365E+11 | 0.159133E+11 | 0.00 | 1.00 | 28-JUN-10:50 | 0.00 | 01-JUN-00:10 | 61776.81 | 29-JUN-18:02 | 39928.97 | 29-JUN-11:00 | 23867.78 | 29-JUN-18:02 | 15767.15 | 29-JUN-18:02 | 0.00 |
July | 0.905107E+11 | 0.248687E+11 | 735.00 | 0.546486E+11 | 0.358621E+11 | 0.00 | 1.00 | 17-JUL-17:03 | 0.00 | 06-JUL-00:10 | 84270.24 | 31-JUL-18:03 | 50899.73 | 31-JUL-12:50 | 40025.96 | 19-JUL-20:10 | 21135.76 | 31-JUL-18:03 | 0.00 |
August | 0.997901E+11 | 0.270381E+11 | 736.50 | 0.584148E+11 | 0.413753E+11 | 0.00 | 1.00 | 06-AUG-09:02 | 0.00 | 24-AUG-01:40 | 76442.87 | 18-AUG-15:10 | 53471.48 | 18-AUG-15:10 | 36833.50 | 18-AUG-18:03 | 19070.68 | 18-AUG-15:10 | 0.00 |
September | 0.680910E+11 | 0.192798E+11 | 665.42 | 0.450342E+11 | 0.230568E+11 | 0.00 | 1.00 | 13-SEP-15:10 | 0.00 | 01-SEP-20:30 | 96844.40 | 29-SEP-13:00 | 96844.40 | 29-SEP-13:00 | 48018.58 | 21-SEP-21:00 | 29156.63 | 29-SEP-13:00 | 0.00 |
October | 0.740130E+11 | 0.204465E+11 | 609.75 | 0.563254E+11 | 0.176877E+11 | 0.00 | 1.00 | 01-OCT-07:40 | 0.00 | 07-OCT-18:40 | 101476.28 | 16-OCT-11:30 | 101476.28 | 16-OCT-11:30 | 39481.64 | 04-OCT-20:22 | 31250.80 | 16-OCT-11:00 | 0.00 |
November | 0.193383E+11 | 0.571646E+10 | 311.93 | 0.165826E+11 | 0.275561E+10 | 0.00 | 1.00 | 18-NOV-11:25 | 0.00 | 01-NOV-00:20 | 71269.64 | 19-NOV-13:00 | 71269.64 | 19-NOV-13:00 | 10932.32 | 20-NOV-13:00 | 18609.70 | 19-NOV-13:00 | 0.00 |
December | 0.203027E+11 | 0.587994E+10 | 273.58 | 0.196538E+11 | 0.648918E+09 | 0.00 | 1.00 | 05-DEC-09:41 | 0.00 | 01-DEC-00:10 | 64087.63 | 19-DEC-13:00 | 64087.63 | 19-DEC-13:00 | 8349.03 | 07-DEC-15:40 | 16739.09 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.513021E+12 | 0.144789E+12 | 5328.16 | 0.358672E+12 | 0.154349E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.102182E+11 | 0.310937E+10 | 184.67 | 0.842739E+10 | 0.648918E+09 | 0.00 | 0.82 | 0.00 | 40705.33 | 39435.70 | 8349.03 | 11218.27 | 0.00 | ||||||
Maximum of Months | 0.997901E+11 | 0.270381E+11 | 736.50 | 0.584148E+11 | 0.413753E+11 | 0.00 | 1.00 | 0.00 | 101476.28 | 101476.28 | 48018.58 | 31250.80 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_6 COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.140425E+11 | 0.414707E+10 | 275.83 | 0.127251E+11 | 0.131742E+10 | 0.00 | 0.97 | 14-JAN-15:00 | 0.00 | 01-JAN-00:05 | 39026.31 | 14-JAN-15:00 | 39026.31 | 14-JAN-15:00 | 6457.04 | 16-JAN-15:40 | 10299.73 | 14-JAN-15:00 | 0.00 |
February | 0.842318E+10 | 0.256941E+10 | 212.08 | 0.690655E+10 | 0.151664E+10 | 0.00 | 0.96 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 38843.14 | 01-FEB-12:00 | 38843.14 | 01-FEB-12:00 | 13997.25 | 11-FEB-14:00 | 10262.05 | 01-FEB-12:00 | 0.00 |
March | 0.959918E+10 | 0.284459E+10 | 192.67 | 0.752459E+10 | 0.207458E+10 | 0.00 | 0.94 | 23-MAR-15:13 | 0.00 | 01-MAR-00:10 | 38184.85 | 23-MAR-15:13 | 35050.52 | 11-MAR-12:30 | 9585.99 | 23-MAR-15:57 | 10084.79 | 23-MAR-15:13 | 0.00 |
April | 0.217171E+11 | 0.631021E+10 | 334.06 | 0.180903E+11 | 0.362677E+10 | 0.00 | 1.00 | 26-APR-12:00 | 0.00 | 01-APR-00:10 | 45800.05 | 30-APR-09:53 | 45800.05 | 30-APR-09:53 | 12062.82 | 30-APR-21:52 | 11964.90 | 30-APR-09:53 | 0.00 |
May | 0.242812E+11 | 0.718558E+10 | 417.50 | 0.199301E+11 | 0.435110E+10 | 0.00 | 0.91 | 04-MAY-12:00 | 0.00 | 01-MAY-01:20 | 36093.69 | 04-MAY-12:00 | 36093.69 | 04-MAY-12:00 | 13338.38 | 05-MAY-15:00 | 9686.85 | 04-MAY-12:00 | 0.00 |
June | 0.475160E+11 | 0.135043E+11 | 612.58 | 0.346396E+11 | 0.128765E+11 | 0.00 | 1.00 | 26-JUN-10:40 | 0.00 | 01-JUN-00:10 | 64510.80 | 29-JUN-18:02 | 39880.88 | 29-JUN-17:03 | 25793.89 | 29-JUN-18:02 | 16451.48 | 29-JUN-18:02 | 0.00 |
July | 0.877419E+11 | 0.235559E+11 | 736.00 | 0.544870E+11 | 0.332549E+11 | 0.00 | 1.00 | 01-JUL-11:00 | 0.00 | 06-JUL-00:20 | 82474.95 | 18-JUL-18:10 | 54082.00 | 19-JUL-15:10 | 37203.34 | 24-JUL-18:20 | 20671.19 | 18-JUL-18:10 | 0.00 |
August | 0.946148E+11 | 0.251125E+11 | 737.50 | 0.559191E+11 | 0.386958E+11 | 0.00 | 1.00 | 02-AUG-14:10 | 0.00 | 24-AUG-01:50 | 77557.00 | 18-AUG-15:20 | 53416.77 | 18-AUG-15:10 | 34150.15 | 18-AUG-18:03 | 19337.32 | 18-AUG-15:20 | 0.00 |
September | 0.607096E+11 | 0.169569E+11 | 668.17 | 0.406504E+11 | 0.200592E+11 | 0.00 | 1.00 | 07-SEP-15:10 | 0.00 | 01-SEP-20:40 | 87847.92 | 21-SEP-21:52 | 75813.37 | 29-SEP-12:50 | 48736.76 | 21-SEP-21:40 | 22763.85 | 29-SEP-12:50 | 0.00 |
October | 0.625569E+11 | 0.171535E+11 | 614.00 | 0.469512E+11 | 0.156057E+11 | 0.00 | 1.00 | 01-OCT-03:30 | 0.00 | 07-OCT-18:50 | 76136.31 | 16-OCT-11:00 | 76136.31 | 16-OCT-11:00 | 38949.31 | 04-OCT-21:05 | 23468.60 | 16-OCT-11:00 | 0.00 |
November | 0.153207E+11 | 0.457065E+10 | 321.00 | 0.129839E+11 | 0.233678E+10 | 0.00 | 1.00 | 19-NOV-09:41 | 0.00 | 01-NOV-00:30 | 46144.98 | 19-NOV-10:53 | 46144.98 | 19-NOV-10:53 | 10108.00 | 09-NOV-22:54 | 12054.80 | 19-NOV-10:53 | 0.00 |
December | 0.152158E+11 | 0.448698E+10 | 280.00 | 0.146750E+11 | 0.540791E+09 | 0.00 | 0.96 | 16-DEC-13:00 | 0.00 | 01-DEC-00:10 | 38929.55 | 16-DEC-13:00 | 38929.55 | 16-DEC-13:00 | 6477.45 | 07-DEC-15:40 | 10279.83 | 16-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.461739E+12 | 0.128398E+12 | 5401.39 | 0.325483E+12 | 0.136256E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.842318E+10 | 0.256941E+10 | 192.67 | 0.690655E+10 | 0.540791E+09 | 0.00 | 0.91 | 0.00 | 36093.69 | 35050.52 | 6457.04 | 9686.85 | 0.00 | ||||||
Maximum of Months | 0.946148E+11 | 0.251125E+11 | 737.50 | 0.559191E+11 | 0.386958E+11 | 0.00 | 1.00 | 0.00 | 87847.92 | 76136.31 | 48736.76 | 23468.60 | 0.00 |
Report: DXReportMonthly
For: VAV_FLR_0 COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.650903E+10 | 0.188450E+10 | 305.87 | 0.499511E+10 | 0.151392E+10 | 0.00 | 0.97 | 17-JAN-20:20 | 0.00 | 01-JAN-00:05 | 25455.12 | 17-JAN-20:20 | 17401.39 | 17-JAN-20:10 | 9600.24 | 25-JAN-21:00 | 6327.02 | 17-JAN-20:20 | 0.00 | 01-JAN-00:05 |
February | 0.188709E+10 | 0.570893E+09 | 165.90 | 0.139637E+10 | 0.490720E+09 | 0.00 | 0.67 | 01-FEB-09:55 | 0.00 | 01-FEB-00:10 | 15371.44 | 01-FEB-09:55 | 15371.44 | 01-FEB-09:55 | 7886.42 | 13-FEB-20:20 | 4465.45 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.191554E+10 | 0.577839E+09 | 124.28 | 0.133607E+10 | 0.579470E+09 | 0.00 | 0.57 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 13602.14 | 23-MAR-14:10 | 11875.77 | 11-MAR-10:53 | 5813.93 | 23-MAR-21:00 | 3907.11 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.637313E+10 | 0.188751E+10 | 282.65 | 0.431272E+10 | 0.206041E+10 | 0.00 | 0.83 | 26-APR-19:20 | 0.00 | 01-APR-00:10 | 20840.91 | 26-APR-19:20 | 14769.93 | 30-APR-09:51 | 11235.73 | 26-APR-21:00 | 5430.30 | 26-APR-19:20 | 0.00 | 01-APR-00:10 |
May | 0.680248E+10 | 0.201911E+10 | 336.31 | 0.441788E+10 | 0.238460E+10 | 0.00 | 0.85 | 04-MAY-19:20 | 0.00 | 01-MAY-00:10 | 21465.49 | 04-MAY-19:20 | 11648.47 | 04-MAY-19:10 | 9989.85 | 04-MAY-19:55 | 5554.51 | 04-MAY-19:20 | 0.00 | 01-MAY-00:10 |
June | 0.155396E+11 | 0.446592E+10 | 495.49 | 0.933798E+10 | 0.620161E+10 | 0.00 | 1.00 | 29-JUN-18:02 | 0.00 | 01-JUN-00:10 | 30311.95 | 29-JUN-18:02 | 16129.49 | 29-JUN-18:02 | 14293.85 | 29-JUN-18:20 | 7398.46 | 29-JUN-18:02 | 0.00 | 01-JUN-00:10 |
July | 0.345769E+11 | 0.942940E+10 | 697.75 | 0.189130E+11 | 0.156639E+11 | 0.00 | 1.00 | 12-JUL-19:05 | 0.00 | 01-JUL-01:10 | 39707.26 | 18-JUL-18:02 | 21927.76 | 18-JUL-18:02 | 21983.48 | 19-JUL-21:00 | 9666.83 | 18-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 0.393680E+11 | 0.106431E+11 | 703.33 | 0.208150E+11 | 0.185531E+11 | 0.00 | 1.00 | 02-AUG-19:10 | 0.00 | 02-AUG-01:10 | 35052.57 | 14-AUG-19:10 | 18223.74 | 19-AUG-17:11 | 18583.65 | 16-AUG-20:00 | 8454.82 | 14-AUG-19:10 | 0.00 | 01-AUG-00:10 |
September | 0.280737E+11 | 0.780316E+10 | 642.46 | 0.163944E+11 | 0.116793E+11 | 0.00 | 1.00 | 07-SEP-19:10 | 0.00 | 01-SEP-01:10 | 46611.64 | 21-SEP-21:00 | 30861.89 | 29-SEP-19:10 | 26979.08 | 21-SEP-21:00 | 11006.92 | 21-SEP-21:00 | 0.00 | 01-SEP-00:10 |
October | 0.316961E+11 | 0.873770E+10 | 624.58 | 0.213952E+11 | 0.103009E+11 | 0.00 | 1.00 | 01-OCT-09:52 | 0.00 | 07-OCT-01:40 | 44203.48 | 04-OCT-20:00 | 27519.22 | 16-OCT-11:00 | 23588.10 | 04-OCT-20:00 | 10504.42 | 04-OCT-20:00 | 0.00 | 01-OCT-00:10 |
November | 0.761041E+10 | 0.222968E+10 | 345.06 | 0.555870E+10 | 0.205170E+10 | 0.00 | 0.93 | 10-NOV-21:00 | 0.00 | 01-NOV-00:20 | 24004.75 | 10-NOV-21:00 | 18655.99 | 19-NOV-09:53 | 12317.42 | 10-NOV-21:00 | 6042.61 | 10-NOV-21:00 | 0.00 | 01-NOV-00:10 |
December | 0.665637E+10 | 0.196649E+10 | 327.57 | 0.609246E+10 | 0.563914E+09 | 0.00 | 0.76 | 05-DEC-09:53 | 0.00 | 01-DEC-00:10 | 17906.48 | 05-DEC-09:58 | 17906.48 | 05-DEC-09:58 | 8291.43 | 07-DEC-21:00 | 5200.86 | 05-DEC-09:58 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.187008E+12 | 0.522153E+11 | 5051.25 | 0.114965E+12 | 0.720436E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.188709E+10 | 0.570893E+09 | 124.28 | 0.133607E+10 | 0.490720E+09 | 0.00 | 0.57 | 0.00 | 13602.14 | 11648.47 | 5813.93 | 3907.11 | 0.00 | |||||||
Maximum of Months | 0.393680E+11 | 0.106431E+11 | 703.33 | 0.213952E+11 | 0.185531E+11 | 0.00 | 1.00 | 0.00 | 46611.64 | 30861.89 | 26979.08 | 11006.92 | 0.00 |
Report: DXReportMonthly
For: PSZ_LAUNDRY COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.470710E+10 | 0.122916E+10 | 189.63 | 0.422720E+10 | 0.479904E+09 | 0.00 | 0.96 | 17-JAN-20:10 | 0.00 | 01-JAN-00:05 | 32812.89 | 17-JAN-20:10 | 24374.87 | 14-JAN-10:51 | 9088.01 | 17-JAN-20:40 | 7495.19 | 17-JAN-20:10 | 0.00 | 01-JAN-00:05 |
February | 0.927033E+09 | 0.247118E+09 | 132.31 | 0.895421E+09 | 31612617.81 | 0.00 | 0.87 | 01-FEB-09:51 | 0.00 | 01-FEB-03:10 | 27979.37 | 01-FEB-09:52 | 27979.37 | 01-FEB-09:52 | 4856.70 | 13-FEB-20:10 | 6897.41 | 01-FEB-10:00 | 0.00 | 01-FEB-00:10 |
March | 0.189778E+10 | 0.500675E+09 | 157.27 | 0.161813E+10 | 0.279652E+09 | 0.00 | 0.78 | 11-MAR-10:51 | 0.00 | 01-MAR-00:10 | 24916.90 | 11-MAR-10:51 | 24916.90 | 11-MAR-10:51 | 6477.17 | 22-MAR-13:00 | 6310.33 | 11-MAR-11:00 | 0.00 | 01-MAR-00:10 |
April | 0.637060E+10 | 0.167575E+10 | 219.77 | 0.518360E+10 | 0.118701E+10 | 0.00 | 0.87 | 26-APR-08:51 | 0.00 | 01-APR-01:40 | 29763.37 | 26-APR-08:51 | 25118.04 | 30-APR-09:51 | 11454.08 | 26-APR-19:10 | 7164.81 | 26-APR-08:51 | 0.00 | 01-APR-00:10 |
May | 0.524360E+10 | 0.140781E+10 | 231.68 | 0.395572E+10 | 0.128788E+10 | 0.00 | 0.80 | 04-MAY-19:10 | 0.00 | 01-MAY-02:70 | 26406.49 | 04-MAY-19:10 | 22856.70 | 04-MAY-12:00 | 11545.23 | 04-MAY-19:10 | 6416.38 | 04-MAY-12:10 | 0.00 | 01-MAY-00:10 |
June | 0.169617E+11 | 0.435702E+10 | 363.93 | 0.114908E+11 | 0.547093E+10 | 0.00 | 1.00 | 29-JUN-17:03 | 0.00 | 01-JUN-00:10 | 52898.36 | 29-JUN-18:08 | 28954.59 | 29-JUN-18:08 | 23943.77 | 29-JUN-18:08 | 12299.65 | 29-JUN-18:08 | 0.00 | 01-JUN-00:10 |
July | 0.354713E+11 | 0.879302E+10 | 469.02 | 0.229043E+11 | 0.125670E+11 | 0.00 | 1.00 | 13-JUL-18:02 | 0.00 | 01-JUL-00:10 | 67756.40 | 18-JUL-18:02 | 37985.41 | 18-JUL-18:02 | 32595.04 | 31-JUL-19:10 | 16200.92 | 18-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 0.390083E+11 | 0.956917E+10 | 480.19 | 0.246153E+11 | 0.143930E+11 | 0.00 | 1.00 | 04-AUG-18:02 | 0.00 | 01-AUG-01:10 | 56019.11 | 14-AUG-19:10 | 32036.21 | 19-AUG-17:13 | 28917.92 | 18-AUG-18:08 | 13091.77 | 14-AUG-18:20 | 0.00 | 01-AUG-00:10 |
September | 0.207281E+11 | 0.533793E+10 | 389.21 | 0.137082E+11 | 0.701992E+10 | 0.00 | 1.00 | 21-SEP-18:50 | 0.00 | 01-SEP-00:10 | 68750.23 | 21-SEP-21:00 | 45242.90 | 29-SEP-20:00 | 39724.22 | 21-SEP-21:00 | 16070.16 | 21-SEP-21:00 | 0.00 | 01-SEP-00:10 |
October | 0.256781E+11 | 0.660273E+10 | 457.18 | 0.190543E+11 | 0.662382E+10 | 0.00 | 1.00 | 01-OCT-10:02 | 0.00 | 01-OCT-00:10 | 65111.43 | 04-OCT-20:00 | 40306.76 | 16-OCT-18:02 | 34579.60 | 04-OCT-20:00 | 15244.70 | 04-OCT-20:00 | 0.00 | 01-OCT-00:10 |
November | 0.330959E+10 | 0.883345E+09 | 196.08 | 0.312535E+10 | 0.184238E+09 | 0.00 | 0.87 | 19-NOV-08:55 | 0.00 | 01-NOV-00:10 | 27937.88 | 19-NOV-09:00 | 27937.88 | 19-NOV-09:00 | 6613.54 | 09-NOV-21:00 | 6890.96 | 19-NOV-09:00 | 0.00 | 01-NOV-00:10 |
December | 0.538105E+10 | 0.142686E+10 | 215.13 | 0.534609E+10 | 34955652.11 | 0.00 | 0.89 | 05-DEC-09:53 | 0.00 | 01-DEC-00:10 | 28284.32 | 05-DEC-09:53 | 28284.32 | 05-DEC-09:53 | 2336.74 | 07-DEC-14:00 | 7222.04 | 05-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.165684E+12 | 0.420306E+11 | 3501.40 | 0.116124E+12 | 0.495599E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.927033E+09 | 0.247118E+09 | 132.31 | 0.895421E+09 | 31612617.81 | 0.00 | 0.78 | 0.00 | 24916.90 | 22856.70 | 2336.74 | 6310.33 | 0.00 | |||||||
Maximum of Months | 0.390083E+11 | 0.956917E+10 | 480.19 | 0.246153E+11 | 0.143930E+11 | 0.00 | 1.00 | 0.00 | 68750.23 | 45242.90 | 39724.22 | 16200.92 | 0.00 |
Report: DXReportMonthly
For: PSZ_CAFE COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.413728E+10 | 0.106042E+10 | 124.71 | 0.386337E+10 | 0.273908E+09 | 0.00 | 1.00 | 13-JAN-12:20 | 0.00 | 01-JAN-00:05 | 28319.95 | 14-JAN-12:10 | 28319.95 | 14-JAN-12:10 | 6141.19 | 20-JAN-12:30 | 7141.46 | 14-JAN-12:00 | 0.00 | 01-JAN-00:05 |
February | 0.174004E+10 | 0.447893E+09 | 65.29 | 0.160422E+10 | 0.135823E+09 | 0.00 | 1.00 | 01-FEB-11:25 | 0.00 | 01-FEB-00:10 | 25128.86 | 01-FEB-12:00 | 25128.86 | 01-FEB-12:00 | 5492.82 | 01-FEB-13:50 | 6222.31 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 |
March | 0.241139E+10 | 0.606264E+09 | 64.25 | 0.194686E+10 | 0.464528E+09 | 0.00 | 0.99 | 11-MAR-12:30 | 0.00 | 01-MAR-00:10 | 22974.57 | 11-MAR-12:30 | 22974.57 | 11-MAR-12:30 | 7584.62 | 22-MAR-13:00 | 5438.59 | 11-MAR-12:30 | 0.00 | 01-MAR-00:10 |
April | 0.445188E+10 | 0.115171E+10 | 131.90 | 0.361961E+10 | 0.832264E+09 | 0.00 | 0.94 | 08-APR-12:00 | 0.00 | 01-APR-00:10 | 22604.39 | 08-APR-12:00 | 19529.09 | 26-APR-13:00 | 5988.88 | 08-APR-12:00 | 5333.32 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.207186E+10 | 0.561007E+09 | 99.38 | 0.166419E+10 | 0.407669E+09 | 0.00 | 0.80 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 | 18148.49 | 04-MAY-12:10 | 15898.73 | 04-MAY-12:00 | 3339.00 | 04-MAY-13:00 | 4529.82 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 0.582065E+10 | 0.154118E+10 | 183.39 | 0.413437E+10 | 0.168629E+10 | 0.00 | 0.82 | 28-JUN-12:10 | 0.00 | 01-JUN-00:10 | 19742.79 | 28-JUN-12:10 | 13543.18 | 25-JUN-12:00 | 7453.82 | 28-JUN-12:10 | 4787.19 | 28-JUN-12:10 | 0.00 | 01-JUN-00:10 |
July | 0.135714E+11 | 0.344807E+10 | 297.50 | 0.905000E+10 | 0.452136E+10 | 0.00 | 1.00 | 31-JUL-11:40 | 0.00 | 01-JUL-00:10 | 26080.88 | 31-JUL-12:30 | 19062.39 | 31-JUL-12:30 | 10641.69 | 30-JUL-09:50 | 6398.78 | 31-JUL-12:30 | 0.00 | 01-JUL-00:10 |
August | 0.174560E+11 | 0.429686E+10 | 304.33 | 0.115165E+11 | 0.593953E+10 | 0.00 | 1.00 | 14-AUG-10:40 | 0.00 | 01-AUG-00:10 | 27539.87 | 18-AUG-12:00 | 20207.85 | 18-AUG-12:00 | 10107.48 | 06-AUG-09:51 | 6805.70 | 18-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 0.124288E+11 | 0.317154E+10 | 240.11 | 0.902723E+10 | 0.340161E+10 | 0.00 | 1.00 | 13-SEP-11:50 | 0.00 | 01-SEP-00:10 | 34708.63 | 29-SEP-12:00 | 34708.63 | 29-SEP-12:00 | 9676.42 | 24-SEP-12:00 | 10959.10 | 29-SEP-11:50 | 0.00 | 01-SEP-00:10 |
October | 0.156427E+11 | 0.404454E+10 | 303.11 | 0.131867E+11 | 0.245591E+10 | 0.00 | 1.00 | 01-OCT-11:00 | 0.00 | 01-OCT-00:10 | 37710.50 | 16-OCT-11:30 | 37710.50 | 16-OCT-11:30 | 14181.22 | 01-OCT-14:10 | 12280.42 | 16-OCT-11:00 | 0.00 | 01-OCT-00:10 |
November | 0.449389E+10 | 0.113405E+10 | 118.71 | 0.410372E+10 | 0.390171E+09 | 0.00 | 1.00 | 18-NOV-11:15 | 0.00 | 01-NOV-00:10 | 29578.78 | 19-NOV-12:30 | 29465.96 | 19-NOV-12:40 | 6959.99 | 10-NOV-13:00 | 7528.48 | 19-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.587891E+10 | 0.145374E+10 | 135.27 | 0.577019E+10 | 0.108725E+09 | 0.00 | 1.00 | 05-DEC-09:41 | 0.00 | 01-DEC-00:10 | 28198.45 | 16-DEC-13:00 | 28198.45 | 16-DEC-13:00 | 6376.40 | 07-DEC-13:00 | 7088.14 | 16-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.901048E+11 | 0.229173E+11 | 2067.95 | 0.694870E+11 | 0.206178E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.174004E+10 | 0.447893E+09 | 64.25 | 0.160422E+10 | 0.108725E+09 | 0.00 | 0.80 | 0.00 | 18148.49 | 13543.18 | 3339.00 | 4529.82 | 0.00 | |||||||
Maximum of Months | 0.174560E+11 | 0.429686E+10 | 304.33 | 0.131867E+11 | 0.593953E+10 | 0.00 | 1.00 | 0.00 | 37710.50 | 37710.50 | 14181.22 | 12280.42 | 0.00 |
Report: DXReportMonthly
For: PSZ_KITCHEN COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.970494E+10 | 0.242511E+10 | 209.83 | 0.843524E+10 | 0.126970E+10 | 0.00 | 1.00 | 13-JAN-11:35 | 0.00 | 01-JAN-00:05 | 38546.86 | 14-JAN-11:40 | 34559.00 | 14-JAN-11:50 | 8603.39 | 17-JAN-13:00 | 9655.63 | 14-JAN-11:40 | 0.00 | 01-JAN-00:05 |
February | 0.463665E+10 | 0.120144E+10 | 149.00 | 0.382944E+10 | 0.807204E+09 | 0.00 | 1.00 | 01-FEB-09:51 | 0.00 | 01-FEB-00:10 | 40297.77 | 01-FEB-11:50 | 34092.76 | 01-FEB-11:50 | 8937.92 | 11-FEB-13:00 | 10002.20 | 01-FEB-11:50 | 0.00 | 01-FEB-00:10 |
March | 0.716968E+10 | 0.177479E+10 | 149.67 | 0.532230E+10 | 0.184738E+10 | 0.00 | 1.00 | 10-MAR-10:51 | 0.00 | 01-MAR-00:10 | 41745.59 | 11-MAR-11:40 | 34338.10 | 11-MAR-11:40 | 12624.80 | 23-MAR-16:00 | 10134.45 | 11-MAR-11:40 | 0.00 | 01-MAR-00:10 |
April | 0.176159E+11 | 0.430282E+10 | 292.00 | 0.134165E+11 | 0.419937E+10 | 0.00 | 1.00 | 01-APR-10:35 | 0.00 | 01-APR-00:10 | 47377.87 | 26-APR-10:40 | 35962.12 | 30-APR-10:40 | 12054.59 | 25-APR-10:40 | 11757.44 | 26-APR-10:40 | 0.00 | 01-APR-00:10 |
May | 0.177091E+11 | 0.436547E+10 | 336.62 | 0.134561E+11 | 0.425296E+10 | 0.00 | 1.00 | 02-MAY-10:40 | 0.00 | 01-MAY-00:10 | 37112.37 | 04-MAY-12:00 | 30753.93 | 04-MAY-12:00 | 9449.26 | 18-MAY-10:40 | 8916.08 | 04-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 0.309913E+11 | 0.742001E+10 | 415.17 | 0.213146E+11 | 0.967662E+10 | 0.00 | 1.00 | 01-JUN-09:40 | 0.00 | 01-JUN-00:10 | 54338.04 | 28-JUN-10:50 | 34719.81 | 29-JUN-10:40 | 21139.85 | 28-JUN-10:40 | 13123.35 | 28-JUN-10:50 | 0.00 | 01-JUN-00:10 |
July | 0.515931E+11 | 0.122716E+11 | 504.83 | 0.322929E+11 | 0.193003E+11 | 0.00 | 1.00 | 01-JUL-07:50 | 0.00 | 01-JUL-00:10 | 56051.67 | 30-JUL-09:50 | 36905.28 | 19-JUL-10:40 | 27182.77 | 29-JUL-10:40 | 13470.60 | 30-JUL-09:50 | 0.00 | 01-JUL-00:10 |
August | 0.550955E+11 | 0.131357E+11 | 510.67 | 0.334253E+11 | 0.216702E+11 | 0.00 | 1.00 | 01-AUG-09:30 | 0.00 | 01-AUG-00:10 | 55444.19 | 26-AUG-10:50 | 37008.26 | 14-AUG-10:40 | 24817.37 | 18-AUG-17:20 | 13475.02 | 14-AUG-10:40 | 0.00 | 01-AUG-00:10 |
September | 0.361346E+11 | 0.872721E+10 | 436.67 | 0.233413E+11 | 0.127933E+11 | 0.00 | 1.00 | 01-SEP-10:15 | 0.00 | 01-SEP-00:10 | 56410.39 | 22-SEP-10:40 | 41992.83 | 29-SEP-10:40 | 31596.86 | 22-SEP-10:40 | 14656.04 | 29-SEP-10:40 | 0.00 | 01-SEP-00:10 |
October | 0.385791E+11 | 0.947542E+10 | 483.67 | 0.279471E+11 | 0.106320E+11 | 0.00 | 1.00 | 01-OCT-07:50 | 0.00 | 01-OCT-00:10 | 56256.94 | 01-OCT-10:40 | 41746.34 | 16-OCT-10:50 | 26046.47 | 01-OCT-09:52 | 14548.98 | 16-OCT-10:40 | 0.00 | 01-OCT-00:10 |
November | 0.977664E+10 | 0.247686E+10 | 237.83 | 0.819241E+10 | 0.158424E+10 | 0.00 | 1.00 | 08-NOV-10:40 | 0.00 | 01-NOV-00:10 | 43434.47 | 19-NOV-11:40 | 35000.80 | 19-NOV-11:50 | 10854.40 | 10-NOV-11:50 | 10886.27 | 19-NOV-11:40 | 0.00 | 01-NOV-00:10 |
December | 0.102384E+11 | 0.254064E+10 | 210.50 | 0.984194E+10 | 0.396419E+09 | 0.00 | 1.00 | 04-DEC-09:51 | 0.00 | 01-DEC-00:10 | 37853.63 | 19-DEC-11:40 | 34021.76 | 19-DEC-11:50 | 7309.96 | 07-DEC-13:00 | 9312.25 | 19-DEC-11:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.289245E+12 | 0.701171E+11 | 3936.45 | 0.200815E+12 | 0.884296E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.463665E+10 | 0.120144E+10 | 149.00 | 0.382944E+10 | 0.396419E+09 | 0.00 | 1.00 | 0.00 | 37112.37 | 30753.93 | 7309.96 | 8916.08 | 0.00 | |||||||
Maximum of Months | 0.550955E+11 | 0.131357E+11 | 510.67 | 0.334253E+11 | 0.216702E+11 | 0.00 | 1.00 | 0.00 | 56410.39 | 41992.83 | 31596.86 | 14656.04 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 984.97 | 717.55 | 267.42 | 1732.51 | 679.28 | 1.17 | 0.00 | 0.00 |
February | 790.60 | 487.68 | 302.92 | 1288.97 | 637.28 | 14.50 | 0.00 | 0.00 |
March | 648.20 | 323.18 | 325.02 | 1030.23 | 662.54 | 21.17 | 0.00 | 0.00 |
April | 565.74 | 240.63 | 325.11 | 935.51 | 527.81 | 10.33 | 0.00 | 0.00 |
May | 391.28 | 63.12 | 328.16 | 529.70 | 465.55 | 1.67 | 0.00 | 0.00 |
June | 338.81 | 30.47 | 308.35 | 465.56 | 350.75 | 0.00 | 0.00 | 0.00 |
July | 363.64 | 55.14 | 308.50 | 580.83 | 305.77 | 0.00 | 0.00 | 0.00 |
August | 478.58 | 172.77 | 305.81 | 877.89 | 325.13 | 0.00 | 0.00 | 0.00 |
September | 637.63 | 331.05 | 306.58 | 1190.94 | 381.23 | 0.00 | 0.00 | 0.00 |
October | 800.26 | 538.25 | 262.01 | 1550.49 | 418.53 | 0.00 | 0.00 | 0.00 |
November | 953.29 | 670.83 | 282.46 | 1674.26 | 611.30 | 5.17 | 0.00 | 0.00 |
December | 1051.32 | 795.15 | 256.17 | 1865.24 | 679.32 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 666.48 | 368.40 | 298.09 | 1143.16 | 503.00 | 55.17 | 0.00 | 0.00 |
Minimum of Months | 338.81 | 30.47 | 256.17 | 465.56 | 305.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1051.32 | 795.15 | 328.16 | 1865.24 | 679.32 | 21.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2773.61 | 2020.57 | 753.04 | 4795.92 | 2121.45 | 1.17 | 0.00 | 0.00 |
February | 2226.28 | 1373.28 | 853.00 | 3532.11 | 2073.29 | 22.67 | 0.00 | 0.00 |
March | 1825.29 | 910.05 | 915.24 | 2798.57 | 2098.48 | 24.00 | 0.00 | 0.00 |
April | 1593.07 | 677.60 | 915.48 | 2526.83 | 1744.14 | 10.83 | 0.00 | 0.00 |
May | 1101.82 | 177.74 | 924.08 | 1353.06 | 1574.30 | 3.83 | 0.00 | 0.00 |
June | 954.08 | 85.80 | 868.28 | 1174.61 | 1210.15 | 0.00 | 0.00 | 0.00 |
July | 1023.99 | 155.26 | 868.73 | 1530.31 | 1031.81 | 0.00 | 0.00 | 0.00 |
August | 1347.65 | 486.52 | 861.13 | 2380.12 | 1084.82 | 0.00 | 0.00 | 0.00 |
September | 1795.53 | 932.22 | 863.31 | 3259.57 | 1279.08 | 0.50 | 0.00 | 0.00 |
October | 2253.48 | 1515.68 | 737.80 | 4270.68 | 1380.06 | 0.00 | 0.00 | 0.00 |
November | 2684.40 | 1889.02 | 795.38 | 4619.16 | 1972.28 | 6.33 | 0.00 | 0.00 |
December | 2960.44 | 2239.09 | 721.34 | 5168.15 | 2126.47 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 1876.78 | 1037.38 | 839.40 | 3116.45 | 1638.80 | 70.50 | 0.00 | 0.00 |
Minimum of Months | 954.08 | 85.80 | 721.34 | 1174.61 | 1031.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2960.44 | 2239.09 | 924.08 | 5168.15 | 2126.47 | 24.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3603.08 | 2624.84 | 978.25 | 6430.12 | 2882.57 | 1.17 | 0.00 | 0.00 |
February | 2892.06 | 1783.97 | 1108.10 | 4770.97 | 2783.69 | 21.00 | 0.00 | 0.00 |
March | 2371.15 | 1182.20 | 1188.95 | 3810.20 | 2880.31 | 24.00 | 0.00 | 0.00 |
April | 2069.49 | 880.24 | 1189.26 | 3488.73 | 2305.74 | 10.83 | 0.00 | 0.00 |
May | 1431.33 | 230.90 | 1200.43 | 1949.72 | 2078.37 | 3.17 | 0.00 | 0.00 |
June | 1239.40 | 111.45 | 1127.95 | 1718.09 | 1577.12 | 0.00 | 0.00 | 0.00 |
July | 1330.23 | 201.70 | 1128.53 | 2179.90 | 1347.23 | 0.00 | 0.00 | 0.00 |
August | 1750.68 | 632.02 | 1118.66 | 3289.17 | 1413.85 | 0.00 | 0.00 | 0.00 |
September | 2332.50 | 1211.01 | 1121.49 | 4440.23 | 1660.14 | 0.50 | 0.00 | 0.00 |
October | 2927.40 | 1968.95 | 958.45 | 5770.79 | 1796.26 | 0.00 | 0.00 | 0.00 |
November | 3487.19 | 2453.95 | 1033.24 | 6213.47 | 2615.74 | 5.67 | 0.00 | 0.00 |
December | 3845.78 | 2908.71 | 937.07 | 6919.67 | 2881.58 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 2438.04 | 1347.61 | 1090.42 | 4247.23 | 2181.89 | 67.50 | 0.00 | 0.00 |
Minimum of Months | 1239.40 | 111.45 | 937.07 | 1718.09 | 1347.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3845.78 | 2908.71 | 1200.43 | 6919.67 | 2882.57 | 24.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.81 | 130.98 | 48.83 | 346.53 | 152.82 | 1.17 | 0.00 | 0.00 |
February | 144.35 | 89.04 | 55.31 | 247.72 | 147.70 | 20.67 | 0.00 | 0.00 |
March | 118.39 | 59.05 | 59.34 | 196.81 | 156.63 | 22.33 | 0.00 | 0.00 |
April | 103.36 | 44.01 | 59.36 | 180.12 | 120.41 | 3.00 | 0.00 | 0.00 |
May | 71.48 | 11.56 | 59.91 | 95.63 | 109.34 | 0.33 | 0.00 | 0.00 |
June | 61.89 | 5.59 | 56.30 | 87.34 | 76.77 | 0.00 | 0.00 | 0.00 |
July | 66.44 | 10.11 | 56.33 | 116.28 | 62.01 | 0.00 | 0.00 | 0.00 |
August | 87.45 | 31.61 | 55.83 | 177.43 | 64.83 | 0.00 | 0.00 | 0.00 |
September | 116.49 | 60.52 | 55.98 | 238.28 | 77.81 | 0.00 | 0.00 | 0.00 |
October | 146.13 | 98.30 | 47.84 | 312.87 | 85.66 | 0.00 | 0.00 | 0.00 |
November | 174.03 | 122.46 | 51.57 | 331.67 | 136.05 | 4.50 | 0.00 | 0.00 |
December | 191.92 | 145.15 | 46.77 | 371.78 | 152.26 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.71 | 67.29 | 54.42 | 225.19 | 111.66 | 54.33 | 0.00 | 0.00 |
Minimum of Months | 61.89 | 5.59 | 46.77 | 87.34 | 62.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 191.92 | 145.15 | 59.91 | 371.78 | 156.63 | 22.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.97 | 67.99 | 65.97 | 197.20 | 311.93 | 1.17 | 0.00 | 0.00 |
February | 158.55 | 73.07 | 85.48 | 217.09 | 291.43 | 20.50 | 0.00 | 0.00 |
March | 181.00 | 79.54 | 101.46 | 257.90 | 296.03 | 22.50 | 0.00 | 0.00 |
April | 249.35 | 129.05 | 120.29 | 428.05 | 214.60 | 3.00 | 0.00 | 0.00 |
May | 245.02 | 112.41 | 132.61 | 402.53 | 190.77 | 0.33 | 0.00 | 0.00 |
June | 259.27 | 128.76 | 130.51 | 472.51 | 131.74 | 0.00 | 0.00 | 0.00 |
July | 274.60 | 146.13 | 128.47 | 548.92 | 106.87 | 0.00 | 0.00 | 0.00 |
August | 257.61 | 138.86 | 118.76 | 520.25 | 114.13 | 0.00 | 0.00 | 0.00 |
September | 220.80 | 117.57 | 103.23 | 419.64 | 139.61 | 0.00 | 0.00 | 0.00 |
October | 170.18 | 93.10 | 77.08 | 334.77 | 167.54 | 0.00 | 0.00 | 0.00 |
November | 153.81 | 80.69 | 73.12 | 237.76 | 273.18 | 4.83 | 0.00 | 0.00 |
December | 135.89 | 73.10 | 62.80 | 206.81 | 312.01 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 203.51 | 103.49 | 100.03 | 354.35 | 212.09 | 54.67 | 0.00 | 0.00 |
Minimum of Months | 133.97 | 67.99 | 62.80 | 197.20 | 106.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 274.60 | 146.13 | 132.61 | 548.92 | 312.01 | 22.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.76 | 0.00 | 27.76 | 18.27 | 172.28 | 1.17 | 0.00 | 0.00 |
February | 34.85 | 0.00 | 34.85 | 18.18 | 163.17 | 22.17 | 0.00 | 0.00 |
March | 42.71 | 0.00 | 42.71 | 28.41 | 167.98 | 23.33 | 0.00 | 0.00 |
April | 49.67 | 0.61 | 49.06 | 41.92 | 128.83 | 3.17 | 0.00 | 0.00 |
May | 60.53 | 4.13 | 56.40 | 50.38 | 108.76 | 0.00 | 0.00 | 0.00 |
June | 64.73 | 7.89 | 56.84 | 69.39 | 82.87 | 0.00 | 0.00 | 0.00 |
July | 61.30 | 6.63 | 54.67 | 79.15 | 74.01 | 0.00 | 0.00 | 0.00 |
August | 50.17 | 1.60 | 48.57 | 65.28 | 82.41 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 0.02 | 41.92 | 51.61 | 96.13 | 0.00 | 0.00 | 0.00 |
October | 33.26 | 0.00 | 33.26 | 49.94 | 104.79 | 0.00 | 0.00 | 0.00 |
November | 30.11 | 0.00 | 30.11 | 21.07 | 154.05 | 4.83 | 0.00 | 0.00 |
December | 25.84 | 0.00 | 25.84 | 16.30 | 172.42 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 43.61 | 1.75 | 41.86 | 42.65 | 125.45 | 57.00 | 0.00 | 0.00 |
Minimum of Months | 25.84 | 0.00 | 25.84 | 16.30 | 74.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.73 | 7.89 | 56.84 | 79.15 | 172.42 | 23.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.97 | 67.99 | 65.97 | 209.13 | 309.88 | 1.17 | 0.00 | 0.00 |
February | 158.55 | 73.07 | 85.48 | 224.67 | 289.52 | 22.00 | 0.00 | 0.00 |
March | 181.00 | 79.54 | 101.46 | 260.49 | 296.19 | 23.33 | 0.00 | 0.00 |
April | 249.35 | 129.05 | 120.29 | 414.32 | 224.91 | 3.17 | 0.00 | 0.00 |
May | 245.02 | 112.41 | 132.61 | 381.01 | 203.62 | 0.00 | 0.00 | 0.00 |
June | 259.27 | 128.76 | 130.51 | 437.12 | 156.53 | 0.00 | 0.00 | 0.00 |
July | 274.60 | 146.13 | 128.47 | 511.83 | 137.76 | 0.00 | 0.00 | 0.00 |
August | 257.61 | 138.86 | 118.76 | 492.39 | 146.84 | 0.00 | 0.00 | 0.00 |
September | 220.80 | 117.57 | 103.23 | 405.89 | 162.75 | 0.00 | 0.00 | 0.00 |
October | 170.18 | 93.10 | 77.08 | 332.81 | 186.10 | 0.00 | 0.00 | 0.00 |
November | 153.81 | 80.69 | 73.12 | 247.52 | 273.97 | 4.67 | 0.00 | 0.00 |
December | 135.89 | 73.10 | 62.80 | 218.60 | 309.71 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 203.51 | 103.49 | 100.03 | 345.29 | 224.51 | 56.67 | 0.00 | 0.00 |
Minimum of Months | 133.97 | 67.99 | 62.80 | 209.13 | 137.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 274.60 | 146.13 | 132.61 | 511.83 | 309.88 | 23.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 143.82 | 104.77 | 39.05 | 247.31 | 181.12 | 0.33 | 0.00 | 0.00 |
February | 115.46 | 71.22 | 44.24 | 171.53 | 180.85 | 2.50 | 0.00 | 0.00 |
March | 94.70 | 47.23 | 47.46 | 133.19 | 183.86 | 11.50 | 0.00 | 0.00 |
April | 82.68 | 35.20 | 47.48 | 119.62 | 150.34 | 1.83 | 0.00 | 0.00 |
May | 57.17 | 9.25 | 47.92 | 54.13 | 141.15 | 0.00 | 0.00 | 0.00 |
June | 49.50 | 4.47 | 45.03 | 45.40 | 109.49 | 0.00 | 0.00 | 0.00 |
July | 53.14 | 8.09 | 45.05 | 66.69 | 94.15 | 0.00 | 0.00 | 0.00 |
August | 69.94 | 25.28 | 44.66 | 115.23 | 99.47 | 0.00 | 0.00 | 0.00 |
September | 93.17 | 48.40 | 44.77 | 163.65 | 113.23 | 0.00 | 0.00 | 0.00 |
October | 116.88 | 78.62 | 38.26 | 220.74 | 121.67 | 0.00 | 0.00 | 0.00 |
November | 139.20 | 97.95 | 41.25 | 235.17 | 167.25 | 0.67 | 0.00 | 0.00 |
December | 153.50 | 116.10 | 37.41 | 266.53 | 181.08 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 97.35 | 53.82 | 43.53 | 153.25 | 143.43 | 18.00 | 0.00 | 0.00 |
Minimum of Months | 49.50 | 4.47 | 37.41 | 45.40 | 94.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.50 | 116.10 | 47.92 | 266.53 | 183.86 | 11.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.21 | 0.00 | 22.21 | 16.22 | 139.04 | 1.17 | 0.00 | 0.00 |
February | 27.88 | 0.00 | 27.88 | 16.46 | 130.79 | 11.50 | 0.00 | 0.00 |
March | 34.17 | 0.00 | 34.17 | 25.72 | 133.47 | 16.17 | 0.00 | 0.00 |
April | 39.74 | 0.49 | 39.26 | 40.28 | 94.48 | 2.00 | 0.00 | 0.00 |
May | 48.43 | 3.30 | 45.12 | 50.08 | 82.06 | 0.00 | 0.00 | 0.00 |
June | 51.79 | 6.32 | 45.48 | 68.70 | 60.26 | 0.00 | 0.00 | 0.00 |
July | 49.05 | 5.30 | 43.75 | 77.16 | 52.20 | 0.00 | 0.00 | 0.00 |
August | 40.14 | 1.28 | 38.86 | 62.80 | 55.91 | 0.00 | 0.00 | 0.00 |
September | 33.56 | 0.01 | 33.54 | 47.70 | 67.01 | 0.00 | 0.00 | 0.00 |
October | 26.61 | 0.00 | 26.61 | 44.22 | 79.36 | 0.00 | 0.00 | 0.00 |
November | 24.09 | 0.00 | 24.09 | 19.13 | 122.23 | 1.83 | 0.00 | 0.00 |
December | 20.68 | 0.00 | 20.68 | 14.66 | 138.94 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 34.89 | 1.40 | 33.49 | 40.42 | 96.14 | 35.00 | 0.00 | 0.00 |
Minimum of Months | 20.68 | 0.00 | 20.68 | 14.66 | 52.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.79 | 6.32 | 45.48 | 77.16 | 139.04 | 16.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.38 | 75.34 | 65.04 | 205.18 | 297.71 | 1.17 | 0.00 | 0.00 |
February | 147.44 | 67.50 | 79.94 | 188.42 | 281.18 | 21.50 | 0.00 | 0.00 |
March | 178.92 | 79.39 | 99.53 | 251.93 | 284.13 | 23.50 | 0.00 | 0.00 |
April | 228.51 | 114.27 | 114.24 | 391.89 | 206.59 | 4.17 | 0.00 | 0.00 |
May | 215.40 | 89.44 | 125.96 | 353.11 | 185.92 | 0.17 | 0.00 | 0.00 |
June | 214.79 | 93.21 | 121.59 | 394.17 | 132.19 | 0.00 | 0.00 | 0.00 |
July | 242.93 | 120.49 | 122.44 | 494.71 | 107.99 | 0.00 | 0.00 | 0.00 |
August | 239.70 | 127.03 | 112.67 | 494.35 | 112.58 | 0.00 | 0.00 | 0.00 |
September | 175.65 | 80.84 | 94.82 | 332.40 | 137.88 | 0.00 | 0.00 | 0.00 |
October | 154.63 | 79.31 | 75.32 | 300.06 | 158.66 | 0.00 | 0.00 | 0.00 |
November | 141.19 | 71.70 | 69.48 | 205.31 | 263.40 | 5.00 | 0.00 | 0.00 |
December | 136.30 | 76.42 | 59.89 | 194.52 | 297.05 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 184.90 | 89.75 | 95.15 | 318.08 | 205.04 | 57.83 | 0.00 | 0.00 |
Minimum of Months | 136.30 | 67.50 | 59.89 | 188.42 | 107.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.93 | 127.03 | 125.96 | 494.71 | 297.71 | 23.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.81 | 130.98 | 48.83 | 344.12 | 151.85 | 1.17 | 0.00 | 0.00 |
February | 144.35 | 89.04 | 55.31 | 246.30 | 146.01 | 21.67 | 0.00 | 0.00 |
March | 118.39 | 59.05 | 59.34 | 194.60 | 155.07 | 23.67 | 0.00 | 0.00 |
April | 103.36 | 44.01 | 59.36 | 177.84 | 117.77 | 4.17 | 0.00 | 0.00 |
May | 71.48 | 11.56 | 59.91 | 94.21 | 106.90 | 0.33 | 0.00 | 0.00 |
June | 61.89 | 5.59 | 56.30 | 86.22 | 73.76 | 0.00 | 0.00 | 0.00 |
July | 66.44 | 10.11 | 56.33 | 114.39 | 59.10 | 0.00 | 0.00 | 0.00 |
August | 87.45 | 31.61 | 55.83 | 175.38 | 62.28 | 0.00 | 0.00 | 0.00 |
September | 116.49 | 60.52 | 55.98 | 237.96 | 75.04 | 0.00 | 0.00 | 0.00 |
October | 146.13 | 98.30 | 47.84 | 311.71 | 84.12 | 0.00 | 0.00 | 0.00 |
November | 174.03 | 122.46 | 51.57 | 330.38 | 134.39 | 4.83 | 0.00 | 0.00 |
December | 191.92 | 145.15 | 46.77 | 369.79 | 150.95 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 121.71 | 67.29 | 54.42 | 223.56 | 109.58 | 58.17 | 0.00 | 0.00 |
Minimum of Months | 61.89 | 5.59 | 46.77 | 86.22 | 59.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 191.92 | 145.15 | 59.91 | 369.79 | 155.07 | 23.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.76 | 0.00 | 27.76 | 15.55 | 171.57 | 1.33 | 0.00 | 0.00 |
February | 34.85 | 0.00 | 34.85 | 15.88 | 160.32 | 22.17 | 0.00 | 0.00 |
March | 42.71 | 0.00 | 42.71 | 25.77 | 164.59 | 24.50 | 0.00 | 0.00 |
April | 49.67 | 0.61 | 49.06 | 39.42 | 118.74 | 5.33 | 0.00 | 0.00 |
May | 60.53 | 4.13 | 56.40 | 50.94 | 101.41 | 0.67 | 0.00 | 0.00 |
June | 64.73 | 7.89 | 56.84 | 72.27 | 74.20 | 0.00 | 0.00 | 0.00 |
July | 61.30 | 6.63 | 54.67 | 79.16 | 65.30 | 0.00 | 0.00 | 0.00 |
August | 50.17 | 1.60 | 48.57 | 62.45 | 71.91 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 0.02 | 41.92 | 50.24 | 84.31 | 0.00 | 0.00 | 0.00 |
October | 33.26 | 0.00 | 33.26 | 48.04 | 99.21 | 0.00 | 0.00 | 0.00 |
November | 30.11 | 0.00 | 30.11 | 18.67 | 151.20 | 5.33 | 0.00 | 0.00 |
December | 25.84 | 0.00 | 25.84 | 13.70 | 171.35 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 43.61 | 1.75 | 41.86 | 41.17 | 119.31 | 61.67 | 0.00 | 0.00 |
Minimum of Months | 25.84 | 0.00 | 25.84 | 13.70 | 65.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.73 | 7.89 | 56.84 | 79.16 | 171.57 | 24.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 140.38 | 75.34 | 65.04 | 212.86 | 293.17 | 1.33 | 0.00 | 0.00 |
February | 147.44 | 67.50 | 79.94 | 194.98 | 277.63 | 22.17 | 0.00 | 0.00 |
March | 178.92 | 79.39 | 99.53 | 256.57 | 283.12 | 24.50 | 0.00 | 0.00 |
April | 228.51 | 114.27 | 114.24 | 390.37 | 213.15 | 5.50 | 0.00 | 0.00 |
May | 215.40 | 89.44 | 125.96 | 343.30 | 195.74 | 0.67 | 0.00 | 0.00 |
June | 214.79 | 93.21 | 121.59 | 373.35 | 151.64 | 0.00 | 0.00 | 0.00 |
July | 242.93 | 120.49 | 122.44 | 466.17 | 133.04 | 0.00 | 0.00 | 0.00 |
August | 239.70 | 127.03 | 112.67 | 470.34 | 136.42 | 0.00 | 0.00 | 0.00 |
September | 175.65 | 80.84 | 94.82 | 325.66 | 152.54 | 0.00 | 0.00 | 0.00 |
October | 154.63 | 79.31 | 75.32 | 299.83 | 172.99 | 0.00 | 0.00 | 0.00 |
November | 141.19 | 71.70 | 69.48 | 211.63 | 261.02 | 5.17 | 0.00 | 0.00 |
December | 136.30 | 76.42 | 59.89 | 201.18 | 292.00 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 184.90 | 89.75 | 95.15 | 313.01 | 213.22 | 61.67 | 0.00 | 0.00 |
Minimum of Months | 136.30 | 67.50 | 59.89 | 194.98 | 133.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 242.93 | 127.03 | 125.96 | 470.34 | 293.17 | 24.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.73 | 0.00 | 43.73 | 21.33 | 270.62 | 240.50 | 0.00 | 0.00 |
February | 54.89 | 0.00 | 54.89 | 22.50 | 259.06 | 284.83 | 0.00 | 0.00 |
March | 67.27 | 0.00 | 67.27 | 38.98 | 259.35 | 342.67 | 0.00 | 0.00 |
April | 78.24 | 0.95 | 77.29 | 64.75 | 185.20 | 116.67 | 0.00 | 0.00 |
May | 95.32 | 6.48 | 88.84 | 84.34 | 159.20 | 85.00 | 0.00 | 0.00 |
June | 101.94 | 12.40 | 89.54 | 121.23 | 113.98 | 7.67 | 0.00 | 0.00 |
July | 96.54 | 10.41 | 86.13 | 136.37 | 96.24 | 0.00 | 0.00 | 0.00 |
August | 79.03 | 2.51 | 76.51 | 107.62 | 104.69 | 0.00 | 0.00 | 0.00 |
September | 66.06 | 0.02 | 66.04 | 78.17 | 130.50 | 4.67 | 0.00 | 0.00 |
October | 52.39 | 0.00 | 52.39 | 69.31 | 153.23 | 46.83 | 0.00 | 0.00 |
November | 47.43 | 0.00 | 47.43 | 26.02 | 241.11 | 152.17 | 0.00 | 0.00 |
December | 40.71 | 0.00 | 40.71 | 18.55 | 271.66 | 220.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.69 | 2.75 | 65.94 | 66.04 | 186.69 | 1501.00 | 0.00 | 0.00 |
Minimum of Months | 40.71 | 0.00 | 40.71 | 18.55 | 96.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.94 | 12.40 | 89.54 | 136.37 | 271.66 | 342.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.12 | 0.00 | 16.12 | 7.86 | 99.76 | 240.50 | 0.00 | 0.00 |
February | 20.24 | 0.00 | 20.24 | 8.29 | 95.50 | 284.83 | 0.00 | 0.00 |
March | 24.80 | 0.00 | 24.80 | 14.37 | 95.61 | 342.67 | 0.00 | 0.00 |
April | 28.84 | 0.35 | 28.49 | 23.87 | 68.27 | 116.67 | 0.00 | 0.00 |
May | 35.14 | 2.39 | 32.75 | 31.09 | 58.69 | 85.00 | 0.00 | 0.00 |
June | 37.58 | 4.57 | 33.01 | 44.69 | 42.02 | 7.67 | 0.00 | 0.00 |
July | 35.59 | 3.84 | 31.75 | 50.27 | 35.48 | 0.00 | 0.00 | 0.00 |
August | 29.13 | 0.93 | 28.21 | 39.67 | 38.59 | 0.00 | 0.00 | 0.00 |
September | 24.35 | 0.01 | 24.34 | 28.82 | 48.11 | 4.67 | 0.00 | 0.00 |
October | 19.31 | 0.00 | 19.31 | 25.55 | 56.49 | 46.83 | 0.00 | 0.00 |
November | 17.49 | 0.00 | 17.49 | 9.59 | 88.88 | 152.17 | 0.00 | 0.00 |
December | 15.01 | 0.00 | 15.01 | 6.84 | 100.15 | 220.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.32 | 1.01 | 24.31 | 24.35 | 68.82 | 1501.00 | 0.00 | 0.00 |
Minimum of Months | 15.01 | 0.00 | 15.01 | 6.84 | 35.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 37.58 | 4.57 | 33.01 | 50.27 | 100.15 | 342.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.37 | 76.03 | 28.34 | 182.48 | 87.81 | 190.00 | 0.00 | 0.00 |
February | 83.78 | 51.68 | 32.10 | 131.06 | 86.83 | 247.83 | 0.00 | 0.00 |
March | 68.69 | 34.25 | 34.44 | 104.00 | 90.47 | 307.00 | 0.00 | 0.00 |
April | 59.95 | 25.50 | 34.45 | 95.73 | 69.79 | 119.67 | 0.00 | 0.00 |
May | 41.46 | 6.69 | 34.77 | 50.83 | 64.02 | 95.67 | 0.00 | 0.00 |
June | 35.90 | 3.23 | 32.67 | 46.07 | 46.63 | 10.17 | 0.00 | 0.00 |
July | 38.53 | 5.84 | 32.69 | 61.16 | 38.63 | 0.00 | 0.00 | 0.00 |
August | 50.71 | 18.31 | 32.40 | 93.24 | 40.57 | 0.00 | 0.00 | 0.00 |
September | 67.57 | 35.08 | 32.49 | 125.47 | 47.81 | 5.50 | 0.00 | 0.00 |
October | 84.80 | 57.04 | 27.76 | 163.55 | 52.63 | 38.50 | 0.00 | 0.00 |
November | 101.01 | 71.08 | 29.93 | 174.96 | 79.11 | 123.17 | 0.00 | 0.00 |
December | 111.40 | 84.26 | 27.14 | 195.77 | 87.48 | 175.33 | 0.00 | 0.00 |
Annual Sum or Average | 70.62 | 39.04 | 31.59 | 118.68 | 65.87 | 1312.83 | 0.00 | 0.00 |
Minimum of Months | 35.90 | 3.23 | 27.14 | 46.07 | 38.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.40 | 84.26 | 34.77 | 195.77 | 90.47 | 307.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.29 | 206.37 | 76.91 | 495.30 | 238.33 | 190.00 | 0.00 | 0.00 |
February | 227.38 | 140.26 | 87.12 | 355.72 | 235.69 | 247.83 | 0.00 | 0.00 |
March | 186.43 | 92.95 | 93.48 | 282.27 | 245.56 | 307.00 | 0.00 | 0.00 |
April | 162.71 | 69.21 | 93.50 | 259.84 | 189.43 | 119.67 | 0.00 | 0.00 |
May | 112.54 | 18.15 | 94.38 | 137.97 | 173.77 | 95.67 | 0.00 | 0.00 |
June | 97.45 | 8.76 | 88.68 | 125.03 | 126.57 | 10.17 | 0.00 | 0.00 |
July | 104.59 | 15.86 | 88.73 | 166.00 | 104.85 | 0.00 | 0.00 | 0.00 |
August | 137.64 | 49.69 | 87.95 | 253.08 | 110.11 | 0.00 | 0.00 | 0.00 |
September | 183.39 | 95.21 | 88.18 | 340.56 | 129.77 | 5.50 | 0.00 | 0.00 |
October | 230.16 | 154.80 | 75.36 | 443.92 | 142.85 | 38.50 | 0.00 | 0.00 |
November | 274.17 | 192.94 | 81.24 | 474.87 | 214.73 | 123.17 | 0.00 | 0.00 |
December | 302.37 | 228.69 | 73.68 | 531.37 | 237.43 | 175.33 | 0.00 | 0.00 |
Annual Sum or Average | 191.69 | 105.95 | 85.73 | 322.13 | 178.78 | 1312.83 | 0.00 | 0.00 |
Minimum of Months | 97.45 | 8.76 | 73.68 | 125.03 | 104.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 302.37 | 228.69 | 94.38 | 531.37 | 245.56 | 307.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.81 | 130.98 | 48.83 | 340.76 | 149.66 | 2.67 | 0.00 | 0.00 |
February | 144.35 | 89.04 | 55.31 | 239.95 | 144.35 | 26.50 | 0.00 | 0.00 |
March | 118.39 | 59.05 | 59.34 | 190.70 | 154.45 | 25.67 | 0.00 | 0.00 |
April | 103.36 | 44.01 | 59.36 | 172.53 | 118.84 | 6.83 | 0.00 | 0.00 |
May | 71.48 | 11.56 | 59.91 | 89.46 | 108.52 | 2.17 | 0.00 | 0.00 |
June | 61.89 | 5.59 | 56.30 | 81.69 | 75.95 | 0.00 | 0.00 | 0.00 |
July | 66.44 | 10.11 | 56.33 | 110.08 | 61.31 | 0.00 | 0.00 | 0.00 |
August | 87.45 | 31.61 | 55.83 | 170.03 | 64.21 | 0.00 | 0.00 | 0.00 |
September | 116.49 | 60.52 | 55.98 | 230.47 | 76.13 | 0.00 | 0.00 | 0.00 |
October | 146.13 | 98.30 | 47.84 | 304.88 | 83.77 | 0.00 | 0.00 | 0.00 |
November | 174.03 | 122.46 | 51.57 | 323.79 | 133.28 | 5.67 | 0.00 | 0.00 |
December | 191.92 | 145.15 | 46.77 | 364.66 | 148.86 | 3.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.71 | 67.29 | 54.42 | 218.25 | 109.76 | 72.50 | 0.00 | 0.00 |
Minimum of Months | 61.89 | 5.59 | 46.77 | 81.69 | 61.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 191.92 | 145.15 | 59.91 | 364.66 | 154.45 | 26.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.97 | 67.99 | 65.97 | 188.26 | 303.26 | 2.33 | 0.00 | 0.00 |
February | 158.55 | 73.07 | 85.48 | 206.03 | 282.72 | 26.50 | 0.00 | 0.00 |
March | 181.00 | 79.54 | 101.46 | 244.28 | 289.72 | 25.67 | 0.00 | 0.00 |
April | 249.35 | 129.05 | 120.29 | 405.72 | 210.35 | 6.83 | 0.00 | 0.00 |
May | 245.02 | 112.41 | 132.61 | 380.03 | 187.59 | 2.00 | 0.00 | 0.00 |
June | 259.27 | 128.76 | 130.51 | 447.43 | 129.21 | 0.00 | 0.00 | 0.00 |
July | 274.60 | 146.13 | 128.47 | 524.05 | 104.74 | 0.00 | 0.00 | 0.00 |
August | 257.61 | 138.86 | 118.76 | 496.26 | 112.39 | 0.00 | 0.00 | 0.00 |
September | 220.80 | 117.57 | 103.23 | 399.93 | 136.01 | 0.00 | 0.00 | 0.00 |
October | 170.18 | 93.10 | 77.08 | 321.24 | 162.86 | 0.00 | 0.00 | 0.00 |
November | 153.81 | 80.69 | 73.12 | 227.00 | 265.61 | 5.67 | 0.00 | 0.00 |
December | 135.89 | 73.10 | 62.80 | 198.63 | 302.78 | 2.67 | 0.00 | 0.00 |
Annual Sum or Average | 203.51 | 103.49 | 100.03 | 337.28 | 206.89 | 71.67 | 0.00 | 0.00 |
Minimum of Months | 133.97 | 67.99 | 62.80 | 188.26 | 104.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 274.60 | 146.13 | 132.61 | 524.05 | 303.26 | 26.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.76 | 0.00 | 27.76 | 18.11 | 167.57 | 3.67 | 0.00 | 0.00 |
February | 34.85 | 0.00 | 34.85 | 17.70 | 158.71 | 26.67 | 0.00 | 0.00 |
March | 42.71 | 0.00 | 42.71 | 26.72 | 165.47 | 25.67 | 0.00 | 0.00 |
April | 49.67 | 0.61 | 49.06 | 37.95 | 129.74 | 7.50 | 0.00 | 0.00 |
May | 60.53 | 4.13 | 56.40 | 45.88 | 110.15 | 2.33 | 0.00 | 0.00 |
June | 64.73 | 7.89 | 56.84 | 61.63 | 85.07 | 0.00 | 0.00 | 0.00 |
July | 61.30 | 6.63 | 54.67 | 71.27 | 77.26 | 0.00 | 0.00 | 0.00 |
August | 50.17 | 1.60 | 48.57 | 59.77 | 86.82 | 0.00 | 0.00 | 0.00 |
September | 41.94 | 0.02 | 41.92 | 47.97 | 97.21 | 0.00 | 0.00 | 0.00 |
October | 33.26 | 0.00 | 33.26 | 48.17 | 103.30 | 0.00 | 0.00 | 0.00 |
November | 30.11 | 0.00 | 30.11 | 20.62 | 150.17 | 5.67 | 0.00 | 0.00 |
December | 25.84 | 0.00 | 25.84 | 16.49 | 167.29 | 4.17 | 0.00 | 0.00 |
Annual Sum or Average | 43.61 | 1.75 | 41.86 | 39.50 | 124.72 | 75.67 | 0.00 | 0.00 |
Minimum of Months | 25.84 | 0.00 | 25.84 | 16.49 | 77.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.73 | 7.89 | 56.84 | 71.27 | 167.57 | 26.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.97 | 67.99 | 65.97 | 202.17 | 299.91 | 3.83 | 0.00 | 0.00 |
February | 158.55 | 73.07 | 85.48 | 215.11 | 280.24 | 26.50 | 0.00 | 0.00 |
March | 181.00 | 79.54 | 101.46 | 247.40 | 290.33 | 25.67 | 0.00 | 0.00 |
April | 249.35 | 129.05 | 120.29 | 390.88 | 223.23 | 7.33 | 0.00 | 0.00 |
May | 245.02 | 112.41 | 132.61 | 356.90 | 203.08 | 2.33 | 0.00 | 0.00 |
June | 259.27 | 128.76 | 130.51 | 408.97 | 158.74 | 0.00 | 0.00 | 0.00 |
July | 274.60 | 146.13 | 128.47 | 483.13 | 141.50 | 0.00 | 0.00 | 0.00 |
August | 257.61 | 138.86 | 118.76 | 465.73 | 151.19 | 0.00 | 0.00 | 0.00 |
September | 220.80 | 117.57 | 103.23 | 385.38 | 162.26 | 0.00 | 0.00 | 0.00 |
October | 170.18 | 93.10 | 77.08 | 319.97 | 182.41 | 0.00 | 0.00 | 0.00 |
November | 153.81 | 80.69 | 73.12 | 238.50 | 265.50 | 5.67 | 0.00 | 0.00 |
December | 135.89 | 73.10 | 62.80 | 212.66 | 299.04 | 3.83 | 0.00 | 0.00 |
Annual Sum or Average | 203.51 | 103.49 | 100.03 | 327.84 | 221.18 | 75.17 | 0.00 | 0.00 |
Minimum of Months | 133.97 | 67.99 | 62.80 | 202.17 | 141.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 274.60 | 146.13 | 132.61 | 483.13 | 299.91 | 26.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 263.71 | 192.10 | 71.61 | 488.17 | 229.49 | 2.17 | 0.00 | 0.00 |
February | 211.70 | 130.59 | 81.11 | 344.27 | 220.50 | 21.83 | 0.00 | 0.00 |
March | 173.63 | 86.60 | 87.03 | 275.24 | 232.50 | 24.00 | 0.00 | 0.00 |
April | 151.59 | 64.54 | 87.05 | 254.38 | 172.85 | 4.50 | 0.00 | 0.00 |
May | 104.83 | 16.96 | 87.87 | 135.94 | 155.62 | 1.17 | 0.00 | 0.00 |
June | 90.77 | 8.20 | 82.57 | 127.67 | 106.16 | 0.00 | 0.00 | 0.00 |
July | 97.44 | 14.83 | 82.61 | 170.81 | 84.10 | 0.00 | 0.00 | 0.00 |
August | 128.25 | 46.36 | 81.89 | 255.75 | 89.56 | 0.00 | 0.00 | 0.00 |
September | 170.84 | 88.75 | 82.09 | 339.26 | 109.94 | 0.00 | 0.00 | 0.00 |
October | 214.32 | 144.16 | 70.16 | 443.78 | 125.08 | 0.00 | 0.00 | 0.00 |
November | 255.23 | 179.60 | 75.63 | 465.89 | 203.27 | 5.00 | 0.00 | 0.00 |
December | 281.47 | 212.88 | 68.59 | 522.71 | 228.50 | 2.33 | 0.00 | 0.00 |
Annual Sum or Average | 178.50 | 98.68 | 79.82 | 318.68 | 162.82 | 61.00 | 0.00 | 0.00 |
Minimum of Months | 90.77 | 8.20 | 68.59 | 127.67 | 84.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.47 | 212.88 | 87.87 | 522.71 | 232.50 | 24.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.70 | 0.00 | 241.70 | 105.91 | 1510.33 | 1.17 | 0.00 | 0.00 |
February | 303.40 | 0.00 | 303.40 | 103.86 | 1483.09 | 22.67 | 0.00 | 0.00 |
March | 371.83 | 0.01 | 371.82 | 177.56 | 1493.09 | 23.17 | 0.00 | 0.00 |
April | 432.42 | 5.25 | 427.17 | 276.34 | 1098.33 | 10.83 | 0.00 | 0.00 |
May | 526.87 | 35.83 | 491.04 | 356.65 | 952.04 | 3.67 | 0.00 | 0.00 |
June | 563.44 | 68.55 | 494.90 | 530.49 | 696.46 | 0.00 | 0.00 | 0.00 |
July | 533.56 | 57.53 | 476.03 | 610.02 | 594.00 | 0.00 | 0.00 | 0.00 |
August | 436.78 | 13.90 | 422.88 | 475.34 | 655.07 | 0.00 | 0.00 | 0.00 |
September | 365.14 | 0.14 | 365.00 | 353.51 | 794.86 | 0.50 | 0.00 | 0.00 |
October | 289.56 | 0.00 | 289.56 | 332.24 | 919.88 | 0.00 | 0.00 | 0.00 |
November | 262.17 | 0.00 | 262.17 | 123.67 | 1373.80 | 6.00 | 0.00 | 0.00 |
December | 225.00 | 0.00 | 225.00 | 92.53 | 1521.02 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 379.66 | 15.19 | 364.47 | 296.13 | 1088.87 | 69.17 | 0.00 | 0.00 |
Minimum of Months | 225.00 | 0.00 | 225.00 | 92.53 | 594.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 563.44 | 68.55 | 494.90 | 610.02 | 1521.02 | 23.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.70 | 0.00 | 241.70 | 94.20 | 1559.12 | 1.17 | 0.00 | 0.00 |
February | 303.40 | 0.00 | 303.40 | 90.69 | 1533.75 | 22.67 | 0.00 | 0.00 |
March | 371.83 | 0.01 | 371.82 | 160.09 | 1539.08 | 23.17 | 0.00 | 0.00 |
April | 432.42 | 5.25 | 427.17 | 255.37 | 1126.72 | 10.83 | 0.00 | 0.00 |
May | 526.87 | 35.83 | 491.04 | 331.79 | 974.31 | 3.67 | 0.00 | 0.00 |
June | 563.44 | 68.55 | 494.90 | 507.90 | 711.86 | 0.00 | 0.00 | 0.00 |
July | 533.56 | 57.53 | 476.03 | 589.27 | 607.33 | 0.00 | 0.00 | 0.00 |
August | 436.78 | 13.90 | 422.88 | 455.91 | 670.62 | 0.00 | 0.00 | 0.00 |
September | 365.14 | 0.14 | 365.00 | 334.43 | 816.26 | 0.50 | 0.00 | 0.00 |
October | 289.56 | 0.00 | 289.56 | 314.54 | 946.88 | 0.00 | 0.00 | 0.00 |
November | 262.17 | 0.00 | 262.17 | 110.45 | 1417.36 | 5.83 | 0.00 | 0.00 |
December | 225.00 | 0.00 | 225.00 | 81.57 | 1569.68 | 1.17 | 0.00 | 0.00 |
Annual Sum or Average | 379.66 | 15.19 | 364.47 | 278.44 | 1120.52 | 69.00 | 0.00 | 0.00 |
Minimum of Months | 225.00 | 0.00 | 225.00 | 81.57 | 607.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 563.44 | 68.55 | 494.90 | 589.27 | 1569.68 | 23.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.53 | 0.00 | 34.53 | 4.64 | 278.41 | 1.17 | 0.00 | 0.00 |
February | 43.34 | 0.00 | 43.34 | 2.25 | 279.26 | 26.00 | 0.00 | 0.00 |
March | 53.12 | 0.00 | 53.12 | 5.94 | 271.74 | 25.67 | 0.00 | 0.00 |
April | 61.78 | 0.75 | 61.03 | 11.46 | 200.08 | 10.83 | 0.00 | 0.00 |
May | 75.27 | 5.12 | 70.15 | 17.31 | 172.05 | 3.83 | 0.00 | 0.00 |
June | 80.49 | 9.79 | 70.70 | 35.84 | 124.63 | 0.00 | 0.00 | 0.00 |
July | 76.23 | 8.22 | 68.01 | 45.99 | 107.33 | 0.00 | 0.00 | 0.00 |
August | 62.40 | 1.99 | 60.41 | 32.29 | 123.38 | 0.00 | 0.00 | 0.00 |
September | 52.16 | 0.02 | 52.15 | 22.18 | 150.22 | 0.00 | 0.00 | 0.00 |
October | 41.37 | 0.00 | 41.37 | 22.75 | 174.89 | 0.00 | 0.00 | 0.00 |
November | 37.45 | 0.00 | 37.45 | 4.66 | 254.77 | 5.83 | 0.00 | 0.00 |
December | 32.14 | 0.00 | 32.14 | 2.35 | 279.04 | 2.17 | 0.00 | 0.00 |
Annual Sum or Average | 54.24 | 2.17 | 52.07 | 17.42 | 200.88 | 75.50 | 0.00 | 0.00 |
Minimum of Months | 32.14 | 0.00 | 32.14 | 2.25 | 107.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.49 | 9.79 | 70.70 | 45.99 | 279.26 | 26.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 349.13 | 187.34 | 161.79 | 381.09 | 934.14 | 1.17 | 0.00 | 0.00 |
February | 366.73 | 167.88 | 198.85 | 328.48 | 956.42 | 25.50 | 0.00 | 0.00 |
March | 445.13 | 197.54 | 247.59 | 448.23 | 927.98 | 25.67 | 0.00 | 0.00 |
April | 568.47 | 284.31 | 284.17 | 723.56 | 699.33 | 10.83 | 0.00 | 0.00 |
May | 535.81 | 222.48 | 313.33 | 616.36 | 651.89 | 3.67 | 0.00 | 0.00 |
June | 534.26 | 231.82 | 302.45 | 693.31 | 511.55 | 0.00 | 0.00 | 0.00 |
July | 604.25 | 299.69 | 304.56 | 909.29 | 440.35 | 0.00 | 0.00 | 0.00 |
August | 596.28 | 315.99 | 280.28 | 918.13 | 463.41 | 0.00 | 0.00 | 0.00 |
September | 436.96 | 201.09 | 235.86 | 593.94 | 538.90 | 0.00 | 0.00 | 0.00 |
October | 384.64 | 197.28 | 187.35 | 530.52 | 603.11 | 0.00 | 0.00 | 0.00 |
November | 351.16 | 178.31 | 172.84 | 364.17 | 862.25 | 5.67 | 0.00 | 0.00 |
December | 339.00 | 190.03 | 148.97 | 349.73 | 935.50 | 2.17 | 0.00 | 0.00 |
Annual Sum or Average | 459.93 | 223.25 | 236.68 | 573.15 | 709.01 | 74.67 | 0.00 | 0.00 |
Minimum of Months | 339.00 | 167.88 | 148.97 | 328.48 | 440.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 604.25 | 315.99 | 313.33 | 918.13 | 956.42 | 25.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 223.69 | 162.96 | 60.73 | 352.48 | 229.23 | 1.17 | 0.00 | 0.00 |
February | 179.55 | 110.75 | 68.79 | 238.42 | 239.90 | 25.17 | 0.00 | 0.00 |
March | 147.21 | 73.39 | 73.81 | 181.35 | 247.33 | 25.67 | 0.00 | 0.00 |
April | 128.48 | 54.65 | 73.83 | 159.26 | 196.73 | 10.83 | 0.00 | 0.00 |
May | 88.86 | 14.33 | 74.53 | 65.37 | 190.26 | 3.83 | 0.00 | 0.00 |
June | 76.94 | 6.92 | 70.03 | 52.06 | 145.14 | 0.00 | 0.00 | 0.00 |
July | 82.58 | 12.52 | 70.06 | 81.16 | 123.14 | 0.00 | 0.00 | 0.00 |
August | 108.69 | 39.24 | 69.45 | 151.31 | 130.21 | 0.00 | 0.00 | 0.00 |
September | 144.81 | 75.18 | 69.62 | 223.78 | 143.72 | 0.00 | 0.00 | 0.00 |
October | 181.74 | 122.24 | 59.50 | 304.73 | 155.89 | 0.00 | 0.00 | 0.00 |
November | 216.49 | 152.35 | 64.15 | 332.42 | 211.98 | 5.67 | 0.00 | 0.00 |
December | 238.75 | 180.58 | 58.18 | 378.64 | 228.84 | 2.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.36 | 83.66 | 67.70 | 210.05 | 186.56 | 74.33 | 0.00 | 0.00 |
Minimum of Months | 76.94 | 6.92 | 58.18 | 52.06 | 123.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 238.75 | 180.58 | 74.53 | 378.64 | 247.33 | 25.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.73 | 0.00 | 43.73 | 17.52 | 266.04 | 291.50 | 0.00 | 0.00 |
February | 54.89 | 0.00 | 54.89 | 17.74 | 257.28 | 326.50 | 0.00 | 0.00 |
March | 67.27 | 0.00 | 67.27 | 32.50 | 256.43 | 364.67 | 0.00 | 0.00 |
April | 78.24 | 0.95 | 77.29 | 53.55 | 187.23 | 172.17 | 0.00 | 0.00 |
May | 95.32 | 6.48 | 88.84 | 71.89 | 161.56 | 126.83 | 0.00 | 0.00 |
June | 101.94 | 12.40 | 89.54 | 106.01 | 116.76 | 20.83 | 0.00 | 0.00 |
July | 96.54 | 10.41 | 86.13 | 121.02 | 98.81 | 2.00 | 0.00 | 0.00 |
August | 79.03 | 2.51 | 76.51 | 93.85 | 108.54 | 0.00 | 0.00 | 0.00 |
September | 66.06 | 0.02 | 66.04 | 67.40 | 133.95 | 23.83 | 0.00 | 0.00 |
October | 52.39 | 0.00 | 52.39 | 61.29 | 156.39 | 76.00 | 0.00 | 0.00 |
November | 47.43 | 0.00 | 47.43 | 21.05 | 241.64 | 217.67 | 0.00 | 0.00 |
December | 40.71 | 0.00 | 40.71 | 15.02 | 268.62 | 269.33 | 0.00 | 0.00 |
Annual Sum or Average | 68.69 | 2.75 | 65.94 | 56.83 | 187.39 | 1891.33 | 0.00 | 0.00 |
Minimum of Months | 40.71 | 0.00 | 40.71 | 15.02 | 98.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.94 | 12.40 | 89.54 | 121.02 | 268.62 | 364.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.13 | 0.00 | 39.13 | 15.67 | 237.98 | 291.50 | 0.00 | 0.00 |
February | 49.11 | 0.00 | 49.11 | 15.88 | 230.19 | 326.50 | 0.00 | 0.00 |
March | 60.19 | 0.00 | 60.19 | 29.07 | 229.43 | 364.67 | 0.00 | 0.00 |
April | 70.00 | 0.85 | 69.15 | 47.91 | 167.51 | 172.17 | 0.00 | 0.00 |
May | 85.29 | 5.80 | 79.49 | 64.32 | 144.55 | 126.83 | 0.00 | 0.00 |
June | 91.21 | 11.10 | 80.11 | 94.85 | 104.46 | 20.83 | 0.00 | 0.00 |
July | 86.37 | 9.31 | 77.06 | 108.28 | 88.40 | 2.00 | 0.00 | 0.00 |
August | 70.70 | 2.25 | 68.45 | 83.97 | 97.11 | 0.00 | 0.00 | 0.00 |
September | 59.11 | 0.02 | 59.09 | 60.30 | 119.84 | 23.83 | 0.00 | 0.00 |
October | 46.87 | 0.00 | 46.87 | 54.83 | 139.93 | 76.00 | 0.00 | 0.00 |
November | 42.44 | 0.00 | 42.44 | 18.84 | 216.19 | 217.67 | 0.00 | 0.00 |
December | 36.42 | 0.00 | 36.42 | 13.44 | 240.27 | 269.33 | 0.00 | 0.00 |
Annual Sum or Average | 61.46 | 2.46 | 59.00 | 50.84 | 167.65 | 1891.33 | 0.00 | 0.00 |
Minimum of Months | 36.42 | 0.00 | 36.42 | 13.44 | 88.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 91.21 | 11.10 | 80.11 | 108.28 | 240.27 | 364.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.09 | 608.36 | 226.73 | 1427.63 | 689.58 | 238.67 | 0.00 | 0.00 |
February | 670.30 | 413.47 | 256.82 | 1005.49 | 690.25 | 290.33 | 0.00 | 0.00 |
March | 549.56 | 274.00 | 275.56 | 796.33 | 718.43 | 327.33 | 0.00 | 0.00 |
April | 479.65 | 204.01 | 275.64 | 721.13 | 565.73 | 171.00 | 0.00 | 0.00 |
May | 331.74 | 53.52 | 278.23 | 366.94 | 524.81 | 141.33 | 0.00 | 0.00 |
June | 287.26 | 25.83 | 261.43 | 329.86 | 385.08 | 28.00 | 0.00 | 0.00 |
July | 308.31 | 46.75 | 261.56 | 448.16 | 319.69 | 2.17 | 0.00 | 0.00 |
August | 405.76 | 146.48 | 259.27 | 700.56 | 337.73 | 0.00 | 0.00 | 0.00 |
September | 540.61 | 280.68 | 259.93 | 957.67 | 392.26 | 23.17 | 0.00 | 0.00 |
October | 678.49 | 456.35 | 222.14 | 1261.24 | 430.33 | 63.50 | 0.00 | 0.00 |
November | 808.23 | 568.76 | 239.48 | 1355.36 | 633.10 | 180.67 | 0.00 | 0.00 |
December | 891.34 | 674.16 | 217.19 | 1526.83 | 689.99 | 217.83 | 0.00 | 0.00 |
Annual Sum or Average | 565.07 | 312.34 | 252.73 | 908.03 | 530.52 | 1684.00 | 0.00 | 0.00 |
Minimum of Months | 287.26 | 25.83 | 217.19 | 329.86 | 319.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 891.34 | 674.16 | 278.23 | 1526.83 | 718.43 | 327.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263815E+10 | 0.192188E+10 | 0.716264E+09 | 0.464036E+10 | 0.181939E+10 |
February | 0.191262E+10 | 0.117980E+10 | 0.732822E+09 | 0.311827E+10 | 0.154170E+10 |
March | 0.173614E+10 | 0.865600E+09 | 0.870537E+09 | 0.275936E+10 | 0.177456E+10 |
April | 0.146639E+10 | 0.623713E+09 | 0.842674E+09 | 0.242483E+10 | 0.136809E+10 |
May | 0.104800E+10 | 0.169060E+09 | 0.878944E+09 | 0.141874E+10 | 0.124692E+10 |
June | 0.878205E+09 | 78973425.51 | 0.799232E+09 | 0.120674E+10 | 0.909154E+09 |
July | 0.973980E+09 | 0.147681E+09 | 0.826299E+09 | 0.155570E+10 | 0.818971E+09 |
August | 0.128183E+10 | 0.462757E+09 | 0.819075E+09 | 0.235133E+10 | 0.870830E+09 |
September | 0.165275E+10 | 0.858087E+09 | 0.794660E+09 | 0.308691E+10 | 0.988148E+09 |
October | 0.214342E+10 | 0.144165E+10 | 0.701767E+09 | 0.415283E+10 | 0.112099E+10 |
November | 0.247093E+10 | 0.173880E+10 | 0.732128E+09 | 0.433969E+10 | 0.158449E+10 |
December | 0.281585E+10 | 0.212973E+10 | 0.686113E+09 | 0.499585E+10 | 0.181950E+10 |
Annual Sum or Average | 0.210183E+11 | 0.116177E+11 | 0.940052E+10 | 0.360506E+11 | 0.158627E+11 |
Minimum of Months | 0.878205E+09 | 78973425.51 | 0.686113E+09 | 0.120674E+10 | 0.818971E+09 |
Maximum of Months | 0.281585E+10 | 0.212973E+10 | 0.878944E+09 | 0.499585E+10 | 0.181950E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.742885E+10 | 0.541190E+10 | 0.201695E+10 | 0.128454E+11 | 0.568210E+10 |
February | 0.538581E+10 | 0.332223E+10 | 0.206358E+10 | 0.854487E+10 | 0.501569E+10 |
March | 0.488885E+10 | 0.243747E+10 | 0.245137E+10 | 0.749569E+10 | 0.562057E+10 |
April | 0.412925E+10 | 0.175633E+10 | 0.237291E+10 | 0.654955E+10 | 0.452081E+10 |
May | 0.295111E+10 | 0.476063E+09 | 0.247505E+10 | 0.362404E+10 | 0.421662E+10 |
June | 0.247297E+10 | 0.222384E+09 | 0.225058E+10 | 0.304459E+10 | 0.313671E+10 |
July | 0.274266E+10 | 0.415861E+09 | 0.232680E+10 | 0.409878E+10 | 0.276360E+10 |
August | 0.360956E+10 | 0.130309E+10 | 0.230646E+10 | 0.637491E+10 | 0.290559E+10 |
September | 0.465403E+10 | 0.241632E+10 | 0.223771E+10 | 0.844881E+10 | 0.331538E+10 |
October | 0.603572E+10 | 0.405959E+10 | 0.197613E+10 | 0.114386E+11 | 0.369636E+10 |
November | 0.695797E+10 | 0.489635E+10 | 0.206162E+10 | 0.119729E+11 | 0.511214E+10 |
December | 0.792924E+10 | 0.599719E+10 | 0.193205E+10 | 0.138424E+11 | 0.569554E+10 |
Annual Sum or Average | 0.591860E+11 | 0.327148E+11 | 0.264712E+11 | 0.982805E+11 | 0.516811E+11 |
Minimum of Months | 0.247297E+10 | 0.222384E+09 | 0.193205E+10 | 0.304459E+10 | 0.276360E+10 |
Maximum of Months | 0.792924E+10 | 0.599719E+10 | 0.247505E+10 | 0.138424E+11 | 0.569554E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.965050E+10 | 0.703036E+10 | 0.262013E+10 | 0.172224E+11 | 0.772067E+10 |
February | 0.699648E+10 | 0.431577E+10 | 0.268071E+10 | 0.115419E+11 | 0.673431E+10 |
March | 0.635089E+10 | 0.316642E+10 | 0.318447E+10 | 0.102052E+11 | 0.771462E+10 |
April | 0.536413E+10 | 0.228158E+10 | 0.308255E+10 | 0.904279E+10 | 0.597649E+10 |
May | 0.383366E+10 | 0.618433E+09 | 0.321523E+10 | 0.522214E+10 | 0.556670E+10 |
June | 0.321253E+10 | 0.288889E+09 | 0.292364E+10 | 0.445329E+10 | 0.408789E+10 |
July | 0.356288E+10 | 0.540227E+09 | 0.302265E+10 | 0.583865E+10 | 0.360841E+10 |
August | 0.468902E+10 | 0.169279E+10 | 0.299622E+10 | 0.880972E+10 | 0.378685E+10 |
September | 0.604584E+10 | 0.313893E+10 | 0.290691E+10 | 0.115091E+11 | 0.430309E+10 |
October | 0.784074E+10 | 0.527363E+10 | 0.256711E+10 | 0.154565E+11 | 0.481110E+10 |
November | 0.903881E+10 | 0.636064E+10 | 0.267817E+10 | 0.161053E+11 | 0.678000E+10 |
December | 0.103005E+11 | 0.779069E+10 | 0.250984E+10 | 0.185337E+11 | 0.771803E+10 |
Annual Sum or Average | 0.768860E+11 | 0.424984E+11 | 0.343876E+11 | 0.133941E+12 | 0.688082E+11 |
Minimum of Months | 0.321253E+10 | 0.288889E+09 | 0.250984E+10 | 0.445329E+10 | 0.360841E+10 |
Maximum of Months | 0.103005E+11 | 0.779069E+10 | 0.321523E+10 | 0.185337E+11 | 0.772067E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.481598E+09 | 0.350824E+09 | 0.130774E+09 | 0.928158E+09 | 0.409322E+09 |
February | 0.349211E+09 | 0.215413E+09 | 0.133797E+09 | 0.599275E+09 | 0.357325E+09 |
March | 0.317103E+09 | 0.158163E+09 | 0.158941E+09 | 0.527139E+09 | 0.419505E+09 |
April | 0.267921E+09 | 0.114067E+09 | 0.153854E+09 | 0.466884E+09 | 0.312105E+09 |
May | 0.191446E+09 | 30969968.28 | 0.160476E+09 | 0.256143E+09 | 0.292859E+09 |
June | 0.160423E+09 | 14500975.78 | 0.145922E+09 | 0.226393E+09 | 0.198996E+09 |
July | 0.177947E+09 | 27083369.31 | 0.150864E+09 | 0.311445E+09 | 0.166087E+09 |
August | 0.234215E+09 | 84669429.45 | 0.149545E+09 | 0.475240E+09 | 0.173640E+09 |
September | 0.301943E+09 | 0.156856E+09 | 0.145087E+09 | 0.617622E+09 | 0.201679E+09 |
October | 0.391402E+09 | 0.263275E+09 | 0.128127E+09 | 0.838004E+09 | 0.229428E+09 |
November | 0.451090E+09 | 0.317420E+09 | 0.133671E+09 | 0.859679E+09 | 0.352654E+09 |
December | 0.514037E+09 | 0.388767E+09 | 0.125269E+09 | 0.995763E+09 | 0.407810E+09 |
Annual Sum or Average | 0.383834E+10 | 0.212201E+10 | 0.171633E+10 | 0.710174E+10 | 0.352141E+10 |
Minimum of Months | 0.160423E+09 | 14500975.78 | 0.125269E+09 | 0.226393E+09 | 0.166087E+09 |
Maximum of Months | 0.514037E+09 | 0.388767E+09 | 0.160476E+09 | 0.995763E+09 | 0.419505E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358820E+09 | 0.182116E+09 | 0.176704E+09 | 0.528188E+09 | 0.835483E+09 |
February | 0.383561E+09 | 0.176759E+09 | 0.206802E+09 | 0.525172E+09 | 0.705038E+09 |
March | 0.484790E+09 | 0.213049E+09 | 0.271741E+09 | 0.690772E+09 | 0.792892E+09 |
April | 0.646306E+09 | 0.334509E+09 | 0.311798E+09 | 0.110949E+10 | 0.556240E+09 |
May | 0.656273E+09 | 0.301089E+09 | 0.355184E+09 | 0.107814E+10 | 0.510946E+09 |
June | 0.672023E+09 | 0.333745E+09 | 0.338279E+09 | 0.122475E+10 | 0.341460E+09 |
July | 0.735490E+09 | 0.391401E+09 | 0.344089E+09 | 0.147022E+10 | 0.286230E+09 |
August | 0.689995E+09 | 0.371921E+09 | 0.318074E+09 | 0.139343E+10 | 0.305695E+09 |
September | 0.572313E+09 | 0.304729E+09 | 0.267584E+09 | 0.108770E+10 | 0.361875E+09 |
October | 0.455804E+09 | 0.249354E+09 | 0.206451E+09 | 0.896660E+09 | 0.448741E+09 |
November | 0.398663E+09 | 0.209141E+09 | 0.189522E+09 | 0.616272E+09 | 0.708087E+09 |
December | 0.363978E+09 | 0.195785E+09 | 0.168193E+09 | 0.553915E+09 | 0.835682E+09 |
Annual Sum or Average | 0.641802E+10 | 0.326360E+10 | 0.315442E+10 | 0.111747E+11 | 0.668837E+10 |
Minimum of Months | 0.358820E+09 | 0.176759E+09 | 0.168193E+09 | 0.525172E+09 | 0.286230E+09 |
Maximum of Months | 0.735490E+09 | 0.391401E+09 | 0.355184E+09 | 0.147022E+10 | 0.835682E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 74354016.30 | 0.00 | 74354016.30 | 48922494.40 | 0.461428E+09 |
February | 84301847.24 | 0.00 | 84301847.24 | 43980967.97 | 0.394740E+09 |
March | 0.114385E+09 | 2143.52 | 0.114383E+09 | 76100946.77 | 0.449926E+09 |
April | 0.128742E+09 | 1571541.63 | 0.127170E+09 | 0.108653E+09 | 0.333924E+09 |
May | 0.162114E+09 | 11057039.83 | 0.151057E+09 | 0.134951E+09 | 0.291302E+09 |
June | 0.167791E+09 | 20459176.36 | 0.147332E+09 | 0.179851E+09 | 0.214809E+09 |
July | 0.164190E+09 | 17749452.31 | 0.146441E+09 | 0.212007E+09 | 0.198240E+09 |
August | 0.134384E+09 | 4293768.64 | 0.130091E+09 | 0.174853E+09 | 0.220716E+09 |
September | 0.108704E+09 | 41213.82 | 0.108663E+09 | 0.133763E+09 | 0.249172E+09 |
October | 89076089.96 | 0.00 | 89076089.96 | 0.133761E+09 | 0.280672E+09 |
November | 78050350.98 | 0.00 | 78050350.98 | 54617649.95 | 0.399289E+09 |
December | 69217244.97 | 0.00 | 69217244.97 | 43648888.11 | 0.461817E+09 |
Annual Sum or Average | 0.137531E+10 | 55174336.11 | 0.132014E+10 | 0.134511E+10 | 0.395604E+10 |
Minimum of Months | 69217244.97 | 0.00 | 69217244.97 | 43648888.11 | 0.198240E+09 |
Maximum of Months | 0.167791E+09 | 20459176.36 | 0.151057E+09 | 0.212007E+09 | 0.461817E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358820E+09 | 0.182116E+09 | 0.176704E+09 | 0.560132E+09 | 0.829978E+09 |
February | 0.383561E+09 | 0.176759E+09 | 0.206802E+09 | 0.543515E+09 | 0.700405E+09 |
March | 0.484790E+09 | 0.213049E+09 | 0.271741E+09 | 0.697698E+09 | 0.793322E+09 |
April | 0.646306E+09 | 0.334509E+09 | 0.311798E+09 | 0.107393E+10 | 0.582978E+09 |
May | 0.656273E+09 | 0.301089E+09 | 0.355184E+09 | 0.102050E+10 | 0.545386E+09 |
June | 0.672023E+09 | 0.333745E+09 | 0.338279E+09 | 0.113300E+10 | 0.405713E+09 |
July | 0.735490E+09 | 0.391401E+09 | 0.344089E+09 | 0.137089E+10 | 0.368967E+09 |
August | 0.689995E+09 | 0.371921E+09 | 0.318074E+09 | 0.131880E+10 | 0.393286E+09 |
September | 0.572313E+09 | 0.304729E+09 | 0.267584E+09 | 0.105207E+10 | 0.421852E+09 |
October | 0.455804E+09 | 0.249354E+09 | 0.206451E+09 | 0.891410E+09 | 0.498445E+09 |
November | 0.398663E+09 | 0.209141E+09 | 0.189522E+09 | 0.641563E+09 | 0.710125E+09 |
December | 0.363978E+09 | 0.195785E+09 | 0.168193E+09 | 0.585491E+09 | 0.829539E+09 |
Annual Sum or Average | 0.641802E+10 | 0.326360E+10 | 0.315442E+10 | 0.108890E+11 | 0.708000E+10 |
Minimum of Months | 0.358820E+09 | 0.176759E+09 | 0.168193E+09 | 0.543515E+09 | 0.368967E+09 |
Maximum of Months | 0.735490E+09 | 0.391401E+09 | 0.355184E+09 | 0.137089E+10 | 0.829978E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.385202E+09 | 0.280604E+09 | 0.104598E+09 | 0.662390E+09 | 0.485112E+09 |
February | 0.279313E+09 | 0.172296E+09 | 0.107016E+09 | 0.414958E+09 | 0.437506E+09 |
March | 0.253632E+09 | 0.126505E+09 | 0.127127E+09 | 0.356729E+09 | 0.492448E+09 |
April | 0.214294E+09 | 91235614.03 | 0.123058E+09 | 0.310056E+09 | 0.389693E+09 |
May | 0.153126E+09 | 24771048.33 | 0.128355E+09 | 0.144994E+09 | 0.378058E+09 |
June | 0.128313E+09 | 11598474.00 | 0.116715E+09 | 0.117675E+09 | 0.283788E+09 |
July | 0.142330E+09 | 21662387.38 | 0.120667E+09 | 0.178631E+09 | 0.252179E+09 |
August | 0.187334E+09 | 67722075.46 | 0.119612E+09 | 0.308639E+09 | 0.266408E+09 |
September | 0.241506E+09 | 0.125460E+09 | 0.116047E+09 | 0.424176E+09 | 0.293483E+09 |
October | 0.313059E+09 | 0.210578E+09 | 0.102481E+09 | 0.591239E+09 | 0.325874E+09 |
November | 0.360801E+09 | 0.253885E+09 | 0.106915E+09 | 0.609565E+09 | 0.433500E+09 |
December | 0.411148E+09 | 0.310952E+09 | 0.100195E+09 | 0.713883E+09 | 0.485017E+09 |
Annual Sum or Average | 0.307006E+10 | 0.169727E+10 | 0.137279E+10 | 0.483293E+10 | 0.452307E+10 |
Minimum of Months | 0.128313E+09 | 11598474.00 | 0.100195E+09 | 0.117675E+09 | 0.252179E+09 |
Maximum of Months | 0.411148E+09 | 0.310952E+09 | 0.128355E+09 | 0.713883E+09 | 0.492448E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59491097.88 | 0.00 | 59491097.88 | 43432255.16 | 0.372412E+09 |
February | 67450417.55 | 0.00 | 67450417.55 | 39830694.50 | 0.316395E+09 |
March | 91520372.78 | 1715.04 | 91518657.74 | 68881595.30 | 0.357478E+09 |
April | 0.103007E+09 | 1257399.95 | 0.101750E+09 | 0.104414E+09 | 0.244890E+09 |
May | 0.129708E+09 | 8846804.40 | 0.120862E+09 | 0.134129E+09 | 0.219791E+09 |
June | 0.134251E+09 | 16369510.67 | 0.117881E+09 | 0.178082E+09 | 0.156201E+09 |
July | 0.131369E+09 | 14201444.08 | 0.117168E+09 | 0.206662E+09 | 0.139806E+09 |
August | 0.107522E+09 | 3435470.24 | 0.104086E+09 | 0.168195E+09 | 0.149746E+09 |
September | 86974691.39 | 32975.43 | 86941715.96 | 0.123641E+09 | 0.173691E+09 |
October | 71270318.00 | 0.00 | 71270318.00 | 0.118442E+09 | 0.212557E+09 |
November | 62448557.60 | 0.00 | 62448557.60 | 49591431.21 | 0.316818E+09 |
December | 55381136.09 | 0.00 | 55381136.09 | 39263856.01 | 0.372146E+09 |
Annual Sum or Average | 0.110039E+10 | 44145319.82 | 0.105625E+10 | 0.127456E+10 | 0.303193E+10 |
Minimum of Months | 55381136.09 | 0.00 | 55381136.09 | 39263856.01 | 0.139806E+09 |
Maximum of Months | 0.134251E+09 | 16369510.67 | 0.120862E+09 | 0.206662E+09 | 0.372412E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375984E+09 | 0.201778E+09 | 0.174206E+09 | 0.549563E+09 | 0.797383E+09 |
February | 0.356683E+09 | 0.163291E+09 | 0.193391E+09 | 0.455824E+09 | 0.680228E+09 |
March | 0.479215E+09 | 0.212629E+09 | 0.266586E+09 | 0.674766E+09 | 0.761013E+09 |
April | 0.592300E+09 | 0.296200E+09 | 0.296100E+09 | 0.101577E+10 | 0.535487E+09 |
May | 0.576936E+09 | 0.239561E+09 | 0.337375E+09 | 0.945759E+09 | 0.497960E+09 |
June | 0.556747E+09 | 0.241597E+09 | 0.315150E+09 | 0.102168E+10 | 0.342648E+09 |
July | 0.650656E+09 | 0.322726E+09 | 0.327930E+09 | 0.132502E+10 | 0.289235E+09 |
August | 0.642012E+09 | 0.340225E+09 | 0.301787E+09 | 0.132407E+10 | 0.301539E+09 |
September | 0.455295E+09 | 0.209525E+09 | 0.245770E+09 | 0.861587E+09 | 0.357373E+09 |
October | 0.414156E+09 | 0.212427E+09 | 0.201730E+09 | 0.803669E+09 | 0.424953E+09 |
November | 0.365955E+09 | 0.185851E+09 | 0.180104E+09 | 0.532156E+09 | 0.682723E+09 |
December | 0.365075E+09 | 0.204677E+09 | 0.160399E+09 | 0.521004E+09 | 0.795620E+09 |
Annual Sum or Average | 0.583101E+10 | 0.283049E+10 | 0.300053E+10 | 0.100309E+11 | 0.646616E+10 |
Minimum of Months | 0.356683E+09 | 0.163291E+09 | 0.160399E+09 | 0.455824E+09 | 0.289235E+09 |
Maximum of Months | 0.650656E+09 | 0.340225E+09 | 0.337375E+09 | 0.132502E+10 | 0.797383E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.481598E+09 | 0.350824E+09 | 0.130774E+09 | 0.921692E+09 | 0.406702E+09 |
February | 0.349211E+09 | 0.215413E+09 | 0.133797E+09 | 0.595841E+09 | 0.353233E+09 |
March | 0.317103E+09 | 0.158163E+09 | 0.158941E+09 | 0.521222E+09 | 0.415342E+09 |
April | 0.267921E+09 | 0.114067E+09 | 0.153854E+09 | 0.460969E+09 | 0.305257E+09 |
May | 0.191446E+09 | 30969968.28 | 0.160476E+09 | 0.252323E+09 | 0.286324E+09 |
June | 0.160423E+09 | 14500975.78 | 0.145922E+09 | 0.223472E+09 | 0.191179E+09 |
July | 0.177947E+09 | 27083369.31 | 0.150864E+09 | 0.306391E+09 | 0.158294E+09 |
August | 0.234215E+09 | 84669429.45 | 0.149545E+09 | 0.469725E+09 | 0.166824E+09 |
September | 0.301943E+09 | 0.156856E+09 | 0.145087E+09 | 0.616788E+09 | 0.194497E+09 |
October | 0.391402E+09 | 0.263275E+09 | 0.128127E+09 | 0.834871E+09 | 0.225310E+09 |
November | 0.451090E+09 | 0.317420E+09 | 0.133671E+09 | 0.856342E+09 | 0.348339E+09 |
December | 0.514037E+09 | 0.388767E+09 | 0.125269E+09 | 0.990458E+09 | 0.404312E+09 |
Annual Sum or Average | 0.383834E+10 | 0.212201E+10 | 0.171633E+10 | 0.705009E+10 | 0.345561E+10 |
Minimum of Months | 0.160423E+09 | 14500975.78 | 0.125269E+09 | 0.223472E+09 | 0.158294E+09 |
Maximum of Months | 0.514037E+09 | 0.388767E+09 | 0.160476E+09 | 0.990458E+09 | 0.415342E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 74354016.30 | 0.00 | 74354016.30 | 41652251.29 | 0.459528E+09 |
February | 84301847.24 | 0.00 | 84301847.24 | 38424982.96 | 0.387858E+09 |
March | 0.114385E+09 | 2143.52 | 0.114383E+09 | 69030874.35 | 0.440835E+09 |
April | 0.128742E+09 | 1571541.63 | 0.127170E+09 | 0.102164E+09 | 0.307764E+09 |
May | 0.162114E+09 | 11057039.83 | 0.151057E+09 | 0.136436E+09 | 0.271618E+09 |
June | 0.167791E+09 | 20459176.36 | 0.147332E+09 | 0.187322E+09 | 0.192335E+09 |
July | 0.164190E+09 | 17749452.31 | 0.146441E+09 | 0.212030E+09 | 0.174898E+09 |
August | 0.134384E+09 | 4293768.64 | 0.130091E+09 | 0.167275E+09 | 0.192593E+09 |
September | 0.108704E+09 | 41213.82 | 0.108663E+09 | 0.130222E+09 | 0.218542E+09 |
October | 89076089.96 | 0.00 | 89076089.96 | 0.128675E+09 | 0.265724E+09 |
November | 78050350.98 | 0.00 | 78050350.98 | 48389896.06 | 0.391898E+09 |
December | 69217244.97 | 0.00 | 69217244.97 | 36683953.21 | 0.458944E+09 |
Annual Sum or Average | 0.137531E+10 | 55174336.11 | 0.132014E+10 | 0.129831E+10 | 0.376254E+10 |
Minimum of Months | 69217244.97 | 0.00 | 69217244.97 | 36683953.21 | 0.174898E+09 |
Maximum of Months | 0.167791E+09 | 20459176.36 | 0.151057E+09 | 0.212030E+09 | 0.459528E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.375984E+09 | 0.201778E+09 | 0.174206E+09 | 0.570111E+09 | 0.785239E+09 |
February | 0.356683E+09 | 0.163291E+09 | 0.193391E+09 | 0.471700E+09 | 0.671632E+09 |
March | 0.479215E+09 | 0.212629E+09 | 0.266586E+09 | 0.687194E+09 | 0.758308E+09 |
April | 0.592300E+09 | 0.296200E+09 | 0.296100E+09 | 0.101185E+10 | 0.552488E+09 |
May | 0.576936E+09 | 0.239561E+09 | 0.337375E+09 | 0.919498E+09 | 0.524278E+09 |
June | 0.556747E+09 | 0.241597E+09 | 0.315150E+09 | 0.967735E+09 | 0.393056E+09 |
July | 0.650656E+09 | 0.322726E+09 | 0.327930E+09 | 0.124860E+10 | 0.356325E+09 |
August | 0.642012E+09 | 0.340225E+09 | 0.301787E+09 | 0.125976E+10 | 0.365387E+09 |
September | 0.455295E+09 | 0.209525E+09 | 0.245770E+09 | 0.844100E+09 | 0.395381E+09 |
October | 0.414156E+09 | 0.212427E+09 | 0.201730E+09 | 0.803062E+09 | 0.463342E+09 |
November | 0.365955E+09 | 0.185851E+09 | 0.180104E+09 | 0.548540E+09 | 0.676563E+09 |
December | 0.365075E+09 | 0.204677E+09 | 0.160399E+09 | 0.538827E+09 | 0.782106E+09 |
Annual Sum or Average | 0.583101E+10 | 0.283049E+10 | 0.300053E+10 | 0.987097E+10 | 0.672411E+10 |
Minimum of Months | 0.356683E+09 | 0.163291E+09 | 0.160399E+09 | 0.471700E+09 | 0.356325E+09 |
Maximum of Months | 0.650656E+09 | 0.340225E+09 | 0.337375E+09 | 0.125976E+10 | 0.785239E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117127E+09 | 0.00 | 0.117127E+09 | 57120669.45 | 0.724836E+09 |
February | 0.132797E+09 | 0.00 | 0.132797E+09 | 54422668.91 | 0.626713E+09 |
March | 0.180187E+09 | 3331.99 | 0.180183E+09 | 0.104404E+09 | 0.694644E+09 |
April | 0.202789E+09 | 2462891.94 | 0.200326E+09 | 0.167835E+09 | 0.480035E+09 |
May | 0.255318E+09 | 17364182.28 | 0.237954E+09 | 0.225898E+09 | 0.426391E+09 |
June | 0.264232E+09 | 32145276.10 | 0.232087E+09 | 0.314228E+09 | 0.295446E+09 |
July | 0.258560E+09 | 27877766.92 | 0.230682E+09 | 0.365243E+09 | 0.257772E+09 |
August | 0.211661E+09 | 6734454.72 | 0.204927E+09 | 0.288258E+09 | 0.280399E+09 |
September | 0.171236E+09 | 64212.67 | 0.171172E+09 | 0.202626E+09 | 0.338247E+09 |
October | 0.140318E+09 | 0.00 | 0.140318E+09 | 0.185641E+09 | 0.410421E+09 |
November | 0.122950E+09 | 0.00 | 0.122950E+09 | 67446326.88 | 0.624965E+09 |
December | 0.109035E+09 | 0.00 | 0.109035E+09 | 49672036.85 | 0.727619E+09 |
Annual Sum or Average | 0.216621E+10 | 86652116.62 | 0.207956E+10 | 0.208279E+10 | 0.588749E+10 |
Minimum of Months | 0.109035E+09 | 0.00 | 0.109035E+09 | 49672036.85 | 0.257772E+09 |
Maximum of Months | 0.264232E+09 | 32145276.10 | 0.237954E+09 | 0.365243E+09 | 0.727619E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43177876.19 | 0.00 | 43177876.19 | 21057043.94 | 0.267205E+09 |
February | 48954648.37 | 0.00 | 48954648.37 | 20062449.22 | 0.231032E+09 |
March | 66424296.87 | 1228.31 | 66423068.56 | 38487703.22 | 0.256074E+09 |
April | 74756420.36 | 907923.95 | 73848496.41 | 61870813.39 | 0.176961E+09 |
May | 94120888.55 | 6401156.58 | 87719731.96 | 83275441.38 | 0.157186E+09 |
June | 97406941.32 | 11850079.80 | 85556861.52 | 0.115838E+09 | 0.108914E+09 |
July | 95315951.74 | 10276899.21 | 85039052.53 | 0.134644E+09 | 95025441.36 |
August | 78027078.61 | 2482598.86 | 75544479.74 | 0.106264E+09 | 0.103367E+09 |
September | 63124854.33 | 23671.45 | 63101182.88 | 74696293.59 | 0.124692E+09 |
October | 51727083.15 | 0.00 | 51727083.15 | 68434931.26 | 0.151298E+09 |
November | 45324362.54 | 0.00 | 45324362.54 | 24863508.82 | 0.230388E+09 |
December | 40194918.61 | 0.00 | 40194918.61 | 18311169.54 | 0.268230E+09 |
Annual Sum or Average | 0.798555E+09 | 31943558.17 | 0.766612E+09 | 0.767804E+09 | 0.217037E+10 |
Minimum of Months | 40194918.61 | 0.00 | 40194918.61 | 18311169.54 | 95025441.36 |
Maximum of Months | 97406941.32 | 11850079.80 | 87719731.96 | 0.134644E+09 | 0.268230E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279549E+09 | 0.203651E+09 | 75898221.86 | 0.488764E+09 | 0.235189E+09 |
February | 0.202669E+09 | 0.125016E+09 | 77652810.06 | 0.317055E+09 | 0.210070E+09 |
March | 0.183968E+09 | 91722500.59 | 92245636.99 | 0.278542E+09 | 0.242316E+09 |
April | 0.155384E+09 | 66091146.44 | 89293131.30 | 0.248141E+09 | 0.180903E+09 |
May | 0.111051E+09 | 17914332.44 | 93136534.87 | 0.136155E+09 | 0.171478E+09 |
June | 93058214.02 | 8368346.03 | 84689867.99 | 0.119403E+09 | 0.120874E+09 |
July | 0.103207E+09 | 15648924.95 | 87557970.85 | 0.163810E+09 | 0.103463E+09 |
August | 0.135828E+09 | 49035651.87 | 86792539.57 | 0.249739E+09 | 0.108662E+09 |
September | 0.175132E+09 | 90926355.24 | 84205440.08 | 0.325222E+09 | 0.123924E+09 |
October | 0.227125E+09 | 0.152763E+09 | 74362131.28 | 0.438061E+09 | 0.140970E+09 |
November | 0.261830E+09 | 0.184250E+09 | 77579284.66 | 0.453490E+09 | 0.205060E+09 |
December | 0.298378E+09 | 0.225675E+09 | 72703326.98 | 0.524362E+09 | 0.234299E+09 |
Annual Sum or Average | 0.222718E+10 | 0.123106E+10 | 0.996117E+09 | 0.374274E+10 | 0.207721E+10 |
Minimum of Months | 93058214.02 | 8368346.03 | 72703326.98 | 0.119403E+09 | 0.103463E+09 |
Maximum of Months | 0.298378E+09 | 0.225675E+09 | 93136534.87 | 0.524362E+09 | 0.242316E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.758753E+09 | 0.552749E+09 | 0.206003E+09 | 0.132661E+10 | 0.638350E+09 |
February | 0.550085E+09 | 0.339320E+09 | 0.210766E+09 | 0.860553E+09 | 0.570173E+09 |
March | 0.499327E+09 | 0.248954E+09 | 0.250374E+09 | 0.756020E+09 | 0.657695E+09 |
April | 0.421745E+09 | 0.179385E+09 | 0.242360E+09 | 0.673505E+09 | 0.491012E+09 |
May | 0.301415E+09 | 48623162.54 | 0.252792E+09 | 0.369551E+09 | 0.465427E+09 |
June | 0.252579E+09 | 22713402.82 | 0.229866E+09 | 0.324083E+09 | 0.328077E+09 |
July | 0.280125E+09 | 42474383.22 | 0.237650E+09 | 0.444613E+09 | 0.280819E+09 |
August | 0.368665E+09 | 0.133093E+09 | 0.235573E+09 | 0.677842E+09 | 0.294931E+09 |
September | 0.475344E+09 | 0.246793E+09 | 0.228551E+09 | 0.882719E+09 | 0.336354E+09 |
October | 0.616464E+09 | 0.414630E+09 | 0.201834E+09 | 0.118899E+10 | 0.382620E+09 |
November | 0.710660E+09 | 0.500094E+09 | 0.210566E+09 | 0.123086E+10 | 0.556575E+09 |
December | 0.809860E+09 | 0.612528E+09 | 0.197332E+09 | 0.142323E+10 | 0.635936E+09 |
Annual Sum or Average | 0.604502E+10 | 0.334136E+10 | 0.270367E+10 | 0.101586E+11 | 0.563797E+10 |
Minimum of Months | 0.252579E+09 | 22713402.82 | 0.197332E+09 | 0.324083E+09 | 0.280819E+09 |
Maximum of Months | 0.809860E+09 | 0.612528E+09 | 0.252792E+09 | 0.142323E+10 | 0.657695E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.481598E+09 | 0.350824E+09 | 0.130774E+09 | 0.912701E+09 | 0.400853E+09 |
February | 0.349211E+09 | 0.215413E+09 | 0.133797E+09 | 0.580482E+09 | 0.349205E+09 |
March | 0.317103E+09 | 0.158163E+09 | 0.158941E+09 | 0.510782E+09 | 0.413682E+09 |
April | 0.267921E+09 | 0.114067E+09 | 0.153854E+09 | 0.447204E+09 | 0.308037E+09 |
May | 0.191446E+09 | 30969968.28 | 0.160476E+09 | 0.239609E+09 | 0.290650E+09 |
June | 0.160423E+09 | 14500975.78 | 0.145922E+09 | 0.211744E+09 | 0.196851E+09 |
July | 0.177947E+09 | 27083369.31 | 0.150864E+09 | 0.294837E+09 | 0.164222E+09 |
August | 0.234215E+09 | 84669429.45 | 0.149545E+09 | 0.455420E+09 | 0.171988E+09 |
September | 0.301943E+09 | 0.156856E+09 | 0.145087E+09 | 0.597386E+09 | 0.197332E+09 |
October | 0.391402E+09 | 0.263275E+09 | 0.128127E+09 | 0.816595E+09 | 0.224367E+09 |
November | 0.451090E+09 | 0.317420E+09 | 0.133671E+09 | 0.839265E+09 | 0.345473E+09 |
December | 0.514037E+09 | 0.388767E+09 | 0.125269E+09 | 0.976706E+09 | 0.398693E+09 |
Annual Sum or Average | 0.383834E+10 | 0.212201E+10 | 0.171633E+10 | 0.688273E+10 | 0.346135E+10 |
Minimum of Months | 0.160423E+09 | 14500975.78 | 0.125269E+09 | 0.211744E+09 | 0.164222E+09 |
Maximum of Months | 0.514037E+09 | 0.388767E+09 | 0.160476E+09 | 0.976706E+09 | 0.413682E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358820E+09 | 0.182116E+09 | 0.176704E+09 | 0.504246E+09 | 0.812246E+09 |
February | 0.383561E+09 | 0.176759E+09 | 0.206802E+09 | 0.498424E+09 | 0.683967E+09 |
March | 0.484790E+09 | 0.213049E+09 | 0.271741E+09 | 0.654274E+09 | 0.775995E+09 |
April | 0.646306E+09 | 0.334509E+09 | 0.311798E+09 | 0.105161E+10 | 0.545233E+09 |
May | 0.656273E+09 | 0.301089E+09 | 0.355184E+09 | 0.101788E+10 | 0.502442E+09 |
June | 0.672023E+09 | 0.333745E+09 | 0.338279E+09 | 0.115974E+10 | 0.334905E+09 |
July | 0.735490E+09 | 0.391401E+09 | 0.344089E+09 | 0.140362E+10 | 0.280541E+09 |
August | 0.689995E+09 | 0.371921E+09 | 0.318074E+09 | 0.132917E+10 | 0.301031E+09 |
September | 0.572313E+09 | 0.304729E+09 | 0.267584E+09 | 0.103662E+10 | 0.352548E+09 |
October | 0.455804E+09 | 0.249354E+09 | 0.206451E+09 | 0.860415E+09 | 0.436204E+09 |
November | 0.398663E+09 | 0.209141E+09 | 0.189522E+09 | 0.588384E+09 | 0.688456E+09 |
December | 0.363978E+09 | 0.195785E+09 | 0.168193E+09 | 0.532022E+09 | 0.810961E+09 |
Annual Sum or Average | 0.641802E+10 | 0.326360E+10 | 0.315442E+10 | 0.106364E+11 | 0.652453E+10 |
Minimum of Months | 0.358820E+09 | 0.176759E+09 | 0.168193E+09 | 0.498424E+09 | 0.280541E+09 |
Maximum of Months | 0.735490E+09 | 0.391401E+09 | 0.355184E+09 | 0.140362E+10 | 0.812246E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 74354016.30 | 0.00 | 74354016.30 | 48511423.13 | 0.448825E+09 |
February | 84301847.24 | 0.00 | 84301847.24 | 42811460.01 | 0.383959E+09 |
March | 0.114385E+09 | 2143.52 | 0.114383E+09 | 71557367.88 | 0.443185E+09 |
April | 0.128742E+09 | 1571541.63 | 0.127170E+09 | 98363714.07 | 0.336279E+09 |
May | 0.162114E+09 | 11057039.83 | 0.151057E+09 | 0.122891E+09 | 0.295028E+09 |
June | 0.167791E+09 | 20459176.36 | 0.147332E+09 | 0.159737E+09 | 0.220506E+09 |
July | 0.164190E+09 | 17749452.31 | 0.146441E+09 | 0.190891E+09 | 0.206920E+09 |
August | 0.134384E+09 | 4293768.64 | 0.130091E+09 | 0.160089E+09 | 0.232546E+09 |
September | 0.108704E+09 | 41213.82 | 0.108663E+09 | 0.124340E+09 | 0.251961E+09 |
October | 89076089.96 | 0.00 | 89076089.96 | 0.129024E+09 | 0.276679E+09 |
November | 78050350.98 | 0.00 | 78050350.98 | 53456227.54 | 0.389229E+09 |
December | 69217244.97 | 0.00 | 69217244.97 | 44155510.00 | 0.448081E+09 |
Annual Sum or Average | 0.137531E+10 | 55174336.11 | 0.132014E+10 | 0.124583E+10 | 0.393320E+10 |
Minimum of Months | 69217244.97 | 0.00 | 69217244.97 | 42811460.01 | 0.206920E+09 |
Maximum of Months | 0.167791E+09 | 20459176.36 | 0.151057E+09 | 0.190891E+09 | 0.448825E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358820E+09 | 0.182116E+09 | 0.176704E+09 | 0.541492E+09 | 0.803289E+09 |
February | 0.383561E+09 | 0.176759E+09 | 0.206802E+09 | 0.520405E+09 | 0.677968E+09 |
March | 0.484790E+09 | 0.213049E+09 | 0.271741E+09 | 0.662623E+09 | 0.777622E+09 |
April | 0.646306E+09 | 0.334509E+09 | 0.311798E+09 | 0.101316E+10 | 0.578609E+09 |
May | 0.656273E+09 | 0.301089E+09 | 0.355184E+09 | 0.955918E+09 | 0.543921E+09 |
June | 0.672023E+09 | 0.333745E+09 | 0.338279E+09 | 0.106005E+10 | 0.411445E+09 |
July | 0.735490E+09 | 0.391401E+09 | 0.344089E+09 | 0.129400E+10 | 0.379002E+09 |
August | 0.689995E+09 | 0.371921E+09 | 0.318074E+09 | 0.124741E+10 | 0.404938E+09 |
September | 0.572313E+09 | 0.304729E+09 | 0.267584E+09 | 0.998903E+09 | 0.420577E+09 |
October | 0.455804E+09 | 0.249354E+09 | 0.206451E+09 | 0.857008E+09 | 0.488555E+09 |
November | 0.398663E+09 | 0.209141E+09 | 0.189522E+09 | 0.618181E+09 | 0.688166E+09 |
December | 0.363978E+09 | 0.195785E+09 | 0.168193E+09 | 0.569596E+09 | 0.800955E+09 |
Annual Sum or Average | 0.641802E+10 | 0.326360E+10 | 0.315442E+10 | 0.103388E+11 | 0.697505E+10 |
Minimum of Months | 0.358820E+09 | 0.176759E+09 | 0.168193E+09 | 0.520405E+09 | 0.379002E+09 |
Maximum of Months | 0.735490E+09 | 0.391401E+09 | 0.355184E+09 | 0.129400E+10 | 0.803289E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.706310E+09 | 0.514517E+09 | 0.191793E+09 | 0.130751E+10 | 0.614672E+09 |
February | 0.512151E+09 | 0.315924E+09 | 0.196226E+09 | 0.832848E+09 | 0.533424E+09 |
March | 0.465063E+09 | 0.231961E+09 | 0.233102E+09 | 0.737192E+09 | 0.622721E+09 |
April | 0.392932E+09 | 0.167290E+09 | 0.225641E+09 | 0.659350E+09 | 0.448029E+09 |
May | 0.280774E+09 | 45420430.68 | 0.235353E+09 | 0.364095E+09 | 0.416817E+09 |
June | 0.235276E+09 | 21267072.64 | 0.214009E+09 | 0.330918E+09 | 0.275155E+09 |
July | 0.260977E+09 | 39720360.29 | 0.221256E+09 | 0.457490E+09 | 0.225265E+09 |
August | 0.343498E+09 | 0.124176E+09 | 0.219322E+09 | 0.684999E+09 | 0.239888E+09 |
September | 0.442828E+09 | 0.230044E+09 | 0.212785E+09 | 0.879372E+09 | 0.284960E+09 |
October | 0.574028E+09 | 0.386117E+09 | 0.187911E+09 | 0.118862E+10 | 0.335005E+09 |
November | 0.661567E+09 | 0.465527E+09 | 0.196041E+09 | 0.120758E+10 | 0.526882E+09 |
December | 0.753884E+09 | 0.570165E+09 | 0.183719E+09 | 0.140002E+10 | 0.612024E+09 |
Annual Sum or Average | 0.562929E+10 | 0.311213E+10 | 0.251716E+10 | 0.100500E+11 | 0.513484E+10 |
Minimum of Months | 0.235276E+09 | 21267072.64 | 0.183719E+09 | 0.330918E+09 | 0.225265E+09 |
Maximum of Months | 0.753884E+09 | 0.570165E+09 | 0.235353E+09 | 0.140002E+10 | 0.622721E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.647374E+09 | 0.00 | 0.647374E+09 | 0.283670E+09 | 0.404526E+10 |
February | 0.733986E+09 | 0.00 | 0.733986E+09 | 0.251258E+09 | 0.358789E+10 |
March | 0.995912E+09 | 18416.29 | 0.995893E+09 | 0.475580E+09 | 0.399911E+10 |
April | 0.112084E+10 | 13612672.38 | 0.110722E+10 | 0.716284E+09 | 0.284688E+10 |
May | 0.141117E+10 | 95973729.27 | 0.131520E+10 | 0.955255E+09 | 0.254994E+10 |
June | 0.146044E+10 | 0.177670E+09 | 0.128277E+10 | 0.137504E+10 | 0.180522E+10 |
July | 0.142909E+10 | 0.154083E+09 | 0.127501E+10 | 0.163388E+10 | 0.159097E+10 |
August | 0.116987E+10 | 37222065.74 | 0.113265E+10 | 0.127314E+10 | 0.175455E+10 |
September | 0.946443E+09 | 354910.42 | 0.946088E+09 | 0.916285E+09 | 0.206028E+10 |
October | 0.775554E+09 | 0.00 | 0.775554E+09 | 0.889865E+09 | 0.246380E+10 |
November | 0.679557E+09 | 0.00 | 0.679557E+09 | 0.320546E+09 | 0.356089E+10 |
December | 0.602650E+09 | 0.00 | 0.602650E+09 | 0.247824E+09 | 0.407389E+10 |
Annual Sum or Average | 0.119729E+11 | 0.478936E+09 | 0.114940E+11 | 0.933863E+10 | 0.343387E+11 |
Minimum of Months | 0.602650E+09 | 0.00 | 0.602650E+09 | 0.247824E+09 | 0.159097E+10 |
Maximum of Months | 0.146044E+10 | 0.177670E+09 | 0.131520E+10 | 0.163388E+10 | 0.407389E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.647374E+09 | 0.00 | 0.647374E+09 | 0.252318E+09 | 0.417594E+10 |
February | 0.733986E+09 | 0.00 | 0.733986E+09 | 0.219399E+09 | 0.371045E+10 |
March | 0.995912E+09 | 18416.29 | 0.995893E+09 | 0.428772E+09 | 0.412228E+10 |
April | 0.112084E+10 | 13612672.38 | 0.110722E+10 | 0.661926E+09 | 0.292047E+10 |
May | 0.141117E+10 | 95973729.27 | 0.131520E+10 | 0.888655E+09 | 0.260959E+10 |
June | 0.146044E+10 | 0.177670E+09 | 0.128277E+10 | 0.131649E+10 | 0.184513E+10 |
July | 0.142909E+10 | 0.154083E+09 | 0.127501E+10 | 0.157829E+10 | 0.162668E+10 |
August | 0.116987E+10 | 37222065.74 | 0.113265E+10 | 0.122112E+10 | 0.179618E+10 |
September | 0.946443E+09 | 354910.42 | 0.946088E+09 | 0.866840E+09 | 0.211574E+10 |
October | 0.775554E+09 | 0.00 | 0.775554E+09 | 0.842459E+09 | 0.253611E+10 |
November | 0.679557E+09 | 0.00 | 0.679557E+09 | 0.286294E+09 | 0.367380E+10 |
December | 0.602650E+09 | 0.00 | 0.602650E+09 | 0.218475E+09 | 0.420423E+10 |
Annual Sum or Average | 0.119729E+11 | 0.478936E+09 | 0.114940E+11 | 0.878104E+10 | 0.353366E+11 |
Minimum of Months | 0.602650E+09 | 0.00 | 0.602650E+09 | 0.218475E+09 | 0.162668E+10 |
Maximum of Months | 0.146044E+10 | 0.177670E+09 | 0.131520E+10 | 0.157829E+10 | 0.420423E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92485490.62 | 0.00 | 92485490.62 | 12418623.82 | 0.745699E+09 |
February | 0.104859E+09 | 0.00 | 0.104859E+09 | 5434098.52 | 0.675596E+09 |
March | 0.142279E+09 | 2631.00 | 0.142276E+09 | 15899876.37 | 0.727823E+09 |
April | 0.160126E+09 | 1944741.14 | 0.158181E+09 | 29708700.40 | 0.518611E+09 |
May | 0.201604E+09 | 13711052.03 | 0.187893E+09 | 46365017.22 | 0.460806E+09 |
June | 0.208642E+09 | 25382453.72 | 0.183260E+09 | 92892097.61 | 0.323042E+09 |
July | 0.204163E+09 | 22012756.30 | 0.182151E+09 | 0.123179E+09 | 0.287477E+09 |
August | 0.167131E+09 | 5317639.36 | 0.161814E+09 | 86487531.23 | 0.330453E+09 |
September | 0.135211E+09 | 50703.41 | 0.135161E+09 | 57497961.40 | 0.389376E+09 |
October | 0.110798E+09 | 0.00 | 0.110798E+09 | 60939909.12 | 0.468420E+09 |
November | 97083188.81 | 0.00 | 97083188.81 | 12076149.92 | 0.660364E+09 |
December | 86096100.51 | 0.00 | 86096100.51 | 6306195.24 | 0.747390E+09 |
Annual Sum or Average | 0.171048E+10 | 68421976.95 | 0.164206E+10 | 0.549205E+09 | 0.633506E+10 |
Minimum of Months | 86096100.51 | 0.00 | 86096100.51 | 5434098.52 | 0.287477E+09 |
Maximum of Months | 0.208642E+09 | 25382453.72 | 0.187893E+09 | 0.123179E+09 | 0.747390E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.935123E+09 | 0.501780E+09 | 0.433343E+09 | 0.102070E+10 | 0.250201E+10 |
February | 0.887198E+09 | 0.406131E+09 | 0.481067E+09 | 0.794650E+09 | 0.231377E+10 |
March | 0.119224E+10 | 0.529103E+09 | 0.663141E+09 | 0.120053E+10 | 0.248550E+10 |
April | 0.147348E+10 | 0.736926E+09 | 0.736558E+09 | 0.187547E+10 | 0.181266E+10 |
May | 0.143512E+10 | 0.595893E+09 | 0.839230E+09 | 0.165086E+10 | 0.174603E+10 |
June | 0.138481E+10 | 0.600865E+09 | 0.783946E+09 | 0.179705E+10 | 0.132594E+10 |
July | 0.161841E+10 | 0.802677E+09 | 0.815737E+09 | 0.243544E+10 | 0.117945E+10 |
August | 0.159706E+10 | 0.846361E+09 | 0.750704E+09 | 0.245912E+10 | 0.124120E+10 |
September | 0.113259E+10 | 0.521232E+09 | 0.611360E+09 | 0.153949E+10 | 0.139682E+10 |
October | 0.103021E+10 | 0.528399E+09 | 0.501808E+09 | 0.142095E+10 | 0.161537E+10 |
November | 0.910203E+09 | 0.462189E+09 | 0.448014E+09 | 0.943931E+09 | 0.223495E+10 |
December | 0.907965E+09 | 0.508969E+09 | 0.398996E+09 | 0.936721E+09 | 0.250563E+10 |
Annual Sum or Average | 0.145044E+11 | 0.704052E+10 | 0.746390E+10 | 0.180749E+11 | 0.223593E+11 |
Minimum of Months | 0.887198E+09 | 0.406131E+09 | 0.398996E+09 | 0.794650E+09 | 0.117945E+10 |
Maximum of Months | 0.161841E+10 | 0.846361E+09 | 0.839230E+09 | 0.245912E+10 | 0.250563E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.599124E+09 | 0.436460E+09 | 0.162664E+09 | 0.944073E+09 | 0.613958E+09 |
February | 0.434357E+09 | 0.267933E+09 | 0.166424E+09 | 0.576796E+09 | 0.580374E+09 |
March | 0.394277E+09 | 0.196578E+09 | 0.197699E+09 | 0.485720E+09 | 0.662445E+09 |
April | 0.333017E+09 | 0.141645E+09 | 0.191371E+09 | 0.412801E+09 | 0.509934E+09 |
May | 0.238002E+09 | 38393671.57 | 0.199609E+09 | 0.175087E+09 | 0.509589E+09 |
June | 0.199441E+09 | 17934887.05 | 0.181506E+09 | 0.134952E+09 | 0.376199E+09 |
July | 0.221191E+09 | 33538491.42 | 0.187653E+09 | 0.217373E+09 | 0.329826E+09 |
August | 0.291105E+09 | 0.105092E+09 | 0.186012E+09 | 0.405267E+09 | 0.348747E+09 |
September | 0.375339E+09 | 0.194872E+09 | 0.180468E+09 | 0.580032E+09 | 0.372509E+09 |
October | 0.486770E+09 | 0.327399E+09 | 0.159372E+09 | 0.816189E+09 | 0.417549E+09 |
November | 0.561149E+09 | 0.394882E+09 | 0.166267E+09 | 0.861628E+09 | 0.549458E+09 |
December | 0.639479E+09 | 0.483663E+09 | 0.155816E+09 | 0.101416E+10 | 0.612917E+09 |
Annual Sum or Average | 0.477325E+10 | 0.263839E+10 | 0.213486E+10 | 0.662408E+10 | 0.588350E+10 |
Minimum of Months | 0.199441E+09 | 17934887.05 | 0.155816E+09 | 0.134952E+09 | 0.329826E+09 |
Maximum of Months | 0.639479E+09 | 0.483663E+09 | 0.199609E+09 | 0.101416E+10 | 0.662445E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117127E+09 | 0.00 | 0.117127E+09 | 46914482.32 | 0.712549E+09 |
February | 0.132797E+09 | 0.00 | 0.132797E+09 | 42927566.09 | 0.622416E+09 |
March | 0.180187E+09 | 3331.99 | 0.180183E+09 | 87038575.96 | 0.686816E+09 |
April | 0.202789E+09 | 2462891.94 | 0.200326E+09 | 0.138790E+09 | 0.485295E+09 |
May | 0.255318E+09 | 17364182.28 | 0.237954E+09 | 0.192542E+09 | 0.432724E+09 |
June | 0.264232E+09 | 32145276.10 | 0.232087E+09 | 0.274772E+09 | 0.302636E+09 |
July | 0.258560E+09 | 27877766.92 | 0.230682E+09 | 0.324150E+09 | 0.264650E+09 |
August | 0.211661E+09 | 6734454.72 | 0.204927E+09 | 0.251367E+09 | 0.290707E+09 |
September | 0.171236E+09 | 64212.67 | 0.171172E+09 | 0.174690E+09 | 0.347188E+09 |
October | 0.140318E+09 | 0.00 | 0.140318E+09 | 0.164155E+09 | 0.418885E+09 |
November | 0.122950E+09 | 0.00 | 0.122950E+09 | 54570059.42 | 0.626322E+09 |
December | 0.109035E+09 | 0.00 | 0.109035E+09 | 40236028.42 | 0.719465E+09 |
Annual Sum or Average | 0.216621E+10 | 86652116.62 | 0.207956E+10 | 0.179215E+10 | 0.590966E+10 |
Minimum of Months | 0.109035E+09 | 0.00 | 0.109035E+09 | 40236028.42 | 0.264650E+09 |
Maximum of Months | 0.264232E+09 | 32145276.10 | 0.237954E+09 | 0.324150E+09 | 0.719465E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104794E+09 | 0.00 | 0.104794E+09 | 41974565.09 | 0.637419E+09 |
February | 0.118814E+09 | 0.00 | 0.118814E+09 | 38407456.03 | 0.556879E+09 |
March | 0.161214E+09 | 2981.15 | 0.161211E+09 | 77873743.70 | 0.614497E+09 |
April | 0.181436E+09 | 2203558.75 | 0.179233E+09 | 0.124176E+09 | 0.434196E+09 |
May | 0.228434E+09 | 15535799.68 | 0.212898E+09 | 0.172268E+09 | 0.387160E+09 |
June | 0.236410E+09 | 28760500.32 | 0.207649E+09 | 0.245839E+09 | 0.270770E+09 |
July | 0.231335E+09 | 24942343.69 | 0.206392E+09 | 0.290018E+09 | 0.236784E+09 |
August | 0.189374E+09 | 6025342.16 | 0.183349E+09 | 0.224899E+09 | 0.260096E+09 |
September | 0.153206E+09 | 57451.32 | 0.153148E+09 | 0.156296E+09 | 0.310631E+09 |
October | 0.125543E+09 | 0.00 | 0.125543E+09 | 0.146870E+09 | 0.374778E+09 |
November | 0.110004E+09 | 0.00 | 0.110004E+09 | 48824038.93 | 0.560362E+09 |
December | 97554277.19 | 0.00 | 97554277.19 | 35999327.09 | 0.643547E+09 |
Annual Sum or Average | 0.193812E+10 | 77527977.07 | 0.186059E+10 | 0.160345E+10 | 0.528712E+10 |
Minimum of Months | 97554277.19 | 0.00 | 97554277.19 | 35999327.09 | 0.236784E+09 |
Maximum of Months | 0.236410E+09 | 28760500.32 | 0.212898E+09 | 0.290018E+09 | 0.643547E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223671E+10 | 0.162944E+10 | 0.607272E+09 | 0.382376E+10 | 0.184697E+10 |
February | 0.162158E+10 | 0.100027E+10 | 0.621311E+09 | 0.243247E+10 | 0.166986E+10 |
March | 0.147195E+10 | 0.733884E+09 | 0.738070E+09 | 0.213289E+10 | 0.192426E+10 |
April | 0.124325E+10 | 0.528804E+09 | 0.714447E+09 | 0.186916E+10 | 0.146638E+10 |
May | 0.888533E+09 | 0.143335E+09 | 0.745198E+09 | 0.982806E+09 | 0.140566E+10 |
June | 0.744571E+09 | 66956277.69 | 0.677615E+09 | 0.855004E+09 | 0.998128E+09 |
July | 0.825772E+09 | 0.125209E+09 | 0.700563E+09 | 0.120035E+10 | 0.856264E+09 |
August | 0.108678E+10 | 0.392341E+09 | 0.694439E+09 | 0.187637E+10 | 0.904567E+09 |
September | 0.140125E+10 | 0.727514E+09 | 0.673739E+09 | 0.248227E+10 | 0.101674E+10 |
October | 0.181726E+10 | 0.122228E+10 | 0.594982E+09 | 0.337810E+10 | 0.115260E+10 |
November | 0.209494E+10 | 0.147421E+10 | 0.620722E+09 | 0.351310E+10 | 0.164099E+10 |
December | 0.238737E+10 | 0.180566E+10 | 0.581709E+09 | 0.408946E+10 | 0.184807E+10 |
Annual Sum or Average | 0.178200E+11 | 0.984990E+10 | 0.797007E+10 | 0.286357E+11 | 0.167305E+11 |
Minimum of Months | 0.744571E+09 | 66956277.69 | 0.581709E+09 | 0.855004E+09 | 0.856264E+09 |
Maximum of Months | 0.238737E+10 | 0.180566E+10 | 0.745198E+09 | 0.408946E+10 | 0.192426E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1732.51 | 679.28 | 984.97 | 717.55 | 267.42 | 0.00 | 0.00 |
February | 1288.97 | 637.28 | 790.60 | 487.68 | 302.92 | 0.00 | 0.00 |
March | 1030.23 | 662.54 | 648.20 | 323.18 | 325.02 | 0.00 | 0.00 |
April | 935.51 | 527.81 | 565.74 | 240.63 | 325.11 | 0.00 | 0.00 |
May | 529.70 | 465.55 | 391.28 | 63.12 | 328.16 | 0.00 | 0.00 |
June | 465.56 | 350.75 | 338.81 | 30.47 | 308.35 | 0.00 | 0.00 |
July | 580.83 | 305.77 | 363.64 | 55.14 | 308.50 | 0.00 | 0.00 |
August | 877.89 | 325.13 | 478.58 | 172.77 | 305.81 | 0.00 | 0.00 |
September | 1190.94 | 381.23 | 637.63 | 331.05 | 306.58 | 0.00 | 0.00 |
October | 1550.49 | 418.53 | 800.26 | 538.25 | 262.01 | 0.00 | 0.00 |
November | 1674.26 | 611.30 | 953.29 | 670.83 | 282.46 | 0.00 | 0.00 |
December | 1865.24 | 679.32 | 1051.32 | 795.15 | 256.17 | 0.00 | 0.00 |
Annual Sum or Average | 1143.16 | 503.00 | 666.48 | 368.40 | 298.09 | 0.00 | 0.00 |
Minimum of Months | 465.56 | 305.77 | 338.81 | 30.47 | 256.17 | 0.00 | 0.00 |
Maximum of Months | 1865.24 | 679.32 | 1051.32 | 795.15 | 328.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4795.92 | 2121.45 | 2773.61 | 2020.57 | 753.04 | 0.00 | 0.00 |
February | 3532.11 | 2073.29 | 2226.28 | 1373.28 | 853.00 | 0.00 | 0.00 |
March | 2798.57 | 2098.48 | 1825.29 | 910.05 | 915.24 | 0.00 | 0.00 |
April | 2526.83 | 1744.14 | 1593.07 | 677.60 | 915.48 | 0.00 | 0.00 |
May | 1353.06 | 1574.30 | 1101.82 | 177.74 | 924.08 | 0.00 | 0.00 |
June | 1174.61 | 1210.15 | 954.08 | 85.80 | 868.28 | 0.00 | 0.00 |
July | 1530.31 | 1031.81 | 1023.99 | 155.26 | 868.73 | 0.00 | 0.00 |
August | 2380.12 | 1084.82 | 1347.65 | 486.52 | 861.13 | 0.00 | 0.00 |
September | 3259.57 | 1279.08 | 1795.53 | 932.22 | 863.31 | 0.00 | 0.00 |
October | 4270.68 | 1380.06 | 2253.48 | 1515.68 | 737.80 | 0.00 | 0.00 |
November | 4619.16 | 1972.28 | 2684.40 | 1889.02 | 795.38 | 0.00 | 0.00 |
December | 5168.15 | 2126.47 | 2960.44 | 2239.09 | 721.34 | 0.00 | 0.00 |
Annual Sum or Average | 3116.45 | 1638.80 | 1876.78 | 1037.38 | 839.40 | 0.00 | 0.00 |
Minimum of Months | 1174.61 | 1031.81 | 954.08 | 85.80 | 721.34 | 0.00 | 0.00 |
Maximum of Months | 5168.15 | 2126.47 | 2960.44 | 2239.09 | 924.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6430.12 | 2882.57 | 3603.08 | 2624.84 | 978.25 | 0.00 | 0.00 |
February | 4770.97 | 2783.69 | 2892.06 | 1783.97 | 1108.10 | 0.00 | 0.00 |
March | 3810.20 | 2880.31 | 2371.15 | 1182.20 | 1188.95 | 0.00 | 0.00 |
April | 3488.73 | 2305.74 | 2069.49 | 880.24 | 1189.26 | 0.00 | 0.00 |
May | 1949.72 | 2078.37 | 1431.33 | 230.90 | 1200.43 | 0.00 | 0.00 |
June | 1718.09 | 1577.12 | 1239.40 | 111.45 | 1127.95 | 0.00 | 0.00 |
July | 2179.90 | 1347.23 | 1330.23 | 201.70 | 1128.53 | 0.00 | 0.00 |
August | 3289.17 | 1413.85 | 1750.68 | 632.02 | 1118.66 | 0.00 | 0.00 |
September | 4440.23 | 1660.14 | 2332.50 | 1211.01 | 1121.49 | 0.00 | 0.00 |
October | 5770.79 | 1796.26 | 2927.40 | 1968.95 | 958.45 | 0.00 | 0.00 |
November | 6213.47 | 2615.74 | 3487.19 | 2453.95 | 1033.24 | 0.00 | 0.00 |
December | 6919.67 | 2881.58 | 3845.78 | 2908.71 | 937.07 | 0.00 | 0.00 |
Annual Sum or Average | 4247.23 | 2181.89 | 2438.04 | 1347.61 | 1090.42 | 0.00 | 0.00 |
Minimum of Months | 1718.09 | 1347.23 | 1239.40 | 111.45 | 937.07 | 0.00 | 0.00 |
Maximum of Months | 6919.67 | 2882.57 | 3845.78 | 2908.71 | 1200.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 528.14 | 449.15 | 313.78 | 198.98 | 114.80 | 0.00 | 0.00 |
February | 455.77 | 430.11 | 302.90 | 162.11 | 140.79 | 0.00 | 0.00 |
March | 448.13 | 446.07 | 299.39 | 138.59 | 160.80 | 0.00 | 0.00 |
April | 602.62 | 329.46 | 352.71 | 173.06 | 179.65 | 0.00 | 0.00 |
May | 491.83 | 293.77 | 316.50 | 123.98 | 192.53 | 0.00 | 0.00 |
June | 553.72 | 202.38 | 321.16 | 134.35 | 186.81 | 0.00 | 0.00 |
July | 660.56 | 164.24 | 341.04 | 156.24 | 184.79 | 0.00 | 0.00 |
August | 694.22 | 175.50 | 345.06 | 170.47 | 174.59 | 0.00 | 0.00 |
September | 654.47 | 213.98 | 337.29 | 178.08 | 159.21 | 0.00 | 0.00 |
October | 643.60 | 249.15 | 316.31 | 191.39 | 124.92 | 0.00 | 0.00 |
November | 557.87 | 397.68 | 327.84 | 203.15 | 124.69 | 0.00 | 0.00 |
December | 560.77 | 446.45 | 327.81 | 218.25 | 109.57 | 0.00 | 0.00 |
Annual Sum or Average | 571.69 | 315.90 | 325.23 | 170.78 | 154.45 | 0.00 | 0.00 |
Minimum of Months | 448.13 | 164.24 | 299.39 | 123.98 | 109.57 | 0.00 | 0.00 |
Maximum of Months | 694.22 | 449.15 | 352.71 | 218.25 | 192.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 220.28 | 475.04 | 161.73 | 67.99 | 93.73 | 0.00 | 0.00 |
February | 234.61 | 444.45 | 193.40 | 73.07 | 120.33 | 0.00 | 0.00 |
March | 279.75 | 455.02 | 223.71 | 79.54 | 144.16 | 0.00 | 0.00 |
April | 447.01 | 344.51 | 299.02 | 129.66 | 169.35 | 0.00 | 0.00 |
May | 426.13 | 307.12 | 305.55 | 116.54 | 189.01 | 0.00 | 0.00 |
June | 502.82 | 235.72 | 324.00 | 136.65 | 187.35 | 0.00 | 0.00 |
July | 587.57 | 208.35 | 335.90 | 152.76 | 183.14 | 0.00 | 0.00 |
August | 552.47 | 224.05 | 307.79 | 140.46 | 167.33 | 0.00 | 0.00 |
September | 448.94 | 250.32 | 262.74 | 117.58 | 145.16 | 0.00 | 0.00 |
October | 377.24 | 285.37 | 203.44 | 93.10 | 110.34 | 0.00 | 0.00 |
November | 260.85 | 420.28 | 183.92 | 80.69 | 103.23 | 0.00 | 0.00 |
December | 227.88 | 475.12 | 161.74 | 73.10 | 88.64 | 0.00 | 0.00 |
Annual Sum or Average | 381.28 | 343.29 | 247.12 | 105.24 | 141.89 | 0.00 | 0.00 |
Minimum of Months | 220.28 | 208.35 | 161.73 | 67.99 | 88.64 | 0.00 | 0.00 |
Maximum of Months | 587.57 | 475.12 | 335.90 | 152.76 | 189.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 247.31 | 181.12 | 143.82 | 104.77 | 39.05 | 0.00 | 0.00 |
February | 171.53 | 180.85 | 115.46 | 71.22 | 44.24 | 0.00 | 0.00 |
March | 133.19 | 183.86 | 94.70 | 47.23 | 47.46 | 0.00 | 0.00 |
April | 119.62 | 150.34 | 82.68 | 35.20 | 47.48 | 0.00 | 0.00 |
May | 54.13 | 141.15 | 57.17 | 9.25 | 47.92 | 0.00 | 0.00 |
June | 45.40 | 109.49 | 49.50 | 4.47 | 45.03 | 0.00 | 0.00 |
July | 66.69 | 94.15 | 53.14 | 8.09 | 45.05 | 0.00 | 0.00 |
August | 115.23 | 99.47 | 69.94 | 25.28 | 44.66 | 0.00 | 0.00 |
September | 163.65 | 113.23 | 93.17 | 48.40 | 44.77 | 0.00 | 0.00 |
October | 220.74 | 121.67 | 116.88 | 78.62 | 38.26 | 0.00 | 0.00 |
November | 235.17 | 167.25 | 139.20 | 97.95 | 41.25 | 0.00 | 0.00 |
December | 266.53 | 181.08 | 153.50 | 116.10 | 37.41 | 0.00 | 0.00 |
Annual Sum or Average | 153.25 | 143.43 | 97.35 | 53.82 | 43.53 | 0.00 | 0.00 |
Minimum of Months | 45.40 | 94.15 | 49.50 | 4.47 | 37.41 | 0.00 | 0.00 |
Maximum of Months | 266.53 | 183.86 | 153.50 | 116.10 | 47.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.22 | 139.04 | 22.21 | 0.00 | 22.21 | 0.00 | 0.00 |
February | 16.46 | 130.79 | 27.88 | 0.00 | 27.88 | 0.00 | 0.00 |
March | 25.72 | 133.47 | 34.17 | 0.00 | 34.17 | 0.00 | 0.00 |
April | 40.28 | 94.48 | 39.74 | 0.49 | 39.26 | 0.00 | 0.00 |
May | 50.08 | 82.06 | 48.43 | 3.30 | 45.12 | 0.00 | 0.00 |
June | 68.70 | 60.26 | 51.79 | 6.32 | 45.48 | 0.00 | 0.00 |
July | 77.16 | 52.20 | 49.05 | 5.30 | 43.75 | 0.00 | 0.00 |
August | 62.80 | 55.91 | 40.14 | 1.28 | 38.86 | 0.00 | 0.00 |
September | 47.70 | 67.01 | 33.56 | 0.01 | 33.54 | 0.00 | 0.00 |
October | 44.22 | 79.36 | 26.61 | 0.00 | 26.61 | 0.00 | 0.00 |
November | 19.13 | 122.23 | 24.09 | 0.00 | 24.09 | 0.00 | 0.00 |
December | 14.66 | 138.94 | 20.68 | 0.00 | 20.68 | 0.00 | 0.00 |
Annual Sum or Average | 40.42 | 96.14 | 34.89 | 1.40 | 33.49 | 0.00 | 0.00 |
Minimum of Months | 14.66 | 52.20 | 20.68 | 0.00 | 20.68 | 0.00 | 0.00 |
Maximum of Months | 77.16 | 139.04 | 51.79 | 6.32 | 45.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 537.86 | 438.11 | 320.18 | 206.32 | 113.87 | 0.00 | 0.00 |
February | 426.15 | 418.63 | 291.79 | 156.54 | 135.25 | 0.00 | 0.00 |
March | 438.02 | 430.69 | 297.31 | 138.44 | 158.87 | 0.00 | 0.00 |
April | 563.78 | 318.41 | 331.88 | 158.28 | 173.59 | 0.00 | 0.00 |
May | 440.89 | 286.40 | 286.88 | 101.00 | 185.88 | 0.00 | 0.00 |
June | 477.49 | 203.06 | 276.69 | 98.80 | 177.88 | 0.00 | 0.00 |
July | 607.79 | 165.77 | 309.37 | 130.60 | 178.76 | 0.00 | 0.00 |
August | 667.65 | 172.79 | 327.15 | 158.64 | 168.51 | 0.00 | 0.00 |
September | 568.72 | 211.27 | 292.14 | 141.35 | 150.79 | 0.00 | 0.00 |
October | 608.67 | 239.69 | 300.76 | 177.61 | 123.15 | 0.00 | 0.00 |
November | 526.69 | 388.79 | 315.22 | 194.16 | 121.05 | 0.00 | 0.00 |
December | 553.09 | 436.78 | 328.22 | 221.57 | 106.66 | 0.00 | 0.00 |
Annual Sum or Average | 535.63 | 308.62 | 306.61 | 157.04 | 149.57 | 0.00 | 0.00 |
Minimum of Months | 426.15 | 165.77 | 276.69 | 98.80 | 106.66 | 0.00 | 0.00 |
Maximum of Months | 667.65 | 438.11 | 331.88 | 221.57 | 185.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 214.99 | 451.33 | 168.14 | 75.34 | 92.80 | 0.00 | 0.00 |
February | 200.79 | 427.88 | 182.29 | 67.50 | 114.79 | 0.00 | 0.00 |
March | 270.66 | 436.02 | 221.62 | 79.39 | 142.24 | 0.00 | 0.00 |
April | 423.84 | 325.94 | 278.18 | 114.88 | 163.30 | 0.00 | 0.00 |
May | 390.57 | 293.49 | 275.93 | 93.57 | 182.36 | 0.00 | 0.00 |
June | 441.21 | 221.43 | 279.53 | 101.10 | 178.43 | 0.00 | 0.00 |
July | 542.05 | 195.05 | 304.23 | 127.12 | 177.11 | 0.00 | 0.00 |
August | 530.26 | 205.79 | 289.87 | 128.63 | 161.24 | 0.00 | 0.00 |
September | 373.01 | 233.97 | 217.59 | 80.85 | 136.74 | 0.00 | 0.00 |
October | 341.23 | 265.57 | 187.89 | 79.31 | 108.57 | 0.00 | 0.00 |
November | 219.43 | 401.34 | 171.30 | 71.70 | 99.60 | 0.00 | 0.00 |
December | 200.73 | 449.22 | 162.15 | 76.42 | 85.73 | 0.00 | 0.00 |
Annual Sum or Average | 346.72 | 325.07 | 228.51 | 91.50 | 137.01 | 0.00 | 0.00 |
Minimum of Months | 200.73 | 195.05 | 162.15 | 67.50 | 85.73 | 0.00 | 0.00 |
Maximum of Months | 542.05 | 451.33 | 304.23 | 128.63 | 182.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 675.87 | 665.42 | 447.51 | 282.41 | 165.10 | 0.00 | 0.00 |
February | 499.48 | 658.99 | 386.29 | 191.94 | 194.35 | 0.00 | 0.00 |
March | 431.56 | 682.93 | 347.19 | 127.20 | 219.99 | 0.00 | 0.00 |
April | 443.36 | 511.87 | 329.74 | 96.01 | 233.73 | 0.00 | 0.00 |
May | 299.68 | 451.12 | 284.46 | 33.72 | 250.75 | 0.00 | 0.00 |
June | 329.29 | 321.48 | 272.87 | 28.96 | 243.90 | 0.00 | 0.00 |
July | 408.11 | 269.51 | 275.24 | 35.95 | 239.30 | 0.00 | 0.00 |
August | 491.98 | 292.32 | 296.51 | 71.44 | 225.07 | 0.00 | 0.00 |
September | 572.43 | 355.59 | 341.37 | 130.33 | 211.05 | 0.00 | 0.00 |
October | 694.72 | 397.59 | 386.66 | 211.84 | 174.82 | 0.00 | 0.00 |
November | 662.33 | 600.73 | 440.11 | 264.02 | 176.09 | 0.00 | 0.00 |
December | 718.40 | 662.59 | 469.49 | 312.95 | 156.54 | 0.00 | 0.00 |
Annual Sum or Average | 519.28 | 488.24 | 356.32 | 148.75 | 207.57 | 0.00 | 0.00 |
Minimum of Months | 299.68 | 269.51 | 272.87 | 28.96 | 156.54 | 0.00 | 0.00 |
Maximum of Months | 718.40 | 682.93 | 469.49 | 312.95 | 250.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 514.77 | 438.67 | 313.78 | 198.98 | 114.80 | 0.00 | 0.00 |
February | 437.69 | 418.79 | 302.90 | 162.11 | 140.79 | 0.00 | 0.00 |
March | 428.63 | 437.82 | 299.39 | 138.59 | 160.80 | 0.00 | 0.00 |
April | 572.43 | 323.37 | 352.71 | 173.06 | 179.65 | 0.00 | 0.00 |
May | 462.67 | 289.28 | 316.50 | 123.98 | 192.53 | 0.00 | 0.00 |
June | 522.49 | 198.52 | 321.16 | 134.35 | 186.81 | 0.00 | 0.00 |
July | 629.03 | 160.95 | 341.04 | 156.24 | 184.79 | 0.00 | 0.00 |
August | 662.55 | 172.86 | 345.06 | 170.47 | 174.59 | 0.00 | 0.00 |
September | 626.82 | 208.56 | 337.29 | 178.08 | 159.21 | 0.00 | 0.00 |
October | 622.53 | 243.04 | 316.31 | 191.39 | 124.92 | 0.00 | 0.00 |
November | 540.09 | 388.19 | 327.84 | 203.15 | 124.69 | 0.00 | 0.00 |
December | 546.94 | 435.27 | 327.81 | 218.25 | 109.57 | 0.00 | 0.00 |
Annual Sum or Average | 547.92 | 309.04 | 325.23 | 170.78 | 154.45 | 0.00 | 0.00 |
Minimum of Months | 428.63 | 160.95 | 299.39 | 123.98 | 109.57 | 0.00 | 0.00 |
Maximum of Months | 662.55 | 438.67 | 352.71 | 218.25 | 192.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 212.74 | 459.94 | 161.73 | 67.99 | 93.73 | 0.00 | 0.00 |
February | 224.03 | 430.18 | 193.40 | 73.07 | 120.33 | 0.00 | 0.00 |
March | 264.27 | 445.95 | 223.71 | 79.54 | 144.16 | 0.00 | 0.00 |
April | 418.02 | 342.16 | 299.02 | 129.66 | 169.35 | 0.00 | 0.00 |
May | 396.07 | 306.52 | 305.55 | 116.54 | 189.01 | 0.00 | 0.00 |
June | 466.47 | 239.68 | 324.00 | 136.65 | 187.35 | 0.00 | 0.00 |
July | 550.42 | 214.79 | 335.90 | 152.76 | 183.14 | 0.00 | 0.00 |
August | 518.62 | 231.13 | 307.79 | 140.46 | 167.33 | 0.00 | 0.00 |
September | 423.69 | 249.81 | 262.74 | 117.58 | 145.16 | 0.00 | 0.00 |
October | 362.20 | 279.77 | 203.44 | 93.10 | 110.34 | 0.00 | 0.00 |
November | 250.89 | 407.44 | 183.92 | 80.69 | 103.23 | 0.00 | 0.00 |
December | 221.82 | 459.01 | 161.74 | 73.10 | 88.64 | 0.00 | 0.00 |
Annual Sum or Average | 359.88 | 338.43 | 247.12 | 105.24 | 141.89 | 0.00 | 0.00 |
Minimum of Months | 212.74 | 214.79 | 161.73 | 67.99 | 88.64 | 0.00 | 0.00 |
Maximum of Months | 550.42 | 459.94 | 335.90 | 152.76 | 189.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 488.17 | 229.49 | 263.71 | 192.10 | 71.61 | 0.00 | 0.00 |
February | 344.27 | 220.50 | 211.70 | 130.59 | 81.11 | 0.00 | 0.00 |
March | 275.24 | 232.50 | 173.63 | 86.60 | 87.03 | 0.00 | 0.00 |
April | 254.38 | 172.85 | 151.59 | 64.54 | 87.05 | 0.00 | 0.00 |
May | 135.94 | 155.62 | 104.83 | 16.96 | 87.87 | 0.00 | 0.00 |
June | 127.67 | 106.16 | 90.77 | 8.20 | 82.57 | 0.00 | 0.00 |
July | 170.81 | 84.10 | 97.44 | 14.83 | 82.61 | 0.00 | 0.00 |
August | 255.75 | 89.56 | 128.25 | 46.36 | 81.89 | 0.00 | 0.00 |
September | 339.26 | 109.94 | 170.84 | 88.75 | 82.09 | 0.00 | 0.00 |
October | 443.78 | 125.08 | 214.32 | 144.16 | 70.16 | 0.00 | 0.00 |
November | 465.89 | 203.27 | 255.23 | 179.60 | 75.63 | 0.00 | 0.00 |
December | 522.71 | 228.50 | 281.47 | 212.88 | 68.59 | 0.00 | 0.00 |
Annual Sum or Average | 318.68 | 162.82 | 178.50 | 98.68 | 79.82 | 0.00 | 0.00 |
Minimum of Months | 127.67 | 84.10 | 90.77 | 8.20 | 68.59 | 0.00 | 0.00 |
Maximum of Months | 522.71 | 232.50 | 281.47 | 212.88 | 87.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 105.91 | 1510.33 | 241.70 | 0.00 | 241.70 | 0.00 | 0.00 |
February | 103.86 | 1483.09 | 303.40 | 0.00 | 303.40 | 0.00 | 0.00 |
March | 177.56 | 1493.09 | 371.83 | 0.01 | 371.82 | 0.00 | 0.00 |
April | 276.34 | 1098.33 | 432.42 | 5.25 | 427.17 | 0.00 | 0.00 |
May | 356.65 | 952.04 | 526.87 | 35.83 | 491.04 | 0.00 | 0.00 |
June | 530.49 | 696.46 | 563.44 | 68.55 | 494.90 | 0.00 | 0.00 |
July | 610.02 | 594.00 | 533.56 | 57.53 | 476.03 | 0.00 | 0.00 |
August | 475.34 | 655.07 | 436.78 | 13.90 | 422.88 | 0.00 | 0.00 |
September | 353.51 | 794.86 | 365.14 | 0.14 | 365.00 | 0.00 | 0.00 |
October | 332.24 | 919.88 | 289.56 | 0.00 | 289.56 | 0.00 | 0.00 |
November | 123.67 | 1373.80 | 262.17 | 0.00 | 262.17 | 0.00 | 0.00 |
December | 92.53 | 1521.02 | 225.00 | 0.00 | 225.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.13 | 1088.87 | 379.66 | 15.19 | 364.47 | 0.00 | 0.00 |
Minimum of Months | 92.53 | 594.00 | 225.00 | 0.00 | 225.00 | 0.00 | 0.00 |
Maximum of Months | 610.02 | 1521.02 | 563.44 | 68.55 | 494.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 94.20 | 1559.12 | 241.70 | 0.00 | 241.70 | 0.00 | 0.00 |
February | 90.69 | 1533.75 | 303.40 | 0.00 | 303.40 | 0.00 | 0.00 |
March | 160.09 | 1539.08 | 371.83 | 0.01 | 371.82 | 0.00 | 0.00 |
April | 255.37 | 1126.72 | 432.42 | 5.25 | 427.17 | 0.00 | 0.00 |
May | 331.79 | 974.31 | 526.87 | 35.83 | 491.04 | 0.00 | 0.00 |
June | 507.90 | 711.86 | 563.44 | 68.55 | 494.90 | 0.00 | 0.00 |
July | 589.27 | 607.33 | 533.56 | 57.53 | 476.03 | 0.00 | 0.00 |
August | 455.91 | 670.62 | 436.78 | 13.90 | 422.88 | 0.00 | 0.00 |
September | 334.43 | 816.26 | 365.14 | 0.14 | 365.00 | 0.00 | 0.00 |
October | 314.54 | 946.88 | 289.56 | 0.00 | 289.56 | 0.00 | 0.00 |
November | 110.45 | 1417.36 | 262.17 | 0.00 | 262.17 | 0.00 | 0.00 |
December | 81.57 | 1569.68 | 225.00 | 0.00 | 225.00 | 0.00 | 0.00 |
Annual Sum or Average | 278.44 | 1120.52 | 379.66 | 15.19 | 364.47 | 0.00 | 0.00 |
Minimum of Months | 81.57 | 607.33 | 225.00 | 0.00 | 225.00 | 0.00 | 0.00 |
Maximum of Months | 589.27 | 1569.68 | 563.44 | 68.55 | 494.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 645.32 | 1348.90 | 607.35 | 350.30 | 257.05 | 0.00 | 0.00 |
February | 502.64 | 1409.08 | 589.62 | 278.63 | 310.99 | 0.00 | 0.00 |
March | 586.49 | 1398.03 | 645.46 | 270.94 | 374.52 | 0.00 | 0.00 |
April | 864.69 | 1066.56 | 758.73 | 339.71 | 419.02 | 0.00 | 0.00 |
May | 679.32 | 994.47 | 699.94 | 241.93 | 458.01 | 0.00 | 0.00 |
June | 767.50 | 767.61 | 691.70 | 248.53 | 443.18 | 0.00 | 0.00 |
July | 1025.50 | 659.89 | 763.06 | 320.43 | 442.63 | 0.00 | 0.00 |
August | 1090.65 | 705.92 | 767.36 | 357.22 | 410.14 | 0.00 | 0.00 |
September | 826.02 | 818.95 | 633.93 | 276.29 | 357.63 | 0.00 | 0.00 |
October | 827.31 | 903.20 | 607.74 | 319.52 | 288.22 | 0.00 | 0.00 |
November | 622.59 | 1250.35 | 605.11 | 330.66 | 274.45 | 0.00 | 0.00 |
December | 639.80 | 1352.44 | 609.89 | 370.61 | 239.29 | 0.00 | 0.00 |
Annual Sum or Average | 758.42 | 1054.27 | 665.53 | 309.09 | 356.44 | 0.00 | 0.00 |
Minimum of Months | 502.64 | 659.89 | 589.62 | 241.93 | 239.29 | 0.00 | 0.00 |
Maximum of Months | 1090.65 | 1409.08 | 767.36 | 370.61 | 458.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1412.90 | 1145.68 | 917.95 | 608.36 | 309.59 | 0.00 | 0.00 |
February | 1009.79 | 1148.41 | 774.30 | 413.47 | 360.83 | 0.00 | 0.00 |
March | 844.69 | 1191.08 | 677.03 | 274.00 | 403.03 | 0.00 | 0.00 |
April | 821.16 | 919.05 | 627.88 | 205.81 | 422.07 | 0.00 | 0.00 |
May | 495.27 | 823.05 | 512.35 | 65.80 | 446.55 | 0.00 | 0.00 |
June | 516.43 | 592.01 | 480.41 | 49.33 | 431.08 | 0.00 | 0.00 |
July | 666.76 | 496.20 | 491.21 | 66.47 | 424.75 | 0.00 | 0.00 |
August | 875.67 | 540.66 | 555.49 | 151.25 | 404.24 | 0.00 | 0.00 |
September | 1084.08 | 644.77 | 665.78 | 280.72 | 385.05 | 0.00 | 0.00 |
October | 1365.03 | 714.32 | 777.75 | 456.35 | 321.40 | 0.00 | 0.00 |
November | 1358.15 | 1053.82 | 898.11 | 568.76 | 329.35 | 0.00 | 0.00 |
December | 1502.65 | 1146.24 | 968.47 | 674.16 | 294.32 | 0.00 | 0.00 |
Annual Sum or Average | 996.49 | 866.35 | 695.21 | 317.54 | 377.67 | 0.00 | 0.00 |
Minimum of Months | 495.27 | 496.20 | 480.41 | 49.33 | 294.32 | 0.00 | 0.00 |
Maximum of Months | 1502.65 | 1191.08 | 968.47 | 674.16 | 446.55 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.464036E+10 | 0.181939E+10 | 0.263815E+10 | 0.192188E+10 | 0.716264E+09 | 0.00 | 0.00 |
February | 0.311827E+10 | 0.154170E+10 | 0.191262E+10 | 0.117980E+10 | 0.732822E+09 | 0.00 | 0.00 |
March | 0.275936E+10 | 0.177456E+10 | 0.173614E+10 | 0.865600E+09 | 0.870537E+09 | 0.00 | 0.00 |
April | 0.242483E+10 | 0.136809E+10 | 0.146639E+10 | 0.623713E+09 | 0.842674E+09 | 0.00 | 0.00 |
May | 0.141874E+10 | 0.124692E+10 | 0.104800E+10 | 0.169060E+09 | 0.878944E+09 | 0.00 | 0.00 |
June | 0.120674E+10 | 0.909154E+09 | 0.878205E+09 | 78973425.51 | 0.799232E+09 | 0.00 | 0.00 |
July | 0.155570E+10 | 0.818971E+09 | 0.973980E+09 | 0.147681E+09 | 0.826299E+09 | 0.00 | 0.00 |
August | 0.235133E+10 | 0.870830E+09 | 0.128183E+10 | 0.462757E+09 | 0.819075E+09 | 0.00 | 0.00 |
September | 0.308691E+10 | 0.988148E+09 | 0.165275E+10 | 0.858087E+09 | 0.794660E+09 | 0.00 | 0.00 |
October | 0.415283E+10 | 0.112099E+10 | 0.214342E+10 | 0.144165E+10 | 0.701767E+09 | 0.00 | 0.00 |
November | 0.433969E+10 | 0.158449E+10 | 0.247093E+10 | 0.173880E+10 | 0.732128E+09 | 0.00 | 0.00 |
December | 0.499585E+10 | 0.181950E+10 | 0.281585E+10 | 0.212973E+10 | 0.686113E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.360506E+11 | 0.158627E+11 | 0.210183E+11 | 0.116177E+11 | 0.940052E+10 | 0.00 | 0.00 |
Minimum of Months | 0.120674E+10 | 0.818971E+09 | 0.878205E+09 | 78973425.51 | 0.686113E+09 | 0.00 | 0.00 |
Maximum of Months | 0.499585E+10 | 0.181950E+10 | 0.281585E+10 | 0.212973E+10 | 0.878944E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.128454E+11 | 0.568210E+10 | 0.742885E+10 | 0.541190E+10 | 0.201695E+10 | 0.00 | 0.00 |
February | 0.854487E+10 | 0.501569E+10 | 0.538581E+10 | 0.332223E+10 | 0.206358E+10 | 0.00 | 0.00 |
March | 0.749569E+10 | 0.562057E+10 | 0.488885E+10 | 0.243747E+10 | 0.245137E+10 | 0.00 | 0.00 |
April | 0.654955E+10 | 0.452081E+10 | 0.412925E+10 | 0.175633E+10 | 0.237291E+10 | 0.00 | 0.00 |
May | 0.362404E+10 | 0.421662E+10 | 0.295111E+10 | 0.476063E+09 | 0.247505E+10 | 0.00 | 0.00 |
June | 0.304459E+10 | 0.313671E+10 | 0.247297E+10 | 0.222384E+09 | 0.225058E+10 | 0.00 | 0.00 |
July | 0.409878E+10 | 0.276360E+10 | 0.274266E+10 | 0.415861E+09 | 0.232680E+10 | 0.00 | 0.00 |
August | 0.637491E+10 | 0.290559E+10 | 0.360956E+10 | 0.130309E+10 | 0.230646E+10 | 0.00 | 0.00 |
September | 0.844881E+10 | 0.331538E+10 | 0.465403E+10 | 0.241632E+10 | 0.223771E+10 | 0.00 | 0.00 |
October | 0.114386E+11 | 0.369636E+10 | 0.603572E+10 | 0.405959E+10 | 0.197613E+10 | 0.00 | 0.00 |
November | 0.119729E+11 | 0.511214E+10 | 0.695797E+10 | 0.489635E+10 | 0.206162E+10 | 0.00 | 0.00 |
December | 0.138424E+11 | 0.569554E+10 | 0.792924E+10 | 0.599719E+10 | 0.193205E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.982805E+11 | 0.516811E+11 | 0.591860E+11 | 0.327148E+11 | 0.264712E+11 | 0.00 | 0.00 |
Minimum of Months | 0.304459E+10 | 0.276360E+10 | 0.247297E+10 | 0.222384E+09 | 0.193205E+10 | 0.00 | 0.00 |
Maximum of Months | 0.138424E+11 | 0.569554E+10 | 0.792924E+10 | 0.599719E+10 | 0.247505E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.172224E+11 | 0.772067E+10 | 0.965050E+10 | 0.703036E+10 | 0.262013E+10 | 0.00 | 0.00 |
February | 0.115419E+11 | 0.673431E+10 | 0.699648E+10 | 0.431577E+10 | 0.268071E+10 | 0.00 | 0.00 |
March | 0.102052E+11 | 0.771462E+10 | 0.635089E+10 | 0.316642E+10 | 0.318447E+10 | 0.00 | 0.00 |
April | 0.904279E+10 | 0.597649E+10 | 0.536413E+10 | 0.228158E+10 | 0.308255E+10 | 0.00 | 0.00 |
May | 0.522214E+10 | 0.556670E+10 | 0.383366E+10 | 0.618433E+09 | 0.321523E+10 | 0.00 | 0.00 |
June | 0.445329E+10 | 0.408789E+10 | 0.321253E+10 | 0.288889E+09 | 0.292364E+10 | 0.00 | 0.00 |
July | 0.583865E+10 | 0.360841E+10 | 0.356288E+10 | 0.540227E+09 | 0.302265E+10 | 0.00 | 0.00 |
August | 0.880972E+10 | 0.378685E+10 | 0.468902E+10 | 0.169279E+10 | 0.299622E+10 | 0.00 | 0.00 |
September | 0.115091E+11 | 0.430309E+10 | 0.604584E+10 | 0.313893E+10 | 0.290691E+10 | 0.00 | 0.00 |
October | 0.154565E+11 | 0.481110E+10 | 0.784074E+10 | 0.527363E+10 | 0.256711E+10 | 0.00 | 0.00 |
November | 0.161053E+11 | 0.678000E+10 | 0.903881E+10 | 0.636064E+10 | 0.267817E+10 | 0.00 | 0.00 |
December | 0.185337E+11 | 0.771803E+10 | 0.103005E+11 | 0.779069E+10 | 0.250984E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.133941E+12 | 0.688082E+11 | 0.768860E+11 | 0.424984E+11 | 0.343876E+11 | 0.00 | 0.00 |
Minimum of Months | 0.445329E+10 | 0.360841E+10 | 0.321253E+10 | 0.288889E+09 | 0.250984E+10 | 0.00 | 0.00 |
Maximum of Months | 0.185337E+11 | 0.772067E+10 | 0.103005E+11 | 0.779069E+10 | 0.321523E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.141456E+10 | 0.120302E+10 | 0.840418E+09 | 0.532940E+09 | 0.307478E+09 | 0.00 | 0.00 |
February | 0.110261E+10 | 0.104052E+10 | 0.732772E+09 | 0.392173E+09 | 0.340599E+09 | 0.00 | 0.00 |
March | 0.120026E+10 | 0.119475E+10 | 0.801894E+09 | 0.371212E+09 | 0.430682E+09 | 0.00 | 0.00 |
April | 0.156199E+10 | 0.853958E+09 | 0.914227E+09 | 0.448576E+09 | 0.465651E+09 | 0.00 | 0.00 |
May | 0.131732E+10 | 0.786839E+09 | 0.847719E+09 | 0.332059E+09 | 0.515659E+09 | 0.00 | 0.00 |
June | 0.143525E+10 | 0.524559E+09 | 0.832446E+09 | 0.348246E+09 | 0.484201E+09 | 0.00 | 0.00 |
July | 0.176925E+10 | 0.439901E+09 | 0.913437E+09 | 0.418484E+09 | 0.494953E+09 | 0.00 | 0.00 |
August | 0.185940E+10 | 0.470066E+09 | 0.924209E+09 | 0.456590E+09 | 0.467619E+09 | 0.00 | 0.00 |
September | 0.169640E+10 | 0.554624E+09 | 0.874256E+09 | 0.461585E+09 | 0.412671E+09 | 0.00 | 0.00 |
October | 0.172382E+10 | 0.667322E+09 | 0.847206E+09 | 0.512628E+09 | 0.334578E+09 | 0.00 | 0.00 |
November | 0.144600E+10 | 0.103079E+10 | 0.849753E+09 | 0.526561E+09 | 0.323192E+09 | 0.00 | 0.00 |
December | 0.150196E+10 | 0.119578E+10 | 0.878015E+09 | 0.584553E+09 | 0.293462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.180288E+11 | 0.996213E+10 | 0.102564E+11 | 0.538561E+10 | 0.487075E+10 | 0.00 | 0.00 |
Minimum of Months | 0.110261E+10 | 0.439901E+09 | 0.732772E+09 | 0.332059E+09 | 0.293462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185940E+10 | 0.120302E+10 | 0.924209E+09 | 0.584553E+09 | 0.515659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.590004E+09 | 0.127236E+10 | 0.433174E+09 | 0.182116E+09 | 0.251058E+09 | 0.00 | 0.00 |
February | 0.567576E+09 | 0.107523E+10 | 0.467863E+09 | 0.176759E+09 | 0.291104E+09 | 0.00 | 0.00 |
March | 0.749273E+09 | 0.121872E+10 | 0.599176E+09 | 0.213052E+09 | 0.386124E+09 | 0.00 | 0.00 |
April | 0.115864E+10 | 0.892963E+09 | 0.775048E+09 | 0.336080E+09 | 0.438968E+09 | 0.00 | 0.00 |
May | 0.114136E+10 | 0.822593E+09 | 0.818387E+09 | 0.312146E+09 | 0.506240E+09 | 0.00 | 0.00 |
June | 0.130331E+10 | 0.610974E+09 | 0.839815E+09 | 0.354204E+09 | 0.485611E+09 | 0.00 | 0.00 |
July | 0.157374E+10 | 0.558053E+09 | 0.899680E+09 | 0.409150E+09 | 0.490530E+09 | 0.00 | 0.00 |
August | 0.147974E+10 | 0.600084E+09 | 0.824379E+09 | 0.376214E+09 | 0.448165E+09 | 0.00 | 0.00 |
September | 0.116364E+10 | 0.648831E+09 | 0.681017E+09 | 0.304770E+09 | 0.376247E+09 | 0.00 | 0.00 |
October | 0.101040E+10 | 0.764346E+09 | 0.544881E+09 | 0.249354E+09 | 0.295527E+09 | 0.00 | 0.00 |
November | 0.676135E+09 | 0.108937E+10 | 0.476713E+09 | 0.209141E+09 | 0.267572E+09 | 0.00 | 0.00 |
December | 0.610340E+09 | 0.127256E+10 | 0.433195E+09 | 0.195785E+09 | 0.237410E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.120242E+11 | 0.108261E+11 | 0.779333E+10 | 0.331877E+10 | 0.447455E+10 | 0.00 | 0.00 |
Minimum of Months | 0.567576E+09 | 0.558053E+09 | 0.433174E+09 | 0.176759E+09 | 0.237410E+09 | 0.00 | 0.00 |
Maximum of Months | 0.157374E+10 | 0.127256E+10 | 0.899680E+09 | 0.409150E+09 | 0.506240E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.662390E+09 | 0.485112E+09 | 0.385202E+09 | 0.280604E+09 | 0.104598E+09 | 0.00 | 0.00 |
February | 0.414958E+09 | 0.437506E+09 | 0.279313E+09 | 0.172296E+09 | 0.107016E+09 | 0.00 | 0.00 |
March | 0.356729E+09 | 0.492448E+09 | 0.253632E+09 | 0.126505E+09 | 0.127127E+09 | 0.00 | 0.00 |
April | 0.310056E+09 | 0.389693E+09 | 0.214294E+09 | 91235614.03 | 0.123058E+09 | 0.00 | 0.00 |
May | 0.144994E+09 | 0.378058E+09 | 0.153126E+09 | 24771048.33 | 0.128355E+09 | 0.00 | 0.00 |
June | 0.117675E+09 | 0.283788E+09 | 0.128313E+09 | 11598474.00 | 0.116715E+09 | 0.00 | 0.00 |
July | 0.178631E+09 | 0.252179E+09 | 0.142330E+09 | 21662387.38 | 0.120667E+09 | 0.00 | 0.00 |
August | 0.308639E+09 | 0.266408E+09 | 0.187334E+09 | 67722075.46 | 0.119612E+09 | 0.00 | 0.00 |
September | 0.424176E+09 | 0.293483E+09 | 0.241506E+09 | 0.125460E+09 | 0.116047E+09 | 0.00 | 0.00 |
October | 0.591239E+09 | 0.325874E+09 | 0.313059E+09 | 0.210578E+09 | 0.102481E+09 | 0.00 | 0.00 |
November | 0.609565E+09 | 0.433500E+09 | 0.360801E+09 | 0.253885E+09 | 0.106915E+09 | 0.00 | 0.00 |
December | 0.713883E+09 | 0.485017E+09 | 0.411148E+09 | 0.310952E+09 | 0.100195E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.483293E+10 | 0.452307E+10 | 0.307006E+10 | 0.169727E+10 | 0.137279E+10 | 0.00 | 0.00 |
Minimum of Months | 0.117675E+09 | 0.252179E+09 | 0.128313E+09 | 11598474.00 | 0.100195E+09 | 0.00 | 0.00 |
Maximum of Months | 0.713883E+09 | 0.492448E+09 | 0.411148E+09 | 0.310952E+09 | 0.128355E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 43432255.16 | 0.372412E+09 | 59491097.88 | 0.00 | 59491097.88 | 0.00 | 0.00 |
February | 39830694.50 | 0.316395E+09 | 67450417.55 | 0.00 | 67450417.55 | 0.00 | 0.00 |
March | 68881595.30 | 0.357478E+09 | 91520372.78 | 1715.04 | 91518657.74 | 0.00 | 0.00 |
April | 0.104414E+09 | 0.244890E+09 | 0.103007E+09 | 1257399.95 | 0.101750E+09 | 0.00 | 0.00 |
May | 0.134129E+09 | 0.219791E+09 | 0.129708E+09 | 8846804.40 | 0.120862E+09 | 0.00 | 0.00 |
June | 0.178082E+09 | 0.156201E+09 | 0.134251E+09 | 16369510.67 | 0.117881E+09 | 0.00 | 0.00 |
July | 0.206662E+09 | 0.139806E+09 | 0.131369E+09 | 14201444.08 | 0.117168E+09 | 0.00 | 0.00 |
August | 0.168195E+09 | 0.149746E+09 | 0.107522E+09 | 3435470.24 | 0.104086E+09 | 0.00 | 0.00 |
September | 0.123641E+09 | 0.173691E+09 | 86974691.39 | 32975.43 | 86941715.96 | 0.00 | 0.00 |
October | 0.118442E+09 | 0.212557E+09 | 71270318.00 | 0.00 | 71270318.00 | 0.00 | 0.00 |
November | 49591431.21 | 0.316818E+09 | 62448557.60 | 0.00 | 62448557.60 | 0.00 | 0.00 |
December | 39263856.01 | 0.372146E+09 | 55381136.09 | 0.00 | 55381136.09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127456E+10 | 0.303193E+10 | 0.110039E+10 | 44145319.82 | 0.105625E+10 | 0.00 | 0.00 |
Minimum of Months | 39263856.01 | 0.139806E+09 | 55381136.09 | 0.00 | 55381136.09 | 0.00 | 0.00 |
Maximum of Months | 0.206662E+09 | 0.372412E+09 | 0.134251E+09 | 16369510.67 | 0.120862E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144061E+10 | 0.117344E+10 | 0.857582E+09 | 0.552602E+09 | 0.304980E+09 | 0.00 | 0.00 |
February | 0.103095E+10 | 0.101274E+10 | 0.705893E+09 | 0.378705E+09 | 0.327188E+09 | 0.00 | 0.00 |
March | 0.117319E+10 | 0.115356E+10 | 0.796318E+09 | 0.370791E+09 | 0.425527E+09 | 0.00 | 0.00 |
April | 0.146131E+10 | 0.825320E+09 | 0.860221E+09 | 0.410267E+09 | 0.449954E+09 | 0.00 | 0.00 |
May | 0.118088E+10 | 0.767081E+09 | 0.768382E+09 | 0.270531E+09 | 0.497851E+09 | 0.00 | 0.00 |
June | 0.123766E+10 | 0.526332E+09 | 0.717170E+09 | 0.256098E+09 | 0.461073E+09 | 0.00 | 0.00 |
July | 0.162789E+10 | 0.444006E+09 | 0.828604E+09 | 0.349809E+09 | 0.478794E+09 | 0.00 | 0.00 |
August | 0.178824E+10 | 0.462807E+09 | 0.876227E+09 | 0.424895E+09 | 0.451332E+09 | 0.00 | 0.00 |
September | 0.147411E+10 | 0.547610E+09 | 0.757238E+09 | 0.366380E+09 | 0.390857E+09 | 0.00 | 0.00 |
October | 0.163027E+10 | 0.641994E+09 | 0.805558E+09 | 0.475701E+09 | 0.329857E+09 | 0.00 | 0.00 |
November | 0.136518E+10 | 0.100775E+10 | 0.817045E+09 | 0.503271E+09 | 0.313775E+09 | 0.00 | 0.00 |
December | 0.148140E+10 | 0.116987E+10 | 0.879112E+09 | 0.593444E+09 | 0.285668E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168917E+11 | 0.973250E+10 | 0.966935E+10 | 0.495249E+10 | 0.471686E+10 | 0.00 | 0.00 |
Minimum of Months | 0.103095E+10 | 0.444006E+09 | 0.705893E+09 | 0.256098E+09 | 0.285668E+09 | 0.00 | 0.00 |
Maximum of Months | 0.178824E+10 | 0.117344E+10 | 0.879112E+09 | 0.593444E+09 | 0.497851E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.575838E+09 | 0.120884E+10 | 0.450338E+09 | 0.201778E+09 | 0.248560E+09 | 0.00 | 0.00 |
February | 0.485753E+09 | 0.103512E+10 | 0.440984E+09 | 0.163291E+09 | 0.277693E+09 | 0.00 | 0.00 |
March | 0.724930E+09 | 0.116785E+10 | 0.593600E+09 | 0.212631E+09 | 0.380969E+09 | 0.00 | 0.00 |
April | 0.109860E+10 | 0.844837E+09 | 0.721041E+09 | 0.297771E+09 | 0.423270E+09 | 0.00 | 0.00 |
May | 0.104611E+10 | 0.786074E+09 | 0.739050E+09 | 0.250618E+09 | 0.488432E+09 | 0.00 | 0.00 |
June | 0.114362E+10 | 0.573950E+09 | 0.724538E+09 | 0.262056E+09 | 0.462483E+09 | 0.00 | 0.00 |
July | 0.145182E+10 | 0.522418E+09 | 0.814846E+09 | 0.340475E+09 | 0.474371E+09 | 0.00 | 0.00 |
August | 0.142025E+10 | 0.551198E+09 | 0.776396E+09 | 0.344519E+09 | 0.431877E+09 | 0.00 | 0.00 |
September | 0.966851E+09 | 0.606452E+09 | 0.563998E+09 | 0.209566E+09 | 0.354433E+09 | 0.00 | 0.00 |
October | 0.913961E+09 | 0.711290E+09 | 0.503232E+09 | 0.212427E+09 | 0.290806E+09 | 0.00 | 0.00 |
November | 0.568751E+09 | 0.104028E+10 | 0.444005E+09 | 0.185851E+09 | 0.258154E+09 | 0.00 | 0.00 |
December | 0.537640E+09 | 0.120318E+10 | 0.434292E+09 | 0.204677E+09 | 0.229616E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109341E+11 | 0.102515E+11 | 0.720632E+10 | 0.288566E+10 | 0.432066E+10 | 0.00 | 0.00 |
Minimum of Months | 0.485753E+09 | 0.522418E+09 | 0.434292E+09 | 0.163291E+09 | 0.229616E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145182E+10 | 0.120884E+10 | 0.814846E+09 | 0.344519E+09 | 0.488432E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181024E+10 | 0.178227E+10 | 0.119861E+10 | 0.756400E+09 | 0.442206E+09 | 0.00 | 0.00 |
February | 0.120834E+10 | 0.159424E+10 | 0.934507E+09 | 0.464336E+09 | 0.470171E+09 | 0.00 | 0.00 |
March | 0.115589E+10 | 0.182917E+10 | 0.929906E+09 | 0.340681E+09 | 0.589226E+09 | 0.00 | 0.00 |
April | 0.114920E+10 | 0.132676E+10 | 0.854674E+09 | 0.248847E+09 | 0.605828E+09 | 0.00 | 0.00 |
May | 0.802666E+09 | 0.120827E+10 | 0.761905E+09 | 90302833.84 | 0.671602E+09 | 0.00 | 0.00 |
June | 0.853521E+09 | 0.833280E+09 | 0.707276E+09 | 75077104.75 | 0.632199E+09 | 0.00 | 0.00 |
July | 0.109309E+10 | 0.721861E+09 | 0.737208E+09 | 96277974.31 | 0.640930E+09 | 0.00 | 0.00 |
August | 0.131771E+10 | 0.782963E+09 | 0.794182E+09 | 0.191345E+09 | 0.602836E+09 | 0.00 | 0.00 |
September | 0.148373E+10 | 0.921685E+09 | 0.884837E+09 | 0.337807E+09 | 0.547030E+09 | 0.00 | 0.00 |
October | 0.186073E+10 | 0.106492E+10 | 0.103563E+10 | 0.567393E+09 | 0.468241E+09 | 0.00 | 0.00 |
November | 0.171676E+10 | 0.155708E+10 | 0.114076E+10 | 0.684344E+09 | 0.456419E+09 | 0.00 | 0.00 |
December | 0.192417E+10 | 0.177469E+10 | 0.125747E+10 | 0.838204E+09 | 0.419265E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.163761E+11 | 0.153972E+11 | 0.112370E+11 | 0.469101E+10 | 0.654595E+10 | 0.00 | 0.00 |
Minimum of Months | 0.802666E+09 | 0.721861E+09 | 0.707276E+09 | 75077104.75 | 0.419265E+09 | 0.00 | 0.00 |
Maximum of Months | 0.192417E+10 | 0.182917E+10 | 0.125747E+10 | 0.838204E+09 | 0.671602E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137877E+10 | 0.117492E+10 | 0.840418E+09 | 0.532940E+09 | 0.307478E+09 | 0.00 | 0.00 |
February | 0.105886E+10 | 0.101313E+10 | 0.732772E+09 | 0.392173E+09 | 0.340599E+09 | 0.00 | 0.00 |
March | 0.114803E+10 | 0.117265E+10 | 0.801894E+09 | 0.371212E+09 | 0.430682E+09 | 0.00 | 0.00 |
April | 0.148373E+10 | 0.838179E+09 | 0.914227E+09 | 0.448576E+09 | 0.465651E+09 | 0.00 | 0.00 |
May | 0.123922E+10 | 0.774816E+09 | 0.847719E+09 | 0.332059E+09 | 0.515659E+09 | 0.00 | 0.00 |
June | 0.135429E+10 | 0.514568E+09 | 0.832446E+09 | 0.348246E+09 | 0.484201E+09 | 0.00 | 0.00 |
July | 0.168479E+10 | 0.431095E+09 | 0.913437E+09 | 0.418484E+09 | 0.494953E+09 | 0.00 | 0.00 |
August | 0.177457E+10 | 0.462999E+09 | 0.924209E+09 | 0.456590E+09 | 0.467619E+09 | 0.00 | 0.00 |
September | 0.162472E+10 | 0.540587E+09 | 0.874256E+09 | 0.461585E+09 | 0.412671E+09 | 0.00 | 0.00 |
October | 0.166739E+10 | 0.650954E+09 | 0.847206E+09 | 0.512628E+09 | 0.334578E+09 | 0.00 | 0.00 |
November | 0.139991E+10 | 0.100619E+10 | 0.849753E+09 | 0.526561E+09 | 0.323192E+09 | 0.00 | 0.00 |
December | 0.146491E+10 | 0.116584E+10 | 0.878015E+09 | 0.584553E+09 | 0.293462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172792E+11 | 0.974593E+10 | 0.102564E+11 | 0.538561E+10 | 0.487075E+10 | 0.00 | 0.00 |
Minimum of Months | 0.105886E+10 | 0.431095E+09 | 0.732772E+09 | 0.332059E+09 | 0.293462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.177457E+10 | 0.117492E+10 | 0.924209E+09 | 0.584553E+09 | 0.515659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.569793E+09 | 0.123190E+10 | 0.433174E+09 | 0.182116E+09 | 0.251058E+09 | 0.00 | 0.00 |
February | 0.541970E+09 | 0.104068E+10 | 0.467863E+09 | 0.176759E+09 | 0.291104E+09 | 0.00 | 0.00 |
March | 0.707815E+09 | 0.119444E+10 | 0.599176E+09 | 0.213052E+09 | 0.386124E+09 | 0.00 | 0.00 |
April | 0.108352E+10 | 0.886876E+09 | 0.775048E+09 | 0.336080E+09 | 0.438968E+09 | 0.00 | 0.00 |
May | 0.106085E+10 | 0.820986E+09 | 0.818387E+09 | 0.312146E+09 | 0.506240E+09 | 0.00 | 0.00 |
June | 0.120909E+10 | 0.621253E+09 | 0.839815E+09 | 0.354204E+09 | 0.485611E+09 | 0.00 | 0.00 |
July | 0.147426E+10 | 0.575283E+09 | 0.899680E+09 | 0.409150E+09 | 0.490530E+09 | 0.00 | 0.00 |
August | 0.138906E+10 | 0.619045E+09 | 0.824379E+09 | 0.376214E+09 | 0.448165E+09 | 0.00 | 0.00 |
September | 0.109822E+10 | 0.647513E+09 | 0.681017E+09 | 0.304770E+09 | 0.376247E+09 | 0.00 | 0.00 |
October | 0.970126E+09 | 0.749327E+09 | 0.544881E+09 | 0.249354E+09 | 0.295527E+09 | 0.00 | 0.00 |
November | 0.650314E+09 | 0.105607E+10 | 0.476713E+09 | 0.209141E+09 | 0.267572E+09 | 0.00 | 0.00 |
December | 0.594123E+09 | 0.122941E+10 | 0.433195E+09 | 0.195785E+09 | 0.237410E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113491E+11 | 0.106728E+11 | 0.779333E+10 | 0.331877E+10 | 0.447455E+10 | 0.00 | 0.00 |
Minimum of Months | 0.541970E+09 | 0.575283E+09 | 0.433174E+09 | 0.176759E+09 | 0.237410E+09 | 0.00 | 0.00 |
Maximum of Months | 0.147426E+10 | 0.123190E+10 | 0.899680E+09 | 0.409150E+09 | 0.506240E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.130751E+10 | 0.614672E+09 | 0.706310E+09 | 0.514517E+09 | 0.191793E+09 | 0.00 | 0.00 |
February | 0.832848E+09 | 0.533424E+09 | 0.512151E+09 | 0.315924E+09 | 0.196226E+09 | 0.00 | 0.00 |
March | 0.737192E+09 | 0.622721E+09 | 0.465063E+09 | 0.231961E+09 | 0.233102E+09 | 0.00 | 0.00 |
April | 0.659350E+09 | 0.448029E+09 | 0.392932E+09 | 0.167290E+09 | 0.225641E+09 | 0.00 | 0.00 |
May | 0.364095E+09 | 0.416817E+09 | 0.280774E+09 | 45420430.68 | 0.235353E+09 | 0.00 | 0.00 |
June | 0.330918E+09 | 0.275155E+09 | 0.235276E+09 | 21267072.64 | 0.214009E+09 | 0.00 | 0.00 |
July | 0.457490E+09 | 0.225265E+09 | 0.260977E+09 | 39720360.29 | 0.221256E+09 | 0.00 | 0.00 |
August | 0.684999E+09 | 0.239888E+09 | 0.343498E+09 | 0.124176E+09 | 0.219322E+09 | 0.00 | 0.00 |
September | 0.879372E+09 | 0.284960E+09 | 0.442828E+09 | 0.230044E+09 | 0.212785E+09 | 0.00 | 0.00 |
October | 0.118862E+10 | 0.335005E+09 | 0.574028E+09 | 0.386117E+09 | 0.187911E+09 | 0.00 | 0.00 |
November | 0.120758E+10 | 0.526882E+09 | 0.661567E+09 | 0.465527E+09 | 0.196041E+09 | 0.00 | 0.00 |
December | 0.140002E+10 | 0.612024E+09 | 0.753884E+09 | 0.570165E+09 | 0.183719E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100500E+11 | 0.513484E+10 | 0.562929E+10 | 0.311213E+10 | 0.251716E+10 | 0.00 | 0.00 |
Minimum of Months | 0.330918E+09 | 0.225265E+09 | 0.235276E+09 | 21267072.64 | 0.183719E+09 | 0.00 | 0.00 |
Maximum of Months | 0.140002E+10 | 0.622721E+09 | 0.753884E+09 | 0.570165E+09 | 0.235353E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.283670E+09 | 0.404526E+10 | 0.647374E+09 | 0.00 | 0.647374E+09 | 0.00 | 0.00 |
February | 0.251258E+09 | 0.358789E+10 | 0.733986E+09 | 0.00 | 0.733986E+09 | 0.00 | 0.00 |
March | 0.475580E+09 | 0.399911E+10 | 0.995912E+09 | 18416.29 | 0.995893E+09 | 0.00 | 0.00 |
April | 0.716284E+09 | 0.284688E+10 | 0.112084E+10 | 13612672.38 | 0.110722E+10 | 0.00 | 0.00 |
May | 0.955255E+09 | 0.254994E+10 | 0.141117E+10 | 95973729.27 | 0.131520E+10 | 0.00 | 0.00 |
June | 0.137504E+10 | 0.180522E+10 | 0.146044E+10 | 0.177670E+09 | 0.128277E+10 | 0.00 | 0.00 |
July | 0.163388E+10 | 0.159097E+10 | 0.142909E+10 | 0.154083E+09 | 0.127501E+10 | 0.00 | 0.00 |
August | 0.127314E+10 | 0.175455E+10 | 0.116987E+10 | 37222065.74 | 0.113265E+10 | 0.00 | 0.00 |
September | 0.916285E+09 | 0.206028E+10 | 0.946443E+09 | 354910.42 | 0.946088E+09 | 0.00 | 0.00 |
October | 0.889865E+09 | 0.246380E+10 | 0.775554E+09 | 0.00 | 0.775554E+09 | 0.00 | 0.00 |
November | 0.320546E+09 | 0.356089E+10 | 0.679557E+09 | 0.00 | 0.679557E+09 | 0.00 | 0.00 |
December | 0.247824E+09 | 0.407389E+10 | 0.602650E+09 | 0.00 | 0.602650E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.933863E+10 | 0.343387E+11 | 0.119729E+11 | 0.478936E+09 | 0.114940E+11 | 0.00 | 0.00 |
Minimum of Months | 0.247824E+09 | 0.159097E+10 | 0.602650E+09 | 0.00 | 0.602650E+09 | 0.00 | 0.00 |
Maximum of Months | 0.163388E+10 | 0.407389E+10 | 0.146044E+10 | 0.177670E+09 | 0.131520E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.252318E+09 | 0.417594E+10 | 0.647374E+09 | 0.00 | 0.647374E+09 | 0.00 | 0.00 |
February | 0.219399E+09 | 0.371045E+10 | 0.733986E+09 | 0.00 | 0.733986E+09 | 0.00 | 0.00 |
March | 0.428772E+09 | 0.412228E+10 | 0.995912E+09 | 18416.29 | 0.995893E+09 | 0.00 | 0.00 |
April | 0.661926E+09 | 0.292047E+10 | 0.112084E+10 | 13612672.38 | 0.110722E+10 | 0.00 | 0.00 |
May | 0.888655E+09 | 0.260959E+10 | 0.141117E+10 | 95973729.27 | 0.131520E+10 | 0.00 | 0.00 |
June | 0.131649E+10 | 0.184513E+10 | 0.146044E+10 | 0.177670E+09 | 0.128277E+10 | 0.00 | 0.00 |
July | 0.157829E+10 | 0.162668E+10 | 0.142909E+10 | 0.154083E+09 | 0.127501E+10 | 0.00 | 0.00 |
August | 0.122112E+10 | 0.179618E+10 | 0.116987E+10 | 37222065.74 | 0.113265E+10 | 0.00 | 0.00 |
September | 0.866840E+09 | 0.211574E+10 | 0.946443E+09 | 354910.42 | 0.946088E+09 | 0.00 | 0.00 |
October | 0.842459E+09 | 0.253611E+10 | 0.775554E+09 | 0.00 | 0.775554E+09 | 0.00 | 0.00 |
November | 0.286294E+09 | 0.367380E+10 | 0.679557E+09 | 0.00 | 0.679557E+09 | 0.00 | 0.00 |
December | 0.218475E+09 | 0.420423E+10 | 0.602650E+09 | 0.00 | 0.602650E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.878104E+10 | 0.353366E+11 | 0.119729E+11 | 0.478936E+09 | 0.114940E+11 | 0.00 | 0.00 |
Minimum of Months | 0.218475E+09 | 0.162668E+10 | 0.602650E+09 | 0.00 | 0.602650E+09 | 0.00 | 0.00 |
Maximum of Months | 0.157829E+10 | 0.420423E+10 | 0.146044E+10 | 0.177670E+09 | 0.131520E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.172841E+10 | 0.361288E+10 | 0.162673E+10 | 0.938240E+09 | 0.688492E+09 | 0.00 | 0.00 |
February | 0.121599E+10 | 0.340886E+10 | 0.142641E+10 | 0.674063E+09 | 0.752350E+09 | 0.00 | 0.00 |
March | 0.157086E+10 | 0.374449E+10 | 0.172880E+10 | 0.725684E+09 | 0.100312E+10 | 0.00 | 0.00 |
April | 0.224128E+10 | 0.276451E+10 | 0.196663E+10 | 0.880516E+09 | 0.108611E+10 | 0.00 | 0.00 |
May | 0.181948E+10 | 0.266359E+10 | 0.187473E+10 | 0.647998E+09 | 0.122673E+10 | 0.00 | 0.00 |
June | 0.198936E+10 | 0.198964E+10 | 0.179289E+10 | 0.644182E+09 | 0.114871E+10 | 0.00 | 0.00 |
July | 0.274670E+10 | 0.176745E+10 | 0.204377E+10 | 0.858228E+09 | 0.118554E+10 | 0.00 | 0.00 |
August | 0.292121E+10 | 0.189074E+10 | 0.205530E+10 | 0.956771E+09 | 0.109853E+10 | 0.00 | 0.00 |
September | 0.214104E+10 | 0.212273E+10 | 0.164314E+10 | 0.716154E+09 | 0.926988E+09 | 0.00 | 0.00 |
October | 0.221586E+10 | 0.241913E+10 | 0.162777E+10 | 0.855797E+09 | 0.771977E+09 | 0.00 | 0.00 |
November | 0.161376E+10 | 0.324090E+10 | 0.156844E+10 | 0.857071E+09 | 0.711364E+09 | 0.00 | 0.00 |
December | 0.171363E+10 | 0.362238E+10 | 0.163354E+10 | 0.992632E+09 | 0.640909E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239176E+11 | 0.332473E+11 | 0.209882E+11 | 0.974734E+10 | 0.112408E+11 | 0.00 | 0.00 |
Minimum of Months | 0.121599E+10 | 0.176745E+10 | 0.142641E+10 | 0.644182E+09 | 0.640909E+09 | 0.00 | 0.00 |
Maximum of Months | 0.292121E+10 | 0.374449E+10 | 0.205530E+10 | 0.992632E+09 | 0.122673E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.378431E+10 | 0.306859E+10 | 0.245863E+10 | 0.162944E+10 | 0.829193E+09 | 0.00 | 0.00 |
February | 0.244288E+10 | 0.277823E+10 | 0.187319E+10 | 0.100027E+10 | 0.872923E+09 | 0.00 | 0.00 |
March | 0.226242E+10 | 0.319019E+10 | 0.181335E+10 | 0.733891E+09 | 0.107946E+10 | 0.00 | 0.00 |
April | 0.212845E+10 | 0.238219E+10 | 0.162748E+10 | 0.533471E+09 | 0.109401E+10 | 0.00 | 0.00 |
May | 0.132652E+10 | 0.220445E+10 | 0.137229E+10 | 0.176235E+09 | 0.119605E+10 | 0.00 | 0.00 |
June | 0.133858E+10 | 0.153450E+10 | 0.124521E+10 | 0.127862E+09 | 0.111735E+10 | 0.00 | 0.00 |
July | 0.178585E+10 | 0.132903E+10 | 0.131567E+10 | 0.178029E+09 | 0.113764E+10 | 0.00 | 0.00 |
August | 0.234538E+10 | 0.144812E+10 | 0.148782E+10 | 0.405101E+09 | 0.108271E+10 | 0.00 | 0.00 |
September | 0.280994E+10 | 0.167125E+10 | 0.172570E+10 | 0.727636E+09 | 0.998060E+09 | 0.00 | 0.00 |
October | 0.365611E+10 | 0.191325E+10 | 0.208312E+10 | 0.122228E+10 | 0.860843E+09 | 0.00 | 0.00 |
November | 0.352032E+10 | 0.273151E+10 | 0.232789E+10 | 0.147421E+10 | 0.853676E+09 | 0.00 | 0.00 |
December | 0.402469E+10 | 0.307008E+10 | 0.259396E+10 | 0.180566E+10 | 0.788299E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.314254E+11 | 0.273214E+11 | 0.219243E+11 | 0.100141E+11 | 0.119102E+11 | 0.00 | 0.00 |
Minimum of Months | 0.132652E+10 | 0.132903E+10 | 0.124521E+10 | 0.127862E+09 | 0.788299E+09 | 0.00 | 0.00 |
Maximum of Months | 0.402469E+10 | 0.319019E+10 | 0.259396E+10 | 0.180566E+10 | 0.119605E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.111387E+12 | -0.109633E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175419E+10 | 82.17 | 0.00 | 0.00 |
February | 0.100679E+12 | -0.990946E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158432E+10 | 82.17 | 0.00 | 0.00 |
March | 0.110700E+12 | -0.108944E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175562E+10 | 82.17 | 0.00 | 0.00 |
April | 0.105719E+12 | -0.104022E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169702E+10 | 82.17 | 0.00 | 0.00 |
May | 0.107495E+12 | -0.105741E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175361E+10 | 82.17 | 0.00 | 0.00 |
June | 0.102508E+12 | -0.100811E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169687E+10 | 82.17 | 0.00 | 0.00 |
July | 0.104959E+12 | -0.103206E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
August | 0.104860E+12 | -0.103106E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175342E+10 | 82.17 | 0.00 | 0.00 |
September | 0.102247E+12 | -0.100550E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169686E+10 | 82.17 | 0.00 | 0.00 |
October | 0.107129E+12 | -0.105375E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175343E+10 | 82.17 | 0.00 | 0.00 |
November | 0.105366E+12 | -0.103669E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.169691E+10 | 82.17 | 0.00 | 0.00 |
December | 0.110433E+12 | -0.108679E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.175382E+10 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.127348E+13 | -0.125283E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.206495E+11 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.100679E+12 | -0.109633E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.175562E+10 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.111387E+12 | -0.990946E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158432E+10 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.804707E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164104565.7 | 82.17 | 0.00 | 0.00 |
February | 0.727159E+10 | -0.712336E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148225951.3 | 82.17 | 0.00 | 0.00 |
March | 0.804566E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164107972.6 | 82.17 | 0.00 | 0.00 |
April | 0.779701E+10 | -0.763820E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158804396.0 | 82.17 | 0.00 | 0.00 |
May | 0.804706E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164095646.5 | 82.17 | 0.00 | 0.00 |
June | 0.778856E+10 | -0.762976E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158796259.6 | 82.17 | 0.00 | 0.00 |
July | 0.805549E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164084997.8 | 82.17 | 0.00 | 0.00 |
August | 0.804705E+10 | -0.788296E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164084421.9 | 82.17 | 0.00 | 0.00 |
September | 0.779840E+10 | -0.763961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158795363.3 | 82.17 | 0.00 | 0.00 |
October | 0.804564E+10 | -0.788156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164087492.9 | 82.17 | 0.00 | 0.00 |
November | 0.778013E+10 | -0.762132E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158808367.9 | 82.17 | 0.00 | 0.00 |
December | 0.805551E+10 | -0.789140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164105443.3 | 82.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.947792E+11 | -0.928471E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193210E+10 | 82.17 | 0.00 | 0.00 |
Minimum of Months | 0.727159E+10 | -0.789140E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164107972.6 | 82.17 | 0.00 | 0.00 |
Maximum of Months | 0.805551E+10 | -0.712336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148225951.3 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.637121E+11 | -0.622046E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150743E+10 | 60.05 | 0.00 | 0.00 |
February | 0.576188E+11 | -0.562574E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.136140E+10 | 60.05 | 0.00 | 0.00 |
March | 0.631742E+11 | -0.616648E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150942E+10 | 60.05 | 0.00 | 0.00 |
April | 0.598844E+11 | -0.584264E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145800E+10 | 60.05 | 0.00 | 0.00 |
May | 0.603797E+11 | -0.588730E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150664E+10 | 60.05 | 0.00 | 0.00 |
June | 0.571418E+11 | -0.556840E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145778E+10 | 60.05 | 0.00 | 0.00 |
July | 0.581583E+11 | -0.566520E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
August | 0.581303E+11 | -0.566239E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
September | 0.568904E+11 | -0.554326E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145778E+10 | 60.05 | 0.00 | 0.00 |
October | 0.600307E+11 | -0.585243E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150637E+10 | 60.05 | 0.00 | 0.00 |
November | 0.595565E+11 | -0.580986E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.145785E+10 | 60.05 | 0.00 | 0.00 |
December | 0.628842E+11 | -0.613773E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.150692E+10 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.717562E+12 | -0.699819E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.177423E+11 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.568904E+11 | -0.622046E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.150942E+10 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.637121E+11 | -0.554326E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.136140E+10 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_1 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.508434E+10 | 25095.26 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154259E+10 | 14416.44 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401607E+10 | 17528.43 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182061E+09 | 9448.91 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271863E+09 | 6786.55 | 14-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75452062.92 | 3383.10 | 29-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111059E+10 | 9231.75 | 05-NOV-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380013E+10 | 14484.65 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.508434E+10 | 25095.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.467423E+09 | 1683.50 | 08-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464365E+09 | 1593.37 | 26-FEB-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.681711E+09 | 2045.75 | 29-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226603E+09 | 1362.97 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248880E+09 | 1211.24 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49005245.32 | 593.70 | 13-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1671042.05 | 165.88 | 06-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11576.77 | 19.29 | 06-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13044455.83 | 464.75 | 20-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71110381.35 | 742.67 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.255818E+09 | 1144.05 | 13-NOV-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412587E+09 | 1990.77 | 13-DEC-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11576.77 | 19.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.681711E+09 | 2045.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29569906.09 | 434.76 | 03-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4677918.39 | 272.05 | 27-FEB-10:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39786086.23 | 543.95 | 29-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3139668.06 | 226.47 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7048184.02 | 452.24 | 13-DEC-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 84221762.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39786086.23 | 543.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108550E+11 | 20545.65 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.552294E+10 | 18264.65 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.938823E+10 | 18857.93 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161757E+10 | 15755.18 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156621E+10 | 13280.63 | 14-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40669443.52 | 3997.79 | 13-JUN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2917.73 | 4.74 | 19-AUG-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37718346.71 | 3843.04 | 20-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.662013E+09 | 9995.21 | 29-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444395E+10 | 16237.35 | 05-NOV-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.970366E+10 | 18303.91 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108550E+11 | 20545.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 939033.08 | 817.93 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 939033.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 939033.08 | 817.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.774030E+09 | 5140.22 | 08-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424761E+09 | 6548.91 | 25-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.780178E+09 | 14512.84 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102544E+09 | 4622.81 | 22-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93810980.17 | 5091.11 | 27-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3452666.44 | 3021.64 | 06-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232200.91 | 1821.64 | 12-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 344370.00 | 1396.57 | 22-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2346674.06 | 2798.05 | 19-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45939331.65 | 4431.56 | 12-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321514E+09 | 5235.38 | 23-NOV-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.668275E+09 | 5284.83 | 28-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 232200.91 | 1396.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.780178E+09 | 14512.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101781E+10 | 9761.06 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.533042E+09 | 7575.66 | 25-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.865749E+09 | 14025.53 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89756425.91 | 6669.03 | 02-APR-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60842036.58 | 6285.63 | 15-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3101910.00 | 4768.41 | 07-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 915701.75 | 2882.87 | 06-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 754749.63 | 3284.77 | 19-AUG-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5054472.68 | 5695.57 | 20-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42868923.88 | 7045.81 | 26-OCT-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.424618E+09 | 7689.65 | 29-NOV-09:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.888468E+09 | 10092.57 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 754749.63 | 2882.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101781E+10 | 14025.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.442341E+10 | 49096.84 | 02-JAN-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152164E+10 | 48738.55 | 05-FEB-17:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327310E+10 | 43440.78 | 10-MAR-19:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263495E+09 | 35779.73 | 16-APR-18:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105387E+09 | 23560.88 | 09-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2266984.80 | 17201.26 | 12-JUN-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 122713.81 | 1227.14 | 17-JUL-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 92785.96 | 1546.43 | 28-AUG-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1687987.65 | 11052.08 | 18-SEP-19:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27456304.23 | 30277.00 | 11-OCT-19:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125134E+10 | 44638.78 | 23-NOV-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333789E+10 | 46559.31 | 10-DEC-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 92785.96 | 1227.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.442341E+10 | 49096.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.824301E+09 | 4064.17 | 15-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.514331E+09 | 6242.91 | 25-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.874914E+09 | 12687.65 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136102E+09 | 6123.41 | 19-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128571E+09 | 5783.67 | 10-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5714825.96 | 2551.62 | 11-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6029672.76 | 3120.27 | 18-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 64451131.24 | 3021.15 | 07-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397086E+09 | 4997.78 | 04-NOV-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.749446E+09 | 5382.64 | 29-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.874914E+09 | 12687.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105467E+10 | 5876.07 | 07-JAN-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.643907E+09 | 7295.81 | 25-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.980628E+09 | 12139.74 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137730E+09 | 6108.00 | 10-APR-18:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109313E+09 | 5602.82 | 25-MAY-21:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4077425.61 | 4267.56 | 03-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1037114.57 | 2990.35 | 17-JUL-21:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1561901.81 | 3400.34 | 21-AUG-20:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7895548.33 | 6232.37 | 18-SEP-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67685661.69 | 6346.10 | 20-OCT-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.513549E+09 | 5415.30 | 10-NOV-22:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.960369E+09 | 8704.95 | 12-DEC-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1037114.57 | 2990.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105467E+10 | 12139.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.442964E+09 | 1402.54 | 25-JAN-16:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315373E+09 | 3805.13 | 25-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.443692E+09 | 3969.44 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112431E+09 | 1384.85 | 21-APR-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99244665.84 | 1309.31 | 24-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11801453.63 | 1058.78 | 07-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 235723.13 | 761.89 | 17-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 212565.32 | 822.83 | 22-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7007693.26 | 806.95 | 15-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 61227355.10 | 1001.98 | 23-OCT-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248373E+09 | 1671.15 | 30-NOV-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411930E+09 | 2440.25 | 12-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 212565.32 | 761.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.443692E+09 | 3969.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.559893E+09 | 3845.18 | 12-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.368090E+09 | 3676.88 | 25-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.477011E+09 | 3849.71 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91377152.80 | 1355.45 | 21-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64496175.40 | 1732.67 | 15-MAY-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4184863.26 | 1383.90 | 16-JUN-21:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 226013.07 | 863.58 | 17-JUL-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 217333.99 | 949.30 | 29-AUG-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3976019.27 | 1766.89 | 19-SEP-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54133046.28 | 1971.96 | 25-OCT-21:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.299845E+09 | 3212.82 | 05-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.517647E+09 | 3787.51 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 217333.99 | 863.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.559893E+09 | 3849.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122223E+10 | 5912.46 | 31-JAN-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.826585E+09 | 10050.20 | 25-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153417E+10 | 17843.65 | 28-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.356211E+09 | 8610.79 | 19-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.423691E+09 | 10731.06 | 10-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41756797.02 | 4449.87 | 11-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3164525.93 | 3748.99 | 17-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2309600.73 | 2064.27 | 29-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17281404.79 | 4861.10 | 18-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130361E+09 | 4129.30 | 07-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.601462E+09 | 6798.55 | 02-NOV-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109020E+10 | 5796.03 | 13-DEC-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2309600.73 | 2064.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153417E+10 | 17843.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_0 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6 HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.400804E+09 | 7881.56 | 08-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53473354.09 | 3328.84 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.442123E+09 | 6600.00 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9042947.99 | 2818.42 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1908617.00 | 606.53 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18490029.82 | 1544.82 | 05-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157306E+09 | 3128.47 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.442123E+09 | 7881.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN HEATING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.576381E+10 | 0.529005E+10 | 23673.85 | 21-JAN-09:01 | 17003.45 | 0.00 |
February | 0.00 | 0.00 | 0.467824E+10 | 0.422430E+10 | 23796.19 | 14-FEB-09:02 | 16736.91 | 0.00 |
March | 0.00 | 0.00 | 0.524848E+10 | 0.459798E+10 | 23801.90 | 18-MAR-08:61 | 16774.67 | 0.00 |
April | 0.00 | 0.00 | 0.845673E+10 | 0.736587E+10 | 23728.84 | 08-APR-08:61 | 16954.41 | 0.00 |
May | 0.00 | 0.00 | 0.803096E+10 | 0.693460E+10 | 23799.49 | 03-MAY-08:62 | 17047.67 | 0.00 |
June | 0.00 | 0.00 | 0.106572E+11 | 0.883971E+10 | 24262.81 | 28-JUN-08:62 | 15639.40 | 0.00 |
July | 0.00 | 0.00 | 0.141661E+11 | 0.114232E+11 | 24662.17 | 24-JUL-08:62 | 15514.83 | 0.00 |
August | 0.00 | 0.00 | 0.146788E+11 | 0.117149E+11 | 24971.22 | 18-AUG-08:62 | 14906.15 | 0.00 |
September | 0.00 | 0.00 | 0.120002E+11 | 0.995246E+10 | 24844.00 | 22-SEP-08:62 | 15141.13 | 0.00 |
October | 0.00 | 0.00 | 0.112037E+11 | 0.983704E+10 | 24927.46 | 01-OCT-08:62 | 14930.62 | 0.00 |
November | 0.00 | 0.00 | 0.654091E+10 | 0.592326E+10 | 23689.96 | 10-NOV-09:02 | 17061.28 | 0.00 |
December | 0.00 | 0.00 | 0.599295E+10 | 0.569385E+10 | 23599.54 | 09-DEC-09:02 | 16773.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107418E+12 | 0.917972E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.467824E+10 | 0.422430E+10 | 23599.54 | 14906.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.146788E+11 | 0.117149E+11 | 24971.22 | 17061.28 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.243968E+10 | 0.213973E+10 | 23002.06 | 16-JAN-22:51 | 16306.85 | 0.00 |
February | 0.00 | 0.00 | 0.240108E+10 | 0.207275E+10 | 23461.61 | 13-FEB-19:11 | 14785.94 | 0.00 |
March | 0.00 | 0.00 | 0.310640E+10 | 0.259715E+10 | 23521.21 | 22-MAR-18:51 | 17949.72 | 0.00 |
April | 0.00 | 0.00 | 0.533012E+10 | 0.442111E+10 | 24366.08 | 26-APR-21:51 | 16497.05 | 0.00 |
May | 0.00 | 0.00 | 0.565914E+10 | 0.472487E+10 | 24169.41 | 02-MAY-21:51 | 16953.40 | 0.00 |
June | 0.00 | 0.00 | 0.694964E+10 | 0.557821E+10 | 25049.96 | 27-JUN-21:51 | 15797.53 | 0.00 |
July | 0.00 | 0.00 | 0.935384E+10 | 0.732915E+10 | 25517.17 | 28-JUL-21:51 | 14986.14 | 0.00 |
August | 0.00 | 0.00 | 0.911849E+10 | 0.699328E+10 | 25576.36 | 19-AUG-08:51 | 15309.20 | 0.00 |
September | 0.00 | 0.00 | 0.717903E+10 | 0.573664E+10 | 25432.67 | 22-SEP-08:51 | 14375.26 | 0.00 |
October | 0.00 | 0.00 | 0.609915E+10 | 0.520843E+10 | 25602.39 | 01-OCT-21:51 | 15072.80 | 0.00 |
November | 0.00 | 0.00 | 0.313023E+10 | 0.270031E+10 | 23462.57 | 10-NOV-22:11 | 15701.09 | 0.00 |
December | 0.00 | 0.00 | 0.240597E+10 | 0.220918E+10 | 22738.93 | 08-DEC-16:12 | 16425.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.631728E+11 | 0.517108E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.240108E+10 | 0.207275E+10 | 22738.93 | 14375.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.935384E+10 | 0.732915E+10 | 25602.39 | 17949.72 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.479403E+11 | 0.474434E+11 | 88294.04 | 14-JAN-12:20 | 88294.04 | 0.00 |
February | 0.00 | 0.00 | 0.296565E+11 | 0.292360E+11 | 74590.62 | 01-FEB-12:00 | 74590.62 | 0.00 |
March | 0.00 | 0.00 | 0.239095E+11 | 0.230432E+11 | 65093.85 | 11-MAR-12:50 | 65093.85 | 0.00 |
April | 0.00 | 0.00 | 0.284254E+11 | 0.270335E+11 | 49782.61 | 08-APR-12:20 | 47088.06 | 0.00 |
May | 0.00 | 0.00 | 0.177279E+11 | 0.167283E+11 | 35747.50 | 04-MAY-12:00 | 34362.85 | 0.00 |
June | 0.00 | 0.00 | 0.244511E+11 | 0.220280E+11 | 25979.52 | 28-JUN-12:00 | 22388.94 | 0.00 |
July | 0.00 | 0.00 | 0.380336E+11 | 0.330452E+11 | 42202.04 | 31-JUL-12:30 | 37351.09 | 0.00 |
August | 0.00 | 0.00 | 0.493766E+11 | 0.430406E+11 | 49058.38 | 26-AUG-13:00 | 44475.52 | 0.00 |
September | 0.00 | 0.00 | 0.520423E+11 | 0.478042E+11 | 90588.43 | 29-SEP-12:10 | 90588.43 | 0.00 |
October | 0.00 | 0.00 | 0.641160E+11 | 0.614248E+11 | 104908.42 | 16-OCT-12:00 | 104908.42 | 0.00 |
November | 0.00 | 0.00 | 0.485320E+11 | 0.476840E+11 | 91999.42 | 19-NOV-12:30 | 91999.42 | 0.00 |
December | 0.00 | 0.00 | 0.530138E+11 | 0.527228E+11 | 92378.19 | 19-DEC-12:30 | 92378.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.477225E+12 | 0.451234E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.177279E+11 | 0.167283E+11 | 25979.52 | 22388.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.641160E+11 | 0.614248E+11 | 104908.42 | 104908.42 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.207631E+11 | 0.174774E+11 | 118141.55 | 16-JAN-22:51 | 85852.44 | 0.00 |
February | 0.00 | 0.00 | 0.205792E+11 | 0.170109E+11 | 119277.68 | 13-FEB-19:11 | 77688.72 | 0.00 |
March | 0.00 | 0.00 | 0.245623E+11 | 0.197189E+11 | 118143.04 | 23-MAR-19:11 | 81031.97 | 0.00 |
April | 0.00 | 0.00 | 0.383205E+11 | 0.302942E+11 | 122890.06 | 26-APR-21:51 | 79609.59 | 0.00 |
May | 0.00 | 0.00 | 0.446168E+11 | 0.361091E+11 | 121566.04 | 02-MAY-21:51 | 83854.12 | 0.00 |
June | 0.00 | 0.00 | 0.549808E+11 | 0.423688E+11 | 126653.19 | 29-JUN-17:51 | 86210.06 | 0.00 |
July | 0.00 | 0.00 | 0.714864E+11 | 0.524268E+11 | 130721.77 | 19-JUL-21:51 | 71765.35 | 0.00 |
August | 0.00 | 0.00 | 0.695265E+11 | 0.495144E+11 | 130594.15 | 19-AUG-08:51 | 77033.71 | 0.00 |
September | 0.00 | 0.00 | 0.545256E+11 | 0.412548E+11 | 132821.44 | 21-SEP-21:51 | 70845.35 | 0.00 |
October | 0.00 | 0.00 | 0.498471E+11 | 0.409398E+11 | 132289.34 | 04-OCT-20:21 | 75230.72 | 0.00 |
November | 0.00 | 0.00 | 0.252998E+11 | 0.210157E+11 | 120586.68 | 09-NOV-22:51 | 78690.89 | 0.00 |
December | 0.00 | 0.00 | 0.192679E+11 | 0.171266E+11 | 116434.54 | 07-DEC-19:02 | 82627.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.493776E+12 | 0.385257E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.192679E+11 | 0.170109E+11 | 116434.54 | 70845.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.714864E+11 | 0.524268E+11 | 132821.44 | 86210.06 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.580230E+10 | 0.533689E+10 | 20132.77 | 20-JAN-19:02 | 15083.47 | 0.00 |
February | 0.00 | 0.00 | 0.432962E+10 | 0.391836E+10 | 20991.66 | 13-FEB-16:12 | 13705.56 | 0.00 |
March | 0.00 | 0.00 | 0.507572E+10 | 0.444982E+10 | 20296.21 | 26-MAR-08:62 | 15090.05 | 0.00 |
April | 0.00 | 0.00 | 0.780768E+10 | 0.677430E+10 | 20585.33 | 15-APR-08:61 | 14428.44 | 0.00 |
May | 0.00 | 0.00 | 0.717531E+10 | 0.614302E+10 | 20503.75 | 09-MAY-15:12 | 14437.53 | 0.00 |
June | 0.00 | 0.00 | 0.941538E+10 | 0.770312E+10 | 21146.60 | 28-JUN-08:62 | 13690.40 | 0.00 |
July | 0.00 | 0.00 | 0.131493E+11 | 0.104834E+11 | 20975.25 | 20-JUL-18:02 | 14043.92 | 0.00 |
August | 0.00 | 0.00 | 0.140166E+11 | 0.111026E+11 | 21282.45 | 08-AUG-08:62 | 13547.94 | 0.00 |
September | 0.00 | 0.00 | 0.106897E+11 | 0.877068E+10 | 21408.17 | 23-SEP-08:62 | 13195.95 | 0.00 |
October | 0.00 | 0.00 | 0.106032E+11 | 0.930802E+10 | 21683.33 | 01-OCT-08:62 | 12854.13 | 0.00 |
November | 0.00 | 0.00 | 0.611664E+10 | 0.553716E+10 | 20485.55 | 11-NOV-16:12 | 14352.79 | 0.00 |
December | 0.00 | 0.00 | 0.584055E+10 | 0.556079E+10 | 20459.96 | 08-DEC-09:02 | 14690.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.100022E+12 | 0.850882E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.432962E+10 | 0.391836E+10 | 20132.77 | 12854.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.140166E+11 | 0.111026E+11 | 21683.33 | 15090.05 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.236617E+10 | 0.206380E+10 | 20007.77 | 17-JAN-09:51 | 16350.12 | 0.00 |
February | 0.00 | 0.00 | 0.212497E+10 | 0.183235E+10 | 20074.28 | 13-FEB-19:11 | 12075.86 | 0.00 |
March | 0.00 | 0.00 | 0.308518E+10 | 0.259743E+10 | 19868.01 | 23-MAR-19:11 | 13700.59 | 0.00 |
April | 0.00 | 0.00 | 0.535625E+10 | 0.452134E+10 | 20619.66 | 27-APR-08:32 | 17465.18 | 0.00 |
May | 0.00 | 0.00 | 0.536636E+10 | 0.452033E+10 | 20748.09 | 03-MAY-08:32 | 17378.56 | 0.00 |
June | 0.00 | 0.00 | 0.658711E+10 | 0.532185E+10 | 21977.53 | 30-JUN-08:22 | 17318.91 | 0.00 |
July | 0.00 | 0.00 | 0.908530E+10 | 0.714030E+10 | 22487.88 | 23-JUL-08:22 | 16765.02 | 0.00 |
August | 0.00 | 0.00 | 0.909946E+10 | 0.703380E+10 | 22842.93 | 19-AUG-08:22 | 16200.46 | 0.00 |
September | 0.00 | 0.00 | 0.647108E+10 | 0.515474E+10 | 22168.57 | 10-SEP-08:22 | 17021.44 | 0.00 |
October | 0.00 | 0.00 | 0.580523E+10 | 0.498179E+10 | 21987.67 | 01-OCT-08:51 | 11953.02 | 0.00 |
November | 0.00 | 0.00 | 0.271187E+10 | 0.232004E+10 | 20177.74 | 10-NOV-09:51 | 15694.09 | 0.00 |
December | 0.00 | 0.00 | 0.211681E+10 | 0.193694E+10 | 19619.67 | 07-DEC-19:02 | 13269.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.601758E+11 | 0.494247E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.211681E+10 | 0.183235E+10 | 19619.67 | 11953.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.909946E+10 | 0.714030E+10 | 22842.93 | 17465.18 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.119271E+10 | 0.109892E+10 | 6544.23 | 21-JAN-09:01 | 4111.13 | 0.00 |
February | 0.00 | 0.00 | 0.959086E+09 | 0.869782E+09 | 6462.40 | 13-FEB-16:12 | 4291.47 | 0.00 |
March | 0.00 | 0.00 | 0.114456E+10 | 0.100610E+10 | 6457.02 | 18-MAR-08:61 | 4045.85 | 0.00 |
April | 0.00 | 0.00 | 0.198571E+10 | 0.173685E+10 | 6428.94 | 08-APR-08:61 | 4128.41 | 0.00 |
May | 0.00 | 0.00 | 0.186224E+10 | 0.161364E+10 | 6418.02 | 03-MAY-08:62 | 4426.98 | 0.00 |
June | 0.00 | 0.00 | 0.258916E+10 | 0.215329E+10 | 6531.85 | 28-JUN-08:62 | 3944.06 | 0.00 |
July | 0.00 | 0.00 | 0.358475E+10 | 0.290446E+10 | 6649.60 | 24-JUL-08:62 | 4017.63 | 0.00 |
August | 0.00 | 0.00 | 0.368637E+10 | 0.295311E+10 | 6748.46 | 18-AUG-08:62 | 3827.08 | 0.00 |
September | 0.00 | 0.00 | 0.285822E+10 | 0.237133E+10 | 6725.65 | 22-SEP-08:62 | 3868.41 | 0.00 |
October | 0.00 | 0.00 | 0.261620E+10 | 0.229368E+10 | 6795.13 | 01-OCT-08:62 | 3727.26 | 0.00 |
November | 0.00 | 0.00 | 0.137854E+10 | 0.125031E+10 | 6265.24 | 14-NOV-09:02 | 4673.07 | 0.00 |
December | 0.00 | 0.00 | 0.124850E+10 | 0.119187E+10 | 6382.66 | 10-DEC-09:01 | 4265.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.251061E+11 | 0.214433E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.959086E+09 | 0.869782E+09 | 6265.24 | 3727.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.368637E+10 | 0.295311E+10 | 6795.13 | 4673.07 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.415394E+09 | 0.366195E+09 | 6105.57 | 16-JAN-22:51 | 4187.80 | 0.00 |
February | 0.00 | 0.00 | 0.424077E+09 | 0.366707E+09 | 6263.81 | 13-FEB-19:11 | 3700.20 | 0.00 |
March | 0.00 | 0.00 | 0.621256E+09 | 0.518984E+09 | 6270.77 | 22-MAR-18:51 | 4872.52 | 0.00 |
April | 0.00 | 0.00 | 0.121747E+10 | 0.101170E+10 | 6517.15 | 26-APR-21:51 | 4447.56 | 0.00 |
May | 0.00 | 0.00 | 0.130432E+10 | 0.109157E+10 | 6455.60 | 02-MAY-21:51 | 4547.04 | 0.00 |
June | 0.00 | 0.00 | 0.174908E+10 | 0.141285E+10 | 6667.20 | 27-JUN-21:51 | 4242.96 | 0.00 |
July | 0.00 | 0.00 | 0.248609E+10 | 0.197299E+10 | 6794.47 | 28-JUL-21:51 | 4027.96 | 0.00 |
August | 0.00 | 0.00 | 0.239571E+10 | 0.185923E+10 | 6836.49 | 19-AUG-08:51 | 4040.28 | 0.00 |
September | 0.00 | 0.00 | 0.173982E+10 | 0.139213E+10 | 6791.57 | 22-SEP-08:51 | 3731.60 | 0.00 |
October | 0.00 | 0.00 | 0.141168E+10 | 0.120523E+10 | 6880.34 | 01-OCT-08:51 | 3562.16 | 0.00 |
November | 0.00 | 0.00 | 0.563241E+09 | 0.485155E+09 | 6239.21 | 10-NOV-22:11 | 4001.99 | 0.00 |
December | 0.00 | 0.00 | 0.408767E+09 | 0.379640E+09 | 5990.95 | 07-DEC-19:02 | 4194.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147369E+11 | 0.120624E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.408767E+09 | 0.366195E+09 | 5990.95 | 3562.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.248609E+10 | 0.197299E+10 | 6880.34 | 4872.52 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.125980E+11 | 0.118153E+11 | 27961.60 | 17-JAN-09:02 | 22081.68 | 0.00 |
February | 0.00 | 0.00 | 0.836435E+10 | 0.769586E+10 | 28990.06 | 13-FEB-16:12 | 19476.59 | 0.00 |
March | 0.00 | 0.00 | 0.805133E+10 | 0.710392E+10 | 28761.18 | 18-MAR-08:61 | 20093.93 | 0.00 |
April | 0.00 | 0.00 | 0.993419E+10 | 0.850032E+10 | 28815.16 | 08-APR-08:61 | 20032.07 | 0.00 |
May | 0.00 | 0.00 | 0.752924E+10 | 0.623160E+10 | 28915.03 | 03-MAY-08:62 | 20129.91 | 0.00 |
June | 0.00 | 0.00 | 0.100575E+11 | 0.782080E+10 | 29502.56 | 29-JUN-08:62 | 18219.83 | 0.00 |
July | 0.00 | 0.00 | 0.148299E+11 | 0.111655E+11 | 30134.22 | 24-JUL-08:62 | 18096.51 | 0.00 |
August | 0.00 | 0.00 | 0.174728E+11 | 0.132987E+11 | 30591.83 | 18-AUG-08:62 | 17202.40 | 0.00 |
September | 0.00 | 0.00 | 0.160160E+11 | 0.130838E+11 | 30328.70 | 22-SEP-08:62 | 17692.78 | 0.00 |
October | 0.00 | 0.00 | 0.177587E+11 | 0.156806E+11 | 30503.06 | 01-OCT-08:62 | 17282.82 | 0.00 |
November | 0.00 | 0.00 | 0.126279E+11 | 0.116608E+11 | 28613.25 | 10-NOV-09:02 | 20697.68 | 0.00 |
December | 0.00 | 0.00 | 0.132204E+11 | 0.127112E+11 | 28473.79 | 09-DEC-09:02 | 20613.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148460E+12 | 0.126768E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.752924E+10 | 0.623160E+10 | 27961.60 | 17202.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.177587E+11 | 0.156806E+11 | 30591.83 | 22081.68 | 0.00 |
Report: CoilReportMonthly
For: PTAC_3 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.125516E+11 | 0.913700E+10 | 15702.93 | 20-JAN-12:00 | 11895.34 | 0.00 |
February | 0.00 | 0.00 | 0.960318E+10 | 0.670837E+10 | 14517.37 | 01-FEB-12:00 | 12414.23 | 0.00 |
March | 0.00 | 0.00 | 0.102624E+11 | 0.666759E+10 | 14742.38 | 11-MAR-11:25 | 11128.36 | 0.00 |
April | 0.00 | 0.00 | 0.145224E+11 | 0.100588E+11 | 13373.58 | 08-APR-12:00 | 9525.82 | 0.00 |
May | 0.00 | 0.00 | 0.143581E+11 | 0.987022E+10 | 11511.51 | 04-MAY-12:00 | 9171.11 | 0.00 |
June | 0.00 | 0.00 | 0.185125E+11 | 0.128637E+11 | 15279.97 | 29-JUN-18:10 | 10940.57 | 0.00 |
July | 0.00 | 0.00 | 0.240157E+11 | 0.164599E+11 | 15857.80 | 18-JUL-18:03 | 11161.45 | 0.00 |
August | 0.00 | 0.00 | 0.254575E+11 | 0.173103E+11 | 16033.48 | 18-AUG-12:00 | 11814.00 | 0.00 |
September | 0.00 | 0.00 | 0.213496E+11 | 0.152162E+11 | 21948.68 | 29-SEP-13:00 | 21948.68 | 0.00 |
October | 0.00 | 0.00 | 0.215801E+11 | 0.167564E+11 | 23548.22 | 16-OCT-12:00 | 23548.22 | 0.00 |
November | 0.00 | 0.00 | 0.136872E+11 | 0.101558E+11 | 17612.38 | 19-NOV-10:53 | 15333.08 | 0.00 |
December | 0.00 | 0.00 | 0.128170E+11 | 0.100210E+11 | 15764.85 | 16-DEC-12:30 | 13260.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198717E+12 | 0.141225E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.960318E+10 | 0.666759E+10 | 11511.51 | 9171.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.254575E+11 | 0.173103E+11 | 23548.22 | 23548.22 | 0.00 |
Report: CoilReportMonthly
For: PTAC_6 PTAC COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.457172E+10 | 0.357557E+10 | 10198.92 | 20-JAN-11:25 | 7758.39 | 0.00 |
February | 0.00 | 0.00 | 0.358118E+10 | 0.275987E+10 | 9302.46 | 18-FEB-12:20 | 6744.06 | 0.00 |
March | 0.00 | 0.00 | 0.423504E+10 | 0.316651E+10 | 10003.94 | 11-MAR-11:25 | 7989.89 | 0.00 |
April | 0.00 | 0.00 | 0.718052E+10 | 0.571369E+10 | 9777.96 | 26-APR-12:30 | 8914.09 | 0.00 |
May | 0.00 | 0.00 | 0.707405E+10 | 0.558960E+10 | 9511.53 | 02-MAY-10:25 | 7008.61 | 0.00 |
June | 0.00 | 0.00 | 0.941217E+10 | 0.750974E+10 | 8742.33 | 27-JUN-12:30 | 7544.52 | 0.00 |
July | 0.00 | 0.00 | 0.122930E+11 | 0.979096E+10 | 10665.42 | 31-JUL-12:30 | 9068.89 | 0.00 |
August | 0.00 | 0.00 | 0.127629E+11 | 0.100851E+11 | 10831.94 | 18-AUG-12:10 | 9177.13 | 0.00 |
September | 0.00 | 0.00 | 0.100951E+11 | 0.810780E+10 | 13716.62 | 29-SEP-12:50 | 13716.62 | 0.00 |
October | 0.00 | 0.00 | 0.968862E+10 | 0.812642E+10 | 13638.26 | 16-OCT-12:00 | 13638.26 | 0.00 |
November | 0.00 | 0.00 | 0.527633E+10 | 0.419080E+10 | 10461.34 | 19-NOV-11:25 | 9287.97 | 0.00 |
December | 0.00 | 0.00 | 0.466711E+10 | 0.382056E+10 | 9717.47 | 19-DEC-12:40 | 9717.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.908377E+11 | 0.724366E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.358118E+10 | 0.275987E+10 | 8742.33 | 6744.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127629E+11 | 0.100851E+11 | 13716.62 | 13716.62 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_1 COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.174625E+11 | 0.157333E+11 | 63760.16 | 14-JAN-12:00 | 63760.16 | 0.00 |
February | 0.00 | 0.00 | 0.102182E+11 | 0.842739E+10 | 56938.94 | 01-FEB-12:00 | 56938.94 | 0.00 |
March | 0.00 | 0.00 | 0.114446E+11 | 0.887351E+10 | 52328.67 | 11-MAR-12:50 | 52328.67 | 0.00 |
April | 0.00 | 0.00 | 0.245631E+11 | 0.196394E+11 | 48386.40 | 26-APR-13:00 | 48386.40 | 0.00 |
May | 0.00 | 0.00 | 0.267373E+11 | 0.207029E+11 | 40705.33 | 04-MAY-12:10 | 39104.45 | 0.00 |
June | 0.00 | 0.00 | 0.505499E+11 | 0.346365E+11 | 61776.81 | 29-JUN-18:02 | 37909.03 | 0.00 |
July | 0.00 | 0.00 | 0.905107E+11 | 0.546486E+11 | 84270.24 | 31-JUL-18:03 | 46425.41 | 0.00 |
August | 0.00 | 0.00 | 0.997901E+11 | 0.584148E+11 | 76442.87 | 18-AUG-15:10 | 53471.48 | 0.00 |
September | 0.00 | 0.00 | 0.680910E+11 | 0.450342E+11 | 96844.40 | 29-SEP-13:00 | 96844.40 | 0.00 |
October | 0.00 | 0.00 | 0.740130E+11 | 0.563254E+11 | 101476.28 | 16-OCT-11:30 | 101476.28 | 0.00 |
November | 0.00 | 0.00 | 0.193383E+11 | 0.165826E+11 | 71269.64 | 19-NOV-13:00 | 71269.64 | 0.00 |
December | 0.00 | 0.00 | 0.203027E+11 | 0.196538E+11 | 64087.63 | 19-DEC-13:00 | 64087.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.513021E+12 | 0.358672E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.102182E+11 | 0.842739E+10 | 40705.33 | 37909.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.997901E+11 | 0.584148E+11 | 101476.28 | 101476.28 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_6 COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.140425E+11 | 0.127251E+11 | 39026.31 | 14-JAN-15:00 | 39026.31 | 0.00 |
February | 0.00 | 0.00 | 0.842318E+10 | 0.690655E+10 | 38843.14 | 01-FEB-12:00 | 38843.14 | 0.00 |
March | 0.00 | 0.00 | 0.959918E+10 | 0.752459E+10 | 38184.85 | 23-MAR-15:13 | 30638.06 | 0.00 |
April | 0.00 | 0.00 | 0.217171E+11 | 0.180903E+11 | 45800.05 | 30-APR-09:53 | 45800.05 | 0.00 |
May | 0.00 | 0.00 | 0.242812E+11 | 0.199301E+11 | 36093.69 | 04-MAY-12:00 | 36093.69 | 0.00 |
June | 0.00 | 0.00 | 0.475160E+11 | 0.346396E+11 | 64510.80 | 29-JUN-18:02 | 38716.91 | 0.00 |
July | 0.00 | 0.00 | 0.877419E+11 | 0.544870E+11 | 82474.95 | 18-JUL-18:10 | 49151.11 | 0.00 |
August | 0.00 | 0.00 | 0.946148E+11 | 0.559191E+11 | 77557.00 | 18-AUG-15:20 | 51719.79 | 0.00 |
September | 0.00 | 0.00 | 0.607096E+11 | 0.406504E+11 | 87847.92 | 21-SEP-21:52 | 40027.30 | 0.00 |
October | 0.00 | 0.00 | 0.625569E+11 | 0.469512E+11 | 76136.31 | 16-OCT-11:00 | 76136.31 | 0.00 |
November | 0.00 | 0.00 | 0.153207E+11 | 0.129839E+11 | 46144.98 | 19-NOV-10:53 | 46144.98 | 0.00 |
December | 0.00 | 0.00 | 0.152158E+11 | 0.146750E+11 | 38929.55 | 16-DEC-13:00 | 38929.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.461739E+12 | 0.325483E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.842318E+10 | 0.690655E+10 | 36093.69 | 30638.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.946148E+11 | 0.559191E+11 | 87847.92 | 76136.31 | 0.00 |
Report: CoilReportMonthly
For: VAV_FLR_0 COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.650903E+10 | 0.499511E+10 | 25455.12 | 17-JAN-20:20 | 17371.14 | 0.00 |
February | 0.00 | 0.00 | 0.188709E+10 | 0.139637E+10 | 15371.44 | 01-FEB-09:55 | 15371.44 | 0.00 |
March | 0.00 | 0.00 | 0.191554E+10 | 0.133607E+10 | 13602.14 | 23-MAR-14:10 | 9331.28 | 0.00 |
April | 0.00 | 0.00 | 0.637313E+10 | 0.431272E+10 | 20840.91 | 26-APR-19:20 | 10171.32 | 0.00 |
May | 0.00 | 0.00 | 0.680248E+10 | 0.441788E+10 | 21465.49 | 04-MAY-19:20 | 11613.67 | 0.00 |
June | 0.00 | 0.00 | 0.155396E+11 | 0.933798E+10 | 30311.95 | 29-JUN-18:02 | 16129.49 | 0.00 |
July | 0.00 | 0.00 | 0.345769E+11 | 0.189130E+11 | 39707.26 | 18-JUL-18:02 | 21927.76 | 0.00 |
August | 0.00 | 0.00 | 0.393680E+11 | 0.208150E+11 | 35052.57 | 14-AUG-19:10 | 17466.23 | 0.00 |
September | 0.00 | 0.00 | 0.280737E+11 | 0.163944E+11 | 46611.64 | 21-SEP-21:00 | 19632.55 | 0.00 |
October | 0.00 | 0.00 | 0.316961E+11 | 0.213952E+11 | 44203.48 | 04-OCT-20:00 | 20615.38 | 0.00 |
November | 0.00 | 0.00 | 0.761041E+10 | 0.555870E+10 | 24004.75 | 10-NOV-21:00 | 11687.33 | 0.00 |
December | 0.00 | 0.00 | 0.665637E+10 | 0.609246E+10 | 17906.48 | 05-DEC-09:58 | 17906.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187008E+12 | 0.114965E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.188709E+10 | 0.133607E+10 | 13602.14 | 9331.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.393680E+11 | 0.213952E+11 | 46611.64 | 21927.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ_LAUNDRY COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.470710E+10 | 0.422720E+10 | 32812.89 | 17-JAN-20:10 | 23862.02 | 0.00 |
February | 0.00 | 0.00 | 0.927033E+09 | 0.895421E+09 | 27979.37 | 01-FEB-09:52 | 27979.37 | 0.00 |
March | 0.00 | 0.00 | 0.189778E+10 | 0.161813E+10 | 24916.90 | 11-MAR-10:51 | 24916.90 | 0.00 |
April | 0.00 | 0.00 | 0.637060E+10 | 0.518360E+10 | 29763.37 | 26-APR-08:51 | 23766.31 | 0.00 |
May | 0.00 | 0.00 | 0.524360E+10 | 0.395572E+10 | 26406.49 | 04-MAY-19:10 | 14861.26 | 0.00 |
June | 0.00 | 0.00 | 0.169617E+11 | 0.114908E+11 | 52898.36 | 29-JUN-18:08 | 28954.59 | 0.00 |
July | 0.00 | 0.00 | 0.354713E+11 | 0.229043E+11 | 67756.40 | 18-JUL-18:02 | 37985.41 | 0.00 |
August | 0.00 | 0.00 | 0.390083E+11 | 0.246153E+11 | 56019.11 | 14-AUG-19:10 | 28342.42 | 0.00 |
September | 0.00 | 0.00 | 0.207281E+11 | 0.137082E+11 | 68750.23 | 21-SEP-21:00 | 29026.01 | 0.00 |
October | 0.00 | 0.00 | 0.256781E+11 | 0.190543E+11 | 65111.43 | 04-OCT-20:00 | 30531.83 | 0.00 |
November | 0.00 | 0.00 | 0.330959E+10 | 0.312535E+10 | 27937.88 | 19-NOV-09:00 | 27937.88 | 0.00 |
December | 0.00 | 0.00 | 0.538105E+10 | 0.534609E+10 | 28284.32 | 05-DEC-09:53 | 28284.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.165684E+12 | 0.116124E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.927033E+09 | 0.895421E+09 | 24916.90 | 14861.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.390083E+11 | 0.246153E+11 | 68750.23 | 37985.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ_CAFE COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.413728E+10 | 0.386337E+10 | 28319.95 | 14-JAN-12:10 | 28319.95 | 0.00 |
February | 0.00 | 0.00 | 0.174004E+10 | 0.160422E+10 | 25128.86 | 01-FEB-12:00 | 25128.86 | 0.00 |
March | 0.00 | 0.00 | 0.241139E+10 | 0.194686E+10 | 22974.57 | 11-MAR-12:30 | 22974.57 | 0.00 |
April | 0.00 | 0.00 | 0.445188E+10 | 0.361961E+10 | 22604.39 | 08-APR-12:00 | 16615.50 | 0.00 |
May | 0.00 | 0.00 | 0.207186E+10 | 0.166419E+10 | 18148.49 | 04-MAY-12:10 | 15411.38 | 0.00 |
June | 0.00 | 0.00 | 0.582065E+10 | 0.413437E+10 | 19742.79 | 28-JUN-12:10 | 12288.97 | 0.00 |
July | 0.00 | 0.00 | 0.135714E+11 | 0.905000E+10 | 26080.88 | 31-JUL-12:30 | 19062.39 | 0.00 |
August | 0.00 | 0.00 | 0.174560E+11 | 0.115165E+11 | 27539.87 | 18-AUG-12:00 | 20207.85 | 0.00 |
September | 0.00 | 0.00 | 0.124288E+11 | 0.902723E+10 | 34708.63 | 29-SEP-12:00 | 34708.63 | 0.00 |
October | 0.00 | 0.00 | 0.156427E+11 | 0.131867E+11 | 37710.50 | 16-OCT-11:30 | 37710.50 | 0.00 |
November | 0.00 | 0.00 | 0.449389E+10 | 0.410372E+10 | 29578.78 | 19-NOV-12:30 | 29444.74 | 0.00 |
December | 0.00 | 0.00 | 0.587891E+10 | 0.577019E+10 | 28198.45 | 16-DEC-13:00 | 28198.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.901048E+11 | 0.694870E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.174004E+10 | 0.160422E+10 | 18148.49 | 12288.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.174560E+11 | 0.131867E+11 | 37710.50 | 37710.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ_KITCHEN COOLING COIL
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.970494E+10 | 0.843524E+10 | 38546.86 | 14-JAN-11:40 | 34523.16 | 0.00 |
February | 0.00 | 0.00 | 0.463665E+10 | 0.382944E+10 | 40297.77 | 01-FEB-11:50 | 34092.76 | 0.00 |
March | 0.00 | 0.00 | 0.716968E+10 | 0.532230E+10 | 41745.59 | 11-MAR-11:40 | 34338.10 | 0.00 |
April | 0.00 | 0.00 | 0.176159E+11 | 0.134165E+11 | 47377.87 | 26-APR-10:40 | 35551.30 | 0.00 |
May | 0.00 | 0.00 | 0.177091E+11 | 0.134561E+11 | 37112.37 | 04-MAY-12:00 | 30753.93 | 0.00 |
June | 0.00 | 0.00 | 0.309913E+11 | 0.213146E+11 | 54338.04 | 28-JUN-10:50 | 33435.43 | 0.00 |
July | 0.00 | 0.00 | 0.515931E+11 | 0.322929E+11 | 56051.67 | 30-JUL-09:50 | 31962.13 | 0.00 |
August | 0.00 | 0.00 | 0.550955E+11 | 0.334253E+11 | 55444.19 | 26-AUG-10:50 | 34083.14 | 0.00 |
September | 0.00 | 0.00 | 0.361346E+11 | 0.233413E+11 | 56410.39 | 22-SEP-10:40 | 24813.53 | 0.00 |
October | 0.00 | 0.00 | 0.385791E+11 | 0.279471E+11 | 56256.94 | 01-OCT-10:40 | 30770.95 | 0.00 |
November | 0.00 | 0.00 | 0.977664E+10 | 0.819241E+10 | 43434.47 | 19-NOV-11:40 | 34978.91 | 0.00 |
December | 0.00 | 0.00 | 0.102384E+11 | 0.984194E+10 | 37853.63 | 19-DEC-11:40 | 34001.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.289245E+12 | 0.200815E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.463665E+10 | 0.382944E+10 | 37112.37 | 24813.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.550955E+11 | 0.334253E+11 | 56410.39 | 35551.30 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 9907.27 | 93285.61 | 08-JAN-06:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 5204.71 | 68906.11 | 27-FEB-16:14 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 8648.28 | 139824.61 | 28-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1269.93 | 48890.86 | 01-APR-05:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1175.63 | 36758.48 | 14-MAY-04:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 62.61 | 19309.51 | 12-JUN-08:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2.87 | 5578.25 | 17-JUL-21:55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2.16 | 4195.44 | 22-AUG-08:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 39.38 | 11409.22 | 18-SEP-19:06 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 483.97 | 37104.40 | 11-OCT-19:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3780.50 | 58346.40 | 23-NOV-19:05 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8349.79 | 73496.62 | 13-DEC-04:30 |
Annual Sum or Average | 0.00 | 3249.24 | ||||
Minimum of Months | 0.00 | 0.00 | 2.16 | 4195.44 | ||
Maximum of Months | 0.00 | 0.00 | 9907.27 | 139824.61 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 23120.51 | 48443.82 | 31-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 23150.48 | 48446.25 | 02-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22919.27 | 48206.65 | 01-MAR-07:56 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22438.01 | 47337.07 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21878.40 | 46292.24 | 01-MAY-06:52 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 21381.45 | 45108.67 | 01-JUN-06:52 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21050.28 | 44195.94 | 03-JUL-06:54 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21039.85 | 44109.19 | 31-AUG-06:51 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21284.59 | 44854.86 | 29-SEP-06:54 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21748.39 | 46035.25 | 31-OCT-06:53 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22311.73 | 47180.59 | 30-NOV-07:45 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 22812.07 | 48035.31 | 29-DEC-07:45 |
Annual Sum or Average | 0.00 | 22088.55 | ||||
Minimum of Months | 0.00 | 0.00 | 21039.85 | 44109.19 | ||
Maximum of Months | 0.00 | 0.00 | 23150.48 | 48446.25 |
Report: FanReportMonthly
For: VAV_FLR_1 FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114252E+11 | 1.01 | 7180.97 | 22-JAN-10:53 | 1.25 |
February | 0.101010E+11 | 1.00 | 6506.69 | 04-FEB-12:30 | 1.21 |
March | 0.109272E+11 | 0.99 | 6601.87 | 11-MAR-12:50 | 1.21 |
April | 0.107396E+11 | 0.99 | 6581.33 | 26-APR-20:10 | 1.20 |
May | 0.109143E+11 | 0.99 | 6725.83 | 04-MAY-20:10 | 1.21 |
June | 0.108759E+11 | 1.00 | 6662.71 | 27-JUN-20:10 | 1.20 |
July | 0.116193E+11 | 1.01 | 7241.64 | 19-JUL-20:10 | 1.25 |
August | 0.119791E+11 | 1.02 | 7316.66 | 18-AUG-20:10 | 1.25 |
September | 0.116294E+11 | 1.02 | 8888.42 | 29-SEP-20:10 | 1.37 |
October | 0.126029E+11 | 1.04 | 8903.37 | 16-OCT-15:10 | 1.37 |
November | 0.112459E+11 | 1.01 | 7937.02 | 19-NOV-09:53 | 1.31 |
December | 0.116930E+11 | 1.02 | 7291.56 | 31-DEC-10:53 | 1.27 |
Annual Sum or Average | 0.135753E+12 | 1.01 | |||
Minimum of Months | 0.101010E+11 | 0.99 | 6506.69 | 1.20 | |
Maximum of Months | 0.126029E+11 | 1.04 | 8903.37 | 1.37 |
Report: FanReportMonthly
For: VAV_FLR_6 FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109715E+11 | 1.13 | 6860.30 | 18-JAN-22:10 | 1.41 |
February | 0.993936E+10 | 1.13 | 6336.83 | 15-FEB-22:10 | 1.36 |
March | 0.111204E+11 | 1.14 | 6656.85 | 24-MAR-21:10 | 1.39 |
April | 0.113820E+11 | 1.16 | 7324.40 | 26-APR-21:10 | 1.44 |
May | 0.120759E+11 | 1.17 | 7665.83 | 02-MAY-21:10 | 1.47 |
June | 0.125560E+11 | 1.21 | 7811.47 | 27-JUN-21:10 | 1.48 |
July | 0.134918E+11 | 1.22 | 7910.75 | 19-JUL-21:10 | 1.49 |
August | 0.132278E+11 | 1.21 | 7892.32 | 02-AUG-21:10 | 1.49 |
September | 0.119788E+11 | 1.18 | 8417.45 | 29-SEP-21:10 | 1.54 |
October | 0.121600E+11 | 1.18 | 7950.15 | 04-OCT-21:52 | 1.49 |
November | 0.107557E+11 | 1.14 | 6552.13 | 10-NOV-22:10 | 1.38 |
December | 0.109671E+11 | 1.14 | 6877.80 | 05-DEC-22:10 | 1.42 |
Annual Sum or Average | 0.140626E+12 | 1.17 | |||
Minimum of Months | 0.993936E+10 | 1.13 | 6336.83 | 1.36 | |
Maximum of Months | 0.134918E+11 | 1.22 | 8417.45 | 1.54 |
Report: FanReportMonthly
For: VAV_FLR_0 SZVAV FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.577673E+10 | 1.12 | 2156.78 | 02-JAN-19:40 | 1.12 |
February | 0.521769E+10 | 1.12 | 2156.78 | 01-FEB-04:30 | 1.12 |
March | 0.577673E+10 | 1.12 | 2156.78 | 02-MAR-09:55 | 1.12 |
April | 0.559038E+10 | 1.12 | 2156.78 | 01-APR-10:02 | 1.12 |
May | 0.577673E+10 | 1.12 | 2156.78 | 01-MAY-10:15 | 1.12 |
June | 0.559078E+10 | 1.11 | 2420.74 | 29-JUN-18:02 | 1.17 |
July | 0.583618E+10 | 1.12 | 3597.48 | 18-JUL-18:02 | 1.38 |
August | 0.583347E+10 | 1.12 | 3052.09 | 14-AUG-19:10 | 1.29 |
September | 0.562907E+10 | 1.12 | 4650.65 | 21-SEP-21:00 | 1.54 |
October | 0.586104E+10 | 1.12 | 4341.24 | 04-OCT-20:00 | 1.49 |
November | 0.559038E+10 | 1.12 | 2156.78 | 01-NOV-00:10 | 1.12 |
December | 0.577673E+10 | 1.12 | 2156.78 | 01-DEC-15:00 | 1.12 |
Annual Sum or Average | 0.682559E+11 | 1.12 | |||
Minimum of Months | 0.521769E+10 | 1.11 | 2156.78 | 1.12 | |
Maximum of Months | 0.586104E+10 | 1.12 | 4650.65 | 1.54 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | -0.0 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | -0.0 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | -0.0 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: ROOM_1_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175945E+10 | 0.48 | 863.97 | 01-JAN-00:10 | 0.53 |
February | 0.157106E+10 | 0.47 | 863.97 | 01-FEB-00:10 | 0.53 |
March | 0.173576E+10 | 0.47 | 863.97 | 01-MAR-00:10 | 0.53 |
April | 0.171468E+10 | 0.50 | 863.97 | 01-APR-00:10 | 0.53 |
May | 0.175033E+10 | 0.50 | 863.97 | 01-MAY-00:10 | 0.53 |
June | 0.171208E+10 | 0.51 | 863.97 | 01-JUN-00:10 | 0.53 |
July | 0.180371E+10 | 0.52 | 863.97 | 01-JUL-00:10 | 0.53 |
August | 0.181638E+10 | 0.52 | 863.97 | 01-AUG-00:10 | 0.53 |
September | 0.174225E+10 | 0.51 | 863.97 | 01-SEP-00:20 | 0.53 |
October | 0.180031E+10 | 0.51 | 863.97 | 01-OCT-00:10 | 0.53 |
November | 0.171041E+10 | 0.49 | 863.97 | 01-NOV-00:20 | 0.53 |
December | 0.176724E+10 | 0.49 | 863.97 | 01-DEC-00:10 | 0.53 |
Annual Sum or Average | 0.208837E+11 | 0.50 | |||
Minimum of Months | 0.157106E+10 | 0.47 | 863.97 | 0.53 | |
Maximum of Months | 0.181638E+10 | 0.52 | 863.97 | 0.53 |
Report: FanReportMonthly
For: ROOM_2_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164538E+10 | 0.45 | 832.61 | 01-JAN-00:05 | 0.53 |
February | 0.148298E+10 | 0.44 | 832.61 | 01-FEB-00:20 | 0.53 |
March | 0.164571E+10 | 0.45 | 832.61 | 01-MAR-00:10 | 0.53 |
April | 0.162212E+10 | 0.48 | 832.61 | 01-APR-00:10 | 0.53 |
May | 0.166967E+10 | 0.48 | 832.61 | 01-MAY-00:10 | 0.53 |
June | 0.163600E+10 | 0.48 | 832.61 | 01-JUN-00:20 | 0.53 |
July | 0.171766E+10 | 0.49 | 832.61 | 01-JUL-00:10 | 0.53 |
August | 0.171640E+10 | 0.48 | 832.61 | 01-AUG-00:10 | 0.53 |
September | 0.164324E+10 | 0.48 | 832.61 | 01-SEP-00:10 | 0.53 |
October | 0.168913E+10 | 0.48 | 832.61 | 01-OCT-00:10 | 0.53 |
November | 0.160190E+10 | 0.46 | 832.61 | 01-NOV-00:10 | 0.53 |
December | 0.164807E+10 | 0.45 | 832.61 | 01-DEC-00:10 | 0.53 |
Annual Sum or Average | 0.197183E+11 | 0.47 | |||
Minimum of Months | 0.148298E+10 | 0.44 | 832.61 | 0.53 | |
Maximum of Months | 0.171766E+10 | 0.49 | 832.61 | 0.53 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.244485E+10 | 0.39 | 5068.68 | 01-JAN-15:10 | 0.53 |
February | 0.168839E+10 | 0.32 | 5068.68 | 01-FEB-15:10 | 0.53 |
March | 0.149431E+10 | 0.30 | 5068.68 | 01-MAR-15:10 | 0.53 |
April | 0.164690E+10 | 0.38 | 5068.68 | 01-APR-14:10 | 0.53 |
May | 0.127520E+10 | 0.38 | 5068.68 | 01-MAY-14:10 | 0.53 |
June | 0.151288E+10 | 0.44 | 5068.68 | 01-JUN-14:10 | 0.53 |
July | 0.202351E+10 | 0.48 | 5068.68 | 01-JUL-14:10 | 0.53 |
August | 0.242497E+10 | 0.51 | 5068.68 | 01-AUG-14:10 | 0.53 |
September | 0.252682E+10 | 0.49 | 5068.68 | 01-SEP-14:10 | 0.53 |
October | 0.303484E+10 | 0.49 | 5068.68 | 01-OCT-14:10 | 0.53 |
November | 0.246524E+10 | 0.41 | 5068.68 | 01-NOV-14:10 | 0.53 |
December | 0.267046E+10 | 0.39 | 5068.68 | 01-DEC-15:10 | 0.53 |
Annual Sum or Average | 0.252084E+11 | 0.42 | |||
Minimum of Months | 0.127520E+10 | 0.30 | 5068.68 | 0.53 | |
Maximum of Months | 0.303484E+10 | 0.51 | 5068.68 | 0.53 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.802163E+10 | 0.41 | 4134.64 | 01-JAN-00:05 | 0.53 |
February | 0.722836E+10 | 0.39 | 4134.64 | 01-FEB-00:10 | 0.53 |
March | 0.802220E+10 | 0.41 | 4134.64 | 01-MAR-00:10 | 0.53 |
April | 0.782082E+10 | 0.45 | 4134.64 | 01-APR-00:10 | 0.53 |
May | 0.811640E+10 | 0.47 | 4134.64 | 01-MAY-00:10 | 0.53 |
June | 0.797589E+10 | 0.48 | 4134.64 | 01-JUN-00:10 | 0.53 |
July | 0.837907E+10 | 0.48 | 4134.64 | 01-JUL-00:10 | 0.53 |
August | 0.835121E+10 | 0.48 | 4134.64 | 01-AUG-00:10 | 0.53 |
September | 0.795861E+10 | 0.48 | 4134.64 | 01-SEP-00:10 | 0.53 |
October | 0.821413E+10 | 0.47 | 4134.64 | 01-OCT-00:20 | 0.53 |
November | 0.775569E+10 | 0.41 | 4134.64 | 01-NOV-00:30 | 0.53 |
December | 0.801089E+10 | 0.40 | 4134.64 | 01-DEC-00:10 | 0.53 |
Annual Sum or Average | 0.958549E+11 | 0.44 | |||
Minimum of Months | 0.722836E+10 | 0.39 | 4134.64 | 0.53 | |
Maximum of Months | 0.837907E+10 | 0.48 | 4134.64 | 0.53 |
Report: FanReportMonthly
For: ROOM_5_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152836E+10 | 0.50 | 750.04 | 01-JAN-00:10 | 0.53 |
February | 0.136288E+10 | 0.48 | 750.04 | 01-FEB-00:20 | 0.53 |
March | 0.151083E+10 | 0.48 | 750.04 | 01-MAR-00:20 | 0.53 |
April | 0.149323E+10 | 0.51 | 750.04 | 01-APR-00:10 | 0.53 |
May | 0.151701E+10 | 0.51 | 750.04 | 01-MAY-00:10 | 0.53 |
June | 0.148402E+10 | 0.52 | 750.04 | 01-JUN-00:20 | 0.53 |
July | 0.157511E+10 | 0.53 | 750.04 | 01-JUL-00:10 | 0.53 |
August | 0.159140E+10 | 0.53 | 750.04 | 01-AUG-00:40 | 0.53 |
September | 0.151148E+10 | 0.51 | 750.04 | 01-SEP-00:10 | 0.53 |
October | 0.157083E+10 | 0.51 | 750.04 | 01-OCT-00:20 | 0.53 |
November | 0.147879E+10 | 0.50 | 750.04 | 01-NOV-00:10 | 0.53 |
December | 0.153213E+10 | 0.50 | 750.04 | 01-DEC-00:10 | 0.53 |
Annual Sum or Average | 0.181561E+11 | 0.51 | |||
Minimum of Months | 0.136288E+10 | 0.48 | 750.04 | 0.53 | |
Maximum of Months | 0.159140E+10 | 0.53 | 750.04 | 0.53 |
Report: FanReportMonthly
For: ROOM_6_FLR_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139758E+10 | 0.45 | 714.82 | 01-JAN-00:05 | 0.53 |
February | 0.126204E+10 | 0.46 | 714.82 | 01-FEB-00:10 | 0.53 |
March | 0.140947E+10 | 0.47 | 714.82 | 01-MAR-00:10 | 0.53 |
April | 0.139735E+10 | 0.50 | 714.82 | 01-APR-00:10 | 0.53 |
May | 0.143797E+10 | 0.49 | 714.82 | 01-MAY-00:10 | 0.53 |
June | 0.140755E+10 | 0.49 | 714.82 | 01-JUN-00:10 | 0.53 |
July | 0.148458E+10 | 0.49 | 714.82 | 01-JUL-00:10 | 0.53 |
August | 0.148569E+10 | 0.49 | 714.82 | 01-AUG-00:10 | 0.53 |
September | 0.140701E+10 | 0.49 | 714.82 | 01-SEP-00:10 | 0.53 |
October | 0.144879E+10 | 0.49 | 714.82 | 01-OCT-00:10 | 0.53 |
November | 0.135490E+10 | 0.46 | 714.82 | 01-NOV-00:10 | 0.53 |
December | 0.139676E+10 | 0.45 | 714.82 | 01-DEC-00:10 | 0.53 |
Annual Sum or Average | 0.168897E+11 | 0.48 | |||
Minimum of Months | 0.126204E+10 | 0.45 | 714.82 | 0.53 | |
Maximum of Months | 0.148569E+10 | 0.50 | 714.82 | 0.53 |
Report: FanReportMonthly
For: ROOM_1_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.467431E+09 | 0.48 | 230.61 | 01-JAN-00:05 | 0.53 |
February | 0.417585E+09 | 0.46 | 230.61 | 01-FEB-00:10 | 0.53 |
March | 0.462551E+09 | 0.46 | 230.61 | 01-MAR-00:10 | 0.53 |
April | 0.458233E+09 | 0.50 | 230.61 | 01-APR-00:10 | 0.53 |
May | 0.467700E+09 | 0.49 | 230.61 | 01-MAY-00:10 | 0.53 |
June | 0.458517E+09 | 0.51 | 230.61 | 01-JUN-00:10 | 0.53 |
July | 0.484328E+09 | 0.52 | 230.61 | 01-JUL-00:10 | 0.53 |
August | 0.487269E+09 | 0.52 | 230.61 | 01-AUG-00:10 | 0.53 |
September | 0.465524E+09 | 0.51 | 230.61 | 01-SEP-00:10 | 0.53 |
October | 0.479703E+09 | 0.50 | 230.61 | 01-OCT-00:10 | 0.53 |
November | 0.454430E+09 | 0.48 | 230.61 | 01-NOV-00:10 | 0.53 |
December | 0.469279E+09 | 0.48 | 230.61 | 01-DEC-00:10 | 0.53 |
Annual Sum or Average | 0.557255E+10 | 0.49 | |||
Minimum of Months | 0.417585E+09 | 0.46 | 230.61 | 0.53 | |
Maximum of Months | 0.487269E+09 | 0.52 | 230.61 | 0.53 |
Report: FanReportMonthly
For: ROOM_2_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.436867E+09 | 0.44 | 221.80 | 01-JAN-00:05 | 0.53 |
February | 0.393990E+09 | 0.43 | 221.80 | 01-FEB-00:10 | 0.53 |
March | 0.438081E+09 | 0.44 | 221.80 | 01-MAR-00:10 | 0.53 |
April | 0.433277E+09 | 0.48 | 221.80 | 01-APR-00:10 | 0.53 |
May | 0.446007E+09 | 0.47 | 221.80 | 01-MAY-00:10 | 0.53 |
June | 0.438043E+09 | 0.48 | 221.80 | 01-JUN-00:10 | 0.53 |
July | 0.461167E+09 | 0.49 | 221.80 | 01-JUL-00:20 | 0.53 |
August | 0.460464E+09 | 0.48 | 221.80 | 01-AUG-00:10 | 0.53 |
September | 0.438990E+09 | 0.48 | 221.80 | 01-SEP-00:10 | 0.53 |
October | 0.450039E+09 | 0.48 | 221.80 | 01-OCT-00:10 | 0.53 |
November | 0.425383E+09 | 0.45 | 221.80 | 01-NOV-00:10 | 0.53 |
December | 0.437487E+09 | 0.44 | 221.80 | 01-DEC-00:40 | 0.53 |
Annual Sum or Average | 0.525979E+10 | 0.47 | |||
Minimum of Months | 0.393990E+09 | 0.43 | 221.80 | 0.53 | |
Maximum of Months | 0.461167E+09 | 0.49 | 221.80 | 0.53 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.223864E+10 | 0.50 | 1044.45 | 01-JAN-00:05 | 0.53 |
February | 0.195692E+10 | 0.48 | 1044.45 | 01-FEB-00:10 | 0.53 |
March | 0.213887E+10 | 0.47 | 1044.45 | 01-MAR-00:10 | 0.53 |
April | 0.208437E+10 | 0.49 | 1044.45 | 01-APR-00:10 | 0.53 |
May | 0.208888E+10 | 0.48 | 1044.45 | 01-MAY-00:10 | 0.53 |
June | 0.202926E+10 | 0.49 | 1044.45 | 01-JUN-00:10 | 0.53 |
July | 0.214406E+10 | 0.51 | 1044.45 | 01-JUL-00:10 | 0.53 |
August | 0.219524E+10 | 0.51 | 1044.45 | 01-AUG-00:10 | 0.53 |
September | 0.214411E+10 | 0.50 | 1044.45 | 01-SEP-00:10 | 0.53 |
October | 0.226183E+10 | 0.50 | 1044.45 | 01-OCT-00:10 | 0.53 |
November | 0.215861E+10 | 0.50 | 1044.45 | 01-NOV-00:10 | 0.53 |
December | 0.225514E+10 | 0.50 | 1044.45 | 01-DEC-00:10 | 0.53 |
Annual Sum or Average | 0.256959E+11 | 0.49 | |||
Minimum of Months | 0.195692E+10 | 0.47 | 1044.45 | 0.53 | |
Maximum of Months | 0.226183E+10 | 0.51 | 1044.45 | 0.53 |
Report: FanReportMonthly
For: PTAC_3_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.487824E+09 | 0.53 | 590.89 | 18-JAN-13:10 | 0.58 |
February | 0.372885E+09 | 0.51 | 550.88 | 01-FEB-12:00 | 0.58 |
March | 0.390669E+09 | 0.49 | 542.71 | 11-MAR-12:00 | 0.58 |
April | 0.556826E+09 | 0.59 | 487.23 | 26-APR-13:00 | 0.58 |
May | 0.552157E+09 | 0.60 | 434.29 | 04-MAY-18:03 | 0.59 |
June | 0.702867E+09 | 0.60 | 554.75 | 29-JUN-18:10 | 0.58 |
July | 0.893867E+09 | 0.59 | 566.10 | 18-JUL-18:03 | 0.58 |
August | 0.941147E+09 | 0.59 | 583.66 | 18-AUG-12:00 | 0.57 |
September | 0.807151E+09 | 0.60 | 885.83 | 29-SEP-13:00 | 0.55 |
October | 0.829491E+09 | 0.60 | 949.02 | 16-OCT-12:00 | 0.55 |
November | 0.534219E+09 | 0.58 | 666.72 | 19-NOV-13:00 | 0.57 |
December | 0.505736E+09 | 0.54 | 602.10 | 16-DEC-13:00 | 0.57 |
Annual Sum or Average | 0.757484E+10 | 0.57 | |||
Minimum of Months | 0.372885E+09 | 0.49 | 434.29 | 0.55 | |
Maximum of Months | 0.941147E+09 | 0.60 | 949.02 | 0.59 |
Report: FanReportMonthly
For: PTAC_6_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.189905E+09 | 0.31 | 407.94 | 18-JAN-13:10 | 0.57 |
February | 0.148866E+09 | 0.30 | 374.20 | 01-FEB-12:00 | 0.57 |
March | 0.173930E+09 | 0.30 | 396.85 | 11-MAR-11:25 | 0.57 |
April | 0.298406E+09 | 0.45 | 411.78 | 26-APR-13:00 | 0.57 |
May | 0.295639E+09 | 0.49 | 384.93 | 04-MAY-11:50 | 0.57 |
June | 0.392147E+09 | 0.57 | 357.92 | 27-JUN-12:30 | 0.58 |
July | 0.507696E+09 | 0.59 | 438.67 | 31-JUL-12:30 | 0.56 |
August | 0.523882E+09 | 0.60 | 443.45 | 18-AUG-12:00 | 0.56 |
September | 0.419546E+09 | 0.58 | 612.86 | 29-SEP-12:50 | 0.54 |
October | 0.407789E+09 | 0.53 | 612.51 | 16-OCT-12:00 | 0.54 |
November | 0.219914E+09 | 0.39 | 436.39 | 19-NOV-12:30 | 0.57 |
December | 0.195912E+09 | 0.31 | 419.51 | 19-DEC-12:50 | 0.57 |
Annual Sum or Average | 0.377363E+10 | 0.45 | |||
Minimum of Months | 0.148866E+09 | 0.30 | 357.92 | 0.54 | |
Maximum of Months | 0.523882E+09 | 0.60 | 612.86 | 0.58 |
Report: FanReportMonthly
For: PSZ_LAUNDRY_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169986E+11 | 1.35 | 6346.56 | 01-JAN-16:16 | 1.35 |
February | 0.153536E+11 | 1.35 | 6346.56 | 21-FEB-11:40 | 1.35 |
March | 0.169986E+11 | 1.35 | 6346.56 | 04-MAR-08:63 | 1.35 |
April | 0.164503E+11 | 1.35 | 6346.56 | 20-APR-17:30 | 1.35 |
May | 0.169986E+11 | 1.35 | 6346.56 | 09-MAY-09:50 | 1.34 |
June | 0.164503E+11 | 1.34 | 6346.56 | 02-JUN-08:62 | 1.35 |
July | 0.169986E+11 | 1.34 | 6346.56 | 01-JUL-21:10 | 1.34 |
August | 0.169986E+11 | 1.34 | 6346.56 | 01-AUG-06:50 | 1.34 |
September | 0.164503E+11 | 1.34 | 6346.56 | 01-SEP-03:30 | 1.34 |
October | 0.169986E+11 | 1.35 | 6346.56 | 01-OCT-09:52 | 1.34 |
November | 0.164503E+11 | 1.35 | 6346.56 | 01-NOV-06:05 | 1.35 |
December | 0.169986E+11 | 1.35 | 6346.56 | 13-DEC-11:05 | 1.35 |
Annual Sum or Average | 0.200145E+12 | 1.35 | |||
Minimum of Months | 0.153536E+11 | 1.34 | 6346.56 | 1.34 | |
Maximum of Months | 0.169986E+11 | 1.35 | 6346.56 | 1.35 |
Report: FanReportMonthly
For: PSZ_CAFE_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.968220E+10 | 1.38 | 3614.92 | 03-JAN-03:50 | 1.38 |
February | 0.874521E+10 | 1.38 | 3614.92 | 03-FEB-09:07 | 1.39 |
March | 0.968220E+10 | 1.38 | 3614.92 | 01-MAR-06:20 | 1.38 |
April | 0.936987E+10 | 1.38 | 3614.92 | 03-APR-09:00 | 1.39 |
May | 0.968220E+10 | 1.38 | 3614.92 | 04-MAY-17:20 | 1.38 |
June | 0.936987E+10 | 1.37 | 3614.92 | 05-JUN-09:40 | 1.38 |
July | 0.968220E+10 | 1.37 | 3614.92 | 04-JUL-15:12 | 1.38 |
August | 0.968220E+10 | 1.37 | 3614.92 | 04-AUG-18:08 | 1.37 |
September | 0.936987E+10 | 1.37 | 3614.92 | 02-SEP-15:00 | 1.38 |
October | 0.968220E+10 | 1.38 | 3614.92 | 01-OCT-17:15 | 1.37 |
November | 0.936987E+10 | 1.38 | 3614.92 | 04-NOV-12:00 | 1.38 |
December | 0.968220E+10 | 1.38 | 3614.92 | 03-DEC-14:50 | 1.38 |
Annual Sum or Average | 0.114000E+12 | 1.38 | |||
Minimum of Months | 0.874521E+10 | 1.37 | 3614.92 | 1.37 | |
Maximum of Months | 0.968220E+10 | 1.38 | 3614.92 | 1.39 |
Report: FanReportMonthly
For: PSZ_KITCHEN_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.117175E+11 | 1.35 | 4374.81 | 17-JAN-11:10 | 1.35 |
February | 0.105835E+11 | 1.35 | 4374.81 | 01-FEB-11:05 | 1.35 |
March | 0.117175E+11 | 1.35 | 4374.81 | 10-MAR-08:48 | 1.35 |
April | 0.113395E+11 | 1.35 | 4374.81 | 05-APR-10:00 | 1.34 |
May | 0.117175E+11 | 1.35 | 4374.81 | 02-MAY-11:40 | 1.35 |
June | 0.113395E+11 | 1.34 | 4374.81 | 08-JUN-16:58 | 1.35 |
July | 0.117175E+11 | 1.34 | 4374.81 | 03-JUL-11:40 | 1.34 |
August | 0.117175E+11 | 1.34 | 4374.81 | 11-AUG-13:10 | 1.34 |
September | 0.113395E+11 | 1.34 | 4374.81 | 03-SEP-07:32 | 1.35 |
October | 0.117175E+11 | 1.35 | 4374.81 | 03-OCT-17:10 | 1.34 |
November | 0.113395E+11 | 1.35 | 4374.81 | 01-NOV-00:10 | 1.35 |
December | 0.117175E+11 | 1.35 | 4374.81 | 16-DEC-08:13 | 1.35 |
Annual Sum or Average | 0.137964E+12 | 1.35 | |||
Minimum of Months | 0.105835E+11 | 1.34 | 4374.81 | 1.34 | |
Maximum of Months | 0.117175E+11 | 1.35 | 4374.81 | 1.35 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.162704E+09 | 0.146433E+09 | 512.80 | 08-JAN-06:50 | 461.52 | 461.52 | 38.88 | 0.63 |
February | 76122371.77 | 68510134.60 | 374.00 | 05-FEB-06:00 | 336.60 | 336.60 | 35.52 | 0.43 |
March | 0.140860E+09 | 0.126774E+09 | 739.44 | 28-MAR-08:62 | 665.50 | 665.50 | 33.97 | 1.04 |
April | 19345314.43 | 17410782.99 | 288.27 | 01-APR-06:00 | 259.44 | 259.44 | 33.07 | 0.32 |
May | 18859330.18 | 16973397.16 | 225.06 | 14-MAY-04:50 | 202.55 | 202.55 | 31.92 | 0.25 |
June | 904352.05 | 813916.84 | 103.07 | 12-JUN-08:56 | 92.76 | 92.76 | 23.04 | 0.11 |
July | 42454.93 | 38209.44 | 30.72 | 17-JUL-21:55 | 27.65 | 27.65 | 23.39 | 0.03 |
August | 32156.40 | 28940.76 | 23.28 | 22-AUG-08:03 | 20.95 | 20.95 | 23.60 | 0.02 |
September | 571120.28 | 514008.25 | 63.02 | 18-SEP-19:06 | 56.72 | 56.72 | 23.93 | 0.07 |
October | 7679529.30 | 6911576.37 | 196.14 | 11-OCT-19:06 | 176.52 | 176.52 | 23.95 | 0.21 |
November | 59309060.32 | 53378154.28 | 320.02 | 23-NOV-19:05 | 288.01 | 288.01 | 27.23 | 0.36 |
December | 0.138349E+09 | 0.124514E+09 | 421.57 | 13-DEC-04:30 | 379.41 | 379.41 | 33.34 | 0.50 |
Annual Sum or Average | 0.624779E+09 | 0.562301E+09 | ||||||
Minimum of Months | 32156.40 | 28940.76 | 23.28 | 20.95 | 20.95 | 23.04 | 0.02 | |
Maximum of Months | 0.162704E+09 | 0.146433E+09 | 739.44 | 665.50 | 665.50 | 38.88 | 1.04 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 50.16 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:10 | 14.37 | 14.37 | 51.31 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:10 | 14.37 | 14.37 | 51.35 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.58 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 53.73 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.90 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.02 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.07 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.03 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.19 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 53.77 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:10 | 14.37 | 14.37 | 51.53 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 50.16 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.07 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 28.96 | 66.76 | 9907.27 | 93285.61 | 08-JAN-06:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.08 | 65.60 | 5204.71 | 68906.11 | 27-FEB-16:14 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 30.28 | 67.96 | 8648.28 | 139824.61 | 28-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.96 | 65.97 | 1269.93 | 48890.86 | 01-APR-05:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 24.99 | 24.99 | 1175.63 | 36758.48 | 14-MAY-04:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.42 | 25.42 | 62.61 | 19309.51 | 12-JUN-08:56 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23.34 | 23.34 | 2.87 | 5578.25 | 17-JUL-21:55 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.44 | 23.44 | 2.16 | 4195.44 | 22-AUG-08:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.70 | 23.70 | 39.38 | 11409.22 | 18-SEP-19:06 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24.32 | 24.32 | 483.97 | 37104.40 | 11-OCT-19:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26.91 | 26.91 | 3780.50 | 58346.40 | 23-NOV-19:05 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 31.46 | 65.60 | 8349.79 | 73496.62 | 13-DEC-04:30 |
Annual Sum or Average | 0.00 | 3249.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.34 | 23.34 | 2.16 | 4195.44 | ||
Maximum of Months | 0.00 | 0.00 | 31.46 | 67.96 | 9907.27 | 139824.61 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 50.16 | 60.05 | 23120.51 | 48443.82 | 31-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 51.31 | 60.05 | 23150.48 | 48446.25 | 02-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 51.35 | 60.05 | 22919.27 | 48206.65 | 01-MAR-07:56 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.58 | 60.05 | 22438.01 | 47337.07 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 53.73 | 60.05 | 21878.40 | 46292.24 | 01-MAY-06:52 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.90 | 60.05 | 21381.45 | 45108.67 | 01-JUN-06:52 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.02 | 60.05 | 21050.28 | 44195.94 | 03-JUL-06:54 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.07 | 60.05 | 21039.85 | 44109.19 | 31-AUG-06:51 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.03 | 60.05 | 21284.59 | 44854.86 | 29-SEP-06:54 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.19 | 60.05 | 21748.39 | 46035.25 | 31-OCT-06:53 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.77 | 60.05 | 22311.73 | 47180.59 | 30-NOV-07:45 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 51.53 | 60.05 | 22812.07 | 48035.31 | 29-DEC-07:45 |
Annual Sum or Average | 0.00 | 22088.55 | ||||||
Minimum of Months | 0.00 | 0.00 | 50.16 | 60.05 | 21039.85 | 44109.19 | ||
Maximum of Months | 0.00 | 0.00 | 54.07 | 60.05 | 23150.48 | 48446.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.558133E+10 | 0.00 | 0.00 | 0.165751E+11 | 0.00 | 0.00 |
February | 0.201164E+10 | 0.00 | 0.00 | 0.132103E+11 | 0.00 | 0.00 |
March | 0.473757E+10 | 0.00 | 0.00 | 0.143207E+11 | 0.00 | 0.00 |
April | 0.411803E+09 | 0.00 | 0.00 | 0.179708E+11 | 0.00 | 0.00 |
May | 0.520743E+09 | 0.00 | 0.00 | 0.189334E+11 | 0.00 | 0.00 |
June | 49005245.32 | 0.00 | 0.00 | 0.255321E+11 | 0.00 | 0.00 |
July | 1671042.05 | 0.00 | 0.00 | 0.364880E+11 | 0.00 | 0.00 |
August | 11576.77 | 0.00 | 0.00 | 0.390173E+11 | 0.00 | 0.00 |
September | 13044455.83 | 0.00 | 0.00 | 0.309093E+11 | 0.00 | 0.00 |
October | 0.146562E+09 | 0.00 | 0.00 | 0.330495E+11 | 0.00 | 0.00 |
November | 0.136641E+10 | 0.00 | 0.00 | 0.169624E+11 | 0.00 | 0.00 |
December | 0.421977E+10 | 0.00 | 0.00 | 0.175730E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.190596E+11 | 0.00 | 0.00 | 0.280542E+12 | 0.00 | 0.00 |
Minimum of Months | 11576.77 | 0.00 | 0.00 | 0.132103E+11 | 0.00 | 0.00 |
Maximum of Months | 0.558133E+10 | 0.00 | 0.00 | 0.390173E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.108559E+11 | 0.00 | 0.00 | 0.151185E+11 | 0.00 | 0.00 |
February | 0.552294E+10 | 0.00 | 0.00 | 0.125088E+11 | 0.00 | 0.00 |
March | 0.938823E+10 | 0.00 | 0.00 | 0.139649E+11 | 0.00 | 0.00 |
April | 0.161757E+10 | 0.00 | 0.00 | 0.176922E+11 | 0.00 | 0.00 |
May | 0.156621E+10 | 0.00 | 0.00 | 0.192615E+11 | 0.00 | 0.00 |
June | 40669443.52 | 0.00 | 0.00 | 0.260603E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.370477E+11 | 0.00 | 0.00 |
August | 2917.73 | 0.00 | 0.00 | 0.383404E+11 | 0.00 | 0.00 |
September | 37718346.71 | 0.00 | 0.00 | 0.289357E+11 | 0.00 | 0.00 |
October | 0.662013E+09 | 0.00 | 0.00 | 0.293135E+11 | 0.00 | 0.00 |
November | 0.444395E+10 | 0.00 | 0.00 | 0.153263E+11 | 0.00 | 0.00 |
December | 0.970366E+10 | 0.00 | 0.00 | 0.154541E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.438389E+11 | 0.00 | 0.00 | 0.269024E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.125088E+11 | 0.00 | 0.00 |
Maximum of Months | 0.108559E+11 | 0.00 | 0.00 | 0.383404E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.766123E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.578859E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.635457E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.747789E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.779584E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.100567E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.152656E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.164766E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.134322E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.145987E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.782006E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.774322E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.120471E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.578859E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.164766E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.182278E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.156007E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.174993E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.181260E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.184064E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.208073E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.257916E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.265678E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.217882E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.236014E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.173336E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.184255E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.242176E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.156007E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.265678E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.107426E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.919310E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.102885E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.105216E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.102432E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.109111E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.131303E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.139791E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.125414E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.137267E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.105039E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.111359E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.136917E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.919310E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.139791E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.141426E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.117850E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.134923E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.156423E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.160830E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.187595E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.239891E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.248532E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.200667E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.211929E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.138164E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142581E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.208081E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.117850E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.248532E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114252E+11 | 0.174625E+11 | 0.558133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101010E+11 | 0.102182E+11 | 0.201164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109272E+11 | 0.114446E+11 | 0.473757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107396E+11 | 0.245631E+11 | 0.411803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109143E+11 | 0.267373E+11 | 0.520743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108759E+11 | 0.505499E+11 | 49005245.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116193E+11 | 0.905107E+11 | 1671042.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119791E+11 | 0.997901E+11 | 11576.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116294E+11 | 0.680910E+11 | 13044455.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126029E+11 | 0.740130E+11 | 0.146562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112459E+11 | 0.193383E+11 | 0.136641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116930E+11 | 0.203027E+11 | 0.421977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135753E+12 | 0.513021E+12 | 0.190596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101010E+11 | 0.102182E+11 | 11576.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126029E+11 | 0.997901E+11 | 0.558133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109715E+11 | 0.140425E+11 | 0.108559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.993936E+10 | 0.842318E+10 | 0.552294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111204E+11 | 0.959918E+10 | 0.938823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113820E+11 | 0.217171E+11 | 0.161757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120759E+11 | 0.242812E+11 | 0.156621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125560E+11 | 0.475160E+11 | 40669443.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134918E+11 | 0.877419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132278E+11 | 0.946148E+11 | 2917.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119788E+11 | 0.607096E+11 | 37718346.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121600E+11 | 0.625569E+11 | 0.662013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107557E+11 | 0.153207E+11 | 0.444395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109671E+11 | 0.152158E+11 | 0.970366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140626E+12 | 0.461739E+12 | 0.438389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.993936E+10 | 0.842318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134918E+11 | 0.946148E+11 | 0.108559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.577673E+10 | 0.650903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.521769E+10 | 0.188709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.577673E+10 | 0.191554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.559038E+10 | 0.637313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.577673E+10 | 0.680248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.559078E+10 | 0.155396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.583618E+10 | 0.345769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.583347E+10 | 0.393680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.562907E+10 | 0.280737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.586104E+10 | 0.316961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.559038E+10 | 0.761041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.577673E+10 | 0.665637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.682559E+11 | 0.187008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.521769E+10 | 0.188709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.586104E+10 | 0.393680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169986E+11 | 0.470710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153536E+11 | 0.927033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169986E+11 | 0.189778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164503E+11 | 0.637060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169986E+11 | 0.524360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164503E+11 | 0.169617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169986E+11 | 0.354713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169986E+11 | 0.390083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164503E+11 | 0.207281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169986E+11 | 0.256781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164503E+11 | 0.330959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169986E+11 | 0.538105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200145E+12 | 0.165684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153536E+11 | 0.927033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169986E+11 | 0.390083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.968220E+10 | 0.413728E+10 | 0.400804E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.874521E+10 | 0.174004E+10 | 53473354.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.968220E+10 | 0.241139E+10 | 0.442123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.936987E+10 | 0.445188E+10 | 9042947.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.968220E+10 | 0.207186E+10 | 1908617.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.936987E+10 | 0.582065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.968220E+10 | 0.135714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.968220E+10 | 0.174560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.936987E+10 | 0.124288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.968220E+10 | 0.156427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.936987E+10 | 0.449389E+10 | 18490029.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.968220E+10 | 0.587891E+10 | 0.157306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114000E+12 | 0.901048E+11 | 0.108315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.874521E+10 | 0.174004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.968220E+10 | 0.174560E+11 | 0.442123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.117175E+11 | 0.970494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105835E+11 | 0.463665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117175E+11 | 0.716968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113395E+11 | 0.176159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117175E+11 | 0.177091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113395E+11 | 0.309913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117175E+11 | 0.515931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117175E+11 | 0.550955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113395E+11 | 0.361346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117175E+11 | 0.385791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113395E+11 | 0.977664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117175E+11 | 0.102384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137964E+12 | 0.289245E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105835E+11 | 0.463665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117175E+11 | 0.550955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.114252E+11 | 0.558133E+10 | 0.00 | 0.00 | 0.514993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101010E+11 | 0.201164E+10 | 0.00 | 0.00 | 0.310937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109272E+11 | 0.473757E+10 | 0.00 | 0.00 | 0.339351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107396E+11 | 0.411803E+09 | 0.00 | 0.00 | 0.723120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109143E+11 | 0.520743E+09 | 0.00 | 0.00 | 0.801916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108759E+11 | 49005245.32 | 0.00 | 0.00 | 0.146562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116193E+11 | 1671042.05 | 0.00 | 0.00 | 0.248687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119791E+11 | 11576.77 | 0.00 | 0.00 | 0.270381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116294E+11 | 13044455.83 | 0.00 | 0.00 | 0.192798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126029E+11 | 0.146562E+09 | 0.00 | 0.00 | 0.204465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112459E+11 | 0.136641E+10 | 0.00 | 0.00 | 0.571646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116930E+11 | 0.421977E+10 | 0.00 | 0.00 | 0.587994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135753E+12 | 0.190596E+11 | 0.00 | 0.00 | 0.144789E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101010E+11 | 11576.77 | 0.00 | 0.00 | 0.310937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126029E+11 | 0.558133E+10 | 0.00 | 0.00 | 0.270381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109715E+11 | 0.108559E+11 | 0.00 | 0.00 | 0.414707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.993936E+10 | 0.552294E+10 | 0.00 | 0.00 | 0.256941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111204E+11 | 0.938823E+10 | 0.00 | 0.00 | 0.284459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113820E+11 | 0.161757E+10 | 0.00 | 0.00 | 0.631021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120759E+11 | 0.156621E+10 | 0.00 | 0.00 | 0.718558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125560E+11 | 40669443.52 | 0.00 | 0.00 | 0.135043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134918E+11 | 0.00 | 0.00 | 0.00 | 0.235559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132278E+11 | 2917.73 | 0.00 | 0.00 | 0.251125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119788E+11 | 37718346.71 | 0.00 | 0.00 | 0.169569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121600E+11 | 0.662013E+09 | 0.00 | 0.00 | 0.171535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107557E+11 | 0.444395E+10 | 0.00 | 0.00 | 0.457065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109671E+11 | 0.970366E+10 | 0.00 | 0.00 | 0.448698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140626E+12 | 0.438389E+11 | 0.00 | 0.00 | 0.128398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.993936E+10 | 0.00 | 0.00 | 0.00 | 0.256941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134918E+11 | 0.108559E+11 | 0.00 | 0.00 | 0.251125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_FLR_0
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.577673E+10 | 0.00 | 0.00 | 0.00 | 0.188450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.521769E+10 | 0.00 | 0.00 | 0.00 | 0.570893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.577673E+10 | 0.00 | 0.00 | 0.00 | 0.577839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.559038E+10 | 0.00 | 0.00 | 0.00 | 0.188751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.577673E+10 | 0.00 | 0.00 | 0.00 | 0.201911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.559078E+10 | 0.00 | 0.00 | 0.00 | 0.446592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.583618E+10 | 0.00 | 0.00 | 0.00 | 0.942940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.583347E+10 | 0.00 | 0.00 | 0.00 | 0.106431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.562907E+10 | 0.00 | 0.00 | 0.00 | 0.780316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.586104E+10 | 0.00 | 0.00 | 0.00 | 0.873770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.559038E+10 | 0.00 | 0.00 | 0.00 | 0.222968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.577673E+10 | 0.00 | 0.00 | 0.00 | 0.196649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.682559E+11 | 0.00 | 0.00 | 0.00 | 0.522153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.521769E+10 | 0.00 | 0.00 | 0.00 | 0.570893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.586104E+10 | 0.00 | 0.00 | 0.00 | 0.106431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_LAUNDRY
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169986E+11 | 0.00 | 0.00 | 0.00 | 0.122916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153536E+11 | 0.00 | 0.00 | 0.00 | 0.247118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169986E+11 | 0.00 | 0.00 | 0.00 | 0.500675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164503E+11 | 0.00 | 0.00 | 0.00 | 0.167575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169986E+11 | 0.00 | 0.00 | 0.00 | 0.140781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164503E+11 | 0.00 | 0.00 | 0.00 | 0.435702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169986E+11 | 0.00 | 0.00 | 0.00 | 0.879302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169986E+11 | 0.00 | 0.00 | 0.00 | 0.956917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164503E+11 | 0.00 | 0.00 | 0.00 | 0.533793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169986E+11 | 0.00 | 0.00 | 0.00 | 0.660273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164503E+11 | 0.00 | 0.00 | 0.00 | 0.883345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169986E+11 | 0.00 | 0.00 | 0.00 | 0.142686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200145E+12 | 0.00 | 0.00 | 0.00 | 0.420306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153536E+11 | 0.00 | 0.00 | 0.00 | 0.247118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169986E+11 | 0.00 | 0.00 | 0.00 | 0.956917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_CAFE
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.968220E+10 | 0.00 | 0.00 | 0.00 | 0.106042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.874521E+10 | 0.00 | 0.00 | 0.00 | 0.447893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.968220E+10 | 0.00 | 0.00 | 0.00 | 0.606264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.936987E+10 | 0.00 | 0.00 | 0.00 | 0.115171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.968220E+10 | 0.00 | 0.00 | 0.00 | 0.561007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.936987E+10 | 0.00 | 0.00 | 0.00 | 0.154118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.968220E+10 | 0.00 | 0.00 | 0.00 | 0.344807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.968220E+10 | 0.00 | 0.00 | 0.00 | 0.429686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.936987E+10 | 0.00 | 0.00 | 0.00 | 0.317154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.968220E+10 | 0.00 | 0.00 | 0.00 | 0.404454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.936987E+10 | 0.00 | 0.00 | 0.00 | 0.113405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.968220E+10 | 0.00 | 0.00 | 0.00 | 0.145374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114000E+12 | 0.00 | 0.00 | 0.00 | 0.229173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.874521E+10 | 0.00 | 0.00 | 0.00 | 0.447893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.968220E+10 | 0.00 | 0.00 | 0.00 | 0.429686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ_KITCHEN
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.117175E+11 | 0.00 | 0.00 | 0.00 | 0.242511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105835E+11 | 0.00 | 0.00 | 0.00 | 0.120144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117175E+11 | 0.00 | 0.00 | 0.00 | 0.177479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113395E+11 | 0.00 | 0.00 | 0.00 | 0.430282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117175E+11 | 0.00 | 0.00 | 0.00 | 0.436547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113395E+11 | 0.00 | 0.00 | 0.00 | 0.742001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117175E+11 | 0.00 | 0.00 | 0.00 | 0.122716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117175E+11 | 0.00 | 0.00 | 0.00 | 0.131357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113395E+11 | 0.00 | 0.00 | 0.00 | 0.872721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117175E+11 | 0.00 | 0.00 | 0.00 | 0.947542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113395E+11 | 0.00 | 0.00 | 0.00 | 0.247686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117175E+11 | 0.00 | 0.00 | 0.00 | 0.254064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137964E+12 | 0.00 | 0.00 | 0.00 | 0.701171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.105835E+11 | 0.00 | 0.00 | 0.00 | 0.120144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117175E+11 | 0.00 | 0.00 | 0.00 | 0.131357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.248281E+09 | 0.111453E+09 | 0.00 | 84912186.30 | 0.00 | 0.00 | 0.477206E+11 | 0.00 | 0.97 |
February | 78963057.91 | 29710592.26 | 0.00 | 68075177.56 | 0.00 | 0.00 | 0.427559E+11 | 0.00 | 0.92 |
March | 0.273823E+10 | 10991604.00 | 0.00 | 66482573.59 | 0.00 | 0.00 | 0.439541E+11 | 0.00 | 0.86 |
April | 57809239.83 | 0.127638E+09 | 0.00 | 82455489.79 | 0.00 | 0.00 | 0.402638E+11 | 0.00 | 1.02 |
May | 5797822.34 | 48895499.33 | 0.00 | 89913543.88 | 0.00 | 0.00 | 0.414948E+11 | 0.00 | 1.05 |
June | 0.00 | 0.469742E+09 | 0.00 | 88284454.89 | 0.00 | 0.00 | 0.312563E+11 | 0.00 | 1.15 |
July | 0.00 | 0.324079E+10 | 0.00 | 83163100.21 | 0.00 | 0.00 | 0.196823E+11 | 0.00 | 1.17 |
August | 0.00 | 0.409419E+10 | 0.00 | 72765523.13 | 0.00 | 0.00 | 0.166001E+11 | 0.00 | 1.16 |
September | 0.00 | 0.167676E+10 | 0.00 | 91676238.91 | 0.00 | 0.00 | 0.256413E+11 | 0.00 | 1.19 |
October | 0.00 | 0.310617E+10 | 0.00 | 84240658.66 | 0.00 | 0.00 | 0.272056E+11 | 0.00 | 1.13 |
November | 0.00 | 65110262.43 | 0.00 | 92419705.13 | 0.00 | 0.00 | 0.464211E+11 | 0.00 | 1.06 |
December | 11728939.92 | 34885389.93 | 0.00 | 89302890.88 | 0.00 | 0.00 | 0.475979E+11 | 0.00 | 0.97 |
Annual Sum or Average | 0.314081E+10 | 0.130163E+11 | 0.00 | 0.993692E+09 | 0.00 | 0.00 | 0.430594E+12 | 0.00 | 1.06 |
Minimum of Months | 0.00 | 10991604.00 | 0.00 | 66482573.59 | 0.00 | 0.00 | 0.166001E+11 | 0.00 | 0.86 |
Maximum of Months | 0.273823E+10 | 0.409419E+10 | 0.00 | 92419705.13 | 0.00 | 0.00 | 0.477206E+11 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.425053E+10 | 12725667.12 | 0.00 | 6858015.47 | 352085.88 | 0.368899E+09 | 0.248306E+10 | 0.00 | 2.76 |
February | 0.422805E+10 | 3246385.51 | 0.00 | 4872347.90 | 0.00 | 89235455.78 | 0.174887E+10 | 0.00 | 2.55 |
March | 0.458246E+10 | 117914.39 | 0.00 | 4180340.46 | 0.00 | 0.482368E+09 | 0.124024E+10 | 0.00 | 2.29 |
April | 0.404234E+10 | 8991744.43 | 0.00 | 4869854.70 | 11566.38 | 58247342.55 | 0.115712E+10 | 0.00 | 2.45 |
May | 0.443571E+10 | 2696330.56 | 0.00 | 2092389.75 | 24356.41 | 14512268.44 | 0.607828E+09 | 0.00 | 2.21 |
June | 0.325339E+10 | 66375105.13 | 0.00 | 2459434.91 | 8178304.56 | 0.00 | 0.601261E+09 | 0.00 | 2.34 |
July | 0.207364E+10 | 0.405947E+09 | 0.00 | 2903683.77 | 28801860.47 | 0.00 | 0.521785E+09 | 0.00 | 2.42 |
August | 0.179091E+10 | 0.581741E+09 | 0.00 | 3203126.94 | 29905054.98 | 0.00 | 0.562475E+09 | 0.00 | 2.67 |
September | 0.252546E+10 | 0.250088E+09 | 0.00 | 5988210.70 | 28947221.03 | 0.00 | 0.105833E+10 | 0.00 | 2.92 |
October | 0.269249E+10 | 0.538828E+09 | 0.00 | 6194613.90 | 17647890.80 | 0.00 | 0.117337E+10 | 0.00 | 2.95 |
November | 0.426341E+10 | 6721803.41 | 0.00 | 7361583.31 | 0.00 | 6546658.44 | 0.219471E+10 | 0.00 | 2.85 |
December | 0.439785E+10 | 3477376.86 | 0.00 | 8537681.72 | 0.00 | 0.140883E+09 | 0.237029E+10 | 0.00 | 2.88 |
Annual Sum or Average | 0.425362E+11 | 0.188096E+10 | 0.00 | 59521283.52 | 0.113868E+09 | 0.116069E+10 | 0.157193E+11 | 0.00 | 2.61 |
Minimum of Months | 0.179091E+10 | 117914.39 | 0.00 | 2092389.75 | 0.00 | 0.00 | 0.521785E+09 | 0.00 | 2.21 |
Maximum of Months | 0.458246E+10 | 0.581741E+09 | 0.00 | 8537681.72 | 29905054.98 | 0.482368E+09 | 0.248306E+10 | 0.00 | 2.95 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290587E+10 | 1964654.41 | 0.00 | 1663224.28 | 2579770.42 | 0.00 | 0.190974E+10 | 0.00 | 1.38 |
February | 0.272801E+10 | 678577.27 | 0.00 | 1512082.44 | 122785.25 | 0.00 | 0.164577E+10 | 0.00 | 1.40 |
March | 0.326187E+10 | 0.00 | 0.00 | 1715480.83 | 37104.68 | 0.00 | 0.160786E+10 | 0.00 | 1.36 |
April | 0.218191E+10 | 589045.64 | 0.00 | 3361270.01 | 3373987.43 | 0.00 | 0.208860E+10 | 0.00 | 1.54 |
May | 0.231838E+10 | 474299.97 | 0.00 | 2882394.63 | 1310797.89 | 0.00 | 0.193280E+10 | 0.00 | 1.57 |
June | 0.132448E+10 | 15860963.63 | 0.00 | 3866914.68 | 36696211.84 | 0.00 | 0.202688E+10 | 0.00 | 1.72 |
July | 0.475118E+09 | 0.170533E+09 | 0.00 | 4549505.29 | 95207785.29 | 0.00 | 0.182151E+10 | 0.00 | 1.74 |
August | 0.271022E+09 | 0.216749E+09 | 0.00 | 5044248.68 | 90636535.54 | 0.00 | 0.183015E+10 | 0.00 | 1.75 |
September | 0.735728E+09 | 71372451.24 | 0.00 | 4748809.59 | 47018565.06 | 0.00 | 0.224372E+10 | 0.00 | 1.72 |
October | 0.103050E+10 | 0.159486E+09 | 0.00 | 4241021.17 | 36181895.14 | 0.00 | 0.207495E+10 | 0.00 | 1.64 |
November | 0.237054E+10 | 1584968.08 | 0.00 | 2145705.17 | 180695.76 | 0.00 | 0.216482E+10 | 0.00 | 1.46 |
December | 0.272530E+10 | 693691.86 | 0.00 | 1975328.94 | 240423.60 | 0.00 | 0.201850E+10 | 0.00 | 1.38 |
Annual Sum or Average | 0.223287E+11 | 0.639986E+09 | 0.00 | 37705985.71 | 0.313587E+09 | 0.00 | 0.233653E+11 | 0.00 | 1.56 |
Minimum of Months | 0.271022E+09 | 0.00 | 0.00 | 1512082.44 | 37104.68 | 0.00 | 0.160786E+10 | 0.00 | 1.36 |
Maximum of Months | 0.326187E+10 | 0.216749E+09 | 0.00 | 5044248.68 | 95207785.29 | 0.00 | 0.224372E+10 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.310047E+10 | 372052.16 | 0.00 | 937665.07 | 3334750.02 | 0.00 | 0.872266E+09 | 0.00 | 0.54 |
February | 0.284670E+10 | 200291.59 | 0.00 | 726845.35 | 453364.80 | 0.00 | 0.752512E+09 | 0.00 | 0.55 |
March | 0.320910E+10 | 0.00 | 0.00 | 786884.53 | 30265.59 | 0.00 | 0.783604E+09 | 0.00 | 0.53 |
April | 0.229265E+10 | 925571.09 | 0.00 | 1959631.03 | 2307000.73 | 0.00 | 0.127828E+10 | 0.00 | 0.61 |
May | 0.221904E+10 | 1140066.02 | 0.00 | 2585752.95 | 316004.86 | 0.00 | 0.142728E+10 | 0.00 | 0.63 |
June | 0.122564E+10 | 40737488.34 | 0.00 | 4539681.68 | 2609255.06 | 0.00 | 0.177334E+10 | 0.00 | 0.72 |
July | 0.585872E+09 | 0.232768E+09 | 0.00 | 5889950.82 | 2961313.02 | 0.00 | 0.148790E+10 | 0.00 | 0.74 |
August | 0.506315E+09 | 0.262855E+09 | 0.00 | 5444076.34 | 5886732.95 | 0.00 | 0.137629E+10 | 0.00 | 0.74 |
September | 0.100014E+10 | 89680420.45 | 0.00 | 4287664.12 | 15597928.15 | 0.00 | 0.158971E+10 | 0.00 | 0.71 |
October | 0.113744E+10 | 0.169587E+09 | 0.00 | 3804630.00 | 5014853.32 | 0.00 | 0.156293E+10 | 0.00 | 0.68 |
November | 0.265908E+10 | 1006748.56 | 0.00 | 1225524.69 | 433470.36 | 0.00 | 0.112020E+10 | 0.00 | 0.57 |
December | 0.296399E+10 | 156706.17 | 0.00 | 972740.25 | 605234.30 | 0.00 | 0.951418E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.237464E+11 | 0.799429E+09 | 0.00 | 33161046.83 | 39550173.16 | 0.00 | 0.149757E+11 | 0.00 | 0.63 |
Minimum of Months | 0.506315E+09 | 0.00 | 0.00 | 726845.35 | 30265.59 | 0.00 | 0.752512E+09 | 0.00 | 0.53 |
Maximum of Months | 0.320910E+10 | 0.262855E+09 | 0.00 | 5889950.82 | 15597928.15 | 0.00 | 0.177334E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.299307E+10 | 0.00 | 0.00 | 0.00 | 2861477.70 | 0.00 | 0.00 | 0.00 | 0.70 |
February | 0.270865E+10 | 0.00 | 0.00 | 0.00 | 504592.13 | 0.00 | 0.00 | 0.00 | 0.71 |
March | 0.301441E+10 | 0.00 | 0.00 | 0.00 | 23363.62 | 0.00 | 0.00 | 0.00 | 0.69 |
April | 0.256719E+10 | 0.00 | 0.00 | 0.00 | 2495394.07 | 0.00 | 0.00 | 0.00 | 0.76 |
May | 0.257549E+10 | 0.00 | 0.00 | 0.00 | 1124018.53 | 0.00 | 0.00 | 0.00 | 0.78 |
June | 0.193182E+10 | 19264.63 | 0.00 | 15016.65 | 33019705.29 | 0.00 | 38036667.05 | 0.00 | 0.83 |
July | 0.125545E+10 | 9515676.27 | 0.00 | 73115.73 | 0.153973E+09 | 0.00 | 69521414.42 | 0.00 | 0.82 |
August | 0.114377E+10 | 14316688.71 | 0.00 | 46201.46 | 0.176489E+09 | 0.00 | 50685470.26 | 0.00 | 0.82 |
September | 0.172710E+10 | 21944473.83 | 0.00 | 45586.42 | 49291290.98 | 0.00 | 9205205.59 | 0.00 | 0.83 |
October | 0.179927E+10 | 31072730.52 | 0.00 | 35444.71 | 88051488.23 | 0.00 | 30895743.04 | 0.00 | 0.79 |
November | 0.278961E+10 | 0.00 | 0.00 | 0.00 | 1111781.56 | 0.00 | 0.00 | 0.00 | 0.73 |
December | 0.293752E+10 | 0.00 | 0.00 | 0.00 | 588182.37 | 0.00 | 0.00 | 0.00 | 0.70 |
Annual Sum or Average | 0.274434E+11 | 76868833.96 | 0.00 | 215364.96 | 0.509533E+09 | 0.00 | 0.198345E+09 | 0.00 | 0.76 |
Minimum of Months | 0.114377E+10 | 0.00 | 0.00 | 0.00 | 23363.62 | 0.00 | 0.00 | 0.00 | 0.69 |
Maximum of Months | 0.301441E+10 | 31072730.52 | 0.00 | 73115.73 | 0.176489E+09 | 0.00 | 69521414.42 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 53297113.69 | 0.00 | 0.114707E+09 | 0.00 | 0.00 | 0.631619E+11 | 0.00 | 24.56 |
February | 0.00 | 7661152.23 | 0.00 | 0.104073E+09 | 0.00 | 0.00 | 0.602860E+11 | 0.00 | 24.84 |
March | 0.00 | 2811501.71 | 0.00 | 0.116315E+09 | 0.00 | 0.00 | 0.659547E+11 | 0.00 | 23.81 |
April | 0.00 | 62896009.66 | 0.00 | 0.131140E+09 | 0.00 | 0.00 | 0.600649E+11 | 0.00 | 29.80 |
May | 0.00 | 23543405.07 | 0.00 | 0.143224E+09 | 0.00 | 0.00 | 0.634183E+11 | 0.00 | 31.77 |
June | 0.00 | 0.753949E+09 | 0.00 | 0.140918E+09 | 0.00 | 0.00 | 0.507069E+11 | 0.00 | 36.33 |
July | 0.00 | 0.267464E+10 | 0.00 | 0.125782E+09 | 0.00 | 0.00 | 0.367604E+11 | 0.00 | 35.34 |
August | 0.00 | 0.348752E+10 | 0.00 | 0.112000E+09 | 0.00 | 0.00 | 0.342667E+11 | 0.00 | 35.30 |
September | 0.00 | 0.762456E+09 | 0.00 | 0.127480E+09 | 0.00 | 0.00 | 0.469378E+11 | 0.00 | 35.86 |
October | 0.00 | 0.147736E+10 | 0.00 | 0.117262E+09 | 0.00 | 0.00 | 0.449942E+11 | 0.00 | 33.31 |
November | 0.00 | 30103529.08 | 0.00 | 0.115621E+09 | 0.00 | 0.00 | 0.627582E+11 | 0.00 | 27.07 |
December | 0.00 | 8728596.06 | 0.00 | 0.116056E+09 | 0.00 | 0.00 | 0.624493E+11 | 0.00 | 25.51 |
Annual Sum or Average | 0.00 | 0.934497E+10 | 0.00 | 0.146458E+10 | 0.00 | 0.00 | 0.651760E+12 | 0.00 | 30.32 |
Minimum of Months | 0.00 | 2811501.71 | 0.00 | 0.104073E+09 | 0.00 | 0.00 | 0.342667E+11 | 0.00 | 23.81 |
Maximum of Months | 0.00 | 0.348752E+10 | 0.00 | 0.143224E+09 | 0.00 | 0.00 | 0.659547E+11 | 0.00 | 36.33 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.936833E+10 | 13998224.96 | 0.00 | 40261682.25 | 0.00 | 0.00 | 0.300563E+11 | 0.00 | 5.26 |
February | 0.595189E+10 | 2582633.59 | 0.00 | 33246631.30 | 0.00 | 0.00 | 0.287765E+11 | 0.00 | 4.80 |
March | 0.106899E+11 | 10983067.98 | 0.00 | 30085344.35 | 0.00 | 0.00 | 0.262474E+11 | 0.00 | 4.55 |
April | 0.256830E+10 | 66634421.69 | 0.00 | 43383021.00 | 0.00 | 0.00 | 0.317004E+11 | 0.00 | 5.60 |
May | 0.198099E+10 | 10090292.75 | 0.00 | 40831907.34 | 0.00 | 0.00 | 0.333911E+11 | 0.00 | 5.58 |
June | 26617007.60 | 0.223403E+09 | 0.00 | 48627653.37 | 0.00 | 0.00 | 0.318632E+11 | 0.00 | 6.81 |
July | 0.00 | 0.167821E+10 | 0.00 | 49802970.82 | 0.00 | 0.00 | 0.290339E+11 | 0.00 | 7.48 |
August | 1340957.13 | 0.252218E+10 | 0.00 | 47317201.11 | 0.00 | 0.00 | 0.282055E+11 | 0.00 | 7.62 |
September | 42018522.42 | 0.805817E+09 | 0.00 | 53147982.40 | 0.00 | 0.00 | 0.305681E+11 | 0.00 | 7.19 |
October | 0.579684E+09 | 0.130346E+10 | 0.00 | 51420873.89 | 0.00 | 0.00 | 0.306176E+11 | 0.00 | 7.09 |
November | 0.318203E+10 | 4588700.36 | 0.00 | 47808077.53 | 0.00 | 0.00 | 0.342538E+11 | 0.00 | 5.42 |
December | 0.818492E+10 | 2561106.04 | 0.00 | 45614383.63 | 0.00 | 0.00 | 0.302350E+11 | 0.00 | 5.36 |
Annual Sum or Average | 0.425760E+11 | 0.664451E+10 | 0.00 | 0.531548E+09 | 0.00 | 0.00 | 0.364949E+12 | 0.00 | 6.07 |
Minimum of Months | 0.00 | 2561106.04 | 0.00 | 30085344.35 | 0.00 | 0.00 | 0.262474E+11 | 0.00 | 4.55 |
Maximum of Months | 0.106899E+11 | 0.252218E+10 | 0.00 | 53147982.40 | 0.00 | 0.00 | 0.342538E+11 | 0.00 | 7.62 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202273E+11 | 65772955.95 | 0.00 | 85996075.47 | 37819312.97 | 0.00 | 0.806767E+11 | 0.00 | 1.73 |
February | 0.224493E+11 | 19936899.07 | 0.00 | 64965808.05 | 0.00 | 0.00 | 0.685019E+11 | 0.00 | 1.75 |
March | 0.359642E+11 | 775166.23 | 0.00 | 57866271.08 | 11355.93 | 0.00 | 0.643394E+11 | 0.00 | 1.67 |
April | 0.179660E+11 | 70179681.10 | 0.00 | 81418010.83 | 11669178.95 | 0.00 | 0.686594E+11 | 0.00 | 1.86 |
May | 0.213519E+11 | 28866521.48 | 0.00 | 66698406.15 | 8001256.93 | 0.00 | 0.650904E+11 | 0.00 | 1.89 |
June | 0.848288E+10 | 0.864675E+09 | 0.00 | 89963610.63 | 0.219178E+09 | 0.00 | 0.589965E+11 | 0.00 | 2.05 |
July | 0.284897E+10 | 0.461028E+10 | 0.00 | 0.106784E+09 | 0.789203E+09 | 0.00 | 0.431390E+11 | 0.00 | 2.05 |
August | 0.201623E+10 | 0.537814E+10 | 0.00 | 0.118366E+09 | 0.936127E+09 | 0.00 | 0.403070E+11 | 0.00 | 2.08 |
September | 0.427890E+10 | 0.206541E+10 | 0.00 | 0.125765E+09 | 0.526922E+09 | 0.00 | 0.561630E+11 | 0.00 | 2.09 |
October | 0.485030E+10 | 0.408211E+10 | 0.00 | 0.125120E+09 | 0.390749E+09 | 0.00 | 0.594093E+11 | 0.00 | 2.04 |
November | 0.114477E+11 | 44028321.42 | 0.00 | 0.100116E+09 | 0.00 | 0.00 | 0.834698E+11 | 0.00 | 1.84 |
December | 0.175155E+11 | 22187380.80 | 0.00 | 0.101853E+09 | 0.00 | 0.00 | 0.819301E+11 | 0.00 | 1.76 |
Annual Sum or Average | 0.169399E+12 | 0.172524E+11 | 0.00 | 0.112491E+10 | 0.291968E+10 | 0.00 | 0.770683E+12 | 0.00 | 1.90 |
Minimum of Months | 0.201623E+10 | 775166.23 | 0.00 | 57866271.08 | 0.00 | 0.00 | 0.403070E+11 | 0.00 | 1.67 |
Maximum of Months | 0.359642E+11 | 0.537814E+10 | 0.00 | 0.125765E+09 | 0.936127E+09 | 0.00 | 0.834698E+11 | 0.00 | 2.09 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5732607.73 | 7835728.51 | 0.00 | 10543161.30 | 0.00 | 0.888683E+09 | 0.825517E+09 | 0.00 | 0.36 |
February | 8651275.67 | 1518616.61 | 0.00 | 10368586.76 | 0.00 | 0.704913E+09 | 0.745473E+09 | 0.00 | 0.35 |
March | 18870588.58 | 15034926.92 | 0.00 | 9563866.69 | 0.00 | 0.867556E+09 | 0.748870E+09 | 0.00 | 0.35 |
April | 1590328.29 | 50125020.94 | 0.00 | 12649784.93 | 0.00 | 0.227537E+09 | 0.739972E+09 | 0.00 | 0.36 |
May | 2470684.48 | 24224490.00 | 9935.29 | 14369968.90 | 0.00 | 0.211688E+09 | 0.746372E+09 | 94.90 | 0.36 |
June | 0.00 | 0.169942E+09 | 0.00 | 9239478.59 | 0.00 | 17718719.79 | 0.340141E+09 | 0.00 | 0.36 |
July | 0.00 | 0.614589E+09 | 55353.10 | 3498217.04 | 0.00 | 90723.70 | 67097099.07 | 421.03 | 0.37 |
August | 0.00 | 0.748602E+09 | 153647.40 | 1996575.91 | 0.00 | 115958.11 | 43895855.59 | 748.03 | 0.37 |
September | 0.00 | 0.300966E+09 | 5755.99 | 6139653.74 | 0.00 | 9521029.06 | 0.221589E+09 | 1754.18 | 0.37 |
October | 0.00 | 0.321784E+09 | 5991.69 | 9545240.96 | 0.00 | 0.151510E+09 | 0.509366E+09 | 2323.95 | 0.37 |
November | 389445.30 | 7437743.93 | 0.00 | 12708154.20 | 0.00 | 0.562955E+09 | 0.811114E+09 | 0.00 | 0.36 |
December | 3189794.81 | 2631888.36 | 0.00 | 12940443.30 | 0.00 | 0.854274E+09 | 0.879864E+09 | 0.00 | 0.36 |
Annual Sum or Average | 40894724.85 | 0.226469E+10 | 230683.48 | 0.113563E+09 | 0.00 | 0.449656E+10 | 0.667927E+10 | 5342.09 | 0.36 |
Minimum of Months | 0.00 | 1518616.61 | 0.00 | 1996575.91 | 0.00 | 90723.70 | 43895855.59 | 0.00 | 0.35 |
Maximum of Months | 18870588.58 | 0.748602E+09 | 153647.40 | 14369968.90 | 0.00 | 0.888683E+09 | 0.879864E+09 | 2323.95 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119911E+09 | 1505626.16 | 0.00 | 4953513.33 | 11057.79 | 0.101804E+10 | 0.688512E+09 | 602.76 | 0.35 |
February | 94338336.07 | 742973.94 | 0.00 | 5343029.45 | 4246.87 | 0.792359E+09 | 0.651876E+09 | 0.00 | 0.35 |
March | 94980934.64 | 2421062.46 | 0.00 | 6380389.86 | 297199.23 | 0.900157E+09 | 0.728956E+09 | 0.00 | 0.35 |
April | 0.209212E+09 | 13100532.22 | 21422.99 | 11208485.17 | 478676.08 | 0.175407E+09 | 0.755696E+09 | 200.03 | 0.36 |
May | 0.291860E+09 | 5825380.73 | 0.00 | 14230234.19 | 143910.74 | 0.125317E+09 | 0.749506E+09 | 0.00 | 0.35 |
June | 0.457975E+09 | 75928501.23 | 35509.56 | 12996273.91 | 4696365.21 | 2485943.21 | 0.279446E+09 | 9052.62 | 0.36 |
July | 0.417493E+09 | 0.339407E+09 | 34308.63 | 10848531.75 | 20999170.98 | 348401.93 | 46194815.12 | 4342.86 | 0.37 |
August | 0.393301E+09 | 0.406093E+09 | 4184.32 | 8988435.49 | 28689284.97 | 239841.60 | 37317648.90 | 2999.72 | 0.37 |
September | 0.360691E+09 | 0.132428E+09 | 29117.88 | 10015791.21 | 7248225.71 | 3570737.11 | 0.188147E+09 | 8755.65 | 0.36 |
October | 0.355449E+09 | 0.167860E+09 | 32026.47 | 8236873.46 | 14830443.28 | 0.125735E+09 | 0.453414E+09 | 5208.39 | 0.36 |
November | 0.156555E+09 | 1407163.84 | 0.00 | 6244206.58 | 13158.82 | 0.661913E+09 | 0.684409E+09 | 195.65 | 0.35 |
December | 0.146723E+09 | 1140752.10 | 0.00 | 5082037.82 | 0.00 | 0.100600E+10 | 0.670701E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.309849E+10 | 0.114786E+10 | 156569.86 | 0.104528E+09 | 77411739.68 | 0.481158E+10 | 0.593418E+10 | 31357.68 | 0.36 |
Minimum of Months | 94338336.07 | 742973.94 | 0.00 | 4953513.33 | 0.00 | 239841.60 | 37317648.90 | 0.00 | 0.35 |
Maximum of Months | 0.457975E+09 | 0.406093E+09 | 35509.56 | 14230234.19 | 28689284.97 | 0.101804E+10 | 0.755696E+09 | 9052.62 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49325473.86 | 3335508.22 | 0.00 | 0.122268E+09 | 0.00 | 0.00 | 0.411961E+10 | 0.00 | 0.09 |
February | 0.215643E+09 | 1171389.74 | 0.00 | 79566913.72 | 0.00 | 0.00 | 0.287684E+10 | 0.00 | 0.07 |
March | 0.340228E+09 | 8607638.85 | 0.00 | 60927738.86 | 0.00 | 0.00 | 0.201802E+10 | 0.00 | 0.06 |
April | 24565586.01 | 8543166.27 | 0.00 | 76929888.54 | 0.00 | 0.00 | 0.190678E+10 | 0.00 | 0.06 |
May | 50407131.03 | 0.00 | 0.00 | 51857792.98 | 0.00 | 0.00 | 0.164085E+10 | 0.00 | 0.05 |
June | 0.00 | 81211382.59 | 0.00 | 63359719.46 | 0.00 | 0.00 | 0.116606E+10 | 0.00 | 0.06 |
July | 0.00 | 0.806912E+09 | 0.00 | 58783002.44 | 0.00 | 0.00 | 0.524729E+09 | 0.00 | 0.07 |
August | 0.00 | 0.127302E+10 | 0.00 | 48662105.90 | 0.00 | 0.00 | 0.361603E+09 | 0.00 | 0.09 |
September | 0.00 | 0.548303E+09 | 0.00 | 96738114.00 | 0.00 | 0.00 | 0.106298E+10 | 0.00 | 0.10 |
October | 0.00 | 0.943614E+09 | 0.00 | 0.113737E+09 | 0.00 | 0.00 | 0.183037E+10 | 0.00 | 0.11 |
November | 0.00 | 2455835.59 | 0.00 | 0.129385E+09 | 0.00 | 0.00 | 0.388138E+10 | 0.00 | 0.09 |
December | 40602105.21 | 761947.31 | 0.00 | 0.144911E+09 | 0.00 | 0.00 | 0.427361E+10 | 0.00 | 0.10 |
Annual Sum or Average | 0.720772E+09 | 0.367794E+10 | 0.00 | 0.104713E+10 | 0.00 | 0.00 | 0.256628E+11 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 48662105.90 | 0.00 | 0.00 | 0.361603E+09 | 0.00 | 0.05 |
Maximum of Months | 0.340228E+09 | 0.127302E+10 | 0.00 | 0.144911E+09 | 0.00 | 0.00 | 0.427361E+10 | 0.00 | 0.11 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.180573E+10 | 49474266.88 | 0.00 | 72542822.27 | 7806523.32 | 0.351146E+10 | 0.171936E+11 | 2029.08 | 0.39 |
February | 0.139273E+10 | 18814021.34 | 0.00 | 69532712.16 | 289504.19 | 0.586828E+09 | 0.168389E+11 | 0.00 | 0.39 |
March | 0.138588E+10 | 30773113.31 | 122871.22 | 78038705.57 | 1103066.70 | 0.259069E+10 | 0.177145E+11 | 1135.65 | 0.39 |
April | 0.214002E+10 | 0.140172E+09 | 0.00 | 0.123908E+09 | 2290666.29 | 0.139019E+09 | 0.117992E+11 | 0.00 | 0.39 |
May | 0.294041E+10 | 74173177.96 | 0.00 | 0.172111E+09 | 417988.89 | 8880074.15 | 0.110860E+11 | 0.00 | 0.39 |
June | 0.466140E+10 | 0.863990E+09 | 0.00 | 0.189942E+09 | 51588590.50 | 1404117.62 | 0.352495E+10 | 0.00 | 0.40 |
July | 0.466995E+10 | 0.403184E+10 | 0.00 | 0.214719E+09 | 0.244956E+09 | 0.00 | 0.605436E+09 | 0.00 | 0.41 |
August | 0.442627E+10 | 0.476720E+10 | 53853.22 | 0.177286E+09 | 0.339921E+09 | 0.00 | 0.494551E+09 | 3525.44 | 0.41 |
September | 0.415981E+10 | 0.165018E+10 | 0.00 | 0.151893E+09 | 53043556.78 | 1772463.92 | 0.254378E+10 | 0.00 | 0.40 |
October | 0.415799E+10 | 0.238625E+10 | 49471.85 | 0.145976E+09 | 0.151775E+09 | 4521283.82 | 0.709785E+10 | 263.29 | 0.40 |
November | 0.227028E+10 | 33700585.57 | 0.00 | 87263367.85 | 200157.04 | 0.209806E+09 | 0.160291E+11 | 0.00 | 0.39 |
December | 0.198898E+10 | 48459541.26 | 487029.23 | 72356559.90 | 482494.61 | 0.199934E+10 | 0.184807E+11 | 567.78 | 0.39 |
Annual Sum or Average | 0.359995E+11 | 0.140950E+11 | 713225.53 | 0.155557E+10 | 0.853875E+09 | 0.905372E+10 | 0.123408E+12 | 7521.25 | 0.40 |
Minimum of Months | 0.138588E+10 | 18814021.34 | 0.00 | 69532712.16 | 200157.04 | 0.00 | 0.494551E+09 | 0.00 | 0.39 |
Maximum of Months | 0.466995E+10 | 0.476720E+10 | 487029.23 | 0.214719E+09 | 0.339921E+09 | 0.351146E+10 | 0.184807E+11 | 3525.44 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5419544.35 | 10096762.97 | 0.00 | 12415329.74 | 0.00 | 0.850986E+09 | 0.869473E+09 | 0.00 | 0.36 |
February | 7620695.00 | 1409922.03 | 0.00 | 10702627.54 | 0.00 | 0.713840E+09 | 0.762029E+09 | 0.00 | 0.35 |
March | 19713865.39 | 16265454.68 | 0.00 | 10707378.71 | 0.00 | 0.866806E+09 | 0.772168E+09 | 0.00 | 0.36 |
April | 2093843.27 | 55592996.76 | 0.00 | 13689236.06 | 0.00 | 0.284819E+09 | 0.732979E+09 | 0.00 | 0.36 |
May | 2514496.64 | 27544469.22 | 13071.86 | 14670827.41 | 0.00 | 0.255086E+09 | 0.755024E+09 | 662.31 | 0.36 |
June | 0.00 | 0.170885E+09 | 40909.67 | 10031892.30 | 0.00 | 24674457.87 | 0.393968E+09 | 24.67 | 0.36 |
July | 0.00 | 0.601622E+09 | 0.00 | 4433108.74 | 0.00 | 4449.13 | 98666926.34 | 0.00 | 0.37 |
August | 0.00 | 0.740625E+09 | 15372.20 | 2736724.79 | 0.00 | 46555.57 | 59973978.34 | 3.08 | 0.37 |
September | 0.00 | 0.291111E+09 | 35017.19 | 6903465.20 | 0.00 | 20867682.33 | 0.258600E+09 | 635.52 | 0.37 |
October | 0.00 | 0.313048E+09 | 218592.86 | 12035602.42 | 0.00 | 0.173782E+09 | 0.508266E+09 | 679.97 | 0.37 |
November | 0.00 | 6965915.08 | 0.00 | 14111417.19 | 0.00 | 0.571558E+09 | 0.823568E+09 | 0.00 | 0.36 |
December | 4845078.12 | 2589116.98 | 0.00 | 14890389.99 | 0.00 | 0.831583E+09 | 0.912175E+09 | 0.00 | 0.36 |
Annual Sum or Average | 42207522.77 | 0.223776E+10 | 322963.76 | 0.127328E+09 | 0.00 | 0.459405E+10 | 0.694689E+10 | 2005.55 | 0.36 |
Minimum of Months | 0.00 | 1409922.03 | 0.00 | 2736724.79 | 0.00 | 4449.13 | 59973978.34 | 0.00 | 0.35 |
Maximum of Months | 19713865.39 | 0.740625E+09 | 218592.86 | 14890389.99 | 0.00 | 0.866806E+09 | 0.912175E+09 | 679.97 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124416E+09 | 3003937.94 | 0.00 | 6181639.72 | 0.00 | 0.976248E+09 | 0.726103E+09 | 0.00 | 0.34 |
February | 97224188.06 | 649449.58 | 0.00 | 5698778.90 | 0.00 | 0.837245E+09 | 0.621072E+09 | 0.00 | 0.35 |
March | 85270353.00 | 6308913.59 | 0.00 | 7026594.70 | 360646.82 | 0.927149E+09 | 0.729843E+09 | 0.00 | 0.35 |
April | 0.159568E+09 | 26075645.61 | 0.00 | 11475666.27 | 464542.37 | 0.268814E+09 | 0.731733E+09 | 0.00 | 0.36 |
May | 0.233638E+09 | 12304520.69 | 0.00 | 14345089.26 | 97977.70 | 0.198493E+09 | 0.746396E+09 | 0.00 | 0.36 |
June | 0.370408E+09 | 87151193.54 | 0.00 | 11889022.65 | 5586079.44 | 11213925.92 | 0.338624E+09 | 0.00 | 0.36 |
July | 0.358237E+09 | 0.341477E+09 | 21227.73 | 11396923.01 | 22359254.81 | 377220.43 | 94169885.16 | 36.82 | 0.37 |
August | 0.341495E+09 | 0.411488E+09 | 0.00 | 9275553.16 | 31377833.71 | 384860.45 | 73383586.58 | 0.00 | 0.37 |
September | 0.315353E+09 | 0.138732E+09 | 0.00 | 9699934.54 | 6288065.42 | 15365804.32 | 0.246181E+09 | 430.47 | 0.36 |
October | 0.330397E+09 | 0.167052E+09 | 0.00 | 10287879.27 | 13005767.73 | 0.152453E+09 | 0.456792E+09 | 0.00 | 0.36 |
November | 0.165821E+09 | 1543582.78 | 0.00 | 7551812.49 | 0.00 | 0.650691E+09 | 0.705529E+09 | 0.00 | 0.35 |
December | 0.162167E+09 | 1013128.26 | 0.00 | 6480572.45 | 0.00 | 0.953233E+09 | 0.720389E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.274399E+10 | 0.119680E+10 | 21227.73 | 0.111309E+09 | 79540167.99 | 0.499167E+10 | 0.619022E+10 | 467.29 | 0.35 |
Minimum of Months | 85270353.00 | 649449.58 | 0.00 | 5698778.90 | 0.00 | 377220.43 | 73383586.58 | 0.00 | 0.34 |
Maximum of Months | 0.370408E+09 | 0.411488E+09 | 21227.73 | 14345089.26 | 31377833.71 | 0.976248E+09 | 0.746396E+09 | 430.47 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 24413464.15 | 0.00 | 0.00 | 0.377297E+10 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.00 | 18789840.84 | 0.00 | 0.00 | 0.311569E+10 | 0.00 | 0.04 |
March | 0.00 | 2649148.40 | 0.00 | 18805065.83 | 0.00 | 0.00 | 0.290992E+10 | 0.00 | 0.04 |
April | 0.00 | 455211.59 | 0.00 | 31103830.34 | 0.00 | 0.00 | 0.304669E+10 | 0.00 | 0.06 |
May | 0.00 | 521.43 | 0.00 | 31615531.22 | 0.00 | 0.00 | 0.322385E+10 | 0.00 | 0.06 |
June | 0.00 | 62780756.79 | 0.00 | 37876585.04 | 0.00 | 0.00 | 0.239301E+10 | 0.00 | 0.08 |
July | 0.00 | 0.593784E+09 | 0.00 | 34498040.75 | 0.00 | 0.00 | 0.135779E+10 | 0.00 | 0.09 |
August | 0.00 | 0.797444E+09 | 0.00 | 27787232.52 | 0.00 | 0.00 | 0.105525E+10 | 0.00 | 0.10 |
September | 0.00 | 0.235612E+09 | 0.00 | 35002725.42 | 0.00 | 0.00 | 0.193002E+10 | 0.00 | 0.09 |
October | 0.00 | 0.304287E+09 | 0.00 | 35601435.98 | 0.00 | 0.00 | 0.277794E+10 | 0.00 | 0.09 |
November | 0.00 | 69593.89 | 0.00 | 28130998.84 | 0.00 | 0.00 | 0.383717E+10 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.00 | 27613248.30 | 0.00 | 0.00 | 0.424877E+10 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.199708E+10 | 0.00 | 0.351238E+09 | 0.00 | 0.00 | 0.336691E+11 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 18789840.84 | 0.00 | 0.00 | 0.105525E+10 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.797444E+09 | 0.00 | 37876585.04 | 0.00 | 0.00 | 0.424877E+10 | 0.00 | 0.10 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1684361.53 | 1651843.17 | 38.20 | 2105815.65 | 0.00 | 0.321387E+09 | 0.130466E+09 | 149.11 | 0.35 |
February | 3774916.96 | 359386.95 | 0.00 | 2130656.07 | 0.00 | 0.267256E+09 | 0.117653E+09 | 0.00 | 0.35 |
March | 6398182.08 | 3751158.38 | 0.00 | 2008780.07 | 0.00 | 0.311167E+09 | 0.119148E+09 | 0.00 | 0.35 |
April | 711348.22 | 12462916.28 | 0.00 | 2816474.68 | 0.00 | 0.152684E+09 | 0.115554E+09 | 0.00 | 0.36 |
May | 716636.53 | 6066879.44 | 1946.60 | 3231949.41 | 0.00 | 0.141232E+09 | 0.124009E+09 | 667.07 | 0.36 |
June | 0.00 | 42016523.76 | 0.00 | 2060679.68 | 0.00 | 37068622.92 | 73339273.18 | 0.00 | 0.36 |
July | 0.00 | 0.147396E+09 | 4295.94 | 835466.11 | 0.00 | 2679048.87 | 23443036.55 | 8.46 | 0.37 |
August | 0.00 | 0.176346E+09 | 5190.21 | 514440.72 | 0.00 | 1593895.02 | 16757912.91 | 86.52 | 0.37 |
September | 44018.00 | 68744750.04 | 1123.39 | 1366958.61 | 0.00 | 18368774.07 | 59238153.20 | 702.73 | 0.37 |
October | 103668.20 | 74969628.77 | 1079.10 | 1978204.02 | 0.00 | 91723849.80 | 89427386.21 | 985.47 | 0.37 |
November | 0.00 | 1753753.41 | 0.00 | 2587224.03 | 0.00 | 0.229214E+09 | 0.139011E+09 | 0.00 | 0.36 |
December | 1860896.23 | 725168.57 | 0.00 | 2602644.25 | 0.00 | 0.313283E+09 | 0.137520E+09 | 0.00 | 0.36 |
Annual Sum or Average | 15294027.74 | 0.536244E+09 | 13673.45 | 24239293.30 | 0.00 | 0.188766E+10 | 0.114557E+10 | 2599.37 | 0.36 |
Minimum of Months | 0.00 | 359386.95 | 0.00 | 514440.72 | 0.00 | 1593895.02 | 16757912.91 | 0.00 | 0.35 |
Maximum of Months | 6398182.08 | 0.176346E+09 | 5190.21 | 3231949.41 | 0.00 | 0.321387E+09 | 0.139011E+09 | 985.47 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 31286052.10 | 257772.47 | 0.00 | 835944.44 | 2677.79 | 0.374739E+09 | 74454960.74 | 0.00 | 0.35 |
February | 27491059.89 | 172186.88 | 0.00 | 963012.87 | 1035.21 | 0.288397E+09 | 93773468.64 | 0.00 | 0.35 |
March | 25040966.45 | 656951.85 | 0.00 | 1281505.43 | 75913.08 | 0.322508E+09 | 0.112166E+09 | 0.00 | 0.35 |
April | 53928459.80 | 3611115.15 | 0.00 | 2621764.42 | 121695.89 | 0.126351E+09 | 0.129251E+09 | 0.00 | 0.36 |
May | 74369441.38 | 1749806.88 | 0.00 | 3385863.71 | 38310.02 | 94868983.50 | 0.143800E+09 | 0.00 | 0.36 |
June | 0.116451E+09 | 20979451.21 | 8114.33 | 3200859.72 | 1128675.55 | 11281703.93 | 70567355.42 | 1444.56 | 0.36 |
July | 0.106286E+09 | 88025890.59 | 5819.84 | 2791955.44 | 4966491.94 | 45352.68 | 15366977.90 | 625.34 | 0.37 |
August | 0.101744E+09 | 0.104337E+09 | 1604.48 | 2298035.47 | 6736946.20 | 54347.88 | 12132814.14 | 980.18 | 0.37 |
September | 92911931.32 | 31785384.31 | 12066.12 | 2375919.37 | 1757825.34 | 9525401.71 | 47937508.06 | 1900.06 | 0.36 |
October | 89132999.81 | 40656709.53 | 4313.64 | 1733865.21 | 3490175.69 | 77165993.14 | 79037739.92 | 343.32 | 0.36 |
November | 39821757.07 | 322580.03 | 0.00 | 1056922.62 | 2867.13 | 0.253789E+09 | 0.108476E+09 | 0.00 | 0.35 |
December | 36567563.06 | 325410.31 | 0.00 | 826520.74 | 0.00 | 0.357897E+09 | 80159873.37 | 2392.48 | 0.35 |
Annual Sum or Average | 0.795031E+09 | 0.292880E+09 | 31918.40 | 23372169.44 | 18322613.84 | 0.191662E+10 | 0.967124E+09 | 7685.94 | 0.36 |
Minimum of Months | 25040966.45 | 172186.88 | 0.00 | 826520.74 | 0.00 | 45352.68 | 12132814.14 | 0.00 | 0.35 |
Maximum of Months | 0.116451E+09 | 0.104337E+09 | 12066.12 | 3385863.71 | 6736946.20 | 0.374739E+09 | 0.143800E+09 | 2392.48 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3039591.28 | 20013674.56 | 0.00 | 25062971.62 | 0.00 | 0.132930E+10 | 0.150139E+10 | 0.00 | 0.43 |
February | 13508940.77 | 2830324.48 | 0.00 | 19516180.00 | 0.00 | 0.115547E+10 | 0.125512E+10 | 0.00 | 0.41 |
March | 30907877.12 | 28691725.23 | 0.00 | 15354905.52 | 0.00 | 0.150636E+10 | 0.119386E+10 | 0.00 | 0.41 |
April | 4095971.88 | 70625995.24 | 2500.32 | 15600613.79 | 0.00 | 0.652555E+09 | 0.110814E+10 | 351.69 | 0.41 |
May | 4025354.70 | 22854775.27 | 8829.58 | 14896842.97 | 0.00 | 0.692918E+09 | 0.110326E+10 | 2030.00 | 0.40 |
June | 0.00 | 0.180895E+09 | 16046.42 | 11416307.01 | 0.00 | 0.137464E+09 | 0.713713E+09 | 1903.04 | 0.40 |
July | 0.00 | 0.717759E+09 | 420144.94 | 6211444.95 | 0.00 | 14999815.08 | 0.248080E+09 | 24147.94 | 0.41 |
August | 0.00 | 0.951602E+09 | 733906.06 | 4442181.33 | 0.00 | 423374.65 | 0.151443E+09 | 35664.25 | 0.42 |
September | 0.00 | 0.448204E+09 | 112420.07 | 9405389.69 | 0.00 | 47161363.26 | 0.478888E+09 | 4653.32 | 0.42 |
October | 0.00 | 0.520926E+09 | 131373.08 | 16223792.31 | 0.00 | 0.313264E+09 | 0.823117E+09 | 1117.97 | 0.43 |
November | 0.00 | 16601436.65 | 0.00 | 26520960.85 | 0.00 | 0.882684E+09 | 0.139664E+10 | 0.00 | 0.42 |
December | 2432767.13 | 6375834.52 | 0.00 | 30881286.48 | 0.00 | 0.128166E+10 | 0.157379E+10 | 0.00 | 0.43 |
Annual Sum or Average | 58010502.88 | 0.298738E+10 | 1425220.46 | 0.195533E+09 | 0.00 | 0.801426E+10 | 0.115474E+11 | 69868.21 | 0.42 |
Minimum of Months | 0.00 | 2830324.48 | 0.00 | 4442181.33 | 0.00 | 423374.65 | 0.151443E+09 | 0.00 | 0.40 |
Maximum of Months | 30907877.12 | 0.951602E+09 | 733906.06 | 30881286.48 | 0.00 | 0.150636E+10 | 0.157379E+10 | 35664.25 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.492086E+10 | 19073079.63 | 0.00 | 42927629.70 | 455505.91 | 0.00 | 0.543558E+11 | 0.00 | 4.82 |
February | 0.301163E+10 | 4755200.22 | 0.00 | 41467796.29 | 0.00 | 0.00 | 0.508931E+11 | 0.00 | 4.83 |
March | 0.337031E+10 | 0.00 | 0.00 | 51591002.97 | 0.00 | 0.00 | 0.584086E+11 | 0.00 | 4.78 |
April | 0.604765E+09 | 10480612.95 | 0.00 | 78785200.20 | 0.00 | 0.00 | 0.521089E+11 | 0.00 | 5.16 |
May | 0.472203E+09 | 0.00 | 0.00 | 89093693.13 | 0.00 | 0.00 | 0.539462E+11 | 0.00 | 5.33 |
June | 0.167510E+09 | 0.196474E+09 | 0.00 | 0.105724E+09 | 0.00 | 0.00 | 0.428156E+11 | 0.00 | 5.80 |
July | 23848035.37 | 0.248661E+10 | 0.00 | 0.102883E+09 | 7009868.21 | 0.00 | 0.294358E+11 | 0.00 | 5.86 |
August | 63317442.88 | 0.299298E+10 | 0.00 | 91662173.03 | 10141553.83 | 0.00 | 0.260059E+11 | 0.00 | 5.80 |
September | 0.341806E+09 | 0.111575E+10 | 0.00 | 85102613.18 | 38919525.48 | 0.00 | 0.355874E+11 | 0.00 | 5.62 |
October | 0.665293E+09 | 0.199126E+10 | 0.00 | 71193306.77 | 25094042.70 | 0.00 | 0.367118E+11 | 0.00 | 5.43 |
November | 0.195936E+10 | 6136867.95 | 0.00 | 48956689.86 | 0.00 | 0.00 | 0.525487E+11 | 0.00 | 4.95 |
December | 0.370575E+10 | 7740994.54 | 0.00 | 43178850.47 | 2474710.70 | 0.00 | 0.543700E+11 | 0.00 | 4.80 |
Annual Sum or Average | 0.193066E+11 | 0.883127E+10 | 0.00 | 0.852566E+09 | 84095206.84 | 0.00 | 0.547188E+12 | 0.00 | 5.27 |
Minimum of Months | 23848035.37 | 0.00 | 0.00 | 41467796.29 | 0.00 | 0.00 | 0.260059E+11 | 0.00 | 4.78 |
Maximum of Months | 0.492086E+10 | 0.299298E+10 | 0.00 | 0.105724E+09 | 38919525.48 | 0.00 | 0.584086E+11 | 0.00 | 5.86 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.249496E+10 | 19529396.12 | 0.00 | 55623563.05 | 0.00 | 0.00 | 0.579393E+11 | 0.00 | 4.91 |
February | 0.128974E+10 | 4755397.60 | 0.00 | 54224406.70 | 0.00 | 0.00 | 0.537242E+11 | 0.00 | 4.92 |
March | 0.154932E+10 | 0.00 | 0.00 | 66420228.02 | 0.00 | 0.00 | 0.616655E+11 | 0.00 | 4.88 |
April | 0.269463E+09 | 11048726.74 | 0.00 | 94896407.68 | 0.00 | 0.00 | 0.544358E+11 | 0.00 | 5.35 |
May | 0.122264E+09 | 0.00 | 0.00 | 0.105738E+09 | 0.00 | 0.00 | 0.565559E+11 | 0.00 | 5.55 |
June | 43893599.44 | 0.208679E+09 | 0.00 | 0.119646E+09 | 0.00 | 0.00 | 0.450612E+11 | 0.00 | 6.09 |
July | 4953536.92 | 0.264504E+10 | 0.00 | 0.113538E+09 | 0.00 | 0.00 | 0.309231E+11 | 0.00 | 6.16 |
August | 7570352.55 | 0.317469E+10 | 0.00 | 0.101946E+09 | 113325.98 | 0.00 | 0.273376E+11 | 0.00 | 6.09 |
September | 99473772.24 | 0.118593E+10 | 0.00 | 98077770.64 | 12401989.66 | 0.00 | 0.375101E+11 | 0.00 | 5.86 |
October | 0.278961E+09 | 0.209127E+10 | 0.00 | 83190213.33 | 6904229.34 | 0.00 | 0.385265E+11 | 0.00 | 5.63 |
November | 0.854265E+09 | 6137122.67 | 0.00 | 62986847.77 | 0.00 | 0.00 | 0.548867E+11 | 0.00 | 5.05 |
December | 0.160082E+10 | 9075654.50 | 0.00 | 56584201.48 | 1140474.78 | 0.00 | 0.575886E+11 | 0.00 | 4.88 |
Annual Sum or Average | 0.861569E+10 | 0.935615E+10 | 0.00 | 0.101287E+10 | 20560019.77 | 0.00 | 0.576154E+12 | 0.00 | 5.45 |
Minimum of Months | 4953536.92 | 0.00 | 0.00 | 54224406.70 | 0.00 | 0.00 | 0.273376E+11 | 0.00 | 4.88 |
Maximum of Months | 0.249496E+10 | 0.317469E+10 | 0.00 | 0.119646E+09 | 12401989.66 | 0.00 | 0.616655E+11 | 0.00 | 6.16 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.119314E+09 | 0.00 | 0.00 | 0.726770E+11 | 0.00 | 20.37 |
February | 0.00 | 0.00 | 0.00 | 0.106862E+09 | 0.00 | 0.00 | 0.693535E+11 | 0.00 | 21.20 |
March | 0.00 | 0.00 | 0.00 | 0.120517E+09 | 0.00 | 0.00 | 0.749627E+11 | 0.00 | 20.22 |
April | 0.00 | 1466131.64 | 0.00 | 0.143471E+09 | 0.00 | 0.00 | 0.646766E+11 | 0.00 | 23.15 |
May | 0.00 | 0.00 | 0.00 | 0.150655E+09 | 0.00 | 0.00 | 0.673156E+11 | 0.00 | 24.22 |
June | 0.00 | 0.217841E+09 | 0.00 | 0.155645E+09 | 0.00 | 0.00 | 0.527713E+11 | 0.00 | 26.60 |
July | 0.00 | 0.168751E+10 | 0.00 | 0.139353E+09 | 0.00 | 0.00 | 0.377613E+11 | 0.00 | 25.78 |
August | 0.00 | 0.223438E+10 | 0.00 | 0.124646E+09 | 0.00 | 0.00 | 0.347181E+11 | 0.00 | 25.83 |
September | 0.00 | 0.441930E+09 | 0.00 | 0.143851E+09 | 0.00 | 0.00 | 0.474746E+11 | 0.00 | 26.35 |
October | 0.00 | 0.698403E+09 | 0.00 | 0.139334E+09 | 0.00 | 0.00 | 0.479753E+11 | 0.00 | 24.40 |
November | 0.00 | 0.00 | 0.00 | 0.120692E+09 | 0.00 | 0.00 | 0.705820E+11 | 0.00 | 22.15 |
December | 0.00 | 0.00 | 0.00 | 0.121858E+09 | 0.00 | 0.00 | 0.724757E+11 | 0.00 | 20.66 |
Annual Sum or Average | 0.00 | 0.528153E+10 | 0.00 | 0.158620E+10 | 0.00 | 0.00 | 0.712744E+12 | 0.00 | 23.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.106862E+09 | 0.00 | 0.00 | 0.347181E+11 | 0.00 | 20.22 |
Maximum of Months | 0.00 | 0.223438E+10 | 0.00 | 0.155645E+09 | 0.00 | 0.00 | 0.749627E+11 | 0.00 | 26.60 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 18499.06 | 0.00 | 8567785.47 | 0.00 | 0.00 | 0.487157E+09 | 0.00 | 0.03 |
February | 0.00 | 152597.81 | 0.00 | 6942132.07 | 0.00 | 0.00 | 0.416851E+09 | 0.00 | 0.03 |
March | 0.00 | 6283250.67 | 0.00 | 7505868.93 | 0.00 | 0.00 | 0.369351E+09 | 0.00 | 0.03 |
April | 0.00 | 17656332.85 | 0.00 | 13953429.03 | 0.00 | 0.00 | 0.429052E+09 | 0.00 | 0.05 |
May | 0.00 | 4614542.40 | 0.00 | 16030262.43 | 0.00 | 0.00 | 0.462708E+09 | 0.00 | 0.05 |
June | 0.00 | 94569959.35 | 0.00 | 15004179.56 | 0.00 | 0.00 | 0.311544E+09 | 0.00 | 0.07 |
July | 0.00 | 0.386316E+09 | 0.00 | 10213177.65 | 0.00 | 0.00 | 0.154052E+09 | 0.00 | 0.09 |
August | 0.00 | 0.488324E+09 | 0.00 | 7738111.17 | 0.00 | 0.00 | 0.119045E+09 | 0.00 | 0.09 |
September | 0.00 | 0.160941E+09 | 0.00 | 11701032.10 | 0.00 | 0.00 | 0.239553E+09 | 0.00 | 0.07 |
October | 0.00 | 0.143780E+09 | 0.00 | 13145278.82 | 0.00 | 0.00 | 0.383975E+09 | 0.00 | 0.07 |
November | 0.00 | 796002.78 | 0.00 | 10434440.35 | 0.00 | 0.00 | 0.537710E+09 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 | 9595094.39 | 0.00 | 0.00 | 0.572786E+09 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.130345E+10 | 0.00 | 0.130831E+09 | 0.00 | 0.00 | 0.448378E+10 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6942132.07 | 0.00 | 0.00 | 0.119045E+09 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.488324E+09 | 0.00 | 16030262.43 | 0.00 | 0.00 | 0.572786E+09 | 0.00 | 0.09 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:25:07
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.255667E+12 | 0.104853E+11 | 0.123488E+12 | 0.401171E+12 | 0.251840E+12 |
February | 0.312929E+12 | 0.935887E+10 | 0.113857E+12 | 0.366906E+12 | 0.168345E+12 |
March | 0.429812E+12 | 0.105969E+11 | 0.130181E+12 | 0.402823E+12 | 0.187284E+12 |
April | 0.567386E+12 | 0.775807E+10 | 0.952368E+11 | 0.360268E+12 | 0.286154E+12 |
May | 0.600057E+12 | 0.793528E+10 | 0.949250E+11 | 0.372474E+12 | 0.279618E+12 |
June | 0.592669E+12 | 0.512986E+10 | 0.634724E+11 | 0.298970E+12 | 0.429357E+12 |
July | 0.632156E+12 | 0.217117E+10 | 0.291037E+11 | 0.202238E+12 | 0.686588E+12 |
August | 0.575389E+12 | 0.157444E+10 | 0.223994E+11 | 0.179618E+12 | 0.744980E+12 |
September | 0.458687E+12 | 0.403521E+10 | 0.535148E+11 | 0.260530E+12 | 0.554166E+12 |
October | 0.324704E+12 | 0.496444E+10 | 0.564312E+11 | 0.261097E+12 | 0.589778E+12 |
November | 0.273766E+12 | 0.918597E+10 | 0.108146E+12 | 0.385825E+12 | 0.258897E+12 |
December | 0.231827E+12 | 0.105157E+11 | 0.121476E+12 | 0.396009E+12 | 0.264892E+12 |
Annual Sum or Average | 0.525505E+13 | 0.837113E+11 | 0.101223E+13 | 0.388793E+13 | 0.470190E+13 |
Minimum of Months | 0.231827E+12 | 0.157444E+10 | 0.223994E+11 | 0.179618E+12 | 0.168345E+12 |
Maximum of Months | 0.632156E+12 | 0.105969E+11 | 0.130181E+12 | 0.402823E+12 | 0.744980E+12 |